Heat Controller Inc Air Conditioner 10 User Manual

HEAT CONTROLLER  
INSTALLATION INSTRUCTIONS  
PACKAGE AIR CONDITIONERS FEATURING EARTH-FRIENDLY  
R410A REFRIGERANT  
e
a
r
t
h
f
r
i
e
n
d
l
y
r
e
f
r
i
g
e
r
a
n
t
PCG SERIES 6, 7.5, 8.5, 10 & 12.5 TON [21.1, 26.4, 29.9, 35.2 & 44 kW]  
60 HZ MODELS  
Recognize this symbol as an indication of Important Safety Information!  
!
DO NOT DESTROY  
PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE  
FOR FUTURE REFERENCE.  
WARNING  
!
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALI-  
FIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLA-  
TION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ  
THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING  
INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE  
INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION,  
ADJUSTMENT, SERVICE OR MAINTENANCE POSSIBLY RESULT-  
ING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PER-  
SONAL INJURY OR DEATH.  
[
] Designates Metric Conversions  
92-21916-45-00  
The units are weatherized for mounting outside of the building.  
• R-410A refrigerant cylinders are pink.  
The information on the rating plate is in compliance with the  
FTC and DOE rating for single phase units. The following infor-  
mation is for three phase units which are not covered under  
the DOE certification program.  
• R-410A, as with other HFC’s is only compatible with POE  
oils.  
• Vacuum pumps will not remove moisture from POE oil.  
• R-410A systems are to be charged with liquid refrigerants.  
Prior to March 1999, R-410A refrigerant cylinders had a dip  
tube. These cylinders should be kept upright for equipment  
charging. Post March 1999 cylinders do not have a dip tube  
and should be inverted to ensure liquid charging of the  
equipment.  
1. The efficiency rating of this unit is a product thermal effi-  
ciency rating determined under continuous operating condi-  
tions independent of any installed system.  
B. MAJOR COMPONENTS  
The unit includes a hermetically-sealed refrigerating system  
(consisting of a compressor, condenser coil, evaporator coil  
with thermal expansion valve), a circulation air blower, a con-  
denser fan, and all necessary internal electrical wiring. The  
cooling system of these units is factory-evacuated, charged  
and performance tested. Refrigerant amount and type are indi-  
cated on rating plate.  
• Do not install a suction line filter drier in the liquid line.  
• A liquid line filter drier is standard on every unit.  
• Desiccant (drying agent) must be compatible for POE oils  
and R-410A.  
3. Evaporator Coil / TXV  
C. R-410A REFRIGERANT  
The thermostatic expansion valve is specifically designed to  
operate with R-410A. DO NOT use an R-22 TXV. The exist-  
ing evaporator must be replaced with the factory specified  
TXV evaporator specifically designed for R-410A.  
All units are factory charged with R-410A refrigerant.  
1. Specification of R-410A:  
Application: R-410A is not a drop-in replacement for R-22;  
equipment designs must accommodate its higher pressures. It  
cannot be retrofitted into R-22 units.  
4. Tools Required For Installing & Servicing R-410A Models  
Manifold Sets:  
-Up to 800 PSIG High side  
-Up to 250 PSIG Low Side  
-550 PSIG Low Side Retard  
Pressure: The pressure of R-410A is approximately 60%  
(1.6 times) greater than R-22. Recovery and recycle equip-  
ment, pumps, hoses and the like need to have design pressure  
ratings appropriate for R-410A. Manifold sets need to range up  
to 800 psig high-side and 250 psig low-side with a 550 psig  
low-side retard. Hoses need to have a service pressure rating  
of 800 psig. Recovery cylinders need to have a 400 psig ser-  
vice pressure rating. DOT 4BA400 or DOT BW400.  
Manifold Hoses:  
-Service Pressure Rating of 800 PSIG  
Recovery Cylinders:  
-400 PSIG Pressure Rating  
-Dept. of Transportation 4BA400 or BW400  
Combustibility: At pressures above 1 atmosphere, mixture of  
R-410A and air can become combustible. R-410A and air  
should never be mixed in tanks or supply lines, or be  
allowed to accumulate in storage tanks. Leak checking  
should never be done with a mixture of R-410A and air.  
Leak checking can be performed safely with nitrogen or a mix-  
ture of R-410A and nitrogen.  
!
CAUTION  
R-410A systems operate at higher pressures than R-22 sys-  
tems. Do not use R-22 service equipment or components on R-  
410A equipment.  
2. Quick Reference Guide For R-410A  
• R-410A refrigerant operates at approximately 60% higher  
pressure (1.6 times) than R-22. Ensure that servicing equip-  
ment is designed to operate with R-410A.  
3
FIGURE 1  
UNIT DIMENSIONS  
40316”  
[1020.7 mm]  
658”  
[168.3 mm]  
418”  
POWER  
ENTRY  
[104.8 mm]  
134” [44.5 mm]  
DIA.  
31316”  
[96.8 mm]  
111116”  
[296.9 mm]  
61316”  
[173 mm]  
CONTROL  
ENTRY  
COMPRESSOR  
ACCESS  
78” [22.2 mm]  
DIA.  
931116”  
[2379.6 mm]  
5”  
[127 mm]  
SUPPLY COVER  
5834”  
[1492.2 mm]  
RETURN COVER  
ST-A1112-02-00  
FIGURE 2  
UNIT DIMENSIONS  
23”  
[584.2 mm]  
2”  
[50.8 mm]  
14”  
[355.6 mm]  
25”  
[635 mm]  
2”  
[50.8 mm]  
1518”  
[384.2 mm]  
34”  
[863.6 mm]  
891116”  
[2278 mm]  
4716”  
[112.7 mm]  
5434”  
[1390.6 mm]  
*ACTUAL OPENING  
DIMENSIONS  
2”  
[50.8 mm]  
10716”  
[265.1 mm]  
2”  
2”  
[
] Designates Metric Conversions  
ST-A1112-01-00  
[50.8 mm]  
[50.8 mm]  
4
FIGURE 3  
UNIT DIMENSIONS  
58.75”  
[1487.7 mm]  
93.688”  
[2379.7 mm]  
44”  
[1117.6 mm]  
GAUGE PORT  
CONNECTIONS  
COMPRESSOR  
ACCESS  
