50TCQA
Single Package Rooftop
Heat Pump
with Puronr (R---410A) Refrigerant
S i z e s 0 4 --- 0 7
Installation Instructions
NOTE: Read the entire instruction manual before starting
the installation
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical
shock or other conditions which may cause personal
injury or property damage. Consult a qualified installer,
service agency, or your distributor or branch for
information or assistance. The qualified installer or
agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when
installing.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Step 1 - Plan for Unit Location . . . . . . . . . . . . . . . . . . 4
Step 2 - Plan for Sequence of Unit Installation . . . . . . 5
Step 3 - Inspect Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Step 4 - Provide Unit Support . . . . . . . . . . . . . . . . . . . 5
Step 5 - Field Fabricate Ductwork . . . . . . . . . . . . . . . . 7
Step 6 - Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 7
Step 7 - Convert to Horizontal & Connect Ductwork . 8
Step 8 - Install Outside Air Hood . . . . . . . . . . . . . . . . 8
Step 9 - Install External Condensate Trap and Line . 10
Step 10 - Make Electrical Connections . . . . . . . . . . . 11
Step 11 - Adjust Factory-Installed Options . . . . . . . . 44
Step 12 - Install Accessories . . . . . . . . . . . . . . . . . . . 45
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloths for brazing operations and
have a fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and appropriate
national electrical codes (in USA, ANSI/NFPA70,
National Electrical Code (NEC); in Canada, CSA C22.1)
for special requirements.
It is important to recognize safety information. This is the
safety-alert symbol
. When you see this symbol on the
unit and in instructions or manuals, be alert to the
potential for personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety-alert symbol. DANGER identifies the most serious
hazards which will result in severe personal injury or
death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify
unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
Download from Www.Somanuals.com. All Manuals Search And Download.
Vertical Connections / Economizer
Horizontal Connections / Economizer
C09001
Fig. 1 - Unit Dimensional Drawing – 04 — 07 Size Units
3
Download from Www.Somanuals.com. All Manuals Search And Download.
C09002
Fig. 1 - Unit Dimensional Drawing – 04 — 07 Size Unit (cont.)
INSTALLATION
Jobsite Survey
18” (457)1
Complete the following checks before installation.
42" (1067)
1. Consult local building codes and the NEC (National
Electrical Code) ANSI/NFPA 70 for special installa-
tion requirements.
2. Determine unit location (from project plans) or select
unit location.
18" (457)
42" (1067)
3. Check for possible overhead obstructions which may
interfere with unit lifting or rigging.
1 Required bottom condensate drain connection.
Otherwise, 36” (914mm) for condensate connection.
Step 1 — Plan for Unit Location
C07459
Select a location for the unit and its support system (curb
or other) that provides for the minimum clearances
required for safety. This includes the clearance to
combustible surfaces, unit performance and service access
below, around and above unit as specified in unit
drawings. See Fig. 2.
Fig. 2 - Service Clearance Dimensional Drawing
Although unit is weatherproof, avoid locations that permit
water from higher level runoff and overhangs to fall onto
the unit.
NOTE: Consider also the effect of adjacent units.
Select a unit mounting system that provides adequate
height to allow for removal and disposal of frost and ice
that will form durring the heating-defrost mode as well as
allow installation of condensate trap per requirements.
Refer to Step 9 — Install External Condensate Trap and
Line – for required trap dimensions.
Unit may be installed directly on wood flooring or on Class
A, B, or C roof-covering material when roof curb is used.
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated
air.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Roof mount —
Step 3 — Inspect unit
Inspect unit for transportation damage. File any claim
with transportation agency.
Check building codes for weight distribution
requirements. Unit operating weight is shown in Table 1.
Confirm before installation of unit that voltage, amperage
and circuit protection requirements listed on unit data
plate agree with power supply provided.
Step 2 — Plan for Sequence of Unit Installation
The support method used for this unit will dictate different
sequences for the steps of unit installation. For example,
on curb-mounted units, some accessories must be
installed on the unit before the unit is placed on the curb.
Review the following for recommended sequences for
installation steps.
Step 4 — Provide Unit Support
Roof Curb Mount —
Accessory roof curb details and dimensions are shown in
Fig. 3. Assemble and install accessory roof curb in
accordance with instructions shipped with the curb.
Curb-mounted installation —
Install curb
Install field-fabricated ductwork inside curb
NOTE: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket supplied with
the roof curb as shown in Fig. 3. Improperly applied
gasket can also result in air leaks and poor unit
performance.
Install accessory thru-base service connection package
(affects curb and unit) (refer to accessory installation
instructions for details)
Prepare bottom condensate drain connection to suit
planned condensate line routing (refer to Step 9 for
details)
Curb should be level. This is necessary for unit drain to
function properly. Unit leveling tolerances are show in
Fig. 4. Refer to Accessory Roof Curb Installation
Instructions for additional information as required.
Rig and place unit
Install outdoor air hood
Install insulation, cant strips, roofing felt, and counter
flashing as shown. Ductwork must be attached to curb and
not to the unit. The accessory thru-the-base power package
must be installed before the unit is set on the roof curb.
Install condensate line trap and piping
Make electrical connections
Install other accessories
Pad-mounted installation —
If electric and control wiring is to be routed through the
basepan, attach the accessory thru-the-base service
connections to the basepan in accordance with the
accessory installation instructions.
Prepare pad and unit supports
Check and tighten the bottom condensate drain
connection plug
Rig and place unit
Slab Mount (Horizontal Units Only) —
Convert unit to side duct connection arrangement
Install field-fabricated ductwork at unit duct openings
Install outdoor air hood
Install condensate line trap and piping
Make electrical connections
Provide a level concrete slab that extends a minimum of
6 in. (150 mm) beyond unit cabinet. Install a gravel apron
in front of condenser coil air inlet to prevent grass and
foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb
if required.
Install other accessories
Frame-mounted installation —
Alternate Unit Support (In Lieu of Curb or Slab
Mount) —
Frame-mounted applications generally follow the
sequence for a curb installation. Adapt as required to
suit specific installation plan.
A non-combustible sleeper rail can be used in the unit curb
support area. If sleeper rails cannot be used, support the long
sides of the unit with a minimum of 3 equally spaced 4-in. x
4-in. (102 mm x 102 mm) pads on each side.
Table 1 – Operating Weights
50TCQA
Component
UNITS LB (KG)
A04
A05
A06
A07
Base Unit
505 (229)
510 (231)
590 (268)
630 (286)
Economizer
Vertical
80 (36)
105 (48)
32 (15)
80 (36)
105 (48)
32 (15)
80 (36)
105 (48)
32 (15)
80 (36)
105 (48)
32 (15)
Horizontal
Powered Outlet
Curb
14---in/356 mm
24---in/610 mm
110 (50)
145 (66)
110 (50)
145 (66)
110 (50)
145 (66)
110 (50)
145 (66)
5
Download from Www.Somanuals.com. All Manuals Search And Download.
ROOFCURB
ACCESSORY
UNIT SIZE
1’ - 2”
[356]
CRRFCURB001A02
CRRFCURB002A02
50TCQA04-07
2’ - 0”
[610]
C08548
Fig. 3 - Roof Curb Details
6
Download from Www.Somanuals.com. All Manuals Search And Download.
should be ducted through the roof deck to comply with
applicable fire codes.
For units with accessory electric heaters: Horizontal
applications require a minimum clearance to combustible
surfaces of 1-in (25 mm) from duct for first 12-in (305 mm)
away from unit. Vertical applications do not require a
minimum clearance.
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
Minimum clearance is not required around ductwork.
A-B
B-C
A-C
Step 6 — Rig and Place Unit
0.5” (13)
1.0” (25)
1.0” (25)
Keep unit upright and do not drop. Spreader bars are not
required if top crating is left on unit. Rollers may be used to
move unit across a roof. Level by using unit frame as a
reference. See Table 1 and Fig. 5 for additional information.
C06110
Fig. 4 - Unit Leveling Tolerances
Step 5 — Field Fabricate Ductwork
Cabinet return-air static pressure (a negative condition)
shall not exceed 0.35 in. wg (87 Pa) with economizer or
0.45 in. wg (112 Pa) without economizer.
Lifting holes are provided in base rails as shown in Fig. 5.
Refer to rigging instructions on unit.
!
CAUTION
For vertical ducted applications, secure all ducts to roof
curb and building structure. Do not connect ductwork to
unit.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in
equipment damage.
Insulate and weatherproof all external ductwork, joints,
and roof openings with counter flashing and mastic in
accordance with applicable codes.
All panels must be in place when rigging. Unit is not
designed for handling by fork truck.
Ducts passing through unconditioned spaces must be
insulated and covered with a vapor barrier.
Before setting the unit onto the curb, recheck gasketing on
curb.
If a plenum return is used on a vertical unit, the return
C06005
DIMENSIONS
MAX WEIGHT
A
B
C
UNIT
LB
KG
343
345
381
399
IN
MM
1889
1889
1889
1889
IN
MM
921
921
905
946
IN
MM
848
50TCQA04
50TCQA05
50TCQA06
50TCQA07
755
760
840
880
74.38
74.38
74.38
74.38
36.25
36.25
35.63
37.25
33.38
33.38
41.38
41.38
848
1051
1051
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the
unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.
Fig. 5 - Rigging Details
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Positioning on Curb —
Step 8 — Install Outside Air Hood
Economizer Hood Removal and Setup - Factory
Option
Position unit on roof curb so that the following clearances
are maintained: /4 in. (6.4 mm) clearance between the
1
roof curb and the base rail inside the front and rear, 0.0 in.
clearance between the roof curb and the base rail inside on
the duct end of the unit. This will result in the distance
between the roof curb and the base rail inside on the
condenser end of the unit being approximately equal to
Fig. 3, section C-C.
1. The hood is shipped in knock-down form and
located in the return air compartment. It is attached
to the economizer using two plastic tie-wraps.
2. To gain access to the hood, remove the filter access
panel. (See Fig. 7.)
3. Locate and cut the (2) plastic tie-wraps, being
careful to not damage any wiring. (See Fig. 8.)
4. Carefully lift the hood assembly through the filter
access opening and assemble per the steps outlined
in Economizer Hood and Two–Position Hood on
page 10.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
After unit is in position, remove the compressor access
panel. Holding the blocking between compressors with
one hand, cut the strapping. Carefully remove the
blocking without damaging tubing, wiring, or controls.
Remove the strapping and replace the access panel.
FILTER ACCESS PANEL
Remove all shipping materials and top skid. Recycle or
dispose of all shipping materials.
Step 7 — Convert to Horizontal and Connect
Ductwork (when required)
Unit is shipped in the vertical duct configuration. Unit
without factory-installed economizer or return air smoke
detector option may be field-converted to horizontal
ducted configuration. To convert to horizontal
configuration, remove screws from side duct opening
covers and remove covers. Using the same screws, install
covers on vertical duct openings with the insulation-side
down. Seals around duct openings must be tight. See
Fig. 6.
COMPRESSOR
ACCESS PANEL
OUTDOOR-AIR OPENING AND
INDOOR COIL ACCESS PANEL
C06023
Fig. 7 - Typical Access Panel Locations
Remove Hood Parts
Cut Plastic Ties
(2) Places
Economizer
C06108
Fig. 6 - Horizontal Conversion Panels
C08633
Fig. 8 - Economizer Wiring
Field-supplied flanges should be attached to horizontal
duct openings and all ductwork should be secured to the
flanges. Insulate and weatherproof all external ductwork,
joints, and roof or building openings with counter flashing
and mastic in accordance with applicable codes.
Do not cover or obscure visibility to the unit’s informative
data plate when insulating horizontal ductwork.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Two Position Damper Hood Removal and Setup -
Factory Option
3. Locate the (2) screws holding the metal tray to the
basepan and remove. Locate and cut the (2) plastic
tie-wraps securing the assembly to the damper. (See
Fig. 9.) Be careful to not damage any wiring or cut
tie-wraps securing any wiring.
4. Carefully lift the hood assembly (with metal tray)
through the filter access opening and assemble per
the steps outlined in Economizer Hood and
Two–Position Hood on page 10.
1. The hood is shipped in knock-down form and
assembled to a metal support tray using plastic
stretch wrap.
Located in the return air
compartment, the assembly’s metal tray is attached
to the basepan and also attached to the damper
using two plastic tie-wraps.
2. To gain access to the hood, remove the filter access
panel. (See Fig. 7.)
Hood Parts
Plastic Tie Wrap
Qty (2)
Screws for Metal Tray
Qty (2)
C08639
Fig. 9 - Damper Assembly
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Economizer Hood and Two-Position Hood —
filter rack (hood divider). Push the filter into position
past the open filter clips. Close the filter clips to lock
the filter into place. See Fig. 12.
NOTE: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be
used and must be discarded. Save the aluminum filter for
use in the power exhaust hood assembly.
1. The indoor coil access panel will be used as the top of
the hood. Remove the screws along the sides and bot-
tom of the indoor coil access panel. See Fig. 10.
DIVIDER
OUTSIDE
AIR
SIDE
PANEL
HOOD
CLEANABLE
ALUMINUM
FILTER
FILTER
BAROMETRIC
RELIEF
FILTER
CLIP
TOP
SIDE
C08634
PANEL
CAULK
HERE
Fig. 12 - Economizer Filter Installation
INDOOR
COIL
ACCESS
PANEL
INDOOR
COIL
ACCESS
PANEL
6. Caulk the ends of the joint between the unit top panel
and the hood top.
7. Replace the filter access panel.
C06025
Fig. 10 - Indoor Coil Access Panel Relocation
Step 9 — Install External Condensate Trap and
Line
2. Swing out indoor coil access panel and insert the
hood sides under the panel (hood top). Use the screws
provided to attach the hood sides to the hood top. Use
screws provided to attach the hood sides to the unit.
See Fig. 11.
3
The unit has one /4-in. condensate drain connection on
the end of the condensate pan and an alternate connection
on the bottom. See Fig. 13. Unit airflow configuration
does not determine which drain connection to use. Either
drain connection can be used with vertical or horizontal
applications.
TOP
When using the standard side drain connection, ensure the
red plug in the alternate bottom connection is tight. Do
this before setting the unit in place. The red drain pan can
be tightened with a 1/2 -in. square socket drive extension.
PANEL
INDOOR COIL
ACCESS PANEL
To use the alternate bottom drain connection, remove the
1
red drain plug from the bottom connection (use a /2 - i n .
LEFT
HOOD
square socket drive extension) and install it in the side
drain connection.
SCREW
SIDE
19 1/16”
B
(483mm)
33 3/8”
(848mm)
HOOD DIVIDER
C06026
Fig. 11 - Economizer Hood Construction
CONDENSATE PAN (SIDE VIEW)
3. Remove the shipping tape holding the economizer ba-
rometric relief damper in place.
