Carrier 50EW User Manual

50EJ,EK,EW,EY024-048  
Single-Package Rooftop Units  
Electric Cooling with Electric Heat Option  
Installation, Start-Up and  
Service Instructions  
CONTENTS  
IMPORTANT — READ BEFORE INSTALLING  
Page  
IMPORTANT: Due to upgrades in unit control soft-  
ware and hardware, units produced currently are slightly  
different than original design units. The unit control  
software (which has changed) is designated with a sticker  
on the unit control board, chip U8 (the large chip in  
the center of the board), which states the software Ver-  
sion number. Version 1.0 is the original version. Ver-  
sion 2.0 is the current version. Differences in instal-  
lation, configuration, and start-up procedures in this  
manual will be identified by Version number.  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . 1  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-31  
Step 1 — Provide Unit Support . . . . . . . . . . . . . . 1  
• ROOF CURB  
• ALTERNATE UNIT SUPPORT  
Step 2 — Rig and Place Unit . . . . . . . . . . . . . . . . . 8  
• POSITIONING  
• ROOF MOUNT  
Step 3 — Field Fabricate Ductwork . . . . . . . . . . . 11  
Step 4 — Make Unit Duct Connections . . . . . . . 11  
Step 5 — Trap Condensate Drain . . . . . . . . . . . . . 11  
Step 6 — Controls Options . . . . . . . . . . . . . . . . . . 12  
• CONSTANT VOLUME APPLICATIONS  
VARIABLE AIR VOLUME (VAV)  
APPLICATIONS  
Step 7 — Make Electrical Connections . . . . . . . 15  
• POWER WIRING  
• FIELD POWER SUPPLY  
• FIELD CONTROL WIRING  
INSTALLATION  
Step 1 — Provide Unit Support  
All panels must be in place when rigging. Unit is not  
designed for handling by fork truck.  
Step 8 — Make Outdoor-Air Inlet  
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
• ECONOMIZER  
ROOF CURB — Assemble and install accessory roof curb  
in accordance with instructions shipped with the curb. Ac-  
cessory roof curb and information required to field fabricate  
a roof curb or horizontal adapter are shown in Fig. 1 and 2.  
Install insulation, cant strips, roofing, and counter flashing  
as shown. Ductwork can be secured to roof curb before unit  
is set in place.  
• ECONOMIZER SETTINGS  
Step 9 — Position Power Exhaust/  
Barometric Relief Damper Hood . . . . . . . . . . . . . 29  
Step 10 — Install Accessories . . . . . . . . . . . . . . . 30  
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-42  
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42-45  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . 46-51  
START-UP CHECKLIST . . . . . . . . . . . . . . . CL-1, CL-2  
IMPORTANT: The gasketing of the unit to the roof  
curb is critical for a leak-proof seal. Install gasket sup-  
plied with the roof curb as shown in Fig. 1. Improp-  
erly applied gasket can result in air leaks and poor unit  
performance.  
SAFETY CONSIDERATIONS  
Curb should be level. This is necessary to permit unit drain  
to function properly. Unit leveling tolerance is shown in  
Fig 1 and 2. Refer to Accessory Roof Curb Installation In-  
structions for additional information as required. When ac-  
cessory roof curb is used, unit may be installed on class A,  
B, or C roof covering material.  
Installation and servicing of air-conditioning equipment  
can be hazardous due to system pressure and electrical com-  
ponents. Only trained and qualified service personnel should  
install, repair, or service air-conditioning equipment.  
Untrained personnel can perform basic maintenance func-  
tions of cleaning coils and filters and replacing filters. All  
other operations should be performed by trained service per-  
sonnel. When working on air-conditioning equipment, ob-  
serve precautions in the literature, tags and labels attached  
to the unit, and other safety precautions that may apply.  
ALTERNATE UNIT SUPPORT — When the curb or adapter  
cannot be used, support unit with sleepers using unit curb or  
adapter support area. If sleepers cannot be used, support long  
sides of unit (refer to Fig. 3-6) with a minimum number of  
equally spaced 4-in.  
x
4-in. pads as follows:  
Follow all safety codes. Wear safety glasses and work gloves.  
Use quenching cloth for unbrazing operations. Have fire ex-  
tinguishers available for all brazing operations.  
50EJ,EK,EW,EY024-034 units require 3 pads on each side;  
50EJ,EK,EW,EY038-048 require 4 pads on each side. Unit  
may sag if supported by corners only.  
Before performing service or maintenance operations on  
unit, turn off main power switch to unit. Electrical shock  
could cause personal injury.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1  
PC 111  
Catalog No. 535-006  
Printed in U.S.A.  
Form 50E-3SI  
Pg 1  
8-96  
Replaces: 50E-1SI  
Tab 1b  
NOTE: To prevent standing water in the drain pan of the indoor section and the  
heat exchangers, UNIT CAN ONLY BE PITCHED AS SHOWN.  
NOTES:  
1. Unless otherwise specified, all dimensions are to out-  
side of part.  
UNIT LEVELING TOLERANCES DIMENSIONS*  
(Degrees and Inches)  
2. Roof curb accessory is shipped disassembled.  
3. All roof curb parts are to be 16 ga galvanized steel.  
4. Dimensions are in inches.  
A
B
Deg.  
in.  
Deg.  
in.  
1.0  
2.9  
.50  
.75  
*From edge of unit to horizontal.  
Fig. 2 — Roof Curb (Sizes 038-048)  
3
NOTES:  
CORNER WEIGHT  
(lb)  
OPERATING  
WEIGHT  
(lb)  
A
B
UNIT SIZE  
50EJ/EK  
ft-in.  
ft-in.  
1
2
3
4
024  
028  
030  
034  
4016  
4102  
4102  
4102  
5-1138 3-51116 823 914 1199 1080  
5- 812 3-758  
5- 812 3-758  
5- 812 3-758  
844 859 1210 1189  
844 859 1210 1189  
844 859 1210 1189  
Fig. 3 — Base Unit Dimensions, 50EJ/EK024-034  
4
NOTES:  
LEGEND  
1. Weights include economizer (Std)  
VFD  
Variable Frequency Drive  
2.  
Center of gravity.  
3. Do not locate adjacent units with discharge facing economizer inlet. Mini-  
mum clearances to be:  
Adjacent Units: 15Ј-0Љ  
Top of Units: No overhang  
Condenser Coil: 4Ј-0Љ  
Economizer Side: 6Ј-0Љ  
Filter Access Side: 10Ј-0Љ (for removal of evaporator coil)  
4. For smaller service and operational clearances, contact Carrier Applica-  
tion Engineering department.  
5. Bottom ducts designed to be attached to accessory roof curb. If unit is  
mounted on dunnage, it is recommended the ducts be supported by cross  
braces as done on accessory roof curb.  
6. Dimensions are in inches. Dimensions in [ ] are in millimeters.  
7. For units with electric heat, a field-supplied 90° elbow must be installed  
in the supply ductwork below the unit discharge.  
CORNER WEIGHT  
(lb)  
OPERATING  
WEIGHT  
(lb)  
A
B
UNIT SIZE  
50E  
ft-in.  
ft-in.  
1
2
3
4
J038  
4282  
4508  
4795  
7-7516 3-1012  
7-31316 3-1112  
7-2316 3-10332 1007 915 1368 1505  
961 858 1162 1302  
J/K044  
J048  
973 868 1258 1409  
Fig. 4 — Base Unit Dimensions, 50EJ038-048 and 50EK044  
5
NOTES:  
LEGEND  
1. Weights include economizer (Std)  
VFD  
Variable Frequency Drive  
2.  
Center of gravity.  
3. Do not locate adjacent units with discharge facing econo-  
mizer inlet. Minimum clearances to be:  
Adjacent Units: 15Ј-0Љ  
Top of Units: No overhang  
Condenser Coil: 4Ј-0Љ  
CORNER WEIGHT  
(lb)  
OPERATING  
WEIGHT  
(lb)  
A
B
UNIT SIZE  
50EW/EY  
Economizer Side: 6Ј-0Љ  
Filter Access Side: 10Ј-0Љ (for removal of evaporator  
coil)  
ft-in.  
ft-in.  
1
2
3
4
024  
028  
030  
034  
4016  
4102  
4102  
4102  
5-1138 3-51116 823 914 1199 1080  
4. For smaller service and operational clearances, con-  
tact Carrier Application Engineering department.  
5. Dimensions are in inches. Dimensions in [ ] are in  
millimeters.  
6. For units equipped with electric heat, a field-supplied  
90° elbow must be installed in the supply ductwork be-  
low the unit discharge.  
5- 812 3-758  
5- 812 3-758  
5- 812 3-758  
844 859 1210 1189  
844 859 1210 1189  
844 859 1210 1189  
7. For side-supply/return applications, a single return and  
supply ductwork connection is recommended for cov-  
ering both return and both supply openings.  
Fig. 5 — Base Unit Dimensions, 50EW/EY024-034  
6
NOTES:  
LEGEND  
1. Weights include economizer (Std)  
VFD  
Variable Frequency Drive  
2.  
Center of gravity.  
3. Do not locate adjacent units with discharge facing economizer inlet.  
Minimum clearances to be:  
Adjacent Units: 15Ј-0Љ  
Top of Units: No overhang  
Condenser Coil: 4Ј-0Љ  
Economizer Side: 6Ј-0Љ  
CORNER WEIGHT  
OPERATING  
WEIGHT  
(lb)  
A
ft-in.  
7-7516 3-1012  
7-31316 3-1112  
B
Filter Access Side: 10Ј-0Љ (for removal of evaporator coil)  
4. For smaller service and operational clearances, contact Carrier  
Application Engineering department.  
UNIT SIZE  
50E  
(lb)  
ft-in.  
1
2
3
4
5. Dimensions are in inches. Dimensions in [ ] are in millimeters.  
6. For units equipped with electric heat, a field-supplied 90° elbow must  
be installed in the supply ductwork below the unit discharge.  
7. For side-supply/return applications, a single return and supply duct-  
work connection is recommended for covering both return and both  
supply air openings.  
W038  
4282  
4508  
4795  
961 858 1162 1302  
W/Y044  
W048  
973 868 1258 1409  
7-2316 3-10332 1007 915 1368 1505  
Fig. 6 — Base Unit Dimensions, 50EW038-048 and 50EY044  
7
Four lifting lugs are provided on the unit base rails as shown  
in Fig. 7. Refer to rigging instructions on unit.  
Step 2 — Rig and Place Unit — Inspect unit for trans-  
portation damage. File any claim with transportation agency.  
Keep unit upright, and do not drop. Use spreader bars over  
unit to prevent sling or cable damage. Rollers may be used  
to move unit across a roof. Level by using unit frame as a  
reference; leveling tolerance is shown in Fig. 1 and 2. See  
Fig. 7 for additional information. Unit weight is shown in  
Table 1.  
NOTE: On retrofit jobs, ductwork may be attached to old  
unit instead of roof curb. Be careful not to damage ductwork  
when removing unit. Attach existing ductwork to roof curb  
instead of unit.  
POSITIONING — Provide clearance around and above unit  
for airflow, safety, and service access (Fig. 3-6).  
Do not install unit in an indoor location. Do not locate air  
inlets near exhaust vents or other sources of contaminated  
air.  
Although unit is weatherproof, guard against water from  
higher level runoff and overhangs.  
NOTICE TO RIGGERS:  
ALL PANELS MUST BE IN PLACE  
WHEN RIGGING.  
NOTE: Rig with four cables and spread with two  
92 in. (2337 mm) spreader bars. Maintain a dis-  
tance of 74 in. (1880 mm) from top of unit to  
eyehook.  
NOTE:  
Add 32 lb (14.5 kg) for domestic crating.  
Add 312 lb (142 kg) for export crating (024-034 units).  
Add 346 lb (157 kg) for export crating (038-048 units).  
Add 250 lb (113 kg) for power exhaust.  
Add 220 lb (100 kg) for copper condenser coil (024-034 units).  
Add 285 lb (129 kg) for copper condenser coil (038-044 units).  
Add 380 lb (172 kg) for copper condenser coil (048 unit).  
WEIGHT  
lb kg  
A
B
C
MODEL  
50EJ/EK/EW/EY  
in.  
mm  
in.  
mm  
in.  
mm  
024  
028  
030  
034  
038*  
044  
048*  
4016 1822 87.68 2227 71.4 1814 41.7 1059  
4102 1860 87.68 2227 68.5 1740 43.6 1107  
4282 1942  
4508 2045  
4795 2175  
91.3 2319 46.5 1181  
3810 87.8 2230 46.5 1181  
86.2 2189 46.1 1171  
150  
*Sizes 038 and 048 are 50EJ,EW units only.  
Fig. 7 — Rigging Label  
8
Table 1 — Physical Data  
UNIT 50EJ,EK,EW,EY  
024  
028  
030  
034  
NOMINAL CAPACITY (tons)  
20  
25  
27  
30  
OPERATING WEIGHT (lb)*  
Unit  
Al/Al†  
4016  
4236  
365  
4102  
4322  
365  
4102  
4322  
365  
4102  
4322  
365  
Al/Cu†  
Roof Curb (14-in. curb)  
COMPRESSOR  
Type  
Ckt 1  
Ckt 2  
06D328  
06D818  
2
06D328  
06D328  
2
06D537  
06D328  
2
06D537  
06D537  
2
Number of Refrigerant Circuits  
Oil (oz) (Ckt1, Ckt 2)  
115, 88  
115 ea.  
115 ea.  
115 ea.  
REFRIGERANT TYPE  
Operating Charge (lb-oz)  
Circuit 1**  
R-22  
25-0  
31-0  
25-0  
25-0  
25-0  
25-0  
25-0  
25-0  
Circuit 2  
3
CONDENSER COIL  
Quantity  
Rows...Fins/in.  
Total Face Area (sq ft)  
Cross-Hatched  
8Љ Copper Tubes, Aluminum Lanced or Copper Fins  
1
1
1
1
4...15  
33.3  
4...15  
33.3  
4...15  
33.3  
4...15  
33.3  
CONDENSER FAN  
Nominal Cfm  
Quantity...Diameter (in.)  
Motor Hp (1075 Rpm)  
Propeller Type  
13,420  
2...30  
1
13,420  
2...30  
1
13,420  
2...30  
1
13,420  
2...30  
1
3
EVAPORATOR COIL  
Rows...Fins/in.  
Total Face Area (sq ft)  
Cross-Hatched ⁄8Љ Copper Tubes, Aluminum or Copper Plate Fins, Intertwined Circuits  
4...15  
31.7  
4...15  
31.7  
4...15  
31.7  
4...15  
31.7  
EVAPORATOR FAN  
Centrifugal Type  
Quantity...Size (in.)  
2...20x15  
Belt  
2...20x15  
Belt  
2...20x15  
Belt  
2..20x15  
Belt  
Type Drive  
Nominal Cfm  
8,000  
10††  
S215T  
Ball  
10,000  
10††  
S215T  
Ball  
11,000  
15††  
S254T  
Ball  
12,000  
15††  
S254T  
Ball  
Motor Hp  
5
15  
7.5  
15  
S254T  
10  
S215T  
20  
10  
20  
Motor Frame Size  
S184T  
S254T  
S213T  
S256T  
S215T  
S256T  
Motor Bearing Type  
Maximum Allowable Rpm  
Motor Pulley Pitch Diameter  
Nominal Motor Shaft Diameter (in.)  
Fan Pulley Pitch Diameter (in.)  
Nominal Fan Shaft Diameter (in.)  
Belt, Quantity...Type  
1200  
6.6  
1200  
6.1  
1200  
6.7  
1200  
6.9  
4.6  
118  
11.1  
6.9  
158  
11.1  
4.9  
138  
11.1  
7.1  
158  
11.1  
6.6  
138  
13.7  
7.5  
158  
11.1  
6.4  
138  
12.5  
7.5  
158  
11.1  
138  
138  
158  
158  
12.5  
11.1  
11.1  
11.1  
11116  
11116  
11116  
11116  
1...BX59 1...BX60 1...5VX590 1...BX56 1...BX56 1...5VX590 1...BX62 1...5VX590 1...5VX600 1...BX60 1...5VX590 1...5VX600  
Belt, Length (in.)  
Pulley Center Line Distance (in.)  
Factory Speed Setting (rpm)  
62  
63  
59  
59  
59  
59  
65  
59  
60  
63  
15.6-18.4  
896  
59  
60  
16.0-18.7 15.6-18.4 15.0-17.9 15.6-18.4 15.6-18.4 15.0-17.9 15.6-18.4  
15.0-17.9  
15.0-17.9  
725  
924  
1088  
773  
962  
1119  
843  
1056  
1182  
1088  
1182  
HIGH-PRESSURE SWITCH (psig)  
Cutout  
Reset (Auto.)  
426  
320  
426  
320  
426  
320  
426  
320  
LOW-PRESSURE SWITCH (psig)  
Cutout  
Reset (Auto.)  
7
22  
7
22  
7
22  
7
22  
RETURN-AIR FILTERS  
Quantity...Size (in.)  
10...20x24x2  
10...20x24x2  
10...20x24x2  
10...20x24x2  
OUTDOOR-AIR FILTERS  
Quantity...Size (in.)  
8...16x25  
4...20x25  
8...16x25  
4...20x25  
8...16x25  
4...20x25  
8...16x25  
4...20x25  
POWER EXHAUST  
Motor, Quantity...Hp  
Fan, Diameter...Width (in.)  
Direct Drive, 3-Speed, Single-Phase Motor (Factory-Wired For High Speed) and Forward Curved Fan  
4...1  
11...10  
NOTES:  
LEGEND  
1. See Table 2 for evaporator fan motor data.  
2. Sizes 038 and 048 are 50EJ,EW units only.  
Al  
Cu  
Aluminum  
Copper  
*Weight of unit does not include variable frequency drive (VFD), barometric relief, or power  
exhaust. If a VAV unit (a VFD is installed), add the VFD weight in the table at right.  
†Evaporator coil fin material/condenser coil fin material.  
**Sizes 024-034: Circuit 1 uses the lower portion of condenser coil, Circuit 2 uses the upper  
portion. Sizes 038-048: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units  
have intertwined evaporator coils.  
††Motor and drive shown will deliver approximately 2.5 in. wg net external static. For more  
drive information, see Table 2.  
VFD WEIGHTS (lb)  
VFD  
(Hp)  
208/230 v  
460 v  
22  
575 v  
5
20  
51  
60  
64  
7.5  
10  
15  
20  
25  
30  
37  
51  
61  
64  
61  
63  
109  
109  
174  
180  
63  
111  
112  
118  
105  
172  
9
Table 1 — Physical Data (cont)  
UNIT 50EJ,EK,EW,EY  
038  
044  
048  
NOMINAL CAPACITY (tons)  
35  
40  
45  
OPERATING WEIGHT (lb)*  
Unit  
Al/Al†  
4282  
4567  
410  
4508  
4793  
410  
4795  
5175  
410  
Al/Cu†  
Roof Curb (14-in. curb)  
COMPRESSOR  
Type  
Ckt 1  
Ckt 2  
06D537  
06D537  
2
06EA250  
06EA250  
2
06EA265  
06EA250  
2
Number of Refrigerant Circuits  
Oil (oz) (Ckt1, Ckt 2)  
115 ea.  
224 ea.  
304, 224  
REFRIGERANT TYPE  
Operating Charge (lb-oz)  
Circuit 1**  
R-22  
34-0  
34-0  
35-0  
35-0  
41-0  
41-0  
Circuit 2  
3
CONDENSER COIL  
Quantity  
Rows...Fins/in.  
Total Face Area (sq ft)  
Cross-Hatched  
8Љ Copper Tubes, Aluminum Lanced or Copper Fins  
2
2
1
1
3...15  
58.3  
3...15  
58.3  
4...15  
3...15  
66.7  
CONDENSER FAN  
Nominal Cfm  
Quantity...Diameter (in.)  
Motor Hp (1075 Rpm)  
Propeller Type  
27,064  
4...30  
1
27,064  
4...30  
1
27,064  
4...30  
1
3
EVAPORATOR COIL  
Rows...Fins/in.  
Total Face Area (sq ft)  
Cross-Hatched  
8Љ Copper Tubes, Aluminum or Copper Plate Fins, Intertwined Circuits  
3...15  
34.7  
3...15  
34.7  
4...15  
34.7  
EVAPORATOR FAN  
Centrifugal Type  
2...20x15  
Belt  
Quantity...Size (in.)  
2..20x15  
Belt  
2...20x15  
Belt  
Type Drive  
Nominal Cfm  
14,000  
15††  
S254T  
Ball  
16,000  
18,000  
25††  
Motor Hp  
10  
20  
15  
20††  
S256T  
Ball  
25  
20  
30  
S286T  
Motor Frame Size  
S215T  
S256T  
S254T  
S284T  
S256T  
S284T  
Ball  
Motor Bearing Type  
Maximum Allowable Rpm  
Motor Pulley Pitch Diameter  
Nominal Motor Shaft Diameter (in.)  
Fan Pulley Pitch Diameter (in.)  
Nominal Fan Shaft Diameter (in.)  
Belt, Quantity...Type  
1200  
6.9  
1200  
8.1  
1200  
4.1  
138  
9.1  
7.5  
158  
12.5  
6.9  
158  
12.5  
9.1  
118  
13.7  
5.3  
158  
9.1  
5.9  
7.5  
178  
11.1  
158  
158  
178  
12.5  
13.7  
9.1  
11116  
1...5VX630  
63  
11116  
1...5VX670  
67  
11116  
1...BX51  
54  
15.6-18.4  
788  
1...5VX650  
65  
1...5VX630  
63  
2...5VX680  
68  
14.6-17.6  
1162  
1...5VX550  
55  
15.0-17.9  
1019  
2...5VX560  
56  
2...5VX610  
59  
14.6-17.6  
1182  
Belt, Length (in.)  
