| S e r v i c e M a n u a l – R 4 1 0 A Models   A Series (Electronic Controls)   Single Package Vertical Air Conditioning System   L Suffix Models   V(E, H)A09K25L-*   V(E, H)A12K25L-*   V(E, H)A18K25L-*   V(E, H)A24K25L-*   V(E, H)A24K75L-*   V(E, H)A09K34L-*   V(E, H)A12K34L-*   V(E, H)A18K34L-*   V(E, H)A24K34L-*   V(E, H)A24K10L-*   V(E, H)A09K50L-*   V(E, H)A12K50L-*   V(E, H)A18K25L-*   V(E, H)A24K50L-*   VPK-ServMan-L (1-10)   *Last Digit May Vary   Table of Contents   Important Safety Information ........................................... 2-4   Capillary Tube Systems/Check Valve ..........................24   Reversing Valve — Description/Operation .................. 25   Testing Coil .................................................................. 25   Checking Reversing Valves ....................................25-26   Introduction .........................................................................4   Vert-I-Pak Model Number Identification Guide ................... 5   Serial Number Identification Guide .................................... 5   Chassis Specifications ....................................................... 6   Extended Cooling Performance ......................................... 7   Electrical Requirements ..................................................... 8   Remote Thermostat and Low Voltage Control .............. 9-10   V-PAK Electronic Control Board Features ........................ 11   Electronic Control Configuration .......................................12   Reversing Valve   Touch Testing Heating/Cooling Cycle ......................... 26   Procedure For Changing Reversing Valve ............. 26-27   Compressor Checks .................................................... 27   Locked Rotor Voltage Test .......................................... 27   Single Phase Connections ......................................... 27   Determine Locked Rotor Voltage ............................... 27   Locked Rotor Amperage Test ...................................... 27   Single Phase Running & Locked Rotor Amperage ..... 27   Checking the Overload ...........................................27-28   External Overload ........................................................28   Compressor Single Phase Resistance Test ................ 28   Compressor Replacement ..................................... 29-30   Routine Maintenance ...................................................30   9-18 Electrical Troubleshooting Chart – Cooling ......... 31   2-Ton Electrical Troubleshooting Chart – Cooling ....... 32   Electrical Troubleshooting Chart – Heat Pump ........... 33   Refrigerant System Diagnosis – Cooling .................... 34   Refrigerant System Diagnosis – Heating .................... 34   Electrical and Thermostat Wiring Diagrams ........... 35-40   Technical Service Data ................................................ 41   Electronic Control Error Code   Diagnostics/Test Mode .................................................12-13   Electronic Control Features .............................................. 14   Checking External Static Pressure ................................... 15   Checking Approximate Airflow .......................................... 16   Airflow Charts ....................................................................16   Components Testing ....................................................17-18   Refrigeration Sequence of Operation ............................... 19   Service ............................................................................. 20   Sealed Refrigeration System Repairs .............................. 21   Refrigerant Charging ........................................................ 21   Method Of Charging ......................................................... 22   Undercharged Refrigerant Systems ............................ 22-23   Overcharged Refrigerant Systems ................................... 23   Restricted Refrigerant Systems ....................................... 23   1 IMPORTANT SAFETY INFORMATION   The information contained in this manual is intended for use by a qualified service technician who is familiar   with the safety procedures required for installation and repair, and who is equipped with the proper tools and   test instruments required to service this product.   Installation or repairs made by unqualified persons can result in subjecting the unqualified person making   such repairs as well as the persons being served by the equipment to hazards resulting in injury or electrical   shock which can be serious or even fatal.   Safety warnings have been placed throughout this manual to alert you to potential hazards that may be   encountered. If you install or perform service on equipment, it is your responsibility to read and obey these   warnings to guard against any bodily injury or property damage which may result to you or others.   Your safety and the safety of others are very important.   We have provided many important safety messages in this manual and on your appliance. Always read   and obey all safety messages.   This is a safety Alert symbol.   This symbol alerts you to potential hazards that can kill or hurt you and others.   All safety messages will follow the safety alert symbol with the word “WARNING”   or “CAUTION”. These words mean:   You can be killed or seriously injured if you do not follow instructions.   WARNING   You can receive minor or moderate injury if you do not follow instructions.   CAUTION   All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury,   and tell you what will happen if the instructions are not followed.   A message to alert you of potential property damage will have the   word “NOTICE”. Potential property damage can occur if instructions   are not followed.   NOTICE   PERSONAL INJURY OR DEATH HAZARDS   ELECTRICAL HAZARDS:   • Unplug and/or disconnect all electrical power to the unit before performing inspections,   maintenance, or service.   • • • Make sure to follow proper lockout/tag out procedures.   Always work in the company of a qualified assistant if possible.   Capacitors, even when disconnected from the electrical power source, retain an electrical charge   potential capable of causing electric shock or electrocution.   • • Handle, discharge, and test capacitors according to safe, established, standards, and approved   procedures.   Extreme care, proper judgment, and safety procedures must be exercised if it becomes necessary   to test or troubleshoot equipment with the power on to the unit.   2 • • Do not spray or pour water on the return air grille, discharge air grille, evaporator coil, control panel,   and sleeve on the room side of the air conditioning unit while cleaning.   Electrical component malfunction caused by water could result in electric shock or other electrically   unsafe conditions when the power is restored and the unit is turned on, even after the exterior is dry.   • • • • • • • Never operate the A/C unit with wet hands.   Use air conditioner on a single dedicated circuit within the specified amperage rating.   Use on a properly grounded outlet only.   Do not remove ground prong of plug.   Do not cut or modify the power supply cord.   Do not use extension cords with the unit.   Follow all safety precautions and use proper and adequate protective safety aids such as: gloves,   goggles, clothing, adequately insulated tools, and testing equipment etc.   • Failure to follow proper safety procedures and/or these warnings can result in serious injury or death.   REFRIGERATION SYSTEM HAZARDS:   • • • Use approved standard refrigerant recovering procedures and equipment to relieve pressure before   opening system for repair.   Do not allow liquid refrigerant to contact skin. Direct contact with liquid refrigerant can result in minor   to moderate injury.   Be extremely careful when using an oxy-acetylene torch. Direct contact with the torch’s flame or hot   surfaces can cause serious burns.   • • • Make sure to protect personal and surrounding property with fire proof materials.   Have a fire extinguisher at hand while using a torch.   Provide adequate ventilation to vent off toxic fumes, and work with a qualified assistant whenever   possible.   • • • Always use a pressure regulator when using dry nitrogen to test the sealed refrigeration system for   leaks, flushing etc.   Make sure to follow all safety precautions and to use proper protective safety aids such as: gloves,   safety glasses, clothing etc.   Failure to follow proper safety procedures and/or these warnings can result in serious injury or death.   MECHANICAL HAZARDS:   • Extreme care, proper judgment and all safety procedures must be followed when testing,   troubleshooting, handling, or working around unit with moving and/or rotating parts.   • Be careful when, handling and working around exposed edges and corners of sleeve, chassis, and   other unit components especially the sharp fins of the indoor and outdoor coils.   • • Use proper and adequate protective aids such as: gloves, clothing, safety glasses etc.   Failure to follow proper safety procedures and/or these warnings can result in serious injury or death.   3 PROPERTY DAMAGE HAZARDS   FIRE DAMAGE HAZARDS:   • • • • • • • Read the Installation/Operation Manual for this air conditioning unit prior to operating.   Use air conditioner on a single dedicated circuit within the specified amperage rating.   Connect to a properly grounded outlet only.   Do not remove ground prong of plug.   Do not cut or modify the power supply cord.   Do not use extension cords with the unit.   Failure to follow these instructions can result in fire and minor to serious property damage.   WATER DAMAGE HAZARDS:   • Improper installation maintenance, or servicing of the air conditioner unit, or not following the above   Safety Warnings can result in water damage to personal items or property.   • • • Insure that the unit has a sufficient pitch to the outside to allow water to drain from the unit.   Do not drill holes in the bottom of the drain pan or the underside of the unit.   Failure to follow these instructions can result in result in damage to the unit and/or minor to serious   property damage.   4 Model Identification Guide   MODEL NUMBER   V E A 24 K 50 RT L   SERIES   V=Vertical Series   ENGINEERING CODE   E=Cooling with or without electric heat   H=Heat Pump   OPTIONS   RT = Standard Remote Operation   d   DESIGN SERIES   A = 32" and 47" Cabinet   NOMINAL CAPACITY   A-Series (Btu/h)   09 = 9,000   ELECTRIC HEATER SIZE   A-Series   00 = No electric heat   25 = 2.5 KW   12 = 12,000   18 = 18,000   34 = 3.4 KW   24 = 24,000   50 = 5.0 KW   75 = 7.5 KW   10 = 10 KW   VOLTAGE   K = 208/230V-1Ph-60Hz   VPAK Serial Number Identification Guide   SERIAL NUMBER   A K A N 00001   YEAR MANUFACTURED   PRODUCTION RUN NUMBER   LJ = 2009 AE = 2015   AK = 2010 AF = 2016   AA = 2011 AG = 2017   AB = 2012 AH = 2018   AC = 2013 AJ = 2019   AD = 2014   PRODUCT LINE   N = VPAK   MONTH MANUFACTURED   A = Jan   B = Feb   C = Mar   D = Apr   E = May   F = Jun   G = Jul   H = Aug   J = Sep   K = Oct   L = Nov   M = Dec   5 Chassis Specifications   Model 2010   COOLING DATA   VEA09K VEA12K VEA18K VEA24K   VHA09K VHA12K VHA18K VHA24K   COOLING BTUh   POWER (W)   EER   9400/9000 11500/11200 17000/16500 23000/22700   9200/9000 11500/11200 17000/16800 23000/22800   959   9.8/9.8   0.74   1173   9.8/9.8   0.72   1888   9.0/9.0   0.70   2421   9.5/9.5   0.70   939   9.8/9.8   0.74   1186   9.7/9.7   0.72   1868   9.1/9.1   0.70   2527   9.1/9.1   0.70   SENSIBLE HEAT RATIO   HEAT PUMP DATA   HEATING BTUh   COP @ 47F   N/A   N/A   N/A   N/A   8500   3.0   10800   3.0   16000   3.0   20000   3.0   HEATING POWER (W)   830   3.6   1055   4.9   1563   7.5   1953   9.4   HEATING CURRENT (A)   ELECTRICAL DATA   VOLTAGE (1 PHASE, 60 Hz)   VOLT RANGE   230/208   253-198   4.2/4.4   19.8   230/208   253-198   5.2/5.4   30   230/208   253-198   8.1/8.5   42   230/208   253-198   10.0/10.4   34.8   230/208   253-198   4.1/4.3   18.5   230/208   253-198   5.3/5.5   26   230/208   253-198   8.2/8.5   42   230/208   253-198   10.6/10.8   34.8   COOLING CURRENT (A)   AMPS L.R.   