Fujitsu Air Conditioner AOU09RL2 User Manual

SPLIT TYPE  
ROOM AIR CONDITIONER  
type  
WALL MOUNTED  
INVERTER  
SERVICE  
INSTRUCTION  
Models Indoor unit  
Outdoor unit  
AOU09RL2  
AOU12RL2  
ASU09RL2  
ASU12RL2  
CONTENTS  
1. DESCRIPTION OF EACH CONTROL OPERATION  
1. COOLING OPERATION................................................................................................ 01-01  
2. HEATING OPERATION................................................................................................. 01-02  
3. DRY OPERATION......................................................................................................... 01-02  
4. AUTO CHANGEOVER OPERATION............................................................................ 01-03  
5. INDOOR FAN CONTROL.............................................................................................. 01-04  
6. OUTDOOR FAN CONTROL.......................................................................................... 01-06  
7. LOUVER CONTROL..................................................................................................... 01-07  
8. COMPRESSOR CONTROL.......................................................................................... 01-08  
9. TIMER OPERATION CONTROL................................................................................... 01-09  
10. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )................................. 01-11  
11. FOUR-WAY VALVE EXTENSION SELECT................................................................ 01-11  
12. AUTO RESTART......................................................................................................... 01-11  
13. MANUAL AUTO OPERATION ( Indoor unit body operation )..................................... 01-11  
14. FORCED COOLING OPERATION.............................................................................. 01-12  
15. COMPRESSOR PREHEATING.................................................................................. 01-12  
16. ECONOMY OPERATION............................................................................................ 01-12  
17. POWERFUL OPERATION.......................................................................................... 01-12  
18. DEFROST OPERATION CONTROL........................................................................... 01-13  
19. OFF DEFROST OPERATION CONTROL................................................................... 01-15  
20. VARIOUS PROTECTIONS.......................................................................................... 01-16  
2. TROUBLE SHOOTING  
2-1 ERROR DISPLAY....................................................................................................... 02-01  
2-2 TROUBLE SHOOTING WITH ERROR CODE............................................................ 02-02  
2-3 TROUBLE SHOOTING WITH NO ERROR CODE..................................................... 02-21  
2-4 SERVICE PARTS INFORMATION.............................................................................. 02-26  
3. APPENDING DATA  
3-1 FUNCTION SETTING................................................................................................. 03-01  
3-1-1 INDOOR UNIT.................................................................................................... 03-01  
3-1-2 Procedures to change the Function Setting for wireless RC.............................. 03-03  
3-2 Thermistor Resistance Values..................................................................................... 03-06  
3-2-1 INDOOR UNIT.................................................................................................... 03-06  
3-2-2 OUTDOOR UNIT................................................................................................ 03-06  
WALL MOUNTED type  
INVERTER  
1 . DESCRIPTION OF EACH  
CONTROL OPERATION  
1. COOLING OPERATION  
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive  
difference or variation between a set temperature and present room temperature, and  
controls the operation frequency of the compressor.  
* If the room temperature is 2°C(4°F) higher than a set temperature, the compressor operation  
frequency will attain to maximum performance.  
* If the room temperature is some degrees lower than a set temperature,  
the compressor will be stopped.  
* When the room temperature is between +2°C(4°F) to -2.5°C(-5°F) of the setting temperature,  
the compressor frequency is controlled within the range shown in Table1.  
However, the maximum frequency is limited in the range shown in Fig.1 based on the indoor  
fan mode and the outdoor temperature.  
( Table 1 : Compressor frequency range )  
Minimum  
frequency  
Maximum  
frequency  
Maximum  
frequency  
AOU09RL2  
AOU12RL2  
57rps  
80rps  
80rps  
96rps  
18rps  
When the compressor operates for 30 minutes continuously at over the maximum frequency ,  
the maximum frequency is changed from Maximum Frequency to Maximum Frequency.  
( Fig.1 : Outdoor temperature zone )  
When the outdoor  
( Table 2 : Limit of maximum speed based on outdoor temperature )  
Indoor fan mode  
Me Lo  
Outdoor  
temp. zone  
Hi  
Quiet  
temperature rises  
When the outdoor  
A zone  
B zone  
C zone  
D zone  
E zone  
F zone  
A zone  
B zone  
C zone  
D zone  
E zone  
F zone  
80rps 49rps 42rps 32rps  
80rps 49rps 42rps 32rps  
80rps 49rps 42rps 32rps  
49rps 44rps 40rps 29rps  
49rps 44rps 40rps 29rps  
49rps 44rps 40rps 29rps  
96rps 61rps 51rps 33rps  
96rps 61rps 51rps 33rps  
96rps 61rps 51rps 33rps  
73rps 57rps 45rps 33rps  
73rps 57rps 45rps 33rps  
73rps 57rps 45rps 33rps  
ASU09RL2  
ASU12RL2  
temperature drops  
36°C  
(97°F)  
A zone  
34°C  
(93°F)  
32°C  
(90°F)  
B zone  
C zone  
D zone  
30°C  
(86°F)  
21°C  
(70°F)  
19°C  
(66°F)  
12°C  
(54°F)  
10°C  
(50°F)  
2°C  
(36°F)  
E zone  
F zone  
0°C  
(32°F)  
01-01  
2. HEATING OPERATION  
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive  
difference or variation between a set temperature and present room temperature, and  
controls the operation frequency of the compressor.  
* If the room temperature is lower by 3°C (6°F) than a set temperature, the compressor operation  
frequency will attain to maximum performance.  
* If the room temperature is some degrees higher than a set temperature,  
the compressor will be stopped.  
* When the room temperature is between +2.5°C (+5°F) to -3°C (-6°F) of the setting temperature,  
the compressor frequency is controlled within the range shown in Table 3.  
However, the maximum frequency is limited shown in Table 4 based on the fan mode.  
( Table 3 : Compressor frequency range )  
Minimum  
frequency  
Maximum  
frequency  
AOU09RL2  
AOU12RL2  
80rps  
18rps  
120rps  
( Table 4 : Limit of maximum speed based on outdoor temperature )  
Indoor fan mode  
Hi  
Me  
Lo  
Quiet  
Auto  
AOU09RL2  
AOU12RL2  
80rps  
120rps  
3. DRY OPERATION  
The compressor frequency shall change according to the temperature, set temperature,  
and room temperature variation which the room temperature sensor of the indoor unit body has  
detected as shown in the Table 5.  
However, after the compressor is driven, the indoor unit shall run at operation frequency of  
(09 : 52 rps, 12 : 61 rps) for 60 seconds.  
( Table 5 : Compressor frequency in Dry mode)  
Operating  
frequency  
Operating  
frequency  
X zone  
J zone  
Y zone  
30rps  
28rps  
0rps  
AO09RL2  
AO12RL2 X zone  
J zone  
33rps  
25rps  
0rps  
Y zone  
( Fig.2 : Compressor control based on room temperature )  
When the room  
temperature rises  
When the room  
temperature drops  
Ts+1.5°C (Ts+3°F)  
X zone  
Ts+0.5°C (Ts+1°F)  
Ts -1.5°C (Ts-3°F)  
Ts -0.5°C (Ts-1°F)  
J zone  
Y zone  
01-02  
4. AUTO CHANGEOVER OPERATION  
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum  
mode from among the Heating, Cooling, Dry and Monitoring modes.  
During operation, the optimum mode is automatically switched in accordance with temperature changes.  
The temperature can be set between 18°C (64°F) and 30°C (88°F) in 1°C (2°F) steps.  
(Fig. 3 : Operation flow chart in Auto changeover)  
START  
Room temp.  
YES  
>Ts+2°C (4°F) ?  
T
S : Setting temperature  
NO  
NO  
Room temp.  
<Ts- 2°C(4°F) ?  
YES  
HEATING OPERATION  
COOLING OPERATION  
Thermostat remains  
Thermostat remains  
in OFF state for 6 minutes or  
longer?  
YES  
YES  
YES  
in OFF state for 6 minutes or  
longer?  
NO  
NO  
System stops  
or operation command other than  
auto changeover operation?  
System stops  
or operation command other than  
auto changeover operation?  
YES  
NO  
NO  
01-03  
5. INDOOR FAN CONTROL  
1. Fan speed  
( Table 6 : Indoor fan speed )  
Speed (rpm)  
Operation mode  
Heating  
Air flow mode  
ASU12RL2  
ASU09RL2  
Powerful  
Hi  
Me+  
1420  
1360  
1290  
1120  
900  
1420  
1360  
1290  
1120  
900  
Me  
Lo  
Quiet  
700  
700  
Cool air prevention  
600  
600  
S-Lo  
Powerful  
Hi  
480  
480  
1400  
1320  
1120  
840  
1400  
1320  
1120  
860  
Cooling/ Fan  
Me  
Lo  
Quiet  
700  
700  
* Soft Quiet  
600  
600  
X zone: 700  
J zone: 600  
X zone: 700  
J zone: 600  
Dry  
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs.  
(Hi > Me, Me > Lo, Lo > Quiet, Quiet > Soft Quiet)  
2. FAN OPERATION  
The airflow can be switched in 5 steps such as Auto, Quiet, Lo, Me, Hi, while the indoor fan only runs.  
When fan mode is set at [Auto], it operates on [Me] fan Speed.  
3. COOLING OPERATION  
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Fig4.  
On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow of [Cool]  
operation modes Quiet, Lo, Me, Hi, as shown in Table 6.  
( Fig.4 : Airflow change - over ( Cooling : Auto ) )  
When the room  
temperature rises  
When the room  
temperature drops  
TR : Room temperature  
Ts : Setting temperature  
TR-Ts > 2.5°C (5°F)  
=
Hi mode  
Me mode  
Lo mode  
TR-Ts > 2°C (4°F)  
2.5°C (5°F) > TR-Ts > 1.5°C (3°F)  
=
2°C (4°F) > TR-Ts > C (2°F)  
=
1.5°C (3°F) > TR-Ts  
1°C (2°F) > TR-Ts  
4. DRY OPERATION  
Refer to the Table 6.  
During the dry mode operation, the fan speed setting can not be changed.  
01-04  
5. HEATING OPERATION  
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Fig. 5  
On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow  
of [Heat] operation modes Quiet, Lo, Me, High, as shown in Table 6.  
