Carrier Furnace 58PHA PHX User Manual

58PHA/PHX Performance Boost 80  
4 --- Way Multipoise  
Induced---Combustion Gas Furnace  
Input Capacities: 45,000 thru 135,000 Btuh  
Installation, Start---up, Operating and  
Service and Maintenance  
Instructions Series 100/A  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . 2  
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
CODES AND STANDARDS . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
General Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Combustion and Ventilation Air . . . . . . . . . . . . . . . . . . . . . 5  
Duct Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Acoustical Lining and Fibrous Glass Duct . . . . . . . . . . . . . 5  
Gas Piping and Gas Pipe Pressure Testing . . . . . . . . . . . . . 5  
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40  
SERVICE AND MAINTENANCE PROCEDURES . . . . . . . 43  
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43  
Care and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 46  
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 49  
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51  
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51  
ama  
ELECTROSTATIC DISCHARGE PRECAUTIONS  
PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
ISO 9001:2000  
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
Upflow Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
Downflow Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
Horizontal Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
Filter Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
Air Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
115--V Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
START--UP, ADJUSTMENT, AND SAFETY CHECK . . . . . 36  
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
Start--up Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
Check Safety Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
CERTIFIED  
REGISTERED  
NOTE: Read the entire instruction manual before starting the  
installation.  
Portions of the text and tables are reprinted from NFPA 54/ANSI  
Z223.1--2006E, with permission of National Fire Protection  
Association, Quincy, MA 02269 and American Gas Association,  
Washington DC 20001. This reprinted material is not the  
complete and official position of the NFPA or ANSI on the  
referenced subject, which is represented only by the standard in  
its entirety.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
instructions thoroughly and follow all warnings or cautions  
include in literature and attached to the unit. Consult local  
building codes, the current editions of the National Fuel Gas  
Code (NFGC) NFPA 54/ANSI Z223.1 and the National  
Electrical Code (NEC) NFPA 70.  
outside the space containing the furnace. See “Air Ducts”  
section.  
8. A gas--fired furnace for installation in a residential garage  
must be installed as specified in the warning box in the  
“Location” section.  
In Canada, refer to the current editions of the National Standards  
of Canada CAN/CSA--B149.1 and .2 Natural Gas and Propane  
Installation Codes, and Canadian Electrical Code CSA C22.1  
9. The furnace may be used for construction heat provided  
that the furnace installation and operation complies with  
the first CAUTION in the LOCATION section of these  
instructions.  
Recognize safety information. This is the safety--alert symbol  
.
10. These Multipoise Gas--Fired Furnaces are CSA (formerly  
A.G.A. and C.G.A). design--certified for use with natural  
and propane gases (see furnace rating plate) and for  
installation in alcoves, attics, basements, closets, utility  
rooms, crawlspaces, and garages. The furnace is  
factory--shipped for use with natural gas. A CSA listed  
accessory gas conversion kit is required to convert furnace  
for use with propane gas.  
When you see this symbol on the unit and in instructions or  
manuals, be alert to the potential for personal injury.  
Understand the signal words DANGER, WARNING, and  
CAUTION. These words are used with the safety--alert symbol.  
DANGER identifies the most serious hazards which will result in  
severe personal injury or death. WARNING signifies hazards  
which could result in personal injury or death. CAUTION is  
used to identify unsafe practices which may result in minor  
personal injury or product and property damage. NOTE is used  
to highlight suggestions which will result in enhanced  
installation, reliability, or operation.  
11. See Fig.  
2
for required clearances to combustible  
construction.  
12. Maintain a 1--in. (25 mm) clearance from combustible  
materials to supply air ductwork for a distance of 36  
inches (914 mm) horizontally from the furnace. See NFPA  
90B or local code for further requirements.  
!
CAUTION  
13. These furnaces SHALL NOT be installed directly on  
carpeting, tile, or any other combustible material other  
than wood flooring. In downflow installations, factory  
accessory floor base MUST be used when installed on  
combustible materials and wood flooring. Special base is  
not required when this furnace is installed on  
manufacturer’s Coil Assembly Part No. CAR, CAP,  
CNRV, and CNPV, or when Coil Box Part No. KCAKC is  
used. See Fig. 2 for clearance to combustible construction  
information.  
CUT HAZARD  
Failure to follow this caution may result in personal injury.  
Sheet metal parts may have sharp edges or burrs. Use care  
and wear appropriate protective clothing, safety glasses and  
gloves when handling parts and servicing furnaces.  
1. Use only with type of gas approved for this furnace. Refer  
to the furnace rating plate.  
2. Install this furnace only in a location and position as  
specified in the “Location” section of these instructions.  
INTRODUCTION  
3. Provide adequate combustion and ventilation air to the  
furnace space as specified in “Air for Combustion and  
Ventilation” section.  
Series 100/A 4--way multipoise Category I fan--assisted furnace is  
CSA design--certified. A Category I fan--assisted furnace is an  
appliance equipped with an integral mechanical means to either  
draw or force products of combustion through the combustion  
chamber and/or heat exchanger. The furnace is factory--shipped  
for use with natural gas.  
This furnace is not approved for installation in mobile homes,  
recreational vehicles, or outdoors. This furnace is designed for  
minimum continuous return--air temperature of 60_F (16_C)db  
or intermittent operation down to 55_F (13_C) db such as when  
used with a night setback thermostat. Return--air temperature  
must not exceed 85_F (29_C) db. Failure to follow these  
return--air temperature limits may affect reliability of heat  
exchangers, motors, and controls. (See Fig. 3).  
4. Combustion products must be discharged outdoors.  
Connect this furnace to an approved vent system only, as  
specified inthe “Venting” section of these instructions.  
5. Never test for gas leaks with an open flame. Use a  
commercially available soap solution made specifically for  
the detection of leaks to check all connections, as specified  
in the “Gas Piping” section.  
6. Always install furnace to operate within the furnace’s  
intended temperature--rise range with a duct system which  
has an external static pressure within the allowable range,  
as specified in the “Start--Up, Adjustments, and Safety  
Check” section. See furnace rating plate.  
For accessory installation details, refer to the applicable  
instruction literature.  
NOTE: Remove all shipping brackets and materials before  
7. When a furnace is installed so that supply ducts carry air  
circulated by the furnace to areas outside the space  
containing the furnace, the return air shall also be handled  
by duct(s) sealed to the furnace casing and terminating  
operating the furnace.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
A08471  
Fig. 2 -- Clearances to Combustibles  
Safety  
CODES AND STANDARDS  
S
USA: National Fuel Gas Code (NFGC) NFPA  
Follow all national and local codes and standards in addition to  
these instructions. The installation must comply with regulations  
of the serving gas supplier, local building, heating, plumbing, and  
other codes. In absence of local codes, the installation must  
comply with the national codes listed below and all authorities  
having jurisdiction.  
54--2006/ANSI Z223.1--2006 and the Installation Stan-  
dards, Warm Air Heating and Air Conditioning Sys-  
tems ANSI/NFPA 90B  
S
CANADA: CSA B149.1--05 National Standard of  
Canada Natural Gas and Propane Installation Codes  
(CAN/CSA--B149.1--05)  
In the United States and Canada, follow all codes and standards  
for the following:  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
S
CANADA: CAN/CSA--B149.1--05 Parts 4, 5, and 6  
Appendices A, B, E, and H.  
Max 85ºF/ 29ºC  
Min 60ºF / 16ºC  
Electrical Connections  
S
US: National Electrical Code (NEC) ANSI/NFPA  
70--2008.  
S
Venting  
S
CANADA: Canadian Electrical Code CSA C22.1.  
US: NFGC NFPA 54 / ANSI Z223.1--2006; Chapters  
12 and 13.  
S
CANADA: CAN/CSA--B149.1--05 Part 8 and  
Appendix C.  
ELECTROSTATIC DISCHARGE (ESD)  
PRECAUTIONS PROCEDURE  
A02055  
Fig. 3 -- Return Air Temperature  
General Installation  
!
CAUTION  
FURNACE RELIABILITY HAZARD  
S
US: Current edition of the NFGC and the NFPA 90B.  
For copies, contact the National Fire Protection  
Association Inc., Batterymarch Park, Quincy, MA  
contact the American Gas Association, 400 N. Capitol  
Street, N.W., Washington, DC 20001 (www.AGA.org).  
Improper installation or service of furnace may cause  
premature furnace component failure.  
Electrostatic discharge can affect electronic components.  
Follow the Electrostatic Discharge Precautions Procedure  
listed below during furnace installation and servicing to  
protect the furnace electronic control. Precautions will  
prevent electrostatic discharges from personnel and hand  
tools which are held during the procedure. These  
precautions will help to avoid exposing the control to  
electrostatic discharge by putting the furnace, the control,  
and the person at the same electrostatic potential.  
S
CANADA: CAN/CSA--B149.1--05. For a copy,  
contact Standard Sales, CSA International, 178  
Rexdale Boulevard, Etobicoke (Toronto), Ontario,  
M9W 1R3 Canada.  
Combustion and Ventilation Air  
S
US: NGFC NFPA54/ANSI Z223.1--2006 Section 9.3,  
Air for Combustion and Ventilation.  
1. Disconnect all power to the furnace. Multiple disconnects  
maybe required. DO NOT TOUCH THE CONTROL OR  
ANY WIRE CONNECTED TO THE CONTROL PRIOR  
S
CANADA: Part 8 of CAN/CSA--B149.1--05, Venting  
Systems and Air Supply for Appliances.  
TO  
DISCHARGING  
YOUR  
BODY’S  
Duct Systems  
ELECTROSTATIC CHARGE TO GROUND.  
2. Firmly touch the clean, unpainted, metal surface of the  
furnace chassis which is close to the control. Firmly touch  
the clean, unpainted, metal surface of the furnace chassis  
which is close to the control. Tools held in a person’s hand  
during grounding will be satisfactorily discharged.  
S
US and CANADA: Air Conditioning Contractors  
Association (ACCA) Manual D, Sheet Metal and Air  
Conditioning Contractors National Association  
(SMACNA), or American Society of Heating,  
Refrigeration, and Air Conditioning Engineers  
(ASHRAE) 2005 Fundamentals Handbook Chapter 35  
or 2004 HVAC Systems and Equipment Handbook  
Chapters 9 and 16.  
3. After touching the chassis, you may proceed to service the  
control or connecting wires as long as you do nothing to  
recharge your body with static electricity (for example;  
DO NOT move or shuffle your feet, do not touch  
ungrounded objects, etc.).  
Acoustical Lining and Fibrous Glass Duct  
S
US and CANADA: current edition of SMACNA and  
NFPA 90B as tested by UL Standard 181 for Class I  
Rigid Air Ducts  
4. If you touch ungrounded objects (and recharge your body  
with static electricity), firmly touch a clean, unpainted  
metal surface of the furnace again before touching control  
or wires.  
Gas Piping and Gas Pipe Pressure Testing  
S
US: NFGC NFPA54/ANSI Z223.1--2006; chapters 5,  
6, 7, and 8 and National Plumbing Codes.  
5. Use this procedure for installed and uninstalled  
(ungrounded) furnaces.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
THE BLOWER IS  
LOCATED BELOW THE  
BURNER SECTION, AND  
CONDITIONED AIR IS  
DISCHARGED UPWARD.  
THE BLOWER IS LOCATED  
TO THE RIGHT OF THE  
BURNER SECTION, AND  
AIR CONDITIONED AIR IS  
DISCHARGED TO THE LEFT.  
THE BLOWER IS  
THE BLOWER IS  
LOCATED ABOVE THE  
BURNER SECTION, AND  
CONDITIONED AIR IS  
DISCHARGED DOWNWARD  
LOCATED TO THE LEFT  
OF THE BURNER SECTION,  
AND CONDITIONED AIR IS  
DISCHARGED TO THE RIGHT.  
A02097  
Fig. 4 -- Multipoise Orientations  
6. Before removing a new control from its container,  
discharge your body’s electrostatic charge to ground to  
protect the control from damage. If the control is to be  
installed in a furnace, follow items 1 through 4 before  
bringing the control or yourself in contact with the  
furnace. Put all used and new controls into containers  
before touching ungrounded objects.  
!
WARNING  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow this warning could result in personal  
injury or death, and unit component damage.  
Corrosive or contaminated air may cause failure of parts  
containing flue gas, which could leak into the living space.  
Air for combustion must not be contaminated by halogen  
compounds, which include fluoride, chloride, bromide, and  
iodide. These elements can corrode heat exchangers and  
shorten furnace life. Air contaminants are found in aerosol  
sprays, detergents, bleaches, cleaning solvents, salts, air  
fresheners, and other household products. Do not install  
furnace in a corrosive or contaminated atmosphere. Make  
sure all combustion and circulating air requirements are met,  
in addition to all local codes and ordinances.  
7. An ESD service kit (available from commercial sources)  
may also be used to prevent ESD damage.  
LOCATION  
GENERAL  
This multipoise furnace is shipped in packaged configuration.  
Some assembly and modifications are required when used in any  
of the four applications shown in Fig. 4.  
This furnace must:  
S
be installed so the electrical components are protected  
from water.  
If air is exposed to the following substances, it should not be used  
for combustion air, and outdoor air may be required for  
combustion:  
S
not be installed directly on any combustible material  
other than wood flooring (refer to SAFETY  
CONSIDERATIONS).  
S
S
S
S
S
S
S
S
S
S
S
S
Permanent wave solutions  
S
S
be located as close to the chimney or vent and attached  
to an airdistribution system. Refer to Air Ducts section.  
Chlorinated waxes and cleaners  
Chlorine based swimming pool chemicals  
Wate softening chemicals  
be provided ample space for servicing and cleaning.  
Always comply with minimum fire protection  
clearances shown on the furnace clearance to  
combustible label.  
De--icing salts or chemicals  
Carbon tetrachloride  
The following types of furnace installations may require  
OUTDOOR AIR for combustion due to chemical exposures:  
Haloge type refrigerants  
S
S
S
S
S
Commercial buildings  
Buildings with indoor pools  
Laundry rooms  
Cleaning solvents (such as perchloroethylene)  
Printing inks, paint removers, varnishes, etc.  
Hydrochloric acid  
Hobby or craft rooms, and  
Chemical storage areas  
Cements and glues  
Antistatic fabric softeners for clothes dryers  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
S
Masonry acid washing materials  
!
CAUTION  
All fuel--burning equipment must be supplied with air for fuel  
combustion. Sufficient air must be provided to avoid negative  
pressure in the equipment room or space. A positive seal must be  
made between the furnace cabinet and the return--air duct to  
prevent pulling air from the burner area and from draft safeguard  
opening.  
PERSONAL INJURY AND/OR PROPERTY  
DAMAGE HAZARD  
Improper use or installation of this furnace may cause  
premature furnace component failure.  
This gas furnace may be used for heating buildings under  
construction provided that:  
--The furnace is permanently installed with all electrical  
wiring, piping, venting and ducting installed according to  
these installation instructions. A return air duct is provided,  
sealed to the furnace casing, and terminated outside the  
space containing the furnace. This prevents a negative  
pressure condition as created by the circulating air blower,  
causing  
a
flame rollout and/or drawing combustion  
products into the structure.  
--The furnace is controlled by a thermostat. It may not be  
“hot wired” to provide heat continuously to the structure  
without thermostatic control.  
--Clean outside air is provided for combustion. This is to  
minimize the corrosive effects of adhesives, sealers and  
other construction materials. It also prevents the  
entrainment of drywall dust into combustion air, which can  
cause fouling and plugging of furnace components.  
--The temperature of the return air to the furnace is  
maintained between 55_F (13_C) and 80_F (27_C), with  
no evening setback or shutdown. The use of the furnace  
while the structure is under construction is deemed to be  
intermittent operation per our installation instructions.  
--The air temperature rise is within the rated rise range on  
the furnace rating plate, and the gas input rate has been set  
to the nameplate value.  
--The filters used to clean the circulating air during the  
construction process must be either changed or thoroughly  
cleaned prior to occupancy.  
--The furnace, ductwork and filters are cleaned as necessary  
to remove drywall dust and construction debris from all  
HVAC system components after construction is completed.  
--Verify proper furnace operating conditions including  
ignition, gas input rate, air temperature rise, and venting  
according to these installation instructions.  
18-IN. (457.2 mm)  
MINIMUM TO BURNERS  
A93044  
Fig. 5 -- Installation in a Garage  
!
WARNING  
ELECTRICAL OPERATION HAZARD  
Failure to follow this warning could result in personal  
injury, death, and/or property damage.  
When the furnace is installed in a residential garage, the  
burners and ignition sources must be located at least 18  
inches above the floor. The furnace must be located or  
protected to avoid damage by vehicles. When the furnace is  
installed in a public garage, airplane hangar, or other  
building having a hazardous atmosphere, the furnace must  
be installed in accordance with the NFGC or  
CAN/CSA--B149.1--05. (See Fig. 5).  
Table 2 – Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors  
TWO OPENINGS OR VERTICAL  
DUCTS  
TWO HORIZONTAL DUCTS  
(1 SQ. IN./2,000 BTUH)  
(1,100 SQ. MM/KW)  
SINGLE DUCT OR OPENING  
(1 SQ. IN./3,000 BTUH)  
(734 SQ. MM/KW)  
FUR-  
NACE  
INPUT  
(BTUH)  
(1 SQ. IN./4,000 BTUH)  
(550 SQ. MM/KW)  
Free Area of Opening  
Round Duct  
Diameter  
(in./mm)  
Free Area of Open-  
Round Duct  
Diameter  
(in. / mm)  
Free Area of  
Round Duct  
Diameter  
(In./mm)  
and Duct  
ing and Duct  
Opening and Duct  
(sq. In. / sq. mm)  
(sq. in. / sq. mm)  
(sq. In. / sq. mm)  
44,000  
66,000  
88,000  
110,000  
132,000  
22 (14193)  
33 (21290)  
44 (28387)  
55 (35484)  
66 (42581)  
6 (152)  
7 (178)  
8 (203)  
9 (229)  
10 (254)  
14.7 (9484)  
22 (14193)  
29.3 (18903)  
36.7 (23677)  
44 (28387)  
5 (127)  
6 (152)  
7 (178)  
7 (178)  
8 (203)  
11 (7097)  
16.5 (10645)  
22 (14193)  
27.5 (17742)  
33 (21290)  
4 (102)  
5 (127)  
6 (152)  
6 (152)  
7 (178)  
EXAMPLES: Determining Free Area  
TOTAL INPUT  
FURNACE  
WATER HEATER  
110,000  
66,000  
88,000  
+
+
+
30,000  
40,000  
30,000  
=
=
=
(140,000 divided by 4,000)  
(106,000 divided by 3,000)  
(118,000 divided by 2,000)  
=
=
=
35.0 Sq. In. for each two Vertical Ducts or Openings  
35.3 Sq. In. for a Single Duct or Opening  
59.0 Sq. In. for each of two Horizontal Ducts  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 3 – Minimum Space volumes for 100% combustion, Ventilation, and Dilution from Indoors  
OTHER THAN FAN---ASSISTED TOTAL  
(1,000’S BTUH GAS INPUT RATE  
FAN---ASSISTED TOTAL  
(1,000’S BTUH GAS INPUT RATE)  
ACH*  
30  
40  
50  
44  
66  
88  
110  
132  
3
Space Volume (ft. )  
0.60  
0.50  
0.40  
0.30  
0.20  
0.10  
0.00  
1,050  
1,260  
1,575  
2,100  
3,150  
6,300  
NP  
1,400  
1,680  
2,100  
2,800  
4,200  
8,400  
NP  
1,750  
2,100  
2,625  
3,500  
5,250  
10,500  
NP  
1,100  
1,320  
1,650  
2,200  
3,300  
6,600  
NP  
1,650  
1,980  
2,475  
3,300  
4,950  
9,900  
NP  
2,200  
2,640  
3,300  
4,400  
6,600  
13,200  
NP  
2,750  
3,300  
4,125  
5,500  
8,250  
16,500  
NP  
3,300  
3,960  
4,950  
6,600  
9,900  
19,800  
NP  
*Air Changes/Hour  
AIR FOR COMBUSTION AND  
VENTILATION  
Provisions for adequate combustion, ventilation, and dilution air  
must be provided in accordance with:  
!
