Emerson Air Conditioner 3000 User Manual

Precision Cooling  
For Business-Critical Continuity™  
Liebert® Challenger3000 with Liebert iCOM®  
Installation Manual - 3 & 5 Tons, 50 & 60Hz  
TABLE OF CONTENTS  
3.2.3 Liebert Lee-Temp /Flood Back Head Pressure Control Condensers . . . . . . . . . . . . . . . . . . . 24  
3.5  
Air-Cooled Condenser with Liebert Lee-Temp“Flooded Condenser” Head Pressure  
Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32  
4.2  
i
4.3.1 Standard Valve - 150psig (1034kPa) System for 3 & 5-Ton Units (Johnson Controls  
Controls Valve) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
5.7.1 Standard Valve - 150psig (1034kPa) System for 3 & 5-Ton Units (Johnson Controls  
Controls Valve) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54  
FIGURES  
Figure 1  
®
Figure 13 Electrical field connections for Liebert iCOM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
Figure 17 General arrangement—Air-cooled models with Liebert Lee-Temp . . . . . . . . . . . . . . . . . . . . . . 34  
iii  
Figure 37 3-ton centrifugal air-cooled condensing unit (con’t.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70  
Figure 39 5-ton centrifugal air-cooled condensing unit dimensional data (con’t.) . . . . . . . . . . . . . . . . . . . . . 72  
Figure 42 3-ton water/glycol-cooled condensing unit (con’t.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76  
Figure 44 5-ton water/glycol-cooled condensing unit (con’t.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78  
TABLES  
Table 3  
Recommended free area ft (m ) for grilles or perforated panels at output velocities of 550  
and 600 fpm (2.8 and 3.1 m/s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
2
2
discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65  
suction gas) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79  
Important Safety Instructions  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS  
This manual contains important safety instructions that should be followed during the installation  
and maintenance of the Liebert Challenger 3000. Read this manual thoroughly before attempting to  
install or operate this unit.  
Only qualified personnel should move, install or service this equipment.  
Adhere to all warnings, cautions and installation, operating and safety instructions on the unit and in  
this manual. Follow all operating and user instructions.  
WARNING  
!
Arc flash and electric shock hazard. Disconnect all local and remote electric power supplies  
and wear protective equipment per NFPA 70E before working within the electrical enclosure.  
Failure to comply can cause injury or death.  
Customer must provide earth ground to unit per NEC, CEC and local codes as applicable.  
Before proceeding with installation, read all instructions, verify that all the parts are included  
and check the nameplate to be sure the voltage matches available utility power.  
®
The Liebert iCOM microprocessor does not isolate power from the unit, even in the “Unit  
Off” mode. Some internal components require and receive power even during the “Unit Off”  
mode of Liebert iCOM control.  
The factory-supplied optional disconnect switch is inside the unit. The line side of this switch  
contains live high-voltage.  
The only way to ensure that there is NO voltage inside the unit is to install and open a remote  
disconnect switch and check the internal power with a voltmeter. Refer to unit electrical  
schematic.  
Follow all local codes.  
WARNING  
!
Risk of explosive discharge from high-pressure refrigerant. Can cause injury or death.  
This unit contains fluids and/or gases under high pressure.  
Relieve pressure before working with piping.  
WARNING  
equipment damage, injury or death.  
!
Risk of refrigerant system rupture or explosion from overpressurization. Can cause  
Local building or plumbing codes may require that a fusible plug or other type of pressure  
relief device be installed in the system.  
For systems requiring EU CE compliance (50Hz), the system installer must provide and  
install a discharge pressure relief valve rated for a maximum of 500psig (34bar) in the high  
side refrigerant circuit. Do not install a shutoff valve between the compressor and the  
field-installed relief valve. The pressure relief valve must be CE certified to the EU Pressure  
Equipment Directive by an EU “Notified Body.”  
NOTE  
The Liebert indoor cooling unit has a factory-installed high-pressure safety switch in the high  
side refrigerant circuit. A pressure relief valve is provided with Liebert Lee-Temp condensers.  
Consult local building codes to determine whether the Liebert Fan Speed Control and VFD  
condensers will require field-provided pressure relief devices. A fusible plug kit for Liebert FSC  
and VFD condensers is available for field installation.  
®
1
Liebert Challenger 3000  
   
Important Safety Instructions  
WARNING  
!
!
Risk of improper handling of top heavy unit. Can cause unit to fall over, resulting in  
equipment damage, serious injury or death.  
Read all instructions before attempting to move, lift, remove packaging from or preparing  
unit for installation.  
WARNING  
Risk of high-speed moving parts. Can cause injury or death.  
Disconnect all local and remote electric power supplies before working in the unit.  
Do not operate upflow units without installing a plenum, ductwork or guard over the blower  
opening(s) on the top surface of the unit cabinet for protection from rotating blower wheel(s).  
CAUTION  
!
!
Risk of contact with hot surfaces. Can cause injury.  
The compressor, refrigerant discharge lines, humidifiers and reheats are extremely hot  
during unit operation. Allow sufficient time for them to cool before working within the unit  
cabinet. Use extreme caution and wear protective gloves and arm protection when working on  
or near hot compressors, discharge lines, humidifiers and reheats.  
CAUTION  
Risk of sharp edges, splinters and exposed fasteners. Can cause injury.  
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,  
shoes and glasses should attempt to move the unit, lift it, remove packaging from or prepare  
the unit for installation.  
NOTICE  
Risk of leaking water/glycol. Can cause equipment and building damage.  
This unit requires a water/glycol. drain connection. It may also require an external  
water/glycol supply to operate.  
Improper installation, application and service practice can result in water/glycol leakage from  
the unit. Water/glycol leakage can result in severe property damage and loss of critical data  
center equipment.  
Do not locate unit directly above any equipment that could sustain water damage.  
Emerson recommends installing monitored leak detection equipment for unit and  
water/glycol supply lines.  
NOTICE  
Risk of a leaking coil due to freezing and/or corrosion. Can cause equipment and building  
damage.  
Cooling coils and piping systems that are connected to open cooling towers or other open  
water/glycol systems are at high risk of freezing and premature corrosion. Fluids in these  
systems must contain the proper antifreeze and inhibitors to prevent freezing and premature  
coil corrosion. The water or water/glycol solution must be analyzed by a competent water  
treatment specialist before startup to establish the inhibitor requirement. The water or  
water/glycol solution must be analyzed every six months to determine the pattern of inhibitor  
depletion. The complexity of water-caused problems and their correction makes it important  
to obtain the advice of a water treatment specialist and follow a regularly scheduled  
maintenance program.  
®
Liebert Challenger 3000  
2
Important Safety Instructions  
NOTICE  
Risk of damage from forklift. Can cause unit damage.  
Keep tines of the forklift level and at a height suitable to fit below the skid and/or unit to  
prevent exterior and/or underside damage.  
NOTICE  
Risk of improper storage. Can cause unit damage.  
Keep the Liebert Challenger 3000 upright, indoors and protected from dampness, freezing  
temperatures and contact damage.  
®
3
Liebert Challenger 3000  
Introduction  
1.0 INTRODUCTION  
1.1 System Descriptions  
Liebert Challenger 3000 Precision Cooling systems are available in three main system configurations:  
• self-contained system with a scroll compressor in the room unit  
• self-contained chilled water system  
• split system with an evaporator section and a remote condensing unit  
All three types are available in upflow or downflow configurations. The standard upflow configuration  
is front return. All models require three-phase power. Units are available in 208, 230, 460, or 575V,  
60Hz; and 200, 230 or 380/415V, 50Hz.  
The following features are included as standard in all room units regardless of the type of system:  
Liebert iCOM® control, A-frame coil (V-frame on upflows), infrared humidifier, finned tubular  
stainless steel electric reheat, 2" filter, individual high voltage fused protection and fan assembly.  
1.1.1 Self-Contained Systems  
Air-Cooled Models  
Complete refrigeration system including hot gas bypass and crankcase heater with standard scroll  
compressor, standard condenser and fan speed control for 95°F (35°C) ambient at sea level. Optional  
Digital scroll compressor with unloading solenoid valve is also available. Digital scroll compressor  
systems do not include hot gas bypass.  
Water-Cooled Models  
Compete refrigeration system including hot gas bypass with standard scroll compressor, water/glycol-  
cooled condenser and two-way water regulating valve with bypass. Optional digital scroll compressor  
with unloading solenoid valve is also available. Digital scroll compressor systems use a 2-way  
motorized ball valve in lieu of the regulating valve; they do not include hot gas bypass.  
Glycol-Cooled Models  
The water-cooled model as described above plus pump package and 95°F (35°C) design ambient  
drycooler.  
GLYCOOL Models (5-Ton Only)  
Complete refrigeration system including hot gas bypass with standard scroll compressor, glycol  
condenser and three-way water regulating valve plus an integrally piped Econ-O-Coil with three-way  
modulating control valve. Optional digital scroll compressor with unloading solenoid valve is also  
available. Digital scroll compressor systems use a 3-way motorized ball valve in lieu of the regulating  
valve; they do not include hot gas bypass.  
1.1.2 Chilled Water Models  
Chilled Water models include chilled water piping, three-way modulating valve, and actuator  
assembly.  
®
Liebert Challenger 3000  
4
       
Introduction  
1.1.3 Split Systems  
Each air-cooled split system consists of an evaporator section and one of the following condensing  
units.  
Prop Fan Air-Cooled  
Prop Fan units include scroll compressor, condenser coil, prop fan, high pressure switch, hot gas  
bypass and Liebert Lee-Temp head pressure control. Unit is designed for outdoor location.  
Centrifugal Fan Air-Cooled  
Centrifugal Fan units include scroll compressor, condenser coil, centrifugal blower assembly,  
high-pressure switch, hot gas bypass and Liebert Lee-Temp head pressure control. Unit must be  
mounted indoors. Duct flanges are optional.  
Water-Cooled  
Each water-cooled split system consists of an evaporator section and a water/glycol condensing unit,  
which includes scroll compressor, coaxial condenser, water regulating valve, hot gas bypass and  
high-pressure switch. Design pressure is 150 psi (1034 kPa) as standard and 350 psi (2413 kPa) as  
optional.  
Glycol-Cooled  
Each glycol-cooled split system consists of an evaporator section, a water/glycol condensing unit (as  
described above), a pump package, and a 95°F (35°C) design ambient drycooler.  
®
5
Liebert Challenger 3000  
 
Installation (Applicable to all Models)  
2.0 INSTALLATION (APPLICABLE TO ALL MODELS)  
2.1  
Room Preparation  
The room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the  
ceiling can be a polyethylene film type. Use a rubber or plastic base paint on concrete walls and floors.  
Doors should not be undercut or have grilles in them.  
Outside (or fresh) air should be kept to an absolute minimum. Outside air adds to the heating,  
cooling, humidifying and dehumidifying loads of the site. It is recommended that outside air be kept  
below 5% of the total air circulated in the room and be preconditioned.  
2.2  
2.3  
Equipment Inspection  
Upon arrival of the unit, inspect all items for visible and concealed damage. Damage should be  
immediately reported to the carrier and a damage claim filed with a copy sent to Emerson® or to your  
sales representative.  
Location Considerations  
The unit can sit on top of an accessible elevated flooring system. It may be necessary to furnish  
additional pedestal support below the unit to ensure maximum structural support (see Table 1). A  
separate floor stand for the unit may be used as support, independent of the elevated floor and  
installed prior to the flooring system.  
Provide approximately 34" (864mm) service clearance on the front of the unit.  
NOTE  
GLYCOOL units require 34" (864mm) service clearance on the right side of the unit in  
addition to front service clearance.  
Avoid placing units in an alcove or at the extreme end of a room that has a high aspect ratio (long,  
narrow room). Ducted units can be placed in room corners or ends as long as front access is  
maintained. Placing units too close together will reduce the effectiveness of the air distribution.  
NOTE  
Locate and remove shipping screw on fan motor base.  
2.4  
Equipment Handling  
WARNING  
equipment damage, serious injury or death.  
!
Risk of improper handling of top heavy unit. Can cause unit to fall over, resulting in  
Read all of the following instructions before attempting to move, lift, remove packaging from  
or preparing unit for installation.  
The instructions below are to be adhered to when handling this unit with or without the skid.  
There is the potential for this unit to tip over if it is handled improperly.  
®
Liebert Challenger 3000  
6
         
Installation (Applicable to all Models)  
2.4.1 Handling With Skid  
• Always keep the unit upright, indoors and protected from damage.  
• If possible, transport the unit using a fork lift; otherwise, use a crane with belts or cables,  
avoiding pressing on the top edges of the packaging.  
• If using a fork lift, make sure the forks, if adjustable, are spread to the widest allowable distance  
to still fit under the skid.  
NOTICE  
Risk of overhead interference. Can cause unit and/or structure damage.  
Refer to the installation plans prior to moving the unit to verify clearances.  
While on the skid, the unit is too tall to fit through a standard height doorway (83 in. or  
2108mm tall). Any attempt to move the unit, while on the skid, through a standard doorway  
will cause damage to the unit.  
2.4.2 Removal of Skid  
• Remove the plywood skirting that keeps the skid and unit in place.  
• Raise the Liebert Challenger 3000 off the skid. Emerson recommends using a fork lift (see  
Figure 1) or similar machine to ensure that the unit is lifted properly.  
• Once the unit is raised, the skid can be removed.  
Figure 1 Removing the Liebert Challenger 3000 from skid  
Raise unit with forklift  
or similar machine.  
Remove plywood skirting holding  
unit and skid in place.  
Table 1  
Model  
Unit net weight  
Lb. (kg)  
036E/035E  
535 (243)  
545 (247)  
615 (279)  
670 (304)  
700 (318)  
750 (340)  
785 (356)  
545 (247)  
555 (252)  
060E/059E  
042A/040A  
067A/065A  
046WG/045WG  
071WG/070WG  
061G/058G  
068C/072C  
102C/101C  
®
7
Liebert Challenger 3000  
       
Installation (Applicable to all Models)  
Figure 2 Upflow (BU) cabinet dimensions  
32-1/2"  
(826mm)  
A
UNIT  
30-1/2"  
STD 3 & 5T 11-3/4 (299mm)  
Hi Static 3T 8-5/8 (219mm)  
Hi Static 5T 11-3/4 (299mm)  
TOP VIEW  
(775mm)  
A
9-5/8"  
(244mm)  
8-1/2"  
(216mm)  
10-1/4"  
(260mm)  
1-5/8"  
13"  
(41mm)  
(330mm)  
30-1/2"  
(775mm)  
Standard Piping Location  
32-1/2"  
(826mm)  
12-1/2"  
(318mm)  
1-7/8"  
(48mm)  
Projection of Display  
Bezel 5/8" (16mm)  
5-1/2" (140mm)  
Standard Electrical Outlet  
Location Through Unit  
32-1/2"  
32-1/2"  
(826mm)  
Overall  
(826mm)  
Overall  
Dimension  
Dimension  
6-7/8" (175mm)  
7-1/2"  
(191mm)  
Filter Access  
Through Top  
Standard Electrical Outlet  
Location Through Plenum  
18"  
(457mm)  
Air Discharge Grille  
29-3/4"  
(756mm)  
Plenum available with:  
-2, 3 or 4 grilles.  
-Solid sides with a 7/8" (22mm)  
duct flange on top.  
1" (25mm)  
FRONT &  
SIDES  
3/4" (19mm)  
REAR  
94"  
(2388mm)  
Blower Outlet with  
1" (25.4mm) Flange  
2-1/2"  
(67mm)  
29"  
(737mm)  
76"  
(1930mm)  
7/8" (22.2mm) Flange for  
Duct or Plenum Connection  
1-3/4 "  
(44mm)  
REAR VIEW  
(rear return configuration)  
Return Air Louvers  
Shaded area indicates a recommended  
clearance of 34" (864mm) for component  
access. Right side access suggested for  
GLYCOOL units.  
DPN000350  
Rev. 1  
FRONT VIEW  
(front return configuration)  
®
Liebert Challenger 3000  
8
 
Installation (Applicable to all Models)  
Figure 3 Downflow (BF) cabinet dimensions  
32-1/2"  
(826mm)  
Overall  
32-1/2"  
(826mm)  
Overall  
Projection of Display  
Bezel 5/8" (16mm)  
Dimension  
Dimension  
30-1/2"  
(775mm)  
30-1/2"  
(775mm)  
Optional 1-5/8" (41mm)  
Flange for Duct or  
Plenum Connection  
76"  
(1930mm)  
1" (25mm) FRONT & SIDES  
3/4" (19mm) REAR  
Shaded area indicates  
a recommended clearance of  
34” (864mm) for component  
1"  
access. Right side access  
(25.4mm)  
1"  
30-1/2"  
(775mm)  
suggested for GLYCOOL units  
(25.4mm)  
30-1/2"  
(775mm)  
12"  
(305mm)  
30-1/2"  
(775mm)  
4"  
9"  
(102mm)  
(229mm)  
1"  
1" (25.4mm)  
(25.4mm)  
28-1/2"  
(724mm)  
Standard Electrical Location  
30-1/2"  
(775mm)  
Standard Piping  
Location  
8"  
Floor  
Level  
(203mm)  
FLOOR CUTOUT DIMENSIONS  
1"  
(25.4mm)  
30-1/2"  
(775mm)  
30-1/2"  
(775mm)  
See Specification  
Sheet for Floor Stand  
Height Ordered.  
DPN000351  
Rev. 1  
OPTIONAL FLOOR STAND DIMENSIONAL DATA  
®
9
Liebert Challenger 3000  
 
Installation (Applicable to all Models)  
2.5  
Piping Considerations  
All piping below the elevated floor must be located so that it offers the least resistance to air flow.  
Careful planning of the piping layout under the raised floor is required to prevent the air flow from  
being blocked. When installing piping on the subfloor, it is recommended that the pipes be mounted in  
a horizontal plane rather than stacked one above the other. Whenever possible, the pipes should be  
run parallel to the air flow.  
Condensate pumps for downflow units are shipped separately to be field-installed under the raised  
floor. Pump height is 11 in. (279mm).  
2.5.1 Drain Line  
A 3/4" (19.1mm) female pipe thread (FPT) connection is provided for the evaporator coil condensate  
drain. This drain line also drains the humidifier, if applicable. The drain line must be located so it will  
not be exposed to freezing temperatures. The drain should be at least the full size of the drain  
connection and pitched a minimum of 1/8" per ft. (11mm per meter).  
NOTICE  
Risk of water backing up in the evaporator coil drain line. Can cause the drain pan to  
overflow, resulting in building and equipment damage.  
Do not install an external trap in the drain line of units without a condensate pump. This line  
already has a factory-installed trap inside the cabinet.  
NOTICE  
Risk of drain line damage. Can cause water leaks resulting in furniture, equipment and  
building damage.  
This line may contain boiling water. Select appropriate drain system materials.  
Units with a condensate pump will require a field-supplied trap downstream from the pump.  
The drain line must comply with all applicable national, state and local plumbing codes.  
Table 2  
Piping connection size  
Air-Cooled Unit Connection Sizes—in.  
Model No. BF/BU  
(50 Hz)  
Liquid Line O.D. Copper  
Hot Gas Line OD Copper  
HG  
L
042A (040A)  
067A (065A)  
3/8  
1/2  
5/8  
7/8  
Split System Fan Coil Unit Connection Sizes—in.  
Model No. BF/BU (50 Hz)  
Liquid Line  
L
Suction Line  
SC  
036E (035E)  
060E (059E)  
5/8 - 18 Female (#6 QC)  
1/2 OD Cu  
1-1/8 - 12 Female (#11 QC)  
1-1/8 OD Cu  
All Units: Connection Sizes—in.  
Humidifier Line  
OD Copper  
H
Condensate  
Drain Line  
C
Condensate Pump Line  
Hot Water Reheat  
OD Copper  
OD Copper  
P
Supply  
HWS  
Return  
HWR  
1/4  
3/4 FPT  
1/2  
5/8  
5/8  
Water/Glycol-Cooled Unit Connection Sizes—inches  
Model No. BF/BU  
(50 Hz)  
Supply Line  
S
Return Line  
R
046WG (045WG)  
071WG (070WG)  
7/8  
7/8  
1-1/8  
1-1/8  
GLYCOOL Unit Connection Sizes —in.  
Model No. BE/BK  
(50 Hz)  
Supply Line  
Return Line  
R
S
061G (058G)  
1-1/8  
1-1/8  
®
Liebert Challenger 3000  
10  
     
