Mitsubishi Electronics Mitsubishi Digital Electronics Car Amplifier MR J3 B User Manual |
General-Purpose AC Servo
J3 Series
SSCNET Compatible
MODEL
MR-J3- B
SERVO AMPLIFIER
INSTRUCTION MANUAL
D
Safety Instructions
(Always read these instructions before using the equipment.)
Do not attempt to install, operate, maintain or inspect the converter unit, servo amplifier (drive unit) and servo
motor until you have read through this Instruction Manual, Installation guide, Servo motor Instruction Manual
(Vol.2) and appended documents carefully and can use the equipment correctly. Do not use the converter unit,
servo amplifier (drive unit) and servo motor until you have a full knowledge of the equipment, safety information
and instructions.
In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
Indicates that incorrect handling may cause hazardous conditions,
WARNING
resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions,
CAUTION
resulting in medium or slight injury to personnel or may cause physical
damage.
Note that the CAUTION level may lead to a serious consequence according to conditions. Please follow the
instructions of both levels because they are important to personnel safety.
What must not be done and what must be done are indicated by the following diagrammatic symbols.
: Indicates what must not be done. For example, "No Fire" is indicated by
: Indicates what must be done. For example, grounding is indicated by
.
.
In this Instruction Manual, instructions at a lower level than the above, instructions for other functions, and so
on are classified into "POINT".
After reading this installation guide, always keep it accessible to the operator.
A - 1
1. To prevent electric shock, note the following
WARNING
Before wiring or inspection, turn off the power and wait for 15 minutes or more (20 minutes or for drive
unit 30kW or more) until the charge lamp turns off. Then, confirm that the voltage between P( ) and
N( ) (L and L
is safe with a voltage tester and others. Otherwise, an
for drive unit 30kW or more)
electric shock may occur. In addition, always confirm from the front of the servo amplifier (converter unit),
whether the charge lamp is off or not.
Connect the converter unit, servo amplifier (drive unit) and servo motor to ground.
Any person who is involved in wiring and inspection should be fully competent to do the work.
Do not attempt to wire the converter unit, servo amplifier (drive unit) and servo motor until they have been
installed. Otherwise, you may get an electric shock.
Operate the switches with dry hand to prevent an electric shock.
The cables should not be damaged, stressed loaded, or pinched. Otherwise, you may get an electric
shock.
During power-on or operation, do not open the front cover. You may get an electric shock.
Do not operate the converter unit and servo amplifier (drive unit) with the front cover removed. High-
voltage terminals and charging area are exposed and you may get an electric shock.
Except for wiring or periodic inspection, do not remove the front cover even if the power is off. The servo
amplifier (drive unit) is charged and you may get an electric shock.
2. To prevent fire, note the following
CAUTION
Install the converter unit, servo amplifier (drive unit), servo motor and regenerative resistor on
incombustible material. Installing them directly or close to combustibles will lead to a fire.
Always connect a magnetic contactor (MC) between the main circuit power supply and L1, L2, and L3 of
the converter unit, servo amplifier (drive unit), and configure the wiring to be able to shut down the power
supply on the side of the converter unit, servo amplifier (drive unit) power supply. If a magnetic contactor
(MC) is not connected, continuous flow of a large current may cause a fire when the converter unit, servo
amplifier (drive unit) malfunctions.
When a regenerative resistor is used, use an alarm signal to switch main power off. Otherwise, a
regenerative transistor fault or the like may overheat the regenerative resistor, causing a fire.
3. To prevent injury, note the follow
CAUTION
Only the voltage specified in the instruction manual should be applied to each terminal, Otherwise, a burst,
damage, etc. may occur.
Connect the terminals correctly to prevent a burst, damage, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
Take safety measures, e.g. provide covers, to prevent accidental contact of hands and parts (cables, etc.)
with the converter unit and servo amplifier (drive unit) heat sink, regenerative resistor, servo motor, etc.
since they may be hot while power is on or for some time after power-off. Their temperatures may be high
and you may get burnt or a parts may damaged.
During operation, never touch the rotating parts of the servo motor. Doing so can cause injury.
A - 2
4. Additional instructions
The following instructions should also be fully noted. Incorrect handling may cause a fault, injury, electric shock,
etc.
(1) Transportation and installation
CAUTION
Transport the products correctly according to their weights.
Stacking in excess of the specified number of products is not allowed.
Do not carry the servo motor by the cables, shaft or encoder.
Do not hold the front cover to transport the converter unit and servo amplifier (drive unit). The converter
unit and servo amplifier (drive unit) may drop.
Install the converter unit and servo amplifier (drive unit) in a load-bearing place in accordance with the
Instruction Manual.
Do not climb or stand on servo equipment. Do not put heavy objects on equipment.
The converter unit, servo amplifier (drive unit), and servo motor must be installed in the specified
direction.
Leave specified clearances between the converter unit, servo amplifier (drive unit), and control enclosure
walls or other equipment.
Do not install or operate the converter unit, servo amplifier (drive unit), and servo motor which has been
damaged or has any parts missing.
When you keep or use it, please fulfill the following environmental conditions.
Conditions
Environment
Converter unit servo amplifier (drive unit)
0 to 55 (non-freezing)
Servo motor
0 to 40 (non-freezing)
In
[
[
[
[
]
]
]
]
operation
Ambient
32 to 131 (non-freezing)
32 to 104 (non-freezing)
15 to 70 (non-freezing)
5 to 158 (non-freezing)
temperature
20 to 65 (non-freezing)
In storage
4 to 149 (non-freezing)
Ambient
humidity
In operation
In storage
90%RH or less (non-condensing)
90%RH or less (non-condensing)
80%RH or less (non-condensing)
Ambience
Altitude
Indoors (no direct sunlight) Free from corrosive gas, flammable gas, oil mist, dust and dirt
Max. 1000m (3280 ft) above sea level
HF-MP series HF-KP series
HF-SP51 81 HF-SP52 to 152
HF-SP524 to 1524 HC-RP Series
HC-UP72 152
X, Y: 49 m/s2
X, Y: 24.5 m/s2
HF-SP121 201 HF-SP202 352
HF-SP2024 3524 HC-UP202 to 502
HF-SP301 421 HF-SP502 702
HF-SP5024 7024
X: 24.5 m/s2 Y: 49 m/s2
X: 24.5 m/s2 Y: 29.4 m/s2
(Note)
[m/s2]
5.9 or less
Vibration
HC-LP52 to 152
X: 9.8 m/s2 Y: 24.5 m/s2
X: 19.6 m/s2 Y: 49 m/s2
HC-LP202 to 302
HA-LP601 to 12K1 HA-LP701M to 15K1M
HA-LP502 to 22K2 HA-LP6014 12K14
X: 11.7 m/s2 Y: 29.4 m/s2
HA-LP701M4 15K1M4 HA-LP11K24 to 22K24
HA-LP15K1 to 37K1 HA-LP22K1M to 37K1M
HA-LP30K2 37K2 HA-LP15K14 to 37K14
HA-LP22K1M4 to 50K1M4 HA-LP30K24 to 55K24
X, Y: 9.8 m/s2
Note. Except the servo motor with reduction gear.
A - 3
CAUTION
Provide adequate protection to prevent screws and other conductive matter, oil and other combustible
matter from entering the converter unit, servo amplifier (drive unit), and servo motor.
Do not drop or strike converter unit, servo amplifier (drive unit), or servo motor. Isolate from all impact
loads.
Securely attach the servo motor to the machine. If attach insecurely, the servo motor may come off during
operation.
The servo motor with reduction gear must be installed in the specified direction to prevent oil leakage.
Take safety measures, e.g. provide covers, to prevent accidental access to the rotating parts of the servo
motor during operation.
Never hit the servo motor or shaft, especially when coupling the servo motor to the machine. The encoder
may become faulty.
Do not subject the servo motor shaft to more than the permissible load. Otherwise, the shaft may break.
When the equipment has been stored for an extended period of time, consult Mitsubishi.
(2) Wiring
CAUTION
Wire the equipment correctly and securely. Otherwise, the servo motor may operate unexpectedly.
Do not install a power capacitor, surge absorber or radio noise filter (FR-BIF (-H) option) between the
servo motor and servo amplifier (drive unit).
Connect the wires to the correct phase terminals (U, V, W) of the servo amplifier (drive unit) and servo
motor. Otherwise, the servo motor does not operate properly.
Connect the servo motor power terminal (U, V, W) to the servo motor power input terminal (U, V, W)
directly. Do not let a magnetic contactor, etc. intervene.
Servo amplifier
(drive unit)
Servo amplifier
(drive unit)
Servo motor
Servo motor
U
V
U
V
U
V
U
V
M
M
W
W
W
W
Do not connect AC power directly to the servo motor. Otherwise, a fault may occur.
The surge absorbing diode installed on the DC output signal relay of the servo amplifier (drive unit) must
be wired in the specified direction. Otherwise, the forced stop (EM1) and other protective circuits may not
operate.
Servo amplifier
(drive unit)
Servo amplifier
(drive unit)
24VDC
24VDC
DOCOM
DICOM
DOCOM
DICOM
Control
output
signal
Control
output
signal
RA
RA
When the cable is not tightened enough to the terminal block (connector), the cable or terminal block
(connector) may generate heat because of the poor contact. Be sure to tighten the cable with specified
torque.
A - 4
(3) Test run adjustment
CAUTION
Before operation, check the parameter settings. Improper settings may cause some machines to perform
unexpected operation.
The parameter settings must not be changed excessively. Operation will be insatiable.
(4) Usage
CAUTION
Provide an external emergency stop circuit to ensure that operation can be stopped and power switched
off immediately.
Any person who is involved in disassembly and repair should be fully competent to do the work.
Before resetting an alarm, make sure that the run signal of the servo amplifier (drive unit) is off to prevent
an accident. A sudden restart is made if an alarm is reset with the run signal on.
Do not modify the equipment.
Use a noise filter, etc. to minimize the influence of electromagnetic interference, which may be caused by
electronic equipment used near the converter unit and servo amplifier (drive unit).
Burning or breaking a converter unit and servo amplifier (drive unit) may cause a toxic gas. Do not burn or
break a converter unit and servo amplifier (drive unit).
Use the converter unit and servo amplifier (drive unit) with the specified servo motor.
The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be used
for ordinary braking.
For such reasons as service life and mechanical structure (e.g. where a ball screw and the servo motor
are coupled via a timing belt), the electromagnetic brake may not hold the motor shaft. To ensure safety,
install a stopper on the machine side.
A - 5
(5) Corrective actions
CAUTION
When it is assumed that a hazardous condition may take place at the occur due to a power failure or a
product fault, use a servo motor with an electromagnetic brake or an external brake mechanism for the
purpose of prevention.
Configure the electromagnetic brake circuit so that it is activated not only by the servo amplifier (drive unit)
signals but also by an external forced stop (EM1).
Contacts must be open when
servo-off, when an trouble (ALM)
and when an electromagnetic brake
interlock (MBR).
Circuit must be
opened during
forced stop (EM1).
Servo motor
RA EM1
24VDC
Electromagnetic brake
When any alarm has occurred, eliminate its cause, ensure safety, and deactivate the alarm before
restarting operation.
When power is restored after an instantaneous power failure, keep away from the machine because the
machine may be restarted suddenly (design the machine so that it is secured against hazard if restarted).
(6) Maintenance, inspection and parts replacement
CAUTION
With age, the electrolytic capacitor of the converter unit and servo amplifier (drive unit) will deteriorate. To
prevent a secondary accident due to a fault, it is recommended to replace the electrolytic capacitor every
10 years when used in general environment.
Please consult our sales representative.
(7) General instruction
To illustrate details, the equipment in the diagrams of this Specifications and Instruction Manual may have
been drawn without covers and safety guards. When the equipment is operated, the covers and safety
guards must be installed as specified. Operation must be performed in accordance with this Specifications
and Instruction Manual.
A - 6
About processing of waste
When you discard converter unit and servo amplifier (drive unit), a battery (primary battery), and other option
articles, please follow the law of each country (area).
FOR MAXIMUM SAFETY
These products have been manufactured as a general-purpose part for general industries, and have not
been designed or manufactured to be incorporated in a device or system used in purposes related to
human life.
Before using the products for special purposes such as nuclear power, electric power, aerospace,
medicine, passenger movement vehicles or under water relays, contact Mitsubishi.
These products have been manufactured under strict quality control. However, when installing the product
where major accidents or losses could occur if the product fails, install appropriate backup or failsafe
functions in the system.
EEP-ROM life
The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If
the total number of the following operations exceeds 100,000, the converter unit, servo amplifier (drive unit)
and/or converter unit may fail when the EEP-ROM reaches the end of its useful life.
Write to the EEP-ROM due to parameter setting changes
Write to the EEP-ROM due to device changes
Precautions for Choosing the Products
Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi;
machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage,
accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other
than Mitsubishi products; and to other duties.
A - 7
COMPLIANCE WITH EC DIRECTIVES
1. WHAT ARE EC DIRECTIVES?
The EC directives were issued to standardize the regulations of the EU countries and ensure smooth
distribution of safety-guaranteed products. In the EU countries, the machinery directive (effective in January,
1995), EMC directive (effective in January, 1996) and low voltage directive (effective in January, 1997) of the
EC directives require that products to be sold should meet their fundamental safety requirements and carry the
CE marks (CE marking). CE marking applies to machines and equipment into which servo have been installed.
(1) EMC directive
The EMC directive applies not to the servo units alone but to servo-incorporated machines and equipment.
This requires the EMC filters to be used with the servo-incorporated machines and equipment to comply
with the EMC directive. For specific EMC directive conforming methods, refer to the EMC Installation
Guidelines (IB(NA)67310).
(2) Low voltage directive
The low voltage directive applies also to servo units alone. Hence, they are designed to comply with the low
voltage directive.
This servo is certified by TUV, third-party assessment organization, to comply with the low voltage directive.
(3) Machine directive
Not being machines, the converter unit, servo amplifiers (drive unit) need not comply with this directive.
2. PRECAUTIONS FOR COMPLIANCE
(1) Converter unit, servo amplifiers (drive unit), and servo motors used
Use the converter unit, servo amplifiers (drive unit), and servo motors which comply with the standard
model.
Converter unit series
:MR-J3-CR55K
MR-J3-CR55K4
Servo amplifier (drive unit) series :MR-J3-10B to MR-J3-22KB
MR-J3-10B1 to MR-J3-40B1
MR-J3-60B4 to MR-J3-22KB4
MR-J3-DU30KB to MR-J3-DU37KB
MR-J3-DU30KB4 to MR-J3-DU55KB4
Servo motor series
:HF-MP
HF-KP
HF-SP (Note)
HF-SP 4(Note)
HC-RP
HC-UP
HC-LP
HA-LP (Note)
HA-LP 4 (Note)
Note. For the latest information of compliance, contact Mitsubishi.
A - 8
(2) Configuration
The control circuit provide safe separation to the main circuit in the converter unit and servo amplifier (drive
unit).
(a) MR-J3-22KB(4) or less
Control box
Reinforced
insulating type
24VDC
power
supply
No-fuse
breaker
Magnetic
contactor
Servo
motor
Servo
amplifier
NFB
MC
M
(b) MR-J3-DU30KB(4) or more
Control box
Reinforced
insulating type
24VDC
power
supply
No-fuse
breaker
Magnetic
contactor
Servo
motor
Converter
unit
Drive
unit
NFB
MC
M
(3) Environment
Operate the converter unit and servo amplifier (drive unit) at or above the contamination level 2 set forth in
IEC60664-1. For this purpose, install the converter unit and servo amplifier (drive unit) in a control box
which is protected against water, oil, carbon, dust, dirt, etc. (IP54).
(4) Power supply
(a) This converter unit and servo amplifier (drive unit) can be supplied from star-connected supply with
earthed neutral point of overvoltage category III set forth in IEC60664-1. However, when using the
neutral point of 400V class for single-phase supply, a reinforced insulating transformer is required in the
power input section.
(b) When supplying interface power from external, use a 24VDC power supply which has been insulation-
reinforced in I/O.
(5) Grounding
(a) To prevent an electric shock, always connect the protective earth (PE) terminals (marked ) of the
converter unit and servo amplifier (drive unit) to the protective earth (PE) of the control box.
A - 9
(b) Do not connect two ground cables to the same protective earth (PE) terminal. Always connect the
cables to the terminals one-to-one.
PE terminals
PE terminals
(c) If a leakage current breaker is used to prevent an electric shock, the protective earth (PE) terminals of
the converter unit and servo amplifier (drive unit) must be connected to the corresponding earth
terminals.
(6) Wiring
(a) The cables to be connected to the terminal block of the converter unit and servo amplifier (drive unit)
must have crimping terminals provided with insulating tubes to prevent contact with adjacent terminals.
Crimping terminal
Insulating tube
Cable
(b) Use the servo motor side power connector which complies with the EN Standard. The EN Standard
compliant power connector sets are available from us as options. (Refer to section 11.1)
(7) Auxiliary equipment and options
(a) The no-fuse breaker and magnetic contactor used should be the EN or IEC standard-compliant
products of the models described in section 11.12 (Section 13.9.5 for 30kW or more).
Use a type B (Note) breaker. When it is not used, provide insulation between the converter unit, servo
amplifier (drive unit) and other device by double insulation or reinforced insulation, or install a
transformer between the main power supply, converter unit and servo amplifier (drive unit).
Note. Type A: AC and pulse detectable
Type B: Both AC and DC detectable
(b) The sizes of the cables described in section 11.8 meet the following requirements. To meet the other
requirements, follow Table 5 and Appendix C in EN60204-1.
Ambient temperature: 40 (104) [°C (°F)]
Sheath: PVC (polyvinyl chloride)
Installed on wall surface or open table tray
(c) Use the EMC filter for noise reduction.
(8) Performing EMC tests
When EMC tests are run on a machine/device into which the converter unit and servo amplifier (drive unit)
has been installed, it must conform to the electromagnetic compatibility (immunity/emission) standards after
it has satisfied the operating environment/electrical equipment specifications.
For the other EMC directive guidelines on the converter unit and servo amplifier (drive unit), refer to the
EMC Installation Guidelines(IB(NA)67310).
A - 10
CONFORMANCE WITH UL/C-UL STANDARD
(1) Converter unit, servo amplifiers (drive unit) and servo motors used
Use the converter unit, servo amplifiers (drive unit) and servo motors which comply with the standard model.
Converter unit series
:MR-J3-CR55K
MR-J3-CR55K4
Servo amplifier (drive unit) series :MR-J3-10B to MR-J3-22KB
MR-J3-10B1 to MR-J3-40B1
MR-J3-60B4 to MR-J3-22KB4
MR-J3-DU30KB to MR-J3-DU37KB
MR-J3-DU30KB4 to MR-J3-DU55KB4
Servo motor series
:HF-MP
HF-KP
HF-SP (Note)
HF-SP 4 (Note)
HC-RP
HC-UP
HC-LP
HA-LP (Note)
HA-LP 4 (Note)
Note. For the latest information of compliance, contact Mitsubishi.
(2) Installation
Install a fan of 100CFM (2.8m3/min) air flow 4[in] (10.16[cm]) above the servo amplifier (drive unit) or
provide cooling of at least equivalent capability to ensure that the ambient temperature conforms to the
environment conditions (55 or less).
(3) Short circuit rating: SCCR (Short Circuit Current Rating)
This servo amplifier (drive unit) conforms to the circuit whose peak current is limited to 100kA or less,
500Volts Maximum. Having been subjected to the short-circuit tests of the UL in the alternating-current
circuit, the servo amplifier (drive unit) conforms to the above circuit.
A - 11
(4) Capacitor discharge time
The capacitor discharge time is as listed below. To ensure safety, do not touch the charging section for 15
minutes (more than 20 minutes in case drive unit is 30kW or more) after power-off.
Servo amplifier
MR-J3-10B 20B
Discharge time [min]
1
2
MR-J3-40B 60B(4) 10B1 20B1
MR-J3-70B
3
MR-J3-40B1
4
MR-J3-100B(4)
5
MR-J3-200B(4) 350B
MR-J3-350B4 500B(4) 700B(4)
MR-J3-11KB(4)
9
10
4
MR-J3-15KB(4)
6
MR-J3-22KB(4)
8
Converter unit
MR-J3-CR55K
Drive unit
Discharge time [min]
MR-J3-DU30KB
MR-J3-DU37KB
MR-J3-DU30KB4
MR-J3-DU37KB4
MR-J3-DU45KB4
MR-J3-DU55KB4
20
MR-J3-CR55K4
(5) Options and auxiliary equipment
Use UL/C-UL standard-compliant products.
(6) Attachment of a servo motor
For the flange size of the machine side where the servo motor is installed, refer to “CONFORMANCE WITH
UL/C-UL STANDARD” in the Servo Motor Instruction Manual (Vol.2).
(7) About wiring protection
For installation in United States, branch circuit protection must be provided, in accordance with the National
Electrical Code and any applicable local codes.
For installation in Canada, branch circuit protection must be provided, in accordance with the Canada
Electrical Code and any applicable provincial codes.
A - 12
<<About the manuals>>
This Instruction Manual and the MELSERVO Servo Motor Instruction Manual (Vol.2) are required if you use
the General-Purpose AC servo MR-J3-B for the first time. Always purchase them and use the MR-J3-B
safely.
Relevant manuals
Manual name
Manual No.
MELSERVO-J3 Series Instructions and Cautions for Safe Use of AC Servos
(Enclosed in converter unit and servo amplifier (drive unit).)
MELSERVO Servo Motor Instruction Manual Vol.2
EMC Installation Guidelines
IB(NA)0300077
SH(NA)030041
IB(NA)67310
Details of MR-J3-CR55K(4) and MR-J3-DU30KB(4) to MR-J3-DU55KB4 are described in chapter 13 of this
INSTRUCTION MANUAL.
For the products of 30kW or more, refer to chapter 13.
<<About the wires used for wiring>>
Wiring wires mentioned in this instruction manual are selected based on the ambient temperature of 40°C
(104 ).
A - 13
MEMO
A - 14
CONTENTS
1. FUNCTIONS AND CONFIGURATION
1 - 1 to 1 -28
1.1 Introduction............................................................................................................................................... 1 - 1
1.2 Function block diagram............................................................................................................................ 1 - 2
1.3 Servo amplifier standard specifications................................................................................................... 1 - 5
1.4 Function list .............................................................................................................................................. 1 - 7
1.5 Model code definition............................................................................................................................... 1 - 8
1.6 Combination with servo motor................................................................................................................1 -10
1.7 Structure..................................................................................................................................................1 -11
1.7.1 Parts identification............................................................................................................................1 -11
1.7.2 Removal and reinstallation of the front cover..................................................................................1 -18
1.8 Configuration including auxiliary equipment...........................................................................................1 -21
2. INSTALLATION
2 - 1 to 2 - 6
2.1 Installation direction and clearances ....................................................................................................... 2 - 1
2.2 Keep out foreign materials....................................................................................................................... 2 - 3
2.3 Cable stress ............................................................................................................................................. 2 - 3
2.4 SSCNET cable laying............................................................................................................................ 2 - 4
2.5 Inspection items ....................................................................................................................................... 2 - 6
2.6 Parts having service lives ........................................................................................................................ 2 - 6
3. SIGNALS AND WIRING
3 - 1 to 3 -52
3.1 Input power supply circuit ........................................................................................................................ 3 - 2
3.2 I/O signal connection example ...............................................................................................................3 -10
3.3 Explanation of power supply system......................................................................................................3 -12
3.3.1 Signal explanations ..........................................................................................................................3 -12
3.3.2 Power-on sequence .........................................................................................................................3 -13
3.3.3 CNP1, CNP2, CNP3 wiring method ................................................................................................3 -14
3.4 Connectors and signal arrangements ....................................................................................................3 -23
3.5 Signal (device) explanations...................................................................................................................3 -24
3.6 Alarm occurrence timing chart................................................................................................................3 -27
3.7 Interfaces.................................................................................................................................................3 -28
3.7.1 Internal connection diagram ............................................................................................................3 -28
3.7.2 Detailed description of interfaces.....................................................................................................3 -29
3.7.3 Source I/O interfaces .......................................................................................................................3 -31
3.8 Treatment of cable shield external conductor........................................................................................3 -32
3.9 SSCNET cable connection ..................................................................................................................3 -33
3.10 Connection of servo amplifier and servo motor ...................................................................................3 -35
3.10.1 Connection instructions..................................................................................................................3 -35
3.10.2 Power supply cable wiring diagrams.............................................................................................3 -36
3.11 Servo motor with an electromagnetic brake.........................................................................................3 -46
3.11.1 Safety precautions .........................................................................................................................3 -46
3.11.2 Timing charts..................................................................................................................................3 -47
3.11.3 Wiring diagrams (HF-MP series HF-KP series servo motor) .....................................................3 -50
3.12 Grounding..............................................................................................................................................3 -51
1
3.13 Control axis selection............................................................................................................................3 -52
4. STARTUP 4 - 1 to 4 -10
4.1 Switching power on for the first time ....................................................................................................... 4 - 1
4.1.1 Startup procedure.............................................................................................................................. 4 - 1
4.1.2 Wiring check...................................................................................................................................... 4 - 2
4.1.3 Surrounding environment.................................................................................................................. 4 - 3
4.2 Start up ..................................................................................................................................................... 4 - 4
4.3 Servo amplifier display............................................................................................................................. 4 - 5
4.4 Test operation .......................................................................................................................................... 4 - 7
4.5 Test operation mode................................................................................................................................ 4 - 8
4.5.1 Test operation mode in MR Configurator......................................................................................... 4 - 8
4.5.2 Motorless operation in controller......................................................................................................4 -10
5. PARAMETERS
5 - 1 to 5 -28
5.1 Basic setting parameters (No.PA
)..................................................................................................... 5 - 1
5.1.1 Parameter list .................................................................................................................................... 5 - 2
5.1.2 Parameter write inhibit ...................................................................................................................... 5 - 3
5.1.3 Selection of regenerative option ....................................................................................................... 5 - 4
5.1.4 Using absolute position detection system ........................................................................................ 5 - 5
5.1.5 Forced stop input selection............................................................................................................... 5 - 5
5.1.6 Auto tuning ........................................................................................................................................ 5 - 6
5.1.7 In-position range................................................................................................................................ 5 - 7
5.1.8 Selection of servo motor rotation direction....................................................................................... 5 - 8
5.1.9 Encoder output pulse ........................................................................................................................ 5 - 8
5.2 Gain/filter parameters (No. PB
).......................................................................................................5 - 10
5.2.1 Parameter list ..................................................................................................................................5 - 10
5.2.2 Detail list ...........................................................................................................................................5 -11
5.3 Extension setting parameters (No. PC
) ...........................................................................................5 -18
5.3.1 Parameter list ...................................................................................................................................5 -18
5.3.2 List of details.....................................................................................................................................5 -19
5.3.3 Analog monitor .................................................................................................................................5 -22
5.3.4 Alarm history clear............................................................................................................................5 -24
5.4 I/O setting parameters (No. PD
).......................................................................................................5 -25
5.4.1 Parameter list ...................................................................................................................................5 -25
5.4.2 List of details.....................................................................................................................................5 -26
6. GENERAL GAIN ADJUSTMENT
6 - 1 to 6 -12
6.1 Different adjustment methods.................................................................................................................. 6 - 1
6.1.1 Adjustment on a single servo amplifier............................................................................................. 6 - 1
6.1.2 Adjustment using MR Configurator................................................................................................... 6 - 2
6.2 Auto tuning ............................................................................................................................................... 6 - 3
6.2.1 Auto tuning mode .............................................................................................................................. 6 - 3
6.2.2 Auto tuning mode operation.............................................................................................................. 6 - 4
6.2.3 Adjustment procedure by auto tuning............................................................................................... 6 - 5
6.2.4 Response level setting in auto tuning mode .................................................................................... 6 - 6
6.3 Manual mode 1 (simple manual adjustment).......................................................................................... 6 - 7
2
6.4 Interpolation mode ..................................................................................................................................6 -11
6.5 Differences between MELSERVO-J2-Super and MELSERVO-J3 in auto tuning................................6 -12
7. SPECIAL ADJUSTMENT FUNCTIONS
7 - 1 to 7 -16
7.1 Function block diagram............................................................................................................................ 7 - 1
7.2 Adaptive filter ......................................................................................................................................... 7 - 1
7.3 Machine resonance suppression filter..................................................................................................... 7 - 4
7.4 Advanced vibration suppression control ................................................................................................. 7 - 6
7.5 Low-pass filter .........................................................................................................................................7 -10
7.6 Gain changing function ...........................................................................................................................7 -10
7.6.1 Applications ......................................................................................................................................7 -10
7.6.2 Function block diagram....................................................................................................................7 -11
7.6.3 Parameters.......................................................................................................................................7 -12
7.6.4 Gain changing operation..................................................................................................................7 -14
8. TROUBLESHOOTING
8 - 1 to 8 -10
8.1 Alarms and warning list............................................................................................................................ 8 - 1
8.2 Remedies for alarms................................................................................................................................ 8 - 2
8.3 Remedies for warnings ............................................................................................................................ 8 - 8
9. OUTLINE DRAWINGS
9 - 1 to 9 -12
9.1 Servo amplifier ......................................................................................................................................... 9 - 1
9.2 Connector................................................................................................................................................9 -10
10. CHARACTERISTICS
10- 1 to 10-10
10.1 Overload protection characteristics......................................................................................................10- 1
10.2 Power supply equipment capacity and generated loss .......................................................................10- 3
10.3 Dynamic brake characteristics..............................................................................................................10- 6
10.3.1 Dynamic brake operation...............................................................................................................10- 6
10.3.2 The dynamic brake at the load inertia moment.............................................................................10- 9
10.4 Cable flexing life...................................................................................................................................10-10
10.5 Inrush currents at power-on of main circuit and control circuit...........................................................10-10
11. OPTIONS AND AUXILIARY EQUIPMENT
11- 1 to 11-90
11.1 Cable/connector sets ............................................................................................................................11- 1
11.1.1 Combinations of cable/connector sets ..........................................................................................11- 2
11.1.2 Encoder cable/connector sets .......................................................................................................11- 8
11.1.3 Motor power supply cables...........................................................................................................11-17
11.1.4 Motor brake cables........................................................................................................................11-18
11.1.5 SSCNET cable ...........................................................................................................................11-19
11.2 Regenerative options...........................................................................................................................11-21
11.3 FR-BU2-(H) Brake unit.........................................................................................................................11-34
11.3.1 Selection........................................................................................................................................11-35
11.3.2 Brake unit parameter setting.........................................................................................................11-35
11.3.3 Connection example .....................................................................................................................11-36
3
11.3.4 Outline dimension drawings..........................................................................................................11-43
11.4 Power regeneration converter .............................................................................................................11-45
11.5 Power regeneration common converter..............................................................................................11-48
11.6 External dynamic brake .......................................................................................................................11-56
11.7 Junction terminal block PS7DW-20V14B-F (recommended).............................................................11-61
11.8 MR Configurator...................................................................................................................................11-62
11.9 Battery MR-J3BAT...............................................................................................................................11-64
11.10 Heat sink outside mounting attachment (MR-J3ACN)......................................................................11-65
11.11 Selection example of wires................................................................................................................11-67
11.12 No-fuse breakers, fuses, magnetic contactors .................................................................................11-72
11.13 Power factor improving DC reactor ...................................................................................................11-72
11.14 Power factor improving AC reactors .................................................................................................11-74
11.15 Relays (recommended) .....................................................................................................................11-75
11.16 Surge absorbers (recommended) .....................................................................................................11-76
11.17 Noise reduction techniques ...............................................................................................................11-76
11.18 Leakage current breaker....................................................................................................................11-83
11.19 EMC filter (recommended) ................................................................................................................11-85
12. ABSOLUTE POSITION DETECTION SYSTEM
12- 1 to 12- 6
12.1 Features ................................................................................................................................................12- 1
12.2 Specifications ........................................................................................................................................12- 2
12.3 Battery installation procedure...............................................................................................................12- 3
12.4 Confirmation of absolute position detection data.................................................................................12- 5
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13- 1 to 13-102
13.1. Functions and menus...........................................................................................................................13- 1
13.1.1 Function block diagram..................................................................................................................13- 2
13.1.2 Packing list .....................................................................................................................................13- 4
13.1.3 Standard specifications..................................................................................................................13- 5
13.1.4 Model definition ..............................................................................................................................13- 8
13.1.5 Combinations of converter units, drive unit and servo motors .....................................................13- 9
13.1.6 Parts identification.........................................................................................................................13-10
13.1.7 Removal and reinstallation of the terminal block cover ...............................................................13-13
13.1.8 Servo system with auxiliary equipment ........................................................................................13-19
13.2 Installation ............................................................................................................................................13-20
13.2.1 Installation direction and clearances ............................................................................................13-21
13.2.2 Inspection ......................................................................................................................................13-22
13.3 Signals and wiring................................................................................................................................13-23
13.3.1 Magnetic contactor control connector (CNP1).............................................................................13-24
13.3.2 Input power supply circuit .............................................................................................................13-26
13.3.3 Terminal.........................................................................................................................................13-31
13.3.4 How to use the connection bars ...................................................................................................13-32
13.3.5 Connectors and signal arrangements ..........................................................................................13-33
13.3.6 Converter unit signal (device) explanations .................................................................................13-35
13.3.7 Timing chart...................................................................................................................................13-37
13.3.8 Servo motor side details ...............................................................................................................13-47
13.4 Display section and operation section of the converter unit...............................................................13-49
4
13.4.1 Display flowchart ...........................................................................................................................13-49
13.4.2 Status display mode......................................................................................................................13-50
13.4.3 Diagnostic mode............................................................................................................................13-51
13.4.4 Alarm mode ...................................................................................................................................13-53
13.4.5 Parameter mode ...........................................................................................................................13-54
13.5. Parameters for converter unit.............................................................................................................13-55
13.5.1 Parameter list ................................................................................................................................13-55
13.5.2 List of details..................................................................................................................................13-56
13.6 Troubleshooting ...................................................................................................................................13-57
13.6.1 Converter unit................................................................................................................................13-57
13.6.2 Drive unit........................................................................................................................................13-62
13.7 Outline drawings ..................................................................................................................................13-64
13.7.1 Converter unit (MR-J3-CR55K(4))................................................................................................13-64
13.7.2 Drive unit........................................................................................................................................13-65
13.8 Characteristics......................................................................................................................................13-67
13.8.1 Overload protection characteristics ..............................................................................................13-67
13.8.2 Power supply equipment capacity and generated loss ...............................................................13-68
13.8.3 Dynamic brake characteristics......................................................................................................13-69
13.8.4 Inrush currents at power-on of main circuit and control circuit....................................................13-72
13.9 Options .................................................................................................................................................13-72
13.9.1 Cables and connectors .................................................................................................................13-72
13.9.2 Regenerative option......................................................................................................................13-75
13.9.3 External dynamic brake ................................................................................................................13-79
13.9.4 Selection example of wires...........................................................................................................13-82
13.9.5 No-fuse breakers, fuses, magnetic contactors.............................................................................13-84
13.9.6 Power factor improving DC reactor ..............................................................................................13-84
13.9.7 Line noise filter (FR-BLF)..............................................................................................................13-85
13.9.8 Leakage current breaker...............................................................................................................13-86
13.9.9 EMC filter (recommended)............................................................................................................13-88
13.9.10 FR-BU2-(H) Brake Unit...............................................................................................................13-90
APPENDIX
App.- 1 to App.- 9
App. 1 Parameter list..................................................................................................................................App.- 1
App. 2 Signal layout recording paper ........................................................................................................App.- 3
App. 3 Twin type connector : Outline drawing for 721-2105/026-000 (WAGO).......................................App.- 3
App. 4 Change of connector sets to the RoHS compatible products.......................................................App.- 4
App. 5 MR-J3-200B-RT servo amplifier ....................................................................................................App.- 5
App. 6 Selection example of servo motor power cable ............................................................................App.- 9
5
MEMO
6
1. FUNCTIONS AND CONFIGURATION
1. FUNCTIONS AND CONFIGURATION
1.1 Introduction
The Mitsubishi MELSERVO-J3 series general-purpose AC servo has further higher performance and higher
functions compared to the current MELSERVO-J2-Super series.
The MR-J3-B servo amplifier connects to servo system controller and others via high speed synchronous
network and operates by directly reading position data. The rotation speed/direction control of servo motor and
the high accuracy positioning are executed with the data from command module. SSCNET equipped by the
MR-J3-B servo amplifier greatly improved its communication speed and noise tolerance by adopting optical
communication system compared to the current SSCNET. For wiring distance, 50m of the maximum distance
between electrodes is also offered.
The torque limit with clamping circuit is put on the servo amplifier in order to protect the power transistor of
main circuit from the overcurrent caused by rapid acceleration/deceleration or overload. In addition, torque limit
value can be changed to desired value in the controller.
As this new series has the USB communication function, a MR Configurator-installed personal computer or the
like can be used to perform parameter setting, test operation, status display monitoring, gain adjustment, etc.
With real-time auto tuning, you can automatically adjust the servo gains according to the machine.
The MELSERVO-J3 series servo motor is with an absolute position encoder which has the resolution of
262144 pulses/rev to ensure more accurate control as compared to the MELSERVO-J2-Super series. Simply
adding a battery to the servo amplifier makes up an absolute position detection system. This makes home
position return unnecessary at power-on or alarm occurrence by setting a home position once.
1 - 1
1. FUNCTIONS AND CONFIGURATION
1.2 Function block diagram
The function block diagram of this servo is shown below.
(1) MR-J3-350B or less MR-J3-200B4 or less
Power factor
improving DC Regenerative
reactor
option
N(
)
Servo amplifier
P( ) C
D
Servo motor
U
P1
P2
Diode
stack
(Note 1)
Relay
NFB MC
U
V
L1
L2
L3
(Note 2)
Power
supply
V
Current
detector
M
W
W
CHARGE
lamp
Regene-
rative
TR
Dynamic
brake
(Note 3)Cooling fan
RA
L11
Electro-
magnetic
brake
Control
circuit
power
supply
24VDC B1
B2
L21
Base
amplifier
Voltage Overcurrent Current
detection protection detection
Encoder
Position
command
input
Virtual
encoder
Model position
control
Model speed
control
Virtual
motor
Model
position
Model
speed
Model
torque
Actual position
control
Actual speed
control
Current
control
MR-J3BAT
USB
CN5
D/A
I/F Control
Optional battery
(for absolute position
detection system)
CN1A
CN1B
CN3
Personal
computer
Analog monitor
(2 channels)
Digital I/O
control
Controller or Servo amplifier
servo amplifier or cap
USB
Note 1. The built-in regenerative resistor is not provided for the MR-J3-10B (1).
2. For 1-phase 200 to 230VAC, connect the power supply to L1, L2 and leave L3 open.
There is no L3 for 1-phase 100 to 120VAC power supply. Refer to section 1.3 for the power supply specification.
3. Servo amplifiers MR-J3-70B or greater have a cooling fan.
1 - 2
1. FUNCTIONS AND CONFIGURATION
(2) MR-J3-350B4 MR-J3-500B(4) MR-J3-700B(4)
Power factor
improving DC Regenerative
reactor
option
N
Servo amplifier
P
C
Servo motor
U
P1
P2
Diode
stack
Relay
NFB MC
U
V
L1
L2
L3
(Note)
Power
supply
V
Current
detector
M
W
W
CHARGE
lamp
Regene-
rative
TR
Dynamic
brake
Cooling fan
RA
L11
Electro-
magnetic
brake
Control
24VDC B1
B2
circuit
power
supply
L21
Base
amplifier
Voltage Overcurrent Current
detection protection detection
Encoder
Position
command
input
Virtual
encoder
Model position
control
Model speed
control
Virtual
motor
Model
position
Model
speed
Model
torque
Actual position
control
Actual speed
control
Current
control
MR-J3BAT
USB
CN5
D/A
I/F Control
Optional battery
(for absolute position
detection system)
CN1A
CN1B
CN3
Personal
computer
Analog monitor
(2 channels)
Digital I/O
control
Controller or Servo amplifier
servo amplifier or cap
USB
Note. Refer to section 1.3 for the power supply specification.
1 - 3
1. FUNCTIONS AND CONFIGURATION
(3) MR-J3-11KB(4) to 22KB(4)
Power factor
improving DC Regenerative
reactor
option
N
Servo amplifier
P
C
Servo motor
U
P1
Diode
stack
Thyristor
NFB MC
U
V
L1
L2
L3
(Note)
Power
supply
V
Current
detector
M
W
W
CHARGE
lamp
Regene-
rative
TR
Dynamic
brake
Cooling fan
RA
L11
Electro-
magnetic
brake
Control
24VDC B1
B2
circuit
power
supply
L21
Base
amplifier
Voltage Overcurrent Current
detection protection detection
Encoder
Position
command
input
Virtual
encoder
Model position
control
Model speed
control
Virtual
motor
Model
position
Model
speed
Model
torque
Actual position
control
Actual speed
control
Current
control
MR-J3BAT
USB
CN5
D/A
I/F Control
Optional battery
(for absolute position
detection system)
CN1A
CN1B
CN3
Personal
computer
Analog monitor
(2 channels)
Digital I/O
control
Controller or Servo amplifier
servo amplifier or cap
USB
Note. Refer to section 1.3 for the power supply specification.
1 - 4
1. FUNCTIONS AND CONFIGURATION
1.3 Servo amplifier standard specifications
(1) 200V class, 100V class
Servo amplifier
MR-J3-
10B 20B 40B 60B 70B 100B 200B 350B 500B 700B 11KB 15KB 22KB 10B1 20B1 40B1
Item
Voltage/frequency
3-phase or 1-phase 200
to 230VAC, 50/60Hz
3-phase or 1-phase 200
to 230VAC: 170 to
253VAC
1-phase 100V to
120VAC, 50/60Hz
3-phase 200 to 230VAC, 50/60Hz
3-phase 170 to 253VAC
1-phase 85 to
132VAC
Permissible voltage fluctuation
Permissible frequency fluctuation
Power supply capacity
Inrush current
Voltage,
Within 5%
Refer to section 10.2
Refer to section 10.5
1-phase 100 to
1-phase 200 to 230VAC, 50/60Hz
frequency
120VAC, 50/60Hz
Permissible
1-phase 85 to
132VAC
voltage
1-phase 170 to 253VAC
fluctuation
Permissible
frequency
fluctuation
Input
Control circuit
power supply
Within 5%
30W
45W
30W
Inrush current
Voltage
Refer to section 10.5
24VDC 10%
Interface power
supply
Power supply
capacity
(Note 1) 150mA or more
Control System
Dynamic brake
Sine-wave PWM control, current control system
Built-in
External option
Built-in
Overcurrent shut-off, regenerative overvoltage shut-off, overload shut-off (electronic thermal relay),
servo motor overheat protection, encoder error protection, regenerative error protection,
undervoltage, instantaneous power failure protection, overspeed protection, excessive error
protection.
Protective functions
Self-cooled, open
(IP00)
Self-cooled, open
(IP00)
Structure
Force-cooling, open (IP00)
In
operation
[
[
[
[
]
(Note 2) 0 to 55 (non-freezing)
32 to 131 (non-freezing)
20 to 65 (non-freezing)
4 to 149 (non-freezing)
Ambient
]
temperature
]
In storage
]
Ambient
humidity
In operation
In storage
90%RH or less (non-condensing)
Indoors (no direct sunlight)
Free from corrosive gas, flammable gas, oil mist, dust and dirt
Max. 1000m above sea level
Ambient
Altitude
Vibration
5.9 [m/s2] or less
[kg] 0.8 0.8 1.0 1.0 1.4 1.4 2.1 2.3 4.6 6.2
18
18
19
0.8
0.8
1.0
Mass
[lb] 1.76 1.76 2.21 2.21 3.09 3.09 4.63 5.07 10.1 13.7 39.7 39.7 41.9 1.76 1.76 2.21
Note 1. 150mA is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of
I/O points.
2. When closely mounting the servo amplifier of 3.5kW or less, operate them at the ambient temperatures of 0 to 45 or at 75% or
smaller effective load ratio.
1 - 5
1. FUNCTIONS AND CONFIGURATION
(2) 400V class
Servo amplifier
MR-J3-
60B4
100B4
200B4
350B4
500B4
700B4
11KB4
15KB4
22KB4
Item
Voltage/frequency
3-phase 380 to 480VAC, 50/60Hz
3-phase 323 to 528VAC
Permissible voltage fluctuation
Permissible frequency
fluctuation
Within 5%
Power supply capacity
Inrush current
Voltage,
Refer to section 10.2
Refer to section 10.5
1-phase 380 to 480VAC, 50/60Hz
frequency
Permissible
voltage
1-phase 323 to 528VAC
fluctuation
Permissible
frequency
fluctuation
Input
Control circuit
power supply
Within 5%
30W
45W
Inrush current
Voltage
Refer to section 10.5
24VDC 10%
Interface power
supply
Power supply
capacity
(Note) 150mA
Control System
Dynamic brake
Sine-wave PWM control, current control system
Built-in
External option
Overcurrent shut-off, regenerative overvoltage shut-off, overload shut-off (electronic thermal relay),
servo motor overheat protection, encoder error protection, regenerative error protection,
undervoltage, instantaneous power failure protection, overspeed protection, excessive error
protection.
Protective functions
Self-cooled, open
Force-cooling, open (IP00)
(IP00)
Structure
In
operation
[
[
[
[
]
0 to 55 (non-freezing)
32 to 131 (non-freezing)
20 to 65 (non-freezing)
4 to 149 (non-freezing)
Ambient
]
temperature
]
In storage
]
Ambient
humidity
In operation
In storage
90%RH or less (non-condensing)
Indoors (no direct sunlight)
Free from corrosive gas, flammable gas, oil mist, dust and dirt
Max. 1000m above sea level
Ambient
Altitude
Vibration
5.9 [m/s2] or less
[kg]
[lb]
1.7
1.7
2.1
4.6
4.6
6.2
18
18
19
Mass
3.75
3.75
4.63
10.14
10.14
13.67
39.68
39.68
41.88
Note. 150mA is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of
I/O points.
1 - 6
1. FUNCTIONS AND CONFIGURATION
1.4 Function list
The following table lists the functions of this servo. For details of the functions, refer to the reference field.
Function
Description
Reference
High-resolution encoder of 262144 pulses/rev is used as a servo motor
encoder.
High-resolution encoder
Absolute position detection
system
Merely setting a home position once makes home position return
unnecessary at every power-on.
Chapter 12
You can switch between gains during rotation and gains during stop or use
an input device to change gains during operation.
Gain changing function
Section 7.6
Section 7.4
Section 7.2
Section 7.5
Advanced vibration
suppression control
This function suppresses vibration at the arm end or residual vibration.
Servo amplifier detects mechanical resonance and sets filter characteristics
automatically to suppress mechanical vibration.
Suppresses high-frequency resonance which occurs as servo system
response is increased.
Adaptive filter
Low-pass filter
Analyzes the frequency characteristic of the mechanical system by simply
connecting a MR Configurator installed personal computer and servo
amplifier.
Machine analyzer function
MR Configurator is necessary for this function.
Can simulate machine motions on a personal computer screen on the basis
of the machine analyzer results.
Machine simulation
Gain search function
MR Configurator is necessary for this function.
Personal computer changes gains automatically and searches for overshoot-
free gains in a short time.
MR Configurator is necessary for this function.
Slight vibration suppression
control
Suppresses vibration of 1 pulse produced at a servo motor stop.
Parameters No.PB24
Chapter 6
Automatically adjusts the gain to optimum value if load applied to the servo
motor shaft varies. Higher in performance than MR-J2-Super series servo
amplifier.
Auto tuning
Brake unit
Used when the regenerative option cannot provide enough regenerative
power.
Can be used the 5kW or more servo amplifier.
Used when the regenerative option cannot provide enough regenerative
power.
Section 11.3
Section 11.4
Return converter
Can be used the 5kW or more servo amplifier.
Used when the built-in regenerative resistor of the servo amplifier does not
have sufficient regenerative capability for the regenerative power generated.
Alarm history is cleared.
Regenerative option
Section 11.2
Alarm history clear
Output signal (DO)
forced output
Parameter No.PC21
Section 4.5.1 (1) (d)
Output signal can be forced on/off independently of the servo status.
Use this function for output signal wiring check, etc.
JOG operation positioning operation DO forced output.
However, MR Configurator is necessary for positioning operation.
Servo status is output in terms of voltage in real time.
Using a personal computer, parameter setting, test operation, status display,
etc. can be performed.
Test operation mode
Analog monitor output
MR Configurator
Section 4.5
Parameter No.PC09
Section 11.8
1 - 7
1. FUNCTIONS AND CONFIGURATION
1.5 Model code definition
(1) Rating plate
AC SERVO
Model
MR-J3-10B
Capacity
POWER : 100W
Applicable power supply
INPUT : 0.9A 3PH+1PH200-230V 50Hz
3PH+1PH200-230V 60Hz
1.3A 1PH 200-230V 50/60Hz
OUTPUT: 170V 0-360Hz 1.1A
SERIAL : A34230001
Rated output current
Serial number
1 - 8
1. FUNCTIONS AND CONFIGURATION
(2) Model
MR-J3-100B or less
MR-J3-60B4 100B4
MR J3
B
With no regenerative resistor
Symbol
Description
Series
Indicates a servo
amplifier of 11k to 22kW
that does not use a
regenerative resistor as
standard accessory.
-PX
Power supply
Symbol
Power supply
Rating plate
MR-J3-350B
Rating plate
3-phase or 1-phase 200
to 230VAC
(Note 1)
None
MR-J3-200B(4)
(Note 2)
1
1-phase 100 to 120VAC
3-phase 380 to 480VAC
4
Note 1. 1-phase 200 to 230V is
supported by 750W or less.
2. 1-phase 100 to 120V is
supported by 400W or less.
SSCNET compatible
Rated output
Rated
Symbol
output [kW]
Rating plate
Rating plate
10
20
0.1
0.2
0.4
0.6
0.75
1
MR-J3-350B4 500B(4)
MR-J3-700B(4)
40
60
70
100
200
350
500
700
11K
15K
22K
2
3.5
5
7
11
15
22
Rating plate
Rating plate
MR-J3-11KB(4) to 22KB(4)
Rating plate
1 - 9
1. FUNCTIONS AND CONFIGURATION
1.6 Combination with servo motor
The following table lists combinations of servo amplifiers and servo motors. The same combinations apply to
the models with an electromagnetic brake and the models with a reduction gear.
Servo motors
Servo amplifier
HF-SP
1000r/min
HF-MP
HF-KP
HC-RP
HC-UP
HC-LP
2000r/min
MR-J3-10B (1)
MR-J3-20B (1)
MR-J3-40B (1)
MR-J3-60B
053 13
23
053 13
23
43
43
51
52
52
MR-J3-70B
73
73
72
MR-J3-100B
MR-J3-200B
MR-J3-350B
MR-J3-500B
MR-J3-700B
MR-J3-11KB
MR-J3-15KB
MR-J3-22KB
81
121 201
301
102
152 202
352
102
152
202
302
103
152
202
153
503
203
421
502
353
352
502
702
Servo motors
HA-LP
Servo amplifier
1000r/min
1500r/min
2000r/min
502
MR-J3-500B
MR-J3-700B
MR-J3-11KB
MR-J3-15KB
MR-J3-22KB
601
701M
11K1M
15K1M
22K1M
702
801 12K1
15K1
11K2
15K2
22K2
20K1 25K1
Servo motors
Servo amplifier
HA-LP
HF-SP
1000r/min
1500r/min
2000r/min
MR-J3-60B4
MR-J3-100B4
MR-J3-200B4
MR-J3-350B4
MR-J3-500B4
MR-J3-700B4
MR-J3-11KB4
MR-J3-15KB4
MR-J3-22KB4
524
1024
1524 2024
3524
5024
7024
6014
8014 12K14
15K14
701M4
11K1M4
15K1M4
22K1M4
11K24
15K24
22K24
20K14
1 - 10
1. FUNCTIONS AND CONFIGURATION
1.7 Structure
1.7.1 Parts identification
(1) MR-J3-100B or less
Detailed
explanation
Name/Application
Display
The 3-digit, seven-segment LED shows the servo
status and alarm number.
Chapter 4
Rotary axis setting switch (SW1)
SW1
8
Used to set the axis No. of servo amplifier.
Section 3.13
8
0
0
ON 4F
SW1
TEST
SW2
Test operation select switch (SW2-1)
Used to perform the test operation
mode by using MR Configurator.
1
2
SW2
Section 3.13
Spare (Be sure to set to the "Down"
position).
1
2
Main circuit power supply connector (CNP1)
Connect the input power supply.
Section 3.1
Section 3.3
USB communication connector (CN5)
Connect the personal computer.
Section 11.8
I/O signal connector (CN3)
Used to connect digital I/O signals.
More over an analog monitor is output.
Section 3.2
Section 3.4
Control circuit connector (CNP2)
Connect the control circuit power supply/regenerative
option.
Section 3.1
Section 3.3
SSCNET cable connector (CN1A)
Used to connect the servo system controller or the front
axis servo amplifier.
Section 3.2
Section 3.4
SSCNET cable connector (CN1B)
Used to connect the rear axis servo amplifier. For the final
axis, puts a cap.
Section 3.2
Section 3.4
Servo motor power connector (CNP3)
Connect the servo motor.
Section 3.1
Section 3.3
Encoder connector (CN2)
Used to connect the servo motor encoder.
Section 3.4
Section 11.1
Charge lamp
Lit to indicate that the main circuit is charged. While
this lamp is lit, do not reconnect the cables.
Battery connector (CN4)
Used to connect the battery for absolute position data
backup.
Section 11.9
Chapter 12
Battery holder
Contains the battery for absolute position data backup.
Section 12.3
Fixed part
(2 places)
Protective earth (PE) terminal (
Ground terminal.
)
Section 3.1
Section 3.3
Rating plate
Section 1.5
1 - 11
1. FUNCTIONS AND CONFIGURATION
(2) MR-J3-60B4 MR-J3-100B4
Detailed
explanation
Name/Application
Display
The 3-digit, seven-segment LED shows the servo
status and alarm number.
Chapter 4
Rotary axis setting switch (SW1)
SW1
8
Used to set the axis No. of servo amplifier.
Section 3.13
8
0
0
ON 4F
SW1
TEST
Test operation select switch (SW2-1)
Used to perform the test operation
mode by using MR Configurator.
1
2
SW2
SW2
Section 3.13
Spare (Be sure to set to the "Down"
position).
1
2
Main circuit power supply connector (CNP1)
Connect the input power supply.
Section 3.1
Section 3.3
USB communication connector (CN5)
Connect the personal computer.
Section 11.8
I/O signal connector (CN3)
Used to connect digital I/O signals.
More over an analog monitor is output.
Section 3.2
Section 3.4
Control circuit connector (CNP2)
Connect the control circuit power supply/regenerative
option.
Section 3.1
Section 3.3
SSCNET cable connector (CN1A)
Used to connect the servo system controller or the front
axis servo amplifier.
Section 3.2
Section 3.4
SSCNET cable connector (CN1B)
Used to connect the rear axis servo amplifier. For the final
axis, puts a cap.
Section 3.2
Section 3.4
Servo motor power connector (CNP3)
Connect the servo motor.
Section 3.1
Section 3.3
Encoder connector (CN2)
Used to connect the servo motor encoder.
Section 3.4
Section 11.1
Battery connector (CN4)
Used to connect the battery for absolute position data
backup.
Section 11.9
Chapter 12
Charge lamp
Lit to indicate that the main circuit is charged. While
this lamp is lit, do not reconnect the cables.
Fixed part
(3 places)
Battery holder
Section 12.3
Contains the battery for absolute position data backup.
Protective earth (PE) terminal (
Ground terminal.
)
Section 3.1
Section 3.3
Rating plate
Section 1.5
1 - 12
1. FUNCTIONS AND CONFIGURATION
(3) MR-J3-200B(4)
Detailed
explanation
Name/Application
Display
The 3-digit, seven-segment LED shows the servo
status and alarm number.
Chapter 4
Rotary axis setting switch (SW1)
SW1
8
Used to set the axis No. of servo amplifier.
Section 3.13
8
0
0
ON 4F
SW1
TEST
Test operation select switch (SW2-1)
Used to perform the test operation
mode by using MR Configurator.
1
2
SW2
SW2
Section 3.13
Spare (Be sure to set to the "Down"
position).
1
2
Main circuit power supply connector (CNP1)
Connect the input power supply.
Section 3.1
Section 3.3
USB communication connector (CN5)
Connect the personal computer.
Section 11.8
I/O signal connector (CN3)
Used to connect digital I/O signals.
More over an analog monitor is output.
Section 3.2
Section 3.4
SSCNET cable connector (CN1A)
Used to connect the servo system controller or the front
axis servo amplifier.
(Note)
Section 3.2
Section 3.4
Servo motor power connector (CNP3)
Connect the servo motor.
Section 3.1
Section 3.3
SSCNET cable connector (CN1B)
Used to connect the rear axis servo amplifier. For the final
axis, puts a cap.
Section 3.2
Section 3.4
Encoder connector (CN2)
Used to connect the servo motor encoder.
Section 3.4
Section 11.1
Battery connector (CN4)
Used to connect the battery for absolute position data
backup.
Section 11.9
Chapter 12
Control circuit connector (CNP2)
Connect the control circuit power supply/regenerative
option.
Section 3.1
Section 3.3
Battery holder
Contains the battery for absolute position data backup.
Section 12.3
Charge lamp
Lit to indicate that the main circuit is charged. While
this lamp is lit, do not reconnect the cables.
Cooling Fan
Protective earth (PE) terminal (
Ground terminal.
)
Section 3.1
Section 3.3
Fixed part
(3 places)
Rating plate
Section 1.5
Note. Connectors (CNP1, CNP2, and CNP3) and appearance of MR-J3-200B servo amplifier have been changed from January 2008
production. Model name of the existing servo amplifier is changed to MR-J3-200B-RT. For MR-J3-200B-RT, refer to appendix 5.
1 - 13
1. FUNCTIONS AND CONFIGURATION
(4) MR-J3-350B
Detailed
explanation
Name/Application
Display
The 3-digit, seven-segment LED shows the servo
status and alarm number.
Chapter 4
Rotary axis setting switch (SW1)
SW1
8
Used to set the axis No. of servo amplifier.
Section 3.13
8
0
0
ON 4F
SW1
TEST
Test operation select switch (SW2-1)
Used to perform the test operation
mode by using MR Configurator.
1
2
SW2
SW2
Section 3.13
Spare (Be sure to set to the "Down"
position).
1
2
Main circuit power supply connector (CNP1)
Connect the input power supply.
Section 3.1
Section 3.3
USB communication connector (CN5)
Connect the personal computer.
Section 11.8
I/O signal connector (CN3)
Used to connect digital I/O signals.
More over an analog monitor is output.
Section 3.2
Section 3.4
SSCNET cable connector (CN1A)
Used to connect the servo system controller or the front
axis servo amplifier.
Section 3.2
Section 3.4
Servo motor power connector (CNP3)
Connect the servo motor.
Section 3.1
Section 3.3
SSCNET cable connector (CN1B)
Used to connect the rear axis servo amplifier. For the final
axis, puts a cap.
Section 3.2
Section 3.4
Encoder connector (CN2)
Used to connect the servo motor encoder.
Section 3.4
Section 11.1
Battery connector (CN4)
Used to connect the battery for absolute position data
backup.
Section 11.9
Chapter 12
Control circuit connector (CNP2)
Connect the control circuit power supply/regenerative
option.
Section 3.1
Section 3.3
Battery holder
Contains the battery for absolute position data backup.
Section 12.3
Charge lamp
Lit to indicate that the main circuit is charged. While
this lamp is lit, do not reconnect the cables.
Cooling fan
Protective earth (PE) terminal (
Ground terminal.
)
Section 3.1
Section 3.3
Fixed part
(3 places)
Rating plate
Section 1.5
1 - 14
1. FUNCTIONS AND CONFIGURATION
(5) MR-J3-350B4 MR-J3-500B(4)
POINT
The servo amplifier is shown without the front cover. For removal of the front
cover, refer to section 1.7.2.
Detailed
explanation
Name/Application
Display
The 3-digit, seven-segment LED shows the servo
status and alarm number.
Chapter 4
Rotary axis setting switch (SW1)
SW1
8
Used to set the axis No. of servo amplifier.
Section 3.13
8
0
0
ON 4F
SW1
TEST
SW2
Test operation select switch (SW2-1)
Used to perform the test operation
mode by using MR Configurator.
