Heat Controller Water Heater Water Source Heat Pump User Manual

WHP - Water Source Heat Pump  
Design, Installation &  
Operations Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Installation & Operations Manual  
Section 1.................................................................................... Design Guide  
Section 2...................................................................Installation and Wiring  
Section 3....................................................................................Programming  
Section 4....................................................... Start-Up and Troubleshooting  
This document is subject to change without notice.  
WattMaster Controls, Inc. assumes no responsibility  
for errors, or omissions herein.  
WHP Installation & Operations Manual - Form WM-WHP-IO-02A  
Copyright 2004 WattMaster Controls, Inc.  
All rights reserved.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1  
Table of Contents  
Conventions .....................................................................1  
General Information.........................................................2  
Water Source Heat Pump Units.......................................................................................2  
Water Source Heat Pump Systems ..................................................................................3  
WattMaster WHP Control System...................................................................................4  
WHP Controller ...........................................................................................................4  
Make Up Air Controller...............................................................................................5  
WHP Sequence of Operation ...........................................6  
HVAC Mode of Operation...............................................................................................6  
Occupied/Unoccupied Mode of Operation ......................................................................7  
Vent Mode Operation ......................................................................................................7  
Off Mode of Operation ....................................................................................................7  
HVAC Operation w/ Reversing Relay.............................................................................8  
HVAC Operation w/ Heat/Cool Relays...........................................................................9  
WHP Loop Controller Sequence of Operations .............10  
Summary........................................................................................................................10  
Pump Control.............................................................................................................10  
Pump VFD Control....................................................................................................11  
Compressor Control...................................................................................................11  
Heat Rejection Control ..................................................................................................12  
Staged Heat Rejection................................................................................................12  
Heat Addition Control ...................................................................................................12  
Staged Heat Addition.................................................................................................13  
Proportional Heat Addition........................................................................................13  
Water Temperature Alarming........................................................................................14  
Fire Alarm......................................................................................................................14  
Notes:.............................................................................16  
Table of Figures  
Figure 1-1: Typical Water Source Heat Pump..............................................................3  
Figure 1-2: Typical Water Source Heat Pump System.................................................3  
Figure 1-3: Typical WattMaster WHP System...........................................................15  
Design Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 1  
Conventions  
This document uses the following definitions throughout as a guide to the user in  
determining the nature of the information presented:  
Note: Additional information which may be helpful.  
Tip: Suggestion to make installation, set-up, and troubleshooting easier.  
Caution: Items which may cause the equipment not to function correctly but will  
not otherwise damage components.  
Warning: Errors which can result in damage to equipment and void warranties.  
Design Guide  
1-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1  
WattMaster WHP  
General Information  
Water Source Heat Pump Units  
A water source heat pump is a self-contained water-cooled packaged heating and cooling  
unit with a reversible refrigerant cycle. Its components are typically enclosed in a  
common casing, and include a tube-in-tube heat exchanger, a heating/cooling coil, a  
compressor, a fan, a reversing valve and controls.  
1-2  
Design Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 1  
Typical Water Source Heat Pump  
During the cooling mode, the tube-in-tube heat exchanger functions as a condenser and  
the coil as an evaporator. In heating mode, the tube-in-tube heat exchanger functions as  
an evaporator and the coil as a condenser. A reversing valve is installed in the refrigerant  
circuit permitting changeover from heating to cooling, and vice versa. The condenser and  
evaporator tubes are designed to accept hot and cold refrigerant liquid or gas.  
Water Source Heat Pump Systems  
The water source heat pump system is, by definition, a heat recovery system. It is best  
applied to buildings that have simultaneous cooling and heating loads. This is the case  
during winter months when the interior zones of a typical building require cooling while  
the exterior zones require heating. When a water source heat pump system is used, the  
heat rejected by the cooling units is used to warm the zones calling for heat. A water  
heater is generally used for adding heat to the condensing water during peak heating  
periods, if necessary. The system also utilizes a water cooling tower to reject the heat  
energy from the condenser water loop during periods of high cooling demand.  
Water source heat pump units can be suspended in the ceiling plenum, floor mounted  
behind walls or placed directly in the occupied space as a console unit. There are also  
rooftop and unit ventilator type water source heat pumps.  
Typical Water Source Heat Pump System  
Water source heat pump systems generally cost less to install than central built-up  
systems. They offer individual zone control with the added flexibility of being able to  
Design Guide  
1-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1  
WattMaster WHP  
accommodate changes in location and sizes as thermal zones or zone occupancy change.  
This system is often installed in ceiling plenums, which frees up valuable floor space.  
Another valuable benefit of water source heat pumps is that they can accommodate  
simultaneous calls from zones requiring heating or cooling. Depending on the climate,  
outside air may require preheat or cooling prior to being introduced to the unit. In the  
example of ceiling mounted water source heat pumps, put outside air ducts near each unit  
to improve indoor air quality.  
Normally, multiple units serve an occupied space. This gives component redundancy to  
the system so if one unit were to fail, the other units could back it up until the unit was  
repaired. The packaged design of most unit types allows quick change-out by service  
personnel so maintenance can typically be performed off site.  
As with any HVAC system, there is a negative side as the water source heat pump system  
often requires higher maintenance costs than conventional air side systems. The system  
also typically has a shorter replacement life than other systems because of continuous fan  
and compressor operation during heating and cooling modes. The system can also create  
room noise since the compressor and fan are commonly located close to the zone  
occupant. Placing units away from the occupied space and ducting the supply air to the  
zone can minimize potential noise problems.  
WattMaster WHP Control System  
The WattMaster WHP system is used to control the water loop and the individual water  
source heat pumps installed in a typical water source heat pump system. The WHP  
system is an excellent alternative over programmable thermostats. The WHP control  
system provides one central location to monitor and program all the water source heat  
pumps on the system instead of having to program each water source heat pumps  
thermostat individually. The system has many features typically not found with  
programmable thermostats such as: central operators interface, heating/cooling failure  
alarm, auxiliary alarm, and holiday scheduling, to name but a few.  
WHP Controller  
The Water Source Heat Pump Controller (WHP) is used for controlling individual water  
source heat pump units. The WHP Controller can operate stand-alone or it can be used  
with the Water Source Heat Pump Loop Controller and in this configuration shares  
common data, such as outside air temperature, proof of flow etc., over a network. A  
System Manager is connected to the WHP Controller to provide a central operators  
interface to all WHP Controllers on the network. WHP Controllers are designed with  
Room Temperature, Room Setpoint Adjust, Discharge Air Temperature, Leaving Water  
Temp or Dirty Filter Alarm and Auxiliary Lockout inputs. Relay outputs provided are;  
Fan (Continuous or Cycling), Reversing Valve-ON/OFF, Compressor-ON/OFF, Heat  
1-4  
Design Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 1  
Pump Reset and Aux. Heating or Cooling. An internal seven day schedule and holiday  
schedule functions are also built into each WHP Controller.  
With the WHP system the sometimes complex control requirements of a large water  
source heat pump system can be handled with an off the shelf controls system that has  
most of the features of a full blown building automation system but at a much lower cost.  
Included with the WHP system is a communications interface module, which allows you  
to connect a computer to the system onsite and a modem connection for remote  
monitoring.  
Prism, a Windows based software package is available at no additional charge. Some of  
Prism’s features include graphics, trend logging, and remote alarm call out capabilities.  
WHP Loop Controller  
The Water Source Heat pump Loop Controller can be supplied with the system to control  
the water loop and its various pieces of equipment. The Loop Controller can operate  
stand-alone or used with the Water Source Heat Pump Controller (WHP) and in this  
configuration communicates common data, such as outside air temperature, proof of flow  
etc., over a network. A System Manager is connected to the Loop Controller to provide a  
central operator’s interface to the Loop Controller’s setpoints and operating  
configurations. The Loop Controller is designed with inputs for Supply and Return Water  
Temperature, Outdoor Air Temperature, Loop Water Pressure Switch or 0-50 PSI Loop  
Pressure Sensor (4-20ma), Manual Reset Contact, Phase Loss Contact, Request to Run  
Relay, and Fire/Smoke Relay. Analog outputs (0-10VDC) are supplied for Pump VFD  
and Proportional Heat. Binary outputs are provided for Compressor Enable, Main Pump  
Relay, Standby Pump Relay, Alarm Contacts and (8) Relays that can be configured for  
Heat Rejection or Heat Addition.  
Make Up Air Controller  
A Make Up Air Controller, for treating 100% outdoor air, is available for use with the  
Water Source Heat Pump system. Please consult factory for more information on this  
product.  
Design Guide  
1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1  
WattMaster WHP  
WHP Sequence of  
Operation  
HVAC Mode of Operation  
There are four possible modes of operation. These are Cooling Mode, Heating Mode,  
Vent Mode, and the Off Mode. The HVAC mode of operation is calculated the same way  
in both occupied and unoccupied modes of operation.  
Off Mode  
The schedule is off and no overrides are active. There is no heating or  
cooling demand in the space. Under these conditions, all outputs will be  
off and the analog output will be set to 0.0 vdc.  
Vent Mode No heating or cooling demand exists during the occupied mode of  
operation. The fan will be on if the WHP is programmed for Constant Fan  
operation. The compressor demand request will not be sent to the Loop  
Controller. If no WHP units are sending a request, the Loop Controller  
will discontinue operation after 15 minutes.  
Cool Mode A cooling demand is generated when the space temperature rises half the  
amount of the Deadband Setpoint above the currently active Cooling  
Setpoint. The space is considered satisfied when it drops that amount  
below the Cooling Setpoint.  
Heat Mode A heating demand is generated when the space temperature drops half the  
amount of the Deadband Setpoint below the currently active Heating  
Setpoint. The space is considered satisfied when it rises that amount above  
the Heating Setpoint.  
1-6  
Design Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 1  
Occupied/Unoccupied Mode of  
Operation  
Since the WHP contains its own built in Real Time Clock, it can operate from its own  
internal scheduling system. This schedule supports two Start & Stop events per day and  
up to 14 Holiday periods. The Holidays all use the same special Holiday Start/Stop times  
programmed by the user.  
If the current operating mode is unoccupied, the WHP can accept a push-button override  
back to the occupied mode. Push-button overrides are not recognized if the current mode  
is already occupied. The push-button override duration is user programmed. If the user  
wants to extend the current override without reprogramming the Duration, they can re-  
initialize the existing programmed period by pressing the override button anytime during  
the current override. If the current override had been active for 1 hour and 45 minutes and  
the user presses the push-button again, the override will reset for another 2 hour period (if  
they programmed a 2 hour period), bringing the total override time to 3 hours and 45  
minutes. If the user wants to cancel an override before it can time-out, simply hold the  
push-button for a period of time between 3 and 10 seconds.  
The WHP calculates its current heating and cooling setpoints based on the current mode  
of operation. If the command is for unoccupied mode, the WHP adds the unoccupied  
setbacks to the occupied heating and cooling setpoints.  
Vent Mode Operation  
During occupied hours when there is no heating or cooling demand, the WHP reverts to a  
Vent Mode of operation. The fan is running and the heating and cooling outputs are held  
off.  
See the section titled HVAC Mode of Operation for a graphical description of how the  
Vent Mode is calculated.  
Off Mode of Operation  
After the schedule goes unoccupied and both heating and cooling demands go away, the  
fan stops running, all relay outputs are turned off. No outputs are allowed to activate in  
the Off Mode until a heating or cooling demand occurs. During occupied hours this  
would be the Vent Mode.  
Design Guide  
1-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1  
WattMaster WHP  
HVAC Operation w/ Reversing Relay  
If the user has configured the WHP to control a Reversing Valve and a Compressor, the  
following sequence of operation occurs during a heating or cooling demand.  
Note: If you configure the WHP to look for a proof of flow Enable signal from the  
Loop Controller then the following sequence assumes a request was made by  
the WHP during a demand condition and that the Loop Controller gave  
permission for the WHP to start its compressor. Otherwise, the WHP will  
ignore the Enable signal and operate anytime there is a heating or cooling  
demand.  
a.  
b.  
If the last mode was the opposite of the current demand mode, make sure  
the Changeover Delay has been satisfied.  
If the unit is configured to control an Isolation Valve, the valve relay is  
activated ( Relay #5 ). The Minimum Off Timer is reset to ZERO and  
must be satisfied before any further operations are allowed.  
c.  
d.  
e.  
If the current mode requires the Reversing Valve to be activated, its relay  
contact is closed and a 10 second delay is started.  
Ten seconds after the Reversing Valve is activated, the Compressor relay  
is activated.  
If the Space Temperature continues to exceed the affected setpoint by the  
full amount of Deadband and you have configured for 2 stages in the  
current mode of operation, relay #5 will activate for the second stage of  
heating and/or cooling. A second stage of either implies that no Isolation  
Valve exists!  
f.  
Once the Space Temperature has crossed back over the affected setpoint,  
stage 2 will be turned off if the unit has a stage 2.  
g.  
As the Space Temperature continues to cross back over the affected  
setpoint by half the Deadband value, the compressor will then be allowed  
to turn off if the Minimum Run Time has been satisfied.  
1-8  
Design Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 1  
HVAC Operation w/ Heat/Cool Relays  
If the user has configured the WHP to control Individual Heating and Cooling relays the  
following sequence of operation occurs during a heating or cooling demand.  
NOTE: If you configure the WHP to look for a proof of flow Enable signal from the  
Loop Controller then the following sequence assumes a request was made by  
the WHP during a demand condition and that the Loop Controller gave  
permission for the WHP to operate its heating or cooling. Otherwise, the WHP  
will ignore the Enable signal and operate anytime there is a heating or cooling  
demand.  
Once a heating or cooling demand exists, the following conditions must be met before  
any relays can be activated:  
a.  
b.  
Make sure any stages of the opposite mode are staged off.  
Verify the system has been configured for at least one stage of heating or  
cooling.  
c.  
d.  
Make sure the Minimum Cycle Time has been satisfied.  
If the last mode was the opposite demand mode, make sure the  
Changeover Delay has been satisfied.  
e.  
f.  
Check the current Minimum Off Timer to make sure this stage has been  
off long enough since the last time it was cycled on and back off.  
If there is more than 1 stage, check the Minimum Run Time from the  
previous stage to be sure it has elapsed before activating the second stage.  
g.  
h.  
Make sure the Space Temperature Demand is the full amount of Deadband  
from the setpoint before activating the second stage.  
Once the compressor or stage 2 has been turned off, a Minimum Off Time  
must be satisfied before it can stage on again. A Minimum Cycle time can  
also be utilized to limit the number of times per hour that the compressor  
can be activated. If you don’t need this limitation, set the Minimum Cycle  
Time to be shorter than the Minimum Run Time setpoint.  
i.  
If the Reversing Valve was configured to cycle with the compressor, it will  
now turn off also. It can be configured to remain active until the opposite  
mode of operation is called for to reduce wear on the valve.  
Design Guide  
1-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1  
WattMaster WHP  
WHP Loop Controller  
Sequence of Operations  
Summary  
The Water Source Heat Pump Loop Controller waits for a Request to Run signal from a  
Heat Pump or from a Binary Contact Closure. Once the request is received the Loop  
Controller activates a Pump to initiate water flow to the Heat Pumps. Once the pump is  
activated and proof of flow has been determined, a Global is broadcast to all Heat Pumps  
to enable them to go ahead and run their compressors. The main goal of the Loop  
Controller is to provide water flow and to maintain the loop water temperature by  
monitoring either the Loop Inlet or Loop Outlet temperature. If a higher temperature is  
required, Heat Addition is enabled. If the temperature needs to be lowered, Heat  
Rejection is enabled.  
Once the Loop Controller has been activated by a request, it will run for a minimum of 15  
minutes to prevent cycling on and off due to borderline requests from the Heat Pumps.  
If a Fire Alarm is detected, the Loop Controller generates a Global broadcast to all Heat  
Pumps to turn off.  
If the High Pressure option is configured, the Loop Controller can generate a Global  
broadcast to force the Heat Pumps to open their Isolation Valves to reduce loop pressure  
if the high limit has been exceeded.  
Pump Control  
If WattMaster Water Source Heat Pump Controllers are used in conjunction with the  
Loop Controller, a Global Binary signal from the attached Heat Pumps sends a Request to  
run or Enable to Run command to the Loop Controller. If the Loop Controller is used in a  
stand alone configuration, a contact closure on the AIN 2 of the Analog Expansion board  
gives the controller a request to run. When a request to run is received, the Loop  
Controller activates a pump to initiate water flow to the heat pumps. The pumps can  
either be constant flow or controlled by a VFD. If the request goes away for at least one  
minute, the request to run command is removed. If the loop controller has been running a  
minimum of 15 minutes then it can be turned off, since there is no longer a request to run.  
If the proof of flow is lost while the pumps are running, the pump is shut off immediately  
if the changeover to the Standby Pump had already been made.  
The pumps are Lead/Lag controlled based on a user definable number of hours. If one  
pump exceeds the other pumps run time by this amount, the lead is changed until that  
1-10  
Design Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 1  
pump exceeds the first pumps run time by the same amount. This keeps both pumps with  
roughly the same number of hours on each pump. Changeover occurs at the time the run  
time setpoint is exceeded. The running pump is shut off at the same time the standby  
pump is energized, this prevents any down time or alarms. The unit can be configured to  
control either the Loop Inlet temperature or the loop outlet temperature.  
A user adjustable low outdoor air temperature setting of XX degrees will allow the unit to  
run the pumps continuously for protection against freezing.  
If the pump is constant volume, and the pump has been started, it has 3 seconds to  
generate flow or the standby pump is activated. If the pump is controlled by a VFD, once  
it starts, it has 60 seconds to generate flow and if it doesn’t the standby pump is activated.  
If the standby pump fails, an alarm is generated and the Loop controller deactivates any  
active heat rejection or addition stages. At the same time an alarm is generated, we  
energize relay #5 on the Loop Controller board so that it may used to turn on a local  
alarm signal.  
Loop flow can be determined by a binary contact closure on input #3 or a 0 to 50 PSI  
pressure sensor on input #3. If a pressure sensor is used, the user can program the  
pressure setpoint that needs to be met for proof of flow.  
Pump VFD Control  
An optional Pump VFD signal can be modulated if the system is configured for  
proportional control and a pressure sensor is attached to analog input #3.  
At a user defined rate, the VFD signal is ramped up when the pressure is below  
a user defined setpoint by a user defined deadband. The signal ramps down when the  
pressure exceeds the setpoint by the deadband value. If the pressure ever exceeds the high  
pressure setpoint, an emergency override activates and begins cutting the VFD signal in  
half each time the control loop is polled by the software. This protects against run away  
over-pressurization.  
The pump relay outputs are still activated and Lead/Lagged as described above  
and the pump relay remains on until the Request signal is removed, provided it  
has been operating for at least 15 minutes.  
Compressor Control  
Anytime a pump is running and proof of flow has been established, the compressor output  
is activated.  
Design Guide  
1-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1  
WattMaster WHP  
Heat Rejection Control  
If the compressor is not running, no heat rejection can be active. If any heat rejection is  
still active when the compressor is turned off, the heat rejection will be immediately  
removed, without regard to any minimum run or off times.  
Heat rejection cannot be active at the same time as heat addition, so any heat addition is  
removed or staged off before the heat rejection can be started.  
A maximum of 8 stages of heat rejection can be controlled.  
Staged Heat Rejection  
Heat Rejection is staged up based on a different deadband level for each stage. Basically,  
if the user programmed a 2° deadband, then the first stage could activate at the setpoint,  
stage 2 would activate 2° above the setpoint, stage 3 would activate 4° above the setpoint,  
etc...  
Staging down is calculated in the same manner, except the water temperature would need  
to drop below the setpoint by the deadband amount. If stage 3 was activated at 4° above  
setpoint, it would de-activate when the temperature fell to within 2° of setpoint, stage 2  
would de-activate at setpoint and stage 1 would de-activate 2° below setpoint.  
A user defined staging up and down interval must be met before any heat rejection stages  
can be added or removed. If the selected Water Temperature is above the current staging  
level and the timer has been satisfied, an additional stage can be added, up to the  
maximum available 8 stages. If the selected Water Temperature is below the staging  
down level and the timer has been satisfied, a stage can be removed.  
Heat Addition Control  
If the compressor is not running, no heat addition can be active. If any heat addition is  
still active when the compressor is turned off, the heat addition will be immediately  
removed, without regard to any minimum run or off times.  
Heat addition cannot be active at the same time as heat rejection, so any heat rejection is  
removed or staged off before the heat addition can be started.  
A maximum of 4 stages of heat addition can be controlled or proportional heating can be  
configured, and an analog output signal will be modulated to control the heat.  
1-12  
Design Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 1  
Staged Heat Addition  
Heat Addition is staged up based on a different deadband level for each stage. Basically,  
if the user programmed a 2° deadband, then the first stage could activate at the setpoint,  
stage 2 would activate 2° below the setpoint, stage 3 would activate 4° below the setpoint,  
etc...  
Staging down is calculated in the same manner, except the water temperature would need  
to increase above the setpoint by the deadband amount. If stage 3 was activated at 4°  
below setpoint, it would de-activate when the temperature rises to within 2° of setpoint,  
stage 2 would de-activate at setpoint and stage 1 would de-activate 2° above setpoint.  
A user defined staging up and down interval must be met before any heat addition stages  
can be added or removed. If the selected Water Temperature is below the current staging  
level and the timer has been satisfied, an additional stage can be added, up to the  
maximum available 8 stages. If the selected Water Temperature is above the staging  
down level and the timer has been satisfied, a stage can be removed.  
Proportional Heat Addition  
If the Water Temperature is below the addition setpoint, a Boiler Enable relay is  
activated. If the Water Temperature rises 1° above the setpoint the Boiler Enable relay is  
de-activated.  
At a user defined rate, the analog output signal is proportionally controlled from 0.0 VDC  
at 1° above setpoint to the full 10.0 VDC signal as the water temperature drops below the  
setpoint by the user defined deadband amount. If a 5° deadband was entered, the  
maximum voltage would be reached at 4° below the setpoint and the minimum voltage  
would be set at 1° above the setpoint. Since this is strictly proportional control, at 1.5°  
below setpoint the controller would set 5.0 VDC since that would be half the deadband  
amount.  
Design Guide  
1-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1  
WattMaster WHP  
Water Temperature Alarming  
The controlling water temperature is monitored to prevent it from exceeding both a user  
defined High and Low Alarm Limit. If either limit is exceeded for a user defined length of  
time, an alarm is generated and the compressor output is de-activated. If the high limit is  
exceeded, the heat addition outputs are de-activated and if the low limit is exceeded, the  
heat rejection outputs are de-activated. The alarming and shutdown only pertains to the  
controlling water temperature. This does not affect the pump operation.  
If a external manual alarm reset button is connected between ground and input #5, All  
outputs are turned off and ALL timers are reset. This forces the loop controller to stage  
off. This reset WILL shut down the pumps and force them to restart!  
Fire Alarm  
If the Fire Alarm is activated on input #1 of the Analog Input Expansion Board (Contact  
OPENS for Alarm!) then ALL outputs and timers are reset and held off for the duration of  
the Fire Alarm signal.  
If the Fire Alarm is not required, input #1 of the Analog Input Expansion Board must  
have a shorting wire to ground to allow the equipment to operate.  
1-14  
Design Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 1  
COMPUTER  
(OPTIONAL)  
RS-485  
Comm Loop  
32K  
8K  
COMM  
RELAY  
OUTPUT  
COM  
T
Room Sensor  
with Optional  
Override & Adj.  
