NXL HVAC & COMPACT
USER’S MANUAL
Download from Www.Somanuals.com. All Manuals Search And Download.
CONTENTS
NXL HVAC & COMPACT
USER’S MANUAL
INDEX
1
2
SAFETY
EU DIRECTIVE
3
RECEIPT OF DELIVERY
TECHNICAL DATA
4
5
INSTALLATION
6
CABLING AND CONNECTIONS
CONTROL KEYPAD
7
8
COMMISSIONING
9
FAULT TRACING
10
11
12
DESCRIPTION OF BOARD NXLOPTAA
DESCRIPTION OF BOARD NXLOPTAI
NXL HVAC BASIC SPEED CONTROL
OTHER NXL MANUALS:
NXL HVAC APPLICATION MANUAL
Programming Manual for NXL HVAC drives
MULTICONTROL APPLICATION MANUAL
Programming Manual for standard NXL and NXL Compact.
Download from Www.Somanuals.com. All Manuals Search And Download.
ABOUT THE NXL HVAC & COMPACT USER'S MANUAL
AND NXL APPLICATION MANUALS
Congratulations for choosing the Smooth Control provided by NXL frequency converters!
The User's Manual will provide you with the necessary information about the installation, commissioning
and operation of NXL Frequency Converter. We recommend that you carefully study these instructions
before powering up the frequency converter for the first time.
In the NXL HVAC Application Manual and the Multi-Control Application Manual you will find information
about the application used in Honeywell NXL drives.
Download from Www.Somanuals.com. All Manuals Search And Download.
HHoonneeyywweellll
HHoonneeyywweellll
Index
5(96)
NXL HVAC & COMPACT User's Manual
Index
Date: 28.10.2008
1.
SAFETY .................................................................................................................................. 7
1.1
1.2
1.3
1.4
Warnings ............................................................................................................................. 7
Safety instructions................................................................................................................ 7
Earthing and earth fault protection ....................................................................................... 8
Running the motor ............................................................................................................... 8
2.
EU DIRECTIVE ....................................................................................................................... 9
2.1
2.2
CE marking.......................................................................................................................... 9
EMC directive ...................................................................................................................... 9
2.2.1
2.2.2
2.2.3
2.2.4
2.2.5
General ............................................................................................................................ 9
Technical criteria.............................................................................................................. 9
NXL frequency converter EMC classification.................................................................... 9
Honeywell EMC classes and market requirements......................................................... 10
Manufacturer's declaration of conformity ........................................................................ 10
3.
4.
5.
6.
RECEIPT OF DELIVERY ...................................................................................................... 13
3.1
3.2
3.3
3.4
3.5
Type designation code NXL Compact................................................................................ 13
Type designation code NXL HVAC .................................................................................... 14
Storage.............................................................................................................................. 14
Maintenance ...................................................................................................................... 14
Warranty............................................................................................................................ 15
TECHNICAL DATA............................................................................................................... 16
4.1
4.2
Introduction........................................................................................................................ 16
Power ratings..................................................................................................................... 18
4.2.1
4.2.1
NXL Compact – Mains voltage 208 – 240 V & 380 – 500 V............................................ 18
NXL HVAC – Mains voltage 380 – 500 V ....................................................................... 19
4.3
5.1
Technical data ................................................................................................................... 20
INSTALLATION .................................................................................................................... 22
Mounting............................................................................................................................ 22
5.1.1
5.1.2
NXL Compact (MF2 and MF3)........................................................................................ 22
NXL HVAC (MF4 – MF6)................................................................................................ 25
5.2
5.3
Cooling .............................................................................................................................. 26
Changing EMC protection class from H/C to T in NXL HVAC ............................................ 27
CABLING AND CONNECTIONS .......................................................................................... 28
6.1
Power connections............................................................................................................. 28
6.1.1
Cabling........................................................................................................................... 29
6.1.1.1 Cable and fuse sizes .................................................................................................. 30
6.1.2
6.1.3
Mounting of cable accessories ....................................................................................... 31
Installation instructions................................................................................................... 33
6.1.3.1 Stripping lengths of motor and mains cables .............................................................. 34
6.1.3.2 Installation of cables to NXL ....................................................................................... 35
6.1.4
6.1.5
Cable installation and the UL standards ......................................................................... 42
Cable and motor insulation checks................................................................................. 42
6.2
Control unit ........................................................................................................................ 43
6.2.1
6.2.2
NXL Compact (MF2 – MF3) ........................................................................................... 43
NXL HVAC (MF4 – MF6)................................................................................................ 43
6.2.2.1 Allowed option boards in NXL HVAC:......................................................................... 43
6.2.3
Control connections........................................................................................................ 44
6.2.4
Control I/O...................................................................................................................... 45
Download from Www.Somanuals.com. All Manuals Search And Download.
6(96)
Index
6.2.5
Control terminal signals.................................................................................................. 46
6.2.5.1 Jumper selections on NXL basic board....................................................................... 47
6.2.6
Motor thermistor (PTC) connection................................................................................. 50
CONTROL KEYPAD............................................................................................................. 51
Indications on the Keypad display...................................................................................... 51
7.
7.1
7.1.1
7.1.2
7.1.3
Drive status indications................................................................................................... 51
Control place indications ................................................................................................ 52
Numeric indications........................................................................................................ 52
7.2
Keypad push-buttons......................................................................................................... 53
7.2.1
Button descriptions......................................................................................................... 53
Start-up wizard................................................................................................................... 54
Navigation on the control keypad....................................................................................... 55
7.3
7.4
7.4.1
7.4.2
7.4.3
Monitoring menu (M1) .................................................................................................... 58
Parameter menu (P2)..................................................................................................... 60
Keypad control menu (K3).............................................................................................. 62
7.4.3.1 Selection of control place............................................................................................ 62
7.4.3.2 Keypad reference....................................................................................................... 63
7.4.3.3 Keypad direction......................................................................................................... 63
7.4.3.4 Stop button activation................................................................................................. 63
7.4.4
Active faults menu (F4)................................................................................................... 64
7.4.4.1 Fault types.................................................................................................................. 64
7.4.5
7.4.6
7.4.7
Fault codes..................................................................................................................... 65
Fault history menu (H5).................................................................................................. 67
System menu (S6).......................................................................................................... 68
7.4.7.1 Copy parameters........................................................................................................ 70
7.4.7.2 Security ...................................................................................................................... 70
7.4.7.3 Keypad settings.......................................................................................................... 71
7.4.7.4 Hardware settings....................................................................................................... 72
7.4.7.5 System information..................................................................................................... 73
7.4.7.6 AI mode...................................................................................................................... 76
7.4.8
Modbus interface............................................................................................................ 77
7.4.8.1 Modbus RTU protocol................................................................................................. 77
7.4.8.2 Termination Resistor .................................................................................................. 78
7.4.8.3 Modbus address area................................................................................................. 78
7.4.8.4 Modbus process data ................................................................................................. 78
7.4.8.5 Fieldbus parameters................................................................................................... 80
7.4.9
Expander board menu (E7) ............................................................................................ 81
7.5
Further keypad functions.................................................................................................... 81
8.
COMMISSIONING................................................................................................................. 82
8.1
8.2
8.3
Safety ................................................................................................................................ 82
Commissioning of the frequency converter ........................................................................ 82
Basic parameters............................................................................................................... 85
8.3.1
8.3.2
8.3.3
Monitoring values (Control keypad: menu M1) ............................................................... 85
HVAC parameters in NXL HVAC (Control keypad: Menu P2 ꢀ B2.1)............................ 86
Basic parameters (Control keypad: Menu P2 ꢀ B2.1 / B2.1.15)..................................... 87
9.
FAULT TRACING.................................................................................................................. 88
DESCRIPTION OF EXPANDER BOARD NXLOPTAA ......................................................... 92
DESCRIPTION OF EXPANDER BOARD NXLOPTAI........................................................... 93
NXL HVAC Basic Speed Control – Quick SETUP .............................................................. 95
10.
11.
12.
Download from Www.Somanuals.com. All Manuals Search And Download.
1
7(96)
Honeywell
HHoonneeyywweellll
Safety
1.
SAFETY
ONLY A COMPETENT ELECTRICIAN MAY CARRY OUT
THE ELECTRICAL INSTALLATION
1.1 Warnings
The components of the power unit of the frequency converter are live
when NXL is connected to mains potential. Coming into contact with
this voltage is extremely dangerous and may cause death or severe
1
injury. The control unit is isolated from the mains potential.
The motor terminals U, V, W (T1, T2, T3) and the DC-link/brake resistor
terminals –/+ (in NXL ≥1.1 kW) are live when NXL is connected to mains,
even if the motor is not running.
2
3
The control I/O-terminals are isolated from the mains potential. However,
the relay outputs and other I/O-terminals may have a dangerous control
voltage present even when NXL is disconnected from mains.
WARNING
The frequency converter has a large capacitive leakage current.
4
5
If the frequency converter is used as a part of a machine, the machine
manufacturer is responsible for providing the machine with a main switch
(EN 60204-1).
Only spare parts delivered by Honeywell can be used.
6
7
The heat sink of types MF2 and MF3 may be hot when the frequency
converter is in use. Coming into contact with the heat sink may cause
burns.
HOT SURFACE
1.2 Safety instructions
The Honeywell NXL frequency converter is meant for fixed installations
only.
1
2
3
Do not perform any measurements when the frequency converter is
connected to the mains.
After disconnecting the frequency converter from the mains, wait until the
fan stops and the indicators on the display go out. Wait 5 more minutes
before doing any work on NXL connections.
Do not perform any voltage withstand tests on any part of NXL. There is
a certain procedure according to which the tests shall be performed.
Ignoring this procedure may result in damaged product.
4
Prior to measurements on the motor or the motor cable, disconnect the
motor cable from the frequency converter.
5
6
Do not touch the IC-circuits on the circuit boards. Static voltage discharge
may damage the components.
Download from Www.Somanuals.com. All Manuals Search And Download.
1
8(96)
Safety
HHoonneeyywweellll
HHoonneeyywweellll
1.3 Earthing and earth fault protection
The Honeywell NXL frequency converter must always be earthed with an earthing conductor
connected to the earthing terminal
The earth fault protection inside the frequency converter protects only the converter itself against
earth faults in the motor or the motor cable.
Due to the high capacitive currents present in the frequency converter, fault current protective
switches may not function properly. If fault current protective switches are used they must be tested
with the drive with earth fault currents that are possible to arise in fault situations.
1.4 Running the motor
Warning symbols
For your own safety, please pay special attention to the instructions marked with the following
symbols:
= Dangerous voltage
WARNING
= General warning
HOT SURFACE
= Hot surface – Risk of burn
MOTOR RUN CHECK LIST
Before starting the motor, check that the motor is mounted properly and
ensure that the machine connected to the motor allows the motor to be
1
started.
Set the maximum motor speed (frequency) according to the motor and
the machine connected to it.
2
Before reversing the motor shaft rotation direction make sure that this
can be done safely.
3
WARNING
Make sure that no power correction capacitors are connected to the
motor cable.
4
Make sure that the motor terminals are not connected to mains potential.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
EU Directive
9(96)
2.
EU DIRECTIVE
2.1 CE marking
The CE marking on the product guarantees the free movement of the product within the EEA
(European Economic Area). It also guarantees that the product meets the various requirements
placed upon it (such as the EMC Directive and possibly other directives according to the so-called
new procedure).
NXL frequency converters carry the CE label as a proof of compliance with the Low Voltage
Directive (LVD) and the Electro Magnetic Compatibility (EMC). The company SGS FIMKO has acted
as the Competent Body.
2.2 EMC directive
2.2.1 General
The EMC Directive provides that the electrical apparatus must not excessively disturb the
environment they are used in, and, on the other hand, it shall have an adequate level of immunity
toward other disturbances from the same environment.
The compliance of NXL frequency converters with the EMC directive is verified with Technical
Construction Files (TCF) checked and approved by SGS FIMKO, which is a Competent Body.
2.2.2 Technical criteria
EMC compliance is a major consideration for NXL drives from the outset of the design. NXL
frequency converters are marketed throughout the world, a fact which makes the EMC requirements
of customers different. All NXL frequency converters are designed to fulfil even the strictest immunity
requirements.
2.2.3 NXL frequency converter EMC classification
NXL frequency converters are divided into two classes according to the level of electromagnetic
disturbances emitted. Later in this manual the division is made according to the mechanical sizes
(MF2, MF3, etc.). The technical data of the different sizes can be found in Chapter 0.
Class C (NXL HVAC IP54):
NXL HVAC drives with IP54 enclosure are delivered as class C products with an integrated RFI
filter. NXL HVAC drives IP54 selection fulfil the requirements of the product standard EN 61800-
3 (2004) category C1 (EN 55011 class B).
The emission levels correspond to the requirements of EN 61000-6-3.
Class N (NXL Compact):
No EMC emission protection. NXL Compact drives (frames MF2 and MF3) are delivered from the
factory without an integrated RFI filter as class N products. External RFI filters for these products for
class H are available.
Class H (NXL HVAC IP21):
NXL HVAC drives with IP21 enclosure are delivered as class H products with an integrated RFI
filter. NXL HVAC drives IP21 selection fulfil the requirements of the product standard EN 61800-
3 (2004) category C2 (EN 55011 class A).
The emission levels correspond to the requirements of EN 61000-6-4.
Class T:
The T-class converters have a small earth current and can be used with IT supplies only. If they are
used with other supplies no EMC requirements are complied with.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
10(96)
EU Directive
HHoonneeyywweellll
HHoonneeyywweellll
All NX frequency converters fulfil all EMC immunity requirements (standards EN 61000-6-1,
61000-6-2 and EN 61800-3).
2.2.4 Honeywell EMC classes and market requirements
1
2
3
4
5
6
NX EMC levels
Hospital
Airport Residential Area
O
Commercial
Light Industry
Area
Heavy Industry
C
H
L
O
R
R
R
R
O
R
O
R
T
R
(IT Network)
O = Optional, R= Required
2.2.5 Manufacturer's declaration of conformity
The following page presents the photocopy of the Manufacturer's Declaration of Conformity assuring
the compliance of frequency converters with the EMC-directives.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
EU Directive
11(96)
EU DECLARATION OF CONFORMITY
We
Manufacturer's name:
Vacon Oyj
Manufacturer's address:
P.O.Box 25
Runsorintie 7
FIN-65381 Vaasa
Finland
hereby declare that the product
Product name:
NXL Frequency Converter
Model designation:
NXL 0001 V3 5…to 0061 V3 5…
NXL 0002 V3 2...to 0006 V3 2…
has been designed and manufactured in accordance with the following standards:
Safety:
EN 50178 (1997), EN 60204-1 (1996)
EN 60950 (3rd edition 2000, as relevant)
EMC:
EN 61800-3 (1996)+A11(2000), EN 61000-6-2
(2001), EN 61000-6-4 (2001)
and conforms to the relevant safety provisions of the Low Voltage Directive (73/23/EEC) as
amended by the Directive (93/68/EEC) and EMC Directive 89/336/EEC as amended by
92/31/EEC.
It is ensured through internal measures and quality control that the product conforms at all
times to the requirements of the current Directive and the relevant standards.
In Vaasa, 6th of September, 2002
Vesa Laisi
President
The year the CE marking was affixed:
2002
2
Download from Www.Somanuals.com. All Manuals Search And Download.
12(96)
EU Directive
HHoonneeyywweellll
HHoonneeyywweellll
EU DECLARATION OF CONFORMITY
We
Manufacturer's name:
Vacon Oyj
Manufacturer's address:
P.O.Box 25
Runsorintie 7
FIN-65381 Vaasa
Finland
hereby declare that the product
Product name:
NXL HVAC DRIVE
Model designation:
HVAC03C… to HVAC61C…
has been designed and manufactured in accordance with the following standards:
Safety:
EN 50178 (1997), EN 60204-1 (1996)
EN 60950 (3rd edition 2000, as relevant)
EMC:
EN 61800-3 (1996)+A11(2000), EN 61000-6-2
(2001), EN 61000-6-4 (2001)
and conforms to the relevant safety provisions of the Low Voltage Directive (73/23/EEC) as
amended by the Directive (93/68/EEC) and EMC Directive 89/336/EEC as amended by
92/31/EEC.
