48MPD,MPE62L-10R
50MP62L-10R
Single Package Electric Cooling Units
and Gas Heating/Electric Cooling Units
With Product Integrated Controls
Installation, Start-Up and Service
Instructions
CONTENTS
Page
Page
Gas Pressure Check . . . . . . . . . . . . . . . . . . . . . . . . 38
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . .
2
2
Check Supply Fan Rotation . . . . . . . . . . . . . . . . . 38
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-42
Initial Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Operating Sequences . . . . . . . . . . . . . . . . . . . . . . 39
• SUPPLY FAN
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-28
Jobsite Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Roof Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Slab Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Field-Fabricated Ductwork . . . . . . . . . . . . . . . . . .
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Condensate Drains . . . . . . . . . . . . . . . . . . . . . . . . .
Condensate Coil Shipping Covers . . . . . . . . . .
Install Outdoor Hoods . . . . . . . . . . . . . . . . . . . . . .
3
3
3
3
3
3
3
3
3
• ECONOMIZER
• COOLING (All Units)
• OCCUPIED COOLING
• UNOCCUPIED COOLING
• OVERRIDES
• ADAPTIVE OPTIMAL START
Make Electrical Connections . . . . . . . . . . . . . . . . 14
• POWER SUPPLY
• ADAPTIVE OPTIMAL STOP
(CV Applications Only)
Field Electrical Connections . . . . . . . . . . . . . . . . 14
• POWER WIRING
• GAS HEATING, OPERATION
(48MP Units Only)
Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
• SENSORS
Control Loop Checkout . . . . . . . . . . . . . . . . . . . . . 41
IAQ Control Loop Adjustment . . . . . . . . . . . . . . . 42
Lead/Lag Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Final Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
• HUMIDITY CONTROL AND HOT WATER
AND STEAM VALVES
• SPACE TEMPERATURE SENSOR (T55)
• SPACE TEMPERATURE SENSOR (T56)
(CV Applications Only)
CONTROL SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . 42-45
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
• PROCESSOR MODULE NO. 1
• SPACE TEMPERATURE AVERAGING
• HEAT INTERLOCK RELAY (VAV Units Only
— Not Necessary For DAV Applications)
• OPTION AND ACCESSORY CONTROL WIRING
Carrier Comfort Network Interface . . . . . . . . . . 23
Air Pressure Tubing . . . . . . . . . . . . . . . . . . . . . . . . 24
Gas Piping (48 Series Units Only) . . . . . . . . . . . . 26
Installing Flue/Inlet Hoods
(48MP Units Only) . . . . . . . . . . . . . . . . . . . . . . . . . 26
Fan Isolator Adjustment . . . . . . . . . . . . . . . . . . . . 27
Check Compressor Mounting . . . . . . . . . . . . . . . 27
Install Accessories . . . . . . . . . . . . . . . . . . . . . . . . . 27
• PROCESSOR MODULE NO. 2
• HIGH-VOLTAGE RELAY MODULES (DSIO)
• KEYPAD AND DISPLAY MODULE (HSIO)
Default Set Points/Changing Set Points . . . . . 43
Motor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Variable Frequency Drive (VFD) . . . . . . . . . . . . . 43
• DISPLAY AND KEYPAD
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45-55
Service Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
• UNIT CONTROL BOX
• COMPRESSORS
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28-38
System Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Evaporator-Fan Belts, Pulleys,
and Sheaves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Controls Configuration and Quick Test . . . . . . 35
• SUPPLY FAN STATUS SWITCH (FS)
• CHECK FILTER SWITCH (CFS)
• LIQUID SERVICE VALVES, SOLENOID VALVES,
FILTER DRIERS, AND SIGHT GLASSES
• EVAPORATOR-FAN MOTORS, PULLEYS, AND
BELTS
• POWER EXHAUST MOTORS, PULLEYS, AND
BELTS
• GAS HEAT SECTION
• UNIT CONTROL BOX
• ECONOMIZER DAMPER MOTORS
• RETURN-AIR FILTERS
• ENTHALPY CONTROL SET POINT
• KEYPAD AND DISPLAY MODULE (HSIO)
CONFIGURATION
• CONDENSER FANS AND FAN MOTORS
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
• SET UNIT TYPE
• ENTER JOB SET POINT VALUES
• CONFIGURE UNIT CONTROLS AND
FUNCTIONS
• QUICK TEST FUNCTION
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 PC 111 Catalog No. 534-893 Printed in U.S.A. Form 48/50MP-1SI Pg 1 12-98 Replaces: 50MP-1SI
Tab 1a 1b
1
Download from Www.Somanuals.com. All Manuals Search And Download.
Secure all ducts to the building structure, using flexible
duct connectors between roof curb and ducts as required. Ducts
passing through an unconditioned space must be insulated
and covered with a vapor barrier. Outlet grilles must not lie
directly below unit discharge. The return duct must have a
90-degree elbow before opening into the building space if
unit is equipped with power exhaust.
INSTALLATION
Jobsite Survey — Complete the following checks be-
fore installation.
1. Consult local building codes and the NEC (National
Electrical Code) (ANSI/NFPA [National Fire Protection
Association] 70) for special installation requirements.
Design supply duct strong enough to handle expected static
pressures.
2. Determine unit location (from project plans) or select unit
location.
3. Check for possible overhead obstructions which may in-
terfere with unit lifting or rigging.
For vertical supply and return units, tools or parts could
drop into ductwork and cause an injury. Install 90 de-
gree turns in the supply and return ductwork between
the unit and the conditioned space. If a 90 degree elbow
cannot be installed, then grilles of sufficient strength and
density should be installed to prevent objects from fall-
ing into the conditioned space.
Do not lift unit with forklift truck. Move unit with
overhead rigging only.
Unit Placement — Inspect unit for transportation dam-
age. File claim with transportation agency.
Provide clearance around and above unit for airflow, safety,
and service access. Do not restrict top (area above con-
denser fans) in any way. Allow at least 6 ft on all sides for
rated performance, code compliance, and service.
Check unit dimensional drawings for unit arrangement and
minimum performance and service clearances.
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated
air.
Rigging — Do not drop unit; keep upright. Use spreader
bars over unit to prevent sling or cable damage. Leave con-
denser coil shipping protection in place while rigging to
prevent coil damage. All lifting lugs MUST be used when
lifting unit.
Level by using unit frame as a reference. See Fig. 7 for
information. Unit and accessory weights are shown in
Tables 1-4. Weight distribution and center of gravity can be
found in Fig. 8.
On units equipped with power exhaust option, high
velocity air is exhausted out the hood. Unit should be
positioned with at least 10 ft clearance between the exhaust
hood and any obstruction. Although unit is weatherproof, guard
against water from higher level runoff and overhangs.
Condensate Drains — The condensate drain connec-
1
tion is a 1 ⁄2-in. NPT pipe connection located on the right
hand side of the unit. See Fig. 9.
NOTE: Use a trap of at least 7-in. deep.
Level by using unit frame as a reference. Physical data is
shown in Tables 1-4.
Condenser Coil Shipping Covers — Remove and
discard.
Roof Mount — Check building codes for weight distri-
bution requirements. Unit weight is shown in Table 1. Unit
may be mounted on class A, B, or C roofing material.
Install Outdoor Hoods
1. Outdoor-air hoods are shipped bolted to the unit in a ship-
ping position. To open hoods, remove the 3 holddown
bars holding the air hood in shipping position. See
Fig. 10.
2. Lift up the highest hood top and swing out hood sides to
form the outside frame of the air hood. Fasten hood top
to hood sides at middle and top holes only, using two screws
on each side. See Fig. 11.
ROOF CURB — Assemble and install as described in in-
structions shipped with the accessory. Accessory roof curb
and information required to field fabricate a roof curb is shown
in Fig. 1 and 2. Install insulation, cant strips, roofing, and
counter flashing as required. For unit condensate drain to func-
tion properly, curb must be level or within tolerances shown
in Fig. 1 and 2.
3. Remove the bottom hood block-off plate and set aside.
STEEL BEAMS — If roof curb is not used, support unit
with steel beams along its entire length and then support steel
as required. As a minimum, unit must be supported across
its width at each lifting lug location.
4. Swing up second hood (from the top of unit) into place
and fasten to hood sides with screws provided using up-
per hole only.
5. Swing up third hood (from the top of unit) into place and
fasten to hood sides with screws provided using upper
hole only.
6. Swing up fourth hood (bottom hood) into place. Before
fastening hood to hood sides, swing down bottom filter
rack. Fasten hood to hood sides with screws provided us-
ing upper hole only.
Slab Mount — Provide a level concrete slab that ex-
tends beyond unit cabinet at least 6 inches. Make a slab 8 in.
thick with 4 in. above grade. Use gravel apron in front of
condenser coil air inlet to prevent grass and foliage from ob-
structing airflow. Ensure that slab is of sufficient height to
allow for 7-in. condensate trap.
7. Attach block off plate removed from Step 3.
Field-Fabricated Ductwork — Units are designed for
vertical supply/return only. Field-fabricated ductwork should
be attached to the roof curb. Supply and return duct dimen-
sions are shown in Fig. 1-6.
8. Clip wire tie holding filter track. Swing filter track into
position and fasten to hood sides using screws provided.
Repeat until all 4 filter racks have been installed.
To attach ductwork to roof curb, insert duct approxi-
mately 10 to 11 in. up into roof curb. Connect ductwork to
14-gage roof curb material with sheet metal screws driven
from inside of the duct.
9. Apply a bead of RTV or similar sealant to corner of each
hood at pivot point to prevent water leaks.
Copy continues on page 14.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1 — Physical Data
BASE UNIT 48/50MP
NOMINAL CAPACITY (tons)
62L
70M
82N
80
90
105
OPERATING WEIGHT (lb)
Base Unit (48MP/50MP)
Copper Condenser Coils
Exhaust Fan
16,810/16,550
675
18,060/17,800
725
22,660/22,400
725
1,675
1,775
2,375
COMPRESSORS
Semi-Hermetic
Number of Refrigerant Circuits
Circuit (No. of Cylinders)
Model 06E
2
2
2
A (6)
B (6)
−299
19
A1 (6), A2 (4)
−275, −250
19, 14
B (6)
−299
19
A1 (6), A2 (4)
B1 (6), B2 (6)
−265, −265
19,19
−299
19
−265, −250
19, 14
Oil Charge (pints)
Capacity Steps (%)
17,33,50,67,83,100
11,22,33,41,56,67,78,89,100
18,26,35,44,53,56,65,74,82,91,100
REFRIGERANT
Operating Charge (lb), Sys 1/Sys 2 (Standard Coil)
Operating Charge (lb), Sys 1/Sys 2 (Alternate Coil)
R-22
85/82
94/85
78/78
83/83
85/82
92/88
CONDENSER COILS
Quantity
Grooved Tube (3⁄8-in. OD)
4
4
4
Rows...Fins/in.
3...17
116.7
3...17
128.3
3...17
128.3
Total Face Area (sq ft)
EVAPORATOR COILS
Quantity
Smooth Tube (5⁄8-in. OD)
2
2
2
Rows...Fins/in.
Standard
3...14
4...14
62.6
3...14
4...14
70.0
3...14
4...14
82.0
Alternate
Total Face Area (sq ft)
Refrigerant Feed
Device...No. per Circuit
TXV...2
TXV...2
TXV...2
EVAPORATOR FANS
Forward Curved Fan
Motor Hp
30
286T
40
324T
40
324T
50
326T
40
324T
50
326T
Motor Frame Size
Efficiency at Full Load (%)
Standard Efficiency
High Efficiency
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Fan Rpm
92.4
93.6
93.0
94.5
93.0
94.5
93.0
94.5
93.0
94.5
93.0
94.5
18.4
16.0
15.4
15.4
20.0
18.4
6.2
608
6.4
705
5.6
658
6.4
747
5.8
526
6.0
590
Belts Quantity...Model No.
Center Distance Range (in.)
Maximum Rpm
3...BX128
42.1-46.1
835
4...BX124
43.1-48.2
835
5...BX124
43.1-48.2
835
5...BX124
43.1-48.2
835
5...BX115
35.4-40.2
715
6...BX112
35.4-40.2
715
Air Foil Fan
Motor Hp
Motor Frame Size
30
286T
40
324T
40
324T
50
326T
40
324T
50
326T
Efficiency at Full Load (%)
Standard Efficiency
High Efficiency
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Fan Rpm
92.4
93.6
93.0
94.5
92.4
93.6
93.0
94.5
92.4
93.6
93.0
94.5
11.0
12.4
12.4
9.1
12.5
12.5
7.4
1192
9.4
1337
9.4
1337
7.5
1442
6.9
966
7.5
1050
Belts Quantity...Model No.
Center Distance Range (in.)
Maximum Rpm
3...B111
39.7-43.7
1595
3...B120
40.4-45.2
1595
3...B120
40.4-45.2
1595
3...5VX1120
40.4-45.2
1595
3...5VX1060
35.4-39.4
1298
3...5VX1060
35.4-39.4
1298
Air Foil Fan (cont)
Motor Hp
Motor Frame Size
50
326T
60
364T
60
364T
Efficiency at Full Load (%)
Standard Efficiency
High Efficiency
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Fan Rpm
93.0
94.5
9.1
94.5
95.4
8.1
94.5
95.4
11.0
7.1
7.5
7.1
1442
1534
1119
Belts Quantity...Model No.
Center Distance Range (in.)
Maximum Rpm
3...5VX1120
40.4-45.2
1595
4...5VX1080
39.4-44.9
1595
4...5VX1030
34.4-39.1
1298
CONDENSER FANS
Quantity...Diameter (in.)
Nominal Cfm
6...30
52,000
1...1140
6...30
52,000
1...1140
6...30
52,000
1...1140
Motor Hp...Rpm
SUPPLY FAN
Forward Curve
Airfoil
32,000
33.0
1595
2.44
Forward Curve
Airfoil
36,000
33.0
1595
2.44
Forward Curve
Airfoil
42,000
40.25
1298
Nominal Cfm
32,000
30.0
36,000
30.0
42,000
36.0
Size (in.)
Maximum Allowable Rpm
Shaft Diameter at Pulley (in.)
835
2.69
835
2.69
715
2.69
2.44
FURNACE SECTION (48MP Units Only)
Rollout Switch Cutout Temp (F)
Number of Burners
190
7
0.136...29
342,000
3.3
190
7
0.136...29
342,000
3.3
Burner Orifice Diameter (in. ...drill size)
Gas Input (Btuh)
Manifold Pressure (in. wg) — Natural Gas
Gas Valve Input Pressure Range
in. wg
5.5-13.5
0.235-0.487
5.5-13.5
0.235-0.487
psig
LOW HEAT (48MPD)/HIGH HEAT (48MPE)
Number of Sections
2/3
515,000/770,000
685,000/1,025,000
81/81
10-40/20-50
12,850/15,400
2
2/3
Gas Input (Btuh) Stage 1
Stage 2
515,000/770,000
685,000/1,025,000
81/81
Efficiency (Steady State %)
Temperature Rise Range (F)
Minimum Heating Airflow (cfm)
Field Gas Connection Size (in.)
5-35/10-40
14,700/19,250
2
FILTERS
Medium Efficiency (30%)
Pleated (Standard)
Quantity...Size (in.)
15...24 x 24 x 2,
5...24 x 12 x 2
15...24 x 24 x 2,
5...24 x 12 x 2
20...24 x 24 x 2,
5...24 x 12 x 2
High Efficiency (90%) Cartridge Filters
with Prefilters (Optional)
Quantity...Size (in.)
Outdoor Air Inlet Screens
Quantity...Size (in.)
15...24 x 24 x 4,
5...24 x 12 x 4
15...24 x 24 x 4,
5...24 x 12 x 4
Cleanable Aluminum
16...20 x 25 x 1
20...24 x 24 x 4,
5...24 x 12 x 4
16...20 x 25 x 1
24...20 x 25 x 1
LEGEND
TXV
—
Thermostatic Expansion Valve
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Table1 — Physical Data (cont)
BASE UNIT 48/50MP
NOMINAL CAPACITY (tons)
90P
10R
115
120
OPERATING WEIGHT (lb)
Base Unit (48MP/50MP)
Copper Condenser Coils
Exhaust Fan
24,660/24,750
950
25,110/25,100
950
2400
2400
COMPRESSORS
Semi-Hermetic
Number of Refrigerant Circuits
Circuit (No. of Cylinders)
Model 06E
2
2
A1 (6), A2 (6)
−265, −275
19, 19
B1 (6), B2 (6)
A1 (6), A2 (6)
−265, −299
19, 19
B1 (6), B2 (6)
−265, −275
19, 19
−265, −275
19, 19
Oil Charge (pints)
Capacity Steps (%)
15,23,30,38,45,58,65,73,85,92,100
14,21,28,35,42,61,68,75,86,93,100
REFRIGERANT
Operating Charge (lb), Sys 1/Sys 2 (Standard Coil)
Operating Charge (lb), Sys 1/Sys 2 (Alternate Coil)
R-22
85/85
93/93
86/87
93/96
CONDENSER COILS
Quantity
Grooved Tube (3⁄8-in. OD)
Smooth Tube (5⁄8-in. OD)
4
4
Rows...Fins/in.
3...17
168.0
3...17
168.0
Total Face Area (sq ft)
EVAPORATOR COILS
Quantity
Rows...Fins/in.
Standard
Alternate
Total Face Area (sq ft)
Refrigerant Feed
Device...No. per Circuit
2
2
3...14
4...14
90.3
3...14
4...14
101.4
TXV...2
TXV...2
EVAPORATOR FANS
Forward Curved Fan
Motor Hp
50
326T
60
364T
60
364T
Motor Frame Size
Efficiency at Full Load (%)
Standard Efficiency
High Efficiency
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Fan Rpm
93.0
94.5
94.5
95.4
94.5
95.4
18.8
18.8
21.3
5.9
555
6.7
630
6.7
556
Belts Quantity...Model No.
Center Distance Range (in.)
Maximum Rpm
4...5VX1120
35.4/40.2
715
4...5VX1120
35.4/40.2
715
4...5VX1150
34.2/40.2
715
Air Foil Fan
Motor Hp
Motor Frame Size
50
326T
60
364T
50
326T
60
364T
Efficiency at Full Load (%)
Standard Efficiency
High Efficiency
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Fan Rpm
93.0
94.5
94.5
95.4
93.0
94.5
94.5
95.4
12.5
13.7
13.7
13.7
7.5
1050
8.7
1111
8.1
1035
8.7
1111
Belts Quantity...Model No.
Center Distance Range (in.)
Maximum Rpm
3...5VX1030
35.4/39.4
1298
3...5VX1060
34.4/39.1
1298
3...5VX1060
35.4/39.4
1298
3...5VX1060
34.4/39.1
1298
Air Foil Fan (cont)
Motor Hp
Motor Frame Size
75
365T
75
365T
Efficiency at Full Load (%)
Standard Efficiency
High Efficiency
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Fan Rpm
95.4
—
95.4
—
16.1
16.1
11.1
1207
11.1
1207
Belts Quantity...Model No.
Center Distance Range (in.)
Maximum Rpm
3...5VX1120
34.4/39.1
1298
3...5VX1120
34.4/39.1
1298
CONDENSER FANS
Quantity...Diameter (in.)
Nominal Cfm
8...30
69,500
1...1140
8...30
69,500
1...1140
Motor Hp...Rpm
SUPPLY FAN
Forward Curve
46,000
36.0
Airfoil
46,000
40.25
1298
Forward Curve
52,000
36.0
Airfoil
52,000
40.25
1298
Nominal Cfm
Size (in.)
Maximum Allowable Rpm
Shaft Diameter at Pulley (in.)
715
715
2.69
2.44
2.69
2.44
FURNACE SECTION (48MP Units Only)
Rollout Switch Cutout Temp (F)
Number of Burners
190
7
0.136...29
342,000
3.3
Burner Orifice Diameter (in. ...drill size)
Gas Input (Btuh)
Manifold Pressure (in. wg) — Natural Gas
Gas Valve Input Pressure Range
in. wg
5.5-13.5
0.235-0.487
psig
LOW HEAT (48MPD)/HIGH HEAT (48MPE)
Number of Sections
2/3
Gas Input (Btuh) Stage 1
Stage 2
515,000/770,000
685,000/1,025,000
81/81
Efficiency (Steady State %)
Temperature Rise Range (F)
Minimum Heating Airflow (cfm)
Field Gas Connection Size (in.)
5-35/10-40
14,700/19,250
2
FILTERS
Medium Efficiency (30%)
Pleated (Standard) Quantity...Size (in.)
High Efficiency (90%)
20...24 x 24 x 2,
5...24 x 12 x 2
20...24 x 24 x 2,
5...24 x 12 x 2
Cartridge Filters with Prefilters (Optional)
Quantity...Size (in.)
Outdoor Air Inlet Screens
Quantity...Size (in.)
20...24 x 24 x 4,
5...24 x 12 x 4
20...24 x 24 x 4,
5...24 x 12 x 4
Cleanable Aluminum
24...20 x 25 x 1
24...20 x 25 x 1
LEGEND
TXV
—
Thermostatic Expansion Valve
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2 — Optional Power Exhaust Specifications
UNIT 48/50MP
62L
70M
82N
Type
100% Mod
30
100% Non Mod
100% Mod
40
100% Non Mod
100% Mod
40
100% Non Mod
Motor Hp
30
40
40
Motor Frame Size
286T
286T
324T
324T
324T
324T
Efficiency at Full Load (%)
Standard Efficiency
92.4
93.6
92.4
93.6
93.0
94.5
93.0
94.5
93.0
94.5
93.0
94.5
High Efficiency
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Fan Rpm
18.4
18.4
18.4
18.4
25.0
20.0
5.6
6.0
6.2
6.6
6.8
5.8
552
590
608
646
491
526
Belts Quantity...Model No.
Center Distance Range (in.)
Maximum Allowable Rpm
4...BX80
19.9-23.3
650
4...BX81
19.9-23.3
650
5...BX80
18.6-22.8
835
5...BX80
18.6-22.8
835
5...B90
21.8-25.9
560
5...BX90
21.8-25.9
560
Type
50% Non Mod
50% Non Mod
50% Non Mod
Motor Hp
7.5
7.5
7.5
Motor Frame Size
213T
213T
213T
Efficiency at Full Load (%)
Standard Efficiency
88.5
91.7
88.5
91.7
88.5
91.7
High Efficiency
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Fan Rpm
15.4
16.0
18.4
3.6
3.6
3.6
412
397
346
Belts Quantity...Model No.
Center Distance Range (in.)
Maximum Allowable Rpm
2...BX75
21.3-24.1
690
2...BX77
21.7-24.2
650
2...BX90
24.9-27.4
600
Table 2 — Optional Power Exhaust Specifications (cont)
UNIT 48/50MP
90P
10R
Type
100% Mod
50
100% Non Mod
100% Mod
60
100% Non Mod
Motor Hp
50
60
Motor Frame Size
326T
326T
364T
364T
Efficiency at Full Load (%)
Standard Efficiency
93.0
94.5
93.0
94.5
94.5
95.4
94.5
95.4
High Efficiency
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Fan Rpm
28.1
28.1
28.1
28.1
8.1
8.1
9.1
9.1
508
508
558
558
Belts Quantity...Model No.
Center Distance Range (in.)
Maximum Allowable Rpm
3...5VX1060
21.8/25.9
560
3...5VX1060
21.8/25.9
560
3...5VX1060
20.9/25.6
560
3...5VX1060
20.9/25.6
560
Type
50% Non Mod
50% Non Mod
Motor Hp
10
15
Motor Frame Size
215T
254T
Efficiency at Full Load (%)
Standard Efficiency
89.5
91.7
89.5
91.7
High Efficiency
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Fan Rpm
20.0
20.0
4.5
4.0
362
371
Belts Quantity...Model No.
Center Distance Range (in.)
Maximum Allowable Rpm
2...BX90
24.9/27.4
600
3...BX90
23.9/26.8
600
Table 3 — Compressor Oil Charge
OIL CHARGE (pints)
Compressor
Circuit A
Compressor
Circuit B
UNIT 48/50MP
Total Circuit A
Total Circuit B
A1
19
19
19
19
19
A2
—
B1
19
19
19
19
19
B2
—
62L
70M
82N
90P
10R
19
33
33
38
38
19
19
38
38
38
14
14
19
19
—
19
19
19
Table 4 — Variable Frequency Drive (VFD) Physical Data
DIMENSIONS (in.)
FAN MOTOR
HP
WEIGHT (lb)
Height
24.02
24.02
30.91
30.91
33.46
Width
12.99
12.99
12.99
12.99
12.99
Length
11.22
11.22
11.22
11.22
11.22
30
40
50
60
75
68
68
106
106
106
6
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES:
1. Roof curb is shipped disassembled.
2. Roof curb: 14 gage [VA03-56] steel.
3. Dimensions in [ ] are in millimeters.
4. To prevent standing water in the drain pan of the
indoor section, roof curb and unit must be level
within tolerances shown.
