| INSTALLATION   & SERVICING   MANUAL   Concord   CXSi 110/H-180/H   BOILERS   Download from Www.Somanuals.com. All Manuals Search And Download.   GENERAL   Table 1 - Performance Data   Boiler   CXSi 110/H   CXSi 120/H   CXSi 140/H   CXSi 160/H   CXSi 180/H   Boiler Input   Low Rate   Gross   Nett   kW   Btu/h x 1000   kW   93.9   320.5   84.6   288.7   134.2   457.8   120.9   412.4   110   102.5   349.6   92.3   119.5   407.9   107.7   367.4   170.8   582.7   153.8   524.9   140   136.6   466.1   123.1   419.9   195.2   665.9   175.8   599.9   160   153.7   524.4   138.5   472.4   219.6   749.1   197.8   674.9   180   Btu/h x 1000   kW   315.0   146.4   499.4   131.9   449.9   120   Boiler Input   High Rate   Gross   Nett   Btu/h x 1000   kW   Btu/h x 1000   kW   Boiler Output   High Rate   Gas rate   Btu/h x 1000   m3/h   375.3   12.78   451.5   0.112   237   409.4   13.95   492.5   0.122   259   477.7   16.27   574.6   0.142   301   545.9   18.59   656.7   0.163   345   614.2   20.92   738.8   0.183   388   High   ft3/h   m3/h   ft3/h   Approx. flue At 4.5% CO2 & 100°C   gas volume At 4.5% CO2 & 212°F   Burner   setting   High   mbar   in.w.g.   mbar   in.w.g.   10.4   4.2   10.1   9.7   9.6   9.7   4.0   3.9   3.8   3.9   pressure   Low   5.1   4.9   4.8   4.7   4.8   2.0   2.0   1.9   1.9   1.9   Part load efficiency   % 83.0   81.6   82.5   82.9   82.8   Note. To obtain gas consumption in l/s divide gross heat input (kW) by a calorific value of 37.8(MJ/m2)   Table 2 - General Data   Boiler   CXSi 110/H   CXSi 120/H   CXSi 140/H   CXSi 160/H   CXSi 180/H   Number of sections   Flow connections   Return tappings   Maximum static head   Maximum pressure   Gas inlet connection   7 7 8 9 10   Rc   Rc   65 mm (2 1/2") nominal bore. Flange to BS.4504 (PN6)   2 x 2   61.0 (200)   6.0 (87)   1 1/2   m. (ft)   bar (psi)   Rc   Minimum dynamic   gas pressure   mbar   in.   17.5   7 17.5   7 17.5   7 17.5   7 17.5   7 Electricity supply   230 Volts - single phase, 50 Hz, fuse 5 A   Nominal flue size (to BS. 835)   mm   in.   250   10   250   10   250   10   250   10   300   12   Diverter outlet socket   internal diameter   mm   in.   288   11.3   288   11.3   288   11.3   288   11.3   344   13.5   Length of burner bars (overall)   mm   in   535   21.1   535   21.1   535   21.1   535   21.1   535   21.1   Approximate dry weight   Water content   kg   lb.   538   1186   53   538   1186   53   608   1340   60   678   1494   68   748   1648   76   litre   gal.   11.7   11.7   13   15   17   Concord CXSi/H - Installation & Servicing   3 Download from Www.Somanuals.com. All Manuals Search And Download.   GENERAL   Concord CXSi 110/H-180/H (Natural gas)   B.G. Certified - P.I. No. 87/AQ/341   Destination Countries: GB and IE   INTRODUCTION   CONTENTS   CONSTRUCTION   BOILER BODY   Air Supply......................................................................... 9   Boiler Assembly - exploded view. ............................... 10   Boiler Clearances............................................................ 6   The sectional boiler body is of cast iron and is supplied with a sheet   steel combustion chamber and integral draught diverter. The boiler   is supplied in sectioned form for site assembly.   CASING   The casing is manufactured in stove enamelled sheet steel and is   easily assembled on site.   Burner Assemblies - exploded views. ............................   CXSi 110/H-160/H. ................................................. 25   CXSi 180/H. ............................................................ 26   BURNERS   The burners are of stainless steel construction.   Casing Assembly. ......................................................... 14   Chimney System. ............................................................ 9   Commissioning. ............................................................ 20   Electrical Connections. ................................................ 17   Electrical Supply. ............................................................ 9   Fault Finding. ................................................................ 29   Gas Safety Regulations .................................................. 4   Gas Supply. ...................................................................... 9   Hydraulic Resistance. ..................................................... 6   Initial Lighting. .............................................................. 21   Installation. .................................................................... 10   Mandatory Requirements. .............................................. 8   Option Kits. ...................................................................... 5   Pump. ............................................................................... 7   Servicing. ....................................................................... 24   Short List of Parts. ........................................................ 31   Static Head Requirements. ............................................ 7   System Connections..................................................... 13   Ventilation. ....................................................................... 9   Water Circulation. ........................................................... 5   Water Connections. ........................................................ 5   Water Treatment. ............................................................. 7   Wiring Diagrams. .......................................................... 19   CURRENT GAS SAFETY (INSTALLATION AND USE)   REGULATIONS OR RULES IN FORCE.   It is the law that all gas appliances are installed and serviced by a   CORGI registered installer in accordance with the above regulations.   Failure to install appliances correctly could lead to prosecution. It   is in your own interest, and that of safety, to ensure that the law is   complied with.   The Concord CXSi 110/H-180/H range of boilers has been tested   and certified by British Gas to prEN656 for use with natural gas   only.   Note. Concord CXSi 110/H - 180/H boilers are intended for use   as COMMERCIAL BOILERS and are NOT certified for use in   domestic applications. A domestic installation is defined as an   installation where the boiler takes its combustion air from a living   space or from a room directly or indirectly connected with the   living space. It is important, therefore, that no external control   devices - e.g. flue dampers, economisers etc., are directly   connected to this appliance unless covered by these Installation   and Servicing Instructions or otherwise recommended by   Caradon Ideal Limited in writing. If in doubt please enquire.   Any direct connection of a control device not approved by Caradon   Ideal Limited could invalidate the British Gas Certification, the   normal appliance warranty and could also infringe the Gas Safety   Regulations. Table 1, Table 2 and the descriptive notes which follow   contain all the essential data likely to be required by the installer.   GAS CONTROLS   The boiler lights at Low rate (approximately 70% of Full rate) by   direct burner ignition. After about 1 minute the boiler goes to High   rate and will continue at High rate until the thermostat sensor set   point is reached. The boiler will then drop to the Low rate; if the   temperature continues to rise the boiler will go Off; if the   temperature falls the boiler will revert to High rate.   ELECTRICAL CONTROLS   The boiler is supplied with 2 printed circuit boards; Board   S4561B1047 is the ignition board containing the flame-proving logic;   Board W4115A1020 contains the electronic thermostat and pump   overrun timer. A preset overheat thermostat is also provided. The   mains voltage supply is via a terminal plug in connection at the   control box. The control box displays neons indicating boiler status   as follows:   - Boiler on   - Lockout   - Overheat   An anti-cycle delay is built in to the controls to prevent rapid cycling.   CAUTION. To avoid the possibility of injury during the installation, servicing or cleaning of   this appliance, care should be taken when handling edges of sheet steel components.   Concord CXSi/H - Installation & Servicing   4 Download from Www.Somanuals.com. All Manuals Search And Download.   GENERAL   FROST PROTECTION   WATER CIRCULATION SYSTEM   Due to the compact nature of the boiler the heat stored within the   castings at the point of shutdown of the burner must be dissipated   into the water circuit in order to avoid the overheat thermostat   tripping. In order to allow pump operation after burner shutdown   the boiler control box incorporates a pump overrun facility which   operates for approximately 6 minutes after the burner shuts down   and, in order to make use of this, the pump must be wired to the   appropriate terminal L2 (pump) in the boiler control box.   Frost protection is incorporated in the boiler as long as there is a   permanent Live supply wired to Terminal L1 on the terminal plug-in   connection at the control box and the boiler thermostat knob is not   switched to Off.   If the temperature sensed by the boiler thermostat falls to about   50C the boiler will fire until the temperature reaches 180C.   Note that this is designed to protect the boiler and may not   necessarily protect remote parts of the system.   1. The minimum flow rate as given in Table 4 must be maintained   whenever the boiler is firing and during the pump overrun period.   The mains voltage supply is via a terminal plug-in connection at the   control box.   2. During the period of pump overrun there must be an open circuit   of adequate water volume and/or load. The minimum size of   this circuit is given by the use of Graph 1.   OPTION KITS   Examples shown on Graph 1   Remote Indication Kit   This kit gives the facility of remote indication of boiler status.   a. For the CXSi 110/H and CXSi 120/H the minimum circuit   during pump overrun could be a load of 7 kW with a volume   of 42 litres or any other combination given by the relevant   line.   Pressure Gauge Kit   A pressure gauge kit is available.   b. For the CXSi 180/H the minimum circuit during pump overrun   could be a load of 9 kW with a volume of 70 litres or any   other combination given by the relevant line.   