48MA/50ME016-040
Combination Multizone Heating/Cooling Units
Gas, Electric, or Glycol Heat
Installation, Start-Up
and Service Instructions
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
CONTENTS
• EVAPORATOR COILS (ZONE COOLING COILS)
AND GLYCOL HEATING COILS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 2
• CONDENSER AND OUTDOOR-AIR COOLING
COILS
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-34
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Roof Openings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Rigging Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Removing Shipping Shields . . . . . . . . . . . . . . . . . . 5
Field-Fabricated Ductwork . . . . . . . . . . . . . . . . . . . . 5
Condensate Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Gas Piping (48MA) . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Optional Glycol Connections (50ME) . . . . . . . . . 10
Field Power Supply Wiring . . . . . . . . . . . . . . . . . . 10
• UNIT COMMON FEED MINIMUM CIRCUIT AMPS
Field Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . 14
• ZONE THERMOSTATS
• CONDENSATE DRAINS
• INDOOR-AIR FILTERS
• OUTDOOR-AIR INLET SCREENS
• GAS HEATING SECTION
• COMBUSTION AIR FAN
Airflow Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
• INDOOR AIRFLOW SWITCH (AFS1)
• COMBUSTION AIRFLOW SWITCH (AFS2)
Service Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Time Guardா Control Circuit . . . . . . . . . . . . . . . . . 39
Capacity Control Pressure Switches (CCP)
(2-Compressor Units Only) . . . . . . . . . . . . . . . . 39
Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
• TO ADD OR REMOVE OIL
Compressor Capacity Control Unloader(s) . . . . 40
• CONTROL SET POINT
• PRESSURE DIFFERENTIAL
• ZONE MODULE CONNECTIONS
• ACCESSORY REMOTE CONTROL PANEL
Reheat Humidity Control . . . . . . . . . . . . . . . . . . . . 34
Optional Economizer . . . . . . . . . . . . . . . . . . . . . . . . 34
Optional Exhaust Damper . . . . . . . . . . . . . . . . . . . 34
Crankcase Heater(s) . . . . . . . . . . . . . . . . . . . . . . . . . 40
Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . 40
• NO CHARGE
• LOW CHARGE
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-39
Evaporator Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Compressor Rail Shipping Bolts . . . . . . . . . . . . . 34
Refrigerant Valves . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Zone Module Gas Valves (48MA) . . . . . . . . . . . . . 34
Gas Heat Lighting Procedure (48MA) . . . . . . . . . 35
• TO SHUT OFF GAS HEAT
Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . 40
• MOTORMASTER HEAD PRESSURE CONTROL
DEVICE
• FAN CYCLING PRESSURESTAT
Condenser Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
• ADJUSTMENT
• FAN MOTOR REMOVAL
• LUBRICATION
Evaporator Fans and Motor . . . . . . . . . . . . . . . . . . 41
• MOTOR REMOVAL
• FAN SHAFT BEARING REMOVAL
• FAN SPEED ADJUSTMENT
• PULLEY REMOVAL
• PULLEY ALIGNMENT
• BELT TENSION ADJUSTMENT
• LUBRICATION
Forced-Draft Blower (48MA) . . . . . . . . . . . . . . . . . 42
• LUBRICATION
• AIR SHUTTER ADJUSTMENT
Zone Module Transformers . . . . . . . . . . . . . . . . . . 42
Optional Economizer . . . . . . . . . . . . . . . . . . . . . . . . 42
• THERMOSTAT SETTINGS
Intermittant Pilots (48MA) . . . . . . . . . . . . . . . . . . . 35
• ADJUSTMENT
• PRESSURE ADJUSTMENT (NATURAL GAS)
Main Burner Adjustment (48MA) . . . . . . . . . . . . . 36
• ORIFICE ALIGNMENT
• PRIMARY AIR ADJUSTMENT
Outdoor-Air Thermostat Adjustment
(50ME With Electric Heat) . . . . . . . . . . . . . . . . . . 36
• UNITS WITH 2-ELEMENT HEATERS
• UNITS WITH 3-ELEMENT HEATERS
Optional Glycol Heating Coils . . . . . . . . . . . . . . . . 38
Zone Airflow Adjustment . . . . . . . . . . . . . . . . . . . . 38
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . 38
• COOLING
• HEATING (48MA)
• HEATING (50ME WITH ELECTRIC HEAT)
• HEATING (50ME WITH GLYCOL HEATING COILS)
• OUTDOOR-AIR DAMPER
• DAMPER POSITION
• OPERATION
Optional Exhaust Damper . . . . . . . . . . . . . . . . . . . 42
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . 42
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39-43
Cabinet Panels and Grilles . . . . . . . . . . . . . . . . . . 39
• SIDE PANELS
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . CL-1
• TOP PANELS
• HEATER ACCESS PANELS
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 PC 111 Catalog No. 564-840 Printed in U.S.A. Form 48MA/50ME-3SI Pg 1 4-96 Replaces: 48MA/50ME-1SI
Tab 1c 1d
1
Download from Www.Somanuals.com. All Manuals Search And Download.
CONDENSER SECTION AIRFLOW
Connection
CONN
—
NOTES:
1. Space required for service and airflow all
around and above unit is 36 inches.
2. For additional information see Fig. 4.
3. Center of gravity is within 6 in. radius of geo-
metric center of unit.
4. Maximum allowable pitch of unit is 1
10 ft in any direction.
⁄2
in. per
Certified dimension drawings available on request.
DIMENSIONS (ft-in.)
UNIT
48MA
A
B
C
D
E
F
G
H
J
K
L
016-030
034,040
7- 23⁄4
3-05⁄8
3-915⁄16*
17-115⁄16
21- 91⁄16
2-215⁄16
4-25⁄8
13-51⁄2
13-51⁄2
0- 91⁄16
0-111⁄16
2-10
3- 45⁄16
7-33⁄16
8-63⁄4
0-31⁄8
0-31⁄32
0-31⁄8
0-215⁄16
0-31⁄8
0-71⁄4
7-11
*Overall height; includes 13⁄4-in. for fan guards.
Fig. 1 — Base Unit Physical Data and Dimensions; 48MA Units
3
Download from Www.Somanuals.com. All Manuals Search And Download.
CONDENSER SECTION AIRFLOW
Connection
CONN
—
NOTES:
1. Space required for service and airflow all
around and above unit is 36 inches.
2. For additional information see Fig. 5.
3. Center of gravity is within 6 in. radius of geo-
metric center of unit.
4. Maximum allowable pitch of unit is 1
10 ft in any direction.
⁄2
in. per
Certified dimension drawings available on request.
DIMENSIONS (ft-in.)
UNIT
50ME
A
B
C
D
E
F
G
H
J
016-030
034,040
7- 23⁄4
3-09⁄16
3-915⁄16*
17-115⁄16
21-91⁄16
2-215⁄16
4-25⁄8
13-51⁄2
13-51⁄2
3-71⁄16
7-33⁄16
8-63⁄4
0-31⁄8
0-215⁄16
0-31⁄8
0-71⁄4
7-11
4-4
*Overall height; includes 13⁄4-in. for fan guards.
Fig. 2 — Base Unit Physical Data and Dimensions; 50ME Units
4
Download from Www.Somanuals.com. All Manuals Search And Download.
AIRFLOW
*Factory supplied (with accessory roof curb).
†Field supplied (when using accessory roof curb).
NOTE: Dimensions are in inches.
Fig. 3 — Roof Curb Detail
Rigging Unit — Inspect unit for shipping damage, and
file any damage claim immediately with transportation
company.
Lift unit with cables and spreader bars, using lifting brack-
ets provided (Fig. 1 and 2). Lift one unit at a time, keep unit
upright, and do not drop. Unit weights are given in Table 1.
Unit center of gravity is within 6 in. of unit’s geometric cen-
ter. Eyebolts may be removed after unit is in final position.
Field-Fabricated Ductwork — Supply- and return-
air openings are shown in Fig. 4 and 5. To simplify supply-
air connection, a zone duct plenum may be field fabricated
as shown in Fig. 7. It is recommended that this plenum be
installed prior to unit positioning.
It is recommended that the unit be supported on blocks
temporarily while the duct plenum is installed, rather than
installing the plenum while the unit is suspended. The duct
plenum may be installed once the unit is located in its final
position, but it is much easier to install the plenum prior to
unit final placement.
Zone supply-air duct openings on the base unit have tab
slot connections similar to those shown in Fig. 7 except that
the end partitions are hemmed. Hem is positioned so that the
1-in. flange at entering end of field-fabricated plenum will
force-fit between hem and adjacent unit frame.
Standard flexible duct connections between duct plenum
and duct system may be used. Follow applicable codes.
IMPORTANT: Do not drill or punch holes in unit frame
or panels; damage to internal components or wiring
may result.
Unit Positioning — When lowering unit onto roof curb,
do not exceed the out-of-symmetry tolerances given in
Fig. 4 and 5. Be sure unit is level or is pitched within speci-
fied tolerances. Units have drains on both sides and may be
pitched to either side.
Insulate any supply-air ducts passing through uncondi-
tioned spaces and cover with a vapor barrier. Separate ducts
with insulation if they run parallel for more than 5 ft. This
will prevent heat transfer between zones.
Removing Shipping Shields (Fig. 6)
1. Remove shield over flue outlet grille (48MA only).
2. Remove shields (sheet metal covers) located in the outdoor-
air inlet screen tracks behind the louvers. If the screens
are removed for this procedure, be sure to replace them
before replacing the louvered assembly.
Install a manual balancing damper in each zone duct to
provide the required zone airflow.
