| D896 Automatic Vent Damper   PRODUCT DATA   FEATURES   • 4-wire plug receptacle.   • Includes wiring harness on select models to fit plug   receptacle onto S86/S8600/S8610/S8620 /L7148/L8148   or Penn Baso G60 or G66.   • • For use only on atmospheric type gas-fired furnaces   and boilers equipped with draft hoods.   Applicable to direct spark ignition (DSI), intermittent   pilot (IP), hot surface ignition (HSI), and standing pilot   systems.   • • Ambient temperature range 32°F (0°C) to 150°F (65°C).   Requires dual automatic combination gas control   valve or two separate single function main gas valves.   • Interlock switch provides safe operation; burner fires   only with damper in open position.   GENERAL   • • • 24V operation for easy, low-cost wiring.   Visual indicator shows damper position.   D896 Automatic Vent Dampers are used with atmospheric   type, gas-fired equipment to reduce home heating losses by   closing off the vent between heat cycles.   30-second nominal closing time for optimum energy   savings.   • • Quiet motor and relay.   Wiring harnesses available separately to fit a variety of   applications.   Contents   General ...............................................................................   Features ..............................................................................   Specifications ......................................................................   Ordering Information ...........................................................   Application...........................................................................   Installation ...........................................................................   Settings ...............................................................................   Operation and Checkout .....................................................   Troubleshooting ...................................................................   Instructions to the Homeowner ...........................................   1 1 2 2 3 4 7 7 8 9 ANSI Standards .................................................................. 10   ® U.S. Registered Trademark   Copyright © 1997 Honeywell Inc.   68-0186   • All Rights Reserved   Download from Www.Somanuals.com. All Manuals Search And Download.   D896 AUTOMATIC VENT DAMPER   NOTE: A minimum of a 30 VA transformer must be used   when D896 is installed with S86/S8600/S8610/   S8620.   Approvals:   American Gas Association Certified:   Certificate No. U-66-2A1.   Canadian Gas Association Design Certified:   1029AVD-9081.   Electrical Connections:   Four-wire plug receptacle.   Replacement Parts:   Thermostat Anticipator Setting:   0.13A.   Damper Actuator is field replaceable without removing the   damper assembly from the stack.   197516A Wiring Harness is a 4-wire cable, 8 feet (2.5   meters) long, with D896 mating plug on one end and   mating plug for S86/S8600/S8610/S8620 or Penn Baso   G60 or G66 on the other. An outlet box connector is on   each end.   Operating Times:   Approximate Damper Opening Time: 30 seconds.   Approximate Damper Closing Time: 30 seconds.   Temperature Ratings:   Minimum Ambient: 32°F (0°C).   Maximum Ambient: 150°F (66°C).   Maximum Furnace Stack: 575°F (302°C).   Shipping: -20°F to +120°F (-29°C to +49°C).   APPLICATION   The D896 Automatic Vent Damper is a 24 Vac, motorized   stack damper. The damper closes off the furnace or boiler   stack during the heating off-cycle. Use the D896 only on   Underwriters Laboratories Inc. listed and American Gas   Association design certified atmospheric type, gas-fired   furnaces and boilers. The furnaces or boilers must be   equipped with a draft hood that has an outlet area no larger   than the damper inlet area. Do not use with oil-fired furnace   or boiler, power burner, or direct vent furnace or boiler.   Mounting: See Fig. 2.   Vertical Stack: Any orientation.   Horizontal Stack: The damper actuator must be on the left   or right side of the vent.   IMPORTANT   Do not mount the vent damper with the actuator   above or below the vent.   Dimensions:   See Fig. 1.   DIM. F   DIM. E   DIA   A DIA   C DIA   B DIM.   G 1 4 1 (32)   DIM.   H 3 4 2 (70)   9 16   DIM.   