( Fig.5 : Airflow change - over ( Heating : Auto ) )  
When the room  
TR : Room temperature  
Ts : Setting temperature  
When the room  
temperature drops  
temperature rises  
TR-Ts > -1°C (-2°F)  
=
Lo mode  
Me mode  
Me+ mode  
TR-Ts > -1.5°C (-3°F)  
=
-1°C (-2°F) > TR-Ts > -2°C (-4°F)  
=
-1.5°C (3°F) > TR-Ts > -2.5°C (-5°F)  
=
-2°C (-4°F) > TR-Ts  
-2.5°C (-5°F) > TR-Ts  
6. COOL AIR PREVENTION CONTROL (Heating mode)  
The maximum value of the indoor fan speed is set as shown in Fig.6 based on the detected  
temperature by the indoor heat-exchanger sensor on heating mode.  
( Fig.6 : Cool air prevension control )  
<Powerful operation>  
<Normal operation>  
When the Indoor heat  
exchanger temp. rises  
When the Indoor heat  
exchanger temp. drops  
When the Indoor heat  
exchanger temp. drops  
When the Indoor heat  
exchanger temp. rises  
* Hi or setting  
Fan mode  
Powerful  
42°C  
42°C (108°F)  
39°C (102°F)  
(108°F)  
37°C  
Hi  
37°C (99°F)  
39°C  
(102°F)  
* Me+ or setting  
Fan mode  
(99°F)  
34°C  
(93°F)  
32°C  
(90°F)  
Lo  
37°C  
(99°F)  
34°C (93°F)  
Cool air  
* Lo or setting  
Fan mode  
prevention  
30°C  
(86°F)  
37°C (99°F)  
30°C (86°F)  
28°C  
(82°F)  
S-Lo  
Cool air  
32°C (90°F)  
28°C (82°F)  
prevention  
* Lower speed is selected.  
S-Lo  
* Lower speed is selected.  
7. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)  
Switch the airflow [Auto] at cooling mode, and the indoor fan motor will run as shown in Fig.7.  
( Fig.7 : Indoor fan control )  
Compressor  
ON  
OFF  
Indoor fan  
Setting air flow  
Indoor fan  
(as shown in Table 7)  
S-Lo  
OFF  
10  
30  
60  
180  
60  
180  
60  
10  
30  
(sec)  
( Table 7 : Indoor fan speed )  
Dry  
Cooling  
X zone  
700rpm  
J zone  
Y zone  
ASU09/12RL2  
600rpm  
0
480rpm 700rpm  
01-05  
6. OUTDOOR FAN CONTROL  
1. Outdoor Fan Motor  
Following table shows the type of the outdoor fan motor. The control method is different  
between AC motor and DC motor.  
( Table 8 : Type of Motor )  
AC motor  
DC motor  
AOU09RL2  
AOU12RL2  
2. Fan Speed  
( Table 9 : Outdoor fan speed )  
Cooling  
Heating  
Dry  
Zone  
Y
Z
F
G
Y
730 / 650 / 470  
730 / 470 / 360  
360 / 150  
AOU09RL2  
900 / 650 / 470  
730 / 470  
210 / 150  
860 / 760 / 470  
860 / 470 / 380  
380 / 280  
Z
F
AOU12RL2  
900 / 760 / 680 / 470  
760 / 470  
G
280 / 200  
Refer to Fig.8  
( Fig.8 : Outside air temperature zone selection )  
Outside air  
temperature  
Outside air  
temperature  
Y zone  
Z zone  
F zone  
G zone  
21°C (70°F)  
12°C (54°F)  
2°C (36°F)  
19°C (66°F)  
10°C (50°F)  
0°C (32°F)  
*The outdoor fan speed mentioned adove depends on the compressor frequency.  
(When the compressor frequency increases, the outdoor fan speed also changes to the higher  
speed. When the compressor frequency decreases, the outdoor fan speed also changes to the  
lower speed.)  
*After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed  
as table 10 without relating to the compressor frequency.  
( Table 10 : Outdoor fan speed after the defrost )  
AOU09RL2  
900 rpm  
AOU12RL2  
01-06  
7. LOUVER CONTROL  
1. VERTICAL LOUVER CONTROL  
(Function Range)  
Each time the button is pressed, the air direction range will change as follow:  
Fig.8 : Air Direction Range  
Types of Air flow Direction Setting:  
,
,
,
,
,
,
: During Cooling/Dry modes  
: During Heating  
1
2
3
The Remote Controller's display does not change.  
4
5
6
7
Use the air direction adjustments within the ranges shown above.  
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.  
Cooling / Dry mode Horizontal flow  
Heating mode  
Downward flow  
for more than 30 minutes in Cooling or Dry mode,  
If you set the angle to position  
~
they automatically return to position  
.
In Cooling or Dry mode, if the angle is set to position  
~
for many hours,  
condensation may be formed, and the drips may wet your property.  
2. ADJUST THE RIGHT-LEFT LOUVERS  
Move the Right-Left louvers to adjust air flow in the direction you prefer.  
Right-Left Louvers  
Knob  
Knob (2 places)  
3. SWING OPERATION  
To select Vertical Airflow Swing Operation  
When the swing signal is received from the remote controller, the vertical louver starts to swing.  
(Table10 : Swinging Range)  
Range  
Cooling / Dry mode  
Fan mode (  
)
ode  
Heating m  
(
)
Fan mode  
The SWING operation may stop temporarily when the air conditioner’s fan is not operating,  
or when operating at very low speeds.  
To select Horizontal Airflow Swing Operation  
(No function)  
01-07  
8. COMPRESSOR CONTROL  
1. OPEARTION FREQUENCY RANGE  
The operation frequency of the compressor is different based on the operation mode as  
shown in the Table 11.  
(Table 11 : Compressor frequency range)  
Cooling / Dry  
Heating  
Minimum Maximum  
Minimum  
18rps  
Maximum  
120rps  
AOU09RL2  
AOU12RL2  
80rps  
18rps  
96rps  
2. OPEARTION FREQUENCY CONTROL AT NORMAL START UP  
The compressor frequency soon after the start-up is controlled as shown in the Fig.9.  
(Fig.9 : Compressor control at start-up)  
Frequency  
Frequency  
Frequency  
Frequency  
Frequency  
Frequency  
Time  
Time  
Time  
Time  
Time  
6
Time  
(Frequency)  
Frequency  
Frequency  
Frequency  
Frequency  
Frequency  
Frequency  
AOU09RL2  
AOU12RL2  
56rps  
56rps  
67rps  
74rps  
75rps  
87rps  
78rps  
97rps  
78rps  
78rps  
108rps  
119rps  
(Time)  
Time  
Time  
Time  
Time  
Time  
Time 6  
AOU09RL2  
AOU12RL2  
80sec  
60sec  
140sec  
100sec  
200sec  
140sec  
380sec  
200sec  
440sec  
350sec  
440sec  
410sec  
3. LIMITATION OF COMPRESSOR FREQUENCY BY OUTDOOR TEMPERATURE  
The minimum compressor frequency is limited by outdoor temperature as shown in the Table12.  
(Table12 : Limitation of Compressor Frequency)  
[ Cooling/ Dry ]  
10°C (50°F)  
14°C (59°F)  
Under Over  
23rps  
27rps  
40°C (104°F)  
Under  
35rps  
45rps  
Over  
Under  
Over  
AOU09RL2  
AOU12RL2  
-------  
30rps  
[ Heating ]  
- 3°C (26°F)  
7°C (45°F)  
Under Over  
27rps  
14°C (59°F)  
40°C (104°F)  
Under  
34rps  
36rps  
Over  
Under  
Over  
Under  
Over  
AOU09RL2  
AOU12RL2  
22rps  
27rps  
-------  
30rps  
27rps  
01-08  
9. TIMER OPEARTION CONTROL  
9-1 WIRELESS REMOTE CONTROLLER  
The Table 13 shows the available timer setting based on the product model.  
( Table 13 : Timer Setting )  
ON TIMER / OFF TIMER  
PROGRAM TIMER  
SLEEP TIMER  
ASU09RL2  
ASU12RL2  
1. OPEARTION FREQUENCY RANGE  
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.  
Operation mode  
Stop mode  
Set time of timer  
ON timer : When the clock reaches the set time, the air conditioner will be turned on.  
Operation mode  
Stop mode  
Set time of timer  
2. PROGRAM TIMER  
The program timer allows the OFF timer and ON timer to be used in combination one time.  
Operation mode  
Operation mode  
Operation mode  
Stop mode  
Stop mode  
Stop mode  
Set time  
Set time  
Set time  
Set time  
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest  
to the clock's current timer setting.  
The order of operations is indicated by the arrow in the remote control unit's display.  
SLEEP timer operation cannot be combined with ON timer operation.  
01-09  
3. SLEEP TIMER  
If the sleep is set, the room temperature is monitored and the operation is stopped automatically.  
If the operation mode or the set temperature is change after the sleep timer is set, the operation is  
continued according to the changed setting of the sleep timer from that time ON.  
In the cooling operation mode  
When the sleep timer is set, the setting temperature is increased 1°C (2°F).  
It increases the setting temperature another 1°C (2°F) after 1 hour.  
After that, the setting temperature is not changed and the operation is stopped at the time  
of timer setting.  
Set temperature rises  
( Ts : Set temperature )  
+2°C (4°F)  
+1°C (2°F)  
Ts  
Stop of operation  
Set  
60min  
In the heating operation mode  
When the sleep timer is set, the setting temperature is decreased 1°C (2°F).  
It decreases the setting temperature another 1°C (2°F) every 30 minutes.  
Upon lowering 4°C (8°F), the setting temperature is not changed and the operation stops at  
the time of timer setting.  
Set temperature lowers  
( Ts : Set temperature )  
Ts  
-1°C (-2°F)  
-2°C (-4°F)  
-3°C (-6°F)  
-4°C (-8°F)  
Stop of operation  
Set  
30min  
30min  
30min  
01-10  
10. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )  
The compressor won't enter operation status for 2 minutes and 20 seconds after the compressor is stopped,  
even if any operation is given.  
11. FOUR-WAY VALVE EXTENSION SELECT  
At the time when the air conditioner is switched from the cooling mode to heating mode, the  
compressor is stopped, and the four-way valve is switched in 2 minutes and 20 seconds later after  
the compressor stopped.  
12. AUTO RESTART  
When the power was interrupted by a power failure, etc. during operation, the operation contents  
at that time are memorized and when power is recovered, operation is automatically started with  
the memorized operation contents.  
When the power is interrupted and recovered during timer operation, since the timer operation time  
is shifted by the time the power was interrupted, an alarm is given by blinking (7 sec ON/2 sec OFF)  
the indoor unit body Timer lamp.  
