Greenheck Fan Patio Heater 45 User Manual

PART #461248  
READ AND SAVE THESE INSTRUCTIONS  
HEAT RECOVERY UNIT  
WITH EVAPORATIVE COOLING  
®
Models:  
HRE-20, 45, 55, & 90  
INSTALLATION, OPERATION AND MAINTENANCE  
MANUAL  
RECEIVING AND HANDLING  
The HRE is thoroughly inspected and test run at the factory. However, damage may occur during  
shipping and handling. Upon delivery, inspect the unit for both obvious and hidden damage.  
If damage is found, record all necessary information on the bill of lading and file a claim with  
the final carrier. In addition, ensure all accessory items are present. Some accessory items are  
stored inside the unit during shipping.  
SAFETY WARNING  
Improper installation, adjustment, alteration, service or maintenance can cause property  
damage, injury or death. Read this installation, operation, and maintenance manual thoroughly  
before installing or servicing this equipment. Installation and service must be performed by a  
qualified installer, service agency, or the gas supplier.  
Indirect Evaporative Cooler  
(Exhaust/Scavenger Airstream)  
INSTALLATION SUPPLEMENT  
Refer to the following  
installation supplement for  
HRE units when supplied with  
Indirect Gas (IG) heating:  
Model PVF, Indirect Gas  
Fired Furnaces for Energy  
Recovery Units, Part #461006  
SAVE THIS MANUAL  
This manual is the property  
of the owner, and is required  
for future maintenance. This  
manual should remain with  
Direct Evaporative Cooler  
each HRE unit when the job  
(Outdoor/Supply Airstream)  
is complete.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
The system design and installation should follow  
accepted industry practice, such as described in the  
ASHRAE Handbook.  
SAFETY WARNING  
All factory provided lifting lugs must  
be used when lifting the units. Failure  
to comply with this safety precaution  
could result in property damage,  
serious injury, or death.  
Adequate space should be left around the unit for piping  
coils and drains, filter replacement, and maintenance.  
Sufficient space should be provided on the side of the  
unit for routine service and component removal should  
that become necessary.  
See Service Clearances/Access Panel Locations section  
for more details.  
Lift using  
lifting lugs and  
spreader bar  
LIFTING  
1) Before lifting, be sure that all shipping material has  
been removed from unit.  
2) To assist in determining rigging requirements,  
weights are shown below.  
3) Unit must be lifted by the eight lifting lugs provided  
on base structure.  
4) Rigger to use suitable mating hardware to attach to  
unit lifting lugs.  
5) Spreader bar(s) must span the unit to prevent  
damage to the cabinet by the lift cables.  
6) Always test-lift the unit to check for proper balance  
and rigging before hoisting to desired location.  
7) Never lift units by weatherhoods.  
8) Never lift units in windy conditions.  
9) Preparation of curb and roof openings should be  
completed prior to lifting unit to the roof.  
10) Check to be sure that gasketing (supplied by others)  
has been applied to the curb prior to lifting the unit  
and setting on curb.  
11) Do not use fork lifts for handling unit.  
V
UNIT WEIGHTS & RECOMMENDED ROOF OPENING  
Approx. Dry Weight Approx. Wet Weight  
Unit Size  
U
V
(lbs)  
1660  
2580  
2950  
4750  
(lbs)  
1800  
2840  
3320  
5400  
EXHAUST  
INLET  
HRE-20  
HRE-45  
HRE-55  
HRE-90  
46  
54  
65  
85  
37  
39  
47  
49  
U
SUPPLY  
OUTLET  
Unit weights assume indirect evap, direct evap, and IG furnace.  
All dimensions shown are in inches.  
0.50  
0.50  
Position the unit roof opening such that the supply discharge and exhaust inlet of the unit will line up with the  
corresponding ductwork. Be sure to allow for the recommended service clearances when positioning opening  
(see Service Clearances). Do not face the outdoor air inlet of the unit into prevailing wind and keep the supply  
inlet of the unit away from any other exhaust fans. Likewise, position the exhaust discharge opening away from  
fresh air intakes of any other equipment.  
When cutting only duct openings, cut opening 1 inch (25mm) larger than duct size to allow clearance for  
installation. Area enclosed by roof curb must comply with clearance to combustible materials. If the roof is  
constructed of combustible materials, area within the roof curb must be ventilated, left open, or covered with  
non-combustible material which has an ÒRÓ value of at least 5. If area within curb is open, higher radiated  
sound levels may result.  
Where the supply or warm air duct passes thru a combustible roof, a clearance of one inch must be maintained  
between the outside edges of the duct and combustible material in accordance with NFPA Standard 90A.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
ROOF CURB MOUNTING  
Rooftop units require curbs to be mounted first. The duct connections must be located so they will be clear of  
structural members of the building.  
Roof curb details, including duct location  
dimensions, are available on HRE roof curb  
assembly instructions.  
1. Factory Supplied Roof Curbs  
Roof curbs are Model GKD, which are shipped in a  
knockdown kit (includes duct adapter) and require field  
assembly (by others). Assembly instructions are included  
with the curb.  
2. Install Curb  
Locate curb over roof opening and fasten in place. (Refer  
to Recommended Roof Openings). Check that the diagonal  
dimensions are within 1/8 inch of each other and adjust as  
necessary. For proper coil drainage and unit operation, it is  
important that the installation be level. Shim as required to  
level.  
3. Install Ductwork  
Installation of all ducts should be done in accordance with  
SMACNA and AMCA guidelines. Duct adapter provided to  
support ducts prior to setting the unit.  
L
W
4. Set the Unit  
Lift unit to a point directly above the curb and duct  
openings. Guide unit while lowering to align with duct  
openings. Roof curbs fit inside the unit base. Make sure the  
unit is properly seated on the curb and is level.  
Curb Outside Dimensions  
Curb Outside Dimensions  
Weight  
Model  
HRE-20  
HRE-45  
L
W
93  
51  
280  
355  
450  
625  
100.5  
60.63  
71.5  
90.75  
HRE-55 112.75  
HRE-90 125.75  
All dimensions shown are in inches.  
SIDE OF UNIT  
BASE  
A
B
C
Curb Cap Dimensions  
Model  
1 INCH INSULATION  
D
A
HRE-20 2.00  
HRE-45 2.00  
HRE-55 2.00  
HRE-90 2.00  
B
C
D
E
E
2.00  
4.25  
4.25  
4.25  
1.00  
2.00  
2.00  
2.00  
0.88  
1.31  
1.31  
1.31  
0.75  
0.50  
0.50  
0.50  
ROOF CURB  
All dimensions shown are in inches.  
Curb CAP Details for Factory Supplied Roof Curbs  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
RAIL MOUNTING  
Rail Layout  
Rails designed to handle the weight of the HRE should be  
positioned as shown on the diagram (rails by others).  
Make sure that rail positioning does not interfere with the supply  
air discharge opening or the exhaust air intake opening on the  
HRE unit. Avoid area dimensioned “B” below  
Rails should run the width of the unit and extend beyond the unit  
a minimum of 12 inches on each side.  
Set unit on rails.  
Isometric view of HRE on rails  
OUTDOOR  
AIR  
INTAKE  
HOOD  
Rail Mounting  
Model  
A
B
HRE-20  
HRE-45  
HRE-55  
HRE-90  
5.1  
7.1  
5.7  
6.6  
25.0  
25.1  
35.0  
36.1  
SUPPLY/EXHAUST  
OPENING  
B
A
Side view of HRE on rails  
All dimensions shown are in inches.  
DUCTWORK CONNECTIONS  
Examples of good and poor fan-to-duct connections are shown below. Airflow out of the fan should be directed  
straight or curve the same direction as the fan wheel rotates. Poor duct installation will result in low airflow and  
other system effects.  
n
o
i
t
Length of Straight Duct  
n
o
i
t
a
t
a
t
o
o
R
R
GOOD  
POOR  
Recommended Discharge Duct Size and Length  
HRE Model  
HRE Blower Size  
Duct Size  
14 x 14  
20 x 20  
28 x 28  
32 x 32  
Straight Duct Length  
HRE-20  
10  
12  
15  
18  
40  
48  
60  
72  
HRE-45  
HRE-55  
HRE-90  
Dimensions shown are in inches.  
SUPPLY WEATHERHOOD  
Supply weatherhood will be factory mounted.  
EXHAUST WEATHERHOOD  
The exhaust weatherhood is shipped separately as a kit with its own  
instructions.  
DAMPERS  
Backdraft dampers are always included as an integral part of the  
exhaust hood assemblies. Motorized outdoor air and exhaust air  
dampers are optional and are factory mounted (and wired) at the  
inlet.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL INFORMATION  
The unit must be electrically grounded in accordance with the current National Electrical Code, ANSI/NFPA  
No. 70. In Canada, use current C.S.A. Standard C22.1, Canadian Electrical Code, Part 1. In addition, the installer  
should be aware of any local ordinances or electrical company requirements that might apply. System power  
wiring must be properly fused and conform to the local and national electrical codes. System power wiring is to  
the unit main disconnect (door interlocking disconnect switch standard on most units) or distribution block and  
must be compatible with the ratings on the nameplate: supply power voltage, phase, and amperage (Minimum  
Circuit Amps - MCA, Maximum Overcurrent Protection - MOP). All wiring beyond this point has been done by  
the manufacturer and cannot be modified without affecting the unit’s agency / safety certification.  
If field installing an additional disconnect switch, it is recommended that there is at least four feet of service  
room between the switch and system access panels. When providing or replacing fuses in a fusible disconnect,  
use dual element time delay fuses and size according to the rating plate.  
If power supply is desired thru bottom of unit, run the wiring through the curb, cut a hole in the cabinet bottom,  
and wire to the disconnect switch.  
The electric supply to the unit must meet stringent requirements for the system to operate properly. Voltage  
supply and voltage imbalance between phases should be within the following tolerances. If the power is not  
within these voltage tolerances, contact the power company prior to operating the system.  
Voltage Supply - See voltage use range on the rating plate. Measure and record each supply leg voltage at all  
line disconnect switches. Readings must fall within the allowable range on the rating plate.  
Voltage Imbalance - In a 3-phase system, excessive voltage imbalance between phases will cause motors  
to overheat and eventually fail. Maximum allowable imbalance is 2%. To determine voltage imbalance, use  
recorded voltage measurements in this formula.  
Key:  
V1, V2, V3 = line voltages as measured  
VA (average) = (V1 + V2 + V3) / 3  
VD = Line voltage (V1, V2 or V3) that deviates farthest from average (VA)  
Formula: % Voltage Imbalance = [100 x (VA-VD)] / VA  
CAUTION  
If any of the original wire as supplied with the appliance must be replaced, it must be  
replaced with wiring material having a temperature rating of at least 105ºC.  
WARNING  
WARNING  
To prevent injury or death due to electrocution or  
For units with a gas furnace, if you turn off the  
contact with moving parts, lock disconnect switch  
power supply, turn off the gas.  
open.  
Most factory supplied electrical components are pre-wired. To determine what electrical accessories require  
additional field wiring, refer to the unit specific wiring diagram located on the inside of the unit control center  
access door. The low voltage control circuit is 24 Vac and control wiring should not exceed 0.75 ohms. Refer to  
Field Control Wiring Length/Gauge table for wire length maximums for a given wire gauge. Control wires should  
not be run inside the same conduit as that carrying the supply power. Make sure that field supplied conduit  
does not interfere with access panel operation.  
Field Control Wiring Length/Gauge  
Total Wire Length  
125 ft.  
Minimum Wire Gauge  
18  
16  
14  
12  
200 ft.  
300 ft.  
450 ft.  
If wire resistance exceeds 0.75 ohms, an industrial-style, plug-in relay should be added to the unit control  
center and wired in place of the remote switch (typically between terminal blocks R and G on the terminal strip  
(refer to Typical Control Center Components). The relay must be rated for at least 5 amps and have a 24 Vac  
coil. Failure to comply with these guidelines may cause motor starters to “chatter” or not pull in which can  
cause contactor failures and/or motor failures.  