D 4 (116)   7 8 7/8 DIA. STD. KNOCKOUT (3)   (ONE, OPPOSITE SIDE)   3 (98)   DIA. A   in. (mm)   DIA. B   in. (mm)   DIA. C   in. (mm)   DIM. D   in. (mm)   DIM. E   in. (mm)   DIM. F   in. (mm)   DIM. G   in. (mm)   DIM. H   in. (mm)   BODY SIZE   (REF)   4 (102)   5 (127)   6 (152)   7 (178)   8 (203)   9 (229)   10 (254)   11 (279)   12 (305)   4 1/16 (103)   5 1/16 (129)   6 1/16 (154)   7 1/16 (179)   8 1/16 (205)   9 1/16 (230)   1 9/16 (40)   1 9/16 (40)   1 9/16 (40)   3 3/16 (81)   3 3/16 (81)   3 3/16 (81)   4 1/2 (114)   4 1/2 (114)   4 1/2 (114)   7 1/2 (191)   7 1/2 (191)   7 1/2 (191)   11 1/2 (292)   11 1/2 (292)   11 1/2 (292)   6 (152)   6 (152)   6 (152)   9 (229)   9 (229)   9 (229)   13 (330)   13 (330)   13 (330)   6 3/4 (171)   7 1/4 (184)   8 7/8 (225)   9 7/8 (251)   4 (102)   5 (127)   6 (152)   7 (178)   8 (203)   9 (229)   10 (254)   11 (279)   12 (305)   3 15/16 (100)   4 15/16 (125)   5 15/16 (151)   6 15/16 (176)   7 15/16 (202)   8 15/16 (224)   9 15/16 (252)   10 15/16 (278)   11 15/16 (303)   7 3/4 (197) 10 7/8 (276)   8 1/4 (209) 11 7/8 (301)   8 3/4 (222) 12 7/8 (327)   9 1/4 (235) 13 7/8 (352)   9 3/4 (248) 14 7/8 (378)   10 1/4 (260) 15 7/8 (403)   10 3/4 (274) 16 7/8 (428)   M11381   10 1/16 (256) 5 3/16 (132)   11 1/16 (281) 5 3/16 (132)   12 1/16 (306) 5 3/16 (132)   Fig. 1. Installation dimensions in in. (mm).   3 68-0186   Download from Www.Somanuals.com. All Manuals Search And Download.   D896 AUTOMATIC VENT DAMPER   IMPORTANT   Location   1. The atmospheric draft hood outlet area must be   smaller or equal to the inlet area of the damper   assembly.   2. If a second gas valve needs to be installed, refer   to the gas valve manufacturer instructions for the   procedure.   3. Using a dual automatic valve combination gas   control or two separate gas valves is required   with the D896.   4. Do not use with L8148 or L8124 with manual/   automatic switch because the switch can override   the safety interlock in the system wiring and   cause a hazardous condition.   The D896 must be installed after the furnace or boiler draft   hood. See Fig. 2. Make sure the D896 Motor Actuator is   readily visible and accessible. The damper must be located   where air can freely circulate around it.   WARNING: DO NOT INSTALL THE   VENT DAMPER WITHIN 6 IN. (152 mm)   OF COMBUSTIBLE MATERIAL.   NO   D896 MOTOR   ACTUATOR   VENT PIPE   CURVE   2 5. Do not install on an appliance equipped with an   automatic valve with a manual opener unless the   manual opener is rendered inoperative or the   automatic valve is replaced with an automatic   valve without a manual opener.   DRAFT   HOOD   1 6. On retrofit applications, installation identification   label (provided) must be filled out by installer and   applied to outside of cover.   CHIMNEY   3 INSTALLATION   When Installing this Product…   FURNACE OR BOILER   1. Read these instructions carefully. Failure to follow them   could cause a hazardous condition.   WATER HEATER   1 INSTALL THE VENT DAMPER TO SERVICE ONLY THE SINGLE   APPLIANCE FOR WHICH IT IS INTENDED. IF IMPROPERLY   INSTALLED, A HAZARDOUS CONDITION, SUCH AS AN EXPLOSION   OR CARBON MONOXIDE POISONING, COULD RESULT.   2. Check the ratings given in the instructions and on the   product to make sure the product is suitable for your   application.   3. Installer must be a trained experienced service   technician. The D896 must be installed in compliance   with local codes or the Natural Gas Installation Code   CAN/CGA-B149.1-B149.1-M91 and CSA C22.2 #3   Electrical Features of Fuel Burning Equipment, or the   National Fuel Gas Code (ANSI Z223.1—NFPA 54) and   the National Electrical Codes (ANSI C1—NFPA70). Use   the ANSI Standard Z21.66-1994 included at the end of   this specification during installation.   DO NOT INSTALL THE VENT DAMPER ON VENT PIPE CURVE.   2 3 DO NOT RUN WIRES NEAR HIGH TEMPERATURE SURFACES.   USE STAND-OFF BRACKETS IF NECESSARY.   M11370   Fig. 2. D896 location.   Do not install the D896:   — Where the stack temperature is higher than 575°F (284°C).   — Where the ambient temperature is higher than 150°F   (66°C).   — In small or enclosed spaces where temperature can   exceed 150° F (66°C). See WARNING following.   — On the vent pipe curve. See Fig. 2.   NOTE: In Canada, the damper is not certified for   retrofit application. Certification for the   suitability of the damper and appliance   combination must be determined by the   Canadian Gas Association.   WARNING   4. Install only on an appliance connected to a factory built   chimney or vent that complies with a recognized   standard, or to a masonry or concrete chimney that is   lined with a material acceptable to local code.   5. After installation is complete, check out product   operation as provided in the Checkout section. See   Exhibits A and B at the end of this specification.   Severe illness or death possible. Prevent   explosion or carbon monoxide poisoning.   Overheating can cause premature device failure. Be   sure the D896 is used to control only one appliance.   