Pulley Center Line Distance (in.)  
Factory Speed Setting (rpm)  
15.0-17.9  
15.0-17.9  
14.6-17.6  
1135  
966  
1050  
1066  
1035  
HIGH-PRESSURE SWITCH (psig)  
Cutout  
Reset (Auto.)  
426  
320  
426  
320  
426  
320  
LOW-PRESSURE SWITCH (psig)  
Cutout  
Reset (Auto.)  
7
22  
7
22  
7
22  
RETURN-AIR FILTERS  
Quantity...Size (in.)  
10...20x24x2  
10...20x24x2  
10..20x24x2  
OUTDOOR-AIR FILTERS  
Quantity...Size (in.)  
8...16x25  
4...20x25  
8...16x25  
4...20x25  
8...16x25  
4...20x25  
POWER EXHAUST  
Motor, Quantity...Hp  
Fan, Diameter...Width (in.)  
Direct Drive, 3-Speed, Single-Phase Motor (Factory-Wired For High Speed) and Forward Curved Fan  
4...1  
11...10  
NOTES:  
LEGEND  
1. See Table 2 for optional evaporator fan motor data.  
2. Sizes 038 and 048 are 50EJ,EW units only.  
Al  
Cu  
Aluminum  
Copper  
*Weight of unit does not include variable frequency drive (VFD), barometric relief, or power  
exhaust. If a VAV unit (a VFD is installed), add the VFD weight in the table at right.  
†Evaporator coil fin material/condenser coil fin material.  
**Sizes 024-034: Circuit 1 uses the lower portion of condenser coil, Circuit 2 uses the upper  
portion. Sizes 038-048: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units  
have intertwined evaporator coils.  
††Motor and drive shown will deliver approximately 2.5 in. wg net external static. For more  
drive information, see Table 2.  
VFD WEIGHTS (lb)  
VFD  
(Hp)  
208/230 v  
460 v  
22  
575 v  
60  
5
20  
51  
7.5  
10  
15  
20  
25  
30  
37  
64  
51  
61  
64  
61  
63  
109  
109  
174  
180  
63  
111  
112  
118  
105  
172  
10  
Table 2 — Evaporator Fan Motor Data  
MOTOR  
SHEAVE  
PITCH  
DIAMETER  
(in.)  
FAN  
SHEAVE  
PITCH  
DIAMETER  
(in.)  
MOTOR  
SHAFT  
FAN  
BELT  
TENSION  
(Lb @  
BUSHING  
DIAMETER  
(in.)  
BUSHING  
DIAMETER  
(in.)  
OUTSIDE  
BELT  
LENGTH  
UNIT MOTOR  
SHAFT  
MOTOR  
FAN  
SHEAVE  
BELT  
SIZE  
HP  
DIAMETER SPEED SHEAVE  
(in.)  
(rpm)  
.24 in.)  
5
10  
15  
1.12  
1.38  
1.62  
725  
924  
BK52  
BK72  
4.6  
6.6  
6.9  
None-1.125 1B5V110  
None-1.375 1B5V124  
11.1  
12.5  
11.1  
B-1.6875  
B-1.6875  
B-1.6875  
BX59  
BX60  
62  
63  
59  
5.02  
7.05  
9.38  
024  
028  
030  
034  
038  
044  
048  
1088  
1B5V68  
B-1.625  
1B5V110  
5VX590  
7.5  
10  
15  
1.38  
1.38  
1.62  
773  
962  
1119  
BK55H  
BK67H  
1B5V70  
4.9  
6.1  
7.1  
H-1.375  
H-1.375  
B-1.625  
1B5V110  
1B5V110  
1B5V110  
11.1  
11.1  
11.1  
B-1.6875  
B-1.6875  
B-1.6875  
BX56  
BX56  
5VX590  
59  
59  
59  
6.87  
7.26  
9.17  
10  
15  
20  
1.38  
1.62  
1.62  
843  
1056  
1182  
BK72  
1B5V66  
1B5V74  
6.6  
6.7  
7.5  
None-1.375 1B5V136  
13.7  
11.1  
11.1  
B-1.6875  
B-1.6875  
B-1.6875  
BX62  
5VX590  
5VX600  
65  
59  
60  
6.96  
9.60  
11.67  
B-1.625  
B-1.625  
1B5V110  
1B5V110  
10  
15  
20  
1.38  
1.62  
1.62  
896  
1088  
1182  
BK70H  
1B5V68  
1B5V74  
6.4  
6.9  
7.5  
H-1.375  
B-1.625  
B-1.625  
1B5V124  
1B5V110  
1B5V110  
12.5  
11.1  
11.1  
B-1.6875  
B-1.6875  
B-1.6875  
BX60  
5VX590  
5VX600  
63  
59  
60  
7.20  
9.38  
11.17  
10  
15  
20  
1.38  
1.62  
1.62  
788  
966  
1050  
2BK47  
1B5V68  
1B5V74  
4.1  
6.9  
7.5  
None-1.375  
B-1.625  
B-1.625  
2B5V90  
1B5V124  
1B5V124  
9.1  
12.5  
12.5  
B-1.6875  
B-1.6875  
B-1.6875  
BX51  
5VX630  
5VX650  
54  
63  
65  
5.49  
9.22  
10.02  
15  
20  
25  
1.62  
1.62  
1.88  
966  
1035  
1162  
1B5V68  
1B5V80  
1B5V90  
6.9  
8.1  
9.1  
B-1.625  
B-1.625  
B-1.875  
1B5V124  
1B5V136  
1B5V136  
12.5  
13.7  
13.7  
B-1.6875  
B-1.6875  
B-1.6875  
5VX630  
5VX670  
5VX680  
63  
67  
68  
9.54  
10.37  
10.88  
20  
25  
30  
1.62  
1.88  
1.88  
1019  
1135  
1182  
2B5V52  
2B5V58  
2B5V76  
5.3  
5.9  
7.5  
B-1.625  
B-1.875  
B-1.875  
2B5V90  
2B5V90  
2B5V110  
9.1  
9.1  
11.1  
B-1.6875  
B-1.6875  
B-1.6875  
5VX550  
5VX560  
5VX610  
55  
56  
59  
7.93  
8.66  
9.07  
NOTE: Motor shaft speed is 1750 rpm. The fan shaft diameter is 11116 inches.  
ROOF MOUNT — Check building codes for weight distri-  
bution requirements.  
Step 3 — Field Fabricate Ductwork — Secure all  
ducts to building structure. Use flexible duct connectors be-  
tween unit and ducts as required. Insulate and weatherproof  
all external ductwork, joints, and roof openings with counter  
flashing and mastic in accordance with applicable codes.  
Ducts passing through an unconditioned space must be  
insulated and covered with a vapor barrier.  
To attach ductwork to roof curb, insert ductwork approxi-  
mately 10 to 11 in. up into the curb. Connect ductwork to  
14-gage roof curb material using sheet metal screw driven  
from inside the duct.  
The units with electric heat require a 1-in. clearance for  
the first 24 in. of ductwork.  
NOTE: A 90-degree elbow must be provided in the duct-  
work to comply with UL (UnderwritersLaboratories) codes  
for use with electric heat.  
Fig. 8 — Air Distribution — Thru-the-Bottom  
Outlet grilles must not lie directly below unit discharge.  
Step 4 — Make Unit Duct Connections  
50EJ,EK UNITS — Unit is shipped for through-the-bottom  
duct connections. Ductwork openings are shown in Fig. 3  
and 4. Attach all ductwork to roof curb. Air distribution  
is shown in Fig. 8. Refer to installation instructions shipped  
with accessory roof curb for more information.  
50EW,EY UNITS — Remove shipping covers from supply  
and return air openings. Attach field-supplied ductwork to  
unit. Use a single duct over both return openings and a single  
duct over both supply openings. See Fig. 5 and 6 for duct  
opening dimensions. Secure all ducts to the building struc-  
ture. See Fig. 9. Use flexible duct connectors between unit  
and ducts as required.  
Install accessory barometric relief or power exhaust in the  
field-fabricated return ductwork. Refer to Position Power  
Exhaust/Barometric Relief Damper Hood Section on  
page 29 for more information.  
Fig. 9 — Air Distribution — Thru-the-Side  
the drain location. One 1-in. FPT coupling is provided in-  
side unit evaporator section for condensate drain connec-  
tion. A trap at least 4-in. deep must be used. Trap must be  
installed to prevent freeze-up.  
Condensate pans are sloped so that water will completely  
drain from the condensate pan to comply with indoor air qual-  
ity guidelines.  
Step 5 — Trap Condensate Drain — See Fig. 3-6  
and 10 for drain location. Condensate drain is open to the  
atmosphere and must be trapped. Install a trapped drain at  
11  
• control of modulating economizer damper to provide free  
cooling when outdoor conditions are suitable, using sup-  
ply air temperature as a control point  
• control of the economizer damper and indoor fan to obtain  
unoccupied free cooling  
• provide power exhaust output to an external power ex-  
haust controller  
• support a field test for field checkout  
• control of 2 stages of CV power exhaust  
• compressor Time Guard(power up and minimum off and  
on times)  
Additional features are provided by accessing the stand-  
ard unit control board via software with a computer. These  
features are:  
• electronic expansion board features (if installed)  
• compressor lockout during low supply air temperature  
• control board diagnostics  
• ability to change supply air set point (economizer control)  
• ability to change high outdoor air temperature lockout set  
point (economizer control)  
Fig. 10 — Condensate Drain Connections  
(Typical Roof Curb or Slab Mount Shown)  
• ability to change power exhaust set points  
Step 6 — Controls Options — The control options  
that the units can provide are based on the following param-  
eters: CV (constant volume) or VAV (variable air volume)  
operation; stand-alone unit with field-supplied sensors in-  
stalled (CV or VAV); as a system via the Carrier Comfort  
System (TEMP or VVT); optional electronic expansion board  
installed (CV or VAV); linked to the Carrier Comfort Net-  
work; and availability of a computer and software (Comfort  
Works, Building Supervisor, and Service Tool) to access the  
base control board. See Table 3.  
NOTE: A CV unit without a thermostat requires a field-  
supplied sensor for operation.  
Features with Sensor Control of Unit (Stand-Alone Appli-  
cations — Unit control is limited to CV unoccupied default  
set points, 90 F for cooling, 55 F for heating. There are  
3 sensor options available:  
• T-57 sensor will monitor room temperature  
• T-55 sensor will monitor room temperature and provide  
unoccupied override capability (1 hour)  
• T-56 sensor will monitor room temperature, provide un-  
occupied override capability (1 hour), and provide a tem-  
perature offset of 5° F.  
NOTE: Access to the base control board allows unit occu-  
pancy schedules, unit timeclock, and various set points to be  
changed from their factory-defined default settings.  
Standard features are:  
• support of remote occupied/unoccupied input to start and  
stop the unit  
• cooling capacity control of 3 stages using economizer and  
2 compressors to maintain space temperature to an occu-  
pied or unoccupied set point  
• enable heating (if installed) or cooling during unoccupied  
periods as required to maintain space temperature within  
the unoccupied set points  
• adjustment of space temperature set points of ± 5° F when  
using a T-56 sensor  
CONSTANT VOLUME APPLICATIONS — The standard  
CV unit is capable of being operated with either a Carrier-  
approved thermostat or a field-supplied sensor. (See Price  
Pages for ordering information.)  
Features with Thermostat Control of Unit  
• two-stage heating (if installed)  
• two-stage cooling  
• control of unit using Y1, Y2, W1, W2, and G thermostat  
inputs  
• control of the indoor fan  
• outdoor air temperature/supply air temperature monitoring  
• control of an outdoor air condenser fan based on outdoor  
air temperature  
Table 3 — Controls Options and Configurations (Non-Thermostat Applications)  
UNIT CONFIGURATION  
DEFAULT COOLING  
DEFAULT HEATING  
UNITS RUNNING VERSION 1.0 UNIT CONTROL SOFTWARE  
Unoccupied Cooling — 90 F (SPT)  
Occupied Cooling — NA  
Unoccupied Heating — 55 F (SPT)  
Occupied Heating — NA  
CV or VAV Unit with SPT Sensor  
CV Unit with SPT Sensor and Remote  
Start/Stop Switch  
Unoccupied Cooling — 90 F (SPT)  
Occupied Cooling — 78 F (SPT)  
Unoccupied Heating — 55 F (SPT)  
Occupied Heating — 68 F (SPT)  
Unoccupied Cooling — NA  
Occupied Cooling — 55 F (SAT)  
Unoccupied Heating — NA  
Occupied Heating — NA  
VAV Unit Remote Start/Switch Only  
VAV Unit with SPT Sensor and Remote  
Start/Stop Switch  
Unoccupied Cooling — 90 F (SPT)  
Occupied Cooling — 55 F (SAT)  
Unoccupied Heating — 55 F (SPT)  
Occupied Heating — NA  
UNITS RUNNING VERSION 2.0 UNIT CONTROL SOFTWARE  
Unoccupied Cooling — 90 F (SPT)  
Occupied Cooling — NA  
Unoccupied Heating — 55 F (SPT)  
Occupied Heating — NA  
CV or VAV Unit with SPT Sensor  
CV Unit with SPT Sensor and Remote  
Start/Stop Switch  
Unoccupied Cooling — 90 F (SPT)  
Occupied Cooling — 78 F (SPT)  
Unoccupied Heating — 55 F (SPT)  
Occupied Heating — 68 F (SPT)  
Unoccupied Cooling — 90 F (RAT)  
Occupied Cooling — 55 F (SAT)  
Unoccupied Heating — 55 F (RAT)  
Occupied Heating — 68 F (RAT)*  
VAV Unit Remote Start/Stop Switch Only  
VAV Unit with SPT Sensor and Remote  
Start/Stop Switch  
Unoccupied Cooling — 90 F (SPT)  
Occupied Cooling — 55 F (SAT)  
Unoccupied Heating — 55 F (SPT)  
Occupied Heating — 68 F (RAT)*  
LEGEND  
*With DIP Switch No. 5 configured to OPEN (Occupied Heat Enabled).  
NOTE: Space temperature sensor and remote stop/switch are field-supplied.  
CV  
Constant Volume  
Not Available  
SAT  
SPT  
VAV  
Supply-Air Temperature  
Space Temperature  
Variable Air Volume  
NA  
RAT  
Return-Air Temperature  
12  
Features with sensor control of unit with computer access  
are:  
or during unexpected power outages. For complete Carrier  
Comfort System (CCS) or Carrier Comfort Network (CCN)  
features and benefits, refer to the product literature.  
• 365 day timeclock with backup (supports minute, hour,  
day of week, date, month, and year)  
VARIABLE AIR VOLUME (VAV) APPLICATIONS  
• daylight savings time function  
Features with Stand-Alone Applications — A VAV unit is  
capable of providing unoccupied cooling controlling to a  
90 F return-air temperature utilizing the factory-supplied return-  
air thermistor located below the return-air damper in the return-  
air section for unit control. The unit will provide unoccupied  
heating (if electric heat is installed) controlling to a 55 F  
return-air temperature. Also provided is a morning warm-up  
which is initiated by the Occupied mode (if electric heat is  
installed) and continues until the return-air temperature rises  
to 68 F. The unit will provide occupied cooling with a de-  
fault temperature of 55 F for the supply air. The supply-air  
temperature is measured by the supply-air thermistor, lo-  
cated in the indoor fan compartment.  
• occupancy control with 8 periods for unit operation  
• holiday table containing up to 18 holiday schedules  
• ability to initiate timed override from T-55 or T-56 sensors  
• ability to use multiple space temperature sensors to aver-  
age the space temperature  
• supply air temperature reset for the supply air temperature  
set point  
• temperature compensated start to calculate early start times  
before occupancy  
• access to the Display, Maintenance, Configuration, Serv-  
ice, and Set Point data table through network software  
When the unit is equipped with a field-supplied space tem-  
perature sensor and a remote contact closure (remote start/  
stop) on the base control board, the occupied default set points  
will monitor unit operation. The occupied default set points  
are 78 F cooling and 68 F heating (if electric heat is in-  
stalled). See Fig. 11 for remote start/stop wiring.  
NOTE: For units which have not had the base unit control  
board accessed via software to set an occupancy schedule,  
the remote start/stop closure will allow the unit to operate in  
the pre-configured occupied default set points (based on return-  
air temperature) of 78 F cooling and 68 F heating. Without  
this feature, the unit will control to the unoccupied default  
set points of 90 F cooling and 55 F heating (if electric heat  
is installed).  
An electronic expansion board may be field-installed to  
provide the following features:  
• control of modulating economizer damper to maintain  
indoor air quality (IAQ) when outdoor conditions are  
suitable  
• provide discrete inputs for fan status, filter status, field-  
applied status, and demand limit  
• provide an output for the external alarm light indicator  
When the unit is connected to the CCN (Carrier Comfort  
Network), the following expansion board features can be  
utilized.  
• perform Demand Limit functions based on CCN loadshed  
commands or the state of the discrete input  
• alarm monitoring of all key parameters  
• CCN protocol  
Standard features of a VAV unit with a remote start/stop  
switch are:  
• control of an outdoor condenser fan based upon outdoor  
air temperature  
• control of modulating economizer to provide free cooling  
when outdoor conditions are suitable, using supply air tem-  
perature as a set point  
• support of remote occupied/unoccupied input to start or  
stop the unit  
• provide power exhaust output to an external power ex-  
haust controller  
• support supply air temperature reset to offset supply air  
set point  
• support a field test for field check out  
• support linkage to DAV systems  
• cooling capacity control of 6 stages plus economizer with  
compressors and unloaders to maintain supply air tem-  
perature set point during occupied periods  
• control of one stage of heat to maintain supply air tem-  
perature at supply air set point during occupied periods  
• provide a variable frequency drive high voltage relay out-  
put to enable VFD  
• control of heat interlock relay  
With the addition of a remote start/stop switch heating or  
cooling is enabled during unoccupied periods as required to  
maintain space temperature to within unoccupied set points.  
• provides power exhaust fire outputs for direct control of  
modulated power exhaust stages during fire or smoke modes  
• smoke control modes including evacuation, smoke purge,  
pressurization, and fire shutdown (modulating power ex-  
haust required)  
• provides CCN IAQ participation  
See Carrier TEMP or VVT(Variable Volume and Tem-  
perature) literature for complete TEMP (single zone) or VVT  
(multi-zone) application information.  
Features with Sensor Control of Unit (Network Applica-  
tions) — The base control board provides, as standard, a con-  
nection for use with a Carrier VVT system and can also be  
integrated into a Carrier Comfort Network.  
When the unit is accessed via a PC equipped with Com-  
fort Works, Building Supervisor, or Service Tool, the fol-  
lowing features can be accessed:  
• on-board timeclock can be programmed  
• occupancy schedules can be programmed  
• unit set points can be changed  
• alarms can be monitored  
This access is available on the base control board via a  
RJ-11 phone jack or a 3-wire connection to the communi-  
cation bus. See Fig. 12. The timeclock has a 10-hour minimum  
back-up time to provide for unit power off for servicing unit  
NOTE: On units running Version 1.0 of the Unit Control Software, the remote  
start/stop switch is connected to R and Y1. On units running Version 2.0 of the  
Unit Control Software, the remote start/stop switch is connected to R and W1.  
Fig. 11 — Field Control Remote Start/Stop  
13  
14  
For units running Version 1.0 of the unit control software,  
network access software is required to enable occupied heat-  
ing. For units running Version 2.0 of the unit control soft-  
ware, occupied heating is enabled or disabled by the posi-  
tion of DIP switch no. 5.  
Additional features may be provided with electronic ac-  
cess to Unit Control Board. These features are:  
• control board diagnostics  
• compressor time guard override (power up, minimum off  
and on times)  
• compressor lockout during low supply-air temperature  
• electronic expansion board features (if installed)  
• field test capability  
• control of the economizer damper and indoor fan to op-  
tion unoccupied free cooling  
• 365 day timeclock with backup (supports minute, hour, day,  
month, and year)  
an occupancy schedule, the unit will control to the unoccu-  
pied default set points of 90 F (return air) cooling and 55 F  
(return air) heating (if electric heat is installed).  
Features with NetworkApplications — The base control board  
provides, as standard, a connection for use with a Carrier  
Comfort System and can also be integrated into a Carrier  
Comfort Network. When the unit is accessed via a PC equipped  
with Comfort Works, Building Supervisor, or Service Tool  
software, the following features can be accessed:  
• on-board timeclock can be programmed  
• occupancy schedules can be programmed  
• unit set points can be changed  
• alarms can be monitored  
This access is available on the base control board via a  
RJ-11 phone jack or a 3-wire connection to the communi-  
cation bus. See Fig. 12. The timeclock has a 10-hour mini-  
mum back-up time to provide for unit power off for servic-  
ing unit or during unexpected power outages. For complete  
Carrier Comfort System (CCS) or Carrier Comfort Network  
(CCN) features and benefits, refer to the product literature.  
• holiday table containing up to 18 holiday schedules  
• occupancy control with 8 periods for unit operation  
• support a set of display, maintenance, configuration, serv-  
ice, and set point data tables for interface with Building  
Supervisor, Comfort Works, or Service Tool  
Step 7 — Make Electrical Connections  
When a VAV unit with a space temperature sensor is ac-  
cessed via a computer, the following additional features are  
available:  
• ability to initiate timed override from T-55 sensors  
• ability to use multiple space temperature sensors to aver-  
age space temperature  
• temperature compensated start to calculate early start time  
before occupancy  
POWER WIRING — Units are factory wired for the voltage  
shown on the unit nameplate. The main terminal block is  
suitable for use with aluminum or copper wires and is sized  
for single-point electric heat.  