WARNING  
FIRE HAZARD  
Failure to follow this warning could result in personal  
injury, death and/or property damage.  
S
U.S. installations: Section 9.3 of the NFGC  
NFPA54/ANSI Z223.1--2006, Air for Combustion and  
Ventilation, and applicable provisions of the local  
building codes.  
Do not install the furnace on its back or hang furnace with  
control compartment facing downward. Safety control  
operation will be adversely affected. Never connect  
return--air ducts to the back of the furnace. (See Fig. 6.)  
!
WARNING  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow this warning could result in personal injury  
or death.  
The operation of exhaust fans, kitchen ventilation fans,  
clothes dryers, attic exhaust fans or fireplaces could create a  
NEGATIVE PRESSURE CONDITION at the furnace.  
Make--up air MUST be provided for the ventilation devices,  
in addition to that required by the furnace. Refer to Carbon  
Monoxide Poisoning Hazard warning in venting section of  
these instructions to determine if an adequate amount of  
make--up air is available.  
A02054  
S
Canadian installations: Part 8 of the  
CAN/CSA--B149.1--05, Venting Systems and Air  
Supply for Appliances, and all authorities having  
jurisdiction.  
Fig. 6 -- Prohibit Installation on Back  
The requirements for combustion and ventilation air depend upon  
whether or not the furnace is located in a space having a volume  
of at least 50 cubic feet per 1,000 Btuh input rating for all gas  
appliances installed in the space.  
!
CAUTION  
FURNACE CORROSION HAZARD  
Failure to follow this caution may result in furnace damage.  
S
Spaces having less than 50 cubic feet per 1,000 Btuh  
require the OUTDOOR COMBUSTION AIR  
METHOD.  
Air for combustion must not be contaminated by halogen  
compounds, which include fluoride, chloride, bromide, and  
iodide. These elements can corrode heat exchangers and  
shorten furnace life. Air contaminants are found in aerosol  
sprays, detergents, bleaches, cleaning solvents, salts, air  
fresheners, and other household products.  
S
Spaces having at least 50 cubic feet per 1,000 Btuh  
may use the INDOOR COMBUSTION AIR,  
STANDARD or KNOWN AIR INFILTRATION  
METHOD.  
Outdoor Combustion Air Method  
LOCATION RELATIVE TO COOLING EQUIPMENT  
1. Provide the space with sufficient air for proper  
combustion, ventilation, and dilution of flue gases using  
permanent horizontal or vertical duct(s) or opening(s)  
directly communicating with the outdoors or spaces that  
freely communicate with the outdoors.  
The cooling coil must be installed parallel with, or on the  
downstream side of the unit to avoid condensation in the heat  
exchangers. When installed parallel with the furnace, dampers or  
other flow control must prevent chilled air from entering the  
furnace. If the dampers are manually operated, they must be  
equipped with means to prevent operation of either unit unless  
the damper is in the full--heat or full--cool position.  
2. Fig. 7 illustrates how to provide TWO OUTDOOR  
OPENINGS, one inlet and one outlet combustion and  
ventilation airopening, to the outdoors.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
a. One opening MUST commence within 12--in. (300 mm)  
of the ceiling and the second opening MUST commence  
within 12--in. (300 mm) of the floor.  
!
WARNING  
b. Size openings and ducts per Fig. 7 and Table 2.  
CARBON MONOXIDE POISONING HAZARD  
c. TWO HORIZONTAL DUCTS require 1 square inch of  
free area per 2,000 Btuh (1,100 mm /kW) of combined  
Failure to follow this warning could result in death and/or  
personal injury.  
2
input for all gas appliances in the space per Fig. 7 and  
Table 2.  
Many homes require air to be supplied from outdoors for  
furnace combustion, ventilation, and dilution of flue gases.  
The furnace combustion air supply must be provided in  
accordance with this instruction manual.  
d. TWO OPENINGS OR VERTICAL DUCTS require 1  
2
square inch of free area per 4,000 Btuh (550 mm /kW)  
for combined input of all gas appliances in the space per  
Fig. 7 and Table 2.  
3. ONE OUTDOOR OPENING requires:  
The Standard Method:  
1. The space has no less volume than 50 cubic feet per 1,000  
Btuh of the maximum input ratings for all gas appliances  
installed in the space and  
2. The air infiltration rate is not known to be less than 0.40  
air changes per hour (ACH).  
2
a. 1 square inch of free area per 3,000 Btuh (734 mm /kW)  
for combined input of all gas appliances in the space per  
Table 2 and  
b. Not less than the sum of the areas of all vent connectors  
in the space.  
The Known Air Infiltration Rate Method shall be used, if the  
infiltration rate is known to be:  
The opening shall commence within 12” (300 mm) of the ceiling.  
Appliances in the space shall have clearances of at least 1” (25  
mm) from the sides and back and 6” (150 mm) from the front.  
The opening shall directly communicate with the outdoors or  
shall communicate through a vertical or horizontal duct to the  
outdoors or spaces (crawl or attic) that freely communicate with  
the outdoors.  
1. Less than 0.40 ACH and  
2. Equal to or greater than 0.10 ACH  
Infiltration rates greater than 0.60 ACH shall not be used. The  
minimum required volume of the space varies with the number of  
ACH and shall be determined per Table 3 or Equations 1 and 2.  
Determine the minimum required volume for each appliance in  
the space and add the volumes together to get the total minimum  
required volume for the space.  
Table 3--Minimum Space Volumes were determined by using  
the following equations from the National Fuel Gas Code ANSI  
Z223.1--2006/NFPA 54--2006, 9.3.2.2:  
1 SQ IN.  
PER 4000  
DUCTS  
BTUH*  
TO  
OUTDOORS  
1. For other than fan--assisted appliances, such as a draft  
(305mm)  
12MAX  
D
12″  
(305mm)  
MAX  
1 SQ IN.  
VENT  
hood--equipped water heater:  
PER 2000  
B
THROUGH  
F
BTUH*  
ROOF  
1 SQ IN.  
PER  
21ft3  
I other  
ACH 1000 Btu/hr  
4000  
Volume  
=
BTUH*  
Other  
DUCTS  
TO  
A04002  
OUTDOORS  
2. For fan--assisted appliances such as this furnace:  
1 SQ IN.  
PER  
15ft3  
I fan  
ACH 1000 Btu/hr  
4000  
BTUH*  
Volume  
=
1 SQ IN.  
PER 2000  
BTUH*  
Fan  
E
G
A
12″  
MAX  
(305mm)  
(305mm)  
12MAX  
C
A004003  
12MAX  
(305mm)  
If:  
Iother = combined input of all other than fan--assisted appliances  
in Btuh/hr  
Ifan = combined input of all fan--assisted appliances in Btuh/hr  
ACH = air changes per hour (ACH shall not exceed 0.60.)  
CIRCULATING AIR DUCTS  
DUCT  
TO  
1 SQ IN.  
PER 4000  
OUTDOORS  
BTUH*  
*Minimum dimensions of 3 in. (76 mm).  
NOTE: Use any of the following combinations of openings:  
A&B, C&D, D&E, F&G  
The following requirements apply to the Standard Method and to  
the Known Air Infiltration Rate Method.  
1. Adjoining rooms can be considered part of a space if:  
a. There are no closable doors between rooms.  
A03174  
Fig. 7 -- Air for Combustion, Ventilation, and Dilution from  
Outdoors  
b. Combining spaces on same floor level. Each opening  
2
shall have free area of at least 1 in. /1,000 Btuh (2,000  
2
mm /kW) of the total input rating of all gas appliances  
Indoor Combustion Air -- NFPA & AGA  
Standard and Known--Air--Infiltration Rate Methods  
Indoor air is permitted for combustion, ventilation, and dilution,  
if the Standard or Known--Air--Infiltration Method is used.  
2
2
in the space, but not less than 100 in. (0.06 m ). One  
opening shall commence within 12” (300 mm) of the  
ceiling and the second opening shall commence within  
12” (300 mm) of the floor. The minimum dimension of  
air openings shall be at least 3 in. (80 mm). (See Fig. 8.)  
c. Combining space on different floor levels. The volumes  
of spaces on different floor levels shall be considered as  
communicating spaces if connected by one or more  
permanent openings in doors or floors having free area  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
2
2
of at least 2 in. /1,000 Btuh (4,400 mm /kW) of total  
input rating of all gas appliances.  
2. An attic or crawlspace may be considered a space that  
freely communicates with the outdoors provided there are  
adequate permanent ventilation openings directly to  
2
outdoors having free area of at least 1--in. /4,000 Btuh of  
total input rating forall gas appliances in the space.  
3. In spaces that use the Indoor Combustion Air Method,  
infiltration should be adequate to provide air for  
combustion, permanent ventilation and dilution of flue  
gases. However, in buildings with unusually tight  
construction, additional air MUST be provided using the  
methods described in the Outdoor Combustion Air  
Method section.  
Unusually tight construction is defined as construction with:  
A02098  
a. Walls and ceilings exposed to the outdoors have a  
continuous, sealed vapor barrier. Openings are gasketed  
or sealed and  
Fig. 9 -- Removing Bottom Closure Panel  
b. Outdoor opening size reduction Factor is 1 minus the  
Ratio in a. above.  
CIRCULATING AIR  
VENT THROUGH ROOF  
DUCTS  
c. Minimum size of Outdoor openings shall be the size  
required in Outdoor Combustion Air Method above  
multiplied by reduction Factorin b.above. Theminimum  
dimension of air openings shall be not less than 3 in. (80  
mm).  
12" MAX(305mm)  
INSTALLATION  
UPFLOW INSTALLATION  
Bottom Return Air Inlet  
1 SQ IN.  
PER 1000  
BTUH* IN DOOR  
OR WALL  
UNCONFINED  
INTERIOR  
These furnaces are shipped with bottom closure panel installed in  
bottom return--air opening. Remove and discard this panel when  
bottom return air is used. To remove bottom closure panel,  
perform the following:  
SPACE  
HEATED  
SPACE  
6" MIN (152mm)  
(FRONT)Ü  
1 SQ IN.  
1. Tilt or raise furnace and remove two screws holding  
bottom filler panel. (See Fig. 9.)  
PER 1000  
BTUH* IN DOOR  
OR WALL  
2. Rotate bottom filler panel downward to release holding  
tabs.  
3. Remove bottom closure panel.  
4. Reinstall bottom filler panel and screws.  
Side Return Air Inlet  
12" MAX  
(305mm)  
CIRCULATING AIR DUCTS  
These furnaces are shipped with bottom closure panel installed in  
bottom return--air opening. This panel MUST be in place when  
only side return air is used.  
NOTE: Side return--air openings can be used in UPFLOW and  
most HORIZONTAL configurations. Do not use side return--air  
openings in DOWNFLOW configuration.  
2
*Minimum opening size is 100 in. with minimum dimensions of 3 in. (76  
mm).  
*Minimum of 3 in. (76 mm), when type ---B1 vent is used.  
A03175  
Leveling Legs (If Desired)  
Fig. 8 -- Air for Combustion, Ventilation, and Dilution from  
Indoors  
In upflow position with side return inlet(s), leveling legs may be  
used. (See Fig. 10.) Install field--supplied, 5/16 x 1--1/2 in. (8 x  
38 mm) (max) corrosion--resistant machine bolts, washers and  
nuts.  
b. Doors and openable windows are weatherstripped and  
c. Other openings are caulked or sealed. These include  
joints around window and door frames, between sole  
plates and floors, between wall--ceiling joints, between  
wall panels, at penetrations for plumbing, electrical and  
gas lines, etc.  
NOTE: Bottom closure must be used when leveling legs are  
used. It may be necessary to remove and reinstall bottom closure  
panel to install leveling legs. To remove bottom closure panel, see  
Item 1. in Bottom Return Air Inlet section.  
Combination of Indoor and Outdoor Air  
To install leveling legs:  
1. Indoor openings shall comply with the Indoor  
Combustion Air Method below and,  
1. Position furnace on its back. Locate and drill a hole in  
each bottom corner of furnace. (See Fig. 10.)  
2. Outdoor openings shall be located as required in the  
Outdoor Combustion Air Method menioned previously  
and,  
2. For each leg, install nut on bolt and then install bolt and  
nut in hole. (Install flat washer if desired.)  
3. Install another nut on other side of furnace base. (Install  
flat washer if desired.)  
3. Outdoor openings shall be sized as follows:  
a. Calculate the Ratio of all Indoor Space volume divided  
by required volume for Indoor Combustion Air  
Method below.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5/  
16  
(8mm)  
(8mm)  
5/  
16″  
1 3/4  
(44mm)  
A
PLENUM  
OPENING  
1 3/4  
(44mm)  
B
D
FLOOR  
OPENING  
C
(8mm)  
5/16″  
(8mm)  
5/  
16″  
(44mm)1 3/  
1 3/  
4″  
4
(44mm)  
A89014  
A96283  
Fig. 10 -- Leveling Legs  
Fig. 11 -- Floor and Plenum Opening Dimensions  
4. Adjust outside nut to provide desired height, and tighten  
inside nut to secure arrangement.  
FURNACE  
(OR COIL CASING  
WHEN USED)  
5. Reinstall bottom closure panel if removed.  
DOWNFLOW INSTALLATION  
NOTE: For downflow applications, this furnace is approved for  
use on combustible flooring when any one of the following 3  
accessories are used:  
S
S
Special Base, KGASB  
COMBUSTIBLE  
FLOORING  
Cased Coil Assembly Part No. CNPV, CNRV, CAP, or  
CAR  
S
Coil Box Part No. KCAKC  
DOWNFLOW  
1. Determine application being installed from Table 4.  
2. Construct hole in floor per Table 4 and Fig. 11.  
3. Construct plenum to dimensions specified in Table 4 and  
Fig. 11.  
SUBBASE  
SHEET METAL  
PLENUM  
FLOOR  
OPENING  
4. If downflow subbase, KGASB is used, install as shown in  
Fig. 12. If Coil Assembly Part No. CNPV, CNRV, CAP  
and CNR or Coil Box PartNo. KCAKC is used, install as  
shown in Fig. 13.  
NOTE: It is recommended that the perforated supply--air duct  
flanges be completely folded over or removed from furnace when  
installing the furnace on a factory--supplied cased coil or coil box.  
To remove the supply--air duct flange, use wide duct pliers or  
hand seamers to bend flange back and forth until it breaks off. Be  
careful of sharp edges. (See Fig. 14.)  
A96285  
Fig. 12 -- Furnace, Plenum, and Subbase Installed  
on a Combustible Floor  
Bottom Return Air Inlet  
These furnaces are shipped with bottom closure panel installed in  
bottom return--air opening. Remove and discard this panel when  
bottom return air is used. To remove bottom closure panel,  
perform the following:  
1. Tilt or raise furnace and remove two screws holding  
bottom filler panel. (See Fig. 9.)  
2. Rotate bottom filler panel downward to release holding  
tabs.  
3. Remove bottom closure panel.  
4. Reinstall bottom filler panel and screws  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FURNACE  
APPROVED  
COIL ASSEMBLY  
OR  
COIL BOX  
COMBUSTIBLE  
FLOORING  
SHEET METAL  
PLENUM  
FLOOR  
OPENING  
A08556  
Fig. 13 -- Furnace, Plenum, and Coil Assembly or  
Coil Box Installed on a Combustible Floor  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4 – Opening Dimensions -- In. (mm)  
PLENUM OPENING  
FURNACE  
CASING  
WIDTH  
FLOOR OPENING  
APPLICATION  
A
B
C
D
Upflow Applications on Combustible or Noncombustible Floor-  
ing (KGASB subbase not required)  
12---11/16  
(322)  
21---5/8  
(549)  
19  
(483)  
19  
(483)  
13---5/16  
(338)  
22---1/4  
(565)  
Downflow Applications on Noncombustible Flooring (KGASB  
subbase not required)  
12---9/16  
(319)  
13---3/16  
(335)  
19---5/8  
(498)  
14–3/16  
(360)  
Downflow applications on combustible flooring (KGASB sub-  
base required)  
11---13/16  
(284)  
13---7/16  
(341)  
20---5/8  
(600)  
Downflow Applications on Combustible Flooring with CNPV,  
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box  
(KGASB subbase not required)  
12---5/16  
(313)  
19  
13---5/16  
(338)  
20  
(483)  
(508)  
Upflow Applications on Combustible or Noncombustible Floor-  
ing (KGASB subbase not required)  
16  
(406)  
21---5/8  
(549)  
19  
(483)  
19  
(483)  
16---5/8  
(422)  
22---1/4  
(565)  
Downflow Applications on Noncombustible Flooring (KGASB  
subbase not required)  
15---7/8  
(403)  
16---1/2  
(419)  
19---5/8  
(498)  
17–1/2  
(445)  
Downflow applications on combustible flooring (KGASB sub-  
base required)  
15---1/8  
(384)  
16---3/4  
(425)  
20---5/8  
(600)  
Downflow Applications on Combustible Flooring with CNPV,  
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box  
(KGASB subbase not required)  
15---1/2  
(394)  
19  
16---1/2  
(419)  
20  
(483)  
(508)  
Upflow Applications on Combustible or Noncombustible Floor-  
ing (KGASB subbase not required)  
19---1/2  
(495)  
21---5/8  
(549)  
19  
(483)  
19  
(483)  
20---1/8  
(511)  
20  
(508)  
20---1/4  
(514)  
22---1/4  
(565)  
Downflow Applications on Noncombustible Flooring (KGASB  
subbase not required)  
19---3/8  
(492)  
19---5/8  
(498)  
21  
(533)  
Downflow applications on combustible flooring (KGASB sub-  
base required)  
18---5/8  
(473)  
20---5/8  
(600)  
Downflow Applications on Combustible Flooring with CNPV,  
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box  
(KGASB subbase not required)  
19  
19  
20  
20  
(483)  
(483)  
(508)  
(508)  
Upflow Applications on Combustible or Noncombustible Floor-  
ing (KGASB subbase not required)  
23  
(584)  
21---1/8  
(537)  
19  
(483)  
19  
(483)  
23---5/8  
(600)  
22---1/4  
(565)  
Downflow Applications on Noncombustible Flooring (KGASB  
subbase not required)  
22---7/8  
(581)  
23---1/2  
(597)  
19---5/8  
(498)  
24---1/2  
(622)  
Downflow applications on Combustible flooring (KGASB sub-  
base required)  
22---1/8  
(562)  
23---3/4  
(603)  
20---5/8  
(600)  
Downflow Applications on Combustible Flooring with CNPV,  
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box  
(KGASB subbase not required)  
22---1/2  
(572)  
19  
(483)  
23---1/2  
(597)  
20  
(508)  
HORIZONTAL INSTALLATION  
from the furnace sides, so that the strap attachment screws are not  
in tension (are loaded in shear) for reliable support.  
