48TFD008-014
48TFE008-014
48TFF008,012
Single-Package Rooftop Heating/Cooling Units
50 Hz
Installation, Start-Up and
Service Instructions
CONTENTS
Page
Disconnect gas piping from unit when leak test-
ing at pressure greater than 3.4 kPa (1/2 psig).
Pressures greater than 3.4 kPa (1/2 psig) will
cause gas valve damage resulting in hazardous
condition. If gas valve is ever subjected to pres-
sure greater than 3.4 kPa (1/2 psig), it must be
replaced before use. When pressure testing
field-supplied gas piping at pressures of 3.4 kPa
(1/2 psig) or less, a unit connected to such piping
must be isolated by manually closing the gas
valve(s).
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-33
Step 1 — Provide Unit Support . . . . . . . . . . . . . . . . . . . 1
• ROOF CURB
• SLAB MOUNT
Step 2 — Field Fabricate Ductwork. . . . . . . . . . . . . . . 2
Step 3 — Install External Trap for
Condensate Drain. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 2
• POSITIONING
Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . . . . . 8
Step 6 — Install Gas Piping . . . . . . . . . . . . . . . . . . . . . . 8
Step 7 — Make Electrical Connection . . . . . . . . . . . . 8
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
• HEAT ANTICIPATOR SETTINGS
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
Step 8 — Adjust Factory-Installed Options . . . . . . 11
• APOLLO CONTROL
• MANUAL OUTDOOR-AIR DAMPER
• OPTIONAL DURABLADE ECONOMIZER
• OPTIONAL ECONOMI$ER
INSTALLATION
Step 9 — Adjust Evaporator-Fan Speed . . . . . . . . . 20
Unit is shipped in the vertical discharge configuration. To
convert to horizontal configuration, remove screws from side
duct opening covers and remove covers. Using the same
screws, install covers on vertical duct openings with the insula-
tion side down. Seals around duct openings must be tight. See
Fig. 1.
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-36
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36-41
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . 42-46
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . CL-1
Step 1 — Provide Unit Support
ROOF CURB — Assemble and install accessory roof curb in
accordance with instructions shipped with curb. See Fig. 2. In-
stall insulation, cant strips, roofing felt, and counter flashing as
shown. Ductwork must be attached to curb. If gas, electric
power or control power is to be routed through the curb, attach
the accessory thru-the-curb service connection plates to the
roof curb in accordance with the accessory installation instruc-
tions. Connection plates must be installed before unit is set in
roof curb.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
IMPORTANT: The gasketing of the unit to the roof curb
is critical for a watertight seal. Install gasket supplied
with the roof curb as shown in Fig. 2. Improperly
applied gasket can also result in air leaks and poor unit
performance.
Curb should be level. Unit leveling tolerances are shown in
Fig. 3. This is necessary for unit drain to function properly. Re-
fer to Accessory Roof Curb Installation Instructions for addi-
tional information as required.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 004-816 Printed in U.S.A. Form 48TF-C1SI Pg 1 1-01 Replaces: New
Book 1
4
Tab 1a 6a
Download from Www.Somanuals.com. All Manuals Search And Download.
D ALT
DRAIN
HOLE
ROOF CURB
ACCESSORY
CRRFCURB003A00 1′-2″ [356]
CRRFCURB004A00 2′-0″ [610]
UNIT SIZE
48TF
CONNECTOR
PKG. ACCY.
“A”
B
C
GAS
POWER
CONTROL
CRBTMPWR001A00
CRBTMPWR002A00
3/4″ [19] NPT
11/4″ [31.7]
3/4″
1/2″
008-014
[19] NPT
[12.7]
2′-87/16
″
1′-1015
/
″
13/4″
1/2″
[827]
[583]16
[44.5]
CRBTMPWR003A00
CRBTMPWR004A00
3/4″ [19] NPT
NOTES:
1/2″
[12.7] NPT
1. Roof curb accessory is shipped disassembled.
2. Insulated panels: 1-in. [25] thick polyurethane
foam, 13/4 lb density.
3/4″
[12.7]
11/4″ [31.7]
[19] NPT
3. Dimensions in [ ] are in millimeters.
4. Roof curb: 16-gage steel.
5. Attach ductwork to curb (flanges of duct rest on
curb).
6. Service clearance 4 ft [1219] on each side.
7.
Direction of airflow.
8. Connector packages CRBTMPWR001A00 and
2A00 are for thru-the-curb gas type. Packages
CRBTMPWR003A00 and 4A00 are for thru-
the-bottom type gas connections.
Fig. 2 — Roof Curb Details
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Position unit on roof curb so that the following clearances
are maintained: 7 mm (1/4-in.) clearance between roof curb and
base rails on each side and duct end of unit; 84 mm (35/16-in.)
clearance between roof curb and condenser coil end of unit.
(See Fig. 2, section C-C.)
Locate mechanical draft system flue assembly at least
1219 mm (48 in.) from any opening through which combustion
products could enter the building, and at least 1219 mm (48 in.)
from an adjacent building or combustible material. When unit
is located adjacent to public walkways, flue assembly must be
at least 2.13 m (7 ft) above grade.
Flue vent discharge must have a minimum horizontal clear-
ance of 1219 mm (48 in.) from electric and gas meters, gas reg-
ulators, and gas relief equipment.
MAXIMUM ALLOWABLE
DIFFERENCE mm (in.)
A-B
B-C
A-C
13 (0.5)
25 (1.0)
25 (1.0)
Fig. 3 — Unit Leveling Tolerances
Flue gas can deteriorate building materials. Orient unit so
that flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper
operation of this equipment. Be sure that installation complies
with all local codes and Section 5.3, Air for Combustion and
Ventilation, NFGC (National Fuel Gas Code), ANSI (Ameri-
can National Standards Institute), latest revision, U.S.A.
Standards.
(Copy continued on page 8.)
DRAIN PLUG
NOTE: Drain plug is shown in factory-installed position.
Fig. 4 — Condensate Drain Pan
NOTES:
1. Dimension in ( ) is in millimeters.
DIMENSIONS
‘‘B’’
lb kg in. mm in. mm in. mm
870 395 87.38 2219 40.25 1022 41.31 1050
1035 469 87.38 2219 40.25 1022 49.31 1253
1050 476 87.38 2219 40.25 1022 49.31 1253
MAX
2. Hook rigging shackles through holes in base rail as shown in
detail ‘‘A.’’ Holes in base rails are centered around the unit cen-
ter of gravity. Use wooden top skid when rigging to prevent rig-
ging straps from damaging unit.
3. Weights include base unit without economizer. See Tables 1A
and 1B for economizer weights.
UNIT
48TF
WEIGHT
‘‘A’’
‘‘C’’
D/E/F008
D/E/F012
D/E014
All panels must be in place when rigging.
Fig. 5 — Rigging Details
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1A — Physical Data (SI)
UNIT SIZE 48TF
Low Heat (D), Medium Heat (E), High Heat (F)
NOMINAL CAPACITY (kW)
008
E
012
E
014
D
F
D
F
D
E
21.5
29.2
35.9
OPERATING WEIGHT (kg)
Unit
395
20
469
20
476
20
Durablade Economizer
EconoMi$er
28
28
28
Roof Curb*
65
65
65
COMPRESSOR TYPE
Quantity
Oil (ml)
Hermetic
2
1479 ea
Hermetic
2
1479 ea
Scroll
2
1597 ea
REFRIGERANT TYPE
Operating Charge (kg)
Circuit 1
R-22
2.10
2.22
3.08
3.22
3.49
3.49
Circuit 2
CONDENSER COIL
Rows...Fins/m
Total Face Area (sq m)
Enhanced Copper Tubes, Aluminum Lanced Fins
1...669
1.90
2...669
1.92
2...669
2.30
CONDENSER FAN
Nominal L/s
Quantity...Diameter (mm)
Motor BkW...r/s
Propeller Type
3050
2880
2...559
.19...15.5
3050
2...559
.19...15.5
2...559
.19...15.5
EVAPORATOR COIL
Rows...Fins/m
Total Face Area (sq m)
Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol™ Feed Device
3...590
0.74
3...590
0.93
4...590
1.03
EVAPORATOR FAN
Centrifugal Type
Quantity...Size (mm x mm)
Type Drive
1...381 x 381
Belt
1...381 x 381
Belt
1...381 x 381
Belt
Nominal L/s
Motor kW
1230
1700
1980
1.12
1.50
2.24
Maximum Continuous BkW
Motor Frame Size
1.79
1.79
2.76
56
56
56
Fan r/s Range
8.2-11.7
Ball
9.5-13.0
Ball
12.0-15.0
Ball
Motor Bearing Type
Maximum Allowable r/s
Motor Pulley Pitch Diameter Min/Max (mm)
Nominal Motor Shaft Diameter (mm)
Fan Pulley Pitch Diameter (mm)
Nominal Fan Shaft Diameter (mm)
Belt, Quantity...Type...Length (mm)
Pulley Center Line Distance (mm)
Speed Change per Full Turn of
Movable Pulley Flange (r/s)
Movable Pulley Maximum Full Turns
From Closed Position
26.7
26.7
26.7
61/86
16
71/97
16
102/127
22
178
25
178
25
203
25
1...A...1245
425-489
1...A...1245
403-445
1...A...1346
403-445
.70
.70
.60
5
5
5
Factory Setting
Factory Speed Setting (r/s)
Fan Shaft Diameter at Pulley (mm)
5
8.2
25
5
9.5
25
5
12.0
25
FURNACE SECTION
Rollout Switch Cutout Temp (C)
Burner Orifice Diameter (mm)
90.6
90.6
90.6
Natural Gas
— Std
3.05
2.44
3.05
2.44
3.05
2.44
3.28
2.59
3.05
3.28
2.59
Liquid Propane — Alt
Thermostat Heat Anticipator Setting (amps)
400 v Stage 1
2.44
.14
.14
.14
.20
.14
.20
.14
.20
.14
.20
Stage 2
Gas Input (kW)
Stage 1
Stage 2
21.1
31.4
31.9
50.4
80
39.8
59.8
31.9
50.4
39.8
59.8
80
43.9
65.6
39.8
59.8
43.9
65.6
Efficiency (Steady State) (%)
Temperature Rise Range (C)
Manifold Pressure (kPa)
80
–6-10
2-18
7-24
2-18
7-24
4-21
7-24
4-21
Natural Gas
— Std
8.3
8.3
19
8.3
8.3
19
8.3
8.3
Liquid Propane — Alt
Field Gas Connection Size (mm)
13
19
19
19
19
19
HIGH-PRESSURE SWITCH (kPa)
Standard Compressor
Internal Relief (Differential)
Cutout
3103 345
3448 345
2951
2206
Reset (Auto.)
LOW-PRESSURE SWITCH (kPa)
Cutout
Reset (Auto.)
48 21
152 48
FREEZE PROTECTION THERMOSTAT
Opens (C)
Closes (C)
–1
7
3
3
OUTDOOR-AIR INLET SCREENS
Quantity...Size (mm)
Cleanable
1...508 x 635 x 25
1...406 x 635 x 25
RETURN-AIR FILTERS
Quantity...Size (mm)
Throwaway
4...406 x 508 x 51
4...508 x 508 x 51
4...508 x 508 x 51
LEGEND
*Weight of 356 mm (14-in.) roof curb.
Bhp
—
Brake Horsepower
NOTE: The 48TF units have a loss-of-charge (low pressure) switch located in
the liquid line.
BkW — Fan Input Watts x Motor Efficiency
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1B — Physical Data (English)
UNIT SIZE 48TF
Low Heat (D), Medium Heat (E), High Heat (F)
NOMINAL CAPACITY (tons)
008
E
012
E
014
D
F
D
F
D
E
6.1
8.3
10.2
OPERATING WEIGHT (lb)
Unit
870
44
1035
44
1050
44
Durablade Economizer
EconoMi$er
62
62
62
Roof Curb*
143
143
143
COMPRESSOR TYPE
Quantity
Oil (oz)
Hermetic
2
50 ea
Hermetic
2
50 ea
Scroll
2
54 ea
REFRIGERANT TYPE
Operating Charge (lb-oz)
Circuit 1
R-22
4-10
4-11
6-13
7- 2
7-11
7- 8
Circuit 2
CONDENSER COIL
Rows...Fins/in.
Total Face Area (sq ft)
Enhanced Copper Tubes, Aluminum Lanced Fins
1...17
20.50
2...17
20.50
2...17
25.00
CONDENSER FAN
Nominal Cfm
Quantity...Diameter (in.)
Motor BkW...Rpm
Propeller Type
6500
6100
2...22
6500
2...22
2...22
1/4...930
1/4...930
1/4...930
EVAPORATOR COIL
Rows...Fins/in.
Total Face Area (sq ft)
Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol™ Feed Device
3...15
8.0
3...15
10.0
4...15
11.1
EVAPORATOR FAN
Centrifugal Type
Quantity...Size (in.)
1...15 x 15
Belt
1...15 x 15
Belt
1...15 x 15
Belt
Type Drive
Nominal Cfm
2600
3500
2
4200
3
Motor Hp
11/2
Maximum Continuous Bhp
Motor Frame Size
2.40
2.40
3.70
56
56
56
Fan Rpm Range
492-700
Ball
571-779
Ball
717-900
Ball
Motor Bearing Type
Maximum Allowable Rpm
Motor Pulley Pitch Diameter Min/Max (in.)
Nominal Motor Shaft Diameter (in.)
Fan Pulley Pitch Diameter (in.)
Nominal Fan Shaft Diameter (in.)
Belt, Quantity...Type...Length (in.)
Pulley Center Line Distance (in.)
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full Turns
From Closed Position
1600
1600
1600
2.4/3.4
2.8/3.8
4.0/5.0
5
5
7
/
/
8
/
7.80
—
7.0
—
8.80
—
1...A...49
16.75-19.25
1...A...49
15.85-17.50
1...A...53
15.85-17.50
41
41
36
5
5
5
Factory Setting
Factory Speed Setting (rpm)
Fan Shaft Diameter at Pulley (in.)
5
492
1
5
571
1
5
717
1
FURNACE SECTION
Rollout Switch Cutout Temp (F)
Burner Orifice Diameter (in. ...drill size)
195
195
195
Natural Gas
— Std
.120...31
.096...41
.120...31
.120...31
.096...41
.129...30
.102...38
.120...31
.129...30
.102...38
Liquid Propane — Alt
Thermostat Heat Anticipator Setting (amps)
400 v Stage 1
.096...41
.096...41
.14
.14
.14
.20
.14
.14
.20
.14
.20
Stage 2
.20
Gas Input (Btuh) Stage 1
72,000
107,000
109,000
172,000
80
136,000
204,000
109,000
172,000
136,000
204,000
80
150,000
224,000
136,000
204,000
150,000
224,000
‘
Efficiency (Steady State) (%)
Temperature Rise Range (F)
Manifold Pressure (in. wg)
80
20-50
35-65
45-75
35-65
45-75
40-70
45-75
40-70
Natural Gas
— Std
3.5
3.5
3.5
Liquid Propane — Alt
3.5
3.5
3.5
1
3
3
3
3
Field Gas Connection Size (in.)
/
2
/
4
/
4
/
4
/
4
HIGH-PRESSURE SWITCH (psig)
Standard Compressor
Internal Relief (Differential)
Cutout
450 50
500 50
428
320
Reset (Auto.)
LOW-PRESSURE SWITCH (psig)
Cutout
Reset (Auto.)
7
22
3
7
FREEZE PROTECTION THERMOSTAT
Opens (F)
Closes (F)
30
45
5
5
OUTDOOR-AIR INLET SCREENS
Quantity...Size (in.)
Cleanable
1...20 x 25 x 1
1...16 x 25 x 1
RETURN-AIR FILTERS
Quantity...Size (in.)
Throwaway
4...16 x 20 x 2
4...20 x 20 x 2
4...20 x 20 x 2
LEGEND
*Weight of 356 mm (14-in.) roof curb.
Bhp
—
Brake Horsepower
NOTE: The 48TF units have a loss-of-charge (low pressure) switch located in
the liquid line.
BkW — Fan Input Watts x Motor Efficiency
6
Download from Www.Somanuals.com. All Manuals Search And Download.
DURABLADE
ECONOMIZER
WEIGHT
STANDARD
ECONOMI$ER
WEIGHT
CORNER
CORNER
CORNER
CORNER
“H”
“J”
“K”
ft-in.
“L”
UNIT
48TF
UNIT WEIGHT
WEIGHT (A) WEIGHT (B) WEIGHT (C) WEIGHT (D)
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
ft-in. [mm] ft-in. [mm]
[mm] ft-in. [mm]
D/E/F008
D/E/F012
D/E014
870
1035
1050
395
469
476
44
44
44
20
20
20
62
62
62
28
28
28
189
225
228
86
102
103
161
192
195
73
87
88
239
285
289
109
129
131
280
333
338
127 1-27/8 [ 378] 3-55/16 [1050] 2-911
151 2-57/8 [ 759] 4-15/16 [1253] 3-03/8
153 1-27/8 [ 378] 4-15/16 [1253] 3-03/8
/
[856] 2- 27/16 [672]
[924] 2-107/16 [875]
[924] 2-107/16 [875]
16
BOTTOM POWER CHART, THESE HOLES
REQUIRED FOR USE WITH ACCESSORY
PACKAGES — CRBTMPWR002A00 (POWER
AND CONTROL) AND CRBTMPWR004A00
(POWER, CONTROL, AND GAS)
NOTES:
CONNECTION SIZES
1. Dimensions in [ ] are in millimeters.
A
B
C
D
E
13/8″ Dia [35] Field Power Supply Hole
21/2″ Dia [64] Power Supply Knockout
13/4″ Dia [44] Charging Port Hole
2.
3.
Center of gravity.
Direction of airflow.
7/8″ Dia [22] Field Control Wiring Hole
3/4″ [19] - 14 NPT Condensate Drain
THREADED
CONDUIT
SIZE
REQURED
HOLE SIZES
(MAX.)