The return-air duct connection consists of 4 sheet metal
flanges as shown in Fig. 1, 2, 4, and 5.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1 — Physical Data
UNIT 48MA/50ME
016
024
028
030
034
040
Zone Modules (Quantity)
Nominal Cooling Capacity (tons)
8
15
8
20
10
25
10
28
12
30
12
37
OPERATING WEIGHT (lb)
Base Unit 48MA
Base Unit 50ME (with electric heat)
Roof Curb
3395
2995
506
3815
3415
506
4075
3675
506
4080
3680
506
5340
4900
630
5710
5270
630
REFRIGERANT CHARGE — R-22 (lb)
28
32
43
43
57
66.1
COMPRESSOR
Reciprocating Hermetic, 1725 Rpm
No. 1 Type
06DE537
06DE824
6...2
06DE537
6...2
06DE537
6...2
06DE537
6...2
06EE250
4...1
Cylinders...Unloaders
No. 2 Type
Cylinders (have no unloaders)
System Oil Charge (pints)
6...2
—
06DA824
6
06DA824
6
06DA537
6
06DA537
6
06EA250
4
—
11
18
18
18
18
31
Unloader Settings (psig)
Compressor No. 1 Only
71.0 ± 1.5
Loads
—
Unloader No. 2
Unloads
57.5 ± 2.5
—
Loads
Unloads
75.0 ± 1.5
62.5 ± 2.5
75.5 ± 1.5
58.0 ± 2.5
Unloader No. 1
100,83,67
50,33,17
100,80,60
40,20
100,80,60
40,20
100,83,67
50,33,17
100,75,
50,25
Capacity Steps (%)
100,67,33
CONDENSER FANS
Propeller, Direct Drive
Motor Hp...Rpm...Frame (NEMA)
No. 1
1...1075...56 (Single phase)
1...1140...56 (3 phase)
No. 2
No. 3
—
16,500
—
15,000
—
15,000
—
15,000
1...1140...56 (3 phase)
Nominal Cfm
24,000
23,000
EVAPORATOR FANS*
Number...Size (in.)
Cfm (Nominal)
Centrifugal, Belt Drive
2...15 × 15
6000
2...15 × 15
8000
2...15 × 15
10,000
10...1725
—
2...15 × 15
3...15 × 9
12,000
3...15 × 9
12,000
10,000
10...1725
—
Std
Alt
5...1725
—
71⁄2...1725
—
15...1725
20...1725
15...1725
20...1725
Motor Hp...Rpm
Fan Pulley
Outside Diameter (in.)
Bore (in.)
Std
Fan Belt Number...Size
Alt
10.6
13⁄16
1...3V630
—
10.6
13⁄16
1...3V630
—
8.0
13⁄16
2...3V560
—
8.0
13⁄16
2...3V560
—
8.0
8.0
111⁄16
111⁄16
2...3V630
3...3V670
2...3V630
3...3V670
Motor Pulley
Factory Installed
Std
Outside Diameter (in.)
Alt
5.3
—
6.0
—
5.0
—
5.0
—
5.0
6.0
5.0
6.0
Bore (in.)
11⁄8
13⁄8
13⁄8
1095
—
13⁄8
1095
—
15⁄8
15⁄8
Std
Resulting Fan Rpm
Alt
880
—
18 ± 2.5
1300
995
—
18 ± 2.5
1300
1095
1320
21 ± 2.5
1550
1095
1320
21 ± 2.5
1550
Shaft Center Line Distance (in.)
Maximum Fan Rpm
18 ± 2.5
1300
18 ± 2.5
1300
CONDENSER COOLING COIL
Face Area (sq ft)
Corrugated Fins/in. ...Rows
Thermostatic Expansion Valve, Hot Gas Bypass
6.8
13...2
6.8
6.8
6.8
10.2
10.2
13...3
13...2
13...2
13...2
13...2
EVAPORATOR COILS (zone)
Number...Face Area (sq ft/ea)
Corrugated Fins/in. ...Rows
Solenoid Valve and Capillary Tube for each
8...2.12
13...3
8...2.12
13...3
10...2.12
13...3
10...2.12
13...3
12...2.01
12...3
12...2.01
15...3
HEATING SECTION (48MA)
Rise Range
One Heat Assembly in Each Zone Module
25 F to 55 F at 0.75 in. wg ESP
Total
432
54
432
54
540
54
540
54
648
54
648
54
Input (1000 Btuh)
Each Module
Total
Each Module
324
324
405
405
40.5
2...38
486
486
Bonnet Cap.† (1000 Btuh)
Burner Spud Qty...Size
40.5
2...38
40.5
2...38
40.5
2...38
40.5
2...38
40.5
2...38
OPTIONAL HEATING SECTION (50ME Electric)
Electric Heaters
Qty...Elements (each)**
Nichrome, Open-Wire Resistance Element in Each Zone Module
8...2 or 3 10...2 or 3 10...2 or 3 12...2 or 3
8...2 or 3
12...2 or 3
OPTIONAL HEATING SECTION
(50ME Glycol Coil)
One Heating Coil in Each Zone Module
Maximum Allowable Inlet Temperature (F)
Maximum Allowable Flow, Each Coil (Gpm)
Solution Mixture
200
6
20% Glycol
30
Maximum Allowable Working Pressure (Psig)
Total Internal Volume (Gal)
2.61
2.61
3.15
3.15
3.76
3.76
PRESSURE SWITCHES
Cutout
Low-Pressure (Psig)
Cut-in
29 ± 5
39 ± 5
400 ± 5
300 ± 5
Cutout
High-Pressure (Psig)
Cut-in
Indoor Airflow Switch (AFS1)
Factory Setting (cfm)
Adjustment Range (cfm)
6000
4000-6000
9000
6000-9000
INDOOR AIR FILTERS
Standard Qty...Size (in.)
High Efficiency (optional)
Qty...Size (in.)
12...20 × 25 × 2
12...20 × 25 × 2 (36.5% Efficient)
OUTDOOR AIR FILTERS
Qty...Size (in.)
2...20 × 25 × 1
2...32 × 35 × 1
LEGEND
ESP
NEMA
—
—
External Static Pressure
National Electrical Manufacturers Association
*Standard unit shipped with standard motor, pulley, and belt(s); alternate unit shipped with alternate motor, pulley, and belt(s).
†The heating efficiency rating is a product thermal efficiency rating determined under continuous operating conditions independent of any installed system.
**See Field Power Supply Wiring section on page 10 and Table 4 for details.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
EVAPORATOR (ZONE MODULE) AIRFLOW
Connection
CONN
—
*Not used on 48MA016,024 (8 zone module units).
NOTES:
1. For additional information, see Table 1 and Fig. 1.
1
2. Maximum allowable unit pitch is
⁄2
in. per 10 ft in any direction.
3. Remove shipping brace before assembling curb section (location
shown).
DIMENSIONS (ft-in.)
UNIT
48MA
A
B
C
D
E
F
G
H
J
016-030
034,040
18-21⁄8
21-97⁄8
7- 3
7-113⁄4
11-9
14-13⁄4
5-61⁄4
6-77⁄16
7-27⁄8
8-43⁄16
1-109⁄16
2- 91⁄8
2-29⁄16
6-03⁄8
6-81⁄2
0- 71⁄2
0-105⁄16
3-1
Fig. 4 — Roof Curb Physical Data and Dimensions; 48MA Units
7
Download from Www.Somanuals.com. All Manuals Search And Download.
EVAPORATOR (ZONE MODULE) AIRFLOW
Connection
CONN
—
*Not used on 50ME016,024 (8 zone module units).
END DETAIL
(034,044 12-ZONE MODULES)
NOTES:
1. For additional information, see Table 1 and Fig. 2.
1
2. Maximum allowable unit pitch is
⁄
2
in. per 10 ft in any direction.
3. Remove shipping brace before assembling curb section (location
shown).
DIMENSIONS (ft-in.)
UNIT
50ME
A
B
C
D
E
F
G
H
J
016-030
034,040
18-21⁄8
21-97⁄8
7- 3
7-113⁄4
11-9
14-13⁄4
5-61⁄4
6-77⁄16
7-27⁄8
8-43⁄16
1-109⁄16
2- 91⁄8
2-29⁄16
6-03⁄8
6-81⁄2
0- 71⁄2
0-105⁄16
3-1
Fig. 5 — Roof Curb Physical Data and Dimensions; 50ME Units
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Do not interconnect drains. Make each trap a minimum of
4 in. deep. Insulate trap against freeze-up or use flexible
material.
Condensate Drains — Pipe nipples covered with foam
rubber insulation are shipped in unit return air filter section
(6 nipples in units 48MA, 4 nipples in units 50ME). Install
a nipple in each drain connection on both sides of unit. See
Fig. 1 and 2 for drain locations. Be sure foam rubber seals
space between nipple and base rail opening to prevent rain
leaks.
Connect a drain line to drain connection under outdoor air
inlet grilles on both sides of unit. These drains need not be
trapped.
Install a trapped drain line on remaining connections on
lowest side of unit depending on unit pitch. If unit is level,
a trapped drain may be installed at each connection if de-
sired. Cap or plug unused connections on high side of unit
to prevent airflow between unit interior and outdoors.
Gas Piping (48MA) — Unit is equipped for use with
type of gas shown on nameplate. Refer to latest edition of
ANSI Z223.1. Unit main gas connection and alternate gas
connection locations are shown in Fig. 1, 4, and 8. Do not
use gas supply pipe smaller than unit gas connection. Maxi-
mum allowable natural gas supply pressure is 10.0 in. wg;
minimum allowable natural gas supply pressure for full rate
input is 5.0 in. wg.
1
Pitch pipe ⁄4 in. per 15 ft. Pitch all horizontal pipe runs
upward to risers and from risers upward to meter. Install a
dirt and moisture pocket (drip leg) at each section of vertical
pipe run. Use only ground joint unions to ensure leakfree
joints. Use only pipe joint compounds that are resistant to
the action of liquefied petroleum gases.
OUTDOOR AIR INLET
(ONE ON EACH SIDE OF UNIT)
FLUE OUTLET
SHIPPING SHIELD
COVER
(BEHIND LOUVERS)
(48MA ONLY)
Fig. 6 — Shipping Shield Locations
(016-030 Units Shown)
DIMENSIONS (in.)
