| Thru-the-Wall Series   Service and Parts   Manual   Thru-the-Wall Series   115 Volts US08B10A:Starting with serial number LFMK00001   US10B10A:Starting with serial number LGBK00003   US12B10A:Starting with serial number LGBK00001   230 Volts US10B30A   US14B30A   Starting with serial number LGBK00001   US12B30B:   Unifit. Cool (03/07)   CONTENTS   2.4 REFRIGERATION CYCLE.................................10   1. PREFACE   2.4.1 CONDENSER ......................................10   2.4.2 EVAPORATOR ....................................10   2.4.3 CAPILLARY TUBE...............................10   1.1 SAFETY PRECAUTIONS ...............................2   1.2 INSULATION RESISTANCE TEST.................2   1.3 SPECIFICATIONS ..........................................3   1.4 FEATURES.....................................................5   1.5 CONTROL LOCATIONS.................................5   3. TROUBLESHOOTING GUIDE   3.1 OUTSIDE DIMENSIONS...............................13   3.2 PIPING SYSTEM ..........................................13   3.3 TROUBLESHOOTING GUIDE......................14   2. DISASSEMBLY INSTRUCTIONS   2.1 MECHANICAL PARTS....................................6   2.1.1 FRONT GRILLE.....................................6   2.1.2 CABINET................................................6   2.1.3 CONTROL BOX.....................................6   2.2 AIR HANDLING PARTS..................................7   2.2.1 ORIFICE, HEATER ASSY AND TURBO FAN .........7   2.2.2 FAN........................................................7   2.2.3 SHROUD................................................8   2.3 ELECTRICAL PARTS.....................................8   2.3.1 MOTOR..................................................8   2.3.2 COMPRESSOR .....................................8   2.3.3 CAPACITOR ..........................................8   2.3.4 POWER CORD......................................9   2.3.5 THERMISTOR .......................................9   4. SCHEMATIC DIAGRAM   4.1 CIRCUIT DIAGRAM......................................19   5. EXPLODED VIEW..................................20   6. REPLACEMENT PARTS LIST .......21   1. PREFACE   This SERVICE MANUAL provides various service information, including the mechanical and electrical   parts etc. This room air conditioner was manufactured and assembled under a strict quality control system.   The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.   1.1 SAFETY PRECAUTIONS   1. When servicing the unit, turn off the air conditioner   and unplug the power cord.   1.2 INSULATION RESISTANCE TEST   1. Unplug the power cord and connect a jumper   between 2 pins (black and white).   2. Observe the original lead dress.   2. The grounding conductor (green or green & yellow)   is to be open.   3. Measure the resistance value with an ohm meter   between the jumpered lead and each exposed   metallic part on the equipment.   If a short circuit is found, replace all parts which   have been overheated or damaged by the short   circuit.   3. After servicing the unit, make an insulation   resistance test to protect the customer from being   exposed to shock hazards.   4. The value should be over 1MΩ.   —2—   1.3 SPECIFICATIONS   1.3.1 FOR US08B10A/US10B10A/US12B10A   MODELS   REMARK   US08B10A   US10B10A   US12B10A   ITEMS   POWER SUPPLY   1Ø, 115V, 60Hz   9,800   COOLING CAPACITY (Btu/h)   INPUT (W)   RUNNING CURRENT (A)   8,000   11,500   1,310   830   7.5   1,110   10.2   12.0   E.E.R   (Btu/w.h)   9.6   8.8   8.8   REFRIGERANT (R-22) CHARGE(g)   545g(19.2OZ)   470g(16.6OZ)   26.7(DB) 19.4(WB)   35(DB) 23.9(WB)   500g(17.6OZ)   OPERATING   INDOOR (°C)   TEMPERATURE   EVAPORATOR   CONDENSER   FAN, INDOOR   FAN, OUTDOOR   OUTDOOR (°C)   2 ROW 12STACKS   3 ROW 12STACKS   2ROW 17STACKS, L-BENDING TYPE   LOUVERED-FIN TYPE   TURBO FAN   PROPELLER TYPE FAN WITH SLINGER-RING   3/3   FAN SPEEDS, FAN/COOLING   FAN MOTOR   6 POLES   4POLES   OPERATION CONTROL   ROOM TEMP. CONTROL   AIR DIRECTION CONTROL   ELECTRIC   THERMISTOR   VERTICAL LOUVER(RIGHT & LEFT)   HORIZONTAL LOUVER(UP & DOWN)   TOP-DOWN   CONSTRUCTION   PROTECTOR   COMPRESSOR   FAN MOTOR   EXTERNAL OVERLOAD PROTECTOR   INTERNAL THERMAL