Carrier JK034 074 User Manual

48FK,JK034-074  
50FK,FY,JK,JY034-104  
Variable-Air Volume Rooftop Units  
Controls Operation,  
and Troubleshooting  
CONTENTS  
Page  
Page  
NIGHT SETBACK CONTROL  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . 2  
UNIT SUPPLY AIR SET POINT ADJUSTMENT  
DEMAND UNIT (1-STAGE OR 2-STAGE)  
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13  
Rooftop Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
VAV Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Processor Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
P1 — SUPPLY-AIR SET POINT  
SUPPLY DUCT PRESSURE SET POINT ADJUSTMENT  
EXTERNAL ALARM SIGNAL  
REMOTE ECONOMIZER CONTROL  
Smoke Control Modes . . . . . . . . . . . . . . . . . . . . . . . . . 21  
FIRE SHUTDOWN MODE  
P2 — ECONOMIZER POSITION  
P3 — RESET LIMIT  
PRESSURIZATION MODE  
P4 — DEMAND LIMIT  
EVACUATION MODE  
P5 — ECONOMIZER MINIMUM POSITION  
P6 — WARM-UP SET POINT  
SMOKE PURGE MODE  
INSTALLATION  
P7 — SASP RESET TEMPERATURE  
PROCESSOR BOARD OUTPUTS  
CONFIGURATION  
OPERATING SEQUENCE  
CONFIGURATION HEADER AND DIP SWITCH  
ASSEMBLY  
Air Pressure Tubing . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
INLET GUIDE VANES  
Relay Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Display Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
T1 — SUPPLY-AIR TEMPERATURE THERMISTOR  
T2 — RETURN-AIR TEMPERATURE THERMISTOR  
T3 — SATURATED CONDENSING TEMPERATURE,  
CIRCUIT 1  
VARIABLE FREQUENCY DRIVE  
MODULATING POWER EXHAUST  
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-30  
Initial Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
Configuration Header . . . . . . . . . . . . . . . . . . . . . . . . . 26  
DIP Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
Adjusting Set Points . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
Potentiometers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
Supply Fan Control with IGV Option . . . . . . . . . . . . . 28  
Supply Fan Control with VFD Option . . . . . . . . . . . . 28  
Modulating Power Exhaust  
T4 — SATURATED CONDENSING TEMPERATURE,  
CIRCUIT 2  
T10 — RESET TEMPERATURE  
Compressor Operation . . . . . . . . . . . . . . . . . . . . . . . . . 7  
CONTROL RELAY (CR)  
Accessory Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
P3 — RESET LIMIT  
P5 — ECONOMIZER MINIMUM POSITION  
P6 — MORNING WARM-UP TEMPERATURE  
Single-Step Demand Unit . . . . . . . . . . . . . . . . . . . . . . . 7  
Demand Limit Control Module (DLCM) . . . . . . . . . . . . 7  
Economizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
ENTHALPY CONTROL  
(Option or Accessory) . . . . . . . . . . . . . . . . . . . . . . . 30  
START UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-34  
Quick Test Program . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
OPERATING INFORMATION . . . . . . . . . . . . . . . . . . . 34-43  
Digital Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
CODES 0 THROUGH 8, CAPACITY STEPS  
CODES 20 THROUGH 30 AND 88, OPERATIONAL  
STATUS  
DIFFERENTIAL ENTHALPY  
CODES 51 THROUGH 87, DIAGNOSTIC  
INFORMATION  
Operating Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
SIZE 034, 038 AND 048-088 UNITS  
SIZE 044 UNITS  
SIZE 104 UNITS  
Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . 36  
Supply Fan Control with IGV . . . . . . . . . . . . . . . . . . . 38  
Supply Fan Control with VFD . . . . . . . . . . . . . . . . . . . 38  
Modulating Power Exhaust (Option or  
Accessory Except FY,JY Units) . . . . . . . . . . . . . . . 38  
Unit Staging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38  
Variable Frequency Drive (VFD) . . . . . . . . . . . . . . . . . 12  
Temperature Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
CONTROLS INSTALLATION . . . . . . . . . . . . . . . . . . . 13-25  
Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
NIGHT SETBACK THERMOSTAT  
SPACE TEMPERATURE RESET ACCESSORY  
(50DJ900021)  
Space Temperature Reset . . . . . . . . . . . . . . . . . . . . . . 13  
INSTALLATION  
CONFIGURATION  
OPERATING SEQUENCE  
Demand Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18  
SINGLE-STEP DEMAND LIMIT  
TWO-STEP DEMAND LIMIT  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 44-57  
Checking Display Codes . . . . . . . . . . . . . . . . . . . . . . . 44  
Complete Unit Stoppage . . . . . . . . . . . . . . . . . . . . . . . 44  
Single Circuit Stoppage . . . . . . . . . . . . . . . . . . . . . . . 44  
Restart Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44  
Diagnostic Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
CODES 51, 52, 55, 56: COMPRESSOR FAILURE  
INSTALLATION  
CONFIGURATION  
OPERATING SEQUENCE  
Control From Remote Building Management  
System (BMS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
OCCUPIED/UNOCCUPIED  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1 PC 111 Catalog No. 534-716 Printed in U.S.A. Form 48/50F,J-1T Pg 1 4-99 Replaces: 48/50D,F,J-1T  
Tab 1a 1b  
1
LEGEND  
*EPROM HT204485-1-XX where ‘‘XX’’ is the current revision  
number.  
DIP  
EPROM  
EXV  
Dual In-Line Package  
Erasable, Programmable Read-Only Memory  
Electronic Expansion Valve  
NOTE: Processor Board is positioned in unit with J3 and J10 con-  
nections at the bottom.  
Do not remove label covering EPROM. Removal causes pro-  
gram to be erased.  
Fig. 1 — Processor Board  
Several temperature inputs are connected to the proces-  
sor. There are either 4 or 5 thermistors (depending on the  
field-installed accessories) which input temperature data  
into the processor through pin terminal connector J1. See  
Table 1 and Fig. 2.  
In addition to the unit status switch inputs, the processor  
board also accepts inputs from several potentiometers. These  
potentiometers control various operational characteristics of  
the system. Inputs are received by the processor through pin  
terminal connector J3. See Fig. 4.  
Several status switches are also monitored. These switches  
are connected to the processor at pin terminal connector J2.  
See Fig. 3 and Table 2.  
All of the potentiometers must be set before the unit is  
started in order for the unit to function properly. See Start-  
Up, Potentiometers section on page 28 for information on  
establishing set points. Each of the potentiometers has a valid  
range that is used by the control. The valid range is defined  
as the potentiometer’s resistance value that the control will  
not consider to be in error. This is usually between 10% and  
90% of the potentiometer’s total resistance. The control has  
been programmed to accept an operational range for the po-  
tentiometer, which may not be the same as the valid range.  
Table 1 — Pin Terminal Connector J1  
Thermistor Inputs  
CONNECTOR J1  
TERMINAL NO.  
TEMPERATURE  
INPUT  
UNIT SIZE  
034-104  
1,2  
Reset Temperature*  
T10  
Saturated Condensing  
Temp., Circuit 2  
14,15  
16,17  
T4  
Saturated Condensing  
Temp., Circuit 1  
T3  
18,19  
20,21  
Return-Air Temperature  
Supply-Air Temperature  
T2  
T1  
LEGEND  
T — Thermistor  
*If equipped with accessory temperature reset package.  
NOTE: Terminal numbers 3-13 are not used on these units.  
3
LEGEND  
CR  
Control Relay  
Enthalpy Control  
Low-Pressure Switch  
EC  
LEGEND  
Thermistor  
LPS  
T
Field Wiring  
Accessory  
Fig. 3 — Pin Terminal Connector J2  
Status Switch Inputs  
Fig. 2 — Pin Terminal Connector J1  
Thermistor Inputs  
Table 2 — Pin Terminal Connector J2  
Status Switch Inputs  
CONNECTOR J2  
TERMINAL NO.  
UNIT SIZE  
034-104  
STATUS SWITCH  
Oil Pressure,  
Circuit 2  
1,2  
Jumpered  
Oil Pressure,  
Circuit 1  
3,4  
Jumpered  
LPS2  
LPS1  
EC  
Loss Of Charge,  
Circuit 2  
7,8  
Loss of Charge,  
Circuit 1  
9,10  
Economizer  
Changeover  
13,14  
15,20  
15,24  
LEGEND  
Compressor Fault  
Signal  
CR2  
Compressor Fault  
Signal  
LEGEND  
CR1  
IN  
Input  
Factory Wiring  
Field Wiring  
Accessory  
P
Potentiometer  
Return  
RNT  
SW  
CR  
Control Relay  
Switch  
EC  
Enthalpy Control  
LPS  
Low-Pressure Switch  
Fig. 4 — Pin Terminal Connector J3  
Potentiometer Inputs  
NOTE: Terminal numbers 5, 6, 11, 12, 16-19, and 21-23 are not used  
on these units.  
4
The potentiometer locations and functions are as follows:  
The configuration header (part no. 30GB660001) is a  
series of 8 small wires that are broken or unbroken in a  
pattern to indicate several unique characteristics of the unit.  
The configuration header is factory set and should not be  
changed. Changing the factory setting may cause the unit to  
malfunction.  
The DIP switches configure the unit for several field-  
installed options, as well as for several other options that  
may be unique to the unit. The DIP switches are located un-  
der a plastic enclosure which must be removed for access.  
The switches can be field adjusted, but must be adjusted only  
when the unit control circuit breaker is off.  
P1 — SUPPLY-AIR SET POINT — This potentiometer is  
located on the display board. The supply-air set point is the  
cooling mode control temperature which the VAV control  
system will attempt to maintain at Thermistor T1 by con-  
trol of economizer position and/or cycling unloaders and  
compressors.  
P2 — ECONOMIZER POSITION — Economizer feedback  
potentiometer is located on the economizer motor. The micro-  
processor is programmed to indicate an alarm if the travel  
during initialization is less than 10% of the total potentiom-  
eter’s resistance. An alarm condition will also be signaled if  
the potentiometer fails during operation, indicating that the  
damper blades are stuck. If either situation occurs, the pro-  
cessor will try to drive the economizer dampers closed.  
Relay Board — The relay board is used to control 24-v  
and 115-v loads. See Fig. 5. The relay board is connected to  
the processor board by a ribbon cable at pin J9. Electrical  
connections to the relay board are made through pins J5  
(115 v) and J6 (24 v). The relay board has eight 24-v relays  
and five 115-v relays. See Table 3.  
P3 — RESET LIMIT — This potentiometer is located on  
the accessory board (provided standard from the factory) in  
the unit main control box and establishes the maximum amount  
of reset that can be applied to the supply-air set point (P1).  
Reset is limited by the P1 default of 70 F. This potentiom-  
eter is used only when accessory, field-installed temperature  
reset is used. If temperature reset is used, DIP (dual, in-line  
package) switch 2 must be in the ON position.  
Display Board — The display board is located in the  
main unit control box and is connected to the J10 port of the  
processor board through a ribbon cable. The display board  
contains the supply-air set point potentiometer P1; a 2-digit,  
LED display; and the display button (see Fig. 6). The LED  
display is used to convey the operating information and op-  
erational error codes.  
P4 — DEMAND LIMIT — This potentiometer is located  
near TRAN4 in the unit control box. The demand limit po-  
tentiometer is used only if accessory, field-installed demand  
limit is used, and if DIP switch 5 is in the ON position. For  
single-step demand limit, a field-installed 5 to 20 Kohm po-  
tentiometer and switch must be used.  
Thermistors — The processor uses up to 5 thermistors  
to sense the temperatures at various points in the system.  
See Table 1 and Fig. 7-14. All the thermistors have identical  
temperature versus resistance and voltage drop characteris-  
tics, and are monitored by the processor for a short or open  
circuit. The valid range for a thermistor is 362,640 to  
219 ohms. Thermistor details and locations are as follows:  
T1 — SUPPLY-AIR TEMPERATURE THERMISTOR —  
This thermistor is located in the unit supply fan discharge.  
It provides information for the processor to stage the num-  
ber of capacity steps required to maintain a desired supply-  
air temperature.  
P5 — ECONOMIZER MINIMUM POSITION — This po-  
tentiometer is on the accessory board (provided standard from  
the factory) located in the unit main control box. This po-  
tentiometer specifies the minimum opening position for the  
optional economizer. If a fault condition is detected by the  
processor, an alarm condition will be signaled and the econo-  
mizer dampers will close.  
P6 — WARM-UP SET POINT — This potentiometer is on  
the accessory board (provided standard from the factory)  
located in the unit main control box. This potentiometer  
establishes the set point temperature for the Morning  
Warm-Up function. When the temperature is reached, Morn-  
ing Warm-Up is terminated and VAV operation begins. DIP  
switch 4 must be in the ON position if morning warm-up  
heat is to be used.  
T2 — RETURN-AIR TEMPERATURE THERMISTOR —  
This thermistor is located in the mixed-air portion of the unit  
cabinet. The thermistor’s primary function is to provide morn-  
ing warm-up information. This sensor will also provide dif-  
ferential information for the processor during cooling opera-  
tion (such as the rate of change for a capacity step).  
P7 — SASP (SUPPLY AIR SET POINT) RESET TEM-  
PERATURE — This 10 Kohm potentiometer is used only if  
the accessory, field-installed temperature reset package is in-  
stalled. This potentiometer determines the temperature at which  
reset will begin. It is located on the accessory temperature  
reset board. DIP switch 2 must be in the ON position to en-  
able SASP reset.  
T3 — SATURATED CONDENSING TEMPERATURE, CIR-  
CUIT 1 — This thermistor is located on the condenser coil  
return bend. See Fig. 13 and 14. It controls the staging of the  
unit condenser fans based on the condensing temperature of  
the refrigerant at the designated position on the condenser  
coil.  
T4 — SATURATED CONDENSING TEMPERATURE, CIR-  
CUIT 2 — This thermistor is located on the condenser coil  
return bend. See Fig. 13 and 14. It controls the staging of the  
unit condenser fans based on the condensing temperature of  
the refrigerant at the designated position on the condenser  
coil.  
PROCESSOR BOARD OUTPUTS — The processor board  
also controls outputs through the relay board. The relay board  
plugs into the processor board using a ribbon cable.  
In addition, the processor board controls the display board.  
The display board is connected to the processor board by a  
ribbon cable, and has an LED (light-emitting diode) display  
showing the status of the unit and diagnostic information.  
T10 — RESET TEMPERATURE — This thermistor is used  
only if the accessory temperature reset package is used. It  
provides occupied space temperature information to the pro-  
cessor, which determines whether or not reset is required.  
The thermistor is remotely mounted outside the unit in the  
conditioned space.  
CONFIGURATION HEADER AND DIP SWITCHASSEM-  
BLY — The processor board is programmed to control a va-  
riety of air conditioning units. To tailor the processor to the  
particular unit being controlled, 2 devices are used. One is  
the configuration header, and the other is the DIP switch  
assembly.  
5
Table 3 — Output Pin and Terminal Assignments  
OUTPUT PIN-  
TERMINAL  
NAME  
RATING  
DEVICE  
CR1  
Stage 1  
J6-1  
J6-2  
J6-3  
J6-4  
J6-5  
J6-6  
Compressor Relay (K1)*  
Stage 2  
U2**  
Compressor Relay (K2)*  
Stage 3  
U1  
Compressor Relay (K3)*  
Stage 4  
Not Used  
CR2  
24 vac  
Compressor Relay (K4)†  
Stage 5  
Compressor Relay (K5)†  
Stage 6  
Not Used  
Compressor Relay (K6)†  
J6-7  
J6-8  
J5-1  
J5-2  
Economizer Open Relay (K7)  
Economizer Close Relay (K8)  
Supply Fan Relay (K9)  
EOR  
ECR  
IFC  
Morning Warm-Up Relay (K10)  
HIR  
Stage 1 Condenser  
Fan Relay (K11)  
J5-3  
OFC2/OFC3 ††  
115 vac  
Stage 2 Condenser  
Fan Relay (K12)  
J5-4  
OFC4  
J5-5  
External Alarm Relay (K13)  
ALM  
LEGEND  
*Circuit 1.  
†Circuit 2.  
ALM  
CR  
Alarm  
Control Relay  
Economizer Close Relay  
Economizer Open Relay  
Heat Interlock Relay  
**U2 is not used on 044 units.  
††OFC2 on 034-048 units; OFC3 on 054-104 units.  
Used on 054-104 units only.  
ECR  
EOR  
HIR  
IFC  
OFC  
U
Indoor (Evaporator) Fan Contactor  
Outdoor (Condenser) Fan Contactor  
Unloader  
LEGEND  
CR  
J
K
Control Relay  
Terminal Pin Connectors  
Relay  
Fig. 5 — Relay Board  
6
P3 — RESET LIMIT — The processor board is programmed  
for occupied space temperature reset. In order for reset to  
work, the accessory temperature reset board must be used.  
Potentiometer P3 is the maximum set point temperature to  
which the supply air can be reset.  
P1 SUPPLY AIR  
SET POINT  
POTENTIOMETER  
TWO-DIGIT  
DISPLAY  
DISPLAY  
BUTTON  
P5 — ECONOMIZER MINIMUM POSITION — This po-  
tentiometer controls the set point for the minimum position  
of the economizer.  
P6 — MORNING WARM-UP TEMPERATURE — This po-  
tentiometer controls the morning warm-up temperature set  
point.  
Single-Step Demand Limit — The single step de-  
mand limit provides a means to limit the capacity of the VAV  
unit using an external switch. Single step demand limit will  
limit the compressor displacement based on the ratio of the  
wiper arm to the full scale resistance. The exact percentage  
of capacity reduction differs depending on the number of ca-  
pacity steps.  
A 3-wire, 5 to 20 Kohm, field-supplied potentiometer (P4)  
is required for this option. The potentiometer should be wired  
to the processor J3 connections. In order to control the de-  
mand limit, the wiper arm of the potentiometer should be  
switched open and closed based on the demand limit  
requirement. The control switch is also field-supplied and  
installed.  
If the wiper arm wire is open, all capacity stages can be  
used. When the wiper arm wire is closed, the capacity is  
reduced by the amount set on potentiometer P4.  
Fig. 6 — Display/Set Point Board  
Compressor Operation  
CONTROL RELAY (CR) — This relay provides informa-  
tion to the processor about compressor operation (one con-  
trol relay per compressor). The relay controls and protects  
the compressor and also controls the crankcase heater.  
Demand Limit Control Module (DLCM) — The  
DLCM provides a 2-step demand limit control using an ex-  
ternal switch. The first step is between 50% and 100% of the  
maximum compressor displacement. See Fig. 16. The sec-  
ond step is between 0% and 49% of the maximum compres-  
sor displacement. The exact percentage differs depending on  
the number of capacity steps.  
Two adjustable potentiometers are used to set the 2 de-  
mand limit points. Potentiometer P1 is used to set a demand  
limit between 50% and 100% of the unit capacity. Potenti-  
ometer P2 is used to set a demand limit between 0% and  
49% of unit capacity.  
If no power is supplied to the demand limit control mod-  
ule, all capacity stages can be used. When power is supplied  
to terminal IN1 only, the first step of the demand limit con-  
trol is energized and the capacity is reduced by the amount  
set on potentiometer P1. When power is supplied to terminal  
IN2 only, or to both IN1 and IN2, the capacity is reduced by  
the amount set on potentiometer P2.  
A control signal to check the safety statuses and to start  
the compressor is sent from the relay board. This signal trav-  
els through all of the safeties: the high-pressure switch, and  
the internal protector (where used) and on to the control re-  
lay coil. Once the control relay coil has been energized, the  
control relay completes a feedback circuit for the processor,  
informs the processor of the status of the compressor safe-  
ties, energizes the compressor contactor coil, and deener-  
gizes the crankcase heaters. A fault will be detected by the  
processor if the control relay opens during operation or start-  
up. The processor will lock the compressor or the circuit off  
by deenergizing the appropriate relay(s) on the relay board  
and energizing an alarm signal.  
Accessory Board — The accessory board is standard  
(factory supplied) in the VAV rooftop units. See Fig. 15. This  
board is located in the control box of each unit. Each board  
has a prewired connector supplied with it to connect directly  
to the processor board. It has 3 potentiometers: P3, P5, and  
P6.  
7
GAS SECTION  
(48FK,JK ONLY)  
HORIZONTAL SUPPLY SECTION  
(50FY,JY ONLY) AND EXTENDED  
PLENUM SECTION (50FKX,FKY,JKX,JKY)  
Fig. 7 — Thermistor T1 Location, 48FK,JK, 50FY,JY and 50FKX,FKY,JKX,JKY 034-048 Units  
FAN DISCHARGE/ELECTRIC HEAT SECTION  
Fig. 8 — Thermistor T1 Location, 50FK,JK034-048 Units  
8
GAS SECTION  
(48FK,JK)  
HORIZONTAL DISCHARGE SECTION (50FY,JY)  
AND EXTENDED  
PLENUM SECTION (50FKX,FKY,JKX,JKY)  
Fig. 9 — Thermistor T1 Location, 48FK,JK, 50JY and  
50JKX,JKY 054-074 Units and 50FKX,FKY and 50FY054-104 Units  
FAN DISCHARGE/ELECTRIC HEAT SECTION  
Fig. 10 — Thermistor T1 Location, 50FK,JK054-074 Units  
9
STANDARD  
FILTERS  
BAG  
FILTERS  
Fig. 11 — Thermistor T2 Location, Size 034-048 Units  
Fig. 13 — Thermistor T3 and T4 Locations,  
Size 034-048 Units  
ENTHALPY CONTROL — Outside air enthalpy control is  
standard with the factory-installed economizer option. En-  
thalpy is sensed by a controller located behind the end out-  
side air hood. The control can be accessed by removing the  
upper hood filter. See Fig. 17.  
DIFFERENTIAL ENTHALPY Added efficiencies in econo-  
mizer control can be gained by installing a differential en-  
thalpy sensor in the return air duct. When differential enthalpy  
control is installed, the economizer control will use the air  
stream with lower enthalpy (outside air or return air) to pro-  
vide for lower compressor operating costs during integrated  
economizer cycle operation. The differential enthalpy sen-  
sor is installed in the return-air duct.  
STANDARD FILTERS  
BAG FILTERS  
(054-074 Only)  
Fig. 12 — Thermistor T2 Location, Size 054-104 Units  
Economizer — Economizer control is used to control  
the outside and return air dampers of the unit, to satisfy space  
cooling demand using all outside air (when permitted), and  
to satisfy cooling in conjunction with compressor operation  
(when conditions permit). During Occupied periods without  
cooling demand, the outside-air dampers will be at the user-  
configured Minimum Damper Position (at P5 on accessory  
board). During Unoccupied periods, the outside-air dampers  
will be closed.  