Installation (Applicable to all Models)  
Table 2  
Piping connection size (continued)  
Chilled Water Unit Connection Sizes—in.  
Model No. BF/BU  
(50 Hz)  
Supply Line  
Return Line  
CWR  
CWS  
1-1/8  
1-1/8  
068C (072C)  
102C (101C)  
1-1/8  
1-1/8  
Figure 4 Piping connections for air-cooled units - Downflow models  
Liebert iCOM  
Control Panel  
Condensate Drain 3/4" FPT  
Liquid Refrigerant Line  
Field-pitch a minimum of 1/8" (3.2mm)  
per foot (305mm). The drain line  
must comply with all applicable codes.  
3/8" OD CU on Models BF042A/BF040A  
1/2" OD CU on Models BF067A/BF065A  
Hot Gas Refrigerant Line  
5/8" OD CU on Models BF042A/BF040A  
7/8" OD CU on Models BF067A/BF065A  
Hot Water Return  
5/8" OD CU (optional)  
Hot Water Supply  
5/8" OD CU (optional)  
Humidifier Water Supply Line  
1/4" OD CU  
PIPING OUTLET LOCATIONS  
(See Cabinet and Floor Planning  
Dimensional Data for Piping  
Opening Sizes.)  
DPN000353  
Rev. 1  
®
11  
Liebert Challenger 3000  
 
Installation (Applicable to all Models)  
Figure 5 Piping connections for air-cooled units - Upflow models  
Piping outlet locations through the plenum  
are the same as the unit. See below for  
descriptions and connection sizes.  
Hot Water Return  
Humidifier Water Supply Line  
1/4" OD CU  
5/8" OD CU (optional)  
Liquid Refrigerant Line  
3/8" OD CU on Models BU042A/BU040A  
1/2" OD CU on Models BU067A/BU065A  
Hot Gas Refrigerant Line  
5/8" OD CU on Models BU042A/BU040A  
7/8" OD CU on Models BU067A/BU065A  
Hot Water Supply  
5/8" OD CU (optional)  
Condensate Pump Line  
1/2" OD CU  
Used only if optional condensate  
pump is ordered.  
Liebert iCOM  
Control  
PIPING OUTLET LOCATIONS  
(See Cabinet and Floor Planning  
Dimensional Data for Piping  
Opening Sizes.)  
Condensate Drain  
3/4" FPT  
Field pitch a min. of 1/8" (3.2mm) per ft. (305mm). Units without  
a condensate pump have a factory-supplied trap in the unit, so  
do not field-install a trap in the drain line. Units with a condensate pump will  
require a field-supplied trap downstream from the pump. The  
drain line must comply with all applicable national, state and local plumbing  
codes. (If condensate pump is ordered piping is out top of unit).  
DPN000352  
Rev. 1  
®
Liebert Challenger 3000  
12  
 
Installation (Applicable to all Models)  
Figure 6 Piping connections for split system fan coil units - Downflow models  
Liebert iCOM  
Control  
PIPING OUTLET LOCATIONS  
(See Cabinet and Floor  
Planning Dimensional Data  
for Piping Opening Sizes.)  
Liquid Refrigerant Line  
Condensate Drain  
#6 Quick Connect on Models BF036E/BF035E  
1/2" OD CU on Models BF060E/BF059E  
3/4" FPT  
Field pitch a minimum  
of 1/8" (3.2mm) per ft. (305mm).  
The drainline must comply  
with all applicable codes.  
Suction Refrigerant Line  
#11 Quick Connect on Models BF036E/BF035E  
1-1/8" OD CU on Models BF060E/BF059E  
Hot Water Return  
5/8" OD CU (optional)  
Humidifier Water Supply Line  
1/4" OD CU  
Hot Water Supply  
5/8" OD CU (optional)  
DPN000376  
Rev. 1  
®
13  
Liebert Challenger 3000  
 
Installation (Applicable to all Models)  
Figure 7 Piping connections for split system fan coil units - Upflow models  
Piping outlet locations through the  
plenum are the same as the unit.  
See below for descriptions and  
connection sizes.  
Humidifier Water Supply Line  
1/4" OD CU  
Hot Water Return  
5/8" OD CU (optional)  
Suction Refrigerant Line  
Liquid Refrigerant Line  
#11 Quick Connect on Models BU036E/BU035E  
1 1/8" OD CU on Models BU060E/BU059E  
Condensate Pump Line  
#6 Quick Connect on Models BU036E/BU035E  
1/2" OD CU on Models BU060E/BU059E  
Hot Water Supply  
5/8" OD CU (optional)  
1/2" OD CU; used only  
if optional condensate pump is ordered.  
iCOM Control  
Panel  
PIPING OUTLET LOCATIONS  
(See Cabinet and Floor Planning  
Dimensional Data for Piping  
Opening Sizes.)  
Condensate Drain; 3/4" FPT  
Field pitch a min. of 1/8" (3.2mm) per ft. (305mm). Units without  
a condensate pump have a factory-supplied trap in the unit, so  
do not field-install a trap in the drain line. Units with a condensate pump will  
require a field-supplied trap downstream from the pump. The  
drain line must comply with all applicable national, state and local plumbing  
codes. (If condensate pump is ordered piping is out top of unit).  
DPN000375  
Rev. 1  
®
Liebert Challenger 3000  
14  
 
Installation (Applicable to all Models)  
Figure 8 Piping connections for water/glycol and GLYCOOL units - Downflow models  
iCOM Control  
Panel  
Condenser Supply Line  
7/8" OD CU on Models BF046WG/BF045WG  
1-1/8" OD CU on Models BF071WG/BF070WG  
Condensate Drain  
3/4" FPT  
Field pitch a minimum  
of 1/8" (3.2mm) per ft. (305mm).  
The drain line must comply with  
all applicable codes  
Condenser Return Line  
7/8" OD CU on Models BF046WG/BF045WG  
1-1/8" OD CU on Models BF071WG/BF070WG  
Hot Water Return  
5/8" OD CU (optional)  
Humidifier Water Supply Line  
1/4" OD CU  
Hot Water Supply  
5/8" OD CU (optional)  
PIPING OUTLET LOCATIONS  
(See Cabinet and Floor Planning  
Dimensional Data for Piping  
Opening Sizes.)  
DPN000364  
Rev. 1  
®
15  
Liebert Challenger 3000  
 
Installation (Applicable to all Models)  
Figure 9 Piping connections for water/glycol and GLYCOOL units - Upflow models  
Piping outlet locations through the plenum  
the same as the unit. See below for  
descriptions and connection sizes.  
Humidifier Water Supply Line  
1/4" OD CU  
Hot Water Return  
5/8" OD CU (optional)  
Condenser Supply Line  
7/8" OD CU on Models BU046WG/BU045WG  
1-1/8" OD CU on Models BU071WG/BU070WG  
Condenser Return Line  
7/8" OD CU on Models BU046WG/BU045WG  
1-1/8" OD CU on Models BU071WG/BU070WG  
Hot Water Supply  
5/8" OD CU (optional)  
Condensate Pump Line  
1/2" OD CU  
Used only if optional condensate  
pump is ordered.  
Liebert iCOM  
Control  
PIPING OUTLET LOCATIONS  
(See Cabinet and Floor Planning  
Dimensional Data for Piping  
Opening Sizes.)  
Condensate Drain  
3/4" FPT  
Field pitch a min. of 1/8" (3.2mm) per ft. (305mm). Units without  
a condensate pump have a factory-supplied trap in the unit, so  
do not field-install a trap in the drain line. Units with a condensate pump will  
require a field-supplied trap downstream from the pump. The  
drain line must comply with all applicable national, state and local plumbing  
codes. (If condensate pump is ordered piping is out top of unit).  
DPN000363  
Rev. 1  
®
Liebert Challenger 3000  
16  
 
Installation (Applicable to all Models)  
Figure 10 Piping connections for chilled water self-contained units - Downflow models  
Liebert iCOM  
Control  
PIPING OUTLET LOCATIONS  
(See Cabinet and Floor Planning  
Dimensional Data for Piping  
Opening Sizes.)  
Condensate Drain  
Chilled Water Supply Line  
1-1/8" OD CU  
3/4" FPT  
Field pitch a minimum  
of 1/8" (3.2mm) per ft. (305mm).  
The drain line must comply  
with all applicable codes.  
Chilled Water Return Line  
1-1/8" OD CU  
Hot Water Return  
5/8" OD CU (optional)  
Hot Water Supply  
5/8" OD CU (optional)  
Humidifier Water Supply Line  
1/4" OD CU  
DPN000371  
Rev. 1  
®
17  
Liebert Challenger 3000  
 
Installation (Applicable to all Models)  
Figure 11 Piping connections for chilled water self-contained units - Upflow models  
Piping outlet locations through  
the plenum are the same as the unit.  
See below for descriptions and  
connection sizes.  
Hot Water Return  
5/8" OD CU (optional)  
Humidifier Water Supply Line  
1/4" OD CU  
Chilled Water Supply Line  
1-1/8" OD CU  
Chilled Water Return Line  
1-1/8" OD CU  
Condensate Pump Line  
1/2" OD CU; used only if optional  
condensate pump is ordered.  
Hot Water Supply  
5/8" OD CU (optional)  
iCOM Control  
Panel  
PIPING OUTLET LOCATIONS  
(See Cabinet and Floor Planning  
Dimensional Data for Piping  
Opening Sizes.)  
Condensate Drain 3/4" FPT  
Field pitch a min. of 1/8" (3.2mm) per ft. (305mm). Units without  
a condensate pump have a factory-supplied trap in the unit, so  
do not field-install a trap in the drain line. Units with a condensate pump will  
require a field-supplied trap downstream from the pump. The  
drain line must comply with all applicable national, state and local plumbing  
codes. (If condensate pump is ordered piping is out top of unit).  
DPN000370  
Rev. 1  
®
Liebert Challenger 3000  
18  
 
Installation (Applicable to all Models)  
2.5.2 Humidifier Supply Water—Optional Infrared  
• 1/4" supply line; maximum water pressure is 150 psi (1034kPa)  
• Size humidifier supply line for 1 gpm (3.8 l/m), with a minimum water pressure of 20 psi (138kPa)  
• Do not supply de-ionized water to the humidifier  
2.6  
2.7  
Facility Fluid and Piping Maintenance  
Facility water and glycol quality remain a requirement throughout the life of the piping system. Fluid  
and piping system maintenance schedules must be established and performed. A local fluid  
maintenance program must be established that will evaluate fluid chemistry and apply necessary  
treatment. A periodic leak inspection of facility and unit fluid piping is recommended. Refer to 5.4 -  
Electrical Connections  
Three-phase electrical service is required for all models in either 208, 230, 460, or 575 V, 60 Hz; or  
200, 230, or 380/415 V, 50 Hz. Electrical service shall conform to national and local electrical codes.  
Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to  
electrical schematic when making connections.  
A manual electrical disconnect switch should be installed within 5 feet (1.6 m) of the unit in  
accordance with codes, or a factory-supplied disconnect switch may be factory mounted within the  
unit accessible from the exterior.  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Potentially lethal voltages exist within this equipment during operation. Observe all cautions  
and warnings on unit and in this manual.  
The Liebert iCOM® microprocessor does not isolate power from the unit, even in the “Unit Off”  
mode. The only way to ensure that there is NO voltage inside the unit is to install and open a  
remote disconnect switch and verify the absence of electrical power with a voltmeter. Refer to  
unit electrical schematic.  
WARNING  
resulting in building and/or equipment damage, injury or death.  
!
Risk of loose electrical wiring connections. Can cause overheating of wire, smoke and fire  
Use copper wire only and verify that all connections are tight.  
NOTICE  
Risk of improper scroll compressor phase sequencing. Could cause poor performance and  
compressor damage.  
Three-phase power must be connected to the unit line voltage terminals in the proper  
sequence so that the scroll compressor rotates in the proper direction. Rotation in the wrong  
direction will result in poor performance and compressor damage. Use a phase sequence and  
motor rotation sensor to ensure that the three-phase power is correctly connected and the  
compressor is rotating properly.  
®
19  
Liebert Challenger 3000  
     
Installation (Applicable to all Models)  
Figure 12 Electrical connections  
1
Electrical Handy Box *  
(Factory-Installed With Cover)  
2
14  
73  
72  
71  
3
4
70  
8
5
Terminal Block  
(for Customer Connectons  
1
7
6
13  
13  
9
9
10  
12  
11  
15 16 17  
75 76 94 95 96 97  
37C38C37B38B 37  
24  
51 55 56  
91 92  
12  
34  
82  
84  
88  
85 89  
38  
50  
93  
83  
DPN000354  
Rev. 2  
2.7.1 Electrical Field Connections for Liebert Challenger 3000 Models  
Source: DPN00354, Rev. 2  
1. Electric conduit knockouts on top and bottom of electric box. Knockout size 1-3/4" (44.5mm).  
2. Three-phase connection. Electric service connection terminals when factory disconnect is NOT  
supplied.  
3. Three-phase connection. Electric service connection terminals when factory disconnect switch  
is supplied.  
4. Factory-installed disconnect switch. (Optional).  
5. Three-phase electric service field-supplied.  
6. Earth ground connection (50/60Hz). Connection terminal for field-supplied earth grounding  
wire.  
7. Earth ground bar (50Hz only). Connection terminals with factory ground from each high  
voltage component for field-supplied earth grounding wire.  
8. Control and monitoring section of electric box.  
9. Remote unit shutdown. Replace existing jumper between Terminals 37 + 38 with normally  
closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring. Two  
additional contact pairs available as an option (labeled as 37B & 38B, 37C & 38C). Replace  
existing jumper for appropriate pair as done for 37 & 38.  
10. Special alarm connections. Field-supplied 24V Class 1 wiring for special alarm. Connection  
made by adding normally open contacts between terminals 24 + 50. Special alarm connections  
may be factory-wired or field-wired. See schematic for factory-wired special alarms. For  
field-wired special alarms, use 24V Class 1 wiring to connect normally open contacts between  
Terminals 24 & 50, 24 & 51, 24 & 55, or 24 & 56.  
11. Remote condensing unit connection. Field-supplied 24V Class 1 wiring to remote condensing  
unit Terminals 1, 2, 3, & 4 from (R2) relay (split system only).  
12. Smoke detector alarm connections. Field-supplied 24V Class 1 wiring to remote alarm  
circuits. Factory-wired contacts from optional smoke detector are #91-comm., #92-NO, and  
#93-NC.  
13. Common alarm connection. Field-supplied 24V. Class 1 wiring to common alarm  
Terminals 75 + 76 (and optional 94 + 95, and 96 + 97), which are factory-connected to common  
alarm relay (R3).  
®
Liebert Challenger 3000  
20  
   
Installation (Applicable to all Models)  
14. Heat rejection connection. Field-supplied 24V Class 1 wiring to interlock heat rejection from  
pigtails 70 + 71, which are factory-connected to compressor side switch (self-contained units only)  
or to GLYCOOL relay (K11, GLYCOOL units only). On Dual Cool units only, pigtails 72 + 73  
connect auxiliary cooling source to GLYCOOL relay K11.  
15. Reheat and Humidifier Lockout. Optional emergency power lockout of reheat and/or  
humidifier: connections provided for remote 24V AC source.  
16. Main Fan Auxiliary Switch. Optional main fan auxiliary side switch. Terminals located in field  
wiring compartment for remote indication that the evaporator fan motor/unit is On. Field to  
connect 24V maximum.  
17. Optional Condensate Alarm (Dual Float Condensate Pump only). Relay terminals located in  
field wiring compartment for remote indication.  
Refer to specification sheet for full load amp. and wire size amp. ratings.  
Figure 13 Electrical field connections for Liebert iCOM®  
24  
22  
23  
21  
22  
24  
19  
20  
25  
23  
25  
20  
19  
DPN001734  
Rev. 0  
DPN001733  
Rev. 0  
Upflow Models with Liebert iCOM  
Downflow Models with Liebert iCOM  
18. Network Cable “C” Connection. Eight-wire Ethernet cable from U2U networking switch.  
19. Network Cable “D” connection. Eight-wire Ethernet cable from U2U networking switch.  
Cable “D” connection supplied on units with large Liebert iCOM display only.  
20. Opening for Field Wiring. Suggested entry point for all field wiring to unit. Hole size Ø2.5"  
(63.5mm).  
21. Loose Wire Ties. To secure field-supplied network cables. Tighten after all field-supplied wires  
have been installed.  
22. Vacant Liebert IntelliSlot®. May contain optional Liebert IntelliSlot cards.  
23. Populated Liebert IntelliSlot. Optional Liebert IntelliSlot cards may be placed in either of the  
two supplied Liebert IntelliSlot locations.  
24. Remote Temperature / Humidity Sensor Connection. Six-wire CAN cable supplied with  
optional remote T/H sensor  
®
21  
Liebert Challenger 3000  
 
Installation (Applicable to all Models)  
2.8  
Balancing the Air Distribution  
2.8.1 Under-Floor Discharge Systems  
The systems are designed for constant air delivery, therefore any unusual restrictions within the air  
circuit must be avoided. For under-floor air distribution, observe the following guidelines:  
• Select the air supply grilles and perforated panels for the raised floor to ensure minimum loss of  
pressure in the circuit. Air volume dampers on grilles, which extend several inches below the  
surface of the raised floor, are usually detrimental to airflow.  
• Consideration of the height of the damper on the grille in conjunction with the floor height will  
determine whether this type of grille may be used.  
• The grilles used in raised floors vary in size, the largest being approximately 18" x 6"  
(457 x 152 mm). A larger grille size would be detrimental to the structural capacity of the raised  
floor panel. An 18" x 6" (457 x 152mm) heavy duty, pencil-proof type grille typically has 56 square  
2
inches (0.036 m ) of free area.  
• Perforated panels are available from various manufacturers of raised floors. These panels are  
usually 2' x 2' (610 x 610mm) square and have a nominal free area of approximately 108 to  
2
144 square inches (0.07 to 0.09m ). Use caution in selecting perforated panels as some  
2
manufacturers have only 36 to 40 square inches (0.023 to 0.026m ) of free area, requiring four  
times as many panels.  
• Avoid floor elevations below 7-1/2" (190.5mm), loosely installed flooring systems, and below-floor  
obstructions such as: electrical wiring chases, unusually long electronic system cables, or piping  
clusters.  
• Always check specifications of the floor supplier before specifying the total number of perforated  
panels and grilles required to handle the air flow. The proper specifications for grilles and  
perforated panels should indicate the total free area required for air delivery rather than the  
number of panels and grilles. (See Table 3 for recommended free area required for each model.)  
This table indicates the recommended free area based on having the supply air grilles and  
perforated panels sized to handle approximately 75% of the total cubic feet per minute (CFM) of  
the units at a velocity of 550 to 600 ft./min. (2.8 - 3.1 m/s). The remaining 25% of the air flow in  
the raised floor passes through cable cutouts, cracks between the panels, and other leakage areas.  
2
2
Table 3  
Recommended free area ft (m ) for grilles or perforated panels at output velocities of  
550 and 600 fpm (2.8 and 3.1 m/s)  
50 Hz Units  
60 Hz Units  
550  
FPM  
2.8  
m/s  
600  
FPM  
3.1  
m/s  
550  
FPM  
2.8  
m/s  
600  
FPM  
3.1  
m/s  
Model  
3-ton  
5-ton  
Model  
3-ton  
5-ton  
2.5  
3.5  
(0.01)  
(0.02)  
2.3  
3.3  
(0.01)  
(0.02)  
2.5  
3.8  
(0.01)  
(0.02)  
2.3  
3.5  
(0.01)  
(0.02)  
2.8.2 Ducted Applications  
For ducted supply applications on upflow units, the duct work should be attached to the blower  
discharge flanges of the unit. For ducted return air applications, the duct work should be attached to  
the filter box flanges on upflow rear return units and on the unit top flange for downflow units. Refer  
to Figure 2 for information on upflow units and to Figure 3 for downflow units.  
The duct work on upflow units must allow access to the motors/blowers for maintenance. The duct  
work on upflow units must be designed within the capacity of the unit, otherwise air flow and  
performance will be compromised.  
2.8.3 Plenum Installation  
A solid plenum or plenum with discharge grille(s) may be installed. The plenum and instructions for  
its installation ship separately from the unit.  
®
Liebert Challenger 3000  
22  
         
