Friedrich Air Conditioner YS12 User Manual

Room Air Conditioners  
AUTO FAN  
CONTINUOUS  
AUTO  
C
F
SYSTEM  
FAN MODE  
POWER  
FAN SPEED  
SCHEDULE  
Standard Chassis Models  
115-Volt: SS08, SS10, SS12, SS14, SM15  
208-230-Volt:  
SS12, SS15 , SM18 , SM21, SM24  
SL 22, SL 24, SL 28, SL 36  
115-Volt: YS10  
208-230-Volt:  
E S12, E S15, YS12 , E M18  
YM18, E M24, E L 36, YL 24  
Table of Contents  
Safety Precautions................................................................................................................................................................................................................... 4  
Unpacking Instructions............................................................................................................................................................................................................. 5  
WARNING: Before Operating Your Unit .................................................................................................................................................................................. 6  
Standard Filter Cleaning / Installation Instructions.................................................................................................................................................................. 7  
Premium Carbon Filter Installation Instructions....................................................................................................................................................................... 8  
Control Panel Operation ......................................................................................................................................................................................................... 9  
New Kühl Control Options ...................................................................................................................................................................................................... 10  
Control Panel Operation Instructions ................................................................................................................................................................................... 11  
Remote Control Operation..................................................................................................................................................................................................... 20  
Remote Effectiveness............................................................................................................................................................................................................ 20  
.......................................................................................................................................................................................... 22  
Remote Thermostat ............................................................................................................................................................................................................... 22  
Installation Instructions .......................................................................................................................................................................................................... 23  
Standard Window Installation ................................................................................................................................................................................................ 25  
Cord Routing Change ............................................................................................................................................................................................................ 34  
Through-the-Wall Installation................................................................................................................................................................................................. 36  
Final Inspection & Start-up Checklist.....................................................................................................................................................................................40  
Routine Maintenance ............................................................................................................................................................................................................. 41  
Service and Assistance ......................................................................................................................................................................................................... 41  
Available Accessories............................................................................................................................................................................................................ 41  
Troubleshooting Tips.............................................................................................................................................................................................................. 42  
Addendum 1........................................................................................................................................................................................................................... 44  
Warranty ................................................................................................................................................................................................................................ 45  
3
Safety Precautions  
Your safety and the safety of others are very important.  
We have provided many important safety messages in this manual and on your appliance. Always read and obey all  
safety messages.  
This is a safety Alert symbol.  
This symbol alerts you to potential hazards that can kill or hurt you and others.  
All safety messages will follow the safety alert symbol with the word “WARNING”  
or “CAUTION”. These words mean:  
Indicates a hazard which, if not avoided, can result in severe personal injury or  
WARNING  
death and damage to product or other property.  
Indicates a hazard which, if not avoided, can result in personal injury and  
CAUTION  
damage to product or other property.  
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you  
what will happen if the instructions are not followed.  
Indicates property damage can occur if instructions are not followed.  
NOTICE  
WARNING  
Refrigeration system  
under high pressure  
Do not puncture, heat, expose to flame or  
incinerate.  
Only certified refrigeration technicians should  
service this equipment.  
R410A systems operate at higher pressures  
than R22 equipment. Appropriate safe  
service and handling practices must be used.  
Only use gauge sets designed for use with  
R410A. Do not use standard R22 gauge sets.  
4
Unpacking Instructions  
STEP 5.  
STEP 6.  
STEP 7.  
Slide the foam front support forward  
STEP 1.  
STEP 2.  
STEP 3.  
STEP 4.  
Cut all 4 packing straps.  
Carefully lift decorative front box from foam front support  
Remove decorative front and set safely aside  
Remove wooden shipping bar dividers.  
Remove top foam pads.  
Slowly remove outer box, careful not to loosen decorative front.  
5
WARNING: Before Operating Your Unit  
WARNING  
NOTICE  
Do not use the LCDI device as an ON/OFF switch.  
Electrical Shock Hazard  
Make sure your electrical receptacle has the  
same configuration as your air conditioner’s  
plug. If different, consult a Licensed Electrician.  
Failure to adhere to this precaution may cause  
premature equipment malfunction.  
Do not use plug adapters.  
Do not use an extension cord.  
Do not remove ground prong.  
Once plugged in, the unit will operate normally without the need to reset  
the LCDI device. If the LCDI device fails to trip when tested or if the power  
supply cord is damaged, it must be replaced with a new power supply cord  
from the manufacturer. Contact our Technical Assistance Line at (800)  
541-6645. To expedite service, please have your model number available.  
Always plug into a grounded 3 prong oulet.  
Failure to follow these instructions can result in  
death, fire, or electrical shock.  
M ake sure the wiring is adequate for your unit.  
Table 1.  
If you have fuses, they should be of the time delay type. Before you install  
or relocate this unit, be sure that the amperage rating of the circuit breaker  
or time delay fuse does not exceed the amp rating listed in Table 1.  
CIRCUIT RATING  
OR TIME DELAY  
FUSE  
REQUIRED  
WALL  
RECEPTACLE  
MODEL  
NEMA  
NO.  
AMP  
VOLT  
DO NOT use an extension cord.  
The cord provided will carry the proper amount of electrical power to the  
unit; an extension cord may not.  
SS08, SS10  
SS12, SS14  
15  
125  
5-15R  
6-15R  
6-20R  
YS10, SM15  
M ake sure that the receptacle is compatible with  
the air conditioner cord plug provided.  
SS12, SS15  
SM18, SM21  
SL22, SL24  
15  
20  
250  
250  
SM24, SL28  
ES12, ES15  
YS12  
Proper grounding must be maintained at all times. Two prong receptacles  
The grounded receptacle should meet all national and local codes and  
ordinances. You must use the three prong plug furnished with the air  
conditioner. Under no circumstances should you remove the ground  
prong from the plug.  
SL36, EM18  
EM24, EL36  
YM18, YL24  
30  
250  
6-30R  
Test the power cord  
Figure 1  
All Friedrich room air conditioners are shipped from the factory with a  
Leakage Current Detection Interrupter (LCDI) equipped power cord. The  
LCDI device on the end of the cord meets the UL and NEC requirements  
for cord connected air conditioners.  
RESET  
To test your power supply cord:  
1. Plug power supply cord into a grounded 3 prong outlet.  
TEST  
2. Press RESET (See Figure 1).  
WARNING:  
TEST BEFORE EACH USE!  
1. PRESS REST BUTTON.  
2. PLUG LCDI INTO POWER  
RECEPTACLE.  
3. Press TEST, listen for click; the RESET button trips and pops out.  
3. PRESS TEST BUTTON,  
RESET BUTTON SHOULD  
POP UP.  
4. PRESS RESET BUTTON  
FOR USE.  
4. Press and release RESET (Listen for click; RESET button latches  
and remains in). The power cord is ready for use.  
DO NOT USE IF ABOVE TEST  
FAILS.  
WHEN GREEN LIGHT IS ON.  
IT IS WORKING  
PROPERLY!  
FRR072  
6
Standard Filter Cleaning / Installation Instructions  
STEP 2.  
STEP 1.  
NOTE:  
Figure 2  
Figure 4  
FILTER  
FILTER  
GRIP  
FRR071  
Figure 3  
FRR047  
STEP 3.  
Swing the front frame open. Clean the front frame by washing  
Figure 5  
FILTER  
GRIP  
A
TOP TAB  
HANDLE  
FRONT  
FRR052  
FRAME WITH  
STANDARD  
MESH FILTER  
FRR048  
STEP 4.  
NOTE:  
the tab in the frame stops the handle from sliding in, slide the  
handle from the other direction. Do not force the handle into  
the frame.  
STEP 5.  
the inside of the front door.  
7
Premium Carbon Filter Installation Instructions  
STEP 4.  
STEP 1.  
STEP 2.  
STEP 3.  
NOTE:  
in Figure 4.  
STEP 5.  
and slide the assembly into the unit as per the instructions  
on the door.  
as shown in Figure 6.  
NOTE: Make sure the frame with the mesh is facing towards you.  
NOTE:  
the tab in the frame stops the handle from sliding in, slide the  
handle from the other direction. Do not force the handle into  
the frame.  
Figure 6  
Figure 7  
FRONT FRAME WITH  
MESH FILTER  
FRR050  
FRR051  
8
Control Panel Operation  
Let’s check out how to control your air conditioner. On the control panel, just above the POWER , is a liquid crystal display (LCD). All of the control panel function  
buttons and mode icons can be viewed in Figure 8.  
Power On – Press the button to turn on the air conditioner. The power button illuminates to indicate that the power is on. The backlight on the power switch  
will automatically dim to 20% intensity after 15 seconds of inactivity. The remote control can also be used to turn power ON / OFF (See Remote Control).  
Display  
inactivity, the display dims to 20% intensity. After an additional 120 seconds, the display switches off. Touching any button automatically changes the display  
to full brightness.  
There are three control push buttons on each side of the display.  
Figure 8  
FAN SPEED  
TEMPERATURE  
TIMER / SCHEDULE  
SYSTEM  
FAN MODE  
Turns ON or OFF  
Cycles between Sets fan to either:  
Increment UP  
Sets fan speed:  
LOW, MED,  
AUTO, HEAT,  
- Cycle automatically  
TEMPERATURE:  
:
ON / OFF  
IR WINDOW  
COOL, or FAN - Run continuously  
HIGH or AUTO  
(if equipped)  
Increment DOWN  
Do not block  
Turns unit on/off  
ONLY  
(if equipped)  
F
SET POINT  
AUTO SPEED  
COOL  
HEAT  
FAN  
ONLY  
CONTROL  
LOCKED  
MAINTENANCE  
REQUIRED  
WI-FI  
OPERATING  
(if equipped)  
AUTO  
WAIT  
Automatically switches  
between cool & heat  
AUTO  
F
C
2 DIGIT DISPLAY  
Shows Setting for:  
- Set Point (Temperature)  
- Room Temperature  
- Clock (AM/PM)  
AUTO FAN  
CONTINUOUS  
AM  
PM  
ON OFF  
SCHEDULE  
SET POINT  
ROOM TEMP  
SCHEDULE ON  
TIMER ON  
FAN SPEED  
CHECK $MART  
FILTER  
Selected fan speed  
AUTO SPEED  
AUTO SPEED  
Automatically  
selects best fan  
cooling speed  
FILTER  
Check / Clean  
$MART OPERATING  
(if equipped)  
9
Kühl Control Options  
scheduling including wireless capabilities  
Kühl gives you a variety of options for control, programming, and  
The  
The “Residential” (40 Hr. Work Week) Schedule has four (4) time periods: 06:00,  
08:00, 18:00, and 22:00. This option will cause your Kühl Q unit to raise the room  
temperature temporarily to 85°F during the hours when most people are away  
at work, lower them again to 78°F prior to the time when most people will return  
home, and then raise slightly to 82°F to maintain a comfortable temperature  
overnight.  
Wireless Programming and Control:  
. The new FriedrichLink™ Adapter (sold seperately) allows you to conviently  
control, program and monitor your air conditioning unit remotely from a  
smartphone or computer.  
The “Commercial” (5-Day Business Week) Schedule has two (2) time periods:  
07:00 and 18:00. This option will cause your air conditioner to raise temperatures  
to 84°F after typical working hours and on weekends when commercial spaces  
are typically unoccupied.  
FriedrichLink™ Adapter accessory available through Friedrich authorized  
(See Control Panel Operation Instructions Section)  
Pre-Programmed Scheduling Options:  
Customizable Programming Options:  
Your unit’s digital control comes equipped with a 24-hour timer and two pre-  
programmed 7-day energy management options.  
Customizable schedules, with up to four temperature adjustments per day, can  
either be uploaded to the unit via the airconditioner’s built-in micro USB interface  
or conveniently transmitted wirelessly using the new FriedrichLink™ Adapter  
accessory, greatly simplifying the programming of one or multiple units.  
See Figure 9.  
24-Hour Timer  
The 24-hour timer allows you to turn the unit off and on at pre-set times by  
setting an on and off time on the unit control panel. (See page 12 for details on  
timer set-up.)  
Programming instructions.  
Pre-programmed Energy Management  
Your unit comes from the factory with two (2) Pre-programmed Energy  
Management settings are shown in Addendum 1 (Residential & Commercial  
Schedule Table).  
Energy Management Schedule Options are:  
1. Residential Schedule – 40 Hr. Work Week  
2. Commercial Schedule – 5-Day Business Week  
Figure 9  
MODEL NUMBER VOLTS 115  
AIR CONDITIONING CO. YS10M10A 60 HZ PH  
SAN ANTONIO, TEXAS SERIAL NUMBER VOLTS MIN 108 EER 12.0  
ASSEMBLED IN MEXICO LICY00008 AMPS 8.0  
COOLING  
HEATING  
REFRIGERANT XXXXXXXXX XXXXXXXXXX FUSE PROTECTED  
U
/
1
BTH/HR 6500 BTH/HR 6500 30.1 OZ R410A 600 PSIG HS XXXXXXXXX  
CIRCUITS USE 15A  
300 PSIG LS XXXXXXXXXX TIME DELAY FUSE  
XXXXXXXXXX  
X
L
XX  
XXXXX  
XXXXXXXXXX  
EER 10.4  
AMPS 7.0  
FriedrichLink™ Adapter  
10  
FAN ONLY MODE  
Control Panel Operation Instructions  
SYSTEM  
SYSTEM - The  
button allows you to sequentially select up to four  
modes of operation:  
AUTO - AUTO - Not available on some models  
COOL  
Not available on some models  
HEAT  
FAN ONLY  
AUTO MODE  
FRR105  
When in the - AUTO-, COOL or HEAT or FAN ONLY mode,  
you can also select FAN MODE, FAN SPEED, TIMER SCHEDULE,  
- AUTO -  
AUTO FAN  
F
. The SYSTEM MODE does not change.  
and  
FA N  
MODE  
AUTO FAN  
FAN MODE – The  
button allows you to select between  
and  
SET POINT  
CONTINUOUS  
modes.  
AUTO FAN (No Cooling Demand)  
FRR204  
COOL MODE  
F
AUTO FAN  
SET POINT  
F
AUTO FAN  
SET POINT  
FRR112  
AUTO FAN  
When in the  
mode, the fan only operates when the system has  
a demand to cool or heat the room. Note: the fan is off (no fan speed icon),  
indicating no command for cooling or heating.  
FRR103  
HEAT MODE  
AUTO FAN (Cooling Demand)  
F
F
AUTO FAN  
AUTO FAN  
SET POINT  
SET POINT  
FRR104  
FRR106  
System has a demand for cooling. The fan is operating at a medium speed.  
N
SPEED  
FAN  
SPEED  
FAN SPEED - Depending on your model, the  
button allows you to toggle between four or five modes of operation: LOW, MEDIUM, HIGH and AUTO.  
AUTO  
AUTO  
When fan speed AUTO FAN mode (SYSTEM mode AUTO, COOL or HEAT) is selected, fan speed automatically varies depending on the difference between  
the unit’s set point on the control panel and the actual room temperature. When the system detects a wide difference between the set point and the actual  
room temperature the fan speed increases to HIGH for a period of time. The fan speed decreases, in step, as the temperature difference decreases. When the  
room temperature matches the system's set point, fan speed returns to the original setting.  
11  
CONTINUOUS  
The  
F
CONTINUOUS  
SET POINT  
F
AUTO FAN  
SET POINT  
FRR113  
CONTINUOUS  
In the  
fan mode, the fan operates all the time. The system  
FRR123  
UP and DOWN  
- arrows - Pressing either  
or button changes  
the system's set point (desired room temperature). These buttons are also  
used to make system parameter changes latter in this manual.  
The icon illuminates.  
system ON and OFF time window. For example, you can command the  
system to turn ON at 8:15 am and turn OFF at 1:30 pm everyday.  
The SCHEDULE function allows you to choose either Residential (option  
2) or Commercial (option 3). The Residential and Commercial options are  
described later in this manual.  
F
AUTO FAN  
OTHER FUNCTIONS  
SET POINT  
Figure 10  
FRR100  
F
AUTO FAN  
SET POINT  
One press equals 1 degree of change. Holding the button down fFoRrRm1o01re  
than 0.6 seconds starts the fast increment/decrement change of the set  
point.  
SET TIME- To adjust the unit's time press and hold the HOUR and the MIN  
buttons for three seconds (Refer to Figure 10).  
TIMER SCHEDULE - The  
button allows you to select the TIMER  
SCHEDUL  
E
or  
The  
function.  
AM  
FRR128  
The unit's current hour displays. Use the  
or  
buttons to adjust the  
hour. To change from AM to PM continue to increment (roll) the display.  
Press TIMER SET (Refer to Figure 10) button to display the unit's current  
minutes.  
FRR122  
The icon illuminates.  
12  
To switch from degrees Fahrenheit (F) to Celsius (C), press  
buttons for three seconds.  
or  
FRR129  
FRR133  
Use the  
or  
buttons to adjust the minutes. The clock is now set  
for 11:25 AM. Press TIMER SET (Refer to Figure 10) button to display the  
unit's day setting.  
from F to C, press the  
or  
button within 5 seconds.  