[ Operation contents memorized when the power is interrupted ]  
Operation mode  
Set temperature  
Set air flow  
Timer mode and set time  
Set air flow Direction  
Swing  
ECONOMY operation  
13. MANUAL AUTO OPERATION (Indoor unit body operation)  
When the remote control is lost or battery power dissipated, this function will work without the remote control.  
When MANUAL AUTO button is set more than 3seconds and less than 10seconds, MANUAL AUTO OPERATION  
will be started as shown in Table14.  
To stop operation, press the MANUAL AUTO button for 3seconds.  
(Table14 : MANUAL AUTO OPERATION)  
Manual auto operation  
OPERATION MODE Auto changeover  
Press and hold MANUAL AUTO  
button for 3 ~ 10seconds  
FAN CONT. MODE  
TIMER MODE  
SETTING TEMP.  
SETTING LOUVER  
SWING  
Auto  
(No timer setting available)  
Continuous  
24°C (75°F)  
Standard  
OFF  
ECONOMY  
OFF  
01-11  
14. FORCED COOLING OPERATION (TEST OPERATION)  
When FORCED COOLING OPERATION is set, the operation is controlled as shown in Table15.  
( Table15 : FORCED COOLING OPERATION )  
Forced cooling operation  
OPERATION MODE  
FAN CONT. MODE  
TIMER MODE  
Cooling  
Hi  
-
SETTING TEMP.  
SETTING LOUVER  
Room Temp is not controlled  
Horizontal  
(It is changed follow as setting of remote controller)  
SWING  
ECONOMY  
OFF  
-
Forced cooling operation is started when press MANUAL AUTO button for 10 seconds or more.  
During the forced cooling operation, it operates regardless of room temperature sensor.  
Operation lamp and Timer lamp blink at the same time during the forced cooling operation.  
They blink for 1 second ON and 1 second OFF on both Operation lamp and Timer lamp (same as test operation).  
Forced cooling operation is released after 60 minutes of starting operation or pressing MANUAL AUTO button  
for 3 seconds or pressing START/STOP button on the remote controller.  
15. COMPRESSOR PREHEATING  
When the outdoor heat exchanger temperature is lower than 5°C and the all operation has  
been stopped for 30 minutes, power is applied to the compressor and the compressor is heated.  
(By heating the compressor, warm air is quickly discharged when operation is started.)  
When operation was started, and when the outdoor temperature rises to 7°C (44.6°F) or greater,  
preheating is ended.  
16. ECONOMY OPERATION  
The ECONOMY operation functions by pressing ECONOMY button on the remote controller.  
At the maximum output, ECONOMY Operation is approximately 70% of normal air conditioner operation  
for cooling and heating.  
The ECONOMY operation is almost the same operation as below settings.  
( Table 16 )  
Heating  
Mode  
Cooling/ Dry  
Target temperature Setting temp.+1°C (2°F) Setting temp.-1°C (-2°F)  
17. POWERFUL OPERATION  
The POWERFUL OPERATION functions by pressing POWERFUL button on the remote controller.  
The indoor unit & outdoor unit will operate at maximum power as shown in Table17.  
(Table17)  
Powerful operation  
COMPRESSOR FREQUENCY Maximum  
FAN CONT. MODE  
SETTING LOUVER  
Powerful  
Cooling/ Dry : 3, Heating : 5  
Release Condition is as follows.  
[Cooling / Dry]  
- Room temperature < Setting temperature - 1.5°C (-3°F) or Operation time has passed 20 minutes.  
=
[Heating]  
- Room temperature > Setting temperature +1.5°C (+3°F) or Operation time has passed 20 minutes.  
=
01-12  
3. Defrost Flow Chart  
The defrosting shall proceed by the integrating operation time, outdoor temperature  
and outdoor heat exchanger temperature as follows.  
Heating operation start : Compressor ON  
(Not defrosted for 10 minutes)  
Integrating defrost  
Normal defrost  
Intermittent operation  
Continuous operation  
Outside air temp. > -10°C Outside air temp. < -10°C  
=
(14°F)  
(14°F)  
Compressor  
integrating  
operation:  
Compressor  
integrating  
operation:  
Compressor  
OFF count :  
40 times  
Outdoor HEX temp.  
- Outside air temp.  
Below - 7°C(-44.6°F)  
or  
Outdoor HEX temp.  
Below - 17°C(1.4°F)  
Over 240 min.  
Over 213 min.  
(Less than 10min.)  
Outdoor HEX temp.  
Below - 20°C(-4°F)  
Outdoor  
Outdoor  
heat exchanger heat exchanger  
temperature:  
Below - 3°C  
(26.6°F)  
temperature:  
Below - 5°C  
(23°F)  
Defrost start  
Defrost Indicator:  
[Operation lamp]  
7 sec ON / 2 sec OFF  
Outdoor fan : OFF  
Compressor speed : 0 rps  
4-way valve : OFF  
Compressor speed : 90rps  
Outdoor HEX temp.: Over 16°C (60.8°F)  
or  
Compressor ON time: Maximum 15 minutes  
Defrost end  
01-14  
19. OFF DEFROST OPEARTION CONTROL  
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat  
exchanger, the defrost operation will proceed automatically. In this time, if indoor unit Operation lamp  
flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost,  
and then stop.  
1. OFF DEFROST OPERATION CONDITION  
In heating operation, the outdoor heat exchanger temperature is less than - 4°C (24.8°F),  
compressor continuous operation more than 10 minutes, and  
compressor operation integrating time lasts for more than 30 minutes.  
2. OFF DEFROST END CONDITION  
Release Condition  
Outdoor heat exchanger temperature sensor value is higher than  
16°C (60.8°F) or Compressor operation time has passed 15 minutes.  
OFF Defrost Flow Chart  
Heating operation stop  
Outdoor heat exchanger temperature :  
Below - 4°C (24.8°F)  
Compressor continuous operation :  
Over 10 minutes  
Compressor integrating operation :  
Over 30 minutes  
Defrost start  
Defrost Indicater:  
[Operation lamp]  
7 sec ON / 2 sec OFF  
Outdoor heat exchanger temperature:  
Over 16°C (60.8°F) or  
Compressor ON time: Over 15 minutes  
Defrost end  
01-15  
20. VARIOUS PROTECTIONS  
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL  
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature.  
When the discharge temperature becomes higher than Temperature , the compressor frequency  
is decreased 20rps, and it continues to decrease the frequency for 20rps every 120 seconds until  
the temperature becomes lower than Temperature .  
When the discharge temperature becomes lower than Temperature , the protection control of the  
compressor frequency will be released.  
When the discharge temperature becomes higher than Temperature , the compressor is stopped  
and the indoor unit body Operation lamp and Timer lamp starts blinking.  
(Table 20 : Discharge temperature over rise prevension control / Release temperature)  
Temperature  
Temperature  
Temperature  
104°C  
101°C  
110°C  
(219.2°F)  
(213.8°F)  
(230°F)  
2. CURRENT RELEASE CONTROL  
The compressor frequency is controlled so that the outdoor unit input current does not exceed  
the current limit value that was set up with the outdoor temperature.  
The compressor frequency returns to the designated frequency of the indoor unit at the time  
when the frequency becomes lower than the release value.  
( Table 21 : Current release operation value / Release value )  
[ Heating ]  
[ Heating ]  
AOU09RL2  
AOU12RL2  
OT (Control / Release)  
OT (Control / Release)  
10.5A / 10.0A  
11.0A / 10.5A  
17°C (62.6°F)  
17°C (62.6°F)  
12.0A / 11.5A  
14.0A / 13.5A  
14.5A / 13.5A  
12.0A / 11.5A  
12.5A / 12.0A  
12.5A / 12.0A  
12°C (53.6°F)  
C (41°F)  
12°C (53.6°F)  
C (41°F)  
OT : Outdoor Temperature  
OT : Outdoor Temperature  
[ Cooling ]  
[ Cooling ]  
AOU09RL2  
AOU12RL2  
OT (Control / Release)  
8.0A / 7.5A  
OT (Control / Release)  
9.0A / 8.5A  
46°C (114.8°F)  
46°C (114.8°F)  
9.0A / 8.5A  
10.0A / 9.5A  
40°C (104°F)  
40°C (104°F)  
12.0A / 11.5A  
12.0A / 11.5A  
OT : Outdoor Temperature  
OT : Outdoor Temperature  
01-16  
3. ANTIFREEZING CONTROL (Cooling and Dry mode)  
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger  
temperature sensor detects the temperature lower than Temperature .  
Then, the anti-freezing control is released when it becomes higher than Temperature .  
(Table 22 : Anti-freezing Protection Operation / Release Temperature)  
Outdoor temperature  
Temperature  
Temperature  
7°C (44.6°F)  
Over than 10°C (50°F)*1  
or 12°C (53.6°F) *2  
4°C (39.2°F)  
Less than 10°C(50°F) *1  
or 12°C (53.6°F) *2  
13°C (55.4°F)  
*1. When the temperature rises.  
*2. When the temperature drops.  
4. COOLING PRESSURE OVERRISE PROTECTION  
When the outdoor unit heat exchange sensor temperature rises to 67°C (152.6°F) or greater,  
the compressor and the outdoor fan motor are stopped and trouble display is performed.  
5. HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )  
On heating mode, the compressor frequency is controlled as following based on the  
detection value of the indoor heat exchanger temperature sensor.  
[ Control System ]  
Indoor heat exchange  
temperature rises  
Compressor is stopped  
63°C (145.4°F)  
The compressor frequency is  
decreased 25rps every 120seconds.  
55°C (131°F)  
The compressor frequency is  
decreased 3rps every 60seconds.  
53°C (127.4°F)  
Stable zone  
50°C (122°F)  
It returns to the normal operation  
Indoor heat exchange  
temperature drops  
01-17  
WALL MOUNTED type  
INVERTER  
2 . TROUBLE SHOOTING  
2. TROUBLESHOOTING  
2-1 ERROR DISPLAY  
Please refer the flashing pattern as follows.  
Indoor Unit : ASU09/ 12RL2  
The Operation, Timer and Economy lamps operate as follows according to the error contents.  