(BOTH SIDE SOME MODELS)  
BLOWER ACCESS  
ELECTRIC HEAT  
ACCESS  
CONTROL ENTRY  
POWER ENTRY  
CONDENSATE DRAIN  
1” [25.4 mm] FNPT  
7.020”  
[178.3 mm]  
27.268”  
[692.6 mm]  
CONTROL/FILTER  
ACCESS  
33.715”  
[805.5 mm]  
5.625”  
[142.9 mm]  
A0737-03  
FIGURE 4  
BOTTOM VIEW  
SUPPLY RETURN DIMENSIONS FOR DOWNFLOW APPLICATIONS  
9311/ ”  
16  
[2379.4 mm]  
16  
47/ ”  
8
151/ ”  
14"  
[355.6 mm]  
25"  
[635 mm]  
[112.7 mm]  
[384.1 mm]  
16  
107/ ”  
[265.1 mm]  
16  
47/ ”  
[112.7 mm]  
23"  
[585.5 mm]  
34"  
[863.6 mm]  
54"  
[1371.6 mm]  
4
583/ ”  
[1492.2 mm]  
8815/ ”  
[2259 mm]  
16  
8
21/ ”  
[54 mm]  
2
61/ ”  
[165.1 mm]  
21/ ”  
8
8
23/ ”  
[54 mm]  
[60.3 mm]  
2
271/ ”  
8"  
[203.2 mm]  
[698.5 mm]  
A0712-02  
THRU THE BASE ELECTRIC  
5
FIGURE 5  
REAR VIEW  
SUPPLY AND RETURN DIMENSIONS FOR HORIZONTAL APPLICATION  
SUPPLY DUCT MAY EXTEND UP TO THIS LEVEL  
44"  
[1117.6 mm]  
*26"  
[660.4 mm]  
34"  
[863.6 mm]  
12"  
[304.8 mm]  
32  
77/ ”  
[183.3 mm]  
8
135/ ”  
16  
47/ ”  
28"  
[711.2 mm]  
14"  
[355.6 mm]  
[346 mm]  
[112.7 mm]  
16  
9311/ ”  
[2379.6 mm]  
A0714-03  
*RECOMMENDED DUCT DIMENSIONS ARE 26”  
6
GENERAL DATA - PCG  
NOM. SIZES 6-1212 TONS [21.1-43.9 kW]  
Model PCG- Series  
072A-3L  
072A-4L  
085A-3L  
085A-4L  
CONTINUED  
1
Cooling Performance  
Gross Cooling Capacity Btu [kW]  
76,000 [22.27]  
11.5/NA  
76,000 [22.27]  
11.5/NA  
88,000 [25.78]  
11.2/NA  
88,000 [25.78]  
11.2/NA  
EER/SEER2  
Nominal CFM/ARI Rated CFM [L/s]  
ARI Net Cooling Capacity Btu [kW]  
Net Sensible Capacity Btu [kW]  
Net Latent Capacity Btu [kW]  
Integrated Part Load Value3  
Net System Power kW  
2400/2375 [1133/1121]  
73,000 [21.39]  
53,900 [15.79]  
19,100 [5.6]  
N/A  
2400/2375 [1133/1121]  
73,000 [21.39]  
53,900 [15.79]  
19,100 [5.6]  
N/A  
2800/3000 [1321/1416]  
85,000 [24.9]  
66,100 [19.37]  
18,900 [5.54]  
N/A  
2800/3000 [1321/1416]  
85,000 [24.9]  
66,100 [19.37]  
18,900 [5.54]  
N/A  
6.31  
6.31  
7.53  
7.53  
Compressor  
No./Type  
1/Scroll  
88  
1/Scroll  
88  
1/Scroll  
88  
1/Scroll  
88  
5
Outdoor Sound Rating (dB)  
Outdoor Coil—Fin Type  
Tube Type  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Tube Size in. [mm] OD  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
0.375 [9.5]  
13.5 [1.25]  
1 / 22 [9]  
0.375 [9.5]  
13.5 [1.25]  
1 / 22 [9]  
0.375 [9.5]  
27 [2.51]  
1 / 22 [9]  
0.375 [9.5]  
27 [2.51]  
1 / 22 [9]  
Indoor Coil—Fin Type  
Tube Type  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Tube Size in. [mm]  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
0.375 [9.5]  
13.5 [1.25]  
2 / 18 [7]  
Orifices  
0.375 [9.5]  
13.5 [1.25]  
2 / 18 [7]  
Orifices  
0.375 [9.5]  
13.5 [1.25]  
2 / 18 [7]  
Orifices  
0.375 [9.5]  
13.5 [1.25]  
2 / 18 [7]  
Orifices  
Refrigerant Control  
Drain Connection No./Size in. [mm]  
1/1 [25.4]  
1/1 [25.4]  
1/1 [25.4]  
1/1 [25.4]  
Outdoor Fan—Type  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
CFM [L/s]  
No. Motors/HP  
Motor RPM  
Propeller  
2/24 [609.6]  
Direct/1  
8000 [3775]  
2 at 1/3 HP  
1075  
Propeller  
2/24 [609.6]  
Direct/1  
8000 [3775]  
2 at 1/3 HP  
1075  
Propeller  
2/24 [609.6]  
Direct/1  
8000 [3775]  
2 at 1/3 HP  
1075  
Propeller  
2/24 [609.6]  
Direct/1  
8000 [3775]  
2 at 1/3 HP  
1075  
Indoor Fan—Type  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
No. Motors  
Motor HP  
Motor RPM  
FC Centrifugal  
1/11x12 [279x305]  
FC Centrifugal  
1/11x12 [279x305]  
FC Centrifugal  
1/15x15 [381x381]  
FC Centrifugal  
1/15x15 [381x381]  
Belt/Variable  
Belt/Variable  
Belt/Variable  
Belt/Variable  
1
1
1
2
1725  
56  
1
2
1725  
56  
1 1/2  
1725  
56  
1 1/2  
1725  
56  
Motor Frame Size  
Filter—Type  
Furnished  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
(No.) Size Recommended in. [mm x mm x mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]  
(6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]  
Refrigerant Charge Oz. [g]  
Weights  
120 [3402]  
120 [3402]  
190.9 [5412]  
190.9 [5412]  
Net Weights lbs. [kg]  
Ship Weights lbs. [kg]  
901 [409]  
938 [425]  
901 [409]  
938 [425]  
965 [438]  
1002 [455]  
965 [438]  
1002 [455]  
7
GENERAL DATA - PCG  
NOM. SIZES 6-1212 TONS [21.1-43.9 kW]  
Model PCG- Series  
090A-3L  
090A-4L  
102A-3L  
102A-4L  
CONTINUED  
1
Cooling Performance  
Gross Cooling Capacity Btu [kW]  
93,000 [27.25]  
11.2/NA  
93,000 [27.25]  
11.2/NA  
101,000 [29.59]  
11.2/NA  
101,000 [29.59]  
11.2/NA  
EER/SEER2  
Nominal CFM/ARI Rated CFM [L/s]  
ARI Net Cooling Capacity Btu [kW]  
Net Sensible Capacity Btu [kW]  
Net Latent Capacity Btu [kW]  
Integrated Part Load Value3  
Net System Power kW  
3000/2775 [1416/1310]  
90,000 [26.37]  
63,100 [18.49]  
26,900 [7.88]  
13  
3000/2775 [1416/1310]  
90,000 [26.37]  
63,100 [18.49]  
26,900 [7.88]  
13  
3200/3200 [1510/1510]  
97,000 [28.42]  
74,000 [21.68]  
23,000 [6.74]  
12.9  
3200/3200 [1510/1510]  
97,000 [28.42]  
74,000 [21.68]  
23,000 [6.74]  
12.9  
7.99  
7.99  
8.59  
8.59  
Compressor  
No./Type  
2/Scroll  
88  
2/Scroll  
88  
2/Scroll  
88  
2/Scroll  
88  
5
Outdoor Sound Rating (dB)  
Outdoor Coil—Fin Type  
Tube Type  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Tube Size in. [mm] OD  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
0.375 [9.5]  
27 [2.51]  
1 / 22 [9]  
0.375 [9.5]  
2.7 [0.25]  
1 / 22 [9]  
0.375 [9.5]  
27 [2.51]  
2 / 18 [7]  
0.375 [9.5]  
27 [2.51]  
2 / 18 [7]  
Indoor Coil—Fin Type  