Installation (Applicable to all Models)  
2.9  
Checklist for Completed Installation  
___ 1. Unpack and check received material.  
___ 2. Proper clearance for service access has been maintained around the equipment.  
___ 3. Equipment is level and mounting fasteners are tight.  
___ 4. Piping completed to refrigerant or coolant loop (if required). Piping has been leak checked,  
evacuated and charged (if required).  
___ 5. Check piping within the unit & outside of the unit. Remove potential of rub-through or  
chaffing.  
___ 6. Condensate pump installed (if required).  
___ 7. Drain line connected and checked for leaks.  
___ 8. Water supply line connected to humidifier and/or water/glycol condenser (if required) and  
checked for leaks.  
___ 9. Field provided pan with drain installed under all ceiling mounted fluid condensing units (if  
installed).  
___ 10. Filter box installed (if applicable).  
___ 11. Ducting completed (if applicable).  
___ 12. Filter(s) installed.  
___ 13. Line voltage to power wiring matches equipment serial tag.  
___ 14. Power wiring connections completed between disconnect switch, evaporator and condensing  
unit, including earth ground.  
___ 15. Power line circuit breakers or fuses have proper ratings for equipment installed.  
___ 16. Control wiring connections completed to evaporator and condensing unit.  
___ 17. Verify water detection is properly installed around all units (if installed).  
___ 18. All wiring connections are tight.  
___ 19. Control panel DIP switches set based on customer requirements.  
___ 20. Foreign materials have been removed from, in and around all equipment installed (literature,  
shipping materials, construction materials, tools, etc.).  
___ 21. Fans and blowers rotate freely.  
___ 22. Inspect all piping connections for leaks during initial operations. Correct as needed.  
___ 23. Verify that a blank startup sheet has been sent with the unit(s) and is ready to be completed  
by the installer.  
___ 24. Rubber band removed from humidifier and/or evaporator pan float switch (if supplied).  
®
23  
Liebert Challenger 3000  
 
Air-Cooled Models—Self-Contained Compressor  
3.0 AIR-COOLED MODELS—SELF-CONTAINED COMPRESSOR  
3.1 Condenser Location  
The air-cooled condenser should be located for maximum security and maintenance accessibility.  
Avoid ground level sites with public access or areas that contribute to heavy snow or ice  
accumulations. Utilize centrifugal condensers whenever interior building locations must by used. To  
assure adequate air supply, it is recommended that condensers be located in a clean air area, away  
from loose dirt and foreign matter that may clog the coil. In addition, condensers should not be located  
in the vicinity of steam, hot air, or fume exhausts. Also, condensers should be located no closer than  
three feet (1 meter) from a wall, obstruction, or adjacent unit.  
NOTE  
If the condenser is located below the level of the room unit, the factory should be consulted.  
Install condensers in a level position to assure proper refrigerant flow and oil return. For roof  
installation, mount condensers on steel supports in accordance with local codes. To minimize sound  
and vibration transmission, mount steel supports across load bearing walls. For ground installation, a  
concrete pad will provide adequate support. Condenser legs have mounting holes for securing the  
condenser to the steel supports or concrete pad.  
3.2  
Electrical Connections  
Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to  
electrical schematic when making connections. Make all wiring and electrical connection in  
accordance with local and national codes.  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Potentially lethal voltages exist within this equipment during operation. Observe all cautions  
and warnings on unit and in this manual.  
The Liebert iCOM® microprocessor does not isolate power from the unit, even in the “Unit  
Off” mode. The only way to ensure that there is NO voltage inside the unit is to install and  
open a remote disconnect switch. Refer to unit electrical schematic.  
Use voltmeter to make sure power is turned Off before making any electrical connections.  
3.2.1 Line Voltage  
Line voltage electrical service is required for all air-cooled condensers at the location of the condenser.  
This power supply does not have to be the same voltage as the indoor unit. This separate power source  
may be 208, 230, 460, or 575 V, 60 Hz; or 200, 230, or 380/415 V, 50 Hz. The disconnect switch may be  
factory-supplied and mounted in the electrical panel or field-supplied and mounted per local and  
national codes.  
WARNING  
resulting in building and/or equipment damage, injury or death.  
!
Risk of loose electrical wiring connections. Can cause overheating of wire, smoke and fire  
Use copper wire only and verify that all connections are tight.  
3.2.2 Low Voltage  
A control interlock between the condenser and the indoor unit is required and is connected between  
70 and 71 in the handy box of the indoor unit and the electric panel of the air-cooled condenser. NEC  
Class 1 wiring is required.  
3.2.3 Liebert Lee-Temp/Flood Back Head Pressure Control Condensers  
Liebert Lee-Temp condensers require a separate power supply for the heated receivers. This power  
supply is connected to the electrical connection box on the end of the receiver.  
®
Liebert Challenger 3000  
24  
           
Air-Cooled Models—Self-Contained Compressor  
Figure 14 Air-cooled condensers  
FAN SPEED AND VFD CONDENSER  
LIEBERT LEE-TEMP CONDENSER  
Liebert Lee-Temp heater  
pad connection box  
* B  
Hot gas  
line  
Electric service  
supplied by  
others  
Electric  
service  
supplied by  
* B  
others  
Liquid line  
Hot gas line  
*B - Inverted traps are to be field-supplied and installed  
(typ). When installing traps, provide clearance for swing  
end of access door. Traps are to extend above base of  
coil by a minimum of 7-1/2" (190mm)  
Liquid line  
Secure each leg to condenser frame at all  
points shown using hardware provided.  
SINGLE FAN AIR-COOLED CONDENSERS  
43-9/16"  
(1106mm)  
51-7/16"  
(1306.5mm)  
18" (457.2mm)  
37-7/8"  
(962mm)  
CONDENSER MOUNTING  
1" typ.  
(25.4mm)  
1-3/4"  
(44.5mm)  
43-3/16"  
44"  
(1097mm)  
(1118mm)  
9/16" (14.3mm)  
diameter holes  
8 places for  
1/2" (12.7mm)  
diameter bolts  
1" typ.  
(25.4mm)  
37-11/16"  
(957.3mm)  
1"  
1-3/4"  
4-1/4"  
(25.4mm) (44.5mm) (108mm)  
1-3/4"  
(44.5mm)  
1-3/4"  
(44.5mm)  
1-3/4"  
(44.5mm)  
4-1/4"  
(108mm)  
1"  
A
(25.4mm)  
Common to all models. See Table 4  
below for key to “A” dimension.  
TYPICAL FOOTPRINT  
Table 4  
Air-cooled condenser statistics  
Connection Sizes  
(OD Copper)  
Number  
of Fans  
Net Weight  
lb (kg)  
“A” Dimension  
in (mm)  
Model  
083  
Hot Gas (in.)  
7/8  
Liquid (in.)  
1
1
2
5/8  
5/8  
7/8  
295 (133.8)  
315 (142.8)  
425 (193)  
42 (1067)  
42 (1067)  
82 (2083)  
104  
1-1/8  
165  
1-1/8  
®
25  
Liebert Challenger 3000  
   
Air-Cooled Models—Self-Contained Compressor  
3.3  
Refrigerant Piping  
All refrigeration piping should be installed with high temperature brazed joints. Prevailing good  
refrigeration practices should be employed for piping supports, leak testing, dehydration and  
charging of the refrigeration circuits.  
Unit refrigeration components and piping are shipped from the factory with a nitrogen holding  
charge.  
WARNING  
!
Risk of explosive discharge from high-pressure refrigerant. Can cause injury or death.  
This unit contains fluids and gases under high pressure. Relieve pressure before working with  
piping.  
NOTICE  
Risk of improper installation. Can cause equipment and property damage.  
The refrigeration piping should be isolated from the building by the use of vibration isolating  
supports.  
When installing field piping, care must be taken to protect all refrigerant lines from the  
atmosphere, especially when using refrigerants with POE oils. Do not allow the piping to  
stand open to air for more than 15 minutes. Units designed for R407C have a compressor that  
contains POE oil that is very hygroscopic; that is, it quickly absorbs water from the air. The  
longer the compressor piping is left open to air, the harder it will be to fully evacuate. If left  
open too long, the POE oil may need to be replaced before achieving the required vacuum  
level.  
Keep the evaporator unit and condenser closed with their factory charge of dry nitrogen while  
all field piping is installed. Keep the field piping clean and dry during installation, and do not  
allow it to stand open to the atmosphere. When all the field interconnecting piping is in place,  
vent the condenser dry nitrogen charge and connect to the field piping. Finally, vent the  
evaporator unit dry nitrogen charge and make its piping connections last.  
Follow all proper brazing practices including a dry nitrogen purge to maintain system  
cleanliness.  
NOTE  
Piping, including inverted trap(s), must be routed to allow unobstructed access to the panel  
per the NEC.  
Traps should be installed in the hot gas line on vertical risers at the base and every 25 feet (7.6m) in  
elevation. These traps will collect condensed refrigerant and refrigerant oil during the Off cycle of the  
unit and ensure flow of refrigerant oil during operation.  
A check valve is factory-supplied with the unit to be field-installed on the discharge side of the scroll  
compressor. Be sure to install the check valve with the refrigerant flow in the proper direction. When  
soldering or brazing the valve, it is very important to protect the internal parts by wrapping the valve  
with a damp cloth to keep the valve temperature below 250°F (121°C).  
Approval is required whenever:  
• a refrigerant piping run exceeds 150 ft. (46 m) equivalent length  
• an R407C system condenser must be located below the level of the cooling coil.  
Total discharge line pressure drop must not exceed 10 PSIG (69 kPa).  
Consult your local Emerson® representative when considering installations outside these guidelines.  
®
Liebert Challenger 3000  
26  
 
Air-Cooled Models—Self-Contained Compressor  
Table 5  
Recommended line sizes — OD copper, inches *  
3.5-ton 042A (040A)  
Hot Gas Line Liquid Line  
5/8 1/2  
5-ton 067A (065A)  
Hot Gas Line Liquid Line  
Equivalent Length  
50 ft. (15 m)  
100 ft. (30 m)  
150 ft. (45 m)  
7/8  
7/8  
7/8  
1/2  
5/8  
5/8  
3/4  
3/4  
1/2  
5/8  
*Recommended vertical line sizes must be used for proper oil return at all cooling and dehumidification steps.  
Table 6  
Equivalent lengths (feet) for various pipe fittings  
Copper Pipe  
O.D. in.  
90 Degree  
Elbow Copper Elbow Cast  
90 Degree  
45 Degree  
Elbow  
Gate  
Tee Valve  
Globe Angle  
Valve  
Valve  
1/2  
5/8  
0.8  
0.9  
1.3  
1.4  
1.5  
1.8  
2.2  
2.9  
3.5  
0.4  
0.5  
0.6  
0.8  
1.0  
1.3  
1.6  
2.5  
2.5  
2.5  
3.6  
4.6  
6.4  
7.2  
0.26  
0.28  
0.3  
7.0  
4.0  
9.5  
5.0  
3/4  
1.0  
12.0  
17.2  
22.5  
32.0  
36.0  
6.5  
7/8  
1.45  
1.85  
2.4  
0.36  
0.48  
0.65  
0.72  
9.5  
1-1/8  
1-3/8  
1-5/8  
12.0  
16.0  
19.5  
2.9  
Refrigerant trap = 4 times equivalent length of pipe per this table.  
Table 7  
Indoor unit refrigerant charge  
R407C  
Approximate Charge  
lb (kg)  
Model  
42A/40A  
67A/65A  
0.9 (0.4)  
1.4 (0.6)  
Table 8  
Line charges - refrigerant per 100 ft. (30 m) of Type “L” copper tube  
R407C  
Liquid Line  
lb (kg)  
Hot Gas Line  
lb (kg)  
O.D.  
1/2"  
5/8"  
3/4"  
7/8"  
7.3 (3.3)  
11.7 (5.3)  
16.6 (7.5)  
24.4 (11.1)  
1.3 (0.6)  
2.1 (1.0)  
3.0 (1.4)  
4.4 (2.0)  
Table 9  
Condenser refrigerant (per serial tag)  
R407C  
Approximate Charge  
lb (kg)  
Liebert  
Lee-Temp *  
Model  
083  
Fan Speed  
5 (2.3)  
26 (11.8)  
104  
8 (3.6)  
37 (16.8)  
165  
15 (6.8)  
50 (22.7)  
* Charge includes the receiver charge.  
®
27  
Liebert Challenger 3000  
         
Air-Cooled Models—Self-Contained Compressor  
3.4  
Fan Speed Control Systems  
The Variable Fan Speed Control systems (FSC & VFD) uses pressure-activated electronic fan speed  
control systems and remotely located thermostat(s) to ensure operation at ambient temperatures as  
low as 0°F (-18°C). For this ambient temperature range, the VFD Control Condenser must be used  
with digital scroll indoor units and can be used for energy savings with any Liebert Challenger 3000™  
unit.  
Variable Fan Speed Control Piping  
A discharge line and a liquid line must be field-installed between the indoor unit and the outdoor  
condenser. See Figures 15 and 16 for details.  
Variable Fan Speed Control Materials Supplied  
• Built-in, pre-wired condenser control box  
• Air-Cooled condenser  
• Piping access cover to be reinstalled when piping is complete  
• Bolts—four per leg (3/8" x 5/8")  
• Terminal block for two-wire, 24V interlock connection between unit and condenser  
• Condenser legs—four with 1-fan, 2-fan and 3-fan models; six with 4-fan models  
Variable Fan Speed Control Leak Check and Evacuation Procedure  
Proper leak check and evacuation can be accomplished only with all system solenoid valves open and  
check valves accounted for.  
NOTE  
Systems with a scroll or digital scroll compressor include a factory-installed check valve and  
an additional downstream Schrader valve with core in the compressor discharge line. Proper  
evacuation of the condenser side of the compressor can be accomplished only using the  
downstream Schrader valve. See piping schematic (Figures 15 and 16).  
1. If unit power is available, open the unit liquid line solenoid valves using the evacuation function  
in the diagnostic section of the Liebert iCOM® control (refer to the Liebert iCOM user manual,  
SL-18835). If unit power is not available, a field-supplied 24VAC / 75VA power source must be  
directly connected to each of the unit solenoid valves.  
2. For scroll and digital scroll compressors, connect refrigerant gauges to the suction rotalock valves  
and discharge line Schrader valves (see Note above) on the compressor.  
3. Open the service valves and place a 150 PSIG (1034 kPa) of dry nitrogen with a tracer of  
refrigerant. Check system for leaks with a suitable leak detector.  
4. After completion of leak testing, release the test pressure (per local code) and pull an initial deep  
vacuum on the system with a suitable pump.  
5. After four hours, check the pressure readings and, if they have not changed, break vacuum with  
dry nitrogen. Pull a second and third vacuum to 250 microns or less. Recheck the pressure after  
two hours. After completing this step, proceed to Variable Fan Speed Charging on page 29.  
®
Liebert Challenger 3000  
28  
 
Air-Cooled Models—Self-Contained Compressor  
Variable Fan Speed Charging  
1. Check unit nameplate for refrigerant type to be used. Unit control configurations differ depending  
on refrigerant type.  
2. Refrigerant charging requires unit operation. Refer to 2.9 - Checklist for Completed  
3. Calculate the amount of charge for the system. Refer to the unit, condenser and refrigerant line  
charge data in Tables 6, 7, 8 and 9.  
4. Weigh in as much of the system charge as possible before starting the unit.  
NOTICE  
Risk of improper refrigerant charging. Can cause equipment damage.  
Refrigerant R407C is a blend of three components and must be introduced and charged from  
the cylinder only as a liquid.  
When adding liquid refrigerant to an operating system, it may be necessary to add the  
refrigerant through the compressor suction service valve. Care must be exercised to avoid  
damage to the compressor. Emerson recommends connecting a sight glass between the  
charging hose and the compressor suction service valve. This will permit adjustment of the  
cylinder hand valve so that liquid can leave the cylinder while allowing vapor to enter the  
compressor.  
5. Turn On unit disconnect switch. Operate the unit for 30 minutes using the charging function for  
the system in the diagnostic section of the Liebert iCOM® control (see Liebert iCOM user manual,  
SL-18835). The charging function operates the compressor at full capacity and energizes the  
blower motor and the liquid line solenoid valve. The reheat and humidifier are disabled. A  
minimum 20psig (138kPa) must be established and maintained for the compressor to operate.  
The charging function can be reset as many times as required to complete unit charging.  
Table 10 Fan speed suction pressure transducer settings  
R-407C  
Gauge (Sea Level)  
psiG (kPa)  
20 (138)  
Absolute  
psiA (kPa)  
35 (241)  
80 (552)  
50 (344)  
67 (461)  
Function  
Pump-Down Cutout  
Pump-Down Reset  
65 (448)  
Minimum to Start-Cooling  
Low-Pressure Cutout (DX only)  
35 (241)  
52 (358)  
6. Charge the unit until the liquid line sight glass becomes clear. Then add one additional pound  
(2.2kg) of refrigerant.  
NOTE  
A digital scroll compressor will have a clear sight glass only when operating at 100% capacity.  
When operating below 100%, the sight glass may show bubbles with each 15-second unloading  
cycle.  
7. As head pressure builds, the variable fan speed controlled condenser fan begins rotating. The fan  
will run at full speed when sufficient head pressure is developed—fan starts to rotate at 190 psig  
(1310 kPA) and is full speed at 250 psig (1724 kPA).  
®
29  
Liebert Challenger 3000  
   
Air-Cooled Models—Self-Contained Compressor  
Figure 15 General arrangement—Air-cooled models with fan speed control  
Condenser  
Coil  
Schrader  
Valve  
* Inverted trap on  
discharge and liquid lines  
to extend above base of  
coil by a minimum  
Schrader  
Valve  
of 7-1/2" (190mm)  
Optional Field-Installed  
Fusible Plug  
* For rises over  
25ft. (7.6m), trap  
every 20ft. (6m) or  
at evenly spaced  
points  
Evaporator  
Coil  
Hot Gas  
Bypass  
Valve  
Expansion  
Valve  
Liquid Return  
Solenoid  
Valves  
Sensing  
Bulb  
Sight  
Glass  
Shutoff*  
Valve  
Filter  
Drier  
External  
Equalizers  
Service  
Valves  
Hot Gas  
Bypass  
Scroll  
Compressor  
Check  
Valve  
SINGLE CIRCUIT SHOWN  
FACTORY PIPING  
Hot Gas  
Discharge  
FIELD PIPING  
* Components are not supplied by Liebert but  
are recommended for proper circuit operation  
and maintenance.  
* Trap at base  
of risers longer  
than 5ft. (1.5m)  
DPN000349  
Rev. 5  
®
Liebert Challenger 3000  
30  
 
Air-Cooled Models—Self-Contained Compressor  
Figure 16 General arrangement—Air-cooled models with digital scroll and fan speed control  
Condenser  
Coil  
Schrader  
Valve  
* Inverted trap on  
discharge and liquid lines  
to extend above base of  
coil by a minimum  
Schrader  
Valve  
of 7-1/2" (190mm)  
Optional Field-Installed  
Fusible Plug  
* For rises over  
25ft. (7.6m), trap  
every 20ft. (6m) or  
at evenly spaced  
points  
Evaporator  
Coil  
Expansion  
Valve  
Liquid Return  
Solenoid  
Valve  
Sensing  
Bulb  
Sight  
Glass  
Shutoff*  
Valve  
Filter  
Drier  
External  
Equalizers  
Service  
Valves  
Digital  
Solenoid Valve  
Digital  
Compressor  
Check  
Valve  
SINGLE CIRCUIT SHOWN  
FACTORY PIPING  
Hot Gas  
Discharge  
FIELD PIPING  
* Components are not supplied by Liebert but  
are recommended for proper circuit operation  
and maintenance.  
* Trap at base  
of risers longer  
than 5ft. (1.5m)  
DPN001726  
Rev. 2  
®
31  
Liebert Challenger 3000  
 
