| HEAT CONTROLLER, INC.   Wall Mounted Multi-Zone Split System   MMC18DA-1 MMH18DA-1   MMC24DA-1 MMH24DA-1   MMC36TA-1 MMH36TA-1   Air Conditioning / Heat Pump   Installation Parts Provided   Installation Parts Provided   Standard Type   Installation plate   Type "A" screws and plastic anchors   Remote Control Holder   Type "B" screws   18/24K BTU/h   Air Intake   (side, rear)   more than 30 cm   (11.8 inch)   more than   30 cm   (11.8 inch)   Control cover   Connecting wire   Connection pipe   Drain hose   more than   more than   70 cm   60 cm   (27.6 inch)   (23.6 inch)   Air Outlet   36K BTU/h   Air Intake   (side, rear)   more than 30 cm   (11.8 inch)   more than   30 cm   (11.8 inch)   Control cover   Connecting wire   Connection pipe   Drain hose   more than   more than   70 cm   60 cm   (27.6 inch)   (23.6 inch)   Air Outlet   Installation Manual   3 Safety Precautions   Safety Precautions   To prevent injury to the user or other people and property damage, the following instructions   must be followed.   I Incorrect operation due to ignoring instructions will cause harm or damage. The seriousness   is classified by the following indications.   This symbol indicates the possibility of death or serious injury.   WARNING   This symbol indicates the possibility of injury or damage.   CAUTION   I Meanings of symbols used in this manual are as shown below.   Be sure not to do.   Be sure to follow the instruction.   WARNING   I Installation   Do not use a defective or   underrated circuit breaker.   Use this appliance on a   dedicated circuit.   For electrical work, contact   the dealer, seller, a qualified   electrician, or an Authorized   Service Center.   Always electrically ground   the product.   • There is risk of fire or electric • Do not disassemble or repair   • There is risk of fire or electric   shock.   the product. There is risk of   fire or electric shock.   shock.   Install the panel and the   cover of control box securely.   Always install a dedicated   circuit and breaker.   Use the correctly rated   breaker or fuse.   • There is risk of fire or electric • Improper wiring or installation • There is risk of fire or electric   shock.   may cause fire or electric   shock.   shock.   4 Wall Mounted Multi-Zone Split System Air Conditioner   Safety Precautions   For installation, always   contact the dealer or an   Authorized Service Center.   Do not modify or extend the   power cable.   Be cautious when   unpacking and installing   the product.   • There is risk of fire or electric   • Sharp edges could cause   • There is risk of fire, electric   shock.   injury. Be especially careful of   the case edges and the fins on   the condenser and evaporator.   shock, explosion, or injury.   Do not install the product   on a defective installation   stand.   Do not let the air conditioner   run for a long time when the   humidity is very high and a   door or a window is left open.   Be sure the installation area   does not deteriorate with age.   • It may cause injury, accident,   or damage to the product.   • Moisture may condense and   dampen or damage furniture.   • If the base collapses, the air   conditioner could fall with it,   causing property damage, product   failure, and personal injury.   Install the indoor unit on the wall where the   height from the floor is more than 8 ft. (2.4m).   Do not handle the pipe by yourself(customer)   • There are sharp moving parts that could cause   personal injury.   • High-Pressure refrigent may cause personal   injury.   8ft(2.4m)   Installation Manual   5 Safety Precautions   I Operation   Do not store or use flammable gas or   combustibles near the product.   • There is risk of fire or failure of product.   Gasolin   CAUTION   I Installation   Always check for gas   (refrigerant) leakage after   installation or repair of   product.   Install the drain hose to   ensure that water is drained   away properly.   Keep level even when   installing the product.   • Low refrigerant levels may   • A bad connection may cause   • To avoid vibration or water   cause failure of product.   water leakage.   leakage.   90°   Do not install the product   where the sound or hot air   from the outdoor unit could   be offensive to neighbors.   Use two or more people to   lift and transport the   product.   Do not install the product   where it will be exposed to   salt spray directly.   • It may cause a problem for   your neighbors.   • Avoid personal injury.   • It may cause corrosion on the   product. Corrosion,   particularly on the condenser   and evaporator fins, could   cause product malfunction or   inefficient operation.   6 Wall Mounted Multi-Zone Split System Air Conditioner   Installation of Indoor, Outdoor Unit   Installation of Indoor, Outdoor Unit   Read completely, then follow step by step.   Select the best location   Indoor unit   Indoor Unit   1. Does not have any heat or steam near the   unit.   2. Select a place where there are no obstacles   More than 10 cm   (3.9 inch)   More than 20 cm   (7.9 inch)   in front of the unit.   3. Make sure that condensation drainage can be   conveniently routed away.   4. Do not install near a doorway.   More than 2.4m   5. Ensure the unit is unobstructed, allow proper   space on all sides according to the arrows   and distance measurements in the figures.   6. Use a stud finder to locate studs to prevent   unnecessary damage to the wall.   (8 ft)   More than 10 cm   (3.9 inch)   CAUTION: Install the indoor unit   on the wall where the height from   the floor is more than 2.4 m (8 ft).   Outdoor unit   18/24K BTU/h   more than 30 cm   (11.8 inch)   1. If an awning is built over the unit to prevent   direct sunlight or rain exposure, make sure   that heat radiation from the condenser is not   restricted.   more than 30 cm   (11.8 inch)   2. Ensure the unit is unobstructed, allow proper   space on all sides according to the arrows   and distance measurements in the figures.   more than 70 cm   (27.6 inch)   3. Do not place animals and plants in the path   of the warm air.   more than 60 cm   (23.6 inch)   4. Take the air conditioner weight into account   and select a place where noise and vibration   are minimum.   more than 30 cm   (11.8 inch)   36K BTU/h   5. Select a place so that the warm air and sound   from the air conditioner does not disturb   neighbors.   more than 30 cm   (11.8 inch)   Rooftop Installations:   If the outdoor unit is installed on a roof   structure, be sure to level the unit. Ensure the   roof structure and anchoring method are   adequate for the unit location. Consult local   codes regarding rooftop mounting.   more than 70 cm   (27.6 inch)   more than 60 cm   (23.6 inch)   Installation Manual   7 Installation of Indoor, Outdoor Unit   Seaside Applications and Installation   1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are   produced.   2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result   in corrosion to the product. Particularly on the condenser and evaporator fins, could   cause product malfunction or inefficient performance.   3. If the outdoor unit is installed close to the seaside, ensure that it is not exposed directly to   the sea wind.   1. Selecting the location(Outdoor Unit)   1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.   Install the outdoor unit on the opposite side of the sea wind direction.   Sea wind   Sea wind   2) To install the outdoor unit on the seaside, set up a windbreaker/barrier, to lessen the unit's exposure to sea air   • It should be strong enough (like concrete) to obstruct   the wind from the sea.   Windbreaker/Barrier   • The height and width should be more than 150% of   the outdoor unit.   Sea wind   • A minimum of 70cm (27.6inches)   of space between outdoor unit and the windbreaker/   barrier for easy air flow.   3) Select a well-drained place.   Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger   using water is recommended.   8 Wall Mounted Multi-Zone Split System Air Conditioner   Installation of Indoor, Outdoor Unit   Piping length and elevation   Multi-Zone Piping Recommendations:   Max total length Max length of   Max Elevation   Max elevation   between each   between indoor   indoor unit and   units (h2)   Min length of   each pipe   (A/B/C)   Capacity   of all pipes   each pipe   (A/B/C)   (A+B/A+B+C)   outdoor unit (h1)   18K BTU/h   24K BTU/h   36K BTU/h   30 m (100 ft)   30 m (100 ft)   45 m (150 ft)   15 m (50 ft)   15 m (50 ft)   15 m (50 ft)   3 m (10 ft)   3 m (10 ft)   3 m (10 ft)   7.5 m (25 ft)   7.5 m (25 ft)   7.5 m (25 ft)   7.5 m (25 ft)   7.5 m (25 ft)   7.5 m (25 ft)   Pipe Size   Indoor Capacity   Additional   Refrigerant   Gas (Flare)   Liquid (Flare)   Standard Length   9K BTU/h   9.52 mm (3/8")   9.52 mm (3/8")   6.35 mm (1/4")   6.35 mm (1/4")   7.5 m (25 ft)   7.5 m (25 ft)   20 g/m (0.22 oz/ft)   20 g/m (0.22 oz/ft)   12K BTU/h   36K BTU/h   18/24K BTU/h   A A h2   h2   h2   B B h1   h1   C h1   h1   h1   B CAUTION: Capacity is based on standard length and maximum allowance   length based on reliability.   