Tube Type  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Tube Size in. [mm]  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
Refrigerant Control  
Drain Connection No./Size in. [mm]  
0.375 [9.5]  
13.5 [1.25]  
2 / 18 [7]  
TX Valves  
1/1 [25.4]  
0.375 [9.5]  
13.5 [1.25]  
2 / 18 [7]  
TX Valves  
1/1 [25.4]  
0.375 [9.5]  
13.5 [1.25]  
2 / 18 [7]  
TX Valves  
1/1 [25.4]  
0.375 [9.5]  
13.5 [1.25]  
2 / 18 [7]  
TX Valves  
1/1 [25.4]  
Outdoor Fan—Type  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
CFM [L/s]  
No. Motors/HP  
Motor RPM  
Propeller  
2/24 [609.6]  
Direct/1  
8000 [3775]  
2 at 1/3 HP  
1075  
Propeller  
2/24 [609.6]  
Direct/1  
8000 [3775]  
2 at 1/3 HP  
1075  
Propeller  
2/24 [609.6]  
Direct/1  
8000 [3775]  
2 at 1/3 HP  
1075  
Propeller  
2/24 [609.6]  
Direct/1  
8000 [3775]  
2 at 1/3 HP  
1075  
Indoor Fan—Type  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
No. Motors  
FC Centrifugal  
1/15x15 [381x381]  
FC Centrifugal  
1/15x15 [381x381]  
FC Centrifugal  
1/15x15 [381x381]  
FC Centrifugal  
1/15x15 [381x381]  
Belt/Variable  
Belt/Variable  
Belt/Variable  
Belt/Variable  
1
2
1
2
1
3
1
3
Motor HP  
Motor RPM  
Motor Frame Size  
1725  
56  
1725  
56  
1725  
56  
1725  
56  
Filter—Type  
Furnished  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
(No.) Size Recommended in. [mm x mm x mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]  
(6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]  
Refrigerant Charge Oz. [g]  
Weights  
107.5/110.7 [3048/3138]  
107.5/110.7 [3048/3138]  
154.4/166.6 [4377/4723]  
154.4/166.6 [4377/4723]  
Net Weights lbs. [kg]  
Ship Weights lbs. [kg]  
1017 [461]  
1054 [478]  
1017 [461]  
1054 [478]  
1067 [484]  
1104 [501]  
1067 [484]  
1104 [501]  
8
GENERAL DATA - PCG  
NOM. SIZES 6-1212 TONS [21.1-43.9 kW]  
Model PCG- Series  
120A-4L  
150A-3L  
150A-4L  
1
Cooling Performance  
Gross Cooling Capacity Btu [kW]  
123,000 [36.04]  
11.2/NA  
156,000 [45.71]  
11/NA  
156,000 [45.71]  
11/NA  
EER/SEER2  
Nominal CFM/ARI Rated CFM [L/s]  
ARI Net Cooling Capacity Btu [kW]  
Net Sensible Capacity Btu [kW]  
Net Latent Capacity Btu [kW]  
Integrated Part Load Value3  
Net System Power kW  
4000/3750 [1888/1770]  
118,000 [34.57]  
88,800 [26.02]  
29,200 [8.56]  
12.9  
5000/4400 [2360/2076]  
148,000 [43.36]  
107,600 [31.53]  
40,400 [11.84]  
11.9  
5000/4400 [2360/2076]  
148,000 [43.36]  
107,600 [31.53]  
40,400 [11.84]  
11.9  
10.49  
13.39  
13.39  
Compressor  
No./Type  
2/Scroll  
88  
2/Scroll  
88  
2/Scroll  
88  
5
Outdoor Sound Rating (dB)  
Outdoor Coil—Fin Type  
Tube Type  
Tube Size in. [mm] OD  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
Louvered  
Rifled  
0.375 [9.5]  
27 [2.51]  
2 / 22 [9]  
Louvered  
MicroChannel  
1 [25.4]  
27 [2.51]  
2 / 20 [8]  
Louvered  
MicroChannel  
1 [25.4]  
27 [2.51]  
2 / 20 [8]  
Indoor Coil—Fin Type  
Tube Type  
Louvered  
Rifled  
Louvered  
Rifled  
Louvered  
Rifled  
Tube Size in. [mm]  
Face Area sq. ft. [sq. m]  
Rows / FPI [FPcm]  
Refrigerant Control  
Drain Connection No./Size in. [mm]  
0.375 [9.5]  
13.5 [1.25]  
3 / 18 [7]  
TX Valves  
1/1 [25.4]  
0.375 [9.5]  
13.5 [1.25]  
4 / 15 [6]  
TX Valves  
1/1 [25.4]  
0.375 [9.5]  
13.5 [1.25]  
4 / 15 [6]  
TX Valves  
1/1 [25.4]  
Outdoor Fan—Type  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
CFM [L/s]  
No. Motors/HP  
Motor RPM  
Propeller  
2/24 [609.6]  
Direct/1  
8000 [3775]  
2 at 1/3 HP  
1075  
Propeller  
2/24 [609.6]  
Direct/1  
8000 [3775]  
2 at 1/2 HP  
1075  
Propeller  
2/24 [609.6]  
Direct/1  
8000 [3775]  
2 at 1/2 HP  
1075  
Indoor Fan—Type  
No. Used/Diameter in. [mm]  
Drive Type/No. Speeds  
No. Motors  
FC Centrifugal  
1/15x15 [381x381]  
FC Centrifugal  
1/15x15 [381x381]  
FC Centrifugal  
1/15x15 [381x381]  
Belt/Variable  
Belt/Variable  
Belt/Variable  
1
3
1
5
1
5
Motor HP  
Motor RPM  
Motor Frame Size  
1725  
56  
1725  
184  
1725  
184  
Filter—Type  
Furnished  
Disposable  
Yes  
Disposable  
Yes  
Disposable  
Yes  
(No.) Size Recommended in. [mm x mm x mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]  
(6)2x18x18 [51x457x457]  
159.2/156 [4513/4423]  
Refrigerant Charge Oz. [g]  
Weights  
172.8/180.8 [4899/5126]  
159.2/156 [4513/4423]  
Net Weights lbs. [kg]  
Ship Weights lbs. [kg]  
1120 [508]  
1157 [525]  
1238 [562]  
1275 [578]  
1238 [562]  
1275 [578]  
9
ELECTRICAL DATA - PCG  
ELECTRICAL DATA - PCG SERIES  
072A-3L  
187-253  
208/230  
37/37  
40/40  
50/50  
1
072A-4L  
414-506  
460  
18  
085A-3L  
187-253  
208/230  
42/42  
45/45  
60/60  
1
085A-4L  
414-506  
460  
21  
090A-3L  
187-253  
208/230  
43/43  
45/45  
50/50  
2
090A-4L  
414-506  
460  
21  
102A-3L  
187-253  
208/230  
54/54  
55/55  
60/60  
2
102A-4L  
414-506  
460  
26  
120A-3L  
187-253  
208/230  
54/54  
55/55  
60/60  
2
Unit Operating Voltage  
Range  
Volts  
Minimum Circuit  
Ampacity  
Minimum Overcurrent  
Protection Device Size  
20  
25  
25  
30  
Maximum Overcurrent  
Protection Device Size  
25  
30  
25  
30  
1
1
2
2
No.  
200/240  
3
480  
3
200/240  
3
480  
3
200/240  
3
480  
3
200/230  
3
460  
3
200/240  
3
Volts  
Phase  
RPM  
3450  
5
3450  
5
3450  
6
3450  
6
3450  
3 1/4  
13.1/13.1  
83.1/83.1  
3 1/4  
13.1/13.1  
83.1/83.1  
2
3450  
3 1/4  
6.1  
41  
3450  
3 3/4  
16/16  
91/91  
3 3/4  
16/16  
91/91  
2
3450  
3 3/4  
7.1  
46  
3450  
4 1/4  
16/16  
110/110  
4 1/4  
16/16  
110/110  
2
HP, Compressor 1  
Amps (RLA), Comp. 1  
Amps (LRA), Comp. 1  
HP, Compressor 2  
Amps (RLA), Comp. 2  
Amps (LRA), Comp. 2  
No.  