It is ensured through internal measures and quality control that the product conforms at all
times to the requirements of the current Directive and the relevant standards.
In Vaasa, 10th of May, 2006
Vesa Laisi
President
The year the CE marking was affixed:
2002
2
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Receipt of delivery
13(96)
3.
RECEIPT OF DELIVERY
NXL frequency converters have undergone scrupulous tests and quality checks at the factory before
they are delivered to the customer. However, after unpacking the product, check that no signs of
transport damages are to be found on the product and that the delivery is complete (compare the
type designation of the product to the code below.
Should the drive have been damaged during the shipping, please contact primarily the cargo
insurance company or the carrier.
If the delivery does not correspond to your order, contact the supplier immediately.
3.1 Type designation code NXL Compact
NXL 0005 V3 5 C 1 N
1
S
Harware modifications:
S = Standard
D = DIN rail mounting
Brake chopper
0 = No brake chopper (MF2)
1 = Internal brake chopper
EMC emission level
N = No EMC emission protection
(External filters available for EN61800-3 cat. C2)
Enclosure classification
1 = IP20
Control keypad
B = No control keypad
C = Standard 7-segment keypad
Nominal mains voltage
2 = 208-240Vac
5 = 380-500Vac
Input Phases
V3 = 3 Phase
Nominal current (low overload)
0005 = 5A etc.
Product range: NXL
Figure 3-1. NXL Compact type designation code for sizes MF2 and MF3
Download from Www.Somanuals.com. All Manuals Search And Download.
3
14(96)
Receipt of delivery
HHoonneeyywweellll
HHoonneeyywweellll
3.2 Type designation code NXL HVAC
HVAC
03 C
2
Enclosure & EMC classification
2 = IP21, EMC class H (fulfils EN 61800-3 cat C2, EN 55011 class A)
5 = IP54, EMC class C (fullfils EN 61800-3 cat C1, EN 55011 class B)
Control keypad
C = Standard 7-segment keypad
Nominal current (low overload)
03 = 3 A etc.
Product range: HVAC = NXL HVAC
Figure 3-2. NXL HVAC type designation code for (sizes MF4 - MF6).
3.3 Storage
If the frequency converter is to be kept in store before use make sure that the ambient conditions are
acceptable:
Storing temperature
–40…+70°
C
Relative humidity
<95%, no condensation
3.4 Maintenance
In normal conditions, NXL frequency converters are maintenance-free. However, we recommend to
clean the heatsink (using e.g. a small brush) whenever necessary.
Most NXL drives are equipped with a cooling fan, which can easily be changed if necessary.
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Receipt of delivery
15(96)
3.5 Warranty
Only manufacturing defects are covered by the warranty. The manufacturer assumes no
responsibility for damages caused during or resulting from transport, receipt of the delivery,
installation, commissioning or use.
The manufacturer shall in no event and under no circumstances be held responsible for damages
and failures resulting from misuse, wrong installation, unacceptable ambient temperature, dust,
corrosive substances or operation outside the rated specifications. Neither can the manufacturer be
held responsible for consequential damages.
Honeywell's time of warranty is 30 months from the delivery or 24 months from the commissioning
whichever expires first.
The local distributor may grant a warranty time different from the above. This warranty time shall be
specified in the distributor's sales and warranty terms. Honeywell assumes no responsibility for any
other warranties than that granted by Honeywell itself.
In all matters concerning the warranty, please contact first your distributor.
Download from Www.Somanuals.com. All Manuals Search And Download.
16(96)
Technical data
HHoonneeyywweellll
HHoonneeyywweellll
4.
TECHNICAL DATA
4.1 Introduction
Honeywell NXL is a compact frequency converter with the output ranging from 250 W to 30 kW.
The Motor and Application Control Block is based on microprocessor software. The microprocessor
controls the motor basing on the information it receives through measurements, parameter settings,
control I/O and control keypad. The IGBT Inverter Bridge produces a symmetrical, 3-phase PWM-
modulated AC-voltage to the motor.
The control keypad constitutes a link between the user and the frequency converter. The control
keypad is used for parameter setting, reading status data and giving control commands. Instead of
the control keypad, also a PC can be used to control the frequency converter if connected through a
cable and a serial interface adapter (optional equipment).
You can have your Honeywell NXL drive equipped with control I/O boards NXLOPTAA, NXLOPTAI,
NXOPTB_ or NXOPTC_. Honeywell NXL HVAC series already includes I/O board NXLOPTAI as
standard.
All other sizes but MF2 have an internal brake chopper. For closer information, contact Honeywell
see back cover). The input EMC filters are available as options externally for MF2 and MF3. In other
sizes the filters are internal and included as standard.
Download from Www.Somanuals.com. All Manuals Search And Download.
4
Technical data
17(96)
Figure 4-1. NXL block diagram
4
Download from Www.Somanuals.com. All Manuals Search And Download.
18(96)
Technical data
HHoonneeyywweellll
HHoonneeyywweellll
4.2 Power ratings
4.2.1 NXL Compact – Mains voltage 208 – 240 V & 380 – 500 V
Mains voltage 208-240 V, 50/60 Hz, 1~/3~ Series NXL Compact
Frequency
Loadability
Motor shaft
power
converter type
Mechanical
size
Enclosure
and
protection
class
Nominal
input
current
1~/3~
Low
High
Low
High
Dimensions
WxHxD
Weight
(kg)
Rated
10%
over-
load
Rated
50%
con-
tinuous
continuous overload
current IH
(A)
current
(A)
40°C
50°C
current current
P(kW)
P(kW)
IL (A)
2,4
3,7
4,8
6,6
(A)
2,6
4,1
5,3
7,3
0,37
0,75
1,1
NXL 0002 2
NXL 0003 2
NXL 0004 2
NXL 0006 2
1,7
2,8
3,7
4,8
2,6
4,2
5,6
7,2
0,25
0,55
0,75
1,1
4,8/--
7,4/5,6
9,6/7,2
13,2/9,9
MF2/IP20
MF3/IP20
MF3/IP20
MF3/IP20
60x130x150
84x184x172
84x184x172
84x220x172
1,0
1,9
1,9
2,0
1,5
Table 4-1. Power ratings and dimensions of NXL, supply voltage 208-240V.
NOTE! NXL 0002 2 is suitable for single phase supply only
Mains voltage 380-500 V, 50/60 Hz, 3~ Series NXL Compact
Frequency
Loadability
Motor shaft power
Mechanical
size
Enclosure
and
protection
class
converter type
Low
High
Rated
con-
400V supply
500V supply
Nominal
input
current
Rated
con-
tinuous
10%
50%
over-
load
10%
over-
load
50%
over-
load
10%
over-
load
50%
over-
load
Dimensions
WxHxD
Weight
(kg)
over-
load tinuous
current current current current
40°C
50°C
40°C
50°C
IL (A)
1,9
2,4
3,3
4,3
5,4
(A)
2,1
2,6
3,6
4,7
5,9
IH (A)
1,3
1,9
2,4
3,3
4,3
(A)
2
2,9
3,6
5
P(kW) P(kW)
P(kW) P(kW)
60x130x150
60x130x150
84x220x172
84x220x172
84x220x172
0,55
0,75
1,1
NXL 0001 5
NXL 0002 5
NXL 0003 5
NXL 0004 5
NXL 0005 5
0,37
0,55
0,75
1,1
0,75
1,1
1,5
2,2
3
0,55
0,75
1,1
1,5
2,2
2,9
3,6
5,0
6,5
8,1
MF2/IP20
MF2/IP20
MF3/IP20
MF3/IP20
MF3/IP20
1,0
1,0
2,0
2,0
2,0
1,5
2,2
6,5
1,5
Table 4-2. Power ratings and dimensions of NXL, supply voltage 380-500V.
Download from Www.Somanuals.com. All Manuals Search And Download.
4
Technical data
19(96)
4.2.1 NXL HVAC – Mains voltage 380 – 500 V
Mains voltage 380-500 V, 50/60 Hz, 3~ Series NXL HVAC
Frequency
Loadability
Motor shaft power
Mechanical
size
Enclosure
and
protection
class
converter type
Low
High
Rated
con-
400V supply
500V supply
Rated
con-
tinuous
10%
50%
over-
load
10%
over-
load
50%
over-
load
10%
over-
load
50%
over-
load
Dimensions
WxHxD
Weight
(kg)
over-
load tinuous
current current current current
45°C
50°C
45°C
50°C
IL (A)
3,3
4,3
5,6
7,6
9
(A)
IH (A)
2,2
3,3
4,3
5,6
7,6
9
12
16
23
(A)
P(kW) P(kW)
P(kW) P(kW)
1,1
1,5
2,2
3
HVAC03C2
HVAC04C2
HVAC05C2
HVAC07C2
HVAC09C2
HVAC12C2
HVAC16C2
HVAC23C2
HVAC31C2
HVAC38C2
HVAC46C2
HVAC61C2
3,6
3,3
0,75
1,1
1,5
2,2
3
1,5
2,2
3
1,1
1,5
2,2
3
MF4/IP21
MF4/IP21
MF4/IP21
MF4/IP21
MF4/IP21
MF4/IP21
MF5/IP21
MF5/IP21
MF5/IP21
MF6/IP21
MF6/IP21
MF6/IP21
128x292x190
128x292x190
128x292x190
128x292x190
128x292x190
128x292x190
144x391x214
144x391x214
144x391x214
195x519x237
195x519x237
195x519x237
5
5
5
5
5
4,7
5,9
8,4
9,9
13,2
17,6
25,3
34
5,0
6,5
8,4
11,4
13,5
18
24
35
47
57
4
4
5,5
7,5
11
15
18,5
22
30
37
4
12
16
23
31
38
46
61
5,5
7,5
11
4
5,5
7,5
11
15
18,5
22
5
5,5
7,5
11
15
18,5
22
8,1
8,1
8,1
18,5
18,5
18,5
15
18,5
22
42
31
51
38
30
67
46
69
30
3,3
4,3
5,6
7,6
9
1,1
1,5
2,2
3
HVAC03C5
HVAC04C5
HVAC05C5
HVAC07C5
HVAC09C5
HVAC12C5
HVAC16C5
HVAC23C5
HVAC31C5
HVAC38C5
HVAC46C5
HVAC61C5
3,6
4,7
5,9
8,4
9,9
13,2
17,6
25,3
34
2,2
3,3
4,3
5,6
7,6
9
12
16
23
31
38
46
3,3
5,0
6,5
8,4
11,4
13,5
18
24
35
47
57
0,75
1,1
1,5
2,2
3
1,5
2,2
3
1,1
1,5
2,2
3
MF4/IP54
MF4/IP54
MF4/IP54
MF4/IP54
MF4/IP54
MF4/IP54
MF5/IP54
MF5/IP54
MF5/IP54
MF6/IP54
MF6/IP54
MF6/IP54
128x292x190
128x292x190
128x292x190
128x292x190
128x292x190
128x292x190
144x391x214
144x391x214
144x391x214
195x519x237
195x519x237
195x519x237
5
5
5
5
5
4
4
5,5
7,5
11
15
18,5
22
30
37
4
12
16
23
31
38
46
61
5,5
7,5
11
4
5,5
7,5
11
15
18,5
22
5
5,5
7,5
11
15
18,5
22
8,1
8,1
8,1
18,5
18,5
18,5
15
18,5
22
42
51
67
30
69
30
Table 4-3. Power ratings and dimensions of NXL HVAC, supply voltage 380 – 500V.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
20(96)
Technical data
HHoonneeyywweellll
HHoonneeyywweellll
4.3 Technical data
Mains
connection
Input voltage Uin
380 - 500V, -15%...+10% 3~
208…240V, -15%...+10% 3~
208…240V, -15%...+10% 1~
45…66 Hz
Once per minute or less (normal case)
0—Uin
Input frequency
Connection to mains
Output voltage
Continuous output
current
Motor
connection
IL: Ambient peak temperature max. +45°C (with 24h
average ambient +40°C),*
overload 1.1 x IL (1min/10min)
IH: Ambient temperature max. +50ºC,
overload 1.5 x IH (1min/10min)
150% (Low overload); 200% (High overload)
2 x IH 2 seconds every 20 seconds, if output frequency
<30Hz
Starting torque
Starting current
and temperature of heatsink <+60ºC
Output frequency
Frequency resolution
Control method
0…320 Hz
0,01 Hz
Frequency Control U/f
Open Loop Sensorless Vector Control
Control
characteristics
Switching frequency
(See parameter 2.6.8)
Frequency reference
Analogue input
Keypad reference
Field weakening point
Acceleration time
Deceleration time
Braking torque
1...16 kHz; Factory default 6 kHz
Resolution 0.1% (10bit), accuracy 1%
Resolution 0.01 Hz
30…320 Hz
0.1…3000 sec
0.1…3000 sec
DC-brake: 30%*TN (without brake option)
–10°C (no frost)…+45°C: IL
(ambient temperature derating 1,5%/Cº)
Ambient
conditions
Ambient operating
temperature
–10°C (no frost)…+50°C: IH
–40°C…+70°C
0…95% RH, non-condensing, non-corrosive,
no dripping water
Storage temperature
Relative humidity
Air quality:
- chemical vapours
- mechanical particles
Altitude
IEC 721-3-3, unit in operation, class 3C2
IEC 721-3-3, unit in operation, class 3S2
100% load capacity (no derating) up to 1000m
1-% derating for each 100m above 1000m; max. 3000m
5...150 Hz
Vibration:
EN50178/EN60068-2-6
Displacement amplitude 1(peak) mm at 5...15.8 Hz
Max acceleration amplitude 1 G at 15.8...150 Hz
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in package)
IP20; MF2 and MF3. IP21/IP54; MF4 – MF6
Shock
EN50178, IEC 68-2-27
Enclosure class
Technical data (continues on next page)
* In NXL Compact the maximum ambient operation temperature is +40°C. (+45°C only applies to NXL HVAC)
Download from Www.Somanuals.com. All Manuals Search And Download.
4
Technical data
21(96)
EMC
Immunity
Complies with EN50082-1, -2, EN61800-3
Emissions
MF2-MF3: EMC level N; With an external RFI filter (option)
attached EMC-level H (see Ch. 6.1.2.2)
MF4-MF6: IP21 : EMC-level H: EN 61800-3 (2004) Cat C2,
EN 55011 Class A
IP54 : EMC level C: EN 61800-3 (2004) Cat C1,
EN 55011 Class B
Safety
EN50178, EN60204-1, CE, UL, cUL, FI, GOST R, IEC
61800-5
(see unit nameplate for more detailed approvals)
Control
connections
Analogue input voltage
0...+10V, Ri = 200kΩ,
Resolution 10 bit, accuracy 1%
Analogue input current
Digital inputs
0(4)…20 mA, Ri = 250Ω differential
3 positive logic; 18…24VDC NXL Compact
6 positive logic; 18…24VDC NXL HVAC
+24V, 15%, max. 100mA
Auxiliary voltage
Output reference voltage +10V, +3%, max. load 10mA
Analogue output
0(4)…20mA; RL max. 500Ω; resolution 16 bit;
accuracy 1%
Relay outputs
1 programmable change over relay output NXL Compact
2 programmable change over relay output NXL HVAC
Switching capacity: 24VDC/8A, 250VAC/8A, 125VDC/0.4A
Rtrip = 4.7 kΩ (PTC) NXL HVAC
NXL_2: 437VDC; NXL_5: 911VDC
Motor thermistor Input *)
Overvoltage protection
Undervoltage protection
Earth-fault protection
Protections
NXL_2: 183VDC; NXL_5: 333VDC
In case of earth fault in motor or motor cable, only the
frequency converter is protected
Unit overtemperature
protection
Yes
Motor overload
protection
Yes
Motor stall protection
Motor underload
protection
Yes
Yes
Short-circuit protection of Yes
+24V and +10V
reference voltages
Overcurrent protection
Table 4- 4. Technical data
Trip limit 4,0*IH instantaneously
4
Download from Www.Somanuals.com. All Manuals Search And Download.
5
22(96)
Installation
HHoonneeyywweellll
HHoonneeyywweellll
5.