SHLD  
R
1-3  
OUT  
1
OUT  
485  
COMM  
RAM  
EPROM  
LD4  
2
OUT  
3
OUT  
4
REC.  
OUT  
5
CPU  
COM  
4-5  
COMM  
TEST  
12V  
ADDRESS  
ADD  
AIN  
1
AIN  
2
AIN  
3
AIN  
4
AIN  
5
GND  
GND  
AOUT  
PWR  
GND  
PRESSURE  
SENSOR  
YS101564  
24VAC  
24 VAC  
110/24 VAC  
Power Pak  
Dirty Filter Alarm  
Supply  
Air  
or Leaving Water Temp  
F
Modem  
(Optional)  
110/24 VAC  
Power Pak  
Sensor  
Typical WHP Controller Wiring  
M
R
T
R
S
D
R
D
O
H
C
D
A
A
H
S
#30  
#1  
Loop #1  
32K  
8K  
32K  
8K  
Network Loop  
RS-485  
19200 Baud  
COMM  
T
COMM  
RELAY  
OUTPUT  
RELAY  
OUTPUT  
COM  
COMM  
T
COM  
1-3  
O
M
M
SHLD  
R
SHLD  
R
1-3  
OUT  
1
OUT  
OUT  
1
OUT  
LINK  
IN  
K
LD4  
485  
COMM  
RAM  
EPROM  
2
LD4  
485  
COMM  
RAM  
EPROM  
2
OUT  
3
OUT  
4
OUT  
3
OUT  
4
REC.  
REC.  
II  
I
OUT  
5
OUT  
5
CPU  
COM  
4-5  
CPU  
COM  
4-5  
L
COMM  
TEST  
COMM  
TEST  
O
O
C
O
M
12V  
12V  
WHP  
Controllers  
ADDRESS  
ADD  
ADDRESS  
ADD  
AIN  
1
AIN  
2
AIN  
1
AIN  
2
M
O
D
P
P
AIN  
3
AIN  
3
E
M
AIN  
4
AIN  
5
AIN  
4
AIN  
5
GND  
GND  
GND  
GND  
AOUT  
AOUT  
PWR  
GND  
PWR  
GND  
PRESSURE  
SENSOR  
PRESSURE  
SENSOR  
W
AT  
C
YS101564  
YS101564  
T
M
CommLink II  
Multiple Loop  
Interface  
A
S
24VAC  
24VAC  
T
E
R
O
N
T
R
OLS  
, INC  
Local Loop  
RS-485  
9600 Baud  
MiniLink  
Loop # 1  
System Manager  
MINILINK  
1
2
T
4
8
16  
SH  
R
32  
24VAC  
GND  
T
SH  
R
#30  
#1  
24VAC  
24VAC  
Loop #2  
32K  
8K  
32K  
WED  
8K  
COMM  
COMM  
RELAY  
OUTPUT  
COM  
RELAY  
OUTPUT  
COM  
T
T
03:38PM  
SHLD  
R
1-3  
SHLD  
R
1-3  
MiniLink  
OUT  
1
OUT  
OUT  
1
OUT  
OCCUPIED  
ALARMS  
485  
COMM  
RAM  
EPROM  
485  
COMM  
RAM  
EPROM  
LD4  
2
LD4  
2
03/31/04  
NO  
OUT  
3
OUT  
4
OUT  
3
OUT  
4
REC.  
REC.  
OUT  
5
OUT  
5
CPU  
COM  
4-5  
CPU  
COM  
4-5  
WHP  
Controllers  
COMM  
TEST  
COMM  
TEST  
Loop # 2  
12V  
12V  
ADDRESS  
ADD  
ADDRESS  
ADD  
AIN  
1
AIN  
2
AIN  
1
AIN  
2
AIN  
3
AIN  
3
MINILINK  
1
2
AIN  
4
AIN  
5
AIN  
4
AIN  
5
T
4
8
16  
SH  
32  
GND  
GND  
R
GND  
GND  
AOUT  
AOUT  
PWR  
GND  
PWR  
GND  
PRESSURE  
SENSOR  
PRESSURE  
SENSOR  
24VAC  
GND  
YS101564  
YS101564  
24VAC  
24VAC  
T
SH  
R
24VAC  
Local Loop  
RS-485  
9600 Baud  
Typical Network & Local Loop Wiring  
2 Conductor Twisted Pair with Shield  
(Beldon #82760 or Equivalent)  
#30  
#1  
Loop #3  
MiniLink  
Loop # 3  
32K  
8K  
32K  
8K  
COMM  
COMM  
RELAY  
OUTPUT  
COM  
RELAY  
OUTPUT  
COM  
T
T
SHLD  
R
1-3  
SHLD  
R
1-3  
OUT  
1
OUT  
OUT  
1
OUT  
485  
COMM  
RAM  
EPROM  
485  
COMM  
RAM  
EPROM  
LD4  
2
LD4  
2
OUT  
3
OUT  
4
OUT  
3
OUT  
4
REC.  
REC.  
OUT  
5
OUT  
5
MINILINK  
1
CPU  
COM  
4-5  
CPU  
COM  
4-5  
2
T
4
COMM  
TEST  
COMM  
TEST  
8
16  
SH  
R
32  
12V  
12V  
ADDRESS  
ADD  
WHP  
ADDRESS  
ADD  
AIN  
1
AIN  
2
AIN  
1
AIN  
2
AIN  
3
AIN  
3
AIN  
4
AIN  
4
24VAC  
GND  
AIN  
5
AIN  
5
GND  
GND  
T
Controllers  
GND  
GND  
SH  
R
AOUT  
AOUT  
PWR  
GND  
PWR  
GND  
Local Loop  
RS-485  
9600 Baud  
PRESSURE  
SENSOR  
PRESSURE  
SENSOR  
YS101564  
YS101564  
24VAC  
24VAC  
24VAC  
WHP Loop  
NOTE: * Only One Outside Air Sensor  
is Required per WHP System  
Controller  
U3  
See Note #3  
Loop #4  
CX1  
CX2  
RN1  
U2  
CX4  
1
U1  
U4  
TB1  
V1  
V2  
V3  
COMM  
#29  
T
#1  
SHLD  
R
CX5  
COM1-3  
U5  
LD6  
PAL  
R1  
R2  
R3  
COMM  
RS-485  
COMM  
1
RAM  
EPROM  
MiniLink  
LD7  
PWR  
TUC-5R PLUS  
(1 MEG)  
YS101816 REV  
1
HH  
.
2
LD8  
LED1  
U6  
R4  
R5  
4RLY  
I
O
B
D
.
Y
S
1
0
1
7
9
0
C1  
LD9  
LED2  
P1  
COM4-5  
32K  
8K  
32K  
8K  
R1  
+VREF  
CX6  
TB2  
5.11V  
COMM  
COMM  
TEST POINT  
RELAY  
OUTPUT  
COM  
RELAY  
OUTPUT  
COM  
U7  
RV1  
V4  
V5  
EWDOG  
R28  
T
T
Loop # 4  
MINILINK  
VREF ADJ  
SHLD  
R
1-3  
SHLD  
R
1-3  
1
OUT  
1
OUT  
OUT  
1
OUT  
*OutsideAir  
INPUTS  
ADDRESS  
ADD  
U8  
1
2
485  
COMM  
RAM  
EPROM  
485  
COMM  
RAM  
EPROM  
+VDC  
4RLY  
I
O
B
D
.
Y
S
1
0
1
7
9
0
LD4  
2
LD4  
2
RN5  
OUT  
3
OUT  
4
OUT  
3
OUT  
4
4
NE5090NPB3192  
0PS  
AIN1  
AIN2  
AIN3  
AIN4  
AIN5  
PU1  
8
REC.  
REC.  
U9  
AIN1  
AIN2  
AIN3  
AIN4  
D6  
16  
32  
PU2  
CX10  
C7  
OUT  
5
OUT  
5
1
D7  
TOKEN  
2
PU3  
R6  
C9  
NETWORK  
T
4
8
D8  
U10  
CPU  
COM  
4-5  
CPU  
COM  
4-5  
SW1  
PU4  
16  
COMM  
TEST  
COMM  
TEST  
SH  
R
D9  
L1  
32  
Sensor  
PU5  
GND  
CX12  
D11  
12V  
12V  
D12  
R13  
GND  
GND  
C10  
PU7  
D14  
X2  
9 9 3 6  
AOUT1  
ADDRESS  
ADD  
WHP  
Controllers  
ADDRESS  
ADD  
AIN  
1
AIN  
2
AIN  
1
AIN  
2
JP1  
M C 3 4 0 6 4 A  
SC1  
4
ANALOG IN MOD I/O BD.  
YS101784  
C13  
C12  
U13  
AOUT1  
R15  
U12  
AIN  
3
AIN  
3
24VAC  
GND  
AOUT2  
AIN7  
CX14  
C14  
R19  
AIN  
4
AIN  
5
AIN  
4
AIN  
5
C16  
U14  
D15  
CX13  
U15  
C17  
GND  
PJ1  
TB4  
T
C15  
R22  
GND  
GND  
TB3  
D19  
GND  
SH  
R
GND  
GND  
R24  
R25  
C20  
CX15  
AOUT  
AOUT  
PWR  
GND  
PWR  
7 8 2 4 C T  
M
PRESSURE  
SENSOR  
PRESSURE  
SENSOR  
GND  
R26  
24VAC  
PRESSURE  
SENSOR  
YS101564  
YS101564  
EXPANSION  
T'STAT  
VR1  
VR2  
24VAC  
24VAC  
24VAC  
Loop # 4  
Local Loop  
RS-485  
9600 Baud  
Notes:  
3.) The Local Loop With The Loop Controller  
Installed Can Only Have Up To 29  
1.) 24 VAC Must Be Connected  
So That All Ground Wires  
Remain Common.  
WHP Controllers Attached As The WHP  
Loop Controller Occupies Address #30.  
2.) All Wiring To Be In Accordance  
With Local And National Electrical  
Codes and Specifications.  
4.) Systems may consist of up to 20 Local  
Loops (600 WHP Controllers). Consult  
factory for systems that exceed these quantities.  
Typical WattMaster WHP System  
Design Guide  
1-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1  
WattMaster WHP  
Notes:  
1-16  
Design Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
Table of Contents  
Tips Before Beginning Installation..................................1  
Communications Loops ...................................................3  
Communications Loop Wiring Overview....................................................4  
WHP Loop Controller .......................................................6  
WHP Loop Controller Addressing ....................................9  
Supply & Return Water Temperature Sensors..............10  
Outside Air Temperature Sensor...................................12  
CommLink II Interface...................................................13  
WHP Controller ..............................................................14  
WHP Controller Addressing ...........................................17  
MiniLink Addressing ......................................................18  
Room Sensors................................................................19  
Supply Air Temperature Sensor ....................................21  
Leaving Water Temperature Sensors............................22  
Installation and Wiring  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
Table of Figures  
Figure 2-1: System Overview........................................................................................2  
Figure 2-2: Communication Loop Wiring, Daisy-Chain Configuration .......................4  
Figure 2-3: WHP Loop Controller.................................................................................6  
Figure 2-4: WHP Loop Controller Wiring ....................................................................7  
Figure 2-5: WHP Loop Controller Address Switch Setting..........................................9  
Figure 2-6: Duct Sensor with Thermowell...................................................................10  
Figure 2-7: Strap-On Water Temperature Sensor ........................................................11  
Figure 2-8: Outside Air Temperature Sensor...............................................................12  
Figure 2-9: CommLink Interface Wiring.....................................................................14  
Figure 2-10: WHP Controller .....................................................................................14  
Figure 2-11: WHP Controller Wiring.........................................................................15  
Figure 2-12: WHP Controller Address Switch Setting...............................................17  
Figure 2-13: MiniLink Address Switch Setting.........................................................18  
Figure 2-14: Room Sensor Wiring..............................................................................19  
Figure 2-15: Room Sensor..........................................................................................20  
Figure 2-16: Supply Air Temperature Sensor..............................................................21  
Figure 2-17: Water Temperature Sensor .....................................................................22  
Figure 2-18: Water Temperature Sensor .....................................................................22  
Installation and Wiring  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 2  
Tips Before Beginning  
Installation  
Take a few moments to review the following before beginning installation of the  
WattMaster WHP System.  
Familiarize yourself with all system components and review all documentation. Pay  
special attention to “Cautions” and “Warnings” since these may keep you from  
experiencing unnecessary problems.  
Before installing controllers, be sure to tag it with its appropriate location. It is also  
best to set the controller address switches before mounting. Use the WHP Address  
Worksheet to list all WHP unit locations. This will assist you greatly when setting up  
the system.  
Be sure and install all wiring according to local, state, and national electric codes.  
Pay close attention to communication wiring since the most common mistakes are  
made in this area. Polarity is the most important rule. Make notes on your wiring  
diagrams as to which color wire you will be using on each terminal.  
When in doubt - ask! Contact your local WattMaster distributor if you have any  
questions. The only dumb questions are the ones you don’t ask.  
Remember - each electronic device contains only one puff of smoke. If you release it,  
you have voided the warranty! So please be careful and pay attention.  
Installation and Wiring  
2-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
WattMaster WHP  
COMPUTER  
(OPTIONAL)  
RS-485  
Comm Loop  
32K  
8K  
COMM  
RELAY  
OUTPUT  
COM  
T
Room Sensor  
with Optional  
Override & Adj.  
SHLD  
R
1-3  
OUT  
1
OUT  
485  
COMM  
RAM  
EPROM  
LD4  
2
OUT  
3
OUT  
4
REC.  
OUT  
5
CPU  
COM  
4-5  
COMM  
TEST  
12V  
ADDRESS  
ADD  
AIN  
1
AIN  
2
AIN  
3
AIN  
4
AIN  
5
GND  
GND  
AOUT  
PWR  
GND  
PRESSURE  
SENSOR  
YS101564  
24VAC  
24 VAC  
110/24 VAC  
Power Pak  
Dirty Filter Alarm  
Supply  
Air  
or Leaving Water Temp  
F
Modem  
(Optional)  
110/24 VAC  
Power Pak  
Sensor  
Typical WHP Controller Wiring  
M
R
T
R
S
D
R
D
O
H
C
D
A
A
H
S
#30  
#1  
Loop #1  
32K  
8K  
32K  
8K  
Network Loop  
RS-485  
19200 Baud  
COMM  
T
COMM  
RELAY  
OUTPUT  
RELAY  
OUTPUT  
COM  
COMM  
T
COM  
1-3  
O
M
M
SHLD  
R
SHLD  
R
1-3  
OUT  
1
OUT  
OUT  
1
OUT  
LINK  
IN  
K
LD4  
485  
COMM  
RAM  
EPROM  
2
LD4  
485  
COMM  
RAM  
EPROM  
2
OUT  
3
OUT  
4
OUT  
3
OUT  
4
REC.  
REC.  
II  
I
OUT  
5
OUT  
5
CPU  
COM  
4-5  
CPU  
COM  
4-5  
L
COMM  
TEST  
COMM  
TEST  
O
O
C
O
M
12V  
12V  
WHP  
Controllers  
ADDRESS  
ADD  
ADDRESS  
ADD  
AIN  
1
AIN  
2
AIN  
1
AIN  
2
M
O
D
P
P
AIN  
3
AIN  
3
E
M
AIN  
4
AIN  
5
AIN  
4
AIN  
5
GND  
GND  
GND  
GND  
AOUT  
AOUT  
PWR  
GND  
PWR  
GND  
PRESSURE  
SENSOR  
PRESSURE  
SENSOR  
W
AT  
C
YS101564  
YS101564  
T
M
CommLink II  
Multiple Loop  
Interface  
A
S
24VAC  
24VAC  
TE  
R
O
N
T
R
OL  
S, INC  
Local Loop  
RS-485  
9600 Baud  
MiniLink  
Loop # 1  
System Manager  
MINILINK  
1
2
T
4
8
16  
SH  
R
32  
24VAC  
GND  
T
SH  
R
#30  
#1  
24VAC  
24VAC  
Loop #2  
D
32K  
8K  
32K  
E
W
8K  
M
P
COMM  
COMM  
RELAY  
OUTPUT  
COM  
RELAY  
OUTPUT  
COM  
8
3
:
T
T
3
D
0
E
1-3  
1-3  
SHLD  
R
SHLD  
R
I
4
0
P
S
OUT  
1
OUT  
OUT  
1
OUT  
MiniLink  
U
M
/
C
R
1
C
A
3
O
L
485  
COMM  
RAM  
EPROM  
485  
COMM  
RAM  
EPROM  
/
LD4  
2
LD4  
2
A
3
0
OUT  
3
OUT  
4
OUT  
3
OUT  
4
O
N
REC.  
REC.  
OUT  
5
OUT  
5
CPU  
COM  
4-5  
CPU  
COM  
4-5  
WHP  
Controllers  
COMM  
TEST  
COMM  
TEST  
Loop # 2  
12V  
12V  
ADDRESS  
ADD  
ADDRESS  
ADD  
AIN  
1
AIN  
2
AIN  
1
AIN  
2
AIN  
3
AIN  
3
MINILINK  
1
2
AIN  
4
AIN  
5
AIN  
4
AIN  
5
4
8
16  
H  
32  
GND  
GND  
GND  
GND  
AOUT  
AOUT  
PWR  
GND  
PWR  
GND  
PRESSURE  
SENSOR  
PRESSURE  
SENSOR  
24VAC  
GND  
YS101564  
YS101564  
24VAC  
24VAC  
H  
24VAC  
Local Loop  
RS-485  
9600 Baud  
Typical Network & Local Loop Wiring  
2 Conductor Twisted Pair with Shield  
(Beldon #82760 or Equivalent)  
#30  
#1  
Loop #3  
MiniLink  
Loop # 3  
32K  
8K  
32K  
8K  
COMM  
COMM  
RELAY  
OUTPUT  
COM  
RELAY  
OUTPUT  
COM  
T
T
SHLD  
R
1-3  
SHLD  
R
1-3  
OUT  
1
OUT  
OUT  
1
OUT  
485  
COMM  
RAM  
EPROM  
485  
COMM  
RAM  
EPROM  
LD4  
2
LD4  
2
OUT  
3
OUT  
4
OUT  
3
OUT  
4
REC.  
REC.  
OUT  
5
OUT  
5
MINILINK  
1
CPU  
COM  
4-5  
CPU  
COM  
4-5  
2
T
4
COMM  
TEST  
COMM  
TEST  
8
16  
SH  
R
32  
12V  
12V  
ADDRESS  
ADD  
WHP  
ADDRESS  
ADD  
AIN  
1
AIN  
2
AIN  
1
AIN  
2
AIN  
3
AIN  
3
AIN  
4
AIN  
4
24VAC  
GND  
AIN  
5
AIN  
5
GND  
GND  
T
Controllers  
GND  
GND  
SH  
R
AOUT  
AOUT  
PWR  
GND  
PWR  
GND  
Local Loop  
RS-485  
9600 Baud  
PRESSURE  
SENSOR  
PRESSURE  
SENSOR  
YS101564  
YS101564  
24VAC  
24VAC  
24VAC  
WHP Loop  
NOTE: * Only One Outside Air Sensor  
is Required per WHP System  
Controller  
U3  
See Note #3  
Loop #4  
CX1  
CX2  
RN1  
U2  
CX4  
1
U1  
U4  
TB1  
V1  
V2  
V3  
COMM  
#29  
T
#1  
SHLD  
R
CX5  
COM1-3  
U5  
LD6  
PAL  
R1  
R2  
R3  
COMM  
RS-485  
COMM  
1
RAM  
EPROM  
MiniLink  
LD7  
PWR  
TUC-5R PLUS  
(1 MEG)  
YS101816 REV  
1
HH  
.
2
LD8  
LED1  
U6  
R4  
R5  
4RLY  
I
O
B
D
.
Y
S
1
0
1
7
9
0
C1  
LD9  
LED2  
P1  
COM4-5  
32K  
8K  
32K  
8K  
R1  
+VREF  
CX6  
TB2  
5.11V  
COMM  
COMM  
TEST POINT  
RELAY  
OUTPUT  
COM  
RELAY  
OUTPUT  
COM  
U7  
RV1  
V4  
V5  
EWDOG  
R28  
T
T
Loop # 4  
MINILINK  
VREF ADJ  
SHLD  
R
1-3  
SHLD  
R
1-3  
1
OUT  
1
OUT  
OUT  
1
OUT  
*OutsideAir  
INPUTS  
ADDRESS  
ADD  
U8  
1
2
485  
COMM  
RAM  
EPROM  
485  
COMM  
RAM  
EPROM  
+VDC  
4RLY  
I
O
B
D
.
Y
S
1
0
1
7
9
0
LD4  
2
LD4  
2
RN5  
OUT  
3
OUT  
4
OUT  
3
OUT  
4
4
NE5090NPB3192  
0PS  
AIN1  
AIN2  
AIN3  
AIN4  
AIN5  
PU1  
8
REC.  
REC.  
U9  
AIN1  
AIN2  
AIN3  
AIN4  
D6  
16  
32  
PU2  
CX10  
C7  
OUT  
5
OUT  
5
1
D7  
TOKEN  
2
PU3  
R6  
C9  
NETWORK  
T
4
8
D8  
U10  
CPU  
COM  
4-5  
CPU  
COM  
4-5  
SW1  
PU4  
16  
COMM  
TEST  
COMM  
TEST  
H  
D9  
L1  
32  
Sensor  
PU5  
GND  
CX12  
D11  
12V  
12V  
D12  
R13  
GND  
GND  
C10  
PU7  
D14  
X2  
9 9 3 6  
AOUT1  
ADDRESS  
ADD  
WHP  
Controllers  
ADDRESS  
ADD  
AIN  
1
AIN  
2
AIN  
1
AIN  
2
JP1  
M C 3 4 0 6 4 A  
SC1  
4
ANALOG IN MOD I/O BD.  
YS101784  
C13  
C12  
U13  
AOUT1  
R15  
U12  
AIN  
3
AIN  
3
24VAC  
GND  
AOUT2  
AIN7  
CX14  
C14  
R19  
AIN  
4
AIN  
5
AIN  
4
AIN  
5
C16  
U14  
D15  
CX13  
U15  
C17  
GND  
PJ1  
TB4  
C15  
R22  
GND  
GND  
TB3  
D19  
GND  
H  
GND  
GND  
R24  
R25  
C20  
CX15  
AOUT  
AOUT  
PWR  
GND  
PWR  
7 8 2 4 C T  
M
PRESSURE  
SENSOR  
PRESSURE  
SENSOR  
GND  
R26  
24VAC  
PRESSURE  
SENSOR  
YS101564  
YS101564  
EXPANSION  
T'STAT  
VR1  
VR2  
24VAC  
24VAC  
24VAC  
Loop # 4  
Local Loop  
RS-485  
9600 Baud  
Notes:  
3.) The Local Loop With The Loop Controller  
Installed Can Only Have Up To 29  
1.) 24 VAC Must Be Connected  
So That All Ground Wires  
Remain Common.  
WHP Controllers Attached As The WHP  
Loop Controller Occupies Address #30.  
2.) All Wiring To Be In Accordance  
With Local And National Electrical  
Codes and Specifications.  
4.) Systems may consist of up to 20 Local  
Loops (600 WHP Controllers). Consult  
factory for systems that exceed these quantities.  
