Goodman Mfg Air Conditioner SS CPC90 150 User Manual

CPC CommerCial  
7½- to 12½-ton three-phase  
paCkaged air Conditioners  
Cooling CapaCity: 90,000 — 118,000 BtU/h  
up to 11.5 EER  
Standard Features  
• R-410A chlorine-free refrigerant  
• High-efficiency scroll compressor  
• Copper tube / aluminum fin coils  
• Contactor with lugs  
• High- and low-pressure switches  
• High-capacity, steel-cased filter dryer  
• Heater kits with single-point entry  
• 24-volt terminal strip  
• Convertible  
• Easy to service  
• Built-in filter rack with standard 2lters  
• Bottom utility entry  
• AHRI Certified; ETL Listed  
Contents  
Nomenclature..................................................................................................2  
Product Specifications................................................................................3  
Airflow Data.......................................................................................................7  
Heat Kit Electrical Data ...........................................................................11  
Expanded Cooling Data..........................................................................16  
Dimensions.....................................................................................................26  
Wiring Diagrams .........................................................................................30  
Accessories......................................................................................................34  
Cabinet Features  
• Heavy-gauge, galvanized-steel cabinet with  
UV-resistant powder-paint finish  
• Full Perimeter Rail  
SS-CPC90-150  
6/11  
Supersedes 3/11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
prodUCt speCifiCations  
prodUCt speCifiCations — 7½ tons  
A Models  
B Models  
CPC090  
XXX3BXXX  
CPC090  
XXX4BXXX  
CPC090  
XXX3BXXX  
CPC090  
XXX4BXXX  
CPC090  
XXX7BXXX  
Cooling Capacity  
Total BTU/h  
90,000  
65,700  
90,000  
65,700  
90,000  
64,000  
90,000  
64,000  
90,000  
64,000  
Sensible BTU/h  
EER / IEER  
11.5 / 11.5  
82.0  
11.5 / 11.5  
82.0  
11.5 / 11.5  
82.0  
11.5 / 11.5  
82.0  
11.5 / 11.5  
82.0  
Decibels  
AHRI Reference #s  
3000986  
3000986  
3620223  
3620223  
3620223  
Evaporator Motor / Coil  
Motor Type  
Belt Drive  
3,000  
Belt Drive  
3,000  
Belt Drive  
3,000  
Belt Drive  
3,000  
Belt Drive  
3,000  
Indoor Nominal CFM  
Indoor Motor FLA (Cooling)  
Horsepower / RPM  
Piston Size (Cooling)  
Filter Size (Qty)  
7.8  
3.9  
5.0  
2.5  
2.3  
2.0 / 1725  
0.076  
2.0 / 1725  
0.076  
1.5 / 1745  
0.078  
1.5 / 1745  
0.078  
1.5 / 1725  
0.078  
(4) 16”x24”x2”  
¾”  
(4) 16”x24”x2”  
¾”  
(4) 16”x20”x2”  
¾”  
(4) 16”x20”x2”  
¾”  
(4) 16”x20”x2”  
¾”  
Drain Size (NPT)  
R-410A Refrigerant Charge Cir #1 & #2  
Evaporator Coil Face Area (ſt²)  
Rows Deep / Fins per Inch  
Belt Drive Evap Fan Data  
# of Wheels (D x W)  
Motor Sheave / Blower Sheave  
Belt  
215 oz.  
10.2  
215 oz.  
10.2  
175 oz.  
8.9  
175 oz.  
8.9  
175 oz.  
8.9  
4 / 16  
4 / 16  
4 / 16  
4 / 16  
4 / 16  
1 (15” x 12”)  
VL40 / AK74  
AX51  
1 (15” x 12”)  
VL40 / AK74  
AX51  
1 (15” x 12”)  
VL40 / AK74  
AX51  
1 (15” x 12”)  
VL40 / AK74  
AX51  
1 (15” x 12”)  
VL40 / AK74  
AX51  
Condenser Fan / Coil  
Quanꢀty of Condenser Fan Motors  
Horsepower - RPM  
Fan Diameter / # Fan Blades  
Outdoor Nominal CFM  
Face Area (ſt²)  
2
2
2
2
2
¼ - 1090  
22 / 4  
7,600  
32.4  
¼ - 890  
22 / 4  
7,600  
32.4  
¼ - 1075  
22 / 4  
7,600  
26.5  
¼ - 890  
22 / 4  
7,600  
26.5  
¼ - 1,075  
22 / 4  
7,600  
26.5  
Rows Deep / Fins per Inch  
Compressor  
2 / 20  
2 / 20  
2 / 22  
2 / 22  
2 / 22  
Quanꢀty / Type  
2 / Scroll  
1
2 / Scroll  
1
2 / Scroll  
1
2 / Scroll  
1
2 / Scroll  
1
Stage  
Electrical Data  
Voltage-Phase-Frequency  
Quanꢀty of Compressors  
Compressor RLA / LRA  
Max External Staꢀc  
Outdoor Fan HP / RLA  
Total Unit Amps  
208/230-3-60  
460-3-60  
2
208/230-3-60  
460-3-60  
2
575-3-60  
2
2
13.1 / 83.1  
1.5”  
2
13.1 / 83.1  
1.0”  
6.1 / 41.0  
1.5”  
6.1 / 41.0  
1.0”  
4.4 / 33.0  
1.0”  
(2) ¼ / 1.4  
36.9  
(2) ¼ / 0.8  
17.7  
(2) ¼ / 1.4  
34.0  
(2) ¼ / 0.8  
16.3  
(2) ¼ / 0.6  
12.3  
Min. Circuit Ampacity¹  
Max. Overcurrent Protecꢀon (amps)²  
Entrance Power Supply  
Entrance Control Voltage  
Operating Weight (lbs)  
Ship Weight (lbs)  
40  
19  
37.3  
17.8  
13.4  
50  
25  
50  
20  
15  
Locaꢀng  
Dimple  
Locaꢀng  
Dimple  
Locaꢀng  
Dimple  
Locaꢀng  
Dimple  
Locaꢀng  
Dimple  
1110  
1150  
1110  
1150  
975  
975  
975  
1000  
1000  
1000  
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
²
SS-CPC90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3
prodUCt speCifiCations  
prodUCt speCifiCations — 8½ tons  
CPC102  
XXX3BXXX  
CPC102  
XXX4BXXX  
CPC102  
XXX7BXXX  
Cooling Capacity  
Total, BTU/h  
102,000  
70,380  
102,000  
70,380  
102,000  
70,380  
Sensible BTU/h  
EER / IEER  
11.3 / 11.2  
83  
11.3 / 11.2  
83  
11.3 / 11.2  
83  
Decibels  
ARI Reference #s  
3620220  
3620220  
3620220  
Evapoartor Motor / Coil  
Motor Type  
Belt Drive  
3,400  
Belt Drive  
3,400  
Belt Drive  
3,400  
Indoor Nominal CFM  
Indoor Motor FLA (Cooling)  
Horsepower - RPM  
7.8  
3.9  
2.3  
1725  
1725  
1725  
Piston Size (Cooling)  
Filter Size (Qty)  
0.08  
0.08  
0.08  
(4) 16” x 20” x 2”  
3/4"  
(4) 16” x 20” x 2”  
3/4"  
(4) 16” x 20” x 2”  
3/4"  
Drain Size (NPT)  
R-410A Refrigerant Charge Cir #1 & #2  
Evaporator Coil Face Area (ſt2)  
Rows Deep / Fins per Inch  
Belt Drive Evap Fan Data  
# of Wheels (D x W)  
Motor Sheave / Blower Sheave  
Belt  
180 oz.  
