Friedrich RC 12 User Manual

DUAL MOTOR PACKAGED TERMINAL  
AIR CONDITIONERS  
RC 11, 12 & 21  
AL  
RC/RH 10, 20, 35, 45, 80, 90  
CEMANU  
RC/RH10  
RC11  
RC12  
RC/RH20  
ODMAITEN  
RC21  
RC/RH35  
TIN,OPERA  
RC/RH80  
LA  
INST  
Enviromaster International LLC  
5780 Success Dr.  
Rome, NY 13440  
An ISO 9001-2000 Certified Company  
P/N# 240004146, Rev. 1.7 [02/07]  
TABLE OF CONTENTS  
MODIFICATION AND TAMPERING  
Warnings and Precautions ..................................... 2-3  
The Dual Motor PTAC Family ................................... 4  
Controls and Components ........................................ 4  
Preparation for Installation ....................................... 5  
Electrical Wiring ....................................................... 5  
Installation Instruction for:  
DANGER  
!
!
Tampering with the RetroAire Dual Motor PTAC is  
dangerous and may result in serious injury or death.  
Tampering voids all warranties. Do not attempt to  
RC/RH10 Replacement PTAC ............................. 6  
RC11 Replacement PTAC.................................... 7  
RC12 Replacement PTAC ................................... 8  
RC/RH20 Replacement PTAC ........................ 9-10  
RC21 Replacement PTAC .............................11-12  
RC/RH35 Replacement PTAC ............................13  
RC/RH45 Replacement PTAC .......................14-15  
RC/RH80 Replacement PTAC .......................16-17  
RC/RH90 Replacement PTAC .......................18-19  
Final Inspection and Start-Up..............................20  
Sequence of Operation .......................................20-23  
Cleaning and Maintenance .....................................24  
Troubleshooting .......................................................24  
Specications ...........................................................25  
Warranty ..................................................................26  
modify or change this unit in any way.  
IMPORTANT SAFETY FEATURE  
Power Cord With Integral Safety Protection  
All PTACs rated 250V or less that are cord connected  
to the power supply are equipped with a power cord  
with integral safety protection as standard. Providing  
personal shock protection as well as arcing and  
fire prevention, the device is designed to sense  
any damage in the line cord and disconnect power  
before a fire can occur. Tested in accordance with  
Underwriters Laboratories, the cord set also offers a  
unique passive operation, meaning the unit does not  
require resetting if main power is interrupted.  
INSTALLER RESPONSIBILITIES  
WARNING - A DAMAGED POWER SUPPLY CORD  
MUST BE REPLACED WITH A NEW CORD FROM  
THE MANUFACTURER, AND NOT REPAIRED.  
This manual has been prepared to acquaint you with the  
installation, operation and maintenance of RetroAire Dual  
Motor PTACs and to provide important safety information  
in these areas.  
Each power cord should be checked before every  
use. Follow the instructions in the order listed on the  
device.  
We urge you to read all of these instructions thoroughly  
before attempting the installation or operation of your unit.  
This manual should be kept for future reference.  
WARNING - DO NOT USE THE PRODUCT IF THE  
UNIT FAILS THE TEST.  
The manufacturer of this unit will not be liable for any  
damages caused by failure to comply with the installation  
and operating instructions outlined in this manual.  
DANGER  
!
!
Do not use the RetroAire Dual Motor PTAC with  
any electrical supply voltage other than the one  
listed on the rating plate.  
A rating plate identifying your RetroAire Dual Motor  
PTAC can be found on the unit. When referring to your  
unit, always have the information listed on the rating plate  
readily available.  
CAUTION  
!
!
WARNING  
!
!
PTAC Chasses are heavy. To avoid injury, use  
assistance when lifting.  
Completely read all instructions prior to assembling,  
installing, operating, or repairing this product. Inspect  
all parts for damage prior to installation and start-up.  
Note: Unit uses R22 refrigerant.  
3
The Right Fit For Comfort  
The RetroAire Dual Motor PTAC is available in nominal  
sizes of 9,000 Btuh, 12,000 Btuh, 15,000 Btuh, and 18,000  
Btuh.* With energy efciency ratings as high as 10, the  
replacement of worn out and inefcient units is a very at-  
tractive option.  
THE DUAL MOTOR PTAC FAMILY  
The RetroAire Dual Motor PTAC is available as a cooling-  
only model or, for those who wish to up-grade to a heat  
pump, the RH10, 20, 35, 45, 80, and 90 heat pump chassis  
will fit the existing wall sleeve. The heat pump version will  
reduce energy costs during periods of outdoor temperature  
ranging down to as low as 40° F.  
* The RC12 PTAC, however, is only available in nominal  
sizes of 12,000 Btuh and 15,000 Btuh.  
All Retroaire products are backed by Enviromaster  
International LLC and are rated in accordance with ARI  
Standards 310 and 380 and UL Standard 484.  
The Dual Motor PTAC uses a high-efciency rotary com-  
pressor protected under a 5-year warranty and an enhanced  
high-efciency heat exchanger to make the replacement of  
worn out and inefcient units a very attractive option.  
PRE-INSTALLATION  
The RetroAire Dual Motor PTAC offers two fan speeds  
– three in the RC12 – and has an optional motorized fresh  
air feature with a positive pressure seal, override switch, and  
positive condensate re-evaporation to improve efciency.  
Test run the Dual Motor PTAC prior to installation. Connect  
the line cord to a proper power supply (such as the one the  
old unit is plugged into) and check all controls for proper  
operation. Disconnect the chassis before installing.  
Whisper quiet operation improves the room ambience and  
the 20 gauge galvanized steel construction of the chassis  
ensures long service life.  
Review baffle and foam tape installation to ensure proper  
air seal and unit operation.  
The RetroAire Dual Motor Packaged Terminal Air Condi-  
tioner family consists of:  
CONTROLS AND COMPONENTS  
Standard Unit Features  
RC/RH10: Astraight cool/heat pump replacement for  
the American Air Filter 16 Series, American Standard  
45, Carteret 45, Remington Type 45, McQuay 45,  
Singer 45, and Nelson Aire 16.  
1. Unit mounted operating controls  
• Thermostat  
• Fan speed control  
• Heat/cool switch  
• Fan cycle switch  
RC11: A straight cool only replacement for the  
Westinghouse RB Series.  
2. Low ambient protection  
3. Foam strip seal for supply air duct  
4. Weather strip insulation  
5. Baffle kit bag  
RC12: A straight cool only replacement for the Len-  
nox PTEIA Series.  
RC/RH20: A straight cool/heat pump replacement  
for the Climate Master (Friedrich) 702 & 703, Cool  
Heat RM Series, TPI Ra-Matic, Weather Twin, and  
ZoneAire S, SC & RM.  
6. Condenser bafes to accommodate extended wall  
sleeve applications (consult factory)  
RC21: A straight cool only replacement for the Cli-  
mate Master 701.  
7. Sea coast coated drainpan  
8. Normally/open normally/closed motor valve-switch,  
(hydronic heat only)  
RC/RH35:Astraight cool/heat pump replacement for  
the Singer/Remington/McQuay EA, ES & RS.  
Optional Controls and Accessories  
RC/RH45: A straight cool/heat pump replacement  
for the American Standard Type 40.  
1. Remote thermostat  
2. Motorized fresh air damper  
3. Electric/hydronic heat  
RC/RH80:Astraight cool/heat pump replacement for  
Fedders CMEO Unizone,” and Mueller/Worthington  
Climatrol.”  
4. Disconnect switch  
RC/RH90:Astraight cool/heat pump replacement for  
Cool Heat AD & 700 and Friedrich Climate Master  
AD & 700.  
5. Sea coast coated coils  
6. Wall sleeves, louvers, and cabinets (consult factory)  
The Right Fit For Comfort  
4
WARNING  
WARNING  
!
!
!
!
Moving parts can cause personal injury. Exercise  
all due caution when test running the chassis.  
The correct condenser air baffles must be properly  
installed or performance will be impaired and/or the  
warranty will be voided!!  
See individual unit installation instructions for more  
information.  
PREPARATION FOR INSTALLATION  
IMPORTANT: RetroAire Dual Motor PTACs are to be used  
with metal wallsleeves. The sleeves must employ front  
panels secured by screws that prevent contact with all parts  
with minor dimensions of openings not exceeding 1/2. The  
nal assembly must employ an indoor air discharge grill  
having dimensions not less than 26” x 4, separating the top  
surface of the chassis from the top surface of the discharge  
grill by a minimum of 1. For all models, the outdoor  
openings must prevent contact of all moving parts by means  
of louvers or grills with minor dimension not exceeding 1.  
All cord connected 265 Volt units must be plugged into  
receptacles within the unit subbase or chassis.  
ELECTRICAL WIRING  
All wiring should be in accordance with the National Electric  
Code (NEC) and the local building codes.  
WARNING  
!
!
To avoid possible injury or death due to electrical  
shock, open the power supply disconnect switch  
and secure it in an open position during installation.  
On a plug and receptacle connection, keep the unit  
unplugged until installation is complete.  
1. Remove the front of the existing room enclosure. This  
will expose the old chassis.  
2. Disconnect the power supply. If a line cord and plug  
were used, remove it from the receptacle. If the chassis  
is hard wired, locate the circuit breaker, place it in the  
OFF” position, and tag it, announcing work is being  
done. DO NOT TURN ON.  
1. Inspect the existing wiring for any deciencies such as  
cut or frayed wires. Replace such wiring if found.  
2. Check the unit rating plate for circuit ampacity and  
breaker or fuse size. Use only HACR type breakers.  
Select the proper wire for the ampacity rating.  
3. Loosen any tie down bolts or screws and remove the  
old chassis.  
3. If plug and receptacle are used, check the compatibility.  
The chassis can be hard wired or direct connected as  
well.  