DUTY   The range of boilers is suitable for: Combined indirect pumped   domestic hot water and central heating systems; Independent   indirect pumped domestic hot water or central heating systems.   The above circuit capacity during pump overrun may be achieved   either by provision of an adequate bypass circuit or by ensuring   that a zone of suitable size is open for circulation during this   period by relevant control of zone valves or pumps.   Fully pumped systems may be open vented or sealed.   The range of boilers is NOT suitable for:   The wiring diagrams in Frames 16,17 &18 illustrate the control   methods for achieving the above.   1. Gravity DHW systems.   2. Gravity heating systems.   3. Direct domestic hot water supply.   3. Pump selection should take account of the hydraulic resistance   given in Graph 2.   1 WATER CONNECTIONS   Cold Feed/Open Vent   Flow connection is 65mm (2 1/2") nominal bore flange to   BS.4504 (PN6)   The independent cold feed and the open vent must comply   with BS. 6644 and be of the following minimum size.   Return tappings are 2" BSP.   The distributor tube must be fitted into the return connection.   The flow header must be fitted in the flow pipe.   The open vent must be brought to either the 1 1/2" BSP tapping   on the flow header or to the unused 2" BSP tapping at the top   rear of the boiler.   The cold feed may be brought to the LH front bottom tapping in   order to avoid excessive surging or pumping over. The unused   bottom rear tapping must not be used for the cold feed pipe as   it is practically blocked by the distributor tube.   Safety Valve   A safety valve must be sized and fitted in accordance with BS.   6644 for every type of system. The valve should be set at 0.7   bar (10 lb/in.2) above the operating pressure in the boiler. The   maximum safety valve setting is 0.7 bar (10 lb/in.2) above the   maximum design operating pressure of 6.0 bar (87 lb/in.2).   Boiler Size   CXSi 110/H   CXSi 120/H   CXSi 140/H   CXSi 160/H   CXSi 180/H   Cold Feed   Open Vent   1 1/4"   1"   1"   1 1/4"   1"   1 1/4"   1 1/4"   1 1/4"   1 1/2"   1 1/2"   Concord CXSi/H - Installation & Servicing   5 Download from Www.Somanuals.com. All Manuals Search And Download.   GENERAL   Graph 2 - Hydraulic Resistance   Graph 1 - Heat Load / Water Volume   2 CLEARANCES & DIMENSIONS   Table 3   Boiler Size   CXSi 110/H   CXSi 120/H   CXSi 140/H   700 (27 1/2)   200 (8)   CXSi 160/H   CXSi 180/H   Front clearance   Rear clearance   Side clearance   Dimension A   Dimension B   Dimension C   Dimension D   Dimension E   Dimension F   mm (in)   mm (in)   mm (in)   100 (4) - not including clearance for side fitted flow header   mm (in) 1036 (40 3/4) 1036 (40 3/4)   mm (in) 175 (7) 175 (7)   mm (in) 1107 (43 3/4) 1107 (43 3/4)   1036 (40 3/4)   175 (7)   1086 (42 3/4)   197 (7 3/4)   1140 (45)   250 (10)   1230 (48 1/2)   939 (37)   1353 (53 1/4)   1062 (42 3/4)   676 (26 5/8)   220 (8 5/8)   1476 (58 1/8)   1185 (46 5/8)   738 (29)   mm (in) 816 (32 1/8)   mm (in) 553 (21 3/4)   mm (in) 220 (8 5/8)   816 (32 1/8)   553 (21 3/4)   220 (8 5/8)   615 (24 1/4)   220 (8 5/8)   320 (12 1/2)   1 POSITION OF BOILER   Minimum clearances required from walls or other fixed   objects to allow for the free access of combustion air are   shown in Table 3 above.   Any combustible material adjacent to the boiler and its flue   system must be so placed or shielded as to ensure that its   temperature does not exceed 65 0C (150 0F).   Concord CXSi/H - Installation & Servicing   6 Download from Www.Somanuals.com. All Manuals Search And Download.   GENERAL   PUMP POSITIONS   WATER TREATMENT FOR HOT WATER AND   Whenever practically possible the circulating pump(s) should be HEATING BOILERS   positioned so that it pressurises the system being served. The   There is a basic need to treat the water contained in all heating and   vertical distance between the pump(s) and any cold feed and   expansion cistern MUST comply with the pump manufacturers   requirements, in order to avoid cavitation. These requirements   override the information given in Frame 3 if the static head required   for the pump(s) exceeds that required for the boiler.   indirect water systems, particularly open vented systems. It is   assumed, incorrectly, that because boilers are operating in   conjunction with what is apparently a closed circuit an open vented   system will not, under normal circumstances, allow damage or loss   of efficiency due to hardness salts and corrosion once the initial   charge of water has been heated up a few times.   MINIMUM FLOW OF WATER - Refer to Table 4   The system design must provide for an adequate flow rate through 1mm of lime reduces the heat transfer from metal to water by 10%.   the boiler at all times when the boiler is firing. The minimum flow   In practice the deposition of these salts is liable to cause noises   from the boiler body or even premature boiler failure. Corrosion   and the formation of black iron oxide sludge will ultimately result in   premature radiator failure.   rate should correspond to a temperature difference across the boiler   flow and return of 35°C (63°F), assessed at catalogue rating.   Table 4 - Flow rates for fully pumped systems   Open vented systems are not completely sealed from the   atmosphere if proper venting and expansion of system water is to   be achieved. The same tank is used to fill the system with water   and it is through the cold feed pipe that system water expands into   the tank when the boiler passes heat into the system. Conversely,   when the system cools, water previously expanded is drawn back   from the tank into the system, together with a quantity of dissolved   oxygen.   Boiler   Minimum flow rates for a   temperature difference of 35°C (63°F)   l/s   g.p.m.   CXSi 110/H   CXSi 120/H   CXSi 140/H   CXSi 160/H   CXSi 180/H   0.75   0.82   0.96   1.10   1.24   9.9   10.8   12.7   14.6   16.4   Even if leakage from the heating and hot water system is eliminated   there will be evaporation losses from the surface of the tank which,   depending upon ambient temperature, may be high enough to   3 OPEN VENTED SYSTEMS - minimum static head requirements   The information provided is based on the   following assumptions:   1. The open vent MUST be brought to either   the 1 1/2" BSP tapping on the flow header   provided or to the unused 2" BSP flow   tapping at the top rear of the boiler.   2. An independent cold feed/expansion pipe   connection is made to the LH lower front   connection. Cold feed/expansion pipe   connections made to the pumped system   return will result in an increase in the static   head requirement, caused by the   additional resistance of the distributor tube.   Surging may also increase.   3. The maximum flow rate through the boiler   is based on a temperature difference of   11°C at full boiler output and the circulating   pump is positioned in the flow to the   system.   4. The boiler is at the highest point of   circulation in the system. Systems   designed to rise above the boiler flow   tappings will automatically require a   minimum static head higher than that   shown.   Note. This diagram does not show safety valves, water flow   switches, etc., necessary for the safe operation of the system.   Particular reference should be made to BS. 6644: Section 2; Subsection   10 and Guidance note PM5 "Automatically controlled steam and hot   water boilers" published by the Health and Safety Executive.   The information and guidance given below is not intended to override any   requirements of either of the above publications or the requirements of   the local authority, gas or water undertakings.   5. The position of the open vent/safety pipe   above the expansion cistern water level is   given as a guide only. The final position will   depend upon the particular characteristics   of the system. Pumping over of water into   the expansion cistern must be avoided.   Other British Standards applicable are BS.5422 and BS.6700.   Concord CXSi/H - Installation & Servicing   7 Download from Www.Somanuals.com. All Manuals Search And Download.   GENERAL   evaporate a large portion of the system water capacity over a full Limitations of Intended Operating Environment   heating season.   These appliances are NOT suitable for installation where they will   be exposed to the elements.   There will always be corrosion within a heating or hot water system   to a greater or lesser degree, irrespective of water characteristics,   unless the initial fill water from the mains is treated. Even the water   in closed systems will promote corrosion unless treated.   A boiler room shall be constructed or adapted to meet the   requirements of BS 6644.   The maximum ambient temperature is 32 °C at 1.5 metres from the   floor with a maximum humidity of 90% RH.   For the reason stated Caradon Ideal Limited strongly recommend   that when necessary the system is thoroughly cleaned, prior to the   use of stable inhibitor, which does not require continual topping up   to combat the effects of hardness salts and corrosion on the heat   exchangers of the boiler and associated systems.   FOR SMALL PIPE INSTALLATIONS;   BS. 6891:   Installation of low pressure pipework   Caradon Ideal Limited advise contact directly with specialists on   water treatment such as:   FOR LARGE PIPE INSTALLATIONS   Gas Installations   Fernox Manufacturing Co. Ltd.,   Tandem House, Marlowe Way   Croydon.   Surrey CRO 4XS   Tel 0870 601 5000   or   Sentinel Division,   Betz Dearborn Ltd.,   Widnes,   Cheshire, WA8 8UD   Tel. 0151 424 5351.   IGE-UP-1:   Purging Procedures of Non-domestic Gas   Installations. Soundness Testing Procedures   for Industrial and Commercial.   IGE-UP-2:   Guidance notes on the Installation of Gas   Pipework, Boosters and Compressors in   Customer’s Premises Equal to or Greater than   25mm (Non-domestic).   SAFE HANDLING OF SUBSTANCES   Care should be taken when handling the boiler insulation panels,   which can cause irritation to the skin. No asbestos, mercury or   CFCs are included in any part of the boiler.   IGE-UP-10:   BS.6644:   Installation of Gas Appliances in Industrial and   Commercial Premises.   Installation of Gas Fired Hot Water Boilers   70kW to 1.8MW (net).   BS 6880 Pt 1-3: Water Supply.   INSTALLATION REQUIREMENTS   The appliance must be installed by a CORGI registered installer,   CP342:2:   Centralised Hot Water Supply.   