PROTECTOR   2.3m (3WIRES WITH GROUNDING)   ATTACHMENT PLUG(CORD-CONNECTED TYPE, LCDI)   SPLASHED BY FAN SLINGER   POWER CORD   DRAIN SYSTEM   NET WEIGHT   (lbs/kg)   73/33   78/35   24 x 1413/32 x 20 3/32   610 x 366 x 499   25 7/8 x 15 17/32 x 16 23/32   656 x 394 x 425   20 1/2   80/36   DIMENSION   (inch)   (W x H x D)   (mm)   (inch)   (mm)   (inch)   (mm)   SLEEVE DIMESION   (W x H x D)   OPTIONAL   PART   SLEEVE DEPTH   WITH FRONT GRILLE   521   —3—   1.3.2 FOR US10B30A/US12B30B/US14B30A   MODELS   US10B30A   US12B30B   US14B30A   REMAR   ITEMS   1Ø, 230/208V, 60Hz   11,500/11,200   1,310/1,270   POWER SUPPLY   10,000/9,800   1,060/1,040   4.7/5.2   13,200/12,800   1,550/1,500   7.1/7.6   COOLING CAPACITY   INPUT   (Btu/h)   (W)   6.0/6.4   RUNNING CURRENT   E.E.R.   (A)   9.4/9.4   8.8/8.8   8.5/8.5   (Btu/W.h)   480g(16.9OZ)   485g(17.1OZ)   26.7(DB) 19.4(WB)   35(DB) 23.9(WB)   545g(19.2OZ)   INDOOR (°C)   OUTDOOR (°C)   OPERATING   TEMPERA-TURE   REFRIGERANT (R-22) CHARGE(g)   EVAPORATOR   3 ROW 12STACKS 3 ROW 12STACKS 3 ROW 12STACKS   2ROW 17STACKS, L-BENDING TYPE   LOUVERED-FIN TYPE   CONDENSER   TURBO FAN   FAN, INDOOR   PROPELLER TYPE FAN WITH SLINGER-RING   3/3   FAN, OUTDOOR   FAN SPEEDS (FAN/COOLING/HEATING)   FAN MOTOR   6 POLES   4POLES   ELECTRIC   4POLES   OPERATION CONTROL   ROOM TEMP. CONTROL   THERMISTOR   VERTICAL LOUVER(RIGHT & LEFT)   HORIZONTAL LOUVER(UP & DOWN)   TOP-DOWN   AIR DIRECTION CONTROL   CONSTRUCTION   EXTERNAL OVERLOAD PROTECTOR   INTERNAL THERMAL PROTECTOR   1.4m (3WIRES WITH GROUNDING)   ATTACHMENT PLUG(CORD-CONNECTED TYPE, LCDI)   SPLASHED BY FAN SLINGER   COMPRESSOR   PROTECTOR   FAN MOTOR   POWER CORD   DRAIN SYSTEM   78/35   80/36   24 x 14 13/32 x 20 3/32   610 x 366 x 499   25 7/8 x 15 17/32 x 16 23/32   656 x 394 x 425   20 1/2   87/40   NET WEIGHT   (lbs/kg)   (inch)   (mm)   (inch)   (mm)   (inch)   (mm)   DIMENSION   (W x H x D)   SLEEVE DIMESION   (W x H x D)   OPTIONAL   PART   SLEEVE DEPTH   WITH FRONT GRILLE   521   —4—   1.4 FEATURES   • Designed for cooling only.   • Built in adjustable THERMOSTAT.   • Washable one-touch filter.   • Compact size.   • Powerful and quiet.   • Slide out chassis for the simple installation and service.   1.5 CONTROL LOCATIONS   1.5.1 COOLING ONLY MODEL   • OPERATION   REMOTE CONTROL SIGNAL RECEIVER   TEMPERATURE SETTING   • Use this button to automatically control the temperature of the room.   The temperature can be set within a range of 60°F to 86°F by   increments of 1°F.   • The setting appears in the display.   POWER   • To turn the air conditioner ON, push this button.   To turn the air conditioner OFF, push the button again.   • This button takes priority over any other button.   • When you first turn it on, the unit is in cool mode, at High fan   speed, and set at a temperature setting of 72°F.   TIMER   - SHUT-OFF TIME   • You will usually use shut-off time while you sleep.   • If unit is running, use Timer to set number of   hours until shut-off.   • For your sleeping comfort, once Timer is set, the   Temperature setting will raise 2°F after 30 min.,   and once again after another 30 min.   FAN SPEED   • Every time you push this button, it advances the setting as follows:   {High ꢀ Low ꢀ Med ꢀ High}   ....   • Push Timer button to advance setting from 1 Hour   ꢀ 2 Hours ꢀꢀ   ꢀ 12 Hours maximum.   - START TIME   • If unit is off, use Timer to set number of hours before unit starts.   ꢀ.....   • Push Timer button to advance setting from 1 Hour   ꢀ 2 Hours   ꢀ ꢀ 12 Hours maximum.   MODE   - Push this button to shift mode of operation from COOL ꢀꢀ MONEY SAVER ꢀ FAN.   - COOL :   • Fan runs continuously for normal cooling operation.   - MONEY SAVER:   • The fan stops when the compressor stops cooling. Approximately every 3 minutes the fan will turn on and the unit will check   the room air to determine if cooling is needed.   - FAN :   • Fan-only operation.   • VENTILATION   Push the lever to the "CLOSE" position to cool, heat or recirculate room air only.   Pull the lever to the "OPEN" position to exhaust smoke or stale air from the room.   This feature is best used in conjunction with the FAN ONLY position.   