INSTALLATION
5.1 Mounting
5.1.1 NXL Compact (MF2 and MF3)
There are two possible positions in the wall mounting for the frames MF2 and MF3 (see Figure 5-1)
The NXL type MF2 is mounted with two screws using the middle holes of the mounting plates. If an
RFI filter is used, the upper mounting plate shall be attached with two screws (see Figure 5-2). MF3
and bigger types are always mounted with four screws.
Figure 5-1. The two possible mounting positions of NXL (MF2 and MF3)
X
X
X
X
X
MF2 with a filter
MF2 without a filter
Figure 5-2. Mounting of NXL, MF2
Download from Www.Somanuals.com. All Manuals Search And Download.
5
Installation
23(96)
Ø
W1
W2
D1
H8
H7
H5
H3
H2
H4
H1
H6
nxlk7.fh8
D2
Figure 5-3. NXL Compact dimensions, MF2
Dimensions (mm)
Type
W1
30
W2
60
H1
H2
H3
H4
H5
80
H6
42
H7
11
H8
D1
150
D2
∅
MF2
172
152
140
130
6
144
6
Table 5-1. Dimensions of NXL, MF2
Download from Www.Somanuals.com. All Manuals Search And Download.
5
24(96)
Installation
HHoonneeyywweellll
HHoonneeyywweellll
D1
W1
W2
W3
H7
H6
H5
H1
H2
H4
H3
Ø
nxlk8.fh8
D2
Figure 5-4. NXL Compact dimensions, MF3
Dimensions (mm)
Type
W1
84
W2
35
W3
23
H1
H2
H3
H4
H5
193
H6
184
H7
220
D1
172
D2
∅
MF3
262
235
223
199
166
6
Table 5-2. Dimensions of NXL, MF3
Download from Www.Somanuals.com. All Manuals Search And Download.
5
Installation
25(96)
5.1.2 NXL HVAC (MF4 – MF6)
The frequency converter shall be fixed with four screws (or bolts, depending on the unit size).
Enough space shall be reserved around the frequency converter in order to ensure a sufficient
cooling, see Table 5-4 and Figure 5-6.
Also see to that the mounting plane is relatively even.
Ø
W2
D1
H1 H2
H3
W1
E1Ø
E2Ø*
fr5ip21.fh8
Ø
Figure 5-5. NXL HVAC dimensions
Type
Dimensions
W1
128
144
195
W2
100
100
148
H1
H2
H3
D1
∅
7
E1∅
3 x 28,3
2 x 37
3 x 37
E2∅*
327
419
558
313
406
541
292
391
519
190
214
237
MF4 (HVAC03-12)
MF5 (HVAC16-31)
MF6 (HVAC38-61)
7
9
1 x 28,3
Table 5-3. Dimensions of NXL HVAC, MF4—MF6
* = MF5 only
Download from Www.Somanuals.com. All Manuals Search And Download.
5
26(96)
Installation
HHoonneeyywweellll
HHoonneeyywweellll
5.2 Cooling
Forced air flow cooling is used for NXL HVAC and NXL Compact size MF3.
Enough free space shall be left above and below the frequency converter to ensure sufficient air
circulation and cooling. You will find the required dimensions for free space in the table below.
Type
Dimensions [mm]
A
B
C
D
C
NXL 0002-0006 2
NXL 0001-0005 5
HVAC 03-12
HVAC 16-31
HVAC 38-61
10
10
20
20
30
10
10
20
20
20
100
100
100
120
160
50
50
50
60
80
Table 5-4. Mounting space dimensions
A
B
= clearance around the freq. converter (see also B)
= distance from one frequency converter to another or
distance to cabinet wall
= free space above the frequency converter
= free space underneath the frequency converter
B
B
A
A
C
D
D
NK5_2
Figure 5-6. Installation space
Type
Cooling air required [m3/h)
HVAC 03—12
HVAC 16—31
HVAC 38—61
70
190
425
Table 5-5. Required cooling air
Download from Www.Somanuals.com. All Manuals Search And Download.
5
Installation
27(96)
5.3 Changing EMC protection class from H/C to T in NXL HVAC
The EMC protection class of NXL HVAC frequency converter types can be changed from class H/C
to class T with a simple procedure presented in the figures below.
Remove this screw
Remove this screw
Figure 5-7. Changing of EMC protection class, MF4 (left) and MF5 (right)
Remove these
screws
Figure 5-8. Changing of EMC protection class, MF6
Note! Do not attempt to change the EMC-level back to class H or C. Even if the procedure above is
reversed, the frequency converter will no longer fulfil the EMC requirements of class H or C!
Download from Www.Somanuals.com. All Manuals Search And Download.
28(96)
Cabling and connections
HHoonneeyywweellll
HHoonneeyywweellll
6.
CABLING AND CONNECTIONS
6.1 Power connections
U/T1 V/T2 W/T3
U/T1 V/T2 W/T3
L1 L2
L1 L2 L3
1~
3~
nxlk10.fh8
Figure 6-1. Power connections, MF2
3~
1~
U/T1 V/T2 W/T3 BR+ BR-
L1 L2 L3
nxlk11.fh8
Figure 6-2. Power connections, NXL Compact MF3 (1~/3~)
U/T1 V/T2 W/T3
B- B+ R-
L1 L2 L3
nxlk58.fh8
Figure 6-3. Power connections, NXL HVAC (MF4-MF6)
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Honeywell
HHoonneeyywweellll
Cabling and connections
29(96)
6.1.1 Cabling
Use cables with heat resistance of at least +70°C. The cables and the fuses must be dimensioned
according to the tables below. Installation of cables according to UL regulations is presented in Chapter
6.1.4.
The fuses function also as cable overload protection.
These instructions apply only to cases with one motor and one cable connection from the frequency
converter to the motor. In any other case, ask the factory for more information.
1st environment
(restricted
2nd environment
distribution)
Level H/C
Cable type
Mains cable
Motor cable
Control cable
Level L
Level T Level N
1
3*
4
1
2
4
1
1
4
1
1
4
Table 6-1. Cable types required to meet standards.
Level C
Level H
=
EN 61800-3 (2004), category C1
EN 61000-6-3
= EN 61800-3 (2004), category C2
EN 61000-6-4
Level L
Level T:
Level N:
= EN61800-3 (2004), 2nd environment (industrial)
See page 9.
See page 9.
1
2
3
= Power cable intended for fixed installation and the
specific mains voltage. Shielded cable not required.
(NKCABLES/MCMK or similar recommended)
= Power cable equipped with concentric protection wire
and intended for the specific mains voltage.
(NKCABLES /MCMK or similar recommended).
= Power cable equipped with compact low-impedance
shield and intended for the specific mains voltage.
(NKCABLES /MCCMK, SAB/ÖZCUY-J or similar recommended).
*360º earthing of both motor and FC connection required to meet the standard
= Screened cable equipped with compact low-impedance
4
shield (NKCABLES /jamak, SAB/ÖZCuY-O or similar).
In NXL HVAC (MF4 – MF6): A cable entry flange should be used when installing the motor cable at both
ends in order to reach the EMC levels.
Note: The EMC requirements are fulfilled at factory defaults of switching frequencies (all frames).
6
Download from Www.Somanuals.com. All Manuals Search And Download.
30(96)
Cabling and connections
HHoonneeyywweellll
HHoonneeyywweellll
6.1.1.1
Cable and fuse sizes
Frame
Type
IL
[A]
Fuse
[A]
Mains
cable
Terminal cable size (min/max)
Main terminal
[mm2]
Earth
terminal
[mm2]
Control
terminal
[mm2]
Relay
terminal
[mm2]
Cu [mm2]
MF2
MF3
NXL0002
NXL0003—0006
2
3-6
10
16
2*1.5+1.5
2*2.5+2.5
0.5—2.5
0.5—2.5
0.5—2.5
0.5—2.5
0.5—1.5
0.5—1.5
0.5—2.5
0.5—2.5
Table 6-2. Cable and fuse sizes for NXL Compact, 208 - 240V
Frame
Type
IL
[A]
Fuse
[A]
Mains
cable
Terminal cable size (min/max)
Main terminal
[mm2]
Earth
terminal
[mm2]
Control
terminal
[mm2]
Relay
terminal
[mm2]
Cu [mm2]
MF2
MF3
MF4
MF4
MF5
MF5
MF5
MF6
NXL0001—0002
NXL0003—0005
HVAC03—09
HVAC12
HVAC16
HVAC23
1-2
1-5
7—9
12
16
22
31
38-
45
10
10
10
16
20
25
35
50
3*1.5+1.5
3*1.5+1.5
3*1.5+1.5
3*2.5+2.5
3*4+4
3*6+6
3*10+10
3*10+10
0.5—2.5
0.5—2.5
1—4
1—4
1—10
1—10
1—10
2.5—50 Cu
6—50 Al
2.5—50 Cu
6—50 Al
0.5—2.5
0.5—2.5
1—2.5
1—2.5
1—10
1—10
1—10
6—35
0.5—1.5
0.5—1.5
0.5—1.5
0.5—1.5
0.5—1.5
0.5—1.5
0.5—1.5
0.5—1.5
0.5—2.5
0.5—2.5
0.5—2.5
0.5—2.5
0.5—2.5
0.5—2.5
0.5—2.5
0.5—2.5
HVAC31
HVAC38—45
MF6
HVAC61
61
63
3*16+16
6—35
0.5—1.5
0.5—2.5
Table 6-3. Cable and fuse sizes for NXL, 380 – 500V
Note! This cable recommendation is based on standard EN 60204-1 and PVC isolated cable where there
is either one cable on a shelf in temperature of + 40°C or four cables on a shelf in temperature of + 30°C.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Cabling and connections
31(96)
6.1.2 Mounting of cable accessories
Enclosed to your NXL frequency converter you have received a plastic bag containing components that are
needed for the installation of the mains and motor cables in the frequency converter.
2
3
4
1
6
5
8
7
Figure 6-4. Cable accessories
Components:
1
2
3
4
5
6
7
8
Grounding terminals (MF4, MF5) (2)
Cable clamps (3)
Rubber grommets (sizes vary from class to class) (3)
Cable entry gland (1)
Screws, M4x10 (5)
Screws, M4x16 (3)
Grounding cable clamps (MF6) (2)
Grounding screws M5x16 (MF6) (4)
NOTE: The cable accessories installation kit for frequency converters of protection class IP54 includes all
components except 4 and 5.
Mounting procedure
1. Make sure that the plastic bag you have received contains all necessary components.
2. Open the cover of the frequency converter (Figure 1).
3. Remove the cable cover. Observe the places for
a) the grounding terminals (MF4/MF5) (Figure 2).
b) the grounding cable clamps (MF6) (Figure 3).
4. Re-install the cable cover. Mount the cable clamps with the three M4x16 screws as shown in Figure 4.
Note that the location of the grounding bar in FR6/MF6 is different from what is shown in the picture.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
32(96)
Cabling and connections
HHoonneeyywweellll
HHoonneeyywweellll
5. Place the rubber grommets in the openings as shown in Figure 5.
6. Fix the cable entry gland to the frame of the frequency converter with the five M4x10 screws (Figure 6).
Close the cover of the frequency converter.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Cabling and connections
33(96)
6.1.3 Installation instructions
Before starting the installation, check that none of the components of the
frequency converter is live.
1
2
The NXL frequency converter types MF2 and MF3 shall be installed inside
switchgear, separate cubicle or electrical room because of the protection class
IP20 and the fact that the cable terminals are not protected.
Place the motor cables sufficiently far from other cables:
3
ꢁ
Avoid placing the motor cables in long parallel lines with other cables
If the motor cables run in parallel with other cables, note the minimum
distances between the motor cables and other cables given in table
below.
ꢁ
ꢁ
ꢁ
ꢁ
The given distances also apply between the motor cables and signal
cables of other systems.
The maximum length of the motor cables is 30 m (MF2-MF3), 50 m
(MF4) and 300 m (MF5 – MF6)
.
The motor cables should cross other cables at an angle of 90 degrees.
Distance
Shielded
cable
[m]
between cables
[m]
0.3
1.0
20
50
≤
≤
If cable insulation checks are needed, see Chapter 6.1.5.
4
5
Connect the cables:
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
Strip the motor and mains cables as advised in Table 6-4 and Figure
6-5.
Connect the mains, motor and control cables into their respective
terminals (see e.g.).
For Information on cable installation according to UL regulations see
Chapter 6.1.4.
Make sure that the control cable wires do not come in contact with the
electronic components of the unit.
If an external brake resistor (option) is used, connect its cable to the
appropriate terminal.
Check the connection of the earth cable to the motor and the frequency
converter terminals marked with
.
ꢁ
ꢁ
Connect the separate shield of the motor cable to the earth plate of the
frequency converter, motor and the supply centre.
Ensure that the control cables or the cables of the unit are not trapped
between the frame and the protection plate.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
34(96)
Cabling and connections
HHoonneeyywweellll
HHoonneeyywweellll
6.1.3.1
Stripping lengths of motor and mains cables
Earth
conductor
Earth
conductor
C1
D1
A2
B2
C2
D2
A1
B1
MAINS
MOTOR
nk6141.fh8
Figure 6-5.Stripping of cables
Frame
MF2
MF3
MF4
MF5
MF6
A1
7
7
15
20
20
B1
35
40
35
40
90
C1
7
7
10
10
15
D1
20
30
20
30
60
A2
7
7
7
20
20
B2
50
60
50
60
90
C2
7
7
7
10
15
D2
35
40
35
40
60
Table 6-4. Cables stripping lengths [mm]
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Cabling and connections
35(96)
6.1.3.2
Installation of cables to NXL
Note: In case you want to connect an external brake resistor (MF3 and bigger sizes), see separate Brake
Resistor Manual.
Figure 6-6. NXL Compact, MF2
Control
cable
Earth terminal
Motor
cable
Mains
cable
Figure 6-7. Cable installation in NXL Compact, MF2 (500V, 3-phase)
6
Download from Www.Somanuals.com. All Manuals Search And Download.
36(96)
Cabling and connections
HHoonneeyywweellll
HHoonneeyywweellll
Figure 6-8. NXL Compact, MF3
Control
cable
Earth terminal
Brake resistor
terminals
BR-
BR+
Motor
cable
Mains
cable
Figure 6-9. Cable installation in NXL Compact, MF3
NOTE! NXL Compact (MF2-3): It is advisable to connect the cables to the
terminals and earthing plate first and then attach the terminals and earthing
plate to the unit.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Cabling and connections
37(96)
Installation of an external RFI filter to NXL Compact (MF2-3)
The EMC protection class of NXL Compact frequency converters MF2 and MF3 can be changed from N to
H with an optional external RFI filter. Install the power cables in terminals L1, L2 and L3 and the grounding
cable in terminal PE of the filter. See the figures below. See also mounting instructions of MF2 in Figure
5-2.
MF2
MF3
BR-
BR+
W/T3
V/T2
W/T3
V/T2
U/T1
U/T1
L3
L2
L1
L3
L2
L1
Earthing
cable
RFI filter
cable
Ground
L1 L2 L3
PE
RFI filter
Earthing
cable
Mains cable
nxlk1.fh8
Figure 6-10. MF2 with the RFI-filter
Figure 6-11. RFI installation for MF2 and MF3, 380…500V, 3
phase supply. Filter type NXLRFIV35
MF3
MF2
BR-
BR+
W/T3
V/T2
W/T3
V/T2
U/T1
U/T1
L3
L2
L1
L2
L1
Earthing
cable
RFI filter
cable
Ground
PE N
L
RFI filter
Earthing
cable
Mains cable
rfi2.fh8
Figure 6-12. RFI cable installation for MF2 and MF3, 208…240V, 1 phase supply. Filter
type NXLRFIV12
6
Download from Www.Somanuals.com. All Manuals Search And Download.
38(96)
Cabling and connections
Input voltage
HHoonneeyywweellll
HHoonneeyywweellll
Dimensions
WxHxD (mm)
RFI Filter type
NXLRFIV35
NXLRFIV12
380-500V 3~
208-240V 1~
Table 6-5. RFI filter types and their dimensions
60x252x35
60x252x35
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Cabling and connections
39(96)
Figure 6-13. NXL HVAC (03-12), MF4
Brake resistor
terminals
Earth terminals
Mains cable
Motor cable
Figure 6-14. Cable installation in NXL HVAC (03-12), MF4
6
Download from Www.Somanuals.com. All Manuals Search And Download.
