Goodman Mfg Air Conditioner SS CPH90 150 User Manual

CPH CommerCial  
7½- to 12½-ton Self-Contained  
PaCkaged Heat PumP  
Cooling / Heating CaPaCitieS:  
up to 11.5 EER  
up to 3.5 Cop  
90,000 — 118,000 Btu/H  
Standard Features  
• R-410A chlorine-free refrigerant  
• High-efficiency scroll compressor  
• Copper tube / aluminum fin coils  
• Contactor with lugs  
• High-capacity, steel-cased filter dryer  
• Single-point entry  
• 24-volt terminal strip  
• Convertible  
• Easy to service  
• Built-in filter rack with standard 2lters  
• Bottom utility entry  
• AHRI Certified; ETL Listed  
Contents  
Cabinet Features  
Nomenclature.............................................................................................2  
Product Specifications...........................................................................3  
Expanded Heating Data ......................................................................7  
Expanded Cooling Data........................................................................8  
Airflow Data............................................................................................... 16  
Heat Kit Electrical Data ...................................................................... 20  
Dimensions................................................................................................ 24  
Wiring Diagrams .................................................................................... 28  
Accessories ............................................................................................... 34  
• Heavy-gauge, galvanized-steel cabinet with  
UV-resistant powder-paint finish  
• Full Perimeter Rail  
• Curb Fit  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6/11  
Supersedes 3/11  
ProduCt SPeCifiCationS  
ProduCt SPeCifiCationS — 7½ tonS  
CPH090  
***3B***  
CPH090  
***4B***  
CPH090  
***7B***  
Cooling Capacity  
Total BTU/h  
Sensible BTU/h  
EER / IEER  
IPLV  
90,000  
65,700  
11.5 / 11.2  
12.30  
90,000  
65,700  
11.5 / 11.2  
12.30  
90,000  
65,700  
11.5 / 11.2  
12.30  
Decibels  
83  
83  
83  
AHRI Reference #s  
3000984  
3000984  
3000984  
Heating Capacity  
BTU/h / COP (47° F)  
BTU/h / COP (17° F)  
Evaporator Motor / Coil  
Motor Type  
Indoor Nominal CFM  
Indoor Motor FLA (Cooling)  
Horsepower - RPM  
Piston Size (Cooling)  
Filter Size  
Drain Size (NPT)  
90,000 / 3.5  
55,500 / 2.4  
90,000 / 3.5  
55,500 / 2.4  
90,000 / 3.5  
56,500 / 2.4  
Belt Drive  
3,000  
7.8  
2.0 - 1725  
0.076  
Belt Drive  
3,000  
3.9  
2.0 - 1725  
0.076  
Belt Drive  
3,000  
2.5  
2.0 - 1725  
0.078  
16" x 24" x 2"  
¾"  
16" x 24" x 2"  
¾"  
16" x 24" x 2"  
¾"  
R-410A Refrigerant Charge: Cir #1 / #2 (oz.)  
Evaporator Coil Face Area (ſt²)  
Rows Deep / Fins per Inch  
Belt Drive Evap Fan Data  
# of Wheels (D x W)  
Motor Sheave / Blower Sheave  
Belt  
215 / 215  
10.2  
4 / 16  
215 / 215  
10.2  
4 / 16  
200 / 200  
10.2  
4 / 16  
1 (15" x 12")  
VL40 / AK74  
AX51  
1 (15" x 12")  
VL40 / AK74  
AX51  
1 (15" x 12")  
VL40 / AK74  
AX51  
Condenser Fan / Coil  
Quanꢀty of Condenser Fan Motors  
Horsepower - RPM  
Fan Diameter / # Fan Blades  
Outdoor Expansion Device  
Outdoor Nominal CFM  
Face Area (ſt²)  
2
2
2
¼ - 1090  
22 / 4  
0.052  
7,600  
32.4  
¼ - 890  
22 / 4  
0.052  
7,600  
32.4  
¼ - 1075  
22 / 4  
0.055  
7,600  
32.4  
# Coils / Rows Deep - Fins per Inch  
Piston Size (Heaꢀng)  
Compressor  
2 / 2 - 20  
0.052  
2 / 2 - 20  
0.052  
2 / 2 - 20  
0.055  
Quanꢀty / Type / Stage  
Compressor RLA / LRA  
Electrical Data  
2 / Scroll / 1  
13.1 / 83.1  
2 / Scroll / 1  
6.1 / 41.0  
2 / Scroll / 1  
4.4 / 33.0  
Voltage / Phase / Frequency  
Indoor Blower HP / FLA  
Outdoor Fan HP / FLA  
Total Unit Amps  
208-230 / 3 / 60  
460 / 3 / 60  
1.5 / 2.5  
¼ / 0.8  
17.7  
575 / 3 / 60  
2 / 2.5  
¼ / 0.6  
12.5  
1.5 / 5.0  
¼ / 1.4  
36.9  
Min. Circuit Ampacity¹  
Max. Overcurrent Protecꢀon (amps)²  
Entrance Power Supply & Control Voltage  
Operating Weight (lbs)  
Ship Weight (lbs)  
40  
50  
19  
25  
13.6  
15  
Locaꢀng Dimple  
1135  
1135  
1175  
1135  
1175  
1175  
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
²
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3
ProduCt SPeCifiCationS  
ProduCt SPeCifiCationS — 8½ tonS  
CPH102  
***3B***  
CPH102  
***4B***  
CPH102  
***7B***  
Cooling Capacity  
Total, BTU/h  
Sensible BTU/h  
102,000  
73,440  
102,000  
73,440  
102,000  
73,440  
EER / IEER  
Decibels  
11.1 / 11.2  
83  
11.1 / 11.2  
83  
11.1 / 11.2  
83  
ARI Reference #s  
3620224  
3620224  
3620224  
Heating Capacity  
BTU/h (47°F)  
COP (47°F)  
102,000  
3.4  
102,000  
3.4  
102,000  
3.4  
BTU/h (17°F)  
COP (17°F)  
55,500  
2.25  
55,500  
2.25  
55,500  
2.25  
Evapoartor Motor / Coil  
Motor Type  
Belt Drive  
3,400  
7.8  
1725  
Belt Drive  
3,400  
3.9  
1725  
Belt Drive  
3,400  
2.3  
1725  
Indoor Nominal CFM  
Indoor Motor FLA (Cooling)  
Horsepower - RPM  
Piston Size (Cooling)  
Filter Size (Qty)  
0.08  
(4) 16” x 24” x 2”  
3/4”  
0.08  
(4) 16” x 24” x 2”  
3/4”  
0.08  
(4) 16” x 24” x 2”  
3/4”  
Drain Size (NPT)  
R-410A Refrigerant Charge Cir #1 & #2 (oz.)  
Evaporator Coil Face Area (ſt²)  
Rows Deep / Fins per Inch  
Belt Drive Evap Fan Data  
# of Wheels (D x W)  
Motor Sheave / Blower Sheave  
Belt  
205 / 205  
10.2  
4 / 14  
205 / 205  
10.2  
4 / 14  
205 / 205  
10.2  
4 / 14  
1 (15” x 12”)  
VL40 / AK74  
AX51  
1 (15” x 12”)  
VL40 / AK74  
AX51  
1 (15” x 12”)  
VL40 / AK74  
AX51  
Condenser Fan / Coil  
Quanꢀty of Condenser Fan Motors  
Horsepower - RPM  
Fan Diameter / # Fan Blades  
Outdoor Nominal CFM  
Face Area (ſt²)  
2
1/4” - 1,090  
22 / 4  
2
2
1/4” - 1,075  
22 / 4  
1/4” - 890  
22 / 4  
7,600  
7,600  
16.19  
7,600  
16.19  
16.19  
Rows Deep / Fins per Inch  
Piston Size (Heaꢀng)  
Compressor  
2 / 22  
0.059  
2 / 22  
0.059  
2 / 22  
0.059  
Quanꢀty / Type  
Stage  
2 / Scroll  
1
2 / Scroll  
1
2 / Scroll  
1
Compressor RLA / LRA ea.  
Electrical Data / Static  
Voltage / Phase / Frequency  
Standard Max Staꢀc  
Outdoor Fan FLA ea.  
