Greenheck Fan Ventilation Hood ERV User Manual

Energy Recovery Ventilator  
Model ERV  
• Commercial • Institutional  
• 400 to 12,000 cfm  
• 1.5 in. wg external  
static pressure  
June  
2010  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model ERV  
How does an energy recovery wheel work?  
The basic objectives for providing acceptable indoor air quality (IAQ) are to  
control indoor contaminates levels while maintaining desired indoor air  
temperature and humidity. Compliance with the prescribed ventilation rates  
in ASHRAE Standard 62 appear to satisfy the contaminant issue. However,  
simply increasing outdoor air (OA) requirements with “traditional” HVAC  
systems may not address the humidity issue properly and often leads to  
significant energy cost increases.  
0.20  
0.25  
0.30  
0.35  
0.40  
SENSIBLE HEAT RATIO = Qs / Qt  
1.15  
1.10  
1.05  
1.00  
0.95  
0.90  
0.85  
0.80  
170  
160  
150  
140  
130  
120  
110  
100  
90  
0.45  
0.50  
80  
80  
0.55  
0.60  
75  
75  
70  
The best solution for most commercial and institutional facilities  
will include an enthalpy wheel product. The enthalpy wheel  
70  
0.75  
0.70  
0.65  
0.60  
0.55  
0.50  
0.45  
0.40  
0.35  
0.30  
0.25  
0.20  
0.15  
0.10  
0.05  
0.65  
0.70  
transfers temperature and moisture properties from one  
65  
65 0.75  
0.80  
airstream to another. The result is capturing the cooling and  
heating energy before it leaves the HVAC system.  
80  
0.85  
60  
60  
0.90  
70  
0.95  
55  
1.00  
55  
50  
60  
Moving through the unit, the return and supply airstreams  
50  
50  
pass on opposite sides of a divider panel. The  
45  
45  
40  
enthalpy wheel rotates between the airstreams  
transferring up to 75% of the energy  
40  
40  
35  
30  
35  
30  
30  
present in the exhaust airstream to  
the supply.  
25  
20  
25  
20  
20  
15  
10  
10  
10  
0
5
0
-5  
-10  
-5  
0
5
10  
15  
20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
95  
100  
105  
110  
115  
120  
DRY BULB TEMPERATURE - °F  
Enthalpy Wheel  
Filters  
Supply Air to Building  
Outdoor Air Weatherhood  
Outdoor Air  
Utilizing an enthalpy wheel to precondition the outdoor air,  
narrows the operational range of outdoor air conditions  
which the building’s HVAC equipment is designed to  
temper. It is this reduction in the outdoor air range that  
allows for size reduction in heating and cooling equipment  
and reduced energy costs.  
Supply  
Blower  
Exhaust Blower  
Return Air From Building  
Filters  
Exhaust Weatherhood  
Exhaust Air  
Certifications  
ERV’s construction is matched with extensive in-house testing and third-party verification of  
performance and safety.  
Greenheck certifies that the ERV models shown herein are licensed  
Licensed to bear the AMCA seal for  
Air Performance  
to bear the AMCA seal. The ratings shown are based on tests and  
procedures performed in accordance with AMCA Publication 211 and  
comply with the requirements of the AMCA Certified Ratings Program.  
Unit is ETL Listed — all internal electrical  
components are factory wired to a single-point  
power connection  
Every unit is tested at the factory before it is shipped to the job site.  
Energy recovery wheels are certified by the ARI Air-to-Air Energy  
Recovery Ventilation Equipment Certification Program in accordance  
with ARI Standard 1060. Actual performance in packaged equipment  
may vary. Certified ratings are available in the Certified Product  
aspx  
ARI Standard 1060 certified energy wheel  
performance assures the ERV model will function  
as required in demanding environments  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
What is the Benefit with  
Greenheck Energy Recovery?  
For the Building Owner  
• Improved Indoor Air Quality (IAQ)  
Introducing fresh, outdoor air to a building is a key component to sustaining excellent indoor air quality.  
Outdoor air can be very expensive to heat and cool, but the ERV unit can provide an economical approach to  
delivering outdoor air into a building.  
• Energy Savings = Quick Payback  
The energy recovery unit provides energy savings throughout the year. In the summer, the energy recovery  
unit removes heat and moisture out of the outdoor air, but in the winter, heat and moisture are added back into  
the fresh airstream. When you combine the energy savings from summer and winter operation, they lead to a  
very fast payback period. In most parts of the United States, the payback is less than 2 years!  
Equipment Reduction Using Energy Recovery on 3000 cfm Outdoor Air  
Cooling  
Equipment  
Reduction  
(tons)  
Annual  
Summer  
Cooling  
Savings  
Heating  
Equipment  
Reduction  
(MBH)  
Annual Winter  
Heating  
Approximate  
Payback  
Gas Price* Electric Cost**  
Savings  
(Years)***  
Boston, MA  
Minneapolis, MN  
St. Louis, MO  
Raleigh, NC  
Houston, TX  
Tampa, FL  
1.68  
1.14  
1.34  
1.48  
1.10  
1.59  
1.21  
1.13  
0.1495  
0.0712  
0.0558  
0.073  
8.72  
9.55  
12.1  
11.3  
13.0  
13.1  
4.17  
9.40  
226  
161  
356  
424  
1701  
1779  
2
161  
217  
173  
138  
111  
89  
4544  
3261  
3088  
2790  
1089  
988  
0.78  
0.88  
0.35  
0.57  
0.22  
0.21  
2.34  
1.95  
0.1011  
0.0974  
0.071  
Portland, OR  
Phoenix AZ  
123  
161  
2930  
1478  
0.0766  
271  
*
Average gas price (dollars per therm) per region in the first six months of 2007 (source: Energy Information Administration)  
** Average electricity cost (dollars per kWh) in March of 2007 (source: Energy Information Administration)  
*** Assumptions: $3/cfm energy recovery cost; $650/ton avoided cooling equipment cost; 75.6% effective energy wheel; 12 hrs/day 5 days/week operation  
For the Maintenance Personnel  
• Low Maintenance Equipment  
Energy Wheel: The most important component in the ERV is the energy wheel.  