1
2
SW2
Section 3.13
Section 11.8
Spare (Be sure to set to the "Down"
position).
1
2
Cooling fan
USB communication connector (CN5)
Connect the personal computer.
I/O signal connector (CN3)
Used to connect digital I/O signals.
More over an analog monitor is output.
Section 3.2
Section 3.4
Battery holder
Contains the battery for absolute position data backup.
Section 12.3
SSCNET cable connector (CN1A)
Used to connect the servo system controller or the front
axis servo amplifier.
Section 3.2
Section 3.4
SSCNET cable connector (CN1B)
Used to connect the rear axis servo amplifier. For the final
axis, puts a cap.
Section 3.2
Section 3.4
Encoder connector (CN2)
Used to connect the servo motor encoder.
Section 3.4
Section 11.1
Battery connector (CN4)
Used to connect the battery for absolute position data
backup.
Section 11.9
Chapter 12
DC reactor terminal block (TE3)
Used to connect the DC reactor.
Section 3.4
Section 11.1
Charge lamp
Lit to indicate that the main circuit is charged. While
this lamp is lit, do not reconnect the cables.
Main circuit terminal block (TE1)
Used to connect the input power supply and servo
motor.
Section 3.1
Section 3.3
Control circuit terminal block (TE2)
Used to connect the control circuit power supply.
Section 3.1
Section 3.3
Fixed part
(4 places)
Protective earth (PE) terminal (
Ground terminal.
)
Section 3.1
Section 3.3
Rating plate
Section 1.5
1 - 15
1. FUNCTIONS AND CONFIGURATION
(6) MR-J3-700B(4)
POINT
The servo amplifier is shown without the front cover. For removal of the front
cover, refer to section 1.7.2.
Detailed
explanation
Name/Application
Display
The 3-digit, seven-segment LED shows the servo
status and alarm number.
Chapter 4
Rotary axis setting switch (SW1)
SW1
8
Used to set the axis No. of servo amplifier.
Section 3.13
8
0
0
ON 4F
SW1
TEST
SW2
Test operation select switch (SW2-1)
Used to perform the test operation
mode by using MR Configurator.
1
2
SW2
Section 3.13
Section 11.8
Spare (Be sure to set to the "Down"
position).
Cooling fan
1
2
Fixed part
(4 places)
USB communication connector (CN5)
Connect the personal computer.
I/O signal connector (CN3)
Used to connect digital I/O signals.
More over an analog monitor is output.
Section 3.2
Section 3.4
SSCNET cable connector (CN1A)
Used to connect the servo system controller or the front
axis servo amplifier.
Section 3.2
Section 3.4
Battery holder
Contains the battery for absolute position data backup.
Section 12.3
SSCNET cable connector (CN1B)
Used to connect the rear axis servo amplifier. For the final
axis, puts a cap.
Section 3.2
Section 3.4
Encoder connector (CN2)
Used to connect the servo motor encoder.
Section 3.4
Section 11.1
Battery connector (CN4)
Used to connect the battery for absolute position data
backup.
Section 11.9
Chapter 12
DC reactor terminal block (TE3)
Used to connect the DC reactor.
Section 3.4
Section 11.1
Charge lamp
Lit to indicate that the main circuit is charged. While
this lamp is lit, do not reconnect the cables.
Control circuit terminal block (TE2)
Used to connect the control circuit power supply.
Section 3.1
Section 3.3
Main circuit terminal block (TE1)
Used to connect the input power supply and servo
motor.
Section 3.1
Section 3.3
Protective earth (PE) terminal (
Ground terminal.
)
Section 3.1
Section 3.3
Rating plate
Section 1.5
1 - 16
1. FUNCTIONS AND CONFIGURATION
(7) MR-J3-11KB(4) to MR-J3-22KB(4)
POINT
The servo amplifier is shown without the front cover. For removal of the front
cover, refer to section 1.7.2.
Detailed
explanation
Name/Application
Display
The 3-digit, seven-segment LED shows the servo
status and alarm number.
Chapter 4
Rotary axis setting switch (SW1)
SW1
8
Used to set the axis No. of servo amplifier.
Section 3.13
8
0
0
ON 4F
SW1
TEST
SW2
Test operation select switch (SW2-1)
Used to perform the test operation
mode by using MR Configurator.
1
2
SW2
Section 3.13
Section 11.8
Spare (Be sure to set to the "Down"
position).
1
2
Cooling fan
Fixed part
(4 places)
USB communication connector (CN5)
Connect the personal computer.
I/O signal connector (CN3)
Used to connect digital I/O signals.
More over an analog monitor is output.
Section 3.2
Section 3.4
SSCNET cable connector (CN1A)
Used to connect the servo system controller or the front
axis servo amplifier.
Section 3.2
Section 3.4
Battery holder
Contains the battery for absolute position data backup.
Section 12.3
SSCNET cable connector (CN1B)
Used to connect the rear axis servo amplifier. For the final
axis, puts a cap.
Section 3.2
Section 3.4
Encoder connector (CN2)
Used to connect the servo motor encoder.
Section 3.4
Section 11.1
Battery connector (CN4)
Used to connect the battery for absolute position data
backup.
Section 11.9
Chapter 12
Rating plate
Section 1.5
Charge lamp
Lit to indicate that the main circuit is charged. While
this lamp is lit, do not reconnect the cables.
Main circuit terminal block control circuit protective
earth (TE)
Used to connect the input power supply, servo motor,
regenerative option and ground.
Section 3.1
Section 3.3
1 - 17
1. FUNCTIONS AND CONFIGURATION
1.7.2 Removal and reinstallation of the front cover
Before removing or installing the front cover, turn off the power and wait for 15
minutes or more until the charge lamp turns off. Then, confirm that the voltage
between P( ) and N( ) is safe with a voltage tester and others. Otherwise, an
electric shock may occur. In addition, always confirm from the front of the servo
amplifier whether the charge lamp is off or not.
WARNING
(1) For MR-J3-350B4 MR-J3-500B(4) MR-J3-700B(4)
Removal of the front cover
A)
A)
Hold the ends of lower side of the front cover with
both hands.
Pull up the cover, supporting at point
.
A)
Pull out the front cover to remove.
1 - 18
1. FUNCTIONS AND CONFIGURATION
Reinstallation of the front cover
Front cover
setting tab
A)
A)
Insert the front cover setting tabs into the sockets of
servo amplifier (2 places).
Pull up the cover, supporting at point
.
A)
Setting tab
Push the setting tabs until they click.
1 - 19
1. FUNCTIONS AND CONFIGURATION
(2) For MR-J3-11KB(4) to MR-J3-22KB(4)
Removal of the front cover
C)
B)
A)
1) Press the removing knob on the lower side of the
front cover ( A) and B) ) and release the installation
hook.
3) Pull it to remove the front cover.
2) Press the removing knob of C) and release the
external hook.
Reinstallation of the front cover
(Note 1)
(Note 1)
C)
D)
(Note 2)
B)
A)
Installation hook
1) Fit the front cover installation hooks on the sockets 2) Push the front cover until you hear the clicking
of body cover ( A) to D) ) to reinstall it.
noise of the installation hook.
Note 1. The cooling fan cover can be locked with enclosed screws (M4
40).
2. By drilling approximately 4 of a hole on the front cover, the front cover can be locked on the body with an enclosed screw (M4
14).
1 - 20
1. FUNCTIONS AND CONFIGURATION
1.8 Configuration including auxiliary equipment
POINT
Equipment other than the servo amplifier and servo motor are optional or
recommended products.
(1) MR-J3-100B or less
(a) For 3-phase or 1-phase 200V to 230VAC
Personal
computer
R S T
(Note 3)
Power supply
MR Configurator
CN5
CN3
Servo amplifier
No-fuse breaker
(NFB) or fuse
Junction terminal
block
Magnetic
contactor
(MC)
Servo system
controller or Front axis
servo amplifier CN1B
CN1A
CN1B
(Note 2)
Line noise
filter
(FR-BSF01)
Rear servo amplifier
CN1A or Cap
U V W
CN2
CN4
L1
L2
(Note 1)
Battery
L3
MR-J3BAT
(Note 2)
Power factor
improving DC
reactor
P1
P2
Servo motor
(FR-BEL)
P
C
Regenerative option
L11
L21
Note 1. The battery (option) is used for the absolute position detection system in the position control mode.
2. The AC reactor can also be used. In this case, the DC reactor cannot be used. When not using DC reactor, short P1 and P2.
3. A 1-phase 200V to 230VAC power supply may be used with the servo amplifier of MR-J3-70B or less.
For 1-phase 200V to 230VAC, connect the power supply to L1 L2 and leave L3 open. Refer to section 1.3 for the power supply
specification.
1 - 21
1. FUNCTIONS AND CONFIGURATION
(b) For 1-phase 100V to 120VAC
Personal
computer
R
S
MR Configurator
(Note 3)
Power supply
CN5
CN3
Servo amplifier
No-fuse breaker
(NFB) or fuse
Junction
terminal
block
Magnetic
contactor
(MC)
(Note 2)
Servo system
controller or Front axis
servo amplifier CN1B
CN1A
CN1B
Power factor
improving
(FR-BAL)
Rear servo amplifier
CN1A or Cap
Line noise filter
(FR-BSF01)
W
U V
CN2
CN4
L1
(Note 1)
Battery
L2
MR-J3BAT
Servo motor
P
C
Regenerative option
L11
L21
Note 1. The battery (option) is used for the absolute position detection system in the position control mode.
2. The power factor improving DC reactor cannot be used.
3. Refer to section 1.3 for the power supply specification.
1 - 22
1. FUNCTIONS AND CONFIGURATION
(2) MR-J3-60B4 MR-J3-100B4
Personal
computer
R S T
MR Configurator
(Note 3)
Power supply
CN5
Servo amplifier
No-fuse breaker
(NFB) or fuse
Junction
CN3
terminal
block
Magnetic
contactor
(MC)
Servo system
controller or Front axis
servo amplifier CN1B
CN1A
CN1B
(Note 2)
Line noise
filter
(FR-BSF01)
Rear servo amplifier
CN1A or Cap
CN2
CN4
L1
L2
L3
(Note 1)
Battery
MR-J3BAT
(Note 2)
P1
Power factor
improving DC
reactor
Servo motor
U V W
P2
(FR-BEL-H)
P
C
Regenerative option
L11
L21
Note 1. The battery (option) is used for the absolute position detection system in the position control mode.
2. The AC reactor can also be used. In this case, the DC reactor cannot be used. When not using DC reactor, short P1 and P2.
3. A 1-phase 200V to 230VAC power supply may be used with the servo amplifier of MR-J3-70B or less.
For 1-phase 200V to 230VAC, connect the power supply to L1
specification.
L2 and leave L3 open. Refer to section 1.3 for the power supply
1 - 23
1. FUNCTIONS AND CONFIGURATION
(3) MR-J3-200B(4)
R S T
(Note 3)
Power supply
No-fuse breaker
(NFB) or fuse
Magnetic
contactor
(MC)
Personal
computer
MR Configurator
CN5
(Note 2)
Line noise filter
(FR-BSF01)
Servo amplifier
(Note 2)
Power factor
improving DC
L1
L2
L3
Junction
terminal
block
reactor
CN3
(FR-BEL/
FR-BEL-H)
P1
Servo system
controller or Front axis
servo amplifier CN1B
(Note 4)
CN1A
P2
Regenerative
option
P
C
L11
L21
CN1B
CN2
Rear servo amplifier
CN1A or Cap
CN4
(Note 1)
Battery
MR-J3BAT
U V
W
Servo motor
Note 1. The battery (option) is used for the absolute position detection system in the position control mode.
2. The AC reactor can also be used. In this case, the DC reactor cannot be used. When not using DC reactor, short P1 and P2.
3. Refer to section 1.3 for the power supply specification.
4. Connectors (CNP1, CNP2, and CNP3) and appearance of MR-J3-200B servo amplifier have been changed from January 2008
production. Model name of the existing servo amplifier is changed to MR-J3-200B-RT. For MR-J3-200B-RT, refer to appendix 5.
1 - 24
1. FUNCTIONS AND CONFIGURATION
(4) MR-J3-350B
R S T
(Note 3)
Power supply
No-fuse breaker
(NFB) or fuse
Magnetic
contactor
(MC)
Personal
computer
MR Configurator
CN5
CN3
(Note 2)
Line noise filter
(FR-BLF)
Servo amplifier
Junction
terminal
block
L1
L2
L3
P1
P2
Servo system
controller or Front axis
servo amplifier CN1B
CN1A
CN1B
(Note 2)
Power factor
improving DC
reactor
Regenerative
option
(FR-BEL)
L11
P
C
Rear servo amplifier
CN1A or Cap
L21
CN2
CN4
(Note 1)
Battery
MR-J3BAT
W
U V
Servo motor
Note 1. The battery (option) is used for the absolute position detection system in the position control mode.
2. The AC reactor can also be used. In this case, the DC reactor cannot be used. When not using DC reactor, short P1 and P2.
3. Refer to section 1.3 for the power supply specification.
1 - 25
1. FUNCTIONS AND CONFIGURATION
(5) MR-J3-350B4 MR-J3-500B(4)
R S T
(Note 3)
Power supply
Personal
computer
MR Configurator
CN5
CN3
No-fuse breaker
(NFB) or fuse
Servo amplifier
Junction
terminal
block
Magnetic
contactor
(MC)
(Note 2)
(Note 1)
Battery
MR-J3BAT
Servo system
controller or Front axis
servo amplifier CN1B
CN1A
CN1B
Line noise filter
(FR-BLF)
Rear servo amplifier
CN1A or Cap
CN2
CN4
L11 L21
P1
P2
L3
(Note 2)
L2
L1
Power factor
improving DC
reactor
(FR-BEL-(H))
P
C
U V W
Regenerative option
Servo motor
Note 1. The battery (option) is used for the absolute position detection system in the position control mode.
2. The AC reactor can also be used. In this case, the DC reactor cannot be used. When not using DC reactor, short P1 and P2.
3. Refer to section 1.3 for the power supply specification.
1 - 26
1. FUNCTIONS AND CONFIGURATION
(6) MR-J3-700B(4)
R S T
Personal
computer
(Note 3)
Power supply
MR Configurator
CN5
CN3
No-fuse breaker
Servo amplifier
(NFB) or fuse
Junction
terminal
block
Magnetic
contactor
(MC)
(Note 2)
Servo system
controller or Front axis
servo amplifier CN1B
Line noise filter
(FR-BLF)
CN1A
CN1B
(Note 1)
L11 L21
Battery
Rear servo amplifier
CN1A or Cap
MR-J3BAT
(Note 2)
CN2
CN4
Power factor
improving DC
reactor
(FR-BEL-(H))
P2
P1
L3
2
L
1
L
P
C
U V W
Regenerative option
Servo motor
Note 1. The battery (option) is used for the absolute position detection system in the position control mode.
2. The AC reactor can also be used. In this case, the DC reactor cannot be used. When not using DC reactor, short P1 and P2.
3. Refer to section 1.3 for the power supply specification.
1 - 27
1. FUNCTIONS AND CONFIGURATION
(7) MR-J3-11KB(4) to MR-J3-22KB(4)
(Note 3)
Power supply
R S T
Personal
computer
MR Configurator
CN5
CN3
No-fuse
breaker (NFB)
or fuse
L21
Servo amplifier
L11
Junction
terminal
block
Magnetic
contactor
(MC)
Servo system
controller or Front axis
servo amplifier CN1B
(Note 2)
(Note 1)
Battery
MR-J3BAT
CN1A
CN1B
Line noise filter
(FR-BLF)
Rear servo amplifier
CN1A or Cap
CN2
CN4
L3
L2
L1
(Note 2)
Power factor improving
DC reactor (FR-BEL-(H))
W V U
P1
P
P
C
Regenerative option
Servo motor
Note 1. The battery (option) is used for the absolute position detection system in the position control mode.
2. The AC reactor can also be used. In this case, the DC reactor cannot be used. When not using DC reactor, short P1 and P.
3. Refer to section 1.3 for the power supply specification.
1 - 28
2. INSTALLATION
2. INSTALLATION
Stacking in excess of the limited number of products is not allowed.
Install the equipment on incombustible material. Installing them directly or close to
combustibles will lead to a fire.
Install the equipment in a load-bearing place in accordance with this Instruction
Manual.
Do not get on or put heavy load on the equipment to prevent injury.
Use the equipment within the specified environmental condition range. (For the
environmental conditions, refer to section 1.3.)
Provide an adequate protection to prevent screws, metallic detritus and other
conductive matter or oil and other combustible matter from entering the servo
amplifier.
CAUTION
Do not block the intake/exhaust ports of the servo amplifier. Otherwise, a fault may
occur.
Do not subject the servo amplifier to drop impact or shock loads as they are
precision equipment.
Do not install or operate a faulty servo amplifier.
When the product has been stored for an extended period of time, consult
Mitsubishi.
When treating the servo amplifier, be careful about the edged parts such as the
corners of the servo amplifier.
2.1 Installation direction and clearances
The equipment must be installed in the specified direction. Otherwise, a fault may
occur.
CAUTION
Leave specified clearances between the servo amplifier and control box inside
walls or other equipment.
(1) 7kW or less
(a) Installation of one servo amplifier
Control box
Control box
40mm
or more
Servo amplifier
Wiring allowance
80mm
Top
10mm
10mm
or more
or more
Bottom
40mm
or more
2 - 1
2. INSTALLATION
(b) Installation of two or more servo amplifiers
POINT
Close mounting is available for the servo amplifier of under 3.5kW for 200V
class and 400W for 100V class.
Leave a large clearance between the top of the servo amplifier and the internal surface of the control
box, and install a cooling fan to prevent the internal temperature of the control box from exceeding the
environmental conditions.
When installing the servo amplifiers closely, leave a clearance of 1mm between the adjacent servo
amplifiers in consideration of mounting tolerances.
In this case, bring the ambient temperature within 0 to 45 (32 to 113 ), or use it at 75% or smaller
effective load ratio.
Control box
Control box
100mm
or more
100mm
or more
10mm
or more
1mm
1mm
Top
30mm
or more
30mm
or more
30mm
or more
30mm
or more
Bottom
40mm
or more
40mm or more
Mounting closely
Leaving clearance
(2) 11k to 22kW
(a) Installation of one servo amplifier
Control box
Control box
40mm or more
Servo amplifier
Wiring allowance
80mm
Top
10mm
or more
10mm
or more
Bottom
120mm
or more
2 - 2
2. INSTALLATION
(b) Installation of two or more servo amplifiers
Leave a large clearance between the top of the servo amplifier and the internal surface of the control
box, and install a cooling fan to prevent the internal temperature of the control box from exceeding the
environmental conditions.
Control box
100mm
or more
10mm or more
Top
30m
30mm
or more
or more
Bottom
120mm or more
(3) Others
When using heat generating equipment such as the regenerative option, install them with full consideration
of heat generation so that the servo amplifier is not affected.
Install the servo amplifier on a perpendicular wall in the correct vertical direction.
2.2 Keep out foreign materials
(1) When installing the unit in a control box, prevent drill chips and wire fragments from entering the servo
amplifier.
(2) Prevent oil, water, metallic dust, etc. from entering the servo amplifier through openings in the control box or
a cooling fan installed on the ceiling.
(3) When installing the control box in a place where there are much toxic gas, dirt and dust, conduct an air
purge (force clean air into the control box from outside to make the internal pressure higher than the
external pressure) to prevent such materials from entering the control box.
2.3 Cable stress
(1) The way of clamping the cable must be fully examined so that flexing stress and cable's own weight stress
are not applied to the cable connection.
(2) For use in any application where the servo motor moves, fix the cables (encoder, power supply, brake) with
having some slack from the connector connection part of the servo motor to avoid putting stress on the
connector connection part. Use the optional encoder cable within the flexing life range. Use the power
supply and brake wiring cables within the flexing life of the cables.
2 - 3
2. INSTALLATION
(3) Avoid any probability that the cable sheath might be cut by sharp chips, rubbed by a machine corner or
stamped by workers or vehicles.
(4) For installation on a machine where the servo motor will move, the flexing radius should be made as large
as possible. Refer to section 10.4 for the flexing life.
2.4 SSCNET cable laying
SSCNET cable is made from optical fiber. If optical fiber is added a power such as a major shock, lateral
pressure, haul, sudden bending or twist, its inside distorts or breaks, and optical transmission will not be
available. Especially, as optical fiber for MR-J3BUS
M
MR-J3BUS M-A is made of synthetic resin, it
melts down if being left near the fire or high temperature. Therefore, do not make it touched the part, which
becomes high temperature, such as radiator or regenerative option of servo amplifier.
Read described item of this section carefully and handle it with caution.
(1) Minimum bend radius
Make sure to lay the cable with greater radius than the minimum bend radius. Do not press the cable to
edges of equipment or others. For SSCNET cable, the appropriate length should be selected with due
consideration for the dimensions and arrangement of servo amplifier. When closing the door of control box,
pay careful attention for avoiding the case that SSCNET cable is hold down by the door and the cable
bend becomes smaller than the minimum bend radius.
For the minimum bend radius, refer to section 11.1.5.
(2) Prohibition of vinyl tape use
Migrating plasticizer is used for vinyl tape. Keep the MR-J3BUS M, and MR-J3BUS M-A cables away
from vinyl tape because the optical characteristic may be affected.
SSCNET cable
MR-J3BUS
Code
Cable
M
MR-J3BUS M-A
MR-J3BUS M-B
: Phthalate ester plasticizer such as DBP and DOP
may affect optical characteristic of cable.
: Cable is not affected by plasticizer.
Optical code
Cable
(3) Precautions for migrating plasticizer added materials
Generally, soft polyvinyl chloride (PVC), polyethylene resin (PE) and Teflon (fluorine resin) contain non-
migrating plasticizer and they do not affect the optical characteristic of SSCNET cable.
However, some wire sheaths and cable ties, which contain migrating plasticizer (phthalate ester), may
affect MR-J3BUS M and MR-J3BUS M-A cables.
In addition, MR-J3BUS M-B cable is not affected by plasticizer.
2 - 4
2. INSTALLATION
(4) Bundle fixing
Fix the cable at the closest part to the connector with bundle material in order to prevent SSCNET cable
from putting its own weight on CN1A CN1B connector of servo amplifier. Optical cord should be given
loose slack to avoid from becoming smaller than the minimum bend radius, and it should not be twisted.
When bundling the cable, fix and hold it in position by using cushioning such as sponge or rubber which
does not contain migratable plasticizers.
If using adhesive tape for bundling the cable, fire resistant acetate cloth adhesive tape 570F (Teraoka
Seisakusho Co., Ltd) is recommended.
Connector
Optical cord
Loose slack
Cable
Bundle material
Recommended product:
NK clamp SP type
( NIX, INC.)
(5) Tension
If tension is added on optical cable, the increase of transmission loss occurs because of external force
which concentrates on the fixing part of optical fiber or the connecting part of optical connector. At worst,
the breakage of optical fiber or damage of optical connector may occur. For cable laying, handle without
putting forced tension. For the tension strength, refer to section 11.1.5.
(6) Lateral pressure
If lateral pressure is added on optical cable, the optical cable itself distorts, internal optical fiber gets
stressed, and then transmission loss will increase. At worst, the breakage of optical cable may occur. As
the same condition also occurs at cable laying, do not tighten up optical cable with a thing such as nylon
band (TY-RAP).
Do not trample it down or tuck it down with the door of control box or others.
(7) Twisting
If optical fiber is twisted, it will become the same stress added condition as when local lateral pressure or
bend is added. Consequently, transmission loss increases, and the breakage of optical fiber may occur at
worst.
(8) Disposal
When incinerating optical cable (cord) used for SSCNET , hydrogen fluoride gas or hydrogen chloride gas
which is corrosive and harmful may be generated. For disposal of optical fiber, request for specialized
industrial waste disposal services who has incineration facility for disposing hydrogen fluoride gas or
hydrogen chloride gas.
2 - 5
2. INSTALLATION
2.5 Inspection items
Before starting maintenance and/or inspection, turn off the power and wait for 15
minutes or more until the charge lamp turns off. Then, confirm that the voltage
between P( ) and N( ) is safe with a voltage tester and others. Otherwise, an
electric shock may occur. In addition, always confirm from the front of the servo
amplifier whether the charge lamp is off or not.
WARNING
Any person who is involved in inspection should be fully competent to do the work.
Otherwise, you may get an electric shock. For repair and parts replacement,
contact your safes representative.
POINT
Do not test the servo amplifier with a megger (measure insulation resistance),
or it may become faulty.
Do not disassemble and/or repair the equipment on customer side.
It is recommended to make the following checks periodically.
(1) Check for loose terminal block screws. Retighten any loose screws.
(2) Check the cables and the like for scratches and cracks. Perform periodic inspection according to operating
conditions.
2.6 Parts having service lives
The following parts must be changed periodically as listed below. If any part is found faulty, it must be changed
immediately even when it has not yet reached the end of its life, which depends on the operating method and
environmental conditions. For parts replacement, please contact your sales representative.
Part name
Life guideline
Smoothing capacitor
10 years
Number of power-on and number of emergency
stop times : 100,000 times
Relay
Servo amplifier
Cooling fan
10,000 to 30,000hours (2 to 3 years)
Refer to section 12.2
Absolute position battery
(1) Smoothing capacitor
Affected by ripple currents, etc. and deteriorates in characteristic. The life of the capacitor greatly depends
on ambient temperature and operating conditions. The capacitor will reach the end of its life in 10 years of
continuous operation in normal air-conditioned environment.
(2) Relays
Their contacts will wear due to switching currents and contact faults occur. Relays reach the end of their life
when the cumulative number of power-on and emergency stop times is 100,000, which depends on the
power supply capacity.
(3) Servo amplifier cooling fan
The cooling fan bearings reach the end of their life in 10,000 to 30,000 hours. Normally, therefore, the
cooling fan must be changed in a few years of continuous operation as a guideline.
It must also be changed if unusual noise or vibration is found during inspection.
2 - 6
3. SIGNALS AND WIRING
3. SIGNALS AND WIRING
Any person who is involved in wiring should be fully competent to do the work.
Before wiring, turn off the power and wait for 15 minutes or more until the charge
lamp turns off. Then, confirm that the voltage between P( ) and N( ) is safe with
a voltage tester and others. Otherwise, an electric shock may occur. In addition,
always confirm from the front of the servo amplifier whether the charge lamp is off
or not.
WARNING
Ground the servo amplifier and the servo motor securely.
Do not attempt to wire the servo amplifier and servo motor until they have been
installed. Otherwise, you may get an electric shock.
The cables should not be damaged, stressed excessively, loaded heavily, or
pinched. Otherwise, you may get an electric shock.
Wire the equipment correctly and securely. Otherwise, the servo motor may
operate unexpectedly, resulting in injury.
Connect cables to correct terminals to prevent a burst, fault, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
The surge absorbing diode installed to the DC relay designed for control output
should be fitted in the specified direction. Otherwise, the signal is not output due to
a fault, disabling the forced stop (EM1) and other protective circuits.
Servo amplifier
Servo amplifier
24VDC
24VDC
DOCOM
DICOM
DOCOM
DICOM
Control output
signal
Control output
signal
CAUTION
RA
RA
Use a noise filter, etc. to minimize the influence of electromagnetic interference,
which may be given to electronic equipment used near the servo amplifier.
Do not install a power capacitor, surge suppressor or radio noise filter (FR-BIF (-H)
option) with the power line of the servo motor.
When using the regenerative resistor, switch power off with the alarm signal.
Otherwise, a transistor fault or the like may overheat the regenerative resistor,
causing a fire.
Do not modify the equipment.
During power-on, do not open or close the motor power line. Otherwise, a
malfunction or faulty may occur.
3 - 1
3. SIGNALS AND WIRING
3.1 Input power supply circuit
Always connect a magnetic contactor (MC) between the main circuit power supply
and L1, L2, and L3 of the servo amplifier, and configure the wiring to be able to shut
down the power supply on the side of the servo amplifier’s power supply. If a
magnetic contactor (MC) is not connected, continuous flow of a large current may
cause a fire when the servo amplifier malfunctions.
CAUTION
Use the trouble signal to switch main circuit power supply off. Otherwise, a
regenerative transistor fault or the like may overheat the regenerative resistor,
causing a fire.
POINT
Even if alarm has occurred, do not switch off the control circuit power supply.
When the control circuit power supply has been switched off, optical module
does not operate, and optical transmission of SSCNET communication is
interrupted. Therefore, the servo amplifier on the rear axis displays "AA" at
the indicator and turns into base circuit shut-off. The servo amplifier stops
with starting dynamic brake.
Wire the power supply/main circuit as shown below so that power is shut off and the servo-on command turned
off as soon as an alarm occurs, a servo forced stop is made valid, or a controller forced stop is made valid. A
no-fuse breaker (NFB) must be used with the input cables of the main circuit power supply.
(1) For 3-phase 200V to 230VAC power supply to MR-J3-10B to MR-J3-350B
(Note 4) Controller
Forced
stop
Alarm
RA1
forced stop
RA2
ON
MC
OFF
MC
SK
Servo amplifier
CNP1
Servo motor
NFB
MC
L1
L2
L3
N(
P1
P2
3-phase
200 to
230VAC
CNP3
(Note 6)
U
V
2
3
4
1
U
Motor
M
V
)
W
W
(Note 1)
(Note 2)
PE
CNP2
P(
)
C
D
(Note 3)
Encoder cable
CN2
Encoder
L11
L21
CN3
EM1
DOCOM
CN3
24VDC
RA1
DOCOM
Forced stop
(Note 5)
DICOM
(Note 5)
ALM
Trouble
(Note 4)
3 - 2
3. SIGNALS AND WIRING
Note 1. Always connect P1 and P2. (Factory-wired.) When using the power factor improving DC reactor, refer to section 11.13.
2. Always connect P( ) and D. (Factory-wired.) When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
4. If deactivating output of trouble (ALM) with parameter change, configure up the power supply circuit which switches off the
magnetic contactor after detection of alarm occurrence on the controller side.
5. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
6. Refer to section 3.10.
(2) For 1-phase 200V to 230VAC power supply to MR-J3-10B to MR-J3-70B
(Note 4) Controller
Forced
stop
Alarm
RA1
forced stop
RA2
ON
MC
OFF
MC
SK
Servo amplifier
CNP1
Servo motor
NFB
MC
1-phase
200 to
230VAC
L1
L2
L3
N
CNP3
(Note 6)
U
V
2
3
4
1
U
Motor
M
V
W
W
P1
P2
(Note 1)
(Note 2)
PE
CNP2
P
C
D
(Note 3)
Encoder cable
CN2
Encoder
L11
L21
CN3
EM1
DOCOM
CN3
24VDC
RA1
DOCOM
Forced stop
(Note 5)
DICOM
(Note 5)
ALM
Trouble
(Note 4)
Note 1. Always connect P1 and P2. (Factory-wired.) When using the power factor improving DC reactor, refer to section 11.13.
2. Always connect P and D. (Factory-wired.) When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
4. If deactivating output of trouble (ALM) with parameter change, configure up the power supply circuit which switches off the
magnetic contactor after detection of alarm occurrence on the controller side.
5. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
6. Refer to section 3.10.
3 - 3
3. SIGNALS AND WIRING
(3) For MR-J3-10B1 to MR-J3-40B1
(Note 4) Controller
Forced
stop
Alarm
RA1
forced stop
RA2
ON
MC
OFF
MC
SK
Servo amplifier
CNP1
Servo motor
NFB
MC
1-phase
100 to
120VAC
L1
CNP3
(Note 6)
Blank
U
V
2
3
4
1
U
Motor
M
L2
V
N
W
W
P1
P2
(Note 1)
(Note 2)
PE
CNP2
P
C
D
(Note 3)
Encoder cable
CN2
Encoder
L11
L21
CN3
EM1
DOCOM
CN3
24VDC
RA1
DOCOM
Forced stop
(Note 5)
DICOM
(Note 5)
ALM
Trouble
(Note 4)
Note 1. Always connect P1 and P2. (Factory-wired.) The power factor improving DC reactor cannot be used.
2. Always connect P and D. (Factory-wired.) When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
4. If deactivating output of trouble (ALM) with parameter change, configure up the power supply circuit which switches off the
magnetic contactor after detection of alarm occurrence on the controller side.
5. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
6. Refer to section 3.10.
3 - 4
3. SIGNALS AND WIRING
(4) MR-J3-60B4 to MR-J3-200B4
(Note 4) Controller
Forced
stop
Alarm
RA1
forced stop
RA2
ON
MC
OFF
MC
SK
(Note 7)
Stepdown
transformer
Servo amplifier
CNP1
Servo motor
NFB
MC
L1
L2
L3
N
3-phase
200 to
230VAC
CNP3
(Note 6)
U
V
2
3
4
1
U
Motor
M
V
W
W
P1
P2
(Note 1)
(Note 2)
PE
CNP2
P
C
D
(Note 3)
Encoder cable
CN2
Encoder
L11
L21
CN3
EM1
DOCOM
CN3
24VDC
RA1
DOCOM
Forced stop
(Note 5)
DICOM
(Note 5)
ALM
Trouble
(Note 4)
Note 1. Always connect P1 and P2. (Factory-wired.) When using the power factor improving DC reactor, refer to section 11.13.
2. Always connect P and D. (Factory-wired.) When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
4. If deactivating output of trouble (ALM) with parameter change, configure up the power supply circuit which switches off the
magnetic contactor after detection of alarm occurrence on the controller side.
5. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
6. Refer to section 3.10.
7. Stepdown transformer is required for coil voltage of magnetic contactor more than 200V class.
3 - 5
3. SIGNALS AND WIRING
(5) MR-J3-500B MR-J3-700B
(Note 4) Controller
Forced
stop
Alarm
RA1
forced stop
RA2
ON
MC
OFF
(Note 7)
Power supply
of Cooling fan
MC
SK
Servo amplifier
TE1
Servo motor
NFB
MC
L1
L2
L3
N
3-phase
200 to
230VAC
(Note 6)
Built-in
regenerative
resistor
U
V
2
3
4
1
U
V
Motor
M
W
W
(Note 2)
P1
TE2
PE
L11
NFB
L21
TE3
N
(Note 3)
Encoder cable
CN2
Encoder
P1
(Note 1)
P2
BU
BV
Cooling fan
CN3
EM1
DOCOM
CN3
24VDC
RA1
DOCOM
Forced stop
(Note 5)
DICOM
(Note 5)
ALM
Trouble
(Note 4)
Note 1. Always connect P1 and P2. (Factory-wired.) When using the power factor improving DC reactor, refer to section 11.13.
2. When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
4. If deactivating output of trouble (ALM) with parameter change, configure up the power supply circuit which switches off the
magnetic contactor after detection of alarm occurrence on the controller side.
5. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
6. Refer to section 3.10.
7. A cooling fan is attached to the HA-LP601 and the HA-LP701M servo motors. For power supply specification of the cooling fan,
refer to section 3.10.2 (3) (b).
3 - 6
3. SIGNALS AND WIRING
(6) MR-J3-350B4 to MR-J3-700B4
(Note 4) Controller
Forced
stop
Alarm
RA1
forced stop
RA2
ON
MC
OFF
(Note 8)
Power supply
of Cooling fan
MC
SK
(Note 7)
Stepdown
transformer
Servo amplifier
TE1
Servo motor
NFB
MC
L1
L2
L3
P
3-phase
380 to
480VAC
(Note 6)
Built-in
regenerative
resistor
U
V
2
3
4
1
U
V
Motor
M
W
W
(Note 2)
C
TE2
PE
L11
NFB
L21
TE3
N
(Note 3)
Encoder cable
CN2
Encoder
P1
(Note 1)
P2
BU
BV
Cooling fan
CN3
EM1
DOCOM
CN3
24VDC
RA1
DOCOM
Forced stop
(Note 5)
DICOM
(Note 5)
ALM
Trouble
(Note 4)
Note 1. Always connect P1 and P2. (Factory-wired.) When using the power factor improving DC reactor, refer to section 11.13.
2. When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
4. If deactivating output of trouble (ALM) with parameter change, configure up the power supply circuit which switches off the
magnetic contactor after detection of alarm occurrence on the controller side.
5. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
6. Refer to section 3.10.
7. Stepdown transformer is required for coil voltage of magnetic contactor more than 200V class.
8. A cooling fan is attached to the HA-LP6014 and the HA-LP701M4 servo motors. For power supply specification of the cooling
fan, refer to section 3.10.2 (3) (b).
3 - 7
3. SIGNALS AND WIRING
(7) MR-J3-11KB to MR-J3-22KB
(Note 4) Controller
Servo motor
thermal relay
RA3
Forced
stop
Alarm
RA1
forced stop
RA2
ON
MC
OFF
MC
SK
Servo amplifier
TE1
Servo motor
Dynamic
break
NFB
MC
(Option)
L1
L2
L3
C
3-phase
200 to
230VAC
U
V
U
V
M
W
W
(Note 6)
(Note 2)
(Note 1)
P
Regenerative
resistor
P1
PE
NFB
L11
L21
(Note 3)
Encoder cable
CN2
Encoder
BU
BV
BW
(Note 7)
Cooling fan
OHS1
RA3
OHS2
Servo motor
thermal relay
24VDC
power supply
CN3
EM1
DOCOM
CN3
24VDC
RA1
DOCOM
Forced stop
(Note 5)
DICOM
(Note 5)
ALM
Trouble
(Note 4)
Note 1. Always connect P1 and P. (Factory-wired.) When using the power factor improving DC reactor, refer to section 11.13.
2. When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
4. If deactivating output of trouble (ALM) with parameter change, configure up the power supply circuit which switches off the
magnetic contactor after detection of alarm occurrence on the controller side.
5. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
6. Refer to section 3.10.
7. Cooling fan power supply of the HA-LP11K2 servo motor is 1-phase. Power supply specification of the cooling fan is different
from that of the servo amplifier. Therefore, separate power supply is required.
3 - 8
3. SIGNALS AND WIRING
(8) MR-J3-11KB4 to MR-J3-22KB4
(Note 4) Controller
Servo motor
thermal relay
RA3
Forced
stop
Alarm
RA1
forced stop
RA2
ON
MC
OFF
(Note 8)
Cooling fan
power supply
MC
SK
(Note 9)
Stepdown
transformer
Servo amplifier
TE1
Servo motor
Dynamic
break
(Option)
NFB
MC
L1
L2
L3
C
3-phase
380 to
480VAC
U
V
U
V
M
W
W
(Note 6)
(Note 2)
(Note 1)
P
Regenerative
resistor
P1
PE
NFB
L11
L21
(Note 3)
Encoder cable
CN2
Encoder
BU
BV
BW
(Note 7)
Cooling fan
OHS1
RA3
OHS2
Servo motor
thermal relay
24VDC
power supply
CN3
EM1
DOCOM
CN3
24VDC
RA1
DOCOM
Forced stop
(Note 5)
DICOM
(Note 5)
ALM
Trouble
(Note 4)
Note 1. Always connect P1 and P. (Factory-wired.) When using the power factor improving DC reactor, refer to section 11.13.
2. When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
4. If deactivating output of trouble (ALM) with parameter change, configure up the power supply circuit which switches off the
magnetic contactor after detection of alarm occurrence on the controller side.
5. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
6. Refer to section 3.10.
7. Servo amplifiers does not have BW when the cooling fan power supply is 1-phase.
8. For the cooling fan power supply, refer to section 3.10.2 (3) (b).
9. Stepdown transformer is required for coil voltage of magnetic contactor more than 200V class.
3 - 9
3. SIGNALS AND WIRING
3.2 I/O signal connection example
Servo amplifier
(Note 10)
24VDC
(Note 12) (Note 12)
CN3
5
3
CN3
13 MBR
Power
(Note 2)
Magnetic brake interlock
supply
DICOM
(Note 14)
RA1
RA2
RA3
DOCOM
9
INP
In-position
(Note 3,4)Forced stop
Upper stroke limit (FLS)
Lower stroke limit (RLS)
Proximity dog (DOG)
EM1 20
DI1
(Note 13,14)
2
15
Trouble (Note 11)
ALM
DICOM
LA
(Note 15)
(Note 5)
DI2 12
DI3 19
10
6
Personal
computer
USB cable
MR-J3USBCBL3M
(option)
Encoder A-phase pulse
(differential line driver)
16 LAR
LB
17 LBR
LZ
18 LZR
MR Configurator
7
Encoder B-phase pulse
(differential line driver)
CN5
8
Encoder Z-phase pulse
(differential line driver)
Control common
Analog monitor 1
11
4
LG
MO1
LG
A
A
Max. 1mA meter
10k
1
Servo system
controller
both directions
14 MO2
Plate SD
Analog monitor 2
Max. 1mA meter
both directions
(Note 6)
10k
SSCNET cable
(option)
2m Max
CN1A
CN1B
SW1
(Note 8)
SW2
1 2
(Note 1)
(Note 7)
Between electrodes
MR-J3-B
(2 axis)
SW1
CN1A
(Note 8)
SW2
1 2
CN1B
MR-J3-B
(3 axis)
(Note 7)
(Note 8)
(Note 6 )
SSCNET cable
(option)
SW1
CN1A
SW2
1 2
CN1B
MR-J3-B
(n axis)
(Note 7)
(Note 8)
SW1
CN1A
(Note 9)
Cap
SW2
1 2
CN1B
3 - 10
3. SIGNALS AND WIRING
Note 1 To prevent an electric shock, always connect the protective earth (PE) terminal (terminal marked ) of the servo amplifier to the
protective earth (PE) of the control box.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will be faulty and will not output
signals, disabling the forced stop (EM1) and other protective circuits.
3. If the controller does not have an forced stop (EM1) function, always install a forced stop switch (Normally closed).
4. When starting operation, always turn on the forced stop (EM1). (Normally closed contacts) By setting " 1
parameter No.PA04 of the drive unit, the forced stop (EM1) can be made invalid.
5. Use MRZJW3-SETUP 221E.
" in DRU
6. For the distance between electrodes of SSCNET cable, refer to the following table.
Distance between
electrodes
Cable
Cable model name
MR-J3BUS
Cable length
Standard code inside panel
Standard cable outside panel
Long-distance cable
M
0.15m to 3m
5m to 20m
30m to 50m
20m
50m
MR-J3BUS M-A
MR-J3BUS M-B
7. The wiring of the second and subsequent axes is omitted.
8. Up to eight axes (n 1 to 8) may be connected. Refer to section 3.13 for setting of axis selection.
9. Make sure to put a cap on the unused CN1A CN1B.
10. Supply 24VDC 10% 150mA current for interfaces from the outside. 150mA is the value applicable when all I/O signals are
used. The current capacity can be decreased by reducing the number of I/O points. Refer to section 3.7.2 (1) that gives the
current value necessary for the interface.
11. Trouble (ALM) turns on in normal alarm-free condition. When this signal is switched off (at occurrence of an alarm), the output
of the programmable controller should be stopped by the sequence program.
12. The pins with the same signal name are connected in the servo amplifier.
13. The signal can be changed by parameter No.PD07, PD08, PD09.
14. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
15. Devices can be assigned for DI1 DI2 DI3 with controller setting. For devices that can be assigned, refer to the controller
instruction manual. The assigned devices are for the Q173DCPU Q172DCPU Q173HCPU Q172HCPU and QD75MH
.
3 - 11
3. SIGNALS AND WIRING
3.3 Explanation of power supply system
3.3.1 Signal explanations
POINT
For the layout of connector and terminal block, refer to outline drawings in
chapter 9.
Connection target
(Application)
Abbreviation
Description
Supply the following power to L1, L2, L3. For the 1-phase 200V to 230VAC power supply, connect
the power supply to L1, L2, and keep L3 open.
Servo amplifier
MR-J3-
100B to
22KB
MR-J3-
10B1 to
40B1
MR-J3-
10B to 70B
Power supply
3-phase 200V to 230VAC, 50/60Hz
1-phase 200V to 230VAC, 50/60Hz
1-phase 100V to 120VAC, 50/60Hz
L1 L2 L3
L1 L2
L1
L2
L3
Main circuit power
supply
L1 L2
Servo amplifier
MR-J3-60B4 to 22KB4
L1 L2 L3
Power supply
3-phase 380V to 480VAC, 50/60Hz
1) MR-J3-700B or less
When not using the power factor improving DC reactor, connect P1 and P2. (Factory-wired.)
When using the power factor improving DC reactor, disconnect P1 and P2, and connect the
power factor improving DC reactor to P1 and P2.
2) MR-J3-11KB(4) to 22KB(4)
MR-J3-11KB(4) to 22KB(4) do not have P2.
Power factor
improving DC
reactor
P1
P2
When not using the power factor improving reactor, connect P1 and P. (Factory-wired)
When using the power factor improving reactor, connect it to P and P1.
Refer to section 11.13.
1) MR-J3-350B or less MR-J3-200B4 or less
When using servo amplifier built-in regenerative resistor, connect P( ) and D. (Factory-
wired)
When using regenerative option, disconnect P( ) and D, and connect regenerative option to
P and C.
2) MR-J3-350B4 500B(4) 700B(4)
P
C
D
MR-J3-350B4 500B(4) 700B(4) do not have D.
When using servo amplifier built-in regenerative resistor, connect P and C. (Factory-wired)
When using regenerative option, disconnect P and C, and connect regenerative option to P
and C.
Regenerative
option
3) MR-J3-11KB(4) to 22KB(4)
MR-J3-11KB(4) to 22KB(4) do not have D.
When not using the power regenerative converter and the brake unit, make sure to connect
the regenerative option to P and C.
Refer to section 11.2 to 11.5.
Supply the following power to L11 L21.
Servo amplifier MR-J3-10B to MR-J3-10B1 to MR-J3-60B4 to
Power supply
22KB
40B1
22KB4
L11
L21
Control circuit
power supply
1-phase 200V to 230VAC, 50/60Hz
1-phase 100V to 120VAC, 50/60Hz
1-phase 380V to 480VAC, 50/60Hz
L11 L21
L11 L21
L11 L21
U
V
W
Connect to the servo motor power supply terminals (U, V, W). During power-on, do not open or
close the motor power line. Otherwise, a malfunction or faulty may occur.
Servo motor power
When using the power regenerative converter/brake unit, connect it to P and N.
Do not connect to servo amplifier MR-J3-350B(4) or less.
For details, refer to section 11.3 to 11.5.
Return converter
Brake unit
N
Protective earth
(PE)
Connect to the earth terminal of the servo motor and to the protective earth (PE) of the control
box to perform grounding.
3 - 12
3. SIGNALS AND WIRING
3.3.2 Power-on sequence
(1) Power-on procedure
1) Always wire the power supply as shown in above section 3.1 using the magnetic contactor with the main
circuit power supply (three-phase: L , L , L , single-phase: L , L ). Configure up an external sequence
1
2
3
1
2
to switch off the magnetic contactor as soon as an alarm occurs.
2) Switch on the control circuit power supply L , L simultaneously with the main circuit power supply or
11 21
before switching on the main circuit power supply. If the main circuit power supply is not on, the display
shows the corresponding warning. However, by switching on the main circuit power supply, the warning
disappears and the servo amplifier will operate properly.
3) The servo amplifier can accept the servo-on command within 3s the main circuit power supply is
switched on. (Refer to paragraph (2) of this section.)
(2) Timing chart
SON accepted
(3s)
Main circuit
Control circuit
ON
OFF
ON
power
Base circuit
OFF
ON
95ms
10ms
95ms
Servo-on command
(from controller)
OFF
(3) Forced stop
Install an forced stop circuit externally to ensure that operation can be stopped and
power shut off immediately.
CAUTION
If the controller does not have an forced stop function, make up a circuit that switches off main circuit power
as soon as EM1 is turned off at a forced stop. When EM1 is turned off, the dynamic brake is operated to
stop the servo motor. At this time, the display shows the servo forced stop warning (E6).
During ordinary operation, do not use forced stop (EM1) to alternate stop and run. The service life of the
servo amplifier may be shortened.
Servo amplifier
24VDC
DICOM
(Note)
DOCOM
Forced stop
EM1
Note. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
3 - 13
3. SIGNALS AND WIRING
3.3.3 CNP1, CNP2, CNP3 wiring method
POINT
Refer to table 11.1 in section 11.11 for the wire sizes used for wiring.
MR-J3-500B or more MR-J3-350B4 or more does not have these connectors.
Use the supplied servo amplifier power supply connectors for wiring of CNP1, CNP2 and CNP3.
(1) MR-J3-10B to MR-J3-100B
(a) Servo amplifier power supply connectors
(Note)Servo amplifier power supply connectors
Connector for CNP1
54928-0670 (Molex)
Servo amplifier
CNP1
Connector for CNP2
<Applicable cable example>
54928-0520 (Molex)
Cable finish OD: to 3.8mm
CNP2
CNP3
Connector for CNP3
54928-0370 (Molex)
Note. These connectors are of insert type. As the crimping type, the following connectors (Molex) are recommended.
For CNP1: 51241-0600 (connector), 56125-0128 (terminal)
For CNP2: 51240-0500 (connector), 56125-0128 (terminal)
For CNP3: 51241-0300 (connector), 56125-0128 (terminal)
Crimping tool: CNP57349-5300
<Connector applicable cable example>
Cable finish OD: to 3.8mm
(b) Termination of the cables
Solid wire: After the sheath has been stripped, the cable can be used as it is.
Sheath
Core
8 to 9mm
Twisted wire: Use the cable after stripping the sheath and twisting the core. At this time, take care to
avoid a short caused by the loose wires of the core and the adjacent pole. Do not solder
the core as it may cause a contact fault. Alternatively, a bar terminal may be used to put
the wires together.
Cable size
Bar terminal type
For 1 cable (Note 1) For 2 cable
AI-TWIN2 1.5-10BK
Crimping tool (Note 2)
Variocrimp 4 206-204
[mm2]
1.25/1.5
2/2.5
AWG
16
AI1.5-10BK
AI2.5-10BU
14
Note 1. Manufacturer: Phoenix Contact
2. Manufacturer: WAGO
3 - 14
3. SIGNALS AND WIRING
(c) The twin type connector for CNP2 (L11 L21): 721-2105/026-000 (WAGO)
Using this connector enables passing a wire of control circuit power supply.
Refer to appendix 3 for details of connector.
Twin type connector for CNP2
CNP2
L11
L11
Power supply
or Front axis
Rear axis
L21
L21
(2) MR-J3-200B MR-J3-60B4 to MR-J3-200B4
(a) Servo amplifier power supply connectors
Servo amplifier power supply connectors
Connector for CNP1
721-207/026-000(Plug)
(WAGO)
Servo amplifier
<Applicable cable example>
Cable finish OD: 4.1mm or less
CNP1
Connector for CNP2
721-205/026-000(Plug)
(WAGO)
CNP2
CNP3
Connector for CNP3
721-203/026-000(Plug)
(WAGO)
(b) Termination of the cables
Solid wire: After the sheath has been stripped, the cable can be used as it is.
Sheath
Core
8 to 9mm
Twisted wire: Use the cable after stripping the sheath and twisting the core. At this time, take care to
avoid a short caused by the loose wires of the core and the adjacent pole. Do not solder
the core as it may cause a contact fault. Alternatively, a bar terminal may be used to put
the wires together.
Cable size
Bar terminal type
For 1 cable (Note 1) For 2 cable
AI-TWIN2 1.5-10BK
Crimping tool (Note 2)
Variocrimp 4 206-204
[mm2]
1.25/1.5
2/2.5
AWG
16
AI1.5-10BK
AI2.5-10BU
14
Note 1. Manufacturer: Phoenix Contact
2. Manufacturer: WAGO
3 - 15
3. SIGNALS AND WIRING
(c) The twin type connector for CNP2 (L11 L21): 721-2205/026-000 (WAGO)
Using this connector enables passing a wire of control circuit power supply.
Refer to appendix 3 for details of connector.
Twin type connector for CNP2
CNP2
L11
L11
Power supply
or Front axis
Rear axis
L21
L21
(3) MR-J3-350B
(a) Servo amplifier power supply connectors
Servo amplifier power supply connectors
Connector for CNP1
PC4/6-STF-7.62-CRWH
(Phoenix Contact)
Servo amplifier
<Applicable cable example>
Cable finish OD: 5mm or less
CNP1
Connector for CNP3
PC4/3-STF-7.62-CRWH
(Phoenix Contact)
CNP3
CNP2
Connector for CNP2(Note)
54928-0520 (Molex)
<Applicable cable example>
Cable finish OD: 3.8mm or less
Note. As twin type connector for CNP2 (L11, L21) is the same as MR-J3-100B or smaller. Refer to (1) (c) of this section.
(b) Termination of the cables
1) CNP1 CNP3
Solid wire: After the sheath has been stripped, the cable can be used as it is.
Sheath
Core
7mm
Twisted wire: Use the cable after stripping the sheath and twisting the core. At this time, take care to
avoid a short caused by the loose wires of the core and the adjacent pole. Do not
solder the core as it may cause a contact fault. Alternatively, a bar terminal may be
used to put the wires together.
Cable size
[mm2] AWG
Bar terminal type
For 1 cable For 2 cables
AI1.5-8BK AI-TWIN2 1.5-8BK
AI-TWIN2 2.5-10BU CRIMPFOX-ZA3
Crimping tool
Manufacturer
1.25/1.5
2.0/2.5
3.5
16
14
12
AI2.5-8BU
AI4-10GY
Phoenix Contact
3 - 16
3. SIGNALS AND WIRING
2) CNP2
CNP2 is the same as MR-J3-100B or smaller capacities. Refer to (1) (b) of this section.
(4) Insertion of cable into Molex and WAGO connectors
Insertion of cable into 54928-0610, 54928-0520, 54928 (Molex) connectors and 721-207/026-000, 721-205/
026-000 and 721-203/026-000 (WAGO) connectors are as follows.
The following explains for Molex, however use the same procedures for inserting WAGO connectors as
well.
POINT
It may be difficult for a cable to be inserted to the connector depending on
wire size or bar terminal configuration. In this case, change the wire type or
correct it in order to prevent the end of bar terminal from widening, and then
insert it.
How to connect a cable to the servo amplifier power supply connector is shown below.
3 - 17
3. SIGNALS AND WIRING
(a) When using the supplied cable connection lever
1) The servo amplifier is packed with the cable connection lever.
a) 54932-0000 (Molex)
[Unit: mm]
20.6
10
Approx. 4.9
M X J
5 4 9 3 2
Approx.3.4
b) 231-131 (WAGO)
[Unit: mm]
20.3
10
16
1.3
1.5
17.5
3 - 18
3. SIGNALS AND WIRING
2) Cable connection procedure
Cable connection lever
1) Attach the cable connection lever to the housing.
(Detachable)
2) Push the cable connection lever in the direction
of arrow.
3) Hold down the cable connection lever and insert
the cable in the direction of arrow.
4) Release the cable connection lever.
3 - 19
3. SIGNALS AND WIRING
(b) Inserting the cable into the connector
1) Applicable flat-blade screwdriver dimensions
Always use the screwdriver shown here to do the work.
[Unit: mm]
Approx. R0.3
Approx. 22
3
Approx. R0.3
2) When using the flat-blade screwdriver - part 1
1) Insert the screwdriver into the square hole.
Insert it along the top of the square hole to insert it smoothly.
2) If inserted properly, the screwdriver is held.
3) With the screwdriver held, insert the cable in the direction
of arrow. (Insert the cable as far as it will go.)
4) Releasing the screwdriver connects the cable.
3 - 20
3. SIGNALS AND WIRING
3) When using the flat-blade screwdriver - part 2
1) Insert the screwdriver into the
square window at top of the
connector.
2) Push the screwdriver in the
direction of arrow.
3) With the screwdriver pushed, insert the cable in the
direction of arrow. (Insert the cable as far as it will go.)
4) Releasing the screwdriver connects the cable.
3 - 21
3. SIGNALS AND WIRING
(4) How to insert the cable into Phoenix Contact connector
POINT
Do not use a precision driver because the cable cannot be tightened with
enough torque.
Insertion of cables into Phoenix Contact connector PC4/6-STF-7.62-CRWH or PC4/3-STF-7.62-CRWH is
shown as follows.
Before inserting the cable into the opening, make sure that the screw of the terminal is fully loose. Insert the
core of the cable into the opening and tighten the screw with a flat-blade screwdriver. When the cable is not
tightened enough to the connector, the cable or connector may generate heat because of the poor contact.
(When using a cable of 1.5mm2 or less, two cables may be inserted into one opening.)
Secure the connector to the servo amplifier by tightening the connector screw.
For securing the cable and the connector, use a flat-blade driver with 0.6mm blade edge thickness and
3.5mm diameter (Recommended flat-blade screwdriver: Phoenix Contact SZS 0.6 3.5). Apply 0.5 to 0.6
N m torque to screw.
[Unit: mm]
Flat-blade
screwdriver
180
100
To loosen To tighten
Wire
Opening
Recommended flat-blade screwdriver dimensions
To loosen
To tighten
Connector screw
Flat-blade
screwdriver
Servo amplifier power
supply connector
3 - 22
3. SIGNALS AND WIRING
3.4 Connectors and signal arrangements
POINT
The pin configurations of the connectors are as viewed from the cable
connector wiring section.
(1) Signal arrangement
The servo amplifier front view shown is that of the MR-J3-20B or less. Refer to chapter 9 Outline Drawings
for the appearances and connector layouts of the other servo amplifiers.
CN5 (USB connector)
Refer to section 11.8.
CN3
OPEN
1
11
LG
L
L
1
2
2
DI1
4
12
DI2
14
LG
3
13
L
3
N
DOCOM
MBR
15
P
1
MO1
6
MO2
16
5
P
2
DICOM
ALM
17
P
C
LA
8
LAR
18
7
LB
9
D
Connector for
the front axis of
CN1A SSCNET
cable.
L11
L12
LBR
19
LZ
LZR
20
U
Connector for the
rear axis of CN1B
SSCNET cable.
10
V
INP
DI1
W
DICOM
EM1
CHARGE
CN2
2
6
5
10
LG
4
8
MRR
MDR
1
P5
9
BAT
3
MR
7
MD
The frames of the CN2 and CN3
connectors are connected to the
PE (earth) terminal ( ) in the
amplifier.
The 3M make connector is shown.
When using any other connector,
refer to section 11.1.2.
3 - 23
3. SIGNALS AND WIRING
3.5 Signal (device) explanations
For the I/O interfaces (symbols in I/O division column in the table), refer to section 3.7.2.
In the control mode field of the table
The pin No.s in the connector pin No. column are those in the initial status.
(1) Connector applications
Connector
CN1A
Name
Function/Application
Connector for bus cable
from preceding axis.
Connector for bus cable to
next axis
Used for connection with the controller or preceding-axis servo amplifier.
CN1B
Used for connection with the next-axis servo amplifier or for connection of the cap.
CN2
CN4
Encoder connector
Battery connection
connector
Used for connection with the servo motor encoder.
When using as absolute position detection system, connect to battery (MR-J3BAT).
Before installing a battery, turn off the main circuit power while keeping the control
circuit power on. Wait for 15 minutes or more (20 minutes or for drive unit 30kW or
more) until the charge lamp turns off. Then, confirm that the voltage between P(
)
and N( ) (L and L for drive unit 30kW or more) is safe with a voltage tester and
others. Otherwise, an electric shock may occur. In addition, always confirm from the
front of the servo amplifier whether the charge lamp is off or not. Replace the
battery with main circuit power OFF and with control circuit power ON. Replacing
the battery with the control circuit power OFF results in loosing absolute position
data.
CN5
Communication connector The personal computer is connected.
(2) I/O device
(a) Input device
Connector
pin No.
I/O
division
Device
Symbol
EM1
Function/Application
Forced stop
CN3-20
Turn EM1 off (open between commons) to bring the motor to an forced
DI-1
stop state, in which the base circuit is shut off and the dynamic brake is
operated.
Turn EM1 on (short between commons) in the forced stop state to reset
that state.
When parameter No.PA.04 is set to "
(always ON) can be set inside.
1
", automatically ON
DI1
DI2
DI3
CN3-2
CN3-12
CN3-19
Devices can be assigned for DI1 DI2 DI3 with controller setting.
For devices that can be assigned, refer to the controller instruction
manual. The following devices can be assigned for Q172HCPU
Q173HCPU QD75MH.
DI-1
DI-1
DI-1
DI1: upper stroke limit (FLS)
DI2: lower stroke limit (RLS)
DI3: proximity dog (DOG)
3 - 24
3. SIGNALS AND WIRING
(b) Output device
Connector
pin No.