IMPORTANT: Dispose of old chassis per present state  
and federal regulations.  
4. Each unit must have a separate branch ciruit protected  
by a fuse or breaker. Refer to the unit rating plate for the  
proper wire and breaker or fuse size. Use of extension  
cords is prohibited.  
4. Inspect the wall sleeve/cabinet for rust, holes, and dam-  
age. Clean the wall sleeve of any dirt, repair any damage,  
and ensure proper drainage of condensate or rainwater  
to exterior of building.  
5. Remove or repair old weather seals and note location  
for installation of any new seals.  
DANGER  
!
!
The RetroAire Dual Motor PTAC must:  
6. Check the wall sleeve/cabinet to assure all drain holes  
are open and that (A) the unit is level left to right and (B)  
the back is pitched to the outside by 1/2” maximum.  
Be connected to a properly grounded electrical  
supply with the proper voltage as stated on the  
rating plate.  
7. Check the present voltage to verify the new chassis is a  
matching voltage and that the line cord and receptacle  
match.  
Use the proper maximum over current protection  
device stated on the rating plate.  
The use of extension cords is prohibited.  
8. Before installing the new chassis, inspect the outdoor  
louver for a minimum free area of 70% and remove  
any obstructions. Any variation will restrict air flow over  
the condenser coil and cause serious damage to the  
chassis. It will also void the warranty.  
Failure to follow these instructions can result in a fire,  
explosion or electrical shock causing property damage,  
personal injury or death.  
5
The Right Fit For Comfort  
INSTALLATION INSTRUCTIONS  
RC/RH10 REPLACEMENT PTAC  
5. Apply one piece of 1/2” x 1/2” open cell polyfoam to top ange  
Install  
1/2” x 1/2”  
Foam Tape  
of evaporator block off (See illustration at left).  
6. Apply 2” x 1 1/2” open cell foam strips around supply air  
duct to ensure that all the conditioned air is delivered into  
the room. Failure to do so results in recirculation of the  
conditioned air around the wall sleeve and through the unit  
causing the unit to short cycle and coils to freez, thus rais-  
ing operating costs through improper heating and cooling  
(Figure C1).  
7. 1” x 1” Open cell foam strips are provided to prevent outside air  
from entering around the chassis to the room from the sides  
and top of the cabinet. Install between wall sleeve and cooling  
chassis. It is imperative to have a solid air seal between wall  
sleeve and chassis. Failure to do so will result in air leakage  
from outdoor to  
RC/RH10 BAFFLE INSTALLATION KIT  
• 1 Installation Manual  
• 1 Top Baffle  
• 2 Sets of Lt.&Rt. Bafes  
• 1/2” x 1/2” Open Cell Foam Tape  
• 1” x 1” Open Cell Foam Tape  
• 2” x 1 1/2” Open Cell Foam Tape  
• 1ea. 2-Position Connector & Pin Mate  
• 14AWG Yellow Wire  
Figure D1  
indoor ca us ing  
Screws  
HYDRONIC  
ONLY  
system problems  
i.e. coils freezing,  
short cycling, and  
constant running  
of unit. If install-  
er is in need of  
more foam than  
s upplie d in kit,  
cons ult fa ctory  
(Figure D1).  
Wall Sleeve  
1. Take unit out of packaging.  
2. Slide unit into wall sleeve. If supply duct on cooling chassis does  
not line up with supply vent on room cabinet it is possible that  
factory installed angle brackets on the top and sides will have  
to be reversed. This will allow approximately 1in or out of the  
wall sleeve (see figures A & B) below.  
Front View  
Cooling Chassis  
1x1Foam Tape  
Figure A1  
Figure B1  
8. Once condent that all seals are the correct size and in the  
proper location, and the correct bafes are attached to the con-  
denser coil in the proper orientation, slide unit into final position  
and tighten any tie down bolts or screws as necessary.  
Hydronic Only: Remove the 2-position connector assembly  
from kit bag supplied with unit (this will have 2 yellow wires  
attached). Connect this 2-position connector to the 2-position  
connection located on the bottom of the control box panel.  
Two sets of baffles are provided in your kit to accommodate  
mounting brackets in either position A or B.  
To Connect Aquastat:  
A. Remove the black jumper wire located on the bottom  
panel of the control box (this is also terminated with a  
2-position connector).  
B. Cut the jumper wire in the middle and splice the aquastat  
to the jumper.  
3. Slide unit out of wallsleeve.  
4. Baffle Installation - Remove bafes from kit bag supplied  
with unit. Install left and right side bafes on the condenser  
coil in existing holes:  
C. Place the connecter back into original location. Refer  
to wire diagram on the unit for details.  
• Choose the proper tting bafes for your application.  
• Bafes must come in contact with the outdoor louver.  
• Ma ke s ure ba ffle s a re  
dire cte d inwa rd towa rd  
the center of coil.  
9. Connect line cord.  
Figure C1  
Bafes Directed Inward  
10. See Final Inspection and Startup on page 20.  
Toward Coil  
Secure bafes tightly to  
the condenser coil using  
the screws provided.  
RC/RH 10 PERFORMANCE DATA*  
�  
Unit Size Cooling Btuh EERs Heat Pump Btuh COP Fresh Air CFM  
9
9,500  
11,900  
14,700  
16,900  
10.0  
10.0  
9.2  
8,500  
11,400  
13,800  
N/A  
2.8  
2.9  
2.8  
N/A  
40/35  
40/35  
40/35  
40/35  
 
(Figures A1,B1 & C1).  
12  
15  
18  
IMPORTANT: The correct  
condenser air baffles must  
be installed or performances  
may be impaired and/or the  
warranty will be voided.  
 
 
��  
9.1  
2” X 1 1/2” Supply Air  
Duct Foam Tape  
*Refer to the charts on page 23 for electrical and  
optional electric heat specifications.  
The Right Fit For Comfort  
6
INSTALLATION INSTRUCTIONS  
RC11 REPLACEMENT PTAC  
6. Apply 2” x 1 1/2” open cell foam strips around supply air  
duct to ensure that all the conditioned air is delivered  
into the room. Failure to do so results in recirculation of  
the conditioned air around the wall sleeve and through  
the unit causing the unit to short cycle, thus raising  
operating costs through improper heating and cooling  
341/2  
393/4  
141/8  
(Figure A2).  
Figure B2  
7. 1” x 1” Open  
cell foam strips  
are provided to  
preventoutside  
air from enter-  
ing around the  
chassis to the  
room from the  
sides and top  
Wall Sleeve  
301/4  
111/4  
187/8  
Install  
1/2” x 1/2”  
Foam Tape  
Front View  
Cooling Chassis  
RC11 BAFFLE INSTALLATION KIT  
• 1 Installation Manual  
• 1 Top Baffle  
• 2 Sets of Lt.&Rt. Bafes  
• 1/2” x 1/2” Open Cell Foam Tape  
• 1” x 1” Open Cell Foam Tape  
• 2” x 1 1/2” Open Cell Foam Tape  
• 1 ea. 2-Position Connector & Pin Mate  
• 14AWG Yellow Wire  
1x1Foam Tape  
of the cabinet. Install between wall sleeve and cooling  
chassis. It is imperative to have a solid air seal between  
wall sleeve and chassis. Failure to do so will result in  
air leakage from outdoor to indoor causing system  
problems i.e. Coils freezing, short cycling, and constant  
running of unit. If installer is in need of more foam than  
supplied in kit, consult factory (Figure B2).  
Screws  
HYDRONIC  
ONLY  
Two sets of baffles are provided in your kit to accommodate  
varying wall sleeve depth.  
1. Take unit out of packaging.  
8. Once condent that all seals are the correct size and in  
the proper location, and the correct bafes are attached  
to the condenser coil in the proper orientation, slide  
unit into final position and tighten any tie down bolts or  
screws as necessary.  
2. Slide unit into wall sleeve. The supply duct on the cool-  
ing chassis should line up with the supply vent on the  
room cabinet. The weather angles should require no  
adjustment.  
3. Slide unit out of wallsleeve.  
Hydronic Only: Remove the 2-position connector as-  
sembly from kit bag supplied with unit (this will have 2  
yellow wires attached). Connect this 2-position connector  
to the 2-position connection located on the bottom of the  
control box panel.  
IMPORTANT: The correct condenser air baffles must be  
installed or performances may be impaired and/or the  
warranty will be voided.  
4. Baffle Installation - Remove bafes from kit bag sup-  
plied with unit. Install left and right side bafes on the  
condenser coil in existing holes:  
To Connect Aquastat:  
A. Remove the black jumper wire located on the bot-  
tom panel of the control box (this is also terminated  
with a 2-position connector).  
• Choose the proper tting bafes for your applica-  
tion.  
B. Cut the jumper wire in the middle and splice the  
aquastat to the jumper.  
C. Place the connecter back into original location.  
Refer to wire diagram on the unit for details.  
Figure A2  
• Ba ffle s mus t come  
in conta ct with the  
outdoor louver.  
Bafes-Directed Inward  
Toward Coil  
• Ma ke s ure ba ffle s  
are directed inward  
�  
9. Connect line cord.  
10. See Final Inspection and Startup on page 20.  
toward the center of  
coil.  
 
RC11 PERFORMANCE DATA*  
Secure bafes tightly  
to the condenser coil  
using the screws pro-  
vided.  
 
 
��  
UNIT SIZE COOLING BTUH EER FRESH AIR CFM  
9
9500  
10  
40/35  
2” X 1 1/2” Supply Air  
Duct Foam Tape  
12  
15  
18  
11,900  
14,700  
16,900  
10  
9.2  
9.1  
40/35  
40/35  
40/35  
5. Apply one piece of 1/2” x 1/2” open cell polyfoam to top  
ange of evaporator block off (See illustration: top of  
this page).  
*Refer to the charts on page 23 for electrical and  
optional electric heat specifications.  