Air-Cooled Models—Self-Contained Compressor  
3.5  
Air-Cooled Condenser with Liebert Lee-Temp “Flooded Condenser” Head  
Pressure Control System  
The Liebert Lee-Temp system consists of a modulating type head pressure control valve and insulated  
receivers with heater pads to ensure operation at ambient temperatures as low as -30°F (-34.4°C).  
The Liebert Lee-Temp system can be used with any compressor choice.  
Liebert Lee-Temp Piping  
A discharge line and a liquid line must be field-installed between the indoor unit and the outdoor  
condenser. See Figures 17 and 18 for details.  
Liebert Lee-Temp Controlled Materials Supplied  
• Built-in, pre-wired condenser control box  
• Air-Cooled condenser  
• Piping access cover to be reinstalled when piping is complete (models with one to four fans only)  
• Bolts—four per leg (3/8" x 5/8")  
• Terminal block for two-wire, 24V interlock connection between unit and condenser  
• Condenser legs—four with 1-fan, six on two-, three- and six-fan models and eight on four- and  
eight-fan models  
• Bolts—six per receiver (3/8" x 1")  
• Liebert Lee-Temp system:  
• Insulated storage receiver  
• Head pressure control valve with integral check valve  
• Service valve  
• Pressure relief valve  
• Liquid level sight glass  
• Check valve  
NOTE  
Liebert Lee-Temp heater pads require a separate, continuous electrical source. See nameplate  
on unit for proper voltage.  
Liebert Lee-Temp Leak Check and Evacuation Procedure  
Proper leak check and evacuation can be accomplished only with all system solenoid valves open and  
check valves accounted for.  
NOTE  
Systems with scroll or digital scroll compressors include a factory-installed check valve and an  
additional downstream Schrader valve with core in the compressor discharge line. Proper  
evacuation of the condenser side of the compressor can be accomplished only using the  
downstream Schrader valve. See piping schematic (Figure 18).  
1. If unit power is available, open the unit liquid line solenoid valves using the evacuation function  
in the diagnostic section of the Liebert iCOM® control. If unit power is not available, a field-  
supplied 24VAC / 75VA power source must be directly connected to each of the unit solenoid  
valves.  
2. Attach a jumper hose from the service valve fitting on the outlet of the receiver and the Schrader  
fitting on the discharge header of the condenser. Front-seat the service valve approximately  
two (2) turns.  
3. For scroll and digital scroll compressors, connect refrigerant gauges to the suction rotalock valves  
and discharge line Schrader valves (see Note above).  
4. Open the service valves and place a 150 PSIG (1034 kPa) of dry nitrogen with a tracer of  
refrigerant. Check system for leaks with a suitable leak detector.  
5. After completion of leak testing, release the test pressure (per local code) and pull an initial deep  
vacuum on the system with a suitable pump.  
®
Liebert Challenger 3000  
32  
 
Air-Cooled Models—Self-Contained Compressor  
6. After four hours, check the pressure readings and, if they have not changed, break vacuum with  
dry nitrogen. Pull a second and third vacuum to 250 microns or less. Recheck the pressure after  
two hours.  
7. Remove the jumper hose installed previously from between the service valve fitting and the  
condenser. After completing this step, proceed to Liebert Lee-Temp Charging.  
Liebert Lee-TempCharging  
1. Check unit nameplate for refrigerant type to be used. Unit control configurations differ depending  
on refrigerant type.  
2. Refrigerant charging requires unit operation. Refer to 2.9 - Checklist for Completed  
3. Calculate the amount of charge for the system. Refer to the unit, condenser and refrigerant line  
charge data in Tables 6, 7, 8 and 9.  
4. Weigh in as much of the system charge as possible before starting the unit.  
NOTICE  
Risk of improper refrigerant charging. Can cause equipment damage.  
Refrigerant R407C is a blend of three components and must be introduced and charged from  
the cylinder only as a liquid.  
When adding liquid refrigerant to an operating system, it may be necessary to add the  
refrigerant through the compressor suction service valve. Care must be exercised to avoid  
damage to the compressor. Emerson recommends connecting a sight glass between the  
charging hose and the compressor suction service valve. This will permit adjustment of the  
cylinder hand valve so that liquid can leave the cylinder while allowing vapor to enter the  
compressor.  
5. Turn on unit disconnect switch. Operate the unit for 30 minutes using the charging function for  
the system in the diagnostic section of the Liebert iCOM® control. The charging function operates  
the compressor at full capacity and energizes the blower motor and liquid line solenoid valve. The  
reheat and humidifier are disabled. A minimum 20psig (138kPa) must established and  
maintained for the compressor to operate. The charging function can be reset as many times as  
required to complete unit charging.  
Table 11  
Liebert Lee-Temp suction pressure transducer settings  
R-407C  
Gauge Reading  
(Sea Level)  
psiG (kPa)  
20 (138)  
Absolute  
Function  
psiA (kPa)  
35 (241)  
80 (552)  
65 (448)  
67 (461)  
Pump-Down Cutout  
Pump-Down Reset  
65 (448)  
Minimum to Start-Cooling  
Low-Pressure Cutout (DX only)  
50 (345)  
52 (358)  
6. Charge the unit until the liquid line sight glass becomes clear. Then add one additional pound  
(2.2 kg) of refrigerant.  
NOTE  
A digital scroll compressor will have a clear sight glass only when operating at 100% capacity.  
When operating below 100%, the sight glass may show bubbles with each 15-second unloading  
cycle.  
®
33  
Liebert Challenger 3000  
   
Air-Cooled Models—Self-Contained Compressor  
Liebert Lee-Temp Receiver Refrigerant Level  
On each receiver at the condenser are two refrigerant-level sight glasses. Refrigerant level will vary  
with outside temperature. Check refrigerant level after the unit has been on for at least 15 minutes.  
Sight Glass Levels  
40°F (4.5°C) and lower—bottom sight glass is 3/4 full  
40 to 60°F (4.5 to 15.5°C)—bottom sight glass is full  
60°F (15.5°C) and higher—top sight glass is 3/4 full.  
Figure 17 General arrangement—Air-cooled models with Liebert Lee-Temp  
Condenser Coil  
Inverted trap * on  
discharge and liquid  
lines to extend above base  
of coil by a minimum  
of 7-1/2" (190mm)  
**Piping Assembly  
**Rotalock Valve  
Check  
Valve  
Head Pressure  
Control with  
Integral Check  
Valve  
1/4" ( 6.4mm)  
Pressure Relief  
Valve * *  
Liebert  
Lee-Temp  
Receiver  
Sight Glass  
* For rises over  
25ft. (7.6m), trap  
every 20ft. (6m) or  
at evenly spaced  
points (hot gas  
line only)  
Liquid Return  
from  
Condenser  
Evaporator  
Coil  
Expansion  
Valve  
Hot Gas  
Bypass  
Valve  
Solenoid  
Valves  
Sensing Bulb  
Shutoff  
Valve *  
Sight Glass  
Liquid Return  
External  
Equalizers  
Service  
Valves  
Hot Gas  
Bypass  
Scroll  
Compressor  
* Components are not supplied by Liebert  
but are recommended for proper  
circuit operation and maintenance.  
** Components supplied by Liebert  
and must be field-installed.  
Check  
Valve  
Hot Gas Discharge  
* Trap at base  
of risers longer  
than 5ft. (1.5m)  
FACTORY PIPING  
OPTIONAL PIPING  
FIELD PIPING  
DPN000674  
Rev. 3  
®
Liebert Challenger 3000  
34  
 
Air-Cooled Models—Self-Contained Compressor  
Figure 18 General arrangement—Air-cooled models with digital scroll and Liebert Lee-Temp  
Condenser Coil  
Inverted trap * on  
discharge and liquid  
lines to extend above base  
of coil by a minimum  
of 7-1/2" (190mm)  
Piping Assembly **  
Check Valve  
Rotalock Valve **  
1/4" ( 6.4mm)  
Head Pressure  
Control with  
Integral Check  
Valve  
Pressure Relief  
Valve * *  
Liebert  
Lee-Temp  
Receiver  
Sight Glass  
* For rises over  
25ft. (7.6m), trap  
every 20ft. (6m) or  
at evenly spaced  
points (hot gas  
line only)  
Evaporator Coil  
Liquid Return  
from Condenser  
Expansion Valve  
Solenoid Valve  
Sensing Bulb  
Shutoff  
Valve *  
Sight Glass  
External Equalizer  
Liquid Return  
Filter  
Drier  
Service  
Valves  
Digital  
Solenoid Valve  
Digital  
Compressor  
* Components are not supplied by Liebert  
but are recommended for proper  
circuit operation and maintenance.  
** Components supplied by Liebert  
and must be field-installed.  
Check  
Valve  
Hot Gas Discharge  
FACTORY PIPING  
* Trap at base  
of risers longer  
than 5ft. (1.5m)  
OPTIONAL PIPING  
FIELD PIPING  
DPN001725  
Rev. 1  
®
35  
Liebert Challenger 3000  
 
Water-Cooled Models—Self-Contained Compressor  
4.0 WATER-COOLED MODELS—SELF-CONTAINED COMPRESSOR  
4.1 Piping Considerations  
Manual shutoff valves should be installed at the supply and return lines of each unit. This will  
provide for routine maintenance or emergency isolation of the unit.  
When the water source for the condenser is of poor quality, it is good practice to provide cleanable  
filters in the supply line. These filters will trap the particles in the water supply and extend the  
service life of the water-cooled condenser.  
To provide for the emergency of water leaks and the consequences of sub-floor flooding, floor drains  
should be provided with wet traps or a water detection system such as a Liebert Liqui-tect® sensor  
that is installed near the base of the unit or below the elevated floor.  
4.2  
Condenser  
The condenser is designed to operate in conjunction with either a cooling tower or city water. The  
maximum water pressure is 150 psig (1034 kPa). A high pressure system rated at 350 psig (2413 kPa)  
is available as an option.  
®
Liebert Challenger 3000  
36  
     
Water-Cooled Models—Self-Contained Compressor  
Figure 19 General arrangement—Water-cooled models with scroll compressor  
Evaporator  
Coil  
Expansion  
Valve  
Sensing  
Bulb  
Sight  
Glass  
External  
Equalizers  
Hot Gas  
Bypass  
Valve  
Filter  
Dryer  
Service  
Valves  
Hot Gas  
Bypass  
Solenoid  
Valve  
Scroll  
Compressor  
Hot Gas  
Bypass  
Tube  
in Tube  
Condenser  
Bypass  
Valve  
Tube  
in Tube  
Fluid  
Supply  
To  
Condenser  
Fluid  
Return  
From  
Unit  
Unit  
2-Way Water  
Regulating  
Valve  
Shutoff*  
Valves  
3-Way Water  
Regulating Valve  
(optional)  
Fluid  
Supply  
To  
Unit  
* Components are not supplied  
by Liebert but are recommended  
for proper circuit operation  
and maintenance.  
Hose Bibs*  
Field-Supplied  
Reducers  
Fluid  
Return  
From  
Unit  
Required  
on 3-Ton Units  
FACTORY PIPING  
FIELD PIPING  
DPN000359  
Rev. 2  
®
37  
Liebert Challenger 3000  
 
Water-Cooled Models—Self-Contained Compressor  
Figure 20 General arrangement diagram—Water-cooled models with digital scroll  
Evaporator  
Coil  
Expansion  
Valve  
Sensing  
Bulb  
Sight  
Glass  
External  
Equalizer  
Digital  
Solenoid  
Valve  
Service  
Valves  
Filter  
Dryer  
Digital  
Compressor  
Tube-  
in-Tube  
Condenser  
Tube-  
Fluid  
Supply  
To  
in-Tube  
Condenser  
Fluid  
Return  
From  
Unit  
Unit  
Shutoff*  
Valves  
To Liebert  
iCOM Control  
2-Way  
Motorized  
Ball Valve  
To Liebert  
iCOM Control  
3-Way  
Fluid  
Supply  
To Unit  
Motorized  
Ball Valve  
(optional)  
Hose Bibs*  
Field-Supplied  
Reducers  
Required  
Fluid  
Return  
From Unit  
*Components are not supplied  
by Liebert but are recommended  
for proper circuit operation  
and maintenance.  
on 3-Ton Units  
FACTORY PIPING  
FIELD PIPING  
DPN001727  
Rev. 0  
®
Liebert Challenger 3000  
38  
 
Water-Cooled Models—Self-Contained Compressor  
4.3  
Water Regulating Valve  
The water regulating valve automatically regulates the amount of fluid necessary to remove the heat  
from the refrigeration system, permitting more fluid to flow when load conditions are high and less  
fluid to flow when load conditions are low. The valve consists of a brass body, balance spring, valve  
seat, valve disc holders, capillary tube to discharge pressure, and adjusting screw.  
4.3.1 Standard Valve - 150psig (1034kPa) System for 3 & 5-Ton Units (Johnson Controls Valve)  
High Pressure Valve - 350psig (2413kPa) System for 5-Ton Units (Johnson Controls Valve)  
Adjustment  
The valve may be adjusted with a standard refrigeration service valve wrench or screw driver.  
To lower the head pressure setting, turn the square adjusting screw clockwise until the high pressure  
gauge indicates the desired setting.  
To raise the head pressure setting, turn the adjusting screw counterclockwise until the desired  
setting is obtained.  
Figure 21 Johnson Controls valve adjustment  
Range  
spring  
Valve spring  
guide  
Range adjustment screw  
Top  
retainer  
Insert screwdrivers underneath  
the valve spring guide  
®
39  
Liebert Challenger 3000  
     
Water-Cooled Models—Self-Contained Compressor  
4.3.2 High Pressure Valve - 350 psig (2413 kPa) System for 3-Ton Units (Metrex Valve)  
Adjustment  
The valve may be adjusted using a 1/8" diameter rod. Turn the adjusting collar nut counterclockwise  
to raise head pressure; turn it clockwise to lower head pressure. Rotation directions are viewed from  
top of valve spring housing.  
Figure 22 Metrex Valve adjustment  
Adjusting collar nut  
Table 12 Refrigerant control settings psi (kPa)  
Low Pressure  
Cut Out  
Low Pressure  
Cut In  
High Pressure  
Cut Out  
20 (137.9)  
65 (448.2)  
400 (2758)  
Manual Flushing  
The valve may be flushed by rotating the socket head screw clockwise. This screw must be in the OUT  
position (counterclockwise) for normal valve operation.  
4.4  
Motorized Ball Valve—Digital Scroll Compressors  
On digital scroll units, discharge pressure is controlled by a motorized ball valve. During unloaded  
operation, the pressure changes during each digital cycle could cause excessive repositions with a  
pressure-operated water regulating valve. The control algorithm for the motorized ball valve uses an  
intelligent sampling rate and adjustable pressure thresholds to reduce valve repositions. The valve  
assembly consists of the brass valve, linkage and actuator.  
4.4.1 Control  
The valve actuator operates on 24VAC power and is controlled by a 2-10VDC proportional control  
signal. The valve will move from fully open to fully closed in 60 seconds. At 2VDC, the valve is closed;  
at 10VDC, the valve is fully open. There is a 20-second delay to position the motorized ball valve  
before starting the compressor.  
®
Liebert Challenger 3000  
40  
         
Water-Cooled Models—Self-Contained Compressor  
Control Method  
The control utilizes an upper and lower pressure threshold with a 35psi (241kPa) deadband to reduce  
valve movement. If the liquid pressure is between the upper and lower threshold, the valve remains  
at the current position. If the liquid pressure exceeds the upper threshold the valve opens, and if the  
pressure falls below the lower threshold the valve closes. There are multiple adjustment bands to ease  
discharge pressure back into control range.  
4.4.2 Adjustment  
Both pressure thresholds can be shifted simultaneously over a 50psi (345kPa) range (the 35psi  
[241kPa] differential remains constant). The ball valve setpoint offset parameter in the Liebert  
iCOM® Service menu can be adjusted from 0 to 50 PSI (345 kPa) to raise or lower the control band  
similar to the pressure adjustment on a water regulating valve. Changing the setpoint offset will  
adjust the pressure thresholds for both circuits. Units are factory-set at a 30psi (207 kPa) setpoint  
offset (30psi [207 kPa] above minimum). This results in a 220psiA (1517kPa) lower threshold and a  
255psiA (1758kPa) upper threshold pressure.  
4.4.3 Startup  
The setpoint offset is adjusted to the minimum value during startup, then changes to the set value  
once the compressor reaches normal operating pressures. Changes in fluid temperature could cause  
pressure changes that do not result in valve movement within the deadband. Fan cycling stats should  
be set to prevent continuous fluid temperature swings greater than 10°F (5.6°C).  
4.4.4 Location  
The motorized ball valve is located in the condenser fluid return line. Three-way valves are piped in a  
mixing arrangement with the common port at the valve outlet.  
4.4.5 Manual Control  
The valve can be manually set by disconnecting AC power, depressing the manual override button on  
the valve actuator and adjusting the valve position with the handle. The motorized ball also can be  
controlled through the Liebert iCOM’s Service menu using manual mode to override the normal  
control.  
®
41  
Liebert Challenger 3000  
       
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor  
5.0 GLYCOL/GLYCOOL-COOLED MODELS—SELF-CONTAINED COMPRESSOR  
5.1  
Drycooler Location  
The drycooler should be located for maximum security and maintenance accessibility. Avoid ground-  
level sites with public access or areas which contribute to heavy snow or ice accumulations. To assure  
adequate air supply, it is recommended that drycoolers be located in a clean air area, away from loose  
dirt and foreign matter that may clog the coil. In addition, drycoolers should not be located in the  
vicinity of steam, hot air or fume exhausts. Also, drycoolers should not be located closer than 3 feet  
(1 meter) from a wall, obstruction or adjacent unit.  
5.2  
5.3  
Drycooler Installation  
For roof installation, mount drycoolers on steel supports in accordance with local codes. To minimize  
sound and vibration transmission, mount steel supports across load bearing walls. For ground  
installation, a concrete pad will provide adequate support. Drycooler legs have mounting holes for  
securing the drycooler to steel supports or concrete pad.  
Electrical Connections  
Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to  
electrical schematic when making connections. Make all wiring and electrical connections in  
accordance with local and national codes.  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Potentially lethal voltages exist within this equipment during operation. Observe all cautions  
and warnings on unit and in this manual.  
The Liebert iCOM® microprocessor does not isolate power from the unit, even in the “Unit  
Off” mode. The only way to ensure that there is NO voltage inside the unit is to install and  
open a remote disconnect switch. Refer to unit electrical schematic.  
Use voltmeter to make sure power is turned Off before making any electrical connections.  
5.3.1 Line Voltage  
Line voltage electrical service is required for all drycoolers at the location of the drycooler. This power  
supply does not have to be the same voltage as the indoor unit. This separate power source may be  
208, 230, 460, or 575 V, 60 Hz; or 200, 230, or 380/415 V, 50 Hz. The disconnect switch is factory-  
supplied and mounted in the electric panel.  
WARNING  
resulting in building and/or equipment damage, injury or death.  
!
Risk of loose electrical wiring connections. Can cause overheating of wire, smoke and fire  
Use copper wire only and verify that all connections are tight.  
5.3.2 Low Voltage  
A control interlock between the drycooler and the indoor unit is required and is connected between 70  
and 71 in the handy box of the indoor unit and the pump and drycooler control box of the drycooler.  
NEC Class 1 wiring is required.  
5.3.3 Pump and Drycooler  
All wiring to the pump and drycooler from the control box should be done in accordance with the  
electrical schematic on the inside lid of the drycooler control box and with local and national codes.  
®
Liebert Challenger 3000  
42  
             