Total Unit Amps  
14.5 / 98  
6.3 / 55  
6.0 / 41  
230 / 3 / 60  
460 / 3 / 60  
575 / 3 / 60  
1”  
1.4  
39.6  
1
0.8  
18.1  
1
0.6  
15.5  
Min. Circuit Ampacity¹  
Max. Overcurrent Protecꢀon (amps)²  
Entrance Power Supply & Control Voltage  
Operating Weight (lbs)  
Ship Weight (lbs)  
43.2  
50  
Locaꢀng Dimple  
1285  
19.7  
25  
Locaꢀng Dimple  
1285  
17  
20  
Locaꢀng Dimple  
1285  
1310  
1310  
1310  
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
²
4
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ProduCt SPeCifiCationS  
ProduCt SPeCifiCationS — 10 tonS  
CPH120  
***3B***  
CPH120  
***4B***  
CPH120  
***7B***  
Cooling Capacity  
Total BTU/h  
Sensible BTU/h  
EER / IEER  
Decibels  
118,000  
87,300  
11.5 / 11.5  
83  
118,000  
87,300  
11.5 / 11.5  
83  
118,000  
87,300  
11.5 / 11.5  
83  
Heating Capacity  
BTU/h (47° F)  
COP (47°F)  
120,000  
3.4  
120,000  
3.4  
120,000  
3.4  
BTU/h (17° F)  
COP (17°F)  
56,000  
2.4  
56,000  
2.4  
56,000  
2.4  
Evaporator Motor / Coil  
Motor Type  
Indoor Nominal CFM  
Indoor motor FLA (Cooling)  
Horsepower - RPM  
Belt Drive  
4,000  
7.8  
2.0/1725  
0.086  
Belt Drive  
4,000  
3.9  
2.0/1725  
0.086  
Belt Drive  
4,000  
2.5  
2.0/1725  
0.086  
Piston Size (Cooling)  
Expansion Device  
Orifice  
Orifice  
Orifice  
Filter Size  
Drain Size (NPT)  
(4) 16" x 24" x 2"  
¾"  
(4) 16" x 24" x 2"  
¾"  
(4) 16" x 24" x 2"  
¾"  
R-410A Refrigerant Charge Cir #1 & #2 (oz.)  
Evaporator Coil Face Area (ſt²)  
Rows Deep/ Fins per Inch  
Belt Drive Evap Fan Data  
# of Wheels (D x W)  
Motor Sheave / Blower Sheave  
Belt  
225 / 225  
10.2  
4 / 14  
225 / 225  
10.2  
4 / 14  
225 / 225  
10.2  
4 / 14  
(1) 15" x 15"  
VL40 / AK74  
AX51  
(1) 15" x 15"  
VL40 / AK74  
AX51  
(1) 15" x 15"  
VL40 / AK74  
AX51  
Condenser Fan / Coil  
Quanꢀty of Condenser Fan Motors  
Horsepower - RPM  
Fan Diameter / # Fan Blades  
Outdoor Nominal CFM  
Face Area (ſt²)  
2
2
2
⅓ - 1,075  
22 / 3  
7,200  
⅓ - 1,075  
22 / 3  
7,200  
⅓ - 1,125  
22 / 3  
7,200  
32.4  
32.4  
32.4  
# Coils / Rows Deep - Fins per Inch  
Piston Size (Heaꢀng)  
Compressor  
2 / 2 - 22  
0.064  
2 / 2 - 22  
0.064  
2 / 2 - 22  
0.064  
Quanꢀty / Type / Stage  
Compressor RLA / LRA ea.  
Electrical Data  
2 / Scroll / 1  
16 / 110.0  
2 / Scroll / 1  
7.8 / 52.0  
2 / Scroll / 1  
5.7 / 38.9  
Voltage/Phase/ Frequency  
Belt-Driven Standard Max Staꢀc  
Outdoor Fan RLA ea.  
Total Unit Amps  
208-230/3/60  
460/3/60  
1.4  
1.20  
575/3/60  
1.4  
0.90  
16  
1.4  
2.40  
45  
22  
Min. Circuit Ampacity¹  
Max. Overcurrent Protecꢀon (amps)²  
Entrance Power Supply & Control Voltage  
Operating Weight (lbs)  
Ship Weight (lbs)  
49  
60  
24  
30  
17  
20  
Locaꢀng Dimple  
1285  
1285  
1310  
1285  
1310  
1310  
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
²
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
ProduCt SPeCifiCationS  
ProduCt SPeCifiCationS — 12½ tonS  
CPH150XXX  
3BXXX  
CPH150XXX  
4BXXX  
CPH150XXX  
7BXXX  
Cooling Capacity  
Total, BTU/h  
Sensible BTU/h  
EER / IPLV  
Decibels  
146,000  
102,200  
10.8 / 11.2  
83  
146,000  
102,200  
10.8 / 11.2  
83  
146,000  
102,200  
10.8 / 11.2  
83  
ARI Reference #s  
3554114  
3554114  
3554114  
Heating Capacity  
BTU/hr (47°F)  
COP (47°F)  
150,000  
3.2  
150,000  
3.2  
150,000  
3.2  
BTU/hr (17°F)  
COP (17°F)  
82,000  
2.1  
82,000  
2.1  
82,000  
2.1  
Evapoartor Motor / Coil  
Motor Type (Belt Drive)  
Indoor Nominal CFM  
Indoor Motor FLA (Cooling)  
Horsepower - RPM  
Piston Size (Cooling)  
Filter Size (Qty)  
AX49  
5,000  
9.4  
AX49  
5,000  
4.7  
AX49  
5,000  
4.2  
3.0 - 1,725  
0.096  
(4) 20" x 25" x 2"  
¾"  
3.0 - 1,725  
0.096  
(4) 20" x 25" x 2"  
¾"  
3.0 - 1,725  
0.096  
(4) 20" x 25" x 2"  
¾"  
Drain Size (NPT)  
R-410A Refrigerant Charge Cir #1 & #2 (oz.)  
Evaporator Coil Face Area (ſt²)  
Rows Deep / Fins per Inch  
# of Wheels (D x W)  
Motor Sheave / Blower Sheave  
Condenser Fan / Coil  
Quanꢀty of condenser Fan Motors  
Horsepower - RPM  
Fan Diameter / # Fan Blades  
Outdoor Nominal CFM  
Face Area (ſt²)  
290 / 290  
14.7  
4 / 15  
(1) 15" x 15"  
VL40 / AK66  
290 / 290  
14.7  
4 / 15  
(1) 15" x 15"  
VL40 / AK66  
290 / 290  
14.7  
4 / 15  
(1) 15" x 15"  
VL40 / AK66  
2
⅓ - 1,075  
22/ 3  
7,200  
35.3  
2
⅓ - 1,075  
22/ 3  
7,200  
35.3  
2
⅓ - 1,075  
22/ 3  
7,200  
35.3  
Rows Deep / Fins per Inch  
Piston Size (Heaꢀng)  
Compressor  
2/3 rows 15 fpi  
0.067  
2/3 rows 15 fpi  
0.067  
2/3 rows 15 fpi  
0.067  
Quanꢀty / Stage  
Type  
2 / Single  
Scroll  
2 / Single  
Scroll  
2 / Single  
Scroll  
Compressor RLA / LRA ea.  
Electrical Data / Static  
Voltage / Phase / Frequency  
Standard Max Staꢀc  
Outdoor Fan FLA ea.  
