Mixed Flow Fans
Belt and Direct Drive
Models QEI-L, QEI, QEID
May
2012
Download from Www.Somanuals.com. All Manuals Search And Download.
Standard Construction
Housing
Slip-Fit Duct Connection (QEI-I/II & QEID)
Tubular housings are constructed of welded steel to
eliminate air leakage. Integral straightening vanes are
constructed from steel and welded into place.
Inlets and outlets are designed with extended collars
for slip-fit duct connections as standard. QEI-L is
flanged as standard. Companion flanges can be
ordered for slip fit connections.
Wheel – Mixed Flow
Adjustable Motor Bases (Belt Drive)
Fabricated wheels are constructed from steel. The
blade profiles are angled and contoured for the most
efficient and quiet performance.
Rigid, heavy-gauge steel motor bases are welded to
the fan housing and include heavy-duty adjustment
screws for belt tensioning.
Bearings (Belt Drive)
Extended Lube Lines
Standard bearings are premium air handling quality,
grease lubricated, self-aligning, ball or roller type.
Bearings are selected with a basic rating fatigue life
Belt drive units have nylon lubrication lines with
grease fittings that allow bearing lubrication without
disassembling the fan. Grease fittings are mounted
on the outside of the fan housing. Direct drive
units have extended lubrication lines for the motor
bearings, if required. Smaller frame sized motors are
typically sealed and not lubricatable.
L
per ABMA standards, in excess of 80,000 hours
10
50
(L at 400,000 hours) at the maximum operating
speed for the QEI-I/II and QEI-L in the horizontal
position. The QEI-L bearings are selected with a
basic rating fatigue life L in excess of 50,000 hours
10
(L at 250,000 hours) in vertical position.
50
Permatector™ Coating
Bolted Access Door
Greenheck’s Permatector coating is a thermosetting
polyester urethane, electrostatically applied to
provide uniform thickness and a clean appearance.
Permatector coatings also provide excellent
corrosion characteristics for general applications,
both indoor and outdoor. For corrosive environments
(ie. coastal), see page 9 for information on our zinc-
rich basecoat technology.
A bolted access door provides an opening through
the fan housing for cleaning or visual inspection of
the wheel. A hinged access door is available as an
accessory.
Belt Guard (Belt Drive)
A totally enclosed belt guard provides protection
from rotating pulleys and belts. Belt guards meet
OSHA Standards.
Model Number Nomenclature
The model number code provides a numbering system designed to identify the fan model,
size and horsepower.
QEI D* - 36 - I - 70 - A 30
Motor Horsepower
D = Direct Drive
4 = ¼
3 =
30 = 3
50 = 5
300 = 30
400 = 40
500 = 50
600 = 60
750 = 75
1000 = 100
1250 = 125
3
Fan Size
5 = ½
7 = ¾
10 = 1
15 = 1½
20 = 2
75 = 7½
100 = 10
150 = 15
200 = 20
250 = 25
9, 12, 15, 16, 18, 20,
22, 24, 27, 30, 33, 36,
40, 44, 49, 54, 60
Belt Drive available in sizes 9 through 60
Direct Drive available in sizes 12 through 54
RPM
Construction
L = Low Pressure
I = Class I
II = Class II
Low Pressure available in sizes 12 through 36
A = 1770 C = 870 J = 1425 M = 3600
B = 1170 F = 690 K = 950 R = 2900
Percent Wheel Width
50 through 100
* Blue text is specific to direct drive model QEID only
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Value Added Features
Quality Assurance Test
Before shipment, all Greenheck mixed flow fans are tested at the design speed after final assembly.
QEI-L fans are checked for amp draw and the levels are recorded. QEI-I/II and QEID fans are
subjected to a complete vibration analysis. The maximum allowable vibration on a QEI-I/II at the fan
bearings is 0.15 in/sec. peak velocity for the specified RPM. QEID maximum vibration is 0.08 in/sec.
peak velocity on the fan housing for the specified RPM. A record
of the vibration test result is available upon request.
By performing the vibration test, we are able to provide more than
wheel balancing, it is also a diagnostic tool for finding potential
problems. A defective bearing or motor, bent shaft or misaligned
sheaves may cause excessive vibration. A
complete vibration test will uncover
these problems before the fan leaves
the factory.
Electrostatic Powder Coatings
Powder coatings offer a uniform, durable and high-quality finish.
Standard powder coating is a one-coat process applied over
a phosphatized surface that generally meets or exceeds the
corrosion resistance of a comparable wet paint.
Greenheck offers a number
of in-house coatings applied
via “electrostatic powder.” The
standard coating, Permatector™,
is excellent for indoor or outdoor
applications and is resistance to
many common chemicals. Consult
Greenheck’s Product Application
Guide, Performance Coatings for
Ventilation Products, for a complete
listing of coatings and a relative
resistance chart. For corrosive environments (i.e. coastal), see page 9
for information on our zinc-rich basecoat technology.
Maintenance / Serviceable Construction Advantages
The following value added features are incorporated into the design to allow for quick and
easy field service.
QEI-L and QEI service advantages:
•
•
•
Bearing lubrication is performed through extended grease fittings located on the
outside of the fan housing.
The entire shaft and bearing assembly can be removed as a single assembly from
the inlet end of the fan housing.
An adjustable motor base is provided for tightening the fan belts.
QEID service advantages:
•
Extended lubrication lines are provided for motor bearing requiring lubrication.
Smaller frame motors use sealed bearings and are permanently lubricated.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Inlet and Outlet Sound Power Levels
All Greenheck mixed flow fans have AMCA licensed sound power levels for both the
fan inlet and outlet.
Application and installation determines which sound power reading (inlet, outlet,
or both) is critical. The differences between the generated sound from the inlet and
outlet are important and noticeable. AMCA licensed inlet and outlet sound power
data provides complete sound information to select a fan based on the acoustical
requirements. For additional information on sound, refer to page 6.
Greenheck’s Sound Lab
Field Rotatable Housing / Compact Size
The QEI-L and QEI are designed to accommodate changing fan
mounting positions and motor orientation in the field. Mounting
fixtures are securely bolted to the fan casing and can be relocated
to reposition how the fan is installed or the position the motor is
oriented. Flexibility in a motor’s location is important for easier
access and can determine where the unit will fit. Last minute
design changes or unexpected obstacles during installation are
no longer a problem.
Greenheck’s mixed flow fans were designed for compact size.
Keeping size to a minimum is important when fitting into tight
spaces like mechanical rooms or air handlers.
Slip-Fit Duct Connections
The inlet and outlet ends of the QEI-I/II and QEID are designed to
accept “slip-fit” connections. Often companion flanges are bolted
to a fan’s inlet/outlet flange to provide a slip-fit connection for a
flexible sleeve, as with the QEI-L. This extra step is now eliminated
by directly attaching the flexible sleeve to the duct and fan. This
saves time and money in the installation process.
It is recommended to use a flexible sleeve connection instead of a
rigid duct connection.
The advantages of a flexible transition are:
• Decreased sound transmission in
the ductwork
• Flexible connections allow for minor
misalignment
• Accommodates the use of thrust
restraints to resist thrust loads
QEID)
USA Patent No. 7048499
China (P.R.) Patent No. CN1294361C
Mexico Patent No. 243465
®
®
AutoCAD and 3-D Revit Models
®
®
Scaled AutoCAD drawings and Revit models
are available through Greenheck’s website
or from the Greenheck CAPS program
which retrieves drawings and places them
automatically into a job folder.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Design & Performance
Mixed Flow: Axial/Centrifugal Hybrid
Centrifugal
A mixed flow wheel is a hybrid between an axial propeller and a
centrifugal wheel. The result is a design that combines the best axial
and centrifugal properties: highly efficient air movement, increased
pressure capabilities, extremely low sound levels, and a steep fan
performance curve. To further enhance the fan’s performance,
straightening vanes are incorporated in the housing. These serve
to convert swirling airflow into a straight axial flow with a resulting
static pressure rise and energy savings.
Mixed Flow
Axial
CFM
Airflow Profiles
Axial Fans: Straight through
nearly linear airflow.
Centrifugal Fans: Two 90°
deflections, before airflow
exits the fan.
Mixed Flow Fans: Slight
airflow deflection from
straight through.
Axial
Centrifugal
Mixed Flow
Sound and Efficiency
Sound power levels and fan efficiency are two very important factors when selecting a fan. There is a noticeable
difference between impeller types. The table and chart below compare the sound power (L A) and the static
w
efficiency of the belt-driven mixed flow fan wheel versus tubular centrifugal and vane axial inline fans. Over a
wide range of operating points, the mixed flow fan provides the quietest and most efficient selection.
Sound Power (L A)
w
Static Efficiency
Mixed Flow
Fan Size
Performance
Inline
Inline
Centrifugal
Mixed Flow
Mixed Flow
Vane Axial
Vane Axial
(QEI-L, QEI-I/II)
(QEI-L, QEI-I/II)
Centrifugal
15,000 cfm
@ 1.0 in. wg
24
36
49
90 dB
86 dB
92 dB
100 dB
93 dB
98 dB
103 dB
102 dB
111 dB
43%
68%
71%
17%
45%
60%
34%
56%
59%
25,000 cfm
@ 2.0 in. wg
50,000 cfm
@ 4.0 in. wg
Model comparisons based on similar outer tube diameters.
Lower Sound Power, Better Sound Quality
Sound power levels shown at each frequency:
Typical
Typical
QEI-L
Tubular Centrifugal
Vane Axial
QEI-I/II
The sound quality of the belt-driven mixed flow fan line is
as beneficial to low sound design as is the reduced overall
sound power. The sound chart compares units of similar
outer tube diameters at an operating point of 20,000 cfm with
1.5 inches wg of static pressure (Ps). Tubular centrifugals
(green) have dominant tones in the 63 Hz through 250 Hz
octave bands, while vane axials (red) have more mid to high
frequency sound. The mixed flow fan (blue) does not have a
dominant tone. A bystander would hear a more bland sound
that is quieter than a tubular centrifugal or vane axial.
100
90
80
70
60
62
125
250
500
1000 2000 4000 8000
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Wheel Characteristics
Belt Drive: Fan Class
Class I and II fans have different wheel designs with different performance characteristics.
Class I mixed flow wheels are optimized for performances involving low pressures and high volumes. Class II
wheels are designed for a steeper fan curve with higher pressure capabilities. This is illustrated in the graph
with the two different class wheels plotted at identical fan RPMs.
When selecting a mixed flow fan, it cannot be assumed that moving into a Class II fan will produce the same
results as a Class I mixed flow fans. Model QEI-L utilizes a Class I wheel.
Class II
Class I
CFM
Direct Drive: Percent Wheel Width
Direct drive mixed flow fans are optimized for performance requirements by the use of partial width wheels. This
is necessary because the fan RPM is commonly fixed and identical to the motor RPM. A reduction in the width
of the wheel (or the air passage) results in reduced airflow capacity and a steeper fan curve. This is similar to
the effect of a reduced pitch in a direct drive vane axial fan. QEID wheels are available in 5% increments from
50 - 100% wheel width.
QEID fans can be used in conjunction with variable frequency drives (VFD’s) for variable air volume (VAV)
systems. In these applications, the wheel width is optimized to ensure efficient operation and stable
performance throughout the turndown range. VFD’s are also used for final system balancing and to reduce the
airflow when building requirements are reduced. In this case, the fan and wheel width are selected using the
final design CFM and static pressure.
100%
Wheel
Width
Intermediate
Wheel
Widths
50%
Wheel
Width
50% Wheel Width
100% Wheel Width
CFM
Sound Power versus Sound Pressure
The sound values displayed on the performance pages are in terms of inlet sound power (LWiA) and outlet sound
power (LWoA). These values are the acoustic power radiating from the inlet and outlet of the fan, respectively.
Sound pressure, expressed as dBA, is the acoustic pressure at a point in space which can be measured with a
microphone or can be heard. To convert sound power (L A) into sound pressure (dBA), the following corrections
w
are applied for a hemispherical free field.
Distance from Fan
Correction
3 ft. (0.9 m)
7 db
5 ft. (1.5 m)
11.5 db
10 ft. (3.0 m)
17.5 db
dBA = L A - correction
w
Note: Refer to AMCA Publication 303, Application of Sound Power Level Ratings for additional information on calculating typical sound pressure levels for fan installation.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Optional Features
Sure-Aire™
The Sure-Aire™ flow monitoring system measures fan
flow within a 3% accuracy. Unlike traditional flow probes
mounted in the fan venturi that create a system effect
hindering fan performance, Sure-Aire™ does not interfere
with airflow and will not impact the fan’s air or sound
performance. This option is available on all mixed flow fan
models and ships completely assembled from our factory.
An electronics package with pressure transmitter and
digital read out is available with the Sure-Aire™ system. The
electronic kits are available for 50 or 60 Hz power supplies
and provide a 4-20 mA output that can be tied into t
building’s automation system.
Sound Sensitive Areas
Sound Vault Housing - Radiated Sound Enclosure
The sound vault housing is an excellent product for fans that will be positioned adjacent to an occupied work
space or in sound critical applications. It locks in radiated sound from the fan casing, motor and drives, and
minimizes vibration transmission. Standard construction includes an acoustically lined housing, integral spring
isolators, and internal flexible connections at the fan’s inlet and outlet to effectively isolate the fan from the
system. Vertical or horizontal mounting configurations are available.
Why use a Sound Vault?
• Sound power attenuation levels determined by
sound intensity tests on actual units
• Ships fully assembled with fan
• Internal isolation to limit breakout noise
• Access panels for inspection of fan and motor
• Bearing lubrication lines extended to outside of
enclosure
• Formed mounting rails with prepunched holes
for easy installation
• Available on both QEI-I and QEID through
size 27 fans
This table lists the radiated sound
Center Frequencies [Hz] 63 125 250 500 1000 2000 4000 8000
Attenuation Value (dB) 13 20 25 31 34 35 36 36
reductions from total sound power
levels for each octave band with
the sound vault housing.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Optional Two-coat
Paint System
In 1972, Greenheck took the lead as the first commercial and industrial fan manufacturer to introduce
electrostatic powder coatings. Today, Greenheck continues to lead by being the first to offer a superior zinc-rich
powder basecoat and powder coating finish.
This zinc-rich basecoat technology is used extensively outside the HVAC industry to protect bridge beams,
automotive components and other heavy-gauge steel products. Now, this advanced technology is available on
Greenheck welded steel products.
Greenheck’s coating process starts with a minimum of five wash stages to treat all components prior to
painting. Cleaner parts result in better coating adhesion and durability. We then use an advanced two-coat
powder application method that includes a basecoat of zinc-rich powder and a topcoat of Greenheck’s
Permatector™ or Hi-Pro Polyester. The combination of these two topcoats over the zinc-rich basecoat results
in the two-coatings, Perma-Z and Hi-Pro-Z. These oven-cured coatings provide superior corrosion resistance
along with a tough, uniform finish to combat the most extreme conditions.
Zinc Advantage
When compared to a traditional single coat
application, the benefits of the two-coat
system include:
One Coat Process
Topcoat
Standard
Surface Preparation
2-3 mils
• An automatic powder coat application
that produces uniform coverage and
unmatched paint quality.
Base Steel
• A double coat thickness that provides
superior durability and protection from
air and water.
Two-coat Process
Zinc-rich Primer
(70% zinc)
Topcoat
• A zinc-rich basecoat that includes
an epoxy component that provides
additional corrosion protection.
Advanced
Surface Preparation
4-6 mils Total
Base Steel
• A zinc-rich basecoat that provides
chemical protection of exposed steel
to prevent corrosion.
Salt Spray ASTM B117
The protection offered by the zinc-rich basecoats in
Perma-Z and Hi-Pro-Z result in extraordinary corrosion
resistance. Test data demonstrates our two-coat paint
system offers three (Perma-Z) and four (Hi-Pro-Z) times
the corrosion resistance of other coatings commonly
available within the fan industry. See table for salt spray
life for various coatings.
Hours
1000
2000
3000
4000
Permatector™
Hi-Pro Poly
Perma-Z
Hi-Pro-Z
Baked Phenolic
Epoxy Phenolic
Fluorocarbon
Coating fans with Perma-Z or Hi-Pro-Z has reduced our
customers annual paint maintenance costs by three to
four times!
Salt Spray ASTM B117 is a comparative test
that indicates the corrosion resistance of
powder paint coatings.
For more information, see Greenheck’s Coatings for
Extreme Applications catalog, available online at
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Certifications & Listings
Seismic Certification
The International Building Code (IBC) has been adopted at the state and lo
level throughout the United States. With the adoption of this code, comes
introduction of standards intended to improve the performance and design
non-structural systems subject to seismic events.
QEI-I/II and QEID
• Meet the 2006 IBC, 2009 IBC
• California OSHPD requirements (horizontal mount only) OSP 0223-10
• Shake table tested at an independent test facility in accordance with
ICC-ES AC 156
Structural Finite Element Analysis
Seismic Design Category F
• All equipment certified to worst case scenario seismic conditions
- Importance factor of 1.5 (IP = 1.5)
- Site Classes (A - F)
- Occupancy Categories (I - IV)
- Seismic Design Categories (A - F)
Consult your Greenheck representative or visit greenheck.com/seismic for more details.
UL 705 Power Ventilator
QEI-L, QEI-I/II and QEID models are available with the UL/cUL 705 (Underwriters Laboratory) listing on a wide
variety of 50 and 60 Hz motors. This listing ensures the use of UL approved electrical components.
Motors are available as either IEC (IP55) or NEMA (TEAO or ODP) designs. IEC design
motors are adjustable speed drive (ASD) compatible, have class F insulation and are
capable of wye-delta starting when over 5.5 kW. NEMA motors use across the line
starting with options for ASD compatibility. Motor (IEC or NEMA) using 50 Hz power have
a 1.0 service factor, while 60 Hz power have 1.15
UL/cUL File E40001
UL/cUL Listed Power Ventilator service factor. Design and construction options
for motors include increased thermal insulation,
overload protection and extended motor leads.
Operating
Temperature Duration
Time
UL Emergency Smoke Evacuation
QEI-I/II and QEID models were tested and
rated for design time and temperature used
in emergency heat and smoke exhaust
applications.
Model
ºC
ºF
Hours
Comments
QEID
QEI-I/II
QEI-I/II
QEID
300
300
260
260
572
572
500
500
1
2
4
5
Per British Spec 7346
UL/cUL File MH17511
UL/cUL Power Ventilators for Smoke Control Systems
Per Industrial Risk
Insurers (North America)
Consult your Greenheck representative for time and temperature
combinations other than those listed.
UL 762 is concerned with fans designed
for removal of smoke and grease laden
vapors with airstream temperatures up
UL 762 Restaurant Exhaust
Inline grease exhaust fans are an excellent alternative for
kitchen applications when roof or wall mounted ventilators
are not practical. A QEI-I/II with UL 762 grease option is
designed to withstand the demands of high temperature
kitchen grease exhaust and high-pressure duct washers.
to 400°F.
Listed Power
Ventilation for
Restaurant
Exhaust
Appliances
13G3 Maximum
Operating
• Meets all UL 705 requirements
• UL/cUL File MH11745
UL/cUL Power Ventilators for
Restaurant Exhaust Appliances
• Bolted access door
A Tough Package to Beat
The QEI-I/II inline grease fan is tough to beat when
packaged with our full line of kitchen hoods and grease
extraction options. Take advantage of Greenheck’s
expertise in providing a total solution in kitchen ventilation
equipment.
• Drain connection
Temperature
400°F.
• Meets requirements of NFPA 96
Ventilation Control and Fire Protection
of Commercial Cooking Operations
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Belt Drive versus Direct Drive
Belt Drive Advantages
• Lower sound levels
• Motor out of the airstream for easy access
• Motor size may be changed to accommodate
possible future air capacity requirements
• Final system balancing accomplished by
changing drives
Direct Drive Advantages
• Fewer wear components and less maintenance, no
shaft, bearings, pulleys, or belts
• More compact than equivalent belt drive size
• Motor in airstream for increased motor efficiency
and cooling
• Equal loading between mounting brackets
• Final system balancing accomplished by adjusting
the motor speed (ex. variable frequency drive use).
High Efficiencies = Lower Operating Costs
Example of Annual Operating Cost Savings
For a system performance requirement of 25,000 cfm at 2.5 inches of static pressure (wg) the corresponding
operating power requirements are 13.97 Bhp with a QEI-I size 36 and 19.8 Bhp for a size 36 tubular centrifugal fan.
Formulas:
- Kilowatt-Hours = (Operating Power (Bhp) x 0.746 x Hours of Operation) / Motor Efficiency
- Operating Cost = Kilowatt-Hours x Power Cost per kW hour
Assumptions:
- Cost of electricity is $0.09 per kilowatt hour
- 3,120 annual hours of operation (12 hours per day, five days a week, 52 weeks a year)
- 93.0% motor efficiency (equal to NEMA Premium minimum efficiency for 15 and 20 hp, ODP, 1725 rpm motor)
Tubular Centrifugal Fan
QEI-I - Mixed Flow Fan
kW-Hours = (19.8 Bhp x 0.746 x 3120) / 0.93 = 49,554
kW-Hours = (13.97 Bhp x 0.746 x 3120) / 0.93 = 34,963
Operating Cost = 49,554 x $0.09 = $4,460
Operating Cost = 34,963 x $0.09 = $3,147
Annual Operating Cost Savings = $4,460 - $3,147 = $1,313
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Belt Drive Mounting
Configurations
QEI-I/II Sizes 9-27 and all QEI-L
Universal Mounting
QEI-I/II models sizes 9-27 and all QEI-L models can be
mounted horizontally or vertically. For ease of installation,
eight mounting brackets are welded on each fan. These
eight brackets along with standard mounting supports
provide for Greenheck’s Universal Mounting System.
Motor positions are viewed from the discharge end.
Optional
Mounting
Rails
Fig. 1
Fig. 2
Fig. 1 Horizontal Base Mount
Each fan is shipped as standard in this arrangement.
Motor at “A” position (12 o’clock) is standard.
Fig. 2 Horizontal Base Mount with motor at “C” or “G”
position (3 or 9 o’clock). A set of optional mounting
rails are recommended for this installation.
Optional
Mounting
Rails
Fig. 3 Horizontal Ceiling Hung
In this installation the supports can be positioned for
mounting the motor at “A” or “E” (12 or 6 o’clock).
Fig. 4 Horizontal Ceiling Hung with motor at “C” or “G” (3
or 9 o’clock). A set of optional mounting rails are
recommended for this installation.
Fig. 3
Fig. 4
Vertical Ceiling Hung
Fig. 5 Vertical Mount
Universal QEI fans can be mounted vertically (ceiling
hung or base mount) for either upward or downward
airflow. Optional mounting rails are suggested for
any vertical installation.
Optional
Mounting Rails
Vertical Base Mount
Fig. 5
A
H
B
QEI-I/II Sizes 30-60
QEI-I/II models 30-60 are available in horizontal and vertical mounting configurations.
Lifting lugs are provided on horizontal fans for ease of installation. Vertical units
should be lifted by the mounting brackets.
G
C
Horizontal Mounting
Horizontal - Base Mount
A
Horizontal mounting configurations, base mount or ceiling hung, are provided with an
identical support. The mounting configuration can be changed between base mount
or ceiling hung in the field. The motor position can also be field rotated to any of the
shown positions. Motor positions are viewed from the discharge end.
Base Mount: Rigid steel base provides stable mounting to floor for the housing.
Motor Positions: A, B, C, G and H
G
C
Ceiling Hung: Suspend the fan horizontally from the ceiling.
Motor Positions: A, C, D, E, F and G
F
D
Mounting rails are recommended for horizontal installations with B, C, D, F, G and H
motor positions.
