CPH CommerCial
7½- to 12½-ton Self-Contained
PaCkaged Heat PumP
Cooling / Heating CaPaCitieS:
up to 11.5 EER
up to 3.5 Cop
90,000 — 118,000 Btu/H
Standard Features
• R-410A chlorine-free refrigerant
• High-efficiency scroll compressor
• Copper tube / aluminum fin coils
• Contactor with lugs
• High-capacity, steel-cased filter dryer
• Single-point entry
• 24-volt terminal strip
• Convertible
• Easy to service
• Built-in filter rack with standard 2”filters
• Bottom utility entry
• AHRI Certified; ETL Listed
Contents
Cabinet Features
Nomenclature.............................................................................................2
Product Specifications...........................................................................3
Expanded Heating Data ......................................................................7
Expanded Cooling Data........................................................................8
Airflow Data............................................................................................... 16
Heat Kit Electrical Data ...................................................................... 20
Dimensions................................................................................................ 24
Wiring Diagrams .................................................................................... 28
Accessories ............................................................................................... 34
• Heavy-gauge, galvanized-steel cabinet with
UV-resistant powder-paint finish
• Full Perimeter Rail
• Curb Fit
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
6/11
Supersedes 3/11
ProduCt SPeCifiCationS
ProduCt SPeCifiCationS — 7½ tonS
CPH090
***3B***
CPH090
***4B***
CPH090
***7B***
Cooling Capacity
Total BTU/h
Sensible BTU/h
EER / IEER
IPLV
90,000
65,700
11.5 / 11.2
12.30
90,000
65,700
11.5 / 11.2
12.30
90,000
65,700
11.5 / 11.2
12.30
Decibels
83
83
83
AHRI Reference #s
3000984
3000984
3000984
Heating Capacity
BTU/h / COP (47° F)
BTU/h / COP (17° F)
Evaporator Motor / Coil
Motor Type
Indoor Nominal CFM
Indoor Motor FLA (Cooling)
Horsepower - RPM
Piston Size (Cooling)
Filter Size
Drain Size (NPT)
90,000 / 3.5
55,500 / 2.4
90,000 / 3.5
55,500 / 2.4
90,000 / 3.5
56,500 / 2.4
Belt Drive
3,000
7.8
2.0 - 1725
0.076
Belt Drive
3,000
3.9
2.0 - 1725
0.076
Belt Drive
3,000
2.5
2.0 - 1725
0.078
16" x 24" x 2"
¾"
16" x 24" x 2"
¾"
16" x 24" x 2"
¾"
R-410A Refrigerant Charge: Cir #1 / #2 (oz.)
Evaporator Coil Face Area (ſt²)
Rows Deep / Fins per Inch
Belt Drive Evap Fan Data
# of Wheels (D x W)
Motor Sheave / Blower Sheave
Belt
215 / 215
10.2
4 / 16
215 / 215
10.2
4 / 16
200 / 200
10.2
4 / 16
1 (15" x 12")
VL40 / AK74
AX51
1 (15" x 12")
VL40 / AK74
AX51
1 (15" x 12")
VL40 / AK74
AX51
Condenser Fan / Coil
Quanꢀty of Condenser Fan Motors
Horsepower - RPM
Fan Diameter / # Fan Blades
Outdoor Expansion Device
Outdoor Nominal CFM
Face Area (ſt²)
2
2
2
¼ - 1090
22 / 4
0.052
7,600
32.4
¼ - 890
22 / 4
0.052
7,600
32.4
¼ - 1075
22 / 4
0.055
7,600
32.4
# Coils / Rows Deep - Fins per Inch
Piston Size (Heaꢀng)
Compressor
2 / 2 - 20
0.052
2 / 2 - 20
0.052
2 / 2 - 20
0.055
Quanꢀty / Type / Stage
Compressor RLA / LRA
Electrical Data
2 / Scroll / 1
13.1 / 83.1
2 / Scroll / 1
6.1 / 41.0
2 / Scroll / 1
4.4 / 33.0
Voltage / Phase / Frequency
Indoor Blower HP / FLA
Outdoor Fan HP / FLA
Total Unit Amps
208-230 / 3 / 60
460 / 3 / 60
1.5 / 2.5
¼ / 0.8
17.7
575 / 3 / 60
2 / 2.5
¼ / 0.6
12.5
1.5 / 5.0
¼ / 1.4
36.9
Min. Circuit Ampacity¹
Max. Overcurrent Protecꢀon (amps)²
Entrance Power Supply & Control Voltage
Operating Weight (lbs)
Ship Weight (lbs)
40
50
19
25
13.6
15
Locaꢀng Dimple
1135
1135
1175
1135
1175
1175
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
²
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
3
ProduCt SPeCifiCationS
ProduCt SPeCifiCationS — 8½ tonS
CPH102
***3B***
CPH102
***4B***
CPH102
***7B***
Cooling Capacity
Total, BTU/h
Sensible BTU/h
102,000
73,440
102,000
73,440
102,000
73,440
EER / IEER
Decibels
11.1 / 11.2
83
11.1 / 11.2
83
11.1 / 11.2
83
ARI Reference #s
3620224
3620224
3620224
Heating Capacity
BTU/h (47°F)
COP (47°F)
102,000
3.4
102,000
3.4
102,000
3.4
BTU/h (17°F)
COP (17°F)
55,500
2.25
55,500
2.25
55,500
2.25
Evapoartor Motor / Coil
Motor Type
Belt Drive
3,400
7.8
1725
Belt Drive
3,400
3.9
1725
Belt Drive
3,400
2.3
1725
Indoor Nominal CFM
Indoor Motor FLA (Cooling)
Horsepower - RPM
Piston Size (Cooling)
Filter Size (Qty)
0.08
(4) 16” x 24” x 2”
3/4”
0.08
(4) 16” x 24” x 2”
3/4”
0.08
(4) 16” x 24” x 2”
3/4”
Drain Size (NPT)
R-410A Refrigerant Charge Cir #1 & #2 (oz.)
Evaporator Coil Face Area (ſt²)
Rows Deep / Fins per Inch
Belt Drive Evap Fan Data
# of Wheels (D x W)
Motor Sheave / Blower Sheave
Belt
205 / 205
10.2
4 / 14
205 / 205
10.2
4 / 14
205 / 205
10.2
4 / 14
1 (15” x 12”)
VL40 / AK74
AX51
1 (15” x 12”)
VL40 / AK74
AX51
1 (15” x 12”)
VL40 / AK74
AX51
Condenser Fan / Coil
Quanꢀty of Condenser Fan Motors
Horsepower - RPM
Fan Diameter / # Fan Blades
Outdoor Nominal CFM
Face Area (ſt²)
2
1/4” - 1,090
22 / 4
2
2
1/4” - 1,075
22 / 4
1/4” - 890
22 / 4
7,600
7,600
16.19
7,600
16.19
16.19
Rows Deep / Fins per Inch
Piston Size (Heaꢀng)
Compressor
2 / 22
0.059
2 / 22
0.059
2 / 22
0.059
Quanꢀty / Type
Stage
2 / Scroll
1
2 / Scroll
1
2 / Scroll
1
Compressor RLA / LRA ea.
Electrical Data / Static
Voltage / Phase / Frequency
Standard Max Staꢀc
Outdoor Fan FLA ea.