WIRE
USE
4. On vertical discharge units, ductwork to be attached to
accessory roof curb only. For horizontal discharge units,
field-supplied flanges should be attached to horizontal dis-
charge openings, and all ductwork should be attached to
the flanges.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Between unit, flue side and combustible surfaces,
36 in. [914].
1/2″ [13] - 14 NPT Gas Connection 48TFD008
3/4″ [19] - 14 NPT Gas Connection 48TFE,F008
48TFD,E012 & 014, 48TJF012
1/2″ [12.7]
24 V
Power
Gas
7/8″ [22.2]
13/4″ [44.4]
15/8″ [41.3]
F
11/4″ [31.7]
3/
G
2″ Dia [51] Power Supply Knockout
4″ [19] FPT
b. Bottom of unit to combustible surfaces (when not using
curb), 1 in. [25]. Bottom of base rail to combustible sur-
faces (when not using curb) 0 inches.
c. Condenser coil, for proper airflow, 36 in. [914] one side,
12 in. [304] the other. The side getting the greater clear-
ance is optional.
d. Overhead, 60 in. [1624] to assure proper condenser fan
operation.
e. Between units, control box side, 42 in. [1067] per NEC
(National Electrical Code).
f. Between unit and ungrounded surfaces, control box
side, 36 in. [914] per NEC.
g. Between unit and block or concrete walls and other
grounded surfaces, control box side, 42 in. [1067] per
NEC.
h. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil
and combustion side as stated in notes 5a, b and c, a
removable fence or barricade requires no clearance.
7. Units may be installed on combustible floors made from
wood or Class A, B, or C roof covering material if set on
base rail.
8. The vertical center of gravity is 1′-7″ [483] for 008, 1′-11″
[584] for 012 and 014 up from the bottom of the base rail.
Fig. 6 — Base Unit Dimensions
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 5 — Install Flue Hood — Flue hood is shipped
screwed to the burner compartment access panel. Remove
from shipping location and, using screws provided, install flue
hood and screen in location shown in Fig. 7.
Step 6 — Install Gas Piping — Unit is equipped for
use with type of gas shown on nameplate. Refer to local
building codes.
For natural gas applications, gas pressure at unit gas connec-
tion must not be less than 13.5 kPa (4.0 in. wg) (17.0 kPa
[5.0 in. wg] in high heat units) or greater than 44.0 kPa
(13.0 in. wg) while unit is operating. For liquid propane applica-
tions, the gas pressure must not be less than 17.0 kPa (5.0 in. wg)
or greater than 44.0 kPa (13.0 in. wg) at the unit connection.
Size gas supply piping for 1.7 kPa (0.5 in. wg) maximum
pressure drop. Do not use supply pipe smaller than unit gas
connection.
NOTE: When installing gas piping to gas valve inlet, use prop-
erly sized back-up wrench on inlet flange flats.
Fig. 7 — Flue Hood Details
Support gas piping as shown in the table in Fig. 8. For ex-
ample, a 19 mm (3/4-in.) gas pipe must have one field-
fabricated support beam every 2.4 m (8 ft).
See Fig. 8 for typical pipe guide and locations of external
manual gas shutoff valve.
X
228 mm (9") MINIMUM CLEARANCE
FOR PANELREMOVAL
GAS
MANUAL GAS
SHUTOFF VALVE*
REGULATOR*
BASE UNIT
Step 7 — Make Electrical Connections
1219 mm (48") MINIMUM
DRIP LEG PER NFGC*
BASE RAIL
Unit cabinet must have an uninterrupted, unbroken electri-
cal ground to minimize the possibility of personal injury if
an electrical fault should occur. This ground may consist of
electrical wire connected to unit ground lug in control com-
partment, or conduit approved for electrical ground when
installed in accordance with NEC (National Electrical
Code), ANSI/NFPA (National Fire Protection Associa-
tion), latest edition (U.S.A. Standards), and local electrical
codes. Do not use gas piping as an electrical ground. Fail-
ure to follow this warning could result in the installer being
liable for personal injury of others.
ROOF CURB
FIELD-FABRICATED
SUPPORT*
FROM GAS METER
LEGEND
NFGC — National Fuel Gas Code (U.S.A. Standard)
*Field supplied.
NOTE: Follow all local codes.
SPACING OF SUPPORTS
STEEL PIPE NOMINAL DIAMETER
mm (in.)
X DIMENSION
m (ft)
13 (1/2)
1.8 (6)
2.4 (8)
3.0 (10)
FIELD POWER SUPPLY — All units are factory wired for
the voltage shown on the nameplate.
Refer to unit label diagram for additional information. Pig-
tails are provided for field service.
When installing units, provide a disconnect per local codes.
Use copper conductors only when splice connectors are used.
19 or 25 (3/4 or 1)
32 or larger (11/4 or larger)
Fig. 8 — Gas Piping Guide (With Accessory
Thru-the-Curb Service Connections)
All field wiring must comply with local requirements.
FIELD CONTROL WIRING — Install a Carrier-approved
accessory thermostat assembly according to installation in-
structions included with the accessory. Locate thermostat
assembly on a solid wall in the conditioned space to sense aver-
age temperature in accordance with thermostat installation
instructions.
NOTE: For wire runs up to 15 m (50 ft), use no. 18 AWG
(American Wire Gage) insulated wire (35 C minimum). For 15
to 23 m (51 to 75 ft), use no. 16 AWG insulated wire (35 C
minimum). For over 23 m (75 ft), use no. 14 AWG insulated
wire (35 C minimum). All wire larger than no. 18 AWG cannot
be directly connected to the thermostat and will require a junc-
tion box and splice at the thermostat. Refer to Table 3 for wire
conversions.
Install conduit through side panel openings indicated in
Fig. 6. Route power lines through connector to terminal con-
nections as shown in Fig. 9.
Voltages between phases must be balanced within 2% and
the current within 10%. Use the formula shown in Table 2,
Note 2 to determine the percentage of voltage imbalance. Op-
eration on improper line voltage or excessive phase imbalance
constitutes abuse and may cause damage to electrical compo-
nents. Such operation would invalidate any applicable Carrier
warranty.
NOTE: If field-installed thru-the-bottom connections are used,
refer to the accessory installation instructions for power wiring.
Refer to Fig. 6 for drilling holes in basepan.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2 — Electrical Data
VOLTAGE
RANGE
COMPR
(ea)
OFM
(ea)
FLA
MINIMUM UNIT
DISCONNECT
NOMINAL
VOLTAGE
(50 Hz)
400
(3 phase)
400
(3 phase)
400
(3 phase)
IFM
FLA
2.6
POWER SUPPLY
UNIT
48TF
Min
Max
RLA
LRA
MCA
MOCP*
FLA
LRA
008
012
014
360
360
360
440
6.4
8.9
42.0
0.3
17.6
23.2
29.4
20
18
108
440
440
52.0
73.0
0.3
0.7
2.6
5.4
30
35
24
31
128
192
10.4
LEGEND
Example: Supply voltage is 400-3-50.
FLA — Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
AB = 393 v
BC = 403 v
AC = 396 v
IFM
— Indoor (Evaporator) Fan Motor
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC — National Electrical Code (U.S.A.)
OFM — Outdoor (Condenser) Fan Motor
RLA — Rated Load Amps
393 + 403 + 396
3
Average Voltage =
1192
3
=
*Fuse or HACR circuit breaker.
= 397
Determine maximum deviation from average voltage.
(AB) 397 – 393 = 4 v
(BC) 403 – 397 = 6 v
(AC) 397 – 396 = 1 v
Maximum deviation is 6 v.
Determine percent of voltage imbalance.
6
% Voltage Imbalance = 100 x
397
NOTES:
1. In compliance with NEC requirements (U.S.A. Standard) for
multimotor and combination load equipment (refer to NEC Arti-
cles 430 and 440), the overcurrent protective device for the unit
shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
= 1.5%
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percent of voltage imbalance.
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Route thermostat cable or equivalent single leads of colored
wire from thermostat subbase terminals to low-voltage connec-
tions on unit (shown in Fig. 10) as described in Steps 1-4
below.
1. If unit is mounted on roof curb and accessory thru-the-
curb service plate connection is used, route wire through
connection plate.
2. Pass control wires through the hole provided on unit (see
connection D in Connection Sizes table in Fig. 6).
3. Feed wires through the raceway built into the corner post
to the 24-v barrier located on the left side of the control
box. See Fig. 11. The raceway provides the UL-required
(Underwriters’ Laboratories) clearance between high-
and low-voltage wiring.
4. Connect thermostat wires to screw terminals on low-
voltage connection board.
HEAT ANTICIPATOR SETTINGS — Set heat anticipator
settings at .14 amp for the first stage and .20 amp for second-
stage heating, except for 008 low heat. Set both first and sec-
ond stage heat anticipator settings for 008 at .14 amp.
Table 3 — American/European Wire Conversions
AMERICAN
EUROPEAN
American
Industry
Standard
Size (mm2)
Industry
Standard Size
Conversion
Size (mm2)
18 AWG
16 AWG
14 AWG
12 AWG
10 AWG
8 AWG
0.82
1.30
1.0
1.5
2.08
2.5
3.30
4.0
6.0
10.0
16.0
25.0
—
35.0
50.0
—
70.0
95.0
120.0
5.25
6.36
6 AWG
13.29
21.14
26.65
33.61
42.39
53.49
67.42
85.00
107.19
4 AWG
3 AWG
2 AWG
1 AWG
1/0 AWG
2/0 AWG
3/0 AWG
4/0 AWG
250 kcmil
300 kcmil
350 kcmil
400 kcmil
500 kcmil
600 kcmil
126.64
151.97
177.90
202.63
253.29
303.95
150.0
—
185.0
240.0
300.0
—
LEGEND
AWG — American Wire Gage
kcmil — Thousand Circular Mils
9
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
C
—
—
Contactor
IFC
Indoor (Evaporator)
Fan Contactor
NEC
—
National Electrical Code
(U.S.A. Standard)
Splice Connection
(Factory Supplied)
Equipment Ground
Field Wiring
Factory Wiring
Fig. 9 — Power Wiring Connections
INTEGRATED
GAS UNIT
CONTROLLER
(IGC)
UNIT LOW VOLTAGE
CONNECTION
BOARD
LEGEND
AHA — Adjustable Heat Anticipator
CC
—
Cooling Compensator
Field Wiring
Factory Wiring
Fig. 10 — Low-Voltage Connections
COMPRESSOR
NO.1
COMPRESSOR
NO. 2
RACEWAY
Fig. 11 — Field Control Wiring Raceway
and Compressor Location
10
Download from Www.Somanuals.com. All Manuals Search And Download.
9. Remove and save screws currently on sides of hood.
Insert screens. Secure screens to hood using the screws.
See Fig. 15.
Step 8 — Adjust Factory-Installed Options
APOLLO CONTROL — The optional Apollo control is used
to actively monitor all modes of operation as well as indoor
(evaporator) fan status, filter status, and indoor-air quality. The
Apollo control is designed to work with Carrier TEMP and
VVT® systems.
The thermostat must be wired to the Apollo control before
starting the unit. Refer to the Apollo control installation
instructions for information on installing the thermostat. See
Fig. 12 for Apollo location.
MANUAL OUTDOOR-AIR DAMPER — The outdoor-air
hood and screen are attached to the basepan at the bottom of
the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building.
Record amount for use in Step 8.
2. Remove and save evaporator coil access panel and
screws. See Fig. 13.
3. Separate hood and screen from basepan by removing the
screws and brackets securing them. Save all screws and
discard brackets.
Fig. 13 — Damper Panel with Manual
Outdoor-Air Damper Installed
4. Replace evaporator coil access panel using screws from
Step 2.
5. Place hood on front of evaporator coil access panel. See
Fig. 14 for hood details. Secure top of hood with the
screws removed in Step 3. See Fig. 15.
6. Remove and save 6 screws (3 on each side) from sides of
the manual outdoor-air damper. Remove and save 2 man-
ual outdoor-air adjustment screws (one on each side of
damper blade).
7. Align screw holes on hood with screw holes on side of
manual outdoor-air damper. See Fig. 14 and 15. Secure
hood with 6 side screws from Step 6.
8. Adjust minimum position setting of the damper blade by
adjusting the 2 manual outdoor-air adjustment screws on
the front of the damper blade. See Fig. 13. Slide blade
vertically until it is in the appropriate position determined
by Fig. 16. Tighten screws.
WIRING TO
THERMOSTAT
CONTROL
WIRING
APOLLO
CONTROL
Fig. 14 — Outdoor-Air Hood Details
Fig. 12 — Apollo Control Factory-Installed
in Typical Unit
Fig. 15 — Damper with Hood Attached
11
Download from Www.Somanuals.com. All Manuals Search And Download.
c. Install horizontal discharge block-off plate over
the opening on the access panel. (Block-off plate
MUST be installed before installing hood assem-
bly.) See Fig. 22.
1.0
250
200
0.8
0.6
0.4
7. Insert economizer plug into economizer harness. Remove
tape from barometric relief damper. See Fig. 20.
150
100
8. If ventilation air is not required, proceed to Step 9. If ven-
tilation air is required, determine the minimum position
setting for required airflow. See Fig. 23. Adjust minimum
position setting by loosening the screws on the position
setting bracket. See Fig. 24. Slide bracket until the top
screw is in the position determined by Fig. 23. Tighten
screws.
9. Remove tape from outdoor-air thermostat (OAT). Fasten
OAT to inside of hood using screws and speed clips pro-
vided. See Fig. 25. Make sure OAT terminals are posi-
tioned up.
3" (76 mm)
1" (25 mm) OPEN
0.2
50
0
0
0
6
8
2
4
10
12
OUTDOOR AIRFLOW (cfm x 100)
100
200
300
400
500
OUTDOOR AIRFLOW (L/s)
10. Replace outdoor-air opening panel using screws from
Step 2. Replace filter access panel. Ensure the filter ac-
cess panel slides along the tracks and is securely engaged.
Fig. 16 — Position Setting
11. Fasten hood top and side plate assembly to outdoor-air
opening panel with screws provided.
12. Place knob supplied with economizer on OAT. See
Fig. 25. Set OAT for 1.7° C (3° F) below indoor room
thermostat setting. If accessory enthalpy control (EC) is
used in place of OAT, see instructions shipped with EC
for installation and adjustment. See Fig. 25.
OPTIONAL DURABLADE ECONOMIZER — The option-
al economizer hood assembly is packaged and shipped in the fil-
ter section. Damper blades and control boards are installed at the
factory and the economizer is shipped in the vertical discharge
position.
13. Connect OAT per Fig. 26.
NOTE: Horizontal discharge block-off plate is shipped with
the air hood package. If unit is to be used for vertical discharge
application, discard this plate.
14. Slide outdoor-air inlet screens into screen track on hood
side plate. While holding screens in place, fasten screen
retainer to hood using screws provided.
Assembly
NOTE: Refer to Fig. 27 for Durablade economizer barometric
relief damper characteristics.
1. Determine if ventilation air is required in building. If so,
determine the minimum amount to be supplied by each
unit and record quantity of ventilation air needed for use
in Step 8.
2. Remove filter access panel by raising panel and swinging
panel outward. Panel is now disengaged from track and
can be removed. No tools are required to remove filter ac-
cess panel. Remove outdoor-air opening panel. Save pan-
els and screws. See Fig. 17. Remove optional economizer
and outdoor-air damper hood package from filter section.
3. Assemble outdoor-air hood top and side plates as shown
in Fig. 18. Install seal strips on hood top and sides. Put
aside screen retainer and retainer screw for later assem-
bly. Do not attach hood to unit at this time.
4. On 012 and 014 units, install vertical discharge block-off
plate on right side over return air duct opening. See
Fig. 19.
5. a. Slide economizer into unit and secure with screws.
See Fig. 20.
NOTE: Be sure to engage rear economizer flange under tabs at
rear of vertical return-air opening.
b. Remove screw and discard from barometric relief
damper. See Fig. 20.
6. To convert to horizontal discharge application:
FILTER ACCESS
PANEL
OUTDOOR-AIR
a. Rotate the economizer 90 degrees until the econo-
mizer motor faces the condenser section (see
Fig. 21).
OPENING PANEL
Fig. 17 — Access Panel Locations
b. Rotate the barometric relief damper hinge
90 degrees. Barometric relief damper should open
vertically to operate properly.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
ECONOMIZER
CONTROL BOARD
ECONOMIZER
PLUG
ECONOMIZER
MOTOR
TOP
SCREW
SHIPPING
SCREW
Fig. 20 — Durablade Economizer Installed in Unit
ECONOMIZER CONTROL BOARD
ECONOMIZER MOTOR
Fig. 18 — Outdoor-Air Hood Details
POSITION SETTING BRACKET
Fig. 21 — Horizontal Durablade Economizer
Installation (90 Degree Rotation)
Fig. 19 — Vertical Discharge Block-Off Plate
(48TF012, 014 Units Only)
BLOCK-OFF PLATE
Fig. 22 — Horizontal Discharge Block-Off Plate
13
Download from Www.Somanuals.com. All Manuals Search And Download.
OAT
(TERMINALS ARE UP)
Example:
TOP
Given —
Negative Pressure . . . . . . . . . . . . . . . . . . . . . . . . . 25 Pa (0.1 in. wg)
Outdoor Airflow . . .. . . . . . . . . . . . . . . . . . . . . . . . 520 L/s (1100 cfm)
Determine —
Setting = 150 mm (6 in.)
Fig. 23 — Durablade Economizer Damper Minimum
UNIT
Position Setting
OUTSIDE AIR
SCREEN
0
ENTHALPY
CONTROL
1
2
3
4
HOOD
5
6
7
8
9
Fig. 25 — Outdoor-Air Thermostat/
Enthalpy Control Installation
Fig. 24 — Durablade Economizer Minimum
Position Damper Setting
14
Download from Www.Somanuals.com. All Manuals Search And Download.