UNIT
48MA,50ME
016,024
028,030
034,040
A*
B*
75⁄8
75⁄8
75⁄8
73⁄4
75⁄16
53⁄4
*Typical; both ends.
NOTE: Dimension to suit job requirements. Twelve inches will bring
duct plenum to bottom of roof curb.
Fig. 7 — Field-Fabricated Zone Duct Plenum Detail
9
Download from Www.Somanuals.com. All Manuals Search And Download.
All units have a main power supply terminal board in the
power and condensing control box. The electric resistance
heater power supply terminal board(s) (if unit is so equipped)
on 50ME units is located in the heater control box at front
of unit. See Fig. 2, 5, and 9.
All terminal boards are suitable for use with copper or
aluminum wire.
Connect electrical conduit (a threaded pipe nipple) shipped
with unit to threaded fitting in roof curb and bottom of main
power and condensing section control box. Route main power
wires through conduit to terminal board in box as shown on
unit label wiring diagram and in Fig. 9.
When installing 48MA,50ME040 units with optional 20-hp
motor, the electrical conduit interconnecting the curb and con-
trol box power wire openings will not accommodate alumi-
num wire of the size that may be required. If aluminum wire
cannot be accommodated, an external transition box and short
lengths of no. 300 kcmil, 75 C copper wire from the tran-
sition box to the unit main power connection are
recommended.
Voltage to compressor terminals during compressor op-
eration must be within voltage range indicated on unit name-
plate. Phases must be balanced within 2%.
*Shutoff valve not used except where required by code.
Properly cap any gas connection not being used.
Fig. 8 — Suggested Gas Piping (48MA)
Unit has factory-installed gas shutoff valves. Install gas
shutoff valve external to unit if required by code (Fig. 8).
After piping is complete, pressurize gas line and check for
leaks with soap and water solution.
Do not use an open flame when checking for gas leaks.
Optional Glycol Connections (50ME) — Each zone
module has its own glycol heating coil and 115-v solenoid
valve. Heating coils are connected in parallel to common sup-
ply and return manifolds. Supply manifolds are equipped with
bleed cocks. Supply and return connections are shown in
Fig. 2 and 5. Unit does not have internal pressure relief for
part-load operation. Maximum allowable system working pres-
sure is 30 psig. Unit ratings are based on 20% glycol solu-
tions. Install solution supply apparatus in accordance with
application requirements, and mix glycol solution percent-
age in accordance with glycol manufacturer’s recommenda-
tions. Freeze-up protection is not factory installed.
Field Power Supply Wiring — When installed, unit
must be electrically grounded in accordance with local codes
or, in the absence of local codes, with the National Electrical
Code (NEC).
LEGEND
EQUIP
GND
TB
—
—
—
Equipment
Ground
Terminal Board
Unit has a circuit breaker for each compressor, each fan
motor, and for each 50ME electric resistance heater assem-
bly (if unit is so equipped). If required by local code, pro-
vide an additional disconnect switch in accordance with code
being followed.
*208/230 v units only.
Fig. 9 — Field Power Supply Details
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Use the following formula to determine the percent volt-
age imbalance.
IMPORTANT: If the supply voltage phase imbalance
is more than 2%, contact your local electric utility com-
pany immediately.
% Voltage Imbalance:
max voltage deviation from average voltage
= 100 ×
average voltage
Unit failure as a result of operation on improper line volt-
age or excessive phase imbalance constitutes abuse and may
cause damage to electrical components. See Tables 2-5 for
unit, electric heater, and 50ME electrical application elec-
trical data.
Each 50ME electric heat unit is fitted with a heating lock-
out circuit (if equipped with optional heat). If any zone mod-
ule is operating on mechanical cooling (compressor is op-
erating), the heating element in each zone module is locked
out and cannot be energized.
On 50ME units, cooling power supply wires and electric
heater power supply wires (if applicable) must be sized ac-
cording to the cooling MCA (Minimum Circuit Amps) val-
ues and heating MCA values shown on unit nameplate and
in Tables 3-5. These wires may be powered by a common
power supply (i.e., a pull-box junction), if desired. The com-
mon power supply wires from the main power source to the
junction must be sized according to the common MCA val-
ues shown in Table 5.
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
3
=
= 457
Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance:
UNIT COMMON FEED MINIMUM CIRCUIT AMPS —
The unit common feed MCA is calculated on the basis of
either: the sum of the cooling MCA plus 1⁄2 heating MCA on
7
% Voltage Imbalance = 100 x
457
2
= 1.53%
units with 2 heating elements per zone module (or ⁄3 heat-
ing MCA on units with 3 heating elements per zone module)
or the sum of the evaporator fan motor full load amps, per
NEC, plus the full heating MCA, whichever is larger. Field
wiring must conform to NEC limitations for Type T wire.
This amount of phase imbalance is satisfactory as it is below
the maximum allowable 2%.
Table 2 — Unit 48MA Electrical Data
VOLTAGE
RANGE
COMP
NO. 1
COMP
NO. 2
OFM
FLA
COMBUSTION
POWER
SUPPLY
IFM
UNIT
Voltage
FAN MOTOR
48MA (3 Ph, 60 Hz)
Min Max RLA LRA RLA LRA No. 1 No. 2 No. 3
FLA
Hp
FLA MCA MOCP
208/230
187
414
518
187
414
518
187
414
518
187
414
518
254 63.6 266
508 28.6 120
6.6
3.0
2.4
6.6
3.0
2.4
6.6
3.0
2.4
6.6
3.0
2.4
16.2 109.6
125
60
016
024
028
030
460
575
—
—
6.2
6.2
6.2
6.2
—
—
—
—
1.8
1.8
1.8
1.8
5
6.6
5.6
49.8
39.8
632 22.8
96
45
208/230
460
254 44.4 170 44.4 170
24.2 137.5
150
70
508 19.9
632 15.7
77 19.9
62 15.7
77
62
7.5 11.0
9.0
62.2
49.4
575
60
208/230
460
254 63.6 266 44.4 170
30.8 168.1
200
90
508 28.6 120 19.9
632 22.8 96 15.7
77
62
10
10
13.0
10.5
76.1
60.4
575
70
208/230
460
254 63.6 266 63.6 266
508 28.6 120 28.6 120
30.8 187.3
200
100
90
13.0
10.5
84.5
67.5
575
632 22.8
96 22.8
96
15
20
15
20
15
20
15
20
15
20
15
20
46.2 210.8
61.0 224.6
225
250
100
125
90
208/230
460
187
414
518
187
414
518
254 63.6 266 63.6 266
508 28.6 120 28.6 120
6.6
3.0
2.4
6.6
3.0
2.4
6.6
3.0
2.4
6.6
3.0
2.4
21.0
94.5
034
040
6.2
6.2
1.8
1.8
26.6 100.5
16.0
21.3
75.6
80.6
575
632 22.8
96 22.8
96
100
300
300
150
150
125
125
46.2 247.7
61.0 261.5
21.0 116.7
27.0 122.7
208/230
460
254 80.0 345 80.0 345
508 38.5 150 38.5 150
632 31.4 120 31.4 120
16.0
95
575
21.3 100
LEGEND
MOCP
OFM
RLA
—
—
—
Maximum Overcurrent Protection
Outdoor (Condenser) Fan Motor
Rated Load Amps
COMP
FLA
IFM
LRA
MCA
—
Compressor
Full Load Amps
—
—
—
—
NOTES:
Indoor (Evaporator) Fan Motor
Locked Rotor Amps
1. Combustion air fan is a 115-1-60 motor on all units.
2. Condenser fan motor no. 1 is a 208/230-1-60 speed control motor
on all units.
Minimum Circuit Amps
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 3 — Unit 50ME Electrical Data
VOLTAGE
RANGE
COMP
NO. 1
COMP
NO. 2
OFM
FLA
POWER
SUPPLY
IFM
FLA
UNIT
VOLTAGE
50ME
(3 Ph, 60 Hz)
Min
Max
254
508
632
254
508
632
254
508
632
254
508
632
RLA
LRA
266
120
96
RLA
LRA
No. 1
No. 2
6.6
3.0
2.4
6.6
3.0
2.4
6.6
3.0
2.4
6.6
3.0
2.4
No. 3
Hp
MCA
MOCP
125
60
208/230
460
187
414
518
187
414
518
187
414
518
187
414
518
63.6
28.6
22.8
44.4
19.9
15.7
63.6
28.6
22.8
63.6
28.6
22.8
16.2
6.6
109.6
49.5
016
024
028
030
—
—
6.2
—
5
575
5.6
39.6
45
208/230
460
170
77
44.4
19.9
15.7
44.4
19.9
15.7
63.6
28.6
22.8
170
77
24.2
11.0
9.0
138.0
61.9
150
70
6.2
6.2
6.2
—
—
—
7.5
10
10
575
62
62
49.2
60
208/230
460
266
120
96
170
77
30.8
13.0
10.5
30.8
13.0
10.5
46.0
61.0
19.8
26.6
16.0
21.3
46.2
61.0
19.8
26.6
16.0
21.3
168.9
75.8
200
90
575
62
60.2
70
208/230
460
266
120
96
266
120
96
188.0
84.5
200
100
90
575
67.3
15
20
15
20
15
20
15
20
15
20
15
20
210.8
224.6
94.5
225
250
100
125
90
208/230
460
187
414
518
187
414
518
254
508
632
254
508
632
63.6
28.6
22.8
80.0
39.3
31.4
266
120
96
63.6
28.6
22.8
80.0
39.3
31.4
266
120
96
6.6
3.0
2.4
6.6
3.0
2.4
6.6
3.0
2.4
6.6
3.0
2.4
034
040
6.2
6.2
100.5
75.6
575
80.6
100
300
300
150
150
125
125
247.7
261.5
118.5
124.5
95
208/230
460
345
150
120
345
150
120
575
100
LEGEND
NOTE: Condenser fan motor no. 1 is a 208/230-1-60 speed control
motor on all units.