When installing units, provide a disconnect per NEC (Na-  
tional Electrical Code) of adequate size (MOCP [maximum  
overcurrent protection] of unit is on the informative plate).  
All field wiring must comply with NEC and all local codes.  
Size wire based on MCA (minimum circuit amps) on the  
unit informative plate. See Fig. 13 for power wiring con-  
nections to the unit power terminal block and equipment ground.  
The main power terminal block is suitable for use with  
aluminum or copper wire. See Fig. 13. Units have circuit  
breakers for compressors, fan motors, and control circuit. If  
required by local codes, provide an additional disconnect,  
per NEC and local codes requirements, of adequate size  
(Table 4). Whenever external electrical sources are used, unit  
must be electrically grounded in accordance with local codes,  
or in absence of local codes, with NEC, ANSI (American  
National Standards Institute) C1-latest year.  
• provide space temperature reset to reset the supply air set  
point upward when the temperature falls below the occu-  
pied cooling set point  
An electronic expansion board may be field-installed to  
provide the following features:  
• fan status  
• filter status  
• field-applied status  
• demand limiting  
• IAQ sensor  
• OAQ sensor  
• alarm light  
When the unit is connected to the CCN (Carrier Comfort  
Network), the following expansion board features can be  
utilized:  
All field wiring must comply with NEC and local code  
requirements.  
FIELD POWER SUPPLY — Unit is factory wired for volt-  
age shown on nameplate. See Table 4 for electrical data.  
Field wiring can be brought into the unit from bottom  
(through basepan and roof curb) or through side of unit (cor-  
ner post next to control box).  
• CCN IAQ (indoor air quality) participation  
• CCN OAQ (outdoor air quality) participation  
• CCN demand limit participation  
• fire unit shutdown  
• fire pressurization  
• fire evacuation  
• fire smoke purge  
• modulated power exhaust override  
A field-supplied space temperature sensor can be added to  
provide the following:  
• T-57 sensor will monitor room temperature  
• T-55 sensor will monitor room temperature and provide  
unoccupied override capability (1 hour)  
When the unit is equipped with a field-supplied space tem-  
perature sensor and a remote contact closure (remote start/  
stop), the occupied default set points will monitor unit op-  
eration. The occupied default set points are 55 F (supply air)  
cooling and 68 F (space temperature) heating (if electric heat  
is installed). See Fig. 11 for remote start/stop wiring.  
LEGEND  
NOTE: For units without a space temperature sensor and which  
have not had the base unit control board accessed via soft-  
ware to set an occupancy schedule, the remote start/stop clo-  
sure will allow the unit to operate in the pre-configured oc-  
cupied default set points of 55 F (supply-air temperature)  
cooling and 68 F (return-air temperature) heating. Without  
EQUIP  
GND  
NEC  
TB  
Equipment  
Ground  
National Electrical Code  
Terminal Block  
NOTE: Maximum wire size for TB1 is 500 MCM.  
Fig. 13 — Field Power Wiring Connections  
15  
A 312-in. NPT coupling for field power wiring and a  
4-in. NPT coupling for 24-v control wiring are provided in  
3
basepan. In the side post, there are two 212-in. (024-034) or  
3-in. (038-048) knockouts for the field power wiring. See  
Fig. 3-6. If control wiring is to be brought in through the  
7
side of unit, a 8-in. diameter hole is provided in the con-  
Table 4 — Electrical Data — 50EJ,EK,EW,EY024-048  
COMPRESSOR  
No. 1 No. 2  
VOLTAGE  
RANGE  
POWER  
ELECTRIC  
HEAT*  
NOMINAL  
VOLTAGE  
(3 Ph 60 Hz)  
OFM  
IFM  
FLA  
POWER SUPPLY  
UNIT  
SIZE  
EXHAUST  
Min  
Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp  
FLA LRA  
kW  
FLA  
MCA  
MOCP†  
23.6  
41.6  
101.8/100.3 125/125  
125.4/123.9 150/150  
16.7/  
15.2  
23.6  
41.6  
29/36  
29/36  
75.1/ 86.6  
114.7/127.3  
125/150  
5
75.1/ 86.6 144.2/156.8 150/175  
23.6  
41.6  
59/72 150.1/173.2 171.0/192.2 200/225  
59/72 150.1/173.2 200.5/221.7 225/225  
23.6  
41.6  
115.9/113.1  
150/150  
139.5/136.7 175/175  
30.8/  
28.0  
29/36  
29/36  
75.1/ 86.6 132.3/143.3 150/150  
75.1/ 86.6 161.8/172.8 175/175  
208/230  
187  
254  
508  
632  
39.1  
19.9  
16.0  
228  
114  
91  
25.6  
11.5  
9.6  
160  
2
2
2
1
1
1
5.3  
2.7  
2.4  
10  
15  
5
23.6  
41.6  
23.6  
41.6  
59/72 150.1/173.2 188.6/208.2 220/225  
59/72 150.1/173.2 218.1/237.7 250/250  
23.6  
41.6  
131.3/127.1 150/150  
154.9/150.7 175/175  
46.2/  
42.0  
23.6  
41.6  
29/36  
29/36  
75.1/ 86.6 151.6/160.8 175/175  
75.1/ 86.6 181.1/190.3 200/200  
23.6  
41.6  
59/72 150.1/173.2 207.9/225.7 250/250  
59/72 150.1/173.2 237.4/255.2 275/275  
12.6  
23.6  
49.4  
62.0  
60  
80  
12.6  
23.6  
36  
36  
43.3  
43.3  
63.6  
79.4  
70  
80  
7.6  
14  
21  
6.1  
11  
12.6  
23.6  
72  
72  
86.6  
86.6  
96.1  
111.9  
110  
125  
12.6  
23.6  
55.8  
68.4  
70  
80  
12.6  
23.6  
36  
36  
43.3  
43.3  
71.6  
87.4  
80  
90  
024  
460  
414  
80  
10  
15  
5
12.6  
23.6  
72  
72  
86.6  
86.6  
104.1  
119.9  
110  
125  
12.6  
23.6  
62.8  
75.4  
80  
90  
12.6  
23.6  
36  
36  
43.3  
43.3  
80.4  
96.1  
90  
100  
12.6  
23.6  
72  
72  
86.6  
86.6  
112.9  
128.6  
125  
150  
12.6  
23.6  
40.5  
53.1  
50  
60  
12.6  
23.6  
36  
36  
34.6  
34.6  
50.9  
66.7  
60  
70  
12.6  
23.6  
72  
72  
69.3  
69.3  
76.9  
92.7  
80  
100  
12.6  
23.6  
45.4  
58.0  
60  
70  
12.6  
23.6  
36  
36  
34.6  
34.6  
57.1  
72.8  
60  
80  
575  
518  
64  
10  
15  
12.6  
23.6  
72  
72  
69.3  
69.3  
83.0  
98.8  
90  
100  
12.6  
23.6  
51.4  
64.0  
60  
80  
12.6  
23.6  
36  
36  
34.6  
34.6  
64.6  
80.3  
70  
90  
17  
12.6  
23.6  
72  
72  
69.3  
69.3  
90.5  
106.3  
100  
110  
Determine maximum deviation from average voltage.  
LEGEND  
Full Load Amps  
(AB) 457 − 452 = 5 v  
(BC) 464 − 457 = 7 v  
(AC) 457 − 455 = 2 v  
FLA  
HACR  
IFM  
Heating, Air Conditioning and Refrigeration  
Indoor (Evaporator) Fan Motor  
Locked Rotor Amps  
LRA  
Maximum deviation is 7 v.  
MCA  
MOCP  
NEC  
OFM  
RLA  
Minimum Circuit Amps  
Maximum Overcurrent Protection  
National Electrical Code  
Determine percent of voltage imbalance.  
7
% Voltage Imbalance = 100 x  
Outdoor (Condenser) Fan Motor  
Rated Load Amps  
457  
= 1.53%  
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v.  
If power distribution voltage to unit varies from rated heater voltage, heater kW will  
vary accordingly.  
This amount of phase imbalance is satisfactory as it is below the maximum  
allowable 2%.  
†Fuse or HACR circuit breaker.  
IMPORTANT: If the supply voltage phase imbalance is more than 2%,  
contact your local electric utility company immediately.  
NOTES:  
1. In compliance with NEC requirements for multimotor and combination load equip-  
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the  
unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit  
breaker.  
3. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps) +  
(1.00 x heater FLA).  
2. Unbalanced 3-Phase Supply Voltage  
Never operate a motor where a phase imbalance in supply voltage is greater than  
2%. Use the following formula to determine the percent of voltage imbalance.  
max voltage deviation from average voltage  
% Voltage Imbalance = 100 x  
average voltage  
EXAMPLE: Supply voltage is 460-3-60.  
AB = 452 v  
BC = 464 v  
AC = 455 v  
452 + 464 + 455  
Average Voltage =  
3
1371  
=
3
=
457  
17  
Table 4 — Electrical Data — 50EJ,EK,EW,EY024-048 (cont)  
COMPRESSOR  
No. 1 No. 2  
VOLTAGE  
RANGE  
POWER  
ELECTRIC  
HEAT*  
NOMINAL  
VOLTAGE  
(3 Ph 60 Hz)  
OFM  
IFM  
FLA  
POWER SUPPLY  
UNIT  
SIZE  
EXHAUST  
Min  
Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp  
FLA LRA  
kW  
FLA  
MCA  
MOCP†  
23.6  
41.6  
122.8/120.6 150/150  
146.4/144.2 175/175  
24.2/  
22.0  
23.6  
41.6  
29/36  
29/36  
75.1/ 86.6 124.1/135.8 150/150  
75.1/ 86.6 153.6/165.3 175/175  
7.5  
23.6  
41.6  
59/72 150.1/173.2 180.4/200.7 200/225  
59/72 150.1/173.2 209.9/230.2 225/250  
23.6  
41.6  
129.4/126.6 150/150  
153.0/150.2 175/175  
30.8/  
28.0  
29/36  
29/36  
75.1/ 86.6 132.3/143.3 150/150  
75.1/ 86.6 161.8/172.8 175/175  
208/230  
187  
254  
508  
632  
39.1  
19.9  
16.0  
228  
114  
91  
39.1  
19.9  
16.0  
228  
114  
91  
2
2
2
1
1
1
5.3  
2.7  
2.4  
10  
15  
7.5  
10  
15  
7.5  
10  
15  
23.6  
41.6  
23.6  
41.6  
59/72 150.1/173.2 188.6/208.2 200/225  
59/72 150.1/173.2 218.1/237.7 225/250  
23.6  
41.6  
144.8/140.6 175/175  
168.4/164.2 200/200  
46.2/  
42.0  
23.6  
41.6  
29/36  
29/36  
75.1/ 86.6 151.6/160.8 175/175  
75.1/ 86.6 181.1/190.3 200/200  
23.6  
41.6  
59/72 150.1/173.2 207.9/225.7 250/250  
59/72 150.1/173.2 237.4/255.2 275/275  
12.6  
23.6  
61.2  
73.8  
80  
90  
12.6  
23.6  
36  
36  
43.3  
43.3  
67.9  
83.6  
70  
90  
11  
14  
21  
9
12.6  
23.6  
72  
72  
86.6  
86.6  
100.4  
116.1  
110  
125  
12.6  
23.6  
64.2  
76.8  
80  
90  
12.6  
23.6  
36  
36  
43.3  
43.3  
71.6  
87.4  
80  
90  
028  
460  
414  
12.6  
23.6  
72  
72  
86.6  
86.6  
104.1  
119.9  
110  
125  
12.6  
23.6  
71.2  
83.8  
90  
100  
12.6  
23.6  
36  
36  
43.3  
43.3  
80.4  
96.1  
90  
100  
12.6  
23.6  
72  
72  
86.6  
86.6  
112.9  
128.6  
125  
150  
12.6  
23.6  
49.8  
62.4  
60  
70  
12.6  
23.6  
36  
36  
34.6  
34.6  
54.6  
70.3  
60  
80  
12.6  
23.6  
72  
72  
69.3  
69.3  
80.5  
96.3  
90  
100  
12.6  
23.6  
51.8  
64.4  
60  
80  
12.6  
23.6  
36  
36  
34.6  
34.6  
57.1  
72.8  
60  
80  
575  
518  
11  
17  
12.6  
23.6  
72  
72  
69.3  
69.3  
83.0  
98.8  
90  
100  
12.6  
23.6  
57.8  
70.4  
70  
80  
12.6  
23.6  
36  
36  
34.6  
34.6  
64.6  
80.3  
70  
90  
12.6  
23.6  
72  
72  
69.3  
69.3  
90.5  
106.3  
100  
110  
18  
Table 4 — Electrical Data — 50EJ,EK,EW,EY024-048 (cont)  
COMPRESSOR  
No. 1 No. 2  
VOLTAGE  
RANGE  
POWER  
ELECTRIC  
HEAT*  
NOMINAL  
VOLTAGE  
(3 Ph 60 Hz)  
OFM  
IFM  
FLA  
POWER SUPPLY  
UNIT  
SIZE  
EXHAUST  
Min  
Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp  
FLA LRA  
kW  
FLA  
MCA  
MOCP†  
23.6  
41.6  
151.9/149.1 200/200  
175.5/172.7 225/225  
30.8/  
28.0  
23.6  
41.6  
29/36  
29/36  
75.1/ 86.6 151.9/149.1 200/200  
75.1/ 86.6 175.5/172.8 225/225  
10  
23.6  
41.6  
59/72 150.1/173.2 188.6/208.2 200/225  
59/72 150.1/173.2 218.1/237.7 225/250  
23.6  
41.6  
167.3/163.1 200/200  
190.9/186.7 225/225  
46.2/  
42.0  
29/36  
29/36  
75.1/ 86.6 167.3/163.1 200/200  
75.1/ 86.6 190.9/186.7 225/225  
208/230  
187  
254  
508  
632  
57.1  
25.6  
20.5  
266  
120  
96  
39.1  
19.9  
16.0  
228  
114  
91  
2
2
2
1
1
1
5.3  
2.7  
2.4  
15  
20  
10  
15  
20  
10  
15  
20  
23.6  
41.6  
23.6  
41.6  
59/72 150.1/173.2 207.9/225.7 250/250  
59/72 150.1/173.2 237.4/255.2 275/275  
23.6  
41.6  
180.5/175.1 225/225  
204.1/198.7 250/250  
59.4/  
54.0  
23.6  
41.6  
29/36  
29/36  
75.1/ 86.6 180.5/175.1 225/225  
75.1/ 86.6 204.1/198.7 250/250  
23.6  
41.6  
59/72 150.1/173.2 224.4/240.7 275/275  
59/72 150.2/173.2 253.9/270.2 300/300  
12.6  
23.6  
71.3  
83.9  
90  
100  
12.6  
23.6  
36  
36  
43.3  
43.3  
71.6  
87.4  
90  
100  
14  
21  
27  
11  
17  
22  
12.6  
23.6  
72  
72  
86.6  
86.6  
104.1  
119.9  
110  
125  
12.6  
23.6  
78.3  
90.9  
100  
110  
12.6  
23.6  
36  
36  
43.3  
43.3  
80.4  
96.1  
100  
110  
030  
460  
414  
12.6  
23.6  
72  
72  
86.6  
86.6  
112.9  
128.6  
125  
150  
12.6  
23.6  
84.3  
96.9  
100  
110  
12.6  
23.6  
36  
36  
43.3  
43.3  
87.9  
103.6  
100  
110  
12.6  
23.6  
72  
72  
86.6  
86.6  
120.4  
136.1  
125  
150  
12.6  
23.6  
57.4  
70.0  
70  
90  
12.6  
23.6  
36  
36  
34.6  
34.6  
57.4  
72.8  
70  
90  
12.6  
23.6  
72  
72  
69.3  
69.3  
83.0  
98.8  
90  
100  
12.6  
23.6  
63.4  
76.0  
80  
90  
12.6  
23.6  
36  
36  
34.6  
34.6  
64.6  
80.3  
80  
90  
575  
518  
12.6  
23.6  
72  
72  
69.3  
69.3  
90.5  
106.3  
100  
110  
12.6  
23.6  
68.4  
81.0  
80  
100  
12.6  
23.6  
36  
36  
34.6  
34.6  
70.8  
86.6  
80  
100  
12.6  
23.6  
72  
72  
69.3  
69.3  
96.8  
112.5  
110  
125  
Determine maximum deviation from average voltage.  
LEGEND  
Full Load Amps  
(AB) 457 − 452 = 5 v  
(BC) 464 − 457 = 7 v  
(AC) 457 − 455 = 2 v  
FLA  
HACR  
IFM  
Heating, Air Conditioning and Refrigeration  
Indoor (Evaporator) Fan Motor  
Locked Rotor Amps  
LRA  
Maximum deviation is 7 v.  
MCA  
MOCP  
NEC  
OFM  
RLA  
Minimum Circuit Amps  
Maximum Overcurrent Protection  
National Electrical Code  
Determine percent of voltage imbalance.  
7
% Voltage Imbalance = 100 x  
Outdoor (Condenser) Fan Motor  
Rated Load Amps  
457  
= 1.53%  
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v.  
If power distribution voltage to unit varies from rated heater voltage, heater kW will  
vary accordingly.  
This amount of phase imbalance is satisfactory as it is below the maximum  
allowable 2%.  
†Fuse or HACR circuit breaker.  
IMPORTANT: If the supply voltage phase imbalance is more than 2%,  
contact your local electric utility company immediately.  
NOTES:  
1. In compliance with NEC requirements for multimotor and combination load equip-  
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the  
unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit  
breaker.  
3. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps) +  
(1.00 x heater FLA).  
2. Unbalanced 3-Phase Supply Voltage  
Never operate a motor where a phase imbalance in supply voltage is greater than  
2%. Use the following formula to determine the percent of voltage imbalance.  
max voltage deviation from average voltage  
% Voltage Imbalance = 100 x  
average voltage  
EXAMPLE: Supply voltage is 460-3-60.  
AB = 452 v  
BC = 464 v  
AC = 455 v  
452 + 464 + 455  
Average Voltage =  
3
1371  
=
3
=
457  
19  
Table 4 — Electrical Data — 50EJ,EK,EW,EY024-048 (cont)  
COMPRESSOR  
No. 1 No. 2  
VOLTAGE  
RANGE  
POWER  
ELECTRIC  
HEAT*  
NOMINAL  
VOLTAGE  
(3 Ph 60 Hz)  
OFM  
IFM  
FLA  
POWER SUPPLY  
UNIT  
SIZE  
EXHAUST  
Min  
Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp  
FLA LRA  
kW  
FLA  
MCA  
MOCP†  
23.6  
41.6  
169.9/167.1 225/200  
193.5/190.7 250/225  
30.8/  
28.0  
23.6  
41.6  
29/36  
29/36  
75.1/ 86.6 169.9/167.1 225/200  
75.1/ 86.6 193.5/190.7 250/225  
10  
23.6  
41.6  
59/72 150.1/173.2 188.6/208.2 225/225  
59/72 150.1/173.2 218.1/237.7 250/250  
23.6  
41.6  
185.3/181.1 225/225  
208.9/204.7 250/250  
46.2/  
42.0  
29/36  
29/36  
75.1/ 86.6 185.3/181.1 225/225  
75.1/ 86.6 208.9/204.7 250/250  
208/230  
187  
254  
57.1  
266  
57.1  
266  
2
1
5.3  
15  
20  
10  
15  
20  
23.6  
41.6  
23.6  
41.6  
59/72 150.1/173.2 207.9/225.7 250/250  
59/72 150.1/173.2 237.4/255.2 275/275  
23.6  
41.6  
198.5/193.1 250/250  
222.1/216.7 275/250  
59.4/  
54.0  
23.6  
41.6  
29/36  
29/36  
75.1/ 86.6 198.5/193.1 250/250  
75.1/ 86.6 222.1/216.7 275/250  
23.6  
41.6  
59/72 150.1/173.2 224.4/240.7 275/275  
59/72 150.1/173.2 253.9/270.2 300/300  
12.6  
23.6  
77.0  
89.6  
100  
110  
12.6  
23.6  
36  
36  
43.3  
43.3  
77.0  
89.6  
100  
110  
14  
21  
27  
12.6  
23.6  
72  
72  
86.6  
86.6  
104.1  
119.9  
110  
125  
12.6  
23.6  
84.0  
96.6  
100  
110  
12.6  
23.6  
36  
36  
43.3  
43.3  
84.0  
96.6  
100  
110  
034  
460  
414  
508  
25.6  
120  
25.6  
120  
2
1
2.7  
12.6  
23.6  
72  
72  
86.6  
86.6  
112.9  
128.6  
125  
150  
90.0  
110  
Table 4 — Electrical Data — 50EJ,EK,EW,EY024-048 (cont)  
COMPRESSOR  
No. 1 No. 2  
VOLTAGE  
RANGE  
POWER  
ELECTRIC  
HEAT*  
NOMINAL  
VOLTAGE  
(3 Ph 60 Hz)  
OFM  
IFM  
FLA  
POWER SUPPLY  
UNIT  
SIZE  
EXHAUST  
Min  
Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp  
FLA LRA  
kW  
FLA  
MCA  
MOCP†  
23.6  
41.6  
180.5/177.7 225/225  
204.1/201.3 250/250  
30.8/  
28.0  
23.6  
41.6  
29/36  
29/36  
75.1/ 86.6 180.5/177.7 225/225  
75.1/ 86.6 204.1/201.3 250/250  
10  
23.6  
41.6  
59/72 150.1/173.2 188.6/208.2 225/225  
59/72 150.1/173.2 218.1/237.7 250/250  
23.6  
41.6  
195.9/191.7 250/225  
219.5/215.3 275/250  
46.2/  
42.0  
29/36  
29/36  
75.1/ 86.6 195.9/191.7 250/225  
75.1/ 86.6 219.5/215.3 275/250  
208/230  
187  
254  
508  
632  
57.1  
25.6  
20.5  
266  
120  
96  
57.1  
25.6  
20.5  
266  
120  
96  
4
4
4
1
1
1
5.3  
2.7  
2.4  
15  
20  
10  
15  
20  
10  
15  
20  
23.6  
41.6  
23.6  
41.6  
59/72 150.1/173.2 207.9/225.7 250/250  
59/72 150.1/173.2 237.4/255.2 275/275  
23.6  
41.6  
209.1/203.7 250/250  
232.7/227.3 275/275  
59.4/  
54.0  
23.6  
41.6  
29/36  
29/36  
75.1/ 86.6 209.1/203.7 250/250  
75.1/ 86.6 232.7/227.3 275/275  
23.6  
41.6  
59/72 150.1/173.2 224.4/240.7 275/275  
59/72 150.1/173.2 253.9/270.2 300/300  
12.6  
23.6  
82.4  
95.0  
100  
110  
12.6  
23.6  
36  
36  
43.3  
43.3  
82.4  
95.0  
100  
110  
14  
21  
27  
11  
17  
22  
12.6  
23.6  
72  
72  
86.6  
86.6  
104.1  
119.9  
110  
125  
12.6  
23.6  
89.4  
102.0  
110  
125  
12.6  
23.6  
36  
36  
43.3  
43.3  
89.4  
102.0  
110  
125  
038  
460  
414  
12.6  
23.6  
72  
72  
86.6  
86.6  
112.9  
128.6  
125  
150  
12.6  
23.6  
95.4  
108.0  
110  
125  
12.6  
23.6  
36  
36  
43.3  
43.3  
95.4  
108.0  
110  
125  
12.6  
23.6  
72  
72  
86.6  
86.6  
120.4  
136.1  
125  
150  
12.6  
23.6  
66.7  
79.3  
80  
90  
12.6  
23.6  
36  
36  
34.6  
34.6  
66.7  
79.3  
80  
90  
12.6  
23.6  
72  
72  
69.3  
69.3  
83.0  
98.8  
90  
100  
12.6  
23.6  
72.7  
85.3  
90  
100  
12.6  
23.6  
36  
36  
34.6  
34.6  
72.7  
85.3  
80  
100  
575  
518  
12.6  
23.6  
72  
72  
69.3  
69.3  
90.5  
106.3  
100  
110  
12.6  
23.6  
77.7  
90.3  
90  
110  
12.6  
23.6  
36  
36  
34.6  
34.6  
77.7  
90.3  
90  
110  
12.6  
23.6  
72  
72  
69.3  
69.3  
96.8  
112.5  
110  
125  
Determine maximum deviation from average voltage.  