Total Unit Amps  
Min. Circuit Ampacity¹  
Max. Overcurrent Protecꢀon (amps)²  
Entrance Power Supply  
Entrance Control Voltage  
Operating Weight (lbs)  
Ship Weight (lbs)  
22.4 / 149  
10.6 / 75  
7.7 / 54  
208-230/ 3/ 60  
460/ 3/ 60  
575/ 3/ 60  
1.4"  
0.9  
21.4  
23  
30  
Locaꢀng  
Dimple  
1.4"  
2.4  
59  
65  
80  
Locaꢀng  
Dimple  
1325  
1350  
1.4"  
1.2  
28  
31  
40  
Locaꢀng  
Dimple  
1325  
1350  
1325  
1350  
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
²
6
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ProduCt SPeCifiCationS  
exPanded Heating data  
CPH090  
Outdoor Ambient Temperature  
35 30 25 20  
65  
60  
55  
50  
47  
45  
40  
17  
15  
10  
5
0
-5  
32.2 26.4  
9.9 8.2  
-10  
MBh  
T/R  
114.4 108.3 101.9 95.3  
35.3 33.4 31.5 29.4  
8.22 8.06 7.91 7.75  
30.2 28.4 26.9 25.6  
4.07 3.93 3.77 3.60  
91.0 88.2 81.9 75.5  
28.1 27.2 25.3 23.3  
7.66 7.59 7.44 7.29  
24.9 24.5 23.4 22.5  
3.48 3.40 3.22 3.03  
70.5 65.0 59.9 56.6  
21.7 20.1 18.5 17.5  
6.93 6.78 6.63 6.54  
21.8 21.1 20.3 20.0  
2.98 2.81 2.64 2.53  
54.5 48.9 43.3 37.8  
16.8 15.1 13.4 11.7  
6.49 6.33 6.19 6.04  
19.8 19.1 18.2 17.4  
2.46 2.26 2.05 1.83  
kW  
5.89 5.74  
16.5 15.4  
1.60 1.35  
Amps  
COP  
HI PR  
LO PR  
424  
134  
406  
124  
390  
117  
373  
107  
365  
101  
358  
97  
344  
89  
330  
80  
316  
72  
302  
64  
290  
56  
283  
52  
278  
51  
267  
43  
257  
37  
246  
31  
238  
27  
229  
21  
CPH102  
Outdoor Ambient Temperature  
35 30 25 20  
65  
60  
55  
50  
47  
45  
40  
17  
15  
10  
5
0
-5  
-10  
MBh  
T/R  
128.2 121.4 114.2 106.8 102.0 98.8 91.8 84.7  
69.2 63.8 58.8 55.5  
18.8 17.4 16.0 15.1  
53.4 48.0 42.5 37.1  
14.6 13.1 11.6 10.1  
31.6 25.9  
34.9 33.1 31.1 29.1  
9.34 9.17 8.99 8.82  
37.6 35.2 33.2 31.6  
4.02 3.87 3.72 3.54  
13.7 13.2 12.7 12.1  
27.8 26.9 25.0 23.1  
8.72 8.64 8.48 8.30  
30.6 30.1 28.7 27.5  
3.42 3.35 3.17 2.98  
11.7 11.4 10.8 10.2  
8.6  
6.7  
7.1  
6.5  
kW  
7.8  
7.7  
7.5  
7.4  
7.3  
7.2  
7.0  
6.9  
Amps  
COP  
EER  
26.6 25.6 24.6 24.2  
23.9 23.0 21.8 20.8  
19.6 18.2  
2.6  
8.8  
2.4  
8.3  
2.3  
7.8  
2.2  
7.5  
2.1  
7.3  
2.0  
6.7  
1.8  
6.1  
1.6  
5.4  
1.4  
4.7  
1.2  
4.0  
HI PR  
LO PR  
419  
136  
401  
126  
386  
118  
369  
108  
360  
103  
354  
99  
340  
91  
326 312.5 298.4 286.5 279.7 274.6 264.2 254.1 243.6 235.0 226.7  
81  
73  
65  
57  
53  
51  
43  
37  
32  
28  
22  
CPH120  
Outdoor Ambient Temperature  
35 30 25 20  
65  
60  
55  
50  
47  
45  
40  
17  
15  
10  
5
0
-5  
-10  
MBh  
T/R  
150.8 142.8 134.4 125.6 120.0 116.3 108.0 99.6  
34.9 33.1 31.1 29.1 27.8 26.9 25.0 23.1  
10.70 10.50 10.31 10.11 10.00 9.92 9.73 9.54  
87.7 81.0 74.6 70.4  
20.3 18.7 17.3 16.3  
8.65 8.47 8.30 8.20  
30.2 29.3 28.3 27.8  
2.97 2.80 2.63 2.51  
67.8 60.8 53.9 47.0  
15.7 14.1 12.5 10.9  
8.13 7.95 7.78 7.61  
27.6 26.6 25.4 24.4  
2.44 2.24 2.03 1.81  
40.1 32.9  
9.3 7.6  
kW  
7.44 7.27  
23.3 21.8  
1.58 1.32  
Amps  
COP  
41.3 38.9 36.9 35.3  
4.13 3.98 3.82 3.64  
34.3 33.8 32.4 31.2  
3.51 3.43 3.25 3.06  
HI PR  
LO PR  
439  
133  
421  
123  
405  
115  
387  
106  
378  
100  
371  
96  
356  
89  
342  
79  
328  
71  
313  
64  
301  
56  
293  
52  
288  
50  
277  
42  
266  
37  
256  
31  
246  
27  
238  
21  
CPH150  
Outdoor Ambient Temperature  
65  
60  
55  
50  
47  
45  
40  
35  
30  
25  
20  
17  
15  
10  
5
0
-5  
-10  
MBh 188.6 178.5 168.0 157.1 150.0 145.4 135.0 124.5 102.2 94.3  
86.8  
19.1  
82.0  
18.1  
79.0  
17.4  
70.8  
15.6  
62.8  
13.8  
54.8  
12.1  
46.7 38.3  
10.3 8.4  
T/R  
KW  
41.6 39.4  
37.0  
34.6  
33.1  
32.0  
29.8  
27.4  
22.5  
20.8  
14.59 14.30 14.00 13.71 13.54 13.42 13.13 12.84 12.18 11.89 11.62 11.45 11.34 11.05 10.78 10.50 10.21 9.94  
AMPS 58.8 55.0  
52.0  
3.51  
434  
113  
49.3  
3.35  
415  
103  
47.8  
3.24  
405  
98  
47.0  
3.17  
398  
94  
44.8  
3.01  
382  
86  
42.9  
2.84  
367  
77  
41.4  
2.46  
351  
69  
39.9  
2.32  
336  
62  
38.3  
2.19  
322  
54  
37.6  
2.10  
315  
51  
37.2  
2.04  
309  
49  
35.7  
1.88  
297  
41  
33.8  
1.71  
286  
36  
32.3  
1.53  
274  
30  
30.4 28.1  
1.34 1.13  
COP  
HI PR  
LO PR  
3.78 3.65  
471  
129  
452  
120  
264  
26  
255  
21  
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.  
High pressure measured at liquid line access fitting; Low pressure measured at compressor suction access fitting.  
Amps = unit amps (comp.+fans)  
kW = Total system power  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
ProduCt SPeCifiCationS  
exPanded Cooling data — 7½ tonS  
8
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ProduCt SPeCifiCationS  
exPanded Cooling data — 7½ tonS (Cont.)  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9
ProduCt SPeCifiCationS  
exPanded Cooling data — 8½ tonS  
10  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ProduCt SPeCifiCationS  
exPanded Cooling data — 8½ tonS (Cont.)  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
ProduCt SPeCifiCationS  
exPanded Cooling data — 10 tonS  
12  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ProduCt SPeCifiCationS  
exPanded Cooling data — 10 tonS (Cont.)  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13  
ProduCt SPeCifiCationS  
exPanded Cooling data — 12½ tonS  
14  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ProduCt SPeCifiCationS  
exPanded Cooling data — 12½ tonS (Cont.)  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15  
ProduCt SPeCifiCationS  
airflow data — 7½ tonS  
Standard Belt Drive — Down Shot  
Turns Open  
ESP, In  
0
1
2
3
4
5
H2O  
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
3617 704 1.07 3293 653 0.84  
0.1  
0.3  
0.5  
0.7  
0.9  
1.1  
3541 749 1.15 3179 704 0.88 2757 656 0.66  
3447 798 1.23 3049 754 0.94 2606 710 0.71  
3400 848 1.33 2950 798 1.01 2474 754 0.75  
3303 890 1.41 2871 848 1.11 2408 804 0.82  
2838 897 1.23  
High-Static Belt Drive — Down Shot (A Models only)  
Turns Open  
ESP, In  
H2O  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
3401 909 1.51  
0.9  
1.1  
1.3  
1.5  
1.7  
1.9  
2.1  
3428 965 1.71 2943 915 1.3  
3471 1015 1.9 3012 971 1.5 2423 920 1.12  
3722 1063 2.25 3041 1023 1.67 2503 976 1.31  
3359 1075 2.04 2540 1031 1.5  
3381 1119 2.22 2890 1080 1.78  
3089 1129 2.04  
Standard Belt Drive — Horizontal  
Turns Open  
ESP, In  
H2O  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
3625 701 1.08 3309 660 0.86  
3815 797 1.44 3468 747 1.11 3177 703 0.88 2796 663 0.68  
3780 841 1.52 3405 803 1.23 3053 753 0.94 2608 709 0.68 2225 665 0.53  
3687 885 1.6 3327 847 1.29 2968 805 1.02 2423 758 0.73  
3236 891 1.39 2850 852 1.1 2352 807 0.8  
0.1  
0.3  
0.5  
0.7  
0.9  
1.1  
2713 896 1.17  
High-Static Belt Drive — Horizontal (A Models only)  
Turns Open  
ESP, In  
H2O  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
0.9  
1.1  
1.3  
1.5  
1.7  
1.9  
2.1  
3447 902 1.54  
3398 956 1.65 3006 908 1.31  
3486 1008 1.87 2960 962 1.44  
3514 1057 2.07 2949 1019 1.62  
3388 1103 2.18 3036 1069 1.84  
2959 1114 2.0  
2527 1124 1.86  
Notes :  
Assume dry coil with filter in place; CFM correction for wet coil = 3%  
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that exceed the above  
could require a larger motor. Minimum rated SCFM is 350 per ton.  