ALTERNATE
BOTTOM DRAIN
STANDARD
SIDE DRAIN
DRAIN PLUG
(FACTORY-INSTALLED)
4. Insert the hood divider between the hood sides. See
Fig. 11 and 12. Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the
bottom filter rack for the aluminum filter.
5. Open the filter clips which are located underneath the
hood top. Insert the aluminum filter into the bottom
C08021
Fig. 13 - Condensate Drain Pan (Side View)
The piping for the condensate drain and external trap can
be completed after the unit is in place. See Fig. 14.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
unit disconnect. On a unit without a unit-mounted
disconnect, connect the source leads to compressor
contactor C and indoor fan contactor IFC pressure lugs
with unit field power leads.
MINIMUM PITCH
1” (25mm) PER
10’ (3m) OF LINE
BASE RAIL
2˝ (51) MIN
All units except 208/230-v units are factory wired for the
voltage shown on the nameplate. If the 208/230-v unit is
to be connected to a 208-v power supply, the control
transformer must be rewired by moving the black wire
with the 1/4-in. female spade connector from the 230-v
connection and moving it to the 208-v 1/4-in. male
terminal on the primary side of the transformer. Refer to
unit label diagram for additional information. Field power
wires will be connected line-side pressure lugs on the
power terminal block or at factory-installed option
non-fused disconnect.
OPEN
VENT
TO ROOF
DRAIN
SEE NOTE
ROOF
CURB
DRAIN PLUG
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4” (102) trap is recommend. ed
C08022
Fig. 14 - Condensate Drain Piping Details
Field power wires are connected to the unit at line-side
pressure lugs on compressor contactor C and indoor fan
contactor IFC or terminal board (see wiring diagram label
for control box component arrangement) or at
factory-installed option non-fused disconnect switch.
Max wire size is #2 AWG (copper only). (See Fig. 16)
All units must have an external trap for condensate
drainage. Install a trap at least 4-in. (102 mm) deep and
protect against freeze-up. If drain line is installed
downstream from the external trap, pitch the line away
from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do
not use a pipe size smaller than the unit connection
(3/4-in.).
NOTE: TEST LEADS - Unit may be equipped with
short leads (pigtails) on the field line connection points on
contactor C or optional disconnect switch. These leads are
for factory run-test purposes only; remove and discard
before connecting field power wires to unit connection
points. Make field power connections directly to line
connection pressure lugs only.
Step 10 — Make Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
!
WARNING
FIRE HAZARD
Do not use gas piping as an electrical ground. Unit
cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of
personal injury if an electrical fault should occur. This
ground may consist of electrical wire connected to
unit ground lug in control compartment, or conduit
approved for electrical ground when installed in
accordance with NEC (National Electrical Code);
ANSI/NFPA 70, latest edition (in Canada, Canadian
Failure to follow this warning could result in
intermittent operation or performance satisfaction.
Do not connect aluminum wire between disconnect
switch and furnace. Use only copper wire.
(See Fig. 15.)
Electrical
Code
CSA
[Canadian
Standards
Association] C22.1), and local electrical codes.
ELECTRIC
DISCONNECT
SWITCH
NOTE: Check all factory and field electrical connections
for tightness. Field-supplied wiring shall conform with
the limitations of 63_F (33_C) rise.
COPPER
WIRE ONLY
ALUMINUM
WIRE
Field Power Supply —
If equipped with optional Powered Convenience Outlet:
The power source leads to the convenience outlet’s
transformer primary are not factory connected. Installer
must connect these leads according to required operation
of the convenience outlet. If an always-energized
convenience outlet operation is desired, connect the
source leads to the line side of the unit-mounted
disconnect. (Check with local codes to ensure this method
is acceptable in your area.) If a de-energize via unit
disconnect switch operation of the convenience outlet is
desired, connect the source leads to the load side of the
A93033
Fig. 15 - Disconnect Switch and Unit
Units Without Factory-Installed Disconnect —
When installing units, provide a disconnect switch per
NEC (National Electrical Code) of adequate size.
Disconnect sizing data is provided on the unit informative
plate. Locate on unit cabinet or within sight of the unit per
national or local codes. Do not cover unit informative
plate if mounting the disconnect on the unit cabinet.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Units with Factory-Installed Disconnect —
Convenience Outlets —
The factory-installed option disconnect switch is located
in a weatherproof enclosure located under the main
control box. The manual switch handle is accessible
through an opening in the access panel. Discard the
factory test leads (see Fig. 16).
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units Without Disconnect Option
Units with convenience outlet circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Tag-out this switch, if necessary.
IFC
(3 Phase
Indoor Motor)
C
(1 Phase Indoor Motor
and 1 Phase Unit)
11
13
13
TB
Disconnect
per
Two types of convenience outlets are offered on 50TCQA
models: Non-powered and unit-powered. Both types
NEC
provide
a
125-volt
GFCI
(ground-fault
L1
L2
L3
circuit-interrupter) duplex receptacle rated at 15-A
behind a hinged waterproof access cover, located on the
end panel of the unit. See Fig. 17.
208/230-1-60
208/230-3-60
460-3-60
575-3-60
Pwd-CO
Transformer
Units With Disconnect Option
Convenience
Outlet
GFCI
L1
2
1
Optional
Disconnect
Switch
Factory
Wiring
L2
L3
4
6
3
5
Pwd-CO
Fuse
Switch
Disconnect factory test leads; discard.
C09011
Fig. 16 - Power Wiring Connections
Control Box
Access Panel
All units -
All field wiring must comply with NEC and all local
codes. Size wire based on MCA (Minimum Circuit Amps)
on the unit informative plate. See Fig. 16 and the unit
label diagram for power wiring connections to the unit
power terminal blocks and equipment ground. Maximum
wire size is #2 ga AWG per pole.
C08128
Fig. 17 - Convenience Outlet Location
Installing Weatherproof Cover –
A
weatherproof
while-in-use
cover
for
the
factory-installed convenience outlets is now required by
UL standards. This cover cannot be factory-mounted due
its depth; it must be installed at unit installation. For
shipment, the convenience outlet is covered with a blank
cover plate.
Provide a ground-fault and short-circuit over-current
protection device (fuse or breaker) per NEC Article 440
(or local codes). Refer to unit informative data plate for
MOCP (Maximum Over-current Protection) device size.
All field wiring must comply with the NEC and local
requirements.
The weatherproof cover kit is shipped in the unit’s control
box. The kit includes the hinged cover, a backing plate
and gasket.
DISCONNECT ALL POWER TO UNIT AND
CONVENIENCE OUTLET.
Remove the blank cover plate at the convenience outlet;
discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until
approximately 1/2-in (13 mm) under screw heads are
exposed. Press the gasket over the screw heads. Slip the
backing plate over the screw heads at the keyhole slots
and align with the gasket; tighten the two screws until
snug (do not over-tighten).
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Mount the weatherproof cover to the backing plate as
shown in Fig. 18. Remove two slot fillers in the bottom of
the cover to permit service tool cords to exit the cover.
Check for full closing and latching.
the face of the receptacle to trip and open the receptacle.
Check for proper grounding wires and power line phasing
if the GFCI receptacle does not trip as required. Press the
RESET button to clear the tripped condition.
COVER – WHILE-IN-USE
RECEPTACLE
WEATHERPROOF
NOT INCLUDED
BASE PLATE FOR
GFCI RECEPTACLE
C09022
Fig. 18 - Weatherproof Cover Installation
C08283
UNIT
CONNECT
AS
PRIMARY
TRANSFORMER
TERMINALS
Non-powered type: This type requires the field
installation of a general-purpose 125-volt 15-A circuit
powered from a source elsewhere in the building. Observe
national and local codes when selecting wire size, fuse or
breaker requirements and disconnect switch size and
location. Route 125-v power supply conductors into the
bottom of the utility box containing the duplex receptacle.
VOLTAGE
CONNECTIONS
208,
230
L1: RED +YEL
L2: BLU + GRA
H1 + H3
H2 + H4
240
480
600
L1: RED
Splice BLU +
YEL
H1
H2 + H3
H4
460
575
L2: GRA
L1: RED
L2: GRA
H1
H2
Unit-powered type: A unit-mounted transformer is
factory-installed to stepdown the main power supply
voltage to the unit to 115-v at the duplex receptacle. This
option also includes a manual switch with fuse, located in
a utility box and mounted on a bracket behind the
convenience outlet; access is through the unit’s control
box access panel. See Fig. 17.
Fig. 19 - Powered Convenience Outlet Wiring
Using unit-mounted convenience outlets: Units with
unit-mounded convenience outlet circuits will often
require that two disconnects be opened to de-energize all
power to the unit. Treat all units as electrically energized
until the convenience outlet power is also checked and
de-energization is confirmed. Observe National Electrical
Code Article 210, Branch Circuits, for use of convenience
outlets.
The primary leads to the convenience outlet transformer
are not factory-connected. Selection of primary power
source is a customer-option. If local codes permit, the
transformer primary leads can be connected at the
line-side terminals on the unit-mounted non-fused
disconnect or HACR breaker switch; this will provide
service power to the unit when the unit disconnect switch
or HACR switch is open. Other connection methods will
result in the convenience outlet circuit being de-energized
when the unit disconnect or HACR switch is open. See
Fig. 19.
Fuse on power type: The factory fuse is a Bussman
“Fusetron” T-15, non-renewable screw-in (Edison base)
type plug fuse.
Factory-Option Thru-Base Connections —
1
This service connection kit consists of a /2 -in electrical
bulkhead connector and a 3/4 -in electrical bulkhead
connector, all factory-installed in the embossed (raised)
section of the unit basepan in the condenser section. The
1/2 -in bulkhead connector enables the low-voltage control
Duty Cycle: the unit-powered convenience outlet has a
duty cycle limitation. The transformer is intended to
provide power on an intermittent basis for service tools,
lamps, etc; it is not intended to provide 15-amps loading
for continuous duty loads (such as electric heaters for
overnight use). Observe a 50% limit on circuit loading
above 8-amps (i.e., limit loads exceeding 8-amps to 30
minutes of operation every hour).
3
wires to pass through the basepan. The /4 -in electrical
bulkhead connector allows the high-voltage power wires
to pass through the basepan. See Fig. 20.
Check tightness of connector lock nuts before connecting
electrical conduits.
Test the GFCI receptacle by pressing the TEST button on
13
Download from Www.Somanuals.com. All Manuals Search And Download.
control the reversing valve operation. If using an
electronic thermostat, configure it for “non-heat pump”
operation. Locate the thermostat accessory on a solid wall
in the conditioned space to sense average temperature in
accordance with the thermostat installation instructions.
LOW VOLTAGE
CONDUIT
CONNECTOR
If the thermostat contains a logic circuit requiring 24-v
power, use a thermostat cable or equivalent single leads of
different colors with minimum of seven leads. If the
thermostat does not require a 24-v source (no “C”
connection required), use a thermostat cable or equivalent
with minimum of six leads. Check the thermostat
installation instructions for additional features which
might require additional conductors in the cable.
HIGH VOLTAGE
CONDUIT
CONNECTOR
C08637
Fig. 20 - Thru-Base Connection Fittings
For wire runs up to 50 ft. (15 m), use no. 18 AWG
(American Wire Gage) insulated wire (35_C minimum).
For 50 to 75 ft. (15 to 23 m), use no. 16 AWG insulated
wire (35_C minimum). For over 75 ft. (23 m), use no. 14
AWG insulated wire (35_C minimum). All wire sizes
larger than no. 18 AWG cannot be directly connected to
the thermostat and will require a junction box and splice
at the thermostat.
Field-supplied and field-installed liquidtight conduit
connectors and conduit may be attached to the connectors
on the basepan. Pull correctly rated high voltage and low
voltage through appropriate conduits. Connect the power
conduit to the internal disconnect (if unit is so equipped)
or to the external disconnect (through unit side panel). A
hole must be field cut in the main control box bottom on
the left side so the 24-v control connections can be made.
Connect the control power conduit to the unit control box
at this hole.
Typical
Thermostat
Connections
Central
Terminal
Board
X
C
G
Units without Thru-Base Connections —
C
1. Install power wiring conduit through side panel open-
ings. Install conduit between disconnect and control
box.
2. Install power lines to terminal connections as shown
in Fig. 16.
T
H
E
R
M
O
S
T
G
W2
W1
Y2
Y1
R
W2
W1
(Note 2)
All Units —
O/B/Y2
(Note 1)
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate. See
Table 10. On 3-phase units, voltages between phases must
be balanced within 2% and the current within 10%. Use
the formula shown in the legend for Table 10, Note 2 (see
page 44) to determine the percent of voltage imbalance.
Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to
electrical components. Such operation would invalidate
any applicable Carrier warranty.
A
T
Y1
R
Note 1: Typical multi-function marking. Follow manufacturer’s configuration
instructions to select Y2. Do not configure for O output.
Note 2: W2 connection not required on units without electric heating.
Field Wiring
C09012
Field Control Wiring —
Fig. 21 - Typical Low-Voltage Control Connections
The 50TCQA unit requires an external temperature
Unit without thru-base connection kit —
control device. This device can be
a
thermostat
(field-supplied) or a PremierLink controller (available as
factory-installed option or as field-installed accessory, for
use on a Carrier Comfort Network or as a stand alone
control) or the RTU-MP Controller for Building
Management Systems using non-CCN protocols
(RTU-MP is available as a factory-installed option only).
Pass the thermostat control wires through the hole
provided in the corner post; then feed the wires through
the raceway built into the corner post to the control box.
Pull the wires over to the terminal strip on the upper-left
corner of the Central Terminal Board (CTB). See Fig. 22.
NOTE: If thru-the-bottom connections accessory is
used, refer to the accessory installation instructions for
information on routing power and control wiring.
Thermostat —
Install
a
Carrier-approved accessory
2
stage
Heat Anticipator Settings —
Cooling/Heating thermostat according to installation
instructions included with the accessory. The 50TCQ
models do not require a thermostat with an O function to
Set heat anticipator settings at 0.14 amp for the first stage
and 0.14 amp for second-stage heating, when available.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
RACEWAY
DISCONNECT MOUNTING
LOCATION
INDOOR
ACCESS
PANEL
UNIT BLOCK-OFF
PANEL
OUTDOOR
ACCESS PANEL
C08133
Fig. 23 - Typical Access Panel Location
HOLE IN END PANEL (HIDDEN)
C08027
Not all available heater modules may be used in every
unit. Use only those heater modules that are UL listed for
use in a specific size unit. Refer to the label on the unit
cabinet for the list of approved heaters.
Fig. 22 - Field Control Wiring Raceway
Electric Heaters
Unit heaters are marked with Heater Model Numbers. But
heaters are ordered as and shipped in cartons marked with
a corresponding heater Sales Package part number. See
Table 2 for correlation between heater Model Number and
Sales Package part number.
NOTE: The value in position 9 of the part number differs
between the sales package part number (value is 1 or 3)
and a bare heater model number (value is 0).
