| Installation & Operation Manual   Central Air Conditioner   Capacity 1.5 to 5 Tons   Models: HC1891VAR HC2491VAR   HC3091VAR HC3691VAR   HC4291VAR HC4891VAR   HC6091VAR   The information contained in this booklet is subject to change without notice.   TABLE OF CONTENT   1.Introduction ---------------------------------------------------------------------------------------   2.Nomenclature for Model Number -------------------------------------------------------------   3.Specification -------------------------------------------------------------------------------------   4.Unit Inspection -----------------------------------------------------------------------------------   5.Equipment Protection From Environment ----------------------------------------------------   6.Installation ----------------------------------------------------------------------------------------   6.1. General ---------------------------------------------------------------------------------------   6.2.Unit clearances ------------------------------------------------------------------------------   6.3.Refrigerant piping ---------------------------------------------------------------------------   6.4.Electrical wiring -----------------------------------------------------------------------------   7.System Startup -----------------------------------------------------------------------------------   1 1 1 3 3 3 3 4 4 8 9 8.Operation ----------------------------------------------------------------------------------------   9.Miscellaneous -----------------------------------------------------------------------------------   9.1.Replacement parts --------------------------------------------------------------------------   9.2.Troubleshooting guide ---------------------------------------------------------------------   9.3.Wiring diagram -----------------------------------------------------------------------------   10   10   10   10   10   1.INTRODUCTION   This manual contains the installation and operating instructions for your new air conditioner.   Improper installation can result in unsatisfactory operation or dangerous conditions. Carefully   read this manual and any instructions packaged with separate equipment required to make up   the system prior to installation. Give this manual to the owner and explain its provisions. The   owner should retain this manual for future reference.   2.NOMENCLATURE FOR MODEL NUMBER   H C Brand symbol - H: Haier   System type - C: Air conditioner; R: Heat pump.   24 Nominal capacity in (000) Btuh   9 1 SEER designation. 9=9, B=11, C=12, D=13, E=14   Design series. 1 - 1 Generation   st   V A R Electric: V=208/230-1-60; C=208/230-3-60, D=460-3-60, Y=575-3-60   Body style   Compressor type   Example: HC2491VAR   3.SPECIFICATION   The dimensions for the condensing unit are illustrated in Figure 1. Physical and electrical   specifications are provided in Table 1 for 9 SEER systems respectively.   D W H Figure 1   1 Model:HC18-6091VAR   Table 1:   2 4.UNIT INSPECTION   This product has been inspected at the factory and released to the transportation agency without   known damage. Inspect exterior of carton for evidence of rough handling in shipment. Unpack   carefully. If damage is found, report immediately to the transportation agency.   5. EQUIPMENT PROTECTION FROM ENVIRONMENT   The metal parts of the unit may be subject to rust or corrosion in adverse environmental conditions.   This oxidation could shorten the unit life. Salt spray or mist in seacoast areas, sulphur or chlorine   from lawn watering systems and various chemical contaminants from industries such as paper mills   and petroleum refineries are especially corrosive.   If the unit is to be installed in an area where contaminants are likely to be a problem, special attention   should be given to the equipment location and exposure.   Avoid having lawn sprinkler heads spray directly on the unit cabinet.   