22.9/22.9  
155/155  
9.6  
75  
23.2/23.2  
164/164  
11.2  
75  
3 1/4  
6.1  
41  
3 3/4  
7.1  
46  
2
2
2
2
2
2
208/230  
1
460  
1
208/230  
1
460  
1
208/230  
1
460  
1
208/230  
1
460  
1
208/230  
1
Volts  
Phase  
1/3  
1/3  
0.7  
2.4  
1
1/3  
1/3  
0.7  
2.4  
1
1/3  
1/3  
0.7  
2.4  
1
1/3  
1/3  
0.7  
2.4  
1
1/3  
HP  
2.4/2.4  
4.7/4.7  
1
1.2/1.2  
4.7/4.7  
1
1.2/1.2  
4.7/4.7  
1
1.2/1.2  
4.7/4.7  
1
1.2/1.2  
4.7/4.7  
1
Amps (FLA, each)  
Amps (LRA, each)  
No.  
208/230  
3
460  
3
208/230  
3
460  
3
208/230  
3
460  
3
208/230  
3
460  
3
208/230  
3
Volts  
Phase  
1 1/2  
1 1/2  
1.9  
14.4  
2
2
2
2
3
3
3
HP  
5.6/5.62.8  
28.8/28.8  
8/8  
4
8/8  
4
13/13  
74.5/74.5  
7
13/13  
74.5/74.5  
Amps (FLA, each)  
Amps (LRA, each)  
56/56  
28  
56/56  
28  
38.1  
10  
ELECTRICAL DATA - PCG  
ELECTRICAL DATA - PCG SERIES  
120A-4L  
414-506  
460  
28  
150A-3L  
150A-4L  
414-506  
460  
36  
Unit Operating Voltage  
Range  
187-253  
208/230  
71/71  
75/75  
90/90  
2
Volts  
Minimum Circuit  
Ampacity  
Minimum Overcurrent  
Protection Device Size  
30  
40  
Maximum Overcurrent  
Protection Device Size  
35  
45  
2
2
No.  
Volts  
480  
3
208/230  
3
460  
3
Phase  
3450  
4 1/4  
9.8  
52  
3450  
3450  
5 3/4  
10.6  
75  
RPM  
5 3/4  
HP, Compressor 1  
Amps (RLA), Comp. 1  
Amps (LRA), Comp. 1  
HP, Compressor 2  
Amps (RLA), Comp. 2  
Amps (LRA), Comp. 2  
No.  
22.4/22.4  
149/149  
5 1/4  
4 1/4  
9.8  
52  
5 1/4  
9.7  
62  
19/19  
123/123  
2
2
2
460  
1
208-230  
1
460  
1
Volts  
Phase  
1/3  
0.7  
2.4  
1
1/2  
1/2  
0.75  
3.1  
1
HP  
1.15/1.15  
5.6/5.6  
1
Amps (FLA, each)  
Amps (LRA, each)  
No.  
460  
3
208/230  
3
460  
3
Volts  
Phase  
3
5
5
HP  
7
18.8/18.8  
82.6/82.6  
10  
Amps (FLA, each)  
Amps (LRA, each)  
38.1  
41.3  
11  
VI. INSTALLATION  
FIGURE 6  
OUTSIDE SLAB INSTALLATION, BASEMENT OR  
CRAWL SPACE DISTRIBUTION SYSTEM  
A. GENERAL  
1. PRE-INSTALLATION CHECK-POINTS  
Before attempting any installation, the following points  
should be carefully considered:  
Recommended  
Location  
Clearance  
a. Structural strength of supporting members.  
(rooftop installation)  
48” [1219.2 mm]  
18” [457.2 mm]  
18” [457.2 mm]  
18”* [457.2 mm]  
60” [1524 mm]  
A - Front  
B - Condenser Coil  
C - Duct Side  
D - Evaporator End  
E - Above  
b. Clearances and provision for servicing.  
c. Power supply and wiring.  
d. Air duct connections.  
*Without Economizer. 48” [1219.2 mm] With  
*Economizer  
e. Drain facilities and connections.  
f. Location for minimum noise.  
2. LOCATION  
These units are designed for outdoor installations. They  
can be mounted on a slab or rooftop. They are not to be  
installed within any part of a structure such as an attic,  
crawl space, closet, or any other place where condenser  
air flow is restricted or other than outdoor ambient condi-  
tions prevail. Since the application of the units is of the  
outdoor type, it is important to consult your local code  
authorities at the time the first installation is made.  
B. OUTSIDE SLAB INSTALLATION (Typical outdoor slab  
installations are shown in Figures 6 and 7.)  
1. Select a location where external water drainage cannot  
collect around the unit.  
2. Provide a level concrete slab extending 3" [76.2 mm]  
beyond all four sides of the unit. The slab should be suf-  
ficient above grade to prevent ground water from enter-  
ing the unit. IMPORTANT: To prevent transmission of  
noise or vibration, slab should not be connected to  
building structure.  
A0741-03  
3. The location of the unit should be such as to provide  
proper access for inspection and servicing.  
4. Locate unit where operating sounds will not disturb  
owner or neighbors.  
FIGURE 7  
OUTSIDE SLAB INSTALLATION, CLOSET DISTRIBUTION  
SYSTEM. SLAB FLOOR CONSTRUCTION  
5. Locate unit so roof runoff water does not pour directly on  
the unit. Provide gutter or other shielding at roof level.  
Do not locate unit in an area where excessive snow drift-  
ing may occur or accumulate.  
C. CLEARANCES  
The following minimum clearances must be observed for  
proper unit performance and serviceability.  
1. Provide 48" [1219.2 mm] minimum clearance at the front  
of the unit. Provide 18" [457.2 mm] minimum clearance  
at all other sides of the unit.  
2. Provide 60" [1524 mm] minimum clearance between top  
of unit and maximum 3 foot [.91 m] overhang.  
3. Unit is design certified for application on combustible  
flooring with 0" [0 mm] minimum clearance.  
4. See Figure 6 for illustration of minimum installation-ser-  
vice clearances.  
A0739-03  
12  
D. ROOFTOP INSTALLATION  
FIGURE 8  
1. Before locating the unit on the roof, make sure that the  
strength of the roof and beams is adequate at that point  
to support the weight involved. This is very important  
and user’s responsibility.  
RIGGING FOR LIFTING  
CORNER WEIGHTS BY PERCENTAGE  
A
B
C
D
2. For rigging and roofcurb details, see Figures 8 and 9.  
Use field-furnished spreaders.  
33%  
27%  
17%  
23%  
3. For roofcurb assembly, see Roofcurb Installation Instruc-  
tions.  
4. If the roofcurb is not used, provisions for disposing of  
condensate water runoff must be provided.  
5. The unit should be placed on a solid and level roofcurb  
or platform of adequate strength. See Figure 10.  
6. The location of the unit on the roof should be such as to  
provide proper access for inspection and servicing.  
IMPORTANT: If unit will not be put into service immediately,  
cover supply and return openings to prevent excessive con-  
densation.  