7
The Right Fit For Comfort  
INSTALLATION INSTRUCTIONS  
RC12 REPLACEMENT PTAC  
IMPORTANT: If adjoining room conditioning is required, the  
RC12 is able to discharge to the right and left by utilizing  
the four-inch knockouts (Figure B3) on either side of the  
evaporator compartment using 4” flex duct.  
3. Once condent that all seals are the correct size and in  
the proper location and the correct bafes are attached  
to the condenser coil and in the proper orientation, slide  
unit into final position and tighten any tie down bolts or  
screws as necessary.  
Figure B3  
Left and Right  
Condenser Bafes  
1” x 1” Open Cell  
Foam Tape  
1” X 1/2”  
Open Cell  
Foam Tape  
5/8” Ref.  
RC12 INSTALLATION KIT  
• 1 Installation Manual  
• 1ea. 2-Position Connector & Pin Mate  
• 14AWG Black Wire  
HYDRONIC  
ONLY  
Air Intake  
Removeable Filter  
1. Take unit out of packaging.  
4” Knockout  
2. Slide unit into wall sleeve. The supply duct on the cool-  
ing chassis should line up with the supply vent on the  
room cabinet. The weather angles should require no  
adjustment.  
Hydronic Only: Remove the 2-position connector as-  
sembly from kit bag supplied with unit (this will have 2  
yellow wires attached). Connect this 2-position connec-  
tor to the 2-position connection located on the bottom  
of the control box panel.  
3. Make sure bafes come in contact with the outdoor  
louver.  
IMPORTANT: Baffles and open cellfoam tape seals  
are factory installed on the RC12 . Baffles fill the gap  
between the rear of the chassis and the outdoor louver  
and prevent the air from recirculating. Consult the factory  
if baffles supplied are not deep enough to accommodate  
wall sleeve application as system efficiency and reliability  
are dependent on proper air flow. (Figure A3)  
To Connect Aquastat:  
A. Remove the black jumper wire located on the  
bottom panel of the control box (this is also ter-  
minated with a 2-position connector).  
B. Cut the jumper wire in the middle and splice the  
aquastat to the jumper.  
C. Place the connecter back into original location.  
Refer to wire diagram on the unit for details.  
Figure A3  
4. Connect line cord.  
Bafes-Directed Inward  
Toward Coil  
5. See Final Inspection and Startup on page 20.  
�  
1” X 1 ”  
Open Cell  
Foam Tape  
RC12 PERFORMANCE DATA*  
 
UNIT COOLING  
EVAP CFM  
HIGH/LOW  
FRESH  
EER  
SIZE  
BTUH  
12,200  
15,500  
AIR CFM  
 
��  
 
12  
10  
9
390/340  
440/390  
40/35  
40/35  
15  
1” X 1/2” Supply Air  
Duct Foam Tape  
*Refer to the charts on page 23 for electrical and  
optional electric heat specifications.  
The Right Fit For Comfort  
8
INSTALLATION INSTRUCTIONS  
RC/RH20 REPLACEMENT PTAC  
ADJUSTABLE WEATHER SEAL ANGLE POSITIONS  
Two sets of baffles are provided in your kit to accommodate  
mounting brackets in either position A or B.  
A
8 5/8”  
7 7/8”  
9 11/16” (1)  
8” (2)  
(1)  
B
9 1/2”  
10 1/4”  
8 7/16”  
10 1/8” (2)  
NOTE: Dimensions calculated without foam gaskets  
(1) Standard position-Factory installed  
Figure A4  
Figure B4  
(2) Position for Climate Master 702 and 703.  
REMOVEABLE  
WEATHER SEAL  
ANGLES  
5 1/2”  
4”  
3”  
35 15/16”  
22” CONDENSER COIL  
2”  
8 1/2”  
8 1/4”  
4. Baffle Installation - Remove bafes from kit bag sup-  
plied with unit. Install left and right side bafes on the  
condenser coil in existing holes:  
26” AIR OUTLETS  
14 13/16”  
• Choose the proper tting bafes for your applica-  
tion.  
• Baffles must come in contact with the outdoor  
louver.  
A
AIR INTAKE FILTER  
• Make sure bafes are directed inward toward the  
center of coil.  
18 1/8”  
B
Secure bafes tightly to the condenser coil using the  
screws provided. (Figures A4,B4 & C4 )  
Figure C4  
RC/RH20 BAFFLE INSTALLATION KIT  
Bafes-Directed Inward  
Toward Coil  
• 1 Installation Manual  
Screws  
• 1 Lt. & Rt. Bafes (size 1)  
• 1 Lt. & Rt. Bafes (size 2)  
• 1” x 1” Open Cell Foam Tape  
• 1/2” x 1/2” Open Cell Foam Tape  
�  
• 1ea. 2-Position Connector & Pin Mate  
• 14AWG Black Wire  
HYDRONIC  
ONLY  
�  
1. Take unit out of packaging.  
�  
���  
�  
2. Slide unit into wall sleeve. If supply duct on cooling  
chassis does not line up with supply vent on room  
cabinet it is possible that factory instlled angle brackets  
on the top and sides will have to be reversed. This will  
allow approximately 1in or out of the wall sleeve (See  
figures A4 & B4).  
1/2” X 1/2” Supply Air  
Duct Foam Tape  
5. Apply 1/2” x 1/2” open cell foam strips around supply  
air duct to ensure that all the conditioned air is delivered  
into the room. Failure to do so results in recirculation of  
the conditioned air around the wall sleeve and through  
the unit causing the unit to short cycle, thus raising  
operating costs through improper heating and cooling  
(Figure C4).  
3. Slide unit out of wallsleeve.  
IMPORTANT: The correct condenser air baffles must be  
installed or performances may be impaired and/or the  
warranty will be voided.  
9
The Right Fit For Comfort  
RC/RH20 INSTALLATION INSTRUCTIONS (Continued)  
6. 1” x 1” Open cell foam strips are provided to prevent  
outside air from entering around the chassis to the room  
from the sides and top of the cabinet. Install between  
wall sleeve and cooling chassis. It is imperative to have  
a solid air seal between wall sleeve and chassis. Failure  
to do so will result in air leakage from outdoor to indoor  
causing system problems i.e. coils freezing, short cy-  
cling, and constant running of unit. If installer is in need  
of more foam than supplied in kit, consult factory.  
Hydronic Only: Remove the 2-position connector as-  
sembly from kit bag supplied with unit (this will have 2  
yellow wires attached). Connect this 2-position connec-  
tor to the 2-position connection located on the bottom  
of the control box panel.  
To Connect Aquastat:  
A. Remove the black jumper wire located on the  
bottom panel of the control box (this is also ter-  
minated with a 2-position connector).  
B. Cut the jumper wire in the middle and splice the  
aquastat to the jumper.  
Figure D4  
Wall Sleeve  
C. Place the connecter back into original location.  
Refer to wire diagram on the unit for details.  
8. Connect line cord.  
Front View  
9. See Final Inspection and Startup on page 20.  
Cooling Chassis  
1x1Foam Tape  
7. Once condent that all seals are the correct size and in  
the proper location and the correct bafes are attached  
to the condenser coil in the proper orientation, slide  
unit into final position and tighten any tie down bolts or  
screws as necessary.  
RC/RH 20 PERFORMANCE DATA*  
RC/RH20 Hydronic Heat *  
Unit  
Size  
Cooling  
Btuh  
Heat Pump  
Btuh  
Fresh Air  
CFM  
Performance 104-101 (Single Row Coil)  
EERs  
COP  
GPM  
EWT (°F)  
180°F Hi  
180°F Lo  
140°F Hi  
140°F Lo  
Capacities Btuh  
16,400  
P.D.  
4.4  
4.4  
4.6  
4.6  
9
9,500  
11,900  
14,700  
10  
10  
8500  
11400  
13800  
2.8  
2.9  
2.8  
40/35  
40/35  
40/35  
12  
15  
15,400  
3.0  
9.2  
10,300  
9,700  
40/35  
18  
16,900  
9.1  
N/A  
N/A  
*Refer to the charts on page 23 for electrical and optional electric heat specifications.  
The Right Fit For Comfort  
10  
INSTALLATION INSTRUCTIONS  
RC21 REPLACEMENT PTAC  
DIMENSIONS  
2. Slide unit out of wallsleeve.  
MODEL  
9-12  
A
B
C
20 14”  
25 1/4”  
9 7/8”  
10 1/8”  
10 3/8”  
15 3/8”  
3. Remove bafes from kit bag supplied with unit.  
15-18  
IMPORTANT: The correct condenser air baffles must be  
installed or performances may be impaired and/or the  
warranty will be voided.  
A - OVERALL CHASSIS DEPTH  
B - CONDENSER SECTION DEPTH  
C - EVAPORATOR SECTION DEPTH  
NOTE: Dimensions “A” and “B” are with condenser  
recirculation baffles and without weather seal  
gasket.  
4. Baffle Installation - Install left and right side bafes on  
the condenser coil in existing holes:  
Condenser recirculation  
bafes for standard 10”  
wall box (provided)  
• Choose the proper tting bafes for your application.  
• Bafes must come in contact with the outdoor lou-  
ver.  
• Make sure bafes are directed inward toward the  
center of coil.  
Secure bafes tightly to the condenser coil using the  
screws provided. (Figures A5, B5 & C5 )  
Figure C5  
Bafes-Directed Inward  
Toward Coil  
�  
RC21 BAFFLE INSTALLATION KIT  
• 1 Installation Manual  
• 1 Lt. & Rt. Bafes (size 1)  
• 1 Lt. & Rt. Bafes (size 2)  
Screws  
• 1” x 1” Open Cell Foam Tape  
• 1/2” x 1/2” Open Cell Foam Tape  
�  
�  
���  
�  
HYDRONIC  
• 1ea. 2-Position Connector & Pin Mate  
• 14AWG Black Wire  
ONLY  
1/2” X 1 1/2” Supply Air  
Duct Foam Tape  
1. Take unit out of packaging.  
2. Slide unit into wall sleeve. If supply duct on cooling  
chassis does not line up with supply vent on room  
cabinet it is possible that factory instlled angle brackets  
on the top and sides will have to be reversed. This will  
allow approximately 1in or out of the wall sleeve (See  
Figures A5 & B5).  