Mounting   The damper must be mounted as close as possible to the   draft hood without modifying the draft hood. The D896 can be   mounted vertically or horizontally. When vertically mounting   the vent damper, the motor actuator can be in any position.   See Fig. 3.   CAUTION   Can cause electrical shock or equipment damage.   1. Disconnect power supply.   2. Do not install within 6 in. (152 mm) of combustible   materials.   3. Do not negate the action of any existing safety or   operational control.   Horizontal mounting requires the actuator to be located within   45 degrees directly above or directly below the horizontal   diameter of the stack pipe. See Fig. 2 and 3.   68-0186   4 Download from Www.Somanuals.com. All Manuals Search And Download.   D896 AUTOMATIC VENT DAMPER   HORIZONTAL VENT INSTALLATION   D896   NO   NO   YES   YES   TO CHIMNEY   FLOW   FROM FURNACE   OR BOILER   INSTALL VENT DAMPER   ONLY WITH ACTUATOR   TO SIDES OF VENT.   DO NOT MOUNT VENT   DAMPER WITH   ACTUATOR ABOVE   OR BELOW THE VENT.   VERTICAL VENT INSTALLATION   TO   CHIMNEY   MOTOR   ACTUATOR   INSTALL VENT   DAMPER WITH   ACTUATOR IN   ANY POSITION.   D896   FLOW   DAMPER   BLADE PLUG   DAMPER   BLADE   FROM FURNACE   OR BOILER   M11371   FOR DSI AND IP INSTALLATIONS ONLY – PLACE PLUG ON HOLE:   HOLD DAMPER BLADE AND PUSH DOWN ON PLUG.   M9675   Fig. 3. Installing D896 Vent Damper.   Fig. 4. Installing damper blade plug.   IMPORTANT   Never mount the vent damper with the motor   actuator above or below the vent.   Wiring   WARNING   Do not install the damper blade plug if the vent damper is   installed on a system with a continuous or standing pilot. The   hole provides the minimum vent area required by code for   safe operation.   Severe illness or death possible. Prevent   explosion or carbon monoxide poisoning.   1. Use dual automatic valve combination gas   controls or two separate single function main gas   valves with the D896.   2. Do not use the D896 with an L8148 or L8124 with   a manual/automatic switch because the switch   can override the safety interlocks in the system   wiring and cause carbon monoxide buildup.   Use the damper blade plug when the damper is installed on a   system with either an intermittent pilot or direct ignition. The   plug will increase system efficiency. See Fig. 4.   To install the D896:   1. Push the female end of the vent damper over the   section of vent pipe coming from the furnace or boiler,   but after the draft hood. Push the section of the vent   pipe coming from the chimney over the male end of the   vent damper.   2. Secure the vent damper to the vent pipe with 1/2 in. (12   mm) sheet metal screws. Use only the holes provided.   3. Visually inspect the venting system for proper pitch.   Pitch must comply with local codes or ANSI Z223.1—   NFPA54.   CAUTION   1. Remove the shorting plug on the S8600, S8610   or L8148E before attaching the wiring harness.   2. Do not permit device wiring to contact high   temperature surfaces.   3. Label all wires prior to disconnecting when   servicing controls. Wiring errors can cause   explosion or carbon monoxide buildup.   Important   To install an additional gas valve:   Do not operate the system with the D896 unplugged.   Once the system has operated with the D896   plugged into the S8600, S8610 or L8148E, the   control module will not operate.   1. Shut off the gas and electricity to the gas burner. (Use   the manual shutoff valve in the supply line to the   appliance.)   2. Locate a position in the supply line between the   appliance automatic gas valve and the burner.   3. At the determined position, install an approved   appropriately-sized, single-function automatic gas valve   downstream from the existing automatic gas valve.   Follow the valve manufacturer instructions for flow   direction and position.   D896 to L8148E, S8600F,H,M; S8610F,H   Use the wiring harness included with the D896 to wire it   according to the following instructions:   1. Connect the molex plug to the D896 Harness Cable   Connector. See Fig. 5.   4. Restore the gas line supply and conduct a leak test on   the gas piping and control system downstream from the   appliance shutoff valve.   2. Use Fig. 6 and 7 to connect the other end of the   harness to the furnace, boiler or control module.   3. Cycle system through at least two appliance operations.   5 68-0186   Download from Www.Somanuals.com. All Manuals Search And Download.   D896 AUTOMATIC VENT DAMPER   D896   Replacing D80B, D892 or Competitive   Control with D896   SERVICE   SWITCH   IGNITION GAS   PWR LED   NORM   SERV   WARNING   Bodily harm and/or death possible. Prevent   unsupervised gas flow.   