NOTES:
1. To prevent the hazard of stagnant water build-up in the drain pan on the indoor section, unit cannot
exceed leveling tolerances shown.
2. If a Carrier roof curb is not used, curb cross rails must be postioned to clear unit base rail locations
shown.
Fig. 1 — Roof Curb Dimensions, 48/50MP62L and 70M
7
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES:
1. Roof curb is shipped disassembled.
2. Roof curb: 14 gage [VA03-56] steel.
3. Dimensions in [ ] are in millimeters.
4. To prevent standing water in the drain pan of the
indoor section, roof curb and unit must be level
within tolerances shown.
NOTES:
1. To prevent the hazard of stagnant water build-up in the drain pan on the indoor section, unit cannot
exceed leveling tolerances shown.
2. If a Carrier roof curb is not used, curb cross rails must be postioned to clear unit base rail locations
shown.
Fig. 2 — Roof Curb Dimensions, 48/50MP82N-10R
8
Download from Www.Somanuals.com. All Manuals Search And Download.
WEIGHT
A
B
C
D
E
F
UNIT SIZE
48MPD,E
lb
kg
mm
3505
3647
ft-in.
mm
957
ft-in.
3-111⁄16
3-97⁄8
mm
5909
6166
ft-in.
mm
1203
1264
ft-in.
3-113⁄8
4- 13⁄4
mm
ft-in.
mm
ft-in.
62L
16,810
18,060
7624
8190
11- 6
19-45⁄8
20-23⁄4
13 011
13 297
42-81⁄4
43-71⁄2
14 256
14 542
46-91⁄4
47-81⁄2
70M
11-119⁄16
1165
NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Center of gravity includes exhaust fan and high heat options. Unit weight does not include exhaust fan or high
heat options.
3. High heat add: 260 lb [118 kg]
Exhaust fan add: 1675 lb [761 kg] on 62L
1775 lb [807 kg] on 70M
4. Unit clearances:
Top — Do not restrict condenser fans, control box end — 6Ј-0Љ.
Sides — 6Ј-0Љ (except on return fan equipped units — 10Ј-0Љ).
Economizer end — 6Ј-0Љ (except power exhaust units — 10Ј-0Љ).
For smaller service and operational clearances, contact Carrier Application Engineering Department.
5. Downshot ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is recommended
the ducts be supported by cross braces as done on the accessory roof curb.
Fig. 3 — Base Unit Dimensions, 48MP62L, 70M
9
Download from Www.Somanuals.com. All Manuals Search And Download.
WEIGHT
A
B
C
D
E
F
UNIT SIZE
48MPD,E
lb
kg
mm
3646
1938
1938
ft-in.
mm
—
ft-in.
—
8-51⁄4
8-51⁄4
mm
6734
7283
7268
ft-in.
mm
1753
1765
1759
ft-in.
5-9
5-91⁄2
5-91⁄4
mm
ft-in.
mm
ft-in.
82N
90P
10R
22,660
24,660
25,110
10 295
11 203
11 408
11-119⁄16
6- 45⁄16
6- 45⁄16
22- 11⁄8
23-103⁄4
23-101⁄8
13 957
14 821
14 821
45-91⁄2
48-71⁄2
48-71⁄2
15 202
16 066
16 066
49-101⁄2
52- 81⁄2
52- 81⁄2
2572
2572
NOTES:
1. Dimensions in [ ] are in millimeters.
4. Unit clearances:
Top — Do not restrict condenser fans, control box end — 6Ј-0Љ.
Sides — 6Ј-0Љ (except on return fan equipped units — 10Ј-0Љ).
Economizer end — 6Ј-0Љ (except power exhaust units — 10Ј-0Љ).
2.
Center of gravity includes exhaust fan and high heat options. Unit weight
does not include exhaust fan or high heat options.
For smaller service and operational clearances, contact Carrier Application En-
gineering Department.
5. Downshot ducts designed to be attached to accessory roof curb. If unit is mounted
on dunnage, it is recommended the ducts be supported by cross braces as done
on the accessory roof curb.
3. High heat add: 260 lb [118 kg]
Exhaust fan add: 2275 lb [1034 kg] on 82N
2400 lb [1090 kg] on 90P and 10R
Fig. 4 — Base Unit Dimensions, 48MP82N-10R
10
Download from Www.Somanuals.com. All Manuals Search And Download.
WEIGHT
C1
C2
UNIT
SIZE
50MP
A
B
D
E
F
(See Note 3)
(See Note 2)
(See Note 2)
lb
16,550 7511 3505 11Ј- 6Љ
17,800 8078 3647 11Ј-119⁄16Љ 1165 3Ј-97⁄8
kg
mm
ft-in.
mm
957 3Ј-111⁄16Љ 5880 19Ј-31⁄2
6166 20Ј-23⁄4
ft-in.
mm
ft-in.
mm
ft-in.
mm
1203 3Ј-113⁄8
1264 4Ј- 13⁄4
Љ
ft-in.
mm
ft-in.
mm
ft-in.
62L
Љ
6325 20Ј-9Љ
6649 21Ј-93⁄4
Љ
13 011 42Ј-81⁄4
13 297 43Ј-71⁄2
Љ
Љ
14 256 46Ј-91⁄4
14 542 47Ј-81⁄2
Љ
Љ
70M
Љ
NOTES:
Sides — 6Ј-0Љ
1. Dimensions in [ ] are in millimeters.
Economizer End — 6Ј-0Љ (Except power exhaust units 10Ј-0Љ).
Control Box End — 6Ј-0Љ
2.
Center of gravity. Use appropriate column for units with or without
exhaust fan option.
For smaller service and operational clearances, contact Carrier Application
Engineering department.
5. Downshot ducts designed to be attached to accessory roof curb. If unit is
mounted on dunnage, it is recommended the ducts be supported by cross
braces as done on the accessory roof curb.
3. Unit weight does not include exhaust fan option.
Exhaust fan add: 1675 lb [761 kg] on 62L
1775 lb [807 kg] on 70M
4. Unit clearances:
Top — Do not restrict condenser fans.
6. All lifting lugs must be used when rigging unit.
Fig. 5 — Base Unit Dimensions, 50MP62L and 70M
11
Download from Www.Somanuals.com. All Manuals Search And Download.
WEIGHT
C1
C2
UNIT
SIZE
50MP
A
B
D
E
F
(See Note 3)
(See Note 2)
(See Note 2)
lb
kg
mm
ft-in.
mm
ft-in.
mm
ft-in.
mm
7180 23Ј-611⁄16Љ 1753 5Ј-9Љ
7787 25Ј-69⁄16Љ 1765 5Ј-91⁄2
7793 25Ј-613⁄16Љ 1759 5Ј-91⁄4
ft-in.
mm
ft-in.
mm
ft-in.
mm
ft-in.
82N
90P
10R
22,400 10 295 3646 11Ј-119⁄16Љ
—
—
6702 21Ј-117⁄8
6Ј- 45⁄16Љ 2572 8Ј-51⁄4 7383 23Ј-103⁄4
6Ј- 45⁄16Љ 2572 8Ј-51⁄4 7383 23Ј-101⁄8
Љ
13 957 45Ј-91⁄2
14 821 48Ј-71⁄2
14 821 48Ј-71⁄2
Љ
Љ
Љ
15 202 49Ј-101⁄2
16 066 52Ј-81⁄2
16 066 52Ј-81⁄2
Љ
24,750 11 375 1938
25,100 11 536 1938
Љ
Љ
Љ
Љ
NOTES:
Sides — 6Ј-0Љ
1. Dimensions in [ ] are in millimeters.
Economizer End — 6Ј-0Љ (Except power exhaust units 10Ј-0Љ).
Control Box End — 6Ј-0Љ
2.
Center of gravity. Use appropriate column for units with or without ex-
For smaller service and operational clearances, contact Carrier Application
Engineering department.
haust fan option.
3. Unit weight does not include exhaust fan option.
Exhaust fan add: 2275 lb [1034 kg] on 82N
5. Downshot ducts designed to be attached to accessory roof curb. If unit is
mounted on dunnage, it is recommended the ducts be supported by cross
braces as done on the accessory roof curb.
2300 lb [1090 kg] on 90R and 10R
4. Unit clearances:
Top — Do not restrict condenser fans.
6. All lifting lugs must be used when rigging unit.
Fig. 6 — Base Unit Dimensions, 50MP82N-10R
12
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTICE TO RIGGERS
A
WEIGHT
B
C
D
E
UNIT
SIZE
Unit 48MP
lb kg
Unit 50MP
Exhaust Fan
lb kg
lb
kg
in.
mm
in.
mm
in.
mm
in.
mm
in.
mm
N/A
N/A
N/A
62L 16,810
70M 18,060
7 624 16,550
8 190 17,800
7 507 1675
8 074 1775
760 71.25 1810 129.00 3277 112.44 2856 138.00 3505
805 71.25 1810 129.00 3277 112.44 2856 143.56 3646
1032 71.25 1810 139.56 3545 127.87 3248 143.56 3646
N/A
N/A
N/A
82N 22,660 10 295 22,400 10 161 2275
90P 24,660 11 203 24,750 11 227 2400
10R 25,110 11 408 25,100 11 385 2400
1089 71.25 1810 139.56 3545 127.87 3248 177.56 4510 101.25 2572
1089 71.25 1810 139.56 3545 127.87 3248 177.56 4510 101.25 2572
NOTE: All lifting lugs must be used when rigging with eight or ten
cables and spread with four or five 95 in. (2413 mm) and two
‘‘B + C + D’’ long suitable spreader bars. Unit weight does not include
exhaust fan option.
1. All panels must be in place when rigging.
2. Unit is not designed for handling by fork truck.
Fig. 7 — Rigging Label
2
3
B
4
1
A
CORNER WEIGHT (lb)
DIMENSIONS (ft-in.)
CORNER WEIGHT (lb)
DIMENSIONS (ft-in.)
UNIT
48MP
UNIT
50MP
1
2
3
4
A
B
1
2
3
4
A
B
62L
70M
82N
90P
10R
5095 5000 4339 4051
5337 5338 5290 3969
6614 6326 6444 5651
7156 6789 7330 6226
7174 6897 7345 6254
19- 45⁄8
20- 23⁄4
22- 11⁄8
23-103⁄4
23-101⁄8
3-113⁄8
4- 13⁄4
5- 9
5- 91⁄2
5- 91⁄4
62L
70M
82N
90P
10R
4237 3967 5038 4933
5258 3955 5185 5167
6351 5571 6574 6279
7211 6132 7045 6761
7288 6196 7195 6820
19- 31⁄2
20- 23⁄4
21-117⁄8
23-103⁄4
23-101⁄8
3-113⁄8
4- 13⁄4
5- 9
5- 91⁄2
5- 91⁄4
Fig. 8 — Unit Center of Gravity and Corner Weights
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Field Electrical Connections
IMPORTANT: The 48/50MP units generate, use, and
can radiate radio frequency energy. If units are not in-
stalled and used in accordance with these instructions,
they may cause radio interference. They have been tested
and found to comply with limits of a Class A com-
puting device as defined by FCC (Federal Communi-
cations Commission) regulations, Subpart J of Part 15,
which are designed to provide reasonable protection
against such interference when operated in a commer-
cial environment.
UNIT
BASE
RAIL
PITCH DRAIN LINE
TO OFFSET LINE
FRICTION
SEALANT
SLAB
2" MIN.
7" MIN.
SLAB MOUNT DRAIN
Fig. 9 — Condensate Drain Piping Details
POWER WIRING — Units are factory wired for 460-v as
shown on the unit nameplate. The main terminal block is
suitable for use with aluminum or copper wires. Maximum
wire size is 500 MCM.
Branch circuit for power supply to unit must be protected
against ground fault or short circuit. Provide an overcurrent
protection device in the branch circuit. The MOCP (Maxi-
mum Overcurrent Protection) value for this device is shown
on unit informative data plate.
Make Electrical Connections
POWER SUPPLY — Electrical characteristics of available
power supply must agree with unit nameplate rating. Supply
voltage must be within the limits shown in Table 5.
When installing units, provide and install a unit safety dis-
connect per NEC of adequate size. Refer to Electrical Data
tables for disconnect sizing. Disconnect may incorporate branch
circuit fusing (if local or national codes permit) but combi-
nation disconnect fuse is not required. Disconnect must be
able to be locked OFF.
Field Wire Routing — Field wiring is brought into the unit
through the bottom of the control box.
A 35⁄8-in. hole for field power wiring and a 7⁄8-in. hole for
24-v control wiring are provided in the bottom of the control
box. Field-supplied couplings must be used when routing wir-
ing into the control box.
HOOD
TOP
FILTER
RACK
HOLD
DOWN
BARS
HOOD
SIDE
BLOCK-OFF
PLATE
Fig. 10 — Outdoor Air Hoods Shipping Position
Fig. 11 — Outdoor Air Hoods Installed
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Disconnect must be located within sight of the unit and read-
ily accessible from the unit in compliance with NEC
Article 440-14.
This amount of phase imbalance is satisfactory as it is be-
low the maximum allowable 2%.
All field wiring must comply with NEC and all local codes.
Size wire based on MCA (Minimum Circuit Amps) value
shown on the unit informative plate. See Fig. 12 for power
wiring connections to the unit power terminal block and equip-
ment ground.
Operating voltage to the compressor must be within the volt-
age range indicated on the unit nameplate. Voltages between
phases must be balanced within 2%, and the current must be
balanced within 10%. See Table 5 for unit electrical data.
IMPORTANT: If the supply voltage phase imbalance
is more than 2%, contact local utility immediately.
Unit failure as a result of operation on improper line volt-
age or excessive phase imbalance constitutes abuse and may
cause damage to electrical components.
Use the following formula to determine the percent voltage
imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
LEGEND
EQUIP
GND
NEC
TB
—
—
—
—
Equipment
Ground
National Electrical Code
Terminal Block
452 + 464 + 455
Average Voltage =
3
1371
Fig. 12 — Field Power Wiring Connections
=
3
457
=
Determine maximum deviation from average voltage:
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance:
7
% Voltage Imbalance = 100 x
457
= 1.53%
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 5 — Electrical Data
CONDENSER
FAN
POWER
EXHAUST
FAN MOTOR
VOLTAGE
RANGE
COMP
NO. A1
COMP
NO. A2
COMP
NO. B1
COMP
NO. B2
EVAPORATOR
FAN MOTOR
UNIT
48MP/
50MP
VOLTAGE
3 Ph, 60 Hz
MCA MOCP
MOTORS
Min Max RLA LRA RLA LRA RLA LRA RLA LRA Qty FLA Hp
FLA
Hp
FLA
—
11
40
—
11
40
—
11
40
—
11
52
—
11
52
—
11
52
—
11
52
—
11
52
—
11
52
—
14
65
—
14
65
—
14
65
—
14
77
—
14
77
—
14
77
Hp
—
207.0
218.0
247.0
219.0
230.0
259.0
232.0
243.0
272.0
235.0
246.0
287.0
248.0
259.0
300.0
262.9
273.9
314.9
250.2
261.2
302.2
266.5
277.5
318.5
281.5
292.5
333.5
288.5
302.5
353.5
303.5
317.5
368.5
327.5
341.5
392.2
307.2
321.1
387.1
322.1
336.1
399.1
345.8
359.8
422.8
250
250
300
250
250
300
250
300
300
300
300
350
300
300
350
300
350
350
300
300
350
300
300
350
350
350
400
350
350
350
350
350
400
400
400
450
350
350
450
350
400
450
400
450
500
40
30
7.5
30
—
62L
70M
82N
90P
10R
460
460
460
460
414 508 65.4 345
—
—
65.4 345
—
—
6
6
6
8
8
3.3
3.3
3.3
3.3
3.3
1
1
1
1
1
52
65
52
65
77
52
65
77
65
77
96
65
77
96
40
50
40
50
60
40
50
60
50
60
75
50
60
75
7.5
30
—
7.5
30
—
7.5
40
—
414 508 46.8 253 34.6 173 65.4 345
—
—
7.5
40
—
7.5
40
—
7.5
40
—
414 508 43.6 223 34.6 173 43.6 223 43.6 223
414 508 43.6 223 46.8 253 43.6 223 46.8 253
414 508 43.6 223 65.4 345 43.6 223 46.8 253
7.5
40
—
7.5
40
—
10
50
—
10
50
—
10
50
—
15
60
—
460
15
60
—
15
60
LEGEND
COMP
FLA
—
Compressor
—
—
—
—
—
—
Full Load Amps
Hp
Nominal Horsepower
Locked Rotor Amps
Minimum Circuit Amps (for wire sizing)
Maximum Overcurrent Protection
Rated Load Amps
LRA
MCA
MOCP
RLA
16
Download from Www.Somanuals.com. All Manuals Search And Download.
pins E2 and E3, and an RJ11 female connector. The RJ11
connector is used to tap into the CCN at the sensor. See RJ11
Plug Wiring section on page 24 to connect the RJ11 con-
nector to the CCN.
Control Wiring — See Fig. 13 for sensor wiring con-
nections to main and auxiliary control boxes. The recom-
mended types of control wiring for 48/50MP unit devices
are shown in Table 6.
Table 6 — Recommended Sensor and
Device Non-Shielded Cable
Jumper MUST be in place between pins E2 and E3 or
inaccurate readings could result.
PART NO.
MANUFACTURER
To connect the space temperature sensor (Fig. 13):
Regular Wiring
1895
Plenum Wiring
Alpha
American
Belden
—
A48301
884421
—
1. Connect one wire of the 3-conductor cable to terminal
TH, one wire to terminal COM, and the other wire to ter-
minal SW on terminal block 1 (TB1) located on the cover
of the space temperature sensor using a 20 AWG twisted
3-conductor cable rated for the application.
A21451
8205
Columbia
Manhattan
Quabik
D6451
M13402
6130
M64430
—
2. Connect the other ends of the wires to terminals 1, 2, and
3 on TB3 located in the unit main control box. The wire
from terminal SW MUST be connected to terminal 3.
SENSORS — Sensors should be wired using single twisted
pairs of 20AWG (American Wire Gage) conductor cable rated
for the application, except for the T56 accessory sensor which
requires 3-conductor cable.
NOTE: Either the T55 or the T56 sensor must be con-
nected for CV applications to function properly.
SPACE TEMPERATUREAVERAGING —Applications that
require averaging using multiple space temperature sensors
can be satisfied using either 4 or 9 sensors as shown in
Fig. 14.
NOTE: Humidity and CO2 sensors must be powered from
isolated 24-v power supplies.
HUMIDITY CONTROLAND HOT WATER AND STEAM
VALVES — These devices require 20 AWG twisted pair con-
ductor cables rated for the application for the 4 to 20 mA
signal.
NOTE: Only Carrier sensors may be used for standard T55
space averaging. Sensors must be used in multiples of 1, 4,
and 9 only, with total sensors wiring not to exceed 1000 ft.
However, space temperature reset can be accomplished with
only one sensor.
SPACE TEMPERATURE SENSOR (T55) — The space tem-
perature sensor (P/N CEC0121448-01) is shipped standard
with every unit, and is located in the main control box. Space
temperature sensor wires are to be connected to terminals in
the unit main control box. The space temperature sensor
includes a terminal block (TB1), a jumper between pins E2
and E3, and an RJ11 female connector. The RJ11 connector
is used to tap into the Carrier Comfort Network (CCN) at
the sensor. See RJ11 Plug Wiring section on page 24 to con-
nect the RJ11 connector to the CCN. A 3-lead cable must
run from the RJ11 connector to the unit for communication
through the sensor.
NOTE: Do not use T56 sensors for space temperature
averaging because the 5 degree offset function will not work
in a multiple sensor application.
HEAT INTERLOCK RELAY (VAV Units Only — Not Nec-
essary For Digital Air Volume Applications) — Variable air
volume (VAV) units using optimal start (morning warm-up)
and/or occupied heating require that room terminals be con-
trolled to the fully open position when the unit goes into
heating mode. The HIR (Heat Interlock Relay) function is
provided for this control on DSIO no. 2, channel 60. When
the unit goes into heating mode, the HIR is energized to pro-
vide switch closure or opening (depending on how the field-
supplied power source is set up) to open the room terminals.
The field connections for the HIR are: Normally Closed, ter-
minals 8 and 10 on TB3; and Normally Open, terminals 8
and 9 on TB3. See Fig. 15.
Jumper MUST be in place between pins E2 and E3 or
inaccurate readings could result.
To connect the space temperature sensor (Fig. 13):
OPTION AND ACCESSORY CONTROL WIRING — The
48/50MP units may be used in applications with additional
control features, options, or accessories. Refer to the Con-
trols and Troubleshooting manual for more information con-
cerning installation and configuration of options and acces-
sories. Figures 15 to 29 contain wiring information on the
following features:
• heat interlock relay (Fig. 15)
• differential enthalpy sensor (Fig. 16)
• remote start (Fig. 17)
• accessory humidity control (Fig. 18)
• fire/smoke control (Fig. 19)
• indoor air quality (Fig. 20)
• outdoor airflow control (Fig. 21)
• timed discrete output (Fig. 22)
• humidifier (Fig. 23)
• hydronic heating (Fig. 24)
• freezestat (Fig. 25)
• remote supply air temperature/space temperature offset
(Fig. 26)
• transducer/thermistor (Fig. 27)
• CCN Building Supervisor (Fig. 28)
• variable frequency drive (VFD) (Fig. 29)
1. Connect 1 wire of the twisted pair to terminal T1 (T55)
and connect the other wire to terminal T2 on terminal
block 1 (TB1) located on the cover of the space tempera-
ture sensor using a 20 AWG twisted pair conductor cable
rated for the application.
2. Connect the other ends of the wires to terminals 1 and 2
on TB3 located in the unit main control box.
NOTE: This sensor should be installed for all applica-
tions. For VAV (variable air volume) applications, it is
used to control heating and cooling during unoccupied
periods. For DAV (digital air volume) applications, it is
used to maintain control of the space during linkage fail-
ures with the TSM (terminal system manager).
NOTE: Either the T55 or T56 sensor must be connect-
ed for CV (constant volume) applications to function
properly.
SPACE TEMPERATURE SENSOR (T56) (CV Applica-
tions Only)
—
The space temperature sensor
(P/N CEC0121503-01) wires are to be connected to termi-
nals in the unit main control box. The space temperature
sensor includes a terminal block (TB1), a jumper between
17
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
COM
SW
T
TB
TH
—
—
—
—
—
Common
Switch
Terminal
Terminal Block
Thermostat Heating
Accessory
Field Wiring
*Constant volume applications only.
Fig. 13 — Space Temperature Sensor Wiring
18
Download from Www.Somanuals.com. All Manuals Search And Download.
RED
BLK
RED
BLK
TB3
1
RED
BLK
RED
BLK
RED
BLK
2
TO PROCESSOR
MODULE NO. 1
SENSOR 1
SENSOR 2
SENSOR 3
SENSOR 4
SPACE TEMPERATURE AVERAGING — 4 SENSOR APPLICATION
TB3
RED
RED
BLK
RED
BLK
1
2
BLK
TO PROCESSOR
MODULE NO. 1
SENSOR 1
SENSOR 2
SENSOR 3
RED
BLK
RED
BLK
SENSOR 4
SENSOR 5
SENSOR 6
RED
BLK
RED
BLK
LEGEND
TB
—
Terminal Block
Factory Wiring
Field Wiring
SENSOR 7
SENSOR 8
SENSOR 9
SPACE TEMPERATURE AVERAGING — 9 SENSOR APPLICATION
Fig. 14 — Space Temperature Sensor Averaging
19
Download from Www.Somanuals.com. All Manuals Search And Download.
FIELD-SUPPLIED
24-V ISOLATED
POWER SUPPLY
ACCESSORY
DSIO2
J5
OUTSIDE AIR
RELATIVE HUMIDITY
FIELD
CONTROL
WIRING
TB3
7
TB3
8
12
11
10
RED
BLU
ORN
2
1
1
2
24V
J1
J1
J2
J2
12
13
15
9
FIELD-SUPPLIED
24-V ISOLATED
POWER SUPPLY
10
1
2
CHANNEL
60
1
2
24V
LEGEND
SPACE/RETURN
RELATIVE HUMIDITY
TB
—
Terminal Block
Field Wiring
Component Terminal
LEGEND
— Terminal Block
□
Terminal Block Terminal
TB
Field Wiring
Fig. 15 — Heat Interlock Relay
Component Terminal
Terminal Block Terminal
□
Fig. 18 — Accessory Humidity Control
ENTHALPY
CONTROL
ENTHALPY
SENSOR
J7
TB2
6
PRESSURIZATION
19
PURGE
22
S
+
SR
+
EVACUATION
25
REMOVE
620 Ω
SHUTDOWN
28
RESISTOR
PSIO
NO. 2
LEGEND
DIFFERENTIAL
ENTHALPY SENSOR
(RETURN AIR)
TB
—
Terminal Block
Field Wiring
Component Terminal
Fig. 16 — Differential Enthalpy Sensor
□
Terminal Block Terminal
Fig. 19 — Fire/Smoke Control
FIELD-SUPPLIED
24-V ISOLATED
POWER SUPPLY
24V
J7
LEGEND
+
16
9
1
DSIO
—
Relay Module
INDOOR AIR
QUALITY ACY
Fig. 17 — Remote Start
17
10
-
5
PSIO
NO. 2
Fig. 20 — Indoor Air Quality
20
Download from Www.Somanuals.com. All Manuals Search And Download.