8.9  
180 oz.  
8.9  
180 oz.  
8.9  
4 / 16  
4 / 16  
4 / 16  
1 (15" x 12")  
VL40 / AK74  
AX51  
1 (15" x 12")  
VL40 / AK74  
AX51  
1 (15" x 12")  
VL40 / AK74  
AX51  
Condenser Fan / Coil  
Quanꢀty of Condenser Fan Motors  
Horsepower - RPM  
2
1/4" - 1,090  
22 / 4  
2
2
1/4" - 1,075  
22 / 4  
1/4" - 890  
22 / 4  
Fan Diameter / # Fan Blades  
Outdoor Nominal CFM  
Face Area (ſt2)  
7,600  
7,600  
7,600  
13.25  
13.25  
13.25  
Rows Deep / Fins per Inch  
Compressor  
2 / 22  
2 / 22  
2 / 22  
Quanꢀty / Type  
2 / Scroll  
1
2 / Scroll  
1
2 / Scroll  
1
Stage  
Electrical Data / Static  
Voltage / Phase / Frequency  
Quanꢀty of Compressors  
Compressor RLA / LRA ea.  
Standard Max Staꢀc  
Outdoor Fan FLA ea.  
Total Unit Amps  
230 / 3 / 60  
460 / 3 / 60  
575 / 3 / 60  
2
14.5 / 98  
1"  
2
6.3 / 55  
1
2
6.0 / 41  
1
1.4  
0.8  
0.6  
39.6  
43.2  
50  
18.1  
19.7  
25  
15.5  
17  
Min. Circuit Ampacity¹  
Max. Overcurrent Protecꢀon (amps)²  
Entrance Power Supply  
Entrance Control Voltage  
Operating Weight (lbs)  
Ship Weight (lbs)  
20  
Locaꢀng  
Dimple  
Locaꢀng  
Dimple  
Locaꢀng  
Dimple  
975  
975  
975  
1000  
1000  
1000  
¹
²
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPC90-150  
prodUCt speCifiCations  
prodUCt speCifiCations — 10 tons  
CPC120  
XXX3BXXX  
CPC120  
XXX4BXXX  
CPC120  
XXX7BXXX  
Cooling Capacity  
Total BTU/h  
118,000  
87,300  
118,000  
87,300  
118,000  
87,300  
Sensible BTU/h  
EER / IEER  
11.5 / 11.2  
83.0  
11.5 / 11.2  
83.0  
11.5 / 11.2  
83.0  
Decibels  
ARI Reference #s  
3023833  
3023833  
3023833  
Evaporator Motor / Coil  
Motor Type  
Belt Drive  
4,000  
Belt Drive  
4,000  
Belt Drive  
4,000  
Indoor Nominal CFM  
Indoor motor FLA (Cooling)  
Horsepower - RPM  
7.8  
3.9  
2.7  
2.0/1725  
0.086  
2.0/1725  
0.086  
2.0/1725  
0.086  
Piston Size (Cooling)  
Filter Size (Qty)  
(4) 16” x 24” x 2”  
¾”  
(4) 16” x 24” x 2”  
¾”  
(4) 16” x 24” x 2”  
¾”  
Drain Size (NPT)  
R-410A Refrigerant Charge Cir #1 & #2  
Evaporator Coil Face Area (ſt²)  
Rows Deep / Fins per Inch  
Belt Drive Evap Fan Data  
# of Wheels (D x W)  
Motor Sheave / Blower Sheave  
Belt  
220 oz.  
10.2  
220 oz.  
10.2  
220 oz.  
10.2  
4 / 14  
4 / 14  
4 / 14  
(1) 15” x 15”  
VL40 / AK74  
AX51  
(1) 15” x 15”  
VL40 / AK74  
AX51  
(1) 15” x 15”  
VL40 / AK74  
AX51  
Condenser Fan / Coil  
Quanꢀty of Condenser Fan Motors  
Horsepower - RPM  
2
⅓ - 1,075  
22 / 3  
2
⅓ - 1,075  
22 / 3  
2
⅓ - 1,075  
22 / 3  
Fan Diameter / # Fan Blades  
Outdoor Nominal CFM  
Face Area (ſt²)  
7,200  
7,200  
7,200  
32.4  
32.4  
32.4  
Rows Deep - Fins per Inch  
Compressor  
2/2 rows - 22 fpi  
2/2 rows - 22 fpi  
2/2 rows - 22 fpi  
Quanꢀty / Type  
2 / Scroll  
1
2 / Scroll  
1
2 / Scroll  
1
Stage  
Electrical Data  
Voltage/Phase/ Frequency  
Quanꢀty of Compressors  
Compressor RLA / LRA ea.  
Standard Max Staꢀc  
Outdoor Fan RLA ea.  
Total Unit Amps  
208-230/3/60  
460/3/60  
2
575/3/60  
2
2
16/110.0  
2.0”  
7.8/52.0  
2.0”  
1.20  
22  
5.7/38.9  
2.0”  
0.89  
16  
2.40  
45  
Min. Circuit Ampacity¹  
Max. Overcurrent Protecꢀon (amps)²  
Entrance Power Supply  
Entrance Control Voltage  
Operating Weight (lbs)  
Ship Weight (lbs)  
49  
24  
17  
60.0  
30  
20  
Locaꢀng  
Dimple  
Locaꢀng  
Dimple  
Locaꢀng  
Dimple  
1135  
1175  
1135  
1175  
1135  
1175  
¹
²
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
SS-CPC90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
prodUCt speCifiCations  
prodUCt speCifiCations — 12½ tons  
CPC150XXX  
3BXXX  
CPC150XXX  
4BXXX  
CPC150XXX  
7BXXX  
Cooling Capacity  
Total, BTU/h  
146,000  
102,200  
11.0 / 11.2  
83  
146,000  
102,200  
11.0 / 11.2  
83  
146,000  
102,200  
11.0 / 11.2  
83  
Sensible BTU/h  
EER / IPLV  
Decibels  
ARI Reference #s  
3542680  
3542680  
3542680  
Evapoartor Motor / Coil  
Motor Type  
Belt Drive  
5,000  
Belt Drive  
5,000  
Belt Drive  
5,000  
Indoor Nominal CFM  
Indoor Motor FLA (Cooling)  
Horsepower - RPM  
Piston Size (Cooling)  
Filter Size  
9.4  
4.7  
4.2  
3.0 - 1,725  
0.096  
3.0 - 1,725  
0.096  
3.0 - 1,725  
0.096  
(4) 20" x 25" x 2"  
¾"  
(4) 20" x 25" x 2"  
¾"  
(4) 20" x 25" x 2"  
¾"  
Drain Size (NPT)  
R-410A Refrigerant Charge Cir #1 & #2  
Evaporator Coil Face Area (ſt2)  
Rows Deep / Fins per Inch  
Condenser Fan / Coil  
Quanꢀty of condenser Fan Motors  
Horsepower - RPM  
Fan Diameter / # Fan Blades  
Outdoor Nominal CFM  
Face Area (ſt2)  
285 oz.  