This device should be inspected and cleaned as necessary, which will vary by  
application and environment. Any cleaning that is required is simplified by the  
easy accessible wheel with removable segments. Cleaning requires no special  
equipment (light detergent and water) and can be performed in a location that is  
convenient to you.  
Fans: The blowers that are used in the ERV are centrifugal, forward-curved- type  
fans. These fans come with easily adjustable pulleys, belt tension bolts and  
permanently sealed bearings.  
Filters: The 2-inch, 30% efficient MERV 8 filters that are included with the unit are  
designed for easy access and removal.  
• Quality Construction  
Greenheck has focused on the manufacturing and unit designs to create well-  
constructed equipment. Investments in automated manufacturing processes  
provide accurate and repeatable results, giving excellent part fit and unit strength.  
Incorporation of innovative designs add to the quality, while keeping maintenance  
work simple to perform.  
• Long-Lasting Equipment  
Because of our high-quality construction, the equipment that goes to the field is made to last. As reassurance  
to the customer, each ERV unit carries a 1-year warranty from the ship date and the wheel components  
(segments, cassette, belt, and pulleys) carry a 5-year warranty.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
What is the Benefit with  
Greenheck Energy Recovery?  
For the Design Engineer  
• Adhering to ASHRAE Guidelines  
ASHRAE Standard 90.1 provides design guidelines regarding when it is most beneficial to use energy  
recovery. Depending upon your geographic location and the percentage of outdoor air in the application,  
ASHRAE recommends when to use energy recovery. An important part of this guideline is that when energy  
recovery is recommended, the device should be a minimum of 50% total (sensible and latent) effectiveness  
according to ARI 1060 testing procedure.  
ASHRAE Standard 189.1 provides high performing building design guidelines. This requires even higher energy  
recovery device performance than Standard 90.1. When energy recovery is recommended, the device shall be  
a minimum 60% total (sensible and latent) effectiveness according to ARI 1060 testing procedure.  
• LEED Certification Credits  
For Green Building designs, the ERV offers an excellent way to acquire credits in both  
Energy and Atmosphere (EA) and Indoor Environmental Quality (EQ) categories towards a  
LEED certification.  
Prepared to Support  
Green Building Efforts  
• CAPS Program  
CAPS is Greenheck’s comprehensive product selection program. The CAPS program was  
developed with ease of use and fast selections in mind. There is also useful information  
available for making selections and educating people who are new to energy recovery  
technology. CAPS also provides submittals which includes unit overview, electrical  
information, fan charts, arrangements, engineering drawings, payback information, and  
psychrometric processes.  
• CSI Specifications  
After a unit has been selected in CAPS, an accurate unit specification is available for use in the job  
specification. These specifications have been recently updated to the CSI format.  
• Industry Certification  
To ensure performance on the job site, Greenheck emphasizes the need for the 3 major industry certifications  
for energy recovery units: AMCA Licensed for Air Performance, ETL Listed for safety, and ARI Certification on  
the energy recovery wheel.  
For the Contractor  
• Easy Installation  
- Lifting Lugs  
Lifting Lugs  
- Single-Point Power  
- Bolt-doors for limited clearance applications  
These are just a few of the built-in features to make the installation process quick and easy. Our  
comprehensive Installation, Operation, and Maintenance Manuals are also available online, so the information  
you need is quick and easy to obtain.  
• Product Approval  
Form, fit and function, the ERV was designed to operate in commercial and institutional applications. With over  
a decade of installations specific to the energy recovery market, Greenheck’s energy recovery product line is  
well known and accepted throughout the industry.  
• 1 — 5-Year Warranty  
Our 1-year unit warranty and 5-year energy recovery wheel warranty lets you to rest easy knowing that we  
stand behind our product.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Accessories  
Low-Leakage Dampers — Internally mounted for  
Roof Curbs  
both supply and exhaust  
For a cohesive fit between  
Where code requires low-leakage  
the ERV and your building,  
dampers they can be provided to keep  
the cold weather out in the winter,  
or hot and humid weather out during  
the summer. Since the dampers are  
wired to a single-point power source,  
a simple run command sent to the  
unit powers the dampers open. When your unit is off  
during unoccupied hours, the dampers close to keep  
the outdoor air out.  
Greenheck offers a pre-  
engineered curb design. They  
are available with duct adaptors  
to simplify field duct installation  
and get the unit up and running more quickly.  
Double Wall Construction  
The supply and exhaust side are internally lined with  
20 gauge galvanized steel.  
Filters  
Weatherhoods  
Standard size 2-inch pleated, medium efficiency filters  
and filter racks are available for supply and/or exhaust  
airstreams.  
A louvered intake hood with 2-inch aluminum mesh  
filters and exhaust hood with an integral backdraft  
damper are available.  