ECONOMI$ER
PLUG
CONTROLLER
GEAR-DRIVEN
DAMPER
ACTUATOR
Fig. 26 — Wiring Connections for
Outdoor-Air Thermostat
175
150
0.70
0.60
OUTDOOR AIR
TEMPERATURE
SENSOR
125
100
0.50
0.40
BAROMETRIC
RELIEF DAMPERS
Fig. 28 — EconoMi$er Component Locations
75
0.30
0.20
0.10
50
25
0
0.00
200
100
400
600
CFM
800
1000
1200
570
0
200
300
L/s
400
500
Fig. 27 — Durablade Economizer Barometric Relief
Damper Characteristics
OPTIONAL ECONOMI$ER — See Fig. 28 for EconoMi$er
component locations.
1. To remove the existing unit filter access panel, raise the
panel and swing the bottom outward. The panel is now
disengaged from the track and can be removed. Remove
the indoor coil access panel and discard. See Fig. 29.
FILTER ACCESS
PANEL
OUTDOOR-AIR
OPENING PANEL
NOTE: If installing an optional Power Exhaust Assembly,
refer to the EconoMi$er Power Exhaust Installation Instruc-
tions, then proceed to Step 6. Controller should be mounted in
vertical position as shown in Fig. 28.
Fig. 29 — Typical Access Panel Locations
2. To assemble the hood assembly remove the EconoMi$er
hood from its packaging. Locate the outdoor air opening
panel. See Fig. 30.
OUTDOOR AIR
OPENING PANEL
EXHAUST AIR
HOOD TOP
3. Install the 19 mm x 19 mm (3/4 x 3/4-in.) seal strip on the
exhaust air hood top panel. Install the 3 mm x 22 mm
(1/8 x 7/8-in.) seal strip on the exhaust air hood side panels
and bottom brackets. Assemble the exhaust air hood to
the outdoor air opening panel as shown in Fig. 30, using
the screws provided. Do not attach hood assembly to unit
at this time.
SCREEN
RETAINER
EXHAUST AIR
HOOD SIDES
SEAL STRIP
7
4. Install the 3 mm x 22 mm (1/8 x /8-in. seal strip on the
outdoor air hood top and side panels. Assemble the out-
door air hood to the outdoor air opening panel as shown
in Fig. 31, using the screws provided. Do not attach com-
pleted hood (Fig. 32) assembly to the unit at this time.
EXHAUST AIR SCREEN
EXHAUST AIR
BOTTOM BRACKET
Fig. 30 — Exhaust Air Hood Assembly
15
Download from Www.Somanuals.com. All Manuals Search And Download.
OUTDOOR AIR
OPENING
PANEL
SEAL STRIP
OUTDOOR AIR
HOOD TOP
BLOWER
FILTER
SCREEN
RETAINER
OUTDOOR AIR
INLET
SCREENS
INSTALL
SEAL STRIP
RETURN AIR
BLOCK-OFF
PLATE
ASSEMBLED
EXHAUST HOOD
OUTDOOR AIR
HOOD SIDES
Fig. 31 — Outdoor Air Hood Assembly
REMOVE FACTORY INSTALLED
BLOCK-OFF PLATE
(008 AND 012 UNITS ONLY)
Fig. 33 — Return Air Block-Off Plate Installation
(48TF014 Units Only)
ECONOMIZER CLIP
HVAC UNIT
UNIT FILTER
RACK
ECONOMIZER
UNIT BASE
Fig. 32 — Completed Hood Assembly
ECONOMIZER REAR
FLANGE
Fig. 34 — Rear EconoMi$er Flange Installation
5. Slide the outdoor air inlet screens into the screen track on
the hood side panels. While holding the screens in place,
fasten the screen retainer to the hood using the screws
provided. Repeat the process for the barometric exhaust
air screen. Do not attach hood assembly to unit at this
time.
6. For 48TF014 units, install the return air block-off plate
over the return air duct opening. See Fig. 33.
WIRING HARNESS
NOTE: For 48TF008 and 012 units, remove the factory-
installed block-off plate. See Fig. 33.
7. Slide the EconoMi$er assembly into the rooftop unit. See
Fig. 34 and 35.
OUTDOOR AIR
BLOCK-OFF PLATE
NOTE: Be sure to engage rear EconoMi$er flange under tabs in
return air opening of the unit base. See Fig. 34.
8. Install the outdoor air block-off plate, then secure the
EconoMi$er with the screws provided. See Fig. 35.
9. Remove and store the 12-pin jumper plug from the unit
wiring harness located in the upper left corner and insert
the EconoMi$er plug into the unit wiring harness. Refer
to wiring diagram Fig. 36 and 37. Also refer to Fig. 38 if
installing an accessory power exhaust.
Fig. 35 — EconoMi$er Installed in
48TF008 and 012 Units
10. Install the complete hood assembly on the unit and secure
using the screws provided.
11. Remove the indoor fan motor access panel.
12. Mount the supply air temperature sensor to the lower left
portion of the indoor blower housing with the two (2)
screws provided (see Fig. 39). Connect the violet and
pink wires to the corresponding connections on the sup-
ply air temperature sensor. Replace the indoor fan motor
access panel.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
OAT
—
Outdoor-Air Thermostat
Fig. 36 — EconoMi$er Wiring
ECONOMI$ER
CONTROLLER
BROWN
TEMP
VIOLET
TEMP
OUTDOOR
AIR
OAT
COM
OAH
+15 V
RAT
COM
OUT
PWR
SENSOR
WHITE
RED
BROWN
TEMP
VIOLET
WHITE
RETURN
AIR
SENSOR
TEMP
COM
OUT
COM
RAH
RED
+15 V
PWR
CO2
V+
SENSOR
24
(+)
CO2
CO2 COM
COM VAC
DAT
COM
REM POT
COM
SUPPLY AIR
TEMPERATURE SENSOR
PINK
TEMP
TEMP
LED
COM
VIOLET
Fig. 37 — EconoMi$er Sensor Wiring
17
Download from Www.Somanuals.com. All Manuals Search And Download.
TO FUSED
DISCONNECT
RED YEL BLU
GRAY
H4
H1
H3
H2
X2 X3
X4
X1
FIELD SUPPLIED
WIRING
SECONDARY
230VAC
BLACK
BLACK
LT. BLUE
B
A
3
2
1
9
8
7
6
5
4
BLACK
BROWN
FAN 1
R1
24 VAC
3-PIN
CONNECTOR
PLUG
C1
GREEN/
YELLOW
4-PIN
CONNECTOR
PLUG
2 x 4 IN.
HANDY BOX
BLUE
ORANGE
1
YELLOW
2
L1
L2
BLACK L1
1
2
3
4
1
2
BLUE
L2
BROWN
3
GREEN GND
GND
BLACK
BLUE
3
4
BLACK
LT. BLUE
230 VAC
1 PHASE
GREEN
B
A
3
2
1
9
8
7
6
5
BLACK
R2
24 VAC
BROWN
C1
FAN 2
GREEN/
YELLOW
4
BLUE
Fig. 38 — Wiring Diagram for Power Exhaust System
SUPPLY AIR
TEMPERATURE
SENSOR
MOUNTING
LOCATION
SUPPLY AIR
TEMPERATURE
SENSOR
Fig. 39 — Supply Air Sensor Placement
18
Download from Www.Somanuals.com. All Manuals Search And Download.
CO2 Control Set Up — If a CO2 sensor is not being used, pro-
ceed to the next section. If a CO2 sensor is being used, perform
the following:
4. Calculate the minimum airflow across the EconoMi$er.
a. Calculate % of outside air using the following
formula.
1. Determine the value at which you want the minimum
position of the dampers to begin opening to allow a great-
er amount of outdoor air to enter. The range is 800 to
1,400 ppm.
% Outdoor air through EconoMi$er
Mixture Temp – Return Air Temp
% Outdoor air =
Outdoor Temp – Return Air Temp
2. Locate the CO2 SP (PPM) potentiometer and adjust to the
desired set point. See Fig. 40.
b. Multiply total CFM by percentage outdoor air, this
gives outdoor air volume in CFM.
Mechanical Cooling Lockout — Determine the outdoor-air
temperature at which you want the mechanical cooling (com-
pressors) to be disabled. Locate the mechanical cooling lockout
(MECH CLG LOCKOUT) potentiometer. To disable this fea-
ture, turn the potentiometer counterclockwise (CCW) to the
OFF position. Otherwise, set the value between –12 and 15 C
(10 and 60 F). Mechanical cooling will not operate when the
outdoor air temperature is below this value. See Fig. 40.
Dry Bulb Changeover Set Up — Determine the dry bulb
changeover set point from Table 4. The settings are A, B, C and
D. Locate the ECON SP potentiometer and set the dry bulb
changeover set point. See Fig. 40. When the OAT is above this
set point, the damper is limited to minimum position setting.
5. Turn on base unit power.
NOTE: The EconoMi$er begins operation three min-
utes after power up.
Personal Injury Hazard. Avoid possible injury by keep-
ing fingers away from damper blades.
6. See Fig. 41 for barometric relief damper characteristics.
Table 4 — Changeover Set Points
SETTINGS
Dry Bulb C (°F)
A
23
B
21
C
19
D
17
(73) (69) (66) (63)
63
58
56
51
Single Enthalpy* KJ/Kg (Btu/lb)
(27) (25) (24) (22)
Differential Temperature* C
1.1
(2)
2
(1)
1.1
(2)
2
(1)
1.1
(2)
2
(1)
1.1
(2)
2
(1)
(°F, Not Adjustable)
Fig. 40 — EconoMi$er Control Adjustment
Differential Enthalpy* KJ/Kg
(Btu/lb, Not Adjustable)
Potentiometers (Factory Settings)
*Field-installed accessory.
If a potentiometer fails, its setting will default to the values
in Table 5.
125
0.5
100
0.4
Table 5 — Default Potentiometer Settings
75
POTENTIOMETER
CO2 SP (PPM)
MECH CLG LOCKOUT, C (F)
ECON SP
DEFAULT SETTING
0.3
1,000
8.3 (47)
D
50
0.2
25
0.1
MIN POS (%)
20
0
Ventilation Air (Minimum Position Set Up) — If ventilation
air is not required, proceed to Step 5. If ventilation air is re-
quired, perform the following:
1. The indoor fan must be on to set the ventilation air. Either
put the thermostat in the continuous fan mode or jumper
the R and G terminals at the rooftop unit connection
board.
0
800
1200 1600 2000 2400
0
0
400
200
FLOW (CUBIC FEET/MINUTE)
600 800
1000 1200
400
FLOW (L/s)
Fig. 41 — EconoMi$er Barometric Relief Capacity
2. Locate the minimum position (MIN POS) potentiometer.
Turn the potentiometer full CCW to fully close the out-
door air dampers. Turn the potentiometer gradually
clockwise (CW) to the desired position. See Fig. 40.
3. Replace the filter access panel. See Fig. 21. Ensure the fil-
ter access panel slides along the tracks and is securely
engaged.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 9 — Adjust Evaporator-Fan Speed — Ad-
just evaporator-fan speed to meet jobsite requirement.
Table 6 shows motor performance. Tables 7 and 8 show fan
rpm at motor pulley settings, Table 9 shows motor efficiencies
and Tables 10 and 11 give accessory static pressure drops. Re-
fer to Tables 12-23 to determine fan speed settings. Fan motor
pulleys are factory set for speed shown in Table 1A or 1B.
To change fan speed:
1. Shut off unit power supply and install lockout tag.
2. Loosen belt by loosening fan motor mounting plate nuts
(see Fig. 42 and 43).
MOTOR MOUNTING
PLATE NUTS
3. Loosen movable pulley flange setscrew (see Fig. 44).
4. Screw movable flange toward fixed flange to increase fan
speed and away from fixed flange to decrease fan speed.
Increasing fan speed increases load on motor. Do not ex-
ceed maximum speed specified in Table 1A or 1B.
Fig. 42 — Typical Belt-Drive Motor Mounting
for Size 008
5. Set movable flange at nearest flat of pulley hub and tight-
en setscrew (see Table 1A or 1B for speed change for
each full turn of pulley flange).
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from
mounting plate.
To adjust belt tension (see Fig. 42 and 43):
1. Loosen fan motor mounting nuts.
2. Size 008 — Slide motor mounting plate away from fan
scroll for proper belt tension (13 mm [1/2-in.] deflection
with 3.6 to 4.5 kg [8 to 10 lbs] of force) and tighten
mounting nuts. See Fig. 42.
Fig. 43 — Typical Belt-Drive Motor Mounting
Sizes 012,014 — Slide motor mounting plate downward
to tighten belt tension (13 mm [1/2-in.] deflection with 2.3
to 4.5 kg [5 to 10 lbs] of force) and tighten mounting nuts.
See Fig. 43.
for Sizes 012,014
3. Adjust bolt and nut on mounting plate to secure motor in
fixed position. See Fig. 44.
Realign fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from
mounting plate.
Fig. 44 — Evaporator-Fan Pulley Adjustment
Table 6 — Evaporator-Fan Motor Performance
MAXIMUM ACCEPTABLE
CONTINUOUS
BkW*
MAXIMUM ACCEPTABLE
MAXIMUM ACCEPTABLE
OPERATING
UNIT
48TF
UNIT RATED
VOLTAGE
MAXIMUM
AMP DRAW
CONTINUOUS
BHP*
WATTS
008
012
014
400
400
400
2.76
2.76
2.76
2.90
3.70
3.70
2615
3313
3313
3.6
5.0
5.0
LEGEND
BHP — Brake Horsepower
BkW — kW x Motor Efficiency
*Extensive motor and electrical testing on these units ensures that
the full range of the motors can be utilized with confidence. Using
your fan motors up to the ratings shown in this table will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 7 — Fan R/s at Motor Pulley Settings (SI)
MOTOR PULLEY TURNS OPEN
UNIT
48TF
1
0
/
1
11/2
2
21/2
3
31/2
9.25
4
41/2
8.55
9.85
12.30
5
2
11.70
13.00
15.00
11.35
12.65
14.70
11.00
12.30
14.40
10.65
11.95
14.10
10.30
11.60
13.80
9.95
9.60
10.90
13.20
8.90
10.20
12.60
8.20
9.50
12.00
008
012
014
11.25
13.50
10.55
12.90
Table 8 — Fan Rpm at Motor Pulley Settings (English)
MOTOR PULLEY TURNS OPEN
UNIT
48TF
1
0
/
1
11/2
639
718
843
2
21/2
597
676
807
3
31/2
555
634
771
4
41/2
513
592
735
5
2
700
779
900
681
760
883
660
739
865
618
697
825
576
655
789
534
613
753
492
571
717
008
012
014
Table 9 — Evaporator-Fan Motor Efficiency
MOTOR
48TF
EFFICIENCY (%)
D/E/F008
D/E/F012
D/E014
80
80
85
NOTE: Convert watts to bhp using the following formula:
watts input x motor efficiency
bhp =
746
Table 10 — Accessory/FIOP Static Pressure Drop (Pa) — 48TF008-014
DURABLADE ECONOMIZER
UNIT 48TF
008-014
RATED VOLTAGE
L/s
ECONOMI$ER
PRESSURE DROP
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
5
6
—
—
—
31
35
41
50
59
67
75
84
90
97
7
8
9
10
11
12
13
14
15
16
17
All
FIOP — Factory-Installed Option
Table 11 — Accessory/FIOP Static Pressure Drop (in. wg) — 48TF008-014
DURABLADE ECONOMIZER
UNIT 48TF
008-014
RATED VOLTAGE
CFM
ECONOMI$ER
PRESSURE DROP
2200
2500
3000
3500
4000
4500
5000
5500
6000
.02
.02
.03
.04
.05
.06
.07
.08
.09
.07
.09
.13
.18
.23
.30
.36
—
All
—
FIOP — Factory-Installed Option
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 12 — Fan Performance, 48TF008 — Vertical Discharge Units (SI)
EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW
(L/s)
50
200
100
150
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
1150
1200
1275
1300
1400
1450
1500
1550
1600
1650
1700
1750
1800
1850
1900
8.8
9.0
9.3
9.6
9.9
10.1
10.4
10.7
11.0
11.3
11.5
11.8
12.2
12.4
12.8
0.45
0.47
0.53
0.58
0.63
0.68
0.78
0.81
0.90
0.99
1.06
1.16
1.24
1.35
1.47
10.1
10.3
10.5
10.8
11.1
11.3
11.5
11.8
12.0
12.4
12.6
12.9
13.2
13.4
13.7
0.62
0.65
0.70
0.78
0.85
0.86
0.96
1.06
1.10
1.22
1.30
1.38
1.49
1.60
1.70
11.2
11.4
11.6
11.9
12.1
12.3
12.6
12.8
13.0
13.3
13.6
13.8
14.1
14.4
14.6
0.79
0.82
0.89
0.96
1.02
1.09
1.18
1.25
1.35
1.43
1.54
1.65
1.75
1.84
1.97
12.2
12.4
12.6
12.8
13.1
13.2
13.5
13.7
14.0
14.2
14.4
14.7
14.9
15.1
15.4
0.96
1.02
1.08
1.17
1.26
1.29
1.38
1.48
1.56
1.67
1.78
1.88
2.00
2.10
2.24
EXTERNAL STATIC PRESSURE (Pa)
300 350
AIRFLOW
(L/s)
250
400
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
1150
1200
1275
1300
1400
1450
1500
1550
1600
1650
1700
1750
1800
1850
1900
13.2
13.3
13.5
13.8
14.0
14.1
14.4
14.5
14.8
15.0
15.2
15.5
15.7
15.9
16.2
1.15
1.21
1.28
1.37
1.45
1.53
1.61
1.72
1.80
1.92
2.01
2.14
2.24
2.37
2.51
14.1
14.1
14.3
14.6
14.7
14.9
15.2
15.4
15.6
15.8
16.0
16.2
16.4
16.7
16.9
1.39
1.41
1.46
1.55
1.65
1.73
1.84
1.95
2.07
2.15
2.27
2.41
2.52
2.66
2.78
15.1
15.2
15.3
15.2
15.5
15.6
15.8
16.1
16.3
16.6
16.7
16.9
17.2
17.4
—
1.73
1.76
1.76
1.72
1.84
1.88
2.04
2.15
2.29
2.42
2.56
2.65
2.82
2.92
—
15.8
15.9
16.1
16.3
16.5
16.7
16.4
16.5
17.0
17.2
17.5
17.6
—
1.96
2.00
2.17
2.17
2.10
2.10
2.18
2.34
2.49
2.66
2.80
2.92
—
—
—
—
—
LEGEND
BkW — Fan Input kW x Motor Efficiency
R/s
Revolutions Per Second of Blower Wheel
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 5.)
2. indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
5. Standard drive range is 8.2 to 11.7 r/s. All other speeds require
a field-supplied drive.
—
6. Maximum continuous BkW is 1.79. Extensive motor and electri-
cal testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 13 — Fan Performance, 48TF012 — Vertical Discharge Units (SI)
EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW
(L/s)
50
200
100
150
250
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
1500
1550
1600
1650
1700
1750
1800
1850
1900
1950
2000
2050
2100
2150
2200
2250
2300
2400
2450
9.8
10.0
10.3
10.6
10.9
11.1
11.4
11.7
12.0
12.2
12.5
12.8
13.1
13.3
13.6
13.9
14.2
14.5
14.8
0.55
0.60
0.66
0.72
0.78
0.86
0.93
1.00
1.08
1.16
1.25
1.34
1.44
1.53
1.64
1.75
1.86
1.98
2.10
10.9
11.2
11.4
11.7
12.0
12.2
12.5
12.7
12.9
13.2
13.4
13.7
13.9
14.2
14.5
14.7
15.0
15.3
15.6
0.67
0.74
0.80
0.86
0.93
1.00
1.08
1.15
1.23
1.31
1.40
1.50
1.60
1.71
1.82
1.94
2.06
2.19
2.32
12.0
12.2
12.4
12.6
12.8
13.1
13.3
13.6
13.8
14.1
14.3
14.6
14.9
15.1
15.3
15.6
15.8
16.1
—
0.79
0.86
0.92
0.98
1.06
1.14
1.22
1.31
1.40
1.49
1.59
1.69
1.80
1.91
2.02
2.13
2.25
2.38
—
12.9
13.1
13.3
13.6
13.7
14.0
14.2
14.4
14.6
14.8
15.1
15.3
15.6
15.8
16.1
16.3
16.6
—
0.92
0.98
1.05
1.12
1.20
1.28
1.36
1.44
1.53
1.63
1.74
1.85
1.97
2.09
2.21
2.34
2.47
—
13.8
13.9
14.2
14.4
14.6
14.8
15.0
15.2
15.4
15.6
15.9
16.1
16.3
16.5
16.8
—
1.04
1.11
1.18
1.25
1.34
1.42
1.52
1.60
1.70
1.79
1.90
2.00
2.12
2.24
2.37
—
—
—
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (Pa)
400
AIRFLOW
(L/s)
300
450
350
500
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
1500
1550
1600
1650
1700
1750
1800
1850
1900
1950
2000
2050
2100
2150
2200
2250
2300
2400
2450
14.6
14.8
15.0
15.1
15.3
15.5
15.8
16.0
16.2
16.4
16.6
16.8
17.0
17.2
—
1.15
1.23
1.30
1.39
1.47
1.56
1.66
1.75
1.86
1.96
2.07
2.18
2.30
2.41
—
15.3
15.5
15.7
15.9
16.1
16.3
16.4
16.6
16.9
17.1
17.3
17.5
—
—
—
—
—
—
—
1.26
1.35
1.44
1.52
1.61
1.70
1.80
1.90
2.01
2.12
2.24
2.36
—
—
—
—
—
—
—
16.1
16.2
16.4
16.6
16.8
17.0
17.2
17.3
17.5
17.7
17.9
—
—
—
—
—
—
—
—
1.38
1.47
1.55
1.65
1.74
1.85
1.95
2.05
2.16
2.26
2.39
—
—
—
—
—
—
—
—
16.9
17.1
17.1
17.3
17.4
17.6
17.8
18.0
18.2
18.4
—
—
—
—
—
—
—
—
—
1.45
1.60
1.68
1.77
1.88
1.98
2.09
2.20
2.31
2.43
—
—
—
—
—
—
—
—
—
17.7
17.8
17.9
18.0
18.1
18.2
18.4
18.6
—
—
—
—
—
—
—
—
—
—
—
1.68
1.81
1.86
1.91
2.00
2.11
2.22
2.34
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
5. Standard drive range is 9.5 to 13.0 r/s. All other speeds require
a field-supplied drive.
BkW — Fan Input kW x Motor Efficiency
R/s
Revolutions Per Second of Blower Wheel
6. Maximum continuous BkW is 1.79. Extensive motor and electri-
cal testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
—
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 5.)
2. indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 14 — Fan Performance, 48TF014 — Vertical Discharge Units (SI)
EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW
(L/s)
50
200
100
150
250
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
1900
1950
2000
2050
2100
2150
2250
2300
2350
2400
2450
2500
2550
2600
2650
2700
2750
2800
2850
2900
2950
3000
3050
3100
12.5
12.7
13.0
13.3
13.6
13.9
14.2
14.5
14.8
15.0
15.4
15.7
15.9
16.2
16.5
16.8
17.1
17.4
17.7
18.0
18.3
18.6
18.9
19.2
1.10
1.18
1.27
1.36
1.46
1.56
1.67
1.78
1.89
2.01
2.16
2.28
2.43
2.58
2.72
2.89
3.05
3.21
3.40
3.57
3.76
3.96
4.15
4.38
13.5
13.7
14.0
14.3
14.5
14.8
15.1
15.4
15.7
15.9
16.2
16.5
16.8
17.1
17.3
17.6
17.9
18.2
18.5
18.8
19.1
19.4
19.6
—
1.27
1.36
1.46
1.56
1.66
1.78
1.89
2.00
2.13
2.25
2.38
2.52
2.65
2.81
2.95
3.12
3.28
3.45
3.64
3.81
4.02
4.21
4.40
—
14.4
14.6
14.9
15.1
15.4
15.7
15.9
16.2
16.4
16.7
17.0
17.3
17.5
17.8
18.1
18.4
18.7
18.9
19.2
19.5
19.8
20.1
—
1.42
1.52
1.62
1.72
1.84
1.95
2.07
2.19
2.32
2.46
2.60
2.75
2.90
3.05
3.22
3.39
3.56
3.74
3.93
4.11
4.29
4.51
—
15.3
15.5
15.7
16.0
16.2
16.5
16.7
17.0
17.2
17.5
17.7
18.0
18.2
18.5
18.8
19.0
19.3
19.6
19.9
20.2
—
1.63
1.73
1.81
1.91
2.01
2.13
2.24
2.37
2.51
2.64
2.79
2.95
3.10
3.26
3.43
3.60
3.80
3.98
4.18
4.37
—
16.1
16.4
16.6
16.8
17.0
17.3
17.5
17.7
18.0
18.2
18.5
18.7
18.0
19.2
19.4
19.7
20.0
20.2
20.5
—
1.81
1.92
2.02
2.14
2.25
2.37
2.48
2.60
2.72
2.85
2.99
3.13
3.29
3.47
3.64
3.83
4.01
4.19
4.41
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (Pa)
400
AIRFLOW
(L/s)
300
450
350
500
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
1900
1950
2000
2050
2100
2150
2250
2300
2350
2400
2450
2500
2550
2600
2650
2700
2750
2800
2850
2900
2950
3000
3050
3100
17.0
17.2
17.4
17.6
17.8
18.0
18.2
18.5
18.7
18.9
19.2
19.4
19.6
19.9
20.1
20.4
20.6
20.9
—
2.00
2.11
2.22
2.33
2.45
2.59
2.71
2.85
2.99
3.12
3.27
3.38
3.54
3.69
3.86
4.03
4.21
4.40
—
17.9
18.0
18.2
18.4
18.6
18.8
19.0
19.2
19.4
19.6
19.8
20.1
20.3
20.5
20.8
21.0
—
—
—
—
—
—
—
—
2.21
2.31
2.43
2.54
2.66
2.79
2.93
3.05
3.21
3.36
3.53
3.67
3.83
4.01
4.16
4.32
—
—
—
—
—
—
—
—
18.7
18.8
19.0
19.2
19.3
19.5
19.7
19.9
20.1
20.3
20.5
20.7
21.0
21.2
21.4
—
—
—
—
—
—
—
—
—
2.39
2.51
2.63
2.76
2.89
3.01
3.15
3.29
3.43
3.59
3.74
3.93
4.09
4.27
4.44
—
—
—
—
—
—
—
—
—
19.4
19.6
19.8
19.9
20.1
20.3
20.4
20.6
20.8
21.0
21.2
21.4
21.6
—
—
—
—
—
—
—
—
—
2.58
2.71
2.84
2.97
3.10
3.24
3.37
3.52
3.67
3.82
3.99
4.15
4.33
—
—
—
—
—
—
—
—
—
20.1
20.3
20.5
20.7
20.8
21.0
21.2
21.3
21.5
21.7
—
—
—
—
—
—
—
—
—
2.74
2.88
3.02
3.17
3.32
3.46
3.60
3.76
3.92
4.08
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
5. Standard drive range is 12.0 to 15.0 r/s. All other speeds
require a field-supplied drive.
BkW — Fan Input kW x Motor Efficiency
R/s
Revolutions Per Second of Blower Wheel
6. Maximum continuous BkW is 2.76. Extensive motor and electri-
cal testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
—
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 5.)
2. indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 15 — Fan Performance, 48TF008 — Horizontal Discharge Units (SI)
EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW
(L/s)
50
200
100
150
225
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
1075
1125
1150
1200
1250
1300
1400
1450
1500
1550
1600
1650
1700
1750
1800
1850
1900
8.1
8.4
8.6
8.9
9.1
9.4
9.7
10.0
10.2
10.5
10.8
11.1
11.4
11.7
12.0
12.2
12.5
0.34
0.39
0.42
0.46
0.51
0.56
0.62
0.67
0.74
0.80
0.88
0.97
1.04
1.12
1.23
1.33
1.42
9.5
9.7
9.9
0.49
0.53
0.58
0.64
0.70
0.75
0.82
0.88
0.94
1.02
1.09
1.17
1.25
1.35
1.45
1.54
1.65
10.7
10.9
11.1
11.3
11.5
11.7
12.0
12.2
12.4
12.7
12.9
13.2
13.4
13.7
13.9
14.2
14.4
0.66
0.71
0.76
0.81
0.87
0.93
0.99
1.07
1.15
1.23
1.32
1.41
1.51
1.61
1.70
1.81
1.92
11.8
12.0
12.2
12.4
12.6
12.7
12.9
13.2
13.4
13.6
13.8
14.0
14.3
14.5
14.8
15.0
15.2
0.81
0.89
0.96
1.02
1.08
1.14
1.22
1.27
1.36
1.44
1.53
1.63
1.73
1.85
1.95
2.08
2.20
12.4
12.5
12.7
12.8
13.0
13.2
13.4
13.6
13.8
14.0
14.2
14.4
14.7
14.9
15.1
15.4
15.6
0.92
0.98
1.05
1.11
1.19
1.25
1.33
1.40
1.48
1.56
1.65
1.75
1.85
1.97
2.07
2.20
2.34
10.2
10.4
10.7
10.9
11.2
11.4
11.7
11.9
12.2
12.4
12.7
13.0
13.2
13.5
EXTERNAL STATIC PRESSURE (Pa)
300 350
AIRFLOW
(L/s)
250
400
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
1075
1125
1150
1200
1250
1300
1400
1450
1500
1550
1600
1650
1700
1750
1800
1850
1900
12.9
13.0
13.1
13.3
13.5
13.7
13.9
14.1
14.3
14.2
14.8
14.9
15.1
15.3
15.5
15.8
16.0
1.03
1.08
1.13
1.21
1.29
1.37
1.44
1.52
1.60
1.68
1.77
1.86
1.97
2.08
2.20
2.32
2.46
13.9
14.0
14.1
14.3
14.4
14.5
14.7
14.9
15.1
15.3
15.5
15.7
15.9
16.1
16.3
16.5
16.7
1.29
1.34
1.38
1.42
1.48
1.56
1.66
1.77
1.86
1.94
2.04
2.13
2.24
2.35
2.45
2.58
2.70
15.0
15.1
15.2
15.2
15.3
15.4
15.5
15.7
15.9
16.1
16.3
16.5
16.6
16.3
17.0
17.2
17.5
1.60
1.68
1.69
1.74
1.78
1.81
1.84
1.97
2.08
2.21
2.31
2.42
2.52
2.64
2.76
2.87
2.99
15.7
15.9
16.0
16.0
16.2
16.3
16.4
16.5
16.6
16.8
17.0
17.2
17.4
17.6
17.7
17.9
18.1
1.89
1.92
1.96
2.01
2.06
2.09
2.19
2.18
2.29
2.43
2.55
2.70
2.82
2.94
3.05
3.19
3.31
LEGEND
5. Standard drive range is 8.2 to 11.7 r/s. All other speeds require
a field-supplied drive.
BkW — Fan Input kW x Motor Efficiency
R/s
Revolutions Per Second of Blower Wheel
6. Maximum continuous BkW is 1.79. Extensive motor and electri-
cal testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
—
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 5.)
2. indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 16 — Fan Performance, 48TF012 — Horizontal Discharge Units (SI)
EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW
(L/s)
50
200
100
150
250
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
1500
1550
1600
1650
1700
1750
1800
1850
1900
1950
2000
2050
2100
2150
2200
2300
2350
2400
2500
9.1
9.4
9.6
0.49
0.54
0.59
0.65
0.71
0.77
0.84
0.92
1.00
1.09
1.18
1.28
1.38
1.49
1.61
1.74
1.86
2.00
—
10.5
10.7
10.9
11.1
11.3
11.5
11.7
11.9
12.1
12.3
12.6
12.8
13.0
13.2
13.4
13.7
13.9
14.2
14.4
0.63
0.68
0.73
0.80
0.86
0.92
0.98
1.04
1.14
1.22
1.31
1.40
1.50
1.60
1.70
1.81
1.93
2.05
2.14
11.6
11.8
12.0
12.2
12.4
12.6
12.8
13.0
13.2
13.4
13.6
13.8
14.0
14.2
14.4
14.6
14.8
15.0
15.2
0.77
0.82
0.88
0.95
1.01
1.07
1.14
1.21
1.29
1.38
1.47
1.56
1.64
1.73
1.83
1.93
2.03
2.14
2.25
12.6
12.8
13.0
13.2
13.4
13.5
13.7
13.9
14.1
14.3
14.5
14.7
14.9
15.1
15.3
15.5
15.7
—
0.89
0.96
1.02
1.09
1.16
1.23
1.30
1.39
1.47
1.55
1.65
1.73
1.82
1.93
2.04
2.15
2.27
—
13.5
13.7
13.9
14.1
14.2
14.4
14.6
14.8
15.0
15.2
15.3
15.5
15.8
15.9
16.1
—
0.99
1.06
1.14
1.22
3.10
1.38
1.47
1.55
1.64
1.72
1.82
1.92
2.02
2.13
2.24
—
9.8
10.1
10.3
10.6
10.8
11.1
11.3
11.6
11.9
12.1
12.4
12.7
12.9
13.2
13.5
—
—
—
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (Pa)
400
AIRFLOW
(L/s)
300
450
350
500
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
1500
1550
1600
1650
1700
1750
1800
1850
1900
1950
2000
2050
2100
2150
2200
2300
2350
2400
2500
14.5
14.6
14.8
14.9
15.0
15.2
15.4
15.6
15.8
16.0
16.2
16.3
16.5
16.7
16.9
—
1.13
1.20
1.26
1.33
1.42
1.51
1.61
1.71
1.80
1.91
2.01
2.10
2.21
2.32
2.43
—
15.2
15.4
15.6
15.7
15.9
16.0
16.2
16.3
16.5
16.7
16.9
17.1
—
—
—
—
—
—
—
1.22
1.30
1.40
1.48
1.56
1.64
1.73
1.84
1.94
2.06
2.17
2.29
—
—
—
—
—
—
—
16.1
16.2
16.3
16.5
16.7
16.8
17.0
17.1
17.2
17.4
17.6
—
—
—
—
—
—
—
—
1.40
1.43
1.50
1.60
1.70
1.79
1.89
1.98
2.07
2.19
2.31
—
—
—
—
—
—
—
—
16.8
16.9
17.1
17.2
17.3
17.5
17.7
17.8
18.0
—
—
—
—
—
1.54
1.60
1.68
1.72
1.81
1.91
2.03
2.15
2.24
—
—
—
—
—
17.7
17.8
17.9
18.0
18.0
18.2
18.3
18.5
18.7
—
—
—
—
—
1.82
1.86
1.91
1.97
1.97
2.04
2.15
2.27
2.40
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
BkW — Fan Input kW x Motor Efficiency
R/s
Revolutions Per Second of Blower Wheel
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 5.)
2. indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
5. Standard drive range is 9.5 to 13.0 r/s. All other speeds require
a field-supplied drive.