LEGEND  
Full Load Amps  
(AB) 457 − 452 = 5 v  
(BC) 464 − 457 = 7 v  
(AC) 457 − 455 = 2 v  
FLA  
HACR  
IFM  
Heating, Air Conditioning and Refrigeration  
Indoor (Evaporator) Fan Motor  
Locked Rotor Amps  
LRA  
Maximum deviation is 7 v.  
MCA  
MOCP  
NEC  
OFM  
RLA  
Minimum Circuit Amps  
Maximum Overcurrent Protection  
National Electrical Code  
Determine percent of voltage imbalance.  
7
% Voltage Imbalance = 100 x  
Outdoor (Condenser) Fan Motor  
Rated Load Amps  
457  
= 1.53%  
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v.  
If power distribution voltage to unit varies from rated heater voltage, heater kW will  
vary accordingly.  
This amount of phase imbalance is satisfactory as it is below the maximum  
allowable 2%.  
†Fuse or HACR circuit breaker.  
IMPORTANT: If the supply voltage phase imbalance is more than 2%,  
contact your local electric utility company immediately.  
NOTES:  
1. In compliance with NEC requirements for multimotor and combination load equip-  
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the  
unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit  
breaker.  
3. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps) +  
(1.00 x heater FLA).  
2. Unbalanced 3-Phase Supply Voltage  
Never operate a motor where a phase imbalance in supply voltage is greater than  
2%. Use the following formula to determine the percent of voltage imbalance.  
max voltage deviation from average voltage  
% Voltage Imbalance = 100 x  
average voltage  
EXAMPLE: Supply voltage is 460-3-60.  
AB = 452 v  
BC = 464 v  
AC = 455 v  
452 + 464 + 455  
Average Voltage =  
3
1371  
=
3
=
457  
21  
Table 4 — Electrical Data — 50EJ,EK,EW,EY024-048 (cont)  
COMPRESSOR  
No. 1 No. 2  
VOLTAGE  
RANGE  
POWER  
ELECTRIC  
HEAT*  
NOMINAL  
VOLTAGE  
(3 Ph 60 Hz)  
OFM  
IFM  
FLA  
POWER SUPPLY  
UNIT  
SIZE  
EXHAUST  
Min  
Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp  
FLA LRA  
kW  
FLA  
MCA  
MOCP†  
23.6  
41.6  
223.1/218.9 275/275  
246.7/242.5 300/300  
46.2/  
42.0  
23.6  
41.6  
29/36  
29/36  
75.1/ 86.6 223.1/218.9 275/275  
75.1/ 86.6 246.7/242.5 300/300  
15  
23.6  
41.6  
59/72 150.1/173.2 223.1/225.7 275/275  
59/72 150.1/173.2 246.7/255.2 300/300  
23.6  
41.6  
236.3/230.9 300/300  
259.9/254.5 300/300  
59.4/  
54.0  
29/36  
29/36  
75.1/ 86.6 236.3/230.9 300/300  
75.1/ 86.6 259.9/254.5 300/300  
208/230  
187  
254  
508  
632  
69.2  
28.8  
26.7  
345  
173  
120  
69.2  
28.8  
26.7  
345  
173  
120  
4
4
4
1
1
1
5.3  
2.7  
2.4  
20  
25  
15  
20  
25  
15  
20  
25  
23.6  
41.6  
23.6  
41.6  
59/72 150.1/173.2 236.3/240.7 300/300  
59/72 150.1/173.2 259.9/270.2 300/300  
23.6  
41.6  
251.7/244.9 300/300  
275.3/268.5 300/300  
74.8/  
68.0  
23.6  
41.6  
29/36  
29/36  
75.1/ 86.6 251.7/244.9 300/300  
75.1/ 86.6 275.3/268.5 300/300  
23.6  
41.6  
59/72 150.1/173.2 251.7/258.2 300/300  
59/72 150.2/173.2 275.3/287.7 300/300  
12.6  
23.6  
96.6  
109.2  
125  
125  
12.6  
23.6  
36  
36  
43.3  
43.3  
96.6  
109.2  
125  
125  
21  
27  
34  
17  
22  
27  
12.6  
23.6  
72  
72  
86.6  
86.6  
112.9  
128.6  
125  
150  
12.6  
23.6  
102.6  
115.2  
125  
125  
12.6  
23.6  
36  
36  
43.3  
43.3  
102.6  
115.2  
125  
125  
044  
460  
414  
12.6  
23.6  
72  
72  
86.6  
86.6  
120.4  
136.1  
150  
150  
12.6  
23.6  
109.6  
122.2  
125  
150  
12.6  
23.6  
36  
36  
43.3  
43.3  
109.6  
122.2  
125  
150  
12.6  
23.6  
72  
72  
86.6  
86.6  
129.1  
144.9  
150  
175  
12.6  
23.6  
86.7  
99.3  
110  
125  
12.6  
23.6  
36  
36  
34.6  
34.6  
86.7  
99.3  
110  
125  
12.6  
23.6  
72  
72  
69.3  
69.3  
91.4  
106.3  
110  
125  
12.6  
23.6  
91.7  
104.3  
110  
125  
12.6  
23.6  
36  
36  
34.6  
34.6  
91.7  
104.3  
110  
125  
575  
518  
12.6  
23.6  
72  
72  
69.3  
69.3  
96.8  
112.5  
125  
125  
12.6  
23.6  
96.7  
109.3  
110  
125  
12.6  
23.6  
36  
36  
34.6  
34.6  
96.7  
109.3  
110  
125  
12.6  
23.6  
72  
72  
69.3  
69.3  
103.0  
118.8  
125  
125  
22  
Table 3 — Electrical Data — 50EJ,EK,EW,EY024-048 (cont)  
COMPRESSOR  
No. 1 No. 2  
VOLTAGE  
RANGE  
POWER  
ELECTRIC  
HEAT*  
NOMINAL  
VOLTAGE  
(3 Ph 60 Hz)  
OFM  
IFM  
FLA  
POWER SUPPLY  
UNIT  
SIZE  
EXHAUST  
Min  
Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp  
FLA LRA  
kW  
FLA  
MCA  
MOCP†  
23.6  
41.6  
252.4/247.0 300/300  
276.0/270.6 300/300  
59.4/  
54.0  
23.6  
41.6  
29/36  
29/36  
75.1/ 86.6 252.4/247.0 300/300  
75.1/ 86.6 276.0/270.6 300/300  
20  
23.6  
41.6  
59/72 150.1/173.2 252.4/247.0 300/300  
59/72 150.1/173.2 276.0/270.6 300/300  
23.6  
41.6  
267.8/261.0 300/300  
291.4/284.6 300/300  
74.8/  
68.0  
29/36  
29/36  
75.1/ 86.6 267.8/261.0 300/300  
75.1/ 86.6 291.4/284.6 300/300  
208/230  
187  
254  
508  
632  
82.1  
42.3  
34.6  
446  
223  
164  
69.2  
28.8  
26.7  
345  
173  
120  
4
4
4
1
1
1
5.3  
2.7  
2.4  
25  
30  
20  
25  
30  
20  
25  
30  
23.6  
41.6  
23.6  
41.6  
59/72 150.1/173.2 267.8/261.0 300/300  
59/72 150.1/173.2 291.4/284.6 300/300  
23.6  
41.6  
281.0/273.0 300/300  
304.6/296.6 350/300  
88.0/  
80.0  
23.6  
41.6  
29/36  
29/36  
75.1/ 86.6 281.0/273.0 300/300  
75.1/ 86.6 304.6/296.6 350/300  
23.6  
41.6  
59/72 150.1/173.2 281.0/273.0 300/300  
59/72 150.2/173.2 304.6/296.6 350/300  
12.6  
23.6  
119.5  
132.1  
150  
150  
12.6  
23.6  
36  
36  
43.3  
43.3  
119.5  
132.1  
150  
150  
27  
34  
40  
22  
27  
32  
12.6  
23.6  
72  
72  
86.6  
86.6  
120.4  
136.1  
150  
150  
12.6  
23.6  
126.5  
139.1  
150  
175  
12.6  
23.6  
36  
36  
43.3  
43.3  
126.5  
139.1  
150  
175  
048  
460  
414  
12.6  
23.6  
72  
72  
86.6  
86.6  
129.1  
144.9  
150  
175  
12.6  
23.6  
132.5  
145.1  
150  
175  
12.6  
23.6  
36  
36  
43.3  
43.3  
132.5  
145.1  
150  
175  
12.6  
23.6  
72  
72  
86.6  
86.6  
136.6  
152.4  
175  
175  
12.6  
23.6  
101.6  
114.2  
125  
125  
12.6  
23.6  
36  
36  
34.6  
34.6  
101.6  
114.2  
125  
125  
12.6  
23.6  
72  
72  
69.3  
69.3  
101.6  
114.2  
125  
125  
12.6  
23.6  
106.6  
119.2  
125  
150  
12.6  
23.6  
36  
36  
34.6  
34.6  
106.6  
119.2  
125  
150  
575  
518  
12.6  
23.6  
72  
72  
69.3  
69.3  
106.6  
119.2  
125  
150  
12.6  
23.6  
111.6  
124.2  
125  
150  
12.6  
23.6  
36  
36  
34.6  
34.6  
111.6  
124.2  
125  
150  
12.6  
23.6  
72  
72  
69.3  
69.3  
111.6  
124.2  
125  
150  
Determine maximum deviation from average voltage.  
LEGEND  
Full Load Amps  
(AB) 457 − 452 = 5 v  
(BC) 464 − 457 = 7 v  
(AC) 457 − 455 = 2 v  
FLA  
HACR  
IFM  
Heating, Air Conditioning and Refrigeration  
Indoor (Evaporator) Fan Motor  
Locked Rotor Amps  
LRA  
Maximum deviation is 7 v.  
MCA  
MOCP  
NEC  
OFM  
RLA  
Minimum Circuit Amps  
Maximum Overcurrent Protection  
National Electrical Code  
Determine percent of voltage imbalance.  
7
% Voltage Imbalance = 100 x  
Outdoor (Condenser) Fan Motor  
Rated Load Amps  
457  
= 1.53%  
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v.  
If power distribution voltage to unit varies from rated heater voltage, heater kW will  
vary accordingly.  
This amount of phase imbalance is satisfactory as it is below the maximum  
allowable 2%.  
†Fuse or HACR circuit breaker.  
IMPORTANT: If the supply voltage phase imbalance is more than 2%,  
contact your local electric utility company immediately.  
NOTES:  
1. In compliance with NEC requirements for multimotor and combination load equip-  
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the  
unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit  
breaker.  
3. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps) +  
(1.00 x heater FLA).  
2. Unbalanced 3-Phase Supply Voltage  
Never operate a motor where a phase imbalance in supply voltage is greater than  
2%. Use the following formula to determine the percent of voltage imbalance.  
max voltage deviation from average voltage  
% Voltage Imbalance = 100 x  
average voltage  
EXAMPLE: Supply voltage is 460-3-60.  
AB = 452 v  
BC = 464 v  
AC = 455 v  
452 + 464 + 455  
Average Voltage =  
3
1371  
=
3
=
457  
23  
DIP  
PEC  
Dual In-Line Package  
Power Exhaust Controller  
Fig. 14 — Control Box Diagram (Sizes 024-034)  
DIP  
PEC  
Dual In-Line Package  
Power Exhaust Controller  
Fig. 15 — Control Box Diagram (Sizes 038-048)  
24  
NOTE: On units running Version 1.0 of  
the unit control software, the remote start/  
stop switch is connected to R and Y1.  
Conductors and drain wire must be 20 AWG minimum  
stranded, tinned copper. Individual conductors must be in-  
sulated with PVC, PVC/nylon, vinyl, Teflon, or polyethyl-  
ene. An aluminum/polyester 100% foil shield and an outer  
jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a  
minimum operating temperature range of −20 C to 60 C  
(−4 F to 140 F) is required. Table 5 lists cables that meet the  
requirements.  
Table 5 — CCN Connection Approved  
Shielded Cables  
MANUFACTURER  
Alpha  
CABLE PART NO.  
2413 or 5463  
A22503  
American  
Belden  
8772  
Columbia  
02525  
IMPORTANT: When connecting the CCN communi-  
cation bus to a system element, use a color coding sys-  
tem for the entire network to simplify installation and  
checkout. See Table 6.  
Fig. 16 — Field Control Thermostat Wiring  
Table 6 — Color Code Recommendations  
SIGNAL  
TYPE  
CCN BUS CONDUCTOR  
INSULATION COLOR  
CCN PLUG  
PIN NO.  
Positive (+)  
Ground  
RED  
1
2
3
WHITE  
BLACK  
Negative (−)  
NOTE: Sensor part numbers are  
as follows:  
NOTE: If a cable with a different color scheme is selected,  
a similar color code should be adopted for the entire network.  
T55 — HH51BX001  
T56 — HH51BX004  
T57 — CEC01215303-01  
At each system element, the shields of the communica-  
tion bus cables must be tied together. If the communication  
bus is entirely within one building, the resulting continuous  
shield must be connected to a ground at one point only. If  
the communication bus cable exits from one building and  
enters another, the shields must be connected to grounds at  
the lightning suppressor in each building where the cable  
enters or exits the building (one point per building only).  
Fig. 17 — Field Control Temperature  
Sensor Wiring  
To connect the unit to the network:  
1. Turn off power to the control box.  
2. Cut the CCN wire and strip the ends of the red (+), white  
(ground), and black (−) conductors. (If a different  
network color scheme is used, substitute appropriate colors.)  
3. Remove the 3-pin male plug from the base module in the  
main control box, and connect the wires as follows:  
a. Insert and secure the red (+) wire to terminal 1 of the  
3-pin plug.  
Remote Field Control (Units Running Version 2.0 of Unit  
Control Software) — A switch closure across terminals R  
and W1 on TB-3 will initiate the Occupied mode. This can  
be done manually as well as through a field-supplied  
timeclock.  
Service Tool, Building Supervisor, and Comfort Works —  
Access to the control board can be achieved through the ter-  
minal marked CCN via a 3-wire bus.  
b. Insert and secure the white (ground) wire to ter-  
minal 2 of the 3-pin plug.  
c. Insert and secure the black (−) wire to terminal 3 of  
the 3-pin plug.  
4. Insert the plug into the existing 3-pin mating connector  
on the base module in the main control box.  
IMPORTANT: Default bus address is 0. Default ele-  
ment number is 1. Refer to CCN literature for infor-  
mation on network addressing or changing CCN com-  
munication defaults.  
Step 8 — Make Outdoor-Air Inlet Adjustments  
ECONOMIZER  
Carrier Comfort Network Interface — The 50E units can be  
connected to the CCN. The communication bus wiring is sup-  
plied and installed in the field. Wiring consists of shielded,  
3-conductor cable with drain wire.  
NOTE: If accessory power exhaust or barometric relief pack-  
ages are being added to the unit, install power exhaust or  
barometric relief before installing economizer hoods.  
Economizer Hood Assembly — The economizer hood is  
shipped in a package secured to the outside of the unit and  
must be field-assembled. There are 2 hoods on every unit.  
The 50EW/EY units are side supply and side return. The re-  
turn duct limits access to economizer filters from below. Fil-  
ter tracks (mounting angle without tabs) must be installed  
correctly to allow access to economizer filters from each side.  
Perform the following procedure to assemble the econo-  
mizer hood.  
The system elements are connected to the communication  
bus in a daisy chain arrangement. The positive pin of each  
system element communication connector must be wired to  
the positive pins of the system element on either side of it,  
the negative pins must be wired to the negative pins, and the  
signal pins must be wired to signal ground pins. Wiring con-  
nections for CCN should be made at the 3-pin plug (CCN  
located at the base board. Consult CCN literature for further  
information.  
25  
NOTE: Before assembly of the economizer hood, check along  
the outer edges of the economizer assembly for any seal strip  
protruding past the flanges. Trim the excess seal strip so that  
it is flush with the economizer assembly flanges.  
1. Apply black seal strip (provided in package) to outside  
top-edge of hood sides. Wrap seal strip over edge to cover  
top flange (4 hood sides). Make sure seal strip covers  
screw holes. Allow strip to overhang 18-in. past the end  
opposite the mounting flange. See Fig. 18.  
2. Assemble hood sides, top, and cross member with gas-  
keted screws provided. See Fig. 19.  
3. Attach 10 green speed clips (provided) to hood top.  
4. Apply black seal strip (provided) to mounting flanges of  
hood sides being sure to cover mounting holes. See  
Fig. 20.  
NOTE: Each hood assembly has a slotted side that should  
be adjacent to the other hood when mounted to the unit.  
5. Apply black seal strip (provided) to hood top mounting  
flange. Seal strip of hood top mounting flange must press  
tightly against seal strip of hood side mounting flanges.  
See Fig. 21.  
NOTE: Left side economizer hood has mounting angle without tabs and filter  
track assembled end on the opposite side.  
6. Add gray foam strip (provided in package) to cross mem-  
bers on bottom tray. See Fig. 22.  
Fig. 19 — Economizer Hood Assembly  
(Right-Side Economizer Hood Shown)  
7. Place gray foam strip (provided) on inside of slotted hood  
side between filter and cross member opposite the mount-  
ing end. See Fig. 23.  
8. Attach gray foam strip (provided) to block-off baffle on  
outer face of flange. See Fig. 24.  
9. Remove the screws on each end and along top of damper  
assembly of unit. Remove top 2 screws on each side of  
filter panel under damper assembly. Set hood assembly  
in place and attach to unit using these screws.  
10. Attach accessory enthalpy bracket on hood side furthest  
from control box end. Locate bracket on inside upper  
right-hand corner of economizer hood using hood mount-  
ing holes. Mount outdoor-air thermistor to enthalpy bracket  
(if purchased). Attach and wire enthalpy assembly. Place  
quick connects on enthalpy wires.  
MOUNTING  
FLANGE  
HOOD SIDE  
11. Remove screws along bottom of damper assembly. Lo-  
cate and mount blockoff baffle using these screws.  
12. Assemble 2 filter tracks side-by-side with the as-  
sembled ends together.  
13. Attach mounting angle (without tabs) to the assembled  
end of the filter track. See Fig. 25.  
14. Attach 6 green speed clips (provided) to mounting angles.  
Engagement section of clip faces inside of rack.  
Fig. 20 — Adding Seal Strip to  
Mounting Flange of Hood Sides  
TOP  
15. Attach remaining mounting angle (with tabs) to other  
end of the filter track with no. 10 screws provided. See  
Fig. 26.  
