Goodman Mfg GPC15 SEER User Manual

TECHNICAL MANUAL  
GPC15 SEER Multi-Position  
Package Air Conditioners  
with R-410A  
Refer to Service Manual RS6300008 for installation, operation, and troubleshooting information.  
All safety information must be followed as provided in the Service Manual.  
Refer to the appropriate Parts Catalog for part number information.  
Models listed on page 3.  
Models qualify for the 2009 and 2010 Federal Tax Credits for Energy Efficiency**  
**Note that these tax credits are subject to specific requirements set forth in the American Recovery and  
Reinvestment Act of 2009 and in the Internal Revenue Code. Goodman recommends that consumers consult  
a tax professional if they have questions about the applicability of these credits.  
RT6322008r3  
August 2009  
This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman  
does not assume any responsibility for property damage or personal injury due to improper  
service procedures or services performed by an unqualified person.  
Copyright © 2009 Goodman Manufacturing Company, L.P.  
PRODUCT IDENTIFICATION  
The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please  
use these numbers when requesting service or parts information.  
GPC1524M41A*  
GPC1530M41A*  
GPC1536M41A*  
GPC1542M41A*  
GPC1548M41A*  
Models qualify for the 2009 and 2010 Federal Tax Credits  
for Energy Efficiency**  
**Note that these tax credits are subject to specific requirements set forth in the American  
Recovery and Reinvestment Act of 2009 and in the Internal Revenue Code. Goodman  
recommends that consumers consult a tax professional if they have questions about the  
applicability of these credits.  
The United States Environmental Protection Agency (“EPA”) has issued various regulations re-  
garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow  
WARNING  
these regulations may harm the environment and can lead to the imposition of substantial fines.  
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.  
Do not connect or use any device  
To prevent the risk of property  
WARNING  
WARNING  
that is not design certified by  
Goodman for use with this unit.  
damage, personal injury, or death,  
do not store combustible materials or use gasoline or  
other flammable liquids or vapors in the vicinity of this  
appliance.  
Serious property damage, personal injury, reduced unit  
performance and/or hazardous conditions may result  
from the use of such non-approved devices.  
3
PRODUCT DESIGN  
GPC Package Cooling Units are designed for outdoor instal- are a number of design characteristics which are different  
lations only in either residential or light commercial applica- from the traditional reciprocating compressor.  
tions and are available in 2, 2-1/2, 3, 3-1/2 and 4 ton sizes.  
-
Due to their design Scroll Compressors are inherently  
more tolerant of liquid refrigerant. NOTE: Even though the  
compressor section of a Scroll compressor is more toler-  
ant of liquid refrigerant, continued floodback or flooded  
start conditions may wash oil from the bearing surfaces  
causing premature bearing failure.  
They are designed for 208/230 volt single phase applications.  
The connecting ductwork (Supply and Return) can be con-  
nected for either horizontal or vertical airflow. In the vertical  
application, a matching Roof Curb is recommended and a  
horizontal duct cover kit is required.  
A return air filter must be installed behind the return air grille(s)  
or provision must be made for a filter in an accessible loca-  
tion within the return air duct. The minimum filter area should  
not be less than those sizes listed in the Specification Sec-  
tion. Under no circumstances should the unit be operated  
without return air filters.  
-
-
Scroll Compressors use white oil which is compatible  
with 3GS oil which may be used if additional oil is re-  
quired.  
Operating pressures and amp draws may differ from stan-  
dard reciprocating compressors. This information may be  
found in the "Cooling Performance Data" section.  
A 3/4” PVC pipe is provided for removal of condensate water  
from the indoor coil In order to provide proper condensate  
flow, a drain trap is supplied and shipped loose inside the  
unit for field installation. (Do not reduce the drain line size.)  
LocationandClearances  
NOTE: To ensure proper condensate drainage, unit must be  
installed in a level position.  
Refrigerant flow control is achieved by use of restrictor ori-  
fices. GPC units use the FasTest Access Fitting System  
with a saddle that is either soldered to the suction and liquid  
lines or is fastened with a locking nut to the access fitting  
box (core) and then screwed into the saddle. Do not re-  
move the core from the saddle until the refrigerant  
charge has been removed. Failure to do so could re-  
sult in property damage or personal injury.  