16  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ProduCt SPeCifiCationS  
airflow data — 8½ tonS  
Standard Belt Drive — Down Shot  
Turns Open  
ESP, In  
0
1
2
3
4
5
H2O  
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
3467 701 1.04 3143 650 0.81  
0.1  
0.3  
0.5  
0.7  
0.9  
1.1  
3391 746 1.12 3029 701 0.85 2607 653 0.63  
3297 795 1.20 2899 751 0.91 2456 707 0.68  
3250 845 1.30 2800 795 0.98  
3153 887 1.38 2721 845 1.08  
2688 894 1.20  
High-Static Belt-Drive — Down Shot  
Turns Open  
ESP, In  
H2O  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
0.9  
1.1  
1.3  
1.5  
1.7  
1.9  
2.1  
3251 906 1.48  
3278 962 1.68 2793 912 1.27  
3321 1012 1.87 2862 968 1.47  
3572 1060 2.22 2891 1020 1.64  
3209 1072 2.01  
3231 1116 2.19 2740 1077 1.75  
3256 1156 2.31 2939 1126 2.01  
Standard Belt Drive — Horizontal  
Turns Open  
ESP, In  
H2O  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
3475 698 1.05 3159 657 0.83  
3665 794 1.41 3318 744 1.08 3027 700 0.85 2646 660 0.65  
3630 838 1.49 3255 800 1.2 2903 750 0.91 2458 706 0.65  
3537 882 1.57 3177 844 1.26 2818 802 0.99  
3086 888 1.36 2700 849 1.07  
0.1  
0.3  
0.5  
0.7  
0.9  
1.1  
2563 893 1.14  
High-Static Belt-Drive — Horizontal  
Turns Open  
ESP, In  
H2O  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
3297 899 1.51  
0.9  
1.1  
1.3  
1.5  
1.7  
1.9  
3248 953 1.62 2856 905 1.28  
3336 1005 1.84 2810 959 1.41  
3364 1054 2.04 2799 1016 1.59  
3238 1100 2.15 2886 1066 1.81  
3188 1146 2.23 2809 1111 1.97  
Notes :  
Assume dry coil with filter in place; CFM correction for wet coil = 3%  
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that exceed the above could  
require a larger motor. Minimum rated SCFM is 350 per ton.  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17  
ProduCt SPeCifiCationS  
airflow data — 10 tonS  
Standard Belt Drive — Down shot  
Turns Open  
ESP, In  
0
1
2
3
4
5
H2O  
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
4629 774 1.76 4269 733 1.42  
0.2  
0.4  
0.6  
0.8  
1
4539 824 1.86 4198 781 1.53 3797 735 1.21  
4511 868 2.01 4103 829 1.63 3752 787 1.33 3312 745 1.03  
4445 912 2.14 4144 873 1.81 3695 833 1.45 3180 790 1.07  
4418 956 2.3 4073 917 1.92 3661 879 1.55  
4064 967 2.09 3518 923 1.6  
1.2  
1.4  
3555 972 1.77  
High-Static Belt Drive — Down shot  
Turns Open  
ESP, In  
H2O  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
4681 937 2.38 4206 891 1.91  
0.8  
1
4634 985 2.57 4288 948 2.19 3721 897 1.63  
4533 1020 2.63 4367 995 2.41 3845 954 1.91  
4550 1064 2.83 4290 1042 2.56 3913 1006 2.13  
4327 1087 2.73 3990 1057 2.37  
1.2  
1.4  
1.6  
1.8  
2
4652 1148 3.33 4023 1105 2.58  
4306 1162 3.05  
Standard Belt Drive — Horizontal  
Turns Open  
ESP, In  
H2O  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
4707 724 1.62  
0.2  
0.4  
0.6  
0.8  
1
4679 774 1.78 4235 730 1.4  
4595 822 1.91 4223 780 1.55 3679 735 1.16  
4468 862 1.96 4121 824 1.64 3596 785 1.26  
4349 907 2.06 3990 868 1.72 3463 829 1.31  
4486 962 2.35 3923 918 1.84 3267 879 1.33  
3990 967 2.03  
1.2  
1.4  
High-Static Belt Drive — Horizontal  
Turns Open  
ESP, In  
H2O  
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP  
4604 886 2.15  
0.8  
1
4737 940 2.48 4236 890 1.93  
1.2  
1.4  
1.6  
1.8  
2
4792 984 2.69 4347 946 2.19 3675 901 1.64  
4431 998 2.46 4404 995 2.45 3710 956 1.82  
4652 1061 2.93 4183 1028 2.42 3845 1006 2.08  
4418 1083 2.81 3847 1050 2.22  
4823 1149 3.5 4055 1105 2.6  
18  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ProduCt SPeCifiCationS  
airflow data — 12½ tonS  
Standard Belt Drive --- Down Shot  
Turns Open  
ESP (in  
0
1
2
3
4
5
W.C.)  
CFM  
BHP  
CFM  
BHP  
CFM  
5378  
4750  
4488  
4019  
BHP  
2.35  
1.97  
1.81  
1.55  
CFM  
4967  
4583  
4258  
BHP  
1.92  
1.71  
1.54  
CFM  
4710  
4319  
BHP  
1.59  
1.40  
CFM  
4512  
4030  
BHP  
1.33  
1.13  
0.2  
0.4  
0.6  
0.8  
1.0  
5514  
5204  
4830  
4497  
2.92  
2.69  
2.42  
2.19  
5349  
4919  
4649  
4264  
2.56  
2.27  
2.09  
1.86  
High-Static Belt Drive --- Down Shot  
Turns Open  
ESP (in  
W.C.)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
5978  
5656  
5459  
4844  
4404  
BHP  
3.87  
3.58  
3.40  
2.88  
2.54  
CFM  
5691  
5376  
4950  
4525  
BHP  
3.38  
3.12  
2.79  
2.45  
CFM  
5324  
4933  
4441  
BHP  
2.81  
2.52  
2.18  
0.8  
1.0  
1.2  
1.4  
1.6  
1.8  
2.0  
2.2  
5947  
5708  
5245  
4894  
4495  
4142  
4.16  
3.93  
3.48  
3.17  
2.83  
2.55  
5776  
5465  
5145  
4805  
4429  
4.64  
4.30  
3.97  
3.63  
3.27  
5510  
5199  
4871  
4565  
4233  
4.07  
3.74  
3.41  
3.13  
2.85  
Standard Belt Drive --- Horizontal  
Turns Open  
ESP (in  
W.C.)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
5570  
4902  
4603  
4393  
BHP  
2.27  
1.88  
1.72  
1.61  
CFM  
4935  
4637  
4341  
BHP  
1.70  
1.55  
1.41  
CFM  
4584  
4178  
BHP  
1.36  
1.19  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
5871  
5610  
5391  
5078  
4521  
3.20  
3.00  
2.83  
2.59  
2.20  
5639  
5358  
5010  
4676  
4226  
2.77  
2.57  
2.33  
2.11  
1.83  
5307  
5051  
4799  
4448  
2.31  
2.15  
2.00  
1.79  
High-Static Belt Drive --- Horizontal  
Turns Open  
ESP (in  
W.C.)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
5858  
5502  
5110  
4793  
4382  
BHP  
3.51  
3.20  
2.88  
2.64  
2.34  
CFM  
5538  
5282  
4869  
4598  
BHP  
2.97  
2.78  
2.47  
2.28  
0.8  
1.0  
1.2  
1.4  
1.6  
1.8  
2.0  
2.2  
5894  
5570  
5312  
4945  
4504  
3.85  
3.55  
3.33  
3.01  
2.66  
5780  
5501  
5257  
5020  
4601  
4222  
4.04  
3.77  
3.54  
3.32  
2.96  
2.65  
5900  
5514  
5315  
4906  
4541  
4.49  
4.08  
3.88  
3.49  
3.15  
5860  
5615  
5529  
4938  
4.76  
4.49  
4.40  
3.78  
Notes  
Assume dry coil with filter in place; CFM correcꢀon for wet coil = 3%  
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applicaꢀon  
that exceed the above could require a larger motor. Minimum rated SCFM is 350 per ton.  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19  
ProduCt SPeCifiCationS  
Heat kit eleCtriCal data — 7½ tonS  
Model and  
Heat Kit Usage  
MCA¹  
at 208 / 240V  
MOP² (amps)  
at 208 / 240V  
Actual kW  
at 240V  
Recommended  
Airflow Range  
CPH090***3B***  
40  
50  
EHK3-16  
EHK3-30  
EHK3-45  
74 / 85  
80 / 90  
15  
30  
43  
3000-3375 CFM  
3000-3375 CFM  
3000-3375 CFM  
113 / 130  
147 / 169  
120 / 150  
150 / 175  
Model and  
Heat Kit Usage  
MCA¹  
at 208 / 240V  
MOP² (amps)  
at 208 / 240V  
Actual kW  
at 240V  
Recommended  
Airflow Range  
CPH090***4B***  
EHK4-16  
19  
42  
64  
84  
25  
45  
70  
90  
15  
30  
43  
3000-3375 CFM  
3000-3375 CFM  
3000-3375 CFM  
EHK4-30  
EHK4-45  
Model and  
Heat Kit Usage  
MCA¹  
at 208 / 240V  
MOP² (amps)  
at 208 / 240V  
Actual kW  
at 240V  
Recommended  
Airflow Range  
CPH090***7B***  
14  
32  
51  
15  
35  
60  
EHK4-16  
EHK4-30  
15  
30  
---  
---  
EHK4-45  
68  
70  
43  
---  
¹
Minimum Circuit Ampacity  
²
Maximum Overcurrent Protection device  
kw CorreCtion faCtorS  
kW Correction Factor for 3-Phase Units  
Supply Voltage  
240  
1
230  
220  
210  
208  
0.76  
Correction Factor  
0.93  
0.82  
0.78  
kW Correction Factor for 575V Units  
kW Correction Factor for 480V Units  
Supply Voltage  
560  
550  
540  
Supply Voltage  
460  
440  
430  
0.8  
Correction Factor  
0.95  
0.91  
0.88  
Correction Factor  
0.92  
0.84  
Mulꢀply rated kW by correcꢀon factor to get actual kW.  