16. Place filter track assembly in bottom of hood by placing  
tabbed end into slotted side (with tab on bottom) and  
attaching opposite end to hood with speed clips and gas-  
keted screws provided. Tabs can be hand bent after they  
have been inserted into the side.  
FLANGE  
BLACK  
HOOD SIDE  
SEAL  
STRIP  
NOTE: The filter track assembly end with screws should  
face away from the other hood when mounted on the unit.  
NOTE: Tabs from both filter tracks will be in the same  
space. After one filter track has been inserted into board,  
bend the tabs so they will not interfere with installation  
of the second hood.  
17. Attach black seal strip (provided) to filter cover. Seal  
strip should be applied to the center of the large flange  
making sure to cover holes. See Fig. 27.  
18. Slide two 20 x 25-in. filters into cross members of hood  
assembly. Attach filter cover over filters with screws and  
speed clips provided.  
Fig. 18 — Adding Seal Strip to  
Top of Hood Sides  
26  
HOOD TOP  
HOOD SIDE  
BLOCKOFF BAFFLE  
GRAY FOAM STRIP  
Fig. 21 — Adding Seal Strip to  
Hood Top Mounting Flange  
GRAY FOAM STRIP  
Fig. 24 — Adding Foam Strip to Blockoff Baffle  
CROSS MEMBER  
MOUNTING ANGLE  
(WITHOUT TABS)  
FILTER TRACK  
ASSEMBLY  
Fig. 25 — Mounting Angle (Without Tabs)  
Attached to Filter Track Assembly  
Fig. 22 — Adding Foam Strip to Cross Member  
HOOD SIDE  
(SLOTTED)  
HOOD  
TOP  
MOUNTING ANGLE  
(WITH TABS)  
Fig. 26 — Mounting Angle (With Tabs)  
Attached to Filter Track Assembly  
Fig. 23 — Adding Foam Strip to Hood Side  
27  
position to go to 10% for 30 seconds, then 20% for 30 sec-  
onds, and when it reaches 30% close DIP switch no. 6 dur-  
ing the 30-second period following the 30% position.  
The minimum outdoor air damper position is now set.  
ECONOMIZER SETTINGS  
Minimum Damper Position Setting — Setting of the out-  
door air damper position is performed in conjunction with a  
shortened version of the field-run test. This is performed by  
first opening DIP (Dual In-Line Package) switch no. 6 then  
no. 4. See Fig. 17 and Table 7.  
The outdoor-air damper closes. The control allows 90 sec-  
onds for the damper to close in case it is in the full open  
position. Next, the indoor-fan contactor will energize. The  
outdoor-air damper will remain at 0% for 30 seconds. It will  
then move to the 10% position for another 30 seconds. This  
will be repeated at every 10% increment for 30 seconds until  
the damper reaches 100% open. Close DIP switch no. 6 dur-  
ing the 30 seconds immediately after the desired outdoor air  
minimum damper position. The 30-second time period is to  
allow time where DIP switch no. 6 can be closed. The de-  
fault value of the minimum outdoor air damper position is  
20%. If the desired minimum position is 30%, allow the damper  
Accessory Enthalpy Control (Fig. 28) — The control  
(HH57AC077) is mounted in the economizer hood. See  
Fig. 19. The enthalpy setting adjustment is on the enthalpy  
control. For maximum benefit of outdoor air, set enthalpy  
control to A. See Fig. 29 and 30.  
Accessory Differential Enthalpy Control — The control  
(HH57AC077), in conjunction with the accessory enthalpy  
sensor (HH57AC078), controls economizer operation ac-  
cording to the differential enthalpy. The control is mounted  
in the economizer hood. The sensor is mounted in the return  
duct (50EJ/EK) or return air plenum (50EW/EY).  
BLACK SEAL STRIP  
(CENTERED)  
FILTER COVER  
NOTE: Switches shown in high enthalpy state. Terminals 2 and 3 close on en-  
thalpy decrease.  
Fig. 29 — Wire Connections for Solid State  
Enthalpy Control (HH57AC077)  
CONTROL POINT  
CONTROL  
Fig. 27 — Attaching Seal Strip  
to Filter Cover  
(APPROX. DEG.)  
CURVE  
AT 50% RH  
A
B
C
D
73 (23)  
70 (21)  
67 (19)  
63 (17)  
HH57AC077  
ENTHALPY CONTROL  
HH57AC078  
C7400A1004  
ENTHALPY SENSOR  
+
(USED WITH ENTHALPY  
CONTROL FOR DIFFERENTIAL  
ENTHALPY OPERATION)  
RH  
Relative Humidity  
Fig. 28 — Differential Enthalpy Control  
and Sensor  
Fig. 30 — Psychrometric Chart for  
Enthalpy Control  
28  
4. With screws saved from Step 1, install brackets on each  
side of damper assembly.  
5. Remove tape from damper blades.  
Step 9 — Position Power Exhaust/Barometric  
Relief Damper Hood — All electrical connections have  
been made and adjusted at the factory. The power exhaust  
blowers and barometric relief dampers are shipped as-  
sembled and tilted back into the unit for shipping. Brackets  
and extra screws are shipped in shrink wrap around the damp-  
ers. If ordered, each unit will have 4 power exhaust blowers  
and motors or 4 barometric relief dampers.  
1. Remove 9 screws holding each damper assembly in place.  
See Fig. 31. Each damper assembly is secured with 3 screws  
on each side and 3 screws along the bottom. Save screws.  
VAV DUCT PRESSURE TRANSDUCER — The VAV duct  
pressure transducer (VAV inverter pressure transducer) is lo-  
cated behind the filter access door on the lower inner panel.  
1
See Fig. 32. A section of 4-in. plastic tubing must be run  
from the high-pressure tap on the differential pressure switch  
and connected to a tap in the supply-air duct. The tap is usu-  
ally located 23 of the way out on the main supply duct. Re-  
move plug button in panel to route tubing.  
2. Pivot each damper assembly outward until edges of damper  
assembly rest against inside wall of unit.  
VAV BUILDING PRESSURE TRANSDUCER — The VAV  
building pressure transducer (modulating power exhaust pres-  
sure transducer) is located behind the filter access door on  
1
the inner panel. See Fig. 32. A section of 4-in. plastic tub-  
ing must be run from the high-pressure tap on the differen-  
tial pressure switch to the conditioned space. The pressure  
tube must be terminated in the conditioned space where a  
constant pressure is required. This location is usually in an  
entrance lobby so that the building exterior doors will open  
and close properly. Remove plug button in panel to route  
tubing.  
Be careful when tilting blower assembly. Hoods  
and blowers are heavy and can cause injury if  
dropped.  
3. Secure each damper assembly to unit with 6 screws across  
top (3 screws provided) and bottom (3 screws from  
Step 1) of damper.  
NOTES:  
1. Unless otherwise specified, all dimensions are to outside of part.  
2. Dimensions are in inches.  
Fig. 31 — Barometric Relief Damper and Power  
Exhaust Mounting Details  
29  
VAV  
Variable Air Volume  
Fig. 33A — Motormaster III Sensor Location  
(Sizes 024-034)  
Fig. 32 — Pressure Transducer Locations  
Step 10 — InstallAccessories After all the factory-  
installed options have been adjusted, install all field-  
installed accessories. Refer to the accessory installation in-  
structions included with each accessory.  
MOTORMASTERIII SENSOR LOCATION — Motor-  
master III sensor locations are shown in Fig. 33A-33C. Re-  
fer to the Motormaster III installation instructions for wiring  
and installation information.  
30  
Fig. 33C — Motormaster III Sensor Location  
(Size 048)  
Fig. 33B — MotormasterIII Sensor Location  
(Sizes 038 and 044)  
31  
3. Close the indoor fan circuit breaker. The VFD now is pow-  
ered but the fan will not operate.  
4. On the front of the VFD is a keypad and display which  
will be used to enter the set point. To access this field,  
press ‘‘SETUP’key, then press the ‘‘SETUP’key 6 times  
to scroll to the sixth parameter, which will display  
‘‘Sr1.’’ This is the VFD set point listed in Table 7.  
START-UP  
Use the following information and Start-Up Checklist on  
page CL-1 to check out unit PRIOR to start-up.  
Unit Preparation — Check that unit has been installed  
in accordance with these installation instructions and appli-  
cable codes.  
5. Press the ‘‘READ/WRITE’’ key. The set point value will  
be displayed. Use the up-arrow or down-arrow key to ad-  
just the set point value to the value desired.  
6. Press the ‘‘READ/WRITE’’ key again to enter the new  
value.  
Compressor Mounting — Loosen the compressor hold-  
down bolts until sidewise movement of the washer under  
each holddown bolt head can be obtained. Do not loosen  
completely as bolts are self-locking and will maintain  
adjustment.  
7. Open the indoor fan circuit breaker.  
8. Replace the jumper between CC and ST on the terminal  
strip of the VFD.  
9. Close the indoor fan circuit breaker, the VFD now is pow-  
ered and the fan will operate.  
Service Valves — Ensure that the suction, discharge,  
and liquid line service valves are open. Damage to the com-  
pressor could result if they are left closed.  
Internal Wiring — Check all electrical connections in  
unit control boxes; tighten as required.  
NOTE: Any field measurement of supply fan amps must be  
taken with an RMS meter between the fan circuit breaker  
and fan contactor (upstream of VFD).  
Refrigerant Service Ports — Each refrigerant sys-  
tem has one suction port located in the top of the compressor  
motor casing. All units also have one service port on the liq-  
uid line valve and one on the compressor discharge valve.  
Be sure that caps on the ports are tight.  
Table 7 — VFD Set Point  
Variable Frequency Drive (VFD) — The variable fre-  
quency drives are factory set. These settings include factory-  
installed jumpers and software configurations. The only  
configured set point is duct static pressure.An Operation Manual  
is shipped with each VAV unit. This manual should be  
used if the drive needs to be customized for a particular  
application.  
To set the duct static pressure, perform the following steps.  
The factory setting is zero. The duct transducer has a range  
from 0 to 5 in. wg. The transducer output is 2 to 10 vdc,  
therefore, 0 to 5 in. wg is proportional to the 2 to 10 vdc and  
must be expressed to the VFD in terms of percentage of the  
frequency range. To do this, refer to Table 7. The set point  
value is a percentage of the maximum output frequency. Lo-  
cate the duct static pressure closest to that desired and use  
the corresponding set point value. If necessary, interpolation  
between duct static pressures is permissible.  
PRESSURE  
(in. wg)  
VOLTAGE  
(vdc)  
VFD  
SET POINT  
0.00  
0.25  
0.50  
0.75  
1.00  
1.25  
1.50  
1.75  
2.00  
2.25  
2.50  
2.75  
3.00  
3.25  
3.50  
2.0  
2.4  
2.8  
3.2  
3.6  
4.0  
4.4  
4.8  
5.2  
5.6  
6.0  
6.4  
6.8  
7.2  
7.6  
12.0  
14.4  
16.8  
19.2  
21.6  
24.0  
26.4  
28.8  
31.2  
33.6  
36.0  
38.4  
40.8  
43.2  
45.6  
To set the VFD, the VFD must be powered up, however,  
since it is located near the indoor air fan, operation of the  
fan is not desirable. To disable the fan, perform the follow-  
ing procedure:  
VFD  
Variable Frequency Drive  
1. Open the indoor fan circuit breaker.  
2. Remove the jumper between CC and ST on the terminal  
strip of the VFD (see Fig. 34).  
NOTE: Terminal strip is located inside the VFD (Variable Frequency  
Drive) at the bottom.  
Fig. 34 — VFD Factory-Installed Jumpers  
32  
At the top of the module are 2 potentiometers. The left  
potentiometer adjusts the offset. The right potentiometer ad-  
justs differential. The potentiometers are factory set for a  
nominal 0 in. wg building pressure.  
Power Exhaust — The optional non-modulating power  
exhaust (CV only) is a two-stage design where the operation  
of the exhaust fans is linked to economizer position. When  
the supply fan is running and the economizer is 25% open,  
the base module closes contacts, activating 2 exhaust fans.  
When the economizer position reaches 75% open, the base  
module activates the other 2 exhaust fans. The fans will turn  
off when the economizer closes below the same points. The  
economizer position set points that trigger the exhaust fans  
can be modified, but only through use of the Service Tool,  
Comfort Works, or Building Supervisor Software. If single-  
stage operation is desired, adjust the economizer set points  
to identical values at the desired point to activate all exhaust  
fans.  
The optional modulating power exhaust (VAV standard,  
CV optional) is controlled by a modular electronic se-  
quencer system. This system consists of a model R353 sig-  
nal input module and 4 model S353 staging modules. The  
signal input module receives a 0 to 10 vdc signal from the  
building pressure transducer, which is mounted adjacent to  
the supply static transducer behind the filter access panel.  
The modules are mounted just below the unit control board.  
The left module is the R353, and the 4 modules on the right  
are S353 modules for stages 1 through 4. On the unit wiring  
label, the R353 is designated PESC, and the S353 modules  
are designated PES1 through PES4.  
The offset set point is defined as the point at which a mod-  
ule turns off a fan, and is measured in terms of percent of the  
input signal. For control purposes, 0 offset is at an arbitrary  
‘‘floor’’ which is established at 10% of the input signal, or  
1 vdc. In this example, the first stage will turn off at 30%  
(3 vdc), and the offset potentiometer will be set at 20%. The  
second stage will turn off at 50% signal (5 vdc), and the off-  
set potentiometer will be set at 40%. The fourth stage is at  
the maximum 75% offset, which equates to 85% signal or  
8.5 vdc. The offset potentiometer is calibrated in 10%  
increments.  
Table 8 relates building pressure to signal level.  
Table 8 — Potentiometer Signal Levels  
BUILDING PRESSURE  
(in. wg)  
SIGNAL LEVEL  
(vdc)  
−0.50  
−0.25  
0.00  
2
4
6
0.25  
8
0.50  
10  
If the building pressure is controlled at 0 in. wg, offset of  
the first stage should be set at 50%, which equates to 60%  
of the input signal, or 6 vdc. The other stages can then be set  
as desired between 50% and 75%.  
The default offset set points for modulating power ex-  
haust are shown in Table 9.  
The building pressure transducer range is −0.5 to  
+0.5 in. wg. It is powered by a 0 to 10 vdc signal. A factory-  
installed hose at the ‘‘Lo’’ connection leads to atmosphere,  
and a field-supplied hose must be connected to the ‘‘Hi’con-  
nection and led into the building to a point where building  
pressure is to be controlled. There is a plug button in the  
bulkhead just above the transducers, for use in leading the  
hoses into the building via the return air ductwork.  
Table 9 — Power Exhaust Default Set Points  
There are 3 adjustments at the R353 module, all of which  
have been factory set. In the center of the circuit board is a  
set of 4 pins with a jumper, labeled J2. This determines the  
mode of operation. The bottom 2 pins must be jumpered for  
direct operation. Direct operation means that the staging mod-  
ules are activated in sequence as the input signal  
increases.  
OFF  
DIFFE-  
OFF  
ON  
STATIC  
STAGE OFFSET  
RENTIAL VOLTAGE VOLTAGE PRESSURE  
(in. wg)  
1
2
3
4
50%  
55%  
60%  
64%  
3%  
3%  
3%  
3%  
6.0  
6.5  
7.0  
7.4  
6.3  
6.8  
7.3  
7.7  
0.00  
0.06  
0.12  
0.18  
At the upper right corner of the board is a set of 5 pins and  
jumper, which determines the time constant for the control.  
The time constant is the delay in response built into the con-  
trols. The jumper should be on the middle or bottom 2 pins,  
for the maximum time constant. The delay can be decreased,  
if desired, by moving the jumper progressively upward, al-  
ways jumpering adjacent pins.  
At the lower left corner of the board below the terminal  
strip is a resistor marked R27. This must be removed in or-  
der to obtain the 0 to 10 vdc signal output. There will not be  
a resistor on a factory-supplied module, but a resistor may  
be present on a replacement module and must be removed.  
The R353 module has a terminal block with 7 connec-  
tions available for wiring. The 2 right-hand terminals are for  
the 24 vac and common connections. The next 2 terminals  
are for the 0 to 10 vdc signal. Consult the wiring label for  
wire identification if replacing the module. The 3 left-hand  
terminals are not used for this application.  
The S353 module has an LED (light-emitting diode), a set  
of 4 jumper pins, and 2 potentiometers. The LED will light  
whenever the module is activated, providing a visual indi-  
cation of the number of exhaust fans running. The jumper  
pins are arranged in a square format. Two jumpers are used  
to determine the mode of operation (direct or reverse). The  
2 jumpers must be arranged horizontally for direct action  
(factory set).  
The differential set point is the difference between the  
turn off point and the turn on point for each module. It also  
is calibrated in terms of percent of input signal, and has a  
range of 1% to 7%. The differential potentiometer is cali-  
brated in 1% increments, and is factory set at approximately  
3%. It is recommended to leave the set point at 3%, to mini-  
mize cycling of the fans.  
The offset and differential potentioments have been fac-  
tory set for atmosphereic pressure. Do not change these set-  
tings until there is some experience with the building. In most  
cases the factory settings will be satisfactory. However, if  
the building pressure is not being maintained as desired, then  
some minor adjusting on a trial and error basis can be made.  
Direct Digital Controls DIP Switch Configura-  
tion — The Direct Digital Control (DDC) board must be  
configured for each application. The DDC board is config-  
ured through the DIP switches located on the board. There  
are 8 DIP switches which configure 8 different applications  
of the DDC. See Tables 10A and 10B. DIP switch 1 is on the  
left of the block. DIP switch 8 is on the right of the block.  
To open a DIP switch, push the switch up with suitable tool  
(small-blade screwdriver). To close a DIP switch, push the  
switch down. Factory settings are shown in Tables 11A  
and 11B.  
33  
Table 10A — DIP Switch Configuration (Version 1.0 of Unit Control Software)  
SETTING  
OPEN  
1
2
3
4
5
6
7
8
Field  
Test  
ON  
Modulated  
Power  
Exhaust  
Time Guard Override  
ON/ Set Min.  
Damper Pos. ON  
CCN/  
Sensors  
Expansion  
I/O Board  
VAV  
Gas Heat  
Factory Test ON  
Field  
Test  
OFF  
CV  
Power  
Exhaust  
Time Guard Override  
OFF/ Set Min.  
Damper Pos. OFF  
Base Board  
Only  
CLOSED  
CV  
TSTAT  
Electric Heat  
Factory Test OFF  
LEGEND  
NOTES:  
1. The Factory Test DIP switch should not be enabled in the field.  
2. The OPEN side of the DIP switch is marked ‘‘OPEN.’’ When the  
rocker switch is on the ‘‘OPEN’’ side of the switch, the switch is  
open.  
3. If DIP switch no. 1 is open, DIP switch no. 2 is ignored, since VAV  
units control to supply-air temperature.  
CCN  
CV  
Carrier Comfort Network  
Constant Volume  
Input/Output  
I/O  
POS.  
TSTAT  
VAV  
Position  
Thermostat  
Variable Air Volume  
Table 10B — DIP Switch Configuration (Version 2.0 of Unit Control Software)  
SETTING  
OPEN  
1
2
3
4
5
6
7
8
VAV —  
VAV — Space Sensor  
Installed  
Occupied Time Guard Override  
Heat  
Enabled  
ON  
Expansion  
Board  
Field Test  
ON  
Heat Pump  
Operation  
VAV  
Gas Heat  
CV —  
Modulated  
Power  
IN CONJUNCTION  
WITH FIELD TEST  
— Set Minimum  
CV — CCN or Sensors  
Used  
Exhaust  
Damper Position  
VAV —  
Occupied  
Heat  
VAV — No Space Sensor  
CV — Thermostat  
Disabled  
Base Control Field Test  
Board Only OFF  
Time Guard Override  
OFF  
Air Conditioner  
Operation  
CLOSED CV  
Electric Heat  
CV —  
Constant  
Volume  
Power  
Exhaust  
LEGEND  
NOTES:  
1. The OPEN side of the DIP switch is marked ‘‘OPEN.’’ When the  
rocker switch is on the ‘‘OPEN’’ side of the switch, the switch is  
OPEN.  
CCN  
CV  
VAV  
Carrier Comfort Network  
Constant Volume  
Variable Air Volume  
2. The configuration of DIP switches 2 and 5 are dependent on DIP  
switch 1. If DIP switch 1 is set to OPEN (VAV operation), then DIP  
switches 2 and 5 will configure CV functions.  
3. When the unit is field-tested (DIP switch 4 to OPEN), the function  
of DIP switch 6 changes and it is used to set the minimum damper  
position.  
Table 11A — DIP Switch Factory Settings (Version 1.0 of Unit Control Software)  
UNIT  
1
2
3
4
5
6
7
8
50EJ/EW  
50EK/EY  
Closed  
Open  
Closed  
Closed  
Closed  
Closed  
Closed  
Closed  
Closed  
Open  
Closed  
Closed  
Closed  
Closed  
Closed  
Closed  
Table 11B — DIP Switch Factory Settings (Version 2.0 of Unit Control Software)  
UNIT  
1
2
3
4
5
6
7
8
50EJ/EW  
50EK/EY  
Closed  
Open  
Closed  
Closed  
Closed  
Closed  
Closed  
Closed  
Closed  
Closed  
Closed  
Closed  
Closed  
Closed  
Closed  
Closed  
34  
DIP switch configurations for Version 1.0 of the Unit Con-  
trol Software are as follows:  
Filter Replacement To replace filters, open filter  
access door (marked with label). Remove inner access panel.  