48" MIN  
The single phase units use permanent split capacitor (PSC)  
design compressors. Starting components are therefore not  
required for these units. A low microfarad run capacitor as-  
sists the compressor to start and remains in the circuit dur-  
ing operation.  
12" MIN  
36" MIN  
(FOR  
SERVICE)  
The outdoor fan motors are single phase capacitor type mo-  
tors. GPC1524-48M41* units have X-13 indoor blower mo-  
tors that are energized by a 24V signal from the thermostat  
and are constant torque motors with very low power con-  
sumption. The X-13 features an integral control module.  
3"  
MIN  
.
12" MIN  
36" MIN  
(FOR SERVICE)  
Air for condensing (cooling cycle) is drawn through the out-  
door coil by a propeller fan, and is discharged vertically out  
the top of the unit. The outdoor coil is designed for .0 static.  
No additional restriction (ductwork) shall be applied.  
Outside Slab Installation - Multi-positional (M)  
NOTE: Roof overhang should be no more than 36" and  
provisionsmadetodeflectthewarmdischargeairoutfromthe  
overhang.  
Conditioned air is drawn through the filter(s), field installed,  
across the coil and back into the conditioned space by the  
indoor blower.  
Minimumclearancesarerequiredtoavoidairrecirculationand  
keep the unit operating at peak efficiency.  
GPC15 models use Copeland Scroll Compressors. There  
4
PRODUCT DESIGN  
WARNING  
TO PREVENT POSSIBLE PROPERTY DAMAGE, THE  
UNIT SHOULD REMAIN IN AN UPRIGHT POSITION  
DURING ALL RIGGING AND MOVING OPERATIONS.  
TO FACILITATE LIFTING AND MOVING IF A CRANE  
IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE  
SLING.  
IMPORTANT: If using bottom discharge with roof curb,  
ductwork should be attached to the curb prior to installing  
the unit.  
Refer to Roof Curb Installation Instructions for proper curb  
installation. Curbing must be installed in compliance with  
the National Roofing Contractors Association Manual.  
Roof Curb  
Rooftop Installation - Multi-positional (M)  
NOTE: To ensure proper condensate drainage, unit must be  
installed in a level position.  
In installations where the unit is installed above ground level  
and not serviceable from the ground (Example: Roof Top in-  
stallations), the installer must provide service platform for ser-  
vice person with rails or guards in accordance with local codes  
or ordinances or in their absence with the latest edition of the  
Uniform Mechanical Code Section 305.  
NOTE: Unit can also use roof curb (and platform for leveling,  
where necessary) to utilize bottom discharge.  
5
PRODUCT DESIGN  
GPC15[24-48]M41*  
HKR ELECTRICAL DATA  
Circuit #1  
Circuit #2  
Maximum  
Overcurrent  
Protection (amps)  
at 208 / 240V  
Maximum  
Actual  
kW & BTU  
at 240V  
Minimum Circuit  
Ampacity  
at 208 / 240V  
Minimum Circuit  
Ampacity  
at 208 / 240V  
Model and Heat Kit Usage  
Overcurrent  
Protection (amps)  
at 208 / 240V  
GPC1524M41*  
HKR05A,CA  
HKR08A,CA  
HKR10A,CA  
24 / 27  
33 / 28  
45 / 51  
30 / 30  
40 / 40  
60 / 60  
----  
----  
----  
----  
----  
----  
4.75 / 16,200  