A
0
7
4
4
0
3
Illustration  
A074403  
A0744-03  
FIGURE 9  
ROOFCURB INSTALLATION  
INSTALL GASKET  
UNIT  
ROOFCURB  
NAILING STRIP  
A0719-02  
DUCT FLANGE NOT  
TO EXCEED 1" [25.4 mm]  
SUPPLY DUCT  
CAULK ALL JOINTS  
WATERTIGHT  
A0719-03  
RETURN DUCT  
13  
Balancing dampers should be provided for each branch duct in  
the supply system. Ductwork should be properly supported  
from the structure.  
FIGURE 10  
FLAT ROOFTOP INSTALLATION, ATTIC OR DROP CEILING  
DISTRIBUTION SYSTEM. MOUNTED ON ROOFCURB.  
CURB MUST BE LEVEL  
When installing ductwork, consider the following items:  
1. Noncombustible flexible connectors should be used  
between ductwork and unit to reduce noise and vibration  
transmission into the ductwork.  
2. When auxiliary heaters are installed, use noncombustible  
flexible connectors and clearance to combustible material  
of 0" [0 mm] for the first 3 feet [.91 m] of discharge duct.  
Clearance to unit top and side is 0" [0 mm].  
VIII. FILTERS  
This unit is provided with 6 - 2" x 18" x 18" [51mm x 457 mm x  
457 mm] disposable filters. When replacing filters, ensure they  
are inserted fully to the back to prevent bypass.  
VIX.CONVERSION PROCEDURE  
DOWNFLOW TO HORIZONTAL  
1. Remove the screws and covers from the outside of the  
supply and return sections.  
2. Install the covers over the bottom supply and return open-  
ings, painted side up inserting the leading flange under the  
bracket provided. Place the back flange to the top of the  
front bracket provided. See Figure 11.  
A1112-03  
VII. DUCTWORK  
3. Secure the return and supply cover to the front bracket with  
one (1) screw.  
Ductwork should be fabricated by the installing contractor in  
accordance with local codes and NFPA90A. Industry manuals  
may be used as a guide when sizing and designing the duct  
system - contact Air Conditioning Contractors of America, 1513  
16th St. N.W., Washington, D.C. 20036.  
FIGURE 11  
COVER GASKET DETAIL  
REAR PANEL  
WARNING  
!
DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT  
RETURN DUCTWORK TO ANY OTHER HEAT PRODUCING  
DEVICE SUCH AS A FIREPLACE INSERT, STOVE, ETC.  
UNAUTHORIZED USE OF SUCH DEVICES MAY RESULT IN  
FIRE, CARBON MONOXIDE POISONING, EXPLOSION,  
PROPERTY DAMAGE, SEVERE PERSONAL INJURY OR  
DEATH.  
INSULATION  
SUPPLY OR RETURN COVER  
BACK  
FRONT BRACKET  
BRACKET  
INSULATION  
BASE PAN  
The unit should be placed as close to the space to be air condi-  
tioned as possible allowing clearance dimensions as indicated.  
Ducts should be run as directly as possible to supply and  
return outlets. Use of non-flammable waterproof flexible con-  
nectors on both supply and return connections at the unit to  
reduce noise transmission is recommended.  
BASE RAIL  
NOTE: COVER SLIDES  
UNDER BACK  
BRACKET FLANGE.  
NOTE: COVER FITS ON  
TOP OF FRONT  
BRACKET FLANGE.  
It is preferable to install the unit on the roof of the structure if  
the registers or diffusers are located on the wall or in the ceil-  
ing. A slab installation could be considered when the registers  
are low on a wall or in the floor.  
A0725-01  
On ductwork exposed to outside air conditions of temperature  
and humidity, use a minimum of 2" [50.8 mm] of insulation and  
a vapor barrier. Distribution system in attic, furred space or  
crawl space should be insulated with at least 2" [50.8 mm] of  
insulation with vapor barrier. One-half to 1" [25.4 mm] thick-  
ness of insulation is usually sufficient for ductwork inside the air  
conditioned space.  
14  
X. CONDENSATE DRAIN  
FIGURE 13  
BRANCH CIRCUIT DISCONNECT LOCATION  
The condensate drain connection of the evaporator is  
1" [25.4 mm] nominal female pipe thread. IMPORTANT: Install  
a condensate trap to ensure proper condensate drainage. See  
Figure 12.  
FIGURE 12  
CONDENSATE DRAIN  
3”  
[76 mm]  
3”  
[76 mm]  
e. Re-install the power entry panel & run conduit and the  
proper size field wiring through the opening in the  
panel.  
XI. ELECTRICAL WIRING  
Field wiring must comply with the National Electrical Code (CEC  
in Canada) and local ordinances that may apply.  
f. Connect field wiring to the power terminal block located  
on the electric heater kit. Connect ground wire to the  
adjacent ground lug.  
A. POWER WIRING  
g. Connect heater kit control plug to the receptacle on the  
control wiring harness.  
1. This unit incorporates single-point electrical connections  
for the unit and electric heat accessory.  
h. Close heater access door and secure with screws pre-  
viously removed.  
2. It is important that proper electrical power is available to  
the unit. Voltage should not vary more than 10% from the  
values marked on the unit rating plate. Phase voltages  
must be balanced within 3%.  
B. CONTROL WIRING (Class II)  
1. Low voltage wiring should not be run in conduit with  
power wiring.  
3. Install a branch circuit disconnect within sight of the unit.  
Use the unit rating plate or RLNL-B Electrical Data to  
determine the required size.  
2. Control wiring is routed through the 7/8" [22 mm] hole in  
the unit side panel. See Figure 14. Use a minimum #18  
AWG thermostat wire. For wire lengths exceeding 50'  
[15.24 m] use #16 AWG thermostat wire. Connect the  
control wiring to the low voltage terminal block located on  
the unit integrated control. Route wires under the control  
voltage shield. See Figure 14.  
4. The branch circuit wire must be sized in accordance with  
the National Electrical Code (C.E.C. in Canada) and local  
ordinances that may apply using the minimum circuit  
ampacity found on the unit rating plate.  
5. Field-installed power wiring must be run through ground-  
ed rain-tight conduit attached to the unit power entry  
panel and connected as follows:  
3. It is necessary that only approved thermostats be used.  
Please contact your distributor for part number informa-  
tion. See thermostat specification catalog for recommend-  
ed thermostat.  
UNITS WITHOUT ELECTRIC HEAT - Connect power  
wiring to the power terminal block located on the left side  
of the electric heat compartment. Connect the ground  
wire to the adjacent ground lug.  
4. Figure 15 shows representative low voltage connection  
diagrams. Read your thermostat installation instructions  
for any special requirements for your specific thermostat.  
UNITS WITH FACTORY INSTALLED ELECTRIC HEAT -  
Connect power wiring to the power terminal block located  
on the electric heater kit. Connect the ground wire to the  
adjacent ground lug. DO NOT connect aluminum wiring  
directly to the electric heater terminal block. Wiring to the  
unit contactors is factory-connected.  
C. INTERNAL WIRING  
1. A diagram of the internal wiring of this unit is located on  
the inside of the control access panel and in this manual.  
If any of the original wiring must be replaced, the wire  
gauge and insulation must be the same as original wiring.  
6. For field installation of an electric heater kit, follow the  
instructions below. Refer to the information supplied with  
the kit.  
Transformer is factory-wired for 220 volts on 200/220 volt  
models and must be changed for 200-volt applications.  
See unit wiring diagram for 200-volt wiring.  
a. Removing screws as required, open heater access  
door and detach adjacent power entry panel.  
D. GROUNDING  
b. Remove wires to unit contactor (1L1, 1L2, 1L3) from  
unit terminal block on the left side of the electric heat  
compartment. Remove and discard the terminal block  
and the adjacent ground lug.  
WARNING  
!