Remove plastic filter retainer in between filter tracks by slid-  
ing and pulling outward. Remove first filter by sliding it out  
of the opening in filter track. Locate filter removal tool, which  
is shipped next to the return air dampers. Use the filter re-  
moval tool to remove the remaining filters.  
• DIP switch 1 configures the unit to operate as a variable  
air volume (VAV) or constant volume (CV) unit  
• DIP switch 2 configures what type of sensors or thermo-  
stats are used with the unit  
• DIP switch 3 configures the DDC for use with the elec-  
tronic expansion board  
Outdoor-Air Inlet Screens — Outdoor-air inlet screens  
must be in place before operating unit.  
• DIP switch 4 is used to field test the unit  
• DIP switch 5 configures the unit to use constant volume or  
modulated power exhaust  
EconomizerAdjustment — Remove filter access panel.  
Check that outdoor-air damper is closed and return-air damper  
is open.  
Economizer operation and adjustment is described in Se-  
quence of Operation and Make Outdoor Air Inlet Adjust-  
ments sections (this page and page 25), respectively.  
• DIP switch 6 configures the Time Guardoverride and the  
minimum damper position  
• DIP switch 7 configures the unit for gas heat or electric  
heat  
• DIP switch 8 is used to factory test the unit  
The DIP switch configurations for Version 2.0 of the unit  
control software are as follows:  
Sequence of Operation  
NOTE: Unit is shipped with default values that can be changed  
through Service Tool or CCN software.  
• DIP switch 1 configures the unit to operate as a VAV or  
CV unit  
• DIP switch 2 configures the unit to use a space sensor (VAV  
units) or a thermostat (CV units)  
COOLING, CONSTANT VOLUME (CV) UNITS — On  
power up, the control module will activate the initialization  
software. The initialization software reads DIP switch no. 1  
position to determine CV or VAV operation. Next, DIP switch  
no. 2 is read to determine if the control is TSTAT or sensor  
type operation. The initialization sequence: clears all alarms  
and alerts; re-maps the input/output database for CV opera-  
tion; sets maximum heat stages to 2; and sets maximum cool  
stages to 3. The control module reads DIP switch no. 3 and  
determines if the unit will use expansion mode operation.  
The TSTAT function performs a thermostat based control  
by monitoring Y1, Y2, W1, W2 and G inputs. These func-  
tions control stages: cool1, cool2, heat1, heat2, and the in-  
door fan respectively. If the TSTAT function is not selected,  
the control module determines the occupancy state based on  
the system time schedules or with remote occupied/unoccupied  
input. If Temperature Compensated Start is active, the unit  
will be controlled as in the Occupied mode. User defined set  
points are shown in Table 17.  
Occupied or unoccupied comfort set points must be se-  
lected. Use of the space temperature offset input can also be  
configured. The control module will set appropriate operat-  
ing mode and fan control. The control module will turn on  
indoor fan if in Occupied mode or if the unit is in Unoccu-  
pied mode and the space temperature is outside of the un-  
occupied comfort set points (Unoccupied Heat or Unoccu-  
pied Cool). The control module will then monitor space  
temperature against comfort set points and control heating  
or cooling stages as required. If the system is in the Occu-  
pied mode, the economizer will operate as required. If the  
system is in Unoccupied mode, the system will perform night  
time free cool and IAQ (indoor air quality) pre-occupancy  
purge as required (when functions are enabled via software).  
Whenever the DX (direct expansion) cooling is requested,  
the outdoor fan will operate.  
• DIP switch 3 configures the DDC for use with an elec-  
tronic expansion board  
• DIP switch 4 is used to field test the unit  
• DIP switch 5 is used to enable occupied heating (VAV units)  
or specify the type of power exhaust (CV units)  
• DIP switch 6 configures the Time Guard override and, when  
used with the field test function, sets the minimum damper  
position  
• DIP switch 7 configures the unit for gas heat or electric  
heat  
• DIP switch 8 configures the unit for heat pump or air con-  
ditioner operation  
Crankcase Heater(s) Heater(s) is energized as long  
as there is power to the unit, except when the compressors  
are operating.  
IMPORTANT: Unit power must be on for 24 hours  
prior to start-up. Otherwise, damage to compressor may  
result.  
Evaporator Fan — Fan belt and fixed pulleys are factory-  
installed. See Tables 12-14 for Fan Performance Data. See  
Table 15 for Air Quantity Limits. See Table 16 for Motor  
Limitation data. Be sure that fans rotate in the proper di-  
rection. Static pressure drop for power exhaust, barometric  
relief damper, and electric heat is negligible. To alter fan per-  
formance, see Evaporator Fan Performance Adjustment sec-  
tion on page 43.  
Condenser Fans and Motors — Fans and motors  
are factory set. Refer to Condenser-Fan Adjustment section  
(page 44) as required.  
Return-Air Filters Check that correct filters are in-  
stalled in filter tracks. See Table 1. Do not operate unit with-  
out return-air filters.  
35  
Table 12 — Fan Performance, 50EJ/EK024-034 — Vertical Discharge Units  
FOR EW/EY UNITS, REDUCE NET AVAILABLE EXTERNAL STATIC PRESSURE BY 0.3 IN. WG  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
(Cfm)  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
4,000  
5,000  
322  
361  
403  
448  
495  
507  
543  
592  
642  
693  
718  
744  
0.77  
1.14  
1.62  
2.22  
2.97  
3.18  
3.85  
4.90  
6.10  
7.48  
8.23  
9.03  
401  
433  
468  
508  
549  
560  
593  
638  
685  
733  
757  
781  
1.09  
1.50  
2.01  
2.65  
3.42  
3.64  
4.34  
5.41  
6.64  
8.04  
8.80  
9.62  
466  
494  
526  
561  
599  
609  
639  
682  
725  
771  
794  
1.43  
1.86  
2.41  
3.08  
3.88  
4.10  
4.82  
5.91  
7.17  
8.60  
9.37  
523  
548  
577  
609  
645  
654  
682  
722  
764  
807  
829  
1.78  
2.23  
2.81  
3.50  
4.33  
4.56  
5.30  
6.42  
7.70  
9.15  
9.94  
575  
598  
624  
654  
687  
696  
723  
760  
800  
841  
862 10.51  
884 11.36  
917 12.71  
928 13.19  
2.13  
2.62  
3.21  
3.93  
4.79  
5.02  
5.78  
6.93  
8.24  
9.71  
622  
643  
668  
696  
727  
735  
761  
797  
835  
874 10.26  
895 11.08  
915 11.93  
947 13.31  
958 13.79  
2.50  
3.00  
3.62  
4.37  
5.25  
5.49  
6.27  
7.44  
8.77  
666  
686  
709  
736  
765  
773  
797  
832  
868  
2.87  
3.40  
4.04  
4.81  
5.71  
5.96  
6.76  
7.95  
9.30  
707  
726  
748  
773  
801  
809  
832  
865  
900  
3.25  
3.80  
4.46  
5.25  
6.18  
6.43  
7.24  
8.46  
9.84  
6,000  
7,000  
8,000  
8,250  
9,000  
10,000  
11,000  
12,000  
12,500  
13,000  
13,750  
14,000  
15,000  
906 10.82  
926 11.64  
946 12.51  
977 13.90 1005 14.50  
987 14.39 1015 14.99  
937 11.38  
956 12.21  
975 13.09  
817 10.20  
852 11.52  
864 11.98  
912 13.96  
851 10.78  
885 12.12  
896 12.59  
943 14.59  
783 10.32  
795 10.77  
847 12.71  
818 10.92  
831 11.38  
880 13.34  
972 15.21 1001 15.83 1029 16.45 1056 17.08  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
2.2 2.4 2.6 2.8  
AIRFLOW  
(Cfm)  
1.8  
2.0  
3.0  
3.2  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
4,000  
5,000  
746  
764  
785  
809  
836  
843  
865  
897  
3.64  
4.21  
4.89  
5.70  
6.65  
6.91  
7.74  
8.98  
783  
800  
820  
843  
869  
876  
898  
928  
4.03  
4.62  
5.32  
6.16  
7.12  
7.39  
8.23  
9.49  
818  
834  
854  
876  
901  
908  
929  
4.44  
5.04  
5.76  
6.61  
7.60  
7.87  
8.73  
852  
868  
886  
908  
932  
938  
959  
4.85  
5.46  
6.21  
7.08  
8.08  
8.36  
9.23  
884  
900  
918  
939  
962  
968  
988  
5.26  
5.89  
6.65  
7.54  
8.57  
8.84  
916  
930  
948  
968  
991  
997  
5.68  
6.33  
7.11  
8.01  
946  
960  
977  
997  
6.11  
6.77  
975  
989  
6.54  
7.22  
8.02  
8.96  
6,000  
7.56 1006  
8.49 1025  
7,000  
8,000  
9.05 1019  
9.34 1025  
9.55 1046 10.04  
9.83 1052 10.33  
8,250  
9,000  
9.74 1016 10.24 1043 10.75 1070 11.27  
10,000  
11,000  
12,000  
12,500  
13,000  
13,750  
14,000  
15,000  
958 10.01  
990 11.45 1018 11.99 1046 12.54 1073 13.08 1099 13.63 1124 14.18  
996 12.49 1024 13.06 1051 13.62 1078 14.18 1104 14.75 1129 15.31 1154 15.88  
987 10.53 1016 11.06 1043 11.58 1070 12.11 1096 12.64  
931 10.37  
967 11.94  
961 10.91  
985 12.78 1014 13.35 1041 13.92 1068 14.49 1094 15.07 1120 15.64 1145 16.22 1169 16.80  
1004 13.67 1032 14.25 1059 14.83 1086 15.42  
1111 16.00 1137 16.59 1161 17.17 1185 17.76  
1033 15.09 1060 15.69 1087 16.29 1112 16.88 1138 17.48 1162 18.08 1186 18.68  
1043 15.59 1070 16.19 1096 16.79 1122 17.40 1147 18.00 1171 18.60 1195 19.21  
1083 17.70 1109 18.32 1134 18.94 1159 19.56 1183 20.19  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
(Cfm)  
LEGEND  
Brake Horsepower  
3.4  
3.6  
3.8  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Bhp  
4,000  
5,000  
1004  
1017  
1034  
1052  
1073  
1079  
1096  
1122  
1149  
1178  
1193  
6.97  
7.67  
8.49  
9.44  
10.54  
10.84  
11.78  
13.18  
14.73  
16.45  
17.38  
1032  
1045  
1061  
1079  
1099  
1105  
1122  
1147  
1173  
1202  
7.41  
8.12  
8.96  
9.93  
11.04  
11.34  
12.30  
13.71  
15.29  
17.03  
1059  
1072  
1087  
1105  
1125  
1130  
1147  
1171  
1197  
7.86  
8.58  
9.43  
10.42  
11.55  
11.85  
12.82  
14.25  
15.84  
NOTES:  
1. Fan performance is based on wet coils, economizer, roof curb,  
cabinet losses, and clean 2-in. filters.  
6,000  
7,000  
2. Conversion — Bhp to watts:  
8,000  
Bhp x 746  
Watts =  
8,250  
9,000  
Motor efficiency  
10,000  
11,000  
12,000  
12,500  
13,000  
13,750  
14,000  
15,000  
3. VAV units will operate down to 70 cfm/ton.  
36  
Table 13 — Fan Performance, 50EJ038,044 and 50EK044 — Vertical Discharge Units  
For EW/EY UNITS, REDUCE NET AVAILABLE EXTERNAL STATIC PRESSURE BY 0.5 IN. WG  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
(Cfm)  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
8,000  
9,000  
448  
492  
537  
582  
629  
675  
722  
770 10.00  
817 11.76  
865 13.70  
913 15.83  
961 18.16  
2.18  
2.87  
3.69  
4.65  
5.75  
7.00  
8.42  
498  
537  
578  
620  
664  
708  
753 10.11  
798 11.94  
844 13.96  
890 16.19  
937 18.64  
2.87  
3.68  
4.63  
5.75  
7.02  
8.48  
544  
580  
617  
657  
698  
739  
782 10.63  
826 12.48  
870 14.53  
915 16.78  
961 19.25  
3.25  
4.09  
5.07  
6.20  
7.50  
8.98  
589  
621  
655  
692  
730  
770  
811 11.16  
853 13.03  
896 15.09  
940 17.37  
3.64  
4.50  
5.50  
6.66  
7.98  
9.48  
631  
660  
692  
726  
763  
800  
840 11.69  
880 13.57  
922 15.66  
964 17.95  
4.04  
4.92  
5.95  
7.13  
8.47  
9.99  
671  
698  
727  
759  
794  
830 10.50  
868 12.22  
907 14.13  
947 16.23  
4.44  
5.35  
6.39  
7.60  
8.96  
710  
734  
761  
792  
824  
859 11.01  
895 12.75  
932 14.68  
971 16.81  
4.86  
5.78  
6.85  
8.07  
9.45  
747  
769  
795  
823  
854  
887 11.53  
922 13.29  
958 15.24  
995 17.38  
5.27  
6.22  
7.30  
8.55  
9.95  
10,000  
11,000  
12,000  
13,000  
14,000  
15,000  
16,000  
17,000  
18,000  
19,000  
20,000  
988 18.54 1011 19.14 1034 19.73  
984 19.85 1007 20.46 1030 21.07 1052 21.68 1074 22.30  
984 21.32 1006 21.94 1029 22.56 1050 23.19 1072 23.82 1093 24.45 1115 25.08  
1009 20.69 1031 24.22 1052 24.86 1074 25.50 1095 26.15 1115 26.80 1136 27.45 1156 28.10  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
(Cfm)  
1.8  
2.0  
2.2  
2.4  
2.6  
2.8  
3.0  
3.2  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
8,000  
9,000  
783  
803  
827  
854  
883 10.45  
914 12.05  
948 13.83  
5.70  
6.66  
7.77  
9.03  
818  
836  
858  
884  
911 10.96  
942 12.57  
974 14.37  
6.13  
7.11  
8.23  
9.51  
852  
869  
889  
913 10.00  
939 11.47  
968 13.10  
6.56  
7.56  
8.70  
884  
900  
919  
7.00  
8.02  
9.18  
916  
930  
948  
7.45  
8.48  
9.66  
947  
960  
7.90  
8.95  
978  
989  
8.36 1007  
9.42 1018  
8.82  
9.90  
10,000  
11,000  
12,000  
13,000  
14,000  
15,000  
16,000  
17,000  
18,000  
19,000  
20,000  
977 10.15 1005 10.64 1032 11.13  
997 11.50 1024 12.01 1050 12.52  
941 10.50  
967 11.98  
969 11.00  
993 12.50 1020 13.02 1046 13.54 1071 14.07  
994 13.63 1020 14.17 1045 14.71 1070 15.25 1094 15.79  
999 14.92 1024 15.47 1049 16.02 1073 16.58 1096 17.14 1120 17.70  
983 15.80 1007 16.36 1032 16.92 1056 17.49 1079 18.06 1102 18.64 1125 19.21 1148 19.79  
1019 17.96 1043 18.54 1066 19.13 1089 19.71 1111 20.30 1134 20.89 1156 21.49 1177 22.08  
1057 20.33 1079 20.93 1102 21.53 1124 22.14 1145 22.75 1167 23.35 1188 23.97  
1096 22.91 1117 23.53 1138 24.15 1160 24.78 1180 25.40  
1135 25.72 1156 26.36 1176 26.99 1197 27.63  
1176 28.75 1196 29.41  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
3.4 3.6 3.8  
LEGEND  
AIRFLOW  
(Cfm)  
Bhp  
Brake Horsepower  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
NOTES:  
8,000  
9,000  
1036  
1046  
1059  
1076  
1096  
1118  
1143  
1170  
1199  
9.29  
10.38  
11.63  
13.03  
14.60  
16.34  
18.26  
20.37  
22.68  
1065  
1073  
1086  
1102  
1121  
1142  
1166  
1192  
9.76  
10.87  
12.13  
13.55  
15.13  
16.89  
18.83  
20.96  
1092  
1100  
1112  
1127  
1145  
1165  
1188  
10.24  
11.36  
12.64  
14.07  
15.67  
17.45  
19.40  
1. Fan performance is based on wet coils, economizer, roof curb,  
cabinet losses, and clean 2-in. filters.  
2. Conversion − Bhp to watts:  
10,000  
11,000  
12,000  
13,000  
14,000  
15,000  
16,000  
17,000  
18,000  
19,000  
20,000  
Bhp x 746  
Watts =  
Motor efficiency  
3. VAV units will operate down to 70 cfm/ton.  
37  
Table 14 — Fan Performance, 50EJ048 — Vertical Discharge Units  
FOR EW UNITS, REDUCE NET AVAILABLE EXTERNAL STATIC PRESSURE BY 0.5 IN. WG  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
(Cfm)  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
13,000  
14,000  
15,000  
16,000  
17,000  
18,000  
19,000  
20,000  
683  
730  
778 10.14  
826 11.93  
875 13.90  
923 16.06  
972 18.42  
7.10  
8.53  
715  
8.59  
747  
9.09  
777  
9.60  
808 10.11  
847 11.83  
888 13.75  
931 15.86  
973 18.19  
837 10.62  
875 12.36  
915 14.30  
955 16.44  
866 11.14  
902 12.90  
941 14.86  
894 11.66  
929 13.44  
966 15.42  
761 10.25  
807 12.10  
853 14.15  
900 16.42  
947 18.90  
790 10.77  
834 12.65  
879 14.72  
925 17.01  
971 19.51  
819 11.30  
862 13.19  
905 15.29  
949 17.60  
980 17.01 1004 17.59  
997 18.78 1020 19.38 1043 19.98  
994 20.12 1017 20.73 1039 21.34 1062 21.96 1084 22.58  
995 21.61 1017 22.24 1039 22.87 1061 23.50 1083 24.13 1104 24.76 1125 25.40  
1021 20.98 1042 24.55 1064 25.20 1085 25.85 1106 26.50 1126 27.15 1147 27.80 1167 28.46  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
(Cfm)  
1.8  
2.0  
2.2  
2.4  
2.6  
2.8  
3.0  
3.2  
Rpm  
Bhp  
Rpm  
948 12.71  
981 14.53 1006 15.08 1031 15.63 1056 16.18 1080 16.74 1103 17.30 1127 17.86  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
13,000  
14,000  
15,000  
16,000  
17,000  
18,000  
19,000  
20,000  
921 12.18  
955 13.98  
975 13.24 1001 13.77 1026 14.30 1051 14.84 1076 15.39 1100 15.93  
991 15.98 1015 16.54 1040 17.11 1063 17.68 1087 18.25 1110 18.83 1133 19.41 1155 19.99  
1028 18.17 1051 18.76 1074 19.34 1097 19.93 1120 20.52 1142 21.12 1164 21.71 1185 22.31  
1066 20.58 1089 21.18  
1111 21.78 1133 22.39 1154 23.00 1175 23.61 1197 24.23  
1106 23.19 1127 23.82 1148 24.44 1169 25.07 1190 25.69  
1146 26.04 1166 26.68 1187 27.32  
1187 29.11  
LEGEND  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
3.4 3.6 3.6  
AIRFLOW  
(Cfm)  
Bhp  
Brake Horsepower  
Rpm  
Bhp  
Rpm  
Bhp  
Rpm  
Bhp  
NOTES:  
13,000  
14,000  
15,000  
16,000  
17,000  
18,000  
19,000  
20,000  
1124  
1150  
1177  
16.48  
18.43  
20.57  
1148  
1173  
1199  
17.03  
19.00  
21.16  
1171  
1195  
17.59  
19.57  
1. Fan performance is based on wet coils, economizer, roof curb,  
cabinet losses, and clean 2-in. filters.  
2. Conversion − Bhp to watts:  
Bhp x 746  
Watts =  
Motor efficiency  
3. VAV units will operate down to 70 cfm/ton.  
Table 15 — Air Quantity Limits  
UNIT  
50EJ,EK,EW,EY  
MINIMUM HEATING  
CFM  
MINIMUM COOLING  
CFM (VAV)  
MINIMUM COOLING  
CFM (CV)  
MAXIMUM  
CFM  
024  
028  
030  
034  
038  
044  
048  
6,000  
7,500  
2000  
2500  
2750  
3000  
3500  
4000  
4500  
6,000  
7,500  
10,000  
12,500  
13,750  
15,000  
17,500  
20,000  
22,500  
8,250  
8,250  
9,000  
9,000  
10,500  
12,000  
13,500  
10,500  
12,000  
13,500  
LEGEND  
CV  
VAV  
Constant Volume  
Variable Air Volume  
38  
Table 16 — Motor Limitations  
STANDARD EFFICIENCY MOTORS  
Maximum Amps  
Nominal  
Hp  
Maximum  
Bhp  
Maximum  
Watts  
Motor  
Efficiency  
208  
17.94  
230  
16.99  
460  
575  
5.9  
5.9  
5,348  
5,240  
82.3  
84.0  
84.1  
82.9  
85.7  
85.6  
83.4  
84.5  
87.8  
87.5  
88.0  
87.1  
90.4  
88.3  
5
8.50  
5.78  
8.7  
25.52  
24.36  
7,717  
7.5  
10  
15  
20  
25  
30  
9.5  
13.30  
9.63  
8,549  
10.2  
11.8  
15.3  
18.0  
22.4  
23.4  
28.9  
29.4  
35.6  
34.7  
26.93  
25.50  
8,879  
14.75  
11.33  
10,284  
13,686  
15,891  
19,032  
19,950  
24,499  
25,181  
29,378  
29,316  
42.84  
40.80  
24.00  
18.00  
59.36  
56.00  
29.25  
22.82  
76.30  
72.83  
37.04  
28.69  
92.56  
87.81  
42.80  
n/a  
HIGH EFFICIENCY MOTORS  
Maximum Amps  
Nominal  
Hp  
Maximum  
Bhp  
Maximum  
Watts  
Motor  
Efficiency  
208  
16.76  
230  
13.92  
460  
575  
5.9  
5.9  
5,030  
5,030  
87.5  
87.5  
89.5  
88.5  
88.5  
91.7  
89.5  
89.5  
91.0  
91.0  
91.0  
93.0  
91.0  
91.0  
93.6  
91.7  
91.7  
93.6  
92.4  
92.4  
93.6  
5
6.96  
5.9  
5.66  
4,918  
8.7  
26.10  
22.27  
7,334  
7.5  
10  
15  
20  
25  
30  
9.5  
12.16  
8,008  
9.5  
9.50  
7,728  
10.2  
11.8  
11.8  
15.3  
18.0  
18.0  
22.4  
23.4  
23.4  
28.9  
29.4  
29.4  
35.6  
34.7  
34.7  
28.56  
24.89  
8,502  
14.40  
9,836  
11.68  
9,600  
45.08  
39.17  
12,543  
14,756  
14,439  
18,363  
19,183  
18,650  
23,511  
23,918  
23,432  
28,742  
28,015  
27,656  
23.04  
18.12  
63.84  
55.55  
29.02  
23.17  
80.69  
70.05  
35.63  
28.81  
102.65  
89.00  
43.38  
33.89  
NOTE: Extensive motor and electrical testing on the Carrier units has ensured  
that the full horsepower range of the motor can be utilized with confidence.  