FRR134  
FRR130  
Use the  
or  
buttons to adjust the day (1 to 7). The day setting is up  
to the you the user. If you set the current day = 1, and today is Tuesday,  
then Day 1 = Tuesday.  
C
AUTO FAN  
F
SET POINT  
AUTO FAN  
SET POINT  
FRR135  
The ºF icon goes away and the ºC icon illuminates on the normal display.  
FRR131  
DIM Function  
Press TIMER SET (Refer to Figure 10) button to exit and save the SET  
TIME function. The TIMER SET button must be pressed within 15 second.  
Button inactivity for more than 15 seconds causes the display to time out  
and return to the normal operating display.  
There are three separate display brightness levels, AUTO, 20% and full  
(100%). To change the DIM setting, press the Power button for three  
seconds.  
ºF - ºC Select  
F
AUTO FAN  
SET POINT  
FRR192  
The 1 indicates a DIM setting of Auto (factory default). Use the  
buttons to change the setting.  
or  
FRR132  
13  
F
AUTO FAN  
SET POINT  
FRR120  
FRR193  
This means there is a compressor demand but the system is not ready  
for the compressor to operate. For example a short power outage, the  
compressor will not restart until the internal pressures of the compressor  
are at the proper level.  
The 2 indicates a DIM setting of 20%. Press the TIMER SET button within  
15 seconds to save the setting. Button inactivity for more than 15 seconds  
causes the display to time out and return to the normal operating display.  
FRR179  
FRR194  
If the room freeze protection is active, the display indicates this by showing  
The 3 indicates a DIM setting of 100% (full brightness). Press the TIMER  
SET (Refer to Figure 10) button within 15 seconds to save the setting.  
Button inactivity for more than 15 seconds causes the display to time out  
and return to the normal operating display.  
SET (Figure 10) button overrides the freeze protection alert for 5 minutes.  
This alert appears when the room is too cold for the air conditioner to  
operate properly. Another cause of alert occurs when to much ice builds  
up on the unit's condenser.  
Lock Control Panel  
Alerts  
FA N  
SPEED  
To lock the front panel controls, press and hold the  
+
buttons  
CHECK  
FI LT ER  
for 3 seconds. The lock icon  
illuminates to indicate the locked status.  
icon displays.  
F
AUTO FAN  
F
AUTO FAN  
SET POINT  
SET POINT  
FILTER  
16  
FRR1  
FRR118  
FA N  
SPEED  
To unlock, presses and hold the  
+
buttons for 3 seconds.  
FA N  
MODE  
The alert can be dismissed by pressing the  
and  
for 3 seconds.  
When maintenance is required, a service icon  
appears on screen.  
F
AUTO FAN  
SET POINT  
FRR117  
The lock icon  
disappears to indicate unlocked status.  
14  
External Control Status  
3. Commercial Schedule - When selected the unit follows a pre-  
programmed set of operational parameters that covers 7 days of  
the week with 2 time windows during each day. Each time window  
ꢁꢍꢊꢃꢎꢇ!ꢊꢃꢅꢗꢆꢃꢊꢂꢇꢃꢅꢓꢃ"ꢃꢅꢛꢂꢈꢍꢇꢎꢆꢜꢃꢛꢍꢈꢍꢌꢂꢇꢂꢈꢊꢞꢃ#ꢂꢓꢂꢈꢃꢇꢅꢃꢖꢑꢑꢂꢆꢑꢒꢌꢃ  
$ꢞꢃ  
$MART  
The  
icon illuminates to indicate that the system is being controlled  
remotely.  
F
AUTO FAN  
79  
SET POINT  
$MART  
1
SCHEDULE  
FRR125  
FRR137  
To change the  
ꢃꢊꢂꢉꢂꢄꢇꢎꢅꢆ*ꢃꢛꢈꢂꢊꢊꢃꢍꢆꢑꢃꢁꢅꢉꢑꢃꢇꢁꢂꢃꢀ<>?#ꢏꢐ@J?VXZ?ꢃ  
button for 3 sec.  
F
AUTO FAN  
If the Schedule function is available, the system displays the icon +  
SCHEDULE  
icon. The display indicates the schedule function that is active.  
79  
To change to an alternate schedule (2 or 3), press the  
or  
button.  
SET POINT  
If the Schedule function is not available, the Timer icon shows without  
SCHEDULE  
the  
icon.  
ꢀꢅꢃꢊꢍ[ꢂꢃꢍꢆꢑꢃꢂ\ꢎꢇꢃꢇꢁꢎꢊꢃꢊꢂꢉꢂꢄꢇꢎꢅꢆ*ꢃꢛꢈꢂꢊꢊꢃꢇꢁꢂꢃꢀ<>?#ꢃꢐ?ꢀꢃ]ꢒꢇꢇꢅꢆꢃ^ꢚꢎꢜꢒꢈꢂꢃ$_`ꢞ  
FRR126  
If there is no button activity for 15 seconds, the function will time out and  
ꢉꢂꢍ[ꢂꢃꢇꢁꢂꢃꢅꢈꢎꢜꢎꢆꢍꢉꢃꢊꢂꢉꢂꢄꢇꢎꢅꢆꢞꢃꢘꢆꢄꢂꢃꢇꢁꢂꢃꢊꢂꢉꢂꢄꢇꢎꢅꢆꢃꢎꢊꢃꢊꢍ[ꢂꢑꢃꢅꢈꢃꢇꢎꢌꢂꢑꢃꢅꢒꢇ*ꢃꢇꢁꢂꢃ  
display reverts to the normal display.  
The  
icon illuminates to indicate that the system is receiving a Wi-Fi  
connection.  
ADVANCED FUNCTIONS  
Zꢂꢇꢃꢌꢂꢃꢛꢒꢇꢃꢎꢆꢃꢛꢉꢍꢎꢆꢃꢗꢅꢈꢑꢊꢃꢌꢍꢆꢋꢃꢅꢓꢃꢋꢅꢒꢈꢃꢒꢆꢎꢇ!ꢊꢃꢍꢑ[ꢍꢆꢄꢂꢑꢃꢓꢒꢆꢄꢇꢎꢅꢆꢊꢃ^ꢀꢎꢌꢂꢈ*ꢃ  
Schedule, Error Mode, Test Mode, and Maintenance Menu). The functions  
mentioned in the following section may or may not be available depending  
on the air conditioner model.  
2
Timer/Schedule Select  
SCHEDULE  
FRR138  
F
AUTO FAN  
ꢖꢓꢇꢂꢈꢃꢛꢈꢂꢊꢊꢎꢆꢜꢃꢇꢁꢂꢃ  
or  
button, within 15 second of pressing the  
]ꢒꢇꢇꢅꢆꢃꢓꢅꢈꢃ{ꢃꢊꢂꢄꢅꢆꢑꢊ*ꢃꢇꢁꢂꢃꢑꢎꢊꢛꢉꢍꢋꢃꢎꢆꢑꢎꢄꢍꢇꢂꢊꢃꢍꢃꢄꢁꢍꢆꢜꢂꢃꢇꢅꢃꢀꢎꢌꢂꢈꢏꢐꢄꢁꢂꢑꢒꢉꢂꢈꢃ  
|ꢞꢃꢀꢅꢃꢊꢍ[ꢂꢃꢍꢆꢑꢃꢂ\ꢎꢇꢃꢇꢁꢎꢊꢃꢊꢂꢉꢂꢄꢇꢎꢅꢆ*ꢃꢛꢈꢂꢊꢊꢃꢇꢁꢂꢃꢀ<>?#ꢃꢐ?ꢀꢃ]ꢒꢇꢇꢅꢆꢃ^ꢚꢎꢜꢒꢈꢂꢃ$_`ꢞ  
79  
SET POINT  
FRR136  
F
ꢀꢁꢂꢃꢄꢅꢆꢇꢈꢅꢉꢃꢊꢋꢊꢇꢂꢌꢃꢁꢍꢊꢃꢇꢁꢈꢂꢂꢃꢀꢎꢌꢂꢈꢏꢐꢄꢁꢂꢑꢒꢉꢂꢃꢓꢒꢆꢄꢇꢎꢅꢆꢊꢔ  
AUTO FAN  
1. Timer (factory default) ꢕꢃꢖꢉꢉꢅꢗꢊꢃꢋꢅꢒꢃꢇꢅꢃꢄꢅꢌꢌꢍꢆꢑꢃꢇꢁꢂꢃꢒꢆꢎꢇꢃꢇꢅꢃꢇꢒꢈꢆꢃ  
ꢘꢙꢃꢍꢆꢑꢃꢘꢚꢚꢃꢍꢇꢃꢇꢎꢌꢂꢃꢋꢅꢒꢃꢛꢈꢅꢜꢈꢍꢌꢃꢗꢎꢇꢁꢎꢆꢃꢍꢃꢝꢃꢑꢍꢋꢃꢗꢎꢆꢑꢅꢗꢞꢃꢐꢂꢇꢇꢎꢆꢜꢃ  
the start, stop and day window can be found latter in this manual.  
79  
SET POINT  
2. Residential Schedule - When selected the unit follows a pre-  
programmed set of operational parameters that covers 7 days of  
the week with 4 time windows during each day. Each time window  
ꢁꢍꢊꢃꢎꢇ!ꢊꢃꢅꢗꢆꢃꢊꢂꢇꢃꢅꢓꢃ"ꢃꢅꢛꢂꢈꢍꢇꢎꢆꢜꢃꢛꢍꢈꢍꢌꢂꢇꢂꢈꢊꢞꢃ#ꢂꢓꢂꢈꢃꢇꢅꢃꢖꢑꢑꢂꢆꢑꢒꢌꢃ  
$ꢞꢃ  
FRR136  
The display reverts to the normal display.  
ꢀ5  
F
AUTO FAN  
79  
SET POINT  
FRR139  
FRR143  
The display returns to normal once the settings are saved.  
ꢙꢅꢗꢃꢇꢁꢂꢃꢆꢂ\ꢇꢃꢇꢎꢌꢂꢃꢇꢁꢂꢃ  
button is pressed the system operates in the  
mode (1, 2 or 3) you programmed.  
Timer Stop Time  
Modify the TIMER Function  
Timer Start Time  
F
AUTO FAN  
F
79  
SET POINT  
AUTO FAN  
79  
SET POINT  
FRR144  
ꢀꢁꢂꢃꢑꢎꢊꢛꢉꢍꢋꢃꢊꢁꢅꢗꢊꢃꢍꢃꢆꢅꢈꢌꢍꢉꢃꢊꢋꢊꢇꢂꢌꢞꢃ}ꢈꢂꢊꢊꢃꢍꢆꢑꢃꢁꢅꢉꢑꢃꢇꢁꢂꢃ><ꢙꢃ]ꢒꢇꢇꢅꢆꢃ^ꢚꢎꢜꢒꢈꢂꢃꢃ  
ꢃ$_`ꢃꢓꢅꢈꢃ{ꢃꢊꢂꢄꢅꢆꢑꢊꢞꢃꢙꢅꢇꢂꢃꢇꢁꢂꢃꢀꢎꢌꢂꢈꢃꢊꢇꢍꢈꢇꢃꢕꢃꢊꢇꢅꢛꢃꢇꢎꢌꢂꢊꢃꢌꢍꢋꢃ]ꢂꢃꢊꢂꢇꢃꢂ[ꢂꢆꢃꢗꢁꢂꢆꢃ  
the system is in the Schedule mode.  
FRR140  
ꢀꢁꢂꢃꢑꢎꢊꢛꢉꢍꢋꢃꢊꢁꢅꢗꢊꢃꢍꢃꢆꢅꢈꢌꢍꢉꢃꢊꢋꢊꢇꢂꢌꢞꢃ}ꢈꢂꢊꢊꢃꢍꢆꢑꢃꢁꢅꢉꢑꢃꢇꢁꢂꢃJꢘX#ꢃ]ꢒꢇꢇꢅꢆꢃ  
^ꢚꢎꢜꢒꢈꢂꢃ$_`ꢃꢓꢅꢈꢃ{ꢃꢊꢂꢄꢅꢆꢑꢊꢞꢃꢙꢅꢇꢂꢃꢇꢁꢂꢃꢀꢎꢌꢂꢈꢃꢊꢇꢍꢈꢇꢕꢊꢇꢅꢛꢃꢇꢎꢌꢂꢊꢃꢌꢍꢋꢃ]ꢂꢃꢊꢂꢇꢃꢂ[ꢂꢆꢃ  
when the system is in the Schedule mode.  
AM  
11  
OFF  
AM  
4
ON  
FRR145  
Use the  
or ꢃ]ꢒꢇꢇꢅꢆꢃꢇꢅꢃꢍꢑ~ꢒꢊꢇꢃꢇꢁꢂꢃꢁꢅꢒꢈꢞꢃ}ꢈꢂꢊꢊꢃꢇꢁꢂꢃꢀ<>?#ꢃꢐ?ꢀꢃ]ꢒꢇꢇꢅꢆꢃ  
^ꢚꢎꢜꢒꢈꢂꢃ$_`ꢃꢇꢅꢃꢍꢑ~ꢒꢊꢇꢃꢇꢁꢂꢃꢌꢎꢆꢒꢇꢂꢊꢞ  
FRR141  
Use the  
or ꢃ]ꢒꢇꢇꢅꢆꢃꢇꢅꢃꢍꢑ~ꢒꢊꢇꢃꢇꢁꢂꢃꢁꢅꢒꢈꢞꢃ}ꢈꢂꢊꢊꢃꢇꢁꢂꢃꢀ<>?#ꢃꢐ?ꢀꢃ]ꢒꢇꢇꢅꢆꢃ  
^ꢚꢎꢜꢒꢈꢂꢃ$_ꢃ$_`ꢃꢇꢅꢃꢍꢑ~ꢒꢊꢇꢃꢇꢁꢂꢃꢌꢎꢆꢒꢇꢂꢊꢞ  
55  
OFF  
21  
ON  
FRR146  
Use the  
or ꢃ]ꢒꢇꢇꢅꢆꢃꢇꢅꢃꢍꢑ~ꢒꢊꢇꢃꢇꢁꢂꢃꢌꢎꢆꢒꢇꢂꢊꢞꢃ}ꢈꢂꢊꢊꢃꢇꢁꢂꢃꢀ<>?#ꢃꢐ?ꢀꢃ  
FRR142  
]ꢒꢇꢇꢅꢆꢃ^ꢚꢎꢜꢒꢈꢂꢃ$_`ꢃꢗꢎꢇꢁꢎꢆꢃ$ꢃꢊꢂꢄꢅꢆꢑꢊꢃꢇꢅꢃꢂ\ꢎꢇꢃꢍꢆꢑꢃꢊꢍ[ꢂꢃꢇꢁꢂꢃꢊꢂꢇꢇꢎꢆꢜꢞꢃꢀꢁꢂꢃꢇꢎꢌꢂꢈꢃ  
ꢎꢊꢃꢆꢅꢗꢃꢊꢂꢇꢃꢇꢅꢃꢊꢇꢅꢛꢃꢍꢇꢃ$$ꢔꢃꢖ>ꢞꢃ  
Use the  
or ꢃ]ꢒꢇꢇꢅꢆꢃꢇꢅꢃꢍꢑ~ꢒꢊꢇꢃꢇꢁꢂꢃꢌꢎꢆꢒꢇꢂꢊꢞꢃ}ꢈꢂꢊꢊꢃꢇꢁꢂꢃꢀ<>?#ꢃꢐ?ꢀꢃ  
]ꢒꢇꢇꢅꢆꢃ^ꢚꢎꢜꢒꢈꢂꢃ$_`ꢃꢗꢎꢇꢁꢎꢆꢃ$ꢃꢊꢂꢄꢅꢆꢑꢊꢃꢇꢅꢃꢂ\ꢎꢇꢃꢍꢆꢑꢃꢊꢍ[ꢂꢃꢇꢁꢂꢃꢊꢂꢇꢇꢎꢆꢜꢞꢃꢀꢁꢂꢃꢇꢎꢌꢂꢈꢃ  
ꢎꢊꢃꢆꢅꢗꢃꢊꢂꢇꢃꢇꢅꢃꢊꢇꢍꢈꢇꢃꢍꢇꢃ€ꢔ|$ꢃꢖ>ꢞ  
 
F
F
AUTO FAN  
AUTO FAN  
79 79  
SET POINT  
SET POINT  
SCHEDULE  
FRR147  
FRR151  
The display returns to normal once the settings are saved.  