THE UNIT MUST BE PERMANENTLY GROUNDED. A  
GROUNDING LUG IS PROVIDED IN THE ELECTRIC  
HEAT ACCESS AREA FOR A GROUND WIRE. FAILURE  
TO GROUND THIS UNIT CAN RESULT IN FIRE OR  
ELECTRICAL SHOCK CAUSING PROPERTY DAMAGE,  
SEVERE PERSONAL INJURY OR DEATH.  
c. Remove the heater kit block-off panel and install the  
heater kit in its place using 9 of the 12 screws previ-  
ously removed.  
d. Connect the unit contactor wires (1L1, 1L2, 1L3) to the  
compressor fuse block on the heater kit.  
15  
FIGURE 14  
GROUNDING MAY ALSO BE ACCOMPLISHED BY  
GROUNDING THE POWER LINE CONDUIT TO THE  
UNIT. MAKE SURE THE CONDUIT NUT LOCKING TEETH  
HAVE PIERCED THE INSULATING PAINT FILM OF THE  
SIDE PANEL.  
XIII. CRANKCASE HEAT (OPTIONAL)  
Crankcase heaters are standard on 6 ton and single stage 712.  
Crankcase heat is not required on other models, but may be  
desirable under certain conditions.  
E. THERMOSTAT  
The thermostat should be mounted on an inside wall about  
five feet above the floor in a location where it will not be  
affected by unconditioned air, sun, or drafts from open doors  
or other sources. READ installation instructions in air condi-  
tioner thermostat package CAREFULLY because each has  
some different wiring requirements.  
XIV. PRE-START CHECK  
1. Is unit properly located and slightly slanted toward indoor  
condensate drain?  
2. Is ductwork insulated, weatherproofed, with proper spacing  
to combustible materials?  
3. Is air free to travel to and from outdoor coil? (See Figure 4.)  
4. Is the wiring correct, tight, and according to unit wiring dia-  
gram?  
XII. INDOOR AIR FLOW DATA  
Belt-drive blower models have motor sheaves set for proper  
CFM at a typical external static. See Tables C through G for  
blower performance.  
5. Is unit grounded?  
6. Are field supplied air filters in place and clean?  
7. Do the outdoor fan and indoor blower turn freely without  
rubbing, and are they tight on the motor shafts?  
16  
FIGURE 15  
THERMOSTAT  
CONNECTIONS  
DIAGRAM  
A0823-01  
8. Turn thermostat system switch to “HEAT.” Unit compres-  
sors should stop. Raise temperature setting to above room  
temperature. Unit should run in heating mode and auxiliary  
heaters, if installed, should come on.  
9. Check the refrigerant charge using the instructions located  
on unit charging chart. Replace service port caps. Service  
port cores are for system access only and will leak if not  
tightly capped.  
10. Adjust discharge air grilles and balance system.  
11. Check ducts for condensation and air leaks.  
12. Check unit for tubing and sheet metal rattles.  
13. Instruct the owner on operation and maintenance.  
14. Leave “INSTALLATION” and ”USE AND CARE“ instruc-  
tions with owner  
XV. STARTUP  
1. Turn thermostat to “OFF,” turn “on” power supply at discon-  
nect switch.  
2. Turn temperature setting as high as it will go.  
3. Turn fan switch to “ON.”  
4. Indoor blower should run. Be sure it is running in the right  
direction.  
5. Turn fan switch to “AUTO.” Turn system switch to “COOL”  
and turn temperature setting below room temperature. Unit  
should run in cooling mode.  
6. Is outdoor fan operating correctly in the right direction?  
7. Is compressor running correctly.  
Record the following after the unit has run some time.  
A. Operating Mode _______________________________  
B. Discharge Pressures (High) _____________PSIG [kPa]  
C. Vapor Pressure at Compressors (Low) _____PSIG [kPa]  
D. Vapor Line Temperature at Compressors ______°F [C°].  
E. Indoor Dry Bulb __________________________°F [C°].  
F. Indoor Wet Bulb__________________________°F [C°].  
G.Outdoor Dry Bulb_________________________°F [C°].  
H. Outdoor Wet Bulb ________________________°F [C°].  
I. Voltage at Contactor ________________________Volts  
J. Current at Contactors ______________________ Amps  
K. Model Number_________________________________  
L. Serial Number _________________________________  
M.Location______________________________________  
N. Owner _______________________________________  
O.Date_________________________________________  
17  
XVI. OPERATION  
XVII. MISCELLANEOUS  
REPLACEMENT PARTS  
COOLING MODE  
Contact your local distributor for a complete parts list.  
.
With thermostat in the cool mode, fan auto and the room tem-  
perature higher than the thermostat setting:  
A. Indoor blower contactor is energized through thermostat  
contact (G).  
B. Compressor contactors are energized through thermostat  
contacts (Y1) & (Y2) and high pressure controls.  
C. Economizer enthalpy control (if installed) controls operation  
of first-stage cooling and positions fresh air damper to main-  
tain mixed air temperature. Second-stage cooling operates  
normally as required by second stage of thermostats.  
D. The system will continue in cooling operation as long as all  
safety controls are closed, until the thermostat is satisfied.  
HEATING MODE  
With the thermostat in heat mode, fan on auto, and the room  
temperature lower than the thermostat setting, the Indoor  
blower contactor is energized through thermostat contact (G).  
WARNING  
!
ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MAN-  
UFACTURER AS DESCRIBED IN THIS PUBLICATION HAVE  
BEEN DESIGNED, TESTED, AND EVALUATED FOR USE  
WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED  
ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY  
CAUSE HAZARDOUS CONDITIONS RESULTING IN PROP-  
ERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.  
In the heating mode, the thermostat will energize one or more  
supplementary heaters.  
18  
19  
20  
21  
22  
23  
XIX. HEATER KIT CHARACTERISTICS  
TABLE A  
AUXILIARY HEATER KITS CHARACTERISTICS AND APPLICATION (PCG MODELS)  
208/240V – 3 PHASE  
MAX. FUSE OR  
CKT. BKR. SIZE  
(CKT. BKR. MUST  
BE HACR TYPE  
FOR USA)  
UNIT MODEL  
NUMBER  
PCG-  
HEATER KIT  
MODEL NO.  
RXJJ-  
HEATER kW  
@ 208/240 V/  
3 PHASE  
UNIT MIN. CKT.  
AMPACITY  
HEATER KIT FLA  
072A-3L  
NONE  
CC10C  
CC15C  
CC20C  
CC30C  
7.2/9.6  
10.8/14.4  
14.4/19.2  
21.6/28.8  
37/37  
37/37  
45/51  
57/65  
82/94  
50/50  
50/50  
50/60  
60/70  
90/100  
20.0/23.1  
30.0/34.6  
40.0/46.2  
60.0/69.3  
085A-4L  
NONE  
CC10C  
CC15C  
CC20C  
CC30C  
CC40C  
7.2/9.6  
10.8/14.4  
14.4/19.2  
21.6/28.8  
28.8/38.4  
42/42  
42/42  
48/54  
60/68  
85/97  
60/60  
60/60  
60/60  
60/70  
90/100  
125/150  
20.0/23.1  
30.0/34.6  
40.0/46.2  
60.0/69.3  
80.1/92.4  
111/126  
090A-4L  
102A-4L  
NONE  
CC10C  
CC15C  
CC20C  
CC30C  
CC40C  
7.2/9.6  
10.8/14.4  
14.4/19.2  
21.6/28.8  
28.8/38.4  
43/43  
43/43  
48/54  
60/68  
85/97  
50/50  
50/50  
50/60  
60/70  
90/100  
125/150  
20.0/23.1  
30.0/34.6  
40.0/46.2  
60.0/69.3  
80.1/92.4  
111/126  
NONE  
CC10C  
CC15C  
CC20C  
CC30C  
CC40C  
7.2/9.6  
10.8/14.4  
14.4/19.2  
21.6/28.8  
28.8/38.4  
54/54  
54/54  
54/60  
67/74  
92/103  
117/132  
60/60  
60/60  
60/60  
70/80  
100/110  
125/150  
20.0/23.1  
30.0/34.6  
40.0/46.2  
60.0/69.3  
80.1/92.4  
24  
HEATER KIT CHARACTERISTICS (continued)  
TABLE B  
AUXILIARY HEATER KITS CHARACTERISTICS AND APPLICATION (PCG MODELS)  
208/240V – 3 PHASE  
MAX. FUSE OR  
CKT. BKR. SIZE  
(CKT. BKR. MUST  
BE HACR TYPE  
FOR USA)  
UNIT MODEL  
NUMBER  
PCG-  
HEATER KIT  
MODEL NO.  