Using your fan motors up to the horsepower ratings shown on the Motor Limi-  
tations table will not result in nuisance tripping or premature motor failure. Unit  
warranty will not be affected.  
LEGEND  
Brake Horsepower  
BHP  
Table 17 — User Defined Set Points  
SET POINT  
OHSP  
OCSP  
UHSP  
UCSP  
SASP  
OATL  
NTLO  
RTIO  
FORMAT  
xx.xF  
xx.xF  
xx.xF  
xx.xF  
xx.xF  
xx.xF  
xx.xF  
xx.x  
DESCRIPTION  
Occupied Heat Set Point  
Occupied Cool Set Point  
Unoccupied Heat Set Point  
Unoccupied Cool Set Point  
Supply Air Set Point  
LIMITS  
55 to 80 F  
55 to 80 F  
40 to 80 F  
75 to 95 F  
45 to 70 F  
55 to 75 F  
40 to 70 F  
0 to 10  
DEFAULT  
68  
78  
55  
90  
55  
65  
50  
3
Hi OAT Lockout Temperature  
Unoccupied OAT Lockout Temperature  
Reset Ratio  
LIMT  
xx.x^F  
xxx%  
xxxx  
Reset Limit  
0 to 20 F  
0 to 100%  
1 to 5000  
0 to 10  
10  
20  
650  
1
MDP  
Minimum Damper Position  
IAQ Set Point  
IAQS  
UHDB  
UCDB  
LTMP  
HTMP  
PES1  
PES2  
xx.x^F  
xx.x^F  
xx.xF  
xx.xF  
xx.xF  
xx.xF  
Unoccupied Heating Deadband  
Unoccupied Cooling Deadband  
Low Temp. Min. Position  
High Temp. Min. Position  
CV Power Exhaust Stage 1 Point  
CV Power Exhaust Stage 2 Point  
0 to 10  
1
0 to 100  
10  
35  
25  
75  
0 to 100  
0 to 100  
0 to 100  
LEGEND  
CV  
IAQ  
OAT  
Constant Volume  
Indoor Air Quality  
Outdoor Air Temperature  
39  
The control module will operate economizer, run diag-  
nostics to monitor alarms/alerts at all times, and respond to  
CCN communications to perform any configured network  
POC (product outboard control) functions such as time/  
outdoor-air temperature broadcast and global occupancy broad-  
cast. When the optional expansion I/O board is employed, it  
will: perform a periodic scan and maintain a database of ex-  
panded I/O points; perform Fire/Smoke control (power ex-  
haust required); if in Occupied mode, perform IAQ control  
and monitor the fan, filter, demand limit, and field-applied  
status (with accessories).  
If thermostats are used to energize the G input, the control  
module will turn on the indoor fan without delay and open  
the economizer dampers to minimum position. If thermo-  
stats are used to deenergize the G input, the control module  
will turn off the indoor fan without delay and close the econo-  
mizer dampers.  
When cooling, G must be energized before cooling can  
operate. The control module determines if outdoor condi-  
tions are suitable for economizer cooling using the standard  
outdoor air thermistor. For the economizer to function for  
outside air cooling: the enthalpy must be below the enthalpy  
set point; the outdoor-air temperature must be equal to or  
less than the High Outdoor Air Temperature Lockout (de-  
fault is 65 F); the SAT (supply-air temperature) thermistor  
must not be in alarm; and the outdoor air reading is avail-  
able. When these conditions are satisfied, the control mod-  
ule will use economizer as the first stage of cooling.  
When Y1 input is energized, the economizer will be modu-  
lated to maintain SAT at the defined set point. (The default  
is 55 F.) When SAT is above the set point, the economizer  
will be 100% open. When SAT is below the set point, the  
economizer will modulate between minimum and 100% open  
position. When Y2 is energized, the control module will turn  
on compressor 1 and continue to modulate the economizer  
as described above. If the Y2 remains energized and the SAT  
reading remains above the set point for 15 minutes, com-  
pressor 2 will turn on. If Y2 is deenergized at any time, only  
the last stage of compression that was energized will be turned  
off. If outdoor conditions are not suitable for economizer cool-  
ing, the economizer will go to minimum position and cycle  
compressors 1 and 2 based on demand from Y1 and Y2 re-  
spectively. The compressors will be locked out when the SAT  
temperature is too low (less than 40 F for compressor 1 and  
less than 45 F for compressor 2). After a compressor is locked  
out, it can restart after normal time-guard period.  
commands to the base unit module. If a linkage is active, the  
control module will replace local comfort set points, space  
and return air temperatures, and occupancy status with the  
linkage data supplied.  
The control module will determine occupancy status from  
Time Schedules (if programmed), Remote Occupied/  
Unoccupied input, global occupancy schedules, or DAV. If  
temperature compensated start is active, the unit will be con-  
trolled as in the Occupied mode.  
NOTE: The temperature compensated start is a period of time  
calculated to bring the unit on while in Unoccupied mode to  
reach the occupied set point when occupancy occurs.  
The control module will set the appropriate operating mode  
and fan control. The control module will turn on the VFD if  
Occupied mode is evident. If in Unoccupied mode and a valid  
space temperature reading is available (either from a sensor  
or DAV), the control module will monitor SPT (space tem-  
perature) against unoccupied heat and cool set points. The  
control module will start the VFD whenever SPT is outside  
of the set points (Unoccupied Heat or Unoccupied Cool).  
The VFD may also be started by nighttime thermostat via  
remote Occupied/Unoccupied input or by a temperature com-  
pensated start algorithm. When the VFD is running in a nor-  
mal mode, the control module will start heating or cooling  
as required to maintain supply-air temperature at the supply  
air set point plus the reset (when enabled). The reset value  
is determined by SAT (supply-air temperature) reset and/or  
space temperature reset algorithms. The reset is only avail-  
able when enabled through software.  
When cooling, the control module will energize the power  
exhaust enable output to the external power exhaust control-  
ler (when power exhaust is used).  
The control module will run continuous diagnostics for  
alarms/alerts; respond to CCN (Carrier Comfort Network)  
communications; perform any configured network POC (Prod-  
uct Outboard Control) functions such as time/outdoor air tem-  
perature broadcast and global broadcast; and perform Fire/  
Smoke control.  
HEATING, CONSTANT VOLUME (CV) UNITS — The  
control module is powered by 24 vac. If the unit is con-  
trolled with a room sensor, the fan will run continuously in  
the Occupied mode, with the outside-air damper in the mini-  
mum position. If the unit is controlled through a room ther-  
mostat (with FAN set to AUTO), upon a call for heat the first  
stage of heat is energized, the indoor-fan motor will turn on,  
and the outdoor-air damper will move to the minimum po-  
sition. Upon a call for additional heat (if the unit is equipped  
with a two-stage heater), the second stage of heat is ener-  
gized. When the call for heat is satisfied, the heaters will  
deenergize. The indoor-fan motor will also deenergize (un-  
less controlled by a room sensor) and the outdoor-air damper  
will move to the closed position.  
If the unit is controlled with a room sensor the fan will not  
run in the unoccupied mode. Upon a call for heat, the first  
stage of heat is energized, the indoor-fan motor will turn on,  
and the outdoor air damper will move to the Unoccupied  
IAQ position (generally set to zero in the unoccupied mode).  
The IAQ feature is enabled through system software. Upon  
a call for additional heat (if the unit is equipped with a two-  
stage heater), the second stage of heat is energized. When  
the call for heat is satisfied, the heaters and indoor-fan motor  
will deenergize and the outdoor-air damper will move to the  
closed position (if open).  
The Time Guardfunction maintains a minimum off time  
of 5 minutes, a minimum on time of 10 seconds, and a  
minimum delay before starting the second compressor of  
10 seconds.  
When heating, the heat stages respond to the demand from  
W1 and W2 of the thermostat input. Heating and cooling  
will be mutually locked-out on demand on a first call basis.  
The heating and the cooling functions cannot operate  
simultaneously.  
COOLING, VARIABLE VOLUME UNITS — On power up,  
the control module will activate the initialization software.  
The initialization software reads DIP switch no. 1 position  
to determine CV or VAV operation. The initialization se-  
quence: clears all alarms and alerts; re-maps the input/  
output database for VAV operation; sets maximum heat stages  
to 1; and sets maximum cool stages to 6. The control module  
reads DIP switch no. 3 and determines if the unit will use  
expansion mode operation. Power up takes a random time of  
1 to 63 seconds plus 5 minutes the first time power is sent  
to the control board after a power outage.  
HEATING, VARIABLE AIR VOLUME (VAV) UNITS —  
The control board is powered by 24 vac. When there is a call  
for heating (from Morning Warm-Up, Unoccupied, or Oc-  
cupied modes), power is sent from the control module to  
energize the first stage of electric heat. A field-supplied heat  
The control module will determine if an interface (link-  
age) is active and if the unit will operate in a Digital Air  
Volume (DAV) mode. In a DAV system, the room terminals  
are equipped with microprocessor controls that give  
40  
interlock relay signals for the air terminals to fully open. See  
Fig. 35. In the Occupied mode, the indoor-fan motor will  
operate continuously and the outdoor-air dampers will be in  
the minimum position. In the Unoccupied mode, the indoor-  
fan motor will be off, but will energize upon the call for heat.  
The outdoor-air dampers will move to the IAQ unoccupied  
position (generally set to zero in the Unoccupied mode). The  
IAQ feature is enabled through system software. The duct  
pressure sensor will signal to the variable frequency drive to  
operate at full speed. Upon a call for additional heat (if the  
unit is equipped with a two-stage heater), the second stage  
of heat will be energized. When the call for heat is satisfied,  
the heaters will deenergize.  
The field-supplied space temperature sensor input signal  
(4 to 20 ma and 2 to 10 vdc) enables the space temperature  
reset function. Refer to Fig. 36 for sensor wiring.  
POWER EXHAUST OPERATION — The optional power  
exhaust packages are factory- or field-installed with vertical  
units and optionally installed in the return air ductwork for  
horizontal applications. The standard (only offered with con-  
stant volume units) and modulating power exhaust (offered  
on VAV units) are the 2 packages available. The modulating  
power exhaust package is equipped with a field-adjustable  
static pressure controller which will control up to 4 power  
exhaust stages to maintain a building static pressure. The blue  
sequencer located in the control box below the control board  
can be adjusted by removing the covers and adjusting the set  
point dial to the desired building pressure. The standard power  
exhaust package controls up to 2 stages of power exhaust to  
maintain building pressure. These power exhaust stages are  
staged according to a percentage of the economizer damper  
position. The default values are 25% for Stage 1 and 75%  
for Stage 2. This package has set points that are adjustable  
through software (such as Service Tool, Building Supervi-  
sor, or Comfort Works).  
NOTE: The HIR is not needed in a DAV system.  
If the unit is in the Unoccupied mode, the indoor-fan mo-  
tor will deenergize and the outdoor-air damper will move to  
the closed position (if open).  
MORNING WARM-UP (VAV ONLYWITH PC ACCESSED/  
CCN OPERATION) — Morning warm-up occurs when the  
control module has been programmed to turn on heat, prior  
to the Occupied mode, to be ready for the occupancy. Morn-  
ing warm-up is a condition in VAV systems that occurs when  
the Temperature Compensated Start algorithm calculates a  
biased occupied start time and the unit has a demand for heat-  
ing. The warm-up will continue into the occupied period as  
long as there is a need for heat. During warm-up, the unit  
can continue heating into the occupied period, even if oc-  
cupied heating is disabled. When the heating demand is sat-  
isfied, the warm-up condition will terminate. To increase or  
decrease the heating demand, use the network access soft-  
ware to change the occupied heating set point.  
NOTE: To utilize morning warm-up mode, the unit occu-  
pancy schedule must be accessed via Service Tool, Comfort  
Works, or Building Supervisor software (units running Ver-  
sion 1.0 of unit control software).  
MORNING WARM-UP (VAV ONLYWITH STAND-ALONE  
OPERATION) — When a unit running version 2.0 of the  
unit control software operates in stand-alone mode, morning  
warm-up occurs when the unit is energized in Occupied mode  
and return-air temperature (RAT) is below 68 F. Warm-up  
will not terminate until the RAT reaches 68 F. The heat in-  
terlock relay output is energized during morning warm-up.  
(A field-installed 24-vdc heat interlock relay is required.) The  
output will be energized until the morning warm-up cycle is  
complete. Refer to Fig. 35 for heat interlock relay wiring.  
Fig. 35 — Heat Interlock Relay Wiring  
SPACE TEMPERATURE RESET (VAV ONLY) — An ac-  
cessory space temperature sensor is required. Space tem-  
perature reset is used to reset the supply-air temperature set  
point of a VAV system higher, as the space temperature falls  
below the Occupied Cool set point. As the space tempera-  
ture falls below the cool set point, the supply-air tempera-  
ture will be reset upward as a function of the reset ratio. Re-  
set ratio is expressed in degrees change in supply-air temperature  
per degree of space temperature change. A reset limit will  
exist which will limit the maximum number of degrees the  
supply-air temperature may be raised. Both the reset ratio  
and the reset limit are user definable. The sequence of op-  
eration is as follows:  
1. The on/off status of the unit supply fan is determined.  
2. If the fan is on, the sequence will check if the system is  
in Occupied mode.  
3. If the system is in Occupied mode, the sequence will de-  
termine if the reset option is enabled.  
4. If the reset option is enabled, the sequence will read the  
space temperature and compare it to the Occupied Cool  
set point. If the temperature is below the Occupied Cool  
set point, the algorithm will compute the reset value and  
compare this value against the reset limit. If it is greater  
than the reset limit, the sequence will use the reset limit  
as the reset value.  
Fig. 36 — Space Temperature Sensor Wiring  
41  
CAPACITY CONTROL, COOLING — The cooling capac-  
ity staging tables are shown in Tables 18 and 19.  
MOTORMASTERIII DEVICE — The Motormaster III  
Solid-State Head Pressure Control is a field-installed acces-  
sory, fan speed control device actuated by a temperature sen-  
sor. The Motormaster III device is specifically designed for  
use on Carrier equipment and controls the outdoor-fan mo-  
tor speed in response to the saturated condensing tempera-  
ture. For outdoor temperatures down to −20 F, the Motor-  
master III device maintains condensing temperature at  
100 F.  
Table 18 — Cooling Capacity Staging Table  
CV Units with 2 Compressors  
1
STAGES  
0
2
3
ECONOMIZER  
Compressor 1  
Compressor 2  
Off  
Off  
Off  
Off  
On  
Off  
On  
On  
NOTE: On CV units that require additional unloading, add suction pres-  
sure unloaders on Compressor 1 only.  
SERVICE  
Table 19 — Cooling Capacity Staging Table  
VAV Units with 2 Compressors  
and 2 Unloaders*  
Before performing service or maintenance operations on  
unit, turn off main power switch to unit. Turn off ac-  
cessory heater power switch if applicable. Electrical shock  
could cause personal injury.  
STAGES  
Compressor 1  
Unloader 1  
0
1
2
3
4
5
6
Off  
Off  
Off  
Off  
On  
On  
On  
Off  
On  
On  
Off  
Off  
On  
Off  
Off  
Off  
On  
On  
On  
On  
On  
On  
Off  
On  
On  
Off  
Off  
On  
Service Access — All unit components can be reached  
through clearly labelled hinged access doors. These doors  
are not equipped with tiebacks, so if heavy duty servicing is  
needed, either remove them or prop them open to prevent  
accidental closure.  
Unloader 2  
Compressor 2  
*40 ton units have only 1 unloader.  
Each door is held closed with 3 latches. The latches are  
secured to the unit with a single 14-in. - 20 x 12-in. long bolt.  
See Fig. 37.  
To open, loosen the latch bolt using a 716-in. wrench. Pivot  
the latch so it is not in contact with the door. Open the door.  
To shut, reverse the above procedure.  
NOTE: Disassembly of the top cover may be required under  
special service circumstances. It is very important that the  
orientation and position of the top cover be marked on the  
unit prior to disassembly. This will allow proper replace-  
ment of the top cover onto the unit and prevent rainwater  
from leaking into the unit.  
FIELD TEST — The field test program is initiated by mov-  
ing up DIP switch no. 4 to the OPEN position. The outdoor-  
air damper will close. The control allows 90 seconds for the  
damper to close in case it was in the full open position. Next,  
the indoor-fan contactor will be energized, and the outside-  
air damper will begin to open to its default value of 20% and  
stay at that position for a short period of time. The outdoor-  
air damper will then open to its full open position and stay  
at that position for a short period of time. The outdoor-air  
damper will then close.  
If the unit is equipped with power exhaust, stage 1 will be  
energized for 5 seconds. If the unit is configured for stage 2  
of power exhaust, stage 2 will be energized for 5 seconds  
after the first stage is deenergized.  
IMPORTANT: After servicing is completed, make sure  
door is closed and relatched properly, and that the latches  
are tight. Failure to do so can result in water leakage  
into the evaporator section of the unit.  
The first stage of heat will be energized for 30 seconds,  
after which the second stage heat will be energized for an  
additional 30 seconds. Heat is then deenergized.  
The last step is the Cooling mode. Outdoor-fan contactor  
no. 1 is energized. This is followed by each stage of cooling  
energized with a 10-second delay between stages. After this  
is complete, outdoor-fan contactor no. 2 is energized for  
10 seconds.  
The compressors will now deenergize, followed by the  
outdoor-fan contactors and indoor-fan contactors.  
The field test is then complete.  
TIME GUARDCIRCUIT — The Time Guard function (built  
into the rooftop’s control module board) maintains a mini-  
mum off time of 5 minutes and a minimum on time of  
10 seconds.  
CRANKCASE HEATER — The unit main power supply must  
remain on to provide crankcase heater operation. The crank-  
case heater in each compressor keeps oil free of refrigerant  
while compressor is off.  
Fig. 37 — Door Latch  
HEAD PRESSURE CONTROL — Each unit has a fan cy-  
cling, outdoor thermostat to shut off outdoor-fan motor(s) at  
55 F (one outdoor-fan motor on 024-034 units and 2 outdoor-  
fan motors on 038-048 units). The head pressure control per-  
mits the unit to operate with correct condensing temperatures  
down to 35 F outdoor-air temperature.  
42  
CONDENSER AND EVAPORATOR-FAN MOTOR BEAR-  
INGS — The condenser and evaporator-fan motors have  
permanently-sealed bearings, so no field lubrication is  
necessary.  
Cleaning — Inspect unit interior at beginning of each heat-  
ing and cooling season and as operating conditions require.  
Remove unit top panel and/or side panels for access to unit  
interior.  
EVAPORATOR COIL — Clean as required with a commer-  
cial coil cleaner.  
Evaporator Fan Performance Adjustment  
(Fig. 38) — Fan motor pulleys are factory set for speed  
shown in Table 1 (factory speed setting).  
CONDENSER COIL — Clean condenser coil annually and  
as required by location and outdoor-air conditions. Inspect  
coil monthly — clean as required.  
To change fan speeds, change pulleys.  
To align fan and motor pulleys:  
1. Shut off unit power supply.  
2. Loosen fan shaft pulley bushing.  
3. Slide fan pulley along fan shaft.  
4. Make angular alignment by loosening motor from mount-  
ing plate.  
5. Retighten pulley.  
CONDENSATE DRAIN — Check and clean each year at  
start of cooling season. In winter, keep drains and traps dry.  
FILTERS — Clean or replace at start of each heating and  
cooling season, or more often if operating conditions re-  
quire. Refer to Table 1 for type and size.  
NOTE: The unit requires industrial grade throwaway filters  
capable of withstanding face velocities up to 625 fpm.  
IMPORTANT: Check to ensure that the unit drive  
matches the duct static pressure in Tables 12 to 14.  
OUTDOOR-AIR INLET SCREENS — Clean screens with  
steam or hot water and a mild detergent. Do not use throw-  
away filters in place of screens.  