40(96)
Cabling and connections
HHoonneeyywweellll
HHoonneeyywweellll
Figure 6-15. NXL HVAC (16-31), MF5
DC
terminals
Brake resistor
terminals
Earth terminals
Mains cable
Motor cable
Figure 6-16. Cable installation in NXL HVAC (16-31), MF5
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Cabling and connections
41(96)
Figure 6-17. NXL HVAC (38-61), MF6
Brake resistor
terminals
DC
terminals
Earth terminals
Motor cable
Mains cable
Figure 6-18. Cable installation in NXL HVAC (38-61), MF6
6
Download from Www.Somanuals.com. All Manuals Search And Download.
42(96)
Cabling and connections
HHoonneeyywweellll
HHoonneeyywweellll
6.1.4 Cable installation and the UL standards
To meet the UL (Underwriters Laboratories) regulations, a UL-approved copper cable with a minimum
heat-resistance of +60/75°C must be used.
The tightening torques of the terminals are given in Table 6-6.
Frame
Tightening torque
[Nm]
Tightening torque
in-lbs.
4—5
4—5
4—5
10—13
35
MF2
MF3
MF4
MF5
MF6
0.5—0.6
0.5—0.6
0.5—0.6
1.2—1.5
4
Table 6-6. Tightening torques of terminals
6.1.5 Cable and motor insulation checks
1. Motor cable insulation checks
Disconnect the motor cable from terminals U, V and W of the frequency converter and from the motor.
Measure the insulation resistance of the motor cable between each phase conductor as well as
between each phase conductor and the protective ground conductor.
The insulation resistance must be >1MΩ.
2. Mains cable insulation checks
Disconnect the mains cable from terminals L1, L2 and L3 of the frequency converter and from the
mains. Measure the insulation resistance of the mains cable between each phase conductor as well as
between each phase conductor and the protective ground conductor.
The insulation resistance must be >1MΩ.
3. Motor insulation checks
Disconnect the motor cable from the motor and open the bridging connections in the motor connection
box. Measure the insulation resistance of each motor winding. The measurement voltage must equal at
least the motor nominal voltage but not exceed 1000 V. The insulation resistance must be >1MΩ.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Cabling and connections
43(96)
6.2 Control unit
6.2.1 NXL Compact (MF2 – MF3)
The control unit of the NXL frequency converter is integrated with the power unit and consists roughly of
the control board and one optional board, which can be connected to the slot connector of the control
board.
6.2.2 NXL HVAC (MF4 – MF6)
In NXL HVAC frames MF4-MF6 there are two option board connectors SLOT D and SLOT E (see Figure
6-19).
Slot E: I/Oboards, fieldbus boards and expanders
Slot D: Fieldbus boards
E
D
Figure 6-19. Option board slots D and E in frames MF4 – MF6
6.2.2.1
Allowed option boards in NXL HVAC:
See below for the allowed option boards in the two slots on NXL HVAC frequency converters:
SLOT D
SLOT E
C2
AA
C3 C4 C6 C7 C8 CI CJ
AI
B1 B2 B4 B5 B9 C2 C3 C4 C6 C7
C8 CI
CJ
In NXL HVAC series the option board NXLOPTAI is included in all deliveries as standard. The free slot
D is meant for additional fieldbus boards.
When two option boards are used, the one in slot E has to be NXLOPTAI or NXLOPTAA. It is not allowed
to use two NXOPTB_ or NXOPTC_ boards. Also combinations of NXOPTB_ and NXOPTC_ –boards are
prohibited.
See descriptions for NXLOPTAA and NXLOPTAI option boards in chapters 10 and 11.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
44(96)
Cabling and connections
HHoonneeyywweellll
HHoonneeyywweellll
6.2.3 Control connections
The basic control connections are shown below.
The signal descriptions of the HVAC and Multicontrol Applications are presented in Chapter 6.2.4 and in
Chapter 2 of the HVAC and Multicontrol Application Manuals.
9 10 11 18 19 A B 30
21 22 23
1 2 3 4 5 6 7 8
nxlk13.fh8
Figure 6-20. Control connections NXL Compact, MF2 – MF3
9 10 11 18 19 A B
30
1 2 3 4 5 6 7 8
21 22 23
nxlk49.fh8
Figure 6-21. Control connections NXL HVAC, MF4 – MF6
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Cabling and connections
45(96)
6.2.4 Control I/O
Reference
Potentiometer 1-10
kΩ
Terminal
Signal
Reference output
Analogue input, voltage range
0—10V DC.
Description
Voltage for potentiometer, etc.
Voltage input frequency reference
1
2
+10Vref
AI1+
3
4
5
AI1-
AI2+
AI2-
I/O Ground
Ground for reference and controls
Analogue input, current range Current input frequency reference
0—20mA
/GND
6
7
+24V
Control voltage output
I/O ground
Voltage for switches, etc. max 0.1 A
Ground for reference and controls
GND
8
9
DIN1
DIN2
Start forward (programmable)
Start reverse (programmable)
Contact closed = start forward
Contact closed = start reverse
10
11
DIN3
GND
Preset speed selection 1
(programmable)
I/O ground
Contact closed = Preset speed 1
Ground for reference and controls
Programmable
18
19
A
B
30
AO1+
AO1-
RS 485
RS 485
+24V
Output frequency
Analogue output
Serial bus
Serial bus
24V aux. input voltage
mA
Range 0—20 mA/RL, max. 500
Differential receiver/transmitter
Differential receiver/transmitter
Control power supply backup
Ω
21
22
23
RO1
RO1
RO1
Relay output 1 Programmable
FAULT
Table 6-7. Default I/O configuration.
Terminal
+24V
Signal
Description
Control voltage output; voltage for
switches etc.
Ground for reference and controls
Contact closed = Preset speed 2
12
13
+24 V DC
I/O ground
GND
14 Exp DIN1 Preset speed selection 2
(programmable)
15 Exp DIN2 Fault Reset
(programmable)
16 Exp DIN3 Disable PID (PID control
selection)
Contact closed = Fault reset
Contact closed = Disable PID
(Programmable)
25 Exp RO1
26 Exp RO1
Expander Relay output 1 (NO)
RUN
Programmable
28
29
TI+
TI-
Motor Thermistor input
Active = Fault, stop according to defined
method
Table 6-8. Additional inputs in NXL HVAC (available as option for NXL Compact)
Terminal
+10Vref
Signal
Reference output
Analogue input, voltage range
0—10V DC
Description
1
2
Voltage for potentiometer, etc.
Voltage input frequency reference (MF2-3)
Voltage/current input frequency reference
(MF4-MF6)
AI1+
or
DIN 4
Can be programmed as DIN4
Ground for reference and controls
Analogue input, voltage range Voltage or current input frequency
0—10V DC or current range reference
0—20mA
3
4
5
AI1-
AI2+
AI2-
I/O Ground
/GND
6
7
+ 24 V
GND
Control voltage output
I/O ground
Ground for reference and controls
Table 6-9. AI1 configuration, when programmed as DIN4
6
Download from Www.Somanuals.com. All Manuals Search And Download.
46(96)
Cabling and connections
HHoonneeyywweellll
HHoonneeyywweellll
6.2.5 Control terminal signals
Terminal
+10 Vref
Signal
Reference voltage
Technical information
Maximum current 10 mA
MF2-MF3: Voltage input
1
2
AI1+
Analogue input,
voltage
(MF4 and bigger: voltage or current)
MF4-MF6 Selection V or mA with jumper block X8 (see
page 39):
Default: 0– +10V (Ri = 200 k
0– 20mA (Ri = 250
Ω)
Ω
)
3
4
AI1–
AI2+
Analogue input common
Differential input if not connected to ground;
Allows 20V differential mode voltage to GND
Selection V or mA with jumper block X4(MF2-MF3) and
X13 (MF4-MF6)
Analogue input, voltage or
current
Default: 0– 20mA (Ri = 250
0– +10V (Ri = 200 k
Differential input;
Ω)
Ω
)
5
AI2–
Analogue input common
Allows 20V differential mode voltage to GND
10%, maximum current 100 mA
6
7
24 Vout
GND
24V auxiliary output voltage
I/O ground
Ground for reference and controls
8
DIN1
Digital input 1
Ri = min. 5k
Ω
9
DIN2
Digital input 2
10
11
18
19
DIN3
Digital input 3
GND
I/O ground
Ground for reference and controls
Output signal range:
AO1+
AO1–/GND
Analogue signal (+output)
Analogue output common
Current 0(4)–20mA, RL max 500
Ω
or
A
B
RS 485
RS 485
+24V
Serial bus
Differential receiver/transmitter, bus impedance 120
Differential receiver/transmitter, bus impedance 120
Control power supply backup
Ω
Ω
Serial bus
30
24V auxiliary input voltage
21
22
23
RO1/1
RO1/2
RO1/3
Relay output 1 Switching capacity:
24VDC/8A
250VAC/8A
125VDC/0,4A
Relay output terminals are galvanically isolated from the
I/O ground
Table 6-9. Control I/O terminal signals
NOTE! NXL HVAC additional inputs terminal signals defined in section 11 NXLOPTAI
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Cabling and connections
47(96)
6.2.5.1
Jumper selections on NXL basic board
The user is able to customise the functions of the frequency converter to better suit his needs by selecting
certain positions for the jumpers on the NXL board. The positions of the jumpers determine the signal type
of analogue input (terminal #2) and whether the termination resistor RS485 is used or not.
The following figures present the jumper selections of NXL frequency converters:
Jumper block X4 in MF3:
Jumper block X4 in MF2:
Analogue input
programming
Termination resistor
programming
0...20mA; Current input
0...20mA; Current input
Termination resistor RS 485 is not used
Analogue input
programming
Voltage input; 0...10V
Termination resistor
programming
Jumper block X7 in MF3:
Voltage input; 0...10V
Termination resistor RS 485 is in use
Termination resistor RS 485 is in use
= Factory default
Termination resistor RS 485 is not used
nxlk15.fh8
Figure 6-22. Jumper selection for NXL, MF2 and MF3
6
Download from Www.Somanuals.com. All Manuals Search And Download.
48(96)
Cabling and connections
HHoonneeyywweellll
HHoonneeyywweellll
Jumper block X8:
AI1 mode
Jumper block X13:
AI2 mode
0...20mA; Current input
0...20mA; Current input
Voltage input; 0...10V
Voltage input; 0...10V
(differential)
Voltage input; 0...10V
Jumper block X9:
Termination resistor RS 485 is in use
Termination resistor RS 485 is not used
= Factory default
nxlk54.fh8
Figure 6-23. Jumper selection for NXL HVAC, MF4 – MF6
Check the correct positions of the jumpers. Running the motor
with signal settings different from the jumper positions will not
harm the frequency converter but may damage the motor.
!!
!!
WARNING
If you change the AI signal content also remember to change
the corresponding parameters (S6.9.1, 6.9.2) in System Menu.
!!
!!
NOTE
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Cabling and connections
49(96)
Jumper block X4
Jumper block X4
Jumper block X7
Figure 6-24. The location of jumper blocks in MF2 (left) and MF3 (right)
X8
X13
X9
Figure 6-25. The location of jumper blocks in the control board of NXL HVAC
6
Download from Www.Somanuals.com. All Manuals Search And Download.
50(96)
Cabling and connections
HHoonneeyywweellll
HHoonneeyywweellll
6.2.6 Motor thermistor (PTC) connection
There are three possibilities to connect a PTC resistor to NXL:
1. With optional board NXLOPTAI. (Recommended method. Board included in NXL HVAC as standard)
NXL equipped with NXLOPTAI fulfils IEC 664 if the motor thermistor
is insulated (= effective double insulation).
2. With optional board NXOPTB2.
NXL equipped with NXOPTB2 fulfils IEC 664 if the motor thermistor
is insulated (= effective double insulation).
3. With the digital input (DIN3) of NXL.
The DIN3 is galvanically connected to other I/O's of NXL.
This is why reinforced or double insulation of the thermistor (IEC 664) is absolutely required outside
the frequency converter (in the motor or between the motor and the frequency converter).
Figure 6-26. Motor thermistor (PTC) connection
+24 V (terminal 6)
External resistor
4.7 kΩ...5.6 kΩ
DIN3 (terminal 10, par.2.1.18 = 14)
External PTC Resistor
nxlk60.fh8
GND (terminal 11)
Note!
The NXL trips when PTC impedance exceeds 4,7 kΩ
It is strongly recommended to use NXLOPTAI or NXOPTB2 board for motor thermistor connection.
If the motor thermistor is connected to DIN3, the instructions above must be followed; otherwise a
serious safety hazard may result from the connection.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Control Keypad
51(96)
7.
CONTROL KEYPAD
The control keypad is the link between the NXL frequency converter and the user. The NXL control
keypad features a seven-segment display with seven indicators for the Run status (RUN,
READY, STOP, ALARM, FAULT) and three indicators for the control place (I/O term, Keypad, ,
Bus/Comm).
,
The control information, i.e. the number of menu, the displayed value and the numeric information
are presented with numeric symbols.
The frequency converter is operable through the seven push-buttons of the control keypad.
Furthermore, the keypad serves the purposes of parameter setting and value monitoring.
The keypad is detachable and isolated from the input line potential.
7.1 Indications on the Keypad display
Figure 7-1. NXL control keypad and drive status indications
7.1.1 Drive status indications
The drive status indications tell the user what the status of the motor and the drive is.
1
RUN
= Motor is running; Blinks when the stop command has been given but the
frequency is still ramping down.
2
= Indicate the direction of motor rotation.
,
STOP = Indicates that the drive is not running.
3
4
READY = Lights when AC power is on. In case of a fault, the symbol will not light up.
ALARM = Indicates that the drive is running outside a certain limit and a warning is given.
5
6
FAULT = Indicates that unsafe operating conditions were encountered due to which the
drive was stopped.
Download from Www.Somanuals.com. All Manuals Search And Download.
7
52(96)
Control Keypad
HHoonneeyywweellll
HHoonneeyywweellll
7.1.2 Control place indications
The symbols I/O term, Keypad and Bus/Comm (see chapter 7.4.3.1) indicate the choice of control
place made in the Keypad control menu (see chapter 7.4.3).
I/O term
= I/O terminals are the selected control place; i.e. START/STOP
commands or reference values are given through the I/O terminals.
a
b
c
Keypad
= Control keypad is the selected control place; i.e. the motor can be
started or stopped and its reference values altered from the keypad.
Bus/Comm
= The frequency converter is controlled through a fieldbus.
7.1.3 Numeric indications
The numeric indications provide the user with information on his present location in the keypad menu
structure as well as with information related to the operation of the drive.
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Control Keypad
53(96)
7.2 Keypad push-buttons
The NXL seven-segment control keypad features 7 push-buttons that are used for the control of the
frequency converter (and motor) and parameter setting.
Figure 7-2. Keypad push-buttons
7.2.1 Button descriptions
ENTER
reset
=
=
There are two operations integrated in this button. The button operates
mainly as reset button except in the parameter edit mode. The button
operation is shortly described below.
ENTER
reset
The Enter button serves for:
1) confirmation of selections
2) fault history reset (2…3 seconds)
=
=
This button is used to reset active faults.
Note! The motor may start immediately after resetting the faults.
Browser button up
Browse the main menu and the pages of different submenus.
Edit values.
+
–
=
=
Browser button down
Browse the main menu and the pages of different submenus.
Edit values.
Menu button left
Move backward in menu.
Move cursor left (in parameter edit mode).
Exit edit mode.
Hold down for 5 seconds for quick change of control place;
manual (keypad) ꢂ remote (fielbuds or I/O).
3
4
=
Menu button right
Move forward in menu.
Move cursor right (in parameter edit mode).
Enter edit mode.
Download from Www.Somanuals.com. All Manuals Search And Download.
7
54(96)
Control Keypad
HHoonneeyywweellll
HHoonneeyywweellll
=
=
Start button.
start
Pressing this button starts the motor if the keypad is the active control
place. See Chapter 7.4.3.1.
Stop button.
stop
Pressing this button stops the motor (unless disabled by parameter P3.4).
Stop button serves also for activating the Start-up Wizard (see below)
7.3 Start-up wizard
NXL has a built-in start-up wizard, which speeds up the programming of the drive. The wizard helps
you choose between four different operating modes, Standard, Fan, Pump and High Performance.