Note: Standard factory installed electric post-heaters have their own disconnect separate from the unit  
disconnect. Thus, each electric post-heater requires its own separate power connection.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL CONTROL CENTER COMPONENTS  
1. Main Disconnect (non-fusible, lockable)  
2. Motor Starter - Exhaust Air Fan  
3. Motor Starter - Outdoor Air Fan  
4. Motor Contactor - Energy Wheel  
5. 24 VAC Control Transformer  
6. 24 VAC Terminal strip  
5
1
7
7. Fuses for blower motors  
6
8. Motor Contactor - Indirect Evap Pump  
9. Motor Contactor - Direct Evap Pump  
10. Evap Pump Transformer  
(115 VAC Secondary)  
10  
8
2
3
4
9
Exploded Detail  
of Terminal Strip  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE CLEARANCES / ACCESS PANEL LOCATIONS  
HRE-20, 45, 55, and 90 units require minimum clearances for access on all sides for routine maintenance. Filter  
replacement, drain pan inspection and cleaning, energy wheel cassette inspection, fan bearing lubrication and  
belt adjustment, are examples of routine maintenance that must be performed. Blower and motor assemblies,  
energy recovery wheel cassette, coil and filter sections are always provided with a service door or panel for  
proper component access. Clearances for component removal may be greater than the service clearances,  
refer to drawings below for these dimensions.  
HRE-20  
HRE-45  
36 in.  
Exhaust  
Hood  
Access Panel  
Electrical Box  
36 in.  
Indirect  
Evap  
Section  
0 in.  
Exhaust Air  
Intake  
Clearance without  
IG Heater  
52 in.  
Clearance with  
IG Heater  
Direct  
Evap  
Section  
Access Panel  
*48 in. **64 in.  
TOP VIEW  
Clearances for service and component removal on HRE-20 and HRE-45  
* Clearance for energy wheel removal on HRE-20  
** Clearance for energy wheel removal on HRE-45  
HRE-55  
HRE-90  
42 in.  
Exhaust  
Hood  
Access Panel  
Electrical Box  
42 in.  
Indirect  
Evap  
Section  
0 in.  
Exhaust Air  
Intake  
Clearance without  
IG Heater  
52 in.  
Clearance with  
IG Heater  
Direct  
Evap  
Section  
Access Panel  
42 in.  
TOP VIEW  
Clearances for service and component removal on HRE-55 and HRE-90  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIMENSIONAL DATA / ACCESS DOOR DESCRIPTIONS  
Exterior Dimensions  
Model  
A
B
C
D
E
F
G
6
H
I
HRE-20  
HRE-45  
HRE-55  
HRE-90  
98  
50  
69  
70  
85  
56  
66  
76  
96  
18  
16  
16  
16  
28.5  
41  
17  
14.25  
13.375  
21.25  
24.5  
18  
20  
25  
27  
106  
118  
131  
23.375  
5.875  
2.875  
10.5  
7.125  
10  
59.5  
78  
All dimensions shown are in inches.  
Overall Exterior Dimensions  
Model  
Width  
Overall Width  
Overall Length  
(including Lifting Lugs)  
(with Exhaust Hood)  
(with Outdoor Air Hood)  
HRE-20  
HRE-45  
HRE-55  
HRE-90  
59.5  
75  
86  
116  
122  
134  
147  
69.5  
79.5  
99.5  
101  
123  
All dimensions shown are in inches.  
Following is a list of items accessible through the access  
doors shown on the diagram at the right. Some items are  
optional and may not have been provided.  
1) Exhaust blower, motor, and drives  
2) Aluminum mesh filters (intake hood)  
3) Energy recovery wheel, motor, belt, and seals  
Outdoor air filters  
5b  
5a  
3
4
Outdoor air intake damper (optional)  
Electric preheater (optional)  
D
6
Frost control sensors (optional)  
B
Economizer sensors (optional)  
4) Direct evaporative cooler, drain pan,  
and pump (optional)  
7
H
E
F
5a) Outdoor air blower, motor, and drives  
(without indirect gas furnace)  
5b) Outdoor air blower, motor, and drives  
(with indirect gas furnace)  
2
1
I
6) Control center  
A
All electrical controls  
VFDs for blowers (optional)  
C
G
VFD for energy recovery wheel (optional)  
7) Indirect evaporative cooler, drain pan, and pump  
Exhaust air filters  
Dimensional data and  
access door locations  
Exhaust air intake damper (optional)  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
EVAPORATIVE COOLING MODULES  
Mount the heat recovery unit level to ensure proper  
operation and water drainage. Piping should be of  
adequate size to provide sufficient supply of water to meet  
the maximum demand of the evaporative coolers.  
Indirect Evaporative Cooler  
(Exhaust/Scavenger Airstream)  
EVAP MODULE INSTALLATION  
1. After the energy recovery unit is set in place, run the  
overflow and drain lines to the exterior fittings on the  
evaporative cooler (drain & overflow connections at  
unit are 1-inch male pipe thread). The supply line can  
be attached at the downstream side of the evaporative  
cooler. A manual shut off valve should be mounted in  
the supply line near the unit for servicing purposes.  
Also, a trap should be installed in the drain line to  
prevent air/sewer gas from being drawn into the unit  
(refer to Drain and Overflow Connection Locations and  
Drain Trap sections). Run bleed line into overflow.  
Direct Evaporative Cooler  
(Outdoor/Supply Airstream)  
EVAP MODULE START-UP  
1. The cooler will be prewired by the factory. (pumps are 115VAC).  
2. Check to make sure that the pump filter is around the pump inlet.  
3. Turn the water on and allow the sump to fill. Adjust the float valve to shut-off the water supply when the  
sump is filled to a 1-inch height.  
4. Open the bleed-off valve completely and saturate the media without any airflow through the unit. A jumper  
wire is required on the terminal strip to provide power to the evaporative cooler pump (see the wiring  
diagram for the proper location). This saturation process will break-in the media and minimize the odors  
associated with the media. The media’s break-in period should  
be no less than 20 minutes. When the process is complete,  
Side of HRE Unit  
remove the jumper wires in the control center.  
Note: Evaporative media may foam for a short period  
following the initial start-up. Leave the bleed-off  
valve fully open until the foaming stops.  
Drain Line  
Evaporative  
Cooling  
Overflow  
Media  
5. After the media break-in period, the  
water flow rate over the media needs to be  
checked. The pumps should provide enough  
water to saturate the media in 1-3  
minutes. If adequate flow rate is  
Sump  
Trap  
Manual  
Shutoff  
Valve  
Drain  
Line  
Roof Curb  
not achieved, adjust via water  
Roof Line  
flow adjustment device found on  
water supply line running to evap  
header.  
Manual Shutoff Valve  
Supply Line  
Standard Trap and Supply Line Configuration  
6. The water bleed-off rate will now need to be adjusted.  
This measurement is 3 to 6 percent of the media flow  
rate. The recommended flow rate is 11/2 to 2 GPM  
per square foot of media pad top area (see table at  
right). Actual water to the unit will be based on the  
evaporation rate. A water flow adjustment device is  
supplied and installed by Greenheck for ease of water  
flow adjustments. After the unit has been installed and  
running for two weeks the unit should be checked for  
mineral deposits. If there are deposits, the bleed-off  
rate needs to be increased. Some areas of the country  
have water with greater amounts of dissolved minerals  
requiring a higher bleed-off rate.  
Media Size  
(w x h x d) (in.)  
Media Pad  
Top Area  
2
Supply  
Exhaust  
18 x 36 x 12  
18 x 36 x 12  
1.5 ft  
HRE-20  
HRE-45  
HRE-55  
HRE-90  
2
1.5 ft  
2
Supply  
Exhaust  
30 x 48 x 12  
24 x 48 x 12  
2.5 ft  
2
2.0 ft  
2
Supply  
Exhaust  
36 x 56 x 12  
30 x 56 x 12  
3.0 ft  
2
2.5 ft  
2
Supply  
Exhaust  
48 x 69.5 x 12  
40 x 69.5 x 12  
4.0 ft  
2
3.3 ft  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Verify that both airflow and system static pressure are in agreement with the specifications. If these  
conditions are met, check for water carry over from the discharge side of the media. If carry over is  
observed, check the distribution header for holes or tears and the water standoff tube for blockage.  
8. After all final adjustments are made, remove the jumper wires, connect “call for cooling” signal, and replace  
all access panels. The unit is now ready for operation.  
Bleed-Off  
Valve  
Pump  
Filter  
Supply  
Connection  
Float  
Valve  
Overflow  
Threaded  
Float  
Adjustment  
Pump and Float Components  
Water Flow Adjustment Device  
HRE WATER SUPPLY CONNECTION LOCATION  
Water Supply Connection Locations  
Model  
A
B
C
D
HRE-20  
HRE-45  
HRE-55  
HRE-90  
37.375  
38.75  
43.50  
43.50  
4.625  
4.625  
4.625  
4.625  
4.625  
4.625  
4.625  
4.625  
39.25  
43.00  
46.125  
52.625  
Dimensions from outside of unit (in inches)  
Ø
0.875  
Run 1/4 inch line up through 7/8 inch  
hole here and bring around end  
of sump to supply connection.  
D
1/4 inch Water Supply Connection  
C
EA INLET  
Top View  
OA INLET  
B
1/4 inch Water Supply Connection  
A
Ø
0.875  
Run 1/4 inch line up through 7/8 inch  
hole here and bring around end  
of sump to supply connection.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WATER CONTROL OPTIONS FOR EVAPORATIVE COOLING  
AUTO DRAIN AND FILL WITH FREEZE PROTECTION  
Temperature  
Setting  
This system will automatically drain the sump tank and fill it with  
fresh water at the field adjustable intervals, typically once every 24  
hours. This flushes mineral build-up and debris from the tank to  
promote low maintenance and increase media pad life. In addition,  
the system will protect the evaporative cooler from freezing  
by draining the sump tank and supply line when the outside  
temperatures fall below the set point of the outside air sensor.  
Typically, this is set at 45º to 50º F. The auto drain and fill outdoor  
air sensor should be installed in an area that is shaded from direct  
sunlight so the outside air sensor probe will detect an accurate air  
temperature. Set the timer. Timer settings are t1:1.0, 10 min and  
t2:0.4, 60h  
t2 settings  
t1 settings  
Evaporative  
Freeze  
Protection  
Evaporative  
Timer  
PLUMBING FOR AUTO DRAIN AND FILL  
1. Run water supply line to the unit and install Water Supply Solenoid Valve (A) in this line as close to the  
water source as possible.  
2. Install Drain Solenoid Valve (B) in the supply line as indicated below. From the outlet on the drain valve,  
run line to a suitable drain location.  
3. Run an unobstructed drain line from the sump overflow to the drain trap as shown below.  
4. Install Sump Drain Solenoid Valve (C) in the drain line from the sump as indicated below. From the outlet  
on this drain valve, run a line to a suitable drain location.  
Note: Water Supply Solenoid Valve (A) is not the same as the Drain Solenoid valves (B) and (C). Make sure to  
use the proper valve for each location. Check your local code requirements for proper installation of this  
type of system. Additional drain and supply plumbing may be needed to meet your local code.  
Caution: All solenoid valves A, B, and C must be installed below the roof to protect the supply water line from  
freezing. If these valves cannot be installed below the roof, an alternate method must be used to protect these  
lines from freezing.  
VB  
1/4 PIPE SIZE (NO)  
SIDE OF HRE UNIT  
VALVE "C"  
3/4 PIPE SIZE (NO)  
VC  
SUMP DRAIN PIPE  
(TO EACH EVAP)  
SUMP OVERFLOW PIPE  
(TO EACH EVAP)  
EVAPORATIVE  
COOLING MEDIA  
SUMP  
WATER LINE CONNECTION  
AT FLOAT IS 1/4 INCH  
ROOF CURB  
ROOF LINE  
SUMP DRAIN SOLENOID VALVE (C)–NORMALLY OPEN  
3/4 INCH PIPE SIZE  
WATER SUPPLY SOLENOID VALVE (A)–NORMALLY CLOSED  
1/2 INCH PIPE SIZE  
TRAP  
DRAIN SOLENOID VALVE (B)–NORMALLY OPEN  
1/4 INCH PIPE SIZE  
Trap & Supply Line Configuration  
with Auto Drain and Fill  
DRAIN LINE  
SUPPLY LINE  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THE FOLLOWING COMPONENTS SHIP FROM GREENHECK WITH HRE (INSTALLATION, WIRING, AND POWER BY OTHERS)  
PART DESCRIPTIONS  
JOHNSON CONTROLLER  
OUTDOOR AIR SENSOR  
24 HOUR TIMER  
GREENHECK P/N  
07458032  
07458298  
07381940  
05461262  
05461263  
05461264  
QTY.  
