Carrier Refrigerator 17 19EX User Manual

17/19EX  
50/60 Hz  
Centrifugal Liquid Chillers  
with HFC-134a  
®
Start-Up, Operation, and Maintenance Instructions  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and  
without incurring obligations.  
PC 211  
Catalog No. 531-715  
9-95  
Form 17/19EX-1SS  
Replaces: 19EX-1SS  
Copyright Carrier Corporation 1995  
©
Safety Considerations  
Centrifugal liquid chillers are designed to provide safe and reliable service when  
operated within design specifications. When operating this equipment, use good  
judgement and safety precautions to avoid damage to equipment and property or injury  
to personnel.  
Be sure you understand and follow the procedures and safety precautions contained  
in the machine instructions as well as those listed in this guide.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING  
WARNING  
!
DO NOT WELD OR FLAMECUT any refrigerant line or vessel until all refrigerant  
(liquid and vapor) has been removed from chiller. Traces of vapor should be dis-  
placed with dry air or nitrogen and the work area should be well ventilated. Refrig-  
erant in contact with an open flame produces toxic gases.  
DO NOT USE eyebolts or eyebolt holes to rig machine sections or the entire  
assembly.  
DO NOT work on high-voltage equipment unless you are a qualified electrician.  
DO NOT WORK ON electrical components, including control panels, switches,  
starters, or oil heater until you are sure ALL POWER IS OFF and no residual volt-  
age can leak from capacitors or solid-state components.  
LOCK OPEN AND TAG electrical circuits during servicing. IF WORK IS INTER-  
RUPTED, confirm that all circuits are deenergized before resuming work.  
AVOID SPILLING liquid refrigerant on skin or getting it into the eyes. USE SAFETY  
GOGGLES. Wash any spills from the skin with soap and water. If any enters the  
eyes, IMMEDIATELY FLUSH EYES with water and consult a physician.  
NEVER APPLY an open flame or live steam to a refrigerant cylinder. Dangerous  
overpressure can result. When necessary to heat refrigerant, use only warm (110  
F [43 C]) water.  
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to refill them. It  
is DANGEROUS AND ILLEGAL. When cylinder is emptied, evacuate remaining  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING  
WARNING  
!
gas pressure, loosen the collar and unscrew and discard the valve stem. DO NOT  
INCINERATE.  
CHECK THE REFRIGERANT TYPE before adding refrigerant to the machine. The  
introduction of the wrong refrigerant can cause damage or malfunction to this  
machine.  
Operation of this equipment with refrigerants other than those cited herein should  
comply with ASHRAE-15 (latest edition). Contact Carrier for further information  
on use of this machine with other refrigerants.  
DO NOTATTEMPT TO REMOVE fittings, covers, etc., while machine is under pres-  
sure or while machine is running. Be sure pressure is at 0 psig (0 kPa) before  
breaking any refrigerant connection.  
CAREFULLY INSPECT all relief devices, rupture discs, and other relief devices AT  
LEAST ONCE A YEAR. If machine operates in a corrosive atmosphere, inspect the  
devices at more frequent intervals.  
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief device when corro-  
sion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve  
body or mechanism. Replace the device.  
DO NOT install relief devices in series or backwards.  
USE CARE when working near or in line with a compressed spring. Sudden  
release of the spring can cause it and objects in its path to act as projectiles.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION  
CAUTION  
!
DO NOT STEP on refrigerant lines. Broken lines can whip about and cause per-  
sonal injury.  
DO NOT climb over a machine. Use platform, catwalk, or staging. Follow safe  
practices when using ladders.  
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection cov-  
ers or other heavy components. Even if components are light, use such equip-  
ment when there is a risk of slipping or losing your balance.  
BE AWARE that certain automatic start arrangements CAN ENGAGE THE  
STARTER. Open the disconnect  
the machine or pump.  
the starter in addition to shutting off  
ahead of  
USE only repair or replacement parts that meet the code requirements of the  
original equipment.  
DO NOT VENT OR DRAIN waterboxes containing industrial brines, liquid, gases,  
or semisolids without permission of your process control group.  
DO NOT LOOSEN waterbox cover bolts until the waterbox has been completely  
drained.  
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or other items have  
been removed before rotating any shafts.  
DO NOT LOOSEN a packing gland nut before checking that the nut has a positive  
thread engagement.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION  
CAUTION  
!
PERIODICALLY INSPECT all valves, fittings, and piping for corrosion, rust, leaks,  
or damage.  
PROVIDE A DRAIN connection in the vent line near each pressure relief device to  
prevent a build-up of condensate or rain water.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
List of Tables  
List of Figures  
Safety Considerations  
Introduction  
Abbreviations  
17/19EX Machine Familiarization  
Machine Identification Label  
System Components  
Cooler  
Condenser  
Motor-Compressor  
Control Center  
Motor Starter  
Utility Vessel  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Refrigeration Cycle  
Motor/Oil Refrigeration Cooling Cycle  
Hermetic Machines (19 Series) Lubrication Cycle  
Summary  
Details  
Open-Drive Machines (17 Series) Lubrication Cycle  
Summary  
Details  
Starters  
Controls  
Definitions  
Analog Signal  
Digital Signal  
Volatile Memory  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
General  
PIC System Components  
Processor Module (PSIO)  
Starter Management Module (SMM)  
Local Interface Device (LID)  
6-Pack Relay Board  
8-Input Modules  
Oil Heater Contactor (1C)  
Oil Pump Contactor (2C)  
Hot Gas Bypass Contactor Relay (3C) (Optional)  
Control Transformers (T1-T4)  
Control and Oil Heater Voltage Selector (S1)  
Oil Differential Pressure/Power Supply Module  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
LID Operation and Menus  
General  
Alarms and Alerts  
LID Default Screen Menu Items  
Menu Structure  
To View or Change Point Status  
Override Operations  
To View or Change Time Schedule Operation  
To View and Change Set Points  
Service Operation  
PIC System Functions  
Capacity Control  
Entering Chilled Water Control  
Deadband  
Proportional Bands and Gain  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Demand Limiting  
Machine Timers  
Occupancy Schedule  
Safety Controls  
Shunt Trip  
Default Screen Freeze  
Motor Cooling Control (Hermetic Motors Only)  
Auxiliary Oil Pump Control (Open-Drive Machines Only)  
Shaft Seal Oil (Open Drive Machines Only)  
Ramp Loading Control  
Capacity Override  
High Discharge Temperature Control  
Oil Sump Temperature Control  
Oil Cooler  
Remote Start/Stop Controls  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Spare Safety Inputs  
Spare Alarm Contacts  
Condenser Pump Control  
Condenser Freeze Prevention  
Tower-Fan Relay  
Auto. Restart After Power Failure  
Water/Brine Reset  
Demand Limit Control, Option (Requires Optional 8-Input Module)  
Surge Prevention Algorithm  
Surge Protection  
Lead/Lag Control  
Common Point Sensor Installation  
Machine Communication Wiring  
Lead/Lag Operation  
Faulted Chiller Operation  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Load Balancing  
Auto. Restart After Power Failure  
Ice Build Control  
Ice Build Initiation  
Start-Up/Recycle Operation  
Temperature Control During Ice Build  
Termination of Ice Build  
Return to Non-Ice Build Operations  
Attach to Network Device Control  
Attaching to Other CCN Modules  
Service Operation  
To Log On  
To Log Off  
Holiday Scheduling  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Start-Up/Shutdown/Recycle Sequence  
Local Start-Up  
Shutdown Sequence  
Automatic Soft Stop Amps Threshold  
Chilled Water Recycle Mode  
Safety Shutdown  
Before Initial Start-Up  
Job Data Required  
Equipment Required  
Using the Utility Vessel and Pumpout System  
Remove Shipping Packaging  
Open-Drive Motor Electrical Connection  
Open-Drive Motor Auxiliary Devices  
Open Oil Circuit Valves  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Torque All Gasketed Joints  
Check Machine Tightness  
Refrigerant Tracer  
Leak Test Machine  
Standing Vacuum Test  
Machine Dehydration  
Inspect Water Piping  
Check Optional Pumpout Compressor Water Piping  
Check Relief Devices  
Inspect Wiring  
Check Insulation Resistance (Hermetic Motor)  
Check Insulation Resistance (Open-Drive Motor)  
Open-Drive Motor Pre-Start Checks  
Carrier Comfort Network Interface  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Check Starter  
Mechanical-Type Starters  
Solid-State Starters  
Oil Charge  
Power Up the Controls and Check the Oil Heater  
Software Version  
Set Up Machine Control Configuration  
Input the Design Set Points  
Input the Local Occupied Schedule (OCCPC01S)  
Input Service Configurations  
Password  
Input Time and Date  
Change LID Configuration If Necessary  
Modify Controller Identification If Necessary  
Input Equipment Service Parameters If Necessary  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Modify Equipment Configuration If Necessary  
Check Voltage Supply  
Perform an Automated Control Test  
Check Pumpout System Controls and Optional Pumpout Compressor  
High Altitude Locations  
Charge Refrigerant into Machine  
Trimming Refrigerant Charge  
Initial Start-Up  
Preparation  
Manual Operation of the Guide Vanes  
Dry Run to Test Start-Up Sequence  
Check Rotation (Open-Drive Motor)  
Check Rotation (Hermetic Motor)  
If Rotation Is Proper  
If the Motor Rotation Is Not Clockwise  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Check Oil Pressure and Compressor Stop  
Calibrate Motor Current Demand Setting  
To Prevent Accidental Start-Up  
Hot Alignment Check for Open-Drive Machines  
Doweling for Open-Drive Machines  
Check Machine Operating Condition  
Instruct the Customer Operator  
Cooler-Condenser  
Utility Vessel  
Pumpout System  
Motor Compressor Assembly  
Motor Compressor Lubrication System  
Control System  
Auxiliary Equipment  
Describe Machine Cycles  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Review Maintenance  
Safety Devices and Procedures  
Check Operator Knowledge  
Review the Start-Up, Operation, and Maintenance Manual  
Operating Instructions  
Operator Duties  
Prepare the Machine for Start-Up  
To Start the Machine  
Check the Running System  
To Stop the Machine  
After Limited Shutdown  
Extended Shutdown  
After Extended Shutdown  
Cold Weather Operation  
Manual Guide Vane Operation  
Refrigeration Log  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Pumpout and Refrigerant Transfer Procedures  
Preparation  
Operating the Optional Pumpout Compressor  
To Read Refrigerant Pressures  
Transferring Refrigerant from Normal Operation into the Utility Vessel  
Transferring Refrigerant from Normal Operation into the  
Cooler/Condenser/Compressor Section  
Return Refrigerant to Normal Operating Conditions  
General Maintenance  
Refrigerant Properties  
Adding Refrigerant  
Removing Refrigerant  
Adjusting the Refrigerant Charge  
Refrigerant Leak Testing  
Leak Rate  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Test After Service, Repair, or Major Leak  
Refrigerant Tracer  
To Pressurize with Dry Nitrogen  
Repair the Leak, Retest, and Apply Standing Vacuum Test  
Checking Guide Vane Linkage  
Contact Seal Maintenance (Open-Drive Machines)  
Seal Disassembly  
Seal Reassembly  
Machine Alignment (Open-Drive Machines)  
Alignment Methods  
Preliminary Alignment  
Near Final Alignment  
Final Alignment  
Hot Alignment Check  
Doweling  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Weekly Maintenance  
Check the Lubrication System  
Scheduled Maintenance  
Service Ontime  
Inspect the Control Center  
Check Safety and Operating Controls Monthly  
Changing Oil Filter  
19EX Compressors  
FA Style Compressors  
Oil Specification  
Oil Changes  
To Change the Oil  
Refrigerant Filter  
Oil Reclaim Filter  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Inspect Refrigerant Float System  
Inspect Relief Valves and Piping  
Coupling Maintenance (Open-Drive Machines)  
Procedure  
Motor Maintenance (Open-Drive Machines)  
Cleanliness  
Sleeve Bearings  
Open-Drive Motor Handling/Rigging  
Open-Drive Motor Storage  
Compressor Bearing and Gear Maintenance  
Inspect the Heat Exchanger Tubes  
Cooler  
Condenser  
Water Leaks  
Water Treatment  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Inspect the Starting Equipment  
Check Pressure Transducers  
Pumpout System Maintenance  
Optional Pumpout Compressor Oil Charge  
Pumpout Safety Control Settings  
Ordering Replacement Chiller Parts  
Open-Drive Motor Renewal Parts  
Troubleshooting Guide  
Overview  
Checking the Display Messages  
Checking Temperature Sensors  
Resistance Check  
Voltage Drop  
Check Sensor Accuracy  
Dual Temperature Sensors  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Checking Pressure Transducers  
Oil Differential Pressure/Power Supply Module Calibration  
Troubleshooting Transducers  
Transducer Replacement  
Control Algorithms Checkout Procedure  
Control Test  
Control Modules  
Red LED  
Green LEDs  
Notes on Module Operation  
Processor Module (PSIO)  
Inputs  
Outputs  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Starter Management Module (SMM)  
Inputs  
Outputs  
Options Modules (8-Input)  
Replacing Defective Processor Modules  
Installation of New PSIO Module  
17/19EX Physical Data and Wiring Schematics  
Compressor Fits and Clearances  
Initial Start-Up Checklist for 17/19EX Centrifugal Liquid Chiller  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
List of Tables  
Table 1 — Major PIC Components and Panel Locations  
Table 2 — LID Screens  
Example 1 — Status01 Display Screen  
Example 2 — Status02 Display Screen  
Example 3 — Status03 Display Screen  
Example 4 — Setpoint Display Screen  
Example 5 — Configuration (Config) Display Screen  
Example 6 — Lead/Lag Configuration Display Screen  
Example 7 — Service1 Display Screen  
Example 8 — Service2 Display Screen  
Example 9 — Service3 Display Screen  
Example 10 — Maintenance (Maint01) Display Screen  
Example 11 — Maintenance (Maint02) Display Screen  
Example 12 — Maintenance (Maint03) Display Screen  
Example 13 — Maintenance (Maint04) Display Screen  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Table 3 — Protective Safety Limits and Control Settings  
Table 4 — Capacity Overrides  
Table 5A — HFC-134a Pressure — Temperature (F)  
Table 5B — HFC-134a Pressure — Temperature (C)  
Table 6 — Recommended Torque  
Table 7 — Control Test Menu Functions  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/  
Alert Messages with Troubleshooting Guides  
A. Shutdown with ON/OFF/RESET-OFF  
B. Timing Out or Timed Out  
C. In Recycle Shutdown  
D. Pre-Start Alerts  
E. Normal or AUTO.-RESTART  
F. Start-Up Failures  
G. Compressor Jumpstart and Refrigerant Protection  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/  
Alert Messages with Troubleshooting Guides (Continued)  
H. Normal Run with Reset, Temperature, Or Demand  
I. Normal Run Overrides Active (Alerts)  
J. Out-of-Range Sensor Failures  
K. Machine Protect Limit Faults  
L. Machine Alerts  
M. Spare Sensor Alert Messages  
N. Other Problems/Malfunctions  
Table 9A — Thermistor Temperature (F) vs Resistance/Voltage Drop  
Table 9B — Thermistor Temperature (C) vs Resistance/Voltage Drop  
Table 10 — 17/19EX Heat Exchanger, Economizer/Storage Vessel,  
Piping, and Pumpout Unit Weights  
Table 11 — Additional Condenser Weights  
Table 12 — Compressor/Motor/Suction Elbow Weights  
Table 13 — Additional Cooler Weights  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Table 14 — Marine Waterbox Cover Weights  
Table 15 — NIH Waterbox Cover Weights  
Table 16 — Auxiliary Systems, Electrical Data  
Table 17 — Open-Drive Compressor Fits and Clearances  
Table 18 — Hermetic Compressor Fits and Clearances  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
List of Figures  
Figure 1 — 17/19EX Identification  
Figure 2 — Typical 17EX Installation  
Figure 3 — Typical 19EX Installation  
Figure 4 — Refrigerant, Motor Cooling, and Oil Cooling Cycles  
Figure 5 — Hermetic Compressor Lubrication System (EX Compres-  
sor Shown)  
Figure 6 — Open-Drive (17 Series) Lubrication Cycle  
Figure 7 — 17EX Controls and Sensor Locations  
Figure 8 — 19EX Controls and Sensor Locations  
Figure 9 — Control Center (Front View); Shown with Options Module  
Figure 10Control Sensors (Temperature)  
Figure 11Control Sensors (Pressure Transducer, Typical)  
Figure 12Power Panel without Options (Open-Drive Machine  
Shown)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Figure 13Power Panel with Options (Hermetic Machine Shown)  
Figure 14LID Default Screen  
Figure 15LID Service Screen  
Figure 1617/19EX Menu Structure  
Figure 1717/19EX Service Menu Structure  
Figure 18Example of Point Status Screen (Status01)  
Figure 19Example of Time Schedule Operation Screen  
Figure 20Example of Set Point Screen  
Figure 2117/19EX Hot Gas Bypass/Surge Prevention  
Figure 2217/19EX with Default Metric Settings  
Figure 23Example of Attach to Network Device Screen  
Figure 24Example of Holiday Period Screen  
Figure 25Control Sequence  
Figure 26Typical Wet-Bulb Type Vacuum Indicator  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Figure 27Shipping Bolt on Open Drive Motor  
Figure 2817/19EX Leak Test Procedures  
Figure 29Dehydration Cold Trap  
Figure 30Correct Motor Rotation  
Figure 31Refrigeration Log  
Figure 32Pumpout Arrangement and Valve Number Locations  
(12-ft Vessel Shown)  
Figure 33Pumpout Unit Wiring Schematic (19EX Shown)  
Figure 34Optional Pumpout Compressor  
Figure 35Electronic Vane Actuator Linkage  
Figure 36Compressor Contact Seal (Open-Drive Machines)  
Figure 37Checking Preliminary Alignment  
Figure 38Measuring Angular Misalignment in Elevation  
Figure 39Measuring Angular Misalignment on Brackets  
Figure 40Alignment Formula  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Figure 41Adjusting Angular Misalignment in Plan  
Figure 42Correcting Parallel Misalignment  
Figure 43Alignment Check — Assembled Coupling  
Figure 44Removing the Oil Filter  
Figure 45Typical Float Valve Arrangement  
Figure 46Lifting Open-Drive Motor  
Figure 47Controls for Optional Pumpout Compressor  
Figure 48Oil Differential Pressure/Power Supply Module  
Figure 49PSIO Module LED Locations  
Figure 50LID Module (Rear View) and LED Locations  
Figure 51Processor (PSIO) Module  
Figure 52Starter Management Module (SMM)  
Figure 53Options Module  
Figure 54Model Number Nomenclature for Compressor Size  
(See Figure 1 also)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Figure 55Open-Drive Compressor Fits and Clearances  
Figure 56Hermetic Compressor Fits and Clearances  
Figure 57Electronic PIC Controls Wiring Schematic —  
Hermetic Machine  
Figure 58Electronic PIC Controls Wiring Schematic —  
Open-Drive Machine  
Figure 59Machine Power Panel, Starter Assembly,  
and Motor Wiring Schematic  
Figure 60Hermetic Drive — Power Panel with Water-Cooled Oil  
Cooler  
Figure 61Hermetic Drive — Power Panel with Motor  
Cooling Solenoid  
Figure 62Open Drive — Power Panel  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
Prior to initial start-up of the 17/19EX unit, those involved in the start-up, operation, and  
maintenance should be thoroughly familiar with these instructions and other necessary job data.  
This book is outlined so that you may become familiar with the control system before performing  
start-up procedures. Procedures in this manual are arranged in the sequence required for  
proper machine start-up and operation.  
WARNING  
WARNING  
!
This unit uses a microprocessor control system. Do not short or jumper between  
terminations on circuit boards or modules; control or board failure may result.  
Be aware of electrostatic discharge (static electricity) when handling or making  
contact with circuit boards or module connections. Always touch a chassis  
(grounded) part to dissipate body electrostatic charge before working inside con-  
trol center.  
Use extreme care when handling tools near boards and when connecting or dis-  
connecting terminal plugs. Circuit boards can easily be damaged. Always hold  
boards by the edges and avoid touching components and connections.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING  
WARNING  
!
This equipment uses, and can radiate, radio frequency energy. If not installed and  
used in accordance with the instruction manual, it may cause interference to  
radio communications. It has been tested and found to comply with the limits for  
a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which  
are designed to provide reasonable protection against such interference when  
operated in a commercial environment. Operation of this equipment in a residen-  
tial area is likely to cause interference, in which case the user, at his own  
expense, will be required to take whatever measures may be required to correct  
the interference.  
Always store and transport replacement or defective boards in anti-static ship-  
ping bag.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Abbreviations  
Frequently used abbreviations in this manual include:  
CCN  
CCW  
CHW  
CHWR  
CHWS  
CW  
Carrier Comfort Network  
Counterclockwise  
Chilled Water  
LCDW — Leaving Condenser Water  
LCW  
LED  
LID  
— Leaving Chilled Water  
— Light-Emitting Diode  
Chilled Water Return  
Chilled Water Supply  
Clockwise  
— Local Interface Device  
OLTA  
PIC  
— Overload Trip Amps  
— Product Integrated Control  
— Processor Sensor Input/Output Module  
— Rated Load Amps  
ECW  
ECDW  
EMS  
Entering Chilled Water  
Entering Condenser Water  
Energy Management System  
Hot Gas Bypass  
PSIO  
RLA  
SCR  
SMM  
TXV  
— Silicon Control Rectifier  
— Starter Management Module  
— Thermostatic Expansion Valve  
HGBP  
I/O  
Input/Output  
LCD  
Liquid Crystal Display  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17/19EX Machine Familiarization (Figure 1, Figure 2, and Figure 3)  
Machine Identification Label  
The identification label is located on the right side of the machine control center panel. The  
label contains information on model number, refrigerant charge, rated voltage, etc.  
System Components  
The components include the cooler and condenser heat exchangers in separate vessels,  
motor-compressor, lubrication package, control center, utility vessel, and motor starter. All  
connections from pressure vessels have external threads to enable each component to be  
pressure tested with a threaded pipe cap during factory assembly.  
Click here for Figure 1 — 17/19EX Identification  
Click here for Figure 2 — Typical 17EX Installation  
Click here for Figure 3 — Typical 19EX Installation  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Cooler  
This vessel (also known as the evaporator) is located underneath the condenser, next to the  
utility vessel. The cooler is maintained at lower temperature/pressure so that evaporating  
refrigerant can remove heat from water flowing through its internal tubes.  
Condenser  
The condenser operates at a higher temperature/pressure than the cooler, and has water  
flowing through its internal tubes in order to remove heat from the refrigerant.  
Motor-Compressor  
This component maintains system temperature/pressure differences and moves the heat  
carrying refrigerant from the cooler to the condenser.  
Control Center  
The control center is the user interface for controlling the machine and regulates the machine  
capacity as required to maintain proper leaving chilled water temperature. The control center:  
• registers cooler, condenser, and lubricating system pressures  
• shows machine operating condition and alarm shutdown conditions  
• records the total machine operating hours and how many hours the machine has  
been running  
• sequences machine start, stop, and recycle under microprocessor control  
• provides access to other CCN (Carrier Comfort Network) devices  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Motor Starter (Purchased Separately)  
The starter allows for the proper starting and disconnecting of the electrical energy for the  
compressor-motor, oil pump, oil heater, and control panels.  
Utility Vessel  
During normal operation, this vessel functions as an economizer, returning flash gas to the  
second stage of the compressor and increasing the efficiency of the refrigeration cycle. During  
periods of shutdown and service, the utility vessel can serve as a storage tank for the  
refrigerant.  
Figure 4  
Refrigeration Cycle (  
)
The machine compressor continuously draws large quantities of refrigerant vapor from the  
cooler, at a rate determined by the amount of guide vane opening. This compressor suction  
reduces the pressure within the cooler, allowing the liquid refrigerant to boil vigorously at a fairly  
low temperature (typically 38 to 42 F [3 to 6 C]).  
The liquid refrigerant obtains the energy needed to vaporize by removing heat from the water  
or brine in the cooler tubes. The cold water or brine can then be used in air conditioning and/or  
other processes.  
After removing heat from the water or brine, the refrigerant vapor enters the first stage of the  
compressor, is compressed and flows into the compressor second stage. Here it is mixed with  
flash-economizer gas and is further compressed.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Compression raises the refrigerant temperature above that of the water flowing through the  
condenser tubes. When the warm (typically 98 to 102 F [37 to 40 C]) refrigerant vapor comes  
into contact with the condenser tubes, the relatively cool condensing water (typically 85 to 95 F  
[29 to 35 C]) removes some of the heat and the vapor condenses into a liquid.  
The liquid refrigerant passes through an orifice into the FLASC chamber. Because the  
coolest condenser water is flowing through the FLASC, it is at a lower pressure and part of the  
entering liquid refrigerant will flash to vapor, thereby cooling the remaining liquid. The vapor is  
then recondensed by the condenser water flowing through the FLASC chamber.  
The subcooled liquid refrigerant drains into a high-side valve chamber which meters the  
refrigerant liquid into a flash economizer chamber. Pressure in this chamber is intermediate  
between condenser and cooler pressures. At this lower pressure, some of the liquid refrigerant  
flashes to gas, further cooling the remaining liquid. The flash gas, having absorbed heat, is  
returned directly to the compressor second stage. Here it is mixed with discharge gas that is  
already compressed by the first-stage impeller. Since the flash gas has to pass through only  
half the compression cycle, to reach condenser pressure, there is a savings in power.  
The cooled liquid refrigerant in the economizer is metered through the low-side valve  
chamber into the cooler. Because pressure in the cooler is lower than economizer pressure,  
some of the liquid flashes and cools the remainder to evaporator (cooler) temperature. The  
cycle is now complete.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Motor/Oil Refrigeration Cooling Cycle  
The motor is cooled by liquid refrigerant taken from the bottom of the condenser vessel  
(Figure 4). Flow of refrigerant is maintained by the pressure differential that exists due to  
compressor operation. After the refrigerant flows past an isolation valve, an in-line filter, and a  
sight glass/moisture indicator, the flow is split between motor cooling and oil cooling systems.  
Flow to the motor flows through an orifice and into the motor. On models with a solenoid  
valve, the valve will open if additional motor cooling is required. Once past the orifice, the  
refrigerant is directed over the motor by a spray nozzle.  
The refrigerant collects in the bottom of the motor casing and then is drained back into the  
cooler through the motor refrigerant drain line. An orifice in this line maintains a higher pressure  
in the motor shell than in the cooler/oil sump. The motor is protected by a temperature sensor  
imbedded in the stator windings. On models with a solenoid valve, higher motor temperatures  
(above 125 F [51 C]) energize the solenoid to provide additional motor cooling. On all models, a  
further increase in temperature past the motor override set point will override the temperature  
capacity control to hold, and if the motor temperature rises 10° F (5.5° C) above this set point,  
will close the inlet guide vanes. If the temperature rises above the safety limit, the compressor  
will shut down.  
On machines with EX compressors, the oil is also cooled by liquid refrigerant. Refrigerant  
that flows to the oil cooling system is regulated by a thermostatic expansion valve. There is  
Download from Www.Somanuals.com. All Manuals Search And Download.  
always a minimum flow bypassing the TXV, which flows through an orifice. The TXV valve  
regulates flow into the oil/refrigerant plate and frame-type heat exchanger. The bulb for the  
expansion valve controls oil temperature to the bearings. The refrigerant leaving the heat  
exchanger then returns to the cooler.  
On machines with FA compressors, the oil is water cooled. Water flow through the oil cooler  
is manually adjusted by a plug valve to maintain an operating temperature at the reservoir of  
approximately 145 F (63 C).  
Click here for Figure 4 — Refrigerant, Motor Cooling, and Oil Cooling Cycles  
Hermetic Machines (19 Series) Lubrication Cycle  
Summary  
The compressor oil pump and oil reservoir are located in the compressor base. Oil is pumped  
through an oil cooler and a filter to remove heat and any foreign particles. Part of the oil flow is  
directed to the compressor motor-end bearings and seal. The remaining flow lubricates the  
compressor transmission, thrust and journal bearings and seal. Oil is then returned to the  
reservoir to complete the cycle (Figure 5).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Details  
Oil is charged into the reservoir (Item 1) through a hand valve (Item 4) which also functions  
as an oil drain. If there is refrigerant in the machine, a pump is required for charging. Sight  
glasses (Item 10) on the reservoir wall permit observation of the oil level. The normal operating  
oil level is from the middle of the lower sight glass to the top of the lower sight glass.  
The motor-driven oil pump (Item 8) discharges oil to an oil cooler (Item 12) at a rate and  
pressure controlled by an oil regulator (Item 7). The differential pressure (supply versus return)  
is registered at the control center. Oil differential pressure is maintained between 18 to 30 psi  
(124 to 207 kPa).  
The oil pump discharges oil to the oil cooler (Item 12). Oil is then piped to the oil filter  
assembly (Item 9). This filter is capable of being valved closed to permit removal of the filter  
without draining the entire oil system (see Scheduled Maintenance, Changing Oil Filter section  
for details). The oil is then piped to the oil cooler (Item 12).  
The oil cooler on the EX compressor is a plate-and-frame type, refrigerant cooled, heat  
exchanger. The EX compressor oil cooler heat exchanger uses refrigerant from the condenser  
as a coolant. The refrigerant cools the oil to a temperature between 110 and 120 F (43 and  
49 C) supply oil temperature to the bearings.  
The FA compressor oil cooler heat exchanger is water cooled. The water flow through the  
cooler is manually controlled by a plug valve. The valve should be adjusted to maintain  
approximately 145 F (63 C) in the oil sump during running conditions.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
As the oil leaves the oil cooler, it passes the oil pressure transducer (Item 14) and then the  
thermostatic expansion valve bulb (Item 13). The oil flow is then divided, and a portion flows to  
the motor-end bearing (Item 19) and seal. The remainder lubricates the compressor  
transmission (Item 2) and the thrust and journal bearings (Item 3). Thrust bearing temperature  
is indicated at the Local Interface Device (LID). Oil from each circuit returns by gravity to the  
reservoir.  
A demister (Items 17 and 18), by centrifugal action, draws refrigerant gas from the  
transmission area to the motor shell. The resulting pressure difference prevents oil in the trans-  
mission cavity from leaking into the motor shell.  
Several safety features are part of the lubrication system:  
In the event of power failure, a small oil reservoir (Item 16) supplies sufficient oil reserve to  
ensure continued lubrication until all compressor parts have come to a complete stop. The  
bearing temperature sensor (Item 15) monitors thrust bearing temperatures and shuts off the  
machine if the temperature rises above a selected point. Low-oil pressure will shut down the  
machine or prevent a start if oil pressure is not adequate.  
The PIC (Product Integrated Control) measures the temperature of the oil in the sump and  
maintains the temperature during shutdown (see Controls, Oil Sump Temperature Control  
section). This temperature is read on the LID default screen.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
During the machine start-up, the PIC will energize the oil pump and provide 15 seconds of  
prelubrication to the bearings after the oil pressure is verified and before the controls start the  
compressor. During shutdown, the oil pump will run for 60 seconds after the compressor  
actually shuts down for the purpose of post-lubrication. The oil pump can also be energized for  
testing purposes in controls test.  
Ramp loading can slow the rate of guide vane opening to minimize oil foaming at start-up. If  
the guide vanes open quickly, the sudden drop in suction pressure can cause any refrigerant in  
the oil to flash. The resulting oil foam cannot be pumped efficiently; oil pressure falls off, and  
lubrication is poor. If oil pressure falls below 15 psi (90 kPa) differential, the PIC will shut down  
the compressor.  
Oil reclaim is accomplished by returning the system oil through the check valve/orifice (Item  
11). As oil builds up behind the second stage impeller, it is drained by the check valve/orifice  
back into the oil reservoir. An oil/refrigerant mixture is drawn up from the operating level of the  
cooler into the guide vane housing. This assists the oil return system at low load operating  
conditions.  
Click here for Figure 5 — Hermetic Compressor Lubrication System  
(EX Compressor Shown)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Open-Drive Machines (17 Series) Lubrication Cycle  
Summary  
The main oil pump and oil reservoir are contained in the compressor base. Oil is pumped  
through an oil cooler and a filter to remove heat and any foreign particles. A portion of the oil is  
then directed to shaft-end bearing and the shaft seal. The balance of the oil lubricates the  
compressor transmission and the thrust and journal bearings. The bearing and transmission oil  
returns directly to the reservoir to complete the cycle. Contact-seal oil leakage, however, is  
collected in an atmospheric float chamber to be pumped back to the main reservoir as the oil  
accumulates.  
Figure 6  
Details (See  
)
Oil may be charged into the reservoir (1) through a hand valve (2) which also functions as an  
oil drain. If there is refrigerant in the machine, however, a hand pump will be required for  
charging at this connection.  
An oil-charging elbow (Item 20) on the seal-oil return chamber allows oil to be added without  
pumping. The seal-oil return pump (Item 21) automatically transfers the oil to the main reservoir.  
Sight glasses (Item 6) on the reservoir wall permit observation of the oil level.  
A motor-driven oil pump (Item 5) discharges oil to an oil cooler (Item 7) at a rate and pressure  
controlled by an oil regulator (Item 4). The differential oil pressure (bearing supply versus oil  
reservoir) is registered on the control panel.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Water flow through the oil cooler is manually adjusted by a plug valve (Item 9) to maintain the  
oil at an operating temperature of approximately 145 F (63 C). During shutdown, the oil  
temperature is also maintained at 150 to 160 F (65 to 71 C) by an immersion heater (Item 3) in  
order to minimize absorption of refrigerant by the oil.  
Upon leaving the oil cooler, the oil is filtered (11) and a portion is directed to the seal-end  
bearing (17) and the shaft seal (18). The remainder lubricates the compressor transmission (15)  
and the thrust and journal bearings (10). Thrust bearing temperature is indicated by the PIC  
controls. Oil from both circuits returns by gravity to the reservoir.  
A demister (13 and 16), by centrifugal action, draws refrigerant gas from the transmission  
area to a housing that is vented to the cooler (Item 19). The resulting pressure difference  
prevents oil from the transmission cavity from leaking into the seal.  
The open compressor drive requires that the shaft seal (18) be kept full of lubrication oil,  
even when the machine is not operating, to prevent loss of refrigerant.  
If the machine is not operating and the oil pump has not operated during the last 12 hours,  
the control system will automatically run the oil pump for one minute in order to keep the contact  
seal filled with oil.  
IMPORTANT: If the control power is to be deenergized for more than one day, the  
machine refrigerant should be pumped over to the utility vessel.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Starters  
All starters, whether supplied by Carrier or the customer, must meet Carrier Starter  
Specification Z-375. This specification can be obtained from the Carrier Sales Representative.  
The purpose of this specification is to ensure the compatibility of the starter and the machine.  
Many styles of compatible starters are available, including solid-state starters, autotransformer,  
wye-delta closed transition starters, and full voltage starters.  
Controls  
Definitions  
Analog Signal  
An analog signal varies in proportion to the monitored source. It quantifies values between  
operating limits. (Example: A temperature sensor is an analog device because its resistance  
changes in proportion to the temperature, generating many values.)  
Digital Signal  
A digital (discrete) signal is a 2-position representation of the value of a monitored source.  
(Example: A switch is a digital device because it only indicates whether a value is above or  
below a set point or boundary by generating an on/off, high/low, or open/closed signal.)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Volatile Memory  
Volatile memory is memory incapable of being sustained if power is lost and subsequently  
restored.  
CAUTION  
CAUTION  
!
The memory of the PSIO and LID modules are volatile. If the battery in a module  
is removed or damaged, all programming will be lost.  
General  
The 17/19EX hermetic centrifugal liquid chiller contains a microprocessor-based control  
center that monitors and controls all operations of the machine. The microprocessor control  
system matches the cooling capacity of the machine to the cooling load while providing state-of-  
the-art machine protection. The system controls cooling load within the set point plus the  
deadband by sensing the leaving chilled water or brine temperature, and regulating the inlet  
guide vane via a mechanically linked actuator motor. The guide vane is a variable flow prewhirl  
assembly that controls the refrigeration effect in the cooler by regulating the amount of  
refrigerant vapor flow into the compressor. An increase in guide vane opening increases  
capacity. A decrease in guide vane opening decreases capacity. Machine protection is provided  
by the processor which monitors the digital and analog inputs and executes capacity overrides  
or safety shutdowns, if required.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Click here for Figure 6 — Open-Drive (17 Series) Lubrication Cycle  
PIC System Components  
The Product Integrated Control (PIC) is the control system on the machine. See Table 1. The  
PIC controls the operation of the machine by monitoring all operating conditions. The PIC can  
diagnose a problem and let the operator know what the problem is and what to check. It  
promptly positions the guide vanes to maintain leaving chilled water temperature. It can  
interface with auxiliary equipment such as pumps and cooling tower fans to turn them on only  
when required. It continually checks all safeties to prevent any unsafe operating condition. It  
also regulates the oil heater while the compressor is off, and the hot gas bypass valve, if  
installed.  
The PIC can be interfaced with the Carrier Comfort Network (CCN) if desired. It can  
communicate with other PIC-equipped chillers and other CCN devices.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The PIC consists of 3 modules housed inside the 3 major components. The component  
names and the control voltage contained in each component are listed below (also see  
Table 1):  
• control center  
– all extra low-voltage wiring (24 v or less)  
• power panel  
– 115 v control voltage  
– up to 600 v for oil pump power  
• starter cabinet  
– machine power wiring (per job requirement)  
Click here for Table 1 — Major PIC Components and Panel Locations  
Processor Module (PSIO)  
This module contains all of the operating software needed to control the machine. The open-  
drive machines use a different software package within the PSIO than the hermetic machines.  
There are also control hardware differences between the two types of machines. The 19EX  
uses 3 pressure transducers and 8 thermistors to sense pressures and temperatures. The  
17EX uses 4 pressure transducers and 7 thermistors to sense pressures and temperatures.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
These inputs are connected to the PSIO module. The PSIO also provides outputs to the:  
guide vane actuator; oil pump; oil heater; hot gas bypass (optional); motor cooling solenoid; and  
alarm contact. The PSIO communicates with the LID, the SMM, and the optional 8-input  
modules for user interface and starter management.  
Starter Management Module (SMM)  
This module is located within the starter cabinet. This module initiates PSIO commands for  
starter functions such as start/stop of the compressor, start/stop of the condenser and chilled  
water pumps, start/stop of the tower fan, spare alarm contacts, and the shunt trip. The SMM  
monitors starter inputs such as flow switches, line voltage, remote start contact, spare safety,  
condenser high pressure, oil pump interlock, motor current signal, starter 1M and run contacts,  
and kW transducer input (optional). The SMM contains logic capable of safely shutting down the  
machine if communication with the PSIO is lost.  
Local Interface Device (LID)  
The LID is mounted to the control center and allows the operator to interface with the PSIO  
or other CCN devices. It is the input center for all local machine set points, schedules, set-up  
functions, and options. The LID has a STOP button, an alarm light, 4 buttons for logic inputs,  
and a display. The function of the 4 buttons or ‘‘softkeys’’ are menu driven and are shown on the  
display directly above the key.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6-Pack Relay Board  
This device is a cluster of 6 pilot relays located in the control center. It is energized by the  
PSIO for the oil pump, oil heater, alarm, optional hot gas bypass relay, and motor cooling  
solenoid (19EX machines) on auxiliary oil pump (17EX machines).  
8-Input Modules  
One optional module is factory installed in the control center panel when ordered. There can  
be up to 2 of these modules per chiller with 8 spare inputs each. They are used whenever  
chilled water reset, demand reset, or reading a spare sensor is required. The sensors or 4 to  
20 mA signals are field-installed.  
The spare temperature sensors must have the same temperature/resistance curve as the  
other temperature sensors on this unit. These sensors are rated 5,000 ohm at 75 F (25 C).  
Oil Heater Contactor (1C)  
This contactor is located in the power panel and operates the heater at 115 v. It is controlled  
by the PIC to maintain oil temperature during machine shutdown.  
Oil Pump Contactor (2C)  
This contactor is located in the power panel. It operates all 200 to 575-v oil pumps. The PIC  
energizes the contactor to turn on the oil pump as necessary.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hot Gas Bypass Contactor Relay (3C) (Optional)  
This relay, located in the power panel, controls the opening of the hot gas bypass valve. The  
PIC energizes the relay during low load, high lift conditions.  
Oil Auxiliary Relay (4C)  
This relay, supplied only with open-drive machines, opens the oil cooler solenoid valve and  
interlocks the oil pump with the compressor.  
Control Transformers (T1-T4)  
These transformers are located in the power panel and convert incoming control voltage to  
either 21 vac power for the PSIO module and options modules, or 24 vac power for 3 power  
panel contactor relays and a control solenoid valve.  
Control and Oil Heater Voltage Selector (S1)  
It is necessary to use 115 v incoming control power in the power panel. The switch must be  
set to the 115-v position.  
Oil Differential Pressure/Power Supply Module  
This module, which is located in the control center, provides 5 vdc power for the transducers  
and LID backlight.  
On open-drive machines, this module outputs the difference between two pressure  
transducer input signals. The module subtracts oil supply pressure from transmission sump  
Download from Www.Somanuals.com. All Manuals Search And Download.  
pressure and outputs the difference as an oil differential pressure signal to the PSIO. The PSIO  
converts this signal to differential oil pressure. To calibrate this reading, refer to the  
Troubleshooting Guide, Checking Pressure Transducers section.  
Click here for Figure 7 — 17EX Controls and Sensor Locations  
Click here for Figure 8 — 19EX Controls and Sensor Locations  
Click here for Figure 9 — Control Center (Front View); Shown with Options Module  
Click here for Figure 10 — Control Sensors (Temperature)  
Click here for Figure 11 — Control Sensors (Pressure Transducer, Typical)  
Click here for Figure 12 — Power Panel Without Options (Open-Drive Machine  
Shown)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Click here for Figure 13 — Power Panel with Options (Hermetic Machine Shown)  
LID Operation and Menus (Figure 14, Figure 15, Figure 16, Figure 17, Figure 18,  
Figure 19, and Figure 20)  
General  
• The LID display will automatically revert to the default screen after 15 minutes if no  
softkey activity takes place and if the machine is not in the Pumpdown mode  
(Figure 14).  
• When not in the default screen, the upper right-hand corner of the LID always dis-  
plays the name of the screen that you have entered (Figure 15).  
• The LID may be configured in English or SI units, through the LID configuration  
screen.  
• Local Operation — By pressing the LOCAL softkey, the PIC is now in the LOCAL  
operation mode and the control will accept modification to programming from the LID  
only. The PIC will use the Local Time Schedule to determine machine start and stop  
times.  
• CCN Operation — By pressing the CCN softkey, the PIC is now in the CCN operation  
mode, and the control will accept modifications from any CCN interface or module  
(with the proper authority), as well as the LID. The PIC will use the CCN time sched-  
ule to determine start and stop times.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Alarms and Alerts  
Alarm (*) and alert (!) status are indicated on the Default screen and the Status tables. An  
alarm (*) will shut down the compressor. An alert (!) notifies the operator that an unusual  
condition has occurred. The machine will continue to operate when an alert is shown.  
Alarms are indicated when the control center alarm light (!) flashes. The primary alarm  
message is viewed on the default screen and an additional, secondary, message and  
troubleshooting information are sent to the Alarm History table.  
Note:  
When an alarm is detected, the LID default screen will freeze (stop updating) at the time  
of alarm. The freeze enables the operator to view the machine conditions at the time of  
alarm. The Status tables will show the updated information. Once all alarms have been  
cleared (by pressing the RESET softkey), the default LID screen will return to normal  
operation.  
Click here for Figure 14 — LID Default Screen  
Click here for Figure 15 — LID Service Screen  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LID Default Screen Menu Items  
To perform any of the operations described below, the PIC must be powered up and have  
successfully completed its self test.  
The Default screen menu selection offers four options (Status, Schedule, Setpoint, and  
Service). The Status menu allows for viewing and limited calibration/modification of control  
points and sensors, relays and contacts, and the options board. The Schedule menu allows for  
the viewing and modification of the Local Control, CCN Control, and Ice Build time schedules.  
Numerous set points including Base Demand Limit, LCW, ECW, and Ice Build can be adjusted  
under the Setpoint menu. The Service menu can be used to revise alarm history, control test,  
control algorithm status, equipment configuration, equipment service, time and date, attach to  
network, log out of device, controller identification, and LID configurations. Figure 16 and  
Figure 17 provide additional information on the menu structure.  
Press the MENU softkey to select from the 4 options. To view or change parameters within  
any menu structure, use the SELECT softkey to choose the desired table or item. The softkey  
modification choices displayed will depend on whether the selected item is a discrete point,  
analog point, or an override point. At this point, press the softkey that corresponds to your  
configuration selection or press the QUIT softkey. If the QUIT softkey is depressed, the  
configuration will not be modified. Use the following softkeys to access and select the desired  
section.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Menu Structure  
To perform any of the operations described below, the PIC must be powered up and have  
successfully completed its self test.  
• Press MENU to select from the four available options.  
CCN  
LOCAL  
RESET  
MENU  
• Press the softkey that corresponds to the desired menu structure.  
STATUS  
SCHEDULE  
SETPOINT  
SERVICE  
• Press NEXT or PREVIOUS to highlight the desired entry.  
NEXT  
PREVIOUS  
SELECT  
ENTER  
Download from Www.Somanuals.com. All Manuals Search And Download.  
• Press SELECT to access the highlighted point.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
• Press QUIT to leave the selected decision or field without saving any changes.  
INCREASE  
DECREASE  
QUIT  
ENTER  
• Or, press ENTER to leave the selected decision or field and save changes.  
INCREASE  
DECREASE  
QUIT  
ENTER  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To View or Change Point Status (Figure 18)  
Point Status is the actual value of all of the temperatures, pressures, relays, and actuators  
sensed and controlled by the PIC.  
1.  
On the Menu screen, press STATUS to view the list of Point Status tables.  
STATUS  
SCHEDULE  
SETPOINT  
SERVICE  
2.  
Press NEXT or PREVIOUS to highlight the desired status table. The list of tables is:  
• Status01 — Status of control points and sensors  
• Status02 — Status of relays and contacts  
• Status03 — Status of both optional 8-input modules and sensors  
NEXT  
PREVIOUS  
SELECT  
ENTER  
Click here for Figure 16 — 17/19EX Menu Structure  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Click here for Figure 17 — 17/19EX Service Menu Structure  
3. Press SELECT to view the desired Point Status table.  
NEXT  
PREVIOUS  
SELECT  
ENTER  
4. On the Point Status table press NEXT or PREVIOUS until desired point is displayed on the  
screen.  
NEXT  
PREVIOUS  
SELECT  
ENTER  
For Discrete Points — Press START or STOP, YES or NO, ON or OFF, etc. to select the  
desired state.  
START  
STOP  
RELEASE  
ENTER  
Download from Www.Somanuals.com. All Manuals Search And Download.  
For Analog Points — Press INCREASE or DECREASE to select the desired value.  
INCREASE  
DECREASE  
RELEASE  
ENTER  
5. Press ENTER to register new value.  
INCREASE  
DECREASE  
RELEASE  
ENTER  
Override Operations  
Note: When overriding or changing metric values, it is necessary to hold the softkey down for a  
few seconds in order to see a value change, especially on kilopascal values.  
Click here for Figure 18 — Example of Point Status Screen (Status01)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To Remove an Override  
1. On the Point Status table press NEXT or PREVIOUS to highlight the desired point.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
2. Press SELECT to access the highlighted point.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
3. Press RELEASE to remove the override and return the point to the PIC’s automatic control.  
INCREASE  
DECREASE  
RELEASE  
ENTER  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Override Indication  
An override value is indicated by ‘‘SUPVSR,’’ ‘‘SERVC,’’ or ‘‘BEST’’ flashing next to the point  
value on the Status table.  
Figure 19  
To View or Change Time Schedule Operation (  
)
1. On the Menu screen, press SCHEDULE .  
STATUS  
SCHEDULE  
SETPOINT  
SERVICE  
2. Press NEXT or PREVIOUS to highlight one of the following schedules.  
OCCPC01S — LOCAL Time Schedule  
OCCPC02S — ICE BUILD Time Schedule  
OCCPC03-99S — CCN Time Schedule (Actual number is defined in Config table.)  
NEXT  
PREVIOUS  
SELECT  
EXIT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Press SELECT to access and view the time schedule.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
4. Press NEXT or PREVIOUS to highlight the desired period or override that you wish to  
change.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
5. Press SELECT to access the highlighted period or override.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.  
a. Press INCREASE or DECREASE to change the time values. Override values are in one-  
hour increments, up to 4 hours.  
INCREASE  
DECREASE  
ENTER  
EXIT  
b. Press ENABLE to select days in the day-of-week fields. Press DISABLE to eliminate  
days from the period.  
