| 	
		 IMI CORNELIUS INC g One Cornelius Place g Anoka, MN 55303-6234   
					Telephone (800) 238-3600   
					Facsimile (800) 535-4231   
					Installation/Service Manual   
					UC 701 SERIES CONTINUOUS–FLOW   
					ICEMAKER   
					IMPORTANT:   
					TO THE INSTALLER.   
					It is the responsibility of   
					the Installer to ensure that   
					the water supply to the   
					dispensing equipment is   
					provided with protection   
					against backflow by an air   
					gap as defined in   
					ANSI/ASME A112.1.2-1979;   
					or an approved vacuum   
					breaker or other such   
					method as proved effective   
					by test.   
					Water pipe connections   
					and fixtures directly   
					connected to a potable   
					water supply shall be   
					sized, installed, and   
					maintained according to   
					Federal, State, and Local   
					Codes.   
					Part No. 630460150   
					February 2001   
					Revision Date: November 7, 2003   
					Revision A   
					THIS DOCUMENT CONTAINS IMPORTANT INFORMATION   
					This Manual must be read and understood before installing or operating this equipment   
					PRINTED IN U.S.A   
					IMI CORNELIUS INC; 2000–2003   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				TABLE OF CONTENTS (cont’d)   
					Page   
					UPPER NUT AND BEARING ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					18   
					TO REPLACE BEARING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18   
					ELECTRICAL CHECKOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					OVERLOAD CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					COMPRESSOR CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					CAPACITOR CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					19   
					19   
					19   
					19   
					20   
					24   
					THE COMPRESSOR WILL NOT RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					24   
					THE COMPRESSOR STARTS BUT TRIPS REPEATEDLY ON THE   
					OVERLOAD PROTECTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					24   
					24   
					25   
					THE COMPRESSOR RUNS BUT WILL NOT REFRIGERATE . . . . . . . . . . . . . . .   
					WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					LIST OF FIGURES   
					FIGURE 1. CLEARANCE REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					FIGURE 2. ICEMAKER FLOAT ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					FIGURE 3. UPPER NUT AND BEARING ASSEMBLY . . . . . . . . . . . . . . . . . . . . . .   
					FIGURE 4. EXPANSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					FIGURE 5. ADJUSTMENT SCREW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					FIGURE 6. GEARMOTOR ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					FIGURE 7. AUGER AND EXTRUDING HEAD REMOVAL . . . . . . . . . . . . . . . . . .   
					FIGURE 8. SHAFT SEAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					FIGURE 9. OVERLOAD CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					FIGURE 10. COMPRESSOR CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					FIGURE 11. GEAR MOTOR OVERLOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					FIGURE 12. WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					5 
					9 
					12   
					15   
					15   
					17   
					17   
					18   
					19   
					19   
					20   
					22   
					LIST OF TABLES   
					TABLE 1. DESIGN DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   
					3 
					630460150   
					ii   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SAFETY INFORMATION   
					Recognize Safety Information   
					This is the safety-alert symbol. When you see this   
					symbol on our machine or in this manual, be alert to   
					the potentially of personal injury.   
					Follow recommended precautions and safe operating   
					practices.   
					Understand Signal Words   
					A signal word - DANGER, WARNING, OR CAUTION   
					is used with the safety-alert symbol. DANGER identi-   
					fies the most serious hazards.   
					DANGER   
					Safety signs with signal word DANGER or WARNING   
					are typically near specific hazards.   
					WARNING   
					General precautions are listed on CAUTION safety   
					signs. CAUTION also calls attention to safety mes-   
					sages in this manual.   
					CAUTION   
					Follow Safety Instructions   
					Carefully read all safety messages in this manual and on your machine safety signs. Keep safety signs in   
					good condition. Replace missing or damaged safety signs. Learn how to operate the machine and how to   
					use the controls properly. Do not let anyone operate the machine without instructions. Keep your machine in   
					proper working condition. Unauthorized modifications to the machine may impair function and/or safety and   
					affect the machine life.   
					CAUTION: Very high discharges pressure is present in the system. Quick disconnects on   
					your gages will minimize danger and loss of refrigerant.   
					CAUTION: The Unit requires a separate electrical line. See Instruction Manual for proper   
					fuse size.   
					WARNING: There must be adequate clearance around the Icemaker. Allow 25–inches on the   
					front side for service access, 4–inches on side opposite the storage bin, and 4–inches on   
					the back side for air exaust.   
					NOTE: The Unit must be installed per local plumbing and electrical codes. Failure to do so may cause   
					damage to the Unit which would void the factory warranty.   
					NOTE: Using parts other thean genuine factory manufactured parts relieves the manufacturer of all   
					liability. The manufacturer reserves the right to change specifications at any time.   
					1 
					630460150   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				THIS PAGE LEFT BLANK INTENTIONALLY   
					630460150   
					2 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				GENERAL DESCRIPTION   
					TO THE USER OF THIS MANUAL   
					This manual covers the installation and assembly of the Air–Cooled or Water–Cooled Model UC700 Icemaker   
					with the Model UC150 Dispenser. Refer to Table of Contents for page location of detailed information pertaining   
					to questions that may arise during installation or operation of this equipment.   
					DESCRIPTION   
					The UC700 is a chuncklet Icemaker designed to be installed under a counter adjacent to an Ice Dispenser or an   
					Ice Storage Bin. The Icemaker will deliver ice to either the left or right side. The Icemaker requires a 12–inch by   
					12–inch opening at the lower front of the Unit for air intake. A minimum of 1.5 sq. ft. opening must be provided   
					out the left or right side and the rear of the machine for air exaust.   
					CLAIMS INSTRUCTIONS   
					Claims: In the event of shortage, notify the carrier as well as IMI Cornelius immediately. In the event of dam-   
					age, notify the carrier. IMI Cornelius is not responsible for damage occurring in transit, but will gladly   
					render assistance necessary to pursue your claim. Merchandise must be inspected for concealed dam-   
					age within 15 days of receipt.   
