Honeywell NIAGARA WEB 700 O User Manual

WEB-700  
WEB-700-O  
CP-700  
INSTALLATION INSTRUCTIONS  
APPLICATION  
The WEB-700 and CP-700 are compact, embedded  
controller/server platforms that allow integrated control and  
management of external devices over the Internet. They  
provide suppport for two optional communications boards as  
well as optional remote I/O expansion modules.  
CONTENTS  
Returning a Defective Unit 27  
95-7776-03  
WEB-700 WEB-700-O CP-700  
PRODUCT DESCRIPTION  
The WEB/CP-700 controller is a compact embedded processor platform using on-board Flash memory for backup, in an  
expandable DIN-modular package. Designed for use in commercial environments, the WEB/CP-700 runs the NiagaraAX  
Framework to provide integrated control, supervision, and network management solutions for wide variety of networked field  
devices. NiagaraAX-3.5 or later is required.  
Packaging and Features  
The WEB/CP-700 features a DIN-mount controller base with mounting tabs for alternate panel mount. Two available comm option  
card slots are accessed under the controller’s removable cover.  
Fig. 1 and Fig. 2 show locations of important features of the WEB/CP-700.  
Removable cover  
Status and heartbeat LEDs  
NiMH backup  
battery pack  
Option card #2 area  
(card shown installed)  
Connector for NPB-PWR-UN-H  
RS-485, 15V Power  
power supply module  
Output Connector  
Option card #1 area  
(card shown installed)  
Connector ports  
Fig. 1. WEB/CP-700 Cover removed with 2 options installed on main board.  
Typical installation requires an NPB-PWR-UN-H universal power supply module (furnishing 15Vdc) for power, attaching to the  
controller’s left side. An RS-485 port is on the controller’s opposite right end connector, along with 15Vdc power for support of  
remote I/O expansion modules, either chained directly and/or wired remotely.  
NOTE: Instead of using the NPB-PWR-UN-H power supply module, you can adapt an NPB-WPM-US wall mount AC  
power adapter to power the WEB/CP-700 controller. However, you cannot directly attach I/O expansion modules  
in this configuration, nor power remote I/O modules from that NPB-WPM-US.  
3
95-7776—03  
   
WEB-700 WEB-700-O CP-700  
.
NiMH battery pack  
and shield removed  
Removed  
option cards  
Main controller board  
DIN-mount base with screw tabs  
for panel mount  
Connector ports  
Fig. 2. WEB/CP-700 main controller board and 2 option cards uninstalled.  
As a 7 series controller, the WEB/CP-700 uses a PowerPC 440EPx processor, 1GB Flash storage, and 1 GB DDR-2 RAM. TCP/  
IP access is via two standard Gigabit Ethernet ports. Serial communications ports (RS-232, RS-485) are standard.  
One or two option cards can be added for additional communications, e.g. LonWorks FTT-10, or another RS-232 port. A MiniPCI  
slot is also available for WiFi 802.11g support. The WEB/CP-700 uses the QNX Neutrino operating system, with the Oracle Java  
Hotspot VM (Virtual Machine).  
Two status LEDs are visible atop the cover. Integral contact inputs are provided to allow system monitoring of UPS power and  
battery, and an external enclosure door. A rechargeable NiMH battery pack is included inside the unit, and a separate connector  
provides recharging and monitoring of an external 12V sealed lead-acid battery ordered separately.  
The table below provides a summary of features of the WEB/CP-700 controller model.  
Table 1. WEB/CP-700 features and options  
Model  
Description  
Ports  
WEB-700-O  
CP-700  
DIN-mountable controller. PowerPC 440Epx 667MHz processor, 1GB NAND  
Flash storage, 1 GB base DDR-2 system RAM.  
Two 1GB Ethernet,  
RJ-45  
Includes integral NiMH battery pack, two open enhanced comm option card  
slots, one open MiniPCI slot (for WiFi 802.11g option card). Not furnished is  
NPB-PWR-UN-H universal power supply, or external 12V sealed lead-acid  
battery and harness.  
One RS-232 Serial,  
DB-9 male  
One RS-485 Serial,  
isolated, with 15V/  
12Vdc power, 6-  
position plug on right  
side.  
.
95-7776—03  
4
WEB-700 WEB-700-O CP-700  
Technical Specifications  
WEB/CP-700 PLATFORM  
PowerPC 440Epx @ 667MHz processor (speed approximate due to spread spectrum clock).  
1GB on-board NAND Flash storage.  
1 GB DDR-2 333Mhz RAM (maximum Java Heap size 384MB).  
Two (2) Gigabit Ethernet ports.  
Standard RS-232 port.  
6-position end connector with isolated RS-485/15Vdc power (usable as a standard non-powered isolated RS-485 port, or to  
support remote I/O modules).  
MiniPCI option slot, for optional NPB-WIFI-7 802.11 b/g WIFI adapter (WEBsAX-3.6 required).  
Two (2) available comm option slots in the WEB/CP-700, for LonWorks, RS-485 or RS-232, GPRS/Edge Cellular, Jennic  
802.15.4 wireless, etc.  
LEDs on front of unit to monitor power and system status.  
Available contact inputs (3) to monitor external UPS AC present, UPS battery level, external enclosure door status.  
POWER SUPPLY  
Requires universal AC input (90V – 264V) NPB-PWR-UN-H power supply module, supplies 15Vdc, 30VA. Alternately, a  
NPB-WPM-US wall-mount AC adapter can power the WEB/CP-700 only (requires removal of barrel plug end and wiring to end  
connector).  
Includes integral rechargeable NiMH backup battery pack, for short duration AC power fail operation.  
Connection for external, rechargeable, 12V sealed lead-acid battery, for continuous system operation over longer power  
outages. Provides trickle charge and monitoring support to separately ordered batteries.  
OPERATING SYSTEM  
QNX Neutrino Real-Time Operating System.  
Oracle Hotspot JVM (Java Virtual Machine) in units with WEBsAX-3.6 or later; IBM J9 JVM is used in units with WEBsAX-3.5.  
NiagaraAX software (WEBsAX-3.5 or later required). WEBsAX-3.6 or later required to use the optional NPB-WIFI-7 adapter.  
PHYSICAL  
Plastic DIN-mount backplate with screw tabs for alternate panel mounting.  
Removable snap-on plastic cover with status LEDs and connecting cable.  
Cooling by internal air convection.  
Dimensions: 8.7" (221mm) wide x 5.6" (142mm) high x 2.44" (62mm) deep.  
Weight: Net 1.67 lbs. (0.76 kg), Gross 2.0 lbs. (0.91 kg).  
ENVIRONMENT  
Operating temperature range: 32°F to 122°F (0°C to 50°C).  
Relative humidity range: 10% to 90% at 77°F (25°C), non-condensing.  
Mechanical ambient conditions are as follows:  
Vibration, in operation: 5 to 9 Hz: 3.5mm amplitude, 9 to 150Hz: 1g.  
Shock resistance, in operation: 15g acceleration, 11 ms duration.  
Storage temperature range: 32°F to 158°F (0°C to 70°C).  
Storage relative humidity range: 5% to 94%, non-condensing.  
Equipment Ratings  
ELECTRICAL  
Input voltage range: 15Vdc (from separate AC power supply, 90Vac to 264Vac, 50/60Hz).  
Power consumption: 20VA maximum.  
5
95-7776—03  
   
