Crown Boiler Boiler CWD060 User Manual

CWD Series  
Gas-Fired Direct Vent Hot Water Boilers  
INSTALLATION INSTRUCTIONS  
These instructions must be afxed on or adjacent to the boiler  
Models:  
CWD060  
WARNING: Improper installation,  
adjustment, alteration, service or  
maintenance can cause property  
damage, injury, or loss of life. For  
assistance or additional information,  
consult a qualied installer, service  
agency or the gas supplier. Read  
these instructions carefully before  
installing.  
CWD083  
CWD110  
CWD138  
CWD165  
CWD193  
CWD220  
CWD245  
Manufacturer of Hydronic Heating Products  
P.O. Box 14818 3633 I. Street  
Philadelphia, PA 19134  
Download from Www.Somanuals.com. All Manuals Search And Download.  
I Product Description  
The CWD series boiler is a cast iron gas red boiler designed for use in forced hot water heating systems. It is is a low  
pressure boiler intended for use in closed heating systems with water temperatures under 240F. This boiler may be vented either  
vertically or horizontally with combustion air supplied from either outdoors or (under certain conditions) indoors. It is ideal for  
use in installations where a reliable source of clean indoor combustion air cannot be guaranteed.  
II Specications  
FIGURE 1: GENERAL CONFIGURATION  
TABLE 1: SPECIFICATIONS  
WATER  
INPUT  
(MBH)  
DOE HTG.  
CAPY (MBH)  
I=B=R NET  
RATING (MBH)  
AFUE  
(%)  
FIG 1  
VENT  
CONTENT  
(Gal.)  
MODEL  
SECTIONS  
DIM. “A” (in.) DIA. (in.)  
CWD060  
3
60  
51  
71  
94  
44  
62  
82  
85.1  
85.1  
85.2  
16-1/8  
19-3/4  
23-3/8  
3
3
3
2.0  
2.6  
3.1  
CWD083  
CWD110  
4
5
82.5  
110  
CWD138  
CWD165  
CWD193  
CWD220  
6
7
8
9
137.5  
165  
118  
142  
165  
189  
103  
123  
143  
164  
85.2  
85.2  
85.2  
85.2  
27  
3
3.6  
4.2  
4.7  
5.2  
30-5/8  
34-1/8  
37-3/4  
3 OR 4  
3 OR 4  
3 OR 4  
192.5  
220  
CWD245  
10  
245  
211  
183  
85.3  
41-3/8  
3 OR 4  
5.8  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
III Before Installing  
1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance  
with this manual and the authority having jurisdiction.  
• In the absence of an authority having jurisdiction, installation must be in accordance with this manual and the National  
Fuel Gas Code, ANSI Z223.1.  
• Where required by the authority having jurisdiction, this installation must conform to the Standard for Controls and  
Safety Devices for Automatically Fired Boilers (ANSI/ASME CSD-1).  
2) Read Section VI to verify that the maximum combustion air and exhaust pipe lengths will not be exceeded in the planned  
installation. Also verify that the vent terminal can be located in accordance with Section VI.  
3) Make sure that the boiler is correctly sized:  
• For heating systems employing convection radiation (baseboard or radiators), use an industry accepted sizing method  
such as the I=B=R Heat Loss Calculation Guide (Pub. #H21 or #H22) published by the Hydronics Institute in Berkely  
Heights, NJ.  
• For new radiant heating systems, refer to the radiant tubing manufacturer’s boiler sizing guidelines.  
• For systems including a Crown Mega-Stor indirect water heater, size the boiler to have either the DOE Heating Capacity  
required for the Mega-Stor or the net rating required for the heating system, whichever results in the larger boiler.  
• For systems that incorporate other indirect water heaters, refer to the indirect water heater manufacturer’s instructions for  
boiler output requirements.  
4) Make sure that the boiler received is congured for the correct gas (natural or LP).  
5) This boiler is not designed for use with return temperatures under 120F for a sustained period of time. Some systems, such  
as those having large water contents, may require a return water bypass or other special provisions to protect the boiler  
against low return temperatures. Failure to provide such provisions if needed could result in severe corrosion damage to the  
boiler. For more information on when low water temperatures protection is required, and appropriate protection, see Part  
VIII.  
6) For installations at altitudes above 2000ft, special orice and pressure switches are required. Make sure that the boiler is  
congured for use at the correct altitude.  
NOTICE  
This product must be installed by a licensed plumber or gas tter when installed within the Commonwealth of Massachusetts.  
See Appendix A for additional important information about installing this product within the Commonwealth of Massachusetts.  
IV Locating the Boiler  
1) Boiler clearances are shown in Figure 2. Figure 2a shows clearances from the boiler when outdoor combustion air is  
used. Figure 2b shows clearances from the boiler when combustion air is obtained from the boiler room. These minimum  
clearances apply to all types of combustible construction as well as noncombustible walls, ceilings and doors. At least 24”  
must be provided for servicing at the front of the boiler. This front clearance may be provided through a door, such as a  
closet door. Boiler will be much easier to service if at least 12” is provided from the sides and rear of the boiler to walls.  
2) Clearances from venting to combustible material depends upon the type of venting, whether the vent pipe is enclosed, and  
whether the venting is vertical or horizontal. See Table 2 for vent clearance information.  
3) Boiler may be installed on a non-carpeted combustible surface.  
4) The relief valve must not be moved from the location shown in Figure 1.  
5) When combustion air is obtained from the boiler room, a 10” clearance is required from the side of the boiler having the air  
inlet collar to combustible or non-combustible obstruction (Figure 2b).  
6) The boiler should be located so as to minimize the length of the vent system.  
7) Do not install this boiler in a location where gasoline or other ammable vapors or liquids will be stored or used. Do  
not install this boiler in an area where large amounts of airborne dust will be present, such as a workshop. When indoor  
combustion air is used, do not install in a location where sources of hydrocarbons will be stored or used. Some common  
sources of hydrocarbons include bleaches, fabric softeners, paints, cleaners, refrigerants, and cat boxes. Traces of these  
substances can be drawn into the boiler causing severe corrosion damage to the boiler and /or objectionable odors.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 2a: CLEARANCES WHEN BOILER IS DIRECT VENTED (OUTDOOR COMBUSTION AIR IS USED)  
FIGURE 2b: CLEARANCES WHEN COMBUSTION AIR IS OBTAINED FROM BOILER ROOM  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 2: CLEARANCES FROM VENT PIPING TO COMBUSTIBLE CONSTRUCTION  
MINIMUM CLEARANCE  
TO COMBUSTIBLE  
MATERIAL  
TYPE OF VENT PIPE  
PIPE DIRECTION  
ENCLOSURE  
HEAT FAB SAF-T VENT  
PROTECH FASNSEAL  
PROTECH FASNSEAL W2  
METAL-FAB CORR/GUARD  
AT LEAST ONE SIDE OPEN,  
COMBUSTIBLE MATERIAL ON A  
MAXIMUM OF THREE SIDES  
VERTICAL OR  
HORIZONTAL  
1”  
HEAT FAB SAF-T VENT  
PROTECH FASNSEAL  
Z-FLEX Z-VENT III  
HORIZONTAL OR VERTICAL  
WITH OFFSETS  
8”  
6”  
ENCLOSED ON ALL FOUR SIDES  
METAL-FAB CORR/GUARD  
HEAT FAB SAF-T VENT  
PROTECH FASNSEAL  
Z-FLEX Z-VENT III  
VERTICAL WITH NO OFFSETS  
ENCLOSED ON ALL FOUR SIDES  
ENCLOSED ON ALL FOUR SIDES  
METAL-FAB CORR/GUARD  
PROTECH FASNSEAL W2  
VERTICAL OR HORIZONTAL  
VERTICAL OR HORIZONTAL  
3”  
0”  
UNENCLOSED OR ENCLOSED ON  
ALL SIDES  
HEAT FAB SAF-T VENT SC  
REFER TO “B” VENT  
MANUFACTURER’S  
INSTRUCTIONS  
“B” VENT CHASE USED AS PART OF  
CROWN COAXIAL VENT SYSTEM*  
PER “B” VENT MANFACTUER’S  
INSTRUCTIONS  
VERTICAL  
* “B” Vent is used as a chase to carry combustion air in this system - never attempt to vent a CWD boiler using “B” vent  
V Air for Combustion and Ventilation  
Sufcient fresh air must be supplied for both combustion and ventilation. In general, combustion air is obtained in one of  
two ways:  
• Direct Vent Installations – Combustion air is piped directly to the boiler inlet collar from the outdoors. This is also  
sometimes called a “sealed combustion” installation.  
• Direct Exhaust Installations – Combustion air is obtained from the boiler room. In some cases, openings or duct work  
may be run from the outdoors to the boiler room, however the ducting is not connected directly to the boiler.  
Air for ventilation is required to keep various boiler components from overheating and is always obtained from indoors. To  
ensure an adequate combustion and ventilation air supply, perform the following steps:  
Step 1: Determine whether the boiler is to be installed in a building of unusually tight construction  
A good denition of “unusually tight construction” is construction having all of the following features:  
• Walls and ceilings exposed to outside atmosphere have a continuous water vapor retarder with a rating of 1 perm or less  
with openings gasketed and sealed.  
• Weather stripping has been added on openable windows and doors.  
• Caulking and sealants are applied to areas such as joints around window and door frames, between sole plates and oors,  
between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other  
openings.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 2: Determine whether the boiler is to be installed in a conned space  
A conned space is dened by the National Fuel Gas Code as having a volume less than 50 cubic feet per 1000 BTU/hr  
input of all appliances installed in that space. To determine whether the boiler room is a conned space:  
1) Total the input of all appliances in the boiler room in thousands of BTU/hr. Round the result to the next highest 1000 BTU/  
hr.  
2) Find the volume of the room in cubic feet. The volume of the room in cubic feet is:  
Length (ft) x width (ft) x ceiling height (ft)  
In calculating the volume of the boiler room, consider the volume of adjoining spaces only if no doors are installed between  
them. If doors are installed between the boiler room and an adjoining space, do not consider the volume of the adjoining  
space, even if the door is normally left open.  
3) Divide the volume of the boiler room by the input in thousands of BTU/hr. If the result is less than 50, the boiler room is a  
conned space.  
Example:  
A CWD245 and a water heater are to be installed in a room measuring 6ft – 3 in x 7ft with an 8 ft ceiling. The water heater  
has an input of 30000 BTU/hr:  
Total input in thousands of BTU/hr = (245000 BTU/hr + 30000 BTU/hr) / 1000 = 275  
Volume of room = 6.25 ft x 7 ft x 8 ft = 350 ft3  
350/275 = 1.27. Since 1.27 is less than 50, the boiler room is a conned space.  
Step 3: Decide whether the boiler will be direct vented or direct exhausted  
The boiler must be direct vented (combustion air piped directly to the boiler) if:  
• The boiler is to be installed in a laundry room  
• The building in which the boiler is installed has an indoor pool.  
• The boiler is located in an area having any of the contaminants described in Section IV.  
It is also strongly recommended that combustion air be piped from outside when the boiler is installed in a building of  
unusually tight construction.  
Step 4: If the boiler is Direct Vented, Provide Air as Follows (If Indoor Combustion Air is used,  
Skip to Step 5):  
1) Combustion air piping must not exceed the maximum lengths called for in Section VI.  
2) Although combustion air is obtained directly from outdoors, openings may be required into the boiler room to allow for  
adequate equipment ventilation. The following guidelines apply regardless of whether or not the building is of unusually  
tight construction:  
Unconned Space– Natural inltration into the boiler room will provide adequate air for ventilation without additional  
openings into boiler room.  
Conned Space – Provide two openings into the boiler room, one near the oor and one near the ceiling. The top edge of  
the upper opening must be within 12” of the ceiling and the bottom edge of the lower opening must be within 12” of the  
oor (Fig 3). The minimum opening dimension is 3 inches.  
• If the CWD boiler is the only gas-burning appliance in the boiler room, these openings must each have a free area of 100  
square inches.  
• If other gas-burning appliances are in the boiler room, size the openings in accordance with the appliance manufacturer’s  
instructions or the National Fuel Gas Code. Minimum opening free area is 100 square inches regardless of opening  
requirements for other appliances.  
• If the total volume of both the boiler room and the room to which the openings connect is less than 50 cubic feet per 1000  
BTU/hr of total appliance input, install a pair of identical openings into a third room. Connect additional rooms with  
openings until the total volume of all rooms is at least 50 cubic feet per 1000 BTU/hr of input.  
• The “free area” of an opening takes into account the blocking effect of mesh, grills, and louvers. Where screens are used,  
they must be no ner than ¼” (4 x 4) mesh.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 5: If Indoor Combustion Air is Used, Provide Air as Follows:  
1) Buildings of other than unusually tight construction:  
Unconned Space– Natural inltration into the boiler room will normally provide adequate air for combustion and  
ventilation without additional louvers or openings into boiler room.  
Conned Space – Provide two openings into the boiler room, one near the oor and one near the ceiling. The top edge of  
the upper opening must be within 12” of the ceiling and the bottom edge of the lower opening must be within 12” of the  
oor (Fig 3).  
• Each opening must have a free area of 1 square inch per 1000 BTU/hr input of all gas burning appliances in the boiler  
room. The minimum opening dimension is 3 inches. Minimum opening free area is 100 square inches per opening.  
• If the total volume of both the boiler room and the room to which the openings connect is less than 50 cubic feet per 1000  
BTU/hr of total appliance input, install a pair of identical openings into a third room. Connect additional rooms with  
openings until the total volume of all rooms is at least 50 cubic feet per 1000 BTU/hr of input.  
• The “free area” of an opening takes into account the blocking effect of mesh, grills, and louvers. Where screens are used,  
they must be no ner than ¼” (4 x 4) mesh.  
2) Buildings of unusually tight construction:  
If at all possible, direct vent the boiler. Where the boiler must be installed in unusually tight construction and cannot be  
direct vented, openings must be installed between the boiler room and the outdoors or a ventilated space, such as an attic  
or crawl space, which communicates directly with the outdoors. Two openings are required. The top edge of the upper  
opening must be within 12 inches of the ceiling. The bottom edge of the lower opening must be within 12 inches of the  
oor. Size openings and ducts as follows:  
Vertical ducts or openings directly outdoors (Fig 4, Fig 5, Fig 6) – Each opening must have a free cross sectional area of  
1 square inch per 4000 BTU/hr of the total input of all gas-red appliances in the boiler room but not less than 100 square  
inches. Minimum opening size is 3 inches.  
• Openings to outdoors via horizontal ducts (Fig 7) - Each opening must have a free cross sectional area of 1 square inch  
per 2000 BTU/hr of the total input of all gas red appliances in the boiler room but not less than 100 square inches.  
Minimum opening size is 3 inches.  
• The “free area” of an opening takes into account the blocking effect of mesh, grills, and louvers. Where screens are used,  
they must be no ner than ¼” (4 x 4) mesh.  
FIGURE 3: BOILER INSTALLED IN A CONFINED SPACE - VENTILATION OR  
COMBUSTION / VENTILATION AIR FROM INSIDE  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 4: ALLAIR FROM OUTSIDE USING VENTILATED CRAWL SPACE AND ATTIC  
FIGURE 5: ALLAIR FROM OUTSIDE USING VENTILATED ATTIC  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 6: ALLAIR FROM OUTSIDE USING OPENINGS INTO BOILER ROOM  
FIGURE 7: ALLAIR FROM OUTSIDE USING HORIZONTAL DUCTS INTO BOILER ROOM  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
VI Venting  
WARNING  
Failure to vent this boiler in accordance with these instructions could result in unreliable boiler  
operation, severe damage to the boiler or property, or unsafe operation:  
* Do not attampt to vent this boiler with galvanized, PVC, or any other vent system not listed in Table 4.  
* Do not attempt to mix components from different approved vent systems.  
* Do not install a barometric damper or drafthood on this boiler.  
* Do not attempt to use the vent system for this boiler with any other appliance.  
* Moisture and ice may form on the surfaces around the vent termination. To prevent deterioration,  
surfaces should be in good repair (sealed, painted, etc.)  
A. Vent System Design  
There are three basic ways to vent the CWD boiler:  
Horizontal (“side wall”) Venting - Vent system exits the building through an outside wall. Combustion air is either  
obtained through a separate pipe from outside (a “direct vent” installation) or obtained from the boiler room (a “direct  
exhaust” installation).  
Vertical Non-Coaxial Venting - Vent system exits the building through a roof. Combustion air is either obtained  
through a separate pipe from outside (a “direct vent” installation) or obtained from the boiler room (a “direct exhaust”  
installation).  
Vertical Coaxial Venting - Vent system exits the building through a roof. A portion of the vent system is coaxial, meaning  
that it consists of a “pipe within a pipe”. Flue gasses exit the building through the inner pipe and combustion air is drawn  
through the space between the two pipes.  