					WARRANTY REFERENCE INFORMATION   
					Warranty Registration Date   
					(to be filled out by customer)   
					Unit Part Number:   
					Serial Number:   
					Install Date:   
					Local Authorized   
					Service Center:   
					DESIGN DATA   
					Table 1. Design Data   
					Unit Model Number:   
					UC700–A Series Continuous–Flow Icemaker (Air–Cooled)   
					UC700–W Series Continuous–Flow Icemaker (Water–Cooled)   
					Unit Overall Dimensions:   
					Height   
					Width   
					Depth   
					27 inches   
					13.7 inches   
					25.5 inches   
					Clearances Dimensions Required:   
					Front Side Service Access (Removable front panel to allow removal of   
					Unit)   
					25 inches   
					Side Opposite Storage Bin for Air Exaust   
					Rear for Air Exaust   
					4 inches   
					4 inches   
					Weights:   
					Shipping Weight   
					184 pounds   
					3 
					630460150   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Table 1. Design Data (cont’d)   
					Water Supply–Water inlet fitting is 1/4–inch SAE flare located at the top front of the Unit. The Unit is designed   
					to   
					operate on water pressure between 10 PSI and 90 PSI.   
					Drain Overflow Line (Located at rear of the Unit)   
					Ambient Operating Temperature   
					3/8–inch Flexible Tubing   
					40° F to 100° F   
					Electrical:   
					Unit Electrical Rating   
					208/230 VAC, 60 Hz, 11.3 Amps,   
					Single Phase   
					Recommended Electrical Supply   
					208/230 VAC, 60 hz, 20 Amps   
					Dedicated 3–Wire   
					Grounded Circuit   
					SPECIFICATION CHART   
					Refrigerant   
					Oz. Type   
					Models   
					Condensing   
					Unit   
					VAC   
					HZ   
					PH   
					Wire   
					Comp.   
					RLA   
					Fan   
					Amps   
					GRMTR   
					Amps   
					Circuit   
					Fuse   
					UC701–A   
					UC701–W   
					Air Cooled   
					Water Cooled   
					208/230   
					208/230   
					60   
					60   
					1 
					1 
					2 
					2 
					7.7   
					7.7   
					1.6   
					N/A   
					2 
					2 
					13   
					13   
					R404A   
					R404A   
					20   
					20   
					UC700   
					650   
					600   
					550   
					500   
					450   
					400   
					350   
					90   
					80   
					70   
					60   
					50   
					Water Temperature Deg. F   
					–50 –70 –90 –100   
					Air Temperature Deg. F   
					630460150   
					4 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				FIGURE 1. CLEARANCE REQUIREMENTS   
					5 
					630460150   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				THIS PAGE LEFT BLANK INTENTIONALLY   
					630460150   
					6 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				INSTALLATION   
					PRE–INSTALLATION   
					Freight Damage Claim   
					The delivery of your equipment (Frieght Company, Distributor, or dealer) is responsible for loss or damage of   
					your shipment. All claims must be filed with the deliverer of your equipment. Please follow the steps below to   
					determine if your shipment is satisfactory or if a claim must be filed:   
					1. Check the number of products delivered against the number of products listed on the delivery receipt.   
					Should the totals not match, have the driver note all errors on both copies and both you and the driver sign   
					and date said notation.   
					2. Inspect all cartons for visible damage. Open and inspect as required before the driver leaves and have him   
					or her note any damage on the receipts. All damaged claims must be inspected within 15 days of delivery.   
					Notify your carrier immediately if concealed damage is found after delivery.   
					3. Should concealed damage be found when the product is unpacked, retain the packing material and the   
					product and request an inspection from the deliverer.   
					4. All claims for loss or damage should be filed at once. Delays in filing will reduce the chance of achieving a   
					satisfactory resolution to the claim.   
					Counter   
					1. A flat and level counter space sufficiently strong to support the weight of the Dispenser and the Icemaker.   
					The Icemaker may be installed on the left or the right side of the Dispenser.   
					2. General Requirements:   
					A. The front of the Icemaker must be free of obstructions.   
					B. Allow a 4–inch minimum clearance between exaust side of the Icemaker and adjacent equipment.   
					C. A louvered front panel (12–inches X 12–inches) aligned with the air inlet of the Icemaker and ade-   
					quate ventilation (1.5 Sq. feet opening) in the counter for exaust air.   
					D. A removable panel in the counter face (from 2–inches below the top of the counter to the floor, a mini-   
					mum of 17–inches wide) to allow removal of the Icemaker.   
					Electrical   
					Two separate 20 amp, 120VAC, 60 Hz electrical circuits.   
					Drain   
					One drain beneath the counter at floor level which will accomodate both the drain from the Icemaker and the   
					Dispenser.   
					7 
					630460150   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				INSTALLATION   
					1. Keep unit in the upright position, remove carton and pallet from the Icemaker and inspect for damage. If   
					any damage is found, file a claim with carrier immediately.   
					2. Locate startup card either on outside of container or on plastic liner. Fill in proper information and send one   
					to factory, and other copy to distributor. Postage is prepaid.   
					3. Install the Dispenser first, following installation instructions supplied with the Dispenser.   
					4. Remove the two hole plugs from the side of the dispenser.   
					A. The plugs are pressed in and sealed with a silastic sealant. To remove pry the outside cap off and   
					then press the inside plug into the bin. Discard both plugs.   
					B. Install the icemaker alignment brackets (Supplied with icemaker) to the dispenser (See Figure 2).   
					5. Install the Icemaker:   
					A. Install the icemaker alignment brackets (Supplied with icemaker) to the icemaker (See Figure 2).   
					B. Roll the Icemaker into the cabinet alongside the Dispenser.   
					C. Level and align the icemaker to the dispenser using the four level adjustment bolts located on the low-   
					er front of the Icemaker.   