6. Maximum continuous BkW is 1.79. Extensive motor and electri-
cal testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
—
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 17 — Fan Performance, 48TF014 — Horizontal Discharge Units (SI)
EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW
(L/s)
50
200
100
150
225
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
1900
1950
2000
2050
2100
2150
2200
2250
2325
2400
2450
2500
2550
2600
2650
2700
2750
2800
2850
2900
2950
3000
3050
3100
11.5
11.8
12.1
12.3
12.6
12.8
13.1
13.3
13.6
13.9
14.1
14.4
14.7
14.9
15.2
15.4
15.7
15.9
16.2
16.5
16.7
17.0
17.3
17.5
0.96
1.04
1.12
1.18
1.27
1.36
1.44
1.53
1.63
1.74
1.84
1.95
2.07
2.18
2.32
2.44
2.57
2.71
2.86
2.98
3.11
3.25
3.38
3.52
12.7
12.9
13.2
13.4
13.6
13.9
14.1
14.4
14.6
14.9
15.1
15.4
15.6
15.8
16.1
16.4
16.6
16.9
17.1
17.3
17.6
17.8
18.1
18.3
1.14
1.22
1.29
1.38
1.46
1.56
1.66
1.75
1.87
1.98
2.10
2.22
2.34
2.47
2.60
2.74
2.89
3.03
3.18
3.32
3.46
3.60
3.74
3.89
13.7
13.9
14.2
14.4
14.6
14.9
15.1
15.3
15.5
15.8
16.0
16.2
16.5
16.7
16.9
17.2
17.4
17.7
17.9
18.2
18.4
18.7
—
1.32
1.40
1.49
1.59
1.68
1.78
1.88
1.99
2.10
2.20
2.31
2.44
2.56
2.69
2.83
2.96
3.11
3.27
3.46
3.57
3.72
3.87
—
14.7
14.9
15.1
15.3
15.5
15.7
16.0
16.2
16.4
16.6
16.8
17.1
17.3
17.5
17.8
18.0
18.2
18.4
18.7
18.9
—
1.49
1.57
1.65
1.75
1.86
1.96
2.07
2.20
2.30
2.44
2.56
2.69
2.83
2.96
3.11
3.26
8.38
3.55
3.70
3.85
—
15.6
15.8
16.0
16.2
16.4
16.6
16.8
17.0
17.2
17.4
17.6
17.8
18.1
18.3
18.5
18.7
19.0
19.2
—
1.71
1.80
1.89
1.96
2.05
2.15
2.26
2.36
2.50
2.64
2.77
2.90
3.05
3.20
3.34
3.51
3.67
3.84
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (Pa)
400
AIRFLOW
(L/s)
300
450
350
500
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
R/s
BkW
1900
1950
2000
2050
2100
2150
2200
2250
2235
2400
2450
2500
2550
2600
2650
2700
2750
2800
2850
2900
2950
3000
3050
3100
16.6
16.7
16.9
17.1
17.2
17.4
17.6
17.8
18.0
18.2
18.4
18.6
18.8
19.0
19.2
19.4
19.7
—
1.91
2.00
2.11
2.20
2.30
2.42
2.52
2.61
2.71
2.83
2.97
3.09
3.25
3.42
3.58
3.73
3.91
—
17.5
17.6
17.8
17.9
18.1
18.2
18.4
18.6
18.8
18.9
19.1
19.3
19.5
19.7
19.9
20.1
—
—
—
—
—
—
—
—
2.11
2.21
2.31
2.42
2.53
2.64
2.76
2.88
3.00
3.13
3.24
3.35
3.49
3.63
3.81
3.92
—
—
—
—
—
—
—
—
18.2
18.4
18.6
18.7
18.9
19.0
19.2
19.4
19.5
19.7
19.9
20.0
20.2
20.4
—
—
—
—
—
—
—
—
—
2.29
2.41
2.52
2.64
2.76
2.88
2.99
3.11
3.26
3.39
3.52
3.66
3.81
3.95
—
—
—
—
—
—
—
—
—
18.9
19.1
19.3
19.5
19.6
19.8
20.0
20.1
20.3
20.5
20.6
20.8
—
—
—
—
—
—
—
—
—
2.44
2.58
2.71
2.84
2.97
3.10
3.23
3.37
3.49
3.64
3.77
3.93
—
—
—
—
—
—
—
—
—
19.3
19.6
19.9
20.1
20.3
20.5
20.7
20.9
21.0
21.2
—
—
—
—
—
—
—
—
—
2.55
2.71
2.87
3.02
3.17
3.31
3.45
3.60
3.75
3.89
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
BkW — Fan Input kW x Motor Efficiency
R/s
Revolutions Per Second of Blower Wheel
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 5.)
2. indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
5. Standard drive range is 12.0 to 15.0 r/s. All other speeds
require a field-supplied drive.
6. Maximum continuous BkW is 2.76. Extensive motor and electri-
cal testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
—
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 18 — Fan Performance, 48TF008 — Vertical Discharge Units (English)
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.8
0.4
0.6
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
2200
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
506
514
521
536
551
559
567
582
598
614
630
646
662
679
695
712
729
745
754
0.52
0.55
0.56
0.63
0.69
0.72
0.75
0.83
0.90
0.98
1.07
1.16
1.26
1.36
1.47
1.59
1.71
1.84
1.91
586
593
600
613
626
634
641
655
670
684
699
714
729
744
759
774
790
805
813
0.72
0.76
0.79
0.85
0.93
0.97
1.00
1.08
1.17
1.25
1.35
1.45
1.55
1.66
1.78
1.90
2.03
2.17
2.24
656
662
668
680
693
700
706
719
732
745
759
773
787
801
816
830
845
860
868
0.95
0.99
1.02
1.09
1.17
1.21
1.25
1.34
1.43
1.53
1.63
1.74
1.86
1.98
2.10
2.23
2.37
2.52
2.59
718
724
730
741
753
759
764
776
789
802
815
828
841
854
867
881
895
909
917
1.18
1.22
1.26
1.34
1.43
1.48
1.52
1.61
1.71
1.81
1.92
2.04
2.16
2.29
2.42
2.56
2.71
2.87
2.95
EXTERNAL STATIC PRESSURE (in. wg)
1.2 1.4
AIRFLOW
(Cfm)
1.0
1.6
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
2200
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
776
781
786
796
808
814
819
831
842
854
866
878
891
904
917
930
943
956
963
1.43
1.78
1.50
1.59
1.69
1.74
1.79
1.89
2.00
2.11
2.23
2.35
2.48
2.61
2.75
2.90
3.05
3.22
3.30
838
841
843
849
859
864
869
880
892
903
915
926
938
950
963
976
988
—
1.78
1.81
1.83
1.88
1.96
2.01
2.06
2.17
2.29
2.42
2.54
2.67
2.81
2.95
3.10
3.25
3.41
—
898
902
905
910
912
915
918
927
938
949
961
972
983
995
1007
—
2.21
2.25
2.28
2.31
2.31
2.34
2.37
2.47
2.58
2.71
2.85
3.00
3.14
3.30
3.45
—
935
939
943
952
963
968
973
976
983
993
1003
1015
1026
—
2.58
2.60
2.62
2.74
2.81
2.81
2.81
2.84
2.92
3.03
3.17
3.32
3.47
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
5. Standard drive range is 492 to 700 rpm. All other rpms require
a field-supplied drive.
Bhp
—
Brake Horsepower at Motor Shaft
Rpm — Revolutions Per Minute of Blower Wheel
6. Maximum continuous bhp is 2.4. Extensive motor and electrical
testing on these units ensures that the full range of the motor
can be utilized with confidence. Using the fan motors up to the
ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 5.)
2.
indicates field-supplied motor and drive are required.
7. Interpolation is permissible. Do not extrapolate.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 19 — Fan Performance, 48TF012 — Vertical Discharge Units (English)
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.8
0.4
0.6
1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
592
607
622
638
653
669
684
700
715
731
747
763
778
794
810
826
842
858
874
890
906
0.76
0.83
0.90
0.98
1.06
1.15
1.24
1.33
1.43
1.54
1.65
1.76
1.88
2.00
2.13
2.27
2.41
2.55
2.70
2.86
3.03
661
676
690
705
719
733
747
760
774
787
801
816
831
846
861
876
892
907
922
938
953
0.93
1.01
1.09
1.17
1.26
1.35
1.44
1.54
1.64
1.74
1.85
1.97
2.10
2.23
2.37
2.52
2.67
2.83
2.99
3.16
3.33
722
734
746
759
772
786
800
814
828
843
857
872
886
900
913
927
940
954
968
—
1.09
1.17
1.25
1.33
1.43
1.53
1.64
1.75
1.86
1.98
2.10
2.23
2.36
2.50
2.64
2.78
2.92
3.08
3.24
—
779
791
803
815
826
838
850
863
875
888
902
916
929
943
958
973
987
1002
—
1.26
1.34
1.43
1.52
1.62
1.72
1.82
1.92
2.04
2.16
2.30
2.44
2.58
2.73
2.89
3.04
3.21
3.38
—
829
840
852
864
876
888
900
912
924
936
948
960
972
985
999
1012
—
1.42
1.51
1.60
1.70
1.81
1.91
2.03
2.14
2.26
2.30
2.51
2.64
2.78
2.93
3.09
3.26
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.8
1.4
2.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
880
890
900
910
921
933
945
957
969
981
993
1005
1016
1028
1040
—
1.58
1.68
1.77
1.88
1.98
2.10
2.22
2.34
2.47
2.60
2.74
2.88
3.03
3.17
3.32
—
924
935
946
957
967
976
986
998
1010
1022
1034
1046
1058
—
—
—
—
—
—
—
—
1.73
1.84
1.95
2.06
2.17
2.29
2.41
2.54
2.67
2.81
2.96
3.11
3.26
—
—
—
—
—
—
—
—
970
977
987
998
1009
1020
1030
1039
1049
1060
1072
1084
—
—
—
—
—
—
—
—
—
1.89
2.00
2.11
2.23
2.35
2.48
2.61
2.74
2.87
3.02
3.17
3.32
—
—
—
—
—
—
—
—
—
1019
1026
1029
1037
1047
1058
1069
1081
1091
1100
1110
—
—
—
—
—
—
—
—
—
2.00
2.17
2.28
2.40
2.53
2.66
2.80
2.94
3.08
3.23
3.38
—
—
—
—
—
—
—
—
—
1066
1070
1075
1082
1087
1095
1106
1117
1128
—
—
—
—
—
—
—
—
—
—
—
—
2.30
2.44
2.51
2.58
2.70
2.84
2.98
3.13
3.29
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
5. Standard drive range is 571 to 779 rpm. All other speeds
require a field-supplied drive.
Bhp
—
Brake Horsepower at Motor Shaft
Rpm — Revolutions Per Minute of Blower Wheel
6. Maximum continuous bhp is 2.4. Extensive motor and electrical
testing on these units ensures that the full range of the motor
can be utilized with confidence. Using the fan motors up to the
ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 5.)
2.
indicates field-supplied motor and drive are required.
7. Interpolation is permissible. Do not extrapolate.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 20 — Fan Performance, 48TF014 — Vertical Discharge Units (English)
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.8
0.4
0.6
1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
729
745
761
777
793
810
826
842
859
876
892
909
926
942
959
976
993
1010
1027
1043
1060
1077
1094
1111
1128
1145
1.36
1.46
1.56
1.67
1.79
1.91
2.04
2.17
2.31
2.46
2.60
2.77
2.93
3.11
3.29
3.47
3.67
3.87
4.07
4.29
4.51
4.74
4.98
5.22
5.48
5.74
790
805
820
836
851
867
883
898
914
930
945
961
977
1.58
1.69
1.80
1.92
2.05
2.18
2.32
2.46
2.60
2.76
2.91
3.07
3.24
3.41
3.60
3.78
3.98
4.18
4.39
4.61
4.83
5.07
5.41
5.55
—
847
861
875
889
904
918
933
948
962
1.79
1.89
2.02
2.14
2.27
2.41
2.55
2.70
2.85
3.01
3.18
3.36
3.54
3.73
3.92
4.12
4.33
4.54
4.76
4.99
5.22
5.46
5.70
—
902
915
928
941
955
968
982
996
1010
1024
2039
1053
1068
1080
1097
1112
1127
1142
1157
1173
1189
—
2.06
2.17
2.29
2.40
2.42
2.54
2.79
2.93
3.09
3.26
3.43
3.61
3.80
3.90
4.19
4.40
4.61
4.84
5.07
5.31
5.55
—
955
967
979
2.29
2.41
2.55
2.68
2.82
2.96
3.11
3.25
3.40
3.55
3.71
3.88
4.06
4.25
4.46
4.67
4.90
5.13
5.36
5.61
—
991
1004
1017
1030
1043
1056
1070
1083
1097
1111
1126
1139
1153
1168
1182
1197
1211
—
977
992
1008
1024
1039
1055
1071
1086
1102
1118
1133
1149
1165
1181
—
993
1009
1025
1041
1057
1073
1090
1106
1122
1139
1155
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.8
1.4
2.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
1008
1019
1029
1040
1052
1064
1076
1088
1101
1114
1126
1140
1153
1166
1180
1194
1208
1221
1235
—
2.55
2.67
2.80
2.94
3.08
3.23
3.40
3.56
3.73
3.90
4.07
4.25
4.41
4.59
4.78
4.98
5.19
5.41
5.64
—
1060
1070
1079
1089
1100
1110
1121
1133
1144
1157
1169
1181
1194
1207
1220
1233
1246
—
—
—
—
—
—
—
—
—
2.80
2.94
3.07
3.22
3.36
3.51
3.67
3.84
4.00
4.19
4.38
4.58
4.77
4.97
5.18
5.38
5.58
—
—
—
—
—
—
—
—
—
1108
1118
1128
1137
1147
1157
1167
1178
1188
1199
1210
1222
1234
1247
1259
1272
—
—
—
—
—
—
—
—
—
3.05
3.19
3.34
3.49
3.65
3.81
3.97
4.14
4.31
4.49
4.68
4.87
5.09
5.30
5.52
5.74
—
—
—
—
—
—
—
—
—
1152
1163
1173
1183
1193
1202
1212
1222
1232
1242
1252
1263
1274
1286
—
—
—
—
—
—
—
—
—
3.27
3.44
3.60
3.76
3.93
4.09
4.27
4.44
4.62
4.81
5.00
5.20
5.40
5.62
—
—
—
—
—
—
—
—
—
1190
1203
1214
1225
1236
1245
1255
1265
1274
1284
1294
—
—
—
—
—
—
—
—
—
3.46
3.65
3.83
4.00
4.19
4.38
4.56
4.74
4.93
5.13
5.33
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
5. Standard drive range is 717 to 900 rpm. All other rpms require
a field-supplied drive.
Bhp
—
Brake Horsepower at Motor Shaft
Rpm — Revolutions Per Minute of Blower Wheel
6. Maximum continuous bhp is 3.7. Extensive motor and electrical
testing on these units ensures that the full range of the motor
can be utilized with confidence. Using the fan motors up to the
ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 5.)
2.
indicates field-supplied motor and drive are required.
7. Interpolation is permissible. Do not extrapolate.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 21 — Fan Performance, 48TF008 — Horizontal Discharge Units (English)
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.8
0.4
0.6
0.9
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
2200
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
499
507
513
528
542
550
557
573
588
604
620
636
652
668
684
701
717
733
742
0.50
0.53
0.55
0.60
0.66
0.69
0.72
0.79
0.86
0.94
1.02
1.11
1.21
1.31
1.41
1.53
1.65
1.77
1.84
580
586
592
606
619
627
634
648
662
676
690
704
718
732
747
762
777
792
800
0.70
0.73
0.76
0.83
0.90
0.94
0.97
1.05
1.13
1.21
1.30
1.39
1.49
1.59
1.70
1.82
1.94
2.07
2.14
652
658
663
674
686
692
698
711
723
737
750
764
778
793
807
821
835
849
856
0.94
0.97
1.00
1.06
1.13
1.17
1.21
1.29
1.38
1.48
1.58
1.69
1.80
1.92
2.04
2.16
2.29
2.42
2.49
717
722
727
738
748
754
759
770
782
794
806
818
831
844
857
871
885
899
907
1.17
1.22
1.26
1.34
1.41
1.45
1.49
1.58
1.66
1.76
1.86
1.97
2.09
2.21
2.35
2.48
2.63
2.78
2.86
748
752
756
766
777
783
787
798
809
821
832
844
856
869
882
895
908
922
929
1.30
1.34
1.38
1.46
1.55
1.60
1.64
1.73
1.82
1.92
2.02
2.13
2.25
2.37
2.51
2.64
2.79
2.95
3.03
EXTERNAL STATIC PRESSURE (in. wg)
1.2 1.4
AIRFLOW
(Cfm)
1.0
1.6
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
2200
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
779
783
786
795
806
812
816
827
837
848
849
870
882
894
907
919
932
945
952
1.43
1.46
1.49
1.58
1.68
1.74
1.79
1.88
1.98
2.08
2.18
2.29
2.40
2.53
2.66
2.80
2.95
3.11
3.20
839
843
846
853
859
864
868
878
889
900
910
920
931
942
954
966
978
990
997
1.78
1.81
1.84
1.88
1.94
1.99
2.04
2.16
2.29
2.41
2.52
2.64
2.76
2.89
3.02
3.15
3.30
3.45
3.54
905
908
910
912
919
920
921
928
937
947
958
968
979
2.21
2.25
2.25
2.31
2.37
2.39
2.41
2.45
2.57
2.70
2.85
2.99
3.13
3.26
3.40
3.55
3.69
3.84
3.93
951
955
959
967
971
974
976
983
986
2.57
2.59
2.61
2.68
2.73
2.76
2.78
2.88
2.91
3.01
3.15
3.30
3.47
3.63
3.79
3.94
4.10
4.28
5.27
993
1002
1012
1023
1034
1044
1054
1065
1076
1082
989
1000
1011
1022
1034
1040
LEGEND
5. Standard drive range is 492 to 700 rpm. All other rpms require
a field-supplied drive.
Bhp
—
Brake Horsepower at Motor Shaft
Rpm — Revolutions Per Minute of Blower Wheel
6. Maximum continuous bhp is 2.4. Extensive motor and electrical
testing on these units ensures that the full range of the motor
can be utilized with confidence. Using the fan motors up to the
ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 5.)
2.
indicates field-supplied motor and drive are required.
