Generac Power Systems Portable Generator 24L User Manual

Serial Number  
2.4L  
25kW  
Models  
STANDBY GENERATOR  
OWNER'S MANUAL  
A new standard of reliability  
Not intended for use in critical life support applications.  
CAUTION—  
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION!  
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!  
This manual should remain with the unit.  
. A v 0 5 / 0 7 e v r 1 1 C 2 o R e  
. 0 G 4 t N 1 r 5 o a 9 P  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Important Safety Instructions  
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation  
be copied and posted in potential hazard areas. Safety should be stressed to all operators,  
potential operators, and service and repair technicians for this equipment.  
GENERAL HAZARDS  
WARNING:  
The engine exhaust from this product  
contains chemicals known to the state  
of California to cause cancer, birth  
defects or other reproductive harm.  
For safety reasons, the manufacturer recommends  
that this equipment be installed, serviced and  
repaired by a Service Dealer or other competent,  
qualified electrician or installation technician who  
is familiar with applicable codes, standards and  
regulations. The operator also must comply with  
all such codes, standards and regulations.  
• Installation, operation, servicing and repair of this  
(and related) equipment must always comply with  
applicable codes, standards, laws and regulations.  
Adhere strictly to local, state and national electri-  
cal and building codes. Comply with regulations  
the Occupational Safety and Health Administration  
(OSHA) has established. Also, ensure that the  
generator is installed, operated and serviced in  
accordance with the manufacturer’s instructions  
and recommendations. Following installation, do  
nothing that might render the unit unsafe or in  
noncompliance with the aforementioned codes,  
standards, laws and regulations.  
• The engine exhaust fumes contain carbon monox-  
ide gas, which can be DEADLY. This dangerous gas,  
if breathed in sufficient concentrations, can cause  
unconsciousness or even death. For that reason,  
adequate ventilation must be provided. Exhaust  
gases must be piped safely away from any building  
or enclosure that houses the generator to an area  
where people, animals, etc., will not be harmed.  
This exhaust system must be installed properly, in  
strict compliance with applicable codes and stan-  
dards.  
WARNING:  
This product contains or emits chemicals  
known to the state of California to cause  
cancer, birth defects or other reproductive harm.  
Study these SAFETY RULES carefully before install-  
ing, operating or servicing this equipment. Become  
familiar with this Owner’s Manual and with the unit.  
The generator can operate safely, efficiently and reli-  
ably only if it is properly installed, operated and  
maintained. Many accidents are caused by failing to  
follow simple and fundamental rules or precautions.  
The manufacturer cannot anticipate every possible  
circumstance that might involve a hazard. The warn-  
ings in this manual, and on tags and decals affixed  
to the unit are, therefore, not all inclusive. If a pro-  
cedure, work method or operating technique is used  
that the manufacturer does not specifically recom-  
mend, ensure that it is safe for others. Also make  
sure the procedure, work method or operating tech-  
nique utilized does not render the generator unsafe.  
DANGER  
Despite the safe design of this generator,  
operating this equipment imprudently, neglect-  
ing its maintenance or being careless can cause  
possible injury or death. Permit only responsible  
and capable persons to install, operate or main-  
tain this equipment.  
• Keep hands, feet, clothing, etc., away from drive  
belts, fans, and other moving or hot parts. Never  
remove any drive belt or fan guard while the unit  
is operating.  
• Adequate, unobstructed flow of cooling and venti-  
lating air is critical in any room or building hous-  
ing the generator to prevent buildup of explosive  
gases and to ensure correct generator operation.  
Do not alter the installation or permit even partial  
blockage of ventilation provisions, as this can seri-  
ously affect safe operation of the generator.  
Potentially lethal voltages are generated by  
these machines. Ensure all steps are taken to  
render the machine safe before attempting to  
work on the generator.  
Parts of the generator are rotating and/or hot  
during operation. Exercise care near running  
• Keep the area around the generator clean and  
uncluttered. Remove any materials that could  
become hazardous.  
generators.  
• When working on this equipment, remain alert  
at all times. Never work on the equipment when  
physically or mentally fatigued.  
• Inspect the generator regularly, and promptly  
repair or replace all worn, damaged or defective  
parts using only factory-approved parts.  
. A v 0 4 / 0 7 e t y 0 S 0 a 4 f R e  
1-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Important Safety Instructions  
• Before performing any maintenance on the gen-  
• Generators installed with an automatic transfer  
switch will crank and start automatically when  
normal (utility) source voltage is removed or is  
below an acceptable preset level. To prevent such  
automatic start-up and possible injury to person-  
nel, disable the generator’s automatic start circuit  
(battery cables, etc.) before working on or around  
the unit. Then, place a “Do Not Operate” tag on  
the generator control panel and on the transfer  
switch.  
erator, disconnect its battery cables to prevent  
accidental start-up. Disconnect the cable from the  
battery post indicated by a NEGATIVE, NEG or (–)  
first. Reconnect that cable last.  
• Never use the generator or any of its parts as a  
step. Stepping on the unit can stress and break  
parts, and may result in dangerous operating con-  
ditions from leaking exhaust gases, fuel leakage,  
oil leakage, etc.  
• In case of accident caused by electric shock, imme-  
diately shut down the source of electrical power.  
If this is not possible, attempt to free the victim  
from the live conductor. AVOID DIRECT CONTACT  
WITH THE VICTIM. Use a nonconducting imple-  
ment, such as a dry rope or board, to free the vic-  
tim from the live conductor. If the victim is uncon-  
scious, apply first aid and get immediate medical  
help.  
• Never wear jewelry when working on this equip-  
ment. Jewelry can conduct electricity resulting in  
electric shock, or may get caught in moving com-  
ponents causing injury.  
ELECTRICAL HAZARDS  
• All generators covered by this manual produce  
dangerous electrical voltages and can cause fatal  
electrical shock. Utility power delivers extremely  
high and dangerous voltages to the transfer switch  
as well as the standby generator. Avoid contact  
with bare wires, terminals, connections, etc., on  
the generator as well as the transfer switch, if  
applicable. Ensure all appropriate covers, guards  
and barriers are in place before operating the gen-  
erator. If work must be done around an operating  
unit, stand on an insulated, dry surface to reduce  
shock hazard.  
• Do not handle any kind of electrical device while  
standing in water, while barefoot, or while hands or  
feet are wet. DANGEROUS ELECTRICAL SHOCK  
MAY RESULT.  
• If personnel must stand on metal or concrete while  
installing, operating, servicing, adjusting or repair-  
ing this equipment, place insulative mats over a  
dry wooden platform. Work on the equipment only  
while standing on such insulative mats.  
FIRE HAZARDS  
• Keep a fire extinguisher near the generator at all  
times. Do NOT use any carbon tetra-chloride type  
extinguisher. Its fumes are toxic, and the liquid  
can deteriorate wiring insulation. Keep the extin-  
guisher properly charged and be familiar with its  
use. If there are any questions pertaining to fire  
extinguishers, consult the local fire department.  
• The National Electrical Code (NEC) requires the  
frame and external electrically conductive parts  
of the generator to be connected to an approved  
earth ground. This grounding will help prevent  
dangerous electrical shock that might be caused  
by a ground fault condition in the generator set or  
by static electricity. Never disconnect the ground  
wire.  
• Wire gauge sizes of electrical wiring, cables and  
cord sets must be adequate to handle the maxi-  
mum electrical current (ampacity) to which they  
will be subjected.  
• Before installing or servicing this (and related)  
equipment, make sure that all power voltage  
supplies are positively turned off at their source.  
Failure to do so will result in hazardous and pos-  
sibly fatal electrical shock.  
• Connecting this unit to an electrical system nor-  
mally supplied by an electric utility shall be by  
means of a transfer switch so as to isolate the  
generator electric system from the electric utility  
distribution system when the generator is operat-  
ing. Failure to isolate the two electric system power  
sources from each other by such means will result  
in damage to the generator and may also result  
in injury or death to utility power workers due to  
backfeed of electrical energy.  
EXPLOSION HAZARDS  
• Properly ventilate any room or building housing  
the generator to prevent build-up of explosive gas.  
• Do not smoke around the generator. Wipe up any  
fuel or oil spills immediately. Ensure that no com-  
bustible materials are left in the generator com-  
partment, or on or near the generator, as FIRE or  
EXPLOSION may result. Keep the area surround-  
ing the generator clean and free from debris.  
• These generator sets may operate using one of  
several types of fuels. All fuel types are potentially  
FLAMMABLE and/or EXPLOSIVE and should be  
handled with care. Comply with all laws regulat-  
ing the storage and handling of fuels. Inspect the  
unit’s fuel system frequently and correct any leaks  
immediately. Fuel supply lines must be prop-  
erly installed, purged and leak tested according to  
applicable fuel-gas codes before placing this equip-  
ment into service.  
• Diesel fuels are highly FLAMMABLE. Gaseous  
fluids such as natural gas and liquid propane  
(LP) gas are extremely EXPLOSIVE. Natural gas  
is lighter than air, and LP gas is heavier than air;  
install leak detectors accordingly.  
. A v 0 4 / 0 7 e t y 0 S 0 a 4 f R e  
1-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Important Safety Instructions  
INTRODUCTION  
Thank you for purchasing this model of the standby  
generator set product line.  
This symbol points out potential explosion  
hazard.  
This symbol points out potential fire hazard.  
Every effort was expended to make sure that the  
information and instructions in this manual were  
both accurate and current at the time the manual was  
written. However, the manufacturer reserves the right  
to change, alter or otherwise improve this product(s)  
at any time without prior notice.  
This symbol points out potential electrical shock  
hazard.  
The operator is responsible for proper and safe use  
of the equipment. The manufacturer strongly recom-  
mends that the operator read this Owner's Manual  
and thoroughly understand all instructions before  
using this equipment. The manufacturer also strong-  
ly recommends instructing other users to properly  
start and operate the unit. This prepares them if they  
need to operate the equipment in an emergency.  
READ THIS MANUAL THOROUGHLY  
If any portion of this manual is not understood, con-  
tact the nearest Service Dealer for starting, operating  
and servicing procedures.  
Throughout this publication, and on tags and  
decals affixed to the generator, DANGER, WARNING,  
CAUTION and NOTE blocks are used to alert person-  
nel to special instructions about a particular service  
or operation that may be hazardous if performed  
incorrectly or carelessly. Observe them carefully.  
Their definitions are as follows:  
OPERATION AND MAINTENANCE  
It is the operator's responsibility to perform all safety  
checks, to make sure that all maintenance for safe  
operation is performed promptly, and to have the  
equipment checked periodically by a Service Dealer.  
Normal maintenance service and replacement of parts  
are the responsibility of the owner/operator and, as  
such, are not considered defects in materials or work-  
manship within the terms of the warranty. Individual  
operating habits and usage contribute to the need for  
maintenance service.  
DANGER  
After this heading, read instructions that, if not  
strictly complied with, will result in personal injury  
or property damage.  
Proper maintenance and care of the generator ensure  
a minimum number of problems and keep operating  
expenses at a minimum. See a Service Dealer for ser-  
vice aids and accessories.  
After this heading, read instructions that, if not  
strictly complied with, may result in personal  
injury or property damage.  
Operating instructions presented in this manual  
assume that the standby electric system has been  
installed by a Service Dealer or other competent,  
qualified contractor. Installation of this equipment is  
not a “do-it-yourselfproject.  
After this heading, read instructions that, if not  
strictly complied with, could result in damage to  
equipment and/or property.  
HOW TO OBTAIN SERVICE  
NOTE:  
When the generator requires servicing or repairs,  
simply contact a Service Dealer for assistance.  
Service technicians are factory-trained and are capa-  
ble of handling all service needs.  
After this heading, read explanatory statements  
that require special emphasis.  
These safety warnings cannot eliminate the hazards  
that they indicate. Common sense and strict compli-  
ance with the special instructions while performing  
the service are essential to preventing accidents.  
When contacting a Service Dealer about parts and  
service, always supply the complete model number of  
the unit as given on the front cover of this manual or  
on the DATA LABEL affixed to the unit.  
Four commonly used safety symbols accompany the  
DANGER, WARNING and CAUTION blocks. The type  
of information each indicates is as follows:  
This symbol points out important safety infor-  
mation that, if not followed, could endanger  
personal safety and/or property of others.  
. A v 0 4 / 0 7 e t y 0 S 0 a 4 f R e  
1-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
General Information  
NOTE:  
IDENTIFICATION RECORD  
For actual information related to this particular  
model, please refer to the Manual Drawing Listing  
located at the end of this manual, or to the data  
label affixed to the unit.  
DATA LABEL  
Every generator set has a DATA LABEL that contains  
important information pertinent to the generator. The  
data label, which can be found attached to the gen-  
erator’s lower connection box, lists the unit’s serial  
number and its rated voltage, amps, wattage capacity,  
phase, frequency, rpm, power factor, etc.  

Generator Model and Serial Number  
This number is the key to numerous engineering and  
manufacturing details pertaining to your unit. Always  
supply this number when requesting service, order-  
ing parts or seeking information.  
Data Label  
MANUFACTURING INFORMATION  
. A v 0 3 / 0 7  
I d e n t y 0 0 5 R e  
2-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Equipment Description  
EQUIPMENT DESCRIPTION  
COOLANT RECOMMENDATIONS  
This equipment is a revolving field, alternating cur-  
rent generator set. It is powered by a gaseous fueled  
engine operating at 1800 rpm for 4-pole direct drive  
units, 3600 rpm for 2-pole direct drive units and  
2300 - 3000 rpm for quiet drive gear units. See the  
Specifications section for exact numbers. The unit  
comes complete with a sound attenuated enclosure,  
internally mounted muffler, control console, main-  
line circuit breaker, battery charger, and protective  
alarms as explained in the following paragraph.  
