| 	
		 GSW WATER HEATING   
					A GSW Company   
					599 Hill Street West   
					Fergus, ON, Canada N1M 2X1   
					DIRECT VENT GAS FIRED WATER HEATER   
					INSTALLATION AND OPERATING INSTRUCTIONS   
					Read these instructions thoroughly before starting   
					TABLE OF CONTENTS   
					I)   
					Installation & Location ............................................1   
					II) Replacement Parts Listing ....................................2   
					III) Vent Connections................................................3-5   
					IV) Gas Connections....................................................5   
					V) Water Pipe Connections ........................................5   
					VI) Temperature & Pressure ....................................5-6   
					VII) Lighting & Operating Instructions........................7-9   
					VIII) Service And Maintenance ....................................10   
					IX) Combo Heating ....................................................11   
					X) Warranty ..............................................................12   
					PLEASE RETAIN THESE INSTRUCTIONS IN A   
					SAFE LOCATION FOR FUTURE   
					FOR YOUR SAFETY   
					• Do not store or use gasoline or other   
					flammable vapours and liquids in the   
					vicinity of this or any other   
					appliance.   
					• Installation and service must be   
					performed by a qualified installer,   
					service agency or the gas supplier.   
					WARNING: Improper installation,   
					adjustment, alteration, service, or   
					maintenance can cause injury or   
					property damage. Refer to this   
					manual. For assistance or additional   
					information, consult a qualified   
					installer, service agency, or the gas   
					supplier.   
					WHAT TO DO IF YOU SMELL GAS?   
					• Do not try to light any appliance.   
					• Do not touch any electrical switch; do   
					not use any phone in your building.   
					• Immediately call your gas supplier   
					from a neighbor’s phone. Follow the   
					gas supplier’s instructions.   
					WARNING: If the information in   
					these instructions is not followed   
					exactly, a fire or explosion may   
					result causing property damage,   
					personal injury or death.   
					• If you cannot reach your gas supplier,   
					call the fire department.   
					PART NO. 70999 REV. G (03-12)   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SEAL TIGHTLY   
					1 
					2 
					14   
					OPTION 2   
					7 
					10   
					13   
					OPTION 1   
					3 
					11   
					6”   
					12   
					9 
					8 
					6 
					Location of pressure relief and/or expansion tank if a check   
					valve or pressure reducing valve is in the cold water supply to   
					the house.   
					4 
					5 
					Use OPTION 1 or 2 whichever is more convenient. If pressure   
					relief valve is used, select one with a setting 25 psi below valve   
					rating at tank.   
					1. COLD WATER INLET   
					2. HOT WATER OUTLET   
					3. GAS SUPPLY MANUAL SHUT-OFF VALVE   
					4. SEDIMENT TRAP   
					5. UNION - GROUND JOINT TYPE   
					6. FLOOR DRAIN   
					7. TEMPERATURE & PRESSURE RELIEF VALVE   
					8. GAS CONTROL   
					9. WATER SUPPLY TO METER   
					10. WATER SUPPLY TO HOME   
					11. WATER METER WITH BACKFLOW PREVENTER   
					12. OVERFLOW   
					13. PRESSURE RELIEF VALVE   
					14. EXPANSION TANK   
					Figure 2   
					– 2 –   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Specially For Direct Vent Water Heater:   
					recommended is 90” or in compliance with figure 3M.   
					*Where the wall is combustible and the wall thickness is   
					over 14”, 1 inch clearance to combustible materials around   
					the terminal pipe is needed. The first 14” is zero clearance.   
					Make certain to observe the vent location limitations   
					complying with the CAN/CGA-B149 Installation Code or   
					ANSI Z223.1 National Fuel Gas code and/or local codes.   
					There are some important issues shown in Figure 3.   
					MAX. 90”   
					WALL   
					Vent Terminal must be located at   
					least 12” from Windows, Doors,   
					or any other Opening through   
					which flue gases could enter the   
					4”   
					3”   
					18”   
					Min.   
					building.   
					Vent terminal must be   
					located at least 36” above   
					any Forced Air Inlet into the   
					building within 10 feet of   
					the Vent Terminal   
					4”   
					12” Min.   
					18”   
					Min.   
					36”   
					Min.   
					Figure 3 B - Moving Water Heater To Its Final   
					Installed Location.   
					Within 10 feet   
					Move the water heater to its final installed location. Make   
					certain clearances from combustible material are   
					observed. The maximum distance from center of water   
					heater to outside wall should not be longer than 90”.   
					12” Min. above grade. Higher   
					in Areas of Heavy Snowfall   
					Any Forced Air Inlet   
					into the building   
					Figure 3 - Vent Location Limitations   
					CLAMP   
					For a second or more direct vent unit, the distance   
					between vent terminals must have a minimum of 1 foot.   
					SPRING   
					INSPECT SHIPMENT –– There may be hidden damage   
					caused by transit. Check to be certain all parts of the   
					venting system, as shown in Figures 3A through 3M, are   
					present. Inspect the upper and lower air inlet boxes, rear   
					air tube and all parts of the venting system.   
					CAUTION   
					If there are any damaged parts, DO NOT install this water   
					heater. Report any shortage to your distributor or damage   
					to your carrier.   
					Figure 3 C - Vent Assembly.   
					The vent pipe and terminal are assembled by the   
					manufacturer as shown in figure 3C. There are springs   
					fastened inside the corrugated pipe. When the vent pipes   
					are pulled to a required length, the distances between the   
					springs will still be equally spaced.   