5. Apply 1/2” x 1/2” open cell foam strips around supply  
air duct to ensure that all the conditioned air is delivered  
into the room. Failure to do so results in recirculation of  
the conditioned air around the wall sleeve and through  
the unit causing the unit to short cycle, thus raising  
operating costs through improper heating and cooling  
(Figure C5).  
Figure A5  
Figure B5  
Two sets of baffles are provided in your kit to accommodate  
mounting brackets in either position A or B.  
11  
The Right Fit For Comfort  
RC21 INSTALLATION INSTRUCTIONS (Continued)  
Figure D5  
Hydronic Only: Remove the 2-position connector as-  
Wall Sleeve  
sembly from kit bag supplied with unit (this will have 2  
yellow wires attached). Connect this 2-position connector  
to the 2-position connection located on the bottom of the  
control box panel.  
To Connect Aquastat:  
Front View  
A. Remove the black jumper wire located on the bot-  
tom panel of the control box (this is also terminated  
with a 2-position connector).  
Cooling Chassis  
B. Cut the jumper wire in the middle and splice the  
aquastat to the jumper.  
1x1Foam Tape  
C. Place the connecter back into original location.  
Refer to wire diagram on the unit for details.  
6. 1” x 1” Open cell foam strips are provided to prevent  
outside air from entering around the chassis to the room  
from the sides and top of the cabinet. Install between  
wall sleeve and cooling chassis. It is imperative to  
have a solid air seal between wall sleeve and chassis.  
Failure to do so will result in air leakage from outdoor  
to indoor causing system problems i.e. coils freezing,  
short cycling, and constant running of unit. If installer is  
in need of more foam than supplied in kit, consult fac-  
tory (See Figure D5).  
8. Connect line cord.  
9. See Final Inspection and Startup on page 20.  
7. Once condent that all seals are the correct size and in  
the proper location and the correct bafes are attached  
to the condenser coil in the proper orientation, slide  
unit into final position and tighten any tie down bolts or  
screws as necessary.  
RC21 Hydronic Heat *  
RC21 PERFORMANCE DATA*  
Cooling  
Btuh  
Fresh Air  
CFM  
Performance 104-101 (Single Row Coil)  
Unit Size  
EERs  
GPM  
EWT (°F)  
180°F Hi  
180°F Lo  
140°F Hi  
140°F Lo  
Capacities Btuh  
16,400  
P.D.  
4.4  
4.4  
4.6  
4.6  
9
9,500  
11,900  
14,700  
10  
10  
40/35  
40/35  
40/35  
40/35  
12  
15  
15,400  
3.0  
9.2  
10,300  
18  
16,900  
9.1  
9,700  
*Refer to the charts on page 23 for electrical and optional electric  
heat specifications.  
The Right Fit For Comfort  
12  
INSTALLATION INSTRUCTIONS  
RC/RH35 REPLACEMENT PTAC  
6. Once condent that all seals are the correct size and in  
the proper location and the correct bafes are attached  
to the condenser coil and in the proper orientation, slide  
unit into final position and tighten any tie down bolts or  
screws as necessary.  
Hydronic Only: Remove the 2-position connector as-  
sembly from kit bag supplied with unit (this will have 2  
yellow wires attached). Connect this 2-position connector  
to the 2-position connection located on the bottom of the  
control box panel.  
To Connect Aquastat:  
A. Remove the black jumper wire located on the  
bottom panel of the control box (this is also ter-  
minated with a 2-position connector).  
B. Cut the jumper wire in the middle and splice the  
aquastat to the jumper.  
C. Place the connecter back into original location.  
Refer to wire diagram on the unit for details.  
RC/RH35 INSTALLATION KIT  
• 1 Installation Manual  
Screws  
• 1 Lt. & Rt. Bafes  
• 1” x 1” Open Cell Foam Tape  
HYDRONIC  
• 1ea. 2-Position Connector & Pin Mate  
• 14AWG Black Wire  
ONLY  
7. Connect line cord.  
1. Take unit out of packaging.  
8. See Final Inspection and Startup on page 20.  
2. Slide unit into wall-sleeve. The supply duct on the cool-  
ing chassis should line up with the supply vent on the  
room cabinet.  
IMPORTANT: The RC/RH35 is equipped with a bracket  
that allows the unit to be adjusted up and down in the chas-  
sis of unleveled wall sleeves. Adjust leveler leg (Shown  
below Figure B6) to desired height and tighten down using  
bolts supplied on bracket.  
3. Slide unit out of wall-sleeve  
IMPORTANT: The correct condenser air baffles must  
be installed or performances may be impaired and/or  
the warranty will be voided.  
Figure B6  
4. Baffle Installation - Remove bafes from kit bag sup-  
plied with unit. Install left and right side bafes on the  
condenser coil in existing holes:  
Figure A6  
• Bafes must come in  
contact with the out-  
door louver.  
Bafes-Directed Inward  
Toward Coil  
�  
• Make sure bafes are  
directed inward toward  
the center of coil.  
�  
RC/RH35 PERFORMANCE DATA*  
Secure bafes tightly  
to the condenser coil  
using the screws pro-  
vided. (Figure A6)  
�  
�  
���  
COOLING  
Btuh  
HEAT PUMP  
Btuh  
FRESH AIR  
CFM  
MODEL  
EER  
COP  
1” X 1” Supply Air  
Duct Foam Tape  
9
9,500  
11,900  
14,700  
16,900  
10  
10  
8,500  
11,400  
13,800  
N/A  
2.8  
2.9  
2.8  
N/A  
40/35  
40/35  
40/35  
40/35  
12  
15  
18  
5. Apply 1” x 1” open cell foam strips around supply air  
duct to ensure that all the conditioned air is delivered  
into the room. Failure to do so results in recirculation of  
the conditioned air around the wall sleeve and through  
the unit causing the unit to short cycle, thus raising  
operating costs through improper heating and cooling  
(Figure A6).  
9.2  
9.1  
*Refer to the charts on page 23 for electrical and optional  
electric heat specifications.  
13  
The Right Fit For Comfort  
INSTALLATION INSTRUCTIONS  
RC/RH45 REPLACEMENT PTAC  
3. Slide unit out of wallsleeve and install bafes on the  
condenser side.  
18.63”  
34.50”  
4. Remove bafes from kit bag supplied with unit.  
16.50”  
IMPORTANT: The correct condenser air baffles must be  
installed or performances may be impaired and/or the  
warranty will be voided.  
14.07”  
5. Baffle Installation - Install left and right side bafes on  
the condenser coil in existing holes:  
5.50”  
• Choose the proper tting bafes for your application.  
• Bafes must come in contact with the outdoor lou-  
ver.  
• Make sure bafes are directed inward toward the  
center of coil.  
Secure bafes tightly to the condenser coil using the  
screws provided. (Figures A7, B7 & C7 )  
RC/RH45 INSTALLATION KIT  
• 1 Installation Manual  
• 1 Lt. & Rt. Bafes (size 1)  
• 1 Lt. & Rt. Bafes (size 2)  
Screws  
• 1” x 1” Open Cell Foam Tape  
• 1/2” x 1/2” Open Cell Foam Tape  
Figure C7  
HYDRONIC  
ONLY  
• 1ea. 2-Position Connector & Pin Mate  
• 14AWG Black Wire  
Bafes-Directed Inward  
Toward Coil  
1. Take unit out of packaging.  
�  
�  
2. Slide unit into wall sleeve. If supply duct on cooling chas-  
sis does not line up with supply vent on room cabinet it  
is possible that factory installed angle brackets on the  
top and sides will have to be reversed. This will allow  
approximately 1in or out of the wall sleeve. ( S e e  
Figures A7 & B7)  
�  
���  
�  
1/2” X 1/2” Supply Air  
Duct Foam Tape  
Figure B7  
Figure A7  
6. Apply 1/2” x 1/2” open cell foam strips around supply  
air duct to ensure that all the conditioned air is delivered  
into the room. Failure to do so results in recirculation  
of the conditioned air around the wall sleeve and  
through the unit causing the unit to short cycle, thus  
raising operating costs through improper heating and  
cooling. (Figure C7)  
Two sets of baffles are provided in your kit to accommodate  
mounting brackets in either position A or B.  
The Right Fit For Comfort  
14  
RC/RH45 INSTALLATION INSTRUCTIONS (Continued)  
7. 1” x 1” Open cell foam strips are provided to prevent  
8. Once condent that all seals are the correct size and in  
the proper location and the correct bafes are attached  
to the condenser coil in the proper orientation, slide  
unit into final position and tighten any tie down bolts or  
screws as necessary.  
outside air from entering around the chassis to the room  
from the sides and top of the cabinet (Figure D7). Install  
between wall sleeve and cooling chassis. It is impera-  
tive to have a solid air seal between wall sleeve and  
chassis. Failure to do so will result in air leakage from  
outdoor to indoor causing system problems i.e. coils  
freezing, short cycling, and constant running of unit. If  
installer is in need of more foam than supplied in kit,  
consult factory.  
Hydronic Only: Remove the 2-position connector as-  
sembly from kit bag supplied with unit (this will have  
2 yellow wires attached). Connect this 2-position  
connector to the 2-position connection located on the  
bottom of the control box panel.  
Figure D7  
To Connect Aquastat:  
Wall Sleeve  
A. Remove the black jumper wire located on the bot-  
tom panel of the control box (this is also terminated  
with a 2-position connector).  