Use a mixture of half low silicate ethylene glycol  
base anti-freeze and deionized water. Cooling system  
capacity is listed in the specifications. Use only deion-  
ized water and only low silicate anti-freeze. If desired,  
add a high quality rust inhibitor to the recommended  
coolant mixture. When adding coolant, always add  
the recommended 50-50 mixture.  
Do not use any chromate base rust inhibitor  
All AC connections, including the power leads from  
the alternator, 120 volt battery charger input and  
control connections to the transfer switch are avail-  
able in the main connection box.  
with ethylene glycol base anti-freeze or chro-  
mium hydroxide (“green slime”) forms and will  
cause overheating. Engines that have been oper-  
ated with a chromate base rust inhibitor must  
be chemically cleaned before adding ethylene  
glycol base anti-freeze. Using any high silicate  
anti-freeze boosters or additives will also cause  
overheating. The manufacturer also recommends  
that any soluble oil inhibitor is NOT used for this  
equipment.  
The generator incorporates the following generator  
features:  
• Rotor and Stator insulation is Class F rated as  
defined by NEMA MG1-32.6, NEMA MG1-1.66.  
The generator is self ventilated and drip-proof con-  
structed.  
• The voltage waveform deviation, total harmonic  
content of the AC waveform and telephone influ-  
ence factor have been evaluated and are acceptable  
according to NEMA MG1-32.  
DANGER  
Do not remove the radiator pressure cap while  
the engine is hot or serious burns from boiling  
liquid or steam could result.  
Ethylene glycol base antifreeze is poisonous.  
Do not use mouth to siphon coolant from the  
radiator, recovery bottle or any container. Wash  
hands thoroughly after handling. Never store  
used antifreeze in an open container because  
animals are attracted to the smell and taste of  
antifreeze even though it is poisonous to them.  
ENGINE OIL RECOMMENDATIONS  
The unit has been filled with 15W-40 engine oil at  
the factory. Use a high-quality detergent oil classi-  
fied “For Service SJ or SH.” Detergent oils keep the  
engine cleaner and reduce carbon deposits. Use oil  
having the following SAE viscosity rating, based on  
the ambient temperature range anticipated before the  
next oil change:  
Temperature  
Above 80° F (27° C)  
32° to 80° F (0° to 27° C)  
Below 32° F (0° C)  
Oil Grade (Recommended)  
SAE 30W or 15W-40  
SAE 20W-20 or 15W-40  
See Note  
Any attempt to crank or start the engine before  
it has been properly serviced with the recom-  
mended oil may result in an engine failure.  
NOTE:  
For temperatures below 32° F, it is strongly recom-  
mended to use the optional Cold Weather Start Kit  
(part number listed in the Specification Section).  
The oil grade for temperatures below 32° F is 5W-  
30 synthetic oil.  
. A v 0 8 / 0 6  
E q u i p 0 0 2 R e  
3-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Engine Protective Devices  
OVERCRANK SHUTDOWN  
ENGINE PROTECTIVE DEVICES  
The standby generator may be required to operate for  
long periods of time without an operator on hand to  
monitor such engine conditions as coolant tempera-  
ture, oil pressure or rpm. For that reason, the engine  
has several devices designed to protect it against  
potentially damaging conditions by automatically  
shutting down the unit when the oil pressure is too  
low, the coolant temperature is too high, the coolant  
level is too low, or the engine is running too fast.  
After a prespecified duration of cranking, this func-  
tion ends the cranking if the engine has failed to  
start. The overcrank LED will turn ON. Turn OFF the  
AUTO/OFF/MANUAL switch, then turn switch back to  
AUTO to reset the generator control board.  
NOTE:  
If the fault is not corrected, the overcrank feature  
will continue to activate.  
NOTE:  
Approximate Crank Cycle Times  
• 15 seconds ON  
• 7 seconds OFF  
• 7 seconds ON  
Engine protective switches and sensors are men-  
tioned here for the reader’s convenience. Also  
refer to the applicable control panel manual for  
additional automatic engine shutdown informa-  
tion.  
• 7 seconds OFF  
• Repeat for 45 seconds  
Approximately 90 seconds total.  
HIGH COOLANT TEMPERATURE SWITCH  
This switches contacts close if the temperature should  
exceed approximately 140° C (284° F), initiating an  
engine shutdown. The generator will automatically  
restart and the LED will reset once the temperature  
has returned to a safe operating level.  
OVERSPEED SHUTDOWN  
A speed circuit controls engine cranking, start-up,  
operation and shutdown. Engine speed signals are  
delivered to the circuit board whenever the unit is  
running. Should the engine overspeed above a safe,  
preset value, the circuit board initiates an automatic  
engine shutdown. Contact the nearest Authorized  
Dealer if this failure occurs.  
LOW COOLANT LEVEL SENSOR  
Should the engine coolant level drop below the level  
of the high coolant temperature switch, it is possible  
for the engine to overheat without automatic shut-  
down. To prevent such overheating, the engine has a  
low coolant level sensor. If the level of engine coolant  
drops below the level of the low coolant level sensor,  
the engine automatically shuts down.  
RPM SENSOR LOSS SHUTDOWN  
If the speed signal to the control panel is lost, engine  
shutdown will occur.  
DC FUSE  
LOW OIL PRESSURE SWITCH  
This fuse is located inside of the control panel. It  
protects the panel wiring and components from  
damaging overload. Always remove this fuse before  
commencing work on the generator. The unit will  
not start or crank if the fuse is blown. Replace the  
fuse with one of the same size, type, and rating. (See  
the exploded views and parts lists at the end of this  
manual for replacement part number.)  
This switch has normally closed contacts that are  
held open by engine oil pressure during cranking and  
operating. Should oil pressure drop below the 8 psi  
range, switch contacts close, and the engine shuts  
down. The unit should not be restarted until oil is  
added, and the AUTO/OFF/MANUAL switch must be  
turned to OFF and then back to AUTO.  
. 0 v 0 8 / 0 5  
E n g P r o t 0 0 1 R  
4-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Fuel Systems  
PROPANE VAPOR WITHDRAWAL FUEL SYSTEM  
FUEL SYSTEM  
This type of system utilizes the vapors formed above  
the liquid fuel in the supply tank. Approximately 10  
to 20 percent of the tank capacity is needed for fuel  
expansion from the liquid to the vapor state. The  
vapor withdrawal system is generally best suited for  
smaller engines that require less fuel. The installer  
should be aware of the following:  
FUEL REQUIREMENTS  
The standby generator may be equipped with one of  
the following fuel systems:  
• Natural gas fuel system  
• Propane vapor (PV) fuel system  
The Manual Drawing Listing that is affixed to the  
unit includes the “Identification Code,” which may be  
used to identify the type of fuel system installed on  
the unit.  
• The natural gas and LP gas systems are similar.  
However, the natural gas system delivers gas at a  
pressure of approximately five inches water col-  
umn to the carburetor.  
Recommended fuels should have a Btu content of at  
least 1,000 Btus per cubic foot for natural gas; or at  
least 2,520 Btus per cubic foot for LP gas. Ask the  
fuel supplier for the Btu content of the fuel.  
• When ambient temperatures are low and engine  
fuel consumption is high, the vapor withdrawal  
system may not function efficiently.  
• Ambient temperatures around the supply tank  
must be high enough to sustain adequate vaporiza-  
tion, or the system will not deliver the needed fuel  
volume.  
• In addition to the cooling effects of ambient air, the  
vaporization process itself provides an additional  
cooling effect.  
Required fuel pressure for natural gas is 5 inches  
to 14 inches water column (0.18 to 0.5 psi); and  
for liquid propane, 5 inches to 14 inches of water  
column (0.18 to 0.5 psi).  
NOTE:  
Any piping used to connect the generator to the  
fuel supply should be of adequate size to ensure  
the fuel pressure NEVER drops below five inches  
water column for natural gas or 5 inches water  
column for propane vapor for all load ranges.  
LP FUEL SYSTEM  
LP is supplied as a liquid in pressure tanks. It is  
usually made up of propane, butane, or a mixture of  
the two gases. Propane tends to vaporize readily even  
at temperatures as low as -20° F (-29° C). However,  
butane reverts to its liquid state when temperatures  
drop below 32° F (0° C).  
NOTE:  
It is the responsibility of the installer to make sure  
that only the correct recommended fuel is sup-  
plied to the generator fuel system. Thereafter, the  
owner/operator must make certain that only the  
proper fuel is supplied.  
LP in a liquid withdrawal system must be converted  
to its gaseous state before it is introduced into the  
engine carburetor. A vaporizer-converter is generally  
used to accomplish this. In such a converter, heated  
engine coolant is ported through the converter to  
provide the necessary heat for conversion of the fuel  
from a liquid to a gaseous state.  
NATURAL GAS FUEL SYSTEM  
Natural gas is supplied in its vapor state. In most  
cases, the gas distribution company provides piping  
from the main gas distribution line to the standby  
generator site. The following information applies to  
natural gas fuel systems.  
• Gas pressure in a building is usually regulated by  
national, state and local codes.  
To reduce gas pressure to a safe level before  
the gas enters a building, a primary regulator is  
needed. The natural gas supplier may or may not  
supply such a regulator.  
• It is the responsibility of the gas supplier to make  
sure sufficient gas pressure is available to operate  
the primary regulator.  
• Gas pressure at the inlet to the fuel shutoff sole-  
noid should not exceed approximately 14 inches  
water column (0.5 psi). Optimum pressure at the  
fuel shutoff solenoid is 11 inches water column  
(0.4 psi).  
. 0 v 0 8 / 0 5  
F u e l S y s 0 0 1 R  
5-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Specifications  
COOLING SYSTEM  
SPECIFICATIONS  
Type...................................................Pressurized Closed Recovery  
Water Pump.................................................................... Belt Driven  
Fan Speed.........................................................................1000 rpm  
Fan Diameter.....................................................................22 inches  
Fan Mode ................................................................................Puller  
Air Flow (inlet air including alternator and  
GENERATOR  
Type............................................................................. Synchronous  
Rotor Insulation ....................................................................Class F  
Stator Insulation .................................................................. Class H  
Total Harmonic Distortion..........................................................<5%  
Telephone Interference Factor (TIF)..........................................< 50  
Alternator Output Leads 3-phase........................................... 6-wire  
Bearings .........................................................................Sealed Ball  
Coupling .......................................................................Flexible Disc  
Load Capacity (Standby Rating) ............................................25kW*  
3
combustion air)...........................................................1600 ft /min.  
Coolant Capacity........................................................ (3.0 U.S. gal.)  
Heat Rejection to Coolant ..........................................106,900 Btu/h  
Maximum Operating Air Temp. on Radiator ..............60° C (150° F)  
Maximum Ambient Temperature................................50° C (140° F)  
* NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE J1349,  
ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate with natural  
FUEL SYSTEM  
gas.  
Type of Fuel.........................................Natural Gas, Propane Vapor  
Carburetor ...................................................................... Down Draft  
Secondary Fuel Regulator .................................................Standard  
Fuel Shut-off Solenoid........................................................Standard  
Operating Fuel Pressure ...................... 5 in. - 14 in. Water Column  
Excitation System....................................................................Direct  
Generator Output Voltage/kW - 60 Hz  
120/240V, 1-phase, 1.0 pf  
120/208V, 3-phase, 0.8 pf  
kW  
25  
25  
25  
Amp CB Size  
104  
87  
125  
100  
40  
277/480V, 3-phase, 0.8 pf  
38  
Generator Locked Rotor KVA Available @ Voltage Dip of 35%  
Single-phase ...................................................................... 50 KVA  
208V, 3-phase .................................................................... 70 KVA  
480V, 3-phase .................................................................... 70 KVA  
Fuel Consumption - ft3/hr (Natural Gas/LPV)  
Exercise  
Cycle  
42/16  
25%  
Load  
50%  
Load  
75%  
Load  
100%  
Load  
375/142  
107/41  
204/77  
293/111  
ENGINE  
ELECTRICAL SYSTEM  
Make................................................................................... Generac  
Model..................................................................................... In Line  
Cylinders and Arrangement............................................................ 4  
Displacement.......................................................................2.4 Liter  
Bore...................................................................................... 3.41 in.  
Stroke ................................................................................... 3.94 in.  
Compression Ratio...............................................................8.5-to-1  
Air Intake System ...............................................Naturally Aspirated  
Valve Seats....................................................................... Hardened  
Lifter Type.......................................................................... Hydraulic  
Battery Charge Alternator ............................................12V, 30 Amp  
Static Battery Charger............................................................2 Amp  
Recommended Battery...................................... Group 26, 525CCA  
System Voltage.....................................................................12 Volts  
Voltage Regulator  
Type.................................................................................. Electronic  
Sensing........................................................................ Single-phase  
Regulation ................................................................................ 1%  
Features .................................................V/F Adjustable, Adjustable  
Voltage and Gain LED Indicators  
Engine Parameters  
Rated Synchronous RPM..............................................60 Hz, 1800  
HP at rated kW..................................................................60 Hz, 40  
Power Adjustment for Ambient Conditions  
Temperature Deration  
3% for every 10° C above °C..................................................... 25  
1.65% for every 10° above °F.................................................... 77  
Altitude Deration  
Exhaust System  
Exhaust Flow at Rated Output 60 Hz.................................. 130 cfm  
Exhaust Temperature at Rated Output.................................. 900° F  
1% for every 100 m above m................................................... 183  
3% for every 1000 ft. above ft. ................................................. 600  
Combustion Air Requirements (Natural Gas)  
Flow at rated power, 60 Hz ................................................... 70 cfm  
Controller.................................................R-200  
Governor  
Type.................................................................................. Electronic  
Frequency Regulation ...................................................Isochronous  
Steady State Regulation...................................................... 0.25%  
Engine Lubrication System  
Type of Oil Pump...................................................................... Gear  
Oil Filter............................................... Full Flow Spin-on, Cartridge  
Crankcase Oil Capacity....................................................4 U.S. qts.  