In coastal areas, locate the unit on the side of the building away from the waterfront.   Shielding provided by fence or shrubs may give some protection.   Regular maintenance will reduce the buildup of contaminants and help to protect the unit's finish.   ! WARNING - Disconnect all electrical power to the unit before servicing. Disconnect power to   both the indoor and outdoor units. NOTE: There may be more than one electrical disconnect switch.   Failure to shut off power can cause electrical shock resulting in personal injury or death.   Frequent washing of the cabinet, fan blade and coil with fresh water.   Regular cleaning and waxing of the cabinet with good automobile polish.   A good liquid cleaner may be used several times a year to remove matter that will not wash   off with water.   The best protection is frequent cleaning, maintenance and minimal exposure to contaminants.   6.INSTALLATION   6.1.GENERAL   These units are designed for outdoor installations. They can be mounted on a slab or rooftop. It   is important to consult your local code authorities at the time the first installation is made.   Check following points before attempting any installation:   Structural strength of supporting members.   Clearances and provision for servicing.   Power supply and wiring.   Location for minimum noise, where operating sounds will not disturb owner or neighbors.   Location where there is no risk of combustible gas leakage.   Location where external water drainage cannot collect around the unit.   Location where roof runoff water does not pour directly on the unit. Provide gutter or other   shielding at roof level. Don't locate unit in an area where excessive snow drifting may occur   or accumulate.   3 Provide a level concrete slab. To prevent transmission of noise or vibration, slab should not be connected   to building structure. Some sort of sound-absorbing material should be placed between the condenser   and the slab. A good material to use is rubber and cork pad.   For rooftop application, make sure the building construction can support the weight and that proper   consideration is given to the weather-tight integrity of the roof. The condensing unit contains moving   parts and can vibrate. Therefore, sound is also a consideration in rooftop applications.   ! WARNING - Install the unit securely in a place that can bear the weight of the unit. When installed   in an insufficiently strong place, the unit could fall causing injury.   6.2.UNIT CLEARANCES   10" Min.   10" Min.   Service Access   18" Min.   Service Access   18" Min.   10"   10"   Figure 2   The minimum clearances for the unit are illustrated in Figure 2. Condenser air enters from three sides.   Air discharges upward from the top of the unit. Refrigerant tube and electrical connections are made   from the service access area. The most common application will find the unit best located about 10"   from back wall with connection side facing the wall. This application minimizes exposed tubing and   wiring, minimizing the space for youngsters to run around the unit with subsequent damage to the   tubing or wiring.   In more confined application spaces, such as corners provide a minimum of 10" clearance on all air   inlet sides. For service access to the compressor and control box, allow 18" minimum clearance. Ensure   top is unobstructed. If units are to be located under an overhang, there should be a minimum of 36"   clearance and provision made to deflect the warm discharge air out from the overhang.   In order to have an unrestricted air flow, owners should be advised to avoid lawn mower discharge   toward the unit depositing debris on the fin coil surface reducing the unit efficiency.   6.3.REFRIGERANT PIPING   The refrigerant piping is very important as it affects the proper operation and efficiency of the air   conditioning system. Note the following guidelines:   4 OUTDOOR UNIT   ADDITIONAL SUCTION LINE   OIL TRAP FOR EACH 20 FOOT   RISE OF PIPE   PITCH SUCTION LINE TOWARD OUTDOOR   UNIT 1/2" FRO EVERY 10' OF LINE   INDOOR UNIT ABOVE OR   LEVEL TO OUTDOOR UNIT   70'   MAX.   