For each of the above three basic methods, there are several variations, resulting in a total of 13 options for venting  
the CWD boiler. A description of each of these venting options is listed in Tables 3a - 3c. For clarity, these vent options are  
numbered from 1 to 13 in Table 3. One of the vent option columns in Table 3 must match the planned vent and air intake  
system exactly. In addition, observe the following guidelines:  
1) Approved vent systems - Use only one of the approved vent systems shown in Table 4. These systems are made of a special  
stainless steel alloy (AL29-4C) for protection against corrosive ue gas condensate. They are also designed to provide a gas  
tight seal at all joints and seams so that ue gas does not enter the building. Each approved vent system has unique method  
for installation - do not attempt to mix components from different vent systems. The only exceptions are:  
• Heat Fab Saf-T Vent SC may be combined with Saf-T Vent EZ Seal.  
• Protech FasNSeal W2 may be combined with Protech FasNSeal.  
See the vent installation section of this manual for information on how this can be done.  
Heat Fab Saf-T Vent SC is a double wall vent system which can be used in two ways on CWD installations. In vertical  
coaxial vent systems (Vent Options 12 and 13), the space between the inner and outer pipes is used as a conduit to bring  
combustion air to the boiler. In Horizontal (Vent Options 1 to 5) and Vertical (Option 6 to 10) vent systems, Saf-T Vent SC  
can be used to obtain a 0” clearance to combustible construction. When this is done, the space between the inner and outer  
pipes is used for ventilation, but boiler combustion air comes from elsewhere.  
Protech FasNSeal W2 is also a double wall vent system. In some cases, it can used to obtain closer clearances to  
combustible construction than are possible using Protech FasNSeal (see Table 2). The space between the inner and outer  
pipes on FasNSeal W2 cannot be used as a combustion air conduit.  
The Crown Vertical coaxial vent system (Vent Option 11) is similar to that constructed using Heat Fab Saf-T Vent SC  
except it is constructed by running one of the 3” single wall vent systems shown in Table 4 inside 5” type “B” vent. The  
space between the 3” vent and the “B” vent forms a conduit to bring combustion air to the boiler. The advantage of this  
system is that it can be constructed using any of the vent systems shown in Table 4 except for Heat Fab Saf-T Vent SC and  
Protech FasNSeal W2. No turns are permitted in the coaxial section of this system.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 3a: SUMMARY OF HORIZONTAL VENTING OPTIONS  
VENT OPTION #  
1
2
3
4
5
(RESERVED  
FOR FUTURE  
USE)  
HORIZONTAL  
DIRECT  
EXHAUST  
HORIZONTAL  
DIRECT  
EXHAUST  
CLASSIFICATION USED IN THIS  
MANUAL  
HORIZONTAL  
DIRECT VENT  
HORIZONTAL  
DIRECT VENT  
ILLUSTRATED IN FIGURE  
8a OR 8b  
WALL  
8a OR 8b  
WALL  
9
9
VENT PIPE STRUCTURE  
PENETRATION  
WALL  
N.A.  
WALL  
N.A.  
AIR INTAKE PIPE STRUCTURE  
PENETRATION  
WALL  
WALL  
VENT PIPE SIZE  
3”  
4”  
4”  
4”  
3”  
4”  
AIR INTAKE PIPE SIZE  
CWD060 - CWD138  
N.A.  
55 FT  
N.A.  
55 FT  
55 FT  
55 FT  
CWD165  
CWD193  
CWD220  
CWD245  
35 FT  
25 FT  
15 FT  
N.R.  
55 FT  
55 FT  
55 FT  
35 FT  
25 FT  
15 FT  
55 FT  
55 FT  
55 FT  
55FT  
60 FT  
60 FT  
60 FT  
60 FT  
60 FT  
10 FT  
N.A.  
N.A.  
N.A.  
N.A.  
N.A.  
55 FT  
N.A.  
N.A.  
N.A.  
N.A.  
N.A.  
CWD060 - CWD138  
CWD165  
60 FT  
40 FT  
30 FT  
20 FT  
N.R.  
CWD193  
CWD220  
CWD245  
3” 90 ELBOW,  
TEE, OR  
4” 90 ELBOW,  
TEE, OR  
CROWN  
CROWN  
3” 90 ELBOW  
OR TEE  
4” 90 ELBOW  
OR TEE  
EXHAUST TERMINAL  
AIR INTAKE TERMINAL  
COAXIAL  
TERMINAL  
#50-003  
COAXIAL  
TERMINAL  
#50-004  
4” 90 ELBOW  
OR CROWN  
COAXIAL  
TERMINAL  
#50-003  
4” 90 ELBOW  
OR CROWN  
COAXIAL  
TERMINAL  
#50-004  
N.A.  
N.A.  
N.A.  
VENT MATERIAL  
APPROVED VENT SYSTEM SHOWN IN TABLE 4  
GALVANIZED OR PVC N.A.  
AIR INTAKE MATERIAL  
“N.R” - Not recommended “N.A.” - Not applicable  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 8a: HORIZONTAL DIRECT VENTING USING SEPARATE TERMINALS (VENT OPTIONS 1-2)  
FIGURE 8b: HORIZONTAL DIRECT VENTING USING COAXIAL TERMINAL (VENT OPTIONS 1-2)  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 9: HORIZONTAL DIRECT EXHAUST VENT SYSTEM (VENT OPTIONS 4,5)  
2) Maximum Vent and Air Intake Lengths - The maximum length of the vent air intake piping depends upon the vent option  
selected, the vent pipe size, and the boiler size. See Table 3 for the maximum vent length. In addition to the maximum  
length of piping shown in Table 3, the following ttings may also be used:  
• Horizontal Vent Systems: One 90 deg. elbow  
Vertical Vent Systems: Two 90 deg. elbows  
Vertical Coaxial Vent Systems: Two 90 deg. elbows  
• Air Intake Systems: Two 90 deg. elbows  
If additional elbows are desired, the maximum allowable vent length must be reduced by the amount shown in Table 5 for  
each additional elbow used. Note: Termination ttings do not need to be counted when counting additional elbows.  
Example:  
A 3” vent system is planned for a horizontal direct vented CWD165 which has the following components:  
2 ft vertical pipe  
1 90 elbow  
5 ft horizontal pipe  
1 90 elbow  
3 ft horizontal pipe  
1 45 elbow  
4 ft horizontal pipe  
1 termination elbow  
The Vent Option #1 column in Table 3a describes a horizontal direct vent system using 3” vent pipe. From this column, we  
see that a CWD165 may vent length of up to 35ft. The rst 90 elbow and the termination elbow are not considered. From  
Table 5, the equivalent length of the 3” 45 elbow is 4ft and the equivalent length of the 3” 90 degree elbow is 5.5ft. The  
maximum allowable run of straight pipe on this system is therefore:  
35ft – 4 ft – 5.5ft = 25.5ft  
Since the planned installation has only 14 ft of straight pipe, the planned vent length is acceptable.  
3) Minimum Vent / Exhaust Pipe Length - Minimum vent length is 2ft. Minimum air inlet length is 0ft.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3) Permitted Terminals for Horizontal Venting (Vent Options 1 - 5) - Table 3a shows permitted types of terminals for both the  
vent and air inlet systems. On horizontal direct vent systems using 4” air inlet pipe (Vent Options 1 and 2), the following  
Crown co-axial terminals may be used. These terminals have the advantage of requiring only one wall penetration. Part  
numbers for the Crown coaxial terminals are as follows:  
• 3” Vent - 50-003  
• 4” Vent - 50-004  
When separate vent and air intake terminals are used, or when the boiler uses indoor combustion air, the vent terminal  
is either a tee or an elbow supplied by the vent system manufacturer and equipped with a rodent screen. Vent system  
manufacturer’s part numbers for these ttings are shown in Table 4. In some cases, the elbows and tees shown in Table 4  
require separate adaptors and/or rodent screens. When this is the case, vent manufacturer part numbers for these additional  
parts are shown in Table 4 along with the termination tting.  
When Heat Fab Saf-T Vent SC is used, the Heat Fab 5300CI or 5400CI tting is used between the last piece of Saf-T  
Vent CI and the terminal. These ttings physically adapt from the CI pipe to the terminal and also provide ventilation  
openings which must remain open for the Saf-T Vent CI to maintain its clearance rating.  
Except when the Crown 50-003 or 50-004 coaxial terminals are used, the air intake tting on a horizontal direct vent  
system (Options 1 - 2) is always a 90 degree elbow with a rodent screen. This elbow is made out of the same material as the  
rest of the air inlet system (either galvanized or PVC) and is installed as shown in Figure 8a.  
4) Horizontal vent terminal location - Observe the following limitations on the vent terminal location (also see Fig 15a - d):  
• Direct exhaust installations (installations using indoor combustion air) - Exhaust terminal must be at least 4 feet below or  
4 feet horizontally from any window, door, or gravity air inlet into the building.  
• Direct vent installations – Exhaust elbow or coaxial terminal must be at least 1 foot from any door, window, or gravity  
inlet into the building.  
• Direct vent installations using termination elbows – Maintain the correct clearance and orientation between the inlet and  
exhaust elbows. The elbows must be at the same level and their center lines must be between 12 and 36 inches apart.  
• The bottom of the exhaust elbow, tee, or coaxial terminal must be at least 12” above the normal snow line. In no case  
should it be less than 12” above grade level.  
• The bottom of the exhaust elbow, tee, or coaxial terminal must be at least 7 feet above a public walkway.  
• The bottom of the exhaust elbow, tee, or coaxial terminal must be at least 3 feet above any forced air inlet located within  
10 feet.  
• A clearance of at least 4 feet horizontally or 4 feet vertically must be maintained between the exhaust terminal and gas  
meters, electric meters, regulators, and relief equipment.  
• Do not locate the terminal under decks or similar structures.  
• Top of exhaust elbow, tee, or coaxial terminal must be at least 4 feet below eves, softs, or overhangs. Overhang may not  
exceed 3 feet (Figure 15d).  
• Terminal must be at least 3 feet from an inside corner.  
• Under certain conditions, water in the ue gas may condense on the structure in areas around the terminal. If these areas  
are made of materials subject to damage by ue gas condensate, they should be protected.  
• If possible, install the terminal on a wall away from the prevailing wind. Reliable operation of this boiler cannot be  
guaranteed if the terminal is subjected to winds in excess of 40 mph.  
• The noise level in the vicinity of the terminal is approximately 65 dB (roughly the level of a normal conversation). Avoid  
positioning the terminal in areas where this might be objectionable.  
5) Horizontal air intake terminal location - Horizontal air intake terminal must be at least 12” above the normal snow line.  
6) Permitted Terminals for Vertical Venting (Vent Options 6 - 10) - Terminals used on these systems are caps. Vent  
manufacturer part numbers for these caps are shown in Table 4. When Heat Fab Saf-T Vent SC is used, the 5300CI or  
5400CI tting is used between the highest piece of Saf-T Vent CI and the cap. These ttings physically adapt from the  
CI pipe to the cap and also provide ventilation openings which must remain open for the Saf-T Vent CI to maintain its  
clearance rating.  
Vertical direct vent systems (Vent Options 6 - 8) can have combustion air obtained from either a vertical or horizontal air  
intake system. When combustion air is obtained from the roof, the air inlet terminal consists of a 180 degree elbow (or two  
90 degree elbows) with a rodent screen as shown in Figure 10. When combustion air is obtained through a horizontal vent  
system, the air inlet termination is a 90 degree elbow with a rodent screen as shown in Figure 8a.  
7) Permitted terminals for Vertical Coaxial Venting (Options 11 - 13) - When the Crown vertical coaxial vent kit is used (Vent  
Option 11), a cap compatible with the vent system is used (Figure 12, Table 4). The concentric air intake hood supplied in  
the Crown kit is the air inlet terminal (Figure 12).  
When vertical coaxial venting is done using Heat Fab Saf-T Vent SC (Options 12, 13), the vent terminal is a SC03VT or  
SC04VT terminal installed with a 5300CI or 5400CI adaptor. The openings in this adaptor are used for combustion air.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 3b: SUMMARY OF VERTICAL VENTING OPTIONS  
VENT OPTION #  
6
7
8
9
10  
(RESERVED  
FOR FUTURE  
USE)  
VERTICAL  
DIRECT  
EXHAUST  
VERTICAL  
DIRECT  
EXHAUST  
CLASSIFICATION USED IN THIS  
MANUAL  
VERTICAL  
DIRECT VENT  
VERTICAL  
DIRECT VENT  
ILLUSTRATED IN FIGURE  
10  
10  
11  
11  
VENT PIPE STRUCTURE  
PENETRATION  
ROOF  
ROOF  
ROOF  
N.A.  
ROOF  
N.A.  
AIR INTAKE PIPE STRUCTURE  
PENETRATION  
ROOF OR WALL  
ROOF OR WALL  
VENT PIPE SIZE  
3”  
4”  
4”  
4”  
3”  
4”  
AIR INTAKE PIPE SIZE  
CWD060 - CWD138  
N.A.  
47 FT  
N.A.  
47 FT  
47 FT  
47 FT  
CWD165  
CWD193  
CWD220  
CWD245  
27 FT  
17 FT  
N.R.  
47 FT  
47 FT  
47 FT  
27 FT  
17 FT  
N.R.  
47 FT  
47 FT  
47 FT  
N.R.  
47 FT  
50 FT  
50 FT  
50 FT  
50 FT  
50 FT  
N.R.  
N.A.  
N.A.  
N.A.  
N.A.  
N.A.  
47 FT  
N.A.  
N.A.  
N.A.  
N.A.  
N.A.  
CWD060 - CWD138  
CWD165  
52 FT  
32 FT  
22 FT  
N.R.  
CWD193  
CWD220  
CWD245  
N.R.  
EXHAUST TERMINAL  
BY VENT SYSTEM MANUFACTURER. SAME DIAMETER AS VENT SYSTEM. SEE TABLE 4.  
AIR INTAKE TERMINAL  
(ROOF PENETRATION)  
4” 180 ELBOW  
4” 90 ELBOW  
4” 180 ELBOW  
4” 90 ELBOW  
N.A.  
N.A.  
N.A.  
N.A.  
AIR INTAKE TERMINAL  
(WALL PENETRATION)  
VENT MATERIAL  
APPROVED VENT SYSTEM SHOWN IN TABLE 4  
GALVANIZED OR PVC N.A.  
AIR INTAKE MATERIAL  
N.A.  
“N.R” - Not recommended “N.A.” - Not applicable  
8) Vertical Vent Terminal Locations (Vent Options 6 - 13) - Observe the following limitations on the location of all vertical  
vent terminals (see Figs. 10, 11, 12, 13):  
• The lowest discharge opening on the cap must be at least 2 feet above any object located within 10 feet.  
• If outside air is used for combustion (Options 6-7, 11-13), the vertical distance between vent and air inlet terminal  
openings must be at least 12”.  
• The bottom of the air inlet terminal must be at least 12” above the normal snow accumulation that can be expected on the  
roof.  
9) Terminal offsets - Horizontal elbow or tee terminals may be offset by as much as 5 ft as shown in Figure 14. This sometimes  
helps maintain the 12” minimum clearance required above the snow line. The extra two elbows and the section of vertical  
pipe on the outside of the building must be counted when checking that the maximum vent / intake pipe length is not  
exceeded. On horizontal direct vent systems, both terminals must be offset by the same amount so that their relationship to  
one another is the same as shown in Figure 8a. When this offset is used, the horizontal section of vent pipe must be pitched  
away from the outside so that condensate cannot collect in the lower offset elbow.  
10) Wall thimbles – Wall thimbles are required where the vent pipe passes through combustible walls with less than the  
required clearance shown in Table 2 or as required by local codes. Vent manufacturer’s wall thimble part numbers are  
shown in Table 4.  
11) Condensate Traps and Pitch of Horizontal piping – All horizontal vent piping must be pitched ¼” per foot so that any  
condensate which forms in this piping will run towards either the outdoors or into a condensate trap. Vent manufacturer’s  
part numbers for suitable condensate traps are shown in Table 4.  
All vertical vent systems must include at least one condensate trap as shown in Figures 10-13. This will collect any  
condensate that forms in the vent system as well as any rain water that gets around the vent cap.  