Indoor Unit Display  
Trouble  
shooting  
Error Contents  
[
]
[
]
[
]
Economy  
Operation  
Timer  
(Green)  
(Green)  
(Orange)  
1 times  
1 times  
Continuous  
Serial communication error  
1
2
3 times  
3 times  
4 times  
4 times  
5 times  
6 times  
6 times  
6 times  
7 times  
7 times  
7 times  
8 times  
9 times  
9 times  
9 times  
9 times  
10 times  
2 times  
5 times  
1 times  
2 times  
1 times  
2 times  
Continuous  
Continuous  
Continuous  
Continuous  
Continuous  
Continuous  
Continuous  
Indoor unit PCB model information error  
Manual auto switch error  
3
Room temp. sensor error  
4
Indoor unit Heat Ex. middle temp.  
sensor error  
5
Indoor unit fan motor error  
6
Outdoor unit main PCB model  
information error or communication error  
7
8
PFC circuit error  
4 times  
5 times  
1 times  
3 times  
4 times  
Trip terminal L error  
9
Continuous  
Continuous  
Discharge temp. sensor error  
10  
11  
12  
13  
14  
15  
16  
17  
18  
Outdoor unit Heat Ex. liquid temp.  
sensor error  
Continuous  
Continuous  
Continuous  
Outdoor temp. sensor error  
Current sensor error  
4 times  
4 times  
5 times  
7 times  
9 times  
1 times  
Trip detection  
Continuous  
Continuous  
Continuous  
Continuous  
Continuous  
Compressor rotor position detection error  
Outdoor unit fan motor error  
4-way valve error  
Discharge temp. error  
02-01  
2-2 TROUBLE SHOOTING WITH ERROR CODE  
Trouble shooting 1-1  
Indicate or Display:  
OUTDOOR UNIT Error Method:  
Refer to error code table.  
Serial communication error  
(Serial Reverse Transfer Error)  
Detective details:  
Detective Actuators:  
When the indoor unit cannot receive the serial signal from Outdoor unit  
more than 2minutes after power ON, or the indoor unit cannot receive  
the serial signal more than 15seconds during normal operation.  
Outdoor unit Main PCB  
Forecast of Cause:  
1. Connection failure  
2. External cause  
3. Main PCB failure  
Check Point 1-1 : Reset the power and operate  
Does Error indication show again?  
NO  
YES  
Check Point 2 : Check Connection  
Check Point 1-2: Check external cause such as noise  
Check any loose or removed connection line of  
Indoor unit and Outdoor unit.  
>> If there is an abnormal condition, correct it by  
referring to Installation Manual or Data &  
Technical Manual.  
Check the complete insulation of the grounding.  
Check if there is any equipment that causes harmonic wave  
near the power cable (Neon light bulb or any electronic  
equipment which causes harmonic wave).  
OK  
Check Point 3 : Check the voltage of power supply  
Check the voltage of power supply  
>> Check if AC103V (AC115V -10%) - 127V (AC115V +10%) appears  
at Outdoor Unit Terminal L - N.  
OK  
Check Point 4 : Check Serial Signal (Reverse Transfer Signal)  
Check Serial Signal (Reverse Transfer Signal)  
>> Check if Indicated value swings between AC45V and AC135V at Outdoor Unit Terminal 1 - 3.  
>> If it is abnormal, replace Main PCB.  
GREEN  
WHITE  
N
BLACK  
L
RED  
+
-
3
WHITE  
2
BLACK  
1
02-02  
Trouble shooting 1-2  
Indicate or Display:  
INDOOR UNIT Error Method:  
Refer to error code table.  
Serial communication error  
(Serial Forward Transfer Error)  
Detective details:  
Detective Actuators:  
When the outdoor unit cannot receive the serial signal from Indoor unit  
more than 10seconds.  
Indoor unit Controller PCB  
Indoor unit Fan motor  
Forecast of Cause:  
1. Connection failure 2. External cause 3. Controller PCB failure 4. Indoor unit fan motor failure  
Check Point 1-1 : Reset the power and operate  
NO  
Does Error indication show again?  
YES  
Check Point 2 : Check Connection  
Check Point 1-2: Check external cause such as noise  
Check the complete insulation of the grounding.  
Check any loose or removed connection line of  
Indoor unit and Outdoor unit.  
>> If there is an abnormal condition, correct it by  
referring to Installation Manual or Data &  
Technical Manual.  
Check if there is any equipment that causes harmonic wave  
near the power cable (Neon light bulb or any electronic  
equipment which causes harmonic wave).  
OK  
Check Point 3 : Check the voltage of power supply  
Check the voltage of power supply  
>> Check if AC103V (AC115V -10%) - 127V (AC115V +10%) appears  
at Outdoor Unit Terminal L - N.  
OK  
Check Point 4 : Check Serial Signal (Reverse Transfer Signal)  
Check Serial Signal (Forward Transfer Signal)  
>> Check if Indicated value swings between AC30V and AC130V at Outdoor Unit Terminal 2 - 3.  
>> If it is abnormal, replace Controller PCB.  
>> If it is abnormal, Check Indoor unit fan motor. (PARTS INFORMATION 4)  
>> If Indoor unit fan motor is abnormal, replace Indoor unit fan motor and Controller PCB.  
GREEN  
WHITE  
N
BLACK  
L
+
-
RED  
3
2
1
WHITE  
BLACK  
02-03  
Trouble shooting 2  
INDOOR UNIT Error Method:  
Indicate or Display:  
Refer to error code table.  
Indoor unit PCB model information  
error  
Detective details:  
Detective Actuators:  
When power is on and there is some below case.  
1. When model information of EEPROM is incorrect.  
2. When the access to EEPROM failed.  
Indoor unit Controller PCB  
Forecast of Cause:  
1. External cause 2. Defective connection of electric components 3. Controller PCB failure  
Check Point 1-1 : Reset Power Supply and operate  
NO  
Does Error indication show again?  
YES  
Check Point 1-2 :  
Check external cause such as noise  
Check Point 2 :  
Check Indoor unit electric components  
Check all connectors.  
Check if the ground connection is proper.  
(loose connector or incorrect wiring)  
Check if there is any equipment that causes harmonic wave  
near the power cable (Neon light bulb or any electronic  
equipment which causes harmonic wave).  
Check any shortage or corrosion on PCB.  
Check Point 3 : Replace Controller PCB  
Change Controller PCB.  
Note : EEPROM  
EEPROM(Electronically Erasable and  
Programmable Read Only Memory) is a non-  
volatile memory which keeps memorized  
information even if power is turned off. It can  
change the contents electronically.  
To change the contents, it uses higher  
voltage than normal, and it can not change a  
partial contents. (Rewriting shall be done  
upon erasing the all contents.)  
There is a limit in a number of rewriting.  
02-04  
Trouble shooting 3  
Indicate or Display:  
INDOOR UNIT Error Method:  
INDOOR UNIT  
Refer to error code table.  
Manual auto switch error  
Detective Actuators:  
Detective details:  
When the Manual auto switch becomes ON for consecutive 60 or  
more seconds.  
Indoor unit Controller PCB  
Indicator PCB  
Manual auto switch  
Forecast of Cause :  
1. Manual auto switch failure 2.Controller PCB and Indicator PCB failure  
Check Point 1 : Check the Manual auto switch  
Check if Manual auto switch is kept pressed.  
Check ON/OFF switching operation by using a meter.  
>>If Manual Auto Switch is disabled (on/off switching), replace it.  
OK  
Check Point 2 : Replace Controller PCB  
If Check Point 1 do not improve the symptom, change Controller PCB and Indicator PCB.  
02-05  
Indicate or Display:  
Trouble shooting 4  
INDOOR UNIT Error Method:  
INDOOR UNIT  
Refer to error code table.  
Room temp. sensor error  
Detective details:  
Detective Actuators:  
When Room temperature thermistor open or short-circuit is detected.  
Indoor unit Controller PCB  
Room temperature thermistor  
Forecast of Cause :  
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure  
Check Point 1 : Check connection of Connector  
Check if connector is removed.  
Check erroneous connection.  
Check if thermistor cable is open.  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
Chheecckk PPooiinntt22:: Remove connector and check Thermistor resistance value  
Thermistor Characteristics (Approx. value)  
-10°C  
-5°C  
0°C  
5°C  
10°C  
15°C  
20°C  
25°C  
Temperature  
(14°F) (23°F) (32°F) (41°F) (50°F) (59°F) (68°F) (77°F)  
Resistance Value (k )  
55.46 42.36 32.67  
30°C 35°C 40°C  
25.39 19.91  
45°C  
15.71  
12.5  
10.0  
Temperature  
(86°F) (95°F) (104°F) (113°F)  
Resistance Value (k )  
8.051 6.52 5.316 4.354  
If Thermistor is either open or shorted, replace it and reset the power.  
OK  
Chheecckk PPooiinntt33:: Check voltage of Controller PCB (DC5.0V)  
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)  
THERMISTOR  
(PIPE)  
BLACK  
1 1  
BLACK  
2 2  
CN4  
BLACK  
BLACK  
3 3  
4 4  
THERMISTOR  
(ROOM TEMP.)  
If the voltage does not appear, replace Controller PCB.  
02-06  
Trouble shooting 5  
Indicate or Display:  
INDOOR UNIT Error Method:  
INDOOR UNIT  
Indoor unit Heat Ex. middle temp.  
sensor error  
Refer to error code table.  
Detective Actuators:  
Detective details:  
When Heat Ex. temperature thermistor open or short-circuit is detected.  
Indoor unit Controller PCB  
Heat Ex. temperature thermistor  
Forecast of Cause :  
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure  
Check Point 1 : Check connection of Connector  
Check if connector is removed.  
Check erroneous connection.  
Check if thermistor cable is open.  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
Chheecckk PPooiinntt22:: Remove connector and check Thermistor resistance value  
Thermistor Characteristics (Approx. value)  
-10°C  
-5°C  
0°C  
5°C  
10°C  
20°C  
Temperature  
(14°F) (23°F) (32°F) (41°F) (50°F) (68°F)  
Resistance Value (k )  
295.1  
30°C  
223.3 170.7 131.4  
40°C 50°C 60°C  
102.1  
63°C  
62.9  
Temperature  
(86°F) (104°F) (122°F) (140°F) (144°F)  
Resistance Value (k )  
39.78 25.8 17.11 11.6 10.36  
If Thermistor is either open or shorted, replace it and reset the power.  
OK  
Check Point 3 : Check voltage of Controller PCB (DC5.0V)  
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)  
THERMISTOR  
(PIPE)  
BLACK  
1 1  
BLACK  
2 2  
CN4  
BLACK  
BLACK  
3 3  
4 4  
THERMISTOR  
(ROOM TEMP.)  
If the voltage does not appear, replace Controller PCB.  
02-07  
Trouble shooting 6  
Indicate or Display:  
INDOOR UNIT Error Method:  
Refer to error code table.  
Indoor unit fan motor error  
Detective Actuators:  
Detective details:  
When the condition that actual frequency of Indoor Fan is  
below 1/3 of target frequency is continued more than 56 seconds.  