Each mode has automatic parameter settings optimised for the mode in question. The programming
wizard is started by pressing the Stop button for 5 seconds, when the drive is in stop mode. See the
figure below for the procedure:
=Push the button
START-UP WIZARD
rpm
START
I (A)
n
MODE
DONE
n
Honeywell
Honeywell
Honeywell
Honeywell
Honeywell
+
A
rpm
+
+
+
-
+
+
-
ENTER
-
reset
ENTER
ENTER
-
ENTER
reset
ENTER
-
-
reset
reset
reset
Accept
Push 5 seconds
to activate (in
stop mode)
Select the
mode. See
table below!
Accept
Tune
n(rpm)
Accept
Tune
I(A)
3
2
5
6
1
4
7
NOTE! Startup Wizard resets all
other parameters to factory
defaults!
M
0
50
3
s
3
s
IH*1,5 400 50
0=
0=
0=
Not
0=
Ai1 Not
0=
I/O
I/O
Hz Hz
Hz Ramp Coasting
*
V
Standard
used 0-10V used
0=
Not
used 0-10V used
0=
Not
20 50 20 20 IL*1,1 400 50
0= 0=
0=
Ai1 Not
0=
Hz Hz
s
s
Hz Ramp Coasting
**
*
V
Fan
20 50
Hz Hz
5
s
5
s
IL*1,1 400 50
0=
1=
0=
Ai1 Not
0=
I/O
I/O
Hz Ramp Ramp
*
V
Pump
**
0=
used 0-10V used
** In NXL HVAC the default start function for Fan or Pump
mode is 2 = Conditional Flying Start which is
recommended start function with Trip Free Output
Switching function enabled as standard.
0
50
1
s
1
s
IH*1,8 400 50
0=
1=
automatic
torque
0=
Ai1 Not
0-10V used
0=
Hz Hz
performance
Hz Ramp Coasting
*
V
High
*In drives of 208V...230V
this value is 230V
boost
Figure 7-3. NXL Start-up wizard
Note! See the Application manuals for detailed parameter descriptions.
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Control Keypad
55(96)
7.4 Navigation on the control keypad
The data on the control keypad are arranged in menus and submenus. The menus are used for
example for the display and editing of measurement and control signals, parameter settings (chapter
7.4.2), reference values (Chapter 7.4.3) and fault displays (chapter 7.4.4).
Location
The first menu level consists of menus M1 to E7 and is called the Main menu. The user can
navigate in the main menu using the Browser buttons up and down. The desired submenu can be
entered from the main menu using the Menu buttons. When there still are pages to enter under the
currently displayed menu or page, the last digit of the figure on the display is blinking and by
pressing the Menu button right, you can reach the next menu level.
The control keypad navigation chart is shown on page 46. Please note that the menu M1 is located
in the lower left corner. From there you will be able to navigate your way up to the desired menu
using the menu and browser buttons.
More detailed descriptions of the menus you will find later in this Chapter.
Download from Www.Somanuals.com. All Manuals Search And Download.
7
56(96)
Control Keypad
HHoonneeyywweellll
HHoonneeyywweellll
READY
READY
STOP
I/O term
STOP
I/O term
READY
READY
READY
STOP
I/O term
STOP
I/O term
STOP
I/O term
READY
READY
READY
STOP
STOP
STOP
I/O term
STOP
STOP
STOP
STOP
STOP
I/O term
STOP
term
I/O
READY
READY
I/O
term
READY
term
STOP
I/O
I/O term
Browse
reset
Press to reset
enter
READY
READY
READY
term
I/O term
I/O term
STOP
I/O
Change
value
enter
Browse
READY
READY
READY
term
Change
value
STOP
I/O term
I/O term
STOP
I/O
enter
Browse
READY
READY
READY
STOP
I/O term
I/O term
STOP
I/O term
No editing!
Hz
Figure 7-4. Keypad navigation chart
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Control Keypad
57(96)
Menu functions
Code
Menu
Min
Max
V1.24
Selections
See chapter 7.4.1 for the
monitoring values
Monitoring menu
V1.1
M1
NXL HVAC
P2.1 = HVAC parameters
P2.1.15 = Basic parameters
NXL Compact
P2.1 = Basic parameters
P2.2 = Input signals
P2.3 = Output signals
P2.4 = Drive control
Parameter menu
P2.1
P2.10
P2
P2.5 = Prohibit frequencies
P2.6 = Motor control
P2.7 = Protections
P2.8 = Autorestart
P2.9 = PID control
P2.10=Pump and fan control
See the application manuals
for detailed parameter lists
P3.1 = Selection of control
place
R3.2 = Keypad reference
P3.3 = Keypad direction
P3.4 = Stop button activation
P3.5 = PID reference 1
P3.6 = PID reference 2
Shows the active faults and
their types
Keypad control menu
P3.1
P3.6
K3
Active faults menu
Fault history menu
F4
H5
Shows the fault history list
S6.3 = Copy parameters
S6.5 = Security
S6.6 = Keypad settings
S6.7 = Hardware settings
System menu
S6.3
E7.1
S6.10 S6.8 = System info
S6.9 = AI mode
S6
S6.10 = Fieldbus parameters
Parameters are described in
chapter 7.4.7
E7.1 = Slot D
E7.2 = Slot E
Expander board menu
E7.2
E7
Table 7-1. Main menu functions
Download from Www.Somanuals.com. All Manuals Search And Download.
7
58(96)
Control Keypad
HHoonneeyywweellll
HHoonneeyywweellll
7.4.1 Monitoring menu (M1)
You can enter the Monitoring menu from the Main menu by pushing the Menu button right when the
location indication M1 is visible on the display. How to browse through the monitored values is
presented in Figure 7-5.
The monitored signals carry the indication V#.# and they are listed in Table 7-2. The values are
updated once every 0.3 seconds.
This menu is meant only for value checking. The values cannot be altered here. For changing values
of parameters see Chapter 7.4.2.
Figure 7-5. Monitoring menu
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Control Keypad
59(96)
Code
Signal name
Unit
ID
Description
Output frequency
Frequency reference
Motor speed
Hz
Hz
rpm
A
1
Frequency to the motor
V1.1
V1.2
V1.3
V1.4
V1.5
V1.6
V1.7
V1.8
V1.9
V1.10
V1.11
V1.12
25
2
Calculated motor speed
Measured motor current
Motor current
3
Motor torque
%
4
Calculated actual torque/nominal torque of the motor
Calculated actual power/nominal power of the motor
Calculated motor voltage
Motor power
%
5
Motor voltage
V
6
DC-link voltage
Unit temperature
Analogue input 1
Analogue input 2
V
7
Measured DC-link voltage
ºC
8
Heat sink temperature
13 AI1
14 AI2
Analogue output
current
mA
mA
26 AO1
Analogue output
current 1, expander
board
V1.13
V1.14
31
Analogue output
current 2, expander
board
mA
32
DIN1, DIN2, DIN3
DIE1, DIE2, DIE3
RO1
Digital input statuses
V1.15
V1.16
V1.17
V1.18
V1.19
V1.20
V1.21
V1.22
V1.23
V1.24
15
33
34
35
36
20
21
22
23
I/O expander board: Digital input statuses
Relay output 1 status
ROE1, ROE2, ROE3
DOE 1
I/O exp. board: Relay output statuses
I/O exp. board: Digital output 1 status
In percent of the maximum process reference
In percent of the maximum actual value
In percent of the maximum error value
In percent of the maximum output value
PID Reference
PID Actual value
PID Error value
PID Output
%
%
%
%
Autochange outputs
1,2,3
30 Used only in
P
ump and
F
an
Cascade control
Shows the current drive configuration mode selected
with start-up wizard:
0
1
2
3
4
= No mode selected (Default)
= Standard
= Fan
= Pump
= High performance
Mode
66
V1.25
Table 7-2. Monitored signals
Download from Www.Somanuals.com. All Manuals Search And Download.
7
60(96)
Control Keypad
HHoonneeyywweellll
HHoonneeyywweellll
7.4.2 Parameter menu (P2)
Parameters are the way of conveying the commands of the user to the frequency converter. The
parameter values can be edited by entering the Parameter Menu from the Main Menu when the
location indication P2 is visible on the display. The value editing procedure is presented in Figure 7-
6.
Push the Menu button right once to move into the Parameter Group Menu (G#). Locate the
parameter group desired by using the Browser buttons and push the Menu button right again to
enter the group and its parameters. Use again the Browser buttons to find the parameter (P#) you
want to edit. Pushing the Menu button right takes you to the edit mode. As a sign of this, the
parameter value starts to blink. You can now change the value in two different manners:
1
2
Just set the new desired value with the Browser buttons and confirm the change with the Enter
button. Consequently, the blinking stops and the new value is visible in the value field.
Push the Menu button right once again. Now you will be able to edit the value digit by digit.
This editing manner may come in handy, when a relatively greater or smaller value than that
on the display is desired. Confirm the change with the Enter button.
The value will not change unless the Enter button is pushed. Pressing the Menu button left
takes you back to the previous menu.
Several parameters are locked, i.e. not editable, when the drive is in RUN status. The frequency
converter must be stopped in order to edit these parameters.
The parameters values can also be locked using the function in menu S6 (see Chapter 7.4.7.2).
You can return to the Main menu anytime by pressing the Menu button left for 1—2 seconds.
The basic parameters are listed in Chapter 8.3. You will find the complete parameter lists and
descriptions in the HVAC and Multi-Control Application manuals.
Once in the last parameter of a parameter group, you can move directly to the first parameter of that
group by pushing the Browser button up.
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Control Keypad
61(96)
READY
STOP
I/O term
READY
READY
READY
STOP
STOP
STOP
I/O term
I/O term
I/O term
READY
READY
READY
STOP
STOP
STOP
I/O term
I/O term
I/O term
enter
Hz
Hz
Hz
nxlk17.fh8
Figure 7-6. Parameter value change procedure
Download from Www.Somanuals.com. All Manuals Search And Download.
7
62(96)
Control Keypad
HHoonneeyywweellll
HHoonneeyywweellll
7.4.3 Keypad control menu (K3)
In the Keypad Controls Menu, you can choose the control place, edit the frequency reference and
change the direction of the motor. Enter the submenu level with the Menu button right.
Parameters in Menu
K3
Selections
1 = I/O terminals
2 = Keypad
3 = Fieldbus
P3.1 = Selection of control
place
R3.2 = Keypad reference
P3.3 = Keypad direction
0 = Forward
1 = Reverse
0 = Limited function of Stop
button
1 = Stop button always
enabled
P3.4 = Stop button activation
P3.5 = PID reference 1
P3.6 = PID reference 2
7.4.3.1
Selection of control place
There are three different places (sources) which the frequency converter can be controlled from. For
each control place, a different symbol will appear on the alphanumeric display:
Control place
I/O terminals
Symbol
I/O term
Keypad (panel)
Fieldbus
Keypad
Bus/Comm
Change the control place by entering the edit mode with the Menu button right. The options can
then be browsed through with the Browser buttons. Select the desired control place with the Enter
button. See the diagram below. See also Chapter 7.4.3 above.
READY
term
READY
term
READY
I/O
term
STOP
STOP
STOP
I/O
I/O
READY
READY
STOP
STOP
I/O term
I/O term
enter
Figure 7-7. Selection of control place
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Control Keypad
63(96)
7.4.3.2
Keypad reference
The keypad reference submenu (R3.2) displays and allows the operator to edit the frequency
reference. The changes will take place immediately. This reference value will not, however,
influence the rotation speed of the motor unless the keypad has been selected as the active
control place.
NOTE: The maximum difference between the output frequency and the keypad reference is 6 Hz.
The application software monitors the keypad frequency automatically.
See Figure 7-6 for how to edit the reference value (pressing the Enter button is not, however,
necessary).
7.4.3.3
Keypad direction
The keypad direction submenu displays and allows the operator to change the rotating direction of
the motor. This setting will not, however, influence the rotation direction of the motor unless
the keypad has been selected as the active control place.
See Figure 7-7 for how to change the rotation direction.
7.4.3.4
Stop button activation
By default, pushing the STOP button will always stop the motor regardless of the selected control
place. You can disable this function by giving parameter 3.4 the value 0. If the value of this
parameter is 0, the STOP button will stop the motor only when the keypad has been selected as
the active control place.
See Figure 7-7 for how to change the value of this parameter.
Download from Www.Somanuals.com. All Manuals Search And Download.
7
64(96)
Control Keypad
HHoonneeyywweellll
HHoonneeyywweellll
7.4.4 Active faults menu (F4)
The Active faults menu can be entered from the Main menu by pushing the Menu button right when
the location indication F4 is visible on the keypad display.
The memory of active faults can store the maximum of 5 faults in the order of appearance. The
display can be cleared with the Reset button and the read-out will return to the same state it was
before the fault trip. The fault remains active until it is cleared with the Reset button or with a reset
signal from the I/O terminal.
Note! Remove external Start signal before resetting the fault to prevent unintentional restart of the
drive.
Normal state,
no faults:
7.4.4.1
Fault types
In the NXL frequency converter, there are two different types of faults. These types differ from each
other on the basis of the subsequent behaviour of the drive. See Table 7-3. Fault types.
Figure 7-8. Fault display
READY
READY
READY
STOP
I/O term
STOP
I/O term
STOP
I/O term
nxlk19.fh8
Fault type symbol
A
Meaning
This type of fault is a sign of an unusual operating
condition. It does not cause the drive to stop, nor does it
require any special actions. The 'A fault' remains in the
display for about 30 seconds.
(Alarm)
F
(Fault)
Table 7-3. Fault types
A 'F fault' is a kind of fault that makes the drive stop.
Actions need to be taken in order to restart the drive.
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Control Keypad
65(96)
7.4.5 Fault codes
The fault codes, their causes and correcting actions are presented in the table below. The shadowed
faults are A faults only. The items written in white on black background present faults for which you
can program different responses in the application. See parameter group Protections.
Note! When you contact the factory or the distributor due to a fault, it is advisable to write down all
fault texts and codes that appear on the keypad
Fault
code
1
Fault
Possible cause
Correcting measures
Check loading.
Check motor size.
Check cables.
Overcurrent
Frequency converter has detected too high a
current (>4*In) in the motor cable:
−
−
−
sudden heavy load increase
short circuit in motor cables
unsuitable motor
2
Overvoltage
The DC-link voltage has exceeded the limits
defined in Table 4-3.
Make the deceleration time longer.
Check motor cables and motor.
−
too short a deceleration time
−
high overvoltage spikes in supply
3
8
Earth fault
Current measurement has detected that the
sum of motor phase current is not zero.
−
insulation failure in cables or motor
System fault
Reset the fault and restart.
Should the fault re-occur, contact
the distributor near to you.
component failure
faulty operation
9
Undervoltage
DC-link voltage is under the voltage limits
defined in Table 4-3.
In case of temporary supply voltage
break reset the fault and restart the
frequency converter. Check the
supply voltage. If it is adequate, an
internal failure has occurred.
−
most probable cause: too low a supply
voltage
−
frequency converter internal fault
Contact the distributor near to you.
11
13
Output phase
supervision
Frequency
Current measurement has detected that there Check motor cable and motor.
is no current in one motor phase.
Heatsink temperature is under –10
°C
converter under
temperature
Frequency
14
Check the correct amount and flow
of cooling air.
Heatsink temperature is over 90
°C.
converter
overtemperature
Check the heatsink for dust.
Check the ambient temperature
(p2.6.8).
Overtemperature warning is issued when the
heatsink temperature exceeds 85
°C.
Make sure that the switching
frequency is not too high in relation
to ambient temperature and motor
load.
15
16
Motor stalled
Motor
Motor stall protection has tripped.
Check motor.
Check that Pump or Fan is not
jammed
Decrease the motor load.
If no motor overload exists, check
the temperature model parameters.
Motor overheating has been detected by
overtemperature frequency converter motor temperature
model. Motor is overloaded.
Download from Www.Somanuals.com. All Manuals Search And Download.
7
66(96)
Control Keypad
HHoonneeyywweellll
HHoonneeyywweellll
17
Motor
Motor underload protection has tripped.