WEB-700 WEB-700-O CP-700  
PREPARATION  
Unpack the WEB/CP-700 and inspect the package contents for damaged or missing components. If damaged, notify the  
appropriate carrier at once and return any damaged components for immediate repair or replacement. See “Returning a  
Included in this Package  
Included in this package you should find the following items:  
WEB/CP-700 controller.  
WEB/CP-700 Installation Instructions, Form Number 95-7776.  
Hardware bag containing the following items:  
Two (2) 6-position screw terminal plugs, one for integral contact inputs (door tamper, UPS battery OK, UPS AC present),  
one end-mount to wire RS-485/power to optional remote expansion devices.  
One (1) 2-position screw terminal plug for external sealed lead-acid (SLA) rechargeable battery (not provided).  
One (1) grounding wire, with quick-disconnect 0.187" female connector.  
Material and Tools Required  
The following supplies and tools are typically required for installation:  
NPB-PWR-UN-H universal AC power supply module, 90-263 Vac input, 15Vdc 30W output, DIN-mount capable, with  
grounding wire.  
Alternatively, a NPB-WPM-US wall-mount AC adapter can power the WEB/CP-700 controller only. You must cut off the  
adapter’s barrel plug end, and then wire leads into the controller’s end connector. A multimeter is needed to check polarity.  
DIN rail, type NS35/7.5 (35mm x 7.5mm) and DIN rail end-clips (stop clips), unless using panel mounting method with screws  
through mounting tabs.  
Suitable tools and fasteners for mounting unit and accessories.  
#2 phillips screwdriver: used to install and remove an optional option card.  
Small flat-blade screwdriver: used for making wiring connections to removable screw terminal plugs.  
(Optional) One or two 12V sealed-lead-acid (SLA) rechargeable backup batteries, with wire harness for connecting to the  
2-position connector on the unit. Should be sized as required by the system. See Contact Input wiring to WEB/CP-700, page  
17.  
PRECAUTIONS  
This document uses the following warning and caution conventions:  
CAUTION  
Cautions remind the reader to be careful. They alert readers to situations where there is a chance that the reader  
might perform an action that cannot be undone, might receive unexpected results, or might lose data. Cautions  
contain an explanation of why the action is potentially problematic.  
WARNING  
Warnings alert the reader to proceed with extreme care in situations where there is a chance that the reader  
might do something that can result in personal injury or equipment damage. Warnings contain an explanation of  
why the action is potentially dangerous.  
Safety Precautions  
The following items are warnings of a general nature relating to the installation and start-up of the WEB/CP-700 controller. Be  
sure to heed these warnings to prevent personal injury or equipment damage.  
95-7776—03  
6
         
WEB-700 WEB-700-O CP-700  
WARNING  
A 120Vac or 240Vac circuit powers the NPB-PWR-UN-H power supply for the controller. 15Vdc input (DC only) to  
controller.  
Disconnect power before installation or servicing to prevent electrical shock or equipment damage.  
Make all connections in accordance with national and local electrical codes. Use copper conductors only.  
To reduce the risk of fire or electrical shock, install in a controlled environment relatively free of contaminants.  
This device is only intended for use as a monitoring and control device. To prevent data loss or equipment  
damage, do not use it for any other purpose.  
Static Discharge Precautions  
Static charges produce voltages high enough to damage electronic components. The microprocessors and associated circuitry  
within a WEB/CP-700 controller are sensitive to static discharge. Follow these precautions when installing, servicing, or operating  
the system:  
CAUTION  
Work in a static-free area.  
Discharge any static electricity you may have accumulated. Discharge static electricity by touching a known,  
securely grounded object. Do not handle printed circuit boards (PCBs) without proper protection against static  
discharge. Use a wrist strap when handling PCBs. The wrist strap clamp must be secured to earth ground.  
Battery Precautions  
CAUTION  
The NiMH battery used in this device may present a risk of fire or chemical burn if mistreated. Do not  
disassemble, heat above 122ºF (50ºC), or incinerate. Replace battery pack with NPB-BATT-7 only. Use of another  
battery may present a risk of fire or explosion.  
Dispose of used battery promptly. Keep away from children. Do not disassemble and do not dispose of in fire.  
Replace external backup battery with Listed Power Source Battery Only.  
MOUNTING  
NOTE: This product is intended for indoor use only. The unit should not be exposed to ambient conditions outside of  
the range of 32ºF (0ºC) to 122ºF (50ºC), or relative humidity outside the range of 10 to 90% at 77ºF (25ºC), non-  
condensing. Refer to Environment, page 5 for further details on mechanical and storage specifications.  
Before mounting the unit, install any option card(s) and memory upgrade. See About Expansion Options, page  
Environmental Requirements  
Note the following requirements for the WEB/CP-700 mounting location:  
If mounting inside an enclosure, that enclosure should be designed to keep the unit within its required operating range  
considering a 20-watt dissipation by the controller, plus dissipation from any other devices installed in the same enclosure.  
This is especially important if the controller is mounted inside an enclosure with other heat producing equipment.  
Do not mount the unit:  
in an area with excessive moisture, corrosive fumes, or explosive vapors.  
where vibration or shock is likely to occur.  
in a location subject to electrical noise. This includes the proximity of large electrical contractors, electrical machinery,  
welding equipment, spark igniters, and variable frequency drives.  
7
95-7776—03  
       
WEB-700 WEB-700-O CP-700  
Physical Mounting  
The following information applies about physically mounting the unit.  
You can mount the WEB/CP-700 in any orientation. It it not necessary to remove the cover before mounting.  
Mounting on a 35mm wide DIN rail is recommended. The WEB/CP-700 unit base has a molded DIN rail slot and locking clip,  
as does the NPB-PWR-UN-H power supply module and any I/O expansion modules. Mounting on a DIN rail ensures accurate  
alignment of connectors between all modules.  
If DIN rail mounting is impractical, use screws in mounting tabs on the NPB-PWR-UN-H module and the WEB/CP-700, as well  
as any end-connected accessory. Tab mounting dimensions are on the last page of this document.  
Fig. 3 and the following procedure provides step-by-step DIN rail mounting instructions for the WEB/CP-700.  
Mounting on  
DIN rail  
Removing from DIN rail  
WEB/CP-700  
NPB-PWR-UN-H  
DIN rail  
end clip  
Secure controller or last directly  
attached I/O module using either  
screws or DIN rail end clip (if end  
clip does not interfere with 6-  
position end connector).  
NPB-PWR-UN-H  
5.6"  
(142)  
IO-16-REM-H  
4.1" (104)  
3.46"  
(88)  
11.75" (298)  
15.125" (384)  
Fig. 3. WEB/CP-700 and accessory mounting details.  
NOTE: Mount the NPB-PWR-UN-H power supply first, then the WEB/CP-700 controller, then any directly attached I/O  
expansion module.  
95-7776—03  
8
 