50TCQ units may be equipped with field-installed
accessory electric heaters. The heaters are modular in
design, with heater frames holding open coil resistance
wires strung through ceramic insulators, line-break limit
switches and a control contactor. One or two heater
modules may be used in a unit.
Heater modules are installed in the compartment below
the indoor (supply) fan outlet. Access is through the
indoor access panel. Heater modules slide into the
compartment on tracks along the bottom of the heater
opening. See Fig. 23, Fig. 24 and Fig. 25.
Table 2 – Heater Model Number
Bare Heater Model Number
C
C
R
R
H
E
A
T
E
R
R
0
1
0
0
1
1
A
A
0
0
0
0
Heater Sales Package PNO
Includes:
Bare Heater
H
E
A
T
E
Carton and packing materials
Installation sheet
DISCONNECT EMT OR RIGID CONDUIT SINGLE
CENTER MANUAL RESET
MOUNTING
LOCATION
(FIELD-SUPPLIED)
POINT BOX POST
LIMIT SWITCH
HEATER
COVERS
SINGLE POINT
MAIN
BRACKET AND BOX
HEATER
MODULE
HEATER
MODULE
HEATER
CONTROL CONDUIT
MOUNTING
SCREW
MOUNTING
BOX
DRIP BOOT
(LOCATION 1) (LOCATION 2) BRACKET
CONTROL WIRE TERMINAL BLOCK
C08134
Fig. 24 - Typical Component Location
15
Download from Www.Somanuals.com. All Manuals Search And Download.
CONTROL
BOX
2
1
1
1
2
1
3
3
BUSHING
SINGLE
POINT BOX
MOUNTING
SCREWS
DRIP BOOT
BRACKET
MOUNTING
SCREWS
TRACK
POWER
WIRES
2 3
2 1
1 3
1 1
FOAM
BUSHING
LLIED
PA
CORP
.
MDEL
NO.
OD
EAL NO.
FLANGE
22.2
IED AIR
NTIONING
UACCESS
1
3
23
2-
46N
.
P
/
N
5610-4
REV
HEATER
RELAYS
HEATER
MOUNTING
SCREWS
C08136
C08135
Fig. 26 - Typical Single Point Installation
Fig. 25 - Typical Module Installation
All fuses on 50TCQ units are 60-A. (Note that all heaters
are qualified for use with a 60-A fuse, regardless of actual
heater ampacity, so only 60-A fuses are necessary.)
Single Point Boxes without Fuses — Refer to accessory
heater and Single Point Box installation instructions for
details on tap connections.
Single Point Boxes and Supplementary Fuses — When
the unit MOCP device value exceeds 60-A, unit-mounted
supplementary fuses are required for each heater circuit.
These fuses are included in accessory Single Point Boxes,
with power distribution and fuse blocks. The single point
box will be installed directly under the unit control box,
just to the left of the partition separating the indoor
section (with electric heaters) from the outdoor section.
The Single Point Box has a hinged access cover. See
Fig. 26. The Single Point Box also includes pigtails to
complete the wiring between the Single Point Box and the
unit’s main control box terminals. Refer to the accessory
heater and Single Point Box installation instructions for
details on tap connections.
Low-Voltage Control Connections
—
Run the
low-voltage control leads from the heater module(s) -
VIO and BRN (two of each if two modules are installed;
identify for Module #1) - to the 4-pole terminal board
TB4 located on the heater bulkhead to the left of Heater
#1. Connect the VIO leads from Heater #1 and Heater #2
to terminal TB4-1. Connect the BRN leads to terminal
TB4-3. See Fig. 27.
DEFROST
BOARD
E-HEAT
ORN
BRN
P3-3
ORN
1
BRN
3
TB4
VIO
VIO
BRN BRN
Field
Connections
Elec Htr
VIO
HR2
HR1
BRN
BRN
VIO
HR1: On Heater 1 in Position #1
HR2: On Heater 2 in Position #2 (if installed)
C09013
Fig. 27 - Accessory Electric Heater Control Connections
16
Download from Www.Somanuals.com. All Manuals Search And Download.
PremierLinkt (Factory--Option) —
C08199
Fig. 28 - PremierLink Controller
The PremierLink controller (see Fig. 28) is compatible
with Carrier Comfort Networkr (CCN) devices. This
control is designed to allow users the access and ability to
change factory-defined settings, thus expanding the
function of the standard unit control board. CCN service
access tools include System Pilot (TM), Touch Pilot (TM)
and Service Tool. (Standard tier display tools Navigatort
and Scrolling Marquee are not suitable for use with latest
PremierLink controller (Version 2.x).)
The SAT is factory-wired. The SAT probe is wire-tied to
the supply-air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installation.
Re-position the sensor in the flange of the supply-air
opening or in the supply air duct (as required by local
codes). Drill or punch a /2 -in. hole in the flange or duct.
Use two field-supplied, self-drilling screws to secure the
sensor probe in a horizontal orientation. See Fig. 29.
1
The PremierLink control is factory-mounted in the
50TCQ unit’s main control box to the left of the Central
Terminal Board (CTB). Factory wiring is completed
through harnesses connected to the CTB thermostat. Field
connections are made at a 16-pole terminal block (TB1)
located on the bottom shelf of the unit control box in front
of the PremierLink controller. The factory-installed
PremierLink control includes the supply-air temperature
(SAT) sensor. The outdoor air temperature (OAT) sensor is
included in the FIOP/accessory EconoMi$ert2 package.
ROOF
CURB
SUPPLY AIR
TEMPERATURE
SENSOR
The PremierLink controller requires the use of a Carrier
electronic thermostat or a CCN connection for time
broadcast to initiate its internal timeclock. This is
necessary for broadcast of time of day functions
(occupied/unoccupied).
SUPPLY AIR
RETURN AIR
C08200
Fig. 29 - Typical Mounting Location for Supply Air
Temperature (SAT) Sensor on Small Rooftop Units
NOTE: PremierLink controller is shipped in Sensor
mode. To be used with a thermostat, the PremierLink
controller must be configured to Thermostat mode. Refer
to PremierLink Configuration instructions for Operating
Mode.
NOTE:
Refer to Form 33CS-58SI for complete
PremierLink configuration, operating sequences and
troubleshooting information. Have a copy of this manual
available at unit start-up.
NOTE: The sensor must be mounted in the discharge
airstream downstream of the cooling coil and any heating
devices. Be sure the probe tip does not come in contact
with any of the unit’s heater surfaces.
Supply Air Temperature (SAT) Sensor
—
On
FIOP-equipped 50TCQ unit, the unit is supplied with a
supply-air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 6-inches
(12.7 mm) in length. It is a nominal 10-k ohm thermistor.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
C09014
Fig. 30 - PremierLink Wiring Schematic
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Outdoor Air Temperature (OAT) Sensor — The OAT is
factory-mounted in the EconoMi$er2 (FIOP or
accessory). It is a nominal 10k ohm thermistor attached to
an eyelet mounting ring.
Connect T
-55
- See Fig. 31 for typical T-55 internal
connections. Connect the T-55 SEN terminals to TB1
terminals 1 and 3 (see Fig. 32).
TB1
1
PL
EconoMi$er2 — The PremierLink control is used with
EconoMi$er2 (option or accessory) for outdoor air
management. The damper position is controlled directly
by the PremierLink control; EconoMi$er2 has no internal
logic device.
SEN
SEN
J6-7
J6-6
3
C08212
Fig. 32 - PremierLink T-55 Sensor
Outdoor air management functions can be enhanced with
field-installation of these accessory control devices:
Connect T-56
-
See Fig. 33 for T-56 internal
Enthalpy control (outdoor air or differential sensors)
Space CO2 sensor
Outdoor air CO2 sensor
connections. Install a jumper between SEN and SET
terminals as illustrated. Connect T-56 terminals to TB1
terminals 1, 3 and 5 (see Fig. 34).
Refer to Table 3 for accessory part numbers.
Field connections — Field connections for accessory
sensor and input devices are made at the 16-pole terminal
block (TB1) located on the control box bottom shelf in
front of the PremierLink control (See Fig. 30). Some input
devices also require a 24-vac signal source; connect at
CTB terminal R at “THERMOSTAT” connection strip for
this signal source. See connections figures on following
pages for field connection locations (and for continued
connections at the PremierLink board inputs).
1
2
4
5
6
3
RED(+)
WHT(GND)
CCN COM
BLK(-)
SET
SEN
SW1
BLK
(T56)
BRN (GND)
BLU (SPT)
SENSOR WIRING
JUMPER
TERMINALS
AS SHOWN
Table 4 provides a summary of field connections for units
equipped with Space Sensor. Table 5 provides a summary
of field connections for units equipped with Space
Thermostat.
Space Sensors
-
The PremierLink controller is
Cool
Warm
factory-shipped configured for Space Sensor Mode. A
Carrier T-55 or T-56 space sensor must be used. T-55
space temperature sensor provides a signal of space
temperature to the PremierLink control. T-56 provides
same space temperature signal plus it allows for
adjustment of space temperature setpoints from the face of
the sensor by the occupants.
C08202
Fig. 33 - T-56 Internal Connections
TB1
1
PL
SEN
SEN
J6-7
PL
TB1
3
J6-6
Jumper
SET
SET
J6-5
5
1
2
4
5
6
3
C08213
RED(+)
WHT(GND)
CCN COM
Fig. 34 - PremierLink T-56 Sensor
BLK(-)
SEN
SW1
Connect Thermostat — A 7-wire thermostat connection
requires a 24-v power source and a common connection.
Use the R and C terminals on the CTB’s THERMOSTAT
connection strip for these. Connect the thermostat’s Y1,
Y2, W1, W2 and G terminals to PremierLink TB1 as
shown in Fig. 35.
BRN (GND)
BLU (SPT)
SENSOR WIRING
If the 50TCQ unit is equipped with factory-installed
smoke detector(s), disconnect the factory BLU lead at
TB1-6 (Y2) before connecting the thermostat. Identify the
BLU lead originating at CTB-DDC-1; disconnect at
TB1-6 and tape off. Confirm that the second BLU lead at
TB1-6 remains connected to PremierLink J4-8.
C08201
Fig. 31 - T-55 Space Temperature Sensor Wiring
19
Download from Www.Somanuals.com. All Manuals Search And Download.
CTB
SPACE
THERMOSTAT
THERMOSTAT
R
TB1
2
R
PL
J4-12
G
Y1
Y2
W1
W2
C
J4-10
J4-8
J4-6
J4-4
4
6
8
10
C
CTB
THERMOSTAT
C08119
Fig. 35 - Space Thermostat Connections
Table 3 – PremierLink Sensor Usage
OUTDOOR AIR
TEMPERATURE
SENSOR
RETURN AIR
TEMPERATURE
SENSOR
OUTDOOR AIR
ENTHALPY SENSOR
RETURN AIR
ENTHALPY SENSOR
APPLICATION
Differential Dry Bulb
Temperature with
PremierLink
(PremierLink requires
4 --- 20 m A A ctuator)
R eq uired ---
33ZCT55SPT
or equivalent
I nclud ed ---
---
---
---
CRTEMPSN001A00
Single Enthalpy with
PremierLink
(PremierLink requires
4 --- 20m A A ctuator)
R eq uires ---
HH57AC077
or equivalent
I nclud ed ---
Not Used
---
---
Differential Enthalpy
with PremierLink
(PremierLink requires
4 --- 20m A A ctuator)
R eq uires ---
HH57AC077
or equivalent
R eq uires ---
HH57AC078
or equivalent
I nclud ed ---
Not Used
NOTES:
CO Sensors (Optional):
2
33ZCSENCO2 --- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 --- Aspirator box used for duct---mounted CO room sensor.
2
33ZCT55CO2 --- Space temperature and CO room sensor with override.
2
33ZCT56CO2 --- Space temperature and CO room sensor with override and setpoint.
2
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4 – Space Sensor Mode
TB1 TERMINAL
FIELD CONNECTION
T55 --- S E N /T56 --- S E N
RMTOCC
INPUT SIGNAL
Analog (10k thermistor)
Discrete, 24VAC
1
2
3
T55 --- S E N /T56 --- S E N
CMPSAFE
Analog (10k thermistor)
Discrete, 24VAC
4
5
T56---SET
Analog (10k thermistor)
Discrete, 24VAC
6
FSD
7
LOOP---PWR
Analog, 24VDC
8
SPS
Discrete, 24VAC
9
IAQ---SEN
A nalog, 4 --- 20m A
Discrete, 24VAC
10
11
12
13
14
15
16
FILTER
I A Q --- CO M /O A Q --- CO M /R H --- CO M
CCN + (RED)
OAQ---SEN/RH---SEN
CCN Gnd (WHT)
AUX OUT(Power Exhaust)
CCN --- (BLK)
A nalog, 4 --- 20m A
Digital, , 5VDC
A nalog, 4 --- 20m A
Digital, 5VDC
(Output)Discrete 24VAC
Digital, 5VDC
LEGEND:
T 5 5
T 5 6
CCN
C MP SA F E
F ILT E R
--- Sp a c e Te m p e r a t u r e S e n so r
F S D --- F ir e S h u t d o w n
IA Q --- In d o o r A ir Q u a lit y ( C O )
OAQ --- Outdoor Air Quality (CO )
2
R H --- R e la t iv e H u m id it y
S F S --- S u p p ly Fa n S t a t u s
--- Sp a c e Te m p e r a t u r e S e n so r
--- Carrier Comfort Network (communication bus)
--- C o m p r e sso r S a f e t y
2
--- D i r t y F i lt e r S w i t c h
Table 5 – Thermostat Mode
TB1 TERMINAL
FIELD CONNECTION
INPUT SIGNAL
Analog (10k thermistor)
Discrete, 24VAC
1
2
RAT SEN
G
3
RAT SEN
Y1
Analog (10k thermistor)
Discrete, 24VAC
4
5
6
Y2
LOOP---PWR
Discrete, 24VAC
Analog, 24VDC
Discrete, 24VAC
Analog, 4---20mA
Discrete, 24VAC
Analog, 4---20mA
Digital, 5VDC
7
8
W1
9
I A Q --- S E N
10
11
12
13
14
15
16
W2
I A Q --- CO M /O A Q --- CO M /R H --- CO M
CCN + (RED)
O A Q --- S E N /R H --- S E N
CCN Gnd (WHT)
AUX OUT (Power Exhaust)
CCN --- (BLK)
Analog, 4---20mA
Digital, 5VDC
(Output) Discrete 24VAC
Digital, 5VDC
LEGEND:
CCN
G
IAQ
OAQ
RAT
---
---
---
---
---
Carrier Comfort Network (communication bus)
Thermostat Fan
RH --- Relative Humidity
W1 --- Thermostat Heat Stage 1
W2 --- Thermostat Heat Stage 2
Y1 --- Thermostat Cool Stage 1
Y2 --- Thermostat Cool Stage 2
Indoor Air Quality (CO )
2
Outdoor Air Quality (CO )
2
Return Air Temperature
21
Download from Www.Somanuals.com. All Manuals Search And Download.