Model  
Filter Size Quantity  
ERV-251  
ERV-361  
ERV-521  
ERV-581  
ERV-522  
16 x 25  
16 x 20  
16 x 25  
16 x 20  
16 x 25  
1
2
3
6
7
Hinged Access Doors  
Panel side doors are a standard feature on all  
units. Hinged access doors are available on models  
ERV-361, -521, -581, -522, and -582. Access doors  
are removable hinge type with lift and turn latches for  
access to internal components.  
All dimensions shown in inches.  
Remote Panel  
Air Filtration — High-Efficiency Filters  
With the optional remote panel you have control and  
the information you want. Monitoring lights, on/off  
time-clock control, or on/off/auto switch are a few of  
the available options. So whether you want to control  
the unit operation via a 7-day time clock or simply  
want to monitor unit performance, the remote panel is  
the option that you’ll need.  
Unit is standard with 2-inch, MERV 8,  
30% efficient filters. Optional MERV 13,  
85% efficient filters are available to help  
meet additional LEED requirements or  
simply improve indoor air quality.  
Painted Exterior  
For added aesthetics and a  
long-lasting finish, Greenheck  
offers many different paint  
DESERT  
SAND  
PERMATECTOR™  
options. Pre painted coatings  
in either Gray or Desert Sand  
offer economical options in customizing your unit. If  
a more specific color is desired, we also offer a wide  
variety of colors to meet your specific needs.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Accessories  
Dirty Filter Sensors  
CO2 Sensor  
Filters require scheduled maintenance to improve  
air quality and system efficiency. A dirty filter sensor  
A good indicator for building health is  
carbon dioxide (CO2). Greenheck offers a  
allows you to minimize maintenance frequency to only CO2 sensor, that can be used to engage  
when it is needed. The dirty filter kit senses when  
the filters are dirty and sends a signal to our built-in  
control center. Greenheck offers an optional remote  
control panel and a “clogged filter” light to tie the  
signal into.  
the unit based on CO2 levels, or it can  
increase or decrease airflows through  
the use of a variable frequency drive  
(VFD) on the blowers. The CO2 sensor  
can be unit mounted or space mounted  
depending on your application.  
Rotation Sensor  
Service Outlet  
Adding a wheel rotation sensor to the unit assures  
you that the energy wheel is operating properly. The  
sensor sends a signal to the control center of the  
unit in the rare event that the wheel stops rotating.  
While performing minimal maintenance on your ERV, a  
service outlet can provide power when and where it’s  
needed. Shipped loose, the outlet can be mounted in  
Greenheck offers an optional remote control panel and the correct location for your building.  
a “wheel rotation” light to tie the signal into.  
Vapor-Tight Lights  
Factory Mounted Sensors  
Access doors provide natural lighting during the day,  
Amp Draw, Pressure, Temperature: Greenheck offers  
factory mounted sensors that are wired back to the  
control center, so you can get the information you  
need to know, exactly where you need to measure  
it. These sensors can be used to simply monitor unit  
operation or to actively control the unit with controls  
by others.  
but there may be times when more light is needed  
to see properly inside the unit. To increase bulb life  
and to also protect the bulb, Greenheck offers a  
vapor-tight light.  
Blower VFD’s  
Variable frequency drives are a great  
tool to control airflow to the space  
or to maintain duct pressures. With  
this optional feature, two VFD’s are  
utilized, one per fan for independent  
and flexible control.  
Amp Monitor  
Blower amp draw can be monitored  
through the use of an amperage  
sensor. These sensors allow for  
either an analog or digital output  
based on your system needs.  
Wheel Pressure Sensors  
In each airstream, a pressure  
sensor is available to monitor  
wheel operation. Wheel pressure  
can be used to indicate a buildup  
of frost during the cold winter  
months or can be used as a CFM  
gauge as the energy wheel is a  
laminar flow device (i.e. a specific  
pressure equals a specific CFM).  
Temperature Sensors  
Wheel performance can be  
determined with factory mounted  
temperature sensors. Every  
compartment can be monitored to  
know how your unit is operating.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Accessories  
Economizer Control (Free Cooling)  
Take advantage of cool outdoor air to handle space loads. A call for cool air is sent to the unit’s control center  
which triggers one of a few different options to bring in fresh cool air:  
Energy Wheel On/Off  
The wheel cycles off when it’s in the free cooling range (temperature or enthalpy), and  
cycles on when outdoor air is too warm or too cold. This option is recommended when the  
air is being supplied to an air handling unit or duct heater, and not directly to the space.  
Energy Wheel Modulation  
The wheel speed modulates to maintain a 55°F discharge temperature. Above 55°F,  
the wheel is off up to a high-limit temperature setting (typically 70°F). This option is  
recommended when the air is supplied directly to the space from the ERV or when more  
precise temperature control is needed.  
Frost Protection  
Cold climates, in combination with higher indoor humidity levels, may cause frost to form on the energy wheel  
during normal operation. To protect against frost, we measure the outdoor temperature and the energy wheel  
pressure drop. When it’s cold enough and the wheel pressure is increasing, the wheel is frosting. Only then will  
the frost methods described below engage. See the “Frost Control Strategy Recommendations” chart on this  
page for which of the three Greenheck frost methods we recommend for your building.  
Timed Exhaust Frost Control  
The supply blower cycles on and off based on a  
factory provided timer. With the supply blower  
off, the warm exhaust air melts the frost. Once the  
wheel pressure decreases, the supply blower turns  
back on.  