The economizer is available as a factory-installed option.  
The user can install an accessory differential enthalpy sensor  
to enhance economizer control. Refer to the installation sec-  
tion for field wiring of the sensor.  
10  
054 UNITS  
064, 074, 078 UNITS  
088, 104 UNITS  
Fig. 14 — Thermistor T3 and T4 Locations, Size 054-104 Units  
11  
Variable Frequency Drive (VFD) — The optional  
VFD is used to modulate supply fan airflow to maintain duct  
static pressure on VAV applications. The VFD is located in  
the supply fan section (see Fig. 18 and 19), and can be ac-  
cessed by opening the fan section access door.  
The unit is supplied with a pressure transducer capable of  
measuring from 0.0 to 5.0 in. wg. The pressure transducer  
will send a 4 to 20 mA signal to the VFD to modulate the  
speed of the indoor fan motor to precisely control the fan to  
the desired static pressure set point. The VFD is factory set  
at 2.5 in. wg duct static pressure. Refer to the Operating Se-  
quence section for more information on the VFD.  
The VFD has been programmed and wired at the factory  
for this application. No further adjustments (except for Duct  
Static Pressure Set Point) should be necessary at start-up.  
Factory jumper wire configurations are shown in the Supply  
Fan Control with VFD Option section on page 28.  
A separate service manual for the factory-installed VFD  
is supplied with each unit. Refer to the VFD manual for more  
information on the VFD controls.  
Temperature Reset — Accessory temperature reset al-  
lows the unit to automatically adjust (‘‘reset’’) the supply-  
air temperature set point to a higher value once most of the  
space cooling load has been met. When the space conditions  
are satisfied, the VAV terminals will close to the minimum  
position. All VAV units will sense the decrease in actual supply-  
air temperature and the unit controls respond by reducing  
LEGEND  
ECON  
MIN  
P
Economizer  
Minimum  
Potentiometer  
Variable-Air Volume  
VAV  
Fig. 15 — Accessory Relay Board  
(Standard; Factory Supplied)  
LEGEND  
IC  
Integrated Circuit  
Input  
Potentiometer  
Return  
IN  
P
RTN  
Fig. 16 — Two-Step Demand Limit Module  
Fig. 18 — Variable Frequency Drive,  
Sizes 034-048 and 078-104  
Fig. 17 — Enthalpy Sensor Location  
Fig. 19 — Variable Frequency Drive, Sizes 054-074  
12  
capacity stages to maintain user-established supply-air set  
point temperature. When VAV units are also equipped with  
optional supply duct pressure controls (either inlet guide vanes  
[IGV] or variable frequency drive package), the unit also senses  
an increase in duct static pressure and responds by closing  
IGV dampers or slowing fan wheel speed to maintain user-  
configured set points for supply duct pressure. Allowing the  
supply-air temperature to be reset to a higher value main-  
tains air circulation in the space without costly overcooling.  
There are no required 115-volt field wiring connections,  
therefore no provisions have been made in the unit for run-  
ning 115-volt wiring. If any of the field-installed options re-  
quiring 115-volt connections are desired, the unit must be  
modified in the field for 115-volt wiring.  
NIGHT SETBACK THERMOSTAT — Wire field-supplied  
thermostat (suitable for 24-v circuit) between terminals 1 and  
2 on terminal block 3 (sizes 034-048) or terminal block 4  
(sizes 054-104). This thermostat is used to bypass the time-  
clock occupied/unoccupied switch and is used to operate unit  
during unoccupied times at more economical temperatures.  
(See Fig. 23.)  
The accessory package is required for temperature reset.  
The accessory includes:  
• thermistor T10, to monitor space temperature  
SPACE TEMPERATURE RESET ACCESSORY  
(50DJ900021) — Consists of a thermistor (T10) and a reset  
board with a potentiometer (P7) that is used to set space tem-  
perature at which reset starts. Mount reset board in unit  
control box or other convenient place. Wire thermistor in se-  
ries with P7 and connect to terminals 12 and 15 on terminal  
block 3 (sizes 034-048) or terminal block 4 (sizes 054-104)  
in unit control box. If there is a long run to conditioned space,  
it is necessary to splice additional wire to thermistor. The  
reset board has 2 pressure connectors for field wiring. (See  
Fig. 25).  
• reset temperature potentiometer P7, to establish start tem-  
perature for reset operation  
• reset limit potentiometer P3, to establish maximum level  
of modified supply-air temperature  
More than one space sensor may be used if an average  
space temperature is desired for initiating temperature reset.  
Refer to installation section for sensor part number and wir-  
ing schematic.  
Temperature reset will start when space temperature (at  
T10) drops to the set point at P7. When Temperature Reset  
is active, the LED (light-emitting diode) display will show  
code  
. Automatic adjustment of supply-air temperature  
21  
Space Temperature Reset  
set point will end when modified SASP equals reset limit set  
point at P3. (See formula for automatic modification of SASP  
in Controls Installation, Space Temperature Reset section on  
this page.)  
INSTALLATION — Install the accessory temperature reset  
package in accordance with instructions provided with the  
accessory kit.  
Mount the reset board in the unit control box (or other  
suitable location) per instructions.  
CONTROLS INSTALLATION  
Locate the thermistor T10 in a suitable location in the oc-  
cupied space per instructions.  
Wire T10 to the reset board and to the unit control ter-  
minal block per Fig. 25. Wire the other terminal on the reset  
board to the unit control terminal block per Fig. 25.  
If multiple sensors are required to average the space tem-  
perature, see Fig. 26. Use only Carrier Part Number  
HH79NZ014 sensor, in arrangements of 4 or 9 sensors, with  
total wiring not to exceed 1000 ft.  
To enable reset function, change DIP (dual in-line pack-  
age) switch 2 to position ON. (Disconnect control power be-  
fore changing DIP switch positions; reconnect power after  
all changes have been made.)  
The VAV units may be used in applications with addi-  
tional control features, options, or accessories. Refer to the  
appropriate accessory installation instructions for more in-  
formation on installing that accessory. Unit control box com-  
ponent arrangement is shown in Fig. 20-22. Control options  
and accessories available for VAV units are:  
• smoke control modes  
• differential enthalpy sensor  
• electric heaters (sizes 034-074 only)  
• modulating power exhaust  
• MotormasterI control  
• space temperature reset  
• night setback thermostat (field-supplied)  
• single step demand limit  
CONFIGURATION — Set points for reset operation are es-  
tablished at potentiometers P7 and P3 (on the reset board).  
• two-step demand limit  
Potentiometer P7 — Reset temperature set point (tempera-  
ture at which reset function will start). Maximum of 80 F,  
minimum 0° F. Set below normal room cooling set point level  
to sense overcooling in the occupied space.  
NOTE: It is difficult to accurately set the P7 potentiometer  
to the desired set point. Use the procedure below.  
Proper setting of the P7 potentiometer may be made on a  
resistance basis. The microprocessor initiates reset when it  
detects a resistance of the thermistor plus the potentiometer  
of 13,084 ohm. The potentiometer set point may be calcu-  
lated using the following formula:  
• inlet guide vanes  
• variable frequency drive  
• variable frequency drive remote display kit  
Control Wiring — A switch or timeclock (field sup-  
plied) must be wired in to control when unit will go into and  
out of Occupied mode. Connect switch or timeclock be-  
tween terminals 1 and 2 on terminal block 3 (sizes 034-048)  
or terminal block 4 (sizes 054-104) in unit control box. See  
Fig. 23. The circuit potential is 24 v.  
Variable air volume units equipped with warm-up heat re-  
quire that room terminals be controlled to go fully open when  
unit goes into the Heating mode. Heating interlock relay (HIR)  
is provided for this function. The relay is located in the unit  
control box. When unit goes into Heating mode, interlock  
relay is energized providing switch closure or opening (de-  
pending on how field power source is set up) to open the  
room terminals. Field connections for interlock relays are  
terminals 3 and 4 (for normally open contacts) and terminals  
3 and 7 (for normally closed contacts) on terminal block 3  
(sizes 034-048) or terminals block 4 (sizes 054-104). See  
Fig. 24. Note that a field-supplied power source is required.  
P7R = 13,084 – T10R  
Where:  
P7R = the desired set point of the P7 potentiometer in ohms  
T10R = the resistance of the T10 thermistor for the desired  
set point  
13  
14  
15  
16  
034-048: TB3  
054-104: TB4  
034-048: TB3  
054-104: TB4  
Control will automatically adjust leaving air temperature by  
the following formula:  
MSP = SP + [(P3 - SP) / 3] x (P7 − T10)  
where:  
1
2
MSP = Modified Leaving-Air Set Point  
SP = Supply-Air Set Point  
OCCUPIED/UNOCCUPIED  
SWITCH  
P3 = Maximum Supply-Air Temperature (reset limit)  
P7 = Reset Initiation Temperature (reset set point)  
T10 = Actual Space Temperature  
NIGHT SETBACK THERMOSTAT  
3
= Ratio for reset (F) (fixed parameter)  
Table 4 — Thermistor Resistance and  
Voltage Drop Characteristics  
NOTES:  
1. Occ/Unocc switch closes when occupied.  
TEMP  
(F)  
RESISTANCE  
(Ohms)  
VOLTAGE  
DROP (v)  
2. Night setback thermostat closes when in night setback heating.  
31.0  
32.0  
33.0  
34.0  
35.0  
36.0  
37.0  
38.0  
39.0  
40.0  
41.0  
42.0  
43.0  
44.0  
45.0  
46.0  
47.0  
48.0  
49.0  
50.0  
51.0  
52.0  
53.0  
54.0  
55.0  
56.0  
57.0  
58.0  
59.0  
60.0  
61.0  
62.0  
63.0  
64.0  
65.0  
66.0  
67.0  
68.0  
69.0  
70.0  
71.0  
72.0  
73.0  
74.0  
75.0  
76.0  
77.0  
78.0  
79.0  
80.0  
16813.8  
16345.7  
15892.2  
15452.7  
15026.7  
14613.9  
14213.6  
13825.5  
13449.2  
13084.2  
12730.1  
12386.6  
12053.3  
11730.0  
11416.1  
11111.5  
10815.8  
10528.7  
10250.0  
9979.3  
9716.5  
9461.3  
9213.4  
8972.6  
8738.6  
8511.4  
8290.6  
8076.1  
7867.7  
7665.1  
7468.3  
7277.1  
7091.2  
6910.6  
6735.1  
6564.4  
6398.6  
6237.5  
6080.8  
5928.6  
5780.6  
5636.8  
5497.0  
5361.2  
5229.1  
5100.8  
4976.0  
4854.8  
4736.9  
4622.4  
3.582  
3.553  
3.523  
3.494  
3.464  
3.434  
3.404  
3.373  
3.343  
3.312  
3.281  
3.250  
3.219  
3.187  
3.156  
3.124  
3.093  
3.061  
3.029  
2.997  
2.965  
2.933  
2.901  
2.869  
2.837  
2.805  
2.772  
2.740  
2.708  
2.676  
2.644  
2.612  
2.581  
2.549  
2.517  
2.486  
2.454  
2.423  
2.391  
2.360  
2.329  
2.299  
2.268  
2.237  
2.207  
2.177  
2.147  
2.117  
2.088  
2.058  
Fig. 23 — Occupied/Unoccupied Switch with  
Night Setback Thermostat  
034-048: TB3  
054-104: TB4  
FIELD  
SUPPLIED  
POWER  
SOURCE  
3
V
4
6
5
N.O.  
N.C.  
4
7
SIGNAL  
TO ROOM  
TERMINALS  
Fig. 24 — Heat Interlock Relay  
034-048: TB3  
054-104: TB4  
T10  
12  
RESET  
BOARD  
P7  
15  
Fig. 25 — Accessory Reset Board  
EXAMPLE:  
T10 desired set point is 70 F.  
T10R from Table 4 for 70 F is 5929 ohms.  
P7R = 13,084 – 5929  
P7R = 7155 ohms  
Using an ohmmeter, set the P7 potentiometer to  
7155 ohms to achieve a reset initiation set point of 70 F.  
Potentiometer P3 — Reset limit set point (maximum tem-  
perature value for modified supply air set point). Maximum  
of 70 F, minimum 40 F. Set between leaving air set point  
(P1) and 70 F (maximum range permitted by control).  
OPERATING SEQUENCE — If space temperature is above  
reset set point (T10 > P7), no reset will occur.  
If space temperature is equal to or less that reset set point  
20  
(T10 р P7), the LED will display  
and reset will begin.  
17  
RED  
BLK  
RED  
BLK  
SIZES 034-048  
TB3  
RED  
RED  
BLK  
RED  
BLK  
12  
15  
BLK  
TO ACCESSORY SPACE  
TEMPERATURE RESET  
CONTROL BOARD  
SIZES 054-104  
TB4  
12  
15  
SENSOR 1  
SENSOR 2  
SENSOR 3  
SENSOR 4  
SPACE TEMPERATURE RESET — 4 SENSOR AVERAGING APPLICATION  
SIZES 034-048  
TB3  
12  
RED  
RED  
BLK  
RED  
BLK  
BLK  
15  
TO ACCESSORY SPACE  
TEMPERATURE RESET  
CONTROL BOARD  
SENSOR 1  
SENSOR 3  
SENSOR 2  
SIZES 054-104  
TB4  
12  
RED  
BLK  
RED  
BLK  
15  
SENSOR 4  
SENSOR 5  
SENSOR 6  
NOTE: Sensor part number is HH79NZ014.  
RED  
BLK  
RED  
BLK  
SENSOR 7  
SENSOR 8  
SENSOR 9  
SPACE TEMPERATURE RESET — 9 SENSOR AVERAGING APPLICATION  
Fig. 26 — Space Temperature Sensor Averaging  
Control Module kit plus installation of 2 field-supplied con-  
trol switches (SPST-NO each). This accessory control pro-  
vides for a first step reduction of 50% to 100% of the maxi-  
mum compressor staging; the second step provides for reduction  
between 0% and 49%. The exact percentage of capacity re-  
duction differs depending on the number of capacity steps.  
Demand Limit — The demand limit function provides  
a means to limit the cooling capacity of the VAV unit using  
an external discrete switch function. When enabled by the  
closure of the external switch, the control will limit the avail-  
able compressor staging capacity according to user set points  
established at demand limit potentiometer(s).  
When demand limit is active, the LED display will show  
The unit controls support two types of demand limit: single-  
step and 2-step control.  
22  
code  
.
SINGLE-STEP DEMAND LIMIT — This function will limit  
the total compressor staging based on the ratio of the set point  
potentiometer’s wiper arm position to the full scale resis-  
tance of the potentiometer. The exact percentage of capacity  
reduction differs depending on the number of capacity steps.  
A field-supplied potentiometer and control switch are re-  
quired for this function. See installation section for speci-  
fication on potentiometer and field wiring.  
INSTALLATION  
Single-Step Demand Limit — A 3-wire 5 to 20 K-ohm po-  
tentiometer must be field-supplied and installed. A single-  
pole normally open switch is also required (field-supplied  
and -installed). Locate the potentiometer (designated P4) and  
the switch in a suitable location (external from the unit or in  
the unit control box).  
TWO-STEP DEMAND LIMIT — Two-step demand limit is  
provided with the installation of the accessory Demand Limit  
18  
Connect the potentiometer end terminals to terminals 8  
and 9 on control terminal block TB3 (sizes 034-048) or TB4  
(sizes 054-104) (see Fig 27). Connect the switch terminals  
to the potentiometer wiper arm terminal and to terminal 10  
on TB3 or TB4.  
034-048: TB3  
054-104: TB4  
8
To enable demand limit function, change DIP switch 5 to  
position ON. (Disconnect control power before changing DIP  
switch positions. Reconnect power after all changes have been  
made.)  
5-20K  
POTENTIOMETER  
(P4)  
9
Set the potentiometer P4 to desired capacity reduction value.  
Two-Step Demand Limit — Install the demand limit con-  
trol module (DLCM) according to the installation instruc-  
tions provided with the accessory. Disconnect existing leads  
at connector J3 on the processor board (see instructions) and  
connect the plug from the DLCM harness to connector J3.  
10  
SWITCH  
Fig. 27 — Single-Step Demand Limit  
Connect the field input control power wires (from the ex-  
ternal control relays) at the terminal strips marked IN1, RTN1,  
IN2 and RTN2 (see Fig. 28 and 29).  
To enable demand limit function, change DIP switch 5 to  
position ON. (Disconnect control power before hanging DIP  
switch positions. Reconnect power after all changes have been  
made.)  
Set the potentiometers DLCM-P1 and DLCM-P2 to de-  
sired capacity reduction values.  
Check the operation of demand limit function by using  
the Quick Test procedures.  
CONFIGURATION  
Single-Step Demand Limit — Field-installed potentiom-  
eter P4 establishes capacity reduction value for demand limit  
operation. Set this potentiometer between 0% and 100%. The  
exact percentage of capacity reduction differs depending on  
the number of capacity steps.  
Fig. 28 — Two-Step Demand Limit Module  
Two-Step Demand Limit — Potentiometer P1 and P2 (lo-  
cated on the accessory demand limit control module) estab-  
lish the capacity reduction values for each step of demand  
limit. Set potentiometer DLCM-P1 between 50% and 100%.  
Set potentiometer DLCM-P2 between 0% and 49%. The ex-  
act percentage of capacity reduction differs depending on the  
number of capacity steps.  
NOTES:  
OPERATING SEQUENCE  
1. Demand limit switches are field supplied and wired.  
2. Demand limit control module terminal blocks will accept up to  
12-gage wire.  
Single-Step Demand Limit — If the field control switch to  
the wiper arm terminal is open, all capacity stages will be  
available (no demand limit in effect). When the field control  
switch is closed, the compressor cooling capacity is reduced  
by the amount set on potentiometer P4.  
is field wiring.  
3.  
Fig. 29 — 115-Volt Field Wiring to Accessory  
2-Step Demand Limit Control Module  
When demand limit is in effect, the LED display will show  
code 22 . If a potentiometer setting or input is out of range,  
the control will terminate the demand limit function and show  
Control From Remote Building Management Sys-  
tem (BMS) — The unit control system is not a commu-  
nicating control system, and it cannot be accessed directly  
by a DDC (Direct Digital Control) control system (or by a  
BACnet communication system). However, it is possible to  
control some functions of these units via 4 to 20 mA or 2 to  
10 vdc signals and discrete inputs (relay contact closures).  
Functions that can be managed from or accessed from an  
external control system include:  
• Occupied/Unoccupied Status  
• Night Setback Control  
• Unit Supply Air Set Point Adjustment  
• Demand Limit (1-stage or 2-stage)  
• Supply Duct Pressure Set Point Adjustment  
• External Alarm Signal  
Remote control of the economizer cycle on these units is  
not recommended. Refer to the Operating Sequence section  
on page 35 for a discussion on the economizer cycle  
operation.  
code  
at the display LED.  
84  
Two-Step Demand Limit — If the field control switches are  
both open (no power supplied to the Demand Limit Control  
Module), all capacity stages will be available (no demand  
limit in effect). When control power is supplied to terminal  
IN1 only (field switch SW1 closes), the first step of the de-  
mand limit is energized and the compressor cooling capacity  
is reduced by the amount set on potentiometer DLCM-P1.  
When control power is supplied to terminal IN2 (field switch  
SW2 closes), the second step of the demand limit is ener-  
gized and compressor cooling capacity is reduced by the amount  
set on potentiometer DLCM-P2.  
When demand limit is in effect, the LED display will show  
code 22 . If a potentiometer setting or input is out of range,  
the control will terminate the demand limit function and show  
code  
at the display LED.  
84  
19  
OCCUPIED/UNOCCUPIED — The unit control system will  
initiate normal occupied mode functions (including Morn-  
ing Warm-up, Economizer Minimum Position, and Cooling  
Cycle) whenever a contact closure is made that emulates the  
normal timeclock contacts. See Fig. 23. (‘‘Occupied/Unoccupied  
Switch’’). The contact closure from the BMS must be an iso-  
lated contact set, normally open, and suitable for 24-volts  
AC pilot duty.  
Configuration — Configure as follows:  
1. Set DIP switch no. 2 to ON.  
2. Adjust manual potentiometer to 12.6 to 12.8 k-ohm.  
3. Configure transducer for job site input signal from BMS.  
4. Adjust Potentiometer (P3) on the rooftop to MAXIMUM  
SASP value (typically 65 to 70 F). The maximum P3 SASP  
control limit is 70 F.  
NIGHT SETBACK CONTROL — Night setback control is  
used to control the space to a set point level that is typically  
lower than during normal occupied periods (Heating Only  
mode). Some applications also require a limitation on the  
maximum space temperature during unoccupied periods (Cool-  
ing mode). Both modes are possible by closing the same con-  
tacts used in the Occupied/Unoccupied control, or by installing  
a dedicated contact set in parallel with the Occupied/  
Unoccupied control contacts, and using the BMS space tem-  
perature sensing system and its logic to determine when to  
initiate unit operation.  
Operation —Unit will initiate SASP Reset (adjust config-  
ured SASP upward) when the sum of the resistance (fixed  
resistance + potentiometer + transducer) exceeds 13.1 k-ohm.  
Once reset is initiated, full range of reset (P3 setting minus  
configured SASP) will be reached with 500-ohm increase in  
transducer resistance (TR).  
During Reset mode operation, Code 21 will appear on unit  
display board.  
Formula:  
MSP = SASP +  
Once the unit operation has been initiated by the BMS  
contact closure, the unit operates in its normal occupied mode  
manner, initiating morning warm-up if needed (as sensed by  
return air temperature to the unit) or cooling (controlling to  
current SASP value). The Night Setback Control contacts  
will interrupt normal unit operation when the BMS senses  
that space temperatures have returned to unoccupied set point  
levels, and the unit will shutdown normally.  
(P3 − SASP)  
(3)  
(0.6 F)  
x
x (TR [email protected])  
[
]
(100 ohm)  
MSP: Modified SASP (SASP plus Reset)  
TR: Resistance at transducer  
[email protected]: TR required to reach 13.1 k-ohm start level  
DEMAND LIMIT (1-STAGE OR 2-STAGE) — Both of the  
Demand Limit functions on the units rely on external switches  
to initiate the reset functions. Contact closures by the BMS  
can be used in place of these switches. Contacts must be  
isolated and suitable for 115-vac pilot duty operation.  