WEB-700 WEB-700-O CP-700  
To mount on DIN rail  
1. Securely install the DIN rail with at least two screws, near the two rail ends.  
2. Position the NPB-PWR-UN-H power supply module on the rail, tilting to hook DIN rail tabs over one edge of the DIN rail  
(Fig. 3).  
3. Use a screwdriver to pry down the plastic locking clip, and push down and in on the module, to force the locking clip to snap  
over the other edge of the DIN rail.  
4. Mount the WEB/CP-700 controller onto the DIN rail in the same way, such that its left 6-position end connector faces the  
NPB-PWR-UN-H power supply.  
5. Slide the two devices together along the DIN rail to connect their 6-position connectors.  
6. If installing any I/O expansion modules, repeat this for each one, until all are mounted on the DIN rail and firmly connected  
into one assembly.  
7. To keep the final assembly together, secure at both ends with DIN rail end-clips provided by the DIN rail vendor. This also  
prevents the assembly from sliding on the DIN rail. See Fig. 3.  
Removing and Replacing the Cover  
You must remove the WEB/CP-700 cover to connect the battery (new unit), and/or to replace the NiMH battery, install any option  
cards, or replace the NiMH battery. The cover snaps onto the base with four plastic end tabs–two on each end.  
CAUTION  
An LED ribbon cable connects the cover to the main board. Be careful when lifting the cover off. If the controller  
is on a flat work surface, you can leave the cable connected, with the cover next to the unit. See Fig. 4.  
Connector for LED cable  
Cover  
LED ribbon  
cable  
LED cable left connected  
between cover and  
controller board  
Fig. 4. Removing WEB/CP-700 cover.  
NOTE: If accessory modules are plugged into the WEB/CP-700, you may need to slide them away from the unit to get to  
the end cover tabs.  
To remove the cover, press in the tabs on both ends of the unit, and carefully lift it off (see previous Caution). If necessary,  
unplug the LED cable from the cover, at the connector on the back of the cover (see Fig. 4).  
To replace the cover, make sure that the LED cable is connected and not folded outside the base. Orient the cover so the  
cutout area for comm ports is correct, then push inwards to snap in place.  
9
95-7776—03  
 
WEB-700 WEB-700-O CP-700  
Board Layout  
Fig. 5 shows the location of connectors, option slots, and other features of the main board in the WEB/CP-700. For side views of  
communications ports and other features, see Fig. 6, page 13.  
Option card 2 area including socket header  
Serial mode select jumper  
Earth grounding lug  
NiMH battery connector (keyed)  
MiniPCI socket  
LED header  
PS - OUT  
PS + OUT  
BB 12V  
RS-485 -  
RS-485 +  
485 GND  
PS -  
PS +  
DDR-2  
RAM  
RS-485  
support of  
remote IO  
modules  
LEDs  
LANn  
Debug  
LED  
LEDs  
status,  
heartbt  
LAN2  
Option card 1  
area including  
socket header  
From  
Secondary  
Ethernet  
(RJ-45)  
power  
supply  
module  
Door  
tamper  
Push-  
button  
SW1  
UPS battery OK  
RS-232 (DB-9) COM1  
LAN1  
Primary Ethernet  
(RJ-45)  
UPS AC present  
Contact Inputs  
External 12V backup battery  
Fig. 5. WEB/CP-700 main board layout details  
A WEB/CP-700 controller ships with both option card slots 1 and 2 open. The DDR-2 RAM socket is populated with a 1GB  
module. A variety of communications option cards are available. For related details, see the next section About Expansion  
95-7776—03  
10  
 
WEB-700 WEB-700-O CP-700  
ABOUT EXPANSION OPTIONS  
The WEB/CP-700 provides for field-installable expansion using these types of options:  
Option card — Install on connectors inside the WEB/CP-700 base unit. See About Option Cards, page 11.  
Remote I/O modules To wire to the WEB/CP-700’s right-side 6-pin connector. See About Remote I/O Modules, page 12.  
MiniPCI option card — (future use). See About MiniPCI Cards, page 12.  
About Option Cards  
The WEB-700/CP has two (2) available option slots to accept a custom option card, compatible with either of these types:  
Series 2 and 6 controller options cards: 30-pin, 2 row connector, or  
Future release Series 7 option cards: 40-pin, 3 row connector.  
To accept either, both option slots on the WEB/CP-700 base board have a 40-pin connector. See Fig. 5, page 10. Installing an  
option card is recommended before mounting the unit. See Installing an Option Card, page 12.  
WARNING  
Power to the WEB/CP-700 must be OFF when installing or removing option cards, or damage will occur! Also,  
you must be very careful to plug an option card into its connector properly (pins aligned).  
Option cards typically provide additional communications features, with the following available models (with others still in  
development) listed in Table 2.  
Table 2. WEB/CP-700 Option Cards  
Option  
Description  
Notes  
NPB-2X-RS485  
Dual, optically-isolated, RS-485 adapter with  
two 3-position removable screw-terminal  
connector plugs.  
30-pin option card.  
If installed in option slot 1, ports operate as COM5  
and COM6.  
NPB-LON  
FTT-10A LON (LonWorks) adapter  
with a 2-position removable  
screw-terminal connector plug.  
30-pin (WEB-2/6) option card.  
Port operates as LON1 if only one LON option, or  
LON2 in slot 2 if two LON cards.  
NPB-RS232  
NPB-GPRS-W-H  
Single port RS-232 adapter, with a DB-9M  
connector. Supports baud rates up to  
115200.  
30-pin (JACE-2/6) option card.  
If installed in option slot 1, port operates as COM5.  
GSM cellular modem card using GPRS  
(General Packet Radio Service), with  
onboard socket for SIM card, and a Wyless  
SIM. Includes a stub SMA antenna.  
30-pin (JACE-2/6) option card.  
Card uses two WEB/CP-700 COM ports, e.g. COM5  
and COM6 if option slot 1.  
1
NPB-MDM  
30-pin (JACE-2/6) option card.  
56Kbps Auto-dial/Auto-answer Modem with  
one RJ-11 connector for phone line.  
Does not have own UART (unlike most other serial  
cards). Operates as COM3 if installed in option slot 1,  
COM4 if in slot 2.  
1
Unlike with a Series 2/6 controller with an NPB-MDM installed in slot 1, the onboard RS-232 COM1 port (DB9) remains opera-  
tional. Also, any NPB-MDM option is unaffected by the “mode jumper” position for serial shell access (jumper in “serial shell”  
position affects the operation of the onboard RS-232 COM1 port only).  
11  
95-7776—03  
   
