Haier HSU 12LEK13 User Manual

Installation Manual of Room Air Conditioner  
Read this manual before installation  
Explain sufficiently the operating means to the user  
according to this manual.  
Necessary Tools for Installation  
1.Driver  
5.Torque wrench(17mm,22mm,26mm)  
9.Nipper  
12.Reamer  
2.Hacksaw  
3.Hole core drill  
4.Spanner(17,19 and 26mm)  
6.Pipe cutter  
7.Flaring tool  
8.Knife  
10.Gas leakage detector or  
soap-and-water solution  
11.Measuring tape  
Drawing for the installation of indoor and outdoor units  
Accessory parts  
Number  
of  
No. Accessory parts  
articles  
Remote controller  
1
1
2
1
Optional parts for piping  
Mark  
Parts name  
2
R-03 dry battery  
A
Non-adhesive tape  
Adhesive tape  
B
C
D
3
Saddle(L.S) with screws  
Mounting plate  
Connecting electric cable  
for indoor and outdoor  
Drain hose  
1
E
F
4
Drain hose  
Heating insulating material  
Piping hole cover  
4X50  
Steel nail, cement  
G
5
6
4
Attention must be paid to  
the rising up of drain hose  
A
6
4X25  
Screw  
Plastic cap  
1
1
7
8
Drain-elbow  
Cover  
Arrangement of piping directions  
Rear left  
C
Rear  
right  
Left  
Cushion  
4
1
9
Right  
Below  
10  
11  
Pipe supporting plate  
Connecting cable  
1
D
Note:Cooling only units don't have Drain-elbow  
E
A
G
The marks from to in the figure are the parts numbers.  
The distance between the indoor unit and the floor should be  
more than 2m.  
No.0010518787  
500  
140  
113.5  
113.5  
140  
583  
140  
415  
140  
Floor fixing dimensions  
of the outdoor unit  
(Unit:mm)  
Floor fixing dimensions  
of the outdoor unit  
(Unit:mm)  
Floor fixing dimensions  
of the outdoor unit  
(Unit:mm)  
HSU-24LEK13  
HSU-18LEK03/(DB)  
HSU-09LEK03/(DB)  
HSU-12LEK03/(DB)  
HSU-18LEK13  
HSU-108CH09  
HSU-138CH09  
HSU-12LEK13-M  
HSU-09LEK13  
HSU-12LEK13  
HSU-07LEK03  
HSU-07HEK03  
HSU-09LEK03  
HSU-12LEK03  
HSU-09HEK03  
HSU-12HEK03  
HSU-18HEK03  
HSU-24HEK03  
Selection of pipe  
For 07 09 108  
For 12 18 138  
6.35mm(1/4")  
12.7mm(1/2")  
For 24  
To this unit, both liquid and gas pipes shall be insulated  
as they become Iow temperature in operation.  
Use optional parts for piping set or pipes covered with  
equivalent insulation material.  
9.52mm(3/8")  
15.88mm(5/8")  
Liquid pipe (  
Gas pipe  
)
6.35mm(1/4")  
9.52mm(3/8")  
(
)
Indoor unit  
1.Fitting of the Mounting Plate and Positioning of the wall Hole  
When the mounting plate is first fixed  
1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be  
fixed against the wall, then temporarily fasten the plate with one steel nail.  
2. Make sure once more the proper level of the plate, by hanging a thread with a weight from  
the central top of the plate, then fasten securely the plate with the attachment steel nail.  
3. Find the wall hole location A using a measuring tape  
B= 60mm  
B= 60mm  
HSU-24HEK03  
HSU-24LEK13  
A=145mm  
B= 60mm  
HSU-12LEK13-M  
HSU-09LEK13  
HSU-12LEK13  
HSU-07LEK03  
HSU-07HEK03  
A=145mm  
HSU-09LEK03  
HSU-12LEK03  
HSU-09HEK03  
HSU-12HEK03  
HSU-108CH09  
HSU-138CH09  
HSU-18HEK03  
HSU-18LEK13  
HSU-18LEK03/(DB)  
HSU-09LEK03/(DB)  
HSU-12LEK03/(DB)  
A=145mm  
2.Making a Hole on the Wall and Fitting the Piping Hole Cover  
Indoor side  
Wall hole  
60mm  
Outdoor side  
Make a hole of 60 mm in diameter,  
slightly descending to outside the wall.  
Install piping hole cover and seal it  
off with putty after installation  
Thickness  
of wall  
G
Piping hole pipe  
(Section of wall hole)  
2
Indoor unit  
Connecting the indoor/outdoor Electric Cable  
Removing the wiring cover  
Remove terminal cover at right bottom corner of indoor unit, then  
take off wiring cover by removing its screws.  
When connecting the cable after installing the indoor unit  
1. Insert from outside the room cable into left side of the wall hole, in which  
the pipe has already existed.  
2. Pull out the cable on the front side, and connect the cable making a loop.  
When connecting the cable before installing the indoor unit  
Insert the cable from the back side of the unit, then pull it out on the front side.  
Loosen the screws and insert the cable ends fully into terminal block, then tighten the screws.  