For Single-Step Demand Limit, emulate function of switch  
SW with contact closure controlled by the BMS. Set poten-  
tiometer P4 manually at the unit control box. Alternatively,  
potentiometer P4 might also be emulated by a variable re-  
sistance transducer, with the BMS now able to adjust the  
amount of demand limit.  
For 2-Step Demand Limit, install the accessory Demand  
Limit Control Module (DLCM) according the instructions  
on page 18. Replace switch functions Switch 1 and Switch  
2 with contact closures controlled by the BMS (see Fig. 29).  
Follow unit control configuration instructions in the De-  
mand Limit section on page 18.  
The contact closure from the BMS must be an isolated  
contact set, normally open, suitable for 24-volts AC pilot duty.  
NOTE: If the rooftop unit is equipped with a VFD and night  
setback cooling operation is intended, the fan system must  
be controlled to permit FULL SUPPLY FAN AIR DELIV-  
ERY during unoccupied cooling operation. This is most con-  
veniently attained by replicating the HIR relay function of  
the rooftop unit. An HIR control sequence will force all room  
terminals to their minimum heating CFM position, thus as-  
suring adequate airflow through the rooftop unit during night  
setback cooling operation. During night setback cooling op-  
eration, the return-air temperature (RAT) will be well above  
normal levels. The higher RAT means that the air tempera-  
ture leaving the evaporator coil will also be well above nor-  
mal levels. This situation is interpreted by the unit control  
system as a demand for additional cooling stages. The unit  
control responds to this demand by bringing on more stages,  
until typically all stages are active. If the VFD is not work-  
ing in-step with the refrigeration system demand, it is pos-  
sible to produce low suction pressures and local frosting  
on the evaporator coil during the night setback cooling  
operation.  
SUPPLY DUCT PRESSURE SET POINT ADJUSTMENT  
— Supply duct pressure set point adjustment from a remote  
BMS is possible when the unit has been equipped with a  
factory-option VFD (variable frequency drive). There are two  
methods available:  
• Direct 4 to 20 mA signal  
• DDC direct to the VFD  
UNIT SUPPLY AIR SET POINT ADJUSTMENT — The  
minimum Supply Air Set Point (SASP) temperature is es-  
tablished by the setting at Potentiometer P1 on the unit dis-  
play board (see Fig. 6). The control point can also be adjusted  
upward by emulating the function of the accessory Space  
Temperature Reset package. The BMS can be used to cause  
this reset by adjusting the resistance value in a variable re-  
sistance transducer with a 4 to 20 mA or 2 to 10 vdc signal  
generated by the BMS.  
Direct 4 to 20 mA Signal — During normal unit operation,  
the factory-installed VFD receives a 4 to 20 mA signal from  
the Duct Pressure (DP) transducer which indicates current  
supply duct pressure. The VFD then determines the appro-  
priate fan speed (using its internal PID logic feature) and  
adjusts its output to the supply fan motor to suit. It is pos-  
sible to emulate this 4 to 20 mA control signal by the BMS,  
which will transfer control of the VFD to the BMS.  
This emulation requires the following field-supplied parts:  
NOTE: When providing a direct 4 to 20 mA signal to the  
VFD from a BMS with DP logic, disable the PID (propor-  
tion integrated derivative calculation process) feature of the  
VFD.  
Variable resistance transducer (Kele RES-1 or equivalent,  
range 0 to 1000 ohms)  
• Series resistance with potentiometer, suitable for manual  
adjustment to 12.5 to 13.0 k-ohms total resistance  
DDC Direct to the VFD — Several accessory interface boards  
are available for the VFDs that permit direct communication  
between the VFD and several BMS communication sys-  
tems. Contact your Carrier representative for information on  
selecting an appropriate accessory interface board and the  
name of the local service office (for sale and installation of  
the accessory boards).  
Field Connections (see Fig. 30) — Connect fixed resistance  
with manual potentiometer and variable resistance trans-  
ducer in series.  
Connect wiring to rooftop unit at:  
Size 034-044: TB3-12 and TB3-15  
Size 054-104: TB4-12 and TB4-15  
20  
034-048: TB3  
054-104: TB4  
EXTERNAL ALARM SIGNAL — The unit controls pro-  
vide an external alarm status signal via a 115-vac output sig-  
nal at the relay board J5, available at TB2-4 and TB2-5  
(common). This signal can be forwarded to the BMS by add-  
ing a signal relay at the alarm output, placing its coil across  
terminals TB2-4 and TB2-5 and using its contacts to control  
a discrete input to the BMS (see Fig. 31).  
TRANSDUCER  
BMS  
P
CONTROL  
R
12  
(4 TO 20 MA  
OR  
2 TO 10 VDC  
SIGNAL)  
15  
The alarm signal output is energized when any of the di-  
agnostic codes is tripped.  
REMOTE ECONOMIZER CONTROL — Economizer con-  
trol is tightly integrated into the unit’s capacity control al-  
gorithms and diagnostic routines. Consequently, control  
modifications that interfere with this standard operating se-  
quence are not recommended.  
Economizer position is determined by the unit processor  
board based on current outdoor air enthalpy status and cool-  
ing capacity demand. The economizer damper actuator is a  
floating point device with an internal brake and spring re-  
turn. Its position is determined by the sequencing of relays  
EOR (Economizer Open Relay) and ECR (Economizer Close  
Relay). The economizer’s current position is sensed by the  
processor board through position feedback potentiometer P2.  
LEGEND  
P
R
Manual Potentiometer  
Fixed Resistor  
Field Wiring  
Fig. 30 — Remote SASP Wiring  
TB2  
TB2  
4
5
LIGHT  
Whenever the economizer position potentiometer signal  
is not consistent with the processor board’s commanded po-  
sition, a fault condition is determined by the processor board  
and an alarm signal is initiated. The processor board also  
attempts to return the economizer damper to its fully closed  
position during this fault condition by energizing the ECR  
relay.  
R
RELAY  
Any attempt to effect an external control of the econo-  
mizer actuator will lead to an alarm condition and an auto-  
matic response by the unit control to attempt to close the  
dampers.  
SIGNAL TO BMS  
Smoke Control Modes — It is common practice to  
use rooftop units for aid in building smoke control in the  
event of a building fire. The available functions include: Fire  
Shutdown, Pressurization, Evacuation, and Smoke Purge. These  
functions are enhanced when multiple rooftop units are used  
to zone a building.  
LEGEND  
R
Resistor (Factory Installed)  
Factory Wiring  
Field Wiring  
Fig. 31 — External Alarm Indication  
Implementation of the various Smoke Control modes on  
these units requires the installer to modify the unit wiring to  
add contacts (via either manual switches or relays) that will  
selectively interrupt and override standard factory control se-  
quences. See Table 5.  
EVACUATION MODE — Evacuation mode removes smoke  
or undesirable air from interior spaces without reintroducing  
unsuitable air. Factory-installed, optional economizer with  
optional or accessory power exhaust are required for this func-  
tion. Evacuation is accomplished by:  
FIRE SHUTDOWN MODE — Fire Shutdown mode termi-  
nates all unit operation (cooling, heating, supply fan and power  
exhaust). This mode prevents recirculation of contaminated  
air back into the space or the admission into the space of  
unsuitable outside air.  
• turning supply fan off  
PRESSURIZATION MODE — Pressurization mode is in-  
tended to keep smoke out of a zone. Factory-installed op-  
tional economizer is required for this function. Pressuriza-  
tion is accomplished by:  
• opening the economizer (option required for this function)  
• running the exhaust fans (must be provided via option or  
accessory)  
• opening the exhaust dampers  
• opening the economizer (option)  
SMOKE PURGE MODE — Smoke Purge mode removes  
smoke from the interior spaces and replaces it with fresh out-  
side air. Factory-option economizer with optional or acces-  
sory power exhaust are required for this function. Smoke purge  
is accomplished by:  
• turning supply fan on  
• opening the economizer (option required for this function)  
• running the exhaust fans (must be provided via option or  
accessory)  
• opening the exhaust dampers  
• running the supply fan (optional inlet guide vanes open or  
optional VFD (variable frequency drive) at normal duct  
static pressure set point)  
• closing the power exhaust dampers (if installed as option  
or accessory)  
• shutting off the power exhaust fans (if installed as option  
or accessory)  
This allows the space to be overpressurized relative to ad-  
jacent zones and prevents or slows entry of smoke into this  
space from adjacent zones.  
21  
INSTALLATION — To enable one or more of the possible  
smoke control modes available with these units, determine  
the switches required for the desired mode(s) from Table 6,  
field-supply and install the appropriate switches and field wire  
per Fig. 32. Switch functions are shown in Table 7.  
Pressurization — At command from the field switches for  
Pressurization mode (see Table 5):  
1. Economizer dampers will open  
2. The HIR function will energize, opening room terminals  
to full-open (heating) positions.  
3. Supply fan will run. (If equipped with IGV: control vanes  
will open. If equipped with VFD: the VFD will control to  
duct static set point or best available with all terminals  
open.)  
4. Power exhaust dampers (if equipped) will close.  
5. Power exhaust fans (if equipped) will turn off.  
Table 5 — Smoke Control Modes  
MODE  
FUNCTION  
Fire  
Shutdown  
Pressur-  
ization  
Smoke  
Purge*  
Evacuation*  
Supply Fan  
IGV/VFD†  
Off  
On  
Off  
On  
Open/On  
Open  
Open/On  
Open  
Evacuation — At command from the field switches for Evacu-  
ation mode (see Table 5):  
1. Supply fan will turn off.  
2. Economizer dampers will open.  
3. Exhaust fans will run at maximum capacity.  
4. Exhaust dampers will open.  
Economizer  
Closed  
Open  
Return Air  
Damper  
Open  
Off  
Closed  
Off  
Closed  
On  
Closed  
On  
Exhaust  
Fans  
Exhaust  
Damper  
Closed  
Closed  
Open  
Open  
Smoke Purge — At command from the field switches for  
Smoke Purge mode (see Table 5):  
1. Economizer dampers will open.  
2. The HIR function will energize, opening room terminals  
to full-open (heating) positions.  
3. Supply fan will run. (If equipped with IGV: Control vanes  
will open. If equipped with VFD: the VFD will control to  
duct static set point or best available with all terminals  
open.)  
LEGEND  
IGV  
VAV  
VFD  
Inlet Guide Vane  
Variable Air Volume  
Variable Frequency Drive  
*Power exhaust option/accessory required for this mode.  
†Applicable to VAV units with appropriate options.  
CONFIGURATION — No set points required for Smoke Con-  
trol modes. Modes are activated by energizing all switches  
appropriate for each Smoke Control mode.  
4. Exhaust fans will run at maximum capacity.  
5. Exhaust dampers will open.  
OPERATING SEQUENCE  
Fire Shutdown — At command from the field switches (see  
Table 5), all unit operation (cooling, heating, supply fan and  
power exhaust) will terminate.  
Table 6 — Smoke Control Switches Required for Each Mode  
EVACUATION  
(Modulating Power  
Exhaust)  
FIRE  
SMOKE  
PURGE  
PRESSURIZATION  
SHUTDOWN  
SW-1  
SW-2  
SW-1  
SW-2  
SW-1  
SW-2  
SW-3  
SW-5  
SW-6  
SW-7  
SW-8  
SW-1  
SW-2  
SW-4  
SW-3  
SW-5  
SW-4  
SW-6  
SW-9A/B  
SW-9A/B  
NOTE: All switches are shown in ‘‘as installed’’ (power OFF or deenergized) position. In these positions, none of these  
modes will be activated; normal unit operation is permitted by the base unit controls. To initiate any mode, all switches listed  
under this mode in the table must be energized, causing the depicted contact position to change from depicted positions to  
energized positions. Switches may be manually or electrically operated.  
22  
Table 7 — Switch Functions  
SWITCH  
NUMBER  
CONFIGURATION  
VOLTAGE  
FUNCTION  
SW-1  
SW-2  
SW-3  
SW-4  
SW-5  
SW-6  
SW-7  
SW-8  
N.C.  
N.C.  
N.O.  
N.O.  
N.C.  
N.O.  
N.O.  
N.C.  
115  
115  
24  
Deenergize 115-v (OFC, Comp, IFC, Electric Heaters)  
Deenergize TRAN7 (Process Board)  
Energize EOR (Open Economizer Outside Air Dampers)  
Energize IFC and CR-3 (IGV/VFD)  
115  
115  
115  
24  
Isolate IFC and PEC for Separate Operation  
Energize PEC (Power Exhaust)  
Open PED at DPS  
24  
Block Auto-Close at DPS (Due to Low BP)  
A: N.O.  
B: N.C.  
SW-9A/B  
115 max  
Signal Room Terminals to Open (HIR1)  
LEGEND  
Building Pressure  
BP  
DPS  
EOR  
HIR  
Differential Pressure Switch  
Economizer Open Relay  
Heat Interlock Relay  
Indoor Fan Contactor  
Inlet Guide Vane  
Normally Closed  
Normally Open  
Power Exhaust Contactor  
Power Exhaust Damper  
Outdoor Fan Contactor  
Variable Frequency Drive  
IFC  
IGV  
N.C.  
N.O.  
PEC  
PED  
OFC  
VFD  
The inlet guide vanes are controlled by a differential pres-  
sure switch (DPS). On sizes 034-048, the DPS is located in  
the auxiliary control box at the economizer end of the unit  
(see Fig. 33). On sizes 054-104, the DPS is located in the  
supply fan section. See Fig. 34. Use a nominal 38-in. plastic  
tubing.  
Air Pressure Tubing — Before options such as inlet  
guide vanes (IGV), variable frequency drive (VFD), and/or  
modulating power exhaust can operate properly, the pneu-  
matic tubing for pressure sensing must be installed. Use fire-  
retardent plenum tubing (field-supplied). Tubing size depends  
on type of control device (see Table 8 below). Tubing must  
be run from the appropriate sensing location (in the duct or  
in the building space) to the control device location in the  
unit.  
VARIABLE FREQUENCY DRIVE — The tubing for the  
duct pressure (DP) control option should sample supply duct  
2
pressure about 3 of the way out from the unit in the main  
trunk duct, at a location where a constant duct pressure is  
desired.  
Table 8 — Tubing Size  
NOMINAL TUBE  
The duct pressure is sensed by a pressure transducer. The  
pressure transducer output is directed to the VFD. On 034-  
048 units the DP transducer is located in the auxiliary con-  
trol box. On 054-104 units, the DP transducer is located in  
OPTION  
UNITS  
ALL  
SIZE (in.)  
3
Inlet Guide Vanes (IGV)  
8
4
8
Variable Frequency  
Drive (VFD)  
1
3
ALL  
1
the supply fan section. See Fig. 34. Use a nominal 4-in.  
Modulating Power Exhaust FK,FKX,JK,JKX  
plastic tubing.  
INLET GUIDE VANES — The tubing for the duct pressure  
(DP) control option should sample supply duct pressure about  
2
3
of the way out from the unit in the main trunk duct, at a  
location where a constant duct pressure is desired.  
23  
054-104 UNITS  
034-048 UNITS  
TB2  
5
SW-1  
TB2  
6
TB2  
13  
SW-1  
TB2  
14  
REMOVE JUMPER  
REMOVE JUMPER  
TB2  
1
SW-2  
TB2  
2
TB2  
7
SW-2  
TB2  
8
REMOVE JUMPER  
REMOVE JUMPER  
SW-3  
SW-4  
TB3  
5
TB3  
1
SW-3  
SW-4  
TB4  
5
TB4  
1
TB2  
9
TB2  
5
TB2  
2
TB2  
13  
TB2  
8
SW-5  
TB2  
9
TB2  
1
SW-5  
TB2  
2
REMOVE JUMPER  
REMOVE JUMPER  
TB2  
8
TB2  
5
SW-6  
TB2  
1
TB2  
13  
SW-6  
SW-9A  
TB3  
4
TB3  
3
SW-9A  
TB4  
4
TB4  
3
HIR  
HIR  
TB4  
7
TB3  
3
SW-9B  
TB3  
7
TB4  
3
SW-9B  
4
4
5
5
REMOVED FROM TB3-7  
REMOVED FROM TB4-7  
ALL UNITS  
SW-7  
SW-8  
DPS  
NC  
WHT  
C
VIO  
NO  
REMOVED  
FROM C-DPS  
GRA  
LEGEND  
DPS  
HIR  
SW  
TB  
Differential Pressure Switch  
Heat Interlock Relay  
Switch  
Terminal Block  
Fig. 32 — Smoke Control Wiring  
24  
MODULATING POWER EXHAUST — The tubing for the  
building pressure control (achieved via the Modulating Power  
Exhaust option) should sample building pressure in the area  
near the entrance lobby (or other appropriate and sensitive  
location) so that location is controlled as closely to design  
pressures as possible.  
A differential pressure switch (DPS) is used to control the  
actuator on the modulating discharge damper in exhaust fan  
no. 1. The building pressure (BP) DPS is located in the aux-  
iliary control box of the unit. See Fig. 33 and 35. Use a nomi-  
3
nal ⁄8-in. plastic tubing.  
For instructions on adjusting BP control set points, refer  
to Start-Up, Modulating Power Exhaust section in this book.  
START-UP  
Fig. 33 — Modulating Power Exhaust and Inlet  
Guide Vane Differential Pressure Switch  
(Sizes 034-048)  
Initial Check  
IMPORTANT: Do not attempt to start unit, even mo-  
mentarily, until all items on the Controls Start-Up Check-  
list (in installation instructions) and the following steps  
have been completed.  
1. Verify unit has been installed per the Installation Instruc-  
tions included in the unit installation packet.  
2. Verify that all auxiliary components (sensors, controls,  
etc.) have been installed and wired to the unit control boxes  
per these instructions, the unit Installation Instructions,  
and the unit wiring label diagrams.  
3. Verify that air pressure hoses (static, duct, etc.) are prop-  
erly attached, routed, and free from pinches or crimps that  
may affect proper control operation.  
4. Set any control configurations that are required (field-  
installed accessories, etc.). The unit is factory configured  
for all appropriate factory-installed options with the ap-  
plicable controls programmed to the default values.  
5. Check and adjust unit set points. See Table 9.  
6. Check tightness of all electrical connections.  
Fig. 34 — Inlet Guide Vane Differential  
Pressure Switch and Variable Frequency Drive  
Duct Pressure Transducer (Sizes 054-104)  
7. Perform quick test (see Quick Test Program section on  
page 31).  
Fig. 35 — Modulating Power Exhaust Differential  
Pressure Switch (Sizes 054-104)  
25  
Table 9 — Potentiometer Inputs and Ranges  
CONTROL  
POTENTIOMETER  
DESCRIPTION  
LOCATION  
VALID  
DEFAULT VALUE  
45 F if -22 F < P1 < 45 F  
RANGE  
Supply Air  
Set Point  
Display  
Board  
P1  
45 to 70 F  
0 to 100%  
0 to 80 F  
0 to 100%  
70 F if P1 > 70 F OR IF P1 < -22 F  
Economizer  
Position  
Economizer  
Motor  
P2*  
P3  
None (0 if P2 is bad)  
Accessory  
Board  
Reset Limit  
None (limited to 70 F maximum)  
None  
Demand Limit,  
Single-Step  
P4†  
Main Control Box  
DLCM-P1  
DLCM-P2  
DLCM Board  
DLCM Board  
50 to 100%  
0 to 49%  
None  
None  
Demand Limit,  
2-Step  
Minimum Economizer  
Position  
P5*  
Accessory Board  
Accessory Board  
Reset Board  
0 to 100%  
40 to 80 F  
40 to 100 F  
None  
40 F if 0° F < P6 < 40 F OR IF P6 < 95 F  
OR IF P6 < 0  
80 F if 80 F < P6 < 95 F  
Warm-Up  
Set Point  
P6  
Reset  
Temperature  
P7**  
None  
*Optional factory-installed economizer is required. Potentiometer P2 is not a set point.  
†Accessory two-step demand limit module is required (which has 2 potentiometers), or a 5 to 20 k-ohm  
field-supplied potentiometer is required for single-step demand limit.  
**Accessory temperature reset is required.  
NOTE: Potentiometers P1-P6 input data to pin terminal connector J3.  
Potentiometer P7 inputs data to pin terminal connector J1.  
Table 11 — Configuration Header Jumpers  
Configuration Header — The configuration header  
is a series of 8 small wires that are broken (open circuit) or  
unbroken (closed circuit) in a pattern to indicate several unique  
characteristics of the unit. The configuration header is fac-  
tory set and should not be changed; changing the factory set-  
ting may cause the unit to malfunction.  
Before start-up, visually check the configuration header  
against the factory setting for the unit size. See Table 10 for  
factory settings. See Table 11 for purpose for each jumper.  
JUMPER  
FACTORY  
SETTING  
FUNCTION  
Unit Type  
MEANING  
NUMBER  
1,2  
3,4,5  
6
▫ Ⅲ  
VAV Rooftop Unit  
2 Compressors  
TXV  
Qty Compressors  
Expansion Valve  
Power Frequency  
Not Used  
Ⅲ ▫ ▫  
7
60 Hz  
8
No Significance  
LEGEND  
TXV  
VAV  
Thermostatic Expansion Valve  
Variable-Air Volume  
Table 10 — Configuration Header and  
DIP Switch Factory Settings  
Broken Jumper (open circuit)  
Unbroken Jumper (closed circuit)  
UNIT SIZES  
UNIT SIZE  
044  
UNIT SIZE  
104  
DIP Switches — The DIP switches configure the unit  
for several factory-installed options and field-installed ac-  
cessories, plus factory unloaders. The DIP switches are lo-  
cated under a plastic enclosure which must be removed for  
access. See Fig. 1. The switches can be field adjusted. Switches  
must only be adjusted when control power is deenergized.  
See Table 12 for DIP switch purposes and Table 10 for fac-  
tory settings of the switch positions.  
034-038,  
048-088  
JUMPER OR  
SWITCH NO.  
Header Switch Header Switch Header Switch  
Position Position Position Position Position Position  
1
2
3
4
5
6
7
8
Off  
Off  
Off  
Off  
Off  
Off  
On/Off*  
On/Off*  
Off  
On/Off*  
On/Off*  
Off  
On/Off*  
On/Off*  
Off  
Off  
On  
On  
On  
Off  
Off  
Off  
Off  
Off  
Disconnect control power before changing the settings  
of the DIP switches. To disconnect control power, open  
the control circuit breaker.  
LEGEND  
DIP  
Dual, In-Line Package  
Broken Jumper (open circuit)  
Unbroken Jumper (closed circuit)  
*Depending on factory-installed options or field-installed accessories.  
26  
DIP SWITCH NO. 1 — Supply Air Set Point (SASP) Reset  
Type. Factory setting is OFF. Do not change.  