ENABLE  
DISABLE  
ENTER  
EXIT  
7. Press ENTER to register the values and to move horizontally (left to right) within a period.  
ENABLE  
DISABLE  
ENTER  
EXIT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Press EXIT to leave the period or override.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
9. Either return to Step 4 to select another period or override, or press EXIT again to leave the  
current time schedule screen and save the changes.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
10. Holiday Designation (HOLIDEF table) may be found in the Service Operation section. You  
must assign the month, day, and duration for the holiday. The Broadcast function in the  
Brodefs table also must be enabled for holiday periods to function.  
Click here for Figure 19 — Example of Time Schedule Operation Screen  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To View and Change Set Points (Figure 20)  
1.  
To view the Set Point table, at the Menu screen press SETPOINT.  
STATUS  
SCHEDULE  
SETPOINT  
SERVICE  
2.  
There are 4 set points on this screen: Base Demand Limit; LCW Set Point (leaving chilled  
water set point); ECW Set Point (entering chilled water set point); and ICE BUILD set point.  
Only one of the chilled water set points can be active at one time, and the type of set point  
is activated in the Service menu. ICE BUILD is also activated and configured in the Service  
menu.  
3.  
Press NEXT or PREVIOUS to highlight the desired set point entry.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Press SELECT to modify the highlighted set point.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
5. Press INCREASE or DECREASE to change the selected set point value.  
INCREASE  
DECREASE  
QUIT  
ENTER  
6. Press ENTER to save the changes and return to the previous screen.  
INCREASE  
DECREASE  
QUIT  
ENTER  
Service Operation  
To view the menu-driven programs available for Service Operation, see Service Operation  
section. For examples of LID display screens, see Table 2.  
Click here for Figure 20 — Example of Set Point Screen  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2 — LID Screens  
Example 1 — Status01 Display Screen  
Example 2 — Status02 Display Screen  
Example 3 — Status03 Display Screen  
Example 4 — Setpoint Display Screen  
Example 5 — Configuration (CONFIG) Display Screen  
Example 6 — Lead/Lag Configuration Display Screen  
Example 7 — Service1 Display Screen  
Example 8 — Service2 Display Screen  
Example 9 — Service3 Display Screen  
Example 10 — Maintenance (Maint01) Display Screen  
Example 11 — Maintenance (Maint02) Display Screen  
Example 12 — Maintenance (Maint03) Display Screen  
Example 13 — Maintenance (Maint04) Display Screen  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PIC System Functions  
Note:  
Throughout this manual, words printed in capital letters and italics are values that may be  
viewed on the LID. See Table 2 for examples of LID screens. Point names are listed in  
the Description column. An overview of LID operation and menus is given in Figure 14,  
Figure 15, Figure 16, Figure 17, Figure 18, Figure 19, and Figure 20.  
Capacity Control  
The PIC controls the machine capacity by modulating the inlet guide vanes in response to  
chilled water temperature changes away from the CONTROL POINT. The CONTROL POINT  
may be changed by a CCN network device, or is determined by the PIC adding any active  
chilled water reset to the chilled water SET POINT. The PIC uses the PROPORTIONAL INC  
(Increase) BAND, PROPORTIONAL DEC (Decrease) BAND, and the PROPORTIONAL ECW  
(Entering Chilled Water) GAIN to determine how fast or slow to respond. CONTROL POINT  
may be viewed/overridden on the Status table, Status01 selection.  
Entering Chilled Water Control  
If this option is enabled, the PIC uses ENTERING CHILLED WATER temperature to  
modulate the vanes instead of LEAVING CHILLED WATER temperature. ENTERING CHILLED  
WATER control option may be viewed/modified on the Equipment Configuration table, Config  
table.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Deadband  
This is the tolerance on the chilled water/ brine temperature CONTROL POINT. If the water  
temperature goes outside of the DEADBAND, the PIC opens or closes the guide vanes in  
response until it is within tolerance. The PIC may be configured with a 0.5° to 2° F (0.3° to  
1.1° C) deadband. DEADBAND may be viewed or modified on the Equipment Service1 table.  
For example, a 1° F (0.6° C) deadband setting controls the water temperature within ±0.5° F  
(0.3° C) of the control point. This may cause frequent guide vane movement if the chilled water  
load fluctuates frequently. A value of 1° F (0.6° C) is the default setting.  
Proportional Bands and Gain  
Proportional band is the rate at which the guide vane position is corrected in proportion to  
how far the chilled water/brine temperature is from the control point. Proportional gain  
determines how quickly the guide vanes react to how quickly the temperature is moving from  
CONTROL POINT.  
The Proportional Band  
can be viewed/modified on the LID. There are two response modes,  
one for temperature response above the control point, the other for response below the control  
point.  
The first type is called PROPORTIONAL INC BAND, and it can slow or quicken vane  
response to chilled water/brine temperature above DEADBAND. It can be adjusted from a  
setting of 2 to 10; the default setting is 6.5. PROPORTIONAL DEC BAND can slow or quicken  
Download from Www.Somanuals.com. All Manuals Search And Download.  
vane response to chilled water temperature below deadband plus control point. It can be  
adjusted on the LID from a setting of 2 to 10, and the default setting is 6.0. Increasing either of  
these settings will cause the vanes to respond slower than a lower setting.  
The PROPORTIONAL ECW GAIN can be adjusted at the LID display from a setting of 1.0 to  
3.0, with a default setting of 2.0. Increase this setting to increase guide vane response to a  
change in entering chilled water temperature. The proportional bands and gain may be viewed/  
modified on the Equipment Service3 table.  
Demand Limiting  
The PIC will respond to the ACTIVE DEMAND LIMIT set point by limiting the opening of the  
guide vanes. It will compare the set point to either COMPRESSOR MOTOR LOAD or  
COMPRESSOR MOTOR CURRENT (percentage), depending on how the control is configured  
for the DEMAND LIMIT SOURCE which is accessed on the SERVICE1 table. The default  
setting is current limiting.  
Machine Timers  
The PIC maintains 2 runtime clocks, known as COMPRESSOR ONTIME and SERVICE ON-  
TIME. COMPRESSOR ONTIME indicates the total lifetime compressor run hours. This timer  
can register up to 500,000 hours before the clock turns back to zero. The SERVICE ONTIME is  
a resettable timer that can be used to indicate the hours since the last service visit or any other  
reason. The time can be changed through the LID to whatever value is desired. This timer can  
register up to 32,767 hours before it rolls over to zero.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The chiller also maintains a start-to-start timer and a stop-to-start timer. These timers limit  
how soon the machine can be started. See the Start-Up/Shutdown/Recycle Sequence section  
for operational information.  
Occupancy Schedule  
This schedule determines when the chiller is either occupied or unoccupied.  
Each schedule consists of from one to 8 occupied/unoccupied time periods, set by the  
operator. These time periods can be enabled to be in effect, or not in effect, on each day of the  
week and for holidays. The day begins with 0000 hours and ends with 2400 hours. The machine  
is in OCCUPIED mode unless an unoccupied time period is in effect.  
The machine will shut down when the schedule goes to UNOCCUPIED. These schedules  
can be set up to follow the building schedule or to be 100% OCCUPIED if the operator wishes.  
The schedules also can be bypassed by forcing the Start/Stop command on the PIC Status  
screen to start. The schedules also can be overridden to keep the unit in an OCCUPIED mode  
for up to 4 hours, on a one-time basis.  
Figure 19 shows a schedule for a typical office building time schedule, with a 3-hour, off-peak  
cool down period from midnight to 3 a.m., following a weekend shutdown. Example: Holiday  
periods are unoccupied 24 hours per day. The building operates Monday through Friday, 7:00  
a.m. to 6:00 p.m., with a Saturday schedule of 6:00 a.m. to 1:00 p.m., and includes the Monday  
midnight to 3:00 a.m. weekend cool-down schedule.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Note: This schedule is for illustration only, and is not intended to be a recommended schedule  
for chiller operation.  
Whenever the chiller is in the LOCAL mode, the machine uses Occupancy Schedule 01.  
The Ice Build Time Schedule is Schedule 02. When in the CCN mode, Occupancy Schedule  
03 is used.  
The CCN schedule number is defined on the Config table in the Equipment Configuration  
table. The schedule number can change to any value from 03 to 99. If this schedule number is  
changed on the Config table, the operator must use the Attach to Network Device table to  
upload the new number into the Schedule screen. See Figure 17.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Controls  
The PIC monitors all safety control inputs, and if required, shuts down the machine or limits  
the guide vanes to protect the machine from possible damage from any of the following  
conditions:  
• high bearing temperature  
• high motor winding temperature  
• high discharge temperature  
• low oil pressure  
• low cooler refrigerant temperature/pressure  
• condenser high pressure or low pressure  
• inadequate water/brine cooler and condenser flow  
• high, low, or loss of voltage  
• excessive motor acceleration time  
• excessive starter transition time  
• lack of motor current signal  
• excessive motor amps  
• excessive compressor surge  
• temperature and transducer faults  
Starter faults or optional protective devices within the starter can shut down the machine.  
These devices are dependent on what has been purchased as options.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION  
CAUTION  
!
If compressor motor overload or ground fault occurs, check the motor for  
grounded or open phases before attempting a restart.  
If the controller initiates a safety shutdown, it displays the fault on the LID with a primary and  
a secondary message, and energizes an alarm relay in the starter and blinks the alarm light on  
the control center. The alarm is stored in memory and can be viewed in the PIC Alarm History  
table along with a message for troubleshooting.  
To give a better warning as to the operating condition of the machine, the operator also can  
define alert limits on various monitored inputs. Safety contact and alert limits are defined in  
Table 3. Alarm and alert messages are listed in the Troubleshooting Guide section.  
Shunt Trip  
The optional shunt trip function of the PIC is a safety trip. The shunt trip is wired from an  
output on the SMM to the motor circuit breaker. If the PIC tries to shut down the compressor  
through normal shutdown procedure but is unsuccessful for 30 seconds, the shunt trip output is  
energized and causes the circuit breaker to trip off. If ground fault protection has been applied  
to the starter, the ground fault trip will also energize the shunt trip to trip the circuit breaker.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Default Screen Freeze  
Whenever an alarm occurs, the LID default screen will freeze displaying the condition of the  
machine at the time of alarm. Knowledge of the operating state of the chiller at the time an  
alarm occurs is useful when troubleshooting. Current machine information can be viewed on the  
Status tables. Once all existing alarms are cleared (by pressing the RESET softkey), the default  
LID will return to normal operation.  
Motor Cooling Control (Hermetic Motors Only)  
Motor temperature is reduced by refrigerant entering the motor shell and evaporating. The  
refrigerant is regulated by the motor cooling relay. This relay will energize when the compressor  
is running and motor temperature is above 125 F (51.7 C). The relay will close when motor  
temperature is below 100 F (37.8 C). Note that there is always a minimum flow of refrigerant  
when the compressor is operating for motor cooling; the relay only controls additional  
refrigerant to the motor.  
Note:  
An additional motor cooling relay is not required for Hermetic FA style compressors.  
Auxiliary Oil Pump Control (Open Drive Machines Only)  
The auxiliary oil pump (optional) is controlled by the PIC. During start-up, if the main oil pump  
cannot raise pressure to 18 psid (124 kPa), the auxiliary oil pump will be energized. During  
compressor operation, the auxiliary oil pump will be energized if the oil pressure falls below the  
Download from Www.Somanuals.com. All Manuals Search And Download.  
alert threshold (18 psid [124 kPa]). Once running, the auxiliary oil pump will remain on until the  
compressor is turned off and will deenergize with the main oil pump after the post-lube time  
period.  
Shaft Seal Oil Control (Open Drive Machines Only)  
All open drive machines require that the shaft seal be bathed in oil at all times, especially  
when the machine is not running. This ensures that refrigerant does not leak past the seal. The  
PIC control will energize the oil pump for one minute if the oil pump has not operated during the  
past 12 hours.  
It is important to note that if control power is to be turned off for longer than this period, the  
refrigerant charge must be pumped over into the utility vessel. Because the oil heater will also  
be off during this time, storing the refrigerant will also prevent refrigerant migration into the oil.  
Ramp Loading Control  
The ramp loading control slows down the rate at which the compressor loads up. This control  
can prevent the compressor from loading up during the short period of time when the machine  
is started, and the chilled water loop has to be brought down to normal design conditions. This  
helps reduce electrical demand charges by slowly bringing the chilled water to control point.  
However, the total power draw during this period remains almost unchanged.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
There are 2 methods of ramp loading with the PIC. Ramp loading can be based on chilled  
water temperature or on motor load.  
1. Temperature ramp loading limits the rate at which either leaving chilled water or entering  
chilled water temperature decreases by an operator-configured rate. The lowest  
temperature ramp table will be used the first time the machine is started (at  
commissioning). The lowest temperature ramp rate will also be used if machine power has  
been off for 3 hours or more (even if the motor ramp load is selected).  
2. Motor load ramp loading limits the rate at which the compressor motor current or  
compressor motor load increases by an operator-configured rate.  
The TEMP (Temperature) PULLDOWN, LOAD PULL DOWN, and SELECT RAMP TYPE  
may be viewed/modified on the LID Equipment Configuration table, Config table (see Table 2).  
Motor load is the default type.  
Table 4  
Capacity Override (See  
)
These can prevent some safety shutdowns caused by exceeding motor amperage limit,  
refrigerant low temperature safety limit, motor high temperature safety limit, and condenser high  
pressure limit. In all cases there are 2 stages of compressor vane control.  
1. The vanes are held from opening further, and the status line on the LID indicates the reason  
for the override.  
2. The vanes are closed until condition decreases below the first step set point, and then the  
vanes are released to normal capacity control.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Whenever the motor current demand limit set point is reached, it activates a capacity  
override, again with a 2-step process. Exceeding 110% of the rated load amps for more than 30  
seconds will initiate a safety shutdown.  
The compressor high lift (surge prevention) set point will cause a capacity override as well.  
When the surge prevention set point is reached, the controller normally will only hold the guide  
vanes from opening. If so equipped, the hot gas bypass valve will open instead of holding the  
vanes.  
High Discharge Temperature Control  
If the discharge temperature increases above 200 F (93 C), the guide vanes are  
proportionally opened to increase gas flow through the compressor. If the leaving chilled water  
temperature drops 5° F (2.8° C) below the control point temperature, machine will enter the  
recycle mode.  
Click here for Table 3 — Protective Safety Limits and Control Settings  
Click here for Table 4 — Capacity Overrides  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Oil Sump Temperature Control  
The oil sump temperature control is regulated by the PIC which uses the oil heater relay  
when the machine is shut down.  
As part of the pre-start checks executed by the controls, oil sump temperature is compared  
against evaporator refrigerant temperature. If the difference between these 2 temperatures is  
50 F (27.8 C) or less, the start-up will be delayed until the oil temperature is 50 F (27.8 C) or  
more. Once this temperature is confirmed, the start-up continues.  
The oil heater relay is energized whenever the chiller compressor is off and the oil sump  
temperature is less than 150 F (65.6 C) or the oil sump temperature is less than the cooler  
refrigerant temperature plus 70° F (39° C). The oil heater is turned off when the oil sump  
temperature is either 1) more than 160 F (71.1 C); or 2) the oil sump temperature is more than  
155 F (68.3 C) and more than the cooler refrigerant temperature plus 75° F (41.6° C). The oil  
heater is always off during start-up or when the compressor is running.  
When a power failure to the PSIO module has occurred for more than 3 hours (i.e., initial  
start-up), the compressor guide vane opening will be slowed down to prevent excessive oil  
foaming that may result from refrigerant migration into the oil sump during the power failure.  
The vane opening will be slowed to a value of 2° F (1.1° C) per minute with temperature ramp  
loading.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Oil Cooler  
The oil must be cooled when the compressor is running.  
EX Compressors: This is accomplished through a small, plate-type heat exchanger. The heat  
exchanger uses liquid condenser refrigerant as the cooling liquid. A refrigerant thermostatic  
expansion valve (TXV) regulates refrigerant flow to control oil temperature entering the  
bearings. There is always a flow of refrigerant bypassing the TXV. The bulb for the expansion  
valve is strapped to the oil supply line leaving the heat exchanger and the valve is set to  
maintain 110 F (43 C).  
Note:  
The expansion valve is not adjustable. Oil sump temperature may be at a lower tempera-  
ture.  
FA Compressors: The oil cooler is a water cooled, tube-in-shell type heat exchanger. A plug  
valve is manually set to maintain proper temperatures. Set the valve to maintain 145 F (63 C) oil  
sump temperatures while the compressor is running.  
Remote Start/Stop Controls  
A remote device, such as a timeclock which uses a set of contacts, may be used to start and  
stop the machine. However, the device should not be programmed to start and stop the  
machine in excess of 2 or 3 times every 12 hours. If more than 8 starts in 12 hours occur, then  
an Excessive Starts alarm is displayed, preventing the machine from starting. The operator  
must reset the alarm at the LID in order to override the starts counter and start the machine. If  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Automatic Restart After a Power Failure is not activated when a power failure occurs, and the  
remote contact is closed, the machine will indicate an alarm because of the loss of voltage.  
The contacts for Remote Start are wired into the starter at terminal strip TB5, terminals 8A  
and 8B. See the certified drawings for further details on contact ratings. The contacts must be  
dry (no power).  
Spare Safety Inputs  
Normally closed (NC) digital inputs for additional field-supplied safeties may be wired to the  
spare protective limits input channel in place of the factory installed jumper. (Wire multiple  
inputs in series.) The opening of any contact will result in a safety shutdown and LID display.  
Refer to the certified drawings for safety contact ratings.  
Analog temperature sensors may also be added to the options modules, if installed. These  
may be programmed to cause an alert on the CCN network, but will not shut the machine down.  
Spare Alarm Contacts  
Two spare sets of alarm contacts are provided within the starter. The contact ratings are  
provided in the certified drawings. The contacts are located on terminal strip TB6, terminals 5A  
and 5B, and terminals 5C and 5D.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Condenser Pump Control  
The machine will monitor the CONDENSER PRESSURE and may turn on this pump if the  
pressure becomes too high whenever the compressor is shut down. CONDENSER  
PRESSURE OVERRIDE is used to determine this pressure point. This value is found on the  
Equipment Service1 LID table and has a default value (Table 4). If the CONDENSER  
PRESSURE is greater than or equal to the CONDENSER PRESSURE OVERRIDE, and the  
ENTERING CONDENSER WATER TEMP (Temperature) is less than 115 F (46 C), then the  
condenser pump will energize to try to decrease the pressure. The pump will turn off when the  
condenser pressure is less than the pressure override less 5 psi (34 kPa), or the CONDENSER  
REFRIG (Refrigerant) TEMP is within 3° F (2° C) of the ENTERING CONDENSER WATER  
temperature.  
Condenser Freeze Prevention  
This control algorithm helps prevent condenser tube freeze-up by energizing the condenser  
pump relay. If the pump is controlled by the PIC, starting the pump will help prevent the water in  
the condenser from freezing. Condenser freeze prevention can occur whenever the machine is  
not running except when it is either actively in pumpdown or in Pumpdown Lockout with the  
freeze prevention disabled (refer to Control Test table, Pumpdown/Terminate Lockout tables).  
When the CONDENSER REFRIG TEMP is less than or equal to the CONDENSER FREEZE  
POINT, or the ENTERING CONDENSER WATER temperature is less than or equal to the  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONDENSER FREEZE POINT, then the CONDENSER WATER PUMP shall be energized  
until the CONDENSER REFRIG TEMP is greater than the CONDENSER FREEZE POINT plus  
5° F (2.7° C). An alarm will be generated if the machine is in PUMPDOWN mode and the pump  
is energized. An alert will be generated if the machine is not in PUMPDOWN mode and the  
pump is energized. If in recycle shutdown, the mode shall transition to a non-recycle shutdown.  
Tower-Fan Relay  
This control can be used to assist the condenser water temperature control system (field  
supplied). Low condenser water temperature can cause the chiller to shut down on low  
refrigerant temperature. The tower fan relay, located in the starter, is controlled by the PIC to  
energize and deenergize as the pressure differential between cooler and condenser vessels  
changes in order to prevent low condenser water temperature and to maximize machine  
efficiency. The tower-fan relay can only accomplish this if the relay has been added to the  
cooling tower temperature controller. The TOWER FAN RELAY is turned on whenever the  
CONDENSER WATER PUMP is running, flow is verified, and the difference between cooler  
and condenser pressure is more than 30 psid (207 kPad) or entering condenser water  
temperature is greater than 85 F (29 C). The TOWER FAN RELAY is deenergized when the  
condenser pump is off, flow is lost, the evaporator refrigerant temperature is less than the  
override temperature, or the differential pressure is less than 28 psid (193 kPad) and entering  
condensing water is less than 80 F (27 C).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT: Afield-supplied water temperature control system for condenser  
water should be installed. The system should maintain the leaving condenser water  
temperature at a temperature that is 20° F (11° C) above the leaving chilled water  
temperature.  
CAUTION  
CAUTION  
!
The tower-fan relay control is not a substitute for a condenser water temperature  
control. When used with a Water Temperature Control system, the tower fan  
relay control can be used to help prevent low condenser water temperatures and  
associated problems.  
Auto. Restart After Power Failure  
This option may be enabled or disabled, and may be viewed/modified in the Config table of  
Equipment Configuration. If enabled, the chiller will start up automatically after a single cycle  
drop-out, low, high, or loss of voltage has occurred, and the power is within ±10% of normal.  
The 15-min start-to-start timer and the stop-to-start timer are ignored during this type of start-up.  
When power is restored after the power failure, and if the compressor had been running, the  
oil pump will be energized for one minute prior to the evaporator pump energizing. Auto restart  
will then continue like a normal start-up.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Water/Brine Reset  
Three types of chilled water or brine reset are available and can be viewed or modified on the  
Equipment Configuration table Config selection.  
The LID default screen status message indicates when the chilled water reset is active. The  
Control Point temperature on the Status01 table indicates the machine’s current reset  
temperature.  
To activate a reset type, input all configuration information for that reset type in the Config  
table. Then input the reset type number in the SELECT/ENABLE RESET TYPE input line.  
1.  
Reset Type 1 (Requires optional 8-input module) — Automatic chilled water temperature  
reset based on a 4 to 20 mA input signal. This type permits up to ±30° F (±16° C) of  
automatic reset to the chilled water or brine temperature set point, based on the input from  
a 4 to 20 mA signal. This signal is hardwired into the number one 8-input module.  
If the 4-20 mA signal is externally powered from the 8-input module, the signal is wired to  
terminals J1-5(+) and J1-6(–). If the signal is to be internally powered by the 8-input module  
(for example, when using variable resistance), the signal is wired to J1-7(+) and J1-6(–).  
The PIC must now be configured on the Service2 table to ensure that the appropriate power  
source is identified.  
2.  
Reset Type 2 (Requires optional 8-input module) — Automatic chilled water temperature  
reset based on a remote temperature sensor input. This type permits ±30° F (±16° C) of  
Download from Www.Somanuals.com. All Manuals Search And Download.  
automatic reset to the set point based on a temperature sensor wired to the number one 8-  
input module (see wiring diagrams or certified drawings).  
The temperature sensor must be wired to terminal J1-19 and J1-20.  
To configure Reset Type 2, enter the temperature of the remote sensor at the point where  
no temperature reset will occur. Next, enter the temperature at which the full amount of  
reset will occur. Then, enter the maximum amount of reset required to operate the machine.  
Reset Type 2 can now be activated.  
3. Reset Type 3 — Automatic chilled water temperature reset based on cooler temperature  
difference. This type of reset will add ±30° F (±16° C) based on the temperature difference  
between entering and leaving chilled water temperature. This is the only type of reset  
available without the need of the number one 8-input module. No wiring is required for this  
type as it already uses the cooler water sensors.  
To configure Reset Type 3, enter the chilled water temperature difference (the difference  
between entering and leaving chilled water) at which no temperature reset occurs. This  
chilled water temperature difference is usually the full design load temperature difference.  
The difference in chilled water temperature at which the full amount of reset will occur is  
now entered on the next input line. Next, the amount of reset is entered. Reset Type 3 can  
now be activated.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Demand Limit Control, Option (Requires Optional 8-Input Module)  
The demand limit may be externally controlled with a 4 to 20 mA signal from an energy  
management system (EMS). The option is set up on the Config table. When enabled, the  
control is set for 100% demand with 4 mA and an operator configured minimum demand set  
point at 20 mA.  
The Demand Reset input from an energy management system is hardwired into the number  
one, 8-input module. The signal may be internally powered by the module or externally  
powered. If the signal is externally powered, the signal is wired to terminals J1-1(+) and J1-2(–).  
If the signal is internally powered, the signal is wired to terminals J1-3(+) and J1-2(–). When  
enabled, the control is set for 100% demand with 4 mA and an operator configured minimum  
demand set point at 20 mA.  
Surge Prevention Algorithm  
This is an operator configurable feature which can determine if lift conditions are too high for  
the compressor and then take corrective action. Lift is defined as the difference between the  
pressure at the impeller eye and the impeller discharge. The maximum lift that a particular  
impeller wheel can perform varies with the gas flow across the impeller, and the size of the  
wheel.  
The algorithm first determines if corrective action is necessary. This is done by checking 2  
sets of operator configured data points, which are the MINIMUM and the MAXIMUM Load  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Points, (T1/P1;T2/P2). These points have default settings as defined on the Service1 table, or  
on Table 4. These settings and the algorithm function are graphically displayed in Figure 21 and  
Figure 22. The 2 sets of load points on this graph (default settings are shown) describe a line  
which the algorithm uses to determine the maximum lift of the compressor. Whenever the actual  
differential pressure between the cooler and condenser, and the temperature difference  
between the entering and leaving chilled water are above the line on the graph (as defined by  
the MINIMUM and MAXIMUM Load Points) the algorithm will go into a corrective action mode. If  
the actual values are below the line, the algorithm takes no action. Modification of the default  
set points of the MINIMUM and MAXIMUM load points is described in the Input Service  
Configurations section.  
Corrective action can be taken by making one of 2 choices. If a hot gas bypass line is  
present, and the hot gas is configured on the Service1 table, then the hot gas bypass valve can  
be energized. If a hot gas bypass if not present, then the action taken is to hold the guide vanes.  
See Table 4, Capacity Overrides. Both of these corrective actions will reduce the lift  
experienced by the compressor and help to prevent a surge condition. Surge is a condition  
when the lift becomes so high that the gas flow across the impeller reverses. This condition can  
eventually cause machine damage. The surge prevention algorithm is intended to notify the  
operator that machine operating conditions are marginal, and to take action, such as lowering  
entering condenser water temperature, to help prevent machine damage.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Surge Protection  
Surging of the compressor can be determined by the PIC through operator configured  
settings. Surge will cause amperage fluctuations of the compressor motor. The PIC monitors  
these amperage swings, and if the swing is greater than the configurable setting in one second,  
then one surge count has occurred. The SURGE DELTA PERCENT AMPS setting is displayed  
and configured on the Service1 screen. It has a default setting of 25% amps, SURGE  
PROTECTION COUNTS can be monitored on the Maint03 table.  
A surge protection shutdown of the machine will occur whenever the surge protection  
counter reaches 12 counts within an operator specified time, known as the SURGE TIME  
PERIOD. The SURGE TIME PERIOD is displayed and configured on the Service1 screen. It  
has a default of 2 minutes.  
Click here for Figure 21 — 17/19EX Hot Gas Bypass/Surge Prevention  
Click here for Figure 22 — 17/19EX With Default Metric Settings  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Lead/Lag Control  
Lead/Lag is a control system process that automatically starts and stops a lag or second  
chiller in a 2-chiller water system. Refer to Figure 16 and Figure 17 for menu, table, and screen  
selection information. On machines that have PSIO software with Lead/Lag capability, it is  
possible to utilize the PIC controls to perform the lead/lag function on 2 machines. A third  
machine can be added to the lead/lag system as a standby chiller to start up in case the lead or  
lag chiller in the system has shut down during an alarm condition and additional cooling is  
required.  
Note:  
Lead/lag configuration is viewed and edited under Lead/Lag in the Equipment Configura-  
tion table (located in the Service menu). Lead/lag status during machine operation is  
viewed in the MAINT04 table in the Control Algorithm Status table. See Table 2.  
Lead/Lag System Requirements:  
• all machines must have PSIO software capable of performing the lead/lag function  
• water pumps MUST be energized from the PIC controls  
• water flows should be constant  
• CCN Time Schedules for all machines must be identical  
Operation Features:  
• 2 chiller lead/lag  
• addition of a third chiller for backup  
• manual rotation of lead chiller  
• load balancing if configured  
• staggered restart of the chillers after a power failure  
• chillers may be piped in parallel or in series chilled water flow  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Common Point Sensor Installation  
Lead/lag operation does not require a common chilled water point sensor. Common point  
sensors can be added to the 8-input option module, if desired. Refer to the certified drawings for  
termination of sensor leads.  
Note:  
If the common point sensor option is chosen on a chilled water system, both machines  
should have their own 8-input option module and common point sensor installed. Each  
machine will use its own common point sensor for control, when that machine is desig-  
nated as the lead chiller. The PIC cannot read the value of common point sensors  
installed on other machines in the chilled water system.  
When installing chillers in series, a common point sensor should be used. If a common point  
sensor is not used, the leaving chilled water sensor of the upstream chiller must be moved into  
the leaving chilled water pipe of the downstream chiller.  
If return chilled water control is required on chillers piped in series, the common point return  
chilled water sensor should be installed. If this sensor is not installed, the return chilled water  
sensor of the downstream chiller must be relocated to the return chilled water pipe of the  
upstream machine.  
To properly control the common supply point temperature sensor when chillers are piped in  
parallel, the water flow through the shutdown chillers must be isolated so that no water by-pass  
around the operating chiller occurs. The common point sensor option must not be used if water  
bypass around the operating chiller is occurring.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Machine Communication Wiring  
Refer to the machine’s Installation Instructions and Carrier Comfort Network Interface section  
for information on machine communication wiring.  
Lead/Lag Operation  
The PIC control provides the ability to operate 2 chillers in the LEAD/LAG mode. It also  
provides the additional ability to start a designated standby chiller when either the lead or lag  
chiller is faulted and capacity requirements are not met. The lead/lag option operates in CCN  
mode only. If any other chiller configured for lead/lag is set to the LOCAL or OFF modes, it will  
be unavailable for lead/lag operation.  
Note:  
Lead/lag configuration is viewed and edited in Lead/Lag, under the Equipment Configu-  
ration table of the Service menu. Lead/lag status during machine operation is viewed in  
the MAINT04 table in the Control Algorithm Status table.  
Lead/Lag Chiller Configuration and Operation  
The configured lead chiller is identified when the LEAD/LAG SELECT value for that chiller is  
configured to the value of ‘‘1.’’ The configured lag chiller is identified when the LEAD/LAG  
SELECT for that chiller is configured to the value of ‘‘2.’’ The standby chiller is configured to a  
value of ‘‘3.’’ A value of ‘‘0’’ disables the lead/lag in that chiller.  
To configure the LAG ADDRESS value on the LEAD/LAG Configuration table, always use  
the address of the other chiller on the system for this value. Using this address will make it  
easier to rotate the lead and lag machines.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the address assignments placed into the LAG ADDRESS and STANDBY ADDRESS  
values conflict, the lead/lag will be disabled and an alert (!) message will occur. For example, if  
the LAG ADDRESS matches the lead machine’s address, the lead/lag will be disabled and an  
alert (!) message will occur. The lead/lag maintenance screen (MAINT04) will display the  
message ‘INVALID CONFIG’ in the LEAD/LAG CONFIGURATION and CURRENT MODE  
fields.  
The lead chiller responds to normal start/stop controls such as occupancy schedule, forced  
start/stop, and remote start contact inputs. After completing start up and ramp loading, the PIC  
evaluates the need for additional capacity. If additional capacity is needed, the PIC initiates the  
start up of the chiller configured at the LAG ADDRESS. If the lag chiller is faulted (in alarm) or is  
in the OFF or LOCAL modes, then the chiller at the STANDBY ADDRESS (if configured) is  
requested to start. After the second chiller is started and is running, the lead chiller shall monitor  
conditions and evaluate whether the capacity has reduced enough for the lead chiller to sustain  
the system alone. If the capacity is reduced enough for the lead chiller to sustain the CONTROL  
POINT temperatures alone, then the operating lag chiller is stopped.  
If the lead chiller is stopped in CCN mode for any reason other than an alarm (*) condition,  
then the lag and standby chillers are stopped. If the configured lead chiller stops for and alarm  
condition, then the configured lag chiller takes the lead chiller’s place as the lead chiller and the  
standby chiller serves as the lag chiller.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the configured lead chiller does not complete the start-up before the PRESTART FAULT  
TIMER (user configured value) elapses, then the lag chiller shall be started and the lead chiller  
will shut down. The lead chiller then monitors the start request from the acting lead chiller to  
start. The PRESTART FAULT TIMER is initiated at the time of a start request. The PRESTART  
FAULT TIMER’s function is to provide a timeout in the event that there is a prestart alert  
condition preventing the machine from starting in a timely manner. The timer is configured  
under Lead/Lag, found in the Equipment Configuration table of the Service menu.  
If the lag chiller does not achieve start-up before the PRESTART FAULT TIMER elapses,  
then the lag chiller shall be stopped and the standby chiller will be requested to start, if  
configured and ready.  
Standby Chiller Configuration and Operation  
The configured standby chiller is identified as such by having the LEAD/LAG SELECT  
configured to the value of ‘‘3.’’ The standby chiller can only operate as a replacement for the lag  
chiller if one of the other two chillers is in an alarm (*) condition (as shown on the LID panel). If  
both lead and lag chillers are in an alarm (*) condition, the standby chiller shall default to  
operate in CCN mode based on its configured Occupancy Schedule and remote contacts input.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Lag Chiller Start-Up Requirements  
Before the lag chiller can be started, the following conditions must be met:  
1. Lead chiller ramp loading must be complete.  
2. Lead chiller CHILLED WATER temperature must be greater than the CONTROL POINT  
plus 1/2 the WATER/BRINE DEADBAND.  
Note: The chilled water temperature sensor may be the leaving chilled water sensor, the return  
water sensor, the common supply water sensor, or the common return water sensor,  
depending on which options are configured and enabled.  
3. Lead chiller ACTIVE DEMAND LIMIT value must be greater than 95% of full load amps.  
4. Lead chiller temperature pulldown rate of the CHILLED WATER temperature is less than  
0.5° F (0.27° C) per minute.  
5. The lag chiller status indicates it is in CCN mode and is not faulted. If the current lag chiller  
is in an alarm condition, then the standby chiller becomes the active lag chiller, if it is  
configured and available.  
6. The configured LAG START TIMER entry has elapsed. The LAG START TIMER shall be  
started when the lead chiller ramp loading is completed. The LAG STARTTIMER entry is  
accessed by selecting Lead/Lag from the Equipment Configuration table of the Service  
menu.  
When all of the above requirements have been met, the lag chiller is forced to a START  
mode. The PIC control then monitors the lag chiller for a successful start. If the lag chiller fails to  
start, the standby chiller, if configured, is started.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Lag Chiller Shutdown Requirements  
The following conditions must be met in order for the lag chiller to be stopped.  
1. Lead chiller COMPRESSOR MOTOR LOAD value is less than the lead chiller percent  
capacity plus 15%.  
Note: Lead chiller percent capacity = 100 – LAG PERCENT CAPACITY  
The LAG PERCENT CAPACITY value is configured on the Lead/Lag Configuration screen.  
2. The lead chiller chilled water temperature is less than the CONTROL POINT plus 1/2 of the  
WATER/BRINE DEADBAND.  
3. The configured LAG STOP TIMER entry has elapsed. The LAG STOP TIMER is started  
when the CHILLED WATER TEMPERATURE is less than the CHILLED WATER  
CONTROL POINT plus 1/2 of the WATER/BRINE DEADBAND and the lead chiller  
COMPRESSOR MOTOR LOAD is less than the lead chiller percent capacity plus 15%. The  
timer is ignored if the chilled water temperature reaches 3° F (1.67° C) below the  
CONTROL POINT and the lead chiller COMPRESSOR MOTOR LOAD value is less than  
the lead chiller percent capacity plus 15%.  
Faulted Chiller Operation  
If the lead chiller shuts down on an alarm (*) condition, it stops communication to the lag and  
standby chillers. After 30 seconds, the lag chiller will now become the acting lead chiller and will  
start and stop the standby chiller, if necessary.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the lag chiller faults when the lead chiller is also faulted, the standby chiller reverts to a  
stand-alone CCN mode of operation.  
If the lead chiller is in an alarm (*) condition (as shown on the LID panel), the RESET softkey  
is pressed to clear the alarm, and the chiller is placed in the CCN mode, the lead chiller will now  
communicate and monitor the RUN STATUS of the lag and standby chillers. If both the lag and  
standby chillers are running, the lead chiller will not attempt to start and will not assume the role  
of lead chiller until either the lag or standby chiller shuts down. If only one chiller is running, the  
lead chiller will wait for a start request from the operating chiller. When the configured lead  
chiller starts, it assumes its role as lead chiller.  
Load Balancing  
When the LOAD BALANCE OPTION is enabled, the lead chiller will set the ACTIVE DE-  
MAND LIMIT in the lag chiller to the lead chiller’s COMPRESSOR MOTOR LOAD value. This  
value has limits of 40% to 100%. When setting the lag chiller ACTIVE DEMAND LIMIT, the  
CONTROL POINT shall be modified to a value of 3° F (1.67° C) less than the lead chiller’s  
CONTROL POINT value. If the LOAD BALANCE OPTION is disabled, the ACTIVE DEMAND  
LIMIT and the CONTROL POINT are forced to the same value as the lead chiller.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Auto. Restart After Power Failure  
When an autorestart condition occurs, each chiller may have a delay added to the start-up  
sequence, depending on its lead/lag configuration. The lead chiller does not have a delay. The  
lag chiller has a 45-second delay. The standby chiller has a 90-second delay. The delay time is  
added after the chiller water flow verification. The PIC controls ensure that the guide vanes are  
closed. After the guide vane position is confirmed, the delay for lag and standby chiller occurs  
prior to energizing the oil pump. The normal start-up sequence then continues. The auto. restart  
delay sequence occurs whether the chiller is in CCN or LOCAL mode and is intended to stagger  
the compressor motors from being energized simultaneously. This will help reduce the inrush  
demands on the building power system.  
Ice Build Control  
Ice build control automatically sets the chilled WATER/BRINE CONTROL POINT of the  
machine from normal operation set point temperature to a temperature where an ice building  
operation for thermal storage can be accomplished.  
Note:  
For ice build control to properly operate, the PIC controls must be placed in CCN mode.  
See Figure 16 and Figure 17.  
The PIC can be configured for ice build operation. Configuration of ice build control is  
accomplished through entries in the Config table, Ice Build Setpoint table, and the Ice Build  
Time Schedule table. Figure 16 and Figure 17 show how to access each entry.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The Ice Build Time Schedule defines the period during which ice build is active if the ice build  
option is ENABLED. If the Ice Build Time Schedule overlaps other schedules defining time, then  
the Ice Build Time Schedule shall take priority. During the ice build period, the WATER/BRINE  
CONTROL POINT is set to the ICE BUILD SETPOINT for temperature control. The ICE BUILD  
RECYCLE OPTION and ICE BUILD TERMINATION entries from a screen in the Config  
(configuration) table provide options for machine recycle and termination of ice build cycle,  
respectively. Termination of ice build can result from the ENTERING CHILLED WATER/BRINE  
temperature being less than the ICE BUILD SETPOINT, opening of the REMOTE CONTACT  
inputs from an ice level indicator, or reaching the end of the Ice Build Time Schedule.  
Ice Build Initiation  
The Ice Build Time Schedule provides the means for activating ice build. The ice build time  
table is named OCCPC02S.  
If the Ice Build Time Schedule is OCCUPIED and the ICE BUILD OPTION is ENABLED, then  
ice build is active and the following events automatically take place (unless overridden by a  
higher authority CCN device):  
1.  
2.  
3.  
Force CHILLER START/STOP to START.  
Force WATER/BRINE CONTROL POINT to the ICE BUILD SETPOINT.  
Remove any force (Auto) on the ACTIVE DEMAND LIMIT.  
Note:  
Items 1-3 (shown above) shall not occur if the chiller is configured and operating as a lag  
Download from Www.Somanuals.com. All Manuals Search And Download.  
or standby chiller for lead/lag and is actively controlled by a lead chiller. The lead chiller  
communicates the ICE BUILD SETPOINT, desired CHILLER START/STOP state, and  
ACTIVE DEMAND LIMIT to the lag or standby chiller as required for ice build, if config-  
ured to do so.  
Start-Up/Recycle Operation  
If the machine is not running when ice build activates, then the PIC checks the following  
parameters, based on the ICE BUILD TERMINATION value, to avoid starting the compressor  
unnecessarily:  
• if ICE BUILD TERMINATION is set to the TEMPERATURE ONLY OPTION and the  
ENTERING CHILLED WATER temperature is less than or equal to the ICE BUILD  
SETPOINT;  
• if ICE BUILD TERMINATION is set to the CONTACTS ONLY OPTION and the  
remote contacts are open;  
• if the ICE BUILD TERMINATION is set to the BOTH (temperature and contacts)  
option and ENTERING CHILLED WATER temperature is less than or equal to the  
ICE BUILD SETPOINT and remote contacts are open.  
The ICE BUILD RECYCLE OPTION determines whether or not the PIC will go into a  
RECYCLE mode. If the ICE BUILD RECYCLE OPTION is set to DSABLE (disable) when the  
ice build terminates, the PIC will revert back to normal temperature control duty. If the ICE  
BUILD RECYCLE OPTION is set to ENABLE, when ice build terminates, the PIC will go into an  
ICE BUILD RECYCLE mode and the chilled water pump relay will remain energized to keep the  
Download from Www.Somanuals.com. All Manuals Search And Download.  
chilled water flowing. If the entering CHILLED WATER/BRINE TEMPERATURE increases  
above the ICE BUILD SETPOINT plus the RECYCLE DELTA T value, the compressor will  
restart and control the CHILLED WATER/BRINE TEMPERATURE to the ICE BUILD  
SETPOINT.  
Temperature Control During Ice Build  
During ice build, the capacity control algorithm uses the WATER/BRINE CONTROL POINT  
minus 5 F (2.7 C) to control the LEAVING CHILLED WATER temperature. The ECW OPTION  
and any temperature reset option are ignored during ice build. The 20 mA DEMAND LIMIT  
OPTION is also ignored during ice build.  
Termination of Ice Build  
Ice build termination occurs under the following conditions:  
1.  
2.  
Ice Build Time Schedule — When the Ice Build Time Schedule transitions to  
UNOCCUPIED, ice build operation shall terminate.  
ECW TEMPERATURE — Termination of compressor operation, based on temperature,  
shall occur if the ICE BUILD TERMINATION is set to the ICE BUILD TERMINATION TEMP  
option and the ENTERING CHILLED WATER temperature is less than the ICE BUILD  
SETPOINT. If the ICE BUILD RECYCLE OPTION is set to ENABLE, a recycle shutdown  
occurs and recycle start-up shall be based on LEAVING CHILLED WATER temperature  
being greater than the WATER/BRINE CONTROL POINT plus RECYCLE DELTA T.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Remote Contacts/Ice Level Input — Termination of compressor operation occurs when ICE  
BUILD TERMINATION is set to CONTACTS ONLY OPTION and the remote contacts are  
open. In this case, the contacts are provided for ice level termination control. The remote  
contacts can still be opened and closed to start and stop the chiller when the Ice Build Time  
Schedule is UNOCCUPIED. The contacts are used to stop the ICE BUILD mode when the  
Ice Build Time Schedule is OCCUPIED.  
4. ECW TEMPERATURE and Remote Contacts — Termination of compressor operation shall  
occur when ICE BUILD TERMINATION is set to BOTH (temperature and contacts) option  
and the previously described conditions for ECW TEMPERATURE and remote contacts  
have occurred.  
Note: Overriding the CHILLER START/STOP, WATER/BRINE CONTROL POINT, and  
ACTIVE DEMAND LIMIT variables by CCN devices (with a priority less than 4) during  
the ice build period is not possible. However, overriding can be accomplished with CCN  
during two chiller lead/lag.  
Return to Non-Ice Build Operations  
Upon termination of ice build, the machine shall return to normal temperature control and  
start/stop schedule operation. If the CHILLER START/STOP or WATER/BRINE CONTROL  
POINT has been forced (with a priority less than 4), prior to entering ice build operation, then  
chiller START/STOP and WATER/BRINE CONTROL POINT forces will be removed.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Attach to Network Device Control  
On the Service menu, one of the selections is ATTACH TO NETWORK DEVICE. This table  
serves the following purposes:  
• to upload the Occupancy Schedule Number (if changed) for OCCPC03S, as defined  
in the Service01 table  
• to attach the LID to any CCN device, if the machine has been connected to a CCN  
Network. This may include other PIC controlled chillers.  
• to change to a new PSIO or LID module or upgrade software.  
Figure 23 illustrates the ATTACH TO NETWORK DEVICE table. The Local description is  
always the PSIO module address of the machine the LID is mounted on. Whenever the  
controller identification of the PSIO is changed, this change is reflected on the bus and address  
for the LOCAL DEVICE of the ATTACH TO DEVICE screen automatically. See Figure 17.  
Whenever the ATTACH TO NETWORK DEVICE table is entered, the LID erases information  
on the module to which it was attached in order to make room for another device. Therefore, it is  
then required to attach to a CCN module when this screen is entered, even if the LID is attached  
back to the original module. When the ATTACH softkey is pressed, the message ‘‘UPLOADING  
TABLES, PLEASE WAIT’’ flashes. The LID will then upload the highlighted device or module. If  
the module address cannot be found, the message ‘‘COMMUNICATION FAILURE’’ will appear.  
The LID will then revert back to the ATTACH TO DEVICE screen. The upload process time for  
various CCN modules is different for each module. In general, the uploading process will take 3  
to 5 minutes.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Attaching to Other CCN Modules  
If the machine PSIO has been connected to a CCN Network or other PIC controlled chillers  
through CCN wiring, the LID can be used to view or change parameters on the other controllers.  
Other PIC machines can be viewed and set points changed (if the other unit is in CCN control),  
if desired from this particular LID module.  
To view the other devices, move to the ATTACH TO NETWORK DEVICE table. Move the  
highlight bar to any device number. Press SELECT softkey to change the bus number and  
address of the module to be viewed. Press EXIT softkey to move back to the ATTACH TO  
NETWORK DEVICE table. If the module number is not valid, the ‘‘COMMUNICATION  
FAILURE’’ message will show and a new address number should be entered or the wiring  
checked. If the model is communicating properly, the ‘‘UPLOAD IN PROGRESS’’ message will  
flash and the new module can now be viewed.  
Whenever there is a question regarding which CCN module the LID is currently showing,  
check the device name descriptor on the upper left hand corner of the LID screen. See  
Figure 23.  
When the CCN device has been viewed, the ATTACH TO NETWORK DEVICE table should  
now be used to attach to the PSIO that is on the machine. Move to the ATTACH TO NETWORK  
DEVICE table and press the ATTACH softkey to upload the LOCAL device. The PSIO for the  
19XT will now be uploaded.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Note: The LID will not automatically re-attach to the PSIO module on the machine. Press the  
ATTACH softkey to attach to LOCAL DEVICE and view the machine PSIO.  
Click here for Figure 23 — Example of Attach to Network Device Screen  
Service Operation  
An overview of the menu-driven programs available for Service Operation is shown in  
Figure 17.  
To Log On  
1. On the Menu screen, press SERVICE. The keys now correspond to the numerals 1, 2, 3, 4.  
2. Press the four digits of your password, one at a time. An asterisk (*) appears as you enter  
each digit.  
ENTER A 4 DIGIT PASSWORD:*  
1
2
3
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
The menu bar (Next-Previous-Select-Exit) is displayed to indicate that you have success-  
fully logged on.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
If the password is entered incorrectly, an error message is displayed. If this occurs, return to  
Step 1 and try logging on again.  
INVALID PASSWORD  
1
2
3
4
Note: The initial factory set password is 1-1-1-1.  
To Log Off  
Access the Log Out of Device table of the Service menu in order to password-protect the  
Service menu. The LID will automatically sign off and password-protect itself if a key is not  
pressed for 15 minutes. The LID default screen is then displayed.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Holiday Scheduling (Figure 24)  
The time schedules may be configured for special operation during a holiday period. When  
modifying a time period, the ‘‘H’’ at the end of the days of the week field signifies that the period  
is applicable to a holiday. (See Figure 24.)  
The Broadcast function must be activated for the holidays configured in the Holidef tables to  
work properly. Access the Brodefs table in the Equipment Configuration table and answer  
‘‘Yes’’ to the activated function. However, when the machine is connected to a CCN Network,  
only one machine or CCN device can be configured to be the broadcast device. The controller  
that is configured to be the broadcaster is the device responsible for transmitting holiday, time,  
and daylight-savings dates throughout the network.  
To view or change the holiday periods for up to 18 different holidays, perform the following  
operation:  
1.  