WEB-700 WEB-700-O CP-700  
OPTION CARD COM PORT ASSIGNMENTS  
COM port assignments for option cards installed in a WEB/CP-700 start at COM5, with Slot 1 evaluated first, then Slot 2. (COM1  
and COM2 are always assigned to the onboard RS-232 and RS-485 ports, while COM3 and COM4 are reserved for slots.)  
INSTALLING AN OPTION CARD  
For option-specific details, see the mounting & wiring document that accompanies the particular option card. The following  
procedure provides a basic set of steps.  
WARNING  
Installing an option card in option Slot 2 requires careful attention—you must carefully pry up the shield tab to  
install the option card under the tab. Do not install an option card in Slot 2 with the card resting on top of the  
shield tab! Otherwise, an electrical short or some other issue from misaligned card header pins may result.  
Mounting an option card in a WEB/CP-700.  
1. Remove power from the WEB/CP-700, including any external battery—see the previous on page 11.  
3. Remove the blanking plate for the option slot, retaining the two screws. Retain the blanking plate in case the option card  
must be removed later.  
4. Carefully insert the pins of the option card into the socket headers of the option card slot.  
NOTE: If installing in Slot 2, first carefully pry up the shield tab that goes over the standoff. Option card 2 must be  
installed under the shield tab.  
The mounting holes on the option board should line up with the standoffs on the base board. If they do not, the connec-  
tor is not properly aligned. Press until the option card is completely seated.  
5. Place the custom end plate for the option card over the connector(s) of the option card. With some option cards, the card’s  
end plate is pre-fastened.  
6. With the mounting holes aligned with the standoffs, place the two screws through the end plate, and into the standoffs on  
the WEB/CP-700 base board. Using a screwdriver, hand tighten these screws.  
7. Replace the cover on the controller.  
About Remote I/O Modules  
The WEB/CP-700 has an integral 6-pin connector to support remote I/O modules. The connector provides both 15Vdc power and  
RS-485 communications to modules on that connected trunk, and is located on the right side of the unit.  
Each remote I/O module has a DIN-mount base, and provides two (2) 6-pin connectors that allow you to “chain” multiple modules  
together into one assembly. Table 3. lists the currently available modules.  
Table 3. Remote I/O modules compatible with the WEB/CP-700  
Model  
Description  
Notes  
Provides the following I/O points:  
IO-16-REM-  
H
Remote I/O RS-485 Module  
DIN-mountable RS-485 comm  
module that provides 16 points I/O,  
with I/O point types as noted.  
8 - Universal Inputs (UIs).  
4 - Digital Outputs (DOs), SPST-relay type.  
4 - Analog Outputs, 0–10Vdc type.  
Up to 16 (maximum) IO-16-REM-H accessory modules are  
supported.  
Wiring is covered in a separate document, see the IO-16-REM-H  
Installation and Configuration Instructions.  
About MiniPCI Cards  
The WEB/CP-700 has one (1) available MiniPCI slot—see Fig. 5, page 10. This slot supports a specific 802.11 wireless (Wifi)  
adapter option, model NPB-WIFI-7.  
95-7776—03  
12  
   
WEB-700 WEB-700-O CP-700  
WIRING DETAILS  
See Fig. 5, page 10 to locate connectors and other components on the WEB/CP-700 controller.  
Make connections to the WEB/CP-700 in the following order.  
1. Install any option board (LON, RS-485, RS-232, etc.) in the available option slots. See Installing an Option Card, page 12  
for a procedure. For complete details, refer to the specific documentation that accompanied the option.  
2. Connect communications cables. See Communications Wiring, page 13 for ports available on the WEB/CP-700 base unit.  
For ports on any installed option board (RS-232, LON, RS-485, modem) see the specific mounting and wiring guide for any  
additional details.  
3. Apply power to the unit. See Power Up and Initial Checkout, page 19.  
Communications Wiring  
Communications ports on the WEB/CP-700 controller are primarily on the bottom side of the unit, with ports also on the right side  
and top (Fig. 6). Communications port types include:  
Ethernet  
Serial  
NOTE: Prior to connecting cables, provide strain relief for them to prevent damage to the controller.  
Top side  
Right side  
15V PS -, + and  
12V Backup Battery out  
Option slot 2 connector area  
Option slot 1 connector area  
Bottom side  
RS-485 COM2  
LAN 2 Ethernet (RJ-45)  
RS-232 (DB-9) COM1  
LAN 1 Primary Ethernet (RJ-45)  
Fig. 6. WEB/CP-700 communications ports.  
ETHERNET  
Two, female 1-Gigabit Ethernet connections are provided on the WEB/CP-700. These are RJ-45 connectors labeled LAN1 and  
LAN2. Use a standard Ethernet patch cable for connecting to a hub or Ethernet switch.  
The factory-default IP address for LAN1 on a WEB/CP-700 is 192.168.1.12n, where the last numeral n in the address matches  
the last digit in the WEB/CP-700’s serial number, and the subnet mask is 255.255.255.0. By default, LAN2 on a WEB/CP-700 is  
disabled.  
Refer to the NiagaraAX Install and Startup Guide for details on changing IP address.  
NOTE: Typically, you only use LAN1 (primary port), unless you have a specific application for the other LAN2 port. For  
example, isolating a driver’s network traffic, using LAN2. Do not use LAN2 as the primary port.  
13  
95-7776—03  
   