AMPS F.L.   3.5   4.5   7.8   9.5   3.5   5 7.8   9.5   INDOOR MOTOR (HP)   INDOOR MOTOR (A)   OUTDOOR MOTOR (HP)   1/4   1/4   1/4   1/4   1/4   1/4   1/4   1/4   1.2   1.2   1.2   1.94   1.2   1.2   1.2   1.94   N/A   1/4   N/A   1/4   OUTDOOR MOTOR (A)   N/A   0.85   N/A   0.85   AIRFLOW DATA   INDOOR CFM*   VENT CFM   300   60   350   60   450   60   610   60   300   60   420   60   450   60   610   60   MAX. ESP   .3"   .3"   .3"   .4"   .3"   .3"   .3"   .4"   PHYSICAL   DIMENSIONS (W x D x H)   NET WEIGHT (LBS)   23x23x32   114   23x23x32   124   23x23x32   144   23x23x47   167   23x23x32   114   23x23x32   125   23x23x32   144   23x23x47   167   SHIPPING WEIGHT (LBS)   R410A CHARGE (oz)   125   135   155   220   125   135   155   220   33.5   35.5   48   65   39   42   52   74   * Normal Value Wet Coil @ .1"ESP.   ELECTRIC HEAT DATA   VE/VHA09   VE/VHA12   HEATER WATTS   2500/2050 3400/2780 5000/4090 2500/2050 3400/2780 5000/4090   230/208 230/208   8500/7000 11600/9500 17000/13900 8500/7000 11600/9500 17000/13900   VOLTAGE   HEATING BTUh   HEATING CURRENT (AMPS)   MINIMUM CIRCUIT AMPACITY   BRANCH CIRCUIT FUSE (AMPS)   BASIC HEATER SIZE   10.9/9.9   15   15   2.5 Kw   14.8/13.4   19.9   20   3.4 Kw   21.7/19.7   28.6   30   5.0 Kw   10.9/9.9   15   15   2.5 Kw   14.8/13.4   19.9   20   3.4 Kw   21.7/19.7   28.6   30   5.0 Kw   ELECTRIC HEAT DATA   VE/VHA18   VE/VHA24   HEATER WATTS   2500/2050 3400/2780 5000/4090 2500/2050 3400/2780 5000/4090 7500/6135 10000/8180   230/208 230/208   8500/7000 11600/9500 17000/13900 8500/7000 11600/9500 17000/1390025598/2093934130/27918   VOLTAGE   HEATING BTUh   HEATING CURRENT (AMPS)   MINIMUM CIRCUIT AMPACITY   BRANCH CIRCUIT FUSE (AMPS)   BASIC HEATER SIZE   10.9/9.9   15   15   2.5 Kw   14.8/13.4   19.9   20   3.4 Kw   21.7/19.7   28.6   30   5.0 Kw   10.9/9.9   17.2/15.9   25   14.8/13.4   22.1/20.3   25   21.7/19.7   30.7/28.1   30   32.6/29.5   44.3/40.3   45   43.5/39.3   57.9/52.7   60   2.5 Kw   3.4 Kw   5.0 Kw   7.5 Kw   10.0 Kw   6 Extended Cooling Performance   VEA - EXTENDED COOLING PERFORMANCE   OUTDOOR DRY BULB TEMP. (DEGREES F AT 40% R.H.)   85 95 105   INDOOR WET BULB TEMP. (DEGREES F AT 80 F D.B.)   67 62 72 67 62 72 67   75   67   110   67   72   62   72   62   72   62   BTUh   WATTS   AMPS   SHR   BTUh   WATTS   AMPS   SHR   BTUh   WATTS   AMPS   SHR   BTUh   WATTS   AMPS   SHR   11054 10631 9842 10528 9926 9156 10114 9400 8319 9475 8413 7417 8954 7835 6914   783   3.5   0.51   795   3.5   0.69   804   3.5   0.93   853   3.7   0.52   861   3.8   0.71   872   3.8   0.95   959   4.2   0.52   959   4.20   0.74   959   4.2   0.95   1037 1036 1039 1084 1083 1087   VEA09   VEA12   VEA18   VEA24   4.5   4.5   4.5   4.7   4.7   4.7   0.53   0.78   0.96   0.55   0.81   0.95   13524 13007 12041 12880 12144 11201 12374 11500 10178 11592 10293 9074 10954 9585 8458   957   4.3   0.49   972   4.3   0.67   983   4.4   0.90   1043 1053 1066 1173 1173 1173 1268 1267 1270 1325 1325 1330   4.6   4.7   4.7   5.2   5.20   0.72   5.2   5.6   5.6   5.6   5.9   5.9   5.9   0.50   0.70   0.92   0.51   0.92   0.52   0.76   0.93   0.53   0.79   0.93   19992 19227 17799 19040 17952 16558 18292 17000 15045 17136 15215 13413 16193 14170 12504   1541 1565 1582 1678 1695 1716 1888 1888 1888 2041 2039 2045 2133 2132 2140   6.7   0.48   6.7   0.65   6.8   0.88   7.2   0.49   7.2   0.68   7.3   0.89   8.1   0.49   8.10   0.70   8.1   0.90   8.7   0.50   8.7   0.74   8.7   0.90   9.1   0.52   9.1   0.76   9.1   0.9   27048 26013 24081 25760 24288 22402 24748 23000 20355 23184 20585 18147 21908 19171 16917   1976 2007 2029 2152 2174 2201 2421 2421 2421 2617 2615 2622 2736 2735 2744   8.3   0.48   8.3   0.65   8.4   0.88   8.9   0.49   9.0   0.68   9.0   0.89   10.0 10.00 10.1   0.49 0.70 0.9   10.8   0.5   10.8   0.74   10.8   0.9   11.3   0.52   11.3   0.76   11.3   0.9   RATING POINT   ARI 310/380   VHA - EXTENDED COOLING PERFORMANCE   OUTDOOR DRY BULB TEMP. (DEGREES F AT 40% R.H.)   85 95 105   INDOOR WET BULB TEMP. (DEGREES F AT 80 F D.B.)   67 62 72 67 62 72 67   75   110   67   72   67   62   72   62   72   62   BTUh   WATTS   AMPS   SHR   BTUh   WATTS   AMPS   SHR   BTUh   WATTS   AMPS   SHR   BTUh   WATTS   AMPS   SHR   10819 10405 9632 10304 9715 8961 9899 9200 8142 9274 8234 7259 8763 7668 6767   766   3.4   0.51   778   3.4   0.69   787   3.5   0.93   835   3.7   0.52   843   3.7   0.71   854   3.7   0.95   939   4.1   0.52   939   4.10   0.74   939   4.1   0.95   1015 1014 1017 1061 1061 1064   VHA09   VHA12   VHA18   VHA24   4.4   4.4   4.4   4.6   4.6   4.6   0.53   0.78   0.96   0.55   0.81   0.95   13524 13007 12041 12880 12144 11201 12374 11500 10178 11592 10293 9074 10954 9585 8458   968   4.4   0.49   983   4.4   0.67   994   4.5   0.9   1054 1065 1078 1186 1186 1186 1282 1281 1284 1340 1340 1344   4.7   0.5   4.7   0.7   4.8   0.92   5.3   0.51   5.30   0.72   5.3   0.92   5.7   0.52   5.7   0.76   5.7   0.93   6 0.53   6 0.79   6 0.93   19992 19227 17799 19040 17952 16558 18292 17000 15045 17136 15215 13413 16193 14170 12504   1524 1549 1565 1661 1677 1698 1868 1868 1868 2019 2017 2023 2111 2110 2117   6.8   0.48   6.8   0.65   6.9   0.88   7.3   0.49   7.3   0.68   7.4   0.89   8.2   0.49   8.20   0.70   8.2   0.90   8.8   0.50   8.8   0.74   8.9   0.90   9.2   0.52   9.2   0.76   9.3   0.9   27048 26013 24081 25760 24288 22402 24748 23000 20355 23184 20585 18147 21908 19171 16917   2062 2095 2118 2247 2269 2297 2527 2527 2527 2732 2729 2737 2856 2854 2864   8.8   0.48   8.8   0.65   8.9   0.88   9.4   0.49   9.5   0.68   9.5   0.89   10.5 10.60 10.7   0.49 0.70 0.90   11.4   0.50   11.4   0.74   11.4   0.90   11.9   0.52   11.9   0.76   12   0.9   RATING POINT   ARI 310/380   7 WARNING   ELECTRIC SHOCK HAZARD   Turn off electric power before service or instal-   lation. All electrical connnections and wiring   MUST be installed by a qualified electrician and   conform to the National Electrical Code and all   local codes which have jurisdiction. Failure to   do so can result in personal injury and/or death.   ELECTRICAL REQUIREMENTS   Wire Size   “Use ONLY time delayed fused disconnect or HACR type circuit breaker as indicated on the unit’s rating plate (see   sample on this page). Proper current protection to the unit is the responsibility of the owner”.   Unit MUST   All units must be hard wired with properly sized breaker. See nameplate for specific chassis electrical requirements.   See Electrical Rating Table below for wire size. Use HACR type breakers to avoid nuisance trips. All field wiring must be done   in accordance with NEC and local codes.   Electrical Rating Tables   15A   20A   30A   14   12   10   Supply voltage   Supply voltage to the unit should be a nominal 208/230 volts. It must be between 197 volts and 253 volts. Supply voltage to   the unit should be checked WITH THE UNIT IN OPERATION. Voltage readings outside the specified range can be expected   to cause operating problems. Their cause MUST be investigated and corrected.   Sample Nameplate   120524   COOLING EQUIPMENT   FOLLOWING ITEMS   OUTDOOR GRILLE   INDOOR GRILLE   8 ReMOTe TheRMOsTAT AND LOw VOLTAge CONTROL   CONNeCTIONs   Auto On   Cool Off Heat   RT5 (Two speed fan)   RT4 (One speed fan)   Remote Thermostat   Location   All Friedrich Vert-I-Pak units are factory configured to be   controlled by using a 24V single stage remote wall mounted   thermostat. The thermostat may be auto or manual changeover   as long as the control configuration matches that of the   Vert-I-Pak unit.   The thermostat should not be mounted where it may be   affected by drafts, discharge air from registers (hot or cold),   or heat radiated from the sun or appliances.   The thermostat should be located about 5 Ft. above the   floor in an area of average temperature, with good air   circulation. Close proximity to the return air grille is the   best choice.   Manual Changeover Thermostat   For Heat Pump equipped units: a single stage, heat/cool   thermostat with a terminal for a reversing valve operation is   required. Terminal “B” should be continuously energized in the   heat mode and terminal “G” should be energized whenever   there is a call for heating or cooling. (Typically, a single stage,   heat/cool thermostat designed for use with electric heat   systems will meet the above requirements).   Mercury bulb type thermostats MUST be level to control   temperature accurately to the desired set-point. Electronic   digital type thermostats SHOULD be level for aesthetics.   Thermostat Location   NOTICE   DO NOT use a two (2) stage Heat Pump Thermostat.   Use of this type of thermostat may result in equipment   and/or property damage   To control the unit with a wall-mounted thermostat:   1) Pull the disconnect switch.   2) Unscrew and remove the control box panel.   3) After selecting which side you want to run your thermostat   wire through, run the wires through the side hole in the box   to reach the connection terminal for the wiring.   4) Make the wire connections, appropriately matching the   wires as shown in the wiring diagram.   5) Once each wire is matched and connected, the unit is now   controlled by the thermostat.   NOTE: An improperly operating, or poorly located room   thermostat can be the source of perceived equipment   problems. A careful check of the thermostat and wiring   must be made then to insure that it is not the source of   problems.   6) Reattach the control box cover.   9 ReMOTe TheRMOsTAT AND LOw VOLTAge CONTROL   CONNeCTIONs (Continued)   Thermostat Connections   For desk control operation, connect one side of the switch to   the D1 terminal and the other to the D2 terminal. Whenever   the switch closes, the unit operation will stop.   C W Y = = = = Common Ground   Call for Heating   Call for Cooling   Maximum Wire Length for Desk Control Switch   R 24V Power from Unit   Wire Size   #24   Maximum Length   400 ft.   GL = Call for Fan (Low Speed)   GH = Call for Fan (High Speed)   #22   600 ft.   B = Reversing Valve Energized in heating mode   Note: The desk   control system and   switches must be   field supplied.   #20   900 ft.   *If only one G terminal is present on thermostat, connect   to GL for low fan or to GH for high fan operation.   #18   1500 ft.   #16   2000 ft.   NOTE: It is the installer’s responsibility to ensure that all   control wiring connections are made in accordance with   the Freidrich installation instructions. Questions concern-   ing proper connections to the unit should be directed to   the factory: 210-357-4400.   Auxiliary Fan Control   The Smart Center also has the ability to control a 24VAC   relay to activate an auxiliary, or transfer, fan. The outputs   are listed as F1 and F2 on the control board.   Desk Control Terminals   To connect the relay, simply wire one side of the relay to   F1 and the other side to F2. Anytime that the fan runs, the   terminals will send a 24VAC signal to the relay. The relay   must be 24 VAC, 50mA or less.   The Friedrich VERT-I-PAK has built-in provisions for   connection to an external switch to control power to the unit.   The switch can be a central desk control system or even a   normally open door switch.   Note: The relay and auxiliary fans must be field supplied.   10   eLeCTRONIC CONTROL BOARD FeATURes   The new Friedrich Vert-I-Pak has state of the art features to improve guest comfort and conserve energy. Through   the use of specifically designed control software, Friedrich has accomplished what other Manufacturer’s have only   attempted – a quiet, dependable, affordable and easy to use Vert-I-Pak.   Below is a list of standard features on every Friedrich VPAK and their benefit to the owner.   The fan start and stop delays prevent abrupt changes in room acoustics due to the compressor energizing   Quiet Start/Stop   or stopping immediately. Upon call for cooling or heating the unit fan will run for five seconds prior to en-   ergizing the compressor. Also, the fan off delay allows for “free cooling” by utilizing the already cool indoor   coil to its maximum capacity by running for 30 seconds after the compressor.   Fan Delay   Remote Thermostat   Operation   VPAK units are thermostat controlled.   The new Friedrich digital VPAK features a self diagnostic program that can alert maintenance to compo-   nent failures or operating problems. The internal diagnostic program saves properties valuable time when   diagnosing running problems.   