FAN: check that Belt is not broken
PUMP: check that Pump is not dry
underload/
Pump Dry
detection/
Broken belt
Detection
22
EEPROM
Parameter save fault
Contact the distributor near to you
checksum fault
−
faulty operation
−
component failure
24
25
Counter fault
Microprocessor
watchdog fault
Values displayed on counters are incorrect
Reset the fault and restart.
Should the fault re-occur, contact
the distributor near to you.
−
−
faulty operation
component failure
29
34
Thermistor fault
The thermistor input of option board has
detected increase of the motor temperature
Check motor cooling and loading
Check thermistor connection
(If thermistor input of the option
board is not in use it has to be short
circuited)
Reset the fault and restart
Should the fault re-occur, contact
the distributor near to you.
Internal bus
communication
Ambient interference or defective hardware
35
39
40
41
Application fault
Selected application does not function.
Contact the distributor near to you.
Reset
Device removed Option board removed.
Drive removed.
Device unknown Unknown option board or drive.
Contact the distributor near to you.
IGBT temperature
Device change
IGBT Inverter Bridge overtemperature
protection has detected too high a motor
current.
Check loading.
Check motor size.
44
Option board changed.
Reset
Option board has default settings.
45
50
Device added
Analogue input
Iin<4mA
(selected signal
range 4 to 20
mA)
Option board added.
Current at the analogue input is < 4mA.
Reset
Check the current loop circuitry.
−
control cable is broken or loose
signal source has failed
−
51
52
External fault
Digital input fault. Digital input has been
programmed as external fault input and this
input is active.
Check the programming and the
device indicated by the external
fault information. Check also the
cabling of this device.
Check keypad connection and
possible keypad cable.
Keypad
communication
fault
The connection between the control keypad
and the frequency converter is broken.
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Control Keypad
67(96)
53
54
55
Fieldbus fault
Slot fault
The data connection between the fieldbus
Master and the fieldbus board is broken
Check installation.
If installation is correct contact the
nearest Honeywell distributor
Defective option board or slot
Check board and slot.
Contact the nearest Honeywell
distributor
Actual value
supervision
Actual value has exceeded or fallen below
(depending on par. 2.7.22) the actual value
supervision limit (par. 2.7.23)
Table 7-4. Fault codes
READY
READY
READY
STOP
I/O term
STOP
I/O term
STOP
I/O term
nxlk20.fh8
Push Enter to reset!
7.4.6 Fault history menu (H5)
The Fault history menu can be entered from the Main menu by pushing the Menu button right when
the location indication H5 is visible on the keypad display.
All faults are stored in the Fault history menu in which you can browse through them using the
Browser buttons. You can return to the previous menu anytime by pushing the Menu button left.
The memory of the frequency converter can store a maximum of 5 faults in the order of appearance.
The latest fault carries the indication H5.1, the second latest H5.2 etc. If there are 5 uncleared faults
in the memory the next occurring fault will erase the oldest from the memory.
Pressing the Enter button for about 2 to 3 seconds resets the whole fault history.
Figure 7-9. Fault history menu
Download from Www.Somanuals.com. All Manuals Search And Download.
7
68(96)
Control Keypad
HHoonneeyywweellll
HHoonneeyywweellll
7.4.7 System menu (S6)
The System menu can be entered from the main menu by pushing the Menu button right when the
location indication S6 is visible on the display.
The controls associated with the general use of the frequency converter, such as keypad settings, customised
parameter sets or information about the hardware and software are located under the System menu
.
Below you will find a list of the functions available in the System menu.
Functions in the System menu
Code
S6.3
Function
Copy parameters
Min
Max
Unit
Default
Cust
Selections
= Select
= Store set 1
= Load set 1
= Store set 2
= Load set 2
0
1
2
3
4
5
6
7
8
P6.3.1
Parameter sets
= Load factory defaults
= Fault
= Wait
= OK
S6.5
Security
0
1
= Change Enabled
= Change Disabled
P6.5.2
Parameter lock
0
1
0
S6.6
P6.6.1
P6.6.3
S6.7
Keypad settings
Default page
Timeout time
Hardware settings
0
5
1.1
1200
65535
s
0
1
= Continuous
= Temperature (only
P6.7.2
Fan control
0
0
sizes MF4 and bigger)
HMI acknowledg.
timeout
P6.7.3
200
1
5000
10
ms
200
5
P6.7.4
S6.8
HMI number of retries
System info
Counters menu
MWh counter
Operating days
counter
S6.8.1
C6.8.1.1
KWh
hh:mm:
ss
hh:mm:
ss
C6.8.1.2
C6.8.1.3
Operating hours
counter
S6.8.2
Trip counters
MWh trip counter
Clear MWh trip
counter
Operating days trip
counter
T6.8.2.1
kWh
0
1
= No action
= Clear MWh trip counter
P6.8.2.2
T6.8.2.3
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Control Keypad
69(96)
Operating hours trip
counter
Clear operating time
counter
hh:mm: ss
T6.8.2.4
0
1
= No action
= Clear T6.8.2.3, T6.8.2.4
P6.8.2.5
S6.8.3
Software info
Scroll information with menu
button right
I6.8.3.1
Software package
I6.8.3.2
I6.8.3.3
I6.8.3.4
S6.8.4
System SW version
Firmware interface
System load
Application info
Application
%
V
S6.8.4.1
A6.8.4.1.1
A6.8.4.1.2
A6.8.4.1.3
S6.8.5
Application id
Application version
Firmware interface
Hardware info
Unit voltage
Brake chopper
Options
I6.8.5.2
I6.8.5.3
S6.8.6
0
=Not present, 1=Present
Note! the submenus are not
showing if no option board is
installed
S6.8.6.1
Slot E OPT-
1
2
=Connection lost
=Initializing
I6.8.6.1.1
Slot E Status
1
1
5
5
3
5
=Run
=Fault
I6.8.6.1.2 Slot E Program version
Note! the submenus are not
showing if no option board is
installed
S6.8.6.2
Slot D OPT-
1
2
=Connection lost
=Initializing
I6.8.6.2.1
Slot D Status
3
5
=Run
=Fault
I6.8.6.2.2 Slot D Program version
S6.9
AI mode
0
1
=Voltage input
=Current input
P6.9.1
AIA1 mode
0
0
1
1
0
1
(Types MF4 – MF6)
0
1
=Voltage input
=Current input
P6.9.2
AIA2 mode
S6.10
Fieldbus parameters
I6.10.1
Communication status
0
1
=Not used
=Modbus protocol
P6.10.2
P6.10.3
Fieldbus protocol
Slave address
1
1
1
1
1
255
Addresses 1 – 255
0
1
2
3
4
5
6
7
8
0
=300 baud
=600 baud
=1200 baud
=2400 baud
=4800 baud
=9600 baud
=19200 baud
=38400 baud
=57600 baud
P6.10.4
Baud rate
0
8
5
=1
=None
=Not used
=2 seconds, etc
1=2
P6.10.5
P6.10.6
Stop bits
Parity type
Communication
timeout
0
0
1
2
0
0
0
1
=Odd
2=Even
0
2
1
=1 second
P6.10.7
0
300
s
0
Table 7-5. System menu functions
Download from Www.Somanuals.com. All Manuals Search And Download.
7
70(96)
Control Keypad
HHoonneeyywweellll
HHoonneeyywweellll
7.4.7.1
Copy parameters
The Copy parameters submenu (S6.3) is located under the System menu.
The Honeywell NX frequency converter features a possibility for the user to store and load two
customised parameter sets (all parameters included in the application, not the system menu
parameters) and to load back the factory default parameter values.
Parameter sets (S6.3.1)
On Parameter sets page (S6.3.1), push the Menu button right to enter the Edit menu. You can store
or load two customised parameter sets or load back the factory defaults. Confirm with the Enter
button. Wait, until 8 (=OK) appears on the display.
READY
READY
STOP
STOP
I/O term
I/O term
READY
READY
STOP
STOP
I/O term
I/O term
enter
nxlk21.fh8
Figure 7-10. Storing and loading of parameter sets
7.4.7.2
Security
The Security submenu (S6.5) under the system menu has a function that allows the user to prohibit
changes to the parameters.
Parameter lock (P6.5.2)
If the parameter lock is activated the parameter values cannot be edited.
NOTE: This function does not prevent unauthorised editing of parameter values.
Enter the edit mode by pushing the Menu button right. Use the Browser buttons to change the
parameter lock status (0 = changes enabled, 1 = changes disabled). Accept the change with the
Enter button or return to the previous level with the Menu button left.
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Control Keypad
71(96)
READY
READY
READY
STOP
STOP
STOP
I/O term
I/O term
I/O term
READY
READY
STOP
STOP
I/O term
I/O term
enter
nxlk22.fh8
Figure 7-11. Parameter locking
7.4.7.3
Keypad settings
In the submenu S6.6 under the System menu you can further customise your frequency converter
operator interface.
Locate the Keypad settings submenu (S6.6). Under the submenu, there are two pages (P#)
associated with the keypad operation, Default page (P6.6.1) and Timeout time (P6.6.3)
Default page (P6.6.1)
Here you can set the location (page) to which the display automatically moves as the Timeout time
(see below) has expired or as the power is switched on to the keypad.
Press the Menu button right once to enter the edit mode. Pressing the Menu button right once again
makes you able to edit the number of the submenu/page digit by digit. Confirm the new default page
value with the Enter button. You can return to the previous step anytime by pushing the Menu button
left.
Note! If you set a page that does not exist in the menu, the display will automatically move to the last
available page in the menu.
READY
READY
READY
STOP
STOP
STOP
I/O term
I/O term
I/O term
READY
READY
CONFIRM CHANGE
enter
STOP
term
I/O
STOP
I/O term
nxlk23.fh8
Figure 7-12. Default page function
Download from Www.Somanuals.com. All Manuals Search And Download.
7
72(96)
Control Keypad
HHoonneeyywweellll
HHoonneeyywweellll
Timeout time (P6.6.3)
The Timeout time setting defines the time, after which the keypad display returns to the Default Page
(P6.6.1), see above.
Move to the Edit menu by pressing the Menu button right. Set the timeout time you want and confirm
the change with the Enter button. You can return to the previous step anytime by pushing the Menu
button left.
NOTE: This function cannot be disabled.
READY
READY
READY
STOP
I/O term
STOP
I/O term
STOP
I/O term
enter CONFIRM CHANGE
CANCEL
s
s
nxlk24.fh8
Figure 7-13. Timeout time setting
7.4.7.4
Hardware settings
In the Hardware settings submenu (S6.7) you can further customise the settings of the frequency
converter with three parameters: Fan control, HMI acknowledgement timeout and HMI retry.
Fan control (P6.7.2)
Note! Only the higher power modules of MF3 have been equipped with a cooling fan, in lower power
modules of MF3 the cooling fan is available as optional equipment.
If the cooling fan has been installed in MF3 it runs continuously, when the power is switched on.
NXL HVAC:
This function allows you to control the frequency converter’s cooling fan. You can set the fan to run
continuously when the power is switched on or depending on the temperature of the unit. If the latter
function has been selected the fan is switched on automatically when the heat sink temperature
reaches 60°C. The fan receives a stop command when the heat sink temperature falls to 55°C.
However the fan runs for about a minute after receiving the stop command, as well as after changing
the value from 0 (Continuous) to 1 (Temperature).
Enter the edit mode by pushing the Menu button right. The present mode shown starts to blink. Use
the Browser buttons to change the fan mode. Accept the change with the Enter button or return to
the previous level with the Menu button left.
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Control Keypad
73(96)
HMI acknowledge timeout (P6.7.3)
This function allows the user to change the timeout of the HMI acknowledgement time.
Note! If the frequency converter has been connected to the PC with a normal cable, the default
values of parameters 6.7.3 and 6.7.4 (200 and 5) must not be changed.
If the frequency converter has been connected to the PC via a modem and there is delay in
transferring messages, the value of par. 6.7.3 must be set according to the delay as follows:
Example
:
•
•
•
Transfer delay between the frequency converter and the PC = 600 ms
The value of par. 6.7.3 is set to 1200 ms (2 x 600, sending delay + receiving delay)
The corresponding setting shall be entered in the
Retries = 5
[Misc]-part of the file NCDrive.ini:
AckTimeOut = 1200
TimeOut = 6000
It must also be considered that intervals that are shorter than the AckTimeOut-time cannot be used
in NC-Drive monitoring.
Enter the edit mode by pushing the Menu button right. Use the Browser buttons to change the
acknowledgement time. Accept the change with the Enter button or return to the previous level with
the Menu button left. See Figure 7-14 for how to change the HMI acknowledgement timeout.
READY
I/O
READY
I/O
READY
STOP
STOP
STOP
I/O
term
term
term
enter
s
s
nxlk25.fh8
Figure 7-14. HMI acknowledge timeout
Number of retries to receive HMI acknowledgement (P6.7.4)
With this parameter you can set the number of times the drive will try receive acknowledgement if
this does not succeed within the acknowledgement time (P6.7.3)
Enter the edit mode by pushing the Menu button right. The present value shown starts to blink. Use
the Browser buttons to change the amount of retries. Accept the change with the Enter button or
return to the previous level with the Menu button left.
7.4.7.5
System information
In the submenu S6.8 under the System menu you can find frequency converter-related hardware
and software information as well as operation-related information.
Enter the Info menu by pressing the Menu button right. Now you can browse through the information
pages with the Browser buttons.
Download from Www.Somanuals.com. All Manuals Search And Download.
7
74(96)
Control Keypad
HHoonneeyywweellll
HHoonneeyywweellll
Counters submenu (S6.8.1)
In the Counters submenu (S6.8.1) you can find information related to the frequency converter
operation times, i.e. the total numbers of MWh, operation days and operation hours passed so far.
Unlike the counters in the trip counters menu, these counters cannot be reset.
Note! The operation time counter (days and hours) runs always, when the power is on.
Page
Counter
MWh counter
Operation day counter
Operation hour counter
C6.8.1.1
C6.8.1.2
C6.8.1.3
Table 7-6. Counter pages
Trip counters submenu (S6.8.2)
Trip counters (menu S6.8.2) are counters the values of which can be reset i.e. restored to zero. You
have the following resettable counters at your disposal:
Page
Counter
MWh counter
Clear MWh counter
Operation day counter
Operation hour counter
Clear operation time counter
T6.8.2.1
P6.8.2.2
T6.8.2.3
T6.8.2.4
P6.8.2.5
Table 7-7. Trip counter pages
Note! The trip counters run only when the motor is running.
Example: When you want to reset the operation counters, you should do the following:
READY
READY
STOP
STOP
I/O term
I/O term
READY
READY
STOP
STOP
I/O term
I/O term
enter
nxlk26.fh8
Figure 7-15. MWh counter reset
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Control Keypad
75(96)
Software info submenu (S6.8.3)
The following information can be found under the Software info submenu (S6.8.3):
Page
Content
I6.8.3.1
I6.8.3.2
I6.8.3.3
I6.8.3.4
Software package
System software version
Firmware interface
System load
Table 7-8. Software information pages
Application information submenu (S6.8.4)
You can find the following information from the Application info submenu (S6.8.4)
Page
A6.8.4.1
Content
Application
D6.8.4.1.1
D6.8.4.1.2
D6.8.4.1.3
Application id
Version
Firmware interface
Table 7-9. Application information pages
Hardware information submenu (S6.8.5)
You can find the following information from the Hardware info submenu (S6.8.5)
Page
Content
I6.8.5.2
I6.8.5.3
Table 7-10. Hardware information pages
Unit voltage
Brake chopper
Connected options submenu (S6.8.6)
The Connected options submenu (S6.8.6) shows the following information on the option board
connected to the frequency converter:
Page
S6.8.6.1
Content
Slot E Option board
I6.8.6.1.1 Slot E Option board status
I6.8.6.1.2 Slot E Program version
S6.8.6.2
Slot D Option board
I6.8.6.2.1 Slot D Option board status
I6.8.6.2.2 Slot D Program version
Table 7-11. Connected options submenu
In this submenu you find information about the option board connected to the control board (see
chapter 6.2)
You can check the status of the slot by entering the board submenu with the Menu button right and
using the Browser buttons. Push the Menu button right again to display the status of the board. The
selections are shown in Table 7-5. The keypad will also display the program version of the
respective board when you push either one of the Browser buttons.
Download from Www.Somanuals.com. All Manuals Search And Download.