					D. Install the locking bolt on the lower front of the icemaker.   
					E. Connect drain, power and water.   
					6. Install transport tube:   
					A. Insert the ice transport tube through the bin into the transport elbow on the Icemaker. (Note: The ice-   
					maker is equipped with a safety switch located at the base of the elbow, this switch will prevent the   
					icemaker from running if the elbow is not properly installed).   
					B. Align the nylon lock screw on the elbow with the recess on the tube. Install lock screw.   
					7. Connect bin thermostat:   
					A. Locate bin thermostat cable supplied with the icemaker (Black cable) and connect to electrical box on   
					the UC700 and the receptacle on the side of the dispenser.   
					ATTACH TO BIN   
					ATTACH TO BIN   
					RIGHT SIDE INSTALL   
					LEFT SIDE INSTALL   
					FIGURE 2. SIDE BRACKET INSTALLATION   
					630460150   
					8 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				INITIAL START UP, CHECKS AND ADJUSTMENT INSTRUCTIONS   
					NOTE: Do not start Icemaker before completing installation steps on pages 7 and 9.   
					Turn on water supply (if Icemaker is water cooled turn water on to condenser also) turn on main power switch   
					(located on top of electrical box), and make the following system checks:   
					NOTE: If Icemaker will not start be sure water reservoir is full. Low water safety control must be prop-   
					erly adjusted to start and shut down the Icemaker. If water level drops below bottom of reservoir, the   
					Icemaker must shut down. Adjustment is made by moving magnet up or down.   
					Water Level—If necessary adjust float by bending float arm up or down as needed, push float assembly down   
					until Icemaker stops running. Release float and Icemaker will restart. Keep water in reservoir at level line while   
					the Icemaker is in operation. See Figure 3   
					Low Water Safety Control—Adjust magnet by bending magnet arm as needed to shut unit down if water level   
					drops below bottom of reservoir.   
					Bin Control—Place ice around probe, unit should shut down in one minute. Remove ice from around probe,   
					unit should start in two minutes.   
					NOTE: For altitudes over 1000 feet above sea level, adjust range screw (behind end cover). Half turn   
					max. raises setting 4_F approx.   
					FIGURE 3. ICEMAKER FLOAT ASSEMBLY   
					Water modulating valve (water cooled units only)—Opening point of condenser water modulating valve   
					should be set to maintain proper operating pressure in the refrigeration system high side. (see chart on   
					page 13). Closing point of valve should be set low enough to close valve during compressor stand by periods.   
					To raise, turn counterclockwise, to lower turn clockwise.   
					9 
					630460150   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				THIS PAGE LEFT BLANK INTENTIONALLY   
					630460150   
					10   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				GUIDE TO SERVICE   
					WARNING: Disconnect electrical power to the Icemaker to prevent personal injury before   
					attempting any internal maintenance. Only qualified personnel should service internal   
					components or electrical wiring.   
					ICEMAKER CLEANING AND SANITIZING PROCEDURES   
					Do not use any of the ice made during cleaning operations.   
					Clean and sanitize ice storage area when cleaning icemaker.   
					1. Turn machine off.   
					2. Shut off water supply.   
					3. Remove ice from storage bin.   
					4. Mix approved cleaner (2 gallons as directed). Recommended cleaner: Calgon Corp. of Virginia Chemi-   
					cals, ice machine cleaner. Mixture: 3-1/3 ounces per gallon of water.   
					5. Clean auger assembly and ice transition tube in a sink using cleaner mixture and reinstall in icemaker.   
					6. Turn machine on and add cleaner solution to water level control until 2 gallons have been used.   
					7. Turn on water supply and run machine for 15 minutes.   
					8. Turn off machine and remove all ice.   
					9. Sanitize using household liquid bleach (50 ppm chlorine). Mixture: 1 fluid ounce per gallon room tempera-   
					ture water. 2 minute exposure time.   
					10. Sanitize auger assembly and ice transition tube in a sink using sanitizing solution and reinstall in icemaker.   
					11. Fill icemaker with sanitizer by slowly pouring solution into water feed reservoir until full. Solution will drain   
					through overflow tube. Do not run machine. Allow to air dry.   
					12. If icemaker is used in conjunction with ice dispenser or storage bin, follow manufacturer’s recommended   
					cleaning instructions at this time.   
					MAINTENANCE   
					Preventive maintenance can increase the trouble free life of your icemaker. Many authorized service agencies   
					offer service contracts for your icemaker. Contact your local distributor for further information.   
					Monthly   
					1. Clean the condenser. Use a brush, vacuum cleaner or blow from inside with air or CO2 gas.   
					2. Inspect water feed reservoir at lease once a month until a definite pattern for cleaning and sanitizing has   
					been established.   
					Quarterly   
					This is the maximum period of time between cleaning and sanitizing the icemaker. In addition to recommended   
					monthly procedure, and if a more frequent cleaning and sanitizing pattern has not been established, unit must   
					be cleaned and sanitized.   
					630460150   
					11   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Semi–Annually   
					Semi-Annually in addition to all previously established service procedures perform the following:   
					1. Check for water leaks in tube connections, water fittings and lower Icemaker water seal.   
					2. Check drain tubes for clogs and aged tubes. Replace if tubes are stained or brittle.   
					3. Check for signs of condensation. Clean where necessary and replace insulation properly.   
					4. Check safety circuits for proper operation.   
					5. Check refrigeration system (see page 13).   
					6. Check unit for abnormal noise. Tighten machine and cabinet screws, if necessary.   
					7. Check white upper bearings on auger assembly. If bearings are less than 1/16Ȃ thick, replace. See Figure 4   
					REPLACE   
					OK   
					1/16Ȃ   
					1/16Ȃ   
					OK   
					REPLACE   
					FIGURE 4. UPPER NUT AND BEARING ASSEMBLY   
					WATER LEVEL CONTROL   
					How Water Level Control Works   
					When water is introduced through the inlet fitting the float rises. the float pushes against a lever which in turn   
					forces the poppet assembly against the inlet fitting valve seat which seals the water off. See Figure 3 Before the   
					water inlet is sealed the safety switch is operated. In the event of a water failure the float would drop down and   
					operate the safety switch to shut off the machine.   