7. Interpolation is permissible. Do not extrapolate.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 22 — Fan Performance, 48TF012 — Horizontal Discharge Units (English)
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.8
0.4
0.6
1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
552
565
578
591
605
619
633
648
662
677
692
707
722
737
752
768
783
799
814
—
0.68
0.74
0.81
0.88
0.96
1.04
1.13
1.23
1.33
1.44
1.55
1.67
1.80
1.94
2.08
2.24
2.40
2.56
2.74
—
632
644
656
668
680
691
703
714
726
738
750
762
775
787
800
814
827
841
855
868
883
0.87
0.93
1.00
1.08
1.16
1.23
1.31
1.39
1.51
1.61
1.73
1.84
1.97
2.09
2.21
2.35
2.50
2.64
2.80
2.90
3.10
701
711
723
734
745
755
766
777
789
801
813
825
837
848
860
871
883
894
906
918
931
1.05
1.12
1.20
1.28
1.36
1.44
1.52
1.61
1.72
1.82
1.94
2.05
2.16
2.27
2.39
2.51
2.64
2.77
2.91
3.05
3.21
761
772
782
793
803
813
824
835
846
857
868
878
889
900
912
924
937
949
961
972
—
1.22
1.31
1.39
1.47
1.56
1.65
1.74
1.85
1.95
2.06
2.17
2.28
2.40
252
2.66
2.80
2.95
3.10
3.26
3.40
—
816
825
835
845
856
867
877
887
897
908
918
929
941
952
962
973
983
994
—
1.36
1.45
1.55
1.65
1.75
1.86
1.97
2.07
2.18
2.29
2.40
2.53
2.66
2.80
2.93
3.07
3.21
3.36
—
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.8
1.4
2.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
871
879
887
895
904
914
924
935
946
956
967
977
987
999
1008
1019
—
1.54
1.63
1.71
1.80
1.91
2.03
2.15
2.28
2.40
2.53
2.66
2.78
2.91
3.04
3.19
3.34
—
918
928
937
946
953
961
970
980
989
1000
1010
1021
1032
1042
—
—
—
—
—
—
—
1.67
1.78
1.90
2.00
2.10
2.20
2.32
2.45
2.58
2.73
2.87
3.02
3.17
3.32
—
—
—
—
—
—
—
967
973
981
991
1000
1009
1017
1024
1033
1042
1052
1062
1072
—
—
—
—
—
—
—
—
1.89
1.94
2.04
2.16
2.29
2.41
2.53
2.64
2.76
2.91
3.06
3.22
3.38
—
—
—
—
—
—
—
—
1010
1018
1026
1032
1041
1051
1061
1069
1077
1085
1093
1102
—
—
—
—
—
—
—
—
—
2.09
2.17
2.26
2.32
2.44
2.57
2.72
2.87
2.99
3.12
3.24
3.41
—
—
—
—
—
—
—
—
—
1063
1070
1075
1080
1083
1090
1099
1109
1118
1127
—
—
—
—
—
—
—
—
—
2.46
2.51
2.57
2.64
2.65
2.74
2.88
3.03
3.20
3.36
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
5. Standard drive range is 571 to 779 rpm. All other rpms require
a field-supplied drive.
Bhp
—
Brake Horsepower at Motor Shaft
Rpm — Revolutions Per Minute of Blower Wheel
6. Maximum continuous bhp is 2.4. Extensive motor and electrical
testing on these units ensures that the full range of the motor
can be utilized with confidence. Using the fan motors up to the
ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 5.)
2.
indicates field-supplied motor and drive are required.
7. Interpolation is permissible. Do not extrapolate.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 23 — Fan Performance, 48TF014 — Horizontal Discharge Units (English)
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.8
0.4
0.6
1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
677
691
705
720
734
749
764
779
793
808
822
837
852
867
882
896
911
926
940
955
970
985
1000
1015
1030
1046
1.20
1.28
1.37
1.47
1.56
1.66
1.77
1.88
1.99
2.11
2.24
2.37
2.51
2.65
2.79
2.95
3.11
3.27
3.44
3.62
3.80
3.99
4.18
4.39
4.59
4.81
748
761
773
786
800
813
826
840
854
868
882
896
910
924
938
952
967
1.43
1.52
1.62
1.71
1.82
1.92
2.04
2.16
2.28
2.42
2.56
2.71
2.86
3.01
3.17
3.33
3.50
3.68
3.86
4.04
4.23
4.42
4.62
4.83
5.04
5.26
810
822
834
847
860
873
886
899
912
925
937
950
963
977
990
1003
1017
1030
1044
1058
1072
1086
1100
1114
1128
1142
1.65
1.75
1.86
1.97
2.09
2.21
2.33
2.46
2.59
2.73
2.86
3.00
3.15
3.30
3.46
3.63
3.80
3.98
4.17
4.38
4.59
4.80
5.02
5.25
5.48
5.71
869
880
891
902
914
926
938
951
963
1.89
1.98
2.08
2.19
2.31
2.44
2.57
2.71
2.86
3.00
3.16
3.32
3.48
3.65
3.82
4.00
4.18
4.35
4.54
4.73
4.93
5.14
5.36
5.58
—
928
937
947
956
967
978
989
1000
1012
1024
1036
1048
1060
1073
1085
1098
1111
1124
1137
1150
1163
1176
—
2.17
2.28
2.39
2.50
2.60
2.71
2.83
2.96
3.09
3.25
3.42
3.59
3.76
3.94
4.12
4.30
4.50
4.70
4.91
5.12
5.34
5.56
—
975
988
1001
1014
1027
1040
1053
1066
1079
1092
1105
1118
1131
1144
1158
—
981
995
1010
1024
1039
1053
1068
1083
1097
—
—
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.8
1.4
2.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
984
993
2.43
2.55
2.66
2.79
2.91
3.04
3.18
3.31
3.43
3.56
3.70
3.86
4.02
4.20
4.40
4.60
4.80
5.01
5.22
5.44
5.67
—
1036
1046
1055
1064
1072
1081
1090
1100
1109
1119
1129
1139
1150
1161
1172
1183
1194
1206
1218
1230
—
2.68
2.81
2.94
3.07
3.20
3.34
3.48
3.63
3.78
3.93
4.09
4.24
4.38
4.54
4.71
4.91
5.08
5.29
5.52
5.75
—
1080
1092
1102
1112
1121
1130
1139
1148
1156
1166
1175
1185
1194
1204
1214
1225
1236
1247
—
2.90
3.05
3.20
3.34
3.49
3.64
3.79
3.94
4.09
4.26
4.43
4.60
4.77
4.95
5.13
5.29
5.47
5.65
—
1114
1129
1143
1155
1165
1175
1185
1194
1203
1212
1221
1230
1239
1248
1257
1267
—
—
—
—
—
—
—
—
—
3.07
3.25
3.42
3.59
3.76
3.92
4.08
4.25
4.42
4.58
4.76
4.93
5.12
5.31
5.61
5.70
—
—
—
—
—
—
—
—
—
1135
1156
1174
1190
1203
1215
1226
1236
1246
1255
1264
1273
1282
1291
—
—
—
—
—
—
—
—
—
3.17
3.39
3.59
3.80
3.99
4.18
4.36
4.54
4.72
4.91
5.09
5.28
5.47
5.66
—
—
—
—
—
—
—
—
—
1002
1011
1021
1030
1040
1050
1061
1071
1082
1093
1105
1117
1129
1141
1153
1166
1178
1190
1203
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
5. Standard drive range is 717 to 900 rpm. All other rpms require
a field-supplied drive.
Bhp
—
Brake Horsepower at Motor Shaft
Rpm — Revolutions Per Minute of Blower Wheel
6. Maximum continuous bhp is 3.7. Extensive motor and electrical
testing on these units ensures that the full range of the motor
can be utilized with confidence. Using the fan motors up to the
ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 5.)
2.
indicates field-supplied motor and drive are required.
7. Interpolation is permissible. Do not extrapolate.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
TO SHUT OFF UNIT — Set system selector switch at OFF
position. Resetting thermostat at a position above room tem-
perature shuts unit off temporarily until space temperature ex-
ceeds thermostat setting.
START-UP
Unit Preparation — Make sure that unit has been in-
stalled in accordance with these installation instructions and
applicable codes. Make sure that Start-Up Checklist, located on
back page of this booklet, has been completed and filled out.
Main Burners — Main burners are factory set and should
require no adjustment.
Return-Air Filters — Make sure correct filters are in-
stalled in filter tracks (see Tables 1A and 1B). Do not operate
unit without return-air filters.
TO CHECK ignition of main burners and heating controls,
move thermostat set point above room temperature and verify
that the burners light and evaporator fan is energized. After en-
suring that the unit continues to heat the building, lower the
thermostat setting below the room temperature and verify that
the burners and evaporator fan turn off (fan will turn off only if
fan selector switch is in the AUTO. position). Refer to Table 24
for the correct orifice to use at high altitudes.
Outdoor-Air Inlet Screens — Outdoor-air inlet screens
must be in place before operating unit.
Compressor Mounting — Compressors are internally
spring mounted. Do not loosen or remove compressor hold-
down bolts. On 48TF014 units, remove the tiedown bands that
hold the compressors together.
NOTE: Upon a call for heat, the main burners will remain on
for a minimum of 60 seconds.
Internal Wiring — Check all electrical connections in
unit control boxes. Tighten as required. Ensure wiring does not
come into direct contact with refrigerant tubing.
ADJUST GAS INPUT — The gas input to the unit is deter-
mined by measuring the gas flow at the meter or by measuring
the manifold pressure. Manifold pressure should be 872 Pa
(3.5 in. wg).
NOTE: Unit uses a 2 stage gas valve. There is no need to
adjust the “Low Fire” manifold pressure.
Measure Gas Flow (Natural Gas Units) — Minor adjustment
to the gas flow can be made by changing the manifold pressure.
The manifold pressure must be 872 Pa (3.5 in wg). Normal
manifold pressure is 872 Pa (3.5 in. wg) in high fire, W1 and
W2 inputs to gas valve.
Proceed as follows:
1. Turn off gas supply to unit.
2. Remove pipe plug on manifold then connect manometer
at this point. Turn on gas to unit. Ensure gas valve is in
high fire operation.
Observe manifold pressure and proceed as follows to adjust
gas input:
Refrigerant Service Ports — Each refrigerant sys-
tem has 4 Schrader-type service gage ports: one on the suction
line, one on the liquid line, and two on the compressor dis-
charge line. Be sure that caps on the ports are tight. One
Schrader-type valve is located under both the high-pressure
switch and the low-pressure switch when ordered as an option.
High Flow Valves — Located on the compressor hot gas
and suction tubes are High Flow Valves. Large black plastic
caps distinguish these valves with O-rings located inside the
caps. These valves cannot be accessed for service in the field.
Ensure the plastic caps are in place and tight or the possibility
of refrigerant leakage could occur.
Compressor Rotation — On 3-phase units with scroll
compressors, it is important to be certain compressor is rotating
in the proper direction. To determine whether or not compres-
sor is rotating in the proper direction:
1. Connect service gages to suction and discharge pressure
fittings.
1. Remove cover screw over regulator adjustment screw on
gas valve. Ensure gas valve is operating in high fire
mode.
2. Turn regulator adjustment screw clockwise to increase
gas input, or turn regulator adjustment screw counter-
clockwise to decrease input. High fire manifold pressure
must be 872 Pa (3.5 in. wg).
2. Energize the compressor.
3. The suction pressure should drop and the discharge pres-
sure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres-
sure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating in
the wrong direction.
2. Turn off power to the unit and install lockout tag.
3. Reverse any two of the unit power leads.
Unsafe operation of the unit may result if manifold pres-
sure is outside 847 to 897 Pa (3.4 to 3.6 in. wg) range. Per-
sonal injury or unit damage may result.
4. Reapply power to unit. Reenergize compressor.
3. Replace cover screw cap on gas valve.
The suction and discharge pressure levels should now move
to their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direc-
tion, the unit will make an elevated level of noise and will not
provide cooling.
4. Turn off gas supply to unit. Remove manometer from
pressure tap and replace pipe plug on gas valve. Turn on
gas to unit and check for leaks.
Heating
1. Purge gas supply line of air by opening union ahead of
gas valve. When gas odor is detected, tighten union and
wait 5 minutes before proceeding.
Cooling — To start unit, turn on main power supply. Set
system selector switch at COOL position and fan switch at
AUTO. position. Adjust thermostat to a setting below room
temperature. Compressor, indoor and outdoor fans start on clo-
sure of contactors.
Check unit charge. Refer to Refrigerant Charge section,
page 37. Unit must operate a minimum of 15 minutes before
adjusting charge.
2. Turn on electrical supply and open manual gas valve.
3. Set system switch selector at HEAT position and fan
switch at AUTO. or ON position. Set heating temperature
lever above room temperature.
4. The induced-draft motor will start, purging heat
exchangers.
Reset thermostat at a position above room temperature.
Compressor and outdoor fans will shut off. Evaporator fan will
shut off after 30-second delay.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
5. After a call for heating, the main burners should light
within 5 seconds. If the burners do not light, then there is
a 22-second delay before another 5-second ignition try.
If the burners still do not light, the time delay is repeated.
If the burners do not light within 15 minutes, there is a
lockout. To reset the control, break the 24 v power to W1.
6. The evaporator-fan motor will turn on 45 seconds after
the burners are ignited.
7. The evaporator-fan motor will turn off 45 seconds after
the thermostat temperature is satisfied.
Safety Relief — A soft-solder joint at the suction line
Schrader port provides pressure relief under abnormal tempera-
ture and pressure conditions.
Ventilation (Continuous Fan) — Set fan and system
selector switches at ON and OFF positions, respectively.
Evaporator fan operates continuously to provide constant air
circulation. When the evaporator-fan selector switch is turned
to the OFF position, there is a 30-second delay before the fan
turns off.
Operating Sequence
8. Adjust airflow to obtain a temperature rise within the
range specified on the unit nameplate and in Table 1A
or 1B.
COOLING, UNITS WITHOUT ECONOMIZER — When
thermostat calls for cooling, terminals G and Y1 are energized.
The indoor (evaporator) fan contactor (IFC) and compressor
contactor no. 1 (C1) are energized, and evaporator-fan motors,
compressor no. 1, and both condenser fans start. The condenser-
fan motor runs continuously while unit is cooling. If the thermo-
stat calls for a second stage of cooling by energizing Y2, com-
pressor contactor no. 2 (C2) is energized and compressor no. 2
starts.
When the thermostat is satisfied, C1 and C2 are deener-
gized and the compressors and outdoor (condenser) fan motors
(OFM) shut off. After a 30-second delay, the indoor (evapora-
tor) fan motor (IFM) shuts off. If the thermostat fan selector
switch is in the ON position, the evaporator motor will run
continuously.
HEATING, UNITS WITHOUT ECONOMIZER — When
the thermostat calls for heating, terminal W1 is energized. In
order to prevent thermostat short-cycling, the unit is locked
into the Heating mode for at least 1 minute when W1 is ener-
gized. The induced-draft motor (IDM) is then energized and
the burner ignition sequence begins. The indoor (evaporator)
fan motor (IFM) is energized 45 seconds after a flame is ignit-
ed. On units equipped for two stages of heat, when additional
heat is needed, W2 is energized and the high-fire solenoid on
the main gas valve (MGV) is energized. When the thermostat
is satisfied and W1 and W2 are deenergized, the IFM stops af-
ter a 45-second time-off delay.
COOLING, UNITS WITH DURABLADE ECONO-
MIZER — When the outdoor-air temperature is above the
OAT (outdoor-air thermostat) setting and the room thermostat
calls for cooling, compressor contactor no. 1 is energized to
start compressor no. 1 and the outdoor (condenser) fan motor
(OFM). The indoor (evaporator) fan motor (IFM) is energized
and the economizer damper moves to the minimum position.
Upon a further call for cooling, compressor contactor no. 2 will
be energized, starting compressor no. 2. After the thermostat is
satisfied, the damper moves to the fully closed position when
using an auto fan or to the minimum position when using a
continuous fan.
Table 24 — Altitude Compensation*
31.4, 50.4, AND 59.8 kW
65.6 kW
(107,000, 172,000 AND
(224,000 BTUH)
204,000 BTUH
NOMINAL INPUT
ELEVATION
m or km
(ft)
NOMINAL INPUT
Natural
Liquid
Propane
Orifice
Size†
Natural Liquid
Gas
Orifice
Size†
Gas
Propane
Orifice Orifice
Size† Size†
0-610 m (0-2,000) 3.0 (31)
610 m (2,000) 2.9 (32)
914 m (3,000) 2.9 (32)
1.22 km (4,000) 2.9 (32)
1.52 km (5,000) 2.8 (33)
1.83 km (6,000) 2.8 (34)
2.13 km (7,000) 2.8 (35)
2.44 km (8,000) 2.7 (36)
2.74 km (9,000) 2.6 (37)
3.05 km (10,000) 2.5 (38)
3.35 km (11,000) 2.5 (39)
3.66 km (12,000) 2.4 (40)
3.96 km (13,000) 2.4 (41)
4.27 km (14,000) 2.3 (42)
2.4 (41)
2.3 (42)
2.3 (42)
2.3 (42)
2.2 (43)
2.2 (43)
2.1 (44)
2.1 (44)
2.0 (45)
2.0 (46)
1.9 (47)
1.9 (47)
1.9 (48)
1.9 (48)
3.2 (30) 2.5 (38)
3.2 (30) 2.5 (39)
3.0 (31) 2.4 (40)
2.9 (32) 2.4 (41)
2.8 (33) 2.3 (42)
2.8 (34) 2.2 (43)
2.8 (35) 2.2 (43)
2.7 (36) 2.1 (44)
2.6 (37) 2.1 (44)
2.5 (38) 2.0 (45)
2.5 (39) 2.0 (45)
2.4 (40) 2.0 (46)
2.4 (41) 1.9 (47)
2.3 (42) 1.9 (47)
*As the height above sea level increases, there is less oxygen.
Therefore, heat input rate should be reduced at higher altitudes.
†Orifice available through your local distributor.
Integrated Gas Controller (IGC) Operation
NOTE: The default value for the evaporator-fan motor ON and
OFF delay is 45 seconds. The Integrated Gas Controller (IGC)
modifies this value when abnormal limit switch cycles occur.