7
76(96)
Control Keypad
HHoonneeyywweellll
HHoonneeyywweellll
For more information on the expander board-related parameters, see Chapter 7.4.9.
READY
READY
STOP
I/O term
STOP
I/O term
nxlk27.fh8
Figure 7-16. Expander board information menu
7.4.7.6
AI mode
The parameters P6.9.1 and P6.9.2 select the analogue input mode. P6.9.1 appears only in classes
MF4 – MF6
0 = voltage input (par. 6.9.1 default)
1 = current input (par. 6.9.2 default)
Note! Make sure that the jumper selections correspond to the selections of this parameter. See
Figure 6-23.
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Control Keypad
77(96)
7.4.8 Modbus interface
NXL has a built-in Modbus RTU bus interface. The signal level of the interface is in accordance with
the RS-485 standard.
RS-485 Transceiver
Control terminal
RS-485 A
RS-485 B
Terminal resistor 120Ω
X7 -> MF2-MF3
X9 -> MF4-MF6
Protocol:
Modbus RTU
Baud rates:
300, 600, 1200, 2400, 4800,
9600, 19200, 38700, 57600 (bit/s)
RS-485 (TIA/EIA-485-A)
2 kΩ
Signal level:
Input impedance:
7.4.8.1
Modbus RTU protocol
Modbus RTU protocol is a simple but effective fieldbus protocol. Modbus network has a bus
topology, where every device has an individual address. With the help of the individual bus
addresses the commands are directed to the single devices within the network. Modbus supports
also broadcast -type messages, which are received by every device of the bus. Broadcast messages
are sent to the address ’0’ which is reserved for these messages.
The protocol includes CRC error detection and parity check for preventing the handling of messages
containing errors. In Modbus the data is transferred in hex mode asynchronically and a break of
approximately 3.5 characters is used as an end character. The length of the break depends on the
used baud rate.
Function
code
03
04
06
Function name
Address
Broadcast
messages
No
No
Yes
Read Holding Register
Read Input Register
Preset Single Register
Preset Multiple Register
All ID numbers
All ID numbers
All ID numbers
All ID numbers
16
Yes
Table 7-12. Modbus commands supported by NXL
Download from Www.Somanuals.com. All Manuals Search And Download.
7
78(96)
Control Keypad
HHoonneeyywweellll
HHoonneeyywweellll
7.4.8.2
Termination Resistor
The RS-485 bus is terminated with 120 Ω termination resistors in both ends. NXL has a built-in
termination resistor which is switched off as a default. See the jumper selections in chapter 6.2.5.1
7.4.8.3
Modbus address area
The Modbus bus of NXL uses the ID numbers of the application as addresses. The ID numbers can
be found in the parameter tables of the Application manual.
When several parameters/monitoring values are read at a time they must be consecutive. 11
addresses can be read and the addresses can be parameters or monitoring values.
7.4.8.4
Modbus process data
Process data is an address area for fieldbus control. Fieldbus control is active when the value of
parameter 3.1 (Control place) is 2 (=fieldbus). The contents of the process data has been
determined in the application. The following tables present the process data contents in the Multi-
Control Application.
Output Process data
Addr.
2101
2102
2103
2104
2105
2106
2107
2108
2109
2110
2111
Modbus register
32101, 42101
32102, 42102
32103, 42103
32104, 42104
32105, 42105
32106, 42106
32107, 42107
32108, 42108
32109, 42109
32110, 42110
32111, 42111
Name
Scale
-
-
Type
Binary coded
Binary coded
%
+/- Hz
+/- Rpm
A
+/- % (of nominal)
+/- % (of nominal)
V
V
FB Status Word
FB General Status Word
FB Actual Speed
Motor speed
0,01
0,01
1
0,1
0,1
0,1
0,1
1
Motor speed
Motor current
Motor Torque
Motor Power
Motor Voltage
DC Voltage
Active Fault
-
Fault code
Input Process data
Addr.
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
Modbus register
Name
FB Control Word
FB General Control Word
FB Speed Reference
PID Control Reference
PID Actual Value
-
-
-
-
-
-
Scale
-
-
0,01
0,01
0,01
-
-
-
-
-
-
Type
Binary coded
Binary coded
%
%
%
-
-
-
32001, 42001
32002, 42002
32003, 42003
32004, 42004
32005, 42005
32006, 42006
32007, 42007
32008, 42008
32009, 42009
32010, 42010
32011, 42011
-
-
-
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Control Keypad
79(96)
Status Word
15
-
14
-
13
-
12
-
11
-
10
-
9
-
8
-
7
F
6
Z
5
4
3
2
1
0
AREF
W
FLT
DIR
RUN RDY
Information about the status of the device and messages is indicated in the Status word. The Status
word is composed of 16 bits the meanings of which are described in the table below:
Actual speed
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
MSB
LSB
This is actual speed of the frequency converter. The scaling is –10000...10000. In the application,
the value is scaled in percentage of the frequency area between set minimum and maximum
frequency.
Control word
15
-
14
-
13
-
12
-
11
-
10
-
9
-
8
-
7
-
6
-
5
-
4
-
3
-
2
1
0
RST
DIR
RUN
In Honeywell applications, the three first bits of the control word are used to control the frequency
converter. However, you can customise the content of the control word for your own applications
because the control word is sent to the frequency converter as such.
Speed reference
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
MSB
LSB
This is the Reference 1 to the frequency converter. Used normally as Speed reference. The allowed
scaling is –10000...10000. In the application, the value is scaled in percentage of the frequency area
between the set minimum and maximum frequencies.
Bit definitions
Bit
Description
Value = 1
Run
Value = 0
Stop
Clockwise
RUN
DIR
RST
RDY
FLT
W
Counter clockwise
Rising edge of this bit will reset active fault
Drive not ready
No fault
No warning
Drive ready
Fault active
Warning active
AREF
Z
F
Ramping
-
-
Speed reference reached
Drive is running at zero speed
Flux Ready
Download from Www.Somanuals.com. All Manuals Search And Download.
7
80(96)
Control Keypad
HHoonneeyywweellll
HHoonneeyywweellll
7.4.8.5
Fieldbus parameters
RS-485 communication status (I6.10.1)
With this function you can check the status of the RS 485 bus. If the bus is not in use, this value is 0.
xx.yyy
xx = 0 – 64 (Number of messages containing errors)
yyy = 0 – 999 (Number of messages received correctly)
Fieldbus protocol (P6.10.2)
With this function you can select the fieldbus communications protocol.
0 = Not used
1 = Modbus protocol
Slave address (P6.10.3)
Set here the slave address for the Modbus protocol. You can set any address between 1 and 255.
Baud rate (P6.10.4)
Selects the baud rate used with the Modbus communication.
0 = 300 baud
1 = 600 baud
2 = 1200 baud
3 = 2400 baud
4 = 4800 baud
5 = 9600 baud
6 = 19200 baud
7 = 38400 baud
8 = 57600 baud
Stop bits (P6.10.5)
Set the number of stop bits used in Modbus communication
0 = 1 stop bit
1 = 2 stop bits
Parity type (P6.10.6)
Here you can select the type of parity checking used with the Modbus communication.
0 = None
1 = Odd
2 = Even
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Control Keypad
81(96)
Communication time-out (P6.10.7)
If communication between two messages is broken for a longer time than that defined by this
parameter, a communication error is initiated. If the value of this parameter is 0, the function is not
used.
0 = Not used
1 = 1 second
2 = 2 seconds, etc
7.4.9 Expander board menu (E7)
The Expander board menu makes it possible for the user 1) to see which expander board is
connected to the control board and 2) to reach and edit the parameters associated with the expander
board.
Enter the following menu level (E#) with the Menu button right. You can view and edit the parameter
values in the same way as described in chapter 7.4.2.
7.5 Further keypad functions
The Honeywell NXL control keypad embodies additional application-related functions. See NXL
Application Manuals for more information.
Download from Www.Somanuals.com. All Manuals Search And Download.
82(96)
Commissioning
HHoonneeyywwee
HHoonneeyywwee
8.
COMMISSIONING
8.1 Safety
Before commissioning, note the following directions and warnings:
Internal components and circuit boards of the frequency converter
1
(except for the galvanically isolated I/O terminals) are live when NXL is
connected to mains potential. Coming into contact with this voltage is
extremely dangerous and may cause death or severe injury.
The motor terminals U, V, W and the DC-link/brake resistor terminals –/+
are live when NXL is connected to mains, even if the motor is not
running.
2
3
WARNING
The control I/O-terminals are isolated from the mains potential. However,
the relay outputs and other I/O-terminals may have a dangerous control
voltage present even when NXL is disconnected from mains.
Do not make any connections with the frequency converter connected to
the mains.
4
5
After having disconnected the frequency converter from the mains, wait
until the fan stops and the indicators on the keypad go out (if no keypad
is attached see the indicator through the keypad base). Wait 5 more
minutes before doing any work on NXL connections. Do not even open
the cover before this time has expired.
Before connecting the frequency converter to mains make sure that the
NXL front cover is closed.
6
7
The heat sink of types MF2 and MF3 may be hot when the frequency
converter is in use. Coming into contact with the heat sink may cause
burns.
HOT SURFACE
8.2 Commissioning of the frequency converter
1
2
Read carefully the safety instructions in Chapter 6 and above and follow them.
After the installation, make sure that:
- both the frequency converter and the motor are grounded.
- the mains and motor cables comply with the requirements given in Chapter 6.1.1.
- the control cables are located as far as possible from the power cables (see Chapter 6.1.3,
step 3); the shields of the shielded cables are connected to protective earth
may not touch the electrical components of the frequency converter.
. The wires
- For option boards only: make sure that the common ends of digital input groups are
connected to +24V or ground of the I/O terminal or the external supply.
3
4
5
6
7
Check the quality and quantity of cooling air (Chapter 5.2).
Check the inside of the frequency converter for condensation.
Check that all Start/Stop switches connected to the I/O terminals are in Stop-position.
Connect the frequency converter to mains.
Set the parameters of group 1 according to the requirements of your application. At least the
following parameters should be set:
-
-
motor nominal voltage
motor nominal frequency
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Commissioning
83(96)
-
-
motor nominal speed
motor nominal current
You will find the values needed for the parameters on the motor rating plate.
NOTE! You can also run the Start-up Wizard. See Chapter 7.3 or NXL HVAC quick guide for
more information.
8
Perform run test without motor
Perform either Test A or Test B:
A Controls from the I/O terminals:
a) Turn the Start/Stop switch to ON position.
b) Change the frequency reference (potentiometer)
c) Check in the Monitoring menu (M1) that the value of Output frequency changes according to the
change of frequency reference.
d) Turn the Start/Stop switch to OFF position.
B
Control from the control keypad:
a) Change the control from the I/O terminals to the keypad as advised in Chapter 7.4.3.1.
start
b) Push the Start button on the keypad
.
c) Move over to the Keypad Control Menu (K3) and Keypad Reference submenu (Chapter7.4.3)
and change the frequency reference using the Browser buttons
-
+
.
d) Check in the Monitoring menu (M1) that the value of Output frequency changes according to the
change of frequency reference.
stop
e) Push the Stop button on the keypad
.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
84(96)
Commissioning
HHoonneeyywwee
HHoonneeyywwee
9
Run the start-up tests without the motor being connected to the process, if possible. If this is not
possible, secure the safety of each test prior to running it. Inform your co-workers of the tests.
a) Switch off the supply voltage and wait up until the drive has stopped as advised at Chapter 8.1,
step 5.
b) Connect the motor cable to the motor and to the motor cable terminals of the frequency converter.
c) See to that all Start/Stop switches are in Stop positions.
d) Switch the mains ON
e) Repeat test 8A or 8B.
10 Connect the motor to the process (if the start-up test was run without the motor being connected)
a) Before running the tests, make sure that this can be done safely.
b) Inform your co-workers of the tests.
c) Repeat test 8A or 8B.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Commissioning
85(96)
8.3 Basic parameters
On the next pages you will find the list of parameters that are essential for the commissioning of the
frequency converter. You will find more details of these and other special parameters in the HVAC and in
the Multi-Control Application manuals.
Column explanations:
Code
Parameter
Min
= Location indication on the keypad; Shows the operator the present param. number
= Name of parameter
= Minimum value of parameter
Max
= Maximum value of parameter
Unit
Default
= Unit of parameter value; Given if available
= Value preset by factory
Cust
= Customer’s own setting
ID
= ID number of the parameter (used with PC tools)
=
On the parameter code: parameter value can only be changed after the FC has been
stopped.
8.3.1 Monitoring values (Control keypad: menu M1)
The monitoring values are the actual values of parameters and signals as well as statuses and
measurements. Monitoring values cannot be edited. See Chapter 7.4.1 for more information.
Code
V1.1
V1.2
V1.3
V1.4
Parameter
Output frequency
Frequency reference
Motor speed
Unit
Hz
Hz
rpm
A
ID
1
25
2
Description
Frequency to the motor
Calculated motor speed
Measured motor current
Motor current
3
V1.5
Motor torque
%
4
Calculated actual torque/nominal torque of the unit
V1.6
Motor power
%
5
Calculated actual power/nominal power of the unit
V1.7
Motor voltage
V
6
Calculated motor voltage
V1.8
DC-link voltage
V
7
Measured DC-link voltage
V1.9
Unit temperature
Analogue input 1
Analogue input 2
Analogue output current
Analogue output current 1, expander board
Analogue output current 2, expander board
DIN1, DIN2, DIN3
DIE1, DIE2, DIE3
RO1
ROE1, ROE2, ROE3
DOE 1
PID Reference
PID Actual value
PID Error value
PID Output
ºC
V
8
Heat sink temperature
AI1
AI2
AO1
V1.10
V1.11
V1.12
V1.13
V1.14
V1.15
V1.16
V1.17
V1.18
V1.19
V1.20
V1.21
V1.22
V1.23
V1.24
13
14
26
31
32
15
33
34
35
36
20
21
22
23
30
mA
mA
Digital input statuses
I/O expander board: Digital input statuses
Relay output 1 status
I/O exp. board: Relay output statuses
I/O exp. board: Digital output 1 status
In percent of the maximum frequency
In percent of the maximum actual value
In percent of the maximum error value
In percent of the maximum output value
Used only in pump and fan control
Shows the current operating mode selected with the
Start-up Wizard: 1=Standard, 2= Fan, 3= Pump, 4=
High Performance
%
%
%
%
Autochange outputs 1, 2, 3
V1.25
Mode
66
Table 8-1. Monitoring values
8
Download from Www.Somanuals.com. All Manuals Search And Download.
86(96)
Commissioning
HHoonneeyywwee
HHoonneeyywwee
8.3.2 HVAC parameters in NXL HVAC (Control keypad: Menu P2
ꢀ
B2.1)
Code
P2.1.1
Parameter
Min frequency
Min
0,00
Max
Par. 2.1.2
Unit
Hz
Default**
0,00
Cust
ID
101
Note
NOTE: If fmax > than the
motor synchronous speed,
check suitability for motor
and drive system
P2.1.2
Max frequency
Par. 2.1.1 320,00
Hz
50,00
102
P2.1.3
P2.1.4
Acceleration time 1
Deceleration time 1
0,1
0,1
3000,0
3000,0
s
s
1,0
1,0
103
104
NOTE: Formulas apply
approximately for
P2.1.5
Current limit
0,1 x IL
1,5 x IL
A
IL
107
frequency converters up to
MF3. For greater sizes,
consult the factory.
Nominal current of
the motor
Check the rating plate of
the motor
The default applies for a 4-
pole motor and a nominal
size frequency converter.
P2.1.6
P2.1.7
0,3 x IL
300
1,5 x IL
20000
A
IL
113
112
Nominal speed of
the motor
rpm
1440
0
1
2
0
1
=Ramp
=Flying start
=Conditional Flying start*
=Coasting
P2.1.8
P2.1.9
Start function
Stop function
0
0
1
1
0
0
505
506
731
110
=Ramp
0
1
=Not used
=Used (3 x automatic
P2.1.10
P2.1.11
Automatic restart
0
1
0
Restart)
Nominal voltage of
the motor
380
500
V
400V
Nominal frequency
of the motor
Preset speed 1
Check the rating plate of
the motor
P2.1.12
P2.1.13
30,00
0,00
320,00
Hz
Hz
50,00
10,00
111
105
Par. 2.1.2
0
1
=All parameters and
menus visible
=HVAC group P2.1 and
115
1
P2.1.14 Parameter conceal
0
1
menus M1 – H5 visible
Table 8-2. HVAC parameters P2.1 in NXL HVAC
* Start mode where Trip Free Output Switching is enabled, recommended to be used with all pump and fan
applications.