14.7  
285 oz.  
14.7  
285 oz.  
14.7  
4 / 15  
4 / 15  
4 / 15  
2
⅓ - 1,075  
22/3  
2
⅓ - 1,075  
22/3  
2
⅓ - 1,075  
22/3  
7,200  
7,200  
7,200  
35.3  
35.3  
35.3  
Rows Deep / Fins per Inch  
Belt Drive Evap Fan Data  
# of Wheels (D x W)  
Motor Sheave / Blower Sheave  
Belt  
2/3 rows 15 fpi  
2/3 rows 15 fpi  
2/3 rows 15 fpi  
(1) 15" x 15"  
VL40 / AK66  
AX49  
(1) 15" x 15"  
VL40 / AK66  
AX49  
(1) 15" x 15"  
VL40 / AK66  
AX49  
Compressor  
Quanꢀty / Type  
1 / Scroll  
Single  
1 / Scroll  
Single  
1 / Scroll  
Single  
Stage  
Compressor RLA / LRA ea.  
Electrical Data / Static  
Voltage / Phase / Frequency  
Outdoor Fan FLA ea.  
Total Unit Amps  
Min. Circuit Ampacity1  
Max. Overcurrent Protecꢀon (amps)2  
Entrance Power Supply  
Entrance Control Voltage  
Operating Weight (lbs)  
Ship Weight (lbs)  
22.4 / 149  
10.6 / 75  
7.7 / 54  
208-230/3/60  
460/3/60  
575/3/60  
0.9  
2.4  
59  
65  
80  
1.2  
28  
31  
40  
21.4  
23  
30  
Locaꢀng  
Dimple  
Locaꢀng  
Dimple  
Locaꢀng  
Dimple  
1275  
1300  
1275  
1300  
1275  
1300  
¹
²
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPC90-150  
prodUCt speCifiCations  
airflow data — 7½ tons  
Standard Belt Drive — Down Shot  
Turns Open  
ESP  
(“ W.C.)  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
0.1  
0.3  
0.5  
0.7  
0.9  
1.1  
3617 704  
1.15 3179 704  
0.94 2606 710  
0.75  
1.07 3293 653  
0.88 2757 656  
0.71  
0.84  
0.66  
3541 749  
1.23 3049 754  
1.01 2474 754  
0.82  
3447 798  
1.33 2950 798  
1.11 2408 804  
3400 848  
1.41 2871 848  
1.23  
3303 890  
2838 897  
High-Static Belt Drive — Down Shot (for A Models only)  
Turns Open  
ESP  
(“ W.C.)  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
0.9  
1.1  
1.3  
1.5  
1.7  
1.9  
2.1  
3401 909  
1.51  
1.3  
3428 965  
3012 971  
1.71 2943 915  
3471 1015  
1.9  
1.5  
2423 920  
1.12  
DO NOT  
OPERATE  
3722 1063 2.25 3041 1023 1.67 2503 976  
3359 1075 2.04 2540 1031 1.5  
3381 1119 2.22 2890 1080 1.78  
1.31  
3089 1129 2.04  
Standard Belt Drive — Horizontal  
Turns Open  
ESP  
(“ W.C.)  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
0.1  
0.3  
0.5  
0.7  
0.9  
1.1  
3625 701  
1.11 3177 703  
0.94 2608 709  
0.73  
1.08 3309 660  
0.88 2796 663  
0.68 2225 665  
0.86  
0.68  
0.53  
3815 797  
1.52 3405 803  
1.29 2968 805  
1.44 3468 747  
1.23 3053 753  
1.02 2423 758  
0.8  
3780 841  
3327 847  
3687 885  
3236 891  
2713 896  
1.6  
1.39 2850 852  
1.17  
1.1  
2352 807  
High-Static Belt Drive — Horizontal (for A Models only)  
Turns Open  
ESP  
(“ W.C.)  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
0.9  
1.1  
1.3  
1.5  
1.7  
1.9  
2.1  
3447 902  
1.65 3006 908  
1.44  
1.54  
1.31  
3398 956  
3486 1008 1.87 2960 962  
DO NOT  
OPERATE  
3514 1057 2.07 2949 1019 1.62  
3388 1103 2.18 3036 1069 1.84  
2959 1114 2.0  
2527 1124 1.86  
Notes :  
Assume dry coil with filter in place; CFM correction for wet coil = 3%  
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that exceed the above could  
require a larger motor. Minimum rated SCFM is 350 per ton.  
SS-CPC90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
prodUCt speCifiCations  
airflow data — 8½ tons  
Standard Belt Drive — Down Shot  
Turns Open  
ESP  
(“ W.C.)  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
0.1  
0.3  
0.5  
0.7  
0.9  
1.1  
3467 701  
1.12 3029 701  
0.91 2456 707  
1.04 3143 650  
0.85 2607 653  
0.68  
0.81  
0.63  
3391 746  
1.20 2899 751  
0.98  
3297 795  
1.30 2800 795  
1.08  
3250 845  
1.38 2721 845  
1.20  
3153 887  
2688 894  
High-Static Belt-Drive — Down Shot  
Turns Open  
ESP  
(“ W.C.)  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
0.9  
1.1  
1.3  
1.5  
1.7  
1.9  
2.1  
3251 906  
1.68 2793 912  
1.47  
1.48  
1.27  
3278 962  
3321 1012 1.87 2862 968  
3572 1060 2.22 2891 1020 1.64  
3209 1072 2.01  
3231 1116 2.19 2740 1077 1.75  
3256 1156 2.31 2939 1126 2.01  
Standard Belt Drive — Horizontal  
Turns Open  
ESP  
(“ W.C.)  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
0.1  
0.3  
0.5  
0.7  
0.9  
1.1  
3475 698  
1.08 3027 700  
0.91 2458 706  
1.05 3159 657  
0.85 2646 660  
0.65  
0.83  
0.65  
3665 794  
1.49 3255 800  
1.26 2818 802  
1.07  
1.41 3318 744  
3630 838  
1.57 3177 844  
1.36 2700 849  
1.14  
1.2  
2903 750  
3537 882  
3086 888  
2563 893  
0.99  
High-Static Belt-Drive — Horizontal  
Turns Open  
ESP  
(“ W.C.)  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
0.9  
1.1  
1.3  
1.5  
1.7  
1.9  
3297 899  
1.62 2856 905  
1.41  
1.51  
1.28  
3248 953  
3336 1005 1.84 2810 959  
3364 1054 2.04 2799 1016 1.59  
3238 1100 2.15 2886 1066 1.81  
3188 1146 2.23 2809 1111 1.97  
Notes :  
Assume dry coil with filter in place; CFM correction for wet coil = 3%  
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that exceed the above could  
require a larger motor. Minimum rated SCFM is 350 per ton.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPC90-150  
prodUCt speCifiCations  
airflow data — 10 tons  
Standard Belt-Drive — Down Shot  
Turns Open  
ESP  
(“ W.C.)  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
0.2  
0.4  
0.6  
0.8  
1
4632 781  
1.85 4183 783  
1.63 3717 786  
1.41  
1.76 4203 742  
1.54 3733 748  
1.31  
1.41 3927 691  
1.23 3512 693  
1.17 3510 658  
1
0.9  
4488 825  
2.02 4066 830  
1.77 3622 835  
1.55  
4442 880  
4001 885  
3603 890  
1.2  
High-Static Belt-Drive — Down Shot  
Turns Open  
ESP  
(“ W.C.)  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