COMP
FLA
—
—
—
—
—
—
—
—
Compressor
Full Load Amps
IFM
Indoor (Evaporator) Fan Motor
Locked Rotor Amps
LRA
MCA
MOCP
OFM
RLA
Minimum Circuit Amps
Maximum Overcurrent Protection
Outdoor (Condenser) Fan Motor
Rated Load Amps
Table 4 — Electric Resistance Heater Data
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
ELECTRIC
HEAT kW
(Unit Total)
UNIT
50ME
HEATING ELEMENTS
PER ZONE MODULE
FLA PER
HEATING ELEMENT
MCA
(Each Circuit)
MOCP
(Each Circuit)
43/ 53
57/ 70
87/106
2
2
3
13.0/14.4
17.3/19.2
17.3/19.2
150/166
200/221
150/166
175/175
225/225
175/175
208/230
016,024
53
70
2
2
3
7.2
9.6
9.6
83
111
166
90
125
175
460
575
106
106
3
7.7
133
150
54/ 66
72/ 88
108/132
2
2
3
13.0/14.4
17.3/19.2
17.3/19.2
188/207
250/276
188/207
200/225
275/300
200/225
208/230
028,030
034,040
66
88
2
2
3
7.2
9.6
9.6
103
138
207
110
150
225
460
575
132
132
3
7.7
166
175
65/ 79
87/106
129/158
2
2
3
13.0/14.4
17.3/19.2
17.3/19.2
225/249
150/165
225/249
250/250
175/175
250/250
208/230
79
106
158
2
2
3
7.2
9.6
9.6
124
166
249
125
175
250
460
575
158
3
7.7
199
200
LEGEND
NOTES:
1. Heaters are rated at 230 v, 460 v, and 575 v.
2. Terminal boards provided for heater power wire connections are
suitable for use with copper or aluminum wire.
FLA
—
—
—
Full Load Amps
MCA
Minimum Circuit Amps
MOCP
Maximum Overcurrent Protection
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 5 — Unit 50ME Electrical Application Data
MCA
UNIT
50ME
kW
(Unit
Total)
Heating
Circuit
NOMINAL
VOLTAGE
Unit
Common
Feed
Cooling
IFM
Hp
Size
016
1
2
43/ 53
57/ 70
87/106
150.0/165.6
200.0/220.9
150.0/165.8
—
—
184.8/192.6
216.7/237.6
316.7/348.3
208/230
109.8/109.8
150.0/165.8
5
53
70
106
82.9
110.5
165.8
90.9
117.1
172.4
460
575
49.5
39.6
—
—
106
132.5
138.1
43/ 53
57/ 70
87/106
150.0/160.6
200.0/220.9
150.0/165.8
—
—
213.0/220.8
238.0/248.5
342.2/359.0
208/230
138.0/138.0
150.0/165.8
024
028
030
7.5
10
10
15
20
15
20
53
70
82.9
110.5
165.8
103.4
121.5
176.8
460
575
61.9
49.2
—
106
106
132.5
—
141.5
54/ 66
72/ 88
108/132
188.0/207.1
250.0/276.1
188.0/207.1
—
—
262.9/272.5
293.9/307.0
419.6/445.0
208/230
168.9
188.0/207.1
66
88
132
102.8
138.0
207.1
127.2
151.0
220.1
460
575
75.8
60.2
—
—
132
165.6
176.1
54/ 66
72/ 88
108/132
188.0/207.1
250.0/276.1
188.0/207.1
—
—
282.0/291.6
313.0/326.0
438.7/464.0
208/230
188.0
188.0/207.1
66
88
132
102.8
138.0
207.1
135.9
153.5
222.6
460
575
84.5
67.3
—
—
132
165.6
177.7
65/ 79
87/106
129/158
225.0/248.5
150.0/165.6
225.0/248.5
—
323.3/335.1
360.8/376.4
510.9/543.2
208/230
210.8
150.0/165.1
225.0/248.5
79
106
158
124.3
165.1
248.5
156.7
185.4
268.3
460
575
94.5
75.6
—
—
158
198.8
214.8
034
65/ 79
87/106
129/158
225.0/248.5
150.0/165.1
225.0/248.5
—
337.1/348.9
374.6/391.2
524.6/558.0
208/230
224.6
150.0/165.1
225.0/248.5
79
106
158
124.3
165.6
248.5
162.7
192.2
275.1
460
575
100.5
80.6
—
—
158
198.8
220.1
65/ 79
87/106
129/158
225.0/248.5
150.0/165.1
225.0/248.5
—
360.2/372.0
397.7/412.8
547.7/579.0
208/230
247.7
150.0/165.1
225.0/248.5
79
106
158
124.3
165.6
248.5
178.9
199.5
282.4
460
575
116.7
95.0
—
—
158
198.8
227.5
040
65/ 79
87/106
129/158
225.0/248.5
150.0/165.1
225.0/248.5
—
374.0/385.8
411.5/426.6
561.5/592.8
208/230
261.5
150.0/165.1
225.0/248.5
79
106
158
124.3
165.6
248.5
148.9
205.5
288.4
460
575
122.7
100.0
—
—
158
198.8
232.5
LEGEND
IFM
MCA
—
—
Indoor (Evaporator) Fan Motor
Minimum Circuit Amps
13
Download from Www.Somanuals.com. All Manuals Search And Download.
quick-connect type multiplexing terminals. This prevents over-
loading the nest control transformers. Factory-supplied jump-
ers with quick-connect terminals are shipped in the zone con-
trol and thermostat panel compartment.
Under no circumstances shall the transformer power from
one Class II circuit be interconnected with any other circuit.
Field Control Wiring
ZONE THERMOSTATS — Install a Carrier approved ac-
cessory zone thermostat assembly in each zone according to
installation instructions included in the accessory. Locate each
thermostat assembly in the space where it will sense average
zone temperature.
Thermostat heat anticipator settings are indicated for each
permitted zone module connection arrangement illustrated
in Fig. 11-28.
To Join Modules of the Same Nest Into the Same Zone (i.e.,
modules no. 1 and 2) — Install field-supplied jumpers on
thermostat connections (screw terminals) Y to Y and W2 to
W2 as shown in Fig. 11. Connect thermostat wires to ter-
minal connections of first module in zone (for consistency).
Two-stage cooling may be obtained in this example as shown
in Fig. 12 (using a 2-stage thermostat).
Route thermostat cable or equivalent single leads of no.
18 AWG (American Wire Gage) colored wire from thermo-
stat subbase terminals through opening on base unit
(Fig. 1, 2, 4, and 5) to low-voltage thermostat connections
on zone control board (Fig. 10). Use no. 16 AWG wire for
lengths exceeding 50 ft.
ZONE MODULE CONNECTIONS — Any module may be
controlled independently or jointly with another module or
modules. Modules are combined into nests that form indi-
vidual Class II circuits (40 va) as follows:
To Join Modules Not of the Same Nest Into the Same Zone
(i.e., modules no. 2 and 3) — Install the factory-supplied jump-
ers on quick-connect terminals 6 to 1, 7 to 2, and 8 to 3 as
shown in Fig. 13. Note that module no. 1 is independently
controlled by its own thermostat (in Fig. 13).
Modules no. 1 and 2, 3 and 4, 5 and 6, 7 and 8, 9 and 10
(028-040 units), 11 and 12 (034,040 units).
The control signal can be transferred from one nest
to another nest by using factory-supplied jumpers on
LEGEND
AFS
CR
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Airflow Switch
Control Relay
ECR
ECT
GV
Economizer Relay
Economizer Outdoor-Air Thermostat
Gas Valve (not used on 50ME units)
Heater Contactor
Heater Relay
HC
HR
IFC
Indoor (Evaporator) Fan Contactor
Liquid Line Solenoid
Master Cooling
LLS
MC
MCR
MH
Master Cooling Relay
Master Heating
MHR
MU
Master Heating Relay
Master Unit
MUR
NC
Master Unit Relay
Normally Closed
NO
Normally Open
NS
Night Setback
SW
Switch
TRAN
Transformer
Quick-Connect Type Terminals (for multiplexing)
Screw-Type Terminals
NOTE: Twelve-zone unit shown. Eight-zone units have modules
1-8 only. Ten-zone units have modules 1-10 only.
Fig. 10 — Zone Control Board Component Location
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 10 — Zone Control Board Component Location (cont)
15
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — First stage of modules 1 and 2
HEATING
TH
TRAN
Stage 1 — First stage of modules 1 and 2
2. Set heat anticipator (HA1) at .26.
Screw Terminal
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
Field Wiring
Fig. 11 — 48MA; One-Stage Heat, One-Stage Cool — 2 Nested Modules, Joint Zone Control
16
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — First stage of modules 1 and 2
HEATING
TH
TRAN
Stage 1 — First stage of modules 1 and 2
2. Set heat anticipator (HA1) at .26.
Screw Terminal
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
Field Wiring
Fig. 12 — 48MA; One-Stage Heat, Two-Stage Cool — 2 Nested Modules, Joint Zone Control
17
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — First stage of modules 1, 2, and 3
HEATING
TH
TRAN
Stage 1 — First stage of modules 1, 2, and 3
2. Set heat anticipators (HA1) at .13.
Screw Terminal
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
Field Wiring
Fig. 13 — 48MA; One-Stage Heat, One-Stage Cool — One Independent Module, 2 Joint Modules Zone Control
18
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — First stage of modules 1, 2, and 3
Stage 2 — Second stage of modules 2 and 3
HEATING
TH
TRAN
Stage 1 — First stage of modules 1, 2, and 3
Screw Terminal
2. Set heat anticipators (HA1) at .13.
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
Field Wiring
Fig. 14 — 48MA; One-Stage Heat, One-Stage Cool; One-Stage Heat, Two-Stage Cool Combination
19
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — First stage of modules 1, 2, 3, and 4
HEATING
TH
TRAN
Stage 1 — First stage of modules 1, 2, 3, and 4
2. Set heat anticipator (HA1) at .26.
Screw Terminal
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
Field Wiring
Fig. 15 — 48MA; One-Stage Heat, One-Stage Cool — 4 Module Joint Zone Control
20
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — First stage of modules 1, 2, 3, and 4
HEATING
TH
TRAN
Stage 1 — First stage of modules 1, 2, 3, and 4
2. Set heat anticipators (HA1) at .13.
Screw Terminal
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
Field Wiring
Fig. 16 — 48MA; One-Stage Heat, One-Stage Cool — One Independent Module, 3 Joint Modules Zone Control
21
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — Modules 1 and 3
Stage 2 — Modules 2 and 4
HEATING
TH
TRAN
Stage 1 — First stage of modules 1, 2, 3, and 4
Screw Terminal
2. Set heat anticipator (HA1) at .26.
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
Field Wiring
Fig. 17 — 48MA; One-Stage Heat, Two-Stage Cool — 4 Module Joint Zone Control
22
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — Module 3
Stage 2 — Module 2 and 4
If thermostat wires are interchanged, the reverse may be
obtained.