E
Horizontal - Ceiling Hung
Vertical Mounting
Vertical mounting configurations, upblast or downblast, are provided with heavy duty steel brackets welded to
both ends. These brackets permit either floor or ceiling mounting on the same unit. Optional mounting rails are
suggested for any vertical installation for sizes 9-27.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Roof Upblast & Spark Resistant
Construction
Roof Upblast
Models QEI-I/II sizes 9 through 54 and model QEID
sizes 12 through 54, are available in roof upblast
configuration. The roof upblast configuration is ideal
for exhausting contaminants away from a building to
prevent roof damage and re-entrainment of exhaust
air. Both QEI-I/II roof upblast models have the high
temperature UL rating and can be used for emergency
smoke exhaust applications.
Standard construction includes a fully-welded heavy-
gauge curb cap to eliminate leaks, a butterfly damper
section for backflow prevention, and a windband
section to protect the butterfly dampers from debris. A
complete line of roof curbs is available for mounting to
a roof deck.
Spark Resistant Construction
Greenheck mixed flow fans are available with spark
resistant designs suitable for applications that involve
flammable particles, fumes or vapors. Spark resistant
construction options adhere to guidelines defined
within AMCA Standard 99-0401-10.
The fan wheel is constructed of a
nonferrous material (aluminum).
QEI-I/II
Spark B A non-ferrous (aluminum) bearing
cover surrounds the driven bearing,
shielding it from the airstream.
The inlet cone is constructed of
non-ferrous material (aluminum).
Spark C A nonferrous (aluminum) bearing
cover surrounds the driven bearing
shielding it from the airstream.
QEI-I/II
QEI-L
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Accessories
Availability
QEI-L QEI-I QEI-II QEID
Motor Cover
A weatherproof motor cover shields the motor components
from dust, dirt and moisture for indoor or outdoor
installations. Motor covers also serve as a personnel guards
and meet OSHA standards.
Hinged Access Door Hinged access doors provide an opening through the fan
housing for cleaning or visual inspection of the wheel. Bolted
access door is standard.
Extended Life
Bearings
Air handling quality, flange mounted bearings meet a basic
rating fatigue life L per ABMA standards, in excess of
10
200,000 hours (L at 1,000,000) at maximum operating
50
speed.
Copper Lube Lines
(Belt Drive)
Copper lube lines can be used as a replacement for
standard nylon lube lines.
Flanges
Inlet and outlet flanges with prepunched holes, welded to
the housing, provide an easy means for bolted connection
to ductwork. Matching bolt-on companion flanges are also
available.
Std.
Disconnect Switches Toggle-type and heavy-duty disconnect switches are
available for positive electrical shut-off and safety when
servicing fans. The following switches are available to
meet individual electrical requirements and can be factory
mounted or shipped loose for field mounting.
• NEMA-1
• NEMA-3R
• NEMA-4
General purpose
Rainproof
Watertight
• NEMA-7 & 9* Class 1 and 2 hazardous locations
*Greenheck will not factory mount NEMA-7 & 9 disconnect switches.
Inlet and Outlet
Guards
Removable inlet and outlet guards provide protection
for personnel and equipment in ducted or non-ducted
installations.
Extended Wiring
Belt Tube
Electric leads from the motor junction box are brought out to
exterior of unit. This provides an easy means of connecting
the motor to the electrical system.
A totally enclosed belt tube isolates the belts and drives
from the airstream.
Sound Vault Housing See page 8 for more details on sound vault housing.
Mounting Rails
Mounting rails are recommended for vertically mounted fans
or horizontal mounting when the motor is to be located in the
C or G (3 or 9 o’clock) position.
Isolators
Both base mount and hanging isolators are available in
either neoprene or spring mounts.
Special Coatings
Special coatings are available for protective purposes.
Consult Greenheck’s Product Application Guide,
Performance Coatings for Ventilation Products, for a
complete list of coatings available and their chemical
Sure Aire™ Flow
Measurement
Sure-Aire provides real-time flow measurement for use in
building automation systems. For additional information,
see page 8 or our Sure-Aire Flow Monitoring System catalog
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Exploded View
Motor Cover
Companion Flange
Slip Fit Connection
(Standard on QEI-I/II)
Inlet Guard
Outlet Flange
(Standard on QEI-L)
Outlet Guard
Bolted Access Door
(Standard)
Spring Base Isolator
Neoprene Base Isolator
Inlet Flange
(Standard on QEI-L)
Companion Flange
Spring Hanging Isolator
Mounting
Rails
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Direct Drive Selection Charts
The quick select charts below and on the following page are a convenient method for sizing the fan required for a
specific performance. Colored bands for a given size in each chart represent the entire operating range available
for that size and speed.
For QEID performance pages showing AMCA Licensed data for sound and air performance please refer to the
12
10
1770 RPM
8
(60 Hz)
Static
Pressure
(in. wg)
6
Model QEID
12—33
4
2
12
15
16 18 20 22 24 27 30 33
0
1
5
10
50
100
Volume (cfm x 1000)
12
10
8
1170 RPM
(60 Hz)
Static
Pressure
(in. wg)
6
Model QEID
15—49
4
2
15
16 18 20 22 24 27 30 33 36 40 44 49
0
1
5
10
50
100
Volume (cfm x 1000)
16
Download from Www.Somanuals.com. All Manuals Search And Download.
QEID Dimensional Data
8
6
870 RPM
(60 Hz)
Static
Pressure
4
(in. wg)
Model QEID
36—54
2
36
40
44
50
49
54
0
10
20
30
40
100
Volume (cfm x 1000)
Slip Fit O.D.
Length*
Weight**
Size
12
inches
mm
435
inches
25.0
25.0
26.0
29.0
34.0
35.5
41.5
45.0
mm
635
635
660
737
864
902
1054
1143
lbs.
100
140
kg.
45
17.13
20.88
23.00
25.38
27.81
30.88
34.00
37.44
41.63
45.75
50.56
55.75
61.63
67.75
75.00
15
16
18
20
22
24
27
30
33
36
40
44
49
54
530
65
Slip Fit
O.D.
584
170
80
645
200
95
706
250
115
170
220
260
390
520
620
750
995
784
370
864
480
951
570
1057
1162
1284
1416
1565
1721
1905
860
Length
1140
1360
1650
2190
2700
3130
Refer to
table below.
*Length varies with motor frame size.
Refer to Length table shown.
**Weight is for unit only and does not
include motor.
1225
1420
Length — inches (millimeters)
254/6 T
284/6 T
324/6 T
364/5 T
404/5 T
444/5 T
Size
30
33
36
40
44
49
54
45.5 (1156)
46.5 (1181)
50.5 (1283)
50.0 (1156)
54.0 (1372)
58.0 (1473)
56.5 (1435)
50.0 (1156)
54.0 (1372)
58.0 (1372)
61.0 (1549)
64.0 (1626)
54.0 (1372)
58.0 (1372)
61.0 (1549)
64.0 (1626)
74.5 (1892)
77.0 (1956)
70.0 (1778)
74.5 (1892)
77.0 (1956)
80.5 (2045)
83.0 (2108)
17
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI Dimensional Data
QEI-L
QEI
Airflow
Airflow
Slip Fit
O.D.
Height
Height
Length
Length
QEI-L
QEI Class I
QEI Class II
Slip-Fit O.D.
Length
Height
Slip-Fit O.D.
Length
Height
Length
Height
Size
inches (mm)
inches (mm)
inches (mm)
inches (mm)
inches (mm)
NA
NA
NA
17.13 (435)
17.13 (435)
20.88 (530)
23.00 (584)
25.38 (645)
27.81 (706)
30.88 (784)
34.00 (864)
37.44 (951)
NA
NA
28.5 (724)
30.5 (775)
36.5 (927)
36.5 (927)
9
17.5 (445)
21.13 (537)
23.31 (592)
25.63 (651)
28.06 (713)
31.13 (791)
34.25 (870)
37.69 (957)
42.00 (1067)
46.13 (1172)
51.06 (1297)
NA
26.5 (673)
29.0 (737)
31.0 (787)
33.0 (838)
35.5 (902)
39.0 (991)
37.5 (953)
41.5 (1054)
44.0 (1118)
46.5 (1181)
50.5 (1283)
53.5 (1359)
28.5 (724)
36.5 (927)
12
15
16
18
20
22
24
27
30
33
36
40
44
49
54
60
31.0 (787) 41.0 (1041) 34.0 (864) 41.0 (1041)
33.0 (838) 44.0 (1118) 34.0 (864) 44.0 (1118)
35.0 (889) 46.5 (1181) 39.5 (1003) 47.5 (1207)
37.5 (953) 50.5 (1283) 41.5 (1054) 50.5 (1283)
41.0 (1041) 53.5 (1359) 44.0 (1118) 53.5 (1359)
44.5 (1130) 57.5 (1461) 49.0 (1245) 59.5 (1511)
47.0 (1194) 61.0 (1549) 53.0 (1346) 63.0 (1600)
42.5 (1080) 55.5 (1410)
45.0 (1143) 61.0 (1549)
52.0 (1321) 64.5 (1638)
56.5 (1435) 68.0 (1727)
62.0 (1575) 75.0 (1905)
41.62 (1057) 54.0 (1372) 65.0 (1651) 60.5 (1537) 72.0 (1829)
45.75 (1162) 58.5 (1486) 69.0 (1753) 65.0 (1651) 76.5 (1943)
50.56 (1284) 64.0 (1626) 75.0 (1905) 69.0 (1753) 82.5 (2096)
55.75 (1416) 68.5 (1740) 83.0 (2108) 75.5 (1918) 90.5 (2299)
61.62 (1565) 74.0 (1880) 89.5 (2273) 80.5 (2045) 97.0 (2464)
67.75 (1721) 80.5 (2045) 96.5 (2451) 86.5 (2197) 104.0 (2642)
75.00 (1905) 87.0 (2210) 105.0 (2667) 93.5 (2375) 111.0 (2819)
82.88 (2105) 91.5 (2324) 113.0 (2870) 102.5 (2604) 119.0 (3023)
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
18
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-9 Class II
10
8
5
50% W
RPM
BHP
OV
Performance Data
Maximum Fan RPM
Specification Data
3
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
60% W
OV
4000
184T
20
15
10
5
70% W
OV
Maximum Motor
Frame Size
2
4
0
6
0
0
1½
Minimum Motor
Starting hp
80% W
OV
1/3 hp
.25 kW
3
4
0
1
Wheel Diameter
15 in.
381 mm
77 kg.
0
4
¾
Approximate Weight
(Less Motor & Drives)
Maximum Bhp = (Fan RPM / 2671)3
Outlet Velocity (FPM) = CFM / 1.56
Tip Speed (FPM) = Fan RPM x 3.93
170 lbs.
2
8
0
0
½
90% W
OV
3
2
2
2
0
0
1
6
0
0
0
0
% WOV = (CFM x 100) / (Fan RPM x 0.73)
0
0
5
10
15
20
25
30
Volume (cfm x 100)
Imperial data — Metric data
1
2
3
4
5
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
1.5 2.5
RPM RPM
CFM
OV
0.25
RPM BHP
0.5
RPM
1
2
3
3.5
4
BHP
RPM
BHP
BHP
RPM
BHP
BHP
RPM
BHP
RPM
BHP
RPM
BHP
850
541 1325 0.09 1463 0.14 1709 0.25 1937 0.38 2148 0.52 2341 0.67
1000 636 1511 0.13 1633 0.18 1854 0.31 2056 0.44 2252 0.59 2432 0.75 2606 0.93 2767 1.11
1150 732 1700 0.17 1811 0.23 2013 0.37 2198 0.52 2371 0.68 2542 0.85 2700 1.03 2858 1.22 3007 1.42
1300 828 1893 0.23 1994 0.29 2177 0.44 2349 0.61 2511 0.78 2661 0.96 2817 1.15 2961 1.35 3098 1.56
1450 923 2088 0.31 2181 0.37 2351 0.53 2510 0.71 2658 0.89 2804 1.08 2940 1.28 3079 1.49 3212 1.71
1600 1019 2285 0.40 2371 0.47 2530 0.63 2674 0.82 2818 1.02 2951 1.23 3083 1.44 3207 1.66 3331 1.88
1750 1114 2483 0.50 2563 0.58 2711 0.75 2849 0.95 2981 1.16 3109 1.38 3230 1.61 3351 1.84 3466 2.08
1900 1210 2682 0.63 2757 0.72 2897 0.89 3027 1.10 3149 1.32 3271 1.56 3387 1.80 3498 2.04 3611 2.29
2050 1305 2883 0.77 2952 0.87 3084 1.06 3207 1.26 3324 1.50 3435 1.75 3549 2.00 3656 2.26 3758 2.53
2200 1401 3083 0.94 3149 1.04 3274 1.25 3390 1.45 3502 1.70 3609 1.96 3713 2.22 3818 2.50 3918 2.78
2350 1496 3285 1.13 3347 1.24 3465 1.46 3576 1.68 3683 1.92 3785 2.19 3883 2.47 3981 2.76
2500 1592 3487 1.34 3545 1.46 3657 1.69 3764 1.93 3865 2.16 3964 2.44
Inlet Sound Power, LWi [dB ref 10-12 watts]
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
1600
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWi
A
RPM
1600
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWoA
69 71 74 70 71 67 65 57
71 69 72 68 68 66 62 56
70 70 71 66 63 65 61 55
72 70 71 65 63 65 61 55
74 75 78 75 75 74 71 65
72 71 73 72 72 71 66 60
73 72 74 70 69 70 66 60
75 73 74 70 69 70 66 61
77 78 82 78 80 79 75 74
77 78 77 74 75 75 71 66
78 79 78 74 74 74 70 65
78 79 79 75 74 74 70 65
78 80 84 80 83 83 79 79
78 81 81 77 79 79 75 71
80 82 81 77 78 78 74 70
80 82 82 79 78 78 74 70
78 82 85 82 87 87 83 83
79 83 84 81 83 83 79 76
82 85 84 80 82 81 78 76
82 84 85 83 82 82 78 75
75
73
71
71
80
77
76
76
85
81
80
80
89
84
84
84
92
88
87
88
76 78 78 70 71 65 63 56
77 80 77 67 68 63 58 56
80 78 76 66 66 62 58 56
82 78 77 66 66 62 58 56
86 86 84 77 78 74 69 64
86 85 84 73 74 70 65 61
87 85 82 73 73 69 65 61
88 86 82 74 73 69 65 61
88 85 87 81 83 80 75 72
87 88 85 77 79 76 71 66
91 85 86 78 78 75 70 67
92 86 86 79 79 75 70 67
88 88 91 84 87 85 80 78
90 88 89 80 83 81 76 71
94 87 89 82 83 80 76 72
94 88 89 83 84 81 76 72
88 93 96 87 91 90 85 83
76
74
73
73
82
80
79
79
87
84
84
84
92
88
88
89
96
92
92
92
2200
2800
3400
4000
2200
2800
3400
4000
94
86 92 82 87 86 81 75
95 89 92 85 86 85 81 76
95 90 92 86 88 85 81 77
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-12 Class I & QEI-L
10
8
Performance Data
7½
50% W
RPM
BHP
OV
60% W
5
% WOV
QEI-L
QEI
3800
3800
Density 0.075 lb/ft3
Density 1.2 kg/m3
Maximum
Fan RPM
OV
20
15
10
5
70% W
OV
Specification Data
3
Maximum
Motor
Frame Size
QEI-L
QEI
184T
184T
80% W
OV
6
3800
2
Minimum Motor
Starting hp
Wheel Diameter
1½
1/3 hp
15 in.
QEI-L 120 lbs. 55 kg.
QEI 160 lbs. 73 kg.
.25 kW
3200
4
381 mm
1
90% W
OV
¾
Approximate Weight
(Less Motor & Drives)
2600
½
2
3
Maximum Bhp = (Fan RPM / 2301)3
Outlet Velocity (FPM) = CFM / 1.56
Tip Speed (FPM) = Fan RPM x 3.93
% WOV = (CFM x 100) / (Fan RPM x 1.34)
Imperial data — Metric data
1400
0
0
0
0
1
2
3
4
5
6
Volume (cfm x 1000)
2
4
6
8
10
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
1.5 2.5
CFM
OV
0.25
RPM
0.5
1
2
3
3.5
4
BHP
0.09
0.13
0.19
0.27
0.38
0.51
0.68
0.88
1.11
1.39
1.71
2.08
RPM
1241
1399
1575
1763
1966
2172
2382
2593
2806
3021
3237
3453
BHP
0.15
0.20
0.27
0.36
0.48
0.62
0.79
1.00
1.25
1.54
1.87
2.25
RPM
1549
1661
1807
1967
2139
2323
2514
2716
2922
3129
3338
3549
BHP
0.30
0.37
0.46
0.56
0.69
0.85
1.04
1.26
1.53
1.84
2.19
2.59
RPM
1823
1907
2020
2162
2317
2479
2657
2840
3029
3231
3435
3641
BHP
0.49
0.57
0.67
0.80
0.94
1.11
1.31
1.55
1.82
2.15
2.53
2.95
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1200
1500
1800
2100
2400
2700
3000
3300
3600
3900
4200
4500
764
1070
1257
1461
1669
1881
2095
2310
2527
2745
2964
3184
3404
955
2137
2228
2341
2484
2636
2799
2969
3150
3335
3527
3729
0.79
0.91
1.04
1.21
1.40
1.62
1.86
2.16
2.49
2.87
3.31
2341
2423
2523
2640
2785
2938
3100
3265
3446
3630
1.03
1.16
1.31
1.49
1.71
1.94
2.21
2.50
2.86
3.25
1146
1337
1528
1719
1910
2101
2292
2484
2675
2866
2607
2690
2801
2926
3072
3226
3387
3551
3731
1.43
1.60
1.79
2.02
2.28
2.57
2.88
3.23
3.65
2776
2858
2954
3067
3201
3348
3503
3665
1.72
1.90
2.11
2.35
2.63
2.94
3.28
3.65
3016
3099
3208
3322
3467
3615
3772
2.22
2.44
2.70
2.98
3.32
3.68
4.08
Inlet Sound Power, LWi [dB ref 10-12 watts]
% WOV
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
1
2
3
4
5
6
7
8
LWi
75
A
RPM
1400
% WOV
1
2
3
4
5
6
7
8
LWo
78
A
100
80
77 78 71 73 67 68 61 52
77 78 69 68 65 64 60 52
78 78 68 65 62 61 60 52
78 77 68 64 62 60 60 52
78 78 78 79 75 75 73 59
74 77 76 75 71 72 66 58
74 76 75 71 68 68 64 58
76 77 75 70 67 67 63 58
83 82 80 80 78 77 83 68
80 82 81 78 75 76 74 65
79 81 79 76 73 74 70 65
81 81 79 75 72 73 69 65
85 85 82 82 81 80 87 79
82 85 83 81 79 78 79 70
83 85 82 81 77 77 74 70
83 84 82 81 77 77 74 70
86 87 85 86 86 84 88 91
80 87 83 83 82 80 80 74
85 88 85 85 80 79 77 74
84 87 84 86 81 80 78 74
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
87 83 75 74 72 71 63 59
87 81 74 71 70 68 62 58
88 82 74 70 68 67 62 59
89 81 73 70 67 66 62 59
84 84 80 80 80 77 75 64
84 84 77 77 77 75 69 64
85 84 76 75 74 71 67 64
87 84 76 75 7 3 70 66 64
90 93 83 82 83 80 82 72
92 90 81 79 82 79 75 69
90 89 81 79 79 77 73 69
91 90 81 78 78 76 71 70
93 95 88 85 86 83 86 81
94 92 85 82 85 82 80 74
93 92 85 82 83 81 77 74
95 93 86 81 83 80 76 74
93 94 93 90 90 88 87 92
93 92 89 85 87 84 83 77
96 93 89 85 87 84 81 77
97 94 90 85 87 84 81 77
72
70
69
82
78
75
74
86
82
80
79
90
86
84
84
95
88
87
88
76
75
74
84
81
79
79
89
86
84
84
92
89
88
88
97
92
91
92
1400
2000
2600
3200
3800
60
50
100
80
60
50
100
80
60
50
2000
2600
3200
3800
100
80
60
50
100
80
60
50
50
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-12 Class II
12
10
8
RPM
BHP
Performance Data
50% WOV
7
½
5
3
% WOV
Maximum Fan RPM
4000
Density 0.075 lb/ft3
Density 1.2 kg/m3
60% WOV
25
20
15
10
5
Specification Data
70% WOV
Maximum Motor
Frame Size
184T
.25 kW
Minimum Motor
Starting hp
1/3 hp
15 in.
80% WOV
6
2
Wheel Diameter
381 mm
82 kg.
1½
Approximate Weight
(Less Motor & Drives)
Maximum Bhp = (Fan RPM / 2345)3
Outlet Velocity (FPM) = CFM / 1.56
Tip Speed (FPM) = Fan RPM x 3.93
4
180 lbs.
1
¾
90% WOV
½
2
1600
0
0
% WOV = (CFM x 100) / (Fan RPM x 1.16)
0
0
1
2
3
4
5
Volume (cfm x 1000)
Imperial data — Metric data
2
4
6
8
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0
0.5
1
2
3
4
5
6
7
RPM
1203
1375
1547
1719
1891
2062
2234
2406
2578
2750
2922
3094
BHP
0.08
0.12
0.17
0.24
0.32
0.41
0.52
0.65
0.80
0.98
1.17
1.39
RPM
1460
1604
1752
1906
2062
2221
2381
2543
2706
2871
3036
3202
BHP
0.21
0.26
0.33
0.41
0.50
0.61
0.74
0.88
1.05
1.24
1.45
1.68
RPM
1696
1812
1943
2080
2223
2370
2519
2673
2829
2987
3145
3305
BHP
0.37
0.43
0.51
0.60
0.71
0.83
0.97
1.13
1.31
1.51
1.74
1.99
RPM
2131
2213
2301
2410
2522
2653
2785
2921
3064
3209
3356
3504
BHP
0.75
0.84
0.93
1.05
1.17
1.32
1.48
1.66
1.87
2.10
2.35
2.62
RPM
2510
2574
2641
2728
2817
2924
3035
3157
3289
3421
3556
3699
BHP
1.21
1.31
1.43
1.56
1.71
1.88
2.06
2.27
2.49
2.74
3.01
3.32
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1400
1600
1800
2000
2200
2400
2600
2800
3000
3200
3400
3600
891
1019
1146
1273
1401
1528
1656
1783
1910
2038
2165
2292
2894
2957
3021
3102
3190
3283
3393
3504
3624
3755
3887
1.84
1.98
2.13
2.30
2.49
2.70
2.92
3.17
3.44
3.74
4.06
3239
3302
3366
3443
3530
3618
3722
3831
3943
2.59
2.76
2.95
3.15
3.38
3.63
3.90
4.19
4.50
3557
3620
3684
3759
3846
3934
3.43
3.64
3.86
4.11
4.38
4.67
3854
3917
3981
4.37
4.62
4.88
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
1600
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWi
A
RPM
1600
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWo
79
A
72 77 77 74 70 69 69 56
74 79 75 69 66 67 61 55
73 80 75 66 64 64 58 55
74 80 76 65 63 63 57 54
76 77 78 78 76 75 76 67
76 78 76 74 72 72 68 63
76 79 75 71 70 70 66 62
77 79 75 71 69 68 64 62
83 82 83 80 80 78 78 79
86 86 81 77 76 75 73 68
85 91 79 76 75 75 72 67
86 89 80 76 74 74 70 67
83 86 85 83 83 82 80 85
87 86 83 80 80 79 76 72
87 90 82 79 79 78 76 71
87 89 83 80 78 78 75 71
80 89 86 86 87 86 84 89
82 83 83 81 83 82 79 76
84 82 85 81 82 81 79 75
84 83 85 83 82 81 79 75
77
73
72
72
82
78
76
76
86
82
82
81
90
85
85
85
93
88
87
88
87 83 78 75 74 71 69 58
84 85 73 70 71 69 63 58
85 84 73 68 68 66 61 58
87 84 73 68 68 65 60 59
89 85 80 80 80 77 75 67
87 84 77 76 77 74 70 66
88 82 77 74 74 72 67 66
89 83 77 74 74 71 67 66
97 89 86 83 84 81 78 78
91 90 83 80 82 79 75 71
91 87 83 79 80 77 73 71
93 88 83 79 79 76 73 70
98 91 88 86 88 85 81 84
93 90 86 83 85 82 79 75
93 89 86 83 84 81 78 75
95 89 86 83 83 81 77 74
95 90 90 89 91 89 85 87
76
75
74
84
81
79
79
89
86
85
84
92
89
89
88
96
92
92
91
2200
2800
3400
4000
2200
2800
3400
4000
94
88 87 85 88 86 82 78
94 89 89 85 88 85 82 78
94 89 88 86 87 84 82 78
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-15 Class I & QEI-L
6
5
4
3
2
1
0
Performance Data
5
RPM
BHP
50% WOV
60% WOV
14
12
10
8
QEI-L
QEI
2721
2721
Maximum
Fan RPM
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
3
2
70% WOV
Specification Data
Maximum
Motor
Frame Size
QEI-L
QEI
184T
213T
80% WOV
Minimum Motor
Starting hp
Wheel Diameter
1/3 hp
18.25 in.