OUTDOOR
AIR
TB2
PSIO
NO. 2
TO 24-V
+
24V
BRN
RED
9
J6
37
38
ISOLATED
-
24V
10
TRANSFORMER
CFM ACY
+
-
LEGEND
HYD VLV
TB
—
Terminal Block
Field Wiring
HYDRONIC VALVE
ACTUATOR
Component Terminal
□
Terminal Block Terminal
LEGEND
Fig. 21 — Outdoor Airflow Control
TB
—
Terminal Block
Field Wiring
Component Terminal
Fig. 24 — Hydronic Heating
PSIO
NO. 2
J7
31
6
Fig. 22 — Timed Discrete Output
TB2
LEGEND
TB
—
Terminal Block
Field Wiring
PSIO
NO. 2
J6
Component Terminal
□
Terminal Block Terminal
+ 43
HUMIDIFIER
HUM VLV
HHR
ACTUATOR
Fig. 25 — Freezestat
-
44
45
HUMIDIFIER
RELAY
+
CARRIER PART NO.
HK35AA001
LEGEND
TB
—
Terminal Block
Field Wiring
Component Terminal
Fig. 23 — Humidifier
LEGEND
CV
VAV
—
—
Constant Volume
Variable Air Volume
Fig. 26 — Remote Supply Air Temperature
Reset/Space Temperature Offset
21
Download from Www.Somanuals.com. All Manuals Search And Download.
PSIO NO. 1
J7
TRANSDUCER ACCESSORY
_
BLK
DPT1
DPT2
WHT
WHT
BRN
BRN
7
8
WHT
WHT
RES
BLK
+
_
RED
BLK
10K OHM
1/2 WATT
+
5%
-
RED
WHT
10
11
WHT
RES
+
_
RED
BLK
10K OHM
1/2 WATT
+
5%
-
BLK
BLK
SPT1
SPT2
WHT
WHT
13
14
RES
+
_
RED
BLK
BLK
BLK
10K OHM
1/2 WATT
+
5%
-
RED
WHT
WHT
16
17
RES
+
RED
BLK
10K OHM
1/2 WATT
4
TB3
5
+
5%
-
RED
J7
2
PSIO NO. 2
6
7
SUCTION GAS
TEMPERATURE
THERMISTOR
1
CHANNEL 31
CHANNEL 32
3
LEGEND
SUCTION GAS
TEMPERATURE
THERMISTOR
DPT
SPT
TB
—
—
—
Duct Pressure
Transducer
5
6
2
Suction Pressure
Transducer
Terminal Block
Fig. 27 — Transducer/Thermistor
PSIO
NO. 1
COMM
1
2
3
1
2
3
RED
GRN
BLK
CCN NETWORK
_
_
LEVEL II
COMMUNICATIONS
BUS (COMM)
4
COMM 1
Fig. 28 — CCN Building Supervisor
22
Download from Www.Somanuals.com. All Manuals Search And Download.
VFD
PEC (EXHAUST)
IFC (SUPPLY)
PECB (EXHAUST)
IFCB (SUPPLY)
T1
L1
(R)
L1
EFM
(EXHAUST)
IDFM
(SUPPLY)
T2
T3
L2
L3
(S)
(T)
L2
L3
GROUND
460V
SHIELD
G
VOLTAGE
SELECTOR
(SUPPLY)
PSIO1
J6
S1
CHANNEL 16
1
3
+
-
46
FI
IFR (SUPPLY
PER (EXHAUST)
FC
47
SC
LEGEND
(EXHAUST)
PSIO1
EFM
IDFM
IFC
—
Exhaust Fan Motor
Indoor Fan Motor
Indoor Fan Contactor
Indoor Fan Circuit Breaker
Indoor Fan Relay
Power Exhaust Contactor
Power Exhaust Circuit Breaker
Power Exhaust Relay
Variable Frequency Drive
—
—
—
—
—
—
—
—
J6
CHANNEL 15
IFCB
IFR
43
44
+
PEC
PECB
PER
VFD
-
Fig. 29 — Optional VFD — Wiring Connections
outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon
with a minimum operating temperature range of Ϫ20 C to
60 C is required. See Table 7 for cables that meet the
requirements.
Carrier Comfort Network Interface — The
48/50MP units can be connected to the CCN if desired. The
communication bus wiring is supplied and installed in
the field. It consists of shielded, 3-conductor cable with
drain wire.
The system elements are connected to the communication
bus in a daisy chain arrangement. The positive pin of each
system element communication connector must be wired to
the positive pins of the system element on either side of it,
the negative pins must be wired to the negative pins, and the
signal pins must be wired to signal ground pins. Wiring con-
nections for CCN should be made at the 4-pin plug (COMM)
located at the bottom right side of the fuse bracket in the
main control box. Consult CCN Contractor’s Manual for fur-
ther information.
Table 7 — CCN Connection Approved
Shielded Cables
MANUFACTURER
Alpha
CABLE PART NO.
2413 or 5463
A22503
American
Belden
8772
Columbia
02525
IMPORTANT: When connecting the CCN communi-
cation bus to a system element, use a color coding sys-
tem for the entire network to simplify installation and
checkout.
NOTE: Conductors and drain wire must be 20 AWG mini-
mum stranded, tinned copper. Individual conductors must
be insulated with PVC, PVC/nylon, vinyl, Teflon, or poly-
ethylene. An aluminum/polyester 100% foil shield and an
23
Download from Www.Somanuals.com. All Manuals Search And Download.
The following color code is recommended:
RJ11 PLUG WIRING — Units on the CCN can be moni-
tored from the space at the sensor through the RJ11 con-
nector, if desired. To wire the RJ11 connector into the CCN
(Fig. 30):
SIGNAL
TYPE
CCN BUS CONDUCTOR
INSULATION COLOR
COMM1 PLUG
PIN NO.
ϩ
GROUND
Ϫ
RED
1
2
3
WHITE
BLACK
IMPORTANT: The cable selected for the RJ11 con-
nector wiring MUST be identical to the CCN com-
munication bus wire used for the entire network. Re-
fer to Table 7 for acceptable wiring.
NOTE: If a cable with a different color scheme is selec-
ted, a similar color code should be adopted for the entire
network.
At each system element, the shields of its communication
bus cables must be tied together. If the communication
bus is entirely within one building, the resulting continuous
shield must be connected to a ground at one point only. If
the communication bus cable exits from one building and
enters another, the shields must be connected to grounds at
the lightning suppressor in each building where the cable
enters or exits the building (one point per building only).
To connect the unit to the network:
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (ϩ), white
(ground) and black (Ϫ) conductors. (If a different net-
work color scheme is used, substitute appropriate
colors.)
1. Cut the CCN wire and strip ends of the red (ϩ), white
(ground), and black (Ϫ) conductors. (If another wire color
scheme is used, strip ends of appropriate wires.)
2. Insert and secure the red (ϩ) wire to pin J2 (T-55) or CCN
+ (T-56) of the space temperature sensor terminal block
(TB1).
3. Insert and secure the white (ground) wire to pin J3 (T-55)
or CCN GND (T-56) of the space temperature sensor TB1.
4. Insert and secure the black (Ϫ) wire to pin J5 (T-55) or
CCN − (T-56) of the space temperature sensor TB1.
5. Connect the other end of the communication bus cable to
the remainder of the CCN communication bus at the
COMM1 plug located on the fuse and control circuit breaker
bracket in the unit main control box.
3. Remove the 4-pin female plug from the fuse and control
circuit breaker bracket in the main control box, and con-
nect the wires as follows:
Air Pressure Tubing — Before options such as supply
fan VFD and modulating power exhaust can operate prop-
erly, the pneumatic tubes for pressure sensing must be in-
stalled. The recommended field-supplied tubing for this use
a. Insert and secure the red (ϩ) wire to terminal 1 of the
4-pin plug.
1
is a nominal ⁄4-in., fire-retardant tubing.
b. Insert and secure the white (ground) wire to terminal
2 of the 4-pin plug.
The tubing must be run from the appropriate location
in the building to the auxiliary control box in the unit.
Figures 31 and 32 show the location and layout of the
auxiliary control box in the 48/50MP unit. Figure 33 shows
the connection locations for the tubing on the duct pressure
(DP) controller for the VFD on the supply fan and on the
building pressure (BP) controller for the VFD on the modu-
lating power exhaust fan.
c. Insert and secure the black (Ϫ) wire to terminal 3 of
the 4-pin plug.
4. Insert the plug into the existing 4-pin mating connector
on the fuse or control circuit breaker bracket in the main
control box.
IMPORTANT: A shorted CCN bus cable will pre-
vent some routines from running and may prevent
unit from starting. If abnormal conditions occur, un-
plug the connector. If conditions return to normal,
check CCN connector, and run new cable if nec-
essary. A short in one section of the bus can cause
problems with all system elements on the bus.
The tubing for the duct pressure control (DP) should sample
2
supply duct pressure about ⁄3 of the way out from the unit
in the main trunk duct. The tubing for the building pressure
control (BP) should sample building pressure in the area near
the entrance lobby so that location is controlled as closely to
design pressures as possible.
LEGEND
CCN
—
—
—
—
Carrier Comfort Network
Common
Communications
Ground
COM
COMM
GND
*Constant volume applications only.
Fig. 30 — Space Sensor to Communication Bus Wiring
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 31 — Auxiliary Control Box Location
(50MP70M Unit Shown)
VARIABLE
FREQUENCY
DRIVE
BPC
DPC
DUCT PRESSURE
TRANSDUCER
HI
LO
HI
LO
TO
BUILDING
PRESSURE
BUILDING PRESSURE
TRANSDUCER
(HIDDEN)
FACTORY
INSTALLED
TUBING
TO SUPPLY
DUCT
FIELD
INSTALLED
TUBING
TO OUTDOOR
REFERENCE
PRESSURE
PORT
LEGEND
BPC
DPC
—
—
Building Pressure Controller
Duct Pressure Controller
Fig. 33 — Air Pressure Tubing Locations
Fig. 32 — Auxiliary Control Box
25
Download from Www.Somanuals.com. All Manuals Search And Download.
INLET HOOD
(62L AND 70M
SIZES ONLY)
GAS HEAT
SECTION
PANEL
Gas Piping (48 Series Units Only) — Unit is equipped
for use with natural gas only. Installation must conform with
local building codes, or in the absence of local codes, with
the National Fuel Gas Code, ANSI Z223.1.
A 1⁄8-in. NPT tapping plug, accessible for test gage con-
nection, must be field installed immediately upstream of gas
supply connection to unit, but after manual gas valve. See
Fig. 34. Natural gas pressure at unit gas connection must not
be less than 5 in. wg or greater than 13 in. wg.
FLUE HOOD
AND FLUE
DEFLECTOR
HOOD
Size gas supply piping for 0.5 in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas
connection.
Disconnect gas piping from unit when leak testing at
pressures greater than 0.5 psig. Pressures greater than
0.5 psig will cause gas valve damage resulting in a haz-
ardous condition. If gas valve is subjected to pressure
greater than 0.5 psig, it must be replaced.
HIGH HEAT
UNITS ONLY
Installing Flue/Inlet Hoods (48MP Units Only)
— The flue/inlet hoods are shipped in a bag taped to the
Fig. 35 — Flue and Inlet Hood Locations
(48MP Units Only)
basepan in the gas section of the unit.
UNITS SIZES 62LAND 70M — The high heat units (48MPE),
have 3 flue hoods, 3 flue deflector hoods, and one inlet air
hood to be field installed. See Fig. 35. The low heat units
(48MPD) have 2 flue hoods, 2 flue deflector hoods, and one
inlet air hood.
INLET HOOD
Remove the shipping block offs and shipping tape from
the flue openings in the access panel and the corner post.
The inlet hood is shipped unassembled and must be as-
sembled before mounting to the access panel. See Fig. 36.
Install inlet screen on inlet hood using speed clips and screws
provided.
Attach the flue hoods to access panel and corner post us-
ing screws provided. See Fig. 37. Hoods go over each com-
bustion air outlet.
INLET HOOD
SIDE PLATE
(TYP EACH SIDE)
Install the flue deflector baffle inside the flue deflector hood.
See Fig. 38. Install flue deflector hoods over each flue hood.
UNIT SIZES 82N, 90P, and 10R — The high heat units
(48MPE), have 3 flue hoods and 3 flue deflector hoods to be
field installed. See Fig. 35. The low heat units (48MPD),
have 2 flue hoods and 2 flue deflector hoods.
Remove the shipping block offs and shipping tape from
the flue openings in the access panel and the corner post.
Fig. 36 — Inlet Hood Assembly
Attach the flue hoods to access panel and corner post us-
ing screws provided. See Fig. 37. Hoods go over each com-
bustion air outlet.
Install the flue deflector baffle inside the flue deflector hood.
See Fig. 38. Install the flue deflector hoods over each flue
hood.
Fig. 37 — Flue Hood
*NPT plug is field supplied.
NOTE: Follow all local codes.
Fig. 34 — Gas Piping Details
26
Download from Www.Somanuals.com. All Manuals Search And Download.
FLUE DEFLECTOR
BAFFLE
FLUE
DEFLECTOR
HOOD
Check Compressor Mounting
PUSH
UNITS 48/50MP62L — Compressors are mounted on pans
and are held down by 4 rail bolts during shipment. After unit
is installed, loosen each of these bolts until the snubber washer
can be moved with finger pressure. See Fig. 40 and 41.
BAFFLE
DOWN SO
THESE 2
HOLES
ALIGN
UNITS 48/50MP70M-10R — Compressors are mounted on
rails and held down by rail bolts during shipment. After unit
is installed, loosen the rail bolts to allow the rails and com-
pressors to float freely on the springs located under the rails.
See Fig. 40, 42, and 43.
Install Accessories — For applications requiring
special accessories, the following packages are available: con-
denser coil hail guard package, condenser coil protective
grilles, and compressor security grilles. Refer to the acces-
sory installation instructions for information on accessory
installation.
TOP (WHEN INSTALLED)
Fig. 38 — Flue Deflector Baffle (Assembled)
Fan Isolator Adjustment — Remove shipping hard-
ware from both the supply fan and the optional exhaust fan.
The indoor fan shipping blocks on both the supply fan and
the optional power exhaust fan (4 per fan) must be removed
from each corner of the fan sled before starting unit. Re-
move shipping bolt connecting bottom flanges of the fan sled
crossrail with the fan support rail. Remove the wooden ship-
ping block from each corner. See Fig. 39.
FAN SLED
ADJUSTING BOLT
CROSS RAIL
FAN SUPPORT
RAIL
7"
SHIPPING
BOLT
After removing all shipping blocks, level fan sled using
the adjusting screws of the spring isolators. Verify dimen-
sions from fan support rail to fan sled cross rail of 7-in. on
all 4 corners.
To adjust, loosen the locknut on top of the adjusting bolt.
Turn the bolt clockwise to decrease the height. Turn the bolt
counterclockwise to increase the height. Tighten the locknut
after adjustment is complete. Make sure that the fan sled
assemblies float freely during and after adjustment.
ISOLATOR SPRING
METAL SHIPPING
BLOCK
VIEW FROM INSIDE UNIT LOOKING OUT
Fig. 39 — Fan isolator Adjustment
MOUNTING SPRINGS
SHIPMENT BOLTS
SHIPMENT BOLTS
48/50MP62L
MOUNTING
BOLTS
MOUNTING
BOLTS
RAIL BOLT (3) (2 SHOWN)
RAIL BOLT (3) (2 SHOWN)
48/50MP70M-10R
Fig. 40 — Outer View, Compressor Mounting
27
Download from Www.Somanuals.com. All Manuals Search And Download.
PRE-START-UP
IMPORTANT: Before beginning Pre-Start-Up or Start-
Up, review Start-Up Checklist at the center of this
publication. The Checklist assures proper start-up of a
unit and provides a record of unit condition, applica-
tion requirements, system information, and operation
at initial start-up.
Do not attempt to start the air-conditioning system until
following checks have been completed.
System Check
1. Check the outside air hoods to ensure the hoods are fully
opened and secure, with filters in place.
2. Check the supply fan and exhaust fan suspension brack-
ets. Shipping spacers should be removed and sleds
levelled to specification.
Fig. 41 — Compressor Mounting —
48/50MP62L Units
3. Check compressor suspension. On 48/50MP62L units
snubber washers can be moved with finger pressure. On
all other units, rails allow compressors to float freely on
compressor rail springs.
4. Electrical power source must agree with unit
nameplate.
5. Check tightness of all electrical connections.
Failure to open discharge service valve prior to start-
ing compressor can result in damage to or failure
of the compressor.
6. Backseat (open) compressor suction and discharge shut-
off valves. Close valves one turn to allow refrigerant pres-
sure to reach the test gages.
7. Open liquid line service valves.
8. Oil should be visible in the compressor sight glasses.
See Fig. 44. An acceptable oil level in the compressor
is from 3⁄8 to 1⁄8 of sight glass (06E-299 compressors are
1
⁄8
of sight glass). Adjust the oil level as required. No oil
should be removed unless the crankcase heater has been
energized for at least 24 hours. Oil Charge section on
page 49 for Carrier-approved oils.
Fig. 42 — Front View of Compressor Mounting
Rail Assembly — 48/50MP70M-10R Units
9. Perform leak test. Be sure there are no refrigerant leaks.
All units are shipped with a complete operating charge
of R-22 and should be under sufficient pressure for leak
testing after installation. If there is no system pressure,
add refrigerant until a pressure is observed and check
for leaks. After leaks are repaired, remove and recover
refrigerant from system. For leak testing procedures, see
GTAC 2, Module 5, Charging, Recovery, Recycling and
Reclamation section. Do not use the system compres-
sors to remove refrigerant from the system.
COMPRESSOR MOUNTING FOOT
10. Crankcase heaters must be firmly locked into compres-
NUT
sors, and must be on for 24 hours prior to start-up.
COMPRESSOR MOUNTING RAIL
Crankcase heaters on all units are wired into the
control circuit, so they are always operable as long
as the main power supply disconnect is on (closed),
even if any safety device is open. Compressor heat-
ers must be on for 24 hours prior to the start-up of
any compressor.
Fig. 43 — Rear View of Compressor Mounting
Rail Assembly — 48/50MP70M-10R Units
28
Download from Www.Somanuals.com. All Manuals Search And Download.
11. Check supply fan belts, sheaves, and bearings. Check
the lubrication of the fan and motor bearings. Check bear-
ing and bearing set screws for tightness. Check sheave
alignment and belt tension. Hand turn fan to ensure fan
wheel does not rub on housing. The fan shaft and motor
shaft must turn freely before power is applied to the unit.
12. Check exhaust fan belts, sheaves, and bearings. Check
the lubrication of the fan and motor bearings. Check bear-
ing and bearing set screws for tightness. Check sheave
alignment and belt tension. Hand turn fan to ensure fan
wheel does not rub on housing.
Observe the maximum wheel speed and unit airflow lim-
its for the specific unit size and fan type.
See Tables 8-12 for forward curve supply fan perfor-
mance. See Tables 13-17 for air foil supply fan perfor-
mance.
FAN PERFORMANCE, 48MP UNITS — To obtain fan per-
formance for 48MP units:
1. Enter fan performance table for appropriate base unit type
and unit size.
2. Determine the external static pressure from the fan per-
formance table using fan type, field-measured rpm, and
airflow (cfm).
13. Check economizer linkage. Economizer dampers should
be fully closed. Linkage should permit full and free travel.
3. Refer to the Component Pressure Drops table (Table 18)
on page 35. Calculate the adjusted external static pres-
sure value for the correct unit size and airflow for gas
heat units.
4. Calculate the net external static pressure for the gas heat
units by subtracting the adjusted external static pressure
value from Table 18 (Step 3) from the external static pres-
sure from the fan performnce table (Step 2).
14. Check that the correct return air filters are installed in
the filter tracks. Do not operate unit without return air
filters.
15. Check that all access doors on the air handler section
have been closed and secured.
16. Fan motors are 3-phase. Check rotation of fans during
first start-up check. Fan rotation is clockwise as viewed
from top of unit. If fan is not turning clockwise, reverse
2 of the power wires.
EXAMPLE:
Field Measurements:
Unit: 48MP62L
Fan Type: Forward Curved
RPM: 500
CFM: 22,000
Compressor Oil — Check that compressor oil is vis-
ible in the sight glass of the compressor. All units are factory
charged with oil. See Table 3. Observe oil level closely at
start-up. If oil level is below the sight glass and cannot
3
1
be seen, add oil until the level is approximately ⁄8 to ⁄8 of
sight glass (06E-299 compressors are 1⁄8 of sight glass). See
Fig. 44. See Oil Charge section on page 49 for information
on adding or removing oil.
1. Select Fan Performance Table 8, 48/50MP62L with For-
ward Curved fan.
2. Determine external static pressure using 500 rpm and
22,000 cfm. ESP = 1.25.
If oil charge is above sight glass, do not remove any oil
until the compressor crankcase heater has been on for at least
24 hours. When additional oil or a complete charge is needed,
use only Carrier-approved compressor oil.
Do not reuse drained oil and do not use any oil that has
been exposed to the atmosphere.
3. Read the adjusted external static pressure from the Com-
ponent Static Pressure Drops table for 48MP62L gas
heat units at 22,000 cfm. Adjusted ESP = 0.31.
4. Calculate external static pressure.
ESP = ESP − ESP Adjusted
= 1.25 − 0.31
= 0.94 in. wg
COMPRESSOR
06E
COMPRESSOR
06E-299
Check rotation of wheel with arrow on the fan housing.
Check fan speed with a strobe-type tachometer, or use this
formula:
(EXCEPT 06E-299)
motor rpm x motor sheave pitch diameter (in.)
Fan
=
1/8
Rpm
fan sheave pitch diameter (in.)
3/8
1/8
(Obtain motor rpm from the fan motor nameplate and read
sheave pitch diameters marked on the fan and motor sheaves.)
Fig. 44 — Operating Oil Levels
(Sight Glass)
EXAMPLE:
Nameplate motor rpm . . . . . . . . . . . . . . . . . . . . . . . . . 1760
Motor sheave pitch diameter (in.) . . . . . . . . . . . . . . . . . 6.4
Fan sheave pitch diameter (in.) . . . . . . . . . . . . . . . . . . 12.4
Evaporator-Fan Belts, Pulleys, and Sheaves —
Belts, pulleys, and sheaves are factory installed. All pulleys
are nonadjustable.
See Table 1 for fan shaft center distance ranges and shaft
sizes when making selections for field-supplied drives.
1760 x 6.4
Fan Rpm =
= 908 Rpm
12.4
Factory-installed drives are fixed-speed and are non-
adjustable. Refer to Table 1 for factory-supplied wheel speeds
and drive set data.
The maximum allowable fan speed for the supply fan is
shown in Table 19. The maximum allowable fan speed for
the power exhaust fan is shown in Table 20.
If different wheel speeds are required for an application,
Carrier recommends that the installer contact the nearest Brown-
ing dealer. The Browning dealer can develop the required
information for the fan drive set.
Excessive fan speed may result in condensate carryover
from the evaporator coil, fan motor overload, or wheel fail-
ure. See Table 21 for Air Quantity Limits on page 35.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 8 — Fan Performance (Forward Curved) — 48/50MP62L*
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.50
0.75
1.00
1.25
1.50
1.75
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
16,000
18,000
20,000
22,000
24,000
26,000
28,000
30,000
32,000
346
371
398
426
455
484
514
544
575
3.4
4.7
382
404
428
454
481
508
537
566
595
4.1
5.5
415
436
458
481
506
532
559
587
615
5.0
6.4
448
466
486
508
531
555
581
608
635
6.0
7.4
478
494
513
533
555
578
602
628
654
7.2
8.6
508
522
539
558
578
600
623
648
673
8.6
10.0
11.9
14.3
17.3
20.9
25.2
30.2
36.1
6.3
7.2
8.2
9.3
10.5
12.9
15.8
19.4
23.6
28.5
34.3
8.4
9.4
10.5
13.3
16.6
20.7
25.4
30.9
11.6
14.5
18.0
22.1
26.9
32.6
11.0
14.2
18.0
22.5
27.9
12.1
15.4
19.3
23.9
29.4
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
2.25 2.50
AIRFLOW
(Cfm)
2.00
2.75
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
16,000
18,000
20,000
22,000
24,000
26,000
28,000
30,000
32,000
536
549
564
582
601
622
644
667
692
10.1
11.5
13.4
15.8
18.9
22.5
26.9
32.0
38.0
563
575
589
605
623
643
664
686
710
11.9
13.2
15.1
17.5
20.6
24.3
28.7
33.9
39.9
590
600
613
628
645
664
684
705
728
13.9
15.1
16.9
19.3
22.4
26.1
30.6
35.8
42.0
615
624
636
650
666
684
703
724
746
16.0
17.1
18.9
21.3
24.3
28.1
32.6
37.9
44.1
LEGEND
Brake Horsepower
Bhp
—
*Refer to Fan Performance, 48MP Units section, for correct procedure on 48MP units.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. Conversion — Bhp to kW:
Bhp × .746
kW =
Motor efficiency
See Table 1 for motor efficiency.