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor  
5.4  
Glycol Piping  
These guidelines apply to the field leak checking and fluid requirements for field piping systems.  
General Guidelines  
• Equipment damage and personal injury can result from improper piping installation, leak  
checking, fluid chemistry and fluid maintenance.  
• Follow local piping codes, safety codes.  
• Qualified personnel must install and inspect system piping.  
• Contact a local water consultant regarding water quality, corrosion protection and freeze  
protection requirements.  
• Install manual shutoff valves at the supply and return line to each indoor unit and drycooler to  
permit routine service and emergency isolation of the unit.  
NOTICE  
Risk of water leakage. Can cause severe property damage and loss of critical data center  
equipment.  
This unit requires a water drain connection. It may require an external water supply to  
operate the humidifier. Improper installation, application and service practices can result in  
water leakage from the unit.  
Do not locate the Liebert Challenger 3000 directly above any equipment that could sustain  
water damage. Emerson recommends installing monitored leak detection equipment for the  
unit and supply lines.  
NOTICE  
Risk of frozen fluids. Can cause equipment and building damage.  
Freezing system fluids can rupture piping. Complete system drain-down cannot be ensured.  
When the field piping or unit may be exposed to freezing temperatures, charge the system  
with the proper percentage of glycol and water for the coldest design ambient.  
Automotive antifreeze is unacceptable and must NOT be used in any glycol fluid system.  
NOTICE  
Risk of corrosion. Can cause equipment damage.  
Read and follow individual unit installation instructions for precautions regarding fluid  
system design, material selection and use of field-provided devices. Liebert systems contain  
iron and copper alloys that require appropriate corrosion protection.  
Contact a local water consultant regarding water quality, corrosion and freeze protection  
requirements.  
Water chemistry varies greatly by location, as do the required additives, called inhibitors,  
that reduce the corrosive effect of the fluids on the piping systems and components. The  
chemistry of the water used must be considered, because water from some sources may  
contain corrosive elements that reduce the effectiveness of the inhibited formulation.  
Sediment deposits prevent the formation of a protective oxide layer on the inside of the  
coolant system components and piping. The water/coolant fluid must be treated and  
circulating through the system continuously to prevent the buildup of sediment deposits and  
or growth of sulfate reducing bacteria.  
Preferably, surface waters that are classified as soft and are low in chloride and sulfate ion  
content should be employed. Proper inhibitor maintenance must be performed in order to  
prevent corrosion of the system. Consult glycol manufacturer for testing and maintenance of  
inhibitors.  
Commercial ethylene glycol (Union Carbide Ucartherm, Dow Chemical Dowtherm SR-1 and  
Texaco E.G. Heat Transfer Fluid 100), when pure, is generally less corrosive to the common  
metals of construction than water itself. It will, however, assume the corrosivity of the water  
®
43  
Liebert Challenger 3000  
 
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor  
from which it is prepared and may become increasingly corrosive with use if not properly  
inhibited.  
NOTICE  
Risk of no-flow condition. Can cause equipment and building damage from corrosion and  
resulting leaks.  
Do not leave the unit in a no-flow condition. Idle fluid allows the collection of sediment that  
prevents the formation of a protective oxide layer on the inside of tubes. Keep unit switched  
On and system pump operating.  
NOTICE  
Risk of debris or precipitate clogging pipes. Can cause equipment damage.  
Galvanized pipe must not be used in or with systems or units that contain glycol. The  
phosphates in the inhibitor can react with the zinc in the galvanized pipe, precipitating an  
insoluble material that can eventually foul the system.  
Fluid-cooled condensers have small internal flow passages. To avoid clogging and other  
resulting system operation problems, install a 16-20 mesh filter in the fluid supply line to the  
indoor unit. The filter should be located where it can be easily serviced or replaced.  
Do not install unit on open loop systems. Debris carried by the fluid will clog the brazed plate  
condenser.  
NOTICE  
Risk of improper installation. Can cause equipment or structural damage.  
Supply and return lines must be supported in a way that keeps their weight from bearing on  
the piping of the unit, drycooler or pumps. Failure to support piping can strain the  
equipment’s structural integrity.  
A relief valve must be installed in the system to avoid the possibility of burst pipes. This valve  
may be obtained from the supplier as an option or obtained from another vendor.  
Emerson recommends installing manual service shutoff valves at the supply and return connections  
to each unit. This enables routine service and/or emergency isolation of the unit. In addition, multiple  
pump packages require a check valve at the discharge of each pump to prevent back flow through the  
standby pump(s).  
To facilitate filling, installation of hose bibs at the lowest point of the system is recommended.  
Consideration of the minimum glycol temperature to be supplied from the drycooler will determine if  
the need exists to insulate the glycol supply and return lines. Insulation will prevent condensation on  
the glycol lines in low ambient conditions.  
All fluid piping must comply with local codes. Care in sizing pipes will help reduce pumping power  
and operating costs.  
Table 13 Room dew point temperatures  
Dry Bulb  
°F (°C)  
Wet Bulb  
°F (°C)  
Relative  
Humidity  
Dew Point*  
°F (°C)  
70 (21.1)  
70 (21.1)  
57.2 (14.0)  
58.5 (14.7)  
45  
50  
48.0 (8.9)  
50.5 (10.3)  
72 (22.2)  
72 (22.2)  
58.9 (24.9)  
60.0 (15.5)  
45  
50  
50.0 (10.0)  
52.4 (11.3)  
75 (23.8)  
75 (23.8)  
61.2 (16.2)  
62.5 (16.9)  
45  
50  
52.4 (11.3)  
55.0 (12.7)  
* Minimum glycol temperature before condensation will occur.  
®
Liebert Challenger 3000  
44  
 
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor  
5.4.1 Expansion Tanks, Fluid Relief Valves and Other Devices  
An expansion tank must be provided for expansion and contraction of the fluid due to temperature  
change in this closed system. Vents are required at system high points to vent trapped air when  
filling the system. A relief valve is a also a necessary piping component.  
Depending on the complexity of the system, various other devices may be specified. Pressure gauges,  
flow switches, automatic air separator, tempering valves, standby pumps, sensors for electrical  
controls, and flow switches are just a few of these devices.  
NOTICE  
Risk of frozen fluids. Can cause piping and system components to rupture and leak, resulting  
in equipment and building damage.  
Immediately following the use of water for leak testing or system cleaning, charge the system  
with the proper percentage of glycol and water for your coldest design ambient. Complete  
system drain-down cannot be assured.  
5.5  
Filling Instructions  
5.5.1 Preparing the System for Filling  
It is important to remove any dirt, oil or metal filings that may contaminate the cooling system piping  
in order to prevent contamination of the fresh glycol solution and fouling of the drycooler piping. The  
system should be flushed thoroughly using a mild cleaning solution or high-quality water and then  
completely drained before charging with glycol. Cleaning new systems is just as important as  
cleaning old ones. New systems can be coated with oil or a protective film; dirt and scale are also  
common. Any residual contaminants could adversely affect the heat transfer stability and  
performance of your system. In many cases, in both old and new systems, special cleaners are needed  
to remove scale, rust and hydrocarbon foulants from pipes, manifolds and passages. Clean heat  
transfer surfaces are important in maintaining the integrity of the heating/cooling system. For more  
information on cleaners and degreasers, contact your sales representative. Follow the manufacturer's  
instructions when using these products.  
Calculate the internal volume of the system as closely as possible. See Table 14 and Table 16 for  
unit volumes. Use volume in Table 15 for glycol piping volumes.  
Table 14  
Indoor unit glycol volume approximate gallons (liters) max.  
Model (50 Hz)  
Glycol-Cooled  
1.2 (4.5)  
2.0 (7.5)  
GLYCOOL  
046WG/(045WG)  
071WG/(070WG)  
061G/(058G)  
4.0 (15.1)  
Table 15 Volume in standard Type “L” copper piping  
Diameter (in.) Volume  
Outside Gal/Ft  
Inside  
0.123  
0.555  
0.666  
0.785  
1.025  
L/M  
0.01  
0.15  
0.22  
0.31  
0.53  
1/2  
5/8  
0.008  
0.012  
0.018  
0.025  
0.043  
3/4  
7/8  
1-1/8  
®
45  
Liebert Challenger 3000  
         
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor  
5.5.2 Glycol Solutions  
NOTE  
Glycol solutions should be considered for protection of the coil. When it is not used, damage can  
occur from either freezing or corrosion from water.  
When considering the use of any glycol products in a particular application, you should review the  
latest Material Safety Data Sheets and ensure that the use you intend can be accomplished safely.  
For Material Safety Data Sheets and other product safety information, contact the supplier nearest  
you. Before handling any other products mentioned in the text, you should obtain available product  
safety information and take necessary steps to ensure safety of use.  
NOTICE  
Risk of improper handling of glycol. Can cause environmental damage and violate national,  
regional and local laws.  
When mishandled, glycol products pose a threat to the environment. Before using any glycol  
products, review the latest Material Safety Data Sheets and ensure that you can use the  
product safely.  
Glycol manufacturers request that the customer read, understand and comply with the  
information on the product packaging and in the current Material Safety Data Sheets. Make  
this information available to anyone responsible for operation, maintenance and repair of the  
drycooler and related equipment.  
No chemical should be used as or in a food, drug, medical device, or cosmetic, or in a product or  
process in which it may contact a food, drug, medical device, or cosmetic until the user has  
determined the suitability and legality of the use. Since government regulations and use conditions  
are subject to change, it is the user's responsibility to determine that this information is appropriate  
and suitable under current, applicable laws and regulations.  
NOTICE  
Risk of using improper cooling agent. Can cause reduced cooling performance and damage to  
equipment and piping.  
Proper formulations of inhibited formula ethylene glycol and propylene glycol must be used in  
the Liebert Challenger 3000 system. Automotive antifreeze is unacceptable and must NOT be  
used.  
Typical inhibited formula ethylene glycol and propylene glycol manufacturers and suppliers are  
Union Carbide (Ucartherm) or Dow Chemical (Dowtherm SR-1, Dowfrost). These glycols are supplied  
with corrosion inhibitors and do not contain a silicone anti-leak formula. Commercial ethylene glycol,  
when pure, is generally less corrosive to the common metals of construction than water itself.  
Aqueous solutions of these glycols, however, assume the corrosivity of the water from which they are  
prepared and may become increasingly corrosive with use if not properly inhibited.  
There are two basic types of additives: corrosion inhibitors and environmental stabilizers. The  
corrosion inhibitors function by forming a surface barrier that protects the metals from attack.  
Environmental stabilizers, while not corrosion inhibitors in the strictest sense of the word, decrease  
corrosion by stabilizing or favorably altering the overall environment. An alkaline buffer such as  
borax is a simple example of an environmental stabilizer since its prime purpose is to maintain an  
alkaline condition (pH above 7).  
The percentage of glycol to water must be determined by using the lowest design outdoor temperature  
in which the system is operating. Table 16 indicates the solution freeze point at several  
concentration levels of ethylene glycol. Propylene glycol concentrations should be 1% higher than the  
ethylene glycol table values to find the freeze point. For example, 41% propylene glycol freezes at  
-10°F (-23°C).  
Table 16 Ethylene glycol concentrations  
% Glycol by Volume  
Freezing Point °F (°C)  
0 *  
10  
20  
30  
40  
50  
32 (0)  
25 (-3.9)  
16 (-8.9)  
5 (-15.0)  
-10 (-23.3)  
-32 (-35.5)  
Apparent Specific Gravity  
@ 50°F (10°C)  
1
1.014  
1.028  
1.042  
1.057  
1.071  
* A minimal amount of glycol should be considered for inhibitive coil protection.  
®
Liebert Challenger 3000  
46  
   
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor  
NOTICE  
Risk of corrosion from water impurities. Can cause equipment damage.  
The quality of water used for dilution must be considered because water may contain  
corrosive elements which reduce the effectiveness of the inhibited formulation. Water that is  
classified as soft (low in chloride and sulfate ion content less than 100 parts per million each)  
should be used.  
5.5.3 Filling the System  
Installation of hose bibs at the lowest point of the system is recommended. When filling a glycol  
system keep air to a minimum. Air in glycol turns to foam and is difficult and time-consuming to  
remove. (Anti-foam additives are available and may be considered.) Open all operating systems to the  
loop. With the top vent(s) open, fill the system from the bottom of the loop. This will allow the glycol to  
push the air out of the top of the system, minimizing trapped air. Fill to approximately 80% of  
calculated capacity. Fill slowly from this point, checking fluid levels until full.  
NOTE  
For glycol solution preparation and periodic testing, follow manufacturer's recommendations.  
Do not mix products of different manufacturers.  
®
47  
Liebert Challenger 3000  
 
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor  
Figure 23 Drycoolers and pump packages  
43-9/16"  
(1105mm)  
DRYCOOLER  
A
GLYCOL PUMP PACKAGE  
See Note 1  
30-1/4"  
(768mm)  
37-7/8"  
(1095mm)  
19"  
(483mm)  
B
43-3/16"  
(1097mm)  
Provided on  
dual pump  
package only  
See Table 18 for keys to  
dimensions “A”, “B” and “C”.  
PUMP PACKAGE  
MOUNTING ANGLES  
1/2" diameter holes  
for mounting (4 typ)  
Notes  
1. Single pump packages are 17-1/4"  
(438 mm) wide. Dual pump packages are  
32-1/4" (819 mm) wide.  
2. Mounting holes are 15-1/4" (387mm)  
apart on single pump packages and  
30-1/4" (768 mm) apart on dual pump  
packages.  
Note: Angles located  
inside, bottom of pump  
package. View used for  
mounting reference.  
3/4"  
(19mm)  
3. Connection sizes apply to primary pump  
supplier.  
C
A
B
dimensions “A”, “B” and “C”.  
For expansion tank dimensions,  
1-3/4"  
4-1/4"  
(25.4mm) (25.4mm)  
1"  
(25.4mm)  
B
C
1-3/4"  
(25.4mm)  
1"  
(25.4mm)  
4-1/4"  
(25.4mm)  
37-11/16"  
(957mm)  
1/2" (12.7mm) diameter  
anchor bolts (typ)  
TYPICAL  
FOOTPRINT  
UNIT ANCHOR PLAN  
®
Liebert Challenger 3000  
48  
 
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor  
Figure 24 Pump packages—expansion tank  
30-1/2  
(774.7mm)  
17-1/4"  
(438.2mm)  
O 9"  
(228.6mm)  
6-13/16"  
(173mm)  
1/2" FPT  
Fitting  
1/2" FPT  
Fitting  
2-3/4"  
(69.9mm)  
2-1/2"  
(63.5mm)  
7"  
(177.8mm)  
4"  
1"  
(25.4mm)  
O 1/2" (12.7mm) 8 holes  
1" (25.4mm)  
(101.6mm)  
EXPANSION TANK  
8.8 gal. (33.3L)  
1-1/2" (38.1mm)  
1-1/2"  
(38.1mm)  
6-1/8"  
SL-10065 Pg. 7B  
SL-10070 Pg. 6B  
3"  
(155.6mm)  
(76.2mm)  
Table 17 Mounting hole dimensional data  
A
B
C
PUMP PACKAGE  
SINGLE (0.75 - 7.5 hp)  
DUAL (0.75 - 5 hp)  
in (mm)  
in (mm)  
in (mm)  
15-1/4 (387.4)  
30-1/4 (768.4)  
2-1/2 (63.5) 22-1/2 (571.5)  
2-1/2 (63.5) 22-1/2 (571.5)  
Table 18 Drycooler data  
Drycooler  
Conn. Sizes  
(Suct. & Disc.) in.  
Model No. of Weight  
“A” Dimension “B” Dimension “C” Dimension  
Coil Internal  
Volume gal. (l)  
No.  
-069  
-092  
-109  
-112  
-139  
-197  
Fans  
lb (kg)  
in. (mm)  
in. (mm)  
44 (1118)  
44 (1118)  
44 (1118)  
44 (1118)  
84 (2134)  
84 (2134)  
in. (mm)  
42 (1067)  
42 (1067)  
42 (1067)  
42 (1067)  
82 (2083)  
82 (2083)  
1
1
1
1
2
2
410 (186)  
430 (195)  
450 (204)  
470 (213)  
565 (256)  
605 (274)  
1-1/4  
51-1/2 (1308)  
51-1/2 (1308)  
51-1/2 (1308)  
51-1/2 (1308)  
91-1/2 (2324)  
91-1/2 (2324)  
2.4 (9.2)  
3.7 (13.9)  
4.9 (18.6)  
5.8 (22.0)  
4.8 (18.2)  
9.0 (34.1)  
1-1/2  
2
2
2
2
Table 19 Glycol pump data*  
Pump  
Pump Suction  
Connection, in.  
Pump Discharge  
Connection, in.  
Hp  
3/4  
1-1/2  
2
Hz  
60  
60  
60  
60  
60  
50  
50  
50  
50  
50  
1-1/4  
3/4  
3/4  
3/4  
1
1-1/4  
1-1/4  
3
1-1/2  
5
1-1/2  
1-1/4  
3/4  
3/4  
3/4  
3/4  
1-1/4  
3/4  
1
1-1/4  
1-1/4  
1-1/2  
2
1-1/4  
1-1/4  
3
1-1/2  
* Connection sizes apply to primary pump supplier  
®
49  
Liebert Challenger 3000  
       
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor  
Figure 25 General arrangement—Glycol-cooled models with scroll compressor  
Expansion Tank Field-Installed at  
Highest Point in System  
Glycol  
Pump  
Pump  
Housing  
Drycooler  
Electric Box  
Unions*  
Fill*  
Drycooler  
Coil  
Fluid  
Isolation  
Expansion  
Port*  
Return  
Evaporator  
Coil  
Valves*  
to Pump  
Expansion  
Valve  
Unions*  
Fluid  
Supply  
from  
Pump  
Hose  
Bibs*  
Sensing  
Bulb  
Air Vents*  
at Top of  
Risers  
Flow Regulating  
Valve*  
Sight  
Glass  
Pressure  
Port*  
Hot Gas  
Bypass  
Valve  
External  
Equalizers  
Filter  
Dryer  
Service  
Valves  
Hot Gas  
Bypass  
Solenoid  
Valve  
Scroll  
Compressor  
Hot Gas  
Bypass  
Tube  
in Tube  
Condenser  
Tube  
in Tube  
Condenser  
Fluid  
Supply  
to Unit  
Bypass  
Valve  
Fluid  
Return  
from  
Unit  
Isolation  
Valves*  
2-Way Water  
Regulating  
Valve  
3-Way Water  
Regulating Valve  
(optional)  
*Components are not  
supplied by Liebert but  
are recommended for  
proper circuit operation  
and maintenance  
Fluid  
Supply  
to Unit  
Hose  
Bibs*  
Fluid  
Return  
from  
Field-Supplied  
FACTORY PIPING  
FIELD PIPING  
Unit  
Reducers Required  
on 3-Ton Units  
DPN000361  
Rev. 2  
®
Liebert Challenger 3000  
50  
 
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor  
Figure 26 General arrangement—Glycol-cooled models with digital scroll  
Expansion Tank Field-Installed at  
Highest Point in System.  
Glycol  
Pump  
Pump  
Housing  
Unions*  
Drycooler  
Electric  
Box  
Fill*  
Drycooler  
Coil  
Evaporator  
Coil  
Fluid  
Expansion  
Port*  
Return  
Isolation  
Valves*  
to Pump  
Expansion  
Valve  
Unions*  
Fluid Supply  
from Pump  
Sensing  
Bulb  
Hose  
Bibs*  
Flow Regulating  
Valve*  
Air Vents*  
at Top of  
Risers  
Sight  
Glass  
External  
Equalizer  
Pressure  
Port*  
Digital  
Compressor  
Filter  
Dryer  
Digital  
Solenoid  
Valve  
Service  
Valves  
Tube  
in Tube  
Condenser  
Tube  
in Tube  
Condenser  
Fluid  
Supply  
to Unit  
Fluid  
Return  
from  
Isolation  
Valves*  
Unit  
To iCOM Control  
2-Way  
To iCOM Control  
Motorized  
Ball Valve  
3-Way  
Motorized  
Ball Valve  
(optional)  
Fluid  
Supply  
to Unit  
Hose  
Bibs*  
Fluid  
Return  
From  
Unit  
Field-Supplied  
Reducers  
Required on 3  
Ton Units  
FACTORY PIPING  
FIELD PIPING  
Hose  
Bibs*  
*Components are not supplied by Liebert but  
are recommended for proper circuit operation  
and maintenance.  
DPN001722  
Rev. 0  
®
51  
Liebert Challenger 3000  
 