HOLDING VA  
INRUSH VA  
1
1
1
1
1
1
-
-
-
-
-
-
VALVE, WATER SUPPLY (A)  
VALVE, DRAIN (B)  
25  
25  
25  
70  
50  
70  
VALVE, SUMP DRAIN (C)  
24V AC POWER AND WIRING  
BY OTHERS  
OUTDOOR AIR  
SENSOR  
24VAC  
SENSOR  
JOHNSON CONTROLLER  
JC  
COM  
OUTDOOR AIR SENSOR  
15  
B1  
A1  
A2  
16  
18  
TIMER  
TIMER  
T1  
JC  
VALVE "A"  
1/2 PIPE SIZE (NC)  
VA  
VB  
VC  
NC  
COM  
VALVE "B"  
1/4 PIPE SIZE (NO)  
SIDE OF HRE UNIT  
VALVE "C"  
3/4 PIPE SIZE (NO)  
SUMP DRAIN PIPE  
(TO EACH EVAP)  
DRAIN TRAP  
Cooling coils are provided with a stainless steel drain pan with 3/4-in. female NPT drain connection. A drain  
trap must be connected to the drain connection to allow excess water to flow out of the drain pan. More  
importantly, though, due to the negative internal static of the cooling coil compartment, installing the drain trap  
prevents outdoor air from being pulled into the drain pan and consequently forcing water out of the pan and  
into the unit.  
To ensure the drain trap works properly, the trap height must account for the difference in static pressure  
between ambient conditions outside the unit and the internal  
negative pressure of the cooling coil compartment. For energy  
recovery units, an assumption of 3.0 in. wg. differential will be  
sufficient. This would require a trap design as shown. If the  
4 in.  
internal static is believed to be higher, consult factory.  
Refer to local codes to determine drainage requirements. If  
draining onto to roof, place a drip pad below drain to protect  
2 in.  
roof. If draining onto roof is not acceptable, a drain line must be  
attached to the trap. The drain line must be pitched away from  
the unit at least 1/8-in. per foot. On longer runs, an air break should be used to ensure proper drainage. Local  
codes may require drainage into a waste water system.  
Drainage problems not only occur from improper drain trap design, but also from lack of maintenance of the  
cooling coil compartment. Algae can form in the drain pan and trap and cause reduced water flow, which can  
in turn result in backup into the system. Regular maintenance will prevent this from occurring. If the drains have  
a cleanout opening, be sure to close the opening after cleaning.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DRAIN AND OVERFLOW CONNECTION LOCATIONS  
Connection Locations - in inches  
Model  
Outdoor Air Side  
Exhaust Side  
A
B
C
D
A
B
C
D
HRE-20  
HRE-45  
HRE-55  
HRE-90  
4.00  
6.25  
6.375  
6.375  
2.875  
5.125  
5.125  
5.125  
40.75  
42.625  
53.00  
47.25  
42.25  
44.125  
54.50  
48.50  
4.00  
6.25  
6.375  
6.375  
2.875  
5.125  
5.125  
5.125  
52.25  
56.50  
66.375  
71.00  
53.75  
58.00  
67.875  
72.25  
Outdoor Air  
OUTDOOR  
AIR  
INTAKE  
COMPARTMENT  
OUTDOOR AIR  
DISCHARGE  
COMPARTMENT  
A
B
C
D
3/4 INCH DIRECT EVAP DRAIN AND  
OVERFLOW CONNECTIONS  
Exhaust  
EXHAUST AIR  
DISCHARGE  
COMPARTMENT  
EXHAUST AIR  
INTAKE  
COMPARTMENT  
A
B
3/4 INCH INDIRECT EVAP DRAIN AND  
OVERFLOW CONNECTIONS  
C
D
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING FOR EVAPORATIVE MODULE  
Symptom  
Solution  
A. Check water level in base pan. The  
level should be at 1 inch.  
Insufficient water  
volume or recirculation  
pump not operating  
B. Check the pump filter at the inlet.  
Clean the filter if clogged or dirty.  
C. If pump is not operating, check  
wiring for loose connections and  
proper voltage.  
C
D. Clogged or worn out pump.  
E. Clogged header.  
F. Water flow adjustment device  
Header  
Detail  
Irregular water  
distribution on cooling  
media  
Water distribution header, orifices or media partially blocked or plugged.  
Remove evaporative cooler from unit.  
Disassemble and clean distribution header, orifices and media.  
A. Increase bleed rate.  
Scale and mineral  
deposit formation on  
face of media  
B. Increase water flow rate. Media is self-cleaning with flow rate of 11/2 to 2  
gpm per square foot of media top area. Generally this flow rate prevents  
dissolved solvents from collecting on the media. To prevent further  
trouble, flush and clean the system more frequently.  
C. Check water flow across the face of the media. Irregular water distribution  
must be corrected (see above)  
D. If this condition persists, chemicals may need to be added. Water pH  
should be maintained between 6 and 8.  
A. Irregular water distribution on face of media (see above).  
B. Average face velocity exceeds 550 fpm. Decrease fan rpm and airflow.  
C. Localized face velocities exceeding 550 fpm. Air filters or media face area  
is partially blocked. Clean or replace air filters and media.  
D. Check the overflow for blockage.  
Water Carry-Over  
Inadequate cooling  
A. Irregular water distribution over face of media (see above).  
B. Check for uniform airflow.  
C. Check outside wet-bulb temperature. High wet-bulb temperatures can  
decrease performance.  
D. Check water flow rate over media. Flow rate should be 11/2 to 2 gpm per  
square foot of media top area.  
A. Check the water bleed off rate and make sure that it is not excessive.  
B. Check water level in base pan. The level should be at 1 inch.  
Excessive water  
discharge into drain  
Pad installed backwards. To get the  
Poor performance  
after cooling pad  
replacement  
°
45  
performance from the cooling pads,  
they must be installed properly. The  
pads are manufactured with 15/45  
degree flute angles. The pads must  
always be installed with the steeper  
flute angle sloping down toward the  
entering air side. See figure on right.  
Entering Air  
Leaving Air  
°
15  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EVAPORATIVE COOLING MAINTENANCE  
Regularly scheduled maintenance is the key to peak  
performance, minimized cost, and extended life of  
the evaporative cooler. The following is a checklist of  
items that need to be looked at on a regular basis.  
c) Open evaporative cooling section door  
d) Flush distribution headers and media for 20  
minutes  
e) Turn off pumps and drain all water distribution  
piping, headers, etc.  
1. The media should be checked for mineral and  
foreign material deposits that have built up. If  
these items are left on the media, the life and  
performance of the unit will be greatly reduced.  
Also, there are risks of water carryover when  
this type of condition exists. When signs of  
mineral build-up are noticed, you should increase  
the bleed off rate. If this does not solve the  
problem, chemicals may need to be added to  
the water. The evaporative pads tend to be self-  
cleaning. Depending on water quality and system  
maintenance, the useful life of the pads should  
be 3 to 5 years.  
f) Dry media completely by running blowers.  
g) Brush media as described in Paragraph 2 and  
perform steps d and e again.  
h) Clean all remaining components (i.e. sump,  
pump, etc.) of any mineral deposits or foreign  
materials  
i) Replace all worn or non-functioning parts  
j) Reassemble the cooling unit.  
k) Close cooling section door.  
l) Turn the main disconnect ‘ON’, leaving the  
cooling switch in the ‘OFF’ position.  
8. If the evaporative cooler will be turned off during  
the cooling season for an extended period of  
time, it is recommended that the media be dried  
out. This can be accomplished by allowing the  
blowers to continue to run for 1-2 hours. Doing  
so, will prevent organic build-up on the media  
and subsequent odors getting into the space.  
2. The media should be periodically brushed lightly  
with a soft bristle brush in an up and down  
motion (never brush side-to-side) while flushing  
with water. This will also aid in reducing the  
amount of foreign material build-up.  
3. The water should be shut off and all the lines  
drained when the temperature drops below 50ºF.  
9. Media should be permitted to dry once per week  
by allowing the blowers to run for 1-2 hours.  
4. When the evaporative cooler is going to be used  
for the first time each season, it is recommended  
that the media be flushed with clean water for a  
period of 2 minutes (see Evap Module Start-Up).  
10. A flush cycle should be performed weekly for one  
hour with the fans off.  
5. At the beginning of each cooling season, the  
upright recirculating pump should have the  
shaft oiled and spun to eliminate the potential of  
seizing and pump burn out.  
IMPORTANT  
Replacement media should be from the same  
manufacturer and be the same size as the original  
media provided with the unit.  
6. If the cooling media was removed from the  
unit, check to make sure that is not installed  
backwards. If the media is installed backwards,  
there will be large amounts of water carry  
over downstream of the evaporative cooler.  
Continuous operation in this manner may cause  
serious damage and void the warranty.  
To remove media, disconnect water line to evap  
header as shown below. Then slide media section  
out of unit. Sump will remain in unit. If media is wet,  
turn off water supply, then turn on unit and allow air  
to flow thru media for 10-20 minutes. This will dry the  
media out and make it lighter and easier to handle.  
7. At the end of each cooling season the  
evaporative cooler should be thoroughly  
cleaned. A dispersant and biocide (consult water  
treatment consultant for suitable materials and  
dosage levels) should be recirculated for 12 to 24  
hours prior to performing the following steps:  
a) Disconnect power to unit.  
b) Shut off all water to the unit  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL ACCESSORIES  
Electric Heater Application/Operation  
Factory installed electric heaters can be provided for preheat and/or post-heat. An electric preheater warms  
the outdoor air prior to the energy recovery wheel to prevent frosting on the wheel. An electric post-heater  
warms the air leaving the energy recovery wheel to a user specified discharge temperature. Electric heaters are  
available in 208, 230, or 460 Vac (refer to heater nameplate for voltage).  
Preheaters:  
Preheaters are standard as 2-stage, step control. Step control heaters are designed with  
multiple stages made up of equal increments of heating capability. For example, a 10 kW  
heater with two stages will be composed of two 5-kW stages. Preheaters are single point  
wired at the factory. A temperature sensor (with field adjustable set point) is mounted in the  
outdoor airstream after the preheater to turn the preheater on. See Frost Control Application  
/Operation for typical set points. If the temperature falls below the set point, the first stage of  
the preheater will turn on. If the first stage does not satisfy the set point, the second stage will  
also turn on.  
Post-heaters: Post-heaters are standard as SCR control. Post-heaters are not single point wired (see  
Electrical Connections). A temperature sensor (with field adjustable set point) is mounted in  
the outdoor airstream after the post-heater to turn the post-heater on. A SCR heater provides  
an infinitely modulating control of the heat to provide an accurate discharge temperature. A  
call for heat is required.  
Post-Heater Control Panel  
The post-heater is not single point  
wired to the HRE control center.  
Separate power must be supplied  
to the post-heater disconnect  
(located in unit control center).  
Access to the post-heater control  
panel is through the exhaust filter  
door. The indirect evaporative  
cooling media must be removed  
from the unit along with the exhaust  
filters to access.  
Electric Preheater  
The preheater is single  
Electric Post-Heater  
point wired to the HRE  
control center. Access to the  
preheater control panel is  
through the supply filter door.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL ACCESSORIES  
Frost Control Application/Operation  
Extremely cold outdoor air temperatures can cause moisture condensation and frosting on the energy recovery  
wheel. Frost control is an optional feature that will prevent/control wheel frosting. Three options are available:  
1) Timed Exhaust frost control  
2) Electric preheat frost control  
3) Modulating wheel frost control  
Indoor RH @ 70º F  
Frost Threshold Temp  
20%  
25%  
30%  
2º F  
7º F  
All of these options are provided with a thermostat (with  
probe) mounted in the outdoor air inlet compartment and  
a pressure sensor to monitor pressure drop across the  
wheel. The typical temperature setting corresponds to the  
14º F  
Frost Threshold Temperatures  
indoor air relative humidity as shown in the Frost Threshold Temperatures Table and represents when frost can  
occur. An increase in pressure drop would indicate that frost is occurring. Both the pressure sensor AND the  
outdoor air temperature sensor must trigger in order to initiate frost control. The two sensors together insure  
that frost control is only initiated during a real frost condition. Field wiring of a light (or other alarm) between  
6 & C in the control center will notify personnel when unit is in frost control mode (refer to Remote Panel Wiring  
schematics section for wiring details). The following explains the three options in more detail.  