I/O
division
Device
Trouble
Symbol
ALM
Function/Application
CN3-15
CN3-13
CN3-9
ALM turns off when power is switched off or the protective circuit is
activated to shut off the base circuit.
Without alarm occurring, ALM turns on within about 1s after power-on.
When using this signal, set operation delay time of the electromagnetic
brake in parameter No.PC02.
DO-1
DO-1
DO-1
Electromagnetic
brake interlock
MBR
INP
In the servo-off or alarm status, MBR turns off.
In-position
(Positioning
completed)
INP turns on when the number of droop pulses is in the preset in-position
range. The in-position range can be changed using parameter No.PA10.
When the in-position range is increased, INP may be on conductive
status during low-speed rotation.
INP turns on when servo on turns on.
This signal cannot be used in the speed loop mode.
When using the signal, make it usable by the setting of parameter
No.PD07 to PD09.
RD turns on when the servo is switched on and the servo amplifier is
ready to operate.
When using the signal, make it usable by the setting of parameter
No.PD07 to PD09. DB turns off simultaneously when the dynamic brake
is operated. When using the external dynamic brake on the servo
amplifier of 11 kW or more, this device is required. (Refer to section
11.6.) For the servo amplifier of 7kW or less, it is not necessary to use
this device.
Ready
RD
DB
DO-1
DO-1
Dynamic brake
interlock
Speed reached
SA
When using this signal, make it usable by the setting of parameter
No.PD07 to PD09.
DO-1
When the servo is off, SA will be turned OFF. When servo motor rotation
speed becomes approximately setting speed, SA will be turned ON.
When the preset speed is 20r/min or less, SA always turns on. This
signal cannot be used in position loop mode.
Limiting torque
Zero speed
TLC
ZSP
When using this signal, make it usable by the setting of parameter
No.PD07 to PD09.
When torque is produced level of torque set with controller, TLC will be
turned ON. When the servo is off, TLC will be turned OFF.
When using this signal, make it usable by the setting of parameter
No.PD07 to PD09.
DO-1
DO-1
When the servo is off, SA will be turned OFF.
ZSP turns on when the servo motor speed is zero speed (50r/min) or
less. Zero speed can be changed using parameter No.PC07.
Example
Zero speed is 50r/min
1)
OFF level
70r/min
ON level
50r/min
Forward
rotation
direction
20r/min
(Hysteresis width)
3)
2)
Parameter
No.PC07
Servo motor
speed
0r/min
Parameter
No.PC07
ON level
50r/min
OFF level
70r/min
Reverse
rotation
direction
20r/min
(Hysteresis width)
4)
zero speed
(ZSP)
ON
OFF
ZPS turns on
when the servo motor is decelerated to 50r/min, and
1)
ZPS turns off when the servo motor is accelerated to 70r/min again.
2)
ZPS turns on
when the servo motor is decelerated again to 50r/min,
3)
and turns off when the servo motor speed has reached -70r/min.
4)
The range from the point when the servo motor speed has reached ON
level, and ZPS turns on, to the point when it is accelerated again and has
reached OFF level is called hysteresis width.
Hysteresis width is 20r/min for the MR-J3-B servo amplifier.
3 - 25
3. SIGNALS AND WIRING
Connector
pin No.
I/O
division
Device
Warning
Symbol
WNG
Function/Application
When using this signal, make it usable by the setting of parameter
No.PD07 to PD09.
DO-1
When warning has occurred, WNG turns on. When there is no warning,
WNG turns off within about 1.5s after power-on.
When using this signal, make it usable by the setting of parameter
No.PD07 to PD09.
Battery warning
BWNG
DO-1
BWNG turns on when battery cable disconnection warning (92) or battery
warning (9F) has occurred. When there is no battery warning, BWNG
turns off within about 1.5s after power-on.
Variable gain
selection
CDPS
ABSV
When using this signal, make it usable by the setting of parameter
No.PD07 to PD09.
CDPS is on during variable gain.
When using this signal, make it usable by the setting of parameter
No.PD07 to PD09.
DO-1
DO-1
Absolute position
erasing
ABSV turns on when the absolute position erased.
This signal cannot be used in position loop mode.
(c) Output signals
Connector
pin No.
Signal name
Symbol
Function/Application
Encoder A-phase
pulse
(Differential line
driver)
Encoder B-phase
pulse
(Differential line
driver)
LA
LAR
CN3-6
CN3-16
Outputs pulses per servo motor revolution set in parameter No.PA15 in the differential
line driver system. In CCW rotation of the servo motor, the encoder B-phase pulse
lags the encoder A-phase pulse by a phase angle of /2.
The relationships between rotation direction and phase difference of the A- and B-
phase pulses can be changed using parameter No.PC03.
LB
LBR
CN3-7
CN3-17
Output pulse specification and dividing ratio setting can be set. (Refer to section
5.1.9.)
Encoder Z-phase
pulse
(Differential line
driver)
LZ
LZR
CN3-8
CN3-18
Outputs the zero-point signal in the differential line driver system of the encoder. One
pulse is output per servo motor revolution. turns on when the zero-point position is
reached.
The minimum pulse width is about 400 s. For home position return using this pulse,
set the creep speed to 100r/min. or less.
Analog monitor 1
Analog monitor 2
MO1
MO2
CN3-4
Used to output the data set in parameter No.PC09 to across MO1-LG in terms of
voltage. Resolution 10 bits
Used to output the data set in parameter No.PC10 to across MO2-LG in terms of
voltage. Resolution 10 bits
CN3-14
(d) Power supply
Connector
pin No.
Signal name
Symbol
DICOM
Function/Application
Digital I/F power
supply input
CN3-5
CN3-10
Used to input 24VDC (24VDC 10% 150mA) for I/O interface of the servo amplifier.
The power supply capacity changes depending on the number of I/O interface points
to be used. Connect the positive terminal of the 24VDC external power supply for the
sink interface.
Digital I/F common DOCOM
CN3-3
Common terminal for input device such as EM1 of the servo amplifier. Pins are
connected internally. Separated from LG. Connect the positive terminal of the 24VDC
external power supply for the source interface.
Monitor common
Shield
LG
SD
CN3-1
CN3-11
Plate
Common terminal of M01 M02
Pins are connected internally.
Connect the external conductor of the shield cable.
3 - 26
3. SIGNALS AND WIRING
3.6 Alarm occurrence timing chart
When an alarm has occurred, remove its cause, make sure that the operation
signal is not being input, ensure safety, and reset the alarm before restarting
operation.
CAUTION
As soon as an alarm occurs, make the Servo off status and interrupt the main
circuit power.
When an alarm occurs in the servo amplifier, the base circuit is shut off and the servo motor is coated to a stop.
Switch off the main circuit power supply in the external sequence. To deactivate the alarm, power the control
circuit off, then on or give the error reset or CPU reset command from the servo system controller. However,
the alarm cannot be deactivated unless its cause is removed.
(Note)
Main circuit
Control circuit
ON
OFF
Power off
power
Power on
ON
OFF
Base circuit
Valid
Invalid
Brake operation
Brake operation
Dynamic brake
ON
Servo-on command
(from controller)
OFF
NO
YES
NO
YES
NO
Alarm
1s
Reset command
(from controller)
ON
OFF
50ms or more
60ms or more
Alarm occurs.
Remove cause of trouble.
Note. Switch off the main circuit power as soon as an alarm occurs.
(1) Overcurrent, overload 1 or overload 2
If operation is repeated by switching control circuit power off, then on to reset the overcurrent (32), overload
1 (50) or overload 2 (51) alarm after its occurrence, without removing its cause, the servo amplifier and
servo motor may become faulty due to temperature rise. Securely remove the cause of the alarm and also
allow about 30 minutes for cooling before resuming operation.
(2) Regenerative alarm
If operation is repeated by switching control circuit power off, then on to reset the regenerative (30) alarm
after its occurrence, the external regenerative resistor will generate heat, resulting in an accident.
(3) Instantaneous power failure
Undervoltage (10) occurs when the input power is in either of the following statuses.
A power failure of the control circuit power supply continues for 60ms or longer and the control circuit is
not completely off.
The bus voltage dropped to 200VDC or less for the MR-J3- B, to 158VDC or less for the MR-J3- B1, or
to 380VDC or less for the MR-J3- B4.
3 - 27
3. SIGNALS AND WIRING
3.7 Interfaces
3.7.1 Internal connection diagram
Servo amplifier
Approx
5.6k
CN3
EM1 20
CN3
10
Forced stop
DICOM
DI1
2
13 MBR
RA
RA
(Note 3)
(Note 2)
INP
(Note 1)
DI2 12
DI3 19
9
Approx
5.6k
(Note 3)
15 ALM
24VDC
DICOM
5
DOCOM
3
<Isolated>
CN3
6
LA
16 LAR
LB
17 LBR
LZ
Differential line
driver output
(35mA or less)
7
8
18 LZR
CN3
Analog monitor
4
1
MO1
LG
CN5
10VDC
VBUS
1
D
2
3
5
USB
14 MO2
11 LG
D
10VDC
GND
Servo motor
Encoder
CN2
7
8
3
4
2
MD
MDR
MR
MRR
LG
E
M
Note 1. Signal can be assigned for these pins with host controller setting.
For contents of signals, refer to the instruction manual of host controller.
2. This signal cannot be used with speed loop mode.
3. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
3 - 28
3. SIGNALS AND WIRING
3.7.2 Detailed description of interfaces
This section provides the details of the I/O signal interfaces (refer to the I/O division in the table) given in
section 3.5. Refer to this section and make connection with the external equipment.
(1) Digital input interface DI-1
Give a signal with a relay or open collector transistor. Refer to section 3.7.3 for the source input.
Servo amplifier
For transistor
EM1,
etc.
5.6k
Approx. 5mA
Switch
TR
DICOM
VCES 1.0V
ICEO 100
24VDC 10%
150mA
A
(2) Digital output interface DO-1
A lamp, relay or photocoupler can be driven. Install a diode (D) for an inductive load, or install an inrush
current suppressing resistor (R) for a lamp load. (Rated current: 40mA or less, maximum current: 50mA or
less, inrush current: 100mA or less) A maximum of 2.6V voltage drop occurs in the servo amplifier.
Refer to section 3.7.3 for the source output.
If polarity of diode is
reversed, servo
Servo amplifier
amplifier will fail.
ALM,
etc.
Load
DOCOM
(Note)
24VDC 10%
150mA
Note. If the voltage drop (maximum of 2.6V) interferes with the relay operation, apply high voltage (up to
26.4V) from external source.
3 - 29
3. SIGNALS AND WIRING
(3) Encoder output pulse DO-2 (Differential line driver system)
(a) Interface
Max. output current: 35mA
Servo amplifier
Servo amplifier
LA
(LB, LZ)
LA
(LB, LZ)
Am26LS32 or equivalent
150
High-speed photocoupler
100
LAR
LAR
(LBR, LZR)
(LBR, LZR)
LG
SD
SD
(b) Output pulse
Servo motor CCW rotation
LA
Time cycle (T) is determined by the settings
of parameter No.PA15 and PC03.
LAR
LB
T
LBR
/2
LZ
LZR
400 s or more
(4) Analog output
Servo amplifier
MO1
(MO2)
Output voltage 10V
Max. 1mA
Max. Output current Resolution: 10 bit
LG
3 - 30
3. SIGNALS AND WIRING
3.7.3 Source I/O interfaces
In this servo amplifier, source type I/O interfaces can be used. In this case, all DI-1 input signals and DO-1
output signals are of source type. Perform wiring according to the following interfaces.
(1) Digital input interface DI-1
Servo amplifier
EM1,
Approx. 5.6k
etc.
Switch
DICOM
24VDC 10%
150mA
Approx. 5mA
VCES 1.0V
ICEO 100 A
(2) Digital output interface DO-1
A maximum of 2.6V voltage drop occurs in the servo amplifier.
If polarity of diode is
reversed, servo
amplifier will fail.
Servo amplifier
ALM,
etc.
Load
DOCOM
(Note)
24VDC 10%
150mA
Note. If the voltage drop (maximum of 2.6V) interferes with the relay operation, apply high voltage (up to
26.4V) from external source.
3 - 31
3. SIGNALS AND WIRING
3.8 Treatment of cable shield external conductor
In the case of the CN2 and CN3 connectors, securely connect the shielded external conductor of the cable to
the ground plate as shown in this section and fix it to the connector shell.
External conductor
Sheath
Core
External conductor
Pull back the external conductor to cover the sheath
Sheath
Strip the sheath.
(1) For CN3 connector (3M connector)
Screw
Cable
Screw
Ground plate
(2) For CN2 connector (3M or Molex connector)
Cable
Ground plate
Screw
3 - 32
3. SIGNALS AND WIRING
3.9 SSCNET cable connection
POINT
Do not see directly the light generated from CN1A CN1B connector of servo
amplifier or the end of SSCNET cable.
When the light gets into eye, may feel something is wrong for eye.
(The light source of SSCNET complies with class1 defined in JIS C6802 or
IEC60825-1.)
(1) SSCNET cable connection
For CN1A connector, connect SSCNET cable connected to controller in host side or servo amplifier.
For CN1B connector, connect SSCNET cable connected to servo amplifier in lower side.
For CN1B connector of the final axis, put a cap came with servo amplifier.
Axis No.1 servo amplifier
Axis No.2 servo amplifier
Final axis servo amplifier
SSCNET cable
SSCNET cable
SSCNET cable
Controller
CN1A
CN1A
CN1A
Cap
CN1B
CN1B
CN1B
(2) How to connect/disconnect cable.
POINT
CN1A CN1B connector is put a cap to protect light device inside connector
from dust.
For this reason, do not remove a cap until just before mounting SSCNET
cable.
Then, when removing SSCNET cable, make sure to put a cap.
Keep the cap for CN1A CN1B connector and the tube for protecting light
code end of SSCNET cable in a plastic bag with a zipper of SSCNET
cable to prevent them from becoming dirty.
When asking repair of servo amplifier for some troubles, make sure to put a
cap on CN1A CN1B connector.
When the connector is not put a cap, the light device may be damaged at the
transit.
In this case, exchange and repair of light device is required.
(a) Mounting
1) For SSCNET cable in the shipping status, the tube for protect light code end is put on the end of
connector. Remove this tube.
2) Remove the CN1A CN1B connector cap of servo amplifier.
3 - 33
3. SIGNALS AND WIRING
3) With holding a tab of SSCNET cable connector, make sure to insert it into CN1A CN1B connector
of servo amplifier until you hear the click.
If the end face of optical code tip is dirty, optical transmission is interrupted and it may cause
malfunctions.
If it becomes dirty, wipe with a bonded textile, etc.
Do not use solvent such as alcohol.
Click
Tab
(b) Removal
With holding a tab of SSCNET cable connector, pull out the connector.
When pulling out the SSCNET cable from servo amplifier, be sure to put the cap on the connector
parts of servo amplifier to prevent it from becoming dirty.
For SSCNET cable, attach the tube for protection optical code's end face on the end of connector.
3 - 34
3. SIGNALS AND WIRING
3.10 Connection of servo amplifier and servo motor
During power-on, do not open or close the motor power line. Otherwise, a
malfunction or faulty may occur.
CAUTION
3.10.1 Connection instructions
Insulate the connections of the power supply terminals to prevent an electric
WARNING
shock.
Connect the wires to the correct phase terminals (U, V, W) of the servo amplifier
and servo motor. Not doing so may cause unexpected operation.
CAUTION
Do not connect AC power supply directly to the servo motor. Otherwise, a fault
may occur.
POINT
Refer to section 11.1 for the selection of the encoder cable.
This section indicates the connection of the servo motor power (U, V, W). Use of the optional cable and
connector set is recommended for connection between the servo amplifier and servo motor. When the
options are not available, use the recommended products. Refer to section 11.1 for details of the options.
(1) For grounding, connect the earth cable of the servo motor to the protective earth (PE) terminal ( ) of the
servo amplifier and connect the ground cable of the servo amplifier to the earth via the protective earth of
the control box. Do not connect them directly to the protective earth of the control panel.
Control box
Servo
amplifier
Servo motor
PE terminal
(2) Do not share the 24VDC interface power supply between the interface and electromagnetic brake. Always
use the power supply designed exclusively for the electromagnetic brake.
3 - 35
3. SIGNALS AND WIRING
3.10.2 Power supply cable wiring diagrams
(1) HF-MP service HF-KP series HF-KP series servo motor
(a) When cable length is 10m or less
10m or less
MR-PWS1CBL M-A1-L
MR-PWS1CBL M-A2-L
MR-PWS1CBL M-A1-H
MR-PWS1CBL M-A2-H
Servo amplifier
Servo motor
U
CNP3
AWG 19(red)
U
V
AWG 19(white)
AWG 19(black)
AWG 19(green/yellow)
V
M
W
W
(b) When cable length exceeds 10m
When the cable length exceeds 10m, fabricate an extension cable as shown below. In this case, the
motor power supply cable should be within 2m long.
Refer to section 11.11 for the wire used for the extension cable.
2m or less
MR-PWS1CBL2M-A1-L
MR-PWS1CBL2M-A2-L
MR-PWS1CBL2M-A1-H
MR-PWS1CBL2M-A2-H
MR-PWS2CBL03M-A1-L
MR-PWS2CBL03M-A2-L
50m or less
Servo amplifier
Servo motor
U
Extension cable
CNP3
AWG 19(red)
U
V
AWG 19(white)
AWG 19(black)
AWG 19(green/yellow)
V
M
W
W
(Note)
(Note)
a) Relay connector for
extension cable
b)
Relay connector for motor
power supply cable
Note. Use of the following connectors is recommended when ingress protection (IP65) is necessary.
Protective
structure
IP65
Relay connector
Description
Connector: RM15WTPZ-4P(71)
a) Relay connector for
extension cable
Cord clamp: RM15WTP-CP(5)(71)
(Hirose Electric)
Numeral changes depending on the cable OD.
Connector: RM15WTJA-4S(71)
Cord clamp: RM15WTP-CP(8)(71)
(Hirose Electric)
Numeral changes depending on the cable OD.
b) Relay connector for
motor power supply
cable
IP65
3 - 36
3. SIGNALS AND WIRING
(2) HF-SP series HC-RP series HC-UP series HC-LP series servo motor
POINT
Insert a contact in the direction shown in the figure. If inserted in the wrong
direction, the contact is damaged and falls off.
Soldered part or
crimping part
facing down
Soldered part
or crimping part
facing up
Pin No.1
Pin No.1
For CM10-SP10S-
For CM10-SP2S-
(a) Wiring diagrams
Refer to section 11.11 for the cables used for wiring.
1) When the power supply connector and the electromagnetic brake connector are separately supplied.
50m or less
Servo amplifier
Servo motor
U
V
U
V
M
W
W
CN3
24VDC
DOCOM
DICOM
RA1
RA2
ALM
MBR
Electromagnetic
Forced
stop
(EM1)
brake interlock Trouble
(MBR) (ALM)
RA2
RA1
24VDC power
supply for
electromagnetic
brake
B1
B2
(Note)
Note. There is no polarity in electromagnetic brake terminals B1 and B2.
3 - 37
3. SIGNALS AND WIRING
2) When the power supply connector and the electromagnetic brake connector are shared.
50m or less
Servo amplifier
Servo motor
U
V
U
V
M
W
W
CN3
24VDC
DOCOM
DICOM
RA1
RA2
ALM
MBR
Electromagnetic
Forced
stop
(EM1)
brake interlock Trouble
(MBR) (ALM)
RA2
RA1
24VDC power
supply for
electromagnetic
brake
B1
B2
(Note)
Note. There is no polarity in electromagnetic brake terminals B1 and B2.
(b) Connector and signal allotment
The connector fitting the servo motor is prepared as optional equipment. Refer to section 11.1. For types
other than those prepared as optional equipment, refer to chapter 3 in Servo Motor Instruction Manual,
Vol. 2 to select.
Servo motor side connectors
Servo motor
Electromagnetic
brake
Encoder
Power supply
MS3102A18-10P
MS3102A22-22P
HF-SP52(4) to 152(4)
HF-SP51 81
CM10-R2P
(DDK)
HF-SP202 352 502(4)
HF-SP121 to 301
HF-SP421 702(4)
HC-RP103 to 203
HC-RP353 503
a
CE05-2A32-17PD-B
CE05-2A22-23PD-B
CE05-2A24-10PD-B
CE05-2A22-23PD-B
CE05-2A24-10PD-B
c
CM10-R10P
(DDK)
The connector for
power is shared
b
HC-UP72 152
HC-UP202 to 502
MS3102A10SL-4P
The connector for
power is shared
HC-LP52 to 152
HC-LP202 302
CE05-2A22-23PD-B
CE05-2A24-10PD-B
MS3102A10SL-4P
3 - 38
3. SIGNALS AND WIRING
Power supply connector signal allotment
MS3102A18-10P
Encoder connector signal allotment
CM10-R10P
Power supply connector signal allotment
CE05-2A22-23PD-B
MS3102A22-22P
CE05-2A32-17PD-B
Terminal
Terminal
Signal
No.
Terminal
Signal
No.
Signal
7
6
5
4
No.
1
10
9
3
2
1
G
H
A
C
B
D
A
MR
A
B
C
U
V
A
B
C
U
V
F
E
B
2
MRR
8
3
W
W
C
D
4
BAT
LG
D
D
5
(earth)
(earth)
View a
View b
View b
6
E
F
7
8
P5
B1
G
H
9
(Note)
B2
10
SHD
(Note)
Note. For the motor
with an
electromagnetic
brake, supply
electromagnetic
brake power
(24VDC). There
is no polarity.
Power supply connector signal allotment
CE05-2A24-10PD-B
Brake connector signal allotment
CM10-R2P
Brake connector signal allotment
MS3102A10SL-4P
Terminal
Signal
No.
Terminal
Terminal
Signal
Signal
No.
No.
A
C
F
A
B
C
U
V
B1
(Note)
B2
B1
(Note)
B2
1
A
2
1
E
G
B
A
B
W
D
2
B
(Note)
(Note)
D
E
(earth)
B1
Note. For the motor
with an
Note. For the motor
with an
View c
View b
View c
electromagnetic
brake, supply
electromagnetic
brake power
electromagnetic
brake, supply
electromagnetic
brake power
(Note)
B2
F
(Note)
G
(24VDC). There
is no polarity.
(24VDC). There
is no polarity.
Note. For the motor
with an
electromagnetic
brake, supply
electromagnetic
brake power
(24VDC). There
is no polarity.
3 - 39
3. SIGNALS AND WIRING
(3) HA-LP series servo motor
(a) Wiring diagrams
Refer to section 11.11 for the cables used for wiring.
1) 200V class
NFB
50m or less
Servo amplifier
Servo motor
M
MC
TE
L1
L2
L3
U
U
V
V
W
W
BU
BV
CN3
DOCOM
DICOM
24VDC
BW
Cooling fan
(Note 2)
RA1
RA2
ALM
MBR
Electromagnetic
Forced
stop
(EM1)
brake interlock Trouble
(MBR) (ALM)
RA2
RA1
24VDC power
supply for
electromagnetic
brake
B1
B2
(Note 1)
OHS1
OHS2 Servo motor
thermal relay
24VDC
power supply
(Note 3)
RA3
Note 1. There is no polarity in electromagnetic brake terminals B1 and B2.
2. Cooling fan power supply of the HA-LP601, the HA-LP701M and the HA-LP11K2 servo motor is 1-phase. Power supply
specification of the cooling fan is different from that of the servo amplifier. Therefore, separate power supply is required.
3. Configure the power supply circuit which turns off the magnetic contactor after detection of servo motor thermal.
3 - 40
3. SIGNALS AND WIRING
2) 400V class
(Note4)
Cooling fan power supply
50m or less
Servo amplifier
Servo motor
MC
TE
U
L1
L2
L3
U
V
V
NFB
M
W
W
BU
BV
CN3
DOCOM
24VDC
BW
Cooling fan
(Note 2)
DICOM
RA1
RA2
ALM
MBR
Electromagnetic
Forced
stop
(EM1)
brake interlock Trouble
(MBR) (ALM)
RA2
RA1
24VDC power
supply for
electromagnetic
brake
B1
B2
(Note 1)
OHS1
OHS2 Servo motor
thermal relay
24VDC
power supply
(Note 3)
RA3
Note 1. There is no polarity in electromagnetic brake terminals B1 and B2.
2. There is no BW when the power supply of the cooling fan is a 1-phase.
3. Configure the power supply circuit which turns off the magnetic contactor after detection of servo motor thermal.
4. For the cooling fan power supply, refer to (3) (b) of this section.
3 - 41
3. SIGNALS AND WIRING
(b) Servo motor terminals
Encoder connector
CM10-R10P
Brake connector
MS3102A10SL-4P
Terminal box
Encoder connector signal
allotment
Terminal
No.
Brake connector signal
Terminal
No.
Signal
Signal
allotment
CM10-R10P
MS3102A10SL-4P
1
2
MR
B1
(Note)
B2
1
2
MRR
7
3
10
9
3
2
1
1
2
6
5
4
4
BAT
LG
(Note)
5
Note. For the motor
with an
8
6
electromagnetic
brake, supply
electromagnetic
brake power
7
8
P5
9
10
SHD
(24VDC). There
is no polarity.
Terminal box inside (HA-LP601(4) 701M(4) 11K2(4) )
Thermal sensor terminal
block
(OHS1 OHS2) M4 screw
Motor power supply
terminal block
Cooling fan terminal
block
(U
V
W) M6 screw
(BU BV) M4 screw
Terminal block signal
arrangement
OHS1OHS2
Earth terminal(
M6 screw
)
Encoder connector
CM10-R10P
BU BV
U
V
W
3 - 42
3. SIGNALS AND WIRING
Terminal box inside (HA-LP801(4) 12K1(4) 11K1M(4) 15K1M(4) 15K2(4) 22K2(4))
Cooling fan terminal
block
Thermal sensor
terminal block
(BU BV BW)
M4 screw
(OHS1 OHS2)
M4 screw
Terminal block signal
arrangement
Motor power supply
terminal block
Encoder connector
CM10-R10P
(U
V
W) M8 screw
BU BV BW OHS1OHS2
Earth terminal(
M6 screw
)
U
V
W
Terminal box inside (HA-LP15K1(4) 20K1(4) 22K1M(4))
Motor power supply
terminal block
(U V W) M8
Encoder connector
CM10-R10P
U
W
V
Thermal sensor
terminal block
(OHS1 OHS2) M4 screw
Cooling fan
terminal block
(BU BV BW) M4 screw
Terminal block signal arrangement
Earth terminal M6 screw
BU BV BW OHS1OHS2
U
V
W
3 - 43
3. SIGNALS AND WIRING
Terminal box inside (HA-LP25K1)
Motor power supply
terminal block
Encoder connector
CM10-R10P
(U
V
W) M10 screw
BU BV BW OHS1OHS2
U
V
W
Thermal sensor terminal
block
(OHS1 OHS2) M4 screw
Cooling fan terminal block
(BU BV BW) M4 screw
Terminal block signal arrangement
Earth terminal(
M6 screw
)
BU BV BW OHS1OHS2
U
V
W
3 - 44
3. SIGNALS AND WIRING
Signal name
Power supply
Abbreviation
Description
Connect to the motor output terminals (U, V, W) of the servo amplifier. During power-on, do
not open or close the motor power line. Otherwise, a malfunction or faulty may occur.
Supply power which satisfies the following specifications.
U
V
W
Power
consumption
[W]
Rated
current
[A]
Voltage
division
Voltage/
Servo motor
frequency
HA-LP601, 701M,
11K2
200V 3-phase 200 to 220VAC
class
42(50Hz)
0.21(50Hz)
0.25(60Hz)
50Hz 54(60Hz)
3-phase 200 to 230VAC
60Hz
3-phase 200 to 230VAC
50Hz/60Hz
HA-LP801, 12K1,
11K1M, 15K1M,
15K2, 22K2
62(50Hz)
76(60Hz)
0.18(50Hz)
0.17(60Hz)
HA-LP15K1, 20K1,
22K1M
65(50Hz)
85(60Hz)
0.20(50Hz)
0.22(60Hz)
(Note)
HA-LP25K1
120(50Hz) 0.65(50Hz)
175(60Hz) 0.80(60Hz)
Cooling fan
BU BV BW
HA-LP6014, 701M4, 400V 1-phase 200 to 220VAC
42(50Hz)
50Hz 54(60hz)
3-phase 200 to 230VAC
60Hz
3-phase 380 to 440VAC
50Hz 76(60Hz)
3-phase 380 to 480VAC
60Hz
3-phase 380 to 460VAC
50Hz 85(60Hz)
3-phase 380 to 480VAC
60Hz 150(60Hz) 0.22(60Hz)
0.21(50Hz)
11K24
class
0.25(60Hz)
HA-LP8014, 12K14,
11K1M4, 15K1M4,
15K24, 22K24
62(50Hz)
0.14(50Hz)
0.11(60Hz)
HA-LP15K14,
20K14, 22K1M4
HA-LP25K14
65(50Hz)
0.12(50Hz)
0.14(60Hz)
110(50Hz) 0.20(50Hz)
OHS1 OHS2 are opened when heat is generated to an abnormal temperature.
Motor thermal relay
Earth terminal
OHS1 OHS2 Maximum rating: 125V AC/DC, 3A or 250V AC/DC, 2A
Minimum rating: 6V AC/DC, 0.15A
For grounding, connect to the earth of the control box via the earth terminal of the servo
amplifier.
Note. There is no BW when the power supply of the cooling fan is a 1-phase.
3 - 45
3. SIGNALS AND WIRING
3.11 Servo motor with an electromagnetic brake
3.11.1 Safety precautions
Configure the electromagnetic brake circuit so that it is activated not only by the
interface unit signals but also by a forced stop (EM1).
Contacts must be open when
servo-off, when an alarm occurrence
and when an electromagnetic brake
interlock (MBR).
Circuit must be
opened during
forced stop (EM1).
Servo motor
RA EM1
24VDC
CAUTION
Electromagnetic brake
The electromagnetic brake is provided for holding purpose and must not be used
for ordinary braking.
Before performing the operation, be sure to confirm that the electromagnetic brake
operates properly.
POINT
Refer to the Servo Motor Instruction Manual (Vol.2) for specifications such as
the power supply capacity and operation delay time of the electromagnetic
brake.
Note the following when the servo motor with an electromagnetic brake is used.
1) Do not share the 24VDC interface power supply between the interface and electromagnetic brake.
Always use the power supply designed exclusively for the electromagnetic brake.
2) The brake will operate when the power (24VDC) switches off.
3) Switch off the servo-on command after the servo motor has stopped.
(1) Connection diagram
Servo amplifier
Servo motor
Electromagnetic Trouble Forced
brake stop
(ALM)
B1
B2
24VDC
DOCOM
DICOM
24VDC
MBR
RA1
(2) Setting
In parameter No.PC02 (electromagnetic brake sequence output), set the time delay (Tb) from
electromagnetic brake operation to base circuit shut-off at a servo off time as in the timing chart in section
3.11.2.
3 - 46
3. SIGNALS AND WIRING
3.11.2 Timing charts
(1) Servo-on command (from controller) ON/OFF
Tb [ms] after the servo-on is switched off, the servo lock is released and the servo motor coasts. If the
electromagnetic brake is made valid in the servo lock status, the brake life may be shorter. Therefore, when
using the electromagnetic brake in a vertical lift application or the like, set delay time (Tb) to about the same
as the electromagnetic brake operation delay time to prevent a drop.
Coasting
Servo motor speed
0 r/min
(95ms)
(95ms)
Tb
ON
Base circuit
OFF
Electromagnetic
brake operation
delay time
Electromagnetic
brake interlock
(MBR)
(Note 1) ON
OFF
ON
Servo-on command
(from controller)
OFF
(Note 3)
Operation command
(from controller)
0 r/min
Release
Activate
Electromagnetic
brake
Release delay time and external relay (Note 2)
Note 1. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
2. Electromagnetic brake is released after delaying for the release delay time of electromagnetic brake and operation time of
external circuit relay. For the release delay time of electromagnetic brake, refer to the Servo Motor Instruction Manual (Vol.2).
3. Give the operation command from the controller after the electromagnetic brake is released.
(2) Forced stop command (from controller) or forced stop (EM1) ON/OFF
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
Servo motor speed
Electromagnetic brake release
(10ms)
(210ms)
ON
Base circuit
OFF
(210ms)
Electromagnetic brake
operation delay time
(Note) ON
Electromagnetic
brake interlock (MBR)
OFF
Invalid (ON)
Valid (OFF)
Forced stop command
(from controller)
or
Forced stop (EM1)
Note. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
3 - 47
3. SIGNALS AND WIRING
(3) Alarm occurrence
Dynamic brake
Dynamic brake
Electromagnetic brake
Servo motor speed
Electromagnetic brake
(10ms)
ON
Base circuit
OFF
(Note) ON
Electromagnetic brake
operation delay time
Electromagnetic
brake interlock (MBR)
OFF
No (ON)
Alarm
Yes (OFF)
Note. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
(4) Both main and control circuit power supplies off
Dynamic brake
Dynamic brake
Electromagnetic brake
(10ms)
Servo motor speed
Base circuit
Electromagnetic brake
(Note 1)
15 to 100ms
ON
OFF
10ms
(Note 2) ON
Electromagnetic
brake interlock (MBR)
OFF
Electromagnetic brake
operation delay time
(Note2)
No (ON)
Alarm
Yes (OFF)
Main circuit
power
ON
OFF
Control circuit
Note 1. Changes with the operating status.
2. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
3 - 48
3. SIGNALS AND WIRING
(5) Only main circuit power supply off (control circuit power supply remains on)
Dynamic brake
Dynamic brake
Electromagnetic brake
(10ms)
Servo motor speed
Electromagnetic brake
(Note 1)
15ms or more
ON
Base circuit
OFF
(Note 3) ON
Electromagnetic
brake interlock
(MBR)
OFF
Electromagnetic brake
operation delay time
(Note 2)
No (ON)
Alarm
Yes (OFF)
ON
Main circuit power
supply
OFF
Note 1. Changes with the operating status.
2. When the main circuit power supply is off in a motor stop status, the main circuit off warning (E9) occurs
and the alarm (ALM) does not turn off.
3. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
3 - 49
3. SIGNALS AND WIRING
3.11.3 Wiring diagrams (HF-MP series HF-KP series servo motor)
POINT
For HF-SP series HC-RP series HC-UP series HC-LP series servo motors,
refer to section 3.10.2 (2).
(1) When cable length is 10m or less
10m or less
24VDC power
supply for
MR-BKS1CBL M-A1-L
MR-BKS1CBL M-A2-L
MR-BKS1CBL M-A1-H
MR-BKS1CBL M-A2-H
electromagnetic
brake
Servo motor
(Note2)
Forced stop
(EM1)
Electromagnetic
brake (MBR)
Trouble
(ALM)
AWG20
AWG20
B1
B2
(Note 1)
Note 1. Connect a surge absorber as close to the servo motor as possible.
2. There is no polarity in electromagnetic brake terminals (B1 and B2).
When fabricating the motor brake cable MR-BKS1CBL- M-H, refer to section 11.1.4.
(2) When cable length exceeds 10m
When the cable length exceeds 10m, fabricate an extension cable as shown below on the customer side. In
this case, the motor brake cable should be within 2m long.
Refer to section 11.8 for the wire used for the extension cable.
2m or less
MR-BKS1CBL2M-A1-L
MR-BKS1CBL2M-A2-L
MR-BKS1CBL2M-A1-H
MR-BKS1CBL2M-A2-H
MR-BKS2CBL03M-A1-L
MR-BKS2CBL03M-A2-L
24VDC power
supply for
electromagnetic
brake
50m or less
Extension cable (To be fabricated)
Servo motor
(Note 3)
B1
Forced stop
(EM1)
Electromagnetic
brake (MBR)
Trouble
(ALM)
AWG20
AWG20
(Note 1)
B2
(Note 2)
(Note 2)
a) Relay connector for b) Relay connector for motor
extension cable brake cable
Note 1. Connect a surge absorber as close to the servo motor as possible.
2. Use of the following connectors is recommended when ingress protection (IP65) is necessary.
Protective
structure
IP65
Relay connector
Description
CM10-CR2P-
(DDK)
a) Relay connector for
extension cable
Wire size: S, M, L
Wire size: S, M, L
CM10-SP2S-
(DDK)
IP65
b) Relay connector for
motor brake cable
3. There is no polarity in electromagnetic brake terminals (B1 and B2).
3 - 50
3. SIGNALS AND WIRING
3.12 Grounding
Ground the servo amplifier and servo motor securely.
To prevent an electric shock, always connect the protective earth (PE) terminal
(terminal marked ) of the servo amplifier with the protective earth (PE) of the
control box.
WARNING
The servo amplifier switches the power transistor on-off to supply power to the servo motor. Depending on the
wiring and ground cable routing, the servo amplifier may be affected by the switching noise (due to di/dt and
dv/dt) of the transistor. To prevent such a fault, refer to the following diagram and always ground.
To conform to the EMC Directive, refer to the EMC Installation Guidelines (IB(NA)67310).
Control box
Servo motor
MC
Servo amplifier
NFB
CN2
L1
Encoder
(Note)
Power supply
L2
L3
L11
L21
U
V
U
V
M
W
W
CN1A
Ensure to connect it to PE
terminal of the servo amplifier.
Do not connect it directly
to the protective earth of
the control panel.
Outer
box
Protective earth(PE)
Note. For 1-phase 200V to 230VAC, connect the power supply to L1
L2 and leave L3 open.
There is no L3 for 1-phase 100 to 120VAC power supply. Refer to section 1.3 for the power supply specification.
3 - 51
3. SIGNALS AND WIRING
3.13 Control axis selection
POINT
The control axis number set to rotary axis setting switch (SW1) should be the
same as the one set to the servo system controller.
Use the rotary axis setting switch (SW1) to set the control axis number for the servo. If the same numbers are
set to different control axes in a single communication system, the system will not operate properly. The control
axes may be set independently of the SSCNET cable connection sequence.
Rotary axis setting switch (SW1)
Spare (Be sure to set to the "Down" position.)
(Note) SW2
Up
8
Down
Test operation select switch (SW2-1)
Set the test operation select switch to the "Up" position, when
performing the test operation mode by using MR Configurator.
0
Note. This table indicates the status when the switch is set to "Down".
(Default)
Spare
Rotary axis setting switch (SW1)
Description
Axis No.1
Axis No.2
Axis No.3
Axis No.4
Axis No.5
Axis No.6
Axis No.7
Axis No.8
Axis No.9
Axis No.10
Axis No.11
Axis No.12
Axis No.13
Axis No.14
Axis No.15
Axis No.16
Display
01
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
02
03
04
05
06
07
Down
08
(Be sure to set to the
"Down" position.)
09
10
11
12
13
14
15
16
3 - 52
4. STARTUP
4. STARTUP
Do not operate the switches with wet hands. You may get an electric shock.
WARNING
Before starting operation, check the parameters. Some machines may perform
unexpected operation.
Take safety measures, e.g. provide covers, to prevent accidental contact of hands
and parts (cables, etc.) with the servo amplifier heat sink, regenerative resistor,
servo motor, etc. since they may be hot while power is on or for some time after
power-off. Their temperatures may be high and you may get burnt or a parts may
damaged.
CAUTION
During operation, never touch the rotating parts of the servo motor. Doing so can
cause injury.
4.1 Switching power on for the first time
When switching power on for the first time, follow this section to make a startup.
4.1.1 Startup procedure
Check whether the servo amplifier and servo motor are wired correctly using
Wiring check
visual inspection, DO forced output function (section 4.5.1), etc. (Refer to
section 4.1.2.)
Check the surrounding environment of the servo amplifier and servo motor.
(Refer to section 4.1.3.)
Surrounding environment check
Axis No. settings
Confirm that the axis No. settings for rotary axis setting switch (SW1) and
servo system controller are consistent. (Refer to section 3.12)
Set the parameters as necessary, such as the used control mode and
regenerative option selection. (Refer to chapter 5)
Parameter setting
For the test operation, with the servo motor disconnected from the machine
and operated at the speed as low as possible, check whether the servo motor
rotates correctly. (Refer to sections 4.5)
Test operation of servo motor
alone in test operation mode
For the test operation with the servo motor disconnected from the machine
and operated at the speed as low as possible, give commands to the servo
amplifier and check whether the servo motor rotates correctly.
Test operation of servo motor
alone by commands
Connect the servo motor with the machine, give operation commands from the
host command device, and check machine motions.
Test operation with servo motor
and machine connected
Make gain adjustment to optimize the machine motions. (Refer to chapter 6.)
Gain adjustment
Actual operation
Stop
Stop giving commands and stop operation.
4 - 1
4. STARTUP
4.1.2 Wiring check
(1) Power supply system wiring
Before switching on the main circuit and control circuit power supplies, check the following items.
(a) Power supply system wiring
The power supplied to the power input terminals (L1, L2, L3, L11, L21) of the servo amplifier should satisfy
the defined specifications. (Refer to section 1.3.)
(b) Connection of servo amplifier and servo motor
1) The servo motor power supply terminals (U, V, W) of the servo amplifier match in phase with the
power input terminals (U, V, W) of the servo motor.
Servo amplifier
U
Servo motor
U
V
V
M
W
W
2) The power supplied to the servo amplifier should not be connected to the servo motor power supply
terminals (U, V, W). To do so will fail the connected servo amplifier and servo motor.
Servo amplifier
Servo motor
M
U
V
W
U
V
W
3) The earth terminal of the servo motor is connected to the PE terminal of the servo amplifier.
Servo amplifier
Servo motor
M
4) P1-P2 (For 11kW or more, P1-P) should be connected.
Servo amplifier
P1
P2
(c) When option and auxiliary equipment are used
1) When regenerative option is used under 3.5kW for 200V class and 2kW for 400V class
The lead between P terminal and D terminal of CNP2 connector should not be connected.
The generative brake option should be connected to P terminal and C terminal.
A twisted cable should be used. (Refer to section 11.2)
4 - 2
4. STARTUP
2) When regenerative option is used over 5kW for 200V class and 3.5kW for 400V class
The lead of built-in regenerative resistor connected to P terminal and C terminal of TE1 terminal block
should not be connected.
The generative brake option should be connected to P terminal and C terminal.
A twisted cable should be used when wiring is over 5m and under 10m. (Refer to section 11.2)
3) When brake unit and power regenerative converter are used over 5kW
The lead of built-in regenerative resistor connected to P terminal and C terminal of TE1 terminal block
should not be connected.
Brake unit, power regenerative converter or power regeneration converter should be connected to P
terminal and N terminal. (Refer to section 11.3 to 11.5)
4) The power factor improving DC reactor should be connected P1 and P2 (For 11k to 22kW, P1 and P).
(Refer to section 11.13.)
Power factor
improving DC
Servo amplifier
reactor
P1
(Note)
P2
Note. Always disconnect P1 and P2. (For 11k to 22kW P1 and P)
(2) I/O signal wiring
(a) The I/O signals should be connected correctly.
Use DO forced output to forcibly turn on/off the pins of the CN3 connector. This function can be used to
perform a wiring check. In this case, switch on the control circuit power supply only.
(b) 24VDC or higher voltage is not applied to the pins of connectors CN3.
(c) SD and DOCOM of connector CN3 is not shorted.
Servo amplifier
CN3
DOCOM
SD
4.1.3 Surrounding environment
(1) Cable routing
(a) The wiring cables are free from excessive force.
(b) The encoder cable should not be used in excess of its flex life. (Refer to section 10.4.)
(c) The connector part of the servo motor should not be strained.
(2) Environment
Signal cables and power cables are not shorted by wire offcuts, metallic dust or the like.
4 - 3
4. STARTUP
4.2 Start up
Connect the servo motor with a machine after confirming that the servo motor operates properly alone.
(1) Power on
When the main and control circuit power supplies are switched on, "b01" (for the first axis) appears on the
servo amplifier display.
In the absolute position detection system, first power-on results in the absolute position lost (25) alarm and
the servo system cannot be switched on.
The alarm can be deactivated by then switching power off once and on again.
Also in the absolute position detection system, if power is switched on at the servo motor speed of 500r/min
or higher, position mismatch may occur due to external force or the like. Power must therefore be switched
on when the servo motor is at a stop.
(2) Parameter setting
Set the parameters according to the structure and specifications of the machine. Refer to chapter 5 for the
parameter definitions.
Parameter No.
PA14
Name
Setting
0
Description
Increase in positioning address rotates the motor in
the CCW direction.
Rotation direction setting
PA08
PA09
Auto tuning mode
1
Used.
Auto tuning response
12
Slow response (initial value) is selected.
After setting the above parameters, switch power off once. Then switch power on again to make the set
parameter values valid.
(3) Servo-on
Switch the servo-on in the following procedure.
1) Switch on main circuit/control circuit power supply.
2) The controller transmits the servo-on command.
When placed in the servo-on status, the servo amplifier is ready to operate and the servo motor is locked.
(4) Home position return
Always perform home position return before starting positioning operation.
(5) Stop
If any of the following situations occurs, the servo amplifier suspends the running of the servo motor and
brings it to a stop.
When the servo motor is with an electromagnetic brake, refer to section 3.11.
Operation/command
Servo off command
Stopping condition
The base circuit is shut off and the servo motor coasts.
The base circuit is shut off and the dynamic brake operates to bring
the servo motor to stop. The controller forced stop warning (E7)
occurs.
Servo system controller
Servo amplifier
Forced stop command
The base circuit is shut off and the dynamic brake operates to bring
the servo motor to stop.
Alarm occurrence
Forced stop
(EM1) OFF
The base circuit is shut off and the dynamic brake operates to bring
the servo motor to stop. The servo forced stop warning (E6) occurs.
4 - 4
4. STARTUP
4.3 Servo amplifier display
On the servo amplifier display (three-digit, seven-segment display), check the status of communication with the
servo system controller at power-on, check the axis number, and diagnose a fault at occurrence of an alarm.
(1) Display sequence
Servo amplifier power ON
Waiting for servo system controller
power to switch ON
(SSCNET communication)
Servo system controller power ON (SSCNET communication beginning)
Initial data communication
with servo system controller
(Initialization communication)
(Note 1)
When alarm warning
No. is displayed
(Note 3)
Ready OFF/servo OFF
Ready ON/servo OFF
At occurrence of overload
Flicker
display
Ready ON
Servo ON
At occurrence of overload
warning (Note 2)
(Note 3)
(Note 3)
Flicker
display
When alarm occurs,
alarm code appears.
During controller
forced stop
Flicker
display
Ready ON/servo ON
During forced stop
Flicker
display
Ordinary operation
Alarm reset or
warning
Servo system controller power OFF
Servo system controller power ON
Note 1.
2.
Only alarm and warning No. are displayed, but no axis No. is displayed
If warning other than E6 or E7 occurs during the servo on, flickering the
second place of decimal point indicates that it is during the servo on.
3. The right-hand segments of b01, c02 and d16 indicate the axis number.
(Below example indicates Axis1)
1 axis 2 axis
16 axis
4 - 5
4. STARTUP
(2) Indication list
Indication
Status
Description
Power of the servo amplifier was switched on at the condition that the power of
servo system controller is OFF.
The axis No. set to the servo system controller does not match the axis No. set
with the rotary axis setting switch (SW1) of the servo amplifier.
A servo amplifier fault occurred or an error took place in communication with the
servo system controller. In this case, the indication changes.
A b
Initializing
"Ab "
"AC "
"Ad "
"Ab "
The servo system controller is faulty.
A b
A C
A d
.
Initializing
Initializing
Initializing
Initializing
Initializing
During initial setting for communication specifications
Initial setting for communication specifications completed, and then it synchronized
with servo system controller.
During initial parameter setting communication with servo system controller
During motor encoder information and telecommunication with servo system
controller
A E
A F
During initial signal data communication with servo system controller
During the completion process for initial data communication with servo system
A H
A A
Initializing completion
Initializing standby
controller
The power supply of servo system controller is turned off during the power supply
of servo amplifier is on.
b # #
d # #
C # #
Ready OFF
Servo ON
The ready off signal from the servo system controller was received.
The ready off signal from the servo system controller was received.
The ready off signal from the servo system controller was received.
The alarm No./warning No. that occurred is displayed. (Refer to section 9.1.)
CPU watchdog error has occurred.
(Note 1)
(Note 1)
(Note 1)
(Note 2)
Servo OFF
Alarm Warning
CPU Error
8 8 8
b 0 0.
JOG operation, positioning operation, programmed operation, DO forced output.
(Note 3)
(Note 1)
b # #.
(Note 3)
Test operation mode
Motor-less operation
d # #.
C # #.
Note 1. ## denotes any of numerals 00 to 16 and what it means is listed below.
#
0
Description
Set to the test operation mode.
First axis
1
2
Second axis
Third axis
3
4
Fourth axis
5
Fifth axis
6
Sixth axis
7
Seventh axis
Eighth axis
8
9
Ninth axis
10
11
12
13
14
15
16
Tenth axis
Eleventh axis
Twelfth axis
Thirteenth axis
Fourteenth axis
Fifteenth axis
Sixteenth axis
2. ** indicates the warning/alarm No.
3. Requires the MR Configurator.
4 - 6
4. STARTUP
4.4 Test operation
Before starting actual operation, perform test operation to make sure that the machine operates normally.
Refer to section 4.2 for the power on and off methods of the servo amplifier.
POINT
If necessary, verify controller program by using motorless operation.
Refer to section 4.5.2 for the motorless operation.
Test operation of servo motor
In this step, confirm that the servo amplifier and servo motor operate normally.
alone in JOG operation of test
operation mode
With the servo motor disconnected from the machine, use the test operation
mode and check whether the servo motor rotates correctly. Refer to section
4.5 for the test operation mode.
Test operation of servo motor
In this step, confirm that the servo motor rotates correctly under the
alone by commands
commands from the controller.
Make sure that the servo motor rotates in the following procedure.
Give a low speed command at first and check the rotation direction, etc. of the
servo motor.
If the servo motor does not operate in the intended direction, check the input
signal.
Test operation with servo motor
In this step, connect the servo motor with the machine and confirm that the
and machine connected
machine operates normally under the commands from the command device.
Make sure that the servo motor rotates in the following procedure.
Give a low speed command at first and check the operation direction, etc. of
the machine. If the machine does not operate in the intended direction, check
the input signal. In the status display, check for any problems of the servo
motor speed, command pulse frequency, load ratio, etc.
Then, check automatic operation with the program of the command device.
4 - 7
4. STARTUP
4.5 Test operation mode
The test operation mode is designed for servo operation confirmation and not for
machine operation confirmation. Do not use this mode with the machine. Always
use the servo motor alone.
CAUTION
If an operation fault occurred, use the forced stop (EM1) to make a stop.
POINT
The content described in this section indicates the environment that servo
amplifier and personal computer are directly connected.
By using a personal computer and the MR Configurator, you can execute jog operation, positioning operation,
DO forced output program operation without connecting the servo system controller.
4.5.1 Test operation mode in MR Configurator
(1) Test operation mode
(a) Jog operation
Jog operation can be performed without using the servo system controller. Use this operation with the
forced stop reset. This operation may be used independently of whether the servo is on or off and
whether the servo system controller is connected or not.
Exercise control on the jog operation screen of the MR Configurator.
1) Operation pattern
Item
Initial value
200
Setting range
0 to max. speed
0 to 50000
Speed [r/min]
Acceleration/deceleration time constant [ms]
1000
2) Operation method
Operation
Screen control
Forward rotation start
Reverse rotation start
Stop
Click the "Forward" button.
Click the "Reverse" button.
Click the "Stop" button.
(b) Positioning operation
Positioning operation can be performed without using the servo system controller. Use this operation
with the forced stop reset. This operation may be used independently of whether the servo is on or off
and whether the servo system controller is connected or not.
Exercise control on the positioning operation screen of the MR Configurator.
1) Operation pattern
Item
Initial value
4000
Setting range
0 to 99999999
0 to max. speed
0 to 50000
Travel [pulse]
Speed [r/min]
200
Acceleration/deceleration time constant [ms]
1000
4 - 8
4. STARTUP
2) Operation method
Operation
Forward rotation start
Reverse rotation start
Pause
Screen control
Click the "Forward" button.
Click the "Reverse" button.
Click the "Pause" button.
(c) Program operation
Positioning operation can be performed in two or more operation patterns combined, without using the
servo system controller. Use this operation with the forced stop reset. This operation may be used
independently of whether the servo is on or off and whether the servo system controller is connected or
not.
Exercise control on the programmed operation screen of the MR Configurator. For full information, refer
to the MR Configurator Installation Guide.
Operation
Screen control
Start
Stop
Click the "Start" button.
Click the "Reset" button.
(d) Output signal (DO) forced output
Output signals can be switched on/off forcibly independently of the servo status. Use this function for
output signal wiring check, etc.
Exercise control on the DO forced output screen of the MR Configurator.
(2) Operation procedure
(a) Jog operation, positioning operation, program operation, DO forced output.
1) Switch power off.
2) Set SW2-1 to "UP".
SW2
Set SW2-1 to "UP"
UP
DOWN
1
2
When SW1 and SW2-1 is set to the axis number and operation is performed by the servo system
controller, the test operation mode screen is displayed on the personal computer, but no function is
performed.
3) Switch servo amplifier power on.
When initialization is over, the display shows the following screen.
Decimal point flickers.
4) Perform operation with the personal computer.
4 - 9
4. STARTUP
4.5.2 Motorless operation in controller
POINT
Use motor-less operation which is available by making the servo system
controller parameter setting.
Motorless operation is done while connected with the servo system controller.
(1) Motorless operation
Without connecting the servo motor, output signals or status displays can be provided in response to the
servo system controller commands as if the servo motor is actually running. This operation may be used to
check the servo system controller sequence. Use this operation with the forced stop reset. Use this
operation with the servo amplifier connected to the servo system controller.
For stopping the motorless operation, set the selection of motorless operation to [Invalid] in servo parameter
setting of servo system controller. Motorless operation will be invalid condition after switching on power
supply next time.
(a) Load conditions
Load item
Condition
Load torque
Load inertia moment ratio
0
Same as servo motor inertia moment
(b) Alarms
The following alarms and warning do not occur. However, the other alarms and warnings occur as
when the servo motor is connected.
Encoder error 1 (16)
Converter error (1B) (Note 1)
Encoder error 2 (20)
Converter warning (9C) (Note 1)
Main circuit off warning (E9) (Note 2)
Absolute position erasure (25)
Battery cable disconnection warning (92)
Battery warning (9F)
Note 1. Alarm and warning for the drive units of 30kW or more. For details, refer to section 13.6.2.
2. Main circuit off warning (E9) does not occur only when the forced stop of the converter unit is enabled as the cause
of occurrence with the drive unit of 30kW or more. Main circuit of warning, otherwise, occurs when the cause of
occurrence with the drive unit of 30kW or more is other than above, or with the servo amplifier of 22 kW or less.
(2) Operating procedure
1) Switch off servo amplifier
2) Set parameter No.PC05 to "1", change test operation mode switch (SW2-1) to normal condition side
"Down", and then turn on the power supply.
SW2
UP
DOWN
Set SW2-1 to "DOWN"
1
2
3) Perform motor-less operation with the personal computer.
The display shows the following screen.
Decimal point flickers.
4 - 10
5. PARAMETERS
5. PARAMETERS
CAUTION
Never adjust or change the parameter values extremely as it will make operation
instable.
POINT
When the servo amplifier is connected with the servo system controller, the
parameters are set to the values of the servo system controller. Switching
power off, then on makes the values set on the MR Configurator (servo
configuration software) invalid and the servo system controller values valid.
Setting may not be made to some parameters and ranges depending on the
model or version of the servo system controller. For details, refer to the servo
system controller user's manual.
In this servo amplifier, the parameters are classified into the following groups on a function basis.
Parameter group
Main description
Basic setting parameters
Make basic setting with these parameters. Generally, the operation is possible only with these
parameter settings.
(No.PA
Gain/filter parameters
(No.PB
Extension setting parameters
(No.PC
I/O setting parameters
(No.PD
)
Use these parameters when making gain adjustment manually.
)
When changing settings such as analog monitor output signal or encoder electromagnetic brake
sequence output, use these parameters.
)
Use these parameters when changing the I/O signals of the servo amplifier.
)
Mainly setting the basic setting parameters (No.PA
of introduction.
) allows the setting of the basic parameters at the time
5.1 Basic setting parameters (No.PA
POINT
)
Parameter whose symbol is preceded by * is made valid with the following
conditions.
* : Set the parameter value, switch power off once after setting, and then
switch it on again, or perform the controller reset.
**: Set the parameter value, switch power off once, and then switch it on
again.
Never change parameters for manufacturer setting.
5 - 1
5. PARAMETERS
5.1.1 Parameter list
No. Symbol
Name
Initial value
0000h
0000h
0000h
0000h
0
Unit
PA01
For manufacturer setting
PA02 **REG Regenerative option
PA03 *ABS Absolute position detection system
PA04 *AOP1 Function selection A-1
PA05
PA06
PA07
For manufacturer setting
1
1
PA08 ATU Auto tuning mode
0001h
12
PA09 RSP Auto tuning response
PA10
PA11
PA12
PA13
INP
In-position range
100
pulse
%
For manufacturer setting
1000.0
1000.0
0000h
0
%
PA14 *POL Rotation direction selection
PA15 *ENR Encoder output pulses
4000
0
pulse/rev
PA16
PA17
PA18
For manufacturer setting
0000h
0000h
000Bh
PA19 *BLK Parameter write inhibit
5 - 2
5. PARAMETERS
5.1.2 Parameter write inhibit
Parameter
Initial value
000Bh
Unit
Setting range
No. Symbol
Name
PA19 *BLK Parameter write inhibit
Refer to the text.
POINT
When setting the parameter values from the servo system controller, the
parameter No.PA19 setting need not be changed.
This parameter is made valid when power is switched off, then on after
setting, or when the controller reset has been performed.
In the factory setting, this servo amplifier allows changes to the basic setting parameter, gain/filter parameter
and extension setting parameter settings. With the setting of parameter No.PA19, write can be disabled to
prevent accidental changes.
The following table indicates the parameters which are enabled for reference and write by the setting of
parameter No.PA19. Operation can be performed for the parameters marked
.
Basic setting
parameters
No.PA
Gain/filter
parameters
No.PB
Extension setting
parameters
No.PC
I/O setting
parameters
No.PD
Parameter No.PA19
setting
Setting operation
Reference
Write
0000h
000Bh
Reference
Write
(initial value)
Reference
Write
000Ch
Reference
100Bh
Parameter
Write
Reference
Write
No.PA19 only
100Ch
Parameter
No.PA19 only
5 - 3
5. PARAMETERS
5.1.3 Selection of regenerative option
Parameter
Initial value
0000h
Unit
Setting range
No. Symbol
Name
PA02 **REG Regenerative option
Refer to the text.
POINT
This parameter value and switch power off once, then switch it on again to
make that parameter setting valid.
Wrong setting may cause the regenerative option to burn.
If the regenerative option selected is not for use with the servo amplifier,
parameter error (37) occurs.
For a drive unit of 30kW or more, always set the parameter to "
selecting regenerative option is carried out by the converter unit.
00" since
Set this parameter when using the regenerative option, brake unit, power regeneration converter, or power
regeneration common converter.
Parameter No.PA02
0 0
Selection of regenerative option
00: Regenerative option is not used
For servo amplifier of 100W, regenerative resistor is not used.
For servo amplifier of 200 to 7kW, built-in regenerative resistor is used.
Supplied regenerative resistors or regenerative option is used with
the servo amplifier of 11k to 22kW.
For a drive unit of 30kW or more, select regenerative option by the
converter unit.
01: FR-BU2-(H) FR-RC-(H) FR-CV-(H)
02: MR-RB032
03: MR-RB12
04: MR-RB32
05: MR-RB30
06: MR-RB50(Cooling fan is required)
08: MR-RB31
09: MR-RB51(Cooling fan is required)
80: MR-RB1H-4
81: MR-RB3M-4(Cooling fan is required)
82: MR-RB3G-4(Cooling fan is required)
83: MR-RB5G-4(Cooling fanis required)
84: MR-RB34-4(Cooling fanis required)
85: MR-RB54-4(Cooling fanis required)
FA: When the supplied regenerative resistor is cooled by the cooling fan to
increase the ability with the servo amplifier of 11k to 22kW.
5 - 4
5. PARAMETERS
5.1.4 Using absolute position detection system
Parameter
Initial value
0000h
Unit
Setting range
No. Symbol
Name
PA03 *ABS Absolute position detection system
Refer to the text.