Model Water Bye-laws   The installation of the boiler must be in accordance with the relevant   requirements of the Gas Safety Regulations, current I.E.E.   (BS.7671) Regulations, Model Water Bye-laws, local water   authority bye-laws and it should also comply with any relevant   requirements of the local gas supplier, local authority and the   relevant British Standard Codes of practice and building   regulations.   Manufacturers notes must not be taken, in any way, as overriding   statutory obligations.   The appliance must be installed in a room separated from living   rooms and provided with appropriate ventilation direct to the outside   - see Table 5.   4 SEALED (PRESSURISED) SYSTEMS   automatic reset. In the event of shutdown both visual and   audible alarms may be necessary.   Working pressure 6.0 bar maximum.   Pressure vessels used must comply with BS. 4814 and must   be sized on the basis of the total system volume and initial   charge pressure.   Particular reference should be made to BS. 6644: Section 6   and Guidance note PM5 "Automatically controlled steam and   hot water boilers" published by the Health and Safety Executive.   Initial minimum charge pressure should not be less than 0.5   bar (7.2 psi) and must take account of the static head and   specification of the pressurising equipment. The maximum water   temperatures permissible at the point of minimum pressure in   the system are specified in Guidance Note PM5.   The information and guidance given below is not intended to   override any requirements of either of the above publications or   the requirements of the local authority, gas or water undertakings.   When make up water is not provided automatically it will be   necessary to fit controls which shut down the plant in the event   of the maximum system pressure approaching to within 0.35   bar (5 psi) of the safety valve setting.   In general commercial closed pressurised systems are provided   with either manual or automatic water make up.   On both instances it will be necessary to fit automatic controls   intended to protect the boiler, circulating system and ancillary   equipment by shutting down the boiler plant if a potentially   hazardous situation should arise.   Other British Standards applicable to commercial sealed systems   are:-   BS. 6880: Part 2   BS. 1212   Examples of such situations are low water level and operating   pressure or excessive pressure within the system. Depending   on circumstances, controls will need to be either manual or   BS. 6281: Part 1   BS. 6282: Part 1   BS. 6283: Part 4   Concord CXSi/H - Installation & Servicing   8 Download from Www.Somanuals.com. All Manuals Search And Download.   GENERAL   CHIMNEY SYSTEM   FOUNDATION   To ensure the safe and satisfactory operation of the boiler then the   chimney system (which may be common or individual, in the case   of twin or multiple boiler installations) must be capable of the   complete evacuation of combustion products at all times. The   effective height of the chimney terminal(s) above the boiler outlet(s)   must ensure sufficient buoyancy to overcome the resistance of the   bends, tees and runs of the flue pipe involved and shall terminate in   a down draught free zone. The number of bends and lengths of   horizontal flue pipe used should be kept to a minimum in order to   reduce gas flow resistance.   The boiler must stand on a non-combustible floor (i.e. concrete   or brick) which must be flat, level and of a suitable load bearing   capacity to support the weight of the boiler (when filled with   water) and any ancillary equipment.   If the boiler is mounted on a plinth then the dimensions must   exceed the plan area of the boiler by at least 75mm on each side.   VENTILATION   Compliance with the recommendations made in BS.6644,   IGE UP/10 Installation of Gas Appliances in Industrial and   Commercial Premises and the 'Third Edition of the 1956 Clean   Air Act Memorandum' should be strictly observed where   applicable.   Safe, efficient and trouble-free operation of conventionally flued gas   boilers is vitally dependent on the provision of an adequate supply   of fresh air to the room in which the appliance is installed. Ventilation   by grilles communicating directly with the outside air is required at   both high and low levels. The minimum free areas of these grilles   must be according to the following scale:   The chimney design should avoid the formation of excessive   quantities of condensate. For this reason it is recommended that all   chimneys are insulated and lined. In the case of brick or similar   structures a stainless steel rigid or flexible flue liner (grade 304/   316) may be used in conjunction with a 50 mm (minimum) thick   layer of vermiculite or perlite granules between the liner and the   inner skin of the chimney body. Liners should be sealed at both top   and bottom.   Table 5 - Ventilation Requirements   Required area (cm2) per kW of total rated input (net)   Boiler room   Enclosure   Low level (inlet)   4 2 10   5 High level (outlet)   As the Concord CXSi/H range of boilers is supplied complete with   an integral draught diverter, a diverter MUST NOT be fitted within   the chimney system.   Note: Where a boiler installation is to operate in summer   months (e.g. DHW) additional ventilation requirements   are stated, if operating for more than 50% of time (refer   to BS6644).   Drainage points positioned at the bottom of all vertical chimney   sections should be provided. Drain pipes should be no less than   25 mm I.D., manufactured from acid condensate resistant material   such as stainless steel and be positioned so that pipe runs and   discharge points are not subject to the effects of frost and that flue   gases cannot leak into the boiler room.   Position ventilation grilles to avoid the risk of accidental obstruction   by blockage or flooding. If further guidance on ventilation is required   then consult BS.6644.   Care should be taken to ensure the specification of the chimney is   suitable for the application by reference to the manufacturers   literature. Caradon Ideal Limited can offer advice on the design of   suitable chimney systems.   AIR SUPPLY BY MECHANICAL VENTILATION   The supply of air by mechanical means to a space housing the   boiler should be by mechanical inlet with natural or mechanical   extraction. Mechanical extract ventilation with natural inlet must not   be used.   GAS SUPPLY   Where a mechanical inlet and a mechanical extract system is   applied, the design ventilation flow rates should be as in Table 4 of   BS.6644.   If there is any doubt regarding the capacity of the gas meter, the   available gas pressure, the adequacy of existing service pipes or   the size required for new service pipes then the advice of the gas   supplier should be requested.   The requirements for air supply by mechanical ventilation are given   in BS.6644.   Installation pipework should be fitted and tested for gas soundness   in accordance in accordance with BS. 6891;   Note. For mechanical ventilation systems an automatic control   should be provided to cause safety shutdown or lockout of the   boiler(s) in the event of failure of air flow in either inlet or extract   fans.   IGE-UP-1 for small installations   IGE-UP-2 for large installations.   The local gas supplier must be consulted if it is necessary to employ   a gas pressure booster.   IMPORTANT.   The use of an extractor fan in the same room as the boiler (or in an   adjacent communicating room) can, in certain conditions, adversely   affect the safe operation of the boiler. Where such a fan is already   fitted (or if it is intended to fit an extractor fan after installation of the   appliance) the advice of the gas supplier should be obtained.   ELECTRICAL SUPPLY   WARNING. This appliance must be efficiently earthed.   A 230 V - 50 Hz mains supply is required, fused at 5 amps.   Tests for spillage of products from the draught diverter when the   extractor fan is running and all doors and windows are shut should   be carried out after installation. If spillage is detected, the area of   permanent ventilation must be increased.   Wiring external to the appliance MUST be in accordance with the   I.E.E. (BS. 7671) Wiring Regulations and any local regulations   which apply.   For details of connections see Frame 14.   Concord CXSi/H - Installation & Servicing   9 Download from Www.Somanuals.com. All Manuals Search And Download.   INSTALLATION   5 CONCORD CXSi BOILER ASSEMBLY - Exploded view   Insulation not shown   Legend   1. Cleanout cover   8. Distribution tube.   9. Downdraught deflector.   10. Section bolt.   15. Lightback shield.   16. Burner manifold assy.   17. NOx duct.   2. Collector hood   3. Middle section   11. Drain cock.   18. Insulation bracket   4. Flow header   12. Base plate.   5. Section alignment rings & 'O' rings.   6. Thermostat pocket.   7. End section.   13. Combustion chamber.   14. Tie rods.   Concord CXSi/H - Installation & Servicing   10   Download from Www.Somanuals.com. All Manuals Search And Download.   INSTALLATION   6 BOILER SECTION ASSEMBLY   TOOLS REQUIRED   The site assembled boiler is supplied in the following packages:   ! ! ! ! Spanners   ! Combustion chamber / manifold / burner assembly.   ! Platework package.   Torque wrench   Pozi screwdriver   Mallet   ! Casing package.   ! Controls box package.   Section Assembly - refer to the exploded view   ! End and centre sections.   5. Take an end section and lift it onto the combustion chamber   so that the combustion chamber side panel return is inside   the section rear lip.   GENERAL   The installation of the boiler must be in accordance with current   Gas Safety (Installation and Use) Regulations or rules in force,   building regulations, I.E.E. (BS.7671) Regulations and the bye-   laws of the local water undertaking. It should also be in accordance   with the relevant British Standard Codes of Practice together with   any relevant requirements of the local gas supplier and local   authority.   6. Locate a slotted steel ring and an ‘O' ring seal into each of   the 4 ports. It will be necessary to squeeze the steel ring   slightly to enable it to be pushed fully into the recess.   