The maximum allowable vertical run directly off of the boiler without a condensate trap is 7.5 ft (Figure 16). Install a  
condensate trap in longer vertical runs so that condensate which might form in this rst vertical section will not run into the  
boiler fan.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 10: VERTICAL NON-COAXIAL DIRECT VENT SYSTEM (VENT OPTIONS 6, 7)  
FIGURE 11: VERTICAL DIRECT EXHAUST SYSTEM (VENT OPTIONS 9, 10)  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 3c : SUMMARY OF VERTICAL COAXIAL VENTING OPTIONS  
VENT OPTION #  
11  
12  
13  
VERTICAL  
COAXIAL  
DIRECT VENT  
VERTICAL  
COAXIAL  
DIRECT VENT  
VERTICAL  
COAXIAL  
DIRECT VENT  
CLASSIFICATION USED IN THIS  
MANUAL  
VENT PIPE STRUCTURE  
PENETRATION  
ROOF  
ROOF  
ROOF  
ROOF  
ROOF  
ROOF  
AIR INTAKE PIPE STRUCTURE  
PENETRATION  
VENT PIPE SIZE  
3”  
4”  
3”  
4”  
4”  
4”  
AIR INTAKE PIPE SIZE  
(NON-COAXIAL SECTION)  
AIR INTAKE PIPE SIZE  
(COAXIAL SECTION)  
CWD060 - CWD138  
5”  
5”  
7”  
47 FT  
47 FT  
27 FT  
N.R.  
47 FT  
CWD165  
CWD193  
CWD220  
CWD245  
27 FT  
N.R.  
N.R.  
N.R.  
CONSULT  
FACTORY  
N.R.  
N.R.  
30 FT OR AS  
LIMITED BY MAX  
VENT LENGTH,  
WHICHEVER IS  
LESS  
AS LIMITED  
BY MAX VENT  
LENGTH  
MAXIMUM LENGTH  
COAXIAL SECTION  
CONSULT  
FACTORY  
CWD060 - CWD138  
CWD165  
52 FT  
32 FT  
N.R.  
50 FT  
32 FT  
N.R.  
50 FT  
CWD193  
CONSULT  
FACTORY  
CWD220  
N.R.  
N.R.  
CWD245  
N.R.  
N.R.  
BY VENT  
SYSTEM  
MANUFAC-  
HEAT FAB  
#SC03RC  
HEAT FAB  
#SC04RC  
EXHAUST TERMINAL  
AIR INTAKE TERMINAL  
TURER. SAME  
DIAMETER AS  
VENT SYSTEM.  
SEE TABLE 4.  
SUPPLIED WITH  
CROWN #500005  
COAXIAL VENT  
KIT  
HEAT FAB  
#SC03VT  
HEAT FAB  
#SC04VT  
5” “B” VENT  
TEE + SUPPORT  
SUPPLIED WITH  
CROWN #500005  
COAXIAL VENT  
KIT  
ADAPTOR FROM NON-COAXIAL  
TO COAXIAL SECTIONS  
HEAT FAB  
#SC03TAD4  
HEAT FAB  
#SC04TAD4  
APPROVED  
VENT SYSTEM  
SHOWN IN  
TABLE 4  
VENT MATERIAL  
(NON-COAXIAL SECTION)  
HEAT FAB  
SAF-T VENT  
HEAT FAB  
SAF-T VENT  
APPROVED  
VENT SYSTEM  
SHOWN IN  
TABLE 4  
VENT MATERIAL  
(COAXIAL SECTION)  
HEAT FAB  
SAF-T VENT SC  
HEAT FAB  
SAF-T VENT SC  
AIR INTAKE MATERIAL  
(NON-COAXIAL SECTION)  
GALVANIZED OR PVC  
AIR INTAKE MATERIAL  
(COAXIAL SECTION)  
5” TYPE “B”  
VENT  
HEAT FAB  
SAF-T VENT SC  
HEAT FAB  
SAF-T VENT SC  
“N.R” - Not recommended “N.A.” - Not applicable  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 12: VERTICAL COAXIAL DIRECT VENT USING CROWN #500005 VENT KIT (VENT OPTION 11)  
FIGURE 13: VERTICAL COAXIAL DIRECT VENT USING HEAT FAB SAF-T VENT SC (VENT OPTIONS 12, 13)  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 4: PERMISSIBLE VENT SYSTEMS AND PRINCIPLE VENT COMPONENTS  
CONDENSATE  
TRAP  
WALL  
THIMBLES  
HORIZONTAL  
TERMINATION  
VERTICAL  
TERMINATION  
MANUFACTURER VENT SYSTEM SIZE  
7393GC  
7393GCS  
5391CI  
ELBOW: 7314TERM  
TEE: 7390TEE  
9321  
(NOTE 3)  
3
5300CI  
5400CI  
SAF-T VENT  
EZ SEAL  
7493GC  
7493GCS  
5491CI  
9421  
(NOTE 3)  
ELBOW: 7414TERM  
TEE: 7490TEE  
4
HEAT FAB  
ELBOW (NOTE 5):  
SC03HT + 7314TERM  
TEE (NOTE 5):  
5300CI + SC03VT  
(NOTE 6)  
SC03DRN  
(NOTE 3)  
SC03FS  
SC03FSA  
3
SC03HT + 7390TEE  
SAF-T VENT SC  
4
ELBOW (NOTE 5):  
SC04HT + 7414TERM  
TEE (NOTE 5):  
5400CI  
+ SC04VT  
(NOTE 6)  
SC04DRN  
(NOTE 3)  
SC04FS  
SC04FSA  
SC04HT + 7490TEE  
ELBOW: FSELB9003 + FSBS3  
TEE: FSTT3  
3
FSHDT3  
FSWT3  
FSWT4  
FSRC3  
FSRC4  
FASNSEAL  
4
FSHDT4  
OR FSCD4  
(NOTE 4)  
ELBOW: FSELB9004 + FSBS4  
TEE: FSTT4  
PROTECH  
SYSTEMS  
ELBOW: FSA-SWDW3  
+ FSELB9003 + FSBS3  
TEE: FSA-SWDW3 + FSTT3  
W2-T3  
+W2-DF3  
INC.  
3
W2-WT3  
W2-RC3  
FASNSEAL W2  
ELBOW: FSA-DWSW4  
+ FSELB9004 + FSBS4  
TEE: FSA-SWDW4 + FSTT4  
W2-T4  
+ W2-DF4  
4
3
4
W2-WT4  
W2-RC4  
ELBOW: 2SVSTEX0390  
TEE: 2SVSTTF03  
SVEDWCF03  
SVEDWCF04  
2SVSWTEF03  
2SVSWTEF04  
2SVSRCF03  
2SVSRCF04  
SVE  
SERIES III  
(“Z-VENT III”)  
Z-FLEX  
ELBOW:  
2SVEEWCF0490 + 2SVSTPF  
TEE: 2SVSTTF04  
ELBOW: CGSW90LTM(3”)  
TEE: CGSWTTM(3”)  
3
4
CGSWDS(3”)  
CGSWDS(4”)  
CGSWWPK(3”)  
CGSWWPK(4”)  
CGSWC(3”)  
CGSWC(4”)  
METAL-FAB  
CORR/GUARD  
ELBOW: CGSW90LTM(4”)  
TEE: CGSWTTM(4”)  
NOTES:  
1) See vent system manufacturer’s literature for other part numbers that are required such as straight pipe, elbows, restops and  
vent supports.  
2) In addition to terminals shown, Crown coaxial terminals may be used in some cases. See Table 3 for applications and Crown  
part numbers.  
3) All Heat Fab condensate traps shown may be installed in vertical or horizontal run.  
4) Protech FSCD4 condensate trap may be installed in a vertical or horizontal run. All other Protech traps must be installed in a  
horizontal run only.  
5) Heat Fab Saf-T Vent SC may not be used for horizontal coaxial venting - a separate air inlet pipe must be provided for hori-  
zontal direct vent systems. SC03HT or SC04HT adapters are used to adapt from SC pipe to terminal. Use of SC pipe in horizon-  
tal systems does allow for reduced clearances to combustibles in some applications. See Table 2.  
6) Heat Fab SC03VT or SC04VT adapters are required on any vertical vent system using Saf-T Vent SC even when combustion  
air is obtained through a separate pipe or from the boiler room.  
7) Metal-Fab CGSWDS condensate traps may only be installed in a horizontal run.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12) Vertical and horizontal sections of piping must be properly supported. See vent system manufacturer’s instructions for more  
information.  
13) Non-coaxial vent piping must be accessible for periodic inspection.  
14) Fire stops and wall thimbles – Use re stops where required by code or by the vent system manufacturer. Consult vent  
system manufacturer’s literature for information on suitable re stops.  
15) Supports - Vertical and horizontal sections of vent pipe must be properly supported. See the Vent System assembly section  
of this manual for more information.  
B. Removing an Existing Boiler From a Common Chimney  
Read this only if the CWD boiler is replacing an existing boiler that is being removed from a common chimney. This  
section does not apply to the installation of a CWD boiler.  
In some cases, when an existing boiler is removed from a common chimney, the common venting system may be too  
large for the remaining appliances. At the time of removal of an existing boiler, the following steps shall be followed with  
each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining  
connected to the common venting system are not in operation.  
(a) Seal any unused openings in the common venting system.  
(b) Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction,  
leakage, corrosion and other deciencies which could cause an unsafe condition.  
(c) Insofar as practical, close all building doors and windows and all doors between the space in which all the appliances  
remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and  
any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom  
exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close replace dampers.  
(d) Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so the appliance will  
operate continuously.  
(e) Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the ame of a match or  
candle, or smoke from a cigarette, cigar, or pipe.  
(f) After it has been determined that each appliance remaining connected to the common venting system properly vents when  
tested as outlined above, return doors, windows, exhaust fans, replace dampers and any other gas-burning appliances to  
their previous condition of use.  
(g) Any improper operation of the common venting system should be corrected so the installation conforms with the National  
Fuel Gas Code, ANSI Z223.1. When resizing any portion of the common venting system, the common venting system  
should be resized to approach the minimum size as determined using the appropriate tables in Part 11 of the National Fuel  
Gas Code, ANSI Z223.1.  
WARNING  
NEVER COMMON VENT A CWD BOILER WITH OTHER APPLIANCES  
TABLE 5a: VENT FITTING  
EQUIVALENT LENGTH  
TABLE 5b: AIR INTAKE FITTING  
EQUIVALENT LENGTH  
VENT FITTING  
EQUIVALENT  
LENGTH (ft)  
INTAKE FITTING  
EQUIVALENT  
LENGTH (ft)  
3” 90 ELBOW  
3” 45 ELBOW  
5.5  
4.0  
4” 90 ELBOW  
4” 45 ELBOW  
8.0  
4.5  
HEAT FAB SC03E90  
5.5  
HEAT FAB SC03E90  
(3” COAXIAL 90 ELBOW)  
(3” COAXIAL 90 ELBOW)  
HEAT FAB SC03E45  
4.0  
HEAT FAB SC03E45  
(3” COAXIAL 45 ELBOW)  
(3” COAXIAL 45 ELBOW)  
CONSULT CROWN  
4” 90 ELBOW  
4” 45 ELBOW  
8.0  
4.5  
8.0  
HEAT FAB SC04E90  
(4” COAXIAL 90 ELBOW)  
HEAT FAB SC04E45  
(4” COAXIAL 45 ELBOW)  
HEAT FAB SC04E90  
(4” COAXIAL 90 ELBOW)  
HEAT FAB SC04E45  
4.5  
(4” COAXIAL 45 ELBOW  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 14: HORIZONTAL TERMINAL OFFSETS  
FIGURE 15a: LOCATION OF DIRECT VENT TERMINAL RELATIVE TO WINDOWS, DOORS, GRADE  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 15b: LOCATION OF DIRECT EXHAUST TERMINAL RELATIVE TO WINDOWS, DOORS, GRADE  
FIGURE 15c: LOCATION OF VENT TERMINAL RELATIVE TO METERS AND FORCED AIR INLETS  
FIGURE 15d: POSITIONING VENT TERMINAL UNDER OVERHANGS  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 16: USE OF CONDENSATE TRAPS  
C. Vent / Intake System Assembly  
1) General Assembly Notes:  
a) Where the use of “silicone” is called for in the following instructions, use GE RTV 106 for the vent collar and coaxial  
terminal. Air inlet piping sections are sealed with any general-purpose silicone sealant such as GE RTV102. PVC air inlet  
piping sections are connected with PVC cement.  
b) Longitudinal welded seams should not be placed at the bottom of horizontal sections of exhaust pipe.  
c) Do not drill holes in vent pipe.  
d) Do not attempt to mix vent components of different vent system manufacturers.  
e) In some cases, there are differences between the vent system installation instructions in this manual and those in the  
vent system manufacturer’s manual. Where such differences exist, this manual takes precedence over the vent system  
manufacturer’s manual.  
CAUTION  
Vent systems made by Heat Fab, Protech, and Z-Flex rely on gaskets for proper sealing. When these vent systems are  
used, take the following precautions:  
• Make sure that gasket is in position and undamaged in the female end of the pipe.  
• Make sure that both the male and female pipes are free of damage prior to assembly.  
• Only cut vent pipe as permitted by the vent manufacturer in accordance with their instructions. When pipe is cut,  
cut end must be square and carefully deburred prior to assembly.  
2) Vent Collar Installation – The vent collar is shipped loose in the accessory bag along with two collar gaskets, the outlet  
orice, and four 10-32 mounting screws. Verify that the 6 digit part number model number marked on the outlet exhaust  
orice matches that shown in Table 6. Mount the collar and orice as shown in Figure 17. If desired, the rst piece of  
exhaust pipe can be connected to the collar before mounting the collar on the boiler.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 6: FAN OUTLET  
ORIFICE  
ORIFICE  
BOILER MODEL  
PART #  
CWD060  
CWD083  
CWD110  
CWD138  
CWD165  
CWD193  
CWD220  
CWD245  
620133  
650136  
620135  
620136  
620137  
620138  
620139  
650138  
FIGURE 17: INSTALLATION OF FAN OUTLET ORIFICE  
3) Optional Coaxial Terminal Installation – If the optional coaxial terminal is used, it should be installed in the wall before vent  
assembly is started. Install the terminal in accordance with the following procedure (Figures 18a & 18b):  
NOTE  
• Coaxial portion of inside terminal section may be installed in direct contact with combustible construction.  
• Maximum wall thickness through which this terminal can be installed is 10”  
a) Position the wall face plate on the outside wall in the desired terminal location. Verify that this location will permit the  
terminal, and connected venting, to clear any obstructions on the inside of the wall with the appropriate clearances. Mark  
the location of the round opening on the wall.  
b) For 3” terminals, cut a 5 ¼” Diameter hole through the wall at this location. For 4” terminals, cut a 7 1/4” opening.  
c) Attach the mounting plate to the outside wall with suitable fasteners.  
d) Attach the intake terminal to the straight coaxial section. To do this, clean the male and female ends of the inner pipes  
with an alcohol pad. Lubricate the gasket in the female end of the straight section with a package of the silicone lubricant  
provided and then push the intake terminal rmly onto the straight section until the intake terminal makes contact with  
the bead on the straight section. Secure the two ttings together with the self-drilling screws provided. Use a low torque  
setting to install these screws so as not to strip out the holes.  
e) Pass the assembled intake terminal and straight section through the wall from the outside. Bend the four Tabs in the wall  
face plate towards the outside when doing this. Do not attach the pipe to the plate yet.  
f) Adjust the position of the terminal in the wall so that the edge of the intake skirt is 2-3” from the wall plate (Figure 18b).  
Also verify that the terminal is pitched in the same direction as the rest of the vent system.  
g) Attach the intake/straight section to the wall face plate using the self drilling screws provided.  
h) Loosen the hose clamp on the end of the exhaust terminal. Mount the exhaust terminal onto the intake terminal with the  
“V” horizontal (ue gas openings on top and bottom) as shown in Figure 18b. Slip the hose clamp over the “ngers” on  
the intake terminal and tighten the clamp.  
i) Seal all exposed exterior joints, including the joint between the wall face plate and the wall and between the wall face  
plate and the straight section with an exterior grade silicone sealant.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 18a: CROWN COAXIAL TERMINAL EXPLODED VIEW  
FIGURE 18b: CROWN COAXIAL TERMINALASSEMBLY  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
j) Attach the intake tee to the end of the straight section protruding from the inside wall. Use the procedure described in (d)  
to clean and assemble these parts.  
k) If the inside terminal section is not supported by the wall through which it passes, install additional supports or bracing  
to support the terminal. Bracing in contact with the coaxial section of the terminal may be combustible.  
4) Assembly of Metal-Fab Corr/Guard Vent System:  
a) Corr/Guard General Notes:  
• Do not cut Corr/Guard vent components.  
• Refer to Corr/Guard installation instructions for proper methods of support.  
• Orient Corr/Guard components so that the males ends of all ttings point in the direction of the boiler.  
b) Start assembly of the vent system at the boiler. Remove the hose clamp shipped on the BWC vent collar. Bend the three  
hose clamp tabs on this collar outward slightly.  
c) Clean the exterior of the male end of the rst piece of pipe and the inside of the vent collar on the boiler. Remove dirt,  
grease, and moisture from the surfaces to be sealed. Dry surfaces or allow to dry thoroughly.  
d) On the male end of the pipe, apply a ¼” wide bead of silicone approximately 1/2” from the end of the pipe (Fig 7.47).  
e) Insert the male end of the pipe into the boiler vent collar until it bottoms out.  
f) Apply an additional bead of silicone over the outside of the joint and smooth out.  
g) Replace and tighten the clamp on the vent collar.  
h) Assemble remaining Corr/Guard components in accordance with the Corr/Guard installation instructions.  
i) Allow the silicone to cure per the silicone manufacturer’s instructions before operating the boiler.  