. A v 0 5 / 0 7  
G e n S p e c 0 3 1  
6-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Specifications  
Figure 1 — Interconnections  
Utility In  
Transfer Switch  
CONTROL PANEL  
NEUTRAL  
TO  
ALTERNATOR  
Gen  
N1  
N2  
23  
NEUTRAL  
N1  
N2  
23  
194  
GENERATOR  
CONNECTION  
BOX  
194  
CIRCUIT  
Load  
Out  
4- # 14 GA  
WIRES TO  
GENERATOR  
CONNECTION  
BOX  
186  
178  
BREAKER  
183  
178  
Battery  
Charger  
Input  
GROUND  
TO GENERATOR  
120 Volt  
+
CONNECTION BOX  
Neutral  
Grd  
To Generator Control Panel  
FRAME RAIL  
Ground Level  
Concrete Slab  
STUB-UP AREA  
See Install Dwg for  
Dimensions  
NOTE:  
COLD WEATHER KIT  
The jet sizes are stamped on the individual jets.  
The larger jet size is used for running on NG.  
For cold climates, optional cold weather kit (part  
number 0F6148) is recommended. The kit includes:  
8. Install the previously removed NG jet into the jet  
keeper port on the side of the regulator housing.  
9. Install the previously removed black pipe onto  
the outlet port of the demand regulator.  
• Battery Warmer  
• 4” Junction Box with hardware  
• 6 qt. pack 5W-30 synthetic oil (engine)  
10. Reverse steps 1-4 in this procedure to reactivate  
RECONFIGURING THE FUEL SYSTEM  
the demand regulator.  
NOTE:  
Figure 6.2 — Reconfigure the Fuel System  
All models are configured to run on natural gas  
from the factory.  
To reconfigure the fuel system from NG to LP, follow  
these steps:  
1. Turn the main gas supply off.  
2. Remove the carburetor fuel hose from the outlet  
port of the demand regulator (see Figure 6.2).  
3. Disconnect the power wires from the fuel sole-  
noid located on top of the regulator assembly.  
4. Loosen the spring clamp on the small fuel enrich-  
ment line and remove the hose from the hose  
barb.  
5. Remove the black pipe assembly from the outlet  
port of the demand regulator.  
6. Remove the NG fuel jet (loosen counter clock-  
wise) from the outlet port.  
7. Remove the LP fuel jet (loosen counter clockwise)  
from the jet keeper port on the side of the regula-  
tor housing. Install this jet into the outlet port in  
the regulator casting.  
DANGER  
Serious injury or damage may occur if not con-  
figured properly. Please consult an Authorized  
Dealer with any questions.  
. A v 0 5 / 0 7  
G e n S p e c 0 3 1 R e  
6-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
General Information  
GENERATOR AC LEAD CONNECTIONS  
ALTERNATOR POWER WINDING  
CONNECTIONS  
See “Voltage Codes”. This generator may be rated  
at any one of three voltages, either single-phase or  
three-phase. The electrical wires in the unit’s AC con-  
nection (lower) panel should be installed according to  
the number of leads and the voltage/phase required  
for the application. If there are any questions regard-  
ing lead connection, refer to the wiring diagrams at  
the back of this manual.  
3-PHASE ALTERNATORS  
The generator is designed to supply 3-phase electri-  
cal loads. Electric power is produced in the alterna-  
tor power windings. These windings were connected  
at the factory to the main circuit breaker with a “Y”  
configuration as shown in Figures 7.2 and 7.3.  
Voltage codes apply to the type of stator assembly  
installed on a particular generator.  
The rated voltage between circuit breaker terminals  
E1-E2, E1-E3 and E2-E3 is either 480V or 208V  
depending on the model.  
FOUR-LEAD, SINGLE-PHASE STATOR  
The rated voltage between each circuit breaker termi-  
nal and the neutral point 00 is either 277V or 120V  
depending on the model.  
Four-lead generators (see Figure 7.1) are designed to  
supply electrical loads with voltage code A” (240V,  
1-phase, 60 Hz). Electrical power is produced in the  
stator power windings. These windings were con-  
nected at the factory to the main circuit breaker as  
shown in Figure 7.1.  
Figure 7.2 — Stator Power Winding  
Connections - 3-phase, 277/480V (6 Lead)  
The rated voltage between each circuit breaker ter-  
minal is 240V. The rated voltage between each circuit  
breaker terminal and the neutral point 00 is 120V.  
S1 E1  
Figure 7.1 — Four-lead, Single-phase Stator  
INTERNAL  
CONNECTIONS  
L-L  
S6  
S4  
NEUTRAL  
S5  
E3 S3  
S2 E2  
L-N  
Figure 7.3 — Stator Power Winding  
Connections - 3-phase, 120/208V (6 Lead)  
E1  
S1  
S1  
L-L  
S4  
S6  
S4  
00 (NEUTRAL)  
S5  
S3  
S2  
S6 S5  
E3  
E2  
S3  
S2  
L-N  
. 0 v 0 8 / 0 5  
C A C o n n 0 0 1 R e  
7-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Installation  
PRIOR TO INITIAL START-UP  
INSTALLATION  
Refer to the separate “Installation Guide” supplied  
with the unit.  
Prior to initially starting the generator, it must  
be properly prepared for use. Any attempt to  
crank or start the engine before it has been  
properly serviced with the recommended types  
and quantities of engine fluids (oil, coolant, fuel,  
etc.) may result in an engine failure.  
PREPARATION BEFORE START-UP  
The instructions in this section assume that the  
standby generator has been properly installed, ser-  
viced, tested, adjusted and otherwise prepared for  
use by a competent, qualified installation contractor.  
Be sure to read the “Safety Rules”, as well as all other  
safety information in this manual, before attempting  
to operate this (and related) equipment.  
ENGINE COOLANT  
Have the engine cooling system properly filled with  
the recommended coolant mixture. Check the system  
for leaks and other problems. See “Specifications”  
and “Coolant” sections.  
Before starting the generator for the first time, the  
installer must complete the following procedures. For  
follow-up maintenance information and/or service  
intervals, please refer to the “Maintenance” section  
and the “Service Schedule”.  
BELT TENSION  
Check-the engine-fan belt tension and condition prior  
to placing the unit into service and at recommended  
intervals. Belt tension is correct when a force of  
approximately 22 pounds (10 kg), applied midway  
between pulleys, deflects the belt about 3/8- to 5/8-  
inch (10 to 16 mm).  
TRANSFER SWITCH  
If this generator is used to supply power to any elec-  
trical system normally powered by an electric utility,  
the National Electrical Code requires that a transfer  
switch be installed. The transfer switch prevents elec-  
trical backfeed between two different electrical sys-  
tems. (For additional information, see the applicable  
transfer switch manual for this unit.) The transfer  
switch, as well as the generator and other standby  
components, must be properly located and mounted  
in strict compliance with applicable codes, standards  
and regulations.  
ELECTRICAL SYSTEM  
Make sure the generator is properly connected to an  
approved earth ground.  
Make sure the generator battery is fully charged,  
properly installed and interconnected, and ready for  
use.  
FUEL SYSTEM  
NOTE:  
Make sure the fuel supply system to the generator (a)  
delivers the correct fuel at the correct pressure and (b)  
is properly purged and leak tested according to code.  
No fuel leakage is permitted. See “Specifications” for  
more information.  
Battery charger must be connected to 120 VAC, 15  
amp circuit to operate.  
Check to ensure that there are no loose electrical con-  
nections. Restrain any loose wires to keep them clear  
of any moving generator set components.  
GENERATOR SET LUBRICATION  
Check the engine crankcase oil level before operating  
and add oil to the proper level – the dipstick “FULL”  
mark. Never operate the engine with the oil level  
below the dipstick ADD” mark. See “Specifications”  
and “Engine Oil Recommendations”.  
INITIAL INSPECTION FOR GENSET  
STARTUP  
Inspect for the following.  
• Freight Damage.  
• Manuals present.  
NOTE:  
• Fluid Levels (Oil, coolant, battery, Gear Drive).  
• Correct fuel piping.  
This engine is shipped from the manufacturer  
with “break-in” oil. This oil should be changed  
after 30 hours of operation.  
• Adequate air flow, clearances and ventilation per  
installation drawings and applicable codes.  
• Correct AC and DC wire size, connections and  
grounding. Control and communication wiring to/  
from the transfer switch must be run in a separate  
conduit from the AC power leads.  
. C v 0 1 / 0 7  
I n s t a l l 0 0 2 R e  
8-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Installation  
• Open the valve to the engine fuel line.  
• Battery charger connection to 120 VAC.  
• Communication wires connected between transfer  
switch and generator (HTS only).  
• Bleed the fuel system of air. (necessary for long fuel  
lines).  
• Open the generator main line circuit breaker.  
• Connect a manometer to the gas line and record  
the static pressure. It must be as listed in the  
Specifications.  
• Unit secured to pad.  
START-UP CHECKLIST  
• Insert the fuse into the control panel.  
• Move the AUTO/OFF/MANUAL switch to the man-  
ual position. The engine should now crank and  
start.  
Before working on the generator, ensure the fol-  
lowing:  
• Check voltage at the generator terminals.  
For 3-phase units, check phase rotation at the  
transfer switch terminals. The generator phase  
rotation must match the utility phase rotation.  
• Check for coolant, fuel, oil, and exhaust leaks.  
• Close the generators main line circuit breaker.  
Turn the generator set off.  
• The AUTO/OFF/MANUAL switch is in the OFF  
position.  
• The 120VAC supply to the battery charger is  
switched OFF.  
PREPARATION FOR START-UP  
• Ensure that the 120VAC circuit breaker to the bat-  
tery charger is open.  
• Remove the fuse from the the control panel. Open  
the front door of the control box and remove the  
15 Amp ATO fuse in the lower left-hand corner of  
the control box.  
• Connect the UTILITY supply to the transfer  
switch.  
• Set the AUTO/OFF/MANUAL switch to AUTO.  
• Disconnect utility power before the transfer  
switch.  
• Connect the battery cables to the battery. Attach  
Engine should start, transfer to load.  
Run at least 15 minutes on generator power.  
Make certain all 3-phase loads are functioning  
correctly (correct phase rotation).  
negative battery cable last.  
• Close the 120VAC circuit breaker to the battery  
charger.  
• Measure the voltage at the battery before and after  
• Reconnect Utility power  
the charger is turned on.  
Transfer switch will transfer back to Utility and  
engine will shut down within the given time  
parameters set up for the specific transfer switch  
and controller.  
Verify all AC electrical connections are tight at the  
circuit breaker and transfer switch.  
• Visually inspect entire area looking for loose paper,  
plastic wrappings, leaves, etc.  
• Install all covers, access plates and door panels.  
• Put the Owners Manual in a safe and accessible  
place.  
• Check all hoses clamps fittings for leaks or dam-  
age.  
• Check all electrical plugs throughout the genera-  
tor. Ensure each plug is seated correctly and fully  
inserted into its receptacle.  
• Make certain the AUTO/OFF/MANUAL switch is in  
the AUTO position.  
Verify the AUTO/OFF/MANUAL switch is in OFF  
position.  
. C v 0 1 / 0 7  
I n s t a l l 0 0 2 R e  
8-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Operation  
GENERATOR CONTROL AND  
OPERATION  
Do not crank the engine continuously for longer  
than 30 seconds, or the heat may  
damage the starter motor.  
Refer to the appropriate control panel operator’s  
manual for this unit.  
• Let engine stabilize and warm up.  
OPERATING UNIT WITH MANUAL  
• Check all applicable instrument and gauge read-  
ings. When certain that all readings are correct,  
move the transfer switch manual handle to its  
STANDBY (GENERATOR) position, i.e., load cir-  
cuits supplied by the generator.  
TRANSFER SWITCH  
If the generator was installed in conjunction with a  
transfer switch capable of manual operation only, the  
following procedure applies. A manually operated  
transfer switch is one that will not provide automatic  
start-up and does not include an intelligence circuit.  
• Set the standby generator’s main line circuit break-  
er to its ON (or CLOSED) position.  
• Load circuits are now powered by the standby  
generator.  
ENGINE START-UP AND TRANSFER  
For additional information, refer to the applicable  
control panel manual for this unit, as well as any lit-  
erature pertaining to the specific transfer switch.  
RETRANSFER AND SHUTDOWN  
For additional information, refer to the applicable  
control panel manual for this unit, as well as any lit-  
erature pertaining to the specific transfer switch.  
DANGER  
To transfer the load back to the utility power source  
and shut down the generator, follow these direc-  
tions:  
The Maintenance Disconnect Switch and the  
AUTO/OFF/MANUAL switches (if so equipped)  
must be set properly, or the generator will crank  
and start as soon as the utility power to the  
transfer switch is turned off. Refer to applicable  
control panel and transfer switch manuals for  
more information.  
• Set the standby generator’s main line circuit break-  
er to its OFF (or OPEN) position.  
• Manually move the transfer switch handle to its  
UTILITY (NORMAL) position, i.e., load circuits  
connected to the utility.  
Turn ON the utility power supply to the transfer  
switch, using the means provided (such as the util-  
ity power source main line circuit breaker).  
• Let the generator run at no-load for a few minutes  
to stabilize internal temperatures.  
Do not proceed until certain that utility source  
voltage is available to the transfer switch and  
the transfer switch main contacts are set to  
UTILITY.  
Do not attempt manual operation until all power  
supplies to the transfer switch have been posi-  
• Shut down the generator.  
tively turned off, or extremely dangerous - pos-  
sibly lethal - electrical shock will result.  
OPERATING UNIT WITH AUTOMATIC  
Transfer switch enclosure doors should be kept  
TRANSFER SWITCH  
closed and locked. Only authorized personnel  
If the generator has been installed with an automatic  
transfer switch, such as an RTS, HTS, or GTS-type  
transfer switch, the engine may be started and  
stopped automatically or manually.  
should be allowed access to the transfer switch  
interior. Extremely high and dangerous voltages  
are present in the transfer switch.  