System Overview  
2-2  
Installation and Wiring  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 2  
Communications Loops  
The Communications Loop is two wire shielded RS-485. The loop is best connected in  
daisy chain configuration, meaning the loop is connected from one controller to another.  
It is not necessary to sequentially address the WHP Controllers in relation to their  
location on the loop. Cable must be Belden No. 82760 or equivalent.  
Tip: Incorrect wiring of the communications loop is the most common mistake made  
during installation. Before beginning installation, write down the wire color used  
on each terminal connection and consistently maintain that color code. It is  
recommended that a continuous wire run be made between devices. Anytime a  
splice is made in the cable you increase your chance of problems.  
Caution: Make sure when you are inserting wires into the terminal blocks that  
strands of wire do not stick out and touch the next terminal. This could  
cause a short or erratic operation.  
Installation and Wiring  
2-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
WattMaster WHP  
Communications Loop Wiring Overview  
COMPUTER  
(OPTIONAL)  
POWER  
24VAC  
GND  
COMMUNICATIONS  
T
SHLD  
R
SYSTEM MANAGER POWER SUPPLY  
RS-485  
YS101716 REV.  
1
SYSTEM MANAGER  
COMM LINK II  
INTERFACE  
(SET TO MULTIPLE LOOP)  
UNIT COMES WITH  
STANDARD WALL MOUNT  
120/24 VAC POWER SUPPLY  
( MAY ALSO BE POWERED FROM 24VAC )  
Remote Link  
(OPTIONAL)  
U3  
CX1  
CX2  
R
N
1
U2  
CX4  
1
U1  
U4  
CPU  
TB1  
COMM  
V1  
V2  
V3  
T
SHLD  
R X5  
C
COM1-3  
U5  
L
D
6
PAL  
R1  
R2  
R3  
C
OMM  
R
S-48  
5
1
RA  
M
EPROM  
TUC-5  
CO  
M
M
LD  
PWR  
7
R
PLU  
(1 MEG)  
EV.  
S
1
H
H
U
6
YS1018  
1
6
R
2
L
D
8
R4  
R5  
4RLY IO BD. YS101790  
LED1  
C1  
L
D9  
LED2  
P1  
COM4-5  
R1  
+VREF  
TB2  
CX6  
5.11V  
U7  
T
E
STPOIN  
T
V4  
V5  
EWDO  
G
R
V1  
VR  
E
FA  
DJ  
R
28  
1
INPUTS  
ADDRESS  
ADD  
1
U8  
+VDC  
4RLY IO BD. YS101790  
2
4
RN  
5
N
E5090NPB3192  
PS  
AIN1  
AIN2  
AIN3  
AIN4  
AIN5  
GND  
GND  
PU1  
6
8
0
U9  
D
AIN1  
AIN2  
16  
32  
PU2  
CX10  
C7  
D
7
PU3  
TOKEN  
NETWORK  
R6  
AIN3  
AIN4  
D
8
PU4  
U10  
SW1  
D
9
PU5  
L1  
C9  
GND  
CX12  
D
11  
PU7  
14  
D
R
12  
13  
C10  
X2  
9
9
3
AOUT1  
4
D
J
P1  
A
6 4  
3
4 C 0 M  
SC  
1
ANALOG IN MOD I/O BD.  
YS101784  
C13  
C12  
U13  
AOUT1  
R15  
U12  
AOUT2  
AIN7  
CX14  
C1  
4
C1  
6
R
19  
U14  
D
15  
C
X13  
C17  
GND  
PJ1  
TB4  
U15  
C15  
TB3  
D19  
GND  
R
22  
24  
25  
R
R
C2  
0
CX15  
T
4 C  
7 8 2  
R26  
24VAC  
PRESSURE  
SENSOR  
EXPANSION  
T'STAT  
VR1  
VR2  
CPU  
NETWORK  
LOOP  
TO OTHER WHP CONTROLLERS  
TO OTHER MINILINKS  
(NETWORK TERMINALS ONLY)  
Communication Loop Wiring, Daisy-Chain Configuration  
2-4  
Installation and Wiring  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 2  
The daisy chain is the best method for running a communications loop since there is only  
one starting point and one ending point for each of the communications loops. Even  
though the daisy chain configuration is preferred, the star configuration can also be used.  
If required, a combination of the two can also be used. Remember, the best  
communication loop wiring is the one which utilizes the minimum number of ends while  
using the shortest wiring path.  
Note: The loop does not have to follow the controller address sequence.  
Caution: If the comm loop is not installed in conduit, be careful to position the  
cable away from high noise devices like fluorescent lights, transformers,  
VFD’s, etc. Conduit is not required for comm loop wiring unless  
required by local codes.  
Make sure CommLink jumper is set for “Multi”.  
Installation and Wiring  
2-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
WattMaster WHP  
WHP Loop Controller  
The WHP Loop Controller may be installed in any convenient protected location. It is  
recommended that the loop controller be mounted indoors in a secure location, that is not  
subject to extremes in temperature or moisture.  
.20 Dia.  
Typ. of 4  
6.2’’  
4.0”  
U3  
CX1  
CX2  
RN1  
U2  
CX4  
1
U1  
U4  
TB1  
COMM  
V1  
V2  
V3  
T
SHLD  
R
CX5  
COM1-3  
U5  
LD6  
PAL  
R1  
R2  
R3  
COMM  
RS-485  
COMM  
1
RAM  
EPROM  
LD7  
PWR  
TUC-5R PLUS  
(1 MEG)  
YS101816 REV.  
1
HH  
2
U6  
LD8  
LED1  
R4  
R5  
C1  
LD9  
LED2  
P1  
COM4-5  
R1  
+VREF  
TB2  
CX6  
5.11V  
TEST POINT  
U7  
RV1  
V4  
V5  
EWDOG  
R28  
VREF ADJ  
7.3”  
1
INPUTS  
ADDRESS  
ADD  
8.29”  
8.96”  
9.5”  
6.6”  
U8  
1
2
+VDC  
AIN1  
AIN2  
AIN3  
AIN4  
AIN5  
RN5  
4
NE5090NPB3192  
0PS  
PU1  
8
U9  
D6  
16  
32  
CX10  
PU2  
C7  
D7  
PU3  
TOKEN  
R6  
C9  
NETWORK  
D8  
PU4  
U10  
SW1  
D9  
PU5  
L1  
CX12  
D11  
PU7  
D12  
R13  
X2  
C10  
9 9 3  
GND  
GND  
3 4 C 0 M 6 4 A  
D14  
JP1  
SC1  
C13  
C12  
U13  
R15  
AOUT1  
AOUT2  
AIN7  
U12  
CX14  
C14  
R19  
C16  
U14  
CX13  
U15  
D15  
C20  
C17  
TB4  
GND  
C15  
R22  
D19  
TB3  
PJ1  
GND  
R24  
R25  
CX15  
T
7 8 2 4 C  
R26  
24VAC  
PRESSURE  
SENSOR  
VR1  
EXPANSION  
VR2  
T'STAT  
2.12”  
0.28”  
4.24”  
WHP Loop Controller Main Board  
WHP Loop Controller Expansion Board  
WHP Loop Controller  
2-6  
Installation and Wiring  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 2  
WHP Loop Controller Expansion Board  
Connect To Next WHP Controller  
And/Or MiniLink On Local Loop  
U3  
CX1  
CX2  
RN1  
U2  
CX4  
1
U1  
U4  
TB1  
COMM  
V1  
V2  
V3  
Local Loop RS-485  
9600 Baud  
T
SHLD  
R (24 VAC By Others)  
Compressor Enable  
Outside Air  
Temp. Sensor  
R
CX5  
COM1-3  
U5  
LD6  
PAL  
R1  
R2  
R3  
R1  
R2  
R3  
COMM  
RS-485  
COMM  
1
RAM  
EPROM  
LD7  
PWR  
TUC-5R PLUS  
(1 MEG)  
YS101816 REV.  
1
HH  
Main Pump  
2
U6  
LD8  
LED1  
R4  
R5  
C1  
Standby Pump  
LD9  
LED2  
P1  
COM4-5  
R1  
+VREF  
TB2  
CX6  
5.11V  
N.C. Pilot Duty Relays  
(By Others)  
TEST POINT  
U7  
RV1  
Return Water  
V4  
V5  
EWDOG  
R28  
Temp Sensor  
VREF ADJ  
1
INPUTS  
Alarm Indicator  
ADDRESS  
ADD  
U8  
1
2
+VDC  
RN5  
4
NE5090NPB3192  
0PS  
PU1  
AIN1  
AIN2  
AIN3  
AIN4  
AIN5  
8
U9  
D6  
16  
32  
CX10  
PU2  
D7  
Supply Water  
Temp Sensor  
C7  
TOKEN  
R6  
C9  
NETWORK  
PU3  
U10  
SW1  
PU4  
D9  
PU5  
L1  
CX12  
D11  
PU7  
D12  
R13  
X2  
C10  
9 9 3  
GND  
GND  
6 4 A 3 4 C 0 M  
D14  
U13  
JP1  
SC1  
See Note 4  
C13  
C12  
R15  
AOUT1  
AOUT2  
AIN7  
U12  
CX14  
C14  
R19  
C16  
Required VA For Transformer  
Loop Controller = 8VA Min.  
U14  
CX13  
U15  
D15  
C20  
C17  
TB4  
GND  
C15  
R22  
D19  
TB3  
PJ1  
GND  
GND  
R24  
R25  
Line Voltage  
See Note 1  
CX15  
Proof of  
Flow  
T
4 C 7 8 2  
24VAC  
R26  
24VAC  
PRESSURE  
SENSOR  
Optional Pressure  
Transmitter  
EXPANSION  
VR1  
VR2  
T'STAT  
Manual  
Reset  
Phase  
Loss  
N.C. Pilot Duty Relays  
(By Others)  
-
R4  
R5  
Heating/Cooling #1  
Heating/Cooling #2  
Pump VFD  
+
R6  
Heating/Cooling #3  
R7  
Heating/Cooling #4  
24 VAC  
-
YS101790  
4RLY IO BD.  
Optional  
Modulating Heat  
+
R8  
R9  
Heating/Cooling #1  
Heating/Cooling #2  
Notes:  
1.)24 VAC Must Be Connected So  
That All Ground Wires Remain  
Common.  
R10  
Heating/Cooling #3  
R11  
Heating/Cooling #4  
24 VAC  
Fire Alarm Contact (N.C.)(See Note 5)  
Request to Run Contact (N.O.)  
YS101790  
4RLY IO BD.  
AIN1  
AIN2  
AIN3  
AIN4  
2.)All Wiring To Be In Accordance  
With Local And National Electrical  
Codes And Specifications.  
GND  
AOUT1  
3.)All Communication Wiring To Be  
2 Conductor Twisted Pair With  
Shield. Use Belden #82760 Or  
Equivalent.  
4 ANALOG IN MOD I/O BD.  
YS101784  
Relay Contacts  
(By Others)  
4.)When a Water Pressure Transmitter  
Is Used, a 250 Ohm Resistor is  
Installed Between AIN3 & GND and  
The Pull Up Resistor PU3 is  
Removed.  
5.)If a Fire Alarm Contact is Not  
Connected to AIN1 on The Analog  
Expansion Board, Then a Jumper  
Must Installed Between AIN1 and  
GND.  
WHP Loop Controller Expansion Board  
WHP Loop Controller Wiring  
Installation and Wiring  
2-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
WattMaster WHP  
Warning: Polarity is very important when connecting power to the controllers!  
The grounded side of the control transformer must be connected to  
the terminal labeled GND on the controller. If a single transformer is  
used to power more than one controller you must connect GND-to-  
GND and 24VAC-to-24VAC on each controller. Failure to  
observe polarity will result in damage to one or  
more components in your system.  
The WHP Loop Controller requires the following electrical connections:  
-24VAC Supply Voltage.................................................... 2 Conductors (18 Ga. Min.)  
-Communications Loop .......2 Conductor twisted pair with shield (18 Ga. Minimum)  
(Belden #82760, WattMaster Cable or equivalent)  
-Supply Water Temperature Sensor...................................(24 ga. Min.) 2 Conductors  
-Return Water Temperature Sensor....................................(24 ga. Min.) 2 Conductors  
-Outside Air Temperature Sensor.......................................(24 ga. Min.) 2 Conductors  
-Loop Pressure Sensor (Optional)........................................(24 ga. Min) 2 Conductors  
-Fire/Smoke Alarm Contacts ..............................................(24 ga. Min.) 2 Conductors  
-Loop Pressure Switch.........................................................(24 ga. Min) 2 Conductors  
-Manual Reset Switch..........................................................(24 ga. Min) 2 Conductors  
-Request to Run Contacts ....................................................(24 ga. Min) 2 Conductors  
-Analog Outputs...................................................................(24 ga. Min) 2 Conductors  
-Binary Outputs....................................................................(24 ga. Min) 2 Conductors  
Tip: After making all electrical connections it is advised to unplug all terminal blocks  
on the WHP Loop Controller until you are ready to begin the checkout  
procedure. This may help to prevent damage if wiring errors occur elsewhere in  
the system during installation or start-up.  
2-8  
Installation and Wiring  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 2  
WHP Loop Controller  
Addressing  
The WHP Loop Controller must be set for address #30. See address setting instructions  
for the WHP Loop Controller that follow. A maximum of 29 WHP Controllers are  
allowed on the loop that contains the WHP Loop Controller. All other loops may have 30  
WHP Controllers.  
ADDRESS  
ADD  
This Switch Should Be  
In The OFF Position  
As Shown  
1
2
4
8
16  
32  
TOKEN  
NETWORK  
Note:  
The Power To The Controller Must Be Removed And  
Reconnected After Changing The Address Switch  
Settings In Order For Any Changes To Take Effect.  
Controller  
Address Switch  
Address Switch Must Be Set For  
Address 30 As Shown  
Caution  
Disconnect All Communication Loop Wiring From The  
Controller Before Removing Power From The Controller.  
Reconnect Power And Then Reconnect Communication  
Loop Wiring.  
INPUTS  
ADD  
ADDRESS  
+VDC  
1
2
RN5  
PU1  
AIN1  
AIN2  
AIN3  
AIN4  
AIN5  
4
8
16  
D6  
CX10  
PU2  
C7  
32  
D7  
PU3  
R6  
TOKEN  
NETWORK  
D8  
PU4  
U10  
SW1  
D9  
PU5  
L1  
C9  
CX12  
D11  
D12  
R13  
X2  
PU7  
GND  
GND  
C10  
D14  
JP1  
SC1  
C13  
C16  
U13  
C12  
R15  
AOUT1  
U12  
AOUT2  
AIN7  
CX14  
C14  
R19  
U14  
CX13  
U15  
D15  
C20  
C17  
TB4  
GND  
C15  
R22  
D19  
TB3  
PJ1  
GND  
R24  
R25  
CX15  
R26  
24VAC  
PRESSURE  
SENSOR  
VR1  
EXPANSION  
VR2  
WHP Loop Controller Address Switch Setting  
Installation and Wiring  
2-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
WattMaster WHP  
Supply & Return Water  
Temperature Sensors  
Sensors for monitoring supply and return water temperature are available in two main  
types, fluid immersion temperature sensors (See Figure 2-6) and strap-on sensors (See  
Figure 2-7). Both are 0-10000 ohm thermistor type sensors. The fluid immersion sensor  
generally has better accuracy than the strap-on type but either is suitable for typical water  
source heat pump temperature requirements. The fluid immersion type sensor requires  
that a thermowell be installed in the pipe and the strap-on type, as its name implies,  
simply straps around the outside of the pipe. The fluid immersion sensor requires that the  
pipe be at least 4” in diameter in order to accept the thermowell. The strap-on type sensor  
is adjustable for use on 1/2” to 6” or larger diameter pipe.  
The fluid immersion sensor is provided with a 4” long stainless steel thermowell. It has  
½” MPT external threads and ½” FPT internal threads. A ½” FPT fitting to accept the  
thermowell must be provided by others in the pipe to be monitored, for connection of the  
thermowell. The thermowell is screwed into the ½” FPT fitting installed by others in the  
pipe and the sensor probe is then screwed into the ½” FPT fitting on the thermowell.  
Leads Are Non-polarized.  
Butt Splice Leads To 24 Gauge  
Wire Minimum. Connect Leads  
To "Analog In" And "Ground"  
At Controller.  
OE230 Duct Sensor  
The OE230 Duct Sensor Threads Into The OE291 Stainless  
Steel Thermowell. The OE291 Thermowell Threads Into A 1/2”  
OE291 Stainless Steel Thermowell  
FPT Elbow or Tee in the Water Piping of the Water Coil  
Where You Wish to Measure the Water Temperature. The  
Pipe must be a minimum of 4” Diameter or an Extended Tee  
and Bushing Configuration Must be Used to Accommodate the  
Length of the Thermowell Assembly.  
Duct Sensor with Thermowell  
2-10  
Installation and Wiring  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 2  
The strap-on type sensor has a brass housing that senses the water temperature through  
contact with the exterior surface of the pipe. The sensor should be mounted in contact  
with the underside of the pipe in order to insure accurate temperature readings. The  
sensor assembly is secured to the pipe by using the supplied wire ties to wrap and secure  
the sensor to the pipe. Thermal conductive compound is also supplied to insure a good  
thermal connection with the pipe. The sensors are supplied with 3 foot long wire leads.  
Supply Or Return  
Wire Tire  
Water Pipe.  
(Supplied)  
Sensing Element  
(Supplied)  
Thermal Mastic Strip  
(Supplied)  
Strap-On Water Temperature Sensor  
Installation and Wiring  
2-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
WattMaster WHP  
Outside Air Temperature  
Sensor  
The outside air sensor must be located where it will not be affected by direct sun or heat  
producing equipment. Mounting under the eve of a roof is often a good choice.  
Caution: Complaints of inaccurate outside sensor readings are very common and  
can almost always be shown to be the result of poor sensor location.  
Note: All temperature sensors supplied with the system utilize the same thermistor  
type sensing element. For troubleshooting sensor problems refer to the  
TEMPERATURE SENSOR RESISTANCE CHART at the end of Section 4.  
Cover  
Mounting  
Screw - Typ.  
Closure Plug  
Gasketed Cover  
2.70”  
2.30”  
3.00”  
0.21" Dia. x 0.73  
Lg. Slot - Typ.  
Mounting Tab  
& Screws - Typ.  
Mounting Tab  
& Screw - Typ.  
Closure Plug  
Sensor Tube  
Back View  
Front View  
Side View  
Outside Air Temperature Sensor  
2-12  
Installation and Wiring  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 2  
CommLink II Interface  
The CommLink II Interface provides for communications between the MiniLink  
communication interfaces installed on the system. The CommLink II is required for  
proper communications, even if a PC is not used. Locate the CommLink II near the  
computer or modem if they are installed on the system. The cable connections between  
the CommLink II and the computer or modem should be kept to less than twenty-five  
feet. The CommLink II comes complete with computer and modem cables, and a plug-in  
power supply.  
COMPUTER  
(OPTIONAL)  
POWER  
24VAC  
GND  
COMMUNICATIONS  
T
SHLD  
R
SYSTEM MANAGER POWER SUPPLY  
RS-485  
YS101716 REV.  
1
SYSTEM MANAGER  
COMM LINK II  
INTERFACE  
(MULTIPLE LOOP)  
UNIT COMES WITH  
STANDARD WALL MOUNT  
120/24 VAC POWER SUPPLY  
( MAY ALSO BE POWERED FROM 24VAC )  
Remote Link  
(OPTIONAL)  
U3  
CX 1  
CX2  
RN1  
U2  
CX4  
1
U1  
U4  
CPU  
T
B
1
V1  
V2  
COMM  
T
V3  
SHLD  
R
CX  
5
COM1-3  
U5  
LD6  
PA L  
R1  
R2  
R3  
CO  
M
M
RS-485  
CO  
1
RA  
M
EPROM  
MM  
LD7  
PW  
T
UC-5R PLUS  
(1ME  
S101816 RE  
1
HH  
R
G)  
Y
V
.
2
LD8  
LED1  
U6  
R4  
R5  
4RLY IO BD. YS101790  
C1  
LD9  
LED2  
P1  
COM4-5  
R1  
+VREF  
TB2  
CX6  
5.11V  
NT  
U7  
T
E
ST  
PO  
I
V4  
V5  
EWDO  
G
RV  
V RE  
1
F
ADJ  
R28  
1
I
NPUTS  
ADDRESS  
ADD  
U8  
1
+VDC  
4RLY IO BD. YS101790  
2
4
RN5  
NE5090NPB3192  
0PS  
AIN1  
AIN2  
AIN3  
AIN4  
AIN5  
P
U1  
8
U9  
AIN1  
AIN2  
AIN3  
AIN4  
D6  
16  
32  
PU2  
CX10  
C7  
D7  
PU3  
TO  
KE  
N
R6  
NE T  
W
O
R K  
D8  
U10  
SW1  
PU4  
D9  
PU5  
L1  
C9  
GND  
CX12  
D1  
PU7  
1
D12  
R13  
C10  
X2  
9 9 3  
AOUT1  
GND  
GND  
D14  
J
P 1  
3 4  
C
0
M
6 4 A  
SC1  
4
ANALOG IN MOD I/O BD.  
YS101784  
C13  
C12  
U13  
AOUT1  
R15  
U12  
AOUT2  
AIN7  
CX14  
C14  
R19  
C16  
U14  
CX13  
D15  
C20  
C17  
GND  
TB4  
U15  
C15  
R22  
T
B3  
P
J 1  
D19  
GND  
R24  
R25  
CX15  
T
7 8 2 4 C  
R26  
24VAC  
PRESSURE  
SENSOR  
EXPANSION  
T'STAT  
VR1  
VR2  
CPU  
NETWORK  
LOOP  
TO OTHER WHP CONTROLLERS  
TO OTHER MINILINKS  
(NETWORK TERMINALS ONLY)  
CommLink Interface Wiring  
Installation and Wiring  
2-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
WattMaster WHP  
WHP Controller  
The WHP Controller may be installed in any convenient protected location. Observe the  
recommended environmental limitations for the WHP Controller when selecting a  
installation location. The environmental limitations are a temperature range of 10°F to  
149°F, and a maximum operating humidity of 90% RH non-condensing.  
The WHP Controller may be mounted by fastening to a flat surface through the mounting  
plate. The unit is mounted by four (4) screws in the corners. Select the correct screws or  
other fasteners for the type of mounting material being utilized.  
RAM SIZE  
SELECT JUMPER  
COMMUNICATIONS  
DRIVER CHIP  
RAM  
EPROM  
PIN 1  
INDICATION  
PAL  
24 VAC Common for Inputs 1 - 3  
Fan-On/Off  
RS-485  
COMMUNICATIONS  
LOOP  
Rev. Valve-On/Off (Heat 1)  
Compressor-On/Off (Heat 2)  
Heat Pump Reset (Cool 1)  
Aux. Heating or Cooling (Cool 2)  
24 VAC Common for Inputs 1 - 3  
COMMUNICATIONS  
LED  
ADDRESS SWITCH  
( ADDRESS 18 SHOWN )  
CPU  
ANALOG INPUTS  
Space Sensor  
DIAGNOSTIC BLINK  
CODE LED  
Slide Adjust  
Supply Air Temp  
Leaving Water  
Temp or  
Dirty Filter  
REAL TIME  
CLOCK CHIP  
Lockout  
POWER LED  
24VAC  
POWER  
INPUT  
STATIC PRESSURE  
SENSOR INPUT  
Mounting Backplate  
WHP Controller  
2-14  
Installation and Wiring  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 2  
All Comm Loop Wiring Is  
Straight Thru  
T
SH  
R
T
SH  
R
T
SH  
R
T
SH  
R
Connect To  
Next Controller  
And/Or  
MiniLink On  
WHP Controller  
Water Source Heat Pump  
Unit Connections  
Local Loop  
RS-485  
9600 Baud  
E
COMM  
RELAY  
OUTPUTS  
COM  
R
A
P
R
O
M
T
M
Room Sensor  
1-3  
24VAC  
Fan-On/Off  
SHLD  
OUT  
1
R
OUT  
Rev. Valve-On/Off  
Compressor-On/Off  
2
LD4  
TMP  
OUT  
W
A
R
M
E
3
OUT  
REC.  