Total Unit Amps
14.5 / 98
6.3 / 55
6.0 / 41
230 / 3 / 60
460 / 3 / 60
575 / 3 / 60
1”
1.4
39.6
1
0.8
18.1
1
0.6
15.5
Min. Circuit Ampacity¹
Max. Overcurrent Protecꢀon (amps)²
Entrance Power Supply & Control Voltage
Operating Weight (lbs)
Ship Weight (lbs)
43.2
50
Locaꢀng Dimple
1285
19.7
25
Locaꢀng Dimple
1285
17
20
Locaꢀng Dimple
1285
1310
1310
1310
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
²
4
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
ProduCt SPeCifiCationS
ProduCt SPeCifiCationS — 10 tonS
CPH120
***3B***
CPH120
***4B***
CPH120
***7B***
Cooling Capacity
Total BTU/h
Sensible BTU/h
EER / IEER
Decibels
118,000
87,300
11.5 / 11.5
83
118,000
87,300
11.5 / 11.5
83
118,000
87,300
11.5 / 11.5
83
Heating Capacity
BTU/h (47° F)
COP (47°F)
120,000
3.4
120,000
3.4
120,000
3.4
BTU/h (17° F)
COP (17°F)
56,000
2.4
56,000
2.4
56,000
2.4
Evaporator Motor / Coil
Motor Type
Indoor Nominal CFM
Indoor motor FLA (Cooling)
Horsepower - RPM
Belt Drive
4,000
7.8
2.0/1725
0.086
Belt Drive
4,000
3.9
2.0/1725
0.086
Belt Drive
4,000
2.5
2.0/1725
0.086
Piston Size (Cooling)
Expansion Device
Orifice
Orifice
Orifice
Filter Size
Drain Size (NPT)
(4) 16" x 24" x 2"
¾"
(4) 16" x 24" x 2"
¾"
(4) 16" x 24" x 2"
¾"
R-410A Refrigerant Charge Cir #1 & #2 (oz.)
Evaporator Coil Face Area (ſt²)
Rows Deep/ Fins per Inch
Belt Drive Evap Fan Data
# of Wheels (D x W)
Motor Sheave / Blower Sheave
Belt
225 / 225
10.2
4 / 14
225 / 225
10.2
4 / 14
225 / 225
10.2
4 / 14
(1) 15" x 15"
VL40 / AK74
AX51
(1) 15" x 15"
VL40 / AK74
AX51
(1) 15" x 15"
VL40 / AK74
AX51
Condenser Fan / Coil
Quanꢀty of Condenser Fan Motors
Horsepower - RPM
Fan Diameter / # Fan Blades
Outdoor Nominal CFM
Face Area (ſt²)
2
2
2
⅓ - 1,075
22 / 3
7,200
⅓ - 1,075
22 / 3
7,200
⅓ - 1,125
22 / 3
7,200
32.4
32.4
32.4
# Coils / Rows Deep - Fins per Inch
Piston Size (Heaꢀng)
Compressor
2 / 2 - 22
0.064
2 / 2 - 22
0.064
2 / 2 - 22
0.064
Quanꢀty / Type / Stage
Compressor RLA / LRA ea.
Electrical Data
2 / Scroll / 1
16 / 110.0
2 / Scroll / 1
7.8 / 52.0
2 / Scroll / 1
5.7 / 38.9
Voltage/Phase/ Frequency
Belt-Driven Standard Max Staꢀc
Outdoor Fan RLA ea.
Total Unit Amps
208-230/3/60
460/3/60
1.4
1.20
575/3/60
1.4
0.90
16
1.4
2.40
45
22
Min. Circuit Ampacity¹
Max. Overcurrent Protecꢀon (amps)²
Entrance Power Supply & Control Voltage
Operating Weight (lbs)
Ship Weight (lbs)
49
60
24
30
17
20
Locaꢀng Dimple
1285
1285
1310
1285
1310
1310
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
²
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
5
ProduCt SPeCifiCationS
ProduCt SPeCifiCationS — 12½ tonS
CPH150XXX
3BXXX
CPH150XXX
4BXXX
CPH150XXX
7BXXX
Cooling Capacity
Total, BTU/h
Sensible BTU/h
EER / IPLV
Decibels
146,000
102,200
10.8 / 11.2
83
146,000
102,200
10.8 / 11.2
83
146,000
102,200
10.8 / 11.2
83
ARI Reference #s
3554114
3554114
3554114
Heating Capacity
BTU/hr (47°F)
COP (47°F)
150,000
3.2
150,000
3.2
150,000
3.2
BTU/hr (17°F)
COP (17°F)
82,000
2.1
82,000
2.1
82,000
2.1
Evapoartor Motor / Coil
Motor Type (Belt Drive)
Indoor Nominal CFM
Indoor Motor FLA (Cooling)
Horsepower - RPM
Piston Size (Cooling)
Filter Size (Qty)
AX49
5,000
9.4
AX49
5,000
4.7
AX49
5,000
4.2
3.0 - 1,725
0.096
(4) 20" x 25" x 2"
¾"
3.0 - 1,725
0.096
(4) 20" x 25" x 2"
¾"
3.0 - 1,725
0.096
(4) 20" x 25" x 2"
¾"
Drain Size (NPT)
R-410A Refrigerant Charge Cir #1 & #2 (oz.)
Evaporator Coil Face Area (ſt²)
Rows Deep / Fins per Inch
# of Wheels (D x W)
Motor Sheave / Blower Sheave
Condenser Fan / Coil
Quanꢀty of condenser Fan Motors
Horsepower - RPM
Fan Diameter / # Fan Blades
Outdoor Nominal CFM
Face Area (ſt²)
290 / 290
14.7
4 / 15
(1) 15" x 15"
VL40 / AK66
290 / 290
14.7
4 / 15
(1) 15" x 15"
VL40 / AK66
290 / 290
14.7
4 / 15
(1) 15" x 15"
VL40 / AK66
2
⅓ - 1,075
22/ 3
7,200
35.3
2
⅓ - 1,075
22/ 3
7,200
35.3
2
⅓ - 1,075
22/ 3
7,200
35.3
Rows Deep / Fins per Inch
Piston Size (Heaꢀng)
Compressor
2/3 rows 15 fpi
0.067
2/3 rows 15 fpi
0.067
2/3 rows 15 fpi
0.067
Quanꢀty / Stage
Type
2 / Single
Scroll
2 / Single
Scroll
2 / Single
Scroll
Compressor RLA / LRA ea.
Electrical Data / Static
Voltage / Phase / Frequency
Standard Max Staꢀc
Outdoor Fan FLA ea.