Internal Diagnostic   Program   The self diagnosis program will also store error codes in memory if certain conditions occur and correct   themselves such as extreme high or low operating conditions or activation of the room freeze protection   feature. Storing error codes can help properties determine if the unit faced obscure conditions or if an error   occurred and corrected itself.   Service Error Code   Storage   When the VPAK senses that the indoor room temperature has fallen to 40°F the unit will cycle on high fan   and the electric strip heat to raise the room temperature to 46°F then cycle off again. This feature works   regardless of the mode selected and can be turned off. The control will also store the Room Freeze cycle   in the service code memory for retrieval at a later date. This feature ensures that unoccupied rooms do not   reach freezing levels where damage can occur to plumbing and fixtures.   Room Freeze   Protection   Multiple compressors starting at once can often cause electrical overloads and premature unit failure.   The random restart delay eliminates multiple units from starting at once following a power outage or initial   power up. The compressor delay will range from 180 to 240 seconds.   Random   Compressor Restart   The new Friedrich VPAK uses a digital thermostat to accurately monitor the outdoor coil conditions to allow   the heat pump to run whenever conditions are correct. Running the VPAK in heat pump mode save energy   and reduces operating costs. The digital thermostat allows maximization of heat pump run time.   Digital Defrost   Thermostat   Heat pump models will automatically run the electric heater during compressor lock-out to quickly provide   heat when initially energized, then return to heat pump mode. This ensures that the room is heated quickly   without the usual delay associated with heat pump units.   Instant Heat   Heat Pump Mode   In the event of a compressor failure in heat pump mode the compressor may be locked out to provide heat   through the resistance heater. This feature ensures that even in the unlikely event of a compressor failure   the room temperature can be maintained until the compressor can be serviced.   Emergency Heat   Override   All electronic VPAK units have low voltage terminals ready to connect a desk control energy management   system. Controlling the unit from a remote location like the front desk can reduce energy usage and   requires no additional accessories at the VPAK.   Desk Control Ready   The frost sensor protects the compressor from damage in the event that airfl ow is reduced or low outdoor   temperatures cause the indoor coil to freeze. When the indoor coil reaches 30°F the compressor is   diabled and the fan continues to operate based on demand. Once the coil temperature returns to 45°F the   compressor returns to operation.   Indoor Coil Frost   Sensor   Ultra-Quiet Air   System   The VPAK series units feature a indoor fan system design that reduces sound levels without   lowering airflow and preventing proper air circulation.   The VPAK benefits quality components and extensive development to ensure a quiet, efficient and   dependable unit.   High Efficiency   High efficiency rotary compressors are used on all Friedrich VPAKs to maximize durability and efficiency.   Rotary Compressor   Auxiliary Fan Ready   The VPAK features a 24V AC terminal for connection to an auxiliary fan that may be used to transfer air to   adjoining rooms. Auxiliary fans can provide conditioning to multiple rooms.   11   Electronic Control Configuration   Electronic Control Error Code   Diagnostics and Test Mode   The adjustable control dip switches are located at the lower   left hand portion of the digital Smart Center. The inputs are   only visible and accessible with the front cover removed from   the Unit.   Error Code Diagnostics   The VPAK electronic control continuously monitors the Vert-I-Pak   unit operation and will store error codes if certain conditions   are witnessed. In some cases the unit may take action and shut   the unit off until conditions are corrected.   Factory Dip Switch Configuration   1 2 3 4 5 6 7 8   O To access the error code menu press the ‘HEAT’ and ‘HIGH   FAN’ buttons simultaneously for three seconds. If error codes   are present they will be displayed. If multiple codes exist you   can toggle between error codes using the temp up ▲ button. To   clear all codes press the temp down ▼ button for three seconds   while in the error code mode. To exit without losing codes   press the ‘Low Fan’ button.   N Dip Switch Setting   Switches 1-4 ON   Switch 5-7 OFF   Switch 8 ON   Button Location for Vert-I-Pak Models   With the remote thermostat escutcheon installed, the button   locations to access the diagnostics mode can be located as   shown below.   Room Freeze Protection – Switch 6   Units are shipped from the factory with the room freeze protec-   tion disabled. Room Freeze Protection can be switched on at   the owner’s preference by moving Dip Switch 6 to ‘ON’. This   feature will monitor the indoor room conditions and in the event   that the room falls below 40°F the unit will cycle on high fan with   the electric heater. This occurs regardless of mode.   Cool   High fan   Heat   Emergency Heat Override – Switch 7   Power   Temp   Units are shipped from the factory with the room emergency   heat override disabled. In the unlikely event of a compressor   failure a heat pump unit may be switched to operate in only the   electric heat mode until repairs can be made, by moving Dip   Switch 7 to ‘ON’.   Temp   Fan only   Low fan   Discharge Air Sensor Override – Switch 8   * Heat and high fan - access error codes   This switch MUST remain in the “ON” position for Vert-I-Pak   models, since they do not use a discharge air sensor. If the   switch is positioned in the “OFF” position on these models it   will result in the erroneous display Error Code 14 indicating that   the Discharge air temperature sensor is open or shorted.   * Temp up ▲ and temp down ▼ - toggle between error codes   * Low fan - exit error code mode without losing stored error   codes.   * Temp down ▼ - clears all error codes   Note: In order for the control to recognize “Dip” switch   setting changes, the unit must be disconnected   from power supply when making any configuration   changes.   NOTE: Hold buttons down for three seconds.   12   electronic Control error Code Diagnostics   Error   Code   Code Translation   Action Taken By Unit   Possible Cause   EF   Error Free   None   Unit Operating Normally   Shut unit down. Flash error code.   voltage rises to adequate level normal unit • Defective breaker   operation is restored.   When • Inadequate power supply   Extreme low voltage condition exists (<198V   for 230V units and <239V for 265V units).   02   • Blown fuse   Return air thermistor sensor open or   short circuit   Indoor coil thermistor sensor open or   short circuit   Leave unit running. Alternately flash error   code and set point.   Leave unit running. Alternately flash   error code and set point.   03   04   • Defective sensor   Leave unit running. Switch to Electric Heat   Mode (Heat Pump only). Alternately flash   error code and set point.   Outdoor coil thermistor sensor open   or short circuit   05   06   • Defective sensor   Shut unit down for 5 minutes, Alternately   flash error code and set point, then try again   2 times, if unit fails the 3rd time then shut   unit down and alternately flash error code   and set point.   • Dirty coil   • Fan motor failure   • Restricted air flow   • Non-condensables in refrigeration system   Outdoor coil Temperature > 175° F for   2 consecutive minutes. (Heat Pump   models only)   Shut down Compressor, and continue fan   • Dirty filters   operation. Alternately flash error code and • Dirty coil   Indoor coil temperature <30° F for 2   consecutive minutes.   set point until the indoor coil thermistor   reaches 45° F. Then, (after lockout time of • Restricted air flow   • Fan motor failure   07   180 to 240 seconds expires), re-energize   the compressor .   • Improper refrigerant charge   • Restriction in refrigerant circuit   Leave unit running. Store error code in   memory.   Unit cycles (Heat or Cool demand) >   9 times per hour   • Unit oversized   • Low load conditions   08   09   Leave unit running. Store Error Code in   memory.   Unit cycles (Heat or Cool demand) <   3 times per hour   • Unit undersized   • High load conditions   Leave unit running. Alternately flash error   code and set point.   10   11   Room Freeze Protection triggered   No Signal to “GL or “GH” terminal   • Room temperature fell below 40°F   • Defective remote thermostat   • Defective thermostat wiring   • Dirty coil   • Fan motor failure   • Restricted air flow   Shut unit down. Flash error code.   Shut unit down. Flash error code.   High Pressure switch open (24K BTU Only)   Jumper wire loose/missing (9-18K BTU)   13   14   • Non-condensables in refrigeration system   Discharge air temperature sensor open or   shorted   Leave unit running. Alternately flash error   code and set point.   • Dip switch # 8 set to "OFF" position   Diagnostics   The Electronic control continuously monitors the VPAK unit operation and will store service codes if certain   conditions are witnessed. In some cases the unit may take action and shut the unit off until conditions are corrected.   To access the error code menu press the ‘Heat’ and ‘High Fan’ buttons simultaneously for three seconds. If   error codes are present they will be displayed. If multiple codes exist you can toggle between messages using the   temp up   button. To clear all codes press the temp down   button for three seconds while in the error code mode. To   exit without changing codes press the ‘Low Fan’ button.   Test Mode   For service and diagnostic use only, the built-in timers and delays on the VPAK may be bypassed by pressing the ‘Cool’ and   ‘Low Fan’ buttons simultaneously for three seconds while in any mode to enter the test mode. CE will be displayed when en-   tering test mode, and oE will be displayed when exiting. The test mode will automatically be exited 30 minutes after entering it   or by pressing the ‘Cool’ and ‘Low Fan’ buttons simultaneously for three seconds.   Note: To access the Test Mode while under remote wall thermostat operation, remove thermostat’s wires at the   terminal block on the electronic control board then connect a jumper wire between GL and GH.   13   VPAk eLeCTRONIC CONTROL FeATURes   Thermostat Compatibility:   Note: The Compressor Time Delay feature is   The VPAK Electronic Control is compatible with   Friedrich RT4 and RT5 Thermostats.   The VPAK Electronic control is also compatible   with most standard Single Stage Heat/Cool   Thermostats.   disabled during “Test Mode” operation.   Fan delay:   The Electronic Control is equipped with a   feature that will start the fan 5 seconds EARLY   (i.e. before compressor or heater) when unit   cycles “ON.” When the unit cycles “OFF” the   fan will DELAY for 30 seconds in Cooling and   15 seconds in Heating.   NOTE: Field supplied Thermostats MUST   energize the fan circuit on a call for Heating   or Cooling, and (when used with a Heat   Pump Unit) MUST energize the “B” terminal   in Heating in order for the unit to function   correctly.   Note: the fan delay is disabled during Test   Mode operation.   Compressor Time Delay:   The Electronic control is equipped with a   random (180 to 240 seconds) Compressor   time delay that is initiated every time the   compressor cycles “Off.” The “delay on break”   timer is initiated by the following actions:   (1) Satisfying the temperature set point   (2) Changing mode to fan only   Emergency Heat:   The Electronic Control is equipped with a   feature that allows servicer/end user to switch   to electric heat operation when the compressor   fails during the heating season, (See DIP   switch position 7) until the compressor can be   replaced.   (3) Turning the unit off   (4) Restoring power after a failure   14   External Static Pressure   External Static Pressure can best be defined as the pressure   difference (drop) between the Positive Pressure (discharge)   and the Negative Pressure (intake) sides of the blower.   