The Timer ꢃꢎꢄꢅꢆꢃꢃꢊꢇꢅꢛꢊꢃ]ꢉꢎꢆꢎꢆꢜꢃꢍꢓꢇꢂꢈꢃ{ꢃꢊꢂꢄꢅꢆꢑꢊꢞꢃ‚ꢅꢒꢃꢌꢒꢊꢇꢃꢇꢒꢈꢆꢃꢇꢁꢂꢃꢍꢄꢇꢎ[ꢂꢃ  
ꢀꢎꢌꢂꢈꢃꢅꢈꢃꢐꢄꢁꢂꢑꢒꢉꢂꢃꢌꢅꢑꢂꢃꢘꢚꢚꢃ]ꢂꢓꢅꢈꢂꢃꢌꢍꢎꢆꢜꢃꢄꢁꢍꢆꢜꢂꢊꢞꢃꢘꢆꢄꢂꢃꢇꢁꢂꢃꢄꢁꢍꢆꢜꢂꢊꢃ  
Timer - Scheduler Control Block  
are made, press the  
button to re-activate Timer or Schedule mode.  
F
F
AUTO FAN  
AUTO FAN  
79  
SET POINT  
79  
SCHEDULE  
SET POINT  
FRR148  
FRR152  
<ꢓꢃꢇꢁꢂꢃꢒꢆꢎꢇꢃꢎꢊꢃꢅꢛꢂꢈꢍꢇꢎꢆꢜꢃꢎꢆꢃꢇꢁꢂꢃꢀ<>?#ꢃꢅꢈꢃꢐ@J?VXZ?ꢃꢌꢅꢑꢂ*ꢃꢍꢆꢑꢃꢇꢁꢂꢆꢃꢋꢅꢒꢃ  
Schedule ON Scenarios  
ꢛꢈꢂꢊꢊꢃꢍꢆꢋꢃ]ꢒꢇꢇꢅꢆꢃꢂ\ꢄꢂꢛꢇꢃꢇꢁꢂꢃ  
button, the Timer  
icon begins to  
]ꢉꢎꢆꢞꢃꢖꢉꢉꢃ]ꢒꢇꢇꢅꢆꢃꢍꢄꢇꢎꢅꢆꢃꢎꢊꢃ]ꢉꢅꢄꢂꢑꢞ  
F
AUTO FAN  
SCHEDULE  
79  
SET POINT  
SCHEDULE  
FRR153  
The display shows a normal system.  
<ꢓꢃꢇꢁꢂꢃꢐꢄꢁꢂꢑꢒꢉꢂꢃꢓꢒꢆꢄꢇꢎꢅꢆꢃꢎꢊꢃꢇꢒꢈꢆꢂꢑꢃꢘꢙꢃꢑꢒꢈꢎꢆꢜꢃꢆꢅꢈꢌꢍꢉꢃꢅꢛꢂꢈꢍꢇꢎꢅꢆ*ꢃꢇꢁꢂꢃ  
FRR149  
SCHEDULE  
The Timer ꢃꢎꢄꢅꢆꢃꢃꢊꢇꢅꢛꢊꢃ]ꢉꢎꢆꢎꢆꢜꢃꢍꢓꢇꢂꢈꢃ{ꢃꢊꢂꢄꢅꢆꢑꢊꢞꢃ‚ꢅꢒꢃꢌꢒꢊꢇꢃꢇꢒꢈꢆꢃꢇꢁꢂꢃꢍꢄꢇꢎ[ꢂꢃ  
ꢀꢎꢌꢂꢈꢃꢅꢈꢃꢐꢄꢁꢂꢑꢒꢉꢂꢃꢌꢅꢑꢂꢃꢘꢚꢚꢃ]ꢂꢓꢅꢈꢂꢃꢌꢍꢎꢆꢜꢃꢄꢁꢍꢆꢜꢂꢊꢞꢃꢘꢆꢄꢂꢃꢇꢁꢂꢃꢄꢁꢍꢆꢜꢂꢊꢃ  
and Timer  
icons illuminates. The control system immediately runs the  
current period schedule parameters.  
are made, press the  
button to re-activate Timer or Schedule mode.  
<ꢓꢃꢇꢁꢂꢃꢒꢆꢎꢇꢃꢎꢊꢃꢅꢛꢂꢈꢍꢇꢎꢆꢜꢃꢎꢆꢃꢇꢁꢂꢃꢀ<>?#ꢃꢅꢈꢃꢐ@J?VXZ?ꢃꢌꢅꢑꢂ*ꢃꢍꢆꢑꢃꢇꢁꢂꢆꢃꢋꢅꢒꢃ  
ꢛꢈꢂꢊꢊꢃꢍꢆꢋꢃ]ꢒꢇꢇꢅꢆꢃꢂ\ꢄꢂꢛꢇꢃꢇꢁꢂꢃ  
button, the Timer icon begins to blink.  
F
AUTO FAN  
79  
F
SET POINT  
AUTO FAN  
79  
SET POINT  
FRR154  
The display shows a normal system.  
FRR150  
ꢖꢉꢉꢃ]ꢒꢇꢇꢅꢆꢃꢍꢄꢇꢎꢅꢆꢃꢎꢊꢃ]ꢉꢅꢄꢂꢑꢞ  
ꢁ  
F
F
AUTO FAN  
AUTO FAN  
79  
79  
SET POINT  
SET POINT  
SCHEDULE  
FRR159  
FRR155  
SCHEDULE  
<ꢓꢃꢇꢁꢂꢃꢐꢄꢁꢂꢑꢒꢉꢂꢃꢓꢒꢆꢄꢇꢎꢅꢆꢃꢎꢊꢃꢇꢒꢈꢆꢂꢑꢃꢘꢙꢃꢑꢒꢈꢎꢆꢜꢃꢍꢃꢐꢎꢛꢃꢛꢂꢈꢎꢅꢑ*ꢃꢇꢁꢂꢃ  
<ꢓꢃꢇꢁꢂꢃꢀꢎꢌꢂꢈꢃꢓꢒꢆꢄꢇꢎꢅꢆꢃꢎꢊꢃꢇꢒꢈꢆꢂꢑꢃꢘꢙꢃꢑꢒꢈꢎꢆꢜꢃꢇꢁꢂꢃꢘꢙꢃꢇꢎꢌꢂ*ꢃꢇꢁꢂꢃꢀꢎꢌꢂꢈꢃ icon  
illuminates. The control system continues to run.  
and Timer  
icons illuminates. The control system immediately runs the  
previous (non-skip) period schedule parameters.  
Scheduler OFF Scenarios  
Timer ON Scenarios  
F
F
AUTO FAN  
AUTO FAN  
79  
SET POINT  
79  
SCHEDULE  
SET POINT  
FRR160  
FRR156  
The display shows the unit in Schedule mode.  
The display shows a normal system.  
F
AUTO FAN  
79  
SET POINT  
FRR161  
FRR157  
<ꢓꢁꢂꢎꢌꢂꢈꢒꢆꢄꢇꢎꢅꢆꢒꢈꢆꢂꢑꢒꢈꢎꢆꢜꢁꢂꢓꢓꢎꢌꢂ*ꢁꢂꢃ  
ꢎꢉꢉꢒꢌꢎꢆꢍꢇꢂꢊꢞꢃꢀꢁꢂꢃꢄꢅꢆꢇꢈꢅꢉꢃꢊꢋꢊꢇꢂꢌꢃꢎꢌꢌꢂꢑꢎꢍꢇꢂꢉꢋꢃꢇꢒꢈꢆꢊꢃꢇꢁꢂꢃꢒꢆꢎꢇꢃꢘꢚꢞ  
icon  
<ꢓꢃꢇꢁꢂꢃꢐꢄꢁꢂꢑꢒꢉꢂꢃꢓꢒꢆꢄꢇꢎꢅꢆꢃꢎꢊꢃꢇꢒꢈꢆꢂꢑꢃꢘꢚꢚꢃꢑꢒꢈꢎꢆꢜꢃꢍꢆꢃꢍꢄꢇꢎ[ꢂꢃꢊꢇꢍꢇꢂꢃ^ꢆꢅꢇꢃꢅꢓꢓ`*ꢃꢇꢁꢂꢃ  
SCHEDULE  
Timer and  
icons turn off. The control stays in the current state.  
The display shows a normal system.  
F
AUTO FAN  
79  
SET POINT  
SCHEDULE  
FRR158  
The display shows a normal system.  
FRR162  
ꢀꢁꢂꢃꢑꢎꢊꢛꢉꢍꢋꢃꢊꢁꢅꢗꢊꢃꢇꢁꢂꢃꢒꢆꢎꢇꢃꢎꢆꢃꢐꢄꢁꢂꢑꢒꢉꢂꢃꢌꢅꢑꢂꢃꢑꢒꢈꢎꢆꢜꢃꢍꢆꢃꢎꢆꢕꢍꢄꢇꢎ[ꢂꢃ^ꢘꢚꢚ`ꢃ  
period.  
ꢂꢃ  
F
F
AUTO FAN  
AUTO FAN  
79  
79  
SET POINT  
SET POINT  
FRR163  
FRR167  
<ꢓꢃꢇꢁꢂꢃꢀꢎꢌꢂꢈꢃꢓꢒꢆꢄꢇꢎꢅꢆꢃꢎꢊꢃꢇꢒꢈꢆꢂꢑꢃꢘꢚꢚꢃꢑꢒꢈꢎꢆꢜꢃꢍꢆꢃꢎꢆꢕꢍꢄꢇꢎ[ꢂꢃ^ꢘꢚꢚ`ꢃꢛꢂꢈꢎꢅꢑ*ꢃꢇꢁꢂꢃ  
Timer icon turns off. The display shows a normal system.  
<ꢓꢃꢇꢁꢂꢃꢐꢄꢁꢂꢑꢒꢉꢂꢃꢓꢒꢆꢄꢇꢎꢅꢆꢃꢎꢊꢃꢇꢒꢈꢆꢂꢑꢃꢘꢚꢚꢃꢑꢒꢈꢎꢆꢜꢃꢍꢆꢃꢎꢆꢕꢍꢄꢇꢎ[ꢂꢃ^ꢘꢚꢚ`ꢃꢛꢂꢈꢎꢅꢑ*ꢃ  
SCHEDULE  
the Timer  
and  
icons turn off. The unit wakes up in the last  
known non-schedule state.  
F
AUTO FAN  
F
AUTO FAN  
79  
SET POINT  
79  
SET POINT  
SCHEDULE  
FRR168  
<ꢓꢃꢇꢁꢂꢃꢀꢎꢌꢂꢈꢃꢓꢒꢆꢄꢇꢎꢅꢆꢃꢎꢊꢃꢇꢒꢈꢆꢂꢑꢃꢘꢚꢚꢃꢑꢒꢈꢎꢆꢜꢃꢇꢁꢂꢃꢘꢙꢃꢇꢎꢌꢂꢞꢃꢀꢁꢂꢃꢀꢎꢌꢂꢈꢃ icon  
turns off. The control stays in the current state.  
FRR164  
<ꢓꢃꢇꢁꢂꢃꢐꢄꢁꢂꢑꢒꢉꢂꢃꢓꢒꢆꢄꢇꢎꢅꢆꢃꢎꢊꢃꢇꢒꢈꢆꢂꢑꢃꢘꢚꢚꢃꢑꢒꢈꢎꢆꢜꢃꢍꢃꢐꢎꢛꢃꢛꢂꢈꢎꢅꢑ*ꢃꢇꢁꢂꢃ and  
SCHEDULE  
icons turn off. The unit wakes up in the last known non-schedule  
state.  
F
AUTO FAN  
79  
F
SET POINT  
AUTO FAN  
79  
SET POINT  
FRR169  
The display shows a normal system.  
FRR165  
The display shows a normal system.  
Timer OFF Scenarios  
FRR166  
ꢀꢁꢂꢃꢑꢎꢊꢛꢉꢍꢋꢃꢊꢁꢅꢗꢊꢃꢇꢁꢂꢃꢒꢆꢎꢇꢃꢎꢆꢃꢀꢎꢌꢂꢈꢃꢌꢅꢑꢂꢃꢑꢒꢈꢎꢆꢜꢃꢍꢆꢃꢎꢆꢕꢍꢄꢇꢎ[ꢂꢃ^ꢘꢚꢚ`ꢃꢛꢂꢈꢎꢅꢑꢞ  
ꢄ  
FAN SPEED Button - Used to sequentially select new fan speed, plus  
Remote Control Operation  
FA N  
SPEED  
AUTO operation. When the  
button is pressed, the fan speed icon  
(triangle) changes to indicate the new speed level. Fan speed automatically  
varies depending on the set temperature on the control panel and the actual  
room temperature. For example if there is a big difference between your  
set temperature and the actual room temperature, the system fan speed  
increases to HIGH. It remains at this speed until the room temperature  
matches the set temperature.  
Remote Control - Refer to Figures 12 and 13 during operation description.  
Getting Started - Install two (2) AAA batteries in the battery compartment  
located on the back of the unit.  
Operation - The remote control should be within 25 feet of the air  
conditioner for operation. (Refer to Figure 11 for effectiveness). Press the  
power button to turn the remote on. The remote will automatically power  
off after 15 seconds if the buttons are not being pressed. The remote must  
be on to control the unit.  
SCHEDULE  
SCHEDULE Button – The  
button turns the schedule function  
on and off. Press the Schedule button once to turn on the Schedule  
(Residential, Commercial, Timer, or Customized) that has already been  
SCHEDULE  
selected on your unit. Pressing the  
the schedule function off.  
button a second time turns  
POWER Button - Turns remote and unit on and off.  
SYSTEM Button - Allows the user to sequentially select the  
UP and DOWN Arrows - Pressing either the  
(UP) or  
(DOWN)  
HEAT , and FAN ONLY  
following: AUTO - AUTO -, COOL  
,
button changes the desired room temperature. The factory preset lower  
and upper limits are 60°F (16°C) and 99°F (37°C). These buttons are also  
used to navigate between function options when using the User Menu or  
Maintenance Mode.  
operations. When the button is pressed, the display indicates which mode  
has been selected via a display message.Note that when the heating  
function is not available, the system will automatically skip the HEAT mode.  
CONTINUOUS  
FAN MODE Button - Selects between automatic ( AUTO FAN ) or  
AUTO FAN  
operation. In the  
mode, the fan only turns on and off when the  
Remote Effectiveness  
compressor operates or the heat function is enabled.  
Hand Held Remote - Has an operating range of up to 25 ft. The infrared  
remote control signal must have a clear path to transmit the command to  
the air conditioning unit. The remote signal has some ability to "bounce"  
off of walls and furniture similar to a television remote control. The diagram  
below shows the typical operating range of the control in a standard room  
with 8 ft high ceilings.  
AUTO FAN  
NOTE:  
is not available in the FAN ONLY Mode, the display  
CONTINUOUS  
CONTINUOUS  
indicates  
. In the  
mode, fan speed is  
button.  
FA N  
SPEED  
determined by your selection on the  
Figure 11  
TOP VIEW  
25ft  
25ft  
7.5ft  
4ft  
60°  
60°  
SIDE VIEW  
6ft  
30°  
45°  
60°  
45°  
45°  
8ft  
25ft  
60°  
30°  
30°  
45°  
30°  
16ft  
8ft  
25ft  
25ft  
25ft  
25ft  
25ft  
FRR080  
20  
Figure 12  
AUTO  
DISPLAY  
AUTO FAN  
CONTINUOUS  
AUTO  
C
F
SYSTEM  
FAN MODE  
POWER  
SYSTEM  
FAN MODE  
POWER  
TEMPERATURE  
UP  
TEMPERATURE  
DOWN  
FAN SPEED  
SCHEDULE  
SCHEDULE  
FAN SPEED  
FRR081  
Figure 13  
FAN ONLY  
ICON  
COOL  
ICON  
HEAT  
ICON  
SYSTEM  
MODE  
AUTO  
AUTO FAN  
FAN  
MODE  
CONTINUOUS  
AUTO  
FAN  
SPEED  
C F  
°F / °C  
ICONs  
SCHEDULE  
ICON  
FRR082  
21  
Figure 14  
Airflow Selection and Adjustment  
Air flow direction adjustment  
left or right side of the discharge opening. Each of the banks of louvers  
can be directed left, right, up or down in order to achieve the most optimum  
move it in the direction that you would like the air to be directed. Please  
louvers than the other.  
Fresh air and exhaust control  
Your air conditioner has the ability to bring fresh air into the room or exhaust  
stale air out of the room. The control slide is found on the upper part of  
the unit (See Figure 14).  
TO BRING IN FRESH AIR – Move the lever to the Fresh Air  
position  
which allows outside air to enter the room. This is useful in fall and spring as  
a means of bringing in fresh outside air when using FAN ONLY . It can also  
be used in the summer with the compressor in the Cooling Mode if you wish.  
FRR008  
TO EXHAUST INDOOR AIR – Move the lever to the Exhaust  
position. This will allow stale air to be expelled to the outside of the dwelling.  
This is especially handy in the spring or fall when indoor air tends to get  
stale, or after a social gathering involving smokers, or to remove cooking  
odors.  
BEST PERFORMANCE – Move the lever to the Re-Circulate Position  
Remote Thermostat  
Remote Thermostat - An external thermostat may be added to the air  
conditioner to provide remote temperature sensing and control. For  
contact Friedrich Service at 1-800-541-6645.  
22  
The following instructions are for standard chassis model groups  
Installation Instructions  
sizes listed in Table 3.  