0.8  
1
4435 940  
2.22 4078 886  
2.05 3539 892  
1.71  
1.82  
1.52  
4462 997  
2.47 4103 945  
1.2  
1.4  
1.6  
1.8  
2
4513 1054 2.75 4127 1003 2.26 3568 950  
4126 1064 2.52 3597 1008 1.92  
4438 1116 2.97 3759 1069 2.25  
3956 1124 2.55  
4050 1179 3.05 3473 1132 2.32  
Standard Belt-Drive — Horizontal  
Turns Open  
ESP  
(“ W.C.)  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
0.2  
0.4  
0.6  
0.8  
1
4562 736  
4200 736  
1.58 4253 691  
1.41 3735 691  
1.18  
1.29 3893 642  
1.06 3322 648  
1
4497 780  
1.81 4221 784  
1.68 3677 785  
1.34  
1.7  
0.83  
4467 824  
2.06 4170 830  
1.81 3498 835  
1.49  
1.55 3689 741  
1.29  
4564 873  
4129 875  
3558 879  
1.2  
High-Static Belt-Drive — Horizontal  
Turns Open  
ESP  
(“ W.C.)  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
0.8  
1
4602 884  
2.44 4180 885  
2.12 3642 896  
1.8  
2.13  
1.89  
1.58  
4749 940  
4251 945  
3744 951  
1.2  
1.4  
1.6  
1.8  
2
DO NOT  
OPERATE  
4443 1001  
2.5  
4587 1056 2.82 3971 1006 2.17  
4760 1105 3.23 4071 1061 2.43 3342 1012 1.86  
4364 1114 2.91 3579 1067 2.05  
Notes :  
Assume dry coil with filter in place; CFM correction for wet coil = 3%  
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that exceed the above could  
require a larger motor. Minimum rated SCFM is 350 per ton.  
SS-CPC90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9
prodUCt speCifiCations  
airflow data — 12½ tons  
Standard Belt Drive --- Down Shot  
Turns Open  
ESP  
(" W.C.)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
5378  
4750  
4488  
4019  
BHP  
2.35  
1.97  
1.81  
1.55  
CFM  
4967  
4583  
4258  
BHP  
1.92  
1.71  
1.54  
CFM  
4710  
4319  
BHP  
1.59  
1.40  
CFM  
4512  
4030  
BHP  
1.33  
1.13  
0.2  
0.4  
0.6  
0.8  
1.0  
5514  
5204  
4830  
4497  
2.92  
2.69  
2.42  
2.19  
5349  
4919  
4649  
4264  
2.56  
2.27  
2.09  
1.86  
High-Static Belt Drive --- Down Shot  
Turns Open  
ESP  
(" W.C.)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
5978  
5656  
5459  
4844  
4404  
BHP  
3.87  
3.58  
3.40  
2.88  
2.54  
CFM  
5691  
5376  
4950  
4525  
BHP  
3.38  
3.12  
2.79  
2.45  
CFM  
5324  
4933  
4441  
BHP  
2.81  
2.52  
2.18  
0.8  
1.0  
1.2  
1.4  
1.6  
1.8  
2.0  
2.2  
5947  
5708  
5245  
4894  
4495  
4142  
4.16  
3.93  
3.48  
3.17  
2.83  
2.55  
5776  
5465  
5145  
4805  
4429  
4.64  
4.30  
3.97  
3.63  
3.27  
5510  
5199  
4871  
4565  
4233  
4.07  
3.74  
3.41  
3.13  
2.85  
Standard Belt Drive --- Horizontal  
Turns Open  
ESP  
(" W.C.)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
5570  
4902  
4603  
4393  
BHP  
2.27  
1.88  
1.72  
1.61  
CFM  
4935  
4637  
4341  
BHP  
1.70  
1.55  
1.41  
CFM  
4584  
4178  
BHP  
1.36  
1.19  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
5871  
5610  
5391  
5078  
4521  
3.20  
3.00  
2.83  
2.59  
2.20  
5639  
5358  
5010  
4676  
4226  
2.77  
2.57  
2.33  
2.11  
1.83  
5307  
5051  
4799  
4448  
2.31  
2.15  
2.00  
1.79  
High-Static Belt Drive --- Horizontal  
Turns Open  
ESP  
(" W.C.)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
5858  
5502  
5110  
4793  
4382  
BHP  
3.51  
3.20  
2.88  
2.64  
2.34  
CFM  
5538  
5282  
4869  
4598  
BHP  
2.97  
2.78  
2.47  
2.28  
0.8  
1.0  
1.2  
1.4  
1.6  
1.8  
2.0  
2.2  
5894  
5570  
5312  
4945  
4504  
3.85  
3.55  
3.33  
3.01  
2.66  
5780  
5501  
5257  
5020  
4601  
4222  
4.04  
3.77  
3.54  
3.32  
2.96  
2.65  
5900  
5514  
5315  
4906  
4541  
4.49  
4.08  
3.88  
3.49  
3.15  
5860  
5615  
5529  
4938  
4.76  
4.49  
4.40  
3.78  
Notes  
Assume dry coil with filter in place; CFM correcꢀon for wet coil = 3%  
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applicaꢀon  
that exceed the above could require a larger motor. Minimum rated SCFM is 350 per ton.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPC90-150  
prodUCt speCifiCations  
heat kit eleCtriCal data (Blower only, heat mode) — 7½ tons (a modles)  
Model and  
Heat Kit Usage  
MCA¹  
at 208 / 240V  
MOP² (amps)  
at 208 / 240V  
Actual kW  
at 240V  
Recommended  
Airflow Range  
CPC090XXX3BXXX  
EHK3-16  
40  
50  
48 / 55  
87 / 100  
121 / 139  
50 / 60  
90 / 100  
125 / 150  
15  
30  
43  
3000 - 3375 CFM  
3000 - 3375 CFM  
3000 - 3375 CFM  
EHK3-30  
EHK3-45  
Model and  
Heat Kit Usage  
MCA¹  
at 480V  
MOP² (amps)  
at 480V  
Actual kW  
at 480V  
Recommended  
Airflow Range  
CPC090XXX4BXXX  
EHK4-16  
19  
27  
50  
70  
25  
30  
50  
70  
15  
30  
43  
3000 - 3375 CFM  
3000 - 3375 CFM  
3000 - 3375 CFM  
EHK4-30  
EHK4-45  
Model and  
Heat Kit Usage  
MCA¹  
at 575V  
MOP² (amps)  
at 575V  
Actual kW  
at 575V  
Recommended  
Airflow Range  
CPC090XXX7BXXX  
EHK7-16  
14  
22  
41  
57  
15  
25  
45  
60  
15  
30  
43  
---  
---  
---  
EHK7-30  
EHK7-45  
¹
²
Minimum Circuit Ampacity  
Maximum Overcurrent Protecꢀon device  
kw CorreCtion faCtors  
kW Correction Factor (for 1- & 3-Phase Units)  
Supply Voltage  
240  
1
230  
220  
210  
208  
Correction Factor  
0.93  
0.82  
0.78  
0.76  
kW Correction Factor (for 480V Units)  
Supply Voltage  
460  
440  
430  
0.8  
Correction Factor  
0.92  
0.84  
minimUm airflow for eleCtriC heat  
For other voltage, use voltage² / 480²  
Heater Size (kW)  
Minimum CFM  
3,000  
15  
30  
43  
kW Correction Factor (for 575V Units)  
3,000  
Supply Voltage  
560  
550  
540  
3,000  
Correction Factor  
0.95  
0.91  
0.88  
Multiply rated kW by correction factor to get actual kW.  