Timed exhaust frost control includes a timer in addition to the thermostat  
A1  
B1  
15  
and pressure sensor. When timed exhaust frost control is initiated, the timer  
will turn the supply blower on and off to allow the warm exhaust air to defrost  
the energy recovery wheel. Default factory settings are 5 minutes off and 30  
minutes on. Use the following test procedure for troubleshooting.  
0.8 0.6  
1.0 0.4  
0.2  
Dip  
Switch  
0
T2  
1 MIN T2  
Testing (refer to diagram at right)  
Timer  
Scale  
• Jumper the pressure switch. Set the Timer Scale for T1 and T2 to  
1 minute. Set the Timer Settings for T1 and T2 to 1.0. Set the dip  
switch to the down position.  
1 MIN T1  
0.8 0.6  
1.0 0.4  
0.2  
0
• Turn the temperature sensor up as high as possible. The supply blower  
T1  
should cycle on for one minute, then turn off for one minute.  
16  
18  
A2  
• After testing, set the Timer Scale as follows: T1 = 10 minutes, T2 =  
1 hour  
Timer  
• Set the Timer Settings as follows: T1 = 0.5, T2 = 0.5. The timer is now  
set for 5 minutes off and 30 minutes on. Remember to remove the jumper.  
Electric preheat frost control includes an electric heater (outdoor air inlet) and an air pressure switch  
(outdoor air outlet) in addition to the thermostat and pressure sensor on wheel. (Refer to Electric Heater  
Application/Operation for electric preheater location). When electric preheat frost control is initiated, the electric  
preheater will turn on and warm the air entering the energy wheel to avoid frosting. Use the following test  
procedure for troubleshooting.  
Testing  
• Turn the thermostat as high as it will go and jumper the wheel pressure sensor. The heater  
should turn on.  
• If it doesn’t, either put the supply side doors on or temporarily jumper the air pressure switch to  
avoid nuisance tripping of the pressure switch. Remember to remove the jumpers.  
Modulating wheel frost control includes a variable frequency drive in addition to the thermostat and pressure  
sensor. When modulating wheel frost control is initiated, the variable frequency drive will reduce the speed  
of the wheel reducing the speed of the energy wheel reduces its effectiveness, which keeps the exhaust air  
condition from reaching saturation, thus, eliminating condensation and frosting. If the outdoor air temperature is  
greater than the frost threshold temperature OR the pressure differential is less than the setpoint, the wheel will  
run at full speed. If the outdoor air temperature is less than the frost threshold temperature AND the pressure  
differential is greater than the setpoint, the wheel will run at reduced speed until the pressure differential falls  
below the setpoint. The temperature and pressure differential set points are set at the factory, but are field-  
adjustable (refer to VFD section for more information). The variable frequency drive will be fully programmed at  
the factory.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL ACCESSORIES  
Economizer Application/Operation  
The energy recovery wheel operation can be altered to take advantage of economizer operation (free cooling).  
Two modes are available: 1) De-energizing the wheel or 2) Modulating the wheel. A field supplied call for cool  
(Y1) is required.  
De-energizing the wheel is accomplished with a signal from a Temperature or Enthalpy sensor mounted in  
the supply air inlet compartment. This Primary sensor will de-energize the energy wheel when the outdoor air  
temperature (factory default is 65ºF) or enthalpy (factory default is the “D” setting) is below the field adjustable  
set point. An Override temperature sensor is also furnished in the supply air inlet compartment to deactivate  
economizer mode. The Override (with field adjustable set point) is set at some temperature lower than the  
Primary sensor (factory default is 50ºF). Effectively, the two sensors create a deadband where the energy  
recovery wheel will not operate and free cooling from outside can be brought into the building unconditioned.  
Testing  
Temperature Sensor with Override  
• Turn both Temperature and Override thermostats down as low as they go. The  
wheel should be rotating.  
• Turn the Temperature sensor up as high as it goes, and keep the Override sensor  
as low as it will go. The wheel should stop rotating.  
• Turn both sensors as high as they will go. The wheel should start rotating.  
• Set the Temperature sensor at desired point for economizer operation to begin.  
Set the Override sensor at desired point for economizer operation to end (factory  
default is 65ºF and 50ºF, respectively).  
Temperature Sensor  
with Override  
Enthalpy Sensor with Override  
• Turn unit power off. Disconnect C7400 solid state enthalpy sensor from terminal  
So on the enthalpy controller. Also, disconnect the 620 ohm resistor from  
terminal Sr on the enthalpy controller. Turn unit power on. The LED on the  
enthalpy controller should light and the energy recovery wheel should not rotate.  
• Turn unit power off. Reconnect 620 ohm resistor to terminal Sr on the enthalpy  
controller. Turn unit power on. The LED on the enthalpy controller should not  
light and the energy recovery wheel should energize and rotate.  
If the steps above provide the results described, the enthalpy  
economizer is working properly.  
Enthalpy Sensor  
with Override  
• Turn unit power off. Reconnect C7400 solid state enthalpy sensor  
to terminal So.  
Modulating the Wheel  
Enthalpy  
Controller  
In applications in which an internal heat gain is present in the space,  
the rotational speed of the energy wheel may be modulated (via variable  
frequency drive) to avoid overheating the space during the winter. The speed of the energy wheel will be  
controlled in response to the discharge temperature setpoint.  
Sequence of Operation: The variable frequency drive is fully programmed at the factory (refer to VFD section  
for more information). A “call for cool” must be field wired to the unit (terminals provided in unit - refer to wiring  
diagram in unit control center) to allow for initiation of economizer mode. When the space calls for cooling,  
factory supplied controls will drive the following wheel operations:  
TOA > TRA  
: Wheel runs at full speed (maximum energy recovery)  
TOA < TRA and TOA > TSA : Wheel is stopped (no energy recovery)  
TOA < TRA and TOA < TSA : Wheel will modulate to maintain discharge temperature  
where (TOA) is the outdoor air temperature set point, (TRA) is the return air temperature set point, and (TSA) is  
the supply air discharge thermostat setpoint (nominal 60¡F Ð not adjustable).  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL ACCESSORIES  
Variable Frequency Drives for Blowers  
Optional factory installed, wired, and programmed variable frequency drives (VFD) may have been provided  
for modulating or multi-speed control of the blowers. One VFD is provided for each blower (outdoor air and  
exhaust). The VFDs provided are either Yaskawa model E7 or model GPD305. Refer to the tables on the  
next page for factory settings and field wiring requirements. Refer to the unit control center for unit specific  
wiring diagram (an example wiring diagram has been provided in this section for reference). When making  
adjustments outside of the factory setpoints, refer to Yaskawa VFD instruction manual, which can be found  
YASKAWA  
GPD 305/J7  
YASKAWA E7  
FREF FOUT  
F/R  
IOUT MNTR  
LO/RE  
PRGM  
RUN  
DSPL  
STOP  
DATA  
RESET  
MIN  
MAX  
ENTER  
AUTO  
MENU  
ESC  
DATA  
ENTER  
MONITOR  
RESET  
OFF  
MA MB MC  
S1 S2 S3 S4 S5 SC FS FR FC AM AC  
RUN  
STOP  
HAND  
OPTION 1 - 0-10 VDC CONTROL  
SN SC SP A1 A2 +V AC  
AC  
R+ R-  
MA MB MC  
S1 S2 S3 S4 S5 S6 S7 FM AC AM IG S+ S-  
M3 M4 M1  
M2  
E(G)  
E(G)  
USER TO PROVIDE ISOLATION AS REQUIRED  
FR FC  
0-10 VDC CONTROL SIGNAL (BY OTHERS)  
WIRED TO FR (+) AND FC (COMMON)  
0 VDC=30 Hz  
10 VDC=60 Hz  
FOR ONE 0-10 SIGNAL, WIRE TO DRIVES IN PARALLEL  
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL  
FOR CONTINUOUS 60Hz OPERATION JUMPER TERMINALS FS AND FR.  
OPTION 1 - 0-10 VDC CONTROL  
USER TO PROVIDE ISOLATION AS REQUIRED  
0-10 VDC CONTROL SIGNAL (BY OTHERS)  
A1 AC  
WIRED TO A1 (+) AND AC (COMMON)  
0 VDC=30 Hz  
10 VDC=60 Hz  
OPTION 2 - MULTI SPEED CONTROL  
FOR ONE 0-10 SIGNAL, WIRE TO DRIVES IN PARALLEL  
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL  
FOR CONTINUOUS 60Hz OPERATION JUMPER TERMINALS A1 AND +V.  
USER TO PROVIDE CONTACTS  
AND ISOLATION AS REQUIRED  
S4 S5 SC  
NEITHER S4 OR S5 CONTACT CLOSED  
DRIVE SPEED = 60 Hz.  
OPTION 2 - MULTI SPEED CONTROL  
S4 TO SC CONTACT CLOSED (BY OTHERS)  
DRIVE SPEED = 40 Hz.  
USER TO PROVIDE CONTACTS AND ISOLATION AS REQUIRED  
S5 TO SC CONTACT CLOSED (BY OTHERS)  
DRIVE SPEED = 30 Hz.  
NEITHER S5 OR S6 CONTACT CLOSED  
DRIVE SPEED = 60 Hz.  
S5 S6 SN  
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL  
S5 TO SN CONTACT CLOSED (BY OTHERS)  
DRIVE SPEED = 40 Hz.  
TO CHANGE THE FACTORY SET Hz CHANGE THE FOLLOWING PARAMETERS.  
PARAMETER n01 CHANGE TO 1  
S6 TO SN CONTACT CLOSED (BY OTHERS)  
DRIVE SPEED = 30 Hz.  
PARAMETER n21 FOR NEW 60Hz SETTING  
PARAMETER n22 FOR NEW 40Hz SETTING  
PARAMETER n23 FOR NEW 30Hz SETTING  
PARAMETER n01 CHANGE TO 0  
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL  
TO CHANGE THE FACTORY SET Hz CHANGE THE FOLLOWING PARAMETERS.  
PARAMETER A1-01 CHANGE TO 2  
PARAMETER D1-01 FOR NEW 60Hz SETTING  
PARAMETER D1-02 FOR NEW 40Hz SETTING  
PARAMETER D1-03 FOR NEW 30Hz SETTING  
PARAMETER A1-01 CHANGE TO 0  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL ACCESSORIES  
Factory Setpoints - MODULATING CONTROL (0-10 VDC) FOR FAN SPEED  
Variable frequency drives (VFD) for the blowers are factory setup to receive a 0-10 VDC signal wired in the field  
(refer to previous page for terminal locations). Most of the setpoints in the VFDs are factory defaults. There are  
a few, though, that are changed at Greenheck and are shown in the tables below. To gain access to change  
setpoints on the E7 drive, parameter A1-01 needs to be set at “2”. To gain access to change setpoints on the GPD-  
305 drive, parameter n01 needs to be set at “1”. To prevent access on either drive, change the parameter to “0”.  