Platform Furnace Support  
!
WARNING  
Construct working platform at location where all required furnace  
clearances are met. (See Fig. 2 and 17.) For furnaces with 1--in.  
(25 mm) clearance requirement on side, set furnace on  
noncombustible blocks, bricks or angle iron. For crawl space  
installations, if the furnace is not suspended from the floor joists,  
the ground underneath furnace must be level and the furnace set  
on blocks or bricks.  
FIRE, EXPLOSION, AND CARBON MONOXIDE  
POISONING HAZARD  
Failure to follow this warning could result in personal  
injury, death, and/or property damage.  
Do not install the furnace on its back or hang furnace with  
control compartment facing downward. Safety control  
operation will be adversely affected. Never connect  
return--air ducts to the back of the furnace.  
Roll--Out Protection  
Provide a minimum 17--3/4 in. x 22 in. (451 mm x 559 mm)  
piece of sheet metal for flame roll--out protection in front of  
burner area for furnaces closer than 12 inches (305 mm) above  
the combustible deck or suspended furnaces closer than 12 inches  
(305 mm) to joists. The sheet metal MUST extend underneath the  
furnace casing by 1 in. (25 mm) with the door removed.  
The bottom closure panel on furnaces of widths 17--1/2 in. (445  
mm) and larger may be used for flame roll--out protection when  
bottom of furnace is used for return air connection. See Fig. 17  
for proper orientation of roll--out shield.  
The furnace can be installed horizontally in an attic or crawl space  
on either the left--hand (LH) or right--hand (RH) side. The furnace  
can be hung from floor joists, rafters or trusses or installed on a  
non--combustible platform, blocks, bricks or pad.  
Suspended Furnace Support  
The furnace may be supported under each end with threaded rod,  
angle iron or metal plumber’s strap as shown. (See Fig. 15 and  
16.) Secure angle iron to bottom of furnace as shown.  
Heavy--gauge sheet metal straps (plumber’s straps) may be used  
to suspend the furnace from each bottom corner. To prevent  
screws from pulling out, use 2 #8 x 3/4--in. (19 mm) screws into  
the side and 2 #8 x 3/4--in. (19 mm) screws in the bottom of the  
furnace casing for each strap. (See Fig. 15 and 16.) If the screws  
are attached to ONLY the furnace sides and not the bottom, the  
straps must be vertical against the furnace sides and not pull away  
Bottom Return Air Inlet  
These furnaces are shipped with bottom closure panel installed in  
bottom return--air opening. Remove and discard this panel when  
bottom return air is used. To remove bottom closure panel,  
perform the following:  
1. Tilt or raise furnace and remove two screws holding  
bottom filler panel. (See Fig. 9.)  
2. Rotate bottom filler panel downward to release holding  
tabs.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Remove bottom closure panel.  
NOTE: Flexible connections should be used between ductwork  
and furnace to prevent transmission of vibration. Ductwork  
passing through unconditioned space should be insulated and  
sealed to enhance system performance. When air conditioning is  
used, a vapor barrier is recommended.  
Maintain a 1--in. (25 mm) clearance from combustible materials  
to supply air ductwork for a distance of 36 in. (914 mm)  
horizontally from the furnace. See NFPA 90B or local code for  
further requirements.  
4. Reinstall bottom filler panel and screws. Side Return Air  
Inlet  
Side Return Air Inlet  
These furnaces are shipped with bottom closure panel installed in  
bottom return--air opening. This panel MUST be in place when  
side return air inlet(s) is used without a bottom return air inlet.  
Not all horizontal furnaces are approved for side return air  
connections. (See Fig. 20).  
Ductwork Acoustical Treatment  
FILTER ARRANGEMENT  
NOTE: Metal duct systems that do not have a 90 degree elbow  
and 10 ft. (3 M) of main duct to the first branch take--off may  
require internal acoustical lining. As an alternative, fibrous  
ductwork may be used if constructed and installed in accordance  
with the latest edition of SMACNA construction standard on  
fibrous glass ducts. Both acoustical lining and fibrous ductwork  
shall comply with NFPA 90B as tested by UL Standard 181 for  
Class 1 Rigid air ducts.  
!
WARNING  
CARBON MONOXIDE AND POISONING  
HAZARD  
Failure to follow this warning could result in personal  
injury, or death.  
Never operate a furnace without a filter or with filter access  
door removed.  
Supply Air Connections  
For a furnace not equipped with a cooling coil, the outlet duct  
shall be provided with a removable access panel. This opening  
shall be accessible when the furnace is installed and shall be of  
such a size that the heat exchanger can be viewed for possible  
openings using light assistance or a probe can be inserted for  
sampling the airstream. The cover attachment shall prevent leaks.  
There are no provisions for an internal filter rack in these  
furnaces.  
Deluxe furnaces are shipped with a factory supplied Media Filter  
Cabinet.  
The Media Filter Cabinet uses either the  
factory--supplied standard 3/4--in. (19 mm) filter or a 4--in. (102  
mm) wide Media Filter which can be purchased separately.  
Refer to the instructions supplied with media Cabinet for  
assembly and installation options.  
Upflow and Horizontal Furnaces  
Connect supply--air duct to flanges on furnace supply--air outlet.  
Bend flange upward to 90_ with wide duct pliers. (See Fig. 14.)  
The supply--air duct must be connected to ONLY the furnace  
supply--outlet--air duct flanges or air conditioning coil casing  
(when used). DO NOT cut main furnace casing side to attach  
supply air duct, humidifier, or other accessories. All accessories  
MUST be connected to duct external to furnace main casing.  
AIR DUCTS  
General Requirements  
The duct system should be designed and sized according to  
accepted national standards such as those published by: Air  
Conditioning Contractors Association (ACCA), Sheet Metal and  
Air Conditioning Contractors National Association (SMACNA)  
or American Society of Heating, Refrigerating and Air  
Conditioning Engineers (ASHRAE) or consult The Air Systems  
Design Guidelines reference tables available from your local  
distributor. The duct system should be sized to handle the  
required system design CFM at the design external static pressure.  
The furnace airflow rates are provided in Table 5--AIR  
DELIVERY--CFM (With Filter).  
When a furnace is installed so that the supply ducts carry air  
circulated by the furnace to areas outside the space containing the  
furnace, the return air shall also be handled by duct(s) sealed to  
the furnace casing and terminating outside the space containing  
the furnace.  
NOTE: For horizontal applications, the top--most flange may be  
bent past 90 degrees to allow the evaporator coil to hang on the  
flange temporarily while the remaining attachment and sealing of  
the coil are performed.  
Downflow Furnaces  
Connect supply--air duct to supply--air outlet on furnace. Bend  
flange inward past 90_ with wide duct pliers. (See Fig. 14.) The  
supply--air duct must be connected to ONLY the furnace  
supplyoutlet or air conditioning coil casing (when used). When  
installed on combustible material, supply--air duct must be  
connected to ONLY the accessory subbase KGASB0201ALL or  
a factory approved air conditioning coil casing. DO NOT cut  
main furnace casing to attach supply side air duct, humidifier, or  
other accessories. All accessories MUST be connected to duct  
external to furnace casing.  
Secure ductwork with proper fasteners for type of ductwork used.  
Seal supply-- and return--duct connections to furnace with code  
approved tape or duct sealer.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPFLOW  
DOWNFLOW  
HORIZONTAL  
90°  
90°  
YES  
YES  
YES  
YES  
YES  
YES  
120°  
MIN  
120°  
MIN  
120°  
MIN  
NO  
NO  
NO  
A02020  
Fig. 14 -- Duct Flanges  
1/4" (6mm) THREADED ROD  
4 REQ.  
OUTER DOOR  
ASSEMBLY  
SECURE ANGLE  
IRON TO BOTTOM  
OF FURNACE WITH  
3 #8 x3/4" (19mm) SCREWS  
TYPICAL FOR 2 SUPPORTS  
8" (203mm) MIN  
FOR DOOR REMOVAL  
1” (25mm) SQUARE, 1-1/4”x1-1/4”x1/8” (32x32x3mm)  
ANGLE IRON OR UNI-STRUT MAY BE USED  
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS  
REQ. PER ROD  
A05027  
Fig. 15 -- Horizontal Unit Suspension  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
METHOD 2  
USE (4) #8 x 3/4 (19 mm) SHEET  
METAL SCREWS FOR EACH  
STRAP. THE STRAPS  
SHOULD BE VERTICAL  
AGAINST THE FURNACE  
SIDES AND NOT PULL AWAY  
FROM THE FURNACE  
SIDES.  
METHOD 1  
FOLD ALL STRAPS UNDER  
FURNACE AND SECURE WTH  
(4) #8 x 3/4 (19 mm) SHEET METAL SCREWS  
(2 SCREWS IN SIDE AND 2 SCREWS  
IN BOTTOM).  
A03176  
Fig. 16 -- Horizontal Suspension with Straps  
LINE CONTACT ONLY PERMISSIBLE BETWEEN  
LINES FORMED BY INTERSECTIONS OF  
THE TOP AND TWO SIDES OF THE FURNACE  
JACKET AND BUILDING JOISTS,  
STUDS, OR FRAMING.  
17 3/  
(451mm)OVERALL  
4 3/  
4 (121mm) UNDER DOOR  
1(425mm) UNDER FURNACE  
GAS  
ENTRY  
TYPE-B  
VENT  
EXTEND OUT 12(305mm)  
FROM FACE OF DOOR  
mm)  
2
15  
(
*
IN  
M
6
30-IN. (762mm)  
MIN WORK AREA  
* WHEN USED WITH  
SINGLE WALL VENT  
CONNECTIONS  
17 3/4  
22  
(451mm)  
SHEET  
METAL  
EQUIPMENT MANUAL  
SHUT-OFF GAS VALVE  
SEDIMENT  
UNION  
TRAP  
A03177  
Fig. 17 -- Typical Attic Installation  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Return Air Connections  
!
WARNING  
!
WARNING  
FIRE OR EXPLOSION HAZARD  
FIRE HAZARD  
Failure to follow this warning could result in personal  
injury, death, and/or property damage.  
Failure to follow this warning could cause personal injury,  
death and/or property damage.  
If local codes allow the use of a flexible gas appliance  
connector, always use a new listed connector. Do not use a  
connector which has previously served another gas  
appliance. Black iron pipe shall be installed at the furnace  
gas control valve and extend a minimum of 2 in.(51 mm)  
outside the furnace.  
Never connect return--air ducts to the back of the furnace.  
Follow instructions below  
Downflow Furnaces  
The return--air duct must be connected to return--air opening  
(bottom inlet) as shown in Fig. 19. DO NOT cut into casing sides  
(left or right). Side opening is permitted for only upflow and most  
horizontal furnaces. (See Fig. 19.) Bypass humidifier connections  
should be made at ductwork or coil casing sides exterior to  
furnace.  
Gas piping must be installed in accordance with national and  
local codes. Refer to current edition of NFGC in the U.S., the  
CAN/CSA--B149.1--05 in Canada.  
Installations must be made in accordance with all authorities  
having jurisdiction. If possible, the gas supply line should be a  
separate line running directly from meter to furnace.  
Upflow and Horizontal Furnaces  
The return--air duct must be connected to bottom, sides (left or  
right), or a combination of bottom and side(s) of main furnace  
casing as shown in Fig. 18 and 20. Bypass humidifier may be  
attached into unused return air side of the furnace casing. (See  
Fig. 18 and 20.)  
Not all horizontal furnaces are approved for side return air  
connections. (See Fig. 20.)  
GAS PIPING  
NOTE: In the state of Massachusetts:  
1. Gas supply connections MUST be performed by a  
licensed plumber or gas fitter.  
2. When flexible connectors are used, the maximum length  
shall not exceed 36 inches (915 mm).  
3. When lever handle type manual equipment shutoff valves  
are used, they shall be T--handle valves.  
4. The use of copper tubing for gas piping is NOT approved  
by the state of Massachusetts.  
!
WARNING  
Refer to Table 6 for recommended gas pipe sizing. Risers must be  
used to connect to furnace and to meter. Support all gas piping  
with appropriate straps, hangers, etc. Use a minimum of 1 hanger  
every 6 ft. (2 M). Joint compound (pipe dope) should be applied  
sparingly and only to male threads of joints. Pipe dope must be  
resistant to the action of propane gas.  
An accessible manual equipment shutoff valve MUST be  
installed external to furnace casing and within 6 ft. (2 M) of  
furnace. A 1/8--in. (3 mm) NPT plugged tapping, accessible for  
test gauge connection, MUST be installed immediately upstream  
of gas supply connection to furnace and downstream of manual  
equipment shutoff valve.  
FIRE OR EXPLOSION HAZARD  
Failure to follow this warning could result in personal  
injury, death, and/or property damage.  
Never purge a gas line into a combustion chamber. Never  
test for gas leaks with an open flame. Use a commercially  
available soap solution made specifically for the detection  
of leaks to check all connections.  
!
WARNING  
NOTE: The furnace gas control valve inlet pressure tap  
connection is suitable to use as test gauge connection providing  
test pressure DOES NOT exceed maximum 0.5 psig (14--in. wc)  
stated on gas control valve. (See Fig. 52.)  
FIRE OR EXPLOSION HAZARD  
Failure to follow this warning could result in personal  
injury,death, and/or property damage.  
Some installations require gas entry on right side of furnace (as  
viewed in upflow.) (See Fig. 21.)  
Use proper length of pipe to avoid stress on gas control  
manifold and a gas leak.  
Install a sediment trap in riser leading to furnace as shown in Fig  
22. Connect a capped nipple into lower end of tee. Capped nipple  
should extend below level of furnace gas controls. Place a ground  
joint union between furnace gas control valve and exterior  
manual equipment gas shutoff valve. A 1/8--in. (3 mm) NPT  
plugged tapping, accessible for test gauge connection, MUST be  
installed immediately upstream of gas supply connection to  
furnace and downstream of manual equipment shutoff valve.  
!
CAUTION  
FURNACE OVERHEAT HAZARD  
Failure to follow this caution may result in property  
damage.  
Connect gas pipe to gas valve using a backup wrench to  
avoid damaging gas controls and burner misalignment.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5 – Air Delivery -- CFM (With Filter)*  
EXTERNAL STATIC PRESSURE (In. wc)  
RETURN---AIR  
SUPPLY  
UNIT SIZE  
SPEED  
0.1  
1185  
920  
0.2  
1145  
880  
0.3  
1115  
835  
0.4  
1075  
800  
0.5  
1035  
755  
0.6  
980  
720  
0.7  
905  
680  
0.8  
820  
0.9  
720  
1
580  
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
645  
605  
540  
045---08/  
024045  
Bottom or  
Side(s)  
735  
685  
625  
585  
530  
490  
435  
395  
345  
295  
820  
765  
725  
670  
630  
580  
545  
490  
455  
405  
650  
595  
535  
490  
430  
390  
330  
280  
235  
--- ---  
1625  
1405  
1240  
1190  
1035  
1845  
1590  
1365  
1225  
1100  
2255  
1600  
1945  
1420  
1280  
2295  
1725  
1910  
1630  
1430  
1585  
1360  
1200  
1140  
985  
1535  
1320  
1155  
1095  
930  
1755  
1500  
1270  
1110  
960  
2150  
1465  
1830  
1280  
1140  
2185  
1605  
1800  
1510  
1285  
1495  
1280  
1110  
1050  
885  
1710  
1455  
1215  
1060  
875  
2100  
1400  
1770  
1200  
1055  
2125  
1545  
1745  
1435  
1200  
1460  
1240  
1065  
1000  
835  
1665  
1410  
1170  
1010  
805  
2040  
1335  
1715  
1140  
990  
2070  
1460  
1685  
1365  
1125  
1415  
1195  
1020  
955  
1365  
1155  
975  
915  
745  
1500  
1315  
1070  
895  
1295  
1115  
935  
1220  
1070  
895  
1125  
1030  
850  
070---16 /  
048070  
Bottom or  
Side(s)  
870  
830  
790  
785  
695  
650  
600  
1800  
1545  
1320  
1160  
1030  
2205  
1525  
1890  
1340  
1205  
2240  
1660  
1865  
1575  
1355  
1595  
1365  
1125  
950  
1400  
1270  
1025  
830  
1275  
1180  
955  
1105  
1000  
900  
090---16 /  
048090  
Bottom or  
Side(s)  
770  
710  
730  
645  
570  
505  
425  
1985  
1275  
1655  
1065  
910  
2005  
1395  
1610  
1300  
1075  
1920  
1210  
1600  
1005  
840  
1925  
1340  
1545  
1245  
1015  
1835  
1150  
1545  
925  
1735  
1080  
1480  
865  
1615  
1015  
1430  
790  
110---20 /  
060110  
Bottom or  
Side(s)  
760  
695  
630  
1805  
1285  
1485  
1185  
945  
1670  
1230  
1435  
1130  
855  
1545  
1170  
1380  
1065  
800  
Bottom or  
Side(s)  
135---20 /  
060135  
*A filter is required for each return---air inlet. Airflow performance included 3/4---in. (19 mm) washable filter media such as contained in factory --- au th or ized  
accessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.  
--- --- Indicates unstable operating conditions.  
Table 6 – Maximum Capacity of Pipe*  
NOMINAL IRON  
PIPE  
INTERNAL  
DIAMETER  
LENGTH OF PIPE --- FT. (M)  
SIZE IN. (mm)  
1/2 (13)  
3/4 (19)  
1 (25)  
1---1/4 (32)  
1---1/2 (38)  
In. (mm)  
0.622 (16)  
0.824 (21)  
1.049 (27)  
1.380 (35)  
1.610 (41)  
10  
175 (53)  
360 (110)  
680 (207)  
1400 (427)  
2100 (640)  
20  
120 (37)  
250 (76)  
465 (142)  
950 (290)  
1460 (445)  
30  
97 (30)  
200 (61)  
375 (114)  
770 (235)  
1180 (360)  
40  
82 (25)  
170 (52)  
320 (98)  
660 (201)  
990 (301)  
50  
73 (22)  
151 (46)  
285 (87)  
580 (177)  
900 (274)  
* Cubic ft. of natural gas per hr for gas pressures of 0.5 psig (14---in. wc) or less and a pressure drop of 0.5---in wc (based on a 0.60 specific gravity  
gas). Ref: Chapter 6 ANSI Z223---2006/NFPA 54---2006.  
Piping should be pressure and leak tested in accordance with  
NFGC in the United States or CAN/CSA--B149.1--05 in Canada,  
local, and national plumbing and gas codes before the furnace has  
been connected. After all connections have been made, purge  
lines and check for leakage at furnace prior to operating furnace.  
If pressure exceeds 0.5 psig (14--in. wc), gas supply pipe must be  
disconnected from furnace and capped before and during supply  
pipe pressure test. If test pressure is equal to or less than 0.5 psig  
(14--in. wc), turn off electric shutoff switch located on furnace gas  
control valve and accessible manual equipment shutoff valve  
before and during supply pipe pressure test. After all connections  
have been made, purge lines and check for leakage at furnace  
prior to operating furnace.  
The gas supply pressure shall be within the maximum and  
minimum inlet supply pressures marked on the rating plate with  
the furnace burners ON and OFF.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A02075  
Fig. 18 -- Upflow Return Air Configurations and Restrictions  
A02163  
Fig. 19 -- Downflow Return Air Configurations and Restrictions  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A02162  
Fig. 20 -- Horizontal Return Air Configurations and Restrictions  
2(51mm)  
Street Elbow  
A08551  
Fig. 21 -- Burner and Manifold  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 7 – Electrical Data  
OPERATING  
VOLTAGE*  
(VOLTS)  
V O LT S ---  
H E R T Z ---  
PHASE  
UNIT  
AMPACITY#  
(AMPS)  
MAX WIRE  
LENGTH}  
FT. (M)  
MAX FUSE/  
CKT BKR{  
(AMPS)  
FURNACE  
MODEL  
MAX UNIT  
(AMPS)  
MIN WIRE  
GAGE  
MAX  
127  
127  
127  
127  
127  
MIN  
045---08 / 024045  
070---16 / 048070  
090---16 / 048090  
110---20 / 060110  
135---20 / 060135  
1 1 5 --- 6 0 --- 1  
1 1 5 --- 6 0 --- 1  
1 1 5 --- 6 0 --- 1  
1 1 5 --- 6 0 --- 1  
1 1 5 --- 6 0 --- 1  
104  
104  
104  
104  
104  
8.1  
9.5  
10.3  
13.1  
13.1  
10.9  
12.6  
13.4  
16.9  
16.9  
34 (10)  
29 (9)  
27 (8)  
34 (10)  
34 (10)  
15  
15  
15  
20  
20  
14  
14  
14  
12  
12  
* Permissible limits of the voltage range at which the unit operates satisfactorily.  
# Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier,  
etc.) full load amps.  
{ Time---delay type is recommended.  
} Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.  
GAS  
SUPPLY  
MANUAL  
SHUTOFF  
VALVE  
(REQUIRED)  
SEDIMENT  
TRAP  
UNION  
A02035  
Fig. 22 -- Typical Gas Pipe Arrangement  
ELECTRICAL CONNECTIONS  
!
WARNING  
!
WARNING  
ELECTRICAL SHOCK AND FIRE HAZARD  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal  
injury, death, or property damage.  
Failure to follow this warning could result in personal  
The cabinet MUST have an uninterrupted or unbroken  
ground according to NEC ANSI/NFPA 70--2008 and  
Canadian Electrical Code CSA C22.1 or local codes to  
minimize personal injury if an electrical fault should occur.  
This may consist of electrical wire, conduit approved for  
electrical ground or a listed, grounded power cord (where  
permitted by local code) when installed in accordance with  
existing electrical codes. Refer to the power cord  
manufacturer’s ratings for proper wire gauge. Do not use  
gas piping as an electrical ground.  
injury or death.  
Blower access panel door switch opens 115--v power to  
control. No component operation can occur. Do not bypass  
or close switch with panel removed.  
See Fig. 25 for field wiring diagram showing typical field 115--v  
wiring. Check all factory and field electrical connections for  
tightness.  
Field--supplied wiring shall conform with the limitations of 63_F  
(35_C) rise.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL CONNECTION TO J--BOX  
Field--Supplied Electrical Box on Furnace J--Box Bracket  
See Fig. 23.  
!
CAUTION  
FURNACE MAY NOT OPERATE  
1. Remove cover from furnace J--Box.  
Failure to follow this caution may result in intermittent  
furnace operation.  
2. Attach electrical box to furnace J--Box bracket with at least  
two field--supplied screws through holes in electrical box  
into holes in bracket. Use blunt--nose screws that will not  
pierce wire insulation.  
Furnace control must be grounded for proper operation or  
else control will lock out. Control must remain grounded  
through green/yellow wire routed to gas valve and manifold  
bracket screw.  
3. Route furnace power wires through holes in electrical box  
and J--Box bracket, and make field--wire connections in  
electrical box. Use best practices (NEC in U.S. and CSA  
C22.1 in Canada) for wire bushings, strain relief, etc.  
115--V WIRING  
4. Route and secure field ground wire to green ground screw  
on J--Box bracket.  
5. Connect line voltage leads as shown in Fig. 25.  
Verify that the voltage, frequency, and phase correspond to that  
specified on unit rating plate. Also, check to be sure that service  
provided by utility is sufficient to handle load imposed by this  
equipment. Refer to rating plate or Table 7 for equipment  
electrical specifications.  
6. Reinstall cover to J--Box. Do not pinch wires between  
cover and bracket.  
U.S. Installations: Make all electrical connections in accordance  
with National Electrical Code (NEC) ANSI/NFPA 70--2008 and  
any local codes or ordinances that might apply.  
Electrical Box on Furnace Casing Side  
See Fig. 23.  
Canadian Installations: Make all electrical connections in  
accordance with Canadian Electrical Code CSA C22.1 or  
authorities having jurisdiction.  
!
WARNING  
FIRE OR ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal  
injury, death, or property damage.  
!
WARNING  
FIRE HAZARD  
If field--supplied manual disconnect switch is to be mounted  
on furnace casing side, select a location where a drill or  
fastener cannot damage electrical or gas components.  
Failure to follow this warning could result in personal  
injury, death, or property damage.  
Do not connect aluminum wire between disconnect switch  
and furnace. Use only copper wire.  
1. Select and remove a hole knockout in the casing where the  
electrical box is to be installed.  
NOTE: Check that duct on side of furnace will not interfere with  
installed electrical box.  
Use a separate, fused branch electrical circuit with a properly  
sized fuse or circuit breaker for this furnace. See Table 7 for wire  
size and fuse specifications. A readily accessible means of  
electrical disconnect must be located within sight of the furnace.  
NOTE: Proper polarity must be maintained for 115--v wiring. If  
polarity is incorrect, control LED status indicator light will flash  
rapidly and furnace will NOT operate.  
2. Remove the desired electrical box hole knockout and  
positionthe hole in the electrical box over the hole in the  
furnace casing.  
3. Fasten the electrical box to casing by driving two  
fieldsupplied screws from inside electrical box into casing  
steel.  
4. Remove and save two screws holding J--Box. (See Fig.  
22.)  
5. Pull furnace power wires out of 1/2--in. (12 mm) diameter  
hole in J--Box. Do not loosen wires from strain--relief  
wire--tie on outside of J--Box.  
J--BOX RELOCATION  
NOTE: If factory location of J--Box is acceptable, go to next  
section (ELECTRICAL CONNECTION TO J--BOX).  
NOTE: On 14--in. (356 mm) wide casing models, the J--Box  
shall not be relocated to other side of furnace casing when the  
vent pipe is routed within the casing.  
6. Route furnace power wires through holes in casing and  
electrical box and into electrical box.  
1. Remove and save two screws holding J--Box.  
NOTE: The J--Box cover need not be removed from the J--Box  
in order to move the J--Box. Do NOT remove green ground  
screw inside J--Box. The ground screw is not threaded into the  
casing flange and can be lifted out of the clearance hole in casing  
while swinging the front edge of the J--Box outboard of the  
casing.  
7. Pull field power wires into electrical box.  
8. Remove cover from furnace J--Box.  
9. Route field ground wire through holes in electrical box  
and casing, and into furnace J--Box.  
10. Reattach furnace J--Box to furnace casing with screws  
removed in Step 4.  
2. Cut wire tie on loop in furnace wires attached to J--box.  
3. Move J--Box to desired location.  
11. Secure field ground wire to J--Box green ground screw.  
12. Complete electrical box wiring and installation. Connect  
line voltage leads as shown in Fig. 25. Use best practices  
(NEC in U.S. and CSA C22.1 in Canada) for wire  
bushings, strain relief, etc.  
4. Fasten J--Box to casing with two screws removed in Step  
1.  
5. Route J--Box wires within furnace away from sharp edges,  
rotating parts and hot surfaces.  
13. Reinstall cover to J--Box. Do not pinch wires between  
cover and bracket.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Connect line voltage leads as shown in Fig. 25.  
6. Reinstall cover to J--Box. Do not pinch wires between  
cover and bracket.  
24--V WIRING  
Make field 24--v connections at the 24--v terminal strip. (See Fig.  
23.) Connect terminal Y/Y2 as shown in Fig. 24 for proper  
cooling operation. Use only AWG No. 18, color--coded, copper  
thermostat wire.  
The 24--v circuit contains an automotive--type, 3--amp.. fuse  
located on the control. Any direct shorts during installation,  
service, or maintenance could cause this fuse to blow. If fuse  
replacement is required, use ONLY a 3--amp.. fuse of identical  
size.  
ACCESSORIES  
1. Electronic Air Cleaner (EAC)  
Connect an accessory Electronic Air Cleaner (if used)  
using 1/4--in female quick connect terminals to the two  
male 1/4--in quick--connect terminals on the control board  
marked EAC--1 and EAC--2. The terminals are rated for  
115 VAC, 1.0 amps maximum and are energized during  
blower motor operation. (See Fig. 24.)  
2. Humidifier (HUM)  
Connect an accessory 24 VAC, 0.5 amp. maximum  
humidifier (if used) to the 1/4--in male quick--connect  
HUM terminal and COM--24V screw terminal on the  
control board thermostat strip. The HUM terminal is  
energized when gas valve relay (GVR) is energized. (See  
Fig. 24.)  
A03221  
Fig. 23 -- Field--Supplied Electrical Box on Furnace Casing  
POWER CORD INSTALLATION IN FURNACE J--BOX  
NOTE: Power cords must be able to handle the electrical  
requirements listed in Table 7. Refer to power cord  
manufacturer’s listings.  
NOTE: A field--supplied, 115--v controlled relay connected to  
EAC terminals may be added if humidifier operation is desired  
during blower operation.  
1. Remove cover from J--Box.  
NOTE: DO NOT connect furnace control HUM terminal to  
HUM (humidifier) terminal on Thermidistatt, Zone Controller  
or similar device. See Thermidistat, Zone Controller, thermostat,  
or controller manufacturer’s instructions for proper connection.  
2. Route listed power cord through 7/8--in. (22 mm) diameter  
hole in J--Box.  
3. Secure power cord to J--Box bracket with a strain relief  
bushing or a connector approved for the type of cord used.  
VENTING  
4. Secure field ground wire to green ground screw on J--Box  
bracket.  
5. Connect line voltage leads as shown in Fig. 25.  
The furnace shall be connected to a listed factory built chimney  
or vent, or a clay--tile lined masonry or concrete chimney. Venting  
into an unlined masonry chimney or concrete chimney is  
prohibited.  
When an existing Category I furnace is removed or replaced, the  
original venting system may no longer be sized to properly vent  
the attached appliances. An improperly sized Category I venting  
system could cause the formation of condensate in the furnace  
and vent, leakage of condensate and combustion products, and  
spillage of combustion products into the living space.  
6. Reinstall cover to J--Box. Do not pinch wires between  
cover and bracket.  
BX CABLE INSTALLATION IN FURNACE J--BOX  
1. Remove cover from J--Box.  
2. Route BX cable into 7/8--inch diameter hole in J--Box.  
3. Secure BX cable to J--Box bracket with connectors  
approved for the type of cable used.  
4. Secure field ground wire to green ground screw on J--Box  
bracket.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER OFF-DELAY  
TWINNING AND/OR  
COMPONENT TEST  
TERMINAL  
24-V THERMOSTAT  
TERMINALS  
HUMIDIFIER TERMINAL  
(24-VAC 0.5 AMP. MAX)  
3-AMP FUSE  
LED OPERATION  
& DIAGNOSTIC  
LIGHT  
HEAT  
COOL  
FAN  
TRANSFORMER  
24-VAC CONNECTIONS  
BLOWER SPEED  
SELECTION  
TERMINALS  
SPARE 2  
SPARE 1  
PL1-LOW VOLTAGE  
DRAIN HARNESS  
CONNECTOR  
115-VAC (L2)  
NEUTRAL  
CONNECTIONS  
EAC-1 TERMINAL  
PL2-HOT SURFACE  
IGNITER & INDUCER  
MOTOR CONNECTOR  
(115-VAC 1.0 AMP. MAX.)  
115-VAC (L1)  
NEUTRAL  
CONNECTIONS  
A08063  
Fig. 24 -- Furnace Control  
FIELD 24-V WIRING  
FIELD 115-, 208/230-, 460-V WIRING  
FACTORY 24-V WIRING  
FACTORY 115-V WIRING  
NOTE 2  
THERMOSTAT  
TERMINALS  
W
C
R
G
Y
FIVE WIRE  
FIELD-SUPPLIED  
DISCONNECT  
THREE-WIRE  
HEATING-ONLY  
208/230- OR  
460-V  
BLOWER DOOR SWITCH  
THREE  
PHASE  
W
BLK  
BLK  
WHT  
C
R
WHT  
O
N
T
208/230-V  
SINGLE  
PHASE  
GND  
GND  
G
R
AUXILIARY  
J-BOX  
115-V FIELD-  
SUPPLIED  
DISCONNECT  
O
COM  
GND  
L
NOTE 1  
CONDENSING  
UNIT  
Y/Y2  
TWO  
WIRE  
24-V  
TERMINAL  
BLOCK  
NOTES: 1. Connect Y-terminal in furnace as shown for proper blower operation.  
2. Some thermostats require a "C" terminal connection as shown.  
3. If any of the original wire, as supplied, must be replaced, use  
same type or equivalent wire.  
FURNACE  
A99440  
Fig. 25 -- Heating and Cooling Application Wiring Diagram with 1--Stage Thermostat  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
the local building codes, and furnace and vent manufacturers’  
instructions.  
!
WARNING  
These furnaces are design--certified as Category I furnaces in  
accordance with ANSI Z21.47--2006/CSA 2.3--2006 and operate  
with a non--positive vent static pressure to minimize the potential  
for vent gas leakage. Category I furnaces operate with a flue loss  
not less than 17 percent to minimize the potential for  
condensation in the venting system. These furnaces are approved  
for common venting and multistory venting with other fan  
assisted or draft hood equipped appliances in accordance with the  
NFGC or the CAN/CSA--B149.1--05, the local building codes,  
and furnace and vent manufacturers’ instructions. The following  
information and warning must be considered in addition to the  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow the steps outlined below for each  
appliance connected to the venting system being placed into  
operation could result in carbon monoxide poisoning or  
death. The following steps shall be followed for each  
appliance connected to the venting system being placed into  
operation, while all other appliances connected to the  
venting system are not in operation:  
1. Seal any unused openings in venting system.  
2. Inspect the venting system for proper size and  
horizontal pitch, as required in the National Fuel Gas  
Code, ANSI Z223.1/NFPA 54 or CSA B149.1,  
Natural Gas and Propane Installation Code and these  
instructions. Determine that there is no blockage or  
restriction, leakage, corrosion and other deficiencies,  
which could cause an unsafe condition.  
3. As far as practical, close all building doors and  
windows and all doors between the space in which  
the appliance(s) connected to the venting system are  
located and other spaces of the building.  
requirements  
defined  
in  
the  
NFGC  
and  
the  
CAN/CSA--B149.1--05.  
1. If a vent (common or dedicated) becomes blocked, the  
furnace will be shut off by the draft safeguard switch  
located on the vent elbow.  
2. Do not vent this Category I furnace into a single--wall  
dedicated or common vent. The dedicated or common  
vent is considered to be the vertical portion of the vent  
system that terminates outdoors.  
3. Vent connectors serving Category I furnaces shall not be  
connected into any portion of a mechanical draft system  
operating under positive pressure.  
4. In the U.S.: Do not vent this appliance with any solid fuel  
burning appliance. In Canada: Check with the authority  
having jurisdiction for approval on use with solid fuel  
burning appliance.  
4. Close fireplace dampers.  
5. Turn on clothes dryers and any appliance not  
connected to the venting system. Turn on any  
exhaust fans, such as range hoods and bathroom  
exhausts, so they are operating at maximum speed.  
Do not operate a summer exhaust fan.  
6. Follow the lighting instructions. Place the appliance  
being inspected into operation. Adjust the thermostat  
so appliance is operating continuously.  
5. Category I furnaces must be vented vertically or nearly  
vertically unless equipped with a listed power ventor.  
6. Do not vent this appliance into an unlined masonry  
chimney. Refer to Chimney Inspection Chart, Fig. 33.  
7. Test for spillage from draft hood equipped  
appliances at the draft hood relief opening after 5  
minutes of main burner operation. Use the flame of a  
match or candle.  
8. If improper venting is observed during any of the  
above tests, the venting system must be corrected in  
accordance with the National Fuel Gas Code, ANSI  
Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas  
and Propane Installation Code.  
9. After it has been determined that each appliance  
connected to the venting system properly vents when  
tested as outlined above, return doors, windows,  
exhaust fans, fireplace dampers and any other  
gas--fired burning appliance to their previous  
conditions of use.  
MASONRY CHIMNEY REQUIREMENTS  
NOTE: These furnaces are CSA design--certified for use in  
exterior tile--lined masonry chimneys with a factory accessory  
Chimney Adapter Kit. Refer to the furnace rating plate for correct  
kit usage. The Chimney Adapter Kits are for use with ONLY  
furnaces having a Chimney Adapter Kit numbers marked on the  
furnace rating plate.  
If a clay tile--lined masonry chimney is being used and it is  
exposed to the outdoors below the roof line, relining might be  
required. Chimneys shall conform to the Standard for Chimneys,  
Fireplaces, Vents, and Solid Fuel Burning Appliances  
ANSI/NFPA 211--2006 in the United States and to a Provincial or  
Territorial Building Code in Canada (in its absence, the National  
Building Code of Canada) and must be in good condition.  
U.S.A.--Refer to Sections 13.1.8 and 13.2.20 of the NFGC  
NFPA54/ANSI Z223.1--2006 or the authority having jurisdiction  
to determine whether relining is required. If relining is required,  
use a properly sized listed metal liner, Type--B vent, or a listed  
alternative venting design.  
Vent system or vent connectors may need to be resized. Vent  
systems or vent connectors, must be sized to approach minimum  
size as determined using appropriate table found in the NFGC or  
CAN/CSA--B149.1--05.  
NOTE: See the NFPA54/ANSI Z223.1--2006, 13.1.8 and  
13.2.20 regarding alternative venting design and the Exception,  
which cover installations such as the Chimney Adapter Kits  
KGACA02014FC and KGACA02015FC, which are listed for  
use with these furnaces.  
GENERAL VENTING REQUIREMENTS  
Follow all safety codes for proper vent sizing and installation  
requirements, including local building codes, the National Fuel  
Gas Code ANSI Z223.1--2006/NFPA 54--2006 (NFGC), Parts 12  
and 13 in the United States or the National Standard of Canada,  
Natural Gas and Propane Installation Code CSA--B149.1--05  
(CAN/CSA--B149.1--05), Section 8 and Appendix C in Canada,  
The Chimney Adapter Kit is listed alternative venting system for  
these furnaces. See the kit instructions for complete details.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
See notes 2,5,7, and 10 on the page following these figures.  
See notes 1, 2, 4, 6, 7, 9, 10 and 12 on the  
page following these figures.  
A04215  
A04217  
Fig. 26 -- Single--Stage Furnace with Single--Speed Air Con-  
ditioner  
Fig. 28 -- Single--Stage Furnace with Single--Speed Heat  
Pump (Dual Fuel)  
See notes 2,5,8, and 10 on the page following these figures.  
See notes 1, 2, 3, 4, 6, 8, 9, 10 and 12 on the  
page following these figures.  
A04216  
Fig. 27 -- Single Stage Furnace with Two--Speed Air Condi-  
tioner  
A04218  
Fig. 29 -- Single--Stage Furnace with Two--Speed heat Pump  
(Dual Fuel)  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HUMIDFIER  
(24VAC)  
HUMIDFIER  
(24VAC)  
See notes 1, 2, 4, 11, 12, and 13 on the page following these figures.  
See notes 1, 2, 3, 4, 11, 12, and 14 on the page following these figures.  
A04220  
A04219  
Fig. 31 -- Dual Fuel Thermostat with Single--Stage Furnace  
and Two--Speed Heat Pump  
Fig. 30 -- Dual Fuel Thermostat with Single--Stage Furnace  
and Single--Speed Heat Pump  
See note 2 on the page following these figures.  
HUMIDFIER  
(24VAC)  
A04221  
Fig. 32 -- Two Stage Thermostat with Single--Stage Furnace and Two--Speed Air Conditioner  
NOTES FOR FIGURES 26--32  
1. Heat pump MUST have a high pressure switch for dual fuel applications.  
2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.  
3. Outdoor Air Temperature Sensor must be attached in all dual fuel applications.  
4. Dip switch No. 1 on Thermidistat should be set in OFF position for air conditioner installations. This is factory default.  
5. Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations.  
6. Dip switch No. 2 on Thermidistat should be set in OFF position for single--speed compressor operation. This is factory default.  
7. Dip switch No. 2 on Thermidistat should be set in ON position for two--speed compressor operation.  
8. Configuration Option No. 10 “Dual Fuel Selection” must be turned ON in all dual fuel applications.  
9. NO connection should be made to the furnace HUM terminal when using a Thermidistat.  
10. The RVS Sensing terminal “L” should not be connected. This is internally used to sense defrost operation.  
11. DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE POINT” option on the two--speed heat pump control board. This  
is controlled internally by the Thermidistat/Dual Fuel Thermostat.  
12. Dip switch D on Dual Fuel Thermostat should be set in OFF position for single--speed compressor operation. This is factory default.  
13. Dip switch D on Dual Fuel Thermostat should be set in ON position for two--speed compressor operation.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Canada (and U.S.A.)--This furnace is permitted to be vented into  
a clay tile--lined masonry chimney that is exposed to the outdoors  
below the roof line, provided:  
Table 9 – Minimum Allowable Input Rating of Space--Heat-  
ing Appliance in Thousands of BTUH per Hour  
INTERNAL AREA OF CHIMNEY  
1. Vent connector is Type--B double--wall, and  
2. This furnace is common vented with at least 1 draft  
hoodequipped appliance, and  
2
2
IN . (MM )  
28  
(12258) (18064) (24516)  
VENT HEIGHT  
FT (M)  
12  
(7741)  
19  
38  
Local 99% Winter Design  
Temperature: 17 to 26_F ( --- 8 t o --- 3 _C)  
3. The combined appliance input rating is less than the  
maximum capacity given in Table A, and  
6 (1.8)  
8 (2.4)  
10 (3.0)  
15 (4.6)  
20 (6.1)  
30 (9.1)  
0
52  
NR  
NR  
NR  
NR  
55  
74  
90  
NR  
NR  
NR  
99  
141  
154  
169  
212  
258  
362  
4. The input rating of each space heating appliance is greater  
than the minimum input rating given in Table B for the  
local 99% Winter Design Temperature. Chimneys having  
internal areas greater than 38 square inches require furnace  
input ratings greater than the input ratings of these  
furnaces. See footnote at bottom of Table B, and  
111  
125  
167  
212  
NR  
Local 99% Winter Design  
Temperature: 5 to 16_F * ( --- 1 5 t o --- 9 _C)  
5. The authority having jurisdiction approves.  
If all of these conditions cannot be met, an alternative venting  
design shall be used, such as the listed chimney adapter kit with  
these furnaces, which are listed for use with the kit, a listed  
chimney--lining system, or a Type--B common vent.  
Inspections before the sale and at the time of installation will  
determine the acceptability of the chimney or the need for repair  
and/or (re)lining. Refer to the Fig. 33 to perform a chimney  
inspection. If the inspection of a previously used tile--lined  
chimney:  
6 (1.8)  
8 (2.4)  
10 (3.0)  
15 (4.6)  
20 (6.1)  
30 (9.1)  
NR  
NR  
NR  
NR  
NR  
NR  
78  
94  
111  
NR  
NR  
NR  
121  
135  
149  
193  
NR  
166  
182  
198  
247  
293  
377  
NR  
Local 99% Winter Design  
Temperature: ---10 to 4_F * ( --- 2 3 t o --- 1 6 _C)  
6 (1.8)  
8 (2.4)  
10 (3.0)  
15 (4.6)  
20 (6.1)  
30 (9.1)  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
145  
159  
175  
NR  
NR  
NR  
196  
213  
231  
283  
333  
NR  
a. Shows signs of vent gas condensation, the chimney  
should be relined in accordance with local codes and the  
authority having jurisdiction. The chimney should be  
relined with a listed metal liner, Type--B vent, or a listed  
chimney adapter kit shall be usedto reducecondensation.  
If a condensate drain is required by local code, refer to  
the NFGC NFPA54/ANSI Z223.1--2006, Section 12.10  
for additional information on condensate drains.  
Local 99% Winter Design  
Temperature: ---11_F ( --- 2 4 _C) or lower  
Not recommended for any vent configuration.  
b. Indicates the chimney exceeds the maximum permissible  
size in the tables, the chimney should be rebuilt or relined  
to conform to the requirements of the equipment being  
installed and the authority having jurisdiction.  
*The 99.6% heating db temperatures found in the 1997 or 2001 ASHRAE  
Fundamentals Handbook, Climatic Design Information chapter, Table 1A  
(United States) and 2A (Canada) or the 2005 ASHRAE Fundamentals  
handbook, Climatic Design Information chapter, and the CD---ROM in-  
cluded with the 2005 ASHRAE Fundamentals Handbook.  
A chimney without a clay tile liner, which is otherwise in good  
condition, shall be rebuilt to conform to ANSI/NFPA 211 or be  
lined with a UL listed (ULC listed in Canada) metal liner or UL  
listed Type--B vent. Relining with a listed metal liner or Type--B  
vent is considered to be a vent--in--a--chase.  
If a metal liner or Type--B vent is used to line a chimney, no other  
appliance shall be vented into the annular space between the  
chimney and the metal liner.  
APPLIANCE APPLICATION REQUIREMENTS  
Appliance operation has a significant impact on the performance  
of the venting system. If the appliances are sized, installed,  
adjusted, and operated properly, the venting system and/or the  
appliances should not suffer from condensation and corrosion.  
The venting system and all appliances shall be installed in  
accordance with applicable listings, standards, and codes.  
The furnace should be sized to provide 100 percent of the design  
heating load requirement plus any margin that occurs because of  
furnace model size capacity increments. Heating load estimates  
can be made using approved methods available from Air  
Conditioning Contractors of America (Manual J); American  
Society of Heating, Refrigerating, and Air--Conditioning  
Engineers; or other approved engineering methods. Excessive  
oversizing of the furnace could cause the furnace and/or vent to  
fail prematurely. When a metal vent or metal liner is used, the  
vent must be in good condition and be installed in accordance  
with the vent manufacturer’s instructions.  
Exterior Masonry Chimney FAN + NAT  
Installations with Type--B Double Wall Vent  
Connectors ©NFPA & AGA  
Table 8 – Combined Appliance Maximum Input Rating in  
Thousands of BTUH per Hour  
INTERNAL AREA OF CHIMNEY  
2
2
VENT HEIGHT  
FT. (M)  
IN (MM )  
12  
19  
(12258)  
28  
(18064)  
38  
(7741)  
(24516)  
6 (1.8)  
8 (2.4)  
10 (3.0)  
15 (4.5)  
20 (6.0)  
30 (9.1)  
74  
80  
84  
NR  
NR  
NR  
119  
130  
138  
152  
NR  
NR  
178  
193  
207  
233  
250  
NR  
257  
279  
299  
334  
368  
404  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHIMNEY INSPECTION CHART  
For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211  
Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances in the U.S.A. or to the Canadian  
installation Code CSA-B149.1 in Canada.  
Crown  
Rebuild  
crown.  
condition:  
Missing mortar  
or brick?  
Yes  
No  
Is chimney  
property lined with  
clay tile liner?  
No  
Yes  
Repair  
Is  
Reline  
No  
liner or top seal  
or reline chimney as  
necessary.  
liner and top  
seal in good  
condition?  
Repair  
Yes  
Debris  
Mortar  
or tile  
debris?  
in cleanout?  
Yes  
Yes  
Remove mortar  
and tile debris  
Mortar, tile, metal vent,  
fuel oil residue?  
No  
Remove metal vent  
or liner.  
No  
Clay  
Yes  
tile misalignment,  
missing sections,  
gaps?  
Consult  
Part B of  
Not Suitable  
chimney adapter venting  
instructions for  
application  
No  
No  
suitability.  
Is chimney  
lined with properly  
sized, listed liner or  
Type-B vent?  
Line chimney with property  
sized, listed flexible metal  
liner or Type-B vent per  
NFGC or NSCNGPIC Vent  
Sizing Tables and liner or  
vent manufacturer’s  
Condensate  
drainage at bottom  
of chimney?  
Suitable  
Yes  
Yes  
Install chimney  
adapter per  
instructions.  
No  
Installation instructions.  
Not Suitable  
Consult  
Yes  
Chimney  
exposed to  
outdoors below  
roof line?  
Part C of  
chimney adapter venting  
instructions for  
application  
Is chimney  
to be dedicated to  
a single  
No  
Suitable  
Yes  
furnace?  
suitability  
Install chimney  
adapter per  
instructions.  
No  
Chimney is  
acceptable for use.  
A03206  
Fig. 33 -- Chimney Inspection Chart  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To prevent condensation in the furnace and vent system, the  
following precautions must be observed:  
!
CAUTION  
1. The return--air temperature must be at least 60_F  
(16_C)db except for brief periods of time during warm--up  
from setback at no lower than 55_F (13_C) db or during  
initial start--up from a standby condition.  
2. Adjust the gas input rate per the installation instructions.  
Low gas input rate causes low vent gas temperatures,  
causing condensation and corrosion in the furnace and/or  
venting system. Derating is permitted only for altitudes  
above 2000 ft. (610 M).  
3. Adjust the air temperature rise to the midpoint of the rise  
range or slightly above. Low air temperature rise can cause  
low vent gas temperature and potential for condensation  
problems.  
CUT HAZARD  
Failure to follow this caution may result in personal injury.  
Sheet metal parts may have sharp edges or burrs. Use care  
and wear appropriate protective clothing, safety glasses and  
gloves when handling parts and servicing furnaces.  
3. Orient the door to determine the correct location of the  
door cutout to be removed.  
4. Use aviation--type tin snips to remove the correct  
U--shaped cut--out in door.  
NOTE: If this furnace is equipped with knockouts in the door  
for the vent, a number of techniques can be used to remove these  
knockouts as seen in Fig. 47 through 51. The knockout in the  
bottom of the door is unique due to its flanging and is not easily  
removed by first cutting the two tie points at the edge of the door,  
using aviation--type tin snips. (See Fig. 47.) A sharp blow to the  
rounded end of the knockout (See Fig. 48.) will separate more tie  
points and allow the knockout to be pulled loose. (See Fig. 49.)  
Remove all burrs and sharp edges. For the knockouts in the other  
locations on the door (top and sides), tin snips can also be used  
along the door edges; however, the preferred method is to use a  
hammer and screwdriver to strike a sharp blow (See Fig. 50.)  
directly to the knockout tie points or use a hammer in the upper  
left corner of the desired knockout. (See Fig. 51.) Remove all  
burrs and sharp edges.  
4. Set the thermostat heat anticipator or cycle rate to reduce  
short cycling.  
Air for combustion must not be contaminated by halogen  
compounds which include chlorides, fluorides, bromides, and  
iodides. These compounds are found in many common home  
products such as detergent, paint, glue, aerosol spray, bleach,  
cleaning solvent, salt, and air freshener, and can cause corrosion  
of furnaces and vents. Avoid using such products in the  
combustion--air supply. Furnace use during construction of the  
building could cause the furnace to be exposed to halogen  
compounds, causing premature failure of the furnace or venting  
system due to corrosion.  
Vent dampers on any appliance connected to the common vent  
can cause condensation and corrosion in the venting system. Do  
not use vent dampers on appliances common vented with this  
furnace.  
ADDITIONAL VENTING REQUIREMENTS  
!
CAUTION  
A 4” (101 mm) round vent elbow is supplied with the furnace. A  
5--inch (127 mm) or 6-- inch (152 mm) vent connector may be  
BURN HAZARD  
required for some model furnaces.  
A
field--supplied  
Failure to follow this caution may cause personal injury.  
4--inch--to--5--inch (101 -- 127 mm) or 4--inch--to--6--inch (101 --  
152 mm) sheet metal increaser fitting is required when 5--inch  
(127 mm) or 6--inch (152 mm) vent connector is used. See Fig.  
34--46 Venting Orientation for approved vent configurations.  
Hot vent pipe is within reach of small children when  
installed in downflow position. See the following  
instruction.  
NOTE: Vent connector length for connector sizing starts at  
furnace vent elbow. The 4--inch vent elbow is shipped for upflow  
configuration and may be rotated for other positions. Remove the  
3 screws that secure vent elbow to furnace, rotate furnace vent  
elbow to position desired, reinstall screws. The factory--supplied  
vent elbow does NOT count as part of the number of vent  
connector elbows.  
An accessory Vent Guard Kit, KGAVG0101DFG is REQUIRED  
for downflow applications for use where the vent exits through  
the lower portion of the furnace casing door. Refer to the Vent  
Guard Kit Instructions for complete details.  
The horizontal portion of the venting system shall slope upwards  
not less than 1/4--in. per linear ft. (21 mm/M) from the furnace to  
the vent and shall be rigidly supported every 5 ft. (2 M) or less  
with metal hangers or straps to ensure there is no movement after  
installation.  
The vent connector can exit the door through one of 5 locations  
on the door.  
1. Attach the single wall vent connector to the furnace vent  
elbow, and fasten the vent connector to the vent elbow  
with at least two field--supplied, corrosion--resistant, sheet  
metal screws located 180_ apart.  
SIDEWALL VENTING  
This furnace is not approved for direct sidewall horizontal  
venting.  
NOTE: An accessory flue extension KGAFE0112UPH is  
available to extend from the furnace elbow to outside the furnace  
casing. If flue extension is used, fasten the flue extension to the  
vent elbow with at least two field--supplied, corrosion--resistant,  
sheet metal screws located 180_ apart. Fasten the vent connector  
to the flue extension with at least two field--supplied, corrosion  
resistant sheet metal screws located 180_ apart.  
In the U.S.: Per section 12.4.3.1 of the NFPA54/ANSI  
Z223.1--2006, any listed mechanical venter may be used, when  
approved by the authority having jurisdiction.  
In Canada: Per section 8.24.2 of the CAN/CSA--B149.1--05,  
any listed venters may be used, when approved by the authority  
having jurisdiction.  
Select the listed mechanical venter to match the Btuh input of the  
furnace being vented. Follow all manufacturer’s installation  
requirements for venting and termination included with the listed  
mechanical venter.  
2. Vent the furnace with the appropriate connector as shown  
in Fig. 34--46.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SEE NOTES: 1,2,4,7,8,9  
on the page following  
these figures  
SEE NOTES:1,2,3,4,5,7,8,9  
on the page following  
these figures  
A03208  
A03210  
Fig. 34 -- Upflow Application--Vent Elbow Up  
Fig. 36 -- Downflow Application--Vent Elbow Up then Left  
SEE NOTES: 1,2,4,5,7,8,9  
on the page following  
these figures  
SEE NOTES: 1,2,3,4,7,8,9  
on the pages following  
these figures  
A03211  
A03209  
Fig. 37 -- Downflow Application--Vent Elbow Up  
Fig. 35 -- Upflow Application--Vent Elbow Right  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SEE NOTES: 1,2,4,7,8,9 on the page  
following these figures  
SEE NOTES: 1,2,4,5,6,7,8,9  
on the page following these figures  
A03207  
A03213  
Fig. 38 -- Downflow Application--Vent Elbow Left then Up  
Fig. 40 -- Horizontal Left Application--Vent Elbow Left  
SEE NOTES: 1,2,4,5,7,8,9 on the page  
following these figures  
SEE NOTES:1,2,3,4,5,7,8,9  
on the page following  
these figures.  
A03212  
A03214  
Fig. 39 -- Downflow Application--Vent Elbow Up then Right  
Fig. 41 -- Horizontal Left Application--Vent Elbow Right  
then Up  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SEE NOTES: 1,2,4,7,8,9 on the page  
following these figures  
SEE NOTES: 1,2,4,5,7,8,9 on the page  
following these figures  
A03214  
A03219  
Fig. 42 -- Horizontal Right Application--Vent Elbow Right  
Fig. 44 -- Horizontal Right Application--Vent Elbow Left  
then Up  
SEE NOTES: 1,2,4,5,7,8,9 on the page  
following these figures  
SEE NOTES: 1,2,4,5,7,8,9 on the page  
following these figures  
A03215  
A03216  
Fig. 43 -- Horizontal Left Application--Vent Elbow Up  
Fig. 45 -- Horizontal Left Application--Vent Elbow Right  
SEE NOTES: 1,2,4,5,7,8,9  
A02068  
Fig. 46 -- Horizontal Right Application--Vent Elbow Left  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Venting Notes for Figures 34--46  
1. For common vent, vent connector sizing and vent  
6. Accessory Downflow Vent Guard Kit, KGAVG0101DFG  
required in downflow installations with lower vent  
configuration.  
material: United States----use the NFGC Canada----use the  
CAN/CSA--B149.1--05  
2. Immediately increase to 5--inch (127 mm) or 6--inch (152  
mm) vent connector outside furnace casing when 5--inch  
(127 mm) vent connector is required, refer to Note 1  
above.  
7. Chimney Adapter Kit may be required for exterior  
masonry chimney applications. Refer to Chimney Adapter  
Kit, KGACA02014FC or KGACA02015FC, for sizing  
and complete application details.  
3. Side outlet vent for upflow and downflow installations  
must use Type B vent immediately after exiting the  
furnace, except when KGAVG0101DFG, Downflow Vent  
Guard Kit, is used in the downflow position.  
8. Secure vent connector to furnace elbow with (2)  
corrosion--resistant  
sheet  
metal  
screws,  
spaced  
approximately 180_ apart.  
9. Secure all other single wall vent connector joints with (3)  
corrosion resistant screws spaced approximately 120_  
apart. Secure Type--B vent connectors per vent connector  
manufacturer’s recommendations.  
4. Type--B vent where required, refer to Note 1 above.  
5. Four--inch single--wall (26 ga. min.) vent must be used  
inside furnace casing and when the KGAVG0101DFG  
Downflow Vent Guard Kit is used external to the furnace.  
A04127  
Fig. 47 -- Using Tin Snips to Cut Tie Points  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A04128  
A04130  
Fig. 48 -- Rounded End of Knockout  
Fig. 50 -- Hammer and Screwdriver Used for Knockout  
A04129  
A04131  
Fig. 49 -- Knockout Pulled Loose  
Fig. 51 -- Remove Knockout with Hammer  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START--UP, ADJUSTMENT, AND SAFETY  
!
WARNING  
CHECK  
General  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal  
injury, or death.  
!
WARNING  
Blower access door switch opens 115--v power to control.  
No component operation can occur unless switch is closed.  
Caution must be taken when manually closing this switch  
for service purposes.  
FIRE HAZARD  
Failure to follow this warning could result in personal  
injury, death and/or property damage.  
This furnace is equipped with manual reset limit switches in  
the gas control area. The switches open and shut off power  
to the gas valve if a flame rollout or overheating condition  
occurs in the gas control area. DO NOT bypass the  
switches. Correct inadequate combustion air supply  
problem before resetting the switches.  
NOTE: The furnace control allows all components, except the  
gas valve, to be run for short period of time. This feature helps  
diagnose a system problem in case of a component failure.  
Component test feature will not operate if any thermostat signal is  
present at the control.  
Component test sequence is as follows:  
Refer to service label attached to furnace or see Fig. 55.  
!
CAUTION  
a. LED will display previous status code 4 times.  
b. Inducer motor starts and continues to run until Step f of  
component test sequence.  
CUT HAZARD  
Failure to follow this caution may result in personal injury.  
c. Hot surface igniter is energized for 15 sec., then off.  
d. Blower motor operates on HEAT speed for 10 sec.  
e. Blower motor operates on COOL speed for 10 sec.  
f. Inducer motor stops.  
Sheet metal parts may have sharp edges or burrs. Use care  
and wear appropriate protective clothing, safety glasses and  
gloves when handling parts and servicing furnaces.  
g. ReconnectR lead to furnace controlboard, releaseblower  
door switch and re--install blower door.  
4. Operate furnace per instruction on door.  
1. Maintain 115--v wiring and ground. Improper polarity will  
result in rapid flashing LED and no furnace operation.  
5. Verify furnace shut down by lowering thermostat setting  
below room temperature.  
2. Make thermostat wire connections at the 24--v terminal  
block on the furnace control. Failure to make proper  
connections will result in improper operation. (See Fig.  
25.)  
6. Verify furnace restarts by raising thermostat setting above  
room temperature.  
Adjustments  
3. Gas supply pressure to the furnace must be greater than  
4.5--in. wc (0.16 psig ) but not exceed 14--in. wc (0.5  
psig).  
!
WARNING  
4. Check all manual--reset switches for continuity.  
FIRE HAZARD  
5. Install blower compartment door. Door must be in place to  
operate furnace.  
Failure to follow this warning could result in injury, death  
and/or property damage.  
6. Replace outer door.  
Start--Up Procedures  
DO NOT bottom out gas valve regulator adjusting screw.  
This can result in unregulated manifold pressure and result in  
excess overfire and heat exchanger failures.  
!
WARNING  
FIRE AND EXPLOSION HAZARD  
!
CAUTION  
Failure to follow this warning could cause personal injury,  
death and/or property damage.  
FURNACE DAMAGE HAZARD  
Never test for gas leaks with an open flame. Use a  
commercially available soap solution made specifically for  
the detection of leaks to check all connections.  
Failure to follow this caution may result in reduced furnace  
life.  
DO NOT redrill orifices. Improper drilling (burrs,  
out--of--round holes, etc.) can cause excessive burner noise  
and misdirection of burner flames. This can result in flame  
impingement of heat exchangers, causing failures. (See Fig.  
53.)  
1. Purge gas lines after all connections have been made.  
2. Check gas lines for leaks.  
3. To Begin Component Self--Test:  
Remove blower access door. Disconnect the thermostat R  
lead from the furnace control board. Manually close the  
blower door switch closed. Short (jumper) the COM--24v  
terminal on control to the TEST/TWIN 3/16--inch quick  
connect terminal on control until LED goes out  
(approximately 2 sec). Gas valve and humidifier will not  
be turned on. (See Fig. 24.)  
Furnace gas input rate on rating plate is for installations at  
altitudes up to 2000 ft. (610 M). Furnace input rate must be  
within +/--2 percent of furnace rating plate input. For altitudes  
above 5500 ft. (1676 M), a field--supplied high altitude pressure  
switch is required.  
1. Determine the correct gas input rate.  
In the U.S.A.:  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The input rating for altitudes above 2,000 ft. (610 M) must  
be reduced by 4 percent for each 1,000 ft. (305 M) above  
sea level. For installations below 2000 ft. (610 M), refer to  
the unit rating plate. For installations above 2000 ft. (610  
M), multiply the input on the rating plate by the de--rate  
multiplier in Table 8 for the correct input rate.  
adjustment tables. All models in all positions, except Low  
NOx models in downflow or horizontal positions, use  
Table 13 (22,000 Btuh/Burner).  
Low NOx models in the downflow or horizontal positions  
must use Table 14 (21,000 Btuh/Burner). See input listed  
on rating plate.  
In Canada:  
a. Obtain averageyearly gasheat value(at installed altitude)  
from local gas supplier.  
The input rating must be derated by 10 percent for  
altitudes of 2,000 ft. (610 M) to 4,500 ft. (1372 M) above  
sea level by an authorized Gas Conversion Station or  
Dealer. To determine correct input rate for altitude, see  
example 1 and use 0.90 as derate multiplier factor.  
b. Obtain average yearly gas specific gravity from local gas  
supplier.  
c. Find installation altitude in Table 13 or 14.  
d. Find closest natural gas heat value and specific gravity  
in Table 13 or 14.  
EXAMPLE 1:  
88,000 BTUH INPUT FURNACE INSTALLED AT 4300  
FT. (1310 M)  
Furnace Input  
Rate at Sea  
Level  
e. Follow heat value and specific gravity lines to point of  
intersection to find orifice size and manifold pressure  
settings for proper operation.  
X
X
Derate  
Multiplier  
Factor  
=
=
Furnace Input  
Rate at  
Installation  
f. Check and verify burner orifice size in furnace. NEVER  
ASSUME ORIFICE SIZE. ALWAYS CHECK AND  
VERIFY.  
g. Replace orifice with correct size if required by Table 10,  
12, 13, and 14. Use only factory--supplied orifices. See  
EXAMPLE 2.  
Altitude  
79,200  
0.90  
88,000  
2. Determine the correct orifice and manifold pressure  
adjustment. There are two different orifice and manifold  
Caution!! For the following applications, use the minimum vertical vent heights as specified below. For all other applications,  
follow exclusively the National Fuel Gas Code.  
MIN. VENT  
DIAMETER  
IN (MM)*  
MIN. VERTICAL VENT  
HEIGHT  
FURNACE  
ORIENTATION  
FURNACE INPUT  
(BTUH/HR)  
VENT ORIENTATION  
FT. (M)**  
Downflow  
Horizontal Left  
Horizontal Left  
Vent elbow left, then up Fig. 38  
Vent elbow right, then up Fig. 41  
Vent elbow right Fig. 42  
132,000  
132,000  
132,000  
5 (127 )  
5 (127 )  
5 (127 )  
12 (4)  
7 (2)  
7 (2)  
NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC  
*4 in. (102 mm) inside casing or vent guard  
**Including 4 in. (102 mm) vent section(s)  
Table 10 – Altitude Derate Multiplier for U.S.A.  
EXAMPLE 2: (0 to 2000 ft. (0 to 610 M) altitude)  
For 22,000 Btuh per burner application use Table 13.  
Heating value = 1000 Btuh/cu ft.  
Specific gravity = 0.62  
Therefore: Orifice No. 43*  
ALTITUDE  
(FT. / M)  
PERCENT  
OF  
DERATE  
DERATE  
MULTIPLIER  
FACTOR*  
0–2000 (0---610)  
0
8–12  
1.00  
0.90  
0.86  
0.82  
0.78  
0.74  
0.70  
0.66  
0.62  
Manifold pressure: 3.7--in. wc  
2001–3000 (610---914)  
3001–4000 (914---1219)  
4001–5000 (1219---1524)  
5001–6000 (1524---1829)  
6001–7000 (1829---2134)  
7001–8000 (2134---2438)  
8001–9000 (2438---2743)  
9001–10,000 (2743---3048)  
*Furnace is shipped with No. 43 orifices.  
In this example all main burner orifices are the correct  
size and do not need to be changed to obtain proper  
input rate.  
12–16  
16–20  
20–24  
24–28  
28–32  
32–36  
36–40  
h. Install regulator seal cap.  
i. Leave manometer or similar device connected and  
proceed to Step 4.  
NOTE: DO NOT set manifold pressure less than 3.2--in wc or  
more than 3.8--in. wc for natural gas at sea level. If manifold  
pressure is outside this range, change main burner orifices. Refer  
to Table 10, 12, 13, and 14.  
* Derate multiplier factors are based on midpoint altitude for altitude  
range.  
3. Adjust manifold pressure to obtain correct input rate.  
a. Turn gas valve ON/OFF switch to OFF.  
NOTE: If orifice hole appears damaged or it is suspected to have  
been redrilled, check orifice hole with a numbered drill bit of  
correct size. Never redrill an orifice. A burr--free and squarely  
aligned orifice hole is essential for proper flame characteristics.  
b. Remove manifold pressure tap plug from gas valve. (See  
Fig. 52.)  
c. Connect a water column manometer or similar device to  
manifold pressure tap.  
d. Turn gas valve ON/OFF switch to ON.  
e. Manually close blower door switch.  
f. Set thermostat to call for heat.  
g. Remove regulator seal cap and turn regulator adjusting  
screw counterclockwise (out) to decrease input rate of  
clockwise (in) to increase input rate.  
4. Verify natural gas input rate by clocking meter.  
NOTE: Gas valve regulator adjustment cap must be in place for  
proper input to be clocked.  
a. Turn off all other gas appliances and pilots served by the  
meter.  
b. Run furnace for 3 minutes in heating operation.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
c. Measure time (in sec) for gas meter to complete 1  
revolution and note reading. The 2 or 5 cubic feet dial  
provides a more accurate measurement of gas flow.  
d. Refer to Table 12 for cubic ft. of gas per hr.  
e. Multiply gas rate (cu ft./hr) by heating value (Btuh/cu ft.)  
to obtain input.  
If clocked rate does not match required input from Step 1,  
increase manifold pressure to increase input or decrease manifold  
pressure to decrease input. Repeat steps b through e until correct  
input is achieved. Reinstall regulator seal cap on gas valve.  
5. Set temperature rise. The furnace must operate within the  
temperature rise ranges specified on the furnace rating  
plate. Do not exceed temperature rise range specified on  
unit rating plate. Determine the temperature rise as  
follows:  
NOTE: Blower access door must be installed when taking  
temperature rise reading. Leaving blower access door off will  
result in incorrect temperature measurements.  
!
WARNING  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal injury  
or death.  
Disconnect 115--v electrical power before changing speed  
tap.  
A06666  
Fig. 52 -- Gas Control Valve  
a. Place thermometers in return and supply ducts as close  
to furnace as possible. Be sure thermometers do not see  
radiant heat from heat exchangers. Radiant heat affects  
temperature rise readings. This practice is particularly  
important with straight--run ducts.  
b. When thermometer readings stabilize, subtract return--air  
temperaturefromsupply--air temperatureto determineair  
temperature rise.  
NOTE: Blower access door must be installed for proper  
temperature rise measurement.  
NOTE: If the temperature rise is outside this range, first check:  
(1.) Gas input for heating operation.  
BURNER  
ORIFICE  
(2.) Derate for altitude if applicable.  
(3.) Return and supply ducts for excessive restrictions  
causing static pressures greater than 0.50--in. wc.  
(4.) Dirty filter.  
c. Reinstall blower access door if removed.  
d. Turn gas valve ON/OFF switch to ON.  
A93059  
Fig. 53 -- Orifice Hole  
e. Adjust air temperature rise by adjusting blower speed.  
Increase blower speed to reduce temperature rise.  
Decrease blower speed to increase temperature rise  
f. Turn thermostat down below room temperature and  
remove blower access door.  
g. To change motor speed selection for heating, remove  
blower motor lead from control HEAT terminal (SeeFig.  
24.) Select desired blower motor speed lead from one of  
the other terminals and relocate it to the HEAT terminal  
(See Table 11 for lead color identification). Reconnect  
original lead to SPARE terminal.  
!
WARNING  
FIRE HAZARD  
Failure to follow this warning could result in personal  
injury, death, and/or property damage.  
Reinstall manifold pressure tap plug in gas valve to prevent  
gas leak.  
h. Repeat steps a through e.  
i. When correct input rate and temperature rise is achieved,  
turn gas valve ON/OFF switch to OFF.  
j. Remove manometer or similar device from gas valve.  
k. Reinstall manifold pressure tap plug in gas valve.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 11 – Speed Selection  
THERMOSTAT SUBBASE  
TERMINALS WITH  
THERMOSTAT REMOVED  
(ANITICIPATOR, CLOCK, ETC.,  
MUST BE OUT OF CIRCUIT.)  
COLOR  
Gray  
SPEED  
AS SHIPPED  
COOL  
5
4
Yellow  
Blue  
Orange  
SPARE  
HOOK-AROUND  
AMMETER  
3
2
HEAT  
SPARE  
Red  
1*  
CONT FAN  
* Con tin u ou s --- bl ower speed --- as sh ipped def au l t  
R
Y
W
G
!
CAUTION  
FURNACE OVERHEATING HAZARD  
Failure to follow this caution may result in reduced furnace  
life.  
Recheck temperature rise. It must be within limits specified  
on the rating plate. Recommended operation is at the  
mid--point of rise range or slightly above.  
10 TURNS  
FROM UNIT 24-V  
CONTROL TERMINALS  
6. Set thermostat heat anticipator.  
0.5 AMPS FOR THERMOSTAT  
ANTICIPATOR SETTING  
5.0 AMPS ON AMMETER  
10 TURNS AROUND JAWS  
=
EXAMPLE:  
a. Mechanical thermostat -- Set thermostat heat anticipator  
to match the amp. draw of the electrical components in  
the R--W circuit. Accurate amp. draw readings can be  
obtained at the wires normally connected to thermostat  
subbase terminals, R and W. The thermostat anticipator  
should NOT be in the circuit while measuring current.  
A96316  
Fig. 54 -- Amp. Draw Check with Ammeter  
a. Verify vent pipe is cool to the touch.  
b. Disconnect power to furnace and remove vent connector  
from furnace vent elbow.  
c. Restore power to furnace and set room thermostat above  
room temperature.  
d. After normal start--up, allow furnace to operate for 2  
minutes, then block vent elbow in furnace 80 percent of  
vent area with a piece of flat sheet metal.  
e. Furnace should cycle off within 2 minutes. Ifgas doesnot  
shut off within 2 minutes, determine reason draft  
safeguard switch did not function properly and correct  
condition.  
(1.) Remove thermostat from subbase or from wall.  
(2.) Connect an amp. meter as shown in Fig. 54 across  
the R and W subbase terminals or R and W wires at  
wall.  
(3.) Record amp. draw across terminals when furnace is  
in heating and after blower starts.  
(4.) Set heat anticipator on thermostat per thermostat  
instructions and install on subbase or wall.  
b. Electronic thermostat: Set cycle rate for 4 cycles per hr.  
7. Adjust blower off delay The blower off delay has 4  
adjustable settings from 90 sec to 180 sec. The blower off  
delay jumpers are located on the furnace control board.  
(See Fig. 24.)  
f. Remove blockage from furnace vent elbow.  
g. Switch will auto--reset when it cools.  
h. Re--install vent connector.  
To change the blower off delay setting, move the jumper  
from one set of pins on the control to the pins used for the  
selected blower off delay. Factory off delay setting is 120  
sec.  
NOTE: Should switch remain open longer than 3 minutes,  
furnace control board will lockout the furnace for 3 hours. To  
reset furnace control board, turn thermostat below room  
temperature or from HEAT to OFF and turn 115v power OFF,  
then back ON.  
8. Set airflow CFM for cooling  
Select the desired blower motor speed lead for cooling  
airflow. See Table 5--Air Delivery--CFM (With Filter). See  
Table 11 for lead color identification.  
3. Check Pressure Switch  
This control proves operation of the draft inducer blower.  
Check Safety Controls  
a. Turn off 115--v power to furnace.  
b. Disconnect inducer motor lead wires from wire harness.  
c. Turn on 115--v power to furnace.  
The flame sensor, gas valve, and pressure switch were all checked  
in the Start--up procedure section as part of normal operation.  
1. Check Main Limit Switch(es)  
This control shuts off combustion control system and  
energizes air--circulating blower motor, if furnace  
overheats. By using this method to check limit control, it  
can be established that limit is functioning properly and  
will operate if there is a restricted duct system or motor  
failure. If limit control does not function during this test,  
cause must be determined and corrected.  
d. Set thermostat to “call for heat” and wait 1 minute. When  
pressure switch is functioning properly, hot surface  
igniter should NOT glow and control diagnostic light  
flashes a status code 32. If hot surface igniter glows when  
inducer motor is disconnected, shut down furnace  
immediately.  
e. Determine reason pressure switch did not function  
properly and correct condition.  
a. Run furnace for at least 5 minutes.  
b. Gradually block off return air with a piece of cardboard  
or sheet metal until the limit trips.  
c. Unblock return air to permit normal circulation.  
d. Burners will re--light when furnace cools down.  
f. Turn off 115--v power to furnace.  
g. Reconnect inducer motor wires, replace outer door, and  
turn on 115--v power.  
h. Blower will run for 90 sec before beginning the call  
forheat again.  
2. Check draft safeguard switch.  
The purpose of this control is to cause the safe shutdown  
of the furnace during certain blocked vent conditions.  
i. Furnace should ignite normally.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 12 – Gas Rate (Cu Ft./Hr.)  
SIZE OF TEST DIAL  
SIZE OF TEST DIAL  
2 Cu Ft.  
SECONDS  
FOR 1 REVOLUTION  
SECONDS  
FOR 1 REVOLUTION  
1
2 Cu Ft.  
5 Cu Ft.  
1 Cu Ft.  
5 Cu Ft.  
Cu Ft.  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
360  
327  
300  
277  
257  
240  
225  
212  
200  
189  
180  
171  
164  
157  
150  
144  
138  
133  
129  
124  
120  
116  
113  
109  
106  
103  
100  
97  
95  
92  
90  
88  
86  
84  
82  
80  
78  
76  
75  
73  
720  
655  
600  
555  
514  
480  
450  
424  
400  
379  
360  
343  
327  
313  
300  
288  
277  
267  
257  
248  
240  
232  
225  
218  
212  
206  
200  
195  
189  
185  
180  
176  
172  
167  
164  
160  
157  
153  
150  
147  
1800  
1636  
1500  
1385  
1286  
1200  
1125  
1059  
1000  
947  
900  
857  
818  
783  
750  
720  
692  
667  
643  
621  
600  
581  
563  
545  
529  
514  
500  
486  
474  
462  
450  
439  
429  
419  
409  
400  
391  
383  
375  
367  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
62  
64  
66  
68  
70  
72  
74  
76  
78  
80  
82  
84  
86  
88  
90  
92  
94  
96  
72  
71  
69  
68  
67  
65  
64  
63  
62  
61  
60  
58  
56  
54  
53  
51  
50  
48  
47  
46  
45  
44  
43  
42  
41  
40  
39  
38  
38  
37  
36  
35  
35  
34  
33  
33  
32  
31  
30  
144  
141  
138  
136  
133  
131  
129  
126  
124  
122  
120  
116  
112  
109  
106  
103  
100  
97  
95  
92  
90  
88  
86  
84  
82  
80  
78  
76  
75  
74  
72  
71  
69  
68  
67  
65  
64  
62  
360  
355  
346  
340  
333  
327  
321  
316  
310  
305  
300  
290  
281  
273  
265  
257  
250  
243  
237  
231  
225  
220  
214  
209  
205  
200  
196  
192  
188  
184  
180  
178  
173  
170  
167  
164  
161  
155  
150  
98  
100  
102  
104  
106  
108  
110  
112  
116  
120  
60  
Checklist  
1. Put away tools and instruments. Clean up debris.  
2. Verify that blower OFF--DELAY time is selected as  
desired.  
3. Verify that blower and burner access doors are properly  
installed.  
4. Cycle test furnace with room thermostat.  
5. Check operation of accessories per manufacturer’s  
instructions.  
6. Review User’s Guide with owner.  
7. Attach literature packet to furnace.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 13 – Orifice Size* and Manifold Pressure (In. wc) for Gas Input Rate  
A08220  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 13 -- Orifice Size* and Manifold Pressure (In. wc) for Gas Input Rate (CONT)  
A08220A  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE AND MAINTENANCE  
PROCEDURES  
The electrical ground and polarity for 115--v wiring must be  
properly maintained. Refer to Fig. 25 for field wiring information  
and to Fig. 59 for furnace wiring information.  
!
WARNING  
FIRE, INJURY, OR DEATH HAZARD  
NOTE: If the polarity is not correct, the STATUS LED on the  
control will flash rapidly and prevent the furnace from heating.  
The control system also requires an earth ground for proper  
operation of the control and flame--sensing electrode.  
Failure to follow this warning could result in personal  
injury, death and/or property damage.  
The ability to properly perform maintenance on this  
equipment requires certain knowledge, mechanical skills,  
tools, and equipment. If you do not possess these, do not  
attempt to perform any maintenance on this equipment  
other than those procedures recommended in the User’s  
Manual.  
The 24--v circuit contains an automotive--type, 3--amp.. fuse  
located on the control. (See Fig. 24.) Any shorts of the 24--v  
wiring during installation, service, or maintenance will cause this  
fuse to blow. If fuse replacement is required, use ONLY a 3--amp.  
fuse. The control LED will display status code 24 when fuse  
needs to be replaced.  
Proper instrumentation is required to service electrical controls.  
The control in this furnace is equipped with a Status Code LED  
(Light--Emitting Diode) to aid in installation, servicing, and  
troubleshooting. It can be viewed through the sight glass in  
blower access door. The furnace control LED is either ON  
continuously, rapid flashing, or a code composed of 2 digits. The  
first digit is the number of short flashes, the second digit is the  
number of long flashes.  
!
WARNING  
ELECTRICAL SHOCK, FIRE OR EXPLOSION  
HAZARD  
Failure to follow this warning could result in personal  
injury or death, or property damage.  
Before servicing, disconnect all electrical power to furnace.  
Verify proper operation after servicing.  
For an explanation of status codes, refer to service label located  
on blower access door or Fig. 55 and the troubleshooting guide  
which can be obtained from your distributor.  
See Fig. 60, a brief Troubleshooting Guide.  
For Controls With an Amber LED  
The stored status code will not be erased from the control  
memory, if 115-- or 24--v power is interrupted.  
!
CAUTION  
ELECTRICAL OPERATION HAZARD  
1. To retrieve status code, proceed with the following:  
NOTE: NO thermostat signal may be present at control, and all  
blower--OFF delays must be completed.  
Failure to follow this caution may result in improper  
furnace operation or failure of furnace.  
Label all wires prior to disconnection when servicing  
controls. Wiring errors can cause improper and dangerous  
operation.  
a. Leave 115--v power to furnace turned on.  
b. Remove outer access door.  
c. Look into blower access door sight glass for current LED  
status. Removing blower access door will open blower  
access door switch and terminate 115--v power to control  
so that status code is not displayed.  
INTRODUCTION  
GENERAL  
These instructions are written as if the furnace is installed in an  
upflow application. An upflow furnace application is where the  
blower is located below the combustion and controls section of  
the furnace, and conditioned air is discharged upward. Since this  
furnace can be installed in any of the 4 positions shown in Fig. 4,  
you must revise your orientation to component location  
accordingly.  
d. BRIEFLY remove insulated terminal wire from the draft  
safeguard (DSS) switch until LED goes out, then  
reconnect it.  
NOTE: If wire to LS or DSS is disconnected longer than 4 sec,  
main blower starts, and retrieval request is ignored.  
2. When above items have been completed, the LED flashes  
status code 4 times. Record this status code for further  
troubleshooting.  
ELECTRICAL CONTROLS AND WIRING  
3. Check LED status. If no previous faults in history, control  
will flash status code 11.  
!
CAUTION  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
There may be more than one electrical supply to the  
furnace. Check accessories and cooling unit for additional  
electrical supplies that must be shut off during furnace  
servicing.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 14 – Orifice Size* And Manifold Pressure (In. wc) For Gas Input Rate  
A08221  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 14-- Orifice Size* And Manifold Pressure (In. wc) For Gas Input Rate (CONT)  
A08221A  
SERVICE  
If status code recall is needed, briefly remove then reconnect one main limit wire to display stored status code. On RED LED boards do not remove power or blower door before initiating status code recall. After  
status code recall is completed component test will occur.  
LED CODE  
STATUS  
CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2.  
CONTINUOUS ON - Control has 24VAC power.  
RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions.  
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.  
11 NO PREVIOUS CODE - Stored status code is erased automatically after 72 hours. On  
RED LED boards stored status codes can also be erased when power  
(115 VAC or 24 VAC) to control is interrupted.  
31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than five minutes,  
inducer shuts off for 15 minutes before retry. Check for: - Excessive wind  
- Proper vent sizing  
- Defective inducer motor  
12 BLOWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for 90 seconds,  
if unit is powered up during a call for heat (R-W closed) or R-W opens during blower  
on-delay.  
- Low inducer voltage (115VAC)  
- Inadequate combustion air supply  
- Low inlet gas pressure (if LGPS used)  
- Defective pressure switch  
- Disconnected or obstructed pressure tubing  
- Restricted vent  
13 LIMIT CIRCUIT LOCKOUT - Lockout occurs if the limit, draft safeguard, flame rollout, or  
blocked vent switch (if used) is open longer than 3 minutes.  
If it opens during blower on-delay period, blower will come on for the selected blower  
off-delay.  
- Control will auto reset after three hours.  
- Refer to #33.  
33 LIMIT CIRCUIT FAULT - Indicates a limit, draft safeguard, flame rollout, or blocked vent  
switch (if used) is open. Blower will run for 4 minutes or until open switch remakes  
whichever is longer. If open longer than 3 minutes, code changes to lockout #13.  
If open less than 3 minutes status code #33 continues to flash until blower shuts off.  
14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.  
21 GAS HEATING LOCKOUT - Control will NOT auto reset.  
Check for: - Mis-wired gas valve  
-Defective control (valve relay)  
22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is de-  
energized. Inducer will run until fault is cleared. Check for: - Leaky gas valve  
- Stuck-open gas valve  
Flame rollout switch and BVSS require manual reset. Check for:  
- Restricted vent  
- Excessive wind  
- Proper vent sizing  
- Loose blower wheel.  
- Dirty filter or restricted duct system.  
23 PRESSURE SWITCH DID NOT OPEN Check for:  
- Defective blower motor or capacitor. - Defective switch or connections.  
- Inadequate combustion air supply (Flame Roll-out Switch open).  
- Obstructed pressure tubing.  
- Pressure switch stuck closed.  
24 SECONDARY VOLTAGE FUSE IS OPEN Check for:  
- Short circuit in secondary voltage (24VAC) wiring.  
34 IGNITION PROVING FAILURE - Control will try three more times before lockout #14  
occurs. If flame signal lost during blower on-delay period, blower will come on for the  
selected blower off-delay. Check for: - Flame sensor must not be grounded  
- Oxide buildup on flame sensor (clean with fine steel wool).  
COMPONENT TEST  
- Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal).  
To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R"  
thermostat lead. Briefly short the TEST/TWIN terminal to the "Com 24V" terminal. Status LED  
will flash code and then turn ON the inducer motor. The inducer motor will run for the entire  
component test. The hot surface ignitor, blower motor fan speed (on AMBER LED boards  
only) blower motor-heat speed, and blower motor-cool speed will be turned ON for 10-15  
seconds each. Gas Valve and Humidifier will not be turned on.  
- Gas valve defective or gas valve turned off  
- Manual valve shut-off  
- Defective Hot Surface Ignitor  
- Low inlet gas pressure  
- Control ground continuity  
- Inadequate flame carryover or rough ignition  
- Green/Yellow wire MUST be connected to furnace sheet metal  
45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour lockout due to;  
- Gas valve relay stuck open  
- Flame sense circuit failure  
- Software check error  
Reset power to clear lockout. Replace control if status code repeats.  
327596-101 REV. B  
A04223  
Fig. 55 -- Service Label  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CARE AND MAINTENANCE  
4. Inspect burner compartment before each heating season  
for rust, corrosion, soot or excessive dust. If necessary,  
have furnace and burner serviced by a qualified service  
agency.  
!
WARNING  
5. Inspect the vent pipe/vent system before each heating  
season for rust, corrosion, water leakage, sagging pipes or  
broken fittings. Have vent pipes/vent system serviced by a  
qualified service agency.  
FIRE OR EXPLOSION HAZARD  
Failure to follow this warning could result in personal  
injury, death and/or property damage.  
Never store anything on, near, or in contact with the  
furnace, such as:  
6. Inspect any accessories attached to the furnace such as a  
humidifier or electronic air cleaner. Perform any service or  
maintenance to the accessories as recommended in the  
accessory instructions.  
1. Spray or aerosol cans, rags, brooms, dust mops,  
vacuum cleaners, or other cleaning tools.  
2. Soap powders, bleaches, waxes or other cleaning  
compounds, plastic or plastic containers, gasoline,  
kerosene, cigarette lighter fluid, dry cleaning fluids,  
or other volatile fluids.  
3. Paint thinners and other painting compounds, paper  
bags, or other paper products.  
CLEANING AND/OR REPLACING AIR FILTER  
The air filter arrangement will vary depending on the application.  
The filter is exterior to the furnace casing.  
NOTE: If the filter has an airflow direction arrow, the arrow  
must point towards the blower.  
Table 15 – Filter Size Information (In. / mm)  
For continuing high performance and to minimize possible  
equipment failure, periodic maintenance must be performed on  
this equipment. Consult your local dealer about proper frequency  
of maintenance and the availability of a maintenance contract.  
FURNACE  
FILTER SIZE (In. / mm)  
CASING  
FILTER TYPE  
WIDTH  
In. (mm)  
Side Return  
Bottom Return  
14---1/2  
(368)  
17---1/2  
(445)  
16 x 25 x 3/4  
14 x 25 x 3/4  
Washable*  
Washable*  
Washable*  
Washable*  
(406 x 635 x 19)  
(356 x 635 x 19)  
!
WARNING  
16 X 25 X 3/4  
(406 x 635 x 19)  
16 x 25 x 3/4  
(406 x 635 x 19)  
16 x 25 x 3/4  
(406 x 635 x 19)  
16 X 25 X 3/4  
(406 x 635 x 19)  
20 X 25 X 3/4  
(508 x 635 x 19)  
24 X 25 X 3/4  
(610 x 635 x 19)  
ELECTRICAL SHOCK AND FIRE HAZARD  
21 (533)  
Failure to follow this warning could result in personal  
injury, death or property damage.  
24 (610)  
Turn off the gas and electrical supplies to the unit before  
performing any maintenance or service. Follow the  
operating instructions on the label attached to the  
furnace.  
* Recommended  
Media cabinet filter procedures :  
NOTE: Media cabinet is included with single--stage deluxe  
furnace.  
1. Turn off electrical supply to furnace before removing filter  
access door.  
!
2. Remove filter cabinet door.  
3. Slide filter out of cabinet.  
4. If equipped with permanent, washable 3/4--in. (19 mm) fil-  
ter, clean filter by spraying cold tap water through filter in  
opposite direction of airflow. Rinse filter and let dry.  
Oiling or coating of the filter is not recommended. See  
Table 15 for size information.  
WARNING  
CARBON MONOXIDE POISONING AND  
FIRE HAZARD  
Failure to follow this warning could result in personal  
injury, death and/or property damage.  
Never operate unit without a filter or with filter access door  
removed.  
5. If equipped with factory--specified disposable media filter,  
replace only with media filter having the same part  
number and size. For expandable replacement media, refer  
to the instructions included with the replacement media. If  
equipped with accessory KGAFR0301ALL external filter  
rack, See Table 15.  
!
CAUTION  
CUT HAZARD  
6. Slide filter into cabinet.  
Failure to follow this caution may result in personal injury.  
7. Replace filter cabinet door.  
8. Turn on electrical supply to furnace.  
BLOWER MOTOR AND WHEEL  
Sheet metal parts may have sharp edges or burrs. Use care  
and wear appropriate protective clothing, safety glasses and  
gloves when handling parts and servicing furnaces.  
!
WARNING  
The minimum maintenance on this furnace is as follows:  
ELECTRICAL SHOCK HAZARD  
1. Check and clean/replace air filter each month or more  
frequently if required. Replace if torn.  
Failure to follow this warning could result in personal injury  
or death.  
2. Check blower motor and wheel for cleanliness each  
heating and cooling season. Clean as necessary.  
Blower access door switch opens 115--v power to control.  
No component operation can occur unless switch is closed.  
Caution must be taken when manually closing this switch  
for service purposes.  
3. Check electrical connections for tightness and controls for  
proper operation each heating season. Service as  
necessary.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: The blower wheel should not be dropped or bent as  
balance will be affected. The following steps should be performed  
by a qualified service agency.  
!
CAUTION  
UNIT DAMAGE HAZARD  
To ensure long life and high efficiency, clean accumulated dirt  
and grease from blower wheel and motor annually.  
The inducer and blower motors are pre--lubricated and require no  
additional lubrication. These motors can be identified by the  
absence of oil ports on each end of the motor.  
Clean blower motor and wheel as follows:  
1. Turn off electrical supply to furnace.  
Failure to follow this caution may result in shortened heat  
exchanger life.  
Heating fan speed(s) MUST be adjusted to provide proper  
air temperature rise as specified on the rating plate.  
Recommended operation is at the midpoint of the rise range  
or slightly above. Refer to “SET TEMPERATURE RISE”  
under START--UP, ADJUSTMENT, and SAFETY  
CHECK.  
2. Loosen the thumbscrew on outer door and remove outer  
door.  
3. For downflow or horizontal furnaces having vent pipes  
within the furnace that pass in front of the blower access  
door:  
NOTE: Refer to Table 11 for motor speed lead relocation if  
leads were not identified before disconnection.  
a. Disconnect vent connector from furnace vent elbow.  
17. Reconnect blower leads to furnace control. Refer to  
furnace wiring diagram, and connect thermostat leads if  
previously disconnected.  
b. Disconnect and remove short piece of vent pipe from  
within furnace.  
18. To check blower for proper rotation:  
a. Turn on electrical supply.  
4. Remove two screws from blower access door and remove  
blower access door.  
5. Disconnect both harness connectors from blower motor  
instead of at the circuit board. This reduces the chances of  
a miswire when reconnecting wiring. The connectors are  
polarized to prevent connection in the wrong orientation.  
!
WARNING  
ELECTRICAL SHOCK HAZARD  
6. Remove two screws holding control box to blower shelf.  
7. Hang control box from front of furnace casing and away  
from blower compartment.  
8. Remove two screws holding blower assembly to blower  
deck and slide blower assembly out of furnace.  
9. Clean blower wheel and motor using a vacuum with soft  
brush attachment. Blower wheel blades may be cleaned  
with a small paint or flux brush. Do not remove or disturb  
balance weights (clips) on blower wheel blades.  
Failure to follow this warning could result in personal  
injury, or death.  
Blower access door switch opens 115--v power to  
furnace control. No component operation can occur  
unless switch is closed. Exercise caution to avoid  
electrical shock from exposed electrical components  
when manually closing this switch for service purposes.  
b. Manually close blower access door switch.  
10. Vacuum any loose dust from blower housing, wheel and  
motor.  
NOTE: If thermostat terminals are jumpered at the time blower  
access door switch is closed, blower will run for 90 sec before  
beginning a heating or cooling cycle.  
11. If a greasy residue is present on blower wheel, remove  
wheel from the blower housing and wash it with an  
appropriate degreaser. To remove wheel:  
c. Perform component self--test as shown at the bottom of  
the SERVICE label, located on the front of blower access  
door.  
NOTE: Before disassembly, mark blower motor, and blower  
housing so motor and each arm is positioned at the same location  
during reassembly.  
d. Verify blower is rotating in the correct direction.  
19. If furnace is operating properly, RELEASE BLOWER  
ACCESS DOOR SWITCH. Remove any jumpers or  
reconnect any disconnected thermostat leads. Replace  
blower access door.  
a. Disconnect power choke wires (if used) and ground wire  
attached to blower housing.  
b. Remove screws securing cutoff plate and remove cutoff  
plate from housing.  
c. Loosen set screw holding blower wheel on motor shaft  
(160+/--20 in.--lb. when reassembling).  
d. Remove bolts holding motor to blower housing and slide  
motor out of wheel (40+/--10in.--lb. whenreassembling).  
e. Remove blower wheel from housing.  
f. Clean wheel and housing.  
20. Downflow or horizontal furnaces with vent pipe through  
furnace only:  
a. Install and connect short piece of vent pipe inside furnace  
to existing vent.  
b. Connect vent connector to vent elbow.  
21. Reinstall casing door.  
22. Turn on gas supply and cycle furnace through one  
complete heating and cooling cycle. Verify the furnace  
temperature rise as shown in “Adjustments” Section.  
Adjust temperature rise as shown in “Adjustments”  
Section. If outdoor temperature is below 70_F, (21_C)  
turn off circuit breaker to outdoor unit before running  
furnace in the cooling cycle. Turn outdoor circuit breaker  
on after completing cooling cycle.  
12. Reassemble motor and blower by reversing steps 11f  
through 11a, finishing with 11a. Be sure to reattach  
ground wire to the blower housing.  
13. Verify that blower wheel is centered in blower housing  
and set screw contacts the flat portion of the motor shaft.  
Loosen set screw on blower wheel and reposition if  
necessary.  
14. Spin the blower wheel by hand to verify that the wheel  
does not rub on the housing.  
CLEANING HEAT EXCHANGER  
The following steps should be performed by a qualified  
service agency:  
15. Reinstall blower assembly in furnace.  
16. Reinstall control box assembly in furnace.  
NOTE: If the heat exchangers get a heavy accumulation of soot  
and carbon, they should be replaced rather than trying to clean  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
them thoroughly. A heavy build--up of soot and carbon indicates  
that a problem exists which needs to be corrected, such as  
improper adjustment of manifold pressure, insufficient or poor  
quality combustion air, incorrect size or damaged manifold  
orifice( s), improper gas, or a restricted heat exchanger. Action  
must be taken to correct the problem.  
9/32”  
7.1mm  
5/16”  
7.9mm  
If it becomes necessary to clean the heat exchangers because of  
dust or corrosion, proceed as follows:  
1. Turn OFF gas and electrical power to furnace.  
2. Remove outer access door.  
3. Disconnect vent connector from furnace vent elbow.  
4. For downflow or horizontal furnace having an internal  
vent pipe, remove internal vent pipe within the casing.  
5. Disconnect wires to the following components. Mark  
wires to aid in reconnection of (be careful when  
disconnecting wires from switches because damage may  
occur):  
A05025  
a. Draft safeguard switch.  
b. Inducer motor.  
Fig. 56 -- Igniter Position--Side View  
c. Pressure switch(es).  
d. Limit overtemperature switch.  
e. Gas valve.  
f. Hot surface igniter.  
g. Flame--sensing electrode.  
h. Flame rollout switches.  
1-7/8  
47.6 mm  
6. Remove screws that fasten the collector box assembly to  
the cell panel. Be careful not to damage the collector box.  
Inducer assembly and elbow need not be removed from  
collector box.  
7. Disconnect gas line from gas manifold.  
A05026  
8. Remove the 5 screws that attach the burner assembly to  
the cell panel. The gas valve and individual burners need  
not be removed from support assembly. Remove NOx  
baffles if installed.  
Fig. 57 -- Igniter Position--Top View  
NOTE: The materials needed in item 9 can usually be purchased  
at local hardware stores.  
NOTE: Be very careful when removing burner assembly to  
avoid breaking igniter. See Fig. 56 and 57 for correct igniter  
location.  
(1.) Attach variable--speed, reversible drill to the end of  
spring cable (end opposite brush).  
(2.) Insert brush end of cable into the outlet opening of  
cell and slowly rotate with drill. DO NOT force  
cable. Gradually insert cable into upper pass of cell.  
(See Fig. 58.)  
(3.) Work cable in and out of cell 3 or 4 times to obtain  
sufficient cleaning. DO NOT pull cable with great  
force. Reverse drill and gradually work cable out.  
9. Using field--provided 25--caliber rifle cleaning brush,  
36--in. (914 mm) long, 1/4” (6 mm) diameter steel spring  
cable, a variable speed, reversible electric drill, and  
vacuum cleaner, clean cells as follows:  
a. Remove metal screw fitting from wire brush to allow  
insertion into cable.  
b. Insert the twisted wire end of brush into end of spring  
cable, and crimp tight with crimping tool or crimp by  
striking with ball--peen hammer. TIGHTNESS IS VERY  
IMPORTANT.  
(4.) Insert brush end of cable in burner inlet opening of  
cell, and proceed to clean 2 lower passes of cell in  
same manner as upper pass.  
(5.) Repeat foregoing procedures until each cell in  
furnace has been cleaned.  
(6.) Using vacuum cleaner, remove residue from each  
cell.  
(7.) Using vacuum cleaner with soft brush attachment,  
clean burner assembly.  
(8.) Clean flame sensor with fine steel wool.  
(9.) Install NOx baffles (if removed).  
(10.) Reinstall burner assembly. Center burners in cell  
openings.  
10. Remove old sealant from cell panel and collector box  
flange.  
11. Spray releasing agent on the heat exchanger cell panel  
where collector box assembly contacts cell panel.  
NOTE: A releasing agent such as cooking spray or equivalent  
(must not contain corn or canola oil, aromatic or halogenated  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
hydrocarbons or inadequate seal may occur) and RTV sealant  
(G.E. 162, 6702, or Dow--Corning 738) are needed before  
starting installation. DO NOT substitute any other type of RTV  
sealant. G.E. 162 (P771--9003) is available through RCD in 3--oz.  
tubes.  
sequence of operation through the different modes. Read and  
follow the wiring diagram very carefully.  
NOTE: If a power interruption occurs during a call for heat (W),  
the control will start a 90--second blower--only ON period two  
seconds after power is restored, if the thermostat is still calling for  
gas heating. The Amber LED light will flash code 12 during the  
90--second period, after which the LED will be ON continuous,  
as long as no faults are detected. After the 90--second period, the  
furnace will respond to the thermostat normally.  
12. Apply new sealant to flange of collector box and attach to  
cell panel using existing screws, making sure all screws  
are secure.  
13. Reconnect wires to the following components. (Use  
connection diagram on wiring label, if wires were not  
marked for reconnection locations.):  
The blower door must be installed for power to be conducted  
through the blower door interlock switch ILK to the furnace  
control CPU, transformer TRAN, inducer motor IDM, blower  
motor BLWM, hot--surface igniter HSI, and gas valve GV.  
a. Draft safeguard switch.  
b. Inducer motor.  
1. Heating  
c. Pressure switch(es).  
(See Fig. 25 for thermostat connections.)  
The wall thermostat “calls for heat,” closing the R--to--W  
circuit. The furnace control performs a self--check, verifies  
the pressure switch contacts PRS are open, and starts the  
inducer motor IDM.  
a. Inducer Prepurge Period-- As the inducer motor IDM  
comesup to speed, thepressureswitch contacts PRS close  
to begin a 15--second prepurge period.  
d. Limit over--temperature switch.  
e. Gas valve.  
f. Hot surface igniter.  
g. Flame--sensing electrode.  
h. Flame rollout switches.  
i. Install NOx baffles (if removed).  
14. Reinstall internal vent pipe, if applicable.  
b. Igniter Warm--Up-- At the end of the prepurge period,  
the Hot--Surface igniter HSI is energized for a 17--second  
igniter warm--up period.  
c. Trial--for--Ignition Sequence-- When the igniter  
warm--up period is completed, the main gas valve relay  
contacts GVR close to energize the gas valve GV, the gas  
valve opens, and 24 vac power is supplied for a  
field--installed humidifier at the HUM terminal. The gas  
valve GV permits gas flow to the burners where it is  
ignited by the HSI. Five seconds after the GVR closes,  
a 2--second flame proving period begins. The HSI igniter  
will remain energized until the flame is sensed or until the  
2--second flame proving period begins.  
d. Flame--Proving-- When the burner flame is proved at the  
flame--proving sensor electrode FSE, the furnace control  
CPU begins the blower--ON delay period and continues  
to hold the gas valve GV open. If the burner flame is not  
proved within two seconds, the control CPU will close  
the gas valve GV, and the control CPU will repeat the  
ignition sequence for up to three more  
Trials--For--Ignition before going to Ignition--Lockout.  
Lockout will be reset automatically after three hours or  
by momentarily interrupting 115 vac power to the  
furnace, or by interrupting 24 vac power at SEC1 or  
SEC2 to the furnace control CPU (not at W, G, R, etc.).  
If flame is proved when flame should not be present, the  
furnace control CPU will lock out of Gas--Heating mode  
and operate the inducer motor IDM until flame is no  
longer proved.  
A91252  
Fig. 58 -- Cleaning Heat Exchanger Cell  
15. Reinstall vent connector on furnace vent elbow. Securely  
fasten vent connector to vent elbow with 2 field--supplied,  
corrosion--resistant, sheet metal screws located 180_ apart.  
16. Replace blower access door only, if it was removed.  
17. Set thermostat above room temperature and check furnace  
for proper operation.  
18. Verify blower airflow and speed changes between heating  
and cooling.  
19. Check for gas leaks.  
20. Replace outer access door.  
e. Blower--On Delay-- If the burner flame is proven, the  
blower motor is energized on HEAT speed 25 seconds  
after the gas valve GV is energized.  
Simultaneously, the electronic air cleaner terminal  
EAC--1 is energized and remains energized as long as the  
blower motor BLWM is energized.  
!
WARNING  
FIRE OR EXPLOSION HAZARD  
Failure to follow this warning could result in personal injury,  
death and/or property damage.  
Never purge a gas line into a combustion chamber. Never  
test for gas leaks with an open flame. Use a commercially  
available soap solution made specifically for the detection of  
leaks to check all connections.  
f. Blower--Off Delay-- When the thermostat is satisfied, the  
R--to--W circuit is opened, de--energizing the gas valve  
GV, stopping gas flow to the burners, and de--energizing  
the humidifier terminal HUM. The inducer motor IDM  
will remain energized for a 5--second post--purge period.  
The blower motor BLWM and air cleaner terminal  
EAC--1 will remain energized for 90, 120, 150, or 180  
seconds (depending on theblower--OFF delayselection).  
The furnace control CPU is factory--set for a 120--second  
blower--OFF delay.  
Sequence of Operation  
NOTE: Furnace control must be grounded for proper operation  
or control will lock out. Control is grounded through  
green/yellow wire routed to gas valve and manifold bracket  
screw. Using the schematic diagram in Fig. 59, follow the  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Cooling Mode  
c. When the “call for cooling” is satisfied and there is a  
demand for dehumidification, the cooling blower--off  
delay is decreased from 90 seconds to 5 seconds.  
The thermostat “calls for cooling.”  
a. Single--Speed Cooling  
(See Fig. 25 -- 32 for thermostat connections)  
The thermostat closes the R--to--G--and--Y circuits. The  
R--to-- Y circuit starts the outdoor unit, and the  
R--to--G--and--Y/Y2 circuits start the furnace blower  
motor BLWM on COOL speed.  
The electronic air cleaner terminal EAC--1 is energized  
with 115 vacwhen theblower motorBLWM isoperating.  
When the thermostat is satisfied, the R--to--G--and--Y  
circuits are opened. The outdoor unit will stop, and the  
furnace blower motor BLWM will continue operating on  
the COOL speed for an additional 90 seconds. Jumper  
Y/Y2 to DHUM to reduce the cooling off--delay to 5  
seconds. (See Fig. 24.)  
4. Continuous Blower Mode  
When the R--to--G circuit is closed by the thermostat, the  
blower motor BLWM will operate on continuous--blower  
speed (can be adjusted to FAN, HEAT, or COOL speed) at  
the thermostat. Factory default is FAN speed. Terminal  
EAC--1 is energized as long as the blower motor BLWM is  
energized. During a call for heat, the blower BLWM will  
stop during igniter warm--up (17 seconds), ignition (7  
seconds), and blower--ON delay (25 seconds), allowing  
the furnace heat exchangers to heat up more quickly, then  
restarts at the end of the blower--ON delay period at HEAT  
speed.  
In heating, the furnace control CPU will hold the blower  
motor BLWM at HEAT speed during the selected  
blower--OFF delay period before reverting to  
continuous--blower speed. When the thermostat “calls for  
low--cooling,” the blower motor BLWM will switch to  
operate at low--cool speed (same speed as FAN). When the  
thermostat is satisfied, the blower motor BLWM will  
operate an additional 90 seconds on low--cool speed (same  
b. Two--Speed Cooling  
(See Fig. 25 -- 32 for thermostat connections.)  
The thermostat closes the R--to--G--and--Y1 circuits for  
low--cooling or closes the R--to--G--and--Y1--and--Y2  
circuits for high--cooling. The R--to--Y1 circuit starts the  
outdoor unit on low--cooling speed, and the  
R--to--G--and--Y1 circuit starts the furnace blower motor  
BLWM on low--cool speed (same speed as FAN). The  
R--to--Y1--and--Y2 circuits start the outdoor unit on  
high--cooling speed, and the R--to--Gand-- Y/Y2 circuits  
start the furnace blower motor BLWM on COOL speed.  
speed  
as  
FAN)  
before  
reverting  
back  
to  
continuous--blower speed.  
When the thermostat “calls for high--cooling”, the blower  
motor BLWM will operate at COOL speed. When the  
thermostat is satisfied, the blower motor BLWM will  
operate an additional 90 seconds on COOL speed before  
reverting back to continuous--blower speed.  
When the R--to--G circuit is opened, the blower motor  
BLWM will continue operating for an additional 5  
seconds, if no other function requires blower motor  
BLWM operation.  
Continuous Blower Speed Selection from Thermostat  
--To select different continuous--blower speeds from the  
room thermostat, momentarily turn off the FAN switch or  
pushbutton on the room thermostat for 1--3 seconds after  
the blower motor BLWM is operating. The furnace control  
CPU will shift the continuous--blower speed from the  
factory setting of FAN to HEAT speed. Momentarily  
turning off the FAN switch again at the thermostat will  
shift the continuous--blower speed from HEAT to COOL.  
Repeating the procedure will shift the continuous--blower  
speed from COOL to FAN speed. The selection can be  
changed as many times as desired and is stored in the  
memory to be automatically used following a power  
interruption.  
The electronic air cleaner terminal EAC--1 is energized  
with 115 vac whenever the blower motor BLWM is  
operating.  
When the thermostat is satisfied, the R--to--G--and--Y1 or  
R--to--G--and--Y1 and Y2 circuits are opened. The  
outdoor unit stops, and the furnace blower BLWM and  
electronic air cleaner terminal EAC--1 will remain  
energized for an additional 90 seconds. Jumper Y1 to  
DHUMtoreducethecoolingoff--delay to5 seconds.(See  
Fig. 24.)  
3. Thermidistat Mode  
(See Fig. 26--29 for Thermidistat connections.)  
The dehumidification output, DHUM on the Thermidistat  
should be connected to the furnace control thermostat  
terminal DHUM. When there is a dehumidify demand, the  
DHUM input is activated, which means 24 vac signal is  
removed from the DHUM input terminal. In other words,  
the DHUM input logic is reversed. The DHUM input is  
turned ON when no dehumidify demand exists. Once 24  
vac is detected by the furnace control on the DHUM input,  
the furnace control operates in Thermidistat mode. If the  
DHUM input is low for more than 48 hours, the furnace  
control reverts back to non--Thermidistat mode.  
The cooling operation described in item 2. above also  
applies to operation with a Thermidistat. The exceptions  
are listed below:  
a. When the R--to--G--and--Y1 circuit is closed and there is  
a demand fordehumidification, thefurnace blowermotor  
BLWM will continue running at low--cool speed (same  
speed as FAN).  
b. When the R--to--G--and--Y/Y2 circuit is closed and there  
is a demand for dehumidification, the furnace blower  
motor BLWM will drop the blower speed from COOL  
to HEAT for a maximum of 10 minutes before reverting  
back to COOL speed. If there is still a demand for  
dehumidification after 20 minutes, the furnace control  
CPU will drop the blower speed back to HEAT speed.  
This alternating 10-- minute cycle will continue as long  
as there is a call for cooling.  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Heat pump  
turn on the blower motor BLWM at HEAT speed, and  
begin a heating cycle. The blower motor BLWM will  
remain on until the end of the prepurge period, then shut  
off for 24 seconds then come back on at HEAT speed.  
When theWinput signal disappears, the furnace control  
begins a normal inducer post--purge period and the blower  
switches to COOL speed after a 3 second delay. If the  
R -- t o -- W -- a n d -- Y / Y 2 -- a n d -- G o r R -- t o -- W -- a n d -- Y 1 -- a n d --  
Y/Y2--and--G signals disappear at the same time, the  
blower motor BLWM will remain on for the selected  
blower--OFF delay period. If the R--to--W--and--Y/Y2 or  
R--to--W--and--Y1--and--Y/Y2 signals disappear, leaving  
the G signal, the blower motor BLWM will remain on for  
the selected blower--OFF delay period then switch to  
continuous blower speed.  
(See Fig. 25 -- 32 for thermostat connections.) When  
installed with  
a
heat pump, the furnace control  
automatically changes the timing sequence to avoid long  
blower off times during demand defrost cycles. When the  
R -- t o -- W -- a n d -- Y 1 o r R -- t o -- W -- a n d -- Y 1 -- a n d -- G c i r c u i t s  
are energized the furnace control CPU will switch to or  
turn on the blower motor BLWM at HEAT speed, and  
begin a heating cycle. The blower motor BLWM will  
remain on until the end of the prepurge period, then shut  
off for 24 seconds then come back on at HEAT speed.  
When the W input signal disappears, the furnace control  
begins a normal inducer post--purge period and the blower  
remains running at HEAT speed for the selected  
blower--OFF delay period then switches to low--cool  
speed  
(same  
speed  
as  
FAN).  
If  
the  
Wiring Diagrams  
R--to--W--and--Y1--and--G signals disappear at the same  
time, the blower motor BLWM will remain on for the  
selected blower--OFF delay period. If the R--to--  
W--and--Y1 signals disappear, leaving the G signal, the  
blower motor BLWM will remain on for the selected  
Refer to Fig. 59 for wiring diagram.  
Troubleshooting  
Refer to the service label. (See Fig. 55.) The Troubleshooting  
Guide (See Fig. 60) can be a useful tool in isolating furnace  
operation problems. Beginning with the word “Start,” answer  
each question and follow the appropriate arrow to the next item.  
The Guide will help to identify the problem or failed component.  
After replacing any component, verify correct operation  
sequence.  
blower--OFF  
continuous--blower speed. When the R--to--W--and--Y/Y2,  
R--to--W--and--Y/Y2--and--G, R--to--W--and--Y1--and--  
delay  
period  
then  
switch  
to  
Y / Y 2 , o r R -- t o -- W -- a n d -- Y 1 -- a n d -- Y / Y 2 -- a n d -- G c i r c u i t s  
are energized the furnace control CPU will switch to or  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A08176  
Fig. 59 -- Wiring Diagram  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A02106A  
Fig. 60 -- Troubleshooting Guide  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A05032  
Printed in U.S.A.  
Edition Date: 11/08  
Copyright 2008 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231  
Catalog No: 58PHA---03SI  
Replaces: 58PHA--02SI  
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Bertazzoni Food Warmer P24 4 00 X User Manual
Black Decker Kitchen Utensil FM1400 User Manual
Bolens Lawn Mower 112 340A User Manual
Bosch Appliances Security Camera VEZ User Manual
Briggs Stratton Switch 01813 0 User Manual
Brother Computer Drive HL 1650 1670N User Manual
Brother Fax Machine FAX 175 User Manual
Campbell Hausfeld Welder WS0900 User Manual
Cannon Camcorder XL H1 a User Manual
Chauvet Telephone Accessories CLP 15N User Manual