CAUTION   When the air conditioner has been operating in the   cooling and is turned off or set to the fan only position,   wait at least 3 minutes before resetting to the cooling   operation again.   PULL OPEN / PUSH CLOSE   —5—   2. DISASSEMBLY INSTRUCTIONS   — Prior to disassembling the unit, make sure that the POWER is off and the power cord is unplugged from the   wall receptacle.   2.1 MECHANICAL PARTS   2.1.1 FRONT GRILLE   1. Open the inlet grille downward.   2. Remove the screw which fastens the front grille.   3. Pull the front grille from the right side.   4. Remove the front grille. (See Fig. 1)   5. Re-install the component by referring to the   removal procedure.   Figure 1   2.1.2 CABINET   1. After disassembling the FRONT GRILLE, remove   the 6 screws which fasten the cabinet at the both   sides and the top. (See Fig. 2)   Keep these for later use.   Figure 2   2.1.3 CONTROL BOX   1. Remove the front grille. (Refer to section 2.1.1)   2. Remove the screw which fasten the control   box. (See Fig. 3)   3. Pull the control box from the barrier.(See Fig.3)   4. Discharge the capacitor by placing a 20,000 ohm   resistor across the capacitor terminals.   5. Disconnect two wire housings in the control box.   6. Pull the control box forward completely.   7. Re-install the components by referring to the   removal procedure. (See Fig. 3)   Figure 3   (Refer to the circuit diagram found on page 19 in   this manual and on the control box.)   —6—   2.2 AIR HANDLING PARTS   2.2.1 ORIFICE, AND TURBO FAN   1. Remove the front grille. (Refer to section 2.1.1)   2. Remove the cabinet. (Refer to section 2.1.2)   3. Remove the 2 screws which fasten the   evaporator at the left side and the right side.   (See Fig. 4)   4. Move the evaporator to the side carefully.   Figure 4   5. Remove the orifice. (See Fig. 5)   Figure 5   8. Using handheld pliers, remove the clamp which   secures the turbo fan. (See Fig. 6)   Figure 6   9. Remove the turbo fan with pliers or your hand,   without touching blades. (See Fig. 7)   10. Re-install the components by referring to the   removal procedures, above.   Figure 7   2.2.2 FAN   1. Remove the cabinet. (Refer to section 2.1.2)   2. Remove the brace.   (Refer to section 2.2.1)   3. Remove the 7 screws which fasten the condenser.   4. Move the condenser to the side carefully.   5. Using handheld pliers, remove the clamp which   secures the fan.   6. Remove the fan. (See Fig. 8)   7. Re-install the components by referring to the   removal procedures, above.   Figure 8   —7—   2.2.3 SHROUD   1. Remove the fan. (Refer to section 2.2.2)   2. Remove the shroud. (See Fig. 9)   3. Re-install the components by referring to the   removal procedures, above.   2.3 ELECTRICAL PARTS   2.3.1 MOTOR   1. Remove the cabinet. (Refer to section 2.1.2)   2. Remove the clamp cord and disconnect the wire   housing in control box. (Refer to section 2.1.3)   3. Remove the turbo fan. (Refer to section 2.2.2)   4. Remove the fan. (Refer to section 2.2.2)   5. Remove the 4 or 2 screws which fasten the motor.   (See Fig. 10)   Figure 9   6. Remove the motor.   7. Re-install the components by referring to the   removal procedures, above.   2.3.2 COMPRESSOR   1. Remove the cabinet. (Refer to section 2.1.2)   2. Discharge the refrigerant system using a FreonTM   Recovery System.   Figure 10   Install a valve for recovery before venting the   Freon. Remove the valve when finished.   3. Disconnect the 3 leads from the compressor.   4. After purging the unit completely, unbraze the   suction and discharge tubes at the compressor   connections.   5. Remove the 3 nuts and the 3 washers which   fasten the compressor. (See Fig. 11)   6. Remove the compressor.   7. Re-install the components by referring to the   removal procedures, above.   2.3.3 CAPACITOR   1. Remove the control box. (Refer to section 2.1.3)   Figure 11   2. Remove the 1 screw   3. Open the control box   4. Disconnect all the leads on the capacitor terminals.   5. Re-install the components by referring to the   removal procedures, above.   Figure 12   —8—   2.3.4 POWER CORD   1. Remove the control box. (Refer to section 2.1.3)   2. Unfold the control box. (Refer to section 2.3.3)   3. Disconnect the grounding screw from the Base   pan.   4. Disconnect 2 receptacles.   