Note: To join Corr/Guard to a Crown coaxial terminal, leave the Corr/Guard gasket in place. Apply a ¼” bead of silicone  
to the terminal connection about ¼” from its end. Slip the Corr/Guard female end over the terminal end so that there is  
an overlap of approximatley 1 ¾ inches. Apply and smooth silicone over the outside of the joint including the tabs in the  
female end of the Corr/Guard pipe. Tighten the terminal hose clamp to mechanically lock the pipe onto the terminal.  
FIGURE 19: CORR/GUARD CONNECTION TO VENT COLLAR  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5) Assembly of Z-Flex Z-Vent III:  
a) General Notes:  
• Non-expanded ends of SVE Series III piping sections may be cut using aviation snips or a 24 thread per inch hacksaw.  
File or sand the cut end smooth before assembling. Expanded ends may be cut to adapt the SVE series III to the vent  
collar or Crown coaxial terminal. See the following instructions.  
• Support horizontal piping sections at intervals of 48” or less.  
Vertical venting systems must be supported by at least one Z-Flex re stop. An additional vertical support is required after  
any offset and as required by the Z-Vent III installation instructions.  
b) Start assembly of the vent system at the boiler. Remove the hose clamp shipped on the CWD vent collar. Bend the three  
hose clamp tabs on this collar outward slightly.  
c) Clean the exterior of the male end of the rst piece of pipe and the inside of the vent collar on the boiler. Remove dirt,  
grease, and moisture from the surfaces to be sealed. Dry surfaces or allow to dry thoroughly.  
d) On the male end of the pipe, apply a ¼” wide bead of high temperature silicone approximately ½ inch from the male end  
of the pipe. Apply ¼” beads of silicone along both sides of the longitudinal seam (Fig. 20).  
e) Insert the male end of the pipe into the boiler vent collar until it bottoms out.  
f) Apply an additional bead of silicone over the outside of the joint and smooth out. Also apply silicone over the seams in  
the collar (Fig 20).  
g) Replace and tighten the clamp on the vent collar.  
h) The female end of each Z-Vent III component has a silicone sealing gasket. Examine all vent components to insure that  
the gasket integrity has remained during shipping. Gaskets must be in the proper position or ue gas could leak resulting  
in carbon monoxide poisoning.  
i) Align the second piece of pipe with the rst and push them together as far as they will go, but not less than 1 3/4”.  
j) Tighten gear clamp to a minimum torque of 40 in-lbs and a maximum of 50 in-lbs.  
k) Repeat Steps (h) – (j) for the remaining Z-Vent III components. If a termination elbow is used, use this procedure to  
complete the vent system.  
l) If a termination elbow or tee is used, a locking band or gear clamp must be used at either side of the wall penetration to  
prevent shifting of the vent system in and out of the wall. This applies to both combustible and non-combustible walls.  
m) To join Z-Vent III to a Crown coaxial terminal, a male end must be present at the end of the piping to be joined to the  
terminal. It will therefore be necessary to cut off the expanded end of the pipe before it can be joined to the terminal.  
This male end of the pipe must be inserted into the terminal connection with at least a 1” overlap. It may be necessary to  
crimp the end of the vent pipe before it can be inserted into the terminal. Apply silicone to the male end of the pipe as in  
(d) above, insert into the terminal, and apply an additional bead of silicone over the outside of the joint. Smooth out the  
excess silicone and tighten the hose clamp on the terminal.  
n) Allow the silicone to cure per the silicone manufacturer’s instructions before operating the boiler.  
FIGURE 20: Z-VENT III CONNECTION TO VENT COLLAR  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6) Assembly of Heat Fab Saf-T Vent EZ Seal:  
a) Saf-T Vent General Notes:  
These instructions cover the installation of Saf-T Vent EZ Seal. Saf-T Vent EZ Seal piping has integral gaskets installed in  
the female ends of the pipe which seal the joints.  
• In general, Saf-T Vent pipe sections may not be cut. Exceptions to this are the Saf-T Vent slip connector and connections  
to the boiler vent collar and Crown coaxial terminal. In these cases, use a sharp pair of aviation snips, an abrasive cut-off,  
or a plasma cutter. See the Saf-T Vent instructions for information on cutting the slip connector.  
• Orient Saf-T Vent components so that the arrows on the piping labels are in the direction of ue gas ow.  
• Support horizontal piping sections at intervals of 6 feet or less.  
Vertical venting systems must be supported by at least one Heat Fab support. An additional vertical support is required  
after any offset.  
b) Connection to Boiler – Start assembly of the vent system at the boiler. Remove the hose clamp shipped on the CWD vent  
collar. Bend the three hose clamp tabs on this collar outward slightly. Cut the male “spigot” off of the rst piece of pipe  
(Fig 21). If necessary, crimp the cut end of the pipe so that it can be inserted at least 1” into the collar. Clean the exterior  
of the male end of the rst piece of pipe and the inside of the vent collar on the boiler with an alcohol pad. On the male  
end of the pipe, apply a ¼” wide bead of high temperature silicone approximately ½ inch from the male end of the pipe.  
Also apply a ¼” bead of silicone along the rst 2 ½” of the longitudinal weld. Insert the male end of the pipe into the  
boiler vent collar until it bottoms out. Apply an additional bead of silicone over the outside of the joint and smooth out  
(Fig 21). Apply silicone over the seams in the vent collar. Replace and tighten the clamp on the vent collar.  
c) Assembly of Saf-T Vent EZ Seal Vent Components - Clean the male end of the next piece of pipe with an alcohol pad and  
make sure that it is free of burrs. Check the female end of the rst piece of pipe to make sure that the gasket is in place  
and is undamaged. Using a slight twisting motion, insert the male end of the second tting into the female end of the rst  
tting, taking care not to dislodge or cut the factory gasket. In extremely arid conditions, it may be easier to assemble  
these ttings if the gasket is moistened with water prior to assembly. Bend the locking tabs over the locking ring on the  
adjacent piece of pipe. Repeat these steps for the remaining Saf-T-Vent components. If a termination elbow is used, use  
this procedure to complete the exhaust system.  
d) Connection of Saf-T Vent to Crown coaxial terminal - Cut the locking tabs off of the female end of the Saf-T Vent  
pipe to be joined to the co-axial terminal. Apply a ¼” bead of silicone around the terminal connection about ¼” from  
the end. Slip the Saf-T Vent pipe over the terminal and apply a second bead of silicone over the joint. Silicone must be  
applied even though there is a gasket on the female end of the pipe. Smooth the excess silicone over the joint, making  
sure that there are no visible voids in the silicone. Tighten the terminal clamp. Allow the silicone to cure per the silicone  
FIGURE 21: SAF-T VENT EZSEAL CONNECTION TO VENT COLLAR  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
manufacturer’s instructions before operating the boiler.  
7) Assembly of Heat Fab Saf-T Vent SC - On CWD Boiler installations where Saf-T Vent SC is used, some Saf-T Vent EZ  
Seal (single wall pipe) will always be required between the boiler and the Saf-T Vent SC. Install this pipe as described  
above. On all systems except vertical coaxial systems (Options 12, 13), the following Heat Fab adapters will be needed to  
adapt from Saf-T Vent EZ Seal to Saf-T Vent SC:  
Vent Size  
3”  
4”  
Heat Fab Part Number  
SC03ADEZ  
SC04ADEZ  
On vertical coaxial vent systems employing Saf-T Vent SC, the transition from Saf-T Vent to Saf-T Vent SC is made with  
one of the following Air Intake Tees:  
Vent Size  
3”  
4”  
Heat Fab Part Number  
SC03TAD4  
SC04TAD4  
Assemble the Saf-T Vent EZ Seal to the boiler and the adapter as described in (6) above. Proceed as follows to assemble the  
Saf-T Vent SC:  
a) Clean both ends of the inner pipes to be joined with an alcohol pad. This will remove any foreign matter which may effect  
the integrity of the seal. Insert the male end of the rst piece of pipe into the adaptor. In extremely dry conditions it may  
be helpful to moisten the gasket with clean water prior to assembly.  
b) Push the rst Saf-T Vent SC section into the adaptor until the outer jacket has made contact with the snap ring located  
inside the female end of the adaptor. When fully assembled the outer female end will overlap the male end by 1”.  
c) Use the three self tapping screws provided with the vent to attach the rst piece of pipe to the adapter. No pre drilling is  
required. If using a variable torque screw gun, use the low torque setting to install the screws so as not to strip out the  
holes. If a hole does become stripped due to over tightening, a larger (1/2” long max.) screw or short pop rivet may be  
used.  
d) Seal all the joints in the outer jacket with foil tape or exterior grade silicone sealant.  
e) Repeat steps (a - d) to assemble the remaining sections of Saf-T Vent SC.  
f) Support the Saf-T Vent SC as called for in Heat Fab’s installation instructions. Also make sure that re stops are provided  
as called for in Heat Fab’s instructions and local codes.  
g) After the Saf-T Vent SC exits the building, one of the following adaptors will be needed to install the terminal:  
Vent Size  
3”  
4”  
Heat Fab Part Number  
5300CI  
5400CI  
On vertical coaxial vent systems (Vent Options 12, 13) this adapter also acts as the combustion air intake terminal. In other  
installations, the openings in this adapter provide ventilation between the inner and outer walls.  
FIGURE 22: FASNSEAL CONNECTION TO VENT COLLAR  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8) Assembly of Protech FasNSeal  
a) FasNSeal General Notes:  
• Do not cut 4” FasNSeal pipe. Consult FasNSeal instructions for method of cutting other 3” pipe.  
• Orient FasNSeal vent components so that the arrows on the piping labels are in the direction of ue gas ow.  
• Support horizontal piping sections at intervals of 6 feet or less.  
Vertical venting systems must be supported by at least one FasNSeal support. An additional vertical support is required  
after any offset.  
a) Remove the hose clamp shipped on the CWD vent collar. Bend the three hose clamp tabs on this collar outward slightly.  
Clean the exterior of the male end of the rst piece of pipe and the inside of the vent collar on the boiler. Remove dirt,  
grease, and moisture from the surfaces to be sealed. Dry surfaces or allow to dry thoroughly. On the male end of the pipe,  
apply a ¼” wide bead of high temperature silicone approximately 1/4 inch from the male end of the pipe. Insert the male  
end of the pipe into the boiler vent collar until it bottoms out. Apply an additional bead of silicone over the outside of the  
joint and the seams on the vent collar and smooth out (Fig 22). Replace and tighten the clamp on the vent collar.  
b) All other joints in the FasNSeal venting system rely on a gasket in the female end of the pipe for a proper seal.  
c) Align the longitudinal seam of both pipes. Insert the male end of the second pipe into the female end of the rst pipe until  
the bead on the male end contacts the are on the female end (Fig. 17b).  
d) Tighten the locking band with a nut driver.  
e) Repeat (c) and (d) for the remaining FasNSeal components. If a termination elbow is used, use this procedure to complete  
the exhaust system.  
f) To join FasNSeal to a Crown coaxial terminal, remove the hose clamp from the female FasNSeal end to be joined to the  
terminal. Leave the FasNSeal gasket in place. Apply a ¼” bead of silicone to the terminal connection about ¼” from its  
end. Slip the FasNSeal female end over the terminal end so that there is an overlap of 1 ¾ inches. Apply and smooth  
silicone over the outside of the joint including the rectangular hose clamp opening in the FasNSeal pipe. Tighten the  
terminal hose clamp to mechanically lock the pipe onto the terminal.  
g) Allow the silicone to cure per the silicone manufacturer’s instructions before operating the boiler.  
9) Assembly of Protech FasNSeal W2 - On CWD Boiler installations where Protech FasNSeal W2 is used, some Protech  
FasNSeal (single wall pipe) will always be required between the boiler and the FasNSeal W2. Install this pipe as described  
above. On all systems, the following components will be needed to adapt from Protech FasNSeal to FasNSeal W2:  
Vent Size  
Protech Part Number  
FSA-SWDW3  
3”  
4”  
FAS-SWDW4  
Follow the joint connection instructions provided with the FasNseal W2. In vertical vent systems, terminate the vent system  
with the cap called for FasNSeal W2 in Table 4. In horizontal vent systems one of the following adapters will be required  
between the FasNSeal W2 and the terminal:  
Vent Size  
3”  
4”  
Protech Part Number  
FSA-DWSW3  
FAS-DWSW4  
10) Assembly of the air intake system:  
a) Assemble the air intake system using either galvanized or PVC pipe.  
b) If PVC piping is used, use PVC cement to assemble the PVC intake system components.  
c) If galvanized piping is used, use at least two sheet metal screws per joint. Seal the outside of all joints.  
d) A 4” galvanized smoke pipe will t inside the inlet collar on the CWD boiler. Depending upon the exact OD of the  
pipe used, it may be necessary to crimp this pipe. Secure with a single #10 sheet metal screw through the hole in the  
inlet collar and seal the outside of the joint with silicone. If PVC is used for the intake system, use a short piece of 4”  
galvanized pipe to connect the PVC to the boiler. Silicone the outside of the joint between the PVC and galvanized pipe.  
e) Either PVC or galvanized pipe will t over the combustion air connection on the Crown coaxial terminal. Secure the  
pipe to the terminal with at least two #10 sheet metal screws. Seal the outside of the joint between the inlet pipe and the  
coaxial terminal.  
f) Two 90-degree elbows may be used to make the 180-degree air intake termination elbow used on vertical direct vent  
installations.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11) Assembly of Vertical Coaxial Vent System Using Crown #500005 Coaxial Vent Kit (Vent Option #11)  
a) Start by installing the “B” vent piping. Install and assemble this piping in accordance with the “B” vent manufacturer’s  
instructions. Seal the joints between sections of “B” vent with GE RTV 106 or Dow 732 RTV sealant. Consult the “B”  
vent manufacturer’s instructions for the clearance to combustibles (typically 1”) as well as for re stop and support  
requirements.  
Install a 5” “B” vent Tee on the bottom of the run of “B” vent as shown in Figure 12. Extend the run of “B” vent far  
enough above the roof so that the bottom of the air intake hood will be at least one foot above the normal snow line that  
can be expected on the roof. Seal the roof penetration with a “B” vent roof ashing and storm collar in accordance with  
the “B” vent manufacturer’s instructions.  
b) Assemble the vent piping that is to be run inside the “B” vent and drop it through the “B” vent. Join and seal the vent  
piping in accordance with the instructions 4, 5,6 or 8 above. Use the longest sections of vent piping possible so as to  
minimize the number of joints inside the “B” vent. Temporarily support the vertical section of vent pipe from underneath  
so that the top of the vent pipe is at the correct height (Figure 12).  
c) Slip the Crown concentric air intake hood over the vent pipe and seat it on the “B” vent. Secure the concentric air intake  
hood to the “B” vent with at least three sheet metal screws. Install a storm collar compatible with the vent system over  
the vent pipe. Secure and seal it in accordance with the vent manufacturer’s instructions. Note: this collar provides a  
watertight seal between the vent piping and the concentric air intake hood and also supports the vent piping. Once the  
storm collar is installed, remove the temporary vent support. Install a compatible rain cap on the top of the vent system  
(Table 4).  
d) Slip the Crown vent support over the vent pipe protruding from the bottom of the “B” vent. Orient the vent support so  
that it will be possible to tighten the gear clamp by reaching through the side opening in the “B” vent Tee (Figure 23).  
Attach the vent support to the “B” vent Tee with at least three sheet metal screws. Tighten the gear clamp. Seal all joints  
in between the vent support, the vent pipe, and the “B” vent.  
e) Install the vent piping between the boiler and the vertical section of “B” vent already installed. Observe the clearance and  
support requirements in the installation manual.  
f) Install a 5 x 4 single wall reducer in the side connection of the “B” vent Tee. Install 4” galvanized or PVC piping between  
this reducer and the combustion air intake on the boiler. Seal all joints in the air intake piping.  
12) Condensate Traps:  
a) Trap should have the basic conguration shown in Figure 24. All tubing is 3/8 I.D.  
b) All drain tubing must be acid resistant.  
c) At least the rst 6 inches of tubing must be silicone with a 300F temperature rating.  
d) Pipe condensate to a drain or other suitable location. Make sure that condensate disposal method is in accordance with  
local regulations. Ensure condensate is not subjected to freezing temperatures.  
