Harman Stove Company Electric Heater The Harman Accentra Pellet Insert User Manual

Installation & Operating Manual  
The Harman Accentra Pellet Insert  
“Ce manuelest disponibleen Françaissur demande”  
R3  
SAFETY NOTICE  
PLEASE READ THIS ENTIRE MANUALBEFORE YOUINSTALL AND USE YOURNEW ROOM HEATER. FAILURE TO  
FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTYDAMAGE, BODILYINJURY, OR EVEN DEATH.  
FOR USE IN THE U.S.AND CANADA. SUITABLE FOR INSTALLATION IN MOBILE HOMES  
IF THIS HARMANACCENTRA PELLET INSERT IS NOT PROPERLY INSTALLED,AHOUSEFIRE MAYRESULT. FOR  
YOURSAFETY, FOLLOWINSTALLATIONDIRECTIONS.  
CONTACT LOCAL BUILDING OR FIRE OFFICIALSABOUT RESTRICTIONSAND INSTALLATION INSPECTION  
REQUIREMENTS INYOUR AREA.  
CONTACT YOUR LOCAL AUTHORITY (SUCHAS MUNICIPAL BUILDING DEPARTMENT, FIRE DEPARTMENT, FIRE  
PREVENTION BUREAU,ETC.) TO DETERMINE THENEED FORA PERMIT.  
CETTEGUIDE D'UTILISATIONEST DISPONIBLEENFRANCAIS.CHEZVOTRECONCESSIONNAIRE DEHARMANSTOVE  
COMPANY.  
SAVETHESEINSTRUCTIONS.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
Automatic Start Up  
Starting First Fire  
Igniter Switch to"AUTO" (up position)  
Make sure the unit is plugged into a 120 VAC,  
60 HZ electrical source. The power light should  
betheonly lightlit.  
1. Turn Mode Selector to "OFF".  
2. Fill hopperwithpellets.1  
3. Clean burn potwithscraper, ifnecessary.  
See Note 7.  
Fig. 1  
1"  
5
4. If starting after an empty hopper, turn Feed  
Adjuster to "TEST" (for one 60 second cycle).2  
Thiswill purgepelletsintotheauger tubeandalso  
allowyoutocheckthemotorsforoperation.NOTE:  
Theauger motor will not operatewith theview  
door or ash pan door open.3  
4
5. Turn Feed Adjuster to #4.  
6. Flip the Igniter Switch up into the "AUTO"  
position.  
7. Turn the Temperature Dial to desired room  
temperature.  
8. Turn Mode Selector to Room Temperature or  
StoveTemperature.  
Fig. 2  
1.Fines are small pieces of broken pellets(sawdust). Fines do  
not floweasily and often build up on the hopperfunnel bottom  
angles. These fines can be pushed into the feeder opening  
and then fill the hopper with pellets. As the system works,they  
will be burned.  
2. The "TEST" cycle will operate the feeder motor for exactly  
one minute. Turning to "TEST" again and againmay purge too  
much fuel into the burn pot causing excessive smoke on start-  
up.  
3.Thefirebox low pressure switchwill notallow the augermotor  
or the igniter element to operate if the view door is open.  
4. Adjust Feed Rate. If this is your first fire or you are trying  
different pellets, set the feed adjuster to #4, Fig. 1. This is a  
conservative numberand will probably need to be increased.  
After you know a feed rate setting that works well, use that  
setting. Remember,ifyour feed rate is too high youmay waste  
fuel.  
9. Fill hopper withpellets andremoveashes as  
required.6  
10. Store pellet fuel in a dry area away from all  
ignitionsources and aboveall limits of thestove's  
clearance requirements to combustibles. Donot  
storethe fuel were it interferes with the refueling  
of the stove or emptying of ashes. Do not store  
anyashes removed from the stovenear the fuel  
orother combustiblematerials.  
5.This is usually a weekly maintence procedure.Cleaning the  
burn potwiththe scraper with asmall amount of new fuel in the  
bottom is not a problem.First,scrape the ashes on the front of  
the burn pot into the ash pan. Then scrape the holed surface  
downward into the burn pot. When the stove is ignited these  
scrapings will be pushed out by the feeder.  
6.The ash pan can hold the ashes from approximately1 ton of  
premium fuel. This means the ashes will only need to be  
emptied a few times a year.  
WARNING  
BURNING GARBAGE, USE OF IMPROPER FUELS,  
FIRE STARTERS ORALTERING THE STOVE FOR  
HIGHER HEAT OUTPUT MAY CAUSE DAMAGE TO  
THESTOVEANDCOULD RESULTINAHOUSE FIRE.  
USE ONLY APPROVED FUELS AND OPERATION  
GUIDELINES.  
7. Setting the feed adjuster # for maximum burn:With the unit  
burning in"AUTO",turn to "Stove Mode" and putthefan on "H".  
Set theTemperature Dial to #7.Allow the unit to burn for about  
30 minutes andcheck ash on frontof burn pot. Fig. 4.If the ash  
line is largerthan 1",turn the feed adjuster from #4 to #5. Allow  
another 30 minutes of burn time and check again. If , at #6  
setting, a 1" orless ash bed is notobtainable,itisnota problem.  
The 1" ash bed is only a maximum burn rate and at most  
normal settings the ash bed will be larger.  
WARNING  
NEVERUSE GASOLINE,GASOLINE-TYPELANTERN  
FUEL, KEROSENE, CHARCOAL LIGHTER FLUID,  
OR SIMILAR LIQUIDS TO START OR'FRESHEN UP'  
A FIRE INTHIS HEATER. KEEPALL SUCH LIQUIDS  
WELL AWAYFROM THE HEATER WHILE INUSE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
Automatic Ignition/Operation  
The Accentra Insert is more thanjust automatic ignition, it is also automatic temperature  
control. The automatic systemwill allow the fire size to be adjustedto matchthe heating  
needs and even put the fire out if necessary. If heat is needed after the fire is out, the  
Accentra Insert will automatically re-ignite and adjust the fire size to match the heating  
need.The totallyautomatic roomsensor modeis recommendedbecause of its efficiency.  
The unit can be switchedbetween "AUTO" and "MANUAL" at any time during operation.  
Igniter switch to "AUTO"  
Room Temperature Mode  
In "Room Temp Mode" heat output is controlled au-  
tomatically by the Room Sensing Probe. When the Room  
Sensing Probe calls for heat, the stove will increase out-  
put. When the Room Sensing Probe is getting close to  
the set temperature, the stove will begin to level off out-  
put and keep the fire burning at just the right temperature  
to maintain that setting.  
High output is determined by the feed rate set-  
ting. This setting, generally on #4, can be increased if  
higher burn rates are necessary (Fig. 1). The unit's maxi-  
mum burn rate should not create less than 1" of ash on  
the burn pot front edge(See Fig.2). Overfeeding is not a  
Fig. 3  
Room Temperature Mode: This setting will produce a room  
temperature of 70 degrees with the distribution blower at medium  
speed.  
safety concern, but fuel may be wasted if unburned pel-  
lets fall into the ash pan.  
In "Room Temp Mode" a constant fuel consumption  
rate is sacrificed for exact room temperature. Therefore,  
as it gets colder more pellets will be burned automati-  
cally.  
Stove Temperature Mode  
The distribution blower speed will vary according to  
the position of the mode selector pointer, and fire size.  
Igniter switch to "AUTO"  
Stove Temperature Mode  
This allows for automatic ignition upon start-up only.  
The unit can then be set at any desired setting. The heat  
output and fuel consumption will remain constant regard-  
less of room temperature (See Fig 4). The unit's maxi-  
mum feed rate should not create less than 1" of ash on  
the burn pot front edge. See Fig 2.  
The unit's low burn or maintenance setting is as low  
as it will go. It will not go out unless it runs out of fuel or is  
turned off.  
This setting will produce medium heatwith the  
distribution blower on "low".  
Shut-Down Procedure  
To killthe fire or stopburningthe stove, turnthe Mode  
Selector to "OFF". This will cause the fire to diminish and  
burn out. When the fire burns out and the stove cools  
down everything will stop.  
If you pull the plug to shut down the stove, all motors  
will stop. This may cause incomplete combustion and  
smoke inthe firebox. If theload door is openedthe smoke  
may escape.  
The best way to shut down the stove is simply let it  
run out of pellets, then the stove will shut down automati-  
cally.  
This setting willproduce continuous maximum heat  
output with the distribution blower atfull speed.  
Fig. 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6
Manual Start Up  
Starting First Fire  
Igniter Switch to"MANUAL" (down position)  
Fig. 6  
Make sure the unit is plugged into a 120  
VAC, 60 HZ electrical source. The power light  
shouldbethe only lightlit.  
Fig. 5  
1. Turn FEED ADJUSTER to desired feed  
See Note 7.  
rate. No. 4 is good for most pellets.4  
1"  
2. Turn the MODE SELECTOR to “OFF” and  
then to the desired mode. This will reset  
control and start thecombustionmotor.  
3. Turn the TEMPERATURE DIAL to the de-  
sired setting.  
5
4. Clean burn pot with scraper if necessary.  
Fig. 7  
5. Fill burn pot with pellets, only level with  
1. Fines are small pieces of broken pellets (sawdust). Fines  
do not flow easily and often build up on the hopper funnel  
bottom angles. These fines can be pushed into the feeder  
opening and then fill the hopper with pellets. As the system  
works, they will be burned.  
2. The "TEST" cycle will operate the feeder motor for exactly  
one minute. Turning to "TEST" again and againmay purge too  
much fuel into the burn potcausing excessive smoke on start-  
up.  