For other voltage, use voltage² / 480²  
minimum airflow for eleCtriC Heat  
Heater Size (kW)  
Minimum CFM  
15  
30  
43  
3,000  
3,000  
3,000  
20  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ProduCt SPeCifiCationS  
Heat kit eleCtriCal data — 8½ tonS  
Recommended  
Airflow Range  
(Downshot)  
Recommended  
Airflow Range  
(Horizontal)  
Model and  
Heat Kit Usage  
MCA¹  
at 240V  
MOP² (amps)  
at 240V  
Actual kW  
at 240V  
CPH102***3B***  
EHK3-16  
43  
88  
50  
90  
15  
35  
43  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
EHK3-30  
133  
173  
150  
175  
EHK3-45  
Recommended  
Airflow Range  
(Downshot)  
Recommended  
Airflow Range  
(Horizontal)  
Model and  
Heat Kit Usage  
MCA¹  
at 480V  
MOP² (amps)  
at 480V  
Actual kW  
at 480V  
CPH102***4B***  
EHK4-16  
20  
42  
65  
84  
25  
45  
70  
90  
15  
30  
43  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
EHK4-30  
EHK4-45  
Recommended  
Airflow Range  
(Downshot)  
Recommended  
Airflow Range  
(Horizontal)  
Model and  
Heat Kit Usage  
MCA¹  
at 575V  
MOP² (amps)  
at 575V  
Actual kW  
at 575V  
CPH102***7B***  
EHK7-16  
17  
36  
55  
71  
20  
40  
60  
80  
15  
30  
43  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
3400 - 3825 CFM  
EHK7-30  
EHK7-45  
¹
²
Minimum Circuit Ampacity  
Maximum Overcurrent Protecꢀon device  
^ - EHK Heater Kits above require a three-phase power supply  
kw CorreCtion faCtor  
kW Correction Factor (for 1- & 3-Phase Units)  
Supply Voltage  
240  
1
230  
220  
210  
208  
0.76  
Correcꢀon Factor  
0.93  
0.82  
0.78  
kW Correction Factor for 480V Units  
Actual Voltage  
460  
440  
430  
0.8  
minimum airflow for eleCtriC Heat  
Correcꢀon Factor  
0.92  
0.84  
Min. CFM  
Heater Size (kW)  
Min. CFM  
Horizontal  
For other voltage use voltage² / 480²  
Down-shot  
15  
30  
43  
3,400  
3,400  
3,400  
3,400  
3,400  
3,400  
kW Correction Factor for 575V Units  
Supply Voltage  
560  
550  
540  
Correcꢀon Factor  
0.95  
0.91  
0.88  
Multiply rated kW by correction factor to get actual kW  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
21  
ProduCt SPeCifiCationS  
Heat kit eleCtriCal data — 10 tonS  
Model and  
Heat Kit Usage  
MCA¹ at  
208 / 240V  
MOP² (amps)  
at 208 / 240V  
Actual kW  
at 240V  
Recommended  
Airflow Range  
CPH120***3B***  
49  
60  
EHK3-16  
EHK3-30  
EHK3-45  
81 / 94  
90 / 100  
125 / 150  
175 / 200  
15  
35  
43  
3500 - 4500 CFM  
3500 - 4500 CFM  
4000 - 4500 CFM  
122 / 139  
154 / 178  
Model and  
Heat Kit Usage  
MCA¹ at  
208 / 240V  
MOP² (amps)  
at 208 / 240V  
Actual kW  
at 240V  
Recommended  
Airflow Range  
CPH120***3H***  
50  
60  
EHK3-16  
EHK3-30  
EHK3-45  
82 / 95  
90 / 100  
125 / 150  
175 / 200  
15  
35  
43  
---  
---  
---  
122 / 140  
155 / 179  
Model and  
Heat Kit Usage  
MCA¹  
at 480V  
MOP² (amps)  
at 480V  
Actual kW  
at 480V  
Recommended  
Airflow Range  
CPH120***4B***  
24  
46  
69  
89  
30  
50  
70  
90  
EHK4-16  
EHK4-30  
EHK4-45  
15  
30  
43  
3500 - 4500 CFM  
3500 - 4500 CFM  
4000 - 4500 CFM  
Model and  
Heat Kit Usage  
MCA¹  
at 575V  
MOP² (amps)  
at 575V  
Actual kW  
at 575V  
Recommended  
Airflow Range  
CPH0120***7B***  
EHK7-16  
17  
36  
55  
71  
20  
40  
60  
80  
15  
30  
43  
3500 - 4500 CFM  
3500 - 4500 CFM  
4000 - 4500 CFM  
EHK7-30  
EHK7-45  
¹
²
Minimum Circuit Ampacity  
Maximum Overcurrent Protecꢀon device  
kw CorreCtion faCtor  
kW Correction Factor (for 1- & 3-Phase Units)  
Supply Voltage  
240  
1
230  
220  
210  
208  
Correcꢀon Factor  
0.93  
0.82  
0.78  
0.76  
kW Correction Factor for 480V Units  
Actual Voltage  
460  
440  
430  
0.8  
minimum airflow for eleCtriC Heat  
Correcꢀon Factor  
0.92  
0.84  
Min. CFM  
Heater Size (kW)  
Min. CFM  
Horizontal  
For other voltage use voltage² / 480²  
Down-shot  
15  
30  
43  
4,000  
4,000  
4,000  
4,000  
4,000  
4,000  
kW Correction Factor for 575V Units  
Supply Voltage  
560  
550  
540  
Correcꢀon Factor  
0.95  
0.91  
0.88  
Multiply rated kW by correction factor to get actual kW  
22  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ProduCt SPeCifiCationS  
Heat kit eleCtriCal data — 12½ tonS  
Model and  
Heat Kit Usage  
MCA¹ at  
208 / 240V  
MOP² (amps)  
at 208 / 240V  
Actual kW  
at 240V  
Recommended  
Airflow Range  
CPH150***3B***  
65  
80  
EHK3-16  
EHK3-30  
EHK3-45  
110  
155  
194  
110  
175  
200  
15  
30  
43  
4000 - 5600  
4300 - 5600  
4500 - 5600  
Model and  
Heat Kit Usage  
MCA¹ at  
208 / 240V  
MOP² (amps)  
at 208 / 240V  
Actual kW  
at 240V  
Recommended  
Airflow Range  
CPH150***4B***  
31  
54  
76  
96  
40  
60  
EHK4-16  
EHK4-30  
EHK4-45  
15  
30  
43  
4000 - 5600  
4300 - 5600  
4500 - 5600  
80  
100  
Model and  
Heat Kit Usage  
MCA¹ at  
208 / 240V  
MOP² (amps)  
at 208 / 240V  
Actual kW  
at 240V  
Recommended  
Airflow Range  
CPH150***7B***  
23  
42  
61  
77  
30  
45  
70  
80  
EHK7-16  
EHK7-30  
EHK7-45  
15  
30  
43  
4000 - 5600  
4300 - 5600  
4500 - 5600  
¹
²
Minimum Circuit Ampacity (standard drive)  
Maximum Overcurrent Protecꢀon device (standard drive)  
kw CorreCtion faCtorS  
kW Correction Factor for 1- & 3-Phase Units  
Supply Voltage  
240  
1
230  
220  
210  
208  
Correction Factor  
0.93  
0.82  
0.78  
0.76  
kW Correction Factor for 480V Units  
Supply Voltage  
460  
440  
430  
0.8  
Correction Factor  
0.92  
0.84  
For other voltage, use voltage² / 480²  
kW Correction Factor for 575V Units  
Supply Voltage  
560  
550  
540  
Correction Factor  
0.95  
0.91  
0.88  
Multiply rated kW by correction factor to get actual kW.  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
23  
Product SPecificationS  
dimenSionS  
L
H
Dimensions  
Model  
Size  
H
L
7½ to 10 Tons  
12½ Tons  
52⅞”  
58⅞”  
99⅛”  
99⅛”  
61¾”  
12⅝”  
5⅞”  
5
28⅜”  
7⅜”  
7 3/8”  
RETURN  
36⅜”  
13⅞”  
”  
SUPPLY  
6½”  
RETURN  
6¼”  
Horizontal Discharge  
5
5⅜”  
SUPPL  
Y
7½”  
7
Vertical Discharge (Bottom of Unit)  
24  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Product SPecificationS  
unit clearanceS  
Maintain an adequate clearance around the unit for safety, service, maintenance, and proper unit  
operation. Leave a total clearance of 75on the main control panel side of the unit for possible removal  
of fan shaft, coil, electric heat, and gas furnace. Leave a clearance of 48on all other sides of the unit for  
possible compressor removal or service access, and to ensure proper  
ventilation and condenser airflow. Do not install the unit beneath  
any obstruction. Install the unit away from all building  
exhausts to inhibit ingestion of exhaust air into the unit’s  
fresh-air intake.  