Heat Pump Reset  
Aux. Heating Or Cooling  
4
GND  
AUX  
OUT  
R
NORMAL  
C
5
O
COM  
4-5  
O
L
OVR  
Connection To  
COMM  
TEST  
E
R
AUX Terminal is Reqd  
Only When Sensor  
Is Specified With  
12V  
AIN  
1
ADDRESS  
ADD  
AIN  
2
Diagnostic Blink Code LED  
Slide Adjust Option  
AIN  
3
Discharge  
Air Temp.  
Sensor  
AIN  
4
AIN  
5
Required VA For Transformer  
Each WHP Controller = 10VA MIN.  
GND  
Mount In HVAC  
Unit Supply  
Air Duct  
GND  
PWR  
GND  
AOUT  
GND  
24VAC  
24VAC  
Dirty Filter  
Alarm Contact  
Thermowell  
Or Surface Mount  
Temp Sensor  
CAUTION!  
WHP CONTROLLERS  
Lockout  
MUST HAVE ADDRESS SWITCHES  
SET BETWEEN 1 AND 30  
(Leaving Water Temp)  
(UP TO 30 UNITS PER LOCAL LOOP)  
EXCEPT ON THE LOOP WITH THE  
LOOP CONTROLLER CONNECTED.  
THE LOOP CONTROLLER ADDRESS  
IS 30, WHICH ALLOWS FOR ONLY  
29 WHP CONTROLLERS ON THIS  
LOCAL LOOP.  
Optional Features  
WHP Controller Wiring  
Warning: Polarity is very important when connecting power to the controllers!  
The grounded side of the control transformer must be connected to  
the terminal labeled GND on the WHP Controller. If a single  
transformer is used to power more than one WHP Controller you  
must connect GND-to-GND and 24VAC-to-24VAC on each WHP  
Controller. Failure to observe polarity will result in  
damage to one or more components in your  
system.  
Warning: Use extreme care not to damage any of the electronic components  
while mounting the backplate. Mark the holes then remove the WHP  
Controller from the backplate before drilling.  
Do not allow metal shavings to fall onto the circuit boards.  
Installation and Wiring  
2-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
WattMaster WHP  
The WHP Controller requires the following electrical connections:  
18 Gauge minimum unless otherwise noted.  
-24VAC Supply Voltage........................................................................... 2 Conductors  
-Communications Loop ...................................... 2 Conductor twisted pair with shield  
(WattMaster Cable, Belden #82760 or equivalent)  
-Discharge Air Temperature Sensor ..................................(24 ga. Min.) 2 Conductors  
-Room Air Temperature Sensor...........(24 ga. Min.) 2 Conductors for standard sensor  
3 Conductors for sensors with setpoint adjustment  
-Outside Air Temperature Sensor.......................................(24 ga. Min.) 2 Conductors  
-WHP Unit Control Wiring .........................................................(24 ga.Min.) 24 VAC  
Fan- ON/OFF  
Rev Valve-ON/OFF  
Compressor-ON/OFF  
Heat Pump Reset  
Aux. Heating or Cooling  
Tip: After making all electrical connections it is advised to unplug all terminal blocks  
on the WHP Controller until you are ready to begin the checkout procedure. This  
may help to prevent damage if wiring errors occur elsewhere in the system  
during installation or start-up.  
2-16  
Installation and Wiring  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 2  
WHP Controller  
Addressing  
NOTE:  
IGNORE ANY MARKINGS  
OR NUMBERS ON THE SWITCH  
USE THE CHART!  
To determine the boards address,  
add the values of all the switches  
which are toggled down in the  
direction of the arrow  
NOTE:  
ADDRESS 30 CANNOT BE USED  
ON THE LOOP THAT HAS THE WHP LOOP  
CONTROLLER ATTACHED. ADDRESS 30  
ON THAT LOOP IS RESERVED FOR THE  
WHP LOOP CONTROLLER.  
CAUTION:  
YOU MUST POWER DOWN THE CONTROLLER  
AFTER CHANGING THE ADDRESS SWITCHES  
IN ORDER FOR ANY CHANGES TO TAKE EFFECT.  
ALWAYS REMOVE THE COMMUNICATIONS LOOP  
PRIOR TO DISCONNECTING POWER. RECONNECT  
POWER AND THEN RECONNECT THE COMMUNICATIONS  
LOOP TO THE CONTROLLER.  
WHP Controller Address Switch Setting  
Installation and Wiring  
2-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
WattMaster WHP  
MiniLink Addressing  
MiniLink Communications Interface  
Connect To Next  
MiniLink And/Or  
CommLink On  
Network Loop  
Network Loop  
RS-485  
ADD  
19200 Baud  
1
2
T
NETWORK  
4
8
16  
SH  
32  
R
OFF  
>
All Communication Loop  
Wiring Is Straight Through  
24VAC  
Line Voltage  
T
SH  
R
T
SH  
R
T
SH  
R
T
SH  
R
24VAC  
GND  
T
SH  
R
Required VA For Transformer  
Local Loop  
RS-485  
9600 Baud  
MiniLink = 6VA Min.  
See Note 1.  
Connect To Next  
Controller or  
System Manager  
ADD  
1
Caution!  
2
4
8
16  
32  
The MiniLinks Must Have Address Switches Set Between 1  
And 30 (Up To 30 MiniLinks Are Allowed Per WHP System  
System). The MiniLinks Should Be Addressed In  
Consecutive Order Starting With Address #1. Address #1  
Must Be Present On The Loop For The System To Function.  
These Switches Must Be  
In The OFF Position  
As Shown  
Note:  
The Power To The MiniLink Must Be Removed And  
Reconnected After Changing The Address Switch  
Settings In Order For Any Changes To Take Effect.  
Caution:  
Disconnect All Communication Loop Wiring  
From The MiniLink Before Removing Power  
From The MiniLink. Reconnect Power And Then  
Reconnect Communication Loop Wiring.  
MiniLink  
Address Switch  
Notes:  
1.)24 VAC Must Be Connected So  
That All Ground Wires Remain  
Common.  
Address Switch Shown Is  
Set For Address 1  
Address Switch Shown Is  
Set For Address 4  
The Address For Each MiniLink  
2.)All Wiring To Be In Accordance  
With Local And National Electrical  
Codes And Specifications.  
Must Be Unique To The Other MiniLinks  
On The Network Loop. Loop #1 MiniLink  
Should Be Addressed As #1  
Loop #2 MiniLink Should Be Addressed  
As #2 Etc..  
3.) All Communication Wiring To Be  
2 Conductor Twisted Pair With  
Shield. Use Belden #82760 Or  
Equivalent.  
MiniLink Address Switch Setting  
2-18  
Installation and Wiring  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 2  
Room Sensors  
The room sensor uses a patented flush mount design to isolate the temperature sensing  
element from the housing which mounts flush with the wall surface.  
Room sensors should be located on an inside wall away from direct sunlight or heat  
producing equipment such as computers, copiers, etc. Such devices can adversely affect  
the accuracy of the sensor.  
Although the sensor eliminates most of the effects of thermal coupling to the walls, try to  
avoid walls which retain large amounts of thermal energy (such as marble or steel). Walls  
containing either cold or warm air currents should also be avoided whenever possible.  
Avoid locating the sensor in dead air areas of a room. This will result in slow response to  
temperature changes in the space.  
Mount the sensor approximately 50-60 inches from the floor for best results.  
The room sensor is designed to mounted vertically in a standard 2 by 4 inch electrical  
box. The sensor may be mounted directly into the drywall where electrical codes do not  
require low voltage wiring to be enclosed in conduit. See enclosed sheet for dimensional  
and installation data.  
Tip: Be careful when cutting the hole for the sensor or the plastic bezel of the sensor  
may not completely cover the opening.  
WHP CONTROLLER  
ROOM SENSOR WITH OVERRIDE  
AND ADJUSTABLE SETPOINT  
TMP  
W
A
R
M
E
R
GND  
AUX  
C
O
O
L
OVR  
E
R
ADJUSTABLE  
SETPOINT  
OVERRIDE  
ONLY REQUIRED WHEN  
USING ADJUSTABLE  
SETPOINT  
Room Sensor Wiring  
Installation and Wiring  
2-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
WattMaster WHP  
Connect the terminal labeled GND on the zone sensor to the terminal labeled GND on the  
WHP Controller Analog Input terminal block. Connect the terminal labeled TMP on the  
zone sensor to the terminal labeled AIN 1 on the WHP Controller Analog Input terminal  
block. If the zone sensor has a setpoint adjust slider, then connect the sensor terminal  
labeled AUX to the WHP Controller AIN 2 terminal block.  
Tip: If sensors must be installed on walls which are solid and cannot be penetrated,  
surface mounted boxes and raceway can be purchased from your local electrical  
distributor.  
2.00“  
2.75“  
0.88“  
TMP  
GND  
AUX  
OUT  
W
A
R
M
E
R
C
O
O
L
E
R
0.25“  
Wall Cut-Out Dimensions  
When Sensor Is To Be  
Mounted Without  
Handy Box (By Others)  
Room Sensor  
2-20  
Installation and Wiring  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 2  
Supply Air Temperature  
Sensor  
The supply air temperature sensor should be located in the duct, as close to the rooftop  
unit discharge as possible for best response.  
Locate the sensor in the center of the widest part of the duct. Use the supplied template  
and a 5/16" drill to make a hole for the sensor. Install the gasket over the probe and  
mount securely to the duct using the supplied sheet metal screws. Be sure the gasket is  
compressed to provide an air tight seal.  
For best accuracy, apply insulation on the outside of the duct, over the sensor. This will  
help prevent thermal gradients from affecting the sensor.  
Leads Are Non-polarized.  
Butt Splice Leads To 24 Gauge  
Wire Minimum. Connect Leads  
To "Analog In" And "Ground"  
At Controller.  
4.0"  
Thread  
3/4"  
Together  
5-1/2" (OE230)  
11-1/2" (OE231)  
Mounting Plate  
1/4" Hex Head Sheet Metal Screws  
Mounting Plate  
Gasket  
Adhesive Backed Drill Guide  
Mounting Template  
Duct Work  
Drill 5/16" Hole In Ductwork For Probe  
Supply Air Temperature Sensor  
Installation and Wiring  
2-21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
WattMaster WHP  
Leaving Water  
Temperature Sensors  
The leaving water temperature sensor (optional) when used should be located on the  
leaving water piping close to the water source heat pump unit. Either a thermowell type or  
a surface mount sensor may be used depending on job requirements.  
Leads Are Non-polarized.  
Butt Splice Leads To 24 Gauge  
Wire Minimum. Connect Leads  
To "Analog In" And "Ground"  
At Controller.  
OE230 Duct Sensor  
The OE230 Duct Sensor Threads Into The OE291 Stainless  
Steel Thermowell. The OE291 Thermowell Threads Into A 1/2”  
FPT Elbow or Tee in the Water Piping of the Water Coil  
Where You Wish to Measure the Water Temperature. The  
Pipe must be a minimum of 4” Diameter or an Extended Tee  
and Bushing Configuration Must be Used to Accommodate the  
Length of the Thermowell Assembly.  
OE291 Stainless Steel Thermowell  
Water Temperature Sensor  
Supply Or Return  
Water Pipe.  
Wire Tire  
(Supplied)  
Sensing Element  
(Supplied)  
Thermal Mastic Strip  
(Supplied)  
Water Temperature Sensor  
2-22  
Installation and Wiring  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
Table of Contents  
LCD/Keypad Operations...................................................1  
System Manager Layout...................................................................................................2  
Keypad Functions ............................................................................................................2  
System Manager LED Indicators .....................................................................................3  
Heat Pump Status Screens..............................................4  
View Status Only.............................................................................................................4  
View Alarms ....................................................................................................................8  
Menu Setpoints ................................................................................................................9  
Set Time & Date ..............................................................9  
New Passcodes..............................................................11  
Rebuild Alarm Map.........................................................12  
Heat Pump Setpoints.....................................................13  
Heat Pump Setpoint Menu.............................................................................................13  
1) WHP Setpoints ..........................................................................................................13  
2) WHP Schedules.........................................................................................................20  
Holidays .........................................................................................................................21  
3) Reset Pumps ..............................................................................................................22  
Loop Controller Status ..................................................23  
Loop Controller Status Menu.........................................................................................23  
Loop Controller Status Screens ....................................23  
Loop Controller Setpoints .............................................27  
Loop Controller Setpoint Menu.....................................................................................27  
Notes:.............................................................................32  
Programming  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 3  
LCD/Keypad Operations  
Main Screen  
The Water Source Heat Pump System Manager is the operator’s interface to the status  
and setpoints of any WattMaster Water Source Heat Pump (WHP) component on your  
communications loop. With the System Manager, you can view any temperature or output  
condition and change any setpoint to fine tune the operations of the total system. All  
keypad operations are simple and straight-forward, utilizing non-cryptic plain English  
messages. The System Manager automatically detects the type of unit that has been  
selected, and displays the appropriate status and setpoint screens. The attractive plastic  
case of the System Manager allows for placement in any area of your building.  
The remainder of this document will lead the user through the system menus and keypad  
operation.  
All user functions are accessed by pressing the Menu button. Once the button is pressed,  
the Main User Menu is displayed.  
Programming  
3-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
WattMaster WHP  
System Manager Layout  
Keypad Functions  
The System Manager keypad is labeled either numerically or as to actual function for that  
key. Below is a summary of the labeled keys and their functions.  
This key is used to gain access to the first menu, and the user will be  
notified, on the LCD, if any subsequent use of the key will be  
required for further access.  
The ESCape key allows the user to abort what they are doing or exit  
back to previous menus. Also, anytime you want to leave the system  
unattended you should press the ESC key until the Main Screen  
appears.  
MENU  
ESC  
If you make a mistake while entering setpoint data, you can clear the  
bad data from the display by pressing the Clear key.  
Use the Enter key to close out a data entry. It can also be used to  
advance to the next field or screen.  
If entering a setpoint that requires a decimal point, press this key  
where the decimal is located while entering the value.  
If you need to enter a negative value, you must press the Minus key  
before entering the digits for that value.  
CLEAR  
ENTER  
DEC  
MINUS  
Use these keys to step forward or backward through Status Screens or  
Setpoint Data Fields.  
UP/DOWN  
Arrows  
If the screen prompts you to use these keys, it is used normally to  
toggle modes of operation.  
LEFT/RIGHT  
Arrows  
3-2  
Programming  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 3  
System Manager LED Indicators  
There are two LED indicators located on the right hand side of the System Manager.  
The top LED indicates an Alarm condition if the Manager detects an alarm condition  
while polling the system.  
The bottom LED is active during actual communications or packet transfers. This LED  
will normally “flicker” and not remain on constantly.  
Main User Menu  
1) View Status Only  
2) View Alarms  
For quick access to an  
individual heat pump or the  
loop controller, select this menu  
item. No passcode is required to  
access the status of any unit  
installed on your system.  
If the System Manager has been  
configured for Alarm Polling,  
the user can select this item to  
get a list of unit addresses that  
are currently in alarm. If an  
alarm exists, the Alarm LED  
will be active on the right side  
of the panel.  
MENU) Setpoints  
ESC) Main Screen  
If you are a Level 2 user, all system  
setpoints are available to you.  
These setpoints are accessed via  
this Menu button.  
When you have finished viewing  
the system you can exit this menu  
and return to the Main Screen by  
pressing the ESC button.  
Programming  
3-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
WattMaster WHP  
Heat Pump Status  
Screens  
View Status Only  
By selecting the View Status Only menu item, you can  
access any heat pump or the loop controller and read all  
available temperatures, outputs, and operating conditions  
for the selected unit. No passcode is required to access  
these status screens, and no setpoints are available to the  
user from these screens. To access a unit, enter the Unit ID  
you wish to view. The Unit ID is actually two separate  
numbers, combined into one value. The first part of the  
number contains the Loop Address at which the zone is  
located. The second part of the number contains the actual  
Board Address.  
EXAMPLE: You would like to view the 3rd heat pump  
on the 5th loop. Enter 503 as the Unit ID  
You would like to view the 12th heat pump  
on the 24th loop. Enter 2412 as the Unit ID  
3-4  
Programming  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 3  
If you selected menu item #1 View Status Only and you entered the Unit ID of an  
installed WHP Controller, the following Status Screens are available.  
Status Screen #1  
Line 2 -  
Line 3 -  
Current Zone Temperature  
°
°
°
°
Current Cooling Setpoint ( CSP ) and Heating  
Setpoint ( HSP )  
Line 4 -  
Effect of optional Sensor Slide Adjustment on the  
current operating setpoints.  
Status Screen #2  
Line 2 -  
Line 3 -  
°
°
°
Current Supply Air Temperature  
Current Leaving Water Temperature if Sensor is  
installed.  
Line 4 -  
Current Outdoor Air Temperature.  
Programming  
3-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
WattMaster WHP  
Status Screen #3  
Line 2 -  
Current Operating Status  
Unoccupied Mode  
Occupied Mode  
Pushbutton Override  
Forced Occupied  
Forced Unoccupied  
Forced Fan Only Mode  
Line 3 -  
Line 4 -  
Current Fan Status  
Fan Start Delay!  
ON  
OFF  
Current Enable Status from Loop  
Controller  
Operations Disabled  
Operations Enabled  
Status Screen #4  
Line 2 -  
Line 3 -  
Line 4 -  
Current Compressor ON/OFF Status  
Current Reversing Valve ON/OFF Status  
Current Status of Relay #5. Operation  
depends on how the user configures this  
output.  
Status Screen #5  
Line 2 -  
Current HVAC Operating Mode  
Neutral Mode  
Cooling Mode  
Heating Mode  
Line 3 -  
Line 4 -  
Reserved for future option.  
Reserved for future option.  
3-6  
Programming  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 3  
Status Screen #6  
Bad Space Sensor  
Hi Space Temp Alarm!  
Lo Space Temp Alarm!  
Space Temp Sensor OK  
Dirty Filter Alarm  
Filter OK  
Line 2 -  
Line 3 -  
Line 4 -  
Cooling Failure!  
Heating Failure!  
Note: If no alarms exist, then the screen displays the message shown for No Alarms!  
If ANY alarm exists then the three lines display one of the messages shown  
above.  
The Cooling Failure and Heating Failure alarms are generated as follows:  
As the unit enters the cooling mode, the current Supply Air Temperature reading  
is stored in memory. After 10 minutes, if the temperature hasn’t changed by 5°F a  
Cooling Failure alarm is generated.  
A Heating Failure is generated in the same manner, only during the heating mode  
instead of the cooling mode.  
The Hi Space Temp and Lo Space Temp Alarms are generated as follows:  
If the space temperature gets 5°F above the cooling setpoint, a Hi Space Temp  
Alarm is generated. If the space temperature gets 5°F below the heating setpoint,  
a Lo Space Temp Alarm is generated.  
Programming  
3-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
WattMaster WHP  
View Alarms  
Alarm Address Locations  
The System Manager can be programmed to poll all the  
units on your heat pump system for alarm information. This  
allows the centrally located System Manager to display an  
Alarm Indicator whenever an alarm condition exists  
anywhere on your system. The actual alarms are not  
displayed on this screen, only the Unit ID where the alarm  
is located. The example screen shows that a unit at location  
118 has experienced an alarm condition. This alarm may or  
may not be current, as the System Manager latches the  
condition. This makes it possible to determine if any  
intermittent alarm conditions have occured. To find out  
what the alarm is, if it is still current, access the status  
screens for the Unit IDs that are displayed on the SYSTEM  
ALARM STATUS screens.  
Alarm Clearing  
If all the alarm conditions have been corrected at the  
individual units, you can clear these alarms from the  
System Manager on the following screen. Use the  
Left/Right arrow keys to select the YES/NO response  
desired. If you clear the alarms, but some still exist, the  
System Manager will show an alarm indication, when the  
affected unit is polled again.  
3-8  
Programming  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 3  
Menu Setpoints  
Full Setpoint Access  
If you selected the Menu key from the first menu screen you  
can access all setpoints available from any unit on your system.  
You must be a Level 2 user to access these setpoints. If you  
haven’t already been asked to enter the passcode, you will be  
asked before the Full Setpoint Access menu is displayed. This  
prevents the casual user from being able to affect the operation  
of your heat pump system.  
Set Time & Date  
The System Manager has its own built in Real Time Clock. It broadcasts this time once a  
day, at midnight, to synchronize all of the WHPs on your system. Although the times are  
displayed on the Main Screen in a standard 12-hour format, they are programmed using  
the 24-hour Military format. Once the time has been entered, it is also broadcast  
immediately to all other units on the system. That means that you only need to program  
the System Manager time to set the Real Time Clocks for all units on your system. In  
order for the System Manager to broadcast the time and date to all controllers, they must  
be powered up and communicating.  
Programming Time  
Day  
- Enter the Day of the Week (0 to 6) with  
Sunday = 0  
Hours (Hr)  
Minutes  
- Enter Hours in 24-Hour Military Format  
(1700 = 5:00 PM)  
- Enter the Minutes (0 to 59)  
Programming  
3-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
WattMaster WHP  
Programming Date  
Month  
- Enter the Month (1 to 12)  
Day  
- Enter the Day of the Month (1 to 31)  
Year  
- Enter the current Year with 2 digits (00  
to 99)  
Daylight Savings Adjustments  
If your area of the country requires Daylight Savings changes,  
you can enable the System Manager to automatically reset its  
own clock during the Daylight Savings changeover. If you  
enable this operation, it knows to changeover the first Sunday  
in April and then switch back the last Sunday in October. No  
other programming is required for this function.  
Use the Left or Right arrow keys to toggle the second line of  
the display between Adjustments Enabled and Adjustments  
Disabled.  
3-10  
Programming  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 3  
New Passcodes  
Programming Passcodes  
The System Manager has two levels of passcode.  
Level 1 users are limited to viewing Setpoints and Alarms only.  
Level 2 users have complete system access. Any status or  
setpoint field can be read or reset from WHP System Manager.  
The default passcode is “1111” for level 1 and “2222” for level  
2. If you need to change these defaults you can enter any 4 digit  
number between 1000 and 9999.  
If you “forget” the passcode you programmed, you can still  
access the system with a built in backdoor code. This backdoor  
code is “9288” and is not programmable. It is not recommended  
that you give out this backdoor code since it would allow the  
user access without regard to the standard programmable  
passcode that most operators should be using.  
The actual digits in your passcodes are never displayed. An "X"  
is used as a place holder for each digit entered. Passcodes must  
always be four digits in length.  