7. Lift a middle section onto the combustion chamber and   carefully offer it up to the end section until it engages the   projecting steel rings. It may be necessary to use a mallet   and hardwood block to ensure that the steel rings are   pushed fully into the recessing and that the sections are   butted up to each other.   ASSEMBLY   The combustion chamber should be positioned as near as possible   to the installation site.   Note. Until the final section is fitted and the tie rods   fastened, the sections in the assembly are not fixed   together therefore CARE MUST BE TAKEN TO PREVENT   the installed sections coming apart.   IMPORTANT.   It must be remembered that the boiler distribution tube has to be   fitted into the rear return tapping of the assembled boiler before   final siting.   8. Repeat the assembly procedure for all of the sections until   complete.   Prior to assembling the sections it will be necessary to remove the   manifold assembly and burners from the combustion chamber. To   do this:   9. Fit the 4 tie rods through the holes in the sides of the end   sections and fit a flat steel washer, a shakeproof washer   and a nut to both ends of each tie rod. Screw up all the   nuts equally, in turn and, finally, tighten them to a torque of   38-41 Nm (28-30 lb. ft).   1. Undo the two M5 screws and washers securing the spark   generator bracket to the combustion chamber. Undo the union   securing the gas valve assembly and remove the gas valve   and spark generator assembly from the boiler.   10. For open vented systems a site test must be carried out at   a hydraulic pressure equal to 1 1/2 times the design   pressure given in Table 2, for a period of 30 minutes.   2. Undo the 4 nuts securing the burner manifold to the combustion   chamber legs.   3. Undo the nuts securing the burner light back shield to the   Note. If it is a sealed system the hydraulic pressure must   combustion chamber and lift it off.   be equal to twice the given design pressure for 30 minutes.   4. Pull the whole burner assembly forward on its runners, ensuring   that no wires are trapped, and remove it completely from the 11. Fit the 4 coach bolts into the lugs at the bottom of the end   combustion chamber.   sections and through the hole in the retaining angle of the   combustion chamber.   Fit a flat washer and nut and secure the section assembly   to the combustion chamber.   PREPARATION OF SECTIONS   Each section should be brushed clean on all external surfaces   and any debris which may have accumulated within the sections   should be removed via the bottom ports.   Concord CXSi/H - Installation & Servicing   11   Download from Www.Somanuals.com. All Manuals Search And Download.   INSTALLATION   7 BOILER SECTION ASSEMBLY - continued   12. Offer the downdraught deflector to the projecting studs at the   back of the combustion chamber and fix, using the nuts and   washers provided.   13. Fit the insulation brackets with the screws provided to the   downdraught deflector.   14. Refit the burner assembly to the combustion chamber and   tighten the 4 nuts securing the burner manifold to the   combustion chamber legs. Offer up the burner light back   shield to the combustion chamber - with the cutout for the   flame detector electrode at the LH end - and fasten, using   the M5 nuts and washers.   spark generator bracket to the combustion chamber   using the two M5 screws and washers.   15. Fit the gas valve and spark generator assembly to the boiler   by doing up the union in the gas line and by fastening the   16. Fit the gas inlet pipe and retain by the semi-circular   clamp, screws and washers provided. Tighten both   unions and the inlet pipe retaining clamp, ensuring   that the gas valve assembly is vertical.   17. To fit the collector hood align the back edge of the   horizontal side returns with the rear of the section   assembly and fasten down the collector hood (using   the M6 screws and nuts provided) through the side   fixing points.   18. Wrap the insulation around the heat exchanger with   the foil outside, tuck behind the insulation brackets   on the downdraught deflector and fasten at the edge,   using the foil tabs and tape provided.   19. Fit the NOx ducts into the burner aeration intakes   and fasten to the collector hood, using the M5   elongated nuts.   Note.   The insulation MUST be behind the NOx ducts (it will be   compressed behind the ducts.)   Concord CXSi/H - Installation & Servicing   12   Download from Www.Somanuals.com. All Manuals Search And Download.   INSTALLATION   8 BOILER ASSEMBLY   1. Fit the distributor tube into the selected return connection.   5. Complete the system connections (using suitable jointing   compound) as follows:   Ensure that the tube flange aligns horizontally and that the   2 sealing gaskets are correctly assembled on the tube -   refer to alignment notches.   The cast iron flow header must be fitted in the chosen   flow connection which will be either of the 2 top rear   tappings. A length of 2" BSP pipe is contained in the   Plateware Package for this purpose.   Fit the flow header so that the 1 1/2" vent tapping in the   header is vertical. Screw the thermostat pocket into one   of the 1/2" tappings.   The other 1/2" tapping is used for the pressure gauge   provided. The flow header terminates in a 2 1/2" flange   connection.   The 1 1/2" BSP tapping on the top of the flow header is   for a vent pipe ONLY and MUST NOT be used for any   other purpose.   A safety valve may be fitted in the remaining top rear   tapping, in accordance with CP332:3.   The unused top rear tapping may be used as an   alternative and independent open vent / safety pipe   connection. The LH front bottom tappings may be used   for an independent cold feed / expansion pipe   connection.   Fit the 2" tapped flange, using the M10 x 35mm screws and   washers provided.   2. Fit the blank flange to the other lower rear connection,   using the gasket and M10 x 25mm screws and washers   provided.   In order to avoid air locks, reduction in pipe sizes should   be made in the vertical plane or eccentric bushes used.   3. Fit the blank flange to the RH front connection, using the   gasket and M10 x 25mm screws provided.   Finally , plug the unused tappings, using the 2" BSP   plugs supplied.   4. The 1 1/4" tapped flange and gasket should be fitted to the   LH front connection with the reducing bush and 1/2" drain   cock. If the cold feed/expansion pipe is to be brought   directly to the boiler, the close taper nipple and 1 1/4" tee   must be fitted so that the drain cock is horizontal. This will   reduce the possibility of the drain becoming blocked by   debris.   10 GAS CONNECTION   9 FLUE CONNECTION   1. Complete the secondary flue connection.   Connect the gas supply to the gas inlet pipe - Table 2 gives   details of the inlet pipe size.   The boiler is designed to accept flues to BS.835. If a   suitable adaptor is used then flues to BS715 may be fitted.   The use of an approved gas cock and union is   recommended here.   2. Seal with an approved boiler putty.   3. A split socket should be fitted immediately above the   boiler to facilitate disconnection of the flue.   Concord CXSi/H - Installation & Servicing   13   Download from Www.Somanuals.com. All Manuals Search And Download.   INSTALLATION   11 CASING ASSEMBLY   4 3 Legend   2 1. Side panel.   2. Supporting angle.   3. Top panel.   5 1 4. Upper front panel.   5. Control box.   6. Bracket.   6 7 7. Support frame.   8. Door panel.   9. Lower panel.   8 9 1. Fit the support angle to   the collector hood and   fasten, using the M5   screws and washers.   2. Fit the front fixing   bracket(s) to the collector   hood and fasten, using the   M5 screws and washers   through the slotted holes.   3. Fit one side panel over its   brackets on the   combustion chamber base   tray and fasten to the   support angle, using the   M5 screw and washer.   Repeat for the other side   panel.   4. Fit the upper front support   framework with the   overheat thermostat at the   bottom and with its green   button facing to the RH side and secure to the   front fixing bracket(s), using the M5 screws and   washers, and to each side panel, using the No.8   screws.   Insulation not shown   5. Fit the 4 shoulder screws into the fixings at the   bottom of the front return of the casing side   panels.   6. Finally, ensure correct alignment by slackening   and retightening the screws into the slotted holes   in the front fixing bracket(s).   Overheat 'stat reset button   Concord CXSi/H - Installation & Servicing   14   Download from Www.Somanuals.com. All Manuals Search And Download.   INSTALLATION   12 CONTROL BOX   1. Make the 3 electrical connections from the overheat   thermostat (fixed to the upper front framework) to the   terminals marked 'Limit Stat' on the electrical plug-in   connector from the gas valve plug lead assembly, as   follows:   N/C   N/O   C C Pink   N/O Red   N/C White   Ensure that the lead is securely fastened under the   strain relief clamp - but bring the earth wire outside   the clamp before tightening   2. Unpack the control box. Fit the plug-in connector   from the gas valve plug lead assembly to the bottom   box at the back of the control box and fasten, using   the M4 screws and washer.   3 3. Fit the control box to the support frame and fix   to the bottom, using the 2 self-tapping screws   provided.   4. Fit the earth connections from the terminal   plug-in connections to the appropriate earth   posts on the back of the control box. Connect   the earth lead prefitted to the control box back   panel to the threaded hole in the casing support   frame.   IMPORTANT   5. Offer up the spark generator assembly to the   combustion chamber base tray and secure the   bracket, using the M5 screws and washers.   Plug the spark generator leads onto the spark   electrode connections on the RH end burner -   access via the side of the combustion chamber.   Con 1468   6. Ensure the electrical cover is correctly fastened   to the spark generator.   Flame detector lead   Electrical cover   5 Spark   generator   leads   6 2 push-in   connections   Concord CXSi/H - Installation & Servicing   15   Download from Www.Somanuals.com. All Manuals Search And Download.   INSTALLATION   13 CONTROL BOX - continued   7. Run the flame detector lead through the clips on the   front of the combustion chamber base tray and plug it   into the flame detector electrode on the LH end burner.   Ensure that any slack is tucked neatly into the clips   then fasten the clips.   