3. The firebox low pressure switch will not allow the auger  
motor or the igniter element to operate if the view door or the  
ash pan door are open.  
4. Adjust Feed Rate. If this is your first fire or you are trying  
different pellets, set the feed adjuster to #4, Fig. 5. This is a  
conservative numberand will probably need to be increased.  
After you know a feed rate setting that works well, use that  
setting.Remember,ifyourfeed rateis too high you may waste  
fuel.  
front edge. (Do Not Over Fill).  
6. Add starting gel on top of the pellets. Stir  
gel intopellets for fastlighting.  
7. Light starting gel with a match, and close  
the door. Operation will begin when the fire  
reaches the propertemperature.3  
8. Fill hopper with pellets and remove ashes  
as required.1, 6  
Notice when using Optional Battery Back-Up:  
If a power outage is expected, change the toggle  
switch to Manual Mode. The Harman 502H Battery  
5.This isusually a weekly maintence procedure. Cleaning the  
burn pot withthe scraperwith a small amountof new fuel in the  
bottom is nota problem. First,scrape the ashes on the front of Backup is incapable of powering the igniter. If an  
the burn pot into the ash pan. Then scrape the holed surface  
downward into the burn pot. When the stove is ignited these  
scrapings will be pushed out by the feeder.  
6.Theash pan can holdthe ashes from approximately 1 ton of  
automatic ignition is attempted while the stoves is  
being powered by the battery back up, it may cause  
damage to both the stove and the battery backup  
unit.  
premium fuel. This means the ashes will only need to be  
emptied a few times a year.  
7. Setting the feed adjuster # for maximum burn: With the unit  
burning in "AUTO",turn to "StoveMode" and putthe fan on "H".  
Warning  
Setthe Temperature Dial to #7.Allow the unit to burn for about  
30 minutes and check ash on frontof burn pot. Fig. 9.Ifthe ash  
line is largerthan 1",turn thefeed adjuster from #4to #5. Allow  
another 30 minutes of burn time and check again. If , at #6  
setting, a 1" or less ash bed is not obtainable, it is not a  
problem. The 1" ash bed is only a maximum burn rate and at  
most normal settings the ash bed will be larger.  
NEVERUSE GASOLINE,GASOLINE-TYPELANTERN  
FUEL, KEROSENE, CHARCOAL LIGHTERFLUID, OR  
SIMILAR LIQUIDS TO START OR 'FRESHEN UP' A  
FIRE IN THIS HEATER. KEEP ALL SUCH LIQUIDS  
WELL AWAYFROM THE HEATER WHILE INUSE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
Manual Ignition/Operation  
The Accentra Insert is capable of manual operation. This also allows the operator to  
manually control operation during an emergency (i.e. igniter failure, when using a 502H  
battery backup, or when using certain generators.)  
The unit can be switched between "AUTO" and "MANUAL" at any time during operation.  
NOTE: When starting the unit in the "AUTO"  
mode and switching to "MANUAL", the fire must be  
large enough to start the distribution blower. The  
starting of the blower is a signal that the start cycle  
is completed and the fire will not go out.  
Igniter Switch to "MANUAL"  
Room Temperature Mode  
The fire will have to be lit with starting gel and a  
match, or started automatically, see "Automatic Opera-  
tion". Turn to "Manual" position when the fire is estab-  
lished.  
The difference between "AUTO" Room Tempera-  
ture Mode and "Manual" Room Temperature Mode is  
that the fire willnot go out as the roomtemperature goes  
above the control board setting. The unit can only go to  
low burn and will remain there until it runs out of fuel or  
until more heat is needed and the feed rate increases.  
Feed rate adjustments and dial settings are the same  
as "AUTO" settings.  
Fig. 8  
Room Temperature Mode: This setting will produce a room  
temperature of 70 degrees with the distribution blower at medium  
speed.  
Manual Stove Temperature Mode  
Igniter Switch to "MANUAL"  
Stove Temperature Mode  
The advantage of this mode is to allow the opera-  
tor to have a large viewing fire without blowingextra heat  
into the room.  
During operation, with the temperature dial set at  
#5 or less, the distribution fan will not operate. A #5 on  
the temperature dial and a #5 on the feed adjuster is  
approximately 80% output. It is not necessary to oper-  
ate the distribution blower below this point. Therefore,  
there can be a higher feed rate ( a larger viewing fire)  
without an excess of hot air blowing into the room.  
An example of when to use the Manual Stove Tem-  
perature Mode is if you want to watch a large fire and  
the room is aleady up to temperature. The Stove Tem-  
perature Mode allows you to have a larger fire and a  
lower sound level, without the distribution blower.  
NOTE: During the useof this mode, if you keep  
increasing the temperature dial setting to increase  
the fire size, the distribution blower will automati-  
cally come on when the ESP Temperature reaches  
350o F, or 81%output.  
This setting willproduce a large viewing fire without a  
distribution blower operating.  
Fig. 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8
ESP Control  
Power Light  
Indicates power to the  
control.  
Feed adjuster  
Sets the maximum  
feed rate  
Test  
Runsallmotorsatfull  
speed forone minute  
to check operation.  
After twominutes the  
stove will go to  
minimum burn and  
the blowers will  
alternate fromhigh to  
low every minute to  
remind you that you  
are still in "Test  
Mode".  
Status Light  
Will be lit in either stove  
orroom tempmode when  
pointer is notwithin off  
positionband except  
after normalshutdown.  
Blinks to indicate errors  
listed below.  
Indicates power to  
distribution blower.  
Igniter switch  
Setto appropriate  
Start-Up mode.  
Indicates power to  
combustion blower  
Distribution Blower  
speedadjustmentrange.  
L = low  
H = high  
Indicates power to the  
feed motor.  
Variablespeedanywhere  
between L and H;  
although as the stove  
temp. goes up ,so does  
the L andH scale.  
Indicates igniter is on.  
Mode Selector  
Temp dial  
Dealer Diagnostic Port  
For dealer maintenance  
only. RequiresspecialDDM  
monitor suppliedto Harman  
Dealers exclusively.  
Allowsyoutochoosebetween  
Room Temp Mode, Stove  
Temp Mode, or OFF. Also  
allows you to vary the  
distribution blower speed by  
turning the knob to the high  
or lowside ofeach mode.  
Allows you to adjust the room temperature in Room Temp  
Mode using the outer scalemarked in degrees Fahrenheit.  
It also allows you to adjust the stove temperature while in  
Stove Temp Mode usingthe innerscale markedfrom 1to 7.  
Status light error messages:  
1 Blink: Indicates controlboard self diagnostic fail- 6 Blinks : Indicates that the control has calculated  
ure. This requires a manual reset*.  
poor or incomplete combustion occurring for more  
3 Blinks: Indicates ESP (Exhaust Sensing Probe)  
failure. This requires a manual reset*.  
4 Blinks: Can occur only in Room Temp Mode and  
than 50 minutes.  
A six blink status may be set if the stove is allowed  
to run out of pellets. To reset, turn mode selector to  
indicates Room Sensing Probe failed or not in- "OFF" then back on to the desired mode. If the unit  
was not out of pellets, see Troubleshooting section,  
Page 24, for more details.  
* Manual reset- disconnect power cord for a few  
seconds and reconnect. If error still occurs call your  
Dealer.  
stalled. If a Room Sensing Probe is then installed,  
the status light will automatically reset.  
NOTE: Unit will not start in "AUTO" with this status  
error.  
5 Blinks (In Igniter Auto. Mode Only): Indicates  
that the unit has failed to light within the 36 minute  
start cycle. To reset - Turn Mode Selector to "OFF",  
then turn to either mode again.)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9
Installation: Removing unit from skid  
How to Reduce the Weight for Installation  
1. Remove the top/lid assembly and side panels.  
Note: Removal of the cast hopper lid itself is  
NOT necessary or recommended.  
Note: The hopper lid must be in the "OPEN" position  
before the top/lid assembly can be lifted off or  
reinstalled on the stove body.  
Bolts require a  
3/8" socket.  
There are (4) 1/4-20 x1/2" flange headbolts securing  
the top/lid assembly to the stove body. They can be  
removed from the underside with a 3/8" socket.  
The cast top and lid assembly bolt down bars:  
On each side of the stove body, underneath the cast  
top, are (2) 1/4" flange head bolts.See Fig. 12.  
These bolts pull the cast top and lid assembly down  
onto the hopper gasket to seal the hopper.  
They also allow for a small amount of front to back  
adjustment for alignment of the top into the wing  
pockets.  
(View looking up under the cast top.)  
Fig. 12  
Top bolt down bar  
Be careful not to  
damage  
the  
distribution blower  
located under the  
insert. There are  
guards on both  
sides of the motor  
to allow the insert  
to rest on a flat  
surface, however,  
extra care should  
be taken.  
Remove the cast side panels by lifting them upward  
off of the hinge pins. See Fig. 13.  
Top and LidAssembly  
DistributionBlower  
ProtectorAngles: These angles aredesigned to  
protect the blower motor from damage when  
placed on a flat surface. Be careful where and  
how the stove body is handled.  
Fig. 10  
Center  
Medallion  
Heat  
Exchanger  
Cover  
(2)SpringLatches  
(One oneach side)  
Mounting Shell  
Internal  
Cast Iron  
(4) pieces  
Ash Pan  
Flame Guide  
Fig. 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10  
Installation  
Removing the Center Medallion  
Lift up on the 2 bottom corners of the medallion until  
it is higher than the top of the flame guide.  
Pull the bottom edge of the medallion front approxi-  
mately 1 inch.  