Table 9 — Fan Performance (Forward Curved) — 48/50MP70M*
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.50
0.75
1.00
1.25
1.50
1.75
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
18,000
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
365
391
418
447
476
506
536
566
597
628
6.4
8.2
398
421
446
472
499
527
556
585
615
645
7.4
9.3
432
451
473
497
523
549
576
604
633
662
8.5
10.4
12.7
15.4
18.6
22.2
26.3
30.9
36.1
41.9
465
482
501
523
546
571
596
623
651
679
9.8
11.7
14.0
16.8
20.0
23.6
27.8
32.5
37.8
43.7
499
512
528
548
569
592
617
642
668
695
11.1
13.1
15.4
18.2
21.5
25.2
29.4
34.2
39.5
45.4
532
542
556
573
592
614
637
661
686
712
12.6
14.5
16.9
19.7
23.0
26.8
31.0
35.9
41.3
47.3
10.4
12.9
15.9
19.4
23.4
27.9
32.9
38.6
11.5
14.1
17.2
20.8
24.8
29.4
34.5
40.2
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
2.50 2.75
AIRFLOW
(Cfm)
2.00
2.25
300
325
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
18,000
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
565
572
583
598
616
635
657
680
704
729
14.2
16.1
18.5
21.3
24.6
28.4
32.7
37.6
43.1
49.1
598
602
610
623
639
657
677
699
722
746
16.0
17.8
20.2
23.0
26.3
30.1
34.5
39.4
44.9
51.0
631
631
638
648
662
679
697
718
740
763
17.8
19.6
21.9
24.7
28.1
31.9
36.3
41.3
46.8
53.0
664
661
665
673
685
700
717
737
757
780
19.9
21.5
23.8
26.6
29.9
33.8
38.2
43.2
48.8
55.0
696
691
692
698
708
722
737
756
775
796
22.1
23.6
25.8
28.5
31.9
35.7
40.2
45.2
50.8
57.1
729
720
719
723
731
743
758
774
793
813
24.4
25.8
27.9
30.6
33.9
37.7
42.2
47.2
52.9
59.2
LEGEND
Brake Horsepower
Bhp
—
*Refer to Fan Performance, 48MP Units section, for correct procedure on 48MP units.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. Conversion — Bhp to kW:
Bhp × .746
kW =
Motor efficiency
See Table 1 for motor efficiency.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10 — Fan Performance (Forward Curved) — 48/50MP82N*
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.50
0.75
1.00
1.25
1.50
1.75
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
42,000
293
308
324
341
358
375
393
411
430
448
467
6.2
7.6
326
339
352
367
382
398
415
432
449
467
485
7.7
9.1
359
369
380
393
407
421
436
452
468
485
502
9.3
10.8
12.6
14.6
16.8
19.4
22.3
25.5
29.1
33.0
37.3
392
399
408
419
431
444
458
473
488
504
520
11.2
12.7
14.5
16.5
18.9
21.5
24.5
27.8
31.4
35.5
39.9
425
429
436
445
455
467
479
493
507
522
537
13.2
14.7
16.6
18.7
21.1
23.8
26.8
30.2
33.9
38.1
42.6
457
459
464
471
480
490
501
513
526
540
555
15.3
16.9
18.8
20.9
23.4
26.2
29.3
32.7
36.5
40.7
45.4
9.2
10.8
12.7
14.9
17.4
20.2
23.3
26.8
30.6
34.9
11.0
13.1
15.5
18.2
21.2
24.6
28.3
32.5
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
2.25 2.50 2.75
AIRFLOW
(Cfm)
2.00
3.00
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
42,000
462
466
472
480
489
500
512
524
538
552
567
15.0
16.6
18.6
20.8
23.4
26.2
29.4
32.9
36.8
41.0
45.7
489
491
495
502
510
520
530
542
555
568
582
16.8
18.5
20.4
22.7
25.3
28.1
31.4
34.9
38.9
43.2
47.9
515
516
519
524
531
539
549
560
572
584
598
18.7
20.4
22.3
24.6
27.2
30.2
33.4
37.0
41.0
45.4
50.2
541
540
542
546
551
559
568
578
589
601
613
20.7
22.4
24.4
26.7
29.3
32.2
35.5
39.2
43.2
47.7
52.5
567
564
564
567
572
578
586
595
605
617
629
22.9
24.5
26.5
28.8
31.4
34.4
37.7
41.4
45.5
50.0
54.9
LEGEND
Brake Horsepower
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. Conversion — Bhp to kW:
Bhp
—
*Refer to Fan Performance, 48MP Units section, for correct procedure on
48MP units.
Bhp × .746
kW =
Motor efficiency
See Table 1 for motor efficiency.
Table 11 — Fan Performance (Forward Curved) — 48/50MP90P*
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.50
0.75
1.00
1.25
1.50
1.75
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
42,000
44,000
46,000
297
313
330
347
365
381
400
419
439
458
478
498
518
6.9
8.5
329
343
357
373
389
400
418
437
455
474
493
512
532
7.9
9.6
360
371
384
398
412
420
437
454
472
490
508
527
546
8.9
10.7
12.7
14.9
17.4
19.4
22.4
25.8
29.6
33.7
38.3
43.2
48.7
375
395
410
422
436
440
455
472
488
505
523
541
559
9.8
11.7
13.8
16.2
18.8
21.0
24.1
27.5
31.3
35.5
40.2
45.2
50.7
402
420
430
442
449
460
474
489
505
521
538
555
573
11.4
13.2
15.3
17.4
19.8
22.7
25.8
29.3
33.2
37.4
42.1
47.2
52.8
430
445
452
462
469
480
493
507
522
537
553
570
587
13.0
14.8
16.9
19.0
21.4
24.5
27.6
31.2
35.1
39.4
44.1
49.3
54.9
10.3
12.3
14.6
16.5
19.4
22.6
26.2
30.3
34.7
39.5
44.8
11.5
13.6
16.0
17.9
20.9
24.2
27.9
32.0
36.4
41.3
46.7
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
2.50 2.75
AIRFLOW
(Cfm)
2.00
2.25
3.00
3.25
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
42,000
44,000
46,000
455
465
475
486
488
501
512
525
539
553
568
584
600
14.5
16.4
18.5
20.8
23.0
26.3
29.5
33.1
37.1
41.4
46.2
51.4
57.1
480
485
500
510
510
522
532
543
556
569
584
599
614
16.0
18.0
20.5
22.5
24.8
28.3
31.5
35.1
39.1
43.5
48.3
53.6
59.3
506
515
525
531
532
542
551
561
573
585
599
613
628
17.8
20.0
22.5
24.5
26.5
30.4
33.6
37.2
41.2
45.7
50.5
55.8
61.6
532
545
548
552
552
563
571
580
590
602
614
628
642
19.5
22.0
24.5
26.5
28.6
32.5
35.8
39.4
43.5
47.9
52.8
58.2
64.0
555
568
570
572
572
585
590
598
607
618
630
642
656
21.5
23.8
26.2
28.5
30.8
34.8
38.1
41.7
45.7
50.2
55.2
60.6
66.4
578
590
590
592
590
602
610
617
625
634
645
657
670
23.5
25.5
28.0
30.5
33.0
36.5
40.4
44.1
48.1
52.6
57.6
63.0
68.0
NOTES:
LEGEND
Brake Horsepower
1. Fan performance is based on wet coils and clean 2-in. filters.
2. Conversion — Bhp to kW:
Bhp
—
*Refer to Fan Performance, 48MP Units section, for correct procedure on
48MP units.
Bhp × .746
kW =
Motor efficiency
See Table 1 for motor efficiency.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 12 — Fan Performance (Forward Curved) — 48/50MP10R*
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.50
0.75
1.00
1.25
1.50
1.75
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
42,000
44,000
46,000
48,000
50,000
52,000
315
330
346
368
386
405
424
443
463
482
502
521
541
561
9.5
11.2
13.2
15.6
18.4
21.5
24.9
28.7
33.0
37.6
42.6
48.1
54.0
60.5
346
359
372
386
404
421
449
458
476
495
514
533
553
572
10.9
12.7
14.8
16.9
19.7
22.9
26.4
30.3
34.6
39.2
44.3
49.9
55.9
62.4
367
380
399
415
430
446
464
473
490
509
527
546
564
583
10.9
14.0
16.8
18.8
21.8
24.4
28.0
31.9
36.2
41.0
46.1
51.7
57.8
64.4
390
401
417
438
450
468
471
487
505
522
540
558
576
594
12.4
14.9
17.6
20.8
23.5
26.3
29.6
33.6
38.0
42.8
48.0
53.6
59.8
66.4
412
422
435
461
470
489
501
513
532
542
553
570
588
606
14.0
16.0
18.5
22.8
25.2
28.2
31.3
35.3
39.7
44.6
49.9
55.6
61.8
68.5
434
446
460
490
490
506
417
530
547
556
566
582
600
617
15.7
17.7
20.2
24.1
26.8
30.1
33.4
37.1
41.6
46.5
51.8
57.6
63.9
70.6
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
2.50 2.75
AIRFLOW
(Cfm)
2.00
2.25
3.00
3.25
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
42,000
44,000
46,000
48,000
50,000
52,000
455
470
485
500
511
522
533
547
562
570
579
595
612
629
17.5
19.5
22.0
25.5
28.5
32.0
35.5
39.8
43.5
48.4
53.8
59.7
66.0
72.8
480
490
502
519
530
538
550
562
577
584
592
607
624
640
19.0
21.2
23.8
27.5
30.7
33.7
37.5
41.3
45.5
50.5
55.9
61.8
68.1
75.0
505
510
520
538
548
555
566
576
592
598
605
620
636
652
20.5
23.0
25.5
29.5
33.0
35.5
39.6
42.9
47.5
52.5
58.0
63.9
70.3
77.2
528
532
539
558
567
574
582
592
603
608
618
633
648
663
22.4
24.7
27.5
31.1
34.3
37.3
41.2
45.0
49.6
54.7
60.2
66.1
72.6
79.5
550
555
558
577
586
592
599
608
614
619
632
646
660
675
24.5
26.5
29.5
32.8
35.7
39.1
42.9
47.1
51.8
56.9
62.4
68.4
74.9
81.9
572
580
580
595
601
608
615
622
628
633
646
659
672
687
26.5
29.0
31.5
35.1
38.0
41.4
45.2
49.4
54.0
59.1
64.7
70.8
77.3
84.3
LEGEND
Brake Horsepower
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. Conversion — Bhp to kW:
Bhp
—
*Refer to Fan Performance, 48MP Units section, for correct procedure on
48MP units.
Bhp × .746
kW =
Motor efficiency
See Table 1 for motor efficiency.
Table 13 — Fan Performance (Air Foil) — 48/50MP62L*
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.25
0.50
0.75
1.00
1.25
1.50
1.75
2.00
833
867 10.4
909 12.2
951 14.1
2.25
866
2.50
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
16,000
18,000
20,000
22,000
24,000
26,000
28,000
30,000
32,000
581
637
698
757
815
877 11.4
937 13.9
3.4
4.5
5.8
7.4
9.2
620
672
730
787
843 10.2
904 12.5
962 15.1
4.1
5.2
6.7
8.4
656
706
761
815
870 11.2
929 13.7
4.8
6.0
7.6
9.3
694
738
792
843 10.2
895 12.3
953 14.8
5.5
6.8
8.4
731
771
820
6.4
7.6
9.3
765
805
849 10.1
897 12.1
946 14.3
7.2
8.5
798
837
880 11.2
922 13.0
971 15.3
8.0
9.5
9.0
9.9
898 10.8
927 12.3
965 14.3
896 11.3
938 13.2
871 11.1
921 13.3
978 15.3 1005 16.4
994 16.4 1019 17.5 1044 18.7
977 15.9 1001 17.0 1024 18.1 1046 19.2 1068 20.3 1089 21.5
986 16.3 1009 17.5 1031 18.7 1053 19.9 1075 21.1 1097 22.3 1118 23.5 1138 24.7
995 16.6 1019 17.9 1042 19.2 1064 20.5 1085 21.8 1106 23.1 1126 24.4 1147 25.7 1168 26.9 1187 28.2
1055 19.8 1078 21.2 1100 22.6 1121 23.9 1141 25.3 1161 26.7 1180 28.1 1199 29.5 1219 30.8 1238 32.2
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
2.75
3.00
3.25
3.50
3.75
4.00
4.25
4.50
4.75
5.00
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
16,000
18,000
20,000
22,000
24,000
26,000
28,000
30,000
32,000
929 11.7
957 13.4
959 12.7
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
986 14.4 1015 15.5 1042 16.6 1068 17.7 1094 18.8
991 15.4 1019 16.5 1046 17.6 1073 18.8 1099 19.9 1124 21.1 1149 22.3 1173 23.5 1197 24.7 1220 25.9
1030 17.5 1055 18.7 1079 19.9 1103 21.1 1129 22.3 1154 23.6 1178 24.8 1202 26.1 1225 27.4 1248 28.7
1069 19.9 1094 21.2 1117 22.4 1140 23.7 1163 24.9 1185 26.2 1207 27.6 1230 28.9 1253 30.3 1276 31.7
1114 22.8 1137 24.1 1160 25.4 1183 26.8 1204 28.1 1226 29.5 1247 30.9 1267 32.2 1287 33.6 1308 35.1
1158 25.9 1179 27.2 1201 28.6 1223 30.0 1244 31.4 1265 32.9 1286 34.3 1306 35.8 1326 37.2 1345 38.7
1207 29.5 1226 30.8 1244 32.1 1264 33.5 1285 35.0 1305 36.5 1325 38.0 1345 39.5 1364 41.1 1383 42.6
1257 33.5 1275 34.9 1293 36.3 1311 37.6 1328 39.0 1346 40.5 1366 42.1 1385 43.7 1404 45.3 1423 47.0
LEGEND
Brake Horsepower
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. Conversion — Bhp to kW:
Bhp
—
*Refer to Fan Performance, 48MP Units section, for correct procedure on
48MP units.
Bhp × .746
kW =
Motor efficiency
See Table 1 for motor efficiency.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 14 — Fan Performance (Air Foil) — 48/50MP70M*
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.50
0.75
1.00
1.25
1.50
1.75
2.00
2.25
2.50
2.75
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
18,000
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
668
725
781
837 10.0
898 12.3
955 14.8
5.1
6.6
8.2
702
756
809
5.9
7.4
9.1
735
787
838 10.0
890 12.1
947 14.5
6.7
8.3
767
816
865 10.9
916 13.1
971 15.6
7.5
9.1
801
8.4
833
9.3
863 10.3
905 12.0
945 13.9
893 11.2
933 13.1
973 15.0
924 12.2
961 14.1
954 13.3
987 15.2
844 10.0
892 11.9
941 14.1
875 11.0
917 12.8
966 15.1
999 16.2 1025 17.3
864 11.0
923 13.4
989 16.2 1013 17.3 1039 18.5 1065 19.7
995 16.7 1018 17.8 1041 19.0 1063 20.1 1084 21.2 1108 22.5
979 16.0 1002 17.2 1025 18.4 1047 19.6 1069 20.8 1091 21.9 1112 23.1 1133 24.3 1153 25.6
1011 17.4 1034 18.8 1056 20.0 1078 21.3 1098 22.6 1119 23.9 1140 25.2 1160 26.5 1180 27.7 1200 29.0
1071 20.7 1093 22.1 1114 23.5 1135 24.9 1154 26.2 1174 27.6 1193 29.0 1213 30.4 1232 31.7 1251 33.1
1129 24.3 1150 25.7 1171 27.2 1190 28.7 1210 30.1 1228 31.6 1246 33.1 1264 34.6 1283 36.0 1301 37.4
1186 28.1 1207 29.6 1226 31.2 1245 32.8 1264 34.3 1282 35.9 1299 37.4 1317 39.0 1334 40.5 1351 42.1
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
3.00
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
983 14.3 1011 15.4 1039 16.4 1065 17.5 1091 18.6
3.25
3.50
3.75
4.00
4.25
4.50
4.75
5.00
18,000
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
—
—
—
—
—
—
—
—
1014 16.3 1042 17.4 1069 18.6 1095 19.7 1120 20.9 1145 22.1 1169 23.3 1193 24.5 1216 25.8
1050 18.5 1074 19.6 1098 20.8 1124 22.1 1149 23.3 1173 24.6 1197 25.9 1220 27.2 1243 28.5
1089 20.9 1113 22.2 1136 23.4 1158 24.7 1180 26.0 1202 27.3 1226 28.6 1249 30.0 1271 31.4
1132 23.8 1155 25.1 1177 26.4 1199 27.8 1221 29.1 1242 30.5 1262 31.9 1282 33.3 1303 34.7
1172 26.8 1195 28.2 1217 29.6 1239 31.0 1260 32.5 1280 33.9 1300 35.4 1320 36.8 1340 38.3
1219 30.3 1238 31.6 1256 32.9 1277 34.4 1298 35.9 1318 37.5 1338 39.0 1357 40.5 1376 42.1
1270 34.4 1288 35.8 1305 37.2 1323 38.6 1340 40.0 1360 41.6 1379 43.2 1398 44.8 1417 46.4
1319 38.9 1337 40.3 1354 41.8 1371 43.2 1388 44.7 1404 46.2 1420 47.7 1439 49.3 1457 51.0
1369 43.6 1386 45.1 1403 46.6 1419 48.2 1435 49.7 1451 51.3 1467 52.8 1483 54.4 1498 55.9
LEGEND
Brake Horsepower
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. Conversion — Bhp to kW:
Bhp
—
*Refer to Fan Performance, 48MP Units section, for correct procedure on
48MP units.
Bhp × .746
kW =
Motor efficiency
See Table 1 for motor efficiency.
Table 15 — Fan Performance (Air Foil) — 48/50MP82N*
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.25 1.50 1.75 2.00
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
AIRFLOW
(Cfm)
0.50
0.75
1.00
2.25
2.50
2.75
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
42,000
449
477
505
535
563
595
4.1 485
4.9 511
5.9 538
7.0 565
8.1 591
5.0 519
5.9 543
7.0 568
8.1 594
6.0 551
7.0 574
8.1 598
7.0 583
8.1 602
8.1 616
9.4
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
9.2 631 10.3 661 11.7
9.2 626 10.4 652 11.6 677 12.9 706 14.3 733 15.8
9.3 622 10.5 649 11.7 675 13.0 699 14.4 723 15.7 748 17.2 773 18.7
9.3 619 10.6 646 11.9 671 13.2 697 14.5 721 15.9 744 17.3 766 18.8 787 20.2
9.6 621 10.8 647 12.1 673 13.5 698 14.9 721 16.3 745 17.8 767 19.3 789 20.8 810 22.3
624 11.0 649 12.3 673 13.7 698 15.2 722 16.6 745 18.1 767 19.6 789 21.2 811 22.8 831 24.4
655 12.7 679 14.1 702 15.6 725 17.1 748 18.7 770 20.2 792 21.8 813 23.4 834 25.0 854 26.7
685 14.6 709 16.1 731 17.6 752 19.2 771 20.8 796 22.4 817 24.1 838 25.8 857 27.5 877 29.2
717 16.7 739 18.3 761 19.9 781 21.5 801 23.2 822 24.9 843 26.6 863 28.4 882 30.1 901 31.9
748 18.9 769 20.5 789 22.2 809 24.0 829 25.7 848 27.4 868 29.3 888 31.1 907 32.9 925 34.8
779 21.3 799 23.1 819 24.8 838 26.6 857 28.4 875 30.3 894 32.1 913 34.0 931 35.9 950 37.9
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
3.00
3.25
3.50
3.75
4.00
4.25
4.50
4.75
5.00
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
20,000
22,000
24,000
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
42,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
798 20.3
812 21.9 835 23.6 858 25.3
831 23.8 851 25.4 874 27.2 896 29.1 917 30.9
851 26.0 871 27.6 890 29.3 910 31.0 931 32.9 952 34.9 972 36.8 992 38.8
874 28.4 893 30.1 912 31.8 930 33.6 948 35.3 966 37.2 986 39.2 1006 41.3 1025 43.4
896 31.0 915 32.7 934 34.5 952 36.3 969 38.2 986 40.0 1003 41.9 1021 43.8 1039 46.0
920 33.7 938 35.6 956 37.5 974 39.4 991 41.3 1008 43.2 1025 45.1 1041 47.1 1057 49.0
943 36.6 961 38.5 978 40.5 996 42.4 1013 44.4 1030 46.4 1046 48.4 1062 50.4 1078 52.5
967 39.8 984 41.8 1001 43.7 1018 45.8 1035 47.8 1052 49.9 1068 52.0 1084 54.0 1099 56.2
LEGEND
Brake Horsepower
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. Conversion — Bhp to kW:
Bhp
—
*Refer to Fan Performance, 48MP Units section, for correct procedure on
48MP units.
Bhp × .746
kW =
Motor efficiency
See Table 1 for motor efficiency.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 16 — Fan Performance (Air Foil) — 48/50MP90P*
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.50
0.75
1.00
1.25
1.50
1.75
2.00
2.25
2.50
2.75
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
24,000
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
42,000
44,000
46,000
501
531
561
591
621 10.6
651 12.5
681 14.3
713 16.3
743 18.5
774 20.9
806 23.5
837 26.3
5.70 534
8.78 581
7.98 588
6.78 565
7.93 591
7.89 594
9.05 622 10.2 649 11.5 674 12.7 702 14.1 729 15.6
—
—
9.12 619 10.3
646 11.6 672 12.9 696 14.2 720 15.5 745 17.0 770 18.5
9.20 617 10.5
644 11.7
670 13.3
695 15.0
721 16.9
748 18.9
777 21.2
805 23.5
834 26.2
863 29.1
892 32.1
669 13.1 695 14.4 719 15.8 742 17.2 764 18.6 788 20.1
695 14.7 718 16.1 742 17.8 765 19.1 787 20.6 808 22.1
719 16.5 742 18.0 764 19.5 787 21.0 806 22.6 829 24.2
744 18.4 767 20.0 789 21.5 810 23.1 831 24.8 851 26.4
770 20.5 792 22.1 813 23.8 833 25.4 853 27.1 873 28.9
797 22.9 818 24.6 839 26.3 856 28.0 878 29.8 897 31.8
824 25.3 843 27.0 863 28.8 883 30.6 902 32.5 921 34.3
853 28.0 871 29.8 889 31.7 908 33.5 927 35.3 945 37.4
882 31.0 900 32.9 917 34.8 934 38.7 953 38.7 971 40.7
910 34.1 928 36.0 945 38.0 961 40.0 978 42.1 995 44.2
9.36 618 10.6
644 12.0
670 13.6
698 15.4
727 17.3
758 19.6
785 21.8
814 24.4
844 27.2
874 30.2
645 12.2
676 13.9
704 15.8
735 18.0
763 20.1
794 22.5
825 25.4
856 28.2
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
3.50 3.75 4.00 4.25 4.50
AIRFLOW
(Cfm)
3.00
3.25
4.75
5.00
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
24,000
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
42,000
44,000
46,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
795 20.1
810 21.7 833 23.4 856 25.1
828 23.6 849 25.2 871 27.0 893 28.8 915 30.7
849 25.8 859 27.4 888 29.1 907 30.8 928 32.7 949 34.6 969 36.6 969 38.8
871 28.1 890 29.8 909 31.6 927 33.3 945 35.0 963 36.9 983 38.9 1003 41.0 1022 43.0
893 30.6 912 32.4 930 34.2 948 36.0 966 37.8 983 38.9 1000 41.5 1017 43.4 1036 45.6
916 33.4 935 35.2 953 37.1 971 39.0 988 40.0 1005 42.8 1022 44.7 1038 46.7 1054 48.6
939 36.2 956 38.1 974 40.0 992 42.0 1009 43.9 1025 45.9 1042 44.9 1058 49.9 1074 52.0
963 39.3 980 41.3 997 43.3 1014 45.3 1031 47.3 1048 49.4 1064 51.5 1080 53.5 1095 55.6
988 42.7 1005 44.6 1022 45.6 1038 48.9 1054 51.0 1070 53.1 1086 55.2 1102 57.4 1118 59.6
1013 46.2 1029 48.4 1046 50.5 1062 52.6 1077 54.8 1093 56.9 1108 59.1 1124 61.4 1139 63.6
LEGEND
Brake Horsepower
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. Conversion — Bhp to kW:
Bhp
—
*Refer to Fan Performance, 48MP Units section, for correct procedure on
48MP units.