7.00 / 23,800  
9.50 / 32,400  
GPC1530M41*  
HKR05A,CA  
24 / 27  
34 / 39  
45 / 52  
45 / 52  
30 / 30  
40 / 40  
60 / 60  
60 / 60  
--  
--  
--  
--  
4.75 / 16,200  
7.0 / 23,800  
9.5 / 32,400  
14.25 / 48,600  
HKR08A,CA  
HKR10A,CA  
HKR15A,CA  
GPC1536M41*  
HKR05A,CA  
HKR08A,CA  
HKR10A,CA  
HKR15A,CA  
GPC1542M41*  
HKR05A,CA  
HKR08A,CA  
HKR10A,CA  
HKR15A,CA  
GPC1548M41*  
HKR05A,CA  
HKR08A,CA  
HKR10A,CA  
HKR15A,CA  
HKR20A,CA  
--  
--  
22 / 25  
30 / 30  
24 / 27  
34 / 39  
30 / 30  
40 / 40  
----  
----  
----  
----  
4.75 / 16,200  
7.00 / 23,800  
45 / 52  
45 / 52  
60 / 60  
60 / 60  
----  
22 / 25  
----  
30 / 30  
9.50 / 32,400  
14.25 / 48,600  
24 / 27  
34 / 39  
45 / 52  
45 / 52  
30 / 30  
40 / 40  
60 / 60  
60 / 60  
--  
--  
--  
--  
4.75 / 16,200  
7.0 / 23,800  
9.5 / 32,400  
14.25 / 48,600  
--  
--  
22 / 25  
30 / 30  
25 / 28  
34 / 40  
46 / 53  
30 / 30  
40 / 40  
60 / 60  
----  
----  
----  
----  
----  
----  
4.75 / 16,200  
7.00 / 23,800  
9.50 / 32,400  
46 / 52  
46 / 52  
60 / 60  
60 / 60  
22 / 25  
43 / 49  
30 / 30  
60 / 60  
14.25 / 48,600  
19.50 / 66,500  
IMPORTANT NOTE: A separate power supply is required for the HKR heater kit.  
Heating kW Correction Factor  
Supply Votage  
240  
1.0  
230  
220  
0.85  
210  
0.78  
208  
0.93  
0.76  
Correction Factor  
Multiply rated kW by correction factor to get actual kW  
All wires and overcurrent protection devices are sized for use with electric heaters only and without  
refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See  
PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent  
protection during refrigeration cycle.  
WARNING  
6
PRODUCT DIMENSIONS  
GPC15[24-48]M41*  
47  
51  
POWER  
WIRE  
ENTRANCE  
A
16  
4 1/8  
2 1/8  
1 3/8  
5 ½  
16  
6 ½  
8
B
2 34  
SUPPLY  
B
SUCTION/LIQUID  
PRESSURE PORT  
RETURN  
3
CONDENSATE  
DRAIN  
CONNECTION  
3/4” NPT FEMALE  
CONTROL  
WIRE  
ENTRANCE  
18 7/8  
BLOWER  
ACCESS PANEL  
MEDIUM CHASSIS  
GPC1524M41*  
GPC1530M41*  
GPC1536M41*  
LARGE CHASSIS  
GPC1542M41*  
GPC1548M41*  
7
GPC15[24-48]M41A*  
PACKAGE COOLING SPECIFICATIONS  
GPC1524M41*  
GPC1530M41*  
GPC1536M41*  
GPC1542M41*  
GPC1548M41*  
COOLING CAPACITY, BTUH  
SEER / EER  
24,000  
14.5 / 12. 0  
208/230-60-1  
15.8  
19.0  
30  
28,000  
14.5 / 12. 0  
208/230-60-1  
17.5  
21.0  
35  
35,000  
14.5 / 12. 0  
208/230-60-1  
20.1  
24.2  
40  
40,000  
45,500  
15.0 / 12.0  
208/230-60-1  
24.2  
COOLING  
14.5 / 12. 0  
CAPACITY  
UNIT  
VOLTAGE (NAMEPLATE)  
AMPS  
208/230-60-1  
ELECTRICAL  
SPECIFICATION  
22.2  
26.7  
40  
MIN CIRCUIT AMPACITY  
MAX OVERCURRENT PROTECTION  
TYPE  
29.2  
45  
COMPRESSOR  
SCROLL  
12.8  
58.3  
1/6  
SCROLL  
14.1  
73.0  
1/4  
SCROLL  
16.7  
79.0  
1/4  
SCROLL  
17.9  
112.0  
1/4  
SCROLL  
19.9  
RATED LOAD AMPS  
LOCKED ROTOR AMPS  
HORSEPOWER  
109.0  
1/4  
CONDENSER  
FAN MOTOR  
RPM  
815  
837  
837  
1075  
1.4  
1075  
1.4  
FULL LOAD AMPS  
1.1  
1.5  
1.5  
LOCKED ROTOR AMPS  
BLADE DIAMETER (INCHES)  
NUMBER OF BLADES  
FACE AREA (SQ. FT.)  