SS-CPC90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
prodUCt speCifiCations  
heat kit eleCtriCal data (Blower only, heat mode) — 7½ tons (B modles)  
Model and  
Heat Kit Usage  
MCA¹  
at 240V  
MOP² (amps)  
at 240V  
Actual kW  
at 240V  
Recommended  
Airflow Range  
CPC090XXX3BXXX  
EHK3-16  
37  
51  
50  
60  
15  
30  
43  
3000 - 3375 CFM  
3000 - 3375 CFM  
3000 - 3375 CFM  
EHK3-30  
97  
100  
150  
EHK3-45  
136  
Model and  
Heat Kit Usage  
MCA¹  
at 480V  
MOP² (amps)  
at 480V  
Actual kW  
at 480V  
Recommended  
Airflow Range  
CPC090XXX4BXXX  
EHK4-16  
18  
26  
48  
68  
20  
30  
50  
70  
15  
30  
43  
3000 - 3375 CFM  
3000 - 3375 CFM  
3000 - 3375 CFM  
EHK4-30  
EHK4-45  
Model and  
Heat Kit Usage  
MCA¹  
at 575V  
MOP² (amps)  
at 575V  
Actual kW  
at 575V  
Recommended  
Airflow Range  
CPC090XXX7BXXX  
EHK7-16  
13  
22  
41  
57  
15  
25  
45  
60  
15  
30  
43  
3000 - 3375 CFM  
3000 - 3375 CFM  
3000 - 3375 CFM  
EHK7-30  
EHK7-45  
¹
²
Minimum Circuit Ampacity  
Maximum Overcurrent Protecꢀon device  
kw CorreCtion faCtors  
kW Correction Factor (for 1- & 3-Phase Units)  
Supply Voltage  
240  
1
230  
220  
210  
208  
Correction Factor  
0.93  
0.82  
0.78  
0.76  
kW Correction Factor (for 480V Units)  
Supply Voltage  
460  
440  
430  
0.8  
Correction Factor  
0.92  
0.84  
minimUm airflow for eleCtriC heat  
For other voltage, use voltage² / 480²  
Heater Size (kW)  
Minimum CFM  
3,000  
kW Correction Factor (for 575V Units)  
15  
30  
43  
Supply Voltage  
560  
550  
540  
3,000  
Correction Factor  
0.95  
0.91  
0.88  
3,000  
Multiply rated kW by correction factor to get actual kW.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPC90-150  
prodUCt speCifiCations  
heat kit eleCtriCal data (Blower only, heat mode) — 8½ tons  
Recommended  
Airflow Range  
(Downshot)  
Recommended  
Airflow Range  
(Horizontal)  
Model and  
Heat Kit Usage  
MCA¹  
at 208 / 240V  
MOP² (amps)  
at 208 / 240V  
Actual kW  
at 240V  
CPC102XXX3BXXX  
EHK3-16  
43  
55  
50  
60  
15  
30  
43  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
EHK3-30  
100  
139  
100  
150  
EHK3-45  
Recommended  
Airflow Range  
(Downshot)  
Recommended  
Airflow Range  
(Horizontal)  
Model and  
Heat Kit Usage  
MCA¹  
at 480V  
MOP² (amps)  
at 480V  
Actual kW  
at 480V  
CPC102XXX4BXXX  
EHK4-16  
20  
27  
50  
70  
25  
30  
50  
70  
15  
30  
43  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
EHK4-30  
EHK4-45  
Recommended  
Airflow Range  
(Downshot)  
Recommended  
Airflow Range  
(Horizontal)  
Model and  
Heat Kit Usage  
MCA¹  
at 575V  
MOP² (amps)  
at 575V  
Actual kW  
at 575V  
CPC102XXX7BXXX  
EHK7-16  
17  
22  
41  
57  
20  
25  
45  
60  
15  
30  
43  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
EHK7-30  
EHK7-45  
¹
²
Minimum Circuit Ampacity  
Maximum Overcurrent Protecꢀon device  
^ - EHK Heater Kits above require a three-phase power supply  
kw CorreCtion faCtors  
kW Correction Factor (for 1- & 3-Phase Units)  
Supply Voltage  
240  
1
230  
220  
210  
208  
Correction Factor  
0.93  
0.82  
0.78  
0.76  
kW Correction Factor (for 480V Units)  
Supply Voltage  
460  
440  
430  
0.8  
Correction Factor  
0.92  
0.84  
For other voltage, use voltage² / 480²  
kW Correction Factor (for 575V Units)  
Supply Voltage  
560  
550  
540  
Correction Factor  
0.95  
0.91  
0.88  
Multiply rated kW by correction factor to get actual kW.  