External Static Pressure is developed by the blower as a   result of resistance to airflow (Friction) in the air distribution   system EXTERNAL to the VERT-I-PAK cabinet.   1. Set up to measure external static pressure at the   supply and return air.   2. Ensure the coil and filter are clean, and that all the   registers are open.   3. Determine the external static pressure with the   blower operating.   Resistance applied externally to the VERT-I-PAK (i.e. duct   work, filters, etc.) on either the supply or return side of the   system causes an INCREASE in External Static Pres-   sure accompanied by a REDUCTION in airflow.   4. Refer to the Air Flow Data for your VERT-I-PAK   system to find the actual airflow for factory-selected   fan speeds.   External Static Pressure is affected by two (2) factors.   5. If the actual airflow is either too high or too low, the   blower speed will need to be changed to appropriate   setting or the ductwork will need to be reassessed   and corrections made as required.   1. Resistance to Airflow as already explained.   2. Blower Speed. Changing to a higher or lower blower   speed will raise or lower the External Static Pressure   accordingly.   6. Select a speed, which most closely provides the   required airflow for the system.   Theseaffectsmustbeunderstoodandtakenintoconsideration   whencheckingExternal StaticPressure/Airflow to insure that   the system is operating within design conditions.   7. Recheck the external static pressure with the   new speed. External static pressure (and actual   airflow) will have changed to a higher or lower value   depending upon speed selected. Recheck the actual   airflow (at this "new" static pressure) to confirm   speed selection.   Operating a system with insufficient or excessive airflow   can cause a variety of different operating problems.   Among these are reduced capacity, freezing evaporator   coils, premature compressor and/or heating component   failures. etc.   8. Repeat steps 8 and 9 (if necessary) until proper   airflow has been obtained.   System airflow should always be verified upon completion   of a new installation, or before a change-out, compressor   replacement, or in the case of heat strip failure to insure   that the failure was not caused by improper airflow.   EXAMPLE: Airflow requirements are calculated as follows:   (Having a wet coil creates additional resistance to airflow.   This addit ional resistance must be taken into consideration   to obtain accurate airflow information.   Determining the Indoor CFM: Chart A – CFM   Model   VEA09/VHA09 VEA12/VHA12 VEA18/VHA18   ESP (") Low   High   385   340   280   190   Low   420   350 *   290   High   470   420 **   350   Low   430   400   340   290   High   480   450   400   330   .00"   .10"   .20"   .30”   340   300   230   140   250   300   Highlighted values indicate rated performance point.   Rated performance for   VEA12   * Rated Performance for   ** VHA12   Model   VEA24/VHA24   ESP (")   .00"   .10"   .20"   .30"   Low   690   610   560   510   450   High   740   700   640   580   520   Checking External Static Pressure   The airflow through the unit can be determined by   measuring the external static pressure of the system, and   consulting the blower performance data for the specific   VERT-I-PAK.   .40"   Highlighted values indicate rated performance point.   15   Correct CFM (if needed):   Chart B – Correction Multipliers   Ductwork Preparation   If flex duct is used, be sure all the slack is pulled out of the   flex duct. Flex duct ESP can increase considerably when   not fully extended. DO NOT EXCEED a total of .30 ESP, as   this is the MAXIMUM design limit for the VERT-I-PAK   A-Series unit.   IMPORTANT: FLEX DUCT CAN COLLAPSE AND   CAUSE AIRFLOW RESTRICTIONS. DO NOT   USE FLEX DUCT FOR: 90 DEGREE BENDS, OR   UNSUPPORTED RUNS OF 5 FT. OR MORE.   Explanation of charts   Chart A is the nominal dry coil VERT-I-PAK CFMs. Chart   B is the correction factors beyond nominal conditions.   Fresh Air Door   The Fresh Air Door is an “intake” system. The fresh air door   opened via a slide on the front of the chassis located just   above the indoor coil. Move the slide left to open and right   to close the fresh air door. The system is capable of up to 60   CFM of fresh air @ ~.3” H20 internal static pressure.   1 ½ TON SYSTEM ( 18,000 Btu)   Operating on high speed @ 230 volts with dry coil   measured external static pressure .10   Air Flow = 450 CFM   Checking Approximate Airflow   If an inclined manometer or Magnehelic gauge is not   available to check the External Static Pressure, or the   blower performance data is unavailable for your unit,   approximate air flow call be calculated by measuring the   temperature rise, then using tile following criteria.   In the same SYSTEM used in the previous example but   having a WET coil you must use a correction factor of   .95 (i.e. 450 x .95=428 CFM) to allow for the resistance   (internal) of the condensate on the coil.   KILOWATTS x 3413   = CFM   It is important to use the proper procedure to check external   Static Pressure and determine actual airflow. Since in   the case of the VERT-I-PAK, the condensate will cause   a reduction in measured External Static Pressure for the   given airflow.   Temp Rise x 1.08   Electric Heat Strips   The approximate CFM actually being delivered can be   calculated by using the following formula:   It is also important to remember that when dealing with   VERT-l-PAK units that the measured External Static   Pressure increases as the resistance is added externally   to the cabinet. Example: duct work, filters, grilles.   DO NOT simply use the Kilowatt Rating of the heater (i.e.   2.5, 3.4, 5.0) as this will result in a less-than-correct airflow   calculation. Kilowatts may be calculated by multiplying   the measured voltage to the unit (heater) times the   measured current draw of all heaters (ONLY) in operation   to obtain watts. Kilowatts are than obtained by dividing   by 1000.   Indoor Airflow Data   The Vert-I-Pak A series units must be installed with a free   return air configuration. The table below lists the indoor   airflow at corresponding static pressures. All units are rarted   at low speed.   EXAMPLE: Measured voltage to unit (heaters) is 230 volts.   Measured Current Draw of strip heaters is 11.0 amps.   The Vert-I-Pak units are designed for either single speed or   two fan speed operation. For single speed operation refer to   the airflow table below and select the most appropriate CFM   based on the ESP level. Connect the fan output from the   thermostat to the unit on either the GL terminal for low speed   or to the GH terminal for high speed operation.   230 x 11.0 = 2530   2530/1000 = 2.53 Kilowatts   2.53 x 3413 = 8635   ° Supply Air   Return Air   95 F   ° 75 F   ° Temperature Rise   20   For thermostats with two-speed fan outputs connect the low   speed output to the unit GL terminal and the high speed   output to the GH terminal.   20 x 1.08 = 21.6   8635   = 400 CFM   21.6   16   COMPONeNTs TesTINg   BLOWER / FAN MOTOR   Many motor capacitors are internally fused. Shorting the   terminals will blow the fuse, ruining the capacitor. A 20,000   ohm 2 watt resistor can be used to discharge capacitors   safely. Remove wires from capacitor and place resistor   across terminals. When checking a dual capacitor with   a capacitor analyzer or ohmmeter, both sides must be   tested.   Asingle phase permanentsplit capacitor motor is usedto drive   the evaporator blower and condenser fan. A self-resetting   overload is located inside the motor to protect against high   temperature and high amperage conditions.   WARNING   ELECTRIC SHOCK HAZARD   Capacitor Check with Capacitor Analyzer   Disconnect power to the unit before   servicing. Failure to follow this warning   could result in serious injury or death.   The capacitor analyzer will show whether the capacitor   is “open” or “shorted.” It will tell whether the capacitor   is within its micro farads rating and it will show whether   the capacitor is operating at the proper power-factor   percentage. The instrument will automatically discharge   the capacitor when the test switch is released.   BLOWER / FAN MOTOR TEST   1. Visually inspect the motor’s wiring, housing etc., and   determine that the capacitor is serviceable.   2. Make sure the motor has cooled down.   3. Disconnect the fan motor wires from the control board.   4. Test for continuity between the windings also, test to   ground.   Capacitor Connections   The starting winding of a motor can be damaged by a   shorted and grounded running capacitor. This damage   usually can be avoided by proper connection of the running   capacitor terminals.   5. If any winding is open or grounded replace the motor.   From the supply line on a typical 230 volt circuit, a 115 volt   potential exists from the “R” terminal to ground through a   possibleshortinthecapacitor. However, fromthe“S”orstart   terminal, a much higher potential, possibly as high as 400   volts, exists because of the counter EMF generated in the   start winding. Therefore, the possibility of capacitor failure   is much greater when the identified terminal is connected   to the “S” or start terminal. The identified terminal should   always be connected to the supply line, or “R” terminal,   never to the “S” terminal.   When connected properly, a shorted or grounded running   capacitor will result in a direct short to ground from the “R”   terminal and will blow the line fuse. The motor protector   will protect the main winding from excessive temperature.   CAPACITORs   WARNING   ELECTRIC SHOCK HAZARD   Turn off electric power before servicing.   Discharge capacitor with a 20,000 Ohm 2 Watt   resistor before handling.   Failure to do so may result in personal injury,   or death.   17   COMPONeNTs TesTINg (Continued)   HEATER ELEMENTS AND LIMIT SWITCHES’   SPECIFICATIONS   All heat pumps and electric heat models are equipped   with a heating element and a limit switch (bimetal ther-   mostat). The limit is in series with the element and will   interrupt the power at a designed temperature.   DRAIN PAN VALVE   During the cooling mode of operation, condensate which   collects in the drain pan is picked up by the condenser fan   blade and sprayed onto the condenser coil. This assists   in cooling the refrigerant plus evaporating the water.   During the heating mode of operation, it is necessary that   water be removed to prevent it from freezing during cold   outside temperatures. This could cause the condenser   fan blade to freeze in the accumulated water and prevent   it from turning.   Should the blower motor fail, filter become clogged or air-   flow be restricted etc., the high limit switch will open and   interrupt the power to the heater before reaching an un-   safe temperature condition.   To provide a means of draining this water, a bellows type   drain valve is installed over a drain opening in the base   pan.   TESTING THE HEATING ELEMENTS AND   LIMIT SWITCHES   WARNING   This valve is temperature sensitive and will open when   the outside temperature reaches 40°F. The valve will   close gradually as the temperature rises above 40°F to   fully close at 60°F.   ELECTRIC SHOCK HAZARD   Disconnect power to the unit before   servicing. Failure to follow this warning   could result in serious injury or death.   Bellows Assembly   Drain Pan Valve   Testing of the heating elements can be made with an   ohmmeter or continuity tester across the terminals after   the power wires have been removed. Test the limit switch   for continuity across its input and output terminals.Test   below the limit switch’s reset temperature.   18   ReFRIgeRATION seQUeNCe OF OPeRATION   A good understanding of the basic operation of the   refrigeration system is essential for the service technician.   Without this understanding, accurate troubleshooting of   refrigeration system problems will be more difficult and time   consuming, if not (in some cases) entirely impossible. The   refrigeration system uses four basic principles (laws) in its   operation they are as follows:   The refrigerant leaves the condenser Coil through the liquid   line as a warm high pressure liquid. It next will pass through   the refrigerant drier (if so equipped). It is the function of the   driertotrapanymoisturepresentinthesystem,contaminants,   and large particulate matter.   