Potentiometer inputs and ranges are summarized in  
Table 9. Information on individual set point potentiometers  
(including function, location and range data) are shown  
below:  
DIP SWITCH NO. 2 — SASP Reset Enabled. Factory set-  
ting is OFF (no SASP reset enabled). If SASP reset has been  
installed, enable it by changing switch position to ON.  
SUPPLY AIR SET POINT (Leaving-Air Temperature) (P1)  
— This potentiometer establishes the set point for cooling  
cycle operation of the VAV unit. The VAV control uses a  
valid control range of 45 to 70 F, and the potentiometer has  
a valid range of −22 to 70 F. If the set point is between −22  
and 45 F, the control will use a value of 45 F. If the set point  
is outside the valid range (less than −22 F or greater than  
70 F), an alarm condition will be signaled and a default value  
of 70 F will be used.  
DIP SWITCH NO. 3 — Economizer option. If economizer  
option has been installed, this switch will be ON. If there is  
no economizer installed, this switch will be OFF. Confirm  
setting per Table 10. Change only if in error.  
DIP SWITCH NO. 4 — Morning Warm-Up. For 48FK,JK  
models, this switch will be ON (morning warm-up enabled).  
For 50FK,JK units with factory-installed electric heaters, this  
switch will be ON. For all other units, this switch will be  
OFF. If accessory electric heaters are installed (for 50FK,JK  
without plenum option), change this switch to ON.  
ECONOMIZER MINIMUM POSITION (P5) — This po-  
tentiometer specifies the minimum opening position for the  
optional economizer during running periods. It has both a  
valid range and an operational range of 0 to 100%.  
DIP SWITCH NO. 5 — Demand Limit. Factory setting is  
OFF (demand limit not enabled). If Demand Limit (single-  
step or 2-step accessory) has been installed, change this switch  
to ON.  
SASP RESET TEMPERATURE (P7) — This potentiometer  
establishes the space temperature at which the control will  
initiate the reset of the SASP (i.e., the unit control begins to  
raise the base SASP, to prevent overcooling of the space).  
The potentiometer has a valid range of 40 to 100 F. Refer to  
Space Temperature Reset section on page 16 for further dis-  
cussion of SASP Reset operation.  
DIP SWITCHES NO. 6 AND NO. 7 — Unloader Configu-  
ration. These are factory set to match unit size. Confirm set-  
tings per Table 12. Change only if in error.  
RESET LIMIT (P3) — Used in conjunction with P7 poten-  
tiometer, this potentiometer establishes the maximum tem-  
perature for the modified SASP value during the Reset func-  
tion. This potentiometer has a valid range of 0° to 80 F.  
Table 12 — DIP Switches  
SWITCH  
NO.  
SWITCH  
FUNCTION  
MEANING  
POSITION*  
DEMAND LIMIT, SINGLE-STEP (P4) — This potentiom-  
eter establishes the maximum amount of compressor capac-  
ity permitted by the unit control when single-step demand  
limit operation is implemented (by closing contact set to po-  
tentiometer wiper arm). This potentiometer is field-supplied  
and -installed and will be located in the main control box.  
The valid range is 0% to 100%, which is also the operational  
range.  
Reset  
Mode  
Space or Outdoor-Air Reset  
(DO NOT CHANGE)  
1
2
3
4
5
Off  
Reset  
Select  
On  
Off  
Reset Used  
Reset Not Used  
On  
Off  
Enable Economizer  
Disable Economizer†  
Economizer  
Morning  
Warm-Up  
On  
Off  
Enable Morning Warm-Up**  
Disable Morning Warm-Up**  
Demand  
Limit  
On  
Off  
Enable Demand Limit  
Disable Demand Limit  
If the wiper arm is open, all capacity stages can be used.  
When the wiper arm is closed, the capacity is reduced by the  
amount set on potentiometer P4.  
Off, Off  
On, Off  
Off, On  
No Unloaders  
1 Unloader  
2 Unloaders  
6,7  
8
Unloaders  
Not Used  
Off  
No Significance  
DEMAND LIMIT, 2-STEP — The accessory 2-step  
demand limit control is a 2-potentiometer system. The  
demand limit control board (DLCM) accessory board is  
field-installed in the main control box; the 2 control poten-  
tiometers are located on the DLCM. Potentiometer DLCM-P1  
establishes the maximum amount of compressor capacity avail-  
able when SW1 is closed and has a valid range is 50% to  
100%. Potentiometer DLCM-P2 establishes the maximum  
amount of compressor capacity available when SW2 is closed  
and has a valid range is 0% to 49%.  
If no power is supplied to the DLCM, all capacity stages  
can be used. When power is supplied to terminal IN1 only,  
the first step of demand limit control is energized and the  
capacity is reduced by the amount set on potentiometer P1.  
When power is supplied to IN2 (or IN1 and IN2), the ca-  
pacity is reduced by the amount set on potentiometer P2.  
LEGEND  
Dual, In-Line Package  
DIP  
*Control circuit breaker must be off before changing the setting of the DIP switch.  
†No economizer.  
**And/or electric heat (50FK,JK units without plenum only).  
Adjusting Set Points — Set points for unit operation  
are established via potentiometer settings. Set points for Sup-  
ply Fan controls are set at the VFD keypad (if installed) or  
at the IGV differential pressure switch (DPS1) (if IGV op-  
tion installed). Set points for modulating power exhaust (op-  
tion or accessory) are set at the differential pressure switch  
(DPS2).  
MORNING WARM-UP (P6) — This potentiometer estab-  
lishes the set point temperature for the Morning Warm-Up  
function. This is the temperature at which the morning warm-up  
sequence is terminated and VAV cooling operation begins.  
The valid control range is 0° to 95 F, but the control is pro-  
grammed to accept a range of 40 to 80 F. If the set point is  
between 0° and 40 F, the control will use a value of 40 F.  
If the set point is between 80 and 95 F, the control will use  
a value of 80 F. If the set point is outside the valid range  
(less than 0° F or greater than 95 F, an alarm condition will  
be signaled and a default value of 40 F will be used.  
Potentiometers — All of the set point potentiometers  
must be set before the unit is started in order for the unit to  
function properly. Each of the potentiometers has a valid range  
that is used by the control. The valid range is defined as the  
potentiometer’s resistance value that the control will not con-  
sider to be in error. This is usually between 10% and 90%  
of the potentiometer’s total resistance. The control has been  
programmed to accept an operational range for the poten-  
tiometer, which may not be the same as the valid range.  
27  
Supply Fan Control with IGV Option — The inlet  
guide vane option will modulate the supply fan airflow in  
order to maintain the static pressure in the supply duct. The  
set point for duct static pressure is established at the differ-  
ential pressure switch for the IGV control.  
SIZE 034-048 UNITS — The inlet guide vane differential  
pressure switch is located in the auxiliary control box mounted  
in the corner under the side air hood that is next to the access  
door marked FILTER SECTION. To gain access to this con-  
trol box, remove the auxiliary control box cover. When  
replacing cover, be sure to properly secure it in order to  
prevent water from being drawn into the unit. See Fig. 36  
and 37.  
SIZE 054-104 UNITS — The inlet guide vane differential  
pressure witch is mounted on an upright located behind the  
supply-fan motor. See Fig. 36-38.  
The IGV differential pressure switch has an adjustable  
set point range of 1.1 to 3.5 in. wg. and a factory setting of  
1.9 in. wg.  
*The inlet guide vane differential pressure switch for the 034-048 units  
is located in the back of the unit in the auxiliary control box. Its lo-  
cation is not shown in this figure.  
Fig. 36 — Inlet Guide Vane Motor,  
50FK,JK034-074 Units  
To adjust set point, turn set point adjusting screw (see  
Fig. 39) clockwise to decrease set point and counterclock-  
wise to increase set point. This switch also has an adjustable  
null span. The null span is the pressure change that can be  
made without contacts opening or closing. It is adjustable  
from 0.06 in. wg to 0.17 in. wg when set point is at mini-  
mum position (1.1 in. wg) and 0.11 in. wg to 0.31 in. wg  
when set point is at maximum position (3.5 in. wg). To ad-  
just null span, turn a null adjusting screw (Fig. 39) clock-  
wise to decrease span and counterclockwise to increase span.  
All switches leave factory with null span set at maximum  
position. The smaller the null span, the closer the pressure  
will be maintained to desired set point.  
Supply Fan Control with VFD Option — The VFD  
option will modulate Supply Fan motor (and thus wheel) speed  
to maintain the static pressure in the ductwork. Set point for  
the VFD option is set at the VFD, using the display key-  
board on the front of the VFD enclosure. See Fig. 40.  
NOTE: The VFD will always provide the proper phase  
sequence to the supply-fan motor. The supply-fan motor op-  
erates in proper rotation regardless of the phase sequence to  
the unit. If, upon start-up, the outdoor fans operate back-  
wards but the supply fan operates in the correct direction,  
reverse any two leads to the main terminal block. All fans  
will then operate in the correct direction.  
*The inlet guide vane differential pressure switch for the 034-048 units  
is located in the back of the unit in the auxiliary control box. Its lo-  
cation is not shown in this figure.  
Fig. 37 — Inlet Guide Vane Motor, 48FK,JK, 50FY,JY,  
and 50FJX,FJY,FKX,FKY034-074 Units  
To set the duct static pressure, perform the following steps.  
The factory setting is 2.5 in. wg. The duct transducer has  
a range from 0 to 5 in. wg. The transducer output is 4 to  
20 mA, therefore, 0 to 5 in. wg is proportional to the 4 to  
20 mA and must be expressed to the VFD in terms of per-  
centage of the frequency range. Refer to Table 13. The set  
point value is a percentage of the maximum output fre-  
quency. Locate the duct static pressure closest to that de-  
sired and use the corresponding set point value. If necessary,  
interpolation between duct static pressures is permissible.  
Factory-installed optional VFD is located near the sup-  
ply fan and motor. During any service work or pro-  
gramming at the VFD, operation of the fan and motor  
is not desirable and may be dangerous. Either disable  
the unit supply fan (following instructions below) or in-  
stall the accessory VFD remote display accessory.  
Fig. 38 — Inlet Guide Vane Motor,  
Size 078-104 Units  
28  
ADJUST VFD SET POINT — To adjust the VFD set point,  
the VFD must be powered; however, since it is located near  
the supply fan and motor, operation of the fan and motor is  
not desirable. Either disable the Supply Fan or install the  
accessory VFD remote display accessory.  
CAPACITOR  
NULL  
ADJUSTMENT  
COM  
N.C.  
N.O.  
DISABLE SUPPLY FAN MOTOR — To disable the supply  
fan motor and change programming of VFD set point:  
1. Turn off Indoor Fan Circuit Breaker (IFCB). This will  
remove power to the VFD.  
2. Wait for the VFD display to go blank and remove VFD  
cover without touching any interior components.  
3. Ensure that the charge indicator lamp is out which in-  
dicates that the VFD is discharged. The lamp is located  
on the upper right hand corner of the terminal block. If  
still lit, wait until lamp goes completely out. This may  
take several minutes.  
4. Remove jumper from terminals ST-CC (see Fig. 41) and  
replace VFD cover.  
5. Turn on IFCB.  
6. The drive output will now be disabled but the program-  
ming can be changed.  
SET  
POINT  
ADJUSTMENT  
SET  
POINT  
INDICATOR  
LEGEND  
COM  
N.C.  
N.O.  
Common  
Normally Closed  
Normally Open  
Fig. 39 — Differential Pressure Switch for Inlet Guide  
Vane and Static Pressure Control Option and  
Modulating Power Exhaust Option  
7. Change VFD set point according to Table 14 shown  
below.  
8. Once the program changes are completed, turn off IFCB.  
9. Wait for the VFD display to go blank and remove VFD  
cover without touching any interior components.  
10. Ensure that the charge indicator lamp is out which in-  
dicates that the VFD is discharged. The lamp is located  
on the upper right hand corner of the terminal block. If  
still lit, wait until lamp goes completely out. This may  
take several minutes.  
HZ  
PERCENT  
SECONDS  
KW/AMPS/VOLTS  
11. Replace jumper to terminals ST-CC.  
12. Replace VFD cover.  
13. Turn on IFCB to enable the drive.  
For additional information on the VFD (including basic  
troubleshooting, factory jumper arrangements, and Carrier  
factory defaults programming), refer to Troubleshooting, Vari-  
able Frequency Drive section (page 52).  
SETUP  
PROGRAM  
MONITOR  
RUN  
READ  
STOP  
WRITE  
RESET  
IMPORTANT: The Carrier factory default values for  
the VFD may be different than the default values of  
the manufacturer. Refer to the Service section when  
checking default values.  
MANUAL/AUTO  
LOCAL/REMOTE  
RUN MODE  
SPEED CTRL  
Fig. 40 — Variable Frequency Drive Keypad  
DETERMINE VFD SET POINT — The unit of measure for  
the Duct Pressure set point at the VFD is output frequency  
(Hz), representing the desired DP set point (DPSP) in inches  
of water gage (in. wg). To convert desired DPSP into the  
VFD set point, refer to Table 13. Locate the pressure value  
in the table closest to the desired DPSP for this installation  
and use the corresponding VFD set point (Hz) value. If nec-  
essary, interpolation between duct static pressure values is  
permissible.  
P24 RES RR  
F
R
S1 S2 S3 S4 RCH P24 LOW LOW  
CC RX PP IV FP FLC FLB FLA  
ST  
FM AM CC  
REMOVE  
JUMPER  
Fig. 41 — Jumper Removal to Disable Motor  
29  
Table 13 — VFD Set Point (Frequency Command) for Duct Pressure  
PRESSURE  
(in. wg)  
CONTROL SIGNAL  
(mA)  
PRESSURE  
(in. wg)  
VFD SET POINT  
(Hz)  
CONTROL SIGNAL  
(mA)  
VFD SET POINT (Hz)  
0.00  
0.25  
0.50  
0.75  
1.00  
1.25  
1.50  
1.75  
0
3
4.0  
4.8  
5.6  
6.4  
7.2  
8.0  
8.8  
9.6  
2.00  
2.25  
2.50  
2.75  
3.00  
3.25  
3.50  
24  
27  
30  
33  
36  
39  
42  
10.4  
11.2  
12.0  
12.8  
13.6  
14.4  
15.2  
6
9
12  
15  
18  
21  
Table 14 — Changing the VFD Set Point (Frequency Command)*  
KEY OPERATION  
LED MESSAGE  
EXPLANATION  
Standard Monitor Mode (output frequency). If drive is disabled, display  
will read ЉOFFЉ. If enabled, display will show current output frequency  
XX.X or OFF  
↓↑  
60.0  
Pressing arrow key once will display the current frequency setpoint  
Pressing up/down arrow keys changes the desired setpoint  
45.0 (flashing)  
When R/W is pressed, the parameter name (FC) and the new value  
(45.0) will alternately flash to indicate that the new value has been  
stored. After 2 cycles, the display will return to the standard monitor  
mode.  
R/W  
FC and 45.0 (flashing)  
XX.X or OFF  
Standard Monitor Mode (output frequency). If drive is disabled, display  
will read ЉOFFЉ. If enabled, display will show current output frequency  
*Choose set point from Table 13 according to desired duct pressure.  
DIFFERENTIAL PRESSURE SWITCH — The modulating  
power exhaust DPS has a set point range of 0.5 in. wg to  
−0.5 in. wg. Factory setting is +0.1 in. wg. To adjust set point,  
turn set point adjusting screw (see Fig. 39) clockwise to  
decrease set point and counterclockwise to increase set point.  
This switch also has an adjustable null span. The null span  
is the pressure change that can be made without contacts  
opening or closing. It is adjustable from 0.06 in. wg to  
0.14 in. wg when set point is at minimum position  
(−0.5 in. wg) and 0.07 in. wg to 0.14 in. wg when set point  
is at maximum position (+0.5 in. wg). To adjust null span,  
turn null adjusting screw (Fig. 39) clockwise to decrease span  
and counterclockwise to increase span. All switches leave  
factory with null span set at maximum position. The smaller  
the null span, the closer the pressure will be maintained to  
desired set point.  
Modulating Power Exhaust (Option or Acces-  
sory) — The Modulating Power Exhaust system will main-  
tain space pressure by modulating power exhaust fan no. 1  
and staging power exhaust fan no. 2. Building pressure set  
point is established at the modulating power exhaust differ-  
ential pressure switch (DPS).  
SIZE 034-048 UNITS — The modulating power exhaust dif-  
ferential pressure switch is located in the auxiliary control  
box mounted in the corner next to the power exhaust motor  
door. To gain access to this control box, remove the auxil-  
iary control box cover. When replacing cover, be sure to prop-  
erly secure it in order to prevent water from being drawn  
into the unit. See Fig. 33.  
SIZE 054-104 UNITS — The modulating power exhaust dif-  
ferential pressure switch is mounted below the auxiliary con-  
trol box next to the access door labeled FILTER SECTION.  
See Fig. 35.  
30  
For each step of the 33-step program, display button must  
be pressed twice. On first press, step number is displayed;  
second press initiates required action and appropriate code  
is displayed.  
NOTE: The step number is a numeral followed by a decimal  
point (a 2-digit number has a decimal point after each nu-  
meral). The action code number is one or 2 digits with no  
decimal point(s).  
START UNIT  
To start unit:  
1. Close the unit-mounted ON/OFF switch (located in the  
main control box).  
2. Close the field-supplied and -installed timeclock (or con-  
trol) switch (contacts located at Terminals 1 and 2 (TB3  
for 034-048, TB4 for 054-104).  
IMPORTANT: The field-supplied and installed switch  
(or timeclock) MUST BE CLOSED to put unit in  
Occupied mode. Unit WILL NOT START until this  
is accomplished.  
IMPORTANT: Once quick test is initiated, display but-  
ton must be pressed at least once every 10 minutes for  
control to remain in quick test mode. If button is not  
pressed within this time, control will attempt to start  
the unit.  
3. Initialization mode begins (see Operating Information sec-  
tion on page 34 for complete description of sequences  
and display codes).  
4. Run Quick Test. If the display button is pressed during  
the initialization mode period, the unit will run its self-  
To recheck any step in quick test program, control must  
be recycled by turning unit control switch off for a few sec-  
onds, and then turning it back on again. Restart quick test  
program as described above and proceed through quick test  
steps. Press display button twice for each step until step to  
be rechecked is reached.  
diagnostic routine. When this is in effect, an 88 will ap-  
pear in the display screen. Refer to Quick Test Program  
section below, for instructions on completing the Quick  
Test program.  
The quick test program is divided into 3 sections as de-  
scribed below and shown in Tables 15-17.  
1. Quick Test Steps 1.-1.3. — Unit Configuration and Switch  
Check  
Quick Test Program — Turn on power to unit.  
IMPORTANT: The field-supplied switch (or time-  
clock) must be closed to put unit into the occupied mode.  
The microprocessor in unit control system is programmed  
by 2 switch assemblies located on processor board  
(Fig. 1). The configuration header is factory set and can-  
not be changed in the field. The DIP switch assembly con-  
tains 8 microswitches that must be set in accordance with  
the various options selected by the customer. All DIP  
switches should be checked and set to proper position for  
options selected prior to the quick test. See Configuration  
of Header and DIP Switch Assembly section on page 5  
for factory switch settings. The DIP switch functions and  
display codes are shown in Table 15.  
The quick test program utilizes the 2-digit LED display  
(see Fig. 6) on the set point board to show status of all input  
and output signals to microprocessor. Display action and quick  
test procedures are described below.  
The quick test program is a 33-step program that provides  
a means of checking all input and output signals of controls  
prior to unit start-up. This check ensures that all control op-  
tions, thermistors, and control switches are in proper work-  
ing order.  
2. Quick Test Steps 1.4.-2.3. — Thermistor and Set Point  
Potentiometer Check  
When unit control circuit is switched to Occupied mode,  
a 20 will appear on the display. Immediately press display  
button once. An 88 will appear on the display and alarm  
In these steps, the microprocessor checks resistance val-  
ues of all sensors and set point potentiometers to ensure  
that they are functional, connected properly, and set within  
proper range for unit configuration.  
Nominal resistance values for all sensors range from 363,000  
to 219 ohms in accordance with Table 18. Normal dis-  
play code for good sensors and potentiometers is 1. A dis-  
play code of 0 indicates a faulty potentiometer, thermistor  
or wiring. A 0 display also indicates that option is not  
being used.  
light on display board will be energized. This indicates that  
control system is ready to run quick test program.  
IMPORTANT: Do not allow unit control circuit to  
remain energized with 20 showing on display for more  
than 2 minutes. If display button is not pressed within  
this time period, control will attempt to start unit.  
Table 16 shows thermistor and set point potentiometer  
functions and quick test display codes.  
31  
Table 15 — Quick Test, Unit Configuration and Switch Check  
QUICK  
TEST  
NORMAL  
DISPLAY  
DESCRIPTION  
CONTROL SWITCH  
STEP NO.  
1.  
2.  
3.  
01  
2
Type Unit — Air-Cooled VAV  
No. of Compressors  
Configuration Header  
Configuration Header  
DIP Switch No. 6 and 7  
No. of Unloaders  
(034,038,048-088)  
2
1
(044, 104)  
4.  
5.  
60  
60-Hertz Power  
Configuration Header  
DIP Switch No. 2  
0 — No Reset (Switch Off)  
1 — Reset On (Switch On)  
0
0
0
0
or  
or  
or  
or  
1
1
1
1
0 — No Economizer (Switch Off)  
1 — Economizer On (Switch On)  
DIP Switch No. 3  
DIP Switch No. 4  
DIP Switch No. 5  
6.  
7.  
8.  
0 — No Warm-Up (Switch Off)  
1 — Warm-Up Used (Switch On)  
0 — Demand Limit Not Used  
(Switch Off)  
1 — Demand Limit Used  
(Switch On)  
0 — Enthalpy Switch Open  
1 — Enthalpy Switch Closed  
EC  
9.  
0
or  
1
1
1 — Low-Pressure Switch Closed  
1 — Low-Pressure Switch Closed  
No Circuit 1 Oil Pressure Switch  
No Circuit 2 Oil Pressure Switch  
Low-Pressure Switch 1  
Low-Pressure Switch 2  
None*  
1.0.  
1.1.  
1.2.  
1
1
1.3.  
1
None*  
LEGEND  
DIP  
EC  
VAV  
Dual, In-Line Package  
Enthlapy Control  
Variable Air Volume  
*Units are not equipped with oil pressure switches.  
32  
Table 16 — Quick Test, Thermistor and Potentiometer Check  
QUICK  
TEST  
STEP NO.  