CALL FOR   HEAT LED   Improper wiring (device malfunction) of the D80B,   D892, D896 or competitive devices can cause   unsupervised gas flow.   HARNESS   CABLE   CONNECTOR   1 A wiring harness is included with most D896 models. Use the   harness to wire the D896 according to the furnace or boiler   manufacturer wiring instructions, if available; otherwise, follow   these instructions. If field wiring is required, see appliance   manufacturer instructions or see Fig. 8 for a typical wiring   example. See Table 1 for competitive wiring cross reference.   Always cycle system through at least two appliance   operations.   Table 1. Wiring Cross Reference.   S3 SWITCH   RELAY 1K   1 USE STANDARD SCREWDRIVER TO MANUALLY OPEN AND   CLOSE VENT DAMPER. PLACE SCREWDRIVER IN SLOTTED   KNOB AND ROTATE COUNTERCLOCKWISE UNTIL   Honeywell   D892/D896   Wires   Honeywell   Johnson   EFFIKAL   M11373   D80B Wires Q35 Wires RVG Wires   BOTH LEDS TURN ON.   Fig. 5. D896 with cover off.   Yellow   Orange   Blue   Orange   Blue and Red   Black   Green   White   Red   1 2 3 4 Black   Yellow   Black   24 Vac   THERMOSTAT   D896   LED 2   L8148E1166/L7148   WIRING   HARNESS   4 4 4 T W Z TV   1K   R1, R2, R3   250 OHMS   K1   MOTOR   6 2 2 NORMAL   S4   5 N.O.   S3   SERVICE   3 FUSE   N.C.   C N.O.   2 N.C.   S1   C K1   1 3 N.O.   N.C.   5 S2   C2   L2   C1   L1   C LED 1   3 1 1K1   6-PRONG FEMALE MOLEX   RECEPTACLE IN L8148E   AND 5-PRONG MALE   POLARIZED 4-PRONG MALE MOLEX PLUG AND   4-PRONG FEMALE MATING PLUG ON CABLE   B2   B1   CIRCULATOR   MOLEX PLUG ON CABLE   DAMPER OPEN   DAMPER CLOSED   SWITCHES AS SHOWN: S1,S2,S3   L1   (HOT)   L2   1 2 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD   PROTECTION AS REQUIRED.   1 AFTER D896 VENT DAMPER IS PLUGGED TO L8148E1166, FUSE   BLOWS WHEN THERMOSTAT FIRST CLOSES. AFTER FUSE BLOWS,   L8148E1166 OPERATES ONLY WHEN VENT DAMPER IS CONNECTED.   24V GND   24V   3 4 5 LED 1 LIGHTS WHEN DAMPER IS OPEN.   LED 2 LIGHTS WITH CALL FOR HEAT.   SERVICE SWITCH. THE NORMAL SWITCH SETTING IS NORM. IF THE   SWITCH IS MOVED TO THE SERV POSITION, THE DAMPER REMAINS OPEN.   6 NO W,Z TERMINALS ON L7148.   M11382   Fig. 6. Wiring diagram for D896 connection to L8148E1166 /L7148 using wiring harness with two Molex plugs.   68-0186   6 Download from Www.Somanuals.com. All Manuals Search And Download.   D896 AUTOMATIC VENT DAMPER   S8600F, H, M; S8610F,H   1 VENT   2 GND   (BURNER)   24V   GND   DAMPER   PLUG   MV MV/PV PV   24V TH-W   SENSE   SPARK   WIRING   HARNESS   1 2 POWER SUPPLY. PROVIDE DISCONNECT MEANS   AND OVERLOAD PROTECTION AS REQUIRED.   D896   VENT   DAMPER   REMOVE PLUG ONLY IF USING VENT DAMPER. FUSE   BLOWS ON STARTUP WHEN PLUG IS REMOVED;   THEN MODULE OPERATES ONLY WHEN VENT   DAMPER IS CONNECTED.   M11375   Fig. 7. Wiring diagram for D896 connection to S8600/S8610 using wiring harness with two Molex plugs.   1. When replacing a D80B or D892 with a D896, use the   included wire nuts to connect the D80B or D892 cable   to the D896 cable. See Fig. 9.   furnace or boiler burner lights. When the heating cycle ends,   both LEDs turn off, the burner turns off and the damper   automatically closes. Heating system efficiency is increased   because the closed damper reduces the loss of residual   appliance heat and heated room air through the draft diverter.   a. Remove the black wire from the D80B (or D892)   terminal 1.   b. Use a wire nut to connect the D80B (or D892)   black wire to the D896 blue wire.   c. Remove the orange wire from the D80B (or   D892) terminal 2.   D896   4 3 2 1 d. Wire nut the D80B (or D892) orange wire to the   D896 yellow wire.   e. Remove the red wire from the D80B (or D892)   terminal 3 and the blue wire from the D80B (or   D892) terminal 5.   2 WIRING   HARNESS   f. Wire nut the D80B (or D892) red and blue wires   to the D896 orange wire.   g. Remove the yellow wire from the D80B (or D892)   terminal 4.   h. Wire nut the D80B (or D892) yellow wire to the   D896 black wire.   THERMOSTAT   LIMIT   CONTROLLER   3 LIMIT   CONTROLLER   1 L1   (HOT)   2. Cycle the system through at least two appliance   operations.   L2   TRANSFORMER   DUAL AUTOMATIC   VALVE COMBINATION   GAS CONTROL   1 2 TH TH   Snap-Tite™ Connector Release   To release the D896 cable from the knockout hole when   secured with a Snap-Tite™ Box Connector (Fig.10), slip a   screwdriver under the tab and twist.   1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD   PROTECTION AS REQUIRED.   2 3 CONNECT COLORS OF WIRING HARNESS AS SHOWN.   