Total Unit Amps
Min. Circuit Ampacity¹
Max. Overcurrent Protecꢀon (amps)²
Entrance Power Supply
Entrance Control Voltage
Operating Weight (lbs)
Ship Weight (lbs)
22.4 / 149
10.6 / 75
7.7 / 54
208-230/ 3/ 60
460/ 3/ 60
575/ 3/ 60
1.4"
0.9
21.4
23
30
Locaꢀng
Dimple
1.4"
2.4
59
65
80
Locaꢀng
Dimple
1325
1350
1.4"
1.2
28
31
40
Locaꢀng
Dimple
1325
1350
1325
1350
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
²
6
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
ProduCt SPeCifiCationS
exPanded Heating data
CPH090
Outdoor Ambient Temperature
35 30 25 20
65
60
55
50
47
45
40
17
15
10
5
0
-5
32.2 26.4
9.9 8.2
-10
MBh
T/R
114.4 108.3 101.9 95.3
35.3 33.4 31.5 29.4
8.22 8.06 7.91 7.75
30.2 28.4 26.9 25.6
4.07 3.93 3.77 3.60
91.0 88.2 81.9 75.5
28.1 27.2 25.3 23.3
7.66 7.59 7.44 7.29
24.9 24.5 23.4 22.5
3.48 3.40 3.22 3.03
70.5 65.0 59.9 56.6
21.7 20.1 18.5 17.5
6.93 6.78 6.63 6.54
21.8 21.1 20.3 20.0
2.98 2.81 2.64 2.53
54.5 48.9 43.3 37.8
16.8 15.1 13.4 11.7
6.49 6.33 6.19 6.04
19.8 19.1 18.2 17.4
2.46 2.26 2.05 1.83
kW
5.89 5.74
16.5 15.4
1.60 1.35
Amps
COP
HI PR
LO PR
424
134
406
124
390
117
373
107
365
101
358
97
344
89
330
80
316
72
302
64
290
56
283
52
278
51
267
43
257
37
246
31
238
27
229
21
CPH102
Outdoor Ambient Temperature
35 30 25 20
65
60
55
50
47
45
40
17
15
10
5
0
-5
-10
MBh
T/R
128.2 121.4 114.2 106.8 102.0 98.8 91.8 84.7
69.2 63.8 58.8 55.5
18.8 17.4 16.0 15.1
53.4 48.0 42.5 37.1
14.6 13.1 11.6 10.1
31.6 25.9
34.9 33.1 31.1 29.1
9.34 9.17 8.99 8.82
37.6 35.2 33.2 31.6
4.02 3.87 3.72 3.54
13.7 13.2 12.7 12.1
27.8 26.9 25.0 23.1
8.72 8.64 8.48 8.30
30.6 30.1 28.7 27.5
3.42 3.35 3.17 2.98
11.7 11.4 10.8 10.2
8.6
6.7
7.1
6.5
kW
7.8
7.7
7.5
7.4
7.3
7.2
7.0
6.9
Amps
COP
EER
26.6 25.6 24.6 24.2
23.9 23.0 21.8 20.8
19.6 18.2
2.6
8.8
2.4
8.3
2.3
7.8
2.2
7.5
2.1
7.3
2.0
6.7
1.8
6.1
1.6
5.4
1.4
4.7
1.2
4.0
HI PR
LO PR
419
136
401
126
386
118
369
108
360
103
354
99
340
91
326 312.5 298.4 286.5 279.7 274.6 264.2 254.1 243.6 235.0 226.7
81
73
65
57
53
51
43
37
32
28
22
CPH120
Outdoor Ambient Temperature
35 30 25 20
65
60
55
50
47
45
40
17
15
10
5
0
-5
-10
MBh
T/R
150.8 142.8 134.4 125.6 120.0 116.3 108.0 99.6
34.9 33.1 31.1 29.1 27.8 26.9 25.0 23.1
10.70 10.50 10.31 10.11 10.00 9.92 9.73 9.54
87.7 81.0 74.6 70.4
20.3 18.7 17.3 16.3
8.65 8.47 8.30 8.20
30.2 29.3 28.3 27.8
2.97 2.80 2.63 2.51
67.8 60.8 53.9 47.0
15.7 14.1 12.5 10.9
8.13 7.95 7.78 7.61
27.6 26.6 25.4 24.4
2.44 2.24 2.03 1.81
40.1 32.9
9.3 7.6
kW
7.44 7.27
23.3 21.8
1.58 1.32
Amps
COP
41.3 38.9 36.9 35.3
4.13 3.98 3.82 3.64
34.3 33.8 32.4 31.2
3.51 3.43 3.25 3.06
HI PR
LO PR
439
133
421
123
405
115
387
106
378
100
371
96
356
89
342
79
328
71
313
64
301
56
293
52
288
50
277
42
266
37
256
31
246
27
238
21
CPH150
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh 188.6 178.5 168.0 157.1 150.0 145.4 135.0 124.5 102.2 94.3
86.8
19.1
82.0
18.1
79.0
17.4
70.8
15.6
62.8
13.8
54.8
12.1
46.7 38.3
10.3 8.4
T/R
KW
41.6 39.4
37.0
34.6
33.1
32.0
29.8
27.4
22.5
20.8
14.59 14.30 14.00 13.71 13.54 13.42 13.13 12.84 12.18 11.89 11.62 11.45 11.34 11.05 10.78 10.50 10.21 9.94
AMPS 58.8 55.0
52.0
3.51
434
113
49.3
3.35
415
103
47.8
3.24
405
98
47.0
3.17
398
94
44.8
3.01
382
86
42.9
2.84
367
77
41.4
2.46
351
69
39.9
2.32
336
62
38.3
2.19
322
54
37.6
2.10
315
51
37.2
2.04
309
49
35.7
1.88
297
41
33.8
1.71
286
36
32.3
1.53
274
30
30.4 28.1
1.34 1.13
COP
HI PR
LO PR
3.78 3.65
471
129
452
120
264
26
255
21
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
High pressure measured at liquid line access fitting; Low pressure measured at compressor suction access fitting.
Amps = unit amps (comp.+fans)
kW = Total system power
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
7
ProduCt SPeCifiCationS
exPanded Cooling data — 7½ tonS
8
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
ProduCt SPeCifiCationS
exPanded Cooling data — 7½ tonS (Cont.)
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
9
ProduCt SPeCifiCationS
exPanded Cooling data — 8½ tonS
10
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
ProduCt SPeCifiCationS
exPanded Cooling data — 8½ tonS (Cont.)
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
11
ProduCt SPeCifiCationS
exPanded Cooling data — 10 tonS
12
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
ProduCt SPeCifiCationS
exPanded Cooling data — 10 tonS (Cont.)
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
13
ProduCt SPeCifiCationS
exPanded Cooling data — 12½ tonS
14
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
ProduCt SPeCifiCationS
exPanded Cooling data — 12½ tonS (Cont.)
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
15
ProduCt SPeCifiCationS
airflow data — 7½ tonS
Standard Belt Drive — Down Shot
Turns Open
ESP, In
0
1
2
3
4
5
H2O
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
3617 704 1.07 3293 653 0.84
0.1
0.3
0.5
0.7
0.9
1.1
3541 749 1.15 3179 704 0.88 2757 656 0.66
3447 798 1.23 3049 754 0.94 2606 710 0.71
3400 848 1.33 2950 798 1.01 2474 754 0.75
3303 890 1.41 2871 848 1.11 2408 804 0.82
2838 897 1.23
High-Static Belt Drive — Down Shot (A Models only)
Turns Open
ESP, In
H2O
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
3401 909 1.51
0.9
1.1
1.3
1.5
1.7
1.9
2.1
3428 965 1.71 2943 915 1.3
3471 1015 1.9 3012 971 1.5 2423 920 1.12
3722 1063 2.25 3041 1023 1.67 2503 976 1.31
3359 1075 2.04 2540 1031 1.5
3381 1119 2.22 2890 1080 1.78
3089 1129 2.04
Standard Belt Drive — Horizontal
Turns Open
ESP, In
H2O
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
3625 701 1.08 3309 660 0.86
3815 797 1.44 3468 747 1.11 3177 703 0.88 2796 663 0.68
3780 841 1.52 3405 803 1.23 3053 753 0.94 2608 709 0.68 2225 665 0.53
3687 885 1.6 3327 847 1.29 2968 805 1.02 2423 758 0.73
3236 891 1.39 2850 852 1.1 2352 807 0.8
0.1
0.3
0.5
0.7
0.9
1.1
2713 896 1.17
High-Static Belt Drive — Horizontal (A Models only)
Turns Open
ESP, In
H2O
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.9
1.1
1.3
1.5
1.7
1.9
2.1
3447 902 1.54
3398 956 1.65 3006 908 1.31
3486 1008 1.87 2960 962 1.44
3514 1057 2.07 2949 1019 1.62
3388 1103 2.18 3036 1069 1.84
2959 1114 2.0
2527 1124 1.86
Notes :
Assume dry coil with filter in place; CFM correction for wet coil = 3%
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that exceed the above
could require a larger motor. Minimum rated SCFM is 350 per ton.