In order to transfer load from the utility source to the  
generator, follow these directions:  
NOTE:  
Refer to the applicable manual for your trans-  
fer switch and to “Transfer Switch Start Signal  
Connections”. In addition, please note the dangers  
under “Engine Start-up and Transfer.”  
Turn OFF or disconnect the utility power circuit  
to the transfer switch, using the means provided  
(such as the utility source main line circuit break-  
er).  
• Set the transfer handle to its UTILITY (NORMAL)  
position with load circuits connected to the utility  
power supply.  
• Set the standby generator’s main line circuit break-  
er to its OFF (or OPEN) position.  
• Start the generator.  
. 0 v 0 8 / 0 5  
O p e r 0 0 1 R e  
9-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Maintenance  
MAINTENANCE PERFORMED BY  
SERVICE FACILITIES  
COOLING SYSTEM  
Air intake and outlet openings in the generator com-  
partment must be open and unobstructed for contin-  
ued proper operation. This includes such obstruc-  
tions as high grass, weeds, brush, leaves and snow.  
Before working on the generator, ensure the fol-  
lowing:  
Without sufficient cooling and ventilating air flow, the  
engine/generator quickly overheats, which causes it  
to shut down. (See the installation diagram.)  
• The AUTO/OFF/MANUAL switch is in the OFF  
position.  
• The 15A fuse has been removed from the con-  
trol box.  
The exhaust system parts from this product get  
• The 120VAC supply to the battery charger is  
switched OFF.  
extremely hot and remains hot after shutdown.  
High grass, weeds, brush, leaves, etc. must  
remain clear of the exhaust. Such materials may  
ignite and burn from the heat of the exhaust  
system.  
EVERY THREE MONTHS  
1. Check battery condition.  
2. Inspect and test fuel system.  
3. Check transfer switch.  
4. Inspect exhaust system.  
5. Check engine ignition system.  
6. Check fan belts.  
OVERLOAD PROTECTION FOR ENGINE  
DC ELECTRICAL SYSTEM  
Engine cranking, start up and running are controlled  
by a solid state Engine Controller circuit board.  
Battery voltage is delivered to that circuit board via  
a 15 amp fuse. These overcurrent protection devices  
will open if the circuit is overloaded.  
ONCE EVERY SIX MONTHS  
1. Test Engine Safety Devices (low oil pressure, low  
coolant level, high coolant temperature).  
ONCE ANNUALLY  
If a circuit breaker opens or a fuse element melts,  
1. Test engine governor; adjust or repair, if needed.  
2. Clean, inspect generator.  
find the cause of the overload before resetting  
the circuit breaker or replacing the fuse.  
3. Flush cooling system.  
CHECKING FLUID LEVELS  
FIRST 30 OPERATING HOURS  
CHECK ENGINE OIL  
1. Change engine "break-in" oil and filter.  
Check engine crankcase oil level (Figure 10.1) at least  
every 20 hours of operation, or prior to use.  
FIRST 100 OPERATING HOURS  
1. Change engine oil and oil filter. After initial  
change, service engine oil and filter at 100 operat-  
ing hours or six months, whichever comes first.  
2. Retorque cylinder head.  
Figure 10.1 - Oil Dipstick and Oil Fill Cap  
Oil Fill Cap  
3. Retorque intake and exhaust manifold.  
EVERY 500 OPERATING HOURS  
Oil  
Dipstick  
1. Service air cleaner.  
2. Check starter.  
3. Check engine DC alternator.  
EVERY 800 OPERATING HOURS  
1. Retorque cylinder head.  
2. Retorque intake and exhaust manifold.  
3. Check engine compression.  
4. Check valve clearance.  
. D v 0 6 / 0 7  
M a i n t 0 1 2 R e  
10-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Maintenance  
• Remove oil dipstick and wipe dry with a clean, lint-  
INSPECT COOLING SYSTEM  
free cloth.  
• Inspect engine cooling system. See “Maintenance  
Schedule”.  
• Check hoses for damage, deterioration, leaks, etc.  
• Install oil dipstick, then remove again.  
• Oil should be between FULL and ADD marks.  
• If oil level is below the dipstick ADD mark, remove  
oil fill cap-. Add the recommended oil to bring oil  
level up to the FULL mark. DO NOT FILL ABOVE  
THE “FULLMARK. See “Engine Oil Recommen-  
dations” for recommended oils.  
Correct any discrepancies found.  
• Check hose clamps for tightness.  
CHECK ENGINE COOLANT LEVEL  
See “Checking Fluid Levels”.  
BATTERY FLUID  
Check battery electrolyte fluid based on the  
Maintenance Schedule. Fluid should cover separa-  
tors in all battery cells. If fluid level is low, add dis-  
tilled water to cover tops of separators. DO NOT USE  
TAP WATER IN BATTERY.  
PERFORM VISUAL INSPECTION  
Complete a thorough visual inspection of the entire  
engine-generator monthly. Look for obvious damage,  
loose, missing or corroded nuts, bolts and other fas-  
teners. Look for fuel, oil or coolant leaks.  
ENGINE COOLANT  
INSPECT EXHAUST SYSTEM  
Check coolant level in coolant recovery bottle. See  
Specifications.  
Inspect the exhaust system at least once every three  
months. Check all exhaust system pipes, mufflers,  
clamps, etc. for condition, tightness, leaks, security,  
damage.  
• Add recommended coolant mixture as necessary.  
• Periodically remove radiator pressure cap (only  
when engine has cooled down) to make sure the  
coolant recovery system is functioning properly.  
Coolant should be at bottom of radiator filler neck.  
If coolant level is low, inspect gasket in radiator  
pressure cap. Replace cap, if necessary. To have  
pressure cap tested, contact a Service Dealer.  
Inspect cooling system and coolant recovery sys-  
tem for leaks.  
CHECK FAN BELT  
• Inspect fan belts every three months. Replace any  
damaged, deteriorated, worn or otherwise defec-  
tive belt.  
• Check fan belt tension. Thumb pressure, exerted  
midway between pulleys, should deflect about 3/8  
to 5/8 of an inch. Adjust belt tension as required.  
MAINTENANCE OWNER/  
OPERATOR CAN PERFORM  
INSPECT ENGINE GOVERNOR  
Visually inspect electronic governor.  
CHECK ENGINE OIL LEVEL  
DANGER  
Refer to “Checking Fluid Levels”.  
Do not attempt to adjust the governor. Only  
qualified service facilities should adjust the  
CHECK BATTERY  
governor. Excessively high operating speeds  
are dangerous and increase the risk of personal  
injury. Low speeds impose a heavy load on the  
engine when adequate engine power is not  
available and may shorten engine life. Correct  
rated frequency and voltage are supplied only  
at the proper governed speed. Some connected  
electrical load devices may be damaged by incor-  
rect frequency and/or voltage. Only qualified  
service technicians should adjust the governed  
speed.  
• See “Checking Fluid Levels”.  
• Check battery cables for condition, tightness, cor-  
rosion or damage. Clean, tighten or replace as  
necessary.  
EXERCISE SYSTEM  
Start the generator engine at least once every seven  
days and let it run at least 20 minutes. For more  
detailed exercise information, see the respective sec-  
tions in the Control Panel Technical Manual that is  
supplied with the unit.  
. D v 0 6 / 0 7  
M a i n t 0 1 2 R e  
10-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Maintenance  
Figure 10.3 – Engine Air Cleaner  
CHANGING ENGINE OIL  
Refer to maintenance performed by service facilities  
for engine oil and filter change frequencies.  
Air Cleaner  
Drain the oil while the engine is still warm from run-  
ning. This means warm up the engine, shut it down  
and drain immediately as follows:  
1. Remove OIL DRAIN HOSE from its retaining  
clip.  
2. Loosen and remove OIL DRAIN HOSE CAP. Drain  
oil completely into suitable container.  
3. When all oil has drained, install and tighten OIL  
DRAIN HOSE CAP, and re-install into its retaining  
clip.  
4. Turn OIL FILTER (Figure 10.2) counterclockwise  
and remove. Properly dispose of old filter.  
(Doors Removed for Clarity)  
Figure 10.2 – Oil Filter  
SPARK PLUGS  
Reset the spark plug gap or replace the spark plugs  
as necessary (Figure 10.4).  
1. Clean the area around the base of the spark plugs  
to keep dirt and debris out of the engine. Clean  
by scraping or washing using a wire brush and  
commercial solvent. Do not blast the spark plugs  
to clean.  
2. Remove the spark plugs and check the condition.  
Replace the spark plugs if worn or if reuse is  
questionable. See the “Service Schedule” section  
for recommended inspection.  
Oil  
Filter  
3. Check the spark plug gap using a wire feeler  
gauge. Adjust the gap to 1.07-1.17 mm (0.042-  
0.046 inch) by carefully bending the ground elec-  
trode (Figure 10.4).  
5. Apply light coating of new engine oil to seal of new  
oil filter.-Install FILTER and tighten by hand only.  
DO NOT OVER TIGHTEN.  
6. Remove OIL FILL CAP. Add recommended oil (see  
SPECIFICATIONS). DO NOT FILL ABOVE THE  
DIPSTICK “FULLMARK. Crankcase oil capacity  
is 4.0 U.S. quarts (3.8 liters).  
Figure 10.4 – Setting the Spark Plug Gap  
SET PLUG GAP AT 1.07 - 1.17 mm  
(0.042 - 0.046 inch)  
After refilling the crankcase with oil, always  
check oil level on dipstick. NEVER OPERATE  
ENGINE WITH OIL BELOW THE DIPSTICK “ADD”  
MARK.  
7. Start engine and check for oil leaks.  
COOLANT CHANGE  
CHANGING THE ENGINE AIR CLEANER  
Every year, have a service facility drain, flush and  
refill the cooling system. See “Specifications” for cool-  
ing system recommendations.  
To replace the engine air cleaner, remove the air  
cleaner cover and replace the air filter making sure  
it is positioned properly before reattaching the cover  
(Figure 10.3).  
See the “Service Schedule,” for air cleaner mainte-  
nance.  
. D v 0 6 / 0 7  
M a i n t 0 1 2 R e  
10-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Maintenance  
2. Check the battery fluid level of unsealed batteries  
MISCELLANEOUS MAINTENANCE  
and, if necessary, fill with DISTILLED WATER  
ONLY. DO NOT USE TAP WATER IN BATTERIES.  
3. Have the state of charge and condition checked.  
This should be done with an automotive-type bat-  
tery hydrometer.  
CLEANING THE GENERATOR  
Keep the generator as clean and as dry as possible.  
Dirt and moisture that accumulates on internal gen-  
erator windings have an adverse effect on insulation  
resistance.  
DANGER  
Periodically clean generator exterior surfaces. A soft  
brush may be used to loosen caked on dirt. Use a  
vacuum system or dry, low pressure air to remove  
any accumulations of dirt. The generator is housed  
inside an all-weather enclosure, clean the enclosure  
with a soft, damp cloth or sponge and water.  
Storage batteries give off explosive hydrogen  
gas. This gas can form an explosive mixture  
around the battery for several hours after charg-  
ing. The slightest spark can ignite the gas and  
cause an explosion. Such an explosion can shat-  
ter the battery and cause blindness or other  
injury. Any area that houses a storage battery  
must be properly ventilated. Do not allow smok-  
ing, open flame, sparks or any spark producing  
tools or equipment near the battery.  
Once each year have the generator cleaned and  
inspected by a Service Dealer. That dealer will use  
dry, low pressure air to clean internal windings. Parts  
inside the control console should be cleaned and  
inspected at this time as well.  
Battery electrolyte fluid is an extremely corro-  
sive sulfuric acid solution that can cause severe  
burns. Do not permit fluid to contact eyes, skin,  
clothing, painted surfaces, etc. Wear protective  
goggles, protective clothing and gloves when  
handling a battery. If fluid is spilled, flush the  
affected area immediately with clear water.  
Finally, have the insulation resistance of stator and  
rotor windings checked. If insulation resistances are  
excessively low, the generator may require drying.  
BATTERY  
Do not use any jumper cables or booster battery  
All lead-acid storage batteries discharge when not in  
use. Refer to specific instructions and warnings that  
accompany the battery. If such information is not  
available, observe the following precautions when  
handling a battery:  
to crank and start the generator engine. If the  
battery has completely discharged, remove it  
from the generator for recharging.  
• DO NOT use jumper cables and a booster battery  
to crank or start the generator engine.  
Be sure the AUTO/OFF/MANUAL switch is set to  
the OFF position, before connecting the battery  
• DO NOT recharge a weak battery while it is  
installed in the generator. Remove battery from  
generator and recharge in a well-ventilated area,  
away from fuel vapors, sparks, heat or flames.  
• Battery electrolyte fluid is an extremely caustic  
sulfuric solution that can cause severe burns. DO  
NOT permit fluid to contact eyes, skin, clothing,  
painted surfaces, wiring insulation, etc. If any bat-  
tery fluid is spilled, flush the affected area with  
clear water immediately.  
cables. If the switch is set to AUTO or MANUAL,  
the generator can crank and start as soon as the  
battery cables are connected.  
Be sure the 120VAC power supply to the battery  
is turned OFF, or sparking may occur at the bat-  
tery posts as the cables are attached and cause  
an explosion.  
BATTERY REPLACEMENT  
NOTE:  
• Always wear safety glasses, rubber apron and  
Unit DOES NOT include battery.  
gloves when handling a battery.  
• Batteries give off explosive hydrogen gas while  
charging. The gas can form an explosive mixture  
around the battery for several hours after charging.  
Any spark, heat or flames can ignite the gas and  
cause an explosion which can shatter the battery,  
causing blindness or other serious injury.  