QEI-L 140 lbs. 64 kg.
QEI 190 lbs. 82 kg.
.25 kW
1
6
464 mm
Approximate Weight
(Less Motor & Drives)
90% WOV
4
½
¼
Maximum Bhp = (Fan RPM / 1617)3
Outlet Velocity (FPM) = CFM / 2.32
Tip Speed (FPM) = Fan RPM x 4.78
% WOV = (CFM x 100) / (Fan RPM x 2.55)
Imperial data — Metric data
2
0
0
1
2
3
4
5
6
7
Volume (cfm x 1000)
0
2
4
6
8
10
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
1.5 2.5
CFM
OV
0.25
RPM
0.5
1
2
3
3.5
4
BHP
0.12
0.17
0.24
0.33
0.44
0.58
0.75
0.95
1.19
1.47
1.79
2.16
RPM
965
BHP
0.21
0.28
0.36
0.46
0.59
0.74
0.93
1.14
1.40
1.69
2.03
2.41
RPM
1229
1301
1391
1495
1615
1740
1870
2003
2141
2282
2426
2570
BHP
0.44
0.52
0.62
0.75
0.92
1.11
1.31
1.55
1.83
2.16
2.52
2.94
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1700
2100
2500
2900
3300
3700
4100
4500
4900
5300
5700
6100
732
823
905
952
1072
1194
1323
1456
1597
1740
1885
2031
2180
2330
2481
1508
1580
1662
1763
1875
1996
2121
2251
2383
2517
2657
0.81
0.93
1.07
1.25
1.47
1.73
2.01
2.31
2.65
3.04
3.48
1077
1250
1422
1594
1767
1939
2112
2284
2456
2629
1088
1231
1376
1524
1674
1825
1977
2130
2283
2436
1753
1827
1907
2008
2114
2234
2356
2483
2613
1.27
1.43
1.62
1.86
2.13
2.45
2.82
3.20
3.61
1915
1976
2054
2135
2236
2339
2458
2579
2704
1.64
1.83
2.03
2.27
2.56
2.90
3.29
3.73
4.20
2122
2188
2266
2350
2451
2553
2672
2.24
2.47
2.73
3.02
3.38
3.77
4.24
2257
2317
2390
2469
2556
2657
2.68
2.94
3.22
3.52
3.88
4.30
2443
2505
2583
2663
3.42
3.72
4.05
4.41
Inlet Sound Power, LWi [dB ref 10-12 watts]
% WOV
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
1
2
3
4
5
6
7
8
LWi
60
A
RPM
650
% WOV
1
2
3
4
5
6
7
8
LWo
63
A
100
80
63 61 59 56 57 52 48 35
62 59 59 53 54 51 48 35
60 59 57 52 54 51 47 35
60 59 56 52 53 51 47 35
65 66 68 65 60 63 52 44
63 63 65 62 58 56 51 42
63 63 63 60 57 55 50 42
66 64 63 59 57 55 50 42
69 77 73 72 69 67 69 53
68 76 70 68 66 63 58 50
67 70 68 66 65 62 57 50
68 71 70 65 64 61 56 50
73 73 82 81 78 74 77 65
68 76 76 78 74 72 67 61
75 77 77 76 72 70 67 62
81 80 77 76 72 71 67 61
79 78 86 88 86 83 80 83
80 73 83 85 81 79 74 69
78 75 78 81 79 77 73 69
80 79 80 81 78 76 74 70
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
74 65 60 58 59 54 52 39
69 64 59 57 57 55 52 40
70 64 58 56 57 54 52 40
71 64 58 56 57 55 52 40
73 73 66 68 65 64 55 47
75 74 64 66 63 60 56 47
76 73 64 65 62 59 55 47
77 74 64 65 62 59 55 47
79 79 74 74 73 69 70 56
79 74 72 71 71 67 61 55
77 75 73 69 68 66 61 55
80 75 72 69 68 65 61 55
83 82 81 83 82 78 78 68
79 78 77 79 79 75 70 63
83 81 78 77 77 74 69 64
86 83 79 77 76 73 69 64
91 85 87 90 90 86 82 84
59
58
58
68
64
63
62
75
71
69
69
84
80
78
78
91
86
84
83
62
61
61
70
68
68
68
78
74
73
73
86
82
81
81
94
90
88
88
650
1000
1400
2000
2721
60
50
100
80
60
50
100
80
60
50
1000
1400
2000
2721
100
80
60
50
100
80
100
80
88
83 81 84 86 84 78 72
60
50
60
50
87 87 83 82 83 81 77 71
90 89 85 83 83 81 76 72
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-15 Class II
10
9
8
7
6
5
4
3
2
1
0
Performance Data
RPM
BHP
50% WOV
10
7½
60% WOV
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
Maximum Fan RPM
3445
5
70% WOV
Specification Data
20
15
10
5
Maximum Motor
Frame Size
215T
80% WOV
3
2
Minimum Motor
Starting hp
1/3 hp
18.25 in. 464 mm
220 lbs. 100 kg.
.25 kW
Wheel Diameter
Approximate Weight
(Less Motor & Drives)
Maximum Bhp = (Fan RPM / 1666)3
Outlet Velocity (FPM) = CFM / 2.32
Tip Speed (FPM) = Fan RPM x 4.78
90% WOV
1
0
% WOV = (CFM x 100) / (Fan RPM x 2.20)
0
1
2
3
4
5
6
7
8
Volume (cfm x 1000)
Imperial data — Metric data
0
2
4
6
8
10
12
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
6
7
8
RPM
1315
1436
1559
1684
1810
1938
2067
2197
2328
2460
2592
2724
BHP
0.42
0.53
0.65
0.79
0.96
1.15
1.37
1.61
1.89
2.20
2.55
2.93
RPM
1471
1575
1687
1805
1926
2047
2170
2294
2420
2546
2673
2802
BHP
0.64
0.77
0.92
1.10
1.30
1.52
1.76
2.04
2.34
2.67
3.04
3.45
RPM
1790
1864
1948
2034
2137
2242
2353
2471
2590
2710
2831
2953
BHP
1.23
1.38
1.54
1.72
1.95
2.21
2.50
2.84
3.22
3.64
4.07
4.53
RPM
2082
2131
2201
2275
2358
2443
2538
2641
2746
2856
2973
3092
BHP
1.91
2.09
2.29
2.51
2.75
3.01
3.31
3.67
4.05
4.49
4.99
5.53
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2500
2800
3100
3400
3700
4000
4300
4600
4900
5200
5500
5800
1077
1206
1336
1465
1594
1724
1853
1982
2112
2241
2370
2500
2392
2435
2500
2570
2647
2730
2816
2908
3011
3115
3221
2.88
3.11
3.36
3.64
3.94
4.26
4.61
5.01
5.47
5.96
6.50
2670
2713
2771
2841
2913
2995
3080
3165
3259
3362
3.99
4.28
4.59
4.92
5.29
5.67
6.09
6.53
7.04
7.61
2884
2926
2968
3023
3093
3164
3243
3326
3411
4.93
5.25
5.59
5.96
6.36
6.78
7.24
7.72
8.23
3122
3164
3207
3261
3331
3402
6.28
6.66
7.05
7.48
7.94
8.43
3347
3389
3431
7.76
8.20
8.65
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
1000
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWi
A
RPM
1000
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWo
74
A
64 70 70 72 66 65 55 48
62 66 67 66 63 60 52 43
61 62 63 62 61 58 51 42
62 63 63 62 60 58 51 41
67 69 73 74 71 72 64 56
66 65 71 72 68 67 61 53
67 66 68 68 66 65 58 51
69 67 69 67 65 63 57 52
71 73 78 77 77 75 79 66
67 69 76 75 74 73 70 62
71 71 74 74 72 71 68 61
75 74 76 74 72 71 67 61
78 78 79 85 85 83 87 77
79 74 76 85 84 80 77 71
81 78 77 82 82 78 75 70
81 80 79 82 81 78 74 70
79 82 84 89 90 88 91 87
75 79 81 85 87 85 83 78
79 83 82 82 84 83 81 77
81 85 85 86 85 82 80 77
73
68
65
65
78
75
71
71
84
79
77
77
91
88
85
85
96
91
89
90
76 75 69 72 70 67 55 47
75 72 67 67 68 62 53 44
75 72 67 64 66 60 53 44
75 71 67 64 65 60 52 44
80 76 74 76 76 73 66 56
78 74 71 72 74 69 62 52
79 75 71 70 72 67 60 52
79 75 71 70 72 67 60 52
90 81 81 83 82 78 79 66
88 78 77 79 80 76 72 65
87 82 78 77 78 74 69 63
89 83 79 78 78 73 69 64
87 85 85 88 90 86 86 78
85 85 83 83 88 83 79 72
88 89 87 82 86 81 77 71
89 90 87 83 86 80 77 72
91 90 91 93 95 93 92 89
71
69
68
80
77
75
75
87
84
82
82
94
90
89
89
100
96
94
94
1400
2000
2700
3445
1400
2000
2700
3445
89
92 91 89 92 89 86 80
92 94 93 87 90 87 84 79
93 94 93 89 90 87 83 78
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-16 Class I & QEI-L
7
6
5
4
3
2
1
0
Performance Data
RPM
BHP
50% WOV
60% WOV
5
7½
QEI-L
QEI
2300
2483
16
14
12
10
8
% WOV
Maximum
Fan RPM
Density 0.075 lb/ft3
Density 1.2 kg/m3
70% WOV
Specification Data
Maximum
QEI-L
184T
213T
3
Motor
Frame Size
80% WOV
QEI
Minimum Motor
Starting hp
Wheel Diameter
1/3 hp
20 in.
QEI-L 160 lbs. 73 kg.
QEI 220 lbs. 100 kg.
.25 kW
1½
508 mm
6
Approximate Weight
(Less Motor & Drives)
90% WOV
¾
4
1/3
Maximum Bhp = (Fan RPM / 1387)3
Outlet Velocity (FPM) = CFM / 2.79
Tip Speed (FPM) = Fan RPM x 5.24
% WOV = (CFM x 100) / (Fan RPM x 3.36)
Imperial data — Metric data
2
0
0
1
2
3
4
5
6
7
8
9
Volume (cfm x 1000)
0
2
4
6
8
10
12
14
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
1.5 2.5
CFM
OV
0.25
RPM
0.5
1
2
3
3.5
4
BHP
0.19
0.25
0.33
0.43
0.55
0.69
0.85
1.05
1.27
1.52
1.81
2.14
RPM
951
BHP
0.31
0.39
0.48
0.59
0.72
0.88
1.06
1.27
1.51
1.77
2.08
2.42
RPM
1169
1230
1307
1389
1479
1573
1673
1774
1878
1984
2092
2201
BHP
0.59
0.69
0.81
0.95
1.11
1.29
1.50
1.74
2.01
2.31
2.64
3.01
RPM
1362
1411
1471
1538
1616
1700
1789
1880
1979
2080
2181
2284
BHP
0.94
1.05
1.18
1.33
1.52
1.73
1.97
2.24
2.54
2.87
3.23
3.63
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2400
2800
3200
3600
4000
4400
4800
5200
5600
6000
6400
6800
860
837
1003
1146
1290
1433
1577
1720
1863
2007
2150
2293
2437
939
1039
1134
1235
1338
1445
1554
1664
1774
1886
1999
2113
1576
1625
1684
1747
1824
1901
1989
2078
2170
2269
2369
1.45
1.60
1.77
1.96
2.20
2.46
2.76
3.09
3.45
3.84
4.27
1046
1155
1266
1378
1492
1607
1722
1837
1954
2070
1770
1820
1879
1940
2016
2093
2177
2265
2355
2449
2.06
2.25
2.46
2.69
2.98
3.30
3.65
4.04
4.47
4.93
1904
1950
2002
2062
2121
2198
2274
2355
2443
2.54
2.76
2.99
3.25
3.52
3.87
4.25
4.66
5.11
2073
2119
2174
2234
2294
2371
2447
3.29
3.55
3.83
4.13
4.46
4.86
5.29
2188
2233
2280
2338
2399
2461
3.85
4.13
4.43
4.76
5.11
5.49
Inlet Sound Power, LWi [dB ref 10-12 watts]
% WOV
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
1
2
3
4
5
6
7
8
LWi
61
A
RPM
600
% WOV
1
2
3
4
5
6
7
8
LWo
64
A
100
80
65 62 60 57 57 52 47 34
64 61 59 55 55 52 47 35
62 60 57 53 54 52 47 35
62 60 57 53 54 52 47 35
65 67 68 65 61 62 51 43
64 64 65 62 58 56 50 41
63 63 63 60 57 55 49 41
66 65 63 60 57 55 49 41
71 78 73 72 69 67 67 51
69 78 70 68 65 62 57 49
68 71 68 66 65 61 57 50
69 73 69 65 64 60 55 50
73 75 81 80 77 75 75 62
69 76 76 77 73 71 66 59
75 77 77 75 71 70 66 60
80 80 77 75 71 70 66 60
80 80 88 88 86 83 81 84
80 75 84 85 81 79 74 69
78 77 80 82 79 77 74 70
81 80 82 81 78 77 74 70
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
75 66 60 59 60 55 51 39
70 65 60 58 58 55 51 39
71 64 59 57 58 55 51 40
72 64 59 57 57 55 51 40
74 73 67 68 65 63 55 46
76 73 65 66 63 60 55 46
76 72 64 65 62 59 54 46
77 73 65 65 62 59 54 46
80 80 74 74 72 70 68 54
78 75 72 71 70 66 61 54
77 75 72 69 68 65 60 55
79 76 72 69 68 65 60 55
82 82 81 83 81 78 76 65
79 78 77 79 78 74 69 62
83 80 77 77 76 73 68 62
86 82 79 77 75 72 68 63
91 86 88 90 90 87 83 85
59
59
58
68
64
63
62
75
71
69
69
83
79
77
77
92
87
84
84
62
62
62
70
68
67
67
77
74
73
73
86
82
80
80
94
90
88
88
600
900
60
50
100
80
60
50
100
80
60
50
900
1250
1750
2483
1250
1750
2483
100
80
60
50
100
80
100
80
88
84 82 85 87 84 78 72
60
50
60
50
88 88 85 83 84 81 77 72
90 89 86 84 84 81 77 72
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-16 Class II
12
11
10
9
Performance Data
RPM
BHP
15
50% WOV
60% WOV
10
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
Maximum Fan RPM
3145
7½
25
20
15
10
5
Specification Data
70% WOV
Maximum Motor
Frame Size
215T
.25 kW
8
5
80% WOV
Minimum Motor
Starting hp
7
1/3 hp
20 in.
6
3
2
Wheel Diameter
508 mm
109 kg.
5
Approximate Weight
(Less Motor & Drives)
Maximum Bhp = (Fan RPM / 1430)3
Outlet Velocity (FPM) = CFM / 2.79
Tip Speed (FPM) = Fan RPM x 5.24
4
240 lbs.
90% WOV
3
1
2
1
0
0
% WOV = (CFM x 100) / (Fan RPM x 2.89)
0
1
2
3
4
5
6
7
8
9
10
Volume (cfm x 1000)
Imperial data — Metric data
12
14
16
0
2
4
6
8
10
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
6
7
8
RPM
1199
1291
1384
1478
1574
1670
1767
1865
1964
2063
2163
2263
BHP
0.50
0.61
0.73
0.86
1.01
1.18
1.38
1.59
1.83
2.10
2.39
2.71
RPM
1342
1421
1503
1592
1683
1774
1867
1960
2054
2149
2245
2341
BHP
0.77
0.89
1.03
1.20
1.39
1.61
1.83
2.06
2.33
2.62
2.93
3.27
RPM
1633
1688
1750
1816
1887
1965
2045
2128
2217
2307
2398
2489
BHP
1.48
1.62
1.78
1.95
2.16
2.39
2.65
2.94
3.27
3.63
4.02
4.45
RPM
1900
1934
1987
2041
2100
2163
2229
2299
2377
2457
2537
2623
BHP
2.29
2.47
2.66
2.88
3.10
3.35
3.61
3.91
4.26
4.63
5.03
5.48
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3000
3300
3600
3900
4200
4500
4800
5100
5400
5700
6000
6300
1075
1182
1290
1397
1505
1612
1720
1827
1935
2043
2150
2258
2176
2209
2249
2302
2356
2415
2478
2543
2608
2684
2762
3.41
3.63
3.88
4.14
4.42
4.73
5.05
5.39
5.76
6.19
6.66
2424
2456
2488
2539
2592
2646
2707
2770
2835
2900
4.68
4.96
5.25
5.57
5.91
6.27
6.65
7.05
7.48
7.93
2650
2682
2715
2758
2811
2865
2920
2983
3046
6.11
6.44
6.78
7.15
7.55
7.97
8.41
8.87
9.36
2861
2893
2926
2964
3017
3071
3125
7.68
8.07
8.46
8.88
9.34
9.82
10.3
3060
3092
3124
9.40
9.84
10.3
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
900
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWi
A
RPM
900
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWo
74
A
66 71 71 72 66 64 54 47
63 67 67 66 63 59 51 42
62 63 63 63 61 57 50 41
63 64 63 62 60 57 50 40
68 70 73 74 71 71 63 55
66 67 71 72 69 67 60 52
67 66 68 68 66 64 57 51
69 68 69 67 65 63 57 51
71 74 78 77 77 76 77 63
67 70 77 74 73 72 68 61
71 72 74 73 72 70 66 60
74 74 76 74 71 70 65 60
79 79 81 86 86 84 86 77
80 75 78 86 84 80 77 71
82 79 78 83 82 78 75 70
82 81 80 83 82 78 74 70
81 84 85 91 91 89 92 87
77 80 81 86 88 85 83 78
81 84 83 83 85 83 81 77
83 86 86 87 85 83 80 77
72
68
65
65
77
74
71
70
83
79
77
77
92
88
86
86
97
92
90
90
77 76 70 72 70 66 55 47
75 73 67 67 67 61 52 43
75 73 67 65 65 60 52 43
75 72 67 64 65 59 52 43
80 76 75 77 76 72 64 54
78 74 71 73 73 68 60 51
79 74 71 71 72 66 59 51
78 75 71 70 71 66 59 51
88 81 82 83 81 78 76 63
86 78 77 79 79 75 70 63
86 81 78 77 77 73 68 62
88 82 79 78 77 72 68 62
88 86 86 89 91 87 86 78
86 86 84 84 88 83 79 72
89 90 87 83 86 81 77 71
90 91 87 84 86 81 77 72
92 91 92 94 96 93 93 90
71
69
68
79
76
75
75
86
83
81
81
95
91
90
89
100
97
95
95
1250
1750
2475
3145
1250
1750
2475
3145
90
93 91 90 93 90 86 80
93 95 93 88 91 88 84 79
94 95 94 90 91 87 83 79
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-18 Class I & QEI-L
7
6
5
4
3
2
1
0
Performance Data
RPM
BHP
7½
50% WOV
60% WOV
QEI-L
QEI
2232
2232
Maximum
Fan RPM
16
14
12
10
8
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
5
70% WOV
Specification Data
Maximum
QEI-L
215T
215T
Motor
Frame Size
80% WOV
3
QEI
Minimum Motor
Starting hp
Wheel Diameter
1/3 hp
22.5 in.
QEI-L 190 lbs. 87 kg.
QEI 260 lbs. 118 kg.
.25 kW
1½
565 mm
6
90% WOV
Approximate Weight
(Less Motor & Drives)
¾
4
Maximum Bhp = (Fan RPM / 1199)3
Outlet Velocity (FPM) = CFM / 3.45
Tip Speed (FPM) = Fan RPM x 5.83
% WOV = (CFM x 100) / (Fan RPM x 4.50)
Imperial data — Metric data
1/3
2
0
0
1
2
3
4
5
6
7
8
9
10
11
Volume (cfm x 1000)
0
2
4
6
8
10
12
14
16
18
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
1.5 2.5
CFM
OV
0.25
RPM
0.5
1
2
3
3.5
4
BHP
0.17
0.23
0.31
0.42
0.54
0.69
0.87
1.08
1.33
1.62
1.94
2.31
RPM
814
BHP
0.30
0.37
0.46
0.58
0.72
0.89
1.09
1.32
1.58
1.88
2.23
2.61
RPM
1026
1080
1142
1213
1293
1376
1466
1558
1653
1752
1851
1952
BHP
0.62
0.72
0.84
0.97
1.13
1.32
1.55
1.81
2.11
2.44
2.82
3.24
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2600
3100
3600
4100
4600
5100
5600
6100
6600
7100
7600
8100
753
697
788
898
889
1250
1300
1358
1425
1498
1578
1660
1748
1840
1932
2028
1.12
1.26
1.43
1.61
1.81
2.06
2.33
2.66
3.02
3.43
3.88
1407
1445
1494
1552
1616
1686
1763
1843
1926
2015
2106
1.57
1.73
1.92
2.14
2.37
2.62
2.92
3.26
3.63
4.07
4.56
1043
1188
1333
1478
1623
1768
1913
2057
2202
2347
886
972
1583
1622
1672
1730
1793
1862
1936
2016
2097
2182
2.24
2.45
2.70
2.96
3.25
3.56
3.91
4.31
4.75
5.25
986
1062
1156
1254
1355
1456
1558
1662
1768
1875
1746
1785
1839
1897
1959
2029
2100
2180
3.03
3.28
3.58
3.91
4.25
4.62
5.02
5.49
1861
1899
1940
1997
2055
2118
2187
3.63
3.91
4.22
4.58
4.96
5.37
5.79
1088
1192
1298
1405
1513
1620
1729
1837
2006
2044
2090
2148
2206
4.57
4.91
5.28
5.69
6.14
Inlet Sound Power, LWi [dB ref 10-12 watts]
% WOV
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
1
2
3
4
5
6
7
8
LWi
65
A
RPM
550
% WOV
1
2
3
4
5
6
7
8
LWo
68
A
100
80
65 68 68 64 57 52 49 41
61 67 68 64 56 52 48 40
60 67 68 64 56 52 48 39
62 67 67 64 56 51 48 39
66 70 69 64 59 61 49 41
62 66 68 62 58 56 49 40
61 64 66 60 55 55 49 40
64 64 66 59 55 54 48 40
70 78 73 72 67 68 66 53
64 78 73 69 64 62 57 51
66 73 70 67 62 61 57 52
69 73 70 66 61 61 56 52
77 80 87 82 78 75 77 64
76 75 80 78 74 72 67 61
78 77 83 75 71 70 66 62
79 78 82 76 70 69 66 62
80 83 92 89 87 84 81 83
74 78 87 85 85 81 76 71
80 79 82 82 82 78 74 70
83 82 83 82 81 77 74 71
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
74 74 67 66 63 55 53 45
72 73 68 68 62 56 56 50
69 72 67 67 62 56 56 51
69 72 67 67 62 56 57 52
74 75 68 67 64 62 54 43
71 73 66 65 63 58 54 43
72 70 66 63 62 57 54 43
72 70 65 63 61 57 54 43
77 84 75 74 72 68 65 51
73 80 70 71 69 64 59 50
75 77 69 69 67 63 58 50
77 77 70 69 66 62 58 51
82 83 84 84 83 77 75 64
78 83 80 80 80 75 70 64
82 82 77 78 77 74 69 64
86 84 78 78 76 73 69 64
88 87 91 93 92 87 82 82
65
65
64
67
65
63
63
75
71
69
69
85
80
79
78
92
89
86
85
68
68
68
70
68
66
66
77
74
72
71
87
83
81
81
95
93
91
90
550
800
60
50
100
80
60
50
100
80
60
50
800
1100
1600
2232
1100
1600
2232
100
80
60
50
100
80
100
80
83
83 85 89 90 85 79 72
60
50
60
50
88 89 83 87 88 82 77 71
93 92 85 86 87 81 76 72
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-18 Class II
12
11
10
9
Performance Data
RPM
BHP
15
10
50% WOV
60% WOV
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
Maximum Fan RPM
2777
25
20
15
10
5
Specification Data
7½
70% WOV
Maximum Motor
Frame Size
254T
8
5
80% WOV
Minimum Motor
Starting hp
7
1/3 hp
.25 kW
6
Wheel Diameter
22.25 in. 565 mm
3
2
5
Approximate Weight
(Less Motor & Drives)
Maximum Bhp = (Fan RPM / 1219)3
Outlet Velocity (FPM) = CFM / 3.45
Tip Speed (FPM) = Fan RPM x 5.83
4
310 lbs.