B. Cut the jumper wire in the middle and splice the  
Aquastat to the jumper.  
C. Place the connecter back into original location.  
Refer to wire diagram on the unit for details.  
Front View  
Cooling Chassis  
1x1Foam Tape  
8. Connect line cord.  
9. See Final Inspection and Startup on page 20.  
RC/RH45 PERFORMANCE DATA*  
Cooling  
Btuh  
Heat Pump  
Btuh  
Fresh Air  
CFM  
Unit Size  
EERs  
COP  
9
9,500  
11,900  
14,700  
16,900  
10  
10  
8500  
11400  
13800  
N/A  
2.8  
2.9  
2.8  
N/A  
40/35  
40/35  
40/35  
40/35  
12  
15  
18  
9.2  
9.1  
*Refer to the charts on page 23 for electrical and optional  
electric heat specifications.  
15  
The Right Fit For Comfort  
INSTALLATION INSTRUCTIONS  
RC/RH80 REPLACEMENT PTAC  
Figure A8  
Bafes-Directed Inward  
Toward Coil  
�  
 
 
 
��  
1/2” X 1/2” Supply Air  
Duct Foam Tape  
Air Filter  
8x30” Permanent  
Aluminum Mesh  
3. Take 1/2” x 1/2” open cell foam strips from kit bag and  
apply to sheet metal anges around the perimeter of  
the discharge outlet as shown in (Figure A8). Failure  
to do so results in recirculation of the conditioned air  
around the wall sleeve and through the unit causing the  
unit to short cycle, thus raising operating costs through  
improper heating and cooling.  
RC/RH80 BAFFLE INSTALLATION KIT  
• 1 Installation Manual  
Screws  
• 1 Lt.Baffle  
• 1 Rt.Baffle  
• 1” x 1” Open Cell Foam Tape  
• 1/2” x 1/2” Open Cell Foam Tape  
• 1ea. 2-Position Connector & Pin Mate  
• 14AWG Yellow Wire  
HYDRONIC  
ONLY  
Figure B8  
Wall Sleeve  
1. Take unit out of packaging.  
2. Slide unit into wall sleeve. The supply duct on the  
cooling chassis should line up with the supply vent on  
the room cabinet. The weather angles should require  
no adjustment.  
Front View  
Cooling Chassis  
3. Slide unit out of wallsleeve.  
1x1Foam Tape  
IIMPORTANT: The correct condenser air baffles must  
be installed or performances may be impaired and/or  
the warranty will be voided.  
5. 1” x 1” Open cell foam strips are provided to prevent  
outside air from entering around the chassis to the  
room from the sides and top of the cabinet (Figure B8).  
Install between wall sleeve and cooling chassis. It is  
imperative to have a solid air seal between wall sleeve  
and chassis. Failure to do so will result in air leakage  
from outdoor to indoor causing system problems i.e.  
coils freezing, short cycling, and constant running of  
unit. If installer is in need of more foam than supplied  
in kit, consult factory.  
4. Baffle Installation - Remove bafes from kit bag sup-  
plied with unit. Install left and right side bafes on the  
condenser coil in existing holes:  
• Bafes must come in contact with the outdoor lou-  
ver.  
• Make sure bafes are directed inward toward the  
center of coil.  
Secure bafes tightly to the condenser coil using the  
screws provided. (Figure A8)  
The Right Fit For Comfort  
16  
RC/RH80 INSTALLATION INSTRUCTIONS (Continued)  
7. Connect line cord.  
6. Once condent that all seals are the correct size and in  
the proper location and the correct bafes are attached  
to the condenser coil and in the proper orientation, slide  
unit into final position and tighten any tie down bolts or  
screws as necessary.  
8. See Final Inspection and Startup on page 20.  
RC/RH80 Performance Date*  
UNIT COOLING  
HEAT PUMP  
BTUH  
FRESH  
AIR CFM  
EER  
COP  
Hydronic Only: Remove the 2-position connector as-  
sembly from kit bag supplied with unit (this will have 2  
yellow wires attached). Connect this 2-position connec-  
tor to the 2-position connection located on the bottom  
of the control box panel.  
SIZE  
BTUH  
9
9,500  
11,900  
14,700  
16,900  
10  
10  
8500  
11400  
13800  
N/A  
2.8  
2.9  
2.8  
N/A  
40/35  
40/35  
40/35  
40/35  
12  
15  
18  
9.2  
9.1  
To Connect Aquastat:  
A. Remove the black jumper wire located on the bot-  
tom panel of the control box (this is also terminated  
with a 2-position connector).  
*Refer to the charts on page 23 for electrical and optional  
electric heat specifications.  
B. Cut the jumper wire in the middle and splice the  
Aquastat to the jumper.  
C. Place the connecter back into original location.  
Refer to wire diagram on the unit for details.  
17  
The Right Fit For Comfort  
INSTALLATION INSTRUCTIONS  
RC/RH90 REPLACEMENT PTAC  
3. Baffle Installation - Remove bafes from kit bag sup-  
Install Duct Collar here  
plied with unit. Install left and right side bafes on the  
condenser coil in existing holes:  
• Bafes must come in contact with the outdoor louver  
• Make sure bafes are directed inward toward the  
center of coil  
Secure bafes tightly to the condenser coil using the  
screws provided (Figure A9)  
NOTE: CONTROL BOX IS  
A SEPARATE PART THAT  
IS ELECTRICALLY CON-  
NECTED TO THE CHASSIS  
ON-SITE.  
Figure A9  
Bafes-Directed Inward  
Toward Coil  
�  
 
RC/RH90 BAFFLE INSTALLATION KIT  
 
��  
 
• 1 Installation Manual  
• 1 Lt. & Rt. Bafes  
• 1 Duct Collar  
Screws  
• 1/4” x 3/4” Open Cell Foam Tape  
• 1” x 1” Open Cell Foam Tape  
• 1/2” x 1/2” Open Cell Foam Tape  
1/2” X 1/2” Supply Air  
Duct Foam Tape  
• 1 Slide-Duct  
HYDRONIC  
• 1ea. 2-Position Connector & Pin Mate  
• 14AWG Yellow Wire  
ONLY  
4. Remove 1/2” x 1/2” open cell foam strips from kit ba g  
a nd a pply to sheet metal anges around the perimeter  
of the supply air duct outlet as shown in Figure A9. Fail-  
ure to do so results in recirculation of the conditioned air  
around the wall sleeve and through the unit causing the  
unit to short cycle, thus raising operating costs through  
improper heating and cooling.  
IMPORTANT: The RC/RH90 chassis is 18 1/4” deep for  
the 9,000, 12,000, and 15,000 Btuh models. The standard  
depth for the 18,000 Btuh is 24”. However, EMI can supply  
it for an 18 1/4” chassis on demand.  
1. Remove unit from box and install duct collar.  
Figure B9  
Duct Collar and Slide-Duct Installation  
Wall Sleeve  
• Remove duct collar and slide-duct from packaging.  
• Fasten 1/4” x 1/2” foam tape to the bottom anges  
of the duct collar, this serves as a gasket between  
the collar and the unit.  
Front View  
Securely fasten duct collar over discharge opening  
with screws provided.  
Cooling Chassis  
1x1Foam Tape  
• Insert slide-duct into duct collar. (See illustration  
above)  
5. 1” x 1” Open cell foam strips are provided to prevent  
outside air from entering around the chassis to the  
room from the sides and top of the cabinet (Figure B9).  
Install between wall sleeve and cooling chassis. It is  
imperative to have a solid air seal between wall sleeve  
and chassis. Failure to do so will result in air leakage  
from outdoor to indoor causing system problems i.e.  
coils freezing, short cycling, and constant running of  
unit. If installer is in need of more foam than supplied  
in kit, consult factory.  
2. Slide unit into wall sleeve. The supply duct on the cool-  
ing chassis should line up with the supply vent on the  
room cabinet. The weather angles should require no  
adjustment.  
IMPORTANT: The correct condenser air baffles must  
be installed or performances may be impaired and/or  
the warranty will be voided.  
The Right Fit For Comfort  
18  
RC/RH90 INSTALLATION INSTRUCTIONS (Continued)  
6. Once condent that all seals are the correct size and in  
RC/RH90 FINAL INSPECTION  
AND START-UP  
the proper location and the correct bafes are attached  
to the condenser coil and in the proper orientation, slide  
unit into final position and tighten any tie down bolts or  
screws as necessary.  
( All other units see “Final Inspecton and Startup” page 20)  
1. Mount control box in wall sleeve (in the same location  
as the old control box)  
Hydronic Only: Remove the 2-position connector as-  
sembly from kit bag supplied with unit (this will have 2  
yellow wires attached). Connect this 2-position connec-  
tor to the 2-position connection located on the bottom  
of the control box panel.  
2. Make sure the chassis is level. Check by pouring water  
into the drain pan and making certain it flows through  
the drain hoses to the condenser side of the unit.  
3. Hard wire line voltage to control box and plug cooling  
chassis line cord into control box receptacle and Molex  
plugs.  
To Connect Aquastat:  
A. Remove the black jumper wire located on the  
bottom panel of the control box (this is also ter-  
minated with a 2-position connector).  
B. Cut the jumper wire in the middle and splice the  
aquastat to the jumper.  
IMPORTANT: Follow the information provided on the  
rating plate for voltage and amperage/fuse size for proper  
supply.  
C. Place the connecter back into original location.  
Refer to wire diagram on the unit for details.  
4. Attach the front panel to the existing cabinet enclo-  
sure.  
5. Turn the power on.  
RC 90 CONTROL BOX OPTIONS  
Select one of the following which properly matches the  
control box of your unit.  
6. Check for proper operation (i.e., cooling, optional fresh  
air, and heating if supplied).  