Frost Control Strategy Recommendations  
Recommended  
Winter Outside Air  
Design  
Winter Indoor Air  
Design  
Frost Control  
Strategy  
Modulating Wheel Frost Control  
≥ 10°F (-12.2°C)  
≤ 50% RH  
≤ 35% RH  
≤ 50% RH  
≤ 35% RH  
Any RH  
None  
≥ -5°F (-20.6°C) <  
10°F (-12.2°C)  
A factory installed variable frequency drive (VFD)  
slows the wheel down making it less effective.  
In other words, the slow rotating wheel spends  
enough time in the warm exhaust airstream to melt  
the frost. Once the wheel pressure decreases,  
it returns to full speed. Both blowers operate  
continuously during this frost mode. Modulating  
wheel frost control is available on all sizes except  
the ERV-251.  
Timed Exhaust  
≥ 10°F (-12.2°C)  
≥ -5°F (-20.6°C) <  
10°F (-12.2°C)  
Electric Preheat  
≥ -5°F (-20.6°C)  
Preheat Frost Control  
An electric preheater is built into the ERV outdoor air intake. When frost occurs, the heater engages, and  
increases the outdoor air temperature above the frost threshold to melt the wheel. Once the pressure  
decreases, the heater shuts off.  
The map at left indicates the frost control  
options, if any, that are appropriate based  
on climactic conditions during typical  
16 hour per day operation.  
Preheat Frost Control Recommended*  
Timed Exhaust Frost Control Recommended*  
No Frost Control Needed  
*Modulating Wheel Frost Control can also be used in these areas.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Arrangements  
Top View  
Interior  
Supply Air  
This compact design is ideal for the space limitations  
that routinely complicate interior installations.  
Arrangement A  
Specify Arrangement A for interior mounting. All ERV  
sizes are available in this arrangement. Fig. 1 is typical  
for ERV-251, -361, -521, and -581.  
Exhaust Air  
Fig. 1  
Arrangement A - Interior Mounted  
Exterior  
Where roof mount or pad mount installations are  
preferred, Greenheck offers three arrangements to  
provide the flexibility to simplify system design and  
installation. Louvered intake hood and an exhaust hood  
are standard on Arrangements B, C and D. The housing  
and hood design minimize re-entrainment of exhaust  
air.  
Top View  
Arrangement B  
Ideal for roof mount installations where both exhaust and  
supply ducts penetrate the roof deck and attach to the  
bottom of the energy recovery ventilator. Fig. 2 is typical  
for ERV-251, -361, -521, and -581.  
Supply  
Air  
Exhaust Air  
Arrangement C  
Ideal for roof mount installations where the supply  
airstream is to be routed directly into a rooftop HVAC  
Exhaust  
Hood  
Fig. 2  
Intake Hood  
unit. Exhaust air enters the ERV from below.  
Arrangement B - Roof Mounted  
Arrangement D  
Suited for pad mounting, where both the exhaust and  
supply ducts connect to the end of the ERV.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions  
ERV-251, ERV-361, ERV-521, ERV-581  
Exterior Dimensions  
Duct Dimensions  
Weight  
(lbs.)  
340  
860  
1290  
1470  
Model  
A
B
C
D
E
8
15  
15  
22  
F
G
K
634  
838  
1034  
16  
L
7
1112  
1312  
1834  
Q
P
ERV-251  
ERV-361  
ERV-521  
ERV-581  
46  
62  
67  
75  
34  
51  
67  
70  
27  
34  
44  
67  
12  
18  
16  
16  
10  
18  
24  
22  
16  
18  
24  
27  
10  
19  
26  
28  
16  
18  
26  
48  
All dimensions shown are in inches. Weight assumes outdoor unit with filters, weatherhoods, and supply damper.  
Arrangement A  
Arrangement B  
Outdoor Air Discharge  
L x K  
Outdoor Air Discharge  
L x K  
B
A
Exhaust Air Inlet  
F x G  
Outdoor Air Inlet  
Q x P  
D
C
C
E
Exhaust Air Inlet  
F x G  
A
B
Exhaust Air Discharge  
L x K  
Intake Hood  
Exhaust Hood  
Arrangement C  
Arrangement D  
Outdoor Air Discharge  
L x K  
Outdoor Air Discharge  
L x K  
B
A
B
A
D
D
C
C
E
E
Exhaust Air Inlet  
F x G  
Exhaust Air Inlet  
F x G  
Intake Hood  
Intake Hood  
Exhaust Hood  
Exhaust Hood  
Service Clearance  
Model  
Exhaust Side  
Supply Side  
Installation must allow clearance for access to the energy  
recovery wheel on the supply side. Minimum clearances  
are shown in the table at right. Page 4 shows the side  
panel that enables wheel access.  
ERV-251  
ERV-361  
ERV-521  
ERV-581  
30  
30  
40  
40  
32  
44  
60  
65  
All dimensions shown are in inches.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions  
ERV-522 and ERV-582  
Exterior Dimensions  
Model  
Duct Dimensions  
Weight  
(lbs.)  
A
ERV-522S 124  
ERV-522H 124  
ERV-582H 146  
B
C
D
16  
E
19  
F
G
H
J
K
L
1858  
22  
Q
P
84  
84  
97  
64  
64  
77  
48  
48  
60  
25  
25  
28  
26  
26  
31  
36  
36  
38  
16  
19  
23  
60  
60  
70  
25  
25  
30  
3230  
3230  
3700  
16  
1712  
19  
2634  
25  
All dimensions shown are in inches. Weight assumes outdoor unit with filters, weatherhoods, and supply damper.  