					Note: The four fasteners that are required to secure the   
					vent terminal to the exterior wall are not provided. These   
					should be screw type (not nails) chosen for the type of   
					construction and obtained locally.   
					CAUTION   
					Cut edges of corrugated (flex) pipe are extremely sharp.   
					Wear gloves when handling.   
					SEALANT   
					VENT CONNECTIONS - After the location for the vent   
					terminal has been selected as outlined in Figure 3, use   
					the following illustrations for installation:   
					7” DIAMETER   
					MIN.   
					68”   
					Figure 3 D - Securing Vent Termination Assembly To   
					The Exterior Wall.   
					BOTTOM OF HEATER   
					Introduce the 6” pipe through the clearance hole from   
					exterior wall then secure the vent terminal to the exterior   
					wall with 4 screw anchors appropriate for the type of   
					wall construction. Caulk the junction of the vent terminal   
					base plate and the exterior wall with exterior type   
					silicone sealant.   
					Figure 3 A - Locating Clearance Hole for Vent.   
					Cut a clearance hole, approximately 7 inches in diameter,   
					through the exterior wall for the vent assembly. The   
					minimum height should not be less than 68” from the hole   
					center to bottom of water heater. The maximum height   
					– 3 –   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SPRING   
					REDUCER   
					H 
					Figure 3 H   
					Figure 3 E - Pull the 3 1/8” and 6” Corrugated Pipe   
					Toward the Water Heater Individually.   
					1. Pull the 3 1/8” corrugated pipe toward the water   
					heater and leave some length over the water   
					heater’s center for bending.   
					Apply silicone around 6” collar on air manifold box. Pull   
					corrugated vent tube all the way on to collar and secure   
					with one sheet metal screw (approx. 3/4”) up from edge   
					of vent tube. Pull gear clamp past screw and tighten.   
					2. Pull the 6” corrugated pipe toward the water heater   
					and leave it 1” shorter than 3 1/8” pipe.   
					3. Make sure there are two springs evenly spaced at   
					the bend in the pipe.   
					SLOPE   
					4. Use metal hangers to keep vent pipe level or with a   
					slope upward from the heater to terminal.   
					Figure 3 J   
					Check the vent pipe’s level or slope again, and adjust if   
					required.   
					Offset vent pipe Arrangement   
					Figure 3 F   
					Bend the 3 1/8” and 6” corrugated pipe all together   
					toward the water heater’s flue connection.   
					TOP VIEW   
					90°   
					MAXIMUM   
					BEND   
					Figure 3 K - CONDITION 1   
					Where a straight vent pipe arrangement is impossible, a   
					horizontal 90 degree maximum bend can be made. Use   
					the water heater casing outer diameter as a template to   
					form the corrugated pipe.   
					Figure 3 G   
					Pull and connect the 3 1/8” corrugated pipe to the water   
					heater’s flue tube reducer with hi-temp red silicone and gear   
					clamp. Make sure this connection is tight and leak proof.   
					*The sealant between 3 1/8” corrugated pipe and water   
					heater’s flue tube reducer must be hi-temp red silicone   
					or other material suitable for 600°F continuous service.   
					– 4 –   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Inlet gas pressure to the appliance must not exceed the   
					gas pressures marked on the rating plate; 7” W.C. for   
					natural gas, 14” W.C. for L.P. gas. The minimum supply   
					pressure for the purpose of input adjustment is 1” above   
					manifold pressure.   
					>1”   
					>1”   
					WALL   
					10”   
					(REF)   
					The appliance and its individual shutoff valve must be   
					disconnected from the gas supply piping system during   
					any pressure testing of that system at test pressure in   
					excess of 1/2 psig (3.5 kPa).   
					68 MINIMUM   
					The appliance must be isolated from the gas supply   
					piping system by closing its individual manual shutoff   
					valve during any pressure testing of the gas supply piping   
					system at test pressures equal to, or less than 1/2 psig   
					(3.5 kPa).   
					The appliance and its gas connection must be leak tested   
					before placing the appliance in operation. It is important   
					to have a readily accessible manual shutoff valve in the   
					gas line supplying the heat close to the heater. A drip leg   
					must be installed ahead of the gas control valve to help   
					trap sediment and foreign material.   
					Figure 3 L - CONDITION 2   
					Where floor joists impede venting, a rise to complete the   
					vent termination is possible. All installations require 1”   
					clearance to combustibles.   
					Note:   
					A ground-joint union must be installed ahead of the gas   
					valve to permit easy removal of the unit. All leak testing   
					must be done with a soapy water solution.   
					A. The maximum horizontal vent pipe length of 90” minus   
					wall thickness should be considered when installing   
					an offset vent arrangement.   
					B. Do not Combine condition (3K) with condition (3L)   
					in the same installation.   
					NEVER USE A MATCH OR OPEN FLAME TO TEST FOR   
					GAS LEAKS. A FIRE OR EXPLOSION COULD RESULT.   
					WATER PIPING   
					High Rise Vent Pipe Arrangement   
					Pipes and fittings should be installed in compliance with   
					the installation drawing. Check for dip tube in cold water   
					fitting before connection of hot and cold water lines. Show   
					where the water shut-off valve for the water heater is   
					installed so that the owner knows where and how to shut   
					the water off. It is recommended that such a valve be   
					located in close proximity to the cold water inlet of the   
					water heater.   