141 kg.
90% WOV
3
1
2
1
0
0
% WOV = (CFM x 100) / (Fan RPM x 3.80)
4
5
6
7
8
9
10
11
0
1
2
3
Volume (cfm x 1000)
Imperial data — Metric data
0
5
10
15
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
6
7
8
RPM
1124
1219
1315
1413
1511
1611
1711
1812
1913
2015
2117
2219
BHP
0.64
0.79
0.96
1.16
1.40
1.66
1.96
2.29
2.66
3.07
3.53
4.03
RPM
1239
1326
1414
1503
1595
1690
1786
1883
1981
2079
2178
2277
BHP
0.97
1.14
1.34
1.56
1.82
2.11
2.44
2.81
3.21
3.66
4.16
4.70
RPM
1467
1538
1609
1682
1758
1844
1932
2020
2110
2200
2295
2390
BHP
1.74
1.98
2.25
2.50
2.77
3.11
3.48
3.89
4.34
4.83
5.38
5.98
RPM
1690
1738
1787
1858
1929
2001
2075
2150
2236
2323
2411
2500
BHP
2.65
2.88
3.15
3.50
3.89
4.29
4.66
5.07
5.57
6.12
6.70
7.34
RPM
1900
1934
1977
2024
2079
2150
2221
2293
2366
2440
2521
2608
BHP
3.67
3.94
4.24
4.56
4.94
5.42
5.94
6.50
6.98
7.49
8.10
8.78
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3800
4200
4600
5000
5400
5800
6200
6600
7000
7400
7800
8200
1101
1217
1333
1449
1565
1681
1797
1913
2028
2144
2260
2376
2120
2154
2193
2241
2289
2354
2424
2495
2568
2641
2715
5.09
5.42
5.78
6.18
6.60
7.14
7.76
8.42
9.11
9.71
10.4
2290
2323
2356
2394
2441
2489
2544
2615
2686
2757
6.31
6.69
7.09
7.51
7.98
8.48
9.06
9.77
10.5
11.3
2478
2511
2545
2582
2629
2676
2726
8.02
8.47
8.93
9.42
9.97
10.5
11.2
2656
2689
2723
2760
9.91
10.4
10.9
11.5
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
800
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWi
A
RPM
800
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWo
72
A
66 75 67 66 63 65 51 43
63 71 64 63 62 62 51 41
62 69 63 61 62 63 53 42
77 73 69 65 62 62 50 41
70 78 72 72 68 72 60 51
62 73 68 67 66 66 57 48
63 72 66 66 65 66 57 49
66 72 67 65 64 65 56 49
78 79 82 80 78 76 80 64
71 76 77 75 74 73 67 60
73 76 74 73 72 72 67 61
77 77 76 73 72 71 66 61
81 84 89 88 87 84 87 78
75 78 83 83 82 80 76 69
79 81 84 81 79 78 75 71
83 83 84 81 78 77 74 70
85 88 89 93 93 90 91 87
80 83 85 89 90 87 82 76
84 86 85 88 87 85 80 76
87 89 89 88 86 84 80 76
70
67
67
68
76
71
71
70
85
79
77
77
93
87
85
85
98
93
91
91
73 79 66 69 68 66 54 45
70 76 63 67 66 63 53 46
70 74 63 65 66 63 53 46
70 75 63 65 65 62 53 47
78 83 74 76 74 72 63 53
73 77 69 73 72 68 60 50
75 75 68 71 71 68 60 52
77 77 70 71 70 68 60 53
87 86 83 85 84 78 79 64
84 80 77 81 80 75 70 61
85 80 77 79 78 74 70 62
86 82 78 79 77 74 69 62
89 89 91 92 91 86 86 80
85 86 85 88 89 83 79 73
89 88 86 86 87 82 78 73
91 89 88 87 86 81 77 73
93 94 93 96 97 93 91 88
70
70
69
79
76
74
75
88
84
82
82
96
92
90
90
1100
1600
2200
2777
1100
1600
2200
2777
101
97
95
88
91 89 92 94 90 86 79
94 94 92 89 92 88 84 79
96 95 92 91 92 88 84 79
96
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-20 Class I & QEI-L
6
5
4
3
2
1
0
Performance Data
RPM
BHP
50% WOV
7½
14
12
10
8
QEI-L
QEI
1900
2027
Maximum
Fan RPM
% WOV
60% WOV
10
Density 0.075 lb/ft3
Density 1.2 kg/m3
5
Specification Data
70% WOV
Maximum
Motor
Frame Size
QEI-L
QEI
215T
215T
3
2
80% WOV
Minimum Motor
Starting hp
Wheel Diameter
1/3 hp
24.5 in.
QEI-L 230 lbs. 105 kg.
QEI 310 lbs. 141 kg.
.25 kW
6
622 mm
90% WOV
1
Approximate Weight
(Less Motor & Drives)
4
½
Maximum Bhp = (Fan RPM / 1021)3
Outlet Velocity (FPM) = CFM / 4.14
Tip Speed (FPM) = Fan RPM x 6.41
% WOV = (CFM x 100) / (Fan RPM x 6.01)
Imperial data — Metric data
2
0
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Volume (cfm x 1000)
0
5
10
15
20
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
1.5 2.5
CFM
OV
0.25
RPM
0.5
1
2
3
3.5
4
BHP
0.19
0.27
0.39
0.53
0.72
0.95
1.23
1.56
1.96
2.41
2.94
3.55
RPM
724
BHP
0.35
0.44
0.57
0.74
0.95
1.20
1.50
1.86
2.28
2.76
3.32
3.95
RPM
923
BHP
0.73
0.86
1.02
1.21
1.45
1.74
2.09
2.49
2.95
3.48
4.08
4.76
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3000
3700
4400
5100
5800
6500
7200
7900
8600
9300
724
613
708
893
801
975
1132
1183
1245
1317
1398
1483
1574
1669
1766
1868
1972
1.34
1.54
1.78
2.03
2.34
2.71
3.15
3.66
4.23
4.88
5.60
1062
1231
1400
1570
1739
1908
2077
2246
810
887
1040
1116
1201
1292
1388
1486
1590
1694
1800
1907
1314
1368
1428
1501
1577
1662
1748
1842
1937
2.11
2.38
2.70
3.03
3.41
3.88
4.40
5.01
5.71
1440
1480
1538
1599
1671
1746
1830
1915
2005
2.73
3.03
3.38
3.78
4.19
4.66
5.22
5.84
6.56
915
982
1593
1637
1697
1759
1832
1907
1990
3.73
4.11
4.54
5.02
5.52
6.07
6.74
1697
1738
1789
1849
1913
1985
4.47
4.88
5.34
5.86
6.42
7.02
1023
1133
1245
1357
1470
1584
1698
1812
1082
1187
1292
1400
1508
1619
1731
1843
1835
1875
1934
1994
5.69
6.17
6.74
7.35
10000 2415
10700 2584
Inlet Sound Power, LWi [dB ref 10-12 watts]
% WOV
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
500
1
2
3
4
5
6
7
8
LWi
65
65
65
65
A
RPM
500
% WOV
1
2
3
4
5
6
7
8
LWo
68
A
100
80
66 69 68 64 57 53 49 40
63 69 68 64 56 52 48 40
62 69 68 64 56 52 48 39
64 68 68 64 56 52 48 39
66 70 68 63 60 59 48 40
62 67 67 62 57 55 48 38
61 65 65 59 55 54 47 39
63 65 65 59 55 53 47 38
72 79 74 72 68 69 65 52
67 79 73 69 65 62 57 51
68 74 70 67 63 61 57 52
71 74 70 66 62 61 57 52
79 82 87 82 78 76 76 63
77 77 81 78 75 72 67 61
79 79 82 76 71 70 66 63
80 80 82 76 71 69 66 63
82 85 93 90 88 84 82 84
76 80 88 86 85 81 76 71
81 81 83 83 82 78 74 71
84 83 84 83 81 77 74 71
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
75 74 68 67 62 56 53 45
73 73 68 68 62 56 56 50
71 72 68 68 62 57 56 51
70 72 68 67 62 57 57 52
74 74 68 66 64 60 52 41
72 72 66 64 62 58 52 41
71 69 65 63 61 57 52 41
71 69 65 62 61 56 52 41
79 84 75 75 72 68 64 50
75 80 71 72 70 64 58 50
76 77 70 70 67 63 58 50
78 77 70 69 67 63 58 51
83 84 85 85 83 77 74 63
79 82 81 81 80 75 69 63
83 81 78 79 78 74 69 64
86 83 79 79 76 73 69 64
89 89 92 93 92 87 83 83
69
68
68
69
67
66
65
77
74
72
72
87
84
82
81
96
93
91
90
60
50
100
80
60
50
100
80
60
50
66
64
62
62
75
72
70
69
85
80
79
79
93
89
86
86
700
1000
1450
2027
700
1000
1450
2027
100
80
60
50
100
80
100
80
84
84 86 90 90 85 79 72
60
50
60
50
89 89 85 88 88 82 77 72
93 92 86 87 87 81 76 72
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-20 Class II
10
9
8
7
6
5
4
3
2
1
0
Performance Data
RPM
BHP
15
10
50% WOV
% WOV
60% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
Maximum Fan RPM
2517
7½
Specification Data
20
15
10
5
70% WOV
Maximum Motor
Frame Size
254T
1/3 hp
80% WOV
5
Minimum Motor
Starting hp
.25 kW
622 mm
163 kg.
3
Wheel Diameter
24.5 in.
360 lbs.
Approximate Weight
(Less Motor & Drives)
Maximum Bhp = (Fan RPM / 1038)3
Outlet Velocity (FPM) = CFM / 4.14
Tip Speed (FPM) = Fan RPM x 6.41
90% WOV
1½
0
% WOV = (CFM x 100) / (Fan RPM x 5.07)
4
5
6
7
8
9
10
11
12
13
0
1
2
3
Volume (cfm x 1000)
Imperial data — Metric data
20
0
5
10
15
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
6
7
8
RPM
1002
1090
1181
1272
1364
1457
1551
1645
1740
1835
1930
2026
BHP
0.74
0.92
1.13
1.38
1.66
1.99
2.36
2.77
3.24
3.75
4.33
4.96
RPM
1110
1189
1271
1355
1440
1529
1619
1710
1801
1893
1986
2079
BHP
1.14
1.34
1.58
1.86
2.18
2.54
2.95
3.40
3.91
4.48
5.10
5.78
RPM
1319
1384
1451
1519
1589
1670
1751
1834
1918
2003
2092
2181
BHP
2.05
2.34
2.67
2.99
3.32
3.74
4.20
4.72
5.28
5.90
6.59
7.34
RPM
1526
1570
1615
1679
1745
1813
1882
1953
2033
2115
2197
2280
BHP
3.15
3.44
3.75
4.19
4.67
5.18
5.64
6.14
6.77
7.45
8.20
9.00
RPM
1719
1750
1788
1833
1882
1948
2015
2082
2151
2220
2297
2378
BHP
4.38
4.71
5.08
5.48
5.94
6.53
7.18
7.88
8.48
9.12
9.89
10.7
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
4500
5000
5500
6000
6500
7000
7500
8000
8500
9000
9500
1076
1196
1315
1435
1555
1674
1794
1913
2033
2153
2272
1920
1951
1986
2031
2075
2135
2201
2268
2336
2404
2474
6.10
6.51
6.95
7.44
7.96
8.64
9.40
10.2
11.1
11.8
12.6
2105
2136
2170
2214
2258
2310
2376
2443
2510
8.04
8.53
9.05
9.64
10.3
11.0
11.9
12.8
13.8
2246
2277
2308
2342
2386
2430
2477
9.65
10.2
10.8
11.4
12.1
12.8
13.5
2408
2439
2471
2505
11.9
12.6
13.2
13.9
10000 2392
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
700
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWi
A
RPM
700
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWo
71
A
68 74 67 66 64 62 49 42
65 70 64 63 62 60 49 39
64 68 62 61 62 61 51 40
76 72 68 65 62 60 48 40
72 80 73 72 70 71 60 51
64 75 69 68 67 65 56 48
65 74 67 67 66 65 57 49
68 74 68 66 65 65 56 49
79 80 82 81 79 77 79 63
73 77 77 76 75 73 67 59
75 77 75 73 72 72 67 61
78 78 77 74 72 71 67 61
82 86 91 89 87 85 87 78
76 80 85 84 83 80 76 69
81 83 85 81 80 78 75 71
84 84 85 82 79 78 75 71
88 89 90 94 94 90 92 87
82 85 86 90 91 87 82 76
86 87 85 89 87 85 80 76
89 90 90 89 87 85 80 77
69
66
66
68
76
72
71
71
85
79
78
78
93
87
86
85
99
94
92
92
74 76 66 69 67 63 52 43
71 73 64 67 66 61 52 44
71 72 63 65 65 61 52 45
71 72 64 65 65 61 52 46
80 85 75 76 75 72 63 52
75 78 70 74 72 68 60 50
76 77 69 71 71 68 60 52
78 79 71 71 71 68 60 52
88 86 84 86 83 79 77 63
84 81 78 82 81 75 70 61
85 80 78 80 79 74 69 62
86 82 79 79 78 74 69 62
90 90 92 93 91 87 86 80
86 87 87 89 89 83 79 73
90 88 87 87 87 82 78 73
92 90 89 87 86 82 78 73
95 94 93 97 98 93 92 89
70
69
69
79
76
75
75
88
84
83
82
96
92
90
90
1000
1450
2000
2517
1000
1450
2000
2517
102
98
96
90
92 89 93 96 90 86 79
95 94 92 90 93 88 85 79
97 96 93 92 93 88 84 79
96
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-22 Class I & QEI-L
6
5
4
3
2
1
0
Performance Data
RPM
BHP
10
50% WOV
14
12
10
8
7½
QEI-L
QEI
1800
1839
Maximum
Fan RPM
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
60% WOV
5
Specification Data
70% WOV
Maximum
Motor
Frame Size
QEI-L
QEI
215T
254T
80% WOV
3
2
Minimum Motor
Starting hp
Wheel Diameter
1/3 hp
27 in.
QEI-L 270 lbs. 123 kg.
QEI 370 lbs. 168 kg.
.25 kW
6
686 mm
Approximate Weight
(Less Motor & Drives)
1
4
90% WOV
½
Maximum Bhp = (Fan RPM / 857)3
Outlet Velocity (FPM) = CFM / 5.12
Tip Speed (FPM) = Fan RPM x 7.07
% WOV = (CFM x 100) / (Fan RPM x 8.60)
Imperial data — Metric data
2
0
0
2
4
6
8
10
12
14
16
Volume (cfm x 1000)
0
5
10
15
20
25
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
1.5 2.5
CFM
OV
0.25
RPM
0.5
1
2
3
3.5
4
BHP
0.25
0.34
0.45
0.60
0.79
1.02
1.29
1.61
1.98
2.41
2.90
3.46
RPM
662
BHP
0.44
0.55
0.69
0.87
1.08
1.33
1.62
1.97
2.37
2.83
3.35
3.94
RPM
837
BHP
0.93
1.07
1.25
1.46
1.72
2.01
2.35
2.75
3.20
3.70
4.27
4.91
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3900
4700
5500
6300
7100
7900
8700
9500
762
918
564
641
725
883
1023
1066
1116
1173
1236
1305
1377
1451
1530
1610
1691
1.68
1.90
2.14
2.43
2.77
3.15
3.59
4.08
4.64
5.26
5.95
1075
1231
1388
1544
1700
1857
723
796
935
1184
1228
1277
1332
1394
1458
1529
1602
1676
1755
2.61
2.90
3.22
3.60
4.02
4.49
5.03
5.63
6.29
7.03
1301
1329
1376
1425
1480
1541
1603
1673
1745
1818
3.38
3.72
4.08
4.49
4.94
5.46
6.03
6.67
7.38
8.16
806
872
997
1434
1466
1515
1564
1619
1680
1742
1809
4.58
4.99
5.44
5.93
6.48
7.09
7.76
8.51
892
953
1065
1137
1213
1293
1374
1456
1539
1624
1560
1598
1646
1696
1751
1813
5.94
6.44
6.97
7.54
8.19
8.91
1650
1678
1723
1772
1822
6.93
7.47
8.05
8.67
9.34
979
1035
1118
1204
1290
1377
1465
1554
1068
1156
1246
1335
1426
1516
10300 2013
11100 2170
11900 2326
12700 2482
Inlet Sound Power, LWi [dB ref 10-12 watts]
% WOV
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
450
1
2
3
4
5
6
7
8
LWi
65
64
63
63
70
68
66
66
78
74
72
71
87
83
79
78
97
93
89
87
A
RPM
450
% WOV
1
2
3
4
5
6
7
8
LWo
69
A
100
80
68 69 64 60 59 59 52 38
67 68 62 59 57 59 52 38
66 67 60 58 56 58 52 38
67 68 60 58 55 58 52 38
70 75 70 67 64 65 54 43
67 75 68 64 61 61 54 41
67 74 65 62 59 60 53 41
68 73 65 62 58 60 53 41
73 79 78 74 71 72 61 53
69 76 77 71 68 66 58 50
70 73 74 68 66 63 56 50
72 74 74 67 65 62 55 49
76 89 85 83 81 78 79 65
72 91 83 79 78 75 69 61
74 83 79 76 74 71 65 61
78 83 79 75 73 69 64 62
81 86 99 94 91 88 88 77
79 82 95 92 87 84 80 72
80 82 87 87 84 81 76 71
84 84 86 86 82 79 75 71
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
71 71 65 64 65 62 56 44
71 70 63 63 64 62 57 44
69 69 62 62 64 62 57 44
72 70 61 61 64 62 57 45
78 75 70 69 67 66 57 47
76 74 70 69 67 65 58 47
75 74 69 67 66 65 58 48
75 74 69 65 65 65 58 48
77 83 77 78 75 73 64 53
73 80 74 76 73 69 62 51
74 78 72 72 71 67 60 51
77 79 72 71 70 66 60 51
83 84 84 86 85 81 79 64
81 82 80 83 82 77 71 60
84 81 78 79 77 72 66 59
88 83 79 78 76 71 65 60
87 89 91 96 93 90 88 79
68
68
68
72
72
71
71
80
78
75
74
89
85
81
81
98
94
91
90
60
50
100
80
60
50
100
80
60
50
650
900
650
900
100
80
60
50
100
80
1300
1839
1300
1839
100
80
86
84 90 92 90 87 82 72
60
50
60
50
91 89 87 89 87 83 78 71
94 91 88 88 85 81 76 71
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-22 Class II
10
8
Performance Data
RPM
BHP
60% WOV
15
20
% WOV
10
Density 0.075 lb/ft3
Density 1.2 kg/m3
Maximum Fan RPM
2265
70% WOV
Specification Data
20
15
10
5
7½
Maximum Motor
Frame Size
256T
.25 kW
80% WOV
6
Minimum Motor
Starting hp
5
1/3 hp
27 in.
Wheel Diameter
686 mm
191 kg.
4
Approximate Weight
(Less Motor & Drives)
Maximum Bhp = (Fan RPM / 869)3
Outlet Velocity (FPM) = CFM / 5.12
Tip Speed (FPM) = Fan RPM x 7.07
90% WOV
420 lbs.
2
2
0
0
18
% WOV = (CFM x 100) / (Fan RPM x 7.17)
0
2
4
6
8
10
Volume (cfm x 1000)
12
14
16
Imperial data — Metric data
25
30
0
5
10
15
20
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
6
7
8
RPM
882
BHP
0.81
1.00
1.22
1.47
1.76
2.09
2.46
2.87
3.33
3.84
4.40
5.02
RPM
982
BHP
1.29
1.51
1.75
2.03
2.34
2.71
3.12
3.58
4.10
4.66
5.28
5.96
RPM
1174
1222
1273
1335
1396
1459
1528
1598
1668
1740
1813
1888
BHP
2.43
2.69
2.97
3.32
3.71
4.13
4.60
5.11
5.68
6.29
6.96
7.72
RPM
1360
1395
1434
1480
1531
1588
1649
1711
1773
1841
1910
1980
BHP
3.80
4.11
4.43
4.81
5.22
5.69
6.23
6.81
7.45
8.13
8.87
9.66
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
5600
6200
6800
7400
8000
8600
9200
9800
1093
1210
1328
1445
1562
1679
1796
1914
956
1045
1115
1185
1257
1331
1407
1483
1560
1637
1715
1794
1564
1588
1626
1666
1714
1764
1820
1881
1942
2005
2068
5.70
6.07
6.49
6.94
7.45
8.00
8.61
9.32
10.1
10.9
11.8
1032
1109
1187
1265
1345
1425
1505
1586
1667
1749
1746
1762
1801
1840
1882
1932
1982
2039
2100
2161
7.86
8.32
8.83
9.37
9.96
10.6
11.3
12.1
13.0
13.9
1912
1925
1962
2001
2040
2088
2138
2189
2249
10.3
10.8
11.4
12.1
12.8
13.5
14.3
15.2
16.2
2065
2078
2113
2152
2192
2237
13.0
13.6
14.3
15.0
15.8
16.7
2195
2209
2222
2257
15.2
15.9
16.6
17.4
10400 2031
11000 2148
11600 2265
12200 2382
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
650
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWi
A
RPM
650
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWo
72
A
66 75 70 65 63 64 51 43
64 72 67 62 62 59 51 41
64 70 65 60 60 59 51 41
67 72 66 61 60 59 52 41
70 79 73 71 69 73 60 52
68 73 69 68 66 66 59 49
70 71 69 66 65 65 59 50
73 75 70 66 65 65 59 50
75 80 89 82 79 76 79 63
71 76 85 79 76 73 68 60
75 76 80 76 74 71 66 61
79 83 86 76 73 71 66 61
81 85 93 89 88 84 87 78
76 79 90 85 85 81 77 69
82 82 87 83 82 78 74 70
85 87 90 83 81 78 74 70
85 88 94 95 94 91 91 89
79 82 89 91 91 87 83 76
85 87 88 88 87 84 80 77
87 92 93 89 87 83 80 77
70
67
65
66
77
72
71
71
86
82
79
81
94
89
87
87
99
95
91
92
74 79 68 69 66 64 55 45
73 78 66 67 65 64 59 49
73 77 65 65 64 63 59 48
75 78 66 65 64 63 58 47
77 80 74 75 72 72 64 54
73 76 70 73 71 68 63 52
74 76 70 71 69 68 63 53
81 79 71 71 70 68 64 54
82 84 85 86 82 77 78 67
79 79 80 84 80 75 71 65
81 82 80 81 78 74 70 65
82 84 80 81 77 74 70 65
87 89 92 92 91 86 86 80
82 86 88 92 89 84 80 71
86 90 89 88 86 81 79 72
88 91 90 88 86 81 79 72
92 94 96 98 96 92 91 90
71
70
70
78
76
74
75
88
85
83
83
95
93
91
91
900
1300
1800
2265
900
1300
1800
2265
101
96
95
87
88 92 93 92 89 85 78
92 93 92 92 91 87 83 77
93 94 93 92 91 87 83 78
95
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-24 Class I & QEI-L
6
5
4
3
2
1
0
Performance Data
RPM
BHP
50% WOV
15
14
12
10
8
60% WOV
QEI-L
QEI
1450
1655
% WOV
Maximum
Fan RPM
10
7½
Density 0.075 lb/ft3
Density 1.2 kg/m3
70% WOV
Specification Data
Maximum
QEI-L
5
3
215T
254T
Motor
Frame Size
80% WOV
QEI
Minimum Motor
Starting hp
Wheel Diameter
1/3 hp
30 in.