At the Menu screen, press SERVICE to access the Service menu.  
STATUS  
SCHEDULE SETPOINT  
SERVICE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. If not logged on, follow the instructions for To Log On or To Log Off. Once logged on, press  
NEXT until Equipment Configuration is highlighted.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
3. Once Equipment Configuration is highlighted, press SELECT to access.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
4. Press NEXT until Holidef is highlighted. This is the Holiday Definition table.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Press SELECT to enter the Data Table Select screen. This screen lists 18 holiday tables.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
6. Press NEXT to highlight the holiday table that you wish to view or change. Each table is one  
holiday period, starting on a specific date, and lasting up to 99 days.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
7. Press SELECT to access the holiday table. The Configuration Select table now shows the  
holiday start month and day, and how many days the holiday period will last.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Press NEXT or PREVIOUS to highlight the month, day, or duration.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
9. Press SELECT to modify the month, day, or duration.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
10. Press INCREASE or DECREASE to change the selected value.  
INCREASE  
DECREASE  
QUIT  
ENTER  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11. Press ENTER to save the changes.  
INCREASE  
DECREASE  
QUIT  
ENTER  
12. Press EXIT to return to the previous menu.  
NEXT  
PREVIOUS  
SELECT  
EXIT  
Click here for Figure 24 — Example of Holiday Period Screen  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start-Up/Shutdown/Recycle Sequence (Figure 25)  
Local Start-Up  
Local start-up (or a manual start-up) is initiated by pressing the LOCAL menu softkey which  
is on the default LID screen. Local start-up can proceed when Time Schedule 01 is in  
OCCUPIED mode, and after the internal 15-minute start-to-start timer and the stop-to-start  
inhibit timer have expired.  
The chiller start/stop status point on the Status01 table may be overridden to start,  
regardless of the time schedule, in order to locally start the unit. Also, the remote contacts may  
be enabled through the LID and closed to initiate a start-up.  
Whenever the chiller is in LOCAL control mode, the PIC will wait for Time Schedule 01 to  
become occupied and the remote contacts to close, if enabled. The PIC will then perform a  
series of pre-start checks to verify that all pre-start alerts and safeties are within the limits  
shown in Table 3. The run status line on the LID now reads ‘‘Starting.’’ If the checks are  
successful, the chilled water/brine pump relay will be energized. Five seconds later, the  
condenser pump relay is energized. Thirty seconds later the PIC monitors the chilled water and  
WATER FLOW VERIFY TIME  
condenser water flow switches, and waits until the  
configured, default 5 minutes) to confirm flow. After flow is verified, the chilled water/brine  
CONTROL POINT DEADBAND  
. If the temperature is less  
(operator  
temperature is compared to  
plus  
than or equal to this value, the PIC will turn off the condenser pump relay and go into a  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RECYCLE mode. If the water/brine temperature is high enough, the start-up sequence  
continues on to check the guide vane position. If the guide vanes are more than 6% open, the  
start-up waits until the PIC closes the vanes. If the vanes are closed, and the oil pump pressure  
is less than 4 psid (28 kPad), the oil pump relay will then be energized. The PIC then waits until  
the OIL PRESS (Pressure) VERIFY TIME (operator configured, default 15 seconds) for oil  
pressure to reach 18 psid (124 kPad). After oil pressure is verified, the PIC waits 10 seconds,  
and then the compressor start relay (1CR) is energized to start the compressor.  
Click here for Figure 25 — Control Sequence  
Failure to verify any of the requirements up to this point will result in the PIC aborting the start  
and displaying the applicable pre-start mode of failure on the LID default screen. A pre-start  
failure does not advance the starts in 12 hours counter. Any failure after the 1CR relay has  
energized results in a safety shutdown, advances the starts in the 12 hours counter by one, and  
displays the applicable shut-down status on the LID display.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Shutdown Sequence  
Shutdown of the machine can occur if any of the following events happen:  
• the STOP button is pressed for at least one second (the alarm light will blink once to  
confirm stop command)  
• recycle condition is present (see Chilled Water Recycle Mode section)  
• time schedule has gone into UNOCCUPIED mode  
• remote contact opens  
• the start/stop status is overridden to stop from the CCN network or the LID  
When a stop signal occurs, the shutdown sequence first stops the compressor by  
deactivating the start relay. A status message of ‘‘SHUTDOWN IN PROGRESS, COMPRES-  
SOR DEENERGIZED’’ is displayed. The guide vanes are then brought to the closed position.  
The oil pump relay and the chilled water/brine pump relay are shut down 60 seconds after the  
compressor stops. The condenser water pump will be shut down when the CONDENSER  
REFRIGERANT TEMP is less than the CONDENSER PRESSURE OVERRIDE minus 5 psi  
(34 kPa) or is less than or equal to the ENTERING CONDENSER WATER TEMP plus 3° F  
(2° C). The stop-to-start timer will now begin to count down. If the start-to-start timer is still  
greater than the value of the start-to-stop timer, then this time is now displayed on the LID.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Certain conditions during shutdown will change this sequence:  
• if the COMPRESSOR MOTOR LOAD is greater than 10% after shutdown, or the  
starter contacts remain energized, the oil pump and chilled water pump remain ener-  
gized and the alarm is displayed  
• if the ENTERING CONDENSER WATER temperature is greater than 115 F (46 C) at  
shutdown, the condenser pump will be deenergized after the 1CR compressor start  
relay  
• if the machine shuts down due to low refrigerant temperature, the chilled water pump  
will stay running until the LEAVING CHILLED WATER is greater than CONTROL  
POINT, plus 5° F (3° C)  
Automatic Soft Stop Amps Threshold  
The SOFT STOP AMPS THRESHOLD closes the guide vanes of the compressor  
automatically when a non-recycle, non-alarm stop signal occurs before the compressor motor is  
deenergized.  
If the STOP button is pressed, the guide vanes close to a preset amperage percent or until  
the guide vane is less than 2% open. The compressor will then shut off.  
If the machine enters an alarm state or if the compressor enters a RECYCLE mode, the  
compressor will be deenergized immediately.  
To activate SOFT STOP AMPS THRESHOLD, view the bottom of Service1 table. Set the  
SOFT STOP AMPS THRESHOLD value to the percentage amps at which the motor will shut  
down. The default setting is 100% amps (no Soft Stop).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
When the SOFT STOP AMPS THRESHOLD is being applied, a status message  
‘‘SHUTDOWN IN PROGRESS, COMPRESSOR UNLOADING’’ is shown.  
Chilled Water Recycle Mode  
The machine may cycle off and wait until the load increases to restart again when the  
compressor is running in a lightly loaded condition. This cycling of the chiller is normal and is  
known as recycle. A recycle shutdown is initiated when any of the following conditions are true:  
• when in LCW control, the difference between the LEAVING CHILLED WATER tem-  
perature and ENTERING CHILLED WATER temperature is less than the RECYCLE  
SHUTDOWN DELTA T (found in the SERVICE 1 table) and the LEAVING CHILLED  
WATER TEMP is below the CONTROL POINT, and the CONTROL POINT has not  
increased in the last 5 minutes  
• when ECW CONTROL OPTION is enabled, the difference between the ENTERING  
CHILLED WATER temperature and the LEAVING CHILLED WATER temperature is  
less than the RECYCLE SHUTDOWN DELTA T (found in the SERVICE 1 table) and  
the ENTERING CHILLED WATER TEMPERATURE is below the CONTROL POINT,  
and the CONTROL POINT has not increased in the last 5 minutes  
• when the LEAVING CHILLED WATER temperature is within 3° F (2° C) of the BRINE  
REFRIG TRIPPOINT  
When the machine is in RECYCLE mode, the chilled water pump relay remains energized so  
that the chilled water temperature can be monitored for increasing load. The recycle control  
uses RECYCLE RESTART DELTA T to check when the compressor should be restarted. This  
Download from Www.Somanuals.com. All Manuals Search And Download.  
is an operator-configured function which defaults to 5° F (3° C). This value is viewed/modified  
on the Service1 table. The compressor will restart when:  
• in LCW CONTROL the LEAVING CHILLED WATER temperature is greater than the  
CONTROL POINT plus the RECYCLE RESTART DELTA T; or  
• in ECW CONTROL, the ENTERING CHILLED WATER temperature is greater than  
the CONTROL POINT plus the RECYCLE RESTART DELTA T  
Once these conditions are met, the compressor shall initiate a start-up, with a normal start-up  
sequence.  
An alert condition may be generated if 5 or more RECYCLE STARTUPs occur in less than 4  
hours. This excessive recycling can reduce machine life. Compressor recycling due to  
extremely low loads should be reduced. To reduce compressor recycling, use the time schedule  
to shut the machine down during low load operation or increase the machine load by running  
the fan systems. If the hot gas bypass is installed, adjust the values to ensure that hot gas is  
energized during light load conditions. Increase the RECYCLE RESTART DELTA T on the  
Service1 table to lengthen the time between restarts.  
The machine should not be operated below design minimum load without a hot gas bypass  
installed on the machine.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Shutdown  
A safety shutdown is identical to a manual shutdown with the exception that the LID will  
display the reason for the shutdown, the alarm light will blink continuously, and the spare alarm  
contacts will be energized. A safety shutdown requires that the RESET softkey be pressed in  
order to clear the alarm. If the alarm is still present, the alarm light will continue to blink. Once  
the alarm is cleared, the operator must press the CCN or LOCAL softkeys to restart the  
machine.  
CAUTION  
CAUTION  
!
Do not reset starter loads or any other starter safety for 30 seconds after the  
compressor has stopped. Voltage output to the compressor start signal is main-  
tained for 10 seconds to determine starter fault.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Before Initial Start-Up  
Job Data Required  
• list of applicable design temperatures and pressures (product data submittal)  
• machine certified drawings  
• starting equipment details and wiring diagrams  
• diagrams and instructions for special controls or options  
• 17/19EX Installation Instructions  
• pumpout unit instructions  
Equipment Required  
• mechanic’s tools (refrigeration)  
• digital volt-ohmmeter (DVM)  
• clamp-on ammeter  
• electronic leak detector  
• absolute pressure manometer or wet-bulb vacuum indicator (Figure 26)  
• 500 v insulation tester (megohmmeter) for compressor motors with nameplate volt-  
age of 600 v or less, or a 5000-v insulation tester for compressor motor rated above  
600 v  
Using the Utility Vessel and Pumpout System  
Refer to Pumpout and Refrigerant Transfer Procedures section for: pumpout system  
preparation, refrigerant transfer, and machine evacuation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Remove Shipping Packaging  
Remove any packaging material from the control center, power panel, guide vane actuator,  
motor cooling and oil reclaim solenoids, motor and bearing temperature sensor covers, and the  
factory-mounted starter.  
Open Drive Motor  
CAUTION  
CAUTION  
!
The motor may be provided with a shipping brace or shipping bolt (normally  
painted yellow) to prevent shaft movement during transit. It must be removed  
prior to operation. See  
.
Figure 27  
Click here for Figure 26 — Typical Wet-Bulb Type Vacuum Indicator  
Click here for Figure 27 — Shipping Bolt on Open Drive Motor  
The motor should be inspected for any temporary, yellow caution tags whose legends  
convey information concerning actions necessary before the motor can be safely operated. Any  
Download from Www.Somanuals.com. All Manuals Search And Download.  
slushing compound on the shaft or other parts must be removed using a petroleum type solvent  
and observing proper safety precautions.  
Note: If the motor utilized a shipping bolt for restraining the rotor, the Westinghouse logo must  
be installed over the hole in the endcover. The logo, the gasket, and hardware can be  
found with the parts that have been shipped loose. (Usually these are packed inside of  
the main power lead box.)  
Open-Drive Motor Electrical Connection  
All interconnecting wiring for controls and grounding should be in strict accordance with both  
the National Electrical Code and any local requirements.  
The main lead box furnished with the motor has been sized to provide adequate space for  
the make-up of the connections between the motor lead cables and the incoming power cables.  
The bolted joints between the motor lead and the power cables must be made and insulated in  
a workman-like manner following the best trade practices.  
Fabricated motors are provided with 2 stainless steel grounding pads drilled and tapped with  
the NEMA 2-hole pattern (two 1/2 -13 tapped holes on 1 3/4 in. centers). Fan cooled cast  
frames are provided with a special grounding bolt. The motor should be grounded by a proper  
connection to the electrical system ground.  
The rotation direction of the motor will be as shown by either a nameplate on the motor or the  
certified drawing. The required phase rotation of the incoming power for this motor rotation may  
Download from Www.Somanuals.com. All Manuals Search And Download.  
also be stated. If either is unknown, the correct sequence can be determined in the following  
manner: While the motor is uncoupled from the load, start the motor and observe the direction  
of rotation. Allow the motor to achieve full speed before disconnecting it from the power source.  
Refer to Open-Drive Motor Pre-Start Checks for information concerning initial start-up. If  
resulting rotation is incorrect, it can be reversed by interchanging any 2 incoming cables.  
Open-Drive Motor Auxiliary Devices  
Auxiliary devices such as resistance temperature detectors, thermocouples, thermoguards,  
etc., will generally terminate on terminal blocks located in the auxiliary terminal box on the  
motor. Other devices may terminate on their own enclosures elsewhere on the motor. Such  
information can be obtained by referring to the certified drawing. Information regarding terminal  
designation and the connection of auxiliary devices can be obtained from auxiliary drawings  
referenced by the outline drawing.  
If the motor is provided with internal space heaters, the incoming voltage supplied to them  
must be exactly as shown by either a nameplate on the motor or the outline drawing for proper  
heater operation. Caution must be exercised anytime contact is made with the incoming space  
heater circuit as space heater voltage is often automatically applied when the motor is shut  
down.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Open Oil Circuit Valves  
Check that the oil filter isolation valves are open by removing the valve cap and checking the  
valve stem. (See Scheduled Maintenance, Changing Oil Filter.)  
Torque All Gasketed Joints  
Gaskets normally have relaxed by the time the machine arrives at the jobsite. Tighten all  
gasketed joints to ensure a leak tight machine.  
Note:  
On open-drive machines, check the machine cold alignment. Refer to Machine Align-  
ment in the Maintenance section.  
Check Machine Tightness  
Figure 28 outlines the proper sequence and procedures for leak testing.  
17/19EX chillers are shipped with the refrigerant contained in the utility vessel and the oil  
charge shipped in the compressor. The cooler/condenser vessels will have a 15 psig (103 kPa)  
refrigerant charge. Units may be ordered with the refrigerant shipped separately, along with a  
15 psig (103 kPa) nitrogen-holding charge in each vessel. To determine if there are any leaks,  
the machine should be charged with refrigerant. Use an electronic leak detector to check all  
flanges and solder joints after the machine is pressurized. If any leaks are detected, follow the  
leak test procedure.  
If the machine is spring isolated, keep all springs blocked in both directions in order to  
Download from Www.Somanuals.com. All Manuals Search And Download.  
prevent possible piping stress and damage during the transfer of refrigerant from vessel to  
vessel during the leak test process, or any time refrigerant is transferred. Adjust the springs  
when the refrigerant is in operating condition, and when the water circuits are full.  
Refrigerant Tracer  
Carrier recommends the use of an environmentally acceptable refrigerant tracer for leak  
testing with an electronic detector or halide torch.  
Ultrasonic leak detectors also can be used if the machine is under pressure.  
WARNING  
WARNING  
!
Do not use air or oxygen as a means of pressurizing the machine. Some mixtures  
of HFC-134a and air can undergo combustion.  
Leak Test Machine  
Due to regulations regarding refrigerant emissions and the difficulties associated with  
separating contaminants from refrigerant, Carrier recommends the following leak test  
procedures. See Figure 28 for an outline of the leak test procedures. Refer to Table 5A and  
Table 5B for refrigerant pressure/temperature values and to Pumpout and Refrigerant Transfer  
Procedures section.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. If the pressure readings are normal for machine condition:  
a. Evacuate the nitrogen holding charge from the vessels, if present.  
b. Raise the machine pressure, if necessary, by adding refrigerant until pressure is at  
equivalent saturated pressure for the surrounding temperature. Follow the pumpout  
procedures in the Pumpout and Refrigerant Transfer Procedures section.  
WARNING  
WARNING  
!
Never charge liquid refrigerant into the machine if the pressure in the machine is  
less than 35 psig (241 kPa). Charge as a gas only, with the cooler and condenser  
pumps running, until this pressure is reached, using PUMPDOWN LOCKOUT and  
TERMINATE LOCKOUT mode on the PIC. Flashing of liquid refrigerant at low  
pressures can cause tube freezeup and considerable damage.  
c. Leak test machine as outlined in Steps 3 -9.  
2. If the pressure readings are abnormal for machine condition:  
a. Prepare to leak test machines shipped with refrigerant (Step 2h).  
b. Check for large leaks by connecting a nitrogen bottle and raising the pressure to 30 psig  
(207 kPa). Soap test all joints. If the test pressure holds for 30 minutes, prepare the test  
for small leaks (Steps 2g - h).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
c. Plainly mark any leaks which are found.  
d. Release the pressure in the system.  
e. Repair all leaks.  
f. Retest the joints that were repaired.  
g. After successfully completing the test for large leaks, remove as much nitrogen, air, and  
moisture as possible, given the fact that small leaks may be present in the system. This  
can be accomplished by following the dehydration procedure, outlined in the Machine  
Dehydration section.  
h. Slowly raise the system pressure to the equivalent saturated pressure for the  
surrounding temperature but no less than 35 psig (241 kPa) by adding HFC-134a  
refrigerant. Proceed with the test for small leaks (Steps 3-9).  
3. Check the machine carefully with an electronic leak detector, halide torch, or soap bubble  
solution.  
4. Leak Determination — If an electronic leak detector indicates a leak, use a soap bubble  
solution, if possible, to confirm. Total all leak rates for the entire machine. Leakage at rates  
greater than 1 lb/year (0.45 kg/year) for the entire machine must be repaired. Note total  
machine leak rate on the start-up report. This leak rate repair is only for new start-ups. See  
operating machine leak rate/repair recommendations in the General Maintenance section.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. If no leak is found during initial start-up procedures, complete the transfer of refrigerant gas  
(see Pumpout and Refrigerant Transfer Procedures section.)  
6. If no leak is found after a retest:  
a. Transfer the refrigerant to the utility vessel or other storage tank and perform a standing  
vacuum test as outlined in the Standing Vacuum Test section.  
b. If the machine fails this test, check for large leaks (Step 2b).  
c. Dehydrate the machine if it passes the standing vacuum test. Follow the procedure in the  
Machine Dehydration section. Charge machine with refrigerant (see Pumpout and  
Refrigerant Transfer Procedures section.)  
7. If a leak is found, pump the refrigerant back into the utility vessel or other storage tank.  
8. Transfer the refrigerant until machine pressure is at 18 in. Hg (41 kPa absolute).  
9. Repair the leak and repeat the procedure, beginning from Step 2g to ensure a leaktight  
repair. (If machine is opened to the atmosphere for an extended period, evacuate it before  
repeating leak test.)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Standing Vacuum Test  
When performing the standing vacuum test, or machine dehydration, use a manometer or a  
wet bulb indicator. Dial gages cannot indicate the small amount of acceptable leakage during a  
short period of time.  
1.  
2.  
Attach an absolute pressure manometer or wet bulb indicator to the machine.  
Evacuate the vessel (see Pumpout and Refrigerant Transfer Procedures section) to at least  
18 in. Hg vac, ref 30-in. bar (41 kPa), using a vacuum pump or the pump-out unit.  
3.  
4.  
Valve off the pump to hold the vacuum and record the manometer or indicator reading.  
a.  
If the leakage rate is less than 0.05 in. Hg (.17 kPa) in 24 hours, the machine is suffi-  
ciently tight.  
b.  
If the leakage rate exceeds 0.05 in. Hg (.17 kPa) in 24 hours, repressurize the vessel and  
test for leaks. If refrigerant is available in the other vessel, pressurize by following Steps  
2-10 of Return Refrigerant to Normal Operating Conditions section. If not, use nitrogen  
and a refrigerant tracer. Raise the vessel pressure in increments until the leak is  
detected. If refrigerant is used, the maximum gas pressure is approximately 70 psig  
(483 kPa) at normal ambient temperature.  
5.  
Repair leak, retest, and proceed with dehydration.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Click here for Table 5A — HFC-134a Pressure — Temperature (F)  
Click here for Figure 28 — 17/19EX Leak Test Procedures  
Click here for Table 5B — HFC-134a Pressure — Temperature (C)  
Machine Dehydration  
Dehydration is recommended if the machine has been open for a considerable period of  
time, if the machine is known to contain moisture, or if there has been a complete loss of  
machine holding charge or refrigerant pressure.  
WARNING  
WARNING  
!
Do not start or megohm test the compressor motor or oil pump motor, even for a  
rotation check, if the machine is under dehydration vacuum. Insulation break-  
down and severe damage may result.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dehydration is readily accomplished at room temperatures. Use of a cold trap (Figure 29)  
may substantially reduce the time required to complete the dehydration. The higher the room  
temperature, the faster dehydration takes place. At low room temperatures, a very deep  
vacuum is required for boiling off any moisture. If low ambient temperatures are involved,  
contact a qualified service representative for the dehydration techniques required.  
Perform dehydration as follows:  
1. Connect a high capacity vacuum pump (5 cfm [.002 m 3/s] or larger is recommended) to the  
refrigerant charging valve (Figure 7 and Figure 8). Tubing from the pump to the machine  
should be as short and as large a diameter as possible to provide least resistance to gas  
flow.  
2. Use an absolute pressure manometer or a wet bulb vacuum indicator to measure the  
vacuum. Open the shutoff valve to the vacuum indicator only when taking a reading. Leave  
the valve open for 3 minutes to allow the indicator vacuum to equalize with the machine  
vacuum.  
3. Open all isolation valves (if present), if the entire machine is to be dehydrated.  
4. With the machine ambient temperature at 60 F (15.6 C) or higher, operate the vacuum  
pump until the manometer reads 29.8 in. Hg vac, ref 30 in. bar. (0.1 psig) (–100.61 kPa) or  
a vacuum indicator reads 35 F (1.7 C). Operate the pump an additional 2 hours.  
Do not apply greater vacuum than 29.82 in. Hg vac (757.4 mm Hg) or go below 33 F (.56 C)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
on the wet bulb vacuum indicator. At this temperature/pressure, isolated pockets of mois-  
ture can turn into ice. The slow rate of evaporation (sublimation) of ice at these low temper-  
atures/pressures greatly increases dehydration time.  
5. Valve off the vacuum pump, stop the pump, and record the instrument reading.  
6. After a 2-hour wait, take another instrument reading. If the reading has not changed,  
dehydration is complete. If the reading indicates vacuum loss, repeat Steps 4 and 5.  
7. If the reading continues to change after several attempts, perform a leak test up to the  
maximum 180 psig (1241 kPa) pressure. Locate and repair the leak, and repeat  
dehydration.  
Click here for Figure 29 — Dehydration Cold Trap  
Inspect Water Piping  
Refer to piping diagrams provided in the certified drawings, and the piping instructions in the  
17/19EX Installation Instructions manual. Inspect the piping to the cooler and condenser. Be  
sure that flow directions are correct and that all piping specifications have been met.  
Piping systems must be properly vented, with no stress on waterbox nozzles and covers.  
Water flows through the cooler and condenser must meet job requirements. Measure the  
pressure drop across cooler and across condenser.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION  
CAUTION  
!
Water must be within design limits, clean, and treated to ensure proper machine  
performance and reduce the potential of tubing damage due to corrosion, scal-  
ing, or erosion. Carrier assumes no responsibility for chiller damage resulting  
from untreated or improperly treated water.  
Check Optional Pumpout Compressor Water Piping  
If the optional storage tank and/or pumpout system are installed, check to ensure the  
pumpout condenser water has been piped in. Check for field-supplied shutoff valves and  
controls as specified in the job data. Check for refrigerant leaks on field-installed piping.  
Check Relief Devices  
Be sure that relief devices have been piped to the outdoors in compliance with the latest  
edition of ANSI/ASHRAE Standard 15 and applicable local safety codes. Piping connections  
must allow for access to the valve mechanism for periodic inspection and leak testing.  
Relief valves are set to relieve at the 225 psig (1551 kPa) machine design pressure.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inspect Wiring  
WARNING  
WARNING  
!
Do not check voltage supply without proper equipment and precautions. Serious  
injury may result. Follow power company recommendations.  
CAUTION  
CAUTION  
!
Do not apply any kind of test voltage, even for a rotation check, if the machine is  
under a dehydration vacuum. Insulation breakdown and serious damage may  
result.  
1.  
2.  
Examine wiring for conformance to job wiring diagrams and to all applicable electrical  
codes.  
On low-voltage compressors (600 v or less) connect voltmeter across the power wires to  
the compressor starter and measure the voltage. Compare this reading with the voltage  
rating on the compressor and starter nameplates.  
3.  
Compare the ampere rating on the starter nameplate with the compressor nameplate. The  
overload trip amps must be 108% to 120% of the rated load amps.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. The starter for a centrifugal compressor motor must contain the components and terminals  
required for PIC refrigeration control. Check certified drawings.  
5. Check the voltage to the following components and compare to the nameplate values: oil  
pump contact, pumpout compressor starter, and power panel.  
6. Be sure that fused disconnects or circuit breakers have been supplied for the oil pump,  
power panel, and pumpout unit.  
7. Check that all electrical equipment and controls are properly grounded in accordance with  
job drawings, certified drawings, and all applicable electrical codes.  
8. Make sure that the customer’s contractor has verified proper operation of the pumps,  
cooling tower fans, and associated auxiliary equipment. This includes ensuring that motors  
are properly lubricated and have proper electrical supply and proper rotation.  
9. Tighten up all wiring connections to the plugs on the SMM, 8-input, and PSIO modules.  
10. Ensure that the voltage selector switch inside the power panel is switched to the incoming  
voltage rating.  
11. On machines with free-standing starters, inspect the power panel to ensure that the  
contractor has fed the wires into the bottom of the panel. Wiring into the top of the panel can  
cause debris to fall into the contactors. Clean and inspect the contactors if this has  
occurred.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Check Insulation Resistance (Hermetic Motor)  
Test the machine compressor motor and its power lead insulation resistance with a 500-v  
insulation tester such as a megohmmeter. (Use a 5000-v tester for motors rated over 600 v.)  
Factory-mounted starters do not require a megohm test.  
1.  
Open the starter main disconnect switch and follow lockout/tagout rules.  
CAUTION  
CAUTION  
!
If the motor starter is a solid-state starter, the motor leads must be disconnected  
from the starter before an insulation test is performed. The voltage generated  
from the tester can damage the starter solid-state components.  
2.  
3.  
With the tester connected to the motor leads, take 10-second and 60-second megohm  
readings as follows:  
6-Lead Motor — Tie all 6 leads together and test between the lead group and ground. Next  
tie leads in pairs, 1 and 4, 2 and 5, and 3 and 6. Test between each pair while grounding the  
third pair.  
3-Lead Motor — Tie terminals 1, 2, and 3 together and test between the group and ground.  
Divide the 60-second resistance reading by the 10-second reading. The ratio, or  
polarization index, must be one or higher. Both the 10- and 60-second readings must be at  
least 50 megohms.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the readings on a field-installed starter are unsatisfactory, repeat the test at the motor with  
the power leads disconnected. Satisfactory readings in this second test indicate the fault is  
in the power leads.  
Note: Unit-mounted starters do not have to be megohm tested.  
Check Insulation Resistance (Open-Drive Motor)  
Before operating voltages is applied to the motor, whether for checking rotation direction or  
for actual operation, the resistance of the stator winding insulation should be measured.  
The test voltage, based on the motor operating voltage, is as follows:  
Operating Voltage  
0- 900  
DC Test Voltage  
500  
1000  
2500  
901- 7000  
7001-14500  
This is particularly important if the motor may have been exposed to excessive dampness  
either during transit or while in storage. A ‘‘megger’’ type instrument can be used to measure  
the insulation resistance. The test voltage should be applied between the entire winding (all  
winding leads connected together) and ground for approximately one minute with the winding at  
ambient temperature. The recommended minimum insulation resistance is determined as  
follows:  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RM =  
Where  
RM =  
KV + 1  
Recommended minimum insulation resistance in megohms at 104° F (40° C) of  
the entire winding.  
KV =  
Rated motor terminal to terminal voltage in kilovolts (1000 volts = 1 KV).  
On a new winding, where the contaminant causing low insulation resistance is generally  
moisture, drying the winding through the proper application of heat will normally increase the  
insulation resistance to an acceptable level. The following are several accepted methods for  
applying heat to a winding:  
1. If the motor is equipped with space heaters, they can be energized to heat the winding.  
2. Direct current (as from a welder) can be passed through the winding. The total current  
should not exceed approximately 50% of rated full load current. If the motor has only 3  
leads, 2 must be connected together to form one circuit through the winding. In this case,  
one phase will carry the full applied current and each of the others, one-half each. If the  
motor has 6 leads (3 mains and 3 neutrals), the 3 phases should be connected into one  
series circuit.  
3. Heated air can be either blown directly into the motor or into a temporary enclosure  
surrounding the motor. The source of heated air should preferably be electrical as opposed  
to fueled (such as kerosene) where a malfunction of the fuel burner could result in carbon  
Download from Www.Somanuals.com. All Manuals Search And Download.  
entering the motor. Caution must be exercised, when heating the motor with any source of  
heat other than self contained space heaters, to raise the winding temperature at a gradual  
rate to allow any entrapped moisture to vaporize and escape without rupturing the  
insulation. The entire heating cycle should extend over 15 to 20 hours.  
Insulation resistance measurements can be made while the winding is being heated.  
However, they must be corrected to 104 F (40 C) for evaluation since the actual insulation  
resistance will decrease with increasing temperature. As an approximation for a new winding,  
the insulation resistance will approximately halve for each 18° F (10° C) increase in insulation  
temperature above the dew point temperature.  
Open-Drive Motor Pre-Start Checks  
To pre-vent damage to the motor, the following steps must be taken prior to initial start-up:  
1.  
2.  
Remove the shaft shipping brace (if supplied).  
For sleeve bearing motors, the oil reservoir must be filled with oil to the correct level. The  
proper oil is a rust and oxidation inhibited, turbine grade oil. The viscosity of the oil must be  
32 ISO (150 SSU) at 100 F (37.7 C). Oil capacity in each of the two bearings is 0.6 gal.  
(2.3 L) per bearing. Use of Carrier Oil Specification PP16-0 is approved (Mobil DTE Light or  
Sun Oil SUNVIS 916).  
3.  
If possible, the shaft should be turned over by hand to ensure that there is free rotation. On  
sleeve bearing motors, the shaft should be moved to both extremes of its end play while it is  
Download from Www.Somanuals.com. All Manuals Search And Download.  
being rotated, and the oil rings should be viewed through the viewing ports in the top of the  
bearing housing to verify free ring rotation.  
4. On fan-cooled motors, the area around he external fan inlet should be checked for loose  
debris that could be drawn into the fan during operation.  
5. All external, factory-made, bolted joints should be checked for any looseness that may have  
occurred in transit. Refer to Table 6 for recommended bolt torques.  
Click here for Table 6 — Recommended Torque  
Carrier Comfort Network Interface  
The Carrier Comfort Network (CCN) communication bus wiring is supplied and installed by  
the electrical contractor. It consists of shielded, 3-conductor cable with drain wire.  
The system elements are connected to the communication bus in a daisy chain  
arrangement. The positive pin of each system element communication connector must be wired  
to the positive pins of the system element on either side of it; the negative pins must be wired to  
the negative pins; the signal ground pins must be wired to signal ground pins.  
To attach the CCN communication bus wiring, refer to the certified drawings and wiring  
diagrams. The wire is inserted into the CCN communications plug (COMM1) on the PSIO  
module. This plug also is referred to as J5.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Note: Conductors and drain wire must be 20 AWG (American Wire Gage) minimum stranded,  
tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl,  
Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of  
PVC, PVC/nylon, chrome vinyl or Teflon with a minimum operating temperature range of  
–20 C to 60 C is required. See table below for cables that meet the requirements.  
Manufacturer  
Alpha  
Cable No.  
2413 or 5463  
A22503  
American  
Belden  
8772  
02525  
Columbia  
When connecting the CCN communication bus to a system element, a color code system for  
the entire network is recommended to simplify installation and checkout. The following color  
code is recommended:  
SIGNAL TYPE  
CCN BUS CONDUCTOR  
INSULATION COLOR  
PSIO MODULE COMM 1  
PLUG (J5) PIN NO.  
RED  
WHITE  
BLACK  
1
2
3
+
Ground  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Check Starter  
CAUTION  
CAUTION  
!
BE AWARE that certain automatic start arrangements  
Open the disconnect  
or pump.  
.
can engage the starter  
of the starter in addition to shutting off the machine  
ahead  
Use the instruction and service manual supplied by the starter manufacturer to verify that the  
starter has been installed correctly.  
CAUTION  
CAUTION  
!
The main disconnect on the starter front panel may not deenergize all internal  
circuits. Open all internal and remote disconnects before servicing the starter.  
Whenever a starter safety trip device activates, wait at least 30 seconds before resetting the  
safety. The microprocessor maintains its output to the 1CR relay for 10 seconds after starter  
safety shutdown to determine the fault mode of failure.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical-Type Starters  
1.  
Check all field wiring connections for tightness, clearance from moving parts, and correct  
connection.  
2.  
Check the contactor(s) to be sure they move freely. Check the mechanical interlock  
between contactors to ensure that 1S and 2M contactors cannot be closed at the same  
time. Check all other electro-mechanical devices, e.g., relays, timers, for free movement. If  
the devices do not move freely, contact the starter manufacturer for replacement  
components.  
3.  
Some dashpot-type magnetic overload relays must be filled with oil on the job site. If the  
starter is equipped with devices of this type, remove the fluid cups from these magnetic  
overload relays. Add dashpot oil to cups per instructions supplied with the starter. The oil is  
usually shipped in a small container attached to the starter frame near the relays. Use only  
dashpot oil supplied with the starter. Do not substitute.  
Factory-filled dashpot overload relays need no oil at start-up and solid-state overload relays  
do not have oil.  
4.  
Reapply starter control power (not main chiller power) to check electrical functions. When  
using a reduced-voltage starter (such as a wye-delta type) check the transition timer for  
proper setting. The factory setting is 30 seconds (±5 seconds), timed closing. The timer is  
adjustable in a range between 0 and 60 seconds and settings other than the nominal 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
seconds may be chosen as needed (typically 20 to 30 seconds are used).  
When the timer has been set, check that the starter (with relay 1CR closed) goes through a  
complete and proper start cycle.  
Solid-State Starters  
WARNING  
WARNING  
!
This equipment is at line voltage when AC power is connected. Pressing the Stop  
button does not remove voltage. Use caution when adjusting the potentiometers  
on the equipment.  
1.  
2.  
3.  
4.  
5.  
6.  
Check that all wiring connections are properly terminated to the starter.  
Verify that the ground wire to the starter is installed properly and is of sufficient size.  
Verify that the motors are properly grounded to the starter.  
Check that all of the relays are properly seated in their sockets.  
Verify that the proper ac input voltage is brought into the starter per the certified drawings.  
Verify the initial factory settings (i.e., starting torque, ramp potentiometers, etc. are set per  
the manufacturer’s instructions.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Oil Charge  
If oil is added, it must meet Carrier’s specification for centrifugal compressor usage as  
described in the Scheduled Maintenance, Oil Specification section.  
On hermetic machines, add oil through the oil drain charging valve (Figure 3, Item 26). A  
pump is required for adding oil against refrigerant pressure. The pumping device must be able  
to lift from 0 to 150 psig (0 to 1034 kPa) or above unit pressure. On open-drive machines, oil  
may be added through the oil drain and charging valve (Figure 2, Item 18) using a pump.  
However, an oil charging elbow on the seal-oil return chamber (Figure 6) allows oil to be added  
without pumping. The seal oil return pump automatically transfers the oil to the main oil  
reservoir.  
Oil should only be charged or removed when the machine is shut down. Maximum oil level is  
the middle of the upper sight glass.  
Power Up the Controls and Check the Oil Heater  
Ensure that an oil level is visible in the compressor before energizing controls. A separate  
disconnect energizes the oil heater and the control circuit. When first powered, the LID should  
display the default screen within a short period of time.  
The oil heater is energized by powering the control circuit. This should be done several hours  
before start-up to minimize oil-refrigerant migration. The oil heater is controlled by the PIC and  
is powered through a contactor in the power panel. Starters contain a separate circuit breaker to  
Download from Www.Somanuals.com. All Manuals Search And Download.  
power the heater and the control circuit. This set up allows the heater to energize when the  
main motor circuit breaker is off for service work or extended shutdowns. The oil heater relay  
status can be viewed on the Status02 screen on the LID. Oil sump temperature can be viewed  
on the LID default screen.  
Software Version  
The software version will always be labeled on the PSIO module, and on the back side of the  
LID module. On both the Controller ID and LID ID display screens, the software version number  
will also appear.  
Set Up Machine Control Configuration  
WARNING  
WARNING  
!
Do not operate the machine before the control configurations have been checked  
and a Control Test has been satisfactorily completed. Protection by safety con-  
trols cannot be assumed until all control configurations have been confirmed.  
As configuration of the 17/19EX unit is performed, write down all configuration settings. A  
log, such as the one shown in Initial Start-Up Checklist, provides a convenient list for con-  
figuration values.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Input the Design Set Points  
Access the LID set point screen and view/modify the base demand limit set point, and either  
the LCW set point or the ECW set point. The PIC can control a set point to either the leaving or  
entering chilled water. This control method is set in the Equipment Configuration table, Config  
table.  
Input the Local Occupied Schedule (OCCPC01S)  
Access the schedule OCCPC01S screen on the LID and set up the occupied time schedule  
per the customer’s requirements. If no schedule is available, the default is factory set for 24  
hours occupied 7 days per week including holidays.  
For more information about how to set up a time schedule, see the Controls section.  
The CCN Occupied Schedule (OCCPC03S) should be configured if a CCN system is being  
installed or if a secondary time schedule is needed.  
The Ice Build Occupied Schedule (OCCPC02S) should be configured for Ice Build  
applications.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Input Service Configurations  
The following configurations require the LID screen to be in the Service portion of the menu.  
• password  
• input time and date  
• LID configuration  
• controller identification  
• service parameters  
• equipment configuration  
• automated control test  
Password  
When accessing the Service tables, a password must be entered. All LIDs are initially set for  
a password of 1-1-1-1. This password may be changed in the LID configuration screen, if  
desired.  
Input Time and Date  
Access the Time and Date table on the Service menu. Input the present time of day, date,  
and day of the week. ‘‘Holiday Today’’ should only be configured to ‘‘Yes’’ if the present day is a  
holiday.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Change LID Configuration If Necessary  
The LID Configuration screen is used to view or modify the LID CCN address, change to  
English or SI units, and to change the password. If there is more than one machine at the job-  
site, change the LID address on each machine so that each machine has its own address. Note  
and record the new address. Change the screen to SI units as required, and change the  
password if desired. A copy of the password should be retained for future reference.  
Modify Controller Identification If Necessary  
The controller identification screen is used to change the PSIO module address. Change this  
address for each machine if there is more than one machine at the job-site. Write the new  
address on the PSIO module for future reference.  
Input Equipment Service Parameters If Necessary  
The Equipment Service table has 3 service tables: Service1, Service2, and Service3.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configure SERVICE1 Table  
Access Service1 table to modify/view the following to jobsite parameters:  
Water or Brine?  
Usually 3 F (1.7 C below design refrigerant temperature  
Is HGBP installed?  
Chilled Medium  
Brine Refrigerant Trippoint  
Surge Limiting or Hot Gas  
Bypass Option  
°
° )  
Minimum Load Points (T1/P1)  
Maximum Load Points (T2/P2)  
Motor Rated Load Amps  
Motor Rated Line Voltage  
Motor Rated Line kW  
Line Frequency  
Per job data — See Modify Load Points section (below)  
Per job data — See Modify Load Points section (below)  
Per job data  
Per job data  
Per job data (if kW meter installed)  
50 or 60 Hz  
Compressor Starter Type  
Stop-to-Start Time*  
Reduced voltage or full?  
Follow motor vendor recommendation for time between starts.  
See certified prints for correct value.  
*Open-drive machines only.  
Note: Other values are left at the default values. These may be changed by the operator as  
required. Service2 and Service3 tables can be modified by the owner/operator as  
required.  
Modify Minimum and Maximum Load Points (T1/P1; T2/P2) If Necessary  
These pairs of machine load points, located on the Service1 table, determine when to limit  
guide vane travel or to open the hot gas bypass valve when surge prevention is needed. These  
points should be set based on individual machine operating conditions.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If, after configuring a value for these points, surge prevention is operating too soon or too late  
for conditions, these parameters should be changed by the operator.  
Example of configuration: Machine operating parameters  
Refrigerant used: HFC-134a  
Estimated Minimum Load Conditions:  
44 F (6.7 C) LCW  
45.5 F (7.5 C) EWC  
43 F (6.1 C) Suction Temperature  
70 F (21.1 C) Condensing Temperature  
Estimated Maximum Load Conditions:  
44 F (6.7 C) LCW  
54 F (12.2 C) ECW  
42 F (5.6 C) Suction Temperature  
98 F (36.7 C) Condensing Temperature  
Calculate Maximum Load  
To calculate maximum load points, use design load condition data. If the machine full load  
cooler temperature difference is more than 15° F (8.3° C), estimate the refrigerant suction and  
condensing temperatures at this difference. Use the proper saturated pressure and temperature  
for the particular refrigerant used.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Suction Temperature:  
42 F (5.6 C) = 37 psig (255 kPa) saturated refrigerant pressure (HFC-134a)  
Condensing Temperature:  
98 F (36.7 C) = 120 psig (1827 kPa) saturated refrigerant pressure (HFC-134a)  
Maximum Load T2:  
54 – 44 = 10° F (12.2 – 6.7 = 5.5° C)  
Maximum Load P2:  
120 – 37 = 83 psid (827 – 255 = 572 kPad)  
To avoid unnecessary surge prevention, add about 10 psid (70 kPad) to P2 from these  
conditions:  
T2 = 10° F (5.5° C)  
P2 = 93 psid (642 kPad)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Calculate Minimum Load  
To calculate minimum load conditions, estimate the temperature difference that the cooler  
will have at 20% load, then estimate what the suction and condensing temperatures will be at  
this point. Use the proper saturated pressure and temperature for the particular refrigerant  
used.  
Suction Temperature:  
43 F (6.1 C) = 38 psig (262 kPa) saturated refrigerant pressure (HFC-134a)  
Condensing Temperature:  
70 F (21.1 C) = 71 psig (490 kPa) saturated refrigerant pressure (HFC-134a)  
Minimum Load T1 (at 20% Load):  
2° F (1.1° C)  
Minimum Load P1:  
71 – 38 = 33 psid (490 – 262 = 228 kPad)  
Again, to avoid unnecessary surge prevention, add 20 psid (140 kPad) at P1 from these  
conditions:  
T1 = 2° F (1.1° C)  
P1 = 53 psid (368 kPad)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If surge prevention occurs too soon or too late:  
Load  
Surge Prevention Occurs Too Soon  
Increase P1 by 10 psid (70 kPad)  
Increase P2 by 10 psid (70 kPad)  
Surge Prevention Occurs Too Late  
Decrease P1 by 10 psid (70 kPad)  
Decrease P2 by 10 psid (70 kPad)  
At low loads (<50%)  
At high loads (>50%)  
Modify Equipment Configuration If Necessary  
The Equipment Configuration table has tables to select and view or modify. Carrier’s certified  
drawings will have the configuration values required for the jobsite. Modify these tables only if  
requested.  
Config Table Modifications  
Change the values in this table per job data. See certified drawings for values. Modifications  
include:  
• chilled water reset  
• entering chilled water control (Enable/Disable)  
• 4-20 mA demand limit  
• auto restart option (Enable/Disable)  
• remote contact option (Enable/Disable)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Owner-Modified CCN Tables  
The following tables are described for reference only.  
Occdef Table Modifications — The Occdef tables contain the Local and CCN time  
schedules, which can be modified here, or in the Schedule screen as described previously.  
Holidef Table Modifications — The Holidef tables configure the days of the year that holidays  
are in effect. See the holiday paragraphs in the Controls section for more details.  
Brodefs Table Modifications — The Brodefs table defines the outside-air temperature sensor  
and humidity sensor if one is to be installed. It will define the start and end of daylight savings  
time. Enter the dates for the start and end of daylight savings if required for the location.  
Brodefs also will activate the Broadcast function which enables the holiday periods that are  
defined on the LID.  
Other Tables —The Alarmdef, Cons-def, and Runt-def contain tables for use with a CCN  
system. See the applicable CCN manual for more information on these tables. These tables can  
only be defined through a CCN Building Supervisor.  
Check Voltage Supply  
Access the Status 01 screen and read the LINE VOLTAGE: ACTUAL value. This reading  
should be equal to the incoming power to the starter. Use a voltmeter to check incoming power  
at the starter power leads. If the readings are not equal, an adjustment can be made by  
selecting the LINE VOLTAGE: ACTUAL point and then increasing or decreasing the value so  
Download from Www.Somanuals.com. All Manuals Search And Download.  
that the value appearing on the LID is calibrated to the incoming power voltage reading. Voltage  
can be calibrated only to between 90 and 100 percent of rated line voltage.  
Perform an Automated Control Test  
Check the safety controls status by performing an automated controls test. Access the  
Control Test table and select the Automated Tests function (Table 7).  
The Automated Control Test will check all outputs and inputs for function. It will also set the  
refrigerant type. The compressor must be in the OFF mode in order to operate the controls test  
and the 24-v input to the SMM must be in range (per line voltage percent on Status01 table).  
The OFF mode is caused by pressing the STOP pushbutton on the LID. Each test will ask the  
operator to confirm that the operation is occurring, and whether or not to continue. If an error  
occurs, the operator has the choice to try to address the problem as the test is being done, or to  
note the problem and proceed to the next test.  
Note:  
If during the Control Test the guide vanes do not open, check to see that the low pres-  
sure alarm is not active. (This will cause the guide vanes to close.)  
Note:  
The oil pump test will not energize the oil pump if cooler pressure is below –5 psig  
(–35 kPa).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
When the test is finished, or the EXIT softkey is pressed, the test will be stopped and the  
Control Test menu will be displayed. If a specific automated test procedure is not completed,  
access the particular control test to test the function when ready. The Control Test menu is  
described as follows.  
As described above, a complete control test.  
Check of all PSIO thermistors only.  
Check of all options boards thermistors.  
Automated Tests  
PSIO Thermistors  
Options Thermistors  
Transducers  
Check of all transducers.  
Check of the guide vane operation.  
Guide Vane Actuator  
Pumps  
Check operation of pump outputs, either all pumps can be activated, or indi-  
vidual pumps. The test will also test the associated input such as flow or  
pressure.  
Activation of all on/off outputs or individually.  
Pumpdown prevents the low refrigerant alarm during evacuation so refriger-  
ant can be removed from the unit; locks the compressor off; and starts the  
water pumps.  
Discrete Outputs  
Pumpdown/Lockout  
To charge refrigerant and enable the chiller to run after pumpdown lockout.  
Terminate Lockout  
Click here for Table 7 — Control Test Menu Functions  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Check Pumpout System Controls and Optional Pumpout Compressor  
Controls include an on/off switch, a 3-amp fuse, the compressor overloads, an internal  
thermostat, a compressor contactor, and a refrigerant high pressure cutout. The high pressure  
cutout is factory set to open at 161 psig (1110 kPa) and reset at 130 psig (896 kPa). Check that  
the water-cooled condenser has been connected. Loosen the compressor holddown bolts to  
allow free spring travel. Open the compressor suction and discharge service valves. Check that  
oil is visible in the compressor sight glass. Add oil if necessary.  
See Pumpout and Refrigerant Transfer Procedures and Pumpout System Maintenance  
sections for details on transfer of refrigerant, oil specifications, etc.  
High Altitude Locations  
Recalibration of the pressure transducers will be necessary as the machine was initially  
calibrated at sea level. Please see the calibration procedure in the Troubleshooting Guide  
section.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Charge Refrigerant into Machine  
CAUTION  
CAUTION  
!
The transfer, addition, or removal of refrigerant in spring isolated machines may  
place severe stress on external piping if springs have not been blocked in both  
up and down directions.  
The 17/19EX machine may have the refrigerant already charged in the utility vessels. If  
machine is not shipped fully charged, refrigerant is shipped separately to conform with  
transportation regulations. The 17/19EX may be ordered with a nitrogen holding charge of  
15 psig (103 kPa). Evacuate the entire machine, and charge machine from refrigerant cylinders.  
The full refrigerant charge on the 17/19EX will vary with machine components and design  
conditions, indicated on the job data specifications. An approximate charge may be found in  
17/19EX Physical Data section. The full machine charge is printed on the machine identification  
label.  