					Connect the cold water supply (3/4 NPT) to the fitting   
					marked “COLD”, the hot water outlet (3/4 NPT) to the   
					fitting marked “HOT”. Do not apply heat to either of these   
					fittings as they contain a nonmetallic tube. When making   
					these connections, always use a good grade of pipe joint   
					compound and be certain that all fittings are tight. See   
					installation drawing (FIGURE 2).   
					D 
					10”   
					(REF)   
					WALL THICKNESS   
					H 
					TO BOTTOM   
					OF HEATER   
					After piping has been installed, allow tank to fill with water   
					and check connections for leaks. To insure complete   
					filling of the tank, allow air to exit by opening the nearest   
					hot water faucet until a constant flow of water is obtained.   
					Figure 3 M   
					When the height H (From vent terminal center line to   
					bottom of heater) is over 90”, it is a high rise vent pipe   
					arrangement. The minimum distance “D” from the center   
					of the water heater to the outside wall surface is 22”, and   
					the maximum height of “H” is 12 feet.   
					TEMPERATURE & PRESSURE RELIEF VALVE   
					GAS CONNECTIONS   
					For protection against excessive pressure and/or   
					temperatures, a temperature and pressure relief valve   
					has been installed in the water heater.   
					Install the gas piping as indicated in Figure 2. Use only   
					new pipe and fittings with sound, clean-cut pipe threads.   
					Sealing compound must conform to the applicable code   
					for pipe sealing compound approved for use with natural   
					gas and propane. Use gas piping of adequate sizing to   
					ensure full gas input. All piping must comply with all local   
					codes. In the absence of local codes, piping must comply   
					with the rules stated by the applicable National Fuel Gas   
					Codes. The final connection to the gas control valve is   
					made using 1/2” N.P.T. pipe.   
					ANY REPLACEMENT VALVE MUST NOT EXCEED   
					THE TEMPERATURE AND PRESSURE RATING.   
					FAILURE TO INSTALL AND MAINTAIN A NEW,   
					PROPERLY LISTED TEMPERATURE AND PRESSURE   
					RELIEF   
					VALVE   
					WILL   
					RELEASE   
					THE   
					MANUFACTURER FROM ANY CLAIMS WHICH MIGHT   
					RESULT FROM EXCESSIVE TEMPERATURE OR   
					WATER PRESSURE.   
					– 5 –   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Pressure rating of the valve must not exceed the working   
					pressure shown on the rating plate of the water heater.   
					The discharge capacity must be equal to or greater than   
					the input to the water heater. Temperature and Pressure   
					Relief valve piping must terminate 6 inches, no more than   
					12” (reference the applicable code) above a floor drain or   
					external to the building. Do not thread, cap, or plug the   
					end of this discharge line. Be certain that no contact is   
					made with any live electrical part. Do not connect   
					discharge line directly to drain. See Figure 2. To prevent   
					bodily injury, hazard to life or damage to property, the   
					relief valve must be allowed to discharge water in the   
					event of excessive temperature or pressure developing in   
					the water heater. The function of the temperature and   
					pressure relief valve is to discharge water in quantities   
					should circumstances demand. If the discharge pipe is   
					not directed to drain as shown in Figure 2 or other   
					suitable means, the water flow may cause property   
					damage.   
					PRESSURE BUILD-UP IN A WATER SYSTEM   
					During the heating cycle of the water heater the water   
					expands, creating a pressure build-up in the water   
					system. The water supply meter may contain a check   
					valve or back flow preventer. This will create a closed   
					water system. A temperature and pressure relief valve   
					must be installed on the water heater (150 PSI maximum   
					pressure setting. See temperature and pressure relief   
					valve).   
					If a water heater is installed in a closed water supply   
					system, the relief valve will discharge water as the   
					volume of water expands with rising water temperatures.   
					This is normal and indicates a normal functioning of the   
					relief valve. Do not plug the relief valve. Only if the   
					discharge from the relief valve is continuous or for an   
					extended period of time would this indicate a   
					malfunction. Have the operation of the heater checked   
					by a qualified serviceman.   
					The discharge line:   
					INSTALLATION CHECK LIST   
					1) must not be smaller than the outlet pipe size of the   
					relief valve,   
					2) must not be plugged or blocked,   
					3) must be material capable of withstanding 210°F   
					without distortion,   
					4) must be installed so as to allow complete drainage of   
					both temperature and pressure relief valve,   
					5) must terminate at an adequate drain, and   
					6) must not have any valve between the relief valve and   
					the water heater.   
					Check Here   
					1. Have the vent location limitations and minimum   
					height for vent termination and maximum vent   
					length been checked?   
					2. Are the terminal and vent pipes installed and   
					sealed properly?   
					3. Has the gas piping been leak tested?   
					4. Is there at least a 1” clearance between the   
					water heater and combustible materials, 20” at   
					the top and 1” around the vent pipe?   
					WARNING   
					Do not attempt to operate this water heater   
					with the cold water inlet valve closed.   
					Manually operate the Temperature and   
					Pressure Relief valve at least once a year.   
					Standing clear of the outlet (discharge water   
					may be hot), lift and release the lever handle   
					on the Temperature and Pressure Relief   
					valve to make the valve operate freely.   
					NEVER OPERATE THE HEATER IF IT IS   
					NOT COMPLETELY FILLED WITH WATER.   
					TO MAKE SURE THE HEATER IS FILLED,   
					OPEN A HOT WATER TAP UNTIL A FULL   
					FLOW OF WATER IS VISIBLE WITH NO   
					AIR ESCAPING.   
					5. Have you taken steps to prevent water damage   
					in case of leaks?   