The liquid refrigerant next enters the metering device. The   metering device is a capillary tube. The purpose of the   metering device is to “meter” (i.e. control or measure) the   quantity of refrigerant entering the evaporator coil.   1. “Heat always flows from a warmer body to a cooler   body.”   2. “Heat must be added to or removed from a substance   before a change in state can occur”   In the case of the capillary tube this is accomplished (by   design) through size (and length) of device, and the pressure   difference present across the device.   3. “Flow is always from a higher pressure area to a lower   pressure area.”   Since the evaporator coil is under a lower pressure (due to   the suction created by the compressor) than the liquid line,   the liquid refrigerant leaves the metering device entering the   evaporator coil. As it enters the evaporator coil, the larger   area and lower pressure allows the refrigerant to expand   and lower its temperature (heat intensity). This expansion is   often referred to as “boiling”. Since the unit’s blower is moving   indoor air across the finned surface of the evaporator coil,   the expanding refrigerant absorbs some of that heat. This   results in a lowering of the indoor air temperature, hence the   “cooling” effect.   4. “The temperature at which a liquid or gas changes state   is dependent upon the pressure.”   The refrigeration cycle begins at the compressor. Starting   the compressor creates a low pressure in the suction line   which draws refrigerant gas (vapor) into the compressor.   The compressor then “compresses” this refrigerant, raising   its pressure and its (heat intensity) temperature.   The refrigerant leaves the compressor through the discharge   Line as a hot High pressure gas (vapor). The refrigerant   enters the condenser coil where it gives up some of its   heat. The condenser fan moving air across the coil’s finned   surface facilitates the transfer of heat from the refrigerant to   the relatively cooler outdoor air.   The expansion and absorbing of heat cause the liquid   refrigerant to evaporate (i.e. change to a gas). Once the   refrigerant has been evaporated (changed to a gas), it is   heated even further by the air that continues to flow across   the evaporator coil.   When a sufficient quantity of heat has been removed from   the refrigerant gas (vapor), the refrigerant will “condense”   (i.e. change to a liquid). Once the refrigerant has been   condensed (changed) to a liquid it is cooled even further by   the air that continues to flow across the condenser coil.   The particular system design determines at exactly what   point (in the evaporator) the change of state (i.e. liquid to a   gas) takes place. In all cases, however, the refrigerant must   be totally evaporated (changed) to a gas before leaving the   evaporator coil.   The VPAK design determines at exactly what point (in   the condenser) the change of state (i.e. gas to a liquid)   takes place. In all cases, however, the refrigerant must be   totally condensed (changed) to a Liquid before leaving the   condenser coil.   The low pressure (suction) created by the compressor   causes the refrigerant to leave the evaporator through the   suction line as a cool low pressure vapor. The refrigerant then   returns to the compressor, where the cycle is repeated.   Refrigeration Assembly   1. Compressor   2. Evaporator Coil Assembly   3. Condenser Coil Assembly   4. Capillary Tube   5. Compressor Overload   19   seRVICe   Servicing / Chassis Quick Changeouts   WARNING   ELECTRIC SHOCK HAZARD   Turn off electric power before service or   installation.   . Extreme care must be used, if it becomes   necessary to work on equipment with power   applied.   To Remove the Chassis from the Closet:   A. Disconnect the power coming into the unit from the main   breaker panel or the closet mounted disconnect.   B. Switch the wall Thermostat off.   Failure to do so could result in serious injury or   death.   C. Pull the Power Disconnect located in the front of the chassis.   D. Disconnect the electrical connection.   E. Disconnect the duct work.   F. Disconnect condensate drain on 9-18,000 BTU models.   G. Slide the chassis out of the wall plenum.   H. Lift the chassis out of the utility closet.   CAUTION   CUT/SEVER HAZARD   Be careful with the sharp edges and corners.   Wear protective clothing and gloves, etc.   Failure to do so could result in minor to   moderate injury.   Warranty   20   seALeD ReFRIgeRATION sYsTeM RePAIRs   IMPORTANT   ANY SEALED SYSTEM REPAIRS TO COOL-ONLY MODELS REQUIRE THE INSTALLATION OF A LIQUID LINE DRIER.   ALSO, ANY SEALED SYSTEM REPAIRS TO HEAT PUMP MODELS REQUIRE THE INSTALLATION OF A SUCTION LINE DRIER.   EQUIPMENT REQUIRED:   9. High Pressure Gauge - (0 - 750 lbs.)   1. Voltmeter   10. Low Pressure Gauge - (30 - 200 lbs.)   2. Ammeter   11. Vacuum Gauge - (0 - 1000 microns)   3. Ohmmeter   12. Facilities for flowing nitrogen through refrigeration tubing   4. E.P.A. Approved Refrigerant Recovery System   during all brazing processes.   5. Vacuum Pump (capable of 200 microns or less   vacuum.)   EQUIPMENT MUST BE CAPABLE OF:   6. Acetylene Welder   1. Recovering refrigerant to EPA required levels.   7. Electronic Halogen Leak Detector capable of detect-   ing HFC (Hydrofluorocarbon) refrigerants.   2. Evacuation from both the high side and low side of the   system simultaneously.   8. Accurate refrigerant charge measuring device such   as:   3. Introducing refrigerant charge into high side of the   system.   a. Balance Scales - 1/2 oz. accuracy   b. Charging Board - 1/2 oz. accuracy   4. Accurately weighing the refrigerant charge actually   introduced into the system.   Too much refrigerant (overcharge) in the system is just as bad   (if not worse) than not enough refrigerant (undercharge). They   both can be the source of certain compressor failures if they   remain uncorrected for any period of time. Quite often, other   problems (such as low air flow across evaporator, etc.) are   misdiagnosed as refrigerant charge problems. The refrigerant   circuit diagnosis chart will assist you in properly diagnosing   these systems.   WARNING   RISK OF ELECTRIC SHOCK   Unplug and/or disconnect all electrical power   to the unit before performing inspections,   maintenances or service.   Failure to do so could result in electric shock,   serious injury or death.   An overcharged unit will at times return liquid refrigerant   (slugging) back to the suction side of the compressor eventually   causing a mechanical failure within the compressor. This   mechanical failure can manifest itself as valve failure, bearing   failure, and/or other mechanical failure. The specific type of   failure will be influenced by the amount of liquid being returned,   and the length of time the slugging continues.   WARNING   HIGH PRESSURE HAZARD   SealedRefrigerationSystemcontainsrefrigerant   and oil under high pressure.   Proper safety procedures must be followed,   and proper protective clothing must be worn   when working with refrigerants.   Not enough refrigerant (undercharge) on the other hand, will   cause the temperature of the suction gas to increase to the point   where it does not provide sufficient cooling for the compressor   motor. When this occurs, the motor winding temperature will   increase causing the motor to overheat and possibly cycle open   the compressor overload protector. Continued overheating of   the motor windings and/or cycling of the overload will eventually   lead to compressor motor or overload failure.   Failure to follow these procedures could   result in serious injury or death.   Refrigerant Charging   Proper refrigerant charge is essential to proper unit opera-   tion. Operating a unit with an improper refrigerant charge will   result in reduced performance (capacity) and/or efficiency.   Accordingly, the use of proper charging methods during ser-   vicing will insure that the unit is functioning as designed and   that its compressor will not be damaged.   21   Method Of Charging / Repairs   CAUTION   The acceptable method for charging the RAC system is the   Weighed in Charge Method. The weighed in charge method is   applicable to all units. It is the preferred method to use, as it is   the most accurate.   FREEZE HAZARD   Proper safety procedures must be followed,   and proper protective clothing must be worn   when working with liquid refrigerant.   The weighed in method should always be used whenever   a charge is removed from a unit such as for a leak repair,   compressor replacement, or when there is no refrigerant   charge left in the unit. To charge by this method, requires the   following steps:   Failure to follow these procedures could   result in minor to moderate injury.   4. Make necessary repairs to system.   1. Install a piercing valve to remove refrigerant from the   sealedsystem. (Piercing valve must be removed from the   system before recharging.)   5. Evacuate system to 200 microns or less.   6. Weigh in refrigerant with the property quantity of R-410A   2. Recover Refrigerant in accordance with EPA regulations.   refrigerant.   7. Start unit, and verify performance.   WARNING   BURN HAZARD   WARNING   Proper safety procedures must be followed,   and proper protective clothing must be worn   when working with a torch.   BURN HAZARD   Proper safety procedures must be followed,   and proper protective clothing must be worn   when working with a torch.   Failure to follow these procedures could   result in moderate or serious injury.   Failure to follow these procedures could   result in moderate or serious injury.   3. Install a process tube to sealed system.   8. Crimp the process tube and solder the end shut.   Undercharged Refrigerant systems   An undercharged system will result in poor performance   (low pressures, etc.) in both the heating and cooling   cycle.   WARNING   ELECTRIC SHOCK HAZARD   Turn off electric power before service or   installation.   Whenever you service a unit with an undercharge of   refrigerant, always suspect a leak. The leak must be   repaired before charging the unit.   Extreme care must be used, if it becomes   necessary to work on equipment with power   applied.   To check for an undercharged system, turn the unit on,   allow the compressor to run long enough to establish   working pressures in the system (15 to 20 minutes).   Failure to do so could result in serious injury or   death.   During the cooling cycle you can listen carefully at the exit   of the metering device into the evaporator; an intermittent   hissing and gurgling sound indicates a low refrigerant   charge. Intermittent frosting and thawing of the evaporator   is another indication of a low charge, however, frosting   and thawing can also be caused by insufficient air over   the evaporator.   WARNING   HIGH PRESSURE HAZARD   SealedRefrigerationSystemcontainsrefrigerant   and oil under high pressure.   Proper safety procedures must be followed,   and proper protective clothing must be worn   when working with refrigerants.   Checks for an undercharged system can be made at   the compressor. If the compressor seems quieter than   normal, it is an indication of a low refrigerant charge.   Failure to follow these procedures could   result in serious injury or death.   A check of the amperage drawn by the compressor   motor should show a lower reading. (Check the Unit   Specification.)   22   After the unit has run 10 to 15 minutes, check the gauge Improper air flow over the evaporator coil may indicate   pressures.Gaugesconnectedtosystemwithanundercharge some of the same symptoms as an over charged system.   will have low head pressures and substantially low suction An overcharge can cause the compressor to fail, since it   pressures.   would be “slugged” with liquid refrigerant.   The charge for any system is critical. When the compressor   is noisy, suspect an overcharge, when you are sure that the   air quantity over the evaporator coil is correct. Icing of the   evaporator will not be encountered because the refrigerant   will boil later if at all. Gauges connected to system will usually   have higher head pressure (depending upon amount of over   charge). Suction pressure should be slightly higher.   