M11372   ALTERNATE LIMIT CONTROLLER HOOKUP.   SETTINGS   Fig. 8. Wiring diagram for D896 connection to continuous   pilot system using wiring harness with one Molex plug.   The service switch operates in both normal (NORM ) or   service (SERV) modes. See Fig. 5.   NORM—D896 opens on a call for heat and closes at the end   of the heating cycle.   SERV—D896 remains open at the end of a call for heat. The   switch must be in the SERVICE position before manually   opening the damper.   D80B   CABLE   D892/D896   CABLE   YELLOW   ORANGE   YELLOW   BLACK   BLUE   ORANGE   BLUE   RED   BLACK   OPERATION AND CHECKOUT   D80B   CONNECTOR   M11383   Operation   On a call for heat, the CALL FOR HEAT LED on the actuator   lights and the damper begins to open. When the damper is   fully open, the IGNITION GAS PWR LED lights and the   Fig. 9. Connecting D80B, D892 Cable to D896 Cable.   7 68-0186   Download from Www.Somanuals.com. All Manuals Search And Download.   D896 AUTOMATIC VENT DAMPER   6. Cycle the heating system at least three times using the   thermostat or controller to assure the system is   operating safely.   Cooling   CAUTION   Damage to air conditioner condenser possible.   Do not operate cooling if outdoor temperature is below   50°F (10°C).   1. Set the thermostat or controller to COOL. Move the   setpoint to 10°F (6°C) below the room temperature.   2. Make sure the cooling system operates.   3. Check that the D896 is in the closed position. See Fig.   11.   4. Return the thermostat or controller to the desired   settings.   NOTE TO INSTALLER: Explain to the homeowner that a   yearly inspection by a trained, experienced service   technician is necessary for safe, efficient operation   of the vent damper and heating system. The   homeowner should check for deterioration from   corrosion or other sources between service   technician calls.   Fig. 10. Snap-Tite™ Box Connector release.   Checkout   Heating   1. Turn on the power supply.   2. If using a thermostat, set the heat anticipator at 0.13A.   3. Set the thermostat or controller to 10°F (6°C) above the   room temperature to call for heat.   4. Check that the D896 CALL FOR HEAT and IGNITION   GAS PWR LEDs light and that the damper opens   before the gas valve opens and the pilot or main burner   ignites. See Fig. 11.   TROUBLESHOOTING   WARNING   Fire or explosion hazard can cause property   damage, severe injury or death.   NOTE: If a boiler gas control is sequenced by the   Aquastat® Controller, make sure that the   damper opens prior to the opening of the gas   control.   Explosion or carbon monoxide poisoning   possible.   Never apply a jumper across or short gas control   terminals or wires because this can force the D896 to   remain closed and cause an explosion.   5. Turn the thermostat or controller 10°F (6°C) below the   room temperature. Make sure the LEDs turn off and the   D896 closes.   THE AIR DUCT IS CLOSED WHEN THE   INDICATOR POINTS PERPENDICULAR TO   THE DIRECTION OF THE AIR DUCT   THE AIR DUCT IS OPEN WHEN   THE INDICATOR POINTS IN THE   DIRECTION OF THE AIR DUCT   M3431   Fig. 11. Determining damper position.   68-0186   8 Download from Www.Somanuals.com. All Manuals Search And Download.   D896 AUTOMATIC VENT DAMPER   NOTE: If there is a power failure, the damper remains   exactly where it is at the moment of failure (open,   closed or any position in between). When power is   restored, the damper opens if the thermostat is   calling for heat or closes if the thermostat is not   calling for heat.   heating contractor for repairs. The name of the original   installer of your vent damper is on the installation label.   Check vent damper operation as follows:   1. Turn the thermostat or controller below the room   temperature to turn off the furnace or boiler. Assure the   vent damper position indicator points to the closed   position. Refer to Fig. 11.   If system fails to start, set the thermostat 10°F (6°C) below   the room temperature for approximately three minutes, and   refer to Table 2 to troubleshoot the system.   2. Turn the thermostat or controller above the room   temperature to call for heat. Assure the vent damper   position indicator points to the open position. Refer to   Fig. 11.   3. Turn the thermostat or controller below the room   temperature again. Assure the vent damper position   indicator returns to the closed position.   4. If the system has central air conditioning, set the   thermostat or controller to COOL and turn it below the   room temperature to call for cooling. Assure the cooling   system operates with the vent damper in the closed   position.   