If the 50TCQ unit has an economizer system and
free-cooling operation is required, a sensor representing
Return Air Temperature must also be connected
(field-supplied and installed). This sensor may be a T-55
Space Sensor (see Fig. 31) installed in the space or in the
return duct, or it may be sensor PNO 33ZCSENSAT,
installed in the return duct. Connect this sensor to TB1-1
and TB1-3 per Fig. 32.
Return Air Enthalpy Sensor — Mount the return-air
enthalpy sensor (33CSENTSEN) in the return-air section
of the economizer. The return air sensor is wired to the
enthalpy controller (33CSENTHSW). See Fig. 37.
24V
RED
ECONO
MOTOR
– 4-20
Main
BLK
GND
LOW
Configure the unit for Thermostat Mode — Connect to the
CCN bus using a CCN service tool and navigate to
PremierLink Configuration screen for Operating Mode.
Default setting is Sensor Mode (value 1). Change the
value to 0 to reconfigure the controller for Thermostat
Mode.
+ VDC
Out
GRA
ESL
When the PremierLink is configured for Thermostat
Mode, these functions are not available: Fire Shutdown
(FSD), Remote Occupied (RMTOCC), Compressor Safety
(CMPSAFE), Supply Fan Status (SFS), and Filter Pressure
Switch (FILTER).
+ 24-36
VDC In
– 4-20 Main
Out
C09027
Fig. 37 - Outside and Return Air Enthalpy Sensor
Wiring
Economizer controls —
Outdoor Air Enthalpy Control (PNO 33CSENTHSW) -
To wire the return air enthalpy sensor, perform the
following:
The enthalpy control (33CSENTHSW) is available as a
field-installed accessory to be used with the EconoMi$er2
damper system. The outdoor air enthalpy sensor is part of
the enthalpy control. (The separate field-installed
accessory return air enthalpy sensor (33CSENTSEN) is
required for differential enthalpy control. See Fig. 36.)
1. Use a 2-conductor, 18 or 20 AWG, twisted pair cable
to connect the return air enthalpy sensor to the enthal-
py controller.
2. Connect the field-supplied RED wire to (+) spade
connector on the return air enthalpy sensor and the
(+) terminal on the enthalpy controller. Connect the
BLK wire to (-) spade connector on the return air en-
thalpy sensor and the (-) terminal on the enthalpy
controller.
Locate the enthalpy control in the economizer next to the
Actuator Motor. Locate two GRA leads in the factory
harness and connect the gray lead labeled “ESL” to the
terminal labeled “LOW”. See Fig. 36. Connect the
enthalpy control power input terminals to economizer
actuator power leads RED (connect to 24V) and BLK
(connect to GND).
Indoor Air Quality (CO2 sensor) — The indoor air quality
sensor accessory monitors space carbon dioxide (CO2)
levels. This information is used to monitor IAQ levels.
Several types of sensors are available, for wall mounting
in the space or in return duct, with and without LCD
display, and in combination with space temperature
sensors. Sensors use infrared technology to measure the
levels of CO2 present in the space air.
Enthalpy
Switch
24V
RED
BLK
ECONO
MOTOR
GND
The CO2 sensors are all factory set for a range of 0 to
2000 ppm and a linear mA output of 4 to 20. Refer to the
instructions supplied with the CO2 sensor for electrical
requirements and terminal locations. See Fig. 38 for
typical CO2 sensor wiring schematic.
CTB
ECON
LOW
GRA
7
ESL
Factory Wiring Harness
C09026
Fig. 36 - Enthalpy Switch (33CSENTHSW) Connections
The outdoor enthalpy changeover setpoint is set at the
enthalpy controller.
Differential Enthalpy Control — Differential enthalpy
control is provided by sensing and comparing the outside
air and return air enthalpy conditions. Install the outdoor
air enthalpy control as described above. Add and install a
return air enthalpy sensor.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Refer to Form 33CS-58SI, PremierLink Installation,
Start-up, and Configuration Instructions, for detailed
configuration information
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus
weatherproof enclosure) — The outdoor air CO2 sensor is
designed to monitor carbon dioxide (CO2) levels in the
outside ventilation air and interface with the ventilation
damper in an HVAC system. The OAQ sensor is packaged
with an outdoor cover. See Fig. 40. The outdoor air CO2
sensor must be located in the economizer outside air hood.
+ 0-10VDC
-
SIG COM
4-20mA
+
ALARM
NC
COM RELAY
}
NO CONTACTS
24 VAC
OR
24 VDC
H G
+
-
2 1
J3
5 4 3 2 1
8 7 6
J4
C08635
Fig. 38 - Indoor/Outdoor Air Quality (CO2) Sensor
(33ZCSENCO2) - Typical Wiring Diagram
To accurately monitor the quality of the air in the
conditioned air space, locate the sensor near a return-air
grille (if present) so it senses the concentration of CO2
leaving the space. The sensor should be mounted in a
location to avoid direct breath contact.
COVER REMOVED
SIDE VIEW
C07135
Do not mount the IAQ sensor in drafty areas such as near
supply ducts, open windows, fans, or over heat sources.
Allow at least 3 ft (0.9 m) between the sensor and any
corner. Avoid mounting the sensor where it is influenced
by the supply air; the sensor gives inaccurate readings if
the supply air is blown directly onto the sensor or if the
supply air does not have a chance to mix with the room air
before it is drawn into the return airstream.
Fig. 40 - Outdoor Air Quality Sensor Cover
Wiring the Outdoor Air CO2 Sensor — A dedicated power
supply is required for this sensor. A two-wire cable is
required to wire the dedicated power supply for the sensor.
The two wires should be connected to the power supply
and terminals 1 and 2.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
OAQ sensor. See Fig. 38. Connect the 4 to 20 mA
terminal to the TB1-13 terminal of the 50TCQ. Connect
the SIG COM terminal to the TB1-11 terminal of the
50TCQA. See Fig. 41.
Wiring the Indoor Air Quality Sensor —
For each sensor, use two 2-conductor 18 AWG (American
Wire Gage) twisted-pair cables (unshielded) to connect
the separate isolated 24 vac power source to the sensor
and to connect the sensor to the control board terminals.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
sensor. See Fig. 38. Connect the 4-20 mA terminal to
terminal TB1-9 and connect the SIG COM terminal to
terminal TB1-11. See Fig. 39.
OAQ Sensor/RH Sensor
TB1
13
PL
J5-2
SEN
TB1
11
COM
J5-3
24 VAC
C08275
IAQ Sensor
TB1
9
PL
J5-5
Fig. 41 - Outdoor CO2 Sensor Connections
SEN
TB1
11
Smoke Detector/Fire Shutdown (FSD) — This function is
available only when PremierLink is configured for
(Space) Sensor Mode. The unit is factory-wired for
PremierLink FSD operation when PremierLink is
factory-installed.
COM
J5-3
24 VAC
C08636
Fig. 39 - Indoor CO2 Sensor (33ZCSENCO2)
Connections
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Fan (Pressure) Switch (NO, close on rise in pressure)
On 50TCQ units equipped with factory-installed Smoke
Detector(s), the smoke detector controller implements the
unit shutdown through its NC contact set connected to the
unit’s CTB input. The FSD function is initiated via the
smoke detector’s Alarm NO contact set. The PremierLink
communicates the smoke detector’s tripped status to the
CCN building control. See Fig. 30, the PremierLink
wiring schematic.
CTB
Thermostat
R
PL
J4-6
TB1
8
C08118
Fig. 43 - PremierLink Wiring Fan Pressure Switch
Connection
Filter Status Switch — This function is available only
when PremierLink is configured for (Space) Sensor Mode.
Remote Occupied Switch — The PremierLink control
permits a remote timeclock to override the control’s
on-board occupancy schedule and place the unit into
Occupied mode. This function may also provide a “Door
Switch” time delay function that will terminate cooling
and heating functions after a 2-20 minute delay.
PremierLink control can monitor return filter status in two
ways: By monitoring a field-supplied/installed filter
pressure switch or via supply fan runtime hours.
Using switch input: Install the dirty filter pressure switch
according to switch manufacturer’s instructions, to
measure pressure drop across the unit’s return filters.
Connect one side of the switch’s NO contact set to CTB’s
THERMOSTAT-R terminal. Connect the other side of the
NO contact set to TB1-10. Setpoint for Dirty Filter is set
at the switch. See Fig. 42.
Connect one side of the NO contact set on the timeclock
to CTB’s THERMOSTAT-R terminal. Connect the other
side of the timeclock contact to the unit’s TB1-2 terminal.
CTB
Thermostat
R
Remote Occupied
Filter Switch (NO, close on rising pressure (high drop))
Time Clock
CTB
Thermostat
TB1
2
PL
J4-12
R
C08214
Fig. 44 - PremierLink Wiring Remote Occupied
TB1
10
PL
J4-4
Refer to Form 33CS-58SI for additional information on
configuring the PremierLink control for Door Switch
timer function.
C08216
Fig. 42 - PremierLink Filter Switch Connection
Power Exhaust (output) - Connect the accessory Power
Exhaust contactor coils(s) per Fig. 45.
When the filter switch’s NO contact set closes as filter
pressure drop increases (indicating dirt-laden filters), the
input signal to PremierLink causes the filter status point to
read “DIRTY”.
Space Relative Humidity Sensor — The RH sensor is not
used with 50TCQ models at this time.
Using Filter Timer Hours: Refer to Form 33CS-58SI for
instructions on using the PremierLink Configuration
screens and on unit alarm sequence.
Power Exhaust
TB1
15
PL
J8-3
PEC
TAN
Supply Fan Status Switch — The PremierLink control can
CTB
THERMOSTAT
monitor
supply
fan
operation
through
a
field-supplied/installed differential pressure switch. This
sequence will prevent (or interrupt) operation of unit
cooling, heating and economizer functions until the
pressure switch contacts are closed indicating proper
supply fan operation.
C
GRA
C08120
Fig. 45 - PremierLink Power Exhaust Output
Connection
Install the differential pressure switch in the supply fan
section according to switch manufacturer’s instructions.
Arrange the switch contact to be open on no flow and to
close as pressure rises indicating fan operation.
CCN Communication Bus — The PremierLink controller
connects to the bus in a daisy chain arrangement.
Negative pins on each component must be connected to
respective negative pins, and likewise, positive pins on
each component must be connected to respective positive
pins. The controller signal pins must be wired to the signal
ground pins. Wiring connections for CCN must be made
at the 3-pin plug.
Connect one side of the switch’s NO contact set to CTB’s
THERMOSTAT-R terminal. Connect the other side of the
NO contact set to TB1-8. Setpoint for Supply Fan Status
is set at the switch. See Fig. 43.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
At any baud (9600, 19200, 38400 baud), the number of
controllers is limited to 239 devices maximum. Bus length
may not exceed 4000 ft, with no more than 60 total
devices on any 1000-ft section. Optically isolated RS-485
repeaters are required every 1000 ft.
Connecting CCN bus:
NOTE: When connecting the communication bus cable,
a
color code system for the entire network is
recommended to simplify installation and checkout. See
Table 7 for the recommended color code.
NOTE: Carrier device default is 9600 band.
Table 7 – Color Code Recommendations
COMMUNICATION BUS WIRE SPECIFICATIONS —
The CCN Communication Bus wiring is field-supplied
and field-installed. It consists of shielded 3-conductor
cable with drain (ground) wire. The cable selected must
be identical to the CCN Communication Bus wire used for
the entire network.
CCN BUS WIRE
COLOR
CCN PLUG PIN
NUMBER
SIGNAL TYPE
+
Ground
---
Red
White
Black
1
2
3
See Table 6 for recommended cable.
Table 6 – Recommended Cables
Connect the CCN (+) lead (typically RED) to the unit’s
TB1-12 terminal. Connect the CCN (ground) lead
(typically WHT) to the unit’s TB1-14 terminal. Connect
the CCN (-) lead (typically BLK) to the unit’s TB1-16
terminal. See Fig. 46.
MANUFACTURER
Alpha
CABLE PART NO.
2413 or 5463
A22503
American
Belden
8772
Columbia
02525
CCN Bus
TB1
12
PL
J2-1
+ (RED)
NOTE: Conductors and drain wire must be at least 20
AWG, stranded, and tinned copper. Individual conductors
must be insulated with PVC, PVC/nylon, vinyl, Teflon, or
polyethylene. An aluminum/polyester 100% foil shield
and an outer jacket of PVC, PVC/nylon, chrome vinyl, or
Teflon with a minimum operating temperature range of
- 2 0 _C to 60_C is required. Do not run communication
wire in the same conduit as or next to any AC voltage
wiring.
TB1
14
GND (WHT)
J2-2
TB1
16
– (BLK)
J2-3
C08276
Fig. 46 - PremierLink CCN Bus Connections
The communication bus shields must be tied together at
each system element. If the communication bus is entirely
within one building, the resulting continuous shield must
be connected to ground at only one single point. If the
communication bus cable exits from one building and
enters another building, the shields must be connected to
the grounds at a lightning suppressor in each building (one
point only).
25
Download from Www.Somanuals.com. All Manuals Search And Download.
The RTU-MP control is factory-mounted in the 50TCQ
unit’s main control box, to the left of the CTB. See
Fig. 48. Factory wiring is completed through harnesses
connected to the CTB. Field connections for RTU-MP
sensors will be made at the Phoenix connectors on the
RTU-MP board. The factory-installed RTU-MP control
includes the supply-air temperature (SAT) sensor. The
outdoor air temperature (OAT) sensor is included in the
FIOP/accessory EconoMi$er2 package.
RTU--MP control system
The RTU-MP controller, see Fig. 47, provides expanded
stand-alone operation of the HVAC system plus
connection and control through communication with
several Building Automation Systems (BAS) through
popular third-party network systems. The available
network systems are BACnet MP/TP, Modbus and
Johnson J2. Communication with LonWorks is also
possible by adding an accessory interface card to the
RTU-MP. Selection of the communication protocol and
baud rate are made at on-board DIP switches.
Refer to Table 8, RTU-MP Controller Inputs and Outputs
for locations of all connections to the RTU-MP board.
C07129
Fig. 47 - RTU-MP Multi-Protocol Control Board
C08652
Fig. 48 - 50TCQ Control Box Component Locations
26
Download from Www.Somanuals.com. All Manuals Search And Download.