** Default values if Start-up wizard has not been used. Look Figure 7-3 on page 54 or NXL HVAC Quick
Guide to see the values with different modes in wizard.
NOTE! Deactivating Parameter conceal P.2.1.14 gets all parameters into use in NXL HVAC drive
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Commissioning
87(96)
8.3.3 Basic parameters (Control keypad: Menu P2
ꢀ
B2.1 / B2.1.15)
In NXL HVAC the full NXL basic group can be found under the subgroup 2.1.15.
Code
Parameter
Min
Max
Unit
Default**
ID
Note
NXL
Compact
NXL
HVAC
Min
frequency
0,00
Par. 2.1.2
320,00
Hz
Hz
0,00
101
102
P2.1.1
P2.1.15.1
P2.1.15.2
NOTE: If fmax > than the
motor synchronous speed,
check suitability for motor
and drive system
Max
frequency
P2.1.2
Par. 2.1.1
50,00
Acceleration
time 1
Deceleration
time 1
P2.1.3
P2.1.4
P2.1.15.3
P2.1.15.4
0,1
0,1
3000,0
3000,0
s
s
1,0
1,0
103
104
NOTE: Formulas apply
approximately for
P2.1.5
P2.1.15.5 Current limit 0,1 x IL
Nominal
1,5 x IL
A
IL
107
frequency converters up to
MF3. For greater sizes,
consult the factory.
NXL2:230V
NXL5:400V
P2.1.6
P2.1.7
P2.1.8
P2.1.15.6
P2.1.15.7
P2.1.15.8
voltage of
the motor
Nominal
frequency
of the motor
Nominal
180
30,00
300
690
V
Hz
rpm
A
110
111
112
Check the rating plate of
the motor
320,00
20 000
50,00
1440
The default applies for a 4-
pole motor and a nominal
size frequency converter.
Check the rating plate of
the motor
speed of
the motor
Nominal
P2.1.9
P2.1.10
P2.1.11
P2.1.15.9
current of
the motor
0,3 x IL
0,30
0
1,5 x IL
1,00
1
IL
0,85
0
113
120
505
Check the rating plate of
the motor
P2.1.15.10
Motor cos
ϕ
0
1
2
0
1
0
1
0
1
2
3
=Ramp
=Flying start
=Conditional Flying start*
=Coasting
=Ramp
=Not used
=Automatic torque boost
=AI1
P2.1.15.11 Start function
P2.1.12
P2.1.13
P2.1.15.12 Stop function
0
0
1
1
0
0
506
109
U/f
P2.1.15.13
optimisation
=AI2
=Keypad reference
=Fieldbus reference
(FBSpeedReference)
=Motor potentiometer
=AI1/AI2 selection
P2.1.14
P2.1.15
P2.1.15.14 I/O reference
0
1
5
4
0
2
117
390
4
5
Not used if AI2 Custom min
> 0% or AI2 custom max. <
100%
AI2 signal
P2.1.15.15
1
2
3
4
=0mA – 20mA
=4mA – 20mA
=0V – 10V
range
=2V – 10V
8
Download from Www.Somanuals.com. All Manuals Search And Download.
88(96)
Commissioning
HHoonneeyywwee
HHoonneeyywwee
0
1
2
3
=Not used
=Output freq. (0—fmax
=Freq. reference (0—fmax
=Motor speed (0—Motor
nominal speed)
)
)
4
=Output current (0—
InMotor
)
Analogue
output
function
5
6
7
=Motor torque (0—TnMotor
=Motor power (0—PnMotor
=Motor voltage (0—
)
)
307
P2.1.16
P2.1.15.16
0
12
1
UnMotor
=DC-link volt (0—1000V)
=PI controller ref. value
)
8
9
10=PI contr. act. value 1
11=PI contr. error value
12=PI controller output
0
=Not used
1
2
3
4
5
6
7
8
9
=Start Reverse
=Reverse
=Stop pulse
=External fault, cc
=External fault, oc
=Run enable
=Preset speed 2
= Motor pot. UP (cc)
= Disable PID (Direct freq.
reference)
DIN2
function
319
P2.1.17
P2.1.15.17
0
10
1
10=Interlock 1
0
1
2
3
4
5
6
7
8
9
=Not used
=Reverse
=External fault, cc
=External fault, oc
=Fault reset
=Run enable
=Preset speed 1
=Preset speed 2
=DC-braking command
=Motor pot. UP (cc)
DIN3
function
301
10=Motor pot. DOWN (cc)
11=Disable PID (PID
control selection)
P2.1.18
P2.1.15.18
0
17
6
12=PID Keypad ref. 2
selection
13=Interlock 2
14=Thermistor input (See
Chapter 6.2.4
)
15=Force CP to I/O
16=Force CP to Fieldbus
17=AI1/AI2 selection
Preset
speed 1
Preset
speed 2
Automatic
restart
105
106
731
P2.1.19
P2.1.20
P2.1.21
P2.1.15.19
P2.1.15.20
P2.1.15.21
0,00
0,00
0
Par. 2.1.2
Par. 2.1.2
1
Hz
Hz
10,00
50,00
0
0
1
0
=Not used
=Used
=All parameters and
menus visible
Parameter
conceal
115
P2.1.22
0
1
0
1
=Only group P2.1 and
menus M1 – H5 visible
Table 8-3. Basic parameters P2.1
* Start mode where Trip Free Output Switching is enabled, recommended to be used with all pump and fan
applications.
** Default values if Start-up wizard has not been used. Look Figure 7-3 on page 54 or NXL HVAC Quick
Guide to see the values with different modes in wizard.
9.
FAULT TRACING
When a fault is detected by the frequency converter control electronics, the drive is stopped and the
symbol F together with the ordinal number of the fault and the fault code appear on the display. The
8
Download from Www.Somanuals.com. All Manuals Search And Download.
9
Fault tracing
89(96)
fault can be reset with the Reset button on the control keypad or via the I/O terminal. The faults are
stored in the Fault history menu (H5) which can be browsed. The different fault codes you will find in
the table below.
The fault codes, their causes and correcting actions are presented in the table below. The shadowed
faults are A faults only. The items written in white on black background present faults for which you
can program different responses in the application. See parameter group Protections.
Fault
code
1
Fault
Possible cause
Correcting measures
Overcurrent
Frequency converter has detected too
high a current (>4*In) in the motor cable:
Check loading.
Check motor size.
Check cables.
−
−
−
sudden heavy load increase
short circuit in motor cables
unsuitable motor
2
3
8
9
Overvoltage
Earth fault
The DC-link voltage has exceeded the
limits defined in.
Make the deceleration time longer.
Check motor cables and motor.
−
too short a deceleration time
−
high overvoltage spikes in utility
Current measurement has detected that
the sum of motor phase current is not
zero.
−
insulation failure in cables or motor
System fault
Undervoltage
Reset the fault and restart.
Should the fault re-occur, contact the
distributor near to you.
component failure
faulty operation
DC-link voltage is under the voltage limits In case of temporary supply voltage
defined in.
break reset the fault and restart the
frequency converter. Check the supply
voltage. If it is adequate, an internal
failure has occurred.
−
most probable cause: too low a
supply voltage
−
frequency converter internal fault
Contact the distributor near to you.
11
13
Output phase
supervision
Frequency
Current measurement has detected that
there is no current in one motor phase.
Check motor cable and motor.
Heatsink temperature is under –10
°C
converter under
temperature
Frequency
14
Check the correct amount and flow of
cooling air.
Heatsink temperature is over 90
°C.
converter
overtemperature
Check the heatsink for dust.
Check the ambient temperature.
Make sure that the switching frequency
is not too high in relation to ambient
temperature and motor load.
Check motor.
Overtemperature warning is issued when
the heatsink temperature exceeds 85
Motor stall protection has tripped.
°C.
15
16
Motor stalled
Motor
Check that Pump or Fan is not blocked.
Decrease the motor load.
Motor overheating has been detected by
overtemperature frequency converter motor temperature
model. Motor is overloaded.
If no motor overload exists, check the
temperature model parameters.
Download from Www.Somanuals.com. All Manuals Search And Download.
9
90(96)
Fault tracing
HHoonneeyywweellll
HHoonneeyywweellll
17
Motor
Motor underload protection has tripped.
FAN: check that Belt is not broken
underload/
Pump Dry
detection/
Broken belt
Detection
EEPROM
checksum fault
PUMP: check that Pump is not dry
Parameter save fault
Contact the distributor near to you
22
24
25
−
faulty operation
−
component failure
Counter fault
Values displayed on counters are
incorrect
Microprocessor
watchdog fault
Reset the fault and restart.
Should the fault re-occur, contact the
distributor near to you.
−
−
faulty operation
component failure
29
34
Thermistor fault
The thermistor input of option board has
detected increase of the motor
temperature
Check motor cooling and loading
Check thermistor connection
(If thermistor input of the option board is
not in use it has to be short circuited)
Should the fault re-occur, contact the
distributor near to you.
Internal bus
communication
Ambient interference or defective
hardware
35
39
40
41
Application fault
Selected application does not function.
Contact the distributor near to you.
Reset
Device removed Option board removed.
Drive removed.
Device unknown Unknown option board or drive.
Contact the distributor near to you.
IGBT temperature
Device change
IGBT Inverter Bridge overtemperature
protection has detected too high a motor
current.
Check loading.
Check motor size.
44
Option board changed.
Reset
Option board has default settings.
45
50
Device added
Analogue input
Iin < 4mA
(selected signal
range 4 to 20
mA)
Option board added.
Current at the analogue input is < 4mA.
Reset
Check the current loop circuitry.
−
control cable is broken or loose
signal source has failed
−
51
52
External fault
Digital input fault. Digital input has been
programmed as external fault input and
this input is active.
Check the programming and the device
indicated by the external fault
information. Check also the cabling of
this device.
Check keypad connection and possible
keypad cable.
Keypad
communication
fault
The connection between the control
keypad and the frequency converter is
broken.
Download from Www.Somanuals.com. All Manuals Search And Download.
9
Fault tracing
91(96)
53
54
55
Fieldbus fault
Slot fault
The data connection between the fieldbus Check installation.
Master and the fieldbus board is broken
If installation is correct contact the
nearest Honeywell distributor.
Defective option board or slot
Check board and slot.
Contact the nearest Honeywell
distributor.
Actual value
supervision
Actual value has exceeded or fallen below
(depending on par. 2.7.22) the actual
value supervision limit (par. 2.7.23)
Table 9-1. Fault codes
Download from Www.Somanuals.com. All Manuals Search And Download.
92(96)
HHoonneeyywweellll
HHoonneeyywweellll
10. DESCRIPTION OF EXPANDER BOARD NXLOPTAA
Description: I/O expander board with one relay output, one open collector output
and three digital inputs.
Allowed slots:
Type ID:
Honeywell NXL board slot E
16705
Terminals:
Two terminal blocks; Screw terminals (M2.6 and M3); No coding
Jumpers:
Board parameters:
None
None
I/O terminals on NXLOPTAA
Terminal
Parameter
setting
Description
X3
1
2
3
4
5
+24V
Control voltage output; voltage for switches etc, max. 150 mA
Ground for controls, e.g. for +24 V and DO
Digital input 1
Digital input 2
Digital input 3
GND
DIN1
DIN2
DIN3
DO1
DIGIN:x.1
DIGIN:x.2
DIGIN:x.3
DIOUT:x.1
6
X5
Open collector output, 50mA/48V
24 RO1/NC
DIOUT:x.2
Relay output 1 (NO)
Switching capacity:
24VDC/8A
250VAC/8A
125VDC/0,4A
25 RO1/C
26 RO1/NO
Table 10-1. I/O terminals of board NXLOPTAA
Note! The +24 V control voltage terminal can also be used to power the control module (but not the
power module).
10
Download from Www.Somanuals.com. All Manuals Search And Download.
11
Expander board NXLOPTAI
93(96)
11. DESCRIPTION OF EXPANDER BOARD NXLOPTAI
Description:
I/O expander board with one relay output (NO), three digital inputs and one
thermistor input for Honeywell NXL frequency converters
Allowed slots:
Type ID:
Honeywell NXL board slot E (standard board in NXL HVAC)
16713
Terminals:
Three terminal blocks; Screw terminals; No coding
Jumpers:
Board parameters:
None
None
Download from Www.Somanuals.com. All Manuals Search And Download.
11
94(96)
Expander board NXLOPTAI
HHoonneeyywweellll
HHoonneeyywweellll
Terminal
Parameter
setting
Description
X4
12 +24V
13 GND
14 DIN1
15 DIN2
16 DIN3
Control voltage output; voltage for switches etc, max. 150 mA
Ground for controls, e.g. for +24 V and DO
Digital input 1
Digital input 2
Digital input 3
DIGIN:B.1
DIGIN:B.2
DIGIN:B.3
X2
25 RO1/
DigOUT:B.1
Relay output 1 (NO)
Switching capacity:
Common
26 RO1/
Normal
Open
24VDC/8A
250VAC/8A
125VDC/0,4A
X3
28 TI+
29 TI-
Thermistor input; Rtrip = 4.7 kΩ (PTC), galvanically isolated
DIGIN:B.4
Table 11-1. I/O terminals of board NXLOPTAI
Note! The +24 V control voltage terminal can also be used to power the control module (but not the
power module).
Download from Www.Somanuals.com. All Manuals Search And Download.
NXL HVAC Basic speed control – Quick setup
95(96)
12. NXL HVAC BASIC SPEED CONTROL – QUICK SETUP
This chapter provides basic setup instructions for the user of NXL HVAC inverters, when using Basic
Speed Control in HVAC applications.
What you need to know
Motor nameplate data
Nominal current
Nominal speed
Speed signal specification
ꢃ
ꢃ
Pump
or
Motor
Load
Signal type (V, mA)
Range (0-10, 2-10, 0-20, 4-20)
ꢃ
ꢃ
Fan
Pressure
Sensor
Speed Signal
V signal to AI1
mA signal to AI2
Variable Frequency Drive
Control System
Setup
1 Run the Start-up Wizard
Note: Running the Start Up Wizard resets all parameters to their default values.
•
•
•
•
•
•
Hold STOP button down for 5 seconds
Select application type FAN or PUMP and confirm with ENTER
Select motor nominal speed and confirm with ENTER
Select motor nominal current and confirm with ENTER
For speed signal 0 – 10 V use AI1 (Analogue Input 1)
All settings DONE
2 Control Signal Settings for Speed Signals other than 0 – 10 V
•
For other selections full parameter view is needed:
P2.1.14 Parameter Conceal
Set to 0 (not in use)
Set to 4 (2 – 10 V)
•
For speed signal 2 – 10 V use Analogue Input 1
P2.2.6 AI1 Signal Range
•
•
For speed signal 4 – 20 mA use Analogue Input 2
P2.1.15.14 I/O Reference Set to 1 (AI2)
For speed signal 0 – 20 mA use Analogue Input 2
P2.1.15.14
I/O Reference
Set to 1 (AI2)
P2.2.12
AI2 Signal Range
Set to 1 (0 – 20 mA)
Manual Test
1 Hold LEFT down for 3-5 seconds
Control Place automatically switches to Keypad
2 Use normal keypad buttons for speed control
•
UP and DOWN to adjust the speed
START and STOP for control
•
3 Hold LEFT down for 3 seconds to return to remote control (I/O or Fieldbus)
Download from Www.Somanuals.com. All Manuals Search And Download.
12
Find out more
For more information on
Honeywell’s frequency
converters and other Honeywell
products, visit us online at
Automation and Control Solutions
Honeywell GmbH
Böblinger Str. 17
71101 Schönaich, Germany
Telephone (49) 7031 637 01
EN1B-0388GE51 R1107
November 2007
© 2007 Honeywell International Inc.
Telefax
(49) 7073 637 493
Download from Www.Somanuals.com. All Manuals Search And Download.
|