POINT
This parameter is made valid when power is switched off, then on after
setting, or when the controller reset has been performed.
This parameter cannot be used in the speed control mode.
Set this parameter when using the absolute position detection system in the position control mode.
Parameter No.PA03
0 0 0
Selection of absolute position detection system (refer to chapter 12)
0: Used in incremental system
1: Used in absolute position detection system
5.1.5 Forced stop input selection
Parameter
Initial value
0000h
Unit
Setting range
No. Symbol
Name
PA04 *AOP1 Function selection A-1
Refer to the text.
POINT
This parameter is made valid when power is switched off, then on after
setting, or when the controller reset has been performed.
The servo forced stop function is avoidable.
Parameter No.PA04
0
0 0
Selection of servo forced stop
0: Valid (Forced stop (EM1) is used.)
1: Invalid (Forced stop (EM1) is not used.)
When not using the forced stop (EM1) of servo amplifier, set the selection of servo forced stop to Invalid ( 1
). At this time, the forced stop (EM1) automatically turns on inside the servo amplifier.
5 - 5
5. PARAMETERS
5.1.6 Auto tuning
Parameter
Initial value
Unit
Setting range
No. Symbol
Name
PA08 ATU Auto tuning mode
PA09 RSP Auto tuning response
0001h
12
Refer to the text.
1 to 32
Make gain adjustment using auto tuning. Refer to section 6.2 for details.
(1) Auto tuning mode (parameter No.PA08)
Select the gain adjustment mode.
Parameter No.PA08
0 0 0
Gain adjustment mode setting
Setting Gain adjustment mode Automatically set parameter No. (Note)
0
1
2
3
Interpolation mode
Auto tuning mode 1
Auto tuning mode 2
Manual mode
PB06 PB08 PB09 PB10
PB06 PB07 PB08 PB09 PB10
PB07 PB08 PB09 PB10
Note. The parameters have the following names.
Parameter No.
Name
PB06
PB07
PB08
PB09
PB10
Ratio of load inertia moment to servo motor inertia moment
Model loop gain
Position loop gain
Speed loop gain
Speed integral compensation
5 - 6
5. PARAMETERS
(2) Auto tuning response (parameter No.PA09)
If the machine hunts or generates large gear sound, decrease the set value. To improve performance, e.g.
shorten the settling time, increase the set value.
Guideline for machine
Guideline for machine
Setting
Response
Setting
Response
resonance frequency [Hz]
resonance frequency [Hz]
1
2
Low response
10.0
11.3
12.7
14.3
16.1
18.1
20.4
23.0
25.9
29.2
32.9
37.0
41.7
47.0
52.9
59.6
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Low response
67.1
75.6
3
85.2
4
95.9
5
108.0
121.7
137.1
154.4
173.9
195.9
220.6
248.5
279.9
315.3
355.1
400.0
6
7
8
9
10
11
12
13
14
15
16
Middle response
Middle response
5.1.7 In-position range
Parameter
Name
Initial value
100
Unit
Setting range
0 to 65535
No. Symbol
PA10
INP
In-position range
pulse
POINT
This parameter cannot be used in the speed control mode.
Set the range, where in position (INP) is output, in the command pulse unit.
Servo motor droop pulse
Command pulse
Droop pulse
Command pulse
In-position range [pulse]
ON
In position (INP)
OFF
5 - 7
5. PARAMETERS
5.1.8 Selection of servo motor rotation direction
Parameter
Initial value
0
Unit
Setting range
No. Symbol
Name
PA14 *POL Rotation direction selection
0
1
POINT
This parameter is made valid when power is switched off, then on after
setting, or when the controller reset has been performed.
Select servo motor rotation direction relative.
Servo motor rotation direction
Parameter No.PA14
setting
When positioning address
When positioning address
decreases
increases
CCW
0
1
CW
CW
CCW
Forward rotation (CCW)
Reverse rotation (CW)
5.1.9 Encoder output pulse
Parameter
Initial value
4000
Unit
Setting range
1 to 65535
No. Symbol
Name
PA15 *ENR Encoder output pulse
pulse/rev
POINT
This parameter is made valid when power is switched off, then on after
setting, or when the controller reset has been performed.
Used to set the encoder pulses (A-phase, B-phase) output by the servo amplifier.
Set the value 4 times greater than the A-phase or B-phase pulses.
You can use parameter No.PC03 to choose the output pulse setting or output division ratio setting.
The number of A/B-phase pulses actually output is 1/4 times greater than the preset number of pulses.
The maximum output frequency is 4.6Mpps (after multiplication by 4). Use this parameter within this range.
5 - 8
5. PARAMETERS
(1) For output pulse designation
Set "
0
" (initial value) in parameter No.PC03.
Set the number of pulses per servo motor revolution.
Output pulse set value [pulses/rev]
For instance, set "5600" to Parameter No.PA15, the actually output A/B-phase pulses are as indicated
below.
5600
4
A B-phase output pulses
1400[pulse]
(2) For output division ratio setting
Set " " in parameter No.PC03.
1
The number of pulses per servo motor revolution is divided by the set value.
Resolution per servo motor revolution
Output pulse
[pulses/rev]
Set value
For instance, set "8" to Parameter No.PA15, the actually output A/B-phase pulses are as indicated below.
262144 1
A B-phase output pulses
8192[pulse]
8
4
5 - 9
5. PARAMETERS
5.2 Gain/filter parameters (No.PB
POINT
)
Parameter whose symbol is preceded by * is made valid with the following
conditions.
* : Set the parameter value, switch power off once after setting, and then
switch it on again, or perform the controller reset.
5.2.1 Parameter list
No. Symbol
Name
Initial value
0000h
Unit
PB01 FILT Adaptive tuning mode (Adaptive filter
)
Vibration suppression control tuning mode
(advanced vibration suppression control)
For manufacturer setting
PB02 VRFT
0000h
PB03
0
0
PB04
PB05
FFC Feed forward gain
%
For manufacturer setting
500
Multiplier
PB06 GD2 Ratio of load inertia moment to servo motor inertia moment
7.0
(
1)
PB07 PG1 Model loop gain
PB08 PG2 Position loop gain
PB09 VG2 Speed loop gain
24
37
rad/s
rad/s
rad/s
ms
823
PB10
PB11 VDC Speed differential compensation
PB12 For manufacturer setting
VIC
Speed integral compensation
33.7
980
0
PB13 NH1 Machine resonance suppression filter 1
PB14 NHQ1 Notch shape selection 1
4500
0000h
4500
0000h
Hz
Hz
PB15 NH2 Machine resonance suppression filter 2
PB16 NHQ2 Notch shape selection 2
PB17
PB18
Automatic setting parameter
LPF Low-pass filter setting
3141
100.0
100.0
0.00
rad/s
Hz
PB19 VRF1 Vibration suppression control vibration frequency setting
PB20 VRF2 Vibration suppression control resonance frequency setting
Hz
PB21
PB22
For manufacturer setting
0.00
PB23 VFBF Low-pass filter selection
0000h
0000h
0000h
0000h
10
PB24 *MVS Slight vibration suppression control selection
PB25
For manufacturer setting
PB26 *CDP Gain changing selection
PB27 CDL Gain changing condition
PB28 CDT Gain changing time constant
1
ms
PB29 GD2B Gain changing ratio of load inertia moment to servo motor inertia moment
Multiplier
7.0
(
1)
PB30 PG2B Gain changing position loop gain
37
823
rad/s
rad/s
ms
PB31 VG2B Gain changing speed loop gain
PB32 VICB Gain changing speed integral compensation
33.7
100.0
100.0
0.00
0.00
100
PB33 VRF1B Gain changing vibration suppression control vibration frequency setting
PB34 VRF2B Gain changing vibration suppression control resonance frequency setting
Hz
Hz
PB35
PB36
PB37
PB38
PB39
For manufacturer setting
0.0
0.0
5 - 10
5. PARAMETERS
No. Symbol
Name
Initial value
0.0
Unit
PB40
PB41
PB42
PB43
PB44
PB45
For manufacturer setting
1125
1125
0004h
0.0
0000h
5.2.2 Detail list
Initial
Setting
range
No. Symbol
Name and function
Unit
value
PB01 FILT Adaptive tuning mode (adaptive filter
)
0000h
Select the setting method for filter tuning. Setting this parameter to "
1" (filter
tuning mode 1) automatically changes the machine resonance suppression filter 1
(parameter No.PB13) and notch shape selection (parameter No.PB14).
Machine resonance point
Frequency
Frequency
Notch frequency
0 0 0
Filter tuning mode selection
Setting Filter adjustment mode Automatically set parameter
0
1
2
Filter OFF
(Note)
Parameter No.PB13
Parameter No.PB14
Filter tuning mode
Manual mode
Note. Parameter No.PB13 and PB14 are fixed to the initial values.
When this parameter is set to "
1", the tuning is completed after positioning is
done the predetermined number or times for the predetermined period of time, and the
setting changes to "
changes to "
2". When the filter tuning is not necessary, the setting
0". When this parameter is set to " 0", the initial values are set
to the machine resonance suppression filter 1 and notch shape selection. However, this
does not occur when the servo off.
5 - 11
5. PARAMETERS
Initial
value
Setting
range
No. Symbol
Name and function
Unit
PB02 VRFT Vibration suppression control tuning mode (advanced vibration suppression control)
This parameter cannot be used in the speed control mode.
0000h
The vibration suppression is valid when the parameter No.PA08 (auto tuning) setting is
"
2" or "
3". When PA08 is "
1", vibration suppression is always
invalid.
Select the setting method for vibration suppression control tuning. Setting this parameter
to " 1" (vibration suppression control tuning mode) automatically changes the
vibration suppression control vibration frequency (parameter No.PB19) and vibration
suppression control resonance frequency (parameter No.PB20) after positioning is done
the predetermined number of times.
Droop pulse
Command
Droop pulse
Command
Automatic
adjustment
Machine end
position
Machine end
position
0 0 0
Vibration suppression control tuning mode
Vibration suppression
control tuning mode
Automatically set
parameter
Setting
0
Vibration suppression
control OFF
(Note)
Vibration suppression
control tuning mode
(Advanced vibration
suppression control)
Manual mode
Parameter No.PB19
Parameter No.PB20
1
2
Note. Parameter No.PB19 and PB20 are fixed to the initial values.
When this parameter is set to "
1", the tuning is completed after positioning is
done the predetermined number or times for the predetermined period of time, and the
setting changes to "
necessary, the setting changes to "
the initial values are set to the vibration suppression control vibration frequency and
2". When the vibration suppression control tuning is not
0". When this parameter is set to "
0",
vibration suppression control resonance frequency. However, this does not occur when
the servo off.
PB03
For manufacturer setting
Do not change this value by any means.
0
0
PB04 FFC Feed forward gain
This parameter cannot be used in the speed control mode.
%
0
to
Set the feed forward gain. When the setting is 100%, the droop pulses during operation
at constant speed are nearly zero. However, sudden acceleration/deceleration will
increase the overshoot. As a guideline, when the feed forward gain setting is 100%, set
1s or more as the acceleration/deceleration time constant up to the rated speed.
For manufacturer setting
100
PB05
500
Do not change this value by any means.
5 - 12
5. PARAMETERS
Initial
value
Setting
range
No. Symbol
Name and function
Unit
PB06 GD2 Ratio of load inertia moment to servo motor inertia moment
Used to set the ratio of the load inertia moment to the servo motor shaft inertia moment.
When auto tuning mode 1 and interpolation mode is selected, the result of auto tuning is
automatically used.
7.0
Multiplier
0
to
(
1)
300.0
(Refer to section 6.1.1)
In this case, it varies between 0 and 100.0.
When parameter No.PA08 is set to "
manually.
2" or "
3", this parameter can be set
PB07 PG1 Model loop gain
Set the response gain up to the target position.
24
37
rad/s
rad/s
1
to
Increase the gain to improve track ability in response to the command.
2000
When auto turning mode 1,2 is selected, the result of auto turning is automatically used.
When parameter No.PA08 is set to "
manually.
1" or "
3", this parameter can be set
PB08 PG2 Position loop gain
1
to
This parameter cannot be used in the speed control mode.
Used to set the gain of the position loop.
1000
Set this parameter to increase the position response to level load disturbance. Higher
setting increases the response level but is liable to generate vibration and/or noise.
When auto tuning mode 1,2 and interpolation mode is selected, the result of auto tuning
is automatically used.
When parameter No.PA08 is set to "
PB09 VG2 Speed loop gain
3", this parameter can be set manually.
823
33.7
980
rad/s
20
to
Set this parameter when vibration occurs on machines of low rigidity or large backlash.
Higher setting increases the response level but is liable to generate vibration and/or
noise.
50000
When auto tuning mode 1 2, manual mode and interpolation mode is selected, the
result of auto tuning is automatically used.
When parameter No.PA08 is set to "
Speed integral compensation
3", this parameter can be set manually.
PB10 VIC
ms
0.1
to
Used to set the integral time constant of the speed loop.
Lower setting increases the response level but is liable to generate vibration and/or
noise.
1000.0
When auto tuning mode 1 2 and interpolation mode is selected, the result of auto
tuning is automatically used.
When parameter No.PA08 is set to "
3", this parameter can be set manually.
PB11 VDC Speed differential compensation
Used to set the differential compensation.
0
to
When parameter No.PB24 is set to "
3
", this parameter is made valid. When
1000
parameter No.PA08 is set to "
controller.
0
", this parameter is made valid by instructions of
PB12
For manufacturer setting
0
Do not change this value by any means.
PB13 NH1 Machine resonance suppression filter 1
Set the notch frequency of the machine resonance suppression filter 1.
4500
Hz
100
to
Setting parameter No.PB01 (filter tuning mode 1) to "
1" automatically changes
4500
this parameter.
When the parameter No.PB01 setting is "
ignored.
0", the setting of this parameter is
5 - 13
5. PARAMETERS
Initial
value
Setting
range
No. Symbol
Name and function
Unit
PB14 NHQ1 Notch shape selection 1
0000h
Refer to
Name
Used to selection the machine resonance suppression filter 1.
and
0
0
function
column.
Notch depth selection
Setting value Depth
Gain
40dB
14dB
8dB
0
1
2
3
Deep
to
Shallow
4dB
Notch width
Setting value Width
0
1
2
3
Standard
2
3
4
5
to
Wide
Setting parameter No.PB01 (filter tuning mode 1) to "
this parameter.
1" automatically changes
When the parameter No.PB01 setting is "
ignored.
0", the setting of this parameter is
100
to
PB15 NH2 Machine resonance suppression filter 2
4500
Hz
Set the notch frequency of the machine resonance suppression filter 2.
4500
Set parameter No.PB16 (notch shape selection 2) to "
valid.
1" to make this parameter
PB16 NHQ2 Notch shape selection 2
0000h
Refer to
Name
Select the shape of the machine resonance suppression filter 2.
and
0
function
column.
Machine resonance suppression filter 2 selection
0: Invalid
1: Valid
Notch depth selection
Setting value Depth
Gain
40dB
14dB
8dB
0
1
2
3
Deep
to
Shallow
4dB
Notch width
Setting value Width
0
1
2
3
Standard
2
3
4
5
to
Wide
PB17
Automatic setting parameter
The value of this parameter is set according to a set value of parameter No.PB06 (Ratio
of load inertia moment to servo motor inertia moment).
5 - 14
5. PARAMETERS
Initial
value
Setting
range
No. Symbol
Name and function
Unit
PB18 LPF Low-pass filter setting
Set the low-pass filter.
3141
rad/s
100
to
Setting parameter No.PB23 (low-pass filter selection) to "
changes this parameter.
0
" automatically
18000
When parameter No.PB23 is set to "
1
", this parameter can be set manually.
PB19 VRF1 Vibration suppression control vibration frequency setting
This parameter cannot be used in the speed control mode.
100.0
Hz
0.1
to
Set the vibration frequency for vibration suppression control to suppress low-frequency
machine vibration, such as enclosure vibration. (Refer to section 7.4.(4))
100.0
Setting parameter No.PB02 (vibration suppression control tuning mode) to "
automatically changes this parameter. When parameter No.PB02 is set to "
this parameter can be set manually.
1"
2",
PB20 VRF2 Vibration suppression control resonance frequency setting
This parameter cannot be used in the speed control mode.
100.0
Hz
0.1
to
Set the resonance frequency for vibration suppression control to suppress low-
100.0
frequency machine vibration, such as enclosure vibration. (Refer to section 7.4.(4))
Setting parameter No.PB02 (vibration suppression control tuning mode) to "
1"
2",
automatically changes this parameter. When parameter No.PB02 is set to "
this parameter can be set manually.
PB21
PB22
For manufacturer setting
0.00
0.00
Do not change this value by any means.
PB23 VFBF Low-pass filter selection
Select the low-pass filter.
0000h
Refer to
Name
and
0 0
0
function
column.
Low-pass filter selection
0: Automatic setting
1: Manual setting (parameter No.PB18 setting)
When automatic setting has been selected, select the filter that has the band width
VG2 10
close to the one calculated with
[rad/s]
1 + GD2
PB24 *MVS Slight vibration suppression control selection
Select the slight vibration suppression control and PI-PID change.
When parameter No.PA08 (auto tuning mode) is set to " 3", this parameter is
0000h
Refer to
Name
and
made valid. (Slight vibration suppression control cannot be used in the speed control
mode.)
function
column.
0 0
Slight vibration suppression control selection
0: Invalid
1: Valid
PI-PID control switch over selection
0: PI control is valid. (Switching to PID
control is possible with instructions of
controller.)
3: PID control is always valid.
PB25
For manufacturer setting
0000h
Do not change this value by any means.
5 - 15
5. PARAMETERS
Initial
value
Setting
range
No. Symbol
Name and function
Unit
PB26 *CDP Gain changing selection
0000h
Refer to
Name
Select the gain changing condition. (Refer to section 7.6.)
and
0 0
function
column.
Gain changing selection
Under any of the following conditions, the gains
change on the basis of the parameter No.PB29 to
PB32 settings.
0: Invalid
1: Control instructions from a controller.
2: Command frequency (Parameter No.PB27
setting)
3: Droop pulse value (Parameter No.PB27 setting)
4: Servo motor speed (Parameter No.PB27 setting)
Gain changing condition
0: Valid at more than condition (For control
instructions from a controller, valid with ON)
1: Valid at less than condition (For control
instructions from a controller, valid with OFF)
PB27 CDL Gain changing condition
10
kpps
pulse
r/min
0
to
Used to set the value of gain changing condition (command frequency, droop pulses,
servo motor speed) selected in parameter No.PB26.The set value unit changes with the
changing condition item. (Refer to section 7.6.)
9999
PB28 CDT Gain changing time constant
1
ms
0
to
Used to set the time constant at which the gains will change in response to the
conditions set in parameters No.PB26 and PB27. (Refer to section 7.6.)
PB29 GD2B Gain changing ratio of load inertia moment to servo motor inertia moment
Used to set the ratio of load inertia moment to servo motor inertia moment when gain
changing is valid.
100
0
7.0
Multiplier
(
1)
to
300.0
This parameter is made valid when the auto tuning is invalid (parameter No.PA08:
3).
PB30 PG2B Gain changing position loop gain
37
rad/s
1
to
This parameter cannot be used in the speed control mode.
Set the position loop gain when the gain changing is valid.
This parameter is made valid when the auto tuning is invalid (parameter No.PA08:
3).
2000
PB31 VG2B Gain changing speed loop gain
823
33.7
rad/s
ms
20
to
Set the speed loop gain when the gain changing is valid.
This parameter is made valid when the auto tuning is invalid (parameter No.PA08:
3).
20000
PB32 VICB Gain changing speed integral compensation
Set the speed integral compensation when the gain changing is valid.
This parameter is made valid when the auto tuning is invalid (parameter No.PA08:
3).
0.1
to
5000.0
PB33 VRF1B Gain changing vibration suppression control vibration frequency setting
This parameter cannot be used in the speed control mode.
Set the vibration frequency for vibration suppression control when the gain changing is
100.0
Hz
0.1
to
100.0
valid. This parameter is made valid when the parameter No.PB02 setting is "
and the parameter No.PB26 setting is " 1".
2"
When using the vibration suppression control gain changing, always execute the
changing after the servo motor has stopped.
5 - 16
5. PARAMETERS
Initial
value
Setting
range
No. Symbol
Name and function
Unit
Hz
PB34 VRF2B Gain changing vibration suppression control resonance frequency setting
This parameter cannot be used in the speed control mode.
100.0
0.1
to
Set the resonance frequency for vibration suppression control when the gain changing is
100.0
valid. This parameter is made valid when the parameter No.PB02 setting is "
and the parameter No.PB26 setting is " 1".
2"
When using the vibration suppression control gain changing, always execute the
changing after the servo motor has stopped.
For manufacturer setting
PB35
PB36
PB37
PB38
PB39
PB40
PB41
PB42
PB43
PB44
PB45
0.00
0.00
100
Do not change this value by any means.
0.0
0.0
0.0
1125
1125
0004h
0.0
0000h
5 - 17
5. PARAMETERS
5.3 Extension setting parameters (No.PC
POINT
)
Parameter whose symbol is preceded by * is made valid with the following
conditions.
* : Set the parameter value, switch power off once after setting, and then
switch it on again, or perform the controller reset.
**: Set the parameter value, switch power off once, and then switch it on
again.
5.3.1 Parameter list
No. Symbol
Name
Initial value
Unit
rev
ms
PC01 ERZ Error excessive alarm level
PC02 MBR Electromagnetic brake sequence output
PC03 *ENRS Encoder output pulses selection
PC04 **COP1 Function selection C-1
PC05 **COP2 Function selection C-2
PC06 *COP3 Function selection C-3
PC07 ZSP Zero speed
3
0
0000h
0000h
0000h
0000h
50
r/min
PC08
For manufacturer setting
0
PC09 MOD1 Analog monitor 1 output
PC10 MOD2 Analog monitor 2 output
PC11 MO1 Analog monitor 1 offset
PC12 MO2 Analog monitor 2 offset
0000h
0001h
0
mV
mV
0
PC13 MOSDL Analog monitor feedback position output standard data Low
PC14 MOSDH Analog monitor feedback position output standard data High
0
pulse
10000
pulse
0
PC15
PC16
For manufacturer setting
0
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
PC17 **COP4 Function selection C-4
PC18
PC19
PC20
For manufacturer setting
PC21 *BPS Alarm history clear
PC22
PC23
PC24
PC25
PC26
PC27
PC28
PC29
PC30
PC31
PC32
For manufacturer setting
5 - 18
5. PARAMETERS
5.3.2 List of details
Initial
value
Setting
range
No. Symbol
Name and function
Unit
PC01 ERZ Error excessive alarm level
3
rev
1
to
(Note 2) This parameter cannot be used in the speed control mode.
Set error excessive alarm level with rotation amount of servo motor.
Note 1. Setting can be changed in parameter No.PC06.
(Note 1)
200
2. For a servo amplifier with software version of B2 or later, reactivating the power
supply to enable the setting value is not necessary. For a servo amplifier with
software version of earlier than B2, reactivating the power supply is required to
enable the setting value.
PC02 MBR Electromagnetic brake sequence output
0
ms
0
Used to set the delay time (Tb) between electronic brake interlock (MBR) and the base
drive circuit is shut-off.
to
1000
PC03 *ENRS Encoder output pulse selection
0000h
Refer to
Name
and
Use to select the, encoder output pulse direction and encoder output pulse setting.
0 0
function
column.
Encoder output pulse phase changing
Changes the phases of A, B-phase encoder pulses output .
Servo motor rotation direction
Set value
CCW
CW
A-phase
B-phase
A-phase
B-phase
0
1
A-phase
B-phase
A-phase
B-phase
Encoder output pulse setting selection (refer to parameter No.PA15)
0: Output pulse designation
1: Division ratio setting
PC04 **COP1 Function selection C-1
Select the encoder cable communication system selection.
0000h
Refer to
Name
and
0 0 0
function
column.
Encoder cable communication system selection
0: Two-wire type
1: Four-wire type
The following encoder cables are of 4-wire type.
MR-EKCBL30M-L
MR-EKCBL30M-H
MR-EKCBL40M-H
MR-EKCBL50M-H
The other encoder cables are all of 2-wire type.
Incorrect setting will result in an encoder alarm 1 (16) or encoder
alarm 2 (20).
PC05 **COP2 Function selection C-2
0000h
Refer to
Name
Motor-less operation select.
and
0 0 0
function
column.
Motor-less operation select.
0: Valid
1: Invalid
5 - 19
5. PARAMETERS
Initial
value
Setting
range
No. Symbol
Name and function
Unit
PC06 *COP3
0000h
Refer to
Name
and
Function selection C-3
Select the error excessive alarm level setting for parameter No.PC01.
function
column.
0 0 0
Error excessive alarm level setting selection
0: 1
[rev]unit
1: 0.1 [rev]unit
2: 0.01 [rev]unit
3: 0.001[rev]unit
This parameter is available to software version B1 or later.
PC07 ZSP Zero speed
Used to set the output range of the zero speed (ZSP).
50
r/min
0
to
Zero speed signal detection has hysteresis width of 20r/min (Refer to section 3.5 (2) (b))
For manufacturer setting
10000
PC08
0
Do not change this value by any means.
Analog monitor 1 output
Used to selection the signal provided to the analog monitor 1 (MO1) output. (Refer to
section 5.3.3)
PC09 MOD1
0000h
Refer to
Name
and
function
column.
0 0 0
Analog monitor 1 (MO1) output selection
Setting
Item
Servo motor speed ( 8V/max. speed)
0
1
2
3
4
5
6
7
8
9
A
B
C
D
Torque ( 8V/max. torque) (Note 2)
Servo motor speed (+8V/max. speed)
Torque (+8V/max. torque) (Note 2)
Current command ( 8V/max. current command)
Speed command ( 8V/max. current command)
Droop pulses ( 10V/100 pulses) (Note 1)
Droop pulses ( 10V/1000 pulses) (Note 1)
Droop pulses ( 10V/10000 pulses) (Note 1)
Droop pulses ( 10V/100000 pulses) (Note 1)
Feedback position ( 10V/1 Mpulses) (Note 1, 3)
Feedback position ( 10V/10 Mpulses) (Note 1, 3)
Feedback position ( 10V/100 Mpulses) (Note 1, 3)
Bus voltage ( 8V/400V)(Note 4)
Note 1. Encoder pulse unit.
2. 8V is outputted at the maximum torque.
3. It can be used by the absolute position detection system.
4. For 400V class servo amplifier, the bus voltage becomes 8V/800V.
Analog monitor 2 output
Used to selection the signal provided to the analog monitor 2 (MO2) output. (Refer to
section 5.3.3)
PC10 MOD2
0001h
Refer to
Name
and
function
column.
0 0 0
Select the analog monitor 2 (MO2) output
The settings are the same as those of parameter No.PC09.
PC11 MO1 Analog monitor 1 offset
Used to set the offset voltage of the analog monitor 1 (MO1) output.
0
mV
-999
to
999
5 - 20
5. PARAMETERS
Initial
value
Setting
range
No. Symbol
Name and function
Unit
mV
PC12 MO2
Analog monitor 2 offset
0
-999
to
Used to set the offset voltage of the analog monitor 2 (MO2) output.
999
-9999
to
PC13 MOSDL Analog monitor feedback position output standard data Low
0
pulse
Used to set the standard position of feedback output with analog monitor 1 (M01) or 2
(M02).
9999
For this parameter, the lower-order four digits of standard position in decimal numbers
are set.
PC14 MOSDH Analog monitor feedback position output standard data High
0
10000
pulse
-9999
to
Used to set the standard position of feedback output with analog monitor 1 (M01) or 2
(M02).
9999
For this parameter, the higher-order four digits of standard position in decimal numbers
are set.
PC15
PC16
For manufacturer setting
0
Do not change this value by any means.
0000h
0000h
PC17 **COP4 Function Selection C-4
Home position setting condition in the absolute position detection system can be
Refer to
Name
selected.
and
function
column.
0 0 0
Selection of home position setting condition
0: Need to pass motor Z-phase after the power
supply is switched on.
1: Not need to pass motor Z-phase after the power
supply is switched on.
PC18
PC19
PC20
For manufacturer setting
0000h
0000h
0000h
0000h
Do not change this value by any means.
PC21 *BPS Alarm history clear
Used to clear the alarm history.
Refer to
Name
and
0 0 0
function
column.
Alarm history clear
0: Invalid
1: Valid
When alarm history clear is made valid, the alarm
history is cleared at next power-on.
After the alarm history is cleared, the setting is
automatically made invalid (reset to 0).
PC22
PC23
PC24
PC25
PC26
PC27
PC28
PC29
PC30
PC31
PC32
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
For manufacturer setting
Do not change this value by any means.
5 - 21
5. PARAMETERS
5.3.3 Analog monitor
The servo status can be output to two channels in terms of voltage. The servo status can be monitored using
an ammeter.
(1) Setting
Change the following digits of parameter No.PC09, PC10.
Parameter No.PC09
0 0 0
Analog monitor (MO1) output selection
(Signal output to across MO1-LG)
Parameter No.PC10
0 0 0
Analog monitor (MO2) output selection
(Signal output to across MO2-LG)
Parameters No.PC11 and PC12 can be used to set the offset voltages to the analog output voltages. The
setting range is between 999 and 999mV.
Parameter No.
PC11
Description
Setting range [mV]
999 to 999
Used to set the offset voltage for the analog monitor 1 (MO1).
Used to set the offset voltage for the analog monitor 2 (MO2).
PC12
(2) Set content
The servo amplifier is factory-set to output the servo motor speed to analog monitor 1 (MO1) and the torque
to analog monitor (MO2). The setting can be changed as listed below by changing the parameter No.PC14
and PC12 value.
Refer to (3) for the measurement point.
Setting
0
Output item
Description
Setting
1
Output item
Description
Driving in CCW
direction
Servo motor speed
Torque (Note 3)
CCW direction
8[V]
8[V]
Max. speed
Max. torque
0
0
Max. speed
Max. torque
-8[V]
-8[V]
Driving in CW
direction
CW direction
2
4
Servo motor speed
Current command
3
5
Torque (Note 3)
Driving in CW
direction
Driving in CCW
direction
8[V]
8[V]
CW direction
CCW direction
Max. speed
0
Max. speed
Max. torque
Max. speed
0
Max. torque
Speed command
CCW direction
8[V]
CCW direction
8[V]
Max. current command
(Max. torque command)
0
0
Max. speed
Max. current command
(Max. torque command)
-8[V]
CW direction
-8[V]
CW direction
5 - 22
5. PARAMETERS
Setting
6
Output item
Description
CCW direction
Setting
7
Output item
Description
CCW direction
Droop pulses (Note 1)
( 10V/100 pulses)
Droop pulses (Note 1)
( 10V/1000 pulses)
10[V]
10[V]
100[pulse]
1000[pulse]
0
0
100[pulse]
1000[pulse]
-10[V]
-10[V]
CW direction
10[V]
CW direction
10[V]
8
A
C
Droop pulses
(Note 1)
CCW direction
9
B
D
Droop pulses
(Note 1)
CCW direction
( 10V/10000 pulses)
( 10V/100000 pulses)
10000[pulse]
100000[pulse]
0
0
10000[pulse]
100000[pulse]
-10[V]
-10[V]
CW direction
10[V]
CW direction
10[V]
Feedback position
(Note 1,2)
CCW direction
Feedback position
(Note 1,2)
CCW direction
( 10V/1 Mpulses)
( 10V/10 Mpulses)
1M[pulse]
10M[pulse]
0
0
1M[pulse]
10M[pulse]
-10[V]
-10[V]
CW direction
10[V]
CW direction
8[V]
Feedback position
(Note 1,2)
CCW direction
Bus voltage (Note 4)
( 10V/100 Mpulses)
100M[pulse]
0
100M[pulse]
0
400[V]
-10[V]
CW direction
Note 1. Encoder pulse unit.
2. Available in position control mode
3. Outputs 8V at the maximum torque.
4. For 400V class servo amplifier, the bus voltage becomes 8V/800V.
5 - 23
5. PARAMETERS
(3) Analog monitor block diagram
Speed
command
Current
command
Droop pulse
Bus voltage
Speed
command
Position
command
received
from a
Differ-
ential
Current encoder
M
Position
control
Current
control
Speed
control
Servo Motor
Encoder
PWM
controller
Current feedback
Differ-
ential
Position feedback
data returned to
a controller
Position feedback
Feedback position
standard position (Note)
Servo Motor
speed
Torque
Feedback
position
Note. The feedback position is output based on the position data passed between servo system controller and servo amplifier. The
parameter number No.PC13/PC14 can set up the standard position of feedback position that is output to analog monitor in order
to adjust the output range of feedback position. The setting range is between 99999999 and 99999999 pulses.
Standard position of feedback position = Parameter No.PC14 setting value 10000 + Parameter No.PC13 setting value
Parameter No.
PC13
Description
Setting range
Sets the lower-order four digits of the standard position
of feedback position
9999 to 9999 [pulse]
Sets the higher-order four digits of the standard position
of feedback position
9999 to 9999 [10000pulses]
PC14
5.3.4 Alarm history clear
The servo amplifier stores one current alarm and five past alarms from when its power is switched on first. To
control alarms which will occur during operation, clear the alarm history using parameter No.PC21 before
starting operation.
Clearing the alarm history automatically returns to "
0 ".
After setting, this parameter is made valid by switch power from OFF to ON.
Parameter No.PC21
0
0 0
Alarm history clear
0: Invalid (not cleared)
1: Valid (cleared)
5 - 24
5. PARAMETERS
5.4 I/O setting parameters (No.PD
POINT
)
Parameter whose symbol is preceded by * is made valid with the following
conditions.
* : Set the parameter value, switch power off once after setting, and then
switch it on again, or perform the controller reset.
5.4.1 Parameter list
No. Symbol
Name
Initial value
0000h
0000h
0000h
0000h
0000h
0000h
0005h
0004h
0003h
0000h
0004h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
Unit
PD01
For manufacturer setting
PD02
PD03
PD04
PD05
PD06
PD07 *DO1 Output signal device selection 1 (CN3-13)
PD08 *DO2 Output signal device selection 2 (CN3-9)
PD09 *DO3 Output signal device selection 3 (CN3-15)
PD10
PD11
PD12
PD13
For manufacturer setting
PD14 *DOP3 Function selection D-3
For manufacturer setting
PD15
PD16
PD17
PD18
PD19
PD20
PD21
PD22
PD23
PD24
PD25
PD26
PD27
PD28
PD29
PD30
PD31
PD32
5 - 25
5. PARAMETERS
5.4.2 List of details
Initial
value
Setting
range
No. Symbol
Name and function
Unit
PD01
PD02
PD03
PD04
PD05
PD06
For manufacturer setting
Do not change this value by any means.
0000h
0000h
0000h
0000h
0000h
0000h
PD07 *DO1 Output signal device selection 1 (CN3-13)
Any input signal can be assigned to the CN3-13 pin.
0005h
Refer to
Name
and
0 0
function
column.
Select the output device of the CN3-13 pin.
The devices that can be assigned in each control mode are those that have the symbols
indicated in the following table.
Setting
00
Device
Setting
0A
Device
Always OFF
For manufacturer
setting (Note 3)
RD
Always OFF (Note 2)
For manufacturer
setting (Note 3)
ZSP
For manufacturer
setting (Note 3)
For manufacturer
setting (Note 3)
CDPS
For manufacturer
setting (Note 3)
ABSV (Note 1)
For manufacturer
setting (Note 3)
For manufacturer
setting (Note 3)
01
02
03
0B
0C
0D
ALM
04
05
06
07
08
INP (Note 1)
MBR
0E
0F
DB
10
TLC
11
WNG
12 to 1F
09
BWNG
20 to 3F
Note 1. It becomes always OFF in speed control mode.
2. It becomes SA in speed control mode.
3. For manufacturer setting
Never change this setting.
Output signal device selection 2 (CN3-9)
PD08 *DO2
0004h
Refer to
Name
Any input signal can be assigned to the CN3-9 pin.
The devices that can be assigned and the setting method are the same as in parameter
No.PD07.
and
function
column.
0 0 0
Select the output device of the CN3-9 pin.
PD09 *DO3 Output signal device selection 3 (CN3-15)
Any input signal can be assigned to the CN3-15 pin.
The devices that can be assigned and the setting method are the same as in parameter
No.PD07.
0003h
Refer to
Name
and
function
column.
0 0 0
Select the output device of the CN3-15 pin.
5 - 26
5. PARAMETERS
Initial
value
Setting
range
No. Symbol
Name and function
Unit
PD10
PD11
PD12
PD13
For manufacturer setting
Do not change this value by any means.
0000h
0004h
0000h
0000h
0000h
PD14 *DOP3 Function selection D-3
Set the ALM output signal at warning occurrence.
Refer to
Name
and
0 0
0
function
column.
Selection of output device at warning occurrence
Select the warning (WNG) and trouble (ALM) output status
at warning occurrence.
Output of Servo amplifier
Setting
0
(Note) Device status
Warning occurrence
Warning occurrence
1
0
1
0
WNG
ALM
1
0
1
0
WNG
ALM
1
Note. 0: off
1: on
PD15
PD16
PD17
PD18
PD19
PD20
PD21
PD22
PD23
PD24
PD25
PD26
PD27
PD28
PD29
PD30
PD31
PD32
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
For manufacturer setting
Do not change this value by any means.
5 - 27
5. PARAMETERS
MEMO
5 - 28
6. GENERAL GAIN ADJUSTMENT
6. GENERAL GAIN ADJUSTMENT
6.1 Different adjustment methods
6.1.1 Adjustment on a single servo amplifier
The gain adjustment in this section can be made on a single servo amplifier. For gain adjustment, first execute
auto tuning mode 1. If you are not satisfied with the results, execute auto tuning mode 2 and manual mode in
this order.
(1) Gain adjustment mode explanation
Parameter
Estimation of load inertia
moment ratio
Automatically set
parameters
Gain adjustment mode
Manually set parameters
No.PA08 setting
Auto tuning mode 1
(initial value)
0001
Always estimated
GD2 (parameter No.PB06)
PG2 (parameter No.PB08)
PG1 (parameter No.PB07)
VG2 (parameter No.PB09)
VIC (parameter No.PB10)
PG2 (parameter No.PB08)
PG1 (parameter No.PB07)
VG2 (parameter No.PB09)
VIC (parameter No.PB10)
Response level setting of
parameter No.2
Auto tuning mode 2
Manual mode
0002
0003
0000
Fixed to parameter No.
PB06 value
GD2 (parameter No.PB06)
Response level setting of
parameter No.PA09
PG1 (parameter No.PB07)
GD2 (parameter No.PB06)
VG2 (parameter No.PB09)
VIC (parameter No.PB10)
PG1 (parameter No.PB07)
Interpolation mode
Always estimated
GD2 (parameter No.PB06)
PG2 (parameter No.PB08)
VG2 (parameter No.PB09)
VIC (parameter No.PB10)
6 - 1
6. GENERAL GAIN ADJUSTMENT
(2) Adjustment sequence and mode usage
START
Usage
Yes
Interpolation
made for 2 or more
axes?
Used when you want to
match the position gain (PG1)
between 2 or more axes.
Normally not used for other
purposes.
Interpolation mode
Operation
No
Allows adjustment by merely
changing the response level
setting.
Auto tuning mode 1
Operation
First use this mode to make
adjustment.
Yes
No
OK?
OK?
Yes
Used when the conditions of
auto tuning mode 1 are not
met and the load inertia
moment ratio could not be
estimated properly, for
example.
No
Auto tuning mode 2
Operation
Yes
OK?
No
You can adjust all gains
manually when you want to
do fast settling or the like.
Manual mode
END
6.1.2 Adjustment using MR Configurator
This section gives the functions and adjustment that may be performed by using the servo amplifier with the
MR Configurator which operates on a personal computer.
Function
Description
Adjustment
Machine analyzer
With the machine and servo motor coupled,
the characteristic of the mechanical system
can be measured by giving a random
vibration command from the personal
computer to the servo and measuring the
machine response.
You can grasp the machine resonance frequency and
determine the notch frequency of the machine resonance
suppression filter.
You can automatically set the optimum gains in response to
the machine characteristic. This simple adjustment is
suitable for a machine which has large machine resonance
and does not require much settling time.
Gain search
Executing gain search under to-and-fro
positioning command measures settling
characteristic while simultaneously
You can automatically set gains which make positioning
settling time shortest.
changing gains, and automatically searches
for gains which make settling time shortest.
Response at positioning settling of a
machine can be simulated from machine
analyzer results on personal computer.
Machine simulation
You can optimize gain adjustment and command pattern on
personal computer.
6 - 2
6. GENERAL GAIN ADJUSTMENT
6.2 Auto tuning
6.2.1 Auto tuning mode
The servo amplifier has a real-time auto tuning function which estimates the machine characteristic (load inertia
moment ratio) in real time and automatically sets the optimum gains according to that value. This function
permits ease of gain adjustment of the servo amplifier.
(1) Auto tuning mode 1
The servo amplifier is factory-set to the auto tuning mode 1.
In this mode, the load inertia moment ratio of a machine is always estimated to set the optimum gains
automatically.
The following parameters are automatically adjusted in the auto tuning mode 1.
Parameter No.
PB06
Abbreviation
GD2
Name
Ratio of load inertia moment to servo motor inertia moment
Model loop gain
PB07
PG1
PB08
PG2
Position loop gain
PB09
VG2
Speed loop gain
PB10
VIC
Speed integral compensation
POINT
The auto tuning mode 1 may not be performed properly if the following
conditions are not satisfied.
Time to reach 2000r/min is the acceleration/deceleration time constant of 5s or
less.
Speed is 150r/min or higher.
The ratio of load inertia moment to servo motor inertia moment is 100 times or
less.
The acceleration/deceleration torque is 10% or more of the rated torque.
Under operating conditions which will impose sudden disturbance torque
during acceleration/deceleration or on a machine which is extremely loose,
auto tuning may not function properly, either. In such cases, use the auto
tuning mode 2 or manual mode to make gain adjustment.
(2) Auto tuning mode 2
Use the auto tuning mode 2 when proper gain adjustment cannot be made by auto tuning mode 1. Since
the load inertia moment ratio is not estimated in this mode, set the value of a correct load inertia moment
ratio (parameter No.PB06).
The following parameters are automatically adjusted in the auto tuning mode 2.
Parameter No.
PB07
Abbreviation
PG1
Name
Model loop gain
PB08
PG2
Position loop gain
PB09
VG2
Speed loop gain
PB10
VIC
Speed integral compensation
6 - 3
6. GENERAL GAIN ADJUSTMENT
6.2.2 Auto tuning mode operation
The block diagram of real-time auto tuning is shown below.
Load inertia
moment
Automatic setting
Encoder
Loop gains
Command
Current
control
Servo
motor
PG1,VG1
PG2,VG2,VIC
Current feedback
Real-time auto
tuning section
Position/speed
feedback
Set 0 or 1 to turn on.
Load inertia
moment ratio
estimation section
Gain
table
Switch
Speed feedback
Parameter No.PB06
Load inertia moment
Parameter No.PA08 Parameter No.PA09
0 0 0
ratio estimation value
Response
setting
Gain adjustment mode
selection
When a servo motor is accelerated/decelerated, the load inertia moment ratio estimation section always
estimates the load inertia moment ratio from the current and speed of the servo motor. The results of estimation
are written to parameter No.PB06 (the ratio of load inertia moment to servo motor). These results can be
confirmed on the status display screen of the MR Configurator.
If the value of the load inertia moment ratio is already known or if estimation cannot be made properly, chose
the "auto tuning mode 2" (parameter No.PA08: 0002) to stop the estimation of the load inertia moment ratio
(Switch in above diagram turned off), and set the load inertia moment ratio (parameter No.34) manually.
From the preset load inertia moment ratio (parameter No.PB06) value and response level (parameter
No.PA09), the optimum loop gains are automatically set on the basis of the internal gain tale.
The auto tuning results are saved in the EEP-ROM of the servo amplifier every 60 minutes since power-on. At
power-on, auto tuning is performed with the value of each loop gain saved in the EEP-ROM being used as an
initial value.
POINT
If sudden disturbance torque is imposed during operation, the estimation of
the inertia moment ratio may malfunction temporarily. In such a case, choose
the "auto tuning mode 2" (parameter No.PA08: 0002) and set the correct load
inertia moment ratio in parameter No.PB06.
When any of the auto tuning mode 1 and auto tuning mode settings is
changed to the manual mode 2 setting, the current loop gains and load inertia
moment ratio estimation value are saved in the EEP-ROM.
6 - 4
6. GENERAL GAIN ADJUSTMENT
6.2.3 Adjustment procedure by auto tuning
Since auto tuning is made valid before shipment from the factory, simply running the servo motor automatically
sets the optimum gains that match the machine. Merely changing the response level setting value as required
completes the adjustment. The adjustment procedure is as follows.
Auto tuning adjustment
Acceleration/deceleration repeated
Yes
Load inertia moment ratio
estimation value stable?
No
Auto tuning
conditions not satisfied.
(Estimation of load inertia
moment ratio is difficult)
No
Yes
Choose the auto tuning mode 2
(parameter No.PA08 : 0002) and
set the load inertia moment ratio
(parameter No.PB06) manually.
Adjust response level setting
so that desired response is
achieved on vibration-free level.
Acceleration/deceleration repeated
Requested
No
performance satisfied?
Yes
END
To manual mode
6 - 5
6. GENERAL GAIN ADJUSTMENT
6.2.4 Response level setting in auto tuning mode
Set the response (The first digit of parameter No.PA09) of the whole servo system. As the response level
setting is increased, the track ability and settling time for a command decreases, but a too high response level
will generate vibration. Hence, make setting until desired response is obtained within the vibration-free range.
If the response level setting cannot be increased up to the desired response because of machine resonance
beyond 100Hz, filter tuning mode (parameter No.PB01) or machine resonance suppression filter (parameter
No.PB13 to PB16) may be used to suppress machine resonance. Suppressing machine resonance may allow
the response level setting to increase. Refer to section 7.3 for filter tuning mode and machine resonance
suppression filter.
Setting of parameter No.PA09
Machine characteristic
Response level setting
Machine resonance
frequency guideline
Machine rigidity
Low
Guideline of corresponding machine
1
10.0
11.3
2
3
12.7
4
14.3
5
16.1
6
18.1
7
20.4
8
23.0
9
25.9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
29.2
32.9
Large conveyor
37.0
41.7
Arm robot
47.0
52.9
General machine
tool conveyor
Middle
59.6
67.1
Precision
working
machine
75.6
85.2
95.9
Inserter
Mounter
Bonder
108.0
121.7
137.1
154.4
173.9
195.9
220.6
248.5
279.9
315.3
355.1
400.0
High
6 - 6
6. GENERAL GAIN ADJUSTMENT
6.3 Manual mode 1 (simple manual adjustment)
If you are not satisfied with the adjustment of auto tuning, you can make simple manual adjustment with three
parameters.
POINT
If machine resonance occurs, filter tuning mode (parameter No.PB01) or
machine resonance suppression filter (parameter No.PB13 to PB16) may be
used to suppress machine resonance. (Refer to section 7.3.)
(1) For speed control
(a) Parameters
The following parameters are used for gain adjustment.
Parameter No.
PB06
Abbreviation
GD2
Name
Ratio of load inertia moment to servo motor inertia moment
Model loop gain
PB07
PG1
PB09
VG2
Speed loop gain
PB10
VIC
Speed integral compensation
(b) Adjustment procedure
Step
Operation
Description
1
2
Brief-adjust with auto tuning. Refer to section 6.2.3.
Change the setting of auto tuning to the manual mode (Parameter
No.PA08: 0003).
3
Set an estimated value to the ratio of load inertia moment to servo motor
inertia moment. (If the estimate value with auto tuning is correct, setting
change is not required.)
4
5
6
7
8
Set a slightly smaller value to the model loop gain
Set a slightly larger value to the speed integral compensation.
Increase the speed loop gain within the vibration- and unusual noise-free Increase the speed loop gain.
range, and return slightly if vibration takes place.
Decrease the speed integral compensation within the vibration-free range, Decrease the time constant of the speed
and return slightly if vibration takes place.
integral compensation.
Increase the model loop gain, and return slightly if overshooting takes Increase the model loop gain.
place.
If the gains cannot be increased due to mechanical system resonance or Suppression of machine resonance.
the like and the desired response cannot be achieved, response may be Refer to section 7.2, 7.3.
increased by suppressing resonance with filter tuning mode or machine
resonance suppression filter and then executing steps 2 and 3.
9
While checking the settling characteristic and rotational status, fine-adjust Fine adjustment
each gain.
6 - 7
6. GENERAL GAIN ADJUSTMENT
(c)Adjustment description
1) Speed loop gain (parameter No.PB09)
This parameter determines the response level of the speed control loop. Increasing this value
enhances response but a too high value will make the mechanical system liable to vibrate. The actual
response frequency of the speed loop is as indicated in the following expression.
Speed loop gain setting
Speed loop response
frequency(Hz)
(1 ratio of load inertia moment to servo motor inertia moment)
2
2) Speed integral compensation (VIC: parameter No.PB10)
To eliminate stationary deviation against a command, the speed control loop is under proportional
integral control. For the speed integral compensation, set the time constant of this integral control.
Increasing the setting lowers the response level. However, if the load inertia moment ratio is large or
the mechanical system has any vibratory element, the mechanical system is liable to vibrate unless
the setting is increased to some degree. The guideline is as indicated in the following expression.
2000 to 3000
Speed integral compensation
setting(ms)
Speed loop gain setting/ (1 ratio of load inertia moment to
servo motor inertia moment setting)
3) Model loop gain (PG1: Parameter No.PB07)
This parameter determines the response level to a position command. Increasing the model loop gain
improves track ability to a position command, but a too high value will make overshooting liable to
occur at the time of setting.
Speed loop gain setting
Model loop gain
guideline
1
4
1
8
to
(1 ratio of load inertia moment to servo motor inertia moment)
6 - 8
6. GENERAL GAIN ADJUSTMENT
(2) For position control
(a) Parameters
The following parameters are used for gain adjustment.
Parameter No.
PB06
Abbreviation
GD2
Name
Ratio of load inertia moment to servo motor inertia moment
Model loop gain
PB07
PG1
PB08
PG2
Position loop gain
PB09
VG2
Speed loop gain
PB10
VIC
Speed integral compensation
(b) Adjustment procedure
Step
Operation
Description
1
2
Brief-adjust with auto tuning. Refer to section 6.2.3.
Change the setting of auto tuning to the manual mode (Parameter
No.PA08: 0003).
3
4
Set an estimated value to the ratio of load inertia moment to servo motor
inertia moment. (If the estimate value with auto tuning is correct, setting
change is not required.)
Set a slightly smaller value to the model loop gain and the position loop
gain.
Set a slightly larger value to the speed integral compensation.
Increase the speed loop gain within the vibration- and unusual noise-free Increase the speed loop gain.
range, and return slightly if vibration takes place.
5
6
Decrease the speed integral compensation within the vibration-free range, Decrease the time constant of the speed
and return slightly if vibration takes place.
integral compensation.
7
8
Increase the position loop gain, and return slightly if vibration takes place.
Increase the position loop gain.
Increase the model loop gain, and return slightly if overshooting takes Increase the position loop gain.
place.
9
If the gains cannot be increased due to mechanical system resonance or Suppression of machine resonance.
the like and the desired response cannot be achieved, response may be Refer to section 7.2 7.3.
increased by suppressing resonance with filter tuning mode or machine
resonance suppression filter and then executing steps 3 to 5.
10
While checking the settling characteristic and rotational status, fine-adjust Fine adjustment
each gain.
6 - 9
6. GENERAL GAIN ADJUSTMENT
(c) Adjustment description
1) Speed loop gain (VG2: parameter No.PB09)
This parameter determines the response level of the speed control loop. Increasing this value
enhances response but a too high value will make the mechanical system liable to vibrate. The actual
response frequency of the speed loop is as indicated in the following expression.
Speed loop gain 2 setting
Speed loop response
frequency(Hz)
(1 ratio of load inertia moment to servo motor inertia moment) 2
2) Speed integral compensation (VIC: parameter No.PB10)
To eliminate stationary deviation against a command, the speed control loop is under proportional
integral control. For the speed integral compensation, set the time constant of this integral control.
Increasing the setting lowers the response level. However, if the load inertia moment ratio is large or
the mechanical system has any vibratory element, the mechanical system is liable to vibrate unless
the setting is increased to some degree. The guideline is as indicated in the following expression.
2000 to 3000
Speed integral compensation
setting(ms)
Speed loop gain 2 setting/ (1 ratio of load inertia moment to
servo motor inertia moment 2 setting)
3) Model loop gain (PG1: Parameter No.PB07)
This parameter determines the response level to a position command. Increasing the model loop gain
improves track ability to a position command, but a too high value will make overshooting liable to
occur at the time of setting.
Speed loop gain setting
Model loop gain
guideline
1
4
1
8
to
(1 ratio of load inertia moment to servo motor inertia moment)
4) Model loop gain (PG1: parameter No.PB07)
This parameter determines the response level to a position command. Increasing position loop gain 1
improves track ability to a position command but a too high value will make overshooting liable to
occur at the time of settling.
Speed loop gain 2 setting
Model loop gain
guideline
1
4
1
8
to
(1 ratio of load inertia moment to servo motor inertia moment)
6 - 10
6. GENERAL GAIN ADJUSTMENT
6.4 Interpolation mode
The interpolation mode is used to match the position loop gains of the axes when performing the interpolation
operation of servo motors of two or more axes for an X-Y table or the like. In this mode, manually set the model
loop gain that determines command track ability. Other parameters for gain adjustment are set automatically.
(1) Parameter
(a) Automatically adjusted parameters
The following parameters are automatically adjusted by auto tuning.
Parameter No.
PB06
Abbreviation
GD2
Name
Ratio of load inertia moment to servo motor inertia moment
Position loop gain
PB08
PG2
PB09
VG2
Speed loop gain
PB10
VIC
Speed integral compensation
(b) Manually adjusted parameters
The following parameters are adjustable manually.
Parameter No.
PB07
Abbreviation
PG1
Name
Model loop gain
(2) Adjustment procedure
Step
Operation
Description
1
Set to the auto tuning mode.
Select the auto tuning mode 1.
During operation, increase the response level setting (parameter
No.PA09), and return the setting if vibration occurs.
2
Adjustment in auto tuning mode 1.
3
4
Check the values of model loop gain.
Check the upper setting limits.
Select the interpolation mode.
Set the interpolation mode (parameter No.PA08: 0000).
Set the model loop gain of all the axes to be interpolated to the same
5
6
value. At that time, adjust to the setting value of the axis, which has the Set position loop gain.
smallest model loop gain.
Looking at the interpolation characteristic and rotation status, fine-adjust
Fine adjustment.
the gains and response level setting.
(3) Adjustment description
(a) Model loop gain (parameter No.PB07)
This parameter determines the response level of the position control loop. Increasing model loop gain
improves track ability to a position command but a too high value will make overshooting liable to occur
at the time of settling. The droop pulse value is determined by the following expression.
Rotation speed (r/min)
262144(pulse)
60
Droop pulse value (pulse)
Model loop gain setting
6 - 11
6. GENERAL GAIN ADJUSTMENT
6.5 Differences between MELSERVO-J2-Super and MELSERVO-J3 in auto tuning
To meet higher response demands, the MELSERVO-J3 series has been changed in response level setting
range from the MELSERVO-J2S-Super series. The following table lists comparison of the response level
setting.
MELSERVO-J2-Super
MELSERVO-J3
Guideline for machine resonance
Guideline for machine resonance
Parameter No.9 setting
Parameter No.PA09 setting
frequency [Hz]
frequency [Hz]
10.0
1
2
11.3
3
12.7
1
2
15
20
4
14.3
5
16.1
6
18.1
7
20.4
8
23.0
3
4
25
30
9
25.9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
29.2
32.9
5
35
37.0
41.7
6
7
45
55
47.0
52.9
59.6
8
9
70
85
67.1
75.6
85.2
95.9
A
105
108.0
121.7
137.1
154.4
173.9
195.9
220.6
248.5
279.9
315.3
355.1
400.0
B
C
130
160
D
E
F
200
240
300
Note that because of a slight difference in gain adjustment pattern, response may not be the same if the
resonance frequency is set to the same value.
6 - 12
7. SPECIAL ADJUSTMENT FUNCTIONS
7. SPECIAL ADJUSTMENT FUNCTIONS
POINT
The functions given in this chapter need not be used generally. Use them if
you are not satisfied with the machine status after making adjustment in the
methods in chapter 7.
If a mechanical system has a natural resonance point, increasing the servo system response level may cause
the mechanical system to produce resonance (vibration or unusual noise) at that resonance frequency.
Using the machine resonance suppression filter and adaptive tuning can suppress the resonance of the
mechanical system.
7.1 Function block diagram
Speed
control
Current
command
Parameter
No.PB23
Parameter
No.PB16
Parameter
No.PB01
Low-pass
filter
Servo
motor
Machine resonance
suppression filter
Encoder
Machine resonance
suppression filter 2
Adaptive tuning
Manual setting
1
7.2 Adaptive filter
(1) Function
Adaptive filter (adaptive tuning) is a function in which the servo amplifier detects machine vibration for a
predetermined period of time and sets the filter characteristics automatically to suppress mechanical system
vibration. Since the filter characteristics (frequency, depth) are set automatically, you need not be conscious
of the resonance frequency of a mechanical system.
Machine resonance point
Machine resonance point
Mechanical
system
Mechanical
system
response
level
response
level
Frequency
Frequency
Notch
depth
Notch
depth
Frequency
Frequency
Notch frequency
Notch frequency
When machine resonance is large and frequency is low When machine resonance is small and frequency is high
POINT
The machine resonance frequency which adaptive tuning mode can respond
to is about 100 to 2.25kHz. Adaptive vibration suppression control has no
effect on the resonance frequency outside this range.
Adaptive vibration suppression control may provide no effect on a mechanical
system which has complex resonance characteristics.
7 - 1
7. SPECIAL ADJUSTMENT FUNCTIONS
(2) Parameters
The operation of adaptive tuning mode (parameter No.PB01).
Parameter No.PB01
0 0 0
Filter tuning mode selection
Setting Filter adjustment mode Automatically set parameter
0
1
2
Filter OFF
(Note)
Parameter No.PB13
Parameter No.PB14
Filter tuning mode
Manual mode
Note. Parameter No.PB19 and PB20 are fixed to the initial values.
7 - 2
7. SPECIAL ADJUSTMENT FUNCTIONS
(3) Adaptive tuning mode procedure
Adaptive tuning adjustment
Operation
Yes
Is the target response
reached?
No
Increase the response setting.
No
Has vibration or unusual noise
occurred?
Yes
Execute or re-execute adaptive
tuning. (Set parameter No.PB01 to
"0001".)
Tuning ends automatically after the
predetermined period of time.
(Parameter No.PB01 turns to "0002"
or "0000".)
If assumption fails after tuning is executed at
a large vibration or oscillation, decrease the
response setting temporarily down to the
vibration level and execute again.
Yes
Has vibration or unusual noise
been resolved?
No
Factor
The response has increased to the
machine limit.
Decrease the response until vibration Using the machine analyzer, set the
or unusual noise is resolved. filter manually.
The machine is too complicated to
provide the optimum filter.
End
7 - 3
7. SPECIAL ADJUSTMENT FUNCTIONS
POINT
"Filter OFF" enables a return to the factory-set initial value.
When adaptive tuning is executed, vibration sound increases as an excitation
signal is forcibly applied for several seconds.
When adaptive tuning is executed, machine resonance is detected for a
maximum of 10 seconds and a filter is generated. After filter generation, the
adaptive tuning mode automatically shifts to the manual mode.
Adaptive tuning generates the optimum filter with the currently set control
gains. If vibration occurs when the response setting is increased, execute
adaptive tuning again.
During adaptive tuning, a filter having the best notch depth at the set control
gain is generated. To allow a filter margin against machine resonance,
increase the notch depth in the manual mode.
7.3 Machine resonance suppression filter
(1) Function
The machine resonance suppression filter is a filter function (notch filter) which decreases the gain of the
specific frequency to suppress the resonance of the mechanical system. You can set the gain decreasing
frequency (notch frequency), gain decreasing depth and width.