TH
TRAN
HEATING
Screw Terminal
Stage 1 — First stage of modules 2, 3, and 4
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
2. Set heat anticipator (HA1) at .13.
Field Wiring
Fig. 18 — 48MA; One-Stage Heat, Two-Stage Cool — 3 Module Joint Zone Control
23
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — First stage of modules 1, 2, 3, and 4
HEATING
TH
TRAN
Stage 1 — First stage of modules 1, 2, 3, and 4
2. Set heat anticipators (HA1) as follows:
Screw Terminal
MODULE(S)
SETTING
.26
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
1, 3
2
.13
4
.13
Field Wiring
Fig. 19 — 48MA; One-Stage Heat, One-Stage Cool — 2 Independent Modules, 2 Joint Modules Zone Control
24
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — First stage of modules 1 and 2
HEATING
TH
TRAN
Stage 1 — First stage of modules 1 and 2
Stage 2 — Second stage of modules 1 and 2
Screw Terminal
2. Set heat anticipator 1 (HA1) at .26, and set heat anticipator 2 (HA2)
at 1.14.
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
Field Wiring
Fig. 20 — 50ME; Two-Stage Heat, One-Stage Cool — 2 Modules, Joint Zone Control
25
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — First stage of modules 1 and 2
Stage 2 — Second stage of modules 1 and 2
HEATING
TH
TRAN
Stage 1 — First stage of modules 1 and 2
Stage 2 — Second stage of modules 1 and 2
Screw Terminal
2. Set heat anticipator 1 (HA1) at .26, and set heat anticipator 2 (HA2)
at 1.14.
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
Field Wiring
Fig. 21 — 50ME; Two-Stage Heat, Two-Stage Cool — 2 Modules, Joint Zone Control
26
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — First stage of modules 1, 2, and 3
HEATING
TH
TRAN
Stage 1 — First stage of modules 1, 2, and 3
Stage 2 — Second stage of modules 1, 2, and 3
Screw Terminal
2. Set heat anticipator 1 (HA1) at .13, and set heat anticipator 2 (HA2)
at .57 (both thermostats).
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
Field Wiring
Fig. 22 — 50ME; Two-Stage Heat, One-Stage Cool — One Independent Module, 2 Joint Modules Zone Control
27
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — First stage of modules 1, 2, and 3
Stage 2 — Second stage of modules 2 and 3
HEATING
TH
TRAN
Stage 1 — First stage of modules 1, 2, and 3
Stage 2 — Second stage of modules 1, 2, and 3
Screw Terminal
2. Set heat anticipator 1 (HA1) at .13, and set heat anticipator 2 (HA2)
at .57 (both thermostats).
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
Field Wiring
Fig. 23 — 50ME; Two-Stage Heat, One-Stage Cool; Two-Stage Heat, Two-Stage Cool Combination
28
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — First stage of modules 1, 2, 3, and 4
HEATING
TH
TRAN
Stage 1 — First stage of modules 1, 2, 3, and 4
Stage 2 — Second stage of modules 1, 2, 3, and 4
Screw Terminal
2. Set heat anticipator 1 (HA1) at .26, and set heat anticipator 2 (HA2)
at 1.14.
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
Field Wiring
Fig. 24 — 50ME; Two-Stage Heat, One-Stage Cool — 4 Module Joint Control
29
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — First stage of modules 1, 2, 3, and 4
HEATING
TH
TRAN
Stage 1 — First stage of modules 1, 2, 3, and 4
Stage 2 — Second stage of modules 1, 2, 3, and 4
Screw Terminal
2. Set heat anticipator 1 (HA1) at .13, and set heat anticipator 2 (HA2)
at .57 (both thermostats).
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
Field Wiring
Fig. 25 — 50ME; Two-Stage Heat, One-Stage Cool — One Independent Module, 3 Joint Modules Zone Control
30
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — Modules 1 and 3
Stage 2 — Modules 2 and 4
HEATING
TH
TRAN
Stage 1 — First stage of modules 1, 2, 3, and 4
Stage 2 — Second stage of modules 1, 2, 3, and 4
Screw Terminal
2. Set heat anticipator 1 (HA1) at .26, and set heat anticipator 2 (HA2)
at 1.14.
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
Field Wiring
Fig. 26 — 50ME; Two-Stage Heat, Two-Stage Cool — 4 Module Joint Zone Control
31
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — Module 3
Stage 2 — Module 2 and 4
If thermostat wires are interchanged, the reverse may be
obtained.
TH
TRAN
HEATING
Screw Terminal
Stage 1 — First stage of modules 2, 3, and 4
Stage 2 — Second stage of modules 2, 3, and 4
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
2. Set heat anticipator 1 (HA1) at .13, and set heat anticipator 2 (HA2)
at .57.
Field Wiring
Fig. 27 — 50ME; Two-Stage Heat, Two-Stage Cool — 3 Module Joint Zone Control
32
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
*One for each module.
C
—
—
—
—
—
—
—
—
Contactor
NOTES:
CR
GV
HA
HR
TC
Control Relay
Gas Valve
1. COOLING
Heat Anticipator
Heating Relay
Thermostat, Cooling
Thermostat, Heating
Transformer
Stage 1 — First stage of modules 1, 2, 3, and 4
HEATING
TH
TRAN
Stage 1 — First stage of modules 1, 2, 3, and 4
Stage 2 — Second stage of modules 1, 2, 3, and 4
Screw Terminal
2. Set heat anticipators as follows:
Quick-Connect Terminal
Factory Control Wires
Printed Circuit
SETTING
MODULE(S)
HA1
.26
HA2
1, 3
2, 4
1.14
.57
Field Wiring
.13
Fig. 28 — 50ME; Two-Stage Heat, One-Stage Cool — 2 Independent Modules, 2 Joint Modules Zone Control
33
Download from Www.Somanuals.com. All Manuals Search And Download.
ACCESSORY REMOTE CONTROL PANEL — This central-
station control can be set to override zone thermostat mode
settings to lock out heating or cooling for the entire unit. The
DAY/NIGHT switch and damper position knob provide in-
space, central control of damper position. Panel also houses
the filter light to indicate reduced airflow and need for clean
filters. See Fig. 29. Install remote control panel in accor-
dance with instructions shipped with this accessory.
START-UP
After unit is installed, perform the following checks and
procedures, and complete Start-Up Checklist on page CL-1.
Evaporator Fan — Fan belt and pulley are shipped at-
tached to fan assembly. The factory-installed pulley pro-
vides fan speeds as shown in Table 1. Adjust fan belt(s) as
described in Evaporator Fans and Motor section on page 41.
Also see Zone Airflow Adjustment section on page 38.
Reheat Humidity Control — Control is achieved in
any module by wiring a humidistat in parallel with the cool-
ing thermostat. If zone thermostat drops below setting of heat-
ing thermostat because the humidistat is closed (cooling coil
is energized), the heating mode will be energized to reheat
the air in order to maintain zone space temperature. A typi-
cal humidistat hookup is shown in Fig. 30.
Compressor Rail Shipping Bolts — Loosen ship-
ping bolts beneath compressor rails so that rails float freely.
Do not loosen or remove bolts that attach compressors to
rails.
Refrigerant Valves — Open compressor discharge serv-
ice valve. Check that the suction service, hot gas shutoff,
and the liquid line shutoff valves are also open. See Fig. 31.
Optional Economizer — Adjust optional economizer
as described in Optional Economizer section on page 42.
Zone Module Gas Valves (48MA) — Each zone mod-
ule has its own combination gas valve and pressure regula-
tor to which gas is supplied by one of the 2 main manual gas
valves (Fig. 32).
Optional Exhaust Damper — Adjust optional ex-
haust damper as described in Optional Exhaust Damper sec-
tion on page 42.
LEGEND
APS
MCR
MHR
MUR
NC
—
—
—
—
—
—
Air Pressure Switch
Master Cooling Relay
Master Heating Relay
Master Unit Relay
Normally Closed
Terminal (Circuit Board,
Field or Accessory Conn.)
Accessory or Field Wiring
Factory Wiring
OR
NO
Normally Open
Circuit Board Run
Fig. 29 — Remote Control Panel Accessory Connections
34
Download from Www.Somanuals.com. All Manuals Search And Download.
The heating thermostat energizes a 115-v solenoid by means
of a gas valve relay and the pilot lights. The main burner
comes on after the pilot is proven.
The safety switches (airflow switches 1 and 2, pilot flame
sensor, door switch, and limit switches) are in series with
the gas valve.
Gas Heat Lighting Procedure (48MA)
1. Purge gas supply line of air. Make sure unit main manual
and zone module gas valves have been off for 5 minutes
before proceeding.
2. Set each zone thermostat to the lowest setting.
3. Turn zone module and main manual gas valves to ON
position, and secure door of burner compartment.