LIQUID LINE   SUCTION LINE OIL   TRAP WHEN INDOOR   UNIT IS 4 FEET OR   OUTDOOR UNIT   INDOOR UNIT   INDOOR UNIT   LIQUID LINE   M O R E   B E L O W   OUTDOOR UNIT   A INDOOR UNIT BELOW OUTDOOR UNIT   6'   B-1   INVERTED LOOP   LIQUID LINE   INDOOR UNIT   50'   OUTDOOR UNIT   MAX.   SUCTION LINE   Figure 3   B-2   Only refrigeration-grade copper piping (dehydrated and sealed) should be used. Take extreme care to keep   the refrigerant tubing clean and dry prior to and during installation. If in doubt, blow out the tubing   with dry nitrogen to remove any chips or debris before connection. Always keep tubing sealed until it is   in place and the connections are to be made.   Refrigerant piping should be as short as possible, with a minimum of elbows or bends, to avoid capacity   loss and increased operating costs.   Refrigerant lines must be adequately supported. If metal strapping is used to secure the tubing, do not allow   the strapping to directly contact the tubing. Use a closed cell insulation to separate the strapping from the   tubing.   Do not kink or twist the tubing.   Refrigerant piping should not be installed in a cement slab, as this limits access to the refrigerant should a   leak be suspected.   To ensure good oil return to the compressor, it is important to pitch the horizontal suction line toward   the compressor, approximately 1/2" for every 10' of line.   Line Insulation   Suction line requires insulation in order to prevent condensation from forming on the piping and to   prevent heat gain caused by surrounding air. Generally 3/8" wall thickness of Armflex or equivalent   is satisfactory. In severe application (hot, high humidity areas) greater thickness may be required. Apply   the line insulation by sliding it on the sealed tuing before cutting and making connections.   Liquid line does not necessarily need insulation, however, if they are exposed to high ambient temperatures   (i.e. kitchen, boiler rooms, hot attics & rooftop surface), then, they should be insulated. Make sure to   use the proper size tubing for the liquid line to prevent liquid refrigerant flashing to a vapor within   the liquid line.   Do not allow the vapor line and liquid line to touch together. This would cause an undesirable heat   transfer resulting in capacity loss and increased power consumption.   5 Refrigerant Line Sizing   Check the following table (Table 2 ) for correct suction and liquid line sizes for any combination of   the unit size and the maximum refrigerant line length.   Refrigerant Line Length(Ft)   0-24   25-49   50-74   Unit Size   (Ton)   Line Outside Diameter(In)   Suction   Liquid   ꢆꢉꢃ   ꢆꢉꢃ   ꢆꢉꢃ   ꢆꢉꢃ   ꢆꢉꢃ   ꢆꢉꢃ   ꢆꢉꢃ   Suction   ꢆꢉꢄ   Liquid   ꢆꢉꢃ   ꢆꢉꢃ   ꢆꢉꢃ   ꢆꢉꢃ   ꢆꢉꢃ   ꢆꢉꢃ   ꢆꢉꢃ   Suction   ꢆꢉꢄ   Liquid   ꢆꢉꢃ   ꢆꢉꢃ   ꢆꢉꢃ   ꢂꢉꢀ   ꢂꢉꢀ   ꢂꢉꢀ   ꢂꢉꢀ   Seer   9 9 9 9 9 9 9 ꢂꢇꢁ   ꢀꢇꢅ   ꢀꢇꢁ   ꢆꢇꢅ   ꢆꢇꢁ   ꢄꢇꢅ   ꢁꢇꢅ   ꢁꢉꢃ   ꢁꢉꢃ   ꢆꢉꢄ   ꢆꢉꢄ   ꢆꢉꢄ   ꢆꢉꢄ   ꢌꢉꢃ   ꢆꢉꢄ   ꢆꢉꢄ   ꢆꢉꢄ   ꢌꢉꢃ   ꢆꢉꢄ   ꢌꢉꢃ   ꢌꢉꢃ   ꢂꢎꢂꢉꢃ   ꢂꢎꢂꢉꢃ   ꢂꢎꢂꢉꢃ   ꢂꢎꢂꢉꢃ   ꢂꢎꢂꢉꢃ   Table 2:Refrigerant Line Sizing   The factory charge is sufficient for 25 feet of standard liquid line. For longer or shorter liquid line   lengths, adjust the charge as follows:   1/4" Line   5/16" Line   3/8" Line   1/2" Line   +/- 0.3 oz. Per foot   +/- 0.4 oz. Per foot   +/- 0.6 oz. Per foot   +/- 1.2 oz. Per foot   Vertical Separation between Indoor and Outdoor Units   Maximum allowable vertical separations between indoor and outdoor units are illustrated in Figure   3-A and Figure 3-B. It's 70' when the indoor unit is below the outdoor unit (Figure 3-A), and 50' when   the indoor unit is above the outdoor unit (Figure 3-B).   To ensure good oil return to the compressor when the indoor unit is below the outdoor unit, suction   line oil trap should be used as illustrated in Figure 3-A.   