RXJJ-  
HEATER kW  
@ 208/240 V  
UNIT MIN. CKT.  
AMPACITY  
HEATER KIT FLA  
120A-4L  
NONE  
CC10C  
CC15C  
CC20C  
CC30C  
CC40C  
CC50C  
7.2/9.6  
54/54  
54/54  
54/60  
60/60  
60/60  
60/60  
20.0/23.1  
30.0/34.6  
40.0/46.2  
60.0/69.3  
80.1/92.4  
100.1/115.5  
10.8/14.4  
14.4/19.2  
21.6/28.8  
28.8/38.4  
36.1/48.0  
67/74  
70/80  
92/103  
117/132  
142/161  
100/110  
125/150  
150/175  
150A-4L  
NONE  
CC10C  
CC15C  
CC20C  
CC30C  
CC40C  
CC50C  
7.2/9.6  
71/71  
71/71  
71/71  
90/90  
90/90  
90/90  
20.0/23.1  
30.0/34.6  
40.0/46.2  
60.0/69.3  
80.1/92.4  
100.1/115.5  
10.8/14.4  
14.4/19.2  
21.6/28.8  
28.8/38.4  
36.1/48.0  
74/82  
90/90  
99/111  
124/139  
149/168  
100/125  
125/150  
150/175  
072A-4L  
085A-4L  
NONE  
CC10D  
CC15D  
CC20D  
CC30D  
9.6  
14.4  
19.2  
28.8  
18  
18  
26  
33  
47  
25  
25  
30  
35  
50  
11.5  
17.3  
23.1  
34.6  
NONE  
CC10D  
CC15D  
CC20D  
CC30D  
CC40D  
9.6  
14.4  
19.2  
28.8  
38.4  
21  
21  
27  
34  
49  
63  
30  
30  
30  
35  
50  
70  
11.5  
17.3  
23.1  
34.6  
46.2  
25  
HEATER KIT CHARACTERISTICS (continued)  
TABLE C  
AUXILIARY HEATER KITS CHARACTERISTICS AND APPLICATION (PCG MODELS)  
480V – 3 PHASE  
MAX. FUSE OR  
CKT. BKR. SIZE  
(CKT. BKR. MUST  
BE HACR TYPE  
FOR USA)  
UNIT MODEL  
NUMBER  
PCG-  
HEATER KIT  
MODEL NO.  
RXJJ-  
HEATER kW  
@ 480 V  
UNIT MIN. CKT.  
AMPACITY  
HEATER KIT FLA  
090A-4L  
102A-4L  
120A-4L  
NONE  
CC10D  
CC15D  
CC20D  
CC30D  
CC40D  
9.6  
14.4  
19.2  
28.8  
38.4  
21  
21  
27  
34  
49  
63  
25  
25  
30  
35  
50  
70  
11.5  
17.3  
23.1  
34.6  
46.2  
NONE  
CC10C  
CC15D  
CC20D  
CC30D  
CC40D  
9.6  
14.4  
19.2  
28.8  
38.4  
26  
6
31  
38  
52  
67  
30  
30  
35  
40  
60  
70  
11.5  
17.3  
23.1  
34.6  
46.2  
NONE  
CC10D  
CC15D  
CC20D  
CC30D  
CC40D  
CC50D  
9.6  
28  
28  
31  
38  
52  
67  
81  
35  
35  
35  
40  
60  
70  
90  
11.5  
17.3  
23.1  
34.6  
46.2  
57.7  
14.4  
19.2  
28.8  
38.4  
48.0  
150A-4L  
NONE  
CC10D  
CC15D  
CC20D  
CC30D  
CC40D  
CC50D  
9.6  
36  
36  
36  
42  
56  
71  
85  
45  
45  
45  
45  
60  
80  
90  
11.5  
17.3  
23.1  
34.6  
46.2  
57.7  
14.4  
19.2  
28.8  
38.4  
48.0  
26  
XX. TROUBLE SHOOTING CHART  
WARNING  
!
DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAILURE  
TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.  
SYMPTOM  
POSSIBLE CAUSE  
REMEDY  
Unit will not run  
Power off or loose electrical connection  
Check for correct voltage at compressor contactor in control  
box  
Thermostat out of calibration-set too high  
Defective contactor  
Reset  
Check for 24 volts at contactor coil - replace if contacts are  
open  
Blown fuses  
Transformer defective  
High pressure control open (if provided)  
Interconnecting low voltage wiring damaged  
Replace fuses  
Check wiring-replace transformer  
Reset-also see high head pressure remedy-  
Replace thermostat wiring  
Condenser fan runs, compressor  
doesn’t  
Run capacitor defective (single phase only)  
Loose connection  
Replace  
Check for correct voltage at compressor -  
check & tighten all connections  
Compressor stuck, grounded or open motor winding  
open internal overload.  
Low voltage condition  
Wait at least 2 hours for overload to reset.  
If still open, replace the compressor.  
At compressor terminals, voltage must be within 10% of rating  
plate volts when unit is operating.  
Insufficient cooling  
Improperly sized unit  
Improper airflow  
Incorrect refrigerant charge  
Air, non-condensibles or moisture in system  
Incorrect voltage  
Recalculate load  
Check - should be approximately 400 CFM [188.78 L/s] per ton.  
Charge per procedure attached to unit service panel.  
Recover refrigerant, evacuate & recharge, add filter drier  
At compressor terminals, voltage must be within 10% of rating  
plate volts when unit is operating.  
Compressor short cycles  
Incorrect voltage  
At compressor terminals, voltage must be 10% of  
nameplate marking when unit is operating.  