READ THIS FIRST! Electrical Requirements  
Table 3  
MODEL DESIGNATION  
CABINET SIZE (H x W x D)  
WARNING  
SMALL CHASSIS - SS, 15 15W " x 25 W " x 29" (405 mm x  
ES, YS  
MEDIUM CHASSIS - SM, 17 15W " x 25 W " x 29" (455 mm x  
EM, YM  
15  
16  
16  
660 mm x 737 mm)  
Electrical Shock Hazard  
Make sure your electrical receptacle has the  
same configuration as your air conditioner’s  
plug. If different, consult a Licensed Electrician.  
15  
16  
16  
660 mm x 737 mm)  
3
1
16  
2
LARGE CHASSIS - SL, 20 W " x 28" x 35 W " (513 mm x 711  
EL, YL  
mm x 851 mm)  
Do not use plug adapters.  
Do not use an extension cord.  
Do not remove ground prong.  
Always plug into a grounded 3 prong oulet.  
Failure to follow these instructions can result in  
death, fire, or electrical shock.  
WARNING  
MOVING PARTS HAZARDS  
* Do not operate unit out of sleeve  
or with front grille removed.  
* Do not place hands in blower or  
fan blade areas.  
IMPORTANT: Before you begin the actual installation of your air  
conditioner, check your local electrical codes and the information below.  
Your air conditioner must be connected to a power source with the same  
alternating current (A.C.) voltage and amperage as marked on the name  
plate located on the chassis. Only A.C. can be used. Direct Current (D.C.)  
cannot be used.  
Failure to do so can result in  
serious injury.  
CIRCUIT PROTECTION – Use on single outlet circuit only. An overloaded  
circuit will invariably cause malfunction or failure of an air conditioner,  
therefore, it is necessary that the electrical protection is adequate. Due  
to momentary high current demand when the air conditioner starts, use a  
"TIME DELAY" fuse or a HACR type circuit breaker. Consult your dealer  
or power company if in doubt.  
CAUTION  
Excessive Weight Hazard  
Use two or more people when  
installing your air conditioner.  
Refer to the electrical name plate located on the air conditioner chassis  
(See page 2) to determine the correct fuse or circuit breaker amperage  
for your model (See Table 1 on Page 6 for electrical receptacle types).  
Failure to do so can result in  
back or other injury.  
The power cord has a plug with a grounding prong and a matching  
receptacle is required.  
Recommended Tools  
1. Power Drill  
2. 5/32" Drill Bit  
4
3. Gloves  
4. Carpenters Level  
1
2
5/16  
1
/4  
5. 5/16" Wrench  
6. 1/4" Wrench  
5
7
6
8
5 / 1 6  
/ 4  
1
7. #2 Phillips Screw Driver  
8. Putty Knife or (wood stir stick)  
3
ITEMS NOT TO SCALE  
23  
INSTALLATION HARDWARE AND ACCESSORY DETAIL  
ITEM 2  
ITEM 3  
ITEM 1  
ITEM 5  
ITEM 6  
ITEM 4  
ITEM 7  
ITEM 8  
ITEM 9  
ITEM 12  
ITEM 13  
ITEM 11  
ITEM 10  
ITEMS NOT TO SCALE  
FRR009  
ITEM  
NO  
DESCRIPTION  
QTY.  
ITEM  
NO  
DESCRIPTION  
QTY.  
WINGBOARD MOUNTING PARTS  
WINGBOARD (MASONITE)  
MOUNTING PARTS  
8
9
10  
11  
1
4
4
4
"J" TYPE SPEED NUT  
4
14  
7
1
SCREW, SHEET METAL #12A x 2”  
CHASSIS SEAL GASKET (LIGHT FOAM)  
WINGBOARD CLIP (SPRING STEEL)  
SCREW, #8 x ½" PHILLIPS TRUSS HD.  
WINDOW SEALING  
12  
13  
WINDOW SEAL GASKET (DARK FOAM)  
CHASSIS SEAL GASKET (LIGHT FOAM)  
1
1
NOTE: Kühl + models do not come with window mounting  
components. When mounting a cooling and heating model  
a window installation kit must be purchased separately.  
SHELL MOUNTING PARTS  
SUPPORT BRACKET  
SCREW, 10-24 x 1" HEX HEAD  
10-24 FLAT WELD NUT  
SCREW, SHEET METAL #12 x 2"  
KWIKS – For all ES and YS models.  
KWIKM – For all EM and YM models.  
KWIKL – For all EL and YL models.  
1
2
3
4
2
4
4
7
WINGBOARD ANGLE MOUNTING  
WINGBOARD ANGLE, TOP  
WINGBOARD ANGLE, SIDE  
8
5
6
7
1
2
2
SCREW, SHEET METAL #8 x 3  
"
ꢅꢆ  
Figure 16  
Standard Window Installation  
NOTE: Hardware and accessories used during installation are shown  
on page 23. Each part will be referred as Item No.  
STEP 1.  
Remove the chassis Entrygard retainer by removing the far  
right screw (See Figure 15), save this screw to reattach the  
chassis retainer after installation (Step 12). Also, remove and  
discard the two retainer screws and washers located at the  
rear of the unit (See Figure 15).  
CAUTION  
Handle Use  
Use handle on both sides to  
pull unit from sleeve.  
Use Handle  
Locations  
(both sides)  
Do not push, pull or lift from  
center of support.  
STEP 2.  
STEP 3.  
Hold the cabinet stationary, then use the hand grips on both  
ends of the control unit support bracket to pull the chassis out  
of the cabinet (See Figure 16).  
CONTROL UNIT  
SUPPORT BRACKET  
FRR012  
Remove the large white foam blocks used to restrain the  
compressor during shipment (See Figure 17). Inspect base  
pan for dislodged white foam blocks and remove. Do not  
remove any other foam parts.  
STEP 4.  
Anchor the side angles (Item 6) by engaging the tabs of the  
lower sill plate (See Figure 18, Detail B-2) with the loops of the  
side angle. Engage the tabs of the top angle (Item 5) with the  
top loops of the side angle (See Figure 18, Detail B-1). Install  
two (2) screws (Item 7) to secure the top angle tabs and the  
side angle to the cabinet (See Figure 18, Detail B-1).  
Figure 15  
RETAINER SCREWS  
AND WASHERS  
ENTRYGARD  
RETAINER  
WIRE  
FAR RIGHT  
SCREW  
FRR011  
25  
NOTE: DO NOT LEVEL the cabinet from front to back. Make sure there  
is approximately 3/8” to 1/2” slope (1/8 to 1/4 bubble on level)  
toward the outside of the house.  
CAUTION  
Remove Shipping Blocks  
Prior to operating the unit remove  
the foam shipping blocks.  
Adjust the support brackets to provide an inside-to-outside slope for excess  
condensation drainage (Refer to Standard Window Installation, Figures 20  
through 24). Tighten all screws.  
Alternate support method A: If you have a wide window sill which prevents  
you from mounting the brackets as shown in Figure 23, try the following:  
Using the elongated holes and different hole locations in the cabinet,  
set the placement of the bracket to support the unit’s weight (Figure 23).  
Tighten all screws.  
Failure to do so may result in  
damage to the unit which is not  
covered by the manufacturer’s  
warranty!  
Alternate support method B: If the window ledge gap is narrow, try the  
STEP 5.  
STEP 6.  
Check the window sill and frame to be sure they are in good  
as shown in Figure 24. Bend the short piece so it will be vertical when  
installed. Adjust the placement as required. Tighten all screws.  
CABINET MOUNTING – Raise the lower window 1/4" more  
than the height of the cabinet. Carefully slide the cabinet  
through the opening until the lower sill plate channel rests  
behind the window sill and the top angle rests against the  
window (See Figure 19). Center the cabinet within the  
opening. Drill three (3) 5/32" diameter pilot holes into window  
sill using the holes in the cabinet sill plate as a guide. Install  
three (3) #12 x 2" long screws (Item 4) (See Figure 19).  
STEP 8.  
between the window side channels and cabinet. (Figure 25).  
Make sure you include the depth of the window channel.  
NOTICE  
STEP 7.  
OUTSIDE SUPPORT MOUNTING – Refer to Figures 20 and  
21. Assemble the support brackets (Item 1) to the bottom of  
the cabinet with four (4) 10-24 1” long screws (Item 2) and four  
For YOUR security and safety, YOU must  
provide a means of preventing the upper  
part of the window from opening.  
combination of the elongated holes of the bracket and different  
hole locations in the cabinet, to bring the bottomsupport bracket  
pads in contact with the wall. A 1" x 4" or 2" x 4" SPACER  
SHOULD BE USED BETWEEN THE WALL AND SUPPORT  
THE BRACKETS WHEN INSTALLED ON ALUMINUM OR  
VINYL SIDING. Drill 5/32" diameter pilot holes and secure  
the brackets to the wall with two (2) 12A x 2" long screws  
(Item 4).  
STEP 9.  
To assemble the wingboard panels, push on the "J" type speed  
nuts (Item 9) and spring steel clips (Item 10) (See Figures 26)  
on page 31. Secure each panel with two (2) screws (Item 11).  
Figure 17  
TOP VIEW OF UNIT  
REMOVE AND DISCARD  
SCREWS  
BACK  
LEFT SIDE  
RIGHT SIDE  
REMOVE AND DISCARD  
FOAM BLOCKS  
COMPRESSOR  
FAN MOTOR  
EVAPORATOR COIL  
REMOVE AND SAVE  
SCREW FOR  
RE-INSTALLATION  
FRONT  
FRR045  
26  
Figure 1  
#8 x 3/8” LONG SCREW  
(ITEM 7) 2 REQUIRED  
TOP ANGLE (ITEM 5)  
CABINET  
TAB  
DETAIL B-2  
SIDE ANGLE  
(ITEM 6)  
2 REQUIRED  
TAB  
LOOP  
SILL PLATE  
TAB  
DETAIL B-1  
FRR013  
Figure 1ꢁ  
TOP ANGLE  
(ITEM 5)  
CENTER  
CABINET  
IN WINDOW  
SIDE TO SIDE  
PULL WINDOW  
SASH DOWN  
BEHIND TOP  
ANGLE  
DRILL (3) 5/32” DIA.  
PILOT HOLES AND  
INSTALL (3) #12 x 2”  
LONG SCREWS  
(ITEM 4)  
SIDE ANGLE  
(ITEM 6)  
WINDOW SILL  
LOCATE SILL PLATE GUIDE CHANNEL  
JUST BACK OF WINDOW SILL  
FRR014  
ꢅꢁ  
Figure ꢂꢃ  
3/8” SLOPE DOWN  
#10-24 x 1” HEX HD.  
SCREW (ITEM 2)  
SUPPORT BRACKET  
(ITEM 1)  
#12 x 2” SCREW  
(ITEM 4)  
SUPPORT  
BRACKET  
(ITEM 1)  
SPACER SHOULD BE USED BETWEEN  
WALL AND BRACKET WHEN INSTALLED  
ON ALUMINUM OR VINYL SIDING.  
10-24 x FLAT WELD  
NUT (ITEM 3)  
FRR015  
Figure 2ꢄ  
3/8” SLOPE DOWN  
CONDENSER  
AIR OUTLET  
CONDENSER  
AIR INLETS  
#10-24 SCREW  
#10-24 FLAT WELD NUT  
#12 x 2” SHEET METAL  
SCREW (ITEM 4)  
SPACER SHOULD BE USED BETWEEN  
WALL AND BRACKET WHEN INSTALLED  
ON ALUMINUM OR VINYL SIDING.  
FRR016  
ꢅꢂ  
Figure 2ꢂ  
3/8” SLOPE DOWN  
CONDENSER  
AIR INLETS  
#10-24 SCREW  
#10-24 FLAT WELD NUT  
#12 x 2” SHEET METAL  
SCREW (ITEM 4)  
STONE LEDGE  
SPACER  
FRR017  
Figure 2ꢅ  
3/8” SLOPE DOWN  
#10-24 SCREW  
STRAIGHTEN TAB TO LAY FLAT  
ALONG THE BOTTOM RAIL OF  
THE SHELL  
#10-24 FLAT WELD NUT  
SECURE THE LONGEST SIDE OF  
THE BRACKET TO THE SHELL  
ADJUST IN OR OUT TO REST  
ON THE LEDGE  
STONE LEDGE  
FRR018  
ꢅꢄ  
Figure 2ꢆ  
3/8” SLOPE DOWN  
#10-24 SCREW  
DIMENSION “A”  
CUT TO FIT DIMENSION “A”  
AND BEND DOWN TO FORM  
A VERTICAL LEG.  
CUT  
HERE  
#10-24 FLAT WELD NUT  
STONE LEDGE  
A
OUTSIDE WALL  
DISCARD  
SHADED AREA  
FRR019  
Figure 2ꢇ  
MEASURE DISTANCE “B” TO INSIDE OF THE  
CHANNEL ON EACH SIDE.  
CUT HERE AND DISCARD CENTER WASTE  
MATERIAL.  
B
WINGBOARD  
B
SUBTRACT 1/8” FROM DIMENSION “B” AND  
B
MEASURE FROM THE EDGE OF THE WING-  
BOARD (ITEM 8), MARK, SCORE AND CUT  
WITH APPROPRIATE CUTTING TOOL.  
B
FRR020  
STEP 10. INSTALL THE WINDOW SEALING GASKETS – Measure  
and cut the dark foam window seal gasket (Item 12) and  
install it between the upper glass panel and the top part of  
the window sash (Figure 28).  
CAUTION  
Cut/Sever  
Although great care has been  
taken to minimize sharp edges  
in the construction of your unit,  
use gloves or other hand  
protection when handling unit  
Failure to do so can result in minor  
CAUTION  
to moderate personal injury.  
Excessive Weight Hazard  
Use two or more people when  
installing your air conditioner.  
STEP 11. Carefully team lift the chassis and set it into the cabinet. Slide  
the chassis stopping approximately 3" from full insertion. Insert  
the chassis seal gasket (Item 13) one inch deep between the  
chassis and  
the cabinet (See Figure 30) as shown on page 33.  
Failure to do so can result in  
back or other injury.  
A paint stir stick or ruler might be helpful here. Begin inserting  
the gasket at either bottom corner and go up the side, across  
the top, and down the opposite side. Then push the chassis  
all the way into the cabinet.  
NOTE: If the chassis seal gasket is not installed or installed improperly,  
the operation of the unit will be negatively affected. Operational  
STEP 12. Reattach the entry guard chassis entry guard retainer wire with  
the same screw retained in Step 1 (See Figure 15).  
Figure 26  
SPRING STEEL  
CLIP (ITEM 10)  
2 REQUIRED  
“J” TYPE SPEED NUT  
(ITEM #9) 2 REQUIRED  
3"  
CUT  
WINGBOARD  
PANEL  
CUT EDGE  
ROTATED 90°  
3"  
SLIDE CLIP OVER CUT EDGE  
OF WINGBOARD PANEL  
CENTER THE HOLE IN THE  
SPEED NUT OVER THE SLOT  
IN THE WINGBOARD PANEL  
FRR021  
31  
Figure 27  
Figure 28  
TOP OF CABINET  
INSERT FOAM WINDOW  
SEAL GASKET (ITEM 12)  
PLACE WINGBOARD PANEL IN WINDOW JAM  
TO COMPRESS THE SPRINGS INSIDE THE  
RUNNERS, AND SWING THE WINGBOARD  
PANELS INTO PLACE AS INDICATED BY THE  
DASHED LINES.  
WINDOW JAM  
CLIP (ITEM 10)  
SECTION A-A  
B
A
A
SECURE THE SIDE WINGBOARD PANELS TO  
THE SIDE ANGLES WITH FOUR (4) #8 x 1/2” LONG  
SCREWS (ITEM 11), TWO ON EACH SIDE.  
SECTION B-B  
FRR022  
32  
OPTIONAL: The factory assembles the supply cord so that it exits the left  
side of the unit at the bottom. At the consumer’s discretion,  
the supply cord can be routed to exit the right side of the unit.  
Use Tool Provided  
Please use the provided tool to attach the decorative front to the chassis.  
To do this, route the supply cord to the right side. Pull the  
supply cord taunt through the loops (Refer to Cord Routing  
Change, Figure 31) and route the cord down.  
Figure 29  
To attach and prevent damage to the front grille align the  
cord notch over the cord and center the fresh air lever, then  
align and tighten the four (4) captive screws as indicated by  
the arrows in Figure 29. Before closing the front panel, be  
sure the filter is in place. Make sure curtains do not block  
the side air intakes.  
STEP 13.  
USE HAND TOOLS  
DO NOT OVER TIGHTEN  
B
STEP 14. Refer to the Control Panel Operation section for instructions.  
STEP 15. You are now ready to control the comfort level of the room.  
LOCATION OF GRILLE  
REMOVAL TOOL  
FRR053  
Figure 30  
POWER CORD  
CLIP  
NOTE: WHEN INSTALLING THE CHASSIS  
SEAL GASKET; BEGIN AT EITHER BOTTOM  
CORNER AND GO UP THE SIDE & ACROSS  
THE TOP & DOWN THE OPPOSITE SIDE.  