QEI-L 400 lbs. 182 kg.
QEI 470 lbs. 213 kg.
.25 kW
6
762 mm
1½
Approximate Weight
(Less Motor & Drives)
4
90% WOV
¾
Maximum Bhp = (Fan RPM / 719)3
Outlet Velocity (FPM) = CFM / 6.21
Tip Speed (FPM) = Fan RPM x 7.85
% WOV = (CFM x 100) / (Fan RPM x 11.8)
Imperial data — Metric data
2
0
0
2
4
6
8
10
12
14
25
16
18
30
20
Volume (cfm x 1000)
0
5
10
15
20
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
1.5 2.5
CFM
OV
0.25
RPM
0.5
1
2
3
3.5
4
BHP
0.28
0.39
0.53
0.71
0.93
1.21
1.54
1.93
2.39
2.91
3.52
4.21
RPM
584
BHP
0.52
0.65
0.82
1.03
1.28
1.59
1.95
2.37
2.86
3.43
4.07
4.80
RPM
748
BHP
1.11
1.29
1.50
1.76
2.06
2.42
2.84
3.33
3.88
4.50
5.21
6.00
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
4600
5600
6600
7600
8600
9600
740
901
494
563
640
786
915
951
2.02
2.29
2.59
2.94
3.35
3.82
4.36
4.96
5.65
6.42
7.27
1062
1223
1384
1545
636
704
831
1060
1097
1142
1190
1247
1304
1369
1435
1502
1574
3.16
3.52
3.91
4.36
4.88
5.46
6.13
6.87
7.69
8.60
712
772
888
996
1191
1231
1276
1324
1380
1436
1499
1564
1631
4.51
4.96
5.46
6.02
6.65
7.35
8.15
9.03
9.99
1286
1312
1357
1402
1450
1506
1562
1623
5.56
6.07
6.63
7.23
7.90
8.66
9.49
10.4
790
845
948
1047
1103
1165
1231
1298
1369
1442
1516
1400
1431
1475
1521
1570
1626
7.24
7.85
8.51
9.22
10.0
10.9
1481
1507
1545
1589
1635
8.45
9.12
9.83
10.6
11.4
869
920
1013
1082
1154
1228
1303
1378
1455
10600 1706
11600 1867
12600 2028
13600 2190
14600 2351
15600 2512
949
996
1030
1112
1193
1275
1358
1073
1152
1231
1311
1392
Inlet Sound Power, LWi [dB ref 10-12 watts]
% WOV
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
400
1
2
3
4
5
6
7
8
LWi
65
A
RPM
400
% WOV
1
2
3
4
5
6
7
8
LWo
69
A
100
80
69 69 64 61 60 58 50 36
68 68 62 59 58 58 50 36
66 67 60 58 57 58 50 37
67 67 60 58 56 58 50 36
72 76 71 68 65 65 55 43
70 75 69 65 62 61 54 41
69 75 66 63 60 61 53 41
71 74 66 63 60 61 53 41
76 81 80 76 73 73 62 55
72 79 79 73 70 67 59 51
72 75 76 69 67 65 57 51
74 77 76 68 66 63 57 51
79 91 85 83 81 79 77 63
76 92 83 80 78 74 68 60
76 85 79 76 74 70 65 61
79 84 79 75 73 69 64 63
83 89 100 95 91 89 87 76
80 85 95 92 88 85 80 72
81 84 88 88 84 81 76 71
85 85 87 86 82 79 75 71
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
72 71 65 65 65 62 55 43
72 70 63 64 64 62 55 43
70 69 63 63 64 62 55 43
72 69 62 63 64 62 56 43
79 76 72 71 68 67 58 47
77 75 71 70 68 66 58 47
77 75 70 68 67 66 58 48
77 75 70 67 66 65 59 48
80 84 79 80 77 75 65 54
76 81 76 78 75 70 63 52
77 79 74 74 73 68 61 52
79 80 74 73 72 68 61 52
83 85 85 86 84 81 77 62
82 83 81 83 81 76 69 59
84 82 78 79 77 72 65 58
87 84 79 79 76 71 65 59
88 90 92 96 94 91 88 78
64
63
63
71
69
67
67
79
76
73
73
87
83
79
78
97
94
89
88
68
68
68
73
73
72
72
82
79
77
76
89
85
81
81
98
94
91
90
60
50
100
80
60
50
100
80
60
50
600
850
600
850
100
80
60
50
100
80
1150
1655
1150
1655
100
80
87
86 91 92 90 87 81 71
60
50
60
50
91 89 88 90 87 83 78 70
94 91 89 89 86 81 76 71
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-24 Class II
10
9
8
7
6
5
4
3
2
1
0
Performance Data
RPM
BHP
20
25
15
60% WOV
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
Maximum Fan RPM
2036
Specification Data
20
15
10
5
70% WOV
10
Maximum Motor
Frame Size
284T
.55 kW
80% WOV
7½
Minimum Motor
Starting hp
3/4 hp
30 in.
5
2
Wheel Diameter
762 mm
249 kg.
Approximate Weight
(Less Motor & Drives)
Maximum Bhp = (Fan RPM / 729)3
Outlet Velocity (FPM) = CFM / 6.21
Tip Speed (FPM) = Fan RPM x 7.85
550 lbs.
90% WOV
0
% WOV = (CFM x 100) / (Fan RPM x 9.84)
12
Volume (cfm x 1000)
14
16
18
30
0
2
4
6
8
10
20
Imperial data — Metric data
0
5
10
15
20
25
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
6
7
8
RPM
784
BHP
0.97
1.18
1.43
1.71
2.03
2.40
2.81
3.26
3.76
4.32
4.94
5.61
RPM
875
BHP
1.56
1.80
2.08
2.39
2.74
3.15
3.60
4.11
4.67
5.29
5.97
6.72
RPM
1051
1090
1133
1184
1236
1289
1345
1404
1464
1524
1585
1648
BHP
2.96
3.25
3.57
3.96
4.39
4.87
5.39
5.97
6.59
7.27
8.00
8.82
RPM
1222
1248
1281
1318
1360
1405
1457
1509
1562
1617
1675
1734
BHP
4.64
4.99
5.36
5.78
6.25
6.76
7.36
8.02
8.72
9.48
10.3
11.2
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6800
7500
8200
8900
9600
1075
1186
1297
1408
1518
847
928
1405
1420
1453
1486
1523
1566
1609
1660
1712
1765
1818
6.94
7.37
7.85
8.36
8.92
9.54
10.2
11.0
11.8
12.7
13.7
911
987
1568
1580
1607
1641
1674
1714
1757
1800
1851
1903
9.57
10.1
10.7
11.3
11.9
12.7
13.5
14.3
15.3
16.3
976
1046
1107
1169
1233
1298
1363
1428
1494
1561
1717
1728
1751
1784
1817
1853
1895
1938
1982
12.5
13.1
13.8
14.5
15.3
16.1
17.0
18.0
19.0
1042
1108
1176
1244
1312
1380
1449
1518
1854
1865
1885
1918
1951
1985
2026
15.7
16.5
17.2
18.1
19.0
19.9
20.9
10300 1629
11000 1740
11700 1851
12400 1962
13100 2072
13800 2183
14500 2294
1983
1994
2013
19.3
20.1
21.0
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
600
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWi
A
RPM
600
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWo
73
A
69 76 71 66 65 64 52 43
67 73 68 64 63 59 51 41
66 71 66 61 61 59 51 41
69 73 67 62 62 60 52 41
73 81 75 73 71 74 61 53
71 76 71 70 68 67 60 50
72 74 71 68 67 67 61 51
76 78 72 68 67 67 60 51
76 82 88 82 79 77 77 61
72 78 85 79 76 73 67 59
76 77 80 76 74 71 66 60
80 84 85 76 73 71 66 61
83 87 95 90 89 86 87 78
78 82 92 86 86 82 77 69
84 84 89 84 83 79 75 71
86 89 91 84 82 78 75 71
86 89 96 96 95 91 92 90
80 84 91 92 92 88 83 76
87 88 89 89 88 84 80 77
89 94 94 89 87 84 80 77
71
68
66
67
78
74
73
73
86
82
79
81
95
91
88
88
100
95
92
93
76 79 70 70 67 65 56 45
76 78 68 68 67 65 59 49
75 77 67 67 66 64 59 49
76 78 67 66 65 64 59 47
79 82 76 77 74 74 65 55
75 78 73 75 73 70 64 53
76 79 72 73 71 69 65 54
83 81 73 73 71 69 65 55
83 84 86 86 82 78 77 65
80 80 81 83 80 75 71 64
81 82 81 81 78 74 70 65
83 83 81 81 77 74 70 65
88 90 94 94 92 87 87 81
84 87 90 93 90 84 80 72
88 91 91 89 87 82 79 72
89 92 91 89 87 82 80 73
94 95 97 99 97 93 92 91
72
71
71
80
77
76
77
87
84
83
82
96
94
92
92
102
97
95
96
850
1150
1650
2036
850
1150
1650
2036
88
89 93 94 93 89 85 77
93 94 93 93 91 87 83 77
94 95 94 93 91 87 83 78
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-27 Class I & QEI-L
6
5
4
3
2
1
0
Performance Data
RPM
BHP
50% WOV
15
14
12
10
8
QEI-L
QEI
1280
1505
10
Maximum
Fan RPM
60% WOV
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
7½
70% WOV
Specification Data
Maximum
Motor
Frame Size
QEI-L
QEI
215T
256T
5
3
80% WOV
Minimum Motor
Starting hp
Wheel Diameter
3/4 hp
33 in.
QEI-L 470 lbs. 214 kg.
QEI 540 lbs. 245 kg.
.55 kW
6
838 mm
90% WOV
Approximate Weight
(Less Motor & Drives)
1½
¾
4
Maximum Bhp = (Fan RPM / 626)3
Outlet Velocity (FPM) = CFM / 7.54
Tip Speed (FPM) = Fan RPM x 8.64
% WOV = (CFM x 100) / (Fan RPM x 15.2)
Imperial data — Metric data
2
0
0
2
4
6
8
10
12
14
16
18
20
22
24
Volume (cfm x 1000)
0
5
10
15
20
25
30
35
40
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
1.5 2.5
CFM
OV
0.25
RPM
0.5
1
2
3
3.5
4
BHP
0.35
0.48
0.65
0.87
1.14
1.47
1.88
2.35
2.91
3.55
4.29
5.13
RPM
541
BHP
0.63
0.79
0.98
1.24
1.54
1.91
2.35
2.86
3.46
4.14
4.92
5.80
RPM
690
BHP
1.32
1.53
1.79
2.10
2.46
2.88
3.38
3.96
4.62
5.37
6.23
7.18
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
5700
6900
8100
9300
755
915
459
524
594
724
843
875
2.40
2.72
3.08
3.51
3.99
4.54
5.15
5.88
6.70
7.61
8.62
950
3.36
3.75
4.17
4.64
5.19
5.81
6.50
7.25
8.10
9.08
10.2
1074
1233
593
651
767
976
1070
1097
1131
1172
1218
1269
1322
1379
1436
1497
4.85
5.34
5.87
6.46
7.14
7.90
8.74
9.64
10.6
11.8
664
716
819
916
1009
1050
1096
1148
1202
1259
1318
1383
1449
1182
1208
1246
1287
1332
1384
1436
1492
6.58
7.17
7.83
8.55
9.36
10.3
11.3
12.3
1260
1287
1314
1355
1396
1442
1494
7.88
8.55
9.26
10.0
10.9
11.9
12.9
10500 1392
11700 1551
12900 1710
14100 1870
15300 2029
16500 2188
17700 2347
18900 2506
737
783
875
964
1359
1386
1418
1459
1500
9.98
10.8
11.6
12.5
13.5
811
853
933
1017
1073
1131
1196
1262
1329
1397
886
924
999
962
997
1065
1133
1203
1275
1346
1038
1114
1191
1268
1070
1144
1219
1294
Inlet Sound Power, LWi [dB ref 10-12 watts]
% WOV
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
400
1
2
3
4
5
6
7
8
LWi
65
A
RPM
400
% WOV
1
2
3
4
5
6
7
8
LWo
68
A
100
80
70 71 64 59 61 58 52 38
65 68 62 58 57 58 52 40
65 67 62 59 57 58 52 42
67 68 61 58 57 58 53 42
73 72 70 65 65 67 54 45
70 70 67 63 61 61 54 44
69 69 64 61 60 60 55 44
74 70 64 61 60 60 54 44
84 83 75 73 70 76 62 54
82 80 73 70 69 66 60 53
79 77 71 68 67 64 59 52
79 78 71 67 66 63 59 52
77 86 86 84 80 78 82 66
73 84 83 80 77 74 70 63
75 84 79 76 75 72 67 64
79 82 82 76 74 71 66 64
80 89 92 93 89 85 90 76
78 87 88 90 86 83 79 72
81 90 88 86 83 80 77 72
85 89 89 86 82 80 76 73
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
70 70 65 67 62 60 55 44
69 68 63 65 59 61 57 45
69 69 63 64 59 61 57 45
68 68 62 64 59 61 56 45
78 73 71 71 67 67 56 46
75 71 68 69 65 65 57 47
74 70 67 67 65 64 57 47
73 71 66 66 64 64 56 46
85 82 77 79 74 75 64 55
85 80 75 76 72 68 62 53
83 79 74 75 71 67 61 53
83 79 74 73 71 66 61 52
85 89 86 89 84 81 82 66
81 86 82 86 81 77 72 63
84 87 81 83 78 75 69 63
87 88 83 82 78 74 68 64
88 91 93 97 93 89 89 79
64
63
64
71
67
66
66
79
74
72
71
88
83
80
80
95
91
89
88
67
67
66
73
71
70
70
81
78
76
75
90
86
84
84
99
95
92
93
60
50
100
80
60
50
100
80
60
50
550
750
550
750
100
80
60
50
100
80
1100
1505
1100
1505
100
80
86
89 90 94 90 87 83 73
60
50
60
50
91 89 88 91 87 84 81 72
93 92 90 92 87 83 80 72
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-27 Class II
10
9
8
7
6
5
4
3
2
1
0
Performance Data
RPM
BHP
30
25
20
60% WOV
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
Maximum Fan RPM
1847
15
Specification Data
20
15
10
5
70% WOV
Maximum Motor
Frame Size
286T
1.1 kW
10
80% WOV
Minimum Motor
Starting hp
11⁄2 hp
33 in.
7½
Wheel Diameter
838 mm
304 kg.
5
2
Approximate Weight
(Less Motor & Drives)
Maximum Bhp = (Fan RPM / 630)3
Outlet Velocity (FPM) = CFM / 7.54
Tip Speed (FPM) = Fan RPM x 8.64
670 lbs.
90% WOV
0
% WOV = (CFM x 100) / (Fan RPM x 12.9)
12
14
16
18
20
22
24
0
2
4
6
8
10
Volume (cfm x 1000)
Imperial data — Metric data
40
0
10
20
30
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
6
7
8
RPM
727
BHP
1.21
1.45
1.73
2.05
2.41
2.82
3.28
3.78
4.35
4.97
5.65
6.39
RPM
807
BHP
1.89
2.16
2.49
2.87
3.28
3.75
4.26
4.82
5.44
6.12
6.86
7.67
RPM
967
BHP
3.57
3.91
4.28
4.71
5.19
5.71
6.30
6.97
7.69
8.48
9.33
10.2
RPM
1119
1147
1175
1207
1243
1280
1325
1371
1417
1464
1515
1566
BHP
5.59
5.98
6.41
6.89
7.42
7.99
8.65
9.36
10.1
11.0
11.9
12.9
RPM
1265
1281
1303
1331
1359
1392
1428
1464
1506
1551
1597
1644
BHP
7.80
8.29
8.81
9.34
9.91
10.6
11.3
12.0
12.8
13.8
14.7
15.8
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
8300
9100
9900
1100
1206
1312
782
854
1002
1038
1082
1128
1174
1223
1275
1327
1380
1434
1488
1410
1427
1444
1472
1500
1529
1563
1599
1635
1676
1721
10.8
11.4
12.0
12.7
13.4
14.1
14.9
15.8
16.7
17.8
18.9
839
906
1543
1560
1576
1602
1630
1658
1688
1724
1760
1797
14.1
14.8
15.6
16.4
17.2
18.0
18.9
20.0
21.0
22.2
10700 1419
11500 1525
12300 1631
13100 1737
13900 1843
14700 1949
15500 2055
16300 2161
17100 2267
896
959
1667
1684
1700
1723
1752
1780
1809
1843
17.8
18.6
19.5
20.4
21.3
22.3
23.3
24.5
953
1012
1067
1123
1179
1236
1293
1351
1409
1783
1800
1816
1839
21.8
22.7
23.8
24.8
1011
1070
1130
1189
1249
1309
1370
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
550
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWi
A
RPM
550
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWo
73
A
81 72 67 64 68 62 50 43
79 71 64 62 62 58 50 44
76 68 62 61 62 59 51 45
74 68 63 61 62 59 51 45
73 80 75 72 71 77 58 53
65 73 71 68 68 62 56 49
67 70 70 65 67 62 56 50
68 71 69 65 67 62 56 51
78 90 84 83 81 83 78 65
74 89 80 79 78 73 67 61
74 84 76 75 77 72 67 62
78 83 77 74 76 71 67 63
83 86 95 91 89 86 89 75
78 80 91 87 85 80 76 70
80 80 87 83 82 79 75 71
83 83 86 83 81 78 75 72
85 90 97 97 96 92 94 84
82 83 91 92 92 87 84 77
89 86 90 89 89 85 82 78
89 89 91 89 88 84 81 78
71
67
66
66
79
72
71
70
88
82
80
80
95
89
87
86
101
96
93
92
83 74 70 71 68 64 55 45
82 72 67 70 66 62 56 45
79 69 65 68 65 62 56 45
79 70 65 67 65 62 56 45
79 81 78 79 74 75 62 55
76 76 75 77 72 67 61 53
75 73 72 74 71 66 61 52
77 75 71 73 70 66 61 53
85 92 88 89 84 84 78 67
81 84 84 86 82 77 69 62
83 82 81 83 79 75 68 63
84 84 81 82 79 74 68 64
90 91 96 96 92 89 90 77
85 86 91 94 89 85 79 72
89 88 88 91 87 82 77 72
91 90 90 90 86 82 77 73
96 95 100 101 99 94 94 86
71
70
70
81
77
75
75
91
87
84
84
98
95
92
91
750
1100
1500
1847
750
1100
1500
1847
103
100
97
91
90 98 98 96 91 86 79
97 94 94 95 93 88 83 79
97 96 96 95 92 88 83 79
97
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-30 Class I & QEI-L
6
5
4
3
2
1
0
Performance Data
RPM
BHP
50% WOV
20
15
14
12
10
8
60% WOV
QEI-L
QEI
1200
1360
Maximum
Fan RPM
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
10
70% WOV
Specification Data
Maximum
Motor
Frame Size
QEI-L
QEI
256T
284T
80% WOV
5
Minimum Motor
Starting hp
Wheel Diameter
1 hp
36.5 in.
QEI-L 630 lbs. 286 kg.
QEI 850 lbs. 386 kg.
.75 kW
6
927 mm
90% WOV
Approximate Weight
(Less Motor & Drives)
2
1
4
Maximum Bhp = (Fan RPM / 528)3
Outlet Velocity (FPM) = CFM / 9.31
Tip Speed (FPM) = Fan RPM x 9.56
% WOV = (CFM x 100) / (Fan RPM x 20.6)
Imperial data — Metric data
2
0
0
2
4
6
8
10 12 14 16 18 20 22 24 26 28 30
Volume (cfm x 1000)
0
10
20
30
40
50
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
1.5 2.5
CFM
OV
0.25
RPM
0.5
1
2
3
3.5
4
BHP
0.42
0.58
0.79
1.07
1.41
1.83
2.34
2.94
3.65
4.47
5.41
6.49
RPM
487
BHP
0.76
0.96
1.20
1.52
1.9
RPM
622
BHP
1.60
1.87
2.19
2.58
3.03
3.55
4.19
4.92
5.76
6.72
7.81
9.03
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6900
8400
9900
748
910
412
472
536
602
669
737
806
876
947
1018
1088
1160
536
654
761
791
2.93
3.32
3.77
4.31
4.92
5.61
6.39
7.31
8.35
9.51
10.8
858
882
4.10
4.58
5.10
5.70
6.39
7.17
8.04
8.99
10.1
11.3
12.7
1073
588
693
968
992
5.93
6.54
7.21
7.95
8.80
9.77
10.8
12.0
13.2
11400 1235
12900 1398
14400 1561
15900 1723
17400 1886
18900 2048
20400 2211
21900 2374
23400 2536
648
742
829
912
1069
1093
1128
1167
1209
1257
1306
1358
8.06
8.80
9.63
10.5
11.6
12.7
14.0
15.3
1140
1164
1190
1228
1266
1310
1358
9.65
10.5
11.4
12.4
13.4
14.7
16.0
710
793
874
950
1024
1062
1104
1152
1202
1254
1307
1230
1254
1285
1323
12.2
13.2
14.3
15.4
775
2.37
2.92
3.57
4.33
5.20
6.19
7.32
847
923
993
841
908
975
1042
1092
1145
1200
1260
1321
908
969
1028
1088
1150
1212
1275
975
1032
1097
1163
1230
1044
1113
1183
Inlet Sound Power, LWi [dB ref 10-12 watts]
% WOV
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
350
1
2
3
4
5
6
7
8
LWi
65
A
RPM
350
% WOV
1
2
3
4
5
6
7
8
LWo
68
A
100
80
70 70 63 60 61 57 49 36
66 67 61 58 57 57 50 38
66 66 61 58 57 57 51 40
67 67 61 58 57 57 51 40
74 73 70 66 66 67 54 44
71 71 68 64 62 61 54 43
70 70 65 62 61 60 54 44
74 71 65 62 61 60 54 43
87 84 77 74 73 76 62 55
84 81 74 72 70 67 61 53
81 78 72 69 68 65 60 53
81 79 73 68 67 64 60 53
78 86 85 83 79 79 79 62
75 84 82 79 77 73 68 61
77 83 78 76 74 71 67 63
79 82 81 76 73 70 66 63
83 91 93 93 89 87 88 75
80 89 90 90 86 83 79 72
84 91 89 86 84 81 77 73
87 91 89 86 83 80 76 73
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
70 69 66 66 62 59 53 42
69 68 64 64 60 60 55 43
69 68 63 63 59 60 55 43
68 67 63 63 59 60 54 43
78 74 72 72 68 67 56 46
76 71 69 70 66 65 56 46
75 71 68 68 66 64 56 46
74 71 67 67 65 64 56 46
87 83 79 80 75 76 64 55
87 81 76 78 73 69 63 54
85 80 75 76 72 68 62 53
85 80 75 75 72 67 61 53
86 89 86 88 84 81 79 63
82 85 83 85 80 76 70 61
84 86 82 82 77 73 68 62
87 87 83 81 77 72 67 63
89 92 95 97 93 90 89 78
63
63
63
72
68
67
66
80
75
73
73
86
82
79
79
96
92
89
89
66
66
66
74
72
71
70
82
79
77
77
89
85
83
83
99
95
93
93
60
50
100
80
60
50
100
80
60
50
500
700
500
700
100
80
60
50
100
80
950
950
100
80
87
90 91 94 90 87 82 72
1360
1360
60
50
60
50
92 91 89 91 87 85 81 72
94 93 91 92 87 84 80 71
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-30 Class II
10
9
8
7
6
5
4
3
2
1
0
Performance Data
RPM
BHP
30
20
15
60% WOV
25
% WOV
Maximum Fan RPM
1670
Density 0.075 lb/ft3
Density 1.2 kg/m3
Specification Data
70% WOV
20
15
10
5
Maximum Motor
Frame Size
324T
80% WOV
10
Minimum Motor
Starting hp
11⁄2 hp
36.5 in.