INSTRUCTIONS TO THE HOMEOWNER   A yearly inspection by a trained, experienced service   technician is necessary for safe, efficient operation of the vent   damper and all flue product-carrying areas of the appliance.   The homeowner should check for deterioration from corrosion   and other sources between service technician calls. If   corrosion or other deterioration is noticed, contact your   5. Return the thermostat or controller to the desired   settings.   Table 2.Troubleshooting.   Possible Cause   Thermostat Setting   Symptom   Action   Set thermostat 10°F   above room temperature   to call for heat.   No response from D896.   Incorrect wiring or blown   fuse.   • • Check the circuit breaker or fuse and,   if necessary, reset or replace.   Check the transformer and limit   control.   • • Check for 24 Vac across resistor R1.   Check for 24 Vac at the S8600, S8610   and L8148E.   • Check wiring and cable connections.   24 Vac is present, damper   is open, CALL FOR HEAT   LED is on, IGNITION GAS   PWR LED is on, but no   heat is produced.   Appliance ignition   system malfunction.   Check appliance ignition system.   24 Vac is present, damper   is open, CALL FOR HEAT   LED is on, IGNITION GAS   PWR LED is off, no heat is   produced.   D896 malfunction.   Replace the D896.   24 Vac is present, damper   Incorrect wiring or D896 Check all wiring and cable connections.   is closed, CALL FOR HEAT malfunction.   LED is off and no heat is   produced.   • If 24 Vac is present across resistor   R1, replace the D896.   • If 24 Vac is not present across R1,   check the appliance ignition   system.   24 Vac is present, damper   is closed and CALL FOR   HEAT LED is off.   Incorrect wiring or D896 Check all wiring and cable connections.   malfunction.   • If 24 Vac is present across resistor   R1, replace the D896.   • If 24 Vac is not present across R1,   check the appliance ignition   system.   24 Vac is present, damper   is closed and CALL FOR   HEAT LED is on.   Incorrect wiring or D896 If wiring is correct and the damper does   malfunction.   not fully open after approximately 30   seconds, replace the D896.   Set thermostat 10°F   below the room   temperature to end the   call for heat.   LEDs turn off, but damper   does not close in   approximately 30 seconds. malfunction.   Incorrect service switch   setting or D896   • Check if the service switch is in the   normal (NORM ) position. If not, move   the switch to the NORM position.   If service switch is in the NORM   position, replace the D896.   • 9 Download from Www.Somanuals.com. All Manuals Search And Download.   68-0186   D896 AUTOMATIC VENT DAMPER   ANSI STANDARDS   EXHIBIT A   Procedure For Safety Inspection of an Existing Appliance Installation   The following procedure is intended as a guide to aid in   determining that an appliance is properly installed and is in a   safe condition for continuing use.   10. Determine that the pilot(s), when provided, is burning   properly and that main burner ignition is satisfactory by   interrupting and reestablishing the electrical supply to   the appliance in any convenient manner.   This procedure is predicated on central furnace, boiler and   water heater installations, and it should be recognized that   generalized procedures cannot anticipate all situations.   Accordingly, in some cases deviation from this procedure may   be necessary to determine safe operation of the equipment:   a. This procedure shall be performed prior to installation   of the automatic vent damper device.   If the appliance is equipped with a continuous pilot(s), test the   pilot safety device(s) to determine if it is operating properly by   extinguishing the pilot(s) when the main burner(s) is off and   determining, after 3 minutes, that the main burner gas does   not flow upon a call for heat.   b. If it is determined there is a condition which could result   in unsafe operation, the appliance should be shut off   and the owner advised of the unsafe condition. Do not   install the automatic vent damper device until the   unsafe condition has been corrected.   If the appliance is not provided with a pilot(s), test for proper   operation of the ignition system in accordance with the   appliance manufacturer’s lighting and operating instructions.   11. (a) Visually determine that main burner gas is burning   properly; i.e., no floating, lifting or flashback. Adjust   the primary air shutter(s) as required.   (b) If the appliance is equipped with high and low   flame controlling or flame modulation, check for   proper main burner operation at low flame.   