Bhp × .746
kW =
Motor efficiency
See Table 1 for motor efficiency.
Table 17 — Fan Performance (Air Foil) — 48/50MP10R*
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.25 1.50 1.75 2.00
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
AIRFLOW
(Cfm)
0.50
0.75
1.00
2.25
2.50
2.75
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
42,000
44,000
46,000
48,000
50,000
52,000
525
554
584
6.55 555
7.69 582
7.69 585
8.88 613 10.1 641 11.3
667 12.6
689 14.1
712 15.7
736 17.5
760 19.5
784 21.5
810 23.9
836 26.3
863 29.0
890 31.8
918 34.9
946 38.3
975 41.9
692 13.9
713 15.5
735 17.2
758 19.0
782 21.0
805 23.2
831 25.8
855 28.1
881 30.8
907 33.7
935 38.0
963 40.3
715 15.3
736 16.9
758 18.7
780 20.6
803 22.8
826 24.8
851 27.3
875 29.9
900 32.7
925 35.0
952 38.9
979 42.4
739 16.7
759 18.3
781 20.2
802 22.1
824 24.3
846 26.5
871 29.1
894 31.7
919 34.6
943 37.6
968 40.9
765 18.2
781 19.7
802 21.7
823 23.7
845 25.9
866 28.2
890 30.9
913 33.6
937 35.5
961 39.6
986 43.0
8.90 610 10.2
637 11.4 663 12.7
663 13.0 688 14.3
688 14.6 712 16.1
714 16.4 737 17.9
740 18.3 761 19.9
769 20.5 789 22.2
797 22.9 817 24.6
825 25.4 844 27.2
853 28.1 872 29.9
882 31.0 900 33.0
911 34.2 929 36.2
941 37.5 958 39.8
9.00 611 10.3
636 11.6
663 13.2
691 14.9
719 15.8
748 18.9
776 21.2
805 23.6
834 26.2
864 29.1
894 32.2
924 38.5
954 39.0
613 10.4
643 12.0
672 13.7
704 15.7
734 17.8
765 20.1
795 22.5
826 25.2
857 28.2
889 31.4
919 34.7
639 11.8
667 13.5
696 15.2
726 17.3
755 19.5
785 21.9
815 24.3
845 27.2
876 30.2
907 33.4
937 35.9
995 44.5 1011 46.6
991 44.0 1007 46.1 1023 48.3 1038 50.5
970 41.2 986 43.4 1003 45.6 1019 47.8 1035 50.0 1050 52.2 1065 54.5
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
3.50 3.75 4.00 4.25 4.50
AIRFLOW
(Cfm)
3.00
3.25
4.75
5.00
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
26,000
28,000
30,000
32,000
34,000
36,000
38,000
40,000
42,000
44,000
46,000
48,000
50,000
52,000
790 19.8
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
804 21.3 828 23.0 851 24.7
823 23.2 843 24.8 865 26.5 887 28.3 909 30.2 930 32.0
844 25.3 863 27.0 882 28.6 901 30.3 922 32.2 943 34.1 964 36.0 984 38.0
865 27.6 884 29.3 903 31.0 921 32.7 939 34.5 957 36.2 977 38.3 997 40.3 1016 42.4
886 30.0 905 31.7 924 33.5 942 35.3 959 37.2 977 39.0 994 40.8 1010 40.3 1029 44.5
909 32.7 927 34.5 946 38.3 964 38.2 981 40.1 998 42.0 1015 43.9 1031 45.9 1047 47.8
931 35.4 949 37.3 967 39.2 985 41.2 1002 43.2 1019 45.1 1038 47.1 1052 49.1 1068 61.2
955 35.5 973 40.4 990 42.2 1007 44.4 1024 46.4 1040 48.5 1057 50.5 1073 52.6 1089 54.7
978 41.6 996 43.6 1013 45.7 1029 47.7 1045 49.8 1061 51.9 1077 54.0 1093 56.2 1109 58.4
1003 45.1 1020 47.2 1037 49.3 1053 51.4 1069 53.6 1084 55.7 1100 57.9 1115 60.1 1139 63.6
1028 48.7 1044 50.9 1061 53.1 1077 55.3 1092 57.5 1108 59.7 1123 62.0 1137 64.2 1152 66.5
1053 52.7 1069 54.9 1085 57.2 1101 59.4 1116 61.7 1132 64.0 1146 65.3 1161 68.7 1175 71.0
1080 56.8 1094 59.0 1109 61.4 1125 63.7 1140 66.1 1165 68.4 1170 70.8 1184 73.2
LEGEND NOTES:
Brake Horsepower
—
—
1. Fan performance is based on wet coils and clean 2-in. filters.
2. Conversion — Bhp to kW:
Bhp
—
*Refer to Fan Performance, 48MP Units section, for correct procedure on
48MP units.
Bhp × .746
kW =
Motor efficiency
See Table 1 for motor efficiency.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 18 — Component Pressure Drop (in. wg)
COMPONENT
22,000 26,400 30,000 34,000 38,000 42,000 45,800 48,200 52,000
HEAT EXCHANGER
(48MP ONLY)
0.31
0.40
0.49
0.58
0.70
0.82
0.95
1.03
1.23
Table 19 — Maximum Allowable
Supply Fan Wheel Speed (Rpm)
and nominal cfm delivery. See Table 22 for clean filter pres-
sure drops for help in locating the ‘‘pivot’’ point. Once this
point is found, turn the screw clockwise to obtain the set
point at which the filter status will be dirty. Use Table 22 as
a guide.
FAN TYPE
48/50MP
Forward Curved
Airfoil
1595
1298
62L, 70M
835
715
82N, 90P, 10R
Table 22 — Filter Switch Dirty Set Point
INCREASED
Table 20 — Maximum Allowable Power Exhaust
Fan Speed (Rpm)
PRESSURE DROP
TO ‘‘DIRTY’’
FROM PIVOT
POINT
APPROXIMATE
CLOCKWISE
TURNS
FILTER TYPE
FAN TYPE
48/50MP
50% Air
690
100% Air
650
2-in. Throwaway
0.30 in. wg
2
5
62L, 70M
4-in. Pleated with
2-in. Throwaway
0.75 in. wg
82N, 90P, 10R
600
560
Table 21 — Air Quantity Limits (cfm)
ENTHALPY CONTROL SET POINT — The enthalpy sen-
sor (See Fig. 45) is located behind the filters in the right side
economizer hood and is accessed through the filter access
door. For maximum benefit of outdoor air, set enthalpy sen-
sor control to the A setting. At this setting, when the relative
humidity is 50%, and the outdoor air is below 74 F, the sen-
sor’s relay contacts will be closed. See Fig. 46 and 47.
MINIMUM
MINIMUM
UNIT
GAS HEATING GAS HEATING
SIZE MINIMUM MAXIMUM
48/50MP
(Low Heat
Units)
48MPD
(High Heat
Units)
48MPE
62L
70M
82N
90P
10R
16,000
18,000
21,000
23,000
26,000
32,000
36,000
42,000
46,000
52,000
12,850
12,850
14,700
14,700
14,700
15,400
15,400
19,250
19,250
19,250
NOTE: Enthalpy control setting dial is on the enthalpy
control.
Economizer Damper Linkage Adjustment — When replac-
ing economizer damper motors, or if the linkage has come
loose, it is critical that the linkages be adjusted correctly.
They are sensitive, and incorrect adjustment can cause the
motor to stall. Check linkage for free movement and com-
plete range of travel.
Minimum Position Set Point — Minimum economizer po-
sition is set using the keypad and display module. Refer to
Control and Troubleshooting literature for more details.
Controls Configuration and Quick Test
SUPPLY FAN STATUS SWITCH (FS) —Asnap acting single-
pole, double-throw (SPDT) differential pressure switch is fac-
tory mounted in the auxiliary control box. The switch senses
the change in pressure across the supply-air fan and pro-
vides the fan status. A length of plenum tubing connects the
switch to the probe located in the fan discharge box.
The switch must be set prior to unit operation. To set the
switch, turn the adjustment screw on top (center) of switch
clockwise to increase set point, or counterclockwise to
decrease set point. The set point switch range is 0.05 to
2.0 in. wg with a deadband of 0.02 in. wg at minimum set
point and 0.1 in. wg at maximum set point.
Set switch so that contact makes to NC when supply-air
fan is energized. The switch should make (fan on) within
1 minute after supply-air fan is energized and break (fan off)
within 1 minute after the fan is deenergized.
ENTHALPY
SENSOR
CHECK FILTER SWITCH (CFS) — A snap acting SPDT
switch is factory mounted in the auxiliary control box. The
switch senses the differential pressure and provides the micro-
processor module with a signal for filter status. Two lengths
of plenum tubing connect the switch to probes located both
upstream and downstream of the unit filters.
The switch must be set prior to unit operation. To set the
switch, turn the adjustment screw on top (center) of switch
slowly clockwise to find the ‘‘pivot’’ point where the filter
status still reads clean under
in the HSIO display.
Fig. 45 — Enthalpy Sensor
Check the switch operation with the supply-air fan running
35
Download from Www.Somanuals.com. All Manuals Search And Download.
The HSIO keypad and display module is installed by con-
necting the power and communication plugs and can be
easily moved from one unit to another. Because of this flex-
ibility, one HSIO can be used for several units.
Unit operation is controlled by the status of the run/
standby mode on the HSIO. To access the mode, press
CONTROL POINT
(Approx Deg F)
AT 50% RH
CONTROL
CURVE
on the HSIO keypad, and then press
.
The HSIO will display either STBY YES or STBY NO.
CLEAR
ENTER
To enable the unit, press
or
and press
while
at the STBY YES display. To disable the unit, press
ENTER
while at the STBY NO display. Clearing an alarm
that has stopped unit operation is accomplished by entering
the STBY YES mode.
IMPORTANT: Use the STBY YES mode when ser-
vicing the unit or running the quick test feature.
IMPORTANT: If remote start function is used, place
LOCAL/REMOTE switch in Local (OFF) position when
ever unit is placed in STBY YES.
SET UNIT TYPE — The correct unit type must be set. The
default unit type is VAV. If the unit is being used in a VAV
application, then the unit type does not need to be changed.
Table 23 — HSIO Keypad Key Usage
Fig. 46 — Psychrometric Chart for
Enthalpy Control
FUNCTION
USE
KEYS
Status — To display diagnostic codes and
current operating information about the unit.
Quick Test — To check inputs and outputs for
proper operation.
History — To check most recent alarms.
Service — To enter specific unit configuration
information.
Set Point — To enter operating set points and
day/time information.
Schedule — To enter occupied/unoccupied
schedules for unit operation.
OPERATIVE
USE
KEYS
Expand Display — To display a non-
abbreviated expansion of the display.
Clear — To clear the screen and return to previous
NOTES:
CLEAR
display. Also used to enter data value
1. Switches shown in high enthalpy state. Terminals 2 and 3 close on enthalpy
decrease.
of zero.
2. When standard economizer is used with accessory differential enthalpy sen-
sor, set enthalpy control to ‘‘D’’ setting.
Up Arrow — To return to previous display position.
Fig. 47 — Wiring Connections for Solid-State
Enthalpy Sensor (HH57AC077)
Down Arrow — To advance to next display position.
ENTER
To enter data.
KEYPAD AND DISPLAY MODULE (HSIO)
CONFIGURATION
IMPORTANT: The HSIO keypad and display module
is required for initial start-up of these units. All units
are shipped in standby mode, and the HSIO should be
used to change the unit to run mode. Once the unit is
in run mode, the HSIO is not required for normal
operation.
TEST
ALRM
EXPN
EDIT
SRVC
HIST
STAT
SET
1
4
2
5
8
0
3
6
9
ALGO
SCHD
CLEAR
ENTER
7
-
The keypad and display module provides unit function in-
formation at the unit. See Fig. 48. The module consists of a
keypad with 6 function keys, 5 operative keys, 10 numeric
keys (0 through 9), and an alphanumeric 8-character liquid
crystal display (LCD). Key usage is explained in Table 23.
Each function has one or more subfunctions.
Fig. 48 — Keypad and Display Module (HSIO)
36
Download from Www.Somanuals.com. All Manuals Search And Download.
If the unit is being used in a CV application, then perform
the following:
For example, the occupied cool set point is currently set
at the default value of 78 F. To change the occupied set point
to 72 F:
1. Enter the configuration function by pressing
.
and
1. Press
to enter the occupied cool set point
function. The display will read OCSP 78.
2. Scroll down to unit type. TYPE 1 will be displayed.
ENTER
2. Press
and the display will read OCSP 72.
ENTER
3. Press
and
to change the unit type to CV.
Set points can be changed by the user provided that the
values are within the allowable range for the input. If the
input is not within the allowable range, the original value
will remain displayed. See Table 24 for allowable ranges and
default values.
To change the demand limit set points, the functions must
first be enabled in the field configuration subfunction.
4. Scroll down to data reset. DTRS will be displayed. Press
ENTER
and
to save changes.
The fan operation type should also be configured for
use in occupied time periods. Fan operation can be
set to continuous or auto. To set, press
to enter
CONFIGURE UNIT CONTROLS AND FUNCTIONS —
Refer to Table 25 for a suggested sequence for entering
Basic System Configuration data. These values may be changed
from the HSIO at any time. If changing default values via
the CCN, the 48/50MP unit must first be in run mode
(STBY NO).
the subfunction. Scroll down to fan mode (FANM). Press
ENTER
ENTER
and
to continuous.
to set to AUTO. Press
and
to set
ENTER JOB SET POINT VALUES — The set point func-
tion allows the user to view the current values set for the
unit. From this function, the user can change the values.
NOTE: After changing any of the values in the
configuration group, enable the Data Reset function.
Reading and Changing Set Points — To change the set point
of a particular feature, enter the appropriate subfunction and
scroll to the variable desired. Once the desired variable has
QUICK TEST FUNCTION — Enable and run the Quick Test
function. Refer to the Controls and Troubleshooting manual
for more information on Quick Test.
ENTER
been reached, type in the new value and press
new value will appear in the display.
. The
Table 24 — Set Point Ranges and Defaults
SET POINT
DEFAULT
VALUE
ALLOWABLE
RANGE
DISPLAY
BPSP
DESCRIPTION
Building pressure set point
Economizer set point offset
High humidity override (percent)
High temperature minimum position
Humidity set point (percent)**
IAQ set point
0.05 in. wg
3
0 to .50 in. wg
1 to 10
ECSO*
HHL†/HHOR*
HTMP
99%
35 F
40%
650 ppm
10 F
50%
10 F
20%
50 F
1 cfm
78 F
68 F
90%
3 F
0 to 100%
0 to 100 F
0 to 100%
0 to 2000 ppm
0 to 20 F
HUSP
IAQS†
LIMT†
LSP
Reset limit (F)
Loadshed set point (percent)
Low temperature minimum position
Minimum damper position (percent)
NTFC lockout temperature (F)
Outdoor-air cfm set point
0 to 100%
0 to 100 F
0 to 100%
40 to 70 F
0 to 50,000 cfm
55 to 80 F
55 to 80 F
30 to 100%
0 to 10 F
LTMP
MDP†
NTLO†
OLS†/OACS*
OCSP
Occupied cool set point (F)**
Occupied heat set point (F)**
Power exhaust on set point (percent)
Reset ratio (F)
OHSP
PES†
RTIO†
SASP
Supply air set point (F)
55 F
1.5 in. wg
1
45 to 70 F
0 to 5.0 in. wg
0 to 10
SPSP
Static pressure set point††
Unoccupied cooling deadband
Unoccupied cool set point (F)**
Unoccupied heating deadband
Unoccupied heat set point (F)**
UCDB*
UCSP
90 F
1
75 to 95 F
0 to 10
UHDB*
UHSP
55 F
40 to 80 F
LEGEND
IAQ
NFTC
ppm
—
—
—
Indoor-Air Quality
Unoccupied Free Cooling
Parts Per Million
*These items are found under the Service function, and can only be accessed using either the Build-
ing Supervisor or Service Tool.
†These items are found under the Service function.
**Occupied space.
††Supply duct.
NOTE: Set points HHL/HHOR and OCS/OACS are displayed differently on the HSIO and Building Su-
pervisor. The set points are shown as HHL and OCS on the HSIO. The set points are shown as HHOR
and OACS on Building Supervisor or Service Tool.
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 25 — Basic Configuration Data
SET POINT
Unit Type
SUBFUNCTION
DISPLAY
DEFAULT
RANGE
TYPE
1 = VAV
1 (Continuous)
20 percent
68 (F)
CV = 0, VAV = 1
CV Fan Mode
FANM
MDP
Auto = 0, Cont = 1
0 to 100
55 to 80
55 to 80
75 to 95
40 to 80
0 to 5.0
Economizer Minimum
Damper Position
Heating Occupied*
Cooling Occupied
Cooling Unoccupied
Heating Unoccupied
Static Pressure
OHSP
OCSP
78 (F)
UCSP
90 (F)
UHSP
55 (F)
SPSP
1.5 (in. wg)
55 (F)
Supply Air Temperature
Date and Time
SASP
45 to 70
—
TIME
dow.hh.mm mm.dd.yy
0 (hrs)
Override Schedules†
Schedule I Periods
LEGEND
OVRD x HR
OCC HH.MM
0, 1, 2, 3 or 4
—
—
CV
VAV
—
—
Constant Volume
Variable Air Volume
*Requires Occupied Heating function enabled.
†See text section for discussion and instructions.
Gas Pressure Check — Prior to performing the Quick
Test, install gas pressure gages and jumper as follows:
START-UP
1. Turn off manual gas stop valve.
Initial Check
2. Install a jumper between HR1-NO and HR2-NO.
3. Connect pressure gage to gas supply pressure tap. See
Fig. 34.
4. Connect pressure gage to manifold pressure tap on each
gas manifold.
IMPORTANT: Do not attempt to start unit, even mo-
mentarily, until all items on the Start-Up Checklist and
the following steps have been completed.
1. Verify unit has been installed per the Installation section
of this literature.
2. Certify that all auxiliary components (sensors, controls,
etc.) have been installed and wired to the control boxes
per these instructions, the Controls and Troubleshooting
literature and the unit wiring label diagrams.
3. Verify that pressure hoses (static, duct, etc.) are properly
attached, routed, and free from pinches or crimps that may
affect proper control operation.
4. Set any control configurations that are required (field-
installed accessories, etc.). The unit is factory configured
for all appropriate factory-installed options with the
applicable controls programmed to the default values. See
unit Controls and Troubleshooting literature for appli-
cable configuration values.
5. Enter unit set points (if applicable). The unit is shipped
with the set point default values shown in the Con-
trols and Troubleshooting literature. If a different set point
is required, change per the example shown under Set
Point Function section in Controls and Troubleshooting
literature.
6. Configure schedule subfunctions (if applicable): occu-
pied, unoccupied, and holiday periods. See Schedule Func-
tion section in Controls and Troubleshooting literature for
details on setting periods.
5. Turn on manual gas stop valve.
During the heating portion of the Quick Test,
,
both the first and second stage of gas heat will be tested.
During the first stage, all of the burner sections will operate
at low fire condition (approximately 75% capacity). During
the second stage, all of the burner sections will operate at
100% capacity.
During the Quick Test of stage 2, after the unit has been
operating for several minutes, verify that the incoming gas
line pressure is 5.5 in. wg or greater. Also, verify that the
manifold pressure at each burner section is 3.3 in. wg. If
manifold pressure must be adjusted, refer to the Gas Valve
Adjustment section on page 52.
After the unit has been in operation for 5 minutes, check
the temperature rise across the unit heat exchangers. See the
unit informative plate for correct rise range limits. Air quan-
tities may need to be adjusted to bring the actual rise within
allowable limits.
IMPORTANT: After the Quick Test has been perfor-
mend for stage 2, remove the jumper betwen HR1-NO
and HR2-NO.
Check Supply Fan Rotation — If unit is equipped
with an optional VFD, check for correct fan rotation. Fan
direction can be changed by disconnecting power and switch-
ing 2 power leads downstream of the VFD output terminals
T1, T2, and T3.
7. Verify that control time periods programmed meet cur-
rent requirements.
8. Check all electrical connections to be sure they are tight.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
Economizer operation is permitted if the system is not in
Heating mode, if outdoor air enthalpy (via switch or humid-
ity differential) is acceptable, and if outside air temperature
is less than space temperature.
If economizer operation is permitted, the ecomizer con-
trol loop checks for Cooling System operation. If ON, the
outside air dampers will be driven to maximum position.
If cooling is not on , for VAV units, the economizer will
modulate to satisfy the supply air set point.
If cooling is not on, for CV units, the economizer will
modulate to satisfy the space temperature set point.
If Economizer operation is not permitted, the outside air
dampers will be driven to minimum position (during Occu-
pied period) or closed (during Unoccupied period).
For VAV units, Economizer operation is not permitted when
Occupied Heating is enabled and the Return Air Tempera-
ture is LESS THAN (OHSP + 1).
General
NOTE: If unit is equipped with REMOTE START function,
place the LOCAL/REMOTE switch in the LOCAL (Off)
position.
1. Put the ON/OFF switch in the ON position. Close the con-
trol circuit breaker (CCB), which will energize the con-
trol circuit and the crankcase heaters.
2. Using the HSIO or Building Supervisor, verify that no
alarms have been detected.
3. Ensure that quick test has been performed to make sure
that the controls are operating properly. Refer to the Con-
trols and Troubleshooting Guide for more information.
4. Using the HSIO, put the unit into Run mode.
a. Press
b. Press
.
.
CLEAR
c. Press
. This will put the unit in Run mode.
COOLING (All Units) — The controls try to control the supply-
air temperature (SAT) to a system-calculated coil reference
temperature value by cycling the compressors and the
unloader(s). Both the supply- and return-air temperature sen-
sors are used to adjust the cycling deadband to match the
actual load. The control system provides cooling capacity
control of up to 11 stages to maintain supply-air temperature
(VAV) or space temperature (CV) to an occupied or un-
occupied set point. Automatic lead-lag circuit switching
occurs (if configured) to equalize run times per compressor
for improved compressor reliability. The compressor to start
first is changed every time stage equals zero.
d. Press
. The unit will change from mode 25
(standby), to mode 32 (occupied) or mode 27 (unoc-
cupied) depending on the programmed time
schedule.
Operating Sequences — Base unit operating
sequences are presented below. Refer to unit Controls and
Troubleshooting literature for expanded details on unit con-
trols operation, additional controls functions, and logic theory.
SUPPLY FAN
VAV Units — During Occupied periods, the control will en-
ergize the supply fan contactor. The contactor will close,
energizing supply fan motor. Fan wheel will turn. Airflow
Switch (differential pressure switch) contacts close, provid-
ing discrete input (DI) to Channel 12 (Closed = Fan ON).
Fan operation will continue through the Occupied period.
During Unoccupied period with demand, the control will
energize fan contactor when demand is sensed. After fan sta-
tus is confirmed, operating routines will start. When demand
is removed, routines will end and fan will shut off.
NOTE: Automatic lead/lag should be disabled if optional hot
gas bypass is employed because the unit only contains hot
gas bypass on one circuit.
The VAV control system sequence uses the modified supply-
air set point (MSAT = supply-air set point ϩ reset value) as
the supply-air temperature required to satisfy conditions (sub-
master reference value [CSSR]) and outputs this value to the
submaster loop.
The submaster loop uses the modified supply-air set point
compared to the actual supply-air temperature to determine
the required number of capacity stages to satisfy the load.
The logic for determining when to add or subtract a stage is
a time-based integration of the deviation from the set point
plus the rate of change of the supply-air temperature.
The CV control system sequence reads the space sensor
and performs a calculation to determine the supply-air tem-
perature required (a cooling coil submaster reference [CCSR]
value) to satisfy conditions and outputs this value to the sub-
master loop.
CV Units, Continuous Fan — During Occupied periods, the
control will energize the supply fan contactor. The contactor
will close, energizing supply fan motor. Fan wheel will turn.
Airflow Switch (differential pressure switch) contacts close,
providing discrete input (DI) to Channel 12 (Closed =
Fan ON). Fan operation will continue through the Occupied
period.
During Unoccupied period with demand, the control will
energize fan contactor when demand is sensed. After fan sta-
tus is confirmed, operating routines will start. When demand
is removed, routines will end and fan will shut off.
OCCUPIED COOLING
General — Economizer cycle must not be usable or damper
position must be open to 90% or higher.
VAV Units — Supply fan must be ON for cooling control to
operate. Sequence is as follows:
CV Units, Automatic Fan — Fan will be turned OFF during
Occupied period when there is no demand for heating or cool-
ing operation. When demand is sensed, control will energize
fan contactor and initiate cooling cycle. Fan status will be
confirmed. When demand is removed, routines will termi-
nate and fan will be shut off.