When supplying or replacing the battery, the recom-  
mended number and type of battery is listed in the  
Specifications Section.  
NOTE:  
The BCI number should be located directly on the  
battery.  
BATTERY MAINTENANCE  
The battery should be inspected per the "Scheduled  
Maintenance" section. The following procedure should  
be followed for inspection:  
REPAIR PARTS  
The later portion of this manuals consists of explod-  
ed views, parts lists and electrical data pertaining to  
this generator set.  
1. Inspect the battery posts and cables for tightness  
and corrosion. Tighten and clean as necessary.  
. D v 0 6 / 0 7  
M a i n t 0 1 2 R e  
10-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Service Schedule  
SERVICE SCHEDULE  
30 KW - 150 KW STANDBY GAS ENGINE DRIVEN GENERATOR SETS  
The following is a recommended maintenance schedule for standby gas engine driven generator sets from 30kW to  
150 kW in size. The established intervals in the schedule are the maximum recommended when the unit is used  
in an average service application. They will need to be decreased (performed more frequently) if the unit is used  
in a severe application. Use calendar time, from the previous maintenance interval to determine the next required  
maintenance interval.  
Service Maintenance Interval Information:  
The various service maintenance intervals are designated by interval numbers as follows:  
1 An early inspection of the generator set to insure it is ready to operate when required and to identify any poten-  
tial problem areas.  
This inspection may be performed by the end user providing the following safety steps are taken to prevent  
the engine from starting automatically without warning:  
To prevent injury, perform the following steps in the order indicated before starting any maintenance:  
• Disable the generator set from starting and/or connecting to the load by setting the control panel Auto/Off/  
Manual switch to the “OFF” position.  
• Remove the 15 amp control panel fuse.  
• Turn off the battery charger.  
• Remove the negative battery cable.  
The battery charger must be turned off BEFORE removing the battery cable to prevent an over current condition  
from burning out sensitive control panel components and circuits.  
Following all maintenance, reverse these steps to insure the unit is returned to standby setup for normal  
operation when required.  
2 A wear-in service inspection of the generator set to insure it is ready to operate and carry the load when  
required, and to identify any potential problem areas.  
Performed ONLY ONCE following the first three months or the first 30 hours of operation after purchase of  
the unit.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an Authorized Service Dealer.  
3 An operational inspection of the generator set to insure it is ready to operate and carry the load when required,  
and to identify any potential problem areas.  
Performed semi-annually or following each 50 hours of operation of the unit.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an Authorized Service Dealer.  
4 A mid-level inspection of the generator set to insure it is ready to operate and carry the load when required,  
and to identify any potential problem areas.  
Performed annually or following each 100 hours of operation of the unit.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an Authorized Service Dealer.  
5 A comprehensive inspection of the generator set to insure it is properly serviced and ready to operate and carry  
the load when required, and to identify any potential problem areas.  
Performed annually or following each 250 hours of operation of the unit.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an Authorized Service Dealer.  
. B v 0 3 / 0 7  
v S S c h r d 0 0 1 R e  
11-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Service Schedule  
Maintenance Level 1  
Level 2  
Level 3  
Level 4  
Level5  
Tasks  
Recom-  
mended  
Task  
Required  
Task  
Required  
Task  
Task  
Required  
Task  
Comp. to be done Comp. to be done Comp.  
Required  
Comp. to be done Comp.  
Bi- (Date-  
Annually/ Initials) annually/ Initials)  
100 hrs. 250 hrs.  
to be done (Date- 3 months/ (Date-  
monthly/  
10 hrs.  
Semi-  
(Date- to be done (Date-  
Initials)  
Initials) Break-in Initials) annually/  
30 hrs. 50 hrs.  
1. Disable the unit  
from operating  
per the first page  
warning.  
2. Check the engine  
oil level. Adjust  
as necessary.  
3. Check the engine  
coolant level.  
Adjust as  
necessary.  
4. Check the engine  
coolant thermal  
protection level.  
Correct as  
necessary.  
5. Check the natural  
gas delivery  
system for leaks  
and correct  
pressure on gas  
engine driven  
units. Tighten  
connections as  
necessary.  
6. Check the air  
inlets and outlets  
for debris. Clean  
as necessary.  
7. Check the battery  
electrolyte level  
and specific  
gravity if  
accessible. Adjust  
as necessary.  
8. Check the battery  
posts, cables,  
and charger for  
loose  
connections,  
corrosion, and  
proper operation.  
Correct as  
necessary.  
9. Check the unit  
wiring for loose  
connections,  
corrosion, and  
damage. Correct  
as necessary.  
. B v 0 3 / 0 7  
v S S c h r d 0 0 1 R e  
11-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Service Schedule  
Maintenance Level 1  
Level 2  
Level 3  
Level 4  
Level5  
Tasks  
Recom-  
mended  
Task  
Required  
Task  
Required  
Task  
Task  
Required  
Task  
Comp. to be done Comp. to be done Comp.  
Required  
Comp. to be done Comp.  
Bi- (Date-  
Annually/ Initials) annually/ Initials)  
100 hrs. 250 hrs.  
to be done (Date- 3 months/ (Date-  
monthly/  
10 hrs.  
Semi-  
(Date- to be done (Date-  
Initials)  
Initials) Break-in Initials) annually/  
30 hrs. 50 hrs.  
10. Check the engine  
accessory drive  
belts and fan  
coupling device  
if equipped for  
correct tension,  
wear, weather  
cracking, and  
damage. Replace  
as necessary.  
11. Check the engine  
valve clearance/  
lash. Adjust as  
necessary.  
12. Visually inspect  
the unit looking  
for leaks, wear or  
damage, loose  
connections or  
components, and  
corrosion. Correct  
as necessary.  
13. Test the engine  
and transfer  
switch safety  
devices. Correct  
and/or adjust as  
necessary.  
14. Initiate an  
automatic start  
and transfer of  
the unit to site  
load and exercise  
it for at least 1  
hour looking for  
leaks, loose  
connections or  
components, and  
abnormal  
operating  
conditions.  
Correct as  
necessary.  
15. Replace the  
engine  
accessory  
drive belts.  
16. Check gearbox  
oil level (if  
equipped).  
17. Change gearbox  
oil (if equipped).  
. B v 0 3 / 0 7  
v S S c h r d 0 0 1 R e  
11-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Service Schedule  
Maintenance Level 1  
Level 2  
Level 3  
Level 4  
Level5  
Tasks  
Recom-  
mended  
Task  
Required  
Task  
Required  
Task  
Task  
Required  
Task  
Comp. to be done Comp. to be done Comp.  
Required  
Comp. to be done Comp.  
Bi- (Date-  
Annually/ Initials) annually/ Initials)  
100 hrs. 250 hrs.  
to be done (Date- 3 months/ (Date-  
monthly/  
10 hrs.  
Semi-  
(Date- to be done (Date-  
Initials)  
Initials) Break-in Initials) annually/  
30 hrs. 50 hrs.  
18. Start and  
exercise the unit  
at full rated load  
(use a load bank  
if the site load is  
not enough) for  
at least 2 hours  
looking for leaks,  
loose  
connections or  
components, and  
abnormal  
operating  
conditions.  
Correct as  
necessary.  
19. Perform an  
engine oil  
analysis (send a  
sample to a lab  
for results).  
Change the  
engine oil and  
filters if the  
analysis results  
indicate this is  
required.  
20. Change the  
engine oil.  
21. Replace the  
engine oil filter(s).  
22. Replace engine  
spark plugs.  
Clean and re-gap  
or replace as  
necessary.  
23. Replace the  
engine air  
filter(s).  
24. Perform a 5  
minute no-load  
operational run  
of the unit  
looking for any  
post service  
problems.  
25. Return the unit  
to standby setup  
for operation  
when required.  
. B v 0 3 / 0 7  
v S S c h r d 0 0 1 R e  
11-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Troubleshooting  
TROUBLESHOOTING GUIDE  
PROBLEM  
Engine won’t crank.  
CAUSE  
1. 15 amp fuse blown.  
CORRECTION  
1. Replace fuse.  
2. Loose or corroded or defective  
battery cables.  
2. Tighten, clean or replace  
battery cables as necessary.  
3. Replace contactor.*  
3. Defective starter contactor.  
4. Defective starter motor.  
5. Dead or Defective Battery.  
6. 5 amp fuse blown.  
4. Replace starter motor.*  
5. Remove, change or replace battery.  
6. Replace fuse.*  
Engine cranks but won't start  
Engine starts hard, runs rough.  
Engine starts then shuts down.  
1. Out of fuel.  
1. Replenish fuel.  
2. Replace solenoid.*  
3. Reconnect wire.  
2. Fuel solenoid (FS) is defective  
3. Open Wire #14A from Engine Control  
circuit board.  
4. Spark plugs defective.  
5. Door on tank not closed.  
4. Clean, regap or replace plugs.  
5. Close door on tank.  
1. Flame arrestor (air cleaner) plugged or  
damaged.  
2. Plugged fuel line.  
1. Clean or replace as needed.  
2. Unclog fuel line.  
3. Defective spark plugs.  
4. Fuel pressure incorrect.  
3. Clean, regap or replace plugs.  
4. Confirm fuel pressure to regulator is as  
recommended in SPECIFICATIONS.  
1. Engine oil level is low.  
2. Engine is overheated.  
1. Check oil and add oil as needed.  
2. Check cooling system for leaks.  
3. Replace switch.*  
3. Defective Low Oil Pressure Switch  
4. Defective Coolant Temperature Switch  
5. Defective Control Module circuit board.  
6. Coolant Level is Low.  
4. Replace switch.*  
5. Replace board.*  
6. Repair leak - Add coolant.  
7. Replace Switch.*  
7. Defective Low Coolant Level Switch  
AUTO/OFF/MANUAL Switch at OFF, 1. Defective AUTO/OFF/MANUAL switch  
1. Replace switch.*  
2. Reconnect/close wire.  
engine continues to run  
2. Open/disconnected wire #15A between  
AUTO/OFF/MANUAL switch and Control  
Module circuit board.  
3. Defective Control Module circuit board  
3. Replace board.*  
No AC output from generator.  
1. Check main line circuit breaker.  
2. Check circuit breaker & fuses.  
3. Transfer switch set to NORMAL position  
4. Generator internal failure.  
1. Reset to ON or CLOSED.  
2. Reset and replace, if necessary.  
3. Set to GENERATOR position.  
4. *  
5. Thermal circuit breaker open.  
5. Auto-reset - Wait 5 min. and  
attempt restart.  
*Contact the nearest Authorized Dealer for assistance.  
. 0 v 0 8 / 0 5 l s b h r t T 0 0 1 R e  
12-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Notes  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standby Generator Sets  
Notes  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
0F3137  
0F3188  
0F3189  
023484N  
0F6366B  
0F6366A  
043180  
022264  
0C3990  
057701  
022155  
0C2428  
0F3824  
0A9457  
057073  
0D5466  
0A7822  
022237  
022241  
049226  
0C2266  
0C2454  
022473  
022097  
0D4698  
0F4464  
025433  
024469  
067210A  
0D6029  
081008  
077043J  
051713  
0F6156  
029289  
047411  
0G0770  
0G5952  
036943  
023897  
022152  
022158  
1
1
1
1
1
1
2
2
2
REF  
4
4
1
1
PAN CB CONN BOX  
STAND RH CONTROL  
STAND LH CONTROL  
BUSHING SNAP SB-2.5-31  
XFMR DUAL 120V/16V (FOR 120/240V & 277/480V UNITS)  
XFMR DUAL 104V/16V (FOR 120/208V UNITS)  
WASHER FLAT M4  
3)  
A
C
D
E
F
G
H
J
UL CIRCUIT BREAKER (JD+LD)  
0F3329  
0D5577  
0F2353  
022770  
022473  
022097  
022127  
0C2454  
029289  
0F1733  
1
1
2
4
4
4
4
7
1
1
COVER JD/LD CB SHRT STAND  
CB 0300A 3P 600V S JD6 LL  
INSULATOR CIRCUIT BR. JD/LD  
SCREW RHM 1/4-20 X 3  
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK M6-1/4  
6
7
8
WASHER LOCK #8-M4  
NUT HEX 1/4-20 STEEL  
SCREW PHTT M4-0.7 X 10 ZYC  
BLOCK TERM 20A 8 X 6 X 1100V  
WASHER LOCK #6  
SCREW PHTT #6-32 X 1/2 ZYC  
DECAL UTIL SENSE/CUST CONN  
DECAL NEUTRAL  
JUNCTION BLOCK 3/8-16  
BUS BAR NEUTRAL BLOCK 390  
LUG SLDLSS 600/250-1/0 X 1/4-28  
WASHER LOCK 3/8  
SCREW THF M6-1 X 16 N WA Z/JS  
TAPE ELEC 1/2 FOAM (AS REQ’D)  
DECAL CUSTOMER CONNECT INSIDE  
(1) 9  
10  
11  
12  
13  
K
L
4)  
A
C
UL CIRCUIT BREAKER (QN)  
0F8135  
0E7283  
0E7284  
0E3664  
074908  
0F8140  
036261  
0C2454  
029289  
0F1733  
1
COVER QN FRM CB  
14  
2
-
-
CB 0150A 2P 240V S QN2 LL  
CB 0175A 2P S QN2 LL 240V  
BASE, QN CIRCUIT BREAKER  
SCREW HHTT M5-0.8 X 10 BP  
COVER QN CB DISH  
(2) 15  
(2) 16  
17  
18  
19  
20  
21  
23  
24  
(1) 26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
(3) 39  
(4) 40  
(4) 41  
(4) 42  
(4) 43  
(4) 44  
REF  
REF  
2
2
4
4
8
8
4
REF  
1
1
1
1
4
1
1
2
1
1
4
1
1
2
4
2
D
E
F
G
H
J
1
2
1
4
7
1
1
NUT HEX 3/8-16 STEEL  
WASHER LOCK M5  
RIVET POP .125 X .275 SS  
SCREW PHTT M5-0.8 X 16 ZYC  
SCREW THF M6-1 X 16 N WA Z/JS  
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK M6-1/4  
BLOCK TERM 20A 6 X 3 X 1100V  
DECAL CUST CONN 120V UTILITY  
LUG SLDLSS #6-14 X 13/64 CU  
SCREW HHTT #10-32 X 3/8 CZ  
DECAL GROUND LUG  
SCREW HHTT M6-1.0 X 16 ZYC  
GROMMET 1.25 X .25 X .75  
CONDUIT FLEX 2.0" ID (36” LG)  
WASHER FLAT M5  
PLATE WIRE SNGL GALV  
TAPE ELEC 1/2 FOAM (AS REQ’D)  
SCREW HHC M6-1.0 X 16 G8.8  
HARNESS, TRANSFORMER ADAPTER  
ASSY PCB IGN MOD 4.2L  
SCREW THF M6-1X16 N WA Z/JS  
TAPE ELEC 1/2 FOAM (AS REQ’D)  
DECAL CUSTOMER CONNECT INSIDE  
K
(1) ITEM INCLUDED WITH HARNESS  
(2) ITEM INCLUDED WITH 0D5464B  
(3) ITEM USED WITH EARLY MODEL 208V UNITS ONLY  
(4) ITEMS USED ON 4.2L MODELS ONLY.  