C09015
Fig. 49 - RTU-MP System Control Wiring Diagram
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 8 – RTU-MP Controller Inputs and Outputs
BACnet OBJECT
TYPE OF I/O
NAME
CONNECTION PIN
NUMBERS
POINT NAME
INPUTS
Space Temperature Sensor
Supply Air Temperature
Local Outside Air Temperature Sensor
Space Temperature Offset Pot
Indoor Air Quality
Outdoor Air Quality
Safety Chain Feedback
Compressor Safety
sptsens
sat
oatsens
sptopot
iaq
oaq
safety
compstat
firedown
enthalpy
humstat
AI (10K Thermistor)
AI (10K Thermistor)
AI (10K Thermistor)
AI (100K Potentiometer)
A I (4 --- 20 m a)
J 20 --- 1, 2
J2---1, 2
J2---3, 4
J 20 --- 3
J4---2, 3
J4---5, 6
J1---9
A I (4 --- 20 m a)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
J1---2
Fire Shutdown
Enthalpy Switch
Humidistat Input Status
J 1 --- 10
J2---6, 7
J5---7, 8
CONFIGURABLE INPUTS*
Space Relative Humidity
Outside Air Relative Humidity
Supply Fan Status
sprh
oarh
A I (4 --- 20 m a)
A I (4 --- 20 m a)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
J 4 --- 2, 3 or J 4 --- 5, 6
fanstat
J5---1,2 or J5---3,4 or
J5 5,6 or J5---7,8
Filter Status
filtstat
Remote Occupancy Input
remocc
OUTPUTS
econocmd
Economizer Commanded Position
Supply Fan Relay State
4---20ma
J2---5
J1---4
J1---8
J1---7
J1---6
J1---5
J 11 --- 3
J 11 --- 7, 8
sf
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC, 1A)
Compressor 1 Relay State
Compressor 2 Relay State
Heat Stage 1 Relay State
Heat Stage 2 Relay State
Power Exhaust Relay State
Dehumidification Relay State
comp_1
comp_2
heat_1
heat_2
aux_2
humizer
LEGEND
AI --- A n a lo g In p u t
AO --- A n a lo g O u t p u t
DI --- D iscr e t e In p u t
DO --- Discrete Output
*
These inputs (if installed) take the place of the default input on the specific channel according to schematic.
Pa r a lle l p in s J 5 --- 1 = J 2 --- 6 , J 5 --- 3 = J 1 --- 1 0 , J 5 --- 5 = J 1 --- 2 a r e u se d f o r f ie ld --- in st a lla t io n .
The RTU-MP controller requires the use of a Carrier
space sensor. A standard thermostat cannot be used with
the RTU-MP system.
accessory). It is a nominal 10k ohm thermistor attached to
an eyelet mounting ring.
EconoMi$er2 - The RTU-MP control is used with
EconoMi$er2 (option or accessory) for outdoor air
management. The damper position is controlled directly
by the RTU-MP control; EconoMi$er2 has no internal
logic device.
Supply Air Temperature (SAT) Sensor
-
On
FIOP-equipped 50TCQ unit, the unit is supplied with a
supply-air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 6-inches (12.7
mm) in length. It is a nominal 10-k ohm thermistor.
Outdoor air management functions can be enhanced with
field-installation of these accessory control devices:
The SAT is factory-wired. The SAT probe is wire-tied to
the supply-air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installation.
Re-position the sensor in the flange of the supply-air
opening or in the supply air duct (as required by local
Enthalpy control (outdoor air or differential sensors)
Space CO2 sensor
Outdoor air CO2 sensor
1
codes). Drill or punch a /2 -in. hole in the flange or duct.
Field Connections - Field connections for accessory
sensors and input devices are made the RTU-MP, at plugs
J1, J2, J4, J5, J11 and J20. All field control wiring that
connects to the RTU-MP must be routed through the
raceway built into the corner post as shown in Fig. 22.
Use two field-supplied, self-drilling screws to secure the
sensor probe in a horizontal orientation. See Fig. 29.
Outdoor Air Temperature (OAT) Sensor - The OAT is
factory-mounted in the EconoMi$er2 (FIOP or
28
Download from Www.Somanuals.com. All Manuals Search And Download.
BRN (COM)
The raceway provides the UL required clearance between
high- and low-voltage wiring. Pass the control wires
through the hole provided in the corner post, then feed the
wires thorough the raceway to the RTU-MP. Connect to
the wires to the removable Phoenix connectors and then
reconnect the connectors to the board.
BLK (STO)
BLU (SPT)
SENSOR
WIRING
OR
SET SEN
Space Temperature (SPT) Sensors
A field-supplied Carrier space temperature sensor is
required with the RTU-MP to monitor space temperature.
There are 3 sensors available for this application:
OPB COM- PWR+
S 33ZCT55SPT, space temperature sensor with override
button
POWER
WIRING
24 VAC
NOTE: Must use a separate isolated transformer.
S 33ZCT56SPT, space temperature sensor with override
button and setpoint adjustment
C07132
S 33ZCT59SPT, space temperature sensor with LCD
(liquid crystal display) screen, override button, and
setpoint adjustment
Fig. 52 - Space Temperature Sensor Typical Wiring
(33ZCT59SPT)
Economizer controls —
Use 20 gauge wire to connect the sensor to the controller.
The wire is suitable for distances of up to 500 ft. Use a
three-conductor shielded cable for the sensor and setpoint
adjustment connections. If the setpoint adjustment
(slidebar) is not required, then an unshielded, 18 or 20
gauge, two-conductor, twisted pair cable may be used.
Outdoor Air Enthalpy Control (PNO HH57AC077) -
The enthalpy control (HH57AC077) is available as a
field-installed accessory to be used with the EconoMi$er2
damper system. The outdoor air enthalpy sensor is part of
the enthalpy control. (The separate field-installed
accessory return air enthalpy sensor (HH57AC078) is
required for differential enthalpy control. See “Return Air
Enthalpy Sensor” below.)
Connect T-55 - See Fig. 31 for typical T-55 internal
connections. Connect the T-55 SEN terminals to
RTU-MP J20-1 and J20-2. See Fig. 50.
Locate the enthalpy control in the economizer hood.
Locate two GRA leads in the factory harness and connect
these leads to enthalpy control sensors 2 and 3. See
Fig. 36. Connect the enthalpy control power input
terminals to economizer actuator power leads RED
(connect to TR) and BLK (connect to TR1).
J20-1
J20-2
SEN
SEN
C08460
Fig. 50 - RTU-MP T-55 Sensor Connections
The outdoor enthalpy changeover setpoint is set at the
enthalpy controller.
Connect T-56 See Fig. 33 for T-56 internal
-
connections. Install a jumper between SEN and SET
terminals as illustrated. Connect T-56 terminals to
RTU-MP J20-1, J20-2 and J20-3 per Fig. 51.
Differential Enthalpy Control — Differential enthalpy
control is provided by sensing and comparing the outside
air and return air enthalpy conditions. Install the outdoor
air enthalpy control as described above. Add and install a
return air enthalpy sensor.
SEN
SEN
J20-1
J20-2
Return Air Enthalpy Sensor — Mount the return-air
enthalpy sensor (HH57AC078) in the return-air duct. The
return air sensor is wired to the enthalpy controller
(HH57AC077). See Fig. 37.
Jumper
SET
SET
To wire the return air enthalpy sensor, perform the
following:
J20-3
1. Use a 2-conductor, 18 or 20 AWG, twisted pair cable
to connect the return air enthalpy sensor to the enthal-
py controller.
C08461
Fig. 51 - RTU-MP T-56 Sensor Connections
2. At the enthalpy control remove the factory-installed
resistor from the (SR) and (+) terminals.
3. Connect the field-supplied RED wire to (+) spade
connector on the return air enthalpy sensor and the
(SR+) terminal on the enthalpy controller. Connect
the BLK wire to (S) spade connector on the return air
Connect T-59 - The T-59 space sensor requires a
separate, isolated power supply of 24 VAC. See Fig. 51
for internal connections at the T-59. Connect the SEN
terminal (BLU) to RTU-MP J20-1. Connect the COM
terminal (BRN) to J20-2. Connect the SET terminal (STO
or BLK) to J20-3.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
enthalpy sensor and the (SR) terminal on the enthalpy
controller.
with an outdoor cover. See Fig. 40. The outdoor air CO2
sensor must be located in the economizer outside air hood.
NOTE: The enthalpy control must be set to the “D”
setting for differential enthalpy control to work properly.
Wiring the Outdoor Air CO2 Sensor — A dedicated power
supply is required for this sensor. A two-wire cable is
required to wire the dedicated power supply for the sensor.
The two wires should be connected to the power supply
and terminals 1 and 2.
Indoor Air Quality (CO2 sensor) — The indoor air quality
sensor accessory monitors space carbon dioxide (CO2)
levels. This information is used to monitor IAQ levels.
Several types of sensors are available, for wall mounting
in the space or in return duct, with and without LCD
display, and in combination with space temperature
sensors. Sensors use infrared technology to measure the
levels of CO2 present in the space air.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
OAQ sensor. See Fig. 38. Connect the 4 to 20 mA
terminal to RTU-MP J4-5. Connect the SIG COM
terminal to RTU-MP J4-6.
The CO2 sensors are all factory set for a range of 0 to
2000 ppm and a linear mA output of 4 to 20. Refer to the
instructions supplied with the CO2 sensor for electrical
requirements and terminal locations. See Fig. 38 for
typical CO2 sensor wiring schematic.
OAQ Sensor/RH Sensor
J4-5
J4-6
SEN
To accurately monitor the quality of the air in the
conditioned air space, locate the sensor near a return-air
grille (if present) so it senses the concentration of CO2
leaving the space. The sensor should be mounted in a
location to avoid direct breath contact.
COM
24 VAC
C08463
Fig. 54 - RTU-MP / Outdoor CO2 Sensor
(33ZCSENCO2) Connections
Do not mount the IAQ sensor in drafty areas such as near
supply ducts, open windows, fans, or over heat sources.
Allow at least 3 ft (0.9 m) between the sensor and any
corner. Avoid mounting the sensor where it is influenced
by the supply air; the sensor gives inaccurate readings if
the supply air is blown directly onto the sensor or if the
supply air does not have a chance to mix with the room air
before it is drawn into the return airstream.
On 50TCQ units equipped with factory-installed Smoke
Detector(s), the smoke detector controller implements the
unit shutdown through its NC contact set connected to the
unit’s CTB input. The FSD function is initiated via the
smoke detector’s Alarm NO contact set. The RTU-MP
controller communicates the smoke detector’s tripped
status to the BAS building control. See Fig. 30, the
PremierLink wiring schematic.
Wiring the Indoor Air Quality Sensor —
For each sensor, use two 2-conductor 18 AWG (American
Wire Gage) twisted-pair cables (unshielded) to connect
the separate isolated 24 vac power source to the sensor
and to connect the sensor to the control board terminals.
The
Fire
Shutdown
Switch
configuration,
identifies the
MENU→Config→Inputs→input 5,
normally open status of this input when there is no fire
alarm.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
sensor. See Fig. 38. Connect the 4-20 mA terminal to
RTU-MP J4-2 and connect the SIG COM terminal to
RTU-MP J4-3. See Fig. 53.
Connecting Discrete Inputs
Filter Status
The filter status accessory is a field-installed accessory.
This accessory detects plugged filters. When installing
this accessory, the unit must be configured for filter status
by setting MENU→Config→Inputs→input 3, 5, 8, or 9
to Filter Status and normally open (N/O) or normally
closed (N/C). Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 47 and Fig. 49 for wire
terminations at J5.
IAQ Sensor
J4-2
SEN
COM
J4-3
24 VAC
C08462
Fan Status
Fig. 53 - RTU-MP / Indoor CO2 Sensor
(33ZCSENCO2) Connections
The fan status accessory is a field-installed accessory.
This accessory detects when the indoor fan is blowing air.
When installing this accessory, the unit must be
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus
weatherproof enclosure) — The outdoor air CO2 sensor is
designed to monitor carbon dioxide (CO2) levels in the
outside ventilation air and interface with the ventilation
damper in an HVAC system. The OAQ sensor is packaged
configured
for
fan
status
by
setting
MENU→Config→Inputs→input 3, 5, 8, or 9 to Fan
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer
to Fig. 47 and Fig. 49 for wire terminations at J5.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Space Relative Humidity Sensor - The RH sensor is not
used with 50TCQ models at this time.
Remote Occupancy
The remote occupancy accessory is a field-installed
accessory. This accessory overrides the unoccupied mode
and puts the unit in occupied mode. When installing this
accessory, the unit must be configured for remote
occupancy by setting MENU→Config→Inputs→input 3,
5, 8, or 9 to Remote Occupancy and normally open (N/O)
or normally closed (N/C).
Also set MENU→Schedules→occupancy source to DI
on/off. Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 47 and Table 8 for wire
terminations at J5.
Communication Wiring -- Protocols
General
Protocols are the communication languages spoken by
control devices. The main purpose of a protocol is to
communicate information in the most efficient method
possible. Different protocols exist to provide different
kinds of information for different applications. In the BAS
application, many different protocols are used, depending
on manufacturer. Protocols do not change the function of
a controller; just make the front end user different.
Power Exhaust (output)
The RTU-MP can be set to communicate on four different
protocols: BACnet, Modbus, N2, and LonWorks. Switch 3
(SW3) on the board is used to set protocol and baud rate.
Switches 1 and 2 (SW1 and SW2) are used to set the
board’s network address. See Fig. 56 for the switch setting
per protocol. The 3rd party connection to the RTU-MP is
through plug J19.
Connect the accessory Power Exhaust contactor coil(s) per
Fig. 55.
Power Exhaust
PEC
J11-3
TAN
CTB
THERMOSTAT
NOTE: Power must be cycled after changing the SW1-3
switch settings.
Refer to the RTU-MP 3rd Party Integration Guide for
more detailed information on protocols, 3rd party wiring,
and networking.
C
GRA
C08464
Fig. 55 - RTU-MP Power Exhaust Connections
SW3 Protocol Selection
DS6 DS5
OFF OFF
PROTOCOL
DS8
DS7
DS4
DS3
DS2
DS1
BACnet MS/TP
(Master)
Unused
OFF
ON
OFF
Select Baud Select Baud
Select Baud Select Baud
Modbus
(Slave)
Unused
OFF
OFF
ON
ON
OFF
N2
Unused
Unused
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
(Slave)
LonWorks
OFF
NOTE:
DS = Dip Switch
BACnet MS/TP SW3 example shown
Baud Rate Selections
BAUD RATE
9600
DS2
OFF
ON
DS1
OFF
OFF
ON
19,200
38,400
OFF
ON
76,800
ON
C07166
Fig. 56 - RTU-MP SW3 Dip Switch Settings
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Virtual BACview
Local Access
Virtual BACview is a freeware computer program that
functions as the BACview6 Handheld. The USB Link
interface (USB-L) is required to connect a computer to
the RTU-MP board. The link cable connects a USB port
to the J12 local access port. This program functions and
operates identical to the handheld.