					6. Is the diptube installed in the cold water inlet   
					connection?   
					7. Is the water heater completely filled with water?   
					8. Does the gas piping conform with the   
					recommendations of your Local Gas Utility   
					Company?   
					9. Is the vent terminal opening unobstructed?   
					10.Is a temperature and pressure relief valve   
					installed?   
					11.Is the drain pipe from the T & P valve   
					unobstructed?   
					12.Has all plastic and cardboard packaging   
					material been removed from the heater and   
					venting?   
					IF the answer to all of the above questions is “YES”   
					proceed with lighting the heater.   
					– 6 –   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				VI) LIGHTING AFTER INSTALLATION   
					WARNING:   
					TO AVOID POSSIBLE INJURY, FIRE AND EXPLOSION,READ THESE PRECAUTIONS BEFORE ATTEMPTING TO LIGHT OR RE-   
					LIGHT THE PILOT. CHECK THAT THE HEATER IS FILLED WITH WATER AND THE VENTING SYSTEM IS UNOBSTRUCTED.   
					FOR YOUR SAFETY READ BEFORE LIGHTING   
					WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or   
					loss of life.   
					A. This appliance has a pilot which must be lighted by hand. When lighting a pilot, follow these instructions exactly.   
					B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier   
					than air and will settle on the floor.   
					WHAT TO DO IF YOU SMELL GAS   
					•Do not try to light any appliance.   
					•Do not touch any electric switch; do not use any phone in your building.   
					•Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.   
					•If you cannot reach your gas supplier, call the fire department.   
					C. Use only your hand to turn the gas control knob. Never use tools. If the knob will not turn by hand, do not try to repair it, call a   
					qualified service technician. Force or attempted repair may result in a fire or explosion.   
					D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance   
					and to replace any part of the control system and any gas control which has been under water.   
					BEFORE PROCEEDING WITH LIGHTING INSTRUCTIONS, PLEASE FAMILIARIZE YOURSELF WITH THE   
					CONTROL USED ON YOUR WATER HEATER. REFER TO ILLUSTRATIONS ON PAGES 7 & 8.   
					WARNING: Should overheating occur or the gas supply fail to shut off, turn off the manual gas valve to the appliance.   
					LIGHTING INSTRUCTIONS FOR HEATER WITH “SIT” GAS CONTROLS   
					1. STOP! Read all safety labels on the water heater before   
					operation.   
					2. Rotate the thermostat/control knob located on the gas control   
					clockwise   
					to the “OFF” position.   
					3. Wait 5 minutes to clear out any gas. If you smell gas, STOP!   
					Follow instruction “B” above on this page. If you do not smell   
					gas, go to the next step.   
					4. To light heater, remove outer door and remove 2 screws from   
					right side of hinged door.   
					5. Find pilot. Follow aluminum tube from the underside of the gas   
					control. The pilot is in front of the burner.   
					SIT GAS CONTROL (TOP VIEW)   
					6. Turn the thermostat/control knob counterclockwise   
					“PILOT” position.   
					to the   
					7. Use a lit match held securely with an extension device, or a   
					long stem igniter. While holding the ignition source at the pilot,   
					depress the pilot button to light the pilot.   
					8. Keep pilot button depressed for 60 seconds to properly heat   
					thermocouple and activate safety controls.   
					9. If pilot does not remain lit, repeat steps 7 & 8.   
					• If the pilot will not stay lit after several attempts, turn the   
					thermostat/control knob to “OFF” and contact your service   
					technician.   
					• If the pilot button does not pop up when released, stop and   
					immediately call your service technician or gas supplier.   
					10. Once the pilot is established, re-fasten 2 screws to right side   
					of hinged door, then replace the outer door.   
					WARNING: FAILURE TO PROPERLY SECURE THE   
					INNER DOOR MAY POSE A SAFETY HAZARD.   
					To Turn Off the Gas Control   
					11. Turn the thermostat control knob counterclockwise   
					to turn   
					1. Rotate the thermostat control knob clockwise   
					position.   
					to the “OFF”   
					on the heater. Set the knob position to the “LOW” marking to   
					start. Adjust the temperature up as required.   
					– 7 –   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				LIGHTING INSTRUCTIONS FOR HEATER WITH “ROBERTSHAW R110” GAS   
					CONTROLS   
					WARNING: Should overheating occur or the gas supply fail to shut off, turn off the manual gas valve to the appliance.   
					1. STOP! Read all safety labels on the water heater before operation.   
					2. Set the thermostat to the lowest setting. Rotate dial on front of control   
					counterclockwise.   
					GAS CONTROL KNOB   
					PILOT BUTTON   
					IN PILOT POSTION   
					3. Rotate gas control knob on top of thermostat clockwise   
					to “OFF” position.   
					4. Wait 5 minutes to clear out any gas. If you smell gas, STOP! Follow   
					instruction “B” above on page 7. If you do not smell gas, go to the next step.   
					5. To light heater, remove outer door and remove 2 screws from right side of   
					hinged door.   
					6. Find pilot. Follow aluminum tube from the “right-underside” of the gas   
					thermostat. The pilot is adjacent to burner.   
					7. Turn gas control knob counterclockwise   
					to “PILOT” position.   
					8. Use a lit match held securely with an extension device, or a long stem igniter.   
					While holding the ignition source at the pilot, depress the red pilot set button   
					(upper left) to light the pilot. Continue to hold the pilot set button for about 1   
					minute after pilot is lit. Release pilot set button and it will pop up. Pilot should   
					remain lit.   