Arrangement A  
Arrangement B  
Outdoor Air Discharge  
L x K  
Exhaust Air Inlet  
H x J  
Outdoor Air Discharge  
L x K  
Exhaust Air Inlet  
Outdoor Air Inlet  
Q x P  
F x G  
C
C
E
A
A
D
Exhaust Air Discharge  
L x K  
B
Intake Hood  
B
Exhaust Hood  
Arrangement C  
Arrangement D  
Outdoor Air Discharge  
L x K  
Exhaust Air Inlet  
H x J  
Outdoor Air Discharge  
L x K  
Exhaust Air Inlet  
F x G  
C
C
E
E
A
A
D
D
Intake Hood  
Intake Hood  
B
B
Exhaust Hood  
Exhaust Hood  
Service Clearance  
Model  
ERV-522  
ERV-582  
Exhaust Side  
Supply Side  
The installation must allow clearance for access to  
the energy recovery wheels and servicing. Minimum  
clearances are shown in the table at right. Model ERV-  
522 and ERV-582 energy wheels are mounted in an  
upright position, side by side. For servicing, the energy  
wheels slide out of the ventilator at opposite corners.  
38  
42  
38  
42  
All dimensions shown are in inches.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Supply and Exhaust - Belt and Direct Drive  
Greenheck Fan Corporation certifies that the  
The airflow performance data shown  
applies to arrangement A and is licensed to  
bear the AMCA Seal for Air Performance.  
Performance data for other arrangements  
may differ slightly.  
ERV models shown herein are licensed to bear  
the Air Performance AMCA seal. The ratings  
shown are based on tests and procedures  
performed in accordance with AMCA Publication  
211 and comply with the requirements of the  
AMCA Certified Ratings Program.  
For specific performance for all arrangements,  
use Greenheck’s Computer Aided Product  
Selection (CAPS) program.  
NOTES:  
All models are available in A, B, C, and  
D arrangements.  
1. Performance tables show EXTERNAL  
static pressure capabilities.  
2. Bhp, watt and amp values shown are for  
one blower motor only.  
ERV-251S (Standard Airflow)  
EXTERNAL STATIC PRESSURE (in. wg)  
Nominal  
RPM  
Max Amps Max. Watts  
115/230  
(input)  
0.25  
0.375  
0.50  
0.625  
0.75  
1.00  
1.25  
950  
1150  
1350  
3.0/1.5  
300  
563  
536  
498  
450  
378  
CFM  
5.3/2.7  
8.6/4.3  
530  
855  
700  
834  
680  
818  
658  
801  
634  
783  
597  
762  
513  
711  
642  
ERV-251H (High Airflow)  
EXTERNAL STATIC PRESSURE (in. wg)  
Nominal  
RPM  
Max Amps Max. Watts  
115/230  
(input)  
0.25  
0.375  
0.50  
0.625  
0.75  
1.00  
1.25  
1150  
1340  
1520  
5.0/2.5  
500  
802  
777  
742  
706  
667  
CFM  
8.1/4.1  
810  
958  
937  
915  
887  
857  
792  
954  
11.5/5.8  
1150  
1089  
1070  
1051  
1032  
1008  
895  
ERV-361S (Standard Airflow)  
EXTERNAL STATIC PRESSURE (in. wg)  
CFM  
1000  
1200  
1400  
1600  
OV  
0.125  
777  
0.250  
863  
0.375  
941  
0.50  
1015  
0.33  
1109  
0.48  
1212  
0.68  
1323  
0.95  
0.75  
1147  
0.41  
1232  
0.58  
1324  
0.80  
1424  
1.07  
1.00  
1277  
0.49  
1343  
0.68  
1429  
0.92  
1520  
1.20  
1.25  
1397  
0.58  
1453  
0.78  
1527  
1.03  
1613  
1.34  
1.50  
1515  
0.69  
1557  
0.87  
1618  
1.14  
1701  
1.47  
FRPM  
BHP  
1495  
1794  
2093  
2392  
0.21  
899  
0.25  
974  
0.29  
1043  
0.43  
1153  
0.64  
1269  
0.89  
FRPM  
BHP  
0.34  
1023  
0.52  
1149  
0.75  
0.39  
1091  
0.58  
1212  
0.82  
FRPM  
BHP  
FRPM  
BHP  
ERV-361H (High Airflow)  
EXTERNAL STATIC PRESSURE (in. wg)  
CFM  
1600  
1800  
2000  
2200  
OV  
0.125  
1006  
0.58  
1119  
0.82  
1232  
1.11  
1347  
1.46  
0.250  
1065  
0.64  
1172  
0.88  
1279  
1.17  
1389  
1.53  
0.375  
1122  
0.69  
1223  
0.93  
1326  
1.23  
1433  
1.60  
0.50  
1175  
0.74  
1272  
0.99  
1372  
1.30  
1474  
1.67  
0.75  
1275  
0.86  
1365  
1.12  
1458  
1.43  
1555  
1.81  
1.00  
1367  
0.96  
1452  
1.25  
1541  
1.58  
1633  
1.97  
1.25  
1457  
1.07  
1533  
1.36  
1618  
1.72  
1.50  
1542  
1.19  
1613  
1.49  
1692  
1.85  
FRPM  
BHP  
2392  
2691  
2990  
3289  
FRPM  
BHP  
FRPM  
BHP  
FRPM  
BHP  
Gross supply air performance ratings (airflow, pressure, and power) are at port 2 with port 1, port 3 and port 4 at 0.0 in. wg. Gross exhaust air  
performance ratings (airflow, pressure, and power) are to port 3 with port 1, port 2 and port 4 at 0.0 in. wg. Power rating (Bhp) does not include drive  