Yaskawa E7 Drive  
Yaskawa GPD-305 Drive  
S1 to SN contact for On/Off  
S1 to SC contact for On/Off  
A1 (0-10VDC) referenced to AC (Can use +15 VDC from +V)  
FR (0-10VDC) referenced to FC (Can use +12 VDC from FS)  
Parameter  
Access Level  
Setting  
Parameter  
Access Level  
Setting  
A1-01  
C6-02  
d2-02  
E2-01  
H3-03  
O2-03  
A1-01  
2
n01  
n31  
n32  
n40  
n42  
n46  
n01  
1
Carrier frequency  
Ref Lower Limit  
Motor Rated FLA  
Terminal A1 Bias  
User Defaults  
2
Ref Lower Limit  
Motor Rated FLA  
50%  
50%  
Motor FLA  
Motor FLA  
Multi-Function output (MA,MB,MC)  
Analog Freq. Reference Bias  
Carrier Frequency  
0
50%  
2
50%  
1
0
Access Level  
Access Level  
0
Factory Setpoints - MULTI-SPEED CONTROL (1/3 OR 1/2 SPEED REDUCTION) FOR FAN SPEED  
Yaskawa E7 Drive  
S1 to SN contact for On/Off  
Parameter  
Yaskawa GPD-305 Drive  
S1 to SC contact for On/Off  
Parameter  
Setting  
Setting  
A1-01  
b1-01  
C6-02  
d1-01  
d1-02  
d1-03  
d1-04  
E2-01  
O2-03  
A1-01  
Access Level  
2
n01  
n03  
n21  
n22  
n23  
n24  
n32  
n38*  
n39*  
n40  
n46  
n01  
Access Level  
1
(Frequency) Reference Source  
Carrier frequency  
0
Reference Selection  
Frequency Reference 1  
Frequency Reference 2  
Frequency Reference 3  
Frequency Reference 4  
Motor Rated FLA  
1
2
60Hz  
Frequency Reference 1  
Frequency Reference 2  
Frequency Reference 3  
Frequency Reference 4  
Motor Rated FLA  
60  
40Hz  
40  
30Hz  
30  
60Hz  
60  
Motor FLA  
Motor FLA  
Multi-function Input Sel 4 (Term S4)  
Multi-function Input Sel 5 (Term S5)  
Multi-Function output (MA,MB,MC)  
Carrier Frequency  
6
7
0
2
0
User Defaults  
1
0
Access Level  
Access Level  
*Parameter n39 must be set to 7 before n38 can be set to 6 (the  
drive does not allow these parameters to be the same number, n39  
default is 6)  
Variable Frequency Drives for  
Energy Recovery Wheel  
Factory installed VFD for the energy recovery wheel are programmed at the factory per the settings shown  
below. Refer to the instruction manual that ships with the unit when making adjustments. A copy of the manual  
Yaskawa GPD-305 Drive  
Parameter  
Access Level  
Setting  
n01  
n30  
n32  
n33  
n36  
n40  
n41  
n42  
n46  
n58  
n01  
1
Ref Upper Limit  
Motor Rated FLA  
100% or 66%*  
Motor FLA  
Elect Thermal Overload  
Multi-Function input (terminal S2)  
Multi-Function output (MA,MB,MC)  
Analog Freq. Reference Gain  
Analog Freq. Reference Bias  
Carrier Frequency  
1
10  
4
0
99  
2
Frequency Detection Level  
Access Level  
20  
0
21  
*36 inch wheel is 66% (40Hz). All other wheels are 100% (60Hz).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL ACCESSORIES  
Wiring Diagram  
Following is an example of a typical wiring diagram located in the unit control center. This wiring diagram  
includes a legend highlighting which accessories were provided with the unit. Factory wiring and field wiring  
are also indicated. This particular example includes 1) variable frequency drives on the blowers requiring a  
modulating input, 2) modulating energy recovery wheel with factory controls for economizer, 3) energy recovery  
wheel rotation sensor, 4) outdoor air and exhaust air dirty filter switches, 5) motorized outdoor air and exhaust  
air intake dampers, and 6) timed exhaust frost control. Many other factory installed and wired accessories are  
available.  
DS1  
L1  
T1  
T2  
T3  
L1  
VFD-E  
MAIN POWER  
TO UNIT  
L2  
L3  
LEGEND  
L2  
L3  
S1 SC FR FC  
R3  
CC COMPRESSOR CONTACTOR  
CF CONDENSING FAN CONTACTOR  
CH COMPRESSOR SUMP HEATER  
EXHAUST FAN  
MOTOR  
GROUND  
1
3
0-10 VDC  
D
DAMPER  
*
T1  
T2  
T3  
L1  
VFD-S  
DB POWER DISTRIBUTION BLOCK  
DL DAMPER LIMIT SWITCH  
DS DISCONNECT SWITCH  
EC ECONOMIZER CONTROLLER  
FCS CONDENSOR FAN CYCLE SWITCH  
FU FUSES  
L2  
L3  
*
*
S1 SC FR FC  
R4  
SUPPLY FAN  
MOTOR  
1
3
0-10 VDC  
FU5 CONTROL TRANSFORMER FUSES (NOT ON CLASS II)  
FZ1 FREEZE PROTECTION  
HPS HIGH PRESSURE SWITCH (MANUAL RESET)  
LPS LOW PRESSURE SWITCH  
PS1 WHEEL FROST PRESSURE SWITCH  
PS2 SUPPLY DIRTY FILTER PRESSURE SWITCH  
PS3 EXHAUST DIRTY FILTER PRESSURE SWITCH  
R1 ENERGY WHEEL RELAY/CONTACTOR  
R2 OCCUPIED/UNOCCUPIED RELAY  
R3 EXHAUST BLOWER VFD RELAY  
R4 SUPPLY BLOWER VFD RELAY  
R5 MODULATING WHEEL FROST CONTROL RELAY  
R6 ECONOMIZER RELAY  
*
L1  
L2  
L3  
S1  
T1  
T2  
T3  
VFD-W  
*
*
*
*
ENERGY WHEEL  
SC  
FR FC MA MC  
R1  
SEE BELOW FOR  
TERMINAL CONNECTIONS  
3
4
*
*
FU5  
TR1  
R7 COMPRESSOR INTERLOCK RELAY  
R8 EVAP RELAY (INDIRECT)  
R9 EVAP RELAY (DIRECT)  
R10 UNIT RELAY  
S1 FAN SWITCH  
S2 ROTATION SENSOR REED SWITCH  
S3 ROTATION SENSOR REED SWITCH  
S4 CALL FOR HEAT SWITCH  
MULTI-VOLTAGE PRIMARY  
24 SECONDARY  
o
*
R
C
S5 BYPASS SWITCH  
o
S6 CALL FOR COOL SWITCH (FIRST STAGE)  
S7 CALL FOR COOL SWITCH (SECOND STAGE)  
ST MOTOR STARTER  
T1 FROST CONTROL TIMER  
TYPICAL SETTINGS t1(OFF) = 5 MIN., t2(ON) = 30 MIN.  
T2 ROTATION SENSOR TIMER  
*
*
S1  
EXHAUST DAMPER  
D1  
R3  
G
*
T3 ROTATION SENSOR TIMER  
T4 ECONOMIZER WHEEL JOG TIMER  
TYPICAL SETTINGS t1(OFF) = 3 HRS., t2(ON) = 10 SEC.  
T5 EVAP DELAY OFF TIMER  
VFD-E O.L.  
MB MC  
EXHAUST FAN  
2
7
T6 COMPRESSOR MINIMUM OFF TIMER (TYP. 3 MIN.)  
T7 COMPRESSOR MINIMUM OFF TIMER (TYP. 3 MIN.)  
TR TRANSFORMER  
TS1 FROST CONTROL THERMOSTAT (JUMPER - HEAT )  
CLOSES ON TEMP. DECREASE TYPICAL SETTING 5 F.  
*
*
SUPPLY DAMPER  
D2  
R4  
R1  
4
º
TS2 ECONOMIZER LOW LIMIT THERMOSTAT (JUMPER - HEAT )  
VFD-S O.L.  
R3  
T1  
º
º
OPENS ON TEMP. DECREASE TYP. SETTING 20 OFFSET OR 50 F.  
SUPPLY FAN  
TS3 ECONOMIZER UPPER LIMIT THERMOSTAT (JUMPER - HEAT)  
6
8
16  
2
7
15  
MB  
MC  
º
º
CLOSES ON TEMP. DECREASE TYP. SETTING 65 F./2 DIFF.  
TS4 ROOM OVERRIDE SENSOR  
TS5 INLET AIR POST HEATER LOCKOUT THERMOSTAT (AFTER WHEEL)  
CLOSES ON TEMP. DECREASE TYPICAL SETTING 65 F.  
TS6 INLET AIR COMPRESSOR LOCKOUT THERMOSTAT (JUMPER-HEAT)  
OPENS ON TEMP. DECREASE TYPICAL SETTING 60 F./2 DIFF.  
ENERGY WHEEL  
ROTATION SENSOR  
º
A2  
A1  
TO MA AND MC  
ON VFD-W  
MA  
º
º
MC  
1
C
S2  
T2  
6
2
NC  
12  
FACTORY SUPPLIED AND WIRED  
*
o
FIELD WIRED  
OA-SENSOR  
SENSOR  
FIELD CONTROL WIRING RESISTANCE SHOULD NOT EXCEED 0.75 OHM. IF  
RESISTANCE EXCEEDS 0.75 OHM THEN CONSULT FACTORY. USE 14 GAUGE  
MINIMUM WIRE THICKNESS FOR CONTROL WIRING.  
24 VAC  
THERMOSTAT(S) TS1,  
COM  
THERMOSTAT CONTROLLER(S)  
FROST CONTROL  
B1  
PS1  
NO  
TS1  
REPLACEMENT FUSES: MUST HAVE A MINIMUM I.R. RATING OF 5 KA  
6
T1  
C
COM  
NO  
A1  
A2  
CAUTION:  
UNIT SHALL BE GROUND IN ACCORDANCE WITH N.E.C.  
POWER MUST BE OFF WHILE SERVICING.  
S6  
Y1  
ECONOMIZER CONTROL  
TR  
1
TR1  
EC  
+
-
FR  
FC  
TO FR AND FC  
ON VFD-W  
2-10V  
USER INTERFACE CONNECTIONS:  
SR  
SR+  
SO  
SO+  
T
T1  
620 OHM RESISTOR OR  
RETURN AIR SENSOR  
USER TO VERIFY THAT TR1 CAN HANDLE THE VA LOAD OF INDICATOR DEVICES.  
DIRTY FILTER INDICATOR SHOWN AS 24V POWER FROM UNIT.  
PS2  
OUTDOOR AIR  
SENSOR  
5
2
MIXED AIR  
SENSOR  
C
NC  
NO  
SUPPLY DIRTY  
FILTER SWITCH  
R
C
PS3  
4
3
C
NC  
NO  
EXHAUST DIRTY  
FILTER SWITCH  
R
C
C
FROST CONTROL INDICATOR  
ROTATION INDICATOR  
6
12  
C
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL ACCESSORIES  
Rotation Sensor  
The rotation sensor monitors energy recovery wheel rotation. If the wheel should stop rotating, the sensor will  
close a set of contacts in the unit control center. Field wiring of a light (or other alarm) between terminals R  
& 12 in the unit control center will notify maintenance personnel when a failure has occurred (refer to Remote  
Panel Wiring Schematics section for wiring details).  
Dirty Filter Sensor  
Dirty filter sensors monitor pressure drop across the outdoor air filters, exhaust air filters, or both. If the  
pressure drop across the filters exceeds the set point, the sensor will close a set of contacts in the unit control  
center. Field wiring of a light (or other alarm) to these contacts will notify maintenance personnel when filters  
need to be replaced.  
The switch has not been set at the factory due to external system losses that will affect the switch. This switch  
will need minor field adjustments after the unit has been installed with all ductwork complete. The dirty filter  
switch is mounted in the exhaust inlet compartment next to the unit control center or in unit control center.  
To adjust the switch, the unit must be running  
with all of the access doors in place, except for  
the compartment where the switch is located  
Setscrew (on front of switch) must be manually  
adjusted after the system is in operation.  
(exhaust inlet compartment). Model ERV units  
require the opening around the control center  
to be covered (with cardboard, plywood, etc.)  
to set up dirty filter switch. The adjusting  
Positive pressure connection is toward the  
screw is located on the top of the switch.  
Open the filter compartment and place a  
sheet of plastic or cardboard over 50% of the  
filter media. Replace the filter compartment  
door. Check to see if there is power at the alert  
signal leads (refer to electrical diagram). If there  
is no power, turn the adjustment screw on  
the dirty filter gauge clockwise until you have  
power. Open the filter compartment and remove  
“front or top” of the switch (senses air inlet  
side of filters)  
Negative pressure connection is toward the “back or bottom”  
of the switch (senses blower side of filters)  
the obstructing material. Replace the door and check to make sure that you do not have power at the alert  
signal leads. The unit is now ready for operation.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL ACCESSORIES  
CO2 Sensor  
This accessory is often used to provide a modulating control signal to a variable frequency drive to raise and  
lower airflow in relationship to the CO2 levels in the space. This strategy is often referred to as Demand Control  
Ventilation and provides further energy savings to the system. Follow instructions supplied with sensor for  
installation and wiring details.  
Service Outlet  
120 VAC GFCI service outlet ships loose for field  
installation. Requires separate power source so power  
is available when unit main disconnect is turned off for  
servicing.  
Vapor Tight Lights  
Vapor tight lights provide light to each of the compartments  
in the energy recovery unit. The lights are wired to a switch  
mounted on the outside of the unit. The switch requires  
a separate power source to allow for power to the lights  
when the unit main disconnect is off for servicing.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL ACCESSORIES  
Remote Control Panel and Wiring Schematics  
The remote panel is a series of junction boxes ganged  
together and includes a stainless steel face plate. The  
remote panel is available with a number of different alarm  
lights and switches to control the unit. The remote panel  
ships loose and requires mounting and wiring in the field.  