Pull downward on the corners of the medallion until  
the top is released from the 2 retainers that keep the  
top aligned when in place.  
Note: The heat exchanger covers will tilt to the front  
when the center medallion is removed.pproximatlely  
12”, but the left side tube requires the total length of the  
brush to be used.  
Center Medallion  
Fig. 13  
rd  
rd  
3 : DOWN  
3 : DOWN  
Lasered hinge pin  
pivoting point  
Cast side  
panel hinge  
1st:UP  
2nd:OUT  
Up and down clearance  
adjustment slots.  
Flameguide  
How to Reduce the Weight for Installation, cont'd  
2. Remove the door by swinging it open approximately  
90o and lift it upward until it clears the hinge pins.  
3. Remove the ash pan  
Burn Pot  
4. Remove the (4) internal pieces of cast iron. See Fig.  
14 and 15.  
Fig. 14  
Removing the Heat Exchanger Covers  
Remove the heat exchanger cover by lifting it upward  
about 1/2 inch and move the bottom edge front until it  
sits flat on the firebox bottom.  
Rotate the edge of the heat exchanger closest to the  
burnpot until it is in front of the burnpot.  
Tip the top of the heat exchanger toward the middle of  
the opening until it can be lifted up and out.  
Lifting tab  
Fig. 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
Installation  
Beginning Installation  
3" Outside Air  
starter collar  
IMPORTANT: The mounting frame/surround  
assembly and flue piping is the most critical part of  
theinstallation andmustbe done correctlyandinstalled  
securely.  
Notch  
1.Choose the chimneyconfigurationthat is best suited  
for the installation. See venting section.  
• Note: If 100% outside air is desired or required, the  
outsideair optionwill needto be installed onthe stoves  
body. (See instructions included with outside air kit  
(part #1-00-674080.) See Page 20.  
2. Make sure the unit will fit into the fireplace opening.  
See Fig # 17. When installing in smaller fireplaces,  
test fit the mounting frame into the firebox. Note: The  
unit overhangs to the rear.  
3. Install the 3 piece cast surround set to the sides  
and top of the mounting frame with the bolts and nuts  
supplied. The left and rightside should be done before  
the center section is installed. Make sure the bolts  
are loose. Do not remove the side panel hinges. The  
left and right side wings should be standing up aligned  
with the side of the mounting frame and slid inward  
towards the center. Note:The wings mount on the rear  
side below the notch and on the front side above the  
notch. See Fig. 16 & 18. Slide the cast ash lip onto  
the frame and check to make sure it can go against  
the roped frame rails and fits into the pockets on the  
left and right cast sides. See Fig. 19.  
Fig. 16  
Ash lip slide rails  
Install the center section.  
4. If the wing extensions are required they should be  
installed next.  
Cast in front of  
the frame. Use  
(1)1/4-20 x 3/8  
flange bolt from  
the rear.  
Fig. 17  
Approximately 2" overhang  
NOTE:The stovebody extends throughthemountingframe  
inthe rear approximately 2".  
Slide the ash lip  
casting into the  
frame, making  
certain the ash lip  
is sitting on the  
slide rails on  
either side. With  
the ash lip in  
place, adjust the  
surroundsides so  
there is an even  
gapwheretheash  
lip extends into the  
surround side and  
Castbehind the  
mounting frame  
flange. Use (2)  
1 / 4 - 2 0 x5 / 8  
flange bolts and  
nuts with bolts  
fromthe front.  
tighten.  
Fig. 18  
Fig. 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12  
Installation  
Optional Wing Extensions  
Connecting the cord retainer to the wing  
Optional wing extensions are made for fireplace open-  
ings which are larger than the cast wing. The 3 piece  
wing extension is 48" wide by 34"high.  
Custom oversized wing extensions can be purchased  
from Harman for any fireplace openings larger than the  
standard wing extension area.  
These optional wing extensions will have a 1/2 inch re-  
turn bend as shown in fig. 20. Custom oversized wing  
extensions with a radius top can be ordered with a ra-  
dius of your choosing. These radius top wings WILL  
NOT have a return bend, although they will be made of  
thicker metal to reduce warpage.  
With the three wing pieces completed, the cord re-  
tainer must be bolted to the bottom rear of the wing.  
Either left exit (shown in fig. 22) or right exit.  
At the bottom rear edge of the right and left wing there  
is a small radius indent for the cord to exit between  
the wing and the fireplace face.  
1/4-20 x 3/8  
bottom head bolts  
(5/32" allenwrench)  
(5/32" allenwrench)  
Fig. 22  
Fig. 20  
5. The power cord can be installed exiting the left  
(standard) or right side of the surround. If a right side  
cord is desired, follow the instructions below.  
Changing the cord exit location from the left side  
to the right side:  
Ground  
Ty-raps  
The cord is located on the left side, standard from  
Harman. (See fig 21.)  
To route the cord to the right side:  
• Cut the tyraps looping the cord to the left  
• Reroute the cord along the top of the steel angle and  
down the right side.  
• Re-tyrap (not supplied by Harman) the wire through  
the notches providedin the mounting frame.Then down  
the right side rail.  
• Do not remove or move the cord retainer, it is made  
to reach both the right and left sides.  
Fig. 23  
6. You must now decide whether to install the room  
sensor as a wall sensor or as a return air sensor.  
Harman highly recommends that the room sensor be  
installed. If you are installing the room sensor as a wall  
sensor, the long black 2 wire cable must be Ty-rapped  
to the powercord. This wire is long enough to reach the  
end of the power cord so the installer can reach past  
the hearth to the location where the extension wire (18/  
2 thermostat wire, not supplied by Harman) can be  
spliced to go to the wall location chosen for the room  
sensor.  
Nothing can ex-  
tend beyond this  
DO  
NOT  
face to the back  
side.  
CUT.  
Fig. 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13  
Installation  
8. Install the (4) 3/8-16 x 1" leveling bolts into the  
threaded holes in the bottom pan of the mounting shell.  
The front two leveing bolts may not be necessary, but  
the back two will need to be used to level the wing so  
that it is flush with the fireplace face. See Fig. 26.  
7. If the room sensor is used as a return air sensor  
rather than a room thermostat/sensor, the black cable  
will not be used. The room sensor itself (gray cable  
with black and red wires) will be connected to the blue  
twisted wires from the control board.  
Note: The stove body must be able to slide out of the  
shell to the limit of the power cord wires for cleaning  
andservice. Therefore, if the room sensor is connected  
as a return air sensor, the wire should be connected  
long enough to allow this, but not too long that it would  
get tangled or pinched anywhere.  
1/2" threaded  
wedging rods  
Notice: The male/female connections between the  
mounting shell and the stove body should always be  
maintained. Wirenut or taped splices should never be  
used.  
Connecting the room sensor as a return airsensor  
Insert the sensor end of the wire from the rear of the  
mounting frame through the hole as shown in fig. 24 .  
Tyrap the sensor end so that the sensing tip is in the  
middle of the front return air opening. See Fig. 25.  
Tyrap the sensor wire to the inside of the mounting  
frame up to the cord grounding location. Follow the  
power wiring to where you make the male/female ter-  
minal connection to the twisted blue wires.  
There are (2) crimp-on connectorsin the hardware pack  
that must be installed on the internal ends of the room  
sensor wires.  
3/8 x 16 tapped  
levelingbolt holes  
(5) bolt downholes  
Fig. 26  
Fig. 24  
Side ReturnAir Holes  
Fig. 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R3  
14  
Installation  
9. Install the completed frame/surround assembly into the  
firebox and level/plumbthe wingto the fireplace faceusingthe  
leveling bolts as jacks.  
* Ash protection must be used from hearth opening to 6" in  
front of door glass and 6" to each side of the stove body to  
protect any combustibles from hot ashes. A minimum size  
will be 16.5" deep by 30" wide and be made of a non-  
combustible materialor meet UL approval.  
Fig. 28  
Flue Pipe Stub Assembly  
(from glass)  
10. Test fit the cast ash lip (See fig. 25) on the shell frame  
mounting rails. The ash lip should slide on these side rails  
without liftingupward off of the rails as the ashlip is slid inward.  
Asmallclearance of about 1/16"is anideal spacebetween the  
legsoftheashlipandthehearth. Thiscast ashlipisa decorative  
part that does not and should not support any weight.  
There are three different diameter flue pipe stub  
assemblys.  
1. The unitcomes standard with the largest for use with 4”  
stainless steel flex pipe.  
2.Part #1-10-082745for use with 4” PL ventstarter pipe.  
3. Part # 1-10-674039 for use with 3” PL vent starter  
pipe and also for use with 3” aluminum flex duct for out-  
side air connections.  
11. Tightenthe (2) 1/2" threaded wedgingrods upagainst the  
lintel of the fireplace opening. It is also recommended to use  
some form ofanchoringscrews throughthe bottomof the shell  
into the hearth. There are up to 5 holes provided. Note: It is a  
good idea to check the ash lip again. The frame may have  
shiftedwhenthe finalanchoring was completed. Seefig. 26.  
The flue stub assembly base is a round plate which al-  
lows it to swivel to allow the flue pipe to exit the mount-  
ing frame in other positions rather than straight up. See  
fig. 28.  
12. Complete the flue piping, and outside air piping, if used.  
Make sure the damper area is sealed.  
CAUTION: IF THE STAINLESS STEEL FLUE PIPE DOES  
NOT EXTEND FAR ENOUGH ABOVE THE OLD DAMPER  
14. Install the flue pipe insulation wrap. See Fig. 27. This  
ceramic insulation is precut to form around the flue pipe  
stub, to reduce heat transfer into the area around the  
OPENING, MAKE SURE THE FIBERGLASS INSULATION rear of the hopper and motor area. This insulation must  
DOES NOT EXTEND UPWARD AND COVER THE PIPE  
OUTLET.  