losses. Performance ratings do not include the effects of appurtenances in the airstream.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Supply and Exhaust - Belt Drive  
ERV-521S (Standard Airflow)  
EXTERNAL STATIC PRESSURE (in. wg)  
CFM  
2,200  
2,700  
3,200  
OV  
0.125  
830  
0.25  
881  
0.375  
933  
0.50  
981  
0.75  
1072  
1.09  
1203  
1.75  
1345  
2.65  
1.00  
1155  
1.25  
1278  
1.93  
1412  
2.86  
1.25  
1238  
1.41  
1350  
2.12  
1477  
3.08  
1.50  
1315  
1.57  
1416  
2.30  
FRPM  
BHP  
2,183  
2,679  
3,175  
0.72  
998  
0.80  
1040  
1.38  
1203  
2.21  
0.87  
1081  
1.47  
1240  
2.32  
0.95  
1124  
1.57  
1274  
2.43  
FRPM  
BHP  
1.29  
1168  
2.11  
FRPM  
BHP  
ERV-521H (High Airflow)  
EXTERNAL STATIC PRESSURE (in. wg)  
CFM  
3,100  
3,700  
4,300  
OV  
0.125  
980  
0.25  
1017  
1.65  
1187  
2.72  
1361  
4.20  
0.375  
1054  
1.73  
0.50  
1089  
1.82  
1249  
2.92  
1415  
4.43  
0.75  
1159  
1.99  
1309  
3.12  
1467  
4.65  
1.00  
1226  
2.18  
1367  
3.33  
1519  
4.89  
1.25  
1290  
2.36  
1425  
3.55  
1569  
5.13  
1.50  
1355  
2.54  
1480  
3.77  
FRPM  
BHP  
3,076  
3,671  
4,267  
1.57  
1156  
2.62  
1334  
4.08  
FRPM  
BHP  
1219  
2.83  
FRPM  
BHP  
1388  
4.31  
ERV-522S (Standard Airflow)  
EXTERNAL STATIC PRESSURE (in. wg)  
CFM  
5,000  
5,750  
6,500  
OV  
0.125  
754  
0.25  
794  
2.39  
892  
3.49  
991  
4.90  
0.375  
831  
0.50  
869  
0.75  
943  
1.00  
1011  
3.54  
1087  
4.81  
1164  
6.33  
1.25  
1072  
3.89  
1146  
5.26  
1222  
6.89  
1.50  
1134  
4.30  
1201  
5.67  
1276  
7.41  
FRPM  
BHP  
2,416  
2,779  
3,141  
2.20  
855  
2.57  
924  
2.76  
957  
3.15  
1022  
4.33  
1108  
5.88  
FRPM  
BHP  
3.28  
956  
3.70  
1021  
5.15  
3.92  
1049  
5.39  
FRPM  
BHP  
4.67  
ERV-522H (High Airflow)  
EXTERNAL STATIC PRESSURE (in. wg)  
CFM  
6,000  
7,500  
9,000  
OV  
2,067  
2,584  
3,100  
0.125  
535  
0.25  
581  
0.375  
619  
0.50  
660  
0.75  
731  
1.00  
797  
1.25  
857  
1.50  
913  
FRPM  
BHP  
1.57  
646  
1.79  
686  
1.96  
722  
2.16  
753  
2.55  
818  
2.94  
877  
3.33  
930  
3.72  
983  
FRPM  
BHP  
2.90  
763  
3.20  
794  
3.46  
827  
3.68  
857  
4.17  
910  
4.66  
964  
5.12  
1016  
7.60  
5.62  
1063  
8.18  
FRPM  
BHP  
4.90  
5.20  
5.57  
5.89  
6.42  
7.01  
ERV-581H (High Airflow)  
EXTERNAL STATIC PRESSURE (in. wg)  
CFM  
4,300  
5,050  
5,800  
OV  
0.125  
637  
0.25  
687  
1.35  
774  
2.05  
866  
2.99  
0.375  
733  
0.50  
772  
1.61  
855  
2.39  
939  
3.38  
0.75  
850  
1.00  
923  
1.25  
988  
1.50  
1055  
2.73  
1111  
3.65  
1177  
4.83  
FRPM  
BHP  
2,064  
2,424  
2,784  
1.20  
731  
1.49  
817  
1.88  
922  
2.16  
989  
2.42  
1053  
3.33  
1120  
4.44  
FRPM  
BHP  
1.89  
826  
2.23  
903  
2.68  
1004  
3.74  
3.00  
1061  
4.07  
FRPM  
BHP  
2.79  
3.18  
ERV-582H (High Airflow)  
EXTERNAL STATIC PRESSURE (in. wg)  
CFM  
9,000  
OV  
0.125  
595  
0.25  
629  
3.95  
713  
5.99  
800  
8.66  
0.375  
661  
0.50  
692  
4.54  
769  
6.74  
849  
9.56  
0.75  
746  
1.00  
797  
1.25  
843  
1.50  
888  
7.09  
952  
9.74  
FRPM  
BHP  
2,254  
2,630  
3,005  
3.61  
685  
4.26  
741  
5.25  
820  
5.89  
867  
6.48  
911  
FRPM  
BHP  
10,500  
12,000  
5.60  
776  
6.38  
825  
7.44  
897  
8.27  
941  
9.03  
982  
FRPM  
BHP  
8.24  
9.12  
10.36  
11.19  
12.13  
Gross supply air performance ratings (airflow, pressure, and power) are at port 2 with port 1, port 3 and port 4 at 0.0 in. wg. Gross exhaust air  
performance ratings (airflow, pressure, and power) are to port 3 with port 1, port 2 and port 4 at 0.0 in. wg. Power rating (Bhp) does not include drive  
losses. Performance ratings do not include the effects of appurtenances in the airstream.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Selection Guidelines  
Motor Specifications  
Blower motor information  
must be specified to select  
unit. The horsepower,  
voltage, phase and enclosure  
availability is presented  
in the table on the right. If  
exhaust and supply blower  
horsepower are different,  
consult the CAPS program.  