13) Rodent Screens:  
a) A rodent screen is provided with the CWD boiler. On direct exhaust boilers, this screen is installed in the air inlet collar  
on the boiler and held in place with screws or RTV sealant.  
b) The Crown coaxial terminal has integral inlet and exhaust rodent screens. The rodent screen supplied with the boiler is not  
used when the boiler is installed with the coaxial terminal.  
c) In horizontal direct vent installations using termination elbows or tees, the rodent screen provided is mounted in the air  
inlet elbow. A second screen is required for the exhaust elbow. This second screen can be any one of the following items:  
A rodent screen provided by the vent system manufacturer.  
A second Crown rodent screen (Crown #60-601).  
A rodent screen made of stainless steel screen having a ½” (2 x 2) or greater mesh.  
d) In vertical direct vent or direct exhaust systems, no rodent screen is required on the exhaust terminal. The rodent screen  
is installed either on the 180-degree inlet elbow (direct vent installations) or on the boiler inlet collar (direct exhaust  
installations).  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 23: INSTALLATION OF VENT SUPPORT PROVIDED IN CROWN #500005 VERT. COAXIAL VENT KIT  
FIGURE 24: CONDENSATE TRAP/DRAIN DETAIL  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VII Gas Piping  
Gas piping to the boiler must be sized to deliver adequate gas for the boiler to re at the nameplate input at a line pressure  
between the minimum and maximum values shown on the rating plate. For more information on gas line sizing, consult the  
utility or the National Fuel Gas Code.  
Figure 25 shows typical gas piping connections to the CWD boiler. A sediment trap must be installed upstream of all gas  
controls. Install a manual shutoff valve outside the jacket and ground joint union as shown.  
The boiler and its gas connection must be leak tested before placing the boiler in operation. When doing this, the boiler and  
its individual shut-off must be disconnected from the rest of the system during any pressure testing of that system at pressures in  
excess of ½ psi. When pressure testing the gas system at pressures of ½ psi or less, isolate the boiler from the gas supply system  
by closing its individual manual shut-off valve.  
FIGURE 25: GAS CONNECTION TO BOILER  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VIII System Piping  
CAUTION  
• Install boiler so that the gas ignition system components are protected from water (dripping, spraying, rain, etc)  
during appliance operation and service (circulator replacement, etc).  
• Operation of this boiler with continuous return temperatures below 120F can cause severe heat exchanger corrosion  
damage.  
• Operation of this boiler in a system having signicant amounts of dissolved oxygen can cause severe heat exchanger  
corrosion damage.  
• Do not use toxic additives, such as automotive antifreeze, in a hydronic system.  
A. Standard Piping  
Figure 26 shows typical boiler system connections on a single zone system. Additional information on hydronic system  
design may be found in Installation of Residential Hydronic Systems (Pub. #200) published by the Hydronics Institute in  
Berkely Heights, NJ. The components in this system and their purposes are as follows:  
1) Relief valve (Required) – Install the relief valve in the 3/4” tapping on the left side of the boiler as shown in Figure 1. The  
relief valve shipped with the boiler is set to open at 30 psi. This valve may be replaced with one having a setting of up to  
the Maximum Allowable Working Pressure (MAWP) shown on the rating plate. If the valve is replaced, the replacement  
must have a relief capacity in excess of the Minimum Relief Valve Capacity shown on the rating plate.  
Pipe the discharge of the relief valve to a location where water or steam will not create a hazard or cause property damage  
if the valve opens. The end of the discharge pipe must terminate in an unthreaded pipe. If the relief valve discharge is not  
piped to a drain, it must terminate at least 6 inches above the oor. Do not run relief valve discharge piping through an area  
that is prone to freezing. The termination of the relief valve discharge piping must be in an area where it is not likely to  
become plugged by debris.  
DANGER  
Pipe relief valve discharge to a safe location.  
Do not install a valve in the relief valve discharge line.  
Do not move relief valve from factory location.  
Do not plug relief valve discharge.  
2) Circulator (Required) – Although the circulator is shipped on the boiler return, it can be installed on the boiler supply. If the  
circulator is moved to the supply it should be positioned just downstream of the expansion tank as shown in Figure 26.  
3) Expansion Tank (Required) – If this boiler is replacing an existing boiler with no other changes in the system, the old  
expansion tank can generally be reused. If the expansion tank must be replaced, consult the expansion tank manufacturer’s  
literature for proper sizing.  
4) Fill Valve (Required) – Either a manual or automatic ll valve may be used. The ideal location for the ll is at the expansion  
tank.  
5) Automatic Air Vent (Required) – At least one automatic air vent is required. Manual vents will usually be required in other  
parts of the system to remove air during initial ll.  
6) Low Water Cut-Off (Required in some situations) – A low water cut-off is required when the boiler is installed above  
radiation. In addition, some codes, such as ASME CSD-1, require low water cut-offs. Codes may also require that this low  
water cut-off have a manual reset function. The low water cut-off may be a oat type or probe type but must be designed  
for use in a hot-water system. The low water cut-off should be piped into the boiler supply just above the boiler with no  
intervening valve between it and the boiler.  
Use a low water cut-off that breaks the 120 VAC supply to the boiler. Do not attempt to connect a 24-volt low water  
cut-off into the boiler factory wiring.  
7) Manual Reset High Limit (Required by some codes) – This control is required by ASME CSD-1 and some other codes.  
Install the high limit in the boiler supply piping just beyond the boiler with no intervening valves. Set manual reset high  
limit as far above the operating limit setting as possible, but not over 240F. Wire the control to break the 120 VAC electrical  
supply to the boiler.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8) Flow control valve (Required under some conditions) – The ow control valve prevents ow through the system unless the  
circulator is operating. A ow control valve may be necessary on converted gravity systems to prevent gravity circulation.  
Flow control valves are also used to prevent “ghost ows” in circulator zone systems through zones that are not calling for  
heat.  
9) Isolation Valves (Optional) – Isolation valves are useful if the boiler must be drained, as they will eliminate having to drain  
and rell the entire system.  
10) Drain Valve – The drain valve is shipped in the boiler parts bag. Install it in the location shown in Figure 1.  
B. Piping for Special Situations  
Certain types of heating systems have additional requirements. Some of the more common variations follow:  
1) Indirect Water Heaters – Figure 27 shows typical indirect water heater piping. Boiler piping is the same as for any two-zone  
system. Figure 27 shows circulator zoning, which is usually preferred for indirect water heaters. Size the circulator and  
indirect water heater piping to obtain the boiler water ow through the indirect water heater called for by the indirect water  
heater manufacturer. The standard CWD control system will operate two circulator zones. See the Wiring section of this  
manual.  
2) Gravity and “Large Water Volume” Systems – The piping shown in Figure 28 will minimize the amount of time that the  
boiler operates with return temperatures below 120F on these systems. A bypass is installed as shown to divert some supply  
water directly into the return water. The bypass pipe should be the same size as the supply. The two throttling valves shown  
are adjusted so that the return temperature rises above 120F during the rst few minutes of operation. A three-way valve  
can be substituted for the two throttling valves shown. If the circulator is mounted on the supply, the bypass must be on the  
discharge side of the circulator.  
3) Low Temperature Systems – Some systems, such as radiant tubing systems, require the system water temperature to  
be limited to a value below the temperature of the water leaving the CWD. These systems also typically have return  
temperatures well below the 120F minimum.  
Figure 29 illustrates the use of a heat exchanger to connect a CWD boiler to this type of system. The heat exchanger will  
permit the transfer of heat from the boiler water to the low temperature system while holding the system supply and boiler  
return temperatures within their limits. For this system to work properly, the heat exchanger must be properly sized and  
the correct ow rates are required on either side of the heat exchanger. Consult the heat exchanger manufacturer for sizing  
information. The water in the boiler is completely isolated from the water in the system. This means that separate ll and  
expansion tanks are required for the heating system loop.  
There are several other ways to connect low temperature systems to the non-condensing boilers like the CWD such as  
four way mixing valve and variable speed injection pumping systems.  
4) Systems containing oxygen – Many hydronic systems contain enough dissolved oxygen to cause severe corrosion damage  
to a cast iron boiler such as the CWD. Some examples include:  
• Radiant systems that employ tubing without an oxygen barrier.  
• Systems with routine additions of fresh water.  
• Systems which are open to the atmosphere.  
If the boiler is to be used in such a system, it must be separated from the oxygenated water being heated with a heat  
exchanger as shown in Figure 29.  
Consult the heat exchanger manufacturer for proper heat exchanger sizing as well as ow and temperature requirements.  
All components on the oxygenated side of the heat exchanger, such as the pump and expansion tank, must be designed for  
use in oxygenated water.  
5) Piping with a Chiller – If the boiler is used in conjunction with a chiller, pipe the boiler and chiller in parallel as shown in  
Figure 30. Use isolation valves to prevent chilled water from entering the boiler.  
6) Air Handlers – Where the boiler is connected to air handlers through which refrigerated air passes, use ow control valves  
in the boiler piping or other automatic means to prevent gravity circulation during the cooling cycle.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 26: BASIC PIPING  
FIGURE 27: INDIRECT WATER HEATER BOILER-SIDE PIPING  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 28: BYPASS PIPING  
FIGURE 29: ISOLATION OF BOILER FROM SYSTEM WITH HEAT EXCHANGER  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 30: CHILLER PIPING  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IX Wiring  
The CWD Series boiler is offered with two different types of control systems:  
• CB502 Control System - Basic operation of the boiler is controlled with a “CB502 control” (Crown part #42-502) located  
in the left side of the boiler vestibule. This device controls one or two circulator zones without the use of additional  
controls and includes LEDs to show the status of the circulators, inducer, and other boiler controls.  
• R8285 Control System - Basic operation of the boiler is controlled by a Honeywell R8285 fan center. This system  
controls a single zone, although it can be used in a multiple zone system through the use of additional controls. No  
diagnostic LEDs are included in this system.  
Both of these control systems use the same gas valves, ignition system components, and pressure switches.  
Separate wiring instructions are provided for each of these two control systems in the following two sections.  
WARNING  
• All wiring and grounding must be done in accordance with the authority having jurisdiction or, in the absence of  
such requirements, with the National Electrical Code (ANSI/NFPA 70).  
• If a low water cut-off is installed, wire it to break the 120VAC supply to the boiler. Attempting to wire a 24 volt  
low water cut-off into the boiler, or otherwise modifying any of the 24 volt boiler wiring, will void the ANSI Z21.13  
certication of this boiler and may cause unsafe boiler operation.  
A. CB502 System - Single Zone Wiring  
1) Line Voltage (120 VAC) Connections (Fig 31) – The line voltage connections are located in the junction box under the  
transformer on the right side of the vestibule:  
• Black – Line voltage “hot”  
• White – “Neutral” for boiler and circulators  
• Red – “Heating” circulator “hot”  
• Blue – “Indirect Water Heater” circulator “hot” (This wire is not used in single zone installations)  
• Green – Ground connection  
2) Maximum circulator continuous current draw = 10A  
3) Low Voltage (24 VAC) Connections (Fig 31) – These connections are screw terminals located on the front edge of the relay  
board:  
• T-T Heat 1 – “Heating” thermostat connections  
• T-T DHW/H2 – “Indirect Water Heater” thermostat connections  
• Heat anticipator setting for both thermostat connections is 0.03 A.  
4) Priority Switch – When this switch is “on”, the “heating” circulator is turned off when a call for heat is present from  
“indirect water heater” zone. It is used to ensure that the entire output of the boiler is available to the indirect water heater.  
This switch should come from the factory in the “off” position and should be turned on only when absolutely necessary to  
provide adequate domestic water.  
5) Auxiliary Jumpers – Two jumpers are located on the relay board as shown in Figure 32. They are present for connection and  
conguration of an auxiliary control. Unless instructions provided with the control call for these jumpers to be moved, they  
should remain as shown in Figure 32.  
CAUTION  
A problem with the indirect water heater zone could result in a total lack of heat and freeze damage to the building if  
this switch is in the priority “on” position.  
Ensure that the priority switch is “off” when it is not to be used.  
Set the priority switch “on” only when absolutely necessary.  
Do not leave the priority switch “on” when the building will be empty for an extended period of time.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 31: CB502 CONTROL SYSTEM - SINGLE ZONE FIELD WIRING  
FIGURE 32: CB502 CONTROL SYSTEM - FACTORY SWITCH / JUMPER CONFIGURATION  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. CB502 System - Wiring Variations  
1) Two Circulator Zones – Figure 33 shows wiring for two circulator zones. The second zone may be either an indirect water  
heater or a heating zone. No additional electrical controls are required to operate two circulator zones with a standard CWD  
boiler.  
2) Hybrid Zone Valve/Circulator Zone System using Honeywell V8043Fs – The system shown in Figure 34 is useful when  
zone valves are to be used for space heating zones but not the indirect water heater zone. Two circulators are wired into  
the CWD boiler as shown in Figure 34. The zone valve end switches are connected in parallel and connected to the “T – T  
Heat” thermostat connections. A separate transformer is required to power the zone valves – do not attempt to use the  
transformer supplied with the boiler.  
When a given heating thermostat calls, it opens the zone valve to which it is wired. When the zone valve opens, its end  
switch makes, sending a call for heat to the CWD board. This starts the heating circulator and res the boiler.  
The indirect water heater thermostat is connected directly to T-T DHW/H2. Upon a call for heat, it starts the indirect  
water heater circulator and res the boiler. If the priority switch is “on”, a call from the indirect water thermostat also turns  
off the heating circulator. CAUTION: Do not use the factory supplied transformer to power zone valves or other loads  
external to the boiler.  
C. CB502 Control System – Sequence of Operation  
(Refer to Figures 35 and 36 for ladder and connection diagrams)  
1) When no call for heat is present and 120 VAC power is supplied to the boiler, the transformer is energized. The “PWR” LED  
connected across the transformer secondary glows.  
2) Assuming that no call for heat is present from the “DHW/H2” thermostat connections, a call for heat from the “Heat 1”  
thermostat will apply voltage across relay coil 1K and the “Heat” LED.  
3) When the 1K relay coil is energized, contacts 1K1 make, starting the heating circulator. Contacts 1K2 also make, sending  
power to the high limit.  
4) Assuming that the high limit is made, voltage will appear across the “Limit” LED which will illuminate, verifying that the  
high limit switch is closed.  
5) At this point, the pressure switch should be open and continuity should be present between the COM” and “N.C.” contacts  
on the pressure switch. If this is the case, relay coil 3K will be energized along with the “FAN” LED. In the event that  
the pressure switch is stuck in “fan proven” position at the beginning of the operating sequence, the “NC” contact on the  
pressure switch will be open at this point and the operating sequence will not proceed further. This prevents the boiler from  
ring if the pressure switch is stuck in the “fan proven” position.  
6) Once relay coil 3K1 is energized, contacts 3K1 and 3K2 make. Contacts 3K1 energize the fan. Contacts 3K2 provide a  
“latch” for coil 3K, ensuring that coil 3K remains energized after the pressure switch “normally closed” contacts open.  
7) Once the combustion fan has created an adequate pressure differential across the pressure switch, the pressure switch “NO”  
contacts will make. Voltage is then applied across both the “PRESS” LED and the ignition module.  
8) After 30 seconds has passed, the ignition module will initiate an ignition spark and apply 24 VAC across the pilot valve  
(terminals “PV” and “MV/PV” on the gas valve).  
9) If pilot ame is established before the 90 second trial for ignition period has ended, the spark will stop. Voltage is then  
applied across the main valve (gas valve terminals “MV” and “MV/PV”) opening the valve and establishing main ame.  
10) If no pilot ame is detected during the 90-second trial for ignition period, the pilot valve will close and the module will wait  
30 seconds. It will then go through at least one more 90 second trial for ignition period, depending on the exact module  
supplied with the boiler.  
11) A call for heat from the DHW/H2 thermostat will energize relay coil 2K and the “DHW” LED. Relay contacts 2K1 make,  
starting the domestic water circulator. SPDT contacts 2K2 also change position, breaking one current path to relay coil 1K  
and energizing the high limit. The boiler will then start following the sequence outlined in Steps (4) - (10).  
12) The “priority switch “SW1” is “on” when it is open and “off” when it is closed. If the priority switch is “off”, a current path  
will still exist to relay coil 1K after the 2K2 N.C. contacts have opened. If the priority switch is “on” (as shown in Figure  
35), relay coil 1K will be de-energized, causing contacts 1K1 and 1K2 to open. The “heat” circulator will be de-energized,  
but the burner will continue to re because the 2K2 “NO” contacts are made.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 33: CB502 CONTROL SYSTEM - FIELD WIRING FOR TWO CIRCULATOR ZONES  
FIGURE 34: CB502 CONTROL SYSTEM - FIELD WIRING FOR HYBRID CIRCULATOR/ZONE VALVE SYSTEM  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 35: CB502 CONTROL SYSTEM - INTERNAL LADDER DIAGRAM  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 36: CB502 CONTROL SYSTEM - INTERNAL CONNECTION DIAGRAM  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
D. R8285 Control System - Single Zone Wiring  
1) Line Voltage (120 VAC) Connections (Fig 37) – The line voltage connections are located in the junction box under the  
R8285 fan center on the right side of the boiler.  