WARNING DO NOT CONNECT THIS UNIT TO ANYAIR DIS-  
TRIBUTION DUCT OR SYSTEM.  
be installed in all configurations, ev en if a rear  
discharge is used. See Fig. 29.  
This picture shows the completed  
insulation wrappedaround the flue pipe  
fromthe mountingframe upward.  
13. If arear exitflue configurationis used,withorwithout outside  
air, makesure theflue pipeterminationclearances are followed  
as per themanufacturers recommendations.  
Twisted tie wire  
d  
t  
,  
e  
Ash lip  
:  
mounting  
t  
rails  
Fig. 29  
Fig. 27  
With larger flue pipes this bottom edge of the insulation will  
need to be trimmed to complete the wrap.  
Pre-cut ceramic insulationand (2) pieces of tie wire.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15  
Connecting the ground from the wing to the  
Installation  
15. Install the cast side panels by sliding them down  
over the lasered hinge pin. Note: Check for rotational  
swing, but finish with them in the open position. The  
cast side panels may need adjustment after the stove  
body is latched into place and the front door is closed.  
stove body  
The green wire with a female terminal is the stove  
body ground.  
On the combustion air inlet box there is a male ter-  
minal ground.  
If service is performed on this stove,this ground  
connection must be the first one on and the last  
one off.  
Fig. 30  
Lasered hinge pin pivoting point  
Cast side  
panel hinge  
Up and down clearance adjustment slots.  
16. Place the stove body onthe mountingshell gasketed  
rails and insert the body into the opening far enough  
that it can't tip out. Note: A service rail kit (Part #1-00-  
08007), ora pair of 2 x4'ssupported infront ofthe hearth  
will make this job easier. See Fig. 31.  
Fig. 32  
Connecting the power cord  
17. Complete the following electrical connections  
(caution: Disconnect the power cord.) There are 5  
connections that must be completed. See Fig. 33 & 34.  
The white from the mounting frame connects to the  
white of the insert body.The black from the mounting  
frame connects to the brown of the insert body.  
Fig. 33  
2 x 4  
Fig.31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
16  
Installation  
19. Inspect the silicone sponge gasket on the top edge  
of the hopper.  
If it is okay, put the cast top/hopper lid assembly (see  
Fig. 35) into place over the hopper.  
Make sure the hopper lid is open to install unit, then  
close it to keep from getting pinched in case the lid falls  
unexpectedly.  
Insert the (4) 1/4-20 x 1/2 flange head bolts into the  
mounting hole but do not tighten them.See page 8, fig.  
12.  
Connecting the Room Sensor  
Connecting the room sensor to the blue twisted wires  
from the control board:  
• (2) 3/16 inch maleterminals areprovided for the ends  
of the room sensor wires.  
• They will mate with the female terminals on the blue  
twisted wires.  
•These connections are “not polarity specific.”  
20. "Test" the unit with the stove body pulled out. This  
will allow you to see the motors in operation.  
• Turn the control to the "OFF" position.  
• Plug the unit into a 120 VAC 60 hz outlet.  
• Turn the control to "test". All of the motors should  
operate at full voltage for 60 seconds.  
Note: The door must be closed for the feed motor to  
operate.  
With the "Test" completed, unplug the unit.  
21. Inspect the flue docking gasket. See Fig. 36.  
Docking Gasket  
Everytime the unit is pulled out of the mounting frame,  
the orange high temperature docking gasket should be  
inspected. Check for tears or signs that the gasket is  
not sealing properly.  
Fig. 34  
18. Install the front door. Check the latch and gasketing.  
Docking Gasket  
Hopper Seal  
Inspect the silicone sponge hopper to top seal gasket.  
Look for tears or areas where the gasketmay not seal  
properly to the bottom of the cast top. This only needs  
to be done when the top is removed. This is NOT nec-  
essary if the cast top is not removed. (Not part of any  
monthly, semi-annual or annual maintenance.)  
Hopper sealgasket (grayor orange)  
Fig. 36  
Fig. 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17  
Installation  
22. Slide the stove body into the mounting frame.  
Cast Side Panel Installation  
• Note: The two spring latches on the bottom  
right and left side of the body must be in the proper  
position to enter the latch holes. (See fig. 37).  
• Latch the (2) spring latches into place.  
The stove body must be pulled out of the mounting  
frame several inches to install the cast side panels.  
Slide the cast side panel down over the hinge pins.  
Slide the stove body in and latch into place.  
Note: The cast side panels must be left in the open  
position to allow access to the latches.  
Slide the ash lip into place. (This would be inward  
until the rear of the cast iron touches the mounting  
frame front.)  
23. Shift the cast top/hopper lid assembly inward as far  
as possible to achieve a parallel fit with the surround  
sides. See Fig. 39. Tighten the cast top/hopper lid  
assembly bolts with a 3/8" socket. See page 8, Fig. 12.  
Close the cast side panels.  
24.Install and adjust the side panel magnets.  
In the hardware pack are (2) magnets, (2) spacers and  
(2) 10-32 x 1 1/4" bolts and nuts.  
Bolt the magnets through the cast iron hole provided.  
Important: The spacer must be on top of the  
hole, the magnet on top of the spacer with the  
bolt going down through the hole with the nut at  
the bottom, under the ash lip. See fig. 38.  
Check the gap alignment and the top and bottom  
gap spacing.  
The topand bottomspacing canbe adjustedby loos-  
ening the 3 bolts and sliding the hinge up or down  
until the spacing suits.  
With the front door closed and latched, check the  
vertical space alignment. The only method of chang-  
ing or adjusting this gap is by bending (slightly) the  
hinge angle. See fig. 39.  
25. Check the fit of the cast ash lip to make sure that it  
Due to the use of all cast iron parts, some small  
can be slid in and out easily. The cast ash lip can remain amounts of misalignment are expected. Since some  
parts are angled and some have rounded edges, this  
misalignment is very seldom noticable.  
It is very important that the cast side panels open  
and close freely for good control board access.  
in place at this time. Note: The cast side panel hinges  
can be moved upward if necessary to gain clearance for  
the cast ash lip.  
Latch Hole  
Spring Latch  
Fit cast  
Fit cast  
Magnet  
top/  
top/  
hopper  
hopper  
lid  
lid  
Fig. 37  
parallel  
parallel  
with  
with  
Magnet  
surround.  
surround.  
Side panel gap  
Fig. 39  
Fig. 38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
18  
Wiring  
Log Set Option  
Always disconnect the power cord beforethe unit  
is pulled from the mounting frame.  
As you can see, the control board is easily accessible  
from the rear with the body pulled out of the frame,  
even if it is only pulled out several inches.  
Always inspect the wiring harness of the 11 pin sock-  
ets (large white flat plug where all of the power wires  
terminate.)  
Always inspect the wiring harness where the wires  
transfer from the control to the rear inside of the body.  
Make sure there are no worn or frayed areas.  
Inspect thewiring harness transition area:This is thearea  
thatcomes closestto the mounting frame asthe unitis slid  
in and out of the frame.  
Thumb  
Screws  
Fig.42  
Install the log bracket with the two thumb screws  
provided.  
6 amp  
glass  
fuse  
11pin  
socket  
on rear  
of control  
board  
Fig. 40  
Fig. 43  
Center the log in the firebox opening with the bottom  
front edge over the thumb screws. The log branch  
tips only rest on the bracket arms for easy installa-  
tion and removal.  
REMINDERS  
Do not allow pellets or sawdust to build up on the  
hopper lip.  
Inspect the hopper lid gasket for damage. A good  
hopper lid seal is very important for proper opera-  
tion.  
IMPORTANT NOTE: BEFORE CLEANING THE  
HEAT EXCHANGERS, THE LOG AND THE  
LOG BRACKET MUST BE REMOVED.  
Hopper lid foam  
gaskets  
Cast Top  
Fig. 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19  
Low Draft Voltage Adjustment  
After the installation is completed but before the first fire is lit,  
check and record the high and low draft readings.  
Combustion  
Motor Speed  
Control  
Low draft only  
set point.  
The small  
straight  
screwdriverslot  
is plastic;  
therefore, the  
unit can be  
adjusted while  
in operation.  
Fig. 45  
Draft Meter bolt hole location  
Fig.44  
The head of the plug bolt can be accessed through  
the bottom distribution air inlet with the cast ash lip  
removed.  
These units are pre-tested at the factory with  
exactly 120 Volts A.C., 60 Hz. They are checked and  
adjusted for firebox tightness, gasket leakage, motor  
operation and igniter operation. The stove is then  
factory set at a high adjustment. NOTE: Low draft  
adjustment maybe required.The factorylow draft  
setting maynot be correct for theunits permanent  
installation conditions.  
The control board on the Accentra Insert is  
equipped with a low draft adjustment port. Located  
on the control face just to the right of the igniter light.  
See Figure 44. This voltage adjustment is provided to  
allowthe unit to be adjusted for the household voltage  
where the unit is going to be in permanant operation.  
NOTE: The line voltage varies from area to area and  
often home to home.  
The low draft voltage should be adjusted to  
achieve the most efficient burn on low burn or  
"maintenance". This voltage adjustment allows the  
installer to change the low voltage set point  
approximately 15 volts. This adjustment should be  
done by the installer during set up because a draft  
meter reading is required to insure proper set up.  