Always operate the condenser and chilled water pumps during charging operations to  
prevent freeze-ups. Use the Controls Test Terminate Lockout to monitor conditions and start  
the pumps.  
If the machine has been shipped with a holding charge, the refrigerant will be added through  
Download from Www.Somanuals.com. All Manuals Search And Download.  
the refrigerant charging valve, (Figure 7 and Figure 8) or to the pumpout charging connection.  
First evacuate the nitrogen holding charge from the vessels. Charge the refrigerant as a gas  
until the system pressure exceeds 35 psig (141 kPa). After the machine is beyond this pressure  
the refrigerant should be charged as a liquid until all of the recommended refrigerant charge has  
been added.  
Trimming Refrigerant Charge  
The 17/19EX is shipped with the correct charge for the design duty of the machine. Trimming  
the charge can be best accomplished when design load is available. To trim, check the  
temperature difference between leaving chilled water temperature and cooler refrigerant  
temperature at full load design conditions. If necessary, add or remove refrigerant to bring the  
temperature difference to design conditions or a minimum differential.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Initial Start-Up  
Preparation  
Before starting the machine, check that the:  
1.  
Power is on to the main starter, oil pump relay, tower fan starter, oil heater relay, and the  
machine control center.  
2.  
3.  
Cooling tower water is at proper level, and at or below design entering temperature.  
Machine is charged with refrigerant and all refrigerant and oil valves are in their proper  
operating position.  
4.  
5.  
Oil is at the proper level in the reservoir sight glasses.  
Oil reservoir temperature is above 140 F (60 C) or refrigerant temperature plus 50° F  
(28° C).  
6.  
Valves in the evaporator and condenser water circuits are open.  
Note:  
If pumps are not automatic, make sure water is circulating properly.  
7.  
Check the starter to ensure it is ready to start and that all safety circuits have been reset. Be  
sure to keep the starter door closed.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING  
WARNING  
!
Do not permit water or brine that is warmer than 110 F (43 C) to flow through the  
cooler or condenser. Refrigerant overpressure may discharge through the relief  
devices and result in the loss of refrigerant charge.  
8. Press RELEASE to automate the chiller start/stop value on the Status01 screen to enable  
the chiller to start. The initial factory setting of this value is overridden to stop in order to  
prevent accidental start-up.  
Manual Operation of the Guide Vanes  
Manual operation of the guide vanes is helpful to establish a steady motor current for  
calibration of the motor amps value.  
In order to manually operate the guide vanes, it is necessary to override the TARGET GUIDE  
VANE POSITION value which is accessed on the Status01 screen. Manual control is indicated  
by the word ‘‘SUPVSR!’’ flashing after the target value position. Manual control is also indicated  
on the default screen on the run status line.  
1. Access the Status01 screen and look at the target guide vane position (Figure 18). If the  
compressor is off, the value will read zero.  
2. Move the highlight bar to the TARGET GUIDE VANE POSITION line and press the  
SELECT softkey.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Press ENTER to override the automatic target. The screen will now read a value of zero,  
and the word ‘‘SUPVSR!’’ will flash.  
4. Press the SELECT softkey, and then press RELEASE softkey to release the vanes to  
AUTOMATIC mode. After a few seconds the ‘‘SUPVSR!’’ will disappear.  
Dry Run to Test Start-Up Sequence  
1. Disengage the main motor disconnect on the starter front panel. This should only  
disconnect the motor power. Power to the controls, oil pump, and starter control circuit  
should still be energized.  
2. Look at the default screen on the LID: the Status message in the upper left-hand corner will  
show a ‘‘Manually Stopped’’ message. Press CCN or Local to start. If not, go to the  
Schedule screen and override the schedule or change the occupied time. Press the LOCAL  
softkey to begin the start-up sequences.  
3. Check that chilled water and condenser water pumps energize.  
4. Check that the oil pump starts and pressurizes the lubrication system. After the oil pump  
has run about 15 seconds, the starter will be energized and go through its start-up  
sequence.  
5. Check the main contactor for proper operation.  
6. The PIC will eventually show an alarm for motor amps not sensed. Reset this alarm and  
continue with the initial start-up.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Check Rotation (Open-Drive Motor)  
Open Drive Motor Initial Start-Up  
Initial Uncoupled Start-Up  
The initial start-up of the motor should be made with the motor uncoupled. Verify that oil has  
been added to each bearing housing to the correct level.  
1.  
If the motor is equipped with unidirectional fans (refer to the certified drawing) and  
verification of rotation direction is required, the following procedure should be followed:  
a.  
Start the motor and observe the rotation direction.  
b.  
c.  
Allow the motor to achieve full speed before disconnecting it from the power source.  
If the rotation direction must be changed, refer to the Before Initial Start-Up, Open Drive  
Motor Electrical Connection section. Otherwise, the motor can be restarted immediately  
after it has coasted to a stop.  
2.  
Following the initial start-up, the bearing temperatures should be closely monitored. On  
sleeve bearings, the free rotation of the oil rings should be verified by observing them  
through the viewing port in the top of the housing. The rate of rise in bearing temperature is  
more indicative of impending trouble than the actual temperature. If the rate of rise in  
temperature is excessive or if the motor exhibits excessive vibration or noise, it should be  
shut down immediately and a thorough investigation made as to the cause before it is  
operated again.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the bearing temperature rises and motor operation appears to be normal, operation  
should continue until the bearing temperatures stabilize. Recommended limits on bearing  
temperature rises over ambient temperature are as follows:  
Sleeve Bearings  
Temperature Rise Over Ambient Temperature  
72° F (40° C)  
By permanently installed detector  
By temporary detector on top of the  
bearing sleeve near the oil ring  
63° F (35° C)  
Note: When operating flood-lubricated sleeve bearings, the bearing temperature must not be  
allowed to exceed 185 F (85 C) total temperature.  
CAUTION  
CAUTION  
!
Under normal conditions, for the self-lube bearing, the rate of temperature rise  
should be from 20° to 25° F (11° to 14° C) for the first 10 minutes after starting up  
and approximately 40° F (22° C) at 30 minutes. The rate of bearing temperature  
rise is a function of the natural ventilation and operating conditions.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION  
CAUTION  
!
When the rate of bearing temperature rise is less than 2° F (1.1° C) per half-hour,  
the bearing temperature is considered to be stabilized.  
CAUTION  
CAUTION  
!
If the total bearing temperature exceeds 195 F (91 C), the motor should be shut  
down immediately.  
3. Any abnormal noise or vibration should be immediately investigated and corrected.  
Increased vibration (with the motor uncoupled from its load) can be indicative of a change in  
balance due to a mechanical failure or the loosening of a rotor part, a stator winding  
problem, foundation problem, or a change in motor alignment.  
4. Verify that the magnetic center indicator aligns with the shaft.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Initial Coupled Start-Up  
After initial uncoupled start-up, the following steps should be taken to ensure safe coupled  
operation:  
1. Follow the procedure stated in General Maintenance, Machine Alignment section to align  
the motor to the driven machine.  
2. Prepare the coupling for operation in accordance with the coupling manufacturer’s  
instructions. Note any match marks on the couplings and assemble accordingly. For sleeve  
bearing motors, verify that the correct limited endfloat coupling has been installed. The  
endfloat limits can be found on the certified drawing.  
3. Ensure that all personnel are at a safe distance from rotating parts. Start the motor in  
accordance with instructions supplied with the motor control.  
4. If the motor rotor fails to start turning in a second or two, shut off the power supply  
immediately. This can result from:  
a. Too low a voltage at the motor terminals.  
b. The load is too much for the rotor to accelerate.  
c. The load is frozen up mechanically.  
d. All electrical connections are not made.  
e. Single phase power has been applied.  
f. Any combination of the above.  
Investigate thoroughly and take corrective action before attempting a restart.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Carefully observe the vibration of the bearing housing and any abnormal noise generator.  
Note that motor vibration may not be identical to the uncoupled values. If coupled vibration  
is excessive, recheck the mounting and alignment.  
6. Carefully observe the bearing temperature rise and the movement of the oil ring.  
If the bearing temperature rise and motor operation appear normal, operation should con-  
tinue until the bearing temperatures stabilize.  
7. If possible, check the motor line currents for balance.  
It should be recognized that each start of an induction motor subjects the motor to full inrush  
current with resulting heating of the stator and rotor windings. Each acceleration and repeated  
starts can produce more heat than is produced and dissipated by the motor under full load. The  
starting duty for which the motor is designed is shown by a nameplate mounted on the motor  
and must not be exceeded, if long motor life is expected. Abnormally low terminal voltage,  
excessive load torque and/or excessive load inertia during motor start-up can cause lengthened  
acceleration times during which rotor ventilation is reduced. This can cause rotor damage or  
can lead to shortened rotor life.  
The temperature rating of the motor is shown on the main nameplate as a temperature rise  
above an ambient temperature. If there is a service factor, it is also shown. If the motor  
temperature switch opens, an investigation should be made before further operation is  
attempted.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the motor is of TEWAC (Totally Enclosed Water-to-Air Cooled) design, the maximum inlet  
water temperature and the water flow rate (GPM) at the air cooler must be as shown by the  
certified drawing. Otherwise, the discharge air temperature from the cooler (actually the  
ambient air for the motor as shown by the main nameplate) could be too high for the motor to  
properly cool.  
Check Rotation (Hermetic Motor)  
1.  
2.  
3.  
Engage the main motor disconnect on the front of the starter panel. The motor is now ready  
for rotation check.  
After the default screen Status message states ‘‘Ready for Start’’ press the LOCAL softkey;  
start-up checks will be made by the control.  
When the starter is energized and the motor begins to turn over, check for clockwise  
rotation (Figure 30).  
If Rotation Is Proper, allow the compressor to come up to speed.  
If the Motor Rotation Is Not Clockwise (as viewed through the sight glass), reverse any  
2 of the 3 incoming power leads to the starter and recheck rotation.  
Note:  
Starters may also have phase protection and will not allow a start if the phase is not cor-  
rect. Instead, a Starter Fault message will occur if this happens.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION  
CAUTION  
!
Do not check motor rotation during coastdown. Rotation may have reversed dur-  
ing equalization of vessel pressures.  
Check Oil Pressure and Compressor Stop  
1.  
When the motor is up to full speed, note the differential oil pressure reading on the LID  
default screen. It should be between 18 and 30 psid (124 to 206 kPad).  
2.  
Press the Stop button and listen for any unusual sounds from the compressor as it coasts to  
a stop.  
Click here for Figure 30 — Correct Motor Rotation  
Calibrate Motor Current Demand Setting  
1.  
Make sure that the compressor motor rated load amps in the Service1 screen has been  
configured. Place an ammeter on the line that passes through the motor load current  
transfer on the motor side of the power factor correction capacitors (if provided).  
2.  
Start the compressor and establish a steady motor current value between 70% and 100%  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RLA by manually overriding the guide vane target value on the LID and setting the chilled  
water set point to a low value. Do not exceed 105% of the nameplate RLA.  
3. When a steady motor current value in the desired range is met, compare the compressor  
motor amps value on the Status01 screen to the actual amps shown on the ammeter on the  
starter. Adjust the amps value on the LID to the actual value seen at the starter if there is a  
difference. Highlight the amps value then press SELECT. Press INCREASE or DECREASE  
to bring the value to that indicated on the ammeter. Press ENTER when equal.  
4. Make sure that the target guide vane position is released into AUTOMATIC mode.  
To Prevent Accidental Start-Up  
The PIC can be set up so that start-up of the unit is more difficult than just pressing the  
LOCAL or CCN softkeys during machine service or when necessary. By accessing the  
Status01 screen, and highlighting the chiller Start/Stop line, the value can be overridden to stop  
by pressing SELECT and then the STOP and ENTER softkeys. ‘‘SUPVSR’’ will appear after the  
value. When attempting to restart, remember to release the override. The default machine  
message line will also state that the Start/Stop has been set to ‘‘Start’’ or ‘‘Stop’’ when the value  
is overridden.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hot Alignment Check for Open-Drive Machines  
Alignment of compressor with heat exchangers, gear, and driver may be affected by the  
operating temperatures of the various components. When all machine components have  
reached operating temperature (after running near full load for 4 to 8 hours), make a hot  
alignment check.  
With the proper equipment and procedure, hot check can be made with either assembled or  
disassembled couplings. The procedures are detailed in the Maintenance section.  
A clamping tool, Part No. TS-170, is available for checking alignment without disassembling  
the couplings. Check with your local Carrier representative.  
WARNING  
WARNING  
!
Never operate compressor or drive with coupling guards removed. Serious injury  
can result from contact with rotating equipment.  
Doweling for Open-Drive Machines  
The size, quantity, and location of dowels vary considerably with type and arrangement of  
gear and drive. Check your job data for specific doweling instructions. Typical doweling  
practices are described in the Maintenance section.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Check Machine Operating Condition  
Check to be sure that machine temperatures, pressures, water flows, and oil and refrigerant  
levels indicate that the system is functioning properly.  
Instruct the Customer Operator  
Check to be sure that the operator(s) understands all operating and maintenance  
procedures. Point out the various machine parts and explain their function as part of the  
complete system.  
Cooler-Condenser  
Relief devices, temperature sensor locations, pressure transducer locations, Schrader  
fittings, waterboxes and tubes, and vents and drains.  
Utility Vessel  
Float chambers, relief valves, charging valve.  
Pumpout System  
Transfer valves and pumpout system, refrigerant charging and pumpdown procedure,  
lubrication, and relief devices.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Motor Compressor Assembly  
Guide vane actuator, transmission, motor cooling system, oil cooling system, temperature  
and pressure sensors, oil sight glasses, integral oil pump, isolatable oil filter, extra oil and motor  
temperature sensors, synthetic oil, and compressor serviceability.  
Motor Compressor Lubrication System  
Oil pump, cooler filter, oil heater, oil charge and specification, operating and shutdown oil  
level, temperature and pressure, oil charging connections, and seal oil chambers.  
Control System  
CCN and Local start, reset, menu, softkey functions, LID operation, occupancy schedule, set  
points, safety controls, and auxiliary and optional controls.  
Auxiliary Equipment  
Starters and disconnects, separate electrical sources, pumps, and cooling tower.  
Describe Machine Cycles  
Refrigerant, motor cooling, lubrication, and oil reclaim.  
Review Maintenance  
Scheduled, routine, and extended shutdowns, importance of a log sheet, importance of water  
treatment and tube cleaning, and importance of maintaining a leak-free machine.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Devices and Procedures  
Electrical disconnects, relief device inspection, and handling refrigerant.  
Check Operator Knowledge  
Start, stop, and shutdown procedures, safety and operating controls, refrigerant and oil  
charging, and job safety.  
Review the Start-Up, Operation, and Maintenance Manual  
Operating Instructions  
Operator Duties  
1.  
Become familiar with refrigeration machine and related equipment before operating the  
machine.  
2.  
Prepare the system for start-up, start and stop the machine, and place the system in a  
shutdown condition.  
3.  
4.  
Maintain a log of operating conditions and document any abnormal readings.  
Inspect the equipment, make routine adjustments, and perform a control test. Maintain the  
proper oil and refrigerant levels.  
5.  
6.  
Protect the system from damage during shutdown periods.  
Maintain the set point, time schedules, and other PIC functions.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Prepare the Machine for Start-Up  
Follow the steps described in the Initial Start-Up section.  
To Start the Machine  
1.  
2.  
Start the water pumps, if they are not automatic.  
On the LID default screen, press the LOCAL or CCN softkey to start the system. If the  
machine is in the OCCUPIED mode, and the 3- and 15-minute start timers have expired,  
the start sequence will start. Follow the procedure described in the Start-Up/Shutdown/  
Recycle section.  
Check the Running System  
After the compressor starts, the operator should monitor the LID display and observe the  
parameters for normal operating conditions:  
1.  
The oil reservoir temperature should be above 150 F (66 C) or refrigerant temperature plus  
70° F (38° C) during shutdown, and above 125 F (52 C) during compressor operation.  
2.  
The bearing oil temperature accessed on the Status01 LID screen should be 150 to 200 F  
(65 to 93 C). If the bearing temperature reads more than 210 F (99 C) with the oil pump  
running, stop the machine and determine the cause of the high temperature. Do not restart  
the machine until corrected.  
3.  
The oil level should be visible in the lower sight glass when the compressor is running.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
At shutdown, oil level should be halfway in the lower sight glass.  
4. The oil pressure should be between 18 and 30 psi (124 to 207 kPa) differential, as seen on  
the LID default screen. Typically the reading will be 18 to 25 psi (124 to 172 kPa) at initial  
start-up.  
5. The moisture indicating sight glass on the refrigerant motor cooling line should indicate  
refrigerant flow and a dry condition.  
6. The condenser pressure and temperature varies with the machine design conditions.  
Typically the pressure will range between 100 and 210 psig (690 to 1450 kPa) with a  
corresponding temperature range of 60 to 105 F (15 to 41 C). The condenser entering  
water temperature should be controlled below the specified design entering water  
temperature to save on compressor kilowatt requirements. The leaving condenser water  
temperature should be at least 20° F (11° C) above leaving chilled water temperature.  
7. Cooler pressure and temperature also will vary with the design conditions. Typical pressure  
range will be between 60 and 80 psig (410 and 550 kPa), with temperature ranging  
between 34 and 45 F (1 and 8 C).  
8. The compressor may operate at full capacity for a short time after the pulldown ramping has  
ended, even though the building load is small. The active electrical demand setting can be  
overridden to limit the compressor IkW, or the pulldown rate can be decreased to avoid a  
high demand charge for the short period of high demand operation. Pulldown rate can be  
Download from Www.Somanuals.com. All Manuals Search And Download.  
based on kW rate or temperature rate. It is accessed on the Equipment Configuration menu  
Config screen (Table 2, Example 5).  
9. On open-drive machines, the oil pump will be energized once every 12 hours during  
shutdown periods to ensure that the shaft seal is filled with oil.  
To Stop the Machine  
1. The occupancy schedule will start and stop the machine automatically once the time  
schedule is set up.  
2. By pressing the Stop button for one second, the alarm light will blink once to confirm that  
the button has been pressed, then the compressor will follow the normal shutdown  
sequence as described in the Controls section. The machine will not restart until the CCN or  
LOCAL softkey is pressed. The machine is now in the OFF mode.  
Note: If the machine fails to stop, in addition to action that the PIC will initiate, the operator  
should close the guide vanes by overriding the guide vane target to zero to reduce  
machine load; then by opening the main disconnect. Do not attempt to stop the machine  
by opening an isolating knife switch. High intensity arcing may occur. Do not restart the  
machine until the problem is diagnosed and corrected.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
After Limited Shutdown  
No special preparations should be necessary. Follow the regular preliminary checks and  
starting procedures. Control Power must be maintained in order to keep oil temperature hot and  
all control safeties operational. The oil pump on open-drive machines will operate occasionally  
to keep the contact seal filled with oil to prevent refrigerant loss.  
Extended Shutdown  
The refrigerant should be transferred into the utility vessel (see Pumpout and Refrigerant  
Transfer Procedures) in order to reduce machine pressure and possibility of leaks. Maintain a  
holding charge of 5 to 10 lbs (2.27 to 4.5 kg) of refrigerant within the cooler/condenser/  
compressor sections, to prevent air from leaking into the machine.  
If freezing temperatures are likely to occur in the machine area, drain the chilled water,  
condenser water, and the pump-out condenser water circuits to avoid freeze-up. Keep the  
waterbox drains open.  
Leave the oil charge in the machine with the oil heater and controls energized to maintain the  
minimum oil reservoir temperature.  
After Extended Shutdown  
Be sure that the water system drains are closed. It may be advisable to flush the water  
circuits to remove any soft rust which may have formed. This is a good time to brush the tubes if  
necessary.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Check the cooler pressure on the LID default screen, and compare to the original holding  
charge that was left in the machine. If (after adjusting for ambient temperature changes) any  
loss in pressure is indicated, check for refrigerant leaks. See Check Machine Tightness section.  
Recharge the machine by transferring refrigerant from the utility vessel. Follow the Pumpout  
and Refrigerant Transfer Procedures section. Observe freeze-up precautions.  
Carefully make all regular preliminary and running system checks. Perform a controls test  
before start-up. If the compressor oil level appears abnormally high, the oil may have absorbed  
refrigerant. Make sure that the oil temperature is above 150 F (66 C) or cooler refrigerant  
temperature plus 70° F (39° C).  
Cold Weather Operation  
When the entering condenser water drops very low, the PIC can automatically cycle the  
cooling tower fans off to keep the temperature up. Piping may also have to be arranged to  
bypass the cooling tower as well as a tower temperature control system.  
Manual Guide Vane Operation  
Manual operation of the guide vanes in order to check control operation or control of the  
guide vanes in an emergency operation is possible by overriding the target guide vane position.  
Access the Status01 screen on the LID and highlight TARGET GUIDE VANE POSITION. To  
control the position, enter a percentage of guide vane opening that is desired. Zero percent is  
Download from Www.Somanuals.com. All Manuals Search And Download.  
fully closed, 100% is fully open. To release the guide vanes to AUTOMATIC mode, press the  
RELEASE softkey.  
Note: Manual control will increase the guide vanes and override the pulldown rate during start-  
up. Motor current above the electrical demand setting, capacity overrides, and chilled  
water below control point will override the manual target and close the guide vanes. For  
descriptions of capacity overrides and set points, see the Controls section.  
Refrigeration Log  
A refrigeration log, such as the one shown in Figure 31, provides a convenient checklist for  
routine inspection and maintenance and provides a continuous record of machine performance.  
It is an aid in scheduling routine maintenance and in diagnosing machine problems.  
Keep a record of the machine pressures, temperatures, and liquid levels on a sheet similar to  
that shown. Automatic recording of PIC data is possible through the use of CCN devices such  
as the Data Collection module and a Building Supervisor. Contact your Carrier representative  
for more information.  
Click here for Figure 31 — Refrigeration Log  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pumpout and Refrigerant Transfer Procedures  
Preparation  
The 17/19EX may come equipped with an optional pumpout compressor. The refrigerant can  
be pumped for service work to either the cooler/condenser/compressor sections or the utility  
vessel by using the pumpout system. The following procedures are used to describe how to  
transfer refrigerant from vessel to vessel and perform machine evacuations.  
Operating the Optional Pumpout Compressor  
1.  
Be sure that the suction and the discharge service valves on the optional pumpout  
compressor are open (backseated) during operation. Figure 32 shows the location of these  
valves. Rotate the valve stem fully counterclockwise to open. Front seating the valve closes  
the refrigerant line and opens the gage port to compressor pressure.  
2.  
Make sure that the compressor holddown bolts have been loosened to allow free spring  
travel.  
3.  
4.  
Open the refrigerant inlet valve on the pumpout compressor.  
Oil should be visible in the compressor sight glass under all operating conditions and during  
shutdown. If oil is low, add oil as described under Optional Pumpout System Maintenance  
section. The pumpout unit control wiring schematic is detailed in Figure 33. The Optional  
Pumpout System is detailed in Figure 34.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To Read Refrigerant Pressures during pumpout or leak testing:  
1.  
The LID display on the machine control center is suitable for determining refrigerant-side  
pressures and low (soft) vacuum. For evacuation or dehydration measurement, use a  
quality vacuum indicator or manometer to ensure the desired range and accuracy. This can  
be placed on the Schrader connections on each vessel (Figure 7 and Figure 8) by removing  
the pressure transducer.  
2.  
3.  
To determine utility vessel pressure, a 30 in.-0-400 psi (-101-0-2760 kPa) gage is attached  
to the vessel.  
Refer to Figure 32 for valve locations and numbers.  
CAUTION  
CAUTION  
!
Transfer, addition, or removal of refrigerant in spring-isolated machines may  
place severe stress on external piping if springs have not been blocked in both  
up and down directions.  
Click here for Figure 32 — Pumpout Arrangement and Valve Number Locations  
(12-ft Vessel Shown)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Click here for Figure 33 — Pumpout Unit Wiring Schematic (19EX Shown)  
Click here for Figure 34 — Optional Pumpout Compressor  
Transferring Refrigerant from Normal Operation into the Utility Vessel  
These steps describe the method of moving refrigerant from the cooler/condenser/  
compressor sections into the utility vessel. This is normally performed for service work on the  
cooler, condenser, or the compressor components or for long-term machine shutdown.  
1.  
Isolate and push refrigerant into the utility vessel with the pumpout compressor.  
a.  
Valve positions: (Blank spaces indicate open valves).  
1
2
3
4
5
6
7
8
9
10  
11  
Valve  
C
C
C
C
C
C
Condition  
b.  
c.  
Turn off the machine water pumps and pumpout condenser water.  
Turn on pumpout compressor to push liquid out of the cooler/condenser/compressor  
section.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
d. When all liquid has been pushed into the utility vessel, close the cooler isolation valve 7.  
e. Access the Control Test, Pumpdown function on the LID display to turn on the machine  
water pumps and view the machine pressures.  
f. Turn off pumpout compressor.  
2. Evacuate refrigerant gas from the cooler/condenser/compressor vessel.  
a. Valve positions: close valves 2 and 5, open valves 3 and 4.  
1
2
3
4
5
6
7
8
9
10  
11  
Valve  
C
C
C
C
C
C
C
Condition  
b. Turn on pumpout condenser water.  
c. Run pumpout compressor until the suction reaches 15 in. Hg (50 kPa abs). Monitor  
pressures on the LID and on the refrigerant gages.  
d. Close valve 1.  
e. Turn off pumpout compressor.  
f. Close valves 3, 4, and 6. (All valves are now closed.)  
g. Turn off pumpout condenser water.  
h. Continue pumpdown function on the LID to turn off the machine water pumps and to lock  
out the machine compressor from operation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Transferring Refrigerant from Normal Operation into the Cooler/Condenser/  
Compressor Section  
These steps describe the method of moving refrigerant from the utility vessel into the cooler/  
condenser/compressor section. This is normally performed for service work on the utility vessel.  
1.  
Isolate and push refrigerant into the cooler/condenser/compressor section:  
a.  
Valve positions:  
1
2
3
4
5
6
7
8
9
10  
11  
Valve  
C
C
C
C
C
C
Condition  
b.  
c.  
d.  
e.  
Turn off machine water pumps and pumpout condenser water.  
Turn on pumpout compressor to push refrigerant out of the utility vessel.  
When all liquid is out of the utility vessel, close cooler isolation valve 7.  
Turn off pumpout compressor.  
2.  
Evacuate refrigerant from the utility vessel.  
a.  
Access the Control Test, pumpout function on the LID display to turn on the machine  
water pumps and monitor vessel pressures.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
b. Valve positions: Close valves 3 and 4, open valves 2 and 5.  
1
2
3
4
5
6
7
8
9
10  
11  
Valve  
C
C
C
C
C
C
C
Condition  
c. Turn on pumpout condenser water.  
d. Run the pumpout compressor until the suction reaches 15 in. Hg (50 kPa abs). Monitor  
pressures on the LID and on refrigerant gages.  
e. Close valve 6.  
f. Turn off pumpout compressor.  
g. Close valves 1, 2, and 5 (all valves are now closed).  
h. Turn off pumpout condenser water.  
i. Continue pumpdown function on the LID to turn off machine water pumps and lock out  
the machine compressor from operation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Return Refrigerant to Normal Operating Conditions  
1.  
2.  
Be sure that the vessel that was opened has been evacuated and dehydrated.  
Access the Control Test, terminate lockout function to view vessel pressures and to turn on  
machine water pumps.  
3.  
Open valves 1, 3, and 6.  
1
2
3
4
5
6
7
8
9
10  
11  
Valve  
C
C
C
C
C
C
C
C
Condition  
4.  
Slowly open valve 5, gradually increasing pressure in the evacuated vessel to 35 psig  
(141 kPa) for HFC-134a. Feed refrigerant slowly to prevent freezeup.  
5.  
6.  
Perform leak test at 35 psig (141 kPa).  
Open valve 5 fully. Let vessel pressures equalize.  
1
2
3
4
5
6
7
8
9
10  
11  
Valve  
C
C
C
C
C
C
C
Condition  
7.  
8.  
Open valves 9 and 10.  
Open valve 7 to equalize liquid refrigerant levels.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9. Close valves 1, 3, 5, and 6.  
1
2
3
4
5
6
7
8
9
10  
11  
Valve  
C
C
C
C
C
C
C
C
Condition  
10. Continue on with the terminate lockout function on the LID to turn off water pumps and  
enable the compressor for operation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Maintenance  
Refrigerant Properties  
HFC-134a is the standard refrigerant in the 17/19EX. At normal atmospheric pressure,  
HFC-134a will boil at -14 F (-25 C) and must, therefore, be kept in pressurized containers or  
storage tanks. The refrigerant is practically odorless when mixed with air. This refrigerant is  
non-combustible at atmospheric pressure. Read the Material Safety Data Sheet and the latest  
ASHRAE Safety Guide for Mechanical Refrigeration to learn more about safe handling of this  
refrigerant.  
DANGER  
DANGER  
!
HFC-134a will dissolve oil and some non-metallic materials, dry the skin, and, in  
heavy concentrations, may displace enough oxygen to cause asphyxiation. In  
handling this refrigerant, protect the hands and eyes and avoid breathing fumes.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Adding Refrigerant  
Follow the procedures described in Charge Refrigerant into Machine section.  
WARNING  
WARNING  
!
Always use the compressor pumpdown function in the Control Test mode to turn  
on the evaporator pump and lock out the compressor when transferring refriger-  
ant. Liquid refrigerant may flash into a gas and cause possible freeze-up when the  
machine pressure is below 30 psig (207 kPa) for HFC-134a.  
Removing Refrigerant  
When the optional pumpout system is used, the 17/19EX refrigerant charge may be  
transferred to a storage vessel, or within the utility vessel. Follow procedures in the Pumpout  
and Refrigerant Transfer Procedures section when removing refrigerant.  
Adjusting the Refrigerant Charge  
If the addition or removal of refrigerant is required for improved machine performance, follow  
the procedures given under the Trim Refrigerant Charge section.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Refrigerant Leak Testing  
Because HFC-134a is above atmospheric pressure at room temperature, leak testing can be  
performed with refrigerant in the machine. Use an electronic detector, soap bubble solution, or  
ultra-sonic leak detector. Be sure that the room is well ventilated and free from concentration of  
refrigerant to keep false readings to a minimum. Before making any necessary repairs to a leak,  
transfer all refrigerant from the leaking vessel.  
Leak Rate  
ASHRAE recommends that machines should be immediately taken off line and repaired if  
the refrigerant leakage rate for the entire machine is more than 10% of the operating refrigerant  
charge per year.  
Additionally, Carrier recommends that leaks totalling less than the above rate but more than  
a rate of 1 lb (0.5 kg) per year should be repaired during annual maintenance or whenever the  
refrigerant is pumped over for other service work.  
Test After Service, Repair, or Major Leak  
If all refrigerant has been lost or if the machine has been opened for service, the machine or  
the affected vessels must be pressured and leak tested. Refer to the Leak Test Machine section  
to perform a leak test.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING  
WARNING  
!
HFC-134a MUST NOT be mixed with air or oxygen and pressurized for leak test-  
ing. In general, this refrigerant should not be allowed to be present with high con-  
centrations of air or oxygen above atmospheric pressures, as the mixture can  
undergo combustion.  
Refrigerant Tracer  
Use an environmentally acceptable refrigerant as a tracer for leak test procedures.  
To Pressurize with Dry Nitrogen  
Another method of leak testing is to pressurize with nitrogen only and use a soap bubble  
solution or an ultrasonic leak detector to determine if leaks are present. This should only be  
done if all refrigerant has been evacuated from the vessel.  
1.  
Connect a copper tube from the pressure regulator on the cylinder to the refrigerant  
charging valve. Never apply full cylinder pressure to the pressurizing line. Follow the listed  
sequence.  
2.  
3.  
4.  
Open the charging valve fully.  
Slowly open the cylinder regulating valve.  
Observe the pressure gage on the machine and close the regulating valve when the  
Download from Www.Somanuals.com. All Manuals Search And Download.  
pressure reaches test level. Do not exceed 140 psig (965 kPa).  
5. Close the charging valve on the machine. Remove the copper tube if no longer required.  
Repair the Leak, Retest, and Apply Standing Vacuum Test  
After pressurizing the machine, test for leaks with an electronic leak detector, soap bubble  
solution, or an ultrasonic leak detector. Bring the machine back to atmospheric pressure, repair  
any leaks found, and retest.  
After retesting and finding no leaks, apply a standing vacuum test, and then dehydrate the  
machine. Refer to the Standing Vacuum Test and Machine Dehydration in the Before Initial  
Start-Up section.  
Figure 35  
Checking Guide Vane Linkage (Refer to  
)
If slack develops in the drive chain, backlash can be eliminated as follows:  
1. With machine shut down (guide vanes closed), remove chain guard, loosen actuator  
holddown bolts and remove chain.  
2. Loosen vane sprocket set screw and rotate sprocket wheel until set screw clears existing  
spotting hole.  
3. With set screw still loose, replace chain and move vane actuator to the left until all chain  
slack is taken up.  
4. Tighten actuator holddown bolts and retighten set screw in new position.  
5. Realign chain guard as required to clear chain.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Click here for Figure 35 — Electronic Vane Actuator Linkage  
Contact Seal Maintenance (Open-Drive Machines) (Refer to Figure 36)  
During machine operation, a few drops of oil per minute normally seeps through the space  
between the contact sleeve (Item 16) and the shaft locknut (Item 8). This oil slowly accumulates  
in an atmospheric oil chamber and is automatically returned to the system by a seal oil return  
pump.  
Oil should never leak between the contact sleeve and the packing gland (Item 14). If oil is  
found in this area, the O-ring (Item 12) should be checked and replaced.  
The oil passing through the shaft seal carries with it some absorbed refrigerant. As the oil  
reaches the atmosphere, the absorbed refrigerant flashes to gas because of the reduction in  
pressure. For this reason, a detector will indicate the presence of a slight amount of refrigerant  
around the compressor shaft whenever the machine is running.  
During machine shutdown, however, no refrigerant should be detected nor should there be  
any oil seepage. If oil flow or the presence of refrigerant is noted while the machine is shut  
down, a seal defect is indicated. Arrange for a seal-assembly inspection by a qualified  
serviceman to determine the cause of the leakage and make the necessary repairs.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Seal Disassembly (Figure 36)  
Contact seal disassembly and repair should be performed only by well qualified compressor  
maintenance personnel. These disassembly instructions are included only as a convenient  
reference for the authorized serviceman.  
For ease of disassembly, refer to Figure 36 while following these instructions.  
1.  
2.  
3.  
4.  
5.  
Remove refrigerant.  
Remove shaft coupling and spacer (if any).  
Remove screws holding windage baffle (Item 4) and remove baffle.  
Remove shaft-end labyrinth (Item 7), gasket (Item 5) and necessary piping.  
Remove snap ring (Item 11) from shaft-end baffle and assemble to contact sleeve (Item  
16).  
6.  
7.  
Remove seal housing cover (Item 2). The contact sleeve, spring (Item 15) and packing  
gland (Item 14) will come out with the cover.  
Place assembly on bench with contact sleeve assembly face down on a soft cloth or clean  
Protect seal faces at all times  
cardboard.  
.
8.  
9.  
Press down on seal housing cover to compress the contact sleeve spring.  
Maintain pressure and remove snap ring.  
10.  
Slowly release pressure on cover. Spring tension will force contact sleeve out of housing.  
For further inspection, remove packing gland and O-ring (Item 12).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11. Place contact sleeve in a protected area to avoid damage to lapped face.  
12. Remove outer carbon ring (Item 17). Handle carefully.  
13. Remove spray header (Item 3).  
14. Use a spanner wrench to remove shaft nut (Item 8).  
15. Remove shaft sleeve (Item 9) and contact ring key (Item 18).  
16. Carefully remove contact ring (Item 19), avoiding a jammed or cocked position. If binding  
occurs, reinstall shaft sleeve and nut to free the ring.  
17. Replace O-ring (Item 10) if damaged or deformed.  
18. Remove inner carbon ring key (Item 27) and retaining ring (Item 21). Screws must be  
loosened evenly against guide-ring spring pressure.  
19. Remove guide ring assembly consisting of inner carbon ring (Item 20), diaphragm (Item 24)  
and guide ring (Item 25). Protect seal faces of ring.  
20. Remove guide-ring spring (Item 26).  
Clean all parts to be reused with solvent, coat with oil and place in a protected area until  
needed.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Seal Reassembly (Figure 36)  
Be sure that all gasket surfaces are clean and that all holes, including oil holes, are properly  
aligned between gasket and mating flange. Coat gasket with oil-graphite mixture to prevent  
sticking.  
1.  
Assembly guide-ring spring (Item 26) and guide-ring assembly (Items 20, 24 and 25).  
Check that travel of inner carbon seal ring (Item 20) is .06 in. minimum in each direction.  
2.  
Tighten screws evenly  
Install retaining ring (Item 21) and inner carbon ring key (Item 27).  
against spring pressure  
.
3.  
4.  
5.  
Replace O-ring (Item 10) in shaft shoulder groove.  
Install spray header gasket (Item 29) and spray header (Item 3).  
Install contact ring (Item 19), contact ring key (Item 18), shaft sleeve (Item 9) and shaft nut  
(Item 8).  
6.  
Carefully install outer carbon ring (Item 17).  
Click here for Figure 36 — Compressor Contact Seal (Open-Drive Machines)  
7.  
Insert O-ring (Item 12) into packing gland (Item 14).  
8.  
Place contact sleeve (Item 16) face down on clean cloth or cardboard.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9. Place outer spring (Item 15) over sleeve.  
10. Separately assemble seal housing cover (Item 2), packing gland gasket (Item 13), packing  
gland (Item 14), and O-ring (Item 12).  
11. Oil the contact sleeve and the O-ring and place the housing and gland assembly over the  
sleeve.  
12. Carefully depress the spring until snap ring (Item 11) can be attached to the sleeve.  
13. Position key (Item 6) to complete the bench assembly.  
14. Install seal housing cover gasket (Item 1) and cover assembly on the compressor.  
15. Remove the snap ring.  
16. Install shaft-end labyrinth gasket (Item 5) and labyrinth (Item 7).  
17. Install windage baffle (Item 4). Attach snap ring to baffle for safekeeping.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Machine Alignment (Open-Drive Machines)  
Alignment Methods  
There are several established procedures for aligning shafts. The dial indicator method is  
presented here since it is considered to be one of the most accurate and reliable. Another faster  
and easier method for alignment involves the use of laser alignment tools and computers.  
Follow the laser tool manufacturer’s guidelines when using the laser technique.  
Where job conditions such as close-spaced shafts prohibit the use of dial indicators for  
coupling face readings, other instruments such as a taper gage may be used. The same  
procedures described for the dial indicator may be used with the taper gage.  
Shafts placed in perfect alignment in the nonoperating (cold) condition will always move out  
of alignment to some extent as the machine warms to operating temperature. In most cases,  
this shaft misalignment is acceptable for the initial run-in period before hot check and alignment  
can be made (see Hot Alignment Check section.)  
General  
1.  
Final shaft alignment must be within .002-in. TIR (Total Indicated Runout) in parallel.  
Angular alignment must be within .00033 inches per inch of traverse across the coupling  
face (or inch of indicator swing diameter) at operating temperatures. For example, if a  
bracket-mounted indicator moves through a 10-in. diameter circle when measuring angular  
misalignment, the allowable dial movement will be 10 times .00033 for a total of .0033  
inches.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Follow the alignment sequence specified in the Near Final Alignment section.  
3. All alignment work is performed on gear and drive equipment. Once the compressor is  
bolted in a perfectly level position and is piped to cooler and condenser, it must not be  
moved prior to hot check.  
4. All alignment checks must be made with equipment holddown bolts tightened.  
5. In setting dial indicators on zero and when taking readings, both shafts should be tight  
against their respective thrust bearings.  
6. Space between coupling hub faces must be held to coupling manufacturer’s  
recommendations.  
7. Accept only repeatable readings.  
Gear and Drive Coupling Alignment  
1. Move gear with coupling attached into alignment with compressor coupling. Adjust  
jackscrews to reach close alignment. Follow procedures outlined in Correcting Angular  
Misalignment and Correcting Parallel Misalignment sections.  
2. Generally, a 5-in. long spacer hub is supplied between gear and compressor. Maintain  
exact hub-to-hub distance specified on job drawings.  
3. Where shaft ends are very close, a taper gage may be used in place of the dial indicator.  
4. Get drive alignment as close as possible by jackscrew adjustment.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Note: Drive shaft end-float at final drive position must not allow coupling hub faces to contact,  
or the coupling shroud to bind.  
Preliminary Alignment  
To get within dial indicator range, roughly align the equipment as shown in Figure 37 and as  
described below.  
Place a straight edge across the OD of one coupling to the OD of the other. Measure the gap  
between the straight edge and the OD of the second coupling with a feeler gage. Then, by  
adding or removing shims at each corner, raise or lower the equipment by the measured  
amount.  
In a similar manner, measure the shaft offset from side to side and jack the equipment over  
as required to correct.  
Click here for Figure 37 — Checking Preliminary Alignment  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Near Final Alignment  
Once the machine components are within dial indicator range, the adjustments for  
misalignment should be made in a specific sequence. The four positions of alignment described  
below are arranged in the recommended order.  
1.  
Angular in elevation — This alignment is adjusted with shims and is not readily lost in  
making the other adjustments.  
2.  
Parallel in elevation — This alignment is also made with shims, but it cannot be made while  
there is angular misalignment in elevation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Angular in plan —This position can easily be lost if placed ahead of the two adjustments in  
elevation.  
4. Parallel in plan — This adjustment cannot be made while there is still angular misalignment  
in plan, and can easily be lost if elevation adjustments are made.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Correcting Angular Misalignment  
Preparation — Shaft angular misalignment is measured on the face of the coupling hubs or  
on brackets attached to each shaft (see Figure 38 and Figure 39). Brackets are preferred since  
they extend the diameter of the face readings.  
Attach a dial indicator to one coupling hub or shaft and place the indicator button against the  
face of the opposite hub. Position the indicator so that the plunger is at approximately mid-  
position when the dial is set to zero. Both shafts should be held tightly against their thrust  
bearings when the dial is set and when readings are taken.  
To be sure that the indicator linkage is tight and the button is on securely, rotate the coupling  
exactly 360 degrees. The dial reading should return to zero. Accept only repeatable readings.  
Click here for Figure 38 — Measuring Angular Misalignment in Elevation  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Click here for Figure 39 — Measuring Angular Misalignment on Brackets  
Measurement — Occasionally, coupling faces may not be perfectly true, or may have been  
damaged in handling. To compensate for any such runout, determine the actual or ‘‘net’’ shaft  
misalignment as follows:  
Check the opening at the top and at the bottom of the coupling faces (or at each side when  
making plan adjustment). Rotate both shafts exactly 180 degrees and recheck the openings.  
Record the difference. (Example below is in inches.)  
If the larger opening remains the same but changes from side to side, the shafts are in  
perfect alignment. The change in opening is due entirely to coupling runout, as above,  
Download from Www.Somanuals.com. All Manuals Search And Download.  
or to a burr or other damage to the coupling face.  
If the larger opening remains the same, and remains on the same side, the amount is entirely  
shaft (net) misalignment.  
If the larger opening remains on the same side but changes amount, misalignment and  
runout are present. Add the two amounts and then divide by two to get the actual or net  
misalignment.  
If the larger opening changes amount and also changes from side to side, subtract the  
Download from Www.Somanuals.com. All Manuals Search And Download.  
smaller amount from the larger and divide by two to obtain the net misalignment.  
Adjustment — Having obtained the net misalignment, the amount by which the equipment  
must be moved can now be calculated.  
To determine:  
S — amount of movement (in plan) or the thickness of shim (in elevation) required.  
Obtain:  
D — coupling face diameter in inches (or indicator button circle)  
L — distance between front and rear holddown bolts (inches)  
M — net misalignment in inches  
And:  
Divide L, the bolt distance, by D, the coupling diameter. Multiply the result by M, the net  
misalignment.  
L
D
S =  
x M  
Click here for Figure 40 — Alignment Formula  
Example: Face diameter 5 in. (D). Distance between front and rear holddown bolts 30 in.  
(L). Net misalignment in elevation .012 in. (M).  
30 divided by 5 is 6  
6 multiplied by .012 is .072 in.  
S = .072 in.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the larger opening between coupling faces is at the top, place .072 in. of shim under each  
rear foot or remove .072 in. from the front footings to bring the couplings into angular alignment  
in elevation.  
Tighten the holddown bolts and recheck the net misalignment.  
The height of the shaft above the footings and the distance the shaft extends beyond the  
equipment will not affect the calculations.  
Determine the angular adjustment in plan by the same method of calculation. At this point,  
however, the procedure should include a correction for the change in coupling gap which  
always occurs in adjusting angular alignment. By selecting the proper pivot point (see  
Figure 40), the coupling gap can be kept at the dimension specified in the job data.  
1. Pivot on the front bolt at the closed side of the couplings to shorten the gap; pivot on the  
front bolt at the open side to lengthen it. It may sometimes be advantageous to pivot half the  
required amount on one front footing and half on the other.  
2. Place a dial indicator against the rear foot as indicated in Figure 41.  
3. Place a screw jack on the other rear foot to move the equipment towards the indicator.  
4. Loosen all holddown bolts except the pivot bolt. Turn the screw jack until the rear end of the  
equipment moves against the indicator by the desired amount.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Click here for Figure 41 — Adjusting Angular Misalignment in Plan  
5. Tighten the holddown bolts and recheck the indicator. If the reading has changed, loosen  
the three bolts and readjust. It may be necessary to over or undershoot the desired reading  
to allow for the effect of bolt tightening.  
Correcting Parallel Misalignment  
Preparation — Attach the dial indicator to one shaft or coupling hub and place the indicator  
button on the O.D. of the other hub. The reach of the dial from one hub to the other should be  
parallel to the shafts, and the dial button shaft should point directly through the center of the  
shaft on which it rests. Compress the plunger to about mid-position and set the dial at zero.  
Check the tightness of the dial button and the indicator linkage by rotating the shaft to which  
the indicator is attached 360 degrees. The dial should return to zero. Check for repeatability.  
Check for runout by rotating the hub on which the dial button rests 180 degrees. If the runout  
exceeds .001 total indicator reading, the hub should be removed and the shaft checked. Shaft  
runout must not exceed .001 TIR.  
The effect of hub runout can be eliminated by locating a position on the half coupling where  
two readings 180 degrees apart read zero. Rotate the coupling so that one zero point is at the  
top and the other at the bottom when checking for misalignment in elevation. Place the zero  
Download from Www.Somanuals.com. All Manuals Search And Download.  
points side to side in a similar manner when checking for misalignment in plan.  
Measurement — With dial set at zero in the top position, rotate the shaft to which the  
indicator is attached 180 degrees. If the dial reading is plus, the shaft on which the button rests  
is low. If the reading is minus, the shaft on which the button rests is high.  
Never accept a single reading. Look for repeatability. Rotate the shaft several times to see if  
the reading remains the same. It is good practice to reverse the procedure and read from zero  
at the bottom.  
Always rotate the shafts in the same direction when taking readings. Backlash in the coupling  
teeth could cause some differences.  
Adjustment — Divide the total indicator reading by two to obtain the exact amount of shaft  
offset. As illustrated in Figure 42, the indicator will read the total of A plus B but the required  
shaft adjustment is only half of this as indicated by C.  
Add or remove identical amounts of shims at all footings to bring the shaft to the proper  
elevation. Tighten all the holddown bolts and recheck the readings. Parallel alignment must be  
within .002 TIR.  
To correct parallel misalignment in plan, use a screw jack and dial indicator as shown in  
Figure 42. With a front holddown bolt as the pivot, move the rear of the equipment over. Then,  
with the rear holddown bolt on the same side acting as the pivot, move the front end of the  
equipment over by the same amount.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Final Alignment  
The procedures and tolerance requirements for final alignment are the same as those de-  
scribed in the Near Final Alignment section. Final alignment is performed just prior to grouting  
and machine hot check. All piping, including water and steam, must be completed, but the water  
and refrigerant charges need not be in place.  
Hot Alignment Check  
General  
When all machine components have reached operating temperature (after running near full  
load for from 4 to 8 hours), a hot alignment check must be made. Hot alignment check may be  
made with couplings assembled or disassembled.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Disassembled Couplings  
1. Shut down machine.  
2. With machine hot, quickly disassemble couplings.  
3. Check angular and parallel alignment in plan and elevation as described in the Near Final  
Alignment section. Record the indicator readings (see Initial Start-Up Checklist) and make  
necessary adjustments to bring alignment within .002 TIR and .00033 inches per in. of  
coupling face traverse (or in. of indicator swing). Follow procedures described in the Near  
Final Alignment section.  
4. Reinstall couplings and run machine until it again reaches operating temperature.  
Click here for Figure 42 — Correcting Parallel Misalignment  
5. Repeat steps 1 through 4 until alignment remains within specified tolerances.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Assembled Couplings  
If there is room on the shaft between coupling and component to clamp a sturdy bracket, the  
arrangement illustrated in Figure 43 may be used. The clamps must have room to rotate with  
the shaft.  