16
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
ProduCt SPeCifiCationS
airflow data — 8½ tonS
Standard Belt Drive — Down Shot
Turns Open
ESP, In
0
1
2
3
4
5
H2O
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
3467 701 1.04 3143 650 0.81
0.1
0.3
0.5
0.7
0.9
1.1
3391 746 1.12 3029 701 0.85 2607 653 0.63
3297 795 1.20 2899 751 0.91 2456 707 0.68
3250 845 1.30 2800 795 0.98
3153 887 1.38 2721 845 1.08
2688 894 1.20
High-Static Belt-Drive — Down Shot
Turns Open
ESP, In
H2O
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.9
1.1
1.3
1.5
1.7
1.9
2.1
3251 906 1.48
3278 962 1.68 2793 912 1.27
3321 1012 1.87 2862 968 1.47
3572 1060 2.22 2891 1020 1.64
3209 1072 2.01
3231 1116 2.19 2740 1077 1.75
3256 1156 2.31 2939 1126 2.01
Standard Belt Drive — Horizontal
Turns Open
ESP, In
H2O
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
3475 698 1.05 3159 657 0.83
3665 794 1.41 3318 744 1.08 3027 700 0.85 2646 660 0.65
3630 838 1.49 3255 800 1.2 2903 750 0.91 2458 706 0.65
3537 882 1.57 3177 844 1.26 2818 802 0.99
3086 888 1.36 2700 849 1.07
0.1
0.3
0.5
0.7
0.9
1.1
2563 893 1.14
High-Static Belt-Drive — Horizontal
Turns Open
ESP, In
H2O
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
3297 899 1.51
0.9
1.1
1.3
1.5
1.7
1.9
3248 953 1.62 2856 905 1.28
3336 1005 1.84 2810 959 1.41
3364 1054 2.04 2799 1016 1.59
3238 1100 2.15 2886 1066 1.81
3188 1146 2.23 2809 1111 1.97
Notes :
Assume dry coil with filter in place; CFM correction for wet coil = 3%
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that exceed the above could
require a larger motor. Minimum rated SCFM is 350 per ton.
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
17
ProduCt SPeCifiCationS
airflow data — 10 tonS
Standard Belt Drive — Down shot
Turns Open
ESP, In
0
1
2
3
4
5
H2O
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
4629 774 1.76 4269 733 1.42
0.2
0.4
0.6
0.8
1
4539 824 1.86 4198 781 1.53 3797 735 1.21
4511 868 2.01 4103 829 1.63 3752 787 1.33 3312 745 1.03
4445 912 2.14 4144 873 1.81 3695 833 1.45 3180 790 1.07
4418 956 2.3 4073 917 1.92 3661 879 1.55
4064 967 2.09 3518 923 1.6
1.2
1.4
3555 972 1.77
High-Static Belt Drive — Down shot
Turns Open
ESP, In
H2O
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
4681 937 2.38 4206 891 1.91
0.8
1
4634 985 2.57 4288 948 2.19 3721 897 1.63
4533 1020 2.63 4367 995 2.41 3845 954 1.91
4550 1064 2.83 4290 1042 2.56 3913 1006 2.13
4327 1087 2.73 3990 1057 2.37
1.2
1.4
1.6
1.8
2
4652 1148 3.33 4023 1105 2.58
4306 1162 3.05
Standard Belt Drive — Horizontal
Turns Open
ESP, In
H2O
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
4707 724 1.62
0.2
0.4
0.6
0.8
1
4679 774 1.78 4235 730 1.4
4595 822 1.91 4223 780 1.55 3679 735 1.16
4468 862 1.96 4121 824 1.64 3596 785 1.26
4349 907 2.06 3990 868 1.72 3463 829 1.31
4486 962 2.35 3923 918 1.84 3267 879 1.33
3990 967 2.03
1.2
1.4
High-Static Belt Drive — Horizontal
Turns Open
ESP, In
H2O
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
4604 886 2.15
0.8
1
4737 940 2.48 4236 890 1.93
1.2
1.4
1.6
1.8
2
4792 984 2.69 4347 946 2.19 3675 901 1.64
4431 998 2.46 4404 995 2.45 3710 956 1.82
4652 1061 2.93 4183 1028 2.42 3845 1006 2.08
4418 1083 2.81 3847 1050 2.22
4823 1149 3.5 4055 1105 2.6
18
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
ProduCt SPeCifiCationS
airflow data — 12½ tonS
Standard Belt Drive --- Down Shot
Turns Open
ESP (in
0
1
2
3
4
5
W.C.)
CFM
BHP
CFM
BHP
CFM
5378
4750
4488
4019
BHP
2.35
1.97
1.81
1.55
CFM
4967
4583
4258
BHP
1.92
1.71
1.54
CFM
4710
4319
BHP
1.59
1.40
CFM
4512
4030
BHP
1.33
1.13
0.2
0.4
0.6
0.8
1.0
5514
5204
4830
4497
2.92
2.69
2.42
2.19
5349
4919
4649
4264
2.56
2.27
2.09
1.86
High-Static Belt Drive --- Down Shot
Turns Open
ESP (in
W.C.)
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
5978
5656
5459
4844
4404
BHP
3.87
3.58
3.40
2.88
2.54
CFM
5691
5376
4950
4525
BHP
3.38
3.12
2.79
2.45
CFM
5324
4933
4441
BHP
2.81
2.52
2.18
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
5947
5708
5245
4894
4495
4142
4.16
3.93
3.48
3.17
2.83
2.55
5776
5465
5145
4805
4429
4.64
4.30
3.97
3.63
3.27
5510
5199
4871
4565
4233
4.07
3.74
3.41
3.13
2.85
Standard Belt Drive --- Horizontal
Turns Open
ESP (in
W.C.)
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
5570
4902
4603
4393
BHP
2.27
1.88
1.72
1.61
CFM
4935
4637
4341
BHP
1.70
1.55
1.41
CFM
4584
4178
BHP
1.36
1.19
0.2
0.4
0.6
0.8
1.0
1.2
5871
5610
5391
5078
4521
3.20
3.00
2.83
2.59
2.20
5639
5358
5010
4676
4226
2.77
2.57
2.33
2.11
1.83
5307
5051
4799
4448
2.31
2.15
2.00
1.79
High-Static Belt Drive --- Horizontal
Turns Open
ESP (in
W.C.)