NOx duct   8. Unstrap the thermostat sensor lead and run both the   sensor and the overheat thermostat phial through the   clips on the appropriate casing side panel to the flow   header, ensuring that both leads run under the support   angle.   Flame   detector   9. Secure both phials into the thermostat pocket in the   7 flow header, using the spring clip.   LH Burner   8 9 Spring clip   Overheat thermostat capillary   Control thermostat lead   Thermostat pocket   Earth connections   10   10. Fit the earth connections from the   terminal plug-in connections to   the appropriate earth posts on the   back of the control box. Connect   the earth lead prefitted to the   control box back panel to the   threaded hole in the casing   support frame.   11. Fit the casing upper front panel   with its location buttons in the   slots and push down to locate.   Fasten at the bottom, using the   No.8 screws.   GV1 & GV2 & o/heat   thermostat earths   12. Fit the casing lower front panel by   locating its slots over the   shoulder screws in the side   panels and pushing down to   locate.   Con 1917   Concord CXSi/H - Installation & Servicing   16   Download from Www.Somanuals.com. All Manuals Search And Download.   INSTALLATION   14 ELECTRICAL CONNECTIONS   The boiler can be controlled either by volt-free external contacts   connected between terminals X1 and X2 or by a switched   live supply brought to X2 (after removal of the factory-fitted   link between X1 and X2), accompanied in each case by a   permanent live supply to terminal L1.   To gain access to the inside of the control box remove   the 2 M4 screws, lift up the plastic front panel and   lower.   Connection must be made in a way that allows   complete isolation of the electrical supply - such as   a double pole switch, having a 3mm (1/8") contact   separation in both poles, or a plug and socket serving   only the boiler and system controls. The means of   isolation must be accessible to the user after   installation.   If a separate frost thermostat is fitted it must be wired   across the time switch contacts and if frost is likely the   system should be turned off using the time switch settings   - all other controls including the boiler thermostat knob   should be in the normal running position.   The earth connections MUST NEVER be omitted.   This should serve only the boiler, together with its   controls and pumps. The unswitched live supply,   which the boiler requires to allow the pump overrun   facility to operate, should be controlled by the above   switched/fused supply, but should connect from there   directly to the boiler and not via any automatic time   or temperature controls.   Wire the earths as shown in Frame 13.   All wiring between entry at the rear of the boiler and the   connection box must be secured neatly under the cable   clips provided.   Wiring must never be allowed to come into contact with   the hot boiler body.   The switched live supply should be subject to control   by time and temperature controls in the usual way.   If a flow switch is fitted, it should be wired between F1 and   F2 on the terminal plug-in connection on the bottom box   at the rear of the control box.   The controls incorporate a pump overrun facility, which   is necessary to dissipate residual heat on plant   shutdown. It is essential therefore that the main pump   (and shunt pump if fitted) is wired to the pump   terminals marked L2, N and Earth on the plug-in   terminal strip on the top box at the rear of the control   box.   Do not wire these connections in conduit up to the boiler   as this will make it impossible to remove the control box   for servicing or maintenance.   Finally, fit the casing top panel and push down to locate.   The main supply to the boiler must be wired to the   boiler terminals L1, N and Earth on the plug-in   terminal strip. This live connection must be   UNSWITCHED, that is a supply not interrupted by   any automatic temperature or time control, to enable   the pump overrun (and the frost protection facility) to   operate.   Failure to operate this procedure will result in nuisance   overheat thermostat operation.   The internal wiring of the boiler control box is shown   in Frame 15.   Wiring should be in four core PVC insulated cable,   not less than 0.75mm2 (24/0.2mm). All fuses must   be ASTA approved to BS. 1362.   The length of the conductor between the cord   anchorage and the terminals must be such that the   current carrying conductors become taut before the   earthing conductor, if the cable or cord slips out of the   cord anchorage.   Concord CXSi/H - Installation & Servicing   17   Download from Www.Somanuals.com. All Manuals Search And Download.   INSTALLATION   LEGEND   15 INTERNAL WIRING   b blue   br brown   red   y/g yellow/green   or orange   y yellow   v violet   bk black   r w white   pk pink   BLUE   YELLOW   PINK   RED   RED   ORANGE   BLUE   O R A N   W H I T E   B L A C K   BROWN   WHITE   RED   YELLOW   BK   E L E C T R O D E   D E T E C T I O N   WHITE   VIOLET   ORANGE   ORANGE   BLUE   BLUE   GREY   YELLOW   DETECTION LEAD   YELLOW/GREEN   2 X YELLOW   2 X RED   2 X VIOLET   CONTACT REMOVED AND   FITTED TO MATING HALF   Concord CXSi/H - Installation & Servicing   18   Download from Www.Somanuals.com. All Manuals Search And Download.   INSTALLATION   16 ZONES WITH BI-DIRECTIONAL MOTORISED VALVES   IMPORTANT   Terminal L2 may control the appropriate   pump(s) directly, provided that the total   running or starting current does not   exceed 6A (resistive or inductive): if this   rating would be exceeded, then   appropriate switchgear must be used to   control the pumps indirectly.   Three zones are illustrated but the   principles may be extended as required,   provided the above conditions are met.   Each relay will then require as many   contacts as there are zones.   Overrun   Since any zone may be the load during   overrun, all zones MUST individually be   able to satisfy the conditions in the   foregoing paragraph. If not all zones can   do this then consider other means of   control, detailed on other sheets.   Normal operation   When any thermostat is satisfied while   others are calling for heat, power is   available via relay contacts to close the valve for that zone.   At the start of the next call for heat (or the next clock period)   valves on zones not calling for heat will motor shut.   When all thermostats are satisfied (also when the clock period   ends) all relays will be off, so the zone valves which were open   will remain open for the pump overrun period.   Water circulation system - refer to page 5   17 ZONES WITH INDIVIDUALLY PUMPED ZONES (3 zones shown)   IMPORTANT   Terminal L2 may control the appropriate pump(s)   directly, provided that the total running or starting   current does not exceed 6A (resistive or   inductive): if this rating would be exceeded then   appropriate switchgear must be used to control   the pumps indirectly.   Three zones are illustrated but the principles may   be extended as required, provided the above   conditions are met. For each zone (except Zone   1) a relay with 2 C/O contacts is required.   Overrun   During overrun periods, Zone 1 pump performs   the overrun facility; this zone, therefore, must   satisfy the conditions in the foregoing paragraphs   and Graph 1.   Normal operation   During a call for heat on Zone 1 only, Zone 1   thermostat energises the boiler, which in turn   energises Zone 1 pump from terminal L2.   During a call for heat on other zones the   appropriate relay directs power to L1 to energise   the boiler, at the same time ensuring that Zone 1   pump is controlled by Zone 1 thermostat.   Water circulation system - refer to page 5   Concord CXSi/H - Installation & Servicing   19   Download from Www.Somanuals.com. All Manuals Search And Download.   INSTALLATION   18 ZONES WITH SPRING-RETURN MOTORISED VALVES   IMPORTANT   Terminal L2 may control the appropriate   pump(s) directly, provided that the total   running or starting current does not exceed   6A (resistive or inductive): if this rating would   be exceeded then appropriate switchgear   must be used to control the pumps indirectly.   X2   Three zones are illustrated but the principles   may be extended as required, provided the   above conditions are met. Only one relay is   required, irrespective of the number of zones.   Overrun   During overrun and dormant periods, Zone   Valve 1 is held open. This zone, therefore,   MUST satisfy the conditions in the foregoing   paragraphs and Graph 1.   Normal operation   During a call for heat on Zone 1 only, the   boiler energises via Zone 1 thermostat and   the normally closed contacts of the relay.   During a call for heat on other zone(s), the   relay will be energised by the auxiliary switch   on the zone valves. This provides power to   energise the boiler. If, in addition, Zone 1 now   calls for heat, its thermostat will open Zone 1   valve via the normally open contacts of the   relay.   When the clock period ends, Zone valve 1 will (stay) open via   normally closed relay contacts to achieve pump overrun.   Water circulation system - refer to page 5   19 COMMISSIONING AND TESTING   GENERAL   TESTING FOR GAS SOUNDNESS   Check that all drain cocks are closed, that any stop valves   fitted to the flow and return pipes are open and that the   system has been filled and properly vented.   Close the gas supply cock at the meter.   Remove the screw in the inlet pressure test point, Frames   20/21, and connect a gas pressure gauge to the test point.   Take particular care to ensure a gas-tight connection. Open   the gas supply cock at the meter and the appliance gas   cock; record the static pressure. Next, close the gas supply   cock at the meter. Wait for 1 minute for temperature   stabilisation then observe the pressure gauge over a period   of 2 minutes.   PURGING   Check that the electricity supply is switched OFF.   Remove the casing lower front panel.   Extinguish all naked lights and open all doors and windows.   DO NOT SMOKE. Check that the gas supply is turned ON at   the meter and open the main gas inlet cock. Loosen the   union and allow air to be purged from the gas line until gas is   smelled. Refer to BS 6891 or IGE-UP-1 for further details.   Retighten the union .   Any leaks must be cured.   