CHASSIS SEAL  
GASKET (ITEM 13)  
FRR024  
33  
STEP 16. Carefully pull out electrical control panel 1", but not all the way.  
Cord Routing Change  
Figure 33  
Unplug unit.  
WARNING  
1 INCH  
Electrical Shock Hazard  
Make sure your electrical receptacle has the  
same configuration as your air conditioner’s  
plug. If different, consult a Licensed Electrician.  
Do not use plug adapters.  
Do not use an extension cord.  
Do not remove ground prong.  
Always plug into a grounded 3 prong oulet.  
Failure to follow these instructions can result in  
death, fire, or electrical shock.  
FRR056  
For convenience and optimum appearance the directionthat the power cord  
exits the unit may be changed from left to right by following the procedure  
below. Select the exit location on the left or right based on proximity to  
the power outlet.  
STEP 17. Pull electrical cord strain relief downward until free and rotate  
90 degrees to the right.  
Figure 34  
Figure 31  
ELECTRICAL  
CONTROL PANEL  
90°  
ELECTRICAL CORD  
NOTE:  
STRAIN RELIEF  
FRR057  
DECORATIVE FRONT REMOVED USE TOOL PROVIDED.  
(SEE FIGURE 29 FOR LOCATION OF TOOL).  
STEP 18. Push electrical cord strain relief back upward into the electrical  
FRR054  
control panel.  
Remove 3 screws as shown from the electrical control panel. Save to  
reinstall later.  
Figure 35  
Figure 32  
ELECTRICAL CONTROL  
PANEL SCREWS (3)  
ENSURE THE ELECTRICAL CORD STRAIN RELIEF IS  
FLUSH WITH THE TOP OF ELECTRICAL CONTROL PANEL  
FRR058  
FRR055  
34  
STEP 19. Carefully push electrical control panel back into chassis.  
STEP 21. If running power cord to the right of the unit install the cord  
into the cord retainer clips along the bottom front of the unit.  
Figure 36  
Figure 38  
ELECTRICAL  
CONTROL PANEL  
CORD RETAINER  
CLIPS  
FRR059  
STEP 20. Reinstall the 3 screws removed earlier to secure electrical  
control panel.  
Figure 37  
POWER  
CORD  
FRONT  
GRILLE  
FRR061  
ELECTRICAL CONTROL PANEL SCREWS (3)  
(RETAINED FROM STEP 1)  
FRR060  
35  
Through-the-Wall Installation  
The following instructions apply to wood, masonry, brick, concrete or cinder  
block wall construction.  
STEP 1.  
STEP 2.  
Follow steps 1, 2, 3, and 4 of the "STANDARD WINDOW  
INSTALLATION" instructions beginning on page 25.  
CABINET PREPARATION – Remove the sill plate from the  
cabinet by removing two (4) nuts and screws (Figure 39).  
Note that the chassis retainer is secured by a right side nut  
and screw (Detail A, Figure 39). Bend the tabs of the sill plate  
down into its channel at both ends of the plate or cut them off  
(Detail B, Figure 39) Rotate the sill plate 180° (end-to-end,  
Detail B, Figure 39) and reinstall. Reverse the orientation of  
the nuts and screws, so that the head of the screws are on the  
underside of cabinet facing up and the nuts are on top (Detail  
C, Figure 39). Ensure that the chassis retainer is reinstalled  
as shown in the detail.  
A
B
Table 3  
FINISHED  
DIMENSION  
SMALL  
CHASSIS  
MEDIUM  
CHASSIS  
LARGE  
CHASSIS  
NOTICE  
A
B
16 3W16"  
26 3W16"  
18 3W16"  
26 3W16"  
20 3W8  
28 1W4  
"
"
The outside cabinet condenser air intake louvers  
MUST NOT BE BLOCKED by extra thick walls.  
size.  
STEP 3.  
WALL PREPARATION – The maximum wall thickness  
permissible without special construction is determined by  
the model size to be installed. Observe the maximum wall  
thickness shown in Figure 40. Walls exceeding the maximum  
thickness shown in the chart, should be altered as shown in  
Figure 40.  
STEP 4.  
STEP 5.  
CHECKING WIRING AND PLUMBING – Check for wiring and  
plumbing inside and outside of the wall to be sure none will be  
damaged when the cabinet framework is being constructed.  
OPENING CONSTRUCTION – Depending upon size of unit  
to be installed, lay out the hole dimensions per Table 3. Cut  
construction is typical frame or 2” x 4” studding with brick or  
stone veneers, locate the opening next to one of the studs.  
For masonry, concrete or cinder block walls, locate opening  
for your convenience (See Figures 41, 42, and 43).  
36  
Figure 39  
CABINET  
BEFORE  
AFTER  
CABINET  
SCREW  
(4 REQUIRED)  
NOTE: HOLES IN SILL  
PLATE MOVED TO  
BACK SIDE  
NUT  
(4 REQUIRED)  
SILL PLATE  
DETAIL A  
TURN SILL PLATE  
END TO END  
NUT  
(4 REQUIRED)  
DETAIL C  
DETAIL B  
SCREW  
(4 REQUIRED)  
NOTE: SCREW AND NUT  
ORIENTATION NOW REVERSED.  
BEND TABS DOWN  
FRR026  
Figure 40  
TOP VIEW  
CONDITIONED  
ROOM SIDE AIR  
MAXIMUM WALL THICKNESS  
CONDENSER AIR  
A
INTAKE LOUVERS  
2" MINIMUM  
BOTH SIDES  
TOP VIEW SHOWING  
BEVELED SIDES FOR  
AIR INTAKE.  
WALL BELOW UNIT MUST  
BE BEVELED ALSO.  
CONDENSER AIR  
INTAKE LOUVERS  
MODEL  
A
CONDENSER AIR  
OUTLET / REJECTED  
HEATED AIR  
SMALL CHASSIS  
7-3/8”  
MEDIUM CHASSIS  
LARGE CHASSIS  
7-3/8”  
NOTE: CONDENSER AIR INLETS AND OUTLETS  
MUST BE UNOBSTRUCTED TO AVOID THE  
RECIRCULATION OF REJECTED HEATED AIR.  
15-1/8”  
FRR027  
37  
Figure 42  
Figure 41  
CAULK ALL SIDES  
INSIDE AND OUTSIDE  
CAULK ALL SIDES  
INSIDE AND OUTSIDE  
CABINET  
CABINET  
SHIM TO FILL IN VOID AT THE  
TOP AND SIDES WITH WOOD  
AS REQUIRED.  
SHIM TO FILL IN VOID AT THE  
TOP AND SIDES WITH WOOD  
AS REQUIRED.  
ELECTRICAL RECEPTACLE  
(SEE FIG. 42 FOR LOCATION NOTE)  
ELECTRICAL RECEPTACLE  
(SEE FIG. 42 FOR LOCATION NOTE)  
FRR028  
FRR029  
Figure 43  
CAULK ALL SIDES  
INSIDE AND OUTSIDE  
CABINET  
MORTAR  
POINT “Y”  
From Point "X" Small/Medium  
Large  
N/A  
115V  
230V  
69”  
45”  
45”  
From Point "Y" Small/Medium  
Large  
N/A  
115V  
230V  
45”  
21”  
20”  
ELECTRICAL  
RECEPTACLE  
POINT “X”  
FRR030  
38  
STEP 6.  
STEP 7.  
Slide the cabinet into the hole far enough to allow the  
guide-channel of the sill plate to contact the inside wall surface  
(Figure 21).  
NOTE: DO NOT LEVEL the cabinet from front to back. Make sure there  
is approximately 3/8” to 1/2” slope (1/8 to 1/4 bubble on the level)  
toward the outside of the house.  
Drill three (3) 5/32” diameter pilot holes (use the sill-plate holes  
as a guide) into the frame and install three (3) #12 x 2" long  
screws (Item 4) (Figure 21).  
STEP 8.  
Drill two (2) 5/32" diameter pilot holes in each cabinet side  
at the locations shown (Figure 21) and install four (4) #12 x  
2" screws (Item 4). Provided that Step 5 (hole construction)  
provides a sturdy mount with solid vertical studs, support  
brackets may not be required. The installation must support  
the weight of the unit plus an additional weight of 400 pounds  
on the rear of the cabinet. If support brackets (Item 1) are  
available, they can be installed as shown in Figure 21.  
NOTE: Alternate fasteners are required when securing the sill plate or  
support brackets to material other than wood (cinder block, brick,  
masonry or concrete). These items can be purchased at your  
local hardware store.  
STEP 9.  
Complete the installation by following steps 12 through 15  
of “STANDARD WINDOW INSTALLATION” instructions,  
page 25.  
EXPANSION ANCHOR BOLT  
MOLLY OR TOGGLE BOLT  
Figure 44  
CAULK ALL SIDES WEATHER TIGHT  
INSIDE AND OUTSIDE  
TRIM MOULDING  
3/8" SLOPE DOWN  
3"  
4"  
NOTE: SUPPORT BRACKET MAY BE  
OMITTED FROM THROUGH-THE-WALL  
INSTALLATIONS IF THE CABINET IS  
SECURED AS FOLLOWS. DRILL TWO  
HOLES IN EACH SIDE AND INSTALL 4  
FASTENERS (2 EACH SIDE). USE #12 x 2"  
SCREWS, (ITEM 4).  
SCREW #12 x 2"  
LONG (USE 3)  
(ITEM 4)  
TOGGLE BOLTS OR EXPANSION BOLTS  
MAY BE REQUIRED.  
SILL PLATE GUIDE CHANNEL  
INSIDE WALL SURFACE  
CABINET  
SUPPORT BRACKETS  
SCREW #12 x 2" LONG  
DRILL 5/32" DIA. PILOT HOLES.  
FRR031  
39  
Final Inspection & Start-up Checklist  
Inspect and ensure that all components and accessories have been  
installed properly and that they have not been damaged during the  
installation progress.  
Heat pumps operate differently  
If your unit is a "Y", or heat pump model, there are some things that you  
will want to be aware of. Some functions of a heat pump differ from your  
unit when it is used for heating:  
1. It is normal for ice to form on the outdoor coil of the heat pump.  
Moisture in the outside air, passing over the coil when very cold,  
will form ice.  
Check the condensate water drain(s) to ensure that they are adequate  
for the removal of condensate water, and that they meet the approval  
of the end user.  
Ensure that all installation instructions concerning clearances around  
2. If the outdoor temperature drops below 37° F (3° C), your heat  
pump will automatically turn on the electric resistance heat. When  
the temperature rises to 40° F (4° C), the compressor will resume  
the heat pump operation. If your unit is a 115 volt model (YS10),  
it is designed for use in warmer climates and does not have an  
electrical heat feature, and will not provide adequate heat below  
37° F (2.8° C).  
indoor coil, and outdoor coil are free from any obstructions.  
Ensure that the circuit breaker(s) or fuse(s) and supply circuit wire  
size have been sized correctly. If the unit was supplied with a power  
supply cord, insure that it is stored properly.  
Ensure that the entire installation is in compliance with all applicable  
national and local codes and ordinances having jurisdiction.  
Secure components and accessories, such as a decorative front  
cover.  
Control Panel Battery Change Procedure  
Remove the grille, by loosening four (4) captive screws (See Figure 45). In  
the upper left corner, remove one (1) screw on the battery retaining door  
(See Figure 46). Remove and replace the battery (CR2450). Reinstall  
the battery retaining door. Align the grille guide pins then tighten the four  
Start the unit and check for proper operation of all components in  
each mode of operation.  
Instruct the owner or operator of the units operation, and the  
manufacturer's Routine Maintenance.  
Clean or replace it as necessary.  
NOTE: A log for recording the dates of maintenance and/or service is  
recommended.  
Figure 45  
Present the owner or operator of the equipment with the Installation  
& Operation Manual, all accessory installation instructions, and the  
name, address and telephone number of the Authorized Friedrich  
Warranty Service Company in the area for future reference if  
necessary.  
This is a warm weather appliance  
USE HAND TOOLS  
Your air conditioner is designed to cool in warm weather when the outside  
temperature is above 60° F (15.6° C) and below 115° F (46.1° C), so it won't  
cool a room if it is already cool outside. If you want to cool a room in the  
spring or fall, select the FAN ONLY mode and set the Fresh Air/Exhaust  
air control to Fresh Air. This will bring in a supply of cooler outside air.  
DO NOT OVER TIGHTEN  
Condensation is normal  
Air conditioners actually pump the heat and humidity from your room to the  
outside. Humidity becomes water, and your air conditioner will use most  
of the water to keep the outside coil cool. If there is excessive humidity,  
there may be excess water that will drip outside. This is normal operation.  
1. USE HAND TOOLS WHEN INSTALLING AND  
REMOVING FRONT PANEL.  
DO NOT OVERTIGHTEN SCREWS.  
Frosting  
2. DISCONNECT POWER AND FOLLOW ALL  
LABELED WARNINGS WHEN FRONT PANEL  
IS REMOVED.  
FRR010  
ONLY and the frost will disappear. Setting the thermostat a little warmer  
will probably prevent the frosting from recurring.  
Figure 46  
Noises  
All air conditioners make some noise. Friedrich units are designed to  
operate as quietly as possible. An air conditioner mounted in a wall is  
quieter than one mounted in a window. It is important to ensure that the  
chassis seal gasket (Item 13) is properly installed (refer to installation  
instructions).  
40  
Routine Maintenance  
monthly, and more frequently if conditions warrant. The unit must be turned  
Service and Assistance  
Before calling for service, please check the “Troubleshooting Tips” section  
42  
43  
avoid unnecessary service calls, and save you the cost of a service call  
if the problem is not due to the product itself. If you have checked the  
“Basic Troubleshooting” section and still need help, it is available as follows:  
To Remove, Wash and Replace Filter  
If you require further assistance  
You can call the Customer Support Call Center at 1-800-541-6645.  
Coils & Chassis  
Before calling, please make sure that you have the complete model and  
serial number, and date of purchase of your equipment available. By  
providing us with this information, we will be better able to assist you.  
NOTE: Do not use a caustic cleaning agent on coils or base pan..  
Use a biodegradable cleaning agent and degreaser. The use  
of harsh cleaning materials may lead to deterioration of the  
Our specialists are able to assist you with:  
The indoor coil and outdoor coils and base pan should be inspected  
periodically (annually or semi-annually) and cleaned of all debris (lint, dirt,  
leaves, paper, etc.) as necessary. Under extreme conditions, more frequent  
cleaning may be required. Clean the coils and base pan with a soft brush  
and compressed air or vacuum. A pressure washer may also be used,  
Referrals to dealers, and distributors.  
Use and Care Information.  
Recommended maintenance procedures.  
Installation information.  
pack when pressure cleaning coils.  
Referrals to Authorized Service Providers and Parts depots.  
NOTE: It is extremely important to insure that none of the electrical  
and/or electronic parts of the unit get wet. Be sure to cover all  
electrical components to protect them from water or spray.  
Available Accessories  
DC-2 Drain Kit – Part No. 01900235  
In some installations, excess condensate water caused by extremely humid  
conditions, may result in an undesirable water drip such as on a patio or  
over an entryway. MODEL DC-2 DRAIN KIT (Part No. 01900-235) can be  
installed to drain excess condensation to an alternate location.  
Decorative Front  
Use a damp (not wet) cloth when cleaning the control area to prevent  
water from entering the unit, and possibly damaging the electronic control.  
The decorative front and the cabinet can be cleaned with warm water  
and a mild liquid detergent. Do NOT use solvents or hydrocarbon based  
cleaners such as acetone, naphtha, gasoline, benzene, etc.  
Carbon Filter Kits  
The kits vary depending on the chassis size (small,medium, large). Each  
The indoor coil can be vacuumed with a dusting attachment if it appears  
to be dirty. DO NOT BEND FINS. The outdoor coil can be gently  
sprayed with a hose if you can get to it. If not, you might call your dealer  
for a more thorough cleaning when needed.  
KWCFS  
KWCFM  
KWCFL  
vacuuming with a dust attachment or by cleaning in the sink using warm  
reinstalling. Use caution the coil surface can be sharp.  
FriedrichLink™ Adapter Accessory:  
KWIFI - FriedrichLink™ Adapter Accessory for wireless control and  
additional programming options  
Fan Motor & Compressor  
Decorative Color Front Panel Kits:  
The kits vary depending on the chassis size (small, medium, large.)  
The fan motor & compressor are permanently lubricated, and require no  
additional lubrication.  
KWBGE(S/M/L)A- S/M/L Decorative Front Cover in Classic Beige  
KWBLK(S/M/L)A - S/M/L Decorative Front Cover in Black Onyx  
KWBLU(S/M/L)A - S/M/L Decorative Front Cover in Cobalt Blue  
Wall Sleeve  
Inspect the inside of the wall sleeve and drain system periodically (annually  
or semi-annually) and clean as required. Under extreme conditions, more  
frequent cleaning may be necessary. Clean both of these areas with an  
antibacterial and antifungal cleaner. Rinse both items thoroughly with  
water and ensure that the drain outlets are operating correctly. Check the  
sealant around the sleeve and reseal areas as needed.  