SCREW PPHM #10/32 X 2  
WASHER FLAT #10 ZINC  
WASHER LOCK #10  
NUT HEX #10-32 STEEL  
2
1)  
A
C
UL CIRCUIT BREAKER (ED)  
0F3328  
0D5552  
0D5554  
0D5556  
0D9693  
0F0492  
048927  
023897  
022152  
022158  
0C2454  
029289  
0F1733  
1
1
-
-
-
1
4
4
4
4
7
1
1
COVER ED CB SHORT STND  
CB 0050A 3P 480V S ED4 LL  
CB 0070A 3P 480V S ED4 LL  
CB 0090A 3P 480V S ED4 LL  
CB 0125A 3P 480V S ED4 LL  
INSULATOR CB S (ED-3P)  
SCREW RHM #10-32 X 4-1/2  
WASHER FLAT #10 ZINC  
D
E
F
G
H
J
WASHER LOCK #10  
NUT HEX #10-32 STEEL  
SCREW THF M6-1 X 16 N WA Z/JS  
TAPE ELEC 1/2 FOAM (AS REQ’D)  
DECAL CUSTOMER CONNECT INSIDE  
K
L
2)  
A
C
UL CIRCUIT BREAKER (FD)  
0F3138  
0D5572  
0D5573  
0D5574  
0D5575  
0D5576  
0F0199  
081320  
022473  
022097  
022127  
0C2454  
029289  
0F1733  
1
1
-
-
-
COVER CB CONN BOX  
CB 0150A 3P 600V S FD6 LL  
CB 0175A 3P 600V S FD6 LL  
CB 0200A 3P 600V S FD6 LL  
CB 0225A 3P 600V S FD6 LL  
CB 0250A 3P 600V S FD6 LL  
INSULATOR CB FD FRAME 30MIL  
SCREW SHC 1/4-20 X 4.5 G8.8 NZ  
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK M6-1/4  
-
D
E
F
G
H
J
1
4
4
4
4
7
1
1
NUT HEX 1/4-20 STEEL  
SCREW THF M6-1 X 16 N WA Z/JS  
TAPE ELEC 1/2 FOAM (AS REQ’D)  
DECAL CUSTOMER CONNECT INSIDE  
K
L
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5)  
A
C
D
E
F
G
H
J
K
L
M
N
P
Q
UL CIRCUIT BREAKER (QJ-2P)  
8)  
A
B
C
D
E
F
NEUTRAL BLOCK 390 / 200-400A  
0F8137  
0E7994  
0F8136  
036261  
022473  
022097  
022127  
0F8139  
0C2454  
022237  
048527  
029289  
022770  
0F1733  
1
-
COVER QJ 2P FRM CB  
CB 0225A 240V 2P S QJ22  
0D5466  
039287  
022145  
022129  
045771  
045335  
083896  
0A7822  
2
1
1
1
1
2
2
1
BUS BAR NEUTRAL BLOCK 390  
SCREW HHC M8-1.25 X 45 G8.8 FT  
WASHER FLAT 5/16-M8 ZINC  
WASHER LOCK M8-5/16  
NUT HEX M8-1.25 G8 YEL CHR  
SCREW HHC 1/4-28 X 3/4 G5  
WASHER LOCK 1/4-M6 SS  
1
4
2
2
2
1
7
2
2
1
2
1
COVER QJ 2P CB DISH  
RIVET POP .125 X .275 SS  
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK M6-1/4  
NUT HEX 1/4-20 STEEL  
INSUL CB 2P QJ  
SCREW THF M6-1 X 16 N WA Z/JS  
WASHER LOCK 3/8  
SCREW SHC 3/8-16 X 3/4 G8.8 NZ  
TAPE ELEC 1/2 FOAM (AS REQ’D)  
SCREW RHM 1/4-20 X 3  
G
H
LUG SLDLSS 600/250-1/0 X 1/4-28  
9)  
A
UL CIRCUIT BREAKER (BQ)  
0G1968  
0G1970  
0A2077  
040532  
0C3990  
0E7890  
0E6002  
022859  
0G0008  
023897  
022152  
022158  
0F1733  
029289  
0C2454  
1
-
1
COVER BQ CIR BREAKER CPL 3P  
COVER BQ CIR BREAKER CPL 2P  
CB 0125A 2P 240V S BQ2 LL  
CB 0100A 3P 240V S BQ3 LL  
SCREW PHTT M4-0.7 X 10 ZYC  
BRKT CB MTG BACK  
MTG TRACK BQ SIEMENS CB 3P  
SCREW RHM #10-32 X 3/4  
BRKT BQ CB STANDOFF  
WASHER FLAT #10 ZINC  
WASHER LOCK #10  
NUT HEX #10-32 STEEL  
DECAL CUSTOMER CONNECT INSIDE  
C
DECAL CUSTOMER CONNECT INSIDE  
-
D
E
2
1
-
6)  
A
B
C
UL CIRCUIT BREAKER (225AF) (2P & 3P)  
0F4185  
058306  
0F4165$  
0F4143  
0F4149  
0F4151  
0G5247$  
0G5250  
0G4478  
0F4186  
0F4186AGS0R  
036261  
053640  
038150  
022264  
022471  
029289  
0F1733  
022129  
0F8432  
0F8432A  
0C2454  
0F8451  
049897  
022145  
045771  
0F8843  
W/CB  
1
COVER CB C2-C4 (225AF)  
3
SCREW SHC M8-1.25 X 25 G12.9  
CIRCUIT BREAKERS 200A FRAME (3P)  
CB 0040A 3P 480V 225AF (3P)  
CB 0150A 3P 480V G 225AF  
CB 0200A 3P 480V G 225AF  
CB 200A FRAME G 240V (2P)  
CB 175A 2 POLE 240V 225AF (2P)  
CB 200A 2 POLE 240V 225AF (2P)  
COVER CB DISH 225AF (3P)  
COVER CB DISH 225AF (2P)  
RIVET POP .125 X .275 SS  
SCREW RHM #8-32 X 3-1/4  
WASHER FLAT #8 ZINC  
WASHER LOCK #8-M4  
NUT HEX #8-32 STEEL  
TAPE ELEC 1/2 FOAM  
F
G
H
J
K
L
6
1
6
6
6
1
1
7
REF  
REF  
REF  
REF  
REF  
REF  
REF  
1
M
N
TAPE ELEC 1/2 FOAM  
SCREW THF M6-1 X 16 N WA Z/JS  
D
E
4
2/4  
2/4  
2/4  
2/4  
2
(1) HARDWARE FOR MTG. CB TERMINAL COVERS IS  
SUPPLIED WITH CIRCUIT BREAKERS.  
(2) F  
(2) G  
(2) H  
(2) J  
K
L
(2) M  
(2) QTY. REQ’D FOR “2POLE / 3POLE” BREAKER  
1
6/9  
DECAL CUSTOMER CONNECT INSIDE  
WASHER LOCK M8-5/16  
N
1
1
7
2/3  
4/6  
4/6  
2/3  
2/3  
2
INSULATOR CB 225AF (3P)  
INSULATOR CB 225AF (2P)  
SCREW THF M6-1 X 16 N WA Z/JS  
LUG SLDLSS 300 MCM-6 AL/CU  
SCREW SHC M8-1.25 X 20 G8  
WASHER FLAT 5/16-M8 ZINC  
NUT HEX M8-1.25 G8 CLEAR ZINC  
BUS BAR 200A LUG ADAPTOR  
TERMINAL COVER CB  
P
(2) R  
(2) S  
(2) T  
(2) U  
(2) V  
(1) W  
X
0G3259  
1
DECAL TERMINAL SHOCK HZD BI  
7)  
A
C
D
E
F
G
H
J
UL CIRCUIT BREAKER (400AF)  
0F4187  
0F4166$  
0F1733  
042419  
023897  
022152  
022158  
0C2454  
029289  
052647  
046526  
W/CB  
0A7822  
W/CB  
023334  
022097  
022473  
W/CB  
1
REF  
1
COVER CB C2-C4 400AF  
CIRCUIT BREAKERS 400A FRAME  
DECAL CUSTOMER CONNECT INSIDE  
SCREW RHM 10-32 X 4  
4
4
WASHER FLAT #10 ZINC  
4
WASHER LOCK #10  
4
7
1
NUT HEX #10-32 STEEL  
SCREW THF M6-1 X 16 N WA Z/JS  
TAPE ELEC 1/2 FOAM  
K
(2) L  
(2) M  
N
P
(1) S  
T
U
V
(2) W  
(2) X  
Y
2/3  
2/3  
3
3
2
SCREW SHC M10-1.5 X 25 G12.9  
WASHER LOCK M10  
BUS BAR CB ADAPTER 225-400 A  
LUG SLDLSS 600/250-1/0 X 1/4-28  
TERM COVER CB  
6
6
SCREW HHC 1/4-28 X 1/2 G5  
WASHER LOCK M6-1/4  
6
WASHER FLAT 1/4-M6 ZINC  
SCREW SHC M10-1.5 X 25 G12.9  
WASHER LOCK M10  
2/3  
2/3  
1
W/CB  
0G3259  
DECAL TERMINAL SHOCK HZD BI  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
0G0056  
0G1155  
0F9677  
0G0959  
0G2101  
0G1931  
0G0057  
0F9664  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
ROTOR-2390-35KD1 CPL  
ROTOR-2390-35KD1 CPL (G2)  
ROTOR-2390-45KD1 CPL  
ROTOR-2390-45KD1 CPL (G2)  
ROTOR 25KW 1PH DIRECT 390 1800  
ROTOR 25KW 3PH DIRECT 390 1800  
STATOR-2390-35AD1 CPL  
STATOR-390 45K 2P 1PH DIRECT  
STATOR-2390-35KD1 CPL  
STATOR-2309-45-KD1 CPL  
STATOR-2390-35GD1 CPL  
STATOR-2309-45KW 2P 3PH 208V  
STR-2390--45JD1 CPL  
ASSY STR 390 25AD1 CPL  
ASSY STR 390 25JD3 CPL  
ASSY STR 390 25GD3 CPL  
ASSY STR 390 25KD3 CPL  
INSTR HYPOT TEST (NOT SHOWN)  
ENGINE ADAPTER  
0G0058  
0G0184  
0G0059  
0G0183  
0G6104  
0G2098  
0G2100  
0G1932  
0G2099  
0C9708  
SEE ENGINE EV  
SEE ENGINE EV  
0F5767B  
0E5706  
3
4
5
6
7
8
9
REF  
REF  
REF  
1
1
1
FLEXPLATE  
ASSY FLYWHEEL CPL W/40MM FAN B  
REAR BEARING CARRIER 390/DRCT  
ASSY BRUSH HOLDER 390/HSB  
GUARD REAR BEARING CARRIER  
WASHER FLAT #8 ZINC  
0F7874  
0G0587  
038150  
1
4
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23 *  
24 *  
25  
26  
023454  
1
1
4
4
4
4
1
1
4
4
4
4
1
1
1
1
KEY WOODRUFF #E  
077043E  
04576100BU  
052646  
043123  
051779  
0A2601  
0A2602  
0F8408  
046526  
0C3993  
022264  
CONDUIT FLEX 1.0" ID (35” LG)  
STUD M14-2.0 570 G5 ZINC  
WASHER FLAT M14  
WASHER LOCK M14  
NUT HEX M14-2.0 G8 YEL CHR  
SCREW HHC M16-2.0 X 45 G8.8  
WASHER FLAT .688 ID X 3.25 OD  
SCREW HHC M10-1.50 X 16 G10.9  
WASHER LOCK M10  
SCREW HHTT M4-0.7 X 25 BP  
WASHER LOCK #8-M4  
BALL BEARING-45 MM  
SLIP RING MACHINED  
GUARD REAR BEARING CARRIER  
CONDUIT FLEX .38" ID (60”)  
047248  
070892  
0G0588  
077043A  
* ROTOR REPLACEMENT PARTS  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMPONENTS INCLUDED IN 0G2283D  
1
2
3
4
5
6
7
8
0F1823A  
0F3078  
0F2606  
036261  
0E7358  
052777  
0G1303C  
0F1262  
0F1263  
0F1264  
0F1725C  
067680  
0E6875A  
055911  
0F5459  
0E3161  
0F5462  
0A5062J  
029673  
048467  
0F1958  
082573  
0E4494  
0F3215  
0F6305  
0F6305A  
0F5886  
051713  
049226  
0F5752F  
0F5884  
0F5896  