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
5858
5502
5110
4793
4382
BHP
3.51
3.20
2.88
2.64
2.34
CFM
5538
5282
4869
4598
BHP
2.97
2.78
2.47
2.28
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
5894
5570
5312
4945
4504
3.85
3.55
3.33
3.01
2.66
5780
5501
5257
5020
4601
4222
4.04
3.77
3.54
3.32
2.96
2.65
5900
5514
5315
4906
4541
4.49
4.08
3.88
3.49
3.15
5860
5615
5529
4938
4.76
4.49
4.40
3.78
Notes
•
•
•
Assume dry coil with filter in place; CFM correcꢀon for wet coil = 3%
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applicaꢀon
that exceed the above could require a larger motor. Minimum rated SCFM is 350 per ton.
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
19
ProduCt SPeCifiCationS
Heat kit eleCtriCal data — 7½ tonS
Model and
Heat Kit Usage
MCA¹
at 208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPH090***3B***
40
50
EHK3-16
EHK3-30
EHK3-45
74 / 85
80 / 90
15
30
43
3000-3375 CFM
3000-3375 CFM
3000-3375 CFM
113 / 130
147 / 169
120 / 150
150 / 175
Model and
Heat Kit Usage
MCA¹
at 208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPH090***4B***
EHK4-16
19
42
64
84
25
45
70
90
15
30
43
3000-3375 CFM
3000-3375 CFM
3000-3375 CFM
EHK4-30
EHK4-45
Model and
Heat Kit Usage
MCA¹
at 208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPH090***7B***
14
32
51
15
35
60
EHK4-16
EHK4-30
15
30
---
---
EHK4-45
68
70
43
---
¹
Minimum Circuit Ampacity
²
Maximum Overcurrent Protection device
kw CorreCtion faCtorS
kW Correction Factor for 3-Phase Units
Supply Voltage
240
1
230
220
210
208
0.76
Correction Factor
0.93
0.82
0.78
kW Correction Factor for 575V Units
kW Correction Factor for 480V Units
Supply Voltage
560
550
540
Supply Voltage
460
440
430
0.8
Correction Factor
0.95
0.91
0.88
Correction Factor
0.92
0.84
Mulꢀply rated kW by correcꢀon factor to get actual kW.
For other voltage, use voltage² / 480²
minimum airflow for eleCtriC Heat
Heater Size (kW)
Minimum CFM
15
30
43
3,000
3,000
3,000
20
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
ProduCt SPeCifiCationS
Heat kit eleCtriCal data — 8½ tonS
Recommended
Airflow Range
(Downshot)
Recommended
Airflow Range
(Horizontal)
Model and
Heat Kit Usage
MCA¹
at 240V
MOP² (amps)
at 240V
Actual kW
at 240V
CPH102***3B***
EHK3-16
43
88
50
90
15
35
43
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
EHK3-30
133
173
150
175
EHK3-45
Recommended
Airflow Range
(Downshot)
Recommended
Airflow Range
(Horizontal)
Model and
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW
at 480V
CPH102***4B***
EHK4-16
20
42
65
84
25
45
70
90
15
30
43
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
EHK4-30
EHK4-45
Recommended
Airflow Range
(Downshot)
Recommended
Airflow Range
(Horizontal)
Model and
Heat Kit Usage
MCA¹
at 575V
MOP² (amps)
at 575V
Actual kW
at 575V
CPH102***7B***
EHK7-16
17
36
55
71
20
40
60
80
15
30
43
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
EHK7-30
EHK7-45
¹
²
Minimum Circuit Ampacity
Maximum Overcurrent Protecꢀon device
^ - EHK Heater Kits above require a three-phase power supply
kw CorreCtion faCtor
kW Correction Factor (for 1- & 3-Phase Units)
Supply Voltage
240
1
230
220
210
208
0.76
Correcꢀon Factor
0.93
0.82
0.78
kW Correction Factor for 480V Units
Actual Voltage
460
440
430
0.8
minimum airflow for eleCtriC Heat
Correcꢀon Factor
0.92
0.84
Min. CFM
Heater Size (kW)
Min. CFM
Horizontal
For other voltage use voltage² / 480²
Down-shot
15
30
43
3,400
3,400
3,400
3,400
3,400
3,400
kW Correction Factor for 575V Units
Supply Voltage
560
550
540
Correcꢀon Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
21
ProduCt SPeCifiCationS
Heat kit eleCtriCal data — 10 tonS
Model and
Heat Kit Usage
MCA¹ at
208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPH120***3B***
49
60
EHK3-16
EHK3-30
EHK3-45
81 / 94
90 / 100
125 / 150
175 / 200
15
35
43
3500 - 4500 CFM
3500 - 4500 CFM
4000 - 4500 CFM
122 / 139
154 / 178
Model and
Heat Kit Usage
MCA¹ at
208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPH120***3H***
50
60
EHK3-16
EHK3-30
EHK3-45
82 / 95
90 / 100
125 / 150
175 / 200
15
35
43
---
---
---
122 / 140
155 / 179
Model and
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW
at 480V
Recommended
Airflow Range
CPH120***4B***
24
46
69
89
30
50
70
90
EHK4-16
EHK4-30
EHK4-45
15
30
43
3500 - 4500 CFM
3500 - 4500 CFM
4000 - 4500 CFM
Model and
Heat Kit Usage
MCA¹
at 575V
MOP² (amps)
at 575V
Actual kW
at 575V
Recommended
Airflow Range
CPH0120***7B***
EHK7-16
17
36
55
71
20
40
60
80
15
30
43
3500 - 4500 CFM
3500 - 4500 CFM
4000 - 4500 CFM
EHK7-30
EHK7-45
¹
²
Minimum Circuit Ampacity
Maximum Overcurrent Protecꢀon device
kw CorreCtion faCtor
kW Correction Factor (for 1- & 3-Phase Units)
Supply Voltage
240
1
230
220
210
208
Correcꢀon Factor
0.93
0.82
0.78
0.76
kW Correction Factor for 480V Units
Actual Voltage
460
440
430
0.8
minimum airflow for eleCtriC Heat
Correcꢀon Factor
0.92
0.84
Min. CFM
Heater Size (kW)
Min. CFM
Horizontal
For other voltage use voltage² / 480²
Down-shot
15
30
43
4,000
4,000
4,000
4,000
4,000
4,000
kW Correction Factor for 575V Units
Supply Voltage
560
550
540
Correcꢀon Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW
22
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
ProduCt SPeCifiCationS
Heat kit eleCtriCal data — 12½ tonS
Model and
Heat Kit Usage
MCA¹ at
208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPH150***3B***
65
80
EHK3-16
EHK3-30
EHK3-45
110
155
194
110
175
200
15
30
43
4000 - 5600
4300 - 5600
4500 - 5600
Model and
Heat Kit Usage
MCA¹ at
208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPH150***4B***
31
54
76
96
40
60
EHK4-16
EHK4-30
EHK4-45
15
30
43
4000 - 5600
4300 - 5600
4500 - 5600
80
100
Model and
Heat Kit Usage
MCA¹ at
208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPH150***7B***
23
42
61
77
30
45
70
80
EHK7-16
EHK7-30
EHK7-45
15
30
43
4000 - 5600
4300 - 5600
4500 - 5600
¹
²
Minimum Circuit Ampacity (standard drive)
Maximum Overcurrent Protecꢀon device (standard drive)
kw CorreCtion faCtorS
kW Correction Factor for 1- & 3-Phase Units
Supply Voltage
240
1
230
220
210
208
Correction Factor
0.93
0.82
0.78
0.76
kW Correction Factor for 480V Units
Supply Voltage
460
440
430
0.8
Correction Factor
0.92
0.84
For other voltage, use voltage² / 480²
kW Correction Factor for 575V Units
Supply Voltage
560
550
540
Correction Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW.