Machine resonance point
Mechanical
system
response
level
Frequency
Notch width
Notch
depth
Notch depth
Frequency
Notch frequency
You can use the machine resonance suppression filter 1 (parameter No.PB13, PB14) and machine
resonance suppression filter 2 (parameter No.PB15, PB16) to suppress the vibration of two resonance
frequencies. Execution of adaptive tuning in the filter tuning mode automatically adjusts the machine
resonance suppression filter. When adaptive tuning is ON, the adaptive tuning mode shifts to the manual
mode after the predetermined period of time. The manual mode enables manual setting using the machine
resonance suppression filter 1.
Machine resonance point
Mechanical
system
response
level
Frequency
Notch
depth
Frequency
Parameter No.PB01, Parameter No.PB15,
PB13, PB14
PB16
7 - 4
7. SPECIAL ADJUSTMENT FUNCTIONS
(2) Parameters
(a) Machine resonance suppression filter 1 (parameter No.PB13, PB14)
Set the notch frequency, notch depth and notch width of the machine resonance suppression filter 1
(parameter No.PB13, PB14)
When you have made adaptive filter tuning mode (parameter No.PB01) "manual mode", set up the
machine resonance suppression filter 1 becomes effective.
POINT
The machine resonance suppression filter is a delay factor for the servo
system. Hence, vibration may increase if you set a wrong resonance
frequency or a too deep notch.
If the frequency of machine resonance is unknown, decrease the notch
frequency from higher to lower ones in order. The optimum notch frequency is
set at the point where vibration is minimal.
A deeper notch has a higher effect on machine resonance suppression but
increases a phase delay and may increase vibration.
A deeper notch has a higher effect on machine resonance suppression but
increases a phase delay and may increase vibration.
The machine characteristic can be grasped beforehand by the machine
analyzer on the MR Configurator. This allows the required notch frequency
and depth to be determined.
7 - 5
7. SPECIAL ADJUSTMENT FUNCTIONS
7.4 Advanced vibration suppression control
(1) Operation
Vibration suppression control is used to further suppress machine end vibration, such as workpiece end
vibration and base shake. The motor side operation is adjusted for positioning so that the machine does not
shake.
Motor end
Motor end
Machine end
Machine end
t
t
Vibration suppression control OFF
(Normal control)
Vibration suppression control ON
When the advanced vibration suppression control (vibration suppression control tuning mode parameter
No.PB02) is executed, the vibration frequency at machine end can automatically be estimated to suppress
machine end vibration.
In the vibration suppression control tuning mode, this mode shifts to the manual mode after operation is
performed the predetermined number of times. The manual mode enables manual setting using the
vibration suppression control vibration frequency setting (parameter No.PB19) and vibration suppression
control resonance frequency setting (parameter No.PB20).
(2) Parameter
Select the operation of the vibration suppression control tuning mode (parameter No.PB02).
Parameter No.PB02
0 0 0
Vibration suppression control
tuning mode
Setting Vibration suppression control tuning mode
Automatically set parameter
0
1
2
Vibration suppression control OFF
Vibration suppression control tuning mode
(Advanced vibration suppression control)
Manual mode
(Note)
Parameter No.PB19
Parameter No.PB20
Note. Parameter No.PB19 and PB20 are fixed to the initial values.
POINT
The function is made valid when the auto tuning mode (parameter No.PA08)
is the auto tuning mode 2 ("0002") or manual mode ("0003").
The machine resonance frequency supported in the vibration suppression
control tuning mode is 1.0Hz to 100.0Hz. The function is not effective for
vibration outside this range.
Stop the motor before changing the vibration suppression control-related
parameters (parameter No.PB02, PB19, PB20, PB33, PB34). A failure to do
so will cause a shock.
For positioning operation during execution of vibration suppression control
tuning, provide a stop time to ensure a stop after full vibration damping.
Vibration suppression control tuning may not make normal estimation if the
residual vibration at the motor end is small.
Vibration suppression control tuning sets the optimum parameter with the
currently set control gains. When the response setting is increased, set
vibration suppression control tuning again.
7 - 6
7. SPECIAL ADJUSTMENT FUNCTIONS
(3) Vibration suppression control tuning mode procedure
Vibration suppression control
tuning adjustment
Operation
Yes
Is the target response
reached?
No
Increase the response setting.
No
Has vibration of workpiece
end/device increased?
Yes
Stop operation.
Execute or re-execute vibration
suppression control tuning. (Set
parameter No.PB02 to "0001".)
Resume operation.
Tuning ends automatically after
operation is performed the
predetermined number of times.
(Parameter No.PB02 turns to "0002"
or "0000".)
Yes
Has vibration of workpiece
end/device been resolved?
No
Factor
Estimation cannot be made as
Using the machine analyzer or from
machine end vibration waveform, set
the vibration suppression control
manually.
Decrease the response until vibration
of workpiece end/device is resolved.
machine end vibration has not been
transmitted to the motor end.
The response of the model loop gain
has increased to the machine end
vibration frequency (vibration
suppression control limit).
End
7 - 7
7. SPECIAL ADJUSTMENT FUNCTIONS
(4) Vibration suppression control manual mode
Measure work end vibration and device shake with the machine analyzer or external measuring instrument,
and set the vibration suppression control vibration frequency (parameter No.PB19) and vibration
suppression control resonance frequency (parameter No.PB20) to set vibration suppression control
manually.
(a) When a vibration peak can be confirmed using MR Configurator, machine analyzer or external FFT
equipment
Gain characteristic
1Hz
100Hz
Resonance of more
Vibration suppression than 100Hz is not the
Vibration suppression control
vibration frequency
(Anti-resonance frequency)
Parameter No.PB19
control resonance
frequency
target of control.
Parameter No.PB20
Phase
-90deg.
(b) When vibration can be confirmed using monitor signal or external sensor
Motor end vibration
(Droop pulses)
External acceleration pick signal, etc.
Position command frequency
t
t
Vibration suppression control
vibration frequency
Vibration cycle [Hz]
Vibration cycle [Hz]
Vibration suppression control
resonance frequency
Set the same value.
7 - 8
7. SPECIAL ADJUSTMENT FUNCTIONS
POINT
When machine end vibration does not show up in motor end vibration, the
setting of the motor end vibration frequency does not produce an effect.
When the anti-resonance frequency and resonance frequency can be
confirmed using the machine analyzer or external FFT device, do not set the
same value but set different values to improve the vibration suppression
performance.
A vibration suppression control effect is not produced if the relationship
between the model loop gain (parameter No.PB07) value and vibration
frequency is as indicated below. Make setting after decreasing PG1, e.g.
reduce the response setting.
1
(1.5 PG1) vibration frequency
2
7 - 9
7. SPECIAL ADJUSTMENT FUNCTIONS
7.5 Low-pass filter
(1) Function
When a ball screw or the like is used, resonance of high frequency may occur as the response level of the
servo system is increased. To prevent this, the low-pass filter is factory-set to be valid for a torque
command. The filter frequency of this low-pass filter is automatically adjusted to the value in the following
expression.
VG2
1 + GD2
Filter frequency(rad/s)
10
When parameter No.PB23 is set to "
(2) Parameter
1
", manual setting can be made with parameter No.PB18.
Set the operation of the low-pass filter selection (parameter No.PB23.)
Parameter No.PB23
Low-pass filter selection
0: Automatic setting (initial value)
1: Manual setting (parameter No.PB18 setting)
7.6 Gain changing function
This function can change the gains. You can change between gains during rotation and gains during stop or
can use an input device to change gains during operation.
7.6.1 Applications
This function is used when.
(1) You want to increase the gains during servo lock but decrease the gains to reduce noise during rotation.
(2) You want to increase the gains during settling to shorten the stop settling time.
(3) You want to change the gains using an input device to ensure stability of the servo system since the load
inertia moment ratio varies greatly during a stop (e.g. a large load is mounted on a carrier).
7 - 10
7. SPECIAL ADJUSTMENT FUNCTIONS
7.6.2 Function block diagram
The valid loop gains PG2, VG2, VIC and GD2 of the actual loop are changed according to the conditions
selected by gain changing selection CDP (parameter No.PB26) and gain changing condition CDS (parameter
No.PB27).
CDP
Parameter No.PB26
Control
command of
controller
Command pulse
frequency
Droop pulses
Changing
Model speed
Comparator
CDS
Parameter No.PB27
GD2
Parameter No.PB06
Valid
GD2 value
GD2B
Parameter No.PB29
PG2
Parameter No.PB08
Valid
PG2 value
PG2B
Parameter No.PB30
VG2
Parameter No.PB09
Valid
VG2 value
VG2B
Parameter No.PB31
VIC
Parameter No.PB10
Valid
VIC value
VICB
Parameter No.PB32
VRF1
Parameter No.PB19
Valid
VRF1 value
VRF1B
Parameter No.PB33
VRF2
Parameter No.PB20
Valid
VRF2 value
VRF2B
Parameter No.PB34
7 - 11
7. SPECIAL ADJUSTMENT FUNCTIONS
7.6.3 Parameters
When using the gain changing function, always set "
3" in parameter No.PA08 (auto tuning) to choose the
manual mode of the gain adjustment modes. The gain changing function cannot be used in the auto tuning
mode.
Parameter No. Abbreviation
Name
Unit
Description
Multi- Control parameters before changing
plier
Ratio of load inertia moment to
servo motor inertia moment
PB06
GD2
(
1)
Position and speed gains of a model used to set the
response level to a command. Always valid.
PB07
PG1
Model loop gain
rad/s
PB08
PB09
PB10
PG2
VG2
VIC
Position loop gain
rad/s
rad/s
ms
Speed loop gain
Speed integral compensation
Gain changing ratio of load inertia
moment to servo motor inertia
moment
Multi- Used to set the ratio of load inertia moment to servo motor
plier inertia moment after changing.
PB29
GD2B
(
1)
Used to set the value of the after-changing position loop
PB30
PB31
PG2B
VG2B
Gain changing position loop gain 2
Gain changing speed loop gain 2
rad/s
rad/s
ms
gain 2.
Used to set the value of the after-changing speed loop
gain.
Gain changing speed integral
compensation
Used to set the value of the after-changing speed integral
compensation.
PB32
PB26
VICB
CDP
Gain changing selection
Used to select the changing condition.
kpps Used to set the changing condition values.
PB27
CDS
Gain changing condition
pulse
r/min
You can set the filter time constant for a gain change at
PB28
PB33
PB34
CDT
Gain changing time constant
ms
changing.
Gain changing vibration suppression
control vibration frequency setting
Gain changing vibration suppression
control resonance frequency setting
Used to set the value of the after-changing vibration
VRF1B
VRF2B
Hz
suppression control vibration frequency setting.
Used to set the value of the after-changing vibration
Hz
suppression control resonance frequency setting.
7 - 12
7. SPECIAL ADJUSTMENT FUNCTIONS
(1) Parameters No.PB06 to PB10
These parameters are the same as in ordinary manual adjustment. Gain changing allows the values of
ratio of load inertia moment to servo motor inertia moment, position loop gain, speed loop gain and speed
integral compensation to be changed.
(2) Gain changing ratio of load inertia moment to servo motor inertia moment (GD2B: parameter No.PB29)
Set the ratio of load inertia moment to servo motor inertia moment after changing. If the load inertia moment
ratio does not change, set it to the same value as ratio of load inertia moment to servo motor inertia moment
(parameter No.PB06).
(3) Gain changing position loop gain (parameter No.PB30), Gain changing speed loop gain (parameter
No.PB31), Gain changing speed integral compensation (parameter No.PB32)
Set the values of after-changing position loop gain, speed loop gain and speed integral compensation.
(4) Gain changing selection (parameter No.PB26)
Used to set the gain changing condition. Choose the changing condition in the first digit and second digit. If
you set "1" in the first digit here, you can use the control command from controller is valid for gain changing.
0 0
Gain changing selection
Under any of the following conditions, the gains
change on the basis of the parameter No.PB29 to
PB32 settings.
0: Invalid
1: Control command from controller is valid
2: Command frequency (Parameter No.PB27 setting)
3: Droop pulse value (Parameter No.PB27 setting)
4: Servo motor speed (Parameter No.PB27 setting)
Gain changing condition
0: Valid at more than condition (Valid with ON for control command from controller.)
1: Valid at less than condition (Valid with OFF for control command from controller.)
(5) Gain changing condition (parameter No.PB27)
When you selected "command frequency", "droop pulses" or "servo motor speed" in gain changing
selection (parameter No.PB26), set the gain changing level.
The setting unit is as follows.
Gain changing condition
Command frequency
Droop pulses
Unit
kpps
pulse
r/min
Servo motor speed
(6) Gain changing time constant (parameter No.PB28)
You can set the primary delay filter to each gain at gain changing. This parameter is used to suppress
shock given to the machine if the gain difference is large at gain changing, for example.
7 - 13
7. SPECIAL ADJUSTMENT FUNCTIONS
7.6.4 Gain changing operation
This operation will be described by way of setting examples.
(1) When you choose changing by input device
(a) Setting
Parameter No. Abbreviation
Name
Setting
100
Unit
rad/s
PB07
PG1
Model loop gain
Ratio of load inertia moment to servo motor
inertia moment
Multiplier
PB06
GD2
4.0
(
1)
PB08
PB09
PB10
PG2
VG2
VIC
Position loop gain
120
3000
20
rad/s
rad/s
Speed loop gain
Speed integral compensation
Gain changing ratio of load inertia moment
to servo motor inertia moment
Gain changing position loop gain
Gain changing speed loop gain
Gain changing speed integral compensation
Ms
Multiplier
PB29
GD2B
10.0
(
1)
PB30
PB31
PB32
PG2B
VG2B
VICB
84
rad/s
rad/s
ms
4000
50
0001
PB26
PB28
CDP
CDT
Gain changing selection
(Changed by ON/OFF of input device)
100
Gain changing time constant
ms
Hz
Used to set the value of the after-changing
vibration suppression control vibration
frequency setting.
Gain changing vibration suppression control
vibration frequency setting
PB33
PB34
VRF1B
VRF2B
Used to set the value of the after-changing
vibration suppression control resonance
frequency setting.
Gain changing vibration suppression control
resonance frequency setting
Hz
(b) Changing operation
OFF
OFF
ON
After-changing gain
Control command
of controller
Before-changing gain
Change of
each gain
CDT 100ms
Model loop gain 1
100
Ratio of load inertia moment
to servo motor inertia moment
Position loop gain
4.0
10.0
4.0
120
3000
20
84
4000
50
120
3000
20
Speed loop gain
Speed integral compensation
7 - 14
7. SPECIAL ADJUSTMENT FUNCTIONS
(2) When you choose changing by droop pulses
(a) Setting
Parameter No. Abbreviation
Name
Setting
100
Unit
rad/s
PB07
PG1
Model loop gain
Ratio of load inertia moment to servo motor
inertia moment
Multiplier
PB06
GD2
4.0
(
1)
PB08
PB09
PB10
PG2
VG2
VIC
Position loop gain
120
3000
20
rad/s
rad/s
Speed loop gain
Speed integral compensation
Gain changing ratio of load inertia moment to
servo motor inertia moment
ms
Multiplier
PB29
GD2B
10.0
(
1)
PB30
PB31
PB32
PG2B
VG2B
VICB
Gain changing position loop gain
Gain changing speed loop gain
Gain changing speed integral compensation
84
rad/s
rad/s
ms
4000
50
0003
PB26
CDP
Gain changing selection
(Changed by droop pulses)
PB27
PB28
CDS
CDT
Gain changing condition
50
pulse
ms
Gain changing time constant
100
(b) Changing operation
Command pulse
Droop pulses
CDS
Droop pulses [pulses]
0
CDS
After-changing gain
Before-changing gain
Change of each gain
CDT 100ms
Model loop gain
100
Ratio of load inertia moment
to servo motor inertia moment
Position loop gain
4.0
10.0
4.0
10.0
120
3000
20
84
4000
50
120
3000
20
84
4000
50
Speed loop gain
Speed integral compensation
7 - 15
7. SPECIAL ADJUSTMENT FUNCTIONS
MEMO
7 - 16
8. TROUBLESHOOTING
8. TROUBLESHOOTING
POINT
As soon as an alarm occurs, make the Servo off status and interrupt the main
circuit power.
If an alarm/warning has occurred, refer to this chapter and remove its cause.
8.1 Alarms and warning list
When a fault occurs during operation, the corresponding alarm or warning is displayed. If any alarm or warning
has occurred, refer to section 8.2 or 8.3 and take the appropriate action. When an alarm occurs, the ALM turns
OFF.
After its cause has been removed, the alarm can be deactivated in any of the methods marked in the alarm
deactivation column. The alarm is automatically canceled after removing the cause of occurrence.
Alarm deactivation
Display
Name
Display
10 Undervoltage
Name
Power
Error
CPU
reset
92 Battery cable disconnection warning
96 Home position setting warning
9F Battery warning
OFF ON reset
12 Memory error 1 (RAM)
13 Clock error
E0 Excessive regeneration warning
E1 Overload warning 1
15 Memory error 2 (EEP-ROM)
16 Encoder error 1 (At power on)
17 Board error
E3 Absolute position counter warning
E4 Parameter warning
E6 Servo forced stop warning
E7 Controller forced stop warning
E8 Cooling fan speed reduction warning
E9 Main circuit off warning
19 Memory error 3 (Flash-ROM)
1A Motor combination error
20 Encoder error 2
24 Main circuit error
EC Overload warning 2
25 Absolute position erase
ED Output watt excess warning
(Note 1) (Note 1) (Note 1)
30 Regenerative error
31 Overspeed
32 Overcurrent
33 Overvoltage
(Note 2)
34 Receive error 1
35 Command frequency error
36 Receive error 2
37 Parameter error
(Note 1) (Note 1) (Note 1)
(Note 1) (Note 1) (Note 1)
45 Main circuit device overheat
46 Servo motor overheat
47 Cooling fan error
50 Overload 1
(Note 1) (Note 1) (Note 1)
(Note 1) (Note 1) (Note 1)
51 Overload 2
52 Error excessive
8A USB communication time-out error
8E USB communication error
888 Watchdog
Note 1. Deactivate the alarm about 30 minutes of cooling time after removing the cause of occurrence.
2. In some controller communication status, the alarm factor may not be removed.
8 - 1
8. TROUBLESHOOTING
8.2 Remedies for alarms
When any alarm has occurred, eliminate its cause, ensure safety, then reset the
alarm, and restart operation. Otherwise, injury may occur.
If an absolute position erase (25) occurred, always make home position setting
again. Not doing so may cause unexpected operation.
CAUTION
As soon as an alarm occurs, mark Servo-off and power off the main circuit and
control circuit.
POINT
When any of the following alarms has occurred, do not deactivate the alarm
and resume operation repeatedly. To do so will cause the servo amplifier/servo
motor to fail. Remove the cause of occurrence, and leave a cooling time of
more than 30 minutes before resuming operation. To protect the main circuit
elements, any of these servo alarms cannot be deactivated from the servo
system controller until the specified time elapses after its occurrence. Judging
the load changing condition until the alarm occurs, the servo amplifier
calculates this specified time automatically.
Regenerative error (30)
Overload 1 (50)
Overload 2 (51)
The alarm can be deactivated by switching power off, then on or by the error
reset command CPU reset from the servo system controller. For details, refer
to section 8.1.
When an alarm occurs, the trouble (ALM) switches off and the dynamic brake is operated to stop the servo
motor. At this time, the display indicates the alarm No.
The servo motor comes to a stop. Remove the cause of the alarm in accordance with this section. Use the MR
Configurator to refer to a factor of alarm occurrence.
Display
10
Name
Definition
Cause
Action
Undervoltage
Power supply voltage 1. Power supply voltage is low.
Check the power supply.
dropped.
2. There was an instantaneous control
power failure of 60ms or longer.
3. Shortage of power supply capacity
caused the power supply voltage to
drop at start, etc.
MR-J3- B:
160VAC or less
MR-J3- B1:
83VAC or less
MR-J3- B4:
280VAC or less
4. The bus voltage dropped to the
following value or less.
MR-J3- B: 200VDC
MR-J3- B1: 158VDC
MR-J3- B4: 380VDC
5. Faulty parts in the servo amplifier
Checking method
Change the servo amplifier.
Alarm (10) occurs if power is
switched on after disconnection
of all cables but the control
circuit power supply cables.
8 - 2
8. TROUBLESHOOTING
Display
12
Name
Definition
Cause
Action
Memory error 1 RAM, memory fault Faulty parts in the servo amplifier
(RAM)
Clock error
Change the servo amplifier.
Checking method
13
Printed board fault
Alarm (any of 12 and 13)
occurs if power is switched on
after disconnection of all cables
but the control circuit power
supply cables.
Clock error
transmitted from the
controller
Faulty controller
Change the servo system controller.
Change the servo amplifier.
Checking method
Alarm (13) occurs, if servo
controller is used in multiple CPU
system.
1. Faulty parts in the servo amplifier
15
Memory error 2 EEP-ROM fault
(EEP-ROM)
Checking method
Alarm (15)
occurs if power is switched on
after disconnection of all cables
but the control circuit power
supply cables.
2. The number of write times to EEP-
ROM exceeded 100,000.
16
Encoder error 1 Communication error 1. Encoder connector (CN2)
Connect correctly.
(At power on)
occurred between
encoder and servo
amplifier.
disconnected.
2. Encoder fault
3. Encoder cable faulty
(Wire breakage or shorted)
Change the servo motor.
Repair or change the cable.
4. Encoder cable type (2-wire, 4-wire) Correct the setting in the fourth digit of
selection was wrong in parameter
setting.
parameter No.PC04.
17
19
Board error 2
CPU/parts fault
Faulty parts in the servo amplifier
Checking method
Alarm (17 or 19) occurs if
Change the servo amplifier.
Memory error 3 ROM memory fault
(Flash ROM)
power is switched on after
disconnection of all cables but the
control circuit power supply cable.
1A
20
Motor
combination
error
Wrong combination Wrong combination of servo amplifier Use correct combination.
of servo amplifier
and servo motor.
and servo motor connected.
Encoder error 2 Communication error 1. Encoder connector (CN2)
Connect correctly.
occurred between
encoder and servo
amplifier.
disconnected.
2. Encoder cable faulty
(Wire breakage or shorted)
3. Encoder fault
Repair or change the cable.
Change the servo motor.
24
Main circuit error Ground fault
1. Power input wires and servo motor Connect correctly.
power wires are in contact.
occurred at the servo
motor power (U,V
and W phases) of
the servo amplifier.
2. Sheathes of servo motor power
cables deteriorated, resulting in
ground fault.
Change the cable.
3. Main circuit of servo amplifier failed.
Change the servo amplifier.
Checking method
Alarm (24) occurs if the servo is
switched on after disconnecting
the U, V, W power cables from
the servo amplifier.
25
Absolute
position erase
Absolute position
data in error
1. Voltage drop in encoder
(Battery disconnected.)
After leaving the alarm occurring for a few
minutes, switch power off, then on again.
Always make home position setting again.
2. Battery voltage low
Change the battery.
Always make home position setting again.
3. Battery cable or battery is faulty.
Power was switched 4. Home position not set.
on for the first time in
the absolute position
After leaving the alarm occurring for a few
minutes, switch power off, then on again.
Always make home position setting again.
detection system.
8 - 3
8. TROUBLESHOOTING
Display
30
Name
Definition
Permissible
regenerative power
of the built-in
regenerative resistor
or regenerative
option is exceeded.
Cause
Action
Regenerative
error
1. Wrong setting of parameter No.
PA02
2. Built-in regenerative resistor or
regenerative option is not
connected.
Set correctly.
Connect correctly.
3. High-duty operation or continuous
1. Reduce the frequency of positioning.
regenerative operation caused the 2. Use the regenerative option of larger
permissible regenerative power of
the regenerative option to be
exceeded.
capacity.
3. Reduce the load.
Checking method
Call the status display and check
the regenerative load ratio.
4. Power supply voltage is abnormal.
MR-J3- B:260VAC or more
Check the power supply.
MR-J3- B1:More than 135VAC
MR-J3- B4: 535VAC or more
5. Built-in regenerative resistor or
regenerative option faulty.
Change the servo amplifier or regenerative
option.
Regenerative
transistor fault
Change the servo amplifier.
6. Regenerative transistor faulty.
Checking method
1) The regenerative option has
overheated abnormally.
2) The alarm occurs even after
removal of the built-in
regenerative resistor or
regenerative option.
31
Overspeed
Speed has exceeded 1. Small acceleration/deceleration time Increase acceleration/deceleration time
the instantaneous
permissible speed.
constant caused overshoot to be
large.
constant.
2. Servo system is instable to cause
overshoot.
1. Re-set servo gain to proper value.
2. If servo gain cannot be set to proper
value.
1) Reduce load inertia moment ratio; or
2) Reexamine acceleration/
deceleration time constant.
Change the servo motor.
3. Encoder faulty.
Current that flew is
higher than the
32
Overcurrent
1. Short occurred in servo motor power Correct the wiring.
(U, V, W).
permissible current of
the servo amplifier.
(If the alarm (32)
occurs again when
turning ON the servo
after resetting the
alarm by turning
OFF/ON the power
when the alarm (32)
first occurred, the
transistor (IPM
2. Transistor (IPM IGBT) of the servo Change the servo amplifier.
amplifier faulty.
Checking method
Alarm (32) occurs if power is
switched on after U,V and W are
disconnected.
3. Ground fault occurred in servo
motor power (U, V, W).
4. External noise caused the
overcurrent detection circuit to
misoperate.
Correct the wiring.
Take noise suppression measures.
IGBT) of the servo
amplifier may be at
fault. In the case, do
not repeat to turn
OFF/ON the power.
Check the transistor
with the checking
method of “Cause
2”.)
8 - 4
8. TROUBLESHOOTING
Display
33
Name
Definition
Cause
Action
Use the regenerative option.
Set correctly.
Overvoltage
The following shows 1. Regenerative option is not used.
the input value of
converter bus
voltage.
2. Though the regenerative option is
used, the parameter No.PA02
setting is "
00 (not used)".
MR-J3- B(1):
400VDC or more
MR-J3- B4:
3. Lead of built-in regenerative resistor 1. Change the lead.
or regenerative option is open or
disconnected.
2. Connect correctly.
800VDC or more
4. Regenerative transistor faulty.
5. Wire breakage of built-in
regenerative resistor or regenerative
option
Change the servo amplifier.
1. For wire breakage of built-in regenerative
resistor, change the servo amplifier.
2. For wire breakage of regenerative option,
change the regenerative option.
Add regenerative option or increase
capacity.
6. Capacity of built-in regenerative
resistor or regenerative option is
insufficient.
7. Power supply voltage high.
8. Ground fault occurred in servo
motor power (U, V, W).
Check the power supply.
Correct the wiring.
9. The jumper across BUE-SD of the Fit the jumper across BUE-SD.
FR-BU2 brake unit is removed.
34
Receive error 1 SSCNET
communication error
1. The SSCNET cable is
disconnected.
Connect it after turning off the control circuit
power supply for servo amplifier.
(Continuously
communication error
with about 3.5ms
interval.)
2. The surface at the end of SSCNET Wipe dirt at the surface away. (Refer to
cable got dirty.
section 3.9)
3. The SSCNET cable is broken or
severed.
Change the cable.
4. Noise entered the servo amplifier.
5. Optical characteristic of SSCNET
cable deteriorated because vinyl
tape and/or wire sheath, which
contains migrating plasticizer,
adhered to the cable.
Take noise suppression measures.
Remove the vinyl tape and/or wire sheath,
which contains migrating plasticizer, and
exchange the cable.
35
Command
Input pulse frequency 1. Command given is greater than the Check operation program.
frequency error of command pulse is
too high.
maximum speed of the servo motor.
2. Servo system controller failure.
3. Noise entered the servo amplifier.
Change the servo system controller.
Take noise of I/O signal suppression
measures.
4. Noise entered the controller.
Take noise from the controller suppression
measures.
36
Receive error 2 SSCNET
communication error
(Intermittently
1. The SSCNET cable is
disconnected.
Connect it after turning off the control circuit
power supply for servo amplifier.
2. The surface at the end of SSCNET Wipe dirt away from the surface. (Refer to
communication error
with about 70ms
interval.)
cable got dirty.
section 3.9)
3. The SSCNET cable is broken or Change the cable.
severed.
4. Noise entered the servo amplifier.
5. Optical characteristic of SSCNET
cable deteriorated because vinyl
tape and/or wire sheath, which
contains migrating plasticizer,
adhered to the cable.
Take noise suppression measures.
Remove the vinyl tape and/or wire sheath,
which contains migrating plasticizer, and
exchange the cable.
8 - 5
8. TROUBLESHOOTING
Display
37
Name
Definition
Cause
Action
Parameter error Parameter setting is 1. Servo amplifier fault caused the
Change the servo amplifier.
wrong.
parameter setting to be rewritten.
2. There is a parameter whose value Change the parameter value to within the
was set to outside the setting range setting range.
by the controller.
Change the servo amplifier.
3. The number of write times to EEP-
ROM exceeded 100,000 due to
parameter write, etc.
45
Main circuit
device overheat overheat
Main circuit device
1. Servo amplifier faulty.
Change the servo amplifier.
The drive method is reviewed.
2. The power supply was turned on
and off continuously by overloaded
status.
3. Ambient temperature of servo motor Check environment so that ambient
is over 55 temperature is 0 to 55
Use within the range of specifications.
.
.
4. Used beyond the specifications of
close mounting.
46
47
Servo motor
overheat
Servo motor
1. Ambient temperature of servo motor Check environment so that ambient
temperature rise
actuated the thermal
sensor.
is over 40
.
temperature is 0 to 40
.
2. Servo motor is overloaded.
1. Reduce load.
2. Check operation pattern.
3. Use servo motor that provides larger
output.
3. Thermal sensor in encoder is faulty. Change the servo motor.
1. Cooling fan life expiration (Refer to Change the cooling fan of the servo
Cooling fan
error
The cooling fan of
the servo amplifier
stopped, or its speed
decreased to or
below the alarm
level.
section 2.5.)
amplifier.
2. Foreign matter caught in the cooling Remove the foreign matter.
fan stopped rotation.
3. The power supply of the cooling fan Change the servo amplifier.
failed.
50
Overload 1
Load exceeded
overload protection
characteristic of
servo amplifier.
1. Servo amplifier is used in excess
of its continuous output current.
1. Reduce load.
2. Check operation pattern.
3. Use servo motor that provides larger
output.
2. Servo system is instable and
hunting.
1. Repeat acceleration/
deceleration to execute auto tuning.
2. Change the auto tuning response setting.
3. Set auto tuning to OFF and make gain
adjustment manually.
3. Machine struck something.
1. Check operation pattern.
2. Install limit switches.
4. Wrong connection of servo motor.
Servo amplifier's output terminals U,
V, W do not match servo motor's
input terminals U, V, W.
Connect correctly.
5. Encoder faulty.
Change the servo motor.
Checking method
When the servo motor shaft is
rotated with the servo off, the
cumulative feedback pulses do not
vary in proportion to the rotary angle
of the shaft but the indication skips
or returns midway.
6. After Overload 2 (51) occurred, turn 1. Reduce load.
OFF/ON the power supply to clear 2. Check operation pattern.
the alarm. Then the overload
operation is repeated.
3. Use servo motor that provides larger
output.
8 - 6
8. TROUBLESHOOTING
Display
51
Name
Definition
Cause
Action
Overload 2
Machine collision or 1. Machine struck something.
the like caused max.
1. Check operation pattern.
2. Install limit switches.
For the time of the
2. Wrong connection of servo motor.
Servo amplifier's output terminals U,
V, W do not match servo motor's
input terminals U, V, W.
Connect correctly.
alarm occurrence,
refer to the section
10.1.
3. Servo system is instable and
hunting.
1. Repeat acceleration/deceleration to
execute auto tuning.
2. Change the auto tuning response setting.
3. Set auto tuning to OFF and make gain
adjustment manually.
4. Encoder faulty.
Checking method
Change the servo motor.
When the servo motor shaft is
rotated with the servo off, the
cumulative feedback pulses do not
vary in proportion to the rotary angle
of the shaft but the indication skips
or returns midway.
52
Error excessive The deviation
between the model
1. Acceleration/deceleration time
constant is too small.
Increase the acceleration/deceleration time
constant.
position and the
2. Torque limit value set with controller Increase the torque limit value.
is too small.
actual servo motor
position exceeds the
parameter No.PC01
setting value (initial
value: 3 revolutions).
3. Motor cannot be started due to
torque shortage caused by power
supply voltage drop.
1. Check the power supply capacity.
2. Use servo motor which provides larger
output.
4. Position loop gain 1 (parameter
No.PB08) value is small.
Increase set value and adjust to ensure
proper operation.
5. Servo motor shaft was rotated by
external force.
1. When torque is limited, increase the limit
value.
2. Reduce load.
3. Use servo motor that provides larger
output.
6. Machine struck something.
1. Check operation pattern.
2. Install limit switches.
Change the servo motor.
Connect correctly.
7. Encoder faulty
8. Wrong connection of servo motor.
Servo amplifier's output terminals U,
V, W do not match servo motor's
input terminals U, V, W.
9. SSCNET cable fault
Change the SSCNET cable.
10. Optical characteristic of SSCNET Remove the vinyl tape and/or wire sheath,
cable deteriorated because vinyl
tape and/or wire sheath, which
contains migrating plasticizer,
adhered to the cable.
which contains migrating plasticizer, and
exchange the cable.
8A
8E
USB
Communication with 1. USB cable breakage.
Change the USB cable.
communication MR Configurator in
time-out error
test operation mode
stopped for longer
than the specified
time.
Serial communication
error occurred
between servo
amplifier and
communication
device (e.g. personal
computer).
USB
1. USB cable fault
Change the USB cable.
communication
error
(Open cable or short circuit)
2. Communication device (e.g.
personal computer) faulty
Change the communication device (e.g.
personal computer).
8 - 7
8. TROUBLESHOOTING
Display
Name
Definition
Cause
Action
(Note) Watchdog
888
CPU, parts faulty
Fault of parts in servo amplifier
Change the servo amplifier.
Checking method
Alarm (888) occurs if power is
switched on after disconnection of
all cables but the control circuit
power supply cable.
Note. At power-on, "888" appears instantaneously, but it is not an error.
8.3 Remedies for warnings
If an absolute position counter warning (E3) occurred, always make home position
setting again. Not doing so may cause unexpected operation.
CAUTION
POINT
When any of the following alarms has occurred, do not resume operation by
switching power of the servo amplifier OFF/ON repeatedly. The servo amplifier
and servo motor may become faulty. If the power of the servo amplifier is
switched OFF/ON during the alarms, allow more than 30 minutes for cooling
before resuming operation.
Excessive regenerative warning (E0)
Overload warning 1 (E1)
If E6, E7 or E9 occurs, the servo off status is established. If any other warning occurs, operation can be
continued but an alarm may take place or proper operation may not be performed.
Remove the cause of warning according to this section. Use the MR Configurator to refer to a factor of warning
occurrence.
Display
92
Name
Definition
Cause
Action
Repair cable or changed.
Change the battery.
Battery cable
disconnection
warning
Absolute position detection 1. Battery cable is open.
system battery voltage is
low.
2. Battery voltage supplied from the servo
amplifier to the encoder fell to about 3V or
less.
(Detected with the encoder)
96
Home position
setting warning
Home position setting
could not be made.
1. Droop pulses remaining are greater than Remove the cause of droop pulse
the in-position range setting. occurrence
2. Command pulse entered after clearing of Do not enter command pulse
droop pulses.
after clearing of droop pulses.
Reduce creep speed.
3. Creep speed high.
9F Battery warning
Voltage of battery for
Battery voltage fell to 3.2V or less.
Change the battery.
absolute position detection (Detected with the servo amplifier)
system reduced.
E0 Excessive
regeneration
warning
There is a possibility that Regenerative power increased to 85% or
1. Reduce frequency of
positioning.
regenerative power may
exceed permissible
regenerative power of
built-in regenerative
resistor or regenerative
option.
more of permissible regenerative power of
built-in regenerative resistor or regenerative 2. Change the regenerative
option.
option for the one with larger
capacity.
Checking method
Call the status display and check
regenerative load ratio.
3. Reduce load.
8 - 8
8. TROUBLESHOOTING
Cause
E1 Overload warning There is a possibility that Load increased to 85% or more of overload Refer to 50, 51.
overload alarm 1 or 2 may alarm 1 or 2 occurrence level.
occur.
Display
Name
Definition
Action
1
Cause, checking method
Refer to 50,51.
E3 Absolute position Absolute position encoder 1. Noise entered the encoder.
counter warning pulses faulty.
Take noise suppression
measures.
2. Encoder faulty.
Change the servo motor.
Make home position setting
again.
The multi-revolution
counter value of the
absolute position encoder
exceeded the maximum
revolution range.
3. The movement amount from the home
position exceeded a 32767 rotation or
37268 rotation in succession.
E4 Parameter
warning
Parameter outside setting Parameter value set from servo system Set it correctly.
range
controller is outside setting range
E6 Servo forced stop EM1 is off.
warning
External forced stop was made valid. (EM1 Ensure safety and deactivate
was turned off.)
forced stop.
E7 Controller forced
Forced stop signal was entered into the
servo system controller.
Ensure safety and deactivate
forced stop.
stop warning
E8 Cooling fan speed The speed of the servo
Cooling fan life expiration (Refer to section Change the cooling fan of the
reduction warning amplifier decreased to or 2.5.)
below the warning level.
servo amplifier.
This warning is not
The power supply of the cooling fan is
Change the servo amplifier.
displayed with MR-J3-
70B/100B among servo
amplifiers equipped with a
cooling fan.
broken.
E9 Main circuit off
warning
Servo-on command was
issued with main circuit
power off.
Switch on main circuit power.
EC Overload warning Operation, in which a
During a stop, the status in which a current 1. Reduce the positioning
2
current exceeding the
rating flew intensively in
any of the U, V and W
phases of the servo motor,
was repeated.
flew intensively in any of the U, V and W
phases of the servo motor occurred
repeatedly, exceeding the warning level.
frequency at the specific
positioning address.
2. Reduce the load.
3. Replace the servo amplifier/
servo motor with the one of
larger capacity.
ED Output watt
The status, in which the
output wattage (speed
Continuous operation was performed with
1. Reduce the servo motor
excess warning
the output wattage (speed
torque) of the speed.
torque) of the servo motor servo motor exceeding 150% of the rated
exceeded the rated output, output.
2. Reduce the load.
continued steadily.
8 - 9
8. TROUBLESHOOTING
MEMO
8 - 10
9. OUTLINE DRAWINGS
9. OUTLINE DRAWINGS
9.1 Servo amplifier
(1) MR-J3-10B MR-J3-20B
MR-J3-10B1 MR-J3-20B1
[Unit: mm]
6 mounting hole
40
6
4
Approx.80
135
(Note)
CNP1
(Note)
CNP2
CNP3
6
Approx.
25.5
Approx.68
With MR-J3BAT
Note. This data applies to the 3-phase or 1-phase 200 to 230VAC power supply models.
For a single-phase, 100 to 120VAC power supply, refer to the terminal signal layout.
Mass: 0.8 [kg] (1.76 [lb])
Mounting screw
Screw size: M5
Tightening torque: 3.24 [N m] (28.7 [lb in])
Terminal signal layout
For 3-phase or
For 1-phase
1-phase
PE terminal
100 to 120VAC 200 to 230VAC
Approx. 40
6
L1
L1
L2
L3
N
L2
N
CNP1
CNP1
Screw size: M4
Tightening torque:
2-M5 screw
1.2 [N m] (10.6 [lb in])
P1
P2
P1
P2
P
C
P
C
CNP2
CNP3
CNP2
CNP3
D
D
L11
L21
L11
L21
U
V
U
V
W
W
Mounting hole process drawing
9 - 1
9. OUTLINE DRAWINGS
(2) MR-J3-40B MR-J3-60B
MR-J3-40B1
[Unit: mm]
6 mounting hole
40
6
5
Approx.80
170
(Note)
L1
L2
CNP1
(Note)
L3
N
P1
P2
CNP2
CNP3
P
C
D
L11
L21
U
V
W
CHARGE
6
Approx.
25.5
Approx.68
With MR-J3BAT
Note. This data applies to the 3-phase or 1-phase 200 to 230VAC power supply models.
For a single-phase, 100 to 120VAC power supply, refer to the terminal signal layout.
Mass: 1.0 [kg] (2.21 [lb])
Terminal signal layout
For 3-phase or
Mounting screw
Screw size: M5
Tightening torque: 3.24 [N m] (28.7 [lb in])
For 1-phase
1-phase
PE terminal
Approx. 40
6
100 to 120VAC 200 to 230VAC
L1
L1
L2
L3
N
L2
N
CNP1
CNP1
Screw size: M4
Tightening torque:
2-M5 screw
1.2 [N m] (10.6 [lb in])
P1
P2
P1
P2
P
C
P
C
CNP2
CNP3
CNP2
CNP3
D
D
L11
L21
L11
L21
U
V
U
V
Mounting hole process drawing
W
W
9 - 2
9. OUTLINE DRAWINGS
(3) MR-J3-70B MR-J3-100B
[Unit: mm]
12
6 mounting hole
Approx.80
60
6
185
CNP1
CNP2
CNP3
6
Cooling fan
wind direction
12
Approx.68
Approx.25.5
With MR-J3BAT
42
Mass: 1.4 [kg] (3.09 [lb])
Terminal signal layout
Mounting screw
Screw size: M5
Tightening torque: 3.24 [N m] (28.7 [lb in])
PE terminal
L1
L2
L3
N
Approx. 60
CNP1
P1
P2
Screw size: M4
Tightening torque:
1.2 [N m] (10.6 [lb in])
P
C
CNP2
CNP3
D
3-M5 screw
42 0.3
L11
L21
U
V
Approx. 6
Mounting hole process drawing
Approx. 12
W
9 - 3
9. OUTLINE DRAWINGS
(4) MR-J3-60B4 MR-J3-100B4
[Unit: mm]
Approx. 80
60
195
6mounting hole
6
12
CNP1
CNP2
CNP3
6
42
12
Approx. 68
Approx. 25.5
With MR-J3BAT
Mass: 1.7 [kg] (3.75 [lb])
Mounting screw
Screw size: M5
Terminal signal layout
Tightening torque: 3.24 [N m] (28.7 [lb in])
PE terminal
L1
L2
L3
Approx. 60
CNP1
N
Screw size: M4
Tightening torque:
P1
1.2 [N m] (10.6 [lb in])
P2
P
C
D
3-M5 screw
42 0.3
CNP2
CNP3
L11
L21
U
V
Approx. 12
Approx. 6
W
Mounting hole process drawing
9 - 4
9. OUTLINE DRAWINGS
(5) MR-J3-200B(4)
POINT
Connectors (CNP1, CNP2, and CNP3) and appearance of MR-J3-200B servo
amplifier have been changed from January 2008 production. Model name of
the existing servo amplifier is changed to MR-J3-200B-RT. For MR-J3-200B-
RT, refer to appendix 5.
[Unit: mm]
6mounting hole
Approx. 80
90
85
195
6
45
CNP1
CNP2
CNP3
6
Approx.
Cooling fan
25.5
wind direction
Approx. 68
6
6
78
With MR-J3BAT
Mass: 2.1 [kg] (4.63 [lb])
Mounting screw
Screw size: M5
Tightening torque: 3.24 [N m] (28.7 [lb in])
Terminal signal layout
PE terminal
L1
L2
L3
Approx. 90
CNP1
N
Screw size: M4
Tightening torque:
P1
1.2 [N m] (10.6 [lb in])
P2
P
C
D
3-M5 screw
CNP2
CNP3
L11
L21
U
V
Approx. 6
Mounting hole process drawing
Approx. 6
78 0.3
W
9 - 5
9. OUTLINE DRAWINGS
(6) MR-J3-350B
[Unit: mm]
6 mounting hole
Approx.80
90
85
6
195
45
21.4
6
Cooling fan
wind direction
Approx.
25.5
6
Approx.68
78
With MR-J3BAT
6
Mass: 2.3 [kg] (5.07 [lb])
Mounting screw
Screw size: M5
Terminal signal layout
PE terminal
Tightening torque: 3.24 [N m] (28.7 [lb in])
L1
L2
L3
N
Approx. 90
CNP1
P1
P2
Screw size: M4
Tightening torque:
1.2 [N m] (10.6 [lb in])
U
V
CNP3
CNP2
W
3-M5 screw
P
C
D
L11
L21
Approx. 6
Mounting hole process drawing
Approx. 6
78 0.3
9 - 6
9. OUTLINE DRAWINGS
(7) MR-J3-350B4 MR-J3-500B(4)
[Unit: mm]
Approx. 80
200
2- 6 mounting hole
6
131.5
68.5
130
Cooling fan
wind direction
118
Terminal layout
(Terminal cover open)
6
Cooling fan
TE2
TE3
TE1
With MR-J3BAT
CHARGE
20.5
3 places for
ground (M4)
Built-in regenerative
resistor lead terminal
fixing screw
Mass: 4.6 [kg] (10.1 [lb])
Approx. 130
Terminal signal layout
Approx. 6
118 0.5
Approx. 6
TE1
Terminal screw: M4
Tightening torque: 1.2[N m]
P
C
U
V
W
L1
L2
L21
P1
L3
(10.6 [lb in])
4-M5 screw
TE2
L11
Terminal screw: M3.5(Note)
Tightening torque: 0.8[N m]
(7.08 [lb in])
TE3
Terminal screw: M4
Tightening torque: 1.2[N m]
(10.6 [lb in])
N
P2
PE terminal
Terminal screw: M4
Tightening torque: 1.2[N m]
(10.6 [lb in])
Built-in regenerative resistor lead
terminal fixing screw
Note. Screw size is M3.5 for the control circuit terminal block (TE2) of the servo
amplifier manufactured in April 2007 or later. Screw size is M3 for the control
terminal block (TE2) of the servo amplifier manufactured in March 2007 or earlier.
Mounting hole process drawing
9 - 7
9. OUTLINE DRAWINGS
(8) MR-J3-700B(4)
[Unit: mm]
Approx.80
200
6
2- 6 mounting hole
62
Cooling fan
wind direction
138
172
160
Terminal layout
(Terminal cover open)
6
Cooling fan
With MR-J3BAT
TE3
CHARGE
20.5
TE1
6
TE2
3 places for
ground (M4)
Built-in regenerative
resistor lead terminal
fixing screw
Mass: 6.2 [kg] (13.7[lb])
Mounting screw
Screw size: M5
Terminal signal layout
Tightening torque: 3.24 [N m] (28.7 [lb in])
Approx. 172
TE1
Terminal screw: M4
Tightening torque: 1.2[N m]
P
C
U
V
W
L1
L2
L3
Approx. 6
Approx. 6
160 0.5
(10.6 [lb in])
TE2
L11
Terminal screw: M3.5(Note)
Tightening torque: 0.8[N m]
L21
4-M5 screw
(7.08 [lb in])
TE3
Terminal screw: M4
Tightening torque: 1.2[N m]
(10.6 [lb in])
N
P1
P2
PE terminal
Terminal screw: M4
Tightening torque: 1.2[N m]
(10.6 [lb in])
Built-in regenerative resistor lead
terminal fixing screw
Note. Screw size is M3.5 for the control circuit terminal block (TE2) of the servo
amplifier manufactured in April 2007 or later. Screw size is M3 for the control
terminal block (TE2) of the servo amplifier manufactured in March 2007 or earlier.
Mounting hole process drawing
9 - 8
9. OUTLINE DRAWINGS
(9) MR-J3-11KB(4) to 22KB(4)
[Unit: mm]
260
236
Approx. 80
260
12
12
Cooling fan
wind direction
2- 12mounting hole
With MR-J3BAT
Rating plate
123.5 13
12
183
227
26
6
26 156
52
Approx. 260
236 0.5
Approx. 12
Approx. 12
4-M10 screw
Servo amplifier
Mass[kg]([lb])
MR-J3-11KB(4)
MR-J3-15KB(4)
MR-J3-22KB(4)
18.0 (40)
18.0 (40)
19.0 (42)
Mounting hole process drawing
Terminal signal layout
TE
L1
Mounting screw
L11 L21
N
U
L2
P
L3
C
V
W
Servo
amplifier
Screw Tightening torque
size
[N m][(Ib:in)]
P1
MR-J3-11KB(4)
MR-J3-15KB(4) M10
MR-J3-22KB(4)
26.5
(234.5)
L1 L2 L3
U
N
V
W
L11 L21
P1
P
C
Screw size
M6
M4
1.2
M4
1.2
MR-J3-11KB(4)
MR-J3-15KB(4)
Tightening torque
[(lb:in)][N m]
3.0
M8
6.0
Screw size
MR-J3-22KB(4)
Tightening torque
[(lb:in)][N m]
9 - 9
9. OUTLINE DRAWINGS
9.2 Connector
(1) CN1A CN1B connector
[Unit: mm]
F0-PF2D103
F0-PF2D103-S
4.8
4.8
1.7
1.7
2.3
2.3
17.6 0.2
20.9 0.2
17.6 0.2
20.9 0.2
8
8
(2) Miniature delta ribbon (MDR) system (3M)
(a) One-touch lock type
[Unit: mm]
E
A
C
Logo etc, are indicated here.
B
12.7
Each type of dimension
Connector
Shell kit
10320-52F0-008
A
B
C
D
E
10120-3000PE
22.0
33.3
14.0
10.0
12.0
9 - 10
9. OUTLINE DRAWINGS
(b) Jack screw M2.6 type
This is not available as option.
[Unit: mm]
E
F
A
C
Logo etc, are indicated here.
B
12.7
Each type of dimension
Connector
Shell kit
10320-52F0-008
A
B
C
D
E
F
10120-3000PE
22.0
33.3
14.0
10.0
12.0
27.4
(3) SCR connector system (3M)
Receptacle: 36210-0100PL
Shell kit
: 36310-3200-008
39.5
34.8
9 - 11
9. OUTLINE DRAWINGS
MEMO
9 - 12
10. CHARACTERISTICS
10. CHARACTERISTICS
10.1 Overload protection characteristics
An electronic thermal relay is built in the servo amplifier to protect the servo motor and servo amplifier from
overloads. Overload 1 alarm (50) occurs if overload operation performed is above the electronic thermal relay
protection curve shown in any of Figs 10.1. Overload 2 alarm (51) occurs if the maximum current flew
continuously for several seconds due to machine collision, etc. Use the equipment on the left-hand side area of
the continuous or broken line in the graph.
In a machine like the one for vertical lift application where unbalanced torque will be produced, it is
recommended to use the machine so that the unbalanced torque is 70% or less of the rated torque.
When you carry out adhesion mounting of the servo amplifier, make circumference temperature into 0 to 45
or use it at 75% or smaller effective load ratio.
,
1000
1000
During operation
During operation
100
100
During servo lock
During servo lock
10
1
10
1
0.1
0
0.1
0
50
100
150
200
250
300
50
100
150
200
250
300
(Note) Load ratio [%]
(Note) Load ratio [%]
MR-J3-10B(1)
MR-J3-20B(1) MR-J3-40B(1)
MR-J3-60B(4) to MR-J3-100B(4)
10000
1000
1000
100
During operation
During operation
During servo lock
During servo lock
10
1
100
10
0.1
0
1
0
50
100
150
200
250
300
50
100
150
200
250
300
(Note) Load ratio [%]
(Note) Load ratio [%]
MR-J3-200B(4) to MR-J3-350B(4)
MR-J3-500B(4) MR-J3-700B(4)
10 - 1
10. CHARACTERISTICS
10000
1000
During operation
100
During servo lock
10
1
0
100
200
300
(Note) Load ratio [%]
MR-J3-11KB(4) to MR-J3-22KB(4)
Note. If operation that generates torque more than 100% of the rating is performed with an abnormally high frequency in a servo motor
stop status (servo lock status) or in a 30r/min or less low-speed operation status, the servo amplifier may fail even when the
electronic thermal relay protection is not activated.
Fig 10.1 Electronic thermal relay protection characteristics
10 - 2
10. CHARACTERISTICS
10.2 Power supply equipment capacity and generated loss
(1) Amount of heat generated by the servo amplifier
Table 10.1 indicates servo amplifiers' power supply capacities and losses generated under rated load. For
thermal design of an enclosure, use the values in Table 10.1 in consideration for the worst operating
conditions. The actual amount of generated heat will be intermediate between values at rated torque and
servo off according to the duty used during operation. When the servo motor is run at less than the
maximum speed, the power supply capacity will be smaller than the value in the table, but the servo
amplifier's generated heat will not change.
Table 10.1 Power supply capacity and generated heat per servo amplifier at rated output
(Note 1)
(Note 2)
Area required for
heat dissipation
[m2]
Servo amplifier
MR-J3-10B (1)
Servo motor
Power supply
capacity[kVA]
Servo amplifier-generated heat[W]
At rated torque
25
With servo off
HF-MP053
0.3
0.3
0.3
0.5
0.5
0.9
0.9
1.0
1.0
1.0
1.3
1.3
1.3
1.7
1.5
1.7
2.5
3.5
2.1
3.5
1.8
2.5
2.5
2.5
5.5
3.5
3.5
3.5
4.8
7.5
5.5
7.5
5.5
7.5
4.5
7.5
6.7
15
0.5
0.5
0.5
0.5
0.5
0.7
0.7
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
1.0
1.8
1.8
1.8
1.8
1.0
1.8
1.8
1.8
2.7
1.8
1.8
1.8
2.4
3.9
2.7
3.9
3.9
3.9
2.4
3.9
3.2
HF-MP13
25
15
HF-KP053 13
HF-MP23
25
15
25
15
MR-J3-20B (1)
MR-J3-40B (1)
HF-KP23
25
15
HF-MP43
35
15
HF-KP43
35
15
HF-SP52 (4)
HF-SP51
40
15
MR-J3-60B (4)
MR-J3-70B
40
15
HC-LP52
40
15
HF-MP73
50
15
HF-KP73
50
15
HC-UP72
50
15
HF-SP102 (4)
HF-SP81
50
15
MR-J3-100B (4)
50
15
HC-LP102
HF-SP152 (4)
HF-SP202 (4)
HF-SP121
HF-SP201
HC-RP103
HC-RP153
HC-UP152
HC-LP152
HF-SP352 (4)
HC-RP203
HC-UP202
HC-LP202
HF-SP301
HF-SP502 (4)
HC-RP353
HC-RP503
HC-UP352
HC-UP502
HC-LP302
HA-LP502
HF-SP421
50
15
90
20
90
20
90
20
90
20
MR-J3-200B (4)
MR-J3-350B (4)
MR-J3-500B (4)
50
15
90
20
90
20
90
20
130
90
20 (25) (Note 3)
20
20
20
20
25
25
25
25
25
25
25
25
90
90
120
195
135
195
195
195
120
195
160
10 - 3
10. CHARACTERISTICS
(Note 1)
(Note 2)
Area required for
heat dissipation
[m2]
Servo amplifier
MR-J3-700B (4)
Servo motor
Power supply
capacity[kVA]
Servo amplifier-generated heat[W]
At rated torque
300
With servo off
HF-SP702 (4)
10.0
10.6
10.0
11.0
16.0
12.0
18.0
16.0
22.0
22.0
22.0
33.0
30.1
37.6
33.0
25
25
25
25
45
45
45
45
45
45
45
55
55
55
55
6.0
6.0
HA-LP702
300
HA-LP601 (4)
HA-LP701M (4)
HC-LP11K2 (4)
HC-LP801 (4)
HC-LP12K1 (4)
HC-LP11K1M (4)
HC-LP15K2 (4)
HC-LP15K1 (4)
HC-LP15K1M (4)
HC-LP22K2 (4)
HC-LP20K1 (4)
HC-LP25K1
260
5.2
300
6.0
530
11.0
7.8
390
MR-J3-11KB
MR-J3-15KB
MR-J3-22KB
580
11.6
11.0
13.0
13.0
13.0
17.0
15.5
19.4
17.0
530
640
640
640
850
775
970
HC-LP22K1M (4)
850
Note 1. Note that the power supply capacity will vary according to the power supply impedance. This value is applicable when the
power factor improving reactor is not used.
2. Heat generated during regeneration is not included in the servo amplifier-generated heat. To calculate heat generated by the
regenerative option, refer to section 11.2.
3. For 400V class, the value is within the ( ).
10 - 4
10. CHARACTERISTICS
(2) Heat dissipation area for enclosed servo amplifier
The enclosed control box (hereafter called the control box) which will contain the servo amplifier should be
designed to ensure that its temperature rise is within 10 at the ambient temperature of 40 . (With a 5
(41 ) safety margin, the system should operate within a maximum 55 (131 ) limit.) The necessary
enclosure heat dissipation area can be calculated by Equation 10.1.
P
............................................................................................................................................. (10.1)
A
K
T
where, A
P
: Heat dissipation area [m2]
: Loss generated in the control box [W]
: Difference between internal and ambient temperatures [
: Heat dissipation coefficient [5 to 6]
T
]
K
When calculating the heat dissipation area with Equation 10.1, assume that P is the sum of all losses
generated in the enclosure. Refer to Table 10.1 for heat generated by the servo amplifier. "A" indicates the
effective area for heat dissipation, but if the enclosure is directly installed on an insulated wall, that extra
amount must be added to the enclosure's surface area.
The required heat dissipation area will vary wit the conditions in the enclosure. If convection in the
enclosure is poor and heat builds up, effective heat dissipation will not be possible. Therefore, arrangement
of the equipment in the enclosure and the use of a cooling fan should be considered.
Table 10.1 lists the enclosure dissipation area for each servo amplifier when the servo amplifier is operated
at the ambient temperature of 40 (104 ) under rated load.
(Outside)
(Inside)
Air flow
Fig. 10.2 Temperature distribution in enclosure
When air flows along the outer wall of the enclosure, effective heat exchange will be possible, because the
temperature slope inside and outside the enclosure will be steeper.
10 - 5
10. CHARACTERISTICS
10.3 Dynamic brake characteristics
10.3.1 Dynamic brake operation
(1) Calculation of coasting distance
Fig. 10.3 shows the pattern in which the servo motor comes to a stop when the dynamic brake is operated.
Use Equation 10.2 to calculate an approximate coasting distance to a stop. The dynamic brake time
constant varies with the servo motor and machine operation speeds. (Refer to (2)(a), (b) of this section.)
ON
Forced stop(EM1)
OFF
Time constant
V0
Machine speed
Time
te
Fig. 10.3 Dynamic brake operation diagram
JL
JM
V0
60
....................................................................................................................... (10.2)
Lmax
te
1
Lmax
Vo
JM
: Maximum coasting distance .................................................................................................... [mm][in]
: Machine rapid feed rate..............................................................................................[mm/min][in/min]
: Servo motor inertial moment..................................................................................... [kg cm2][oz in2]
: Load inertia moment converted into equivalent value on servo motor shaft ............ [kg cm2][oz in2]
: Brake time constant .......................................................................................................................... [s]
: Delay time of control section............................................................................................................. [s]
For 7kW or less servo, there is internal relay delay time of about 30ms. For 11k to 22kW servo,
there is delay time of about 100ms caused by a delay of the external relay and a delay of the
magnetic contactor built in the external dynamic brake.
JL
t
e
(2) Dynamic brake time constant
The following shows necessary dynamic brake time constant for the equations (10.2).