This method is quicker because the couplings do not have to be disassembled. In addition,  
eccentricity or coupling face runout are not problems since both shafts rotate together.  
When using brackets, the diameter in the alignment formula (see Near Final Alignment,  
Connecting Angular Misalignment section) will be that of the circle through which the dial  
indicator rotates.  
1. Shut down the machine.  
2. With machine at operating temperature, quickly install brackets.  
3. Check that alignment is within .002 TIR and .00033 per in. of traverse across the diameter  
of measurement. Adjust alignment as required. (Refer to Near Final Alignment section.)  
4. Remove brackets and run machine until operating temperature is again reached.  
5. Recheck the alignment per steps 1 through 4 until it remains within the specified tolerances.  
Be sure that coupling guards are replaced after these checks.  
Click here for Figure 43 —Alignment Check —Assembled Coupling  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Doweling  
Techniques  
After hot alignment check has been completed, the compressor, gear and drive must be  
doweled to their soleplates. Doweling permits exact repositioning of components if they have to  
be moved.  
1.  
2.  
Doweling must be completed with equipment at maximum operating temperature (full load).  
Use no. 8 taper dowels to dowel compressor, gear and drive to the base. Use a 13/32-in.  
drill and no. 8 taper reamer with straight flutes. Drill pilot hole and then expand the pilot hole  
to final dimension.  
3.  
Fit dowel so that 1/16-in. of taper is left above the equipment foot. If dowel holes are  
rereamed as a result of re-alignment, be sure dowels are tight and do not bottom.  
4.  
5.  
6.  
Place dowels as nearly vertical as possible.  
Coat the dowels with white lead or other lubricant to prevent rusting.  
Tap dowel lightly into position with a small machinist’s hammer. A ringing sound will  
indicate proper seating.  
Dowel the suction end of the compressor base, the two feet at the high speed end of the  
gear, and the drive feet in accordance with the drive manufacturer’s instructions. The number of  
dowels used in the drive is usually four, but some manufacturers require more.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Weekly Maintenance  
Check the Lubrication System  
Mark the oil level on the reservoir sight glass, and observe the level each week while the  
machine is shut down.  
If the level goes below the lower sight glass, the oil reclaim system will need to be checked  
for proper operation. If additional oil is required, add oil as follows:  
On hermetic machines, add oil through the oil drain charging valve (Figure 3, Item 26.) A  
pump is required for adding oil against refrigerant pressure. On open-drive machines, oil may  
be added through the oil drain and charging valve (Figure 2, Item 18) using a pump. However,  
an oil charging elbow on the seal-oil return chamber (Figure 6) allows oil to be added without  
pumping. The seal oil return pump automatically transfers the oil to the main oil reservoir. A  
pump is required for adding oil against refrigerant pressure. The oil charge is approximately  
15 gallons (57 L) for EX and FA (size 421-469) style compressors; 20 gallons (76 L) for EA (size  
531-599) style compressors. The added oil must meet Carrier’s specifications. Refer to  
Changing Oil Filter and Oil Changes sections. Any additional oil that is added should be logged  
by noting the amount and date. Any oil that is added due to oil loss that is not related to service  
will eventually return to the sump, and must be removed when the level is high.  
An oil heater is controlled by the PIC to maintain oil temperature above 150 F (65.5 C) or  
refrigerant temperature plus 70° F (38.9° C) (see the Controls section) when the compressor is  
Download from Www.Somanuals.com. All Manuals Search And Download.  
off. The LID Status02 screen displays whether the heater is energized or not. If the PIC shows  
that the heater is energized, but the sump is not heating up, the power to the oil heater may be  
off or the oil level may be too low. Check the oil level, the oil heater contactor voltage, and oil  
heater resistance.  
The PIC will not permit compressor start-up if the oil temperature is too low. The control will  
continue with start-up only after the temperature is within limits.  
After the initial start or a 3 hour power failure, the controls will allow the machine to start once  
the oil is up to proper temperature, but a slow ramp load rate of 2° F (1.6° C) per minute is used.  
Be sure that the hand isolation valves on the oil line near the filter(s) (Figure 44, Items 1 and  
2) are fully open before operating the compressor.  
Lubrication requirements for the FA coupling and drive are contained in the manufacturer’s  
instructions for these components.  
Click here for Figure 44 — Removing the Oil Filter  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Scheduled Maintenance  
Establish a regular maintenance schedule based on the actual machine requirements such  
as machine load, run hours, and water quality. The time intervals listed in this section are  
offered as guides to service only.  
Service Ontime  
The LID will display a SERVICE ONTIME value on the Status01 screen. This value should be  
reset to zero by the service person or the operator each time major service work is completed  
so that time between service can be viewed.  
Inspect the Control Center  
Maintenance is limited to general cleaning and tightening of connections. Vacuum the  
cabinet to eliminate dust build-up. In the event of machine control malfunctions, refer to the  
Troubleshooting Guide section for control checks and adjustments.  
CAUTION  
CAUTION  
!
Be sure power to the control center is off when cleaning and tightening connec-  
tions inside the control center.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Check Safety and Operating Controls Monthly  
To ensure machine protection, the Control Test Automated Test should be done at least  
once per month. See Table 3 for safety control settings.  
Changing Oil Filter  
19EX Compressors  
Change the oil filter on an annual basis or when the machine is opened for repairs. The 19EX  
compressor has an isolatable oil filter so that the filter may be changed with the refrigerant  
remaining in the machine. See Figure 44. Use the following procedure:  
1.  
2.  
3.  
4.  
5.  
Make sure that the compressor is off, and the disconnect for the compressor is open.  
Disconnect the power to the oil pump.  
Close the oil filter isolation valves (Figure 44, Items 1 and 2).  
Loosen the filter holding clamp, (Figure 44, Item 3).  
Rotate the filter nut, (Figure 44, Item 4), counterclockwise to remove the filter housing.  
Keep the filter housing upright to avoid an oil spill.  
6.  
7.  
Drain the oil; use this oil to obtain an oil analysis; remove and replace the filter cartridges.  
Do not use any of the extra felt washers supplied with the filters.  
Bench assemble Items A - D upside down, then slide the filter housing (Item 5) over the  
stack to ensure that the spring (Item D) is centered in the bottom of the housing as  
Download from Www.Somanuals.com. All Manuals Search And Download.  
indicated. Screw the assembly into the locking ring.  
8. Evacuate the filter/piping assembly.  
9. Open the isolation valves.  
FA Style Compressors  
1. Turn off oil heater.  
2. Close the line valve (Figure 44, Item 1) to isolate the oil filter(s).  
Note: FA STYLE COMPRESSORS DO NOT HAVE ISOLATION VALVE NO. 2, ONLY A  
CHECK VALVE. Vent the pressure in the oil filter by opening the Schrader valve on the  
oil filter housing. Run a hose from the valve to a bucket to catch the oil. Check to ensure  
that the check valve is properly seating.  
3. Loosen the filter holding clamp (Item 3).  
4. Rotate filter nut (Item 4) counterclockwise to remove filter housing. Keep the filter housing  
upright to avoid oil spill.  
5. Drain the oil; remove and replace filter cartridges. Do not use any of the extra felt washers  
supplied with the filters.  
6. Bench assemble Items A - D upside down. Then slide filter housing (Item 5) over the stack  
to ensure that spring (Item D) is centered in the bottom of the filter housing as indicated.  
7. Evacuate air from the filter assembly. Open the isolation valve.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Turn on oil heater and warm the oil to 140 to 150 F (60 to 66 C). Operate the oil pump for 2  
minutes. Add oil if required to keep level up to lower sight glass.  
Oil should be visible in the reservoir sight glass during all operating and shutdown condi-  
tions.  
Oil Specification  
If oil is to be added, it must meet the following Carrier specifications:  
• Oil Type for units using HFC-134a............................................ Inhibited  
polyol ester-based synthetic compressor oil formatted for use with  
HCFC and HFC, gear-driven, hermetic compressors.  
• ISO Viscosity Grade............................................................................68  
The polyol ester-based oil may be ordered from your local Carrier representative (Carrier  
Part No. PP23B2103).  
Oil Changes  
Carrier recommends changing the oil after the first year of operation and every three to five  
years thereafter as a minimum along with a yearly oil analysis. However, if a continuous oil  
monitoring system is functioning and a yearly oil analysis is performed, time between oil  
changes can be extended.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To Change the Oil  
1.  
2.  
Open the control and oil heater circuit breaker.  
Drain the oil reservoir by opening the oil charging valve, (Figure 2, Item 18 or Figure 3, Item  
26). Slowly open the valve against refrigerant pressure.  
3.  
4.  
5.  
Change the oil filter at this time. See Changing Oil Filter section.  
Change the refrigerant filter at this time, see the next section, Refrigerant Filter.  
Charge the machine with oil. The EX uses approximately 15 gallons (57 L), for EX and FA  
(size 421-469) style compressors; 20 gallons (76 L) for FA (size 531-599) style  
compressors in order to bring the level to the middle of the upper sight glass (Figure 2, Item  
17 and Figure 3, Item 19). Turn on the power to the oil heater and let the PIC warm it up to  
at least 140 F (60 C). Operate the oil pump manually, through the Control Test, for 2  
minutes. The oil level should be between the lower sight glass and one-half full in the upper  
sight glass for shutdown conditions.  
Refrigerant Filter  
On hermetic machines with EX compressor, a replaceable core refrigerant filter/drier is  
located on the refrigerant cooling line to the motor (Figure 3, Item 29). On FA style machines,  
the refrigerant filter is located behind the compressor. The filter core should be changed once a  
year, or more often if filter condition indicates a need for more frequent replacement. Change  
the filter with the machine pressure at 0 psig (0 kPa) by transferring the refrigerant to the utility  
Download from Www.Somanuals.com. All Manuals Search And Download.  
vessel. A moisture indicating sight glass is located beyond this filter to indicate the volume and  
moisture in the refrigerant. If the dry-eye indicates moisture, locate the source of water  
immediately by performing a thorough leak check.  
Oil Reclaim Filter  
The oil reclaim system has a filter on the cooler scavenging line. Replace this filter once per  
year, or more often if filter condition indicates a need for more frequent replacement. Change  
this filter with the cooler/condenser/compressor vessel at 0 psig (0 kPa) by transferring the  
refrigerant charge to the utility vessel.  
Inspect Refrigerant Float System  
Perform inspection once every 5 years or when the utility vessel is opened for service.  
Transfer the refrigerant into the cooler vessel, or into a storage tank. There are two floats on the  
17/19EX, one on each side of the utility vessel. Remove the float access covers. Clean the  
chambers and valve assembly thoroughly. Be sure that the valves move freely. Make sure that  
all openings are free of obstructions. Examine the cover gaskets and replace if necessary. See  
Figure 45 for a view of both floats.  
Inspect Relief Valves and Piping  
The relief valves on this machine protect the system against the potentially dangerous  
Download from Www.Somanuals.com. All Manuals Search And Download.  
effects of overpressure. To ensure against damage to the equipment and possible injury to  
personnel, these devices must be kept in peak operating condition.  
As a minimum, the following maintenance is required.  
1. At least once a year, disconnect the vent piping at the valve outlet and carefully inspect the  
valve body and mechanism for any evidence of internal corrosion or rust, dirt, scale,  
leakage, etc.  
2. If corrosion or foreign material is found, do not attempt to repair or recondition. Replace the  
valve.  
3. If the machine is installed in a corrosive atmosphere or the relief valves are vented into a  
corrosive atmosphere, make valve inspections at more frequent intervals.  
Coupling Maintenance (Open-Drive Machines)  
Proper maintenance of the coupling is important since the coupling supports the outboard  
end of the compressor low speed shaft. Only the compressor end of the coupling has gear teeth  
and these are manufactured with special tolerances for this application.  
Procedure  
Clean and inspect the gear teeth in the compressor end coupling for wear yearly. If the teeth  
are worn, replace the tapered coupling hub, sleeve and O-ring. Repack the gear teeth and  
Download from Www.Somanuals.com. All Manuals Search And Download.  
spacer with 8 oz. of Kop-Flex KHP high performance coupling grease (Carrier Part No. 17DK  
680 001). Install new gaskets.  
When the coupling assembly is removed for scheduled service of the carbon seal, replace  
the O-ring, spacer gaskets, and hex bolts.  
Operating conditions such as high temperatures or severe environments may require more  
frequent inspection and relubrication.  
Misalignment causes undue noise and wear. Check alignment yearly, or more often if  
vibration or heating occur. Refer to Machine Alignment section.  
WARNING  
WARNING  
!
Never operate drive without coupling guards in place. Contact with moving shaft  
or coupling can cause serious injury.  
Click here for Figure 45 — Typical Float Valve Arrangement  
Motor Maintenance (Open-Drive Machines)  
A carefully planned and executed program of inspection and maintenance will do much to  
ensure maximum motor availability and minimum maintenance cost. If it becomes necessary to  
Download from Www.Somanuals.com. All Manuals Search And Download.  
repair, recondition, or rebuild the motor, it is recommended that the nearest Westinghouse  
apparatus repair facility be consulted.  
In addition to a daily observation of the appearance and operation of the motor, it is  
recommended that a general inspection procedure be established to periodically check the  
following items:  
1. Cleanliness, both external and internal  
2. Stator and rotor (squirrel-cage) windings  
3. Bearings  
Cleanliness  
On open ventilated motors, screens and louvers over the inlet air openings should not be  
allowed to accumulate any build-up of dirt, lint, etc. that could restrict free air movement.  
Screens and louvers should never be cleaned or disturbed while the motor is in operation  
because any dislodged dirt or debris can be drawn directly into the motor.  
If the motor is equipped with air filters, they should be replaced (disposable type) or cleaned  
and reconditioned (permanent type) at a frequency that is dictated by conditions. It is better to  
replace or recondition filters too often than not often enough.  
Totally enclosed, air-to-air cooled (TEAAC) motors and totally enclosed, fan-cooled (TEFC)  
motors require special cleaning considerations. The external fan must be cleaned thoroughly  
since any dirt build-up not removed can lead to imbalance and vibration. All of the tubes of the  
Download from Www.Somanuals.com. All Manuals Search And Download.  
air-to-air heat exchanger of TEAAC motors should be cleaned using a supplied tube brush  
having synthetic fiber bristles (not wire of any type). The standard cooler is equipped with steel  
tubes, however, in special cases aluminum tubes may be used and wire brushes can seriously  
erode the tube interiors over several cleanings. All tube brushing should be conducted from the  
front (fan end) toward the drive end of the motor such that dislodged dirt will not fall into the fan  
housing.  
CAUTION  
CAUTION  
!
Water spray washing of motors is not recommended. Manual or compressed air  
cleaning is preferred. If it becomes necessary to spray wash a motor, it should  
be done with extreme care. Do not aim high pressure sprays directly at air inlet  
openings, conduit connections, shaft seals, or gasketed surfaces to prevent the  
possibility of forcing water inside the machine.  
The stator windings of motors with open ventilation systems can become contaminated with  
dirt and other substances brought into the motor by the ventilating air. Such contaminants can  
impair cooling of the winding by clogging the air passages in the winding end-turns and vent  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ducts through the stator core and by reducing heat transfer from the winding insulation surfaces  
to the cooling air. Conducting contaminants can change or increase electrical stresses on the  
insulation and corrosive contaminants can chemically attack and degrade the insulation. This  
may lead to shortened insulation life and failure.  
Several satisfactory methods of cleaning stator windings and stator cores are offered below:  
Compressed Air  
Low pressure (30 psi max.), clean (no oil) and dry air can be used to dislodge loose dust and  
particles in inaccessible areas such as air vent ducts in the stator core and vent passages in the  
winding end-turns. Excessive air pressure can damage insulation and can drive contaminants  
into inaccessible cracks and crevices.  
Vacuum  
Vacuum cleaning can be used, both before and after other methods of cleaning, to remove  
loose dirt and debris. It is a very effective way to remove loose surface contamination from the  
winding without scattering it. Vacuum cleaning tools should be nonmetallic to avoid any damage  
to the winding insulation.  
Wiping  
Surface contamination on the winding can be removed by wiping, using a soft, lint-free  
wiping material. If the contamination is oily, the wiping material can be moistened (not dripping  
wet) with a safety-type petroleum solvent, such as Stoddard solvent. In hazardous locations, a  
Download from Www.Somanuals.com. All Manuals Search And Download.  
solvent such as inhibited methyl chloroform may be used, but must be used sparingly and  
immediately removed. While this solvent is non-flammable under ordinary conditions, it is toxic  
and proper health and safety precautions should be followed while using it.  
Solvents of any type should never be used on windings provided with abrasion protection.  
Abrasion protection is a grey, rubber-like coating applied to the winding end-turns.  
WARNING  
WARNING  
!
Adequate ventilation must always be provided in any area where solvents are  
being used to avoid the danger of fire, explosion or health hazards. In confined  
areas (such as pits) each operator should be provided with an air line respirator, a  
hose mask or a self-contained breathing apparatus. Operators should wear gog-  
gles, aprons and suitable gloves. Solvents and their vapors should never be  
exposed to open flames or sparks and should always be stored in approved  
safety containers.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Sleeve Bearings  
Oil Changing  
The oil reservoirs of the self lubricated bearings should be drained and refilled every 6  
months. More frequent changes may be needed if severe oil discoloration or contamination  
occurs. In conditions where contamination does occur, it may be advisable to flush the reservoir  
with kerosene to remove any sediment before new oil is added. Proper care must be taken to  
thoroughly drain the reservoir of the flushing material before refilling with the new oil.  
Refill the reservoir to the center of the oil sight glass with a rust and oxidation inhibited,  
turbine grade oil. The viscosity of the oil must be 32 ISO (150 SSU) at 100 F (37.7 C). Oil  
capacity in each of the 2 bearings is 0.6 gal. (2 l) per bearing. Use of Carrier Oil Specification  
PP16-0 is approved (Mobil DTE Light or Sun Oil SUNVIS 916).  
Disassembly  
The bearing sleeve is of the spherically seated, self-aligning type. The opposite drive end  
bearing is normally insulated for larger motors (or when specified). On some motors, the  
insulation is bonded to the spherical seat of the bearing housing. Use extreme care when  
removing the sleeve from the insulated support to avoid damaging this insulation.  
Note that some bolts and tapped holes associated with the bearing housings, bearing  
sleeves, and seals are metric.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The following is the recommended procedure for removing the bearing sleeve:  
1. Remove the oil drain plug in the housing bottom and drain the oil sump.  
2. Remove all instrumentation sensors that are in contact with the bearing sleeve. These  
would include resistance temperature detectors, thermocouples, temperature relay bulbs,  
thermometers, etc.  
3. Remove the end cover.  
4. Remove the socket head bolts holding the bearing cap and the inner air seal together at the  
horizontal split. The front end cover plate must also be removed if the front bearing is being  
disassembled. Remove the bearing cap and top half of the inner air seal by lifting straight  
up to avoid damaging the labyrinth seals. Place them on a clean, dry surface to avoid  
damage to the parting surfaces.  
5. Remove any split bolts that may be holding the two bearing halves together. Remove the  
top half of the bearing sleeve using suitable eye-bolts in the tapped holes provided. Lift the  
bearing top straight up and avoid any contact with the shoulders of the shaft journals that  
might damage the thrust faces of the bearing. Place on a clean, dry surface taking care to  
prevent damage to either the parting surfaces or the locating pins that are captive in the top  
bearing half.  
6. Remove the 4 screws at the partings in the oil ring and dismantle the ring by gently tapping  
the dowel pin ends with a soft face mallet. Remove the ring halves and immediately  
Download from Www.Somanuals.com. All Manuals Search And Download.  
reassemble them to avoid any mix up in parts or damage to the surfaces at the partings.  
7. When removing the labyrinth seals, make note of the position of the anti-rotation button  
located on the inside of the top half of the seal. Pull up the garter spring surrounding the  
floating labyrinth seal and carefully slip out the top half. Rotate the garter spring until the  
lock is visible. Twist counterclockwise to disengage the lock, remove the garter spring, then  
rotate the lower half of the seal out of the groove in the bearing housing while noting the  
orientation of the oil drain holes. Note the condition of these floating labyrinth seals. If they  
are cracked or chipped, they must be replaced. Do not attempt to reuse a damaged seal.  
8. To remove the bottom bearing half, the shaft must be raised a slight amount to relieve  
pressure on the bearing. On the rear end, this can be done by jacking or lifting on the shaft  
extension. (Care must be taken to protect the shaft from damage.) On the front end, jacking  
or lifting can be done using bolts threaded into the tapped holes provided in the shaft end.  
Note: Lift only enough to free the bearing; overlifting the shaft can cause difficulty in removal of  
the bearing.  
9. Roll the bottom bearing half to the top of the shaft journal and then lift it using suitable  
eyebolts threaded into the holes provided. Again avoid any contact with the shaft shoulders  
that could damage the bearing thrust faces. Place the lower bearing half on a clean, dry  
surface to protect the parting surfaces.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING  
WARNING  
!
Use extreme care when rolling out the lower bearing half. Keep the hands and fin-  
gers well clear of any position where they might be caught by the bearing half if it  
were accidentally released and rotated back to its bottom position. Serious per-  
sonal injury could result.  
10. Protect the shaft journal by wrapping it with clean, heavy paper or cardboard.  
Reassembly  
Bearing reassembly is basically a reversal of the disassembly procedures outlined above,  
with the following additional steps.  
CAUTION  
CAUTION  
!
Curil-T is the only approved compound for use in the assembly of the bearings  
on this motor. Other products may harden and impede the operation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION  
CAUTION  
!
During the reassembly of the bearing parts, a thin layer of Curil-T should be  
applied to all gasketed and machined interface surfaces. This suggestion does  
not apply to the machined surfaces of the bearing liner halves.  
CAUTION  
CAUTION  
!
When seating the bearing shell, apply a thin layer of lube oil at the spherical sur-  
face of the liner. Slowly roll the lower bearing liner into the bearing housing mak-  
ing sure that the split surfaces of the liner and the housing are flush. Gradually  
lower the shaft onto the bearing. The weight of the shaft will help rotate the bear-  
ing liner so that the babbitt surface of the liner will match the slope of the journal.  
Sometimes it is required to use a rubber mallet to tap lightly on the bearing hous-  
ing while slowly rolling the shaft to help this seating operation.  
1. The interior of the bearing housing should be cleaned and then flushed with clean oil or  
kerosene.  
2. The bearing halves and the shaft journal should be wiped clean using lint-free cloth soaked  
with clean oil.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. All parts should be carefully inspected for nicks, scratches, etc., in any contact surfaces.  
Such imperfections should be removed by an appropriate method such as stoning,  
scraping, filing, etc., followed by thorough cleaning.  
4. Apply a few drops of oil to the journal and bearing saddles.  
5. Roll the bottom half of the bearing into place and lower the shaft.  
6. Before installing the floating labyrinth seal halves, observe their condition. Do not attempt to  
use a cracked or chipped seal. The bottom half seal has a set of drilled holes in its side  
face. These must be placed at the bottom toward the inside of the bearing so that  
accumulating oil may drain back into the housing.  
7. Put a small head of Curil-T around the bottom seal half outside diameters on both sides  
adjacent to the garter spring groove. This will prevent oil by-passing the seal around its  
outside.  
8. Place the bottom seal half on top of the shaft (ensuring that the proper orientation of the  
drain holes is provided and roll it into position. Install the top half of the seal making sure  
that the anti-rotation button is located in the proper position on the inboard side of the  
bearing. Insert the garter spring pulling up on both ends to permit engaging the lock. Run a  
small bead of Curil-T around the outside diameters on both sides adjacent to the garter  
spring groove on this half also.  
9. Carefully reassemble the two oil ring halves. Inspect the dowel pins for burrs and  
Download from Www.Somanuals.com. All Manuals Search And Download.  
straightness and make any corrections required. Do not force the ring halves together.  
Excessive force may alter the roundness or flatness of the ring which can change its oil  
delivery performance. Apply locking compound to the oil ring screws prior to reassembly.  
10. Assemble the top half of the bearing liner making sure that the match marks on the liner  
halves align with one another. Failure to ensure alignment of match marks can cause  
misalignment and possible damage to bearings and journal surfaces. Reinstall any split  
bolts, if supplied, between the bearing halves.  
11. Some of the pipe plugs in the housing are metric thread type. These are identified as those  
which have a copper, lead, or similar material washer. If these plugs are removed, be  
careful not to lose the washers. Before reassembly, inspect the washers and replace them  
as required.  
12. Before installing the bearing cap, observe the position of the floating labyrinth seal. The  
‘‘tab’’ must be on top to engage the pocket. Failure to position the seal properly will result in  
damage when the cap is assembled.  
13. Carefully lower the bearing housing cap over the floating seals. Keep the bearing cap level  
to avoid binding and possibly damaging the seals. The bearing cap should seat evenly on  
the bearing housing base.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION  
CAUTION  
!
Do not force bearing cap down. Damage could occur to the labyrinth seals.  
If the bearing cap does not seat completely, remove and reset the floating labyrinth seal  
position. When installing upper bearing cap the floating labyrinth seals sometimes rotate  
and the anti-rotation ‘‘tab’’ does not seat in its holder, thus preventing the bearing housing  
from seating properly. This procedure should be repeated until the bearing cap seats prop-  
erly.  
14. Reinstall the bearing housing split bolts. Before torquing bearing housing cap bolts, rotate  
shaft by hand while bumping bearing housing with a rubber or rawhide mallet in the  
horizontal and axial planes to allow the bearings to align themselves to the shaft journals.  
15. Torque the bearing housing cap bolts by following the torque values as provided in Table 6.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Open-Drive Motor Handling/Rigging  
Each motor is provided with lifting lugs, welded to the four corners of the motor frame, for  
lifting the assembled machine. The motor should always be lifted by using the lifting lugs  
located on all four corners of the motor frame. (See Figure 46.)  
CAUTION  
CAUTION  
!
Spreader bars of adequate capacity and number must be used to avoid applying  
any pressure against the top air housing with the lifting plugs.  
Click here for Figure 46 — Lifting Open-Drive Motor  
If the motor is lifted with the top air housing removed, the angle of the lifting slings with the  
horizontal should never be less than 45 degrees.  
With the exclusion of the TEWAC cooler, the top air housing is provided with 3/4 -10 tapped  
holes for lifting devices to be installed in order to remove the air housing from the motor. The top  
air housing can be detached by removing the enclosure holddown bolts, located in the inside  
corners of the enclosure. These enclosure holddown bolts are accessed through the louver/  
screens located on the front and rear end of the machine or through access panels bolted to the  
sides of the enclosure.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION  
CAUTION  
!
Uneven lifting must always be avoided. When single point lifting is to be used,  
slings of equal lengths must always be used to avoid uneven lifting.  
CAUTION  
CAUTION  
!
Under no circumstances should the motor be lifted using the shaft as an attach-  
ment point.  
Note: Refer to weights specified on certified drawing to determine proper lifting equipment  
required for specific components or assemblies.  
Open-Drive Motor Storage  
If the machine is to be placed in extended shutdown, certain precautions must be taken to  
provide proper protection while the motor is being stored. The motor should be stored under  
cover in a clean, dry location and should be protected from rapid temperature changes.  
Since moisture can be very detrimental to electrical components, the motor temperature  
should be maintained at approximately 5° F (3° C) above the dew point temperature by  
providing either external or internal heat. If the motor is equipped with space heaters, they  
Download from Www.Somanuals.com. All Manuals Search And Download.  
should be energized at the voltage shown by the space heater nameplate attached to the  
motor. Incandescent light bulbs can be placed within the motor to provide heat. However, if  
used, they must not be allowed to come in contact with any parts of the motor because of the  
concentrated hot spot that could result.  
This motor has been provided with a shaft shipping brace or shipping bolt (normally painted  
yellow) to prevent shaft movement during transit, it must be removed to allow shaft rotation  
(refer to Before Initial Start-Up, Remove Shipping Packaging section). It is very important that  
this brace be reinstalled exactly as it was originally, before the motor is moved from storage or  
any time when the motor is being transported. This prevents axial rotor movement that might  
damage the bearings.  
Motors equipped with sleeve bearings are shipped from the factory with the bearing oil  
reservoirs drained. In storage, the oil reservoirs should be properly filled to the center of the oil  
level gage with a good grade of rust inhibiting oil (refer to the certified drawing for oil viscosity  
and any special requirements). To keep the bearing journals well oiled and to prevent rusting,  
the motor shaft should be rotated several revolutions every 2 weeks. While the shaft is rotating  
it should be pushed to both extremes of the endplay to allow for oil flow over the entire length of  
the journals.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Compressor Bearing and Gear Maintenance  
The key to good bearing and gear maintenance is proper lubrication. Use the proper grade of  
oil, maintained at recommended level, temperature, and pressure. Inspect the lubrication  
system regularly and thoroughly.  
Only a trained service technician should remove and examine the bearings. The bearings  
and gears should be examined on a scheduled basis for signs of wear. The frequency of  
examination is determined by the hours of machine operation, load conditions during operation,  
and the condition of the oil and the lubrication system. Excessive bearing wear can sometimes  
be detected through increased vibration or increased bearing temperature. If either symptom  
appears, contact an experienced and responsible service organization for assistance.  
Inspect the Heat Exchanger Tubes  
Cooler  
Inspect and clean the cooler tubes at the end of the first operating season. Because these  
tubes have internal ridges, a rotary-type tube cleaning system is necessary to fully clean the  
tubes. Upon inspection, the tube condition will determine the scheduled frequency for cleaning,  
and will indicate whether water treatment is adequate in the chilled water/brine circuit. Inspect  
the entering and leaving chilled water temperature sensors for signs of slime, corrosion, or  
scale. Replace the sensor if corroded or remove any scale if found.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Condenser  
Since this water circuit is usually an open-type system, the tubes may be subject to  
contamination and scale. Clean the condenser tubes with a rotary tube cleaning system at least  
once per year, and more often if the water is contaminated. Inspect the entering and leaving  
condenser water sensors for signs of slime, corrosion, or scale. Replace the sensor if corroded  
or remove any scale if found.  
Higher than normal condenser pressures, together with the inability to reach full refrigeration  
load, usually indicate dirty tubes or air in the machine. If the refrigeration log indicates a rise  
above normal condenser pressures, check the condenser refrigerant temperature against the  
leaving condenser water temperature. If this reading is more than what the design difference is  
supposed to be, then the condenser tubes may be dirty, or water flow may be incorrect.  
Because HFC134-a is a high-pressure refrigerant, air usually does not enter the machine,  
rather, the refrigerant leaks out.  
During the tube cleaning process, use brushes especially designed to avoid scraping and  
scratching the tube wall. Contact your Carrier representative to obtain these brushes. Do not  
use wire brushes.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION  
CAUTION  
!
Hard scale may require chemical treatment for its prevention or removal. Consult  
a water treatment specialist for proper treatment.  
Water Leaks  
Water is indicated during machine operation by the refrigerant moisture indicator (Figure 2)  
on the refrigerant motor cooling line. Water leaks should be repaired immediately.  
CAUTION  
CAUTION  
!
Machine must be dehydrated after repair of water leaks. See  
section.  
Machine Dehydration  
Water Treatment  
Untreated or improperly treated water may result in corrosion, scaling, erosion, or algae. The  
services of a qualified water treatment specialist should be obtained to develop and monitor a  
treatment program.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION  
CAUTION  
!
Water must be within design flow limits, clean, and treated to ensure proper  
machine performance and reduce the potential of tubing damage due to corro-  
sion, scaling, erosion, and algae. Carrier assumes no responsibility for chiller  
damage resulting from untreated or improperly treated water.  
Inspect the Starting Equipment  
Before working on any starter, shut off the machine, and open all disconnects supplying  
power to the starter.  
WARNING  
WARNING  
!
The disconnect on the starter front panel does not deenergize all internal circuits.  
Open all internal and remote disconnects before servicing the starter.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING  
WARNING  
!
Never open isolating knife switches while equipment is operating. Electrical arc-  
ing can cause serious injury.  
Inspect starter contact surfaces for wear or pitting on mechanical-type starters. Do not  
sandpaper or file silver-plated contacts. Follow the starter manufacturer’s instructions for  
contact replacement, lubrication, spare parts ordering, and other maintenance requirements.  
Periodically vacuum or blow off accumulated debris on the internal parts with a high-velocity,  
low-pressure blower.  
Power connections on newly installed starters may relax and loosen after a month of  
operation. Turn power off and retighten. Recheck annually thereafter.  
CAUTION  
CAUTION  
!
Loose power connections can cause voltage spikes, overheating, malfunction-  
ing, or failures.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Check Pressure Transducers  
Once a year, the pressure transducers should be checked against a pressure gage reading.  
Check all three transducers: oil pressure, condenser pressure, cooler pressure.  
Note the evaporator and condenser pressure readings on the Status01 screen on the LID.  
Attach an accurate set of refrigeration gages to the cooler and condenser Schrader fittings.  
Compare the two readings. If there is a difference in readings, the transducer can be calibrated,  
as described in the Troubleshooting Guide section.  
Pumpout System Maintenance  
For compressor maintenance details, refer to the 06D, 07D Installation, Start-Up, and  
Service Instructions.  
Optional Pumpout Compressor Oil Charge  
Use oil conforming to Carrier specifications for reciprocating compressor usage. Oil  
requirements are as follows:  
• HFC-134a  
ISO Viscosity ................................68  
Carrier Part Number ..................PP23BZ103  
The total oil charge, 4.5 pints (2.6 L), consists of 3.5 pints (2.0 L) for the compressor and one  
additional pint (0.6 L) for the oil separator.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Oil should be visible in the compressor sight glass both during operation and at shutdown.  
Always check the oil level before operating the compressor. Before adding or changing oil,  
relieve the refrigerant pressure as follows:  
1. Attach a pressure gage to the gage port of either compressor service valve (Figure 34).  
2. Close the suction service valve and open the discharge line to the storage tank or the  
machine.  
3. Operate the compressor until the crankcase pressure drops to 2 psig (13 kPa).  
4. Stop the compressor and isolate the system by closing the discharge service valve.  
5. Slowly remove the oil return line connection (Figure 33). Add oil as required.  
6. Replace the connection and reopen the compressor service valves.  
Figure 47  
Pumpout Safety Control Settings (  
)
The pumpout system high-pressure switch should open at 161 psig (1110 kPa) and closes at  
130 psig (896 kPa). Check the switch setting by operating the pumpout compressor and slowly  
throttling the pumpout condenser water.  
Click here for Figure 47 — Controls for Optional Pumpout Compressor  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ordering Replacement Chiller Parts  
When ordering Carrier specified parts, the following information must accompany an order:  
• machine model number and serial number  
• name, quantity, and part number of the part required  
• delivery address and method of shipment  
Open-Drive Motor Renewal Parts  
Renewal parts information for the motor and any auxiliary devices can be obtained from the  
nearest Westinghouse Motor Company sales office. A complete description of the part(s)  
required is necessary, together with the complete motor nameplate reading for positive motor  
identification.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide  
Overview  
The PIC has many features to aid the operator and the technician in troubleshooting a  
17/19EX machine.  
• By using the LID display, the chiller actual operating conditions can be viewed while  
the unit is running.  
• The Control Algorithm Status screens will display various screens of information in  
order to diagnose problems with chilled water temperature control, chilled water tem-  
perature control overrides, hot gas bypass, surge algorithm status, and time schedule  
operation.  
• The Control Test feature allows proper operation and testing of temperature sensors,  
pressure transducers, the guide vane actuator, oil pump, water pumps, tower control,  
and other on/off outputs while the compressor is stopped. It also has the ability to lock  
off the compressor and turn on water pumps for pumpout operation. The display will  
show the required temperatures and pressures during these operations.  
• Other Service menu tables can access configured items, such as chilled water resets,  
override set points, etc.  
• If an operating fault is detected, an alarm message is generated and displayed on the  
LID default screen. A more detailed message — along with a diagnostic message —  
also is stored into the Alarm History table.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Checking the Display Messages  
The first area to check when troubleshooting the 17/19EX is the LID display. If the alarm light  
is flashing, check the primary and secondary message lines on the LID default screen (Figure  
14). These messages will indicate where the fault is occurring. The Alarm History table on the  
LID Service menu will also carry an alarm message to further expand on this alarm. For a  
complete listing of messages, see Table 8. If the alarm light starts to flash while accessing a  
menu screen, depress EXIT to return to the Default screen to read the failure message. The  
compressor will not run with an alarm condition existing, unless the alarm type is an  
unauthorized start or a failure to shut down.  
Checking Temperature Sensors  
All temperature sensors are of the thermistor type. This means that the resistance of the  
sensor varies with temperature. All sensors have the same resistance characteristics.  
Determine sensor temperature by measuring voltage drop if the controls are powered, or  
resistance if the controls are powered off. Compare the readings to the values listed in Table 9A  
or Table 9B.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Resistance Check  
Turn off the control power and disconnect the terminal plug of the sensor in question from the  
module. Measure sensor resistance between receptacles designated by the wiring diagram with  
a digital ohmmeter. The resistance and corresponding temperature is listed in Table 9A or  
Table 9B. Check the resistance of both wires to ground. This resistance should be infinite.  
Voltage Drop  
Using a digital voltmeter, the voltage drop across any energized sensor can be measured  
while the control is energized. Table 9A or Table 9B lists the relationship between temperature  
and sensor voltage drop (volts dc measured across the energized sensor). Exercise care when  
measuring voltage to prevent damage to the sensor leads, connector plugs, and modules.  
Sensor wire should also be checked at the sensor plug connection. Check the sensor wire by  
removing the condenser at the sensor and measure for 5 vdc back to the module if the control is  
powered.  
CAUTION  
CAUTION  
!
Relieve all refrigerant pressure or drain the water prior to replacing the tempera-  
ture sensors.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Check Sensor Accuracy  
Place the sensor in a medium of a known temperature and compare that temperature to the  
measured reading. The thermometer used to determine the temperature of the medium should  
be of laboratory quality with 0.5° F (.25° C) graduations. The sensor in question should be  
accurate to within 2° F (1.2° C).  
See Figure 7 and Figure 8 for sensor locations. The sensors are immersed directly in the  
refrigerant or water circuits. The wiring at each sensor is easily disconnected by unlatching the  
connector. These connectors allow only one-way connection to the sensor. When installing a  
new sensor, apply a pipe sealant or thread sealant to the sensor threads.  
Dual Temperature Sensors  
There are 2 sensing elements on each of the bearing temperature sensors (hermetic and  
open-drive machines) and motor temperature sensors (hermetic machines only) for servicing  
convenience. In case one of the dual sensors is damaged, the other one can be used by  
moving a wire.  
The number 1 terminal in the sensor terminal box is the common line. To use the second  
sensor, move the wire from the number 2 position to the number 3 position.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Checking Pressure Transducers  
There are 3 pressure transducers on hermetic machines. These determine cooler,  
condenser, and oil pressure. Open-drive machines have 4 transducers. These transducers  
sense cooler pressure, condenser pressure, oil supply pressure, and oil sump pressure. The oil  
supply pressure and the oil transmission sump pressure difference is calculated by a differential  
pressure power supply module on open-drive machines. The PSIO then reads this differential.  
In effect, then, the PSIO reads 3 pressure inputs for open-drive machines and 3 pressure inputs  
for hermetic machines. The cooler and condenser transducers are used by the PIC to  
determine refrigerant temperatures.  
All pressure inputs can be calibrated, if necessary. It is not usually necessary to calibrate at  
initial start-up. However, at high altitude locations, calibration of the transducer will be  
necessary to ensure the proper refrigerant temperature/pressure relationship. Each transducer  
is supplied with 5 vdc power from a power supply. If the power supply fails, a transducer voltage  
reference alarm will occur. If the transducer reading is suspected of being faulty, check the  
supply voltage. It should be 5 vdc ± .5 v. If the supply voltage is correct, the transducer should  
be recalibrated or replaced.  
IMPORTANT: For hermetic machines, whenever the oil pressure or the cooler pres-  
sure transducer is calibrated, the other sensor should be calibrated to prevent prob-  
lems with oil differential pressure readings.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To calibrate oil pressure differential on open-drive machines, refer to Oil Pressure Differential  
Calibration at the end of this section.  
Calibration can be checked by comparing the pressure readings from the transducer against  
an accurate refrigeration gage. These readings are all viewed or calibrated from the Status01  
table on the LID. The transducer can be checked and calibrated at 2 pressure points. These  
calibration points are 0 psig (0 kPa) and between 240 and 260 psig (1655 to 1793 kPa). To  
calibrate these transducers:  
1. Shut down the compressor.  
2. Disconnect the transducer in question from its Schrader fitting.  
Note: If the cooler or condenser vessels are at 0 psig (0 kPa) or are open to atmospheric pres-  
sure, the transducers can be calibrated for zero without removing the transducer from  
the vessel.  
3. Access the Status01 table, and view the particular transducer reading; it should read 0 psi  
(0 kPa). If the reading is not 0 psi (0 kPa), but within ± 5 psi (35 kPa), the value may be  
zeroed by pressing the SELECT softkey while the highlight bar is located on the transducer,  
and then by pressing the ENTER. The value will now go to zero.  
If the transducer value is not within the calibration range, the transducer will return to the  
original reading. If the LID pressure value is within the allowed range (noted above), check  
the voltage ratio of the transducer. To obtain the voltage ratio, divide the voltage (dc) input  
Download from Www.Somanuals.com. All Manuals Search And Download.  
from the transducer by the supply voltage signal, measured at the PSIO terminals J7-J34  
and J7-J35. For example, the condenser transducer voltage input is measured at PSIO ter-  
minals J7-1 and J7-2. The voltage ratio must be between 0.80 vdc and 0.11 vdc for the soft-  
ware to allow calibration. Pressurize the transducer until the ratio is within range. Then  
attempt calibration again.  
4. A high pressure point can also be calibrated between 240 and 260 psig (1655 and  
1793 kPa) by attaching a regulated 250 psig (1724 kPa) pressure (usually from a nitrogen  
cylinder). The high pressure point can be calibrated by accessing the transducer on the  
Status01 screen, highlighting the transducer, pressing the SELECT softkey, and then  
increasing or decreasing the value to the exact pressure on the refrigerant gage. Press  
ENTER to finish. High altitude locations must compensate the pressure so that the  
temperature/pressure relationship is correct.  
If the transducer reading returns to the previous value and the pressure is within the  
allowed range, check the voltage ratio of the transducer. Refer to Step 3 above. The voltage  
ratio for this high pressure calibration must be between 0.585 and 0.634 vdc to allow cali-  
bration. Change the pressure at the transducer until the ratio is within the acceptable range.  
Then attempt calibrate to the new pressure input.  
The PIC will not allow calibration if the transducer is too far out of calibration. A new  
transducer must be installed and re-calibrated.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Oil Differential Pressure/Power Supply Module Calibration (See Figure 48.)  
The oil reservoir in the 17EX machine is not common to cooler pressure. Therefore, a  
comparison of pump output to cooler pressure could not be used to provide differential oil  
pressure information. A different method has been developed.  
Oil transmission sump pressure and oil supply pressure are fed to a comparator circuit on a  
5V power supply board. The output of this circuit, which represents differential oil pressure, is  
fed to the PSIO. The oil differential pressure is calibrated to zero PSIO (0 kPad) by selecting the  
oil pressure input on the Service1 screen. Then, with the oil pump turned OFF and the  
transducers CONNECTED, press ENTER to zero the point. No high end calibration is needed  
or possible.  
Click here for Figure 48 — Oil Differential Pressure/Power Supply Module  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Transducers  
When troubleshooting transducers, keep the negative lead of your voltohmmeter on terminal  
U4 of the power supply (or terminal 4 on power supplies without the comparator circuit).  
voltage VO1 = (VH1-VL1) + .467 ± .1 V  
For all PIC transducers:  
Measured pressure = (507.97 × (Vout /Vin)) -47.33  
Vout = transducer output ref. to neg. terminal (4 or U4) i.e., VH1 to U4 or VL1 to U4  
Vin  
= power supply output, i.e., U3 to U4  
Transducer Replacement  
Since the transducers are mounted on Schrader-type fittings, there is no need to remove  
refrigerant from the vessel. Disconnect the transducer wiring by pulling up on the locking tab  
while pulling up on the weather-tight connecting plug from the end of the transducer. Do not pull  
on the transducer wires. Unscrew the transducer from the Schrader fitting. When installing a  
new transducer, do not use pipe sealer, which can plug the sensor. Put the plug connector back  
on the sensor and snap into place. Check for refrigerant leaks.  
WARNING  
WARNING  
!
Make sure to use a backup wrench on the Schrader fitting whenever removing a  
transducer.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Algorithms Checkout Procedure  
In the LID Service menu, one of the tables is Control Algorithm Status. This table contains 6  
tables that may be viewed in order to see how the particular control algorithm is operating.  
MAINT01  
MAINT02  
MAINT03  
Capacity Control  
This table shows all values that are used to calculate the  
chilled water/brine control point.  
Details of all chilled water control override values are  
viewed here.  
The surge and hot gas bypass control algorithm status is  
viewed from this screen. All values dealing with this con-  
trol are displayed.  
Override Status  
Surge/HGBP  
Status  
MAINT04  
LEAD/LAG Status This screen indicates LEAD/LAG operation status.  
OCCDEFM  
Time Schedules  
Status  
The Local and CCN occupied schedules are displayed  
here in a manner that allows the operator to quickly  
determine whether the schedule is in the OCCUPIED  
mode or not.  
WSMDEFME  
Water System  
Manager Status  
The water system manager is a CCN module which can  
turn on the chiller and change the chilled water control  
point. This screen indicates the status of this system.  
These maintenance tables are very useful in determining guide vane position, reaction from  
load changes, control point overrides, hot gas bypass reaction, surge prevention, etc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Test  
The Control Test feature can check all of the thermistor temperature sensors, including those  
on the Options modules, pressure transducers, pumps and their associated flow switches, the  
guide vane actuator, and other control outputs, such as hot gas bypass. The tests can help to  
determine whether a switch is defective, or a pump relay is not operating, among other useful  
troubleshooting tests. During pumpdown operations, the pumps are energized to prevent  
freeze-up and the vessel pressures and temperatures are displayed. The lockout feature will  
prevent start-up of the compressor when no refrigerant is present in the machine, or if the  
vessels are isolated. The lockout is then terminated by the operator by using the Terminate  
Lockout function after the pumpdown procedure is reversed and refrigerant is added.  
Table 8, A - N — LID Primary and Secondary Messages and Custom Alarm/Alert  
Messages with Troubleshooting Guides  
Click here for Table 8A — Shutdown with ON/OFF/RESET-OFF  
Click here for Table 8B — Timing OUT or Timed OUT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Click here for Table 8C — In Recycle Shutdown  
Click here for Table 8D — Pre-Start Alerts  
Click here for Table 8E — Normal or Auto.-Restart  
Click here for Table 8F — Start-Up Failures  
Click here for Table 8G — Compressor Jumpstart and Refrigerant Protection  
Click here for Table 8H — Normal Run with Reset, Temperature, or Demand  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Click here for Table 8I — Normal Run Overrides Active (Alerts)  
Click here for Table 8J — Out-of-Range Sensor Failures  
Click here for Table 8K — Machine Protect Limit Faults  
Click here for Table 8L — Machine Alerts  
Click here for Table 8M — Spare Sensor Alert Messages  
Click here for Table 8N — Other Problems/Malfunctions  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Click here for Table 9A — Thermistor Temperature (F) vs Resistance/Voltage Drop  
Click here for Table 9B — Thermistor Temperature (C) vs Resistance/Voltage Drop  
Control Modules  
CAUTION  
CAUTION  
!
Turn controller power off before servicing controls. This ensures safety and pre-  
vents damage to controller.  
The Processor module (PSIO), 8-input (Options) modules, Starter Management Module  
(SMM), and the Local Interface Device (LID) module perform continuous diagnostic evaluations  
of the hardware to determine its condition. Proper operation of all modules is indicated by LEDs  
(light-emitting diodes) located on the side of the LID, and on the top horizontal surface of the  
PSIO, SMM, and 8-input modules.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Red LED  
If the LED is blinking continuously at a 2-second rate, it is indicating proper operation. If it is  
lit continuously it indicates a problem requiring replacement of the module. Off continuously  
indicates that the power should be checked. If the red LED blinks 3 times per second, a  
software error has been discovered and the module must be replaced. If there is no input  
power, check fuses and the circuit breaker. If fuse is good, check for shorted secondary of  
transformer, or if power is present to the module, replace the module.  
Green LEDs  
There are 1 or 2 green LEDs on each type of module. These LEDs indicate communication  
status between different parts of the controller and the network modules as follows:  
LID Module  
Upper LED — Communication with CCN network, if present; blinks when communication  
occurs.  
Lower LED — Communication with PSIO module; must blink every 5 to 8 seconds when the  
LID default screen is displayed.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PSIO Module  
Green LED Closest to Communications Connection — Communication with SMM and 8-  
input module; must blink continuously.  