NUMBER OF ROWS  
FINS PER INCH  
1.7  
3.0  
3.0  
2.9  
2.9  
22  
22  
22  
22  
22  
CONDENSER  
FAN  
3
3
3
3
3
CONDENSER  
COIL  
12.33  
1
12.33  
2
12.33  
2
15.38  
2
15.38  
2
24  
16  
16  
16  
16  
HORSEPOWER - NO. OF SPEEDS  
FULL LOAD AMPS  
1/2 - 5  
1.9  
1/2 - 5  
1.9  
1/2 - 5  
1.9  
3/4 - 5  
2.9  
3/4 - 5  
2.9  
EVAPORATOR  
BLOWER  
MOTOR  
LOCKED ROTOR AMPS  
MOTOR SPEED TAP-COOLING X-13  
RPM  
---  
---  
---  
---  
---  
T2  
T2  
T2  
T2  
T2  
1,050  
10 x 9  
850  
1,050  
10 x 9  
1,050  
0.5  
1,050  
10 x 9  
1,150  
0.5  
1,050  
10 x 9  
1,350  
0.5  
1,050  
10 x 9  
1,350  
0.5  
DIAMETER X WIDTH (INCHES)  
RATED SCFM COOLING  
MAX EXTERNAL STATIC PRESS ("w.c.)  
FACE AREA (SQ. FT.)  
NUMBER OF ROWS  
FINS PER INCH  
EVAPORATOR  
BLOWER  
0.5  
4.52  
3
4.52  
3
4.52  
4
6.17  
4
6.17  
EVAPORATOR  
COIL  
4
16  
16  
14  
14  
14  
GENERAL  
FILTER SIZE *  
25 x 25 x 1  
3/4"  
25 x 25 x 1  
3/4"  
25 x 25 x 1  
3/4"  
(2) 20 x 20 x 1  
3/4"  
(2) 20 x 20 x 1  
3/4"  
DRAIN SIZE (INCHES)  
EXPANSION DEVICE  
REFRIGERANT CHARGE R410A (OZS.)  
INFORMATION  
0.057  
80  
0.065  
100  
0.068  
115  
0.072  
140  
0.076  
170  
POWER SUPPLY  
CONDUIT KNOCKOUT SIZE (INCHES)  
3/4, 1, 1-1/4  
1/2  
3/4, 1, 1-1/4  
1/2  
3/4, 1, 1-1/4  
1/2  
3/4, 1, 1-1/4  
1/2  
3/4, 1, 1-1/4  
1/2  
LOW VOLTAGE  
CONDUIT KNOCKOUT SIZE (INCHES)  
SHIPPING WEIGHT (LBS.)  
OPERATING WEIGHT (LBS.)  
375  
354  
384  
363  
416  
395  
459  
438  
459  
438  
(1)  
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.  
*
Calculated external filter size based on air velocity of 300 ft/min.  
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.  
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers  
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.  
All wires and overcurrent protection devices are sized for use with electric heaters only and without  
refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See  
PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent  
protection during refrigeration cycle.  