If the unit is not adjusted properly, it does not  
cause a safetyconcern. If the unitis adjustedtoo high,  
only effiency is lost. If the unit is adjusted too low, the  
low draft pressure switch will not allow the feeder  
motor or the igniter to operate.  
A simple draft test should be performed after  
completing the flue pipe installation. To record the  
results for future reference:  
1. Plug unit into a 120VAC, 60 HZ outlet.  
2. Close the hopper lid and front view door. Neither  
pellets or a fire are required for this test.  
3. With the mode selector in the "OFF" position, turn  
the feed adjuster to "TEST".  
4. Record the high draft_____in. W.C. (Normal is -  
.45 to -.55) The control will be on the High Draft for a  
total of 2 minutes.  
5. After 2 minutes is up, the combustion motor will  
go down to low draft and the distribution blower will  
go on high. Allow approximately 15 seconds to pass  
for the combustion motor to slowbefore checking the  
low draft.  
6. If the low draft is between .30 and .35, record the  
reading _____ in. W.C. If the reading is higher, slowly  
turn the set screw counter-clockwise until the draft  
lowers. If the reading is lower, very slowlyturn the set  
screw clockwise until the draft increases.  
NOTE:The test mode alternates from high to low  
draft every 60 seconds. If more time is needed  
for draft adjustment, wait until the next low draft  
cycle.  
NOTE: In some cases, the draft may not go as  
low as .30 even with the set screw completely  
counter-clockwise.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
20  
Mobile Home Installation  
Safety Reminders  
Mobile Home Installation  
Mobilehome installation should bedone in  
accordance with the Manufactured Home and  
Safety Standard (HUD), CFR 3280, Part 24.  
When installing the Accentra in a mobile home  
several requirements must be followed:  
1. The unit must be bolted to the floor. This can  
be done with 1/4" lag screws through the 5 holes in  
the base plate shown in Fig. 26.  
2. The unit must also be connected for the out-  
side air. See page 21.All mobile home installations  
require the use of outside air, this willincrease the  
heating efficiencyofthe unitand keepitfrom suffer-  
ing any effects associated with room air starvation  
such as poor combustion and or erratic operation.  
Periodically check the air inlet for any obstructions  
such as snow or ice build up.  
Kitchen exhaust fans, clothes dryers and  
other similar devices maycause improper operation  
ofthe pelletstove, if,while inuse itkeeps the room in  
a negative pressure thus allowingpipe joints notcom-  
pletelysealed to leakexhaustinto the room. Be sure  
to allow adequate ventilation while using such appli-  
ances  
When installing and operating your Harman  
Accentra Insert, respect basic safety standards.  
Readthese instructions carefullybeforeyou attempt  
to install or operate the Accentra Insert. Failure to  
do so may result in damage to property or personal  
injury and may void the product warranty.  
Consult with your local building code agency  
andinsurance representative before youbegin your  
installation to ensure compliance with local codes,  
including the need for permits and follow-up inspec-  
tions.  
CAUTION: This appliance must be vented  
to the outside.  
Due to high temperatures, this stove should  
be placed out of traffic and away from furniture and  
draperies.  
Children and adults should be alerted to the  
hazards of high surface temperatures and should  
stay away to avoid burn to skin and/or clothing.  
Young children should be carefully supervised  
when they are in the same room as the stove.  
Clothing and other flammable materials should  
not be placed on or near this stove.  
Installation and repair of this stove should be  
done by a qualified service person. The appliance  
should be inspected before use and at least annu-  
ally by a qualified service person. More frequent  
cleaning will be required. It is imperative that control  
compartments, burners, and circulating air pas-  
sageways of this stove be kept clean.  
3. Floor protection and clearances must be  
followed.Floorprotectionandclearances to combus-  
tibles mustbe followedas perinstallationinstructions  
for the stove. Clearances may only be reduced by  
means approved by the regulatory authority.  
4. Unit must be grounded to the metalframe of the  
mobile home.  
5. Smoke alarms and smoke detectors are recom-  
mended to be used with wood and biomass fueled  
stoves. W hen opening the firebox door some ex-  
haustmayescapeinto theroom andsetoffthe alarm.  
If this should happen ventilate the room to remove  
the smoke and resetthe alarm, ifthe alarm would go  
offwhen no one was working with the stove ventilate  
the room and have your home checked to find the  
source ofthe leak.  
CAUTION  
THE STOVE IS HOT WHILE IN OPERATION.  
KEEP CHILDREN, CLOTHING AND  
FURNITUREAWAY. CONTACT MAY CAUSE  
SKIN BURNS.  
WARNING  
KEEP COMBUSTIBLE MATERIALS SUCH  
AS GRASS, LEAVES, ETC.AT LEAST 3 FEET  
AWAY FROM THE POINT DIRECTLY UNDER  
THE VENT TERMINATION.  
WARNING  
USE OF IMPROPER FUELS, FIRE STARTERS  
ORALTERING THESTOVE FOR HIGHER HEAT  
OUTPUTMAYCAUSEDAMAGETOTHE STOVE  
AND COULD RESULT IN A HOUSE FIRE. USE  
ONLY APPROVED FUELS AND OPERATION  
GUIDELINES  
WARNING  
DO NOT INSTALL THIS UNIT IN ANY  
SLEEPING ROOM  
CAUTION  
THE STRUCTURAL INTEGRITY OF THE  
MOBILE HOME FLOOR, WALL, AND CEILING/  
ROOF MUST BE MAINTAINED.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
21  
Venting  
A combustion blower is used to extract the com-  
bustion gases from the firebox. This causes a negative  
pressure in the firebox and a positive pressure in the  
venting system as shown in fig. 46. The longer the vent  
pipe and more elbows used in the system, the greater  
the flow resistance.  
The recommended maximum flue lengths for the  
Accentra Insert are as follows:  
4" StainlessSteel Flex: 30 Linealft. Vertical*  
In flue pipe  
Inside hopper  
4" PL Vent Pipe:  
4" PlVent Pipe: 30 Linealft. Vertical*  
4" Pl Vent Pipe:14 ft. Vertical w/1-90o and12 linealft. horizontal*  
If additional 4" PL Vent fittings are required, the overall  
length must be reduced by:  
Vertical 90o or T: 2.5'  
Vertical 45o:  
1.5'  
Horizontal 90o or T: 5.0'  
Horizontal 45o:  
2.5'  
3" PL Vent Pipe:  
20 Linealft. vertical*  
8 Linealft. verticalw/1-90o & 8lineal ft. horizontal*  
Inside  
firebox  
In fan  
chamber  
&
starter  
collar  
If additional 3" PL Vent fittings are required, the overall  
length must be reduced by:  
Vertical 90o or T: 2.0'  
Vertical 45o:  
1.0'  
Horizontal 90o or T: 4.0'  
Horizontal 45o:  
2.0'  
Fig.46  
+ = Positive static pressure  
= Negative static pressure  
* Longruns of flex orPL vent pipe installeddirectly vertical fromtheflue stub  
may require more frequent cleaning due to fly ash falling off inside and  
collecting directly abovethe combustion blower outlet.  
Any use of horizontal venting will require more frequent cleaning. It is the  
responsibility oftheinstaller to makesure allflue configurationare accessible  
for cleaning.  
4" stainless steel flex vent piping is only allowed  
for use in masonry fireplaces and chimneys or factory  
built wood burning fireplaces with class A metal chim-  
neys. All pellet vent pipe whether flex type, PL or an-  
other approved type must be secured together either  
by means provided bypipe manufacturer or by3 screws  
at each joint.  
DO NOT INSTALL A FLUE DAMPER IN THE  
EXHAUST VENTING SYSTEM OF THIS UNIT.  
DO NOT CONNECT THIS UNIT TO A CHIMNEY  
FLUE SERVING ANOTHER APPLAINCE.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Venting  
22  
100% Outside Air Kit  
Designedfor 3" flex pipe  
Vent Pipe  
Be sure to use approved pellet vent pipe  
wall and ceiling pass- through fittings to go  
through combustible walls and ceilings.Be sure  
to usea starting collar to attach the venting sys-  
tem to the stove. The starting collar must be  
sealed to the vent pipe with high temp silicone  
caulking.  
4" stainless steel flex vent piping is only  
allowed for use in masonaryfireplaces and chim-  
neys or factorybuilt woodburning fireplaces with  
class A metal chimneys.  
100% Outside Air  
Kit# 1-00-674080  
1/8" Fiberglass Gasket  
2 3/8" IDFlex Pipe  
1/2" Silicone Gasket  
Intake Box  
Pellet venting pipe ( also known as PL vent  
) is constructed of two layers with air space be-  
tween thelayers. This air spaceacts as an insu-  
lator and reduces the outside surface tempera-  
ture to allow a clearance to combustibles of only  
3 inches. The sections of pipe lock together to  
form an air tight seal in most cases; however, in  
some cases a perfect seal is not achieved. For  
this reason and the fact that theAccentra Insert  
operates with a positive vent pressure, we  
specify that the joints also be sealed with clear  
silicone.  
Fig. 47  
Outside Air  
Outside air is optional (not required) except in  
mobile homes and where building codes require it  
to be installed. The benefit of outside air is mainly  
noticed in small, very tight houses.  
The outside air kit consists of a flue stub pipe,  
fiberglass gasket, silicone gasket, intake box and a  
section of flex pipe. See Fig. 47.  
An adjustable chimney intake extension, part #  
1-00-674104 is available to be used on masonry  
chimneys only. See Fig. 48.  
Additional information and diagrams can be  
found on pages 22 thru 26 under venting.  
To install outside air, use kit part number 1-10-  
674080. Follow the installation instructions provided  
with the kit.  