Installation Manual   9 Installation of Indoor, Outdoor Unit   Mounting Installation Plate   The wall you select should be strong and solid   enough to prevent vibration   Installation Plate   1. Mount the installation plate on the wall with   type "A" screws. If mounting the unit on a   concrete wall, use anchor bolts.   • Mount the installation plate horizontally by   aligning the centerline using a level.   Chassis   Hook   Type "A" screw   2. Measure the wall and mark the centerline. It   is also important to use caution concerning   the location of the installation plate-routing   of the wiring to power outlets is through the   walls typically.   Distance mm (inch)   CHASSIS   (Grade)   A B C D 9K BTU/h   50 (1.97) 105 (4.13) 59 (2.32) 105 (4.13)   65 (2.56) 110 (4.33) 85 (3.35) 110 (4.33)   12K BTU/h   Installation plate   B D A C Ø 70 mm   Ø 2.75 inch   Ø 70 mm   Ø 2.75 inch   Left rear piping   Right rear piping   Drilling the hole in the wall   • Drill the piping hole with a Ø 70 mm (Ø 2.75 inch) hole core drill. Drill the piping hole at either   the right or the left with the hole slightly slanted to the outdoor side.   WALL   Indoor   Outdoor   10 Wall Mounted Multi-Zone Split System Air Conditioner   Flaring Work and Connection of Piping   Flaring Work and Connection of Piping   Flaring work   Main cause for gas leakage is due to defect in flaring work. Carry out the correct flaring work by   using the following procedures.   Cut the pipes   1. Use the piping kit accessory or the pipes   purchased locally.   Copper   pipe   Slanted Uneven Rough   2. Measure the distance between the indoor and   the outdoor unit.   90°   3. Cut the pipes a little longer than measured   distance.   4. Cut the cable 1.5 m (5.0 ft) longer than the pipe   length.   Pipe   Burrs removal   Reamer   1. Completely remove all burrs from the cut cross   section of pipe/tube.   Point down   2. Put the end of the copper tube/pipe in a   downward direction as you remove burrs in   order to avoid dropping burrs into the tubing.   Flare nut   Putting flare nuts on   1. Remove flare nuts attached to indoor and   outdoor unit, then put them on pipe/tube having   completed burr removal.   Copper tube   (not possible to put them on after flaring work)   Flaring work   1. Carry out flaring work using flaring tool as   shown below.   2. Firmly hold copper pipe in a bar in the   dimension shown in the table below.   Handle   Yoke   Bar   Bar   Cone   Outside diameter   A mm   Ø6.35   Ø9.52   inch   1/4   3/8   mm   1.1~1.3   1.5~1.7   inch   0.4 - 0.5   0.6 - 0.7   Copper pipe   Clamp handle   Red arrow mark   Installation Manual 11   Flaring Work and Connection of Piping   Check   Smooth all round   1. Compare the flared work with the figure on   the right.   Inside is shiny without scratches   2. If a flared section is defective, cut it off and   repeat the flaring process again.   = Improper flaring =   Inclined Surface Cracked Uneven   damaged   thickness   Even length   all round   Connecting the Piping   Indoor   1. Prepare the indoor unit's piping and drain hose for installation through the wall.   2. Remove the plastic tubing retainer(see the   illustration on the right) and pull the tubing   and drain hose away from chassis.   For right rear piping   1. Route the indoor tubing and the drain hose in   the direction of rear right.   2. Insert the connecting cable into the indoor unit   from the outdoor unit through the piping hole.   • Do not connect the cable to the indoor unit.   • Make a small loop with the cable for easy   Drain hose   connection later.   3. Tape the tubing, drain hose, and the   connecting on cable. Be sure that the drain   hose is located on the lowest side of the   bundle. Locating on the upper side can cause   the condensation to overflow in the drain pan   inside the indoor unit.   If the drain hose is routed inside the room,   insulate the hose with an insulation material*   so that dripping from "sweating"(condensation)   will not damage furniture or floors.   *Foamed polyethylene or equivalent is   recommended.   