0C2265  
0C3990  
091526  
051716  
079224  
043182  
051714  
0F3192  
0E7403C  
0G2281  
1
1
1
6
4
3
1
4
1
1
1
1
2
1
1
1
1
4
1
1
1
1
1
1
2
1
3
12  
12  
1
2
2
4
2
4
9
2
7
7
1
1
1
ENCL HSB CONTROL PANEL  
COVER CONTROL PANEL  
HINGE CONTINUOUS H-PANEL  
RIVET POP .125 X .275 SS  
SCREW PPPH HI-LO #4-24 X 3/8  
WASHER FLAT M3  
ASSY PCB R-200 1800 RPM 2.4L  
HOLDER FUSE WICKMANN 178.6150  
ADPTR RH SIDE WICKMAN 178.6191  
ADPTR LH SIDE WICKMAN 178.6192  
ASSY PCB 2AMP 12V UL BATT CHGR  
ASSY VOLTAGE REGULATOR 60HZ  
RELAY 12VDC C FORM W/DIODE  
BLOCK TERM 20A 12 X 6 X 1100V  
DECAL CPL CONTROL PANEL FUSES  
ASSY PCB BOSCH GOV DRIVER  
DECAL CPL 3.9L TB1  
9
10  
11  
12  
13  
14  
15  
16  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
43  
44  
45  
46  
47  
SPACER 9.5H 3.2 ID  
DIO BRIDGE 25A 600V  
CIRCT BRK 7 X 1 ETA 46-500-P  
PLATE HARNESS CLAMP  
SWITCH RKR DPST 125V SPD  
SWITCH RKR DPDT ON-OFF-ON  
DECAL, CONTROL HSB  
SEAL COVER 3.18 X 12.7 X 382  
SEAL COVER 3.18 X 12.7 X 283  
SCREW HHPM M5-0.8 X 12  
WASHER FLAT M5  
WASHER LOCK M5  
RES WW 15R 5% 25W QK CONN  
SCREW PHTT M3.5-0.6 X 10  
SCREW PHTT M3.5-0.6 X 16  
SCREW PHTT M4-0.7 X 12 ZYC  
SCREW PHTT M4-0.7 X 10 ZYC  
SCREW PPHM M5-0.8 X 12 ZNC  
NUT HEX M5-0.8 G8 CLEAR ZINC  
SCREW PPHM M5-0.8 X 30 SS  
WASHER LOCK M3  
NUT HEX M3-0.5 G8 YEL CHR  
SUPPORT ANGLE PCB  
FUSE ATO TYPE 15 AMP (BLUE)  
HARN R-200 CTRL PNL 1800 RPM (NOT SHOWN)  
COMPONENTS INSTALLED PER THIS DRAWING  
A
B
C
D
E
F
G
H
J
056739  
022287  
022473  
022097  
022127  
0F6145  
0F2627A  
091526  
049226  
051713  
1
2
4
2
2
A/R  
1
4
4
4
RELAY SOLENOID 12VDC PNL MNT  
SCREW HHC 1/4-20 X 3/4 G5  
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK M6-1/4  
NUT HEX 1/4-20 STEEL  
SEAL WEATHER .45"DIA  
COVER CONTROL PANEL SIDE  
SCREW PPHM M5-0.8 X 12 ZNC  
WASHER LOCK M5  
K
WASHER FLAT M5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
6
7
8
0F9517  
052860  
052251  
052257  
052252  
052259  
052891  
0536210410  
042909  
047411  
055414  
022447  
022097  
022473  
049813  
022261  
0F9597A  
045764  
062963  
022302  
022131  
065852  
0F9597  
022129  
026204  
022145  
045771  
0F9596  
0F9596A  
1
4
5
5
5
5
5
1
1
1
1
1
1
2
1
1
1
1
4
4
4
1
1
1
1
1
1
1
1
WELDMENT FRAME 2.4L C2  
NUT FLANGED HEX M12-1.75  
DAMPENER VIBRATION 40 BLUE  
SPACER .49 X .62 X 1.87 PWDR/ZNC  
DAMPENER VIBRATION  
WASHER FLAT M12  
SCREW HHC M12-1.75 X 80 G8.8  
ASSY WIRE 14.00"  
9
SCREW HHC M8-1.25 X 30 G8.8  
SCREW HHC M6-1.0 X 16 G8.8  
LUG SLDLSS #2-#8 X 17/64 CU  
WASHER SHAKEPROOF INT 1/4  
WASHER LOCK M6-1/4  
WASHER FLAT M6-1/4 ZINC  
NUT HEX M6 -1.0 G8 YEL CHR  
WASHER SHAKEPROOF INT 3/8  
SUPPORT LH ENGINE 2.4L  
SCREW HHTT M4-0.7 X 8 BP  
SCREW HHC M10-1.25 X 30 G8.8  
WASHER LOCK 7/16  
WASHER FLAT 3/8-M10 ZINC  
SPRING CLIP HOLDER .37-.62  
SUPPORT RH ENGINE 2.4L  
WASHER LOCK M8-5/16  
WASHER SHAKEPROOF INT 5/16  
WASHER FLAT 5/16-M8 ZINC  
NUT HEX M8-1.25 G8 CLEAR ZINC  
SPACER ENGINE MOUNT (2.4L G1)  
SPACER LH ENGINE MOUNT (2.4L G2)  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
6
7
8
9
10  
11  
12  
14  
15  
16  
17  
0F3408B  
0F3411  
025507  
052212  
046526  
022131  
050331A  
050331  
038805Y  
03880400AE  
045771  
1
1
BATTERY TRAY C1 CPL  
STRAP BATTERY RETAINMENT  
WASHER SHAKEPROOF EXT 7/16 STL  
SCREW HHC M10-1.25 X 25 G8.8  
WASHER LOCK M10  
WASHER FLAT 3/8-M10 ZINC  
BATTERY POST COVER RED +  
BATTERY POST COVER BLACK -  
CABLE BATTERY BLACK #1 X 18.00  
CABLE BATT RED #1 X 18.00  
NUT HEX M8-1.25 G8 YEL CHR  
WASHER LOCK M8-5/16  
REF  
REF  
REF  
REF  
REF  
REF  
1
1
REF  
REF  
1
4
REF  
REF  
022129  
0F3976  
0C2454  
022145  
BOOT CONTACTOR CABLES  
SCREW THF M6-1 X 16 N WA Z/JS  
WASHER FLAT 5/16-M8 ZINC  
BATTERY 12VDC 75-AH 26  
077483  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
6
7
8
9
0E6586  
0E0519A  
0C8127  
052619  
022127  
062974  
0G0190  
037561  
022097  
1
1
1
4
1
1
1
1
1
GASKET BOSCH 32 & 40  
ADAPTER CARBURETOR W/PVC CONN  
ELEMENT AIR CLEANER  
SCREW HHC M5-0.8 X 20 G8.8  
NUT HEX 1/4-20 STEEL  
STUD TH 1/4-20 X 4-1/2 G2 ZNC  
PLATE, AIR CLEANER TOP 2.4L  
NUT WING 1/4-20 NYLK  
WASHER LOCK M6-1/4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
0G0408  
046526  
039414  
0G0149  
0E9868A  
0F3217  
042574  
0A8584  
0F4612  
057772  
057765  
043790  
0C7649  
069860E  
063076  
0G1394  
052830  
025507  
062963  
049821  
022129  
0D6029  
0A6751  
0E0502  
022145  
045771  
022131  
049813  
046525  
058306  
022097  
022473  
043116  
026073A  
052243  
0A8258  
0G0664  
0G1502  
047290  
049340  
045757  
0G0951  
0G3910  
0G0608  
0F9965E  
0D2244M  
0F9420  
0E9747  
0G1472A  
0G1476  
0G0707  
0G0950  
0F9583  
0G0792  
0G0792A  
0G1501  
0F9501  
0G0952  
0D3488S  
0G0788  
0G2750  
049721  
026925  
0F2776  
052203  
0F2776D  
1
3
4
1
1
1
1
1
1
1
1
1
1
1
7
7
2
5
3
3
26  
3
1
1
7
3
1
3
2
15  
7
10  
ENGINE 2.4L MITSUBISHI 4G64  
WASHER LOCK M10  
SCREW HHC M8-1.25 X 35 G8.8  
SCREW SHC M14-1.5 X 35 G10.9  
ALTERNATOR DC W/OUT PULLEY  
SPACER DC ALTERNATOR PULLEY  
ADAPTOR 1/8 NPTF TO 1/8 BSPT  
SWITCH OIL PRESSURE 10 PSI 2 POL (R-PANEL)  
SENDER OIL PRESSURE 1/8" NPT (H-PANEL)  
WASHER NYLON .565  
5
(2) 6  
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
ADAPTER M14-1.50 X 3/8 NPT  
BARBED EL 90 3/8 NPT X 3/8  
CLAMP HOSE .38-.87  
HOSE DRAIN ASSY 28"  
WASHER FLAT .531 ID X 1.062 OD  
SCREW HHC M12-1.25 X 20 G10.9  
SCREW HHC M10-1.25 X 45 G8.8  
WASHER SHAKEPROOF EXT 7/16 STL  
SCREW HHC M10-1.25 X 30 G8.8  
SCREW SHC M8-1.25 X 30 G12.9  
WASHER LOCK M8-5/16  
SCREW THF M6-1 X 16 N WA Z/JS  
SWITCH HI-TEMP 245D X 3/8 NPT (R-PANEL)  
TEMPERATURE SENDER DELPHI (H-PANEL)  
WASHER FLAT 5/16-M8 ZINC  
NUT HEX M8-1.25 G8 CLEAR ZINC  
WASHER FLAT 3/8-M10 ZINC  
NUT HEX M6 X 1.0 G8 YEL CHR  
NUT HEX M10-1.25 G8 YEL CHR  
SCREW SHC M8-1.25 X 25 G12.9  
WASHER LOCK M6-1/4  
23  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
(1) 36  
37  
38  
39  
(3) 40  
(1) 44  
45  
WASHER FLAT 1/4-M6 ZINC  
4
2
1
1
SCREW HHC M6-1.0 X 12 G8.8  
PLUG STD PIPE 1/4 STEEL SQ HD  
SCREW HHC M10-1.5 X 60 G8.8  
SCREW HHC M8-1.25 X 25 G10.9  
OIL FILTER G2 ENGINE  
1(REF)  
1
1
1
COIL PACK  
HOSE 3/8 ID SINGLE BRAID (15” LG)  
BARBED EL 90 1/4 NPT X 3/8  
SCREW HHC M6-1.0 X 25 G8.8  
GASKET EXHAUST MANIFOLD  
EXHAUST MANIFOLD G2 (MACHINE) (35KW & 45KW)  
MANIFOLD EXHAUST (MACHINED) (25KW ONLY)  
FLEX PLATE 2 POLE 2.4L G2  
ASSY MAGPICKUP(3/8-24 MALE)  
ADAPTER ENGINE 2.4L MACHINE  
STARTER, 12 VOLT  
CAM SENSOR PIN ASSY  
COVER CAM GEAR G2 REWORKED  
MANIFOLD INTAKE  
GASKET INTAKE MANIFOLD  
SPACER 2.4L G2 FLEX PLATE  
SHIELD HEAT G2  
1
1(REF)  
1
1
1
2
1
1
1
1(REF)  
1
1(REF)  
1
1
1
1
1
46  
47  
48  
49  
50  
51  
52  
(1) 53  
54  
55  
56  
57  
59  
(1) 60  
SHIELD HEAT SML  
BRACKET COIL PACK  
ADAPTER 2.4L CRANKSHAFT MACH  
POLY V-BELT G2 (3600 RPM)  
BELT SERPENTINE 37.0" (1800 RPM)  
PULLEY DC ALTERNATOR (3600 RPM)  
PULLEY 69 OD DC ALTERNATOR (1800 RPM)  
SCREW HHC M6-1.0 X 35 G8.8 BLK  
PLUG STD PIPE 3/8 STEEL SQ HD  
BRACKET, SIGNAL CONDITIONER  
SCREW HHC M8-1.25 X 70 G8.8  
BRACKET SIGNAL CONDITONER  
(1) SUPPLIED WITH ENGINE.  
1(REF)  
1
1
1
3
1
1
2
1
61  
62  
63  
(3) 64  
65  
(3) 66  
(2) NOT USED ON 1800 RPM UNITS.  