					TEMPERATURE   
					DIAL   
					ROBERTSHAW R110 GAS CONTROL   
					•If knob does not pop up when released, stop and immediately call your   
					service technician or gas supplier.   
					•If the pilot will not stay lit after several tries, turn the control knob to “OFF”   
					and call your service technician or gas supplier.   
					9. Once the pilot is established, re-fasten 2 screws to right side of hinged door,   
					then replace the outer door.   
					WARNING: FAILURE TO PROPERLY SECURE THE INNER DOOR   
					MAY POSE A SAFETY HAZARD.   
					To Turn Off the Gas Control   
					1. Set the thermostat dial to the lowest setting. Turn   
					counterclockwise.   
					10. Turn gas control knob counterclockwise   
					to “ON” position.   
					2. Turn gas control knob “OFF”. Rotate clockwise.   
					11. Set the thermostat to desired setting clockwise.   
					LIGHTING INSTRUCTIONS FOR HEATER WITH “ROBERTSHAW 220R” GAS   
					CONTROLS   
					WARNING: Should overheating occur or the gas supply fail to shut off, turn off the manual gas valve to the appliance.   
					1. STOP! Read all safety labels on the water heater before operation.   
					2. Rotate gas control knob on top of thermostat clockwise   
					3. Set the thermostat to lowest setting.   
					to “OFF” position.   
					GAS CONTROL KNOB   
					SHOWN IN “OFF” POSITION   
					4. Wait (5) minutes to clear out any gas. If you then smell gas, STOP! Follow   
					instruction “B” above on page 7. If you don’t smell gas, go to the next step.   
					5. To light heater, remove outer door and remove 2 screws from right side of   
					hinged door.   
					PRESSURE REGULATOR   
					6. Find pilot. Follow aluminum tube from the “right-underside” of the gas   
					thermostat. The pilot is adjacent to burner.   
					7. Turn gas control knob counterclockwise   
					to “PILOT” position.   
					8. Use a lit match held securely with an extension device, or a long stem igniter.   
					While holding the ignition source at the pilot, depress the gas control knob to   
					light the pilot.   
					9. After pilot lights, keep knob depressed for at least 60 seconds to properly   
					heat thermocouple and activate safety valves.   
					10. If the pilot does not remain lit wait at least 10 minutes and repeat steps 1-9.   
					•If knob does not pop up when released, stop and immediately call your   
					service technician or gas supplier.   
					TEMPERATURE DIAL   
					ROBERTSHAW 220R GAS CONTROL   
					•If the pilot will not stay lit after several tries, turn the control knob to “OFF”   
					and call your service technician or gas supplier.   
					11. Once the pilot is established, re-fasten 2 screws to right side of hinged door,   
					then replace the outer door.   
					WARNING: FAILURE TO PROPERLY SECURE THE INNER DOOR   
					MAY POSE A SAFETY HAZARD.   
					To Turn Off the Gas Control   
					1. Set the thermostat dial to the lowest setting. Turn   
					counterclockwise.   
					12. Turn gas control knob counterclockwise   
					13. Set thermostat to desired setting clockwise.   
					to “ON” position.   
					2. Turn gas control knob “OFF”. Rotate clockwise.   
					– 8 –   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EXPOSURE TO WATER   
					WARNING   
					If the water heater needs to be relit;   
					IMPORTANT   
					Should the water heater be subjected to   
					flooding, fire, or other unusual condition, turn   
					off gas at the manual gas shut-off valve and   
					water at the inlet valve to the heater. Do not   
					put the heater in operation until it has been   
					thoroughly checked by a qualified gas   
					technician.   
					1. Open the inner door for at least 10 minutes   
					and force some fresh air into the   
					combustion chamber to clear any gas from   
					the water heater and vent system.   
					2 Check the vent terminal for blockage.   
					3. Follow the lighting instruction again.   
					SPECIAL NOTE ON PROPANE FUEL:   
					L.P. GAS IS HEAVIER THAN AIR   
					TAMPERING   
					Should there be a leak in the system, the gas will settle at   
					FLOOR LEVEL. Basements, crawl spaces, closets and   
					areas below ground level will serve as pockets for the   
					accumulation of the gas.   
					Tampering with the thermostat, gas valve or temperature   
					pressure relief valve is DANGEROUS and voids all   
					warranties. Only qualified personnel should service these   
					components.   
					BEFORE LIGHTING, SNIFF AT FLOOR LEVEL.   
					IF YOU SMELL GAS, FOLLOW THESE RULES.   
					1. Get all people out of the building.   
					BURNER MAINTENANCE   
					2. DO NOT light matches.   
					At least every 3 months, check the burner and pilot   
					flames. The burner flames must be a soft blue flame with   
					no yellow tips. Yellow tips indicate a carburizing flame   
					which can, depending on severity, deposit carbon (soot)   
					on the combustion chamber and flue passages.   
					3. DO NOT touch electrical switches (on or off).   
					4. DO NOT use an electrical fan to remove gas from   
					area.   
					5. SHUT OFF GAS at the L.P. tank outside of the   
					building.   
					6. IMMEDIATELY call the L.P. Gas Company or the fire   
					department from a neighbor’s phone. Ask for   
					instructions. Before hanging up, give your name,   
					address and telephone number.   
					A sheet metal burner is used on natural gas models. See   
					Figure 5.   
					7. DO NOT go back into the building. If help is coming,   
					wait for it outside the building.   