Replace all pressure test point screws.   Concord CXSi/H - Installation & Servicing   20   Download from Www.Somanuals.com. All Manuals Search And Download.   INSTALLATION   20 INITIAL LIGHTING   1. Check that the boiler thermostat knob (1) on the control   7. The boiler will light at Low rate and the Boiler-on light (5)   will be illuminated. If it does not light the Lockout light (6)   will be illuminated. Press in and release the Lockout   button (7). The controls will reset and attempt to relight.   box (2) is OFF.   2. Ensure that the mains gas inlet cock (3) is open (groove   in the square head in line with the gas pipe).   8. The burner will remain at Low rate for about 1 minute   3. Press in and release the overheat thermostat button (4).   4. Switch on the electrical supply to the boiler.   before going to High rate.   9. Check all connections for gas soundness, using leak   detection fluid.   5. Ensure that all system controls (time switch, system   controls etc.) are calling for heat.   10. Set the boiler thermostat knob and the system controls to   the required settings.   6. Turn the boiler thermostat knob (1) to position 6.   11. Turn off the electrical supply to the boiler.   7 5 1 LEGEND   1. Boiler thermostat knob.   2. Control box.   OFF   BOILER ON   6 C 3. Mains inlet gas cock.   4. Overheat thermostat .   5. Boiler on light.   OVERHEAT   5 C O N C O R D CXSi   LOCKOUT   4 1 3 2 6. Lockout light.   7. Lockout reset button.   8. Burner pressure test point.   9. Inlet pressure test point.   10. Overheat light.   6 10   11. High/low gas valve   2 11   9 3 4 8 Concord CXSi/H - Installation & Servicing   21   Download from Www.Somanuals.com. All Manuals Search And Download.   INSTALLATION   21 MANIFOLD GAS PRESSURE - CXSi 110/H-160/H ONLY   The manifold setting pressure must now be   checked and adjusted as necessary. It is   essential to set the High Pressure first   Start the adjustment procedure with the   system cold, on full load and with all   temperature controls set to maximum to   avoid thermostatic shutdown. Remove the   screw in the burner setting pressure test   point and connect a suitable gas pressure   gauge.   Turn on the electrical supply to light the   boiler and let it operate for about 10 minutes   to stabilise the burners. Check the pressure   and if it differs noticeably from that given in   Table 1 for the appropriate boiler size adjust   it as follows:   SETTING THE HIGH BURNER PRESSURE   SETTING THE LOW BURNER PRESSURE   5. Turn the boiler thermostat knob to OFF.   1. Remove the dust cover from the adjustment screw in   the bottom valve and gently screw the adjustment in   fully.   6. Disconnect the 'high' solenoid plug from the top valve.   7. Disconnect the LH electrical plug from the bottom valve.   2. Remove the plastic dust cover from the adjustment   screw on the top (high/low) valve and, using a spanner,   screw the adjuster gently fully in then screw the adjuster   out until the burner pressure is approximately 10.9 mbar.   8. Turn the boiler on and set the low pressure to the value   given in Table 1, using the low rate adjustment screw inside   the spindle of the top valve.   3. Finally, screw out the adjustment on the bottom valve   until the burner pressure is correctly set to the value   given in Table 1.   9. Turn the appliance off and reconnect all the electrical plugs.   Do not overtighten the electrical plug fixing screws.   10. Refit both dust covers over the adjustment screws and refit   4. After setting, allow the boiler to operate for 3 minutes to   the pressure test point screw.   stabilise then recheck the setting.   11. Check for gas soundness.   Concord CXSi/H - Installation & Servicing   22   Download from Www.Somanuals.com. All Manuals Search And Download.   INSTALLATION   22 MANIFOLD GAS PRESSURE - CXSi 180/H ONLY   The manifold setting pressure must now be   checked and adjusted as necessary. It is   essential to set the High Pressure first   Inlet PTP   Start the adjustment procedure with the   system cold, on full load and with all   temperature controls set to maximum to avoid   thermostatic shutdown. Remove the screw in   the burner setting pressure test point and   connect a suitable gas pressure gauge.   Turn on the electrical supply to light the boiler   and let it operate for about 10 minutes to   stabilise the burners. Check the pressure and   if it differs noticeably from that given in Table 1   for the appropriate boiler size adjust it as   follows:   5 Dust cover   3 Remove plastic   dust cover   Low rate   adjustment   screw   Gas rate   adjuster   maximum   High solenoid plug   IMPORTANT. Do not adjust the middle valve, which is factory set.   SETTING THE LOW BURNER PRESSURE   SETTING THE HIGH BURNER PRESSURE   7. Turn the boiler thermostat knob to OFF.   1. Turn the boiler thermostat knob to OFF.   8. Disconnect the 'high' solenoid plug from the top valve.   2. Undo the screws holding the electrical plug on the bottom gas   valve and pull it off.   9. Disconnect the electrical plug from the bottom and middle   valves.   3. Turn the boiler on and remove the plastic dust cover from the   adjustment screw on the top gas valve and, using a suitable   spanner, screw the adjuster gently fully in. Then screw the   adjuster out until the burner pressure is approximately 9.0 mbar.   10. Turn the boiler on and set the low pressure to the value   given in Table 1, using the low rate adjustment screw   inside the spindle of the top valve.   4. Turn the boiler off and refit the electrical plug on the bottom   11. Turn the appliance off and reconnect all the electrical   valve.   plugs.   5. Turn the boiler on and remove the dust cover from the adjustment   screw in the bottom valve. Set the burner pressure to the value in   Table 1.   12. Refit both dust covers over the adjustment screws and   refit the pressure test point screw.   13. Check for gas soundness   6. After setting, allow the boiler to operate for 3 minutes to stabilise   then recheck the setting.   Concord CXSi/H - Installation & Servicing   23   Download from Www.Somanuals.com. All Manuals Search And Download.   SERVICING   24 TESTING   23 SPILLAGE CHECK   Check the main burner responds correctly to manual on/off operations of any controls fitted in   the gas control circuit.   Check that there is no spillage   of combustion products from   the boiler draught diverter by   carrying out a spillage test, as   detailed in BS. 5440:1.   Check the operation of the flame failure safety system by lighting the boiler and then turning   the gas inlet cock off.   The Burner On light will go out and the controls will try to relight the boiler. After a period of   about 5 seconds, the Lockout light will be illuminated.   Turn on the gas cock again and press in and release the Lockout button. The boiler will   relight.   Complete the Commissioning section of the boiler log book.   Important Commissioning / Operating Instructions:   Do not operate this appliance for long periods or take any combustion readings with the   casing or any part of the casing removed.   25 ADJUSTMENT OF WATER FLOW RATE THROUGH THE BOILER   When commissioning the heating/domestic hot water system the shunt pump must be   adjusted to give the minimum flow rate given in Table 4, when that part of the system   intended to be used for dissipation of residual heat only is in operation.   26 HANDING OVER   Hand over these, the User’s Instructions and the Commissioning &   Servicing Log Book to the customer and request him to keep them in   a safe place for ready reference.   ROUTINE OPERATION   Full instructions covering routine lighting and operation of   the boiler are given on the Lighting and Operation   Instruction Label located on the inside of the casing door.   IMPORTANT. Point out to the owner that the boiler must have   regular maintenance and cleaning, at least annually, in order to   ensure reliable and efficient operation. Regular attention will also   prolong the life of the boiler and should preferably be performed at   the end of the heating season.   Draw the attention of the boiler owner or their   representative to the Lighting and Operating Instruction   Label on the inside of the front panel. Give a practical   demonstration of the lighting and shutting down of the   boiler.   After servicing, complete the service section of the log book and   return it to the owner or their representative.   Describe the function of the boiler and system controls and   show how they are adjusted and used.   Recommend that a contract for this work should be made with a   CORGI registered installer.   Concord CXSi/H - Installation & Servicing   24   Download from Www.Somanuals.com. All Manuals Search And Download.   SERVICING   27 SERVICING   Caradon Ideal Limited does not accept any liability resulting   from the use of unauthorised parts or the repair and servicing   of appliances not carried out in accordance with the Company’s   recommendations and specifications.   A comprehensive service should be carried out at least once a   year. The User is advised to make a contract with a CORGI   registered installer.   WARNING. ALWAYS turn OFF the gas supply at the gas cock   and disconnect the electricity supply to the appliance BEFORE   servicing or replacing any components.   If access is required to the electrical plug-in terminals at the   back of the control box then remove the casing top panel; it is   not advisable to try and remove the control box back panel   from the boiler with the plugs in place.   CLEANING THE BOILER   Remove the casing door panel. Lift and remove the casing lower   front panel. Undo and pull off all the plugs from the gas valve   solenoids. Turn off the gas at the gas inlet cock. Undo the 2   unions at either side of the gas valve assembly and remove   the assembly complete.   If available, an industrial vacuum cleaner may be useful to assist in   this work. When cleaning the burner bars, take care to avoid damage   from rough handling to the ignition or detection electrodes.   Pull off the leads to the spark electrode on the RH end burner   - access via the side of the combustion chamber. Pull off the   lead to the flame detector electrode at the LH end burner.   Inspect the ignition and detection electrodes.   