Other Green LED — Communication with LID; must blink every 3 to 5 seconds.  
8-Input Modules and SMM  
Green LED — Communication with PSIO module; will blink continuously.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes on Module Operation  
1.  
The machine operator monitors and modifies configurations in the microprocessor through  
the 4 softkeys and the LID. Communication with the LID and the PSIO is accomplished  
through the CCN bus. The communication between the PSIO, SMM, and both 8-input  
modules is accomplished through the sensor bus, which is a 3-wire cable.  
On sensor bus terminal strips, Terminal 1 of PSIO module is connected to Terminal 1 of  
each of the other modules. Terminals 2 and 3 are connected in the same manner. See  
Figure 49, Figure 50, Figure 51, Figure 52, and Figure 53. If a Terminal 2 wire is connected  
to Terminal 1, the system does not work.  
2.  
If a green LED is solid on, check communication wiring. If a green LED is off, check the red  
LED operation. If the red LED is normal, check the module address switches (Figure 49,  
Figure 50, Figure 51, Figure 52, and Figure 53). Proper addresses are:  
Address  
Module  
SW1  
SW2  
SMM (Starter Management Module)  
8-input Options Module 1  
3
6
7
2
4
2
8-input Options Module 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If all modules indicate communications failure, check communications plug on the PSIO  
module for proper seating. Also check the wiring (CCN bus — 1:red, 2:wht, 3:blk; Sensor  
bus — 1:red, 2:blk, 3:clr/wht). If a good connection is assured and the condition persists,  
replace the PSIO module.  
If only one 8-input module or SMM indicates communication failure, check the communica-  
tions plug on that module. If a good connection is assured and the condition persists,  
replace the module.  
All system operating intelligence rests in the PSIO module. Some safety shutdown logic  
resides in the SMM in case communications are lost between the 2 modules. The PSIO  
monitors conditions using input ports on the PSIO, the SMM, and the 8-input modules. Out-  
puts are controlled by the PSIO and SMM as well.  
3. Power is supplied to modules within the control panel via 21-vac power sources.  
The transformers are located within the power panel, with the exception of the SMM, which  
operates from a 24-vac power source and has its own 24-vac transformer located within the  
starter.  
Within the power panel, T1 supplies power to the LID, the PSIO, and the 5-vac power sup-  
ply for the transducers. The other 21-vac transformer is T4, which supplies power to both 8-  
input modules (if present). T4 is capable of supplying power to two modules; if additional  
modules are added, another power supply will be required.  
Power is connected to Terminals 1 and 2 of the power input connection on each module.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Processor Module (PSIO) (Figure 51)  
Inputs  
Each input channel has 3 terminals; only 2 of the terminals are used. Application of machine  
determines which terminals are normally used. Always refer to individual unit wiring for terminal  
numbers.  
Outputs  
Output is 20 vdc. There are 3 terminals per output, only 2 of which are used, depending on  
the application. Refer to the unit wiring diagram.  
Click here for Figure 49 — PSIO Module LED Locations  
Click here for Figure 50 — LID Module (Rear View) and LED Locations  
Click here for Figure 51 — Processor (PSIO) Module  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Starter Management Module (SMM) (Figure 52)  
Inputs  
Inputs on strips J2 and J3 are a mix of analog and discrete (on/off) inputs. Application of the  
machine determines which terminals are used. Always refer to the individual unit wiring diagram  
for terminal numbers.  
Outputs  
Outputs are 24 vdc and wired to strip J1. There are 2 terminals used per output.  
Click here for Figure 52 — Starter Management Module (SMM)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Options Modules (8-Input)  
The options modules are optional additions to the PIC, and are used to add temperature  
reset inputs, spare sensor inputs, and demand limit inputs. Each option module contains 8  
inputs, each input meant for a specific duty. See the wiring diagram for exact module wire  
terminations. Inputs for each of the options modules available include the following:  
Options Module 1  
4 to 20 mA Auto. Demand Reset  
4 to 20 mA Auto. Chilled Water Reset  
Common Chilled Water Supply Temperature  
Common Chilled Water Return Temperature  
Remote Temperature Reset Sensor  
Spare Temperature 1  
Spare Temperature 2  
Spare Temperature 3  
Options Module 2  
4 to 20 mA Spare 1  
4 to 20 mA Spare 2  
Spare Temperature 4  
Spare Temperature 5  
Spare Temperature 6  
Spare Temperature 7  
Spare Temperature 8  
Spare Temperature 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Terminal block connections are provided on the options modules. All sensor inputs are field  
wired and installed. Options module 1 can be factory or field-installed. Options module 2 is  
shipped separately and must be field installed. For installation, refer to the unit or field wiring  
diagrams. Be sure to address the module for the proper module number (Figure 53) and to  
configure the chiller for each feature being used.  
Replacing Defective Processor Modules  
The replacement part number is printed in a small label on front of the PSIO module. The  
model and serial numbers are printed on the unit nameplate located on an exterior corner post.  
The proper software is factory-installed by Carrier in the replacement module. When ordering a  
replacement processor module (PSIO), specify complete replacement part number, full unit  
model number, and serial number. This new unit requires reconfiguration to the original  
machine data by the installer. Follow the procedures described in the Set Up Machine Control  
Configuration section.  
Click here for Figure 53 — Options Module  
CAUTION  
CAUTION  
!
Electrical shock can cause personal injury. Disconnect all electrical power  
before servicing.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation of New PSIO Module  
1.  
Verify if the existing PSIO module is defective, by using the procedure described in the  
Notes on Module Operation section, and Control Modules section. Do not select the Attach  
to Network Device table if the LID displays communication failure.  
2.  
Data regarding the PSIO configuration should have been recorded and saved. This data will  
have to be reconfigured into the LID. If this data is not available, follow the procedures  
described in the Set Up Machine Control Configuration section. Record the TOTAL  
COMPRESSOR STARTS and the COMPRESSOR ONTIME from the STATUS01 table on  
the LID.  
If a CCN Building Supervisor or Service Tool is present, the module configuration should  
have already been uploaded into memory; then, when the new module is installed, the con-  
figuration can be downloaded from the computer (if the software version is the same).  
Any communication wires from other machines or CCN modules must be disconnected.  
3.  
4.  
Check that all power to the unit is off. Carefully disconnect all wires from the defective  
module by unplugging the 6 connectors. It is not necessary to remove any of the individual  
wires from the connectors.  
Remove defective PSIO by removing its mounting screw with a long-shaft Phillips  
screwdriver, and removing the module from the control box. Save the screw for later use.  
The green ground wire is held in place with the module mounting screw.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Package the defective module in the carton of the new module for return to Carrier.  
6. Restore control system power (LID will show ‘‘COMMUNICATION FAILURE’’ at bottom of  
screen).  
7. Access the SERVICE menu. Highlight and select ‘‘ATTACH TO NETWORK DEVICE.’’  
Push the ‘‘ATTACH’’ softkey. (The LID will show ‘‘UPLOADING TABLES. PLEASE WAIT,’’  
then show ‘‘COMMUNICATION FAILURE.’’) Press the EXIT softkey.  
8. Turn off control power.  
9. Mount the new module in the unit control box using a long-shaft Phillips screwdriver and the  
screw saved in Step 4 above. Make sure that the green grounding wire is reinstalled along  
with the mounting screw.  
10. Connect the LID communication wires (CCN bus) and the power wires. If CCN wiring has  
been attached to the CCN bus, disconnect the wires. Attach the sensor bus plug and the  
input and output plugs.  
11. Carefully check all wiring connections before restoring power.  
12. Restore control power and verify that the red and green LEDs on the PSIO are functioning  
properly.  
13. The LID should indicate ‘‘AVAILABLE MEMORY’’ and a value. This value should start to  
decrease. (If not, check LID wiring to PSIO, ensure connection to the proper plug.) The  
bottom of the screen will indicate ‘‘UPLOADING TABLES, PLEASE WAIT.’’  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14. After the PSIO tables have been uploaded into the LID, access the STATUS01 screen.  
Move the highlight bar to the ‘‘TOTAL COMPRESSOR STARTS’’ value. Select this value  
and increase the value until it is the same as the value from the old module. Press ENTER  
to save this value.  
15. Move the highlight bar to the ‘‘COMPRESSOR ONTIME’’ value. Select this point and  
increase the value until it matches the old module run hours. Press SELECT to save this  
value.  
16. Change the address of the PSIO in the Controller Identification table back to the previous  
value. Write the address on the PSIO.  
17. Use the configuration sheets to input setpoint, configuration, and schedule information into  
the PSIO. The Time and Date table also must be set. A Building Supervisor can be used to  
download, the old configuration into the PSIO.  
18. Perform a Control Test and verify all tests. If the software version has been updated, a CCN  
download of the configuration will not be allowed. Configure the PSIO by hand, and upload  
the PSIO into the network by using the Attach to Network Device table.  
19. Restore chiller to normal operation, calibrate motor amps.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17/19EX Physical Data and Wiring Schematics  
Table 10, Table 11, Table 12, Table 13, Table 14, Table 15, Table 16, Table 17, Table 18,  
Figure 54, Figure 55, Figure 56, Figure 57, Figure 58, Figure 59, Figure 60, Figure 61, and  
Figure 62 provide additional information regarding compressor fits and clearances, physical and  
electrical data, and wiring schematics for operator convenience during troubleshooting.  
Click here for Figure 54 — Model Number Nomenclature for Compressor Size  
(See Figure 1 also)  
Click here for Table 10 — 17/19EX Heat Exchanger, Economizer/Storage Vessel,  
Piping, and Pumpout Unit Weights  
Click here for Table 11 — Additional Condenser Weights  
Click here for Table 12 — Compressor/Motor/Suction Elbow Weights  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Click here for Table 13 — Additional Cooler Weights  
Click here for Table 14 — Marine Waterbox Cover Weights  
Click here for Table 15 — NIH Waterbox Cover Weights  
Click here for Table 16 — Auxiliary Systems, Electrical Data  
Compressor Fits and Clearances  
Service and repair of Carrier centrifugal compressors should be performed only by fully  
trained and qualified service personnel.The information in this section is included as a reference  
for such personnel only.  
Click here for Figure 55 — Open-Drive Compressor Fits and Clearances  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Click here for Table 17 — Open-Drive Compressor Fits and Clearances  
Click here for Figure 56 — Hermetic Compressor Fits and Clearances  
Click here for Table 18 — Hermetic Compressor Fits and Clearances  
Click here for Figure 57 — Electronic PIC Controls Wiring Schematic — Hermetic  
Machine  
Click here for Figure 58 — Electronic PIC Controls Wiring Schematic — Open-Drive  
Machine  
Click here for Figure 59 — Machine Power Panel, Starter Assembly, and Motor  
Wiring Schematic  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Click here for Figure 60 — Hermetic Drive — Power Panel With Water-Cooled Oil  
Cooler  
Click here for Figure 61 — Hermetic Drive — Power Panel With Motor  
Cooling Solenoid  
Click here for Figure 62 — Open Drive — Power Panel  
Click here for Initial Start-Up Checklist for 17/19EX Centrifugal Liquid Chiller  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1 — Major PIC Components and Panel Locations*  
PIC Component  
Panel Location  
Control Center  
Processor Sensor Input/Output Module  
(PSIO)  
Starter Cabinet  
Control Center  
Control Center  
Control Center  
Control Center  
Starter Management Module (SMM)  
Local Interface Device (LID)  
6-Pack Relay Board  
8-Input Modules (Optional)  
Oil Differential Pressure/Power Supply  
Module  
Power Panel  
Power Panel  
Power Panel  
Power Panel  
Power Panel  
Oil Heater Contactor (1C)  
Oil Pump Contactor (2C)  
Hot Gas Bypass Relay (3C) (Optional)  
Control Transformers (T1-T4)  
Control and Oil Heater Voltage Selector  
(S1)  
See Figure 10  
See Figure 11  
Temperature Sensors  
Pressure Transducers  
* See Figure 7, Figure 8, Figure 9, Figure 10, Figure 11, Figure 12, and Figure 13.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2 — LID Screens  
Notes:  
1.  
NEXT PREVIOUS  
or  
Only 12 lines of information appear on the LID screen at any given time. Press  
highlight a point or to view points below or above the current screen.  
to  
2.  
3.  
The LID may be configured in English or SI units, as required, through the LID configuration screen.  
Data appearing in the Reference Point Names column is used for CCN operations only.  
Example 1 — Status01 Display Screen  
To access this display from the LID default screen:  
1.  
2.  
3.  
MENU  
.
Press  
Press  
Press  
STATUS STATUS01  
(
will be highlighted).  
SELECT  
.
Table 2, Example 1 — Status01 Display Screen  
ReferencePoint  
Name (Alarm  
History)  
Description  
Range  
Units  
Control Mode  
Run Status  
Reset.Off.Local.CCN  
Timeout.Recycle.Startup.  
Ramping.Running.Demand.  
Override.Shutdown.Abnormal.  
Pumpdown  
MODE  
STATUS  
Occupied ?  
Alarm State  
No/Yes  
OCC  
NORMAL/ALARM  
STOP/START  
40-100  
ALM  
*Chiller Start/Stop  
Base Demand Limit  
*Active Demand Limit  
Compressor Motor Load  
Current  
CHIL S S  
DLM  
DEM LIM  
CA L  
%
%
%
%
40-100  
0-999  
0-999  
CA P  
Amps  
AMPS  
0-9999  
CA A  
*Target Guide Vane Pos  
Actual Guide Vane Pos  
Water/Brine: Setpoint  
%
%
0-100  
0-100  
10-120 (–12.2-48.9)  
10-120 (–12.2-48.9)  
GV TRG  
GV ACT  
SP  
DEG F (DEG C)  
DEG F (DEG C)  
*
Control Point  
LCW STPT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2, Example 1 — Status01 Display Screen (Continued)  
ReferencePoint  
Name (Alarm  
History)  
Description  
Range  
Units  
Entering Chilled Water  
Leaving Chilled Water  
Entering Condenser Water  
Leaving Condenser Water  
Evaporator Refrig Temp  
Evaporator Pressure  
Condenser Refrig Temp  
Condenser Pressure  
Discharge Temperature  
Bearing Temperature  
–40-245 (–40-118)  
–40-245 (–40-118)  
–40-245 (–40-118)  
–40-245 (–40-118)  
–40-245 (–40-118)  
–6.7-420 (–46-2896)  
–40-245 (–40-118)  
–6.7-420 (–46-2896)  
–40-245 (–40-118)  
–40-245 (–40-118)  
–40-245 (–40-118)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
PSI (kPa)  
DEG F (DEG C)  
PSI (kPa)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
ECW  
LCW  
ECDW  
LCDW  
ERT  
ERP  
CRT  
CRP  
CMPD  
MTRB  
MTRW  
Motor Winding Temp  
Normal/Alarm  
MTRW  
Motor Winding Hi  
Temp Cutout**  
–40-245 (–40-118)  
–6.7-420 (–46-2896)  
–6.7-420 (–46-2896)  
0-999  
0-9999  
Off/On  
0-65535  
0-8  
0-500000.0  
0-32767  
0-9999  
DEG F (DEG C)  
PSI (kPa)  
PSID (kPad)  
%
OILT  
OILP  
OILPD  
V P  
V A  
REMCON  
c starts  
STARTS  
c hrs  
S HRS  
CKW  
Oil Sump Temperature  
Oil Pressure Transducer  
Oil Pressure  
††  
Line Voltage: Percent  
Actual  
VOLTS  
*Remote Contacts Input  
Total Compressor Starts  
Starts in 12 Hours  
Compressor Ontime  
*Service Ontime  
HOURS  
HOURS  
kW  
*Compressor Motor kW  
Note: All values are variables available for read operation to a CCN. Descriptions shown with (*) support  
write operations for BEST programming language, data-transfer, and overriding.  
Information is applicable to hermetic machines only.  
** Information is applicable to open-drive machines only.  
†† Oil pressure is read directly from a differential pressure module on 17EX machines.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example 2 — Status02 Display Screen  
To access this display from the LID default screen:  
1. Press MENU.  
2. Press STATUS.  
3. Scroll down to highlight STATUS02.  
4. Press SELECT.  
Table 2, Example 2 — Status02 Display Screen  
Point Type  
Description  
Reference Point  
Name (Alarm  
History)  
Units  
Input  
Output  
X
X
OFF/ON  
OFF/ON  
NO/YES  
OFF/ON  
NO/YES  
OFF/ON  
OPEN/CLOSED  
OPEN/CLOSED  
OPEN/CLOSED  
OPEN/CLOSED  
NORMAL/ALARM  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
OFF/ON  
HGBR  
CHWP  
EVFL  
CDP  
CDFL  
CMPR  
1CR AUX  
RUN AUX  
STR FLT  
PRS TRIP  
V1 CYCLE  
OILR  
OILH  
MTRC  
AUXOILR  
TFR  
TRIPR  
Hot Gas Bypass Relay  
*Chilled Water Pump  
Chilled Water Flow  
X
X
X
X
*Condenser Water Pump  
Condenser Water Flow  
Compressor Start Relay  
Compressor Start Contact  
Compressor Run Contact  
Starter Fault Contact  
Pressure Trip Contact  
Single Cycle Dropout  
Oil Pump Relay  
X
X
X
X
X
X
X
X
X
X
X
X
Oil Heater Relay  
Motor Cooling Relay†  
Auxiliary Oil Pump Relay**  
*Tower Fan Relay  
Compr. Shunt Trip Relay  
Alarm Relay  
OFF/ON  
NORMAL/ALARM  
ALARM/NORMAL  
ALM  
SPR PL  
X
Spare Prot Limit Input  
Note: All values are variables available for read operation to a CCN. Descriptions shown with (*) support  
write operations from the LID only.  
† Information is applicable to hermetic machines only.  
** Information is applicable to open-drive machines only.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example 3 — Status03 Display Screen  
To access this display from the LID default screen:  
1. Press MENU.  
2. Press STATUS.  
3. Scroll down to highlight STATUS03.  
4. Press SELECT.  
Table 2, Example 3 — Status03 Display Screen  
Reference Point Name  
(Alarm History)  
Description  
Range  
Units  
OPTIONS BOARD 1  
4-20  
4-20  
mA  
mA  
DEM OPT  
RES OPT  
CHWS  
*Demand Limit 4-20 mA  
*Temp Reset 4-20 mA  
*Common CHWS Sensor  
*Common CHWR Sensor  
*Remote Reset Sensor  
*Temp Sensor — Spare 1  
*Temp Sensor — Spare 2  
*Temp Sensor — Spare 3  
OPTIONS BOARD 2  
–40-245 (–40-118)  
–40-245 (–40-118)  
–40-245 (–40-118)  
–40-245 (–40-118)  
–40-245 (–40-118)  
–40-245 (–40-118)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
CHWR  
R RESET  
SPARE1  
SPARE2  
SPARE3  
4-20  
4-20  
mA  
mA  
SPARE1 M  
SPARE2 M  
SPARE4  
SPARE5  
SPARE6  
SPARE7  
SPARE8  
SPARE9  
*4-20 mA — Spare 1  
*4-20 mA — Spare 2  
–40-245 (–40-118)  
–40-245 (–40-118)  
–40-245 (–40-118)  
–40-245 (–40-118)  
–40-245 (–40-118)  
–40-245 (–40-118)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
*Temp Sensor — Spare 4  
*Temp Sensor — Spare 5  
*Temp Sensor — Spare 6  
*Temp Sensor — Spare 7  
*Temp Sensor — Spare 8  
*Temp Sensor — Spare 9  
Note: All values shall be variables available for read operation to a CCN network. Descriptions shown with (*)  
support write operations for BEST programming language, data-transfer, and overriding.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example 4 — Setpoint Display Screen  
To access this display from the LID default screen:  
1. Press MENU.  
2. Press SETPOINT.  
Table 2, Example 4 — Setpoint Display Screen  
Configurable  
Range  
Reference Point  
Name  
Description  
Units  
Default Value  
40-100  
%
DLM  
100  
Base Demand Limit  
LCW Setpoint  
ECW Setpoint  
20-120 (–6.7-48.9)  
20-120 (–6.7-48.9)  
20-60 (–6.7-15.6)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
lcw sp  
ecw sp  
ice sp  
50.0 (10.0)  
60.0 (15.6)  
40.0 ( 4.4)  
ICE BUILD Setpoint  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example 5 — Configuration (Config) Display Screen  
To access this display from the LID default screen:  
1. Press MENU.  
2. Press SERVICE.  
3. Scroll down to highlight EQUIPMENT CONFIGURATION.  
4. Press SELECT.  
5. Scroll down to highlight CONFIG.  
6. Press SELECT.  
Table 2, Example 5 — Configuration (Config) Display Screen  
Configurable  
Range  
Reference  
Point Name  
Default  
Value  
Description  
Units  
RESET TYPE 1  
–30-30 (–17-17)  
DEG F (DEG C)  
deg 20mA  
10 (6 )  
Degrees Reset at 20 mA  
∆ ∆  
RESET TYPE 2  
–40-245 (–40-118)  
–40-245 (–40-118)  
–30-30 (–17-17)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
res rt1  
res rt2  
res rt  
85 (29)  
65 (18)  
10 (6 )  
∆ ∆  
Remote Temp (No Reset)  
Remote Temp (Full Reset)  
Degrees Reset  
RESET TYPE 3  
0-15 (0-8)  
0-15 (0-8)  
–30-30 (–17-17)  
0-3  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
restd 1  
restd 2  
deg chw  
res sel  
10 (6 )  
∆ ∆  
0 (0 )  
∆ ∆  
CHW Delta T (No Reset)  
CHW Delta T (Full Reset)  
Degrees Reset  
5 (3 )  
∆ ∆  
0
Select/Enable Reset Type  
DISABLE/ENABLE  
40-100  
DISABLE/ENABLE  
DISABLE/ENABLE  
DISABLE/ENABLE  
2-10  
ecw opt  
dem 20ma  
dem sel  
astart  
r contact  
tmp ramp  
kw ramp  
ramp opt  
DISABLE  
40  
DISABLE  
DISABLE  
DISABLE  
3
10  
1
ECW CONTROL OPTION  
Demand Limit At 20 mA  
20mA Demand Limit Option  
Auto Restart Option  
Remote Contacts Option  
Temp Pulldown Deg/Min  
Load Pulldown %/Min  
Select Ramp Type:  
%
5-20  
0/1  
Temp = 0, Load = 1  
0-99  
0-60  
0-120  
ldsgrp  
ldsdelta  
maxldstm  
0
20  
60  
Loadshed Group Number  
Loadshed Demand Delta  
Maximum Loadshed Time  
CCN Occupancy Config:  
Schedule Number  
%
MIN  
3-99  
occpcxxe  
occbrcst  
ibopt  
3
DISABLE/ENABLE  
DISABLE/ENABLE  
DISABLE  
DISABLE  
Broadcast Option  
ICE BUILD Option  
ICE BUILD TERMINATION  
0 =Temp, 1 =Contacts, 2 =Both  
ICE BUILD Recycle Option  
0-2  
ibterm  
ibrecyc  
0
DISABLE/ENABLE  
DISABLE  
Note: = delta degrees.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example 6 — Lead/Lag Configuration Display Screen  
To access this display from the LID default screen:  
1. Press MENU.  
2. Press SERVICE.  
3. Scroll down to highlight EQUIPMENT CONFIGURATION.  
4. Press SELECT.  
5. Scroll down to highlight Lead/Lag.  
6. Press SELECT.  
Table 2, Example 6 — Lead/Lag Configuration Screen  
Configurable  
Range  
Reference  
Point Name  
Default  
Value  
Description  
Units  
LEAD/LAG SELECT  
DISABLE =0, LEAD =1,  
LAG =2, STANDBY =3  
Load Balance Option  
Common Sensor Option  
LAG Percent Capacity  
LAG Address  
LAG START Timer  
LAG STOP Timer  
PRESTART FAULT Timer  
STANDBY Chiller Option  
STANDBY Percent Capacity  
STANDBY Address  
0-3  
leadlag  
0
DISABLE/ENABLE  
DISABLE/ENABLE  
25-75  
1-236  
2-60  
2-60  
0-30  
DISABLE/ENABLE  
25-75  
1-236  
loadbal  
commsens  
lag per  
lag add  
lagstart  
lagstop  
preflt  
stndopt  
stnd per  
stnd add  
DISABLE  
DISABLE  
50  
92  
10  
10  
15  
DISABLE  
%
MIN  
MIN  
MIN  
%
50  
93  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example 7 — Service1 Display Screen  
To access this display from the LID default screen:  
1. Press MENU.  
2. Press SERVICE.  
3. Scroll down to highlight EQUIPMENT SERVICE.  
4. Press SELECT.  
5. Scroll down to highlight SERVICE1.  
6. Press SELECT.  
Table 2, Example 7 — Service1 Display Screen  
Reference  
Point  
Name  
Configurable  
Range  
Description  
Units  
Default Value  
150-200 (66-93)  
90-200 (620-1379)  
2-5 (1-3)  
Water/Brine  
8-40 (–13.3-4)  
125-200 (52-93)  
165-210 (74-99)  
0.5-5  
DEG F (DEG C) mt over  
PSI (kPa)  
cp over  
DEG F (DEG C) ref over  
medium  
DEG F (DEG C) br trip  
DEG F (DEG C) cd alert  
DEG F (DEG C) tb alert  
200 (93)  
125 (862)  
Motor Temp Override*  
Cond Press Override  
Refrig Override Delta T  
Chilled Medium  
Brine Refrig Trippoint  
Compr Discharge Alert  
Bearing Temp Alert  
Water Flow Verify Time  
Oil Press Verify Time  
Water/Brine Deadband  
Recycle Restart Delta T  
Recycle Shutdown Delta†  
Surge Limit/HGBP Option  
Select: Surge = 0, HGBP = 1  
Surge/HGBP Delta T1  
Surge/HGBP Delta P1  
Min. Load Points (T1/P1)  
Surge/HGBP Delta T2  
Surge/HGBP Delta P2  
Full Load Points (T2/P2)  
Surge/HGBP Deadband  
Surge Delta Percent Amps  
Surge Time Period  
3 (1.6 )  
WATER  
33 (1)  
200 (93)  
175 (79)  
5
MIN  
SEC  
wflow t  
oilpr t  
15-300  
15  
0.5-2.0 (0.3-1.1)  
2.0-10.0 (1.1-5.6)  
0.5-4.0 (.27-2.2)  
0/1  
DEG F (DEG C) cw db  
DEG F (DEG C) rcycrdt  
rcycsdt  
1.0 (0.6)  
5 (2.8)  
1.0 (0.6)  
0
srg hgbp  
0.5-15 (0.3-8.3)  
30-170 (207-1172)  
DEG F (DEG C) hgb dt1  
1.5 0.8  
)
(
PSI (kPa)  
hgb dp1  
50 (345)  
0.5-15 (0.3-8.3)  
30-170 (207-1172)  
DEG F (DEG C) hgb dt2  
PSI (kPad)  
hgb dp2  
10 5.6)  
(
85 (586)  
1.3 (0.6-1.6)  
10-50  
1-5  
DEG F (DEG C) hgb dp  
1 (0.6)  
25  
2
%
MIN  
surge a  
surge t  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2, Example 7 — Service1 Display Screen (Continued)  
Reference  
Point  
Name  
Configurable  
Range  
Description  
Units  
Default Value  
0/1  
dem src  
0
Demand Limit Source  
Select: Amps=0, Load=1  
Amps Correction Factor  
Motor Rated Load Amps  
Motor Rated Line Voltage  
Meter Rated Line KW  
Line Frequency  
1-8  
corfact  
a fs  
v fs  
kw fs  
freq  
3
1-9999  
1-9999  
1-9999  
0/1  
AMPS  
VOLTS  
kW  
200  
460  
600  
0
HZ  
Select: 0=60 Hz, 1=50 Hz  
Compr Starter Type  
Condenser Freeze Point  
Soft Stop Amps Threshold  
Stop to Start Timer†  
REDUCE/FULL  
–20-35 (–28.9-1.7)  
40-100  
starter  
REDUCE  
34 (1)  
100  
DEG F (DEG C) cdfreeze  
%
MIN  
softstop  
stopmtr  
3-50  
20  
Note: = delta degrees.  
* Information is applicable to hermetic machines only.  
† Information is applicable to open-drive machines only.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example 8 — Service2 Display Screen  
To access this display from the LID default screen:  
1. Press MENU.  
2. Press SERVICE.  
3. Scroll down to highlight EQUIPMENT SERVICE.  
4. Press SELECT.  
5. Scroll down to highlight SERVICE2.  
6. Press SELECT.  
Table 2, Example 8 — Service2 Display Screen  
Reference  
Point  
Name  
Configurable  
Default  
Value  
Description  
Range  
Units  
OPTIONS BOARD 1  
20 mA POWER CONFIGURATION  
External = 0, Internal = 1  
0, 1  
0, 1  
res 20 ma  
dem 20 ma  
0
0
RESET 20 mA Power Source  
DEMAND 20 mA Power Source  
SPARE ALERT ENABLE  
Disable = 0, 1 = High Alert, 2 = Low Alert,  
3 = High Alarm, 4 = Low Alarm  
Temp = Alert Threshold  
CHWS Temp Enable  
CHWS Temp Alert  
CHWR Temp Enable  
CHWR Temp Alert  
Reset Temp Enable  
Reset Temp Alert  
Spare Temp 1 Enable  
Spare Temp 1 Alert  
Spare Temp 2 Enable  
Spare Temp 2 Alert  
Spare Temp 3 Enable  
Spare Temp 3 Alert  
0-4  
chws en  
chws al  
chwr en  
chwr al  
rres en  
rres al  
spr1 en  
spr1 al  
spr2 en  
spr2 al  
spr3 en  
spr3 al  
0
–40-245 (–40-118) DEG F (DEG C)  
0-4  
–40-245 (–40-118)  
0-4  
–40-245 (–40-118)  
0-4  
–40-245 (–40-118)  
0-4  
245 (118)  
0
245 (118)  
0
245 (118)  
0
245 (118)  
0
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
–40-245 (–40-118)  
0-4  
–40-245 (–40-118)  
245 (118)  
0
245 (118)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2, Example 8 — Service2 Display Screen (Continued)  
Reference  
Point  
Name  
Configurable  
Range  
Default  
Value  
Description  
Units  
OPTIONS BOARD 2  
20 mA POWER CONFIGURATION  
External = 0, Internal = 1  
SPARE 1 20 mA Power Source  
SPARE 2 20 mA Power Source  
SPARE ALERT ENABLE  
Disable = 0, 1 = High Alert, 2 = Low Alert,  
3 = High Alarm, 4 = Low Alarm  
Temp = Alert Threshold  
Spare Temp 4 Enable  
Spare Temp 4 Alert  
Spare Temp 5 Enable  
Spare Temp 5 Alert  
Spare Temp 6 Enable  
Spare Temp 6 Alert  
Spare Temp 7 Enable  
Spare Temp 7 Alert  
Spare Temp 8 Enable  
Spare Temp 8 Alert  
Spare Temp 9 Enable  
Spare Temp 9 Alert  
0, 1  
0, 1  
sp1 20 ma  
sp2 20 ma  
0
0
0-4  
spr4 en  
spr4 al  
spr5 en  
spr5 al  
spr6 en  
spr6 al  
spr7 en  
spr7 al  
spr8 en  
spr8 al  
spr9 en  
spr9 al  
0
–40-245 (–40-118)  
0-4  
–40-245 (–40-118)  
0-4  
–40-245 (–40-118)  
0-4  
–40-245 (–40-118)  
0-4  
–40-245 (–0-118)  
0-4  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
245 (118)  
0
245 (118)  
0
245 (118)  
0
245 (118)  
0
245 (118)  
0
245 (118)  
–40-245 (–40-118)  
Note: This screen provides the means to generate alert messages based on exceeding the ‘‘Temp’’ thresh-  
old for each point listed. If the ‘‘Enable’’ is set to 1, a value above the ‘‘Temp’’ threshold shall generate  
an alert message. If the ‘‘Enable’’ is set to 2, a value below the ‘‘Temp Alert’’ threshold shall generate  
an alert message. If the ‘‘Enable’’ is set to 0, alert generation is disabled. If the “Enable” is set to 3, a  
value above the “Temp” threshold will generate an alarm. If the “Enable” is set to 4, a value below the  
“Temp” threshold will generate an alarm.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example 9 — Service3 Display Screen  
To access this display from the LID default screen:  
1. Press MENU.  
2. Press SERVICE.  
3. Scroll down to highlight EQUIPMENT SERVICE.  
4. Press SELECT.  
5. Scroll down to highlight SERVICE3.  
Table 2, Example 9 — Service3 Display Screen  
Reference  
Point  
Name  
Configurable  
Range  
Description  
Units  
Default Value  
2-10  
2-10  
1-3  
gv inc  
gv de  
gv ecw  
6.5  
6.0  
2.0  
Proportional Inc Band  
Proportional Dec Band  
Proportional ECW Gain  
30-100  
%
gv lim  
50  
Guide Vane Travel Limit  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example 10 — Maintenance (Maint01) Display Screen  
To access this display from the LID default screen:  
1. Press MENU.  
2. Press SERVICE.  
3. Scroll down to highlight ALGORITHM STATUS.  
4. Press SELECT.  
5. Scroll down to highlight MAINT01.  
Table 2, Example 10 — Maintenance (Maint01) Display Screen  
Reference  
Point Name  
Description  
Range/Status  
Units  
CAPACITY CONTROL  
Control Point  
Leaving Chilled Water  
Entering Chilled Water  
Control Point Error  
ECW Delta T  
ECW Reset  
LCW Reset  
Total Error + Resets  
Guide Vane Delta  
10-120 (–12.2-48.9)  
–40-245 (–40-118)  
–40-245 (–40-118)  
–99-99 (–55-55)  
–99-99 (–55-55)  
–99-99 (–55-55)  
–99-99 (–55-55)  
–99-99 (–55-55)  
–2-2  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
%
ctrlpt  
LCW  
ECW  
cperr  
ecwdt  
ecwres  
lcwres  
error  
gvd  
0-100  
0-100  
2-10  
2-10  
%
%
GV TRG  
GV ACT  
gv inc  
gv dec  
gv ecw  
cwdb  
Target Guide Vane Pos  
Actual Guide Vane Pos  
Proportional Inc Band  
Proportional Dec Band  
Proportional ECW Gain  
Water/Brine Deadband  
1-3  
0.5-2 (0.3-1.1)  
DEG F (DEG C)  
Note: Overriding is not supported on this maintenance screen. Active overrides show the associated point in  
alert (*). Only values with capital letter reference point names are variables available for read opera-  
tion.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example 11 — Maintenance (Maint02) Display Screen  
To access this display from the LID default screen:  
1. Press MENU.  
2. Press SERVICE.  
3. Scroll down to highlight CONTROL ALGORITHM STATUS.  
4. Press SELECT.  
5. Scroll down to highlight MAINT02.  
6. Press SELECT.  
Table 2, Example 11 — Maintenance (Maint02) Display Screen  
Reference  
Point Name  
Description  
Range/Status  
Units  
OVERRIDE/ALERT STATUS  
MOTOR WINDING TEMP†  
Override Threshold  
CONDENSER PRESSURE  
Override Threshold  
EVAPORATOR REFRIG TEMP  
Override Threshold  
DISCHARGE TEMPERATURE  
Alert Threshold  
–40-245 (–40-118)  
150-200 (66-93)  
-6.7-420 (-42-2896)  
90-245 (621-1689)  
–40-245 (–40-118)  
2-45 (1-7.2)  
–40-245 (–40-118)  
125-200 (52-93)  
–40-245 (–40-118)  
175-185 (79-85)  
DEG F (DEG C)  
DEG F (DEG C)  
PSI (kPa)  
MTRW  
mt over  
CRP  
cp over  
ERT  
rt over  
CMPD  
cd alert  
MTRB  
tb alert  
PSI (kPa)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
DEG F (DEG C)  
BEARING TEMPERATURE  
Alert Threshold  
Note: Overriding is not supported on this maintenance screen. Active overrides show the associated point in  
alert (*). Only values with capital letter reference point names are variables available for read opera-  
tion.  
† Information is applicable to hermetic machines only.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example 12 — Maintenance (Maint03) Display Screen  
To access this display from the LID default screen:  
1. Press MENU.  
2. Press SERVICE.  
3. Scroll down to highlight CONTROL ALGORITHM STATUS.  
4. Press SELECT.  
5. Scroll down to highlight MAINT03.  
6. Press SELECT.  
Table 2, Example 12 — Maintenance (Maint03) Display Screen  
Description  
Range/Status  
Units  
Reference Point Name  
NO/YES  
SURGE/HGBP ACTIVE?  
0-200 (0-1379)  
0-200 (0-111)  
0-200 (0-111)  
PSI (kPa)  
DEG F (DEG C)  
DEG F (DEG C)  
dp a  
dt a  
dt c  
Active Delta P  
Active Delta T  
Calculated Delta T  
0-12  
spc  
Surge Protection Counts  
Note: Override is not supported on this maintenance screen. Only values with capital letter reference point  
names are variables available for read operation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example 13 — Maintenance (Maint04) Display Screen  
To access this display from the LID default screen:  
1. Press MENU.  
2. Press SERVICE.  
3. Scroll down to highlight CONTROL ALGORITHM STATUS.  
4. Press SELECT.  
5. Scroll down to highlight MAINT04.  
6. Press SELECT.  
Table 2, Example 13 — Maintenance (Maint04) Display Screen  
Reference  
Point  
Description  
Range/Status  
Units  
Name  
DISABLE, LEAD, LAG, STANDBY, INVALID  
DISABLE, LEAD, LAG, STANDBY, CONFIG  
DISABLE/ENABLE  
0-60  
0-60  
0-30  
x.xx  
No/Yes  
No/Yes  
Reset,Off,Local,CCN  
Timeout,Recycle,Startup,Ramping,Running  
Demand,Override,Shutdown,Abnormal,Pumpdown  
leadlag  
llmode  
loadbal  
lagstart  
lagstop  
preflt  
pull dt  
pull sat  
leadctrl  
lagmode  
lagstat  
LEAD/LAG: Configuration  
Current Mode  
Load Balance Option  
LAG Start Time  
MIN  
MIN  
MIN  
LAG Stop Time  
Prestart Fault Time  
Pulldown: Delta T/Min  
Satisfied?  
LEAD CHILLER in Control  
LAG CHILLER: Mode  
Run Status  
DEG ( DEG C)  
Stop,Start,Retain  
No/Yes  
Reset,Off,Local,CCN  
Timeout,Recycle,Startup,Ramping,Running  
Demand,Override,Shutdown,Abnormal,Pumpdown  
lag s s  
lag rec  
stdmode  
Start/Stop  
Recovery Start Request  
STANDBY CHILLER: Mode  
Run Status  
stdstat  
Stop,Start,Retain  
No/Yes  
std s s  
std rec  
Start/Stop  
Recovery Start Request  
Notes:  
1. Only values with capital letter reference point names are variables available for read operation. Forcing is  
not supported on this maintenance screen.  
2. = delta degrees.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 3 — Protective Safety Limits and Control Settings  
Monitored Parameter  
Limit  
Applicable Comments  
–40 to 245 F (–40 to 118.3 C)  
Must be outside range for 2 seconds  
Temperature Sensors Out  
Of Range  
0.08 to 0.98 Voltage Ratio  
Must be outside range for 2 seconds.  
Ratio = Input Voltage ÷ Voltage Refer-  
ence  
Pressure Transducers Out  
Of Range  
>220 F (104.4 C)  
Preset, alert setting configurable  
Compressor Discharge  
Temperature  
>220 F (104.4 C)  
Preset; alert setting configurable  
Preset; alert setting configurable  
Motor Winding Temperature  
Bearing Temperature  
>220 F (104.4 C)  
<33 F (for water chilling) (0.6° C)  
Preset; configure chilled medium for  
water (Service1 table)  
Evaporator Refrigerant  
Temperature (Temp  
converted from Pressure  
Reading)  
<Brine Refrigerant Trippoint (set point Configure chilled medium for brine  
adjustable from 0 to 40 F [–18 to 4 C] (Service1 table). Adjust brine refrigerant  
for brine chilling)  
trippoint for proper cutout  
<4.5 vdc > 5.5 vdc  
Preset (Read voltage at terminals 34  
and 35 on PSIO module)  
Transducer Voltage  
>218 psig ± 7 psig (1503 ± 48 kPa),  
reset at 120 ± 10 (827 ± 69 kPa)  
Preset  
Condenser Pressure – Switch  
– Control  
215 psig (1482 kPa)  
Preset  
Cutout <11 psid (76 kPad) ± 1.5 psid  
(10.3 kPad) Cut-in > 16.5 psid (114  
kPad) ± 4 psid (27.5 kPad)  
Preset, no calibration needed  
Oil Pressure  
– Switch  
– Control  
Cutout < 15 psid (103 kPad)  
Preset  
Alert < 18 psid (124 kPad)  
>110% for one minute  
Line Voltage High  
Low  
Preset, based on transformed line volt-  
age to 24 vac rated-input to the Starter  
Management Module. Also monitored at  
PSIO power input.  
<90% for one minute and 85% for 3  
seconds  
<50% for one cycle  
Single-cycle  
>110% for 30 seconds  
Preset  
Preset  
Preset  
Compressor Motor Load  
(% Compressor Amps)  
<10% with compressor running  
>10% with compressor off  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 3 — Protective Safety Limits and Control Settings (Continued)  
Monitored Parameter  
Limit  
Applicable Comments  
45 seconds  
>
10 seconds  
>
75 seconds  
>
For machines with reduced voltage  
mechanical and solid-state starters  
Starter Acceleration Time  
(Determined by inrush  
current going below 100%  
compressor motor load)  
For machines with full voltage starters  
(Configured on Service1 table)  
Reduced voltage starters only  
Starter Transition  
Energizes condenser pump relay if  
condenser refrigerant temperature or  
condenser entering water tempera-  
ture is below the configured con-  
denser freeze point temperature.  
Deenergizes when the temperature is  
5 F (3 C) above condenser freeze  
point temperature.  
CONDENSER FREEZE POINT config-  
ured in Service01 table with a default  
seting of 34 F (1 C).  
Condenser Freeze  
Protection  
Displacement switch open  
Thrust movement excessive  
Impeller Clearance  
Water from motor cooling is leaking  
Water sensors are installed only on  
open-drive motors that use water cool-  
ing. (Totally enclosed, water-to-air  
cooled [TEWAC] motors)  
Motor Leak Detector*  
Flow Switches (Field Supplied)  
Operate water pumps with machine off. Manually reduce water flow and observe switch for proper cutout.  
Safety shutdown occurs when cutout time exceeds 3 seconds.  
NO ADJUSTMENTS ARE TO BE MADE ON THIS  
SETSCREW! (FACTORY ADJUSTED ONLY)  
Carrier Part No. HK06ZC033  
Carrier Part No. HK06ZC001  
* Applicable to open drive machines only.  
Note: Dimensions in parenthesis are  
in millimeters  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4 — Capacity Overrides  
Second  
Stage  
Setpoint  
Override  
Termination  
First Stage Setpoint  
Override  
Capacity  
Control  
Modify  
View/  
Default Value  
Configurable Range Value  
Value  
on LID  
Screen  
Equip-  
ment  
Service1  
125 psig (862 kPa)  
90 to 200 psig  
(620-1379 kPa)  
Override Set  
Point + 4 psid  
(28 kPad)  
Override  
<
Set Point  
>
High  
Condenser  
Pressure  
Equip-  
ment  
Service1  
200 F (93.3 C)  
150 to 200 F  
(66 to 93 C)  
Override Set  
Point +10° F  
(6° C)  
Override  
<
>
>
High Motor  
Temperature*  
Set Point  
Trippoint +  
>
Override  
T +2° F  
Equip-  
ment  
Service1  
3° F (1.6° C) (Above 2° to 5° F  
<
Trippoint +  
Low  
Trippoint)  
(1° to 3° C)  
Override  
T –1° F  
Refrigerant  
Temperature  
(Refrigerant  
Override  
(0.56° C)  
(1.2° C)  
Delta  
Temperature)  
Equip-  
ment  
Service1  
Min: T1 – 1.5° F  
(0.8° C)  
P1 – 50 psid  
(345 kPad)  
Max: T2 – 10° F  
(5.6° C)  
0.5° to 15° F  
None  
Within Lift  
Limits Plus  
Surge/HGBP  
Deadband  
Setting  
(0.3° to 8.3° C)  
30 to 170 psid  
(207 to 1172 kPad)  
0.5° to 15° F  
(0.3° to 8.3° C)  
30 to 170 psid  
(207 to 1172 kPad)  
High  
Compressor  
LIft (Surge  
Prevention)  
P2 – 85 psid  
(586 kPad)  
Control  
Algorithm  
Maint01  
Automatic  
100%  
0 to 100%  
None  
Release of  
Manual Con-  
trol  
Manual Guide  
Vane Target  
Status01  
40 to 100%  
5% of Set  
2% Lower  
Than Set  
Point  
Motor Load —  
Active  
Demand Limit  
Point  
Legend  
P1 — Minimum Pressure Load  
T1 — Minimum Temperature Load  
T2 — Maximum Temperature Load  
P2 — Maximum Pressure Load  
* Not available on open drive machines.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5A — HFC-134a Pressure — Temperature (F)  
Temperature (F)  
Pressure (psi)  
0
2
4
6
8
6.50  
7.52  
8.60  
9.66  
10.79  
10  
12  
14  
16  
18  
11.96  
13.17  
14.42  
15.72  
17.06  
20  
22  
24  
26  
28  
18.45  
19.88  
21.37  
22.90  
24.48  
30  
32  
34  
36  
38  
26.11  
27.80  
29.53  
31.32  
33.17  
40  
42  
44  
46  
48  
35.08  
37.04  
39.06  
41.14  
43.28  
50  
52  
54  
56  
58  
45.48  
47.74  
50.07  
52.47  
54.93  
60  
62  
64  
66  
68  
57.46  
60.06  
62.73  
65.47  
68.29  
70  
72  
74  
76  
78  
71.18  
74.14  
77.18  
80.30  
83.49  
80  
82  
84  
86  
88  
86.17  
90.13  
93.57  
97.09  
100.70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5A — HFC-134a Pressure — Temperature (F) (Continued)  
Temperature (F)  
Pressure (psi)  
90  
92  
94  
96  
98  
104.40  
108.18  
112.06  
116.02  
120.08  
100  
102  
104  
106  
108  
124.23  
128.47  
132.81  
137.25  
141.79  
110  
112  
114  
116  
118  
146.43  
151.17  
156.01  
160.96  
166.01  
120  
122  
124  
126  
128  
171.17  
176.45  
181.83  
187.32  
192.93  
130  
132  
134  
136  
138  
140  
198.66  
204.50  
210.47  
216.55  
222.76  
229.09  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5B — HFC-134a Pressure — Temperature (C)  
Temperature (C)  
Pressure (kPa)  
-18.0  
-16.7  
-15.6  
-14.4  
-13.3  
44.8  
51.9  
59.3  
66.6  
74.4  
-12.2  
-11.1  
-10.0  
-8.9  
82.5  
90.8  
99.4  
108.0  
118.0  
-7.8  
-6.7  
-5.6  
-4.4  
-3.3  
-2.2  
127.0  
137.0  
147.0  
158.0  
169.0  
-1.1  
0.0  
1.1  
2.2  
3.3  
180.0  
192.0  
204.0  
216.0  
229.0  
4.4  
5.0  
5.6  
6.1  
6.7  
242.0  
248.0  
255.0  
261.0  
269.0  
7.2  
7.8  
8.3  
8.9  
9.4  
276.0  
284.0  
290.0  
298.0  
305.0  
10.0  
11.1  
12.2  
13.3  
14.4  
314.0  
329.0  
345.0  
362.0  
379.0  
15.6  
16.7  
17.8  
18.9  
20.0  
396.0  
414.0  
433.0  
451.0  
471.0  
21.1  
22.2  
23.3  
24.4  
25.6  
491.0  
511.0  
532.0  
554.0  
576.0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5B — HFC-134a Pressure — Temperature (C) (Continued)  
Temperature (C)  
Pressure (kPa)  
26.7  
27.8  
28.9  
30.0  
31.1  
598.0  
621.0  
645.0  
669.0  
694.0  
32.2  
33.3  
34.4  
35.6  
36.7  
720.0  
746.0  
773.0  
800.0  
828.0  
37.8  
38.9  
40.0  
41.1  
42.2  
857.0  
886.0  
916.0  
946.0  
978.0  
43.3  
44.4  
45.6  
46.7  
47.8  
1010.0  
1042.0  
1076.0  
1110.0  
1145.0  
48.9  
50.0  
51.1  
52.2  
53.3  
1180.0  
1217.0  
1254.0  
1292.0  
1330.0  
54.4  
55.6  
56.7  
57.8  
58.9  
60.0  
1370.0  
1410.0  
1451.0  
1493.0  
1536.0  
1580.0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 6 — Recommended Torque  
Bolt size 1/4”  
Grade  
5/16” 3/8”  
1/2” 5/8”  
3/4”  
7/8”  
1”  
1 1/3” 1 1/2”  
SAE GR 5  
3.5  
7
12  
16  
31  
42  
63  
85  
115  
156  
180  
244  
275  
373  
550  
746  
960  
Ft-lbs  
Torque*  
4.7  
9.5  
1302  
N•m  
Bolt size M4  
Grade  
M6  
M8  
M10  
M12  
M10  
M12  
M16  
DIN 8.8  
15  
DIN 12.9  
92  
2
8
35  
47  
65  
88  
45  
61  
225  
305  
Ft-lbs  
N•m  
Torque*  
2.7  
11  
20  
125  
* Torque values based upon dry friction.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 7 — Control Test Menu Functions  
Tests To Be Performed  
1. Automated Tests*  
Devices Tested  
Operates the second through seventh tests  
2. PSIO Thermistors  
Entering chilled water  
Leaving chilled water  
Entering condenser water  
Leaving condenser water  
Discharge temperature  
Bearing temperature  
Motor winding temperature  
Oil sump temperature  
3. Options Thermistors  
Common chilled water supply sensor  
Common chilled water return sensor  
Remote reset sensor  
Temperature sensor — Spare 1  
Spare 2  
Spare 3  
Spare 4  
Spare 5  
Spare 6  
Spare 7  
Spare 8  
Spare 9  
4. Transducers  
Evaporator pressure  
Condenser pressure  
Oil pressure differential  
Oil pump pressure**  
5. Guide Vane Actuator  
6. Pumps  
Open  
Close  
All pumps or individual pumps may be activated:  
Oil pump — Confirm pressure  
Chilled water pump — Confirm flow  
Condenser water pump — Confirm flow  
Auxiliary oil pump — Confirm pressure  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 7 — Control Test Menu Functions (Continued)  
Tests To Be Performed  
7. Discrete Outputs  
Devices Tested  
All outputs or individual outputs may be energized:  
Hot gas bypass relay  
Oil heater relay  
Motor cooling relay**  
Tower fan relay  
Alarm relay  
Shunt trip relay  
When using pumpdown/lockout, observe freeze up precau-  
tions when removing charge:  
8. Pumpdown/Lockout  
Instructs operator as to which valves to close and when  
Starts chilled water and condenser water pumps and con-  
firms flows  
Monitors —  
Evaporator pressure  
Condenser pressure  
Evaporator temperature during pumpout procedures  
Turns pumps off after pumpdown  
Locks out compressor  
9. Terminate Lockout  
Starts pumps and monitors flows  
Instructs operator as to which values to open and when  
Monitors —  
Evaporator pressure  
Condenser pressure  
Evaporator temperature during charging process  
Terminates compressor lockout  
* During any of the tests that are not automated, an out-of-range reading will have an asterisk (*) next to  
the reading and a message will be displayed.  