Tape   Connecting   pipe   Drain hose   Connecting cable   12 Wall Mounted Multi-Zone Split System Air Conditioner   Flaring Work and Connection of Piping   4. Indoor unit installation   Hook the indoor unit onto the upper portion of   the installation plate.(Engage the two hooks   of the rear top of the indoor unit with the   upper edge of the installation plate.) Ensure   that the hooks are properly seated on the   installation plate by moving it left and right.   Connecting   cable   Drain hose   Press the lower left and right sides of the unit   against the installation plate until the hooks   engage into their slots(clicking sound).   Connecting the piping to the indoor unit and   drain hose to drain pipe.   1. Align the center of the pipes and sufficiently   tighten the flare nut by hand.   Indoor unit tubing   Flare nut Pipes   2. Tighten the flare nut with a wrench.   Open-end wrench (fixed)   Outside diameter   Torque   mm   Ø6.35   Ø9.52   inch   1/4   3/8   kgf.m (lbf-ft)   1.8 ~ 2.5 (13)   3.4 ~ 4.2 (20)   Flare nut   Wrench   Connection pipe   Indoor unit tubing   3. Next, extend the indoor unit's drain hose.   Then attach the drain pipe.   Drain pipe   Indoor unit drain hose   Vinyl tape(narrow)   Adhesive   Wrap the insulation material around all   connections.   Plastic bands   Insulation material   1. Overlap the connection pipe insulation   material and the indoor unit pipe insulation   material. Bind them together with vinyl tape   so that there is no gap.   Indoor unit pipe   Wrap with vinyl tape   Connection pipe   Vinyl tape (wide)   2. Wrap the area which accommodates the rear   piping housing section with vinyl tape.   Connecting cable   Pipe   Vinyl tape(narrow)   3. Bundle the piping and drain hose together by   wrapping them with vinyl tape for enough to   cover where they fit into the rear piping   housing section.   Wrap with vinyl tape   Pipe   Vinyl tape(wide)   Drain hose   Installation Manual 13   Flaring Work and Connection of Piping   For left rear piping   1. Route the indoor tubing and the drain hose to   the required piping hole position.   Connecting   cable   2. Insert the piping, drain hose, and the   connecting cable into the piping hole.   3. Insert the connecting cable into the indoor unit.   • Don't connect the cable to the indoor unit.   • Make a small loop with the cable for easy   connection later.   Drain pipe   4. Tape the drain hose and the connecting   cables.   5. Indoor unit installation   • Hang the indoor unit from the hooks at the   top of the installation plate.   Indoor unit   Spacer   • Insert the spacer between the indoor unit   and the installation plate and separate the   bottom of the indoor unit from the wall.   Installation plate   8 cm   (3.15 inch)   Connecting the piping to the indoor unit and   the drain hose to drain pipe.   1. Align the center of the pipes and sufficiently   tighten the flare nut by hand.   Indoor unit tubing   Flare nut Pipes   2. Tighten the flare nut with a wrench.   Open-end wrench (fixed)   Outside diameter   Torque   mm   Ø6.35   Ø9.52   inch   1/4   3/8   kgf.m (lbf-ft)   1.8 ~ 2.5 (13)   3.4 ~ 4.2 (20)   Flare nut   Wrench   Connection pipe   Indoor unit tubing   3. Next, extend the indoor unit's drain hose.   Then attach the drain pipe.   Drain hose   Indoor unit drain hose   Vinyl tape (narrow)   Adhesive   14 Wall Mounted Multi-Zone Split System Air Conditioner   Flaring Work and Connection of Piping   Wrap the insulation material around the   connecting portion.   Plastic bands   Insulation material   1. Overlap the connection pipe insulation and   the indoor unit pipe heat insulation material.   Bind them together with vinyl tape so that   there is no gap.   Indoor   unit piping   2. Wrap the area which accommodates the rear   piping housing section with vinyl tape.   Connection   pipe   Vinyl tape   (wide)   Wrap with vinyl tape   Pipe   Vinyl tape(narrow)   Connecting cable   Drain hose   Pipe   3. Bundle the piping and drain hose together by   wrapping them with vinyl tape over the range   within which they fit into the rear piping   housing section.   Vinyl tape(narrow)   Wrap with   vinyl tape(wide)   Reroute the piping and the drain hose   across the back of the chassis.   Piping for   passage through   piping hole   Indoor unit installation   1. Remove the spacer.   Connecting   cable   2. Ensure that the hooks are properly seated on   the installation plate by moving it left and   right.   Drain hose   3. Press the lower left and right sides of the unit   against the installation plate until the hooks   engage into their slots(clicking sound).   