Indoor unit Controller PCB  
Indoor unit Fan motor  
Forecast of Cause:  
1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temperature rise  
4. Control PCB failure 5. Indoor unit fan motor failure  
Check Point 1 : Check rotation of Fan  
Rotate the fan by hand when operation is off.  
(Check if fan is caught, dropped off or locked motor)  
>>If Fan or Bearing is abnormal, replace it.  
OK  
Check Point 2 : Check ambient temp. around motor  
Check excessively high temperature around the motor.  
(If there is any surrounding equipment that causes heat)  
>>Upon the temperature coming down, restart operation.  
OK  
Check Point 3 : Check Indoor unit fan motor  
Check Indoor unit fan motor. (PARTS INFORMATION 4)  
>>If Indoor unit fan motor is abnormal, replace Indoor unit fan motor.  
OK  
Check Point 4 : Replace Controller PCB  
If Check Point 1- 3 do not improve the symptom, replace Controller PCB.  
02-08  
Trouble shooting 7  
OUTDOOR UNIT Error Method:  
Indicate or Display:  
Refer to error code table.  
Outdoor unit main PCB model  
information error or communication error  
Detective details:  
Detective Actuators:  
When model information of EEPROM is incorrect at power ON.  
If the above operation is repeated 3 times,  
Outdoor unit Main PCB  
the compressor stops permanently.  
Forecast of Cause:  
1. External cause (Noise, temporary open, voltage drop) 2. Main PCB failure  
Check Point 1-1 : Reset Power supply and operate  
NO  
Does Error indication show again?  
YES  
Check Point 1-2 : Check external cause  
Check Point 2 : Replace Main PCB  
Check if temporary voltage drop was not generated.  
Check if momentary open was not generated.  
Check if ground is connection correctly or there are no related  
cables near the power line.  
Change Main PCB.  
02-09  
Trouble shooting 8  
Indicate or Display:  
OUTDOOR UNIT Error Method:  
INDOOR UNIT  
Refer to error code table.  
PFC circuit error  
Detective Actuators:  
Detective details:  
When inverter output DC voltage is higher than 415V for over 3 seconds,  
the compressor stops.  
Outdoor unit Main PCB  
If the same operation is repeated 5 times, the compressor stops permanently.  
Forecast of Cause :  
1. External cause 2. Connector connection failure 3. Main PCB failure  
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)  
Instant drop : Check if there is a large load electric apparatus in the same circuit.  
Momentary power failure : Check if there is a defective contact or leak current  
in the power supply circuit.  
Noise : Check if there is any equipment causing harmonic wave near electric line.  
(Neon bulb or electric equipment that may cause harmonic wave)  
Check the complete insulation of grounding.  
OK  
Check Point 2 : Check connection of Connector  
Check if connector is removed.  
Check erroneous connection.  
Check if cable is open.  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
Check Point 3 : Replace Main PCB  
If Check Point 1, 2 do not improve the symptom, change Main PCB.  
02-10  
Trouble shooting 9  
Indicate or Display:  
OUTDOOR UNIT Error Method:  
Refer to error code table.  
Trip terminal L error  
Detective details:  
Detective Actuators:  
When the signal from FO terminal of IPM in Main PCB is "L"(=0V)  
while the compressor stops.  
Outdoor unit Main PCB  
Forecast of Cause :  
1. Main PCB failure  
Check Point 1 : Replace Main PCB  
Change Main PCB.  
02-11  
Trouble shooting 10  
Indicate or Display:  
OUTDOOR UNIT Error Method:  
INDOOR UNIT  
Refer to error code table.  
Discharge temp. sensor error  
Detective details:  
Detective Actuators:  
When Discharge pipe temperature thermistor open or short-circuit  
is detected at power ON or while running the compressor.  
Outdoor unit Main PCB  
Discharge pipe temperature thermistor  
Forecast of Cause :  
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure  
Check Point 1 : Check connection of Connector  
Check if connector is removed.  
Check erroneous connection.  
Check if thermistor cable is open.  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
CChhecckk PPooiinntt 22:: Remove connector and check Thermistor resistance value  
Thermistor Characteristics (Approx. value)  
-10°C -5°C  
0°C  
5°C  
10°C 20°C 30°C  
Temperature  
(14°F) (23°F) (32°F) (41°F) (50°F) (68°F) (86°F)  
41.33  
286.3 218.6 168.6 130.9 102.5 64.22  
Resistance Value (k )  
40°C 50°C 60°C 70°C 80°C 90°C 100°C 110°C 120°C  
(104°F)(122°F)(140°F)(158°F) (176°F)(194°F)(212°F)(230°F)(248°F)  
Temperature  
Resistance Value (k )  
27.26 18.40 12.68 8.909 6.375 4.639 3.430 2.573 1.956  
If Thermistor is either open or shorted, replace it and reset the power.  
OK  
Check Point 3 :  
Check Point 3 : Check voltage of Main PCB (DC5.0V)  
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)  
THERMISTOR  
(PIPE)  
BLACK  
1 1  
BLACK  
2 2  
BLACK  
BLACK  
CN71  
3 3  
4 4  
THERMISTOR  
(DISCHARGE)  
THERMISTOR  
(OUTDOOR)  
BLACK  
BLACK  
1 1  
2 2 CN70  
3 3  
If the voltage does not appear, replace Main PCB.  
02-12  
Trouble shooting 11  
Indicate or Display:  
OUTDOOR UNIT Error Method:  
Refer to error code table.  
Outdoor unit Heat Ex. liquid temp.  
sensor error  
Detective details:  
Detective Actuators:  
Outdoor unit Main PCB  
When Heat exchanger temperature thermistor open or  
Heat exchanger temperature thermistor  
short-circuit is detected at power ON or while running the compressor.  
Forecast of Cause :  
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure  
Check Point 1 : Check connection of Connector  
Check if connector is removed.  
Check erroneous connection.  
Check if thermistor cable is open.  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
CChhecckk PPooiinntt 22:: Remove connector and check Thermistor resistance value  
Thermistor Characteristics (Approx. value)  
-10°C -5°C  
0°C  
5°C 10°C 20°C 30°C  
Temperature  
(14°F) (23°F) (32°F) (41°F) (50°F) (68°F) (86°F)  
3.947  
Resistance Value (k )  
27.21 20.80 16.05 12.47 9.775 6.129  
40°C 50°C 60°C 70°C 80°C  
(104°F)(122°F)(140°F)(158°F)(176°F)  
Temperature  
Resistance Value (k )  
2.606 1.759 1.213 0.8531 0.6115  
If Thermistor is either open or shorted, replace it and reset the power.  
OK  
Check Point 3 :  
Check Point 3 : Check voltage of Main PCB (DC5.0V)  
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)  
THERMISTOR  
(PIPE)  
BLACK  
1 1  
BLACK  
2 2  
BLACK  
BLACK  
CN71  
3 3  
4 4  
THERMISTOR  
(DISCHARGE)  
THERMISTOR  
(OUTDOOR)  
BLACK  
BLACK  
1 1  
2 2 CN70  
3 3  
If the voltage does not appear, replace Main PCB.  
02-13  
Indicate or Display:  
Trouble shooting 12  
OUTDOOR UNIT Error Method:  
Refer to error code table.  
Outdoor temp. sensor error  
Detective details:  
Detective Actuators:  
Outdoor unit Main PCB  
Outdoor temperature thermistor  
When Outdoor temperature thermistor open or short-circuit is  
detected at power ON or while running the compressor.  
Forecast of Cause :  
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure  
Check Point 1 : Check connection of Connector  
Check if connector is removed.  
Check erroneous connection.  
Check if thermistor cable is open.  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
CChhecckk PPooiinntt 22:: Remove connector and check Thermistor resistance value  
Thermistor Characteristics (Approx. value)  
-20°C -15°C -10°C -5°C  
(4.0°F) (5°F) (14°F) (23°F) (32°F) (41°F) (50°F)  
0°C  
5°C 10°C  
Temperature  
20.56  
109.0 80.56 60.23 45.40 34.57 26.53  
Resistance Value (k )  
15°C 20°C 25°C 30°C 35°C 40°C 45°C 50°C 55°C  
(59°F) (68°F) (77°F) (86°F) (95°F) (104°F)(113°F) (122°F)(131°F)  
Temperature  
Resistance Value (k )  
16.04 12.26 10.00 7.978 6.408 5.184 4.216 3.451 2.841  
If Thermistor is either open or shorted, replace it and reset the power.  
OK  
Check Point 3 :  
Check Point 3 : Check voltage of Main PCB (DC5.0V)  
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)  
THERMISTOR  
(PIPE)  
BLACK  
1 1  
BLACK  
2 2  
BLACK  
BLACK  
CN71  
3 3  
4 4  
THERMISTOR  
(DISCHARGE)  
THERMISTOR  
(OUTDOOR)  
BLACK  
BLACK  
1 1  
2 2 CN70  
3 3  
If the voltage does not appear, replace Main PCB.  
02-14  
Trouble shooting 13  
Indicate or Display:  
OUTDOOR UNIT Error Method:  
Refer to error code table.  
Current sensor error  
Detective details:  
Detective Actuators:  
When Input Current Sensor has detected 0A, while Inverter Compressor is  
operating at higher than 56rps, after 1minute upon starting the Compressor.  
(Except during the defrost operation)  
Outdoor unit Main PCB  
Forecast of Cause :  
1. Defective connection of electric components  
2. External cause  
3. Main PCB failure  
Check Point 1-1 : Reset Power Supply and operate  
Does Error indication show again?  
NO  
YES  
Check Point 2 :  
Check Point 1-2 :  
Check connections of Outdoor Unit Electrical Components  
Check external cause at Indoor and Outdoor  
(Voltage drop or Noise)  
Check if the terminal connection is loose.  
Check if connector is removed.  
Check erroneous connection.  
Check if cable is open.  
>>Upon correcting the removed connector or mis-wiring,  
reset the power.  
Instant drop : Check if there is a large load electric  
apparatus in the same circuit.  
Momentary power failure : Check if there is a defective  
contact or leak current in the  
power supply circuit.  
Noise : Check if there is any equipment causing harmonic  
wave near electric line.(Neon bulb or electric  
equipment that may cause harmonic wave)  
Check the complete insulation of grounding.  
OK  
Check Point 4 : Replace Main PCB  
If Check Point 1, 2 do not improve the symptom, change Main PCB.  
02-15  
Trouble shooting 14  
Indicate or Display:  
OUTDOOR UNIT Error Method:  
Refer to error code table.  