4. Turn on unit main power supply. Set control circuit serv-
ice switch in condensing control box at ON position. Evapo-
rator fan will be energized.
5. Set zone thermostat to call for heat. Pilot will light. The
main burner will come on after the pilot is proven.
NOTE: A time-delay relay will shut unit down in 180 sec-
onds if main manual gas valve is not open.
LEGEND
TO SHUT OFF GAS HEAT — Set control circuit service
switch at OFF position. Shut off unit power supply only if
necessary. Remove heating controls compartment access door.
Shut off main manual gas valves and pilot manual gas valves.
HA
HU
TC
TH
—
—
—
—
Heat Anticipator
Humidistat
Screw Terminal
Printed Circuit
Factory Control Wires
Field Wiring
Thermostat, Cooling
Thermostat, Heating
Intermittent Pilots (48MA) — Pilot flame should be
approximately 1 to 11⁄2 in. high.
Fig. 30 — Humidistat Connections
ADJUSTMENT
1. Turn system switch to OFF position.
2. If intending to adjust every zone, disconnect main gas
valve wires from terminal W on pilot switches in each
zone.
LEGEND
CCP
DLT
—
—
—
—
—
—
—
—
Capacity Control Pressure Switch
Discharge Line Thermostat
Fan Cycling Pressure Switch
Fusible Plug
LPS
OFM
TXV
—
—
—
Low-Pressure Switch
Outdoor (Condenser) Fan Motor
Thermostatic Expansion Valve
FCPS
FP
Hand Valve
Auto. Valve
Capilliary
HGBP
HPS
IFM
Hot Gas Bypass
High-Pressure Switch
Indoor (Evaporator) Fan Motor
Liquid Line Solenoid
LLS
Fig. 31 — Refrigerant Piping Schematic (10-Zone Unit Shown — 8- and 12-Zone Units Similar)
35
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
GV
—
—
—
—
Gas Valve (Zone Module)
Main Burner
Main Manual Gas Valve
Pilot Burner
NOTE: Unit is equipped with a forced-draft blower and the following safety de-
vices: forced-draft airflow switch, flame roll-out protection switch, combustion
chamber access door switch, heating limit switches, and spark-ignited auto-
matic pilots. All of these switches are located in the heating section and must
be in safe condition before the main burners can ignite.
MB
MGV
PB
Fig. 32 — Gas Piping Schematic (10-Zone 48MA Unit Shown — 8- and 12-Zone Units Similar)
3. Turn system switch to ON position. Set each zone ther-
mostat at setting to call for heat. Pilot will ignite.
10. Remove burner access panel. Disconnect gage line con-
nection on zone manifold. Replace plug in manifold pres-
sure tap.
NOTE: A time-delay relay will shut unit down in 180 sec-
onds if main manual gas valve is not open.
11. Repeat steps 3-10 for each heating module.
12. Replace all unit panels. Turn control circuit service switch
to ON position, and set zone thermostat as desired.
4. Remove burner access panel.
5. Remove screw-cap cover on zone gas valve to expose pi-
lot adjusting screw. With a small screwdriver, turn ad-
justing screw until flame is correct height. Replace screw-
cap cover on gas valve.
6. Turn system switch to OFF position.
7. Reconnect main gas valve wires to W1 on pilot switches.
8. Set system switch at ON position, and set zone thermo-
stats as desired.
9. Replace burner access panel.
Main Burner Adjustment (48MA) — Flame should
appear clear blue (almost transparent) in color with a well-
defined inner cone. If there is insufficient primary air, flame
will be yellow tipped. If there is too much primary air, flame
will be well defined but have a tendency to lift or dance off
ports. Allow unit to operate for at least 15 minutes before
making final primary air adjustment.
ORIFICE ALIGNMENT — The most likely cause of burner
flame flashback is misalignment of the burner orifice. Be sure
that orifice points straight down the burner.
PRESSURE ADJUSTMENT (NATURAL GAS)
1. Turn control circuit service switch to OFF position, and
set thermostat at lowest setting.
2. Remove the 2 heating control access panels and the burner
access panel.
PRIMARY AIR ADJUSTMENT — Observe flame charac-
teristics through view ports in main burner access panel. Turn
off main manual gas valves in burner control compartment.
Then remove main burner access panel.
If Flame Is Yellow (Insufficient Primary Air) — Turn spoiler
screw counterclockwise about 4 turns for each1⁄4 in. of change
in spoiler length. See Fig. 33 for spoiler screw location.
3. Remove plug from zone manifold pressure tap. Connect
suitable gage. Route gage line through pilot switch grom-
met so that burner access panel may be closed.
If Flame Lifted Off Ports (Too Much Primary Air) — Turn
spoiler screw clockwise about 4 turns for each1⁄4 in. of change
in spoiler length. See Fig. 33 for spoiler screw location.
Replace main burner access panel and turn on main manual
gas valves. Observe flame characteristics. Repeat these pro-
cedures as required until correct flame characteristics are
achieved.
4. Close burner access panel.
5. Turn control circuit service switch to ON position. Set
zone thermostat to call for heat. After pilot is proven,
burner will operate.
NOTE: A time-delay relay will shut unit down in
180 seconds if main manual gas valve is not open.
6. Remove screw cap from zone module gas valve pres-
sure regulator to expose pressure adjustment screw.
Outdoor-Air Thermostat Adjustment (50ME with
Electric Heat) — The outdoor-air thermostat (OAT) is
located in upper right-hand area of zone control board
(Fig. 34 and 35), is factory set at 40 F, and is adjustable be-
tween −10 F and 55 F.
7. Turn pressure adjustment screw with a small screw-
driver until 3.5 in. wg is achieved.
8. Replace screw cap.
9. Turn control circuit service switch to OFF position and
set zone thermostat at lowest position.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 33 — Spoiler Screw Location
LEGEND
COMPR
COND
—
—
Compressor
Condensing
*AFS1 deenergizes control circuit if loss of indoor air occurs.
†Factory-supplied option.
Fig. 34 — Major Component Identification (Typical 10-Zone Unit Shown; 8-Zone Units Similar)
37
Download from Www.Somanuals.com. All Manuals Search And Download.
HTR
—
Heater
*AFS1 deenergizes control circuit if loss of outdoor air occurs.
†Factory-supplied option.
Fig. 35 — Major Component Identification (Typical 12-Zone Unit Shown).
When OAT is open, final stage heating element in all zone
modules is inactive. When OAT is closed, final stage heating
element in a zone module may be energized whenever second-
stage thermostat for that zone module calls for heat as
follows:
Be sure that temperature rise is within range shown on
unit instruction plate and Table 1 (48MA only).
Sequence of Operation — When unit power is on
and no zone thermostat is calling for cooling or heating, the
evaporator fan and crankcase heater(s) are on. The outdoor-
air dampers are at the pre-set position.
UNITS WITH 2-ELEMENT HEATERS
First-Stage Heat — One element energized
Second-Stage Heat
OAT Open — One element energized
OAT Closed — Two elements energized
UNITS WITH 3-ELEMENT HEATERS
First-Stage Heat — One element energized
Second-Stage Heat
OAT Open — Two elements energized
OAT Closed — Three elements energized
COOLING — On a call for cooling from a zone thermostat,
compressor no. 1, with unloader(s), starts; the liquid line so-
lenoid for that zone evaporator coil opens; and condenser-
fan motor no. 1 starts. Compressor will load or unload in
response to suction pressure as required. As additional cool-
ing is required (i.e., more zones call for cooling), compres-
sor no. 2 (no unloaders) will be energized (024-040 units
only). If required, compressor no. 1 will unload when com-
pressor no. 2 (024-040 units only) is energized. As cooling
requirements decrease, capacity control pressurestats pre-
vent compressor no. 1 from shutting down while compres-
sor no. 2 (024-040 units only) is in operation. Compressor
no. 1 will fully load up after compressor no. 2 (024-040 units
only) shuts down as required to match heat load.
If heat load is not sufficient to maintain operation of com-
pressor no. 1 in an unloaded condition, hot gas bypass valve
will meter hot gas to outdoor air evaporator coil to supply
additional load. On 48MA and 50ME040, hot gas is intro-
duced into evaporator whenever required to eliminate un-
loader short-cycle operation.
Optional Glycol Heating Coils — Start up glycol
solution supply system in accordance with equipment manu-
facturer’s instructions. Solution supply temperature must not
exceed 200 F. Maximum solution flow through each zone
module heating coil is 6 gpm.
Zone Airflow Adjustment — Adjust each zone duct
balancing damper to provide required airflow to each zone.
Increasing or decreasing airflow to one zone may cause a
change in the airflow to other zones. After initial damper
settings have been made, repeat the adjustment procedure,
as required, to be sure final desired airflows are achieved.
Do not go below 600 cfm or above 1200 cfm per zone
module.
The Motormaster head pressure control device will vary
speed of condenser-fan motor no. 1 to regulate airflow across
condenser coil. As required, condenser-fan motor no. 2
(no. 2 and 3 on 3-fan units) will cycle on and off in response
to head pressure via a cycling pressurestat. See Head Pres-
sure Control section on page 40.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
HEATING (48MA) — On call for heating from a zone, the
forced draft blower will start and the pilot will light. The
zone burner will ignite after the pilot has been proven. (Ap-
proximately 60 seconds.)
NOTE: A time-delay relay will shut unit down in 180 sec-
onds if the unit main gas valve is not open.
OUTDOOR-AIR INLET SCREENS — Clean with steam or
hot water and mild detergent.
GAS HEATING SECTION — Inspect burners and heat ex-
changers before each heating season. Remove exhaust grilles
to inspect heat exchangers. Clean with wire brush if there is
any accumulation of debris. The main burners should also
be cleaned if there is any accumulation of debris. Fire each
zone to be assured of proper operation. Correct pilot height
is 1 to 11⁄2 inches.