					If water level control will not shut off and seal at level as indicated, be sure inlet pressure does not exceed rec-   
					ommended factory operating range.   
					Under ordinary circumstances adjustment should not be necessary providing it was properly adjusted when unit   
					was installed or relocated. If, however, the control becomes inoperative, repair or replace. See Start-Up Adjust-   
					ment, page 9.   
					Purpose   
					1. To automatically maintain proper water level in the evaporator when unit is running and making ice.   
					2. A safety switch is operated in the event of an interruption in water supply. The switch shuts off the electrical   
					power to the icemaker and its refrigeration system. Switch will reset as soon as cause of water failure has   
					been corrected and proper water level in icemaker has again been reached.   
					630460150   
					12   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				3. The transparent bowl not only provides a visible check of water level, but also is a good guide to the inter-   
					nal conditions which exist within the icemaker assembly itself. (See Cleaning Procedure.)   
					To Replace Water Level Control   
					1. Shut off the water supply. Shut off the main power switch or unplug the ice dispenser from electrical outlet.   
					2. Remove the flexible tubing from bottom of water level control and drain water from water level control and   
					evaporator.   
					3. Remove flexible tubing at bottom of water level bowl connected to the overflow.   
					4. Hold water inlet fitting with proper tool to prevent it from rotating when disconnecting the water inlet.   
					5. Remove wing nut holding water control to its mounting bracket. Control can be removed by lifting straight   
					up.   
					To Replace Water Level Safety Switch   
					1. Shut off main power switch or unplug the ice dispenser from electrical outlet.   
					2. Unplug molex connector connecting switch to electrical box.   
					3. Remove the 2 screws anchoring the water level safety switch to the bottom of the water level control   
					mounting bracket.   
					REFRIGERATION SYSTEM   
					NOTE: Thermostatic Expansion Valve No Adjustment   
					+ 10 Lbs Discharge Pressure   
					WATER TEMPERATURE   
					A 
					I 
					40°   
					174   
					202   
					230   
					265   
					300   
					328   
					65°   
					177   
					205   
					233   
					269   
					304   
					334   
					90°   
					180   
					208   
					236   
					272   
					307   
					340   
					50°   
					60°   
					70°   
					80°   
					90°   
					100°   
					R 
					T 
					E 
					M 
					P 
					REFRIGERATION SYSTEM ADJUSTMENTS   
					A complete understanding of the icemaker and hermetic refrigeration system is necessary before any adjust-   
					ments are made. The refrigeration technician must use high and low side pressure readings, water and air tem-   
					peratures, plus general conditions of cleanliness to assess the refrigeration system status when making any   
					adjustments.   
					All icemaker products are tested and adjusted at the factory prior to shipment where the ambient temperature   
					ranges from 65_ to 90_F, depending on the season of the year.   
					Whenever a new icemaker product is initially installed and started-up, it is imperative that the start-up operation   
					make the following checks and/or readjustments for local conditions.   
					630460150   
					13   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EXPANSION VALVE   
					You will find a thermostatic expansion valve on icemakers, which is used to control the amount of refrigerant   
					flowing through the evaporator. Improperly installed or defective expansion valves may cause low production,   
					soft ice, squeaking from evaporator and excessive load inside evaporator.   
					By using general refrigeration system troubleshooting along with the pressure charts you can easily determine   
					whether or not the expansion valve is working properly.   
					ADJUSTMENT AND TROUBLESHOOTING   
					When troubleshooting the expansion valve you must first be sure you have adequate water flowing into evapo-   
					rator, a clean condenser, unit is properly ventilated, and system is properly charged and free from any restric-   
					tions. Also be sure compressor is operating properly.   
					Second, take reservoir water temperature and air temperature from condenser inlet and determine at what pres-   
					sure unit should be running. Machines are equipped with thermostatic valves, there is NO adjustment. If correct   
					pressure cannot be obtained, first be sure system has time to stabilize 10-15 minutes. Second, be sure sensing   
					bulb is located at 12:00 position on outlet side of evaporator about 3-4 inches away from evaporator and be sure   
					to insulate well and clamp tightly to tubing. If system pressures are still not adequate, take a second water and   
					air temperature reading and go over other parts of system for possible problems. If proper charge is question-   
					able evacuate and recharge to nameplate and leak check. If valve still malfunctions replace valve.   
					When replacing valve be sure to bleed refrigerant gas from low side port so as not to lose refrigerant oil. Use   
					general refrigerant system practices when replacing and recharging unit. After new valve is in place, go through   
					previous monitored adjustments and troubleshooting to be sure valve is functioning properly.   
					NOTE: Units with thermostatic expansion valve—The valve is located on bottom refrigerant line. Sens-   
					ing bulb is located on top refrigerant line. On water cooled units adjust condenser modulating valve   
					before troubleshooting expansion valve.   
					CAUTION: Very high discharge pressure is present in system. Quick disconnects on your   
					gauges will minimize danger and loss of refrigerant. Comply with federal regulations for   
					reclaiming refrigerant.   
					CONDENSER MODULATING VALVE   
					The reason for using a water modulating valve is to supply the correct amount of water to the condenser. and to   
					maintain a proper operating pressure to refrigeration system high side.   
					The flow of water through the valve is increased as the high side pressure rises and is decreased as high side   
					pressure lowers.   
					To calibrate the amount of water flow with the refrigeration system high side pressure, turn adjustment screw   
					located on end of valve opposite of bellows. See Figure 6. Turn screw counterclockwise to raise opening point   
					or clockwise to lower opening point. Opening point of valve should be set to maintain proper operating pressure   
					in refrigeration system high side. Refer to Pressure Chart on page 3. Closing point of valve should be set low   
					enough to close valve during compressor stand-by periods.   