NORMAL  
DISPLAY  
THERMISTOR OR  
POTENTIOMETER*  
DESCRIPTION  
1 — Thermistor OK  
0 — Thermistor Faulty  
Supply Air  
Thermistor (T1)  
1.4.  
1.5.  
1.6.  
1.7.  
1
1
1
1
1 — Thermistor OK  
0 — Thermistor Faulty  
Return Air  
Thermistor (T2)  
1 — Thermistor OK  
0 — Thermistor Faulty  
Circuit 1 Condenser Thermistor  
(T3)  
1 — Thermistor OK  
0 — Thermistor Faulty  
Circuit 2 Condenser Thermistor  
(T4)  
1 — Thermistor or Potentiometer OK  
0 — Thermistor or Potentiometer Faulty or  
Option not used  
Accessory Space Temperature Thermistor (T10)  
or Accessory Reset Potentiometer (P7)  
1.8.  
1
1 — Potentiometer OK  
0 — Potentiometer Faulty  
Supply-Air Set Point  
Potentiometer (P1)  
1.9.  
2.0.  
2.1.  
1
1
1
1 — Potentiometer OK  
0 — Potentiometer Faulty or Option not used  
Accessory Reset Limit  
Potentiometer (P3)  
1 — Potentiometer OK  
0 — Potentiometer Faulty or Option not used  
Accessory Demand Limit  
Potentiometer (P4)  
Minimum Position  
Economizer  
Potentiometer (P5)  
1 — Potentiometer OK  
0 — Potentiometer Faulty or Option not used  
2.2.  
2.3.  
1
1
1 — Potentiometer OK  
0 — Potentiometer Faulty or Option not used  
Warm-Up Set Point  
Potentiometer (P6)  
*Potentiometer P2 is not listed since it is not part of the quick test. If on unit start-up a Code 83 is displayed, check potentiometer P2.  
Table 17 — Quick Test, Output Relay Check  
QUICK  
TEST  
STEP NO.  
NORMAL  
DISPLAY  
DESCRIPTION  
RELAY NUMBER  
2.4.  
2.5.  
1
1
1 — Open Economizer or Open Relay if no Economizer  
1 — Close Economizer or Close Relay if no Economizer  
1 — Energize Fan Relay and Heat Relay  
Energize Stage 1 Condenser Fan(s)  
Energize Stage 2 Condenser Fan(s)  
Energize Compressor 1†  
K7  
K8  
K9* and K10  
2.6.  
2.7.  
1
1
K11  
K12  
K1  
2.8.  
2.9.  
1
0
0
then  
1
0
0
1
0
then  
0
0
3.0.  
Energize Unloader 2; Not Used (044, 104)  
Energize Unloader 1  
K2  
3.1.  
K3  
3.2.  
then  
then  
Energize Compressor 2†  
K5  
3.3.  
Not Used  
K6  
LEGEND  
CR  
Control Relay  
*K9 (fan relay) will remain on for duration of quick test.  
†Compressor will be energized for 10 seconds. Zero indicates open CR; 1 indicates closed CR.  
33  
Table 18 — Sensor Resistance Values  
load if the outdoor enthalpy is good. As long as the outdoor-  
air enthalpy is acceptable, no mechanical cooling will take  
place until the economizer dampers are fully open. The rest  
of the steps and the operational sequence vary due to the  
number of compressors and unloaders. Refer to Operating  
Sequence section on page 35 for the unit stages of operation.  
TEMP RESISTANCE TEMP RESISTANCE TEMP RESISTANCE  
(F)  
(Ohms)  
(F)  
(Ohms)  
(F)  
(Ohms)  
−60  
362,640  
297,140  
245,245  
202,841  
168,250  
139,960  
116,820  
98,420  
82,665  
69,685  
58,915  
50,284  
42,765  
36,475  
31,216  
26,786  
23,164  
19,978  
17,276  
14,980  
13,085  
45  
50  
55  
60  
65  
70  
75  
80  
85  
11,396  
9,950  
8,709  
7,642  
6,749  
5,944  
5,249  
4,644  
4,134  
3,671  
3,265  
2,913  
2,600  
2,336  
2,092  
1,879  
1,689  
1,527  
1,377  
1,244  
1,126  
150  
155  
160  
165  
170  
175  
180  
185  
190  
195  
200  
205  
210  
215  
220  
225  
230  
235  
240  
1,020  
929  
844  
768  
699  
640  
585  
535  
490  
449  
414  
380  
350  
323  
299  
276  
255  
236  
219  
−55  
−50  
−45  
−40  
−35  
−30  
−25  
−20  
−15  
−10  
−5  
CODES 20 THROUGH 30 AND 88, OPERATIONAL STA-  
TUS — These codes indicate special operational modes, such  
as initialization, morning warm-up, temperature reset, de-  
mand limit, or an internal failure of the board. Codes 23-25  
and 27-29 are not used on these units.  
90  
95  
Initialization — When the control is turned on, the display  
100  
105  
110  
115  
120  
125  
130  
135  
140  
145  
0
5
shows a  
for approximately 2 minutes to indicate that the  
20  
10  
15  
20  
25  
30  
35  
40  
control is in the initialization mode. During this time, the  
economizer dampers open and close to determine the resis-  
tance range of the economizer position potentiometer (P2)  
for full economizer operation. The processor loads the nec-  
essary constants for proper unit operation and checks the ther-  
mistors and other potentiometers for their values and valid-  
ity. After the initialization period, the display screen goes  
blank until the display button is pressed. If the display but-  
ton is pressed during the 2-minute initialization period, the  
control goes into the Quick Test mode.  
3. Quick Test Steps 2.4.-3.3. — Output Relay Check  
Temperature Reset — If the unit is equipped with the ac-  
cessory temperature reset package, and DIP switch 2 is in  
the ON position, the unit will reset the supply-air tempera-  
ture to a calculated value when necessary. When this con-  
These quick test steps allow microprocessor to check  
output signals from relay boards in unit control system. In ad-  
dition, operation of all the condenser fans, compres-  
sors, and economizer (if equipped) are checked at each step.  
dition is in effect, a  
will appear in the display.  
21  
Normal display for Steps 2.4. through 2.8. is 1. In Steps  
2.9. through 3.2., each compressor and unloader is started  
and allowed to run for approximately 10 seconds. At start-  
up, a 0 will appear on the display followed by a 1 (Steps  
2.9. and 3.2.) in a few seconds. Steps 3.0. and 3.1. will  
always be 0 since there are unloaders, and Step 3.3. will  
always be zero since it is not used.  
At end of the 10-second time period, a 0 will return to the  
display board indicating that test step has been success-  
fully completed (Steps 2.9. and 3.2.). The 1 indicates that  
was tested.  
Demand Limit — If the unit is equipped with the accessory  
demand limit control module or the field-supplied, single-  
step demand limit potentiometer, and DIP switch 5 is in the  
ON position, the unit will limit the capacity stages to a pre-  
determined value. When this condition is in effect, a  
appear in the display.  
Morning Warm-Up —If the morning warm-up heat routine  
is enabled using DIP switch 4, and conditions of the occu-  
pied space warrant, the unit will begin the morning warm-up  
routine. When this condition is in effect, a  
in the display.  
will  
22  
will appear  
26  
Fan and compressor operating sequence for quick test  
Steps 2.4. through 3.3. are shown in Table 17.  
Internal Failure — If the unit detects an internal fault (such  
as a time measurement failure), or detects an incorrect volt-  
If the quick test steps do not operate as described above,  
a defect exists in one or more of the following: relay being  
tested, electronic control, or unit wiring. Determine problem  
and correct.  
age on an input channel, a  
unit will shut down.  
will be displayed, and the  
30  
Quick Test — If the display button is pressed during the  
initialization period of the processor, the unit will run its self-  
OPERATING INFORMATION  
diagnostic routine. When this is in effect, an  
in the display screen.  
will appear  
88  
Digital Display — The VAV control system uses a 2-digit  
LED display located on the display board to display opera-  
tional information and diagnostic codes.  
CODES 51 THROUGH 87, DIAGNOSTIC INFORMA-  
TION — These codes indicate diagnostic information when  
there is a unit problem such as a faulty thermistor, potenti-  
ometer, or compressor fault. Refer to Diagnostic Codes sec-  
tion on page 45 for more details. Codes 53, 54, 57, 58, 61,  
62, 65-69, 73, 74, and 77-80 are not used on these units.  
CODES 0 THROUGH 8, CAPACITY STEPS — These codes  
indicate the number of cooling stages active at the time the  
display button is pressed. The highest code indicated on the  
display will be 6 for the 034,038 and 048-088 units, 4 for the  
044 units, and 8 for the 104 units.  
Under normal operation, only the stage number is dis-  
played when the display button is pressed. If a status or over-  
load code is displayed, the display will rotate every 2 sec-  
onds and will display up to 3 codes. Overload information  
takes priority over all other codes. The codes are stored in  
the microprocessor as long as the board remains energized.  
Capacity steps are directly related to pin terminal connec-  
tor J6 output. At step zero, the unit has no mechanical cool-  
ing on, and the economizer may or may not be operating  
(depending on the outdoor air conditions). Once a cooling  
load is detected (T1 thermistor reads above the supply-air  
set point), the economizer will begin modulating to meet the  
34  
Compressors, unloaders, and condenser fans will be cycled  
to maintain a supply-air temperature 2° F below the poten-  
tiometer P1 set point once the mechanical cooling stages be-  
gin. Each unit’s cycling is slightly different, and is based on  
the number of compressors and unloaders. The operational  
loading sequence of compressors is as follows:  
During the start-up of the lead compressor for each cir-  
cuit, the low-pressure switch will be bypassed for 120 sec-  
onds to prevent nuisance trips of the low-pressure switch.  
After start-up, a low-pressure trip will be ignored for 30 sec-  
onds by the processor.  
Operating Sequence — The sequence presented be-  
low assumes that the unit is equipped with heat for morning  
warm-up and an economizer. If these items are not enabled  
with the appropriate DIP switches, the processor bypasses  
these subroutines. This sequence is also based on an EPROM  
(erasable, programmable, read-only memory) processor chip  
with the identification ‘HT204485-1-XX,’ where ‘XX’ is re-  
placed by a 2-digit number representing the current software  
version. See Fig. 1 for EPROM chip location.  
When power is applied to the occupied mode relay (OMR)  
through the closure of either a field-installed timeclock or a  
field-installed switch in the occupied space, the unit will be-  
gin its initialization mode.  
SIZE 034,038 AND 048-088 UNITS — These units have 2  
compressors and 2 unloaders on compressor 1. See Fig. 42  
and 43 for compressor and condenser-fan motor locations.  
The operating sequence is as follows:  
20  
A
will appear in the display screen, and the initial-  
ization period will last approximately 2 minutes. During this  
time, the economizer dampers open and close to determine  
the resistance range for full economizer operation of the econo-  
mizer position potentiometer (P2). The processor loads the  
necessary constants for unit operation, and also checks the  
thermistors and other potentiometers for their values and va-  
lidity. After the initialization period, the screen goes blank  
until the display button is pressed.  
Stage 1 Relays K1, K2, and K3 are energized. Compressor  
no. 1 starts with both unloaders energized. Com-  
1
pressor no. 1 runs at 3 capacity. The crankcase  
heater for this compressor has been deenergized,  
and the first stage of condenser fans have been en-  
ergized. Outdoor (condenser) fan motor no. 1  
(OFM1) has started on all units.  
Stage 2 Relays K1 and K3 are energized. Compressor  
no. 1 is running with unloader 1 (U1) energized.  
2
The compressor is now operating at 3 capacity.  
Use caution during this time (after initialization when  
the screen is blank), because the unit supply and return  
fans could start at any time. Personal injury could result  
from contact with rotating fans.  
Stage 3 Relay K1 is energized. Compressor no. 1 is fully  
loaded.  
Stage 4 Relays K1, K2, K3, and K5 are energized. Com-  
1
pressor no. 1 is running at 3 capacity, and com-  
Once the initialization period is complete, the supply fan  
begins operation. While the fan is operating, the economizer  
dampers are closed and return air from the building is being  
circulated. After 2 minutes, the processor checks the resis-  
tance value of thermistor T2. If T2 temperature sensed is  
5° F or more below the set point of the morning warm-up  
potentiometer (P6), the unit will begin the morning  
pressor no. 2 is running at full capacity. The crankcase  
heater for compressor no. 2 has been deenergized.  
Stage 5 Relays K1, K3, and K5 are energized. Compressor  
2
no. 1 is running at 3 capacity, and compressor  
no. 2 is running at full capacity.  
Stage 6 Relays K1 and K5 are energized. Both compres-  
sors are running fully loaded.  
warm-up routine, and a 26 will be displayed.  
Size 034 and 038 units have 2 condenser fans, one of which  
is controlled by the microprocessor. The OFM1 is energized  
with compressor no. 1. The OFM2 is controlled by the pro-  
cessor and is cycled based on input from circuit thermistor  
T3 or T4.  
Size 048 units have one fan that can be controlled by the  
processor. The other 2 are controlled by the compressors.  
The OFM1 is energized by compressor no. 1, and OFM3 is  
energized by compressor no. 2. The OFM2 is cycled by the  
processor based on input from either circuit (thermistors T3  
and T4).  
Unit heat will be energized through the heat interlock re-  
lay (HIR), and all of the occupied space air terminals open.  
The unit will continue heating the space until the return-air  
temperature is within 2° F of set point. The unit will then  
shut off the heat and continue to circulate air. The unit will  
cycle in and out of the heating mode until the return-air tem-  
perature reaches the morning warm-up set point (P6). Once  
morning warm-up has been terminated, the unit cannot re-  
turn to morning warm-up until the unit is powered down and  
restarted. This action signals a return to the Occupied mode.  
NOTE: Occupied heat is NOT AVAILABLE on these units.  
On size 054,064 units, the first 2 condenser fans energize  
with the compressors; compressor no. 1 controls OFM1, and  
compressor no. 2 controls OFM2. The OFM3 and OFM4 are  
staged by the microprocessor based on the condensing tem-  
perature input from thermistor T3 or T4.  
On size 074-078 units, the first 3 condenser fans energize  
with the compressors; compressor no. 1 controls OFM1, and  
compressor no. 2 controls OFM2 and OFM3. The OFM4  
and OFM5 are staged by the microprocessor based on con-  
densing temperature input from either circuit’s T3 or T4  
thermistor.  
On Size 088 units, the first 4 condenser fans energize with  
the compressors; compressor no. 1 controls OFM1 and OFM3,  
and compressor no. 2 controls OFM2 and OFM4. The OFM5  
and OFM6 are staged by the microprocessor based on  
condensing temperature input from either circuit’s T3 or T4  
thermistor.  
Once out of the morning warm-up routine, the unit will  
begin its cooling routine based on the supply-air set point  
(P1). At step zero, the unit has no mechanical cooling on,  
and the economizer may or may not be operational. The econo-  
mizer will move to the minimum position determined by po-  
tentiometer P5 if no cooling load is detected. Once a cooling  
load is detected by thermistor T1 sensing a temperature higher  
than the cooling demand set point (P1), the economizer will  
begin modulating to meet the load if the outdoor enthalpy is  
good. The processor will attempt to maintain a supply-  
air temperature of P1 ± 2° F by modulating the economizer  
dampers.  
No mechanical cooling will take place until the econo-  
mizer dampers are fully open (if the outdoor-air enthalpy  
permits). If the economizer is unable to meet the cooling  
demand, then mechanical cooling is used in conjunction with  
the economizer. If the economizer is unable to meet the load  
due to unacceptable outdoor-air enthalpy, the dampers will  
return to the minimum position as determined by P5.  
35  
SIZE 044 UNITS — These units have 2 compressors and 1  
unloader on compressor no. 1. See Fig. 42 for compressor  
and condenser fan motor locations. The unit operating se-  
quence is as follows:  
Stage 1 Relays K1 and K3 are energized. Compressor  
no. 1 starts with the unloader energized. Com-  
pressor no. 1 is running at 12 capacity. The crank-  
case heater on compressor no. 1 has been deen-  
ergized, and the first stage condenser fan has been  
energized. Outdoor (condenser) fan motor no. 1  
(OFM1) has started.  
Stage 4 Relays K1 and K5 are energized. Both compres-  
sors no. 1 and no. 2 are running fully loaded.  
Stage 5 Relays K1, K3, K5, and K5 are energized. Com-  
pressor no. 1 runs at 23 capacity and compressors  
no. 2 and no. 4 are running at full capacity. The  
crankcase heater on compressor no. 4 is deener-  
gized. Fans OFM1, OFM2, OFM3, and OFM4 are  
operating.  
Stage 6 Relays K1, K5, and K6 are energized. Compres-  
sors no. 1, no. 2, and no. 4 are running fully loaded.  
Stage 7 Relays K1, K2, K3, K5, and K6 are energized.  
Stage 2 Relay K1 is energized. Compressor no. 1 is fully  
loaded.  
2
Compressor no. 1 runs at 3 capacity and com-  
pressors no. 2, no. 3, and no. 4 are running at full  
capacity. Fans OFM1, OFM2, OFM3, and OFM4  
are operating. Crankcase heater for compressor  
no. 3 is deenergized.  
Stage 3 Relays K1, K3, and K5 are energized. Compres-  
1
sor no. 1 is running at 2 capacity, and compres-  
sor no. 2 is running at full capacity. The crankcase  
heater for compressor no. 2 is deenergized. The  
second stage condenser fan has been energized.  
Both OFM1 and OFM3 are operating.  
Stage 8 Relays K1, K2, K5, and K6 are energized. Com-  
pressors no. 1, no. 2, no. 3, and no. 4 are running  
fully loaded.  
On Size 104 units, the first 4 condenser fans energize with  
the compressors; circuit no. 1 compressors control OFM1  
and OFM3, and circuit no. 2 compressors control OFM2 and  
OFM4. The OFM5 and OFM6 are staged by the micro-  
processor based on condensing temperature input from  
either circuit’s T3 or T4 thermistor.  
Stage 4 Relays K1 and K5 are energized. Both compres-  
sors are running fully loaded.  
Size 044 units have one fan that can be controlled by the  
processor. The other 2 are controlled by the compressors.  
The OFM1 is energized by compressor no. 1, and OFM3 is  
energized by compressor no. 2. The OFM2 is cycled by the  
processor based on input from either circuit (thermistors T3  
and T4).  
SIZE 104 UNITS — These units have 4 compressors and  
1 unloader on compressor no. 1. See Fig. 43 for compressor  
and condenser fan motor locations. The unit operating se-  
quence is as follows:  
Head Pressure Control — All units have as standard  
a basic head pressure control function which allows the units  
to operate in cooling down to 45 F. If cooling is required at  
outdoor ambient temperatures lower than 45 F, refer to ac-  
cessory head pressure control literature for details.  
Head pressure control is handled by the processor. The  
processor attempts to maintain the head pressure by cycling  
the condenser-fan motors. No condenser fans will be run-  
ning without a call for mechanical cooling. Thermistors T3  
and T4 provide the condensing temperature information to  
the processor. These VAV rooftop units have dual refrigera-  
tion circuits, and the higher circuit temperature will govern  
unit operation. If the condensing temperature is above  
133 F (236 psig), a condenser fan stage will be added. If the  
condensing temperature is 78 F (142 psig) or less, the num-  
ber of condenser fans operating will be decreased. After each  
fan stage, the processor will wait one minute for the head  
pressures to stabilize before changing again, unless ther-  
mistor T3 or T4 senses a temperature greater than 125 F  
(278 psig), in which case all condenser fans are started.  
Stage 1 Relays K1 and K3 are energized. Compressor  
no. 1 starts with unloader energized. Compressor  
no. 1 runs at 23 capacity. The crankcase heater for  
this compressor has been deenergized, and first stage  
of condenser fans has been energized. Outdoor (con-  
denser) fan motor no. 1 (OFM1) and oudoor fan  
motor no. 3 (OFM3) have started.  
Stage 2 Relay K1 is energized. Compressor no. 1 is fully  
loaded.  
Stage 3 Relays K1, K3, and K5 are energized. Compres-  
2
sor no. 1 runs at 3 capacity and compressor  
no. 2 is running at full capacity. The crankcase  
heater for compressor no. 2 is deenergized. The  
first stae of condenser fans on circuit 2 has been  
energized. Fans OFM1, OFM2, OFM3, and OFM4  
are operating.  
During start-up, if the outdoor ambient is above 70 F (as  
sensed by thermistor T3 or T4), the first-stage, processor-  
controlled fans are turned on to prevent excessive discharge  
pressures.  
034 AND 038 UNITS  
LEGEND  
044 AND 048 UNITS  
OFM  
Outdoor (Condenser) Fan Motor  
Fig. 42 — Component Arrangement, 034-048 Units  
36  
054, 064 UNITS  
054-088 UNITS  
074, 078 UNITS  
088, 104 UNITS  
104 UNITS  
Fig. 43 — Component Arrangement, 054-104 Units  
37  
Supply Fan Control with IGV — In most VAV units,  
the supply fan static pressure is controlled by inlet guide vanes.  
The inlet guide vanes operate independently from the micro-  
processor. The supply static pressure is controlled by a dif-  
ferential pressure switch. If the unit is equipped with a re-  
turn fan, building pressure is controlled by another differential  
pressure switch.  
Modulating Power Exhaust (Option or Acces-  
sory except FY,JY units) — The power exhaust as-  
sembly consists of two parallel and independent belt-drive  
forward curve fans. The fans, motors, and drives are located  
over the return air opening of the unit, in a plenum beneath  
the outside air intake plenum. The fans discharge air hori-  
zontally out the back of the unit through individual baro-  
metric backdraft dampers with hoods. (See Fig. 44 and 45.)  
Operation is interlocked with economizer operation. Sheet  
metal installation is shown in Fig. 46 and 47.  
Fan no. 1 is equipped with a variable position discharge  
damper located in the outlet of the fan housing. This damper  
is controlled by an actuator (PEDM), based on signals from  
the building pressure differential pressure switch (DPS). Avail-  
able range on the DPS is −0.50 to +0.50 in. wg, adjustable.  
Building pressure is sensed by a pick-up (field-supplied and  
-installed) located in the occupied space.  
Operation of the modulating power exhaust is a combi-  
nation modulating/staged control, with fan no. 1 providing  
modulating control from 0 to 100%, and fan no. 2 being staged  
On/Off according to damper position on fan no. 1.  
As the economizer actuator opens past 17% open, auxil-  
iary switch DMS1 closes, energizing fan contactor PEC1.  
Fan motor no. 1 starts and runs.  