Tubing Connections   ! CAUTION - Use extreme caution in removing the caps from the suction and liquid line fittings, as   there is pressure present. A fitting is on the liquid line to remove pressure.   ! CAUTION - Condensing units are charged with refrigerant. Condensing unit liquid and suction   valves are closed to contain the charge within the unit. Do not force the valve stem against the retaining   ring. If the valve stem is backed out past the retaining ring, system pressure could force the valve stem   out of the valve body and possibly cause personal injury.   ! CAUTION - The piston is in the accessory bag. Don't forget to take it out and put into the indoor   liquid pipe orifice.   Instructions on the field tubing connections and valve opening procedure are as follow:   6 1.Tubing should be cut square. Make sure it is round and free of burrs at the connecting ends.   Clean the tubing to prevent contamination from entering the system.   2.Make sure that both refrigerant stop valves at the outdoor unit are closed.   3.Push the tubing into the fitting until it stops. This prevents flux from getting into the system.   4.Remove the cap and Schrader valve core from the service port to protect the valve seals.   5.Wrap a wet rag around the valve stub before brazing.   6.Braze the joints of interconnecting tubing. Flow dry nitrogen into the shutoff valve port   and through the tubing while brazing.   7.After brazing quench with a wet rag to cool the joint. Reinstall the Schrader core in the valve,   if removed for brazing.   8.Pressurize the lines to 150 psi maximum with dry nitrogen. Check for leaks at all joints with   liquid detergent. If a leak is found, repair it after removing the nitrogen. Repeat the process   and re-ckeck.   9.Do not purge the lines with refrigerant. Evacuate the lines and indoor coil.   Evacuation   All new installations must be evacuated to a deep vacuum in order that all noncondensible gases   and moisture are removed prior to charging the system. Air in a system causes high condensing   pressure, which increases power consumption and reduces performance. The presence of moisture   in a system can render it inoperable in a very short time. Proper evacuation assures a dry, uncontaminated   system. Here is the recommended evacuation procedure:   1.Connect vacuum pump to both liquid and suction valve service ports.   2.Evacuate the interconnecting tubing and indoor coil to 500 microns or less for a minimum   of 30 minutes. Close the valve to the vacuum pump and wait 15 minutes. Vacuum should   not rise above 800 microns. If unable to obtain 500 microns, or vacuum rises above 800   microns over 15 minutes period, discontinue evacuation, pressurize and check for leaks.   Repair any leaks found and repeat the step 2.   3.Close valve to the vacuum pump and stop pump.   4.When sure of a tight, well evacuated system, charge with refrigerant.   Charging the System   (For systems with capillary tube or fixed orifice metering device)   Before checking the system charge, make sure that the outdoor unit and indoor coil must be an   approved match per the unit specification. The indoor conditions should be within 2 F of the desired   comfort conditions.   ! WARNING - Do not vent refrigerant to the atmosphere! It is a violation of federal law to do   so. If the refrigerant needs to be removed from a system to correct the charge inside, always use a   recovery or recycling device.   ! WARNING - To prevent personal injury, wear safety glasses and gloves when handling   refrigerant.   7 1.Fully open both shutoff valves.   2.Connect service gage manifold to the valve service   ports, being sure to evacuate lines.   System Superheat   Ambient   Temperature At   Return Air Temperature ( F)   65   70   75   80   85   3.Startup the system (Refer to the Section 7 - "System   Startup"). Run system at least 10 minutes to allo   pressure to stabilize.   