Adjustable Chimney  
Intake Extension  
Part# 1-00-674104  
Fig. 48  
HRV  
Wheninstalling ina house with a Heat Reclaim-  
ing Ventilation System (HRV) be sure the system is  
balanced and is not creating a negative pressure in  
the house.  
If the Accentra Insert is installed with the 100%  
outside air kit, the HRV should not have to be ad-  
justed.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
23  
Venting  
The chimney topmustbe capped  
to prevent rainand/or snow from  
enteringthe chimney.  
#1 Installing into an existing fireplace  
chimney (US & Canada)  
See Page 21. for information on  
the optional Harman Adjustable  
Stainless SteelIntake Extension.  
This method provides excellent venting with  
100% outside air which is the most efficient opera-  
tion of this unit. This method also provides natural  
draft in the event of a power failure.  
A 4 inch stainless steel flex pipe is needed for  
the flue pipe, and3" aluminumor Stainless Steel Flex  
Pipe is used for the intake.  
In Canada and some places in the US it is re-  
quired that the vent pipe extend all the way to the top  
of the chimney.  
Fiberglass insulation  
packed above the  
damper opening and  
sealed plate. (Not a  
Harman product.)  
Height of existinghearth  
Fig. 49  
The chimney top must be  
capped to prevent rain and/or  
snowfromenteringthe chimney.  
#2 Installing into an existing  
fireplace chimney (US & Canada)  
This method provides excellent venting for nor-  
mal operation. This method also provides natural  
draft in the event of a power failure.  
The damper area must be sealed with a steel  
plate or fiberglass. A cap should be installed on the  
chimney to keep out rain.  
Combustion air is provided from the living area  
and enters the feed system from around the wing  
and stove body spaces.  
Fiberglass insulation  
packed above the  
damper opening and  
sealed plate. (Not a  
Harman product.)  
Fig. 50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
24  
Venting  
The chimney top must be  
#3 Installing into an existing  
chimney (US only)  
capped to prevent rain and/or  
snowfromenteringthe chimney.  
This method provides excellent venting for nor-  
mal operation. This method also provides natural  
draft in the event of a power failure. If the chimney  
condition is questionable you may want to install a  
liner as in method #2.  
This is the minimum allowed vent pipe using 4"  
stainless steel flex pipe.  
The vent pipe must extend past the damper  
sealing area by at least 12 inches.  
Note: The fiberglass insulation must not be al-  
lowed to expand to the point that it covers the end of  
the flex pipe.  
Fiberglass insulation  
packed above the  
damper opening and  
sealed plate. (Not a  
Harman product.)  
The chimney should be capped with any style  
cap that will not allow rain or snow to enter.  
Fig.51  
Chimney top  
MUSTBE SEALED  
#4 Preferred method  
This method provides excellent venting for nor-  
mal operation and in a fireplace with inadaquate flue  
space, or a height of over 30 feet. A3" or 4" PL vent  
pipe should be used with an optional swivel flue stub.  
NOTE: The flue stub insulation wrap must still  
be used with this method. See page 13, Fig. 27 &  
29. With a 100% outside air kit the outside air can  
be installed in the same manner as the flue pipe.  
Fiberglass insulation  
packed above the  
damper opening and  
sealed plate. (Not a  
Harman product.)  
Stainless Steel  
Outside Air Inlet  
Cover  
3" Flex  
pipe  
part# 1-10-09542  
36"  
CAUTION  
KEEP COMBUSTIBLES (SUCH AS  
GRASS, LEAVES, ETC.) AT LEAST 3  
FEET AWAY FROM THE FLUE OUTLET  
ON THE OUTSIDE OF THE BUILDING.  
18" min.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
25  
Venting  
Installing the Accentra Insert into an  
existing factory built wood burning  
fireplace  
When installing the Accentra Insert into a factory  
built wood burning fireplace, several things need to be  
taken into consideration.  
The size of the fireplace opening. Will the unit fit  
into the opening? Many of these units have metal  
smoke shields inside the top that can be removed to  
gain height. Often the side and rear refractory can be  
removed to gain depth and width.  
Some factory built fireplaces have a firebox that  
is lower than the opening. Many have a bottom lip that  
is higher than the hearth. This is an issue with the  
Harman Accentra Insert since we do not have any-  
thing to fill the space between the bottom of the unit  
and the hearth. It would be the responsibility of the  
installer to supply something to fill this space and be  
strong enough to support the front of the insert.  
As for the size and position of the existing chim-  
ney and its damper system, the Harman Accentra In-  
sert has a swivel style flue stub that will allowthe stain-  
less steel flex pipe to exit into most factory built fire-  
places.  
Fig. 53  
OPTIONAL HOPPER CONFIGURATIONS FOR  
SMALLER FIREPLACE OPENINGS:  
The Harman Accentra Insert can be factory built with  
shorter hopper configurations.  
The standard requires a 24" opening. Part #1-90-00674  
Option1: Requiresa 22" opening height. Part #1-90-00675  
Option2: Requiresa 20" opening height. Part #1-90-00676  
Keep in mind the hopper capacities will decrease with the  
optional heights.  
Note: If the Harman Accentra Insert is installed into a factory built wood  
burning fireplace, this label (Harman part # 3-90-00675)MUST be attached  
to the altered fireplace.  
Fig. 54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
26  
Accentra Insert Zero Clearance Cabinet  
Harman Mantel System  
Harman Zero  
Clearance cabinet  
(top flue only)  
Part #1-00-674070  
Insert Body  
Insert Wing &  
Mounting Frame  
See your dealer for part details  
and installation instructions.  
Fig. 55  
Be su re to use ap-  
proved pellet vent pipe wall  
and ceiling pass- through  
fittings to go through com-  
bustible walls and ceilings.  
Be sure to use a starting col-  
lar to attach the venting sys-  
tem to the flue stub and seal  
the connection with high  
temperature silicone.  
Harman Zero Clearance Box  
Flue Pipe Support (optional)  
Part# 1-00-674119  
A minimum of a 1" hearth is  
required when using the  
Harman Zero Clearance box.  
When using 3" or 4" PL vent  
pipe, there must be a 3"  
clearance to combustibles.  
Fig. 56  
Combustible materials are allowed to touch the cabinet anywhere behind the front mounting flanges except vent  
clearance areas. The hearth substructure may be built of combustible material although a non-combustible hearth  
surface (tile, stone, metal, glass) must extend as far as shown on the UL label.  
AFTER THE INSTALLATION IS COMPLETED  
Download from Www.Somanuals.com. All Manuals Search And Download.  
27  
Venting  
Requirements for Terminating the Venting  
WARNING: Venting terminals must not be re-  
cessed into a wall or siding.  
I. The clearance to service regulator vent outlet  
must be a minimum of 6 feet.  
J. The clearance to a non-mechanical air sup-  
1
NOTE: Only PL vent pipe wall pass-throughs  
and fire stops should be used when venting through ply inlet to the building or the combustion air inlet to  
1
combustible materials.  
any other appliance must be a minimum of 48”.  
NOTE: Always take into consideration the ef-  
fect the prevailing wind direction or other wind cur- inlet must be a minimum of 10 feet.  
K. The clearance to a mechanical air supply  
1
rents will cause with flyash and /or smoke when plac-  
ing the termination.  
(with outside air installed, 6 feet )  
L. The clearance above a paved sidewalk or a  
In addition, thefollowing must be observed: paved driveway located on public property must be  
A. The clearance above grade must be a mini- a minimum of 7 feet.1,2  
mum of 18".1  
M. The clearance under a veranda, porch,deck  
1,3  
B. The clearance to a window or door that may or balcony must be a minimum of 12 inches.  
be opened must be a minimum of 48" to the side  
NOTE: The clearance to vegetation and other  
and 48" below the window/door, and 12" above the exterior combustibles such as mulch is 36” as mea-  
1
window/door.  
( with outside air installed, 18)  
sured from the center of the outlet or cap. This 36”  
radius continues to grade or a minimum of 7 feet  
C.A12"clearance to a permanentlyclosed win- below the outlet.  
dow is recommended to prevent condensation on  
the window.  
1CertainCanadian andor Local codes or regu-  
lations may require different clearances.  
D. The vertical clearance to a ventilated soffit  
2Avent shallnot terminate directly above a side-  
located above the terminal within a horizontal dis- walk or paved driveway which is located between  
tance of 2 feet (60 cm) from the center-line of the two single family dwellings and serves both dwell-  
terminal must be a minimum of 18".  
E. The clearance to an unventilated soffit must  
be a minimum of 12".  
ings.  
3Only permitted if veranda, porch, deck, or bal-  
cony is fully open on a minimum of 2 sides beneath  
F. The clearance to an outside corner is 11" the floor.  
from center of pipe.  
NOTE: Where passage through a w all, or  
G. The clearance to an inside corner is 12".  
H. Avent must not be installed within 3 feet (90  
cm) above a gas meter/regulator assembly when  
measured fromthe horizontalcenter-line of the regu-  
lator.1  
partition of combustible construction is desired,  
the installation shall conformto CAN/CSA-B365.  
(if in Canada)  
Inside  
Corner  
Detail  
Fixed  
Closed  
Fixed  
Closed  
Openable  
Openable  
= Air supply inlet  
= Vent terminal  
= Area where terminal is not permitted  
A
V
Download from Www.Somanuals.com. All Manuals Search And Download.  
28  
Maintenance - Cleaning Glass on View Door  
The unit should be out and cool to clean the door glass. It may not always be possible to allow the unit to  
cool off before cleaning. Therefore, if the unit is turned to the lowest setting about 1 hour before cleaning, it will  
make it possible to clean the glass with the unit in operation.  