Pull the cable slightly to make sure the cables have been properly inserted and tightened.  
After the cable connection, never fail to fasten the connected cable with the wiring cover.  
Note: When connecting the cable, confirm the terminal number of indoor and outdoor units carefully. If wi  
is not correct, proper operation can not be carried out and will cause defect.  
ring  
1. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar  
qualified person. The type of connecting wire is H05/07RN-F or 245IEC57(YZW).  
2. If the fuse on PC board is broken please change it with the type of T. 3.15A/250V.  
If the fuse of outdoor unit on PC board is broken, please change it with the type of T. 25A/250V.  
3. The wiring method should be in line with the local wiring standard.  
4. After installation, the power plug should be easily reached.  
5. A breaker should be incorporated into fixed wiring. The breaker should be all-pole switch and the  
distance between its two contacts should be not less than 3mm.  
Power cable:  
3G1.0mm  
Power cable:  
5G1.0mm  
3G1.0mm  
3G1.0mm  
Indoor unit  
HSU-12HE K03  
Outdoor unit  
HSU-07HE K03  
Indoor unit  
Indoor unit  
Outdoor unit  
Outdoor unit  
HSU-09HE K03  
HSU-18HEK03  
HSU-12LEK13-M  
HSU-108CH09  
HSU-138CH09  
HSU-09LEK03  
HSU-12LEK03  
/
(DB)  
/(DB)  
Power cable:  
3G1.5mm  
connecting wiring:  
3G1.5mm +1X0.75mm  
Power cable:  
3G2.5mm  
3G2.0mm  
Power cable:  
3G1.0mm  
4G0.75mm  
HSU-18LEK13  
Indoor unit  
Outdoor unit  
Indoor unit  
HSU-24LEK13  
Power cable:  
3G1.5mm  
Power cable:  
3G2.5mm  
Outdoor unit  
4G0.75mm2  
6G0.75mm  
Indoor unit  
Indoor unit  
Indoor unit  
Outdoor unit  
POWER  
HSU-24HEK03  
Outdoor unit  
HSU-09LEK13  
{
HSU-09LEK03  
HSU-12LEK03  
HSU-12LEK13  
HSU-07LEK03  
connecting wiring:  
HSU-18LEK03/(DB)  
BR  
BL  
POWER  
SUPPLY  
Outdoor unit  
Y/G  
-mod 07-12: 3G1.0mm  
Power cable:  
-mod 07-12: 3G1.0mm  
3
Outdoor unit  
Outdoor unit  
1.Connection of pipes  
To bend a pipe, give the roundness as large as possible not to crush the pipe  
Connecting the pipe of gas side first makes working easier.  
The max vertical distance between the indoor unit and the outdoor unit is 5 m.  
Forced fastening without careful centering  
may damage the threads and cause a  
leakage of gas.  
Half union  
Flare nut  
Fastening torque  
Pipe Diameter (  
)
Spanner  
Liquid side 6.35mm(1/4")  
Liquid side 9.52mm(3/8")  
18N.m  
40N.m  
Torque wrench  
Gas side 9.52mm(3/8")  
Gas side 12.7mm(1/2")  
40N.m  
50N.m  
Be careful that matters, such as wastes of sands, etc.  
shall not enter the pipe.  
Gas side 15.88mm(5/8")  
60N.m  
2.Attaching Drain-Elbow  
If the drain-elbow is used, please attach it as  
figure. (Note: Only for heat pump unit.)  
3.Purging Method:  
Push the air out of the indoor unit and piping as followes:  
Tighten the caps on the valves with specified torque.  
Tighten torque N.m  
7-9  
Valve rod  
Valve cap  
20-25  
When connecting pipe exceeds 5 meters, 20g or 60g(only for 22k 24k) refrigerant shall be  
added per exceeding meter. Charge according to the following list.  
for 22k 24k  
for 5k 7k 9k 10k 12k 13k 18k  
10m  
Piping length  
Piping length  
5m  
7m  
5m  
7m  
10m  
20m  
Additional amount No need  
40g  
100g  
300g  
Additional amount  
120g  
No need  
900g  
Outdoor unit  
Indoor unit  
A
A
A
Outdoor unit  
Oil trap  
Indoor unit  
B
C
Outdoor unit  
B
Indoor unit  
B
for 5K 7K 9K 10K 12K 13K: B=5m  
for 18K 22K 24K: B=10m  
Max.Elevation:  
Max. Length:  
CAUTION  
C
In case more than 5 metresoil trap  
for 5K 7K 9K 10K: A=7m  
should be installed every 5~7m.  
for 12K 13K:  
A=10m  
for 18K 22K 24K: A=20m  
4

Brother MFC 9660 User Manual
Bryant R 410A 583B User Manual
Carrier 40RM007 034 User Manual
Carrier GL User Manual
Datalogic Scanning QUICKSCAN QS6500 User Manual
Friedrich SM18M30 User Manual
Fujitsu BILDSCANNER M4097D User Manual
Graco Baby Accessories PD162498A User Manual
Haier Portable Air Conditioner HPD10XCM User Manual
HP Hewlett Packard ENVY D410 User Manual