Trip detection  
Detective details:  
Detective Actuators:  
When more than normal operating current to IPM in Main PCB flows,  
the compressor stops.  
After the compressor restarts, if the same operation is repeated  
within 40sec, the compressor stops again.  
Outdoor unit Main PCB  
Compressor  
If  
and  
repeats 5 times, the compressor stops permanently.  
Forecast of Cause :  
1. Defective connection of electric components 2. Outdoor heat exchanger clogged 3. Compressor failure  
4. Main PCB failure  
Check Point 1 : Check connections of Outdoor unit electrical components  
Check if the terminal connection is loose.  
Check if connector is removed.  
Check erroneous connection.  
Check if cable is open.  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
Check Point 2 : Check Heat exchanger  
Is there anything obstructing the air distribution circuit?  
Is there any clogging of Outdoor Heat Exchanger?  
OK  
Check Point 3 : Check Compressor  
Check Compressor. (PARTS INFORMATION 2)  
OK  
Check Point 4 : Replace Main PCB  
If Check Point 1 ~ 3 do not improve the symptom, change Main PCB.  
02-16  
Trouble shooting 15  
Indicate or Display:  
OUTDOOR UNIT Error Method:  
Refer to error code table.  
Compressor rotor position  
detection error  
Detective details:  
Detective Actuators:  
If the detected rotor location is out of phase with actual rotor location  
more than 90°, the compressor stops.  
After the compressor restarts, if the same operation is repeated  
within 40sec, the compressor stops again.  
Outdoor unit Main PCB  
Compressor  
If  
and  
repeats 5 times, the compressor stops permanently.  
Forecast of Cause :  
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure  
Check Point 1 : Check Noise from Compressor  
Turn on Power and check operation noise.  
If an abnormal noise show, replace Compressor.  
OK  
Check Point 2 : Check connection of around the Compressor components  
For Compressor Terminal, Main PCB  
Check if connector is removed.  
Check erroneous connection.  
Check if cable is open.  
(Refer to PARTS INFORMATION 2)  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
Check Point 3: Replace Main PCB  
If Check Point 1,2 do not improve the symptom, change Main PCB.  
OK  
Check Point 4: Replace Compressor  
If Check Point 3 do not improve the symptom, change Compressor.  
02-17  
Trouble shooting 16  
Indicate or Display:  
OUTDOOR UNIT Error Method:  
Refer to error code table.  
Outdoor unit fan motor error  
Detective details:  
Detective Actuators:  
When outdoor fan rotation speed is less than 100rpm in 20 seconds  
after fan motor starts, fan motor stops.  
After fan motor restarts, if the same operation within 60sec is repeated  
3 times in a row, compressor and fan motor stops.  
Outdoor unit Main PCB  
Outdoor unit Fan motor  
If  
and  
repeats 5 times in a row, compressor and fan motor stops  
permanently.  
Forecast of Cause:  
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Main PCB failure  
4. Outdoor unit fan motor  
Check Point 1 : Check rotation of Fan  
Rotate the fan by hand when operation is off.  
(Check if fan is caught, dropped off or locked motor)  
>>If Fan or Bearing is abnormal, replace it.  
OK  
Check Point 2 : Check ambient temp. around motor  
Check excessively high temperature around the motor.  
(If there is any surrounding equipment that causes heat)  
>>Upon the temperature coming down, restart operation.  
OK  
Check Point 3 : Check Outdoor unit fan motor  
Check Outdoor unit fan motor. (PARTS INFORMATION 5)  
>>If Outdoor unit fan motor is abnormal, replace Outdoor unit fan motor.  
OK  
Check Point 4 : Check Output Voltage of Main PCB  
Check outdoor unit circuit diagram and the voltage.  
(Measure at Main PCB side connector)  
RED  
1
FAN MOTOR  
2
3
BLACK  
WHITE  
YELLOW  
BROWN or BLUE  
CN800  
4
5
6
7
FM  
Read wire  
Red - Black  
White - Black  
DC voltage  
290V (AC115V-10%)~ 360V (AC115+10%)  
15 1.5V  
If the voltage is not correct, replace Main PCB.  
02-18  
Trouble shooting 17  
Indicate or Display:  
INDOOR UNIT Error Method:  
Refer to error code table.  
4-way valve error  
Detective Actuators:  
Detective details:  
When the indoor heat exchanger temperature is compared with  
the room temperature, and either following condition is detected  
continuously two times, the compressor stops.  
Indoor unit Controller PCB  
Heat Ex. temperature thermistor  
Room temperature thermistor  
4-way valve  
Cooling or Dry operation  
[Indoor heat exchanger temp.] - [Room temp.] > 10degC (20°F)  
Heating operation  
[Indoor heat exchanger temp.] - [room temp.] < - 10degC (-20°F)  
If the same operation is repeated 5 times,  
the compressor stops permanently.  
Forecast of Cause :  
1. Connector connection failure 2. Thermistor failure 3. Coil failure 4. 4-way valve failure  
5. Controller PCB failure  
Check Point 1 : Check connection of Connector  
Check if connector is removed.  
Check erroneous connection.  
Check if thermistor cable is open.  
>> Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
Check Point 2 : Check each thermistor  
Isn’t it fallen off the holder?  
Is there a cable pinched?  
>> Check characteristics of thermistor (Refer to Trouble shooting 5, 6),  
If defective, replace the thermistor  
OK  
Check Point 3 : Check the solenoid coil and 4-way valve  
[ Solenoid coil ]  
Remove CN30 from PCB and check the resistance value of coil.  
Resistance value is 1.88k  
2.29k (at 20°C (68°F)).  
>> If it is Open or abnormal resistance value, replace Solenoid Coil.  
[ 4-way valve ]  
Check each piping temperature,  
and the location of the valve by the temperature difference.  
>> If the value location is not proper, replace 4-way valve.  
OK  
Check Point 4 : Replace Controller PCB  
If Check Point 1- 3 do not improve the symptom, replace Controller PCB.  
02-19  
Trouble shooting 18  
Indicate or Display:  
OUTDOOR UNIT Error Method:  
INDOOR UNIT  
Discharge temperature error  
Refer to error code table.  
Detective details:  
Detective Actuators:  
"Protection stop by "discharge temperature  
110degC during compressor  
Outdoor unit Main PCB  
operation"" generated 2 times within 24 hours.  
Discharge temperature thermistor  
Forecast of Cause :  
1. 2/ 3-way valve not opened  
2. Capillary tube, strainer clogged  
3. Outdoor unit operation failure, foreign matter on heat exchanger  
4. Discharge temperature thermistor failure  
6. Main PCB failure  
5. Insufficient refrigerant  
<Cooling operation>  
<Heating operation>  
Check Point 1 : Check if 3-way valve(gas side) is open.  
Check Point 1 : Check if 2-way valve(liquid side) is open.  
If the 3-way valve(gas side) was closed, open the  
3-way valve(gas side) and check operation.  
If the 2-way valve(liquid side) was closed, open the  
2-way valve(liquid side) and check operation.  
OK  
OK  
Check Point 2 : Check the capillary tube, strainer  
Check Point 2 : Check the capillary tube, strainer  
Capillary tube, Strainer(after Capillary) clogging check.  
Refer to "Service Parts Information 3".  
Capillary tube, Strainer(before Capillary) clogging check.  
Refer to "Service Parts Information 3".  
OK  
Check Point 3 : Check the outdoor unit fan,heat exchanger  
OK  
Check for foreign object at heat exchanger  
Check if fan can be rotated by hand.  
Motor check (PARTS INFORMATION 5)  
OK  
Check Point 4 : Check the discharge thermistor  
Discharger thermistor characteristics check.  
(Check by disconnecting thermistor from PCB.)  
* For the characteristics of the thermistor, refer to the "Trouble shooting 10".  
OK  
Check Point 5 : Check the refrigerant amount  
Leak check  
02-20  
2-3 TROUBLE SHOOTING WITH NO ERROR CODE  
Forecast of Cause:  
Trouble shooting 19  
1. Power supply failure 2. External cause  
3. Electrical components defective  
Indoor Unit - No Power  
Check Point 1 : Check Installation Condition  
Isn’t the breaker down?  
Check loose or removed connection cable.  
>>If abnormal condition is found, correct it by referring  
to Installation Manual or Data & Technical Manual.  
OK  
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)  
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.  
Momentary power failure ----- Check if there is a defective contact or leak current in  
the power supply circuit.  
Noise ----- Check if there is any equipment causing harmonic wave near electric line.  
(Neon bulb or electric equipment that may cause harmonic wave)  
Check the complete insulation of grounding.  
OK  
Check Point 3 : Check Electrical Components  
NO  
Check the voltage of power supply.  
>> Check if AC103 - 127V appears at Outdoor Unit Terminal L - N.  
YES  
Check Fuse in Main PCB.  
>> If Fuse is open, check if the wiring between Terminal and Main PCB  
is loose, and replace Fuse.  
Check Varistor in Main PCB.  
>> If Varistor is defective, there is a possibility of an abnormal power supply.  
Check the correct power supply and replace Varistor.  
Upon checking the normal power supply, replace Varistor.  
02-21  
Forecast of Cause:  
Trouble shooting 20  
1. Power supply failure 2. External cause  
3. Electrical Components defective  
Outdoor Unit - No Power  
Check Point 1 : Check Installation Condition  
Isn’t the breaker down?  
Check loose or removed connection cable.  
>>If abnormal condition is found, correct it by referring  
to Installation Manual or Data & Technical Manual.  
OK  
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)  
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.  
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.  
Noise ----- Check if there is any equipment causing harmonic wave near electric line.  
(Neon bulb or electric equipment that may cause harmonic wave)  
Check the complete insulation of grounding.  
OK  
Check Point 3 : Check Electrical Components  
NO  
Check the voltage of power supply.  
>> Check if AC103 - 127V appears at Outdoor Unit Terminal L - N.  
YES  
Check Fuse in Main PCB.  
>> If Fuse is open, check if the wiring between Terminal and Main PCB is loose,  
and replace Fuse.  
Check Varistor in Main PCB.  
>> If Varistor is defective, there is a possibility of an abnormal power supply.  
Check the correct power supply and replace Varistor.  
Upon checking the normal power supply, replace Varistor.  
OK  
If the symptom does not change by above Check 3, replace Main PCB.  
02-22  
Forecast of Cause:  
Trouble shooting 21  
1. Setting/ Connection failure 2. External cause  
3. Electrical component defective  
No Operation (Power is ON)  
Check Point 1 : Check indoor and outdoor installation condition  
Are these Indoor Unit, Outdoor Unit, and Remote Control suitable model numbers to connect?  