WEB-700 WEB-700-O CP-700  
SERIAL  
There are two “RS” serial ports on the WEB/CP-700 base board. Each has a UART capable of operation up to 115,200 baud. At  
the bottom of the board (see Fig. 6, page 13) is an RS-232 port using an DB-9 plug (male) connector. On the right side of the unit  
is an isolated RS-485 port, using the bottom three terminals of a 6-position screw-terminal connector plug.  
NOTE: Additional serial ports may be added with option card(s) in Option Slot 1 and Slot 2, such as an NPB-RS232  
card, or NPB-2X-RS485 card (note the last option actually adds two serial ports).  
RS-232  
An RS-232 serial port using a male DB-9 connector always operates as COM1. You can use standard DB-9 serial cables with this  
port. The WEB/CP-700 is a serial DTE device, another DTE device (PC, for example) requires a “null modem” cable. If  
connecting to a DCE device (modem, for example), use a straight-through cable. Table 4. provides standard serial DB-9 pinouts.  
NOTE: If rebooted with the mode jumper in the “Serial Shell” position (see Fig. 5, page 10), the RS-232 port provides  
“system shell” access. See the NiagaraAX Install and Startup Guide for related details.  
.
Table 4. Serial port (RS-232 and RS-485) pinouts.  
Base RS-232 DB-9 Port (COM1)  
Base RS-485 Port (COM2)  
Pinouts  
Pinout Reference  
Signal  
Data carrier detect  
Receive data  
DB-9 Pin  
DB-9 Plug  
DCD  
RXD  
TXD  
DTR  
GND  
DSR  
RTS  
CTS  
1
2
3
4
5
6
7
8
9
6-Position end connector  
PS – (GND)  
Power  
PS + (15V)  
Transmit data  
BB (12V Batt)  
Data terminal ready  
Ground  
(male)  
+
RS-485  
S
Data set ready  
Request to send  
Clear to send  
(male)  
not used on the 7  
RS-485  
An RS-485, optically isolated port is available on 3 pins of the 6-position right-side connector, and always operates as COM2. As  
shown in Table 4, the screw terminals are minus (–), plus (+), and shield. Wire in a continuous multidrop fashion to other RS-485  
devices, meaning “minus to minus”, “plus to plus,and “shield to shield.Connect the shield to earth ground at one end only, such  
as at the WEB/CP-700.  
Grounding  
An earth ground spade lug (0.187") is provided on the controller for connection to earth ground. For maximum protection from  
electrostatic discharge or other forms of EMI, connect the supplied earth grounding wire to this lug and a nearby earth ground.  
Keep this wire as short as possible, see Fig. 7.  
95-7776—03  
14  
 
WEB-700 WEB-700-O CP-700  
WEB/CP-700  
NPB-PWR-UN-H  
(remove cover)  
Grounding lug  
Supplied earth  
grounding wire  
20-pin  
connector  
not used  
AC Input  
L N  
Line  
Grounding lug  
Neutral  
120 or 240Vac  
50–60 Hz  
Single Phase  
Earth Ground  
Fig. 7. Grounding and power wiring connections to NPB-PWR-UN-H module.  
Power Wiring  
There are two power options for the WEB/CP-700 controller: the NPB-PWR-UN-H power supply module (typical), or a NPB-  
WPM-US (Wall Mount AC Adapter).  
NPB-PWR-UN-H  
The NPB-PWR-UN-H module lets you power the WEB/CP-700 (and if installed, connected I/O modules) from AC line power, with  
a universal input range from 90–263Vac. The NPB-PWR-UN-H installs on the left side (end) of the WEB/CP-700 controller. See  
Fig. 7.  
WARNING  
A 120Vac or 240Vac circuit powers the NPB-PWR-UN-H. Disconnect power to this circuit before installation to  
prevent electrical shock of equipment damage.  
Make all connections in accordance with national and local electrical codes. Use copper conductors only.  
Do not exceed the 30W capacity of NPB-PWR-UN-H by the powered devices.  
Power input connections are made to the terminals on the NPB-PWR-UN-H circuit board (cover removal is required). Use the  
supplied earth grounding wires to make a connection from a nearby earth ground to the grounding lug on both the  
NPB-PWR-UN-H power supply and the WEB/CP-700 controller. See Fig. 7, page 15.  
15  
95-7776—03  
 
WEB-700 WEB-700-O CP-700  
Wiring NPB-PWR-UN-H input power and earth ground.  
1. Remove power from the AC circuit being wired to the NPB-PWR-UN-H—see previous .  
2. Remove the NPB-PWR-UN-H cover.  
To do this, press in the four tabs on both ends of the unit, and lift the cover off. If the WEB/CP-700 is plugged into the unit,  
you may need to slide it away to get to the cover tabs.  
3. Connect the supplied earth grounding wire to a nearby grounding point. See Fig. 7.  
4. Make AC circuit connections line (mains) and neutral to the terminals labeled “INPUT PWR.”  
5. Replace the cover on the NPB-PWR-UN-H.  
Make sure all modules in the mounted assembly are firmly connected together and secured.  
CAUTION  
Do not energize the AC circuit wired to the NPB-PWR-UN-H until all other controller mounting and wiring is  
Power and ground is also provided in wiring to remote I/O modules through the 6-position connector. However, note for each  
remote I/O module, you should also connect its earth ground spade lug to earth ground at that module’s location.  
NPB-WPM-US (WALL MOUNT AC ADAPTER)  
You can order and adapt a wall mount AC adapter (model NPB-WPM-US) to power only the WEB/CP-700 controller. To use the  
adapter, you must cut off its “barrel plug” end, then wire the two leads into the top positions of the 6-position end connector plug,  
observing proper + and – polarity.  
NOTE: I/O modules cannot be powered by that NPB-WPM-US adapter.  
Before plugging the wired connector plug into the WEB/CP-700, check for 15Vdc at the proper polarity using a  
multimeter (see Fig. 8).  
Check with multimeter before  
Cut off barrel plug  
6-position  
end  
connector  
plug  
15.1  
V
DC  
-
-
+
+
NPB-WPM-US  
Positive (+) Wire with White Stripe  
Fig. 8. Adapting a NPB-WPM-US wall mount AC adapter to power the WEB/CP-700.  
Do not power the controller until all other mounting and wiring is completed. See Power Up and Initial Checkout, page 19.  
95-7776—03  
16  
WEB-700 WEB-700-O CP-700  
Contact Inputs  
Three contact inputs (CIs) are available on a 6-position connector next to the 2-position external battery connector. CIs are  
typically used to monitor normally-closed (N.C.) alarm contacts, if available on a UPS and/or the “door tamper” switch of an  
enclosure. These CIs are unsupervised—no end-of-line resistors are required. Fig. 9 shows example wiring to all three CIs of  
the WEB/CP-700.  
WEB/CP-700  
UPS Alarm Contacts  
Tamper  
switch  
Power Fail (if available)  
Low Battery (if available)  
Fig. 9. Contact Input wiring to WEB/CP-700  
17  
95-7776—03  
 
WEB-700 WEB-700-O CP-700  
EXTERNAL 12V BACKUP BATTERY  
A 2-position connector provides support for an external 12V sealed lead-acid (SLA) type rechargable battery. For more details,  
WEB/  
CP-700  
15Vdc power and  
backup battery  
passed through  
6-position  
connector  
712BNP 12V Sealed  
Lead Acid Backup  
Battery(ies)  
Fig. 10. Sealed lead-acid backup battery connection on WEB/CP-700.  
2
2
NOTE: The minimum wire size for battery connections is 18AWG (1.0mm ) for up to 4 ft. (1.22m), or 16AWG (1.29mm )  
for up to 12 ft. (3.66m).  
95-7776—03  
18  
 