Based upon unit operating conditions, the ON delay can be
reduced to 0 seconds and the OFF delay can be extended to
180 seconds.
When one flash of the LED (light-emitting diode) is ob-
served, the evaporator-fan ON/OFF delay has been modified.
If the limit switch trips at the start of the heating cycle during
the evaporator ON delay, the time period of the ON delay for
the next cycle will be 5 seconds less than the time at which the
switch tripped. (Example: If the limit switch trips at 30 sec-
onds, the evaporator-fan ON delay for the next cycle will occur
at 25 seconds.) To prevent short-cycling, a 5-second reduction
will only occur if a minimum of 10 minutes has elapsed since
the last call for heating.
The evaporator-fan OFF delay can also be modified. Once
the call for heating has ended, there is a 10-minute period dur-
ing which the modification can occur. If the limit switch trips
during this period, the evaporator-fan OFF delay will increase
by 15 seconds on the next cycle. A maximum of 9 trips can oc-
cur, extending the evaporator-fan OFF delay to 180 seconds.
To restore the original default value, reset the power to the unit.
When the outdoor-air temperature is below the OAT setting
and the thermostat calls for cooling, the economizer dampers
move to the minimum position. If the supply-air temperature is
above 14 C (57 F), the damper continues to open until it reach-
es the fully open position or until the supply-air temperature
drops below 11 C (52 F).
When the supply-air temperature falls to between 14 C
(57 F) and 11 C (52 F), the damper will remain at an intermedi-
ate open position. If the supply-air temperature falls below
11 C (52 F), the damper will modulate closed until it reaches
the minimum position or until the supply-air temperature is
above 11 C (52 F). When the thermostat is satisfied, the damp-
er will move to the fully closed position when using an auto fan
or to the minimum position when using a continuous fan.
TO SHUT OFF UNIT — Set system selector switch at OFF
position. Resetting heating selector lever below room tempera-
ture will shut unit off temporarily until space temperature falls
below thermostat setting.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
If the outdoor air alone cannot satisfy the cooling require-
ments of the conditioned space, economizer cooling is integrat-
ed with mechanical cooling, providing second-stage cooling.
Compressor no. 1 and the condenser fan will be energized and
the position of the economizer damper will be determined by
the supply-air temperature. Compressor no. 2 is locked out.
SERVICE
When servicing unit, shut off all electrical power to unit to
avoid shock hazard or injury from rotating parts.
When the second stage of cooling is satisfied, the compres-
sor and OFM will be deenergized. The damper position will be
determined by the supply-air temperature.
After a 30-second delay, the IFM shuts off. If the thermostat
fan selector switch is in the ON position, the IFM will run
continuously.
Cleaning — Inspect unit interior at the beginning of each
heating and cooling season or more frequently as operating
conditions require.
EVAPORATOR COIL — Clean coil as required. Inspect coil
at beginning of heating and cooling seasons.
1. Turn unit power off. Remove evaporator coil access panel.
COOLING UNITS WITH ECONOMI$ER — When the
OAT is above the ECON SP set point and the room thermostat
calls for Stage 1 cooling (R to G + Y1), the indoor fan motor
(IFM) is energized and the EconoMi$er damper modulates to
minimum position. The compressor contactor is energized to
start the compressor and outdoor-fan motor (OFM). After the
thermostat is satisfied, the damper modulates to the fully closed
position when the IFM is deenergized.
2. If economizer is installed, remove economizer by discon-
necting Molex plug and removing economizer mounting
screws. Refer to Accessory Economizer Installation In-
structions or Optional Economizer sections on pages 12
and 15 for more details.
3. Remove filters from unit.
4. Clean coil using a commercial coil cleaner or dishwasher
detergent in a pressurized spray canister. Wash both sides
of coil and flush with clean water. For best results, back-
flush toward return-air section to remove foreign materi-
al. Caution should be taken as to not overflow the evapo-
rator drain condensate pan.
5. Flush condensate pan after completion.
6. Reinstall economizer and filters.
7. Reconnect wiring.
When the OAT is below the ECON SP setting and the room
thermostat calls for Stage 1 cooling (R to G + Y1), the
EconoMi$er modulates to the minimum position when the
IFM is energized. The EconoMi$er provides Stage 1 of cooling
by modulating the return and outdoor air dampers to maintain a
13 C (55 F) supply air set point. If the supply-air temperature
(SAT) is greater than 14 C (57 F), the EconoMi$er modulates
open, allowing a greater amount of outdoor air to enter the unit.
If the SAT drops below 12 C (53 F), the outdoor air damper
modulates closed to reduce the amount of outdoor air. When
the SAT is between 12 C (53 F) and 14 C (57 F), the
EconoMi$er maintains its position.
If outdoor air alone cannot satisfy the cooling requirements
of the conditioned space, and the OAT is above the MECH
CLG LOCKOUT set point, the EconoMi$er integrates free
cooling with mechanical cooling. This is accomplished by the
strategies below.
8. Replace access panels.
CONDENSER COIL — Inspect coil monthly. Clean con-
denser coil annually, and as required by location and outdoor-
air conditions.
One-Row Coils — Wash coil with commercial cleaner. Clean
outer surfaces with a stiff brush in the normal manner. It is not
necessary to remove top panel.
NOTE: Compressors have a two-minute Minimum On, Mini-
mum Off, and interstage delay timer.
2-Row Coils — Clean coil as follows:
1. Turn off unit power.
1. If Y1 is energized, and the room thermostat calls for Y2
(2-stage thermostat), the compressor and OFM are ener-
gized. The position of the EconoMi$er damper is main-
tained at its current value.
2. If Y1 is energized for more than 20 minutes, and Y2 is
not energized (whether or not a 2-stage thermostat is
used), the compressor and OFM are energized. The posi-
tion of the EconoMi$er damper is maintained at its cur-
rent value.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 45. To hold
top panel open, place coil corner post between top panel
and center post. See Fig. 46.
4. Remove screws securing coil to center post.
5. Remove fastener holding coil sections together at return
end of condenser coil. Carefully separate the outer coil
section 3 to 4 in. from the inner coil section. See Fig. 47.
6. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and de-
bris. Clean the outer surfaces with a stiff brush in the nor-
mal manner.
7. Secure inner and outer coil rows together with a field-
supplied fastener.
8. Reposition the outer coil section and remove the coil cor-
ner post from between the top panel and center post.
9. Reinstall the coil corner post and replace all screws.
CONDENSATE DRAIN — Check and clean each year at
start of cooling season. In winter, keep drain dry or protect
against freeze-up.
FILTERS — Clean or replace at start of each heating and cool-
ing season, or more often if operating conditions require it. Re-
placement filters must be same dimensions as original filters.
BELTS — Adjust belt tension and pulley alignment at least
twice a year or more frequently as operating conditions require.
Refer to Step 9 — Adjust Evaporator for Fan Speed
for procedures.
3. If Y1 is energized, and compressor no. 1 is already ener-
gized (see Step 2) and the room thermostat calls for Y2,
compressor no. 1 continues to operate. If Y2 remains
energized for more than 20 minutes, compressor no. 2 is
energized.
NOTE: Compressor no. 2 cannot be energized unless there is a
signal for Y2 from the space thermostat.
4. If compressor no. 2 is energized, and the Y2 signal from
the thermostat is satisfied, compressors 1 and 2 are deen-
ergized. Re-asserting Y2 will start compressor no. 1 and
(after a 20-minute interstage delay) compressor no. 2.
5. If compressor no. 1 is energized and the thermostat is sat-
isfied, compressor no. 1, the OFM, and IFM are deener-
gized and the EconoMi$er modulates closed.
When the OAT is below the MECH CLG LOCKOUT set
point, the compressors remain off.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
Lubrication
COMPRESSORS — Each compressor is charged with the
correct amount of oil at the factory.
FAN-MOTOR BEARINGS — Fan-motor bearings are of
the permanently lubricated type. No further lubrication is re-
quired. No lubrication of condenser- or evaporator-fan motors
is required.
Condenser-Fan Adjustment (Fig. 48)
1. Shut off unit power supply and tag disconnect.
2. Remove condenser-fan assembly (grille, motor, motor
cover, and fan) and loosen fan hub setscrews.
3. Adjust fan height as shown in Fig. 48.
4. Tighten setscrews and replace condenser-fan assembly.
Fig. 45 — Cleaning Condenser Coil
48TF UNIT VOLTAGE
400 V
FAN HEIGHT “A” (in.)
89 (3.50)
Fig. 48 — Condenser-Fan Adjustment
Manual Outdoor-Air Damper — If outdoor-air damp-
er blade is required, see Manual Outdoor-Air Damper section on
page 12.
Economizer Adjustment — Refer to Optional Dura-
blade Economizer section on page 14.
Condenser Coil Grille — Condenser coil grille is
Fig. 46 — Propping Up Top Panel
shipped factory-installed. No adjustments are required.
Refrigerant Charge — Amount of refrigerant charge is
listed on unit nameplate (also refer to Tables 1A and 1B). Refer
to Carrier GTAC 2-5 Charging, Recovery, recycling, and recla-
mation training manual and the following procedures.
Unit panels must be in place when unit is operating during
charging procedure.
NO CHARGE — Use standard evacuating techniques. After
evacuating system, weigh in the specified amount of refriger-
ant (refer to Tables 1A and 1B).
LOW CHARGE COOLING — Using the Cooling Charging
Charts, Fig. 49-51 vary refrigerant until the conditions of the
appropriate chart are met. Note the charging charts are differ-
ent from the type normally used. The charts are based on
charging the units to the correct superheat for the various oper-
ating conditions. Accurate pressure gage and temperature sens-
ing device are required. Connect the pressure gage to the
service port on the suction line. Mount the temperature sensing
device on the suction line and insulate it so that outdoor ambi-
ent temperature does not affect the reading. Indoor-air cfm
must be within the normal operating range of the unit.
TO USE COOLING CHARGING CHARTS — Take the out-
door ambient temperature and read the suction pressure gage.
Refer to appropriate chart to determine what suction tempera-
ture should be. If suction temperature is high, add refrigerant.
If suction temperature is low, carefully reclaim some of the
charge. Recheck the suction pressure as charge is adjusted.
Example (Fig. 51, Circuit 1):
Fig. 47 — Separating Coil Sections
Outdoor Temperature. . . . . . . . . . . . . . . . . . . . . . . . .13 C (55 F)
Suction Pressure. . . . . . . . . . . . . . . . . . . . . . . .483 kPa (70 psig)
Suction Temperature should be. . . . . . . . . . . . . . . . .23 C (74 F)
(Suction temperature may vary ± 3 C [5 F].)
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 49 — Cooling Charging Charts, 48TF008 Units
Fig. 50 — Cooling Charging Charts, 48TF012 Units
38
Download from Www.Somanuals.com. All Manuals Search And Download.
CIRCUIT NO. 2
CIRCUIT NO. 1
Fig. 51 — Cooling Charging Chart; 48TF014 Units
Flue Gas Passageways — To inspect the flue collec-
problems when the power supply is interrupted. When a break
in power occurs, the module will be reset (resulting in a loss of
fault history) and the indoor (evaporator) fan ON/OFF times
will be reset. For additional information, refer to the Start-Up,
Heating section on page 34. The LED error code can be ob-
served through the viewport. During servicing refer to the label
on the control box cover or Table 25 for an explanation of LED
error code descriptions.
tor box and upper areas of the heat exchanger:
1. Remove the combustion blower wheel and motor assem-
bly according to directions in Combustion-Air Blower
section below.
2. Remove the flue cover to inspect the heat exchanger.
3. Clean all surfaces as required using a wire brush.
If lockout occurs, unit may be adjusted by interrupting pow-
er supply to unit for at least 5 seconds.
Combustion-Air Blower — Clean periodically to as-
sure proper airflow and heating efficiency. Inspect blower
wheel every fall and periodically during heating season. For the
first heating season, inspect blower wheel bimonthly to deter-
mine proper cleaning frequency.
Table 25 — LED Error Code Description*
To inspect blower wheel, shine a flashlight into draft hood
opening. If cleaning is required, remove motor and wheel as
follows:
1. Slide burner access panel out.
2. Remove the 6 screws that attach induced-draft motor
housing to vestibule plate (Fig. 52).
3. The blower wheel can be cleaned at this point. If addi-
tional cleaning is required, continue with Steps 4 and 5.
4. To remove blower from the motor shaft, remove
2 setscrews.
5. To remove motor, remove the 4 screws that hold blower
housing to mounting plate. Remove the motor cooling fan
by removing one setscrew. Then remove nuts that hold
motor to mounting plate.
LED INDICATION
ON
ERROR CODE DESCRIPTION
Normal Operation
Hardware Failure
Evaporator Fan On/Off Delay Modified
Limit Switch Fault
Flame Sense Fault
4 Consecutive Limit Switch Faults
Ignition Lockout Fault
Induced-Draft Motor Fault
Rollout Switch Fault
Internal Control Fault
Temporary 1 hour automatic reset fault
OFF
1 Flash†
2 Flashes
3 Flashes
4 Flashes
5 Flashes
6 Flashes
7 Flashes
8 Flashes
9 Flashes**
LEGEND
LED
—
Light-Emitting Diode
6. To reinstall, reverse the procedure outlined above.
*A 3-second pause exists between LED error code flashes. If more
than one error code exists, all applicable codes will be displayed in
numerical sequence.
†Indicates a code that is not an error. The unit will continue to oper-
ate when this code is displayed.
**Indicates internal processor fault and will reset itself in 1 hour.
Limit Switch — Remove blower access panel (Fig. 6).
Limit switch is located on the fan deck.
Burner Ignition — Unit is equipped with a direct spark
ignition 100% lockout system. Integrated Gas Unit Controller
(IGC) is located in the control box (Fig. 11). Module contains a
self-diagnostic LED (light-emitting diode). A single LED on
the IGC provides a visual display of operational or sequential
IMPORTANT: Refer to Troubleshooting Tables 26-30 for addi-
tional information.
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Main Burners — At the beginning of each heating sea-
son, inspect for deterioration, blockage due to corrosion or oth-
er causes. Observe the main burner flames and replace burners
if necessary.
INDUCED-
DRAFT
ROLLOUT
SWITCH
MOTOR
MOUNTING
PLATE
When working on gas train, do not hit or plug orifice
spuds.
BURNER
SECTION
FLUE
EXHAUST
REMOVAL AND REPLACEMENT OF GAS TRAIN
(Fig. 52 and 53)
VESTIBULE
PLATE
1. Shut off manual gas valve.
INDUCED-
DRAFT
2. Shut off power to unit and tag disconnect.
3. Slide out burner section side panel (not shown).
4. Disconnect gas piping at unit gas valve.
5. Remove wires connected to gas valve. Mark each wire.
BLOWER
HOUSING
MOTOR
MANIFOLD
PRESSURE
TAP
GAS
VALVE
6. Remove wires from ignitor and sensor wires at the Inte-
grated Gas Unit Controller (IGC).
Fig. 52 — Burner Section Details
7. Remove the 2 screws that attach the burner rack to the
vestibule plate.
8. Slide the burner tray out of the unit (Fig. 53).
9. To reinstall, reverse the procedure outlined above.
CLEANING AND ADJUSTMENT
1. Remove burner rack from unit as described in Removal
and Replacement of Gas Train section on this page.
2. Inspect burners; if dirty, remove burners from rack.
3. Using a soft brush, clean burners and cross-over port as
required.
4. Adjust spark gap. See Fig. 54.
5. Reinstall burners on rack.
6. Reinstall burner rack as described in Removal and Re-
placement of Gas Train section.
Fig. 53 — Burner Tray Details
Replacement Parts — A complete list of replacement
parts may be obtained from any Carrier distributor upon
request.
40
Download from Www.Somanuals.com. All Manuals Search And Download.
48TFD008
31.4/21.1 kW INPUT (107,000/72,000 BTUH)
48TFE008, 48TFD012
50.4/31.9 kW INPUT/ (172,000/109,000 BTUH)
48TFD014, 48TFE012, 48TFF008
59.8/39.8 kW INPUT
(204,000/136,000 BTUH)
48TFE014, 48TFF012
65.6/43.9 kW INPUT
(224,000/150,000 BTUH)
NOTE: Dimensions in ( ) are millimeters.
Fig. 54 — Spark Gap Adjustment
41
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
Table 26 — LED Error Code Service Analysis
CAUSE
PROBLEM
REMEDY
Hardware failure.
(LED OFF)
Loss of power to control module (IGC).
Check 5- amp fuse on IGC, power to unit, 24-v circuit breaker,
and transformer. Units without a 24-v circuit breaker have an
internal overload in the 24-v transformer. If the overload trips,
allow 10 minutes for automatic reset.
Limit switch fault.
(LED 2 flashes)
High temperature limit switch is open.
Check the operation of the indoor (evaporator) fan motor.
Ensure that the supply-air temperature rise is in accordance with
the range on the unit nameplate.
Flame sense fault.
(LED 3 flashes)
The IGC sensed flame that should not be Reset unit. If problem persists, replace control board.
present.
4 consecutive limit switch trips. Inadequate airflow to unit.
(LED 4 flashes)
Check operation of indoor (evaporator) fan motor and that supply-air
temperature rise agrees with range on unit nameplate information.
Ignition lockout.
(LED 5 flashes)
Unit unsuccessfully attempted ignition for Check ignitor and flame sensor electrode spacing, gaps, etc.
15 minutes.
Ensure that flame sense and ignition wires are properly termi-
nated. Verify that unit is obtaining proper amount of gas.
Induced-draft motor fault.
(LED 6 flashes)
IGC does not sense that induced-draft
motor is operating.
Check for proper voltage. If motor is operating, check the
speed sensor plug/IGC Terminal J2 connection. Proper
connection: PIN 1— White, PIN 2 — Red, PIN 3 — Black.
Rollout switch fault.
(LED 7 flashes)
Rollout switch has opened.