Programming  
3-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
WattMaster WHP  
Rebuild Alarm Map  
Rebuilding Screens  
If you would like the LED Alarm Indicator to function on the  
front of your System Manager, you must enable Alarm Polling  
by building an Alarm Map. This map keeps track of which  
units exist on your communications loop so the System  
Manager will poll only those units. That means you will need  
to rebuild this map anytime units are added or removed from  
your system. It also means you can disable alarm polling. To  
do this, disconnect the RS-485 communications plug from the  
back of your Comm Link II. Then, select the Rebuild Alarm  
Map menu. The System Manager will not find any units to poll  
for alarms since none are connected. This is useful during  
building startup, when you don't want nuisance alarms  
bothering you.  
The screen will display each address it is testing and if a unit is  
found at that address. If you don't want to wait for the System  
Manager to check for all 30 loops, you can press the ESC key  
as soon as the number of loops on your system are exceeded  
and the test will conclude. All units found up to that point will  
be saved in memory.  
The System Manager does not rebuild this map  
automatically on powerup! You must do this manually. This  
rebuild need only be performed one time, when all units are up  
and running. It is not a regular requirement. As mentioned  
above, only when the number of units connected changes  
should the alarm map be rebuilt.  
3-12  
Programming  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 3  
Heat Pump Setpoints  
Heat Pump Setpoint Menu  
From the main menu screen select MENU on the keypad,  
select MENU again for Setpoints. Then select “Access Units”  
(keypad #2) and finally enter the loop and zone number for the  
desired unit.  
As the screen above shows, there are three areas of  
programming available for each WHP Controller. Menu item  
#1 accesses all the standard temperature and configuration  
settings for the heat pump. Menu item #2 accesses the week  
schedule and holiday programming for the individual unit.  
Menu item #3 can be selected to force the heat pump to  
manually reset in the case of an operating problem.  
1) WHP Setpoints  
Setpoint Screen #1  
The Occupied Heating and Cooling Setpoints are  
programmed on this screen. The setpoints must be at least one  
degree apart. If you try to enter the same value or to cross the  
cooling and heating setpoints, the value you enter will not be  
accepted.  
°
°
Cooling Setpt  
Heating Setpt  
50°F  
50°F  
74°F  
72°F  
90°F  
90°F  
Programming  
3-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
WattMaster WHP  
Setpoint Screen #2  
The Unoccupied Heating and Cooling Setbacks are programmed  
on this screen. The Cooling SetUp is added to the Occupied  
Cooling Setpt to create the Unoccupied Cooling Setpoint. The  
Heating SetBack is added to the Occupied Heating Setpt to  
create the Unoccupied Heating Setpt.  
°
°
Cool SetUp  
1°F  
10°F  
30°F  
Heat SetBack  
-1°F  
-10°F  
-30°F  
Setpoint Screen #3  
If the Space Temperature Sensor has the optional slide  
adjustment, then the Slide Effect is the maximum amount of  
change that it can have on the Heating and Cooling Setpoint and  
it is programmed here.  
°
°
The SP Deadband is divided in half across the current heating  
and cooling setpoint, and is used in staging the heating and  
cooling on or off.  
If you have an override pushbutton on the space sensor, the OV  
Duration is the length of time the unit will be in the occupied  
mode after pushing the button  
Slide Effect  
SP Deadband  
OV Duration  
0°F  
0°F  
0.0 Hr  
3°F  
1°F  
1.0 Hr  
5°F  
20°F  
8.0 Hr  
Setpoint Screen #4  
If the Heat Pump is configured to operate with a Reversing  
Valve, relay #5 can be configured as a second stage for either  
heating or cooling or both. If the Heat Pump is configured for  
individual heating and cooling, this determines how many of  
each stage there are.  
Cooling Stages  
Heating Stages  
0
0
1
1
2
2
3-14  
Programming  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 3  
Setpoint Screen #5  
The Min Run Time determines how long the compressor  
must remain on once it has been activated. The Min Off Time  
determines how long the compressor must remain off once it  
is de-activated. The Min Cycle time determines how many  
times per hour the compressor can be started. If you entered  
10 minutes, the compressor could start a maximum of 6 times  
in a one hour period.  
Min Run Time  
Min Off Time  
Min Cycle  
0 Min  
0 Min  
0 Min  
1 Min  
6 Min  
12 Min  
20 Min  
20 Min  
60 Min  
Setpoint Screen #6  
To prevent rapid cycling between heating and cooling modes,  
you can enter a time period that must be satisfied before the  
changeover can occur.  
Changeover Delay  
1 Min  
30 Min  
60 Min  
Setpoint Screen #7  
Normally you would want to have an Enable Signal that gave  
assurance of water flow before you activate the heat pumps  
compressor. If you need to operate without this enable signal,  
use the arrow keys to select the NO ENABLE REQUIRED  
message. Otherwise, select the LOOP FLOW REQUIRED  
message so that the signal must be present for the compressor  
to run.  
Programming  
3-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
WattMaster WHP  
Setpoint Screen #8  
If your heat pump uses a reversing valve to determine the  
heating or cooling mode of operation, select the message  
R/VALVE & COMPRESSOR. If you are controlling  
separate stages of heating and cooling select the  
INDIVIDUAL STAGING message.  
Setpoint Screen #9  
If you have configured the system to use the reversing valve,  
you must select which mode requires it to be active. Select  
either the COOLING MODE or the HEATING MODE  
message.  
Setpoint Screen #10  
If you have configured the system to use the reversing valve,  
you can also set it to cycle on and off with the compressor,  
(CYCLES w/COMPRESSOR) or, to remain on once it is  
activated, and stay on until the opposite mode or unoccupied  
mode is selected (RUNS CONTINUOUS MODE). The  
valve always activates 10 seconds before the compressor  
starts no matter which method you select.  
3-16  
Programming  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 3  
Setpoint Screen #11  
If your system is configured to use the reversing valve and  
you only have one stage of heating and cooling, that last  
relay becomes available for other uses. The AUXILIARY  
RELAY MODE can be used to operate the relay manually  
from the Prism computer front end program. If you select  
ISOLATION VALVE MODE, the relay activates anytime  
the compressor is called for or whenever the Loop Controller  
sends an override command to activate and reduce loop  
pressure.  
If the relay needs to follow an external week schedule, select  
the AUXILIARY RELAY MODE and then see the Aux  
Relay #5 Schedule assignment screen.  
Setpoint Screen #12  
You can program the fan to run continuously during the  
occupied mode, (RUNS CONTINUOUS MODE) or you  
can program it to cycle on and off with the compressor  
during both the occupied and the unoccupied mode of  
operation.  
(CYCLES W/COMPRESSOR)  
Setpoint Screen #13  
If you configured relay #5 as an Auxiliary Relay, you can  
also program it to follow an external schedule command.  
You must have an OSS Optimal Start Scheduler installed  
somewhere on you communications loop to provide the  
external schedule you select here.  
Programming  
3-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
WattMaster WHP  
Setpoint Screen #14  
The Heat Pump Controller can use the internal time clock for  
a setting an occupied schedule, for this the setpoint will be 0.  
It can also be programmed to follow an external schedule  
command. You must have an OSS Optimal Start Scheduler  
installed somewhere on you communications loop to provide  
the external schedule, and you select the schedule number  
here.  
Setpoint Screen #15  
If you entered the same starting time for several heat pumps,  
they are prevented from all starting their fans at the same  
time by a Startup Delay Period that is determined by their  
address switch setting. The address is multiplied by the  
number of seconds you enter on this screen, up to a  
maximum of 60 seconds per address. This is the time period  
the fan must wait before it starts when the schedule goes  
occupied.  
If you entered 5 seconds and the address was 10 then the fan  
would start 5 x 10 or 50 seconds after the schedule goes  
occupied.  
Setpoint Screen #16  
An Energy Demand Limit sequence is programmed into all  
heat pump controllers. It is currently an option that is not  
supported by a controller that can send the Demand Limit  
signal to initiate a limiting condition. It is included here for  
future use only.  
°
Max Effect  
0°F  
3°F  
30°F  
3-18  
Programming  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 3  
Setpoint Screen #17  
This setpoint is to shut the heating off when the supply air  
temperature is too warm. When the supply air temperature is  
above this setpoint, it will prevent the second stage of heat  
from coming on.  
°
Max Effect  
30°F  
60°F  
200°F  
Setpoint Screen #18  
The Thermister Type III Sensor readings can be calibrated.  
Enter Positive values to increase the reading or Negative  
values to decrease the reading. If no sensor is attached, the  
calibration offset will still allow a value to be input and read  
for diagnostic purposes.  
°
°°  
°°  
°°  
°°  
°°  
Space Sensor  
Supply Air Sensor SAT  
Water Sensor  
SPC  
-100.0°F  
-100.0°F  
0.0°F  
0.0°F  
0.0°F  
+100.0°F  
+100.0°F  
+100.0°F  
WAT -100.0°F  
Setpoint Screen #19  
Select if you want the notification LED on the front of the  
System manager to illuminate when an alarm occurs. If  
Enabled is selected, any WHP alarm will cause the Alarm  
LED on the front panel to light up. If Disable is selected, the  
Alarm LED will not light up but the alarm will still show up in  
the Status screen.  
Note: You must do a Rebuild Alarm Map after all controllers are powered up and  
communicating.  
Programming  
3-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
WattMaster WHP  
2) WHP Schedules  
The Water Source Heat Pump controllers contain their own built in scheduling capability  
for calculating Occupied/Unoccupied periods. Select item #2 from Schedules menu to  
access the following schedule programming menu.  
Schedule Menu  
Week Schedule Programming  
Event #1  
There are two Start / Stop events available per day.  
The first line is the start time for event #1 and the next line is  
the stop time for event #1.  
The screens will step through the Start Time and then the Stop  
Time for each day of the week. You can quit at any point in the  
process by pressing the "ESC" key.  
Event #2  
If no second event is required, simply leave a ZERO for both  
the start and stop times on the event #2 screens.  
All times are in 24-hour format, so 5:00 PM would be entered  
as 1700.  
If both the Start and Stop Times are ZERO, the schedule is in a  
Continuous OFF mode.  
If both the Start and Stop Times are 2359, the schedule is in a  
Continuous ON mode.  
3-20  
Programming  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 3  
Holidays  
Holiday Day Selection  
There are 14 Holiday periods available, organized as a Start Day / Stop Day event. If the  
Holiday only lasts one day, enter the same date for the Start & Stop days. There is no  
limit to the duration or number of days that can be included in one holiday, other than it  
cannot extend past December 31st. If you have a holiday that crosses the end of year  
border, you will need to use two holiday periods to accomplish this event.  
The screens will step through the 14 possible holidays, one  
at a time. Line 2 shows which holiday is currently being  
programmed.  
Line 3 shows which event, the Start Day or Stop Day, is  
currently being programmed.  
Remember to combine the month and day into a single four  
digit value.  
EXAMPLE: 0704 = July 4th  
1225 = December 25th  
Holiday Start / Stop Times  
The 14 holidays all use the same Holiday Start / Stop  
time. The start/stop times are programmed back on the  
Week Schedule screens. The holiday schedule screen  
appears after the Saturday schedule screen, as you are  
stepping through the days of the week.  
Note: Normally there is no schedule in the Loop Controller device. It simply looks at  
all the Water Source Heat Pumps for a request to run signal. Scheduling is  
maintained separately in each Water Source Heat Pump. If you want to be able  
to schedule all Water Source Heat Pumps on and off at the same time, you can  
input a schedule on the Loop Controller and it will broadcast that schedule to all  
WHPs.  
Programming  
3-21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
WattMaster WHP  
3) Reset Pumps  
If one of your heat pumps has tripped off, it can be manually  
reset from the following screen. You will have entered the  
Unit ID to access the WHP Menu screen, so that is the unit  
that will receive this reset command. If you don’t want to  
send the command, select the Disabled message with the  
arrow keys. If you do want to send the command, select the  
Enabled message with the arrow keys and then press the  
Enter button. This command will automatically clear itself  
when the WHP detects it and performs the reset.  
There are two methods of resetting:  
1. Relay #4, on the WHP will activate with the reset  
command and can be wired to provide the reset  
action.  
2. The compressor relay will be cycled off. On  
newer heat pumps, this is all that is required to  
reset the operation.  
3-22  
Programming  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 3  
Loop Controller Status  
Loop Controller Status Menu  
From the main menu screen select MENU on the keypad. Then select “View Status  
Only” (keypad #1) and finally enter the loop and zone number for the desired unit.  
As the screen above shows, there are two areas of status available for the Loop  
Controller. Menu item #1 accesses all the status screens for the Loop Controller. Menu  
item #2 accesses the alarms for the Loop Controller. “Menu” can be selected to access the  
Setpoints screens.  
Loop Controller Status  
Screens  
If you selected menu item #1, View Status Only, and you entered the Unit ID of the Loop  
Controller, the following Status Screens are available.  
Status Screen #1  
Line 2 -  
Current operating Mode:  
°
°
OCCUPIED  
UNOCCUPIED  
Line 3 -  
Line 4 -  
Current Return Water Temperature  
Current Supply Water Temperature  
Programming  
3-23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
WattMaster WHP  
Status Screen #2  
Line 2 -  
Current operating Mode:  
No Call To Run  
ACTIVE CALL TO RUN  
FREEZE PROTECTION!  
Line 3 -  
Line 4 -  
Current Water Flow Status:  
Water Flow Proved!  
No Flow Detected  
Current Request to Operate Status:  
LOOP ENABLED  
LOOP DISABLED  
Status Screen #3  
Line 2 -  
Line 3 -  
LEAD Pump #1 On or Off  
STANDBY Pump #2 On or Off  
Status Screen #4  
Cool/Heat Stage #1 On/Off  
Cool/Heat Stage #2 On/Off  
Line 1 -  
Line 2 -  
Cool/Heat Stage #3 On/Off  
Cool /Heat Stage #4 On/Off  
Line 3 -  
Line 4 -  
3-24  
Programming  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 3  
Status Screen #5  
Cool/Heat Stage #5 On/Off  
Cool/Heat Stage #6 On/Off  
Line 1 -  
Line 2 -  
Cool/Heat Stage #7 On/Off  
Cool/Heat Stage #8 On/Off  
Line 3 -  
Line 4 -  
Status Screen #6  
Line 2 -  
Line 3 -  
Line 4 -  
Current Loop Water Pressure  
Current Variable Speed Pump Voltage Signal  
Current Proportional Heat Voltage Signal  
Note: If none of the above options have been configured, then the values in this status  
screen will be 0.  
Programming  
3-25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
WattMaster WHP  
Status Screen #7  
Line 2 -  
Line 3 -  
Pump Failure or Blank Line  
Hi Control Water Temp  
Lo Control Water Temp  
Fire/Smoke Alarm  
Line 4 -  
Phase Shutdown  
Note: If no alarms exist, then the screen displays the message shown for No Alarms! If  
ANY alarm exists, then the three lines display one of the messages shown above.  
The Fire/Smoke Alarm is generated as follows:  
If the NC (normally closed) contact from a firestat or smoke detector that is wired  
between GND and AIN1, on the Analog Input expansion board, opens, the  
Fire/Smoke Alarm is generated.  
The Phase Shutdown Alarm is generated as follows:  
If the NO (normally open) contact from a phase monitoring device, that is wired  
between GND and AIN7 is made, the Phase Shutdown Alarm is generated.  
Status Screen #8  
Line 2 -  
Line 3 -  
Line 4 -  
Message Only  
Pump #1 Hours and Minutes Run Time  
Pump #2 Hours and Minutes Run Time  
3-26  
Programming  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 3  
Loop Controller Setpoints  
Loop Controller Setpoint Menu  
Setpoint Screen #1  
If the controlling water temperature rises above this Setpoint,  
the Heat Rejection or Cooling Stages begin to stage on. As the  
temperature continues to rise above the Setpoint by the  
°
°
Deadband amount, an additional stage is added. Each  
additional stage can only activate if the temperature rises above  
the Setpoint by the number of active stages times the deadband  
value.  
Example: There are 2 stages on, a 3° deadband and the setpoint  
is 79°  
2 x 3° + 79° = 85° before stage 3 can activate  
Setpoint  
Stage Deadband  
50°F  
1°F  
79°F  
3°F  
99°F  
10°F  
Setpoint Screen #2  
The Staging Delay period must also be satisfied before an  
additional stage of cooling or heat rejection can be activated.  
The maximum number of heat rejection stages are programmed  
on this screen also.  
Stage Delay  
1 Minute  
1 Minute  
60 Minutes  
Programming  
3-27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
WattMaster WHP  
Setpoint Screen #3  
If the controlling water temperature drops below this Setpoint,  
the Heat Addition or Boilers begin to stage on. As the  
temperature continues to drop below the Setpoint by the  
Deadband amount, an additional stage is added. Each  
additional stage can only activate if the temperature drops  
below the Setpoint by the number of active stages times the  
deadband value.  
°
°
Example: There are 2 stages on, a 3° deadband and the setpoint  
is 79°  
79° - 2 x 3° = 73° before stage 3 can activate  
Setpoint  
Stage Deadband  
50°F  
1°F  
76°F  
3°F  
99°F  
10°F  
Setpoint Screen #4  
The Staging Delay period must also be satisfied before an  
additional boiler or heat addition stage can be activated.  
The maximum number of heat addition stages are programmed  
on this screen also.  
Stage Delay  
1 Minute  
1 Minute  
60 Minutes  
Setpoint Screen #5  
If the outdoor air temperature drops below this setpoint, the  
pump will be energized to prevent the water lines from  
freezing.  
°
Setpoint  
-50°F  
40°F  
50°F  
3-28  
Programming  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 3  
Setpoint Screen #6  
If the controlling water temperature rises above the Water Hi  
Limit setpoint, all heat addition will be removed and one  
stage of heat rejection will be activated. If the controlling  
water temperature drops below the Water Lo Limit setpoint,  
all heat rejection stages will be removed and one heat  
addition stage will be activated. An alarm will be generated if  
it remains out of limits for the Alarm Delay Time.  
°
°
Water Hi Limit  
Water Lo Limit  
Alarm Delay  
0°F  
0°F  
0 Min  
120°F  
0°F  
30 Min  
120°F  
120°F  
120 Min  
Setpoint Screen #7  
The Loop Controller can modulate a Variable Speed Pump.  
Select the PRESSURE option in place of the CONSTANT  
option for variable speed pumping.  
The water flow proving can be accomplished by a differential  
pressure contact closure or an actual pressure sensor. If you  
select Variable Speed Pumping, you must select the  
PRESSURE option in place of the CONTACT option for  
Flow Proof.  
Setpoint Screen #8  
There are two methods of Heat Addition control, STEP  
HEATING CONTROL or PROPORTIONAL HEATING  
The Loop Controller can be configured to maintain Return  
Water Temperature ( RETURN WATER CONTROL ) or  
the Supply Water Temperature ( SUPPLY WATER  
CONTROL )  
Programming  
3-29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
WattMaster WHP  
Setpoint Screen #9  
The two pumps will switch after this programmed amount of  
time so that each pump accumulates roughly the same  
number of run time hours. If a pump is currently running and  
this time period is exceeded, the changeover will occur as  
soon as pump run time exceeds the setpoint. The current  
pump will shut off and the standby pump will start at the  
same time.  
Changeover  
1 Hour  
40 Hours  
240 Hours  
Setpoint Screen #10  
If you attached a Pressure Sensor for proof of flow instead of a  
differential pressure contact closure for proof of flow, the  
controlling pressure is programmed on this screen. This  
Setpoint represents the amount of pressure that you set to prove  
water flow exists in the system. Otherwise, this screen will not  
appear.  
Flow PR. SP  
0
5 PSI  
50 PSI  
Setpoint Screen #11  
If you configured the system for Variable Speed Pumping with  
a Pressure Sensor for proof of flow, the controlling pressure,  
deadband and control adjust time period are programmed on  
this screen. Otherwise, this screen will not appear.  
Pressure SP  
SP Deadband  
Adjust Time  
1 PSI  
1 PSI  
40 PSI  
2 PSI  
50 PSI  
50 PSI  
0.1 Seconds 1.0 Seconds 25 Seconds  
3-30  
Programming  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 3  
Setpoint Screen #12  
If you configured the system for Variable Speed Pumping with a  
Pressure Sensor for proof of flow, the Loop Controller can send  
a signal to all the Heat Pumps to open their Isolation Valves  
whenever a Hi Limit Pressure is exceeded. If the Heat Pumps do  
not control an Isolation Valve, then the only reaction is to  
reduce the variable speed pump voltage signal.  
Hi Limit  
1 PSI  
50 PSI  
50 PSI  
Setpoint Screens #13  
The Thermister Type III Sensor readings can be calibrated.  
Enter a Positive value to increase the reading or a Negative  
value to decrease the reading. If no sensor is attached, the  
calibration offset will still allow a value to be input and read for  
diagnostic purposes.  
°
°°  
°°  
°°  
°°  
°°  
Return Water  
Supply Water  
Outdoor Air  
RWT  
SWT  
OAT  
-10.0°F  
-10.0°F  
-10.0°F  
0.0°F  
0.0°F  
0.0°F  
+10.0°F  
+10.0°F  
+10.0°F  
Note: Due to memory limitations in the Loop Controller, the maximum amount of  
calibration offset is 10.0°F.  
Setpoint Screen #14  
Alarms can be configured to light the LED on the front of the  
System Manager by setting Alarms to Enabled, if you do not  
wish to report alarms, select Disabled.  
Setpoint Screen #15  
Use this screen to configure the relays on the expansion board  
for heat ADDITION, REJECTION or NOT USED. All 8  
relays come up one at a time.  