5. Remove a screw which fastens the clip cord.   6. Pull the power cord. (See Fig. 13)   7. Re-install the components by referring to the   removal procedure, above.   (Use only one ground-marked hole, , for ground   connection.)   8. If the supply cord of this appliance is damaged, it   must be replaced with the factory-authorized and   specified cord.   Figure 13   2.3.5 ELECTRONIC CONTROL BOARD   1. Remove the control box. (Refer to section 2.1.3)   2. Unfold the control box. (Refer to section 2.3.3)   3. Disconnect all the leads of Electronic control board   terminals.   4. Remove the Electronic control board. (See Fig. 14)   5. Re-install the components by referring to the   removal procedures, above.   Figure 14   —9—   2.4 REFRIGERATION CYCLE   CAUTION   TM   Discharge the refrigerant system using a Freon   Recovery System.   Install a valve for the recovery, before venting   the Freon, remove the valve when finished.   2.4.1 CONDENSER   1. Remove the cabinet. (Refer to section 2.1.2)   2. Remove the brace.   (Refer to section 2.2.1)   3. Remove the 7 screws which fasten the condenser.   4. After discharging the refrigerant completely into a   FreonTM Recovery System, unbraze the   interconnecting tube at the condenser   connections.   5. Remove the condenser.   6. Re-install the components by referring to the notes   – on pages 11-13. (See Fig. 15)   Figure 15   2.4.2 EVAPORATOR   1. Remove the cabinet. (Refer to section 2.1.2)   2. Discharge the refrigerant completely – into a   FreonTM Recovery System.   3. Remove the 2 screws which fasten the evaporator   at the left side and the right side.   4. Move the evaporator to the side carefully and then   unbraze the interconnecting tube at the evaporator   connectors.   5. Remove the evaporator.   6. Re-install the components by referring to the notes   – on pages 11-13. (See Fig. 16)   Figure 16   2.4.3 CAPILLARY TUBE   1. Remove the cabinet. (Refer to section 2.1.2)   2. After discharging the refrigerant completely – into   a FreonTM Recovery System, unbraze the   interconnecting tube at the capillary tube.   3. Remove the capillary tube.   4. Re-install the components by referring to the notes   – on page 11-13.   —10—   NOTES   — Replacement of the refrigeration cycle.   1. When replacing refrigeration components, be sure   to discharge the refrigerant system using a FreonTM   recovery System.   Install a valve for the recovery, before venting the   Freon, remove the valve when finished.   2. After discharging the unit completely, remove the   desired component, and unbraze the pinch-off   tubes.   3. Solder service valves into the pinch-off tube ports,   leaving the valves open.   4. Solder the pinch-off tubes with Service valves.   5. Evacuate as follows.   6. Recharge as follows :   1) Refrigeration cycle systems are charged from the   High-side. If the total charge cannot be put   in the High-side, the balance will be put in the   suction line through the access valve which you   installed as the system was opened.   2) Connect the charging cylinder as shown in Fig. 17B.   With valve C open, discharge the hose at the   manifold connection.   3) Open valve A and allow the proper charge to   enter the system. Valve B is still closed.   4) If more charge is required, and the high-side will   not   1) Connect the vacuum pump, as illustrated Fig.   17A.   take it. Close valve A.   2) Start the vacuum pump, slowly open manifold   valves A and B with two full turns   5) With the unit running, open valve B and add the   balance of the charge.   counterclockwise and leave the valves closed.   The vacuum pump is now pulling through valves   A and B up to valve C by means of the manifold   and entire system.   a. Do not add the liquid refrigerant to the Low-   side.   b. Watch the Low-side gauge; allow pressure to   rise to 30 lbs.   c. Turn off valve B and allow pressure to drop.   d. Repeat steps B and C until the balance of the   charge is in the system.   CAUTION   If high vacuum equipment is used, just crack   valves A and B for a few minutes, then open   slowly with the two full turns counterclockwise.   