(3) USED WITH H-PANEL ONLY  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
6
0F9529  
0F2608  
0F5263  
046526  
059981  
0F2776A  
1
1
1
5
4
1
WELDMENT RADIATOR SUPPORT 2.4L  
RADIATOR 598 X 568 X 49 CPL RH  
V-BELT 31/64" X 57-3/8"  
13  
14  
15  
16  
17  
18  
19  
20  
21  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
0F2862  
0F2560  
022131  
0E2507  
035685  
0F2561  
0C8145  
052250  
0C7043  
022473  
0C8146  
022097  
076749  
048031C  
031971  
0F4496  
042911  
0F2872  
022304  
022195  
022196  
0F8651  
070015  
0F9867  
0F2461  
022145  
022129  
039414  
082774  
0G0795  
0G0816  
049813  
052644  
0C8566  
0C2454  
090283  
080713  
0G4376  
1
1
4
1
4
1
8
2
12  
8
4
16  
1
1
1
1
1
1
2
1
1
9
1
1
1
1
10  
1
1
1
1
8
1
16  
2
1
SPRING TENSION CPL  
PULLEY V-BELT 4" FLANGED  
WASHER FLAT 3/8-M10 ZINC  
PROBE COOLANT LEVEL 3/8 NPTF  
CLAMP HOSE #28 1.32-2.25  
HUB FLEX PLATE  
WASHER FLEX (THIN)  
TAPE FOAM 1 X 1 (26.75” LG)  
DISK FLEX  
WASHER FLAT 1/4-M6 ZINC  
SCREW HHC 5/16-24 X 1.124  
WASHER LOCK M6-1/4  
TANK COOLANT RECOVERY  
CLAMP HOSE BAND 1/4  
BEARING #6205 2NSE C3 E SRI2 S  
PULLEY 4.5" DIA MACHINED  
SCREW HHC M10-1.5 X 30 G8.8  
SCREW HHC 1/2-13 X 2" G8  
WASHER FLAT 1/2 ZINC  
WASHER LOCK 1/2  
NUT HEX 1/2-13 STEEL  
SCREW HHFC M8-1.25 X 20 W/M6  
NUT HEX LOCK 5/16-18 NY INS SS  
SHAFT FAN DRIVE  
RETAINER BEARING  
WASHER FLAT 5/16-M8 ZINC  
WASHER LOCK M8-5/16  
WASHER LOCK M10  
SCREW HHC M10-1.5 X 30 G10.9  
BRACKET, SIGNAL CONDITIONER (USED ONLY  
WITH QTA PRODUCT)  
7
9
10  
11  
12  
0F5050A  
0F2573  
0F4011  
0F2572  
0G2990  
1
1
1
1
1
SHIELD RADIATOR C4  
PULLEY FAN V-GROOVE 9"  
FAN COOL 22" DIA 10 BLADE LH  
ARM TENSIONER  
SHOULDER BOLT 3/8 X 1/2"  
SCREW HHC M8-1.25 X 35 G8.8  
KEY WOODRUFF 4 X 19D  
HOSE LOWER RADIATOR G2  
HOSE UPPER RADIATOR G2  
NUT HEX M6 X 1.0 G8 YEL CHR  
SPACER .5 X 1.5 X .25 STL/ZINC  
SCREW HHFC M6-1.0 X 20 G8.8  
SCREW THF M6-1 X 16 N WA Z/JS  
CAP RADIATOR 13 PSI  
1
1
BRACKET COOLANT TANK  
WASHER BELLEVILLE .75X.38X.028  
BEARING PRESS NOTE:  
APPLY LOCTITE 620 BEARING RETAINMENT  
COMPOUND TO BEARING SURFACE ON ITEM 37  
PRIOR TO PRESSING ITEM 28 ONTO ITEM 37.  
ALSO APPLY LOCTITE 620 BEARING RETAINMENT  
COMPOUND TO THE OUTSIDE OF 28 PRIOR TO  
INSTALLING ITEM 28 INTO ITEM 38.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
026915  
075580  
0F6390C  
0F6390B  
039253  
022145  
022129  
045771  
0E8286  
026812  
0F8379  
057823  
059057  
047527  
0D1509  
050279  
050280  
0F2119  
0E6586  
0E4394  
0E4395  
040105  
057753B  
0G4573C  
0G4573B  
0F7790E  
0F7790H  
0E7121  
022097  
046580  
035685  
0F6155  
047290  
057823  
2
1
1
1
2
2
2
2
1
2
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
4
2
1
1
2
NIPPLE CLOSE 3/4 X 1.375  
FLANGE FUEL INLET  
REGULATOR ASSY 2.4L (25KW)  
REGULATOR ASSY 2.4L (35KW & 45KW)  
SCREW HHC M8-1.25 X 20 G8.8  
WASHER FLAT 5/16-M8 ZINC  
4
5
6
7
9
10  
11  
13  
14  
15  
16  
17  
WASHER LOCK M8-5/16  
NUT HEX M8-1.25 G8 CLEAR ZINC  
STREET EL 45D 1/2 NPT BRASS  
ELBOW 90D 3/4 NPT  
NIPPLE PIPE 3/4 NPT X 7  
CLAMP HOSE #10 .56 - 1.06  
HOSE 3/4 ID SAE-30R2 (18” LG)  
BARBED STR 1/2 NPT X 3/4  
DECAL INLET PRESSURE  
DECAL FUEL INLET NG (NATURAL GAS APPLICATION)  
DECAL FUEL INLET LPG (LP VAPOR APPLICATION)  
O-RING 45.63 ID X 2.62 WIDTH  
GASKET BOSCH 32  
ACTUATOR BOSCH 40 GOVERNOR (45KW)  
ACTUATOR BOSCH 32 GOVERNOR (25 & 35KW)  
HOSE COOL 2 IN ID 20R4 (45KW)  
HOSE 1.5 ID X 2 LG 20R4 (35KW)  
MIXER ACTUATOR 32MM MACHINED (25KW)  
MIXER ACTUATOR 40MM MACHINED (35 & 45KW)  
VENTURI THROTTLE 26MM (35 & 45KW)  
VENTURI THROTTLE 19MM (25KW)  
O-RING 47.625 ID X 2.38 WIDTH  
WASHER LOCK M6-1/4  
18  
19  
20  
21  
22  
23  
24  
26  
27  
28  
29  
30  
32  
SCREW SHC M6-1.0 X 45 G12.9  
CLAMP HOSE #28 1.32-2.25  
HARNESS CPL FUEL JUMPER  
HOSE 3/8 ID SINGLE BRAID (18” LG)  
CLAMP HOSE #10 .56-1.06  
RECONFIGURING THE FUEL SYSTEM  
Note: All models are configured to run on natural gas from the factory.  
To reconfigure the fuel system from NG to LP, follow these steps:  
1. Turn the main gas supply off.  
2. Remove the carburetor fuel hose from the outlet port of the demand regulator (See Detail “A”).  
3. Disconnect the power wires from the fuel solenoid located on top of the regulator assembly.  
4. Loosen the spring clamp on the small fuel enrichment line and remove the hose from the hose barb.  
5. Remove the black pipe assembly from the outlet port of the demand regulator.  
6. Remove the NG fuel jet (loosen counter clockwise) from the outlet port.  
7. Remove the LP fuel jet (loosen counter clockwise) from the jet keeper port on the side of the regulator housing.  
Install this jet into the outlet port in the regulator casting.  
Note: The jet sizes are stamped on the individual jets. The larger jet size is used for running on NG.  
8. Install the previously removed NG jet into the jet keeper port on the side of the regulator housing.  
9. Install the previously removed black iron pipe onto the outlet port of the demand regulator.  
10. Reverse steps 1-4 in this procedure to reactivate the demand regulator.  
11. For LP vapor application substitute LPG fuel inlet decal p/n 050280 for NG fuel inlet decal p/n 050279 (Item 17).  
12. When switching fuel types, the proper dip switch settings must be made to the control panel. See owners  
manual, fuel section, for more details.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
6
7
8
0G0045 (XX)  
0C2454  
0F5849 (XX)  
087233  
1
54  
2
2
4
2
2
1
2
21  
1
2
1
1
2
2
1
3
1
1
10  
38  
2
1
2
1
2
2
2
10  
2
4
3
1
2
2
REAR WRAP C2 CPL  
SCREW THF M6-1 X 16 N WA Z/JS  
DOOR C2  
RIVET POP .1875 X .450 SS  
SCREW TH-FRM M6 W/CAP SHKPRF W  
DISCHARGE DUCT LH & RH SIDE C2  
FRONT CORNERS C2  
DISCHARGE CENTER DUCT C2  
NUT HEX M6 X 1.0 G8 YEL CHR  
NUT HEX LOCK M6-1.0 SS NY INS  
ROOF C2  
SLITTER C4  
SPLITTER LOWER C4  
SPLITTER STINGER C2  
SUPPORT SPLITTER LH C2  
TAB PULL  
0E3257  
0F5852 (XX)  
0F9833 (XX)  
0F5851 (XX)  
049813  
077992  
0F9835 (XX)  
0F2786  
0F2785  
0F3364  
0F4880  
0F5049  
0C2634A  
022473  
022097  
022127  
0F3072  
9
10 *  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
ASSEMBLY COVER ACCESS  
WASHER FLAT 1/4-M6 ZINC  
WASHER LOCK M6-1/4  
NUT HEX 1/4-20 STEEL  
INSULATION RETAINMENT HANGER  
WASHER SELF LOCKING DOME #4-40  
INSULATION DOOR C2  
078115  
0F4051  
0F4051A  
0F5048D  
0E5968  
0F3760K  
0F3760E  
0F4051C  
0F3890B  
0F4051B  
0F3890  
0F3890A  
0F3760L  
042568  
0912970094  
022447  
INSULATION ROOF TOP  
VISE-ACTION LATCH SLOTTED CIR  
GASKET EXTRUDED TRIM (328” LG)  
INSULATION SPLITTER  
INSULATION SPLITTER  
INSULATION DUCT  
RETAINER INSULATION (820)  
INSULATION DUCT SIDES  
RETAINER INSULATION (450)  
RETAINER INSULATION (740)  
INSULATION LOWER SPLITTER  
SCREW HHC M6-1.0 X 20 G8.8  
ASSY WIRE 14 AWG 34.8" GRN/YEL  
WASHER SHAKEPROOF INT 1/4  
INSULATION REAR WRAP  
KEY VISE-ACTION LATCH SLOT CIR  
WASHER SELF LOCKING DOME #8-32  
2
1
1
6
0F4051E  
0F8869D  
078115A  
OPTIONAL COMPARTMENT MATERIALS:  
ALL P/N’S WITH AN (XX) SUFFIX INDICATE A MULTIPLE MATERIAL AND COLOR OPTION.  
USE THE FOLLOWING LEGEND TO IDENTIFY THE CORRECT PART NUMBER:  
PART NO.  
0XXXXXSN  
0XXXXXAN  
0XXXXXSG  
0XXXXXAG  
MATERIAL  
STEEL  
ALUMINUM  
STEEL  
COLOR  
TAN  
TAN  
GRAY  
GRAY  
ALUMINUM  
* ALUMINUM ENCLOSURE NOTE: ALL ENCLOSURE PANELS THAT FASTEN TO  
THE BASE FRAME MUST BE SECURED USING ITEM 2 & 5 THREAD FORMING  
FASTENER AND ITEM 39 LOCK NUT. LOCK NUT IS TO BE INSTALLED AFTER THREAD  
FORMING FASTENER HAS PENETRATED THROUGH EXTRUSIONS IN  
ENCLOSURE PANELS. ALL ROOF PANELS ARE TO BE SECURED IN THE SAME  
MANNER.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
0F9794  
0G0113  
0G1007  
0F2830  
0F2962  
080762  
0E0170A  
0C2454  
0G0776  
0G0007  
044149  
085917  
0D2611  
0E8816  
049721  
022097  
022473  
036797  
022259  
070006  
088775  
022241  
085917  
0F2809  
0F2808B  
2
1
1
2
2
5
1
4
1
1
1
2
2
1
4
4
4
1
2
2
2
10  
10  
1
1
MUFFLER 7" X 9" X 18-1/2" 2" IN/OUT  
EXHAUST ELBOW 2 1/4 OD 2 1/2OD  
BRACKET MUFFLER  
MUFFLER BRACKET STIFFENER  
MUFFLER STRAP  
BOLT U 3/8-16 X 2.62  
EXHAUST BLANKET 988MM (C2)  
SCREW THF M6-1 X 16 N WA Z/JS  
PIPE EXHAUST G2  
DIFFUSER EXHAUST WELDMENT  
GASKET EXHAUST RING  
WASHER LOCK 3/8 SS  
SCREW HHC 3/8-16 X 1-3/4 SS  
EXHAUST FLANGE 2" PIPE  
SCREW HHC M6-1.0 X 35 G8.8 BLK  
WASHER LOCK M6-1/4  
WASHER FLAT 1/4-M6 ZINC  
BOLT U 5/16-18 X 2.25  
NUT HEX 5/16-18 STEEL  
WASHER LOCK M8 SS  
WASHER FLAT 3/8 SS  
NUT HEX 3/8-16 STEEL  
WASHER LOCK 3/8 SS  
PIPE EXHAUST CROSSOVER  
PIPE EXHAUST MUFFLER OUT  
* NOT USED ON OPEN SET.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.)  
A
C2 UNITS  
0F9832  
1
1
3
SHIELD CONN BOX C2  
SHIELD CONTROL STAND C2  
SCREW THF M6-1 X 16 N WA Z/JS  
0F9832GGS0R  
0C2454  
B
2.)  
A
C3 UNITS  
0F9832B  
1
1
3
SHIELD CONTROL STAND C3  
SHIELD CONTROL STAND C3  
SCREW THF M6-1 X 16 N WA Z/JS  
0F9832KGS0R  
B
0C2454  
3.)  
A
B
C4 UNITS  
0F9832A  
0C2454  
1
2
SHIELD CONTROL STAND C4  
SCREW THF M6-1 X 16 N WA Z/JS  
4.)  
A
C5 UNITS  
0F9832C  
1
1
1
1
1
1
3
SHIELD CONTROL STAND C5  
SHIELD CONTROL STAND C5  
SHIELD CONTROL STAND C5  
SHIELD CONTROL STAND C5  
SHIELD CONTROL STAND C5  
SHIELD CONTROL STAND C5  
SCREW THF M6-1 X 16 N WA Z/JS  
0F9832D  
0F9832EGS0R  
0F9832HGS0R  
0F9832JGS0R  
0F9832FGS0R  
0C2464  
B
C
Download from Www.Somanuals.com. All Manuals Search And Download.  
. A v 0 4 / 0 7 k P g B 0 0 a 1 c R e  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Extron electronic Stereo Receiver MGP 464 HD SDI User Manual
Fellowes Printer Accessories Quasar e 500 User Manual
Fortinet Network Card FSAE User Manual
Fujitsu TV Cables FCN 086 User Manual
GBC Paper Shredder 3870M User Manual
GE Freezer WMR04GAV User Manual
Gemini CD Player CD 340 User Manual
GE Monogram Ventilation Hood ZV925SL User Manual
GE Monogram Washer ZBD6605 User Manual
Global Machinery Company Drill LD108V User Manual