HEATING (50ME WITH ELECTRIC HEAT) — On a call
for heating from a zone, the first-stage heating relay, con-
tactor, and heating element are energized. Upon additional
calls for heating from that zone, stage 2 is energized in a
similar manner. However, second element on 2-element heater
assemblies and second and third heating elements on 3-element
heater assemblies are energized as described in Outdoor Air
Thermostat Adjustment section on page 36.
COMBUSTION AIR FAN — Inspect blower wheel for dirt,
and remove and clean if necessary.
Airflow Switches
INDOOR AIRFLOW SWITCH (AFS1) — This switch is
located in evaporator fan inlet venturi. This switch will shut
down unit if airflow through zone modules is insufficient.
COMBUSTIONAIRFLOW SWITCH (AFS2) — This switch
(48MAonly) is located in combustion air plenum. This switch
will shut down unit heating mode if combustion air is in-
sufficient. See Forced-Draft Blower (48MA) section on
page 42 for details on combustion air shutter adjustment.
Heating Lockout (50ME with Electric Heat) — If any zone
module is operating on mechanical cooling (Compressor[s]
is operating), one heating element in each zone module is
locked out and zone module cannot be energized. Operation
of lockout circuit is independent of outdoor-air thermostat
operation.
HEATING (50ME WITH GLYCOL HEATING COILS) —
On a call for heating from a zone, the heating relay and heat-
ing coil solenoid valve for that zone are energized. If 2 or
more unit zone modules are joined to serve a common zone,
stage 2 of heating thermostat operates remaining heating
relays and solenoid valves depending on connection
arrangement.
OUTDOOR-AIR DAMPER — This control regulates the
amount of outdoor air that passes through the outdoor air
evaporator coil and enters the return air-stream (Fig. 34 and
35). A knob in the zone control and thermostat panel acti-
vates the damper control motor (damper operator). Damper
may be fully closed, fully open, or set at any intermediate
position by setting the knob as desired. In the fully open po-
sition, the damper will permit 25% outdoor air and 75% re-
turn air into the unit.
Service Switch — A control circuit service switch is
located in the power and condensing control box (Fig. 34
and 35). Shut down unit (compressors, fans, and control cir-
cuits) at this switch.
Do not use compressor circuit breakers to start and stop
compressors except in emergency.
Time Guardா Control Circuit — Each compressor
circuit has a 5-minute delay before restarting compressor af-
ter shutdown for any reason. On starting, Time Guard device
timer causes a delay of 15 seconds after thermostat closes
before compressor starts. On compressor shutdown, timer re-
cycles for 4 minutes, 45 seconds. During this time, compres-
sor cannot restart.
On 2-compressor units, no. 2 compressor will not start for
at least 21⁄2 minutes after no. 1 compressor starts. See
Capacity Control Pressure Switches section below.
SERVICE
Cabinet Panels and Grilles
Capacity Control Pressure Switches (CCP)
SIDE PANELS — To remove a panel, remove lower screw
on T-fastener. Loosen T-fastener pivot screw. Swing aside
T-fastener. Pull bottom of panel out and down.
TOP PANELS — Remove end caps from each end of rain
covers. Remove panel screws and lift off panels as required.
Save end caps and screws for reinstallation.
(2-Compressor Units Only) — These switches are
connected to the suction side of the system on compressor
no. 2. Approximately 21⁄2 minutes after compressor no. 2 starts,
the timer makes the circuit to CCP1 and CCP2 to operate
compressor no. 2 as follows:
1. CCP1 is open (opens at 63 psig; closes at 83 psig). This
prevents cycling of compressor no. 2 at start-up.
HEATERACCESS PANELS — See Side Panels section above.
2. CCP2 is closed (opens at 54 psig; closes at 78 psig).
3. Holding relay no. 2 (HR2) is deenergized.
When the suction pressure reaches 83 psig, CCP1 closes
to energize HR2 and compressor no. 2. Compressor no. 2
will then be operated by CCP2.
Cleaning — Inspect unit interior at the beginning of each
heating and cooling season and during each season as op-
erating conditions require. Remove unit side panels and top
panels to expose unit interior as required.
EVAPORATOR COILS (ZONE COOLING COILS) AND
GLYCOL HEATING COILS — Clean with a stiff brush,
vacuum cleaner, or compressed air.
CONDENSER AND OUTDOOR-AIR COOLING COILS
— Clean with a stiff brush or vacuum cleaner. If cleaning
with compressed air or low-pressure water or steam, guard
against damaging compressor, wiring, and nearby controls.
CONDENSATE DRAINS — Check and clean annually at
start of cooling season.
INDOOR-AIR FILTERS — Clean or replace filters at start
of each heating and cooling season and as often as necessary
during each season, depending on operating conditions. Re-
fer to Table 1 for type and size of filters used. Filter section
is shown in Fig. 34 and 35. Indoor-air filter tracks will ac-
cept 2 layers of one-in. thick filters.
Compressor Oil — Compressors have their own oil sup-
ply. Compressor crankcases on 2-compressor units are in-
terconnected. Loss of oil due to a leak in the system should
be the only reason for adding oil after unit has been in op-
eration. A sight glass is provided in the crankcase intercon-
nection line or on the compressor crankcase. Remove end
panels to gain access to compressors. Sight glass on 06D
1
2
compressor should be about ⁄3 to ⁄3 full of oil. Sight glass
1
1
on 06E compressor should be about ⁄8 to ⁄2 full of oil.
Compressor data is shown in Table 1 and on dataplate at-
tached to compressor body. Refer to 06D or 06E Compres-
sor Service Manual for additional compressor service
information.
39
Download from Www.Somanuals.com. All Manuals Search And Download.
TO ADD OR REMOVE OIL
1. Close liquid line and hot gas bypass shutoff valves. See
Fig. 31.
2. Pump down compressor and close suction and discharge
service valves. Recover remaining refrigerant in
compressor.
If unit power is shut off for longer than a few hours, make
sure power is on and that crankcase heater(s) has been on for
at least 24 hours prior to start-up. This will ensure that re-
frigerant has been driven out of compressor crankcase(s). To
prevent start-up during this warm-up period, set control cir-
cuit service switch at OFF position.
Refrigerant Charge — Quantity and type of refriger-
ant is shown on unit nameplate and in Table 1. Add refrig-
erant as follows:
NO CHARGE — Evacuate refrigerant system and add re-
frigerant quantity specified or add 15 lb of refrigerant vapor
to system and then refer to Low Charge section below.
3. Add oil through oil filler plug.
4. To remove oil, remove crankcase oil drain plug, and drain
only as much oil as is required.
Compressor Capacity Control Unloader(s)
(Fig. 36) — Unloader(s) on compressor no. 1 are suction-
pressure actuated to load or unload compressor at factory
settings indicated in Table 1. If necessary, unloader(s) may
be field adjusted or reset as follows:
CONTROL SET POINT (Cylinder Load Point) — This un-
loader set point is adjustable from 0 to 85 psig. To adjust,
turn control set point adjustment nut clockwise to its bottom
stop. In this position, load point is 85 psig. Turn adjustment
nut counterclockwise to desired load point. Each full turn
counterclockwise decreases load point by 7.5 psig.
LOW CHARGE
1. Set control circuit service switch at OFF position.
2. Disconnect evaporator-fan contactor.
3. Manually close airflow switch (AFS1) on evaporator fan
housing (Fig. 34 and 35) with a piece of tape.
4. Remove MH jumper (or master heating relay, MHR, if
remote control panel accessory is used) from zone con-
trol board to lock out heating.
PRESSURE DIFFERENTIAL (Difference Between Cylin-
der Load and Unload Points) — This unloader set point is
adjustable from 6 to 22 psig. To adjust, remove differential
adjustment screw sealing cap to expose pressure differential
adjustment screw. Turn adjustment screw counterclockwise
to its backstop position. In this position pressure differential
is 6 psig. Turn adjustment clockwise to desired pressure dif-
ferential. Each full turn clockwise increases differential by
1.5 psig.
5. Remove all cooling relays (CR) except CR8, from zone
control board.
6. Add jumper on terminals R-Y on module 8.
7. Reset control circuit service switch to ON position.
8. Operate unit for about 5 minutes.
9. Add refrigerant vapor at no. 1 compressor suction serv-
ice valve fitting at a rate of one lb per minute.
10. Check liquid level in accumulator sight glass. Use ac-
cumulator no. 1 on 040 units (adjacent to compressor
no. 1). Add refrigerant until sight glass is 1⁄2 full. If sight
glass appears clear (no bubbles) but a film of refrigerant
shows at bottom of sight glass, refrigerant level is be-
low sight glass. Continue adding refrigerant until sight
glass is 1⁄2 full. If sight glass appears clear, but bubbles
can be seen, refrigerant level is above top of glass. Re-
frigerant system is overcharged. Recover refrigerant un-
1
til sight glass is ⁄2 full.
11. When correct refrigerant charge has been achieved, re-
store unit to normal operation (reverse Steps 2-7).
12. Be sure airflow switch (AFS1) functions normally and
control circuit service is set at ON position.
Head Pressure Control
MOTORMASTER HEAD PRESSURE CONTROL
DEVICE — Outdoor (condenser) fan motor no. 1 (OFM1)
is a 208/230-v motor operated by a Motormaster device ther-
mistor (a thermally sensitive resistor) located on the con-
denser coil as shown in Fig. 37. The function of this control
is to maintain proper saturated condensing temperature at
low outdoor ambient temperatures. The control does this by
modulating OFM1 speed in response to the saturated con-
densing temperature sensed by the thermistor. Control is fac-
tory set and cannot be adjusted or serviced. However, ther-
mistor or control may be replaced if necessary.
FAN CYCLING PRESSURESTAT — Outdoor (condenser)
fan motor no. 2 (OFM2), and no. 3 on 3-fan units (OFM3)
is controlled by a nonadjustable pressurestat connected to
compressor no. 1.
Fan(s) shuts off at 86 F saturated condensing temperature
(160 psig), restarts at 118 F (approximately 255 psig).