7. Check to be sure nothing will interfere with the room  
discharge air or the return air to the units (i.e., curtains  
or drapes that obstruct the air flow or plush carpeting  
that can obstruct the return air. Items like these can  
cause serious damage to the chassis and can void the  
warranty.  
8. See Sequence of Operation pages 20- 22.  
7. Install the control section:  
RC/RH 90 Performance Date*  
• In a standard unit mount installation, take the thermal  
bulb from the control section and run the line along the  
unit to the blower section. There will be no thermostat  
bulb if a remote thermostat option is used.  
UNIT COOLING  
HEAT PUMP  
BTUH  
FRESH  
AIR CFM  
EER  
COP  
SIZE  
BTUH  
9
9,500  
10  
10  
8500  
11400  
13800  
N/A  
2.8  
2.9  
2.8  
N/A  
40/35  
40/35  
40/35  
40/35  
12  
11,900  
14,700  
16,900  
• While looking at the sides of the blower housing,  
there are two clips that will support the thermal bulb.  
Take out the screws that hold these clips and slide  
the thermal bulb into the clips.  
15  
9.2  
9.1  
18  
*Refer to the charts on page 23 for electrical and optional  
electric heat specifications.  
• Fasten the clips back into place, making sure you do not  
kink the bulb as you might break the thermostat end.  
After the thermostat is back in place, reinstall the front  
cover of the unit and nish the installation.  
8. Connect line cord.  
9. See Final Inspection and Startup page 20.  
19  
The Right Fit For Comfort  
FINAL INSPECTION AND STARTUP  
CAUTION  
discharge air or the return air to the units (i.e., curtains  
!
!
or drapes that obstruct the air flow or plush carpeting  
that can obstruct the return air (see below)). Items like  
these can cause serious damage to the chassis and  
can void the warranty.  
When the unit is first powered up, high humidity condi-  
tions can cause condensation to form on the discharge  
grill. Keep doors and windows closed to reduce humidity  
and condensation will evaporate.  
The pos ition of curta ins or dra pe s  
over supply air grille may cause air to  
recirculate without cooling the room.  
The unit will short cycle and may cause  
premature compressor failure.  
1. Make sure the chassis is level. Check by pouring water  
into the drain pan and making certain it flows through  
the drain hoses to the condenser side of the unit.  
2. Plug or hard wire line voltage to unit.  
IMPORTANT: Follow the information provided on the rat-  
ing plate for voltage and amperage/fuse size for proper  
supply.  
3. Attach the front panel to the existing cabinet enclo-  
sure.  
NOTE: Any obstruction of supply air  
including the use of deflector baffles,  
may cause condensate to form on the  
louver or cabinet.  
4. Turn the power on.  
5. Check for proper operation (i.e., cooling, optional fresh  
air, and heating if supplied).  
To ensure optimum performance of your PTAC,  
avoid restricting the air flow.  
6. Check to be sure nothing will interfere with the room  
SEQUENCE OF OPERATION  
NOTE: RetroAire units can be equipped with Unit  
Mounted or Remote Controlled Thermostats.  
Typical Representation Of A Unit Mount Control  
SYSTEM  
SWITCH  
UNIT MOUNTED THERMOSTAT  
OPERATIONAL INSTRUCTIONS  
Turning the unit mounted thermostat knob to the far left  
will produce the warmest room temperature while turning  
it all the way to the right will produce the coolest. These  
settings can be adjusted for personal comfort.  
FAN SPEED SWITCH  
THERMOSTAT KNOB  
RC12 SAFETY NOTE: When turning the selector switch on  
the RC12 for mode of operation, it is very important to make  
sure the switch position is SEATED” directly on a mode of  
operation (clicks into position). Do not mistakenly place  
between two positions. This can result in a potential fan  
failure while the system is in a cooling or heating operation.  
A fan failure could result in the unit overheating (smoke) in  
an electric heating mode, or freezing coil in a cooling mode.  
COOLING CYCLE:  
1. Place system switch in the COOL position.  
CAUTION  
2. Rotate thermostat knob (below) clockwise until the com-  
pressor fans start running and cold air begins to flow  
from the unit. For a colder room temperature, continue  
turning the thermostat knob clockwise and let the unit  
continue operating to cool the room and remove humid-  
ity. If a warmer room temperature is desired, rotate the  
thermostat knob counter-clockwise until the compressor  
cycles off.  
!
!
Avoid rotating the thermostat knob back and forth from  
heating to cooling. This causes the compressor to cycle  
on and off rapidly and WILL cause damage to the com-  
pressor. Allow the compressor to remain off for at least  
three minutes prior to restarting the unit.  
The Right Fit For Comfort  
20  
SEQUENCE OF OPERATION (Continued)  
UNIT MOUNTED THERMOSTAT OPERATIONAL INSTRUCTIONS (Continued)  
controls will power a normally closed valve that is the  
IMPORTANT: The room temperature must be above  
same voltage as the unit (ex: a unit rated 208/230V  
will power a 208/230V normally closed valve). Be sure  
to check the wiring diagram (located on the unit) and  
voltage application for the specific unit. Other valve  
configurations and voltage options are available. Con-  
sult Technical Service if the unit voltage does not match  
your valve application.  
65º F for the compressor to operate.  
3. Place system switch in the OFF” position. All operation  
should stop.  
HEATING CYCLE - Electric:  
1. Place system switch in the HEAT position.  
2. Rotate thermostat knob counter-clockwise until the  
indoor fans start running and the electric coil starts  
emitting heat. The condenser fans do not run during  
the heating cycle unless the chassis is a heat pump.  
After the unit starts running and the area gets warmer,  
turn the thermostat knob clockwise until a slight click  
is heard and the electric heater turns off. If a warmer  
room temperature is desired, continue turning the knob  
counter-clockwise and let the unit continue operating. If  
a cooler room temperature is desired, rotate the thermo-  
stat knob clockwise until the electric heater cycles off.  
A. Place system switch in the HEAT position.  
B. Turn thermostat knob counter-clockwise. Motorized valve  
should open and allowhotwaterto run through the coil. The  
indoor fans will run, blowing air through the hydronic coil.  
C. Check room comfort level as outlined under Heating  
Cycle - Electric.”  
MOTORIZED FRESH AIR DAMPER (Optional): The  
optional motorized fresh air damper allows the operator  
to move fresh air into the space to be conditioned. This is  
done by placing the damper door switch in the YES” posi-  
tion, opening the damper door and allowing fresh air to be  
moved into the space. To stop the flow of fresh air, simply  
place the switch in the NO” position.  
IMPORTANT: Room temperature must be below 85º F  
to energize the heater.  
3. Place system switch in the OFF” position. All operation  
should stop.  
CHANGEOVERT-STATS(HeatPumpOnly):On units with a  
changeover thermostat, the compressor can run to an outdoor  
temperature of 40° F and then shut off. Electric heat will then  
energize and assume the heating demand until the tempera-  
ture of the outdoor air rises to approximately 5F.  
Manual Reset Limit Switch  
Reset Button  
(5 Kw heat models only) In the  
event the limit switch opens  
and de-energizes the electric  
heat, the limit switch will need  
*Note:  
Button will pop  
FAN CYCLE SWITCH: This option allows the operator of the  
Dual Motor PTAC to have the evaporator fan cycle or run con-  
tinuously. With the switch in the cycling position the evaporator  
fan willonlyrun when the unitis calling forheatorcooling. When  
the switch is in the CONSTANT” position, the evaporator fan  
will run continuously unless the unit is physically turned off.  
to be manually reset.  
out when limit  
To reset switch remove the  
switch opens.  
control box cover.  
Push in to reset.  
• Locate the limit switch.  
Push in the reset button on  
the face of the switch. (Refer to illustration above)  
CONDENSATE REMOVAL: The Dual Motor PTAC has a  
drain connection at each end of the condensate drain pan.  
This allows the condensate to drain through the bulkhead  
to the area near the condenser fan. The condenser fan has  
a slinger ring that picks up the condensate and slings it on  
the hot condenser coil where it evaporates. On heat pump  
models condensate can form on the outdoor coil during  
the heat pump cycle. A temperature sensitive valve in the  
base pan will allow condensate to ow to an internal piping  
system or external drain kit (supplied by others).  
HYDRONIC COIL: The coil with the old unit can be located  
in the subbase, under the chassis in a special attachment,  
or above the chassis in a special attachment. It is neces-  
sary to know where the coil is to be located and the physical  
size of the coil so the right coil can be supplied if ordered for  
replacement. The coil is shipped loose for eld installation.  
It should be installed in the same manner as the coil it is  
replacing. When the hydronic coil is not replaced, installation  
of the chassis should follow the instructions in this manual.  
HEATING CYCLE - Hydronic: All straight cool Dual Motor  
PTACs are equipped with a field supplied hydronic heat op-  
tion. The unit is provided with a two-position molex plug for  
motor valve connection. To wire this option, take the molex  
plug connector with (2) yellow wires from the kit and plug  
it into the molex on the unit. Then wire the opposite end of  
the molex to the motorized valve in the hydronic circuit.  
AQUASTAT CONNECTION (Optional): All straight cool  
Dual Motor PTACs are supplied with a standard high volt  
aquastat connection. The connection is located on the bot-  
tom or side with a black jumper wire installed in molex. To  
wire option take jumper wire and cut in half. Then connect  
2 field supplied wires to the cut ends of jumper and wire  
to aquastat (see wiring diagram for more information). If  
option is not being used simply leave jumper wire con-  
nected to unit.  
IMPORTANT: Make sure the motor valve is rated for the  
correct voltage. Most RetroAire units with unit mount  
21  
The Right Fit For Comfort  
SEQUENCE OF OPERATION (CONTINUED)  
REMOTE THERMOSTAT OPERATIONAL INSTRUCTIONS  
CHOOSING A THERMOSTAT: EMI offers a thermostat  
NOTE: The start of the compressor will not take place until  
that is compatible with your PTAC/PTHP unit. Select EMI  
part number 240-2960 from the latest Retroaire price list  
for this option. This is a single stage, cool/heat, mercury  
bulb thermostat that can be used in all Retroaire cooling,  
heating or heat pump applications. The thermostat has  
an adjustable set-point range of between 55°F and 95°F.  