					OUT OF FUEL   
					When your L.P. tank runs out of fuel, turn off gas at all gas   
					appliances. After L.P. tank is refilled, all appliances must   
					be re-lit according to the manufacturers instructions.   
					WATER TEMPERATURE REGULATION   
					The thermostat is adjusted to its lowest temperature   
					position when shipped from the factory. The temperature   
					of the water can be selected by setting of the temperature   
					dial on the top of the gas control. See Figure 4.   
					The “LOW” position on the thermostat is the preferred   
					starting point for setting the temperature/control knob   
					(approximately 120°F (50°C)).   
					The lowest setting will maintain the minimum water   
					temperature if you are going away for an extended   
					period. The burner may be extinguished if operated   
					below this temperature.   
					Figure 5   
					The sheet metal burner for Natural Gas has no external   
					air adjustment. It is fully self-compensating and no   
					outside adjustment is required. Observe the flame   
					pattern. Ensure that no debris has fallen on top of the   
					burner and no foreign objects have been introduced into   
					the combustion chamber. Ensure that the vent terminal   
					openings are not obstructed and the inner door to the   
					combustion chamber is closed.   
					Energy conservation is a consideration when   
					selecting the water temperature setting.   
					HIGHER SETTING INCREASES   
					THE RISK OF SCALD INJURY   
					GAS CONTROL   
					For gas control replacement, contact your local gas utility,   
					or a qualified serviceman. The replacement control must   
					be an identical model to the control which has been   
					removed.   
					In households with children or invalids and/or elderly   
					persons, select a lower temperature setting. To reduce   
					the risk of scalding, valves for reducing the point of   
					discharge water temperature by mixing in branch water   
					lines are available. Please consult a licensed plumber or   
					plumbing authority.   
					– 9 –   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				MAINTENANCE INSTRUCTIONS -   
					GENERAL HOUSEKEEPING   
					CATHODIC PROTECTION   
					Depending on the model, one or two magnesium anodes   
					are factory installed inside the tank to provide corrosion   
					protection and to extend tank life. Permanent removal of   
					the anode(s) for any purpose will void the warranty. Read   
					the warranty attached to this water heater for a full   
					explanation of the time period that parts and the heater   
					are warranted.   
					It is advisable to inspect the condition of the anode(s) at   
					certain intervals. A 2 year period may be a guide to begin   
					with. The life of the anode depends on many factors and   
					can differ greatly from one location to another.   
					As a precaution against fire, and to maintain an adequate   
					flow of combustion air to the heater:   
					• 
					keep the appliance area clear and free from   
					combustible material, gasoline, and other flammable   
					vapours and liquids,   
					• 
					• 
					keep the terminal openings unobstructed   
					do not pile cartons, paper or combustible material on   
					top of the heater.   
					TANK   
					To remove an anode, proceed as follows:   
					Drain at least a pail of water from the drain valve once a   
					month. Some deposit will be washed out of the tank. If   
					larger particles, resembling a coarse sand are washed   
					out, or if the drain becomes clogged while draining, an   
					excess of lime deposit has settled on the tank bottom and   
					it is time to do a major tank cleaning. Consult your local   
					Gas Utility or a qualified serviceman.   
					1. Turn the gas off at the inlet to the heater.   
					2. Turn water off at the cold water inlet valve.   
					3. Open a nearby hot water tap.   
					4. Drain approximately one pail full of water from the   
					heater.   
					5. With a 1 1/16” hexagon socket wrench, loosen the   
					anode from the fitting in the tank top.   
					VENTING SYSTEM INSPECTION   
					NOTE: The anode has been factory installed using a   
					power tool. It will be necessary for a second person to   
					restrain the heater. A few sharp blows on the handle of   
					the socket wrench will loosen the anode nut.   
					Every 3 months, when inspecting the burner flame, an   
					inspection of the venting system should be made.   
					Check these points:   
					1. To make certain vent terminal is securely attached   
					and free of obstruction.   
					2. Inspect air pipe to make certain its components are   
					securely fastened, sealed and are in good condition.   
					3. To make certain inner door on water heater is securely   
					fastened.   
					If an impact wrench (power drive) is available, this is   
					an easy way to remove an anode.   
					6. Lift the anode up and inspect. There should be at least   
					3/8” to 1/2” of anode diameter left. The surface may be   
					rough, full of pits and crevices, but this is normal.   
					CORRECT ANY DEFECTS IMMEDIATELY.   
					If there is less than approximately 3/8” diameter left,   
					the anode needs to be replaced.   
					TEMPERATURE & PRESSURE RELIEF VALVE   
					7. Apply a good grade of pipe dope to the threads of the   
					anode adaptor and screw securely into the tank top.   
					8. Open the cold water inlet valve and fill tank.   
					9. Check for leaks.   
					10. Relight burner by following lighting instructions on   
					page 7.   
					The Temperature and Pressure Relief Valve (T&P valve)   
					is a part of the safety equipment on the water heater.   
					In order to keep the T&P valve functioning properly,   
					operate the valve at least once a year by lifting the   
					manual lever until water discharges from the overflow   
					pipe.   
					Water supply conditions may vary depending on the   
					region where this water heater is installed, and in some   
					cases the water may have an adverse effect on the   
					operation of the anode.   
					CAUTION   
					The water flowing from the valve will be HOT.   
					Keep hands and feet away from the stream of water.   
					Take care that the discharging water does not damage   
					any flooring, carpeting or other parts of the building   
					which may be damaged by water.   
					See also section on T&P valve in the installation   
					section.   