48”  
48”  
36” Min.  
75”  
48”  
electrical entrance locationS  
Dimples Mark Drill Locaꢀons  
11⅝”  
High-Voltage Entrance  
103/16”  
Low-Voltage Entrance  
3”  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
25  
Product SPecificationS  
roof curb inStallation — rigging  
Provisions for forks have been included in the unit base frame. No other  
fork locations are approved.  
Unit must be lifted by the four lifting holes located at the base  
frame corners.  
Lifting cables should be attached to the unit with shackles.  
The distance between the crane hook and the top of the unit must  
not be less than 60.  
Two spreader bars must span over the unit to prevent damage to  
the cabinet by the lift cables. Spreader bars must be of sufficient  
length so that cables do not come in contact with the unit during  
transport. Remove wood struts mounted beneath unit base frame  
before setting unit on roof curb. These struts are intended to protect  
unit base frame from fork lift damage. To remove the struts, extract  
the sheet metal retainers and pull the struts through the base of the  
unit. Refer to rigging label on the unit.  
Important: If using bottom discharge with roof curb, duct-work  
should be attached to the curb prior to installing the unit. Duct-work  
dimensions are shown in Roof Curb Installation Instructions Manual.  
Refer to the Roof Curb Installation Instructions  
for proper curb installation. Curbing must  
be installed in compliance with the National  
Roofing Contractors Association Manual.  
Lower unit carefully onto roof mounting curb.  
Return  
30”  
While rigging the unit, the center of gravity will  
cause the condenser end to be lower than the  
supply air end.  
Evaporator Coil  
Compressor 1  
Compressor 2  
Bring condenser end of unit into alignment  
with the curb. With condenser end of the  
unit resting on curb member and using curb  
as a fulcrum, lower opposite end of the unit  
until entire unit is seated on the curb. When a  
rectangular cantilever curb is used, take care  
to center the unit. Check for proper alignment  
and orientation of supply and return openings  
with duct.  
Supply  
49”  
Corner & Center-of-Gravity Locations  
7½-Ton  
Weights (lbs)  
8½-Ton  
Weights (lbs)  
10-Ton  
Weights (lbs)  
12½-Ton  
Weights (lbs)  
Unit Weights  
Weight A  
285  
285  
345  
325  
345  
325  
435  
345  
Weight B  
Weight C  
285  
320  
320  
300  
Weight D  
285  
300  
300  
240  
Shipping Weight  
Operaꢀng Weight  
1175  
1135  
1310  
1285  
1310  
1285  
1350  
1325  
Note: These weights are calculated without accessories installed.  
26  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ProduCt SPeCifiCationS  
roof CurB inStallation (Cont.)  
Curb installations must comply with local codes and should follow the  
established guidelines of the National Roofing Contractors Association.  
Proper unit installation requires that the roof curb be firmly and permanently  
attached to the roof structure. Check for adequate fastening method prior to  
setting the unit on the curb.  
Full perimeter roof curbs are available from the factory and are shipped  
unassembled. The installing contractor is responsible for field assembly,  
squaring, leveling, and mounting on the roof structure. All required hardware  
necessary for the assembly of the sheet metal curb is included in the curb  
accessory package.  
• Determine sufficient structural support before locating and mounting the  
curb and package unit.  
• Duct-work must be constructed using industry guidelines. The duct-work  
must be placed into the roof curb before mounting the package unit. Our  
full perimeter curbs include duct connection frames to be assembled with  
the curb. Cantilevered-type curbs are not available from the factory.  
• Contractor furnishes curb insulation, cant strips,  
flashing, and general roofing material.  
3-d View  
• Support curbs on parallel sides with roof members.  
To prevent damage to the unit, the roof members  
92¼  
53¼  
cannot penetrate supply and return duct openings.  
Note: The unit and curb accessories are designed to  
allow vertical duct installation before unit placement.  
15 x 31  
Supply Opening  
Duct installation after unit placement is not  
14  
14 x 38  
recommended.  
Return Opening  
See the manual shipped with the roof curb for  
assembly and installation instructions.  
1
¾
14  
1
toP View  
Power Wiring  
Thermostat  
Wiring  
Power and low-Voltage BloCk loCationS  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
27  
ProduCt SPeCifiCationS  
wiring diagram — CPH090-120***3B/ 4B  
(for modelS witH Serial numBerS 0907 and Below)  
Wiring is subject to change. Always  
refer to the wiring diagram or the  
unit for the most up-to-date wiring.  
High Voltage: Disconnꢁct all powr bꢁforsrvicing or installing this unit. Mulꢀplꢁ powr  
sources may be present. Failure to do so may cause property damage, personal injury, or death.  
Warning  
28  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ProduCt SPeCifiCationS  
wiring diagram — CPH090-120***3B/ 4B (Cont.)  
(for modelS witH Serial numBerS 0907 and Below)  
Wiring is subject to change. Always  
refer to the wiring diagram or the  
unit for the most up-to-date wiring.  
High Voltage: Disconnꢁct all powr bꢁforsrvicing or installing this unit. Mulꢀplꢁ powr  
sources may be present. Failure to do so may cause property damage, personal injury, or death.  
Warning  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
29  
ProduCt SPeCifiCationS  
wiring diagram — CPH090-120***3B/ 4B/ 7B***  
OR  
2
0
8
~
2
4
0
~
4
6
0
~
5
7
5
/
BK  
OR  
L3  
BL  
BK  
RD  
P
BR  
BL  
RD  
PB  
O
W
E
2
3
1
C
BL  
RD  
T3  
T2  
YL  
OR  
208 240  
460  
GR  
EBTDR  
PK  
RD  
OR  
RD  
575  
R
G
R
RD  
BK  
L2  
C
RD  
RD  
NO  
K1  
K1  
TB1  
S1  
S2  
S
U
P
P
L
BL  
XFMR-R  
XFMR-C  
C
GR  
PU  
REPLACE JUMPER WITH  
SMOKE/FIRE DETECTOR  
T1  
L1  
BK  
COM  
BL  
SEE  
NOTE #2  
CC2  
BK  
NC  
M2  
YL  
SPEED  
UP  
YL  
3
/
6
0
M1  
BL  
Y
BR  
OR  
PU  
GND  
BL  
BL  
GR  
DC  
OR  
3
9
8
6
5
4
C
2
WH  
PU  
BL  
1
3
NO  
NC  
OR  
2
1
4
YL  
Y
O
NOTE 3  
PLF  
7
DR  
YL  
SSHR  
5
OR  
BK  
OR  
WH  
YL  
PU  
YL  
BL  
O
LVDR  
GR  
SEE NOTE 4  
OR  
BK  
WH  
W2  
R
BL  
WH  
T
H
E
R
PLF 1  
YL  
PU  
RD  
GR  
WH  
BR  
OR  
BL  
Y1  
Y/Y2  
R
G
BL  
L1  
T1  
L2  
T2  
L3  
PU  
BK  
RD  
RD  
R
HVDR  
3
2
1
6
5
4
9
8
7
RD  
C
DFT  
RCCF2  
M
T3  
W1  
O
DF1  
DF2  
RD  
WH  
BL  
WH  
OR  
BR  
W2  
S
BC  
C
F
BK  
O
C
T
A
T
OR  
BL  
RD  
OR  
RD  
BR  
BK  
++  
BL  
TB1  
BK  
RD  
BK  
RD  
BK  
YL  
RD  
RD  
RD  
YL  
BK  
BK  
BL  
T3 T2 T1  
COMP2  
BK  
EM  
DFT2  
DFT1  
CM2  
BK  
BK  
LPS2  
HPS2  
RVC2  
BR  
BL  
RVC1  
BL  
BK  
PU  
YL  
BK  
RD  
RCCF1  
LPS1  
T2  
L2  
HPS1  
PU  
T3  
T2  
L3  
L2  
OR  
RD  
C
F
CMC  
PU  
T1  
L1  
RD  
BR  
RD  
BK  
BL  
PU  
C
BK  
RD  
BR  
YL  
L1  
BK  
T1  
BL  
CC1  
CM1  
BL  
T3 T2 T1  
COMP1  
BL  
0140L00546 REV B  
Wiring is subject to change. Always  
refer to the wiring diagram or the  
unit for the most up-to-date wiring.  