This will keep oil from foaming and being   drawn into the vacuum pump.   6) When satisfied the unit is operating correctly,   use the pinch-off tool with the unit still running   and clamp on to the pinch-off tube. Using a tube   cutter, cut the pinch-off tube about 2 inches from   the pinch-off tool. Use sil-fos solder and solder   pinch-off tube closed. Turn off the unit, allow it to   set for a while, and then test for leakage add the   pinch-off connection.   3) Operate the vacuum pump for 20 to 30 minutes,   until 600 microns of vacuum is obtained. Close   valves A and B, and observe vacuum gauge for   a few minutes. A rise in pressure would   indicate a possible leak or moisture remaining in   the system. With valves A and B closed, stop   the vacuum pump.   4) Remove the hose from the vacuum pump and   place it on the charging cylinder. See Fig. 17B.   Open valve C.   Discharge the line at the manifold connection.   5) The system is now ready for final charging.   —11—   Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment, Pinch-off tool   capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service   valve.   COMPOUND GAUGE   CONDENSER   (HIGH PRESSURE SIDE)   MANIFOLD   GAUGE   A B CAPILLARY TUBE   SEE INSETS   BELOW   EVAPORATOR   (LOW PRESSURE SIDE)   COMPRESSOR   HI   LOW   A B A B EXTERNAL   VACUUM PUMP   CHARGING   CYLINDER   C Figure 17A-Pulling Vacuum   Figure 17B-Charging   —12—   3. TROUBLESHOOTING GUIDE   3.1 OUTSIDE DIMENSIONS   20-3/32"   24"   (610mm)   (499mm)   3.2 PIPING SYSTEM   CONDENSER COILS   FAN   CAPILLARY TUBE   COMPRESSOR   MOTOR   TURBO FAN   EVAPORATOR COILS   : REFRIGERANT FLOW   Following is a brief description of the important components and their functions in the refrigeration system.   Refer to Fig. 18 to follow the refrigeration cycle and the flow of the refrigerant in the cooling cycle.   ROOM AIR CONDITIONER   CYCLE OF REFRIGERATION   EVAPORATOR COILS   CONDENSER COILS   VAPOR INLET   SUCTION LINE   COOL LOW PRESSURE VAPOR   HOT   DISCHARGED   AIR   COMPLETE LIQUID   BOIL OFF POINT   COOLED   AIR   ROOM AIR HEAT LOAD   OUTSIDE COOLING   AIR FOR REFRIGERANT   PASS THROUGH   MOTOR   COMPRESSOR   OIL   LIQUID   PRESSURE   DROP   LIQUID OUTLET   HIGH PRESSURE VAPOR   (LIQUID REFRIGERANT)   LIQUID REFRIGERANT   LOW PRESSURE VAPOR   CAPILLARY TUBE   Figure 18   —13—   3.3 TROUBLESHOOTING GUIDE   In general, possible trouble is classified in two causes.   One is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning   caused by a defect in the refrigeration circuit and/or improper application.   Unit is running but cooling is ineffective   Ineffective Cooling   Check cold air circulation   for smooth flow.   Check outdoor coil   (heat exchanger) & the fan   operation.   Check heat load increase.   Unexpected residue   Overloaded Circuit   Dirty indoor coil   (Heat exchanger)   Check gas leakage.   Repair gas leak.   Malfunction of fan   Clogged air filter   Check inside gas pressure.   Replacement of unit if the   unit is beyond repair.   Obstruction at air outlet   Adjusting of refrigerant   charge   Correct above troubles   Malfunction of compressor   Check for a clog in   refrigeration circuit.   Replacement of   compressor   Satisfactory operation with   temperature difference of   inlet & outlet air ; 18-26°F   Repair for a clog in   refrigeration circuit.   —14—   Fails to Start   Check power source.   Check circuit breaker   and fuse.   Check control switch   setting.   Check control board   Only compressor fails to   start.   Only fan fails to start.   Improper wiring.   Drop in power voltage.   Improper thermostat setting   Defect of fan motor   capacitor.   Defective compressor   capacitor.   Loose terminal connection.   Improper wiring   Irregular motor resistance   ( ).   Irregular motor insulation   ).   Check capacitor.   Replacement.   ( Replacement of fan motor   Regular but fails to start   Irregular motor resistance ( )   Irregular motor insulation ( )   Replacement of compressor   (locking of rotor, metal)   Replacement of compressor   (Motor damaged)   —15—   COMPLAINT   CAUSE   REMEDY   Fan motor will not run.   No power   Check voltage at outlet. Correct if none.   