WEB-700 WEB-700-O CP-700  
Wiring to Remote I/O Modules  
Wiring to remote I/O modules typically provides both 15Vdc power and 12V battery backup, along with RS-485 communications  
to the modules. See Fig. 11.  
Connect shield wire to ground at one end only  
WEB/CP-700  
Power Supply (15V) and 12V Backup  
Battery is routed to remote IO modules using  
a 3-conductor with shield cable. Use the  
shortest wiring route possible for power  
wiring—star, tee, bus, and loop topologies  
are all permissible.  
IO-16-REM-H  
RS-485 communications must be “daisy-  
chained” to remote IO modules using a  
separate shielded twisted-pair cable.  
IO-16-REM-H  
Connect RS-485 shield wire to ground at  
one end only  
Fig. 11. Power and RS-485 cabling between WEB/CP-700 and remote I/O modules  
POWER UP AND INITIAL CHECKOUT  
Following all mounting and wiring, perform the following:  
Initial power up and checkout.  
Apply Power  
The WEB/CP-700 controller does not include an on/off switch. To apply power, you simply energize the AC circuit (90–263 Vac)  
wired to the attached NPB-PWR-UN-H power supply module. If remote I/O modules are wired to the unit, they are also typically  
powered by the WEB/CP-700 as well.  
If powering the WEB/CP-700 controller with a NPB-WPM-US (Wall Mount AC Adapter), simply plug the AC adapter into a nearby  
wall outlet.  
Check the Status LED  
When power is applied, the front cover STATUS LED will light green. This indicates that the system is OK and that power is  
applied. The STATUS LED may be blinking until the QNX OS has finished loading and the Niagara platform daemon is running.  
Once this boot sequence has finished, the STATUS LED should remain lit (steady), and the BEAT LED should start blinking, at a  
typical rate of 1Hz. Typically, this is about 30 seconds after power is applied.  
19  
95-7776—03  
       
WEB-700 WEB-700-O CP-700  
If after applying power, the STATUS LED goes out, or if the BEAT LED comes on (steady) and stays lit longer than 2 minutes,  
contact your local distributor for technical assistance. See also “About LEDs” on page 21.  
About the Backup Batteries  
A WEB/CP-700 controller has two different backup batteries:  
An optional external, sealed lead-acid, rechargeable backup battery (or batteries). See below.  
For continuous system operation during loss of primary power (to the NPB-PWR-UN-H module powering the unit), unless power  
loss is only a few seconds, both batteries should be installed. Station alarms are generated if either battery is uncharged or  
unable to hold a sufficient charge, as well as whenever primary power is lost. You should always investigate any alarm related to  
backup batteries.  
NiMH battery pack  
A custom 10-cell NiMH (nickel metal hydride) battery pack is installed inside the WEB/CP-700, mounted atop the shield, and is  
secured by a metal bracket and two kep nuts. This battery allows the controller to continue station operation (only) through very  
short power bumps, meaning a few seconds in duration. In the case of a longer outage, the NiMH battery provides enough run  
time for the unit to backup data and then shutdown. Typically, this process takes about one minute. Shutdown occurs  
automatically, after data is backed up to on-board flash memory.  
Upon startup (boot), a test of the NiMH battery is performed. A system alarm is generated if the NiMH battery voltage level is  
found to be bad. A charge is also initiated upon startup, which lasts from 3 hours minimum, and can range up to 18 hours if the  
battery is completely discharged. During this NiMH battery charge period, neither the NiMH battery or the external backup battery  
is tested. After the startup NiMH charge period, a periodic test of both batteries occurs, and the appropriate battery alarm is  
generated is either battery is found to be bad.  
NOTE: If the last NiMH battery test was “bad,upon loss of primary power the controller performs an immediate shut-  
down, backing up data and powering off (including attached readers, and expansion modules).  
A NiMH battery characteristic is to lose charge if not left in charge mode (trickle charge). Leaving the battery  
unconnected, or the unit powered off, will cause the battery to fully discharge in a matter of weeks. Note that in  
the case of a new controller, it ships from the factory with a completely discharged battery. Therefore, allow at  
least 18 hours for the battery to charge after the controller is initially powered.  
Replace the NiMH battery pack approximately every three years, or more often if the unit is in a high temperature environment.  
For more information on the use and replacement of the battery, refer to Required NiMH Battery Maintenance, page 22.  
BACKUP BATTERY  
The optional sealed lead-acid backup battery (part number 712BNP) is an external, 12V, rechargeable battery (or multiple  
batteries) sized to operate the system during loss of primary power, for some duration. This includes the controller, as well as  
power to attached I/O expansion modules.  
Connect the backup battery to the controller using a 2-position connector—see Fig. 10, page 18. Whenever primary-powered, the  
controller supplies a constant “trickle” charge to this battery, at 200mA maximum. At startup (boot), a test of the backup battery is  
performed, as well as a periodic test. A system alarm is generated if a battery test deems the backup battery to be bad.  
Providing that the backup battery has tested good, upon loss of primary power the system operates from this backup battery  
power until the charge level of the on-board NiMH battery pack reaches 0. Note that both batteries discharge in parallel. However,  
as the sealed lead-acid backup battery capacity is much greater, the NiMH battery pack discharges much slower than if these  
backup battery(ies) were bad or not present.  
NOTE: If the backup battery test was “bad,upon loss of primary power, the controller performs an immediate shut-  
down, backing up data and powering off (including attached readers, expansion modules).  
Replace the sealed lead-acid backup battery(ies) approximately every three years, or more often if the unit is in a high  
temperature environment.  
95-7776—03  
20  
   