(a) 200V class servo motor
25
20
15
10
5
25
20
15
10
5
73
23
73
23
053
43
13
053
43
13
0
0
0
1000 2000 3000 4000 5000 6000
Speed [r/min]
0
1000 2000 3000 4000 5000 6000
Speed [r/min]
HF-MP series
HF-KP series
10 - 6
10. CHARACTERISTICS
120
100
80
60
40
20
0
60
50
40
52
51
352
81
421
30
20
10
0
102
702
301
2000
201
202
152
121
1500
502
0
500 1000 1500 2000 2500 3000
0
500
1000
Speed [r/min]
Speed [r/min]
HF-SP1000r/min series
HF-SP2000r/min series
18
16
14
12
10
100
90
80
70
60
50
40
30
20
10
0
72
502
352
103
503
8
6
153
4
2
0
353
202
203
152
0
500 1000 1500 2000 2500 3000
Speed [r/min]
0
500
1000 1500 2000
Speed [r/min]
HC-RP series
HC-UP2000r/min series
70
60
50
40
30
20
10
0
20K1
73
60
50
40
30
20
10
0
12K1
15K1
801
601
25K1
0
200 400 600 800 1000 1200
Speed[r/min]
43
23
13
0
50 500 10001500200025003000
Speed [r/min]
HC-UP3000r/min
HA-LP1000r/min series
120
100
80
60
40
20
0
80
60
40
20
0
22K1M
11K1M
15K2
11K2
22K2
702
15K1M
701M
1500
502
0
500
1000
2000
0
500
1000
1500
2000
Speed[r/min]
Speed[r/min]
HA-LP1500r/min series
HA-LP2000r/min series
10 - 7
10. CHARACTERISTICS
200
160
120
80
52
202
302
102
40
152
2000
0
0
500
1000
Speed[r/min]
1500
HC-LP series
(b) 400V class servo motor
90
35
30
25
20
15
10
5
2024
1024
20K14
75
60
45
524
12K14
8014
3524
15K14
30
15
0
5024
6014
1524
2000
7024
0
0
400
800
1200
0
1000
3000
Speed[r/min]
Speed[r/min]
HA-SP2000r/min series
HA-LP1000r/min series
20
40
35
30
16
25
12
8
11K1M4
701M4
15K24
15K1M4
20
15
11K24
10
4
22K1M4
5
0
22K2
0
0
500
1000
1500
0
500
1000 1500 2000
Speed[r/min]
Speed[r/min]
HA-LP1500r/min series
HA-LP2000r/min series
10 - 8
10. CHARACTERISTICS
10.3.2 The dynamic brake at the load inertia moment
Use the dynamic brake under the load inertia moment ratio indicated in the following table. If the load inertia
moment is higher than this value, the built-in dynamic brake may burn. If there is a possibility that the load
inertia moment may exceed the value, contact Mitsubishi.
The values of the load inertia moment ratio in the table are the values at the maximum rotation speed of the
servo motor.
Servo motor
HF-SP 1 HF-SP 2 HC-RP HC-UP
Servo
HA-
amplifier
HF-KP
HF-MP
HC-LP
HA-LP
1
HA-LP
2
LP 1M
MR-J3-10B(1)
MR-J3-20B(1)
MR-J3-40B(1)
MR-J3-60B
30
30
30
30
30
30
30
30
30
MR-J3-70B
30
30
30
MR-J3-100B
MR-J3-200B
MR-J3-350B
MR-J3-500B
MR-J3-700B
30
30
16
15
30
30
30
30
16
15
30
16
15
30
16
15
16
15
15
5 (Note 1) 5 (Note 1) 5 (Note 1)
5 (Note 1)
MR-J3-11KB
(Note 2)
30
30
30
30
30
30
30
30
30
MR-J3-15KB
(Note 2)
MR-J3-22KB
(Note 2)
Servo motor
Servo
HA-LP
1M4
amplifier
HF-SP 4 HA-LP 14
HA-LP 24
MR-J3-60B4 5 (Note 1)
MR-J3-100B4 5 (Note 1)
MR-J3-200B4 5 (Note 1)
MR-J3-350B4 5 (Note 1)
MR-J3-500B4 5 (Note 1)
MR-J3-700B4 5 (Note 1)
MR-J3-11KB4
10
30
10
30
30
30
30
(Note 2)
MR-J3-15KB4
(Note 2)
30
30
30
30
MR-J3-22KB4
(Note 2)
Note 1. The load inertia moment ratio is 15 at the rated rotation speed.
2. When the external dynamic brake is used.
10 - 9
10. CHARACTERISTICS
10.4 Cable flexing life
The flexing life of the cables is shown below. This graph calculated values. Since they are not guaranteed
values, provide a little allowance for these values.
1
5
108
107
a
1
5
107
106
a : Long flex life encoder cable
Long flex life motor power cable
Long flex life motor brake cable
SSCNET cable using long distance cable
b : Standard encoder cable
1
5
106
105
Standard motor power cable
Standard motor brake cable
SSCNET cable using inside panel standard cord
SSCNET cable using outside panel standard cable
1
5
105
104
1
5
104
103
b
1
103
4
7
10
20
40
70 100
200
Flexing radius [mm]
10.5 Inrush currents at power-on of main circuit and control circuit
The following table indicates the inrush currents (reference data) that will flow when the maximum permissible
voltage (200V class: 253VAC, 400V class: 528VAC) is applied at the power supply capacity of 2500kVA and
the wiring length of 1m (3.28ft).
Inrush currents (A0-p)
Servo amplifier
Main circuit power supply (L1, L2, L3)
38A (Attenuated to approx. 14A in 10ms)
30A (Attenuated to approx. 5A in 10ms)
54A (Attenuated to approx. 12A in 10ms)
120A (Attenuated to approx. 12A in 20ms)
44A (Attenuated to approx. 20A in 20ms)
88A (Attenuated to approx. 20A in 20ms)
Control circuit power supply (L11, L21)
MR-J3-10B1 to 40B1
MR-J3-10B to 60B
MR-J3-70B 100B
MR-J3-200B 350B
MR-J3-500B
20 to 30A
(Attenuated to approx. 0A in 1 to 2ms)
MR-J3-700B
30A (Attenuated to approx. 0A in 3ms)
MR-J3-11KB
235A (Attenuated to approx. 20A in 20ms)
MR-J3-15KB
MR-J3-22KB
MR-J3-60B4 100B4
MR-J3-200B4
MR-J3-350B4 500B4
MR-J3-700B4
100A (Attenuated to approx. 5A in 10ms)
120A (Attenuated to approx. 12A in 20ms)
66A (Attenuated to approx. 10A in 20ms)
67A (Attenuated to approx. 34A in 20ms)
40 to 50A
(Attenuated to approx. 0A in 2ms)
41A (Attenuated to approx. 0A in 3ms)
45A (Attenuated to approx. 0A in 3ms)
MR-J3-11KB4
325A (Attenuated to approx. 20A in 20ms)
MR-J3-15KB4
MR-J3-22KB4
Since large inrush currents flow in the power supplies, always use no-fuse breakers and magnetic contactors.
(Refer to section 11.12.)
When circuit protectors are used, it is recommended to use the inertia delay type that will not be tripped by an
inrush current.
10 - 10
11. OPTIONS AND AUXILIARY EQUIPMENT
11. OPTIONS AND AUXILIARY EQUIPMENT
Before connecting any option or peripheral equipment, turn off the power and wait
for 15 minutes or more until the charge lamp turns off. Then, confirm that the
voltage between P( ) and N( ) is safe with a voltage tester and others.
Otherwise, an electric shock may occur. In addition, always confirm from the front
of the servo amplifier whether the charge lamp is off or not.
WARNING
Use the specified auxiliary equipment and options. Unspecified ones may lead to a
fault or fire.
CAUTION
11.1 Cable/connector sets
POINT
Protective structure indicated for cables and connecters is for a cable or
connector alone. When the cables and connectors are used to connect the
servo amplifier and servo motor, and if protective structures of the servo
amplifier and servo motor are lower than that of the cable and connector,
specifications of the servo amplifier and servo motor apply.
As the cables and connectors used with this servo, purchase the options indicated in this section.
11 - 1
11. OPTIONS AND AUXILIARY EQUIPMENT
11.1.1 Combinations of cable/connector sets
Servo system
cont
Personal computer
35)
32)33)34)
Servo amplifier
Servo amplifier
37)
1)2)
CN5
CN5
CN3
Note
CNP1
CN3
36)
CN1A
CN1B
CN2
CN1A
CNP2
32)33)34)
CN1B
CNP3
CN2
CN4
Cap
(Servo amplifier
attachment)
CN4
Direct connection type (cable length 10m or less, IP65)
15)16)17)18)
31)
Junction type (cable length more than 10m, IP20)
21)22)
19)20)
Battery
MR-J3BAT
23)
13)14)
To 24VDC power
supply for
electromagnetic
brake
9)10)11)12)
7)8)
Servo
motor
3)4)5)6)
HF-MP
HF-KP
Power supply
connector
Brake
connector connector
Encoder
26)
24)25)
27)
Servo
motor
HF-SP
28)29)
30)
To next page a)
To next page b)
Power supply
connector
Brake
connector connector
Encoder
Note. Connectors for 3.5kW or less. For 5kW or more, terminal blocks.
11 - 2
11. OPTIONS AND AUXILIARY EQUIPMENT
From previous page a)
From previous page b)
26)
24)25)
38)
Servo motor
HC-RP
30)39)40)
HC-UP
HC-LP
Power supply
connector
Encoder
connector
Brake
connector
26)
24)25)
Servo motor
HA-LP
Terminal box
No.
1) Servo
amplifier
Product
Model
Description
Application
Supplied with
servo
power supply
connector
amplifiers of
1kW or less in
100V class
and 200V
class
CNP1
CNP2
CNP3
connector: 54928-0610 connector: 54928-0520 connector: 54928-0310
(Molex)
(Molex)
(Molex)
<Applicable cable example>
Wire size: 0.14mm2(AWG26) to 2.5mm2
(AWG14)
REC. Lever:
Cable finish OD: to 3.8mm
54932-0000
(Molex)
11 - 3
11. OPTIONS AND AUXILIARY EQUIPMENT
No.
2) Servo
amplifier
Product
Model
Description
Application
Supplied with
servo
power supply
connector
amplifiers of
3.5kW in 200V
class
CNP1 connector:
PC4/6-STF-7.62-
CRWH
CNP2 connector:
54928-0520
(Molex)
CNP3 connector:
PC4/3-STF-7.62-
CRWH
(Phoenix Contact)
(Phoenix Contact)
<Applicable cable example>
Wire size: 0.2mm2 (AWG24) to 5.5mm2
(AWG10)
REC. Lever:
Cable finish OD: to 5mm
54932-0000
(Molex)
Supplied with
servo
amplifiers of
2kW in 200V
class and 2kW
in 400V class
CNP1 connector:
721-207/026-000
(Plug)
CNP2 connector:
721-205/026-000
(Plug)
CNP3 connector:
721-203/026-000
(Plug)
(WAGO)
(WAGO)
(WAGO)
<Applicable cable example>
Wire size: 0.08mm2 (AWG28) to 2.5mm2
(AWG12)
REC. Lever: 231-131
(WAGO)
Cable finish OD: to
mm
4.1
3) Motor power MR-PWS1CBL M-A1-L
supply cable Cable length: 2 10m
4) Motor power MR-PWS1CBL M-A1-H
supply cable Cable length: 2 10m
IP65
Power supply connector
5
Load side lead
IP65
HF-MP series
HF-KP series
5
Load side lead
Long flex life
Refer to section 11.1.3 for details.
5) Motor power MR-PWS1CBL M-A2-L
supply cable Cable length: 2 10m
IP65
Power supply connector
5
Opposite-to-
load side lead
IP65
HF-MP series
HF-KP series
6) Motor power MR-PWS1CBL M-A2-H
supply cable Cable length: 2 10m
5
Opposite-to-
load side lead
Long flex life
IP55
Refer to section 11.1.3 for details.
7) Motor power MR-PWS2CBL03M-A1-L
supply cable Cable length: 0.3m
Power supply connector
Load side lead
HF-MP series
HF-KP series
Refer to section 11.1.3 for details.
8) Motor power MR-PWS2CBL03M-A2-L
supply cable Cable length: 0.3m
IP55
Power supply connector
Opposite-to-
load side lead
HF-MP series
HF-KP series
Refer to section 11.1.3 for details.
11 - 4
11. OPTIONS AND AUXILIARY EQUIPMENT
No.
9) Motor brake MR-BKS1CBL M-A1-L
cable Cable length: 2 10m
10) Motor brake MR-BKS1CBL M-A1-H
cable Cable length: 2 10m
Product
Model
Description
Application
IP65
Brake connector
5
Load side lead
IP65
HF-MP series
HF-KP series
5
Load side lead
Long flex life
Refer to section 11.1.4 for details.
11) Motor brake MR-BKS1CBL M-A2-L
cable Cable length: 2 10m
IP65
Brake connector
5
Opposite-to-
load side lead
IP65
HF-MP series
HF-KP series
12) Motor brake MR-BKS1CBL M-A2-H
cable Cable length: 2 10m
5
Opposite-to-
load side lead
Long flex life
IP55
Refer to section 11.1.4 for details.
13) Motor brake MR-BKS2CBL03M-A1-L
cable Cable length: 0.3m
Brake connector
Load side lead
HF-MP series
HF-KP series
Refer to section 11.1.4 for details.
Refer to section 11.1.4 for details.
Refer to section 11.1.2 (1) for details.
Refer to section 11.1.2 (1) for details.
14) Motor brake MR-BKS2CBL03M-A2-L
IP55
Brake connector
cable
Cable length: 0.3m
Opposite-to-
load side lead
HF-MP series
HF-KP series
15) Encoder
cable
MR-J3ENCBL M-A1-L
IP65
Encoder connector
Cable length: 2
MR-J3ENCBL M-A1-H
Cable length: 2 10m
5
10m
Load side lead
IP65
16) Encoder
cable
HF-MP series
HF-KP series
5
Opposite-to-
load side lead
Long flex life
17) Encoder
cable
MR-J3ENCBL M-A2-L
Cable length: 2 10m
IP65
Encoder connector
5
Opposite-to-
load side lead
IP65
HF-MP series
HF-KP series
18) Encoder
cable
MR-J3ENCBL M-A2-H
Cable length: 2 10m
5
Opposite-to-
load side lead
Long flex life
IP20
19) Encoder
cable
MR-J3JCBL03M-A1-L
Cable length: 0.3m
Encoder connector
Load side lead
HF-MP series
HF-KP series
Refer to section 11.1.2 (3) for details.
Encoder connector
20) Encoder
cable
MR-J3JCBL03M-A2-L
Cable length: 0.3m
IP20
Opposite-to-
load side lead
HF-MP series
HF-KP series
Refer to section 11.1.2 (3) for details.
11 - 5
11. OPTIONS AND AUXILIARY EQUIPMENT
No
Product
Model
Description
Application
IP20
21) Encoder
cable
MR-EKCBL M-L
Cable length: 20 30m
MR-EKCBL M-H
Cable length:
22) Encoder
cable
IP20
Long flex life
For HF-MP HF-KP series
20 30 40 50m
MR-ECNM
Refer to section 11.1.2 (2) for details.
23) Encoder
connector
set
IP20
For HF-MP HF-KP series
Refer to section 11.1.2 (2) for details.
24) Encoder
cable
MR-J3ENSCBL M-L
Cable length:
IP67
Standard flex
life
2
5
10 20 30m
For HF-SP HC-UP HC-LP HC-RP HA-LP series
Refer to section 11.1.2 (4) for details.
25) Encoder
cable
MR-J3ENSCBL M-H
Cable length:
IP67
Long flex life
2
5
10 20 30 40
50m
26) Encoder
connector
set
MR-J3SCNS
IP67
For HF-SP HC-UP HC-LP HC-RP HA-LP series
Refer to section 11.1.2 (4) for details.
Straight plug: CM10-SP2S-L
Socket contact: CM10-#22SC(S2)-100
(DDK)
27) Brake
connector
set
MR-BKCNS1
MR-PWCNS4
IP67
IP67
For HF-SP series
28) Power
supply
Plug: CE05-6A18-10SD-D-BSS
Cable clamp: CE3057-10A-1-D
(DDK)
connector
set
For HF-SP51 81
For HF-SP52 152
Example of applicable cable
Applicable wire size: 2mm2 (AWG14) to
3.5mm2 (AWG12)
Cable finish D: 10.5 to 14.1mm
29) Power
supply
MR-PWCNS5
Plug: CE05-6A22-22SD-D-BSS
Cable clamp: CE3057-12A-1-D
(DDK)
IP67
connector
set
For HF-SP121 to 301
For HF-SP202 to 502
Example of applicable cable
Applicable wire size: 5.5mm2 (AWG10) to
8mm2 (AWG8)
Cable finish D: 12.5 to 16mm
Plug: CE05-6A32-17SD-D-BSS
Cable clamp: CE3057-20A-1-D
(DDK)
30) Power
supply
MR-PWCNS3
IP67
Be sure to use
this when
corresponding
to EN
connector
set
For HF-SP421
For HF-SP702
For HA-LP702
Example of applicable cable
Applicable wire size: 14mm2 (AWG6) to
22mm2 (AWG4)
Standard.
Cable finish D: 22 to 23.8mm
31) Cable for
connecting
battery
MR-J3BTCBL03M
For connection
of battery
Refer to section 11.1.2 (5) for details.
11 - 6
11. OPTIONS AND AUXILIARY EQUIPMENT
No.
Product
Model
MR-J3BUS
Description
Connector: PF-2D103
Application
32) SSCNET
cable
M
Connector: PF-2D103
Inside panel
Cable length: 0.15 to 3m (Japan Aviation Electronics
(Refer to section 11.1.5.) Industry, Ltd.)
MR-J3BUS M-A
(Japan Aviation Electronics
Industry, Ltd.)
standard cord
33) SSCNET
cable
Outside panel
standard cable
Cable length: 5 to 20m
(Refer to section 11.1.5.)
34) SSCNET
cable
MR-J3BUS M-B
Connector: PF-2D103
Connector: PF-2D103
(Japan Aviation Electronics
Industry, Ltd.)
Long distance
cable
Cable length: 30 to 50m
(Refer to section 11.1.5.) Industry, Ltd.)
(Japan Aviation Electronics
35) USB cable
MR-J3USBCBL3M
Cable length: 3m
For CN5 connector
minB connector (5 pins)
For personal computer connector For connection
A connector
with PC-AT
compatible
personal
computer
36) Connector set MR-CCN1
Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or similar product)
37) Junction
terminal block
(Recommend
ed)
PS7DW-20V14B-F
(YOSHIDA ELECTRIC
INDUSTRY CO., LTD.)
MR-J2HBUS
M
Junction terminal block PS7DW-20V14B-F is not available from us as
option. For using the junction terminal block, our option MR-
J2HBUS M is necessary. Refer to section 11.7 for details.
Plug: D/MS3106A10SL-4S(D190) (DDK)
38) Break
connector set
MR-BKCN
EN standard
compliant
IP65
For cable connector : YS010-5-8(Daiwa Dengyo)
Example of applicable cable
Applicable wire size: 0.3mm2 (AWG22) to 1.25mm2
For HA-LP
For HC-UP
(AWG16)
For HC-LP
Cable finish: 5 to 8.3mm
39) Power supply MR-PWCNS1
connector set
Plug: CE05-6A22-23SD-D-BSS
Cable clamp: CE3057-12A-2-D (DDK)
Example of applicable cable
Be sure to use
this when
corresponding
to EN standard
IP65
For HC-UP
Applicable wire size: 2mm2 (AWG14) to 3.5mm2
For HC-LP
(AWG12)
For HC-RP
Cable finish: 9.5 to 13mm
40) Power supply MR-PWCNS2
connector set
Plug: CE05-6A24-10SD-D-BSS
Cable clamp: CE3057-16A-2-D (DDK)
Example of applicable cable
For HA-LP
Applicable wire size: 5.5mm2 (AWG10) to 8mm2
For HC-UP
(AWG8)
For HC-LP
Cable finish: 13 to 15.5mm
For HC-RP
11 - 7
11. OPTIONS AND AUXILIARY EQUIPMENT
11.1.2 Encoder cable/connector sets
(1) MR-J3ENCBL M-A1-L/H MR-J3ENCBL M-A2-L/H
These cables are encoder cables for the HF-MP HF-KP series servo motors. The numerals in the Cable
Length field of the table are the symbols entered in the part of the cable model. The cables of the lengths
with the symbols are available.
Cable length
10m 20m 30m
Protective
structure
Cable model
Flex life
Application
2m
2
5m
5
40m
50m
For HF-MP HF-KP servo
motor
MR-J3ENCBL M-A1-L
MR-J3ENCBL M-A1-H
MR-J3ENCBL M-A2-L
MR-J3ENCBL M-A2-H
10
10
10
10
IP65
IP65
IP65
IP65
Standard
Long flex
life
Load side lead
2
2
2
5
5
5
Standard
For HF-MP HF-KP servo
motor
Long flex
life
Opposite-to-load side lead
(a) Connection of servo amplifier and servo motor
Servo amplifier
MR-J3ENCBL M-A1-L
MR-J3ENCBL M-A1-H
2)
Servo motor
HF-MP
HF-KP
1)
or
MR-J3ENCBL M-A2-L
MR-J3ENCBL M-A2-H
2)
Servo motor
HF-MP
CN2
HF-KP
1)
Cable model
1) For CN2 connector
2) For encoder connector
MR-J3ENCBL M-
A1-L
Connector set: 54599-1019(Molex)
Connector: 1674320-1
Crimping tool for ground clip:
1596970-1
Receptacle: 36210-0100PL
Shell kit: 36310-3200-008
(3M)
Crimping tool for receptacle
contact: 1596847-1
(Tyco Electronics)
MR-J3ENCBL M-
A1-H
(Note) Signal layout
(Note) Signal layout
2
6
5
10
(Note) Signal layout
2
4
6
5
8
7
10
LG
4
8
7
MRR
LG
MRR
SHD
9
7
5
3
1
or
1
P5
9
BAT
MR-J3ENCBL M-
A2-L
8
6
4
2
1
3
9
BAT
3
MR
P5 MR
MR
P5
P5G
MRR
BAT
View seen from wiring side.
View seen from wiring side.
MR-J3ENCBL M-
A2-H
View seen from wiring side.
Note. Keep open the pins shown with
. Especially, pin 10 is provided
for manufacturer adjustment. If it is connected with any other pin, the
servo amplifier cannot operate normally.
Note. Keep open the pin shown
with an
.
11 - 8
11. OPTIONS AND AUXILIARY EQUIPMENT
(b) Cable internal wiring diagram
MR-J3ENCBL2M-L/-H
MR-J3ENCBL5M-L/-H
MR-J3ENCBL10M-L/-H
Encoder side
connector
Servo amplifier
side connector
P5
1
2
3
4
3
6
5
4
2
9
P5
LG
LG
MR
MRR
BAT
SD
MR
MRR
BAT
SHD
9
Plate
(2) MR-EKCBL M-L/H
POINT
The following encoder cables are of four-wire type. When using any of these
encoder cables, set parameter No.PC04 to "1
type.
" to select the four-wire
MR-EKCBL30M-L
MR-EKCBL30M-H
MR-EKCBL40M-H
MR-EKCBL50M-H
The servo amplifier and servo motor cannot be connected with these cables only. The servo motor side
encoder cable (MR-J3JCBL03M-A1-L or MR-J3JCBL03M-A2-L) is required.
The numerals in the Cable Length field of the table are the symbols entered in the part of the cable
model. The cables of the lengths with the symbols are available.
Cable length
Protective
structure
Cable model
Flex life
Application
2m
5m
10m
20m
30m
40m
50m
For HF-MP HF-KP servo
motor
(Note)
30
MR-EKCBL M-L
20
IP20
IP20
Standard
Use in combination with
MR-J3JCBL03M-A1-L or
MR-J3JCBL03M-A2-L.
(Note) (Note) (Note)
30 40 50
Long flex
life
MR-EKCBL M-H
20
Note. Four-wire type cable.
11 - 9
11. OPTIONS AND AUXILIARY EQUIPMENT
(a) Connection of servo amplifier and servo motor
Servo amplifier
MR-EKCBL M-L
MR-EKCBL M-H
MR-J3JCBL03M-L
Cable length: 0.3m
Servo motor
HF-MP
HF-KP
CN2
1)
2)
Cable model
1) For CN2 connector
2) For encoder connector
MR-EKCBL M-L
Connector set: 54599-1019(Molex)
Housing: 1-172161-9
Receptacle: 36210-0100PL
Shell kit: 36310-3200-008
(3M)
Crimping pin: 170359-1
(Tyco Electronics or equivalent)
Cable clamp: MTI-0002
(Toa Electric Industries)
(Note) Signal layout
(Note) Signal layout
2
6
5
10
Signal layout
2
4
6
5
8
10
LG
4
8
MRR
MDR
LG
MRR
MDR
or
1
2
3
1
P5
9
BAT
1
3
7
MD
9
BAT
MR MRR BAT
3
MR
7
MD
P5 MR
MR-EKCBL M-H
4
5
6
MD MDR CONT
View seen from wiring side.
View seen from wiring side.
7
8
9
P5 LG SHD
Note. Keep open the pins shown with
. Especially, pin 10 is provided
View seen from wiring side.
for manufacturer adjustment. If it is connected with any other pin, the
servo amplifier cannot operate normally.
Note. Keep open the pin shown
with an
.
11 - 10
11. OPTIONS AND AUXILIARY EQUIPMENT
(b) Internal wiring diagram
MR-EKCBL20M-L
MR-EKCBL30M-L
Servo amplifier side Encoder side
Servo amplifier side
Encoder side
P5
LG
1
2
7
8
P5E
P5
LG
1
2
7
8
P5E
P5G
P5G
MR
3
4
1
2
3
9
MR
MR
3
4
7
8
9
1
2
4
5
3
6
9
MR
MRR
BAT
SD
MRR
BAT
SHD
MRR
MD
MRR
MD
9
Plate
MDR
BAT
MDR
BAT
CONT
SHD
(Note)
Plate
SD
(Note)
MR-EKCBL20M-H
MR-EKCBL30M-H
MR-EKCBL40M-H
MR-EKCBL50M-H
Servo amplifier side
Encoder side
Servo amplifier side
Encoder side
P5
LG
1
2
7
8
P5E
P5G
P5
LG
1
2
7
8
P5E
P5G
MR
3
4
1
2
3
9
MR
MRR
BAT
SD
MRR
BAT
SHD
MR
3
4
7
8
9
1
2
4
5
3
6
9
MR
9
MRR
MD
MRR
MD
Plate
(Note)
MDR
BAT
MDR
BAT
CONT
SHD
SD
Plate
(Note)
Note. Always make connection for use in an absolute position detection system. Wiring is not necessary for use in an incremental
system.
When fabricating the cable, use the wiring diagram corresponding to the length indicated below.
Applicable wiring diagram
Cable flex life
Less than 10m
MR-EKCBL20M-L
MR-EKCBL20M-H
30m to 50m
Standard
Long flex life
MR-EKCBL30M-H
MR-EKCBL40M-H
MR-EKCBL50M-H
11 - 11
11. OPTIONS AND AUXILIARY EQUIPMENT
(c) When fabricating the encoder cable
When fabricating the cable, prepare the following parts and tool, and fabricate it according to the wiring
diagram in (b). Refer to section 11.8 for the specifications of the used cable.
Parts/tool
Description
Connector set
MR-ECNM
Servo amplifier side connector
Receptacle: 36210-0100PL
Shell kit: 536310-3200-008
(3M)
Encoder side connector
Housing: 1-172161-9
Connector pin: 170359-1
(Tyco Electronics or equivalent)
Cable clamp: MTI-0002
(Toa Electric Industries)
Or
Connector set: 54599-1019(Molex)
(3) MR-J3JCBL03M-A1-L MR-J3JCBL03M-A2-L
The servo amplifier and servo motor cannot be connected with these cables only. The servo motor side
encoder cable (MR-EKCBL M-L/H) is required.
Protective
Cable model
Cable length
Flex life
Application
structure
MR-J3JCBL03M-A1-L
For HF-MP HF-KP servo motor
Load side lead
Use in combination with MR-EKCBL
M-L/H.
0.3m
IP20
Standard
MR-J3JCBL03M-A2-L
For HF-MP HF-KP servo motor
Opposite-to-load side lead
Use in combination with MR-EKCBL
M-L/H.
11 - 12
11. OPTIONS AND AUXILIARY EQUIPMENT
(a) Connection of servo amplifier and servo motor
MR-J3JCBL03M-A1-L
2)
Servo amplifier
Servo motor
HF-MP
HF-KP
1)
MR-EKCBL M-L/-H
or
MR-J3JCBL03M-A2-L
2)
Servo motor
HF-MP
HF-KP
CN2
1)
Cable model
1) Junction connector
2) For encoder connector
MR-J3JCBL03M-A1-L Housing: 1-172169-9
Contact: 1473226-1
Connector: 1674320-1
Crimping tool for ground clip: 1596970-1
Crimping tool for receptacle contact: 1596847-1
(Tyco Electronics)
Cable clamp: 316454-1
Crimping tool: 91529-1
(Tyco Electronics)
Signal layout
Signal layout
9 SHD
7 MDR 8 MD
5 MR 6 P5G
MR-J3JCBL03M-A2-L
3
2
1
BAT MRR MR
3
P5 4 MRR
6
CONT
9
5
4
1 CONT 2 BAT
MDR MD
8
View seen from wiring
7
SHD LG P5
View seen from wiring side.
(b) Internal wiring diagram
MR-J3JCBL03M-A1-L
Junction
connector
Encoder side
connector
P5
7
8
1
3
6
5
4
8
7
2
1
P5
LG
MR
P5G
MR
MRR
MD
2
4
5
3
6
MRR
MD
MDR
BAT
SEL
MDR
BAT
CONT
SHD
9
9
SHD
11 - 13
11. OPTIONS AND AUXILIARY EQUIPMENT
(4) MR-J3ENSCBL M-L MR-J3ENSCBL M-H
These cables are detector cables for HF-SP HA-LP HC-RP HC-UP HC-LP Series servo motors. The
number in the cable length column of the table indicates the symbol filling the square in the cable model.
Cable lengths corresponding to the specified symbols are prepared.
Cable length
Protective
structure
Cable model
Flex life
Application
2m
2
5m
5
10m
10
20m
30m
40m
40
50m
50
MR-J3ENSCBL
M-L
For HF-SP HA-LP
HC-RP HC-UP
20
30
30
IP67
IP67
Standard
MR- J3ENSCBL
M-H
Long flex
life
HC-LP servo motor
2
5
10
20
(a) Connection of servo amplifier and servo motor
Servo amplifier
MR-J3ENSCBL M-L
MR-J3ENSCBL M-H
2)
Servo motor
HF-SP
CN2
1)
Cable model
1) For CN2 connector
2) For encoder connector
Connector set: 54599-1019(Molex)
In case of 10m or shorter cables
Straight plug: CM10-SP10S-M
Socket contact: CM10-
#22SC(C1)-100
MR-J3ENSCBL M-L Receptacle: 36210-0100PL
Shell kit: 36310-3200-008
(3M)
Crimping tool: 357J-50446
(DDK)
(Note) Signal layout
(Note) Signal layout
Applicable cable AWG20 to 22
2
6
5
10
2
4
6
5
8
7
10
LG
4
8
7
MRR
LG
MRR
In case of 20m or longer cables
Straight plug: CM10-SP10S-M
Socket contact: CM10-
#22SC(C2)-100
or
1
P5
9
BAT
1
3
9
BAT
3
MR
P5 MR
Crimping tool: 357J-50447
(DDK)
View seen from wiring side.
View seen from wiring side.
Applicable cable AWG23 to 28
Note. Keep open the pins shown with
. Especially, pin 10 is provided for
MR-J3ENSCBL M-
H
(Note) Signal layout
manufacturer adjustment. If it is connected with any other pin, the servo
amplifier cannot operate normally.
3
2
1
MRR
MR
7
6
5
4
LG
BAT
10
9
8
SHD
P5
View seen from wiring side
Note. Keep open the pin shown
with an
.
11 - 14
11. OPTIONS AND AUXILIARY EQUIPMENT
(b) Internal wiring diagram
MR-J3ENSCBL2M-L/H
MR-J3ENSCBL5M-L/H
MR-J3ENSCBL10M-L/H
MR-J3ENSCBL20M-L
MR-J3ENSCBL30M-L
MR-J3ENSCBL20M-H
MR-J3ENSCBL30M-H
MR-J3ENSCBL40M-H
MR-J3ENSCBL50M-H
Encoder side
connector
Servo amplifier
side connector
Encoder side
connector
Servo amplifier
side connector
Encoder side
connector
Servo amplifier
side connector
P5
1
2
8
5
P5
LG
LG
1
8
P5
P5
P5
1
2
8
5
P5
2
3
5
1
LG
LG
LG
LG
MR
MRR
BAT
SD
MR
4
2
MRR
BAT
SHD
9
4
MR
3
4
1
2
4
MR
10
Plate
MRR
BAT
SD
MRR
BAT
9
10 SHD
Plate
MR
3
4
9
1
2
4
MR
MRR
BAT
SD
MRR
BAT
10 SHD
Plate
(c) When fabricating the encoder cable
When fabricating the cable, prepare the following parts and tool, and fabricate it according to the wiring
diagram in (b). Refer to section 11.8 for the specifications of the used cable.
Parts/Tool
Description
Connector set
MR- J3SCNS (Option)
Servo amplifier side connector
Receptacle: 36210-0100PL
Shell kit: 536310-3200-008
(3M)
Encoder side connector
Straight plug: CM10-SP10S-M
Socket contact: CM10-#22SC(S1)-100
Applicable wire size: AWG20 or less
Recommended tightening jig: 357J-51456T
(DDK)
Or
Connector set: 54599-1019
(Molex)
11 - 15
11. OPTIONS AND AUXILIARY EQUIPMENT
(5) MR-J3BTCBL03M
This cable is a battery connection cable. Use this cable to retain the current position even if the detector
cable is disconnected from the servo amplifier.
Cable model
Cable length
0.3m
Application
MR-J3BTCBL03M
For HF-MP HF-KP HF-SP HA-LP HC-RP HC-UP HC-LP
servo motor
(a) Connection of servo amplifier and servo motor
Servo amplifier
1)
MR-J3BTCBL03M
2)
(Note)
Encoder cable
Servo motor
CN2
Battery
3)
Note. For the detector cable, refer to (1), (2), (3) and (4) of this section.
Cable model
MR-J3BTCBL03M
1) For CN2 connector
2) Junction connector
3) For battery connector
Receptacle: 36210-0100PL
Plug: 36110-3000FD
Shell kit: 36310-F200-008
(3M)
Connector: DF3-2EP-2C
Contact: DF3-EP2428PCA
(Hirose Denki)
Shell kit: 536310-3200-008
(3M)
Or
Connector set: 54599-1019
(Molex)
11 - 16
11. OPTIONS AND AUXILIARY EQUIPMENT
11.1.3 Motor power supply cables
These cables are motor power supply cables for the HF-MP HF-KP series servo motors. The numerals in the
Cable length field of the table are the symbols entered in the part of the cable model. The cables of the
lengths with the symbols are available.
Refer to section 3.10 when wiring.
Cable length
Protective
structure
Cable model
Flex life
Application
0.3m
2m
5m
10m
10
For HF-MP HF-KP servo motor
Load side lead
For HF-MP HF-KP servo motor
Opposite-to-load side lead
For HF-MP HF-KP servo motor
Load side lead
For HF-MP HF-KP servo motor
Opposite-to-load side lead
For HF-MP HF-KP servo motor
Load side lead
For HF-MP HF-KP servo motor
Opposite-to-load side lead
MR-PWS1CBL M-A1-L
MR-PWS1CBL M-A2-L
MR-PWS1CBL M-A1-H
MR-PWS1CBL M-A2-H
MR-PWS2CBL M-A1-L
MR-PWS2CBL M-A2-L
2
5
IP65
IP65
IP65
IP65
IP55
IP55
Standard
Standard
2
2
2
5
5
5
10
10
10
Long flex
life
Long flex
life
03
03
Standard
Standard
(1) Connection of servo amplifier and servo motor
MR-PWS1CBL M-A1-L
MR-PWS1CBL M-A1-H
MR-PWS2CBL03M-A1-L
1)
Servo amplifier
Servo motor
HF-MP
or
HF-KP
MR-PWS1CBL M-A2-L
MR-PWS1CBL M-A2-H
MR-PWS2CBL03M-A2-L
CNP3 connector
supplied with servo
amplifier
1)
Servo motor
HF-MP
CNP3
HF-KP
Cable model
1) For motor power supply connector
Connector: JN4FT04SJ1-R
Hood, socket insulator
Bushing, ground nut
Contact: ST-TMH-S-C1B-100-(A534G)
Crimping tool: CT160-3-TMH5B
(Japan Aviation Electronics Industry)
MR-PWS1CBL M-A1-L
MR-PWS1CBL M-A2-L
MR-PWS1CBL M-A1-H
MR-PWS1CBL M-A2-H
Signal layout
1
2 U
3 V
Connector: JN4FT04SJ2-R
Hood, socket insulator
4
W
MR-PWS2CBL03M-A1-L
MR-PWS2CBL03M-A2-L
Bushing, ground nut
Contact: ST-TMH-S-C1B-100-(A534G)
Crimping tool: CT160-3-TMH5B
(Japan Aviation Electronics Industry)
View seen from wiring side.
(2) Internal wiring diagram
MR-PWS1CBL M-A1-H MR-PWS1CBL M-A2-H
MR-PWS2CBL03M-A1-L MR-PWS2CBL03M-A2-L
AWG 19 (Red) (Note)
U
V
W
AWG 19 (White)
AWG 19 (Black)
AWG 19 (Green/yellow)
Note. These are not shielded cables.
11 - 17
11. OPTIONS AND AUXILIARY EQUIPMENT
11.1.4 Motor brake cables
These cables are motor brake cables for the HF-MP HF-KP series servo motors. The numerals in the Cable
length field of the table are the symbols entered in the part of the cable model. The cables of the lengths with
the symbols are available.
Refer to section 3.11 when wiring.
Cable length
Protective
structure
Cable model
Flex life
Application
0.3m
2m
5m
10m
10
For HF-MP HF-KP servo motor
Load side lead
For HF-MP HF-KP servo motor
Opposite-to-load side lead
For HF-MP HF-KP servo motor
Load side lead
For HF-MP HF-KP servo motor
Opposite-to-load side lead
For HF-MP HF-KP servo motor
Load side lead
For HF-MP HF-KP servo motor
Opposite-to-load side lead
MR-PWS1CBL M-A1-L
MR-PWS1CBL M-A2-L
MR-PWS1CBL M-A1-H
MR-PWS1CBL M-A2-H
MR-PWS2CBL M-A1-L
MR-PWS2CBL M-A2-L
2
5
IP65
IP65
IP65
IP65
IP55
IP55
Standard
Standard
2
2
2
5
5
5
10
10
10
Long flex
life
Long flex
life
03
03
Standard
Standard
(1) Connection of servo amplifier and servo motor
MR-BKS1CBL M-A1-L
MR-BKS1CBL M-A1-H
MR-BKS2CBL03M-A1-L
1)
Servo motor
HF-MP
HF-KP
24VDC power
supply for
electromagnetic
brake
or
MR-BKS1CBL M-A2-L
MR-BKS1CBL M-A2-H
MR-BKS2CBL03M-A2-L
1)
Servo motor
HF-MP
HF-KP
Cable model
1) For motor brake connector
Connector: JN4FT02SJ1-R
Hood, socket insulator
MR-BKS1CBL M-A1-L
MR-BKS1CBL M-A2-L
MR-BKS1CBL M-A1-H
MR-BKS1CBL M-A2-H
Signal layout
Bushing, ground nut
Contact: ST-TMH-S-C1B-100-(A534G)
Crimping tool: CT160-3-TMH5B
(Japan Aviation Electronics Industry)
Connector: JN4FT02SJ2-R
1 B1
2 B2
View seen from wiring side.
MR-BKS2CBL03M-A1-L
MR-BKS2CBL03M-A2-L
Hood, socket insulator
Bushing, ground nut
Contact: ST-TMH-S-C1B-100-(A534G)
Crimping tool: CT160-3-TMH5B
(Japan Aviation Electronics Industry)
(2) Internal wiring diagram
MR-BKS1CBL M-A1-H
MR-BKS2CBL03M-A1-L
MR-BKS1CBL M-A2-H
MR-BKS2CBL03M-A2-L
(Note)
B1
AWG 20
AWG 20
B2
Note. These are not shielded cables.
11 - 18
11. OPTIONS AND AUXILIARY EQUIPMENT
11.1.5 SSCNET cable
POINT
Do not see directly the light generated from CN1A CN1B connector of servo
amplifier or the end of SSCNET cable. When the light gets into eye, you
may feel something is wrong for eye. (The light source of SSCNET complies
with class1 defined in JIS C6802 or IEC60825-1.)
(1) Model explanations
Numeral in the column of cable length on the table is a symbol put in the part of cable model. Cables of
which symbol exists are available.
Cable length
5m 10m
Application
remark
Cable model
Flex life
0.15m 0.3m
0.5m
05
1m
1
3m
3
20m
30m
40m
50m
Using inside
MR-J3BUS M
015
03
Standard panel standard
cord
Using outside
MR-J3BUS M-A
5
10
20
Standard panel standard
cable
(Note)
Long flex Using long
30
40
50
MR-J3BUS M-B
life
distance cable
Note. For cable of 30m or less, contact our company.
(2) Specifications
Description
SSCNET cable model
SSCNET cable length
Optical
MR-J3BUS M
MR-J3BUS M-A
5 to 20m
MR-J3BUS M-B
30 to 50m
0.15m
0.3 to 3m
Enforced covering cord: 50mm Enforced covering cord: 50mm
Cord: 25mm Cord: 30mm
420N 980N
(Enforced covering cord)
Minimum bend radius
25mm
cable
(cord)
Tension strength
70N
140N
(Enforced covering cord)
-20 to 70
Temperature range
for use (Note)
-40 to 85
Indoors (no direct sunlight)
No solvent or oil
Ambient
4.4 0.1
4.4 0.4
External appearance
[mm]
2.2 0.07
4.4 0.1
6.0 0.2
7.6 0.5
Note. This temperature range for use is the value for optical cable (cord) only. Temperature condition for the connector is the same as
that for servo amplifier.
11 - 19
11. OPTIONS AND AUXILIARY EQUIPMENT
(3) Outline drawings
(a) MR-J3BUS015M
[Unit: mm]
(6.7)
(15)
(13.4)
(37.65)
Protective tube
50
0
150
(20.9)
0
8
(b) MR-J3BUS03M to MR-J3BUS3M
Refer to the table shown in (1) of this section for cable length (L).
[Unit: mm]
Protective tube
(Note)
(100)
(100)
L
Note. Dimension of connector part is the same as that of MR-J3BUS015M.
(c) MR-J3BUS5M-A to MR-J3BUS20M-A MR-J3BUS30M-B to MR-J3BUS50M-B
Refer to the table shown in (1) of this section for cable length (L).
Distortion dimension [mm]
SSCNET cable
A
B
MR-J3BUS5M-A to MR-J3BUS20M-A
MR-J3BUS30M-B to MR-J3BUS50M-B
100
150
30
50
[Unit: mm]
Protective tube
(Note)
(A)
(B)
(B)
(A)
L
Note. Dimension of connector part is the same as that of MR-J3BUS015M.
11 - 20
11. OPTIONS AND AUXILIARY EQUIPMENT
11.2 Regenerative options
The specified combinations of regenerative options and servo amplifiers may only
be used. Otherwise, a fire may occur.
CAUTION
(1) Combination and regenerative power
The power values in the table are resistor-generated powers and not rated powers.
Regenerative power[W]
Built-in
(Note 1)
MR-RB50
[13 ]
(Note 1)
MR-MB51
[6.7 ]
Servo amplifier
MR-RB032
[40 ]
MR-RB12
[40 ]
MR-RB30
[13 ]
MR-RB31
[6.7 ]
MR-RB32
[40 ]
regenerative
resistor
MR-J3-10B (1)
MR-J3-20B (1)
MR-J3-40B (1)
MR-J3-60B
30
30
30
30
30
30
10
10
100
100
100
100
100
10
MR-J3-70B
20
300
300
MR-J3-100B
MR-J3-200B
MR-J3-350B
MR-J3-500B
MR-J3-700B
20
100
100
130
170
300
300
500
500
300
300
500
500
Regenerative power[W]
(Note 1) (Note 1) (Note 1)
Built-in
(Note 1)
(Note 1)
Servo amplifier
MR-RB1H-4
[82 ]
regenerative
resistor
MR-RB3M-4 MR-RB3G-4 MR-RB5G-4 MR-RB34-4 MR-RB54-4
[120 ]
300
[47 ]
[47 ]
[26 ]
[26 ]
MR-J3-60B4
MR-J3-100B4
MR-J3-200B4
MR-J3-350B4
MR-J3-500B4
MR-J3-700B4
15
15
100
100
300
100
100
130
170
300
300
500
500
300
300
500
500
(Note 2) Regenerative power[W]
Servo amplifier
External regenerative
resistor (Accessory)
MR-RB5E
[6 ]
MR-RB9P
[4.5 ]
MR-RB9F
[3 ]
MR-RB6B-4 MR-RB60-4 MR-RB6K-4
[20 ]
[12.5 ]
[10 ]
MR-J3-11KB
MR-J3-15KB
MR-J3-22KB
MR-J3-11KB4
MR-J3-15KB4
MR-J3-22KB4
500 (800)
850 (1300)
850 (1300)
500 (800)
850 (1300)
850 (1300)
500 (800)
850 (1300)
850 (1300)
500 (800)
850 (1300)
850 (1300)
Note 1. Always install a cooling fan.
2. Values in parentheses assume the installation of a cooling fan.
11 - 21
11. OPTIONS AND AUXILIARY EQUIPMENT
(2) Selection of the regenerative option
Use the following method when regeneration occurs continuously in vertical motion applications or when it
is desired to make an in-depth selection of the regenerative option.
(a) Regenerative energy calculation
Use the following table to calculate the regenerative energy.
tf(1 cycle)
No
Up
Time
Down
M
t1
Tpsa1
t2
t3
t4
Tpsd1
Tpsa2
Tpsd2
Friction
torque
1)
( )
(Driving)
2)
TF
4)
8)
5)
TU
6)
3)
7)
(Regenerative)
( )
Formulas for calculating torque and energy in operation
Torque applied to servo motor [N m]
Regenerative power
Energy [J]
0.1047
2
(JL JM)
1
Tpsa1
N0
E1
N0 T1 Tpsa1
T1
TU
TF
1)
2)
104
9.55
T2 TU TF
E2 0.1047 N0 T2 t1
(JL JM)
N0
9.55 104
0.1047
2
1
E3
N0 T3 Tpsd1
T3
TU
TF
3)
Tpsd1
T4 TU
E4 0 (No regeneration)
0.1047
4), 8)
5)
(JL JM)
1
Tpsa2
N0
E5
N0 T5 Tpsa2
T5
T6
T7
TU TF
9.55 104
TU TF
2
E6 0.1047 N0 T6 t3
0.1047
6)
(JL JM)
1
N0
N0
E7
T7 Tpsd2
TU TF
7)
9.55 104
2
Tpsd2
From the calculation results in 1) to 8), find the absolute value (Es) of the sum total of negative energies.
11 - 22
11. OPTIONS AND AUXILIARY EQUIPMENT
(b) Losses of servo motor and servo amplifier in regenerative mode
The following table lists the efficiencies and other data of the servo motor and servo amplifier in the
regenerative mode.
Servo amplifier Inverse efficiency[%] Capacitor charging[J]
Servo amplifier Inverse efficiency[%] Capacitor charging[J]
MR-J3-10B
MR-J3-10B1
MR-J3-20B
MR-J3-20B1
MR-J3-40B
MR-J3-40B1
MR-J3-60B(4)
MR-J3-70B
MR-J3-100B
MR-J3-100B4
55
55
70
70
85
85
85
80
80
80
9
MR-J3-200B
85
85
85
85
90
90
90
90
90
40
25
4
MR-J3-200B4
MR-J3-350B
9
40
4
MR-J3-350B4
MR-J3-500B(4)
MR-J3-700B(4)
MR-J3-11KB(4)
MR-J3-15KB(4)
MR-J3-22KB(4)
36
11
10
11
18
18
12
45
70
120
170
250
Inverse efficiency ( ) : Efficiency including some efficiencies of the servo motor and servo amplifier
when rated (regenerative) torque is generated at rated speed. Since the
efficiency varies with the speed and generated torque, allow for about 10%.
Capacitor charging (Ec) : Energy charged into the electrolytic capacitor in the servo amplifier.
Subtract the capacitor charging from the result of multiplying the sum total of regenerative energies by
the inverse efficiency to calculate the energy consumed by the regenerative option.
ER [J]
Es Ec
Calculate the power consumption of the regenerative option on the basis of single-cycle operation
period tf [s] to select the necessary regenerative option.
PR [W] ER/tf
(3) Parameter setting
Set parameter No.PA02 according to the option to be used.
Parameter No.PA02
0 0
Selection of regenerative option
00: Regenerative option is not used
For servo amplifier of 100W, regenerative resistor is not used.
For servo amplifier of 200 to 7kW, built-in regenerative resistor is used.
Supplied regenerative resistors or regenerative option is used with
the servo amplifier of 11k to 22kW.
For a drive unit of 30kW or more, select regenerative option by the
converter unit.
01: FR-BU2-(H) FR-RC-(H) FR-CV-(H)
02: MR-RB032
03: MR-RB12
04: MR-RB32
05: MR-RB30
06: MR-RB50(Cooling fan is required)
08: MR-RB31
09: MR-RB51(Cooling fan is required)
80: MR-RB1H-4
81: MR-RB3M-4(Cooling fan is required)
82: MR-RB3G-4(Cooling fan is required)
83: MR-RB5G-4(Cooling fanis required)
84: MR-RB34-4(Cooling fanis required)
85: MR-RB54-4(Cooling fanis required)
FA: Whenhe supplied regenerative resistor is cooled by the cooling fan to
increase the ability with the servo amplifier of 11k to 22kW.
11 - 23
11. OPTIONS AND AUXILIARY EQUIPMENT
The following are setting values for regenerative resistor and regenerative option which are used with a
servo amplifier of 11k to 22kW.
Setting
Regenerative resistor, regenerative option
value
Standard supplied regenerative resistor
Standard supplied regenerative resistor
(with a cooling fan to cool it)
MR-RB5E
00
FA
00
FA
00
FA
00
FA
00
00
FA
00
FA
00
MR-RB5E (with a cooling fan to cool it)
MR-RB9P
MR-RB9P (with a cooling fan to cool it)
MR-RB9F
MR-RB9F (with a cooling fan to cool it)
MR-RB6B-4
MR-RB6B-4 (with a cooling fan to cool it)
MR-RB60-4
MR-RB60-4 (with a cooling fan to cool it)
MR-RB6K-4
MR-RB6K-4 (with a cooling fan to cool it)
(4) Connection of the regenerative option
POINT
When the MR-RB50 MR-RB51 MR-RB3M-4 MR-RB3G-4 MR-RB5G-4
MR-RB34-4 MR-RB54-4 is used, a cooling fan is required to cool it.
The cooling fan should be prepared by the customer.
For the sizes of wires used for wiring, refer to section 11.11.
The regenerative option will cause a temperature rise of 100 relative to the ambient temperature. Fully
examine heat dissipation, installation position, used cables, etc. before installing the option. For wiring, use
flame-resistant wires and keep them clear of the regenerative option body. Always use twisted cables of
max. 5m length for connection with the servo amplifier.
11 - 24
11. OPTIONS AND AUXILIARY EQUIPMENT
(a) MR-J3-350B or less MR-J3-200B4 or less
Always remove the wiring from across P-D and fit the regenerative option across P-C.
The G3 and G4 terminals act as a thermal sensor. G3-G4 is disconnected when the regenerative option
overheats abnormally.
Always remove the lead from across P-D.
Servo amplifier
Regenerative option
P
P
C
D
C
G3
(Note 2)
5m max.
G4
(Note 1)
Cooling fan
Note 1. When using the MR-RB50 MR-RB3M-4 MR-RB3G-4 MR-RB5G-4, forcibly cool it with a cooling fan (92 92, minimum air
flow : 1.0m3).
2. Make up a sequence which will switch off the magnetic contactor (MC) when abnormal heating occurs.
G3-G4 contact specifications
Maximum voltage: 120V AC/DC
Maximum current: 0.5A/4.8VDC
Maximum capacity: 2.4VA
For the MR-RB50 MR-RB3M-4 MR-RB3G-4 MR-RB5G-4 install the cooling fan as shown.
[Unit : mm]
Cooling fan installation screw hole dimensions
2-M3 screw hole
Top
(for cooling fan installation)
Depth 10 or less
(Screw hole already
machined)
Cooling fan
Terminal block
Thermal relay
Bottom
82.5
40
Installation surface
Horizontal installation
Vertical
installation
11 - 25
11. OPTIONS AND AUXILIARY EQUIPMENT
(b) MR-J3-350B4 MR-J3-500B(4) MR-J3-700B(4)
Always remove the wiring (across P-C) of the servo amplifier built-in regenerative resistor and fit the
regenerative option across P-C.
The G3 and G4 terminals act as a thermal sensor. G3-G4 is opened when the regenerative option
overheats abnormally.
Always remove wiring (across P-C) of servo
amplifier built-in regenerative resistor.
Servo amplifier
Regenerative option
P
P
C
C
G3
(Note 2)
5m or less
G4
Cooling fan(Note 1)
Note 1. When using the MR-RB51 MR-RB3G-4 MR-RB5G-4 MR-RB34-4 MR-RB54-4, forcibly
cool it with a cooling fan (92 92, minimum air flow : 1.0m3).
2. Make up a sequence which will switch off the magnetic contactor (MC) when abnormal heating
occurs.
G3-G4 contact specifications
Maximum voltage: 120V AC/DC
Maximum current: 0.5A/4.8VDC
Maximum capacity: 2.4VA
When using the regenerative resistor option, remove the servo amplifier's built-in regenerative resistor
terminals (across P-C), fit them back to back, and secure them to the frame with the accessory screw as
shown below.
Mounting method
Accessory screw
11 - 26
11. OPTIONS AND AUXILIARY EQUIPMENT
The drawing below shows the MR-J3-350B4 MR-J3-500B(4). Refer to section 9.1 (6) outline drawings
for the position of the fixing screw for MR-J3-700B(4).
Built-in regenerative resistor
lead terminal fixing screw
For the MR-RB51, MR-RB3G-4, MR-RB5G-4, MR-RB34-4 or MR-RB54-4 install the cooling fan as
shown.
[Unit : mm]
Cooling fan installation screw hole dimensions
2-M3 screw hole
Top
(for cooling fan installation)
Depth 10 or less
(Screw hole already
machined)
Cooling fan
Terminal block
Thermal relay
Bottom
82.5
40
Installation surface
Horizontal installation
Vertical
installation
11 - 27
11. OPTIONS AND AUXILIARY EQUIPMENT
(c) MR-J3-11KB(4) to MR-J3-22KB(4) (when using the supplied regenerative resistor)
When using the regenerative resistors supplied to the servo amplifier, the specified number of resistors
(4 or 5 resistors) must be connected in series. If they are connected in parallel or in less than the
specified number, the servo amplifier may become faulty and/or the regenerative resistors burn. Install
the resistors at intervals of about 70mm. Cooling the resistors with two cooling fans (92 92, minimum
air flow : 1.0m3) improves the regeneration capability. In this case, set "
FA" in parameter No.PA02.
5m or less
Do not remove
Servo amplifier
the short bar.
P1
P
C
(Note) Series connection
Cooling fan
Note. The number of resistors connected in series depends on the resistor type. The thermal sensor is not mounted on the
attached regenerative resistor. An abnormal heating of resistor may be generated at a regenerative circuit failure. Install a
thermal sensor near the resistor and establish a protective circuit to shut off the main circuit power supply when abnormal
heating occurs. The detection level of the thermal sensor varies according to the settings of the resistor. Set the thermal
sensor in the most appropriate position on your design basis or use the thermal sensor built-in regenerative option (MR-
RB5E, 9P, 9F, 6B-4, 60-4 and 6K-4) provided by Mitsubishi Electric Corporation.
Regenerative
resistor
Regenerative power [W] Resistance
Number of
resistors
Servo amplifier
[ ]
Normal
500
Cooling
800
MR-J3-11KB
MR-J3-15KB
MR-J3-22KB
MR-J3-11KB4
MR-J3-15KB4
MR-J3-22KB4
GRZG400-1.5
GRZG400-0.9
GRZG400-0.6
GRZG400-5.0
GRZG400-2.5
GRZG400-2.0
6
4.5
3
4
5
5
4
5
5
850
1300
1300
800
850
500
20
850
1300
1300
12.5
10
850
11 - 28
11. OPTIONS AND AUXILIARY EQUIPMENT
(d) MR-J3-11KB(4)-PX to MR-J3-22KB(4)-PX (when using the regenerative option)
The MR-J3-11KB(4)-PX to MR-J3-22KB(4)-PX servo amplifiers are not supplied with regenerative
resistors. When using any of these servo amplifiers, always use the MR-RB5E, 9P, 9F, 6B-4, 60-4 and
6K-4 regenerative option.
The MR-RB5E, 9P, 9F, 6B-4, 60-4 and 6K-4 are regenerative options that have encased the GRZG400-
1.5 , GRZG400-0.9 , GRZG400-0.6 , GRZG400-5.0 , GRZG400-2.5 , GRZG400-2.0 respectively.
When using any of these regenerative options, make the same parameter setting as when using the
GRZG400-1.5 , GRZG400-0.9 , GRZG400-0.6 , GRZG400-5.0 , GRZG400-2.5 , GRZG400-2.0
(supplied regenerative resistors or regenerative option is used with 11kW or more servo amplifier).
Cooling the regenerative option with cooling fans improves regenerative capability.
The G3 and G4 terminals are for the thermal protector. G3-G4 is opened when the regenerative option
overheats abnormally.
Servo amplifier
Do not remove
Regenerative option
the short bar.
P1
P
C
P
C
G3
G4
(Note)
Configure up a circuit which
shuts off main circuit power
when thermal protector operates.
Note. Specifications of contact across G3-G4
Maximum voltage : 120V AC/DC
Maximum current : 0.5A/4.8VDC
Maximum capacity : 2.4VA
Regenerative power [W]
Regenerative option
Servo amplifier
model
Resistance [ ]
Without
With
cooling fans
cooling fans
MR-J3-11KB-PX
MR-J3-15KB-PX
MR-J3-22KB-PX
MR-J3-11KB4-PX
MR-J3-15KB4-PX
MR-J3-22KB4-PX
MR-RB5E
MR-RB9P
6
4.5
3
500
850
850
500
850
850
800
1300
1300
800
MR-RB9F
MR-RB6B-4
MR-RB60-4
MR-RB6K-4
20
12.5
10
1300
1300
When using cooling fans, install them using the mounting holes provided in the bottom of the
regenerative option. In this case, set "
FA" in parameter No.PA02.
Top
MR-RB5E 9P 9F 6B-4 60-4 6K-4
Bottom
TE1
2 cooling fans
(92 92, minimum air flow: 1.0m3)
TE
G4 G3 C
P
Mounting screw
4-M3
11 - 29
11. OPTIONS AND AUXILIARY EQUIPMENT
(5) Outline drawing
(a) MR-RB032 MR-RB12
[Unit: mm (in)]
TE1
Terminal block
G3
G4
P
6 mounting hole
LA
LB
C
Terminal screw: M3
Tightening torque: 0.5 to 0.6 [N m]
(4 to 5 [lb in])
MR-RB
Mounting screw
Screw size: M5
Tightening torque: 3.24 [N m]
(28.7 [lb in])
5
G3
G4
P
TE1
C
1.6
6
Approx. 20
LD
LC
Regenerative
Variable dimensions
Mass
option
LA
LB
LC
LD
[kg] [lb]
MR-RB032
MR-RB12
30
40
15
15
119
169
99
0.5 1.1
1.1 2.4
149
11 - 30
11. OPTIONS AND AUXILIARY EQUIPMENT
(b) MR-RB30 MR-RB31 MR-RB32 MR-RB34-4 MR-RB3M-4 MR-RB3G-4
[Unit: mm (in)]
TE1
Terminal block
Cooling fan mounting
screw (2-M4 screw)
P
C
G3
G4
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.62 [lb in])
Mounting screw
Screw size: M6
7
101.5
82.5
318
10
90
Tightening torque: 5.4 [N m] (47.79 [lb in])
A
100
B
Variable
Wind blows in the
arrow direction
Regenerative
option
Mass
dimensions
[kg] (Ib)
A
B
MR-RB30
MR-RB31
17
335
MR-RB32
2.9 (6.4)
MR-RB34-4
MR-RB3M-4
MR-RB3G-4
23
341
(c) MR-RB50 MR-RB51 MR-RB54-4 MR-RB5G-4
[Unit: mm (in)]
Terminal block
Cooling fan mounting
screw (2-M3 screw)
On opposite side
P
C
G3
G4
49
82.5
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.62 [lb in])
Mounting screw
Screw size: M6
7 14
slot
Tightening torque: 5.4 [N m] (47.79 [lb in])
Variable
Wind blows
in the arrow
direction
Regenerative
option
Mass
dimensions
[kg] (Ib)
A
B
MR-RB50
MR-RB51
17
217
5.6 (12.3)
MR-RB54-4
MR-RB5G-4
23
233
2.3
7
200
B
A
12
108
120
(30)
8
11 - 31
11. OPTIONS AND AUXILIARY EQUIPMENT
(d) MR-RB5E MR-RB9P MR-RB9F MR-RB6B-4 MR-RB60-4 MR-RB6K-4
[Unit: mm (in)]
Terminal block
2- 10
mounting hole
G4 G3 C
P
Terminal screw: M5
Tightening torque: 2.0 [N m] (17.70 [lb in])
Mounting screw
Screw size: M8
Tightening torque: 13.2 [N m] (116.83 [lb in])
Regenerative
option
Mass
[kg]
10
11
11
10
11
11
[Ib]
MR-RB5E
MR-RB9P
22.0
24.3
24.3
22.0
24.3
24.3
TE1
G4 G3 C P
MR-RB9F
10
2.3
15
230
260
230
MR-RB6B-4
MR-RB60-4
MR-RB6K-4
215
Cooling fan mounting screw
4-M3 screw
82.5 82.5
(e) GRZG400-1.5
GRZG400-0.9
GRZG400-0.6
GRZG400-5.0
GRZG400-2.5
GRZG400-
2.0 (standard accessories)
Approx.