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
23
Product SPecificationS
dimenSionS
L
H
Dimensions
Model
Size
H
L
7½ to 10 Tons
12½ Tons
52⅞”
58⅞”
99⅛”
99⅛”
61¾”
12⅝”
5⅞”
5
28⅜”
7⅜”
7 3/8”
RETURN
36⅜”
13⅞”
”
SUPPLY
6½”
RETURN
6¼”
Horizontal Discharge
5
5⅜”
SUPPL
Y
7½”
7
Vertical Discharge (Bottom of Unit)
24
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
Product SPecificationS
unit clearanceS
Maintain an adequate clearance around the unit for safety, service, maintenance, and proper unit
operation. Leave a total clearance of 75”on the main control panel side of the unit for possible removal
of fan shaft, coil, electric heat, and gas furnace. Leave a clearance of 48”on all other sides of the unit for
possible compressor removal or service access, and to ensure proper
ventilation and condenser airflow. Do not install the unit beneath
any obstruction. Install the unit away from all building
exhausts to inhibit ingestion of exhaust air into the unit’s
fresh-air intake.
48”
48”
36” Min.
75”
48”
electrical entrance locationS
Dimples Mark Drill Locaꢀons
11⅝”
High-Voltage Entrance
103/16”
Low-Voltage Entrance
3”
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
25
Product SPecificationS
roof curb inStallation — rigging
Provisions for forks have been included in the unit base frame. No other
fork locations are approved.
•
Unit must be lifted by the four lifting holes located at the base
frame corners.
•
•
Lifting cables should be attached to the unit with shackles.
The distance between the crane hook and the top of the unit must
not be less than 60”.
•
Two spreader bars must span over the unit to prevent damage to
the cabinet by the lift cables. Spreader bars must be of sufficient
length so that cables do not come in contact with the unit during
transport. Remove wood struts mounted beneath unit base frame
before setting unit on roof curb. These struts are intended to protect
unit base frame from fork lift damage. To remove the struts, extract
the sheet metal retainers and pull the struts through the base of the
unit. Refer to rigging label on the unit.
Important: If using bottom discharge with roof curb, duct-work
should be attached to the curb prior to installing the unit. Duct-work
dimensions are shown in Roof Curb Installation Instructions Manual.
Refer to the Roof Curb Installation Instructions
for proper curb installation. Curbing must
be installed in compliance with the National
Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb.
Return
30”
While rigging the unit, the center of gravity will
cause the condenser end to be lower than the
supply air end.
Evaporator Coil
Compressor 1
Compressor 2
Bring condenser end of unit into alignment
with the curb. With condenser end of the
unit resting on curb member and using curb
as a fulcrum, lower opposite end of the unit
until entire unit is seated on the curb. When a
rectangular cantilever curb is used, take care
to center the unit. Check for proper alignment
and orientation of supply and return openings
with duct.
Supply
49”
Corner & Center-of-Gravity Locations
7½-Ton
Weights (lbs)
8½-Ton
Weights (lbs)
10-Ton
Weights (lbs)
12½-Ton
Weights (lbs)
Unit Weights
Weight A
285
285
345
325
345
325
435
345
Weight B
Weight C
285
320
320
300
Weight D
285
300
300
240
Shipping Weight
Operaꢀng Weight
1175
1135
1310
1285
1310
1285
1350
1325
Note: These weights are calculated without accessories installed.
26
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
ProduCt SPeCifiCationS
roof CurB inStallation (Cont.)
Curb installations must comply with local codes and should follow the
established guidelines of the National Roofing Contractors Association.
Proper unit installation requires that the roof curb be firmly and permanently
attached to the roof structure. Check for adequate fastening method prior to
setting the unit on the curb.
Full perimeter roof curbs are available from the factory and are shipped
unassembled. The installing contractor is responsible for field assembly,
squaring, leveling, and mounting on the roof structure. All required hardware
necessary for the assembly of the sheet metal curb is included in the curb
accessory package.
• Determine sufficient structural support before locating and mounting the
curb and package unit.
• Duct-work must be constructed using industry guidelines. The duct-work
must be placed into the roof curb before mounting the package unit. Our
full perimeter curbs include duct connection frames to be assembled with
the curb. Cantilevered-type curbs are not available from the factory.
• Contractor furnishes curb insulation, cant strips,
flashing, and general roofing material.
3-d View
• Support curbs on parallel sides with roof members.
To prevent damage to the unit, the roof members
92¼
53¼
cannot penetrate supply and return duct openings.
Note: The unit and curb accessories are designed to
allow vertical duct installation before unit placement.
15 x 31
Supply Opening
Duct installation after unit placement is not
14
14 x 38
recommended.
Return Opening
See the manual shipped with the roof curb for
assembly and installation instructions.
1
¾
14
1
toP View
Power Wiring
Thermostat
Wiring
Power and low-Voltage BloCk loCationS
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
27
ProduCt SPeCifiCationS
wiring diagram — CPH090-120***3B/ 4B
(for modelS witH Serial numBerS 0907 and Below)
Wiring is subject to change. Always
refer to the wiring diagram or the
unit for the most up-to-date wiring.
High Voltage: Disconnꢁct all powꢁr bꢁforꢁ sꢁrvicing or installing this unit. Mulꢀplꢁ powꢁr
sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
⚠ Warning
28
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
ProduCt SPeCifiCationS
wiring diagram — CPH090-120***3B/ 4B (Cont.)
(for modelS witH Serial numBerS 0907 and Below)
Wiring is subject to change. Always
refer to the wiring diagram or the
unit for the most up-to-date wiring.