Any glass cleaner with a high amonia content will work the best. Use only non-synthetic cleaning rags  
such as cotton or paper towels.  
CAUTION: Take care when spraying cleaner on the inside surface of the glass. The glass may be hot  
enough to cause undesirable fumes to fill the area around the unit very rapidly. Gloves and eye  
protection are recommended.  
Disposal of ashes: Ashes should be placed in a metal container with a tight fitting lid. The closed container of  
ashes should be placed on a non-combustible floor or on the ground, well away from all combustible materials,  
pending final disposal. If the ashes are disposed of by burial in soil or otherwise locally dispersed, they should be  
retained in the closed container until all cinders have thoroughly cooled.  
Soot and fly ash: Formation and need for removal. The products of combustion contain small particles of fly  
ash. The fly ash will collect in the exhaust venting system and will restrict the flow of the flue gases. Pellet fuels  
have different ash contents depending on what type of wood has been used to make the pellets. We  
recommend to clean the system after approximately 1 ton of pellets have been burned and judge from  
that how often the stove should be cleaned, remember if you change pellets it may change how often  
you have to clean your stove.  
Incomplete combustion such as occurs during start up, shutdown, or improper operation of the heater  
will lead to some soot formation, which will collect in the exhaust venting system. The exhaust vent should be  
inspected at least once every year to determine if cleaning is necessary.  
Replace glass  
only with high  
tem per ature  
ceramic glass.  
Inspect door gasket during  
Glass Gasket  
cleaning and inspection  
Fig. 57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
29  
Maintenance - Burn Pot  
Burn Pot Cleaning and Maintenance  
1. Scrape the top holed surface and sides of the  
burn pot down to auger tube.(Fig 58) It is not  
necessary to completely remove all material from  
the burn pot. The excess will be pushed out during  
the next use.  
2. Loosen the (2) wing thumb screws on the lower  
front angle of the burn pot. (Fig. 59)  
3. Lift off the clean-out cover (Fig.59) to open the  
bottom clean-out chamber. (Fig.60)  
DANGER  
Disconnect the power to the unit before  
removing cover.  
Fig.58  
4. Clean ashbuildup frominside the chamber while  
cover is off. Use the scraper to tap on the top front  
edge of the burn pot. This will help knock pieces of  
ash, loosened by the scraping process, down  
through the holes. It also helps knock scale off of  
the igniter element.  
Figure 60  
The igniter is made to be removable for  
service by insulated male/female wire connectors.  
These connections between the hot leads (the  
wires inside the burn pot) and the cold leads (the  
wires from the control board) are always pulled to  
the inside rear of the feeder body. (Not coiled  
inside the burn pot.)  
It is very important that these connections  
are to the inside rear of the feeder body. Also, the  
extra wire of the igniter wire service loop must be  
pulled out through the rear of the feeder and tied  
up so that it will not be damaged by any moving  
parts.  
Fig. 59  
Burn pot igniter  
DANGER  
Disconnect the power to the unit before  
removing cover.  
WARNING  
Use caution when cleaning burn pot clean-  
out chamber. Do not damage the high  
temperature igniter wires.  
Igniter hot leadwires  
(high temperature)  
Note: The hot lead/cold lead connection  
must always be pulled to the rear of the  
feeder body before operation.  
Fig. 60  
Viewed frombelowthroughthe ash pan opening.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30  
Maintenance - Cleaning  
There is a 2" square exhaust tube on each side (lower  
left and right corners) of the firebox. They can only be  
seen with the cast heat exchanger covers removed.  
Fig. 61  
Cleaning the Heat Exchanger tubes  
Using the cleaning brush provided, clean these tubes  
after every 1 ton of pellets are used.  
These tubes are an important part of the heat ex-  
changer. Efficiency will be lost if they are not properly  
maintained.  
Note: The brust will only extend into the fight side tube  
approximatlely 12”, but the left side tube requires the  
total length of the brush to be used.  
Fig. 62  
Cleaning the Heat Exchanger  
The accordion heat exchanger surfaces are the pri-  
mary source of heat transfer into the room. Therefore,  
it is very important to keep them clean from flyash and  
soot buildup.  
Primary Air Inlets  
The heat exchanger surfaces should be cleaned af-  
ter approximately every 1 ton of pellets are used.  
Use the scraper provided to clean all the way into the  
point.  
Note: An old paint brush works well to clean these  
surfaces.  
Note: The unit “must be cold” before using anything  
other than a wire brush.  
There are 2 primary air inlet holes on the rear flange  
of the burnpot. They should be checked for blockage  
and cleaned with a vacuum if necessary. Note: The  
bottom of the flame guide has 2 notches that match  
the holes.  
Fig. 63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
31  
Maintenance - Cleaning  
Feeder Chamber  
This chamber may get a buildup of fines from the feeder  
mechanism movement. This area should be checked and  
cleaned at least once a year.  
To remove the feeder cover:  
Remove the 5/16" wing nut.  
Slide the cover off of the threaded stud.  
Inspect and clean the inner chamber if necessary. See  
Fig. 65.  
Reinstall the cover making certain it is centered on the  
feeder body and tighten as tightly as you can by hand.  
The combustion blower is made to be removed easily for  
inspection and cleaning. See Fig. 67.  
The combustion blower is mounted on a precision cut  
gasketless mounting plate. This plate is held into place  
with (3) thumb screws. See Fig. 67.  
Feeder  
rear  
chamber/  
clean out  
cover  
ESP  
5/16"  
wing nut  
Fig. 64  
To remove the combustion blower:  
Turn the thumb screws counterclockwise approximately  
5 turns. Rotate the entire assembly counter clockwise  
until the points of the retaining slots are visible.  
Remove the blower assembly with the fan blade by  
pulling it directly away from the blower housing.  
The cord on the motor is long enough to allowthe motor  
to be set down on the black plastic fan cover. This allows  
for easy access to inspect and clean the area. See Fig.  
66.  
Pellet  
Metering  
slide plate  
Withthe blower assembly out, inspectionshouldbe done  
on the surfaces of the blower assembly and the housing  
openingwhere theymeet. Thesesurfaces MUST be clean  
and free from dirt, grit, flyash, soot or nicks in the metal.  
This gasketless seal relies on an extremely close  
tolerance. Therefore, anythingother thana cleanjoint may  
cause exhaust gases and/or flyash to escape.  
The assembly can only be reinstalled in one position:  
with the motor winding in the upward location. See Fig.  
67. The mounting plate will not allowfor anyother position.  
Alwyas make sure that the assembly is fully seated and  
the (3) thumb screws are tightened before operating the  
unit.  
Possible pellet  
fines buildup  
area.  
Fig.65  
Close  
l
Tolerance  
l
Mating  
Surface  
Close  
l
Tolerance  
l
Fig. 67  
Fig. 66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
33  
Trouble-Shooting  
FEEDER DOES NOT FEED  
3. Something is restricting fuel flow.  
4. Feed motor or draft motor has failed.  
5. Power failure or blown fuse.  
1. No pellets in hopper.  
2. Firebox draft may be too low for low draft pres-  
sure switch in feeder circuit to operate.Check for  
open doors, loose or missing gasket on doors or  
hopper lid, faulty pressure switch.  
3. Feed motor will not run until ESP  
senses 165 deg. F. Maybe you did not put  
enough pellets in the burn pot before lighting the  
fire.  
SMOKE IS VISIBLE COMING OUT OF VENT  
1. Air-fuel ratio is too rich.  
A. Feed rate too high.  
B. Draft too low caused by a gasket leak.  
LOW HEAT OUTPUT  
4. Something is restricting flow in the hopper or  
causing the slide plate to stick.  
5. Feed motor has failed.  
1. Feed rate too low  
2. Draft too low because of gasket leak.  
3. Poor quality or damp pellets  
4. Combination of 1. and 2.  
PARTIALLY BURNED PELLETS  
1. Feed rate too high.  
Helpful Hints  
2. Draft too low. (Check burn pot clean out slide  
and door gasket).  
3. Burn pot or heat exchanger tubes may need to  
be cleaned.  
Cleaning Burn Pot  
Whenever your stove is not burning, take the op-  
portunity to scrape the burn pot to remove carbon  
buildup. A vacuum cleaner is handy to remove the resi-  
due. Be sure the stove is cold if you use a vacuum.  
Carbon buildup can be scraped loose with the fire  
burning using the special tool provided with your stove.  
Scrape the floor and sides of the burn pot. The carbon  
will be pushed out by the incoming fuel. Always wear  
gloves to do this.  
4. Combination of all the above.  
5. #6 status blink: A 6 blink control board status  
indication is caused by poor or incomplete com-  
bustion. The Automatic Ignition circuit board has  
the ability to track the combustion through feed  
settings and ESP temperatures. When the control  
board has calculated poor or incomplete combus-  
tion it will shut down the unit as a safety feature.  
(Poor or incomplete combustion is a contributer of  
creasote which may cause a chimney fire)  
A 6 blink status may be caused by several things:  
1. Blocked or partially blocked flue.  
2. Blocked or partially blocked inlet air.  
a. backdraft damper on the inlet pipe may be  
stuck closed.  
b. if outside air is installed the inlet cover may be  
blocked.  
3. The air chamber under the burnpot may be filled  
with fines and small bits of ash.  
4. The holes in the burnpot may be getting filled  
with ash or carbon buildup.  
5. Combustion blower fan blades may need  
cleaned.  