Installation Manual 15   Flaring Work and Connection of Piping   Installation Information. For left piping. Follow the instruction below.   Best Practice   • Press on the upper side of clamp and unfold the tubing to slowly downward.   Worst Practice   • Bending the pipe from right to left may cause damage to the tubing.   16 Wall Mounted Multi-Zone Split System Air Conditioner   Flaring Work and Connection of Piping   Outdoor   Align the center of the piping and sufficiently   tighten the flare nut by hand.   Finally, tighten the flare nut with a torque   wrench until the wrench clicks.   Outdoor unit   18/24K BTU/h   • When tightening the flare nut with the torque   wrench, ensure the direction for tightening   follows the arrow on the wrench.   A-UNIT   Gas side piping   Outside diameter   Torque   mm   Ø6.35   Ø9.52   inch   1/4   3/8   kgf.m (lbf-ft)   1.8 ~ 2.5 (13)   3.4 ~ 4.2 (20)   B-UNIT   Liquid side piping   Torque wrench   Outdoor unit   36K BTU/h   A-UNIT   Gas side piping   B-UNIT   Liquid side piping   C-UNIT   Torque wrench   Installation Manual 17   Connecting the Cable between Indoor Unit and Outdoor Unit   Connecting the Cable between Indoor Unit and Outdoor Unit   Connect the cable to the Indoor unit   Connect the cable to the indoor unit by connecting the wires to the terminals on the control   board individually according to the outdoor unit connection. (Ensure that the color of the wires   of the outdoor unit and the terminal No. are the same as those of the indoor unit.)   The ground wire should be longer than the common wires.   The circuit diagram is subject to change without notice.   When installing, refer to the electrical diagram behind the front panel of Indoor Unit.   The wiring for the outdoor unit can be found on the inside of the Outdoor Unit control cover.   RECOMMENDATION:   • The circuit diagram is subject to change without notice.   • Be sure to connect wires according to the wiring diagram.   • Connect the wires firmly, so that they can not be pulled out easily.   • Connect the wires according to color codes by referring to the wiring diagram.   RECOMMENDATION:   Main power source   Provide a   circuit breaker between power   source and the outdoor unit as   Air   Circuit Breaker   Use a circuit breaker   or time delay fuse.   shown below.   Conditioner   RECOMMENDATION: The power cord connected to the outdoor unit should   comply with the following specifications: ETL recognized and CSA certified.   AWG12 (Allowable temperature   to the wire rated at least 90C˚)   18 / 24K BTU/h   36K BTU/h   AWG14   Line voltage (208~230V)   Line voltage (208~230V)   The power connecting cable connected to the indoor and outdoor unit   should be comply with the following specifications: ETL recognized and   CSA certified.   AWG18   Low voltage (below 40V)   RECOMMENDATION: When using the separate wires as the power cord, please secure   the separate wires into the control box panel using tie wraps to hold all wires   together in place.   18 Wall Mounted Multi-Zone Split System Air Conditioner   Connecting the Cable between Indoor Unit and Outdoor Unit   Connect the cable to the Outdoor unit   1. Remove the control cover from the unit by   loosening the screws.   Outdoor unit   Connect the wires to the terminals on the   control board individually per the following.   Terminal block   Over 5 mm   (0.2 inch)   2. Secure the cable onto the control board with   the holder (clamper).   Holder for   power supply   cord   3. Re-attach the control cover to the original   position using the screws.   18K BTU/h   Power supply   cable   Teminal on the Indoor Unit   A-UNIT   Teminal on the Indoor Unit   B-UNIT   1 2 3 4 1 2 3 4 Control cover   Connecting cable(Low voltage)   Connecting   cable   L1   L2   1 2 3 4 1 2 3 4 Teminal on the Outdoor Unit   Teminal on the Outdoor Unit   A Indoor   B Indoor   Power Source   208/230V AC   (High voltage)   24K BTU/h   Teminal on the Indoor Unit   A-UNIT   Teminal on the Indoor Unit   B-UNIT   1 1 2 3 4 1 2 3 4 Connecting cable(Low voltage)   2 3 4 1 2 3 4 L1   L2   Teminal on the Outdoor Unit   Teminal on the Outdoor Unit   Teminal on the Outdoor Unit   A Indoor   B Indoor   Power Source   208/230V AC   (High voltage)   36K BTU/h   Teminal on the Indoor Unit   A-UNIT   Teminal on the Indoor Unit   B-UNIT   Teminal on the Indoor Unit   C-UNIT   1 1 2 3 4 1 2 3 4 1 2 3 4 Connecting cable(Low voltage)   2 3 4 1 2 3 4 1 2 3 4 L1   L2   Teminal on the Outdoor Unit   Teminal on the Outdoor Unit   Teminal on the Outdoor Unit   Teminal on the Outdoor Unit   A Indoor   B Indoor   C Indoor   Power Source   208/230V AC   (High voltage)   NOTICE   : 1. Separately wire the high and low voltage lines.   