Ensure that they are clean and in good condition. In particular, check   that:   Lift off the casing top panel. Undo the 3 elongated nuts from   each of the NOx ducts and remove all the ducts. Undo the M5   nuts and washers retaining the burner light back shield and   remove it. Undo the four M6 nuts and washers securing the   burner tray and carefully pull it from the boiler, ensuring that no   wires are trapped. Undo the screws securing the cleanout   cover(s) and remove.   1. The ignition electrode shield and base fixing screws are tight.   2. The electrodes are correctly positioned .   3. Check that the gap between the electrode tips is 4mm.   Remove all loose deposits from the heat exchanger (especially   from between the fins), using the brush provided, and remove   all debris from the combustion chamber floor - take care not to   damage the insulation.   4. Reassemble in reverse order. Ensure that no wires are   trapped when replacing the burner tray. Refit the flue baffles,   cleanout cover, light back shield, NOx ducts, electrode   connections and casing panels.   When refitting the plugs to the gas valve solenoids do NOT   overtighten the fixing screws.   Examine the burner assembly. Clean the burner bars by   brushing them down with a stiff bristle (not wire) brush. Check   each bar carefully to ensure that all flame ports are   clear, that there are no cracks and that all surfaces   are free from accumulated deposits.   LH burner   Concord CXSi/H - Installation & Servicing   25   Download from Www.Somanuals.com. All Manuals Search And Download.   SERVICING   28 REPLACEMENT OF COMPONENTS - Refer to Frames 5, 31 and 32   GENERAL   WARNING. ALWAYS turn OFF the gas supply at the gas inlet cock and switch OFF   and DISCONNECT the electricity supply BEFORE working on the appliance.   29 GAS CONTROL VALVE   30 MAIN BURNER   1. Undo and pull off all the plugs from the gas valve solenoids.   1. Remove the burner tray from   the boiler, as described in   Frames 27-28.   2. Turn off the gas at the gas inlet cock. Undo the 2 unions at either side of the gas valve   assembly and remove the assembly (complete) to a suitable working area.   2. Each burner can be removed   by lifting it at the back and   pushing it backward to clear   the injector. Disconnect the   spark electrode assembly and   heat shield from the RH   3. In order to be able to remove the faulty gas valve it will be necessary to slacken or   remove all the screws on either the inlet or the outlet manifold and only those 4 screws   securing the faulty gas valve on the other manifold. The faulty gas valve can then be   removed and replaced. Ensure that the arrow on the gas valve points in the direction   of flow.   burner (or the flame detector   electrode from the LH burner),   as necessary.   4. Ensure that new ‘O’ ring seals are fitted and that the 'O' ring seals on the remaining   gas valves are correctly in place. Ensure that all screws are retightened.   5. Test for gas soundness.   3. Reassemble in reverse order.   6. Recommission the appliance and set the manifold pressure, as described in Frame 21.   31 BURNER AND CONTROLS ASSEMBLY - Exploded View - CXSi 110/H - 160/H   LEGEND   10. Main burner RH.   7. Burner manifold.   8. Main injector.   1. Main gas inlet cock.   2. Gas inlet union.   3. 'O' ring seal.   4. High/Low gas control valve   5. Gas control valve.   11. Ignition electrodes.   12. Detection electrode assembly.   PTP Pressure test point.   9. Main burner - LH.   6. Spark generator.   Concord CXSi/H - Installation & Servicing   26   Download from Www.Somanuals.com. All Manuals Search And Download.   SERVICING   32 BURNER AND CONTROLS ASSEMBLY - Exploded view - CXSi 180/H   LEGEND   10. Main burner (RH).   1. Main gas inlet cock.   2. Gas inlet union.   3. 'O' ring seal.   7. Burner manifold.   8. Main injector.   4. High/low gas control valve.   5. Gas control valve.   11. Ignition electrodes.   12. Detection electrode assembly.   PTP Pressure test point.   9. Main burner - LH.   6. Spark generator.   33 OVERHEAT THERMOSTAT   1. Pull out the spring clip in the thermostat pocket in the flow   header and pull out the overheat thermostat phial and   capillary.   2. Ensure that the electrical supply is switched OFF.   3. Lift off the casing front panel and top panel.   4. Unclip the capillary from its clips on the casing side panel.   5. Undo the 2 screws securing the overheat thermostat   assembly and withdraw the assembly.   6. Undo the screw and remove the cover.   7. Remove the wires   8. Undo the backnut and remove the thermostat.   9. Fit the new thermostat and secure with the backnut.   10. Reconnect the wires as follows:   11. Reassemble in reverse order.   12. Ensure that the thermostat capillary is rerouted through the   casing side panel clips and that the phial is secure in the   pocket fitted to the flow header, using the spring clip.   1. Pink   2. White   3. Red   Reconnect the earth terminal.   Concord CXSi/H - Installation & Servicing   27   Download from Www.Somanuals.com. All Manuals Search And Download.   SERVICING   34 CONTROL BOX - Basic Boiler, Exploded View   1 2 Printed circuit board support detail   6 5 12   3 7 2 1 4 8 10   11   9 LEGEND   1. Wiring clamp.   5. Terminal strip   9. Potentiometer   2. Connection box plug.   3. Connection box.   4. PCB S456B1047   6. Back panel   10. Warning light lens   11. Controls box   7. Lockout reset button   8. Thermostat knob   12. PCB W 4115A1020   35 CONTROL SENSOR   1. Lift off the casing top panel and front panel.   2. Trace the sensor lead to the pocket in the flow header,   remove the spring clip and remove the sensor phial.   3. Undo and remove the 2 screws securing the control box   front panel. Carefully lift up and lower it.   4. Pull out the sensor plug from the PCB and remove the   strain relief bush. Remove the sensor and lead.   5. Fit the new sensor, ensuring that the lead is routed along   the casing in the clips provided.   6. Reassemble in reverse order.   Concord CXSi/H - Installation & Servicing   28   Download from Www.Somanuals.com. All Manuals Search And Download.   SERVICING   36 CONTROL SENSOR POTENTIOMETER ASSEMBLY   1. Prise the front cap from the thermostat knob.   PCB   Plug   2. Carefully loosen the brass retaining nut one full turn   anticlockwise   3. Gently pull the thermostat knob from the potentiometer. When   reassembling ensure the arrow on the body is lined up in the   OFF position.   Backnut   4. Remove the back nut and brass washer securing the thermostat   knob to the panel.   Potentiometer   Thermostat knob   5. Undo and remove the 2 screws securing the control box front   panel. Carefully lift it up and lower it.   6. Remove the terminal plugs from the back of the potentiometer.   Con 1500   7. Undo the purse clips holding the wires from the potentiometer   are made either to the top 2 tags or the bottom 2 tags and that the   lug on the body of the potentiometer locates through the hole in   the front panel of the control box.   to the PCB then pull the wires out.   8. Remove the connections from the PCB.   Also ensure that the potentiometer is rotated fully anticlockwise   and clicks before commencing the reassembling.   9. Fit the new potentiometer and reassemble in reverse order.   Ensure that the connections to the back of the potentiometer   37 PC BOARD S4561B1047   38 PC BOARD W4115A1020   Flame detector connection   Earth connection   Retaining barbs   Plugs   Plugs   Plugs   Retaining   barbs   PCB   PCB   1. Remove the lower front panel.   Con 1910   2. Undo and remove the 2 screws securing the control box front   panel. Carefully lift it up and lower it.   1. Remove the lower front panel.   3. Pull off the 2 plugs and the 2 push-on connections from the   board. The board can now be removed by squeezing in the   retaining barbs.   2. Undo and remove the 2 screws securing the control   box front panel. Carefully lift it up and lower it .   3. Remove the 4 plugs from the board. The board can now   4. Fit the new board and reassemble in reverse order, ensuring   that the push-on connections are correctly fitted, as follows (from   left to right): Earth - flame detector lead.   be removed by squeezing in the retaining barbs.   4. Reassemble in reverse order.   Prior to removal of the boards the following protective equipment   should be worn:   39 COMBUSTION CHAMBER   INSULATION REPLACEMENT   • • Face mask supplied with the spare part.   Gloves supplied with the spare part.   The insulation boards used in the combustion chambers   of these products contain man-made fibres, refractory   fillers, organic and inorganic binders and as such are   deemed to be harmless to humans.   1 Damp down the combustion chamber area containing the insulation   boards.   2. Remove the insulation boards. The replacement boards are supplied   in a plastic bag. This bag should be retained and the discarded boards   should now be placed into it.   Caradon Ideal Limited, however, recommend that for   your own comfort and to comply with good working   practise the procedure described below is followed.   3. Sweep any dampened particles and place in the plastic bag.   4. Fit new insulation boards.   IMPORTANT. Turn OFF the gas and DISCONNECT the   electricity supply.   5. Remove the gloves and face mask and place them in the plastic bag.   6. Wash your hands and any areas of skin which may have come into   To replace the insulation boards the major boiler   components (including the heat exchanger and burners)   have to be removed to gain access to the combustion   chamber.   contact with any of the particles from the insulation board.   7. Seal the plastic bag and dispose of it and its contents into a   commercial tip.   Concord CXSi/H - Installation & Servicing   29   Download from Www.Somanuals.com. All Manuals Search And Download.   FAULT FINDING   40 BOILER CONTROL   feature reduces component wear and ensures continuous   trouble free operation. The anti-cycle duration is 4 minutes.   Before attempting any electrical fault finding ALWAYS carry out   the preliminary electrical system checks as detailed in the   Instructions for the British Gas Multimeter or other similar   commercially available meter.   If the system pump, with a maximum current of 3A, is   connected to the boiler pump terminals, pump overrun will be   in operation when the demand for heat is satisfied, and will   continue to run for 6 minutes.   