• Black – Line voltage “hot”  
• White – “Neutral” for boiler and circulators  
• Green – Ground connection  
2) The circulator is factory wired. If a different circulator is wired to the boiler, its full load current draw must not exceed 12A.  
3) Connect the 24-volt thermostat to terminals “R” and “G” on the R8285 fan center. Set the heat anticipator to 0.34 Amps.  
E. R8285 Control System - Wiring Variations  
1) Multiple Circulator Zones – Figure 38 shows wiring for two or more circulator zones using Honeywell R845As. One fewer  
R845A is used than the total number of circulator zones. A DPST Honeywell RA832A may be substituted in place of the  
R845A using the “X” and “X” terminals in place of the “5” and “6” terminals on a R845A.  
A call for heat from the “zone #1” thermostat causes the zone #1 circulator to start and the boiler to re exactly as in a  
single zone system (see “Sequence of Operation”). A call for heat from any other thermostat will energize the DPST relay in  
that zone’s R845A. When this relay is energized, electrical continuity is created between terminals 3 and 4, energizing the  
circulator for that zone. At the same time, electrical continuity is created between terminals 5 and 6 on the R845A, creating  
a current path from terminal “R” to “Y” on the R8285 fan center in the CWD. Assuming that the supply water temperature  
is below the high limit setting, the normal ignition sequence will be initiated. If this happens when there is no call from the  
zone #1 thermostat, the relay on the R8285A will not be energized and the zone #1 circulator will remain off.  
2) Multiple Zones using Zone Valves – Figure 39 shows wiring for multiple zones using Honeywell V8043F zone valves. This  
wiring diagram may be used for other 24-volt zone valves as long as they are equipped with end switches. Do not attempt  
to use the transformer on the R8285 to power the zone valves; use a separate transformer. Up to ve V8043Fs may be  
powered by one 40VA transformer, such as the Honeywell AT87A.  
A call for heat from a given thermostat will result in the application of 24 volts across the TH and TR terminals on the  
corresponding zone valve, energizing the zone valve motor. The zone valve opens and the end switch contacts are then  
made. The end switches are connected in parallel with each other and to the CWD “thermostat” connections so that any  
zone valve that opens will also start the circulator and re the boiler (assuming the high limit is not open). Zone valve  
terminal TH/TR has no internal connection on the zone valve; it is merely a “binding post” used to connect two or more  
wires.  
F. R8285 Control System – Sequence of Operation  
(Refer to Figures 40 and 41 for ladder and connection diagrams)  
1) A call for heat from the thermostat energizes relay coil 1K (the relay on the R8285), causing contacts 1K1 and 1K2 to make.  
Contact 1K1 starts the circulator. Contact 1K2 sends power to the high limit.  
2) Assuming that the high limit is made, current will ow through the normally closed contacts on the pressure switch to relay  
coil “2K” (the R8222 relay coil). Contacts 2K1 make, starting the combustion blower. Contacts 2K2 make, creating a  
current path in parallel with the normally closed pressure switch contacts.  
3) As the combustion fan comes up to full speed, the normally closed contacts on the vacuum switch break. Power remains  
applied to the 2K coil, however, through the 2K2 contacts. Once the combustion fan has created adequate pressure across  
the pressure switch, the normally open contacts on the pressure switch will make, sending power to the ignition module.  
4) After 30 seconds has passed, the ignition module will initiate an ignition spark and apply 24 VAC across the pilot valve  
(terminals “PV” and “MV/PV” on the gas valve).  
5) If pilot ame is established before the 90 second trial for ignition period has ended, the spark will stop. Voltage is then  
applied across the main valve (gas valve terminals “MV” and “MV/PV”) opening the valve and establishing main ame.  
6) If no pilot ame is detected during the 90-second trial for ignition period, the pilot valve will close and the module will wait  
30 seconds. It will then go through at least one more 90 second trial for ignition period, depending on the exact module  
supplied with the boiler.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 37: R8285 CONTROL SYSTEM - SINGLE ZONE FIELD WIRING  
FIGURE 38: R8285 CONTROL SYSTEM - FIELD WIRING FOR TWO CIRCULATOR ZONES  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 39: R8285 CONTROL SYSTEM - ZONE VALVE FIELD WIRING  
FIGURE 40: R8285 CONTROL SYSTEM - INTERNAL LADDER DIAGRAM  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 41: R8285 CONTROL SYSTEM - INTERNAL CONNECTION DIAGRAM  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
X Start-up and Checkout  
WARNING  
• Never attempt to ll a hot empty boiler.  
• Never use a ame to check for gas leaks.  
• Make sure that the area around the boiler is clear and free from combustible materials, gasoline, and other am-  
mable vapors and liquids.  
• If antifreeze is used in the system, it must be a nontoxic type such as propylene glycol.  
NOTE  
Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the  
boiler when the boiler underwent the tests specied in Z21.13.  
Use the following procedure for initial start-up of the boiler:  
1) Make sure that the boiler and system are lled with water.  
2) Check all new gas piping for leaks and purge piping sections that are lled with air. See the National Fuel Gas Code for  
additional information on testing and purging gas lines.  
3) Verify that vent system is complete and free of obstructions before attempting to re boiler. Make sure that the silicone cure  
time called for in the vent assembly instructions has passed before ring boiler.  
4) Inspect all wiring for loose or uninsulated connections.  
5) Adjust thermostat to the highest setting.  
6) Start the boiler using the lighting instructions on the opposite page.  
7) Upon initial start-up, the gas train will be lled with air. Even if the gas line has been completely purged of air, it may take  
several tries for ignition before a ame is established. Once a ame has been established for the rst time, subsequent calls  
for burner operation should result in a ame on the rst try.  
8) Observe pilot burner ame. Pilot burner produces three ames. The center one should be a steady medium blue ame  
covering around 3/8” to ½” of spark electrode / ame rod (Figure 42).  
9) Inspect the main burner ames visible through the observation port in burner access panel. The ame should be stable and  
mostly blue. No yellow tipping should be present; however, intermittent ecks of yellow and orange in the ame are normal  
(Figure 43).  
10) Check entire gas train for leaks using soap and water or other approved leak detection method while boiler is ring. Fix any  
leaks found immediately.  
11) Run gas valve safety shutdown test. With main burners ring, disconnect ignition cable from ignition module. Both pilot  
burner and main burners should stop ring.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR YOUR SAFETY READ BEFORE OPERATING  
WARNING: If you do not follow these instructions exactly, a fire or explosion  
may result causing property damage, personal injury or loss of life.  
A. This appliance is equipped with an ignition  
device which automatically lights the pilot.  
Do not try to light the pilot by hand.  
If you cannot reach your gas supplier, call  
the fire department.  
C. Use only your hand to push in or turn the gas  
control knob. Never use tools. If the knob will  
not push in or turn by hand, don’t try to repair it,  
call a qualified service technician. Force or  
attempted repair may result in a fire or explosion.  
B. BEFORE LIGHTING smell all around the  
appliance area for gas. Be sure to smell next  
to the floor because some gas is heavier than  
air and will settle on the floor.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
Do not touch any electric switch; do not  
use any phone in your building.  
Immediately call your gas supplier from  
a neighbor’s phone. Follow the gas  
supplier’s instructions.  
D. Do not use this appliance if any part has been  
under water. Immediately call a qualified service  
technician to inspect the appliance and to  
replace any part of the control system and any  
gas control which has been under water.  
OPERATING INSTRUCTIONS  
1. STOP! Read the safety information above on  
this label.  
5. Remove front access panel.  
6. Rotate the gas control knob clockwise  
to OFF.  
2. Set the thermostat to lowest setting.  
7. Wait five (5) minutes to clear out any gas. Then  
smell for gas, including near the floor. If you then  
smell gas, STOP! Follow “B” in the safety inform-  
ation above on this label. If you don’t smell gas  
go to the next step.  
3. Turn off all electric power to the appliance.  
4. This appliance is equipped with an ignition  
device which automatically lights the pilot.  
Do not try to light the pilot by hand.  
8. Rotate the gas control knob counter clockwise  
to “ON”.  
GAS CONTROL KNOB  
(SHOWN IN “ON” POSITION)  
9. Replace front access panel.  
10. Turn on all electric power to the appliance.  
11. Set thermostat to desired setting.  
GAS INLET  
GAS OUTLET  
12. If the appliance will not operate, follow the  
instructions “To Turn Off Gas To Appliance” and  
call your service technician or gas supplier.  
GAS VALVE - TOP VIEW  
TO TURN OFF GAS TO APPLIANCE  
1. Set the thermostat to lowest setting.  
3. Push in gas control knob slightly and turn  
clockwise to “OFF”. Do not Force.  
2. Turn off all electric power to the appliance if  
service is to be performed.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING  
Failure to follow the following procedure exactly could result in over-ring of the boiler and a carbon monoxide  
hazard.  
12) Check the manifold pressure and adjust if necessary. To do this, use the following procedure:  
a) Connect a manometer to the line pressure tap on the gas valve (see Figure 44).  
b) Check the line pressure with all gas appliances on and off. The line pressure at the boiler must be within the following  
limits regardless of what combination of appliances is ring:  
Line Press (inches w.c.)  
Minimum  
Maximum  
Natural Gas  
5.0  
14.0  
LP Gas  
11.0  
13.0  
If the line pressure falls outside of these limits, nd and correct the cause of the problem before proceeding further.  
c) Disconnect the silicone regulator tube from the hose barb on the gas valve (Figure 45).  
d) Connect a manometer to the manifold (outlet) pressure tap on the gas valve (Figure 44).  
e) Read the manifold pressure. It should be set at:  
Natural Gas  
3.5  
LP Gas  
10.0  
Manifold Press. (inches w.c.)  
e) If a manifold pressure adjustment is needed, make the adjustment by turning the regulator screw (see Figure 44)  
clockwise to raise the pressure and counter-clockwise to reduce the pressure. If a manifold pressure adjustment is made,  
recheck the line pressure to be certain that it is still within acceptable limits. Replace the cover screw on the regulator.  
f) Reconnect the silicone regulator tube disconnected in Step (c)  
13) Test thermostat operation while the boiler is running. Turn the thermostat to the lowest setting. Circulator should stop  
running. Raise the thermostat back to the highest setting. Circulator should restart. The pilot burner and main burners  
should relight.  
14) Verify high limit operation. Allow the boiler water temperature to increase to high limit setting. Circulator should continue  
running and pilot burner and main burners should stop ring. When water temperature drops below the limit setting, the  
pilot burner and main burners should relight.  
15) After the boiler has operated for approximately 30 minutes, check the boiler and heating system piping for leaks. Repair any  
leaks found at once.  
16) Inspect the vent system for ue gas leaks. Repair any leaks found before leaving the boiler in operation.  
FIGURE 43: MAIN BURNER FLAME  
FIGURE 42: PILOT BURNER FLAME  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 44: GAS VALVE  
FIGURE 45: MEASURING MANIFOLD PRESSURE  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XI Service and Maintenance  
The following routine maintenance should be performed on an annual basis:  
1) Turn off electrical power and gas supply to the boiler.  
2) Remove the burner tray. To do this:  
a) Remove the intake cover.  
b) Remove the four Allen head screws holding the elbow ange onto the gas valve.  
c) Remove the three 10-32 screws holding the manifold gasket plate to the intake box.  
d) Remove the four 5-16 nuts holding the burner tray in the boiler.  
f) Carefully remove the burner assembly being careful not to damage the redoor insulation or the manifold gasket.  
3) Inspect the ue passages for signs of blockage. If there is any carbon in the combustion chamber or the ue passages, clean  
the heat exchanger before proceeding further. See the cleaning procedure below.  
4) Remove any debris found in the combustion chamber, being careful not to disturb combustion chamber insulation.  
5) Inspect and clean the burners. Clean the burners by rst brushing the ports with a soft bristle brush and then vacuuming out  
any debris through the venturi opening. If burners show signs of deterioration, they should be replaced (some discoloration  
around the burner ports is normal).  
6) Inspect the pilot assembly. Clean any deposits found on the electrode and grounding strap. The ideal gap between the  
electrode and the ground strap is 1/8”. Inspect the porcelain for cracks or other deterioration. Replace pilot assembly if  
deterioration is found. Inspect the ignition cable insulation for cracks or other deterioration. If deterioration is found,  
replace cable assembly.  
7) Inspect the combustion chamber insulation for deterioration. Replace insulation if necessary.  
8) Inspect all boiler wiring for loose connections or deterioration.  
9) Inspect the vent system:  
Make sure that the vent system is free of obstructions.  
Make sure that all vent system supports are intact.  
Inspect joints for signs of condensate or ue gas leakage.  
Inspect venting components for corrosion or other deterioration. Replace any defective vent components.  
10) Inspect the boiler and hydronic system for leaks.  
11) Place the boiler back in operation using the procedure outlined in Part X. Check the pilot line and any other gas piping  
disturbed during the inspection process for leaks.  
CAUTION  
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous  
operation. Verify proper operation after servicing.  
CAUTION  
Water leaks can cause severe corrosion damage to the boiler or other system components. Repair any leaks found  
immediately.  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Heat Exchanger Cleaning Procedure  
WARNING  
Soot deposits in the ue passages are a sign that the boiler may be operating at high carbon monoxide (co) levels. After  
cleaning the boiler of soot deposits, check the CO level in the ue gas to insure that the boiler is operating properly.  
If it is necessary to check CO, use a combustion analyzer, or other instrument which is designed to measure CO in  
ue gas. A CO “sniffer” designed for testing CO levels in ambient air cannot be used to check boiler combustion. Take  
a ue gas sample by inserting a sample probe through the vent terminal. Do not take a sample until the boiler has  
been ring for at least ve minutes.  
A normal CO reading for an CWD series boiler is less than 50ppm (0.005%). A reading of more than 100ppm  
(0.01%) is indicative of a combustion problem.  
Some causes of excessive CO include:  
• Incorrectly sized or drilled burner orice  
• Partially plugged ue passages  
• Improper manifold pressure  
• Partial blockage of vent or intake system  
• Foreign material in burner venturis or burner ports  
• Missing regulator cover or disconnected regulator reference tube  
• Damaged fan impeller or housing  
• Damaged or missing fan gasket  
• Leak in seal between ue collector and heat exchanger  
• Distorted or missing combustion chamber oor  
• Damaged base  
• Flue gas leak in the concentric section of the coaxial terminal  
1) Turn off electrical power and gas supply to the boiler.  
2) Remove the burner tray. To do this:  
a) Remove the intake cover.  
b) Remove the four Allen head screws holding the elbow ange onto the gas valve.  
c) Remove the three 10-32 screws holding the manifold gasket plate to the intake box.  
d) Remove the four 5-16 nuts holding the burner tray in the boiler.  
e) Carefully remove the burner assembly being careful not to damage the redoor insulation or the manifold gasket.  
3) Disconnect the vent system from the boiler by removing the four 10-32 screws holding the vent collar in place.  
4) Remove the top jacket panel. If possible, remove the rear and left side jacket panels.  
5) Unplug the fan and remove the fan cover plate.  
6) Disconnect the pressure switch hoses.  
7) Loosen the two ¼-20 nuts and washers in the ue collector lugs. Slide the ue collector lugs off of each ue collector ange.  
8) Score the silicone seal around the ue collector with a utility knife or similar tool.  
9) Pry the ue collector off of the heat exchanger, being careful not to damage the ue collector or fan.  
10 Remove the stainless steel ue bafe from each ue passage.  
11) Clean the ue passageways using a stiff bristle brush. Be certain that all foreign material is removed from the gaps between  
the pins.  
12) Clean the bottom surfaces of the heat exchanger.  
13) Put a light in the combustion chamber and look through the ue passages from the top to verify that they have been  
thoroughly cleaned.  
14) Replace the ue bafes.  
15) Apply a heavy (1/4”) bead of silicone with a temperature rating of at least 400F around the perimeter of the heat exchanger.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
16) Set the ue collector onto the block and press down so that the ue collector is set into the silicone applied in the previous  
step.  
17) Slide the ue collector lugs back into position and retighten the ¼-20 bolts. DO NOT OVER TIGHTEN.  
18) Apply a bead of silicone around the outside of the joint between the heat exchanger and the ue collector.  
19) Reattach all the jacket components.  
20) Reconnect the pressure switch tubes (see Figure 46 for correct tubing orientation).  
21) Reconnect the fan.  
22) Reconnect the vent system.  
23) Reinstall the burner tray.  
Service Notes  
1) Orice Size – Sea level orice sizes are:  
Natural Gas – #50 Drill Size  
LP Gas – Consult Factory  
Consult your Crown representative for correct orice sizes for use at altitudes above 2000 ft. Orice for this boiler cannot  
be drilled in the eld.  