SS-CPC90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13  
prodUCt speCifiCations  
heat kit eleCtriCal data (Blower only, heat mode) — 10 tons  
Model and  
Heat Kit Usage  
MCA¹  
at 208 / 240V  
MOP² (amps)  
at 208 / 240V  
Actual kW  
at 240V  
Recommended  
Airflow Range  
CPC120XXX3BXXX  
49  
60  
EHK3-16  
EHK3-30  
EHK3-45  
48 / 55  
87 / 100  
121 / 139  
50 / 60  
90 / 100  
125 / 150  
15  
30  
43  
3500 - 4500 CFM  
3500 - 4500 CFM  
4000 - 4500 CFM  
Model and  
Heat Kit Usage  
MCA¹  
at 208 / 240V  
MOP² (amps)  
at 208 / 240V  
Actual kW  
at 240V  
Recommended  
Airflow Range  
CPC120XXX3HXXX  
EHK3-16  
50  
60  
49 / 57  
88 / 102  
122 / 141  
50 / 60  
90 / 110  
125 / 150  
15  
30  
43  
3500 - 4500 CFM  
3500 - 4500 CFM  
4000 - 4500 CFM  
EHK3-30  
EHK3-45  
Model and  
Heat Kit Usage  
MCA¹  
at 480V  
MOP² (amps)  
at 480V  
Actual kW  
at 480V  
Recommended  
Airflow Range  
CPC120XXX4BXXX  
EHK4-16  
24  
27  
50  
70  
30  
30  
50  
70  
15  
30  
43  
3500 - 4500 CFM  
3500 - 4500 CFM  
4000 - 4500 CFM  
EHK4-30  
EHK4-45  
MCA¹  
at 575V  
MOP² (amps)  
at 575V  
Actual kW  
at 575V  
Model and  
Heat Kit Usage  
Recommended  
Airflow Range  
CPC0120XXX7BXXX  
EHK7-16  
17  
22  
41  
57  
20  
25  
45  
60  
15  
30  
43  
3500 - 4500 CFM  
3500 - 4500 CFM  
4000 - 4500 CFM  
EHK7-30  
EHK7-45  
¹
²
Minimum Circuit Ampacity  
Maximum Overcurrent Protecꢀon device  
kw CorreCtion faCtor  
kW Correction Factor (for 1- & 3-Phase Units)  
Supply Voltage  
240  
1
230  
220  
210  
0.78  
208  
Correcꢀon Factor  
0.93  
0.82  
0.76  
kW Correction Factor for 480V Units  
minimUm airflow for eleCtriC heat  
Actual Voltage  
460  
440  
430  
0.8  
Correcꢀon Factor  
0.92  
0.84  
Min. CFM  
Heater Size (kW)  
Min. CFM  
Horizontal  
For other voltage use voltage² / 480²  
Down-shot  
15  
30  
43  
4,000  
4,000  
4,000  
4,000  
4,000  
4,000  
kW Correction Factor for 575V Units  
Supply Voltage  
560  
550  
540  
Correcꢀon Factor  
0.95  
0.91  
0.88  
Multiply rated kW by correction factor to get actual kW  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPC90-150  
prodUCt speCifiCations  
heat kit eleCtriCal data (Blower only, heat mode) — 12½ tons  
Model and  
Heat Kit Usage  
MCA1 at  
208 / 240V  
MOP2 (amps)  
at 208 / 240V  
Actual kW  
at 240V  
Recommended  
Airflow Range  
CPC150***3B***  
65  
65  
80  
80  
EHK3-16  
EHK3-30  
EHK3-45  
15  
30  
43  
4000 - 5600  
4300 - 5600  
4500 - 5600  
102  
141  
110  
150  
Model and  
Heat Kit Usage  
MCA1 at  
208 / 240V  
MOP2 (amps)  
at 208 / 240V  
Actual kW  
at 240V  
Recommended  
Airflow Range  
CPC150***4B***  
31  
31  
51  
71  
40  
40  
60  
80  
EHK4-16  
EHK4-30  
EHK4-45  
15  
30  
43  
4000 - 5600  
4300 - 5600  
4500 - 5600  
Model and  
Heat Kit Usage  
MCA1 at  
208 / 240V  
MOP2 (amps)  
at 208 / 240V  
Actual kW  
at 240V  
Recommended  
Airflow Range  
CPC150***7B***  
23  
24  
43  
59  
30  
30  
45  
60  
EHK7-16  
EHK7-30  
EHK7-45  
15  
30  
43  
4000 - 5600  
4300 - 5600  
4500 - 5600  
¹
²
Minimum Circuit Ampacity (standard drive)  
Maximum Overcurrent Protecꢀon device (standard drive)  
kw CorreCtion faCtors  
kW Correction Factor (for 1- & 3-Phase Units)  
Supply Voltage  
240  
1
230  
220  
210  
208  
0.76  
Correction Factor  
0.93  
0.82  
0.78  
kW Correction Factor (for 480V Units)  
Supply Voltage  
460  
440  
430  
0.8  
Correction Factor  
0.92  
0.84  
For other voltage, use voltage² / 480²  
kW Correction Factor (for 575V Units)  
Supply Voltage  
560  
550  
540  
Correction Factor  
0.95  
0.91  
0.88  
Multiply rated kW by correction factor to get actual kW.  
SS-CPC90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15  
prodUCt speCifiCations  
expanded Cooling data — 7½ tons (a models)  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPC90-150  
prodUCt speCifiCations  
expanded Cooling data — 7½ tons (a models Cont.)  
SS-CPC90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17  
prodUCt speCifiCations  
expanded Cooling data — 7½ tons (B models)  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPC90-150  
prodUCt speCifiCations  
expanded Cooling data — 7½ tons (B models Cont.)  
SS-CPC90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19  
prodUCt speCifiCations  
expanded Cooling data — 8½ tons  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPC90-150  
prodUCt speCifiCations  
expanded Cooling data — 8½ tons (Cont.)  
SS-CPC90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
21  
prodUCt speCifiCations  
expanded Cooling data — 10 tons  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPC90-150  
prodUCt speCifiCations  
expanded Cooling data — 10 tons (Cont.)  
SS-CPC90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
23  
prodUCt speCifiCations  
expanded Cooling data — 12½ tons  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPC90-150  
prodUCt speCifiCations  
expanded Cooling data — 12½ tons (Cont.)  
SS-CPC90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
25  
Product SPecificationS  
dimenSionS  
L
H
Dimensions  
Model  
Size  
H
L
7½ to 10 Tons  
12½ Tons  
52⅞”  
58⅞”  
99⅛”  
99⅛”  
61¾”  
12⅝”  
5⅞”  
5
28⅜”  
7⅜”  
7 3/8”  
RETURN  
36⅜”  
13⅞”  
”  
SUPPLY  
6½”  
RETURN  
6¼”  
Horizontal Discharge  
5
5⅜”  
SUPPL  
Y
7½”  
7
Vertical Discharge (Bottom of Unit)  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPC90-150  
Product SPecificationS  
unit clearanceS  
Maintain an adequate clearance around the unit for safety, service, maintenance,  
and proper unit operation. Leave a total clearance of 75on the main control  
panel side of the unit for possible removal of fan shaft, coil, electric heat, and  
gas furnace. Leave a clearance of 48on all other sides of the unit for possible  
compressor removal or service access, and to ensure proper ventilation  
and condenser airflow. Do not install the unit beneath any obstruct-  
ion. Install the unit away from all building exhausts to inhibit  
ingestion of exhaust air into the unit’s fresh-air intake.  
48”  
48”  
36” Min.  
75”  
48”  
electrical entrance locationS  
Dimples Mark Drill Locaꢀons  
11⅝”  
High-Voltage Entrance  
103/16”  
Low-Voltage Entrance  
3”  
SS-CPC90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
27  
Product SPecificationS  
roof curb inStallation — rigging  
Provisions for forks have been included in the unit base frame. No other  
fork locations are approved.  
Unit must be lifted by the four lifting holes located at the base  
frame corners.  
Lifting cables should be attached to the unit with shackles.  
The distance between the crane hook and the top of the unit must  
not be less than 60.  
Two spreader bars must span over the unit to prevent damage to  
the cabinet by the lift cables. Spreader bars must be of sufficient  
length so that cables do not come in contact with the unit during  
transport. Remove wood struts mounted beneath unit base frame  
before setting unit on roof curb. These struts are intended to protect  
unit base frame from fork lift damage. To remove the struts, extract  
the sheet metal retainers and pull the struts through the base of the  
unit. Refer to rigging label on the unit.  