Programming  
3-31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
WattMaster WHP  
Notes:  
3-32  
Programming  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4  
Table of Contents  
1.0 Communications Overview........................................1  
1.1 How It Works...........................................................................................................1  
1.2 WattMaster WHP System........................................................................................1  
2.0 WHP Controller Overview..........................................4  
2.1 How It Works...........................................................................................................4  
2.1.1 Initialization .....................................................................................................4  
2.1.2 Operating Summary.........................................................................................4  
2.2 Becoming Familiar with the WHP Controller .........................................................5  
2.2.1 24 VAC Power Connector ...............................................................................5  
2.2.2 Analog Inputs...................................................................................................6  
2.2.3 Analog Output Description..............................................................................6  
2.2.4 Relay Output Descriptions...............................................................................6  
2.2.5 RS-485 Communications Connector ...............................................................7  
2.2.6 WHP Controller Wiring...................................................................................8  
3.0 Loop Controller Overview.........................................9  
3.1 How It Works...........................................................................................................9  
3.1.1 Initialization .....................................................................................................9  
3.1.2 Operating Summary.........................................................................................9  
3.2 Loop Controller Inputs & Outputs.........................................................................10  
3.2.1 Analog Inputs.................................................................................................10  
3.2.2 Analog Output................................................................................................10  
3.2.3 Binary Output.................................................................................................11  
3.2.4 Relay Expansion Board - Outputs..................................................................11  
3.2.5 Analog Input Expansion Board......................................................................11  
3.2.6 Comm Connector - Communications ............................................................12  
3.2.7 Power Terminal..............................................................................................12  
4.0 Start-Up....................................................................14  
4.1 Blink Codes for WHP Controllers.........................................................................14  
4.2 Blink Codes for Loop Controllers..........................................................................15  
4.3 Communications Checklist...................................................................................15  
4.4 Installation and Commissioning Information ........................................................16  
4.5 Setting Address Switches.......................................................................................19  
4.5.1 Setting the MiniLink Address Switch............................................................19  
4.5.2 Loop Controller Addressing...........................................................................20  
4.5.3 WHP Controller Addressing..........................................................................20  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4  
5.0 Troubleshooting ...................................................... 21  
5.1 General Troubleshooting........................................................................................21  
5.1.1 Communications Troubleshooting Checklist.................................................21  
5.1.2 General Troubleshooting Checklist ...............................................................22  
5.2 Alarms......................................................................................................................23  
5.3 Checking Comm. Loop Voltages.............................................................................24  
5.3.1 Checking the CommLink II Network Loop ...................................................24  
5.3.2 Checking the Comm Loop at the CommLink II ............................................25  
5.3.3 Checking the CommLink II Driver................................................................26  
5.3.4 Checking the MiniLink Network Loop..........................................................27  
5.3.5 Checking the MiniLink Network Driver........................................................28  
5.3.6 Checking the MiniLink Local Loop...............................................................29  
5.3.7 Checking the Local Loop at MiniLink...........................................................30  
5.3.8 Checking the MiniLink Local Loop Driver ...................................................32  
5.3.9 Checking the Local Loop at a WHP Controller.............................................33  
5.3.10 Checking WHP Controller Driver Chip.........................................................34  
5.4 Troubleshooting Loop Controller ..........................................................................35  
5.4.1 Checking the Loop Controller Analog Inputs................................................35  
5.4.2 Checking the Loop Controller Outputs..........................................................37  
5.4.3 Checking the Local Loop at a WHP Loop Controller....................................38  
5.4.4 Checking WHP Loop Controller Driver Chip ...............................................39  
5.4.5 Comm Driver Chip Replacement...................................................................40  
5.5 Temperature Sensor Resistance Chart ...................................................................41  
5.6 Pressure Sensor Voltage Chart...............................................................................42  
Notes: ............................................................................ 43  
Table of Figures  
Figure 4-1: System Wiring Overview.............................................................................2  
Figure 4-2: Communications Loop Routing...................................................................3  
Figure 4-3: WHP Controller Component Layout ...........................................................5  
Figure 4-4: Typical WHP Controller Wiring Diagram...................................................8  
Figure 4-5: Loop Controller Inputs & Outputs.............................................................13  
Figure 4-6: Diagnostic LED Blink Codes.....................................................................14  
Figure 4-7: Diagnostic LED Blink Codes.....................................................................15  
Figure 4-8: Communications Loop Wiring ..................................................................18  
Figure 4-9: MiniLink Address Switch Setting.............................................................19  
Figure 4-10: WHP Controller Address Switch Setting...............................................20  
Figure 4-11: Comm Driver Chip Replacement............................................................40  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
1.0 Communications  
Overview  
Perhaps no other portion of the system seems as difficult to diagnose as the communica-  
tions loop, yet it really can be quite simple if you understand how it works. In fact, much  
of the troubleshooting can be done by simple observation. We will lead you through the  
system functions and then provide you with detailed instructions for checking each piece  
of equipment.  
1.1 How It Works  
WattMaster uses a token-passing loop architecture, which means in simple terms that an  
“electronic message” called a token is passed from controller to controller in a round-  
robin fashion. A controller must wait to receive the token before it can send or request  
any data.  
Note: It is very important to know which device is the loop master on the loop  
you are troubleshooting.  
1.2 WattMaster WHP System  
The standard WattMaster WHP system may have only one communications loop or as  
many as thirty communication loops depending on the number of WHP Controllers to be  
connected to the system. It is important to remember that each loop must have its own  
master.  
If you are using the multiple loop version of the WHP system (for systems with more than  
30 WHP Controllers) a loop is required for each group of 30 WHP Controllers. The WHP  
Loop Controller may be connected to any of the Local Loops. The Local Loop that has  
the WHP Loop Controller installed can only have 29 WHP Controllers on that loop. Each  
Local Loop is connected to a MiniLink loop interface. The MiniLink is always the  
master on the Local Loops. The MiniLinks are connected to the CommLink II and to  
each other via the Network Loop.  
The CommLink II is always the master on the Network Loop. You must be sure the  
CommLink II is connected and functioning if you are troubleshooting the communica-  
tions loops. Make sure the CommLink II is set for multiple loops  
.
Start-Up and Troubleshooting  
4-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
COMPUTER  
(OPTIONAL)  
RS-485  
Comm Loop  
32K  
8K  
COMM  
RELA  
OUTPUT  
COM  
Y
T
Room Sensor  
with Optional  
Override & Adj.  
SHLD  
R
1-3  
OUT  
1
OUT  
485  
COMM  
RAM  
EPROM  
LD4  
REC.  
2
OUT  
3
OUT  
4
OUT  
5
CPU  
COM  
4-5  
COMM  
TEST  
12V  
ADDRESS  
ADD  
AIN  
1
AIN  
2
AIN  
3
AIN  
4
AIN  
5
GND  
GND  
AOUT  
PWR  
GND  
PRESSURE  
SENSOR  
YS101564  
24VAC  
24 VAC  
110/24 VAC  
Power Pak  
Dirty Filter Alarm  
Supply  
Air  
or Leaving Water Temp  
F
Modem  
(Optional)  
110/24 VAC  
Power Pak  
Sensor  
Typical WHP Controller Wiring  
M
R
T
R
S
D
R
D
O
H
C
D
A
A
H
S
#30  
#1  
Loop #1  
32K  
8K  
32K  
8K  
Network Loop  
RS-485  
19200 Baud  
COMM  
COMM  
RELA  
OUTPUT  
COM  
Y
RELA  
OUTPUT  
COM  
Y
COMM  
T
T
O
M
M
SHLD  
R
1-3  
SHLD  
R
1-3  
OUT  
1
OUT  
OUT  
1
OUT  
LINK  
I
K
LD4  
REC.  
485  
COMM  
RAM  
EPROM  
2
LD4  
REC.  
485  
COMM  
RAM  
EPROM  
2
N
OUT  
3
OUT  
4
OUT  
3
OUT  
4
II  
I
OUT  
5
OUT  
5
CPU  
COM  
4-5  
CPU  
COM  
4-5  
L
COMM  
TEST  
COMM  
TEST  
O
O
C
O
M
12V  
12V  
WHP  
Controllers  
ADDRESS  
ADD  
ADDRESS  
ADD  
AIN  
1
AIN  
2
AIN  
1
AIN  
2
M
O
D
P
P
AIN  
3
AIN  
3
E
M
AIN  
4
AIN  
5
AIN  
4
AIN  
5
GND  
GND  
GND  
GND  
AOUT  
AOUT  
PWR  
GND  
PWR  
GND  
PRESSURE  
SENSOR  
PRESSURE  
SENSOR  
W
AT  
C
YS101564  
YS101564  
TM  
CommLink II  
Multiple Loop  
Interface  
A
ST  
24VAC  
24VAC  
ER  
O
N
TR  
OLS  
, INC  
Local Loop  
RS-485  
9600 Baud  
MiniLink  
Loop # 1  
System Manager  
MINILINK  
1
2
T
4
8
16  
H  
R
32  
24VAC  
GND  
T
H  
R
#30  
#1  
24VAC  
24VAC  
Loop #2  
32K  
8K  
32K  
WED  
8K  
COMM  
COMM  
RELA  
OUTPUT  
COM  
Y
RELA  
OUTPUT  
COM  
Y
T
T
03:38PM  
SHLD  
R
1-3  
SHLD  
R
1-3  
MiniLink  
OUT  
1
OUT  
OUT  
1
OUT  
OCCUPIED  
ALARMS  
485  
COMM  
RAM  
EPROM  
485  
COMM  
RAM  
EPROM  
LD4  
REC.  
2
LD4  
REC.  
2
03/31/04  
NO  
OUT  
3
OUT  
4
OUT  
3
OUT  
4
OUT  
5
OUT  
5
CPU  
COM  
4-5  
CPU  
COM  
4-5  
WHP  
Controllers  
COMM  
TEST  
COMM  
TEST  
Loop # 2  
12V  
12V  
ADDRESS  
ADD  
ADDRESS  
ADD  
AIN  
1
AIN  
2
AIN  
1
AIN  
2
AIN  
3
AIN  
3
MINILINK  
1
2
AIN  
4
AIN  
5
AIN  
4
AIN  
5
T
4
8
16  
SH  
32  
GND  
GND  
R
GND  
GND  
AOUT  
AOUT  
PWR  
GND  
PWR  
GND  
PRESSURE  
SENSOR  
PRESSURE  
SENSOR  
24VAC  
GND  
YS101564  
YS101564  
24VAC  
24VAC  
H  
R
24VAC  
Local Loop  
RS-485  
9600 Baud  
Typical Network & Local Loop Wiring  
2 Conductor Twisted Pair with Shield  
(Beldon #82760 or Equivalent)  
#30  
#1  
Loop #3  
MiniLink  
Loop # 3  
32K  
8K  
32K  
8K  
COMM  
COMM  
RELA  
OUTPUT  
COM  
Y
RELA  
OUTPUT  
COM  
Y
T
T
SHLD  
R
1-3  
SHLD  
R
1-3  
OUT  
1
OUT  
OUT  
1
OUT  
485  
COMM  
RAM  
EPROM  
485  
COMM  
RAM  
EPROM  
LD4  
REC.  
2
LD4  
REC.  
2
OUT  
3
OUT  
4
OUT  
3
OUT  
4
OUT  
5
OUT  
5
MMIINNIILLIINK  
1
CPU  
COM  
4-5  
CPU  
COM  
4-5  
2
4
COMM  
TEST  
COMM  
TEST  
8
16  
H  
32  
12V  
12V  
ADDRESS  
ADD  
WHP  
ADDRESS  
ADD  
AIN  
1
AIN  
2
AIN  
1
AIN  
2
AIN  
3
AIN  
3
AIN  
4
AIN  
4
24VAC  
GND  
AIN  
5
AIN  
5
GND  
GND  
Controllers  
GND  
GND  
H  
AOUT  
AOUT  
PWR  
GND  
PWR  
GND  
Local Loop  
RS-485  
9600 Baud  
PRESSURE  
SENSOR  
PRESSURE  
SENSOR  
YS101564  
YS101564  
24VAC  
24VAC  
24VAC  
WHP Loop  
NOTE: * Only One Outside Air Sensor  
is Required per WHP System  
Controller  
U3  
See Note #3  
Loop #4  
CX1  
CX2  
RN1  
U2  
CX4  
1
U1  
U4  
TB1  
V1  
V2  
V3  
COMM  
#29  
T
#1  
SHLD  
R
CX5  
COM1-3  
U5  
LD6  
PAL  
R1  
R2  
R3  
COMM  
RS-485  
COMM  
1
RAM  
EPROM  
MiniLink  
LD7  
PWR  
TUC-5R PLUS  
(1 MEG)  
YS101816 REV  
1
HH  
.
2
LD8  
LED1  
U6  
R4  
R5  
4RLY  
I
O
B
D
.
Y
S
1
0
1
7
9
0
C1  
LD9  
LED2  
P1  
COM4-5  
32K  
8K  
32K  
8K  
R1  
+VREF  
CX6  
TB2  
5.11V  
COMM  
COMM  
TEST POINT  
RELA  
OUTPUT  
COM  
Y
RELA  
OUTPUT  
COM  
Y
U7  
RV1  
V4  
V5  
EWDOG  
R28  
T
T
Loop # 4  
MINILINK  
V
R
E
F
A
D
J
SHLD  
R
1-3  
SHLD  
R
1-3  
1
OUT  
1
OUT  
OUT  
1
OUT  
*OutsideAir  
INPUTS  
ADDRESS  
ADD  
U8  
1
2
485  
COMM  
RAM  
EPROM  
485  
COMM  
RAM  
EPROM  
+VDC  
4RLY  
I
O
B
D
.
Y
S
1
0
1
7
9
0
LD4  
REC.  
2
LD4  
REC.  
2
RN5  
OUT  
3
OUT  
4
OUT  
3
4
NE5090NPB3192  
0PS  
AIN1  
AIN2  
AIN3  
AIN4  
AIN5  
PU1  
8
OUT  
4
U9  
AIN1  
AIN2  
AIN3  
AIN4  
D6  
16  
32  
PU2  
CX10  
C7  
OUT  
5
OUT  
5
1
D7  
TOKEN  
2
PU3  
R6  
C9  
NETWORK  
T
4
8
D8  
U10  
CPU  
COM  
4-5  
CPU  
COM  
4-5  
SW1  
PU4  
16  
COMM  
TEST  
COMM  
TEST  
SH  
R
D9  
L1  
32  
Sensor  
PU5  
GND  
CX12  
D11  
12V  
12V  
D12  
R13  
GND  
GND  
C10  
PU7  
D14  
X2  
9 9 3 6  
AOUT1  
ADDRESS  
ADD  
WHP  
Controllers  
ADDRESS  
ADD  
AIN  
1
AIN  
2
AIN  
1
AIN  
2
JP1  
M C 3 4 0 6 4 A  
SC1  
4
ANALOG IN MOD I/O BD.  
YS101784  
C13  
C12  
U13  
AOUT1  
R15  
U12  
AIN  
3
AIN  
3
24VAC  
GND  
AOUT2  
AIN7  
CX14  
C14  
R19  
AIN  
4
AIN  
5
AIN  
4
AIN  
5
C16  
U14  
D15  
CX13  
U15  
C17  
GND  
PJ1  
TB4  
T
C15  
R22  
GND  
GND  
TB3  
D19  
GND  
SH  
R
GND  
GND  
R24  
R25  
C20  
CX15  
AOUT  
AOUT  
PWR  
GND  
PWR  
7 8 2 4 C T  
M
PRESSURE  
SENSOR  
PRESSURE  
SENSOR  
GND  
R26  
24VAC  
PRESSURE  
SENSOR  
YS101564  
YS101564  
EXPANSION  
T'STAT  
VR1  
VR2  
24VAC  
24VAC  
24VAC  
Loop # 4  
Local Loop  
RS-485  
9600 Baud  
Notes:  
3.) The Local Loop With The Loop Controller  
Installed Can Only Have Up To 29  
1.) 24 VAC Must Be Connected  
So That All Ground Wires  
Remain Common.  
WHP Controllers Attached As The WHP  
Loop Controller Occupies Address #30.  
2.) All Wiring To Be In Accordance  
With Local And National Electrical  
Codes and Specifications.  
4.) Systems may consist of up to 20 Local  
Loops (600 WHP Controllers). Consult  
factory for systems that exceed these quantities.  
System Wiring Overview  
4-2  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
All communications wiring should be labeled to avoid confusion and to aid future  
servicing.  
COMPUTER  
(OPTIONAL)  
POWER  
24VAC  
GND  
COMMUNICATIONS  
T
SHLD  
R
SYSTEM MANAGER POWER SUPPLY  
YS101716 REV. 1  
RS-485  
SYSTEM MANAGER  
COMM LINK II  
INTERFACE  
(MULTIPLE LOOP)  
UNIT COMES WITH  
STANDARD WALL MOUNT  
120/24 VAC POWER SUPPLY  
( MAY ALSO BE POWERED FROM 24VAC )  
Remote Link  
(OPTIONAL)  
U3  
CX1  
CX2  
RN1  
1
U2  
CX4  
U1  
U4  
CPU  
TB  
COMM  
1
V1  
V2  
T
V3  
SHLD  
R
CX  
5
COM1-3  
U5  
LD6  
PAL  
R1  
R2  
R3  
COMM  
RS-485  
COMM  
1
RAM  
EPROM  
LD7  
PW  
TUC-5R PLUS  
(1 EG  
1
HH  
R
M
)
YS101816 RE  
V
.
2
U6  
LD8  
LED1  
R4  
R5  
4RLY IO BD. YS101790  
C1  
LD9  
LED2  
P1  
COM4-5  
R1  
+VRE  
F
TB2  
CX6  
5.11V  
U
7
T
E
S
T
P
V4  
V5  
EWDO  
G
RV  
1
VREFADJ  
R28  
1
INPUTS  
ADDRESS  
ADD  
U8  
1
2
+VDC  
4RLY IO BD. YS101790  
RN5  
4
NE5090NPB319  
S
2
AIN1  
AIN2  
AIN3  
AIN4  
AIN5  
PU  
D6  
1
8
16  
32  
0P  
U9  
AIN1  
AIN2  
AIN3  
AIN4  
PU2  
CX10  
C7  
D7  
PU3  
TOKE  
N
R6  
NETWORK  
D8  
PU4  
U10  
SW1  
D9  
PU5  
L1  
C9  
GND  
CX12  
D11  
D12  
R13  
X2  
9 9 3  
6 4 A 3 4 0 M C  
AOUT1  
C10  
PU7  
GND  
D14  
JP  
1
SC1  
4
ANALOG IN MOD I/O BD.  
YS101784  
GND  
AOUT1  
C13  
C12  
U13  
R
15  
U12  
CX1  
AOUT2  
AIN7  
4
C1  
4
C16  
R19  
U14  
CX13  
U15  
D15  
C17  
GND  
TB4  
C1  
5
TB3  
PJ  
1
D19  
GND  
R
22  
24  
25  
R
R
C20  
CX15  
T
7 8 2 4 C  
R26  
24VAC  
PRESSURE  
SENSOR  
EXPANSION  
T'STAT  
VR1  
VR2  
CPU  
NETWORK  
LOOP  
TO OTHER WHP CONTROLLERS  
TO OTHER MINILINKS  
(NETWORK TERMINALS ONLY)  
Communications Loop Routing  
Start-Up and Troubleshooting  
4-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
2.0 WHP Controller  
Overview  
2.1 How It Works  
2.1.1 Initialization  
On system powerup the COMM LED remains extinguished for five seconds. After this  
delay, the COMM LED will blink out the address of the controller (Address Switch  
Setting). The COMM LED will then extinguish for another five seconds and then begin  
to blink for a twenty second startup delay. At the conclusion of this twenty second period,  
the COMM LED will begin blinking a diagnostic code every ten seconds. This code is  
described later in this document. The duration of a powerup initialization sequence is  
roughly one minute.  
During this initialization period, the controller retrieves all operating setpoints from its  
non-volatile EEPROM memory and initializes all outputs to an OFF condition.  
Note: All future references to the Water Source Heat Pump Controller in this docu-  
ment use WHP as the designation.  
2.1.2 Operating Summary  
At all times, after the conclusion of the initialization sequence, the WHP performs a  
specific set of operating instructions in the following order: (a - g repeat continuously)  
a. Read Analog Inputs for Temperatures and Overrides.  
b. Check the RS-485 communications port for any new setpoints from the System  
Manager and keeps the status updated for the System Manager.  
c. If the push-button override is active, it checks the timer to see if the override is  
finished.  
d. Calculates the current occupied/unoccupied mode from its internal week sched-  
uling.  
e. Calculates what state the output relays and analog output should be set to.  
f. Updates the diagnostic COMM LED blinking.  
g. Stores data in the internal trend log if ready for another log.  
4-4  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
2.2 Becoming Familiar with the WHP  
Controller  
RAM SIZE  
SELECT JUMPER  
COMMUNICATIONS  
RAM  
EPROM  
PIN 1  
DRIVER CHIP  
PAL  
INDICATION  
24 VAC Common for Inputs 1 - 3  
Fan-On/Off  
RS-485  
COMMUNICATIONS  
LOOP  
Rev. Valve-On/Off (Heat 1)  
Compressor-On/Off (Heat 2)  
Heat Pump Reset (Cool 1)  
Aux. Heating or Cooling (Cool 2)  
24 VAC Common for Inputs 1 - 3  
COMMUNICATIONS  
LED  
ADDRESS SWITCH  
( ADDRESS 18 SHOWN )  
CPU  
ANALOG INPUTS  
Space Sensor  
DIAGNOSTIC BLINK  
CODE LED  
Slide Adjust  
Supply Air Temp  
Leaving Water  
Temp or  
Dirty Filter  
REAL TIME  
CLOCK CHIP  
Lockout  
POWER LED  
24VAC  
POWER  
INPUT  
STATIC PRESSURE  
SENSOR INPUT  
Mounting Backplate  
WHP Controller Component Layout  
2.2.1 24 VAC Power Connector  
This connector provides power to the WHP Controller.  
24VAC - The “hot” side of the control transformer.  
GND - The grounded side of the control transformer. If the secondary of the con-  
trol transformer is not grounded, you must still observe polarity if the trans-  
former powers any other device!  
Warning: Connect only the GND terminal to the grounded side of a transformer  
- Failure to properly observe polarity will result in  
damage to the system. Observe polarity at all points in the  
system.  
Start-Up and Troubleshooting  
4-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
2.2.2 Analog Inputs  
This connector carries the analog and binary control input signals.  
AIN1 - Space Temp - This input accepts a two wire 10K Type III thermistor tem-  
perature sensor. The sensor measures 10,000 Ohms @ 77°F. The resistance drops  
as the temperature increases. The sensor is connected between this terminal and  
the GND terminal. This input is also monitored for push-button override com-  
mands. The push-button is only active during unoccupied hours so a push during  
occupied hours has no effect.  
AIN2 - Slide Adjust - If the OE212 or OE213 space temperature sensor is in-  
stalled, the sensor contains a slide adjust control for varying the current heating  
and cooling setpoints. If the OE210 or OE211 sensors are used, this input will not  
be used.  
AIN3 - Discharge Temp - The discharge temperature reading is used to detect  
discharge air temperature and to monitor for equipment failure. Once the com-  
pressor has activated, the discharge air temperature has 10 minutes to change by  
5°F or the controller assumes a mechanical failure has occurred.  
AIN4 - Leaving Water Temp and/or Dirty Filter Alarm - Can provide status  
only water temperature and/or dirty filter contact closure. If both are used at the  
same time, water temperature will be lost when the dirty filter contact is closed.  
AIN5 - Lockout - If this input is active all operations are terminated to protect the  
equipment.  
GND - Common return wire. This point is tied to ground on the WHP  
Controller.  
2.2.3 Analog Output Description  
AOUT - Analog Output - This output is not used.  
2.2.4 Relay Output Descriptions  
COM1-3 - Common 1 thru 3. - This ties the common return of the first 3 outputs  
together.  
OUT1 - Fan On/Off - The fan is enabled to run when this contact is closed.  
OUT2 - Reversing Valve or Heat 1 - This output enables the reversing valve if  
you have configured the WHP Controller for a compressor and reversing valve  
configuration. If the WHP Controller is configured for individual staging of heat-  
ing and cooling (no reversing valve) then this output enables heating stage 1.  
4-6  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
OUT3 - Compressor or Heat 2 - This output enables the compressor if you have  
configured the WHP Controller for a compressor and reversing valve configura-  
tion. If the WHP Controller is configured for individual staging of heating and  
cooling (no reversing valve) then this output enables heating stage 2.  
OUT4 - Heat Pump Reset or Cool 1 - This output can be used to reset a com-  
pressor that has gone off line. If the WHP Controller is configured for individual  
staging of heating and cooling (no reversing valve) then this output enables cool-  
ing stage 1.  
OUT5 - Aux. Relay or Cool 2 - If you have configured the WHP Controller for a  
compressor and reversing valve configuration this output can be configured as  
follows:  
1.) Stage 2 for cooling and/or heating mode.  
2.) Auxiliary scheduling relay. In this mode it can be programmed to follow an  
externally broadcast schedule signal.  
3.) Auxiliary relay. In this mode it can be used for any function requiring a man-  
ual user intervention.  
4.) Isolation valve. May be used to initiate opening of an isolation valve in case of  
high loop water pressure even if the WHP Controller is satisfied or in an un-  
occupied mode. In occupied mode this relay operates in conjunction with the  
compressor.  