KWPNK(S/M/L)A  
KWRED(S/M/L)A  
KWWHT(S/M/L)A  
- S/M/L Decorative Front Cover in Pink Diamond  
- S/M/L Decorative Front Cover in Deep Red  
- S/M/L Decorative Front Cover in Designer White  
Window Installation Kits (Standard in Kühl Models withoutHeat)  
KWIKS – For all ES and YS models.  
KWIKM – For all EM and YM models.  
KWIKL – For all EL and YL models.  
41  
Troubleshooting Tips  
@ꢘ>}Zꢖ<ꢙꢀ  
@ꢖXꢐ?  
ꢐꢘZXꢀ<ꢘꢙ  
Turn the unit to the on position and raise or lower  
temperature setting (as appropriate) to call for  
operation.  
Plug into a properly grounded 3 prong receptacle.  
ꢐꢂꢂꢃO?ꢉꢂꢄꢇꢈꢎꢄꢍꢉꢃ#ꢍꢇꢎꢆꢜꢃꢀꢍ]ꢉꢂꢊPꢃꢅꢆꢃꢛꢜꢞꢃ‹ꢃꢓꢅꢈꢃꢇꢁꢂꢃ  
proper receptacle type for your unit.  
The unit is turned to the off position,  
ꢅꢈꢃꢇꢁꢂꢃꢇꢁꢂꢈꢌꢅꢊꢇꢍꢇꢃꢎꢊꢃꢊꢍꢇꢎꢊ[ꢂꢑꢞ  
ꢀꢁꢂꢃZ@V<ꢃꢛꢅꢗꢂꢈꢃꢄꢅꢈꢑꢃꢎꢊꢃꢒꢆꢛꢉꢒꢜꢜꢂꢑꢞ  
ꢀꢁꢂꢃZ@V<ꢃꢛꢅꢗꢂꢈꢃꢄꢅꢈꢑꢃꢁꢍꢊꢃꢇꢈꢎꢛꢛꢂꢑꢃ  
^#ꢂꢊꢂꢇꢃ]ꢒꢇꢇꢅꢆꢃꢁꢍꢊꢃꢛꢅꢛꢛꢂꢑꢃꢅꢒꢇ`ꢞ  
The circuit breaker has tripped or  
the supply circuit fuse has blown.  
}ꢈꢂꢊꢊꢃꢍꢆꢑꢃꢈꢂꢉꢂꢍꢊꢂꢃ#?ꢐ?ꢀꢃ^ꢉꢎꢊꢇꢂꢆꢃꢓꢅꢈꢃꢄꢉꢎꢄŒꢃ#ꢂꢊꢂꢇꢃ  
button latches and remains in) to resume operation.  
#ꢂꢊꢂꢇꢃꢇꢁꢂꢃꢄꢎꢈꢄꢒꢎꢇꢃ]ꢈꢂꢍꢂꢈ*ꢃꢅꢈꢃꢈꢂꢛꢉꢍꢄꢂꢃꢇꢁꢂꢃꢓꢒꢊꢂꢃꢍꢊꢃ  
applicable. If the problem continues, contact a  
licensed electrician.  
Unit does not operate.  
There has been a local power  
failure.  
ꢘꢇꢁꢂꢈꢃꢍꢛꢛꢉꢎꢍꢆꢄꢂꢊꢃꢍꢈꢂꢃ]ꢂꢎꢆꢜꢃꢒꢊꢂꢑꢃꢅꢆꢃ  
the same circuit.  
The unit will resume normal operation once power  
has been restored.  
The unit requires a dedicated outlet circuit, not  
shared with other appliances.  
Vꢅꢃꢙꢘꢀꢃꢒꢊꢂꢃꢍꢆꢃꢂ\ꢇꢂꢆꢊꢎꢅꢆꢃꢄꢅꢈꢑꢃꢗꢎꢇꢁꢃꢇꢁꢎꢊꢃꢅꢈꢃꢍꢆꢋꢃ  
other air conditioner.  
#ꢂꢛꢉꢍꢄꢂꢃꢗꢎꢇꢁꢃꢍꢃꢄꢎꢈꢄꢒꢎꢇꢃ]ꢈꢂꢍꢂꢈꢃꢅꢈꢃꢇꢎꢌꢂꢕꢑꢂꢉꢍꢋꢃꢓꢒꢊꢂꢃ  
ꢅꢓꢃꢇꢁꢂꢃꢛꢈꢅꢛꢂꢈꢃꢈꢍꢇꢎꢆꢜꢞꢃꢐꢂꢂꢃO?ꢉꢂꢄꢇꢈꢎꢄꢍꢉꢃ#ꢍꢇꢎꢆꢜꢃꢀꢍ]ꢉꢂꢊPꢃ  
ꢅꢆꢃꢛꢜꢞꢃ‹ꢃꢓꢅꢈꢃꢇꢁꢂꢃꢛꢈꢅꢛꢂꢈꢃꢄꢎꢈꢄꢒꢎꢇꢃ]ꢈꢂꢍꢂꢈꢏꢓꢒꢊꢂꢃꢈꢍꢇꢎꢆꢜꢃ  
for your unit. If the problem continues, contact a  
licensed electrician.  
ꢖꢆꢃꢂ\ꢇꢂꢆꢊꢎꢅꢆꢃꢄꢅꢈꢑꢃꢎꢊꢃ]ꢂꢎꢆꢜꢃꢒꢊꢂꢑꢞ  
Xꢆꢎꢇꢃꢀꢈꢎꢛꢊꢃ@ꢎꢈꢄꢒꢎꢇꢃꢈꢂꢍꢂꢈꢃꢅꢈꢃꢉꢅꢗꢊꢃꢚꢒꢊꢂꢊꢞ  
The circuit breaker or time-delay  
fuse is not of the proper rating.  
ꢀꢁꢂꢃZ@V<ꢃꢛꢅꢗꢂꢈꢃꢄꢅꢈꢑꢃꢄꢍꢆꢃꢇꢈꢎꢛꢃ^#ꢂꢊꢂꢇꢃ }ꢈꢂꢊꢊꢃꢍꢆꢑꢃꢈꢂꢉꢂꢍꢊꢂꢃ#?ꢐ?ꢀꢃ^ꢉꢎꢊꢇꢂꢆꢃꢓꢅꢈꢃꢄꢉꢎꢄŒꢃ#ꢂꢊꢂꢇꢃ  
button pops out) due to disturbances  
on your power supply line.  
button latches and remains in) to resume normal  
operation.  
Electrical overload, overheating, or  
ꢄꢅꢈꢑꢃꢛꢎꢆꢄꢁꢎꢆꢜꢃꢄꢍꢆꢃꢇꢈꢎꢛꢃ^#ꢂꢊꢂꢇꢃ]ꢒꢇꢇꢅꢆꢃ  
ꢛꢅꢛꢊꢃꢅꢒꢇ`ꢃꢇꢁꢂꢃZ@V<ꢃꢛꢅꢗꢂꢈꢃꢄꢅꢈꢑꢞ  
ꢘꢆꢄꢂꢃꢇꢁꢂꢃꢛꢈꢅ]ꢉꢂꢌꢃꢁꢍꢊꢃ]ꢂꢂꢆꢃꢑꢂꢇꢂꢈꢌꢎꢆꢂꢑꢃꢍꢆꢑꢃ  
ꢄꢅꢈꢈꢂꢄꢇꢂꢑ*ꢃꢛꢈꢂꢊꢊꢃꢍꢆꢑꢃꢈꢂꢉꢂꢍꢊꢂꢃ#?ꢐ?ꢀꢃ^ꢉꢎꢊꢇꢂꢆꢃꢓꢅꢈꢃ  
ꢄꢉꢎꢄŒꢃ#ꢂꢊꢂꢇꢃ]ꢒꢇꢇꢅꢆꢃꢉꢍꢇꢄꢁꢂꢊꢃꢍꢆꢑꢃꢈꢂꢌꢍꢎꢆꢊꢃꢎꢆ`ꢃꢇꢅꢃ  
resume normal operation.  
Z@V<ꢃ}ꢅꢗꢂꢈꢃ@ꢅꢈꢑꢃꢀꢈꢎꢛꢊꢃ^#ꢂꢊꢂꢇꢃꢒꢇꢇꢅꢆꢃ}ꢅꢛꢊꢃꢘꢒꢇ`ꢞ  
ꢙꢘꢀ?ꢔꢃꢃꢃꢖꢃꢑꢍꢌꢍꢜꢂꢑꢃꢛꢅꢗꢂꢈꢃꢊꢒꢛꢛꢉꢋꢃꢄꢅꢈꢑꢃꢌꢒꢊꢇꢃ]ꢂꢃꢈꢂꢛꢉꢍꢄꢂꢑꢃꢗꢎꢇꢁꢃꢍꢃꢆꢂꢗꢃꢛꢅꢗꢂꢈꢃꢊꢒꢛꢛꢉꢋꢃꢄꢅꢈꢑꢃꢅ]ꢇꢍꢎꢆꢂꢑꢃ  
from the product manufacturer and must not be repaired.  
ꢀꢁꢂꢃꢈꢂꢇꢒꢈꢆꢏꢑꢎꢊꢄꢁꢍꢈꢜꢂꢃꢍꢎꢈꢃꢜꢈꢎꢉꢉꢂꢃꢎꢊꢃ  
blocked.  
Windows or doors to the outside are  
open.  
The temperature is not set at a cool  
ꢂꢆꢅꢒꢜꢁꢏꢗꢍꢈꢌꢃꢂꢆꢅꢒꢜꢁꢃꢊꢂꢇꢇꢎꢆꢜꢞ  
ꢀꢁꢂꢃ[ꢉꢇꢂꢈꢃꢎꢊꢃꢑꢎꢈꢇꢋꢃꢅꢈꢃꢅ]ꢊꢇꢈꢒꢄꢇꢂꢑꢞ  
?ꢆꢊꢒꢈꢂꢃꢇꢁꢍꢇꢃꢇꢁꢂꢃꢈꢂꢇꢒꢈꢆꢃꢍꢆꢑꢏꢅꢈꢃꢑꢎꢊꢄꢁꢍꢈꢜꢂꢃꢍꢎꢈꢃꢛꢍꢇꢁꢊꢃ  
are not blocked by curtains, blinds, furniture, etc.  
Ensure that all windows and doors are closed.  
ꢖꢑ~ꢒꢊꢇꢃꢇꢁꢂꢃꢀꢂꢌꢛꢂꢈꢍꢇꢒꢈꢂꢃꢄꢅꢆꢇꢈꢅꢉꢃꢇꢅꢃꢍꢃꢄꢅꢅꢉꢂꢈꢃꢅꢈꢃ  
warmer setting as necessary.  
@ꢉꢂꢍꢆꢃꢇꢁꢂꢃ[ꢉꢇꢂꢈ*ꢃ^ꢐꢂꢂꢃ#ꢅꢒꢇꢎꢆꢂꢃ>ꢍꢎꢆꢇꢂꢆꢍꢆꢄꢂ`*ꢃꢅꢈꢃ  
remove obstruction.  
@ꢉꢂꢍꢆꢃꢇꢁꢂꢃꢄꢅꢎꢉꢊ*ꢃ^ꢐꢂꢂꢃ#ꢅꢒꢇꢎꢆꢂꢃ>ꢍꢎꢆꢇꢂꢆꢍꢆꢄꢂ`*ꢃꢅꢈꢃ  
remove obstruction.  
ꢂꢃꢊꢒꢈꢂꢃꢇꢅꢃꢒꢊꢂꢃꢂ\ꢁꢍꢒꢊꢇꢃ[ꢂꢆꢇꢃꢓꢍꢆꢊꢃꢗꢁꢎꢉꢂꢃꢄꢅꢅꢎꢆꢜꢃ  
or bathing and, if possible, try not to use heat  
producing appliances during the hottest part of the  
day.  
XꢆꢎꢇꢃVꢅꢂꢊꢃꢙꢅꢇꢃ@ꢅꢅꢉꢏJꢂꢍꢇꢃ#ꢅꢅꢌꢃꢐꢒꢓ[ꢄꢎꢂꢆꢇꢉꢋ*ꢃꢘꢈꢃ  
@ꢋꢄꢉꢂꢊꢃꢘꢆꢃꢖꢆꢑꢃꢘꢓꢓꢃꢀꢅꢅꢃꢚꢈꢂ‘ꢒꢂꢆꢇꢉꢋꢞ  
The indoor coil or outdoor coil is  
dirty or obstructed.  
ꢀꢁꢂꢈꢂꢃꢎꢊꢃꢂ\ꢄꢂꢊꢊꢎ[ꢂꢃꢁꢂꢍꢇꢃꢅꢈꢃꢌꢅꢎꢊꢇꢒꢈꢂꢃ  
(cooking, showers, etc.) in the room.  
The temperature of the room you  
ꢍꢈꢂꢃꢇꢈꢋꢎꢆꢜꢃꢇꢅꢃꢄꢅꢅꢉꢃꢎꢊꢃꢂ\ꢇꢈꢂꢌꢂꢉꢋꢃꢁꢅꢇꢞ  
ꢖꢉꢉꢅꢗꢃꢍꢑꢑꢎꢇꢎꢅꢆꢍꢉꢃꢇꢎꢌꢂꢃꢓꢅꢈꢃꢇꢁꢂꢃꢍꢎꢈꢃꢄꢅꢆꢑꢎꢇꢎꢅꢆꢂꢈꢃꢇꢅꢃꢄꢅꢅꢉꢃ  
off a very hot room.  
ꢆꢅ  
@ꢘ>}Zꢖ<ꢙꢀ  
@ꢖXꢐ?  
ꢐꢘZXꢀ<ꢘꢙ  
The outside temperature is below  
‹_ꢟꢚꢃ^$‹ꢟꢃ@`ꢞ  
Vꢅꢃꢆꢅꢇꢃꢇꢈꢋꢃꢇꢅꢃꢅꢛꢂꢈꢍꢇꢂꢃꢋꢅꢒꢈꢃꢍꢎꢈꢃꢄꢅꢆꢑꢎꢇꢎꢅꢆꢂꢈꢃꢎꢆꢃꢇꢁꢂꢃ  
cooling mode when the outside temperature is  
]ꢂꢉꢅꢗꢃ‹_ꢟꢚꢃ^$‹ꢟꢃ@`ꢞꢃꢃꢀꢁꢂꢃꢒꢆꢎꢇꢃꢗꢎꢉꢉꢃꢆꢅꢇꢃꢄꢅꢅꢉꢃꢛꢈꢅꢛꢂꢈꢉꢋ*ꢃ  
and the unit may be damaged.  
The digital control is set to fan  
cycling mode.  
Since the fan does not circulate the room air  
continuously at this setting, the room air does not  
ꢌꢎ\ꢃꢍꢊꢃꢗꢂꢉꢉꢃꢍꢆꢑꢃꢁꢅꢇꢃ^ꢅꢈꢃꢄꢅꢉꢑ`ꢃꢊꢛꢅꢇꢊꢃꢌꢍꢋꢃꢈꢂꢊꢒꢉꢇꢞꢃꢃ  
Using the continuous fan setting is recommended  
to obtain optimum comfort levels.  
ꢃ@ꢁꢂꢄꢃꢇꢁꢂꢃꢄꢅꢅꢉꢎꢆꢜꢃꢄꢍꢛꢍꢄꢎꢇꢋꢃꢅꢓꢃꢋꢅꢒꢈꢃꢒꢆꢎꢇꢃꢇꢅꢃꢂꢆꢊꢒꢈꢂꢃꢎꢇꢃ  
ꢎꢊꢃꢛꢈꢅꢛꢂꢈꢉꢋꢃꢊꢎ”ꢂꢑꢃꢓꢅꢈꢃꢇꢁꢂꢃꢈꢅꢅꢌꢃꢎꢆꢃꢗꢁꢎꢄꢁꢃꢎꢇꢃꢎꢊꢃꢎꢆꢊꢇꢍꢉꢉꢂꢑꢞꢃ  
#ꢅꢅꢌꢃꢍꢎꢈꢃꢄꢅꢆꢑꢎꢇꢎꢅꢆꢂꢈꢊꢃꢍꢈꢂꢃꢆꢅꢇꢃꢑꢂꢊꢎꢜꢆꢂꢑꢃꢇꢅꢃꢄꢅꢅꢉꢃ  
multiple rooms.  