4.Temporarily install thermometer on suction (large)   line near condensing unit. Be sure of good contact   between thermometer and line. Wrap thermometer   with insulating material to assure accurate reading.   5.Refer to Table 3 for proper system superheat. Add   charge to lower superheat. Remove charge to raise   superheat.   Condenser Inlet ( F)   60   65   70   75   80   85   90   95   100   17   13   5 25   19   14   10   5 30   26   20   17   12   10   7 33   32   28   25   21 26   17 20   12 18   37   35   32   29   5 5 5 5 5 5 5 Carefully remove gage lines.   Table 3:System charging table by superheat   6.4.ELECTRICAL WIRING   ! WARNING -   A means of strain relief must be installed to this appliance at the electrical service entrance.   Make sure that interconnecting wires between indoor and outdoor units meet the standards, codes   and regulations. Incomplete connection or fixing of the wire could result in a fire.   A means of strain relief must be installed to this appliance at the electrical service entrance.   Do not use intermediate connection of the power cord or the extension cord and do not connect   many devices to one AC outlet. It could cause a fire or an electric shock due to defective contact,   defective insulation, exceeding the permissible current, etc.   Perform electrical work according to the installation manual and be sure to use an exclusive   circuit. If the capacity of the power circuit is insufficient or there is incomplete electrical work, it   could result in a fire or an electric shock.   Ground the unit. Do not connect the ground to a gas pipe, water pipe, lighting rod or telephone   ground. Defective grounding could cause an electric shock.   Electrical installation will consists of power supply wiring to the condensing unit and control wiring   between thermostat, indoor unit and the condensing unit. All wiring must be in accordance with National   Electrical Code and/or local ordinances that may apply.   (See unit wiring diagram furnished with this instruction).   Note: Some states need the power supply wiring within special tybe be careful to use the waterproof   tube when installation the outdoor unit power supply wiring.(See the figure 4)   Figure 4-1   Figure 4-2   8 The condensing unit rating plate and the tables of "Physical and Electrical Specifications / Outdoor   Units" (Table 1 and 2) provide pertinent data necessary for the selection of proper size electrical service   and over-current protection devices.   Table 4 provides data on the minimum copper wire size as a function of supply wire length and circuit   ampacity.   Copper Wire Size - AWG   (1% Voltage Drop)   Supply Circuit   Supply Wire Length - Ft   Ampacity   50   14   12   10   10   8 8 6 6 100   10   8 8 6 6 6 4 4 150   8 6 6 4 4 4 3 3 200   6 4 4 4 3 2 2 1 15   20   25   30   35   40   45   50   Table 4: Minimum Wire Size Based on N.E.C. for 60 C Type Copper Conductors Below 100   Ampacity.   The owner should be made familiar with the location of the over-current protection, the proper size   for this application and the proper procedure for disconnecting power service to the unit.   The condensing unit control wiring requires a 24 Volt minimum, 25 VA service from the indoor   transformer as shown on the wiring diagram.   7.SYSTEM STARTUP   1.Turn thermostat to "OFF", turn on power supply at disconnect switch.   2.Turn temperature setting as high as it will go.   3.Turn fan switch to "ON". Indoor blower should run. Be sure it is running in the right direction.   4.Turn fan switch to "AUTO". Turn system switch to "COOL" and turn temperature setting below   room temperature. Unit should run in cooling mode.   5.Check to see if compressor and outdoor fan are running correctly?   6.Check the refrigerant charge (see Instructions under "Charging the System").   7.Replace service port caps. Service port cores are for system access only and will leak if not tightly   capped.   8.Check unit for tubing and sheet metal rattles.   