Replace - check for correct voltage  
Add refrigerant  
Defective overload protector  
Refrigerant undercharge  
Registers sweat  
Low evaporator airflow  
Increase speed of blower or reduce restriction - replace air  
filter  
High head-low vapor pressures  
Restriction in liquid line, expansion device or filter drier  
Flow check piston size too small  
Incorrect capillary tubes  
Remove or replace defective component  
Change to correct size piston  
Change coil assembly  
TXV does not open  
Replace TXV  
High head-high or normal vapor  
pressure - Cooling mode  
Dirty condenser coil  
Refrigerant overcharge  
Condenser fan not running  
Air or non-condensibles in system  
Clean coil  
Correct system charge  
Repair or replace  
Recover refrigerant, evacuate & recharge  
High head-high or normal vapor  
pressure - Heating mode  
Low air flow - condenser coil  
Refrigerant overcharge  
Air or non-condensibles in system  
Dirty condenser coil  
Check filters - correct to speed  
Correct system charge  
Recover refrigerant, evacuate & recharge  
Check filter - clean coil  
Low head-high vapor pressures  
Defective Compressor valves  
Low evaporator airflow  
Replace compressor  
Low vapor - cool compressor -  
iced evaporator coil  
Increase speed of blower or reduce restriction - replace air  
filter  
Operating below 65°F outdoors  
Moisture in system  
TXV limiting refrigerant flow  
Add Low Ambient Kit  
Recover refrigerant - evacuate & recharge - add filter drier  
Replace TXV  
High vapor pressure  
Excessive load  
Defective compressor  
Recheck load calculation  
Replace  
Fluctuating head & vapor  
pressures  
TXV hunting  
Check TXV bulb clamp - check air distribution on coil - replace  
TXV  
Recover refrigerant, evacuate & recharge  
Air or non-condensibles in system  
Air or non-condensibles in system  
Gurgle or pulsing noise at  
Recover refrigerant, evacuate & recharge  
expansion device or liquid line  
27  
XXI. WIRING DIAGRAMS  
WIRING DIAGRAM  
072/085  
208-230/460/575V 3 PH, 60 HZ.  
ROOFTOP  
28  
WIRING SCHEMATIC  
072/085  
PACKAGED A/C  
208-230, 3PH, 60HZ./460, 3PH, 60HZ.  
575V, 3PH, 60HZ.  
29  
WIRING DIAGRAM  
090/102/120/150  
208-230/460/575V 3 PH, 60 HZ.  
ROOFTOP  
30  
WIRING SCHEMATIC  
090/102/120/150  
PACKAGED A/C  
208-230, 3PH, 60HZ./460, 3PH, 60HZ.  
575V, 3PH, 60HZ.  
31  
XXII. CHARGING CHARTS  
PCG SYSTEM CHARGE CHARTS  
FIGURE 16  
SYSTEM CHARGE CHART - REFRIGERANT 410A  
-072, CIRCUIT 1  
525  
500  
475  
450  
425  
400  
375  
350  
325  
300  
275  
250  
225  
200  
175  
115  
105  
95  
85  
75  
65  
55  
160  
165  
100  
105  
110  
115  
120  
125  
130  
135  
140  
145  
150  
155  
92-102259-06-00  
32  
PCG SYSTEM CHARGE CHARTS  
FIGURE 17  
SYSTEM CHARGE CHART - REFRIGERANT 410A  
-085, CIRCUIT 1  
525  
500  
475  
450  
425  
400  
375  
350  
325  
300  
275  
250  
225  
200  
175  
115  
105  
95  
85  
75  
65  
55  
160  
165  
100  
105  
110  
115  
120  
125  
130  
135  
140  
145  
150  
155  
92-102259-07-00  
33  
PCG SYSTEM CHARGE CHARTS  
FIGURE 18  
SYSTEM CHARGE CHART - REFRIGERANT 410A  
-090, CIRCUITS 1 & 2  
BOTH COMPRESSORS MUST BE OPERATING BEFORE CHECKING  
REFRIGERANT CHARGE.  
RETURN AIR TEMPERATURE MUST BE WITHIN COMFORT CONDITIONS  
BEFORE FINAL REFRIGERANT CHECK!  
525  
500  
475  
450  
425  
400  
375  
350  
325  
300  
275  
250  
225  
200  
175  
115  
105  
95  
85  
75  
65  
55  
160 165  
100 105 110 115 120 125 130 135 140 145 150 155  
-B090, CIRCUIT 1  
525  
500  
475  
450  
425  
400  
375  
350  
325  
300  
275  
250  
225  
200  
175  
115  
105  
95  
85  
75  
65  
55  
160 165  
100 105 110 115 120 125 130 135 140 145 150 155  
-B090, CIRCUIT 2  
92-102259-08-00  
34  
PCG SYSTEM CHARGE CHARTS  
FIGURE 19  
SYSTEM CHARGE CHART - REFRIGERANT 410A  
-102, CIRCUITS 1 & 2  
BOTH COMPRESSORS MUST BE OPERATING BEFORE CHECKING  
REFRIGERANT CHARGE.  
RETURN AIR TEMPERATURE MUST BE WITHIN COMFORT CONDITIONS  
BEFORE FINAL REFRIGERANT CHECK!  
525  
500  
475  
450  
425  
400  
375  
350  
325  
300  
275  
250  
225  
200  
175  
115  
105  
95  
85  
75  
65  
55  
160 165  
100 105 110 115 120 125 130 135 140 145 150 155  
-B102, CIRCUIT 1  
525  
500  
475  
450  
425  
400  
375  
350  
325  
300  
275  
250  
225  
200  
175  
115  
105  
95  
85  
75  
65  
55  
160 165  
100 105 110 115 120 125 130 135 140 145 150 155  
-B102, CIRCUIT 2  
92-102259-09-00  
35  
PCG SYSTEM CHARGE CHARTS  
FIGURE 20  
SYSTEM CHARGE CHART - REFRIGERANT 410A  
-120, CIRCUITS 1 & 2  
BOTH COMPRESSORS MUST BE OPERATING BEFORE CHECKING  
REFRIGERANT CHARGE.  
RETURN AIR TEMPERATURE MUST BE WITHIN COMFORT CONDITIONS  
BEFORE FINAL REFRIGERANT CHECK!  
525  
500  
475  
450  
425  
400  
375  
350  
325  
300  
275  
250  
225  
200  
175  
115  
105  
95  
85  
75  
65  
55  
160 165  
100 105 110 115 120 125 130 135 140 145 150 155  
-B120, CIRCUIT 1  
525  
500  
475  
450  
425  
400  
375  
350  
325  
300  
275  
250  
225  
200  
175  
115  
105  
95  
85  
75  
65  
55  
160 165  
100 105 110 115 120 125 130 135 140 145 150 155  
92-102259-10-00  
-B120, CIRCUIT 2  
36  
PCG SYSTEM CHARGE CHARTS  
FIGURE 21  
SYSTEM CHARGE CHART - REFRIGERANT 410A  
-150, CIRCUITS 1 & 2  
BOTH COMPRESSORS MUST BE OPERATING BEFORE CHECKING  
REFRIGERANT CHARGE.  
RETURN AIR TEMPERATURE MUST BE WITHIN COMFORT CONDITIONS  
BEFORE FINAL REFRIGERANT CHECK!  
525  
500  
475  
450  
425  
400  
375  
350  
325  
300  
275  
250  
225  
200  
175  
115  
105  
95  
85  
75  
65  
55  
160 165  
100 105 110 115 120 125 130 135 140 145 150 155  
-B150, CIRCUIT 1  
525  
500  
475  
450  
425  
400  
375  
350  
325  
300  
275  
250  
225  
200  
175  
115  
105  
95  
85  
75  
65  
55  
160 165  
100 105 110 115 120 125 130 135 140 145 150 155  
92-102259-11-00  
-B150, CIRCUIT 2  
37  
38  
39  
40  
CM 1108  

Aiphone LAF C CONSOLE MASTER LAF 40C User Manual
Black Decker Univolt 98014 User Manual
Black Decker VP110 User Manual
Canon MultiPASS MP730 User Manual 2
Friedrich PH12R__B User Manual
Friedrich WS14B10A User Manual
GE ASQ28DL User Manual
Graco Baby Accessories PD162498A User Manual
Honeywell W7459A User Manual
HP Hewlett Packard Officejet 6500 User Manual