WEB-700 WEB-700-O CP-700  
ABOUT LEDS  
The WEB/CP-700 provides a number of LEDs on its main board. Only the Status and Heartbeat LEDs are visible on the cover.  
Checking other LEDs requires first removing the cover.  
LEDs include the following types:  
For the location of LEDs on the main board, see Fig. 5, page 10.  
Status  
The green “STATUS” LED is located on the cover. On the main board, it is also the green “SYSOK” LED next to the “HBEAT”  
LED—both are found near the Ethernet connector housing. The status LED should remain lit whenever the WEB/CP-700 is  
powered, or else be blinking during the boot sequence. If the status LED does not light while power is applied, contact System  
Engineering for technical support.  
Heartbeat  
The yellow heartbeat “HBEAT” LED is located on the cover, as well as on the main board next to the “SYSOK” Status LED. The  
heartbeat LED blinks about once per second. If the heartbeat LED stays on constantly, does not light, or blinks very fast (more  
than once per second), contact your local distributor for technical support.  
Debug  
The yellow “DEBUG” LED is located on the main board near the Ethernet connector housing, and remains lit whenever the WEB/  
CP-700 has been rebooted with the “serial mode select” jumper in the “serial shell” position (see Fig. 5, page 10). This indicates  
that the DB-9 RS-232 port is operating in serial shell mode.  
Ethernet Ports  
Two LEDs for each of the two LAN ports are provided on the back of the metal LAN connector housing, and operate as follows.  
The left-side green “activity” LED indicates activity on that port as follows:  
Off — No Ethernet link is made  
On — Ethernet link is present, but no activity on the LAN  
Blinking — Ethernet link is present with data activity on the LAN.  
The right-side yellow “speed” LED Indicates Ethernet connection speed, as either:  
OFF - "Fast Ethernet"/"Ethernet" (100 Mbps/10 Mbps).  
ON - "Gigabit Ethernet" speed (1000 Mbps).  
MAINTAINING THE WEB/CP-700  
This section provides information on the following topics:  
Cleaning  
If dust or metal filings are present inside the unit, clean with vacuum or compressed air. Otherwise, no cleaning inside the unit is  
required. If the cover becomes dirty, you can wipe it with a damp cloth and mild detergent.  
21  
95-7776—03  
             
WEB-700 WEB-700-O CP-700  
Required NiMH Battery Maintenance  
Battery life expectancy is a function of its discharge cycles (the number of discharges and their depth) and the ambient  
temperature of the battery during normal operation. In most applications, the NiMH battery should see relatively few discharges.  
Therefore, ambient temperature has more to do with the life expectancy of the battery than does any other factor. If the WEB/  
CP-700 is installed in a conditioned space, this battery should provide dependable service for approximately three years  
(average). In an environment where the operating temperature is higher (that is, 50ºC or 122ºF), you should only expect the  
battery to last approximately one year.  
The NiMH battery in the WEB/CP-700 controller is fully discharged when factory shipped. Additionally, NiMH batteries lose  
charge over time if not kept trickle-charged (for more details, see NiMH battery pack, page 20). Therefore, even a new unit (or  
replacement battery) will require up to 18 hours of powered operation before it can provide reliable backup power (is at full  
charge).  
The WEB/CP-700 monitors the NiMH battery and periodically loads the battery to test its ability to maintain battery-backed  
functions. Investigate any battery trouble message, and check the battery connections to the unit. Replace the battery as  
required. To order a new battery, see “Standard Replacement Parts” on page 23. See the section below for a replacement  
procedure.  
REPLACING THE NIMH BATTERY  
The replacement NiMH battery is an assembly, that is a custom battery pack with an attached cable and connector plug. See  
Fig. 12. To replace the battery, you must remove power to the unit and remove its cover.  
CAUTION  
Use only NiMH battery packs approved for use with the WEB/CP-700.  
Replacing NiMH battery assembly on a WEB/CP-700.  
1. Backup the WEB/CP-700 controller’s configuration to your PC using the appropriate WEBsAX software tool (for example,  
Workbench).  
2. Remove all power from the WEB/CP-700, including any sealed lead-acid battery. Wait for LED activity to stop—after a  
couple of minutes, all LEDs on the unit should be off.  
At this point you have access to the NiMH battery assembly (Fig. 12).  
Cover removed  
NiMH battery pack  
(NPB-BATT-7)  
Unplug/plug NiMH battery  
from/to connector  
1/4" (6mm) Kep nuts (2)  
fasten battery bracket to  
shield  
Battery  
bracket  
NiMH battery  
connector on  
controller board  
Fig. 12. Replacing NiMH battery pack in WEB/CP-700.  
95-7776—03  
22  
 
WEB-700 WEB-700-O CP-700  
NOTE: Dispose of the used NiMH battery properly.  
4. Unplug the NiMH battery from the main board connector (see Fig. 12).  
5. Using a 1/4" (6mm) nutdriver, unfasten and retain the two kep nuts that secure the metal battery bracket to the shield, and  
remove the shield and battery pack.  
6. Put the replacement battery into the metal shield, and refasten back into place on the shield, using the two kep nuts. Hand  
tighten with a nutdriver.  
7. Plug the battery connector plug of the replacement battery into the NiMH battery connector on the main board of the WEB/  
CP-700. The connector is keyed—you cannot plug the battery in reversed.  
8. Replace the cover.  
9. Restore power to the WEB/CP-700 and verify normal operation.  
BATTERY DISPOSAL  
Please dispose of the used NiMH battery in accordance with local, state, and federal regulations.  
WARNING  
Do not incinerate or mutilate the battery, as this may cause it to burst or release toxic materials.  
If regulations specify returning the old battery to a recycling center, but no acceptable recycling center can be found, please  
return the old NiMH battery pack to Tridium for proper disposal.  
REPLACEMENT PARTS  
Servicing the WEB/CP-700 may call for replacement parts. There are three categories of parts:  
Non-replaceable Parts  
FUSE  
The WEB/CP-700 contains a non-user replaceable 2.5A slow-blow fuse, soldered on the main circuit board. This fuse provides  
protection from internal shorts or connection to incorrect power supplies. If the fuse circuitry is suspect, contact your regional  
Tridium office for technical support. See “Returning a Defective Unit” on page 25.  
Standard Replacement Parts  
MEMORY  
Standard replacement parts are listed in Table 5, and can be ordered from stock without restriction. Standard replacement parts  
cannot be returned for credit and should be disposed of in an appropriate manner.  
Table 5. Standard replacement parts for a WEB/CP-700.  
Part Number  
NPB-BATT-7  
NPM-1GB  
Description  
1 GB DDR-2 333MHz SODIMM memory module (upgrade)  
H11696  
Hardware Bag for WEB/CP-700, containing screw terminal connector plugs (two 6-position,  
one 2-position, earth grounding wire).  
712BNP  
SLA 12V 7AH External backup battery.  
New Replacement Unit  
To replace an entire unit, order and install a new WEB/CP-700. If the faulty WEB/CP-700 is still in warranty, you can receive  
credit by returning it to Tridium. Be sure to contact Tridium for a return authorization (RA) number before shipping an item for  
return credit. See Returning a Defective Unit, page 25, for more details.  
NOTE: Before ordering a new WEB/CP-700, it is strongly recommended that you contact your normal technical support  
resource to eliminate the possibility of a software issue or mis-configuration problem.  
23  
95-7776—03  
       