WARNING  
8
ACCESSORIES  
ACCESSORIES - GPC/GPH****M MODELS  
Description  
Part Number  
OT18-60A  
Outdoor Thermostat Kit w/Lockout Stat  
Emergency Heat Relay Kit  
OT/EHR18-60  
HKR  
Electric Heat Kit  
PGC101/102/103  
PEHH101/102  
PEHH103  
Roof Curb  
Horizontal Economizer For Heat Pump, Small and Medium Chassis  
Horizontal Economizer For Heat Pump, Large Chassis  
Horizontal Economizer For A/C, Small and Medium Chassis  
Horizontal Economizer For A/C, Large Chassis  
PEHC101/102  
PEHC103  
PGMDD101/102  
PGMDD103  
Manual 25% Fresh Air Damper Downflow Application, Small and Medium Chassis  
Manual 25% Fresh Air Damper Downflow Application, Large Chassis  
Manual 25% Fresh Air Damper Horizontal Application, Medium Chassis  
Manual 25% Fresh Air Damper Horizontal Application, Large Chassis  
Motorized 25% Fresh Air Damper Downflow Application,Small and Medium Chassis  
Motorized 25% Fresh Air Downflow Application, Large Chassis  
Motorized 25% Fresh Air Damper Horizontal Application, Medium Chassis  
Motorized 25% Fresh Air Damper Horizontal Application, Large Chassis  
Downflow Economizer For A/C, Medium Chassis  
PGMDH102  
PGMDH103  
PGMDMD101/102  
PGMDMD103  
PGMDMH102  
PGMDMH103  
GPC13MED102  
GPC13MED103  
GPH13MED102  
GPH13MED103  
GPH13MFR102  
GPH13MFR103  
GPGHFR101-103  
SQRPG101/102  
SQRPG103  
Downflow Economizer For A/C, Large Chassis  
Downflow Economizer For Heat Pump, Medium Chassis  
Downflow Economizer For Heat Pump, Large Chassis  
Internal Filter Rack, Medium Chassis  
Internal Filter Rack, Large Chassis  
External Horizontal Filter Rack for Goodman/Amana Gas/Electric and Multi-position Package Units All Chassis  
Square to Round Adapter w/ 16" Round Downflow Application, Medium Chassis  
Square to Round Adapter w/ 18" Round Downflow Application, Large Chassis  
Square to Round Adapter w/ 16" Round Horizontal Application, Medium Chassis  
Square to Round Adapter w/ 18" Round Horizontal Application, Large Chassis  
Flush Mount Concentric Duct Kit  
SQRPGH101/102  
SQRPGH103  
CDK36  
CDK36515  
Flush Mount Concentric Duct Kit w/ Filter  
CDK36530  
Step Down Concentric Duct Kit  
CDK36535  
Step Down Concentric Duct Kit w/ Filter  
CDK4872  
Flush Mount Concentric Duct Kit  
CDK4872515  
CDK4872530  
CDK4872535  
Flush Mount Concentric Duct Kit w/ Filter  
Step Down Concentric Duct Kit  
Step Down Concentric Duct Kit w/ Filter  
9
BLOWER PERFORMANCE DATA  
GPC15[24-48]M41A*  
Dry Coil Data  
E.S.P (In. of H O)  
2
Model  
Speed  
Volts  
0.1  
0.2  
0.3  
0.4  
0.5  
545  
0.6  
0.7  
0.8  
CFM  
882  
808  
727  
649  
---  
---  
---  
T1 (G)  
230  
230  
230  
WATTS  
CFM  
82  
933  
86  
873  
103  
1012  
136  
824  
95  
92  
102  
733  
120  
896  
153  
665  
111  
959  
179  
1123  
239  
592  
95  
108  
637  
126  
816  
168  
575  
115  
889  
184  
1066  
244  
545  
99  
---  
584  
135  
723  
172  
---  
---  
---  
---  
---  
810  
109  
945  
142  
752  
101  
1011  
168  
1165  
228  
711  
85  
T2 / T3  
T4 / T5  
WATTS  
CFM  
93  
---  
---  
1058  
124  
672  
179  
---  
---  
WATTS  
CFM  
---  
893  
---  
T1 (G)  
T2 / T3  
T4 / T5  
T1 (G)  
T2 / T3  
T4 / T5  
T1 (G)  
T2 / T3  
T4 / T5  
T1 (G)  
T2 / T3  
T4 / T5  
230  
230  
230  
230  
230  
230  
230  
230  
230  
230  
230  
230  
WATTS  
CFM  
87  
---  
---  
---  
1132  
153  
1070  
162  
1236  
217  
764  
82  
827  
195  
1012  
255  
---  
733  
206  
958  