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor  
Figure 27 General arrangement—GLYCOOL models with scroll compressor  
Expansion Tank Field-Installed at  
Glycol  
Pump  
Highest Point in System  
Pump  
Housing  
Drycooler  
Unions*  
Drycooler  
Coil  
Electric Box  
Unions*  
Fill*  
Fluid  
Return to  
Pump  
Evaporator  
Coil  
Pressure  
Port*  
Isolation  
Valves*  
Fluid  
Expansion  
Valve  
Supply  
from Pump  
Hose  
Bib*  
Sensing  
Bulb  
Flow Regulating  
Valve*  
Air Vents*  
at Top of  
Risers  
Sight  
Glass  
Pressure  
Port*  
Hot Gas  
Bypass  
Valve  
External  
Filter  
Dryer  
Equalizers  
Service  
Valves  
Scroll  
Compressor  
Hot Gas  
Bypass  
Econ-O-Coil  
3-Way Water  
Regulating  
Valve  
Fluid  
Supply to  
Unit  
Tube  
Valve  
Actuator  
in Tube  
Fluid  
Return  
from  
Condenser  
Econ-O-Cycle  
Comparator  
Unit  
3-Way Chilled  
Glycol Valve  
Isolation  
Valves*  
Econ-O-Coil  
Circuit  
*Components are not supplied  
by Liebert but are recommended  
for proper circuit operation  
and maintenance.  
Field-Supplied  
Reducers  
Required on 3-Ton Units  
Hose  
Bibs*  
FACTORY PIPING  
DPN000379  
Rev. 3  
FIELD PIPING  
®
Liebert Challenger 3000  
52  
 
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor  
Figure 28 General arrangement—GLYCOOL models with digital scroll compressor  
Glycol  
Expansion Tank Field-Installed at  
Pump  
Housing  
Pump  
Highest Point in System  
Drycooler  
Electric  
Box  
Unions*  
Drycooler  
Coil  
Fill*  
Fluid  
Evaporator  
Coil  
Pressure  
Port*  
Return to  
Isolation  
Pump  
Valves*  
Unions*  
Expansion  
Valve  
Fluid  
Supply  
from  
Hose  
Bib*  
Sensing  
Bulb  
Pump  
Air Vents*  
at Top of  
Risers  
Flow Regulating Valve*  
External  
Equalizer  
Pressure  
Port*  
Sight  
Glass  
Digital  
Filter  
Dryer  
Solenoid  
Valve  
Service  
Valves  
Digital  
Compressor  
Tube-  
Econ-O-Coil  
in-Tube  
Condenser  
r
Fluid  
Supply to  
Unit  
Valve  
Actuator  
Fluid  
Return  
from  
To Liebert  
Econ-O-Cycle  
Comparator  
iCOM Control  
Unit  
3-Way Chilled  
Glycol Valve  
3-Way Motorized  
Ball Valve  
Isolation  
Valves*  
Econ-O-Coil  
Circuit  
Field-Supplied  
*Components are not supplied by Liebert but  
are recommended for proper circuit operation  
and maintenance.  
Reducers  
Required on 3-Ton Units  
Hose  
Bibs*  
FACTORY PIPING  
FIELD PIPING  
DPN001724  
Rev. 0  
®
53  
Liebert Challenger 3000  
 
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor  
5.5.4 Motor Ball Valve—Digital Scroll Compressors  
Refer to 4.4 - Motorized Ball Valve—Digital Scroll Compressors for details on the motorized ball  
valve.  
5.6  
5.7  
Condenser  
The condenser is designed to operate in conjunction with a drycooler. The maximum coolant pressure  
is 350 psig (2413 kPa).  
Glycol Regulating Valve  
The glycol regulating valve automatically regulates the amount of coolant necessary to remove the  
heat from the refrigeration system, permitting more fluid to flow when load conditions are high and  
less fluid to flow when load conditions are low. The valve consists of a brass body, balance spring,  
valve seat, valve disc holders, capillary tube to discharge pressure, and adjusting screw.  
5.7.1 Standard Valve - 150psig (1034kPa) System for 3 & 5-Ton Units (Johnson Controls Valve)  
High Pressure Valve - 350psig (2413kPa) System for 5-Ton Units (Johnson Controls Valve)  
5.7.2 High Pressure Valve - 350 psig (2413 kPa) System for 3-Ton Units (Metrex Valve)  
5.7.3 Testing Valve Function  
When the refrigeration system has been Off for approximately 10-15 minutes, the coolant flow should  
stop.  
Should the coolant continue to flow, the valve is either improperly adjusted (head pressure is too low)  
or the pressure sensing capillary is not connected properly to the condenser.  
Table 20 Refrigerant control settings psi (kPa)  
Low Pressure  
Cut Out  
Low Pressure  
Cut In  
High Pressure  
Cut Out  
20 (137.9)  
65 (448.2)  
400 (2758)  
®
Liebert Challenger 3000  
54  
             
Chilled Water Models  
6.0 CHILLED WATER MODELS  
6.1 Piping Considerations  
Manual shutoff valves should be installed at the supply and return lines to each unit. This will  
provide for routine service and emergency isolation of the unit.  
Consideration of the minimum water temperature to be supplied from the chiller will determine if the  
need exists to insulate supply and return lines. Insulation will prevent condensation on the supply  
and return lines.  
To provide for the emergency of water leaks and the consequences of sub-floor flooding, floor drains  
should be provided with wet traps or a water detection system, such as a Liebert Liqui-tect®, that is  
installed near the base of the unit or below the elevated floor.  
Figure 29 Chilled water general arrangement - Upflow (BU)  
Air  
Flow  
Bleed  
Valve  
Chilled  
Water  
Supply  
Chilled  
Water  
Coil  
Chilled  
Water  
Return  
Valve  
Actuator  
3-WAY VALVE  
Shutoff  
Valves *  
A
3-Way  
Chilled  
AB  
Water  
Valve  
B
Flow  
Switch  
(optional)  
Air  
Flow  
Hose  
Bibs *  
Bleed  
Valve  
Valve  
Actuator  
Chilled  
Water  
2-Way  
Chilled  
Water  
Valve  
Supply  
Chilled  
Water  
Coil  
Chilled  
Water  
Return  
2-WAY VALVE  
Shutoff  
Valves *  
FACTORY PIPING  
FIELD PIPING  
Hose  
Bibs *  
SL-11899  
Pg. 5  
*Components are not supplied by Liebert but  
are recommended for proper circuit operation  
and maintenance.  
®
55  
Liebert Challenger 3000  
     
Chilled Water Models  
Figure 30 Chilled water general arrangement - Downflow (BF) models  
Air  
Flow  
Bleed  
Valve  
Chilled  
Valve  
Water  
Return  
Actuator  
AB  
A
Chilled  
Water  
Supply  
Chilled  
Water  
Coil  
3-Way  
Chilled  
Water  
Valve  
B
Shutoff  
Valves *  
3-WAY VALVE  
Flow  
Switch  
(optional)  
Air  
Chilled  
Water  
Return  
Flow  
Hose  
Bibs *  
Bleed  
Valve  
Valve  
Actuator  
Chilled  
Water  
Supply  
Chilled  
Water  
Coil  
Shutoff  
Valves *  
2-Way Chilled  
Water Valve  
2-WAY VALVE  
FACTORY PIPING  
FIELD PIPING  
Hose  
Bibs *  
*Components are not supplied by Liebert,  
but are recommended for proper circuit  
operation and maintenance.  
SL-11899  
Pg. 6  
®
Liebert Challenger 3000  
56  
 
Split System Models  
7.0 SPLIT SYSTEM MODELS  
Three condensing unit styles are available: two air-cooled and one water/glycol-cooled condensing  
unit.  
7.1  
Location Considerations  
7.1.1 Air-Cooled Condensing Units  
To assure an adequate air supply, it is recommended that all condensing units be located in a clean  
air area, away from loose dirt and foreign matter that may clog the coil.  
The outdoor condensing unit must not be located in the vicinity of steam, hot air, or fume exhausts or  
closer than 18" from a wall, obstruction, or adjacent unit.  
The outdoor condensing unit should be located for maximum security and maintenance accessibility.  
Avoid ground-level sites with public access or areas that will contribute to heavy snow accumulations.  
Do not allow the discharge air to blow into another condensing unit.  
The outdoor condensing unit must be located at the same level or above the indoor Liebert Challenger  
3000 unit. It must NOT be located below the indoor unit.  
A solid base, capable of supporting the weight of the condenser and at least 2" (51mm) higher than the  
surrounding grade and at least 2" (51mm) larger than the condensing unit base dimensions, should be  
installed at the pre-determined location. In snow areas, a base of sufficient height to clear snow  
accumulation must be installed.  
The centrifugal fan air-cooled condensing unit may be located above the dropped ceiling or any remote  
indoor area. If noise is of concern, the condensing unit should be located away from personnel. Normal  
operating sound may be objectionable if the condensing unit is placed near quiet work areas.  
To mount the unit in the ceiling, refer to 7.5.1 - Installing the Indoor Condensing Unit for  
hanging guidelines and to Figure 35 - Detail of ceiling hanging bracket for dimensional data.  
7.1.2 Water/Glycol-Cooled Condensing Units  
The condensing unit may be located above the dropped ceiling or any remote indoor area. If noise is of  
concern, the condensing unit should be located away from personnel. Normal operating sound may be  
objectionable if the condensing unit is placed near quiet work areas. To mount the unit the in ceiling,  
7.2  
Electrical Connections  
Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to  
electrical schematic when making connections. Make all wiring and electrical connections in  
accordance with local and national codes.  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Potentially lethal voltages exist within this equipment during operation. Observe all  
cautions and warnings on unit and in this manual.  
The Liebert iCOM® microprocessor does not isolate power from the unit, even in the “Unit  
Off” mode. The only way to ensure that there is NO voltage inside the unit is to install and  
open a remote disconnect switch. Refer to unit electrical schematic.  
Use voltmeter to make sure power is turned Off before making any electrical connections.  
WARNING  
resulting in building and/or equipment damage, injury or death.  
!
Risk of loose electrical wiring connections. Can cause overheating of wire, smoke and fire  
Use copper wire only and verify that all connections are tight.  
®
57  
Liebert Challenger 3000  
         
Split System Models  
7.2.1 Line Voltage  
Line voltage electrical service is required for all condensing units at the location of the condensing  
unit. This power supply does not have to be the same voltage as the indoor unit. This separate power  
source may be 208, 230, 460 or 575V, 60 Hz; or 200, 230, or 380/415V, 50 Hz. A disconnect switch is  
required and must be mounted per local and national codes to isolate the unit for maintenance.  
7.2.2 Low Voltage  
The control cable between the condensing unit and the evaporator unit is connected between  
terminals 1,2 and 3 on the terminal strip in the evaporator unit and the condensing unit control box.  
A fourth wire is required on systems with hot gas bypass. NEC Class 1 wiring is required. Glycol-  
cooled units also require a two-wire control connection to the drycooler and pump package.  
7.3  
Piping Considerations  
7.3.1 Refrigerant Loop  
WARNING  
!
Risk of explosive discharge from high-pressure refrigerant. Can cause injury or death.  
This unit contains fluids and gases under high pressure. Relieve pressure before working with  
piping.  
NOTICE  
Risk of improper refrigerant charge. Can cause equipment damage, environmental  
degradation and violation of national, state and local law.  
Follow all applicable codes for handling refrigerant.  
R22 and R407C are similar in properties—proper safety equipment and proper refrigeration  
tools are required on both types. Check unit nameplate for correct refrigerant type before  
topping off or recharging a system.  
R407C refrigerant must be introduced and charged from the cylinder only as a liquid.  
NOTICE  
Risk of improper piping installation. Can cause contamination of hygroscopic oil with water.  
When installing field piping, care must be taken to protect all refrigerant lines from the  
atmosphere, especially when using refrigerants, such as R407C which requires use of polyol  
ester oils. Do not allow the piping to stand open to air for more than 15 minutes. Units  
designed for R407C have a compressor that contains polyol ester oil, which is very  
hygroscopic; that is, it quickly absorbs water from the air. The longer the compressor piping is  
left open to air, the harder it will be to fully evacuate. If left open too long, the polyol ester oil  
may need to be replaced before achieving the required vacuum level.  
NOTE  
Complete all piping and evacuate lines before connecting quick connects when using an  
optional sweat adapter kit and field installed hard piping.  
Follow all proper brazing practices including a dry nitrogen purge to maintain system  
cleanliness.  
®
Liebert Challenger 3000  
58  
       
Split System Models  
All split systems require two refrigerant lines (an insulated copper suction line and a copper liquid  
line) between the evaporator and the condensing unit.  
Two possible methods exist for installing the copper suction and liquid lines.  
1. Using an optional Sweat Adapter Kit and hard piping between the two units.  
2. Using optional pre-charged line sets (for 3-ton models only).  
All refrigeration piping should be installed with high temperature brazed joints. Prevailing good  
refrigeration practices should be employed for piping supports, leak testing, evacuation, dehydration,  
and charging of the refrigeration circuits. The refrigeration piping should be isolated from the  
building by the use of vibration isolating supports.  
It is important to handle the pre-charged lines for 3-ton units with care so they will not get kinked or  
damaged. Use tube benders and make all bends before making connections to either end. Coil any  
excess tubing in a horizontal plane with the slope of the tubing toward the condensing unit.  
To prevent tube damage when sealing openings in walls and to reduce vibration transmission, use a  
soft flexible material to pack around the tubes.  
When installing remote condensing units mounted above the evaporator, the suction gas line should  
be trapped at the evaporator. This trap will retain refrigerant oil in the Off cycle. When the unit  
starts, oil in the trap is carried up the vertical riser and returns to the compressor.  
Refrigerant charge requirements: Total refrigerant charge will be required only if units are evacuated  
during installation or maintenance. Total refrigerant charge = evaporator + lines + condensing unit.  
NOTE  
All condensing units and 3-ton evaporator units are fully charged with refrigerant. All 5 ton  
evaporator units include a nitrogen holding charge only. See Table 21 for field charge  
required. If field-supplied refrigerant piping is installed, refrigerant must be added to the  
system.  
Once all piping is complete, check for leaks and dehydrate the field piping as follows:  
1. Pressurize the field piping to 150 PSIG (1034 kPa) using dry nitrogen with a trace of refrigerant.  
Check system for leaks with a suitable leak detector.  
2. After completion of leak testing, release the test pressure (per local code) and pull a deep vacuum  
on the field piping with a suitable pump.  
3. After 15 minutes, check the pressure readings and, if they have not changed, break vacuum with  
dry nitrogen. Pull a second vacuum to 250 microns or less. Recheck the pressure after 15 minutes.  
Table 21  
Unit refrigerant charge  
R407C Charge  
lb (kg)  
R407C Charge  
lb (kg)  
Model  
Model  
BF/BU 036E  
BF/BU 035E  
BF/BU 060E  
BF/BU 059E  
MC_40/39A  
MC_65/64A  
PF_042A-_L  
PF_041A-_L  
PF_Z42A-_L  
PF_Z41A-_L  
0.5 (0.2)  
0.5 (0.2)  
PF_042A-_H  
PF_041A-_H  
PF_067A-_L  
PF_066A-_L  
PF_Z67A-_L  
PF_Z66A-_L  
PF_067A-_H  
PF_066A-_H  
MC_44/43W  
MC_69/68W  
25.8 (11.7)  
25.8 (11.7)  
25.8 (11.7)  
25.8 (11.7)  
50.1 (22.7)  
50.1 (22.7)  
50.1 (22.7)  
50.1 (22.7)  
3.4 (1.5)  
0.8 (0.4)  
0.8 (0.4)  
12.9 (5.8)  
26.1 (11.8)  
12.9 (5.8)  
12.9 (5.8)  
25.8 (11.7)  
25.8 (11.7)  
5.9 (2.7)  
®
59  
Liebert Challenger 3000  
 
Split System Models  
Table 22 Line charges - refrigerant per 100 ft. (30 m) of Type “L” copper tube  
R407C  
Liquid Line Suction Line  
O.D.  
1/2"  
lb (kg)  
lb (kg)  
7.3 (3.3)  
-
5/8"  
11.7 (5.3)  
24.4 (11.1)  
41.6 (18.9)  
63.3 (28.7)  
0.4 (0.2)  
1.0 (0.4)  
1.7 (0.7)  
2.7 (1.1)  
7/8"  
1-1/8"  
1-3/8"  
Table 23 Recommended refrigerant lines (R407C) sizes OD copper  
3.5-Ton  
036E (035E)  
5-Ton  
060E (059E)  
Equivalent Feet (m)  
0-50 (0-15)  
Suction  
Liquid  
1/2"  
Suction  
Liquid  
1/2"  
7/8"  
1-1/8"  
1-1/8"  
1-3/8"  
51-100 (16-30)  
101-150 (31-45)  
1-1/8"  
1-1/8"  
1/2"  
5/8"  
5/8"  
5/8"  
Table 24 Line coupling sizes  
Model  
(Tons)  
Line Size  
OD Cu, in.  
Coupling  
Size  
Torque  
lb-ft.  
10-12  
35-45  
35-45  
50-65  
3
5
3
5
3/8  
1/2 & 5/8  
7/8  
#6  
#10  
#11  
#12  
1-1/8  
Table 25 Equivalent lengths (feet) for various pipe fittings  
Copper Pipe  
OD in.  
90 Degree  
Elbow Copper Elbow Cast  
90 Degree  
45 Degree  
Elbow  
Gate  
Tee Valve  
Globe Angle  
Valve  
Valve  
1/2  
5/8  
0.8  
0.9  
1.3  
1.4  
1.5  
1.8  
2.2  
2.9  
3.5  
0.4  
0.5  
0.6  
0.8  
1.0  
1.3  
1.6  
2.5  
2.5  
2.5  
3.6  
4.6  
6.4  
7.2  
0.26  
0.28  
0.3  
7.0  
4.0  
5.0  
9.5  
3/4  
1.0  
12.0  
17.2  
22.5  
32.0  
36.0  
6.5  
7/8  
1.45  
1.85  
2.4  
0.36  
0.48  
0.65  
0.72  
9.5  
1-1/8  
1-3/8  
1-5/8  
12.0  
16.0  
19.5  
2.9  
Refrigerant trap = 4 times equivalent length of pipe per this table  
Figure 31 Refrigerant piping diagram  
Condensing unit  
Evaporator  
Suction Line Piping  
Condensing unit  
above evaporator  
Traps recommended at the base of riser and  
every 25 feet (7.6m) of vertical rise.  
®
Liebert Challenger 3000  
60  
         
Split System Models  
7.3.2 Quick Connect Fittings  
NOTE  
When hard piping is used, complete all piping and evacuate lines before connecting quick  
connects.  
Be especially careful when connecting the quick connect fittings. Read through the following steps  
before making the connections.  
1. Remove protector caps and plugs.  
2. Carefully wipe coupling seats and threaded surfaces with a clean cloth.  
3. Lubricate the male diaphragm and synthetic rubber seal with refrigerant oil.  
4. Thread the coupling halves together by hand to ensure that the threads mate properly.  
5. Tighten the coupling body hex nut and union nut with the proper sized wrench until the coupling  
bodies “bottom out” or until a definite resistance is felt.  
6. Using a marker or pen, make a line lengthwise from the coupling union nut to the bulkhead.  
7. Tighten the nuts an additional quarter turn; the misalignment of the lines shows how much the  
coupling has been tightened. This final quarter turn is necessary to ensure that the joint will not  
leak. Refer to Table 24 for torque requirements.  
8. Add charge for the additional piping (refer to Table 22).  
®
61  
Liebert Challenger 3000  
 