1. Unit must not be in Heating mode.
2. Master Loop will survey occupancy status, Supply Air
Set Point (SASP) and any Supply Air Temperature Reset
command, then issue Cooling Coil Submaster Reference
(CCSR) to Cooling Submaster Loop (CSL).
3. The CSL surveys actual SAT, then calculates number of
capacity stages required to produce the CCSR leaving the
unit.
4. Stages of cooling capacity are initiated. From zero stages,
there will be a 1.5 to 3 minute delay before the first stage
is initiated. The time delay between stages in increasing
demand is 90 seconds.
ECONOMIZER — The economizer control loop will be de-
layed 2 minutes after the supply fan is turned ON, to allow
system and temperatures to stabilize before starting control.
When coming out of STANDBY or Heating mode, a 4-minute
delay will occur before the economizer damper is con-
trolled. During this delay, damper position is limited to CLOSED
or MINIMUM position (depending on current unit occu-
pancy status).
If fan status is OFF, the outside air dampers will remain
closed (return air dampers will be open). If fan status is ON,
the outside air dampers will normally be at minimum damper
position.
39
Download from Www.Somanuals.com. All Manuals Search And Download.
5. As actual SAT approaches CCSR value, stages are re-
leased. The minimum time delay between stages on de-
creasing demand is 90 seconds.
set point is user configurable. Like adaptive optimal start,
the control corrects itself for optimal operation by adjusting
the ‘‘K’’ factor as required.
NOTE: Demand for heating has priority and Master Loop
will either terminate existing or prevent initiation of
Cooling Cycle by issuing a CCSR at the maximum limit.
This will cause the CSL to select zero stages of cooling
capacity, initiating a stoppage of an existing cooling cycle.
GAS HEATING, OPERATION (48MP Units Only) — Re-
fer to the Controls, Operation and Troubleshooting instruc-
tions for information on the control logic used by the unit
controls for gas heat operation.
The 48MPD units have 2 gas heat sections. The 48MPE
units have 3 gas heat sections. Each individual section op-
erates in the same manner.
CV Units — Supply fan must be ON for cooling control to
operate. Sequence is as follows:
1. Master Loop will survey space temperature and space tem-
perature offset inputs, then calculate CCSR value.
2. The CSL surveys actual SAT, then calculates number of
capacity stages required to satisfy space load.
3. Stages of cooling capacity are initiated. (From zero stages,
there will be a 1.5 to 3 minute delay before first stage is
initiated.)
NOTE: The 48MP units have 2 stages of heat.
When the PIC control calls for heating, power is sent to
W on each IGC (integrated gas controller) board. An LED
(light-emitting diode) on the IGC board will be on during
normal operation. A check is made to ensure that the rollout
switch and the limit switch are closed and the induced-draft
motor is not running. The induced-draft motor is then en-
ergized, and when speed is proven with the hall effect sensor
on the motor, the ignition activation period begins. The burn-
ers will ignite within 5 seconds.
If the burners do not light, there is a 22-second delay be-
fore another 5-second attempt. If the burners still do not light,
this sequence is repeated for 15 minutes. After the 15 min-
utes have elapsed, if the burners have not been lit, heating is
locked out. To reset the control, use the manual reset method
found in the Controls Operation and Troubleshooting book.
When ignition occurs the IGC board will continue to moni-
tor the condition of the rollout and limit switches, the hall
effect sensor, and the flame sensor.
When additional heat is required, W2 closes and initiates
power to the second stage of the main gas valve. When the
thermostat is satisfied, W1 and W2 open and the gas valve
closes, interrupitng the flow of gas to the main burners. If
the call for W1 lasted less than 1 minute, the heating cycle
will not terminate until 1 minute after W1 became active.
UNOCCUPIED COOLING — The unoccupied cooling
sequence of operation is similar to Occupied Cooling (see
above) except for the following:
1. Supply Fan will be OFF as demand is initiated.
2. The Master Loop will start Supply Fan and cooling cycle.
Fan status must be proved as ON within 2 minutes to con-
tinue with cooling operation.
3. Control set point will be Unoccupied Cooling Set Point
(UCSP).
4. At end of cooling cycle, Supply Fan will be turned OFF.
OVERRIDES
First Stage and Slow Change Override — The first stage over-
ride reduces cycling on the first stage of capacity, and the
slow change override prevents the addition or subtraction of
another stage of capacity if the SAT is close to the set point
and gradually moving towards the set point.
An LED indicator is provided on the IGC to monitor op-
eration. The IGC is located by removing the side panel and
viewing the IGC through the view port located in the control
box access panel. During normal operation, the LED is con-
tinuously on. See Table 26 for error codes.
Low Temperature Override —This override function pro-
tects against rapid load decreases by removing a stage every
30 seconds when required based on temperature and the tem-
perature rate of change.
High Temperature Override — This override function pro-
tects against rapid load increases by adding a stage once
every 60 seconds as required, based on temperature and tem-
perature rate of change.
Table 26 — IGC Control Board LED Alarms
INDICATION
ON
ERROR MODE
Normal Operation
ADAPTIVE OPTIMAL START — Optimal start is used
to heat up or cool down the space prior to occupancy. The
purpose is to have the space temperature approach and then
achieve the occupied set point by the time of occupancy. The
control utilizes outdoor-air temperature, space temperature,
occupied set point, and a ‘‘K’’ factor. The ‘‘K’’ factor is ex-
pressed in minutes per degree, and calculates a start time
offset, which is the time in minutes that the system shall be
started in advance of the occupied time. The control moni-
tors its results and adjusts the ‘‘K’’ factor to ensure that the
occupied set point is achieved at time of occupancy rather
than too early or too late.
OFF
Hardware Failure
1 FLASH
Fan ON/OFF Delay Modified
Limit Switch Fault
2 FLASHES
3 FLASHES
4 FLASHES
5 FLASHES
6 FLASHES
7 FLASHES
8 FLASHES
Flame Sense Fault
4 Consecutive Limit Switch Faults
Ignition Lockout Fault
Induced Draft Motor Fault
Rollout Switch Fault
Internal Control Fault
LEGEND
Integrated Gas Unit Controller
Light-Emitting diode
ADAPTIVE OPTIMAL STOP (CV Applications Only) —
Optimal stop is used to allow space temperature to drift to
an expanded occupied set point during the last portion of an
occupied period. The control calculates a stop time offset,
(the time in minutes prior to the scheduled unoccupied time)
during which expanded heating and cooling set points can
be used. Adaptive optimal stop utilizes space temperature,
an expanded occupied set point, and a ‘‘K’’ factor to calcu-
late stop time offset. The amount (F) to expand the occupied
IGC
LED
—
—
NOTES:
1. There is a 3-second pause between error code displays.
2. If more than one error code exists, all applicable error codes will
be displayed in numerical sequence.
3. Error codes on the IGC will be lost if power to the unit is
interrupted.
40
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Verify/adjust the SMG. If the SMG is too large, the loop
will tend to oscillate (hunt). If it is too small, the loop
will react too slowly.
Control Loop Checkout
Verify or adjust the SMG as follows:
Using the HSIO keypad, force the submaster reference
of the control loop to a value above or below the actual
sensor reading. Verify that the actuator responds cor-
rectly. If the actuator drives in the wrong direction, go
to the submaster gain (SMG) for the control loop and
reverse the sign of the gain.
The checkout and adjustment of control loops should
only be done by certified Carrier Comfort Network
(CCN) technicians. The following checkout procedure
is offered as a guide and presumes the user has obtained
basic knowledge of controls through CCN training.
For example: If the submaster loop gain is 5.0, change
it to -5.0.
TO CHECK OPERATION OF ANALOG OUTPUTS — The
control algorithms of the unit controls utilize the master/
submaster loop concept. The master loop monitors the
master sensor (the sensor which tries to maintain the desired
set point), and calculates the submaster reference required to
do so. The submaster loop monitors the submaster sensor
and controls the actual output to the controlled device.
These algorithms require the adjustment of a number of
gain values to function properly. The 48/50MP units come
with preset default values. However, it may be necessary to
adjust several of these values to achieve stable control. These
values are submaster loop gain (SMG), submaster loop cen-
ter value (SCV), and master loop gain (MLG). In addition,
proportional, integral, and derivative multiplier values can
be accessed through the Building Supervisor, Service Tool,
or ComfortWorks™ software.
6. Observe the operation of the controlled device for a few
minutes. If the device oscillates every few seconds around
the forced value, then lower the SMG by small amounts
until the output steadies. If the output to the device re-
sponds to a change in the temperature in small incre-
ments, then increase the SMG in small amounts until
the output steadies.
NOTE: Do not be alarmed if the submaster sensor sta-
bilizes at a value greater or less than the forced value.
This is called the submaster droop offset and is normal.
7. It is not necessary to adjust the submaster loop center
value, as the master loop will adjust the submaster ref-
erence as required to satisfy its set point. However, it
may be desirable to keep the submaster droop to a mini-
mum. This is most often required for economizer loops.
To verify or adjust submaster default values, perform the
following for each controlled device (control loop):
If the submaster droop is too large, adjust the SCV as
follows:
If the submaster droop is positive (actual value greater
than reference value), the SCV should be decreased for
HCV (heating coil) and IGV (supply fan VFD) loops
and increased for CC (cooling control) and ECON (econo-
mizer) loops.
1. Verify that the system is in the Occupied mode and the
supply-air fan is running.
2. Verify that the supply-air fan status indicates ON. If the
fan status is OFF, the unit control algorithms will dis-
able all routines.
3. Verify that all forced values have been removed.
4. Table 27 indicates recommended starting values for MLG
and SMG for 48/50MP units. Verify that these values
have been entered by checking the service function.
If the submaster droop is negative (actual value less than
reference value), the SCV should be increased for HCV
and IGV loops and decreased for CC and ECON loops.
Table 27 — 48/50MP Units SMG, SCV and MLG Recommended Starting Values
SERVICE
SUBFUNCTION
(HSIO)
GAIN VALUE
FUNCTION/GAIN OR SCV
CV Application
VAV Application
Cooling Control
MLG
8
1.0
1.0
Economizer
MLG
10
10
10
1.0
−7.5
50
1.0
−7.5
50
SMG
SCV
Duct Pressure (VFD)
MLG
SMG
SCV
9
9
9
N/A
N/A
N/A
1.0
2.0*
35*
Building Pressure
MLG
SMG
SCV
18
18
18
1.0
−5.0
50
1.0
−5.0
50
Staged Heat
MLG †
SMG †
11
11
1.0
5.0
1.0
5.0
Heating Coil
MLG
7
7
7
1.0
7.5
50
1.0
7.5
50
SMG
SCV
Humidifier
MLG
17
17
17
1.0
7.5
50
1.0
7.5
50
SMG
SCV
*Factory setting; differs from new control setting.
†48MP only.
LEGEND
CV
—
—
—
—
—
Constant Volume
MLG
SCV
SMG
VAV
Master Loop Gain
Submaster Center Value
Submaster Loop Gain
Variable Air Volume
41
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Once the submaster loop is adjusted, remove all forced
values and proceed with verification and adjustment of
master loop.
CONTROL SYSTEM
General — The control system consists of the following
components:
9. To check the master loop:
• standard processor module (PSIO 8088 or PSIO1)
• options processor module (PSIO 8052 or PSIO2)
• two standard high-voltage relay modules (DSIO-HV or
DSIO1 and DSIO2)
• keypad and display module (HSIO or LID)
• enthalpy sensor
Create a demand in the master loop. For example: Force
the actual space temperature to a value less than the heat-
ing set point or greater than the cooling set point.
10. Observe system (loop) response for 10 to 20 minutes to
verify stable control. After 10 minutes, if the output con-
tinues to swing from full open to full closed, lower the
MLG and observe again.
11. Do this until the loop operation is stable. After 10 min-
utes, if the loop does not seem to respond (little change
in submaster reference), increase the MLG and observe
again. Do this until stable operation is achieved.
• thermistors
• pressure transducers
• accessory humidity sensors
• space temperature sensors (standard T55 and accessory T56)
• supply-air fan status switch
• check filter switch
12. Once satisfied with loop operation, remove all forced
values which may have been initiated during this
procedure.
Components
PROCESSOR MODULE NO. 1 — The PSIO1 module moni-
tors and processes the following inputs, outputs, and system
information:
13. Repeat Steps 1-12 until all loops have been checked.
NOTE: For better tuning, the building supervisor or service
tool should be used to adjust the proportional and integral
terms. Contact your Carrier representative for more details.
Inputs:
• transducers
• thermistors
• switches
Outputs:
• condenser-fan contactors
• integrated economizer motor (4 to 20 mA)
• optional supply duct static pressure control (VFD) (4 to
20 mA)
• optional modulating power exhaust control (VFD)
(4 to 20 mA)
IAQ Control Loop Adjustment — The IAQ (indoor
air quality) control loop is different from the other control
loops. It has one gain value that can be adjusted in the serv-
ice subfunction (
) under IAQG (indoor-air quality
gain). This gain is used to speed up or slow down the
response of the economizer dampers to the difference be-
tween the IAQ set point and the IAQ sensor. If the econo-
mizer is moving too slowly, then the gain needs to be
increased. If the economizer moves too rapidly and over-
shoots the set point, then the gain should be reduced.
System Information:
• generates alert and alarm information (via transducer, ther-
mistor, and sensor inputs)
• supports CCN level II communications
• supports digital air volume (DAV) interface
NOTE: The correct module address for the PSIO1 is 01 (S1
set at 0; S2 set at 1).
PROCESSOR MODULE NO. 2 — The PSIO2 module sup-
ports the sensors used for:
Lead/Lag Circuits — Lead/lag circuits and compres-
sors are shown in Table 20.
• humidity control
• outdoor-air cfm
• indoor-air quality (IAQ)
• smoke control
Table 29 — Index of Lead/Lag Circuits and
Compressors
• superheat monitoring (only when accessory transducer ther-
mistor kit is field-installed).
In addition, the PSIO2 supplies the outputs for humidity
and hydronic heating coil control and a discrete output with
timed clock control (for outdoor building or parking lot lights).
UNIT 48/50MP
62L
70M
82N, 90P, 10R
LEAD CIRCUIT
Compressor, Lead
Compressor, Lag
A
A1
*
A
A1
A2
A
A1
A2
LAG CIRCUIT
Compressor, Lead
Compressor, Lag
B
B1
*
B
B1
*
B
B1
B2
NOTE: The correct module address for the PSIO2 is 31 (S1
set at 3; S2 set at 1).
*Circuit only has 1 compressor.
HIGH-VOLTAGE RELAY MODULES (DSIO) — The DSIO
modules close contacts to energize evaporator and con-
denser fan contactors. The modules also control compressor
unloaders, compressor contactors, compressor crankcase heat-
ers, heat interlock function, and power exhaust contactor.
The compressor status through the compressor lockout (CLO)
relays and high-pressure switches (safety circuits) are the in-
puts to these modules.
Final Checks — Ensure all safety controls are opera-
ting, control panel covers are on, and the service panels are
in place.
Recheck all set points against project specifications. Com-
plete Start-Up Checklist and record operating values. Leave
completed checklist with unit for future reference.
NOTE: The correct module addresses for the DSIO1 and DSIO2
modules are 19 and 49, respectively. Set the switch closest
to the mounting plate at 1 (DSIO1) or 4 (DSIO2), and the
other switch at 9 (both modules).
NOTE: If the REMOTE START function is used in this ap-
plication, set the LOCAL/REMOTE switch to REMOTE (On)
at the end of start-up.
42
Download from Www.Somanuals.com. All Manuals Search And Download.
Motor Protection — Manual reset, calibrated trip, mag-
netic circuit breakers are provided for each compressor, sup-
ply fan motor, and optional exhaust fan motor.
Outdoor fan motor circuits are also protected by circuit
breakers.
KEYPAD AND DISPLAY MODULE (HSIO)
IMPORTANT: The HSIO (human sensor input/output)
keypad and display module is required for initial start-up
of these units. All units are shipped in standby mode,
and the HSIO must be used to change the unit to run
mode. Once the unit is in run mode, the HSIO is not
required for normal operation.
Refer to the Service section more information on serv-
icing motors.
Variable Frequency Drive (VFD) — An optional VFD
can be factory-installed and is used to modulate supply fan
airflow to maintain duct static pressure on VAV applications.
The keypad and display module HSIO (or local interface
device, LID, factory-installed and located in the main
control box) provides unit function information at the unit.
The module consists of a keypad with 6 function keys,
5 operative keys, 10 numeric keys (0 through 9), and an
alphanumeric 8-character liquid crystal display (LCD). Key
usage is explained in Table 23. Each function has one or more
subfunctions as shown in Table 29.
A second VFD can be used to modulate exhaust fan airflow
to maintain building pressure on units equipped with modu-
lating power exhaust option.
The supply fan VFD is located in the auxiliary control
compartment, on the left hand side of the unit, at the end of
the supply fan section.
The HSIO keypad and display module is installed through
connection of the power and communication plugs and can
be easily moved from one unit to another. Because of this
flexibility, one HSIO can be used for several units.
Unit operation is controlled by the status of the RUN/
STANDBY mode on the HSIO. To access the mode, press
The modulating power exhaust VFD is located in the ex-
haust fan compartment, on the right hand side of the unit, at
the return air end.
Control input to the supply fan VFD is provided by a 4 to
20 mA signal from the PSIO1 (Channel 16).
Control input to the exhaust fan VFD is provided by a
4 to 20 mA signal from the PSIO1 (Channel 15).
on the HSIO keypad, and then use the
Set point control for the VFD is done through the HSIO
key. The HSIO will display either STBY YES or STBY NO.
or other network devices (subfunction
). Refer to the
CLEAR
ENTER
To enable the unit, press
or
and press
while
Controls and Troubleshooting manual for configuration in-
structions and sequence of operation.
The VFD has been programmed at the factory for 48/
50MP applications. No further adjustments should be nec-
essary at start-up.
at the STBY YES display. To disable the unit, press
ENTER
while at the STBY NO display. Clearing an alarm
that has stopped unit operation is accomplished by entering
the
STBY
YES
mode.
A separate technical and service manual for the factory
installed VFD is supplied with each unit. Refer to the VFD
manual for more information on accessing and diagnosing
the VFD controls.
IMPORTANT: Use the STBY YES mode when ser-
vicing the unit or running the Quick Test feature.
DISPLAY AND KEYPAD — All functions of the VFD are
accessed using the Digital Operator. See Fig. 49. The Digital
Operator has a 4-digit LED display. By pressing the
IMPORTANT: If unit is also equipped with REMOTE
START function, place LOCAL/REMOTE switch in
LOCAL (Off) position when servicing or running Quick
Test feature.
DSPL key on the Digital Operator while the drive is stopped,
the user can step to each of the 16 functions and displays.
See Table 30.
Default Set Points/Changing Set Points — Re-
fer to Table 24 for factory default configuration and set point
values.
Record any changes made during start-up and leave with
unit for future reference.
These values may be changed from the HSIO keypad at
any time. If changing values via Service Tool or CCN Build-
ing Supervisor, the unit must be in RUN mode (STBY NO),
which is done through HSIO input or a Remote Start input.
After changing the values in subfunction
Reset function must be enabled.
, the Data
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 29 — HSIO Keypad and Display Module Functions and Subfunctions
FUNCTIONS
SUB
FUNCTION
NO.
Status
History
Schedule
Service
Set Point
Test
Occupied
Mode
Override
(Unit)
Current
Alarms
Log on and
Log off
System
Set Point
Test of
Inputs
1
Alarms
Current
Alerts
Period 1
(Unit)
Software
Version
Demand
Limit
Analog
2
3
Maintenance
—
Outputs
Current
Operating
Modes
Period 2
(Unit)
Factory
Configuration
Current
Time
Discrete
Outputs
Daylight
Savings
Time
Capacity
Stages
Period 3
(Unit)
Test
4
5
—
—
Bus Address
Compressors
Current
Operating
Set Points
Period 4
(Unit)
Units
of Measure
Configure
Holiday
Test Heat
System
Period 5
(Unit)
User
6
7
8
9
—
—
—
—
—
—
—
—
Exit Test
Temperatures
Configuration
System
Pressures
Period 6
(Unit)
Heating Coil
Cooling
—
—
—
Period 7
(Unit)
Inputs
Analog
Outputs
Period 8
(Unit)
Duct Pressure
Occupied
Mode
Override
(TDO)
Discrete
Outputs
10
—
Economizer
—
—
Run/
Period 1
(TDO)
11
12
—
—
Heat
—
—
—
—
Standby
Period 2
(TDO)
Nighttime
Free Cool
—
—
Adaptive
Optimal
Start/Stop
Period 3
(TDO)
13
—
—
—
Period 4
(TDO)
Temperature
Reset
14
15
16
17
18
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Period 5
(TDO)
Configure
Loadshed
Period 6
(TDO)
Configure IAQ
Period 7
(TDO)
Configure
Humidity
Period 8
(TDO)
Building
Pressure
19
20
—
—
—
—
—
—
Alert Limits
—
—
—
—
Service History
Service
Maintenance
Alarm
21
22
—
—
—
—
—
—
—
—
—
—
Override History
LEGEND
Indoor-Air Quality
Timed Discrete Output
IAQ
TDO
—
—
44
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 30 — Variable Frequency Drive (VFD) Display
SERVICE
DISPLAY
Fref
ACTION
Service Access — All unit components can be reached
through clearly labeled hinged access doors. These doors are
equipped with tiebacks, but if heavy duty servicing is needed,
it is recommended that the doors be removed or propped open.
Not used.
Displays the output frequency at which the VFD is cur-
rently operating. This is a display only function. The user
cannot change this displayed value.
Fout
lout
Each door is held closed with 3 latches. The latches are
Displays the level of output current that the VFD is cur-
rently producing. This is a display only function. The user
cannot change this displayed value.
1
1
secured to the unit with a single ⁄4-in. Ϫ20 x ⁄2-in. long
bolt. See Fig. 50.
Displays the output power that the VFD is currently pro-
ducing. This is a display only function. The user cannot
change this displayed value.
To open, loosen the latch bolt using a 7/16-in. wrench.
Pivot the latch so it is not in contact with the door. Open the
door. To shut, reverse the above procedure.
kWout
F/R
Sets the rotation direction of the motor when a run com-
mand is given.
NOTE: Disassembly of the top cover may be required under
special service circumstances. It is very important that the
orientation and position of the top cover be marked on the
unit prior to disassembly. This will allow proper replace-
ment of the top cover onto the unit and prevent rainwater
from leaking into the unit.
ENTER
Press
to access the monitor parameters
Montr
(U-01 through U-13).
Not used.
Accel
Decel
Vmtr
Not used.
Sets the rated voltage of the motor.
Sets a preset V/f pattern or allows a custom V/f pattern
to be set.
V/F
IMPORTANT: After servicing is completed, make sure
door is closed and relatched properly, and that the latches
are tight. Failure to do this can result in water leakage
into the indoor-air section of the unit.
Sets the frequency reference gain for the analog fre-
quency reference.
Fgain
Fbias
FLA
Sets the frequency reference bias for the analog fre-
quency reference.
Sets the full load amps used for detecting motor over-
load. When FLA is set to 0 it is disabled.
PID
Enables or disables the PID.
kWsav
PRGM
Enables or disables the energy saving function.
Allows parameter programming.
LEGEND
PID
—
Proportional Integral Derivative
REMOTE Mode indication LEDs.
The LEDs light when REMOTE
Mode has been selected.
REMOTE
REF
SEQ
4-digit, 7-segment LED
display; shows selected
operation status, fault code,
or parameter data.
DISPLAY SECTION
Fref
F/R
Fout
Montr
V / F
PID
lout
kWout
Accel Decel
Fgain Fbias
Function LEDs
Vmtr
FLA
kWsav PGRM
Switch between Function
LEDs*
DIGITAL OPERATOR
JVOP-131
KEYPAD SECTION
Increase parameter
number or displayed
value.
Displays data to be
changed, and enters new
data.*
DSPL
ENTER
Switch between LOCAL
and REMOTE operation
modes.
LOCAL
REMOTE
Decrease parameter number
or displayed value.
STOP
RESET
RUN
Stop the motor, or reset a
drive fault. LED lights when
drive is in stopped condition.
Run the motor. LED lights
when drive is controlling
motor speed.
*Pressing DSPL and ENTER keys simultaneously allows all parameter
data to be read, but not set, while the drive is running.
Fig. 49 — VFD Digital Operator
45
Download from Www.Somanuals.com. All Manuals Search And Download.
GAS HEAT SECTION — Access to the gas heat section is
through the door labeled ‘‘HEAT SECTION’’ on the right
hand side of the unit. All gas system components are in the
gas section. On 48MP62L and 70M units, additional access
to the gas components is through the access panels in the
unit corner post at the gas section. See Fig. 51.
UNIT CONTROL BOX —Access to this component is through
the doors marked ELECTRICAL SECTION on the con-
denser end of the unit.