2. Use heat resistant electrical wiring capable of withstanding temperatures up to 75°C(167°F).   3. Use outdoor waterproof connection cable rated for at least 300V for the connection between   indoor and outdoor unit. (For example, Type SJO-WA)   WARNING:   • Be sure to comply with local and national codes while running the wire from the   indoor unit to the outdoor unit(size of wire and wiring method, etc).   • Every wire must be connected firmly.   • No wire should be allowed to touch refrigerant tubing, the compressor or any   moving parts.   Installation Manual 19   Connecting the Cable between Indoor Unit and Outdoor Unit   Methods of connecting the cable   (1) Remove two-caps on the conduit panel.   (for low voltage line)   (2) Pull the connection cable through conduit.   (3) After conduit is through the panel, secure the nut   on the opposite side of panel.   Terminal   block   (4) Pass the connection cable through the hole.   (5) Properly connect the cable onto the terminal   block.   Cord clamp   Cap(Reuse)   G Lock nut   (6) Secure the connection cable with cord clamp   provided on the unit to reduce strain at the   terminal when the connection cable is pulled   outside up to a 35 pound weight   Hole   (for low voltage line)   Cap(Remove)   Taping   (for sealing)   WARNING: Loose wiring may cause   the terminal to overheat or result in   unit malfunction. A fire hazard may   also exist. Therefore, be sure all   wiring is tightly connected.   Power supply line Conduit panel   (1ø, 230/208V)   Low voltage line   (connecting cable)   When connecting each power wire to the   corresponding terminal, follow instructions "How   to connect wiring to the terminals" and fasten the   wire tightly using the screw on of the terminal   plate.   How to connect wiring to the terminals   High voltage   For strand wiring   (1) Cut the wire end with a wire cutter or wire-   cutting pliers, then strip the insulation to   expose the strand wiring about 10 mm(3/8").   (2) Using a screwdriver, remove the terminal   screw(s) on the terminal plate.   Strand wire   Round   terminal   (3) Using a round terminal fastener or pliers,   securely clamp each stripped wire end with a   round terminal.   (4) Position the round terminal wire, and replace   by tightening the terminal screw using a   screwdriver.   Low voltage   Loosening the   terminal block   screw   Fastening the   wire tightly   Connecting cable   20 Wall Mounted Multi-Zone Split System Air Conditioner   Connecting the Cable between Indoor Unit and Outdoor Unit   CAUTION: Provide a circuit breaker between power source and the unit   as shown below.   Main power source   Fuse or breaker   Model   Power source   Capacity   Air   18K BTU/h 1Ø, 230 / 208V   24K BTU/h 1Ø, 230 / 208V   36K BTU/h 1Ø, 230 / 208V   20 A   25 A   40 A   Circuit Breaker   Use a circuit   breaker or time   delay fuse.   Conditioner   Connect the cable to the indoor unit   1. Connect the wires to the terminals on the   control board individually according to the   outdoor unit connection.   • Ensure that the color of the wires of outdoor   unit and the terminal No. are the same as   those of indoor unit respectively.   Connecting cable   2. Attach the Grille onto the cabinet.   • Grasp the lower left and right side of the   Grille and engage four tabs on the top inside   edge of the chassis.   • Press the Grille toward the chassis until it   goes back into place.   Installation Manual 21   Checking the Drainage, Insulating the Pipe and Special Piping Applications   Checking the Drainage, Insulating the Pipe and Special Piping Applications   Checking the drainage   To check the drainage.   1. Pour a glass of water into the evaporator.   2. Ensure the water flows through the drain   hose of the indoor unit without any leakage   and goes out through the drain exit.   Drain piping   1. The drain hose should point downward for   optimum drainage.   