Power supply cord   Rotary switch   Check voltage to rotary switch. If none, check   power supply cord. Replace cord if circuit is open.   Check switch continuity. Refer to wiring diagram   for terminal identification. Replace switch if   defective.   Wire disconnected or   connection loose   Connect wire. Refer to wiring diagram for terminal   identification. Repair or replace loose terminal.   Capacitor (Discharge   Test capacitor.   capacitor before testing.)   Replace if not within ±10% of manufacturer's   rating. Replace if shorted, open, or damaged.   Will not rotate   Fan blade hitting shroud or blower wheel hitting   scroll. Realign assembly.   Units using slinger ring condenser fans must   have 1/4 to 5/16 inch clearance to the base. If it is   hitting the base, shim up the bottom of the fan   motor with mounting screw(s).   Check fan motor bearings; if motor shaft will not   rotate, replace the motor.   Fan motor runs   intermittently   Cycles on overload.   Check voltage. See limits on page 17. If not within   limits, call an electrician.   Test capacitor.   Check bearings. Does the fan blade rotate freely?   If not, replace fan motor.   Pay attention to any change from high speed to   low speed. If the speed does not change, replace   the motor.   Fan motor noise.   Grommets   Fan   Check grommets; if worn or missing, replace them.   If cracked, out of balance, or partially missing,   replace it.   Turbo fan   If cracked, out of balance, or partially missing,   replace it.   Loose set screw   Worn bearings   Tighten it.   If knocking sounds continue when running or   loose, replace the motor. If the motor hums or   noise appears to be internal while running,   replace motor.   —16—   COMPLAINT   CAUSE   REMEDY   Compressor will not run,   but fan motor runs.   Voltage   Wiring   Check voltage. See the limits on the preceding.   page. If not within limits, call an electrician.   Check the wire connections, if loose, repair or   replace the terminal. If wires are off, refer to wiring   diagram for identification, and replace. Check wire   locations. If not per wiring diagram, correct.   Rotary   Check for continuity, refer to the wiring diagram   for terminal identification. Replace the switch if   circuit is open.   Capacitor (Discharge   capacitor before   servicing.)   Check the capacitor.   Replace if not within ±10% of manufacturers   rating. Replace if shorted, open, or damaged.   Check the compressor for open circuit or   ground. If open or grounded, replace the   compressor.   Compressor   Overload   Check the compressor overload, if externally   mounted. Replace if open. (If the compressor   temperature is high, remove the overload, cool it,   and retest.)   ROOM AIR CONDITIONER VOLTAGE LIMITS   NAME PLATE RATING   MINIMUM   MAXIMUM   126.5V   253V   115V   103.5V   187V   208/230V   —17—   REMEDY   COMPLAINT   CAUSE   Compressor cycles   on overload.   Voltage   Check the voltage. See the limits on the preced-   ing page. If not within limits, call an electrician.   Overload   Check overload, if externally mounted.   Replace if open. (If the compressor temperature   is high, remove the overload, cool, and retest.)   Fan motor   If not running, determine the cause. Replace if   required.   Condenser air flow   restriction   Remove the cabinet. Inspect the interior surface   of the condenser; if restricted, clean carefully   (do not damage fins). Clean the interior base before   reassembling.   Condenser fins   (damaged)   If condenser fins are closed over a large area   on the coil surface, head pressures will increase,   causing the compressor to cycle. Straighten the   fins or replace the coil.   Capacitor   Test capacitor.   Wiring   Refrigerating system   Air filter   Check the terminals. If loose, repair or replace.   Check the system for a restriction.   If restricted, clean or replace.   Insufficient cooling or   heating   Exhaust damper door   Unit undersized   Close if open.   Determine if the unit is properly sized for the area to   be cooled.   Excessive noise.   Blower or fan   Copper tubing   Check the set screw or clamp. If loose or missing,   correct. If the blower or fan is hitting air guide,   rearrange the air handling parts.   