					If a sulphurous, or “rotten egg” smell is noticeable in the   
					hot water supplied by this heater, it is an indication that   
					the water source is not compatible with the magnesium   
					anode which is factory installed. Replace the anode to an   
					aluminum anode or a water treatment for removal of   
					sulphur from the water supply.   
					– 10 –   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				CONTROL   
					3. Do not use this heater as a replacement for an existing   
					boiler installation.   
					If the heater or the controls have been subjected to   
					flooding, shut off the gas at the manual shut-off valve to   
					the heater and call your gas company.   
					4. Do not introduce toxic chemicals such as those used   
					for boiler treatment into the potable water used for   
					space heating.   
					The heater operates under a fully automatic control.   
					Once the desired water temperature has been selected,   
					the gas control will maintain that temperature within close   
					limits.   
					5. If the space heating water system requires water with   
					temperatures in excess of 140°F, a mixing valve or   
					other means must be installed in the potable hot water   
					supply to temper the water and reduce scald hazard   
					potential.   
					DO NOT TAMPER WITH THE GAS CONTROL!   
					6. If the heater is installed with a back-flow preventer on   
					the incoming water line or in a closed system, a   
					diaphragm-type expansion tank must be installed in   
					the system to prevent weeping due to expansion.   
					CAUTION   
					Hydrogen gas can be produced in a hot water   
					system served by this heater that has not   
					been used for a long period of time (generally   
					two weeks or more). Hydrogen gas is   
					extremely flammable. To reduce the risk of   
					injury under these conditions, it is   
					recommended that the hot water faucet be   
					opened for several minutes at the kitchen sink   
					before using any electrical appliance. If   
					hydrogen is present, there will probably be an   
					unusual sound such as air escaping through   
					the pipe as the water begins to flow. There   
					should be no smoking or open flame near the   
					faucet at the time it is open.   
					7. Proper sizing of the water heater for the given space   
					and potable heating application is essential to ensure   
					adequate heating capacity. The sizing and installation   
					of such combination system must be performed by   
					qualified personnel and be in accordance with public   
					utility requirements and/or Codes having jurisdiction.   
					The sizing of the water heater should be based on the   
					design heat loss of the structure to be heated plus the   
					potable water requirements.   
					IT IS IMPORTANT THAT THE WATER HEATER USED   
					BE OVERSIZED TO ALLOW ADEQUATE HEATING   
					AND POTABLE WATER HEATING CAPACITY.   
					INSTALLATION INSTRUCTIONS FOR WATER   
					HEATERS APPROVED FOR SPACE HEATING AND   
					POTABLE WATER HEATING   
					CIRC. PUMP   
					CHECK VALVE   
					HOT   
					WATER   
					TO   
					When using this water heater in the application of a   
					combination space and potable water heating system, be   
					sure to follow instructions provided with the water heater   
					and the manual shipped with the air handler.   
					COLD TO   
					WATER HEATER   
					HOUSE   
					NOTE the following warnings:   
					DIRECT   
					VENT   
					WATER   
					HEATER   
					1. The piping and components connected to the water   
					heater for the space heating applications shall be   
					suitable for use with potable water. The system should   
					be installed with new non-ferrous piping. Do not use   
					pumps, valves, fittings, solder, gluing and pipe sealant   
					that are not completely compatible with potable water   
					piping.   
					AIR HANDLER   
					2. A water heater which will be used to supply potable   
					water must not be connected to any heating system or   
					components previously used with a non-potable water   
					heating appliance. Do not use: piping that has been   
					treated; broiler seal chromates; or other chemicals.   
					RADIATOR OR RADIANT FLOOR PIPING ARE   
					VIABLE ALTERNATIVES TO AIR HANDLER.   
					Figure 9   
					– 11 –   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				~ Certificate of Warranty ~   
					Warranty Code: P R S T U V W   
					Y 
					See Rating Label Serial Number prefix for   
					Warranty Code. Reduced warranty period   
					applies to Newfoundland.   
					Standard Warranty Years: 3 5 6 7 8 9 10 12   
					Reduced Warranty Years: 2 3 3 5 5 5   
					5 
					7 
					For its GSW and John Wood water heaters and storage boosters ("Unit"), GSW Water Heating ("GSW") warrants that, upon   
					receipt of a properly verified Warranty claim within the Warranty Period, it will, at its election, repair or replace: units which leak or parts which are defective   
					in material or workmanship, subject to the terms and conditions set forth in this certificate. GSW will not assume any expense or liability for unauthorized   
					returns, nor repairs made by a person who has not been authorized by GSW or one of its authorized dealers. GSW Units/parts must be replaced with GSW or   
					John Wood products to be eligible for Warranty. This Warranty is available to the original owner of a Unit installed within the boundaries of continental United   
					States, of Canada, or their territories. Consumers must retain point-of-sale proof of purchase to validate warranty entitlement. This Warranty does not   
					cover components not manufactured by GSW, such as oil burners, which carry the warranty given by the manufacturer thereof, copy of which warranty GSW   
					will make available, to the extent supplied by the manufacturer, without recourse to GSW.   
					THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. THIS EXPRESS   
					WARRANTY IS, WHERE PERMITTED BY LAW, IN LIEU OF AND EXCLUDES AND REPLACES ALL OTHER CONDITIONS,   
					WARRANTIES, GUARANTEES, REPRESENTATIONS, OBLIGATIONS OR LIABILITIES OF GSW OF ANY NATURE OR KIND,   
					EXPRESS OR IMPLIED, HOWEVER ARISING (WHETHER BY CONTRACT, CONDUCT, STATEMENT, STATUTE,   
					NEGLIGENCE, PRINCIPLES OF MANUFACTURER'S LIABILITY, OPERATION OF LAW OR OTHERWISE) WITH RESPECT   
					TO THE UNIT OR ITS FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, INSTALLATION, OPERATION,   
					REPAIR OR REPLACEMENT. GSW EXPRESSLY DISCLAIMS ANY AND ALL IMPLIED WARRANTIES. IN NO EVENT WILL   
					GSW'S LIABILITIES EXCEED THE COST OF THE DEFECTIVE PART(S) OR UNIT. GSW WILL NOT PAY FOR ANY   
					TRANSPORTATION, LABOUR, INSTALLATION, OR OTHER INCIDENTAL COSTS ASSOCIATED WITH THE REPAIR OR   
					REPLACEMENT OF A DEFECTIVE PART OR UNIT.   
					This warranty and GSW's obligations shall be construed and determined in accordance with the laws of both the Province of Ontario, and of Canada in force   
					therein. This Warranty does not affect specific legal rights of a consumer under applicable law, except to the extent that such rights may be waived or replaced,   
					and the provisions hereof are deemed to be amended to the extent necessary. The unenforceability of any provision, in whole or in part, of this Certificate shall   
					not affect the remaining provisions. Any and all repair and/or replacement of part(s) or Unit are the sole and exclusive remedy available against GSW.   
					LIABILITY OF GSW COVERED BY THIS WARRANTY IS CONDITIONAL UPON THE FOLLOWING:   
					1. The Unit shall be installed in accordance with all manufacturers' 7. A properly documented claim shall be received by GSW or one of its   
					instructions, all applicable equipment and building codes, ordinances and   
					regulations (hereinafter referred to as the "standards").   
					authorized dealers, or point of purchase, within the following Warranty   
					Period, except as provided otherwise below*:   
					2. The Unit must not be installed where water damage can result from a   
					leak, while provision(s) shall be made for directing any water escaping   
					from the Unit, to a properly operating drainpipe. As all units of this type   
					may eventually leak, you must protect against any potential water   
					damage. GSW accepts no responsibility for such damage, nor any   
					incidental or consequential loss, nor damage(s) related thereto, suffered   
					by the owner of the Unit nor by any third party.   
					3. The Unit shall not be installed where it will be exposed to adverse or   
					unusual environmental or corrosive conditions. No warranty extends, for   
					example, and without limitation of the foregoing, to Units exposed to:   
					salts; chemicals; exhausts; pollutants or contaminants. Further, no   
					warranty extends to Units affected by fire, freezing or flood, "Acts of   
					God", or any other contingency beyond the control of GSW.   
					a) for any defective part, within one (1) year; or   
					b) for any Unit that develops leaks in the inner tank due to rust, corrosion   
					or other chemical reactions caused by the potable domestic water   
					supplied to your home, within the period of time shown in table at the top   
					of this page.   
					* Residential units installed and used in a commercial application carry a   
					warranty period of one (1) year from date of installation; and,   
					Any repair or replacement of any part, tank, or Unit under this Warranty   
					will not extend the Warranty Period beyond that calculated from the date   
					of first installation of the original Unit. The date of first installation will   
					be deemed to be the later of the date indicated by the Unit's serial number,   
					or if supplied with the Warranty claim, the sales receipt, or installer's   
					receipt.   
					4. The Unit shall be equipped with a properly operating temperature and 8. A claim under this Warranty must include the model and serial number of   
					pressure relief valve as specified by GSW and applicable standards. The   
					Unit shall be operated at temperatures not exceeding the maximum   
					setting of the thermostat and/or high limit control provided by GSW, and   
					at water pressures not exceeding the pressure reading stated on the Unit.   
					5. The Unit must be carefully inspected, maintained, and operated in   
					accordance with the manufacturer's instructions. No warranty extends,   
					for example, and without limitation of the foregoing, to any Unit   
					operated: without the tank being completely filled with water; without an   
					operating anode; with levels of sediment or lime precipitate which cause   
					failure; in connection to any attachment(s), energy saving device(s), or   
					other means of heating, except as approved by GSW for the Unit; other   
					the Unit, proof of date on which the Unit was first installed, and the   
					identity of the defective part(s) for which a claim is being made and be   
					submitted within 15 days following discovery of the defect(s), by   
					personal delivery to a GSW authorized dealer, point of purchase, or GSW   
					itself at:   
					GSW Water Heating   
					A GSW Company   
					599 Hill Street West   
					Fergus, ON Canada N1M 2X1   
					Should you have questions, please call our Technical Support Line at 1-   
					888-479-8324.   
					than with potable water without any additives such as salts, chlorine or 9. If requested by GSW, information relating to the purchase, transportation,   
					chemicals, except those added for the sole purpose of rendering the water   
					fit for domestic use.   
					6. All repairs must be made by a competent and qualified person who is   
					certified, by GSW or one of its authorized dealers, to work on the Unit,   
					using factory approved replacement parts, and the Unit shall not be   
					otherwise modified, altered or improperly repaired.   
					operation and installation of the Unit must be supplied. The defective   
					part(s) or Unit, with all components properly and securely packed, shall   
					be returned transportation pre-paid, to the address designated by GSW in   
					the written request. All claims are subject to validation by GSW.   
					Download from Www.Somanuals–.co1m2. A–ll Manuals Search And Download.   
				 |