6
BACview Handheld
The BACview6 is a keypad/display interface used to
connect to the RTU-MP to access the control information,
read sensor values, and test the RTU, see Fig. 57. This is
an accessory interface that does not come with the MP
controller and can only be used at the unit. Connect the
BACview6 to the RTU-MP’s J12 local access port. There
are 2 password protected levels in the display (User and
Admin). The user password is defaulted to 0000 but can
be changed. The Admin password is 1111 and cannot be
changed. There is a 10 minute auto logout if a screen is
idle. See Form 48-50H-T-2T, Appendix A for navigation
and screen content.
RTU--MP Troubleshooting
Communication LEDs
The LEDs indicate if the controller is speaking to the
devices on the network. The LEDs should reflect
communication traffic based on the baud rate set. The
higher the baud rate the more solid the LEDs will appear.
C07170
Fig. 57 - BACview6 Handheld Connections
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 9 – LEDs
The LEDs on the RTU-MP show the status of certain functions
If this LED is on...
Status is...
Power
Rx
Tx
The RTU MP has power
The RTU MP is receiving data from the network segment
The RTU MP is transmitting data over the network segment
The digital output is active
DO#
The Run and Error LEDs indicate control module and network status
If Run LED shows...
And Error LED shows...
Status is...
2 flashes per second
Off
Normal
2 flashes,
2 flashes per second
2 flashes per second
2 flashes per second
2 flashes per second
Five minute auto---restart delay after system error
Control module has just been formatted
alternating with Run LED
3 flashes,
then off
4 flashes,
then pause
Two or more devices on this network have the
same ARC156 network address
Exec halted after frequent system errors or
control programs halted
On
5 flashes per second
5 flashes per second
On
Off
Exec start---up aborted, Boot is running
Firmware transfer in progress, Boot is running
7 flashes per second, alternating with
7 flashes per second
14 flashes per second
Ten second recovery period after brownout
Run LED
14 flashes per second,
alternating with Run LED
Brownout
Failure. Try the following solutions:
S
S
S
S
Turn the RTU---MP off, then on.
Form at the R TU --- M P.
Download memory to the RTU---MP.
Replace the RTU---MP.
On
On
NOTE: Refer to Form 48-50H-T-2T for complete
configuration of RTU-MP, operating sequences and
troubleshooting information. Refer to RTU-MP 3rd Party
Integration Guide for details on configuration and
troubleshooting of connected networks. Have a copy of
these manuals available at unit start-up.
System
The smoke detector system consists of a four-wire
controller and one or two sensors. Its primary function is
to shut down the rooftop unit in order to prevent smoke
from circulating throughout the building. It is not to be
used as a life saving device.
Controller
SMOKE DETECTORS
The controller (see Fig. 58) includes a controller housing,
a printed circuit board, and a clear plastic cover. The
controller can be connected to one or two compatible duct
smoke sensors. The clear plastic cover is secured to the
housing with a single captive screw for easy access to the
wiring terminals. The controller has three LEDs (for
Power, Trouble and Alarm) and a manual test/reset button
(on the cover face).
Smoke detectors are available as factory-installed options
on 50TCQ models. Smoke detectors may be specified for
Supply Air only or for Return Air without or with
economizer or in combination of Supply Air and Return
Air. Return Air smoke detectors are arranged for vertical
return configurations only. All components necessary for
operation are factory-provided and mounted. The unit is
factory-configured for immediate smoke detector
shutdown operation; additional wiring or modifications to
unit terminal board may be necessary to complete the unit
and smoke detector configuration to meet project
requirements.
Sensor
The sensor (see Fig. 59) includes a plastic housing, a
printed circuit board, a clear plastic cover, a sampling
tube inlet and an exhaust tube. The sampling tube (when
used) and exhaust tube are attached during installation.
The sampling tube varies in length depending on the size
of the rooftop unit. The clear plastic cover permits visual
inspections without having to disassemble the sensor. The
cover attaches to the sensor housing using four captive
screws and forms an airtight chamber around the sensing
electronics. Each sensor includes a harness with an RJ45
Units equipped with factory-optional Return Air smoke
detectors require a relocation of the sensor module at unit
installation. See “Completing Installation of Return Air
Smoke Sensor:” on page 35 for details.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
terminal for connecting to the controller. Each sensor has
four LEDs (for Power, Trouble, Alarm and Dirty) and a
manual test/reset button (on the left-side of the housing).
Duct smoke sensor
Exhaust gasket
Exhaust tube
Sensor housing
and electronics
Duct smoke sensor
controller
See
Detail A
Conduit nuts
(supplied by installer)
Intake
gasket
Cover gasket
(ordering option)
Conduit support plate
Terminal block cover
TSD-CO2
(ordering option)
Sensor cover
Plug
Controller housing
and electronics
Cover gasket
(ordering option)
Sampling tube
(ordered separately)
Controller cover
Conduit couplings
(supplied by installer)
Coupling
Fastener
(2X)
Detail A
Trouble
Magnetic
test/reset
switch
Alarm
Power
Test/reset
switch
Alarm
Trouble
Power
Dirty
C08209
C08208
Fig. 59 - Smoke Detector Sensor
Smoke Detector Locations
Fig. 58 - Controller Assembly
Air is introduced to the duct smoke detector sensor’s
sensing chamber through a sampling tube that extends into
the HVAC duct and is directed back into the ventilation
system through a (shorter) exhaust tube. The difference in
air pressure between the two tubes pulls the sampled air
through the sensing chamber. When a sufficient amount of
smoke is detected in the sensing chamber, the sensor
signals an alarm state and the controller automatically
takes the appropriate action to shut down fans and
blowers, change over air handling systems, notify the fire
alarm control panel, etc.
Supply Air — The Supply Air smoke detector sensor is
located to the left of the unit’s indoor (supply) fan. See
Fig. 60. Access is through the fan access panel. There is
no sampling tube used at this location. The sampling tube
inlet extends through the side plate of the fan housing
(into a high pressure area). The controller is located on a
bracket to the right of the return filter, accessed through
the lift-off filter panel.
The sensor uses a process called differential sensing to
prevent gradual environmental changes from triggering
false alarms. A rapid change in environmental conditions,
such as smoke from a fire, causes the sensor to signal an
alarm state but dust and debris accumulated over time
does not.
For installations using two sensors, the duct smoke
detector does not differentiate which sensor signals an
alarm or trouble condition.
Smoke Detector Sensor
C08245
Fig. 60 - Typical Supply Air Smoke Detector Sensor
Location
Return Air without Economizer — The sampling tube is
located across the return air opening on the unit basepan.
See Fig. 61. The holes in the sampling tube face
34
Download from Www.Somanuals.com. All Manuals Search And Download.
downward, into the return air stream. The sampling tube is
connected via tubing to the return air sensor that is
mounted on a bracket high on the partition between return
filter and controller location. (This sensor is shipped in a
flat-mounting location. Installation requires that this
sensor be relocated to its operating location and the tubing
to the sampling tube be connected. See “Completing
Installation of Return Air Smoke Sensor:” for details.)
Completing Installation of Return Air Smoke
Sensor:
1. Unscrew the two screws holding the Return Air
Sensor detector plate. See Fig. 63. Save the screws.
2. Remove the Return Air Sensor and its detector plate.
3. Rotate the detector plate so the sensor is facing out-
wards and the sampling tube connection is on the bot-
tom. See Fig. 64.
4. Screw the sensor and detector plate into its operating
position using screws from Step 1. Make sure the
sampling tube connection is on the bottom and the ex-
haust tube is on the top. See Fig. 64.
Return Air Detector module
(shipping position shown)*
5. Connect the flexible tube on the sampling inlet to the
sampling tube on the basepan.
Controller module
Screws
Flexible
Exhaust Tubes
Return Air Detector Sampling Tube
*RA detector must be moved from shipping position to operating position by installer
Sample Tube
C07307
Fig. 61 - Typical Return Air Detector Location
C08126
Fig. 63 - Return Air Detector Shipping Position
Return Air with Economizer — The sampling tube is
inserted through the side plates of the economizer
housing, placing it across the return air opening on the
unit basepan. See Fig. 61. The holes in the sampling tube
face downward, into the return air stream. The sampling
tube is connected via tubing to the return air sensor that is
mounted on a bracket high on the partition between return
filter and controller location. (This sensor is shipped in a
flat-mounting location. Installation requires that this
sensor be relocated to its operating location and the tubing
to the sampling tube be connected. See the following
installation procedure.)
C08127
Fig. 64 - Return Air Sensor Operating Position
Additional Application Data — Refer to Catalog No.
HKRNKA-1XA for discussions on additional control
features of these smoke detectors including multiple unit
coordination.
Return Air
Sampling Tube
C08129
Fig. 62 - Return Air Sampling Tube Location
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10 – Unit Wire/MOCP Sizing Data
ELECTRIC HEATER
NO C.O. or UNPWRD C.O.
NO P.E.
w/ P.E. (pwrd fr/unit)
IFM
TYPE
Nom
FLA
DISC. SIZE
DISC. SIZE
(kW)
MCA
MOCP
MCA
MOCP
FLA
LRA
FLA
LRA
---
3.3/4.4
4.9/6.5
6.5/8.7
7.9/10.5
9.8/13.0
---
3.3/4.4
4.9/6.5
6.5/8.7
7.9/10.5
12.0/16.0
---
---
30.7
50.6/53.6
60.1/64.6
69.9/76.1
78.1/85.4
89.3/98.4
24.8
36.3/38.1
41.8/44.3
47.4/50.9
52.2/56.4
66.6/72.9
22.6
45
60/60
70/70
70/80
80/90
90/100
30
45/45
50/50
50/60
60/60
70/80
30
30
48/51
57/61
66/72
74/81
84/92
25
35/37
40/43
46/49
50/54
63/69
22
121
137/139
145/148
152/157
159/165
215/229
97
106/108
111/113
115/118
119/122
130/136
109
32.6
52.5/55.5
62.0/66.5
71.8/78.0
80.0/87.3
91.2/100.3
26.7
38.2/40.0
43.7/46.2
49.3/52.8
54.1/58.3
68.5/74.8
24.5
50
60/60
70/70
80/80
80/90
100/110
30
45/50
50/50
50/60
60/60
70/80
30
32
51/53
59/63
68/74
76/83
86/95
27
37/39
43/45
48/51
52/56
65/71
24
123
139/141
147/150
154/159
161/167
217/231
99
108/110
113/115
117/120
121/124
132/138
111
15.9/18.3
23.5/27.1
31.4/36.3
37.9/43.8
46.9/54.2
---
9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.5
---
STD
STD
3.3/4.4
4.9/6.5
6.5/8.7
7.9/10.5
12.0/16.0
---
3.3/4.4
4.9/6.5
6.5/8.7
7.9/10.5
12.0/16.0
---
9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.5
---
9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.5
---
34.1/35.9
39.6/42.1
45.2/48.7
50.0/54.2
64.4/70.7
22.6
34.1/35.9
39.6/42.1
45.2/48.7
50.0/54.2
64.4/70.7
16.0
45/45
45/50
50/50
50/60
70/80
30
45/45
45/50
50/50
50/60
70/80
20
33/34
38/40
43/46
47/51
61/66
22
33/34
38/40
43/46
47/51
61/66
16
118/120
123/125
127/130
131/134
142/148
120
129/131
134/136
138/141
142/145
153/159
53
36.0/37.8
41.5/44.0
47.1/50.6
51.9/56.1
66.3/72.6
24.5
36.0/37.8
41.5/44.0
47.1/50.6
51.9/56.1
66.3/72.6
17.0
45/45
50/50
50/60
60/60
70/80
30
45/45
50/50
50/60
60/60
70/80
20
35/37
40/42
45/48
50/53
63/69
24
35/37
40/42
45/48
50/53
63/69
17
120/122
125/127
129/132
133/136
144/150
122
131/133
136/138
140/143
144/147
155/161
54
MED
HIGH
6.0
7.2
25.0
30
24
60
26.0
30
26
61
8.8
11.5
14.0
---
6.0
8.8
11.5
14.0
10.6
13.8
16.8
---
7.2
10.6
13.8
16.8
29.3
33.3
37.0
10.6
19.6
23.9
27.9
31.6
30
35
40
15
20
25
30
35
28
32
36
10
19
23
26
30
64
67
70
54
61
65
68
71
30.3
34.3
38.0
11.6
20.6
24.9
28.9
32.6
35
35
40
15
25
25
30
35
30
33
37
12
20
24
27
31
65
68
71
55
62
66
69
72
STD
MED
HIGH
---
6.0
8.8
---
7.2
10.6
10.6
19.6
23.9
15
20
25
10
19
23
60
67
71
11.6
20.6
24.9
15
25
25
12
20
24
61
68
72
11.5
13.8
27.9
30
26
74
28.9
30
27
75
14.0
16.8
31.6
35
30
77
32.6
35
31
78
STD
MED
HIGH
---
---
---
---
---
---
5.4
3.4
2.9
15
15
15
5
3
3
5
8
7.4
5.4
4.9
20
20
20
15
15
15
7
10
14
12
NOTE: See page 44 for table legend and notes.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10 — Unit Wire/MOCP Sizing Data (cont)
ELECTRIC HEATER
w/ PWRD C.O.