					NOTE: Cold water will absorb heat faster than warm water. The water flow will therefore automatically   
					increase as inlet temperature increases.   
					630460150   
					14   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SIGHT   
					GLASS   
					THERMOSTATIC   
					EXPANSION VALVE   
					FIGURE 5. EXPANSION VALVE   
					FSCREW   
					CONDENSER MODULATING VALVE REMOVAL   
					1. Disconnect power to unit, then shut off water supply to condenser and evacuate refrigerant from system.   
					2. Remove inlet water line from Condenser Modulating Valve. Also remove tube from high side refrigerant   
					line.   
					3. Remove Condenser Modulating Valve and bracket from unit.   
					4. Remove valve from bracket.   
					5. Replace Condenser Modulating Valve by reversing Steps 2 thru 4. Then pull system into vacuum.   
					6. Charge unit with proper amount of refrigeration.   
					7. Turn power and water on to unit.   
					8. With unit running, adjust modulating valve to proper setting.   
					9. Go through a complete system check.   
					BIN CONTROL   
					The type of bin control used on all UC Models is thermostatically controlled. The switch itself is inside the elec-   
					trical box of the Dispenser and can be serviced from the front of the unit. The cap tube bulb is located in the   
					thermostat well directly under the ice inlet.   
					To test switch, disconnect power to unit and remove one wire from switch. Connect both leads of your ohmme-   
					ter to the Bin Control Switch terminals. With control bulb at room temperature ohmmeter should read “Closed   
					Circuit”.   
					Now cover the control bulb with ice, within 1 minute switch should “click” and ohmmeter should read “Open Cir-   
					cuit.” The Bin control is in electrical series with a 24 volt transformer located in the ice dispenser and a 24 volt   
					control relay located in the Icemaker.   
					The Bin 24 volt control relay is in electrical series with coil on antifreeze relay along with the low water safety. If   
					unit is water cooled, the condenser high pressure cut out is also in series.   
					The Control Switch is held in place inside electrical box by 2 screws. Control bulb is positioned under ice chute   
					and can be replaced by removing the capillary from the thermostat well.   
					The most important thing to remember when replacing probe is to be careful not to cut or kink probe and be   
					sure sensor bulb is located in a position to shut unit down before ice reaches ice chute.   
					This icemaker is equipped with a safety ice level sensor. This sensor control is located on top of theevaporator.   
					This switch is also in electrical series with the anti-freeze relay and other safety circuitry.   
					630460150   
					15   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				GEARMOTOR   
					The gearmotor is equipped with a start relay and a manual reset overload.   
					When current is applied, the relay energizes and completes the circuit to the start winding. The motor reaches a   
					predetermined speed and the relay drops out, disconnecting the start winding. The run winding remains in the   
					circuit as long as current is applied.   
					The purpose of the overload is to automatically shut off the motor in the event of a mechanical bind of the trans-   
					mission, an overload condition within the evaporator or an electrical malfunction. It does this by sensing amper-   
					age draw. If the motor stalls the start relay would energize and stay energized. The amperage would surge 5 to   
					6 times greater than the normal draw. In this event the overload would shut off the transmission in 4 to 8 sec-   
					onds.   
					If the motor is subjected to an abnormal load, but does not reach a stall condition, the overload will react, but   
					over a greater period of time. The reaction time depends upon the amperage to which it is subjected.   
					The overload, through the safety circuit, also shuts off the compressor.   
					GEARMOTOR   
					OVERLOAD TRIPPED   
					Check water level control   
					and evaporator water tube   
					for line build-up restrictions.   
					NO   
					YES   
					CAUTION   
					evaporator and   
					auger before   
					resetting overload.   
					Clear ice from   
					CLEAN   
					See Instructions.   
					Reset overload.   
					IMPORTANT   
					Icemaker   
					runs.   
					Will not   
					Reset.   
					Resets but   
					motor does   
					not run.   
					Icemaker runs when   
					reset but problem has   
					not been found.   
					Continue checking for   
					overload as follows to   
					guard against future   
					problems.   
					Short run. Trips   
					again in 2   
					minutes. Check   
					gearmotor circuits.   
					Overload   
					hot try   
					again.   
					Resets but   
					motor does   
					not run.   
					Will not   
					reset.   
					Replace   
					overload.   
					Check   
					gearmotor   
					circuits.   
					OVERLOAD GUIDE   
					ELECTRICAL:   
					S 
					S 
					S 
					High or low voltage. Weak power lines can cause overloads on icemakers restarts.   
					High running current (2.4amps or above). Check motor circuits and start relay.   
					Auger delay failed.   
					ICEMAKER   
					S 
					S 
					S 
					Mechanical parts worn. Scored evaporator or auger. Worn thrust bearing.   
					Icemaker not turning off. Failed ice level control.   
					Over compression. Low water inlet temperature. Restrictions in water line from reservoir.   
					REFRIGERANT   
					S 
					S 
					S 
					Contaminated charge or bad compressor.   
					Low charge or gas leak.   
					Low suction pressure. Improper expansion valve. Sensing bulb location or insulation   
					and/or defective expansion valve.   
					MOTOR CHECK   
					The resistance readings on the winding will be between 5 to 25 ohms. A meter capable of these low readings   
					must be used. The start relay cover must be removed. (See Figure 7).   
					If no continuity on start or run winding test, replace gearmotor. If continuity on grounded motor test, replace   
					gearmotor.   
					630460150   
					16   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				START RELAY   
					1. Check between “2” and “4” on relay (with relay unplugged). If there is continuity replace the relay, as the   
					relay contacts should be open.   
					2. Check between “3” and “4” on relay, if no continuity replace the relay.   
					FIGURE 7. GEARMOTOR ASSEMBLY   
					TO REPLACE GEARMOTOR ASSEMBLY   
					1. Disconnect the icemaker from the electrical power source.   
					2. Disconnect the transmission cable from the electrical box.   
					3. Remove the 4 hex head bolts securing the evaporator to the top of the transmission.   
					4. Remove the 4 bolt’s holding the transmission and bracket to frame base, while supporting the weight of the   
					evaporator. Remove the transmission from the unit.   