† On open-drive machines, differential pressure is the only oil pressure displayed.  
** Displayed only on hermetic machines.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND For Table 8, A - N  
1CR AUX — Compressor Start Contact  
OILPD  
OILT  
PIC  
— Oil Pressure  
CA P  
CDFL  
— Compressor Current  
— Condenser Water Flow  
— Oil Sump Temperature  
— Product Integrated Control  
CHIL S S — Chiller Start/Stop  
PRS TRIP — Pressure Trip Contact  
CMPD  
CRP  
— Discharge Temperature  
— Condenser Pressure  
PSIO  
RLA  
— Processor Sensor Input/Output Module  
— Rated Load Amps  
ERT  
— Evaporator Refrigerant Temperature  
— Chilled Water Flow  
RUN AUX — Compressor Run Contact  
EVFL  
GV TRG  
LID  
SMM  
— Starter Management Module  
— Spare Protective Limit Input  
— Starter Fault  
— Target Guide Vane Position  
— Local Interface Device  
SPR PL  
STR FLT  
TXV  
MTRB  
MTRW  
— Bearing Temperature  
— Thermostatic Expansion Valve  
— Line Voltage: Percent  
— Voltage Reference  
— Motor Winding Temperature  
V P  
V REF  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
A. Shutdown with ON/OFF/RESET-OFF  
Primary Message  
Secondary Message  
Probable Cause/Remedy  
CCN or Local to Start  
PIC in OFF mode; press the CCN or local softkey to  
start unit.  
Manually Stopped —  
Press  
To Select CCN or Local  
Compressor Unloading  
Enter the Control Test table and select Terminate Lock-  
out to unlock compressor.  
Terminate Pumpdown  
Mode  
Machine unloading before shutdown due to Soft Stop  
feature.  
Shutdown In Progress  
Compressor Deenergized Machine compressor is being commanded to stop.  
Water pumps are deenergized within one minute.  
Shutdown In Progress  
Ice Build  
Operation Complete  
Machine shutdown from Ice Build operation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
B. Timing Out or Timed Out  
Primary Message  
Secondary Message  
Probable Cause/Remedy  
Unoccupied Mode  
Time schedule for PIC is unoccupied. Machines will  
start only when occupied.  
Ready To Start In XX  
Min  
Remote Contacts Open  
Stop Command In Effect  
Remote contacts have stopped machine. Close con-  
tacts to start.  
Ready To Start In XX  
Min  
Chiller START/STOP on Status01 manually forced to  
stop. Release value to start.  
Ready To Start In XX  
Min  
Recycle Restart Pending Machine in recycle mode.  
Ready To Start In XX  
Min  
Unoccupied Mode  
Time schedule for PIC is UNOCCUPIED. Machine will  
Ready To Start  
start when occupied. Make sure the time and date have  
been set on the Service menu.  
Remote Contacts Open  
Stop Command In Effect  
Remote contacts have stopped machine. Close con-  
tacts to start.  
Ready To Start  
Ready To Start  
Chiller START/STOP on Status01 manually forced to  
stop. Release value to start.  
Remote Contacts Closed Machine timer counting down unit. Ready for start.  
Ready To Start In XX  
Min  
Occupied Mode  
Machine timer counting down unit. Ready for start.  
Ready To Start In XX  
Min  
Remote Contacts Closed Machine timers complete, unit start will commence.  
Ready To Start  
Ready To Start  
Startup Inhibited  
Occupied Mode  
Machine timers complete, unit start will commence.  
CCN loadshed module commanding chiller to stop.  
Loadshed In Effect  
Start Command In Effect Chiller START/STOP on Status01 has been manually  
forced to start. Machine will start regardless of time  
schedule or remote contact status.  
Ready To Start In XX  
Min  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
C. In Recycle Shutdown  
Primary Message  
Secondary Message Probable Cause/Remedy  
Occupied Mode  
Unit in recycle mode, chilled water temperature is not high  
enough to start.  
Recycle Restart  
Pending  
Remote Contact Closed Unit in recycle mode, chilled water temperature is not high  
enough to start.  
Recycle Restart  
Pending  
Start Command In  
Effect  
Chiller START/STOP on Status01 manually forced to start,  
chilled water temperature is not high enough to start.  
Recycle Restart  
Pending  
Ice Build Mode  
Machine in ICE BUILD mode. Chilled Water/Brine Tem-  
perature is satisfied for Ice Build Setpoint temperature.  
Recycle Restart  
Pending  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
These alerts only delay start-up. When alert is corrected, the start-up will continue. No  
D. Pre-Start Alerts:  
reset is necessary.  
Primary  
Message  
Secondary  
Message  
Alarm Message/Primary  
Cause  
Additional Cause/Remedy  
Starts Limit Exceeded  
STARTS EXCESSIVE Com-  
pressor Starts (8 in 12 hours)  
Depress the RESET softkey if addi-  
tional start is required. Reasses  
start-up requirements.  
Prestart Alert  
High Motor Tempera-  
ture  
MTRW [VALUE] exceeded limit Check motor cooling line for proper  
of [LIMIT]*. Check motor tem-  
perature.  
operation. Check for excessive  
starts within a short time span.  
Prestart Alert  
Prestart Alert  
Prestart Alert  
High Bearing Tempera- MTRB [VALUE] exceeded limit  
ture  
Check oil heater for proper opera-  
tion, check for low oil level, partially  
closed oil supply valves, etc. Check  
sensor accuracy.  
of [LIMIT]*. Check thrust bear-  
ing temperature.  
High Discharge Temp  
Low Refrigerant Temp  
CMPD [VALUE] exceeded limit  
of [LIMIT]*. Check discharge  
temperature.  
Check sensor accuracy. Allow dis-  
charge temperature to cool. Check  
for excessive starts.  
ERT [VALUE] exceeded limit of Check transducer accuracy.  
[LIMIT]*. Check refrigerant tem- Check for low chilled water/brine  
Prestart Alert  
Prestart Alert  
perature.  
supply temperature.  
Low Oil Temperature  
Low Line Voltage  
OILT [VALUE] exceeded limit of Check oil heater power, oil heater  
[LIMIT]*. Check oil temperature. relay. Check oil level.  
V P [VALUE] exceeded limit of Check voltage supply. Check volt-  
[LIMIT]*. Check voltage supply. age transformers. Consult power  
utility if voltage is low. Calibrate  
Prestart Alert  
voltage reading on STATUS01  
Table.  
High Line Voltage  
V P [VALUE] exceeded limit of Check voltage supply. Check volt-  
[LIMIT]*. Check voltage supply. age transformers. Consult power  
utility if voltage is low. Calibrate  
Prestart Alert  
Prestart Alert  
voltage reading on STATUS01  
Table.  
High Condenser Pres-  
sure  
CRP [VALUE] exceeded limit of Check for high condenser water  
[LIMIT]*. Check condenser  
water and transducer.  
temperature. Check transducer  
accuracy.  
* [LIMIT] is shown on the LID as temperature, pressure, voltage, etc., set point predefined or selected by  
the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature,  
voltage, etc., at which the control tripped.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
E. Normal or AUTO.-RESTART  
Primary Message  
Startup in Progress  
Startup in Progress  
Secondary Message  
Probable Cause/Remedy  
Occupied Mode  
Machine starting. Time schedule is occupied.  
Remote Contact Closed  
Start Command In Effect  
Machine starting. Remote contacts are closed.  
Machine starting. Chiller START/STOP on Status01  
manually forced to start.  
Startup in Progress  
Occupied Mode  
Machine starting. Time schedule is occupied.  
Machine starting. Remote contacts are closed.  
AutoRestart in Progress  
AutoRestart in Progress  
Remote Contact Closed  
Start Command In Effect  
Machine starting. Chiller START/STOP on Status01  
manually forced to start.  
AutoRestart in Progress  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
This is an alarm condition. A manual reset is required to clear.  
F. Start-Up Failures:  
Primary  
Message  
Secondary  
Message  
Alarm Message/Primary  
Cause  
Additional Cause/Remedy  
Low Oil Pressure OILPD [VALUE] exceeded limit  
Check for closed oil supply valves.  
Failure To  
Start  
of [LIMIT]*. Check oil pump sys- Check oil filter. Check for low oil tem-  
tem.  
perature. Check transducer accuracy.  
Oil Press Sensor OILPD [VALUE] exceeded limit  
Check for excessive refrigerant in oil  
sump. Run oil pump manually for 5 min-  
utes. For hermetic compressors, check  
both oil pressure and cooler pressure.  
For open-drive units, check calibration  
of oil pressure differential amplifier  
modules. Check wiring. Replace trans-  
ducers if necessary.  
Fault  
of [LIMIT]*. Check oil pressure  
sensor.  
Failure To  
Start  
Low Chilled  
Water Flow  
EVFL Evap Flow Fault: Check  
water pump/flow switch.  
Check wiring to flow switch. Check  
through Control Test for proper switch  
operation.  
Failure To  
Start  
Low Condenser  
Water Flow  
CDFL Cond. Flow Fault: Check  
water pump/flow switch.  
Check wiring to flow switch. Check  
through Control Test for proper switch  
operation.  
Failure To  
Start  
Starter Fault  
STR FLT Starter Fault: Check  
starter for Fault Source.  
A starter protective device has faulted.  
Check starter for ground fault, voltage  
trip, temperature trip, etc.  
Failure To  
Start  
Starter Overload STR FLT Starter Overload Trip: Reset overloads, check ICR relay  
Failure To  
Start  
Trip  
Check amps calibration/reset  
overload.  
before restarting machine.  
Line Voltage  
Dropout  
V P Single-Cycle Dropout  
Check voltage supply. Check trans-  
Detected: Check voltage supply. formers for supply. Check with utility if  
voltage supply is erratic. Monitor must  
be installed to confirm consistent,  
Failure To  
Start  
single-cycle dropouts. Check low oil  
pressure switch.  
High Condenser  
Pressure  
High Condenser Pressure  
[LIMIT]:* Check switch 2C aux,  
and water temperature/flow.  
Check for proper design condenser flow  
and temperature. Check condenser  
approach. Check 2C auxiliary contacts  
on oil sump starter. Check high pres-  
sure switch.  
Failure To  
Start  
Excess Accelera- CA P Excess Acceleration:  
Check that guide vanes are closed at  
start-up. Check starter for proper opera-  
tion. Reduce unit pressure if possible.  
Failure To  
Start  
tion Time  
Check guide vane closure at  
start-up.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
This is an alarm condition. A manual reset is required to clear.  
F. Start-Up Failures:  
(Continued)  
Primary  
Message  
Secondary  
Message  
Alarm Message/Primary  
Cause  
Additional Cause/Remedy  
Starter Transi-  
tion Fault  
RUN AUX Starter Transition  
Fault: Check 1CR/1M/Interlock  
mechanism.  
Check starter for proper operation. Run  
contact failed to close.  
Failure To  
Start  
1CR AUX Con-  
tact Fault  
1CR AUX Starter Contact Fault: Check starter for proper operation. Start  
Failure To  
Start  
Check 1CR/1M aux. contacts.  
contact failed to close.  
Motor Amps Not  
Sensed  
CA P Motor Amps Not Sensed:  
Check motor load signal.  
Check for proper motor amps signal to  
SMM. Check wiring from SMM to cur-  
rent transformer. Check main motor cir-  
cuit breaker for trip.  
Failure To  
Start  
Check Refriger-  
ant Type  
Current Refrigerant Properties  
Abnormal — Check Selection of another refrigerant type in Contol Test.  
refrigerant type  
Pressures at transducers indicate  
Failure To  
Start  
Make sure to access the ATTACH TO  
NETWORK DEVICE table after specify-  
ing HFC-134a refrigerant type.  
Low Oil Pressure Low Oil Pressure [LIMIT]:*  
Check oil pressure switch/pump  
and 2C aux.  
The oil pressure differential switch is  
open when the compressor tried to  
START. Check the switch for proper  
operation. Also, check the oil pump  
interlock (2C aux) in the power panel  
and the high condenser pressure  
switch.  
Failure To  
Start  
* [LIMIT] is shown on the LID as temperature, pressure, voltage, etc., set point predefined or selected by  
the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature,  
voltage, etc., at which the control tripped.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
G. Compressor Jumpstart and Refrigerant Protection  
Secondary  
Message  
Alarm Message/Primary  
Cause  
Primary Message  
Additional Cause/Remedy  
Unit Should Be  
Stopped  
CA P Emergency: Compres-  
sor running without control  
authorization.  
Compressor is running with  
more than 10% RLA and control  
is trying to shut it down. Throw  
power off to compressor if  
unable to stop. Determine cause  
before repowering.  
Unauthorized  
Operation  
Evap Press/Temp  
Too Low  
ERT Emergency: Freeze-up  
prevention.  
Determine cause. If pumping  
refrigerant out of machine, stop  
operation and go over pumpout  
procedures.  
Potential Freeze-  
up  
Disconnect Power  
With Starter  
RUN AUX Emergency: DIS-  
CONNECT POWER.  
Starter and run and start con-  
tacts are energized while control  
tried to shut down. Disconnect  
power to starter.  
Failure To Stop  
Loss of Communication with  
Starter: Check machine.  
Check wiring from PSIO to  
SMM. Check SMM module trou-  
bleshooting procedures.  
Loss Of  
Communciation  
Abnormal 1CR or  
RUN AUX  
1CR AUX Starter Contact  
Fault: Check 1CR/1M aux.  
contacts.  
Starter run and start contacts  
energized while machine was  
off. Disconnect power.  
Starter Contact  
Fault  
Cond Press/Temp  
Too Low  
CRT [VALUE] exceeded limit  
of [LIMIT]* Emergency:  
Freeze-up prevention.  
The condenser pressure trans-  
ducer is reading a pressure that  
could freeze the water in the  
condenser tubes. Check for con-  
denser refrigerant leaks, bad  
transducers, or transferred  
Potential Freeze-  
up  
refrigerant. Place the unit in  
Pumpdown mode to eliminate  
ALARM if vessel is evacuated.  
* [LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected  
by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature,  
voltage, etc., at which the control tripped.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
H. Normal Run with Reset, Temperature, Or Demand  
Primary Message  
Secondary Message  
Probable Cause/Remedy  
4-20MA Signal  
Running — Reset Active  
Running — Reset Active  
Running — Reset Active  
Running — Temp Control  
Running — Temp Control  
Remote Sensor Control  
CHW Temp Difference  
Leaving Chilled Water  
Entering Chilled Water  
Reset program active based upon Config  
table setup.  
Default method of temperature control.  
ECW control activated on Config table.  
Temperature Ramp Loading Ramp loading in effect. Use Service1 table to  
modify.  
Running — Temp Control  
By Demand Ramp Loading  
Ramp loading in effect. Use Service1 table to  
modify.  
Running — Demand Limited  
By Local Demand Setpoint  
By 4-20MA Signal  
By CCN Signal  
Demand limit setpoint is < actual demand.  
Running — Demand Limited  
Running — Demand Limited  
Running — Demand Limited  
Running — Demand Limited  
Demand limit is active based on Config table  
setup.  
By Loadshed/Redline  
Hot Gas Bypass  
Hot Gas Bypass is energized. See surge pre-  
vention in the Control section.  
Running — Temp Control  
Running — Demand Limited  
Running — Temp Control  
By Local Signal  
Ice Build Mode  
Active demand limit manually overridden or  
Status01 table.  
Machine is running under Ice Build tempera-  
ture control.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
I. Normal Run Overrides Active (Alerts)  
Alarm Message/Primary  
Cause  
Additional Cause/  
Remedy  
Primary Message  
Secondary Message  
High Condenser Pres-  
sure  
CRP [VALUE] exceeded limit of  
[LIMIT]*. Condenser pressure  
override.  
Run Capacity  
Limited  
High Motor Temperature  
Low Evap Refrig Temp  
High Compressor Lift  
MTRW [VALUE] exceeded limit of  
[LIMIT]*. Motor temperature over-  
ride.  
Run Capacity  
Limited  
See Capacity Over-  
rides, Table 4. Correct  
operating condition,  
modify setpoint, or  
release override.  
ERT [VALUE] exceeded limit of  
[LIMIT]*. Check refrigerant charge  
level.  
Run Capacity  
Limited  
Surge Prevention Override; lift too  
high for compressor.  
Run Capacity  
Limited  
Manual Guide Vane Tar-  
get  
GV TRG Run Capacity Limited:  
Manual Guide Vane Target.  
Run Capacity  
Limited  
* [LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected  
by the operator as an override, alert, or alarm contition. [VALUE] is the actual temperature, pressure,  
voltage, etc., at which the control tripped.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
J. Out-of-Range Sensor Failures  
Alarm Message/Primary  
Cause  
Additional Cause/  
Remedy  
Primary Message  
Secondary Message  
Leaving CHW Tempera-  
ture  
Sensor Fault: Check leaving CHW  
sensor.  
Sensor Fault  
Sensor Fault  
Sensor Fault  
Sensor Fault  
Sensor Fault  
Sensor Fault  
Sensor Fault  
Sensor Fault  
Sensor Fault  
Entering CHW Tempera-  
ture  
Sensor Fault: Check entering  
CHW sensor.  
Condenser Pressure  
Evaporator Pressure  
Bearing Temperature  
Motor Winding Temp  
Discharge Temperature  
Oil Sump Temperature  
Oil Pressure Transducer  
Sensor Fault: Check condenser  
pressure transducer.  
Sensor Fault: Check evaporator  
pressure transducer.  
See  
sensor test procedure  
and check sensors for  
proper operation and  
wiring.  
Sensor Fault: Check bearing tem-  
perature sensor.  
Sensor Fault: Check motor tem-  
perature sensor.  
Sensor Fault: Check discharge  
temperature sensor.  
Sensor Fault: Check oil sump tem-  
perature sensor.  
Sensor Fault: Check oil pressure  
transducer.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
K. Machine Protect Limit Faults  
WARNING  
WARNING  
!
Excessive numbers of the same fault can lead to severe machine damage. Seek service expertise.  
Primary  
Message  
Secondary  
Message  
Alarm Message/  
Primary Cause  
Additional Cause/Remedy  
High Discharge  
Temp  
CMPD [VALUE] exceeded  
limit of [LIMIT]*. Check dis- ately. Check sensor for accuracy; check  
Check discharge temperature immedi-  
charge temperature.  
for proper condenser flow and tempera-  
ture; check oil reservoir temperature.  
Check condenser for fouled tubes or air in  
machine. Check for proper guide vane  
actuator operation.  
Protective  
Limit  
Low Refrigerant  
Temp  
ERT [VALUE] exceeded  
limit of [LIMIT]*. Check  
evap pump and flow switch. temperatures. Check for proper guide  
vane actuator operation.  
Check for proper amount of refrigerant  
charge; check for proper water flow and  
Protective  
Limit  
High Motor Temper-  
ature  
MTRW [VALUE] exceeded Check motor temperature immediately.  
limit of [LIMIT]*. Check  
Check sensor for accuracy. Check for  
Protective  
Limit  
motor cooling and solenoid. proper condenser flow and temperature.  
Check motor cooling system for restric-  
tions. Check motor cooling solenoid for  
proper operation. Check refrigerant filter.  
High Bearing Tem-  
perature  
MTRB [VALUE] exceeded  
limit of [LIMIT]*. Check oil  
cooling control.  
Check for throttled oil supply isolation  
valves. Valves should be wide open.  
Check oil cooler thermal expansion valve.  
Check sensor accuracy. Check journal  
and thrust bearings. Check refrigerant fil-  
ter. Check for excessive oil sump level.  
Protective  
Limit  
Low Oil Pressure  
OILPD [VALUE] exceeded  
limit of [LIMIT]*. Check oil  
pump and transducer.  
Check power to oil pump and oil level.  
Check for dirty filters or oil foaming at  
start-up. Check for thermal overload cut-  
out. Reduce ramp load rate if foaming  
noted.  
Protective  
Limit  
Note:  
This is not related to pressure  
switch problems.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
K. Machine Protect Limit Faults (Continued)  
WARNING  
WARNING  
!
Excessive numbers of the same fault can lead to severe machine damage. Seek service expertise.  
Primary  
Message  
Secondary  
Message  
Alarm Message/  
Primary Cause  
Additional Cause/Remedy  
No Motor Current  
CA P Loss of Motor Cur-  
rent: Check sensor.  
Check wiring: Check torque setting on  
solid-state starter. Check for main circuit  
breaker trip. Check power supply to PSIO  
module.  
Protective  
Limit  
Power Loss  
V P Power Loss: Check  
voltage supply.  
Protective  
Limit  
Check 24-vac input on the SMM (termi-  
nals 23 and 24). Check transformers to  
SMM. Check power to PSIO module.  
Check distribution bus. Consult power  
company.  
Low Line Voltage  
V P [VALUE] exceeded  
limit of [LIMIT]*. Check volt-  
age supply.  
Protective  
Limit  
High Line Voltage  
V P [VALUE] exceeded  
limit of [LIMIT]*. Check volt-  
age supply.  
Protective  
Limit  
Low Chilled Water  
Flow  
EVFL Flow Fault: Check  
evap pump/flow switch.  
Protective  
Limit  
Perform pumps Control Test and verify  
proper switch operation. Check all water  
valves and pump operation.  
Low Condenser  
Water Flow  
CDFL Flow Fault: Check  
cond pump/flow switch.  
Protective  
Limit  
High Condenser  
Pressure  
High Cond Pressure  
[OPEN]: Check switch, 2C  
aux., and water temp/flow.  
Check the high-presure switch. Check for  
proper condenser pressures and con-  
denser waterflow. Check for fouled tubes.  
Check the 2C aux. contact and the oil  
pressure switch in the power panel. This  
alarm is not caused by the transducer.  
Protective  
Limit  
High Condenser  
Pressure  
High Cond Pressure  
[VALUE]: Check switch,  
water flow, and transducer. checked for accuracy. This alarm is not  
caused by the high pressure switch.  
Check water flow in condenser. Check for  
fouled tubes. Transducer should be  
Protective  
Limit  
1CR AUX Contact  
Fault  
CR AUX Starter Contact  
Fault: Check 1CR/1M aux  
contacts.  
1CR auxiliary contact opened while  
machine was running. Check starter for  
proper operation.  
Protective  
Limit  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
K. Machine Protect Limit Faults (Continued)  
WARNING  
WARNING  
!
Excessive numbers of the same fault can lead to severe machine damage. Seek service expertise.  
Primary  
Message  
Secondary  
Message  
Alarm Message/  
Primary Cause  
Additional Cause/Remedy  
Run AUX Contact  
Fault  
RUN AUX Starter Contact Run auxiliary contact opened while  
Protective  
Limit  
Fault: Check 1CR/1M aux  
contacts.  
machine was running. Check starter for  
proper operation.  
CCN Override Stop  
CHIL S S CCN Override  
Stop while in LOCAL run  
mode.  
CCN has signaled machine to stop. Reset  
and restart when ready. If the signal was  
sent by the LID, release the Stop signal  
on STATUS01 screen.  
Protective  
Limit  
Spare Safety Device SRP PL Spare Safety  
Fault: Check contacts.  
Spare safety input has tripped or factory-  
installed jumper not present.  
Protective  
Limit  
Excessive Motor  
Amps  
CA P [VALUE] exceeded  
limit of [LIMIT]*. High  
Amps; Check guide vane  
drive.  
Check motor current for proper calibra-  
tion. Check guide vane drive and actuator  
for proper operation.  
Protective  
Limit  
Excessive Compr  
Surge  
Compressor Surge: Check  
condenser water temp and Check configuration of surge protection.  
flow.  
Check condenser flow and temperatures.  
Protective  
Limit  
Starter Fault  
STR FLT Starter Fault:  
Check starter for fault  
source.  
Check starter for possible ground fault,  
reverse rotation, voltage trip, etc.  
Protective  
Limit  
Starter Overload Trip STR FLT Starter Overload Reset overloads and reset alarm. Check  
Protective  
Limit  
Trip: Check amps calibra-  
tion/reset overload.  
motor current calibration or overload cali-  
bration (do not field-calibrate overloads).  
Transducer Voltage  
Fault  
V REF [VALUE] exceeded Check transformer power (5 vdc) supply  
Protective  
Limit  
limit of [LIMIT]*. Check  
to transducers. Power must be 4.5 to  
5.5 vdc.  
transducer power supply.  
Low Oil Pressure  
Low Oil Pressure [OPEN]:  
Check oil pressure switch/  
pump and 2C aux.  
Check the oil pressure switch for proper  
operation. Check oil pump for proper  
pressure. Check for excessive refrigerant  
in oil system.  
Protective  
Limit  
* [LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected  
by the operator as an override, alert, or alarm contition. [VALUE] is the actual temperature, pressure,  
voltage, etc., at which the control tripped.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
L. Machine Alerts  
Primary  
Message  
Secondary  
Message  
Alarm Message/  
Primary Cause  
Additional Cause/Remedy  
High Amps at Shut-  
down  
High Amps at Recycle:  
Check guide vane  
drive.  
Check that guide vanes are closing.  
Check motor amps correction calibration is  
correct. Check actuator for proper opera-  
tion.  
Recycle Alert  
Leaving Cond Water  
Temp  
Sensor Fault: Check  
leaving condenser  
water sensor.  
Sensor Fault  
Alert  
Check sensor. See sensor test procedure.  
Entering Cond Water  
Temp  
Sensor Fault: Check  
entering condenser  
water sensor.  
Sensor Fault  
Alert  
Check Oil Filter  
Power Loss  
Low Oil Pessure Alert:  
Check oil.  
Check oil filter. Check for improper oil level  
or temperature.  
Low Oil  
Pressure Alert  
V P Power Loss:  
Check voltage supply.  
AutoRestart  
Pending  
Low Line Voltage  
V P [VALUE] exceeded  
limit of [LIMIT]*. Check  
voltage supply.  
AutoRestart  
Pending  
Check power supply if there are excessive  
compressor starts occurring.  
High Line Voltage  
V P [VALUE] exceeded  
limit of [LIMIT]*. Check  
voltage supply.  
AutoRestart  
Pending  
High Discharge Temp  
CMPD [VALUE]  
Discharge temperature exceeded the alert  
threshold. Check entering condenser  
water temperature.  
exceeded limit of  
[LIMIT]*. Check dis-  
charge temperature.  
Sensor Alert  
Sensor Alert  
High Bearing Temper- MTRB [VALUE]  
Thrust bearing temperature exceeded the  
alert threshold. Check for closed valves,  
improper oil level or temperatures.  
ature  
exceeded limit of  
[LIMIT]*. Check thrust  
bearing temperature.  
Pump Relay Energized CRP High Condenser  
Pressure [LIMIT]*.  
Check ambient conditions. Check con-  
denser pressure for accuracy.  
Condenser  
Pump energized to  
reduce pressure.  
Pressure Alert  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
L. Machine Alerts (Continued)  
Primary  
Message  
Secondary  
Message  
Alarm Message/  
Primary Cause  
Additional Cause/Remedy  
Excessive Recycle  
Starts  
Excessive recycle  
starts.  
The machine load is too small to keep the  
machine on line and there have been  
more than 5 restarts in 4 hours. Increase  
machine load, adjust hot gas bypass,  
increase RECYCLE RESTART DELTA T.  
Recycle Alert  
* [LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected  
by the operator as an override, alert, or alarm contition. [VALUE] is the actual temperature, pressure,  
voltage, etc., at which the control tripped.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
M. Spare Sensor Alert Messages  
Secondary  
Message  
Additional Cause/  
Remedy  
Primary Message  
Alarm Message/Primary Cause  
Common CHWS Sen- Sensor Fault: Check common CHWS  
sor sensor.  
Spare Sensor  
Alert  
Common CHWR Sen- Sensor Fault: Check common CHWR  
sor sensor.  
Spare Sensor  
Alert  
Remote Reset Sensor Sensor Fault: Check remote reset  
temperature sensor.  
Spare Sensor  
Alert  
Temp Sensor —  
Spare 1  
Sensor Fault: Check temperature sen-  
sor — Spare 1.  
Spare Sensor  
Alert  
Temp Sensor —  
Spare 2  
Sensor Fault: Check temperature sen-  
sor — Spare 2.  
Spare Sensor  
Alert  
Check alert tempera-  
ture set points on  
Equipment Service,  
SERVICE2 LID  
table.  
Check sensor for  
accuracy if reading is  
not accurate.  
Temp Sensor —  
Spare 3  
Sensor Fault: Check temperature sen-  
sor — Spare 3.  
Spare Sensor  
Alert  
Temp Sensor —  
Spare 4  
Sensor Fault: Check temperature sen-  
sor — Spare 4.  
Spare Sensor  
Alert  
Temp Sensor —  
Spare 5  
Sensor Fault: Check temperature sen-  
sor — Spare 5.  
Spare Sensor  
Alert  
Temp Sensor —  
Spare 6  
Sensor Fault: Check temperature sen-  
sor — Spare 6.  
Spare Sensor  
Alert  
Temp Sensor —  
Spare 7  
Sensor Fault: Check temperature sen-  
sor — Spare 7.  
Spare Sensor  
Alert  
Temp Sensor —  
Spare 8  
Sensor Fault: Check temperature sen-  
sor — Spare 8.  
Spare Sensor  
Alert  
Temp Sensor —  
Spare 9  
Sensor Fault: Check temperature sen-  
sor — Spare 9.  
Spare Sensor  
Alert  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
N. Other Problems/Malfunctions  
Description  
Remedy  
Chilled water set point set too high. Access set point on LID and verify.  
Capacity override or excessive cooling load (machine at design capacity). Check LID  
status messages. Check for outside air infiltration into conditioned space.  
Condenser temperature too high. Check for proper flow, examine cooling tower opera-  
tion, check for air or water leaks, check for fouled tubes.  
Chilled Water/Brine  
Temperature Too  
High  
Refrigerant level low. Check for leaks, add refrigerant, and trim charge.  
Liquid bypass in waterbox. Examine division plates and gaskets for leaks.  
Guide vanes fail to open. Use Control Test to check operation.  
(Machine Running)  
Chilled water control point too high. Access control algorithm status and check chilled  
water control operation.  
Guide vanes fail to open fully. Be sure that the guide vane target is released. Check  
guide vane linkage. Check limit switch in actuator. Check that sensor is in the proper ter-  
minals.  
Chilled water set point set too low. Access set point on LID and verify.  
Chilled Water  
Temperature Too  
Low  
Chilled water control point too low. Access control algorithm status and check chilled  
water control for proper resets.  
High discharge temperature keeps guide vanes open.  
(Machine Running)  
Guide vanes fail to close. Be sure that guide vane target is released. Check chilled water  
sensor accuracy. Check guide vane linkage. Check actuator operation.  
Deadband too narrow. Configure LID for a larger deadband.  
Proportional bands too narrow. Either INC or DEC proportional bands should be  
increased.  
Loose guide vane drive. Adjust chain drive.  
Defective vane actuator. Check through Control Test.  
Defective temperature sensor. Check sensor accuracy.  
Chilled Water  
Temperature  
Fluctuates. Vanes  
Hunt  
Check for proper oil level (not enough oil).  
Low Oil Sump  
Temperature While  
Running (Less than  
100 F [38 C])  
Check for proper communications wiring on PSIO module. Check that the COMM1 com-  
munications wires from the LID are terminated to the COMM1 PSIO connection. Check  
for ground or short on CCN system wiring.  
At Power Up, Default  
Screen Does Not  
Appear, “Tables  
Loading” Message  
Continually Appears  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages  
with Troubleshooting Guides  
N. Other Problems/Malfunctions (Continued)  
Description  
Remedy  
Check that PSIO communication plugs are connected correctly. Check SMM communi-  
cation plug. Check for proper SMM power supply. See Control Modules section.  
SMM  
Communications  
Failure  
Check for proper oil level (too much oil). On hermetic EX compressors, check that TXV  
valve is operating properly. On hermetic or open-drive FA compressors, check water  
supply to oil cooler.  
High Oil  
Temperature While  
Running  
Incrase contrast potentiometer. See Figure 50. Check red LED on LID for proper opera-  
tion, (power supply). If LED is blinking, but green LED’s are not, replace LID module,  
(memory failure). Check light bulb if backlit model.  
Blank LID Screen  
(Minimal Contrast  
Visible)  
LID is not properly addressed to the PSIO. Make sure that “Attach to Network Device,”  
“Local Device” is set to read the PSIO address. Check LED’s on PSIO. Is red LED oper-  
ating properly? Are green LED’s blinking? See control module troubleshooting section.  
‘‘Communications  
Failure’’ Highlighted  
Message At Bottom  
of LID Screen  
Press the “Stop” pushbutton. The PIC must be in the OFF mode for the Control Test to  
operate. Clear all alarms. Check line voltage percent on Status01 screen. The percent  
must be within 90% to 110%. Check voltage input to SMM, calibrate starter voltage  
potentiometer for accuracy.  
Control Test Disabled  
Low pressure alarm is active. Put machine into pumpdown mode or equalize pressure.  
Check guide vane actuator wiring.  
Vanes Will Not Open  
in Control Test  
Check oil pump voltage supply. Cooler vessel pressure under vacuum. Pressurize ves-  
sel. Check temperature overload cutout switch.  
Oil Pump Does Not  
Run  
This is normal operation when an alarm is present. The screen freezes the moment the  
alarm is activated to aid in troubleshooting. The Status01 screen provides current infor-  
mation.  
LID Default Screen  
Does Not Update  
The STOP button wiring connector on the LID module is not properly connected or the  
machine is in soft stop mode and the guide vanes are closing.  
Machine Does Not  
Stop When the STOP  
Button is Pressed  
Light bulb burned out. Replace as needed.  
LID Screen Dark  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9A — Thermistor Temperature (F) vs Resistance/Voltage Drop  
Voltage  
Drop  
(V)  
Voltage Resistance Temperature Voltage Resistance  
Temperature  
(F)  
Resistance Temperature  
Drop  
(V)  
(Ohms)  
(F)  
Drop  
(V)  
(Ohms)  
(Ohms)  
(F)  
-25.0  
-24.0  
-23.0  
-22.0  
-21.0  
-20.0  
-19.0  
-18.0  
-17.0  
-16.0  
-15.0  
-14.0  
-13.0  
-12.0  
-11.0  
-10.0  
-9.0  
-8.0  
-7.0  
-6.0  
-5.0  
-4.0  
-3.0  
-2.0  
-1.0  
0.0  
25.0  
26.0  
27.0  
28.0  
29.0  
30.0  
31.0  
32.0  
33.0  
34.0  
35.0  
36.0  
37.0  
38.0  
39.0  
40.0  
41.0  
42.0  
43.0  
44.0  
45.0  
46.0  
47.0  
48.0  
49.0  
50.0  
51.0  
52.0  
53.0  
54.0  
55.0  
56.0  
57.0  
58.0  
59.0  
60.0  
61.0  
62.0  
63.0  
64.0  
65.0  
66.0  
67.0  
68.0  
69.0  
70.0  
71.0  
72.0  
73.0  
74.0  
75  
76  
4.821  
4.818  
4.814  
4.806  
4.800  
4.793  
4.786  
4.779  
4.772  
4.764  
4.757  
4.749  
4.740  
4.734  
4.724  
4.715  
4.705  
4.696  
4.688  
4.676  
4.666  
4.657  
4.648  
4.636  
4.624  
4.613  
4.602  
4.592  
4.579  
4.567  
4.554  
4.540  
4.527  
4.514  
4.501  
4.487  
4.472  
4.457  
4.442  
4.427  
4.413  
4.397  
4.381  
4.366  
4.348  
4.330  
4.313  
4.295  
4.278  
4.258  
98010  
94707  
91522  
88449  
85486  
82627  
79871  
77212  
74648  
72175  
69790  
67490  
65272  
63133  
61070  
59081  
57162  
55311  
53526  
51804  
50143  
48541  
46996  
45505  
44066  
42679  
41339  
40047  
38800  
37596  
36435  
35313  
34231  
33185  
32176  
31202  
30260  
29351  
28473  
27624  
26804  
26011  
25245  
24505  
23789  
23096  
22427  
21779  
21153  
20547  
4.241  
4.223  
4.202  
4.184  
4.165  
4.145  
4.125  
4.103  
4.082  
4.059  
4.037  
4.017  
3.994  
3.968  
3.948  
3.927  
3.902  
3.878  
3.854  
3.828  
3.805  
3.781  
3.757  
3.729  
3.705  
3.679  
3.653  
3.627  
3.600  
3.575  
3.547  
3.520  
3.493  
3.464  
3.437  
3.409  
3.382  
3.353  
3.323  
3.295  
3.267  
3.238  
3.210  
3.181  
3.152  
3.123  
3.093  
3.064  
3.034  
3.005  
19960  
19393  
18843  
18311  
17796  
17297  
16814  
16346  
15892  
15453  
15027  
14614  
14214  
13826  
13449  
13084  
12730  
12387  
12053  
11730  
11416  
11112  
10816  
10529  
10250  
9979  
2.977  
2.947  
2.917  
2.884  
2.857  
2.827  
2.797  
2.766  
2.738  
2.708  
2.679  
2.650  
2.622  
2.593  
2.563  
2.533  
2.505  
2.476  
2.447  
2.417  
2.388  
2.360  
2.332  
2.305  
2.277  
2.251  
2.217  
2.189  
2.162  
2.136  
2.107  
2.080  
2.053  
2.028  
2.001  
1.973  
1.946  
1.919  
1.897  
1.870  
1.846  
1.822  
1.792  
1.771  
1.748  
1.724  
1.702  
1.676  
1.653  
1.630  
5229  
5101  
4976  
4855  
4737  
4622  
4511  
4403  
4298  
4196  
4096  
4000  
3906  
3814  
3726  
3640  
3556  
3474  
3395  
3318  
3243  
3170  
3099  
3031  
2964  
2898  
2835  
2773  
2713  
2655  
2597  
2542  
2488  
2436  
2385  
2335  
2286  
2239  
2192  
2147  
2103  
2060  
2018  
1977  
1937  
1898  
1860  
1822  
1786  
1750  
77  
78  
79  
80  
81  
82  
83  
84  
85  
86  
87  
88  
89  
90  
91  
92  
93  
94  
95  
96  
97  
98  
99  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
123  
124  
1.0  
9717  
2.0  
9461  
3.0  
9213  
4.0  
8973  
5.0  
8739  
6.0  
8511  
7.0  
8291  
8.0  
8076  
9.0  
7868  
10.0  
11.0  
12.0  
13.0  
14.0  
15.0  
16.0  
17.0  
18.0  
19.0  
20.0  
21.0  
22.0  
23.0  
24.0  
7665  
7468  
7277  
7091  
6911  
6735  
6564  
6399  
6238  
6081  
5929  
5781  
5637  
5497  
5361  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9A — Thermistor Temperature (F) vs Resistance/Voltage Drop (Continued)  
Voltage  
Drop  
(V)  
Voltage Resistance Temperature Voltage Resistance  
Temperature  
(F)  
Resistance Temperature  
Drop  
(V)  
(Ohms)  
(F)  
Drop  
(V)  
(Ohms)  
(Ohms)  
(F)  
125  
126  
127  
128  
129  
130  
131  
132  
133  
134  
135  
136  
137  
138  
139  
140  
141  
142  
143  
144  
145  
146  
147  
148  
149  
150  
151  
152  
153  
154  
155  
156  
157  
158  
159  
160  
161  
162  
163  
164  
165  
166  
1.607  
1.585  
1.562  
1.538  
1.517  
1.496  
1.474  
1.453  
1.431  
1.408  
1.389  
1.369  
1.348  
1.327  
1.308  
1.291  
1.289  
1.269  
1.250  
1.230  
1.211  
1.192  
1.173  
1.155  
1.136  
1.118  
1.100  
1.082  
1.064  
1.047  
1.029  
1.012  
0.995  
0.978  
0.962  
0.945  
0.929  
0.914  
0.898  
0.883  
0.868  
0.853  
1715  
1680  
1647  
1614  
1582  
1550  
1519  
1489  
1459  
1430  
1401  
1373  
1345  
1318  
1291  
1265  
1240  
1214  
1190  
1165  
1141  
1118  
1095  
1072  
1050  
1029  
1007  
986  
167  
168  
169  
170  
171  
172  
173  
174  
175  
176  
177  
178  
179  
180  
181  
182  
183  
184  
185  
186  
187  
188  
189  
190  
191  
192  
193  
194  
195  
196  
197  
198  
199  
200  
201  
202  
203  
204  
205  
206  
207  
208  
0.838  
0.824  
0.810  
0.797  
0.783  
0.770  
0.758  
0.745  
0.734  
0.722  
0.710  
0.700  
0.689  
0.678  
0.668  
0.659  
0.649  
0.640  
0.632  
0.623  
0.615  
0.607  
0.600  
0.592  
0.585  
0.579  
0.572  
0.566  
0.560  
0.554  
0.548  
0.542  
0.537  
0.531  
0.526  
0.520  
0.515  
0.510  
0.505  
0.499  
0.494  
0.488  
719  
705  
690  
677  
663  
650  
638  
626  
614  
602  
591  
581  
570  
561  
551  
542  
533  
524  
516  
508  
501  
494  
487  
480  
473  
467  
461  
456  
450  
445  
439  
434  
429  
424  
419  
415  
410  
405  
401  
396  
391  
386  
209  
210  
211  
212  
213  
214  
215  
216  
217  
218  
219  
220  
221  
222  
223  
224  
225  
0.483  
0.477  
0.471  
0.465  
0.459  
0.453  
0.446  
0.439  
0.432  
0.425  
0.417  
0.409  
0.401  
0.393  
0.384  
0.375  
0.366  
382  
377  
372  
367  
361  
356  
350  
344  
338  
332  
325  
318  
311  
304  
297  
289  
282  
965  
945  
925  
906  
887  
868  
850  
832  
815  
798  
782  
765  
750  
734  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9B — Thermistor Temperature (C) vs Resistance/Voltage Drop  
Voltage  
Temperature (C) Drop (V)  
Resistance  
(Ohms)  
Voltage  
Drop (V)  
Resistance  
(Ohms)  
Temperature (C)  
-40  
-39  
-38  
-37  
-36  
-35  
-34  
-33  
-32  
-31  
-30  
-29  
-28  
-27  
-26  
-25  
-24  
-23  
-22  
-21  
-20  
-19  
-18  
-17  
-16  
-15  
-14  
-13  
-12  
-11  
-10  
-9  
6
7
4.896  
4.889  
4.882  
4.874  
4.866  
4.857  
4.848  
4.838  
4.828  
4.817  
4.806  
4.794  
4.782  
4.769  
4.755  
4.740  
4.725  
4.710  
4.693  
4.676  
4.657  
4.639  
4.619  
4.598  
4.577  
4.554  
4.531  
4.507  
4.482  
4.456  
4.428  
4.400  
4.371  
4.341  
4.310  
4.278  
4.245  
4.211  
4.176  
4.140  
4.103  
4.065  
4.026  
3.986  
3.945  
3.903  
168 230  
157 440  
147 410  
138 090  
129 410  
121 330  
113 810  
106 880  
100 260  
94 165  
88 480  
83 170  
78 125  
73 580  
69 250  
65 205  
61 420  
57 875  
54 555  
51 450  
48 536  
45 807  
43 247  
40 845  
38 592  
38 476  
34 489  
32 621  
30 866  
29 216  
27 633  
26 202  
24 827  
23 532  
22 313  
21 163  
20 079  
19 058  
18 094  
17 184  
16 325  
15 515  
14 749  
14 026  
13 342  
12 696  
3.860  
3.816  
3.771  
3.726  
3.680  
3.633  
3.585  
3.537  
3.487  
3.438  
3.387  
3.337  
3.285  
3.234  
3.181  
3.129  
3.076  
3.023  
2.970  
2.917  
2.864  
2.810  
2.757  
2.704  
2.651  
2.598  
2.545  
2.493  
2.441  
2.389  
2.337  
2.286  
2.236  
2.186  
2.137  
2.087  
2.039  
1.991  
1.944  
1.898  
1.852  
1.807  
1.763  
1.719  
1.677  
1.635  
12 085  
11 506  
10 959  
10 441  
9 949  
9 485  
9 044  
8 627  
8 231  
7 855  
7 499  
7 161  
6 840  
6 536  
6 246  
5 971  
5 710  
5 461  
5 225  
5 000  
4 786  
4 583  
4 389  
4 204  
4 028  
3 861  
3 701  
3 549  
3 404  
3 266  
3 134  
3 008  
2 888  
2 773  
2 663  
2 559  
2 459  
2 363  
2 272  
2 184  
2 101  
2 021  
1 944  
1 871  
1 801  
1 734  
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
-8  
-7  
-6  
-5  
-4  
-3  
-2  
-1  
0
1
2
3
4
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9B — Thermistor Temperature (C) vs Resistance/Voltage Drop (Continued)  
Voltage  
Temperature (C) Drop (V)  
Resistance  
(Ohms)  
Voltage  
Drop (V)  
Resistance  
(Ohms)  
Temperature (C)  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
1.594  
1.553  
1.513  
1.474  
1.436  
1.399  
1.363  
1.327  
1.291  
1.258  
1.225  
1.192  
1.160  
1.129  
1.099  
1.069  
1.040  
1.012  
0.984  
0.949  
0.920  
0.892  
0.865  
0.838  
0.813  
0.789  
0.765  
0.743  
0.722  
0.702  
0.683  
0.665  
1 670  
1 609  
1 550  
1 493  
1 439  
1 387  
1 337  
1 290  
1 244  
1 200  
1 158  
1 118  
1 079  
1 041  
1 006  
971  
938  
906  
876  
836  
805  
775  
747  
719  
84  
85  
86  
87  
88  
89  
90  
91  
92  
93  
94  
95  
96  
97  
98  
99  
100  
101  
102  
103  
104  
105  
106  
107  
0.648  
0.632  
0.617  
0.603  
0.590  
0.577  
0.566  
0.555  
0.545  
0.535  
0.525  
0.515  
0.506  
0.496  
0.486  
0.476  
0.466  
0.454  
0.442  
0.429  
0.416  
0.401  
0.386  
0.370  
531  
516  
502  
489  
477  
466  
456  
446  
436  
427  
419  
410  
402  
393  
385  
376  
367  
357  
346  
335  
324  
312  
299  
285  
693  
669  
645  
623  
602  
583  
564  
547  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 10 — 17/19EX Heat Exchanger, Economizer/Storage Vessel, Piping, and Pumpout Unit Weights*  
(Page 1 of 2)  
Economizer/  
Storage  
Vessel  
Economizer Miscellaneous Pumpout  
Cooler Total Weight  
Cooler Charge  
Refrigerant  
Piping  
Unit  
Cooler  
Size†  
Dry**  
lb  
Operating††  
lb kg  
Refrigerant  
Water  
lb  
lb  
kg  
lb  
kg  
lb  
kg  
lb  
kg  
kg  
lb  
kg  
kg  
41  
42  
43  
44  
45  
46  
47  
48  
21,674 9 831 26,120 11 848 2,005  
22,019 9 988 26,736 12 127 2,142  
22,364 10 144 27,322 12 393 2,249  
23,841 10 814 29,836 13 533 2,710  
25,032 11 354 30,790 13 966 2,752  
25,529 11 580 31,658 14 360 2,937  
26,025 11 805 32,496 14 740 3,093  
28,153 12 770 36,053 16 353 3,727  
909  
2,441  
2,575  
2,709  
3,285  
3,006  
3,192  
3,378  
4,173  
1 107  
1 168  
1 229  
1 490  
1 363  
1 448  
1 532  
1 893  
972  
7,169 3 525 610  
277  
1,095  
1,149  
497  
1 020  
1 229  
1 248  
1 332  
1 403  
1 691  
210 95  
7,900 3 583 844  
383  
521  
* If a machine configuration other than 2-pass, 150 psig (1034 kPa), NIH waterbox configuration is used, refer to the Additional Cooler  
Weights or Additional Condenser Weights tables, Table 11 and Table 13 to obtain the additional dry and water weights that must be  
added to the values shown in this table.  