There are two independent, adjustable stops that can limit the  
heating or cooling range of the thermostat. If a non-mercury,  
electronic thermostatis needed, then choose EMIpartnumber  
240-3926.  
the anti-short/random start time period has elapsed.  
ELECTRIC HEAT OPERATION: Place the thermostat  
s ys te m s witch in he a t mode . Adjus t the s e t-point  
temperature above the room temperature. The electric  
heat will energize along with the indoor fan motor. Heating  
will continue so long as the set-point remains above room  
temperature. Next place the set-point temperature below  
room temperature. The Electric heater will switch off and the  
indoor fan will remain on for an additional sixty seconds.  
HYDRONIC HEAT OPERATION (Optional): An optional  
hydronic heat package may be selected in lieu of electric  
heat. Heating operation is essentially the same as that of  
units with electric heat. With the thermostat system switch  
set to heat and the set-point temperature above room  
temperature, the hydronic valve will open allowing water  
to flow through the coil. The indoor fan will also switch on  
and warm air will flow from the unit. Heating will continue  
so long as the set-point remains above room temperature.  
Place the set-point temperature below room temperature.  
The hydronic valve will close and indoor fan will switch off  
after the sixty-second purge time has elapsed. The hydronic  
valve is a 24Vac normally open valve. Should power be lost  
to the unit, the valve will default to the open position.  
SELECTING A THERMOSTAT “By Others”: Whe n  
selecting a thermostat other than those offered by EMI,  
it is important to choose a single stage heat/cool, 24V  
thermostat. For models 09-17, do NOT select a thermostat  
that requires connection to a C terminal since these units  
do not have provisions for connecting to a C terminal.  
Only models 19 and 24 have provisions for connecting a  
C” terminal to the unit.  
If a thermostat without a C” terminal is used in a models 19  
or 24, then it is important to insulate the unused BROWN C”  
low volt wire to prevent it from shorting at the thermostat.  
COOLING ONLY WITH ELECTRIC HEAT OR HYDRONIC  
HEAT (RC- PTAC’s):Select a thermostat that is compatible  
with a cooling - electric heat system. The thermostat should  
have R, “Y”, “W and G terminals  
HEAT PUMP (Cooling Mode): Cooling operation in a heat  
pump unit is described in “Cooling operation” above. The  
unit is equipped with a reversing valve that is energized for  
cooling and de-energized in heating mode.  
HEAT PUMP WITH ELECTRIC HEAT (RH - PTHP’S):  
Select a thermostat that is compatible with a cooling - single  
stage heat - heat pump system. The thermostat should have  
R, “Y”, “O” and G” terminals. Retroaire units are single  
stage heating only. The electric heat and heat pump will  
not operate simultaneously.  
HEAT PUMP(Heating Mode): Heat pump units are Limited  
Range” equipped with back-up electric resistance heat.  
Limited Range heat pumps are designed to operate when  
outdoor temperatures are between 75°F and 40°F and with  
a maximum indoor temperature of 80°F. When the outdoor  
temperature falls below approximately 40°F the unit will  
switch from heat pump to electric resistance heat. Electric  
heat will then remain as the heat source until the outdoor  
temperatures rise above 50°F. Retroaire heat pumps (RH  
PTHP) are single-stage heating units. The electric heat  
and heat pump will NOT operate simultaneously.  
FAN OPERATION: Some thermostats are equipped with  
an auto/on fan switch. When this switch is placed in the  
on position the indoor fan will run continuous. When the  
switch is in the auto position the indoor fan will cycle with  
the call for heating or cooling.  
FAN PURGE (Optional): After the room thermostat has  
been satised, the purge feature allows the indoor fan to  
remain on for an additional 60 seconds. This increases  
efciency by pulling the remaining energy from the unit.  
To operate the unit in heating mode, it must rst be connected  
to an appropriate heat pump thermostat. (See choosing a  
thermostat). Select heat on the thermostat system switch.  
Then, adjust the set-point temperature above the room  
temperature. The compressor and fan motors will start  
and heating will begin. If the outdoor temperature is below  
approximately 40°F the heat pump system will not operate.  
Electric heat will then take over the heating demand.  
Heating will continue so long as the set-point temperature  
remains above the room temperature. Place the set-point  
COOLING OPERATION: After connecting the thermostat  
to the unit place the system switch in cool mode. Adjust the  
set-point temperature below the room temperature. The  
compressor and fan motors will start and cooling will begin.  
Place the set-point temperature above the room temperature.  
The compressor and condenser fan will stop and the indoor  
fan will remain on for an additional sixty seconds.  
The Right Fit For Comfort  
22  
SEQUENCE OF OPERATION (CONTINUED)  
condition be detected, the compressor and condenser fan  
temperature below the room temperature. The heating  
mode will cease and the indoor fan will remain on for an  
additional sixty seconds.  
will be switched off for a minimum of three minutes and until  
the freeze condition is satised. During this time the indoor  
fan will continue to run to aid in the defrost process.  
NOTE: The start of the compressor will not take place until  
AJ4004 CONTROL BOARD: There are two sets of jumper  
pins on the control board that are factory set so there  
should no need to set them later on in the field. The rst  
is a set of three pins labeled HP for selection of either a  
Straight Coolor Heat Pump” unit. For Straight Cool” the  
center pin and outer most pin (usually on the top) are to be  
jumped together. For Heat Pump units the center pin and  
the pin closest to the relay are to be jumped together (see  
Firure #1).  
the anti-short/random start time period has elapsed.  
HEAT PUMP (Emergency Heat)  
WARNING  
!
!
Before accessing the control compartment, disconnect  
power to the unit. Failure to do so could result in  
serious injury or electrical shock.  
Should the heat pump system fail, it is possible to force the  
control board into electric heat mode. This is a temporary  
solution until the heat pump system can be repaired.  
Locate the circuit board in the control section of the unit.  
Locate the terminals where the outdoor sensor connects  
to the circuit board. Using a small needle nose type pliers,  
disconnect one side of the sensor from the circuit board.  
This will appear to the circuit board as an outdoor coil freeze  
condition there-by energizing the electric resistance heater  
on the call for heat.  
The second is a set of two pins labeled TEST. When these  
two pins are jumped together, all timers are eliminated (i.e.  
anti-short, purge, ect.). This is mainly used for production  
line testing however it may also be useful for eld-testing  
as well. The units are shipped with the TEST” jumper on  
only one of the pins. Please, do not leave a unit with the  
test jumper in the test mode (see Firure #2).  
Figure #1  
STRAIGHT COOL/HEAT PUMP JUMER  
HEAT PUMP (Thermostatic Drain Pan Valve): Heat pump  
units are equipped with a thermostatic drain valve that will  
open when outdoor temperatures fall below 50°F. This  
keeps the base pan free of condensate water where it may  
otherwise freeze during colder outdoor temperatures. As  
part of its normal operation, the unit will produce condensate  
and collect it in the base pan of the unit. There it will be  
picked up by the condenser fan slinger ring and deposited  
onto the condenser coil. During the cooling season, this  
improves the units efciency by maintaining adequate  
refrigeration system pressures.  
HP  
HP  
HEAT PUMP  
STRAIGHT COOL  
Figure #2  
ANTI-SHORT CYCLE TIMER Random Start Feature:  
This feature will prevent compressor short cycling and also  
prevent multiple units in a single facility from simultaneously  
starting following a power outage. This delay on break  
feature ensures that the compressor remains off, between  
cycles, until the three-minute time delay period has elapsed  
allowing system pressures to equalize before re-starting.  
TEST JUMPER POSITION  
FOR NORMAL OPERATION  
The LED Blink codes are as listed in below.  
The random start feature, initiated after a power failure,  
will add a random time delay (between 5-120 seconds) to  
the three-minute anti short cycle time following a power  
outage. This will stagger the starting of multiple units in a  
single facility allowing a building to slowly go back on line  
when power is restored.  
1 Blink Normal Operation  
2 Blinks Compressor Lockout (ASCT)  
3 Blinks Outdoor freeze condition  
4 Blinks Indoor freeze condition  
5 Blinks Simultaneous W & Y Call  
Important sensor resistances are as follows.  
77 °F - 10K ohms  
INDOOR COIL FREEZE PROTECTION: This feature will  
prevent the indoor coil from freeze up in the cooling mode.  
Indoor coil freeze up can occur due to a dirty air filter, low  
refrigerant charge or low room or outdoor temperatures.  
This in turn can cause compressor damage. Should a freeze  
50 °F - 19.9K ohms  
35 °F - 30K ohms  
30 °F - 34.4K ohms  
23  
The Right Fit For Comfort  
CLEANING AND MAINTENANCE  
11. Replace panels and reconnect electrical power.  
12. Test unit operation.  
CLEANING THE INTERIOR OF THE UNIT  
DANGER  
!
!
CLEANING THE EXTERIOR  
Before servicing the RetroAire Dual Motor PTAC, be  
sure to turn off electrical power to the unit. Failure to  
do so can result in a fire, explosion or electrical shock  
causing property damage, personal injury or death.  
1. Clean the air filter at least once a month by removing  
it from the unit and washing or vacuuming any dust  
from its surface. Allowing dust to collect on the lter  
will cause the PTAC to lose efciency and eventually  
malfunction.  
1. Disconnect power from unit.  
2. Remove access panels and do a visual inspection of  
the unit, making sure to check for obvious problems  
such as damaged coils or evidence of extended wear  
on any moving part.  
2. When cleaning the lter, be sure to vacuum any dust  
from the return air grille surface as well.  