Split System Models  
7.4  
Outdoor Air-Cooled Condensing Units  
Figure 32 Outdoor air-cooled condensing unit—horizontal air discharge models  
UNIT DIMENSIONS  
Removable (Right) Panel  
for access to refrigeration  
components  
Fan Rotation  
CCW (left side)  
A
Right Air  
Discharge  
Left Air  
Intake  
B
Shaded area indicates  
a minimum clearance  
of 18" (457mm) for  
proper air flow  
C
Shaded area indicates  
a minimum clearance  
of 24" (610mm) for component  
access and removal  
SL-11081  
Shaded area indicates  
a minimum clearance  
of 18" (457mm) for  
proper air flow  
Removable (Front) Panel  
for access to high-voltage and  
low-voltage connections and  
refrigeration components  
Pg. 4  
Liquid Line  
Quick Connect  
(Male Coupling)  
Suction Line  
A
Quick Connect  
(Male Coupling)  
Except as noted  
F
G
Electrical Entrance  
for High-Voltage  
Connection  
B
C
Electrical Entrance  
for Low-Voltage  
Connection  
D
SL-11081  
Pg. 6  
E
®
Liebert Challenger 3000  
62  
   
Split System Models  
Table 26 Horizontal air discharge cabinet and floor planning dimensional data  
Model Numbers  
Dimensional Data in. (mm)  
Module  
Weight  
60 Hz  
50 Hz  
PFC041A-_L  
A
B
C
lb (kg) net  
PFC042A-_L  
PFH042A-_L  
48 (1219)  
31 (787)  
18 (457)  
241 (109)  
PFC042A-_H PFC041A-_H  
PFH042A-_H  
PFCZ42A-_L  
PFC067A-_L  
PFH067A-_L  
PFCZ41A-_L 53 (1343) 36-1/4 (918) 18 (457)  
351 (159)  
PFC066A-_L  
Table 27 Horizontal air discharge piping and electrical connection data  
Model Numbers Dimensional Data in. (mm) Piping Connections in. (mm)  
60 Hz  
50 Hz  
PFC041A-_L  
A
B
C
D
E
F
G
PFC042A-_L  
PFH042A-_L  
2 (51) 5-3/4 (146) 8-1/2 (216) 4-3/4 (121) 6-3/4 (171)  
8-1/2 (216)  
PFC042A-_H PFC041A-_H  
PFH042A-_H PFCZ41A-_L  
PFCZ42A-_L  
PFC067A-_L  
PFH067A-_L  
PFC066A-_L  
2 (51)  
6 (152)  
8-1/2 (216) 4-3/4 (121) 7-3/4 (197)  
8-1/2 (216)  
®
63  
Liebert Challenger 3000  
   
Split System Models  
Figure 33 Outdoor air-cooled condensing unit—top air discharge models  
Guard Height  
Top Air  
Discharge  
D
Right Air  
Discharge  
UNIT DIMENSIONS  
B
Shaded area indicates  
Left Air  
Intake  
a minimum clearance  
of 18" (457mm) for  
proper air flow  
2"  
(51mm)  
A
C
Shaded area indicates  
a minimum clearance  
of 18" (457mm) for  
Shaded area indicates  
a minimum clearance  
of 24" (610mm) for component  
access and removal  
Removable (Front) Panel  
for access to high-voltage and  
low-voltage connections and  
refrigeration components  
proper air flow  
36-1/8"  
(918mm)  
53-3/16"  
(1351mm)  
4" (typ.)  
(102mm)  
2" (typ.)  
(51mm)  
FOOTPRINT  
1/2" (13mm)  
Bolt-Down Holes  
6 places  
DIMENSIONS  
4-23/32"  
(120mm)  
32-1/8"  
(816mm)  
25-3/32"  
(637mm)  
2"  
(51mm)  
46-7/32"  
(1174mm)  
SL-11081  
Pg. 5  
Electrical Entrance  
for High-Voltage Connection  
A
F
G
PIPING & ELECTRICAL  
CONNECTIONS  
(see Table 29)  
B
C
Electrical Entrance  
for Low-Voltage  
Connection  
Liquid Line  
Quick Connect  
(Male Coupling)  
D
Suction Line  
Quick Connect  
(Male Coupling)  
SL-11081  
Pg. 7  
E
®
Liebert Challenger 3000  
64  
 
Split System Models  
Table 28 Cabinet and floor planning dimensional data - prop fan condensing modules, top air discharge  
Model Numbers  
Dimensional Data in. (mm)  
Module  
Weight  
60 Hz  
50 Hz  
PFC066A-_H  
A
B
C
D
lb (kg) net  
PFC067A-_H  
PFH067A-_H  
PFCZ67A-_L  
53 (1343)  
36-1/4 (918)  
38-1/2 (978)  
5-1/2 (140)  
488 (222)  
PFCZ66A-_L  
Table 29 Piping and electrical connections - top air discharge  
Model Numbers Dimensional Data in. (mm) Piping Connections in. (mm)  
60 Hz  
50 Hz  
PFC066A-_H  
A
B
C
D
E
F
PFC067A-_H  
PFH067A-_H  
PFCZ67A-_L  
2 (51)  
6 (152)  
8-1/2 (216)  
4-3/4 (121)  
7-3/4 (197)  
8-1/2 (216)  
PFCZ66A-_L  
®
65  
Liebert Challenger 3000  
   
Split System Models  
Figure 34 Electrical field connections, prop fan condensing module  
TOP AIR  
DISCHARGE MODELS  
(5-Ton High Ambient  
& 5-Ton Quiet-Line)  
Field-supplied unit  
disconnect switch  
HORIZONTAL AIR DISCHARGE MODELS  
Field-supplied 24V NEC  
Class 2 wiring to  
evaporator module  
Single- or  
3-phase electric  
service; not by  
Liebert  
SL-11081  
Pg. 8A  
Single- or  
3-phase  
electric  
service; not  
by Liebert  
Field-supplied 24V  
NEC Class 2 wiring  
to evaporator  
module  
Factory-wired  
to components on  
electric panel.  
Electric service  
connection to contactor  
or terminal block  
Single- or 3-phase  
electric service; not  
by Liebert  
High-voltage electric  
power supply entrance  
Low-voltage electric  
power supply entrance  
Heat rejection connection. Field  
supplied 24V NEC class 2 wiring.  
Wire connections from evaporator module:  
1. 24V GND  
Earth ground connection  
terminal for field wiring.  
2. 24V Supply  
3. High Pressure Alarm  
4. Hot Gas Bypass Connection  
(only on units with hot gas bypass.  
If no hot gas bypass, connection is  
provided in the evaporator module.  
Connect wire 4 with wire 2 to the  
24V supply).  
NOTE: Refer to specification sheet for full load amp  
and wire size amp ratings  
SL-11081 Pg. 8  
®
Liebert Challenger 3000  
66  
 
Split System Models  
7.5  
Centrifugal Air-Cooled Condensing Units  
7.5.1 Installing the Indoor Condensing Unit  
Refer to drawings for unit dimensions and component locations.  
WARNING  
!
Risk of ceiling collapse and heavy unit falling. Can cause equipment and building damage,  
serious injury or death.  
Verify that the supporting roof structure is capable of supporting the weight of the unit(s) and  
the accessories during installation and service. (See Table 30 - Indoor centrifugal  
Be sure to securely anchor the top ends of the suspension rods. Make sure all nuts are tight.  
The indoor condensing unit is usually mounted above the ceiling and must be securely mounted to the  
roof structure. The ceiling and ceiling supports of existing buildings may require reinforcements. Be  
sure to follow all applicable national, state and local building, plumbing and electrical codes. Use  
field-supplied threaded suspension rods and 3/8"-16 factory hardware kit.  
The indoor condensing unit must be located at the same level or above the Liebert Challenger 3000  
unit. It must NOT be located below the Liebert Challenger 3000.  
Recommended clearance between ceiling grids and building structural members is unit height plus  
3 inches (76.2mm).  
Install the four field-supplied rods by suspending them from suitable building structural members.  
Locate the rods so that they will align with the four mounting holes in the flanges that are part of the  
unit base.  
Using a suitable lifting device, raise the unit up and pass the threaded rods through the four  
mounting holes in the flanges that are part of the unit base.  
Attach the threaded rods to the unit flanges using the supplied nuts and grommets. (See Figure 35 -  
Detail of ceiling hanging bracket, Threaded Rod and Hardware Kit Installation). The rubber  
grommets provide vibration isolation.  
1. Use the plain nuts to hold unit in place. Adjust these nuts so that the weight of the unit is  
supported evenly by the four rods, does not rest on the ceiling grid, and is level.  
NOTE  
The units must be level in order to operate properly.  
2. Use the Nylock nuts to “jam” the plain nuts.  
Table 30 Indoor centrifugal condensing unit  
Model  
Net Weight  
60 Hz  
50 Hz  
lb (kg)  
MC_40A  
MC_65A  
MC_39A  
MC_64A  
240 (109)  
449 (204)  
®
67  
Liebert Challenger 3000  
     
Split System Models  
Figure 35 Detail of ceiling hanging bracket  
3/8" threaded rod  
(field-supplied)  
3/8" hex nut  
3/8" washer  
Sleeve  
Isolator  
3/8" fender washer  
3/8" hex nut  
3/8" hex nut  
Nylock  
Unit base pan (ref)  
7.5.2 Ducting  
The total external static pressure for the inlet and outlet ducts, including grille, must not exceed  
0.5 inches of H O. Hood intake dimensions should be the same as the condensing unit duct  
2
dimensions.  
If the condensing unit is located close to the outside of the building, rain hoods must be installed. In  
addition, install a triple layer bird screen over rain hood openings to eliminate the possibility of  
insects, birds, water, or debris entering the unit.  
Use flexible ductwork or nonflammable cloth collars to attach ductwork to the unit and to control  
vibration transmission to the building. Attach the ductwork to the unit using the flanges provided.  
Locate the unit and ductwork so that the return air does not short circuit to the supply air inlet.  
Avoid directing the hot exhaust air toward adjacent doors or windows.  
Normal operating sound may be objectionable if the condensing unit is placed directly over quiet work  
areas. Ductwork that runs through a conditioned space or is exposed to areas where condensation  
may occur must be insulated. Whenever possible, ductwork should be suspended using flexible  
hangers. Ductwork should not be fastened directly to the building structure. In applications where  
the ceiling plenum is used as the heat rejection domain, the discharge air must be directed away from  
the condensing unit air inlet and a screen must be added to the end of the discharge duct to protect  
service personnel.  
For multiple unit installations, space the units so that the hot condensing unit exhaust air is not  
directed toward the air inlet of an adjacent unit.  
Table 31 Airflow CFM (CMH)  
3-Ton  
5-Ton  
60 Hz  
50 Hz  
2000 (3398)  
1650 (2800)  
3500 (5947)  
3500 (5947)  
®
Liebert Challenger 3000  
68  
     
Split System Models  
Figure 36 3-ton centrifugal air-cooled condensing unit dimensional data & piping connections  
Customer-supplied  
threaded rods for ꢀ  
module supportꢀ  
22-3/4" (578mm)  
Overall Dimension  
50-1/4" (1276mm)  
Overall Dimension  
21-1/2" (546mm)  
Cabinet Dimension  
from ceiling (typ. 4)  
46-1/2" (1181mm)  
Cabinet Dimension  
C
19-1/2" (495mm)  
Threaded Rod  
Centers  
48-1/4" (1225mm)  
Threaded Rod Centers  
1/2" (13mm)  
D
Air Outlet  
20-3/4"  
(527mm)  
Duct Connection  
22-1/2"  
(572mm)  
Cabinet  
20-7/16"  
(519mm)  
Coil Inlet  
Duct  
Air Outlet  
Duct Dimension  
Dimension  
B
Conn.  
A
30-1/8"  
(765mm)  
Coil Inlet  
Duct Connection  
Blower Motor Service Access  
Panel on Bottom of Unit  
Minimum Clearance 33" (838mm)  
for ComponentAccess and Removal.  
Holes for Module  
Rigging (typ. 2 each end)  
1"  
Duct Flange  
Integral Hanging  
Bracket  
(25.4mm)  
2-1/4"  
Note:Unit is evenly spaced in  
reference to threaded for centers.  
(57mm)  
Minimum Clearance 33" (838mm)  
This End for ComponentAccess  
and Removal  
DIMENSIONAL DATA  
7/8" (22.2mm) Dia.  
Electrical Entrance  
for Line-Voltage  
Connection  
7/8" (22.2mm) Dia.  
Electrical Entrance  
for Low-Voltage  
Connection  
Suction Line  
Male Quick  
Connect  
Liquid Line  
Male Quick  
Connect  
PIPING CONNECTIONS  
SL-11085 Pg. 4  
®
69  
Liebert Challenger 3000  
 
Split System Models  
Figure 37 3-ton centrifugal air-cooled condensing unit (con’t.)  
Field-supplied unit disconnect  
switch when optional disconnect  
is not provided in unit  
Single- or three-phase  
electric service  
not by Liebert  
Field-supplied 24V  
NEC Class 2 wiring  
to fan/coil unit  
Factory-wired  
to components  
on electric panel  
Optional factory-installed  
disconnect switch  
Line voltage electric power  
supply conduit entrance  
Single- or three-phase  
electric service  
not by Liebert  
Connection terminal  
for field-supplied  
grounding wire  
Low-voltage electric  
power supply entrance  
Heat rejection connection.  
Field-supplied 24V NEC  
Class 2 wiring. See NOTE 2.  
DPN000207  
Rev0  
Wire connections from evaporator  
mod:  
1. 24V ground  
2. 24V supply  
NOTES:  
3. High-pressure alarm (optional)  
4. Hot gas bypass connection  
(only on units with hot gas  
bypass)  
1. Refer to specification sheet for full load amp. and wire size amp. ratings.  
2. Control voltage wiring must be a minimum of 16 GA (1.6mm) for up to 75' (23m)  
or not to exceed 1 volt drop in control line.  
®
Liebert Challenger 3000  
70  
 
Split System Models  
Figure 38 5-ton centrifugal air-cooled condensing unit dimensional data  
32"  
(812.8mm)  
Cabinet  
54"  
(1371.6mm)  
Cabinet  
Dimension  
Dimension  
1-5/8"  
(41.1mm)  
15-3/4"  
(400mm)  
48"  
(1219.2mm)  
8-15/16"  
(227mm)  
Customer-supplied  
threaded rods for  
module support  
3-3/8"  
(85.7mm)  
from ceiling (typ. 4)  
14-1/2"  
(368.3mm)  
24"  
(610mm)  
Cabinet  
Dimension  
21-1/4"  
(539.8mm)  
Shaded area indicates a  
recommended clearance of  
30" (762mm) for component  
access and removal.  
1-3/4"  
(44.5mm)  
Hanger  
Bracket  
33-5/8"  
51-13/16"  
(1316mm)  
Threaded Rod  
Centers  
(854.1mm)  
Threaded Rod  
Centers  
NOTE: Unit is spaced evenly in  
reference to threaded  
rod centers.  
1/2" (12.7mm) dia. holes for  
threaded rods (typ. 2 each end)  
7/8" (22.2mm) & 1-1/8" (28.6mm)  
dia. knockouts electrical entrance for high-  
voltage connection (Single Point Power Kit)  
7/8" (22.2mm) & 1-1/8" (28.6mm)  
dia. knockouts electrical entrance  
for high-voltage connection  
Single Point Power Kit  
connection to Evaporator  
Air  
Air Inlet  
Outlet  
Liquid Line male quick  
connect location  
Suction Line male quick  
connect location  
7/8" (22.2mm) dia.  
electrical entrance  
for low voltage connection  
7/8" (22.2mm) dia. knockout  
electrical entrance for alternate  
control panel low-voltage routing  
SL-11087 Pg. 4  
®
71  
Liebert Challenger 3000  
 
Split System Models  
Figure 39 5-ton centrifugal air-cooled condensing unit dimensional data (con’t.)  
Field-Supplied Unit Disconnect  
Switch when Factory Unit  
Disconnect Switch is not Supplied  
Electric service  
not by Liebert  
Optional  
Factory-Installed  
Disconnect Switch  
AIR COOLED  
Line Voltage Electric Power  
Supply Conduit Voltage  
Connection terminal  
for field-supplied  
earth grounding wire  
Removable Access Panels  
Heat rejection connection. Field-supplied  
24V NEC Class 2 wiring. See Note 2.  
Wire connections from evaporator module.  
1. 24V GND  
Field-Supplied 24V NEC Class 2  
wiring between condensing unit  
and fan/coil unit  
Low-voltage  
electric power  
supply conduit  
entrance  
2. 24V supply  
3. High pressure alarm (optional)  
4. Hot gas bypass connection (only on  
units with hot gas bypass)  
NOTES:  
Refer to specification sheet for full load amp and wire size amp ratings.  
Control voltage wiring must be a minimum of 16 GA (1.6mm) for up  
to 75’ (23m) or not to exceed 1 volt drop in control line.  
DPN000226  
Rev0  
®
Liebert Challenger 3000  
72  
 
Split System Models  
Figure 40 Split systems general arrangement  
Hot-Gas  
Bypass Solenoid  
Valve  
High-Pressure  
Switch  
Condenser  
Coil  
Scroll  
Compressor  
1/2" (12.7mm) NPT  
Pressure Relief Valve  
Liquid Injection  
Valve Bulb  
Suction Line  
Male Quick  
Connect  
Check  
Valve  
Sight  
Glass  
AIR COOLED  
Suction Line  
Female Quick  
Connect  
Coupling*  
Lee-Temp  
Receiver  
Head-Pressure  
Service  
Access  
Ports  
Control with  
Integral Check  
Valve  
Coupling*  
Pressure  
Balancing  
Valve  
Tube in  
Tube  
Condenser  
Hot-Gas  
External  
Equalizer  
Liquid  
Sensing  
Bulb  
Bypass Control  
Valve  
Receiver Heater  
Pressure Limiting  
Switch  
Injection  
Valve  
Liquid Line  
Male Quick  
Connect  
Filter  
Dryer  
Liquid Line  
Coupling* Solenoid Valve  
Liquid Line  
High-Pressure  
Switch  
Female Quick  
Connect  
Coupling*  
Scroll  
Compressor  
Expansion  
Valve  
Hot-Gas  
Liquid Injection  
Valve Bulb  
Bypass  
Solenoid  
Valve  
Evaporator  
Coil  
Water/Glycol  
Return  
Line  
Water/Glycol  
Supply Line  
Suction Line  
Male Quick  
Connect  
WATER COOLED  
GLYCOL COOLED  
Fluid Return  
from Unit  
Coupling*  
Suction Line  
Female Quick  
Service  
Access  
Ports  
Shutoff  
Valves *  
Connect  
Coupling*  
Fluid Supply  
to Unit  
Hot-Gas  
External  
Equalizer  
Bypass Control  
Valve  
Liquid  
Sensing  
Bulb  
Tube in  
Tube  
Condenser  
Injection  
Valve  
2-Way Water  
Regulating Valve  
Liquid Line  
Male Quick  
Connect  
Filter  
Dryer  
Liquid Line  
Female Quick  
Connect  
Coupling*  
Hose Bibs *  
Coupling*  
Expansion  
Valve  
Evaporator  
Coil  
FACTORY PIPING  
OPTIONAL PIPING  
* Components are not supplied by Liebert but  
are recommended for proper circuit operation  
maintenance.  
Fluid  
Return  
from Unit  
SL-11900 Pg. 5  
Fluid Supply  
to Unit  
3-Way Water  
Regulating Valve (optional)  
®
73  
Liebert Challenger 3000  
 