ECONOMIZER DAMPER MOTORS — The economizer
motors are located in the return air section. Access to the
motors is through the doors labelled FAN SECTION on the
each side of the unit.
Fig. 50 — Door Latch
RETURN-AIR FILTERS — Access to these filters is through
the door marked FILTER SECTION on the right side of the
unit.
UNIT CONTROL BOX — Viewed facing compressors, the
control box is at the left end of the unit. Incoming power for
controls, refrigerant system, and fan system enters through
the control box. The control box contains power compo-
nents and electronic controls. Outer panels are hinged and
latched for easy opening. Remove screws to remove inner
panels. Outer panels can be held open for service and in-
spection by using a door retainer on each panel. Remove
bottom pin from door retainer assembly, swing retainer out
horizontally, and engage pin in one of the retainer ears in the
hinge assembly.
CONDENSER FANS AND FAN MOTORS — Remove the
wire fan guard on top of the unit to gain access to the con-
denser fans and motors.
Cleaning — Inspect unit at the beginning of each heating
and cooling season and during each season as operating con-
ditions may require.
Clean condenser coil with a vacuum cleaner, fresh water,
compressed air, or a bristle brush (not wire). Coil cleaning
should be a part of the planned maintenance program. Clean
evaporator coil with a stiff bristle brush (not wire), vacuum
cleaner, or compressed air.
Check and clean condensate drain annually at the start of
the cooling season.
Replace return-air filters at the start of each heating and
cooling season or as often as necessary during each season,
depending on operating conditions. See Table 1 for filter types,
quantities, and sizes.
COMPRESSORS — The oil pump end (compressor access)
of each compressor is readily accessible from sides of unit
as shown in Fig. 51. Access the motor end of the compressor
through the condenser end of the unit or by removing
compressor.
LIQUID SERVICE VALVES, SOLENOID VALVES, FIL-
TER DRIERS, AND SIGHT GLASSES — These compo-
nents are located in the inside corner of the condenser sec-
tion on the right-hand side of the unit. Filter driers are
replaceable-core type. See Fig. 51.
1. Remove economizer outdoor-air filters from the hoods by
removing the filter retainers.
2. Clean filters with steam or hot water and mild detergent.
3. Reinstall filters in hoods after cleaning. Never replace clean-
able filters with throwaway filters.
EVAPORATOR-FAN MOTORS, PULLEYS, AND BELTS
— Access to these components is through the 2 doors
labeled FAN SECTION on each side of the unit.
POWER EXHAUST MOTORS, PULLEYS, AND BELTS
— Access to these components is through the doors at the
return air end of the unit.
Fig. 51 — Access Locations (48MP70M Unit Shown)
46
Download from Www.Somanuals.com. All Manuals Search And Download.
MAIN BURNERS (48MP Only) — At the beginning of each
heating season, inspect for deterioration or blockage due to
corrosion or other causes. Observe the main burner flames.
Refer to Main Burners section on page 52.
All units are shipped with a complete operating charge of
R-22. See unit nameplate and Table 1 for amount of charge.
When adding a complete charge, evacuate system using stand-
ard evacuating procedures and weigh in the specified amount
of charge. All units have charging charts for each refrigerant
circuit. See Fig. 55-59.
FLUE GAS PASSAGEWAYS (48MP Only) — The flue col-
lector box and heat exchanger cells may be inspected by re-
moving heat exchanger access panel (Fig. 3 and 4), flue box
cover, and main burner assembly (Fig. 52). Refer to Main
Burners section on page 52 for burner removal sequence. If
cleaning is required, remove heat exchanger baffles and clean
tubes with a wire brush.
Use caution with ceramic heat exchanger baffles. When
installing retaining clip, be sure the center leg of the clip
extends inward toward baffle. See Fig. 53.
COMBUSTION-AIR BLOWERS (48MP Only) — Clean pe-
riodically to assure proper airflow and heating efficiency. In-
spect blower wheel every fall and periodically during heat-
ing season. For the first heating season, inspect blower wheel
bi-monthly to determine proper cleaning frequency.
To inspect blower wheel, remove heat exchanger access
panel. Shine a flashlight into opening to inspect wheel. If
cleaning is required, remove motor and wheel assembly by
removing screws holding motor mounting plate to top of com-
bustion fan housing (Fig. 54). The motor and wheel assem-
bly will slide up and out of the fan housing. Remove the
blower wheel from the motor shaft and clean with a deter-
gent or solvent. Replace motor and wheel assembly.
Lubrication
Fig. 52 — Burner Section Detail
COMPRESSORS — Each compressor is correctly charged
at the factory. Refer to 06E Compressor Service Manuals if
additional information regarding compressor lubrication sys-
tem is required. See Compressor Oil section on page 29 and
Table 3.
CERAMIC
BAFFLE
CLIP
FAN SHAFT BEARINGS — Lubricate fan shaft bearings at
least once a year with suitable bearing grease. Extended grease
lines are provided on pulley side of blower. Typical lubri-
cants are given below:
MANUFACTURER
LUBRICANT
Texaco
Mobil
Sunoco
Texaco
Regal AFB-2*
Mobilplex EP No. 1
Prestige 42
Multifak 2
*Preferred lubricant because it contains rust and oxidation inhibitors.
HEAT EXCHANGER
TUBES
FAN MOTOR BEARINGS — The condenser- and evaporator-
fan motors have sealed bearings so no field lubrication is
required.
NOTE: One baffle and clip wll be in each upper tube of the heat
exchanger.
Fig. 53 — Removing Heat Exchanger Ceramic
Baffles and Clips
DOOR HINGES — All door hinges should be lubricated at
least once a year.
Coil Cleaning — Clean the coils with a vacuum cleaner,
compressed air, water, or a non-wire bristle brush.
Refrigerant Circuit
LEAK TESTING — Units are shipped with a full operating
charge of R-22 (see Table 1). If there is no pressure in
the system, introduce enough nitrogen to search for the leak.
Repair the leak using good refrigeration practices. After leaks
are repaired, system must be evacuated and dehydrated
using methods described in GTAC II, Module 4, System
Dehydration.
REFRIGERANT CHARGE (Refer to Table 1) — At the liq-
uid line connection point on each circuit is a factory-
installed liquid line service valve. On each valve is a 1⁄4-in.
Schrader connection for charging liquid refrigerant.
Fig. 54 — Combustion Blower Removal
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 55 — Charging Chart — Unit 48/50MP62L
Fig. 56 — Charging Chart — Unit 48/50MP70M
Fig. 57 — Chrging Chart — Unit 48/50MP82N
48
Download from Www.Somanuals.com. All Manuals Search And Download.
150
125
100
75
ADD CHARGE IF ABOVE CURVE
REMOVE CHARGE IF BELOW CURVE
50
100
150
200
250
300
350
400
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
ALL OUTDOOR FANS MUST BE OPERATING
Fig. 58 — Charging Chart Unit 48/50MP90P
150
125
150
130
110
90
ADD CHARGE IF ABOVE CURVE
REMOVE CHARGE IF BELOW CURVE
ADD CHARGE IF ABOVE CURVE
100
75
REMOVE CHARGE IF BELOW CURVE
70
50
50
300
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
350
400
450
150
200
100
250
100
150
200
250
300
350
400
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
ALL OUTDOOR FANS MUST BE RUNNING
Fig. 59 — Charging Chart — Unit 48/50MP10R
Charging with Unit Off and Evacuated — Close liquid
line service valve before charging. Weigh in charge shown
in Table 1. Open liquid line service valve; start unit and
allow it to run several minutes fully loaded. Check for a clear
sight glass. Be sure clear condition is liquid and not vapor.
Complete charging the unit.
IMPORTANT: For units with 2 compressors per re-
frigeration circuit, both compressors must be running
to adjust the oil level. Two oil level equalizer lines be-
tween compressors distribute the oil to each
compressor.
Charging with Unit Running — If charge is to be added while
unit is operating, it is necessary to have all condenser fans
and compressors operating. It may be necessary to block con-
denser coils at low-ambient temperatures to raise condens-
ing pressure to approximately 280 psig (1931 kPag) to turn
all condenser fans on. Do not totally block a coil to do this.
Partially block all coils in uniform pattern. Charge vapor into
compressor low-side service port located above oil pump crank-
shaft housing. Charge each circuit until sight glass shows
clear liquid.
REMOVE OIL — Pump down compressor to 2 psig
(14 kPag). Loosen the 1⁄4-in. (6.4-mm) pipe plug at the com-
pressor base and allow the oil to seep out past the threads of
the plug.
NOTE: The crankcase will be slightly pressurized. Do not
remove the plug, or the entire oil charge will be lost.
Small amounts of oil can be removed through the oil pump
discharge connection while the compressor is running.
Oil Charge (Refer to Table 3) — All units are fac-
tory charged with oil. Acceptable oil level for each compres-
sor is from 3⁄8 to 1⁄8 (on 06E299, 1⁄8 max) of sight glass (see
Fig. 44, page 29).
When additional oil or a complete charge is required, use
only Carrier-approved compressor oil.
Moisture/Liquid Indicator — A clear flow of liquid
refrigerant indicates sufficient charge in the system. Bubbles
indicate undercharged system or the presence of non-
condensables. Moisture in the system measured in parts per
million (ppm) changes the color of the indicator:
Green
Chartreuse — 45 to 130 ppm (caution!)
Yellow — moisture above 130 ppm (wet)
— moisture below 45 ppm (dry)
Approved oils are:
Petroleum Specialties, Inc. — Cryol 150A (factory oil charge)
Change filter driers at the first sign of moisture in the sys-
tem. See Carrier Charging Handbook for more information.
Texaco, Inc.
Witco Chemical Co.
— Capella WF-32-150
— Suniso 3GS
Do not reuse drained oil, and do not use any oil that has
been exposed to atmosphere.
IMPORTANT: Unit must be in operation at least
12 hours before moisture indicator can give an accu-
rate reading. With unit running, indicating element must
be in contact with liquid refrigerant to give a true
reading.
ADD OIL — Close suction shutoff valve and pump down
crankcase to 2 psig (14 kPa). (Low-pressure cutout must be
jumped.) Wait a few minutes and repeat until pressure re-
mains steady at 2 psig (14 kPa). Remove oil fill plug above
the oil level sight glass, add oil through plug hole, and re-
place plug. Run compressor for 20 minutes and check oil
level.
Filter Driers — The 48/50MP units use replaceable core
type filter driers, one in each refrigeration circuit. The filter
driers are located in the condenser sections, accessible from
the right side of the unit.
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Replace the filter cores whenever the moisture/liquid in-
dicator shows moisture in the system.
Follow instructions on the packaging for the replacement
cores for disassembling and reassembling the filter assem-
blies and housings.
Pressure Relief — High-side pressure relief is
provided by a fusible plug in the liquid line at the serv-
ice valve. For low-side pressure relief, a fusible plug is
inserted in the side of the accumulator. See Fig. 60. A pres-
sure relief valve installed on the compressor relieves at
450 psig (3102 kPag).
Liquid Line Service Valve — Located immediately
ahead of the filter drier, this valve has a 1⁄4-in. flare connec-
tion for field charging. With the liquid circuit shut, the com-
pressor can be used to pump the refrigerant down into the
high side. The refrigerant can then be stored there by closing
the compressor discharge valve.
Adjustments
EVAPORATOR FAN AND POWER EXHAUST MOTOR
PLATE — Adjust using a 15⁄16-in. wrench on the adjusting
bolts:
1. Loosen holddown bolts. (See Fig. 61.)
Compressor Suction and Discharge Service
2. Turn the adjusting bolts to move the motor mounting plate
toward or away from the fan to loosen or tighten the belts.
Make the same number of turns to each bolt.
3. Retighten holddown bolts.
BELT INSTALLATION AND TENSIONING
Valves — Each compressor is provided with suction and
discharge service valves. With these valves, the compressor
can be isolated from the refrigerant system for servicing or
replacing.
High-Pressure Switch — This switch has nonadjust-
able settings. Figure 60 shows connection on a cylinder head.
See Table 31 for pressure switch settings.
IMPORTANT: When installing or replacing belts, al-
ways use a complete set of new, matched belts to pre-
vent potential vibration problems. Mixing belts often
results in premature breakage of the new belts.
Table 31 — Pressure Switch Settings,
Psig (kPag)
1. Turn off unit power.
SWITCH
High
CUTOUT
CUT-IN
2. Adjust motor plate so belts can be installed without stretch-
ing over the grooves of the pulley. (Forcing the belts can
result in uneven belt stretching and a mismatched set of
belts.)
426 ± 7
(2935 ± 48)
320 ± 20
(2205 ± 138)
27 ± 4
(186 ± 28)
67 ± 7
(462 ± 48)
Low
3. Before tensioning the belts, equalize belt slack so that it
is on the same side of the belt for all belts. Failure to do
so may result in uneven belt stretching.
NOTE: High-pressure switch must be removed from cylin-
der head before removing compressor from the unit.
4. Tighten belts using the motor plate adjusting bolts.
TO CHECK — Slowly close the discharge shutoff valve
until the compressor shuts down. This should be at approx-
imately 426 psig (2935 kPag). Slowly open the valve. When
the pressure drops to approximately 320 psig (2205 kPag),
the pressure switch resets. To reenergize the control circuit,
manually switch the fan circuit breaker off and then on. The
compressor starts again under Time Guard controls.
5. Adjust until proper belt tension (1/2-in. deflection with
one finger) is obtained. Be sure to adjust both adjusting
bolts the same number of turns.
NOTE: Check the tension at least twice during the first
day of operation, as there is normally a rapid decrease in
tension until the belts have run in. Check tension
periodically thereafter and keep it at the recommended
tension.
Low-Pressure Switch — The low-pressure switch (LPS)
has fixed nonadjustable settings. It is located at the pump
end of the compressor above the bearing head. See Table 31
for pressure switch settings.
With the correct belt tension, belts may slip and squeal
momentarily on start-up. This slippage is normal and dis-
appears after wheel reaches operating speed. Excessive belt
tension shortens belt life and may cause bearing and shaft
damage.
TO CHECK — Slowly close the suction cut-off valve and
allow the compressor to shut down. This should occur at
approximately 27 psig (186 kPag). Slowly open the valve.
The compressor restarts under Time Guard control when the
pressure builds to approximately 67 psig (462 kPag).
50
Download from Www.Somanuals.com. All Manuals Search And Download.
HIGH-
PRESSURE
SWITCH
CYLINDER
HEADS
MUFFLER
SIGHT
GLASS
OIL
EQUALIZER
LINE
LOW-
RAIL
CRANKCASE
HEATER
SIGHT
GLASS
MOUNTING
SPRING
(HIDDEN)
PRESSURE RELIEF
VALVE
PRESSURE
SWITCH
NOTE: Units 48/50MP62L compressors are pan mounted. Units 48/50MP70M and 82N
compressors are mounted on rails.
Fig. 60 — 06E Compressors, Typical
Fig. 61 — Motor Plate Adjustment
51
Download from Www.Somanuals.com. All Manuals Search And Download.
PULLEY ALIGNMENT — For proper belt life, the motor
and fan pulleys must be properly aligned. To check, first turn
off unit power. Place a straightedge against the motor and
fan pulleys. See Fig. 62. If the pulleys are properly aligned,
the straightedge should be parallel to the belts.
If they are not parallel, check that the motor shaft and fan
shaft are parallel. If they are not, adjust the motor plate
adjusting bolts until they are.
6. Remove screw cap covering regulator adjustment screw
(see Fig. 63).
7. Turn adjustment screw clockwise to increase pressure or
counterclockwise to decrease pressure.
8. Once desired pressure is established, set thermostat set-
ting for no call for heat, turn off main gas valve, remove
1
pressure-measuring device, and replace ⁄8-in. pipe plug
and screw cap.
After verifying that the shafts are parallel, loosen the set-
screws on the motor pulley. Move pulley on the shaft until
the pulleys are parallel. To move the sheave on the shaft,
loosen the belts. If necessary, blower sheave can also be moved
on the shaft.
Fig. 63 — Gas Valve
Main Burners — For all applications, main burners are
factory set and should require no adjustment.
MAIN BURNER REMOVAL
1. Shut off (field-supplied) manual main gas valve.
2. Shut off power to unit.
3. Remove gas section access door, door frame, and corner
post.
4. Disconnect gas piping from gas valve inlet.
5. Remove wires from gas valve.
6. Remove wires from rollout switch.
7. Remove sensor wire and ignitor cable from IGC board.
8. Remove 2 screws securing manifold bracket to
basepan.
9. Remove 2 screws that hold the burner support plate flange
to the vestibule plate.
10. Lift burner assembly out of unit.
Protective Devices
COMPRESSOR PROTECTION
Overcurrent — Each compressor has one manual reset, cali-
brated trip, magnetic circuit breaker. Do not bypass connec-
tions or increase the size of the circuit breaker to correct trouble.
Determine the cause and correct it before resetting the breaker.
Crankcase Heater — Each compressor has a crankcase heater
to prevent absorption of liquid refrigerant by oil in the crank-
case when the compressor is idle. Since 115-v power for the
crankcase heaters is drawn from the unit control circuit, main
unit power must be on for the heaters to be energized.
Fig. 62 — Pulley Alignment
Gas Valve Adjustment
NATURAL GAS — The gas valve opens and closes in re-
sponse to the PIC control or limit control.
IMPORTANT: After a prolonged shutdown or service
job, energize the crankcase heaters for 24 hours before
starting the compressor.
When power is supplied to valve terminals D1 and C2,
the main valve opens to its preset position.
The regular factory setting is stamped on the valve body
(3.3 in. wg).
To adjust regulator:
1. Set thermostat at setting for no call for heat.
2. Turn main gas valve to OFF position.
3. Remove 1⁄8-in. pipe plug from manifold or gas valve pres-
sure tap connection. Install a suitable pressure-measuring
device.
Compressor Lockout — If any of the safeties (high-pressure,
or low-pressure) trip, or if there is a loss of power to the
compressors, the compressors will be locked out. To reset,
consult the controls and troubleshooting literature for the
appropriate unit for details.
EVAPORATOR-FAN MOTOR PROTECTION — A manual
reset, calibrated trip, magnetic circuit breaker protects against
overcurrent. Do not bypass connections or increase the size
of the breaker to correct trouble. Determine the cause and
correct it before resetting the breaker.
4. Set main gas valve to ON position.
5. Set thermostat at setting to call for heat.
52
Download from Www.Somanuals.com. All Manuals Search And Download.
CONDENSER-FAN MOTOR PROTECTION — Each
condenser-fan motor is internally protected against over-
temperature. They are also protected against a severe over-
current condition by manual reset, calibrated trip, magnetic
circuit breakers on a common circuit. As with the circuit break-
ers, do not bypass connections or increase breaker size to
correct trouble. Determine the cause and correct it before
resetting the breaker.
pressed. The fault code will also be entered into the fault
register. The register retains, in sequence, the last 3 fault codes.
A newly occurring fault code will not change the fault reg-
ister if it a recurrence of the most recently entered fault. The
contents of the register can be displayed by performing the
following steps:
1. Press DSPL until the MONTR LED is on.
2. Press
3. Press
4. Press
until U-09 is displayed.
HIGH- AND LOW-PRESSURE SWITCHES — See Fig. 60
for compressor mounting locations. Settings for these switches
are shown in Table 33. If either switch trips, that refrigerant
circuit will be automatically locked out by the controls. To
reset, interrupt control power.
ENTER
. The current fault code will be displayed.
. The display will indicate that this is the first
code in the memory register.
NOTE: When a pressure transducer is used, the low pres-
sure trip point is the same as the low-pressure switch.
5. Continue to press
to display the other codes in the
fault resister. After the last code has been displayed, the
sequence will return to the first code.
Variable Frequency Drive (VFD)
SUPPLY FAN VFD — The optional supply fan VFD is lo-
cated in the auxiliary control box. Wiring should only be
performed by qualified personnel. All parameters have been
factory set. Do not change parameters unless necessary.
The VFD can be easily damaged by static electricity. Use
proper electrostatic discharge procedures when handling the
controls of the VFD.
Never connect main circuit output terminals T1, T2, and
T3 to AC main circuit power supply. Always ground the VFD
using the designated ground terminal. Refer to the VFD tech-
nical manual for more information.
The VFD can indicate faults and alarms. A blinking alarm
condition is a warning that a trouble condition will occur or
that there is a problem in the external circuitry. The VFD
will continue to operate during an alarm condition. Alarm
conditions are not entered into the fault register.
Control Modules — The standard PSIO1 and optional
PSIO2 (processor modules) and standard DSIO1 and DSIO2
(high-voltage relay modules) all perform continuous diag-
nostic evaluations of the hardware condition. Proper opera-
tion of these modules is indicated by 2 light-emitting diodes
(LED) on the front surface of the DSIO modules and on the
top horizontal surface of the PSIO modules.
RED LED — Blinking continuously at a 3 to 5 second rate
indicates proper operation. Lit continuously indicates a prob-
lem requiring replacement of the module. Off continuously
indicates the power supply should be checked. If there is no
input power, check the fuses. If a fuse is bad, check for shorted
secondary of the transformer or a bad module.
GREEN LED — On a PSIO module, this is the green light
that is closest to the COMM connectors. The other green
LED on the module indicates external communications (when
used). The green LED should always be blinking when power
is on. It indicates that the modules are communicating prop-
erly. If the green LED is not blinking, check the red LED.
If the red LED is normal, check the module addresses.
A steady fault indicator is displayed when the VFD fault
relay has tripped. The motor will coast to a stop, and a fault
signal is output is present.
Refer to the VFD technical manual for more information
on alarms and faults.
NOTE: If the wrong address is entered for the DSIO1 and 2
and/or PSIO1 and 2, then the wrong input channel will be
read and the wrong output channel energized.
If all modules indicate a communication failure, check the
COMM plug on the PSIO module for proper seating. If a
good connection is made and the condition persists, replace
the PSIO module.
If only the DSIO module indicates a communication fail-
ure, check the COMM plug on that module for a proper con-
nection. If a good connection is made and the condition
persists, replace the DSIO module.
EXHAUST FAN VFD — The optional exhaust fan VFD con-
sists of an exhaust fan, motor, VFD, and pressure transducer.
All components (except the tranducer) are located in the re-
turn air section of the 48/50MP, through the hinged access
door. The BP transducer is located in the auxiliary control
box. Wiring should only be performed by qualified person-
nel. All parameters have been factory set. Do not change pa-
rameters unless necessary.
The VFD can be easily damaged by static electricity. Use
proper electrostatic discharge procedures when handling the
controls of the VFD.
All system operating intelligence resides in the PSIO mod-
ule. This module monitors conditions through the input and
output ports and the DSIO modules.
The machine operator communicates with the micro-
processor through the HSIO keypad and display module. Com-
munication between the PSIO and the other modules is
accomplished by a 3-wire sensor bus. These 3 wires run in
parallel from module to module.
On the sensor bus terminal strips, terminal 1 of the PSIO1
module is connected to Terminal 1 of all of the other mod-
ules. Terminals 2 and 3 are connected in the same manner.
If any of the wires are crossed, the system will not work.
Never connect main circuit output terminals T1, T2, and
T3 to AC main circuit power supply. Always ground the VFD
using the designated ground terminal. Refer to the VFD tech-
nical manual for more information.
The VFD can indicate faults and alarms. A blinking alarm
condition is a warning that a trouble condition will occur or
that there is a problem in the external circuitry. The VFD
will continue to operate during an alarm condition. Alarm
conditions are not entered into the fault register.
A steady fault indicator is displayed when the VFD fault
relay has tripped. The motor will coast to a stop, and a fault
signal is output is present.
The unit processor modules, the high-voltage relay mod-
ules, and the HSIO keypad module are all powered from two
21-vac power sources which connect to terminals 1 and 2 of
the power input strip on each module.
Refer to the VFD technical manual for more information
on alarms and faults.
DISPLAYING FAULT SEQUENCE — Whenever the fault
relay trips and shuts down the VFD, the display code of the
fault that caused the trip will be displayed until RESET is
53
Download from Www.Somanuals.com. All Manuals Search And Download.
16. Press
to check the remainder of the user con-
Processor Module(s) (PSIO)
figuration values.
INPUTS — Each input channel has 3 terminals; 2 are used.
17. After completing the configuration steps outlined above,
close all remaining circuit breakers and perform a unit
test.
18. Complete this procedure and restore the unit to normal
operation by returning the STANDBY/RUN mode to
STBY NO.
OUTPUTS— Output of the PSIO module is 24 vdc or
4 to 20 mA dc. There are 3 terminals; 2 are used.
REPLACING DEFECTIVE PSIO MODULES — The re-
placement part number is printed on a label on the front of
the PSIO module. The replacement module order is config-
ured as a generic replacement module, which will require
configuration in the field.
Before any service work is started, be sure that all elec-
trical disconnects are open and tagged.
High-Voltage Relay Modules (DSIO1 and DSIO2)
INPUTS — Inputs on terminal strip J3 are discrete inputs
(on/off). When 24 vac is applied across the 2 terminals in a
channel, it reads as an on signal. Zero v is read as an off
signal.