Overcharged Refrigerant systems   Compressor amps will be near normal or higher.   Noncondensables can also cause these symptoms. To   confirm, remove some of the charge, if conditions improve,   system may be overcharged. If conditions don’t improve,   Noncondensables are indicated.   Wheneveranoverchargedsystemisindicated,alwaysmake   sure that the problem is not caused by air flow problems.   Restricted Refrigerant system   Troubleshooting a restricted refrigerant system can be   difficult. The following procedures are the more common   problems and solutions to these problems. There are two   types of refrigerant restrictions: Partial restrictions and   complete restrictions.   With a complete restriction the current drawn may be   considerably less than normal, as the compressor is   running in a deep vacuum (no load.) Much of the area of   the condenser will be relatively cool since most or all of the   liquid refrigerant will be stored there.   A partial restriction allows some of the refrigerant to   circulate through the system.   The following conditions are based primarily on a system   in the cooling mode.   With a complete restriction there is no circulation of   refrigerant in the system.   Restricted refrigerant systems display the same symptoms   as a “low-charge condition.”   When the unit is shut off, the gauges may equalize very   slowly.   Gauges connected to a completely restricted system will   run in a deep vacuum. When the unit is shut off, the gauges   will not equalize at all.   A quick check for either condition begins at the evaporator.   With a partial restriction, there may be gurgling sounds   at the metering device entrance to the evaporator. The   evaporator in a partial restriction could be partially frosted   or have an ice ball close to the entrance of the metering   device. Frost may continue on the suction line back to the   compressor.   Often a partial restriction of any type can be found by feel,   as there is a temperature difference from one side of the   restriction to the other.   With a complete restriction, there will be no sound at the   metering device entrance. An amperage check of the   compressor with a partial restriction may show normal   current when compared to the unit specification.   23   heRMeTIC COMPONeNTs CheCk   WARNING   BURN HAZARD   WARNING   Proper safety procedures must be followed,   and proper protective clothing must be worn   when working with a torch.   CUT/SEVER HAZARD   Be careful with the sharp edges and corners.   Wear protective clothing and gloves, etc.   Failure to follow these procedures could   result in moderate or serious injury.   Failure to do so could result in serious injury.   MeTeRINg DeVICe   Capillary Tube systems   All units are equipped with capillary tube metering   devices.   3. Switch the unit to the heating mode and observe the   gauge readings after a few minutes running time. If   the system pressure is lower than normal, the heating   capillary is restricted.   Checking for restricted capillary tubes.   1. Connect pressure gauges to unit.   4. If the operating pressures are lower than normal in both   the heating and cooling mode, the cooling capillary is   restricted.   2. Start the unit in the cooling mode. If after a few minutes   of operation the pressures are normal, the check valve   and the cooling capillary are not restricted.   CheCk VALVe   the port (liquid line) to the outdoor coil. The flow path of   the refrigerant is then through the filter drier and heating   capillary to the outdoor coil.   A unique two-way check valve is used on the reverse cycle   heat pumps. It is pressure operated and used to direct the   flow of refrigerant through a single filter drier and to the   proper capillary tube during either the heating or cooling   cycle.   Failure of the slide in the check valve to seat properly in   either mode of operation will cause flooding of the cooling   coil. This is due to the refrigerant bypassing the heating or   cooling capillary tube and entering the liquid line.   One-way Check Valve   (Heat Pump Models)   COOLING MODE   In the cooling mode of operation, liquid refrigerant from   condenser (liquid line) enters the cooling check valve   forcing the heating check valve shut. The liquid refrigerant   is directed into the liquid dryer after which the refrigerant   is metered through cooling capillary tubes to evaporator.   (Note: liquid refrigerant will also be directed through the   heating capillary tubes in a continuous loop during the   cooling mode).   NOTE: The slide (check) inside the valve is made of teflon.   Should it become necessary to replace the check valve,   place a wet cloth around the valve to prevent overheating   during the brazing operation.   HEATING MODE   In the heating mode of operation, liquid refrigerant from   the indoor coil enters the heating check valve forcing the   cooling check valve shut. The liquid refrigerant is directed   into the liquid dryer after which the refrigerant is metered   through the heating capillary tubes to outdoor coils. (Note:   liquid refrigerant will also be directed through the cooling   capillary tubes in a continuous loop during the heating   mode).   CHECK VALVE OPERATION   In the cooling mode of operation, high pressure liquid enters   the check valve forcing the slide to close the opposite port   (liquid line) to the indoor coil. Refer to refrigerant flow chart.   This directs the refrigerant through the filter drier and cooling   capillary tube to the indoor coil.   In the heating mode of operation, high pressure refrigerant   enters the check valve from the opposite direction, closing   24   ReVeRsINg VALVe DesCRIPTION/OPeRATION   of the system. The pilot section of the valve opens and   WARNING   ELECTRIC SHOCK HAZARD   closes ports for the small capillary tubes to the main valve   to cause it to shift.   Disconnect power to the unit before servicing.   Failure to follow this warning could result in   serious injury or death.   NOTE: System operating pressures must be near   normal before valve can shift.   The Reversing Valve controls the direction of refrigerant flow   to the indoor and outdoor coils. It consists of a pressure-   operated, main valve and a pilot valve actuated by a solenoid   plunger. The solenoid is energized during the heating cycle   only. The reversing valves used in the PTAC system is a   2-position, 4-way valve.   The single tube on one side of the main valve body is the   high-pressure inlet to the valve from the compressor. The   center tube on the opposite side is connected to the low   pressure (suction) side of the system. The other two are   connected to the indoor and outdoor coils. Small capillary   tubes connect each end of the main valve cylinder to the “A”   and “B” ports of the pilot valve. A third capillary is a common   return line from these ports to the suction tube on the main   valve body. Four-way reversing valves also have a capillary   tube from the compressor discharge tube to the pilot valve.   The piston assembly in the main valve can only be shifted   by the pressure differential between the high and low sides   TesTINg The COIL   NOTE: Do not start unit with solenoid coil removed from   valve, or do not remove coil after unit is in operation. This   will cause the coil to burn out.   WARNING   ELECTRIC SHOCK HAZARD   Unplug and/or disconnect all electrical power   to the unit before performing inspections,   maintenances or service.   CheCkINg The ReVeRsINg VALVe   NOTE: You must have normal operating pressures before   Failure to do so could result in electric shock,   serious injury or death.   the reversing valve can shift.   WARNING   The solenoid coil is an electromagnetic type coil mounted   on the reversing valve and is energized during the   operation of the compressor in the heating cycle.   HIGH PRESSURE HAZARD   Sealed Refrigeration System contains refrigerant   and oil under high pressure.   1. Turn off high voltage electrical power to unit.   Proper safety procedures must be followed,   and proper protective clothing must be worn   when working with refrigerants.   2. Unplug line voltage lead from reversing valve coil.   3. Check for electrical continuity through the coil. If you   Failure to follow these procedures could   result in serious injury or death.   do not have continuity replace the coil.   4. Check from each lead of coil to the copper liquid line   as it leaves the unit or the ground lug. There should   be no continuity between either of the coil leads   and ground; if there is, coil is grounded and must be   replaced.   Check the operation of the valve by starting the system   and switching the operation from “Cooling” to “Heating”   and then back to “Cooling”. Do not hammer on valve.   Occasionally, the reversing valve may stick in the heating   or cooling position or in the mid-position.   5. If coil tests okay, reconnect the electrical leads.   6. Make sure coil has been assembled correctly.   25   When sluggish or stuck in the mid-position, part of the   discharge gas from the compressor is directed back to the   suction side, resulting in excessively high suction pressure.   Touch Test in heating/Cooling Cycle   WARNING   BURN HAZARD   Certain unit components operate at   temperatures hot enough to cause burns.   Should the valve fail to shift from coooling to heating,   block the air flow through the outdoor coil and allow the   discharge pressure to build in the system. Then switch the   system from heating to cooling.   Proper safety procedures must be followed,   and proper protective clothing must be   worn.   If the valve is stuck in the heating position, block the air   flow through the indoor coil and allow discharge pressure   to build in the system. Then switch the system from heating   to cooling.   Failure to follow these procedures could   result in minor to moderate injury.   Shouldthevalvefailtoshiftineitherpositionafterincreasing   the discharge pressure, replace the valve.   The only definite indications that the slide is in the mid-   position is if all three tubes on the suction side of the valve   are hot after a few minutes of running time.   Dented or damaged valve body or capillary tubes can   prevent the main slide in the valve body from shifting.   NOTE: A condition other than those illustrated above, and   on Page 31, indicate that the reversing valve is not shifting   properly. Both tubes shown as hot or cool must be the same   corresponding temperature.   If you determing this is the problem, replace the reversing   valve.   Procedure For Changing Reversing Valve   After all of the previous inspections and checks have been   made and determined correct, then perform the “Touch   Test” on the reversing valve.   WARNING   HIGH PRESSURE HAZARD   SealedRefrigerationSystemcontainsrefrigerant   and oil under high pressure.   Proper safety procedures must be followed,   and proper protective clothing must be worn   when working with refrigerants.   Failure to follow these procedures could   result in serious injury or death.   NOTICE   FIRE HAZARD   The use of a torch requires extreme care and proper   judgment. Follow all safety recommended precautions   and protect surrounding areas with fire proof materials.   Have a fire extinguisher readily available. Failure to follow   this notice could result in moderate to serious property   damage.   Reversing Valve in Heating Mode   1. Install Process Tubes. Recover refrigerant from sealed   system. PROPER HANDLING OF RECOVERED   REFRIGERANT ACCORDING TO EPA REGULATIONS   IS REQUIRED.   2. Remove solenoid coil from reversing valve. If coil is to   be reused, protect from heat while changing valve.   3. Unbraze all lines from reversing valve.   4. Clean all excess braze from all tubing so that they will   slip into fittings on new valve.   5. Remove solenoid coil from new valve.   Reversing Valve in Cooling Mode   26   6. Protectnewvalvebodyfromheatwhilebrazingwith plastic   heat sink (Thermo Trap) or wrap valve body with wet   rag.   Determine L.R.V.   