>> If there is some abnormal condition, correct it by referring to Installation manual and  
Data & Technical Manual.  
OK  
Turn off Power and check/ correct followings.  
Is there loose or removed communication line of Indoor Unit and Outdoor Unit?  
OK  
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)  
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.  
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.  
Noise ----- Check if there is any equipment causing harmonic wave near electric line.  
(Neon bulb or electric equipment that may cause harmonic wave)  
Check the complete insulation of grounding.  
OK  
If the symptom does not change by above Check 1, 2, replace Main PCB.  
02-23  
Forecast of Cause:  
Trouble shooting 22  
1. Indoor Unit error 2. Outdoor unit error  
3. Effect by surrounding environment  
No Cooling / No Heating  
4. Connection pipe / Connection wire failure 5. Refrigeration cycle failure  
Check Point 1 : Check Indoor unit  
Does Indoor unit Fan run on High fan?  
Is Air filter dirty?  
Is Heat exchanger clogged?  
Check if Energy save function is operated.  
OK  
Check Point 2 : Check Outdoor unit operation  
Check if Outdoor unit is operating  
Check any objects that obstruct the air flow route.  
Check clogged Heat Exchanger.  
Is the Valve open?  
OK  
Attention  
Check Point 3 : Check Site condition  
Strainer normally does not have temperature difference  
between inlet and outlet as shown in , but if there is a  
difference like shown in , there is a possibility of inside  
clogged. In this case, replace Strainer.  
Is capacity of Indoor unit fitted to room size?  
Any windows open? or direct sunlight ?  
OK  
Pipe (In)  
Pipe (Out)  
Check Point 4 :  
Check Indoor/ Outdoor installation condition  
Check connection pipe  
(specified pipe length & Pipe diameter?)  
Check any loose or removed communication line.  
>> If there is an abnormal condition, correct it by  
referring to Installation Manual or Data & Technical  
Manual.  
MPa MPa  
OK  
Pipe (In)  
Pipe (Out)  
Check Point 5 : Check Refrigeration cycle  
Check if Strainer is clogged (Refer to the figure at right).  
Measure Gas pressure and if there is a leakage, correct it.  
>> When recharging the refrigerant, make sure to perform  
vacuuming, and recharge the specified amount.  
Check Capillary tube (PARTS INFORMATION 3)  
Check Compressor (PARTS INFORMATION 1,2)  
02-24  
Forecast of Cause :  
Trouble shooting 23  
1. Abnormal installation (Indoor/ Outdoor)  
2. Fan failure (Indoor/ Outdoor)  
Abnormal Noise  
3. Compressor failure (Outdoor)  
Diagnosis method when abnormal noise is occurred  
Abnormal noise is coming from Indoor unit.  
(Check and correct followings)  
Abnormal noise is coming from Outdoor unit.  
(Check and correct followings)  
Is Main unit installed in stable condition?  
Is Fan guard installed normally?  
Is Main unit installed in stable condition?  
Is the installation of air suction grille and  
front panel normal?  
OK  
OK  
Is Fan broken or deformed?  
Is the screw of Fan loose?  
Is there any object which obstruct the Fan rotation?  
Is Fan broken or deformed?  
Is the screw of Fan loose?  
OK  
Is there any object which obstruct the Fan rotation?  
Check if vibration noise by loose bolt or contact noise  
of piping is happening.  
OK  
Is Compressor locked?  
>> Check Compressor (PARTS INFORMATION 1,2)  
Forecast of Cause:  
1. Erroneous installation 2. Drain hose failure  
Trouble shooting 24  
Water Leaking  
Diagnosis method when water is spitting out.  
Is the filter clogged?  
Diagnosis method when water leak occurs  
Is Main unit installed in stable condition?  
Is Main unit broken or deformed at the time of  
transportation or maintenance?  
OK  
OK  
MPa MPa  
Check Gas pressure and correct it  
if there was a gas leak.  
Is Drain hose connection loose?  
Is there a trap in Drain hose?  
Is Drain hose clogged?  
OK  
Is Fan rotating?  
02-25  
2-4 SERVICE PARTS INFORMATION  
SERVICE PARTS INFORMATION 1  
Compressor  
Diagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting )  
Abnormal noise  
Stops soon after starting up  
Does not start up  
Check if vibration noise by  
loose bolt or contact noise  
of piping is happening.  
Is there open or loose connection  
cable?  
Is there open or loose connection  
cable?  
Is Gas pipe valve open?  
(Low pressure is too low)  
Check Main PCB, connection of  
Compressor, and winding resistance.  
(Refer to the next page).  
Defective Compressor  
can be considered.  
(due to inside dirt clogging  
or broken component)  
>> If there is no failure, the defect of  
Compressor is considered (Locked  
compressor due to clogged dirt or  
less oil)  
MPa MPa  
Check if Refrigerant is leaking.  
(Recharge Refrigerant)  
Replace Compressor  
Check if capillary tube, strainer is  
clogged.  
(PARTS INFORMATION 3)  
Replace Compressor  
Check Main PCB, connection of Compressor,and winding  
resistance. (Refer to the next page).  
>> If there is no failure, the defect of Compressor can be  
considered. (Compression part broken or valve defective.)  
Replace Compressor  
02-26  
SERVICE PARTS INFORMATION 2  
Inverter Compressor  
Check Point 1 : Check Connection  
Check terminal connection of Compressor  
(loose or incorrect wiring)  
Terminal cover opened  
C(W)  
(BLACK)  
S(V)  
(WHITE)  
R(U)  
(RED)  
Check Point 2 : Check Winding Resistance  
Check winding resistance of each terminal  
If the resistance value is 0 or infinite, replace Compressor.  
C
Resistance Value :  
1.3 at 20°C (68°F)  
S
R
Check Point 3 : Replace Main PCB  
If the symptom does not change with above Check 1, 2, replace Main PCB.  
02-27  
SERVICE PARTS INFORMATION 3  
Outdoor unit Electronic Expansion Valve  
( EEV )  
Check Point 1 : Check Connections  
Check connection of connector (CN40)  
( Loose connector or open cable )  
EXPANSION  
VALVE COIL  
RED  
BLUE  
ORANGE  
YELLOW  
WHITE  
1 1  
2 2  
3 3  
4 4  
5 5  
EV  
CN40  
Check Point 3 : Check Voltage from Main PCB.  
Check Point 2 : Check Coil of EEV  
DC  
Remove connector, check each winding  
resistance of Coil.  
Remove Connector and check Voltage (DC12V)  
If it does not appear, replace Main PCB.  
Read wire  
White - Red  
Yellow - Red  
Orange - Red  
Blue - Red  
Resistance value  
Check Point 4 : Check Noise at start up  
Turn on Power and check operation noise.  
46  
4
at 20°C  
If an abnormal noise does not show,  
replace Main PCB.  
If Resistance value is abnormal, replace EEV.  
Check Point 5 : Check Opening and Closing Operation of Valve  
If it is open,  
When Valve is closed,  
it has no temp. difference between Inlet and Outlet.  
it has a temp. difference between Inlet and Outlet.  
CLOSE  
Example : Hot Gas  
OPEN  
Example : Hot Gas  
Pipe (In)  
Pipe (In)  
Hi TEMP.  
Hi TEMP.  
Pipe (Out)  
Hi TEMP.  
Pipe (Out)  
Normal TEMP.  
Check Point 6 : Check Strainer  
Strainer normally does not have temperature difference between inlet and outlet as shown in  
,
but if there is a difference as shown in  
, there is a possibility of inside clogged. In this case, replace Strainer.  
Pipe (In)  
Pipe (Out)  
Pipe (In)  
Pipe (Out)  
02-28  
SERVICE PARTS INFORMATION 4  
Indoor unit fan motor  
Check Point 1 : Check rotation of Fan  
Rotate the fan by hand when operation is off.  
(Check if fan is caught, dropped off or locked motor)  
>>If Fan or Bearing is abnormal, replace it.  
Check Point 2 : Check resistance of Indoor Fan Motor  
Refer to below. Circuit-test "Vm" and "GND" terminal.  
(Vm: DC voltage, GND: Earth terminal)  
>>If they are short-circuited (below 300 k ), replace Indoor fan motor and Controller PCB.  
Terminal function  
(symbol)  
Pin number  
(wire color)  
1 (Blue)  
2 (Yellow)  
3 (White)  
4 (Black)  
5
Feed back (FG)  
Speed command (Vsp)  
Control voltage (Vcc)  
Earth terminal (GND)  
No function  
6 (Red)  
DC voltage (Vm)  
SERVICE PARTS INFORMATION 5  
Outdoor unit fan motor  
Check Point 1 : Check rotation of Fan  
Rotate the fan by hand when operation is off.  
(Check if fan is caught, dropped off or locked motor)  
>>If Fan or Bearing is abnormal, replace it.  
Check Point 2 : Check resistance of Outdoor Fan Motor  
Refer to below. Circuit-test "Vm" and "GND" terminal.  
(Vm: DC voltage, GND: Earth terminal)  
>>If they are short-circuited (below 300 k ), replace Outdoor fan motor and Main PCB.  
Terminal function  
(symbol)  
Pin number  
(wire color)  
1 (Red)  
DC voltage (Vm)  
No function  
2
3
No function  
4 (Black)  
5 (White)  
6 (Yellow)  
Earth terminal (GND)  
Control voltage (Vcc)  
Speed command (Vsp)  
7 (Brown or Blue) Feed back (FG)  
02-29  
WALL MOUNTED type  
INVERTER  
3 . APPENDING DATA  
3-1. FUNCTION SETTING  
3-1-1 INDOOR UNIT  
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control,  
in accordance with the installed condition.  
After the power is turned on, perform the Function Setting on the remote control.  
The settings may be selected between the following two: Function Number or Setting Value.  
Settings will not be changed if invalid numbers or setting values are selected.  
1-1. Setting the Filter Sign  
The indoor unit has a sign to inform the user that it is time to clean the filter.  
Select the time setting for the filter sign display interval in the table  
below according to the amount of dust or debris in the room.  
If you do not wish the filter sign to be displayed, select the setting value for "No indication".  
(
Factory setting)  
Setting Description  
Standard (400 hours)  
Long interval (1000 hours)  
Short interval ( 200 hours)  
No indication  
Function Number  
Setting Value  
00  
01  
02  
03  
11  
1-2. Cooling Room Temperature Correction  
Depending on the installed environment, the room temperature sensor may require a correction.  
The settings may be selected as shown in the table below.  