Fig. 36 — Compressor Capacity Control
Unloader
Crankcase Heater(s) — One heater for each compres-
sor keeps oil free of refrigerant while compressor is off. Crank-
case heater(s) is automatically deenergized when the com-
pressor(s) is in operation.
40
Download from Www.Somanuals.com. All Manuals Search And Download.
LUBRICATION — Condenser-fan motors have factory-
lubricated bearings. No relubrication is necessary for the first
3 to 5 years of continuous operation except in excessively
dirty outdoor-air applications. After the first relubrication bear-
ings must be opened, cleaned, and repacked annually with
light- to medium-duty multi-purpose grease.
Evaporator Fans and Motor
Shut off service switch to deenergize evaporator-fan
motor.
MOTOR REMOVAL — Disconnect motor power wires at
conduit connection on unit junction box. Then remove mo-
tor and conduit assembly from unit.
FAN SHAFT BEARING REMOVAL
1. Remove fan motor and belts.
2. Loosen the locknut on each shaft bearing collar and re-
move the fan drive pulley.
3. Loosen the fan wheel locknuts and slide out fan shaft.
4. Remove the 2 bearings.
Reverse steps 1-4 to reassemble.
FAN SPEED ADJUSTMENT — Pulley listed in Table 1 is
factory installed in the unit.
If the factory-supplied pulley is not suitable, provide a field-
supplied pulley of the correct size as required. Refer to
Table 1 for additional fan data.
IMPORTANT: Increasing fan speed increases load on
motor. Do not exceed maximum fan motor full load
amperage (Tables 2 and 3).
Fig. 37 — Motormasterா Thermistor
Locations on Condenser Coil
Condenser Fans
Fig. 38 — Condenser-Fan Adjustment
Shut off service switch to deenergize condenser-fan
motors.
ADJUSTMENT — Remove fan guard from top of unit. Re-
move rubber hubcap from fan hub and loosen fan hub set-
screws. Adjust fan height using a straight edge laid across
fan deck venturi (Fig. 38). Tighten setscrews and replace rub-
ber hubcap to prevent hub from rusting to motor shaft. Fill
hub recess with Permagum (or similar adhesive) if rubber
hubcap is missing.
FAN MOTOR REMOVAL — Disconnect motor electrical
leads at motor control box. Loosen fan hub setscrews and
remove fan. Loosen motor mounting band and lift out
motor.
Reverse this procedure for reassembly.
41
Download from Www.Somanuals.com. All Manuals Search And Download.
PULLEY REMOVAL
1. Shut off unit power.
2. Loosen fan motor mounting plate and remove belt.
3. Loosen pulley setscrew.
4. Slide pulley off shaft.
Reverse steps 1-4 to install new pulley.
PULLEYALIGNMENT — Loosen fan pulley setscrews and
slide fan pulley along fan shaft for parallel alignment. Make
angular alignment by loosening motor from mounting plate.
BELT TENSION ADJUSTMENT — Loosen fan motor pivot
bolts. Pull back motor mounting plate to proper belt tension
(approximately 3⁄4-in. deflection with one finger) and tighten
motor pivot bolts.
LUBRICATION — Evaporator-fan shaft and motor bear-
ings require annual lubrication after 3 to 5 years of continu-
ous operation as follows:
48MA016 AND 024
48MA028-040
Fig. 39 — Forced-Draft Blower
Shutter Position
DAMPER POSITION — When outdoor-air damper is fully
open, the return-air damper will be fully closed and vice versa.
OPERATION
Heating or Compressor Cooling — Dampers will assume the
ventilation position indicated by the ventilation control knob.
If a remote control center is used, DAY/NIGHT switch must
be at the DAY position.
Fan Shaft Bearings — Automotive-type grease fittings are
factory supplied. Apply a medium-duty, lithium-based grease
to fittings while rotating shaft.
Fan Motor Bearings — Remove plugs and install automotive-
type grease fittings. Use a suitable motor bearing grease per
motor manufacturer’s recommendations.
If terminals in unit control box labeled SHORT TO CLOSE
DAMPERS are shorted or if DAY/NIGHT switch is set at
NIGHT position, outdoor-air damper will close.
Intermediate Season (Free Cooling Using Optional Econo-
mizer) — If outdoor-air temperature drops below econo-
mizer outdoor-air thermostat (ECT) setting, the compressor(s)
will remain off. The dampers will modulate to maintain the
mixed-air thermostat (MAT) setting. If the outdoor air tem-
perature rises above the ECT setting, the unit will operate as
described in Heating or Compressor Cooling section above.
Forced-Draft Blower (48MA)
LUBRICATION — Add 2 or 3 drops of a good grade of
no. 20 SAE (Society of Automotive Engineers) motor oil at
each oil cup on the motor once a year.
AIR SHUTTER ADJUSTMENT — The air shutter is held
in position on the blower inlet by a wing nut. Loosen wing
nut and reposition shutter until correct pressure is achieved.
Combustion chamber air pressure is to be measured through
drain connection below heat exchangers. Correct pressures
are 0.10 ± 0.01 in. wg for units 48MA016,024,034, and 040;
0.14 ± 0.01 for units 48MA028 and 030. Figure 39 shows
correct shutter position. Note pivot hole location.
Optional Exhaust Damper — See Fig. 34 and 35.
When unit is on economizer cycle (free cooling) and an ex-
haust damper is part of the unit, the exhaust relay is ener-
gized. The fan motor controls the Motormaster head pres-
sure control and the fan cycling pressure switches are bypassed
so that condenser fans operate at full speed as follows:
Zone Module Transformers — When replacing these
transformers, be sure to connect wires on correct terminals
to maintain correct polarity. See base unit label diagram on
the unit for connections.
• Fan no. 1 and 2 on units 48MA/50ME016-030
• Fan no. 2 and 3 on units 48MA/50ME034,040
When the return air damper is 25% closed, the exhaust
damper begins to open. The condenser fans pull indoor re-
turn air through the open exhaust damper and discharge it to
the outdoors.
Optional Economizer — See Fig. 40.
THERMOSTAT SETTINGS — Set economizer outdoor air
thermostat (ECT) at a temperature which will provide cool-
ing with outdoor air only. This setting, when achieved, will
lock out the compressor(s). A 45 F setting is suggested.
Replacement Parts — A complete list of replacement
parts may be obtained from any Carrier distributor upon
request.
Set mixed-air thermostat (MAT) as desired to provide mixed
air of the correct temperature. This setting cannot be lower
than the ECT setting. A 58 F setting is suggested.
42
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
1
2
—
—
—
—
—
—
—
—
—
—
Bearing Liner
Speed Nut (5⁄16 in.)
Washer
3
4
Rivet
5
Speed Nut (7⁄16 in.)
Speed Nut (1⁄4 in.)
Damper Lever
Linkage Bar
6
7
8
9
Linkage Rod (15 in.)
Linkage Rod (22 in.)
10
Airflow Direction
Fig. 40 — Economizer and Exhaust Damper Assemblies, Exploded View
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
PACKAGED SERVICE TRAINING
Our packaged service training programs provide an excellent way to increase your knowledge of the
equipment discussed in this manual. Product programs cover:
• Unit Familiarization
• Installation Overview
• Maintenance
• Operating Sequence
A large selection of product, theory, and skills programs is available. All programs include a video
cassette and/or slides and a companion booklet. Use these for self teaching or to conduct full training
sessions.
For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are
included.
Copyright 1996 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 PC 111 Catalog No. 564-840 Printed in U.S.A. Form 48MA/50ME-3SI Pg 46 4-96 Replaces: 48MA/50ME-1SI
Tab 1c 1d
1
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
START-UP CHECKLIST
MODEL NO.:
DATE:
SERIAL NO.:
TECHNICIAN:
PRE-START-UP:
Ⅺ VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
Ⅺ REMOVE ALL SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTRUCTIONS
Ⅺ VERIFY INSTALLATION OF ECONOMIZER HOOD
Ⅺ VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS
Ⅺ VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT
Ⅺ CHECK GAS PIPING FOR LEAKS (48MA)
Ⅺ CHECK THAT INDOOR-AIR FILTER IS CLEAN AND IN PLACE
Ⅺ VERIFY THAT UNIT IS LEVEL
Ⅺ CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SET SCREW
IS TIGHT
Ⅺ VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED
START-UP
ELECTRICAL
SUPPLY VOLTAGE L1-L2
L2-L3
L3-L1
COMPRESSOR AMPS — COMPRESSOR NO. 1 L1
— COMPRESSOR NO. 2 L1
L2
L2
L3
L3
SUPPLY FAN AMPS
EXHAUST FAN AMPS
ELECTRIC HEAT AMPS (50ME, IF APPLICABLE) L1
L2
L3
TEMPERATURES
OUTDOOR-AIR TEMPERATURE
RETURN-AIR TEMPERATURE
COOLING SUPPLY AIR
F
F
F
F
DB (Dry-Bulb)
DB
F
WB (Wet-Bulb)
GAS HEAT SUPPLY AIR (48MA)
ELECTRIC HEAT SUPPLY AIR (50ME, IF APPLICABLE)
F
PRESSURES
GAS INLET PRESSURE (48MA)
IN. WG
STAGE NO. 1
STAGE NO. 2
GAS MANIFOLD PRESSURE (48MA)
IN. WG
IN. WG
REFRIGERANT SUCTION
CIRCUIT NO. 1
PSIG
PSIG
CIRCUIT NO. 2
CIRCUIT NO. 2
PSIG
PSIG
REFRIGERANT DISCHARGE CIRCUIT NO. 1
Ⅺ VERIFY REFRIGERANT CHARGE
GENERAL
Ⅺ ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS
Copyright 1996 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 PC 111 Catalog No. 564-840 Printed in U.S.A. Form 48MA/50ME-3SI Pg CL-1 4-96 Replaces: 48MA/50ME-1SI
Tab 1c 1d
1
Download from Www.Somanuals.com. All Manuals Search And Download.
|