					5. When replacing the transmission, it may be necessary to rotate the auger back and forth to align the motor   
					shaft and auger.   
					AUGER NUT   
					AUGER   
					BEARING NYLON   
					BEARING DELRIN   
					“D” DRIVE   
					GROOVE   
					EXTRUDING   
					HEAD   
					ANTI–ROTATION   
					RIB – 3 PLACES   
					FIGURE 8. AUGER AND EXTRUDING HEAD REMOVAL   
					630460150   
					17   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				AUGER AND EXTRUDING HEAD REMOVAL   
					1. Disconnect unit from power supply.   
					2. Remove storage container cover and put aside.   
					3. Turn off water supply to icemaker.   
					4. After ice has melted from head take hold of the auger nut and lift straight up to disengage from icemaker.   
					5. When replacing the auger assembly, make certain that both the auger engages the output shaft drive and   
					the extruding head ribs engage the evaporator tube. (See Figures 8 )   
					E–RING   
					WASHER, PLAIN FLAT   
					SHAFT SEAL   
					MOUNT, SHAFT   
					SEAL   
					SEAT, SHAFT SEAL   
					GEARMOTOR   
					FIGURE 9. SHAFT SEAL   
					INSTALLATION AND SHAFT SEAL REPLACEMENT (See Figure 9)   
					1. Place shaft seal locator seat and shaft seal mount over gearmotor output shaft and push down until shaft   
					seal seat and shaft seal mount rest flush on top of gearmotor.   
					2. Place rubber coated ceramic seal (important: ceramic face up) over output shaft and push down until seal   
					nest in recess of shaft seal mount. (lubricate rubber on ceramic seal with rubber lubricant).   
					3. Place shaft seal with carbon face down (spring up) over output shaft and push (gently) downward until seal   
					rests on carbon face of the output shaft seal.   
					4. Place flat washer over output shaft and let rest on the output shaft seal. Push down on the washer com-   
					pressing the spring on the output shaft seal. While holding the seals (down) in place slide the E-ring into   
					the groove on the output shaft.   
					UPPER NUT AND BEARING ASSEMBLY   
					The upper white bearing located on top of the auger is used to absorb the force between the auger and extrud-   
					ing head.   
					NOTE: The bearings are 3/32Ȃ thick. When they wear below 1/16Ȃ they should be replaced. Bearings to   
					be inspected for wear during quarterly maintenance. (See Figure 4)   
					To Replace Bearing   
					1. Disconnect unit from electric power.   
					2. Remove top panels.   
					630460150   
					18   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				3. Remove Dispense Tray Cover.   
					4. Use an open end wrench on auger nut connected to bearing and turn counterclockwise to remove   
					assembly.   
					5. Remove worn bearings. Replace with new bearings and then reinstall assembly.   
					NOTE: If auger turns with nut, remove cover on top of gearmotor stator and hold motor while loosen-   
					ing nut.   
					FIGURE 10. OVERLOAD CHECK   
					FIGURE 11. COMPRESSOR CHECK   
					ELECTRICAL CHECKOUT   
					1. Be sure the unit is disconnected from the power source. Remove the compressor electrical box cover.   
					Check for obvious damage and loose wires.   
					2. Disconnect the fan motor leads. Since capacitors store energy, short the capacitor with a screwdriver. This   
					will prevent shocks.   
					3. Disconnect the compressor terminal wires.   
					OVERLOAD CHECK (See Figure 10)   
					1. Using a volt-ohmmeter check the continuity across the overload, contact #1 and #3. If none, wait for unit to   
					cool down and try again. If still no continuity, the overload protector is defective and should be replaced.   
					COMPRESSOR CHECK (See Figure 11)   
					The resistance readings on the windings will be between 0.25 to 10.00 ohms, a meter capable of these low   
					readings must be used.   
					1. Check between “C” and “R.” Replace the compressor if there is no continuity as the run windings are open.   
					2. Check between “C” and “S.” Replace the compressor if there is no continuity as the start windings are   
					open.   
					3. Check between “C” and “R” or “S” and the shell of the compressor. If there is continuity, replace the com-   
					pressor as the motor is grounded.   
					4. Check between screw terminal on the overload and “C” on the compressor. Check and repair the lead or   
					connections if there is no continuity.   
					CAPACITOR CHECK   
					1. Check or replace start capacitor, disconnect bleed resistor before checking for shorted capacitor.   
					2. Check or replace run capacitor (if supplied) check for shorted capacitor or either terminal grounded to case.   
					630460150   
					19   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				FIGURE 12. GEAR MOTOR OVERLOAD   
					SAFETY CONTROLS   
					Your icemaker unit has several safety and control devices incorporated into its design.   
					WARNING: None of the below described devices should ever be “bypassed” to allow the   
					unit to function.   
					The safety and control system shut-off devices are:   
					1. Low water shut off reed switch located in icemaker float assembly. (Automatic reset type.)   
					See Figure 3   
					2. Gearmotor thermal overload, manual reset type (red button on motor). See Wiring Diagram Figure 13.   
					3. Compressor thermal overload, automatic reset type. See Figure 10   
					4. Anti-freeze relay and associated circuit. See Wiring Diagram Figure 13.   
					5. Main service switch located on top of the control box. See Wiring diagram Figure 13.   
					6. Bin Control.   
					7. High pressure cut out (water cooled only).   
					630460150   
					20   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				GUIDE TO GOOD ICE   
					CUSTOMER   
					COMMENTS   
					CHECK ICEMAKER   
					LOCATION CONDITIONS   
					FIRST   
					CHECK ICE MAKER   
					“It runs but the ice is   
					too soft.”   