12. Test for spillage at the draft hood relief opening after 5   minutes of main burner operation. Use the flame of a   match or candle, or smoke from a cigarette, cigar or   pipe.   13. Turn on all other fuel-burning appliances within the   same room so they will operate at their full inputs.   Follow lighting instructions for each appliance.   14. Repeat Steps 11 and 12 on the appliance being   inspected.   15. Return doors, windows, exhaust fans, fireplace   dampers and any other fuel-gas burning appliances to   their previous conditions of use.   The following steps are to be followed in making the safety   inspection:   1. Conduct a gas leakage test of the appliance piping and   control system downstream of the shutoff valve in the   supply line to the appliance.   2. Visually inspect the venting system for proper size,   horizontal pitch and vent termination, and determine   there is no blockage or restriction, leakage, corrosion   and other deficiencies which could cause an unsafe   condition.   3. Determine that the chimney or vent is acceptable to the   authority having jurisdiction.   4. Shut off all gas to the appliance and shut off any other   fuel-gas burning appliance within the same room. Use   the shutoff valve in the supply line to each appliance.   5. Inspect burners and crossovers for blockage and   corrosion.   16. Applicable only to furnaces—Check both the limit   control and the fan control for proper operation. Limit   control operation can be checked by blocking the   circulating air inlet or temporarily disconnecting the   electrical supply to the blower motor and determining   that the limit control acts to shut off the main burner   gas.   6. Applicable only to furnaces—inspect heat exchanger for   cracks, openings or excessive corrosion.   7. Applicable only to boilers—inspect for evidence of water   or combustion product leaks.   8. Insofar as is practical, close all building doors and   windows and all doors between the space in which the   appliance is located and other spaces of the building.   Turn on clothes dryers. Turn on any exhaust fans, such   as range hoods and bathroom exhausts, so they will   operate at maximum speed. Do not operate a summer   exhaust fan. Close fireplace dampers. If, after   completing Steps 9 through 14, it is believed sufficient   combustion air is not available, refer to local codes, or   in the absence of local codes, to the National Fuel Gas   Code, ANSI Z223.1-1988 (NFPA 54), for guidance.   9. Place in operation the appliance being inspected.   Follow the lighting instructions. Adjust thermostat so   appliance will operate continuously.   17. Applicable only to boilers—   (a) Determine that the water pumps are in operating   condition.   (b) Test low water cutoffs, automatic feed controls,   pressure and temperature limit controls, and relief   valves in accordance with the manufacturer’s   recommendations to determine they are in   operating condition.   Exhibit A of ANSI Standard Z21.66-1994 for Electrically Operated Automatic Vent Damper Devices   for use with Gas-Fired Appliances.   68-0186   10   Download from Www.Somanuals.com. All Manuals Search And Download.   D896 AUTOMATIC VENT DAMPER   EXHIBIT B   Procedure for Installing Electrically Operated Automatic Vent Damper Devices on Existing Appliances   This procedure is intended as a guide to aid in safely   installing an electrically operated or mechanically actuated   automatic vent damper device on an existing appliance.   10. Insofar as is practical, close all building doors and   windows and all doors between the space in which the   appliance is located and other spaces of the building.   Turn on clothes dryers. Turn on any exhaust fans, such   as range hoods and bathroom exhausts, so they will   operate at maximum speed. Do not operate a summer   exhaust fan. Close fireplace dampers.   This procedure is based on the assumption that the history of   the specific appliance has been one of safe and satisfactory   operation.   11. Place appliance in operation. Follow the lighting   instructions. Adjust thermostat so appliance will operate   continuously.   12. Test for spillage at the draft hood relief opening after 5   minutes of main burner operation. Use the flame of a   match or candle, or smoke from a cigarette, cigar or   pipe.   13. (a) Visually determine that main burner gas is burning   properly; i.e., no floating, lifting or flashback. Adjust   the primary air shutter(s) as required.   This procedure is predicated on central furnace, boiler and   water heater installations, and it should be recognized that   generalized procedures cannot anticipate all situations.   