10
C
Variable
Tightening
Approx. A
Approx. 2.4
Regenerative
brake
Mounting
Mass [kg]
([lb])
dimensions
torque
[N m]
([lb in])
screw size
A
C
K
GRZG400-1.5
GRZG400-0.9
GRZG400-0.6
GRZG400-5.0
GRZG400-2.5
GRZG400-2.0
10
16
5.5
8.2
39
46
Approx. 330
385
9.5
40
13.2
0.8
(1.76)
411
M8
(116.83)
Approx. 47
10
5.5
39
11 - 32
11. OPTIONS AND AUXILIARY EQUIPMENT
(f) MR-RB1H-4
[Unit: mm (in)]
Terminal screw: M3
Tightening torque: 0.5 to 0.6 [N m]
(4.43 to 5.31 [lb in])
40
36
G3
G4
P
15
6 mounting hole
C
Mounting screw
Screw size: M5
Tightening torque: 3.24 [N m]
(28.32 [lb in])
Regenerative
Mass [kg] ([lb])
option
MR-RB1H-4
1.1 (2.4)
TE1
2
6
6
Approx. 24
149
173
11 - 33
11. OPTIONS AND AUXILIARY EQUIPMENT
11.3 FR-BU2-(H) Brake unit
POINT
Use a 200V class brake unit and a resistor unit with a 200V class servo
amplifier, and a 400V class brake unit and a resistor unit with a 400V class
servo amplifier. Combination of different voltage class units and servo
amplifier cannot be used.
Install a brake unit and a resistor unit on a flat surface vertically. When the
unit is installed horizontally or diagonally, the heat dissipation effect
diminishes.
Temperature of the resistor unit case rises to higher than 100 . Keep cables
and flammable materials away from the case.
Ambient temperature condition of the brake unit is between 10 (14 ) and
50 (122 ). Note that the condition is different from the ambient
temperature condition of the servo amplifier (between 0 (32 ) and 55
(131 )).
Configure the circuit to shut down the power-supply with the alarm output of
the brake unit and resistor unit under abnormal condition.
Use the brake unit with a combination indicated in section 11.3.1.
For executing a continuous regenerative operation, use FR-RC-(H) power
regeneration converter or FR-CV-(H) power regeneration common converter.
Brake unit and regenerative options (Regenerative resistor) cannot be used
simultaneously.
Connect the brake unit to the bus of the servo amplifier. As compared to the MR-RB regenerative option, the
brake unit can return larger power. Use the brake unit when the regenerative option cannot provide sufficient
regenerative capability.
When using the brake unit, set the parameter No.PA02 of the servo amplifier to "
01".
When using the brake unit, always refer to the FR-BU2-(H) Brake Unit Instruction Manual.
11 - 34
11. OPTIONS AND AUXILIARY EQUIPMENT
11.3.1 Selection
Use a combination of servo amplifier, brake unit and resistor unit listed below.
Number of
connected
units
Permissible
continuous
power [kW]
Total
Applicable servo
amplifier
Brake unit
Resistor unit
resistance
[
]
200V FR-BU2-15K
class
FR-BR-15K
1
0.99
1.98
8
4
MR-J3-500B (Note)
MR-J3-500B
MR-J3-700B
MR-J3-11KB
MR-J3-15KB
MR-J3-500B
MR-J3-700B
MR-J3-11KB
MR-J3-15KB
MR-J3-11KB
MR-J3-15KB
MR-J3-22KB
MR-J3-22KB
MR-J3-500B4
MR-J3-700B4
MR-J3-11KB4
MR-J3-11KB4
MR-J3-15KB4
MR-J3-22KB4
MR-J3-22KB4
2 (parallel)
FR-BU2-30K
FR-BU2-55K
FR-BR-30K
FR-BR-55K
1
1
1.99
3.91
4
2
2
MT-BR5-55K
FR-BR-H30K
1
1
5.5
400V FR-BU2-H30K
class
1.99
16
FR-BU2-H55K
FR-BR-H55K
1
1
3.91
7.5
8
FR-BU2-H75K
MT-BR5-H75K
6.5
11.3.2 Brake unit parameter setting
Normally, when using the FR-BU2-(H), changing parameters is not necessary. Whether a parameter can be
changed or not is listed below.
Parameter
Name
Change
possible/
impossible
Remarks
No.
0
1
Brake mode switchover
Impossible
Possible
Do not change the parameter.
Refer to the FR-BU2-(H) Brake Unit
Instruction Manual.
Monitor display data selection
2
3
Input terminal function selection 1
Input terminal function selection 2
Parameter write selection
Impossible
Do not change the parameter.
77
78
Cumulative energization time
carrying-over times
CLr Parameter clear
ECL Alarm history clear
C1
For manufacturer setting
11 - 35
11. OPTIONS AND AUXILIARY EQUIPMENT
11.3.3 Connection example
POINT
Connecting PR terminal of the brake unit to P terminal of the servo amplifier
results in brake unit malfunction. Always connect the PR terminal of the brake
unit to the PR terminal of the resistor unit.
(1) Combination with FR-BR-(H) resistor unit
(a) When connecting a brake unit to a servo amplifier
(Note 8) Servo motor
thermal relay
RA2
Controller
forced stop
RA3
ON
MC
EM1
OFF
MC
SK
ALM
RA1
(Note 5)
Servo amplifier
CN3
NFB
MC
20 EM1
L1
L2
L3
(Note 1)
Power
supply
DOCOM
3
24VDC
RA1
FR-BR-(H)
(Note 6)
DICOM
10
TH1
TH2
15 ALM
P
L11
PR
L21
P1
(Note 3)
FR-BU2-(H)
P2
PR
P/
MSG
P(
N(
)
SD
A
(Note 4)
(Note 9)
N/
B
C
)
C
BUE
SD
(Note 10)
(Note 7)
(Note 2)
Note 1. For power supply specifications, refer to section 1.3.
2. For the servo amplifier of 5k and 7kW, always disconnect the lead of built-in regenerative resistor, which is connected to the P
and C terminals. For the servo amplifier of 11k to 22kW, do not connect a supplied regenerative resistor to the P and C
terminals.
3. Always connect P1 and P2 terminals (P1 and P for the servo amplifier of 11k to 22kW) (Factory-wired). When using the power
factor improving DC reactor, refer to section 11.13.
4. Connect the P/ and N/ terminals of the brake unit to a correct destination. Wrong connection results in servo amplifier and
brake unit malfunction.
5. For 400VAC class, a step-down transformer is required.
6. Contact rating: 1b contact, 110VAC_5A/220VAC_3A
Normal condition: TH1-TH2 is conducting. Abnormal condition: TH1-TH2 is not conducting.
7. Contact rating: 230VAC_0.3A/30VDC_0.3A
Normal condition: B-C is conducting/A-C is not conducting. Abnormal condition: B-C is not conducting/A-C is conducting.
8. For the servo amplifier of 11kW or more, connect the thermal relay censor of the servo amplifier.
9. Do not connect more than one cable to each P( ) to N( ) terminals of the servo amplifier.
10. Always connect BUE and SD terminals (Factory-wired).
11 - 36
11. OPTIONS AND AUXILIARY EQUIPMENT
(b) When connecting two brake units to a servo amplifier
POINT
To use brake units with a parallel connection, use two sets of FR-BU2 brake
unit. Combination with other brake unit results in alarm occurrence or
malfunction.
Always connect the master and slave terminals (MSG and SD) of the two
brake units.
Do not connect the servo amplifier and brake units as below. Connect the
cables with a terminal block to distribute as indicated in this section.
Servo amplifier
Brake unit
Servo amplifier
Brake unit
P (
N (
)
)
P/
N/
P (
N (
)
)
P/
N/
Brake unit
Brake unit
P/
N/
P/
N/
Connecting two cables to
P and N terminals
Passing wiring
11 - 37
11. OPTIONS AND AUXILIARY EQUIPMENT
(Note 7) Servo motor
thermal relay
RA2
Controller
forced stop
RA3
ON
MC
OFF
EM1
MC
SK
ALM
RA1
Servo amplifier
CN3
NFB
MC
(Note 1)
Power
supply
20 EM1
L1
L2
L3
DOCOM
3
24VDC
RA1
FR-BR
(Note 5)
DICOM
10
TH1
TH2
15 ALM
P
L11
PR
L21
P1
(Note 3)
FR-BU2-(H)
P2
(Note 11)
PR
P/
MSG
(Note 10)
(Note 4)
P
SD
A
(Note 8)
N/
B
C
BUE
N
C
(Note 6)
(Note 9)
SD
Terminal
block
(Note 2)
FR-BR
(Note 5)
TH1
TH2
P
PR
FR-BU2-(H)
PR
P/
MSG
(Note 10)
(Note 4)
SD
A
N/
B
C
BUE
(Note 9)
(Note 6)
SD
Note 1. For power supply specifications, refer to section 1.3.
2. For the servo amplifier of 5k and 7kW, always disconnect the lead of built-in regenerative resistor, which is connected to the P
and C terminals. For the servo amplifier of 11k and 15kW, do not connect a supplied regenerative resistor to the P and C
terminals.
3. Always connect P1 and P2 terminals (P1 and P for the servo amplifier of 11k and 15kW) (Factory-wired). When using the power
factor improving DC reactor, refer to section 11.13.
4. Connect the P/ and N/ terminals of the brake unit to a correct destination. Wrong connection results in servo amplifier and
brake unit malfunction.
5. Contact rating: 1b contact, 110VAC_5A/220VAC_3A
Normal condition: TH1-TH2 is conducting. Abnormal condition: TH1-TH2 is not conducting.
6. Contact rating: 230VAC_0.3A/30VDC_0.3A
Normal condition: B-C is conducting/A-C is not conducting. Abnormal condition: B-C is not conducting/A-C is conducting.
7. For the servo amplifier of 11kW or more, connect the thermal relay censor of the servo amplifier.
8. Do not connect more than one cable to each P and N terminals of the servo amplifier.
9. Always connect BUE and SD terminals (Factory-wired).
10. Connect the MSG and SD terminals of the brake unit to a correct destination. Wrong connection results in servo amplifier and
brake unit malfunction.
11. For the cable to connect the terminal block and the P and N terminals of the servo amplifier, use the cable indicated in (4) (b) of
this section.
11 - 38
11. OPTIONS AND AUXILIARY EQUIPMENT
(2) Combination with MT-BR5-(H) resistor unit
Servo motor
thermal relay
RA2
Controller
forced stop
RA3
ON
MC
OFF
EM1
RA4
MC
SK
ALM
RA1
(Note 4)
NFB
Servo amplifier
CN3
MC
(Note 1)
Power
supply
20 EM1
L1
L2
L3
DOCOM
3
SK
24VDC
RA1
MT-BR5-(H)
(Note 5)
DICOM
10
TH1
TH2
15 ALM
P
RA4
L11
PR
L21
FR-BU2-(H)
C
P1
)
(Note 9)
(Note 2)
PR
P/
MSG
P(
(Note 7)
N(
SD
A
(Note 3)
N/
B
)
C
BUE
(Note 8)
(Note 6)
SD
Note 1. For power supply specifications, refer to section 1.3.
2. Always connect P1 - P( ) terminals (Factory-wired). When using the power factor improving DC reactor, refer to section 11.13.
3. Connect the P/ and N/ terminals of the brake unit to a correct destination. Wrong connection results in servo amplifier and
brake unit malfunction.
4. For the servo amplifier of 400V class, a step-down transformer is required.
5. Contact rating: 1a contact, 110VAC_5A/220VAC_3A
Normal condition: TH1-TH2 is not conducting. Abnormal condition: TH1-TH2 is conducting.
6. Contact rating: 230VAC_0.3A/30VDC_0.3A
Normal condition: B-C is conducting/A-C is not conducting. Abnormal condition: B-C is not conducting/A-C is conducting.
7. Do not connect more than one cable to each P and N terminals of the servo amplifier.
8. Always connect BUE and SD terminals (Factory-wired).
9. For the servo amplifier of 22kW, do not connect a supplied regenerative resistor to the P and C terminals.
11 - 39
11. OPTIONS AND AUXILIARY EQUIPMENT
(3) Precautions for wiring
The cables between the servo amplifier and the brake unit, and between the resistor unit and the brake unit
should be as short as possible. Always twist the cable longer than 5m (twist five times or more per one
meter). Even when the cable is twisted, the cable should be less than 10m. Using cables longer than 5m
without twisting or twisted cables longer than 10m, may result in the brake unit malfunction.
Servo amplifier
Servo amplifier
Brake unit
Resistor unit
Brake unit
Resistor unit
Twist
Twist
P(
N(
)
)
P
N
P
PR
P
PR
P(
N(
)
)
P
N
P
PR
P
PR
5m or less
5m or less
10m or less
10m or less
(4) Cables
(a) Cables for the brake unit
For the brake unit, HIV wire (600V Grade heat-resistant polyvinyl chloride insulated wire) is
recommended.
1) Main circuit terminal
Main
circuit
terminal
screw
size
Crimping
terminal
Wire size
N/ , P/ , PR,
Tightening
torque
Brake unit
N/ , P/
PR,
,
HIV wire [mm2]
AWG
200V FR-BU2-15K
class FR-BU2-30K
FR-BU2-55K
M4
M5
M6
M4
M5
M6
5.5-4
5.5-5
14-6
5.5-4
5.5-5
14-6
1.5
2.5
4.4
1.5
2.5
4.4
3.5
5.5
14
12
10
6
N/
P/
PR
400V FR-BU2-H30K
class FR-BU2-H55K
FR-BU2-H75K
3.5
5.5
14
12
10
6
Terminal block
11 - 40
11. OPTIONS AND AUXILIARY EQUIPMENT
2) Control circuit terminal
POINT
Undertightening can cause a cable disconnection or malfunction.
Overtightening can cause a short circuit or malfunction due to damage to the
screw or the brake unit.
Sheath
RES
MSG MSG
SD
SD SD
Core
BUE
PC
SD
Jumper
A
B
C
6mm
Terminal block
Wire the stripped cable after twisting to prevent the cable
from becoming loose. In addition, do not solder it.
Screw size: M3
Tightening torque: 0.5N m to 0.6N
m
Wire size: 0.3mm2 to 0.75 mm2
Screw driver: Small flat-blade screwdriver
(Tip thickness: 0.4mm/Tip width 2.5mm)
(b) Cables for connecting the servo amplifier and a distribution terminal block when connecting two sets of
the brake unit
Wire size
Brake unit
HIV wire [mm2]
8
AWG
8
FR-BU2-15K
11 - 41
11. OPTIONS AND AUXILIARY EQUIPMENT
(5) Crimping terminals for P and N terminals of servo amplifier
(a) Recommended crimping terminals
POINT
Always use recommended crimping terminals or equivalent since some
crimping terminals cannot be installed depending on the size.
Number of
(Note 1)
Applicable
tool
Servo amplifier
Brake unit
connected
units
Crimping terminal (Manufacturer)
200V MR-J3-500B
class
FR-BU2-15K
1
2
FVD5.5-S4(Japan Solderless Terminal)
c
8-4NS(Japan Solderless Terminal)
(Note 2)
d
FR-BU2-30K
FR-BU2-15K
1
2
FVD5.5-S4(Japan Solderless Terminal)
8-4NS(Japan Solderless Terminal)
(Note 2)
c
MR-J3-700B
MR-J3-11KB
MR-J3-15KB
MR-J3-22KB
d
FR-BU2-30K
FR-BU2-15K
FR-BU2-30K
FR-BU2-55K
FR-BU2-15K
FR-BU2-30K
FR-BU2-55K
FR-BU2-55K
FR-BU2-H30K
FR-BU2-H30K
FR-BU2-H30K
FR-BU2-H55K
FR-BU2-H55K
FR-BU2-H55K
FR-BU2-H75K
1
2
1
1
2
1
1
1
1
1
1
1
1
1
1
FVD5.5-S4(Japan Solderless Terminal)
FVD8-6(Japan Solderless Terminal)
FVD5.5-6(Japan Solderless Terminal)
FVD14-6(Japan Solderless Terminal)
FVD8-6(Japan Solderless Terminal)
FVD5.5-6(Japan Solderless Terminal)
FVD14-6(Japan Solderless Terminal)
FVD14-8(Japan Solderless Terminal)
c
a
c
b
a
c
b
b
c
c
c
c
c
c
b
400V MR-J3-500B4
class MR-J3-700B4
MR-J3-11KB4
FVD5.5-S4(Japan Solderless Terminal)
FVD5.5-S4(Japan Solderless Terminal)
FVD5.5-6(Japan Solderless Terminal)
FVD5.5-6(Japan Solderless Terminal)
FVD5.5-6(Japan Solderless Terminal)
FVD5.5-8(Japan Solderless Terminal)
FVD14-8(Japan Solderless Terminal)
MR-J3-15KB4
MR-J3-22KB4
Note 1. Symbols in the applicable tool field indicate applicable tools in (5)(b) of this section.
2. Coat the crimping part with an insulation tube.
(b) Applicable tool
Servo amplifier side crimping terminals
Symbol
Crimping
terminal
Applicable tool
Head
Manufacturer
Body
Dice
a
b
FVD8-6
YF-1 E-4
YNE-38
DH-111 DH121
FVD14-6
FVD14-8
FDV5.5-S4
FDV5.5-6
8-4NS
YF-1 E-4
YNE-38
DH-112 DH122
Japan Solderless
Terminal
c
YNT-1210S
YHT-8S
d
11 - 42
11. OPTIONS AND AUXILIARY EQUIPMENT
11.3.4 Outline dimension drawings
(1) FR-BU2- (H) brake unit
[Unit: mm]
FR-BU2-15K
5 hole
(Screw size: M4)
Rating
plate
4
5
18.5
6
56
68
6
52
62
132.5
FR-BU2-30K
FR-BU2-H30K
2- 5 hole
(Screw size: M4)
Rating
plate
5
5
96
6
6
18.5
52
59
108
129.5
FR-BU2-55K
FR-BU2-H55K, H75K
2- 5 hole
(Screw size: M4)
Rating
plate
5
5
18.5
6
158
170
6
52
72
142.5
11 - 43
11. OPTIONS AND AUXILIARY EQUIPMENT
(2) FR-BR- (H) resistor unit
[Unit: mm]
2-
C
(Note)
Control circuit
terminal
(Note)
Main circuit
terminal
C
C
Approx. 35
Approx. 35
W1
1
For FR-BR-55K/FR-BR-H55K, a hanging bolt
is placed on two locations (Indicated below).
Hanging bolt
204
W
5
Note. Ventilation ports are provided on both sides and the top. The bottom is open.
Approximate
Resistor unit
W
W1
H
H1
H2
H3
D
D1
C
mass
[kg]
FR-BR-15K
FR-BR-30K
FR-BR-55K
FR-BR-H30K
FR-BR-H55K
170 100 450 410 20 432 220 3.2
340 270 600 560 20 582 220
480 410 700 620 40 670 450 3.2
340 270 600 560 20 582 220
480 410 700 620 40 670 450 3.2
6
15
30
70
30
70
200V
class
4
10
12
10
12
400V
class
4
(3) MT-BR5- (H) resistor unit
[Unit: mm]
Approximate
mass
Resistance
value
Resistor unit
[kg]
NP
200V
class
400V
class
MT-BR5-55K
2.0
6.5
50
70
MT-BR5-H75K
M4
M6
193
189
37
60 10 21
480
510
75
300
450
75
4
15 mounting hole
7.5
7.5
11 - 44
11. OPTIONS AND AUXILIARY EQUIPMENT
11.4 Power regeneration converter
When using the power regeneration converter, set "
01" in parameter No.PA02.
(1) Selection
The converters can continuously return 75% of the nominal regenerative power. They are applied to the
servo amplifiers of the 5k to 22kW.
Nominal
Power regeneration
regenerative power
(kW)
Servo amplifier
500
converter
300
200
MR-J3-500B
MR-J3-700B
MR-J3-11KB
MR-J3-15KB
MR-J3-22KB
MR-J3-500B4
MR-J3-700B4
MR-J3-11KB4
MR-J3-15KB4
MR-J3-22KB4
FR-RC-15K
15
100
FR-RC-30K
FR-RC-55K
FR-RC-H15K
30
55
15
50
30
20
0
50
75 100
150
FR-RC-H30K
FR-RC-H55K
30
55
Nominal regenerative power (%)
11 - 45
11. OPTIONS AND AUXILIARY EQUIPMENT
(2) Connection example
Servo amplifier
L11
L21
Power factor improving reactor
NFB
MC
FR-BAL-(H)
L1
(Note 6)
Power supply
L2
L3
CN3
EM1
24VDC
RA
CN3
Forced stop
DOCOM
DICOM
DOCOM
(Note 3)
ALM
Trouble
(Note 2)
P1 P2
N
C P
P/
5m or less
(Note 4)
N/
RDY
SE
A
B
(Note 5)
Ready
RDY
B
C
output
C
R/L1
S/L2
T/L3
Alarm
output
RX
R
(Note 1)
SX
S
Phase detection
terminals
TX
T
Power regeneration
converter FR-RC-(H)
Operation ready
ON
FR-RC-(H)
ALM
RA2
EMG
OFF
B
C
MC
SK
MC
Note 1. When not using the phase detection terminals, fit the jumpers across RX-R, SX-S and TX-T. If the jumpers remain
removed, the FR-RC-(H) will not operate.
2. When using servo amplifiers of 5kW and 7kW, always remove the lead of built-in regenerative resistor connected
to P terminal and C terminal.
3. When setting not to output Trouble (ALM) with parameter change, configure power supply circuit for turning
magnetic contactor off after detecting an occurrence of alarm on the controller side.
4. Always connect P1-P2 (For 11k to 22kW, connect P1-P). (Factory-wired.) When using the power factor improving
DC reactor, refer to section 11.13.
5. Stepdown transformer is required for coil voltage of magnetic contactor more than 200V class in 400V class servo
amplifiers.
6. Refer to section 1.3 for the power supply specification.
11 - 46
11. OPTIONS AND AUXILIARY EQUIPMENT
(3) Outside dimensions of the power regeneration converters
[Unit : mm]
Mounting foot (removable)
Mounting foot
movable
2- D hole
Rating plate
Front cover
Display
panel
window
Cooling fan
K
D
F
AA
A
C
Heat generation area outside mounting dimension
Power
Approx. mass
[kg(Ib)]
regeneration
converter
A
AA
200
270
410
B
BA
C
D
E
EE
8
K
F
19
FR-RC-15K
270
340
480
450
600
700
432
582
670
195
195
250
10
10
12
10
10
15
3.2
3.2
3.2
87
(41.888)
FR-RC-H15K
FR-RC-30K
FR-RC-H30K
FR-RC-55K
FR-RC-H55K
31
8
90
(68.343)
55
15
135
(121.3)
(4) Mounting hole machining dimensions
When the power regeneration converter is fitted to a totally enclosed type box, mount the heat generating
area of the converter outside the box to provide heat generation measures. At this time, the mounting hole
having the following dimensions is machined in the box.
[Unit : mm]
Power
(2- D hole)
(AA)
regeneration
converter
a
b
D
AA
200
270
BA
432
582
FR-RC-15K
FR-RC-H15K
FR-RC-30K
FR-RC-H30K
FR-RC-55K
FR-RC-H55K
260
330
412
562
10
10
(Mounting hole)
470
642
12
410
670
a
11 - 47
11. OPTIONS AND AUXILIARY EQUIPMENT
11.5 Power regeneration common converter
POINT
Use the FR-CV for the servo amplifier of 200V class and the FR-CV-H for that
of 400V class.
For details of the power regeneration common converter FR-CV-(H), refer to
the FR-CV-(H) Installation Guide (IB(NA)0600075).
Do not supply power to the main circuit power supply terminals (L1, L2, L3) of
the servo amplifier. Doing so will fail the servo amplifier and FR-CV-(H).
Connect the DC power supply between the FR-CV-(H) and servo amplifier
with correct polarity. Connection with incorrect polarity will fail the FR-CV-(H)
and servo amplifier.
Two or more FR-CV-(H)'s cannot be installed to improve regeneration
capability. Two or more FR-CV-(H)'s cannot be connected to the same DC
power supply line.
When using the power regeneration common converter, set parameter No.PA02 to "
01".
(1) Model
Capacity
Symbol
7.5K
11K
Capacity [kW]
7.5
11
15
22
30
37
55
15K
22K
30K
37K
55K
Symbol
None
H
Voltage class
200V class
400V class
(2) Selection
The power regenerative common converter FR-CV can be used for the servo amplifier of 200V class with
750 to 22kW and that of 400V class with 11k to 22kW. The following shows the restrictions on using the
FR-CV-(H).
(a) Up to six servo amplifiers can be connected to one FR-CV-(H).
(b) FR-CV-(H) capacity [W] Total of rated capacities [W] of servo amplifiers connected to FR-CV-(H) 2
(c) The total of used servo motor rated currents should be equal to or less than the applicable current [A] of
the FR-CV-(H).
(d) Among the servo amplifiers connected to the FR-CV-(H), the servo amplifier of the maximum capacity
should be equal to or less than the maximum connectable capacity [W].
11 - 48
11. OPTIONS AND AUXILIARY EQUIPMENT
The following table lists the restrictions.
FR-CV-
22K
6
Item
7.5K
11K
15K
30K
37K
55K
Maximum number of connected servo amplifiers
Total of connectable servo amplifier capacities [kW]
Total of connectable servo motor rated currents [A]
Maximum servo amplifier capacity [kW]
3.75
33
5.5
46
5
7.5
61
7
11
15
115
15
18.5
145
15
27.5
215
22
90
3.5
11
FR-CV-H
Item
22K
30K
37K
55K
Maximum number of connected servo amplifiers
Total of connectable servo amplifier capacities [kW]
Total of connectable servo motor rated currents [A]
Maximum servo amplifier capacity [kW]
6
11
90
11
15
115
15
18.5
145
15
27.5
215
22
When using the FR-CV-(H), always install the dedicated stand-alone reactor (FR-CVL-(H)).
Power regeneration common converter
FR-CV-7.5K(-AT)
FR-CV-11 K(-AT)
FR-CV-15K(-AT)
FR-CV-22K(-AT)
FR-CV-30K(-AT)
FR-CV-37K
Dedicated stand-alone reactor
FR-CVL-7.5K
FR-CVL-11 K
FR-CVL-15K
FR-CVL-22K
FR-CVL-30K
FR-CVL-37K
FR-CV-55K
FR-CVL-55K
FR-CV-H22K(-AT)
FR-CV-H30K(-AT)
FR-CV-H37K
FR-CVL-H22K
FR-CVL-H30K
FR-CVL-H37K
FR-CVL-H55K
FR-CV-H55K
11 - 49
11. OPTIONS AND AUXILIARY EQUIPMENT
(3) Connection diagram
(a) 200V class
Servo amplifier
Servo motor
U
FR-CVL
FR-CV
NF
MC
U
V
L11
L21
P1
P
R/L11
R2/L12
S2/L22
T2/L32
R2/L1
3-phase
200 to
V
S/L21
T/L31
S2/L2
T2/L3
Thermal
W
W
230VAC
(Note 7)
relay
OHS2
OHS1
P/L
N/L
(Note 6)
(Note 2)
N
CN2
R/L11
S/L21
EM1
RA1
(Note 1)
(Note 5)
EM1
DOCOM
DICOM
P24
SD
T/MC1
RESET
RES
RDYB
RDYA
RSO
Servo system
controller
SD
(Note 3)
(Note 4)
(Note 1)
(Note 1)
SE
A
EM1
ON
RA1 RA2
OFF
(Note 1)
RA1
MC
B
C
MC
SK
24VDC
RA2
power
supply
Note 1. Configure a sequence that will shut off main circuit power at an emergency stop or at FR-CV or servo amplifier alarm
occurrence.
2. For the servo motor with thermal relay, configure a sequence that will shut off main circuit power when the thermal relay
operates.
3. For the servo amplifier, configure a sequence that will switch the servo on after the FR-CV is ready.
4. For the FR-CV, the RSO signal turns off when it is put in a ready-to-operate status where the reset signal is input.
Configure a sequence that will make the servo inoperative when the RSO signal is on.
5. Configure a sequence that will make a stop with the emergency stop input of the servo system controller if an alarm occurs in
the FR-CV. When the servo system controller does not have an emergency stop input, use the forced stop input of the servo
amplifier to make a stop as shown in the diagram.
6. When using the servo amplifier of 7kW or less, make sure to disconnect the wiring of built-in regenerative resistor (3.5kW or
less: P and D, 5k/7kW: P and C).
7. When using the servo amplifier of 11k to 22kW, make sure to connect P1 and P. (Factory-wired.)
11 - 50
11. OPTIONS AND AUXILIARY EQUIPMENT
(b) 400V class
Servo amplifier
Servo motor
U
FR-CVL
FR-CV-H
NF
MC
U
V
L11
L21
P1
R/L11
R2/L12
S2/L22
T2/L32
R2/L1
S2/L2
T2/L3
3-phase
380 to
V
S/L21
T/L31
Thermal
W
W
480VAC
(Note 7)
relay
(Note 6)
OHS2
OHS1
P/L
N/L
P(
N(
)
(Note 2)
)
CN2
R/L11
S/L21
EM1
RA1
(Note 1)
(Note 5)
(Note 8)
EM1
DOCOM
DICOM
P24
SD
Stepdown
transformer
T/MC1
RESET
RES
RDYB
RDYA
RSO
Servo system
controller
SD
(Note 3)
(Note 4)
(Note 1)
(Note 1)
SE
A
EM1
ON
RA1 RA2
OFF
(Note 1)
RA1
MC
B
C
MC
SK
24VDC
RA2
power
supply
Note 1. Configure a sequence that will shut off main circuit power at an emergency stop or at FR-CV-H or servo amplifier alarm
occurrence.
2. For the servo motor with thermal relay, configure a sequence that will shut off main circuit power when the thermal relay
operates.
3. For the servo amplifier, configure a sequence that will switch the servo on after the FR-CV-H is ready.
4. For the FR-CV-H, the RSO signal turns off when it is put in a ready-to-operate status where the reset signal is input.
Configure a sequence that will make the servo inoperative when the RSO signal is on.
5. Configure a sequence that will make a stop with the emergency stop input of the servo system controller if an alarm occurs
in the FR-CV-H. When the servo system controller does not have an emergency stop input, use the forced stop input of the
servo amplifier to make a stop as shown in the diagram.
6. When using the servo amplifier of 7kW or less, make sure to disconnect the wiring of built-in regenerative resistor (2kW or
less: P and D, 3.5k to 7kW: P and C).
7. When using the servo amplifier of 11k to 22kW, make sure to connect P1 and P( ). (Factory-wired.)
8. Stepdown transformer is required for coil voltage of magnetic contactor more than 200V class servo amplifiers.
11 - 51
11. OPTIONS AND AUXILIARY EQUIPMENT
(4) Selection example of wires used for wiring
POINT
Selection condition of wire size is as follows.
Wire type: 600V Polyvinyl chloride insulated wire (IV wire)
Construction condition: One wire is constructed in the air
(a) Wire sizes
1) Across P-P( ), N-N(
)
The following table indicates the connection wire sizes of the DC power supply (P, N terminals)
between the FR-CV and servo amplifier.
Total of servo amplifier capacities [kW]
Wires[mm2]
1 or less
2
2
5
3.5
5.5
8
7
11
15
22
14
22
50
The following table indicates the connection wire sizes of the DC power supply (P( ), N(
terminals) between the FR-CV-H and servo amplifier.
)
Total of servo amplifier capacities [kW]
Wires[mm2]
1 or less
2
3.5
5.5
8
2
5
7
11
15
22
8
22
22
2) Grounding
For grounding, use the wire of the size equal to or greater than that indicated in the following
table, and make it as short as possible.
Power regeneration common converter
FR-CV-7.5K to FR-CV-15K
FR-CV-22K FR-CV-30K
Grounding wire size [mm2 ]
14
22
38
8
FR-CV-37K FR-CV-55K
FR-CV-H22K FR-CV-H30K
FR-CV-H37K FR-CV-H55K
22
11 - 52
11. OPTIONS AND AUXILIARY EQUIPMENT
(b) Example of selecting the wire sizes
When connecting multiple servo amplifiers, always use junction terminals for wiring the servo amplifier
terminals P, N. Also, connect the servo amplifiers in the order of larger to smaller capacities.
1) 200V class
Wire as short as possible.
50mm2
22mm2
FR-CV-55K
Servo amplifier (15kW)
First unit:
P/L
N/L
P
N
R2/L1
S2/L2
T2/L3
50mm2 assuming that the total of servo amplifier
capacities is 27.5kW since 15kW + 7kW + 3.5kW
+ 2.0kW = 27.5kW.
(Note)
22mm2
8mm2
3.5mm2
2mm2
Servo amplifier (7kW)
Second unit:
P
N
R/L11
22mm2 assuming that the total of servo amplifier
capacities is 15kW since 7kW + 3.5kW + 2.0kW =
12.5kW.
(Note)
S/L21
T/MC1
8mm2
2mm2
Servo amplifier (3.5kW)
Third unit:
P
N
8mm2 assuming that the total of servo amplifier
capacities is 7kW since 3.5kW + 2.0kW = 5.5kW.
(Note)
Servo amplifier (2kW)
Fourth unit:
P
N
2mm2 assuming that the total of servo amplifier
capacities is 2kW since 2.0kW = 2.0kW.
(Note)
Junction terminals
Overall wiring length 5m or less
Note. When using the servo amplifier of 7kW or less, make sure to disconnect the wiring of built-in regenerative resistor (3.5kW or
less: P-D, 5k/7kW: P-C).
2) 400V class
Wire as short as possible.
Servo amplifier (15kW)
22mm2
14mm2
FR-CV-55K
First unit:
P/L+
N/L-
P
N
R2/L1
S2/L2
T2/L3
22mm2 assuming that the total of servo amplifier
capacities is 27.5kW since 15kW + 7kW + 3.5kW
+ 2.0kW = 27.5kW.
14mm2
5.5mm2
Servo amplifier (7kW)
(Note)
Second unit:
P
N
R/L11
14mm2 assuming that the total of servo amplifier
capacities is 15kW since 7kW + 3.5kW + 2.0kW =
12.5kW.
S/L21
T/MC1
5.5mm2
2mm2
Servo amplifier (3.5kW)
(Note)
Third unit:
P
N
5.5mm2 assuming that the total of servo amplifier
capacities is 7kW since 3.5kW + 2.0kW = 5.5kW.
2mm2
2mm2
Servo amplifier (2kW)
(Note)
Fourth unit:
P
N
2mm2 assuming that the total of servo amplifier
capacities is 2kW since 2.0kW = 2.0kW.
Junction terminals
Overall wiring length 5m or less
Note. These servo amplifiers are development forecasted.
11 - 53
11. OPTIONS AND AUXILIARY EQUIPMENT
(5) Other precautions
(a) Always use the FR-CVL-(H) as the power factor improving reactor. Do not use the FR-BAL or FR-BEL.
(b) The inputs/outputs (main circuits) of the FR-CV-(H) and servo amplifiers include high-frequency
components and may provide electromagnetic wave interference to communication equipment (such as
AM radios) used near them. In this case, interference can be reduced by installing the radio noise filter
(FR-BIF-(H)) or line noise filter (FR-BSF01, FR-BLF).
(c) The overall wiring length for connection of the DC power supply between the FR-CV-(H) and servo
amplifiers should be 5m or less, and the wiring must be twisted.
11 - 54
11. OPTIONS AND AUXILIARY EQUIPMENT
(6) Specifications
Power regeneration common converter
FR-CV-
7.5K
11K
15K
22K
30K
37K
55K
Item
Total of connectable servo amplifier capacities [kW]
3.75
3.5
5.5
5
7.5
7
11
11
15
15
18.5
15
27.5
22
Maximum servo amplifier capacity
[kW]
Total of connectable servo motor
33
46
61
90
115
145
215
rated currents
[A]
Short-time
Output
Total capacity of applicable servo motors, 300% torque, 60s (Note 1)
100% torque
Regenerative
braking torque
rating
Continuous
rating
Rated input AC voltage/frequency
Permissible AC voltage fluctuation
Permissible frequency fluctuation
Power supply capacity (Note 2) [kVA]
Three-phase 200 to 220V 50Hz, 200 to 230V 60Hz
Three-phase 170 to 242V 50Hz, 170 to 253V 60Hz
5%
Power supply
17
20
28
41
52
66
100
Protective structure (JEM 1030), cooling system
Ambient temperature
Open type (IP00), forced cooling
-10 to +50 (non-freezing)
90%RH or less (non-condensing)
Environment
Ambient humidity
Ambience
Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt)
1000m or less above sea level, 5.9m/s2 2 or less
Altitude, vibration
30AF
30A
50AF
50A
100AF
75A
100AF
100A
225AF
125A
225AF
125A
225AF
175A
No-fuse breaker or leakage current breaker
Magnetic contactor
S-N20
S-N35
S-N50
S-N65
S-N95
S-N95
S-N125
Power regeneration common converter
FR-CV-H
22K
30K
37K
55K
Item
Total of connectable servo amplifier capacities
Maximum servo amplifier capacity
[kW]
[kW]
11
11
15
15
18.5
15
27.5
22
Total of connectable servo motor
rated currents
43
57
71
110
[A]
Short-time
Total capacity of applicable servo motors, 300%
torque, 60s (Note 1)
Output
Regenerative
braking torque
rating
Continuous
rating
100% torque
Rated input AC voltage/frequency
Three-phase 380 to 480V, 50Hz/60Hz
Three-phase 323 to 528V, 50Hz/60Hz
5%
Permissible AC voltage fluctuation
Permissible frequency fluctuation
Power supply
Power supply capacity
[kVA]
41
52
66
100
Protective structure (JEM 1030), cooling system
Ambient temperature
Open type (IP00), forced cooling
-10 to +50 (non-freezing)
90%RH or less (non-condensing)
Ambient humidity
Environment
Indoors (without corrosive gas, flammable gas, oil
mist, dust and dirt)
Ambience
Altitude, vibration
1000m or less above sea level, 5.9m/s2 2 or less
60AF
60A
100AF
175A
100AF
175A
225AF
125A
No-fuse breaker or leakage current breaker
Magnetic contactor
S-N25
S-N35
S-N35
S-N65
Note 1. This is the time when the protective function of the FR-CV-(H) is activated. The protective function of the servo amplifier is
activated in the time indicated in section 10.1.
2. When connecting the capacity of connectable servo amplifier, specify the value of servo amplifier.
11 - 55
11. OPTIONS AND AUXILIARY EQUIPMENT
11.6 External dynamic brake
POINT
Configure up a sequence which switches off the contact of the brake unit after
(or as soon as) it has turned off the servo on signal at a power failure or
failure.
For the braking time taken when the dynamic brake is operated, refer to
section 10.3.
The brake unit is rated for a short duration. Do not use it for high duty.
When using the 400V class dynamic brake, the power supply voltage is
restricted to 1-phase 380VAC to 463VAC (50Hz/60Hz).
(1) Selection of dynamic brake
The dynamic brake is designed to bring the servo motor to a sudden stop when a power failure occurs
or the protective circuit is activated, and is built in the 7kW or less servo amplifier. Since it is not built
in the 11kW or more servo amplifier, purchase it separately if required. Assign the dynamic brake interlock
(DB) to any of CN3-9, CN3-13, and CN3-15 pins in parameter No.PD07 to PD09.
Servo amplifier
MR-J3-11KB
MR-J3-15KB
MR-J3-22KB
MR-J3-11KB4
MR-J3-15KB4
MR-J3-22KB4
Dynamic brake
DBU-11K
DBU-15K
DBU-22K
DBU-11K-4
DBU-22K-4
11 - 56
11. OPTIONS AND AUXILIARY EQUIPMENT
(2) Connection example
Operation-ready
Servo amplifier
ALM
ON
RA1
EM1
OFF
Servo motor
M
MC
SK
U
V
MC
U
V
W
W
NFB
MC
(Note 4)
L1
L2
(Note 5)
Power
supply
CN3
L3
RA1
RA2
15 ALM
L11
L21
P
DICOM
10
(Note 3)
DB
(Note 2)
P1
DICOM
5
3
DOCOM
20 EM1
Plate SD
(Note 1)
14
13
U
V
W
(Note 6)
a
b
RA2
External dynamic brake
Note 1. Terminals 13, 14 are normally open contact outputs. If the dynamic brake is seized, terminals 13, 14 will open.
Therefore, configure up an external sequence to prevent servo-on.
2. For the servo amplifiers from 11k to 22kW, be sure to connect P1 and P. (Factory-wired)
When using the power factor DC reactor, refer to section 11.13.
3. Assign the dynamic brake interlock (DB) in the parameters No.PD07 to PD09.
4. Stepdown transformer is required for coil voltage of magnetic contactor more than 200V class in 400V class servo amplifiers.
5. Refer to section 1.3 for the power supply specification.
6. The power supply voltage of the inside magnet contactor for 400V class dynamic brake DBU-11K-4 and DBU-22K-4 is restricted
as follows. When using these dynamic brakes, use them within the range of the power supply.
Dynamic brake
DBU-11K-4
DBU-22K-4
Power supply voltage
1-phase 380 to 463VAC 50Hz/60Hz
11 - 57
11. OPTIONS AND AUXILIARY EQUIPMENT
Coasting
Coasting
Dynamic brake
Servo motor rotation
Dynamic brake
Present
Absent
ON
Alarm
Base
OFF
ON
OFF
RA1
Invalid
Valid
Dynamic brake
Short
Open
Forced stop
(EM1)
a. Timing chart at alarm occurrence
Servo motor speed
b. Timing chart at forced stop (EM1) validity
Coasting
Dynamic brake
Electro magnetic
brake interlock
(Note 1)7ms
10ms
ON
Base circuit
OFF
Electro magnetic
brake interlock(MBR)
Invalid (ON)
Valid (OFF)
(Note 2)15 to 60ms
Electro magnetic
brake operation
delay time
Invalid
Valid
ON
Alarm
Main circuit
Control circuit
Power
OFF
ON
RA1
OFF
Invalid (ON)
Valid (OFF)
Dynamic brake
Note 1. When powering OFF, the RA1 of external dynamic brake circuit will be turned OFF, and the base circuit
is turned OFF earlier than usual before an output shortage occurs.
(Only when assigning the DB as the output signal in the parameter No.PD07, PD08 or PD09)
2. Variable according to the operation status.
c. Timing chart when both of the main and control circuit power are OFF
11 - 58
11. OPTIONS AND AUXILIARY EQUIPMENT
(3) Outline dimension drawing
(a) DBU-11K DBU-15K DBU-22K
[Unit: mm]
5
5
G
F
100
D
D
2.3
C
Terminal block
E
U
V
W
a
b
13 14
(GND)
Screw : M4
Screw : M3.5
Tightening torque: 1.2 [N m](10.6 [lb in])
Tightening torque: 0.8 [N m](7 [lb in])
Connection
Mass
Dynamic brake
A
B
C
D
E
F
G
wire [mm2]
(Note)
[kg]([Ib])
DBU-11K
200
250
190
238
140
150
20
25
5
6
170
235
163.5
228
2 (4.41)
5.5
5.5
DBU-15K, 22K
6 (13.23)
Note. Selection condition of wire size is as follows.
Wire type: 600V Polyvinyl chloride insulated wire (IV wire)
Construction condition: One wire is constructed in the air
11 - 59
11. OPTIONS AND AUXILIARY EQUIPMENT
(b) DBU-11K-4 DBU-22K-4
[Unit: mm]
2- 7mounting hole
51 73.75
150
7
2.3
15
25
25
15
195
210
200
15
170
Mass: 6.7[kg]
Terminal block
TE1
TE2
U
a
b
13 14
V
W
Screw: M3.5
Screw: M4
Tightening torque: 1.2[N m](10.6[lb in])
Tightening torque: 0.8[N m](7[lb in])
Wire [mm2] (Note)
Dynamic brake
a
b
U
V
W
DBU-11K
2
2
5.5
5.5
DBU-15K, 22K
Note. Selection condition of wire size is as follows.
Wire type: 600V Polyvinyl chloride insulated wire (IV wire)
Construction condition: One wire is constructed in the air
11 - 60
11. OPTIONS AND AUXILIARY EQUIPMENT
11.7 Junction terminal block PS7DW-20V14B-F (recommended)
(1) How to use the junction terminal block
Always use the junction terminal block (PS7W-20V14B-F(YOSHIDA ELECTRIC INDUSTRY)) with the
option cable (MR-J2HBUS M) as a set. A connection example is shown below.
Servo amplifier
Cable clamp
(AERSBAN-ESET)
Junction terminal block
PS7DW-20V14B-F
CN3
MR-J2HBUS
M
Ground the option cable on the junction terminal block side with the cable clamp fitting (AERSBAN-ESET).
For the use of the cable clamp fitting, refer to section 11.14, (2)(c).
(2) Connection of MR-J2HBUS M cable and junction terminal block
Junction terminal block
Servo amplifier
CN3
PS7W-20V14B-F
Terminal block
CN
(Note)MR-J2HBUS
M
LG
1
2
1
2
1
2
3
4
5
6
7
8
9
1
2
1
2
LG
DI1
DI1
DOC
MO1
DICO
LA
3
3
3
3
DOC
MO1
DICO
LA
4
4
4
4
5
5
5
5
6
6
6
6
LB
7
7
7
7
LB
LZ
8
8
8
8
LZ
INP
DICO
LG
9
9
9
9
INP
DICO
LG
10
11
12
13
14
15
16
17
18
19
20
10
11
12
13
14
15
16
17
18
19
20
10
11
12
13
14
15
16
17
18
19
20
10
11
12
13
14
15
16
17
18
19
20
10
11
12
13
14
15
16
17
18
19
20
DI2
DI2
MBR
MO2
AMR
LAR
LBR
LZR
DI3
MBR
MO2
AMR
LAR
LBR
LZR
DI3
EM1
SD
EM1
Shell Shell
Shell Shell
E
SD
Connector: 10120-6000EL (3M)
Shell kit: 10320-3210-000 (3M)
Note. Symbol indicating cable length is put in
.
05: 0.5m
1: 1m
5: 5m
11 - 61
11. OPTIONS AND AUXILIARY EQUIPMENT
(3) Outline drawings of junction terminal block
[Unit : mm]
63
54
44.11
7.62
4.5
TB.E
(
6)
M3 5L
6.2
1.42
M3 6L
11.8 MR Configurator
The MR Configurator (MRZJW3-SETUP221E) uses the communication function of the servo amplifier to
perform parameter setting changes, graph display, test operation, etc. on a personal computer.
(1) Specifications
Item
Description
The following table shows MR Configurator software version for each servo amplifier.
Compatible servo amplifier (Drive unit)
Version
100V class 200V class
400V class
Compatibility with a
servo amplifier
7kW or less 11k to 22kW 30k to 37kW 7kW or less 11k to 22kW 30k to 55kW
B1
C0 or later
Display, high speed monitor, trend graph
Monitor
Alarm
Minimum resolution changes with the processing speed of the personal computer.
Display, history, amplifier data
Digital I/O, no motor rotation, total power-on time, amplifier version info, motor information,
tuning data, absolute encoder data, Axis name setting.
Parameter list, turning, change list, detailed information
Jog operation, positioning operation, Do forced output, program operation.
Machine analyzer, gain search, machine simulation.
Data read, save, delete, print
Diagnostic
Parameters
Test operation
Advanced function
File operation
Others
Automatic demo, help display
11 - 62
11. OPTIONS AND AUXILIARY EQUIPMENT
(2) System configuration
(a) Components
To use this software, the following components are required in addition to the servo amplifier and servo
motor.
Equipment
(Note 1) Description
IBM PC/AT compatible where the English version of WindowsR 98, Windows R Me,
WindowsR 2000 Professional, Windows R XP Professional, WindowsR XP Home Edition,
Windows VistaR Home Basic, Windows VistaR Home Premium, Windows VistaR Business,
Windows VistaR Ultimate, Windows VistaR Enterprise operates
PentiumR 133MHz or more (WindowsR 98, WindowsR 2000 Professional)
PentiumR 150MHz or more (WindowsR Me)
OS
PentiumR 300MHz or more (WindowsR XP Professional, WindowsR XP Home Edition)
32-bit (x86) processor of 1GHz or higher (Windows VistaR Home Basic, Windows VistaR
Home Premium, Windows VistaR Business, Windows VistaR Ultimate, Windows VistaR
Enterprise)
Processor
(Note 2, 3)
Personal computer
24MB or more (WindowsR 98)
32MB or more (WindowsR Me, Windows R 2000 Professional)
128MB or more (WindowsR XP Professional, WindowsR XP Home Edition)
512MB or more (Windows VistaR Home Basic)
Memory
1GB or more (Windows VistaR Home Premium, Windows VistaR Business, Windows VistaR
Ultimate, Windows VistaR Enterprise)
Hard Disk 130MB or more of free space
Internet Explorer 4.0 or more
Browser
Display
One whose resolution is 800 600 or more and that can provide a high color (16 bit) display.
Connectable with the above personal computer.
Connectable with the above personal computer.
Connectable with the above personal computer.
Connectable with the above personal computer.
MR-J3USBCBL3M
Keyboard
Mouse
Printer
USB cable
Note 1. Windows and Windows Vista is the registered trademarks of Microsoft Corporation in the United States and other
countries.
Pentium is the registered trademarks of Intel Corporation.
2. On some personal computers, MR Configurator may not run properly.
3. 64-bit Windows XP and 64-bit Windows Vista are not supported.
(b) Connection with servo amplifier
1) For use of USB
Personal computer
Servo amplifier
CN5
USB cable
To USB
connector
MR-J3USBCBL3M
(Option)
CN2
11 - 63
11. OPTIONS AND AUXILIARY EQUIPMENT
11.9 Battery MR-J3BAT
POINT
The revision (Edition 44) of the Dangerous Goods Rule of the International Air
Transport Association (IATA) went into effect on January 1, 2003 and was
enforced immediately. In this rule, "provisions of the lithium and lithium ion
batteries" were revised to tighten the restrictions on the air transportation of
batteries. However, since this battery is non-dangerous goods (non-Class 9),
air transportation of 24 or less batteries is outside the range of the
restrictions. Air transportation of more than 24 batteries requires packing
compliant with the Packing Standard 903. When a self-certificate is necessary
for battery safety tests, contact our branch or representative. For more
information, consult our branch or representative. (As of Jun, 2008).
(1) Purpose of use for MR-J3BAT
This battery is used to construct an absolute position detection system. Refer to section 12.3 for the fitting
method, etc.
(2) Year and month when MR-J3BAT is manufactured
The year and month when MR-J3BAT is manufactured are written down in Serial No. on the rating plate of
the battery back face.
The year and month of manufacture are indicated by the last one digit of the year and 1 to 9, X(10), Y(11),
Z(12).
For October 2004, the Serial No. is like, "SERIAL 4X
".
MELSERVO
3.6V,2000mAh
SERIAL 4X
MR-J3BAT
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
The year and month of manufacture
11 - 64
11. OPTIONS AND AUXILIARY EQUIPMENT
11.10 Heat sink outside mounting attachment (MR-J3ACN)
Use the heat sink outside mounting attachment to mount the heat generation area of the servo amplifier in the
outside of the control box to dissipate servo amplifier-generated heat to the outside of the box and reduce the
amount of heat generated in the box, thereby allowing a compact control box to be designed.
In the control box, machine a hole having the panel cut dimensions, fit the heat sink outside mounting
attachment to the servo amplifier with the fitting screws (4 screws supplied), and install the servo amplifier to
the control box.
The environment outside the control box when using the heat sink outside mounting attachment should be
within the range of the servo amplifier operating environment conditions.
The heat sink outside mounting attachment of MR-J3ACN can be used for MR-J3-11KB(4) to MR-J3-22KB(4).
(1) Panel cut dimensions
[Unit : mm]
203
4-M10 Screw
Punched
hole
236
255
270
(2) How to assemble the attachment for a heat sink outside mounting attachment
Attachment
Screw
(2 places)
11 - 65
11. OPTIONS AND AUXILIARY EQUIPMENT
(3) Fitting method
Attachment
Punched
hole
Servo
amplifier
Servo
amplifier
Fit using the
assembling
screws.
Control box
Attachment
a. Assembling the heat sink outside mounting attachment
b. Installation to the control box
(4) Outline dimension drawing
[Unit: mm]
20
Panel
Servo
amplifier
Servo amplifier
Attachment
Panel
3.2
155
Approx. 260
236
280
Approx. 11.5
105
Mounting
hole
Approx. 260
11 - 66
11. OPTIONS AND AUXILIARY EQUIPMENT
11.11 Selection example of wires
POINT
Refer to section 11.1.5 for SSCNET cable.
Wires indicated in this section are separated wires. When using a cable for
power line (U, V, and W) between the servo amplifier and servo motor, use a
600V grade EP rubber insulated chloroprene sheath cab-tire cable (2PNCT).
For selection of cables, refer to appendix 6.
To comply with the UL/C-UL (CSA) Standard, use UL-recognized copper
wires rated at 60 (140 ) or more for wiring. To comply with other
standards, use a wire that is complied with each standard
Selection condition of wire size is as follows.
Construction condition: One wire is constructed in the air
Wire length: 30m or less
(1) Wires for power supply wiring
The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent.
1) Main circuit power supply lead
3) Motor power supply lead
Servo motor
Servo amplifier
Power supply
L1
U
V
U
V
L2
L3 (Note)
Motor
W
W
2) Control power supply lead
L11
L21
8) Power regeneration
converter lead
4) Electromagnetic
brake lead
Electro-
magnetic
brake
B1
B2
Power regeneration
converter
N
C
Regenerative option
P
C
Encoder
P
Encoder cable
Power supply
4) Regenerative option lead
Cooling fan
BU
BV
BW
6) Cooling fan lead
7) Thermal
Thermal
OHS1
OHS2
Note. There is no L3 for 1-phase 100 to 120VAC power supply.
11 - 67
11. OPTIONS AND AUXILIARY EQUIPMENT
(a) When using the 600V Polyvinyl chloride insulated wire (IV wire)
Selection example of wire size when using IV wires is indicated below.
Table 11.1 Wire size selection example 1 (IV wire)
Wires [mm2] (Note 1, 4)
Servo amplifier
1)
3)
6)
7)
2) L11 L21
4) P
C
5) B1 B2
L1 L2 L3
U
V
W
BU BV BW OHS1 OHS2
MR-J3-10B(1)
MR-J3-20B(1)
MR-J3-40B(1)
MR-J3-60B
MR-J3-70B
MR-J3-100B
MR-J3-200B
MR-J3-350B
MR-J3-500B
(Note 2)
1.25(AWG16)
2(AWG14)
1.25(AWG16)
2(AWG14)
2(AWG14)
3.5(AWG12)
3.5(AWG12)
5.5(AWG10): a
5.5(AWG10): a 2(AWG14): g
1.25(AWG16):
h
MR-J3-700B
(Note 2)
2(AWG14)
(Note 3)
1.25(AWG16)
(Note 3)
8(AWG8): b
14(AWG6): c
22(AWG4): d
8(AWG8): b
22(AWG4): d
30(AWG2): e
3.5(AWG12): a
MR-J3-11KB
(Note 2)
5.5(AWG10): j 1.25(AWG16)
MR-J3-15KB
(Note 2)
1.25(AWG16):
g
2(AWG14)
1.25(AWG16)
MR-J3-22KB
(Note 2)
50(AWG1/0):
f
60(AWG2/0): f 5.5(AWG10): k
MR-J3-60B4
MR-J3-100B4
MR-J3-200B4
MR-J3-350B4
MR-J3-500B4
(Note 2)
1.25(AWG16)
2(AWG14)
2(AWG14)
1.25(AWG16)
2(AWG14)
2(AWG14): g
2(AWG14): g
1.25(AWG16):
h
2(AWG14): g
5.5(AWG10): a
5.5(AWG10): a
MR-J3-700B4
(Note 2)
2(AWG14)
(Note 3)
1.25(AWG16)
(Note 3)
MR-J3-11KB4
(Note 2)
8(AWG8): l
8(AWG8): l
3.5(AWG12): j
5.5(AWG10): j
5.5(AWG10): k
MR-J3-15KB4
(Note 2)
1.25(AWG16):
g
14(AWG6): c
14(AWG6): m
22(AWG4): d
22(AWG4): n
2(AWG14)
1.25(AWG16)
MR-J3-22KB4
(Note 2)
Note 1. Alphabets in the table indicate crimping tools. For crimping terminals and applicable tools, refer to (1) (c) in this section.
2. When connecting to the terminal block, be sure to use the screws which are provided with the terminal block.
3. For the servo motor with a cooling fan.
4. Wires are selected based on the highest rated current among combining servo motors.
Use wires 8) of the following sizes with the power regeneration converter (FR-RC-(H)).
2
Model
Wires[mm ]
14(AWG6)
14(AWG6)
22(AWG4)
14(AWG6)
14(AWG6)
14(AWG6)
FR-RC-15K
FR-RC-30K
FR-RC-55K
FR-RC-H15K
FR-RC-H30K
FR-RC-H55K
11 - 68
11. OPTIONS AND AUXILIARY EQUIPMENT
(b) When using the 600V Grade heat-resistant polyvinyl chloride insulated wire (HIV wire)
Selection example of wire size when using HIV wires is indicated below. For the wire (8)) for power
regeneration converter (FR-RC-(H)), use the IV wire indicated in (1) (a) in this section.
Table 11.2 Wire size selection example 2 (HIV wire)
Wires [mm2] (Note 1, 4)
Servo amplifier
1)
3)
6)
7)
2) L11 L21
4) P
C
5) B1 B2
L1 L2 L3
U
V
W
BU BV BW OHS1 OHS2
MR-J3-10B(1)
MR-J3-20B(1)
MR-J3-40B(1)
MR-J3-60B
MR-J3-70B
MR-J3-100B
MR-J3-200B
MR-J3-350B
MR-J3-500B
(Note 2)
1.25(AWG16)
2(AWG14)
1.25(AWG16)
2(AWG14)
1.25(AWG16)
2(AWG14)
3.5(AWG12)
3.5(AWG12)
5.5(AWG10): a
5.5(AWG10): a 2(AWG14): g
1.25(AWG16):
h
MR-J3-700B
(Note 2)
1.25(AWG16) 1.25(AWG16)
(Note 3) (Note 3)
8(AWG8): b
14(AWG6): c
22(AWG4): d
38(AWG1): p
8(AWG8): b
14(AWG6): c
22(AWG4): d
38(AWG1): p
1.25(AWG16)
2(AWG14): g
MR-J3-11KB
(Note 2)
3.5(AWG12): j 1.25(AWG16)
MR-J3-15KB
(Note 2)
1.25(AWG16):
g
1.25(AWG16) 1.25(AWG16)
MR-J3-22KB
(Note 2)
5.5(AWG10): k
2(AWG14)
MR-J3-60B4
MR-J3-100B4
MR-J3-200B4
MR-J3-350B4
MR-J3-500B4
(Note 2)
2(AWG14)
1.25(AWG16)
2(AWG14)
2(AWG14): g
2(AWG14): g
1.25(AWG16):
h
3.5(AWG12): a
5.5(AWG10): a
8(AWG8): l
2(AWG14): g
3.5(AWG12): a
MR-J3-700B4
(Note 2)
1.25(AWG16) 1.25(AWG16)
(Note 3) (Note 3)
MR-J3-11KB4
(Note 2)
5.5(AWG10): j
8(AWG8): l
2(AWG14): q
3.5(AWG12): j
MR-J3-15KB4
(Note 2)
1.25(AWG16):
g
14(AWG6): c
1.25(AWG16) 1.25(AWG16)
MR-J3-22KB4
(Note 2)
14(AWG6): m
14(AWG6): m 3.5(AWG12): k
Note 1. Alphabets in the table indicate crimping tools. For crimping terminals and applicable tools, refer to (1) (c) in this section.