† Cooler and condenser weights shown are based upon 2-pass, nozzle-in-head (NIH) waterboxes with 150 psig (1034 kPa) covers.  
Includes components attached to cooler, but does not include suction/discharge, elbow, or other interconnecting piping.  
** Dry weight includes all components attached to economizer: Covers, float valves, brackets, control center (31 lb [14 kg]), and power  
panel (20 lb [9 kg]). Dry weight does not include compressor weight, motor weight, or pumpdown condensing unit weight. The pumpdown  
condensing unit weight is 210 lb (95 kg). For compressor and motor weights, refer to Table 12.  
†† Operating weight includes dry weight, refrigerant weight, and water weight.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 10 — 17/19EX Heat Exchanger, Economizer/Storage Vessel, Piping, and  
Pumpout Unit Weights* (Continued)  
Condenser Total Weight  
Condenser Charge  
Refrigerant  
Condenser  
Size†  
Dry**  
lb  
Operating††  
Water  
lb  
kg  
lb  
kg  
lb  
1,085  
kg  
kg  
41  
42  
43  
45  
46  
47  
51  
52  
53  
55  
56  
57  
13,768  
14,118  
14,468  
16,676  
17,172  
17,669  
17,188  
17,848  
18,400  
20,725  
21,663  
22,446  
6 245 16,999  
6 404 17,498  
6 563 17,978  
7 564 20,800  
7 789 21,489  
8 015 22,178  
7 796 20,993  
8 096 21,923  
8 346 22,682  
9 401 25,598  
9 826 26,896  
10 181 27,980  
7 711  
7 937  
8 155  
9 435  
9 747  
492  
498  
495  
637  
639  
641  
498  
504  
501  
644  
646  
648  
2,146  
2,282  
2,419  
2,720  
2,908  
3,096  
2,707  
2,964  
3,178  
3,453  
3,808  
4,105  
973  
1,098  
1,091  
1,404  
1,409  
1,413  
1,098  
1,111  
1,104  
1,420  
1,425  
1,429  
1 035  
1 097  
1 234  
1 319  
1 404  
1 228  
1 344  
1 442  
1 566  
1 727  
1 862  
10 060  
9 522  
9 944  
10 288  
11 611  
12 199  
12 691  
* If a machine configuration other than 2-pass, 150 psig (1034 kPa), NIH waterbox configuration is used,  
refer to the Additional Cooler Weights or Additional Condenser Weights tables, Table 11 and Table 13 to  
obtain the additional dry and water weights that must be added to the values shown in this table.  
† Cooler and condenser weights shown are based upon 2-pass, nozzle-in-head (NIH) waterboxes with 150  
psig (1034 kPa) covers. Includes components attached to cooler, but does not include suction/discharge,  
elbow, or other interconnecting piping.  
** Dry weight includes all components attached to economizer: Covers, float valves, brackets, control  
center (31 lb [14 kg]), and power panel (20 lb [9 kg]). Dry weight does not include compressor weight,  
motor weight, or pumpdown condensing unit weight. The pumpdown condensing unit weight is 210 lb (95  
kg). For compressor and motor weights, refer to Table 12.  
†† Operating weight includes dry weight, refrigerant weight, and water weight.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 11 — Additional Condenser Weights*  
Additional  
Water  
Weight  
Design  
Maximum  
Additional  
Dry Weight  
Number  
of  
Passes  
HeatExchanger Waterbox  
Component  
Size  
Type  
psig  
150  
300  
300  
150  
150  
300  
300  
150  
300  
300  
150  
300  
kPa  
lb  
kg  
lb  
kg  
NIH  
1, 3  
1, 3  
2
1034  
2068  
2068  
1034  
1034  
2068  
2068  
1034  
2068  
2068  
1034  
2068  
344  
156  
-
-
-
-
NIH  
1652  
1132  
1692  
674  
749  
513  
767  
306  
-
-
NIH  
41 – 43  
45 – 47  
Marine  
Marine  
Marine  
Marine  
NIH  
1, 3  
2
3 400 1 542  
1 700 771  
1, 3  
2
2651  
1630  
1 202 3 400 1 542  
Condenser  
739  
1 700  
771  
1
-
-
1588  
1591  
25  
NIH  
1
720  
721  
11  
-
-
51 – 53  
55 – 57  
NIH  
2
-
-
Marine  
Marine  
2
1 700  
1 700  
771  
771  
2
1225  
555  
NIH — Nozzle-In-Head  
† Subtract 228 lb (103 kg) from the rigging weight shown in Table 10.  
* When using a machine configuration other than 2-pass, NIH waterboxes with 150 psig (1034 kPa)  
covers, add the weights listed in this table to the appropriate weights in Table 10 to obtain the correct  
condenser weight.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 12 — Compressor/Motor/Suction Elbow Weights  
(English)  
Compressor/Motor/Suction Elbow  
17 Series, All Compressor Sizes*  
Weight (lb)  
14,650  
8,853  
6,352  
9,950  
19 Series, 51-89 Compressor Sizes†  
19 Series, 421-469 Compressor Sizes**  
19 Series, 531-599 Compressor Sizes††  
*
Based on 4160 v, FD motor.  
Based on 6900 v, DQ motor.  
** Based on 6900 v, DP motor.  
†† Based on 6900 v, EE motor.  
(SI)  
Compressor/Motor/Suction Elbow  
17 Series, All Compressor Sizes*  
19 Series, 51-89 Compressor Sizes†  
19 Series, 421-469 Compressor Sizes**  
19 Series, 531-599 Compressor Sizes††  
Weight (kg)  
6 645  
4 081  
2 927  
4 638  
*
Based on 3300 v, FD motor.  
Based on 6300 v, DQ motor.  
** Based on 6300 v, DP motor.  
†† Based on 6300 v, EE motor.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 13 — Additional Cooler Weights*  
Design  
Maximum  
Water Pressure  
Additional  
Dry Weight  
Additional  
Water Weight  
Number  
of  
Waterbox  
Type  
Component  
Passes  
psig  
150  
300  
300  
150  
150  
300  
300  
kPa  
lb  
kg  
lb  
kg  
NIH  
1, 3  
1, 3  
2
1034  
2068  
2068  
1034  
1034  
2068  
2068  
515  
234  
-
-
-
-
-
-
NIH  
2941  
2085  
2100  
792  
1334  
946  
NIH  
Marine  
Marine  
Marine  
Marine  
1, 3  
2
953 5102  
359 2551  
1744 5102  
1150 2551  
2314  
1157  
2314  
1157  
Condenser  
1, 3  
2
3844  
2536  
NIH — Nozzle-In-Head  
* When using a machine configuration other than 2-pass, NIH waterboxes with 150 psig (1038 kPa)  
covers, add the weights listed in this table to the appropriate weights in Table 10 to obtain the correct  
cooler weight.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 14 — Marine Waterbox Cover Weights*  
Design Maximum  
Water Pressure  
Cooler  
Condenser  
Heat Exchanger Size  
psi  
kPa  
lb  
kg  
lb  
kg  
150  
300  
150  
300  
1034  
2068  
1034  
2068  
2236  
3060  
1015  
1389  
1275  
1660  
1643  
2243  
579  
754  
746  
1018  
41 – 48  
51 – 57  
* Heat exchangers with marine waterboxes have heavier dry and operating weights than heat exchangers  
with nozzle-in-head waterboxes.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 15 — NIH Waterbox Cover Weights*  
Design Maximum  
Water Pressure  
Cooler  
Condenser  
Heat Exchanger  
Size  
Passes  
psi  
150  
300  
150  
300  
150  
300  
150  
300  
150  
300  
150  
300  
kPa  
lb  
kg  
1361  
1918  
1355  
1901  
1378  
1927  
lb  
kg  
1
1034  
2068  
1034  
2068  
1034  
2068  
1034  
2068  
1034  
2068  
1034  
2068  
2997  
4225  
2984  
4188  
3035  
4244  
1735  
2510  
1885  
2590  
1777  
2539  
2032  
2940  
2649  
3640  
788  
1140  
856  
1176  
807  
1153  
923  
1335  
1203  
1653  
2
3
1
41 – 48  
2
3
51 – 57  
NIH — Nozzle-in-Head  
* The 150 psig (1034 kPa) waterbox cover weights are included in the dry weight shown in Table 10.  
† Two different waterbox covers are present on 2-pass machines. The weight shown in this table  
represents the weight of the waterbox cover that contains the nozzles. A blank waterbox cover is also  
present on 2-pass units. The weight of the blank waterbox cover is identical to the weight of the same  
size marine waterbox cover. Refer to Table 14.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 16 — Auxiliary Systems, Electrical Data  
Power Source  
Item  
Supply V-PH-HZ  
FLA  
LRA  
Control Module and  
Actuator  
115-1-60  
115-1-50  
3.50  
1
Oil Sump Heater  
115-1-60  
115-1-50  
8.70  
Oil Pump  
200/240-3-60  
380/480-3-60  
507/619-3-60  
4.32  
2.15  
2.13  
24.5  
12.2  
25.0  
2
220/240-3-50  
346/440-3-50  
4.83  
2.59  
28.0  
12.2  
Pumpout Compressor  
200/208-3-60  
220/240-3-60  
440/480-3-60  
550/600-3-60  
10.9  
9.50  
4.70  
3.80  
63.5  
57.5  
28.8  
23.0  
3 (Optional)  
380/415-3-50  
4.70  
28.8  
Legend  
FLA — Full Load Amps  
LRA — Locked Rotor Amps  
Notes:  
1. The oil pump is powered through a field wiring terminal into the power panel.  
2. Power to the controls and oil heater via the power panel must be on circuits that can provide continuous  
service when the compressor starter is disconnected.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 17 — Open-Drive Compressor Fits and Clearances  
Clearance  
17FA4  
Min  
17FA5  
Min  
Type of  
Measure  
Item  
Description  
Max  
in.  
Max  
in.  
in.  
mm  
mm.  
in.  
mm  
mm  
1st stage impeller to  
diaphragm  
Axial  
Axial  
1
2
See Tabulation  
2nd stage impeller  
to discharge wall  
1st stage labyrinth  
Interstage labyrinth  
2nd stage labyrinth  
.016  
.012  
.008  
.4060  
.3050  
.2030  
.2030  
.020  
.016  
.012  
.012  
.5080 .016  
.4060 .012  
.3050 .008  
.3050 .008  
.4060  
.3050  
.2030  
.2030  
.020  
.016  
.012  
.012  
.5080  
.4060  
.3050  
.3050  
Diametral  
Diametral  
Diametral  
Diametral  
3
4
5
Balancing piston lab- .008  
yrinth  
6
Impeller shaft jour-  
nal bearing  
.0020  
.0510  
.0035  
.0889 .0030  
.0762  
.0045  
.1143  
Diametral  
7
8
9
Thrust-end float  
.010  
.002  
.2540  
.0510  
.015  
.004  
.381  
.010  
.2540  
.0510  
.015  
.004  
.381  
Axial  
Counterthrust bear-  
ing seal ring  
.1020 .002  
.1020  
Diametral  
Gear bearing to gear .0040  
Gear bearing to gear .010  
.1016  
.2540  
.0127  
.0055  
.0185  
.0025  
.1397 .0050  
.4699 .010  
.0635 .0005  
.1270  
.2540  
.0127  
.0065  
.0185  
.0025  
.1651  
.4699  
.0635  
Diametral  
Axial  
10  
10a  
Gear bearing to  
bearing housing  
.0005  
Diametral  
11  
12  
13  
Pinion bearing to pin- .0020  
ion  
.0510  
.0254  
.1520  
.0254  
.0035  
.003  
.010  
.005  
.0889 .0040  
.0762 .0005  
.2540 .006  
.1270 .001  
.1016  
.0127  
.1520  
.0254  
.0055  
.0025  
.010  
.1397  
.0635  
.2540  
.1270  
Diametral  
Diametral  
Diametral  
Diametral  
Pinion bearing to  
bearing housing  
.001  
.006  
.001  
Transmission laby-  
rinth  
14  
15  
Shaft end labyrinth  
.005  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 17 — Open-Drive Compressor Fits and Clearances (Continued)  
Clearance  
17FA4  
Min  
17FA5  
Min  
Type of  
Measure  
Item  
Description  
Max  
Max  
in.  
mm  
in.  
mm.  
in.  
mm  
in.  
mm  
Drive-end journal  
bearing  
.003  
.0762  
.005  
.1270 .0035  
.0889  
.0055  
.1397  
Diametral  
Diametral  
Axial  
16  
17  
18  
Windage baffle to  
shaft  
.083  
2.108  
.104  
2.642 .079  
2.007  
.100  
2.540  
Inner carbon ring  
travel  
.06 MIN Each Direction  
.06 MIN Each Direction  
See Figure 55 for item callouts.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 17 — Open-Drive Compressor Fits and Clearances (Continued)  
Tabulation — Impeller Clearances (Open-Drive Compressors)  
Dinension*  
Impeller Diameter  
Compressor  
Size  
Diam  
Code  
Shroud  
Item 1  
in.  
Item 2  
in.  
in.  
mm  
304.8  
mm  
21.26  
mm  
16.21  
3
1
3
5
7
9
1
3
5
7
9
1
3
5
7
9
1
3
5
7
9
12.00  
12.38  
12.75  
13.25  
13.75  
12.00  
12.38  
12.75  
13.25  
13.75  
12.00  
12.38  
12.75  
13.25  
13.75  
12.00  
12.38  
12.75  
13.25  
13.75  
.837  
.638  
.609  
.579  
.541  
.541  
.760  
.726  
.688  
.639  
.632  
.895  
.852  
.809  
.750  
.731  
.972  
.928  
.880  
.817  
.796  
314.5  
323.8  
336.6  
349.2  
304.8  
314.5  
323.8  
336.6  
349.2  
304.8  
314.5  
323.8  
336.6  
349.2  
304.8  
314.5  
323.8  
336.6  
349.2  
.797  
20.24  
19.23  
18.21  
17.53  
24.82  
23.80  
22.78  
23.62  
20.57  
29.90  
28.88  
27.36  
25.83  
24.64  
32.94  
31.42  
29.90  
27.86  
26.67  
15.47  
14.71  
13.74  
13.74  
19.30  
18.44  
17.48  
16.23  
16.05  
25.02  
21.64  
20.55  
19.05  
18.57  
24.69  
23.57  
22.35  
20.75  
20.22  
.757  
.717  
.690  
4
5
6
.977  
.937  
.897  
.837  
.810  
17FA5  
1.177  
1.137  
1.077  
1.017  
.970  
1.297  
1.237  
1.177  
1.097  
1.050  
* Measured with shaft in thrust position (towards suction end); tolerance = ± .005 in. (± .127 mm).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 18 — Hermetic Compressor Fits and Clearances  
Clearance†  
Type of  
Measure  
Item* Description  
in.  
mm  
Minimum Maximum Minimum Maximum  
1st Stage Impeller to Diaphragm  
Axial  
Axial  
1
2
See Tabulation  
2nd Stage Impeller to Discharge  
Wall  
1st Stage Labyrinth  
.0160  
.0120  
.0080  
.0080  
.0030  
.0100  
.0020  
.0050  
.0100  
.0005  
.0040  
.0200  
.0160  
.0120  
.0120  
.0045  
.0150  
.0040  
.0065  
.0185  
.0025  
.0055  
.0025  
.0100  
.0080  
.0054  
.0020  
.4060  
.3050  
.2030  
.2030  
.0762  
.2540  
.0510  
.1270  
.2540  
.0127  
.1016  
.1270  
.1520  
.1270  
.1016  
.0127  
.5080  
.4060  
.3050  
.3050  
.1143  
.3810  
.1020  
.1651  
.4699  
.0635  
.1397  
.0635  
.2540  
.0635  
.1372  
.0508  
Diametral  
Diametral  
Diametral  
Diametral  
Diametral  
Axial  
3
4
Interstage Labyrinth  
2nd Stage Labyrinth  
5
Balancing Piston Labyrinth  
Impeller Shaft Journal Bearing  
Thrust-end Float  
6
7
8
Counterthrust Bearing Seal Ring  
Gear Bearing to Gear  
Diametral  
Diametral  
Axial  
9
10  
11  
12  
13  
14  
15  
16  
17  
Gear Bearing to Gear  
Gear Bearing to Bearing Housing  
Pinion Bearing to Pinion  
Diametral  
Diametral  
Diametral  
Diametral  
Diametral  
Diametral  
Diametral  
Pinion Bearing to Bearing Housing .0005  
Transmission Labyrinth  
Motor-End Labyrinth  
.0060  
.0050  
.0040  
.0005  
Motor-End Bearing to Shaft  
Motor-End Bearing to Bearing  
Housing  
18  
*
See Figure 56 for item callouts.  
Clearances represent factory tolerances for new components.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 18 — Hermetic Compressor Fits and Clearances (Continued)  
Tabulation — Impeller Clearances (Hermetic Compressors)  
Dimension*  
Impeller  
Diameter  
19EX  
Shroud  
Code  
FA Shroud Impeller  
Code Code  
Item 1  
in.  
Item 2  
in.  
in.  
mm  
mm  
mm  
1
12.00  
12.38  
12.75  
13.25  
13.75  
304.8  
314.5  
323.8  
336.6  
349.2  
0.837  
0.797  
0.757  
0.717  
0.690  
21.26  
20.24  
19.23  
18.21  
17.53  
0.638  
0.609  
0.579  
0.541  
0.541  
16.21  
15.47  
14.71  
13.74  
13.74  
3
5
7
9
5
6
7
8
3
1
3
5
7
9
12.00  
12.38  
12.75  
13.25  
13.75  
304.8  
314.5  
323.8  
336.6  
349.2  
0.977  
0.937  
0.897  
0.837  
0.810  
24.82  
23.80  
22.78  
23.62  
20.57  
0.760  
0.726  
0.688  
0.639  
0.632  
19.30  
18.44  
17.48  
16.23  
16.05  
4
5
6
1
3
5
7
9
12.00  
12.38  
12.75  
13.25  
13.75  
304.8  
314.5  
323.8  
336.6  
349.2  
1.177  
1.137  
1.077  
1.017  
0.970  
29.90  
28.88  
27.36  
25.83  
24.64  
0.895  
0.852  
0.809  
0.750  
0.731  
25.02  
21.64  
20.55  
19.05  
18.57  
1
3
5
7
9
12.00  
12.38  
12.75  
13.25  
13.75  
304.8  
314.5  
323.8  
336.6  
349.2  
1.297  
1.237  
1.177  
1.007  
1.050  
32.94  
31.42  
29.90  
27.86  
26.67  
0.972  
0.928  
0.880  
0.817  
0.796  
24.69  
23.57  
22.35  
20.75  
20.22  
349.2  
342.9  
1.341  
1.638  
34.06  
41.61  
.876  
22.25  
26.80  
13.75  
8
9
13.50**  
1.055  
*
Measured with shaft in thrust position (towards suction end); tolerance = ± .005 in. (± .127 mm).  
First-stage diameter.  
** Second-stage diameter.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 1 — 17/19EX Identification  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 2 — Typical 17EX Installation  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 3 — Typical 19EX Installation  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 4 — Refrigerant, Motor Cooling, and Oil Cooling Cycles  
Download from Www.Somanuals.com. All Manuals Search And Download.  
v
Figure 5 — Hermetic Compressor Lubrication System (EX Compressor Shown)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 6 — Open-Drive (17 Series) Lubrication Cycle  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Machine Rear; Compressor Side View  
Figure 7 — 17EX Controls and Sensor Locations  
(Figure 7 continued on next page)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Compressor End View  
Figure 7 — 17EX Controls and Sensor Locations  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(Figure 7 continued on next page)  
Machine Front View  
Figure 7 — 17EX Controls and Sensor Locations  
(Figure 7 continued on next page)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Motor End View  
Figure 7 — 17EX Controls and Sensor Locations  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(Figure 7 continued on next page)  
Figure 7 — 17EX Controls and Sensor Locations  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Machine Rear; Compressor Side View  
Figure 8 — 19EX Controls and Sensor Locations  
(Figure 8 continued on next page)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Compressor End View  
Figure 8 — 19EX Controls and Sensor Locations  
(Figure 8 continued on next page)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Machine Rear View  
Figure 8 — 19EX Controls and Sensor Locations  
(Figure 8 continued on next page)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Motor End View  
Figure 8 — 19EX Controls and Sensor Locations  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(Figure 8 continued on next page)  
Figure 8 — 19EX Controls and Sensor Locations  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 9 — Control Center (Front View); Shown with Options Module  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 10 — Control Sensors (Temperature)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 11 — Control Sensors (Pressure Transducer, Typical)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 12 — Power Panel without Options  
(Open-Drive Machine Shown)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 13 — Power Panel with Options (Hermetic Machine Shown)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 14 — LID Default Screen  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 15 — LID Service Screen  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 16 — 17/19EX Menu Structure  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 17 — 17/19EX Service Menu Structure  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 18 — Example of Point Status Screen  
(Status01)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 19 — Example of Time Schedule Operation Screen  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 20 — Example of Set Point Screen  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 21 — 17/19EX Hot Gas Bypass/Surge Prevention  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 22 — 17/19EX with Default Metric Settings  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 23 — Example of Attach to Network Device Screen  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 24 — Example of Holiday Period Screen  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 25 — Control Sequence  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 26 — Typical Wet-Bulb Type Vacuum Indicator  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 27 — Shipping Bolt on Open Drive Motor  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 28 — 17/19EX Leak Test Procedures  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 29 — Dehydration Cold Trap  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 30 — Correct Motor Rotation  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 31 — Refrigeration Log  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 32 — Pumpout Arrangement and Valve Number Locations  
(12-ft Vessel Shown)  
(Figure 32 continued on next page)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 32 — Pumpout Arrangement and Valve Number Locations  
(12-ft Vessel Shown) (Continued)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 33 — Pumpout Unit Wiring Schematic (19EX Shown)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 34 — Optional Pumpout Compressor  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 35 — Electronic Vane Actuator Linkage  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 36 — Compressor Contact Seal (Open-Drive Machines)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 37 — Checking Preliminary Alignment  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 38 — Measuring Angular Misalignment in Elevation  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 39 — Measuring Angular Misalignment on Brackets  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 40 — Alignment Formula  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 41 — Adjusting Angular Misalignment in Plan  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Preparation  
Figure 42 — Correcting Parallel Misalignment  
(Figure 42 continued on next page)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Measurement  
Figure 42 — Correcting Parallel Misalignment  
(Figure 42 continued on next page)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Adjustment  
Figure 42 — Correcting Parallel Misalignment  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To Check Angular Alignment  
Figure 43 — Alignment Check — Assembled Coupling  
(Figure 43 continued on next page)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To Check Parallel Alignment  
Figure 43 — Alignment Check — Assembled Coupling  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 44 — Removing the Oil Filter  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 45 — Typical Float Valve Arrangement  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 46 — Lifting Open-Drive Motor  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 47 — Controls for Optional Pumpout Compressor  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 48 — Oil Differential Pressure/Power Supply Module  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 49 — PSIO Module LED Locations  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 50 — LID Module (Rear View) and LED Locations  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 51 — Processor (PSIO) Module  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 52 — Starter Management Module (SMM)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Switch Setting  
Options Module 1  
Options Module 2  
6
4
7
2
S1  
S2  
Figure 53 — Options Module  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 54 — Model Number Nomenclature for Compressor  
Size (See Figure 1 Also)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Note: See Table 17 for dimensions  
Figure 55 — Open-Drive Compressor Fits and Clearances  
(Figure 55 continued on next page)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Note: See Table 17 for dimensions  
Figure 55 — Open-Drive Compressor Fits and Clearances  
(Figure 55 continued on next page)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Note: See Table 17  
for dimensions  
Figure 55 — Open-Drive Compressor Fits and Clearances  
Download from Www.Somanuals.com. All Manuals Search And Download.  
View B  
View A  
Refer to Table 18 for dimensions  
Figure 56 — Hermetic Compressor Fits and Clearances  
(Figure 56 continued on next page)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 56 — Hermetic Compressor Fits and Clearances  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 57 — Electronic PIC Controls Wiring Schematic — Hermetic Machine  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(Figure 57 continued on next page)  
Figure 57 — Electronic PIC Controls Wiring Schematic — Hermetic Machine  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 58 — Electronic PIC Controls Wiring Schematic — Open Drive Machine  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(Figure 58 continued on next page)  
Figure 58 — Electronic PIC Controls Wiring Schematic —  
Open Drive Machine  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 59 — Machine Power Panel, Starter Assembly,  
and Motor Wiring Schematic  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(Figure 59 continued on next page)  
Figure 59 — Machine Power Panel, Starter Assembly,  
and Motor Wiring Schematic  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 60 — Hermetic Drive — Power Panel with Water-Cooled Oil Cooler  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 61 — Hermetic Drive — Power Panel with Motor Cooling Solenoid  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 62 — Open-Drive — Power Panel  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INITIAL START-UP CHECKLIST FOR  
17/19EX CENTRIFUGAL LIQUID CHILLER  
(Remove and use for job file.)  
MACHINE INFORMATION:  
NAME  
JOB NO.  
MODEL  
ADDRESS  
CITY  
STATE  
ZIP  
S/N  
DESIGN CONDITIONS:  
TONS BRINE  
FLOW TEMPERATURE TEMPERATURE PRESSURE  
SUCTION  
CONDENSER  
PASS  
RATE  
IN  
OUT  
DROP  
TEMPERATURE TEMPERATURE  
COOLER  
******  
CONDENSER  
******  
COMPRESSOR: Volts  
RLA  
Type  
RLA  
OLTA  
STARTER:  
OIL PUMP:  
Mfg  
Volts  
OLTA  
REFRIGERANT: Charge  
CARRIER OBLIGATIONS:  
Lbs  
Assemble . . . . . . . . . . . . . . . Yes  
Leak Test . . . . . . . . . . . . . . . Yes Ⅺ  
Dehydrate . . . . . . . . . . . . . . . Yes Ⅺ  
Charging . . . . . . . . . . . . . . . . Yes Ⅺ  
Alignment . . . . . . . . . . . . . . . Yes Ⅺ  
Operating Instructions  
No Ⅺ  
No Ⅺ  
No Ⅺ  
No Ⅺ  
No Ⅺ  
Hrs.  
START-UP TO BE PERFORMED IN ACCORDANCE WITH APPROPRIATE MACHINE START-UP  
INSTRUCTIONS  
JOB DATA REQUIRED:  
1. Machine Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . Yes Ⅺ  
2. Machine Assembly, Wiring and Piping Diagrams . . . . . . . . . . . . Yes Ⅺ  
3. Starting Equipment Details and Wiring Diagrams . . . . . . . . . . . . Yes Ⅺ  
4. Applicable Design Data (see above) . . . . . . . . . . . . . . . . . . . . . . Yes Ⅺ  
5. Diagrams and Instructions for Special Controls . . . . . . . . . . . . . Yes Ⅺ  
No Ⅺ  
No Ⅺ  
No Ⅺ  
No Ⅺ  
No Ⅺ  
INITIAL MACHINE PRESSURE:  
YES  
NO  
Was Machine Tight?  
If Not, Were Leaks Corrected?  
Was Machine Dehydrated After Repairs?  
CHECK COMPRESSOR OIL LEVEL AND RECORD:  
ADD OIL: Yes Ⅺ  
No Ⅺ  
Amount:  
RECORD PRESSURE DROPS:  
Cooler  
Condenser  
CHARGE REFRIGERANT:  
Initial Charge  
Final Charge After Trim  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 2 PC 211 Catalog No. 531-715 Printed in U.S.A. Form 17/19EX-1SS Pg CL-1 9-95 Replaces: 19EX-1SS  
Tab 5a 5d  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSPECT WIRING AND RECORD ELECTRICAL DATA:  
RATINGS:  
Motor Voltage  
Motor(s) Amps  
Oil Pump  
Oil Pump Voltage  
Controls/Oil Heater  
Starter Amps  
Line Voltages: Motor  
STARTER CHECKOUT:  
Check continuity T1 to T1, etc. (Motor to starter, disconnect motor leads T4, T5, T6.) Do not megohm test solid-state starters,  
disconnect leads to motor and megger the leads.  
‘‘PHASE TO PHASE’’  
T1-T2 T1-T3 T2-T3  
‘‘PHASE TO GROUND’’  
MEGGER MOTOR  
T1-G  
T2-G  
T3-G  
10-Second Readings:  
60-Second Readings:  
Polarization Ratio:  
STARTER:  
Motor Load Current Transformer Ratio  
Transition Timer Time Seconds  
Check Magnetic Overloads Add Dash Pot Oil Yes No Ⅺ  
Solid State Starter: Torque Setting O’Clock  
Electro-Mechanical Ⅺ  
Solid-State Ⅺ  
:
Signal Resistor Size  
Ohms  
Solid-State Overloads Yes Ⅺ  
No Ⅺ  
Ramp Setting  
Yes  
Seconds  
OPEN-DRIVE MOTOR BEARINGS: Added Oil to Proper Level  
CONTROLS: SAFETY, OPERATING, ETC.  
Perform Controls Test (Yes/No)  
PIC CAUTION  
Yes  
COMPRESSOR MOTOR AND CONTROL PANEL MUST BE PROPERLY AND INDIVIDUALLY CON-  
NECTED BACK TO THE EARTH GROUND IN THE STARTER. (IN ACCORDANCE WITH BULLETIN  
C-8912).  
RUN MACHINE:  
Do these safeties shut down machine?  
Condenser Water Flow Switch  
Chilled Water Flow Switch  
Pump Interlocks  
Yes Ⅺ  
Yes Ⅺ  
Yes Ⅺ  
No Ⅺ  
No Ⅺ  
No Ⅺ  
INITIAL START:  
Line Up All Valves in Accordance With Instruction Manual:  
Start Water Pumps and Establish Water Flow  
Oil Level OK and Oil Temperature OK  
Check Oil Pump Rotation-Pressure  
Check Compressor Motor Rotation (Motor End Sight Glass) and Record:  
Clockwise  
Restart Compressor, Bring Up To Speed. Shut Down. Any Abnormal Coastdown Noise?  
*If yes determine cause.  
Yes* Ⅺ  
No Ⅺ  
START MACHINE AND OPERATE. COMPLETE THE FOLLOWING:  
A: Trim Charge and Record Under Charge Refrigerant Section on page 57.  
B: Complete Any Remaining Control Calibration and Record Under Controls Section (pages 12-45).  
C: Take At Least 2 Sets of Operational Log Readings and Record.  
E: After Machine Has Been Successfully Run and Set Up, Shut Down and Mark Shutdown Oil and Refrigerant Levels.  
F: Give Operating Instructions to Owner’s Operating Personnel.  
G: Perform Hot Alignment (Open Drive Machines Only)  
Hours Given:  
Hours  
SIGNATURES:  
DATE  
CARRIER  
TECHNICIAN  
CUSTOMER REPRESENTATIVE  
DATE  
CL-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17/19EX  
CENTRIFUGAL LIQUID CHILLER  
CONFIGURATION SETTINGS LOG  
(Remove and use for job file.)  
SET POINT TABLE CONFIGURATION SHEET  
DESCRIPTION  
RANGE  
UNITS  
DEFAULT  
VALUE  
Base Demand Limit  
40 to 100  
%
100.0  
20 to 120  
DEG F  
LCW Setpoint  
50.0  
60.0  
40.0  
(–6.7 to 48.9)  
(DEG C)  
20 to 120  
(–6.7 to 48.9)  
DEG F  
(DEG C)  
ECW Setpoint  
20 to 60  
(–6.7 to 15.6)  
DEG F  
(DEG C)  
ICE BUILD Setpoint  
PSIO Software Version Number:  
LID Software Version Number:  
PSIO Controller Identification: BUS  
ADDRESS  
ADDRESS  
LID Identification:  
BUS  
CL-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LOCAL MODE TIME SCHEDULE CONFIGURATION SHEET OCCPC01S  
Day Flag  
M T W T F  
Occupied  
Time  
Unoccupied  
Time  
S
S H  
Period 1:  
Period 2:  
Period 3:  
Period 4:  
Period 5:  
Period 6:  
Period 7:  
Period 8:  
NOTE: Default setting is OCCUPIED 24 hours/day.  
ICE BUILD MODE TIME SCHEDULE CONFIGURATION SHEET OCCPC02S  
Day Flag  
M T W T F  
Occupied  
Time  
Unoccupied  
Time  
S
S H  
Period 1:  
Period 2:  
Period 3:  
Period 4:  
Period 5:  
Period 6:  
Period 7:  
Period 8:  
NOTE: Default setting is UNOCCUPIED 24 hours/day.  
CCN MODE TIME SCHEDULE CONFIGURATION SHEET OCCPC  
S
Day Flag  
M T W T F  
Occupied  
Time  
Unoccupied  
Time  
S
S H  
Period 1:  
Period 2:  
Period 3:  
Period 4:  
Period 5:  
Period 6:  
Period 7:  
Period 8:  
NOTE: Default setting is OCCUPIED 24 hours/  
CL-4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONFIG TABLE CONFIGURATION SHEET  
DESCRIPTION  
RESET TYPE 1  
RANGE  
UNITS  
DEFAULT  
VALUE  
–30 to 30  
(–17 to 17)  
DEG F  
(DEG C)  
10  
(6)  
Degrees Reset at 20 mA  
RESET TYPE 2  
–40 to 245  
(–40 to 118)  
DEG F  
(DEC C)  
85  
(29)  
Remote Temp (No Reset)  
–40 to 245  
(–40 to 118)  
DEG F  
(DEG C)  
65  
(18)  
Remote Temp (Full Reset)  
–30 to 30  
(–17 to 17)  
DEG F  
(DEG C)  
10  
(6)  
Degrees Reset  
RESET TYPE 3  
CHW Temp (No Reset)  
0 to 15  
(0 to 8)  
DEG F  
(DEG C)  
10  
(6)  
0 to 15  
(0 to 8)  
DEG F  
0
CHW Temp (Full Reset)  
Degrees Reset  
(DEG C)  
(0)  
–30 to 30  
(–17 to 17)  
DEG F  
(DEG C)  
5
(3)  
Select/Enable Reset Type  
ECW Control Option  
0 to 3  
0
Disable/Enable  
40 to 100  
Disable  
40  
Demand Limit at 20 mA  
20 mA Demand Limit Option  
Auto Restart Option  
%
Disable/Enable  
Disable/Enable  
Disable/Enable  
2 to 10  
Disable  
Disable  
Disable  
3
Remote Contacts Option  
Temp Pulldown Deg/Min  
Load Pulldown %/Min  
5 to 20  
10  
Select Ramp Type:  
Temp=0/Load=1  
0/1  
1
Loadshed Group Number  
Loadshed Demand Delta  
Maximum Loadshed Time  
0 to 99  
0 to 60  
0 to 120  
0
%
20  
60  
Min  
CCN Occupancy Config:  
Schedule Number  
3 to 99  
3
CCN Occupancy Config:  
Broadcast Option  
Disable/Enable  
Disable/Enable  
Disable  
Disable  
ICE BUILD Option  
ICE BUILD TERMINATION:  
0 =Temp, 1 =Contacts, 2 =Both  
0, 1, 2  
0
ICE BUILD RECYCLE Option  
Disable/Enable  
Disable  
CL-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEAD/LAG TABLE CONFIGURATION SHEET  
DESCRIPTION  
RANGE  
UNITS  
DEFAULT  
VALUE  
LEAD/LAG SELECT  
DISABLE =0, LEAD =1,  
LAG =2, STANDBY =3  
0, 1, 2, 3  
0
Load Balance Option  
Common Sensor Option  
LAG Percent Capacity  
LAG Address  
Disable/Enable  
Disable/Enable  
25 to 75  
Disable  
Disable  
50  
%
1 to 236  
92  
LAG START Timer  
2 to 60  
Min  
Min  
Min  
10  
LAG STOP Timer  
2 to 60  
10  
PRESTART FAULT Timer  
STANDBY Chiller Option  
STANDBY Percent Capacity  
STANDBY Address  
0 to 30  
5
Disable/Enable  
25 to 75  
Disable  
50  
%
1 to 236  
93  
CL-6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE1 TABLE CONFIGURATION SHEET  
DESCRIPTION  
RANGE  
UNITS  
DEFAULT  
VALUE  
150 to 200  
(66 to 93)  
DEG F  
(DEG C)  
200  
(93)  
Motor Temp Override  
psig  
(kPa)  
Cond Pressure Override  
90 to 200 (620 to 1379)  
125 (862)  
2 to 5  
DEG F  
(DEG C)  
3
Refrig Override Delta T  
Chilled Medium  
(1 to 3)  
(1.6)  
Water/Brine  
Water  
8 to 40  
(–13.3 to 4)  
DEG F  
(DEG C)  
33  
(1)  
Brine Refrig Trippoint  
125 to 200  
(52 to 93)  
DEG F  
200  
Compr Discharge Alert  
Bearing Temp Alert  
(DEG C)  
(93)  
165 to 210  
(74 to 99)  
DEG F  
(DEG C)  
210  
(99)  
Water Flow Verify Time  
Oil Press Verify Time  
0.5 to 5  
MIN  
SEC  
5
15 to 300  
15  
0.5 to 2.0  
DEG F  
1.0  
Water/Brine Deadband  
Recycle Restart Delta T  
Recycle Shutdown Delta T  
(0.3 to 1.1)  
(DEG C)  
(0.6)  
2.0 to 10  
(1.1 to 5.5)  
DEG F  
(DEG C)  
5
(2.8)  
0.5 to 4.0  
(0.27 to 2.2)  
DEG F  
(DEG C)  
1.0  
(0.6)  
Surge Limit/HGBP Option  
Surge=0/HGBP=1  
0/1  
0
0.5 to 15  
DEG F  
1.5  
Surge/HGBP Delta T1  
Surge/HGBP Delta P1  
Surge/HGBP Delta T2  
Surge/HGBP Delta P2  
Surge/HGBP Deadband  
(0.3 to 8.3)  
(DEG C)  
(0.8)  
psi  
(kPa)  
30 to 170 (206 to 1172)  
50 (345)  
0.5 to 15.0  
(0.3 to 8.3)  
DEG F  
(DEG C)  
10  
(5.6)  
psi  
(kPa)  
30 to 170 (206 to 1172)  
85 (586)  
1 to 3  
(0.6 to 1.6)  
DEG F  
(DEG C)  
1
(0.6)  
Surge Delta Percent Amps  
Surge Time Period  
10 to 50  
1 to 5  
%
25  
2
MIN  
Demand Limit Source  
Amps=0/Load=1  
0/1  
0
3
Amps Correction Factor  
1 to 8  
CL-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE1 TABLE CONFIGURATION SHEET  
DESCRIPTION  
RANGE  
1 to 9999  
UNITS  
AMPS  
VOLTS  
kW  
DEFAULT  
200  
VALUE  
Motor Rated Load Amps  
Motor Rated Line Voltage  
Meter Rated Line kW  
1 to 9999  
1 to 9999  
460  
600  
Line Frequency  
0=60 Hz/1=50 Hz  
0/1  
0
Compressor Starter Type  
Condenser Freeze Point  
REDUCE/FULL  
REDUCE  
–20 to 35  
(–28.9 to 1.7)  
DEG F  
(DEG C)  
34  
(1.1)  
Soft Stop Amps Threshold  
Stop-to-Start Timer*  
40 to 100  
3 to 50  
%
100  
20  
MIN  
*Open-drive machines only. Standard stop-to-start time for hermetic machines is 3 minutes.  
CL-8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE2 TABLE CONFIGURATION SHEET  
DESCRIPTION  
RANGE  
UNITS  
0 = EXTERNAL, 1 = INTERNAL  
0 = EXTERNAL, 1 = INTERNAL  
DEFAULT  
VALUE  
RESET 20 mA Power Source  
DEMAND 20 mA Power Source  
0/1  
0/1  
0
0
0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,  
3 = HIGH ALARM, 4 = LOW ALARM  
CHWS Temp Enable  
CHWS Temp Alert  
CHWR Temp Enable  
CHWR Temp Alert  
Reset Temp Enable  
Reset Temp Alert  
0 to 4  
0
–40 to 245  
(–40 to 118)  
DEG F  
(DEG C)  
245  
(118)  
0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,  
3 = HIGH ALARM, 4 = LOW ALARM  
0 to 4  
0
–40 to 245  
(–40 to 118)  
DEG F  
(DEG C)  
245  
(118)  
0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,  
3 = HIGH ALARM, 4 = LOW ALARM  
0 to 4  
0
–40 to 245  
(–40 to 118)  
DEG F  
(DEG C)  
245  
(118)  
0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,  
3 = HIGH ALARM, 4 = LOW ALARM  
Spare Temp 1 Enable  
Spare Temp 1 Alert  
Spare Temp 2 Enable  
Spare Temp 2 Alert  
Spare Temp 3 Enable  
Spare Temp 3 Alert  
0 to 4  
0
–40 to 245  
(–40 to 118)  
DEG F  
(DEG C)  
245  
(118)  
0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,  
3 = HIGH ALARM, 4 = LOW ALARM  
0 to 4  
0
–40 to 245  
(–40 to 118)  
DEG F  
(DEG C)  
245  
(118)  
0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,  
3 = HIGH ALARM, 4 = LOW ALARM  
0 to 4  
0
–40 to 245  
(–40 to 118)  
DEG F  
(DEG C)  
245  
(118)  
SPARE 1 20 mA Power Source  
SPARE 2 20 mA Power Source  
0/1  
0/1  
0 = EXTERNAL, 1 = INTERNAL  
0 = EXTERNAL, 1 = INTERNAL  
0
0
0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,  
3 = HIGH ALARM, 4 = LOW ALARM  
Spare Temp 4 Enable  
Spare Temp 4 Alert  
Spare Temp 5 Enable  
Spare Temp 5 Alert  
Spare Temp 6 Enable  
Spare Temp 6 Alert  
Spare Temp 7 Enable  
Spare Temp 7 Alert  
Spare Temp 8 Enable  
Spare Temp 8 Alert  
Spare Temp 9 Enable  
Spare Temp 9 Alert  
0 to 4  
0
–40 to 245  
(–40 to 118)  
DEG F  
(DEG C)  
245  
(118)  
0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,  
3 = HIGH ALARM, 4 = LOW ALARM  
0 to 4  
0
–40 to 245  
(–40 to 118)  
DEG F  
(DEG C)  
245  
(118)  
0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,  
3 = HIGH ALARM, 4 = LOW ALARM  
0 to 4  
0
–40 to 245  
(–40 to 118)  
DEG F  
(DEG C)  
245  
(118)  
0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,  
3 = HIGH ALARM, 4 = LOW ALARM  
0 to 4  
0
–40 to 245  
(–40 to 118)  
DEG F  
(DEG C)  
245  
(118)  
0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,  
3 = HIGH ALARM, 4 = LOW ALARM  
0 to 4  
0
–40 to 245  
(–40 to 118)  
DEG F  
(DEG C)  
245  
(118)  
0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,  
3 = HIGH ALARM, 4 = LOW ALARM  
0 to 4  
0
–40 to 245  
(–40 to 118)  
DEG F  
(DEG C)  
245  
(118)  
CL-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE3 TABLE CONFIGURATION SHEET  
DESCRIPTION  
RANGE  
2 to 10  
2 to 10  
1 to 3  
UNITS  
DEFAULT  
VALUE  
Proportional Inc Band  
Proportional Dec Band  
Proportional ECW Gain  
Guide Vane Travel Limit  
6.5  
6.0  
2.0  
50  
30 to 100  
%
HOLIDAY (HOLIDEF) CONFIGURATION SHEET HOLIDEF  
RANGE UNITS  
1 to 12  
S
DESCRIPTION  
Holiday Start Month  
Start Day  
VALUE  
1 to 31  
0 to 99  
Duration  
DAYS  
HOLIDAY (HOLIDEF) CONFIGURATION SHEET  
DESCRIPTION RANGE UNITS  
1 to 12  
HOLIDEF  
S
VALUE  
Holiday Start Month  
Start Day  
1 to 31  
0 to 99  
Duration  
DAYS  
HOLIDAY (HOLIDEF) CONFIGURATION SHEET  
DESCRIPTION RANGE UNITS  
1 to 12  
HOLIDEF  
S
VALUE  
Holiday Start Month  
Start Day  
1 to 31  
0 to 99  
Duration  
DAYS  
NOTE: There are no HOLIDAYS defined on the default menu. HOLIDAY dates must be updated yearly if they are used.  
CL-10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BROADCAST (BRODEFS) CONFIGURATION SHEET  
DESCRIPTION  
Activate  
RANGE  
Yes/No  
UNITS  
DEFAULT  
VALUE  
No  
OAT Broadcast  
Controller Name  
Bus Number  
Element Number  
OARH Broadcast  
Controller Name  
Bus Number  
Element Number  
Daylight Savings Start  
Month  
8 characters  
0 to 239  
Text  
Bus #s  
SE #s  
0
0
0 to 239  
8 characters  
0 to 239  
Text  
Bus #s  
SE #s  
0
0
0 to 239  
1 to 12  
4
15  
Day  
1 to 31  
Time  
00:00 to 23:59  
1 to 1440  
HH:MM  
MIN  
02:00  
60  
Minutes To Add  
Daylight Savings Stop  
Month  
1 to 12  
10  
15  
Day  
1 to 31  
Time  
00:00 to 23:59  
1 to 1440  
HH:MM  
MIN  
02:00  
60  
Minutes To Subtract  
CL-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MACHINE ALIGNMENT REPORT  
JOB NAME  
COUPLING SIZE  
JOB NUMBER  
MACHINE SER. NO.  
DRIVER TYPE  
TYPE  
WEAR CONDITION  
SPACER LENGTH  
HOT CHECK  
COLD CHECK  
COMPRESSOR COUPLING  
Top  
DRIVE COUPLING  
Top  
’’  
Open  
On  
’’  
’’  
Open  
On  
Bottom  
Diam  
Bottom  
’’  
Diam  
Step 1 — Angular in Elevation  
Gear □  
Drive □  
Hi □  
Hi □  
Drive  
’’  
’’ Lo □  
Lo □  
Step 2 — Parallel in Elevation  
In  
In  
Open  
On  
’’  
’’  
Open  
On  
’’  
’’  
Out  
Diam  
Out  
Diam  
Step 3 — Angular in Plan  
Gear □  
Drive □  
In  
Drive  
’’  
In  
’’ Out □  
Out □  
Step 4 — Parallel in Plan  
KEY:  
In — Side toward compressor discharge (side next to cooler).  
Out — Side opposite compressor discharge (side furthest from cooler).  
SIGNED  
DATE  
Copyright 1995 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 2 PC 211 Catalog No. 531-715 Printed in U.S.A. Form 17/19EX-1SS Pg CL-12 9-95 Replaces: 19EX-1SS  
Tab 5a 5d  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  

Belkin Network Card USB10 User Manual
BenQ Computer Monitor FP531 User Manual
Black Box Home Theater Server ServSwitch Secure and Secure PLus User Manual
Black Decker Pressure Washer 598111 01 User Manual
Brinly Hardy Lawn Mower Accessory hdc 10 User Manual
Brother Sewing Machine EF4 N11 User Manual
Bush Hog Lawn Mower FTH 600 User Manual
Canon Fax Machine MF6500 Series User Manual
Casio Digital Camera QV R3 User Manual
Chicago Electric Welder 8878 User Manual