Important: If using bottom discharge with roof curb, duct-work  
should be attached to the curb prior to installing the unit. Duct-work  
dimensions are shown in Roof Curb Installation Instructions Manual.  
Refer to the Roof Curb Installation Instructions  
for proper curb installation. Curbing must be  
installed in compliance with the National  
Roofing Contractors Association Manual.  
Lower unit carefully onto roof mounting curb.  
While rigging the unit, the center of gravity  
will cause the condenser end to be lower  
than the supply air end.  
Return  
30”  
Evaporator Coil  
Compressor 1  
Bring condenser end of unit into alignment  
with the curb. With condenser end of the  
unit resting on curb member and using curb  
as a fulcrum, lower opposite end of the unit  
until entire unit is seated on the curb. When  
a rectangular cantilever curb is used, take  
care to center the unit. Check for proper  
alignment and orientation of supply and  
return openings with duct.  
Compressor 2  
Supply  
49”  
Corner & Center-of-Gravity Locations  
7½-Ton B Models  
& 8½-Ton  
Weights (lbs)  
7½-Ton A Models  
Weights (lbs)  
10-Ton  
12½-Ton  
Unit Weights  
Weight A  
Weights (lbs) Weights (lbs)  
280  
280  
260  
245  
240  
225  
1000  
975  
285  
285  
420  
335  
Weight B  
Weight C  
280  
285  
290  
Weight D  
280  
285  
230  
Shipping Weight  
Operaꢀng Weight  
1150  
1110  
1175  
1135  
1300  
1275  
To assist in determining rigging requirements, unit weights are shown to the right.  
Note: These weights are calculated without accessories installed.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPC90-150  
Product SPecificationS  
roof curb inStallation (cont.)  
Curb installations must comply with local codes and should follow the  
established guidelines of the National Roofing Contractors Association.  
Proper unit installation requires that the roof curb be firmly and permanently  
attached to the roof structure. Check for adequate fastening method prior to  
setting the unit on the curb.  
Full perimeter roof curbs are available from the factory and are shipped  
unassembled. The installing contractor is responsible for field assembly,  
squaring, leveling, and mounting on the roof structure. All required hardware  
necessary for the assembly of the sheet metal curb is included in the curb  
accessory package.  
Determine sufficient structural support before locating and mounting the  
curb and package unit.  
Duct-work must be constructed using industry guidelines. The duct-work  
must be placed into the roof curb before mounting the package unit. Our  
full perimeter curbs include duct connection frames to be assembled with  
the curb. Cantilevered-type curbs are not available from the factory.  
Contractor furnishes curb insulation, cant strips,  
flashing, and general roofing material.  
3-d View  
Support curbs on parallel sides with roof members.  
To prevent damage to the unit, the roof members  
cannot penetrate supply and return duct openings.  
92¼  
53¼  
Note: The unit and curb accessories are designed to  
allow vertical duct installation before unit placement.  
Duct installation after unit placement is not  
recommended.  
15 x 31  
Supply Opening  
14  
14 x 38  
Return Opening  
See the manual shipped with the roof curb for  
assembly and installation instructions.  
1
¾
14  
1
toP View  
Power Wiring  
Thermostat  
Wiring  
Power and low-Voltage block locationS  
SS-CPC90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
29  
prodUCt speCifiCations  
wiring diagram — CpC090-120 (for models with serial nUmBers 0907 and Below)  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPC90-150  
prodUCt speCifiCations  
wiring diagram — CpC090-120 (Cont.) (for models with serial nUmBers 0907 and Below)  
Wiring is subject to change. Always  
refer to the wiring diagram or the  
unit for the most up-to-date wiring.  
High Voltage: Disconnect all power before servicing or installing this unit. Mulꢀple power  
sources may be present. Failure to do so may cause property damage, personal injury, or death.  
Warning  
SS-CPC90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
31  
prodUCt speCifiCations  
wiring diagram — CpC090-150  
OR  
SMOKE/FIRE DETECTOR  
REPLACES JUMPER  
BK  
3
240  
460  
575  
OR  
BK  
TB1  
TR  
BL  
RD  
BR  
BL  
2
208  
1
C
RD  
RD  
T3  
T2  
YL  
RD  
L3  
L2  
BR  
GR  
S1  
S2  
G
R
EBTDR  
NO  
K1  
K1  
PK  
BL  
24V  
C
RD  
XFMR-R  
XFMR-C  
GR  
PU  
2
0
8
-
2
4
0
-
4
6
0
-
5
7
5
/
L1  
T1  
COM  
BL  
SEE  
NOTE #2  
BL  
C
OR  
RD  
BK  
CC2  
NOTE #2 NC  
M1 M2  
SPEED  
UP  
PB  
YL  
P
O
W
E
R
S
U
P
P
L
BK  
RD  
BL  
BL  
OR  
BK  
BL  
BK  
OR  
RD  
T3  
T2  
YL  
L3  
L2  
RD  
BR  
Y
BK  
T1  
YL  
RD  
L2  
OR  
BK  
RCCF2  
RD  
BK  
GND  
BK  
C
3
/
6
0
C
F
T1  
L1  
GR  
L1  
T1  
L3  
BK  
RD  
T3 T2  
PU  
BK  
CC1  
BR  
YL  
T3  
PU  
BR  
C
BK  
BK  
T2 T3  
YL  
RD  
T2 T1 RCCF1  
BR  
COMP2  
CM2  
BC  
BL  
PU  
BK  
BK  
C
F
CM1  
COMP1  
OR  
RD  
BK  
PU  
YL  
BK  
SEE  
NOTE 3  
PLF 2  
BL  
PU  
HPS1  
LPS1  
BK  
GR  
9
BL  
BK  
3
2
1
6
5
4
WH  
PU  
OR  
8
7
WH  
YL  
YL  
EM  
BK  
WH  
T
H
E
R
M
O
S
T
PLF 1  
Y1  
YL  
PU  
RD  
GR  
WH  
BR  
BL  
Y/Y2  
R
G
W1  
W2  
C
RD  
3
6
5
4
9
RD  
PU  
2
1
8
7
WH  
BR  
A
T
O
BL  
OR  
TB1  
++  
BL  
SEE NOTE 4  
YL  
HPS2  
LPS2  
0140L00548 REV B  
Wiring is subject to change. Always  
refer to the wiring diagram or the  
unit for the most up-to-date wiring.  
High Voltage: Disconnect all power before servicing or installing this unit. Mulꢀple power  
sources may be present. Failure to do so may cause property damage, personal injury, or death.  
Warning  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPC90-150  
prodUCt speCifiCations  
wiring diagram — CpC090-150 (Cont.)  