If the WHP Controller is configured for individual staging of heating and cooling  
(no reversing valve) then this output enables cooling stage 2.  
COM4-5 - Common 4 and 5. - This ties the common return of the last 2 outputs  
together. Jumper this terminal to COM1-3 if the unit does not have separate  
cooling and heating power supplies.  
2.2.5 RS-485 Communications Connector  
This connector provides the connection point for the Local Loop RS-485 communications  
loop. The wiring consists of a twisted pair of wires with a shield.  
T - RS-485 (+) Communications terminal  
SHLD - Common return wire, this point is internally tied to GND on the WHP  
Controller.  
R - RS-485 (-) Communications terminal  
Start-Up and Troubleshooting  
4-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
2.2.6 WHP Controller Wiring  
Communication LED  
Typical WHP Controller Wiring Diagram  
4-8  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
3.0 Loop Controller  
Overview  
3.1 How It Works  
3.1.1 Initialization  
On system powerup LED2 remains extinguished for five seconds. After this delay, the  
LED2 will blink out the address of the controller (Address Switch Setting). The LED2  
will then extinguish for another five seconds and then the LED2 will begin blinking a  
diagnostic code every ten seconds. This code is described in the troubleshooting section.  
The duration of a powerup initialization sequence is roughly thirty seconds.  
During this initialization period, the controller retrieves all operating setpoints from its  
non-volatile EEPROM memory and initializes all outputs to an OFF condition.  
3.1.2 Operating Summary  
There is a standard set of operating instructions that are continuously performed over and  
over during normal Loop Controller operations. They are listed below.  
a
Read analog inputs for temperatures, pressures and binary contact closures  
b
Checks for new setpoints from System Manager or Prism Software and keeps the  
status values updated for these interfaces.  
c
Looks for “request to run” broadcast from any installed WHP Controller or from  
an on-board binary input.  
d. Set all outputs to match calculations for heat rejection or addition.  
e. Store data in internal trend log if ready for another log  
f. Broadcasts the operating commands to all WHP Controllers.  
g. Tests for lead/lag pump changeover if both pumps are off.  
h. Repeat steps a-g continuously  
Start-Up and Troubleshooting  
4-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
3.2 Loop Controller Inputs & Outputs  
3.2.1 Analog Inputs  
AIN1 - Return Water Temp - This input accepts a two wire 10K Type III ther-  
mistor temperature sensor. The sensor measures 10,000 Ohms @ 77°F. The re-  
sistance drops as the temperature increases. The sensor is connected between this  
terminal and the GND terminal.  
AIN2 - Supply Water Temp - This input accepts a two wire 10K Type III ther-  
mistor temperature sensor. The sensor measures 10,000 Ohms @ 77°F. The re-  
sistance drops as the temperature increases. The sensor is connected between this  
terminal and the GND terminal.  
AIN3 – Proof of Flow/Loop Pressure - This input accepts a differential pressure  
contact closure for proof of flow or a 0-50 PSI (0-5VDC) pressure transducer sig-  
nal.  
AIN4 - Outdoor Air Temp - The OA temperature is used to determine if pumps  
should be turned on during off periods, to prevent freezing. When the OA tem-  
perature is below 40° F, the pumps will be turned on.  
AIN5 - Manual Reset Input - Used to restart equipment after alarm condition  
has occurred. When this input is shorted to GND by a momentary pushbutton, a  
signal to restart is sent.  
AIN7 Phase Loss – If a phase monitor is being used, a normally open contact is  
connected here. When a loss of phase is detected, this contact closes shutting  
down the Loop Controller.  
GND - Common return wire. This point is tied to ground on the Loop Controller.  
3.2.2 Analog Output  
This connector carries a 0-10 volt control signal for the following items:  
AOUT1- Pump VFD Signal - If you have selected the variable speed pump op-  
tion this output signal is used to control the loop pressure.  
AOUT2 - Proportional Heat Signal - This output may be used when a modulat-  
ing signal is required to control heat addition temperature.  
GND - Common return wire, this point is tied to GND on the Loop Controller.  
4-10  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
3.2.3 Binary Output  
R1 Compressor Enable – Energizes the first stage of cooling.  
R2 Main Pump – Energizes the lead water pump.  
R3 Standby Pump – Energizes the standby pump if the main pump fails to  
start.  
R4 Alarm Indicator – Energizes when an alarm occurs on the Loop Controller.  
R5 Not Used – This output is not used.  
COM 1-3 - Common – 24 VAC from the AHU is connected to this terminal and  
is the common for inputs 1 through 3.  
COM 4-5 - Common – 24 VAC from the AHU is connected to this terminal and  
is the common for inputs 4 and 5.  
3.2.4 Relay Expansion Board - Outputs  
This connector carries the output relay dry contact open/closed signal.  
Relays 1-4 - Heat Addition/Rejection Stages - Can be configured to be used for  
either stages of heating or cooling of water when required.  
Relays 5-8 - Heat Addition/Rejection Stages – Same as above, can be used for  
heating or cooling of the water.  
3.2.5 Analog Input Expansion Board  
The following inputs use dry contact open/closed signals.  
AIN1 – Fire Alarm Contact - Used to shut down all equipment in case of a  
smoke or fire condition.  
AIN2 - Request to Run - Used to initiate system start when a water source heat  
pump controller other than the WattMaster WHP Controller is used.  
Warning: Fire Alarm Contact input must be connected to the AIN1- GND  
terminal if it is not used, a jumper must be connected between AIN1  
and GND, since this is a normally closed contact input. If this is not  
done the system will not operate.  
Start-Up and Troubleshooting  
4-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
3.2.6 Comm Connector - Communications  
RS-485 Communications Connector - This connector provides the connection point for  
the Local Loop RS-485 communications loop. The wiring consists of a twisted pair of  
wires with a shield.  
T - RS-485 (+) Communications terminal  
SHLD - Common return wire, this point is internally tied to GND on the WHP  
Controller.  
R - RS-485 (-) Communications terminal  
3.2.7 Power Terminal  
This connector provides power to the Loop Controller  
24 VAC - Connect to the “HOT” side of the control transformer.  
GND - The grounded side of the control transformer. If the secondary of the con-  
trol transformer is not grounded, you must still observe polarity if the trans-  
former powers any other device!  
Warning: Connect only the GND terminal to the grounded side of a transformer  
Failure to properly observe polarity will result in damage to the  
system. Observe polarity at all points in the system.  
4-12  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
Connect To Next Controller And/Or  
MiniLink On Local Loop  
Local Loop RS-485  
9600 Baud  
(See Note 3).  
Optional  
Pressure sensor  
Line Voltage  
Figure 4-5: Loop Controller Inputs & Outputs  
Start-Up and Troubleshooting  
4-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
4.0 Start-Up  
4.1 Blink Codes for WHP Controllers  
The WHP Controller uses an on board LED to indicate various diagnostic conditions  
during powerup and operation. The WHP Unit LED is labeled “COMM”. Starting with  
power up the LED blink codes are as follows:  
Off for five seconds  
COMM LED blinks the board address (Address 14 = 14 blinks)  
Five second pause  
Twenty second time delay - LED blinks twenty times  
Status code is repeatedly blinked every ten seconds to indicate controller  
status:  
Lowest  
1
2
3
4
5
Normal Operation  
Override Active  
Bad Space Sensor  
Heat Pump Lockout  
Communication Failure  
-
-
-
Highest  
Figure 4-6: Diagnostic LED Blink Codes  
Only the highest priority failure code will be shown. You must correct the highest priority  
alarm before other problems will be indicated.  
4-14  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
4.2 Blink Codes for Loop Controllers  
The Loop Controller uses an on board LED to indicate various diagnostic conditions  
during powerup and operation. The Loop Controller Unit LED is labeled “LED2”.  
Starting with power up the LED blink codes are as follows:  
Off for five seconds  
COMM LED blinks the board address (Address 14 = 14 blinks)  
Five second pause  
Status code is repeatedly blinked every ten seconds to indicate controller  
status:  
Lowest  
1
2
3
4
5
6
Normal Operation  
Pump and/or Flow Failure  
Bad Water Temp Sensor  
Single Phase Shutdown  
Water Pressure Alarm  
Fire Alarm  
-
-
-
-
Highest  
Figure 4-7: Diagnostic LED Blink Codes  
Only the highest priority failure code will be shown. You must correct the highest priority  
alarm before other problems will be indicated.  
4.3 Communications Checklist  
WHP Controllers are addressed from 1 to 30 on each loop except the loop with the  
WHP Loop Controller. This loop can only use address 1 thru 29 for the WHP Con-  
trollers. WHP Loop Controller is addressed as 30 on the loop it is connected to.  
Power has been cycled after changing addresses  
A multiple loop CommLink II is powered and connected to the communications loop.  
System Manager is connected to one of the local loops.  
The MiniLinks on each local loop are addressed with a unique address 1 thru 30,  
depending on the number of loops on your system.  
Start-Up and Troubleshooting  
4-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
4.4 Installation and Commissioning  
Information  
Familiarize yourself with the installation manual and system wiring diagrams  
before installing!  
1. Check to see if you have all the correct components for your installation.  
2. Establish the location for the CommLink Interface first. This is where your communi-  
cation cable will begin.  
3. Layout your communication wiring. For systems with more than 30 WHPs or more  
than one MiniLink, there are multiple communication loops:  
A. The Network Loop - This loop originates at the CommLink and interconnects  
MiniLinks together.  
B. The Local Loop – This loop originates at the MiniLink. The WHPs, Loop  
Controllers and the System Manager are connected to this loop.  
Tip: Using the WattMaster color-coded and labeled Communication Cable insures a  
quality installation. It also makes your installation much easier and less likely to  
have communications wiring errors!  
4. Communication cable must always be shielded – no exceptions!  
5. Mount controllers in appropriate locations according to their operating specification.  
6. Address controllers according to location and addressing instructions located in the  
system manual.  
7. With no power connected, wire controller according to wiring diagrams and in  
accordance with local codes. Never apply power until you have completed these pro-  
cedures in accordance to all system instructions.  
8. After completing all wiring connections, unplug the terminals for power and commu-  
nications. Always unplug the communications loop first and then the power. When  
reconnecting the wiring, connect the power first and then the communication loop.  
9. Continue step 8 until all devices have been wired and the power and communication  
terminals have been unplugged.  
4-16  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
10. Install CommLink and power-up. At this point you are ready to begin commissioning  
the system. It is preferred, though not necessary, to use a PC with Prism software to  
assist in the commissioning process.  
11. Start with the first controller on the communication loop or in multiple loop systems;  
start with the MiniLink or with the System Manager. Plug in the Communication  
terminal then plug in the Power terminal.  
12. Observe the LED indicator for the blink codes as outlined in the troubleshooting  
section of the manual. The blink code will first verify the address, then the operation.  
If the address is incorrect, reset the dipswitch, then reapply power to the controller.  
13. After each controller is connected and completes its initialization sequence, use the  
PC or System Manager to verify communication to that device. If you cannot com-  
municate, verify wiring, voltages, etc. in accordance with the troubleshooting section  
in the system manual. Do not proceed to the next device until you are properly com-  
municating with the current device.  
Continue this process until all controllers are connected and properly communicating.  
By following the above steps and procedures, your installation will be much faster and  
trouble free. Remember that each controller only contains one puff of smoke. Making  
sure that all wiring terminations and voltages are correct prior to applying power to a  
controller will insure that you don’t use that one puff.  
Start-Up and Troubleshooting  
4-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
COMM LINK II  
INTERFACE  
(MULTIPLE LOOP)  
POWER  
24VAC  
GND  
COMMUNICATIONS  
T
SHLD  
R
SYSTEM MANAGER POWER SUPPLY  
RS-485  
YS101716 REV.  
1
SYSTEM MANAGER  
U3  
CX1  
CX2  
RN1  
U2  
CX4  
1
U1  
U4  
CPU  
T
COM  
B1  
M
V1  
V2  
V3  
T
SHLD  
R X  
C
5
COM1-3  
U5  
LD6  
PA  
L
R1  
R2  
R3  
COM  
M
RS-48  
5
1
RAM  
EPROM  
COM  
M
L
D7  
TUC-5R PLUS  
EG)  
1
HH  
P
WR  
(
RE  
1
V.  
M
2
YS101816  
U6  
L
D8  
R4  
R5  
4RLY IO BD. YS101790  
LED1  
C1  
LD9  
LED2  
P1  
COM4-5  
R1  
+V  
RE  
F
TB2  
CX6  
5.11V  
POINT  
U7  
TES  
T
V4  
EWDOG  
RV  
1
V
5
V
REF ADJ  
R28  
1
INPUTS  
ADDRES  
S
ADD  
1
U8  
+VDC  
4RLY IO BD. YS101790  
2
4
RN  
5
NE  
5090NPB3192  
S
AIN1  
AIN2  
AIN3  
P
U1  
8
16  
0P  
U9  
AIN1  
AIN2  
AIN3  
AIN4  
D6  
U2  
P
CX10  
C7  
32  
TO KEN  
D7  
U3  
P
R
6
NETWORK  
D8  
U4  
U10  
SW1  
AIN4  
AIN5  
GND  
GND  
P
D9  
U5  
L1  
C9  
P
GND  
CX12  
D1  
1
D
12  
C10  
P
U7  
X2  
9 9  
6 4 A 3 4  
AOUT1  
4
R
13  
D14  
J
P1  
C M  
0
SC1  
ANALOG IN MOD I/O BD.  
YS101784  
C
13  
C12  
U13  
AOUT1  
R15  
U12  
AOUT2  
AIN7  
CX14  
C
14  
C
16  
R19  
U14  
CX13  
D15  
C20  
C17  
GND  
TB4  
U1  
5
C15  
TB  
3
PJ  
1
D19  
GND  
R22  
R24  
R25  
CX15  
T
2 4 7 C 8  
R26  
24VAC  
PRESSURE  
SENSOR  
EXPANSION  
T'STAT  
V
R1  
VR2  
CPU  
NETWORK  
LOOP  
TO OTHER WHP CONTROLLERS  
TO OTHER MINILINKS  
(NETWORK TERMINALS ONLY)  
Communications Loop Wiring  
4-18  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
4.5 Setting Address Switches  
4.5.1 Setting the MiniLink Address Switch  
LOOP  
ADDRESS SWITCH  
ADD  
1
2
4
8
8
7
6
5
16  
32  
4
3
2
1
OFF  
>
ADDRESS SWITCH SHOWN IS  
SET FOR ADDRESS 1  
ADDRESS SWITCH SHOWN IS  
SET FOR ADDRESS 13  
LOOP  
ADDRESS SWITCH  
1
2
4
8
8
7
6
5
T
16  
32  
4
3
2
1
SH  
R
NOTE:  
THE POWER TO THE MINILINK MUST BE  
REMOVED AND RECONNECTED AFTER  
CHANGING THE ADDRESS SWITCH SETTINGS  
IN ORDER FOR ANY CHANGES TO TAKE  
EFFECT.  
OFF  
>
24VAC  
GND  
CAUTION:  
T
DISCONNECT ALL COMMUNICATION  
LOOP WIRING FROM THE MINILINK BEFORE  
REMOVING POWER FROM THE MINILINK.  
RECONNECT POWER AND THEN RECONNECT  
COMMUNICATION LOOP WIRING.  
SH  
R
MiniLink Address Switch Setting  
Start-Up and Troubleshooting  
4-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
4.5.2 Loop Controller Addressing  
The Loop Controller address should always be set for address #30. A maximum of 29  
WHP Controllers on the loop that contains the Loop Controller. All other loops may have  
30 WHP Controllers. (Refer to Figure 2-10 for more detail)  
4.5.3 WHP Controller Addressing  
NOTE:  
IGNORE ANY MARKINGS  
OR NUMBERS ON THE SWITCH  
USE THE CHART!  
To determine the boards address,  
add the values of all the switches  
which are toggled down in the  
direction of the arrow  
NOTE:  
ADDRESS 30 CANNOT BE USED  
ON THE LOOP THAT HAS THE WHP LOOP  
CONTROLLER ATTACHED. ADDRESS 30  
ON THAT LOOP IS RESERVED FOR THE  
WHP LOOP CONTROLLER.  
CAUTION:  
YOU MUST POWER DOWN THE CONTROLLER  
AFTER CHANGING THE ADDRESS SWITCHES  
IN ORDER FOR ANY CHANGES TO TAKE EFFECT.  
ALWAYS REMOVE THE COMMUNICATIONS LOOP  
PRIOR TO DISCONNECTING POWER. RECONNECT  
POWER AND THEN RECONNECT THE COMMUNICATIONS  
LOOP TO THE CONTROLLER.  
WHP Controller Address Switch Setting  
4-20  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.0 Troubleshooting  
5.1 General Troubleshooting  
The following is a guide to assist in troubleshooting the WattMaster WHP System. It is  
provided as a systematic approach to determining and resolving common system  
problems.  
5.1.1 Communications Troubleshooting Checklist  
No WHP or Loop Controller Units are Communicating  
Is the CommLink II connected and plugged in?  
Is the CommLink II installed, a single or multiple loop version. A jumper in the  
CommLink can be set for “Single” or “Multi”. On the WHP system is considered a  
Multiple Loop version and the CommLink jumper must be set on Multi.  
Are Comm Loop voltages correct? See the Comm Loop troubleshooting guides.(page  
4-24)  
Is the Comm Loop open or shorted?  
Is the CommLink II connected and plugged in?  
Is the MiniLink Voltage correct?  
Are the WHP and Loop Controller address switches set correctly? See the addressing  
chart. (WHP Loop Controller should always be set to address 30, see Figure 4-10)  
Is the MiniLink address switch set correctly? See the addressing chart.(see Figure 4-  
10)  
Are the WHP and Loop Controllers powered? Check 24 VAC to the controllers.  
Is the System Manager connected to the Local Communications loop?  
Some WHP Units are communicating but others are not:  
Are the WHP Controller address switches set correctly? See the addressing chart.  
Is the WHP Loop Controller address switch set correctly? See the addressing chart.  
Are the WHP Controllers and Loop Controller powered? Check 24 VAC to the  
controllers.  
Is the REC LED on the missing WHP Controller “flickering”? See WHP Controller  
introduction for location of the REC LED. (see Figure 4-4)  
Is the COMM LED on the WHP Controller blinking an error code? See the Blink  
Code chart. (see Figure 4-6)  
Are Comm Loop voltages correct at the missing unit? See Comm Loop troubleshoot-  
ing guide starting on page 4-24.  
Start-Up and Troubleshooting  
4-21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.1.2 General Troubleshooting Checklist  
Begin troubleshooting by locating the general problem in the list below. Detailed  
component troubleshooting information follows later in this section.  
Zone is too warm  
Is zone calling for cooling?  
Is the compressor disabled due to minimum off time setting?  
Is water proof of flow signal disabled?  
Is the LED blinking an error code? See Figure 4-6.  
Zone is too cool  
Is zone calling for heating?  
Is the compressor disabled due to minimum off time setting?  
Is water proof of flow signal disabled?  
Is the LED blinking an error code? See Figure 4-6.  
Zone Sensor reading incorrectly  
Is the sensor near a source of heat or a cold draft? Location is a common problem.  
The sensor should be mounted on an inside wall away from heat sources and in a  
location with adequate room air circulation.  
Is the resistance reading correct? Check with the Temperature/Resistance Chart in  
this section. (see page 4-42)  
Is wiring correct? Check for errors.  
Check the Room sensor  
To meter the Room sensor:  
Unplug the room sensor terminal block. Using your meter, check the resistance of the  
unplugged terminal block. Use the supplied Temperature/Resistance Chart (page 4-  
42) to see if the sensor is within a reasonable range. Readings which are much too  
high or too low generally indicate wiring problems.  
To meter the Slide Adjust (optional):  
Use your ohmmeter to check the resistance between the room sensor GND wire and  
the AIN2 terminal on the unplugged terminal block.  
The resistance for various positions of the slider on the sensor should be as follows:  
Full UP position  
MID position  
Full DN position  
15K ( 500 )  
12.5K ( 500 )  
10K ( 500 )  
4-22  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.2 Alarms  
When an alarm occurs in the WHP or Loop Controller, it is reported to the System  
Manager. The alarms cause the light on the System Manager to illuminate. The View  
Alarms screen will indicate the address of the alarms. The Status screen will display the  
type of alarm that has occurred. Here is a list of the alarms that are reported to the System  
Manager.  
WHP:  
Bad Space Sensor – Space sensor is either open or shorted  
Hi Space Temp Alarm – If space temperature is 5° or more above cooling setpoint  
Lo Space Temp Alarm – If space temperature is 5° or more below heating setpoint  
Dirty Filter Alarm – Contacts between AIN4 and GND are shorted  
Cooling Failure – If supply air doesn’t drop 5° in 10 minutes in cooling mode  
Heating Failure - If supply air doesn’t go up 5° in 10 minutes in heating mode  
Loop Controller:  
Pump Failure – No proof of flow within 5 seconds after pump starts  
No Flow Detected – The contact between AIN3 and GND is open, no water flow  
Phase Shutdown – The contact between AIN7 and GND is open, loss of phase  
Lo Water Temp Alarm – Water Temp is below Lo Limit setpoint  
Hi Water Temp Alarm - Water Temp is above Hi Limit setpoint  
Start-Up and Troubleshooting  
4-23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.3 Checking Comm. Loop Voltages  
5.3.1 Checking the CommLink II Network Loop  
Diagram  
Overview  
This test checks for proper Network loop voltages at the CommLink II.  
The Loop LED (located on the front panel) should “flicker” when the CommLink II is  
attempting to communicate. The Loop LED will flicker more noticeably for a few  
seconds when first powered up. If the Loop LED does not flicker, the unit is defective.  
Make sure CommLink II jumper is set to “Multi” position.  
Proper loop voltages are essential for reliable communications. It is normal to see fluctua-  
tions at this point on the CommLink II. The average value should be close to the acceptable  
range described below. Values will vary upon initial powerup for about 10-15 seconds as  
the unit attempts to communicate.  
Measurements  
T - G (SHLD)  
R - G (SHLD)  
Action  
2.9 - 3.1 Volts DC  
1.9 - 2.1 Volts DC  
If voltages are too high or too low on either  
side  
1. Unplug the Network loop from the  
CommLink II and check for proper loop  
voltages. If a problem exists, disconnect  
each MiniLink Network loop until the  
problem is isolated.  
2. Check the CommLink II Driver chip.  
Replace the driver chip if necessary  
4-24  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.3.2 Checking the Comm Loop at the CommLink II  
Diagram  
The indicated values are typical of a normal system, actual readings may deviate slightly  
due to the number of units connected and other system specific factors.  
All of the connected Minilinks should be powered up for this test.  
Overview  
This is a “quick check” to determine if any of the driver chips on the Network loop are  
damaged. Since all units will “float” both of their communications connections at about  
2.45 Volts, you can quickly check the Network loop by unplugging it at the CommLink II.  
Be sure that the loop you are testing does not have a short circuit from T to R.  
The Loop LED (located on the front panel) should “flicker” when the CommLink II is  
attempting to communicate with the MiniLinks. There is a noticeable change in the  
flicker when the loop is disconnected, if you observe a normal functioning unit. When  
the loop is reconnected it may take up to 60 seconds before the CommLink II re-  
establishes communications with the MiniLinks.  