9.Instruct the owner on operation and maintenance.   Leave this "Installation and Operating Manual" and the "Use and Care Manual" with owner.   9 8.OPERATION   Most single phase units are operated without start relay or start capacitor. Such systems should   be off for a minimum of 5 minutes before restarting to allow equalization of pressures. The   thermostat should not be moved to cycle unit without waiting 5 minutes. To do so may cause   the compressor to stop on an automatic open overload device or blow a fuse. Poor electrical   service can cause nuisance tripping in overloads or blow fuses.   The compressor has an internal overload protector. Under some conditions, it can take up to 2   hours for this overload to reset. Make sure overload has had time to reset before condemning   the compressor.   9.MISCELLANEOUS   9.1.   Replacement Parts   Contact your local distributor for a complete parts list.   9.2.   Troubleshooting Guide   Refer to the troubleshooting guide (Table 5) included in this manual.   9.3. Wiring Diagram   Refer to the appropriate wiring diagram included in this manual.(P12)   Table 5:Troubleshooting Guide   ! WARNING - Disconnect all electrical power to the unit before servicing. Disconnect power to   both the indoor and outdoor units. NOTE: There may be more than one electrical disconnect switch.   Failure to shut off power can cause electrical shock resulting in personal injury or death.   10   Symptom   Possible Cause   Remedy   Power off or loose electrical connection   Incorrect thermostat setting   Defective contactor   Open circuit breaker of blown fuses   Defective transformer   Make sure main switch is ON. Check and tighten all connections.   Set thermostat correctly   Check for 24V at contactor coil.   Reset or replace   Check wiring - Replace it.   No cooling   Interconnecting low voltage wiring damage Replace thermostat wiring   Dirty filters   Clean & replace   Indoor air blockage   Blocked outdoor coil   Improperly sized unit   Check supply registers and return grills for blockage.   Clear away leaves and other debris   Recalculate load   Insufficient Cooling Improper airflow   Incorrect refrigerant charge   Check - should be 400CFM/Ton   Charge correctly per instruction.   Air, non-condensibles or moisture in system Recover refrigerant, evacuate & recharge, add filter drier   Incorrect voltage   At compressor terminals, voltage must be within   10% of rating plate volts when unit is running.   Water on floor or in   furnace   Blocked condensate drain and "P" trap   Remove blockage   Run or start capacitor defective   Loose connection   Condenser fan runs, Compressor stuck, grounded or open   compressor doesn't motor winding, open internal overload   Low voltage condition   Replace   Check and tighten all connections.   Wait for 2 hours for overload to reset.   Replace compressor if still open.   At compressor terminals, voltage must be within 10% of rating   plate volts when unit is running.   Low voltage condition   Incorrect voltage   Add start kit components   At compressor terminals, voltage must be within 10% of rating   plate volts when unit is running.   Compressor   short-cycling   Defective overload protector   Refrigerant undercharge   Low evaporator airflow   Restriction in liquid line,   Replace - check for correct voltage   Add refrigerant   Increase blower speed or reduce restriction - replace air filter   Replace defective components   Register sweat   High head - Low metering device or filter drier   vapor pressures   Flowrator piston size too small   Incorrect capillary tubes   Blocked outdoor coil   Change to correct size piston   Change coil assembly   Clear away leaves and other debris   Correct system charge   Repair or replace   Recover refrigerant, evacuate &   recharge, add filter drier   High head - High   or normal vapor   pressures   Refrigerant overcharge   Condenser fan not running   Air, non-condensibles