Open  
TE  
Two Speed Open  
Model  
115/1 230/1 230/460/3 230/1 230/460/3 230/1 230/460/3  
1
1
1
1
ERV-251S*  
4
4
-
-
-
-
-
ERV-251H*  
ERV-361*  
ERV-521*  
ERV-581*  
ERV-522*  
ERV-582*  
2  
2  
-
-
-
-
-
1
1
1
1
1
1
1
1
1
1
-
-
-
-
-
4
- 2  
- 3  
-
4
- 2  
- 5  
4
- 2  
- 112  
4
- 2  
- 5  
2
2
- 1  
- 1  
-
1
2
- 112  
1
2  
2
2  
2  
2
- 3  
1 - 5  
-
112  
-
1 - 5  
1 - 15  
1 - 15  
1 - 3  
112 - 3 112 - 15  
112 - 15  
-
1 - 712  
1 - 712  
-
-
UL Listing is available on most open drip proof motors.  
*Energy wheel drive motor is only available with open drip proof motors.  
Minimum Circuit Amps (MCA) Calculations for ERV Units  
Wheel drive, 24 volt internal control amp and standard electric preheat kW. Single or three phase ERV units  
24v  
Control  
Amps  
Wheel Drive Amps  
115 208/230 460  
Standard Electric Preheat kW  
Model  
115/1 208/1 230/1  
208/3  
230/3  
460/3  
NA  
ERV-251 0.6  
ERV-361 NA  
0.6  
1.2  
NA  
0.6  
0.5  
1
2.5 2.1, 4.1 2.5, 5  
NA  
NA  
NA  
NA  
NA  
NA  
NA  
NA  
4.1, 8.2, 12.3 5, 10, 15  
8.2, 12.3,  
5, 10, 15  
ERV-521 NA  
2.8  
1.4  
1
10, 15, 19 10, 15, 20, 25, 30  
15.5  
ERV-581 NA  
ERV-522 NA  
1.6  
5.6  
3.2  
0.8  
2.8  
1.6  
1
1
1
NA  
NA  
NA  
NA  
NA  
NA  
NA  
NA  
NA  
12.3, 15.5  
15, 19  
19  
15, 20, 25, 30, 38  
20, 25, 30, 45  
20, 38, 50  
15.5  
ERV-582 NA  
15.5, 24.5  
19, 30  
NA = not available  
MCA Example Calculation  
Greenheck ERV selected: ERV-361S-B, 2 hp  
supply motor, 112 hp exhaust motor, 15kW  
preheater operating at 460 volt, three phase.  
Filter Pressure Drop  
Intake Hood  
Pleated  
2-inch  
filters  
with 2-inch  
aluminum  
Model  
CFM  
Step 1: Consult NEC table (not shown) for 2 hp  
supply motor amps = 3.4 A  
Step 2: Consult NEC table (not shown) for 112 hp  
filters  
500  
1,000  
1,000  
2,200  
2,500  
4,500  
4,500  
5,500  
6,000  
9,000  
9,000  
12,000  
0.09  
0.32  
0.09  
0.45  
0.13  
0.45  
0.17  
0.30  
0.15  
0.40  
0.13  
0.45  
0.09  
0.19  
0.10  
0.28  
0.14  
0.32  
0.15  
0.24  
0.14  
0.25  
0.16  
0.27  
ERV-251  
ERV-361  
ERV-521  
ERV-581  
ERV-522  
ERV-582  
exhaust motor amps = 2.6 A  
Step 3: Calculate 15kW preheater amp draw =  
15,000W/ [460 * 3 ] = 18.8 A  
If no preheater is used skip step 3  
Step 4: Wheel drive amps for ERV-361 from  
table above = 0.6 A  
Step 5: 24v Control Amps for ERV-361 from  
table above = 1.0 A  
Step 6: MCA = Amperage total from steps  
1 thru 5 x 1.25  
MCA = (3.4 + 2.6 + 18.8 + 0.6 + 1.0)  
1.25 = 33 A  
Note: Calculations are approximate, use our Computer Aided Product Selection (CAPS) program for exact  
MCA calculations.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical Applications  
The ERV unit can add to the benefit of a building design anywhere that outdoor air is required and the exhaust  
air is considered “clean” (ASHRAE class 1 or class 2 air ratings). Some examples of commercial and institutional  
applications where energy recovery units have been utilized are given below.  