Remove the cabinet and carefully rearrange tubing   not to contact cabinet, compressor, shroud, and   barrier.   —18—   4. SCHEMATIC DIAGRAM   4.1 CIRCUIT DIAGRAM   • MODEL : US08B10A, US10B10A, US12B10A, US10B30A, US12B30B,US14B30A   —19—   5. EXPLODED VIEW   • MODEL: US08B10A, US10B10A, US12B10A, US10B30A, US12B30B,US14B30A   749180   E 152302   147581   147582-1   135303   147582-2   130900   149980   135312   346811   W48602   559010   435301   359012   W48602   435301   435300   352380   349600   731273   147900   130410   A 264110   W6631   268714   263230   B C 567502   268712   C o o l E n e v r e g S y a r F a n F 1 L F O W 2 M H F E 3 D H I G T i m e ' F r M O D E T N E M P W0CZZ   T I M E R F A S P E E D P O W E R 550140   238310   237200   267110   —20—   6. REPLACEMENT PARTS LIST   • MODEL: US08B10A   US08B10A(TXC121BPMK0.AWYBFRD)   LocNo   W0CZZ   130410   130900   731273   749180   135303   135312   238310   W48602   346811   147581   147582-1   147582-2   147900   149980   550140   15302   FRD P/NO   67300726   67302925   67303712   67306311   67308102   67306106   67306012   67500114   67302500   67303021   67306205   67306256   67306257   67306802   67500112   67305000   67500113   67302725   67302607   67303202   67307804   67300027   67307701   67301406   67307620   67307619   67304801   67305510   Description   CAPACITOR,DRAWING   BASE ASSEMBLY,SINGLE   CABINET   REMARK   R R R R R R R R R R R R R R R R R R R R R R R R R R R R INSTALL PART ASSEMBLY. SINGLE   FRAME   GRILLE,INLET   GRILLE ASSEMBLY,FRONT(SINGLE)   ESCUTCHEON   CLAMP,SPRING   MOTOR ASSEMBLY,SINGLE   LOUVER,HORIZONTAL   LOUVER,VERTICAL   LOUVER,VERTICAL   BARRIER,SINGLE   SHROUD   ISOLATOR,COMP   Filter,Air   352380   359012   559010   263230   264110   267110   567502   268714   268712   435301   237200   AIR GUIDE   FAN,TURBO   FAN ASSEMBLY,AXIAL   THERMISTOR ASSEMBLY   POWER CORD ASSEMBLY   REMOTE CONTROLLER ASSEMBLY   O.L.P   PWB(PCB) ASSEMBLY,MAIN   PWB(PCB) ASSEMBLY,DISPLAY   GRILLE,REAR   PANEL,CONTROL   —21—   • MODEL: US10B10A   US10B10A(TXC101BPMK0.AWYBFRD)   LocNo   W0CZZ   130410   130900   731273   749180   135303   135312   238310   W48602   346811   147581   147582-1   147582-2   346900   149980   550140   15302   FRD P/NO   Description   CAPACITOR,DRAWING   BASE ASSEMBLY,SINGLE   CABINET   REMARK   67300724   67302926   67303712   67306311   67308102   67306106   67306012   67500114   67302500   67303023   67306205   67306250   67306256   67303606   67500112   67305000   67500113   67302724   67302607   67303202   67307804   67300027   67307701   67301409   67307620   67307619   67304801   67305510   R R R R R R R R R R R R R R R R R R R R R R R R R R R R INSTALL PART ASSEMBLY. SINGLE   FRAME   GRILLE,INLET   GRILLE ASSEMBLY,FRONT(SINGLE)   ESCUTCHEON   CLAMP,SPRING   MOTOR ASSEMBLY,SINGLE   LOUVER,HORIZONTAL   LOUVER,VERTICAL   LOUVER,VERTICAL   MOUNT, MOTOR   SHROUD   ISOLATOR,COMP   Filter,Air   352380   359012   559010   263230   264110   267110   567502   268714   268712   435301   237200   AIR GUIDE   FAN,TURBO   FAN ASSEMBLY,AXIAL   THERMISTOR ASSEMBLY   POWER CORD ASSEMBLY   REMOTE CONTROLLER ASSEMBLY   O.L.P   PWB(PCB) ASSEMBLY,MAIN   PWB(PCB) ASSEMBLY,DISPLAY   GRILLE,REAR   PANEL,CONTROL   —22—   • MODEL: US12B10A   US12B10A(TXC081BPMK0.AWYBFRD)   LocNo   W0CZZ   130410   130900   731273   749180   135303   135312   238310   W48602   346811   147581   147582-1   147582-2   346900   550140   149980   15302   FRD P/NO   Description   CAPACITOR,DRAWING   BASE ASSEMBLY,SINGLE   CABINET   REMARK   67300724   67302926   67303712   67306311   67308102   67306106   67306012   67500114   67302500   67303023   67306205   67306256   67306257   67303606   67305000   67500112   67500113   67302724   67302607   67303202   67307804   67300025   67307701   67301407   67307620   67307619   67304801   67305510   R R R R R R R R R R R R R R R R R R R R R R R R R R R R INSTALL PART ASSEMBLY. SINGLE   FRAME   GRILLE,INLET   GRILLE ASSEMBLY,FRONT(SINGLE)   ESCUTCHEON   CLAMP,SPRING   MOTOR ASSEMBLY,SINGLE   LOUVER,HORIZONTAL   LOUVER,VERTICAL   LOUVER,VERTICAL   MOUNT MOTOR   ISOLATOR,COMP   