Downward slope   2. Incorrect Installation Examples:   Accumulated   drain water   Air   Do not raise   Less than   50mm gap   Tip of drain hose   dipped in water   Water   leakage   Water   leakage   Water   leakage   Kinking   Ditch   22 Wall Mounted Multi-Zone Split System Air Conditioner   Checking the Drainage, Insulating the Pipe and Special Piping Applications   Insulating the Pipe and Special Piping Applications   Insulate the piping by wrapping the   connecting portion of the indoor   unit with insulation material and   secure it with two kinds of vinyl   Seal a small   opening around   the pipings with   gum type sealant.   Taping   Drain hose   tape.   • If you want to connect an additional drain   hose, the end of the drain outlet should be   Plastic   routed above the ground. Secure the drain   hose appropriately.   Pipings   band   Connecting   cable   In cases where the outdoor unit is   installed below the indoor unit   perform the following:   Power supply   cord   1. Tape the piping, drain hose and connecting   cable from down to up.   2. Secure the taped piping along the exterior   wall using saddle or equivalent.   • Trap is required to prevent water from entering   into electrical parts.   In cases where the Outdoor unit is   installed above the Indoor unit   perform the following.   1. Tape the piping and connecting cable from   down to up.   Seal a small opening   around the pipings   with gum type sealant.   Trap   2. Secure the taped piping along the exterior   wall. Form a trap to prevent water entering   the room.   3. Secure the piping onto the wall using a   saddle or equivalent.   Trap   Installation Manual 23   Air Purging and Evacuation   Air Purging and Evacuation   Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.   1. Pressure in the system rises.   2. Operating current rises.   3. Cooling(or heating) efficiency drops.   4. Moisture in the refrigerant circuit may freeze and block capillary tubing.   5. Water may lead to corrosion of parts in the refrigeration system.   Therefore, the indoor/outdoor unit and connecting tube must be checked for leaks and vacuumed   to remove incondensible gas and moisture in the system.   Leak Checking   1. Do a leakage test of all joints of the   tubing(both indoor and outdoor) and both gas   and liquid side service valves with soap   bubbles.   Bubbles indicate a leak. Be sure to wipe off   the soap with a clean cloth.   Preparation   • Check that each tube(both liquid and gas side   tubes) between the indoor and outdoor units have   been properly connected and all wiring for the test   run has been completed. Remove the service   valve caps from both the gas and the liquid sides   on the outdoor unit. Check that both the liquid and   the gas side service valves on the outdoor unit   are kept closed at this stage.   2. After the system is found to be free of leaks,   relieve the nitrogen pressure by loosening the   charge hose connector at the nitrogen   cylinder. When the system pressure is   reduced to normal, disconnect the hose from   the cylinder.   Leakage test   • Connect the manifold valve(with pressure gauges)   and dry nitrogen gas cylinder to this service port   with charge hoses.   Indoor unit   CAUTION: Be sure to use a   manifold valve for leak testing.   The high side manifold valve must   always be kept closed.   Outdoor unit   • Pressurize the system to no more than 150   P.S.I.G. with dry nitrogen gas and close the   cylinder valve when the gauge reading   reached 150 P.S.I.G. Next, test for leaks with   liquid soap.   Manifold valve   Pressure   CAUTION: To avoid nitrogen   entering the refrigerant system in a   liquid state, the top of the cylinder must be   higher than its bottom when you pressurize   the system. Usually, the cylinder is used in   a vertical standing position.   Lo   Hi   gauge   Charge hose   Nitrogen gas   cylinder(in vertical   standing position)   NOTICE   : Leakage testing should be done   for each indoor unit connection set,   separately.   24 Wall Mounted Multi-Zone Split System Air Conditioner   Air Purging and Evacuation   Evacuation   1. Connect the charge hose end described in   the preceding steps to the vacuum pump to   evacuate the tubing and indoor unit.   Confirm the "Lo" knob of the manifold valve is   open. Then, run the vacuum pump.   Indoor unit   The operation time for evacuation varies with   tubing length and capacity of the pump.   [Each Room] The vacuum pump must be   operated less than 0.8torr (0.015 psi) of the   gage pressure.   