1.1 kW
7½
Wheel Diameter
927 mm
Approximate Weight
(Less Motor & Drives)
5
3
90% WOV
1000 lbs. 454 kg.
Maximum Bhp = (Fan RPM / 533)3
Outlet Velocity (FPM) = CFM / 9.31
Tip Speed (FPM) = Fan RPM x 9.56
% WOV = (CFM x 100) / (Fan RPM x 17.4)
Imperial data — Metric data
0
20
25
30
0
5
10
15
Volume (cfm x 1000)
40
50
0
10
20
30
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
6
7
8
RPM
650
BHP
1.43
1.76
2.15
2.60
3.11
3.70
4.37
5.11
5.94
6.87
7.90
9.03
RPM
723
BHP
2.26
2.63
3.09
3.61
4.20
4.86
5.60
6.43
7.34
8.35
9.46
10.7
RPM
870
BHP
4.31
4.77
5.28
5.88
6.56
7.31
8.18
9.15
10.2
11.4
12.6
14.0
RPM
1009
1036
1065
1098
1135
1176
1222
1269
1317
1367
1420
1473
BHP
6.76
7.30
7.89
8.56
9.31
10.1
11.1
12.1
13.2
14.5
15.9
17.4
RPM
1141
1158
1180
1209
1237
1273
1310
1349
1395
1442
1489
1537
BHP
9.50
10.1
10.8
11.6
12.4
13.3
14.3
15.4
16.6
18.0
19.4
20.9
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
10000 1084
11100 1203
12200 1323
13300 1442
14400 1561
15500 1681
16600 1800
17700 1919
18800 2039
19900 2158
21000 2277
22100 2396
706
771
905
1274
1291
1311
1339
1368
1399
1436
1473
1513
1559
1606
13.1
14.0
14.9
15.8
16.7
17.8
19.0
20.3
21.7
23.2
24.9
763
824
942
1397
1413
1431
1460
1489
1517
1553
1590
1627
17.3
18.3
19.4
20.5
21.6
22.8
24.2
25.7
27.2
821
877
987
1510
1527
1545
1573
1602
1631
1665
21.9
23.1
24.4
25.6
26.9
28.3
29.9
880
931
1034
1082
1133
1186
1240
1294
1349
1406
1617
1634
1652
27.0
28.4
29.8
939
988
999
1045
1103
1161
1219
1278
1338
1060
1121
1182
1243
1304
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
500
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWi
A
RPM
500
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWo
73
A
83 72 68 66 68 61 50 43
81 71 65 63 63 58 50 44
78 68 63 62 62 59 51 45
76 68 63 62 62 59 51 46
75 81 77 74 73 76 59 54
68 74 72 70 69 63 56 50
69 72 71 67 68 63 57 51
70 72 70 67 68 63 57 52
80 91 83 82 81 82 75 63
76 90 79 78 77 71 66 59
76 85 76 76 76 71 66 61
79 84 77 75 75 70 66 62
84 88 95 92 89 87 88 74
79 82 91 87 85 80 76 69
81 82 87 84 82 79 75 71
84 85 87 83 82 79 75 72
87 91 99 97 97 92 95 84
84 84 93 93 93 87 84 77
91 86 92 90 90 85 82 78
91 90 92 89 89 85 82 79
71
67
66
66
80
73
72
71
87
82
80
79
95
90
87
87
102
96
94
93
84 75 71 72 69 64 54 45
83 72 68 70 66 62 55 44
80 70 66 68 66 62 55 44
80 71 66 68 65 62 56 45
80 82 80 80 76 75 63 55
77 77 76 78 73 68 62 54
76 74 73 75 72 67 61 53
78 76 73 74 71 67 61 54
86 93 88 88 84 83 76 64
82 85 84 85 81 75 68 61
83 83 81 82 78 73 67 61
84 85 81 81 78 73 67 63
91 92 97 97 93 90 89 76
86 87 92 94 90 85 79 72
90 89 90 91 87 82 77 72
92 91 91 90 86 82 77 73
98 96 102 102 99 95 95 85
72
70
70
82
79
76
76
90
86
83
83
98
95
92
91
700
950
700
950
1350
1670
1350
1670
104
101
98
92
91 100 99 97 91 86 79
98 94 95 96 94 89 83 79
99 97 97 95 92 88 83 79
97
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
37
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-33 Class I & QEI-L
6
5
4
3
2
1
0
Performance Data
RPM
BHP
14
12
10
8
60% WOV
15
QEI-L
QEI
1000
1234
25
% WOV
Maximum
Fan RPM
20
Density 0.075 lb/ft3
Density 1.2 kg/m3
70% WOV
10
Specification Data
Maximum
Motor
Frame Size
QEI-L
QEI
256T
286T
80% WOV
Minimum Motor
Starting hp
Wheel Diameter
5
11⁄2 hp
1.1 kW
6
40.25 in.
QEI-L 730 lbs. 332 kg.
QEI 990 lbs. 449 kg.
1022 mm
90% WOV
Approximate Weight
(Less Motor & Drives)
4
2
1
Maximum Bhp = (Fan RPM / 450)3
Outlet Velocity (FPM) = CFM / 11.27
Tip Speed (FPM) = Fan RPM x 10.5
% WOV = (CFM x 100) / (Fan RPM x 26.7)
Imperial data — Metric data
2
0
0
4
8
12
20
16
20
24
28
32
Volume (cfm x 1000)
0
10
30
40
50
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
1.5 2.5
CFM
OV
0.25
RPM
0.5
1
2
3
3.5
4
BHP
0.52
0.72
0.99
1.35
1.79
2.32
2.97
3.74
4.64
5.69
6.89
8.25
RPM
444
489
539
595
653
714
775
837
900
965
1029
1094
BHP
0.93
1.17
1.48
1.88
2.37
2.96
3.67
4.50
5.46
6.56
7.83
9.25
RPM
562
BHP
1.93
2.27
2.67
3.13
3.69
4.37
5.17
6.08
7.16
8.38
9.75
11.3
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
8400
745
905
379
435
494
556
618
682
747
812
878
944
1010
1076
10200
593
687
717
3.52
4.02
4.60
5.22
5.97
6.83
7.83
8.99
10.3
11.8
13.4
12000 1064
13800 1224
15600 1384
17400 1543
19200 1703
21000 1863
22800 2023
24600 2182
26400 2342
28200 2502
631
795
827
5.48
6.17
6.93
7.74
8.67
9.75
10.9
12.4
13.9
15.6
675
753
893
927
7.81
8.71
9.66
10.7
11.8
13.1
14.5
16.2
966
988
9.68
10.6
11.6
12.8
14.0
15.3
16.9
723
793
862
1050
1077
1112
1149
1189
1231
12.6
13.7
15.0
16.3
17.8
19.3
1113
1129
1163
1198
14.7
15.8
17.2
18.7
776
840
902
963
1022
1058
1098
1140
1188
832
888
947
1003
1045
1093
1141
1192
889
940
994
948
996
1042
1097
1153
1209
1009
1070
1132
1053
1111
1171
Inlet Sound Power, LWi [dB ref 10-12 watts]
% WOV
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
300
1
2
3
4
5
6
7
8
LWi
64
A
RPM
300
% WOV
1
2
3
4
5
6
7
8
LWo
67
A
100
80
68 68 62 60 61 48 39 32
66 66 60 60 60 49 40 34
62 65 59 60 60 49 39 32
65 66 60 60 60 49 39 33
74 76 71 70 70 59 50 45
71 75 68 70 66 58 51 44
69 72 66 70 65 59 52 45
69 72 66 70 65 58 52 44
83 81 78 74 73 74 59 54
79 80 75 72 72 66 60 53
78 79 73 70 71 66 60 54
78 79 73 70 71 66 60 54
84 93 88 83 79 84 70 62
82 92 85 80 78 74 67 61
81 90 80 76 75 73 68 63
81 88 80 75 75 73 68 63
88 98 95 94 90 88 90 75
86 96 93 91 88 84 78 72
86 95 88 87 84 82 77 73
86 95 88 87 84 82 77 73
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
71 67 64 64 64 52 45 38
68 68 63 63 63 52 45 38
67 68 62 63 63 52 46 39
68 69 62 63 64 53 46 40
80 76 73 72 71 62 54 46
77 76 70 71 68 61 54 46
77 76 68 70 67 60 54 46
78 76 69 70 68 60 54 46
88 82 79 80 76 74 61 54
86 82 77 78 75 68 61 53
85 82 75 75 73 67 61 53
84 82 75 75 73 67 61 54
85 90 87 88 83 83 74 65
84 90 84 85 80 76 70 62
84 88 82 83 78 75 69 64
86 89 82 82 78 75 69 64
91 95 97 99 94 91 91 78
62
62
62
73
70
70
70
79
76
75
75
88
84
81
81
97
93
90
90
66
66
66
74
72
71
72
81
79
78
77
90
86
84
84
60
50
100
80
60
50
100
80
60
50
450
600
450
600
100
80
60
50
100
80
850
850
100
80
100
97
94
89
95 94 96 91 87 82 74
1234
1234
60
50
60
50
92 93 92 93 88 85 80 74
94 94 92 93 88 85 80 75
94
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-33 Class II
10
9
8
7
6
5
4
3
2
1
0
Performance Data
RPM
BHP
50% WOV
60% WOV
40
30
25
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
Maximum Fan RPM
1522
20
15
Specification Data
20
15
10
5
70% WOV
Maximum Motor
Frame Size
324T
1.5 kW
80% WOV
Minimum Motor
Starting hp
2 hp
10
Wheel Diameter
40.25 in. 1022 mm
1200 lbs. 544 kg.
Approximate Weight
(Less Motor & Drives)
5
3
90% WOV
Maximum Bhp = (Fan RPM / 450)3
Outlet Velocity (FPM) = CFM / 11.27
Tip Speed (FPM) = Fan RPM x 10.5
% WOV = (CFM x 100) / (Fan RPM x 23.5)
Imperial data — Metric data
0
16
Volume (cfm x 1000)
20
24
36
0
4
8
12
20
28
32
50
60
0
10
30
40
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
6
7
8
RPM
599
BHP
1.76
2.17
2.64
3.20
3.84
4.57
5.40
6.34
7.38
8.55
9.85
11.3
RPM
668
BHP
2.84
3.32
3.87
4.50
5.22
6.03
6.95
7.98
9.12
10.4
11.8
13.3
RPM
797
BHP
5.47
6.06
6.71
7.47
8.30
9.26
10.3
11.5
12.8
14.2
15.8
17.5
RPM
923
BHP
8.58
9.29
10.0
10.9
11.9
12.9
14.1
15.4
16.8
18.4
20.1
21.9
RPM
1043
1059
1080
1107
1136
1174
1212
1253
1296
1340
1384
1432
BHP
11.9
12.8
13.8
14.8
15.8
17.0
18.3
19.7
21.2
22.9
24.7
26.7
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
12500 1109
13900 1233
15300 1357
16700 1481
18100 1606
19500 1730
20900 1854
22300 1978
23700 2102
25100 2227
26500 2351
27900 2475
652
714
833
948
1165
1181
1200
1227
1254
1288
1326
1365
1407
1450
1493
16.6
17.8
18.9
20.1
21.4
22.8
24.3
25.9
27.7
29.7
31.7
707
762
872
975
1277
1293
1311
1338
1365
1395
1433
1471
1510
21.9
23.3
24.7
26.1
27.6
29.2
31.0
32.9
34.9
762
812
915
1011
1050
1092
1134
1178
1224
1272
1320
1370
1381
1398
1415
1442
1469
1496
27.8
29.4
31.1
32.7
34.4
36.2
818
862
958
1480
1496
1514
34.3
36.1
38.0
874
916
1004
1053
1101
1151
1201
1254
1308
931
971
988
1026
1081
1137
1193
1249
1046
1103
1161
1219
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
450
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWi
A
RPM
450
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWo
76
A
83 74 69 67 71 61 50 44
80 72 66 66 67 58 48 40
78 70 63 64 66 57 48 40
75 69 62 64 66 56 48 40
83 83 77 75 74 78 59 53
79 80 73 72 73 65 56 49
76 77 70 70 72 64 56 49
76 77 70 69 72 63 55 49
79 93 84 85 81 87 73 65
75 90 82 82 79 75 67 60
74 87 77 79 77 74 67 61
79 88 78 77 76 72 65 61
85 92 97 94 90 89 92 76
79 89 94 91 87 83 79 70
81 86 91 87 85 81 77 70
83 87 89 86 84 81 76 71
90 94 101 100 96 94 98 86
85 89 97 98 94 90 87 79
87 88 93 94 90 87 84 78
90 91 93 93 90 87 83 79
73
69
69
68
81
76
75
74
90
84
82
81
98
93
90
89
104
99
96
95
87 77 73 73 74 64 54 47
85 77 71 72 72 61 52 45
84 76 69 70 72 60 52 45
83 77 68 68 72 59 52 45
82 82 79 80 76 76 62 54
82 82 77 79 75 68 60 51
82 81 75 76 75 67 59 52
82 83 74 75 74 65 58 52
85 89 88 90 83 86 75 66
82 87 85 88 81 77 70 61
82 85 82 84 79 75 68 62
85 87 82 83 79 74 67 62
89 92 95 99 93 90 92 78
87 89 93 97 91 87 82 73
88 89 90 94 88 84 79 72
91 92 92 93 87 83 78 73
94 96 102 104 99 96 98 87
75
74
74
82
80
78
77
91
88
85
84
600
850
600
850
100
97
94
1200
1522
1200
1522
93
106
103
100
100
92
93 98 102 97 93 89 81
94 95 95 99 94 90 86 79
96 97 98 99 94 90 85 80
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
39
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-36 Class I & QEI-L
6
5
4
3
2
1
0
Performance Data
RPM
BHP
30
25
20
14
12
10
8
QEI-L
QEI
920
1116
Maximum
Fan RPM
% WOV
60% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
15
70% WOV
Specification Data
Maximum
Motor
Frame Size
QEI-L
QEI
256T
286T
10
80% WOV
Minimum Motor
Starting hp
Wheel Diameter
11⁄2 hp
1.1 kW
5
6
44.5 in.
1130 mm
90% WOV
3
QEI-L 900 lbs. 409 kg.
QEI 1200 lbs. 544 kg.
Approximate Weight
(Less Motor & Drives)
4
1½
Maximum Bhp = (Fan RPM / 380)3
Outlet Velocity (FPM) = CFM / 13.79
Tip Speed (FPM) = Fan RPM x 11.7
% WOV = (CFM x 100) / (Fan RPM x 36.1)
Imperial data — Metric data
2
0
0
5
10
15
20
25
30
35
40
Volume (cfm x 1000)
0
10
20
30
40
50
60
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
1.5 2.5
CFM
OV
0.25
RPM
0.5
1
2
3
3.5
4
BHP
0.63
0.88
1.22
1.65
2.19
2.85
3.64
4.59
5.69
6.97
8.44
10.1
RPM
402
443
488
539
592
646
702
758
815
873
932
991
BHP
1.14
1.44
1.82
2.31
2.90
3.63
4.50
5.51
6.69
8.05
9.59
11.3
RPM
508
537
571
611
654
702
753
805
859
913
969
1024
BHP
2.36
2.79
3.27
3.83
4.52
5.35
6.33
7.45
8.76
10.3
12.0
13.8
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
10300
12500
746
906
343
394
448
503
560
618
677
736
795
854
914
974
622
649
681
718
760
803
851
902
953
1005
1060
4.31
4.93
5.63
6.39
7.31
8.36
9.59
11.0
12.6
14.4
16.4
14700 1065
16900 1225
19100 1385
21300 1544
23500 1704
25700 1863
27900 2023
30100 2182
32300 2342
34500 2501
720
748
780
817
857
899
943
993
1043
1094
6.71
7.55
8.49
9.48
10.6
11.9
13.4
15.1
17.0
19.1
808
839
9.57
10.7
11.8
13.1
14.4
16.0
17.8
19.8
874
894
11.8
12.9
14.3
15.7
17.1
18.8
20.7
950
975
15.4
16.7
18.3
20.0
21.7
23.6
1007
1022
1052
1084
18.0
19.3
21.0
22.9
872
925
908
958
1006
1040
1076
1114
946
994
989
1032
1075
1033
1079
Inlet Sound Power, LWi [dB ref 10-12 watts]
% WOV
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
275
1
2
3
4
5
6
7
8
LWi
64
A
RPM
275
% WOV
1
2
3
4
5
6
7
8
LWo
67
A
100
80
70 68 63 62 61 48 39 32
68 67 61 61 59 49 40 34
64 65 60 61 60 49 39 32
66 66 61 61 59 49 39 33
75 76 71 70 69 58 49 45
72 74 69 70 65 57 50 43
70 72 67 70 65 58 51 44
70 71 67 69 65 58 51 43
85 82 79 75 75 73 60 54
81 80 76 73 72 66 60 53
80 80 74 72 72 66 61 54
80 80 74 72 72 66 61 55
87 95 89 84 81 84 71 63
85 93 86 81 79 75 68 62
84 91 82 77 77 74 69 64
84 89 81 77 77 74 69 64
91 100 96 94 91 89 89 74
89 98 94 91 88 84 78 72
88 96 89 87 84 82 78 73
88 96 89 87 84 82 78 73
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
72 68 65 65 64 53 45 38
69 69 64 65 63 53 45 38
69 69 63 64 63 53 46 40
69 69 63 64 64 53 47 40
80 76 73 72 70 61 53 45
78 75 71 71 67 60 53 45
77 75 69 70 67 60 53 46
78 75 70 70 67 59 53 45
90 83 80 80 77 74 62 54
88 82 78 79 75 68 61 53
86 82 76 76 74 68 61 53
86 82 76 76 74 67 61 54
88 91 89 90 85 84 75 66
86 91 86 87 82 77 71 64
86 89 84 84 80 76 71 65
88 90 84 83 80 76 71 65
92 97 98 99 95 92 90 77
63
63
63
72
70
70
70
79
76
76
75
89
85
82
82
97
93
90
90
66
66
66
74
72
71
71
82
80
78
78
91
87
85
85
60
50
100
80
60
50
100
80
60
50
400
550
400
550
100
80
60
50
100
80
800
800
100
80
100
97
94
91
96 95 97 92 87 82 74
1116
1116
60
50
60
50
93 94 93 93 89 85 80 74
95 95 93 93 89 85 80 75
94
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
40
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-36 Class II
10
9
8
7
6
5
4
3
2
1
0
Performance Data
RPM
BHP
50
50% WOV
60% WOV
40
30
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
Maximum Fan RPM
1377
Specification Data
20
15
10
5
70% WOV
20
15
Maximum Motor
Frame Size
326T
2.2 kW
80% WOV
Minimum Motor
Starting hp
3 hp
10
5
Wheel Diameter
44.5 in. 1130 mm
1400 lbs. 635 kg.
Approximate Weight
(Less Motor & Drives)
90% WOV
Maximum Bhp = (Fan RPM / 381)3
Outlet Velocity (FPM) = CFM / 13.79
Tip Speed (FPM) = Fan RPM x 11.7
% WOV = (CFM x 100) / (Fan RPM x 31.7)
Imperial data — Metric data
0
20
25
30
40
45
0
5
10
15
35
60
Volume (cfm x 1000)
0
20
40
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
6
7
8
RPM
534
579
625
671
718
766
814
862
910
959
1008
1057
BHP
2.08
2.53
3.05
3.66
4.35
5.14
6.02
7.02
8.13
9.37
10.7
12.2
RPM
598
636
677
718
760
805
851
897
943
990
1038
1085
BHP
3.39
3.91
4.52
5.21
5.99
6.87
7.86
8.96
10.2
11.5
13.0
14.6
RPM
716
BHP
6.58
7.23
7.96
8.78
9.71
10.7
11.9
13.8
14.6
16.1
17.7
19.5
RPM
832
BHP
10.3
11.2
12.0
13.0
14.0
15.1
16.4
17.8
19.3
21.0
22.9
24.8
RPM
941
BHP
14.4
15.4
16.5
17.6
18.8
20.1
21.5
22.9
24.6
26.4
28.4
30.4
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
15000 1088
16600 1204
18200 1320
19800 1436
21400 1552
23000 1669
24600 1785
26200 1901
27800 2017
29400 2133
31000 2249
32600 2365
745
852
955
1050
1064
1078
1099
1122
1146
1178
1210
1243
1280
1316
20.0
21.3
22.6
24.0
25.4
26.9
28.5
30.3
32.2
34.3
36.5
778
875
970
1151
1165
1178
1198
1221
1244
1272
1305
1337
1371
26.3
27.8
29.4
31.0
32.7
34.5
36.4
38.4
40.6
42.9
814
902
993
1244
1258
1272
1291
1314
1337
1362
33.3
35.1
37.0
38.8
40.8
42.8
44.9
850
935
1016
1045
1077
1110
1146
1182
1219
1257
1332
1346
1360
41.0
43.0
45.2
888
968
928
1005
1041
1078
1118
1159
1200
969
1010
1052
1095
1140
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
400
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWi
A
RPM
400
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWo
76
74
73
73
83
80
79
78
92
89
86
86
100
98
94
A
84 73 69 69 70 60 50 43
81 71 67 66 66 57 47 39
78 69 64 65 65 56 47 39
76 68 63 65 65 55 47 40
85 84 78 76 76 77 60 54
82 80 74 73 73 65 57 49
78 77 71 71 72 64 56 50
79 78 71 71 72 63 55 50
82 94 86 86 83 87 74 66
79 92 84 84 80 76 68 61
78 89 79 80 78 75 68 62
82 90 80 79 78 73 67 62
87 94 98 95 91 91 91 75
82 91 95 92 88 84 79 71
83 88 91 88 85 82 77 71
85 88 90 87 84 81 77 72
92 95 103 101 97 94 100 84
87 90 98 98 94 90 88 79
89 89 94 95 91 88 84 78
92 91 94 94 90 87 84 79
73
69
68
67
81
76
75
74
91
86
83
82
98
94
91
90
105
100
96
96
87 76 73 74 73 62 53 47
85 77 72 72 71 60 52 44
84 76 69 71 71 59 51 44
84 76 68 70 70 58 51 45
84 83 80 81 77 76 62 55
84 83 78 80 75 68 60 52
83 82 76 77 75 67 59 52
84 83 75 76 74 66 59 53
87 91 90 91 85 86 76 67
84 89 87 89 83 78 71 62
84 86 84 86 81 76 69 63
87 89 84 85 80 75 68 63
91 94 97 99 94 92 92 77
88 91 94 98 91 87 82 73
90 90 91 94 89 85 79 73
93 93 93 94 88 84 78 73
96 97 103 105 99 96 100 86
550
800
550
800
1100
1377
1100
1377
94
107
104
100
100
93
93 100 104 97 93 89 80
96 96 97 100 94 91 86 79
98 98 99 100 94 90 85 80
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
41
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-40 Class I
6
5
4
3
2
1
0
Performance Data
Maximum Fan RPM
Specification Data
RPM
BHP
40
30
25
14
12
10
8
60% WOV
% WOV
1013
324T
Density 0.075 lb/ft3
Density 1.2 kg/m3
70% WOV
15
10
Maximum Motor
Frame Size
80% WOV
Minimum Motor
5 hp
3.7 kW
1245 mm
Starting hp
Wheel Diameter
49 in.