The preliminary electrical system checks are the FIRST   electrical checks to be carried out during a fault finding   procedure.   Frost protection is inbuilt with the boiler. If the flow   temperature falls to approximately 5 oC then the boiler will   operate until the flow temperature exceeds 18 oC. Note that it   is designed to protect the boiler and may not protect remote   parts of the system. Neither the pump overrun nor the inbuilt   frost protection will operate if the boiler thermostat is switched   OFF.   On completion of any service/fault finding task which has   required the breaking and remaking of electrical connections   the following checks MUST be repeated:   a. Earth continuity   b. Polarity   The gas valves operate on High/Low and Off principle. The   boiler will start at low rate and after 1 minute the high rate gas   valve will open. On reaching the set point, determined by the   user, the boiler will go to low rate and when the temperature   reaches the set point plus 3 oC the low rate gas valve will   close. Should the temperature fall below the set point the   boiler will go back to the high rate.   c. Resistance to earth   Detailed instructions on the replacement of faulty components   are contained in the 'Servicing' section of these Installation &   Servicing Instructions.   GENERAL INFORMATION   The full sequence control enables a single ignition attempt   lasting about 5 seconds and will go to lockout if detection   does not take place.   Anti-cycle will be in operation each time the boiler thermostat is   satisfied and a rapid demand for heat is required. The same   situation will occur if the external controls operate rapidly. This   41 SIMPLE FLOW CHART   OF OPERATION   SHUTDOWN   Demand = ON   IGNITION   Overrun   completed   Flame = ON   Temp   > than   set point   LOW RATE   HIGH RATE   Temp at   set point   Demand   = off   PUMP OVERRUN   (6 minutes)   4 minutes anti-cycle   Concord CXSi/H - Installation & Servicing   30   Download from Www.Somanuals.com. All Manuals Search And Download.   FAULT FINDING   Before carrying out any Fault Finding, ensure that all internal controls are calling for heat and that the overheat thermostat has not   operated. There should be 230V ± 10% available at the control box connection.   42 BOILER DOES NOT LIGHT   NO   Is the spark gap approximately 4mm and are the   electrodes, leads and connections clean and secure?   Is there a spark at the electrode?   YES   YES   Are the gas valve electrical plugs clean and secure?   YES   Is there 230V ± 10% at the spark generator   NO   YES   Is there 230V ± 10% at the gas valve plugs?   YES   Are connections sound at   the plug-on terminal strip   at the control box?   Replace   spark generator   YES   Is the gas valve inlet pressure sufficient?   YES   Replace   PCB S4561B1047   Replace the gas valve   43 BOILER LIGHTS BUT GOES TO LOCKOUT   Is the flame detector and its lead and connections sound   NO   and secure and correctly positioned on the LH end   Clean and secure   burner?   YES   NO   Check LH end burner, inlet and burner pressure; check   the LH end burner injector   Measure the flame current - expect approximately 3.5µA   YES   Replace PCB S4561B1047   44 BOILER GOES OUT ON OVERHEAT THERMOSTAT   Is there an unswitched Live supply to terminal L1 on   the plug-on terminal connection at the control box?   YES   NO   Is there sufficient open circuit water volume or load   Refer to Installation Instructions for details   available on boiler shutdown for the pump overrun?   YES   Is the pump (or shunt pump) wired to terminal L2   in the control box?   YES   NO   Has the boiler thermostat knob been switched to OFF?   Replace PCB W4115A1020   YES   Advise USER   Concord CXSi/H - Installation & Servicing   31   Download from Www.Somanuals.com. All Manuals Search And Download.   SHORT LIST OF PARTS   When ordering spare parts please quote:   The following are parts commonly required as   replacements, due to damage or   expendability.   1. Boiler model   2. Boiler serial no. (refer to the data plate on the combustion chamber)   3. Boiler P.I. No. (refer to the data plate on the combustion chamber)   Their failure or absence is likely to affect the   safety and/or performance of this appliance.   4. Description   5. Quantity   6. Product no.   When replacing a part on this appliance, use only spare parts that you can be assured conform to the safety and performance   specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers.   Key No.   Description   Qty.   Product No.   Gas valve   28   HONEYWELL VR4605PB2003   CXSi 110/H, 120/H, 140/H, 160/H & 180/H   CXSi 110/H & 120/H   1 1 2 1 111 867   138 896   138 896   111 869   28.1   HONEYWELL VR4605A 1104   HONEYWELL VR4605A 1104   HONEYWELL VR4605AB 1019   CXSi 180/H   28.2   CXSi 140/H & 160/H   28.3   28.4   28.5   28.6   28.7   Plug and lead   Plug and lead   Plug and lead   Plug and lead   Plug and lead   CXSi 110/H, 120/H, 140/H, 160/H & 180/H   CXSi 110/H, 120/H, 140/H & 160/H   CXSi 110/H, 120/H, 140/H & 160/H   CXSi 110/H, 120/H, 140/H, 160/H & 180/H   CXSi 180/H   1 1 1 1 2 154 734   139 269   112 431   155 657   111 870   29   31   Spark generator   1 139 300   Injector 4.02 mm diameter   Injector 4.20mm diameter   Injector 4.20mm diameter   Injector 4.20mm diameter   Injector 4.20mm diameter   CXSi 110/H   CXSi 120/H   CXSi 140/H   CXSi 160/H   CXSi 180/H   6 6 7 8 9 013 175   013 180   013 180   013 180   013 180   32   Flame detection electrode   Flame detection lead   1 1 138 895   139 271   32.1   33   Main burners ............... Worgas   Main burners ............... Worgas   Main burners ............... Worgas   Main burners ............... Worgas   CXSi 110/H & 120/H   CXSi 140/H   5 6 7 8 139 824   139 824   139 824   139 824   CXSi 160/H   CXSi 180/H   34   36   Main burner (RH end) . Worgas   Ignition electrode   CXSi 110/H - 180/H   1 1 139 825   112 365   Concord CXSi/H - Installation & Servicing   32   Download from Www.Somanuals.com. All Manuals Search And Download.   SHORT LIST OF PARTS   Key No.   Description   Qty.   Product No.   45   Control box complete   Thermistor   1 1 1 1 155 641   154 816   154 814   154 815   46   47.1   48.1   PCB S4561B1047 (ignition)   PCB W4115A1020 (Aquastat)   56   56   56   56   Casing assembly complete .................................................. CXSi 110/H & 120/H   Casing assembly complete ................................................................ CXSi 140/H   Casing assembly complete ................................................................ CXSi 160/H   Casing assembly complete ................................................................... XSi 180/H   1 1 1 1 157 449   157 450   157 451   157 452   57   57   57   57   Casing front panel ................................................................ CXSi 110/H & 120/H   Casing front panel .............................................................................. CXSi 140/H   Casing front panel .............................................................................. CXSi 160/H   Casing front panel .............................................................................. CXSi 180/H   1 1 1 1 155 647   155 648   155 649   155 650   58   59   Casing LH side panel ...............................................................CXSi 110/H-180/H   Casing RH side panel ..............................................................CXSi 110/H-180/H   1 1 076 978   076 979   60   60   60   60   Casing lower front panel ...................................................... CXSi 110/H & 120/H   Casing lower front panel .................................................................... CXSi 140/H   Casing lower front panel .................................................................... CXSi 160/H   Casing lower front panel .................................................................... CXSi 180/H   1 1 1 1 138 475   138 474   138 473   138 472   61   61   61   61   Casing upper front panel...................................................... CXSi 110/H & 120/H   Casing upper front panel.................................................................... CXSi 140/H   Casing upper front panel.................................................................... CXSi 160/H   Casing upper front panel.................................................................... CXSi 180/H   1 1 1 1 155 643   155 644   155 645   155 646   62   62   62   62   Casing top panel .................................................................. CXSi 110/H & 120/H   Casing top panel ................................................................................ CXSi 140/H   Casing top panel ................................................................................ CXSi 160/H   Casing top panel ................................................................................ CXSi 180/H   1 1 1 1 138 465   138 464   138 463   138 462   63A   78   Overheat thermostat ..................... RAK77.4/3835   Boiler status neons ...............................Boiler ON   Boiler status neons .............. Overheat & Lockout   Lockout reset button assembly   1 1 1 1 155 791   154 854   154 855   155 269   79   80   Concord CXSi/H - Installation & Servicing   33   Download from Www.Somanuals.com. All Manuals Search And Download.   NOTES   Concord CXSi/H - Installation & Servicing   34   Download from Www.Somanuals.com. All Manuals Search And Download.   NOTES   Concord CXSi/H - Installation & Servicing   35   Download from Www.Somanuals.com. All Manuals Search And Download.   Technical Training   The Ideal Boilers Technical Training Centre offers a series of first class training   courses for domestic, commercial and industrial heating installers, engineers and   system specifiers. For details of courses please ring: ..........   01482 498 432   Ideal Boilers P.O. Box 103, National Ave, Kingston upon Hull,   , HU5 4JN. Telephone: 01482 492 251 Fax: 01482 448 858.   Registration No. London 322 137.   Caradon Ideal Limited pursues a policy of continuing   improvement in the design and performance of its products. The   right is therefore reserved to vary specification without notice.   November 2005   UIN 157 294 A03   I deal Installer/Technical Helpline: 01482 498 376   Download from Www.Somanuals.com. All Manuals Search And Download.   |