Outdoor unit   2. When the desired vacuum is reached, close   the "Lo" knob of the manifold valve and stop   the vacuum pump.   Finishing the job   1. With a service valve wrench, turn the valve   stem of liquid side valve counter-clockwise to   fully open the valve.   Manifold valve   Pressure   gauge   Lo   Hi   2. Turn the valve stem of gas side valve   counter-clockwise to fully open the valve.   3. Loosen the charge hose connected to the   gas side service port slightly to release the   pressure, then remove the hose.   Open   Close   4. Replace the flare nut and its bonnet on the   gas side service port and fasten the flare nut   securely with an adjustable wrench. This   process is very important to prevent leakage   from the system.   Vacuum pump   5. Replace the valve caps at both gas and liquid   side service valves and fasten them tight.   This completes air purging with a vacuum   pump.   The air conditioner is now ready for test   running.   NOTICE   : Repeat evacuation procedure for each   indoor unit.   Installation Manual 25   Charging   Charging   I Each outdoor unit is factory charged (see rating plate) for the evaporator as well as a 7.5 m (25 ft) line   set for each indoor line.   Any time total line set is used either shorter or longer then the nominal, which is for Single Zone   = 7.5m, Dual Zone = 15m, and Tri-Zone = 22.5 (Single Zone = 25ft, Dual Zone = 50ft, and Tri   Zone = 75 ft), the line set length the refrigerant charge has to be adjusted.   I Whether the line set is made shorter or longer you must adjust the charge based on how many ft   of tubing are either added or removed based on 20 g (0.22 oz) of R410A per meter(foot).   Max Elevation   between each   indoor unit and   outdoor unit (h1)   Max elevation   between   indoor units   (h2)   Max total   length of all   pipes (A+B+C)   Max length of Min length of   Additional   Refrigerant   Capacity   each pipe   (A/B/C)   each pipe   (A/B/C)   18K BTU/h   24K BTU/h   36K BTU/h   30 m (100 ft)   30 m (100 ft)   45 m (150 ft)   15 m (50 ft)   15 m (50 ft)   15 m (50 ft)   3 m (10 ft)   3 m (10 ft)   3 m (10 ft)   7.5 m (25 ft)   7.5 m (25 ft)   7.5 m (25 ft)   7.5 m (25 ft)   7.5 m (25 ft)   7.5 m (25 ft)   20 g/m (0.22 oz/ft)   20 g/m (0.22 oz/ft)   20 g/m (0.22 oz/ft)   Example: A 80 ft line set is used for tri - zone 5 additional ft X 0.22 ounces per foot= add 1.1   ounces of R410A   Important:   If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using   the charge amount specified on the unit's rating plate, adjusting for line sets longer or shorter than   7.5 m(25 ft) for each indoor unit.   26 Wall Mounted Multi-Zone Split System Air Conditioner   Test Running   Test Running   1. Check that all tubing and wiring have been properly connected.   2. Check that the gas and liquid side service valves are fully open.   Prepare remote control   Remove the battery cover by pulling it according   to the arrow direction.   Insert new batteries making sure that the (+) and   (–) of battery are installed correctly.   Reattach the cover by pushing it back into   position.   Bolt   NOTICE   : • Use 2 AAA(1.5volt) batteries. Do not use   rechargeable batteries.   • Remove the batteries from the remote control if   the system is not going to be used for a long   time.   Tubing connection   Evaluation of the performance   Operate all indoor units for 15~20 minutes, then   check the system refrigerant charge:   Intake temperature   1.Measure the pressure of one of the gas side   service valves.   Discharge air   2. Measure the temperature of the intake and   discharge of air.   3. Ensure the difference between the intake air   temperature and the discharge air is more   than 8°C(14.4°F).   4. For reference, optimum gas pressure for   cooling is shown below.   Discharge   temperature   Outside ambient   TEMP.   The pressure of the gas side   service valve.   Refrigerant   R410A   35°C (95°F) 8.5 ~ 9.5 kg/cm2G (120 ~ 135 P.S.I.G)   NOTICE   : If the actual pressure is higher than   shown, the system is most likely over-charged, and   charge should be removed. If the actual pressure is   lower than shown, the system is most likely   undercharged, and charge should be added.   Important:   ❏ Individual zones should be all in the same   operation mode (Heating or Cooling mode)   Installation Manual 27   Specifications and performance data subject to change without notice.   03-18-08   P/No. : MFL39059502   |