Installation
1. Verify the existing PSIO module is defective by using
the procedure described in the Control Modules section
on this page.
2. Refer to the Start-Up Checklist on pages CL-1 through
CL-4 that should have been completed at start-up. This
information is needed later in this procedure. If the check-
OUTPUTS — Terminal strips J4 and J5 are internal relays
whose coils are energized by a signal from the microproces-
sor. The relays switch the circuit to which they are con-
nected. No power is supplied to these connections by the
DSIO module.
list does not exist, make a new checklist by filling out
DSIO REPLACEMENT — Before any service work is started,
be sure that all electrical disconnects are opened and tagged.
the
and
configurations on paper. Tailor
Installation
the various options and configurations as needed for this
particular installation.
1. Verify the existing DSIO module is defective by using
the procedure described in the Control Modules section
on page 53.
2. Check that all power to the unit is off. Switch off all
circuit breakers. Carefully disconnect all wires from the
defective module by unplugging the connectors. It is not
necessary to remove any of the individual wires from
the connectors. Remove the green ground wire.
3. Remove the DSIO module mounting screws and re-
move the module from the control box. Save the screws.
4. With a small screwdriver, set the address switches S1
and S2 on the new DSIO module to match those on the
defective module.
5. Mount the new module in the control box using the screws
saved in Step 3.
6. Reinstall all of the wire connectors and the green ground
wire.
7. Carefully check all wire connections before restoring power
to the unit.
3. Check that all power to the unit is off. Switch off all
circuit breakers. Carefully disconnect all wires from the
defective module by unplugging the 6 connectors. It is
not necessary to remove any of the individual wires from
the connectors. Remove the green ground wire.
4. Remove the PSIO module mounting screws and remove
the module from the control box. Save the screws.
5. With a small screwdriver, set the address switches S1
and S2 on the new PSIO module to match those on the
defective module.
6. Mount the new module in the control box using the screws
saved in Step 4.
7. Reinstall all 6 wire connectors and the green ground wire.
8. Check all wire connections before restoring power to
the unit.
9. Verify that the unit ON/OFF switch is in the ON
position.
10. Restore power to the unit and close the control circuit
breaker (CCB). Verify that the red and green LEDs re-
spond as described in the Control Modules section on
this page. The HSIO keypad should begin its rotating
display.
8. Verify that the unit ON/OFF switch is in the ON
position.
9. Restore power to the unit and close the control circuit
breaker (CCB). Verify that the red and green LEDs
respond as described in the Control Modules section
on page 53. The LID (keypad) should begin its rotating
display.
10. After completing the configuration steps outlined above,
close all remaining circuit breakers and perform a unit
test.
11. Complete this procedure and restore the unit to normal
operation by returning the STANDBY/RUN mode to
STBY NO.
11. Using the HSIO keypad and display module, press
to verify that the software version matches the version
number shown on the PSIO label.
12. Press
to verify that the factory configuration
codes agree with the values listed in Table 24 on
page 37.
13. Set other applicable inputs required in
and
to match the options and accessories installed on the
equipment.
Refrigerant Feed Components — Each refrigerant
circuit (2 per unit) has all the necessary refrigerant controls.
14. Enable data reset function to store all data. The HSIO
ENTER
keypad display will blank out after pressing the
key
Thermostatic Expansion Valve (TXV) — On 48/
50MP units, each circuit has 2 TXVs on which superheat
may be adjusted if absolutely necessary.
The TXV is set to maintain 10 to 13 F superheat leaving
the evaporator coil. It controls the flow of refrigerant to the
evaporator coils.
while displaying data reset (DTRS). The rotating dis-
play returns when the data reset has been completed.
15. Press
and verify each item is now configured
as needed for this particular installation. Verify the fac-
tory default settings for both a specified unit and
generic control unit.
54
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Disconnect power wires at terminal box and disconnect
conduit.
6. Disconnect wires from crankcase heater.
7. Disconnect service valves from compressor.
Hot Gas Bypass — An optional hot gas bypass system
may be factory installed on circuit no. 1. This system will
introduce discharge vapor from the compressor discharge line
into the distributors and evaporator coil circuits on circuit
no. 1 when suction pressures drop to damaging levels. No
field adjustments of the hot gas bypass valve should be
required.
NOTE: On units with 2 compressors per circuit, discon-
nect both oil equalizer lines located on the motor barrel
and on the oil pump sump.
Condenser Fans — Each fan is supported by a formed
wire mount bolted to fan deck and covered with a wire guard.
The exposed end of the fan motor shaft is protected from
weather by grease. If fan motor must be removed for service
or replacement, be sure to regrease fan shaft and reinstall
8. Units 48/50MP62L:
a. Remove 4 large screws securing compressor mount-
ing pan to unit base rail.
b. Slide compressor (on mounting pan) to outside of unit
frame; support and/or lower to ground.
7
fan guard. For proper performance, fan should be ⁄8 in.
(22 mm) below top of venturi on the fan deck to top of
the fan hub. (See Fig. 64.) Tighten set screws to 15 ± 1 ft-lbs
(20 ± 1.3 N-m). Figure 64 shows proper position of
mounted fan.
c. Unbolt compressor from mounting pan and remove.
9. Units 48/50MP70M,82N,90P,10R:
a. Remove 4 large screws securing compressor to the com-
pressor rails.
b. Lift compressor off mounting bolts and remove.
Compressor Replacement — Perform the following:
1. Reverse procedure in Compressor Removal section to end
of Step 4.
2. Reinstall service valves and safety switches, and tighten
to torques as listed:
TORQUE
COMPRESSOR(S)
Tighten discharge valves to —
20-25 ft-lbs ( 27- 34 N-m)
80-90 ft-lbs (109-122 N-m)
06E-250
06E-265,275,299
Tighten suction valves to —
80- 90 ft-lbs (109-122 N-m)
90-120 ft-lbs (122-163 N-m)
06E-250
06E-265,275,299
Tighten the following fittings as specified —
120 in.-lbs (13.5 N-m)
120 in.-lbs (13.5 N-m)
High-Pressure Switch
Low-Pressure Switch
3. Leak-check and evacuate system, reclaim refrigerant.
4. Recharge system per pre-start-up and start-up sequences.
Recheck oil levels.
5. Energize crankcase heater for 24 hours prior to restart of
system.
NOTE: Fan rotation is clockwise when viewed from top of unit.
Fig. 64 — Condenser Fan Adjustment
TROUBLESHOOTING
The 48/50MP units provide extensive troubleshooting in-
formation to service personnel through the use of status codes
and alarm and alert codes from the control system, which
are displayed on the unit HSIO or through the use of Service
Tool or CCN Building Supervisor. For more information on
diagnostics, codes, and possible causes, refer to the Controls
and Troubleshooting manual.
Use the Quick Test function to check control inputs and
outputs (including economizer actuators). Refer to Controls
and Troubleshooting Guide.
IMPORTANT: Check for proper fan rotation (clock-
wise viewed from above). If necessary to reverse, switch
leads.
Compressor Removal — Access to the pump end of
the compressor is from the compressor side of the unit.
Access to the motor end of the compressor is from the inside
of the unit. All compressors can be removed from the com-
pressor side of the unit.
If there are indications of hunting (rapid oscillations) of
control functions (such as duct static pressure or supply air
temperature), or if the response rate is too slow, check the
gain values. Refer to the Control Loop Checkout section on
page 40 for more information.
IMPORTANT: All compressor mounting hardware and
support brackets removed during servicing must be re-
installed prior to start-up.
If the unit is equipped with an optional VFD and the sup-
ply or exhaust fan is not running when required, refer to the
troubleshooting section of the separate VFD technical manual
provided with the unit.
For troubleshooting information on mechanical systems,
refer to the troubleshooting and diagnostics table on the next
page.
1. Disconnect power to unit; lockout power to compressor.
2. Close suction and discharge service valves.
3. Relieve refrigerant pressure into a refrigerant recovery
system.
4. Remove:
a. Fan-cycling pressure switch (FCPS)
b. High-pressure switch
c. Low-pressure switch
55
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING AND DIAGNOSTICS
PROBLEM
COMPRESSOR DOES NOT RUN
SOLUTION
Contactor Open
1. Power off.
1. Restore power.
2. Fuses blown in field power circuit.
3. Alarm tripped.
2. After finding cause and correcting, replace with correct size fuse.
3. Check alarm history on HSIO.
4. No control power.
4. Check secondary fuse(s); replace with correct type and size. Re-
place transformer if primary windings receiving power.
5. Check for excessive compressor current draw. Reset breaker; re-
place if defective.
6. Reset lockout circuit at HSIO or circuit breaker.
7. Check for refrigerant undercharge, obstruction of indoor airflow, or
whether compressor suction shutoff valve is fully open. Make sure
liquid line solenoid valve(s) is open.
8. Check for refrigerant overcharge, obstruction of outdoor airflow, air in
system or whether compressor discharge valve is fully open. Be sure
outdoor fans are operating correctly.
9. Tighten all connections.
10. See 06E compressor service literature.
5. Compressor circuit breaker tripped.
6. Safety device lockout circuit active.
7. Low-pressure switch open.
8. High-pressure switch open.
9. Loose electrical connections.
10. Compressor stuck.
Contactor Closed
1. Compressor leads loose.
2. Motor windings open.
3. Single phasing.
1. Check connections.
2. See 06E compressor service literature.
3. Check for blown fuse. Check for loose connection at
compressor terminal.
COMPRESSOR STOPS ON HIGH-PRESSURE SWITCH
Outdoor Fan On
1. High-pressure switch faulty.
2. Airflow restricted.
3. Air recirculating.
1. Replace switch.
2. Remove obstruction.
3. Clear airflow area.
4. Noncondensables in system.
5. Refrigerant overcharge.
6. Line voltage incorrect.
7. Refrigerant system restrictions.
4. Purge and recharge as required.
5. Purge as required.
6. Consult power company.
7. Check or replace filter drier, expansion valve, etc. Check that com-
pressor discharge valve is fully open.
Outdoor Fan Off
1. Fan slips on shaft.
2. Motor not running.
3. Motor bearings stuck.
4. Motor overload open.
5. Motor burned out.
1. Tighten fan hub setscrews.
2. Check power and capacitor.
3. Replace bearings.
4. Check overload rating. Check for fan blade obstruction.
5. Replace motor.
COMPRESSOR CYCLES ON LOW-PRESSURE SWITCH
Indoor-Air Fan Running
1. Filter drier plugged.
2. Expansion valve power head defective.
3. Low refrigerant charge.
1. Replace filter drier.
2. Replace power head.
3. Add charge. Check low-pressure switch setting.
Airflow Restricted
1. Coil iced up.
2. Coil dirty.
3. Air filters dirty.
4. Dampers closed.
1. Check refrigerant charge.
2. Clean coil fins.
3. Clean or replace filters.
4. Check damper operation and position.
Indoor-Air Fan Stopped
1. Electrical connections loose.
2. Fan relay defective.
1. Tighten all connections.
2. Replace relay.
3. Motor overload open.
4. Motor defective.
3. Power supply.
4. Replace motor.
5. Replace or tighten belt.
5. Fan belt broken or slipping.
LEGEND
HSIO
DSIO
VFD
—
—
—
Human Sensory Input/Output Device
Processor Module
Variable Frequency Drive
56
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING AND DIAGNOSTICS (cont)
PROBLEM
SOLUTION
COMPRESSOR RUNNING BUT COOLING INSUFFICIENT
Suction Pressure Low
1. Refrigerant charge low.
2. Head pressure low.
1. Add refrigerant.
2. Check refrigerant charge.
3. Clean or replace filters.
4. Replace power head.
5. Check low-pressure setting.
6. Remove obstruction.
3. Air filters dirty.
4. Expansion valve power head defective.
5. Indoor coil partially iced.
6. Indoor airflow restricted.
Suction Pressure High
1. Unloaders not functioning.
2. Compressor valve defective.
3. Heat load excessive.
1. Check unloader adjustments. Check unloader setting.
2. See 06E compressor service literature.
3. Check for open doors or windows in vicinity of fan coil.
UNIT OPERATES TOO LONG OR CONTINUOUSLY
1. Low refrigerant charge.
1. Add refrigerant.
2. Control contacts fused.
2. Replace control.
3. Air in system.
4. Partially plugged expansion valve or filter drier.
3. Purge and evacuate system.
4. Clean or replace.
SYSTEM IS NOISY
1. Piping vibration.
2. Compressor noisy.
1. Support piping as required.
2. Check valve plates for valve noise. Replace compressor if bearings
are worn.
COMPRESSOR LOSES OIL
1. Leak in system.
1. Repair leak.
2. Check wiring and relays. Check heater and replace if
defective.
2. Crankcase heaters not energized during shutdown.
FROSTED SUCTION LINE
Expansion valve admitting excess refrigerant.
Adjust expansion valve.
HOT LIQUID LINE
1. Shortage of refrigerant due to leak.
2. Expansion valve opens too wide.
1. Repair leak and recharge.
2. Adjust expansion valve.
FROSTED LIQUID LINE
Restricted filter drier.
Remove restriction or replace.
COMPRESSOR WILL NOT UNLOAD
1. Defective unloader.
2. Defective capacity control solenoid valve.
3. Miswired capacity control liquid line solenoid.
1. Replace unloader.
2. Replace valve.
3. Rewire correctly.
COMPRESSOR WILL NOT LOAD
1. Miswired capacity control liquid line solenoid.
2. Defective capacity control solenoid valve.
3. Plugged strainer (high side).
1. Rewire correctly.
2. Replace valve.
3. Clean or replace strainer.
4. Clean or replace the necessary parts.
4. Stuck or damaged unloader piston or piston ring(s).
CONTACTOR OPEN
1. Power off.
1. Restore power.
2. Fuses blown in field power circuit.
3. No control power.
2. After finding cause and correcting, replace with correct fuses.
3. Check secondary fuses. Replace with correct type and size. Replace
transformer if primary windings are receiving power.
4. Check unit status at HSIO. Check alerts and alarms at HSIO. Cor-
rect as required and reset.
4. No demand by unit control.
5. Fan status switch not closed.
6. VFD overload function tripped.
5. Check continuity at fan status switch contacts. Check wiring from fan
status switch to PSIO no. 1, channel 12.
6. Refer to separate VFD technical manual for troubleshooting instruc-
tions.
7. Motor leads loose.
8. Motor windings open.
9. Single phasing.
7. Check connections at motor lead junction box.
8. Check motor windings.
9. Check for blown fuse. Check for loose connections at motor junction
box.
10. Belts broken or thrown.
11. Fan status switch contacts defective.
10. Check belts. Replace as complete set if necessary.
11. Check for input signal at PSIO no. 1, channel 12. Replace switch if
defective.
CONTACTOR CLOSED
1. No output signal from control at PSIO no. 1,
channel 16.
1. Check alerts and alarms at HSIO. Check status at HSIO.
Replace PSIO no. 1.
2. Check for input signal at VFD, terminals FI (+) and FC (-).
3. Check switch continuity. Replace switch if defective.
2. Communication failure at VFD.
3. Fan status switch contacts defective.
LEGEND
HSIO
DSIO
VFD
—
—
—
Human Sensory Input/Output Device
Processor Module
Variable Frequency Drive
57
Download from Www.Somanuals.com. All Manuals Search And Download.
Refer to Fig. 65 for IGC troubleshooting information.
LEGEND
IGC
PIC
—
—
Integrated Gas Unit Controller
Product Integrated Control
Fig. 65 — IGC Control (Heating) — 48MP Units Only
58
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
PACKAGED SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your knowledge of the equip-
ment discussed in this manual, including:
• Unit Familiarization
• Installation Overview
• Maintenance
• Operating Sequence
A large selection of product, theory, and skills programs are available, using popular video-based for-
mats and materials. All include video and/or slides, plus companion book.
Classroom Service Training which includes ‘‘hands-on’’ experience with the products in our labs can
mean increased confidence that really pays dividends in faster troubleshooting and fewer callbacks.
Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-962-9212
[
] Packaged Service Training
[
] Classroom Service Training
Copyright 1998 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 PC 111 Catalog No. 534-893 Printed in U.S.A. Form 48/50MP-1SI Pg 60 12-98 Replaces: 50MP-1SI
Tab 1a 1b
1
Download from Www.Somanuals.com. All Manuals Search And Download.
START-UP CHECKLIST
MODEL NO.:
DATE:
SERIAL NO.:
TECHNICIAN:
I. PRE-START-UP:
Ⅺ VERIFY THAT UNIT IS LEVEL
Ⅺ VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
Ⅺ LOOSEN ALL SHIPPING HOLDDOWN BOLTS AND REMOVE SHIPPING BRACKETS PER INSTRUCTIONS
Ⅺ VERIFY THAT COMPRESSOR SUSPENSION SPRINGS HAVE BEEN LOOSENED PER INSTRUCTIONS
Ⅺ VERIFY ASSEMBLY OF ECONOMIZER HOOD
Ⅺ VERIFY INSTALLATION OF EXHAUST HOOD
Ⅺ VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS
Ⅺ VERIFY THAT POWER SUPPLY MATCHES UNIT DATA PLATE
Ⅺ VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT
Ⅺ CHECK GAS PIPING FOR LEAKS (48MP ONLY)
Ⅺ CHECK THAT INDOOR-AIR FILTERS ARE CLEAN AND IN PLACE
Ⅺ CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SET SCREW
IS TIGHT
Ⅺ VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED
Ⅺ OPEN SUCTION, DISCHARGE, AND LIQUID LINE SERVICE VALVES
Ⅺ CHECK COMPRESSOR OIL LEVEL SIGHT GLASS AND VERIFY PROPER LEVEL
Ⅺ VERIFY THAT CRANKCASE HEATERS HAVE BEEN ENERGIZED FOR 24 HOURS
Ⅺ CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS:
(AB + AC + BC)/3 = AVERAGE VOLTAGE =
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =
AB
V
AC
V
BC
V
V
V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =
%
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
II. PRELIMINARY CHECKLIST ITEMS (DETERMINE BEFORE CONFIGURING CONTROLS):
CONTROL SETTINGS FOR NON-NETWORKED, FREESTANDING UNIT
Ⅺ UNIT TO BE OPERATED ON CONSTANT AIR VOLUME (CV) RATHER THAN VARIABLE-AIR VOLUME (VAV)
Ⅺ CONFIRM THAT SPACE TEMPERATURE SENSOR (T55) HAS BEEN WIRED CORRECTLY PER SPACE
TEMPERATURE SENSOR (T55) SECTION ON PAGE 17.
Ⅺ CONFIRM THAT TUBING FOR SPACE AND SUPPLY DUCT PRESSURES HAS BEEN INSTALLED
Ⅺ SET ENTHALPY CONTROL SET POINT ON ECONOMIZER
Ⅺ SET SUPPLY FAN AND ‘‘CHECK FILTER’’ STATUS SWITCHES FOR JOB REQUIREMENTS
UNIT OPTION CHECKLIST
ITEM
PRESENT?
A
B
C
D
E
Ⅺ
Ⅺ
Ⅺ
Ⅺ
Ⅺ
CONSTANT VOLUME POWER EXHAUST
VARIABLE VOLUME POWER EXHAUST
VARIABLE FREQUENCY DRIVE ON SUPPLY FAN (VAV ONLY)
HOT GAS BYPASS
VAV WITH OCCUPIED HEAT
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 PC 111 Catalog No. 534-893 Printed in U.S.A. Form 48/50MP-1SI CL-1 12-98 Replaces: 50MP-1SI
Tab 1a 1b
1
Download from Www.Somanuals.com. All Manuals Search And Download.
III. PRELIMINARY CHECKLIST ITEMS (cont)
CHANGES TO DEFAULT VALUES
Ⅺ RECORD ALL CHANGES MADE TO FACTORY DEFAULT VALUES
IV. START-UP
CHECK EVAPORATOR FAN SPEED AND RECORD.
CHECK CONDENSER FAN SPEED AND RECORD.
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
COMP A1
COMP A2
COMP B1
COMP B2
OIL PRESSURE
SUCTION PRESSURE
SUCTION LINE TEMP
DISCHARGE PRESSURE
DISCHARGE LINE TEMP
ENTERING CONDENSER AIR TEMP
LEAVING CONDENSER AIR TEMP
EVAP ENTERING AIR DB TEMP
EVAP ENTERING AIR WB TEMP
EVAP LEAVING AIR DB TEMP
EVAP LEAVING AIR WB TEMP
COMPRESSOR AMPS (L1)
COMPRESSOR AMPS (L2)
COMPRESSOR AMPS (L3)
ELECTRICAL
SUPPLY FAN AMPS
ELECTRIC HEAT AMPS L1
EXHAUST FAN AMPS
L2 L3
TEMPERATURES
OUTDOOR-AIR TEMPERATURE
RETURN-AIR TEMPERATURE
COOLING SUPPLY AIR
F
F
F
DB (Dry-Bulb)
DB
F
WB (Wet-Bulb)
PRESSURES
GAS INLET PRESSURE
IN. WG
GAS MANIFOLD PRESSURE STAGE NO. 1
REFRIGERANT SUCTION CIRCUIT NO. 1
REFRIGERANT DISCHARGE CIRCUIT NO. 1
IN. WG
PSIG
STAGE NO. 2
IN. WG
PSIG
CIRCUIT NO. 2
CIRCUIT NO. 2
PSIG
PSIG
Ⅺ VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGES 48 AND 49
GENERAL
Ⅺ ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS
CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES; ARE THE SIGHT GLASSES SHOWING
OIL LEVEL PER INSTRUCTIONS ON PAGE 29.
(Y/N)
Ⅺ PERFORM CONTROL CONFIGURATION PROCEDURE ON PAGES CL-3 AND CL-4.
CL-2
Download from Www.Somanuals.com. All Manuals Search And Download.
CONTROL CONFIGURATION
KEYBOARD
ENTRY
DESCRIPTION
VALUES IN [ ] INDICATE FACTORY DEFAULTS
DISPLAY
LOG ON
Enter password followed by
Logged on okay
ENTER
LOGGEDON
FACT CFG
TYPE X
Factory configuration
Unit type (0 = CV, 1 = VAV) [Default is 1]
x
ENTER
TYPE X
DTRS
Verify unit type and change if necessary. If CV unit, see CV
control configuration.
Data Reset
Enable Data Reset
ENTER
FACT CFG
LLAG X
Factory Configuration
Use
to access lead/lag option — disable with
HGBP (Item D, page CL-1)
ENTER
DISABLE
Disable lead/lag (0 = DIS, 1 = ENB) [1]
BLD PRES
Configure building pressure control (modulating power
exhaust)
BPS .05
BPS X
Use
for building pressure set point (range 0 to .5) [.05]
Set building pressure set point per job requirements
Access log on/off function
x
ENTER
LOGGEDON
LOG OFF
Use
to access log off
Logged off okay
LOGD OFF
ENTER
INPUTS
Run quick test to verify operation of unit functions
(see Controls and Troubleshooting Guide)
through
SETPOINT
OHSP X
Set system set points per job requirements
Set occupied heat set point (Range 55-80 F) [68] CV only
Set occupied cool set point (Range 55-80 F) [78] CV only
Set unoccupied heat set point (Range 40-80 F) [55]
Set unoccupied cool set point (Range 75-95 F) [90]
OCSP X
UHSP X
UCSP X
SPSP X
SASP X
Set supply duct pressure set point (Range 0-5.0 in. wg) [1.5]
Set supply air set point temperature (Range 45-70 F) [55]
TIME
Current time/date
dow.hh.mm
mm.dd.yy
Set day of week and time
Set month, day, and year
DAYLIGHT
HOLIDAY
PERIOD X
Set daylight savings time begin/end dates. Required if job
conditions require adjustment of clock for daylight savings time
(see Controls and Troubleshooting Guide)
Set holiday dates. Required if job conditions require a different
schedule on holidays than other days (see Controls and Trouble-
shooting Guide)
Set occupied/unoccupied schedules. Required if job condi-
tions require unit to enter unoccupied cycle at programmed
times of day or days of week (see Controls and Troubleshoot-
ing Guide)
through
NOTE: Data in brackets [ ] is default value.
CL-3
Download from Www.Somanuals.com. All Manuals Search And Download.
CONSTANT VOLUME CONTROL CONFIGURATION
KEYBOARD
ENTRY
DESCRIPTION
DISPLAY
FACT CONFIG
FANM
Fan Mode
FANMx
Select Fan Mode (Auto. = 0, Cont. = 1) [1]
ENTER
x
ECONOMIZER
SMG x.x
Configure Economizer
Submaster Gain
ENTER
SMG 8.0
Set SMG to 8.0 [−7.5[
NOTES:
Copyright 1998 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 PC 111 Catalog No. 534-893 Printed in U.S.A. Form 48/50MP-1SI CL-4 12-98 Replaces: 50MP-1SI
Tab 1a 1b
Download from Www.Somanuals.com. All Manuals Search And Download.
1
|