2) Operating the Boiler with Intake Cover Removed – For inspection and troubleshooting purposes, this boiler may be started  
and run with the intake cover removed. When this is done, a resonance (“hum”) may be observed. This is normal and  
should disappear as soon as the intake cover is replaced.  
WARNING  
Do not leave the boiler in service with the intake cover removed.  
3) Pressure Switch – This boiler is equipped with a differential pressure switch which makes when there is adequate ue gas  
ow through the boiler. This switch measures the pressure drop across an orice plate inside the ue collector - the higher  
the ue gas ow through this plate, the higher the pressure drop. The N.O. contacts on the pressure switch make, allowing  
the boiler to re, when the pressure drop across the ue collector orice plate switch exceeds the “make setting” shown in  
Table 7. Once the switch is made, the boiler will re as long as the pressure at the switch is above the “break setting” shown  
in Table 7. The pressure at both pressure switch tappings is actually below atmospheric (“negative”) with the pressure at the  
upper ue collector tap being the more negative of the two pressures. Figure 46a shows the pressure switch connections.  
Figure 46b shows the correct method of reading the pressure across the pressure switch tappings. It is normal for the  
pressure reading across the switch to drop as the boiler heats up.  
4) Burner and Pilot Removal - If necessary, the pilot can be removed without removing the burner tray. To do so, remove the  
screws holding the main burners on each side of the pilot bracket. The main burners will then be loose enough to allow the  
pilot hood to slip between them.  
Main burners cannot be removed without removing the burner tray from the boiler.  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 7: PRESSURE SWITCH SETTINGS  
MAKE SETTING*  
(inches w.c.)  
BREAK SETTING*  
ALTITUDE  
SEA LEVEL - 5200 ft  
ABOVE 5200 ft  
CROWN PN  
620009  
(inches w.c.)  
1.26  
1.10  
1.16  
620010  
1.00  
*Settings shown are based on “plus tolerance” - actual setting may be lower.  
FIGURE 46a: PRESSURE SWITCH CONNECTIONS  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURE 46b: MEASURING PRESSURE ACROSS PRESSURE SWITCH  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XII Troubleshooting  
The following pages contain troubleshooting charts for use in diagnosing control problems. If troubleshooting a CB502  
control system, go to the box marked “Start” at the top of the chart on page 58 and follow the appropriate path though the chart  
until a box with a list of possible causes is reached. If troubleshooting a R8285 control system, go to the box marked “Start”  
at the top of the chart on page 62 and follow the appropriate path though the chart until a box with a list of possible causes is  
reached.If the problem is known to be within the ignition system, go directly to the ingition system troubleshooting guide on  
page 64. In using these charts, the following should be kept in mind:  
1) These charts are only meant to be used by a professional heating technician as an aid in diagnosing control problems.  
2) Where applicable, follow all precautions outlined in the appropriate lighting instructions on page 49.  
3) In general, these charts assume that there are no loose or miswired electrical connections. Before using these charts, inspect  
all electrical connections on the boiler to make sure that they are tight. Also, check the wiring on the boiler against the  
appropriate wiring diagrams in the Wiring section.  
4) The possible causes at the end of each branch in these charts are not listed in order of likelihood. All controls on the CWD  
are tested at least once in the manufacturing process and a defective control or component is generally the least likely cause.  
Before replacing a component, try to rule out all other possible causes.  
5) If the charts indicate that the boiler transformer is defective, it is possible that this transformer has been destroyed by a short  
circuit in the boiler wiring. Before replacing the transformer, carefully inspect all low voltage wiring on the boiler for places  
where it is touching the frame of the boiler or wiring on the other side of the transformer.  
6) If the charts indicate that one of the relays in the CB502 board or the R8285 are defective, it is possible that a second  
transformer is present in the thermostat or zone valve circuit, resulting in the application of 48 volts across the relay coil. In  
older buildings, this transformer may be hidden in a location far from the boiler. If this second transformer exists, it must be  
found and removed before the relay is replaced.  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
N
START  
(No call for  
heat from  
Y
Call from  
"HEAT 1"  
zone  
"HEAT 1"  
Circulator  
start?  
"DHW/H2"  
zone used?  
PWR  
LED On?  
Y
Y
either zone)  
N
N
Y
HEAT  
LED On?  
Y
24volts  
transformer  
secondary?  
N
*Defective  
transformer  
harness  
*Defective  
CB502  
120 volts  
N
N
across red and  
white circulator  
leads?  
N
24V across  
"HEAT 1" T  
and T  
Y
120 volts across  
black and white  
transformer  
Y
Y
primary leads ?  
* Loose  
N
"DHW  
PRIORITY"  
Switch on?  
connection  
between boiler  
J-box circ.  
* Defective  
circulator  
N
Y
* Power off  
* Blown fuse or  
tripped breaker  
* Miswired or  
loose electrical  
connection in  
120 volt line  
* Loose connection in  
t'stat or zone valve end  
switch wiring  
* Defective t'stat or zone  
valve end switch  
*Defective CB502  
board  
*Defective  
"DHW/H2" relay  
* T'stat or zone system  
miswired-consult zone  
valve or t'stat  
* Defective  
transformer.  
manufacturer's  
instructions.  
*Defective CB502  
board  
* Defective "HEAT 1" relay  
on CB502  
* Relay not fully seated in  
socket  
TROUBLESHOOTING CHART FOR BOILERS WITH CB502 CONTROL SYSTEM (USING #42-502A BOARD)  
PAGE 1 OF 4  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Call for heat  
from  
"DHW/H2"  
zone  
"DHW/H2"  
circulator  
start?  
Y
Continued on  
next page  
N
N
Y
DHW  
LED On?  
Y
24V across  
"DHW/H2" T  
and T  
N
Y
120 volts across  
blue and white  
circulator leads?  
Defective  
CB502 board  
N
*Loose  
connection  
between boiler  
J-box and circ  
* Loose connection in  
t'stat or zone valve end  
switch wiring  
* Defective t'stat or zone  
valve end switch  
* T'stat or zone system  
miswired-consult zone  
valve or t'stat  
manufacturer's  
instructions.  
* Defective "DHW/H2"  
relay on CB502  
* Relay not fully seated  
in socket  
* Loose connection in  
circulator wiring  
TROUBLESHOOTING CHART FOR BOILERS WITH CB502 CONTROL SYSTEM (USING #42-502A BOARD)  
PAGE 2 OF 4  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Continued  
from previous  
page  
Y
Y
Y
Y
LIMIT  
LED on?  
PRESS  
LED on?  
Fan On?  
N
N
N
FAN  
LED on?  
* Missing or loose  
"RESET CONTROL"  
jumper  
*Missing or loose  
"CN1" jumper  
*Defective CB502  
board  
24V between  
brown lead on  
limit and yellow  
lead on  
N
N
transformer?  
Y
* Boiler water  
temp over L4080D  
setpoint  
*Defective L4080D  
24 volts present  
across yellow  
transformer lead and  
red lead on pressure  
switch?  
Y
24 volts present  
across yellow  
transformer lead and  
purple lead on  
N
pressure switch?  
* Kinked or blocked  
vacuum switch tubing  
* Defective vacuum  
switch  
Unplug fan and  
check for 120V  
across H FAN  
and N FAN on  
CB502 board  
N
Y
*Loose pressure  
switch harness  
*Defective CB502  
board  
Minimum  
pressure at  
switch called in  
Table 7 present  
across switch?  
N
* Loose  
Y
connection at  
fan plug or fan  
capacitor  
120 volts  
present?  
Y
* Defective  
*Tubes reversed on  
pressure switch  
*Leak in tubes at pressure  
switch connection  
capacitor  
* Defective fan  
N
*Loose pressure switch  
harness connection  
*Defective CB502 board  
*Defective "FAN"  
relay  
*Defective CB502  
board  
TROUBLESHOOTING CHART FOR BOILERS WITH CB502 CONTROL SYSTEM (USING #42-502A BOARD)  
PAGE 3 OF 4  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Do burners shut  
down before  
gauge temp  
exceeds high limit  
setting +15F?  
Y
Wait 30  
seconds  
(prepurge)  
Main  
burners  
light?  
Y
Y
Pilot  
light?  
N
N
N
24 volts  
between 24V  
and  
24V (GND) on  
ign. module?  
See "Intermittent  
Ignition System  
Troubleshooting  
Chart" on page 64  
Y
END  
N
* Defective L4080D  
* Sensing bulb not bottomed  
out in well  
Do burner,  
circulator and  
fan shut down at  
end of call for  
heat?  
*Loose  
harness  
*Defective  
CB502 board  
Y
N
*Loose, leaking, blocked, or reversed  
pressure switch tubes  
*Leaks in flue collector joints  
*Foreign object in fan or flue collector  
* Blockage in venting system  
* Vent system not installed in  
accordance with installation manual  
* Excessive silicone on I.D. of vent  
system joints  
Does boiler shut  
down when t'stat  
wire is removed from  
t'sat terminal  
N
* Damaged or missing fan gasket  
* Defective fan  
* Wind at horizontal vent terminal in  
excess of 40 mph  
Y
*Incorrect fan outlet orifice  
* T'stat or zone system  
calling for heat  
* T'stat wires shorted  
* Internal boiler wiring  
problem, consult  
Crown representative  
TROUBLESHOOTING CHART FOR BOILERS WITH CB502 CONTROL SYSTEM (USING #42-502A BOARD)  
PAGE 4 OF 4  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START  
Induced  
draft fan  
start?  
Wait 30  
seconds  
(prepurge)  
Y
Y
Circulator  
start?  
N
N
Unplug fan and  
check for 120 volts  
across black and  
white connections  
on female half of  
plug.  
Thermostat  
calls for heat  
24volts across R  
and C on R8285  
fan center?  
N
Y
Y
120 volts  
present?  
120 volts across  
black and white  
transformer  
primary leads on  
back of R8285 ?  
24 volts across  
G and C on  
R8285 fan  
center?  
Y
N
N
* Loose  
Y
Reconnect fan  
connection at  
fan plug or fan  
capacitor  
N
* Loose connection in  
t'stat or zone valve end  
switch wiring  
* Power off  
* Defective  
capacitor  
* Defective fan  
* Defective t'stat or zone  
valve end switch  
* T'stat or zone system  
miswired-consult zone  
valve or t'stat  
* Blown fuse or  
tripped breaker  
* Miswired or  
loose electrical  
connection in  
120 volt line  
24 volts  
present across  
yellow and  
N
manufacturer's  
instructions.  
purple leads on  
R8222?  
* Defective  
transformer.  
Replace R8285.  
24 volts present  
across yellow  
and orange  
connections on  
R8222?  
N
Y
120 volts across  
N
circulator  
* Defective  
R8222 relay  
connections?  
* Socket not fully  
seated on relay  
Y
* Defective relay on  
R8285  
* Relay not fully seated  
in socket  
* Loose connection in  
circulator wiring  
Y
* Kinked or blocked  
pressure switch  
tubing  
* Defective pressure  
switch  
* Boiler off on  
high limit  
* Defective  
L4080D  
* Defective  
circulator  
TROUBLESHOOTING CHART FOR BOILERS WITH R8285 CONTROL SYSTEM - PAGE 1 OF 2  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
END  
Main  
burners  
light?  
Y
Y
Do burners shut  
down before  
gauge temp  
Pilot  
light?  
Y
exceeds high limit  
setting +15F?  
N
N
N
See "Intermittent  
Ignition System  
Troubleshooting  
Chart" on page 64.  
24 volts  
between 24V  
and  
24V (GND) on  
ign. module?  
Y
Do burner,  
circulator and  
fan shut down at  
end of call for  
heat?  
Y
* Defective L4080D  
* Sensing bulb not bottomed  
out in well  
N
N
Does boiler shut  
down when t'stat  
wire is removed from  
terminal R on  
N
R8285?  
Minimum  
pressure at  
switch called in  
Table 7 present  
across switch?  
N
Y
* Blockage in venting system  
* Vent system not installed in  
accordance with installation manual  
* Excessive silicone on I.D. of vent  
system joints  
Y
* Internal boiler wiring  
problem, consult  
Crown representative  
* Blockage, condensate or leakage in  
vacuum switch tubing  
* Improperly sealed flue collector  
* Damaged or missing fan gasket  
* Defective fan  
*Tubes reversed on  
pressure switch  
*Leak in tubes at pressure  
switch connection  
* T'stat or zone system  
calling for heat  
* T'stat wires shorted  
*Loose pressure switch  
harness connection  
* Wind at horizontal vent terminal in  
excess of 40 mph  
TROUBLESHOOTING CHART FOR BOILERS WITH R8285 CONTROL SYSTEM - PAGE 2 OF 2  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START  
IMPORTANT: ALL PILOT TROUBLESHOOTING  
ON THIS CHART MUST BE PERFORMED AFTER  
THE 30 SECOND PREPURGE HAS ENDED AND  
BEFORE THE END OF THE 90 SECOND TRIAL  
FOR IGNITION PERIOD.  
(24 volts is present across 24V and 24V (GND) on  
Ignition Module, 30 second prepurge period has  
passed)  
Pulsing  
Spark  
across  
Does  
Main  
Y
Y
Y
Y
Pilot  
lights?  
spark stop  
when pilot  
lights?  
burner  
lights?  
END  
ignitor/sensor  
gap?  
N
N
N
N
24VAC  
across  
terminals MV  
& MV/PV on  
module?  
N
24 volts  
across  
terminals PV  
& MV/PV at  
module?  
N
Y
* Defective  
module  
Y
* Defective  
module  
* Module is in soft  
lockout. Reset by  
momentarily  
interupting power to  
boiler and waiting for  
prepurge.  
24 volts  
between MV &  
MV/PV on gas  
valve?  
24 volts  
across PV &  
MV/PV at gas  
valve?  
N
Y
* Break in spark  
cable insulation  
* Break in pilot  
porcelain  
N
Y
* Incorrect pilot  
spark gap  
* Loose connection  
in spark cable  
* Loose ground  
connection  
* Loose connection in  
ignition cable or  
ground wire  
* Pilot electrode  
porcelain cracked  
* Pilot flame not  
covering gap  
* Defective EI  
wiring harness.  
*Defective EI  
harness  
* Defective Ignition  
Module  
between electrode  
and grounding  
strap  
* Low inlet gas  
pressure  
* Low inlet gas pressure  
* Plugged, kinked or leaking  
pilot tubing  
* Plugged pilot orifice  
* Gas line not purged of air  
* Defective pilot assembly  
* Defective gas valve  
* Defective  
gas valve  
* Defective module  
TROUBLESHOOTING CHART FOR IGNITION SYSTEMS USING UT 1003-626A IGNITION MODULE  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XIII PARTS  
The following parts may be obtained from any Crown distributor. To nd the closest Crown distributor, consult the area  
Crown representative or the factory at:  
Crown Boiler Co.  
Customer Service  
P.O. Box 14818  
Philadelphia Pa. 19134  
Main burner orice shown are for sea level congured boilers. For boilers installed at elevations above 2000 ft, consult the  
local Crown representative or the factory for the correct main burner orice.  
In some cases, the following parts lists do not include Crown part numbers because they were not available at the time of  
printing. Order these parts by their description, specifying the boiler model number on which they are to be used.  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOCK, BASE, FLUE COLLECTOR COMPONENTS  
PART  
# OR  
QTY.  
PART # OR QTY.  