6
Approximate Weight
(Less Motor & Drives)
5
2
1500 lbs. 680 kg.
90% WOV
4
Maximum Bhp = (Fan RPM / 324)3
Outlet Velocity (FPM) = CFM / 16.77
Tip Speed (FPM) = Fan RPM x 12.8
% WOV = (CFM x 100) / (Fan RPM x 48.1)
Imperial data — Metric data
2
0
0
5
10
15
20
25
30
35
40
45
50
Volume (cfm x 1000)
0
10
20
30
40
50
60
70
80
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
1.5 2.5
CFM
OV
0.25
RPM
0.5
1
2
3
3.5
4
BHP
0.77
1.08
1.49
2.03
2.70
3.51
4.50
5.67
7.05
8.64
10.5
12.6
RPM
365
403
445
491
540
590
641
693
746
799
853
907
BHP
1.39
1.75
2.22
2.82
3.56
4.47
5.54
6.81
8.27
9.96
11.9
14.1
RPM
462
488
520
557
596
641
687
735
785
835
886
937
BHP
2.86
3.39
3.98
4.68
5.53
6.56
7.77
9.17
10.8
12.7
14.8
17.1
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
12500
15200
745
906
312
359
408
459
511
565
619
673
727
782
837
892
565
590
620
654
693
733
777
824
871
919
969
5.23
6.00
6.86
7.81
8.94
10.2
11.8
13.5
15.5
17.7
20.3
17900 1067
20600 1228
23300 1389
26000 1550
28700 1711
31400 1872
34100 2033
36800 2194
39500 2355
42200 2516
654
681
710
744
781
820
861
907
953
1000
8.16
9.20
10.4
11.6
13.0
14.6
16.4
18.6
21.0
23.6
735
764
794
827
864
903
942
986
11.7
13.0
14.4
16.0
17.7
19.7
21.8
24.3
795
813
842
872
906
941
981
14.4
15.7
17.4
19.1
21.0
23.0
25.3
863
887
916
947
981
18.7
20.4
22.4
24.4
26.6
915
930
958
986
21.9
23.5
25.7
28.0
Inlet Sound Power, LWi [dB ref 10-12 watts]
% WOV
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
250
1
2
3
4
5
6
7
8
LWi
64
A
RPM
250
% WOV
1
2
3
4
5
6
7
8
LWo
67
A
100
80
71 68 64 63 60 48 39 32
69 67 62 62 59 49 40 34
65 66 61 62 59 48 39 32
68 66 62 62 59 48 39 33
76 75 71 70 66 56 49 44
73 73 69 69 63 56 49 42
71 71 68 69 64 57 50 42
71 70 68 69 63 57 50 42
86 82 79 76 76 72 60 54
82 81 76 74 72 66 60 53
81 80 75 73 72 66 61 54
81 80 74 73 72 66 61 55
90 94 88 84 82 82 69 62
88 92 85 81 78 74 67 61
86 89 81 77 76 73 68 63
86 88 80 77 76 73 68 63
94 101 96 94 91 90 87 72
91 99 94 92 88 84 78 72
90 97 90 88 85 82 78 73
90 97 90 88 85 82 78 73
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
72 69 66 66 63 52 45 38
70 69 65 65 62 53 45 38
70 69 64 65 63 53 46 40
70 69 64 65 63 53 46 40
79 76 73 72 68 60 51 44
77 74 71 70 66 59 51 44
77 74 69 69 65 59 52 44
78 74 70 70 65 58 51 44
90 83 81 81 77 73 61 54
88 82 79 79 75 68 61 53
87 82 77 77 74 68 61 53
86 82 77 76 73 67 61 54
89 91 89 89 85 82 73 65
88 90 86 86 81 76 69 62
87 88 84 83 79 75 69 64
88 89 84 83 79 75 70 64
94 98 99 99 95 93 89 76
63
63
63
71
69
69
69
80
77
76
76
88
84
82
81
97
94
91
91
66
66
67
73
71
70
71
82
80
78
78
90
87
85
84
101
97
94
95
60
50
100
80
60
50
100
80
60
50
350
500
350
500
100
80
60
50
100
80
700
700
100
80
92
97 96 97 92 87 81 73
1013
1013
60
50
60
50
94 95 94 93 89 85 80 74
95 96 94 93 89 85 80 75
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
42
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-40 Class II
10
9
8
7
6
5
4
3
2
1
0
Performance Data
RPM
BHP
60
50
40
50% WOV
60% WOV
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
Maximum Fan RPM
1251
30
20
Specification Data
20
15
10
5
70% WOV
Maximum Motor
Frame Size
364T
5.5 kW
1245 mm
80% WOV
Minimum Motor
Starting hp
71⁄2 hp
Wheel Diameter
49 in.
10
5
Approximate Weight
(Less Motor & Drives)
1900 lbs. 862 kg.
90% WOV
Maximum Bhp = (Fan RPM / 324)3
Outlet Velocity (FPM) = CFM / 16.77
Tip Speed (FPM) = Fan RPM x 12.8
% WOV = (CFM x 100) / (Fan RPM x 42.4)
Imperial data — Metric data
0
25
30
35
40
45
55
0
5
10
15
20
50
Volume (cfm x 1000)
80
0
20
40
60
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
6
7
8
RPM
481
523
566
609
653
698
743
788
833
879
925
971
BHP
2.48
3.03
3.68
4.43
5.30
6.29
7.41
8.67
10.1
11.7
13.4
15.3
RPM
540
575
613
652
691
733
776
820
863
907
951
996
BHP
4.06
4.70
5.45
6.31
7.29
8.40
9.65
11.0
12.6
14.3
16.2
18.2
RPM
649
675
705
739
773
808
846
884
923
963
1003
1046
BHP
7.91
8.71
9.61
10.7
11.8
13.1
14.6
16.2
17.9
19.8
21.9
24.2
RPM
754
BHP
12.4
13.5
14.5
15.7
17.0
18.4
20.1
21.8
23.7
25.9
28.2
30.7
RPM
853
BHP
17.3
18.6
20.0
21.3
22.8
24.4
26.2
28.1
30.2
32.5
34.9
37.6
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
18000 1077
20000 1197
22000 1317
24000 1437
26000 1556
28000 1676
30000 1796
32000 1916
34000 2035
36000 2155
38000 2275
40000 2395
772
866
953
966
24.1
25.7
27.4
29.1
30.9
32.7
34.9
37.1
39.5
42.2
45.0
794
880
1045
1058
1071
1089
1111
1132
1160
1190
1221
31.8
33.7
35.7
37.8
39.8
42.0
44.5
47.1
49.8
819
902
979
1130
1143
1156
1174
1195
1217
1242
40.4
42.6
44.9
47.3
49.7
52.2
55.0
849
923
999
1210
1223
1236
49.8
52.3
55.0
881
950
1021
1043
1073
1104
1135
1169
1203
915
981
949
1011
1046
1080
1114
1150
984
1022
1060
1099
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
350
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWi
A
RPM
350
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWo
75
A
82 73 69 69 68 58 49 42
79 70 67 67 64 55 46 38
77 68 64 66 63 54 46 38
75 67 63 65 63 54 46 38
87 84 78 77 77 75 60 54
83 80 75 74 73 65 56 49
80 77 72 73 72 64 56 50
81 77 72 72 72 63 55 50
85 93 86 85 84 85 73 64
82 90 84 83 80 75 67 60
80 87 80 80 78 74 67 61
84 88 80 79 77 72 66 62
89 96 98 95 92 92 90 74
85 93 95 92 88 84 79 70
85 90 92 89 86 82 77 71
87 89 90 88 85 81 77 72
93 97 104 101 97 96 99 83
89 92 99 99 94 90 87 78
90 91 95 95 91 88 84 78
93 93 95 94 90 88 84 79
72
68
67
66
81
76
75
75
90
85
82
82
99
94
91
90
105
100
97
96
85 76 73 74 71 61 52 46
83 75 72 72 68 58 50 42
83 74 70 71 68 57 50 43
82 74 68 70 68 57 50 43
85 84 81 81 78 75 62 54
85 83 80 80 75 68 60 51
85 82 77 78 75 67 59 52
85 82 76 77 74 66 59 53
88 91 90 90 86 84 74 65
85 89 87 88 82 77 69 61
85 86 84 85 80 75 68 62
87 88 84 84 79 74 67 62
92 95 98 99 94 93 91 76
89 92 96 98 92 88 81 73
91 91 93 94 89 85 79 73
94 93 94 94 88 84 78 74
97 99 104 105 100 97 99 85
73
72
72
83
81
79
78
92
88
85
85
500
700
500
700
101
98
95
1000
1251
1000
1251
94
107
104
101
100
94
95 101 104 97 94 89 80
97 97 98 100 94 91 86 79
99 99 100 100 94 90 85 80
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
43
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-44 Class I
6
5
4
3
2
1
0
Performance Data
Maximum Fan RPM
Specification Data
RPM
BHP
40
14
12
10
8
30
60% WOV
% WOV
915
Density 0.075 lb/ft3
Density 1.2 kg/m3
20
70% WOV
Maximum Motor
Frame Size
326T
80% WOV
Minimum Motor
71⁄2 hp
5.5 kW
Starting hp
10
Wheel Diameter
54.25 in. 1378 mm
2000 lbs. 907 kg.
6
Approximate Weight
(Less Motor & Drives)
90% WOV
5
2
4
Maximum Bhp = (Fan RPM / 273)3
Outlet Velocity (FPM) = CFM / 20.49
Tip Speed (FPM) = Fan RPM x 14.2
% WOV = (CFM x 100) / (Fan RPM x 65.3)
Imperial data — Metric data
2
0
0
5
10
15
20
25
30
35
40
45
50
55
60
Volume (cfm x 1000)
0
10
20
30
40
50
60
70
80
90
100
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
1.5 2.5
CFM
OV
0.25
RPM
0.5
1
2
3
3.5
4
BHP
0.93
1.30
1.81
2.45
3.26
4.25
5.44
6.86
8.53
10.5
12.7
15.2
RPM
329
362
400
442
485
531
577
623
670
719
767
816
BHP
1.69
2.12
2.69
3.42
4.32
5.42
6.72
8.25
10.0
12.1
14.4
17.0
RPM
417
440
468
501
537
577
619
661
706
751
797
843
BHP
3.49
4.12
4.84
5.70
6.72
7.97
9.44
11.1
13.1
15.4
17.9
20.8
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
15200
18500
741
902
280
322
367
413
459
507
556
605
654
703
753
802
510
532
559
589
624
660
700
741
784
827
872
6.39
7.31
8.36
9.51
10.9
12.5
14.3
16.5
18.9
21.6
24.6
21800 1063
25100 1224
28400 1386
31700 1547
35000 1708
38300 1869
41600 2030
44900 2191
48200 2352
51500 2513
590
613
640
670
704
739
775
816
858
901
9.96
11.2
12.6
14.1
15.8
17.8
20.0
22.6
25.5
28.7
663
689
715
745
777
813
849
888
14.2
15.9
17.6
19.5
21.5
23.9
26.6
29.6
717
733
759
786
816
847
883
17.6
19.2
21.2
23.3
25.6
28.0
30.9
779
800
826
853
884
22.8
24.9
27.3
29.8
32.4
826
838
864
889
26.8
28.7
31.3
34.1
Inlet Sound Power, LWi [dB ref 10-12 watts]
% WOV
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
225
1
2
3
4
5
6
7
8
LWi
64
A
RPM
225
% WOV
1
2
3
4
5
6
7
8
LWo
67
A
100
80
71 68 64 64 59 47 39 32
70 67 63 63 58 48 40 34
66 65 62 63 58 48 39 32
68 66 63 63 58 47 39 33
77 76 72 72 67 56 50 45
75 74 71 70 64 57 49 42
73 72 70 70 64 58 51 43
73 71 70 70 64 57 50 42
86 83 79 77 76 71 60 54
83 81 77 75 72 66 60 53
82 80 75 74 72 66 60 54
82 79 75 74 72 66 61 54
92 95 89 85 84 82 70 63
91 93 86 82 79 74 68 62
89 90 82 79 78 74 69 64
88 88 81 79 78 74 69 64
96 101 97 95 92 91 86 71
94 99 95 92 88 84 78 71
93 96 90 88 86 82 78 74
93 96 90 88 86 82 78 74
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
72 69 67 67 62 52 45 38
71 69 66 66 62 52 45 38
71 68 65 66 62 53 46 39
71 69 65 66 62 53 46 40
80 77 74 74 69 60 52 45
79 75 73 71 66 59 52 44
78 74 71 71 66 59 52 45
79 75 71 71 66 59 52 45
90 84 82 81 78 72 61 53
88 83 80 80 75 68 60 52
87 82 78 77 74 68 61 53
87 82 77 77 73 67 61 54
91 92 91 90 86 83 74 65
90 91 88 87 82 77 70 63
89 89 86 84 80 76 70 65
90 90 85 84 80 76 71 65
95 99 100 100 95 93 88 75
63
63
63
72
70
70
70
80
77
76
76
89
85
83
82
98
94
91
91
67
66
67
74
72
71
72
82
80
79
78
91
88
86
86
60
50
100
80
60
50
100
80
60
50
325
450
650
915
325
450
650
915
100
80
60
50
100
80
100
80
101
98
95
94
98 97 97 92 88 81 73
60
50
60
50
95 96 95 93 89 85 80 74
96 97 95 93 89 85 80 75
95
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
44
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-44 Class II
10
9
8
7
6
5
4
3
2
1
0
Performance Data
RPM
BHP
75
60
40
30
% WOV
Maximum Fan RPM
1129
Density 0.075 lb/ft3
Density 1.2 kg/m3
60% WOV
Specification Data
20
15
10
5
70% WOV
Maximum Motor
Frame Size
365T
7.5 kW
80% WOV
Minimum Motor
Starting hp
20
10 hp
Wheel Diameter
54.25 in. 1378 mm
2300 lbs. 1043 kg.
Approximate Weight
(Less Motor & Drives)
10
5
90% WOV
Maximum Bhp = (Fan RPM / 274)3
Outlet Velocity (FPM) = CFM / 20.49
Tip Speed (FPM) = Fan RPM x 14.2
% WOV = (CFM x 100) / (Fan RPM x 57.5)
Imperial data — Metric data
0
30
40
45
55
60
65
0
5
10
15
20
25
35
50
Volume (cfm x 1000)
100
0
20
40
60
80
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
6
7
8
RPM
434
472
512
552
592
633
675
716
758
800
842
885
BHP
3.02
3.71
4.52
5.46
6.55
7.80
9.21
10.8
12.6
14.6
16.8
19.2
RPM
487
519
554
590
626
665
705
745
785
825
866
907
BHP
4.95
5.75
6.70
7.78
9.00
10.4
12.0
13.7
15.7
17.8
20.2
22.8
RPM
585
609
637
668
700
732
767
803
839
875
913
952
BHP
9.67
10.7
11.8
13.1
14.5
16.2
18.0
20.0
22.3
24.7
27.4
30.3
RPM
681
698
717
741
769
798
829
861
894
928
963
999
BHP
15.2
16.5
17.8
19.3
20.9
22.8
24.8
27.0
29.4
32.2
35.1
38.3
RPM
770
782
795
815
835
860
888
917
949
980
1012
1046
BHP
21.2
22.8
24.5
26.2
28.0
30.1
32.3
34.7
37.4
40.2
43.3
46.7
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
22000 1074
24500 1196
27000 1319
29500 1441
32000 1563
34500 1685
37000 1807
39500 1929
42000 2051
44500 2173
47000 2296
49500 2418
861
873
29.6
31.6
33.7
35.8
38.0
40.4
43.0
45.8
48.9
52.3
55.8
944
956
39.0
41.4
44.0
46.5
49.1
51.8
54.9
58.2
61.7
885
1021
1033
1045
1062
1082
1102
1126
49.6
52.4
55.3
58.2
61.3
64.4
67.9
903
968
1094
1106
1118
61.1
64.4
67.7
923
985
945
1005
1025
1051
1079
1107
972
1000
1029
1061
1093
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
325
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWi
A
RPM
325
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWo
76
A
82 74 70 71 69 58 49 43
79 71 68 68 64 55 46 38
77 69 66 67 64 55 46 38
75 68 65 67 63 54 46 39
89 83 79 78 78 73 60 53
85 80 75 75 72 64 56 49
82 77 73 74 72 64 56 50
82 77 72 73 71 62 55 50
88 93 88 86 86 85 73 65
85 91 85 84 81 75 68 61
83 87 81 81 79 74 68 62
86 88 81 80 78 73 67 63
91 98 99 95 92 94 88 72
87 95 96 92 88 84 78 70
86 91 92 89 86 82 77 71
88 90 91 88 85 82 77 72
95 99 104 102 98 97 97 82
90 95 100 99 95 91 87 78
91 92 96 95 92 88 84 78
94 94 96 95 91 88 84 80
73
69
68
67
82
77
75
75
91
86
83
83
99
94
91
91
105
100
97
97
85 77 75 75 71 61 53 46
84 76 73 74 69 59 51 43
83 75 71 73 68 58 51 44
83 75 70 72 68 58 51 44
87 84 82 81 79 73 62 54
86 83 81 80 75 67 59 51
86 81 78 79 74 66 59 52
86 82 77 77 73 65 59 52
90 92 92 91 87 85 75 66
87 90 89 89 83 78 70 61
86 87 86 86 81 76 69 62
89 89 86 85 80 74 68 63
93 96 100 99 95 94 89 75
90 93 98 97 92 88 81 72
92 91 94 94 89 85 79 73
94 93 95 94 89 84 79 74
98 101 105 105 100 99 98 84
74
73
73
83
81
79
78
93
89
86
86
450
650
450
650
101
98
95
900
900
95
107
104
101
101
95
97 103 104 98 94 88 80
1129
1129
98 98 99 100 95 91 86 79
99 100 101 100 94 90 85 80
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
45
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-49 Class I
6
5
4
3
2
1
0
Performance Data
Maximum Fan RPM
Specification Data
RPM
BHP
14
12
10
8
50
40
% WOV
828
60% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
25
15
70% WOV
Maximum Motor
Frame Size
364T
80% WOV
Minimum Motor
10 hp
7.5 kW
1524 mm
2400 lbs. 1089 kg.
Starting hp
Wheel Diameter
60 in.
6
Approximate Weight
(Less Motor & Drives)
7½
3
90% WOV
4
Maximum Bhp = (Fan RPM / 231)3
Outlet Velocity (FPM) = CFM / 24.85
Tip Speed (FPM) = Fan RPM x 15.7
% WOV = (CFM x 100) / (Fan RPM x 88.4)
Imperial data — Metric data
2
0
0
10
20
30
40
50
60
70
80
Volume (cfm x 1000)
0
20
40
60
80
100
120
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
1.5 2.5
CFM
OV
0.25
RPM
0.5
1
2
3
3.5
4
BHP
1.08
1.52
2.10
2.85
3.79
4.95
6.34
8.01
9.96
12.2
14.8
17.8
RPM
293
323
356
393
432
472
513
554
597
640
683
727
BHP
2.00
2.51
3.16
4.02
5.06
6.35
7.88
9.67
11.8
14.2
16.9
20.0
RPM
375
394
418
448
479
514
552
590
630
670
711
752
BHP
4.18
4.91
5.77
6.77
7.98
9.43
11.2
13.2
15.5
18.1
21.1
24.5
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
18000
22000
724
885
248
285
325
366
407
450
494
538
582
626
670
714
459
477
500
527
558
590
625
662
700
739
779
7.67
8.73
10.0
11.4
13.0
14.8
17.0
19.5
22.4
25.5
29.2
26000 1046
30000 1207
34000 1368
38000 1529
42000 1690
46000 1851
50000 2012
54000 2173
58000 2334
62000 2494
532
551
574
601
629
661
694
730
767
805
12.0
13.4
15.1
16.9
18.9
21.3
23.9
26.9
30.3
34.1
597
618
641
668
696
728
760
794
17.1
19.0
21.1
23.3
25.8
28.6
31.7
35.2
647
659
682
705
732
759
792
823
21.2
23.1
25.5
28.0
30.7
33.6
36.9
40.6
703
719
742
766
793
820
27.6
29.9
32.8
35.8
38.9
42.3
755
776
799
824
34.6
37.7
41.0
44.4
Inlet Sound Power, LWi [dB ref 10-12 watts]
% WOV
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
200
1
2
3
4
5
6
7
8
LWi
64
A
RPM
200
% WOV
1
2
3
4
5
6
7
8
LWo
67
A
100
80
72 68 64 64 57 46 38 31
70 66 63 63 57 47 40 34
67 65 63 63 57 47 38 31
69 66 63 63 56 46 39 33
79 76 73 73 67 57 50 46
77 74 73 71 65 57 50 43
75 72 72 71 65 58 51 44
74 72 71 70 65 58 51 43
88 84 81 79 78 71 61 55
85 82 78 77 74 67 61 54
84 81 76 76 73 68 62 55
84 81 76 76 73 68 62 56
94 94 89 84 85 80 69 62
93 92 86 82 79 74 67 61
91 88 81 79 78 74 68 63
90 87 81 79 77 73 68 64
98 101 98 95 92 93 85 70
96 99 96 93 89 84 78 71
95 96 91 89 86 83 78 74
95 96 91 89 86 83 78 74
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
72 69 67 67 60 51 44 37
72 69 67 67 60 52 44 37
71 68 66 67 60 52 45 39
71 68 66 67 61 52 46 39
81 78 76 75 69 61 53 45
80 76 74 72 67 60 52 45
79 75 72 72 67 60 53 45
80 75 73 72 67 60 53 45
91 85 84 82 80 73 62 55
89 84 82 81 76 69 61 53
89 83 80 79 75 69 62 54
88 83 79 79 75 69 62 55
92 92 91 89 87 81 73 64
92 90 88 86 82 76 69 62
90 88 86 84 80 76 70 64
91 89 86 83 80 75 70 65
97 100 102 100 96 94 87 74
63
63
63
73
71
71
71
82
78
78
78
89
85
82
82
99
94
91
91
67
66
67
75
73
72
73
84
82
80
80
91
87
86
85
102
98
95
95
60
50
100
80
60
50
100
80
60
50
300
425
575
828
300
425
575
828
100
80
60
50
100
80
100
80
96
98 99 97 92 88 81 73
60
50
60
50
96 96 96 94 90 86 80 74
97 97 96 94 90 85 81 75
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
46
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-49 Class II
10
9
8
7
6
5
4
3
2
1
0
Performance Data
RPM
BHP
100
75
50
40
60% WOV
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
Maximum Fan RPM
1020
50% WOV
Specification Data
20
15
10
5
70% WOV
Maximum Motor
Frame Size
405T
30
20
80% WOV
Minimum Motor
Starting hp
15 hp
60 in.
11 kW
1524 mm
Wheel Diameter
Approximate Weight
(Less Motor & Drives)
3100 lbs. 1406 kg.