Capacity of fan no. 1 is controlled by the position of the  
outlet damper. As building pressure increases above set point,  
the DPS will close its contact and drive the power exhaust  
damper motor (PEDM) open until set point is achieved. DPS  
then opens its control contacts and PEDM maintains current  
position.  
When space demand moves PEDM to 90% of full-open  
position, auxiliary switch PEDMS closes, energizing fan con-  
tactor PEC2. Fan motor no. 2 starts and runs. Increased ex-  
haust airflow will lower space pressure, causing DPS to drive  
PEDM back towards its closed position, until the set point  
is achieved.  
For example, assume that set point on supply fan differ-  
ential switch is 1.9 in. wg. If pressure in supply duct goes  
above 1.9 in. wg, switch will make to the normally open  
contact and energize inlet guide vane motor to drive inlet  
guide vanes to a more closed position, thus reducing airflow  
and lowereing duct pressure. Once set point pressure is reached,  
switch will open and deenergize inlet guide vane motor. If  
pressure in supply duct is below 1.9 in. wg, the switch will  
make to the normally closed contact and energize inlet guide  
vane motor to drive inlet guide vane to a more open posi-  
tion; increasing airflow and raising duct pressure. Once again,  
once desired pressure has been reached, switch will open and  
deenergize inlet guide vane motor. How far above or below  
the set point setting the switch goes before energizing de-  
pends on setting of null span (null span is pressure change  
that can be made without contacts opening or closing). If  
null span is at maximum position, pressure will vary from  
0.17 in. wg to 0.31 in. wg depending on set point (if set point  
is at minimum setting, null span will be 0.17 in. wg, while  
if it is at maximum position, the null span will be  
0.31 in. wg) before switch acts. If null span is adjusted to a  
minimum setting, duct pressure will vary from 0.06 in. wg  
to 0.11 in. wg (again depending on switch set point) before  
switch acts. Setting null span to minimum position will re-  
sult in a smaller pressure fluctuation than if it is set at maxi-  
mum position.  
Supply Fan Control with VFD — When equipped  
with the VFD option, the supply fan static pressure is con-  
trolled by modulating the fan wheel speed. The VFD oper-  
ates independently from the microprocessor. A duct pressure  
transducer monitors duct static pressure. The transducer out-  
put (4 to 20 mA) is directed into the VFD. The VFD adjusts  
supply fan motor speed (which changes wheel speed) as mea-  
sured duct pressure varies from set point as established at  
the VFD. The VFD will modulate fan speed until the duct  
pressure set point is achieved.  
If space pressure decreases until PEDM position is re-  
duced to 10% of open position, PEDMS will open, deener-  
gizing fan contactor PEC2 and shutting off fan no. 2.  
Unit Staging — Compressor loading and unloading se-  
quences are shown in Table 19.  
NOTE: The VFD will always provide the proper phase se-  
quence to the supply fan motor. This motor will operate in  
proper rotation regardless of the phase sequence to the unit.  
If, upon start-up, the outdoor fans operate backwards but the  
indoor fan operates in the correct direction, reverse any two  
leads to the main terminal block. All fans will then operate  
in the correct direction.  
38  
Fig. 44 — Modulating Power Exhaust Component Locations; Sizes 034-048  
39  
40  
Fig. 46 — Modulating Power Exhaust Return End Sheet Metal Skin Detail; Sizes 034-048  
Fig. 47 — Modulating Power Exhaust Return End Sheet Metal Skin Detail; Sizes 054-104  
41  
Table 19 — Compressor Loading and Unloading Sequences  
SIZE 034 UNITS  
COOLING  
STAGE  
Lead Circuit  
Lag Circuit  
Active  
Cylinders  
Percent  
Capacity  
Unloader  
U1  
Unloader  
U2  
Comp 1  
Comp 2  
0
1
2
3
4
5
6
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
0
2
0
17  
ON  
OFF  
OFF  
ON  
4
33  
OFF  
ON  
6
50  
8
67  
ON  
OFF  
OFF  
ON  
10  
12  
83  
OFF  
ON  
100  
SIZE 038 UNITS  
COOLING  
STAGE  
Lead Circuit  
Lag Circuit  
Active  
Cylinders  
Percent  
Capacity  
Unloader  
U1  
Unloader  
U2  
Comp 1  
Comp 2  
0
1
2
3
4
5
6
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
0
2
0
14  
ON  
OFF  
OFF  
ON  
4
28  
OFF  
ON  
6
42  
6
72  
ON  
OFF  
OFF  
ON  
8
86  
OFF  
ON  
10  
100  
SIZE 044 UNITS  
COOLING  
STAGE  
Lead Circuit  
Unloader  
Lag Circuit  
Active  
Percent  
Cylinders  
Capacity  
Comp 1  
Comp 2  
U1  
OFF  
ON  
0
1
2
3
4
OFF  
ON  
ON  
ON  
ON  
OFF  
OFF  
OFF  
ON  
0
2
4
6
8
0
25  
OFF  
ON  
50  
75  
OFF  
ON  
100  
SIZE 048 UNITS  
Lag Circuit  
COOLING  
STAGE  
Lead Circuit  
Active  
Cylinders  
Percent  
Capacity  
Unloader  
U1  
Unloader  
U2  
Comp 1  
Comp 2  
0
1
2
3
4
5
6
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
0
2
0
19  
ON  
OFF  
OFF  
ON  
4
38  
OFF  
ON  
6
58  
6
62  
ON  
OFF  
OFF  
ON  
8
81  
OFF  
ON  
10  
100  
42  
Table 19 — Compressor Loading and Unloading Sequences (cont)  
SIZE 054 UNITS  
COOLING  
STAGE  
Lead Circuit  
Lag Circuit  
Comp 2  
OFF  
Active  
Cylinders  
Percent  
Capacity  
Comp 1  
OFF  
ON  
Unloader U1  
OFF  
Unloader U2  
OFF  
0
1
2
3
4
5
0
2
0
20  
ON  
ON  
OFF  
ON  
ON  
OFF  
OFF  
4
40  
ON  
OFF  
OFF  
OFF  
6
60  
ON  
ON  
OFF  
ON  
10  
12  
80  
ON  
OFF  
OFF  
ON  
100  
SIZE 064 UNITS  
COOLING  
STAGE  
Lead Circuit  
Lag Circuit  
Comp 2  
OFF  
Active  
Cylinders  
Percent  
Capacity  
Comp 1  
OFF  
ON  
Unloader U1  
OFF  
Unloader U2  
OFF  
0
1
2
3
4
5
6
0
2
0
17  
ON  
ON  
OFF  
ON  
ON  
OFF  
OFF  
4
33  
ON  
OFF  
OFF  
OFF  
6
50  
ON  
ON  
ON  
ON  
8
67  
ON  
ON  
OFF  
ON  
10  
12  
83  
ON  
OFF  
OFF  
ON  
100  
SIZE 074, 078 UNITS  
COOLING  
STAGE  
Lead Circuit  
Lag Circuit  
Comp 2  
OFF  
Active  
Cylinders  
Percent  
Capacity  
Comp 1  
OFF  
ON  
Unloader U1  
OFF  
Unloader U2  
OFF  
0
1
2
3
4
5
6
0
2
0
14  
ON  
ON  
OFF  
ON  
ON  
OFF  
OFF  
4
29  
ON  
OFF  
OFF  
OFF  
6
43  
ON  
ON  
ON  
ON  
8
71  
ON  
ON  
OFF  
ON  
10  
12  
86  
ON  
OFF  
OFF  
ON  
100  
SIZE 088 UNITS  
COOLING  
STAGE  
Lead Circuit  
Lag Circuit  
Comp 2  
OFF  
Active  
Cylinders  
Percent  
Capacity  
Comp 1  
OFF  
ON  
Unloader U1  
OFF  
Unloader U2  
OFF  
0
1
2
3
4
5
6
0
2
0
16  
ON  
ON  
OFF  
ON  
ON  
OFF  
OFF  
4
33  
ON  
OFF  
OFF  
OFF  
6
50  
ON  
ON  
ON  
ON  
8
66  
ON  
ON  
OFF  
ON  
10  
12  
83  
ON  
OFF  
OFF  
ON  
100  
SIZE 104 UNITS  
Lag Circuit  
COOLING  
STAGE  
Lead Circuit  
Unloader U1  
OFF  
Active  
Percent  
Cylinders  
Capacity  
Comp 1  
OFF  
ON  
Comp 3  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
Comp 2  
OFF  
OFF  
OFF  
ON  
Comp 4  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
0
1
2
3
4
5
6
7
8
0
4
0
20  
ON  
ON  
OFF  
6
30  
ON  
ON  
10  
12  
14  
16  
18  
20  
50  
ON  
OFF  
ON  
60  
ON  
ON  
ON  
70  
ON  
OFF  
ON  
ON  
80  
ON  
ON  
ON  
ON  
90  
ON  
OFF  
ON  
ON  
ON  
100  
43  
Table 21 — Operation Status Codes  
TROUBLESHOOTING  
By using the display module, actual operating conditions  
of the unit are displayed while it is running. The Quick Test  
function allows proper operation of compressors, compres-  
sor unloaders, fans, and other components to be checked while  
unit is stopped. If an operating fault is detected, an alarm is  
generated and an alarm code(s) is displayed. For checking  
specific items, see Table 20.  
CODE  
MEANING  
0 cooling stages active  
0
1
1 cooling stage active  
2
2 cooling stages active  
3 cooling stages active  
Checking Display Codes — To view the digital dis-  
play codes, press the button located to the right of the LED  
display/set point board in the control box. See Table 21 for  
Operational Status Codes. See Table 22 for Diagnostic Codes.  
3
4
4 cooling stages active  
5 cooling stages active  
6 cooling stages active  
7 cooling stages active  
8 cooling stages active  
5
Complete Unit Stoppage — If the unit is off, there  
are several conditions that can cause this situation to occur:  
• Remote ON/OFF circuit in Unoccupied mode.  
• Unit ON/OFF switch moved to OFF position.  
• Programmed schedule at the timeclock.  
• General power failure.  
• Blown fuse in the control power feed.  
• Open control circuit fuse.  
• Operation of the unit blocked by the demand limit  
function.  
6
7
8
Initialization mode (Allow 2 minutes  
for initialization. To initiate Quick Test,  
press the Display button while 20 is displayed.)  
20  
• Unit supply-air temperature (T1) thermistor failure.  
• Supply-air fan is not operating.  
• High duct static pressure.  
21  
Temperature Reset in effect  
Demand Limit in effect  
22  
Single Circuit Stoppage — If a single circuit stops,  
there are several potential causes:  
26  
Morning Warm-Up in effect  
Internal failure detected  
• Open contacts in the compressor high-pressure switch.  
• Low refrigerant pressure.  
30  
• Thermistor failure.  
• Unit supply-air temperature thermistor (T1) failure.  
• Compressor circuit breaker trip.  
• Operation of the circuit blocked by the demand limit  
function.  
88  
Self-diagnostic mode in effect  
Restart Procedure Before attempting to restart the  
machine, check the display for alarm codes to determine the  
cause of the shutdown. If the unit, circuit, or compressor stops  
more than once as a result of a safety device, determine and  
correct the cause before attempting to start the unit again.  
After the cause of the shutdown has been corrected, unit  
restart may be automatic or manual depending upon the fault.  
Table 20 — Controls Troubleshooting  
SYMPTOM(S)  
PROBABLE CAUSE(S)  
SOLUTION(S)  
Controls do not seem  
to be operating.  
Remote on-off function may be  
keeping controls off.  
Check status.  
Evaporator fan does not run.  
1. Circuit breaker open.  
2. Inverter overload (if equipped).  
1. Find cause and reset circuit breaker.  
2. Find cause and reset.  
Compressor does not run.  
1. Circuit breaker is open.  
1. Find cause and reset circuit breaker.  
2. Correct operation.  
2. There is no demand for cooling.  
3. The control is locking out cooling operation.  
3. Check rotating display for alarm codes. Resolve  
alarm cause and reset control by changing to  
standby and back to run mode.  
4. Demand Limit in effect.  
Circuit breaker is open.  
4. Check Demand Limit Settings.  
Condenser fans do not  
turn on.  
Find cause and reset circuit breaker  
Cooling demand exists and  
economizer modulates, but  
compression is not operating.  
Compression cannot be initiated  
until economizer damper is 90% open.  
Correct operation.  
44  
Code 51 is for compressor 1, and Code 55 is for com-  
pressor 2. Codes 52 and 56 are used for compressors 3 and  
4, respectively, on size 104 units.  
The microprocessor has also been programmed to indi-  
cate a compressor failure if CR switch is closed when com-  
pressor is not supposed to be on.  
Diagnostic Codes Diagnostic codes are warnings  
of abnormal or fault conditions, and may cause either one  
circuit or the whole unit to shut down. They are assigned  
code numbers as described below.  
Table 22 contains a description of each diagnostic code  
error and possible cause. Manual reset is accomplished by  
moving the ON/OFF Switch to the OFF position, then back  
to ON.  
The 2-digit LED display is used to display the diagnostic  
codes and the alarm light (located next to display) is ener-  
gized whenever a diagnostic code is tripped. When a prob-  
lem is suspected, always check the display first for diagnos-  
tic information.  
NOTE: Codes 53, 54, 57, 58, 61, 62, 65-69, 73, 74, and 77-80  
are not used on these units.  
If a failure occurs, the following are possible causes:  
High-Pressure Switch Open — The high-pressure switch for  
each compressor is wired in series with 24-v power that en-  
ergizes CR. If high-pressure switch opens during operation,  
CR will stop compressor and this will be detected by micro-  
processor through the feedback contacts.  
Internal Thermostat — The internal thermostat in each 06D  
compressor is also wired in series with 24-v power that en-  
ergizes CR. If thermostat fails or switch opens during op-  
eration of compressor, compressor will shut down and fail-  
ure is detected through feedback contacts (size 034 and 038  
only).  
IMPORTANT: The microprocessor memory and the  
display will be cleared if the power to the microproces-  
sor is shut off. DO NOT attempt to bypass, short, or  
modify the control circuit or electronic boards in any  
way to correct a problem. This could result in a haz-  
ardous operating condition.  
CR Failure — If CR fails with large relay either open or closed,  
microprocessor will detect this, lock compressor off, and in-  
dicate an error.  
Relay Board Failure — If small 24-v relay on the relay board  
fails, microprocessor will detect this through feedback con-  
tacts and indicate an error.  
Processor Board Failure — If hardware that monitors feed-  
back switch fails and processor board fails to energize the  
relay board relay to ON position, an error may be indicated.  
CODES 51, 52, 55, 56: COMPRESSOR FAILURE — If con-  
trol relay (CR) opens while compressor should be operating,  
compressor will stop and microprocessor will energize alarm  
light and display a code of 51 , 52 , 55 or 56 (de-  
pending on compressor) when display button is pushed. The  
compressor will be locked off; to reset, the ON-OFF switch  
must be turned to OFF and then to ON position.  
If lead compressor in a refrigerant circuit is shut down,  
the other compressor in that circuit will also be shut down  
and locked off. Only the error code for the lead compressor  
will be displayed.  
The control does not detect compressor circuit breaker  
failures.  
Wiring Problem — A wiring error or a loose wire may cause  
the feedback circuit to be broken.  
Table 22 — Diagnostic Codes  
DISPLAY  
DESCRIPTION OF FAILURE  
ACTION TAKEN  
BY CONTROL  
RESET  
METHOD  
PROBABLE CAUSE  
51  
55  
52  
56  
Compressor 1 failure  
Circuit 1 shut off  
Manual  
Manual  
Manual  
Manual  
High-pressure switch or high dis-  
charge gas thermostat switch  
trip, compressor ground current  
Ͼ 2.5 amp or compressor board  
relay on when it is not supposed  
to be on. Wiring error between  
electronic control and compres-  
sor protection module.  
Compressor 2 failure  
Compressor 3 failure  
Compressor 4 failure  
Circuit 2 shut off  
Compressor 3 shut off  
Compressor 4 shut off  
59  
60  
Loss-of-charge circuit 1  
Loss-of-charge circuit 2  
Circuit 1 shut off  
Circuit 2 shut off  
Manual  
Manual  
This indicates either a low refrig-  
erant charge, or a loss-of-charge  
switch failure.  
63  
64  
Low oil pressure circuit 1  
Low oil pressure circuit 2  
Circuit 1 shut off  
Circuit 2 shut off  
Manual  
Manual  
Not used; Check jumper on pro-  
cessor board.  
70  
Illegal unit configuration  
Unit will not start  
Manual  
Configuration error (see Note 1).  
71  
72  
75  
Supply-air thermistor failure  
Unit shut off  
Auto.  
Auto.  
Auto.  
Thermistor or resistor failure, wir-  
ing error, or thermistor or resistor  
not connected to the processor  
board.  
Return-air thermistor failure  
Use default value  
Unit shut off  
Circuit 1 saturated condensing thermistor  
76  
Circuit 2 saturated condensing thermistor  
Unit shut off  
Auto.  
81  
Reset temperature thermistor failure  
Stop reset  
Auto.  
82  
83  
84  
85  
86  
87  
Leaving-air set point potentiometer failure  
Economizer potentiometer failure  
Use default value  
Close economizer  
Stop reset  
Stop demand limit  
Close economizer  
Use default value  
Auto.  
Auto.  
Auto.  
Auto.  
Auto.  
Auto.  
Potentiometer improperly con-  
nected, potentiometer setting out  
of range, potentiometer failure or  
wiring error.  
Reset limit set point potentiometer failure  
Demand limit potentiometer failure  
Minimum economizer potentiometer failure  
Warm-up set point potentiometer failure  
NOTES:  
1. Illegal unit configuration caused by missing programmable header or both unloader DIP switches on.  
2. All auto. reset failures that cause the unit to stop will restart when the error has been corrected.  
3. All manual reset errors must be reset by turning the control switch off and then back on.  
4. Valid resistance range for the thermistors is 363,000 to 585 ohms.  
5. Codes 53, 54, 57, 58, 61, 62, 65-69, 73, 74, and 77-80 are not used on these units.  
45  
CODES 59 AND 60: LOW-PRESSURE SWITCH — These  
codes are used to indicate a low-pressure switch failure.  
CODE 82: LEAVING-AIR TEMPERATURE SET POINT  
POTENTIOMETER FAILURE — If leaving-air set point po-  
tentiometer (P1 — located on display board) fails, control  
will use a default value. A failure will cause an error code of  
The processor monitors the low-pressure switch. If the switch  
opens, either by low refrigerant charge, circuit failure, or wir-  
ing error, the circuit is locked off. Code 59 indicates a failure  
of the lead circuit, and as a result, that circuit will be shut  
down. Code 60 indicates a failure of the lag circuit, and as  
a result, that circuit will be shut down. These codes will only  
be displayed when the display button is pressed. To reset the  
circuit, the ON-OFF switch must be turned to OFF, then ON  
position.  
82 to be displayed on display board when display button is  
pushed; alarm light will also be energized. A failure is de-  
termined by establishing a range of −22 F to 70 F as a valid  
range. Anything outside this range will be treated as a fail-  
ure. If setting is outside the −22 F to 70 F range, alarm light  
will be energized and an error code of 82 will be displayed  
when display button is pushed; the control will use a set point  
of 70 F. If set point is between −22 F and 45 F, control will  
use a set point of 45 F and no error code will be indicated.  
If potentiometer returns to normal, control will automati-  
cally reset.  
NOTE: The full range of the potentiometer is not used for  
the cooling set point range of 45 F to 70 F. The full scale  
resistance of the potentiometer is 10 Kohms.  
CODES 63 AND 64: OIL PRESSURE SWITCH — These  
codes are used to indicate an oil pressure switch failure. Since  
the units do not have oil pressure switches, these codes are  
not used. The terminals on the processor board must be jum-  
pered together or an error will occur. If these errors occur,  
check jumper between J2-1 and J2-2 for a code 63, or be-  
tween J2-3 and J2-4 for a code 64 to be sure jumper is prop-  
erly connected. To reset the circuit, the ON-OFF switch must  
be turned to OFF and then to ON position.  
If a failure occurs, one of the following is a probable cause:  
Incorrect Potentiometer Setting — Apotentiometer turned fully  
clockwise or counterclockwise is outside the valid range and  
will cause a failure.  
Faulty Wiring — If wiring is incorrect between potentiom-  
eter and processor board or display board, a failure will  
result.  
CODE 70: ILLEGAL UNIT CONFIGURATION — If the  
unit configuration header is not installed and properly con-  
figured, and/or if DIP switches are not properly set, unit will  
not start, and an error code of 70 will be indicated on display  
board when display button is pushed. Check the header and  
DIP switch settings.  
CODES 71 TO 76: THERMISTOR/RESISTOR FAILURE  
— If measured temperature of a thermistor is less than  
−60 F (363,000 ohms) or greater than 180 F (585 ohms), the  
appropriate sensor error code (Table 22) will be displayed  
when the display button is pushed. The unit will be shut down.  
Thermistor failures will automatically reset once the error  
has been corrected. If a failure occurs, the following are pos-  
sible causes:  
Potentiometer Failure — If potentiometer is shorted or open,  
a failure will result.  
CODE 83: ECONOMIZER FEEDBACK POTENTIOM-  
ETER FAILURE — If potentiometer on economizer motor  
(P2) fails, control will use a default value of 0% and econo-  
mizer outdoor-air dampers will close. The failure will en-  
83  
ergize alarm light and cause an error code of  
to be dis-  
played when display button is pushed. This potentiometer is  
a 5 to 15 Kohm potentiometer. If potentiometer returns to  
normal, control will automatically reset. If a failure occurs,  
one of the following is the probable cause.  
Faulty Wiring — If the wiring between processor board and  
potentiometer is wrong, this will cause a failure.  
Thermistor or Resistor Failure — A shorted or open ther-  
mistor or resistor will cause the failure.  
Wiring Failure — If a wiring error exists that causes a shorted  
or open circuit, this will cause a failure.  
Processor Board Failure — If circuitry on processor board  
fails, this could cause an error.  
The codes are designated as follows:  
Potentiometer Failure — If potentiometer is shorted or open,  
this will cause a failure.  
Code 71 Supply-Air Thermistor Failure  
Code 72 Return-Air Thermistor Failure  
Code 73 Not used  
Code 74 Not used  
Code 75 Circuit 1 Saturated Condensing Thermistor  
Code 76 Circuit 2 Saturated Condensing Thermistor  
Economizer Damper Stuck — The control has been pro-  
grammed to indicate an error if potentiometer travel is less  
than 10% of the full range. This would happen if dampers or  
damper linkage were hung up and could not move  
properly.  