Evaporator Fan Service and Replacement  
1. Turn off unit power.  
Lubrication  
2. Remove supply-air section panels.  
3. Remove belt and blower pulley.  
4. Loosen set screws in blower wheels.  
5. Remove locking collars from bearings.  
6. Remove shaft.  
7. Remove venturi on opposite side of bearing.  
8. Lift out wheel.  
9. Reverse above procedure to reinstall fan.  
10. Check and adjust belt tension as necessary.  
COMPRESSORS — Each compressor is charged with the  
correct amount of oil at the factory. The correct oil charge is  
shown in Table 1. If oil is visible in the compressor sight  
glass, check unit for operating readiness as described in Start-Up  
section, then start the unit. Observe oil level and add oil, if  
required, to bring oil level in compressor crankcase up to  
1
1
between ⁄4 and ⁄3 of sight glass during steady operation.  
If oil charge is above 13 sight glass, do not remove any oil  
until the compressor crankcase heater has been energized for  
at least 24 hours with compressor off.  
When additional oil or a complete charge is required, use  
only Carrier-approved compressor oil:  
Petroleum Specialties, Inc. . . . . . . . . . . . . . . . . . Cryol 150  
Texaco, Inc. . . . . . . . . . . . . . . . . . . . . . . . . . Capella WF-32  
Witco Chemical Corp. . . . . . . . . . . . . . . . . . . . Suniso 3GS  
IMPORTANT: Do not use reclaimed oil or oil that has  
been exposed to the atmosphere. Refer to Carrier Stand-  
ard Service Techniques Manual, Chapter 1, Refriger-  
ants section, for procedures to add or remove oil.  
FAN SHAFT BEARINGS — Lubricate the bearings at least  
twice annually with suitable bearing grease. Do not over grease.  
Typical lubricants are show below:  
MANUFACTURER  
LUBRICANT  
Texaco  
Mobil  
Sunoco  
Texaco  
Regal AFB-2*  
Mobilplex EP No. 1  
Prestige 42  
Fig. 38 — Evaporator-Fan Pulley Alignment  
and Adjustment  
Multifak 2  
*Preferred lubricant because it contains rust and oxidation inhibitors.  
43  
3. Fully retract motor plate adjusting bolts.  
4. Loosen the 2 rear (nearest the evaporator coil) motor  
plate nuts.  
5. Remove the 2 front motor plate nuts and carriage bolts.  
6. Slide motor plate to the rear (toward the coil) and re-  
move fan belt(s).  
7. Slide motor plate to the front and hand tighten one of  
the rear motor plate nuts (tight enough to prevent the  
motor plate from sliding back but loose enough to allow  
the plate to pivot upward).  
8. Pivot the front of the motor plate upward enough to al-  
low access to the motor mounting hex bolts and secure  
in place by inserting a prop.  
Belt Tension Adjustment — To adjust belt tension:  
1. Remove power to unit.  
2. Remove motor mount nuts and bolts.  
3. Loosen fan motor nuts. See Fig. 39.  
4. Turn motor jacking bolts to move motor mounting plate  
left or right for proper belt tension. A slight bow should  
be present in the belt on the slack side of the drive while  
running under full load.  
5. Tighten nuts.  
6. Adjust bolts and nut on mounting plate to secure motor  
in fixed position. Recheck belt tension after 24 hours of  
operation. Adjust as necessary.  
Condenser-Fan Adjustment  
1. Shut off unit power supply.  
2. Remove fan guard.  
9. Remove the nuts from the motor mounting hex bolts and  
remove motor.  
10. Reverse above steps to install new motor.  
3. Loosen fan hub setscrews.  
4. Adjust fan height on shaft using a straightedge placed across  
venturi and measure per Fig. 40.  
Power Failure — Dampers have a spring return. In event  
of power failure, dampers will return to fully closed position  
until power is restored.  
5. Tighten setscrews and replace fan guard.  
6. Turn on unit power.  
Refrigerant Charge — Amount of refrigerant charge  
is listed on unit nameplate and in Table 1. Refer to Carrier  
GTAC II; Module 5; Charging, Recovery, Recycling, and Rec-  
lamation section for charging methods and procedures.  
Evaporator-Fan Motor Replacement  
1. Shut off unit power supply.  
2. Remove upper outside panel and open hinged door to  
gain access to motor.  
Unit panels must be in place when unit is operating dur-  
ing charging procedure.  
NO CHARGE — Use standard evacuating techniques. After  
evacuating system, weigh in the specified amount of refrig-  
erant (refer to Table 1).  
LOW CHARGE COOLING — Using appropriate cooling  
charging chart (see Fig. 41 and 42), add or remove refrig-  
erant until conditions of the appropriate chart are met. Note  
that charging chart is different from those normally used. An  
accurate pressure gage and temperature sensing device are  
required. Measure liquid line pressure at the liquid line serv-  
ice valve using pressure gage. Connect temperature sensing  
device to liquid line near the liquid line service valve and  
insulate it so that outdoor ambient temperature does not af-  
fect reading. Indoor-air cfm must be within normal operat-  
ing range of unit. Take outdoor ambient temperature and read  
the suction pressure gage. Refer to appropriate chart to de-  
termine correct suction temperature. If intersection point on  
chart is above the curve, add refrigerant. If intersection point  
on chart is below curve, carefully recover some of the charge.  
Recheck suction pressure as charge is adjusted.  
Filter Drier — Replace whenever refrigerant system is  
exposed to atmosphere.  
Thermostatic Expansion Valve (TXV) — Each cir-  
cuit has one. It is nonadjustable and is factory set to main-  
tain 10 to 13° F superheat leaving the evaporator coil. Con-  
trols flow of liquid refrigerant to the evaporator coils.  
Fig. 39 — Belt Tension Adjustment  
Protective Devices  
COMPRESSOR PROTECTION  
Overcurrent — Each compressor has one manual reset, cali-  
brated trip, magnetic circuit breaker. Do not bypass connec-  
tions or increase the size of the circuit breaker to correct trouble.  
Determine the cause and correct it before resetting the breaker.  
Overtemperature — Each 06D type compressor (024-038 units  
only) has an internal protector to protect it against exces-  
sively high discharge gas temperatures.  
Fig. 40 — Condenser-Fan Adjustment  
44  
Crankcase Heater — Each compressor has a crankcase heater  
to prevent absorption of liquid refrigerant by oil in the crank-  
case when the compressor is idle. Since power for the crank-  
case heaters is drawn from the unit incoming power, main  
unit power must be on for the heaters to be energized.  
Relief Devices — All units have relief devices to pro-  
tect against damage from excessive pressures (i.e., fire). These  
devices are installed on the suction line, liquid line, and on  
the compressor.  
Control Circuit, 24-V — This control circuit is pro-  
tected against overcurrent by a 3.2-amp circuit breaker (CB4).  
Breaker can be reset. If it trips, determine cause of trouble  
before resetting.  
IMPORTANT: After a prolonged shutdown or serv-  
ice job, energize the crankcase heaters for 24 hours  
before starting the compressors.  
Control Circuit, 115-V — This control circuit is pro-  
tected against overcurrent by a 5.0-amp circuit breaker (CB3).  
Breaker can be reset. If it trips, determine cause of trouble  
before resetting.  
EVAPORATOR-FAN MOTOR PROTECTION — A man-  
ual reset, calibrated trip, magnetic circuit breaker protects  
against overcurrent. Do not bypass connections or increase  
the size of the breaker to correct trouble. Determine the cause  
and correct it before resetting the breaker. If the evaporator-  
fan motor is replaced with a different horsepower motor, re-  
sizing of the circuit breaker is required. Contact Carrier Ap-  
plication Engineering.  
Compressor Lockout Logic — If any of the safe-  
ties trip, the circuit will automatically reset (providing the  
safety has reset) and restart the compressor in 15 minutes. If  
any of the safeties trip 3 times within a 90-minute period,  
then the circuit will be locked out and will require manual  
resetting by turning off either the unit disconnect or the con-  
trol circuit breaker, or opening the thermostat.  
CONDENSER-FAN MOTOR PROTECTION — Each  
condenser-fan motor is internally protected against  
overtemperature.  
Replacement Parts — A complete list of replacement  
parts may be obtained from any Carrier distributor upon  
request.  
HIGH- AND LOW-PRESSURE SWITCHES — If either  
switch trips, or if the compressor overtemperature switch ac-  
tivates, that refrigerant circuit will be automatically locked  
out. To reset, manually move the thermostat setting.  
FREEZE PROTECTION THERMOSTAT (FPT) — An FPT  
is located on the evaporator coil for each circuit. It detects  
frost build-up and turns off the compressor, allowing the coil  
to clear. Once the frost has melted, the compressor can be  
reenergized.  
Fig. 41 — Cooling Charging Chart,  
Sizes 024-034  
Fig. 42 — Cooling Charging Chart,  
Sizes 038-048  
45  
TROUBLESHOOTING  
Typical refrigerant circuiting diagrams are shown in Fig. 43-45.  
LEGEND  
FPS  
HPS  
LPS  
Freeze Protection Switch  
High-Pressure Switch  
Low-Pressure Switch  
Fig. 43 — Typical Refrigerant Circuiting  
(50EJ,EK,EW,EY024-034)  
46  
LEGEND  
FPS  
HPS  
LPS  
Freeze Protection Switch  
High-Pressure Switch  
Low-Pressure Switch  
Fig. 44 — Typical Refrigerant Circuiting  
(50EJ,EK,EW,EY038,044)  
47  
LEGEND  
FPS  
HPS  
LPS  
Freeze Protection Switch  
High-Pressure Switch  
Low-Pressure Switch  
Fig. 45 — Typical Refrigerant Circuiting  
(50EJ,EW048)  
48  
to Table 20 below for a description of alarms. The yellow  
LED blinks during transmission with the CCN (Carrier Com-  
fort Network). The green LED blinks during transmission  
with the expansion board.  
Diagnostic LEDs (Light-Emitting Diodes) — There  
are 3 LEDs (red, yellow, and green) on the lower right hand  
side of the control board. The red light is used to check  
unit operation and alarms. A constant pulse is normal unit  
operation. A series of quick blinks indicates an alarm. Refer  
Table 20 — Control Board LED Alarms  
LED  
BLINKS  
ERROR  
CODE  
TROUBLESHOOTING  
COMMENTS  
DESCRIPTION  
1
2
Normal Operation  
The expansion board and control board flash the red LED in one-  
second intervals when the board is operating properly.  
HF-13  
HF-14  
HF-15  
Compressor 1 Safety  
Compressor 2 Safety  
Thermostat Failure  
The high or low pressure safety switch for compressor no. 1 has  
opened for 3 seconds. The error will be cleared and compressor  
no. 1 will be allowed to turn on in 15 minutes. If the safeties have  
been tripped 3 times in 90 minutes, compressor no. 1 will be  
locked out until the control board has been manually reset.  
3
4
The high or low pressure safety switch for compressor no. 2 has  
opened for 3 seconds. The error will be cleared and compressor  
no. 2 will be allowed to turn on in 15 minutes. If the safeties have  
been tripped 3 times in 90 minutes, compressor no. 2 will be  
locked out until the control board has been manually reset.  
The thermostat is calling for both heating and cooling at the  
same time. The unit will operate on a first call basis and will auto-  
matically reset.  
5
6
7
8
HF-05  
HF-06  
HF-03  
HF-12  
SAT Thermistor Failure  
OAT Thermistor Failure  
Space Temp. Sen. Failure  
RAT Thermistor Failure  
The supply-air temperature (SAT) sensor has failed. First check for  
wiring errors, then replace sensor.  
The outside-air temperature (OAT) sensor has failed. First check  
for wiring errors, then replace sensor.  
The space temperature sensor has failed. First check for wiring  
errors, then replace sensor.  
The return-air temperature (RAT) sensor has failed. Ensure that  
the unit is a VAV unit. If NOT a VAV unit set DIP switch position 1  
to the closed position and reset power. Then check for wiring  
errors. Finally, replace sensor.  
9
SE-05  
Loss of Communications  
with Expansion board  
Communications between the expansion board and the control  
board have been interrupted. Ensure that an expansion board  
is installed and wired using the wire harness supplied with the  
expansion module. If an expansion board is not used ensure that  
DIP switch position 3 is in the closed position, and reset power.  
10  
11  
HF-16  
HF-17  
Control Board Failure  
Generated when hardware has failed on control board. Replace  
the control board.  
Expansion Board Failure  
Generated when hardware has failed on the expansion board.  
Replace the expansion board.  
LEGEND  
DIP  
LED  
VAV  
Dual In-Line Package  
Light-Emitting Diode  
Variable Air Volume  
49  
Tables 21-23 show the input and output channel designations.  
Table 21 — I/O Channel Designations  
Table 22 — I/O Channel Designations  
Base Module — VAV  
Base Module — CV  
TERMINAL  
NO.  
TERMINAL  
NO.  
ASSIGNMENT  
ASSIGNMENT  
T1-2  
SPT (CCN) — 10KThermistor  
STO (CCN) — 10KThermistor  
OAT — 5KThermistor  
SAT — 5KThermistor  
T1-2  
SPT (CCN) — 10KThermistor  
RAT — 5KThermistor  
OAT — 5KThermistor  
SAT — 5KThermistor  
T3-4  
T3-4  
T5-6  
T5-6  
T7-8  
T7-8  
T9-10  
T9-10  
T11-12  
T13-14  
T15-16  
T17-25  
T18-25  
T19-25  
T20-25  
T21-25  
T22-25  
T23-25  
T24-25  
T26-27  
T28-29  
T30-29  
T31-32  
T33-32  
T34-35  
T36-35  
T37-38  
T39-38  
K1  
T11-12  
T13-14  
T15-16  
T17-25  
T18-25  
T19-25  
T20-25  
T21-25  
T22-25  
T23-25  
T24-25  
T26-27  
T28-29  
T30-29  
SAT Reset — AI (2-10 vdc)  
SAT Reset — AI (2-10 vdc)  
Y1 or Remote Start/Stop — DI (24 vac)  
Y2 — DI (24 vac)  
Remote Start/Stop — DI (24 vac)  
W1 — DI (24 vac)  
W2 — DI (24 vac)  
G — DI (24 vac)  
Compressor 1 Safety — DI (24 vac)  
Compressor 2 Safety — DI (24 vac)  
Outside Air Enthalpy — DI (24 vac)  
Economizer Pos. — AO (4-20 mA)  
Heat 1 Relay — DO (24 vac)  
Heat 2 Relay — DO (24 vac)  
Compressor 1 Safety — DI (24 vac)  
Compressor 2 Safety — DI (24 vac)  
Outside Air Enthalpy — DI (24 vac)  
Economizer Pos. — AO (4-20 mA)  
Heat 1 Relay — DO (115 vac)  
Heat Interlock Relay — DO (115 vac)  
Modulated Power Exhaust — DO (115 vac)  
CV Power Exhaust 1/Modulating Pwr Exht — DO  
(115 vac)  
T31-32  
T33-32  
T34-35  
T36-35  
T37-38  
T39-38  
K1  
CV Power Exhaust 2 — DO (115 vac)  
Condenser Fan — DO (115 vac)  
OFC2 — DO (115 vac)  
Condenser Fan — DO (115 vac)  
OFC2 — DO (115 vac)  
Unloader 1 — DO (115 vac)  
Unloader 2 — DO (115 vac)  
Indoor Fan Relay — DO (HV)  
Compr. 1 — DO (HV)  
Compr. 2 — DO (HV)  
Indoor Fan Relay — DO (HV)  
Compr. 1 — DO (HV)  
Compr. 2 — DO (HV)  
K2  
K2  
K3  
K3  
LEGEND  
(Tables 21 and 22)  
AI  
Analog Input  
AO  
CCN  
CV  
Analog Output  
Carrier Comfort Network  
Constant Volume  
Direct Input  
DI  
DO  
HV  
Direct Output  
High Voltage  
K⍀  
OAT  
OFC  
RAT  
SAT  
SPT  
STO  
T
Kilo-Ohms  
Outdoor-Air Temperature  
Outdoor Fan Contactor  
Return-Air Temperature  
Supply-Air Temperature  
Space Temperature  
Space Temperature Offset  
Terminal  
VAV  
Variable Air Volume  
50  
Table 23 — I/O Channel Designations Expansion  
Module — CV and VAV  
TERMINAL  
ASSIGNMENT  
NO.  
T1-2  
T3-4  
T5-6  
T7-8  
T9-10  
T11-12  
T13-14  
T15-16  
T17-25  
T18-25  
T19-25  
T20-25  
T21-25  
T22-25  
T23-25  
T24-25  
T26-27  
T28-29  
T30-29  
T31-32  
T33-32  
T34-35  
T36-35  
T37-38  
T39-38  
K1  
IAQ Indoor — AI (2-10 vdc)  
IAQ Outdoor — AI (2-10 vdc)  
Fan Status — DI (24 vac)  
Filter Status — DI (24 vac)  
Field Applied Status — DI (24 vac)  
Demand Limit — DI (24 vac)  
Fire — Unit Shutdown — DI (24 vac)  
Fire — Pressurization — DI (24 vac)  
Fire — Evacuation — DI (24 vac)  
Fire — Smoke Purge — DI (24 vac)  
Alarm Light Indicator — DO (24 vac)  
Power Exhaust Fire #1 — DO (115 vac)  
Power Exhaust Fire #2 — DO (115 vac)  
Power Exhaust Fire #3 — DO (115 vac)  
Power Exhaust Fire #4 — DO (115 vac)  
K2  
K3  
LEGEND  
AI  
Analog Input  
Direct Input  
Direct Output  
Indoor Air Quality  
Terminal  
DI  
DO  
IAQ  
T
51  
PACKAGED SERVICE TRAINING  
Our packaged service training programs provide an excellent way to increase your knowledge of the  
equipment discussed in this manual. Product programs cover:  
• Unit Familiarization  
• Installation Overview  
• Maintenance  
• Operating Sequence  
A large selection of product, theory, and skills programs is available. All programs include a video  
cassette and/or slides and a companion booklet. Use these for self teaching or to conduct full training  
sessions.  
For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are  
included.  
Copyright 1996 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1  
PC 111  
Catalog No. 535-006  
Printed in U.S.A.  
Form 50E-3SI  
Pg 54  
8-96  
Replaces: 50E-1SI  
Tab 1b  
START-UP CHECKLIST  
MODEL NO.:  
SERIAL NO.:  
TECHNICIAN:  
SOFTWARE VERSION (SEE FIG. 15)  
DATE:  
PRE-START-UP:  
VERIFY THAT DIP SWITCH SETTINGS ARE CORRECT  
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT  
REMOVE ALL SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTRUCTIONS  
VERIFY INSTALLATION OF ECONOMIZER HOOD  
VERIFY INSTALLATION OF ALL OPTIONS AND ACCESSORIES  
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS  
VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT  
CHECK THAT INDOOR-AIR FILTER IS CLEAN AND IN PLACE  
VERIFY THAT UNIT IS LEVEL WITHIN TOLERANCES  
CHECK FAN WHEELS AND PROPELLERS FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SET SCREW  
IS TIGHT  
VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED  
VERIFY THAT SUCTION, DISCHARGE, AND LIQUID LINE SERVICE VALVES ON EACH CIRCUIT ARE OPEN  
START-UP  
ELECTRICAL  
SUPPLY VOLTAGE L1-L2  
L2-L3  
L3-L1  
COMPRESSOR AMPS — COMPRESSOR NO. 1  
— COMPRESSOR NO. 2  
L1  
L1  
L2  
L2  
L3  
L3  
SUPPLY FAN AMPS (CV)  
(VAV)  
EXHAUST FAN AMPS  
*
*VAV fan supply amps reading must be taken with a true RMS meter for accurate readings.  
ELECTRIC HEAT AMPS (IF SO EQUIPPED) L1  
L2  
L3  
TEMPERATURES  
OUTDOOR-AIR TEMPERATURE  
RETURN-AIR TEMPERATURE  
COOLING SUPPLY AIR  
F
DB (Dry-Bulb)  
DB  
F
F
F
WB (Wet-Bulb)  
ELECTRIC HEAT SUPPLY AIR (IF SO EQUIPPED)  
F
PRESSURES  
REFRIGERANT SUCTION  
CIRCUIT NO. 1  
PSIG  
PSIG  
CIRCUIT NO. 2  
CIRCUIT NO. 2  
PSIG  
PSIG  
REFRIGERANT DISCHARGE CIRCUIT NO. 1  
VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGE 45  
CL-1  
START-UP CHECKLIST (cont)  
GENERAL  
ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS  
ENSURE DRIVES OPERATE WITHIN LIMITS OF FAN PERFORMANCE TABLES  
HIGH-PRESSURE SWITCH SETTING  
LOW-PRESSURE SWITCH SETTING  
MOTOR PULLEY PART NUMBER  
FAN PULLEY PART NUMBER  
BELT PART NUMBER  
PSIG  
PSIG  
BELT SIZE  
in.  
in.  
FILTER QUANTITY  
FILTER SIZES  
ADDITIONAL NOTES:  
Copyright 1996 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1  
PC 111  
Catalog No. 535-006  
Printed in U.S.A.  
Form 50E-3SI  
Pg CL-2  
8-96  
Replaces: 50E-1SI  
Tab 1b  

Amcor 000E User Manual
Briggs Stratton Automobile Parts 31P900 User Manual
Brother MFC 7360N User Manual
Epson Stylus CX7400 User Manual
Frigidaire FSC18CH8MV User Manual
Fujitsu Printer FP 410 User Manual
Garmin STYLUS PRO PRO 4900 User Manual
Garmin STYLUS PRO PRO WT7900 User Manual
Goodman Mfg AVPTC183014AA User Manual
HP Hewlett Packard LaserJet M1522 MFP Series User Manual