| C554A   Cadmium Sulfide Flame Detector   INSTALLATION INSTRUCTIONS   APPLICATION   CAUTION   Disconnect power supply before beginning   installation to prevent electrical shock or equipment   damage.   The C554A Cadmium Sulfide Flame Detector (cad cell) is   a photo conductive flame detector (see Fig. 1) used with   oil primary controls such as R4166, R4184, R8182,   R8184, R8185, R8404 and R8991. It consists of a plug-in,   light sensitive cell and a socket with Type E mounting   bracket, factory-installed leadwire and an oil line adapter   bracket. Leadwire length is 60 in. (1520 mm). The detector   is installed inside the air tube of the burner where the cell   can view the flame and is wired to the F-F terminals of the   oil primary control.   Location   The burner manufacturer determines the cad cell location   (see Fig. 2). If an alternate location must be used, make   sure that:   ³ · » The cell has a clear view of the flame.   Ambient light does not reach the cell.   Ambient temperature at the cell location is below   140°F (60°C).   Movement, shielding, or radiation of metal surfaces   near the cell do not affect cell function.   The photocell is a ceramic disk coated with cadmium   sulfide and overlaid with a conductive grid. Electrodes   attached to the ceramic disk transmit an electrical signal to   the primary control. In darkness, cadmium sulfide has a   very high resistance to the passage of electrical current. In   visible light, its resistance is very low and current is   allowed to pass. The entire cell is hermetically sealed   (glass to metal) to prevent cell deterioration.   ¿ IGNITION   TRANSFORMER   CAD CELL   IGNITION   ELECTRODE   AIR TUBE   SOCKET   LEADWIRE   NOZZLE   MOUNTING   BRACKET   M7854   PLUG-IN-CELL   Fig. 1. C554A Cadmium Sulfide Flame   Detector (cad cell).   M7857   INSTALLATION   Fig. 2. Cad cell location.   When Installing this Product…   1. Read these instructions carefully. Failure to follow   them could damage the product or cause a   hazardous condition.   2. Check the ratings given in the instructions and on   the product to make sure the product is suitable for   your application.   Mounting   Direct Replacement   ³ · Remove the cell from the socket.   Insert the mounting bracket into the socket slot   (Fig. 3) as far as it will go.   NOTE: Bend the mounting bracket to fit, if   necessary.   3. Installer must be a trained, experienced service   technician.   4. After installation is complete, check out product   operation as provided in these instructions.   ®U.S. Registered Trademark   Copyright © 1996 Honeywell Inc. • All Rights Reserved   60-0164-1   Download from Www.Somanuals.com. All Manuals Search And Download.   C554A CADMIUM SULFIDE FLAME DETECTOR   SCREW   OIL LINE ADAPTER   BRACKET   CHECKOUT   To check cad cell operation, use the following procedure:   OIL LINE   TO   NOZZLE   ³ Disconnect cad cell leadwires; then start burner.   Shortly after burner starts, place a temporary jumper   between terminals F-F. Connect an ohmmeter   across cad cell leadwires; resistance should be less   than 1600 ohms.   MOUNTING   BRACKET   · » Stop burner and remove temporary jumper.   With burner off, check dark cell resistance across   cad cell leadwires. Resistance should be greater   than 20,000 ohms.   PLUG-IN   CELL   SOCKET   M7856   LEADWIRE   NOTE: If cell resistances are different than   specified, recheck wiring and location of   cell. If necessary, replace plug-in portion of   cell, Honeywell part no. 130367 Replace-   ment Cad Cell.   Fig. 5. Use oil line adapter bracket to mount   C554A on oil line.   Wiring   ¿ Reconnect cad cell leadwires. Check the   Protectorelay (burner sequencing relay) control   according to the instructions packed with the control.   Disconnect power supply before beginning wiring to   prevent electrical shock or equipment damage.   All wiring must comply with local electrical codes and   ordinances. See Fig. 6 for a typical C554A hookup to the   oil burner primary control.   SERVICE AND REPLACEMENT   Under normal operating conditions, the C554A does not   require cleaning. If a badly adjusted burner causes heavy   accumulation of dirt and soot on the cell surface, carefully   wipe the cell surface to restore full view of the oil flame.   OIL BURNER RELAY   THERMOSTAT   (24 VOLT)   T T F F If the C554A is damaged, replace the plug-in portion of the   cell. Order Honeywell part no. 130367 Replacement Cad   Cell.   C554A   CAD CELL   M7858   Fig. 6. Typical hookup for C554A to oil   burner primary control.   3 60-0164—1   Download from Www.Somanuals.com. All Manuals Search And Download.   Automation and Control Solutions   Honeywell Inc.   1985 Douglas Drive North   Golden Valley, MN 55422   Honeywell Limited-Honeywell Limitée   35 Dynamic Drive   Scarborough, Ontario   M1V 4Z9   60-0164—1 J.S. Rev. 2-96   Download from Www.Somanuals.com. All Manuals Search And Download.   |