The remote panel is available with the following options:  
• Unit on/off switch  
• Unit on/off light  
• 7-day time clock  
• Hand/off/auto switch  
• Time delay override  
• Exhaust air dirty filter light  
• Outdoor air dirty filter light  
• Economizer light  
• Frost control light  
• Wheel rotation sensor light  
Refer to Electrical Connections section for Field Control Wiring recommendations.  
7-Day Timer or On/Off Switch  
7-Day Timer  
R
Terminal Block  
in  
Timer  
Override  
C
G
Unit Control  
Center  
S1 - Unit On/Off  
For 7-Day Timer, use blue and black wires.  
Red wires should be capped off.  
Hand/Off/Auto Switch  
R
C
G
Terminal Block  
in  
Unit Control  
Center  
On  
Off  
BMS  
Auto  
Hand/Off/Auto Switch allows the unit to  
“Off” - off  
“On” - Manual Operation  
“Auto” - Unit is controlled by BMS, RTU, etc.  
NOTE: RTU controllers are by others.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL ACCESSORIES  
Remote Panel Wiring Schematics  
Indicator Lights  
powered by the ER Unit  
R
C
Unit On/Off  
G
Y1  
Y2  
W1  
6
Frost Control  
Economizer  
7
Rotation Sensor  
12  
PS2  
Supply Dirty Filter  
NC  
C
NO  
PS3  
Exhaust Dirty Filter  
NC  
C
NO  
Dirty Filter Indicator  
(Power by Others)  
PS2  
C
NC  
NO  
Supply Dirty Filter  
Exhaust Dirty Filter  
PS3  
C
NC  
NO  
Hot  
L1  
Refer to Pressure Switch for voltage and load ratings.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL ACCESSORIES  
Remote Panel Wiring Schematics  
Heating/Cooling Switches and Night Setback  
Switch/Timer  
R
C
Unit On/Off  
G
S1  
S6  
S7  
S4  
Econ/First Stage Cooling  
Second Stage Cooling  
Heat  
Y1  
Y2  
W1Terminal Block in  
Unit Control  
Center  
6
7
12  
Night Setback Timer  
Night Setback Switch  
S5  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL ACCESSORIES  
Sensors Mounted by Factory  
Factory mounted temperature, pressure, and current sensors are available in the locations indicated on the unit  
diagram below. A list of available sensors is shown below. The specific sensors provided on a given unit are  
labeled in the unit control center on the terminal strip. Sensors are wired to the terminal strip to make it easy for  
the controls contractor to connect the Building Management System for monitoring purposes.  
EW-P  
RAF-P  
EF-A  
EAW  
RAI  
RA  
FILTER  
TO  
OUTSIDE  
FROM INSIDE  
EXHAUST  
BLOWER  
OAF-P  
OAI  
OAAW  
OAF-A  
OA  
FILTER  
COOL  
COIL  
HEAT  
COIL  
FROM  
OUSTIDE  
TO INSIDE  
SUPPLY  
BLOWER  
ACC  
OAD  
OAW-P  
Temperature Sensors - 1K Ohm RTD  
Drawing Labels  
OAI  
Terminal Strip Labels  
OA/Supply Inlet Temp  
OA After  
OAAW  
ACC  
After Cooling Coil Temp  
Supply Discharge Temp  
OAD  
EAW  
Exhaust After Wheel Temp  
RA/Exhaust Inlet Temp  
RAI  
Pressure Sensors (analog or digital)  
Drawing Labels  
OAF-P  
Terminal Strip Labels  
OA/Supply Filter Pressure  
Outdoor Air Wheel Pressure  
RA/Exhaust Filter Pressure  
Exhaust Wheel Pressure  
OAW-P  
RAF-P  
EW-P  
Amp - Current Sensors (analog or digital)  
Drawing Labels  
OAF-P  
Terminal Strip Labels  
Supply Fan Amps  
Exhaust Fan Amps  
EF-A  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START-UP CHECKLIST FOR UNIT  
SAFETY DANGER!  
Electric shock hazard. Can cause injury or death.  
Before attempting to perform any service or  
maintenance, turn the electrical power to unit to OFF  
at disconnect switch(es). Unit may have multiple  
power supplies.  
SAFETY CAUTION!  
Use caution when removing access panels or other  
unit components, especially while standing on a  
ladder or other potentially unsteady base. Access  
panels and unit components can be heavy and  
serious injury may occur.  
SAFETY CAUTION!  
CAUTION!  
Do not operate energy recovery ventilator without  
the filters and birdscreens installed. They prevent the  
entry of foreign objects such as leaves, birds, etc.  
Do not run unit during construction phase. Damage  
to internal components may result and void warranty.  
Every installation requires a comprehensive start-up to ensure proper operation of the unit. As part of  
that process, the following checklist must be completed and information recorded. Starting up the unit in  
accordance with this checklist will not only ensure proper operation, but will also provide valuable information  
to personnel performing future maintenance. Should an issue arise which requires factory assistance, this  
completed document will allow unit experts to provide quicker resolve. Qualified personnel should perform  
start-up to ensure safe and proper practices are followed.  
Unit Model Number ____________________________ (e.g. HRE-55)  
Unit Serial Number ____________________________ (e.g. 04C99999)  
Energy Wheel Date Code ____________________________ (e.g. 0450)  
Start-up date ____________________________ (MM/DD/YYYY)  
Start-up Personnel Name ____________________________  
Start-up Company ____________________________  
Phone Number ____________________________  
Pre-Start Up Checklist - check boxes as items are completed  
o
o
o
Disconnect and lock-out all power switches  
Remove any foreign objects that are located in the energy recovery unit.  
Check all fasteners, set-screws, and locking collars on the fans, bearings, drives, motor bases and  
accessories for tightness.  
o
o
o
Rotate the fan wheels and energy recovery wheels by hand and ensure no parts are rubbing. If rubbing  
occurs, refer to Start-Up section for more information.  
Check the fan belt drives for proper alignment and tension (refer to Start-Up section for more  
information).  
Filters can load up with dirt during building construction. Replace any dirty pleated filters and clean the  
aluminum mesh filters in the intake hood (refer to Routine Maintenance section).  
o
o
o
o
Verify that non-motorized dampers open and close properly.  
Check the tightness of all factory wiring connections.  
Verify control wire gauge (refer to the Electrical Connections section).  
Verify diameter seal settings on the energy recovery wheel (refer to Start-Up section for more  
information.  
o
o
Verify proper drain trap installation (refer to Drain Trap section).  
For plenum or BI fans, check the radial gap and overlap. Adjust if necessary.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START-UP CHECKLIST FOR UNIT  
Special Tools Required  
Voltage Meter (with wire probes)  
Amperage Meter  
Incline manometer or equivalent  
Tachometer  
Thermometer  
Start-Up Checklist  
The unit will be in operational mode during start-up. Use necessary precautions to avoid injury. All data must  
be collected while the unit is running. In order to measure volts & amps, the control center door must be open,  
and the unit energized using a crescent wrench to turn the disconnect handle.  
Line Voltage - check at unit disconnect  
L1-L2 ________ Volts  
L2-L3 ________ Volts  
L1-L3 _______ Volts  
Motor Amp Draw:  
Supply Motor Amps  
Exhaust Motor Amps  
L1  
L1  
________ Amps  
________ Amps  
L2  
L2  
________ Amps  
________ Amps  
L3 ________ Amps  
L3 ________ Amps  
Fan RPM:  
Supply Fan RPM _____________  
Exhaust Fan RPM _____________  
Correct fan rotation direction:  
Supply Fan  
Exhaust Fan  
Yes / No  
Yes / No  
START-UP CHECKLIST FOR EVAPORATIVE COOLER  
Evaporative coolers are an integral part of the unit and must be set up properly. Doing so will ensure correct  
operation and avoid water or leakage problems. HRE units will have one or two evaporative coolers. The  
following checklist must be completed for each evaporative cooler. Qualified personnel should perform  
installation and be present for start-up to ensure safe and proper practices are followed. Please refer to the  
Evaporative Cooling Modules section for detailed information on start-up items below.  
Indirect Evap  
Direct Evap  
Connect overflow line (run bleed line into overflow)  
Connect drain line  
o
o
o
o
o
o
o
o
Install trap  
Connect water supply line  
For units with Auto Drain & Fill with Freeze Protection  
Install, wire, and provide power to components  
Confirm temperature and timer settings  
Pump filter clean and installed properly  
Saturate media per IOM  
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
Adjust bleed-off rate per IOM  
Check for water carryover  
Connect ‘Call for Cooling’ signal  
Remove jumper wire  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL ACCESSORIES CHECKLIST  
Refer to the respective sections in this Installation, Operation and Maintenance Manual for detailed information.  
Refer to wiring diagram in unit control center to determine what electrical accessories were provided.  
Provided with Unit? Frost Control Application / Operation section:  
Setting  
Factory Default  
Yes  
No  
Frost Control Setpoint  
Differential  
5ºF  
2ºF  
Timer  
Refer to IOM  
Refer to IOM  
Yes  
No  
Frost Control Modulating  
Economizer Application / Operation section:  
Yes  
No  
Economizer (temperature)  
Setpoint  
65ºF  
20ºF  
2ºF  
Offset  
Differential  
Yes  
Yes  
No  
No  
Economizer (enthalpy)  
Setpoint  
B
Economizer (modulating)  
Refer to IOM  
Optional Accessories section:  
Operational  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
No  
No  
No  
No  
Wheel Rotation Sensor  
OA Dirty Filter Sensor  
EA Dirty Filter Sensor  
CO2 Sensor  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
No  
No  
No  
No  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
Service Outlet  
Vapor Tight Lights  
Remote Control Panel  
Variable Frequency Drives section:  
Operational  
Yes  
Yes  
No  
No  
Blower VFDs  
Wheel VFD  
Yes  
Yes  
No  
No  
N/A  
N/A  
Damper section:  
Operational  
Yes  
Yes  
Yes  
No  
No  
No  
Outdoor Air Damper  
Exhaust Air Damper  
Night Setback Damper  
Yes  
Yes  
Yes  
No  
No  
No  
N/A  
N/A  
N/A  
Yes  
No  
Indirect Gas Furnace (refer to the PVF IOM, Part #461006 for start-up information)  
Indirect Evaporative Cooler Section (refer to Evap Start-Up checklist on following page)  
Direct Evaporative Cooler Section (refer to Evap Start-Up checklist on following page)  
Standard  
Yes  
No  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT START-UP  
Refer to Parts List section for component locations.  
Fans (Forward Curved Type)  
The HRE Models contain a forward curved supply fan and  
a forward curved exhaust fan. These forward curved fans  
should be checked for free rotation. If any binding occurs,  
check for concealed damage and foreign objects in the fan  
housing. Be sure to check the belt drives per the start-up  
recommendations in the following section.  
Fan Performance Modifications  
Due to job specification revisions, it may be necessary to  
adjust or change the sheave or pulley to obtain the desired  
airflow at the time of installation. Start-up technician must  
check blower amperage to ensure that the amperage listed  
on the motor nameplate is not exceeded. Amperage to be  
tested with access doors closed and ductwork installed.  
SAFETY CAUTION!  
When operating conditions of the fan are to be  
changed (speed, pressure, temperature, etc.),  
consult Greenheck to determine if the unit can  
operate safely at the new conditions.  
Fan Belt Drives  
The fan belt drive components, when supplied by Greenheck, have been carefully selected for the unit’s  
specific operating condition. Caution: utilizing different components than those supplied could result in unsafe  
operating conditions which may cause personal injury or failure of the following components: 1) Fan Shaft, 2)  
Fan Wheel, 3) Bearings, 4) Belt, 5) Motor. Tighten all fasteners and set screws securely and realign drive pulleys  
after adjustment. Check pulleys and belts for proper alignment to avoid unnecessary belt wear, noise, vibration  
and power loss. Motor and drive shafts must be parallel and pulleys in line (see below).  
Belt Drive Installation  
1. Remove the protective coating from the end of the fan shaft and  
assure that it is free of nicks and burrs.  
2. Check fan and motor shafts for parallel and angular alignment.  
3. Slide sheaves on shafts - do not drive sheaves on as this may result  
in bearing damage.  
