| Extruded BACKDRAFT DAMPER   ADJUSTABLE COUNTERBALANCE   EM-40 SERIES   Horizontal Mount - Vertical Airflow Down   Application and Design   The EM-40 series is a horizontally mounted backdraft damper that is designed to allow vertical airflow down and prevent   reverse airflow. The damper is opened by air pressure differential and closed by gravity. Standard models include adjustable   counterbalance weights to assist closing.   Ratings (See page 2 for specific limitations)   Pressure: 4.0 - 10.0 in. wg (996 Pa - 2491 Pa)   H*   differential pressure   Velocity: 2500 to 3500 fpm (13m/s - 18 m/s)   Temperature: 180°F (82ºC)   Standard Construction   Frame: Heavy gauge 6063T5 extruded aluminum.   W*   (0.125 in.[3.2mm] thickness)   Blades: Heavy gauge 6063T5 extruded aluminum.   (0.070 in. [1.8mm] thickness)   Axles: 3/4 in. (19mm) dia. metallic   *W & H dimensions furnished approximately 1/4 in. (6mm) under size.   Bearings: Synthetic (acetal) sleeve type   Linkage: 1/8 in. (3mm) plated steel   3 in.   5 in.   Blade Seals: Vinyl   EM-40   3 1/8 in.   No Flange   11 1/8 in.   Size Limitations   Minimum Size: 8 in. W x 11 in. H   (203mm x 279mm)   Maximum Panel Size: 48 in. W x 74 in. H   (1219mm x 1880mm)   Sizes larger than maximum shown will be supplied   as two or more equal size smaller dampers required   to make up the size specified. These larger multiple   damper assemblies require field assembly and may   require additional reinforcement (not supplied by   Greenheck) to support the assembly.   EM-41   Flange On   Discharge   1 1/2 in.   Options and Accessories   • 11/2 in. flange on discharge: EM-41   1 1/2 in.   • 11/2 in. flange on intake:   EM-42   EM-42   Flange On   Intake   • APC (Adjustable Pressure Controller).   Allows field setting of relief pressure on   all EM dampers. Use one per panel.   Maximum recommended pressure set   limitations are as follows:   Maximum Set   Pressure   in. wg (Pa)   2 Area ft   (m )   2 4 (.37)   6 (.56)   .75 (187)   .50 (125)   .40 (100)   .30 (75)   .20 (50)   .15 (37)   .125 (31)   8 (100)   10 (.93)   15 (1.39)   20 (1.86)   24 (2.23)   Counterbalance weights may require field adjustment. Instructions are   Download from Www.Somanuals.com. All Manuals Search And Download.   |