WEB-700 WEB-700-O CP-700  
Replacing the WEB/CP-700  
NOTE: Before handling circuit boards, discharge any accumulated static by touching a nearby earth ground. For  
To replace a WEB/CP-700 with a new replacement unit, proceed as follows:  
Replacing a WEB/CP-700 main controller board.  
1. If possible, use the appropriate NiagaraAX software tool to back up the WEB/CP-700’s configuration to your PC.  
2. Remove power to the WEB/CP-700, including any external 12V battery. The unit should power down automatically. Wait for  
all LEDs to remain off.  
3. Remove the front cover. See Removing and Replacing the Cover, page 9.  
4. Note positions of all communications and other wiring cables going to the controller. If necessary, label connectors and  
accessory modules to avoid mis-connection later, after WEB/CP-700 is replaced.  
5. Unplug all Ethernet, serial, LON, modem, and I/O connectors from the controller. Note the position of installed option cards,  
if any. You must transfer them to the replacement WEB/CP-700 controller.  
6. Remove the controller from its mounting (DIN rail, panel mount tabs, etc).  
7. Remove any option cards from the old controller and install them into the replacement WEB/CP-700, if applicable. See  
Installing an Option Card, page 12 for more details.  
8. Mount the replacement WEB/CP-700 as it was previously, using the same DIN rail location and/or screws.  
9. Reconnect the earth ground wire to the WEB/CP-700 grounding lug and any installed accessory modules.  
10. Reconnect any Ethernet, serial, modem, and I/O connectors to the WEB/CP-700 board.  
11. If using IO modules, and any of your I/O points have voltage, turn the devices back on, or reconnect power to them.  
13. Restore power to the unit. It should boot up as a new unit (see Check the Status LED, page 19).  
14. Using the WEBsAX platform tools, re-commission the WEB/CP-700, and install the saved station database. For more  
details, see the WEBsAX Install and Startup Guide.  
95-7776—03  
24  
 
WEB-700 WEB-700-O CP-700  
Returning a Defective Unit  
For proper credit on an in-warranty unit, ship the defective unit to Tridium within 30 days.  
NOTE: If the defective unit is under warranty, please follow return instructions provided in this section.  
If the unit is out of warranty, please discard any replaced part.  
Do not return an out-of-warranty WEB/CP-700 to Tridium.  
Prior to returning the unit, contact one of the following Tridium offices to obtain a return materials authorization (RMA) number  
and other instructions.  
Please provide:  
Product model  
Serial number  
Nature of the defect  
PO number to secure the RMA  
United States  
Phone: 804-254-7086, ext. 11  
Return to:  
Tridium, Inc.  
2256 Dabney Road, Suite C  
Richmond, VA 23230  
Attn: Return Department RMA# ____________  
Asia/Pacific  
Phone: +65 6887 5154  
Fax: +65 6887 5342  
Email for technical support: [email protected]  
Return to:  
Tridium Asia Pacific Pte Ltd  
17 Changi Business Park Central 1  
Honeywell Building  
Attn: Mr Lim Hoon Chat, Engineering Mgr.  
Singapore 486073  
Attn: Return Department RA# ____________  
Australia/Asia Pacific Sales:  
25  
95-7776—03  
 
WEB-700 WEB-700-O CP-700  
CERTIFICATIONS  
Federal Communications Commission (FCC)  
This equipment generates, uses, and can radiate radio frequency energy, and if not installed and used in accordance with the  
instruction manual, may cause interference with radio communications. It has been tested and found to comply with the limits for  
a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection  
against such interference when operated in a commercial environment. Operation of this equipment in a residential area may  
cause interference, in which case, users at their own expense will be required to take whatever measures may be required to  
correct the interference. Any unauthorized modification of this equipment may result in the revocation of the owner's authority to  
continue its operation.  
Canadian Department of Communications (DOC)  
This Class A digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.  
Cet appareil numerique de la classe A respecte toutes les exigencies du Reglement sur le material broilleur du Canada.  
CE Declaration of Conformity  
Date: December, 2009  
Application of Council 89/336/EEC, 92/31/EEC, 73/23/EEC, 93/68/EEC  
Directive:  
Manufacturer: Tridium Inc.  
3951 Westerre Parkway, Suite 350  
Richmond, Virginia 23233  
United States of America  
Manufacturer’s Steve Fey, President  
Representative: Tridium Inc.  
Product Model Numbers: WEB/CP-700  
Type of Equipment: Electrical Equipment for Measurement, Control and Laboratory Use  
EMS Standards Applied:  
Standard  
Description  
Criteria Met  
Complies  
CISPR  
Radiated Emissions - Class A  
16-2-3:2006  
IEC 61000-4-2  
Electrostatic Discharge Immunity  
PASS  
Class B  
PASS  
IEC 61000-4-3  
IEC 61000-4-4  
IEC 61000-4-6  
Radiated Electromagnetic Field  
Immunity  
Class A  
PASS  
Electrical Fast Transient / Burst  
Immunity  
Class B  
Conducted Radio-Frequency Immunity PASS  
Class A  
PASS  
IEC 61010-1:2001  
rev. 9/19/03  
Safety requirement for electrical  
equipment  
For measurement, control and  
laboratory use  
I, Steve Fey, President of Tridium Inc., hereby declare that the equipment specified above conforms to the above Directives and  
Standards.  
95-7776—03  
26  
       
WEB-700 WEB-700-O CP-700  
TAB MOUNTING DIMENSIONS  
Measurements are in inches and (mm). DIN mounting is recommended over tab mounting. See Fig. 3, page 8.  
NOTE: Electronic and printed versions of this guide may not show the dimensions to scale.  
Verify all measurements before drilling.  
0.170" Dia. (4.32)  
0.1590" Dia. (4.04)  
0.98" (24.9)  
0.35" (8.9)  
1.72"  
(43.7)  
0.334"  
5.0" (127)  
Dia. (8.5)  
5.6"  
(142)  
2.50"  
(63.5)  
8.7" (221)  
Fig. 13. WEB/CP-700 tab mounting dimensions.  
27  
95-7776—03  
 
WEB-700 WEB-700-O CP-700  
NPB-PWR-UN-H  
3.48”  
(88.55)  
2.50"  
(63.5)  
8.125" (206)  
Distance between center of tabs from one unit to another unit  
Fig. 14. WEB/CP-700 with power supply attached.  
Automation and Control Solutions  
Honeywell International Inc.  
1985 Douglas Drive North  
Golden Valley, MN 55422  
customer.honeywell.com  
® U.S. Registered Trademark  
© 2012 Honeywell International Inc.  
95-7776—03 M.S. Rev. 03-12  
Printed in U.S.A.  

Black Diamond Equipment Automobile Accessories User Manual
Brother Printer 8910DW User Manual
Carrier 90MU User Manual
Century 5230 User Manual
Epson STYLUS RX500 User Manual
Friedrich MW18Y3FM User Manual
Haier Air Conditioner AC36ES1ERA User Manual
Hisense Group KFR 28GWE User Manual
Hollywood Baja Bicycle Carriers B2 User Manual
Honeywell VU844A User Manual