High Voltage: Disconnꢁct all powr bꢁforsrvicing or installing this unit. Mulꢀplꢁ powr  
sources may be present. Failure to do so may cause property damage, personal injury, or death.  
Warning  
30  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ProduCt SPeCifiCationS  
wiring diagram — CPH090-120***3B/ 4B/ 7B*** (Cont.)  
SUPPLY VOLTAGE  
208-240/460/575/3/60  
L3  
L1  
L2  
FACTORY WIRING  
LINE VOLTAGE  
LOW VOLTAGE  
CC1  
T2  
OPTIONAL  
HIGH VOLTAGE  
T2  
COMP1  
CC1  
COMPONENT LEGEND  
T1  
CC1  
BC  
BLOWER CONTACTOR  
FIELD WIRING  
T3  
COMPRESSOR CONTACTOR  
CONDENSER MOTOR  
CC  
CM  
HIGH VOLTAGE  
LOW VOLTAGE  
RCCF2  
CONDENSER MOTOR CONTACTOR  
COMPRESSOR  
DEFROST CONTROL  
CMC  
COMP  
DC  
CMC  
DEFROST THERMOSTAT  
ECONOMIZER  
ELECTRONIC BLOWER TIME DELAY  
EVAPORATOR MOTOR RELAY  
RELAY  
EVAPORATOR MOTOR  
FAN CAPACITOR  
EQUPIMENT GROUND  
HIGH PRESSURE SWITCH  
HIGH VOLTAGE DEFROST RELAY  
LOW PRESSURE SWITCH  
LOW VOLTAGE DEFROST RELAY  
POWER DISTRIBUTION BLOCK  
FEMALE PLUG / CONNECTOR  
REVERSING VAVLE COIL  
RUN CAPACITOR FOR  
CONDENSER FAN  
TERMINAL BLOCK (24V SIGNAL)  
TRANSFORMER  
DFT  
ECON  
EBTD  
EMR  
R
EM  
FC  
GND  
HPS  
HVDR  
LPS  
LVDR  
PB  
PLF  
RVC  
RCCF  
WIRE CODE  
C
CM2  
BK  
BL  
BLACK  
BLUE  
RCCF  
CMC  
F
BR  
GR  
OR  
PK  
PU  
RD  
WH  
YL  
BROWN  
GREEN  
ORANGE  
PINK  
CM1  
PURPLE  
RED  
CC2  
WHITE  
YELLOW  
T2  
COMP2  
CC2  
T1  
T2  
T1  
YL/PK YELLOW WITH  
PINK STRIP  
BL/PK BLUE WITH  
CC2  
T3  
PINK STRIP  
BC  
EM  
208-240V  
BC  
BC  
TB1  
TR  
SSHR  
OR APPROPRIATE  
INPUT VOLTAGE  
THERMOSTAT  
FIELD WIRING  
SECOND STAGE HEATER RELAY  
DEFROST RELAY  
3
1
DR  
2 STAGE COOLING  
S2  
S1  
TR  
W1  
G
WH  
GR  
RD  
YL  
W1  
G
24V  
TB1  
EBTDR  
NOTES:  
R
G
C
R
R
1. REPLACEMENT WIRE MUST BE SAME SIZE AND  
TYPE INSULATION AS ORIGINAL (AT LEAST 105°C)  
USE COPPER CONDUCTOR ONLY.  
2. USE COPPER CONDUCTORS ONLY  
++ USE N.E.C. CLASS 2 WIRE  
3. ECONOMIZER PLUG LOCATED IN THE RETURN AIR  
COMPARTMENT. REMOVE MALE PLUG AND ATTACH  
FEMALE PLUG TO THE ECONOMIZER ACCESSORY.  
4. FOR TWO STAGE OPERATION REMOVE W1 TO W2  
JUMPER WIRE.  
Y1  
Y1  
R
PK  
BL  
Y/Y2  
C
Y2  
C
CMC  
EBTDR  
C
R
HVDR  
BC  
OR  
R
R
O
O
DFT1  
DFT2  
EBTDR  
DFT  
W2  
W2  
BR  
DC  
Y
STAT  
TB1  
R
W2  
RVC2  
RVC1  
LVDR  
O
5. FOR 208V OPREATION, MOVE BLACK WIRE FROM  
TERMINAL 3 TO TERMINAL 2 ON 240V TRANSFORMER.  
LPS1  
HPS1  
HPS2  
LPS2 CC2  
CC1  
P
7
8
9
4
5
6
L
F
1
NC  
NO  
SSHR  
3
2
1
9
8
6
5
4
PLF2  
NC  
NO  
SEE NOTE 3  
DR  
SEE UNIT RATING PLATE FOR TYPE AND SIZE  
OF OVER CURRENT PROTECTION  
7
208-240/460/575/3/60 0140L00547 REV. B  
Y
R
W2  
O
G
C
W1  
Y2  
Y1  
SEE NOTE 4  
THERMOSTAT  
++  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
31  
ProduCt SPeCifiCationS  
wiring diagram — CPH150***3B/ 4B/ 7B***  
OR  
2
0
8
~
2
4
0
~
4
6
0
~
5
7
5
/
BK  
OR  
L3  
BL  
BK  
RD  
P
BR  
BL  
PB  
RD  
O
W
E
2
3
1
C
BL  
RD  
T3  
T2  
YL  
OR  
208 240  
460  
GR  
EBTDR  
PK  
RD  
OR  
575  
R
G
R
RD  
BK  
L2  
C
RD  
RD  
NO  
K1  
K1  
TB1  
S1  
RD  
S2  
S
U
P
P
L
BL  
XFMR-R  
XFMR-C  
C
GR  
PU  
REPLACE JUMPER WITH  
SMOKE/FIRE DETECTOR  
L1  
T1  
BK  
COM  
BL  
SEE  
NOTE #2  
CC2  
BK  
NC  
M2  
YL  
SPEED  
UP  
YL  
3
/
6
0
M1  
BL  
BR  
Y
OR  
PU  
GND  
BL  
BL  
GR  
DC  
OR  
3
9
8
6
5
4
C
2
WH  
PU  
BL  
1
3
NO  
NC  
OR  
2
1
4
YL  
Y
O
NOTE 3  
PLF  
7
DR  
YL  
SSHR  
5
OR  
BK  
OR  
WH  
YL  
PU  
YL  
BL  
O
LVDR  
GR  
SEE NOTE 4  
OR  
BK  
WH  
W2  
R
BL  
WH  
T
H
E
PLF 1  
YL  
PU  
RD  
GR  
WH  
BR  
OR  
BL  
Y1  
Y/Y2  
R
BL  
PU  
L2  
T2  
L3  
L1  
T1  
BK  
RD  
RD  
R
HVDR  
3
2
1
6
5
4
9
8
7
RD  
R
G
C
DFT  
RCCF2  
M
T3  
W1  
O
DF1  
DF2  
WH  
BL  
WH  
OR  
W2  
BR  
S
BC  
C
F
BK  
O
C
T
A
T
RD  
OR  
BL  
RD  
OR  
RD  
BR  
BK  
++  
TB1  
BL  
BK  
RD  
BK  
RD  
BK  
YL  
RD  
RD  
RD  
YL  
BK  
BK  
BL  
T1  
T3  
T2  
BK  
EM  
DFT2  
DFT1  
CM2  
BK  
BK  
COMP2  
LPS2  
HPS2  
RVC2  
BR  
BL  
RVC1  
BL  
BK  
PU  
YL  
BK  
RD  
RCCF1  
LPS1  
T2  
L2  
HPS1  
PU  
T3  
T2  
L3  
L2  
OR  
C
F
CMC  
L1  
T1  
RD  
BR  
RD  
RD  
BK  
PU  
BL  
PU  
C
BK  
RD  
BR  
YL  
L1  
BK  
T1  
BL  
CC1  
CM1  
BL  
T3 T2  
T1  
BL  
COMP1  
0140L00546 REV B  
32  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ProduCt SPeCifiCationS  
wiring diagram — CPH150***3B/ 4B/ 7B*** (Cont.)  