265  
---  
669  
208  
857  
272  
---  
WATTS  
CFM  
1287  
211  
WATTS  
CFM  
852  
WATTS  
CFM  
80  
---  
---  
---  
1232  
202  
1190  
214  
1213  
226  
1070  
170  
1390  
317  
1490  
379  
1138  
173  
1745  
493  
1865  
585  
1131  
221  
1162  
236  
1025  
182  
1354  
331  
1450  
391  
1085  
185  
1698  
508  
1818  
602  
1082  
229  
1120  
245  
984  
193  
1318  
342  
1410  
403  
1017  
193  
1658  
521  
1780  
625  
1023  
235  
1058  
247  
942  
204  
1281  
355  
1383  
416  
957  
211  
1610  
531  
1719  
627  
966  
246  
1009  
260  
894  
216  
1243  
366  
1348  
427  
889  
219  
1560  
545  
1667  
621  
889  
258  
932  
272  
839  
229  
1204  
377  
1312  
439  
820  
232  
1522  
550  
1579  
595  
819  
264  
841  
275  
774  
242  
1165  
389  
1267  
451  
755  
245  
1450  
547  
1483  
569  
WATTS  
CFM  
1267  
218  
WATTS  
CFM  
1123  
162  
Watts  
CFM  
1437  
310  
Watts  
CFM  
1528  
372  
Watts  
CFM  
1199  
162  
WATTS  
CFM  
1799  
480  
WATTS  
CFM  
1921  
582  
WATTS  
NOTES:  
Data shown is Dry Coil. Wet Coil Pressure Drop is approximate. 0.1" H2O, for 2 row indoor coil; 0.2” H2O, for 3 row indoor coil;  
and 0.3” H2O, for 4 row indoor coil.  
Data shown does not include filter pressure drop, approx. 0.08” H2O.  
ALL MODELS SHOULD RUN NO LESS THAN 350 CFM / TON.  
Reduce airflow by 2% for 208V operation.  
10  
BLOWER PERFORMANCE DATA  
S E R E I R U  
M P T E E R A T  
11  
COOLING PERFORMANCE DATA  
GPC1524M41*  
12  
COOLING PERFORMANCE DATA  
GPC1524M41*  
13  
COOLING PERFORMANCE DATA  
GPC1530M41*  
14  
COOLING PERFORMANCE DATA  
GPC1530M41*  
15  
COOLING PERFORMANCE DATA  
GPC1536M41*  
16  
COOLING PERFORMANCE DATA  
GPC1536M41*  
17  
COOLING PERFORMANCE DATA  
GPC1542M41*  
18  
COOLING PERFORMANCE DATA  
GPC1542M41*  
19  
COOLING PERFORMANCE DATA  
GPC1548M41*  
20  
COOLING PERFORMANCE DATA  
GPC1548M41*  
21  
COOLING PERFORMANCE DATA  
PERFORMANCE TEST  
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor  
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:  
If conditions vary from this, results will change as follows:  
1. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low  
and high side pressures and power will not change.  
2. As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will  
occur in low and high side pressures and power.  
A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.  
A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.  
A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.  
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.  
22  
WIRING DIAGRAMS  
HKR***  
BK  
BK  
BK  
BK  
BK  
BK  
M1  
M1  
M2  
M3  
M4  
M2  
BK  
BK  
BK  
BK  
BK  
BK  
BK  
BK  
BK  
BK  
M1  
M3  
M1  
M2  
M1  
M2  
M3  
M5  
M7  
M8  
M4  
M2  
M4 M6  
BK  
BK  
BK  
BK  
BK  
BK  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
23  
WIRING DIAGRAMS  
GPC15[24-48]M41*  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
24  
WIRING DIAGRAMS  
GPC15[24-48]M41*  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
25  

Briggs Stratton 136200 User Manual
Briggs Stratton Automobile Parts 90000 User Manual
Canon PIXMA MP240 User Manual
Danby DAC12344DE User Manual
Epson Stylus NX530 User Manual
Friedrich Air Conditioner P12B User Manual
GE ASQ12DL User Manual
Gravely 927064 RM1440 User Manual
Haier CWH08A User Manual
Heat Controller Inc Air Conditioner REG 183J User Manual