(
Factory setting)  
Setting Description  
Standard  
Function Number  
Setting Value  
00  
01  
02  
03  
Slightly lower control  
Lower control  
30  
Warmer control  
1-3. Heating Room Temperature Correction  
Depending on the installed environment, the room temperature sensor may require a correction.  
The settings may be selected as shown in the table below.  
(
Factory setting)  
Setting Description  
Standard  
Function Number  
Setting Value  
00  
01  
02  
03  
Lower control  
31  
Slightly warmer control  
Warmer control  
03-01  
1-4. Setting the Auto Restart  
Enable or disable automatic system restart after a power outage.  
(
Factory setting)  
Setting Description  
Function Number  
Setting Value  
Yes  
No  
00  
01  
40  
*Auto restart is an emergency function such as for power failure etc.  
Do not start and stop the indoor unit by this function in normal operation.  
Be sure to operate by the control unit, or external input device.  
1-5. Remote controller signal code  
Change the indoor unit Signal Code, depending on the remote controllers.  
(
Factory setting)  
Setting Description  
Function Number  
Setting Value  
A
B
C
D
00  
01  
02  
03  
44  
03-02  
3-1-2 Procedures to change the Function Setting for wireless RC  
The function settings of the control of the indoor unit can be changed by this procedure according  
to the installation conditions. Incorrect settings can cause the indoor unit malfunction.  
After the power is turned on, perform the "FUNCTION SETTING" according to the installation  
conditions using the remote controller.  
The settings may be selected between the following two: Function Number or Setting Value.  
Settings will not be changed if invalid numbers or setting values are selected.  
PREPARATION  
Turn on the power  
*By turning on the power indoor units, so make sure the piping air-tight test and vacuuming  
have been conducted before turning on the power.  
*Also check again to make sure no wiring mistakes were made before turning on the power.  
FUNCTION SETTING METHOD (for Wireless remote controller)  
Entering the Function Setting Mode  
While pressing the FAN button and SET TEMP.( ) button simultaneously,  
press the RESET button to enter the function setting mode.  
STEP 1.  
Setting the Remote controller Signal Code  
Use the following steps to select the signal code of the remote controller.  
(Note that the air conditioner cannot receive a signal code if the air conditioner  
has not been set for the signal code.)  
The signal code that is set through this process are applicable only to  
the signal in the FUNCTION SETTING.  
For details on how to set the signal code through the normal process,  
refer to SELECTING THE REMOTE CONTROLLER SIGNAL CODE.  
(1) Press the SET TEMP.( ) ( ) button to change the signal code  
between  
Match the code on the display to the air conditioner signal code.  
(inituially set to  
.
)
(If the signal code does not need to be selected, press the MODE button and  
proceed to STEP 2.)  
(2) Press the MODE button to accept the signal code, and proceed to STEP 2.  
*1  
The air conditioner signal code is set to prior to shipment.  
Contact your retailer to change the signal code.  
The remote controller resets to signal code when the batteries in the remote controller are replaced.  
If you use a signal code other than signal code , reset the signal code after replacing the batteries.  
If you do not know the air conditioner signal code setting, try each of the signal codes (  
until you find the code which operates the air conditioner.  
)
Note :  
*1) Small " " is displayed on the right of the signal code during the FUNCTION SETTING.  
03-03  
STEP 2.  
Selecting the Function Number and Setting Value  
(1) Press the SET TEMP.( ) ( ) buttons to select the function number.  
(Press the MODE button to switch between the left and right digits.)  
(2) Press the FAN button to proceed to setting the value.  
(Press the FAN button again to return to the function number selection.)  
(3) Press the SET TEMP.( ) ( ) buttons to select the setting value.  
(Press the MODE button to switch between the left and right digits.)  
Function  
Number  
Setting Value  
*1  
*1  
(4) Press the SLEEP button, then after you hear the beep emitted from  
the indoor unit, press the START/STOP button to confirm the settings.  
(5) Press the RESET button to cancel the function setting mode.  
(6) After completing the FUNCTION SETTING, be sure to turn off the  
power and turn it on again.  
CAUTION  
After turning off the power, wait 10 seconds or more before turning on it again.  
The FUNCTION SETTING doesn't become effective if it doesn't do so.  
Note :  
*1) Small " " is displayed on the right of the signal code during the FUNCTION SETTING.  
03-04  
REMOTE CONTROLLER SIGNAL CODE SETTING  
Use the following steps to select the signal code of the remote controller.  
(Note that the air conditioner cannot receive a signal code if the air conditioner  
has not been set for the signal code.)  
(1) Press the MODE button for at least 5 seconds to display the current signal code.  
(initially set to ).  
(2) Press the SET TEMP.( ) ( ) button to change the signal code  
between  
.
Match the code on the display to the air conditioner signal code.  
(3) Press the MODE button again. The signal code will be changed.  
If no buttons are pressed within 30 seconds after the signal code is displayed,  
the display returns to the original status. In this case, start again from step 1.  
The air conditioner signal code is set to prior to shipment.  
Contact your retailer to change the signal code.  
The remote controller resets to signal code when the batteries in the remote controller are replaced.  
If you use a signal code other than signal code , reset the signal code after replacing the batteries.  
If you do not know the air conditioner signal code setting, try each of the signal codes (  
until you find the code which operates the air conditioner.  
)
03-05  
3-2. Thermistor Resistance Values  
3-2-1 INDOOR UNIT  
Indoor heat exchanger thermistor  
Room temperature thermistor  
Resistance(k  
)
Voltage(V)  
Resistance(k  
)
Voltage(V)  
Temp ( C)  
Temp ( C)  
-10.0  
-5.0  
0.0  
55.46  
42.36  
32.67  
25.39  
19.91  
15.71  
12.5  
10.0  
8.051  
6.52  
0.76  
0.95  
1.17  
1.41  
1.67  
1.94  
2.22  
2.50  
2.77  
3.03  
3.26  
3.48  
-30.0  
-25.0  
-20.0  
-15.0  
-10.0  
-5.0  
977.6  
713.2  
526.8  
392.1  
295.1  
223.3  
170.7  
131.4  
102.1  
79.81  
62.9  
49.84  
39.78  
31.92  
25.8  
20.94  
17.11  
14.05  
11.6  
0.24  
0.33  
0.43  
0.56  
0.72  
0.91  
1.13  
1.38  
1.64  
1.92  
2.21  
2.50  
2.78  
3.05  
3.30  
3.52  
3.72  
3.90  
4.06  
4.14  
5.0  
10.0  
15.0  
20.0  
25.0  
30.0  
35.0  
40.0  
45.0  
0.0  
5.0  
10.0  
15.0  
20.0  
25.0  
30.0  
35.0  
40.0  
45.0  
50.0  
55.0  
60.0  
63.0  
5.316  
4.354  
10.36  
3-2-2 OUTDOOR UNIT  
Outdoor heat exchanger thermistor  
Outdoor temperature thermistor  
Discharge thermistor  
Resistance(k  
)
Voltage(V)  
Resistance(k  
)
Voltage(V)  
Resistance(k  
)
Voltage(V)  
Temp ( C)  
Temp ( C)  
Temp ( C)  
-30.0  
-25.0  
-20.0  
-15.0  
-10.0  
-5.0  
920.3  
676.6  
503.5  
377.6  
286.3  
218.6  
168.6  
130.9  
102.5  
80.82  
64.22  
51.36  
41.33  
33.64  
27.26  
22.33  
18.40  
15.23  
12.68  
10.60  
8.909  
7.518  
6.375  
5.427  
4.639  
3.981  
3.430  
2.965  
2.573  
2.239  
1.956  
0.07  
0.09  
0.13  
0.17  
0.22  
0.28  
0.36  
0.45  
0.56  
0.69  
0.84  
1.01  
1.20  
1.39  
1.61  
1.84  
2.07  
2.30  
2.53  
2.75  
2.97  
3.17  
3.35  
3.53  
3.69  
3.83  
3.96  
4.07  
4.17  
4.27  
4.35  
-30.0  
-25.0  
-20.0  
-15.0  
-10.0  
-5.0  
87.21  
64.16  
47.78  
35.86  
27.21  
20.80  
16.05  
12.47  
9.775  
7.709  
6.129  
4.903  
3.947  
3.196  
2.606  
2.135  
1.759  
1.457  
1.213  
1.015  
0.8531  
0.7206  
0.6115  
0.26  
0.34  
0.45  
0.58  
0.74  
0.93  
1.14  
1.38  
1.64  
1.91  
2.18  
2.46  
2.73  
2.99  
3.23  
3.45  
3.65  
3.83  
3.98  
4.12  
4.24  
4.34  
4.43  
-30.0  
-25.0  
-20.0  
-15.0  
-10.0  
-5.0  
205.7  
148.8  
109.0  
80.56  
60.23  
45.40  
34.57  
26.53  
20.56  
16.04  
12.26  
10.00  
7.978  
6.408  
5.184  
4.216  
3.451  
2.841  
0.78  
1.02  
1.30  
1.61  
1.94  
2.29  
2.63  
2.95  
3.25  
3.52  
3.79  
3.96  
4.14  
4.28  
4.40  
4.50  
4.59  
4.65  
0.0  
5.0  
0.0  
5.0  
0.0  
5.0  
10.0  
15.0  
20.0  
25.0  
30.0  
35.0  
40.0  
45.0  
50.0  
55.0  
60.0  
65.0  
70.0  
75.0  
80.0  
85.0  
90.0  
95.0  
100.0  
105.0  
110.0  
115.0  
120.0  
10.0  
15.0  
20.0  
25.0  
30.0  
35.0  
40.0  
45.0  
50.0  
55.0  
60.0  
65.0  
70.0  
75.0  
80.0  
10.0  
15.0  
20.0  
25.0  
30.0  
35.0  
40.0  
45.0  
50.0  
55.0  
03-06  
1116,Suenaga,Takatsu-ku,Kawasaki 213-8502,Japan  
Mar. 2012 Printed in Japan  

BLACKHAWK! AUTOMOTIVE BH6221 User Manual
Brother MFC 8680DN User Manual
Canon PIXMA Black Photo All In One Printer 6226B002 User Manual
Carrier 38AU User Manual
GE AZ75W09DAC User Manual
Graco Baby Accessories PD216493B User Manual
Haier Air Conditioner HW 24EMA13T3 User Manual
Heat Controller Inc Air Conditioner DMC12SB 0 User Manual
HP Hewlett Packard Officejet g85 C6737A User Manual
HP Hewlett Packard OFFICEJET PRO 8000 A809 User Manual