SHROUD   Filter,Air   352380   359012   559010   263230   264110   267110   567502   268714   268712   435301   237200   AIR GUIDE   FAN,TURBO   FAN ASSEMBLY,AXIAL   THERMISTOR ASSEMBLY   POWER CORD ASSEMBLY   REMOTE CONTROLLER ASSEMBLY   O.L.P   PWB(PCB) ASSEMBLY,MAIN   PWB(PCB) ASSEMBLY,DISPLAY   GRILLE,REAR   PANEL,CONTROL   —23—   • MODEL: US10B30A   US10B30A(TXC103BPMK0.AWYBFRD)   DESCRIPTION   LocNo   W0CZZ   130410   130900   731273   749180   135303   135312   238310   W48602   346811   147581   147582-1   147582-2   149980   550140   15302   FRD P/NO   67300723   REMARK   CAPACITOR,DRAWING   BASE ASSEMBLY,SINGLE   CABINET   R R R R R R R R R R R R R R R R R R R R R R R R R R R 67302924   67303712   67306311   67308102   67306106   67306012   67500114   67302500   67303024   67306205   67306256   67306257   67500112   67305000   67500113   67302725   67302607   67303202   67307804   67300026   67307701   67301416   67307618   67307619   67304801   67305510   INSTALL PART ASSEMBLY. SINGLE   FRAME   GRILLE,INLET   GRILLE ASSEMBLY,FRONT(SINGLE)   ESCUTCHEON   CLAMP,SPRING   MOTOR ASSEMBLY,SINGLE   LOUVER,HORIZONTAL   LOUVER,VERTICAL   LOUVER,VERTICAL   SHROUD   ISOLATOR,COMP   Filter,Air   352380   359012   559010   263230   264110   267110   567502   268714   268712   435301   237200   AIR GUIDE   FAN,TURBO   FAN ASSEMBLY,AXIAL   THERMISTOR ASSEMBLY   POWER CORD ASSEMBLY   REMOTE CONTROLLER ASSEMBLY   O.L.P   PWB(PCB) ASSEMBLY,MAIN   PWB(PCB) ASSEMBLY,DISPLAY   GRILLE,REAR   PANEL,CONTROL   —24—   • MODEL: US12B30B   US12B30B(TXC123BPMK0.AWYBFRD)   DESCRIPTION   LocNo   W0CZZ   130410   130900   731273   749180   135303   135312   238310   W48602   346811   147581   147582-1   147582-2   346900   149980   550140   15302   FRD P/NO   67300723   REMARK   CAPACITOR,DRAWING   BASE ASSEMBLY,SINGLE   CABINET   R R R R R R R R R R R R R R R R R R R R R R R R R R R R 67302926   67303712   67306311   673008102   67306106   67306012   67500114   67302500   67303037   67306205   67306256   67306257   67303606   67500112   67305000   67500113   67302724   67302608   67303202   67307804   67300026   67307701   67500056   67307618   67307619   67304801   67305510   INSTALL PART ASSEMBLY. SINGLE   FRAME   GRILLE,INLET   GRILLE ASSEMBLY,FRONT(SINGLE)   ESCUTCHEON   CLAMP,SPRING   MOTOR ASSEMBLY,SINGLE   LOUVER,HORIZONTAL   LOUVER,VERTICAL   LOUVER,VERTICAL   MOUNT MOTOR   SHROUD   ISOLATOR,COMP   Filter,Air   352380   359012   559010   263230   264110   267110   567502   268714   268712   435301   237200   AIR GUIDE   FAN,TURBO   FAN ASSEMBLY,AXIAL   THERMISTOR ASSEMBLY   POWER CORD ASSEMBLY   REMOTE CONTROLLER ASSEMBLY   O.L.P   PWB(PCB) ASSEMBLY,MAIN   PWB(PCB) ASSEMBLY,DISPLAY   GRILLE,REAR   PANEL,CONTROL   —25—   • MODEL: US14B30A   US14B30A(TXC143BPMK0.AWYBFRD)   DESCRIPTION   LocNo   130410   130900   731273   749180   135303   135312   238310   W48602   346811   147581   147582-1   147582-2   346900   149980   550140   15302   FRD P/NO   67302926   REMARK   BASE ASSEMBLY,SINGLE   CABINET   R R R R R R R R R R R R R R R R R R R R R R R R R R R R 67303712   67306311   67308102   67306106   67306012   67500114   67302500   67303037   67306205   67306256   67306257   67303606   67500112   67305000   67500113   67302724   67302607   67303202   67300727   67307804   67300026   67307701   67301406   67307618   67307619   67304801   67305510   INSTALL PART ASSEMBLY. SINGLE   FRAME   GRILLE,INLET   GRILLE ASSEMBLY,FRONT(SINGLE)   ESCUTCHEON   CLAMP,SPRING   MOTOR ASSEMBLY,SINGLE   LOUVER,HORIZONTAL   LOUVER,VERTICAL   LOUVER,VERTICAL   MOUNT MOTOR   SHROUD   ISOLATOR,COMP   Filter,Air   352380   359012   559010   W0CZZ   263230   264110   267110   567502   268714   268712   435301   237200   AIR GUIDE   FAN,TURBO   FAN ASSEMBLY,AXIAL   CAPACITOR,DRAWING   THERMISTOR ASSEMBLY   POWER CORD ASSEMBLY   REMOTE CONTROLLER ASSEMBLY   O.L.P   PWB(PCB) ASSEMBLY,MAIN   PWB(PCB) ASSEMBLY,DISPLAY   GRILLE,REAR   PANEL,CONTROL   —26—   FRIEDRICH AIR CONDITIONING CO.   Post Office Box 1540 • 4200 N. Pan Am Expressway • San Antonio, Texas 78295-1540   • (210) 357-4400 • FAX (210) 357-4480   P/NO.:3828A20294U   Printed in the U.S.A   UNi-fit. Cool (03/07)   |