KEY DESCRIPTION  
CWD060 CWD083 CWD110 CWD138 CWD165 CWD193 CWD220 CWD245  
1
2
BASE  
1
620113  
4
620114  
4
620115  
4
620116  
4
620117  
4
620118  
4
620119  
4
620120  
4
NYLON FEET (GLIDES)  
700111  
3
4
5
6
*
*
*
*
INTAKE BOX  
1
620233  
14  
620234  
14  
620235  
14  
620236  
14  
620237  
14  
620238  
14  
620239  
14  
620240  
14  
1/4-20 X1/2 PAN HEAD SCREW  
5/16-18 X 1 1/4 TAP BOLT  
COMPLETE CAST IRON BLOCK ASSEMBLY  
LEFT END SECTION  
INTERMEDIATE SECTION  
RIGHT END SECTION  
900100  
900101  
1
620011  
620006  
620012  
620008  
2
2
2
2
2
2
2
2
620013  
620014  
620015  
620016  
620017  
620018  
620019  
620020  
1
1
1
4
1
2
1
6
1
3
1
8
1
4
1
1
5
1
1
6
1
1
7
1
1
8
1
PUSH NIPPLE  
10  
12  
14  
16  
18  
5/16-18 X 1 1/2 FULLY THREADED ZINC  
PLATED STUDS  
7
900425  
4
4
4
4
4
4
4
4
8
9
10  
5/16 USS FLAT WASHER  
5/16-18 S,S HEX NUT  
5/16-18 NYLON INSERT HEX NUT  
3/4 X 1/4 BLACK IRON REDUCING  
BUSHING  
900102  
90-010  
900103  
14  
8
2
14  
8
2
14  
8
2
14  
8
2
14  
8
2
14  
8
2
14  
8
2
14  
8
2
11  
12  
13  
14  
15  
950017  
1
1
1
1
1
1
1
1
3/4 IN BLACK IRON PLUG  
95-048  
35-  
1010  
1
2
2
2
2
2
2
2
2
3/4” HIGH LIMIT WELL  
1
620143  
1
1
620144  
1
1
820145  
1
1
620146  
1
1
620147  
1
1
620148  
1
1
620149  
1
1
620150  
1
CWD DISTRIBUTOR PIPE  
3/8-16 X 1 1/4 ZINC PLATED HEX HEAD  
CAP SCREW  
900452  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
*
30  
31  
32  
33  
34  
35  
36  
FLUE BAFFLE  
TINNERMAN NUT  
10-32 X 1/8 I.D.HOSE BARB  
10-32 HEX NUT  
REAR FIREDOOR  
REAR FIREDOOR INSULATION  
1 1/4 CUP HEAD PIN  
1 1/4 SELF LOCKING WASHER  
1” CERAFELT SEALING STRIP  
5/16-18 X 3/4 HEX CAP SCREW  
FLUE COLLECTOR  
FLUE COLLECTOR LUG  
FAN GASKET  
FAN ASSEMBLY  
620100  
90-217  
90-222  
90-219  
1
2
10  
3
3
620203  
620533  
4
3
10  
3
3
620204  
620534  
4
4
12  
3
3
620205  
620535  
6
5
12  
3
3
620206  
620536  
6
6
12  
3
3
620207  
620537  
6
7
12  
3
3
620208  
620538  
6
8
12  
3
3
620209  
620539  
6
9
12  
3
3
620210  
620540  
6
1
900203  
900200  
4
4
6
6
6
6
6
6
900145 0.75 FT 1.05 FT 1.35 FT 1.65 FT 1.95 FT 2.25FT 2.55 FT 2.85 FT  
900400  
1
60-501  
1
1
1
90-202  
60-600  
1
90-058  
90-057  
1
4
4
4
4
620126  
2
650002  
60-001  
60-003  
4
4
620127  
2
650002  
60-001  
60-003  
4
4
620128  
2
650002  
60-001  
60-003  
4
4
620129  
2
650002  
60-001  
60-003  
4
4
620130  
2
650002  
60-001  
60-003  
4
620123  
2
620002  
620001  
620003  
4
620124  
2
620002  
620001  
620003  
4
620125  
2
620002  
620001  
620003  
4
REPLACEMENT FAN CAPACITOR  
1/4-20 HEX NUT  
COLLAR GASKET  
2
2
2
2
2
2
2
2
FAN OUTLET ORIFICE  
10-32 X1/2 SLOTTED ROUND SCREW  
#10 FLAT WASHER  
COMB CHAMBER FLOOR  
DISTRIBUT0R SCREEN  
10-32 X1/2 SLOTTED HEX WASHER SCREW,  
TYPE “F”, ZINC PLATED  
INTAKE BOX INSULATION  
INTAKE COVER  
INTAKE COVER GASKET  
SIGHT GLASS  
SIGHT GLASS GASKET  
SIGHT GLASS FRAME  
#10 X 3/4 HEX HEAD TYPE “B” SCREW  
3 “ VENT COLLAR  
620133  
6
650136  
6
620135  
6
620136  
6
620137  
6
620138  
6
620139  
6
650138  
6
4
4
4
4
4
4
4
4
620223  
620253  
620224  
620254  
620225  
620255  
620226  
620256  
620227  
620257  
620228  
620258  
620229  
620259  
620230  
620260  
1
37  
900155  
25  
31  
37  
43  
49  
55  
61  
67  
38  
39  
40  
41  
42  
43  
44  
45  
45  
*
1
1
1
620553  
620213  
620613  
1
1
1
10  
1
0
620554  
620214  
620614  
1
1
1
10  
1
0
620555  
620215  
620615  
1
1
1
12  
1
0
620556  
620216  
620616  
1
1
1
12  
1
0
620557  
620217  
620617  
1
1
1
12  
1
1
620558  
620218  
620618  
1
1
1
12  
1
1
620559  
620219  
620619  
1
1
1
12  
0
1
620560  
620220  
620620  
1
1
1
12  
0
1
60-052  
60-056  
60-055  
90-054  
60-603  
60-604  
90-045  
4” VENT COLLAR  
10.1 oz TUBE SILICONE SEALANT  
1
1
1
1
1
1
1
1
* NOT PICTURED  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BURNER TRAY COMPONENTS  
PART#  
OR  
PART # OR QTY.  
KEY  
DESCRIPTION  
CWD060 CWD083 CWD110 CWD138 CWD165 CWD193 CWD220 CWD245  
QTY.  
1
50  
51  
52  
53  
54  
55  
56  
56  
56  
56  
57  
58  
59  
FRONT FIREDOOR  
620543  
620523  
620544  
620524  
620545  
620525  
620546  
620547  
620548  
620528  
620549  
620529  
620550  
620530  
FRONT FIREDOOR INSULATION  
INSULATION SUPPORT BRACKET  
MICA SIGHT GLASS  
1/8 ALUMINUM POP RIVET  
BURNER MANIFOLD  
#49 ORIFICE (SEA LEVEL, NAT GAS)  
#50 ORIFICE (SEA LEVEL, NAT GAS)  
#56 ORIFICE (SEA LEVEL, LP GAS)  
#57 ORIFICE (SEA LEVEL, LP GAS)  
MANIFOLD GASKET  
MANIFOLD GASKET PLATE  
3/4” 90 DEGREE FLANGE  
HONEYWELL VR8204C2328 GAS VALVE  
(NAT GAS)  
HONEYWELL VR8304P2342 GAS VALVE  
(NAT GAS)  
HONEYWELL VR8204P2294 GAS VALVE  
(LP GAS)  
HONEYWELL VR8304P3522 GAS VALVE  
(LP GAS)  
1
620526  
620527  
620101  
60-050  
90-068  
1
950305  
950306  
950331  
950332  
60-151  
60-150  
35-1055  
2
1
2
2
1
2
2
1
2
2
2
4
1
2
4
1
2
4
1
2
1
1
2
2
620153  
620154  
620155  
620156  
620157  
620158  
620159  
620160  
4
0
4
0
1
1
1
0
6
0
6
1
1
1
0
8
0
8
1
1
1
0
10  
0
0
12  
0
0
14  
0
14  
1
0
16  
0
16  
1
0
18  
0
18  
1
10  
1
12  
1
1
1
1
1
1
1
1
1
1
1
60  
60  
60  
60  
3507400  
3507410  
3507405  
3507245  
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
0
1
0
1
0
1
0
1
0
1
0
1
61  
62  
63  
1/8” GAS VALVE HOSE BARB HW#394537 35-1060  
1
4
1
1
6
1
1
8
1
1
10  
1
1
12  
1
1
14  
1
1
16  
1
1
18  
1
BECKETT GAS BURNERS  
PILOT BRACKET  
150620  
150625  
Q3481B1131 PILOT ASSEMBLY (NAT GAS)  
- INCLUDES IGNITION CABLE  
Q3481B1149 PILOT ASSEMBLY (LP GAS)  
- INCLUDES IGNITION CABLE  
64  
64  
3504100  
3504105  
1
1
1
1
1
1
1
1
65  
66  
30” X 1/8” PILOT TUBING  
IGNITION GROUND HARNESS  
90-043  
9601101  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
146-95-  
301  
67  
68  
69  
70  
70  
10-32 X 3/16 HEX HEAD PILOT SCREW  
1
1
1
1
1
1
1
1
1/8 SHORT FERRULE (INCLUDED WITH  
GAS VALVE)  
1/8 LONG FERRULE (INCLUDED WITH  
PILOT ASSY.)  
KF24 PILOT ORIFICE (NAT GAS) -  
INCLUDED WITH PILOT ASSY.  
K14 PILOT ORIFICE (LP GAS) -  
INCLUDED WITH PILOT ASSY.  
35-1600  
35-1650  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
JACKET COMPONENTS  
PART # OR QTY  
PART#  
OR  
QTY  
KEY DESCRIPTION  
CWD060 CWD083 CWD110 CWD138 CWD165 CWD193 CWD220 CWD245  
80  
81  
82  
83  
84  
85  
86  
87  
88  
89  
90  
91  
92  
VESTIBULE PANEL  
LARGE PLASTIC BUSHING  
FAN COVER PLATE  
#10 X 1/2 SHEET METAL SCREW  
LH JACKET PANEL  
RH JACKET PANEL  
REAR JACKET PANEL  
PLASTIC BUSHING  
CONTROL PANEL  
TOP JACKET PANEL  
CWD FRONT JACKET PANEL  
DOOR KNOB  
1
620323  
620324  
620325  
620326  
620327  
620328  
620329 620330  
960051  
1
90-212  
620301  
620300  
1
96-050  
620350  
1
1
1
1
1
1
1
1
1
620302  
31  
1
1
620303  
2
1
620323  
620323  
2
620302  
31  
1
1
620304  
2
1
620324  
620324  
2
620302  
32  
1
1
620305  
2
1
620325  
620325  
2
60-300  
31  
1
1
620306  
2
1
620326  
620326  
2
60-300  
34  
1
1
620307  
2
1
620327  
620327  
2
60-300  
36  
1
1
620308  
2
1
620328  
620328  
2
60-300  
60-300  
36  
1
36  
1
1
1
620309 620310  
2
1
2
1
620329 620330  
620329 620330  
1
90-210  
90-211  
2
2
2
2
8-32 X 1/4 MACH. SCREWS  
2
2
2
2
2
2
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMON CONTROLS & TRIM  
PART#  
OR  
PART # OR QTY  
KEY DESCRIPTION  
CWD060 CWD083 CWD110 CWD138 CWD165 CWD193 CWD220 CWD245  
QTY  
14-008  
35-3300  
95-069  
3503062  
905000  
9601100  
96-055  
*
1/8” SILICONE TUBING  
HONEYWELL L4080D LIMIT  
TRIDICATOR GAUGE  
UT IGNITION MODULE 1003-626A  
MODULE BRACKET  
2.5 FT  
2.5 FT  
2.5 FT  
2.5 FT  
2.5 FT  
2.5 FT  
2.5 FT  
2.5 FT  
100  
101  
102  
103  
*
1
1
1
0
1
1
1
1
1
0
1
1
1
1
1
0
1
1
1
1
1
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
INTERMITTENT IGNITION HARNESS  
4X4 JUNCTION BOX  
104  
SEA LEVEL PRESSURE SWITCH (ALL  
SIZES)  
PRESSURE SWITCH (AS NEEDED ABOVE  
5200FT)  
105  
105  
620009  
620010  
1
1
1
1
1
1
1
1
106  
111  
112  
113  
114  
115  
116  
117  
118  
119  
120  
*
#8 X1/2 SHEETMETAL SCREWS  
1 1/2 X 1 1/4 BLACK 90 DEGREE ELBOW  
ISOLATION FLANGE SET  
TACO 007 CIRCULATOR  
3/4” X 5” NIPPLE  
3/4” 90 DEGREE ELBOW  
3/4” CLOSE NIPPLE  
3/4” ASME RELIEF VALVE  
3/4” X 4 1/2” NIPPLE  
900130  
950200  
95-061  
95-012  
95-044  
95-057  
95-105  
95-040  
95-102  
95-056  
95-041  
9601630  
2
1
1
1
1
1
1
1
1
1
1
0
2
1
1
1
1
1
1
1
1
1
1
0
2
1
1
1
1
1
1
1
1
1
1
0
2
1
1
1
1
1
1
1
1
1
1
0
2
1
1
1
1
1
1
1
1
1
1
0
2
1
1
1
1
1
1
1
1
1
1
0
2
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
3/4” COUPLING  
3/4” BOILER DRAIN  
CWD FAN EXTENSION HARNESS  
CONTROLS UNIQUE TO CB502 CONTROL SYSTEM  
PART#  
OR  
PART # OR QTY  
CWD060 CWD083 CWD110 CWD138 CWD165 CWD193 CWD220 CWD245  
KEY DESCRIPTION  
QTY  
107  
108  
109  
*
CB502A RELAY BOARD  
REPLACEMENT RELAY FOR CB502A  
RESET PLUG FOR CB502A  
42-502A  
42-503  
42-504  
1
1
3
1
1
3
1
1
3
1
1
3
1
1
3
1
1
3
1
1
3
1
1
3
1
HIGH VOLTAGE HARNESS  
96-1005 96-1005 96-1005 96-1005 96-1006 96-1006 96-1006 96-1006  
9601620 9601620 9601620 9601620 9601625 9601625 9601625 9601625  
9601635 9601635 9601635 9601635 9601635 9601635 9601635 9601635  
*
*
110  
CWD/CB502 TRANSFORMER HARNESS  
CWD LOW VOLTAGE HARNESS  
TRANSFORMER-AT72D1006  
1
1
35-2100  
1
1
1
1
1
1
1
1
CONTROLS UNIQUE TO R8285 CONTROL SYSTEM  
PART#  
OR  
PART # OR QTY  
KEY  
DESCRIPTION  
CWD060 CWD083 CWD110 CWD138 CWD165 CWD193 CWD220 CWD245  
QTY  
1
*
*
*
CWD/R8285 HARNESS #1  
CWD/R8285 HARNESS #2  
BWF HARNESS #4  
9601600 9601600 9601600 9601600 9601605 9601605 9601605 9601605  
9601610 9601610 9601610 9601610 9601615 9601615 9601615 9601615  
9601120 9601120 9601120 9601120 9601120 9601120 9601120 9601120  
1
1
121  
122  
123  
R8285D5001 FAN CENTER  
R8222U1006 RELAY  
R8222 MOUNTING PLATE  
3505555  
3505556  
620102  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
* NOT PICTURED  
72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix A: Special Requirements For Side-Wall Vented Appliances  
In The Commonwealth of Massachusetts  
IMPORTANT  
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR 4.00 and 5.00 for  
installation of side-wall vented gas appliances as follows:  
1. For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment, where  
the bottom of the vent terminal and the air intake is installed below four feet above grade the following  
requirements must be satised:  
a. If there is not already one present, on each oor level where there are bedroom(s), a carbon  
monoxide detector and alarm shall be placed in the living area outside the bedroom(s). The carbon  
monoxide detector shall comply with NFPA 720 (2005 Edition).  
b. A carbon monoxide detector shall be located in the room that houses the appliance or equipment  
and shall:  
i. Be powered by the same electrical circuit as the appliance or equipment such that only one  
service switch services both the appliance and the carbon monoxide detector;  
ii. Have battery back-up power;  
iii. Meet ANSI/UL 2034 Standards and comply with NFPA 720 (2005 Edition); and  
iv. Have been approved and listed by a Nationally Recognized Testing Laboratory as recognized  
under 527 CMR.  
c. A product-approved vent terminal must be used, and if applicable, a product-approved air intake  
must be used. Installation shall be in strict compliance with the manufacturer’s instructions. A copy  
of the installation instructions shall remain with the appliance or equipment at the completion of the  
installation.  
d. A metal or plastic identication plate shall be mounted at the exterior of the building, four feet  
directly above the location of the vent terminal. The plate shall be of sufcient size to be easily read  
from a distance of eight feet away, and read “Gas Vent Directly Below”.  
2. For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment, where  
the bottom of the vent terminal and the air intake is installed above four feet above grade the following  
requirements must be satised:  
a. If there is not already one present, on each oor level where there are bedroom(s), a carbon  
monoxide detector and alarm shall be placed in the living area outside the bedroom(s). The carbon  
monoxide detector shall comply with NFPA 720 (2005 Edition).  
b. A carbon monoxide detector shall :  
i. Be located in the room that houses the appliance or equipment  
ii. Be either hard-wired or battery powered or both; and  
iii. Comply with NFPA 720 (2005 Edition)  
c. A product-approved vent terminal must be used, and if applicable, a product-approved air intake  
must be used. Installation shall be in strict compliance with the manufacturer’s instructions. A copy  
of the installation instructions shall remain with the appliance or equipment at the completion of the  
installation.  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CROWN  
Boiler Co  
Manufacturer of Hydronic Heatings Products  
P.O. Box 14818 3633 I. Street  
PN 980060  
CWDMANV4  
04/09  
Philadelphia, PA 19134  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Coleman Tent 2000002251 User Manual
Compaq Personal Computer SR5109UK User Manual
Cooper Bussmann Switch Electronics Short Circuit Current Rating User Manual
Cornelius Beverage Dispenser 414384 XXX User Manual
Craftsman Lawn Mower 37409 User Manual
Cuisinart Coffeemaker DCC 450CN User Manual
Eaton Electrical Power Supply IM01005012E User Manual
Fisher Price High Chair V3393 User Manual
Furuno Boating Equipment C 500 User Manual
GE Mouse HO97796 User Manual