NO P.E.
w/ P.E. (pwrd fr/unit)
IFM
TYPE
Nom
(kW)
DISC. SIZE
DISC. SIZE
FLA
MCA
MOCP
MCA
MOCP
FLA
LRA
FLA
LRA
---
3.3/4.4
4.9/6.5
6.5/8.7
7.9/10.5
9.8/13.0
---
3.3/4.4
4.9/6.5
6.5/8.7
7.9/10.5
12.0/16.0
---
---
35.5
55.4/58.4
64.9/69.4
74.7/80.9
82.9.90.2
94.1/103.2
29.6
41.1/42.9
46.6/49.1
52.2/55.7
57.0/61.2
71.4/77.7
27.4
50
60/60
70/80
80/90
90/100
100/110
40
50/50
50/50
60/60
60/70
80/80
40
36
54/57
63/67
72/77
79/86
90/98
30
41/42
46/48
51/54
55/59
69/75
28
126
142/144
150/153
157/162
164/170
220/234
102
111/113
116/118
120/123
124/127
135/141
114
37.4
57.3/60.3
66.8/71.3
76.6/82.8
84.8/92.1
96.0/105.1
31.5
43.0/44.8
48.5/51.0
54.1/57.6
58.9/63.1
73.3/79.6
29.3
50
60/70
70/80
80/90
90/100
100/110
40
50/50
50/60
60/60
60/70
80/80
40
38
56/59
65/69
74/80
81/88
92/100
32
43/45
48/50
53/56
58/62
71/77
30
128
144/146
152/155
159/164
166/172
222/236
104
113/115
118/120
122/125
126/129
137/143
116
15.9/18.3
23.5/27.1
31.4/36.3
37.9/43.8
46.9/54.2
---
9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.5
---
STD
STD
3.3/4.4
4.9/6.5
6.5/8.7
7.9/10.5
12.0/16.0
---
3.3/4.4
4.9/6.5
6.5/8.7
7.9/10.5
12.0/16.0
---
9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.5
---
9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.5
---
38.9/40.7
44.4/46.9
50.0/53.5
54.8/59.0
69.2/75.5
27.4
38.9/40.7
44.4/46.9
50.0/53.5
54.8/59.0
69.2/75.5
18.2
45/50
50/50
60/60
60/60
70/80
40
45/50
50/50
60/60
60/60
70/80
25
38/40
43/46
49/52
53/57
66/72
28
38/40
43/46
49/52
53/57
66/72
19
123/125
128/130
132/135
136/139
147/153
125
134/136
139/141
143/146
147/150
158/164
55
40.8/42.6
46.3/48.8
51.9/55.4
56.7/60.9
71.1/77.4
29.3
40.8/42.6
46.3/48.8
51.9/55.4
56.7/60.9
71.1/77.4
19.2
50/50
50/50
60/60
60/70
80/80
40
50/50
50/50
60/60
60/70
80/80
25
40/42
46/48
51.54
55/59
68/74
30
40/42
46/48
51/54
55/59
68/74
20
125/127
130/132
134/137
138/141
149/155
127
136/138
141/143
145/148
149/152
160/166
56
MED
HIGH
6.0
7.2
27.2
30
27
62
28.2
30
28
63
8.8
11.5
14.0
---
6.0
8.8
11.5
14.0
10.6
13.8
16.8
---
7.2
10.6
13.8
16.8
31.5
35.5
39.2
12.8
21.8
26.1
30.1
33.8
35
40
40
15
25
30
35
35
31
35
38
13
21
25
29
32
66
69
72
56
63
67
70
73
32.5
36.5
40.2
13.8
22.8
27.1
31.1
34.8
35
40
45
20
25
30
35
35
32
36
39
14
22
26
30
33
67
70
73
57
64
68
71
74
STD
MED
HIGH
---
6.0
8.8
---
7.2
10.6
12.8
21.8
26.1
15
25
30
13
21
25
62
69
73
13.8
22.8
27.1
20
25
30
14
22
26
63
70
74
11.5
13.8
30.1
35
29
76
31.1
35
30
77
14.0
16.8
33.8
35
32
79
34.8
35
33
80
STD
MED
HIGH
---
---
---
---
---
---
7.1
5.1
4.6
15
15
15
7
5
5
7
9.5
7.5
7.0
15
15
15
9
7
7
9
10
14
12
16
NOTE: See page 44 for table legend and notes.
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10 — Unit Wire/MOCP Sizing Data (cont)
ELECTRIC HEATER
NO C.O. or UNPWRD C.O.
NO P.E.
w/ P.E. (pwrd fr/unit)
IFM
TYPE
Nom
(kW)
DISC. SIZE
DISC. SIZE
FLA
MCA
MOCP
MCA
MOCP
FLA
LRA
FLA
LRA
---
3.3/4.4
6.5/8.7
9.8/13.0
13.1/17.4
15.821.0
---
4.9/6.5
6.5/8.7
12.0/16.0
15.8/21.0
---
4.9/6.5
6.5/8.7
12.0/16.0
15.8/21.0
---
4.9/6.5
6.5/8.7
12.0/16.0
15.8/21.0
---
---
36.2
50
35
128
38.1
50
37
130
15.9/18.3
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
---
13.6/15.6
18.1.20.9
33.4/38.5
43.8/50.5
---
13.6/15.6
18.1.20.9
33.4/38.5
43.8/50.5
---
13.6/15.6
18.1.20.9
33.4/38.5
43.8/50.5
---
56.0/59.0
75.4/81.5
94.8/103.9
60/60
80/90
100/110
54/56
71/77
89/98
144/146
159/164
222/236
57.9/60.9
77.3/83.4
96.7/105.8
60/70
80/90
100/110
56/59
74/79
91/100
146/148
161/166
224/238
STD
114.7/126.8 125/150 108/119 254/273 166.6/128.7 125/150 110/121 256/275
130.9/145.5 150/150 122/136 280/303 132.8/147.4 150/150 125/138 282/305
26.0
43.0/45.5
48.7/52.2
67.8/74.2
80.8/98.2
23.8
40.8/43.3
46.5/50.0
65.6/72.0
78.6/87.0
23.8
40.8/43.3
46.5/50.0
65.6/72.0
78.6/87.0
16.5
30
50/50
50/60
70/80
90/90
30
50/50
50/50
70/80
80/90
30
50/50
50/50
70/80
80/90
20
26
42/44
47/50
64/70
76/84
23
39/41
44/47
62/68
74/82
23
39/41
44/47
62/68
74/82
17
94
108/110
112/115
127/133
182/195
106
120/122
124/127
139/145
194/207
117
131/133
135/138
150/156
202/218
51
27.9
44.9/47.4
50.6/54.1
69.7/76.1
82.7/91.1
25.7
42.7/45.2
48.4/51.9
67.5/73.9
80.5/88.9
25.7
42.7/45.2
48.4/51.9
67.5/73.9
80.5/88.9
17.5
40
50/50
60/60
70/80
90/100
30
50/50
50/60
70/80
90/90
30
50/50
50/60
70/80
90/90
25
28
44/46
49/52
67/72
79/86
26
41/44
46/50
64/70
76/84
26
41/44
46/50
64/70
76/84
18
96
110/112
114/117
129/135
184/197
108
122/124
126/129
141/147
196/209
119
133/135
137/140
152/158
207/220
52
STD
MED
HIGH
STD
6.0
11.5
7.2
13.8
25.5
33.8
30
35
25
33
58
65
26.5
34.8
30
35
26
34
59
66
14.0
16.8
37.5
40
36
68
38.5
40
37
69
23.0
27.7
51.1
60
49
106
52.1
60
50
107
---
---
11.2
15
11
52
12.2
15
12
53
6.0
7.2
20.2
25
19
59
21.2
25
20
60
11.5
14.0
23.0
---
6.0
11.5
13.8
16.8
27.7
---
7.2
13.8
28.4
32.2
45.8
11.2
20.2
28.4
30
35
50
15
25
30
27
30
43
11
19
27
66
69
107
58
65
72
29.4
33.2
46.8
12.2
21.2
29.4
30
35
50
15
25
30
28
32
44
12
20
28
67
70
108
59
66
73
MED
HIGH
14.0
16.8
32.2
35
30
75
33.2
35
32
76
23.0
27.7
45.8
50
43
113
46.8
50
44
114
STD
MED
HIGH
---
---
---
---
---
---
10.6
9.0
15
15
15
11
9
43
46
50
12.5
10.9
10.5
15
15
15
13
11
11
45
48
52
8.6
9
NOTE: See page 44 for table legend and notes.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10 — Unit Wire/MOCP Sizing Data (cont)
ELECTRIC HEATER
w/ PWRD C.O.
NO P.E.
w/ P.E. (pwrd fr/unit)
IFM
TYPE
Nom
(kW)
DISC. SIZE
DISC. SIZE
FLA
MCA
MOCP
MCA
MOCP
FLA
LRA
FLA
LRA
---
3.3/4.4
6.5/8.7
9.8/13.0
13.1/17.4
15.821.0
---
4.9/6.5
6.5/8.7
12.0/16.0
15.8/21.0
---
4.9/6.5
6.5/8.7
12.0/16.0
15.8/21.0
---
4.9/6.5
6.5/8.7
12.0/16.0
15.8/21.0
---
---
41.0
60
41
133
149/151
164/169
42.9
62.7/65.7
82.1/88.2
60
80/80
90/100
43
135
15.9/18.3
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
---
13.6/15.6
18.1.20.9
33.4/38.5
43.8/50.5
---
13.6/15.6
18.1.20.9
33.4/38.5
43.8/50.5
---
13.6/15.6
18.1.20.9
33.4/38.5
43.8/50.5
---
60.8/63.8
80.2/86.3
99.6/108.7
70/80
90/90
100/110
59/62
77/83
95/103
61/64
79/85
97/105
151/153
166/171
229/243
STD
227/241 101.5/110.6 110/125
119.5/131.6 125/150 113/124 259/278 121.4/133.5 125/150 115/126 261/280
135.7/150.3 150/175 128/141 285/308 137.6/152.2 150/175 130/144 287/310
30.8
47.8/50.3
53.5/57.0
72.6/79.0
85.6/94.0
28.6
45.6/48.1
51.3/54.8
70.4/76.8
83.4/91.8
28.6
45.6/48.1
51.3/54.8
70.4/76.8
83.4/91.8
18.7
40
50/60
60/60
80/80
90/100
40
50/50
60/60
80/80
90/100
40
50/60
60/60
80/80
80/90
25
32
47/49
52/56
70/76
82/90
29
45/47
50/53
67/73
79/87
29
45/47
50/53
67/73
79/87
19
99
113/115
117/120
132/138
187/200
111
125/127
129/132
144/150
199/212
122
136/138
140/143
155/161
210/223
53
32.7
49.7/52.5
55.4/58.9
74.5/80.9
87.5/95.9
30.5
47.5/50.0
53.2/56.7
72.3/78.7
85.3/93.7
30.5
47.5/50.0
53.2/56.7
72.3/78.7
85.3/93.7
19.7
45
60/60
60/60
80/90
90/100
40
50/60
60/60
80/80
90/100
40
50/60
60/60
80/80
90/100
25
34
49/52
55/58
72/78
84/92
31
47/49
52/55
70/75
82/89
31
47/49
52/55
70/75
82/89
20
101
115/117
119/122
134/140
189/202
113
127/129
131/134
146/152
201/214
124
138/140
142/145
157/163
212/225
54
STD
MED
HIGH
STD
6.0
11.5
7.2
13.8
27.7
36.0
30
40
28
35
60
67
28.7
37.0
30
40
29
36
61
68
14.0
16.8
39.7
40
39
70
40.7
45
40
71
23.0
27.7
53.3
60
51
108
54.3
60
52
109
---
---
13.4
15
14
54
14.4
20
15
55
6.0
7.2
22.4
25
22
61
23.4
25
23
62
11.5
14.0
23.0
---
6.0
11.5
13.8
16.8
27.7
---
7.2
13.8
30.6
34.4
48.0
13.4
22.4
30.6
35
35
50
15
25
35
29
33
45
14
22
29
68
71
109
60
67
74
31.6
35.4
49.0
14.4
23.4
31.6
35
40
50
20
25
35
31
34
47
15
23
31
69
72
110
61
68
75
MED
HIGH
14.0
16.8
34.4
35
33
77
35.4
40
34
78
23.0
27.7
48.0
50
45
115
49.0
50
47
116
STD
MED
HIGH
---
---
---
---
---
---
12.3
10.7
10.3
15
15
15
13
11
10
45
48
52
14.2
12.6
12.2
20
15
15
15
13
13
47
50
54
NOTE: See page 44 for table legend and notes.
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10 — Unit Wire/MOCP Sizing Data (cont)
ELECTRIC HEATER
NO C.O. or UNPWRD C.O.
NO P.E.
w/ P.E. (pwrd fr/unit)
IFM
TYPE
Nom
(kW)
DISC. SIZE
DISC. SIZE
FLA
MCA
MOCP
MCA
MOCP
FLA
LRA
FLA
LRA
---
4.9/6.5
6.5/8.7
9.8/13.0
13.1/17.4
15.821.0
---
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
---
---
41.7
71.0/75.5
80.9/87.0
60
80/80
90/100
40
145
169/172
176/181
43.6
72.9/77.4
82.8/88.9
60
80/80
100/100
43
147
23.5/27.1
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
---
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
---
67/72
76/82
94/103
70/74
79/84
96/105
171/174
178/183
241/255
STD
STD
100.3/109.4 110/110
239/253 102.2/111.3 110/125
120.2/132.3 125/150 113/124 271/290 122.1/134.2 125/150 115/126 273/292
136.4/151.0 150/175 128/141 297/320 138.3/152.9 150/175 130/143 299/322
28.4
45.4/47.9
55.8/60.0
70.2/76.5
83.2/91.5
97.4/108.2
26.2
40
50/50
60/70
80/80
90/100
100/110
40
28
44/46
53/57
67/72
79/86
92/102
26
121
135/137
143/146
154/160
209/222
231/249
144
30.3
47.3/49.8
57.7/61.9
72.1/78.4
85.1/93.4
99.3/110.1
28.1
45
50/60
60/70
80/80
90/100
100/125
40
30
46/48
56/59
69/75
81/88
94/104
28
123
137/139
145/148
156/162
211/224
233/251
146
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
---
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
---
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
---
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
---
43.2/45.7
53.6/57.8
68.0/74.3
81.0/89.3
95.2/106.0
28.5
45.5/48.0
55.9/60.1
70.3/76.6
83.3/91.6
97.5/108.3
18.0
50/50
60/60
70/80
90/90
100/110
40
50/50
60/70
80/90
90/100
100/110
25
41/44
51/55
64/70
76/84
89/99
28
44/46
53/57
67/73
79/86
92/102
19
158/160
166/169
177/183
232/245
254/272
170
184/186
192/195
203/209
258/271
280/298
62
45.1/47.6
55.5/59.7
69.9/76.2
82.9/91.2
97.1/107.9
30.4
47.4/49.9
57.8/62.0
72.2/78.5
85.2/93.5
99.4/110.2
19.0
50/50
60/60
70/80
90/100
100/110
45
50/60
60/70
80/80
90/100
100/125
25
43/46
53/57
66/72
78/86
91/101
30
46/48
56/60
69/75
81/89
94/104
20
160/162
168/171
179/185
234/247
256/274
172
186/188
194/197
205/211
260/273
282/300
63
MED
HIGH
STD
6.0
11.5
14.0
7.2
13.8
16.8
27.0
35.3
39.0
30
40
40
27
34
38
69
76
79
28.0
36.3
40.0
30
40
45
28
36
39
70
77
80
23.0
27.7
52.7
60
50
117
53.7
60
52
118
25.5
30.7
56.4
60
54
123
57.4
60
55
124
---
---
13.0
20
13
69
14.0
20
14
70
6.0
7.2
22.0
25
21
76
23.0
25
22
77
11.5
14.0
23.0
25.5
---
6.0
11.5
14.0
13.8
16.8
27.7
30.7
---
7.2
13.8
16.8
30.3
34.0
47.7
51.4
13.8
22.8
31.1
34.8
35
35
50
50
20
25
35
35
29
32
45
48
14
22
30
33
83
86
124
130
82
89
96
99
31.3
35.0
48.7
52.4
14.8
23.8
32.1
35.8
35
40
50
60
20
25
35
40
30
33
46
49
15
23
31
34
84
87
125
131
83
90
97
100
MED
HIGH
23.0
27.7
48.5
50
46
137
49.5
50
47
138
25.5
30.7
52.2
60
49
143
53.2
60
50
144
STD
MED
HIGH
---
---
---
---
---
---
11.9
9.9
15
15
15
12
10
11
45
52
63
13.8
11.8
12.6
20
15
15
14
12
13
47
54
65
10.7
NOTE: See page 44 for table legend and notes.
40
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10 — Unit Wire/MOCP Sizing Data (cont)
ELECTRIC HEATER
w/ PWRD C.O.
NO P.E.
w/ P.E. (pwrd fr/unit)
IFM
TYPE
Nom
(kW)
DISC. SIZE
DISC. SIZE
FLA
MCA
MOCP
MCA
MOCP
FLA
LRA
FLA
LRA
---
4.9/6.5
6.5/8.7
9.8/13.0
13.1/17.4
15.821.0
---
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
---
---
46.5
75.8/80.3
85.7/91.8
60
80/90
100/100
46
73/77
82/88
150
174/177
181/186
48.4
77.7/82.2
87.7/93.7
60
80/100
100/100
48
75/79
84/90
152
176/179
183/188
23.5/27.1
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
---
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
---
STD
STD
105.1/114.2 110/125 100/108 244/258 107.0/116.1 110/125 102/110 246/260
125.0/137.1 125/150 118/129 276/295 126.9/139.0 150/150 120/131 278/297
141.2/155.8 150/175 133/147 302/325 143.1/157.7 150/175 135/149 304/327
33.2
45
34
49/52
59/63
72/78
84/92
97/107
31
126
35.1
50
36
52/54
61/65
74/80
86/94
99/109
33
128
142/144
150/153
161/167
216/229
238/256
151
50.2/52.7
60.6/64.8
75.0/81.3
88.0/96.3
60/60
70/70
80/90
90/100
140/142
148/151
159/165
214/227
52.1/54.6
62.5/66.7
76.9/83.2
89.9/98.2
60/60
70/70
80/90
90/100
102.2/113.0 110/125
236/254 104.1/114.9 110/125
149
31.0
45
32.9
45
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
---
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
---
6.0
11.5
14.0
23.0
25.5
---
6.0
11.5
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
---
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
---
7.2
13.8
16.8
27.7
30.7
---
7.2
13.8
48.0/50.5
58.4/62.6
72.8/79.1
85.8/94.1
60/60
60/70
80/80
90/100
47/49
56/60
70/75
82/89
95/105
34
49/52
59/63
72/78
84/92
97/107
21
29
37
40
53
56
15
24
31
163/165
171/174
182/188
237/250
49.9/52.4
60.3/64.5
74.7/81.0
87.7/96.0
60/60
70/70
80/90
90/100
49/51
59/62
72/78
84/91
97/107
36
52/54
61/65
74/80
86/94
99/109
22
30
38
42
54
58
16
25
32
165/167
173/176
184/190
239/252
261/279
177
191/193
199/202
210/216
265/278
287/305
65
72
78
82
120
126
72
79
86
MED
HIGH
STD
100.0/110.8 100/125
259/277 101.9/112.7 110/125
175
189/191
197/200
208/214
263/276
285/303 104.2/115.0 110/125
64
71
78
81
119
125
71
78
85
33.3
45
35.2
50
50.3/52.8
60.7/64.9
75.1/81.4
88.1/96.4
60/60
70/70
80/90
90/100
52.2/54.7
62.6/66.8
77.0/83.3
90.0/98.3
60/60
70/70
80/90
90/100
102.3/113.1 110/125
20.2
29.2
37.5
41.2
54.9
58.6
15.2
24.2
32.5
36.2
49.9
53.6
16.0
25.0
33.3
37.0
50.7
54.4
25
30
40
45
60
60
20
30
35
40
50
60
20
30
35
40
60
60
21.2
30.2
38.5
42.2
55.9
59.6
16.2
25.2
33.5
37.2
50.9
54.6
17.0
26.0
34.3
38.0
51.7
55.4
25
35
40
45
60
60
20
30
35
40
60
60
20
30
35
40
60
60
MED
HIGH
14.0
23.0
25.5
---
6.0
11.5
14.0
23.0
16.8
27.7
30.7
---
7.2
13.8
16.8
27.7
35
47
51
16
24
32
36
48
88
36
48
52
17
26
33
37
49
89
127
133
85
92
99
102
140
126
132
84
91
98
101
139
145
25.5
30.7
52
53
146
STD
MED
HIGH
---
---
---
---
---
---
13.6
11.6
12.4
15
15
15
14
12
13
47
54
65
15.5
13.5
14.3
20
15
20
16
14
15
49
56
67
NOTE: See page 44 for table legend and notes.
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10 — Unit Wire/MOCP Sizing Data (cont)
ELECTRIC HEATER
NO C.O. or UNPWRD C.O.
NO P.E.
w/ P.E. (pwrd fr/unit)
IFM
TYPE
Nom
(kW)
DISC. SIZE
DISC. SIZE
FLA
MCA
MOCP
MCA
MOCP
FLA
LRA
FLA
LRA
---
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
---
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
---
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
---
6.0
11.5
14.0
23.0
25.5
---
6.0
11.5
---
30.5
45
60/60
60/70
80/80
90/100
100/125
50
60/60
70/70
80/90
90/100
30
45/47
55/59
68/74
80/88
93/103
32
48/50
57/61
71/76
83/90
96/106
32
48/50
57/61
71/76
83/90
96/106
15
23
31
34
47
50
16
24
32
146
32.4
50
32
47/50
57/61
70/76
82/90
95/105
34
50/52
60/63
73/79
85/92
98/108
34
50/52
60/63
73/79
85/92
98/108
16
24
32
36
48
52
17
25
33
148
162/164
170/173
181/187
236/249
258/276
185
199/201
207/210
218/224
273/286
295/313
185
199/201
207/210
218/224
273/286
295/313
74
81
88
91
129
135
93
100
107
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
---
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
---
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
---
7.2
13.8
16.8
27.7
30.7
---
7.2
13.8
47.5/50.0
57.8/62.1
72.2/78.6
85.2/93.6
99.5/110.2
32.8
49.8/52.3
60.1/64.4
74.5/80.9
87.5/95.9
160/162
168/171
179/185
234/247
49.4/51.9
59.7/64.0
74.1/80.5
87.1/95.5
60/60
60/70
80/90
90/100
STD
MED
HIGH
STD
256/274 101.4/112.1 110/125
183
197/199
205/208
216/222
271/284
293/311 103.7/114.4 110/125
183
197/199
205/208
216/222
271/284
293/311 103.7/114.4 110/125
73
80
87
90
128
134
92
34.7
50
51.5/54.2
62.0/66.3
76.4/82.8
89.4/97.8
60/60
70/70
80/90
90/100
101.8/112.5 110/125
32.8
50
34.7
50
49.8/52.3
60.1/64.4
74.5/80.9
87.5/95.9
60/60
70/70
80/90
90/100
51.7/54.2
62.0/66.3
76.4/82.8
89.4/97.8
60/60
70/70
80/80
90/100
101.8/112.5 110/125
15.5
24.4
32.8
36.5
50.2
53.9
16.3
25.3
33.6
37.3
51.0
54.7
16.3
25.3
33.6
37.3
51.0
54.7
25
30
35
40
60
60
25
30
35
40
60
60
25
30
35
40
60
60
16.5
25.5
33.8
37.5
51.2
54.9
17.3
26.3
34.6
38.3
52.0
55.7
17.3
26.3
34.6
38.3
52.0
55.7
25
30
40
40
60
60
25
30
40
40
60
60
25
30
40
40
60
60
99
106
109
147
153
92
MED
HIGH
14.0
23.0
25.5
---
6.0
11.5
14.0
23.0
16.8
27.7
30.7
---
7.2
13.8
16.8
27.7
35
48
51
16
24
32
35
48
36
49
52
17
25
33
36
49
110
148
154
93
100
107
110
148
99
106
109
147
153
25.5
30.7
51
52
154
STD
MED
HIGH
---
---
---
---
---
---
12.3
12.7
12.7
15
20
20
12
12
12
59
74
74
14.2
14.6
14.6
20
20
20
14
15
15
61
76
76
NOTE: See page 44 for table legend and notes.
42
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10 — Unit Wire/MOCP Sizing Data (cont)
ELECTRIC HEATER
w/ PWRD C.O.
NO P.E.
w/ P.E. (pwrd fr/unit)
IFM
TYPE
Nom
(kW)
DISC. SIZE
DISC. SIZE
FLA
MCA
MOCP
MCA
MOCP
FLA
LRA
FLA
LRA
---
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
---
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
---
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
---
6.0
11.5
14.0
23.0
25.5
---
6.0
11.5
---
35.3
50
35
151
37.2
50
37
153
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
---
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
---
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
---
7.2
13.8
16.8
27.7
30.7
---
7.2
13.8
52.3/54.8
62.6/66.9
77.0/83.4
90.0/98.4
60/60
70/70
80/90
90/100
51/53
60/64
73/79
85/93
99/108
38
53/56
63/67
76/82
88/96
165/167
173/176
184/190
239/252
54.2/56.7
64.5/68.8
78.9/85.3
91.9/100.3
60/60
70/80
80/90
100/110
53/55
62/66
76/82
88/95
167/169
175/178
186/192
241/254
STD
MED
HIGH
STD
104.3.115.0 110/125
261/279 106.2/116.9 110/125 101/111 263/281
188
202/204
210/213
221/227
276/289
37.6
50
39.5
50
40
190
54.6/57.1
64.9/69.2
79.3/85.7
92.3/100.7
60/60
70/80
80/90
100/110
56.5/59.0
66.8/71.1
81.2/87.6
94.2/102.6
60/60
80/80
90/90
100/110
56/58
65/69
78/84
90/98
204/206
212/215
223/229
278/291
106.6/117.3 110/125 101/111 298/316 108.5/119.2 110/125 103/113 300/318
37.6
50
38
188
39.5
50
40
190
54.6/57.1
64.9/69.2
79.3/85.7
92.3/100.7
60/60
70/80
80/90
100/110
53/56
63/67
76/82
88/96
202/204
210/213
221/227
276/289
56.5/59.0
66.8/71.1
81.2/87.6
94.2/102.6
60/60
80/80
90/90
100/110
56/58
65/69
78/84
90/98
204/206
212/215
223/229
278/291
106.6/117.3 110/125 101/111 298/316 108.5/119.2 110/125 103/113 300/318
17.7
26.7
35.0
38.7
52.4
56.1
18.5
27.5
35.8
39.5
53.2
56.9
18.5
27.5
35.8
39.5
53.2
56.9
25
30
40
40
60
60
25
30
40
45
60
60
25
30
40
45
60
60
18
26
33
37
49
53
19
27
34
38
50
54
19
27
34
38
50
54
75
82
89
18.7
27.7
36.0
39.7
53.4
57.1
19.5
28.5
36.8
40.5
54.2
57.9
19.5
28.5
36.8
40.5
54.2
57.9
25
30
40
45
60
60
25
30
40
45
60
60
25
30
40
45
60
60
19
27
35
38
51
54
20
28
36
39
52
55
20
28
36
39
52
55
76
83
90
92
93
130
136
94
101
108
111
149
155
94
101
108
111
149
155
131
137
95
102
109
112
150
156
95
102
109
112
150
156
MED
HIGH
14.0
23.0
25.5
---
6.0
11.5
14.0
23.0
16.8
27.7
30.7
---
7.2
13.8
16.8
27.7
25.5
30.7
STD
MED
HIGH
---
---
---
---
---
---
14.0
14.4
14.4
20
20
20
14
14
14
61
76
76
15.9
16.3
16.3
20
20
20
16
17
17
63
78
78
NOTE: See page 44 for table legend and notes.
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Legend and Notes for Table 10
LEGEND:
Example: Supply voltage is 230-3-60
CO
--- Convenient outlet
AB = 224 v
BC = 231 v
AC = 226 v
DISC
FLA
--- Disconnect
--- Full load amps
--- Indoor fan motor
IFM
LRA
--- Locked rotor amps
--- Minimum circuit amps
--- Maximum over current protection
--- Po w e r e x h a u st
MCA
(224 + 231 + 226)
681
3
Average Voltage =
3
=
MOCP
P E
=
227
UNPWR CO
NOTES:
--- Unpowered convenient outlet
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
1. In compliance with NEC requirements for multimotor and
combination load equipment (refer to NEC Articles 430 and
440), the overcurrent protective device for the unit shall be
fuse or HACR breaker. Canadian units may be fuse or circuit
breaker.
Determine percent of voltage imbalance.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to de-
termine the percentage of voltage imbalance.
4
% Voltage Imbalance
= 100 x
= 1.76%
227
max voltage deviation from average voltage
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
% Voltage Imbalance = 100 x
average voltage
Unit Without Economizer or
2 Position Damper
Economizer
2 Position Damper
C08631
Fig. 65 - EconoMi$ert IV Wiring
EconoMi$er IV Occupancy Switch —
Step 11 — Adjust Factory--Installed Options
Smoke Detectors —
Refer to Fig. 65 for general EconoMi$er IV wiring.
External occupancy control is managed through a
connection on the Central Terminal Board.
Smoke detector(s) will be connected at the Central
Terminal Board (CTB), at terminals marked “Smoke
Shutdown”. Remove jumper JMP 3 when ready to
energize unit.
If external occupancy control is desired, connect a time
clock or remotely controlled switch (closed for Occupied,
open for Unoccupied sequence) at terminals marked
OCCUPANCY on CTB. Remove or cut jumper JMP 2 to
complete the installation.
44
Download from Www.Somanuals.com. All Manuals Search And Download.
Pre-Start and Start-Up
Step 12 — Install Accessories
Available accessories include:
Roof Curb
Thru-base connection kit (must be installed before unit
is set on curb)
This completes the mechanical installation of the unit.
Refer to the unit’s Service Manual for detailed Pre-Start
and Start-up instructions.
Manual outside air damper
Two-Position motorized outside air damper
EconoMi$er IV (with control and integrated barometric
relief)
EconoMi$er2 (without control/for external signal and
integrated barometric relief)
Power Exhaust
Differential dry-bulb sensor (EconoMi$er IV)
Outdoor enthalpy sensor
Differential enthalpy sensor
Time Guard II compressor anti-cycle control
Outdoor coil hail guard
Outdoor coil protector grille
Head pressure control
Programmable setback thermostat
Electrical/Mechanical thermostat and subbase
Thermidistatt device
Humidistat
Electric Heaters
Single Point kits
Thermostat / Sensors
CO2 sensor
DDC interface (PremierLink)
Louvered hail guard
Phase monitor control
Refer to separate installation instructions for information
on installing these accessories.
45
Download from Www.Somanuals.com. All Manuals Search And Download.
46
Download from Www.Somanuals.com. All Manuals Search And Download.
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Catalog No: 50TCQ---01SI
Copyright 2009 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231
Printed in U.S.A.
Edition Date: 02/10/09
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Replaces: NEW
48
Download from Www.Somanuals.com. All Manuals Search And Download.
|