Rollout switch will automatically reset, but IGC will continue to
lock out unit. Check gas valve operation. Ensure that induced-
draft blower wheel is properly secured to motor shaft. Reset unit
at unit disconnect.
Internal control fault.
(LED 8 flashes)
Microprocessor has sensed an error in
the software or hardware.
If error code is not cleared by resetting unit power, replace the
IGC.
Temporary 1 hour automatic reset Stray radio frequency signals in ??
fault. (LED 9 flashes)
Processor will be reset after 1 hour.
LEGEND
IMPORTANT: Refer to Table 28 — Heating Service Trouble-
shooting for additional troubleshooting information.
IGC — Integrated Gas Unit Controller
LED — Light-Emitting Diode
If the IGC must be replaced, be sure to ground yourself to dissi-
pate any electrical charge that may be present before handling
new control board. The IGC is sensitive to static electricity and
may be damaged if the necessary precautions are not taken.
42
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 27 — Cooling Service Troubleshooting
PROBLEM
CAUSE
REMEDY
Call power company.
Replace fuse or reset circuit breaker.
Replace component.
Compressor and
condenser fan
will not start.
Power failure.
Fuse blown or circuit breaker tripped.
Defective thermostat, contactor, transformer,
or control relay.
Insufficient line voltage.
Incorrect or faulty wiring.
Thermostat setting too high.
Faulty wiring or loose connections in com-
pressor circuit.
Determine cause and correct.
Check wiring diagram and rewire correctly.
Lower thermostat setting below room temperature.
Check wiring and repair or replace.
Compressor will not start
but condenser fan runs.
Compressor motor burned out, seized, or
internal overload open.
Defective run/start capacitor, overload, or
start relay.
Determine cause. Replace compressor.
Determine cause and replace.
One leg of 3-phase power dead.
Replace fuse or reset circuit breaker. Determine
cause.
Compressor cycles (other than
normally satisfying thermostat).
Refrigerant overcharge or undercharge.
Recover refrigerant, evacuate system, and
recharge to nameplate.
Defective compressor.
Insufficient line voltage.
Blocked condenser.
Defective run/start capacitor, overload, or
start relay.
Replace and determine cause.
Determine cause and correct.
Determine cause and correct.
Determine cause and replace.
Defective thermostat.
Replace thermostat.
Faulty condenser-fan motor or capacitor.
Restriction in refrigerant system.
Dirty air filter.
Replace.
Locate restriction and remove.
Replace filter.
Compressor operates continuously.
Unit undersized for load.
Thermostat set too low.
Low refrigerant charge.
Leaking valves in compressor.
Air in system.
Decrease load or increase unit size.
Reset thermostat.
Locate leak, repair, and recharge.
Replace compressor.
Recover refrigerant, evacuate system, and
recharge.
Condenser coil dirty or restricted.
Dirty air filter.
Clean coil or remove restriction.
Replace filter.
Excessive head pressure.
Dirty condenser coil.
Refrigerant overcharged.
Air in system.
Clean coil.
Remove excess refrigerant.
Recover refrigerant, evacuate system, and
recharge.
Condenser air restricted or air short-cycling.
Low refrigerant charge.
Compressor valves leaking.
Restriction in liquid tube.
High heat load.
Compressor valves leaking.
Refrigerant overcharged.
Dirty air filter.
Determine cause and correct.
Check for leaks, repair, and recharge.
Replace compressor.
Remove restriction.
Check for source and eliminate.
Replace compressor.
Head pressure too low.
Excessive suction pressure.
Suction pressure too low.
Recover excess refrigerant.
Replace filter.
Low refrigerant charge.
Metering device or low side restricted.
Insufficient evaporator airflow.
Check for leaks, repair, and recharge.
Remove source of restriction.
Increase air quantity. Check filter and replace if
necessary.
Temperature too low in conditioned area.
Field-installed filter drier restricted.
Unit in economizer mode.
Reset thermostat.
Replace.
Proper operation; no remedy necessary.
Compressor no. 2 will not run.
Compressor makes excessive
noise (48TF014 scroll only).
Compressor rotating in wrong direction.
Reverse the 3-phase power load as described in
Start-Up, Compressor Rotation section on
page 34.
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 28 — Heating Service Troubleshooting
PROBLEM
CAUSE
REMEDY
Burners will not
ignite.
Misaligned spark electrodes.
Check flame ignition and sensor electrode positioning.
Adjust as needed.
No gas at main burners.
Check gas line for air purge as necessary. After purging
gas line of air, allow gas to dissipate for at least 5 minutes
before attempting to relight unit.
Check gas valve.
Water in gas line.
Drain water and install drip leg to trap water.
Check power supply, fuses, wiring, and circuit breaker.
No power to furnace.
No 24 v power supply to control circuit.
Check transformer. Transformers with internal overcurrent
protection require a cool down period before resetting.
Miswired or loose connections.
Burned-out heat anticipator in thermostat.
Broken thermostat wires.
Dirty air filter.
Check all wiring and wirenut connections.
Replace thermostat.
Run continuity check. Replace wires, if necessary.
Clean or replace filter as necessary.
Inadequate heating.
Gas input to unit too low.
Check gas pressure at manifold. Clock gas meter for input. If too
low, increase manifold pressure, or replace with correct orifices.
Unit undersized for application.
Restricted airflow.
Replace with proper unit or add additional unit.
Clean filter, replace filter, or remove any restrictions.
Blower speed too low.
Use high speed tap, increase fan speed, or install optional
blower, as suitable for individual units.
Limit switch cycles main burners.
Too much outdoor air.
Check rotation of blower, thermostat heat anticipator settings,
and temperature rise of unit. Adjust as needed.
Adjust minimum position.
Check economizer operation.
Poor flame
characteristics.
Incomplete combustion (lack of
combustion air) results in:
Check all screws around flue outlets and burner compartment.
Tighten as necessary.
Aldehyde odors, CO, sooting flame, or floating flame. Cracked heat exchanger.
Overfired unit — reduce input, change orifices, or adjust
gas line or manifold pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.
Burners will not
turn off.
Unit is locked into Heating mode for a
one minute minimum.
Wait until mandatory one minute time period has
elapsed or power to unit.
Table 29 — EconoMi$er Troubleshooting
PROBLEM
POTENTIAL CAUSE
REMEDY
Damper Does Not
Open
Indoor (Evaporator) Fan is Off
Check to ensure that 24 vac is present at Terminal C1 (Common Power)
on the IFC (Indoor [Evaporator] Fan Contactor) or that 24 vac is present at
the IFO (Indoor [Evaporator] Fan On) terminal. Check whether 24 vac is
present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is not
present, check wiring (see unit label diagram).
Check proper thermostat connection to G on the connection board.
No Power to EconoMi$er Controller
Check to ensure that 24 vac is present across Terminals 24 VAC and
24 V COM on the EconoMi$er control. If 24 vac is not present, check wiring
(see unit label diagram). If 24 vac is present, STATUS light should be on
constantly.
No Power to G Terminal
Controller Fault
If IFM is on, check to ensure 24 vac is present on G Terminal of the
EconoMi$er controller. If 24 vac is not present, check wiring (see unit
label diagram).
If STATUS light is flashing one flash, the EconoMi$er controller is
experiencing a fault condition. Cycle power to the controller. If condition
continues, replace the EconoMi$er controller.
Thermostat Fault
If STATUS light is flashing two flashes, the EconoMi$er controller senses
the thermostat is wired incorrectly. Check wiring between the thermostat
and the connection board in the electrical panel. The fault condition is
caused by Y2 being energized before Y1.
Actuator Fault
Check the wiring between the EconoMi$er controller and the actuator.
Hold CONFIG button between 3 and 10 seconds to verify the
actuator’s operation. (This process takes 3 minutes to complete.)
EconoMi$er
Operation Limited to
Minimum Position
Minimum Position Set Incorrectly
Verify that the MIN POS (%) is set greater than zero. Adjust MIN POS (%)
to 100% to verify operation, and then set to correct setting.
Set at correct value. See Table 4.
EconoMi$er Changeover Set Point Set Too
High or Too Low
Supply Air Temperature Sensor Faulty
Outdoor Air Temperature Sensor Faulty
Supply Air Low Limit Strategy Controlling
If STATUS light is flashing 4 flashes, Supply Air Temperature Sensor is
faulty. Check wiring or replace sensor.
If STATUS light is flashing 5 flashes, Outdoor Air Temperature Sensor is
faulty. Check wiring or replace sensor.
The supply-air temperature is less than 7 C (45 F), causing the minimum
position to be decreased. Refer to the Start-Up instructions. Verify correct
setting of MIN POS (%). If correct, EconoMi$er is operating correctly.
Damper Position
Less than Minimum
Position Set Point
Damper Does Not
Return to Minimum
Position
Damper Does Not
Close on Power Loss
CO2 Ventilation Strategy Controlling
Damper Travel is Restricted
If a CO2 sensor is being used, and the damper position is greater than
minimum position, the ventilation control strategy is controlling. Refer to
the Start-Up instructions. EconoMi$er is operating correctly.
Check to ensure the damper is not blocked.
LEGEND
IFM — Indoor Fan Motor
PL
—
Plug
44
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 30 — Durablade Economizer Troubleshooting
PROBLEM
CAUSE
REMEDY
Damper does not
open.
Indoor (evaporator) fan is off.
1. Check to ensure that 24 vac is present at terminal C1 on the IFC or
that 24 vac is present at the IFO terminal. Check whether 24 vac is
present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is
not present, check wiring (see unit label diagram).
2. Check proper thermostat connection to G on the connection board.
No power to economizer motor.
1. Check that SW3 is properly making contact with the damper
blade. Check that SW1 is in the NC (normally closed) position.
2. Check diode D1. If diode is not functioning properly, replace D1.
3. Confirm that the economizer control board is grounded properly at
PL6-4 (brown wire) and at brown terminal of the economizer control
board (brown wire). The economizer motor must also be grounded
properly at the negative motor terminal (brown wire).
4. Verify SW1 and SW3 are working and wired properly (see unit label
diagram).
5. Check for 24 vac input at both PL6-1 (red wire) and PL6-3 (black
wire). If 24 vac not present, check unit wiring (see unit label dia-
gram). If 24 vac is found in both places, check for 24 vac at the
yellow terminal of the economizer control board (yellow wire). If
24 vac power is not present, replace the economizer control board.
Economizer motor failure.
OAT or EC set too high.
If the indoor (evaporator) fan and economizer motor are energized,
verify that there is a minimum of 18 vdc at the positive motor
terminal. If the motor is not operating, replace the motor.
1. Set at correct temperature (1.7 C [3 F] below indoor space
temperature).
2. Check OAT or EC by setting above outdoor temperature or humidity
level. If the OAT or EC switches do not close, replace OAT or EC.
Economizer
operation
limited to minimum
position.
Verify economizer control board is 1. Perform the following tests when OAT or EC is closed, Y1 is called
correctly wired and works properly.
for and damper is at minimum position. Confirm 24 vac on gray ter-
minal of the economizer control board (gray wire). If 24 vac is not
present, check wiring (see unit label diagram).
2. Verify that SW1 and SW3 are wired correctly and working properly
(see unit label diagram).
3. Check to ensure that 24 vac exists at PL6-2 (blue wire). If
24 vac is not present, check wiring (see unit wiring label diagram).
4. Check 24 vac output at PL6-10 (white wire). If 24 vac is not
present, replace economizer control board.
Check SAT.
1. After verifying that the OAT and EC settings and the economizer
control board wiring are correct, check to ensure that the 24 vac
terminal of the SAT has 24 vac (white wire). If OAT, EC, and control
board are functioning and wired properly and no 24 vac exists,
check wiring (see unit label diagram).
2. If supply-air temperature is greater than 14 C (57 F), 24 vac should
be found at terminal T2 on the SAT (pink wire). If 24 vac is not
present, replace SAT.
Damper does not
close.
Incorrect wiring of economizer.
1. Verify that SW2 and SW4 are wired and working properly (see unit
label diagram).
2. Check diode D2. If diode is not functioning properly, replace D2.
Verify economizer control board is 1. After verifying that the wiring is correct, modulate the damper to the
functioning properly.
minimum position. Remove the call for G (evaporator fan).
2. If the damper does not move, check for 24 vac at PL6-1 (red wire).
If 24 vac is not present, check wiring (see unit label diagram).
3. If damper still does not move, check for 24 vac at blue terminal of
economizer control board (blue wire). If 24 vac is not present,
replace the economizer circuit board.
Check SAT.
1. After verifying that the wiring is correct and the economizer control
board is functioning properly, place the OAT or EC switch in the
closed position. Place a call for Y1 and open the damper to the fully
open position. Confirm that the 24 vac terminal of the SAT has
24 vac (white wire). If 24 vac is not present, check wiring (see unit
label diagram).
2. If supply-air temperature is less than 11 C (52 F), 24 vac should be
found at terminal T1 on the SAT (violet wire). If 24 vac not found,
replace SAT.
Economizer motor failure.
If economizer control board and SAT are functioning properly, verify
that there is a minimum of 18 vdc at the positive motor terminal. If a
minimum if 18 vdc is present and the motor is still not operating,
replace the motor.
Economizer damper Verify that close-on-power-loss and 1. Check voltage potential across batteries. If lower than 14 vdc,
does not close on
power loss.
economizer control board are func-
tioning properly.
replace close-on-power-loss power supply (9-v alkaline batteries). It
is recommended that you check this emergency power supply on a
regular basis or whenever the filters are changed.
2. If the close-on-power-loss and economizer control board are func-
tioning properly, check for 14 vdc or higher at the blue terminal of
the economizer control board (blue wire) when power is discon-
nected from unit. If 14 vdc is not present, replace the control board.
LEGEND
C1 — Common Power
OAT — Outdoor-Air Thermostat
EC — Enthalpy Control
PL — Plug
IFC — Indoor (Evaporator) Fan Contactor
IFO — Indoor (Evaporator) Fan On
SAT — Supply-Air Thermostat
SW — Economizer Position Switch
45
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
AHA
BR
—
—
—
—
—
—
—
—
—
—
—
—
Adjustable Heat Anticipator
Blower Relay
C
Contactor, Compressor
Capacitor
CAP
CB
Circuit Breaker
CC
Cooling Compensator
Compressor Motor
Combustion Relay
Diode
COMP
CR
D
EC
Enthalpy Control
Economizer
ECON
EPS
Emergency Power Supply
(9-Volt Battery)
EQUIP
ER
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Equipment
Economizer Relay
Freeze-Up Protection Thermostat
Filter Status Sensor
Ground
FPT
FSS
GND
GVR
HPS
HS
Gas Valve Relay
High-Pressure Switch
Hall-Effect Sensor
Ignitor
I
IDM
IFC
Induced-Draft Motor
Indoor-Fan Contactor
Indoor Fan Motor
Integrated Gas Unit Controller
Low-Pressure Switch
Limit Switch
IFM
IGC
LPS
LS
MGV
MTR
OAT
OFM
P
Main Gas Valve
Motor
Outdoor-Air Thermostat
Outdoor-Fan Motor
Plug
PL
Plug Assembly
QT
Quadruple Terminal
Relay
R
RS
Rollout Switch
SAT
SEN
SW1
SW2
SW3
SW4
TC
Supply-Air Thermostat
Sensor
Switch Fully Open
Switch Fully Closed
Switch Min. Vent Position
Switch Max. Vent Position
Thermostat-Cooling
Thermostat-Heating
Transformer
TH
TRAN
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential
only. Not to represent wiring.
NOTES:
1. If any of the original wire furnished must be replaced, it must be
replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single phasing
conditions.
Thermostat: HH07AT170, 172, 174 and P272-2783
Subbase:
HH93AZ176, 178 and P272-1882, 1883
3. Set heat anticipator for first stage at 0.14 amp, second stage at
0.2 amp, except for 008 low heat, set both first and second stage at
0.14 amp.
4. Use copper conductors only.
Fig. 55 — Typical Unit Wiring Schematic
Copyright 2001 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 004-816 Printed in U.S.A. Form 48TF-C1SI Pg 46 1-01 Replaces: New
Book 1
4
Tab 1a 6a
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO.:________________________________
DATE:______________________________________
SERIAL NO.: ___________________________________
TECHNICIAN: __________________________________
JOB LOCATION: _______________________________
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
REMOVE ALL SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
CHECK GAS PIPING FOR LEAKS
CHECK THAT INDOOR-AIR FILTERS ARE CLEAN AND IN PLACE
VERIFY THAT UNIT INSTALLATION IS LEVEL
CHECK FAN WHEELS AND PROPELLERS FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
AND DRIVE BELTS TENSION.
III. START-UP
ELECTRICAL
SUPPLY VOLTAGE
COMPRESSOR AMPS L1
COMPRESSOR AMPS L1
L1-L2
L2-L3
L2
L2
L3-L1
L3
L3
INDOOR-FAN AMPS
L1
L2
L3
TEMPERATURES
OUTDOOR-AIR TEMPERATURE
RETURN-AIR TEMPERATURE
COOLING SUPPLY AIR
DB
DB
DB
DB
WB
GAS HEAT SUPPLY AIR
PRESSURES
GAS INLET PRESSURE
GAS MANIFOLD PRESSURE
REFRIGERANT SUCTION
kPa (IN. WG)
kPa (IN. WG) (HI FIRE)
Pa (PSIG) — CIRCUIT NO. 1
Pa (PSIG) — CIRCUIT NO. 2
REFRIGERANT DISCHARGE
Pa (PSIG) — CIRCUIT NO. 1
Pa (PSIG) — CIRCUIT NO. 2
VERIFY REFRIGERANT CHARGE USING CHARGING TABLES
VERIFY THAT 3-PHASE SCROLL COMPRESSOR ROTATING IN CORRECT DIRECTION (014 ONLY)
Copyright 2001 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book
1
4
Catalog No. 004-816
Printed in U.S.A.
Form 48TF-C1SI
Pg CL-1
1-01
Replaces: New
Tab
1a 6a
Download from Www.Somanuals.com. All Manuals Search And Download.
|