					S Proper air flow for condens-   
					S Use gauges for checking   
					suction and head   
					ing system.   
					pressures. See manual   
					for correct reading and   
					conditions. Check frost   
					line and sight glass.   
					“The icemaker is not   
					S Location too close to high   
					units such as coffee urns,   
					deep fryers, grills, etc.   
					producing enough ice.”   
					“The ice is too wet.”   
					S Supply water conditions   
					S Check water level for   
					proper adjustment and   
					restrictions. See   
					Manual.   
					Water too warm   
					(above 90_F).   
					Water artificially softened   
					above 262 ppm sodium chlo-   
					ride.   
					S Check evaporator   
					assembly for worn   
					parts, bearings, scored   
					evaporator and auger,   
					bad expansion valve.   
					etc.   
					Normal water supply too high   
					in total dissolved solids   
					(above 500 PPM).   
					“It makes too much   
					noise.”   
					(With this comment   
					the ice is usually   
					extremely hard and   
					larger than normal.)   
					S Check to see if noise   
					objection is normal fan and   
					air flow noise.   
					S Check for loose parts   
					and screws rattling.   
					S Check evaporator   
					assembly for worn   
					parts, bearings, scored   
					evaporator and auger,   
					bad expansion valve,   
					etc.   
					Over   
					Compression   
					S Supply water conditions.   
					Water too cold (below   
					50_F). (Possibly running   
					from pre-cooler.)   
					S Obstructions partially   
					blocking ice exit from top of   
					evaporator.   
					S Check fan and fan shroud.   
					630460150   
					21   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				FIGURE 13. WIRING DIAGRAM   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				TROUBLESHOOTING CHART – ICEMAKER NOT OPERATING   
					LOW WATER SAFETY   
					ICEMAKER RUNS BUT   
					GEARMOTOR OVERLOAD   
					TRIPPED   
					NO POWER   
					ICEMAKER OPERATING BUT   
					SOFT ICE   
					SWITCH OPEN   
					DOES NOT MAKE ICE   
					Remote condenser   
					units only   
					Condenser fan running   
					Check water level control   
					and evaporator water tube   
					for lime build up restriction.   
					Check electrical wiring in con-   
					trol box for loose connec-   
					tions.   
					Check for failed service   
					switch or relay.   
					Check power to machine.   
					but compressor not running   
					Check bin switch   
					Check line voltage.   
					Check compressor winding   
					& components.   
					Check that water is turned on.   
					Check for restriction in water line.   
					Check incoming water pressure   
					(minimum 10 lbs.).   
					Remote condenser   
					not running.   
					Yes   
					No   
					No   
					Yes   
					Check water safety switch.   
					Evaporator water tube   
					may have an air bubble.   
					Clear air bubble from   
					tube.   
					High pressure   
					Check electrical   
					Check power   
					to condenser.   
					Clean all related   
					drain lines.   
					Refer to guide   
					to Good Ice in   
					service manual.   
					CAUTION   
					Clear ice from   
					evaporator and   
					auger before re-   
					setting over-   
					load.   
					CLEAN   
					see   
					instructions.   
					switch open or   
					wiring in control box   
					cycling on and off.   
					for loose connections.   
					High suction pressure   
					Low suction pressure   
					(20 lbs. or below).   
					(30 lbs. or above).   
					Reset   
					overload.   
					Head   
					Pressure   
					high.   
					TXV not   
					operating   
					properly.   
					Suction line   
					not   
					insulated.   
					TXV bulb   
					lost charge.   
					Discharge   
					king valve   
					partially   
					Non-condensible   
					in system.   
					Too much   
					refrigerant in   
					system.   
					Condenser   
					fan not   
					running.   
					Condenser   
					dirty or   
					Valve   
					Bulb   
					loose.   
					Bulb   
					uninsulated.   
					Replace valve   
					evacuate and   
					recharge.   
					restricted.   
					stuck   
					Icemaker runs   
					closed.   
					Reset but   
					motor does   
					not run.   
					Will not   
					reset.   
					open.   
					Replace   
					valve.   
					Clean   
					and   
					Clean and   
					insulate.   
					tighten.   
					Evacuate and   
					recharge system.   
					Clean condenser.   
					Check electrical circuit   
					to fan motor.   
					Check fan motor.   
					IMPORTANT   
					Short run trips   
					again in 2 min-   
					utes. Check gear-   
					motor circuit.   
					Check   
					gearmotor   
					circuit.   
					Overload   
					hot try   
					again.   
					Open   
					valve   
					Icemaker runs when reset   
					but problem has not been   
					found.   
					Continue checking for   
					overload as follows to   
					guard against future   
					problems   
					Low pressure switch open   
					or cycling on and off.   
					Will not   
					reset   
					replace   
					overload   
					Remote condenser   
					units only   
					Low on   
					refrigerant.   
					Plugged   
					liquid line   
					dryer.   
					Restricted   
					liquid line.   
					Plugged or   
					faulty TXV.   
					Icemaker   
					froze up.   
					Check if   
					auger is   
					turning.   
					Check for   
					leaks.   
					LAC not operating   
					properly (minimum   
					discharge pressure   
					180 lbs.).   
					Replace   
					dryer.   
					Evacuate   
					and   
					recharge   
					system.   
					Check for   
					kinks or   
					damage to   
					liquid line.   
					Replace   
					valve.   
					Evacuate   
					and   
					recharge   
					system.   
					OVERLOAD GUIDE   
					ELECTRICAL   
					High or low voltage weak power lines can cause overloads on icemaker restarts   
					High running current. Check motor circuits and start relay – Auger delay failed.   
					ICEMAKER   
					Mechanical parts worn. Scored evaporator or auger. Worn thrust bearing.   
					Ice maker not turning off. Failed ice level control.   
					Over compression. Low water inlet temperature. Restriction in water line from   
					reservoir.   
					No   
					REFRIGERANT   
					Replace LAC valve,   
					evacuate and   
					recharge system.   