CODE 84: RESET LIMIT POTENTIOMETER FAILURE  
— This code is applicable only if reset is being used. If reset  
is being used, DIP switch 2 must be in the ON position. This  
potentiometer (P3) is located on the accessory board. If po-  
tentiometer setting is less than 0° F or greater than 80 F,  
CODE 81: RESET THERMISTOR OR POTENTIOM-  
ETER FAILURE — This is a unique code since the reset  
temperature potentiometer (P7) is in series with the space  
temperature thermistor (T10). If either one of these compo-  
nents fail, reset will be terminated. This error will automati-  
cally reset once the situation is corrected. If an error is  
detected, the most probable cause is one of the following:  
• Thermistor Failure — A shorted or open thermistor will  
cause the failure.  
• Potentiometer Failure — If the potentiometer is outside of  
the valid range (40 to 90 F), a failure will result.  
• Wiring Problem — If the circuit is open, a failure will be  
detected.  
• Processor Board Failure — If the processor board fails (hard-  
ware), an alarm will be detected.  
84  
alarm light will be energized, a diagnostic code of  
will  
be displayed if display button is pushed, and reset will be  
terminated. The full-scale resistance of potentiometer is  
10 Kohms, but when installed on the accessory board in par-  
allel with the other 2 potentiometers, measured resistance  
will be 3.3 Kohms. This failure will automatically reset once  
potentiometer returns to normal. If a failure occurs, one of  
the following is the probable cause:  
DIP Switch Problem — DIP switch 2 is in the ON position  
and the accessory board is not installed (accessory board is  
standard on these units so it should always be on the unit).  
46  
potentiometer (P6) is located on the accessory board. If po-  
tentiometer is set at less than 0° F or more than 95 F, alarm  
Incorrect Potentiometer Setting — Apotentiometer turned fully  
clockwise or counterclockwise is outside the valid range and  
will result in a failure.  
87  
light will be energized, a diagnostic code of  
will ap-  
Faulty Wiring — If the wiring between the potentiometer and  
the processor board is incorrect, a failure will result.  
Potentiometer Failure — If potentiometer is shorted or open,  
a failure will occur.  
CODE 85: DEMAND LIMIT POTENTIOMETER (P4) FAIL-  
URE — Used only if demand limit is being used. If demand  
limit is used, DIP switch 5 must be in the ON position.  
Two types of demand limit are available: a field-supplied  
and installed single-step control consisting of a 10 Kohm,  
3-wire linear potentiometer and an accessory 2-step control  
are available from Carrier. The single-step control has a single  
potentiometer while 2-step control has 2 potentiometers  
(mounted on the demand limit board, see Fig. 26).  
pear on the display when display button is pushed, and con-  
trol will use a default value of 40 F. If setting is between  
0° F and 40 F, control will use a value of 40 F but no di-  
agnostic code will be displayed; if setting is between 80 F  
and 95 F, control will use a value of 80 F but no diagnostic  
code will be displayed.  
The potentiometer full-scale resistance is 10 Kohm, but  
when wired in parallel with other potentiometers on the ac-  
cessory board, measured resistance is 3.3 Kohm.  
The failure will automatically reset once potentiometer re-  
turns to normal. If a failure occurs, one of the following is  
the probable cause:  
DIP Switch 4 — If this switch is in the ON position and the  
accessory board is not installed (accessory board is standard  
on these units, so it should always be on the unit).  
Incorrect Potentiometer Setting — If potentiometer is turned  
fully clockwise or counterclockwise, potentiometer will be  
out of the allowable range, resulting in an error.  
Faulty Wiring — If the wiring between the potentiometer and  
the processor board is incorrect, an error will occur.  
Potentiometer Failure — If potentiometer is shorted or open,  
potentiometer will be out of range, resulting in an error.  
For both types of demand limit, the control uses only 80%  
of the total potentiometer resistance. If resistance of poten-  
tiometer is less than 10% or greater than 90%, alarm light  
will be energized, a diagnostic code of 85 will be displayed  
when the display button is pushed, and demand limit will be  
terminated. If a failure occurs, it is probably due to one of  
the following:  
Potentiometer Failure — If a potentiometer is shorted or open,  
a failure will occur.  
Incorrect Potentiometer Setting — Apotentiometer turned fully  
clockwise or counterclockwise will put potentiometer out of  
range resulting in an error.  
Faulty Wiring — If wiring between the potentiometer and  
the processor board is incorrect, an error will occur.  
DIP Switch 5 — If DIP switch 5 is in the ON position and  
potentiometer is not installed, an error will occur.  
CODE 86: MINIMUM POSITION ECONOMIZER PO-  
TENTIOMETER FAILURE — If potentiometer P5 (on ac-  
cessory board) setting is less than 0% or greater than 100%,  
Thermistor Troubleshooting — The VAV control sys-  
tem uses thermistors to measure temperatures of the enter-  
ing and supply air, as well as the saturated condensing tem-  
peratures of the refrigerant circuits. The resistance versus  
temperature and electrical characteristics for all thermistors  
in the system are identical. To obtain an accurate reading, a  
high-impedance meter (such as a digital meter) must be used.  
Thermistors in the VAV control system have a 5 vdc sig-  
nal applied across them any time the unit control circuit  
is energized. The voltage drop across the thermistor is di-  
rectly proportional to the temperature and resistance of the  
thermistor.  
alarm light will be energized, a code of 86 will be dis-  
To determine temperatures at the various thermistor lo-  
cations, disconnect the thermistor from the processor board  
and measure the resistance across the appropriate thermistor  
using a high-quality digital ohmmeter. Use the resistance read-  
ing to determine the thermistor temperature.  
played when display button is pushed and economizer out-  
door air dampers will move to the fully closed position.  
The potentiometer full-scale resistance is 10 Kohm, but  
when installed in parallel with the other 2 potentiometers on  
the accessory board, measured resistance will be 3.3 Kohm.  
The microprocessor has been programmed to check the  
operation of the thermistors. If the measured temperature is  
outside of the range of −24 to 225 F or 98,010 to 282 ohms,  
then it will be treated as a sensor failure and a diagnostic  
code will be displayed. See Table 17 for sensor temperatures  
versus resistance drop. It is also possible to check the op-  
eration of the thermistors using the quick test routine.  
If a thermistor has failed or the wire is damaged, replace  
the complete assembly. Do not attempt to spice the wires or  
repair the assembly.  
This failure will automatically reset when potentiometer  
returns to normal.  
If a failure occurs, one of the following is the probable  
cause:  
DIP Switch 3 — If this switch is in the ON position and the  
accessory board is not installed (accessory board is standard  
on these units, so it should always be on the unit).  
Incorrect Potentiometer Setting — If potentiometer is turned  
fully clockwise or counterclockwise, potentiometer will be  
out of the allowable range, and an error will result.  
Faulty Wiring — If wiring between the potentiometer and  
the processor board is incorrect, an error will occur.  
Potentiometer Failure — If potentiometer is shorted or open,  
potentiometer will be out of range and an error will result.  
Electronic Controls Checkout — The following will  
help determine whether a processor board, a relay board, dis-  
play set point board, accessory board, or 2-step demand limit  
module is faulty.  
Before checking out any board, do the following:  
CODE 87: WARM-UP TEMPERATURE SET POINT FAIL-  
URE Applicable only if morning warm-up is used. Whether  
or not unit is equipped with electric resistance heaters, use  
of the morning warm-up function is recommended if the unit  
is shut down at night or over weekends. In this application,  
cooling will remain off and the outdoor-air damper will stay  
closed until heat load from the occupied space elevates return-  
air temperature to the warm-up set point. If warm-up func-  
tion is used, DIP switch 4 must be in the ON position. The  
1. At initial start-up, enter the Quick Test mode. This test  
will determine if all components are connected and op-  
erating properly.  
2. If system has been operating and a malfunction occurs,  
check display for diagnostic codes. Use diagnostic chart  
located on inner panel of access door to control box sec-  
tion of unit; this chart will help determine probable cause  
of failure.  
47  
These 2 steps will help determine if a component other  
than a board is at fault or if the problem is external to control  
circuit.  
A volt-ohmmeter will be needed to troubleshoot boards. A  
digital meter is preferred but a Simpson 260 or equivalent  
will work.  
Step 3 — Check Voltage Tolerance Circuitry  
1. Turn power to OFF position.  
2. Negative test probe on TP18 and system in Quick Test  
mode.  
3. Check voltage TP18 to TP9.  
4. If voltage is greater than ϩ1 vdc, recheck transformer  
input voltage.  
5. If transformer is okay, replace processor board.  
6. Turn power to ON position.  
Step 4 — Check Processor Reset Line  
1. Turn power to OFF position.  
To prevent damage to solid-state electronic components  
on boards, meter probes should only be placed on ter-  
minals and test points listed in following sections. Do  
not short the electrical components, and use extreme care  
while working on the processor board.  
2. Negative probe on TP18.  
3. Check voltage TP18 to TP11.  
PROCESSOR BOARD CHECKOUT — Refer to Fig. 48  
and 49 for location of terminal pins and test points.  
4. If voltage is greater than ϩ3 vdc, reset power and  
recheck.  
Step 1 — Check Transformer Input to the Board — Connector  
J4 is used to connect the control transformer to the processor  
board.  
1. Set the volt-ohmmeter to ac voltage with a range setting  
of approximately 30 v.  
5. If voltage is still incorrect, replace processor board.  
6. Turn power to ON position.  
2. Turn control switch to ON position.  
3. Check voltage at following terminals on pin terminal con-  
nector J4:  
TERMINALS  
VOLTAGE (AC)  
1 to 2  
4 to 6  
5 to 6  
5 to 4  
15.3 to 20.9  
16.2 to 22.0  
8.1 to 11.0  
8.1 to 11.0  
4. If voltage is not within range, check primary side.  
115-v transformer — 104 to 127 vac  
230-v transformer — 207 to 254 vac  
5. If primary voltage is not correct, check system fuse, trans-  
former, ON-OFF switch, and wiring. If these are okay,  
contact power company.  
6. If primary voltage is correct, but secondary voltage  
(24 v ± 10%) is incorrect, replace transformer.  
LEGEND  
J
TP  
Pin Terminal Strip  
Test Pin  
Fig. 48 — Processor Board Test Points  
7. Turn control switch to OFF position.  
Step 2 — Check Processor Board Power Supply  
1. Set meter to approximately 20 vdc.  
2. Turn power to OFF position.  
J6  
J5  
R9  
C9  
R10  
C10  
R11  
R12  
C12  
R13  
C13  
C11  
3. Connect negative lead to TP18.  
4. Turn power switch to ON position and press display but-  
ton to enter Quick Test mode.  
5. Check voltage between TP18 and each of the following  
test pins:  
CR9  
CR10  
CR11  
CR12  
CR13  
TEST PIN  
VOLTAGE (DC)  
TP3  
TP4  
ϩ10  
ϩ12  
ϩ5  
C1  
C2  
C3  
C4  
C5  
C6  
C7  
C8  
TP6  
TP10  
TP14  
TP15  
TP7  
ϩ5  
ϩ12  
ϩ12  
−5*  
CR1  
CR2  
CR3  
CR4  
CR5  
C19  
CR6  
CR7  
E3  
CR8  
*If not using a digital meter, leads must be reversed.  
6. If voltage is incorrect, replace processor board.  
7. Turn power to ON position.  
K1  
LEGEND  
K2  
K3  
CR  
J
K
Control Relay  
Pin Terminal Strip  
Relay  
Fig. 49 — Relay Board Test Points  
48  
Step 5 — Check Relay Board Outputs from the Processor  
Board — This step involves checking the output signals from  
relays K1-K3 on the relay board.  
5. Place the other lead on terminals shown in table below,  
and check voltage at pin terminals on pin terminal con-  
nector J10 (see Fig. 51 for pin terminal connector J10  
details):  
1. Turn power to OFF position.  
2. Connect negative test probe to TP19 (meter still set to  
dc).  
3. Turn switch to ON position and enter Quick Test mode.  
4. Connect positive test probe to terminal 14 on pin termi-  
nal connector J9, and check voltage from TP19 to ter-  
minal 14 on pin terminal connector J9.  
PIN TERMINAL  
VOLTAGE (DC)  
17  
18  
20*  
22*  
24  
5
5
2.5  
2.5  
5
*Voltage reading is dependent on the meter’s impedance. Readings  
may vary with different meters.  
5. If not ϩ12 ± 1 vdc, replace processor board.  
6. If voltage is not correct, replace processor board.  
Step 7 — Potentiometer Connection Checkout.  
1. Turn power to OFF position.  
6. Turn switch to OFF position.  
7. Remove negative test probe from TP19. Connect positive  
test probe to TP15.  
8. Turn switch to ON position and go into Quick Test mode.  
2. Remove plug connection from pin terminal strip J3.  
3. Connect negative meter lead to terminal 2 of J3.  
4. Turn switch to ON position and go into Quick Test mode.  
9. Place negative lead on terminals shown in Table 23, and  
check voltage between TP15 and terminals shown in  
Table 23 on pin terminal connector J9. See Fig. 50 for J9  
details.  
5. Place the other lead on terminals shown in table below,  
and check voltage at pin terminals on terminal connector  
J3:  
PIN TERMINAL  
VOLTAGE (DC)  
1*  
3
2.5  
5
6
5
8*  
2.5  
2.5  
5
2.5  
2.5  
10*  
12  
13*  
14*  
*Voltage reading is dependent on the meter’s impedance. Readings  
may vary with different meters.  
6. If voltage is not correct, replace processor board.  
Step 8 − Thermistor Input Connector Checkout  
1. Turn power to OFF position.  
2. Remove the thermistor connections from pin terminal con-  
nector J1, and mark them for later replacement.  
Fig. 50 — Relay Board Pin Terminal Connector (J9)  
Table 23 — Voltage Reading  
3. Connect the negative test lead to test pin TP18.  
4. Turn power to ON position, and enter the Quick Test  
routine.  
J9 PIN NUMBERS  
QUICK TEST  
STEP NO.  
1
2
3
4
5
6
7
8
9
10 11 12 13  
1.-2.3.  
2.4.  
2.5.  
2.6.  
2.7.  
2.8.  
2.9.  
3.0.  
3.1.  
3.2.  
3.3.  
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
12  
12  
12  
12  
12  
5. Place the other lead on terminals shown in Table 24, and  
check the voltages.  
6. If voltages are incorrect (per Table 24), replace processor  
board.  
7. Turn power to OFF position, and replace the thermistor  
connections removed in Step 2.  
8. Turn power to ON position.  
0
0
0
0
0
0
0
0
0
0
12  
0
0
0
0
0
0
0
0
0
0
12  
12  
12  
12  
12  
12  
12  
12  
12  
0
0
0
0
0
0
0
12  
0
0
0
0
0
0
0
12  
0
0
0
0
0
0
0
12 12  
12  
0
0
0
0
0
0
0
0
0
0
0
0
12  
12  
12  
12  
12  
12  
0
0
0
0
0
0
0
12  
0
0
0
0
0
0
0
0
12  
0
0
0
0
0
0
12  
0
0
NOTES:  
1. Pins shown in boldface type will only be energized for 10 sec-  
onds. All other pins will be energized continuously while at the proper  
quick test step. The control will only stay in the Quick Test routine  
for 10 minutes unless the display button is pressed.  
2. Acceptable range for the voltage reading:  
0 v — 0 to 4 v  
12 v — 11 to 13 v  
3. If any of these voltages are not measured, replace the processor  
board.  
Step 6 — Display Board Connection Checkout  
1. Turn power to OFF position.  
2. Disconnect the ribbon cable.  
3. Connect negative lead of meter to TP18.  
4. Turn power to ON position and go into Quick Test mode.  
Fig. 51 — Display Board Pin Terminal Connector (J10)  
49  
Table 24 — Pin Terminal Connector J1 Voltages  
The following procedure can be used to check out the op-  
eration of the relays. To do this, turn the control ON/OFF  
switch to the OFF position, and remove the wiring connec-  
tors connected to pin terminal connectors J5 and J6. Set the  
meter for resistance. If the contacts do not close at the re-  
quired quick test step, check the relay outputs from the pro-  
cessor board.  
Relay Board Checkout (Fig. 5)  
Step 1 — Low-voltage relay resistance check.  
1. Turn switch to OFF position.  
2. Remove plug connection from terminal strip J6.  
3. Set meter to measure resistance. Connect negative test  
lead to both terminals 11 and 12 of J6.  
4. Turn switch to ON position and go into quick test mode.  
5. Place other meter lead on terminals shown in Table 26  
and check resistances at each quick test step.  
PIN  
TERMINAL  
VOLTAGE  
(vdc ± 0.25 v)  
1
0
5
0
5
0
5
0
5
0
5
0
5
0
5
0
5
0
5
2
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
6. If these resistances are not correct and relay board out-  
puts from processor board have been checked out, re-  
place relay board.  
Step 2 — High-voltage relay resistance check.  
1. Turn switch to OFF position.  
2. Remove plug connection from terminal connector J5.  
3. Connect negative test lead to terminal 8.  
4. Check the resistance between terminals 8 and 5 before  
entering Quick Test mode. The resistance should be  
infinity.  
5. Turn switch to ON position and go into Quick Test mode.  
6. Place other meter lead on terminals shown in Table 27  
and check resistance at each quick test step.  
7. If these resistances are not correct and relay board out-  
puts from processor board have been checked per Pro-  
cessor Board Checkout section on page 48, replace relay  
board.  
Step 9 − Thermistor Input Connector Checkout  
1. Turn power to OFF position.  
2. Disconnect all plugs for pin terminal connector J2 and  
mark them for later replacement.  
3. Connect a negative test lead to test pin TP18.  
4. Turn power to ON position, and enter the Quick Test  
routine.  
5. Place the other lead on terminals shown in Table 25, and  
check the voltages.  
6. If voltages are incorrect (per Table 25), replace processor  
board.  
7. Turn power to OFF position, and replace the plugs re-  
moved in Step 2.  
8. Turn power to ON position.  
Table 25 — Pin Terminal Connector J2 Voltages  
DISPLAY BOARD CHECKOUT  
Step 1 — Check the Output Voltage from Processor Board  
to the Relay Board — Refer to Step 6 — Display Board Con-  
nection Checkout section on page 49.  
PIN  
VOLTAGE  
TERMINAL  
(vdc ± 0.25 v)  
1
0
5
0
5
0
5
0
5
0
5
5
5
5
5
5
5
5
5
5
2
Table 26 — Terminal Strip J6 Connection  
Resistance Reading  
3
4
7
8
J6 PIN NUMBERS  
QUICK TEST  
STEP NO.  
9
1
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
0
2
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
0
3
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
0
4
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
5
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
0
6
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
0
7
ϱ
0
8
ϱ
ϱ
0
10  
13  
14  
15  
17  
18  
19  
20  
21  
22  
23  
24  
1. to 2.3.  
2.4.  
2.5.  
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
2.6.  
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
ϱ
2.7.  
2.8.  
2.9.  
3.0.  
ϱ
ϱ
ϱ
ϱ
3.1.  
ϱ
ϱ
ϱ
3.2.  
ϱ
ϱ
If Steps 1 through 9 have been competed and the unit still  
will not function properly, replace the processor board.  
3.3.  
ϱ
LEGEND  
RELAY BOARD TROUBLESHOOTING — The relay board  
contains 13 electromechanical relays. The small relays are  
24 vac, and the large relays are 115 vac. These relays are  
controlled by the processor through the ribbon cable at-  
tached to the relay board.  
ϱ
Infinity  
NOTE: Pins shown in boldface type will be energized for only  
10 seconds. All other pins will be energized continuously while at the  
proper quick test step. The control will remain in the Quick Test mode  
for only 10 minutes unless the display button is pressed.  
50  
Table 27 — Terminal Strip J5 Connector  
Resistance Reading  
IMPORTANT: Be careful to avoid damaging the con-  
nector or the processor board when taking the voltage  
readings.  
J5 PIN NUMBERS  
QUICK TEST  
STEP NO.  
1
ϱ
0
0
0
0
2
3
ϱ
ϱ
0
4
5
0
0
0
0
0
Test under the following conditions:  
• No power to IN1 or IN2  
Terminal 1 to 2 should read 4.5 vdc ±0.1 v  
Terminal 2 to 3 should read 5.0 vdc ±0.1 v  
• Power to IN2 or to both IN1 and IN2, and P2 set at 24%  
Terminal 1 to 2 should read 1.5 vdc ± 0.1 v  
1. to 2.5.  
2.6  
ϱ
0
ϱ
ϱ
ϱ
0
2.7.  
ϱ
ϱ
ϱ
2.8.  
ϱ
ϱ
2.9. to 3.3.  
ϱ
LEGEND  
NOTE: Voltage should vary between 0.5 vdc and 2.5 vdc  
as the setting of P2 is varied between 0% and 49%.  
ϱ
Infinity  
Terminal 2 to 3 should read 5.0 vdc ± 0.1 v  
• Power to IN1 only and P1 set at 50%  
Terminal 1 to 2 should read 2.5 vdc ± 0.1 v  
Terminal 2 to 3 should read 5.0 vdc ± 0.1 v  
NOTE: Voltage should vary between 0.5 vdc and 2.5 vdc  
as the setting of P2 is varied between 50% and 100%.  
Step 2 — Check the Display LEDs  
1. Enter Quick Test mode.  
2. If 88 is not displayed, replace display board.  
Step 3 — Check Set Point Potentiometer — Advance the dis-  
play to quick test step 1.9. to determine if this potentiometer  
is set and connected properly.  
Step 4 — Check Display Switch — Press switch. If switch  
does not click, it is faulty and the display will be energized  
continuously. The switch is an integral part of display board  
and cannot be replaced separately.  
NOTE: If the voltages listed in these 3 tests are not obtained  
during testing, the DLCM board must be replaced.  
Enthalpy Sensor Checkout — To test operation of  
enthalpy sensor, see Table 28.  
Table 28 — Enthalpy Sensor Checkout  
ACCESSORY BOARD CHECKOUT — The accessory board  
can be completely checked using quick test steps 2.0., 2.2.,  
and 2.3. It can also be checked out as follows:  
TEST  
EXPECTED RESULT  
AND RESPONSE  
Outdoor-air sensor:  
1. Remove the accessory board connector from the proces-  
sor board and connect an ohmmeter to terminals 3 and 4  
on the connector. Numbers are marked on the connector.  
See Fig. 15.  
2. Set the meter to 10,000 ohms. The resistance value ob-  
tained should be 3,333 ohms. Adjust the potentiometers  
and the resistance value should not change.  
3. Connect the ohmmeter to terminals 3 and 6. As the reset  
limit potentiometer is turned clockwise, resistance should  
increase from 0 to approximately 3,400 ohms.  