or   moisture in system   Low head - High   vapor pressures   Flowrator piston size too large   Defective compressor valves   Incorrect capillary tubes   Change to correct size piston   Replace compressor   Replace coil assembly   Low vapor - cool Low evaporator airflow   compressor - iced Operating below 65 F outdoors   Increase blower speed or reduce restriction - replace air filter   Add low ambient kit   evaporator coil   High vapor   Moisture in the system   Excessive load   Recover refrigerant, evacuate & recharge, add filter drier   Recheck load calculation   pressure   Defective compressor   Air or non-condensibles in system   Replace   Fluctuating head   and vapor pressures   Pulsing noise at   metering device   or liquid line   Recover refrigerant, evacuate & recharge.   Air or non-condensibles in system   Recover refrigerant, evacuate & recharge   11   HC18-6091VAR   Air Conditioner Wiring Diagram   LINE VOLTA GE   FACTORY STANDARD   FIELD INSTALLED   OPTIONAL   LOW VOLTAGE   FACTORY STANDARD   FIELD INSTALLED   OPTIONAL   OPTIONAL   ELECTRIC HEATER KIT   5 L1   BRK   OFM   FL BK   BK   BK   6 BR   RD   RD   BK   FL   RD   R M TL   S BR   RD   L2   TL   YL   RD   USE COPPER CONDUCTORS ONLY   RD   RD   C WARNING CABINET MUST BE PERMANENTLY GROUNDED   AND ALL WIRING TO CONFORM TO I.E.C.,N.E.C.,C.E.C.,   C.L.C. AND LOCAL CODES AS APPLICABLE.   REPLACEMENT WIRE MUST BE THE SAME GAGE AND   INSULATION TYPE AS ORIGINAL WIRE.   S 6 RD   BK   R BK   PU   BR   RD   PU   BL   WH   BK   208/230V   60Hz 1PH   L1 BK   2 3 4 5 6 1 COMPONENT CODES   CC   BCR - BLOWER CONTROL RELAY   BCAP - RUN CAPACITOR BLOWER MOTOR   CC - COMPRESSOR CONTACTOR   CCH - CRANKCASE HEATER (OPTIONAL)   CHS - CRANKCASE HEATER SWITCH (OPTIONAL)   CMPR - COMPRESSOR   BK   L1   L2   7 4 WH   L2   GND   WH   RD   2 2 3 3 4 4 5 5 6 1 1 GND   6 HPS - HIGH PRESSURE SWITCH   LPS - LOW PRESSURE SWITCH   IBM - INDOOR BLOWER MOTOR   OFM - OUTDOOR FAN MOTOR   BCR   NC   PU   BK RD PU   BR   WH   BL   208/230V   60Hz 1PH   2 4 6 1 3 YL   BL   IBM   NO   BR   RCAP - RUN CAPACITOR COMPRESSOR   RVS - REVERSING VALVE SOLENOID   STCAP - START CAPACITOR (OPTIONAL)   STRLY - START RELAY (OPTIONAL)   STRTH - START THERMISTOR (OPTIONAL)   TRAN - TRANSFORMER   BCAP   5 7 COM   Compressor   Protect 3 Min.   Time Delay   S R M P1   P3   8 P2   BR   GR   BL   GR   PU   230/208 SELECTABLE   BK-HI   3 TRAN   BK   BK   RD   230   L1   COLOR CODES   RD-LO   BK - BLACK   BR - BROWN   BL - BLUE   GY - GRAY   OR - ORANGE   VI - VIOLET   208   BL   GR- GREEN   COM   YL   Optional   PU - PURPLE RD - RED   WH - WHITE   RD   OR   LPS   HPS   Low & High   Pressure   Switches   YL - YELLOW   L2   2 RD   YL   BL   BL   BL   BL   RD   BL   YL   HEAT   BR WH   W2   OFF   HA   CA   COOL   C Y R C G W AUTO   ON   TS   HEAT   Y RESISTANCE   COMPRESSOR   HEAT CONTROL   W OFF   COOL   G INDOOR FAN CONTROL   RHS-2   24VAC COMMON   R C LED   1) Confirm system selection. Optional components may be field or factory installed.   2) If LPS and/or HPS not installed or removed, a jumper wire must be present across circuit for system to operate.   3) For proper system operation, consult indoor unit and outdoor unit installation instructions to confirm system match up and blower speed selection.   4) Alternate double pole contactor used on some systems.   5) Only one start assist method to be used at a time, consult outdoor unit installation instructions for application information. Use only factory approved accessories.   6) Optional OFM components may connect capacitor common and motor common, for reciprocating compressor there may have crankcase heater consult outdoor unit installation   instructions for details.Select the running capacitor(one or dual)and connect.If IFM or OFM only have one capacitor wire,connect Com wire to capacitor.   7)   When supplying power for outdoor unit,the black line is for neutral line and white line for live line.   12   Made in P.R.C.   |