Start the compressor with the volt meter attached; then stop   the unit. Attempt to restart the compressor within a couple   of seconds and immediately read the voltage on the meter.   The compressor under these conditions will not start and will   usually kick out on overload within a few seconds since the   pressures in the system will not have had time to equalize.   Voltage should be at or above minimum voltage of 197 VAC,   as specified on the rating plate. If less than minimum, check   for cause of inadequate power supply; i.e., incorrect wire   size, loose electrical connections, etc.   7. Fit all lines into new valve and braze lines into new   valve.   WARNING   EXPLOSION HAZARD   The use of nitrogen requires a pressure   regulator. Follow all safety procedures and   wear protective safety clothing etc.   Amperage (L.R.A.) Test   Failure to follow proper safety procedures   could result in serious injury or death.   The running amperage of the compressor is the most impor-   tant of these readings. A running amperage higher than that   indicated in the performance data indicates that a problem   exists mechanically or electrically.   8. Pressurize sealed system with a combination of R-22   and nitrogen and check for leaks, using a suitable leak   detector. Recover refrigerant per EPA guidelines.   Single Phase Running and L.R.A. Test   NOTE: Consult the specification and performance section   for running amperage. The L.R.A. can also be found on the   rating plate.   9. Once the sealed system is leak free, install solenoid coil   on new valve and charge the sealed system by weighing   in the proper amount and type of refrigerant as shown   on rating plate. Crimp the process tubes and solder the   ends shut. Do not leave Schrader or piercing valves in   the sealed system.   Select the proper amperage scale and clamp the meter   probe around the wire to the “C” terminal of the compressor.   Turn on the unit and read the running amperage on the me-   ter. If the compressor does not start, the reading will indicate   the locked rotor amperage (L.R.A.).   NOTE: When brazing a reversing valve into the system, it is   of extreme importance that the temperature of the valve does   not exceed 250°F at any time.   Overloads   The compressor is equipped with an external or internal   overload which senses both motor amperage and winding   temperature. High motor temperature or amperage heats   the overload causing it to open, breaking the common circuit   within the compressor.   Wrap the reversing valve with a large rag saturated with   water. “Re-wet” the rag and thoroughly cool the valve after   each brazing operation of the four joints involved.   The wet rag around the reversing valve will eliminate   conduction of heat to the valve body when brazing the line   connection.   Heat generated within the compressor shell, usually due to   recycling of the motor, is slow to dissipate. It may take any-   where from a few minutes to several hours for the overload   to reset.   COMPRessOR CheCks   Checking the Overload   WARNING   ELECTRIC SHOCK HAZARD   Turn off electric power before service or   installation. Extreme care must be used, if it   becomes necessary to work on equipment with   power applied.   WARNING   ELECTRIC SHOCK HAZARD   Turn off electric power before service or   installation. Extreme care must be used, if it   becomes necessary to work on equipment   with power applied.   Failure to do so could result in serious injury or   death.   Locked Rotor Voltage (L.R.V.) Test   Failure to do so could result in serious injury or   death.   Locked rotor voltage (L.R.V.) is the actual voltage available   at the compressor under a stalled condition.   single Phase Connections   Disconnect power from unit. Using a voltmeter, attach one   lead of the meter to the run “R” terminal on the compressor   and the other lead to the common “C” terminal of the com-   pressor. Restore power to unit.   27   Add values “C” to “S” and “C” to “R” together and check   resistancefromstarttorunterminals(“S”to“R”). Resistance   “S” to “R” should equal the total of “C” to “S” and “C” to “R.”   WARNING   BURN HAZARD   Certain unit components operate at   temperatures hot enough to cause burns.   In a single phase PSC compressor motor, the highest   value will be from the start to the run connections (“S” to   “R”). The next highest resistance is from the start to the   common connections (“S” to “C”). The lowest resistance   is from the run to common. (“C” to “R”) Before replacing a   compressor, check to be sure it is defective.   Proper safety procedures must be followed,   and proper protective clothing must be   worn.   Failure to follow this warning could result   in moderate to serious injury.   external Overload VPAk 9, 12, 18 k Btus   With power off, remove the leads from compressor termi-   nals. If the compressor is hot, allow the overload to cool   before starting check. Using an ohmmeter, test continu-   ity across the terminals of the external overload. If you   do not have continuity; this indicates that the overload is   open and must be replaced.   Internal Overload VPAk 24 k Btus   The overload is embedded in the motor windings to   sense the winding temperature and/or current draw. The   overload is connected in series with the common motor   terminal.   GROUND TEST   Use an ohmmeter set on its highest scale. Touch one   lead to the compressor body (clean point of contact as a   good connection is a must) and the other probe in turn   to each compressor terminal. If a reading is obtained the   compressor is grounded and must be replaced.   1. With no power to unit, remove the leads from the com-   pressor terminals. Allow motor to cool.   2. Using an ohmmeter, test continuity between terminals   C-S and C-R. If no continuity, the compressor overload is   open and the compressor must be replaced.   Check the complete electrical system to the compressor   and compressor internal electrical system, check to be   certain that compressor is not out on internal overload.   Completeevaluationofthesystemmustbemadewhenever   you suspect the compressor is defective. If the compressor   has been operating for sometime, a careful examination   must be made to determine why the compressor failed.   Internal Overload   Many compressor failures are caused by the following   conditions:   1. Improper air flow over the evaporator.   single Phase Resistance Test   2. Overcharged refrigerant system causing liquid to be   returned to the compressor.   WARNING   ELECTRIC SHOCK HAZARD   3. Restricted refrigerant system.   Turn off electric power before service or   installation. Extreme care must be used, if it   becomes necessary to work on equipment   with power applied.   4. Lack of lubrication.   5. Liquid refrigerant returning to compressor causing oil   Failure to do so could result in serious injury or   death.   to be washed out of bearings.   6.   Noncondensables such as air and moisture in   the system. Moisture is extremely destructive to a   refrigerant system.   Remove the leads from the compressor terminals and set   the ohmmeter on the lowest scale (R x 1).   Touch the leads of the ohmmeter from terminals common   to start (“C” to “S”). Next, touch the leads of the ohmmeter   from terminals common to run (“C” to “R”).   28   COMPRessOR RePLACeMeNT   Recommendedprocedure forcompressor   replacement   3. After all refrigerant has been recovered, disconnect   suction and discharge lines from the compressor and   remove compressor. Be certain to have both suction   and discharge process tubes open to atmosphere.   WARNING   4. Carefully pour a small amount of oil from the suction   RISK OF ELECTRIC SHOCK   Unplug and/or disconnect all electrical power   to the unit before performing inspections,   maintenances or service.   stub of the defective compressor into a clean   container.   5. Using an acid test kit (one shot or conventional kit), test   the oil for acid content according to the instructions   with the kit.   Failure to do so could result in electric shock,   serious injury or death.   6. If any evidence of a burnout is found, no matter how   slight, the system will need to be cleaned up following   proper procedures.   1. Be certain to perform all necessary electrical and   refrigeration tests to be sure the compressor is   actually defective before replacing.   7. Install the replacement compressor.   WARNING   WARNING   HIGH PRESSURE HAZARD   SealedRefrigerationSystemcontainsrefrigerant   and oil under high pressure.   EXPLOSION HAZARD   The use of nitrogen requires a pressure   regulator. Follow all safety procedures and   wear protective safety clothing etc.   Proper safety procedures must be followed,   and proper protective clothing must be worn   when working with refrigerants.   Failure to follow proper safety procedures   result in serious injury or death.   Failure to follow these procedures could   result in serious injury or death.   8. Pressurize with a combination of R-410A and nitrogen   and leak test all connections with leak detector capable of   detecting HFC (Hydrofluorocarbon) refrigerant. Recover   refrigerant/nitrogen mixture and repair any leaks found.   2. Recover all refrigerant from the system though   the process tubes. PROPER HANDLING OF   RECOVERED REFRIGERANT ACCORDING TO   EPA REGULATIONS IS REQUIRED. Do not use   gauge manifold for this purpose if there has been   a burnout. You will contaminate your manifold and   hoses. Use a Schrader valve adapter and copper   tubing for burnout failures.   Repeat Step 8 to insure no more leaks are present.   9. Evacuate the system with a good vacuum pump capable   of a final vacuum of 200 microns or less. The system   should be evacuated through both liquid line and suction   line gauge ports. While the unit is being evacuated, seal   all openings on the defective compressor.   WARNING   HIGH TEMPERATURES   CAUTION   FREEZE HAZARD   Extreme care, proper judgment and all safety   procedures must be followed when testing,   troubleshooting, handling or working around   unit while in operation with high temperature   components. Wear protective safety aids   such as: gloves, clothing etc.   Proper safety procedures must be followed,   and proper protective clothing must be worn   when working with liquid refrigerant.   Failure to follow these procedures could   result in minor to moderate injury.   Failure to do so could result in serious burn   injury.   10. Recharge the system with the correct amount of   refrigerant. The proper refrigerant charge will be   found on the unit rating plate. The use of an accurate   measuring device, such as a charging cylinder,   NOTICE   FIRE HAZARD   electronic scales or similar device is necessary.   The use of a torch requires extreme care and proper   judgment. Follow all safety recommended precautions   and protect surrounding areas with fire proof materials.   Have a fire extinguisher readily available. Failure to follow   this notice could result in moderate to serious property   damage.   NOTICE   NEVER, under any circumstances, charge a rotary   compressor through the LOW side. Doing so would   cause permanent damage to the new compressor.   29   SPECIAL PROCEDURE IN THE CASE OF MOTOR   COMPRESSOR BURNOUT   To ensure proper unit operation and life expectancy, the   following maintenance procedures should be performed   on a regular basis   WARNING   ELECTRIC SHOCK HAZARD   Turn off electric power before service or   installation.   1. Air Filter   To ensure proper unit operation, the air filters should   be cleaned at least monthly, and more frequently if   conditions warrant. The unit must be turned off before   the filters are cleaned.   Failure to do so may result in personal injury,   or death.   To remove the air filters, grasp the top of the filter and lift   out of the front cabinet. Reverse the procedure to reinstall   the filters.   WARNING   HIGH PRESSURE HAZARD   Clean the filters with a mild detergent in warm water, and   allow them to dry thoroughly before reinstalling.   SealedRefrigerationSystemcontainsrefrigerant   and oil under high pressure.   2. Coils & Chassis   Proper safety procedures must be followed,   and proper protective clothing must be worn   when working with refrigerants.   