@ꢁꢂꢄꢃꢇꢁꢂꢃꢁꢂꢍꢇꢎꢆꢜꢃꢄꢍꢛꢍꢄꢎꢇꢋꢃꢅꢓꢃꢋꢅꢒꢈꢃꢒꢆꢎꢇꢞꢃꢃꢖꢎꢈꢃ  
ꢄꢅꢆꢑꢎꢇꢎꢅꢆꢂꢈꢊꢃꢍꢈꢂꢃꢊꢎ”ꢂꢑꢃꢇꢅꢃꢌꢂꢂꢇꢃꢇꢁꢂꢃꢄꢅꢅꢉꢎꢆꢜꢃꢉꢅꢍꢑ*ꢃ  
ꢍꢆꢑꢃꢁꢂꢍꢇꢂꢈꢃꢊꢎ”ꢂꢃꢎꢊꢃꢇꢁꢂꢆꢃꢊꢂꢉꢂꢄꢇꢂꢑꢃꢇꢅꢃꢌꢂꢂꢇꢃꢇꢁꢂꢃ  
ꢁꢂꢍꢇꢎꢆꢜꢃꢉꢅꢍꢑꢞꢃꢃ<ꢆꢃꢂ\ꢇꢈꢂꢌꢂꢃꢆꢅꢈꢇꢁꢂꢈꢆꢃꢄꢉꢎꢌꢍꢇꢂꢊ*ꢃꢈꢅꢅꢌꢃ  
air conditioners may not be able to be used as a  
primary source of heat.  
XꢆꢎꢇꢃVꢅꢂꢊꢃꢙꢅꢇꢃ@ꢅꢅꢉꢏJꢂꢍꢇꢃ#ꢅꢅꢌꢃꢐꢒꢓ[ꢄꢎꢂꢆꢇꢉꢋ*ꢃꢘꢈꢃ  
@ꢋꢄꢉꢂꢊꢃꢘꢆꢃꢖꢆꢑꢃꢘꢓꢓꢃꢀꢅꢅꢃꢚꢈꢂ‘ꢒꢂꢆꢇꢉꢋꢃ^ꢄꢅꢆꢇꢎꢆꢒꢂꢑ`ꢞ  
ꢀꢁꢂꢃꢍꢎꢈꢃꢄꢅꢆꢑꢎꢇꢎꢅꢆꢂꢈꢃꢁꢍꢊꢃꢎꢆꢊꢒꢓ[ꢄꢎꢂꢆꢇꢃ  
cooling capacity to match the heat  
gain of the room.  
ꢀꢁꢂꢃꢍꢎꢈꢃꢄꢅꢆꢑꢎꢇꢎꢅꢆꢂꢈꢃꢁꢍꢊꢃꢎꢆꢊꢒꢓ[ꢄꢎꢂꢆꢇꢃ  
heating capacity to match the heat  
loss of the room.  
ꢀꢁꢎꢊꢃꢌꢍꢋꢃ]ꢂꢃꢑꢒꢂꢃꢇꢅꢃꢍꢆꢃꢂ\ꢄꢂꢊꢊꢎ[ꢂꢃ  
heat load in the room.  
If there are heat producing appliances in use in the  
room, or if the room is heavily occupied, the unit will  
need to run longer to remove the additional heat.  
ꢂꢃꢊꢒꢈꢂꢃꢇꢅꢃꢒꢊꢂꢃꢂ\ꢁꢍꢒꢊꢇꢃ[ꢂꢆꢇꢃꢓꢍꢆꢊꢃꢗꢁꢎꢉꢂꢃꢄꢅꢅꢎꢆꢜꢃ  
or bathing and, if possible, try not to use heat  
producing appliances during the hottest part of the  
day.  
It may also be due to an improperly  
ꢊꢎ”ꢂꢑꢃꢒꢆꢎꢇꢞ  
This may be normal for higher  
ꢀꢁꢂꢃꢒꢊꢂꢃꢅꢓꢃꢁꢎꢜꢁꢂꢈꢃꢂꢓ[ꢄꢎꢂꢆꢄꢋꢃꢄꢅꢌꢛꢅꢆꢂꢆꢇꢊꢃꢎꢆꢃꢋꢅꢒꢈꢃ  
new air conditioner may result in the unit running  
longer than you feel it should. This may be more  
ꢍꢛꢛꢍꢈꢂꢆꢇ*ꢃꢎꢓꢃꢎꢇꢃꢈꢂꢛꢉꢍꢄꢂꢑꢃꢍꢆꢃꢅꢉꢑꢂꢈ*ꢃꢉꢂꢊꢊꢃꢂꢓ[ꢄꢎꢂꢆꢇ*ꢃ  
model. The actual energy usage, however, will be  
ꢊꢎꢜꢆꢎ[ꢄꢍꢆꢇꢉꢋꢃꢉꢂꢊꢊꢃꢗꢁꢂꢆꢃꢄꢅꢌꢛꢍꢈꢂꢑꢃꢇꢅꢃꢅꢉꢑꢂꢈꢃꢌꢅꢑꢂꢉꢊꢞ  
ꢀꢁꢂꢃꢂꢆꢂꢈꢜꢋꢃꢂꢓ[ꢄꢎꢂꢆꢄꢋꢃꢈꢍꢇꢎꢅꢃ^??#`ꢃꢍꢆꢑꢃꢄꢅꢅꢉꢎꢆꢜꢃ  
ꢄꢍꢛꢍꢄꢎꢇꢋꢃꢈꢍꢇꢎꢆꢜꢃ^ꢇꢒꢏꢁ`ꢃꢉꢎꢊꢇꢂꢑꢃꢅꢆꢃꢇꢁꢂꢃꢒꢆꢎꢇRꢊꢃꢈꢍꢇꢎꢆꢜꢃ  
ꢛꢉꢍꢇꢂꢃꢍꢈꢂꢃ]ꢅꢇꢁꢃꢍꢜꢂꢆꢄꢋꢃꢄꢂꢈꢇꢎ[ꢂꢑꢞ  
ꢂꢓ[ꢄꢎꢂꢆꢄꢋꢃ^??#`ꢃꢍꢎꢈꢃꢄꢅꢆꢑꢎꢇꢎꢅꢆꢂꢈꢊꢞ  
Xꢆꢎꢇꢃ#ꢒꢆꢊꢃꢀꢅꢅꢃ>ꢒꢄꢁꢞ  
‚ꢅꢒꢃꢌꢍꢋꢃꢆꢅꢇꢎꢄꢂꢃꢇꢁꢍꢇꢃꢇꢁꢂꢃꢑꢎꢊꢄꢁꢍꢈꢜꢂꢃ  
air temperature of your new air  
conditioner may not seem as cold  
as you may be accustomed to from  
older units. This does not, however,  
indicate a reduction in the cooling  
capacity of the unit.  
ꢆꢇ  
Addendum 1  
Schedule Table with Energy Saving Values  
Residenꢀal Schedule  
Wed  
600 Start Time  
Period  
1
Sun  
Start Time  
System Mode  
Fan Mode  
Fan Speed  
Mon  
600 Start Time  
Tues  
600 Start Time  
Thur  
600 Start Time  
Fri  
600 Start Time  
Sat  
600 Start Time  
600  
Cool  
Auto  
Low  
78  
70  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
78 Set Point Cool  
70 Set Point Heat  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
78 Set Point Cool  
70 Set Point Heat  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
78 Set Point Cool  
70 Set Point Heat  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
78 Set Point Cool  
70 Set Point Heat  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
78 Set Point Cool  
70 Set Point Heat  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
78 Set Point Cool  
70 Set Point Heat  
Set Point Cool  
Set Point Heat  
Start Time  
System Mode  
Fan Mode  
Fan Speed  
Set Point Cool  
Set Point Heat  
800 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
85 Set Point Cool  
62 Set Point Heat  
800 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
85 Set Point Cool  
62 Set Point Heat  
800 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
85 Set Point Cool  
62 Set Point Heat  
800 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
85 Set Point Cool  
62 Set Point Heat  
800 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
85 Set Point Cool  
62 Set Point Heat  
800 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
85 Set Point Cool  
62 Set Point Heat  
800  
Cool  
Auto  
Low  
85  
2
3
4
62  
Start Time  
System Mode  
Fan Mode  
Fan Speed  
Set Point Cool  
Set Point Heat  
1800 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
78 Set Point Cool  
70 Set Point Heat  
1800 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
78 Set Point Cool  
70 Set Point Heat  
1800 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
78 Set Point Cool  
70 Set Point Heat  
1800 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
78 Set Point Cool  
70 Set Point Heat  
1800 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
78 Set Point Cool  
70 Set Point Heat  
1800 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
78 Set Point Cool  
70 Set Point Heat  
1800  
Cool  
Auto  
Low  
78  
70  
Start Time  
System Mode  
Fan Mode  
Fan Speed  
Set Point Cool  
Set Point Heat  
2200 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
82 Set Point Cool  
62 Set Point Heat  
2200 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
82 Set Point Cool  
62 Set Point Heat  
2200 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
82 Set Point Cool  
62 Set Point Heat  
2200 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
82 Set Point Cool  
62 Set Point Heat  
2200 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
82 Set Point Cool  
62 Set Point Heat  
2200 Start Time  
Cool System Mode  
Auto Fan Mode  
Low Fan Speed  
82 Set Point Cool  
62 Set Point Heat  
2200  
Cool  
Auto  
Low  
82  
62  
Commercial Schedule  
Wed  
Period  
1
Sun  
Start Time  
System Mode  
Fan Mode  
Fan Speed  
Mon  
700 Start Time  
Tues  
700 Start Time  
Thur  
Fri  
700 Start Time  
Sat  
700 Start Time  
700 Start Time  
700 Start Time  
700  
Cool  
Auto  
Med  
84  
Cool System Mode  
Auto Fan Mode  
Med Fan Speed  
84 Set Point Cool  
62 Set Point Heat  
Cool System Mode  
Auto Fan Mode  
Med Fan Speed  
75 Set Point Cool  
70 Set Point Heat  
Cool System Mode  
Auto Fan Mode  
Med Fan Speed  
75 Set Point Cool  
70 Set Point Heat  
Cool System Mode  
Auto Fan Mode  
Med Fan Speed  
75 Set Point Cool  
70 Set Point Heat  
Cool System Mode  
Auto Fan Mode  
Med Fan Speed  
75 Set Point Cool  
70 Set Point Heat  
Cool System Mode  
Auto Fan Mode  
Med Fan Speed  
75 Set Point Cool  
70 Set Point Heat  
Set Point Cool  
Set Point Heat  
62  
Start Time  
System Mode  
Fan Mode  
Fan Speed  
Set Point Cool  
Set Point Heat  
1800 Start Time  
Cool System Mode  
Auto Fan Mode  
Med Fan Speed  
84 Set Point Cool  
62 Set Point Heat  
1800 Start Time  
Cool System Mode  
Auto Fan Mode  
Med Fan Speed  
84 Set Point Cool  
62 Set Point Heat  
1800 Start Time  
Cool System Mode  
Auto Fan Mode  
Med Fan Speed  
84 Set Point Cool  
62 Set Point Heat  
1800 Start Time  
Cool System Mode  
Auto Fan Mode  
Med Fan Speed  
84 Set Point Cool  
62 Set Point Heat  
1800 Start Time  
Cool System Mode  
Auto Fan Mode  
Med Fan Speed  
84 Set Point Cool  
62 Set Point Heat  
1800 Start Time  
Cool System Mode  
Auto Fan Mode  
Med Fan Speed  
84 Set Point Cool  
62 Set Point Heat  
1800  
Cool  
Auto  
Med  
84  
2
62  
ꢆꢆ  
Friedrich Air Conditioning Company  
10001 Reunion Place, Suite 500  
San Antonio, TX 78216  
1-800-541-6645  
ROOM AIR CONDITIONERS  
LIMITED WARRANTY  
FIRST YEAR  
ANY PART:<ꢆꢋꢍꢈꢇꢒꢛꢛꢉꢎꢂꢑ]#<?V#<@Jꢍꢎꢉꢊ]ꢂꢄꢍꢒꢊꢂꢂꢓꢂꢄꢇꢅꢈꢌꢍꢆꢊꢁꢎꢛꢍꢇꢂꢈꢎꢍꢉꢎꢇꢁꢎꢆꢇꢗꢂꢉ[ꢂꢅꢆꢇꢁꢊꢈꢅꢌꢍꢇꢂꢈꢎꢜꢎꢆꢍꢉꢃ  
ꢛꢒꢈꢄꢁꢍꢊꢂ*#<?V#<@Jꢎꢉꢉꢂꢛꢍꢎꢈꢁꢂꢈꢅꢑꢒꢄꢇꢁꢍꢈꢜꢂ*ꢈꢅ[ꢎꢑꢂꢑꢅꢅꢌꢎꢈꢅꢆꢑꢎꢇꢎꢅꢆꢂꢈꢂꢍꢊꢅꢆꢍ]ꢉꢋꢄꢄꢂꢊꢊꢎ]ꢉꢂꢅꢈꢂꢈ[ꢎꢄꢂꢞꢆꢋꢑꢑꢎꢇꢎꢅꢆꢍꢉꢍ]ꢅꢈꢃ  
ꢄꢅꢊꢇꢅꢈꢂꢌꢅ[ꢎꢆꢜꢆꢍꢄꢄꢂꢊꢊꢎ]ꢉꢂꢆꢎꢇꢊꢆꢑꢏꢅꢈꢁꢍꢈꢜꢂꢊꢅꢈꢎꢉꢂꢍꢜꢂꢂꢉꢍꢇꢂꢑꢈꢍ[ꢂꢉ]ꢂꢈ[ꢎꢄꢂꢜꢂꢆꢄꢋꢁꢍꢇ\ꢄꢂꢂꢑꢊ|ꢎꢉꢂꢊꢆꢂꢍꢋꢎꢉꢉ]ꢁꢂꢃ  
ꢈꢂꢊꢛꢅꢆꢊꢎ]ꢎꢉꢎꢇꢋꢁꢂꢗꢆꢂꢈꢞꢁꢎꢊꢂꢌꢂꢑꢋ\ꢛꢈꢂꢊꢊꢉꢋꢜꢈꢂꢂꢑ]ꢁꢂ\ꢄꢉꢒꢊꢎ[ꢂꢂꢌꢂꢑꢋꢎꢇꢁꢎꢆꢇꢗꢂꢉ[ꢂꢅꢆꢇꢁꢊꢈꢅꢌꢁꢂꢍꢇꢂꢇꢁꢂꢃꢅꢈꢎꢜꢎꢆꢍꢉꢃꢛꢒꢈꢄꢁꢍꢊꢂꢞ  
SECOND THROUGH FIFTH YEAR  
SEALED REFRIGERANT SYSTEM:ꢃ<ꢓꢃꢇꢁꢂꢃꢐꢂꢍꢉꢂꢑꢃ#ꢂꢓꢈꢎꢜꢂꢈꢍꢇꢎꢅꢆꢃꢐꢋꢊꢇꢂꢌꢃ^ꢑꢂ[ꢆꢂꢑꢃꢓꢅꢈꢃꢇꢁꢎꢊꢃꢛꢒꢈꢛꢅꢊꢂꢃꢍꢊꢃꢇꢁꢂꢃꢄꢅꢌꢛꢈꢂꢊꢊꢅꢈ*ꢃꢄꢅꢆꢑꢂꢆꢊꢂꢈꢃꢄꢅꢎꢉ*ꢃꢂ[ꢍꢛꢅꢈꢍꢇꢅꢈꢃꢄꢅꢎꢉ*ꢃꢈꢂ[ꢂꢈꢊ-  
ꢎꢆꢜꢃ[ꢍꢉ[ꢂ*ꢃꢄꢁꢂꢄꢃ[ꢍꢉ[ꢂ*ꢃꢄꢍꢛꢎꢉꢉꢍꢈꢋ*ꢃ[ꢉꢇꢂꢈꢃꢑꢈꢎꢂꢈ*ꢃꢍꢆꢑꢃꢍꢉꢉꢃꢎꢆꢇꢂꢈꢄꢅꢆꢆꢂꢄꢇꢎꢆꢜꢃꢇꢒ]ꢎꢆꢜ`ꢃꢊꢒꢛꢛꢉꢎꢂꢑꢃ]ꢋꢃꢚ#<?V#<@Jꢃꢎꢆꢃꢋꢅꢒꢈꢃ#ꢅꢅꢌꢃꢖꢎꢈꢃ@ꢅꢆꢑꢎꢇꢎꢅꢆꢂꢈꢃꢓꢍꢎꢉꢊꢃ]ꢂꢄꢍꢒꢊꢂꢃꢅꢓꢃꢍꢃꢑꢂꢓꢂꢄꢇꢃ  
ꢎꢆꢃꢗꢅꢈꢌꢍꢆꢊꢁꢎꢛꢃꢅꢈꢃꢌꢍꢇꢂꢈꢎꢍꢉꢃꢗꢎꢇꢁꢎꢆꢃꢊꢎ\ꢇꢋꢃꢌꢅꢆꢇꢁꢊꢃꢓꢈꢅꢌꢃꢑꢍꢇꢂꢃꢅꢓꢃꢛꢒꢈꢄꢁꢍꢊꢂ*ꢃꢚ#<?V#<@Jꢃꢗꢎꢉꢉꢃꢛꢍꢋꢃꢍꢃꢉꢍ]ꢅꢈꢃꢍꢉꢉꢅꢗꢍꢆꢄꢂꢃꢍꢆꢑꢃꢛꢍꢈꢇꢊꢃꢆꢂꢄꢂꢊꢊꢍꢈꢋꢃꢇꢅꢃꢈꢂꢛꢍꢎꢈꢃꢇꢁꢂꢃꢐꢂꢍꢉꢂꢑꢃ  
#ꢂꢓꢈꢎꢜꢂꢈꢍꢇꢎꢅꢆꢋꢊꢇꢂꢌŒ}#ꢘ–<V?V#<?V#<@Jꢎꢉꢉꢅꢇꢍꢋꢁꢂꢅꢊꢇꢎꢍꢜꢆꢅꢊꢎꢊꢁꢂꢈꢅ]ꢉꢂꢌ*ꢂꢌꢅ[ꢍꢉ*ꢈꢂꢎꢜꢁꢇꢁꢍꢈꢜꢂꢊ*ꢆꢑꢈꢍꢆꢊꢛꢅꢈꢇꢍꢇꢎꢅꢆꢁꢂꢎꢈꢃ  
ꢄꢅꢆꢑꢎꢇꢎꢅꢆꢂꢈꢃꢇꢅꢃꢍꢆꢑꢃꢓꢈꢅꢌꢃꢇꢁꢂꢃꢐꢂꢈ[ꢎꢄꢂꢃꢖꢜꢂꢆꢄꢋ*ꢃꢍꢆꢑꢃꢇꢁꢂꢃꢈꢂꢎꢆꢊꢇꢍꢉꢉꢍꢇꢎꢅꢆꢃꢄꢁꢍꢈꢜꢂꢊꢃꢍꢊꢊꢅꢄꢎꢍꢇꢂꢑꢃꢗꢎꢇꢁꢃꢈꢂꢛꢍꢎꢈꢃꢅꢓꢃꢇꢁꢂꢃꢐꢂꢍꢉꢂꢑꢃ#ꢂꢓꢈꢎꢜꢂꢈꢍꢇꢎꢅꢆꢃꢐꢋꢊꢇꢂꢌꢞꢃꢖꢉꢉꢃꢊꢒꢄꢁꢃꢄꢅꢊꢇꢃꢗꢎꢉꢉꢃ]ꢂꢃ  
ꢇꢁꢂꢃꢊꢅꢉꢂꢃꢈꢂꢊꢛꢅꢆꢊꢎ]ꢎꢉꢎꢇꢋꢃꢅꢓꢃꢇꢁꢂꢃꢅꢗꢆꢂꢈꢞꢃꢀꢁꢎꢊꢃꢈꢂꢌꢂꢑꢋꢃꢎꢊꢃꢂ\ꢛꢈꢂꢊꢊꢉꢋꢃꢍꢜꢈꢂꢂꢑꢃꢇꢅꢃ]ꢂꢃꢇꢁꢂꢃꢂ\ꢄꢉꢒꢊꢎ[ꢂꢃꢈꢂꢌꢂꢑꢋꢃꢗꢎꢇꢁꢎꢆꢃꢊꢎ\ꢇꢋꢃꢌꢅꢆꢇꢁꢊꢃꢓꢈꢅꢌꢃꢇꢁꢂꢃꢑꢍꢇꢂꢃꢅꢓꢃꢇꢁꢂꢃꢅꢈꢎꢜꢎꢆꢍꢉꢃꢛꢒꢈꢄꢁꢍꢊꢂꢞ  
APPLICABILITY AND LIMITATIONS: ꢀꢁꢎꢊꢃꢗꢍꢈꢈꢍꢆꢇꢋꢃꢎꢊꢃꢍꢛꢛꢉꢎꢄꢍ]ꢉꢂꢃꢅꢆꢉꢋꢃꢇꢅꢃꢒꢆꢎꢇꢊꢃꢈꢂꢇꢍꢎꢆꢂꢑꢃꢗꢎꢇꢁꢎꢆꢃꢇꢁꢂꢃꢚꢎꢓꢇꢋꢃꢐꢇꢍꢇꢂꢊꢃꢅꢓꢃꢇꢁꢂꢃXꢞꢐꢞꢖꢞ*ꢃVꢎꢊꢇꢈꢎꢄꢇꢃꢅꢓꢃ@ꢅꢉꢒꢌ]ꢎꢍ*ꢃꢍꢆꢑꢃ@ꢍꢆꢍꢑꢍꢞꢃ  