L1  
L2  
L3  
COMPONENT LEGEND  
FACTORY WIRING  
LINE VOLTAGE  
LOW VOLTAGE  
SUPPLY VOLTAGE  
208-240/460/575/3/60  
BC  
CC  
CM  
BLOWER CONTACTOR  
COMPRESSOR CONTACTOR  
CONDENSER MOTOR  
OPTIONAL  
HIGH VOLTAGE  
CMR  
COMP  
DC  
DFT  
ECON  
EBTD  
EMR  
R
CONDENSER MOTOR RELAY  
COMPRESSOR  
DEFROST CONTROL  
DEFROST THERMOSTAT  
ECONOMIZER  
ELECTRONIC BLOWER TIME DELAY  
EVAPORATOR MOTOR RELAY  
RELAY  
EVAPORATOR MOTOR  
FAN CAPACITOR  
T2  
FIELD WIRING  
CC1  
T2  
COMP1  
HIGH VOLTAGE  
LOW VOLTAGE  
CC1  
T1  
CC1  
T3  
T3  
C
WIRE CODE  
RCCF1  
EM  
FC  
BK  
BL  
BLACK  
BLUE  
BROWN  
GREEN  
ORANGE  
PINK  
PURPLE  
RED  
WHITE  
YELLOW  
F
CM1  
GND  
HPS  
HVDR  
LPS  
LVDR  
PB  
PLF  
RVC  
RCCF  
EQUPIMENT GROUND  
BR  
GR  
OR  
PK  
PU  
RD  
WH  
YL  
HIGH PRESSURE SWITCH  
HIGH VOLTAGE DEFROST RELAY  
LOW PRESSURE SWITCH  
LOW VOLTAGE DEFROST RELAY  
POWER DISTRUBTION BLOCK  
FEMALE PLUG / CONNECTOR  
REVERSING VAVLE COIL  
RUN CAPACITOR FOR  
C
RCCF2  
F
CM2  
YL/PK YELLOW WITH  
PINK STRIP  
BL/PK BLUE WITH  
PINK STRIP  
COMPRESSOR AND FAN  
TERMINAL BLOCK (24V SIGNAL)  
TRANSFORMER  
TB1  
TR  
T2  
CC2  
T2  
T1 COMP2  
CC2  
T1  
CC2  
T3  
THERMOSTAT  
T3  
FIELD WIRING ++  
BC  
2 STAGE COOLING  
BC  
NOTES:  
W1  
G
WH  
GR  
RD  
YL  
W1  
G
EM  
BC  
208-240V  
OR APPROPRIATE  
INPUT VOLTAGE  
1. REPLACEMENT WIRE MUST BE SAME SIZE AND  
TYPE INSULATION AS ORIGINAL (AT LEAST 105°C)  
USE COPPER CONDUCTOR ONLY.  
2. USE COPPER CONDUCTORS ONLY  
++ USE N.E.C. CLASS 2 WIRE  
R
R
Y1  
Y/Y2  
C
Y1  
Y2  
C
PK  
BL  
3. ECONOMIZER PLUG LOCATED IN THE RETURN AIR  
COMPARTMENT, REMOVE MALE PLUG, ATTACH  
FEMALE PLUG TO THE ECONOMIZER ACCESSORY.  
4. FOR TWO STAGE OPERATION REMOVE W1 TO W2  
WIRE JUMPER.  
5. FOR 208V OPERATION MOVE BLACK WIRE FROM  
TERMINAL 3 TO TERMINAL 2 ON 240V  
TRANSFORMER.  
O
OR  
BR  
O
1
3
TB1  
S2  
W2  
W2  
STAT  
TB1  
S1  
TR  
24V  
G
EBTDR  
R
C
BC  
R
EBTDR  
EBTDR  
LPS1  
LPS2  
CC1  
SEE UNIT RATING PLATE FOR TYPE AND SIZE  
OF OVER CURRENT PROTECTION  
PLF1  
HPS2 CC2  
HPS1  
7
4
9
8
7
6
5
4
3
2
1
PLF2  
8
9
5
6
SEE NOTE 4  
Y/  
R
W2  
O
W1  
Y1  
Y2  
G
C
TB1  
208-240/460/575/3/60 0140L00549 REV. B  
THERMOSTAT  
++  
SEE NOTE 3  
Wiring is subject to change. Always  
refer to the wiring diagram or the  
unit for the most up-to-date wiring.  
High Voltage: Disconnect all power before servicing or installing this unit. Mulꢀple power  
sources may be present. Failure to do so may cause property damage, personal injury, or death.  
Warning  
SS-CPC90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
33  
Product SPecificationS  
acceSSorieS  
Fits  
Model Sizes  
Item #  
Description  
14CURB90150  
25FD90150  
25MFD90150  
BRD3672  
Roof Curb 14" Tall  
25% Manual Fresh Air Damper  
7½-12½ tons  
7½-12½ tons  
7½-12½ tons  
7½-12½ tons  
10 tons  
25% Motorized Fresh Air Damper  
Horizontal Barometric Relief Damper (two required)  
Concentric Duct Kit  
CDK120  
CDK150  
Concentric Duct Kit  
12½ tons  
CDK90102  
DNBBS90150  
DNECONGS90120  
DNECONGS150  
DNSQRRND90  
GHRC-1  
Concentric Duct Kit  
7½-8½ tons  
7½-12½ tons  
7½-10 tons  
12½ tons  
Burglar Bar Sleeves: Includes Supply & Return  
Downflow Economizer  
Downflow Economizer  
Downflow Square-to-Round Adapter 20" Round  
Hurricane Restraint Clip  
7½ tons  
All Models  
7½-10 tons  
12½ tons  
HailGD02  
Condenser Coil Hail Guard  
HailGD05  
Condenser Coil Hail Guard  
HSKT090  
High-Staꢀc Kit for 7½-ton AA models & 8½-ton AA models (230/460v)  
High-Staꢀc Kit for BA models (230/460v)  
High-Staꢀc Kit for AA models (230/460v)  
High-Staꢀc Kit for AA models (230/460v)  
Horizontal Economizer  
7½-8½ tons  
7½ tons  
HSKT090G  
HSKT120  
10 tons  
HSKT150  
12½ tons  
HZECONGS90150  
LAKT02  
7½-12½ tons  
7½ - 12½ tons  
7½ - 12½ tons  
7½-12½ tons  
7½-12½ tons  
Low-Ambient Kit for units with serial number below 0909  
Low Ambient Kit for units with serial numbers 0909 and above  
Power Exhaust 208/230 Volt  
LAKT03  
PE901502  
PE901504  
Power Exhaust 460 Volt  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPC90-150  
prodUCt speCifiCations  
notes  
SS-CPC90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
35  
prodUCt speCifiCations  
notes  
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without  
notice or without incurring obligations. © 2011 • Goodman Manufacturing Company, L.P. Houston, Texas • Printed in the USA.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPC90-150  

Electro Voice Speaker System DH2T 16 User Manual
Fitness Quest Home Gym 95e User Manual
Franke Consumer Products Oven FHPL 301 1CO User Manual
Fujitsu Switch MB3842 User Manual
Furman Sound Music Pedal SPB 8 8E User Manual
Gamber Johnson Printer 7160 0526 00 User Manual
GE Coffeemaker 106840 User Manual
GE Convection Oven JBP95 User Manual
GE Refrigerator 21 23 25 27 29 User Manual
GE Water Heater GEH50DEED User Manual