High Voltage: Disconnꢁct all powꢁr bꢁforꢁ sꢁrvicing or installing this unit. Mulꢀplꢁ powꢁr
sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
⚠ Warning
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
29
ProduCt SPeCifiCationS
wiring diagram — CPH090-120***3B/ 4B/ 7B***
OR
2
0
8
~
2
4
0
~
4
6
0
~
5
7
5
/
BK
OR
L3
BL
BK
RD
P
BR
BL
RD
PB
O
W
E
2
3
1
C
BL
RD
T3
T2
YL
OR
208 240
460
GR
EBTDR
PK
RD
OR
RD
575
R
G
R
RD
BK
L2
C
RD
RD
NO
K1
K1
TB1
S1
S2
S
U
P
P
L
BL
XFMR-R
XFMR-C
C
GR
PU
REPLACE JUMPER WITH
SMOKE/FIRE DETECTOR
T1
L1
BK
COM
BL
SEE
NOTE #2
CC2
BK
NC
M2
YL
SPEED
UP
YL
3
/
6
0
M1
BL
Y
BR
OR
PU
GND
BL
BL
GR
DC
OR
3
9
8
6
5
4
C
2
WH
PU
BL
1
3
NO
NC
OR
2
1
4
YL
Y
O
NOTE 3
PLF
7
DR
YL
SSHR
5
OR
BK
OR
WH
YL
PU
YL
BL
O
LVDR
GR
SEE NOTE 4
OR
BK
WH
W2
R
BL
WH
T
H
E
R
PLF 1
YL
PU
RD
GR
WH
BR
OR
BL
Y1
Y/Y2
R
G
BL
L1
T1
L2
T2
L3
PU
BK
RD
RD
R
HVDR
3
2
1
6
5
4
9
8
7
RD
C
DFT
RCCF2
M
T3
W1
O
DF1
DF2
RD
WH
BL
WH
OR
BR
W2
S
BC
C
F
BK
O
C
T
A
T
OR
BL
RD
OR
RD
BR
BK
++
BL
TB1
BK
RD
BK
RD
BK
YL
RD
RD
RD
YL
BK
BK
BL
T3 T2 T1
COMP2
BK
EM
DFT2
DFT1
CM2
BK
BK
LPS2
HPS2
RVC2
BR
BL
RVC1
BL
BK
PU
YL
BK
RD
RCCF1
LPS1
T2
L2
HPS1
PU
T3
T2
L3
L2
OR
RD
C
F
CMC
PU
T1
L1
RD
BR
RD
BK
BL
PU
C
BK
RD
BR
YL
L1
BK
T1
BL
CC1
CM1
BL
T3 T2 T1
COMP1
BL
0140L00546 REV B
Wiring is subject to change. Always
refer to the wiring diagram or the
unit for the most up-to-date wiring.
High Voltage: Disconnꢁct all powꢁr bꢁforꢁ sꢁrvicing or installing this unit. Mulꢀplꢁ powꢁr
sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
⚠ Warning
30
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
ProduCt SPeCifiCationS
wiring diagram — CPH090-120***3B/ 4B/ 7B*** (Cont.)
SUPPLY VOLTAGE
208-240/460/575/3/60
L3
L1
L2
FACTORY WIRING
LINE VOLTAGE
LOW VOLTAGE
CC1
T2
OPTIONAL
HIGH VOLTAGE
T2
COMP1
CC1
COMPONENT LEGEND
T1
CC1
BC
BLOWER CONTACTOR
FIELD WIRING
T3
COMPRESSOR CONTACTOR
CONDENSER MOTOR
CC
CM
HIGH VOLTAGE
LOW VOLTAGE
RCCF2
CONDENSER MOTOR CONTACTOR
COMPRESSOR
DEFROST CONTROL
CMC
COMP
DC
CMC
DEFROST THERMOSTAT
ECONOMIZER
ELECTRONIC BLOWER TIME DELAY
EVAPORATOR MOTOR RELAY
RELAY
EVAPORATOR MOTOR
FAN CAPACITOR
EQUPIMENT GROUND
HIGH PRESSURE SWITCH
HIGH VOLTAGE DEFROST RELAY
LOW PRESSURE SWITCH
LOW VOLTAGE DEFROST RELAY
POWER DISTRIBUTION BLOCK
FEMALE PLUG / CONNECTOR
REVERSING VAVLE COIL
RUN CAPACITOR FOR
CONDENSER FAN
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
DFT
ECON
EBTD
EMR
R
EM
FC
GND
HPS
HVDR
LPS
LVDR
PB
PLF
RVC
RCCF
WIRE CODE
C
CM2
BK
BL
BLACK
BLUE
RCCF
CMC
F
BR
GR
OR
PK
PU
RD
WH
YL
BROWN
GREEN
ORANGE
PINK
CM1
PURPLE
RED
CC2
WHITE
YELLOW
T2
COMP2
CC2
T1
T2
T1
YL/PK YELLOW WITH
PINK STRIP
BL/PK BLUE WITH
CC2
T3
PINK STRIP
BC
EM
208-240V
BC
BC
TB1
TR
SSHR
OR APPROPRIATE
INPUT VOLTAGE
THERMOSTAT
FIELD WIRING
SECOND STAGE HEATER RELAY
DEFROST RELAY
3
1
DR
2 STAGE COOLING
S2
S1
TR
W1
G
WH
GR
RD
YL
W1
G
24V
TB1
EBTDR
NOTES:
R
G
C
R
R
1. REPLACEMENT WIRE MUST BE SAME SIZE AND
TYPE INSULATION AS ORIGINAL (AT LEAST 105°C)
USE COPPER CONDUCTOR ONLY.
2. USE COPPER CONDUCTORS ONLY
++ USE N.E.C. CLASS 2 WIRE
3. ECONOMIZER PLUG LOCATED IN THE RETURN AIR
COMPARTMENT. REMOVE MALE PLUG AND ATTACH
FEMALE PLUG TO THE ECONOMIZER ACCESSORY.
4. FOR TWO STAGE OPERATION REMOVE W1 TO W2
JUMPER WIRE.
Y1
Y1
R
PK
BL
Y/Y2
C
Y2
C
CMC
EBTDR
C
R
HVDR
BC
OR
R
R
O
O
DFT1
DFT2
EBTDR
DFT
W2
W2
BR
DC
Y
STAT
TB1
R
W2
RVC2
RVC1
LVDR
O
5. FOR 208V OPREATION, MOVE BLACK WIRE FROM
TERMINAL 3 TO TERMINAL 2 ON 240V TRANSFORMER.
LPS1
HPS1
HPS2
LPS2 CC2
CC1
P
7
8
9
4
5
6
L
F
1
NC
NO
SSHR
3
2
1
9
8
6
5
4
PLF2
NC
NO
SEE NOTE 3
DR
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
7
208-240/460/575/3/60 0140L00547 REV. B
Y
R
W2
O
G
C
W1
Y2
Y1
SEE NOTE 4
THERMOSTAT
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
31
ProduCt SPeCifiCationS
wiring diagram — CPH150***3B/ 4B/ 7B***
OR
2
0
8
~
2
4
0
~
4
6
0
~
5
7
5
/
BK
OR
L3
BL
BK
RD
P
BR
BL
PB
RD
O
W
E
2
3
1
C
BL
RD
T3
T2
YL
OR
208 240
460
GR
EBTDR
PK
RD
OR
575
R
G
R
RD
BK
L2
C
RD
RD
NO
K1
K1
TB1
S1
RD
S2
S
U
P
P
L
BL
XFMR-R
XFMR-C
C
GR
PU
REPLACE JUMPER WITH
SMOKE/FIRE DETECTOR
L1
T1
BK
COM
BL
SEE
NOTE #2
CC2
BK
NC
M2
YL
SPEED
UP
YL
3
/
6
0
M1
BL
BR
Y
OR
PU
GND
BL
BL
GR
DC
OR
3
9
8
6
5
4
C
2
WH
PU
BL
1
3
NO
NC
OR
2
1
4
YL
Y
O
NOTE 3
PLF
7
DR
YL
SSHR
5
OR
BK
OR
WH
YL
PU
YL
BL
O
LVDR
GR
SEE NOTE 4
OR
BK
WH
W2
R
BL
WH
T
H
E
PLF 1
YL
PU
RD
GR
WH
BR
OR
BL
Y1
Y/Y2
R
BL
PU
L2
T2
L3
L1
T1
BK
RD
RD
R
HVDR
3
2
1
6
5
4
9
8
7
RD
R
G
C
DFT
RCCF2
M
T3
W1
O
DF1
DF2
WH
BL
WH
OR
W2
BR
S
BC
C
F
BK
O
C
T
A
T
RD
OR
BL
RD
OR
RD
BR
BK
++
TB1
BL
BK
RD
BK
RD
BK
YL
RD
RD
RD
YL
BK
BK
BL
T1
T3
T2
BK
EM
DFT2
DFT1
CM2
BK
BK
COMP2
LPS2
HPS2
RVC2
BR
BL
RVC1
BL
BK
PU
YL
BK
RD
RCCF1
LPS1
T2
L2
HPS1
PU
T3
T2
L3
L2
OR
C
F
CMC
L1
T1
RD
BR
RD
RD
BK
PU
BL
PU
C
BK
RD
BR
YL
L1
BK
T1
BL
CC1
CM1
BL
T3 T2
T1
BL
COMP1
0140L00546 REV B
32
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
ProduCt SPeCifiCationS
wiring diagram — CPH150***3B/ 4B/ 7B*** (Cont.)