ꢀꢁꢎꢊꢃꢗꢍꢈꢈꢍꢆꢇꢋꢃꢎꢊꢃꢆꢅꢇꢃꢍꢛꢛꢉꢎꢄꢍ]ꢉꢂꢃꢇꢅꢔ  
1. ꢖꢎꢈꢃ[ꢉꢇꢂꢈꢊꢃꢅꢈꢃꢓꢒꢊꢂꢊꢞ  
2. Products on which the model and serial numbers have been removed.  
3. Products which have defects or damage which results from improper installation, wiring, electrical current characteristics, or maintenance; or caused by  
ꢍꢄꢄꢎꢑꢂꢆꢇ*ꢃꢌꢎꢊꢒꢊꢂꢃꢅꢈꢃꢍ]ꢒꢊꢂ*ꢃ[ꢈꢂ*ꢃ\ꢅꢅꢑ*ꢃꢍꢉꢇꢂꢈꢍꢇꢎꢅꢆꢊꢃꢍꢆꢑꢏꢅꢈꢃꢌꢎꢊꢍꢛꢛꢉꢎꢄꢍꢇꢎꢅꢆꢃꢅꢓꢃꢇꢁꢂꢃꢛꢈꢅꢑꢒꢄꢇꢃꢍꢆꢑꢏꢅꢈꢃꢒꢆꢎꢇꢊꢃꢎꢆꢊꢇꢍꢉꢉꢂꢑꢃꢎꢆꢃꢍꢃꢄꢅꢈꢈꢅꢊꢎ[ꢂꢃꢍꢇꢌꢅꢊꢛꢁꢂꢈꢂ*ꢃꢑꢂꢓꢍꢒꢉꢇꢃꢅꢈꢃꢑꢂꢉꢍꢋꢃ  
ꢎꢆꢃꢛꢂꢈꢓꢅꢈꢌꢍꢆꢄꢂꢃꢄꢍꢒꢊꢂꢑꢃ]ꢋꢃꢗꢍꢈ*ꢃꢜꢅ[ꢂꢈꢆꢌꢂꢆꢇꢃꢈꢂꢊꢇꢈꢎꢄꢇꢎꢅꢆꢊꢃꢅꢈꢃꢈꢂꢊꢇꢈꢍꢎꢆꢇꢊ*ꢃꢊꢇꢈꢎꢂꢊ*ꢃꢌꢍꢇꢂꢈꢎꢍꢉꢃꢊꢁꢅꢈꢇꢍꢜꢂꢊꢃ]ꢂꢋꢅꢆꢑꢃꢇꢁꢂꢃꢄꢅꢆꢇꢈꢅꢉꢃꢅꢓꢃꢚ#<?V#<@J*ꢃꢅꢈꢃꢍꢄꢇꢊꢃꢅꢓꢃ˜ꢅꢑꢞ  
OBTAINING WARRANTY PERFORMANCE: ꢐꢂꢈ[ꢎꢄꢂꢃꢗꢎꢉꢉꢃ]ꢂꢃꢛꢈꢅ[ꢎꢑꢂꢑꢃ]ꢋꢃꢇꢁꢂꢃꢚ#<?V#<@Jꢃꢖꢒꢇꢁꢅꢈꢎ”ꢂꢑꢃVꢂꢍꢉꢂꢈꢃꢅꢈꢃꢐꢂꢈ[ꢎꢄꢂꢃꢘꢈꢜꢍꢆꢎ”ꢍꢇꢎꢅꢆꢃꢎꢆꢃꢋꢅꢒꢈꢃꢍꢈꢂꢍꢞꢃꢀꢁꢂꢋꢃꢍꢈꢂꢃꢉꢎꢊꢇꢂꢑꢃ  
ꢎꢆꢃꢇꢁꢂꢃ‚ꢂꢉꢉꢅꢗꢃ}ꢍꢜꢂꢊꢞꢃ<ꢓꢃꢍꢊꢊꢎꢊꢇꢍꢆꢄꢂꢃꢎꢊꢃꢈꢂ‘ꢒꢎꢈꢂꢑꢃꢎꢆꢃꢅ]ꢇꢍꢎꢆꢎꢆꢜꢃꢗꢍꢈꢈꢍꢆꢇꢋꢃꢛꢂꢈꢓꢅꢈꢌꢍꢆꢄꢂ*ꢃꢗꢈꢎꢇꢂꢃꢇꢅꢔꢃ#ꢅꢅꢌꢃꢖꢎꢈꢃ@ꢅꢆꢑꢎꢇꢎꢅꢆꢂꢈꢃꢐꢂꢈ[ꢎꢄꢂꢃ>ꢍꢆꢍꢜꢂꢈ*ꢃꢚꢈꢎꢂꢑꢈꢎꢄꢁꢃꢖꢎꢈꢃ@ꢅꢆꢑꢎꢇꢎꢅꢆꢎꢆꢜꢃ@ꢅꢞ  
LIMITATIONS: THIS WARRANTY IS GIVEN IN LIEU OF ALL OTHER WARRANTIESꢞꢃꢖꢆꢋꢇꢁꢎꢆꢜꢃꢎꢆꢃꢇꢁꢂꢃꢗꢍꢈꢈꢍꢆꢇꢋꢃꢆꢅꢇꢗꢎꢇꢁꢊꢇꢍꢆꢑꢎꢆꢜ*ꢃꢖꢙ‚ꢃ<>}Z<?Vꢃ™ꢖ##ꢖꢙꢀ<?ꢐꢃ  
ꢘꢚꢃꢚ<ꢀꢙ?ꢐꢐꢃꢚꢘ#ꢃ}ꢖ#ꢀ<@XZꢖ#ꢃ}X#}ꢘꢐ?ꢃꢖꢙVꢏꢘ#ꢃ>?#@Jꢖꢙꢀꢖ<Z<ꢀ‚ꢃꢐJꢖZZꢃ?ꢃZ<><ꢀ?VꢃꢀꢘꢃꢀJ?ꢃVX#ꢖꢀ<ꢘꢙꢃꢘꢚꢃꢀJ<ꢐꢃ?š}#?ꢐꢐꢃ™ꢖ##ꢖꢙꢀ‚ꢞꢃ  
>ꢖꢙXꢚꢖ@ꢀX#?#ꢃ?š}#?ꢐꢐZ‚ꢃV<ꢐ@Zꢖ<>ꢐꢃꢖꢙVꢃ?š@ZXV?ꢐꢃꢖꢙ‚ꢃZ<ꢖ<Z<ꢀ‚ꢃꢚꢘ#ꢃ@ꢘꢙꢐ?›X?ꢙꢀ<ꢖZꢃꢘ#ꢃ<ꢙ@<V?ꢙꢀꢖZꢃVꢖ>ꢖ˜?ꢃꢚꢘ#ꢃ#?ꢖ@Jꢃꢘꢚꢃ  
ꢖꢙ‚ꢃ?š}#?ꢐꢐ?Vꢃꢘ#ꢃ<>}Z<?Vꢃ™ꢖ##ꢖꢙꢀ‚ꢞ  
NOTE:ꢃꢐꢅꢌꢂꢃꢊꢇꢍꢇꢂꢊꢃꢑꢅꢃꢆꢅꢇꢃꢍꢉꢉꢅꢗꢃꢉꢎꢌꢎꢇꢍꢇꢎꢅꢆꢊꢃꢅꢆꢃꢁꢅꢗꢃꢉꢅꢆꢜꢃꢍꢆꢃꢎꢌꢛꢉꢎꢂꢑꢃꢗꢍꢈꢈꢍꢆꢇꢋꢃꢉꢍꢊꢇꢊ*ꢃꢅꢈꢃꢑꢅꢃꢆꢅꢇꢃꢍꢉꢉꢅꢗꢃꢇꢁꢂꢃꢉꢎꢌꢎꢇꢍꢇꢎꢅꢆꢃꢅꢈꢃꢂ\ꢄꢉꢒꢊꢎꢅꢆꢃꢅꢓꢃꢄꢅꢆꢊꢂ‘ꢒꢂꢆꢇꢎꢍꢉꢃꢅꢈꢃꢎꢆꢄꢎꢑꢂꢆꢇꢍꢉꢃ  
ꢑꢍꢌꢍꢜꢂꢊ*ꢃꢊꢅꢃꢇꢁꢂꢃꢓꢅꢈꢂꢜꢅꢎꢆꢜꢃꢂ\ꢄꢉꢒꢊꢎꢅꢆꢊꢃꢍꢆꢑꢃꢉꢎꢌꢎꢇꢍꢇꢎꢅꢆꢊꢃꢌꢍꢋꢃꢆꢅꢇꢃꢍꢛꢛꢉꢋꢃꢇꢅꢃꢋꢅꢒꢞ  
OTHER:ꢃꢀꢁꢎꢊꢃꢗꢍꢈꢈꢍꢆꢇꢋꢃꢜꢎ[ꢂꢊꢃꢋꢅꢒꢃꢊꢛꢂꢄꢎ[ꢄꢃꢉꢂꢜꢍꢉꢃꢈꢎꢜꢁꢇꢊ*ꢃꢍꢆꢑꢃꢋꢅꢒꢃꢌꢍꢋꢃꢍꢉꢊꢅꢃꢁꢍ[ꢂꢃꢅꢇꢁꢂꢈꢃꢈꢎꢜꢁꢇꢊꢃꢗꢁꢎꢄꢁꢃ[ꢍꢈꢋꢃꢓꢈꢅꢌꢃꢊꢇꢍꢇꢂꢃꢇꢅꢃꢊꢇꢍꢇꢂꢞ  
PROOF OF PURCHASE:ꢃꢘꢗꢆꢂꢈꢃꢌꢒꢊꢇꢃꢛꢈꢅ[ꢎꢑꢂꢃꢛꢈꢅꢅꢓꢃꢅꢓꢃꢛꢒꢈꢄꢁꢍꢊꢂꢃꢎꢆꢃꢅꢈꢑꢂꢈꢃꢇꢅꢃꢈꢂꢄꢂꢎ[ꢂꢃꢍꢆꢋꢃꢗꢍꢈꢈꢍꢆꢇꢋꢃꢈꢂꢉꢍꢇꢂꢑꢃꢊꢂꢈ[ꢎꢄꢂꢊꢞ  
ꢖꢉꢉꢃꢊꢂꢈ[ꢎꢄꢂꢃꢄꢍꢉꢉꢊꢃꢓꢅꢈꢃꢂ\ꢛꢉꢍꢎꢆꢎꢆꢜꢃꢇꢁꢂꢃꢅꢛꢂꢈꢍꢇꢎꢅꢆꢃꢅꢓꢃꢇꢁꢎꢊꢃꢛꢈꢅꢑꢒꢄꢇꢃꢗꢎꢉꢉꢃ]ꢂꢃꢇꢁꢂꢃꢊꢅꢉꢂꢃꢈꢂꢊꢛꢅꢆꢊꢎ]ꢎꢉꢎꢇꢋꢃꢅꢓꢃꢇꢁꢂꢃꢄꢅꢆꢊꢒꢌꢂꢈꢞ  
ꢖꢉꢉꢃꢗꢍꢈꢈꢍꢆꢇꢋꢃꢊꢂꢈ[ꢎꢄꢂꢃꢌꢒꢊꢇꢃ]ꢂꢃꢛꢈꢅ[ꢎꢑꢂꢑꢃ]ꢋꢃꢍꢆꢃꢖꢒꢇꢁꢅꢈꢎ”ꢂꢑꢃꢚ#<?V#<@Jꢃꢐꢂꢈ[ꢎꢄꢂꢃꢖꢜꢂꢆꢄꢋ*ꢃꢒꢆꢉꢂꢊꢊꢃꢍꢒꢇꢁꢅꢈꢎ”ꢂꢑꢃ]ꢋꢃꢚ#<?V#<@Jꢃꢛꢈꢎꢅꢈꢃꢇꢅꢃꢈꢂꢛꢍꢎꢈꢊꢃ]ꢂꢎꢆꢜꢃꢌꢍꢑꢂꢞ  
ꢆꢈ  
Friedrich Air Conditioning Co.  
10001 Reunion Place, Suite 50ꢀꢁꢂꢁSan Antonio, Texas 78216  
1-800-541-66450  
Printed in the U.S.A.  
93001000_00  

Blue Sea Systems Battery Charger 7611 User Manual
Briggs Stratton 8FB User Manual
Brother IntelliFAX 2480C User Manual
Buffalo Technology AIRSTATION WHR G125 User Manual
Canon PIXMA MX870 User Manual
Daewoo DWC 121R User Manual
Haier Air Conditioner HW 24L1V User Manual
Harbor Freight Tools Creeper With Adjustable Headrest 46087 User Manual
Heat Controller Inc Air Conditioner DMC18SB 1 User Manual
Heat Controller PD 91B User Manual