Animal Shelters  
Locker Rooms  
Restaurants  
Bars and Clubs  
Nursing Homes  
Schools  
Churches  
Dormitories  
Printing Shops  
Casinos  
Office Buildings  
Function Halls  
Veterinary Hospitals  
With Ducted Air Handlers  
The ERV unit may be combined with ducted air handling units or fan coil boxes. A single energy recovery  
ventilator may provide fresh outdoor air for multiple air handling units or in a one-to-one ratio where a single  
energy recovery ventilator and air handler serve one space.  
SUPPLY AIR  
OUTDOOR AIR UNIT (OA unit)  
WITH ENERGY RECOVERY  
AIR HANDLING  
UNIT (AHU)  
AHU  
Heating  
Coil  
Heating  
Coil  
Energy  
Wheel  
Cooling  
Coil  
Cooling  
Coil  
OUTDOOR  
AIR  
72°F  
50%  
72°F  
50%  
Exhaust  
Fan  
ZONE 1  
ZONE 2  
EXHAUST AIR  
RESTROOM  
RELIEF AIR  
With Packaged Rooftop Equipment  
RESTROOM  
This diagram illustrates how energy recovery  
ventilators may be used in conjunction  
with packaged rooftop equipment. Fresh,  
outdoor air enters the energy recovery  
ventilator and is pretreated before entering  
the heating/cooling equipment. This  
pretreating occurs because the energy  
recovery wheel is transferring latent and  
sensible energy between the outdoor air and  
the building exhaust air.  
ZONE 1  
72°F  
50%  
EXHAUST  
AIR  
Exhaust  
Fan  
AIR HANDLING  
UNIT (AHU)  
Energy  
Wheel  
Supply  
Fan  
SUPPLY AIR  
ENERGY RECOVERY  
VENTILATOR (ERV)  
Heating Cooling  
Coil  
Coil  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Greenheck’s Energy  
Recovery Models  
Model MiniVent - Energy Recovery Ventilator  
The MiniVent-450 & 750 are energy recovery ventilators  
used for commercial and institutional applications that  
require 300 to 800 cfm of ventilation air. The compact  
design provides an economical solution for individual  
spaces, such as school classrooms and small offices.  
Model ERH - Energy Recovery with Heating  
With the ERH, you save money with the total energy wheel  
and get the convenience of supplemental heating. The ERH  
provides preconditioned air in the summer and space neutral  
air in the winter, which is ideal if your climate has prominent  
summer and winter seasons. The heating section further  
tempers cold outdoor air to desired conditions. Four housing  
sizes available with airflow capacities up to 10,000 cfm and  
external static pressures up to 1.5 in. wg.  
Model ERCH - Energy Recovery with Cooling and Heating  
The model ERCH combines the benefits of the total energy wheel with  
supplemental cooling and heating. The result is a product that is specifically  
designed to process 100% outdoor air to desired supply conditions. Four housing  
sizes provide airflow capacities from 1,000 to 10,000 cfm with external static  
pressures up to 1.5 in. wg. A variety of tempering options are available. The coil  
section of the ERCH accommodates a cooling coil, a heating coil, or both.  
Model VER - Versatile Energy Recovery (VersiVent)  
The Model VER is a fully featured, versatile energy recovery unit with a wide  
range heating and cooling options available. The unit includes an  
energy wheel to pre temper the outdoor air which reduces the heating  
and cooling equipment needed, while also lowering operational costs.  
In addition to the standard heating and cooling options, the VersiVent  
has options such as environmentally friendly R410 refrigerant, a wrap-  
around heat pipe for additional dehumidification and reheat capacity,  
and a quiet, efficient, plenum supply fan. Capacities range from 2,000 to  
10,000 cfm with external static pressures up to 3.0 in. wg.  
Model APEX - Affordable, Practical, Energy Exchanger  
The model APEX combines high airflow capacities with cost saving energy  
recovery ventilation by providing centralized outdoor air distribution and  
reducing the need for multiple unit installations. Fresh outdoor air is  
preconditioned by the total enthalpy wheel, which recovers a majority of  
the energy from the exhaust air. It saves 3-4 tons of cooling per 1,000 cfm  
and saves 50-60 MBH of heating per 1,000 cfm. Easy to install and operate  
with airflow capacities from 10,000 to 20,000 cfm and external static  
pressures up to 2.5 in. wg.  
Our Warranty  
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one  
year from the shipment date. The energy recovery wheel is warranted to be free from defects in material  
and workmanship for a period of five years from the shipment date. Any units or parts which prove defective  
during the warranty period will be replaced at our option when returned to our factory, transportation  
prepaid. Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished  
by Greenheck prove defective during this period, they should be returned to the nearest authorized motor  
service station. Greenheck will not be responsible for any removal or installation costs.  
Prepared to Support  
Green Building Efforts  
As a result of our commitment to continuous improvement, Greenheck reserves the right to change  
specifications without notice.  
00.TAP.1000 R7 6-2010 SN  
P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com  
Copyright © 2010 Greenheck Fan Corp.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Greenheck Fan Ventilation Hood DFD M210 User Manual
Hamilton Beach Griddle 38541 User Manual
Hamilton Beach Toaster 24669 User Manual
Hans Grohe Indoor Furnishings 31102XX1 User Manual
Heath Zenith Universal Remote 598 1116 10 User Manual
HP Hewlett Packard Digital Camera EOS30DBODY User Manual
HP Hewlett Packard Server V5 1B 1 User Manual
IBM Laptop MT 2632 User Manual
Iiyama Car Video System ProLite P1704S User Manual
Impex Home Gym PHC 715 User Manual