Split System Models  
7.6  
Water and Glycol-Cooled Condensing Units  
For installation guidelines, refer to Installing the Indoor Condensing Unit on page 67.  
7.6.1 Piping Considerations  
It is recommended that manual service shutoff valves be installed at the supply and return line to  
each unit. This will provide for routine service or emergency isolation of the unit.  
When the water source for the condenser is of poor quality, it is good practice to provide cleanable  
filters in the supply line. These filters will trap the particles in the water supply and extend the  
service life of the water-cooled condenser.  
3-Ton Connection Sizes  
Condenser Water Inlet 7/8" OD Cu  
Condenser Water Outlet 7/8" OD Cu  
Suction Line 1-1/8 - 12 male #11 quick connect  
Liquid Line: 5/8 - 18 male #6 quick connect  
5-Ton Connection Sizes  
Condenser Water Inlet 1-1/8" OD Cu  
Condenser Water Outlet 1-1/8" OD Cu  
Suction Line 1-7/16" - 16 male #12 quick connect  
Liquid Line 1-1/16" - 12 male #10 quick connect  
Table 32 Water and glycol-cooled condensing unit data  
Net Weight, Glycol Volume,  
Model  
lb (kg)  
gal (l)  
MC_44W  
MC_43W  
200 (91)  
1.7 (6.4)  
MC_69W  
MC_68W  
282 (128)  
2.0 (7.6)  
7.6.2 Condenser Water Requirements  
The standard maximum water pressure is 150 psig (1034 kPa). For applications above this pressure,  
consult the factory about high pressure systems.  
The system will operate in conjunction with a cooling tower, city water, or drycooler.  
7.6.3 Regulating Valve  
®
Liebert Challenger 3000  
74  
         
Split System Models  
7.6.4 Glycol Systems  
For split system glycol systems, use drycooler and pump data found in 5.0 - Glycol/GLYCOOL-  
Electrical control interconnect to drycooler is wired from water/glycol condensing unit.  
Figure 41 3-ton water/glycol-cooled condensing unit  
8-7/8" (225mm)  
14" (356mm)  
Overall Cabinet  
Dimension  
50-1/4" (1276mm)  
Overall Dimension  
3-7/8" (98mm)  
48-1/4" (1225mm)  
Threaded Rod Centers  
12" (305mm)  
Threaded Rod  
Centers  
8-7/16" (214mm)  
46-1/2" (1181mm)  
Cabinet Dimension  
20-3/4"  
(527mm)  
22-1/2"  
(572mm)  
Customer-Supplied  
Threaded Rods for Module  
Support from Ceiling (typ. 4)  
Cabinet  
Dimension  
Outlet  
Inlet  
Holes for Module  
Rigging (typ. 2 each end)  
Minimum Clearance  
DIMENSIONAL DATA  
33" (838mm) This side  
for component access  
and removal  
Integral Hanging Bracket  
3/4" (19mm) NPT Female  
Water/Glycol Inlet Connection  
7/8" (22mm) Dia.  
3/4" (19mm) NPT Female  
Water/Glycol Outlet Connection  
Electrical Entrance  
for High-Voltage  
Connection  
Suction Line  
Male Quick  
Connect  
Liquid Line  
Male Quick  
Connect  
PIPING CONNECTIONS  
7/8" (22mm) Dia.  
Electrical Entrance  
for Low-Voltage Connection  
SL-11085 Pg. 6  
®
75  
Liebert Challenger 3000  
   
Split System Models  
Figure 42 3-ton water/glycol-cooled condensing unit (con’t.)  
Single- or  
Field-supplied unit disconnect  
switch when optional disconnect  
is not provided in unit  
three-phase  
electric service  
not by Liebert  
Field-supplied 24V NEC Class 1  
wiring to fan/coil unit  
Field-supplied 24V NEC Class 1  
wiring to drycooler  
(glycol-cooled units only)  
Earth/ground connection  
Connection terminal for field-supplied  
earth-grounding wire  
Factory-wired components  
on electric panel  
Line-voltage electric  
power supply entrance  
Optional factory-installed  
disconnect switch  
Low-voltage electric  
power supply entrance  
Remote drycooler connection  
Terminals 70 & 71 supplied  
for connection to remote drycooler  
Use field-supplied 24V NEC Class 1  
wiring (glycol-cooled units only)  
Heat rejection connection.  
Field-supplied 24V NEC Class 2 wiring.  
Wire connections from evaporator mod:  
1. 24V GND  
NOTES  
2. 24V supply  
1. Refer to specification sheet for full load amp  
and wire size amp ratings.  
3. High-pressure alarm (optional)  
4. Hot gas bypass connection  
(only on units with hot-gas bypass)  
2. Control voltage wiring must be a minimum  
of 16 GA (1.6mm) for up to 75' (23m) or  
not to exceed 1 volt drop in control line.  
DPN000209  
Rev. 0  
®
Liebert Challenger 3000  
76  
 
Split System Models  
Figure 43 5-ton water/glycol-cooled condensing unit dimensional data  
32"  
32"  
(812.8mm)  
(812.8mm)  
Cabinet  
Dimension  
Dimension  
Customer-supplied  
threaded rods  
for module support  
from ceiling (typ. 4).  
Cabinet  
Removable  
Access Panel  
1/2" (12.7mm) dia. holes for  
module rigging (typ. 2 each end)  
24 "  
(610mm)  
Cabinet  
Hanger  
Bracket  
Dimension  
33-5/8"  
(854.1mm)  
Threaded Rod  
Shaded area indicates a  
29-13/16 "  
recommended clearance of  
(757.2mm)  
30" (762mm) for component  
Threaded Rod  
Centers  
access and removal.  
Centers  
NOTE: Unit is evenly spaced in reference  
to threaded rod centers.  
7/8" (22.2mm) & 1-1/8" (28.6mm)  
dia. knockouts electrical entrance  
for line voltage connection  
7/8" (22.2mm) & 1-1/8" (28.6mm)  
dia. knockouts electrical entrance for  
8-7/16"  
(214.4mm)  
line voltage connection (Single Point  
Power Kit)  
3-3/4"  
(95.2mm)  
7"  
(177.8mm)  
Suction Line male quick  
connect location  
1" (25.4mm) NPT Female  
Water/Glycol Inlet Connection  
Liquid Line male quick  
connect location  
1" (25.4mm) NPT Female  
Water/Glycol Outlet Connection  
7/8" (22.2mm) dia. electrical entrance  
for low-voltage connection  
7/8" (22.2mm) dia. knockout  
electrical entrance for alternate  
control panel low-voltage routing  
SL-11087  
Pg. 6  
®
77  
Liebert Challenger 3000  
 
Split System Models  
Figure 44 5-ton water/glycol-cooled condensing unit (con’t.)  
Field-supplied unit disconnect  
switch when factory unit  
disconnect switch is not suplied  
Electric service;  
not by Liebert  
WATER/GLYCOL  
Optional factory-installed  
disconnect switch  
Field-supplied 24V  
NEC Class 1 wiring  
to fan/coil unit  
Field-supplied 24V  
NEC Class 1 wiring  
to drycooler  
(glycol-cooled units only)  
Line voltage electric  
power supply conduit voltage  
Removable  
Access Panel  
Heat rejection connection.  
Connection terminal  
Field-supplied 24V NEC Class 2 wiring.  
Wire connections from evaporator mod:  
1. 24V ground  
for field-supplied  
earth grounding wire  
2. 24V supply  
3. High pressure alarm (optional)  
4. Hot gas bypass connection  
(only on units with hot gas bypass)  
Low-voltage electric  
power supply conduit  
entrance  
Field-supplied 24V NEC  
Remote drycooler  
Class 1 wiring between  
glycol condensing unit  
and drycooler  
connection; field-supplied  
24V NEC Class 1 wiring  
(glycol-cooled units only)  
DPN000228  
Rev. 0  
NOTES  
1. Refer to specification sheet for full load amp. and wire size amp. ratings.  
2. Control voltage wiring must be a minimum of 16 GA (1.6mm) for up to 75' (23m)  
or not to exceed 1 volt drop in control line.  
®
Liebert Challenger 3000  
78  
 
R407C Refrigerant  
8.0 R407C REFRIGERANT  
Table 33 R407C pressure/temperature chart for operation and superheat (discharge/hot gas and suction  
gas)  
Temperature  
Gauge Pressure  
Temperature  
Gauge Pressure  
Temperature  
Gauge Pressure  
°F  
°C  
Psig  
18.9  
19.6  
20.4  
21.2  
22.0  
22.8  
23.6  
24.5  
25.4  
26.2  
27.1  
28.0  
28.9  
29.9  
30.8  
31.8  
32.8  
33.8  
34.8  
35.8  
36.9  
38.0  
39.0  
40.1  
41.3  
42.4  
43.6  
44.7  
45.9  
47.1  
48.4  
49.6  
50.9  
52.1  
53.5  
-
kPa  
130  
135  
141  
146  
152  
157  
163  
169  
175  
181  
187  
193  
200  
206  
213  
219  
226  
233  
240  
247  
254  
262  
269  
277  
284  
292  
300  
308  
317  
325  
333  
342  
351  
359  
369  
-
°F  
°C  
1.7  
Psig  
54.8  
56.1  
57.5  
58.9  
60.3  
62.2  
63.1  
64.6  
66.1  
67.6  
69.1  
70.7  
72.2  
73.8  
75.4  
77.1  
78.7  
80.4  
82.1  
83.9  
85.6  
87.4  
89.2  
91.0  
92.9  
94.8  
96.7  
98.6  
100.5  
102.5  
104.5  
106.5  
108.6  
110.7  
112.8  
-
kPa  
378  
387  
396  
406  
415  
429  
435  
445  
456  
466  
476  
487  
498  
509  
520  
531  
543  
554  
566  
578  
590  
603  
615  
628  
640  
653  
666  
680  
693  
707  
721  
735  
749  
763  
778  
-
°F  
°C  
Psig  
114.9  
119.3  
124  
128  
133  
138  
143  
148  
153  
158  
164  
169  
175  
181  
187  
193  
199  
205  
212  
219  
225  
232  
239  
247  
254  
262  
269  
277  
285  
294  
302  
311  
320  
329  
338  
347  
kPa  
792  
0.0  
-17.8  
-17.2  
-16.7  
-16.1  
-15.6  
-15.0  
-14.4  
-13.9  
-13.3  
-12.8  
-12.2  
-11.7  
-11.1  
-10.6  
-10.0  
-9.4  
-8.9  
-8.3  
-7.8  
-7.2  
-6.7  
-6.1  
-5.6  
-5.0  
-4.4  
-3.9  
-3.3  
-2.8  
-2.2  
-1.7  
-1.1  
-0.6  
0.0  
35.0  
36.0  
37.0  
38.0  
39.0  
40.0  
41.0  
42.0  
43.0  
44.0  
45.0  
46.0  
47.0  
48.0  
49.0  
50.0  
51.0  
52.0  
53.0  
54.0  
55.0  
56.0  
57.0  
58.0  
59.0  
60.0  
61.0  
62.0  
63.0  
64.0  
65.0  
66.0  
67.0  
68.0  
69.0  
-
70.0  
21.1  
22.2  
23.3  
24.4  
25.6  
26.7  
27.8  
28.9  
30.0  
31.1  
32.2  
33.3  
34.4  
35.6  
36.7  
37.8  
38.9  
40.0  
41.1  
42.2  
43.3  
44.4  
45.6  
46.7  
47.8  
48.9  
50.0  
51.1  
52.2  
53.3  
54.4  
55.6  
56.7  
57.8  
58.9  
60.0  
1.0  
2.2  
72.0  
822  
2.0  
2.8  
74.0  
853  
3.0  
3.3  
76.0  
885  
4.0  
3.9  
78.0  
917  
5.0  
4.4  
80.0  
950  
6.0  
5.0  
82.0  
984  
7.0  
5.6  
84.0  
1019  
1054  
1091  
1128  
1167  
1206  
1246  
1287  
1329  
1372  
1416  
1461  
1507  
1553  
1601  
1650  
1701  
1752  
1804  
1858  
1912  
1968  
2025  
2083  
2143  
2203  
2265  
2329  
2393  
8.0  
6.1  
86.0  
9.0  
6.7  
88.0  
10.0  
11.0  
12.0  
13.0  
14.0  
15.0  
16.0  
17.0  
18.0  
19.0  
20.0  
21.0  
22.0  
23.0  
24.0  
25.0  
26.0  
27.0  
28.0  
29.0  
30.0  
31.0  
32.0  
33.0  
34.0  
-
7.2  
90.0  
7.8  
92.0  
8.3  
94.0  
8.9  
96.0  
9.4  
98.0  
10.0  
10.6  
11.1  
11.7  
12.2  
12.8  
13.3  
13.9  
14.4  
15.0  
15.6  
16.1  
16.7  
17.2  
17.8  
18.3  
18.9  
19.4  
20.0  
20.6  
-
100.0  
102.0  
104.0  
106.0  
108.0  
110.0  
112.0  
114.0  
116.0  
118.0  
120.0  
122.0  
124.0  
126.0  
128.0  
130.0  
132.0  
134.0  
136.0  
138.0  
140.0  
0.6  
1.1  
-
NOTE  
Use this table for superheat and for control adjustment (e.g., pressure switches). See  
Table 34 for subcooling.  
®
79  
Liebert Challenger 3000  
   
R407C Refrigerant  
Table 34 R407C pressure/temperature chart for subcooling only (liquid measurements)  
Temperature Pressure Gauge Temperature Pressure Gauge Temperature  
Pressure Gauge  
°F  
°C  
2.2  
Psig  
73  
kPa  
500  
511  
522  
533  
544  
556  
567  
579  
591  
602  
615  
627  
639  
652  
664  
677  
690  
704  
717  
730  
744  
758  
772  
-
°F  
°C  
Psig  
114  
116  
118  
120  
123  
125  
127  
129  
131  
134  
136  
138  
143  
148  
153  
158  
163  
169  
174  
180  
185  
191  
197  
-
kPa  
786  
°F  
°C  
Psig  
203  
209  
216  
222  
229  
236  
242  
249  
257  
264  
271  
279  
287  
294  
302  
310  
319  
327  
336  
345  
354  
363  
372  
381  
kPa  
1402  
1444  
1488  
1532  
1578  
1624  
1671  
1720  
1769  
1819  
1870  
1922  
1975  
2029  
2085  
2141  
2198  
2256  
2315  
2376  
2437  
2500  
2563  
2628  
36.0  
37.0  
38.0  
39.0  
40.0  
41.0  
42.0  
43.0  
44.0  
45.0  
46.0  
47.0  
48.0  
49.0  
50.0  
51.0  
52.0  
53.0  
54.0  
55.0  
56.0  
57.0  
58.0  
-
59.0  
60.0  
61.0  
62.0  
63.0  
64.0  
65.0  
66.0  
67.0  
68.0  
69.0  
70.0  
72.0  
74.0  
76.0  
78.0  
80.0  
82.0  
84.0  
86.0  
88.0  
90.0  
92.0  
-
15.0  
15.6  
16.1  
16.7  
17.2  
17.8  
18.3  
18.9  
19.4  
20.0  
20.6  
21.1  
22.2  
23.3  
24.4  
25.6  
26.7  
27.8  
28.9  
30.0  
31.1  
32.2  
33.3  
-
94.0  
34.4  
35.6  
36.7  
37.8  
38.9  
40.0  
41.1  
42.2  
43.3  
44.4  
45.6  
46.7  
47.8  
48.9  
50.0  
51.1  
52.2  
53.3  
54.4  
55.6  
56.7  
57.8  
58.9  
60.0  
2.8  
74  
801  
96.0  
3.3  
76  
815  
98.0  
3.9  
77  
830  
100.0  
102.0  
104.0  
106.0  
108.0  
110.0  
112.0  
114.0  
116.0  
118.0  
120.0  
122.0  
124.0  
126.0  
128.0  
130.0  
132.0  
134.0  
136.0  
138.0  
140.0  
4.4  
79  
845  
5.0  
81  
860  
5.6  
82  
875  
6.1  
84  
891  
6.7  
86  
906  
7.2  
87  
922  
7.8  
89  
938  
8.3  
91  
954  
8.9  
93  
987  
9.4  
95  
1021  
1055  
1090  
1126  
1163  
1201  
1239  
1279  
1319  
1360  
-
10.0  
10.6  
11.1  
11.7  
12.2  
12.8  
13.3  
13.9  
14.4  
-
96  
98  
100  
102  
104  
106  
108  
110  
112  
-
NOTE  
Use this table for subcooling calculation ONLY. See Table 33 for superheat or control  
adjustment.  
8.1  
Calculating Subcooling  
Example  
Measure the liquid pressure (e.g., 200 psig). Find the liquid saturation temperature at that pressure  
on Table 34 (e.g., 93°F). Measure the temperature of the liquid line (e.g., 90°F). Subtract the actual  
temperature from the liquid saturation temperature to obtain the subcooling (e.g., 93 – 90 = 3°F). If  
the actual temperature is greater than the liquid saturation temperature, then there is no subcooling,  
and the fluid may be a mixture of liquid and vapor.  
Why There Are Two R407C Temperature and Pressure Tables  
R407C is a blend of refrigerants that exhibits a temperature “glide” of approximately 8 to 12°F  
(4 to 7°C). This “glide” is the difference between the liquid and vapor saturation temperatures at a  
given pressure. Use the correct table for the saturation temperature you need. Table 33 is for  
superheat or operating controls. Table 34 is for subcooling only.  
®
Liebert Challenger 3000  
80  
   
Ensuring The High Availability  
Of Mission-Critical Data And Applications.  
Emerson Network Power, a business of Emerson (NYSE:EMR),  
is the global leader in enabling Business-Critical Continuity™  
from grid to chip for telecommunication networks, data centers,  
health care and industrial facilities. Emerson Network Power  
provides innovative solutions and expertise in areas including  
AC and DC power and precision cooling systems, embedded  
computing and power, integrated racks and enclosures,  
power switching and controls, infrastructure management,  
and connectivity. All solutions are supported globally by local  
Emerson Network Power service technicians. Liebert AC power,  
precision cooling and monitoring products and services  
from Emerson Network Power deliver Efficiency Without  
Compromiseby helping customers optimize their data center  
infrastructure to reduce costs and deliver high availability.  
Technical Support / Service  
Web Site  
Monitoring  
800-222-5877  
Outside North America: +00800 1155 4499  
Single-Phase UPS & Server Cabinets  
800-222-5877  
Outside North America: +00800 1155 4499  
Three-Phase UPS & Power Systems  
800-543-2378  
Outside North America: 614-841-6598  
Environmental Systems  
800-543-2778  
Outside the United States: 614-888-0246  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Europe  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD) Italy  
+39 049 9719 111  
While every precaution has been taken to ensure the accuracy  
and completeness of this literature, Liebert Corporation assumes no  
responsibility and disclaims all liability for damages resulting from use of  
this information or for any errors or omissions.  
© 2009 Liebert Corporation  
All rights reserved throughout the world. Specifications subject to change  
without notice.  
® Liebert is a registered trademark of Liebert Corporation.  
All names referred to are trademarks  
or registered trademarks of their respective owners.  
Fax: +39 049 5841 257  
Asia  
29/F, The Orient Square Building  
F. Ortigas Jr. Road, Ortigas Center  
Pasig City 1605  
Philippines  
+63 2 687 6615  
Fax: +63 2 730 9572  
SL-11962_REV4_12-12  
Emerson Network Power.  
The global leader in enabling Business-Critical Continuity™  
EmersonNetworkPower.com  
AC Power  
Embedded Computing  
Outside Plant  
Racks & Integrated Cabinets  
Connectivity  
DC Power  
Embedded Power  
Power Switching & Controls  
Services  
Infrastructure Management & Monitoring  
Precision Cooling  
Surge Protection  
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies.  
©2009 Emerson Electric Co.  

Brada Appliances YPL3 10C User Manual
Briggs Stratton 193700 User Manual
Briggs Stratton 256700 User Manual
Bush Hog M246 User Manual
Bushnell Battery Charger PP2010 User Manual
Continental Electric CE11125 User Manual
Danby Premiere DPAC 11010 User Manual
Datamax All in One Printer E4203 User Manual
HoMedics BKP 300 2 User Manual
Honda Automobiles GX270 User Manual