NOTE: Do not use a caustic coil cleaning agent on coils   or base pan. Use a biodegradable cleaning agent and   degreaser. The use of harsh cleaning materials may   lead to deterioration of the aluminum fins or the coil end   plates.   Failure to follow these procedures could   result in serious injury or death.   The indoor coil and outdoor coils and base pan should   be inspected periodically (annually or semi-annually)   and cleaned of all debris (lint, dirt, leaves, paper, etc.)   as necessary. Under extreme conditions, more frequent   cleaning may be required. Clean the coils and base   pan with a soft brush and compressed air or vacuum.   A pressure washer may also be used, however, you   must be careful not to bend the aluminum fin pack. Use   a sweeping up and down motion in the direction of the   vertical aluminum fin pack when pressure cleaning coils.   WARNING   EXPLOSION HAZARD   The use of nitrogen requires a pressure   regulator. Follow all safety procedures and   wear protective safety clothing etc.   Failure to follow proper safety procedures   result in serious injury or death.   1.   Recover all refrigerant and oil from the system.   Note: It is extremely important to insure that none of the   electrical and/or electronic parts of the unit get wet. Be   sure to cover all electrical components to protect them   from water or spray.   Remove compressor, capillary tube and filter drier   from the system.   2.   3.   Flush evaporator condenser and all connecting   tubing with dry nitrogen or equivalent. Use approved   flushing agent to remove all contamination from   system. Inspect suction and discharge line for   carbon deposits. Remove and clean if necessary.   Ensure all acid is neutralized.   3. Decorative Front   The decorative front and discharge air grille may be   cleaned with a mild soap or detergent. Do NOT use   solvents or hydrocarbon based cleaners such as   acetone, naphtha, gasoline, benzene, etc., to clean the   decorative front or air discharge grilles.   4. Reassemble the system, including new drier strainer   and capillary tube.   Use a damp (not wet) cloth when cleaning the control   area to prevent water from entering the unit, and possibly   damaging the electronic control   5. Proceed with step 8-10 on previous page.   4. Fan Motor & Compressor   The fan motor & compressor and are permanently   lubricated, and require no additional lubrication.   ROUTINe MAINTeNANCe   WARNING   5. Wall Sleeve   Inspect the inside of the wall sleeve and drain system   periodically (annually or semi-annually) and clean as   required. Under extreme conditions, more frequent   cleaning may be necessary. Clean both of these areas   with an antibacterial and antifungal cleaner. Rinse both   items thoroughly with water and ensure that the drain   outlets are operating properly.   ELECTRICAL SHOCK HAZARD!   Turn off electrical power before service or   installation. All eletrical connections and wiring   MUST be installed by a qualified electrician   and conform to the National Code and all local   codes which have jurisdiction. Failure to do so   can result in property damage, personal injury   and/or death.   30   eLeCTRICAL TROUBLeshOOTINg ChART - COOLINg   9k BTU, 12k BTU, & 18k BTU   NO COOLING OPERATION   Before continuing   check for Error   Insure that Fuses   are good and/or that   Circuit Breakers are   on and voltage is 208/230   Codes, see   electronics control   diagnostics and   test mode, page 15   O.K.   Set thermostat to   "Cool," and the Temp.   below the present   Room Temp.   Nothing operates,   entire system   appears dead   Yes   No   O.K.   Check Supply Circuit’s   jumper at transformer. If   okay, replace board   Line voltage present   at the Transformer   Primary   Compressor and Fan   Motor should now   operate   Compressor runs but   Blower/Fan doesn't   Fan runs but   Compressor doesn't   No   No   Yes   Yes   Yes   Yes   Problems indicated with   Control Transformer   replace board   24 Volts at   See Refrigerant Circuit   diagnosis if unit still is   not cooling properly   “R” Terminal on board   No   No   Yes   24 Volts present at   Y terminals on   t-stat and board?   Problems indicated with   Room Thermostat or   Control Wiring   Yes   208/230 Volts present   at #1 relay on board?   Replace board   Yes   Defective t-stat   defective control wiring   or transformer   24V at t-stat and   control wiring?   No   No   Yes   Yes   Compressor and fan   motor should now   operate   No   Yes   Problems indicated   in Blower Relay   of board   Is Line Voltage present   at Motor Leads?   No   Supply Circuit   problems, loose   Connections, or bad   Relays/Board   Is Locked Rotor   See Refrigerant   Circuit Diagnosis if   unit still is not cooling   properly   Yes   Voltage a minimum of   197 Volts?   No   No   Yes   Check Capacitor, is   Capacitor Good?   Replace Capacitor   No   No   Replace Capacitor   and/or Start Assist   Device   Are Capacitor and (if   so equipped) Start   Assist good?   Yes   Possible motor   problem indicated.   Check motor   Yes   Motor should run   thoroughly   Allow ample time   for pressures to   equalize   Have System   Pressures Equalized?   No   No   Yes   Possible Compressor   problem indicated.   See Compressor   Checks   Compressor should   run   31   eLeCTRICAL TROUBLeshOOTINg ChART - COOLINg   24k BTU   NO COOLING OPERATION   Before continuing   check for Error   Insure that Fuses   are good and/or that   Circuit Breakers are   on and voltage is 208/230   Codes, see   electronics control   diagnostics and   test mode, page 15   O.K.   Set thermostat to   "Cool," move the Temp.   lever below the present   Room Temp.   Nothing operates,   entire system   appears dead   Yes   No   O.K.   Check Supply Circuit’s   jumper at transformer. If   okay, replace board   Line voltage present   at the Transformer   Primary   Compressor outdoor   fan motor and indoor   blower should now   operate   Compressor and outdoor   fan motor run but indoor   blower does not run   Indoor blower runs but   outdoor fan motor and   compressor do not run   No   No   No   No   Yes   Yes   Yes   Yes   Problems indicated with   Control Transformer   replace board   24 Volts at   “R” Terminal on board   See Refrigerant Circuit   diagnosis if unit still is   not cooling properly   Yes   Yes   24 Volts present at   Y terminals on   t-stat and board?   Problems indicated with   Room Thermostat or   Control Wiring   Yes   Yes   208/230 Volts present   at #1 relay and “OD”   terminal on board?   Replace board   Defective t-stat   defective control wiring   or transformer   24V at t-stat and   control wiring?   No   No   No   Yes   Yes   208/230 Volts present   at compressor’s   contactor?   Check contactor   If defective replace   Yes   Yes   Compressor and   outdoor fan motor   should now operate   No   Problems indicated   in Blower Relay   of board   Yes   Is Line Voltage present   at Motor Leads?   No   Supply Circuit   problems, loose   Connections, or bad   Relays/Board   Is Locked Rotor   See Refrigerant   Circuit Diagnosis   if unit still is not   cooling properly   Yes   Voltage a minimum of   197 Volts?   No   No   Yes   Check Capacitor, is   Capacitor Good?   Replace Capacitor   No   No   Replace Capacitor   and/or Start Assist   Device   Are Capacitor and (if   so equipped) Start   Assist good?   Yes   Possible motor   problem indicated.   Check motor   Yes   Motor should run   thoroughly   Allow ample time   for pressures to   equalize   Have System   Pressures Equalized?   No   No   Yes   Possible Compressor   problem indicated.   See Compressor   Checks   Compressor should   run   32   eLeCTRICAL TROUBLeshOOTINg ChART   heAT PUMP   HEAT PUMP MODE   SYSTEM COOLS WHEN   HEATING IS DESIRED.   Is Line Voltage   Present at   Solenoid Valve?   NO   Is Selector Switch   set for Heat?   YES   NO   Is the Solenoid   Coil Good?   Replace Solenoid Coil   YES   Reversing Valve Stuck   YES   Replace Reversing Valve   33   TROUBLeshOOTINg ChART - COOLINg   REFRIGERANT SYSTEM DIAGNOSIS COOLING   PROBLEM   PROBLEM   PROBLEM   PROBLEM   LOW SUCTION PRESSURE   HIGH SUCTION PRESSURE   LOW HEAD PRESSURE   HIGH HEAD PRESSURE   Low Load Conditions   High Load Conditions   Low Load Conditions   High Load Conditions   Low Air Flow Across   Indoor Coil   High Air Flow Across   Indoor Coil   Refrigerant System   Restriction   Low Air Flow Across   Outdoor Coil   Refrigerant System   Restriction   Reversing Valve not   Fully Seated   Reversing Valve not   Fully Seated   Overcharged   Undercharged   Overcharged   Non-Condensables (air)   Undercharged System   Defective Compressor   Moisture in System   Defective Compressor   TROUBLeshOOTINg ChART - heATINg   REFRIGERANT SYSTEM DIAGNOSIS HEATING   PROBLEM   PROBLEM   PROBLEM   PROBLEM   LOW SUCTION PRESSURE   HIGH SUCTION PRESSURE   LOW HEAD PRESSURE   HIGH HEAD PRESSURE   Low Air Flow Across   Outdoor Coil   Outdoor Ambient Too High   for Operation in Heating   Refrigerant System   Restriction   Outdoor Ambient Too High   For Operation In Heating   Refrigerant System   Restriction   Reversing Valve not   Fully Seated   Reversing Valve not   Fully Seated   Low Air Flow Across   Indoor Coil   Undercharged   Overcharged   Undercharged   Overcharged   Non-Condensables (air)   in System   Moisture in System   Defective Compressor   Defective Compressor   34   COOL wITh eLeCTRIC heAT   eLeCTRICAL & TheRMOsTAT wIRINg DIAgRAM   VeA 09/12/18 with 2.5 kw, 3.4 kw or 5kw   eLeCTRIC heAT   NOTE:   THE DIAGRAM ABOVE, ILLUSTRATES THE TYPICAL THERMOSTAT WIRING FOR TWO SPEED   FAN OPERATION. SEE THE UNIT CONTROL PANEL FOR THE ACTUAL UNIT WIRING DIAGRAM   AND SCHEMATIC.   35   heAT PUMP wITh eLeCTRIC heAT   eLeCTRICAL & TheRMOsTAT wIRINg DIAgRAM   VhA 09/12/18 with 2.5 kw, 3.4 kw or 5kw   eLeCTRIC heAT   NOTE:   THE DIAGRAM ABOVE, ILLUSTRATES THE TYPICAL THERMOSTAT WIRING FOR TWO SPEED   FAN OPERATION. SEE THE UNIT CONTROL PANEL FOR THE ACTUAL UNIT WIRING DIAGRAM   AND SCHEMATIC.   36   COOL wITh eLeCTRIC heAT   eLeCTRICAL & TheRMOsTAT wIRINg DIAgRAM   VeA 24 with 2.5 kw, 3.4 kw or 5kw eLeCTRIC heAT   37   heAT PUMP wITh eLeCTRIC heAT   eLeCTRICAL & TheRMOsTAT wIRINg DIAgRAM   VhA 24 with 2.5 kw, 3.4 kw or 5kw eLeCTRIC heAT   38   COOL wITh eLeCTRIC heAT   eLeCTRICAL & TheRMOsTAT wIRINg DIAgRAM   VeA 24 with 7.5 kw and 10 kw eLeCTRIC heAT   39   heAT PUMP wITh eLeCTRIC heAT   eLeCTRICAL & TheRMOsTAT wIRINg DIAgRAM   VhA 24 with 7.5 kw and 10kw eLeCTRIC heAT   40   TeChNICAL seRVICe DATA   INDOOR COIL   TEMPERATURE   º F   ELECTRICAL   RATINGS   OPERATING   PRESSURES   Refrigerant   Charge   OUTDOOR COIL Discharge Line Suction Line   SERVICE DATA   Cooling¹   TEMPERATURE   º F   Temperature   º F   Temperature Super Heat Sub-Cooling   º F   Temperature   Voltage   Amps Supply Air   Suction Discharge R-410A - Oz.   Drop ¨   22   VEA09K**RTL   VEA12K**RTL   VEA18K**RTL   VEA24K**RTL   VHA09K**RTL   VHA12K**RTL   VHA18K**RTL   VHA24K**RTL   230/208   230/208   230/208   230/208   230/208   230/208   230/208   230/208   4.2   5.2   58   57   55   55   57   55   51   51   118   116   127   125   117   119   129   128   156   158   180   170   155   165   190   174   66   59   60   61   62   65   60   60   9 24   17   28   34   20   23   35   32   151   141   135   135   155   145   133   140   389   396   455   440   405   450   465   480   33.5   32.0   48.0   65.0   39.0   42.0   45.0   74.0   23   12   12   10   12   15   14   12   8.1   25   10.0   4.1   25   23   5.3   25   8.2   10.6   29   29   ¹Test Conditions: 80º F, Room Air Temperature with 50% Relative Humidity, and 95º F, Outdoor Air Temperature with 40% Relative Humidity   **Denotes Heater KW - Numbers Vary   41   TECHNICAL SUPPORT   CONTACT INFORMATION   FRIEDRICH AIR CONDITIONING CO.   Post Office Box 1540 · San Antonio, Texas 78295-1540   4200 N. Pan Am Expressway · San Antonio, Texas 78218-5212   (210) 357-4400 · 1-800-541-6645 · FAX (210) 357-4490   Printed in the U.S.A.   VPK-ServMan-L (1-10)   Printed in the U.S.A.   FRIEDRICH AIR CONDITIONING CO.   Post Office Box 1540 · San Antonio, Texas 78295-1540   4200 N. Pan Am Expressway · San Antonio, Texas 78218-5212   (210) 357-4400 · FAX (210) 357-4490   VPK-ServMan-L (1-10)   Printed in the U.S.A.   |