4. Connect the ohmmeter to terminals 3 and 5. As the econo-  
mizer minimum position potentiometer is turned clock-  
wise, resistance should increase from 0 to approximately  
3,400 ohms.  
Enthalpy sensor + terminal  
should be connected to +  
Milliammeter reading should be  
between 3 and 24 mA if sensor  
terminal on motor. Connect the is operating correctly. If reading  
positive terminal of a DC  
is 0 mA, the sensor is either  
milliammeter to the S terminal wired backwards or is defective.  
of the sensor and the negative  
terminal of the meter to SO  
terminal of the enthalpy board.  
Indoor-air sensor:  
Enthalpy sensor + terminal  
should be connected to +  
terminal on motor. Connect the is 0 mA, the sensor is either  
positive terminal of a DC  
milliammeter to the S terminal  
of the sensor and the negative  
terminal of the meter to SR  
terminal of the enthalpy board.  
Milliammeter reading should be  
between 3 and 24 mA if sensor  
is operating correctly. If reading  
wired backwards or is defective.  
5. Connect the ohmmeter to terminals 3 and 2. As the warm-up  
set point potentiometer is turned clockwise, resistance should  
increase from 0 to approximately 3,400 ohms.  
If any of the Steps 1 through 5 result in any other ohm  
reading, replace the board; it cannot be serviced.  
TWO-STEP DEMAND LIMIT CONTROL MODULE  
(DLCM) TROUBLESHOOTING — If a problem is  
suspected in the DLCM board, use the following test  
procedure:  
The board can only be checked when it is connected to  
the processor and the processor is energized so that the DLCM  
is supplied with 5 vdc power. The terminals referenced are  
shown in Fig. 16. Potentiometers P1 and P2 refer to the DLCM  
potentiometers.  
51  
Economizer Motor — All control of the motor (i.e.,  
enthalpy changeover, minimum position control and mixed  
air control) is accomplished from the main unit microproces-  
sor through a relay board. Service and installation instruc-  
tions for the unit should be consulted to verify proper op-  
eration of these controls. The economizer motor may be checked  
out separately. See Fig. 52 for VAV economizer motor con-  
nection information.  
Variable Frequency Drive  
Factory-installed optional VFD is located near the sup-  
ply fan and motor. During any service work or pro-  
gramming at the VFD, operation of the fan and motor  
is not desirable. Either disable the supply fan or install  
an accessory VFD remote display.  
Motor Test  
NOTE: The VFDs (part no. TOSVERT130-E3) are specially  
modified for use on Carrier equipment. Some specifications  
and control configuration defaults for Carrier applications  
will differ from the VFD manufacturer manual included in  
the packet. See Table 29 for listing of Carrier-specific de-  
fault values.  
Apply 24 volt AC power to terminals T1 and T2 of  
motor. Connections to motor terminals 2 and 3 must be  
disconnected  
A Motor Test  
A Expected Result and Response  
Jumper 1 to  
2 at motor  
Motor drives open; if not,  
replace motor.  
STANDARD TRANSDUCER CONTROL — The VFD moni-  
tors and controls duct pressure (DP) via a differential pres-  
sure transducer. The pressure transducer is located in the  
auxiliary control box (034-048 units) or in the supply fan  
compartment (see Fig. 34). The pressure transducer’s low  
pressure reference port is connected to the outside of the unit  
cabinet by a factory-installed tubing section. The pressure  
transducer’s high pressure reference point must be field-  
connected to the duct pressure pick-up (field-supplied and  
installed in the supply duct).  
B Motor Test  
B Expected Result and Response  
Jumper 1 to  
3 at motor  
Motor drives closed; if not,  
replace motor.  
The DP transducer monitors the static pressure in the sup-  
ply duct and provides a 4 to 20 mA signal directly to the  
VFD. (Refer to Table 13 for transducer output signal (mA)  
for actual duct static pressure.) The internal logic of the VFD  
compares this signal representing actual duct pressure to the  
user-configured DP set point. The VFD automatically ad-  
justs its output to the supply fan motor to maintain the de-  
sired DP set point. When operating with the factory-standard  
DP transducer, the internal PID logic of the VFD is enabled.  
LIMIT SWITCHES  
CAPACITOR  
3
EXTERNAL SIGNAL CONTROL — If the VFD is to be  
controlled by an external control system other than the fac-  
tory supplied pressure transducer, the internal PID logic func-  
tion of the VFD must be disabled. To disable the PID  
control:  
1. Disconnect all power to the unit and the VFD.  
2. Install a jumper across S2-CC (see Fig. 53 and 54 for  
VFD terminal board connections).  
CW  
ECONOMIZER  
MOTOR  
WINDING  
(OPEN)  
2
CCW  
WINDING  
(CLOSE)  
T1  
T2  
1
BRAKE  
WINDING  
1
3. Remove factory-supplied cable attached to IV and CC.  
1
2
3
4. Remove other end of the same cable from the pressure  
sensor.  
5. Connect field supplied speed reference (4 to 20mA) across  
terminals IV-CC.  
6. Disable the supply fan motor operation.  
7. Reconnect power to the unit and VFD.  
CW  
FEEDBACK  
POTENTIOMETER  
8. Reprogram the VFD to accept an external reference (in  
the Utility parameters group [Gr.Ut], set parameter item  
Fnod [no.312] = 4).  
BLU  
RED  
YEL  
9. Enable supply fan motor and return power to the unit.  
AUX. SWITCH  
SUPPLY FAN MOTOR OVERLOAD PROTECTION — The  
VFD provides operating overload protection for the supply  
fan motor. The factory has programmed the VFD overload  
function to match the factory-installed motor (motor size and  
efficiency). If the supply fan motor is changed from the origi-  
nal factory selection, the overload value may need to be changed  
by the service person. Contact your local Carrier represen-  
tative for assistance in determining the proper overload  
setting.  
LEGEND  
Counterclockwise  
Clockwise  
CCW  
CW  
Fig. 52 — Damper Motor Connection Diagram (VAV)  
NOTE: Variable frequency drive size is matched to factory-  
installed motor size. Do not increase motor size without also  
changing to equivalent VFD size.  
52  
Table 29 — Carrier Default Program Parameter Values  
PARAMETER GROUP  
PARAMETER  
ACC1  
DEC1  
UL  
DEFAULT VALUE  
60.0 Sec  
60.0 Sec  
60.0 Hz  
LL  
10.0 Hz*  
Luln  
P3  
1
20%  
F-P3  
P4  
0.0 Hz  
SEtP  
(Setup)  
100%  
F-P4  
tHr1  
StC1  
StL1  
OLN  
tYP  
60 Hz  
See Table 31  
0
110%  
1
5*  
FH  
60 Hz  
Gr.F  
(Fundamental)  
Pt  
2
FbP1  
Fbln  
GP  
1*  
2
.30  
Gl  
2 sec  
GA  
0
Gr.Fb  
(Feedback)  
GFS  
P1LL  
PuL  
80  
10  
1
PuUl  
PuLL  
Fsor  
Sr.n  
10  
10  
60 Hz  
Gr.SF  
(Frequency Settings)  
1* (054-104 only)  
0* (054-104 only)  
SrN1  
Gr.Pn  
(Panel Control)  
Fr  
0*  
1t  
1
1t0  
0
1t1  
56  
Gr.St  
(Terminal Selection)  
1t2  
13  
1t3  
3
1t4  
10  
UuC  
UuCt  
ArSt  
Cnod  
bLSF  
Fnod  
bLPn  
1*  
Gr.Pr  
2
(Protection)  
3
1*  
1* (054-104 only)  
Gr.Ut  
(Utility)  
2*  
1*  
*These settings differ from the Toshiba defaults and are required for Carrier applications.  
NOTE: To restore original factory settings, change tYP to 6 in Setup mode (SetP). This restores the VFD original factory settings.  
53  
If using the VFD display panel, disconnect all power  
to the unit and the VFD before entering unit, or use  
the accessory remote display module. Disable supply fan  
and motor operation before accessing VFD-mounted dis-  
play module.  
RR  
SI S2  
S4  
RCH  
P24  
LOW LOW  
RES  
F
R
S3  
P24  
ST  
RX  
FLB  
FLA  
AM CC CC  
PP  
IV FP  
FM  
FLC  
When power is first supplied to the VFD, the display au-  
tomatically starts with the frequency monitor function of its  
standard monitor mode. In the frequency monitor function,  
the output frequency is displayed. Push the S/P/M (Setup/  
Program/Monitor) key to switch to the Mode Selection menu.  
Push the S/P/M key again to toggle the display back to the  
standard monitor mode.  
4-20mA  
Fig. 53 — Variable Frequency Drive Terminal Block  
(Size 034-048 Units)  
From the Mode Selection menu, the service person can  
view all of the monitored status variables, including up to  
four user-selected variables and any trip history in the memory.  
Refer to the separate VFD Operation Manual for detailed  
instructions on accessing diagnostic information, initiating  
troubleshooting, and clearing any trip history.  
RCH  
RES  
F
R
S3  
P24  
LOW LOW  
RR  
SI S2  
S4  
P24  
ST  
RX  
FLB  
FLA  
AM CC CC  
PP  
IV FP  
FM  
FLC  
Restoring Factory VFD Defaults — The original  
factory configuration values are saved in the memory of the  
VFD and can be restored by the service person if required.  
There are two types of saved file data: Carrier-factory set-  
tings (factory programmed settings made to the VFD which  
apply specifically to the unit it is installed on) and standard  
defaults for general Carrier unit use.  
4-20mA  
Fig. 54 — Variable Frequency Drive Terminal Block  
(Size 054-104 Units)  
The Carrier-factory settings are maintained as user set-  
tings. These can be restored by entering the Setup mode (in  
the S/P/M menu) and setting parameter tYP = 6 on the keypad/  
display. This will recall the specific factory defaults for this  
unit.  
Occasionally it may be necessary to restore the VFD de-  
faults to the general Carrier use values. These are stored in  
an OPTION ROM (read-only memory chip). However, some  
variables may need to be manually changed to match the  
specific unit’s factory default settings. To recall the general  
Carrier defaults, enter the Setup mode and set parameter  
tYP = 3. Refer to Table 30 for items requiring manual  
adjustment.  
VFD Operation — When troubleshooting the VFD, check  
first that all required conditions for VFD operation are  
satisfied.  
For the VFD to run, the following conditions must be met  
at the VFD:  
1. Drive enable jumper is installed from terminals CC-ST  
(factory supplied) (see Fig. 53 and 54).  
2. Proper rotation jumper is installed at terminals R-CC (re-  
verse rotation, factory supplied) or terminals F-CC (for-  
ward rotation, factory supplied).  
Table 30 — Required User Adjusted Defaults  
SIZES  
All  
ITEM  
Motor overload settings (see Table 31)  
UNIT SIZES  
034-048  
ROTATION  
Reverse  
Forward  
Forward  
JUMPER  
R-CC  
1. Check jumper CC-F  
2. Gr.UT/bLSF = 1  
054-074  
F-CC  
054-104  
3. Gr.SF/Sr.n = 1  
4. Gr.SF/SrN1 = 0  
5. SEtP/tYP = 5 (Save User Settings)  
078-104  
F-CC  
3. Emergency stop jumper is installed from terminals S4-CC  
(factory supplied).  
4. A 4 to 20 mA signal is applied across terminals IV-C (from  
pressure transducer, factory supplied).  
5. DIP switch SW1 (located on the VFD’s printed circuit  
control panel) must be set to ‘‘I’’ (indicating usage of a  
4 to 20 mA input signal at terminals ‘‘IV’’).  
6. Speed Control (located on the VFD’s keypad/display) set  
for ‘‘Remote’’ (press the ‘‘Speed Ctrl’’ button until LED  
‘‘Remote’’ is illuminated).  
Table 31 — Motor Overload Settings  
UNIT  
IFM HP  
DESIGNATION  
VOLTAGE  
tHr1  
DESIGNATION  
UNIT 48/50  
AND  
SETTING  
Model No.  
Position 12  
Model No.  
Position 15  
FK,FY, JK,JY  
5
5
6
6
6
6
6
And  
And  
And  
And  
And  
And  
And  
N
Q
A
K
Q
Q
T
82.0  
86.0  
80.0  
80.0  
80.0  
80.0  
78.0  
7. Programmed according to Carrier defaults.  
8. Duct Pressure set point established by user, or use fac-  
tory default (30 Hz indicating 2.50-in. wg) (see Table 13).  
FKX,FKY,  
JKX,JKY  
LEGEND  
VFD Operational Status — The VFDs contain ex-  
tensive self-diagnostic functions which are accessed through  
the VFD display panel (located on the front of the VFD or  
at a remote location when the accessory remote display pack-  
age has been installed).  
IFM  
Indoor Fan Motor  
Unit Wiring — A typical wiring schematic is shown in  
Fig. 55.  
54  
LEGEND AND NOTES FOR FIG. 55  
ALM  
C
Alarm  
LAT  
LPS  
MTR  
MV  
Leaving-Air Temperature  
Low-Pressure Switch  
Motor  
Contactor  
CB  
Circuit Breaker  
CCB  
COMP  
CH  
Control Circuit Breaker  
Compressor  
Main Valve  
NC  
Normally Closed  
Normally Open  
Crankcase Heater  
Control Relay  
NO  
CR  
OFC  
OFM  
OMR  
PCB  
PEC  
PEDM  
PEM  
P, PL  
RCB  
RES  
RFC  
RFM  
SCT  
TB  
Outdoor Fan Contactor  
Outdoor (Condenser) Fan Motor  
Outdoor Motor Relay  
Power Exhaust Circuit Breaker  
Power Exhaust Contactor  
Power Exhaust Damper Motor  
Power Exhaust Motor  
Plug  
DPS  
DPT  
EAT  
EC  
Differential Pressure Switch  
Discharge Pressure Transducer  
Enering-Air Temperature  
Enthalpy Control  
ECR  
EOR  
EQUIP  
FS  
Economizer Close Relay  
Economizer Open Relay  
Equipment  
Fan Status Switch  
Ground  
Return Fan Circuit Breaker  
Resistor  
Return Fan Contactror  
Return Fan Motor  
Saturated Condensing Thermistor  
Terminal Block  
Transformer  
Unloader  
Variable Frequence Drive  
GND  
HIR  
Heat Interlock Relay  
High-Pressure Switch  
Heater Relay  
HPS  
HR  
HTR  
IDC  
Heater  
Induced Draft Contactor  
Induced Draft Motor  
Indoor (Evaporator) Fan Contactor  
Indoor Fan Circuit Breaker  
Inlet Guide Vanes  
Inlet Guide Vanes Motor  
TRAN  
U
VFD  
IDM  
IFC  
IFCB  
IGV  
Field Wiring  
Factory Wiring  
IGVM  
NOTES:  
H4  
H3  
1. Connect TRAN1 to  
for 460 v units. Connect to  
for 230 v  
units. If 208/230 v units are run with a 208 v power supply  
H2  
connect to  
.
2. Connect TRAN2 to BLK lead for 460 v units. Connect to ORN lead  
for 230 v units. If 208/230 v units are run with a 208 v power sup-  
ply connect to RED lead.  
3. Circuit breaker must trip amps are equal to or less than 156% FLA  
(full load amps) for CB1 and CB2. All others are 140%.  
4. If any of the original wire furnished must be replaced, it must be  
replaced with type 90° C wire or its equivalent.  
5. Number(s) indicates the line location of contacts. A bracket over  
(2) numbers signifies single pole double throw contacts. An un-  
derlined number signifies a normally closed contact. Plain num-  
bers (no lines), signify a normally opened contact.  
6. Condenser fan motors are thermally protected.  
7. Three phase motors are protected under primary single phasing  
conditions.  
55  
5 6  
5 7  
SERVICE TRAINING  
Packaged Service Training programs are an excellent way to increase your knowledge of the equip-  
ment discussed in this manual, including:  
• Unit Familiarization  
• Installation Overview  
• Maintenance  
• Operating Sequence  
A large selection of product, theory, and skills programs are available, using popular video-based for-  
mats and materials. All include video and/or slides, plus companion book.  
Classroom Service Training which includes ‘‘hands-on’’ experience with the products in our labs can  
mean increased confidence that really pays dividends in faster troubleshooting and fewer callbacks.  
Course descriptions and schedules are in our catalog.  
CALL FOR FREE CATALOG 1-800-962-9212  
[
] Packaged Service Training  
[
] Classroom Service Training  
Copyright 1999 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1 PC 111 Catalog No. 534-716 Printed in U.S.A. Form 48/50F,J-1T Pg 58 4-99 Replaces: 48/50D,F,J-1T  
Tab 1a 1b  
1
START-UP CHECKLIST  
MODEL NO.:  
DATE:  
SERIAL NO.:  
TECHNICIAN:  
I. PRE-START-UP:  
VERIFY THAT UNIT IS LEVEL  
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT  
LOOSEN ALL SHIPPING HOLDDOWN BOLTS AND REMOVE SHIPPING BRACKETS PER INSTRUCTIONS  
VERIFY THAT COMPRESSOR SUSPENSION SPRINGS HAVE BEEN LOOSENED PER INSTRUCTIONS  
VERIFY OPENING OF ECONOMIZER HOODS  
VERIFY INSTALLATION OF EXHAUST HOODS  
CONFIRM THAT TUBING FOR SPACE AND SUPPLY DUCT PRESSURES HAS BEEN INSTALLED  
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS  
VERIFY THAT POWER SUPPLY MATCHES UNIT DATA PLATE  
VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT  
CHECK GAS PIPING FOR LEAKS (48FK,JK ONLY)  
CHECK THAT INDOOR-AIR FILTERS ARE CLEAN AND IN PLACE  
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SET SCREWS  
ARE TIGHT  
VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED  
OPEN SUCTION, DISCHARGE, AND LIQUID LINE SERVICE VALVES  
CHECK COMPRESSOR OIL LEVEL SIGHT GLASS AND VERIFY PROPER LEVEL  
VERIFY THAT CRANKCASE HEATERS HAVE BEEN ENERGIZED FOR 24 HOURS  
CHECK VOLTAGE IMBALANCE  
LINE-TO-LINE VOLTS:  
(AB + AC + BC)/3 = AVERAGE VOLTAGE =  
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =  
AB  
V
AC  
V
BC  
V
V
V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =  
%
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!  
CALL LOCAL POWER COMPANY FOR ASSISTANCE.  
II. PRELIMINARY CHECKLIST ITEMS:  
CONTROL SETTINGS  
DIP SWITCHES SET TO MATCH INSTALLED ACCESSORIES:  
SUPPLY AIR SET POINT RESET (DIP SWITCH NO. 4 ON)  
MORNING WARM-UP (DIP SWITCH NO. 4 ON)  
DEMAND LIMIT (DIP SWITCH NO. 5 ON)  
SUPPLY AIR SET POINT (P1) SET BETWEEN 45 AND 70 F  
ECONOMIZER MINIMUM POSITION (P5) SET PER PLANS  
SUPPLY AIR SET POINT RESET SETTINGS:  
RESET INITIATION TEMPERATURE (P7) (TYPICALLY 68 TO 72 F)  
RESET LIMIT TEMPERATURE (P3) (TYPICALLY 60 TO 70 F)  
MORNING WARM-UP TEMPERATURE (TYPICALLY 50 TO 65 F)  
IGV/VFD DUCT PRESSURE SET POINT PER PLANS  
BUILDING PRESSURE (MODULATING POWER EXHAUST) SET PER PLANS  
DEMAND LIMIT SETTINGS PER PLAN:  
SINGLE STEP DEMAND LIMIT (P4) SET (TYPICALLY 25 TO 50%)  
TWO-STEP DEMAND LIMIT  
DLCM-P1 SET (TYPICALLY 50 TO 75%)  
DLCM-P2 SET (TYPICALLY 0 TO 25%)  
OCCUPIED/UNOCCUPIED SWITCH INSTALLED PER FIG. 21 (CLOSE TO START UNIT)  
CL-1  
III. START-UP  
CHECK EVAPORATOR FAN SPEED AND RECORD.  
CHECK CONDENSER FAN SPEED AND RECORD.  
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:  
COMP A1  
COMP A2  
COMP B1  
COMP B2  
OIL PRESSURE  
SUCTION PRESSURE  
SUCTION LINE TEMP  
DISCHARGE PRESSURE  
DISCHARGE LINE TEMP  
ENTERING CONDENSER AIR TEMP  
LEAVING CONDENSER AIR TEMP  
EVAP ENTERING AIR DB TEMP  
EVAP ENTERING AIR WB TEMP  
EVAP LEAVING AIR DB TEMP  
EVAP LEAVING AIR WB TEMP  
COMPRESSOR AMPS (L1)  
COMPRESSOR AMPS (L2)  
COMPRESSOR AMPS (L3)  
ELECTRICAL  
SUPPLY FAN AMPS  
ELECTRIC HEAT AMPS L1  
EXHAUST FAN AMPS  
L2 L3  
TEMPERATURES  
OUTDOOR-AIR TEMPERATURE  
RETURN-AIR TEMPERATURE  
COOLING SUPPLY AIR  
F
F
F
DB (Dry-Bulb)  
DB  
F
WB (Wet-Bulb)  
PRESSURES  
GAS INLET PRESSURE  
IN. WG  
GAS MANIFOLD PRESSURE STAGE NO. 1  
REFRIGERANT SUCTION CIRCUIT NO. 1  
REFRIGERANT DISCHARGE CIRCUIT NO. 1  
IN. WG  
PSIG  
STAGE NO. 2  
IN. WG  
PSIG  
CIRCUIT NO. 2  
CIRCUIT NO. 2  
PSIG  
PSIG  
VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS IN UNIT INSTALLATION INSTRUCTIONS  
GENERAL  
ECONOMIZER MINIMUM VENT SETTING TO JOB REQUIREMENTS  
IV. NOTES  
Copyright 1999 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1  
1
PC 111  
Catalog No. 534-716  
Printed in U.S.A.  
Form 48/50F,J-1T  
Pg CL-2  
4-99  
Replaces: 48/50D,F,J-1T  
Tab 1a 1b  

Carbine PLUS 5900 User Manual
Carrier 38CKC036 Air User Manual
Carrier 39LE User Manual
Fujitsu Air Conditioner ASU9D User Manual
GE 2 9022 User Manual
GE ASV05 User Manual
Haier Air Conditioner HPY08XCM User Manual
Haier Commercial Cool CPN11XCJ User Manual
Heat Controller Inc Air Conditioner HDG24 User Manual
HoMedics Shiatsu and Vibration Massaging Cussion MCS 300H User Manual