3. Clean exterior of the cabinet as desired with a mild soap  
or household cleaner.  
3. Check for unusual odors, oil leaks, or stains on or  
around the coil and refrigerant lines. The presence of  
oil here may indicate a potentially serious problem such  
as a refrigerant leak.  
IMPORTANT: If a new air filter is needed for your  
RetroAire Dual Motor PTAC, consult factory for avail-  
ability and/or proper sizing.  
4. Inspect all electrical connections. Look for frayed wires  
and poor connections. Terminal ends that are loose will  
eventually fail, causing a loss of performance or worse.  
TROUBLESHOOTING  
5. Check fan motors and blower assemblies. Some units  
may require a drop of light oil to motors and/or bearing  
assemblies (look for oil cups). Check setscrews and  
motor mounting hardware, making sure they are tight.  
NO HEAT OR COOLING: Check to see if the unit has  
power and if the thermostat is satised. If the thermostat is  
not satised, refer to the wiring diagram and check control  
components for continuity.  
6. Brush and/or vacuum the centrifugal fan blades and  
blower cage assemblies. These parts must be clean to  
operate efciently.  
Check The Manual Reset Limit Switch  
(5 Kw heat models only)  
Reset Button  
In the event the limit switch  
opens and de-energizes  
the electric heat, the limit  
switch will need to be man-  
ually reset.  
7. Inspect and clean the indoor and outdoor coils, using a  
fin comb, if necessary, to straighten any damaged ns.  
these coils must be clean for proper operation.  
*Note:  
Button will pop  
out when limit  
switch opens.  
Push in to reset.  
IMPORTANT: Do not use a solvent-based cleaner  
on the indoor or outdoor coils. Some solvents can  
produce a noxious odor when starting the fan or  
electric heat.  
To reset switch remove  
the control box cover.  
• Locate the limit switch.  
Push in the reset button  
8. Inspect and clean the drain pan and drainline (if any).  
Use of an anti-fungicide tablet is recommended to  
keep the condensate system free from bacterial con-  
taminants.  
on the face of the switch. (Refer to illustration above)  
9. Check weep holes along the rear ange of the base pan,  
making sure they are open.  
WARNING  
!
!
It is illegal to discharge refrigerant into the atmo-  
sphere. Use proper reclaiming methods and equip-  
ment when servicing a RetroAire Dual Motor PTAC.  
10. Check the pitch of the unit. Over time the building and  
equipment may settle, causing a shift in the direction  
of the condensate ows. Ideally the unit should pitch  
a minimum of 5° (at least ½) to the outside to allow for  
proper drainage.  
The Right Fit For Comfort  
24  
SPECIFICATIONS FOR THE RC/RH10/20/35/45/80/90 & RC11/12/21  
Due to EMI’s ongoing development programs, design, specifications, and performance data may change without notice.  
When installing the RC/RH10/20/35/45/80/90 or the RC11/12/21 refer to  
the charts below for electrical and optional electric heat specications.  
RC/RH10/20/35/45/80/90 & RC11/21 Electrical Specifications*  
Model  
Evap Motor  
Cond Motor  
Compressor  
Total  
Amps  
10.4  
5.4  
Min  
Voltage  
Voltage/hz/ph  
MCA Max Fuse  
Line Cord  
Number  
FLA  
1.4  
Hp  
FLA  
1.6  
Hp  
RLA  
7.4  
LRA  
44  
20  
18  
54  
28  
26  
35  
32  
45  
32  
115/60/1  
208/230/60/1  
265/60/1  
0.09  
0.08  
0.08  
0.09  
0.08  
0.08  
0.08  
0.08  
0.08  
0.08  
0.125  
0.125  
0.125  
0.125  
0.125  
0.125  
0.125  
0.125  
0.09  
12.3  
6.4  
15  
15  
15  
20  
15  
15  
15  
15  
15  
15  
104  
197  
240  
104  
197  
240  
197  
240  
197  
240  
5-15P  
6-15P  
7-20P  
5-20P  
6-15P  
7-20P  
6-15P  
7-20P  
6-15P  
7-20P  
9
0.6  
0.72  
0.7  
4.1  
0.67  
1.4  
3.35  
9.7  
4.7  
5.6  
115/60/1  
1.6  
12.7  
6.4  
15.1  
7.7  
12  
208/230/60/1  
265/60/1  
0.6  
0.72  
0.7  
5.1  
0.67  
0.6  
4.25  
6.4  
5.6  
6.7  
208/230/60/1  
265/60/1  
0.72  
0.7  
7.7  
9.3  
15  
18  
0.67  
0.6  
5.4  
6.8  
8.1  
208/230/60/1  
265/60/1  
0.71  
0.71  
7.6  
8.9  
10.8  
9.3  
0.67  
0.09  
6.3  
7.7  
Note: 18,000 not available in heat pump application.  
RC/RH10/20/35/45/80/90 & RC11/12/21 Optional Electric Heat Specifications*  
Total Heat  
Amps  
8.5  
Max  
Fuse  
Line  
Cord  
Heater No. Voltage Watts  
Btuh  
Amps  
MCA  
208  
230  
265  
208  
230  
265  
208  
230  
265  
208  
230  
1636  
2000  
2655  
2454  
3000  
3983  
3271  
4000  
5310  
4089  
5000  
5600  
6900  
7.9  
10.4  
11.5  
13.2  
15.3  
16.9  
19.5  
20.3  
22.3  
25.7  
25.2  
27.8  
15  
15  
15  
20  
20  
20  
25  
25  
30  
30  
30  
6-15P  
6-15P  
7-20P  
6-20P  
6-20P  
7-20P  
6-30P  
6-30P  
7-30P  
6-30P  
6-30P  
2
3
8.7  
9.3  
9100  
10.0  
11.8  
13.0  
15.0  
15.7  
17.4  
20.0  
19.7  
21.7  
10.7  
8400  
12.4  
10300  
13600  
11200  
13700  
18200  
14000  
17100  
13.6  
15.7  
16.3  
4
5
18.0  
20.7  
20.3  
22.3  
RC12 Electrical Specifications*  
Model  
Evap Motor  
Cond Motor  
Compressor  
Total  
Max  
Fuse  
Min  
Voltage  
Line  
Cord  
Voltage/hz/ph  
MCA  
Number  
FLA  
Hp  
FLA  
0.71  
0.71  
0.71  
0.71  
Hp  
RLA  
5.1  
LRA  
Amps  
6.4  
208/230/60/1  
265/60/1  
0.6  
0.67  
0.6  
0.08  
0.08  
0.08  
0.08  
0.09  
0.09  
0.09  
0.09  
28  
26  
45  
32  
7.7  
6.7  
15  
15  
15  
15  
197  
240  
197  
240  
6-15P  
7-20P  
6-15P  
7-20P  
12  
15  
4.25  
7.6  
5.6  
208/230/60/1  
265/60/1  
8.9  
10.8  
9.3  
0.67  
6.3  
7.7  
NEMA Specifications Non-Locking/Receptacles  
* Note: Data will vary if alternate components (including compressor or motor) are used to meet production needs.  
Consult factory for current electrical specifications.  
25  
The Right Fit For Comfort  
ALL PRODUCT LIMITED WARRANTY  
Enviromaster International LLC (EMI) warrants to the purchaser/owner that EMI products will be free from  
defects in material and workmanship under the normal use and maintenance for a period of twelve months for  
all components and sixty months on unit compressors from the date of original installation, or fifteen months  
for all components and sixty-three months on unit compressors from the date of manufacture, whichever  
comes rst.  
WHAT WE WILL COVER  
EMI will replace any defective part returned to EMI’s approved service organization with a new or rebuilt part  
at no charge. The replacement part assumes that unused portion of this warranty.  
WHAT WE DON’T COVER  
THIS WARRANTY DOES NOT INCLUDE LABOR or other costs incurred for repairing, removing, installing,  
shipping, servicing, or handling of either defective or replacement parts.  
EMI IS NOT RESPONSIBLE FOR:  
• Normal maintenance  
• Damage or repairs required as a consequence of faulty installation or application by others.  
• Failure to start due to voltage conditions, blown fuses, open circuit breakers, or other damages due to the  
inadequacy or interruption of electrical service.  
• Damage or repairs needed as a consequence of any misapplication, abuse, improper servicing, unauthor-  
ized alteration, or improper operation.  
• Damage as a result of oods, winds, res, lightening, accidents, corrosive atmosphere, or other conditions  
beyond the control of EMI.  
Parts not supplied or designated by EMI.  
Products installed outside the United States or Canada.  
• Any damages to person or property of whatever kind, direct or indirect, special or consequential, whether  
resulting from use or loss of use of the product.  
LIMITATION OF WARRANTIES  
This warranty is exclusive and in lieu of any implied warranties of merchantability and tness for a particular  
purpose and all other warranties express or implied. The remedies provided for in this warranty are exclusive  
and shall constitute the only liabilities on the part of EMI including any statements made by any individual  
which shall be of no effect.  
FOR SERVICE OR REPAIR:  
(1) Contact the Installer  
(2) Call the nearest Distributor  
(3) Call or write:  
ENVIROMASTER INTERNATIONAL LLC  
5780 Success Dr., Rome, NY 13440  
The Right Fit For Comfort  
26  

Briggs Stratton AIR CLEANER 286700 User Manual
Canon Printer S830D User Manual
Carrier 50DP016 User Manual
Cornelius Ice Drink Dispenser Enduro 250 User Manual
Cornelius MJ31 4 PB User Manual
Friedrich Air Conditioner CP08E10 User Manual
Friedrich MR09Y1F User Manual
Friedrich QUIETMASTER 2008 User Manual
Goodman Mfg Co LP Air Conditioner 2 to 5 Tone Packaged Air Conditioner User Manual
HP Hewlett Packard LASERJET 2400 User Manual