SUPPLY VOLTAGE
208-240/460/575/3/60
L3
L1
L2
FACTORY WIRING
LINE VOLTAGE
LOW VOLTAGE
CC1
T2
OPTIONAL
HIGH VOLTAGE
T2
COMP1
CC1
COMPONENT LEGEND
T1
CC1
BC
CC
CM
BLOWER CONTACTOR
COMPRESSOR CONTACTOR
CONDENSER MOTOR
FIELD WIRING
T3
HIGH VOLTAGE
LOW VOLTAGE
RCCF2
CMC
COMP
DC
CONDENSER MOTOR CONTACTOR
COMPRESSOR
DEFROST CONTROL
CMC
DFT
ECON
EBTD
EMR
R
EM
FC
GND
HPS
HVDR
LPS
LVDR
PB
PLF
RVC
RCCF
DEFROST THERMOSTAT
ECONOMIZER
ELECTRONIC BLOWER TIME DELAY
EVAPORATOR MOTOR RELAY
RELAY
EVAPORATOR MOTOR
FAN CAPACITOR
EQUPIMENT GROUND
HIGH PRESSURE SWITCH
HIGH VOLTAGE DEFROST RELAY
LOW PRESSURE SWITCH
LOW VOLTAGE DEFROST RELAY
POWER DISTRIBUTION BLOCK
FEMALE PLUG / CONNECTOR
REVERSING VAVLE COIL
RUN CAPACITOR FOR
WIRE CODE
C
CM2
BK
BL
BLACK
RCCF
BLUE
CMC
F
BR
GR
OR
PK
PU
RD
WH
YL
BROWN
GREEN
ORANGE
PINK
PURPLE
RED
CM1
CC2
WHITE
YELLOW
T2
COMP2
CC2
T1
T2
T1
YL/PK YELLOW WITH
PINK STRIP
BL/PK BLUE WITH
CC2
T3
PINK STRIP
BC
EM
CONDENSER FAN
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
SECOND STAGE HEATER RELAY
DEFROST RELAY
208-240V
BC
BC
TB1
TR
SSHR
OR APPROPRIATE
INPUT VOLTAGE
THERMOSTAT
FIELD WIRING
1
3
DR
2 STAGE COOLING
S2
S1
TR
W1
G
WH
GR
RD
YL
W1
G
24V
TB1
EBTDR
NOTES:
R
G
C
R
R
1. REPLACEMENT WIRE MUST BE SAME SIZE AND
TYPE INSULATION AS ORIGINAL (AT LEAST 105°C)
USE COPPER CONDUCTOR ONLY.
2. USE COPPER CONDUCTORS ONLY
++ USE N.E.C. CLASS 2 WIRE
3. ECONOMIZER PLUG LOCATED IN THE RETURN AIR
COMPARTMENT. REMOVE MALE PLUG AND ATTACH
FEMALE PLUG TO THE ECONOMIZER ACCESSORY.
4. FOR TWO STAGE OPERATION REMOVE W1 TO W2
JUMPER WIRE.
Y1
Y/Y2
C
Y1
Y2
R
PK
BL
CMC
EBTDR
C
R
HVDR
C
O
BC
OR
R
R
O
DFT1
DFT2
EBTDR
DFT
W2
W2
BR
DC
Y
STAT
TB1
R
W2
RVC2
RVC1
LVDR
O
5. FOR 208V OPREATION, MOVE BLACK WIRE FROM
TERMINAL 3 TO TERMINAL 2 ON 240V TRANSFORMER.
LPS1
HPS1
HPS2 LPS2
CC2
CC1
P
7
8
9
4
5
6
L
F
1
NC
NO
SSHR
3
2
1
9
8
6
5
4
PLF2
NC
NO
SEE NOTE 3
DR
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
7
208-240/460/575/3/60 0140L00547 REV. B
Y
Y2
R
W2
O
W1
Y1
G
C
SEE NOTE 4
THERMOSTAT
++
Wiring is subject to change. Always
refer to the wiring diagram or the
unit for the most up-to-date wiring.
High Voltage: Disconnꢁct all powꢁr bꢁforꢁ sꢁrvicing or installing this unit. Mulꢀplꢁ powꢁr
sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
⚠ Warning
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
33
ProduCt SPeCifiCationS
aCCeSSorieS
Fits
Model Sizes
Item #
Description
14CURB90150
25FD90150
25MFD90150
BRD3672
Roof Curb 14" Tall
25% Manual Fresh Air Damper
7½-12½ tons
7½-12½ tons
7½-12½ tons
7½-12½ tons
10 tons
25% Motorized Fresh Air Damper
Horizontal Barometric Relief Damper (two required)
Concentric Duct Kit
CDK120
CDK150
Concentric Duct Kit
12½ tons
CDK90102
DNBBS90150
DNECONGS90120
DNECONGS150
DNSQRRND90
GHRC-1
Concentric Duct Kit
7½-8½ tons
7½-12½ tons
7½-10 tons
12½ tons
Burglar Bar Sleeves: Includes Supply & Return
Downflow Economizer
Downflow Economizer
Downflow Square-to-Round Adapter 20" Round
Hurricane Restraint Clip
7½ tons
All Models
7½-10 tons
12½ tons
HailGD02
Condenser Coil Hail Guard
HailGD05
Condenser Coil Hail Guard
HAKT36300
HSKT090
High-Alꢀtude Kit
All Models
8½ tons
High-Staꢀc Kit for 8½-ton AA models (230/460v)
High-Staꢀc Kit for AA & BA models (230/460v)
High-Staꢀc Kit for AA models (230/460v)
High-Staꢀc Kit for AA models (230/460v)
Horizontal Economizer
HSKT090G
HSKT120
7½ tons
10 tons
HSKT150
12½ tons
HZECONGS90150
LAKT02
7½-12½ tons
7½ - 12½ tons
7½ - 12½ tons
7½-12½ tons
7½-12½ tons
7½-12½ tons
Low-Ambient Kit for units with serial number below 0909
Low Ambient Kit for units with serial numbers 0909 and above
LP Conversion Kit
LAKT03
LPKT36150
PE901502
PE901504
Power Exhaust 208/230 Volt
Power Exhaust 460 Volt
34
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
ProduCt SPeCifiCationS
noteS
SS-CPH90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
35
Product SPecificationS
noteS
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without