4. Align fan and motor sheaves with a straight-edge or string and  
tighten.  
5. Place belts over sheaves. Do not pry or force belts, as this could  
result in damage to the cords in the belts.  
6. With the fan off, adjust the belt tension by moving the motor base. (See  
belt tensioning procedures in the Routine Maintenance section of this  
manual). When in operation, the tight side of the belts should be in a  
straight line from sheave to sheave with a slight bow on the slack side.  
WRONG  
WRONG  
WRONG  
CORRECT  
Proper alignment of motor and drive shaft.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT START-UP  
Direction of Fan Wheel Rotation  
Blower access is labeled on unit. Check for proper wheel rotation by momentarily  
energizing the fan. Rotation is determined by viewing the wheel from the drive  
side and should match the rotation decal affixed to the fan housing (see Rotation  
Direction figures). If the wheel is rotating the wrong way, direction can be reversed  
by interchanging any two of the three electrical leads. Check for unusual noise,  
vibration, or overheating of bearings. Refer to the Troubleshooting section of this  
manual if a problem develops.  
Airflow  
Fan RPM  
Supply fan and exhaust fan will have an adjustable motor pulley (on 15 HP and  
below) preset at the factory to the customer specified RPM. Fan speed can be  
increased or decreased by adjusting the pitch diameter of the motor pulley. Multi-  
groove variable pitch pulleys must be adjusted an equal number of turns open or  
closed. Any increase in fan speed represents a substantial increase in load on the  
motor. Always check the motor amperage reading and compare it to the amperage  
rating shown on the motor nameplate when changing fan RPM. All access doors  
must be installed except the control center door. Do not operate units with access  
doors open or without proper ductwork in place as the fan motors will overload.  
Rotation Direction  
Vibration  
Excessive vibration may be experienced during initial start-up. Left unchecked, excessive vibration can cause  
a multitude of problems, including structural and/or component failure. The most common sources of vibration  
are listed below.  
1. Wheel Unbalance  
Many of these conditions can be discovered by careful observation. Refer  
to the Troubleshooting section of this manual for corrective actions. If  
observation cannot locate the source of vibration, a qualified technician using  
vibration analysis equipment should be consulted. If the problem is wheel  
unbalance, in-place balancing can be done.  
2. Drive Pulley Misalignment  
3. Incorrect Belt Tension  
4. Bearing Misalignment  
5. Mechanical Looseness  
6. Faulty Belts  
7. Drive Component Unbalance  
8. Poor Inlet/Outlet Conditions  
9. Foundation Stiffness  
Generally, fan vibration and noise is transmitted to other parts of the building  
by the ductwork. To eliminate this undesirable effect, the use of heavy canvas  
connectors is recommended.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT START-UP  
Energy Recovery Wheel  
The HRE models contain a sensible energy recovery wheel. The  
wheels are inspected for proper mechanical operation at the  
factory. However, during shipping and handling, shifting can occur  
that may affect wheel operation. The wheel is accessible through  
the access door marked “Energy Wheel Cassette Access”. For  
the HRE-20 AND HRE-45 models, the wheel cassette slides out.  
Due to the size and weight of the HRE-55 AND HRE-90 wheels,  
they remain stationary and all maintenance is performed in place.  
There is room inside the unit to perform energy recovery wheel  
servicing.  
Turn the energy recovery wheels by hand to verify free operation.  
The wheel should rotate smoothly and should not wobble.  
Inside layout of HRE unit  
Drive Belt  
Inspect the drive belt. Make sure the belt rides smoothly through the pulley and over the wheel rim.  
Air Seals  
Air seals are located around the perimeter of the  
Bearing Support  
wheel and across the face of the wheel (both sides  
of wheel). Check that these seals are secure and in  
good condition.  
Adjustable  
Air Seals  
Check that the air seals located around the outside  
of the wheel and across the center (both sides of  
wheel) are secure and in good condition. Air seal  
clearance is determined by placing a sheet of  
paper, to act as a feeler gauge, against the wheel  
face. To access seals, enter unit for HRE-55 &  
HRE-90, or pull out the cassette for HRE-20 & HRE-  
45, following the instructions in Energy Recovery  
Wheel Maintenance section. To adjust the air seals,  
loosen all eight seal retaining screws. These screws  
are located on the bearing support that spans the  
length of the cassette through the wheel center.  
Label showing  
cassette serial #  
and date code  
Drive Belt  
Drive Pulley  
Tighten the screws so the air seals tug slightly on the sheet of paper.  
Replace cassette into unit, plug in wheel drive, replace access door and apply power. Observe by opening door  
slightly (remove filters if necessary to view wheel) that the wheel rotates freely at about 35 RPM.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ROUTINE MAINTENANCE  
SAFETY CAUTION!  
SAFETY DANGER!  
Electric shock hazard. Can cause injury or death.  
Before attempting to perform any service or  
maintenance, turn the electrical power to unit to OFF  
at disconnect switch(es). Unit may have multiple  
power supplies.  
Use caution when removing access panels or other  
unit components, especially while standing on a  
ladder or other potentially unsteady base. Access  
panels and unit components can be heavy and  
serious injury may occur.  
Once the unit has been put into operation, a routine maintenance program should be set up to preserve  
reliability and performance. Items to be included in this program are:  
DATE  
DATE  
DATE  
DATE  
_____  
______  
______  
______  
Lubrication  
Apply lubrication where required  
Dampers  
Check for unobstructed operation  
Fan Belts  
Check for wear, tension, alignment  
Motors  
Check for cleanliness  
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
Blower Wheel & Fasteners  
Check for cleanliness  
o
o
o
o
o
o
o
o
o
o
o
o
Check all fasteners for tightness  
Check for fatigue, corrosion, wear  
Bearings  
Check for cleanliness  
o
o
o
o
o
o
o
o
o
o
o
o
Check set screws for tightness  
Lubricate as required  
External Filter  
Check for cleanliness - clean if required  
Internal Filter  
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
Check for cleanliness - replace if required  
Door Seal  
Check if intact and pliable  
Coil Maintenance  
Check for cleanliness (coil and drain pan)  
Winterizing Coils  
Drain - Fill with antifreeze - Drain  
Energy Recovery Wheel  
Check for cleanliness - clean if required  
Check belt for wear  
o
o
o
o
o
o
o
o
o
o
o
o
Check pulley, bearings, and motor  
Evap Cooler Section  
Refer to Evaporative Cooler Maintenance section  
o
o
o
o
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ROUTINE MAINTENANCE  
Lubrication  
Check all moving components for proper lubrication. Apply lubrication where required. Any components  
showing excessive wear should be replaced to maintain the integrity of the unit and ensure proper operation.  
Dampers  
Check all dampers to ensure they open and close properly and without binding. Backdraft dampers can be  
checked by hand to determine if blades open and close freely. Apply power to motorized dampers to ensure  
the actuator opens and closes the damper as designed.  
Fan Belts  
Belts must be checked on a regular basis for wear, tension, alignment, and dirt accumulation. Premature  
or frequent belt failures can be caused by improper belt tension (either too loose or too tight) or misaligned  
sheaves. Abnormally high belt tension or drive misalignment will cause excessive bearing loads and may result  
in failure of the fan and/or motor bearings. Conversely, loose belts will cause squealing on start-up, excessive  
belt flutter, slippage, and overheated sheaves. Both loose and tight belts can cause fan vibration.  
When replacing belts on multiple groove drives, all belts should be changed to provide uniform drive loading.  
Do not pry belts on or off the sheave. Loosen belt tension until belts can be removed by simply lifting the  
belts off the sheaves. After replacing belts, insure that slack in each belt is on the same side of the drive. Belt  
dressing should never be used.  
Do not install new belts on worn sheaves. If the sheaves have grooves worn in them, they must be replaced  
before new belts are installed.  
The proper belt setting is the lowest tension  
at which the belts will not slip under peak load  
operation. For initial tensioning, set the belt  
deflection at 1/64-inch for each inch of belt span  
(measured half-way between sheave centers).  
For example, if the belt span is 64 inches, the  
belt deflection should be 1 inch (using moderate  
thumb pressure at mid-point of the drive). Check  
belt tension two times during the first 24 hours of  
operation and periodically thereafter.  
Belt Span  
64  
Deflection =  
Belt Span  
Proper fan belt settings  
Fan Motors  
Motor maintenance is generally limited to cleaning and lubrication. Cleaning  
should be limited to exterior surfaces only. Removing dust and grease buildup  
on the motor housing assists proper motor cooling. Never wash-down motor  
with high pressure spray. Greasing of motors is only intended when fittings are  
provided. Many fractional motors are permanently lubricated for life and require  
no further lubrication.  
Fan Wheel & Fasteners  
Wheels require very little attention when moving clean air. Occasionally oil and  
dust may accumulate on the wheel causing imbalance. When this occurs the  
wheel and housing should be cleaned to assure smooth and safe operation.  
Inspect fan impeller and housing for fatigue, corrosion or wear.  
Routinely check all fasteners, set screws and locking collars on the fan, bearings, drive, motor base and  
accessories for tightness. A proper maintenance program will help preserve the performance and reliability  
designed into the fan.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ROUTINE MAINTENANCE  
Bearings  
Most bearings are permanently lubricated and require not further lubrication under normal use. Normal use  
being considered -20ºF to 120ºF and in a relatively clean environment. Some bearings are re-lubricatable and  
will need to be regreased depending on fan use. Check your bearings for grease zert to find out what type of  
bearing you have. If your fan is not being operated under normal use, bearings should be checked monthly for  
lubrication.  
External Filter Maintenance  
Aluminum mesh, 2-inch deep filters are located in the  
supply weatherhood (if the weatherhood option was  
purchased). Filters should be checked and cleaned on  
a regular basis for best efficiency. The frequency of  
cleaning depends upon the cleanliness of the incoming  
air. These filters should be cleaned prior to start-up.  
To access these filters, remove bottom bolt in the access  
door on the side of the weatherhood. Slide the access  
door up and then pull bottom out to remove door. Then,  
slide the filters out (see figure at right).  
Clean filters by rinsing with a mild detergent in warm  
water.  
Internal Filter Maintenance  
Outdoor air intake hood  
mesh filter access  
The HRE units will typically be provided with 2-inch,  
pleated filters in the outdoor air and exhaust airstreams.  
These filters should be checked per a routine  
maintenance schedule and replaced as necessary to  
ensure proper airflow through the unit. See table at  
right for pleated filter size and quantity for each unit.  
Replacement filters shall be of same performance and  
quality as factory installed filters. Filter type must be  
pleated design with integral metal grid. Two acceptable  
Filter Size and Quantities  
Internal  
Filter Size  
Quantity  
Supply  
Quantity  
Exhaust  
Model  
®
filter replacements are Aerostar Series 400 or Farr 30/30 .  
HRE-20  
HRE-45  
HRE-55  
HRE-90  
20 in. x 20 in.  
20 in. x 25 in.  
16 in. x 25 in.  
20 in. x 20 in.  
2
3
6
8
2
3
6
8
Outdoor Air Filters: Access to the outdoor air filters  
is through the door labeled as “Filter Access” on the  
outdoor air side of the unit.  
Exhaust Air Filters: Access to the exhaust air filters  
is through the door labeled as “Filter Access” on the  
exhaust air side of the unit.  
Refer to Access Door Descriptions section for additional  
information on filter locations.  
Door Seal Maintenance  
Slip-on type vinyl seal is installed on the perimeter of the  
door openings. Inspect at least annually to ensure that  
seal is still pliable and intact.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ROUTINE MAINTENANCE  
Energy Recovery Wheel Maintenance  
Annual inspection of the energy recovery wheel is recommended. Units  
ventilating smoking lounges and other non-clean air spaces should  
have energy recovery wheel inspections more often based upon need.  
Inspections for smoke ventilation applications are recommended  
bimonthly to quarterly until a regular schedule can be established.  
ACCESSING ENERGY RECOVERY WHEEL  
The HRE units have one energy recovery wheel. Open the outdoor  
air filter door to access the wheel. For the HRE-20 and HRE-45  
models, the wheel cassette slides out. Due to the size and weight  
of the HRE-55 and HRE-90 wheels, they remain stationary and all  
maintenance is performed in place. There is room inside the unit to  
perform energy recovery wheel servicing. Filters must be removed to  
access stationary wheels.  
**WARNING: Disconnect power to the unit before performing  
any type of service.  
Access to wheel through  
outdoor air filter door  
REMOVING THE ENERGY RECOVERY WHEEL SEGMENTS  
Models HRE-20, 45, 55, & 90  
Bracket Segment Retainer  
Steel retainers are located on the  
inside of the wheel rim (see diagram  
Lift Away  
From Segment  
at right). Push the retainer toward  
center of wheel, then lift up and  
Catch-  
Segment Retainer  
Inside of Wheel Rim  
Spoke  
away to release segments (see  
below).  
Push Toward Center  
Center of Wheel  
IMPORTANT! PLACE RETAINERS BACK IN THE  
ORIGINAL POSITION BEFORE  
ROTATING THE ENERGY RECOVERY WHEEL.  
OTHERWISE DAMAGE TO RETAINER WILL  
OCCUR.  
Wheel segment removed  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ROUTINE MAINTENANCE  
CLEANING THE ENERGY RECOVERY WHEEL  
If the wheel appears excessively dirty, it should be cleaned to ensure maximum operating efficiency. Only  
excessive buildup of foreign material needs to be removed. DISCOLORATION AND STAINING OF ENERGY  
RECOVERY WHEEL DOES NOT AFFECT ITS PERFORMANCE.  
®
Thoroughly spray wheel matrix with household cleaner such as Fantastic or equivalent. Gently rinse with  
warm water and using a soft brush remove any heavier accumulation. A detergent/water solution can also be  
used. Avoid aggressive organic solvents, such as acetone. The energy recovery wheel segments can be soaked  
in the above solution overnight for stubborn dirt or accumulation.  
After cleaning is complete, shake the excess water from the wheel or segments. Dry wheel or segments  
before placing them back into the cassette. Place wheel or segments back into cassette by reversing removal  
procedures.  
** DO NOT CLEAN ENERGY RECOVERY WHEEL SEGMENTS WITH WATER IN EXCESS OF 140ºF  
** DO NOT DRY ENERGY RECOVERY WHEEL SEGMENTS IN AIR IN EXCESS OF 140ºF.  
** THE USE OF A PRESSURE WASHER TO CLEAN SEGMENTS IS NOT RECOMMENDED. DAMAGE COULD  
RESULT.  
Energy Recovery Wheel Belt  
Inspect belts each time filters are replaced. Belts that  
look chewed up or are leaving belt dust near the motor  
pulley may indicate a problem with the wheel. Be sure to  
inspect wheel for smooth and unrestricted rotation. If a  
belt requires replacement, contact the local Greenheck  
representative. Instructions for replacement will ship with  
the new belt.  
Wheel Belt & Pulley  
Energy Recovery Wheel Bearings  
In the unlikely event that a wheel bearing fails, access is  
available through the outdoor air filter door and through  
a removable plate in the divider in the unit (accessed  
through the exhaust air filter door). Contact the local  
Greenheck representative for detailed instructions on how  
to replace the bearing.  
Wheel Bearing  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PARTS LIST  
7
8
3
11  
6
1
5
2
9
12  
7
4
10  
Model HRE  
(shown with indirect evaporative  
cooler, optional direct evaporative  
cooler, and indirect gas heater)  
1. Supply blower  
8. Electrical control box (standard features)  
- Single point power  
- Forward curved fan  
- Adjustable motor mount for belt tensioning  
- Adjustable sheaves for speed control  
- Disconnect interlocked with access door  
- Motor starters for the supply blower, exhaust  
blower and energy wheel motors  
- 24 Vac, control circuit with terminal strip  
9. Supply air tempering options  
- Electric heat (requires separate power)  
- Hot water heat  
2. Vibrations isolators (quantity 4 per blower)  
- Neoprene  
3. Energy recovery wheel cassette  
- Indirect gas heat  
4. Removable energy recovery wheel segments  
10. Exhaust blower  
5. Optional supply weatherhood with 2 in. aluminum  
mesh filter  
- Forward curved fan  
- Adjustable motor mount for belt tensioning  
- Adjustable sheaves for speed control  
6. Optional exhaust weatherhood with birdscreen  
11. Indirect evaporative cooler  
12. Direct evaporative cooler  
7. Optional supply and exhaust air filter racks for  
2 in. pleated, 30% efficient filters  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SEQUENCE OF OPERATION  
Basic Unit  
The HRE units are pre-wired such that when a call for outside air is made (via field supplied 24 VAC control  
signal wired to unit control center), the supply fan, exhaust fan and energy wheel are energized and the  
motorized dampers open. The HRE units can be supplied with or without heating and cooling coils. For units  
with coils, controls can be supplied by Greenheck or by the controls contractor. If supplied by the controls  
contractor, they would provide, mount, and wire any temperature controllers and temperature or relative  
humidity sensors required for the unit to discharge air at the desired conditions.  
Summer Operation  
A sensible wheel preconditions the outdoor air (temperature is decreased) by the transfer of energy from the  
cool exhaust air coming out of the indirect evaporative cooler.  
Units supplied with a direct evaporative cooling coil can further cool the air coming off the wheel to levels near  
55ºF.  
Economizer Operation: See Economizer Application/Operation section  
Winter Operation  
Outdoor air is preconditioned (temperature is increased) by the transfer of energy from the warmer exhaust air  
via the sensible recovery wheel.  
Units supplied with heating coils can further heat the air coming off the wheel to levels at or above room  
design.  
Frost Control Operation: See Frost Control Application/Operation section  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Airflow  
Test and Balance Report  
The test and balance report (TAB) is utilized to determine whether the appropriate amount of outdoor air  
and exhaust air is being supplied and removed from a building, respectively. There are no set rules on what  
information must be included in a TAB report. As such, if a TAB report indicates that the airflow on a unit is low,  
prior to contacting the factory, please determine the following information:  
Unit #1  
Unit #2  
Unit #3  
Unit #4  
Model Number  
Serial Number  
Name Plate Information  
Voltage  
Hertz  
Phase  
Outdoor Air Fan Amps  
Exhaust Fan Amps  
Outdoor Air Fan Horsepower  
Exhaust Fan Horsepower  
Design Airflow  
Outdoor Air  
Exhaust  
Measured Airflow  
Outdoor Air  
Exhaust  
Measured Data  
Blower Rotation  
Outdoor Air Fan RPM  
Exhaust Fan RPM  
Outdoor Air Fan Amp Draw  
Exhaust Fan Amp Draw  
Pressure Drop Across Energy Recovery Wheel  
Outdoor Air Side  
Exhaust Side  
Airflow problems can often be tied back to improper ductwork installation. Be sure to install ductwork in  
accordance with SMACNA and AMCA guidelines.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Symptom  
Possible Cause  
Corrective Action  
Blown fuse or open circuit  
breaker.  
Replace fuse or reset circuit breaker and check amps.  
Defective motor or capacitor.  
Motor starter overloaded.  
Electrical.  
Replace.  
Blower Fails to  
Operate  
Reset starter and check amps.  
Check for On/Off switches. Check for correct supply voltage.  
Check for broken or loose belts. Tighten loose pulleys.  
Drive.  
Control power (24 Vac) wiring  
run is too long (resistance  
Shorten wiring run to mechanical room or install a relay  
which will turn unit on/off (C/F for relay information).  
should not exceed 0.75 ohms).  
Motor Starters  
‘Chatter’  
Incoming supply power is  
less than anticipated. Voltage  
supplied to starter coil must  
be within +10% / -15% of  
nominal voltage stated on  
the coil.  
Need to increase supply power or use a special control  
transformer which is sized for the actual supply power.  
or  
Do Not Pull In  
Cfm too high.  
Check cfm and adjust drives if needed.  
Static pressures are higher or  
lower than design.  
If higher, ductwork should be improved.  
If lower, fan rpm should be lower.  
Blower rotation is incorrect.  
Motor voltage incorrect.  
Motor horsepower too low.  
Check rotation and reverse if necessary.  
Motor Over Amps  
Check motor nameplate versus supplied voltage.  
See specifications and catalog for fan curves to determine if  
horsepower is sufficient.  
Shorted windings in motor.  
Unit damper not fully open.  
Replace motor.  
Adjust damper linkage or replace damper motor.  
System static pressure too high Improve ductwork to eliminate losses using good duct  
practices.  
Blower speed too low.  
Check for correct drives and rpm with catalog data.  
Fan wheels are operating  
backwards.  
For 3-phase, see Direction of Fan Wheel Rotation under Unit  
Start-Up section.  
Low Airflow (cfm)  
Dirty filter or energy wheel.  
Leaks in ductwork.  
Follow cleaning procedures in Routine Maintenance section.  
Repair.  
Elbows or other obstructions  
may be obstructing fan outlet.  
Correct or improve ductwork.  
Belt slippage.  
Adjust belt tension.  
Blower fan speed too high.  
Filter(s) not in place.  
Check for correct fan rpm. Decrease fan speed if necessary.  
Install filters.  
High Airflow (cfm)  
Insufficient static pressure (Ps)  
(airflow resistance).  
Induce Ps into system ductwork. Make sure grilles and  
access doors are installed. Decrease fan speed if necessary.  
* Always provide the unit model and serial number when requesting parts or service information. * Always check motor amps and compare to nameplate rating.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Symptom  
Possible Cause  
Corrective Action  
One or Both  
Blowers Turn Off  
Intermittently and  
Back on After  
Blower fan motor overloads are Decrease fan speed.  
tripping and auto-resetting.  
Exhaust Only frost control  
sensors are tripping.  
Adjust frost temperature sensor set point as needed.  
About 2 Minutes  
Air seals are too tight.  
See Energy Recovery Wheel under Unit Start-Up section.  
Adjust temperature or enthalpy set points as needed.  
‘Economizer’ sensors are  
operating.  
Energy Wheel  
Does NOT Turn  
No power to wheel motor.  
Make sure wheel drive is plugged in. Verify power is  
available.  
Wheel drive belt  
Check for loose or broken belts. Replace belts (consult  
factory).  
Wheel motor overloads are  
tripping, due to rubbing  
between wheel and air seals.  
Recheck air seals, make sure they are not too tight. See  
Energy Recovery Wheel under Unit Start-Up Section.  
Energy Wheel  
Runs Intermittently  
Fan wheel rubbing on inlet  
Adjust wheel and/or inlet cone. Tighten wheel hub or bearing  
collars on shaft.  
Bearings.  
Replace defective bearings (s). Lubricate bearings. Tighten  
collars and fasteners.  
Wheel out of balance.  
Replace or rebalance.  
Loose wheel on shaft.  
Tighten wheel setscrew.  
Tighten sheave setscrew.  
Loose motor or blower sheave.  
Excessive Noise or  
Belts too loose.  
Belts too tight.  
Adjust belt tension after 24 hours of operation.  
Vibration  
Loosen to maintain a 3/8 inch deflection per foot of span  
between sheaves.  
Worn belt.  
Replace.  
Motor base or blower loose.  
Build-up of material on wheel.  
Bearing and drive misaligned.  
Tighten mounting bolts.  
Clean wheel and housing.  
Realign.  
Noise being transmitted by  
duct.  
Make sure duct work is supported properly. Make sure duct  
work metal thickness is sized for proper stiffness. Check duct  
size at discharge to ensure that air velocities are not too high.  
*Always provide the unit model and serial number when requesting parts or service information. *Always check motor amps and compare to nameplate rating.  
Warranty  
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from  
the purchase date. The energy recovery wheel is warranted to be free from defects in material and workmanship for a  
period of five years from the purchase date. Any units or parts which prove defective during the warranty period will be  
replaced at our option when returned to our factory, transportation prepaid.  
Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck prove  
defective during this period, they should be returned to the nearest authorized motor service station. Greenheck will not  
be responsible for any removal or installation costs.  
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.  
#461248 IOM HRE FS  
Rev. 4, April 2012  
Copyright © 2012 Greenheck Fan Corp.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Grizzly Paint Sprayer G5353 User Manual
Haier Air Conditioner HWVR08XCK User Manual
Haier Flat Panel Television HL26B User Manual
Harbor Freight Tools Staple Gun 93197 User Manual
Hearth and Home Technologies Ventilation Hood ST1175 User Manual
Heath Zenith Dehumidifier 000703 000 000 User Manual
Hotpoint Range RGB533WEAWW User Manual
Hotpoint Washer BS 1400 User Manual
HP Hewlett Packard Speaker 4275A User Manual
Hubbell Switch LXi 2400 User Manual