SUPPLY VOLTAGE  
208-240/460/575/3/60  
L3  
L1  
L2  
FACTORY WIRING  
LINE VOLTAGE  
LOW VOLTAGE  
CC1  
T2  
OPTIONAL  
HIGH VOLTAGE  
T2  
COMP1  
CC1  
COMPONENT LEGEND  
T1  
CC1  
BC  
CC  
CM  
BLOWER CONTACTOR  
COMPRESSOR CONTACTOR  
CONDENSER MOTOR  
FIELD WIRING  
T3  
HIGH VOLTAGE  
LOW VOLTAGE  
RCCF2  
CMC  
COMP  
DC  
CONDENSER MOTOR CONTACTOR  
COMPRESSOR  
DEFROST CONTROL  
CMC  
DFT  
ECON  
EBTD  
EMR  
R
EM  
FC  
GND  
HPS  
HVDR  
LPS  
LVDR  
PB  
PLF  
RVC  
RCCF  
DEFROST THERMOSTAT  
ECONOMIZER  
ELECTRONIC BLOWER TIME DELAY  
EVAPORATOR MOTOR RELAY  
RELAY  
EVAPORATOR MOTOR  
FAN CAPACITOR  
EQUPIMENT GROUND  
HIGH PRESSURE SWITCH  
HIGH VOLTAGE DEFROST RELAY  
LOW PRESSURE SWITCH  
LOW VOLTAGE DEFROST RELAY  
POWER DISTRIBUTION BLOCK  
FEMALE PLUG / CONNECTOR  
REVERSING VAVLE COIL  
RUN CAPACITOR FOR  
WIRE CODE  
C
CM2  
BK  
BL  
BLACK  
RCCF  
BLUE  
CMC  
F
BR  
GR  
OR  
PK  
PU  
RD  
WH  
YL  
BROWN  
GREEN  
ORANGE  
PINK  
PURPLE  
RED  
CM1  
CC2  
WHITE  
YELLOW  
T2  
COMP2  
CC2  
T1  
T2  
T1  
YL/PK YELLOW WITH  
PINK STRIP  
BL/PK BLUE WITH  
CC2  
T3  
PINK STRIP  
BC  
EM  
CONDENSER FAN  
TERMINAL BLOCK (24V SIGNAL)  
TRANSFORMER  
SECOND STAGE HEATER RELAY  
DEFROST RELAY  
208-240V  
BC  
BC  
TB1  
TR  
SSHR  
OR APPROPRIATE  
INPUT VOLTAGE  
THERMOSTAT  
FIELD WIRING  
1
3
DR  
2 STAGE COOLING  
S2  
S1  
TR  
W1  
G
WH  
GR  
RD  
YL  
W1  
G
24V  
TB1  
EBTDR  
NOTES:  
R
G
C
R
R
1. REPLACEMENT WIRE MUST BE SAME SIZE AND  
TYPE INSULATION AS ORIGINAL (AT LEAST 105°C)  
USE COPPER CONDUCTOR ONLY.  
2. USE COPPER CONDUCTORS ONLY  
++ USE N.E.C. CLASS 2 WIRE  
3. ECONOMIZER PLUG LOCATED IN THE RETURN AIR  
COMPARTMENT. REMOVE MALE PLUG AND ATTACH  
FEMALE PLUG TO THE ECONOMIZER ACCESSORY.  
4. FOR TWO STAGE OPERATION REMOVE W1 TO W2  
JUMPER WIRE.  
Y1  
Y/Y2  
C
Y1  
Y2  
R
PK  
BL  
CMC  
EBTDR  
C
R
HVDR  
C
O
BC  
OR  
R
R
O
DFT1  
DFT2  
EBTDR  
DFT  
W2  
W2  
BR  
DC  
Y
STAT  
TB1  
R
W2  
RVC2  
RVC1  
LVDR  
O
5. FOR 208V OPREATION, MOVE BLACK WIRE FROM  
TERMINAL 3 TO TERMINAL 2 ON 240V TRANSFORMER.  
LPS1  
HPS1  
HPS2 LPS2  
CC2  
CC1  
P
7
8
9
4
5
6
L
F
1
NC  
NO  
SSHR  
3
2
1
9
8
6
5
4
PLF2  
NC  
NO  
SEE NOTE 3  
DR  
SEE UNIT RATING PLATE FOR TYPE AND SIZE  
OF OVER CURRENT PROTECTION  
7
208-240/460/575/3/60 0140L00547 REV. B  
Y
Y2  
R
W2  
O
W1  
Y1  
G
C
SEE NOTE 4  
THERMOSTAT  
++  
Wiring is subject to change. Always  
refer to the wiring diagram or the  
unit for the most up-to-date wiring.  
High Voltage: Disconnꢁct all powr bꢁforsrvicing or installing this unit. Mulꢀplꢁ powr  
sources may be present. Failure to do so may cause property damage, personal injury, or death.  
Warning  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
33  
ProduCt SPeCifiCationS  
aCCeSSorieS  
Fits  
Model Sizes  
Item #  
Description  
14CURB90150  
25FD90150  
25MFD90150  
BRD3672  
Roof Curb 14" Tall  
25% Manual Fresh Air Damper  
7½-12½ tons  
7½-12½ tons  
7½-12½ tons  
7½-12½ tons  
10 tons  
25% Motorized Fresh Air Damper  
Horizontal Barometric Relief Damper (two required)  
Concentric Duct Kit  
CDK120  
CDK150  
Concentric Duct Kit  
12½ tons  
CDK90102  
DNBBS90150  
DNECONGS90120  
DNECONGS150  
DNSQRRND90  
GHRC-1  
Concentric Duct Kit  
7½-8½ tons  
7½-12½ tons  
7½-10 tons  
12½ tons  
Burglar Bar Sleeves: Includes Supply & Return  
Downflow Economizer  
Downflow Economizer  
Downflow Square-to-Round Adapter 20" Round  
Hurricane Restraint Clip  
7½ tons  
All Models  
7½-10 tons  
12½ tons  
HailGD02  
Condenser Coil Hail Guard  
HailGD05  
Condenser Coil Hail Guard  
HAKT36300  
HSKT090  
High-Alꢀtude Kit  
All Models  
8½ tons  
High-Staꢀc Kit for 8½-ton AA models (230/460v)  
High-Staꢀc Kit for AA & BA models (230/460v)  
High-Staꢀc Kit for AA models (230/460v)  
High-Staꢀc Kit for AA models (230/460v)  
Horizontal Economizer  
HSKT090G  
HSKT120  
7½ tons  
10 tons  
HSKT150  
12½ tons  
HZECONGS90150  
LAKT02  
7½-12½ tons  
7½ - 12½ tons  
7½ - 12½ tons  
7½-12½ tons  
7½-12½ tons  
7½-12½ tons  
Low-Ambient Kit for units with serial number below 0909  
Low Ambient Kit for units with serial numbers 0909 and above  
LP Conversion Kit  
LAKT03  
LPKT36150  
PE901502  
PE901504  
Power Exhaust 208/230 Volt  
Power Exhaust 460 Volt  
34  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ProduCt SPeCifiCationS  
noteS  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  
35  
Product SPecificationS  
noteS  
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without  
notice or without incurring obligations. © 2010 • Goodman Manufacturing Company, L.P. Houston, Texas • Printed in the USA.  
36  
SS-CPH90-150  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Electro Voice Microphone 366 User Manual
Fender Guitar 131002 User Manual
Finisar Computer Accessories FCLF 8521 3 User Manual
Fisher Price Car Seat 79013 User Manual
Fujioh Ventilation Hood BUF 03R User Manual
Fujitsu Network Card MB86617A User Manual
Gardena Lawn Mower ES 500 User Manual
Garmin Hiking Equipment Hiking Equipment User Manual
Gembird Headphones BTHS 002 User Manual
Generac Portable Generator 5747 User Manual