90% WOV
10
Maximum Bhp = (Fan RPM / 231)3
Outlet Velocity (FPM) = CFM / 24.85
Tip Speed (FPM) = Fan RPM x 15.7
% WOV = (CFM x 100) / (Fan RPM x 77.8)
Imperial data — Metric data
0
60
70
80
0
10
20
30
40
50
Volume (cfm x 1000)
100
120
0
20
40
60
80
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
6
7
8
RPM
393
427
462
498
534
570
607
644
681
718
755
793
BHP
3.72
4.55
5.52
6.65
7.95
9.43
11.1
13.0
15.1
17.5
20.1
23.0
RPM
441
470
501
533
565
599
634
670
705
741
777
814
BHP
6.09
7.05
8.18
9.48
10.9
12.6
14.5
16.6
18.9
21.4
24.2
27.3
RPM
530
551
576
604
631
660
691
722
754
786
820
854
BHP
11.9
13.1
14.4
16.0
17.7
19.6
21.8
24.2
26.9
29.8
32.9
36.4
RPM
616
631
648
669
694
719
748
775
804
835
866
898
BHP
18.7
20.2
21.8
23.5
25.5
27.7
30.1
32.7
35.6
38.8
42.3
46.1
RPM
697
707
719
736
754
776
801
826
854
882
910
940
BHP
26.0
28.0
30.0
32.0
34.2
36.6
39.2
42.1
45.3
48.7
52.3
56.4
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
27000 1078
30000 1198
33000 1317
36000 1437
39000 1557
42000 1677
45000 1797
48000 1916
51000 2036
54000 2156
57000 2276
60000 2396
778
789
800
816
834
852
876
901
927
955
983
36.2
38.6
41.1
43.6
46.3
49.1
52.3
55.6
59.2
63.2
67.5
853
864
874
890
907
925
947
972
997
47.7
50.6
53.6
56.6
59.7
63.0
66.7
70.6
74.7
923
933
944
959
976
994
1014
60.5
63.9
67.4
70.9
74.5
78.3
82.4
988
999
74.6
78.5
82.5
1010
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
300
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWi
A
RPM
300
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWo
77
75
74
74
85
82
81
80
93
89
86
86
102
99
96
A
82 75 72 73 69 58 50 44
79 72 69 70 65 56 47 39
77 69 67 69 64 55 47 39
76 68 66 68 63 55 47 39
91 85 81 79 81 73 61 55
87 81 77 77 74 65 57 50
84 78 75 76 73 65 57 51
84 78 74 75 72 63 57 51
91 92 88 86 88 83 72 64
88 89 86 84 80 74 67 60
86 86 82 81 79 74 67 61
88 87 81 80 77 72 66 62
93 100 99 96 93 95 87 71
89 97 97 93 89 85 78 70
88 93 93 90 87 83 77 71
90 92 92 89 86 82 78 73
96 102 105 102 98 99 96 80
91 97 101 99 95 91 86 77
92 94 97 96 92 89 84 78
94 95 97 95 91 88 84 80
73
70
69
68
83
78
77
76
91
86
83
82
100
95
92
91
105
101
97
97
85 78 76 77 71 61 53 47
84 77 75 75 69 59 51 44
83 75 73 75 68 59 51 44
83 75 71 74 68 58 51 45
89 85 84 83 81 74 63 55
88 84 83 82 76 69 60 52
88 83 80 80 75 68 60 53
88 83 79 79 74 67 60 54
91 93 93 90 88 83 74 64
89 90 90 88 83 77 69 60
87 87 87 85 81 75 68 62
90 88 86 84 80 74 68 63
95 98 101 99 95 96 89 74
92 95 99 98 93 88 81 72
93 92 96 95 90 85 79 73
96 94 97 94 89 84 79 74
99 103 106 105 101 100 97 83
425
575
425
575
825
825
95
107
104
101
101
96
99 104 104 98 94 88 79
1020
1020
98 99 101 100 95 91 86 79
100 101 102 100 95 90 85 80
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
47
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-54 Class I
6
5
4
3
2
1
0
Performance Data
Maximum Fan RPM
Specification Data
RPM
50
BHP
14
12
10
8
60
40
% WOV
752
60% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
30
20
70% WOV
Maximum Motor
Frame Size
365T
80% WOV
Minimum Motor
10 hp
7.5 kW
1676 mm
2900 lbs. 1315 kg.
Starting hp
Wheel Diameter
66 in.
6
10
5
Approximate Weight
(Less Motor & Drives)
90% WOV
4
Maximum Bhp = (Fan RPM / 197)3
Outlet Velocity (FPM) = CFM / 30.46
Tip Speed (FPM) = Fan RPM x 17.3
% WOV = (CFM x 100) / (Fan RPM x 118)
Imperial data — Metric data
2
0
0
10
20
30
40
50
60
70
80
90
Volume (cfm x 1000)
0
2
4
6
8
10
12
14
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
1.5 2.5
CFM
OV
0.25
RPM
0.5
1
2
3
3.5
4
BHP
1.43
1.99
2.73
3.68
4.87
6.32
8.06
10.1
12.5
15.3
18.5
22.2
RPM
272
300
331
365
400
437
474
511
550
589
628
667
BHP
2.56
3.21
4.05
5.13
6.44
8.05
9.94
12.2
14.7
17.7
21.1
24.9
RPM
343
363
386
414
442
475
508
543
579
616
653
690
BHP
5.24
6.20
7.25
8.50
10.0
11.8
14.0
16.4
19.3
22.6
26.2
30.4
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
23000
27800
755
912
234
268
304
341
379
418
457
497
536
576
616
656
420
439
460
485
514
542
574
608
643
678
714
9.54
10.9
12.5
14.1
16.2
18.4
21.1
24.2
27.7
31.6
36.0
32600 1070
37400 1227
42200 1385
47000 1543
51800 1700
56600 1858
61400 2015
66200 2173
71000 2330
75800 2488
486
505
527
551
578
607
636
669
703
737
14.8
16.7
18.8
20.9
23.4
26.3
29.5
33.2
37.4
42.0
536
546
567
588
612
638
667
696
727
19.4
21.2
23.6
26.1
28.8
31.8
35.3
39.1
43.4
590
603
624
646
670
695
725
26.2
28.5
31.5
34.5
37.8
41.3
45.4
641
658
679
701
725
751
33.9
36.9
40.4
44.0
47.8
52.0
679
689
710
730
39.7
42.6
46.4
50.4
Inlet Sound Power, LWi [dB ref 10-12 watts]
% WOV
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
200
1
2
3
4
5
6
7
8
LWi
67
A
RPM
200
% WOV
1
2
3
4
5
6
7
8
LWo
70
A
100
80
75 71 67 67 60 49 41 34
73 69 66 66 60 50 43 37
71 68 66 66 60 49 41 34
72 69 66 66 59 49 42 36
80 77 74 74 66 57 51 47
78 74 74 71 65 57 50 43
76 72 73 71 65 58 51 44
76 72 73 71 65 58 51 43
87 84 80 79 79 69 60 55
85 82 78 77 73 66 60 53
84 80 76 76 73 67 61 54
84 80 76 76 72 67 61 55
96 94 89 85 87 79 69 62
95 92 86 83 79 74 67 61
93 88 82 80 78 74 69 64
91 87 81 80 78 74 69 64
100 101 98 96 93 94 84 69
98 99 96 93 89 84 78 71
97 95 92 89 87 83 79 74
97 95 92 89 87 83 79 74
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
75 72 70 70 63 54 47 40
74 71 69 70 63 54 47 40
74 71 69 70 63 55 48 42
74 71 69 70 64 55 49 42
82 78 77 75 69 61 53 45
81 76 75 73 67 60 52 45
80 75 74 72 67 60 53 45
81 75 74 73 67 60 53 45
90 85 84 82 80 70 61 53
88 83 83 81 75 68 60 52
88 82 80 79 74 68 61 53
88 82 80 79 74 68 61 54
94 93 92 89 88 81 72 64
93 91 89 87 82 76 69 62
91 88 87 84 81 76 70 64
93 89 86 84 80 76 70 65
98 101 103 100 96 95 86 73
66
66
66
74
72
71
71
81
78
77
77
90
85
83
83
99
95
92
92
69
69
70
76
73
73
73
84
81
80
79
92
88
86
86
60
50
100
80
60
50
100
80
60
50
275
375
525
752
275
375
525
752
100
80
60
50
100
80
100
80
102
98
96
98
99 100 97 93 88 81 73
60
50
60
50
97 97 97 94 90 86 80 74
98 98 97 94 90 86 81 75
96
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
48
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-54 Class II
10
8
RPM
BHP
Performance Data
100
125
60% WOV
75
% WOV
50% WOV
Maximum Fan RPM
929
Density 0.075 lb/ft3
Density 1.2 kg/m3
50
Specification Data
20
15
10
5
70% WOV
Maximum Motor
Frame Size
405T
80% WOV
6
30
20
Minimum Motor
Starting hp
15 hp
66 in.
11 kW
1676 mm
Wheel Diameter
4
Approximate Weight
(Less Motor & Drives)
3600 lbs. 1633 kg.
90% WOV
10
Maximum Bhp = (Fan RPM / 197)3
Outlet Velocity (FPM) = CFM / 30.46
Tip Speed (FPM) = Fan RPM x 17.3
% WOV = (CFM x 100) / (Fan RPM x 104)
Imperial data — Metric data
2
0
0
40
60
Volume (cfm x 1000)
80
90
100
0
10
20
30
50
70
120
140
160
0
20
40
60
80
100
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
6
7
8
RPM
364
394
425
457
488
520
552
584
617
650
682
715
BHP
4.71
5.71
6.88
8.22
9.76
11.5
13.5
15.7
18.1
20.9
23.9
27.2
RPM
407
433
460
488
516
546
577
608
639
671
702
734
BHP
7.61
8.78
10.1
11.7
13.4
15.4
17.6
20.0
22.7
25.6
28.9
32.4
RPM
485
505
527
552
576
602
629
656
684
712
741
771
BHP
14.7
16.1
17.7
19.6
21.6
23.9
26.5
29.3
32.3
35.7
39.3
43.3
RPM
562
577
592
611
632
655
680
704
729
756
784
811
BHP
23.0
24.8
26.7
28.8
31.1
33.6
36.5
39.5
42.9
46.6
50.7
55.0
RPM
636
645
656
671
687
707
728
750
775
800
824
850
BHP
32.0
34.3
36.6
39.0
41.6
44.4
47.5
50.8
54.5
58.5
62.8
67.4
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
33500 1105
37000 1221
40500 1336
44000 1452
47500 1567
51000 1683
54500 1798
58000 1914
61500 2029
65000 2145
68500 2260
72000 2376
710
719
728
743
759
775
796
818
840
865
889
44.4
47.2
50.1
53.1
56.2
59.5
63.2
67.1
71.2
75.9
80.8
777
786
796
810
825
840
860
881
903
926
58.3
61.7
65.2
68.7
72.3
76.2
80.4
85.0
89.7
94.9
840
849
859
872
887
903
920
73.7
77.7
81.8
85.9
90.1
94.5
99.3
899
909
918
90.7
95.2
99.9
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
275
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWi
A
RPM
275
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWo
78
A
81 75 72 75 69 58 50 44
79 72 70 71 65 55 47 38
77 70 68 70 64 55 47 39
76 69 68 70 63 55 47 39
90 84 80 79 81 70 60 54
87 80 77 77 72 64 56 49
83 77 75 76 72 63 56 50
84 77 74 76 70 62 56 50
93 92 89 87 89 82 72 63
91 89 87 85 81 74 67 60
88 85 83 82 79 74 67 61
90 86 82 81 78 72 67 63
95 101 100 96 94 97 86 70
91 98 97 94 89 85 78 70
90 95 93 90 87 83 77 71
91 93 92 89 86 82 78 73
97 104 105 102 99 101 95 79
92 99 102 100 95 92 86 77
93 96 98 96 92 89 84 79
95 96 97 95 92 89 85 80
74
71
70
69
83
78
77
76
92
86
84
83
101
95
93
92
106
101
98
97
84 78 77 78 71 61 54 47
84 77 76 76 68 59 51 44
83 75 74 76 68 59 51 44
83 75 73 76 67 58 51 45
88 85 85 82 81 71 61 54
88 84 83 81 75 67 59 51
88 82 81 80 74 66 59 52
88 81 79 79 73 65 59 53
93 93 94 90 89 83 73 64
90 90 91 88 83 77 69 60
88 87 88 85 81 75 68 62
91 88 87 85 80 74 68 63
96 99 103 99 96 97 87 73
93 96 101 98 93 88 81 72
94 94 97 95 90 86 79 73
97 96 98 94 90 84 79 74
100 104 108 105 101 102 96 82
97 101 105 104 98 94 88 79
99 99 102 100 96 91 86 79
101 102 103 100 95 91 85 80
76
75
75
84
82
80
79
93
89
87
86
375
525
750
929
375
525
750
929
103
99
96
96
108
105
101
101
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
49
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-60 Class I
8
7
6
5
4
3
2
1
0
Performance Data
Maximum Fan RPM
Specification Data
RPM
BHP
75
60% WOV
% WOV
18
16
14
12
10
8
Density 0.075 lb/ft3
Density 1.2 kg/m3
680
60
50
40
70% WOV
Maximum Motor
Frame Size
405T
80% WOV
Minimum Motor
15 hp
6
11 kW
8
0
30
25
Starting hp
Wheel Diameter
73 in.
1854 mm
20
15
Approximate Weight
(Less Motor & Drives)
3500 lbs. 1588 kg.
5
6
90% WOV
0
0
10
Maximum Bhp = (Fan RPM / 167)3
Outlet Velocity (FPM) = CFM / 37.23
Tip Speed (FPM) = Fan RPM x 19.1
% WOV = (CFM x 100) / (Fan RPM x 159)
Imperial data — Metric data
4
2
0
0
0
20
40
60
Volume (cfm x 1000)
80
100
120
20
40
60
80
100
120
140
160
180
200
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
1.5 2.5
CFM
OV
0.25
RPM
0.5
1
2
3
3.5
4
BHP
2.43
3.36
4.56
6.06
7.89
10.1
12.7
15.8
19.4
23.5
28.2
33.5
RPM
271
300
331
364
398
432
467
502
538
575
611
647
BHP
3.92
4.98
6.33
8.00
10.0
12.4
15.3
18.5
22.3
26.6
31.5
37.0
RPM
328
349
374
402
432
463
495
529
562
597
631
666
BHP
7.58
8.89
10.5
12.4
14.7
17.4
20.5
24.2
28.3
33.0
38.3
44.2
RPM
380
397
417
440
465
493
523
555
586
619
652
BHP
11.7
13.4
15.3
17.4
20.0
22.9
26.3
30.3
34.7
39.7
45.3
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
34000
912
242
276
310
345
381
417
454
490
527
564
601
638
40000 1073
46000 1234
52000 1395
58000 1556
64000 1717
70000 1878
76000 2039
82000 2200
88000 2361
94000 2522
100000 2683
439
458
477
500
525
551
579
610
642
673
18.2
20.5
23.1
25.8
29.0
32.6
36.7
41.5
46.8
52.7
484
494
514
533
556
580
606
634
663
23.7
26.0
29.0
32.2
35.6
39.4
43.8
48.7
54.3
534
547
566
586
609
632
659
32.1
35.1
38.8
42.6
46.7
51.3
56.5
580
596
616
636
659
41.6
45.5
49.9
54.4
59.2
615
625
644
663
48.8
52.5
57.2
62.3
Inlet Sound Power, LWi [dB ref 10-12 watts]
% WOV
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
300
1
2
3
4
5
6
7
8
LWi
78
A
RPM
300
% WOV
1
2
3
4
5
6
7
8
LWo
80
A
100
80
85 81 78 78 73 63 56 51
83 79 77 75 69 62 55 49
82 77 76 75 69 63 56 49
81 77 76 75 69 63 56 49
92 89 84 82 83 72 64 58
91 86 82 80 76 70 63 57
89 84 79 79 76 70 65 59
89 83 79 79 75 70 65 59
99 96 90 87 89 79 70 63
97 93 87 85 81 75 69 63
95 89 83 82 80 75 70 65
94 88 83 82 80 75 70 65
101 101 95 91 92 87 76 69
99 99 93 89 86 80 74 68
98 96 88 86 84 80 75 70
96 95 88 86 84 80 75 70
103 105 99 95 94 92 81 73
101 104 97 92 90 85 78 72
99 101 92 89 88 84 79 74
99 99 92 89 88 84 79 74
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
86 82 82 80 75 65 57 50
85 81 80 78 71 64 57 49
85 79 78 77 71 65 57 49
85 79 78 77 71 64 57 50
92 89 89 86 84 75 66 58
92 87 87 84 78 72 64 56
91 85 84 82 77 72 65 58
91 85 84 82 77 72 65 59
96 94 94 91 90 82 73 65
95 92 91 88 83 78 70 63
93 90 89 86 82 77 71 65
95 90 88 86 82 77 72 67
98 99 98 96 93 88 79 71
98 97 95 93 88 83 76 69
96 95 93 91 87 82 77 71
98 96 92 90 87 82 77 72
100 102 101 100 96 93 84 76
99 101 98 97 92 87 81 73
98 99 95 95 91 87 81 75
100 100 95 94 90 86 81 76
76
75
75
86
82
81
81
92
87
85
85
96
92
89
89
100
96
93
93
78
77
77
88
85
83
83
94
90
88
88
98
94
93
92
60
50
100
80
60
50
100
80
60
50
400
500
600
680
400
500
600
680
100
80
60
50
100
80
102
98
96
60
50
50
96
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
50
Download from Www.Somanuals.com. All Manuals Search And Download.
QEI-60 Class II
12
10
8
50% WOV
60% WOV
Performance Data
RPM
BHP
125
150
100
75
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
Maximum Fan RPM
840
25
20
15
10
5
Specification Data
70% WOV
Maximum Motor
Frame Size
405T
60
50
80% WOV
Minimum Motor
Starting hp
15 hp
73 in.
11 kW
1854 mm
40
6
Wheel Diameter
30
25
Approximate Weight
(Less Motor & Drives)
4
4200 lbs. 1905 kg.
20
15
90% WOV
Maximum Bhp = (Fan RPM / 167)3
Outlet Velocity (FPM) = CFM / 37.23
Tip Speed (FPM) = Fan RPM x 19.1
% WOV = (CFM x 100) / (Fan RPM x 140)
Imperial data — Metric data
2
0
0
0
20
40
60
80
100
120
Volume (cfm x 1000)
0
50
100
150
200
Volume (m3/hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
6
7
8
RPM
323
355
388
421
454
488
522
556
591
625
660
695
BHP
5.51
6.91
8.58
10.6
12.9
15.5
18.6
22.0
25.9
30.3
35.2
40.7
RPM
362
390
418
448
479
511
543
576
610
643
677
711
BHP
9.20
10.6
12.6
14.8
17.4
20.4
23.8
27.5
31.8
36.5
41.7
47.5
RPM
436
455
479
504
531
559
588
617
647
678
710
742
BHP
17.6
19.6
21.9
24.6
27.6
31.1
35.0
39.3
44.1
49.4
55.3
61.7
RPM
507
520
537
557
580
605
631
658
687
715
745
774
BHP
27.6
30.2
32.9
35.9
39.3
43.2
47.5
52.2
57.6
63.4
69.8
76.7
RPM
573
583
595
611
628
651
674
699
724
751
779
808
BHP
38.5
41.8
45.1
48.6
52.4
56.6
61.3
66.5
72.2
78.3
85.1
92.6
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
40000 1073
45000 1207
50000 1341
55000 1476
60000 1610
65000 1744
70000 1878
75000 2012
80000 2147
85000 2281
90000 2415
95000 2549
641
651
662
678
694
715
738
762
787
813
840
54.1
58.1
62.3
66.6
71.1
76.2
81.8
87.8
94.5
101.7
109.3
704
713
724
740
757
776
799
822
71.7
76.6
81.7
86.7
92.1
98.1
104.6
111.5
762
772
783
799
815
834
91.5
97.2
817
827
839
113.4
119.9
126.7
103.1
109.1
115.3
122.1
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
Outlet Sound Power, LWo [dB ref 10-12 watts]
RPM
300
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWi
A
RPM
300
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
7
8
LWo
82
A
86 80 77 78 76 64 56 49
83 77 75 75 69 60 52 44
81 74 73 75 68 59 52 45
80 73 72 74 67 59 52 45
95 90 88 86 89 79 70 61
93 87 86 84 79 72 65 58
90 83 82 82 78 72 65 59
91 84 81 81 77 70 65 61
96 98 96 93 93 91 80 66
94 95 94 91 86 81 73 66
91 91 90 88 84 79 73 67
92 91 89 87 83 78 74 69
98 103 103 99 97 99 89 73
95 101 100 96 92 88 81 72
93 97 96 93 90 86 80 74
94 97 95 92 89 85 81 76
100 105 106 102 100 101 94 78
96 102 103 100 95 91 85 76
95 99 99 96 93 89 84 78
97 100 98 95 92 89 84 79
79
75
74
74
91
85
83
82
98
92
90
89
87 82 82 81 77 66 58 51
86 81 81 80 72 64 55 48
86 79 78 80 71 63 56 49
86 78 77 79 70 62 56 49
93 92 93 89 89 80 71 62
91 89 91 87 82 75 66 58
90 87 88 85 80 73 66 60
92 87 87 84 79 72 67 61
96 98 100 96 94 92 81 69
93 95 98 94 89 84 76 67
93 93 95 91 87 81 75 69
95 94 95 91 86 80 75 70
99 102 105 103 99 99 90 76
96 99 104 101 96 91 83 75
97 98 100 98 93 88 82 76
99 100 100 97 92 87 82 77
101 104 107 106 102 102 95 81
98 101 105 104 99 95 88 79
99 101 102 101 96 92 86 79
102 104 103 101 96 91 86 81
80
79
78
92
88
86
85
99
96
93
92
450
600
750
840
450
600
750
840
104
98
95
105
102
99
95
99
107
101
99
108
105
102
102
98
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWiA and outlet LWo
,
LWoA sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWiA and LWoA values only.
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
Model QEI-L, QEI-I/II and QEID
Supply, exhaust, or return air fans shall be
of the inline mixed flow type.
maximum allowable fan vibration shall be
0.15 in/sec. peak velocity, filter-in for
QEI-I/II with signatures taken on each
bearing in three planes; horizontal, vertical,
and axial. Maximum vibration of 0.08 in/sec.
peak velocity, filter-in for QEID in a single
plane on the fan housing. This report shall
be provided at no charge to the customer
upon request.
The housing shall be constructed of welded
heavy-gauge steel to assure no air leakage.
Housing shall have inlet and outlet collars
for slip-fit duct connections. The housing
and bearing and/or motor supports shall be
constructed of heavy-gauge steel members
to prevent vibration and rigidly support the
shaft and bearings. Welded steel vanes
shall straighten the flow of air from the fan
discharge.
Inlet and outlet sound power levels shall be
provided for each of the eight octave bands
at the point of operation.
Fans shall be licensed to bear the AMCA
Seal for Sound and Air Performance.
All QEI-L and QEI-I/II units up through size
27 shall incorporate a universal mounting
system that allows the fan to be mounted in
either vertical or horizontal configurations
and field rotation of the motor position in
90 degree increments. Bearing life shall not
be reduced below specified level in different
configurations. QEI-I/II units size 30 and
larger shall allow for field rotation of motor
positions. Units shall accommodate base
mount or ceiling hung mounting without
structural modifications to the fan.
Mixed flow fans shall be Model QEI-L,
QEI-I/II or QEID as manufactured by
Greenheck Fan Corporation, Schofield,
Wisconsin, USA and shall be supplied as
shown on the plans and in the fan schedule.
Additional Belt Drive Specification
Turned, precision ground and polished steel
shafts shall be sized so the first critical
speed is at least 25% over the maximum
operating speed. Close tolerances shall be
maintained where the shaft makes contact
with the bearings.
The wheel shall be of the mixed flow type.
Wheels shall have a wheel cone, spherical
back plate and single thickness cambered
blades. Wheels shall be statically and
dynamically balanced to balance grade
G6.3 per ANSI S2.19. The wheel cone and
fan inlet cone shall be carefully matched
and shall have precise running tolerances
for maximum performance and operating
efficiency.
Bearings shall be heavy-duty, grease
lubricated, self-aligning ball or roller type
with extended lubrication lines.
QEI-I/II and QEI-L (horizontal mount)
bearings shall be selected for a minimum
life L of 80,000 (L of 400,000) hours at
10
50
maximum operating speed. QEI-L (vertical
mount) bearings shall be selected for a
minimum life, L of 50,000 (L of 250,000)
10
50
Each assembled fan shall be test run at
the factory at the specified fan RPM. The
hours at maximum operating speed.
Our Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period
of one year from the shipment date. Any units or parts which prove defective during the warranty
period will be replaced at our option when returned to our factory, transportation prepaid. Motors are
warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck
prove defective during this period, they should be returned to the nearest authorized motor service
station. Greenheck will not be responsible for any removal or installation costs.
Prepared to Support
Green Building Efforts
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.