					Contaminated charge or bad compressor.   
					Low charge or gas leak.   
					Low suction pressure. Improper expansion valve sensing bulb. Location or insulation   
					and/or defective expansion valve   
					Check if extruding   
					head is down in   
					evaporator tube.   
					Check drive on   
					gearmotor.   
					Check gears in   
					gearbox.   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				TROUBLESHOOTING   
					IMPORTANT: Only qualified personnel should service internal components or electrical wiring.   
					TROUBLESHOOTING COMPRESSORS   
					Trouble   
					Probable Cause   
					Remedy   
					Basically the compressor problems can be narrowed down to three areas of checkout.   
					THE COMPRESSOR WILL   
					NOT RUN   
					A. No voltage to the compressor   
					terminals.   
					A. Check circuit.   
					B. Low voltage.   
					B. Below 90% of nameplate rated   
					voltage.   
					C. Problems in the compressor   
					electrical circuit.   
					C. See electrical checkout   
					instructions.   
					THE COMPRESSOR STARTS   
					BUT TRIPS REPEATEDLY ON   
					THE OVERLOAD   
					A.   
					A. Check for proper fan operation   
					and clean condenser.   
					B.   
					B. Check the compressor suction   
					and discharge pressures.   
					PROTECTOR   
					C. Voltage.   
					C. Voltage should be within 10% of   
					the rated nameplate voltage.   
					D. High compressor amperage   
					draw.   
					D. It should never exceed 120% of   
					the rated nameplate amperage.   
					See electrical checkout   
					instructions.   
					THE COMPRESSOR RUNS   
					BUT WILL NOT   
					REFRIGERATE   
					A. Compressor not working.   
					A. Check the compressor suctions   
					and discharge pressures. See   
					chart on page 13.   
					24   
					630460150   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				IMI CORNELIUS   
					CERTIFICATE OF WARRANTY   
					TWO YEAR LIMITED ICE EQUIPMENT WARRANTY   
					IMI Cornelius warranty to the original commercial purchaser/user, that any commercial product of its manufacture bearing the name Cornelius will   
					be free from defect in material and/or factory workmanship, and that if properly installed, maintained, and serviced in accordance with the Service   
					Manual furnished with the product, it will perform adequately under normal use. This product warranty shall be effective for a period of two years   
					from the date of original installation of 27 months from the date of original shipment by IMI Cornelius, whichever period elapses first, provided the   
					warranty registration card is completed and returned to IMI Cornelius within 30 days from the date of installation.   
					IMI Cornelius obligation under this warranty is limited to the repair or replacement, including reasonable labor charges, of any part of parts which   
					the purchaser/user returns to IMI Cornelius factory, transportation costs prepaid, and which IMI Cornelius finds to be defective in workmanship and/   
					or material within the warranty period. To be reimbursable under this warranty, labor charges must be submitted to IMI Cornelius within 30 days from   
					the date of service, must be performed by a qualified company acceptable to IMI Cornelius, and must be for reasonable and customary straight time   
					labor charges only. No travel time, mileage, or other charges in excess of straight time charges will be accepted. Any replacement parts must be   
					approved IMI Cornelius parts. The serial and model numbers and date of original installation of the product must be given.   
					ADDITIONAL THREE YEAR LIMITED WARRANTY ON COMPRESSOR   
					The hermetically sealed refrigeration compressor is covered by the above two year limited warranty. In addition to that warranty, if the compressor   
					fails because of a defect in materials or workmanship during the third through fifth year from the date of installation, IMI Cornelius will repair or at   
					its option, replace the compressor. Labor charges and the cost of relays, overloads and capacitors are not included.   
					This warranty does not include failure or other damage resulting from:   
					S 
					S 
					S 
					S 
					S 
					S 
					S 
					S 
					Electrical power failure to the ice machine for any reason   
					Water supply failure to the ice machine for any reason   
					Adverse operating conditions as set forth in your Service Manual   
					Drain line malfunctions as set forth in your Service Manual   
					Failure to clean and maintain the ice machine as set forth in your Service Manual   
					Use of non-authorized replacements parts   
					Unauthorized modification of the ice machine   
					Any product installed outside the U.S.A. or Canada   
					No part or assembly which has be subject to accident, alteration or misuse or which is not installed, maintained, or serviced in accordance with the   
					Service Manual furnished with the product, or which is from a machine on which the serial number has been altered or removed, shall be covered   
					by this warranty.   
					THIS WARRANTY DOES NOT COVER DAMAGE CAUSED BY LACK OF PREVENTATIVE MAINTENANCE, IMPROPER INSTALLATION,   
					ACCIDENT, MISUSE, NEGLIGENCE, ALTERATION, FIRE, FLOOD, OR ACTS OF GOD. In those jurisdictions where liability for damages cannot   
					be disclaimed, original purchasers recovery shall not exceed the cost of the warranted product.   
					IMI CORNELIUS ASSUMES NO LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND, INCLUDING, BUT NOT LIM-   
					ITED TO, SPOILED PRODUCT, LOST PROFITS, OR DAMAGE TO OTHER PROPERTY.   
					THIS WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, WHETHER WRITTEN, ORAL, OR IMPLIED, INCLUDING ANY   
					WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, AND SUPERSEDES AND EXCLUDES ANY ORAL   
					WARRANTIES OR REPRESENTATIONS OR WRITTEN LANGUAGE IN ANY MANUAL, LITERATURE, ADVERTISING BROCHURE OR   
					OTHER MATERIALS NOT EXPRESSLY DESIGNATED IN WRITING AS A “WARRANTY   
					IMI CORNELIUS   
					25   
					630460150   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				THIS PAGE LEFT BLANK INTENTIONALLY   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				IMI CORNELIUS INC.   
					Corporate Headquarters:   
					One Cornelius Place   
					Anoka, Minnesota 55303-6234   
					Telephone (800) 238-3600   
					Facsimile (763) 422-3246   
					630460150   
					27   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |