Allied Air Enterprises Furnace 80G1UH2V User Manual

INSTALLATION INSTRUCTIONS  
A80UH2V & 80G1UH2V  
Warm Air Gas Furnace  
Upflow / Horizontal Left and Right Air Discharge  
This manual must be left with the homeowner for future reference.  
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in  
manuals, be alert to the potential for personal injury or death.  
WARNING  
CAUTION  
Improper installation, adjustment, alteration, service or  
maintenance can cause property damage, personal injury  
or loss of life. Installation and service must be performed  
by a licensed professional installer (or equivalent), service  
agency or the gas supplier.  
As with any mechanical equipment, personal injury can  
result from contact with sharp sheet metal edges. Be  
careful when you handle this equipment.  
TABLE OF CONTENTS  
Unit Dimensions ............................................................ 2  
A80UH2V & 80G1UH2V Parts Arrangement ................ 3  
A80UH2V & 80G1UH2V Gas Furnace ......................... 4  
Shipping and Packing List ............................................ 4  
Safety Information ......................................................... 4  
Use of Furnace as a Construction Heater .................... 5  
General ......................................................................... 6  
Combustion, Dilution, Ventilation Air............................. 6  
Setting Equipment ........................................................ 9  
Filters .......................................................................... 12  
Duct System................................................................ 12  
Venting ........................................................................ 13  
Gas Piping .................................................................. 23  
Electrical ..................................................................... 25  
Thermostat .................................................................. 27  
Unit Start-Up ............................................................... 30  
Heating Sequence of Operation ................................. 31  
Gas Pressure Adjustment ........................................... 33  
High Altitude ................................................................ 34  
Other Unit Adjustments ............................................... 34  
Maintenance ............................................................... 33  
Repair Parts List ......................................................... 37  
Wiring Diagram ........................................................... 38  
Manufactured By  
Allied Air Enterprises, Inc.  
A Lennox International, Inc. Company  
215 Metropolitan Drive  
*506471-01*  
West Columbia, SC 29170  
506471-01  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 1 of 41  
EXPLODED VIEW  
HEAT EXCHANGER  
COMBUSTION AIR INDUCER  
COMBUSTIONAIR INDUCER  
PRESSURE SWITCH  
GAS VALVE  
ROLLOUT SWITCH  
BURNER BOX  
CABINET  
CONTROL BOX  
ACCESS PANEL  
BLOWER ASSEMBLY  
Figure 1  
506471-01  
Issue 1034  
Page 3 of 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A80UH2V & 80G1UH2V Gas Furnace  
The A80UH2V & 80G1UH2V gas furnace is shipped with  
ready for installation in the upflow or horizontal position (left  
or right). for horizontal left position the combustion air  
pressure switch must be moved). The furnace is shipped  
with the bottom panel in place. The bottom panel must be  
removed if the unit is to be installed in a horizontal application.  
The panel may also be removed in upflow applications.  
CAUTION  
As with any mechanical equipment, personal injury can  
result from contact with sharp sheet metal edges. Be  
careful when you handle this equipment.  
The furnace is equipped for installation in natural gas  
applications. Aconversion kit (ordered separately) is required  
for use in propane/LP gas applications.  
Certifications  
These units are CSA International certified to ANSI Z21.47.  
In the USA, installation of gas furnaces must conform with  
local building codes. In the absence of local codes, units  
must be installed according to the current National Fuel Gas  
Code (ANSI-Z223.1). The National Fuel Gas Code is  
available from the following address: American National  
Standards Institute, Inc., 11 West 42nd Street, New York,  
NY 10036.  
Shipping and Packing List  
1 - Assembled Gas Furnace  
1 - Bag assembly containing the following:  
2 - Screws  
3 - Wire nuts  
1 - Snap bushing  
1 - Snap Plug  
1 - Wire tie  
Clearances  
Adequate clearance must be made around the air openings  
into the vestibule area. In order to ensure proper unit  
operation, combustion and ventilation air supply must be  
provided according to the current National Fuel Gas Code.  
Vent installations must be consistent with the venting tables  
(in this instruction) and applicable provisions of local building  
codes.  
1 - Vent warning label  
1 - Owner’s manual and warranty card  
Check equipment for shipping damage. If you find any  
damage, immediately contact the last carrier.  
Please refer to specification sheets for available accessories.  
This furnace is CSA International certified for installation  
clearances to combustible material as listed on the unit  
nameplate and in the tables in Figures 7 and 11. Accessibility  
and service clearances must take precedence over fire  
protection clearances.  
Safety Information  
NOTE: For installation on combustible floors, the furnace  
shall not be installed directly on carpeting, tile, or other  
combustible material other than wood flooring.  
DANGER  
DANGER OF EXPLOSION!  
Installed Locations  
There are circumstances in which odorant used with  
LP/Propane gas can lose its scent. In case of a leak,  
LP/Propane gas will settle close to the floor and may be  
difficult to smell. An LP/Propane leak detector should  
be installed in all LP applications.  
For installation in a residential garage, the furnace must be  
installed so that the burner(s) and the ignition source are  
located no less than 18 inches (457 mm) above the floor.  
The furnace must be located or protected to avoid physical  
damage by vehicles. When a furnace is installed in a public  
garage, hangar, or other building that has a hazardous  
atmosphere, the furnace must be installed according to  
recommended good practice requirements and current  
National Fuel Gas Code.  
WARNING  
Improper installation, adjustment, alteration, service or  
maintenance can cause property damage, personal  
injury or loss of life. Installation and service must be  
performed by a licensed professional installer (or  
equivalent), service agency or the gas supplier.  
Page 4 of 41  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506471-01  
Temperature Rise  
This furnace may be installed in alcoves, closets, attics,  
basements, garages, and utility rooms in the upflow or  
horizontal position.  
NOTE: Furnace must be adjusted to obtain a temperature  
rise within the range specified on the unit nameplate. Failure  
to do so may cause erratic limit operation and may result in  
premature heat exchanger failure.  
This furnace design has not been certified for  
installation in mobile homes, recreational vehicles, or  
outdoors.  
This furnace must be installed so that its electrical  
components are protected from water.  
Use of Furnace as a Construction Heater  
Allied Air does not recommended the use of these units as  
a construction heater during any phase of construction. Very  
low return air temperature, harmful vapors and operation of  
the unit with clogged or misplaced filters will damage the  
unit.  
Installed in Combination with a Cooling Coil  
When this furnace is used with cooling units, it shall be  
installed in parallel with, or on the upstream side of, cooling  
units to avoid condensation in the heating compartment. See  
Figure 2. With a parallel flow arrangement, a damper (or  
other means to control the flow of air) must adequately  
prevent chilled air from entering the furnace. If the damper  
is manually operated, it must be equipped to prevent  
operation of either the heating or the cooling unit, unless it  
is in the full HEAT or COOL setting. See Figure 2.  
Units may be used for heating of buildings or structures  
under construction, if the following conditions are met:  
The vent system must be permanently installed per these  
installation instructions.  
Aroom thermostat must control the furnace. The use of  
fixed jumpers that will provide continuous heating is not  
allowed.  
Heating Unit Installed Parallel to Air Handler Unit  
The return air duct must be provided and sealed to the  
furnace.  
Return air temperature range between 60°F (16°C) and  
80°F (27°C) must be maintained.  
Air filters must be installed in the system and must be  
maintained during construction.  
Air filters must be replaced upon construction  
completion.  
Heating Unit Installed Upstream of Cooling Unit  
The input rate and temperature rise must be set per the  
furnace rating plate.  
One hundred percent (100%) outdoor air must be  
provided for combustion air requirements during  
construc-tion. Temporary ducting may supply outdoor  
air to the furnace. Do not connect duct directly to the  
furnace. Size the temporary duct following these  
instructions in section for Combustion, Dilution and  
Ventilation Air in a confined space with air from outside.  
Figure 2  
When installed, this furnace must be electrically grounded  
according to local codes. In addition, in the United States,  
installation must conform with the current National Electric  
Code,ANSI/NFPANo. 70. The National Electric Code (ANSI/  
NFPA No. 70) is available from the following address:  
National Fire Protection Association  
The furnace heat exchanger, components, duct system,  
air filters and evaporator coils must be thoroughly  
cleaned following final construction clean-up.  
1 Battery March Park  
Quincy, MA 02269  
All furnace operating conditions (including ignition, input  
rate, temperature rise and venting) must be verified  
according to these installation instructions.  
NOTE: This furnace is designed for a minimum continuous  
return air temperature of 60° F (16°C) or an intermittent  
operation down to 55° F (13°C) dry bulb for cases where a  
night setback thermostat is used. Return air temperature  
must not exceed 85° F (29°C) dry bulb.  
506471-01  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 5 of 41  
Combustion, Dilution & Ventilation Air  
General  
In the past, there was no problem in bringing in sufficient  
outdoor air for combustion. Infiltration provided all the air  
that was needed. In today’s homes, tight construction  
practices make it necessary to bring in air from outside for  
combustion. Take into account that exhaust fans, appliance  
vents, chimneys, and fireplaces force additional air that could  
be used for combustion out of the house. Unless outside  
air is brought into the house for combustion, negative  
pressure (outside pressure is greater than inside pressure)  
will build to the point that a downdraft can occur in the furnace  
vent pipe or chimney. As a result, combustion gases enter  
the living space creating a potentially dangerous situation.  
These instructions are intended as a general guide and do  
not supersede local codes in any way. Consult authorities  
having jurisdiction before installation.  
In addition to the requirements outlined previously, the  
following general recommendations must be considered  
when installing one of these furnaces:  
Place the furnace as close to the center of the air  
distribution system as possible. The furnace should also  
be located close to the chimney or vent termination point.  
Do not install the furnace where drafts might blow directly  
into it. This could cause improper combustion.  
Do not block the furnace combustion air openings with  
clothing, boxes, doors, etc. Air is needed for proper  
combustion and safe unit operation.  
In the absence of local codes concerning air for combustion  
and ventilation, use the guidelines and procedures in this  
section to install these furnaces to ensure efficient and safe  
operation. You must consider combustion air needs and  
requirements for exhaust vents and gas piping.  
When the furnace is installed in an attic or other insulated  
space, keep insulation away from the furnace.  
A portion of this information has been reprinted with  
permission from the National Fuel Gas Code (ANSI-Z223.1).  
This reprinted material is not the complete and official  
position of the ANSI on the referenced subject, which is  
represented only by the standard in its entirety.  
NOTE: The Commonwealth of Massachusetts stipulates  
these additional requirements:  
Gas furnaces shall be installed by a licensed plumber  
or fitter only.  
The gas cock must be “T handle” type.  
When a furnace is installed in an attic, the passageway  
to and service area surrounding the equipment shall be  
floored.  
WARNING  
Insufficient combustion air can cause headaches,  
nausea, dizziness or asphyxiation. It will also cause  
excess water in the heat exchanger resulting in rusting  
and premature heat exchanger failure. Excessive  
exposure to contaminated combustion air will result in  
safety and performance related problems. Avoid  
exposure to the following substances in the combustion  
air supply:  
WARNING  
Product Contains Fiberglass Wool.  
Disturbing the insulation in this product during  
installation, maintenance, or repair will expose you to  
fiberglass wool. Breathing this may cause lung cancer.  
(Fiberglass wool is known to the State of California to  
cause cancer.)  
Permanent wave solutions  
Chlorinated waxes and cleaners  
Chlorine base swimming pool chemicals  
Water softening chemicals  
De-icing salts or chemicals  
Carbon tetrachloride  
Halogen type refrigerants  
Fiberglass wool may also cause respiratory, skin, and  
eye irritation.  
Cleaning solvents (such as perchloroethylene)  
Printing inks, paint removers, varnishes, etc.  
Hydrochloric acid  
Antistatic fabric softeners for clothes dryers  
Masonry acid washing materials  
To reduce exposure to this substance or for further  
information, consult material safety data sheets available  
from address shown below, or contact your supervisor.  
Allied Air Enterprises, Inc.  
215 Metropolitan Drive  
West Columbia, SC 29170  
Page 6 of 41  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506471-01  
All gas fired appliances require air for the combustion  
process. If sufficient combustion air is not available, the  
furnace or other appliances will operate inefficiently and  
unsafely. Enough air must be provided to meet the needs  
of all fuel burning appliances and appliances such as exhaust  
fans which force air out of the house. When fireplaces,  
exhaust fans, or clothes dryers are used at the same time  
as the furnace, much more air is necessary to ensure proper  
combustion and to prevent a downdraft. Insufficient air  
causes incomplete combustion which can result in carbon  
monoxide.  
Equipment in Confined Space - All Air From Inside  
In addition to providing combustion air, fresh outdoor air  
dilutes contaminants in the indoor air. These contaminants  
may include bleaches, adhesives, detergents, solvents and  
other contaminants which can corrode furnace components.  
NOTE: Each opening shall have a free area of at least one square  
inch per 1,000 Btu (645 mm² per .29 kW) per hour of the total input  
rating of all equipment in the enclosure, but not less than 100 square  
inches (64546 mm²).  
The requirements for providing air for combustion and  
ventilation depend largely on whether the furnace is installed  
in an unconfined or a confined space.  
Figure 3  
Unconfined Space  
An unconfined space is an area such as a basement or  
large equipment room with a volume greater than 50 cubic  
feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the  
combined input rating of all appliances installed in that space.  
This space also includes adjacent rooms which are not  
separated by a door. Though an area may appear to be  
unconfined, it might be necessary to bring in outdoor air for  
combustion if the structure does not provide enough air by  
infiltration. If the furnace is located in a building of tight  
construction with weather stripping and caulking around the  
windows and doors, follow the procedures in the air from  
outside section.  
Air from Inside  
If the confined space that houses the furnace adjoins a  
space categorized as unconfined, air can be brought in by  
providing two permanent openings between the two spaces.  
Each opening must have a minimum free area of 1 square  
inch (645 mm2) per 1,000 Btu (.29 kW) per hour of total  
input rating of all gas fired equipment in the confined space.  
Each opening must be at least 100 square inches (64516  
mm2). One opening shall be within 12 inches (305 mm) of  
the top of the enclosure and one opening within 12 inches  
(305 mm) of the bottom. See Figure 3.  
Confined Space  
Air from Outside  
A confined space is an area with a volume less than 50  
cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the  
combined input rating of all appliances installed in that space.  
This definition includes furnace closets or small equipment  
rooms.  
If air from outside is brought in for combustion and ventilation,  
the confined space must have two permanent openings. One  
opening shall be within 12 inches (305 mm) of the top of the  
enclosure and one opening within 12 inches (305 mm) of  
the bottom. These openings must communicate directly or  
by ducts with the outdoors or spaces (crawl or attic) that  
freely communicate with the outdoors or indirectly through  
vertical ducts. Each opening shall have a minimum free  
area of 1 square inch (645 mm2) per 4,000 Btu (1.17 kW)  
per hour of total input rating of all equipment in the en-closure.  
See Figures 4 and 5. When communicating with the  
outdoors through horizontal ducts, each opening shall have  
a minimum free area of 1 square inch (645 mm2) per 2,000  
Btu (.56 kW) per total input rating of all equipment in the  
enclosure. See Figure 6.  
When the furnace is installed so that supply ducts carry air  
circulated by the furnace to areas outside the space  
containing the furnace, the return air must be handled by  
ducts which are sealed to the furnace casing and which  
terminate outside the space containing the furnace. This is  
especially important when the furnace is mounted on a  
platform in a confined space such as a closet or small  
equipment room. Even a small leak around the base of the  
unit at the platform or at the return air duct connection can  
cause a potentially dangerous negative pressure condition.  
Air for combustion and ventilation can be brought into the  
confined space either from inside the building or from outside.  
506471-01  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 7 of 41  
When ducts are used, they shall be of the same cross  
sectional area as the free area of the openings to which  
they connect. The minimum dimension of rectangular air  
ducts shall be no less than 3 inches (75 mm). In calculating  
free area, the blocking effect of louvers, grilles, or screens  
must be considered. If the design and free area of protective  
covering is not known for calculating the size opening  
required, it may be assumed that wood louvers will have 20  
to 25 percent free area and metal louvers and grilles will  
have 60 to 75 percent free area. Louvers and grilles must  
be fixed in the open position or interlocked with the  
equipment so that they are opened automatically during  
equipment operation.  
EQUIPMENT IN CONFINED SPACE  
(ALL AIR FROM OUTSIDE)  
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE  
(Inlet Air from Crawlspace &  
Outlet Air to Ventilated Attic)  
NOTE: Each air duct opening shall have a free area of at least one  
square inch per 2,000 Btu (645 mm² per .59 kW) per hour of the  
total input rating of all equipment in the enclosure. If the equipment  
room is located against an outside wall and the air openings  
communicate directly with the outdoors, each opening shall have a  
free area of at least 1 square inch per 4,000 Btu (645 mm² per 1.17  
kW) per hour of the total input rating of all other equipment in the  
enclosure.  
Figure 6  
NOTE: The inlet and outlet air openings shall each have a free area  
of at least one square inch per 4,000 Btu (645 mm² per 1.17 kW) per  
hour of the total input rating of all equipment in the enclosure.  
Figure 4  
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE  
(All Air through Ventilated Attic)  
NOTE: The inlet and outlet air openings shall each have a free area  
of at least one square inch per 4,000 Btu (645 mm² per 1.17 kW) per  
hour of the total input rating of all equipment in the enclosure.  
Figure 5  
Page 8 of 41  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506471-01  
Setting Equipment  
Upflow Applications  
Allow for clearances to combustible materials as indicated  
on the unit nameplate. Minimum clearances for closet or  
alcove installations are shown in Figure 8.  
WARNING  
Do not install the furnace on its front or its back. Do not  
connect the return air ducts to the back of the furnace.  
Doing so will adversely affect the operation of the safety  
control devices, which could result in personal injury or  
death.  
Upflow Application Installation Clearances  
The gas furnace can be installed as shipped in either the  
upflow position or the horizontal position.  
Select a location that allows for the required clearances that  
are listed on the unit nameplate. Also consider gas supply  
connections, electrical supply, vent connection, and  
installation and service clearances [24 inches (610 mm) at  
unit front]. The unit must be level.  
NOTE: Units with 1/2 hp blower motors are equipped with  
three flexible legs and one rigid leg. See Figure 7. The rigid  
leg is equipped with a shipping bolt and a flat white plastic  
washer (rather than the rubber mounting grommet used with  
a flexible mounting leg). The bolt and washer must be  
removed before the furnace is placed into operation. After  
the bolt and washer have been removed, the rigid leg will  
not touch the blower housing.  
Units with 1/2 HP  
Blower Motor.  
* Front clearance In alcove Installation must be 24 in. (610 mm).  
Maintain a minimum of 24 in. (610 mm) for front service access.  
‡ For installation on a combustible floor, do not install the furnace  
directly on carpeting, tile or other combustible materials other than  
wood flooring.  
† Left side requires 3 inches if a single wall vent is used on 14-1/2  
inch cabinets.  
Figure 8  
Figure 7  
506471-01  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 9 of 41  
Return Air - Upflow Applications  
Return air can be brought in through the bottom or either  
side of the furnace installed in an upflow application. If the  
furnace is installed on a platform with bottom return, make  
an airtight seal between the bottom of the furnace and the  
platform to ensure that the furnace operates properly and  
safely. The furnace is equipped with a removable bottom  
panel to facilitate installation.  
Single Side Return Air  
(with transition and filter)  
Markings are provided on both sides of the furnace cabinet  
for installations that require side return air. Cut the furnace  
cabinet at the maximum dimensions shown on page 2.  
NOTE: 20C and 20D units that require air volumes over  
1800 cfm (850 L/s) must have one of the following:  
1. Single side return air with transition to  
accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm)  
cleanable air filter. (Required to maintain proper air  
velocity.) See Figure 9.  
2. Single side return air with optional return airbase.  
See Figure 10.  
3. Bottom return air.  
Figure 9  
4. Return air from both sides.  
5. Bottom and one side return air.  
Optional Return Air Base  
(Upflow Applications Only - For use with A, B, C and D cabinets))  
FRONT VIEW  
NOTE: Optional Side Return Air Filter Kits are not for use with Return Air Base.  
1 Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.  
Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm).  
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.  
Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air opening.  
The size of the opening must not extend beyond the markings on the furnace cabinet.  
² To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.  
Figure 10  
Page 10 of 41  
Issue 1034  
506471-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Removing the Bottom Panel  
Horizontal Applications  
The furnace can be installed in horizontal applications. Order  
horizontal suspension kit (51W10) from Allied Air, or use  
equivalent suspension method.  
Remove the two screws that secure the bottom cap to the  
furnace. Pivot the bottom cap down to release the bottom  
panel. Once the bottom panel has been removed, reinstall  
the bottom cap. See Figure 11.  
Allow for clearances to combustible materials as indicated  
on the unit nameplate. Minimum clearances for closet or  
alcove installations are shown in Figure 12.  
Removing the Bottom Panel  
This furnace may be installed in either an attic or a crawl  
space. Either suspend the furnace from roof rafters or floor  
joists, as shown in Figure 13, or install the furnace on a  
platform, as shown in Figure 14.  
Typical Horizontal Application  
Unit Suspended in Attic or Crawlspace  
Figure 11  
Horizontal Application  
Installatioin clearances  
Figure 13  
NOTE: Heavy gauge perforated sheet metal straps may  
be used to suspend the unit from roof rafters or ceiling joists.  
When straps are used to suspend the unit in this way, support  
must be provided for both the ends. The straps must not  
interfere with the plenum or exhaust piping installation.  
Cooling coils and supply and return air plenums must  
be supported separately.  
NOTE: When the furnace is installed on a platform in a  
crawlspace, it must be elevated enough to avoid water  
damage and to allow the evaporator coil to drain.  
Return Air - Horizontal Applications  
Return air must be brought in through the end of a furnace  
installed in a horizontal application. The furnace is equipped  
with a removable bottom panel to facilitate installation. See  
Figure 11.  
* Front clearance in alcove installation must be 24 in. (610 mm).  
Maintain a minimum of 21 in. (610 mm) for front service access.  
‡ For installations on a combustible floor, do not install the furnace  
directly on carpeting, tile or other combustible materials other than  
wood flooring.  
Figure 12  
506471-01  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 11 of 41  
Horizontal Application  
Unit installed on Platform  
Table 1  
Duct System  
Use industry approved standards (such as those published  
by Air Conditioning Contractors of America or American  
Society of Heating, Refrigerating and Air Conditioning  
Engineers) to size and install the supply and return air duct  
system. This will result in a quiet and low static system that  
has uniform air distribution.  
Figure 14  
NOTE: Do not operate the furnace in the heating mode  
with an external static pressure that exceeds 0.8 inches w.c.  
Higher external static pressures may cause erratic limit  
operation.  
WARNING  
Improper installation of the furnace can result in personal  
injury or death. Combustion and flue products must  
never be allowed to enter the return air system or the  
living space. Use screws and joint tape to seal the return  
air system to the furnace.  
Supply Air Plenum  
If the furnace is installed without a cooling coil, a removable  
access panel must be installed in the supply air duct. The  
access panel should be large enough to permit inspection  
(either by smoke or reflected light) of the heat exchanger  
for leaks after the furnace is installed. The furnace access  
panel must always be in place when the furnace is operating  
and it must not allow leaks into the supply air duct system.  
In platform installations with bottom return air, the furnace  
should be sealed airtight to the return air plenum. A  
door must never be used as a portion of the return air  
duct system. The base must provide a stable support  
and an airtight seal to the furnace. Allow absolutely no  
sagging, cracks, gaps, etc..  
Return Air Plenum  
NOTE: Return air must not be drawn from a room where  
this furnace, or any other gas fueled appliance (i.e., water  
heater), or carbon monoxide producing device (i.e., wood  
fireplace) is installed.  
The return and supply air duct systems must never be  
connected to or from other heating devices such as a  
fireplace or stove, etc.. Fire, explosion, carbon  
monoxide poisoning, personal injury and/or property  
damage could result.  
When return air is drawn from a room, a negative pressure  
is created in the room. If a gas appliance is operating in a  
room with negative pressure, the flue products can be pulled  
back down the vent pipe and into the room. This reverse  
flow of the flue gas may result in incomplete combustion  
and the formation of carbon monoxide gas. This toxic gas  
might then be distributed throughout the house by the furnace  
duct system.  
WARNING  
The inner blower panel must be securely in place when  
the blower and burners are operating. Gas fumes,  
which could contain carbon monoxide, can be drawn  
into living space resulting in personal injury or death.  
In upflow applications, the return air can be brought in through  
the bottom or either side of the furnace. If a furnace with  
bottom return air is installed on a platform, make an airtight  
seal between the bottom of the furnace and the platform to  
ensure that the unit operates properly and safely. Use  
fiberglass sealing strips, caulking, or equivalent sealing  
method between the plenum and the furnace cabinet to  
ensure a tight seal. If a filter is installed, size the return air  
duct to fit the filter frame.  
Filters  
This unit is not equipped with a filter or rack. Afield provided  
high velocity filter is required for the unit to operate properly.  
Table 1 lists recommended filter sizes.  
A filter must be in place any time the unit is operating.  
Page 12 of 41  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506471-01  
Venting  
If necessary reposition the combustion air inducer, pressure  
switch and/or make-up box as needed per the following  
steps. See Figures 16 through 22.  
1. Remove the four mounting screws (Figure 15) which  
secure the combustion air inducer / pressure switch  
assembly to the orifice plate. Lift the assembly and rotate it  
90° clockwise or counter clockwise to either the 3 o’clock  
position or 9 o’clock position. Resecure with four secrews.  
Gasket should be left in place.  
A 4 inch diameter flue transition is factory installed on the  
combustion air inducer outlet of all models. Figure 16 shows  
the combustion air inducer as shipped from the factory.  
Mounting Screws Location  
2. Use tin snips to cut preferred opening on the cabinet for  
repositioning the flue outlet. Use the cut-out piece as a cover  
plate to patch unused opening on cabinet.  
UPFLOW POSITION  
Left Side Vent Discharge  
Figure 15  
UPFLOW POSITION  
Top Vent Discharge  
Remove make-up box assembly (2 screws) and cut wire tie to free make-  
up box wires. Reinstall make-up box on other side of cabinet.  
Resecure make-up box wires: Either pull excess wires through the blower  
companrtment and secure using supplied wire tie, or coil excess wire and  
secure to the gas manifold.  
Figure 17  
UPFLOW POSITION  
Right Side Vent Discharge  
Figure 16  
IMPORTANT  
The unit will not vent properly with the flue transition  
pointed down in the 6 o’clock position.  
The combustion air inducer may be rotated clockwise  
or counterclockwise by 90° to allow for top or side vent  
discharge in all applications. When the unit is installed,  
the flue transition must be in the 9 o’clock, 12 o’clock or  
3 o’clock position.  
Pressure switch tubing may be too long. Cut to fit, then reattach to barbed  
fitting on pressure switch. Tubing must not be allowed to sag.  
Figure 18  
506471-01  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 13 of 41  
Horizontal Position  
HORIZONTAL LEFT POSITION  
HORIZONTAL RIGHT POSITION  
Top Vent discharge  
Top Vent Discharge  
Disconnect pressure switch hose from barbed fitting on the pressure  
switch assembly. Remove pressure switch assembly (1 screw) and cut  
wire tie to free pressure switch wires. Reinstall pressure switch on the  
other side of orifice plate and reconnect pressure switch hose.  
Resecure pressure seitch wires: Either pull excess wires through the  
blower compartment and secure using supplied wire tie, or coil excess  
wire and secure to the gas manifold.  
Remove make-up box assembly (2 screws) and cut wire tie to free make-  
up box wires. Reinstall make-up box on other side of cabinet.  
Resecure make-up box wires: Either pull excess wires through the blower  
compartment and secure using supplied wire tie, or coil excess wire and  
secure to the gas manifold.  
Figure 21  
Figure 19  
HORIZONTAL LEFT POSITION  
Side Vent Discharge  
HORIZONTAL RIGHT POSITION  
Side Vent Discharge  
Disconnect pressure switch hose from barbed fitting on the pressure  
switch assembly. Remove pressure switch assembly (1 screw) and cut  
wire tie to free pressure switch wires. Reinstall pressure switch on the  
other side of orifice plate and reconnect pressure switch hose.  
Resecure pressure seitch wires: Either pull excess wires through the  
blower compartment and secure using supplied wire tie, or coil excess  
wire and secure to the gas manifold.  
Figure 22  
Figure 20  
Page 14 of 41  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506471-01  
These series units are classified as fan assisted Category I  
furnaces when vertically vented according to the latest edition  
of National Fuel Gas Code (NFPA 54 / ANSI Z223.1) in the  
USA. A fan assisted Category I furnace is an appliance  
equipped with an integral mechanical means to either draw  
or force combustion products through the combustion  
chamber and/or heat exchanger. This unit is not approved  
for use with horizontal venting.  
Use self drilling sheet metal screws or a mechanical fastener  
to firmly secure the vent pipe to the round collar of the flue  
transition. If self drilling screws are used to attach the vent  
pipe, it is recommended that three be used. Drive one self  
drilling screw through the front and one through each side  
of the vent pipe and collar. See Figure 23.  
Install the first vent connector elbow at a minimum of six  
inches (152 mm) from the furnace vent outlet. See Figure  
23.  
NOTE: Use these instructions as a guide. They do not  
supersede local codes. This furnace must be vented  
according to all local codes these installation instructions,  
and the provided venting tables in these instructions.  
Venting Using a Masonry Chimney  
The following additional requirements apply when a lined  
masonry chimney is used to vent this furnace.  
The venting tables in this manual were extracted from the  
National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are  
provided as a guide for proper vent installation. Proper  
application, termination, construction and location of vents  
must conform to local codes having jurisdiction. In the  
absence of local codes, the NFGC serves as the defining  
document.  
Masonry chimneys used to vent Category I central furnaces  
must be either tile lined or lined with a listed metal lining  
system or dedicated gas vent. Unlined masonry chimneys  
are prohibited. See Figures 24 and 25 for common venting.  
Achimney with one or more sides exposed to the outside of  
the structure is considered to be an exterior chimney.  
Refer to the tables and the venting information contained in  
these instructions to properly size and install the venting  
system.  
An exterior masonry chimney that is not tile lined must be  
lined with B1 vent or a listed insulated flexible metal vent.  
An exterior tile lined chimney that is sealed and capped may  
be lined with a listed uninsulated flexible metal vent.  
IMPORTANT  
If the existing chimney will not accommodate a listed metal  
liner, either the chimney must be rebuilt to accommodate  
one of these liners or an alternate approved venting method  
must be found.  
Insulation for the flexible vent pipe must be an encapsulated  
fiberglass sleeve recommended by the flexible vent pipe  
manufacturer. See Figure 24.  
Once the venting system is installed, attach the  
“Disconnected Vent” warning sticker to a visible area of  
the plenum near the vent pipe. See Figure 23. The  
warning sticker is provided in the bag assembly. Order  
kit 66W04 for additional stickers.  
WARNING  
Common Venting Using Metal Lined  
Masonry Chimney  
Asphyxiation hazard. The exhaust vent for this furnace  
must be securely connected to the furnace flue transitiion  
at all times.  
Vent Connection  
NOTE 1: Refer to the provided venting tables for installations.  
Refer to the capacity requirements shown in the provided venting  
tables.  
Figure 24  
Figure 23  
506471-01  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 15 of 41  
Common Venting Using Tile Lined Interior Masonry Chimney and Combined Vent Connector  
NOTE: Refer to provided venti
tables for installations.  
himney must be properly sized  
venting tables or lined with  
ning system.  
Figure 25  
DO NOT insulate the space between the liner and the  
chimney wall with puffed mica or any other loose granular  
insulating material.  
Do not install a manual damper, barometric draft regulator,  
or flue restrictor between the furnace and the chimney.  
Never connect a Category I appliance to a chimney that is  
servicing a solid fuel appliance. If a fireplace chimney flue  
is used to vent this appliance, the fireplace opening must be  
permanently sealed.  
IMPORTANT  
SINGLE appliance venting of a fan assisted furnace into  
a tile lined masonry chimney (interior or outside wall) is  
prohibited. The chimney must first be lined with either  
type B1 vent or an insulated single wall flexible vent  
lining system which has been sized according to the  
provided venting tables and the vent pipe manufacturer’s  
instructions.  
Atype B or listed chimney lining system that passes through  
an unused masonry chimney flue is not considered to be  
exposed to the outdoors.  
General Venting Requirements  
Vent these furnaces according to these instructions:  
1. Vent diameter recommendations and maximum  
allowable piping runs are found in the provided venting  
tables.  
2. In no case should the vent or vent connector diameter  
be less than the diameter specified in the provided  
venting tables.  
A fan assisted furnace may be commonly vented into an  
existing lined masonry chimney if the following conditions  
are met:  
The chimney is currently serving at least one drafthood  
equipped appliance.  
3. The minimum vent capacity determined by the sizing  
tables must be less than the low fire input rating and the  
maximum vent capacity must be greater than the high  
fire input rating.  
The vent connectors and chimney are sized according  
to the provided venting tables.  
If type B1 double wall vent is used inside a chimney, no  
other appliance can be vented into the chimney. The outer  
wall of type B1 vent pipe must not be exposed to flue  
products. A type B1 vent or masonry chimney liner shall  
terminate above the roof surface with a listed cap or a’iisted  
roof assembly according to the terms of their respective  
listings and the vent manufacturer’s instructions.  
4 . Single appliance vents - If the vertical vent or tile lined  
chimney has a larger diameter or flow area than the  
vent connector, use the vertical vent diameter to  
determine the minimum vent capacity and the vent  
connector diameter to determine the maximum vent  
capacity. The flow area of the vertical vent, however,  
shall not exceed 7 times the flow area of the listed  
appliance categorized vent area, drafthood outlet area  
or flue collar area unless designed according to  
approved engineering methods.  
5. Multiple appliance vents - The flow area of the largest  
section of vertical vent or chimney shall not exceed 7  
times the smallest listed appliance categorized vent  
area, drafthood outlet area or flue collar area unless  
designed according to approved engineering methods.  
When inspection reveals that an existing chimney is not safe  
for the intended purpose, it shall be rebuilt to conform to  
nationally recognized standards, lined or relined with suitable  
materials, or replaced with a gas vent or chimney suitable  
for venting. The chimney passageway must be checked  
periodically to ensure that it is clear and free of obstructions.  
Page 16 of 41  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506471-01  
6. The entire length of single wall metal vent connector  
shall be readily accessible for inspection, cleaning, and  
replacement.  
13. When the vent connector used for Category I appliances  
must be located in or pass through a crawl space, attic  
or other areas which may be cold, that portion of the  
vent connector shall be constructed of listed doublewall  
type B vent material or material having equivalent  
insulation qualities.  
14. All venting pipe passing through floors, walls, and  
ceilings must be installed with the listed clearance to  
combustible materials and be fire stopped according to  
local codes. In absence of local codes, refer to NFGC  
(2223.1 ).  
15. No portion of the venting system can extend into, or  
pass through any circulation air duct or plenum.  
16. Vent connectors serving Category I appliances shall not  
be connected to any portion of mechanical draft systems  
operating under positive pressure such as Category III  
or IV venting systems.  
7. Single appliance venting configurations with zero lateral  
lengths (Tables 3 and 4) are assumed to have no elbows  
in the vent system. For all other vent configurations,  
the vent system is assumed to have two 90° elbows.  
For each additional 90° elbow or equivalent (for example  
two 45° elbows equal one 90° elbow) beyond two, the  
maximum capacity listed in the venting table should be  
reduced by 10% (0.90 x maximum listed capacity).  
8. The common venting Tables (5, 6,7, and 8) were  
generated using a maximum horizontal vent connector  
length of 1-1/2 feet (.46 m) for each inch (25 mm) of  
connector diameter as follows:  
17. If vent connectors are combined prior to entering the  
common vent, the maximum common vent capacity  
listed in the common venting tables must be reduced by  
10%, the equivalent of one 90° elbow (0.90 x maximum  
common vent capacity).  
18. The common vent diameter must always be at least as  
large as the largest vent connector diameter.  
19. In no case, shall the vent connector be sized more than  
two consecutive table size diameters over the size of  
the draft hood outlet or flue collar outlet.  
20. Do not install a manual damper, barometric draft  
regulator or flue restrictor between the furnace and the  
chimney.  
21. When connecting this appliance to an existing dedicated  
or common venting system, you must inspect the venting  
system’s general condition and look for signs of  
corrosion. The existing vent pipe size must conform to  
these instructions and the provided venting tables. If  
the existing venting system does not meet these  
requirements, it must be resized.  
Table 2  
9. If the common vertical vent is offset, the maximum  
common vent capacity listed in the common venting  
tables should be reduced by 20%, the equivalent of two  
90° elbows (0.80 x maximum common vent capacity).  
The horizontal length of the offset shall not exceed  
1-1/2 feet (.46 m) for each inch (25 mm) of common  
vent diameter.  
10. The vent pipe should be as short as possible with the  
least number of elbows and angles required to complete  
the job. Route the vent connector to the vent using the  
shortest possible route.  
11. Avent connector shall be supported without any dips or  
sags and shall slope a minimum of 1/4 inch (6.4 mm)  
per linear foot (305 mm) of connector, back toward the  
appliance.  
12. Vent connectors shall be firmly attached to the furnace  
flue collar by self drilling screws or other approved  
means,except vent connectors of listed type B vent  
material which shall be assembled according to the  
manufacturer’s instructions. Joints between sections  
of single wall connector piping shall be fastened by  
screws or other approved means.  
506471-01  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 17 of 41  
Capacity of Type B Double Wall Vents with Type B Double Wall Connectors  
Serving a Single Category I Appliance  
NOTE: Single appliance venting configureations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent  
configurations, the vent system is assumed to have two 90 ° elbows. For each additional 90° elbow or equivalent (for example two 45° elbows equal  
one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity).  
Table 3  
Page 18 of 41  
Issue 1034  
506471-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Capacity of Type B Double Wall Vents with Single Wall Metal Connectors  
Serving a Single Category I Appliance  
NOTE: Single appliance venting configureations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent  
configurations, the vent system is assumed to have two 90 ° elbows. For each additional 90° elbow or equivalent (for example two 45° elbows equal  
one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity).  
Table 4  
506471-01  
Issue 1034  
Page 19 of 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Vent Connector Capacity  
Type B Double Wall Vents with Type B Double Wall Connectors  
Serving Two or More Category I Appliances  
Table 5  
Common Vent Capacity  
Type B Double Wall Vents with Type B Double Wall Connectors  
Serving Two or More Category I Appliances  
Table 6  
Page 20 of 41  
Issue 1034  
506471-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Vent Connector Capacity  
Type B Double Wall Vents with Single Wall Metal Connectors  
Serving Two or More Category I Appliances  
NOTE: Single appliance venting configureations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent  
configurations, the vent system is assumed to have two 90 ° elbows. For each additional 90° elbow or equivalent (for example two 45° elbows equal  
one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity).  
Table 7  
Common Vent Capacity  
Type B Double Wall Vents with Single Wall Metal Connectors  
Serving Two or more Category I Appliances  
Table 8  
506471-01  
Issue 1034  
Page 21 of 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Removal of the Furnace from Common Vent  
In the event that an existing furnace is removed from a  
venting system commonly run with separate gas appliances,  
the venting system is likely to be too large to properly vent  
the remaining attached appliances.  
3. Close all building doors and windows and all doors  
between the space in which the appliances remaining  
connected to the common venting system are located  
and other spaces of the building. Turn on clothes dryers  
and any appliances not connected to the common  
venting system. Turn on any exhaust fans, such as  
range hoods and bathroom exhausts, so they will  
operate at maximum speed. Do not operate a summer  
exhaust fan. Close fireplace dampers.  
Conduct the following test while each appliance is operating  
and the other appliances (which are not operating) remain  
connected to the common venting system. If the venting  
system has been installed improperly, you must correct the  
system as indicated in the general venting requirements  
section.  
4. Follow the lighting instructions. Turn on the appliance  
that is being inspected. Adjust the thermostat so that  
the appliance operates continuously.  
5. After the burners have operated for 5 minutes, test for  
leaks of flue gases at the draft hood relief opening. Use  
the flame of a match or candle.  
WARNING  
6. After determining that each appliance connected to the  
common venting system is venting properly, (step 3)  
return all doors, widows, exhaust fans, fireplace  
dampers, and any other gas burning appliances to their  
previous mode of operation.  
7. If a venting problem is found during any of the preceding  
tests, the common venting system must be modified to  
correct the problem.  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow the steps outlined below for each  
appliance connected to the venting system being placed  
into operation could result in carbon monoxide poisoning  
or death.  
Resize the common venting system to the minimum vent  
pipe size determined by using the appropriate tables in  
Appendix G. (These are in the current standards of the  
National Fuel Gas Code ANSI 2223.1.  
The following steps shall be followed for each appliance  
connected to the venting system being placed into operation,  
while all other appliances connected to the venting system  
are not in operation:  
1. Seal any unused openings in the common venting  
system.  
2. Inspect the venting system for proper size and horizontal  
pitch. Determine that there is no blockage, restriction,  
leakage, corrosion, or other deficiencies which could  
cause an unsafe condition.  
Page 22 of 41  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506471-01  
Gas Piping  
4. The piping should be sloped 1/4 inch (6.4 mm) per 15  
feet (4.57 m) upward toward the meter from the furnace.  
The piping must be supported at proper intervals [every  
8 to 10 feet (2.44 to 3.01 m)] with suitable hangers or  
straps. Install a drip leg in vertical pipe runs to the unit.  
5. A 1/8" N.P.T. plugged tap or pressure post is located on  
the gas valve to facilitate test gauge connection. See  
Figure 38.  
6. In some localities, codes may require the installation of  
a manual main shut off valve and union (furnished by  
the installer) external to the unit. The union must be of  
the ground joint type.  
CAUTION  
If a flexible gas connector is required or allowed by the  
authority that has jurisdiction, black iron pipe shall be  
installed at the gas valve and extend outside the furnace  
cabinet. The flexible connector can then be added  
between the black iron pipe and the gas supply line.  
Gas Supply  
1. This unit is shipped standard for left or right side  
installation of gas piping (or top entry in horizontal  
applica-tions). Connect the gas supply to the piping  
assembly.  
2. When connecting the gas supply piping, consider factors  
such as length of run, number of fittings, and furnace  
rating to avoid excessive pressure drop. Table 9 lists  
recommended pipe sizes for typical applications.  
3. The gas piping must not run in or through air ducts,  
clothes chutes, gas vents or chimneys, dumb waiters,  
or elevator shafts.  
IMPORTANT  
Compounds used on threaded joints of gas piping must  
be resistant to the actions of liquified petroleum gases.  
NOTE: If emergency shutoff is necessary, shut off the main  
manual gas valve and disconnect main power to the furnace.  
The installer should properly label these devices.  
Gas Pipe Capacity - ft³/hr (m³/hr)  
Note: Capacity given in cubic feet (m³) of gas per hour and based on 06.0 specific gravity gas.  
Table 9  
506471-01  
Issue 1034  
Page 23 of 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET  
Figure 26  
Horizontal Applications  
Possible Gas Piping Configurations  
NOTE: BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET  
Figure 27  
Page 24 of 41  
Issue 1034  
506471-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Leak Check  
The unit is equipped with a field make-up box on the left  
hand side of the cabinet. The make-up box may be moved  
to the right side of the furnace to facilitate installation. If the  
make-up box is moved to the right side, clip the wire ties  
that bundle the wires together. The excess wire must be  
pulled into the blower compartment. Secure the excess wire  
to the existing harness to protect it from damage.  
After gas piping is completed, carefully check all piping  
connections (factory and field installed) for gas leaks. Use  
a leak detecting solution or other preferred means.  
NOTE: If emergency shutoff is necessary, shut off the main  
manual gas valve and disconnect the main power to the  
furnace. The installer should properly label these devices.  
INTERIOR MAKE-UP BOX INSTALLATION  
CAUTION  
Some soaps used for leak detection are corrosive to  
certain metals. Carefully rinse piping thoroughly after  
leak test has been completed. Do not use matches,  
candles, flame or other sources of ignition to check for  
gas leaks.  
The furnace must be isolated by closing its individual manual  
shut-off valve and disconnecting from from the gas supply  
system the during any pressure testing of the gas supply  
system at pressures less than or equal to 1/2 psig (3.48  
kPa, 14 inches w.c.).  
Figure 29  
IMPORTANT  
INTERIOR MAKE-UP BOX INSTALLATION  
When testing pressure of gas lines, gas valve must be  
disconnected and isolated. See Figure 28. Gas valves  
can be damaged if subjected to pressures greater than  
1/2 psig (3.48 kPa, 14 inches w.c.).  
Figure 28  
Figure 30  
Electrical  
Refer to Figure 40 for schematic wiring diagram and  
troubleshooting and Figure 41 for field wiring.  
ELECTROSTATIC DISCHARGE (ESD)  
Precautions and Procedures  
1. The power supply wiring must meet Class I restrictions.  
Protected by either a fuse or circuit breaker, select circuit  
protection and wire size according to unit nameplate.  
CAUTION  
Electrostatic discharge can affect electronic  
components. Take precautions during furnace  
installation and service to protect the furnace’s electronic  
controls. Precautions will help to avoid control exposure  
to electrostatic discharge by putting the furnace, the  
control and the technician at the same electrostatic  
potential. Neutralize electrostatic charge by touching  
hand and all tools on an unpainted unit surface, such  
as the gas valve or blower deck, before performing any  
service procedure.  
NOTE: Unit nameplate states maximum current draw.  
Maximum over current protection allowed is 15 AMP.  
2. Holes are on both sides of the furnace cabinet to facilitate  
wiring.  
3. Install a separate (properly sized) disconnect switch near  
the furnace so that power can be turned off for servicing.  
506471-01  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 25 of 41  
Indoor Blower Speeds  
1. When the thermostat is set to “FAN ON,” the indoor  
blower will run continuously at approximately 38% of  
the second stage cooling speed when there is no cooling  
or heating demand.  
2. When this unit is running in the heating mode, the indoor  
blower will run on the heating speed designated by the  
positions of DIP switches 11 and 12.  
3. When there is a cooling demand, the indoor blower will  
run on the cooling speed designated by the positions of  
DIP switches 5 and 6.  
Table 10  
4. Before connecting the thermostat, check to make sure  
the wires will be long enough for servicing at a later  
date. Make sure that thermostat wire is long enough to  
facilitate future removal of blower for service.  
5. Complete the wiring connections to the equipment. Use  
the provided unit wiring diagram and the field wiring  
diagram shown in Figure 41. Use 18 gauge wire or  
larger that is suitable for Class II rating for thermostat  
connections.  
Generator Use - Voltage Requirements  
The following requirements must be kept in mind when  
specifying a generator for use with this equipment:  
The furnace requires 120 volts ± 10% (Range: 108 volts  
to 132 volts).  
The furnace operates at 60 Hz ± 5% (Range: 57 Hz to  
63 Hz).  
The furnace integrated control requires both polarity and  
proper ground. Both polarity and proper grounding  
should be checked before attempting to operate the  
furnace on either permanent or temporary power.  
Generator should have a wave form distortion of less  
than 5% RHO.  
6. Electrically ground the unit according to local codes or,  
in the absence of local codes, according to the current  
National Electric Code (ANSI/NFPA No. 70). A green  
ground wire is provided in the field make-up box.  
NOTE: This furnace contains electronic components that  
are polarity sensitive. Make sure that the furnace is wired  
correctly and is properly grounded.  
7. One line voltage “EAC” 1/4" spade terminal is provided  
on the furnace integrated control. Any electronic air  
cleaner or other accessory rated up to one amp can be  
connected to this terminal with the neutral leg of the  
circuit being connected to one of the provided neutral  
terminals. See Figure 41 for control configuration. This  
terminal is energized when the indoor blower is  
operating.  
Electrical Wiring  
WARNING  
Risk of electrical shock. Disconnect electrical power at  
the circuit breaker or service panel before making  
electrical connections. Failure to disconnect power  
supplies can result in property damage, personal injury,  
or death.  
8. One line voltage “HUM” 1/4" spade terminal is provided  
on the furnace integrated control. Any humidifier rated  
up to one amp can be connected to this terminal with  
the neutral leg of the circuit being connected to one of  
the provided neutral terminals. See Figure 41 for control  
configuration. This terminal is energized in the heating  
mode whenever the combustion air inducer is operating.  
The furnace must be grounded and wired in accordance  
with local codes or, in the absence of local codes, with the  
National Electrical Code ANSI/NFPA No. 70 (latest edition)  
and/or CSA C22.1 Electrical Code (latest edition) if an  
external electrical source is utilized.  
9. One 24V “H” terminal is provided on the furnace  
inte-grated control terminal block. Any humidifier rated  
up to 0.5 amp can be connected to this terminal with  
the ground leg of the circuit being connected to either  
ground or the “C” terminal. See Figure 41 for control  
configuration.  
10. Install the room thermostat according to the instructions  
provided with the thermostat. If the furnace is being  
matched with a heat pump, refer to the instruction  
packaged with the dual fuel thermostat.  
Page 26 of 41  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506471-01  
In all instances, other than wiring for the thermostat, the  
wiring to be done and any replacement of wire shall conform  
with the temperature limitation for Type T wire –63°F (35°C)  
rise.  
Automatic Heat Staging Jumper  
Connect a sufficiently sized wire with ground to the furnace’s  
line voltage connections and ground lug. Refer to the furnace  
rating plate for electrical characteristics to be used in sizing  
field supply wiring and overcurrent protection.  
The line voltage supply should be routed through a readily  
accessible disconnect located within sight of the furnace. A  
junction box on the furnace side panel is provided for line  
voltage connections. Refer to the furnace wiring diagram  
for specific connection information.  
Figure 31  
Electronic Air Cleaner  
Terminals are provided on the integrated ignition/blower  
control board for connection of a 120-volt electronic air  
cleaner. The “EAC” terminal is energized whenever the  
thermostat calls for heat, cooling, or continuous blower. See  
furnace wiring diagram for specific connection information.  
Proper polarity of the supply connections (“HOT” and  
“NEUTRAL”) must be observed to ensure that safety  
controls provide the protection intended.  
A connection to the ground lug and actual earth ground  
(typically a ground stake or buried steel pipe) must be  
maintained for proper operation.  
Variable Speed Features  
This furnace is equipped with a variable speed circulation  
air blower motor that will deliver a constant airflow within a  
wide range of external static pressures. Other features of  
this variable speed motor include:  
Thermostat  
Install a room thermostat according to the instructions  
furnished with it. Select a location on an inside wall that is  
not subject to drafts, direct sunshine, or other heat sources.  
The initial heat anticipator setting should be equal to the  
total current draw of the control circuit. Low voltage  
thermostat connections are to be made to the integrated  
ignition/blower control board as indicated on the wiring  
diagram.  
Soft Start  
The variable speed motor will slowly ramp up to normal  
operating speed. This minimizes noise and increases  
comfort by eliminating the initial blasts of air encountered  
with standard motors.  
Soft Stop  
Single Stage Thermostat Operation  
At the end of a cooling or heating cycle, the variable speed  
motor will slowly ramp down after a short blower “off” delay.  
If continuous blower operation has been selected, the  
variable speed motor will slowly ramp down until it reaches  
the airflow for that mode.  
(A80UH2V and 80G1UH2V Models )  
The automatic heat staging option allows a single stage  
thermostat to be used with two stage furnace models  
(A80UH2V or 80G1UH2V). To activate this option, move  
the jumper pin (see Figure 31) to desired setting (5 minutes  
or 10 minutes). The furnace will start on 1st stage heat and  
stay at 1st stage heat for the duration of the selected time  
before switching to 2nd stage heat.  
Passive and Active Dehumidification  
Passive Dehumidification  
For situations where humidity control is a problem, a  
dehumidification feature has been built into the variable  
speed motor. At the start of each cooling cycle, the variable  
speed motor will run at 82% of the rated airflow for 7.5  
minutes. After 7.5 minutes has elapsed, the motor will  
increase to 100% of the rated airflow.  
W1 on the control board must be connected to W1 on the  
thermostat.  
Humidifier  
Terminals are provided on the integrated ignition/blower  
control board for connection to a 120-volt humidifier. The  
“HUM” terminal is energized whenever the thermostat calls  
for heat. See the furnace wiring diagram for specific  
connection information.  
506471-01  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 27 of 41  
Heating Mode  
Active Dehumidification  
The unit as shipped is factory set to run at the middle of the  
heating rise range as shown on the unit rating plate. If higher or  
lower rise is desired, change the airflow 15% up or down by  
movingtheADJUSTjumperplug(seeFigure32)fromtheNORM  
position to the (+) or (–) position. This adjustment will also cause  
the cooling airflow to be raised or lowered by 15%.  
To achieve additional dehumidification, clip the jumper wire  
located below the DEHUM terminal on the integrated ignition/  
blower control board and connect a humidity control that  
opens on humidity rise to the DEHUM and R terminals. The  
DEHUM terminal on the control board must be connected  
to the normally closed contact of the humidity control so that  
the board senses an open circuit on high humidity. In this  
setup, the variable speed motor will operate at a 18%  
reduction in the normal cooling airflow rate when there is a  
call for dehumidification.  
The TEST position on the ADJUST tap is not used.  
The jumper plug on the HEAT tap should remain in the position  
(A, B, C, or D) listed in the HEAT Setting column in the table  
found in Figure 32. Changing the setpoints may not increase or  
decrease heating blower speeds. In some cases, running the  
blower with the heat settings in the wrong position may cause  
thefurnacetooperateoutsidethefurnace’sintendedtemperature  
rise range.  
Both the passive and active dehumidification methods  
described above can be utilized on the same furnace.  
Circulating Airflow Adjustments  
Cooling Mode  
Continuous Blower Operation  
The units are factory set for the highest airflow for each model.  
Adjustments can be made to the cooling airflow by  
repositioning the jumper plug marked COOL – A, B, C, D  
(see Figure 32) based on the information found in the table.  
To determine what CFM the motor is delivering at any time,  
count the number of times the amber LED on the control board  
flashes. Each flash signifies 100 CFM; count the flashes and  
multiply by 100 to determine the actual CFM delivered (for  
example: 10 flashes x 100 = 1000 CFM).  
The comfort level of the living space can be enhanced when  
using this feature by allowing continuous circulation of air  
between calls for cooling or heating. The circulation of air  
occurs at half the full cooling airflow rate.  
To engage the continuous blower operation, place the fan  
switch on the thermostat into the ON position. A call for fan  
from the thermostat closes R to G on the ignition control  
board. The control waits for a 1 second thermostat debounce  
delay before responding to the call for fan by ramping the  
circulating blower up to 50% of the cooling speed. When  
the call for continuous fan is satisfied, the control immediately  
ramps down the circulating blower.  
ADJUST, HEAT, and COOL Taps  
on Integrated Ignition/Blower  
Control Board  
Figure 32  
Page 28 of 41  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506471-01  
ADJUSTING AIRFLOW  
Table 11  
506471-01  
Issue 1034  
Page 29 of 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To Start Furnace:  
START-UP  
Lighting Instructions  
CAUTION  
For Your Safety, Read Before Operating  
Be sure the manual gas control has been in the “OFF”  
position for at least 5 minutes before starting the unit.  
Do not attempt to manually light the burners.  
WARNING  
If you do not follow these instructions exactly, a fire or  
explosion may result causing property damage, personal  
injury, or loss of life.  
1. Set the room thermostat to lowest setting.  
2. Remove burner access door.  
These furnaces are equipped with an ignition device which  
automatically lights the burners. Do not try to light the  
burners by hand.  
3. Move the gas control knob to the “ON” position. Use  
only your hand to turn the gas control knob. Never use  
tools. If the knob will not turn by hand, don’t try to repair  
it; call a qualified service technician. Force or  
attempted repair may result in a fire or explosion.  
Before operating, smell all around the appliance area for  
gas. Be sure to smell next to the floor because some gas is  
heavier than air and will settle on the floor.  
4. Replace the burner access door.  
What to do if you smell gas:  
5. Turn on the electrical power to the furnace.  
Do not try to light any appliances.  
Extinguish any open flame.  
6. Set room thermostat to a point above room temperature  
to light the burners. After the burners have ignited, set  
room thermostat to desired temperature.  
Do not touch any electric switch; do not use any phone  
in your building.  
To Shut Down Furnace:  
Immediately call your gas supplier from a neighbor’s  
phone. Follow the gas supplier’s instructions.  
1. Set the room thermostat to the lowest setting.  
2. Turn off all electric power to the furnace.  
3. Remove burner access door.  
If you cannot reach your gas supplier, call the fire  
department.  
Do not use this furnace if any part has been under water.  
Immediately call a qualified service technician to inspect the  
furnace and to replace any part of the control system and  
gas control which has been under water.  
4. Shut off gas by moving gas control knob to “OFF” position.  
5. Replace the burner access door.  
IMPORTANT: Refer to the Lighting Instruction label on  
the furnace for instructions on operating the specific  
controls used on your unit.  
WARNING  
Should overheating occur or the gas supply fail to shut  
off, shut off the manual gas valve to the appliance  
before shutting off the electrical supply.  
Page 30 of 41  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506471-01  
the R to G circuit and the circulating blower motor runs at  
50% of the selected cooling CFM until switched off. When  
the call for fan is turned off, the control de-energizes the  
circulating blower.  
OPERATION  
Sequence of Operation (see Figures 33 – 37)  
Heating  
On a call for heat from the room thermostat, the control board  
performs a 1 second self check. Upon confirmation that the  
pressure switch contacts are in an open position, the control  
energizes the combustion blower on high speed. The control  
then checks for adequate combustion air by making sure  
the low-fire pressure switch contacts are closed.  
Cooling  
The unit is set up at the factory for single stage cooling. For  
two stage cooling operation, clip the jumper wire located  
between the Y to Y2 terminals on the integrated ignition/  
blower control board.  
The igniter energizes and is allowed to warm up for 7  
seconds before the gas valve energizes on 1st stage and  
burners ignite. 45 seconds after the control confirms ignition  
has occurred, the control drops the combustion blower to  
low speed.  
If the active dehumidification feature is enabled, the  
circulating blower runs at 82% of the selected cooling speed  
as long as there is a call for dehumidification.  
IMPORTANT  
The circulating blower ramps up to 50% of 1st stage heat speed  
and operates at that speed for one minute (including ramp up  
time), then at 75% of 1st stage heat speed for an additional  
minute. After that, the circulating blower operates at full 1st  
stage heat speed until either the heat call is satisfied or the  
thermostat initiates a call for 2nd stage heat. On a call for 2nd  
stage heat, the control energizes the circulating air blower on  
full CFM 2nd stage heat.  
The system must not be in either the passive or active  
dehumidification mode when charging a cooling system.  
Single Stage Cooling  
Acall for cooling from the thermostat closes the R to Y circuit  
on the integrated ignition/blower control board. The control  
waits for a 1-second delay before energizing the circulating  
blower to 82% of the selected cooling CFM (passive  
dehumidification mode). After 7.5 minutes, the circulating  
blower automatically ramps up to 100% of the selected cooling  
airflow. When the call for cooling is satisfied, the circulating  
blower ramps back down to 82% of the selected cooling  
airflow for 1 minute, then shuts off.  
If the automatic heat staging option is being used (see Single  
Stage Thermostat Operation on page 27), the furnace does  
not switch to 2nd stage heat in response to a call from the  
thermostat but instead operates at 1st stage heat for the  
duration of the selected time before automatically switching  
to 2nd stage heat.  
When the call for heat is satisfied, the gas valve and  
combustion air blower shut down. The control board shuts  
off the gas valve and runs the combustion blower for an  
additional 15 seconds. The circulating air blower continues  
to run for 2 minutes at 82% of the selected heating speed  
(low fire or high fire) before ramping down.  
Two Stage Cooling  
A call for 1st stage cooling from the thermostat closes the R  
to Y circuit on the control board. The control waits for a 1-  
second delay before energizing the circulating blower. The  
blower motor runs at 57% of the selected air flow for the first  
7.5 minutes of the 1st stage cooling demand (passive  
dehumidification mode). After 7.5 minutes, the blower motor  
runs at 70% of the selected cooling air flow until 1st stage  
cooling demand is satisfied.  
In the event the unit loses ignition, the control will attempt to  
recycle up to five times before it goes into a 1 hour lockout.  
Lockout may be manually reset by removing power from  
the control for more than 1 second or removing the  
thermostat call for heat for more than 3 seconds.  
A call for 2nd stage cooling from the thermostat closes the R to  
Y2 circuit on the control board. The blower motor ramps up to  
100% of the selected cooling air flow. When the demand for  
cooling is met, the blower ramps down to Y1 until satisfied,  
then ramps down to 57% for 1 minute, then turns off.  
If during a heating cycle the limit control senses an abnormally  
high temperature and opens, the control board de-energizes  
the gas valve and the combustion blower while the circulating  
blower ramps up to 2nd stage heat speed. The circulating blower  
remains energized until the limits are closed.  
Heat Pump  
For heat pump operation, clip the jumper wire located below  
the O terminal on the integrated ignition/blower control board.  
In heat pump mode, a call for heat will result in the circulating  
air blower operating at the selected cooling airflow after a  
brief ramp-up period.  
Fan On  
When the thermostat is set for continuous fan operation and  
there is no demand for heating or cooling, a call for fan closes  
506471-01  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 31 of 41  
1st Stage - 2nd Stage (W1/W2) Heat Call  
W1/W2  
w1  
w2  
W1  
2 min  
100%**  
2 min  
82%*  
W1 - Heat Demand Present  
w1- Heat Demand Satisfied  
82%**  
1
100%*  
1
min  
W2 - High Heat Demand Present  
w2- High Heat Demand Satisfied  
min  
75%*  
w1  
50%*  
OFF  
** Percentage of High Fire CFM  
CALL  
* Percentage of Low Fire CFM  
Figure 33  
Single Stage Cooling  
High Heat (W2) Call  
y
Y
W2  
w2  
1
7.5 minutes  
100%  
min  
82%  
2 min  
82%  
100*  
82%*  
Y - Cool Demand Present  
y
- Cool Demand Satisfied  
CALL  
OFF  
W2 - High Heat Demand Present  
w2- High Heat Demand Satisfied  
OFF  
CALL  
Figure 36  
* Percentage of High Fire CFM  
Two Stage Cooling  
Figure 34  
Y1 Y2  
y2  
y1  
Y1  
/
/
Y1  
100%  
7.5  
Call for Fan  
minutes  
57%  
70%  
70%  
1
G
1
min  
57%  
g
min  
57%  
50%  
y1  
G - Fan Switch ON  
g - Fan Switch OFF  
CALL  
OFF  
CALL Y1 - 1st Stage Cool Demand Present  
OFF  
st  
y1  
- 1 Stage Cool Demand Satisfied  
Y2 - 2nd Stage Cool Demand Present  
Figure 35  
nd  
y2  
- 2 Stage Cool Demand Satisfied  
Figure 37  
Page 32 of 41  
Issue 1034  
506471-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controls  
propane gas, the manifold pressures are 4.9" w.c. (1st stage)  
and 10.0" w.c. (2nd stage).  
Following is a description of the operation of some of the  
controls used in this furnace. All models use one of each  
control, except as noted.  
To measure inlet or outlet pressure, remove plug from  
desired pressure tap (inlet or outlet) as shown in Figure 38  
and connect a water manometer or gauge to the proper  
pressure tap.  
Pressure Switch  
The pressure switch is a normally open switch that monitors  
combustion air flow. Inadequate air flow resulting from  
excessive venting system restriction or a failed combustion  
blower will cause the switch to remain open. A80UH2V and  
80G2UHV models have two pressure switches.  
GAS VALVE SHOWN IN “ON” POSITION  
Rollout Switch  
The rollout switch is a normally closed switch that opens when  
abnormal temperatures exist in the burner area. This can be  
caused by a restricted heat exchanger causing burner flame  
to “roll out” into the vestibule area or burner box.  
This switch must be manually reset by pushing the button  
on top to restore furnace operation. A80UH2V and  
80G2UHV models have two rollout switches.  
Figure 38  
Primary Limit Control  
This is a normally closed control that opens if abnormally  
high circulating air temperatures occur. It is an automatic  
reset control.  
These models have separate adjusting screws (3/32" hex) for  
1st stage (marked “LO”) and 2nd stage (marked “HI”). The  
adjusting screws are positioned on either side of the barbed  
fitting (see Figure 38). Turn the adjusting screws clockwise to  
increase pressure and input; counterclockwise to decrease  
pressure and input. The pressure regulator adjustment is  
sensitive; one turn of the adjusting screw will result in a relatively  
large change in manifold pressure.  
Auxiliary Limit Control  
This is a normally closed control, located on the circulating  
air blower housing, that opens under abnormal “reverse air  
flow” conditions that could occur in a counterflow or horizontal  
installation if the circulating air blower fails. It is an automatic  
reset control.  
To adjust the regulator:  
1. Set high-fire (2nd stage) setting by turning hex adjustment  
screw to desired rate.  
Interlock (Blower Door) Switch  
When the blower door is removed, the interlock switch  
breaks the power supply to the burner controls and blower  
motor. The switch operation must be checked to confirm it  
is operating correctly.  
2. Set low-fire (1st stage) setting by turning hex adjustment  
screw to desired rate.  
Make sure the final high and low fire manifold pressures  
are within the allowable ranges specified above for the  
gas being used.  
Checking and Adjusting Gas Input  
The minimum permissible gas supply pressure for the  
purpose of input adjustment is 5"w.c. for natural gas or 11"  
w..c. for propane gas. This furnace requires conversion for  
use with propane (see Accessories section on page 26 for  
correct kit). The maximum inlet gas supply pressure is 10.5"  
w.c. for natural gas and 13" w.c. for propane. Gas input  
must never exceed the value shown on the furnace rating  
plate.  
CAUTION  
The furnace rate must be within +/- 2% of the appliance  
rating input.  
Be sure to replace the inlet and outlet pressure tap plugs  
after testing and/or adjusting gas input.  
These units are equipped for rated input at manifold pressures  
of 1.7" w.c. (1st stage) and 3.5" w.c. (2nd stage) for natural gas.  
When these furnaces have been converted for use with  
506471-01  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 33 of 41  
For Natural Gas: Check the furnace rate by observing the  
gas meter, when available, making sure all other gas  
appliances are turned off. The test hand on the meter should  
be timed for at least one revolution. Note the number of  
seconds for one revolution.  
according to the information shown in Table 12. To adjust  
the manifold pressure, refer to previous section Checking  
and Adjusting Gas Input. For installations above 7500  
feet, call Technical Service at 1-800-515-3501 for assistance.  
For installations above 4500 feet fill in the appropiate  
information on the furnace label that has the words “This  
furnace was converted on . . . . . . “.  
BTU/HR Cubic Feet Per Revolution  
Heating  
Value  
x 3600 x  
=
INPUT  
# Seconds Per Revolution  
The heating value of the gas can be obtained from the local  
utility company.  
Emergency Replacement Motor Operation  
If the variable speed motor needs to be replaced in an  
emergency situation (such as “no heat”) and an exact  
replacement motor is not immediately available, a standard  
PSC motor of equivalent frame size, voltage, rotation, and  
horsepower can be temporarily installed until the correct  
replacement motor can be obtained.  
For Propane Gas: The only check for the furnace rate is to  
properly adjust the manifold pressure using a manometer  
and the information provided in Table 12. Typical manifold  
set point for installations at altitudes from 0 to 4500 feet  
above sea level is 10.0" W.C.  
Connect the desired speed tap to the “EAC” terminal and the  
neutral tap to the neutral terminal on the ignition control (refer  
to the furnace wiring diagram). The ignition control will control  
the motor’s operation, including a nominal 20 second “on” delay  
with a call for heat and a nominal 180 second “off” delay when  
the thermostat is satisfied. It will also operate the motor on a  
call for cooling, with no “on” or “off” delays.  
Temperature Rise  
Check the temperature rise and, if necessary, adjust blower  
speed to maintain temperature rise within the range shown  
on the unit rating plate.  
High Altitude  
Verify that the unit is operating at the desired speed and  
within the rise range as shown on the unit rating plate.  
In both the United States and Canada, this furnace is  
approved for operation at altitudes from 0 to 4500 feet above  
sea level without any required modifications. From 4500 to  
7500 feet, the gas manifold pressure needs to be adjusted  
The correct replacement motor must be installed as  
soon as possible to ensure continued satisfactory  
operation of the furnace.  
MANIFOLD PRESSURE SETTINGS  
* Consult local utility for actual heating value.  
Furnace input = Input Factor x Nameplate Input  
NOTE: A natural to LP/Propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the  
conversion procedure.  
Table 12  
Page 34 of 41  
Issue 1034  
506471-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE  
WARNING  
Typical Flame Appearance  
Heat  
Exchanger  
ELECTRICAL SHOCK, FIRE,  
OR EXPLOSION HAZARD  
Burner  
Failure to follow the safety warnings exactly could result  
in dangerous operation, serious injury, death, or property  
damage.  
Gas  
Manifold  
Burner  
Flame  
(Blue Only)  
Improper servicing could result in dangerous operation,  
serious injury, death, or property damage.  
Before servicing, disconnect all electrical power to  
furnace.  
Figure 39  
When servicing controls, label all wires prior to  
disconnecting. Reconnect wires correctly.  
Verify proper operation after servicing.  
Lubrication  
The blower motor and induced draft motor are pre-lubricated  
by the manufacturer and do not require further lubricating  
attention. However, the motors should be cleaned  
periodically to prevent the possibility of overheating due to  
an accumulation of dust and dirt on the windings or on the  
motor exterior.  
It is recommended that this furnace be inspected by a  
qualified service technician at the beginning of each heating  
season.  
Filters  
Filters should be checked at least every 6 weeks. Disposable  
filters should be replaced when dirty, and cleanable filters  
should be cleaned regularly. It is important to keep the air filters  
clean, as dirty filters can restrict airflow and the blower and  
induced draft motors depend upon sufficient air flowing across  
and through them to keep from overheating.  
Burners  
Light the burners and allow to operate for a few minutes to  
establish normal burning conditions. Observe the burner  
flames. Compare this observation to Figure 39 to determine if  
proper flame adjustment is present. Flame should be  
predominantly blue in color and strong in appearance. Check  
that all burners are lit, and that the flame does not impinge on  
the sides of the heat exchanger.  
Distorted flame or yellow tipping of the natural gas burner  
flame, or long yellow tips on propane, may be caused by lint  
accumulation or dirt inside the burner or burner ports, at the  
air inlet between the burner and manifold pipe, or  
obstructions over the burner orifice.  
Use a soft brush or vacuum to clean the affected areas.  
506471-01  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 35 of 41  
CONTROL DIAGNOSTICS  
Failure Codes - Red LED  
Troubleshooting  
Make the following visual checks before troubleshooting:  
LED Status  
Fault Description  
1. Check to see that the power to the furnace and the  
integrated ignition/blower control board is ON.  
No power to control or control  
hardware fault detected  
LED Off  
2. The manual shutoff valves in the gas line to the furnace  
must be open.  
LED On  
1 Flash  
Normal operation  
Flame Present with gas valve off  
3. Make sure all wiring connections are secure.  
Pressure switch closed with  
inducer off  
2 Flashes  
3 Flashes  
4. Review the Sequence of Operation (see page 31).  
Start the system by setting thermostat above room  
temperature. Observe system response. Then use the  
information provided in this section to check the system  
operation.  
Low-fire pressure, rollout, or aux  
limit switch open  
High limit switch open  
Not used  
4 Flashes  
5 Flashes  
6 Flashes  
7 Flashes  
The furnace has a built-in, self-diagnostic capability. If a  
system problem occurs, a fault code is shown by a red LED  
on the control board. The control continuously monitors its  
own operation and the operation of the system. If a failure  
occurs, the LED will indicate the failure code. The flash  
codes are presented in Table 13  
Pressure switch cycle lockout  
Lockout due to no ignition  
Lockout due to too many flame  
dropouts  
8 Flashes  
9 Flashes  
Incorrect polarity and phasing  
Fault Code History Button  
The control stores the last five fault codes in memory. A  
pushbutton switch is located on the control (see Figure 40  
on page 38). When the pushbutton switch is pressed and  
released, the control flashes the stored fault codes. The  
most recent fault code is flashed first; the oldest fault code  
is flashed last. To clear the fault code history, press and  
hold the pushbutton switch in for more than 5 seconds before  
releasing.  
Table 13  
High Heat State - Green LED  
LED  
Status  
Description  
High Heat State LED  
On A80UH2V and 80G1UH2V models, a green LED is  
provided on the control board to indicate high heat state  
(see Table 14).  
LED Off  
No demand for high heat  
High heat demand, operating  
normally  
LED On  
High heat demand, high pressure  
switch not closed  
CFM LED  
LED Flashing  
On A80UH2V and 80G1UH2V models equipped with a  
variable speed motor, an amber LED is provided on the  
control board to display CFM. To determine what CFM the  
motor is delivering at any time, count the number of times  
the amber LED flashes. Each flash signifies 100 CFM; count  
the flashes and multiply by 100 to determine the actual CFM  
delivered (for example: 10 flashes x 100 = 1000 CFM).  
Table 14  
Page 36 of 41  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506471-01  
REPAIR PARTS  
The following repair parts are available from the local distributor. When ordering parts, include the complete furnace model  
number and serial number which are printed on the rating plate located on the furnace.  
Control Group  
Heat Exchanger Group  
Transformer  
Heat exchanger  
High limit control  
Auxiliary limit  
Gas valve  
Blower Group  
Integrated ignition/blower control board  
Flame sensor  
Blower housing assembly  
Blower wheel  
Pressure switches – 1st stage and 2nd stage  
Blower door interlock switch  
Combustion blower assembly  
Flame rollout protector switch  
Hot surface igniter  
Blower mount  
Blower motor  
Blower motor mount  
Input choke  
Burner Group  
Gas manifold  
Burner orifices  
Burners  
506471-01  
Issue 1034  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 37 of 41  
Wiring Diagram  
IGNITER  
INDUCED  
DRAFT  
BLOWER  
FLAME  
SENSOR  
PRESSURE  
SWITCH -  
DRAIN  
PRESSURE PRESSURE  
ROLLOUT  
SWITCH  
(IF USED)  
SWITCH  
(HIGH)  
SWITCH  
(LOW)  
ROLLOUT  
SWITCH  
(IF USED)  
GAS VALVE  
M C HI  
VLT  
VLT  
VLT  
BRN  
WHT/BLK  
1 2  
1 2  
2-PIN  
CONNECTOR  
MAIN  
LIMIT  
RED  
RED/BLK  
ORN  
HOT  
120/1/60  
NEUTRAL  
BRN  
BLU  
GRY  
GROUND  
S1 3 2 1  
P1 3 2 1  
VLT  
INTERLOCK  
SWITCH  
WHT  
BLK  
BLK/WHT  
WHT  
TRANSFORMER  
AUX LIMIT  
SWITCH  
(IF USED)  
AUX LIMIT  
SWITCH  
HOT  
1
2
3
4
5
IGNITION CONTROL  
YEL  
AUTOMATIC  
HEAT STAGING  
JUMPER  
P5  
0 1  
5
E
O N  
12  
11  
10  
9
6
5
4
3
5-PIN  
8
2
CONNECTOR  
GREEN LED  
RED LED  
1
7
AMBER LED  
W1W2 C  
R
G
Y
CIRCULATION  
BLOWER  
O
Y2  
5-PIN  
CONNECTOR  
SW1  
1
2
3
4
5
GRN  
BLK  
WHT  
INPUT CHOKE  
(IF USED)  
FAULT CODE  
HISTORY  
W1W2  
THERMOSTAT  
C
Y
R
G
CONDENSER  
WHT  
BUTTON  
(SEE NOTE 1)  
YEL  
YEL  
WHT  
BLK  
LINE VOLTAGE - FACTORY  
LINE VOLTAGE - FIELD  
LOW VOLTAGE - FACTORY  
LOW VOLTAGE - FIELD  
BRN  
TYP  
NOTES:  
1. PRESS AND RELEASE FAULT CODE HISTORY BUTTON TO  
DISPLAY FAULT CODES. TO ERASE CODES, PRESS AND HOLD  
BUTTON IN FOR MORE THAN 5 SECONDS  
2. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED, IT MUST BE REPLACED  
WITH WIRING MATERIAL HAVING A TEMP. RATING OF AT LEAST 90°C.  
3. PROPER POLARITY MUST BE OBSERVED FOR FIELD LINE VOLTAGE SUPPLY; IGNITION CONTROL WILL LOCK  
OUT IF POLARITY IS REVERSED.  
4. FOR TEMPORARY SERVICE REPLACEMENT OF CIRCULATING BLOWER MOTOR WITH PSC MOTOR, CONNECT  
DESIRED SPEED TAP TO “EAC” TERMINAL AND NEUTRAL TAP TO NEUTRAL TERMINAL ON IGNITION CONTROL.  
5. DO NOT CONNECT C (COMMON) CONNECTION BETWEEN INDOOR UNIT AND THERMOSTAT EXCEPT WHEN  
REQUIRED BY THE INDOOR THERMOSTAT. REFER TO THE THERMOSTAT INSTALLATION INSTRUCTIONS.  
Figure 40  
Page 38 of 41  
Issue 1034  
506471-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical Field Wiring Diagram  
Figure 41  
506471-01  
Issue 1034  
Page 39 of 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START-UP & PERFORMANCE CHECK LIST  
UNIT SET UP  
Page 40 of 41  
Issue 1034  
506471-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT OPERATION  
506471-01  
Issue 1034  
Page 41 of 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Adcom Stereo Amplifier GFA7807 User Manual
Adesso Computer Keyboard ACK 540U User Manual
ADTRAN Network Router DSU 56 User Manual
Aiwa Satellite Radio FR C300 User Manual
Alcatel Carrier Internetworking Solutions Cell Phone 535 735 User Manual
Allied Telesis Network Card AT MC110 Series User Manual
American Dryer Corp Automobile Parts AD 81 User Manual
Atlona Car Amplifier AT 3GSDI 14 User Manual
Audiovox Car Stereo System AVD300T User Manual
Axis Communications Security Camera AXIS Q1614 User Manual