Removing Ashes  
Turn the Temp Dial to number 1 approximately 30  
minutes before removing ashes. This will result in a  
cooler stove and ash pan.  
Maximum Feed Adjuster settings are not needed  
in most cases. Operating in the normal range (#4) is  
recommended when maximum heat output is not re-  
quired. The ESP probe prevents the stove from being  
over-fired.  
Keep the stove free of dust and dirt.  
Fuel  
Pellet fuels are put into 3 categories in terms of  
ash content. Premium at 1% or less, Standard at 3% or  
less and all others at 3% or more.  
The Accentra is capable of burning all 3 categories  
of pellets due to a patented feeder and burn pot system.  
It should be noted, however, that higher ash con-  
tent will require more frequent ash removal and may  
provide less BTU's per pound. Normally, standard and  
high ash pellets cost less than premium pellets and can  
be cost effective when burned in the Accentra.  
The moisture content must not exceed 8%. Higher  
moisture will rob BTU's and may not burn properly.  
6. Combustion intake assembly not properly  
latched.  
7. No fuel in hopper  
SMOKE SMELL  
Seal the vent pipe joints and connection to frame  
with silicone.  
FIRE HAS GONE OUT  
1. No pellets in hopper.  
2. Draft setting is too low.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
34  
Specifications  
Weight  
450 lbs.  
Blower  
180 cfm  
Hopper Capacity  
Fuel  
57 lbs. (24" hopper #1-90-00674)  
Wood Pellets  
Outside Air Size  
Fuse Rating  
BTU Range  
Feed Rate  
3 inches  
6 amp  
0 to 42,000  
.75 lbs./hr. on minimum(on maintenance)  
5 lbs./ hr. on maximum  
4 inch Pellet Vent Pipe, standard,  
3 inch Pellet Vent Pipe, option  
Vent Size  
Maximum Wattage 440 Watts (Start cycle and test)  
Start Cycle Wattage 340 Watts  
Normal Run Wattage 255 Watts  
Download from Www.Somanuals.com. All Manuals Search And Download.  
35  
Accentra Insert Wiring Diagram  
Download from Www.Somanuals.com. All Manuals Search And Download.  
36  
Accentra Insert Feeder Parts  
Download from Www.Somanuals.com. All Manuals Search And Download.  
37  
Accentra Insert Parts List  
Description  
Part Number  
Hopper Lid Gasket  
(5.25',1/2 x 3/8" silicone w/PSA)  
Ignitor Element Assembly  
Wiring Harness  
Burn Pot Weldment  
Heat Exchanger Cover (2)  
Center Medallion (1)  
Arrow Scraper  
Flame Guide  
Gear Motor  
Thermister Probe  
Room Sensor  
3-44-375501  
1-10-06620  
3-20-08727  
1-10-00675  
3-00-674050  
3-00-674060  
2-00-773850  
3-00-674069  
3-20-60906  
3-20-00744  
3-20-00906  
3-20-05237  
Circuit Board G5237  
25/8" Black CCW Fan Blade(auger motor) 3-20-2046399  
Differential Switch  
3-20-9301  
43/4" SinglePaddleCombustion FanBlade 3-21-00661  
Combustion Blower  
Distribution Blower  
Tailpipe Insulator  
White/Black Control Knob (3)  
Control Knob Shaft (3)  
Front Glass w/gasket  
Docking Gasket (red silicone)  
Wood Handle  
Wiring Diagram  
Control Panel Sticker  
Owner's Manual  
Hopper Lid Label  
Ash Pan Assembly  
Cast Hopper Lid  
3-21-08639  
3-21-47120  
3-44-674102  
3-31-00968  
3-31-00982  
3-40-674090  
3-44-06108  
3-40-00123  
3-90-09321  
3-90-06655  
3-90-00674  
3-90-08416  
1-10-674030  
3-00-674059  
3-31-5500  
Ball Spring Plunger (3)  
Glass Clips (4)  
Power Cord  
Flue Brush  
3/8" Black Door Gasket (5 1/2 ft.)  
2-00-249140  
3-20-674200  
3-40-00126  
3-44-37525  
Options:  
Outside Air Assembly  
Log Kit  
Zero Clearance Cabinet  
1-10-674080  
1-00-674099  
1-10-674070  
Zero Clearance Box Flue Pipe Support 1-00-674119  
4" PL vent stub  
3" PL vent stub  
1-00-674040  
1-00-674039  
See page 35 for  
Feeder Part Numbers  
Download from Www.Somanuals.com. All Manuals Search And Download.  
38  
Harman Gold Warranty  
HARMAN GOLD WARRANTY  
6 YEAR TRANSFERABLE LIMITED  
WARRANTY (Residential)  
1YEAR LIMITED WARRANTY (Commercial)  
Harman Stove Company warrants its products to be free from defects in material or workmanship, in normal use and  
service, for a period of 6 years from the date of sales invoice and for mechanical and electrical failures, in normal use and  
service, for a period of 3 years from the date of sales invoice.  
If defective in material or workmanship, during the warranty period, Harman Stove Company will, at its option, repair or  
replace the product as described below.  
The warranty above constitutes the entire warranty with respect to Harman Stove Company products. HARMAN STOVE  
COMPANY MAKES NO OTHER WARRANTY, EXPRESSED OR IMPLIED, INCLUDING “ANY” WARRANTY OF  
MERCHANTABILITY, OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. No employee, agent, dealer, or  
other person is authorized to give any warranty on behalf of Harman Stove Company. This warranty does not apply if the  
product has been altered in any way after leaving the factory. Harman Stove Company and its agents assume no liability for  
“resultant damages of any kind” arising from the use of its products. In addition, the manufacturer and its warranty administra-  
tor shall be held free and harmless from liability from damage to property related to the operation, proper or improper, of the  
equipment.  
THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF.  
THESE WARRANTIES APPLY only if the device is installed and operated as recommended in the user’s manual.  
THESE WARRANTIES WILL NOT APPLY if abuse, accident, improper installation, negligence, or use beyond rated  
capacity causes damage.  
HOW TO MAKE A CLAIM - Any claim under this warranty should be made to the dealer from whom this appliance was  
purchased. Then contact is made with manufacturer, giving the model and serial numbers, the date of purchase, your dealer’s  
name and address, plus a simple explanation of the nature of the defect. Extra costs such as mileage and overtime are not  
covered. Nuisance calls are not covered by these warranties.  
THIS WARRANTY IS LIMITED TO DEFECTIVE PARTS - REPAIR AND/OR REPLACEMENT AT  
HARMAN STOVE COMPANY’S OPTION AND EXCLUDES ANY INCIDENTAL AND CONSEQUENTIAL  
DAMAGES CONNECTED THEREWITH.  
WARRANTY EXCLUSIONS: Failure due, but not limited to, fire, lightning, acts of God, power failures and/or surges,  
rust, corrosion and venting problems are not covered. Damage and/or repairs including but not limited to; remote controls,  
filters, fuses, knobs, glass, ceramic brick panels, ceramic fiber afterburners, door packing, tile, ceramic log sets, paint, batteries  
or battery back-up and related duct work are not covered. Also excluded from this warranty are consumable or normal wear  
items including but not limited to; flame guides, grates, coal bars, afterburner hoods, fire brick, gaskets. Additional exclusions  
for corn stoves are burnpot housing weldment, burnpot grate weldment (pellet or corn), burnpot front plate (pellet or corn),  
burnpot front plate lock, corn auger extension, ceramic insert, and ceramic insert plate. Additional or unusual utility bills incurred  
due to any malfunction or defect in equipment and the labor cost of gaining access to or removal of a unit that requires special  
tools or equipment are not covered. Maintenance needed to keep the stove in “good operating condition” is not covered. This  
includes, but is not limited to, cleaning, adjustment of customer controls and customer education. Labor, materials, expenses  
and/or equipment needed to comply with law and/or regulations set forth by any governmental agencies are not covered.  
This Warranty provides specific legal rights and the consumer may have other rights that vary from state to state.  
In the event of change in ownership, the remaining portion of this warranty may be transferred to the new owner by  
sending the new owner information to the Harman Stove Company.  
PLEASE READ THE LITERATURE BY THE MANUFACTURER FOR THE VARIOUS ACCESSORY DEVICES.  
THE MANUFACTURER WARRANTS THESE ACCESSORY DEVICES, NOT HARMAN STOVE COMPANY OR THEIR  
WARRANTY ADMINISTRATOR. FURTHERMORE, THESE ACCESSORY DEVICES MUST BE INSTALLED AND  
USED ACCORDING TO THE RECOMMENDATIONS OF THE MANUFACTURER.  
REMEDIES - The remedies set forth herein are exclusive and the liability of seller with respect to any contract or sale or  
anything done in connection therewith, whether in Contract, in tort, under any warranty, or otherwise, shall not, except as herein  
expressly provided, exceed the price of the equipment or part of which such liability is based.  
CLARIFY - The above represents the complete warranty, which is given in connection with stoves, manufactured by  
Harman Stove Company. No other commitments, verbal or otherwise, shall apply except by a written addendum to this  
warranty.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Baby Accessories PD167532A User Manual
Haier Freezer BD 478A User Manual
HannsG Computer Monitor HW173AB User Manual
Hasbro Games Talking Toy Phone User Manual
Heatcraft Refrigeration Products Air Compressor SRN User Manual
Honeywell Thermostat CT3697 User Manual
Hotpoint Cooktop CEM 645 D C User Manual
HP Hewlett Packard Refrigerator HP 8901A User Manual
Huffy Fitness Equipment M5800152 User Manual
IMC Networks Computer Hardware MCPC 10 100 User Manual