Measurements  
T – G (SHLD)  
R – G (SHLD)  
Action  
2.4-to-2.5 Volts DC  
2.4-to-2.5 Volts DC  
If voltages are too high or too low on  
either side  
One or more of the MiniLinks has a damaged  
Network driver chip. Disconnect the Mini-  
Links one at a time to isolate the problem.  
Start-Up and Troubleshooting  
4-25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.3.3 Checking the CommLink II Driver  
Diagram  
Overview  
This test checks for proper Network loop voltages coming from the CommLink II.  
The Loop LED (located on the front panel) should “flicker” when the CommLink II is  
attempting to communicate. The Loop LED will flicker more noticeably for a few  
seconds when first powered up. If the LED does not flicker, the unit is not function-  
ing.  
Proper loop voltages are essential for reliable communications. It is normal to see fluctua-  
tions at this point on the CommLink II. The average value should be close to the acceptable  
range described below. Values will vary upon initial powerup for about 10-15 seconds as  
the unit attempts to communicate.  
Measurements  
T
G
G
2.4 - 2.5 Volts DC  
2.5 - 2.7 Volts DC  
(SHLD)  
R
(SHLD)  
Action  
If voltages are too high or too low on either  
side  
1. The CommLink II has a damaged comm  
driver chip. Replace the driver chip.  
See instructions in section 1.3.11 for  
“Comm Driver Chip Replacement”.  
2. The CommLink II is defective.  
4-26  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.3.4 Checking the MiniLink Network Loop  
Diagram  
Meter Set To Read DC Volts  
The indicated readings are typical of a normally operating system. Actual readings may  
vary slightly due to the number of units installed and other factors. Any significant devia-  
tion from these values generally indicates a problem.  
These tests assume that the CommLink II is connected and powered, and that all  
MiniLinks which are connected are also powered.  
Overview  
Proper loop voltages are essential for reliable communications. It is normal to see fluctua-  
tions on an operating communications loop. The average value should be close to the ac-  
ceptable range described below. Values will vary upon initial powerup for about 15-30  
seconds as normal communications occur.  
Measurements  
T - G (SHLD)  
R - G (SHLD)  
Action  
2.9 - 3.1 Volts DC  
1.9 - 2.1 Volts DC  
Readings near Zero Volts  
Check for shorted wiring.  
If voltages are too high or too low on either  
side  
1. One or more devices connected to this  
loop may have damaged Comm driver  
chips.  
2. Wiring errors. Check for multiple loops  
“cross connected”, short circuits, etc.  
Start-Up and Troubleshooting  
4-27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.3.5 Checking the MiniLink Network Driver  
Diagram  
Meter Set To Read DC Volts  
These tests assume that the MiniLink being checked is powered up  
Overview  
This check is intended to determine if the Network Comm Driver chip on a MiniLink is  
damaged.  
Before unplugging the Network loop from the MiniLink, observe the Network Loop  
LED (located near the connector). It should periodically “flicker” as the CommLink II  
requests data from the MiniLink. The LED will also flicker when power to the  
CommLink II is cycled. If the LED is not flickering, the unit is not communicating  
with the CommLink II.  
Damage typically occurs when the communications loop is exposed to excessive voltage, as  
may occur during installation due to wiring errors. The driver chips are socketed on all  
boards to facilitate servicing. It is unusual for driver chips to fail during normal operation.  
Almost all failures occur as a result of wiring related problems.  
Measurements  
T – SHLD  
R – SHLD  
2.4 - 2.5 Volts DC  
2.4 - 2.5 Volts DC  
Minor variances may not indicate a problem if both tests indicate similar values  
Action  
If voltages are too high or too low on either  
side  
The MiniLink has a damaged Network  
Comm Driver chip. Replace the driver  
chip. See "1.3.11Comm Driver Chip Re-  
placement”.  
4-28  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.3.6 Checking the MiniLink Local Loop  
Diagram  
Meter Set To Read DC Volts  
The indicated readings are typical of a normally operating system. Actual readings may vary  
slightly due to the number of units installed and other factors. Any significant deviation  
from these values generally indicates a problem.  
These tests assume the MiniLink is powered up  
Overview  
Proper loop voltages are essential for reliable communications. It is normal to see fluctua-  
tions on an operating communications loop. The average value should be close to the ac-  
ceptable range described below. Values will vary upon initial powerup for about 30-45 sec-  
onds. Voltages fluctuate as normal communications occur.  
Measurements  
T – SHLD  
R – SHLD  
Action  
2.9 - 3.1 Volts DC  
1.9 - 2.1 Volts DC  
Readings near zero volts  
Check for shorted wiring.  
If voltages are too high or too low on either  
side  
1. One or more devices connected to this  
loop may have damaged Comm Driver  
chips.  
2. Wiring errors. Check for multiple loops  
inadvertently “cross connected”, short  
circuits, etc.  
Start-Up and Troubleshooting  
4-29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.3.7 Checking the Local Loop at MiniLink  
Diagram  
Meter Set To Read DC Volts  
The indicated values are typical of a normal system. Actual readings may deviate slightly  
due to the number of units connected and other system specific factors  
These tests assume that the controllers being checked are powered up.  
Overview  
This is a “quick check” to determine if any of the WHP Controllers or WHP Loop Control-  
ler on a Local Communications Loop are damaged. Since all WHP Controllers will “float”  
both of their communications connections at about 2.45 Volts, you can quickly check an  
entire loop by unplugging it at the MiniLink.  
Be sure that the loop you are testing does not have a short circuit from T - R.  
Damage typically occurs when the communications loop is exposed to excessive voltage, as  
may occur during installation, due to wiring errors. The driver chips are socketed on all  
boards to facilitate servicing. It is unusual for driver chips to fail during normal operation.  
Almost all failures occur due to wiring related problems.  
Measurements  
T – SHLD  
R – SHLD  
2.4 - 2.5 Volts DC  
2.4 - 2.5 Volts DC  
Minor variances may not indicate a problem if both tests indicate similar values.  
4-30  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.3.7 (continued)  
Action  
If voltages are too high or too low on either  
side  
1. One or more of the attached controllers  
has a damaged Comm Driver chip. Lo-  
cate and replace the driver chip(s).  
See "1.3.11 Comm Driver Chip Re-  
placement”.  
2. Wiring errors such as "crossed connec-  
tions", short circuits, etc.  
Start-Up and Troubleshooting  
4-31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.3.8 Checking the MiniLink Local Loop Driver  
Diagram  
Meter Set To Read DC Volts  
The indicated values are typical of a normal operating system. Actual readings may deviate  
slightly.  
These tests assume that the MiniLink is powered up.  
Overview  
This test checks for proper Local Loop voltages coming from the MiniLink.  
The Local Loop LED (located near the connector) should “flicker” when the Mini-  
Link is operating and when first powered up. If the LED is not flickering, the unit is  
not functioning.  
Proper loop voltages are essential for reliable communications. It is normal to see fluctua-  
tions at this point on the MiniLink. The average value should be close to the acceptable  
range described below. Values will vary upon initial powerup for about 10-15 seconds. The  
voltage will fluctuate as the unit attempts to communicate.  
Measurements  
T
G
G
2.9 - 3.1 Volts DC  
1.9 - 2.1 Volts DC  
(SHLD)  
R
(SHLD)  
Action  
If voltages are too high or too low on either  
side  
1. The MiniLink has a damaged Comm  
Driver chip. Locate and replace the  
driver chip(s). See "1.3.11 Comm  
Driver Chip Replacement”.  
2. The MiniLink is not functioning.  
4-32  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.3.9 Checking the Local Loop at a WHP Controller  
Diagram  
Meter Set To Read DC Volts  
The indicated readings are typical of a normal operating system. Actual readings may vary  
slightly due to the number of units installed and other factors. Any significant deviation  
from these values generally indicates a problem.  
These tests assume that a MiniLink is connected and powered up.  
Overview  
Proper loop voltages are essential for reliable communications. It is normal to see fluctua-  
tions on an operating communications loop. The average value should be close to the ac-  
ceptable range described below. Values will vary upon initial powerup for about 30-45 sec-  
onds. The voltages may fluctuate as normal communications occur.  
Measurements  
T – SHLD  
R – SHLD  
Action  
2.9 - 3.1 Volts DC  
1.9 - 2.1 Volts DC  
If meter reads between 2.4 VDC and 2.5  
VDC  
1) No CommLink II or MiniLink is con-  
nected and powered up.  
The Comm Loop “floats” at 2.4 - 2.5VDC  
when only controllers are connected to the  
loop. When a MiniLink is connected it will  
“bias” each side of the loop to the values  
listed above.  
2) If a CommLink II or MiniLink is con-  
nected, look for “open” wiring.  
If voltages are too high or too low on either  
side  
One or more devices connected to this loop  
have damaged Comm Driver chips.  
Start-Up and Troubleshooting  
4-33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.3.10 Checking WHP Controller Driver Chip  
Diagram  
Meter Set To Read DC Volts  
These tests assume that the controller being checked is powered up.  
Overview  
This check is intended to determine if the Comm Driver chip on a controller is damaged.  
Damage typically occurs when the communications loop is exposed to excessive voltage, as  
may occur during installation, due to wiring errors. The driver chips are socketed on all  
boards to facilitate servicing. It is unusual for driver chips to fail during normal operation.  
Almost all failures occur as a result of wiring related problems.  
Measurements  
T – SHLD  
R – SHLD  
2.4 - 2.5 Volts DC  
2.4 - 2.5 Volts DC  
Minor variances may not indicate a problem if both tests indicate similar values.  
Action  
If voltages are too high or too low on either  
side  
The controller has a damaged Comm  
Driver chip. Replace the driver chip. See  
"1.3.11 Comm Driver Chip Replacement”.  
4-34  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.4 Troubleshooting Loop Controller  
5.4.1 Checking the Loop Controller Analog Inputs  
Diagram  
Overview  
The analog input wiring can be checked at the  
Loop Controller by checking voltages on the  
Analog Input Connector.  
SET METER TO  
READ DC VOLTS  
If any of the RWT, SWT, OAT inputs read  
greater than 5.0 volts then it is OPEN (no  
sensor is connected), an input that reads less  
than 0.1 volts is SHORTED. Check for wiring  
problems before proceeding.  
+
12V  
R
AIN1  
AIN2  
AIN3  
AIN4  
AIN5  
GND  
-
The Loop Pressure, Manual Reset, Phase  
Loss, Fire Alarm and Request to Run inputs  
should read greater than 5.0 volts if the at-  
tached contact is OPEN and less than 0.5 volts  
if the contact is CLOSED (contacts CLOSE  
between the input and GND). The Fire Alarm  
and Request to Run contacts are located on  
the Analog Input Expansion Board.  
GND  
ALL READINGS ARE TAKEN  
WITH THE (-) LEAD OF THE  
METER ON THE GND  
TERMINAL  
AOUT1  
AOUT2  
AIN7  
GND  
The Loop Controller must be pow-  
ered for these tests.  
Measurements  
Ignore readings for any connections which are not used in the  
equipment.  
AIN1  
1.9 volts (100°F) - 3.6 volts (40°F)  
Typical is 2.5 volts @ 77°F  
Return Water Temp  
AIN2  
1.9 volts (100°F) - 3.6 volts (40°F)  
Supply Water Temp  
Typical is 2.5 volts @ 77°F  
AIN3  
When used with the Low Pressure Switch option:  
If the input is OPEN, the voltage will be greater than 5.0 volts  
If the input is CLOSED, the voltage will be less than 0.5 volts  
When used with 0-50 PSI Loop Pressure Sensor option:  
5.1 VDC = 50 PSI – 0.0 VDC = 0 PSI  
Proof of Flow  
Start-Up and Troubleshooting  
4-35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.4.1 (continued)  
AIN4  
1.9 volts (100°F) - 3.6 volts (40°F)  
Typical is 2.5 volts @ 77°F  
Outdoor Air Temp  
AIN5  
If the input is OPEN, the voltage will be greater than 5.0 volts  
If the input is CLOSED, the voltage will be less than 0.5 volts  
Manual Reset  
AIN7  
If the input is OPEN, the voltage will be greater than 5.0 volts  
If the input is CLOSED, the voltage will be less than 0.5 volts  
Phase Loss  
AIN1-Exp. Bd.  
Fire Alarm  
If the input is OPEN, the voltage will be greater than 5.0 volts  
If the input is CLOSED, the voltage will be less than 0.5 volts  
Caution: AIN1 – Fire/Smoke input must be connected  
to the AIN1- GND terminal. If it is not used, a jumper must be  
installed, since this is a normally closed contact input. If this  
is not done the system will not operate.  
AIN2-Exp. Bd.  
Request to Run  
If the input is OPEN, the voltage will be greater than 5.0 volts  
If the input is CLOSED, the voltage will be less than 0.5 volts  
SWT, RWT, OAT Input voltage reads too  
low  
1. Check for shorts or other wiring errors.  
2. Defective Sensor. Check using the chart.  
3. High temperature at sensor. See chart.  
1. Check for open circuit wiring errors.  
2. Defective sensor. Check using the chart.  
3. Low temperature at sensor. See chart.  
1. Check for shorts or other wiring errors.  
2. Defective Sensor. Check using the chart.  
3. High pressure at sensor. See chart.  
SWT, RWT, OAT input voltage reads too  
high  
LPR (when optional 0-5VDC Loop Pres-  
sure Sensor is used) input voltage reads too  
low.  
LPR (When Loop Pressure Switch is used)  
input voltage reads too high.  
1. Check for open circuit wiring errors.  
4-36  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.4.2 Checking the Loop Controller Outputs  
Diagram  
Overview  
The analog output wiring can be checked at  
the Loop Controller by checking voltages on  
the Analog Output Connector.  
SET METER TO  
READ DC VOLTS  
The Loop Controller must be pow-  
ered for these tests.  
R
+
ALL READINGS ARE TAKEN  
WITH THE (-) LEAD OF THE  
METER ON THE GND  
TERMINAL  
-
Measurements  
Ignore readings for any connections which are not used in the equip-  
ment.  
AOUT1  
Pump VFD  
AOUT2  
This output will vary between 0 and 10 VDC to correspond with pump  
pressure setpoint.  
This output will vary between 0 and 10 VDC to correspond with Heat  
Addition setpoint.  
Mod. Heat  
Start-Up and Troubleshooting  
4-37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.4.3 Checking the Local Loop at a WHP Loop Controller  
Diagram  
Meter Set To Read DC Volts  
The indicated readings are typical of a normal operating system. Actual readings may vary  
slightly due to the number of units installed and other factors. Any significant deviation  
from these values generally indicates a problem.  
These tests assume that a MiniLink is connected and powered up.  
Overview  
Proper loop voltages are essential for reliable communications. It is normal to see fluctua-  
tions on an operating communications loop. The average value should be close to the ac-  
ceptable range described below. Values will vary upon initial powerup for about 30-45 sec-  
onds. The voltages may fluctuate as normal communications occur.  
Measurements  
T – SHLD  
R – SHLD  
Action  
2.9 - 3.1 Volts DC  
1.9 - 2.1 Volts DC  
If meter reads between 2.4 VDC and 2.5  
VDC  
1) No CommLink II or MiniLink is con-  
nected and powered up.  
The Comm Loop “floats” at 2.4 - 2.5VDC  
when only controllers are connected to the  
loop. When a MiniLink is connected it will  
“bias” each side of the loop to the values  
listed above.  
2) If a CommLink II or MiniLink is con-  
nected, look for “open” wiring.  
If voltages are too high or too low on either  
side  
One or more devices connected to this loop  
have damaged Comm Driver chips.  
4-38  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.4.4 Checking WHP Loop Controller Driver Chip  
Diagram  
Meter Set To Read DC Volts  
These tests assume that the controller being checked is powered up.  
Overview  
This check is intended to determine if the Comm Driver chip on a controller is damaged.  
Damage typically occurs when the communications loop is exposed to excessive voltage, as  
may occur during installation, due to wiring errors. The driver chips are socketed on all  
boards to facilitate servicing. It is unusual for driver chips to fail during normal operation.  
Almost all failures occur as a result of wiring related problems.  
Measurements  
T – SHLD  
R – SHLD  
2.4 - 2.5 Volts DC  
2.4 - 2.5 Volts DC  
Minor variances may not indicate a problem if both tests indicate similar values.  
Action  
If voltages are too high or too low on either  
side  
The controller has a damaged Comm  
Driver chip. Replace the driver chip. See  
"1.3.11Comm Driver Chip Replacement”.  
Start-Up and Troubleshooting  
4-39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.4.5 Comm Driver Chip Replacement  
MINILINK COMMUNICATIONS INTERFACE  
WHP CONTROLLER  
1
2
4
8
WHP CONTROLLER  
COMM DRIVER CHIP  
( U5 )  
T
16  
SH  
R
PIN 1  
32  
NETWORK LOOP  
24VAC  
GND  
COMMUNICATIONS  
DRIVER CHIP  
(U5)  
T
SH  
R
LOCAL LOOP  
COMMUNICATIONS  
DRIVER CHIP  
(U8)  
Ys101806 REV.2  
DSPY1  
U1  
MODULAR  
SYSTEM MANAGER  
RV1  
U2  
R1  
R4  
U3  
U3  
CX4  
CX6  
D1  
R5  
R6  
D2  
R7  
U4  
COMMUNICATIONS  
DRIVER CHIP  
PJ1  
CX5  
C3  
PIN 1  
U7  
X2  
U6  
RN1  
R13  
U8  
CX7  
SC1  
U9  
U12  
U13  
Comm Driver Chip  
(U13) Pin 1  
LOOP CONTROLLER CPU BOARD  
System Manager  
DOT  
PIN 1  
SOCKET  
COMM DRIVER CHIP  
( U1 )  
PIN 1  
PRINTED  
CIRCUIT  
BOARD  
TYPICAL RS-485  
DRIVER CHIP  
WARNING!  
USE EXTREME CAUTION WHEN REMOVING ANY CHIPS  
TO AVOID DAMAGING ANY CIRCUIT BOARD TRACES WHICH  
ARE UNDER THE CHIP.  
BE SURE THAT ANY SMALL SCREWDRIVER OR OTHER  
SHARP OBJECT USED TO REMOVE THE CHIP DOES NOT  
COME INTO CONTACT WITH THE PRINTED CIRCUIT BOARD  
SURFACE.  
A SMALL SCREWDRIVER MAY BE INSERTED BETWEEN THE  
CHIP AND THE SOCKET TO AID IN REMOVAL OF THE CHIP.  
BE VERY CAREFUL NOT TO INSERT THE SCREWDRIVER UNDER  
THE SOCKET!! DAMAGE TO THE BOARD IS NOT COVERED  
BY WARRANTY.  
COMMLINK II  
Comm Driver Chip Replacement  
4-40  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.5 Temperature Sensor Resistance  
Chart  
º
º
-10  
-5  
0
93333  
80531  
69822  
60552  
52500  
45902  
40147  
35165  
30805  
27140  
23874  
21094  
18655  
17799  
16956  
16164  
15385  
14681  
14014  
13382  
12758  
12191  
11906  
11652  
11379  
11136  
10878  
10625  
10398  
10158  
9711  
4.620  
4.550  
4.474  
4.390  
4.297  
4.200  
4.095  
3.982  
3.862  
3.737  
3.605  
3.470  
3.330  
3.275  
3.217  
3.160  
3.100  
3.042  
2.985  
2.927  
2.867  
2.810  
2.780  
2.752  
2.722  
2.695  
2.665  
2.635  
2.607  
2.577  
2.520  
2.465  
82  
84  
86  
88  
90  
95  
100  
105  
110  
115  
120  
125  
130  
135  
140  
145  
150  
8893  
8514  
8153  
7805  
7472  
6716  
6047  
5453  
4923  
4449  
4030  
3656  
3317  
3015  
2743  
2502  
2288  
2.407  
2.352  
2.297  
2.242  
2.187  
2.055  
1.927  
1.805  
1.687  
1.575  
1.469  
1.369  
1.274  
1.185  
1.101  
1.024  
0.952  
5
10  
15  
20  
25  
30  
35  
40  
45  
50  
52  
54  
56  
58  
60  
62  
64  
66  
68  
69  
70  
71  
72  
73  
74  
75  
76  
78  
80  
*Notes:  
1. Use the resistance column to check the  
thermistor sensor while disconnected from  
the controllers (not powered).  
2. Use the voltage column to check sensors  
while connected to powered controllers. Read  
voltage with meter set on DC volts. Place the  
“-”(minus) lead on GND terminal and the  
“+”(plus) lead on the sensor input terminal  
being investigated.  
If the voltage is above 5.08 VDC, then the  
sensor or wiring is “open.” If the voltage is  
less than 0.05 VDC, the sensor or wiring is  
shorted.  
9302  
Start-Up and Troubleshooting  
4-41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
5.6 Pressure Sensor Voltage Chart  
0
1
2
3
4
5
6
7
4.00  
4.32  
4.64  
4.96  
5.28  
5.60  
5.92  
6.24  
6.56  
6.88  
7.20  
7.52  
7.84  
8.16  
8.48  
8.80  
9.12  
1.00  
1.08  
1.16  
1.24  
1.32  
1.40  
1.48  
1.56  
1.64  
1.72  
1.80  
1.88  
1.96  
2.04  
2.12  
2.20  
2.28  
2.36  
2.44  
2.52  
2.60  
2.68  
2.76  
2.84  
2.92  
3.00  
3.08  
3.16  
3.24  
3.32  
3.40  
3.48  
3.56  
3.64  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
14.88  
15.20  
15.52  
15.84  
16.16  
16.48  
16.80  
17.12  
17.44  
17.76  
18.08  
18.40  
18.72  
19.04  
19.36  
19.78  
20.00  
3.72  
3.80  
3.88  
3.96  
4.04  
4.12  
4.20  
4.28  
4.36  
4.44  
4.52  
4.60  
4.68  
4.76  
4.84  
4.92  
5.00  
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
9.44  
9.76  
*Notes:  
10.08  
10.40  
10.72  
11.04  
11.36  
11.68  
12.00  
12.32  
12.64  
12.96  
13.28  
13.60  
13.92  
14.24  
14.56  
1. Use the voltage column to compare the  
meter voltage with the sensor connected to  
the controller and with the controller pow-  
ered.  
2. Read voltage with meter set on DC volts.  
Place the “-”(minus) lead on GND terminal  
and the “+”(plus) lead on the sensor input  
terminal being investigated.  
3. If the voltage is less than 0.05 VDC, then  
the sensor or wiring is “shorted” or “open”  
4-42  
Start-Up and Troubleshooting  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WattMaster WHP  
Section 4  
Notes:  
Start-Up and Troubleshooting  
4-43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Form: WM-WHP-IO-02A  
All rights reserved  
Printed in the USA  
October 2004  
Copyright 2004  
Wattmaster Controls Inc. 8500 NW River Park Drive Parkville MO 64152  
Phone (816) 505-1100  
Fax (816) 505-1101  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Great Dane Lawn Mower GSRKA1934S User Manual
Groupe SEB USA T FAL Iron PROTECT User Manual
Hasbro Games 33500 User Manual
Heat Glo LifeStyle Cooktop TiaraE 4035 822 User Manual
Honeywell Weather Radio C7046A User Manual
Hotpoint Cooktop CEM 645 D C User Manual
Hotpoint Ventilation Hood LI2SZA User Manual
Hunter Fan Landscape Lighting 43540 01 User Manual
Husqvarna Brush Cutter 355FRM User Manual
hussman Refrigerator IGSV ASCS 0303 User Manual