Accordingly, in some cases deviation from this procedure may   be necessary to determine safe operation of the equipment.   The following steps are to be followed in making the   modifications:   1. Perform a safety inspection of the existing appliance   installation. See Exhibit A for the recommended   procedure for such a safety inspection.   2. Shut off all gas and electricity to the appliance. To shut   off gas use the shutoff valve in the supply line to the   appliance.   3. Install the automatic vent damper device in strict   accordance with the manufacturer’s installation   instructions. Make certain the device is not located in   that portion of the venting system which serves any   appliance other than the one for which the damper is   installed.   (b) If the appliance is equipped with high and low   flame controlling or flame modulation, check for   proper main burner operation at low flame.   14. Determine that the pilot(s), when provided, is burning   properly and that main burner ignition is satisfactory by   interrupting and reestablishing the electrical supply to   the appliance in any convenient manner.   If the appliance is equipped with a continuous pilot(s), test the   pilot safety device(s) to determine if it is operating properly by   extinguishing the pilot(s) when the main burner(s) is off and   determining, after 3 minutes, that the main burner gas does   not flow upon a call for heat.   4. Make certain wiring connections are tight and wires are   positioned and secured so they will not be able to   contact high temperature locations.   5. When an additional automatic valve has been   incorporated or an existing gas control replaced,   conduct a gas leakage test of the appliance piping and   control system downstream of the shutoff valve in the   supply line to the appliance.   If the appliance is not provided with a pilot(s), test for proper   operation of the ignition system in accordance with the   appliance manufacturer’s lighting and operating instructions.   15. Applicable only to furnaces—Check both the limit   control and the fan control for proper operation. Limit   control operation can be checked by blocking the   circulating air inlet or temporarily disconnecting the   electrical supply to the blower motor and determining   that the limit control acts to shut off the main burner   gas.   6. Visually inspect the modified venting system for proper   horizontal pitch.   7. Check that the damper and gas valve(s) are in the   correct operating sequence.   (a) The damper must be in the full open position   before the gas valve(s) opens.   (b) The damper must remain in the full open position   while the gas valve(s) is open.   (c) The gas valve(s) must be closed before damper   begins its return to the closed position.   (d) The damper shall remain in the closed position   during the off cycle of the appliance.   16. Applicable only to boilers—   (a) Determine that the water pumps are in operating   condition.   (b) Test low water cutoffs, automatic feed controls,   pressure and temperature limit controls, and relief   valves in accordance with the manufacturer’s   recommendations to determine they are in   operating condition.   8. Determine the amperage draw of the gas control circuit   and damper device.   (a) Check appliance transformer for adequate   capacity.   17. Label the damper device (see 1.7.5) with information as   to:   (b) Check heat anticipator in comfort thermostat to   determine if it is properly adjusted.   9. Sequence the appliance through at least three normal   operating cycles.   (a) Name of qualified agency responsible for damper   installation.   (b) Date of installation.   Exhibit B of ANSI Standard Z21.66-1994 for Electrically Operated Automatic Vent Damper Device   for use with Gas-Fired Appliances.   11   68-0186   Download from Www.Somanuals.com. All Manuals Search And Download.   Home and Building Control   Honeywell Inc.   Honeywell Plaza   P.O. Box 524   Minneapolis MN 55408-0524   Home and Building Control   Honeywell Limited-Honeywell Limitée   155 Gordon Baker Road   North York, Ontario   Honeywell Asia Pacific Inc.   Room 3213-3225   Sun Hung Kai Centre   No. 30 Harbour Road   Wanchai   M2H 2C9   Hong Kong   Honeywell Europe S.A.   3 Avenue du Bourget   Honeywell Latin American Division   Miami Lakes Headquarters   B-1140 Brussels Belgium   14505 Commerce Way Suite 500   Miami Lakes FL 33016   Helping You Control Your World®   68-0186 J.S. 3-97 Printed in U.S.A.   customer.honeywell.com   Download from Www.Somanuals.com. All Manuals Search And Download.   |