2. When connecting to the terminal block, be sure to use the screws which are provided with the terminal block.
3. For the servo motor with a cooling fan.
4. Wires are selected based on the highest rated current among combining servo motors.
11 - 69
11. OPTIONS AND AUXILIARY EQUIPMENT
(c) Selection example of crimping terminals
Selection example of crimping terminals for the servo amplifier terminal box when using the wires
mentioned in (1) (a) and (b) in this section is indicated below.
Servo amplifier side crimping terminals
(Note 2)
Crimping
terminal
Applicable tool
Symbol
a
Manufacturer
Body
Head
Dice
FVD5.5-4
YNT-1210S
YHT-8S
(Note 1)b 8-4NS
c
FVD14-6
FVD22-6
DH-112 DH122
DH-113 DH123
YF-1 E-4
YNE-38
d
YPT-60-21
YF-1 E-4
YPT-60-21
YF-1 E-4
(Note 1)e 38-6
(Note 1)f R60-8
TD-112 TD-124
YET-60-1
YET-60-1
TD-113 TD-125 Japan Solderless
Terminal
g
h
j
FVD2-4
YNT-1614
FVD2-M3
FVD5.5-6
FVD5.5-8
FVD8-6
YNT-1210S
k
l
DH-111 DH121
DH-112 DH122
DH-113 DH123
YF-1 E-4
YNE-38
m
n
FVD14-8
FVD22-8
YPT-60-21
YF-1 E-4
YNT-1614
(Note 1)p R38-8
FVD2-6
TD-112 TD-124
YET-60-1
q
Note 1. Coat the part of crimping with the insulation tube.
2. Some crimping terminals may not be mounted depending on the size. Make sure to use the
recommended ones or equivalent ones.
11 - 70
11. OPTIONS AND AUXILIARY EQUIPMENT
(2) Wires for cables
When fabricating a cable, use the wire models given in the following table or equivalent.
Table 11.3 Wires for option cables
Characteristics of one core
(Note 3)
Finishing
OD [mm]
Insulation
coating OD
d [mm]
Length Core size Number
Structure
Conductor
resistance
Type
Model
Wire model
[m]
[mm2]
of Cores
[Wires/mm]
[
/mm]
(Note 1)
(Note 3)
VSVP 7/0.26 (AWG#22 or
equivalent)-3P
MR-J3ENCBL M-A1-L
MR-J3ENCBL M-A2-L
MR-J3ENCBL M-A1-H
MR-J3ENCBL M-A2-H
MR-J3JCBL03M-A1-L
MR-J3JCBL03M-A2-L
6
53
or less
2 to 10 AWG22
2 to 10 AWG22
7/0.26
70/0.08
30/0.08
1.2
1.2
1.2
7.1 0.3
(3 pairs)
Ban-gi-shi-16823
(Note 3)
6
56
or less
7.1 0.3 ETFE SVP 70/0.08 (AWG#22 or
equivalent)-3P Ban-gi-shi-16824
(3 pairs)
(Note 5)
7.1 0.3 T/2464-1061/II A-SB 4P
26AWG
8
233
or less
0.3
AWG26
(4 pairs)
4
65.7
or less
234
or less
63.6
or less
105
or less
105
or less
0.3mm2
12/0.18
7/0.127
12/0.18
40/0.08
40/0.08
1.3
0.67
1.2
(Note 3)
(2 pairs)
2 to 10
7.3
20276 composite 4-pair shielded
cable (A-TYPE)
4
0.08mm2
MR-EKCBL M-L
MR-EKCBL M-H
MR-J3ENSCBL M-L
(2 pairs)
12
(6 pairs)
12
(6 pairs)
14
Encoder
cable
20 30 0.3mm2
0.2mm2
8.2
7.2
8.0
UL20276 AWG#23 6pair(BLACK)
(Note 3) A14B2343 6P
20
0.88
0.88
30 to 50 0.2mm2
(Note 3) J14B0238(0.2*7P)
(Note 3)
7.1 0.3 VSVP 7/0.26 (Equivalent to
AWG#22)-3P Ban-gi-shi-16823
(Note 3)
(7 pairs)
6
53
or less
2 to 10 AWG22
7/0.26
12/0.18
70/0.08
40/0.08
1.2
1.2
(3 pairs)
12
(6 pairs)
63.3
or less
20 30 AWG23
2 to 10 AWG22
20 to 50 AWG24
8.2 0.3 20276 VSVCAWG#23 6P
Ban-gi-shi-15038
(Note 3)
6
56
or less
1.2
7.1 0.3 ETEF SVP 70/0.08 (Equivalent to
AWG#22)-3P Ban-gi-shi-16824
(Note 3)
(3 pairs)
MR-J3ENSCBL M-H
12
(6 pairs)
105
or less
0.88
7.2
ETFE SVP 40/0.08mm 6P
Ban-gi-shi-15266
MR-PWS1CBL M-A1-L 2 to 10
MR-PWS1CBL M-A2-L 2 to 10
Motor power MR-PWS1CBL M-A1-H 2 to 10 (Note 6)
supply cable AWG19
25.40
or less
(Note 4)
UL Style 2103 AWG19 4 cores
4
2
50/0.08
1.8
1.3
5.7 0.3
MR-PWS1CBL M-A2-H 2 to 10
MR-PWS2CBL03M-A1-L
MR-PWS2CBL03M-A2-L
MR-BKS1CBL M-A1-L
MR-BKS1CBL M-A2-L
0.3
0.3
2 to 10
2 to 10
Motor brake MR-BKS1CBL M-A1-H 2 to 10 (Note 6)
cable AWG20
38.14
or less
(Note 4)
UL Style 2103 AWG20 2 cores
100/0.08
4.0 0.3
MR-BKS1CBL M-A2-H 2 to 10
MR-BKS2CBL03M-A1-L
MR-BKS2CBL03M-A2-L
0.3
0.3
Note 1. d is as shown below.
d
Conductor Insulation sheath
2. Purchased from Toa Electric Industry
3. Standard OD. Max. OD is about 10% greater.
4. Kurabe
5. Taiyo Electric Wire and Cable
6. These wire sizes assume that the UL-compliant wires are used at the wiring length of 10m.
11 - 71
11. OPTIONS AND AUXILIARY EQUIPMENT
11.12 No-fuse breakers, fuses, magnetic contactors
Always use one no-fuse breaker and one magnetic contactor with one servo amplifier. When using a fuse
instead of the no-fuse breaker, use the one having the specifications given in this section.
No-fuse breaker
Fuse
Magnetic
contactor
Not using power
Servo amplifier
Using power factor
improving reactor
Voltage
AC [V]
factor improving
reactor
(Note) Class Current [A]
MR-J3-10B (1)
MR-J3-20B
30A frame 5A
30A frame 5A
30A frame 10A
30A frame 10A
30A frame 5A
30A frame 5A
30A frame 10A
30A frame 5A
10
10
15
15
MR-J3-20B1
MR-J3-40B
S-N10
MR-J3-60B
MR-J3-70B
30A frame 15A
30A frame 10A
20
MR-J3-100B
MR-J3-40B1
MR-J3-200B
MR-J3-350B
MR-J3-500B
MR-J3-700B
MR-J3-11KB
MR-J3-15KB
MR-J3-22KB
MR-J3-60B4
MR-J3-100B4
MR-J3-200B4
MR-J3-350B4
MR-J3-500B4
MR-J3-700B4
MR-J3-11KB4
MR-J3-15KB4
MR-J3-22KB4
250
30A frame 20A
30A frame 30A
50A frame 50A
100A frame 75A
30A frame 15A
30A frame 30A
50A frame 40A
50A frame 50A
40
70
S-N18
S-N20
S-N35
S-N50
S-N65
S-N95
S-N125
125
150
T
100A frame 100A 100A frame 75A
225A frame 125A 100A frame 100A
225A frame 175A 225A frame 150A
200
250
350
10
30A frame 5A
30A frame 10A
30A frame 15A
30A frame 20A
30A frame 30A
50A frame 40A
60A frame 60A
100A frame 75A
30A frame 5A
30A frame 10A
30A frame 15A
30A frame 20A
30A frame 30A
50A frame 30A
50A frame 50A
60A frame 60A
15
S-N10
25
35
600
50
S-N18
S-N20
S-N25
S-N35
S-N65
65
100
150
175
225A frame 125A 100A frame 100A
Note. When not using the servo amplifier as a UL/C-UL Standard compliant product, K5 class fuse can be used.
11.13 Power factor improving DC reactor
POINT
For the 100V power supply type (MR-J3- B1), the power factor improving DC
reactor cannot be used.
The power factor improving DC reactor increases the form factor of the servo amplifier's input current to
improve the power factor. It can decrease the power supply capacity. As compared to the power factor
improving AC reactor (FR-BAL), it can decrease the loss. The input power factor is improved to about 95%.
It is also effective to reduce the input side harmonics.
When connecting the power factor improving DC reactor to the servo amplifier, always disconnect P1 and P2
(For 11kW or more, disconnect P1 and P). If it remains connected, the effect of the power factor improving DC
reactor is not produced.
When used, the power factor improving DC reactor generates heat. To release heat, therefore, leave a 10cm or
more clearance at each of the top and bottom, and a 5cm or more clearance on each side.
11 - 72
11. OPTIONS AND AUXILIARY EQUIPMENT
Rating plate Terminal box - screw size G
Rating plate
(Note 1)Terminal cover
Screw size G
Servo amplifier
FR-BEL-(H)
Servo amplifier
FR-BEL-(H)
P1
(Note 2)
P2
P1
(Note 2)
(Note 3)
P2
5m or less
E
H
5m or less
A or less
B or less
E
H
2-F L notch
A or less
B or less
2-F L notch
Mounting leg
F
Mounting leg
F
Fig. 11.1
Fig. 11.2
Note 1. Since the terminal cover is supplied, attach it after connecting a wire.
2. When using DC reactor, disconnect P1 and P2.
3. When over 11kW, "P2" becomes "P", respectively.
Power factor
improving DC
reactor
Dimensions [mm]
Outline
Mounting
screw size
Mass
Wire
[mm2] (Note)
Servo amplifier
drawing
[kg(lb)]
A
B
C
D
E
F
L
G
H
MR-J3-10B 20B
MR-J3-40B
FR-BEL-0.4K
FR-BEL-0.75K
FR-BEL-1.5K
110
120
130
50
53
65
65
75
75
93
94
1.6
1.6
1.6
1.6
2.0
2.0
2.3
95
6
6
6
6
6
6
6
12
12
12
12
12
12
14
M3.5
M4
M4
M4
M4
M5
M5
25
25
30
30
40
40
50
M5
M5
M5
M5
M5
M5
M5
0.5(1.10)
0.7(1.54)
1.1(2.43)
1.2(2.65)
1.7(3.75)
102
110
110
102
126
132
105
115
115
135
135
155
MR-J3-60B 70B
MR-J3-100B
MR-J3-200B
MR-J3-350B
MR-J3-500B
MR-J3-700B
MR-J3-11KB
MR-J3-15KB
MR-J3-22KB
MR-J3-60B4
MR-J3-100B4
MR-J3-200B4
MR-J3-350B4
MR-J3-500B4
MR-J3-700B4
MR-J3-11KB4
MR-J3-15KB4
MR-J3-22KB4
2(AWG14)
FR-BEL-2.2K Fug. 11.1 130
FR-BEL-3.7K
FR-BEL-7.5K
FR-BEL-11K
150
150
170
2.3(5.07) 3.5(AWG12)
3.1(6.83) 5.5(AWG10)
8(AWG8)
3.8(8.38)
FR-BEL-15K
170
93
170
2.3
155
6
14
M8
56
M5
22(AWG4)
Fig. 11.2
FR-BEL-22K
FR-BEL-30K
185
185
130
130
119
119
63
182
201
89
2.6
2.6
1.6
1.6
2
165
165
115
115
135
135
155
7
7
6
6
6
6
6
15
15
12
12
12
12
14
M8
M8
70
70
32
32
40
40
50
M6
M6
M5
M5
M5
M5
M5
5.4(11.91) 30(AWG2)
6.7(14.77) 60(AWG2/0)
0.9(1.98)
FR-BEL-H1.5K
FR-BEL-H2.2K
M3.5
M3.5
M4
63
101
102
124
132
1.1(2.43)
2(AWG14)
1.7(3.75)
FR-BEL-H3.7K Fig. 11.1 150
75
FR-BEL-H7.5K
FR-BEL-H11K
150
170
75
2
M4
2.3(5.07)
93
2.3
M5
3.1(6.83) 5.5(AWG10)
FR-BEL-H15K
170
93
160
2.3
155
6
14
M6
56
M5
3.7(8.16)
8(AWG8)
Fig. 11.2
FR-BEL-H22K
FR-BEL-H30K
185
185
119
119
171
189
2.6
2.6
165
165
7
7
15
15
M6
M6
70
70
M6
M6
5.0(11.02)
6.7(14.77)
22(AWG4)
Note. Selection condition of wire size is as follows.
Wire type: 600V Polyvinyl chloride insulated wire (IV wire)
Construction condition: One wire is constructed in the air
11 - 73
11. OPTIONS AND AUXILIARY EQUIPMENT
11.14 Power factor improving AC reactors
The power factor improving AC reactors improve the phase factor by increasing the form factor of servo
amplifier's input current.
It can reduce the power capacity.
The input power factor is improved to be about 90%. For use with a 1-phase power supply, it may be slightly
lower than 90%.
In addition, it reduces the higher harmonic of input side.
When using power factor improving reactors for two servo amplifiers or more, be sure to connect a power factor
improving reactor to each servo amplifier.
If using only one power factor improving reactor, enough improvement effect of phase factor cannot be
obtained unless all servo amplifiers are operated.
[Unit : mm]
Servo amplifier
MR-J3- B(4)
FR-BAL-(H)
MC
NFB
R
S
T
X
Y
Z
L1
3-phase
200 to 230VAC
or
3-phase
380 to 480VAC
L2
L3
Servo amplifier
FR-BAL
MR-J3-
B
MC
NFB
W
D1
R
S
T
X
Y
Z
L1
Installation screw
(Note)
1-phase
200v to 230VAC
L2
L3
RXSYT Z
W1
Servo amplifier
MR-J3- B1
C
FR-BAL
MC
NFB
R
S
T
X
Y
Z
1-phase
100 to120VAC
L1
Blank
L2
Note. For the 1-phase 200V to 230V power supply, Connect the power
supply to L1, L2 and leave L3 open.
11 - 74
11. OPTIONS AND AUXILIARY EQUIPMENT
Dimensions [mm]
Mounting
screw size screw size
Terminal
Mass
[kg (lb)]
Servo amplifier
Model
W
W1
120
120
145
145
200
200
255
H
D
D1
0
C
7.5
7.5
7.5
7.5
10
FR-BAL-0.4K
FR-BAL-0.75K
FR-BAL-1.5K
FR-BAL-2.2K
FR-BAL-3.7K
FR-BAL-7.5K
FR-BAL-11K
MR-J3-10B 20B 10B1
MR-J3-40B 20B1
MR-J3-60B 70B 40B1
MR-J3-100B
-2.5
135
135
160
160
220
220
280
115
115
140
140
192
194
220
59
45
57
M4
M4
M4
M4
M5
M5
M6
M3.5
M3.5
M3.5
M3.5
M4
2.0 (4.41)
2.8 (6.17)
0
-2.5
69
0
-2.5
71
55
3.7 (8.16)
0
-2.5
91
75
5.6 (12.35)
8.5 (18.74)
14.5 (31.97)
19 (41.89)
0
MR-J3-200B
-2.5
90
70
0
MR-J3-350B
-2.5
120
135
100
100
10
M5
0
-2.5
MR-J3-500B
MR-J3-700B
MR-J3-11KB
MR-J3-15KB
12.5
M6
0
FR-BAL-15K
-2.5
295
270
275
133
110
12.5
M6
M6
27 (59.53)
FR-BAL-22K
170 5
290
290
160
160
220
220
280
240
240
145
145
200
200
255
301
301
140
140
190
192
226
199
219
87
25
25
M8
M8
M4
M4
M5
M5
M6
M8
M8
35 (77.16)
43 (94.80)
5.3 (11.68)
5.9 (13.01)
8.5 (18.74)
14 (30.87)
18.5 (40.79)
FR-BAL-30K
190 5
MR-J3-22KB
MR-J3-60B4
MR-J3-100B4
MR-J3-200B4
MR-J3-350B4
MR-J3-500B4
0
FR-BAL-H1.5K
FR-BAL-H2.2K
FR-BAL-H3.7K
FR-BAL-H7.5K
FR-BAL-H11K
-2.5
70
7.5
7.5
10
M3.5
M3.5
M3.5
M4
0
-2.5
91
75
0
-2.5
90
70
100 5
100 5
120
130
10
12.5
M5
MR-J3-700B4
MR-J3-11KB4
FR-BAL-H15K
FR-BAL-H22K
110 5
170 5
295
290
270
240
244
269
130
199
12.5
25
M6
M8
M5
M8
27 (59.53)
Approx.35
(Approx.77.16)
Approx.43
MR-J3-15KB4
MR-J3-22KB4
FR-BAL-H30K
190 5
290
240
290
219
25
M8
M8
(Approx.94.80)
11.15 Relays (recommended)
The following relays should be used with the interfaces.
Interface
Selection example
Relay used for digital input command signals (interface DI-1) To prevent defective contacts , use a relay for small signal
(twin contacts).
(Ex.) Omron : type G2A , MY
Relay used for digital output signals (interface DO-1)
Small relay with 12VDC or 24VDC of rated current 40mA or
less
(Ex.) Omron : type MY
11 - 75
11. OPTIONS AND AUXILIARY EQUIPMENT
11.16 Surge absorbers (recommended)
A surge absorber is required for the electromagnetic brake. Use the following surge absorber or equivalent.
When using the surge absorber, perform insulation beforehand to prevent short-circuit.
Maximum rating
Surge
Static capacity
(reference
value)
Maximum
Varistor voltage
Permissible circuit
voltage
Energy
immunity
[J]
Rated
power
[W]
limit voltage
rating (range) V1mA
immunity
[A]
AC[Vma]
DC[V]
[A]
25
[V]
[pF]
[V]
(Note)
220
140
180
5
0.4
360
300
500/time
(198 to 242)
Note. 1 time
8
20 s
[Unit: mm]
13.5
4.7 1.0
(Example) ERZV10D221 (Matsushita Electric Industry)
TNR-10V221K (Nippon chemi-con)
Outline drawing [mm] (ERZ-C10DK221)
0.8
11.17 Noise reduction techniques
Noises are classified into external noises which enter the servo amplifier to cause it to malfunction and those
radiated by the servo amplifier to cause peripheral devices to malfunction. Since the servo amplifier is an
electronic device which handles small signals, the following general noise reduction techniques are required.
Also, the servo amplifier can be a source of noise as its outputs are chopped by high carrier frequencies. If
peripheral devices malfunction due to noises produced by the servo amplifier, noise suppression measures
must be taken. The measures will vary slightly with the routes of noise transmission.
(1) Noise reduction techniques
(a) General reduction techniques
Avoid laying power lines (input and output cables) and signal cables side by side or do not bundle
them together. Separate power lines from signal cables.
Use shielded, twisted pair cables for connection with the encoder and for control signal transmission,
and connect the shield to the SD terminal.
Ground the servo amplifier, servo motor, etc. together at one point (refer to section 3.12).
(b) Reduction techniques for external noises that cause the servo amplifier to malfunction
If there are noise sources (such as a magnetic contactor, an electromagnetic brake, and many relays
which make a large amount of noise) near the servo amplifier and the servo amplifier may malfunction,
the following countermeasures are required.
Provide surge absorbers on the noise sources to suppress noises.
Attach data line filters to the signal cables.
Ground the shields of the encoder connecting cable and the control signal cables with cable clamp
fittings.
Although a surge absorber is built into the servo amplifier, to protect the servo amplifier and other
equipment against large exogenous noise and lightning surge, attaching a varistor to the power input
section of the equipment is recommended.
11 - 76
11. OPTIONS AND AUXILIARY EQUIPMENT
(c) Techniques for noises radiated by the servo amplifier that cause peripheral devices to malfunction
Noises produced by the servo amplifier are classified into those radiated from the cables connected to
the servo amplifier and its main circuits (input and output circuits), those induced electromagnetically or
statically by the signal cables of the peripheral devices located near the main circuit cables, and those
transmitted through the power supply cables.
Noise radiated directly
from servo amplifier
Noises produced
by servo amplifier
Noises transmitted
in the air
Route 1)
Route 2)
Route 3)
Noise radiated from the
power supply cable
Noise radiated from
servo motor cable
Magnetic induction
noise
Routes 4) and 5)
Static induction
noise
Route 6)
Noises transmitted
through electric
channels
Noise transmitted through
power supply cable
Route 7)
Route 8)
Noise sneaking from
grounding cable due to
leakage current
5)
7)
7)
2)
1)
7)
Sensor
power
supply
Servo
amplifier
2)
Instrument
Receiver
3)
8)
6)
Sensor
4)
3)
Servo motor
M
11 - 77
11. OPTIONS AND AUXILIARY EQUIPMENT
Noise transmission route
Suppression techniques
When measuring instruments, receivers, sensors, etc. which handle weak signals and may malfunction
due to noise and/or their signal cables are contained in a control box together with the servo amplifier or
run near the servo amplifier, such devices may malfunction due to noises transmitted through the air. The
following techniques are required.
1. Provide maximum clearance between easily affected devices and the servo amplifier.
2. Provide maximum clearance between easily affected signal cables and the I/O cables of the servo
amplifier.
1) 2) 3)
3. Avoid laying the power lines (Input cables of the servo amplifier) and signal cables side by side or
bundling them together.
4. Insert a line noise filter to the I/O cables or a radio noise filter on the input line.
5. Use shielded wires for signal and power cables or put cables in separate metal conduits.
When the power lines and the signal cables are laid side by side or bundled together, magnetic
induction noise and static induction noise will be transmitted through the signal cables and malfunction
may occur. The following techniques are required.
1. Provide maximum clearance between easily affected devices and the servo amplifier.
2. Provide maximum clearance between easily affected signal cables and the I/O cables of the servo
amplifier.
4) 5) 6)
3. Avoid laying the power lines (I/O cables of the servo amplifier) and signal cables side by side or
bundling them together.
4. Use shielded wires for signal and power cables or put the cables in separate metal conduits.
When the power supply of peripheral devices is connected to the power supply of the servo amplifier
system, noises produced by the servo amplifier may be transmitted back through the power supply
cable and the devices may malfunction. The following techniques are required.
7)
8)
1. Insert the radio noise filter (
) on the power cables (Input cables) of the servo amplifier.
FR-BIF-(H)
2. Insert the line noise filter (FR-BSF01 FR-BLF) on the power cables of the servo amplifier.
When the cables of peripheral devices are connected to the servo amplifier to make a closed loop
circuit, leakage current may flow to malfunction the peripheral devices. If so, malfunction may be
prevented by disconnecting the grounding cable of the peripheral device.
(2) Noise reduction products
(a) Data line filter (Recommended)
Noise can be prevented by installing a data line filter onto the encoder cable, etc. For example, the
ZCAT3035-1330 of TDK and the ESD-SR-25 of NEC TOKIN make are available as data line filters. As a
reference example, the impedance specifications of the ZCAT3035-1330 (TDK) are indicated below.
This impedances are reference values and not guaranteed values.
[Unit: mm]
Impedance[ ]
10 to 100MHz
80
100 to 500MHz
150
39 1
34 1
Loop for fixing the
cable band
TDK
Product name Lot number
Outline drawing (ZCAT3035-1330)
11 - 78
11. OPTIONS AND AUXILIARY EQUIPMENT
(b) Surge suppressor
The recommended surge suppressor for installation to an AC relay, AC valve or the like near the servo
amplifier is shown below. Use this product or equivalent.
MC
Relay
Surge suppressor
Surge suppressor
This distance should be short
(within 20cm).
(Ex.) 972A.2003 50411
(Matsuo Electric Co.,Ltd. 200VAC rating)
Rated
voltage
AC[V]
Outline drawing [Unit: mm]
Vinyl sheath
C [ F]
0.5
R [ ]
Test voltage AC[V]
18 1.5
Blue vinyl cord
Red vinyl cord
50
Across
200
6
(1W)
T-C 1000(1 to 5s)
10 or less
10 or less
4
10 3
10 3
15 1
200 or more 48 1.5 200 or more
31
Note that a diode should be installed to a DC relay, DC valve or
the like.
RA
Maximum voltage: Not less than 4 times the drive voltage of the
relay or the like
Maximum current: Not less than twice the drive current of the
relay or the like
Diode
(c) Cable clamp fitting AERSBAN - SET
Generally, the earth of the shielded cable may only be connected to the connector's SD terminal.
However, the effect can be increased by directly connecting the cable to an earth plate as shown below.
Install the earth plate near the servo amplifier for the encoder cable. Peel part of the cable sheath to
expose the external conductor, and press that part against the earth plate with the cable clamp. If the
cable is thin, clamp several cables in a bunch.
The clamp comes as a set with the earth plate.
[Unit: mm]
Cable
Cable clamp
Earth plate
(A,B)
Strip the cable sheath of
the clamped area.
cutter
cable
External conductor
Clamp section diagram
11 - 79
11. OPTIONS AND AUXILIARY EQUIPMENT
Outline drawing
[Unit: mm]
Earth plate
Clamp section diagram
2- 5 hole
17.5
installation hole
L or less
10
22
6
(Note)M4 screw
35
Note. Screw hole for grounding. Connect it to the earth plate of the control box.
Type
A
B
C
Accessory fittings
clamp A: 2pcs.
clamp B: 1pc.
Clamp fitting
L
AERSBAN-DSET
AERSBAN-ESET
100
70
86
56
30
A
B
70
45
11 - 80
11. OPTIONS AND AUXILIARY EQUIPMENT
(d) Line noise filter (FR-BSF01, FR-BLF)
This filter is effective in suppressing noises radiated from the power supply side and output side of the
servo amplifier and also in suppressing high-frequency leakage current (zero-phase current) especially
within 0.5MHz to 5MHz band.
Connection diagram
Outline drawing [Unit: mm]
Use the line noise filters for wires of the main power supply (L1 L2
FR-BSF01 (for wire size 3.5mm2 (AWG12) or less))
Approx.110
L3) and of the motor power supply (U
V
W). Pass each of the
3-phase wires through the line noise filter an equal number of
times in the same direction. For the main power supply, the effect
of the filter rises as the number of passes increases, but generally
four passes would be appropriate. For the motor power supply,
passes must be four times or less. Do not pass the grounding
(earth) wire through the filter, or the effect of the filter will drop.
Wind the wires by passing through the filter to satisfy the required
number of passes as shown in Example 1. If the wires are too
thick to wind, use two or more filters to have the required number
of passes as shown in Example 2. Place the line noise filters as
close to the servo amplifier as possible for their best performance.
2-
5
95 0.5
Approx.65
33
Example 1
NFB MC
Servo amplifier
Power
supply
L1
L2
L3
Line noise
filter
FR-BLF(for wire size 5.5mm2 (AWG10) or more))
7
(Number of turns: 4)
Example 2
MC
NFB
Servo amplifier
130
85
Power
supply
L1
L2
L3
Line noise
filter
Two filters are used
(Total number of turns: 4)
160
180
(e) Radio noise filter (
FR-BIF-(H))
This filter is effective in suppressing noises radiated from the power supply side of the servo amplifier
especially in 10MHz and lower radio frequency bands. The FR-BIF (-H) is designed for the input only.
Connection diagram
Outline drawing (Unit: mm)
Make the connection cables as short as possible.
Grounding is always required.
Leakage current: 4mA
Red White Blue
Green
When using the FR-BIF with a single-phase power
supply, always insulate the wires that are not used
for wiring.
Servo amplifier
NFB
MC
L1
Power
supply
29
L2
5
hole
L3
29
Radio noise
filter FR-BIF
-(H)
58
200V class: FR-BIF
400V class: FR-BIF-H
7
44
11 - 81
11. OPTIONS AND AUXILIARY EQUIPMENT
(f) Varistors for input power supply (Recommended)
Varistors are effective to prevent exogenous noise and lightning surge from entering the servo amplifier.
When using a varistor, connect it between each phase of the input power supply of the equipment. For
varistors, the TND20V-431K, TND20V-471K and TND20V-102K, manufactured by NIPPON CHEMI-
CON, are recommended. For detailed specification and usage of the varistors, refer to the manufacturer
catalog.
Maximum rating
Static
capacity
(reference
value)
Varistor voltage
rating (range)
V1mA
Maximum limit
voltage
Power
supply
voltage
Rated
pulse
power
[W]
Permissible circuit Surge current
Energy
Varistor
voltage
immunity
immunity
AC[Vrms]
DC[V]
350
8/20 s[A]
2ms[J]
195
[A]
[V]
710
775
[pF]
1300
1200
[V]
100V class TND20V-431K
200V class TND20V-471K
275
300
10000/1 time
7000/2 time
7500/1 time
6500/2 time
430(387 to 473)
470(423 to 517)
385
215
1.0
100
400V class TND20V-102K
625
825
400
1650
500
1000(900 to 1100)
[Unit: mm]
D
H
T
E
(Note)L
min.
d
W
D
T
Model
Max.
Max.
Max.
1.0
0.05
1.0
TND20V-431K
TND20V-471K
TND20V-102K
6.4
6.6
9.5
3.3
3.5
6.4
21.5
24.5
20
0.8
10.0
22.5
25.5
Note. For special purpose items for lead length (L), contact the manufacturer.
W
E
d
11 - 82
11. OPTIONS AND AUXILIARY EQUIPMENT
11.18 Leakage current breaker
(1) Selection method
High-frequency chopper currents controlled by pulse width modulation flow in the AC servo circuits.
Leakage currents containing harmonic contents are larger than those of the motor which is run with a
commercial power supply.
Select a leakage current breaker according to the following formula, and ground the servo amplifier, servo
motor, etc. securely.
Make the input and output cables as short as possible, and also make the grounding cable as long as
possible (about 30cm) to minimize leakage currents.
Rated sensitivity current 10 {Ig1 Ign Iga K (Ig2 Igm)} [mA] (11.1)
K: Constant considering the harmonic contents
Cable
Leakage current breaker
K
Mitsubishi
products
Type
Noise
filter
NV
Servo
amplifier
Cable
Ig2
NV-SP
NV-SW
NV-CP
NV-CW
NV-L
M
Models provided with
harmonic and surge
reduction techniques
1
3
Ig1 Ign
Iga
Igm
BV-C1
NFB
General models
NV-L
Ig1:
Ig2:
Leakage current on the electric channel from the leakage current breaker to the input terminals of the
servo amplifier (Found from Fig. 11.3.)
Leakage current on the electric channel from the output terminals of the servo amplifier to the
servo motor (Found from Fig. 11.3.)
Ign:
Iga:
Igm:
Leakage current when a filter is connected to the input side (4.4mA per one FR-BIF(-H))
Leakage current of the servo amplifier (Found from Table 11.5.)
Leakage current of the servo motor (Found from Table 11.4.)
120
100
80
60
40
20
0
120
100
80
60
40
20
[mA]
[mA]
0
2
5.5 14 38 100
2
3.5 8 1422 38 80 150
5.5
30 60 100
3.5
8
22 60 150
30 80
Cable size[mm2]
b. 400V class
Cable size[mm2]
a. 200V class
Fig. 11.3 Leakage current example (lg1, lg2) for CV cable run in metal conduit
11 - 83
11. OPTIONS AND AUXILIARY EQUIPMENT
Table 11.4 Servo motor's leakage current example (Igm)
Table 11.5 Servo amplifier's leakage current example (Iga)
Servo motor power
[kW]
Leakage current
[mA]
Servo amplifier capacity
[kW]
Leakage current
[mA]
0.05 to 1
0.1
0.2
0.3
0.5
0.7
1.0
1.3
2.3
0.1 to 0.6
0.1
0.15
2
2
3.5
5
0.75 to 3.5 (Note)
5
7
11 15
22
5.5
7
7
11
15
22
Note. For the 3.5kW of 400V class, leakage current is 2mA,
which is the same as for 5kW and 7kW.
Table 11.6 Leakage circuit breaker selection example
Rated sensitivity current of leakage
Servo amplifier
circuit breaker [mA]
MR-J3-10B to MR-J3-350B
MR-J3-10B1 to MR-J3-40B1
MR-J3-60B4 to MR-J3-350B4
15
MR-J3-500B(4)
MR-J3-700B(4)
30
50
MR-J3-11KB(4) to MR-J3-22KB(4)
100
(2) Selection example
Indicated below is an example of selecting a leakage current breaker under the following conditions.
2mm2 5m
2mm2 5m
NV
Servo
Servo motor
HF-KP43
amplifier
MR-J3-40B
M
Ig1
Iga
Ig2
Igm
Use a leakage current breaker generally available.
Find the terms of Equation (11.1) from the diagram.
5
1000
Ig1
Ig2
20
20
0.1 [mA]
0.1 [mA]
5
1000
Ign 0 (not used)
Iga 0.1 [mA]
Igm 0.1 [mA]
Insert these values in Equation (11.1).
Ig 10 {0.1 0 0.1 1 (0.1 0.1)}
4.0 [mA]
According to the result of calculation, use a leakage current breaker having the rated sensitivity current (Ig)
of 4.0[mA] or more. A leakage current breaker having Ig of 15[mA] is used with the NV-SP/SW/CP/CW/HW
series.
11 - 84
11. OPTIONS AND AUXILIARY EQUIPMENT
11.19 EMC filter (recommended)
For compliance with the EMC directive of the EN Standard, it is recommended to use the following filter. Some
EMC filters are large in leakage current.
(1) Combination with the servo amplifier
Recommended filter (Soshin Electric)
Servo amplifier
Mass [kg]([lb])
3 (6.61)
Model
Leakage current [mA]
MR-J3-10B to MR-J3-100B
MR-J3-10B1 to MR-J3-40B1
MR-J3-250B MR-J3-350B
MR-J3-500B MR-J3-700B
MR-J3-11KB to MR-J3-22KB
MR-J3-60B4 MR-J3-100B4
MR-J3-200B4 to MR-J3-700B4
MR-J3-11KB4
(Note) HF3010A-UN
5
(Note) HF3030A-UN
(Note) HF3040A-UN
(Note) HF3100A-UN
TF3005C-TX
5.5 (12.13)
6.0 (13.23)
15 (33.07)
1.5
6.5
6(13.23)
7.5(16.54)
12.5(27.56)
TF3020C-TX
5.5
TF3030C-TX
MR-J3-15KB4
TF3040C-TX
MR-J3-22KB4
TF3060C-TX
Note. A surge protector is separately required to use any of these EMC filters.
(2) Connection example
EMC filter
Servo amplifier
NFB
MC
1
2
3
4
5
6
E
L1
L2
L3
(Note 1)
Power supply
L11
L21
(Note 2)
Surge protector 1
(RAV-781BYZ-2)
1
2
3
(OKAYA Electric Industries Co., Ltd.)
(Note 2)
Surge protector 2
(RAV-781BXZ-4)
1
2
3
(OKAYA Electric Industries Co., Ltd.)
Note 1. For 1-phase 200V to 230VAC power supply, connect the power supply to L1,L2 and leave L3 open.
There is no L3 for 1-phase 100 to 120VAC power supply. Refer to section 1.3 for the power supply specification.
2. The example is when a surge protector is connected.
11 - 85
11. OPTIONS AND AUXILIARY EQUIPMENT
(3) Outline drawing
(a) EMC filter
HF3010A-UN
[Unit: mm]
3-M4
4-5.5
7
3-M4
M4
IN
Approx.41
258
273
288
300
4
2
4
5
65
4
HF3030A-UN HF-3040A-UN
6-K
3-L
3-L
M
J
2
C
1
C
1
H
2
B
A
2
5
Dimensions [mm]
Model
A
B
C
D
E
F
G
H
J
K
L
M
HF3030A-UN
HF3040A-UN
260
210
85
155
140
125
44
140
70
R3.25,
length
8
M5
M4
260
210
85
155
140
125
44
140
70
M5
M4
11 - 86
11. OPTIONS AND AUXILIARY EQUIPMENT
HF3100A-UN
2- 6.5
2-6.5
8
M8
M8
M6
380 1
400 5
TF3005C-TX TX3020C-TX TF3030C-TX
[Unit: mm]
3-M4
6-R3.25 length8
M4 M4
3 M4
M4
IN
Approx.67.5
3
100 1
100 1
290 2
308 5
332 5
150 2
Approx.160
170 5
11 - 87
11. OPTIONS AND AUXILIARY EQUIPMENT
TF3040C-TX TF3060C-TX
[Unit: mm]
3-M6
8-M
M4 M4
3-M6
M6
IN
D 1
D 1
C 2
B 5
A 5
D 1
L
K 2
J
H 5
Dimensions [mm]
Model
A
B
C
D
E
F
G
H
J
K
L
M
R3.25
length 8
(M6)
TF3040C-TX
TF3060C-TX
438 412 390 100 175 160 145 200
Approx.190
180 Approx.91.5
11 - 88
11. OPTIONS AND AUXILIARY EQUIPMENT
(b) Surge protector
RAV-781BYZ-2
[Unit: mm]
1)
2)
3)
Black Black Black
4.2 0.2
UL-1015AWG16
1
2
3
41 1.0
[Unit: mm]
RAV-781BXZ-4
1)
2)
3)
4)
4.2 0.2
UL-1015AWG16
1
2
3
41 1.0
11 - 89
11. OPTIONS AND AUXILIARY EQUIPMENT
MEMO
11 - 90
12. ABSOLUTE POSITION DETECTION SYSTEM
12. ABSOLUTE POSITION DETECTION SYSTEM
If an absolute position erase alarm (25) or absolute position counter warning (E3)
has occurred, always perform home position setting again. Not doing so can cause
runaway. Not doing so may cause unexpected operation.
CAUTION
POINT
If the encoder cable is disconnected, absolute position data will be lost in the
following servo motor series. HF-MP, HF-KP, HC-SP, HC-RP, HC-UP, HC-LP,
and HA-LP. After disconnecting the encoder cable, always execute home
position setting and then positioning operation.
12.1 Features
For normal operation, as shown below, the encoder consists of a detector designed to detect a position within
one revolution and a cumulative revolution counter designed to detect the number of revolutions.
The absolute position detection system always detects the absolute position of the machine and keeps it
battery-backed, independently of whether the servo system controller power is on or off.
Therefore, once home position return is made at the time of machine installation, home position return is not
needed when power is switched on thereafter.
If a power failure or a fault occurs, restoration is easy.
Servo system controller
Servo amplifier
Position data
Current
position
Detecting
Detecting the
position within
Home position data
the number
LS0
of revolutions one revolution
CYC0
MR-J3BAT
Battery
Servo motor
High speed serial
communication
1 pulse/rev accumulative revolution counter
Within one-revolution counter
12 - 1
12. ABSOLUTE POSITION DETECTION SYSTEM
12.2 Specifications
POINT
Replace the battery with only the control circuit power ON. Removal of the battery
with the control circuit power OFF will erase the absolute position data.
(1) Specification list
Item
Description
System
Battery
Electronic battery backup system
1 piece of lithium battery ( primary battery, nominal 3.6V)
Type: MR-J3BAT
Maximum revolution range
Home position 32767 rev.
(Note 1) Maximum speed at power failure
(Note 2) Battery backup time
Battery storage period
3000r/min
Approx. 10,000 hours (battery life with power off)
5 years from date of manufacture
Note 1. Maximum speed available when the shaft is rotated by external force at the time of power failure or the like.
2. Time to hold data by a battery with power off. It is recommended to replace the battery in three years independently of
whether power is kept on or off.
(2) Configuration
Servo amplifier
CN1 CN2
CN4
Servo system controller
Battery
(MR-J3BAT)
Servo motor
(3) Parameter setting
Set "
1" in parameter No.PA03 to make the absolute position detection system valid.
Parameter No.PA03
Absolute position detection system selection
0: Used in incremental system
1: Used in absolute position detection system
12 - 2
12. ABSOLUTE POSITION DETECTION SYSTEM
12.3 Battery installation procedure
Before installing a battery, turn off the main circuit power while keeping the control
circuit power on. Wait for 15 minutes or more (20 minutes or for drive unit 30kW or
more) until the charge lamp turns off. Then, confirm that the voltage between P(
and N( ) (L and L for drive unit 30kW or more) is safe with a voltage tester
and others. Otherwise, an electric shock may occur. In addition, always confirm
from the front of the servo amplifier whether the charge lamp is off or not.
)
WARNING
POINT
The internal circuits of the servo amplifier may be damaged by static electricity.
Always take the following precautions.
Ground human body and work bench.
Do not touch the conductive areas, such as connector pins and electrical parts,
directly by hand.
Before starting battery changing procedure, make sure that the main circuit
power is switched OFF with the control circuit power ON. When battery is
changed with the control power OFF, the absolute position data is lost.
(1) For MR-J3-350B or less MR-J3-200B4 or less
POINT
For the servo amplifier with a battery holder on the bottom, it is not possible to
wire for the earth with the battery installed. Insert the battery after executing
the earth wiring of the servo amplifier.
Insert connector into CN4.
12 - 3
12. ABSOLUTE POSITION DETECTION SYSTEM
(2) For MR-J3-500B or more MR-J3-350B4 or more
Insert connector into CN4.
12 - 4
12. ABSOLUTE POSITION DETECTION SYSTEM
12.4 Confirmation of absolute position detection data
You can confirm the absolute position data with MR Configurator.
Choose "Diagnostics" and "Absolute Encoder Data" to open the absolute position data display screen.
(1) Choosing "Diagnostics" in the menu opens the sub-menu as shown below:
(2) By choosing "Absolute Encoder Data" in the sub-menu, the absolute encoder data display window appears.
(3) Press the "Close" button to close the absolute encoder data display window.
12 - 5
12. ABSOLUTE POSITION DETECTION SYSTEM
MEMO
12 - 6
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
This chapter explains the MELSERVO-J3-B series AC servo featuring a large capacity of 200V (30k to
37kW)/400V (30k to 55kW).
Explanation made in this chapter is exclusively for the MR-J3-CR (4) converter units and the MR-J3-DU B(4)
drive units. Explanations on the following items are the same as those for servo amplifiers with 22kW or less.
For such explanations, refer to the section indicated in the table.
Item
Reference
Chapter 4
Chapter 6
Chapter 7
Chapter 12
Startup
General gain adjustment
Special adjustment functions
Absolute position detection system
13.1. Functions and menus
POINT
Explanations on the following item are the same as those for servo amplifiers
with 22kW or less. Refer to the section below for details.
Function list section 1.4
13 - 1
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.1.1 Function block diagram
The function block diagram of this servo is shown below.
Power factor Regenerative
improving DC option
Converter
P1
P2
C
Diode
stack
Thyristor
NFB
MC
L
L
L1
L2
L3
L
L
Power
supply
CHARGE
lamp
Regenerative
TR
Cooling fan
L11
Control
power
supply
L21
Base
amplifier
Voltage
detection
Current
detection
CPU
I/F
CNP1
CN1
CN40
Converter unit
protection coordination
CN40
MC drive
Trouble, warning, forced stop
L11
L21
13 - 2
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
NFB
(Note)
Power
supply
Drive unit
Servo motor
L
U
V
U
V
L
L
Current
detector
M
W
W
L
Cooling fan
11
21
L
L11
Control
power
supply
L
L21
Base amplifier
Over
current
Current
detection
Encoder
BU
BV
BW
Cooling fan
Virtual
encoder
Position command
input
Model position
control
Model speed
control
Servo motor
thermal
Virtual
motor
OHS1
OHS2
Model position
Model speed
Model torque
Actual position
control
Actual speed
control
Current
control
CN40
Termination
connector
MR-J3-TM
(Option)
MR-J3BAT
D/A
USB
I/F
Control
Optional battery
(For absolute position detection
system)
CN3
CN1A
CN1B
CN5
Personal
computer
Controller
or
drive unit
Drive unit
or
cap
Analog monitor
(2 channel)
Digital I/O
control
USB
Note. Refer to section 13.3.6 for the power supply specification of the servo motor cooling fan.
13 - 3
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.1.2 Packing list
Unpack the product and check the rating plate to see if the converter unit, drive unit and servo motor are as you
ordered.
(1) Converter unit
POINT
Regenerative resistor and power factor improving DC reactors are option.
Purchase them separately if required. (Section 13.9.2, 13.9.6)
Magnetic contactor
wiring connector
[pcs.] (Note)
To use the AC
servo safely
[manuals]
Converter unit
[units]
Eyebolt
[pcs.]
Digital I/O connector
[pcs.]
Model
MR-J3-CR55K
MR-J3-CR55K4
1
2
1
1
1
Note. Magnetic contactor control connector is mounted to CNP1 of the converter unit before shipping.
(2) Drive unit
Connection
Drive unit
To use the AC
servo safely
[manuals]
Eyebolt
[pcs.]
Model
conductor
[pcs.]
[units]
MR-J3-DU30KB MR-J3-DU37KB
MR-J3-DU30KB4 to MR-J3-DU55KB4
1
2
2
1
(3) Servo motor
To use the AC
servo safely
[manuals]
Servo motor
[units]
Model
HA-LP30K1 HA-LP37K1
HA-LP30K1M HA-LP37K1M
HA-LP30K2 HA-LP37K2
1
1
HA-LP25K14 to HA-LP37K14
HA-LP30K1M4 to HA-LP50K1M4
HA-LP30K24 to HA-LP55K24
13 - 4
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.1.3 Standard specifications
(1) Converter unit
Model
MR-J3-CR55K
MR-J3-CR55K4
Item
Voltage/frequency
Permissible voltage
fluctuation
3-phase 200 to 230VAC, 50/60Hz
3-phase 170 to 253VAC
3-phase 380 to 480VAC, 50/60Hz
3-phase 323 to 528VAC
Main circuit power
supply
Permissible frequency
fluctuation
Within 5%
Voltage/frequency
Permissible voltage
fluctuation
1-phase 200 to 230VAC, 50/60Hz
1-phase 170 to 253VAC
1-phase 380 to 480VAC, 50/60Hz
1-phase 323 to 528VAC
Control power
supply
Permissible frequency
fluctuation
Within 5%
45W
Power consumption
Voltage
Interface power
supply
24VDC 10%
(Note) 130mA
55kW
Power supply capacity
Rated output
Regenerative power
One MR-RB139: 1300W
Three MR-RB137: 3900W
One MR-RB136-4: 1300W
Three MR-RB138-4: 3900W
(Using regenerative option)
Protective function
Structure
Regenerative overvoltage shutoff, overload shutoff (electronic thermal protector)
Regenerative alarm protection, undervoltage, instantaneous power failure protection
Force-cooling, open (IP00)
[
[
[
[
]
]
]
]
0 to 55 (non-freezing)
In operation
Ambient
32 to 131 (non-freezing)
temperature
20 to 65 (non-freezing)
In storage
4 to 149 (non-freezing)
Ambient
humidity
In operation
In storage
90%RH or less (non-condensing)
Indoors (no direct sunlight)
Ambient
Altitude
Vibration
Free from corrosive gas, flammable gas, oil mist, dust and dirt
Max. 1000m above sea level
5.9 [m/s2] or less
19.4 [ft/s2] or less
[kg]
[lb]
25
Mass
55.1
Note. 130mA is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of
I/O points.
13 - 5
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(2) Drive unit
(a) 200V class
Model
MR-J3-DU30KB
MR-J3-DU37KB
Item
Voltage/frequency
Permissible voltage
fluctuation
1-phase 200 to 230VAC, 50/60Hz
1-phase 170 to 253VAC
Within 5%
Control power
supply
Permissible frequency
fluctuation
Power consumption
45W
The main circuit power of the drive unit is supplied by the converter unit.
24VDC 10%
Main circuit power supply
Interface power
supply
Voltage
Power supply capacity
(Note) 150mA
Control system
Dynamic brake
Sine-wave PWM control, current control system
External option
Overcurrent shut-off, overload shutoff (electronic thermal protector)
Servo motor overheat protection, encoder error protection, undervoltage
Instantaneous power failure protection, overspeed protection
Excessive error protection
Protective function
Structure
Force-cooling, open (IP00)
[
[
[
[
]
]
]
]
0 to 55 (non-freezing)
In operation
In storage
Ambient
32 to 131 (non-freezing)
temperature
20 to 65 (non-freezing)
4 to 149 (non-freezing)
Ambient
humidity
In operation
In storage
90%RH or less (non-condensing)
Indoors (no direct sunlight)
Ambient
Altitude
Vibration
Free from corrosive gas, flammable gas, oil mist, dust and dirt
Max. 1000m above sea level
5.9 [m/s2] or less
19.4 [ft/s2] or less
[kg]
[lb]
26
Mass
57.3
Note. 150mA is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of
I/O points.
13 - 6
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(b) 400V class
Model
MR-J3-DU30KB4
MR-J3-DU37KB4
MR-J3-DU45KB4
MR-J3-DU55KB4
Item
Voltage/frequency
Permissible voltage
fluctuation
1-phase 380 to 480VAC, 50/60Hz
1-phase 323 to 528VAC
Control power
supply
Permissible frequency
fluctuation
Within 5%
45W
Power consumption
Main circuit power supply
The main circuit power of the drive unit is supplied by the converter unit.
24VDC 10%
Interface power
supply
Voltage
Power supply capacity
(Note)150mA
Control system
Dynamic brake
Sine-wave PWM control, current control system
External option
Overcurrent shut-off, overload shutoff (electronic thermal protector)
Servo motor overheat protection, encoder error protection, undervoltage
Instantaneous power failure protection, overspeed protection
Excessive error protection
Protective function
Structure
Force-cooling, open(IP00)
[
[
[
[
]
]
]
]
0 to 55 (non-freezing)
In operation
In storage
Ambient
32 to 131 (non-freezing)
temperature
20 to 65 (non-freezing)
4 to 149 (non-freezing)
Ambient
humidity
In operation
In storage
90%RH or less (non-condensing)
Indoors (no direct sunlight)
Free from corrosive gas, flammable gas, oil mist, dust and dirt
Max. 1000m above sea level
Ambient
Altitude
Vibration
5.9 [m/s2] or less
19.4 [ft/s2] or less
[kg]
[lb]
18
26
Mass
39.7
57.3
Note. 150mA is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of
I/O points.
13 - 7
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.1.4 Model definition
(1) Rating plate
ACSERVO
MITSUBISHI
Model
MODE
MR-J3-CR55K
Capacity
POWER : 55kW
Applicable power supply
INPUT : AC200V-230V 50/60Hz
Rated output current
Serial number
OUTPUT :
SERIAL : A5*******
PASSED
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
(2) Model
(a) Converter unit
Power supply
Symbol Power supply
None 3-phase 200 to 230VAC
3-phase 380 to 480VAC
Series
4
Indicates converter unit.
Rated output: 55kW
(b) Drive unit
Power supply
Symbol Power supply
None 3-phase 200 to 230VAC
3-phase 380 to 480VAC
Series
4
Indicates drive unit.
SSCNET compatible
Rated output
Rated output [kW]
200V class 400V class
Symbol
30K
37K
45K
55K
30
37
30
37
45
55
13 - 8
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.1.5 Combinations of converter units, drive unit and servo motors
The following tables indicate the combinations of the converter units, drive unit and servo motors.
(1) 200V class
Servo motor
Converter unit
MR-J3-CR55K
Drive unit
HA-LP
1500r/min
30K1M
1000r/min
30K1
2000r/min
30K2
MR-J3-DU30KB
MR-J3-DU37KB
37K1
37K1M
37K2
(2) 400V class
Servo motor
HA-LP
Converter unit
Drive unit
1000r/min
1500r/min
2000r/min
30K24
25K14
30K14
37K14
MR-J3-DU30KB4
30K1M4
MR-J3-CR55K4
MR-J3-DU37KB4
MR-J3-DU45KB4
MR-J3-DU55KB4
37K1M4
45K1M4
50K1M4
37K24
45K24
55K24
13 - 9
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.1.6 Parts identification
(1) Converter unit (MR-J3-CR55K(4))
POINT
The servo amplifier is shown without the front cover. For removal of the front
cover, refer to section 13.1.7.
Detailed
explanation
Name/Application
Magnetic contactor control connector (CNP1)
Connect to the operation coil of the magnetic contactor.
Section 13.3.4
I/O signal connector (CN1)
Used to connect digital I/O signals.
Charge lamp
Lit to indicate that the main circuit is charged. While
this lamp is lit, do not reconnect the cables.
Display
Fixed part
(4 places)
The 3-digit, seven-segment LED shows the servo status
and alarm number.
Cooling fan
Operation section
Used to perform status display, diagnostic, alarm,
parameter and point table setting operations.
Section 13.4
DOWN
MODE
UP
SET
Used to set data.
Used to change the
display or data in each
mode.
Used to change the
mode.
For manufacturer setting connector (CN6)
The connector is for manufacturer setting. Although the
shape is similar to analog monitor connector (CN6) of the
drive unit, do not connect anything including an analog
monitor.
Protection coordination connector (CN40)
Connect to CN40A of the drive unit.
For manufacturer setting connector (CN3)
For manufacturer adjustment. Though the shape is similar
to RS-422 communication connector (CN3), do not
connect anything, including a personal computer and MR-
PRU03 parameter unit.
L
L
terminal (TE2-2)
Used to connect to a drive unit using a connection
conductor supplied with drive unit.
Control circuit terminal L11 L21(TE3)
Supply control circuit power.
Regenerative option Power factor improving DC reactor
(TE1-2)
Section 13.3.3
Protective earth (PE) terminal (
Ground terminal.
)
Main circuit terminal block (TE1-1)
Supply main circuit power.
L
L
terminal (TE2-1)
When using brake unit, connect it to this terminal. Do not Section 13.9.10
connect anything other than the brake unit.
Rating plate
Section 13.1.4
13 - 10
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(2) Drive unit (MR-J3-DU30KB4 MR-J3-DU37KB4)
POINT
The servo amplifier is shown with the front cover opened. For removal of the
front cover, refer to section 13.1.7.
Detailed
explanation
Name/Application
Display
Chapter 4
The 3-digit, seven-segment LED shows the servo
status and alarm number.
Rotary axis setting switch (SW1)
SW1
8
Used to set the axis No. of drive unit.
Section 3.13
8
0
0
ON 4F
SW1
TEST
SW2
Test operation select switch (SW2-1)
SW2
1
2
Used to perform the test operation mode
Section 3.13
Section 11.8
by using MR Configurator.
Spare (Be sure to set to the "Down"
position).
1
2
USB communication connector (CN5)
Connect with the personal computer.
Fixed part
(4 places)
Cooling fan
I/O signal connector (CN3)
Used to connect digital I/O signals.
More over an analog monitor is output
Section 3.2
Section 3.4
SSCNET cable connector (CN1A)
Used to connect the servo system controller or the front
axis drive unit.
Battery holder
Contains the battery for absolute position data backup.
Section 12.3
SSCNET cable connector (CN1B)
Used to connect the rear axis drive unit. For the final axis,
puts a cap.
Section 3.2
Section 3.4
Encoder connector (CN2)
Used to connect the servo motor encoder.
Section 3.4
Section 11.1
Battery connector (CN4)
Used to connect the battery for absolute position data
Section 11.9
Chapter 12
Converter unit connectors (CN40A)
Connect to CN40 of the converter unit.
Section 13.3.2
Converter unit connectors (CN40B)
Connect the termination connector (MR-J3-TM).
L
L
terminals (TE2)
Connect to the L terminals of the converter unit
L
using the connection conductors supplied.
Control circuit terminal L11 L21 (TE3)
Supply control circuit power.
Section 13.3.3
Section 13.1.4
Motor power supply terminals (TE1)
Connect to U, V, W of the servo motor.
Protective earth (PE) terminal (
Ground terminal.
)
Rating plate
13 - 11
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(3) Drive unit (MR-J3-DU30KB MR-J3-DU37KB MR-J3-DU45KB4 MR-J3-DU55KB4)
POINT
This servo amplifier is shown without the front cover. For removal of the front
cover, refer to section 13.1.7.
Detailed
Name/Application
explanation
Display
The 3-digit, seven-segment LED shows the servo
status and alarm number.
Chapter 4
Rotary axis setting switch (SW1)
SW1
8
Used to set the axis No. of drive unit.
8
0
0
Section 3.13
ON 4F
SW1
TEST
SW2
Test operation select switch (SW2-1)
SW2
1
2
Used to perform the test operation mode
by using MR Configurator.
Spare (Be sure to set to the "Down"
1
2
position).
USB communication connector (CN5)
Connect with the personal computer.
Section 11.8
Cooling fan
fixed part
(4 places)
I/O signal connector (CN3)
Used to connect digital I/O signals.
More over an analog monitor is output
Section 3.2
Section 3.4
SSCNET cable connector (CN1A)
Used to connect the servo system controller or the front
axis drive unit.
Battery holder
Contains the battery for absolute position data backup.
Section 12.3
SSCNET cable connector (CN1B)
Used to connect the rear axis drive unit. For the final axis,
puts a cap.
Section 3.2
Section 3.4
Encoder connector (CN2)
Section 3.4
Section 11.1
Used to connect the servo motor encoder.
Battery connector (CN4)
Used to connect the battery for absolute position data
Section 11.9
Chapter 12
Converter unit connectors (CN40A)
Connect to CN40 of the converter unit.
Section 13.3.2
Converter unit connectors (CN40B)
Connect the termination connector (MR-J3-TM).
TE2-2
For manufacturer adjustment. Leave this open.
Control circuit terminal L11 L21 (TE3)
Supply control circuit power.
Motor power supply terminals (TE1)
Connect to U, V, W of the servo motor.
Section 13.3.3
Section 13.1.4
Protective earth (PE) terminal (
Ground terminal.
)
L
L
terminals (TE2)
Connect to the L
L
terminals of the converter unit
using the connection conductors supplied.
Rating plate
13 - 12
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.1.7 Removal and reinstallation of the terminal block cover
Before removing or installing the front cover, turn off the power and wait for 20
minutes or more until the charge lamp turns off. Then, confirm that the voltage
between L and L is safe with a voltage tester and others. Otherwise, an
CAUTION
electric shock may occur. In addition, always confirm from the front of the servo
amplifier whether the charge lamp is off or not.
(1) MR-J3-CR55K(4), MR-J3-DU30KB, MR-J3-DU37KB, MR-J3-DU45KB4 or MR-J3-DU55KB4
Here, the method for removing and reinstalling the terminal block cover using the figure of converter unit as
an example. For a drive unit, the shape of the main unit is different. However, the removal and reinstallation
of the terminal block can be performed in the same procedure.
(a) How to remove the terminal block cover
Remove the installation screws (A), B), C), D)) on
the four corners of the terminal block cover.
A)
B)
D)
C)
Pull the terminal block cover toward you and
remove it.
13 - 13
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(b) How to reinstall the terminal block cover
1) Put the terminal block cover on and match the
screw holes of the cover fit with those of the
main unit.
2) Install the installing screws into the screw holes
(A), B), C), D)).
A)
1)
B)
D)
C)
2) Mounting screw
13 - 14
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(2) MR-J3-DU30KB4 or MR-J3-DU37KB4
(a) Upper terminal block cover
1) How to open
Pull up the cover using the axis A), A)' as a
support.
A)
A)'
When pulled up to the top, the cover is fixed.
13 - 15
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
2) How to close
Close the cover using the axis A), A)' as a
support.
Setting tab
A)
A)'
Press the cover against the terminal box until
the installing knobs click.
Setting tab
13 - 16
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(b) Lower terminal block cover
1) How to open
Hold the bottom of the terminal block cover
with both hands.
Pull up the cover using the axis B), B)' as a
support.
B)
B)'
When pulled up to the top, the cover is fixed.
13 - 17
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
2) How to close
Hold the bottom of the terminal block cover
with both hands.
Setting tab
Setting tab
Close the cover using the axis B), B)' as a
support.
B)
B)'
Press the cover against the terminal box until
the installing knobs click.
Setting tab
13 - 18
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.1.8 Servo system with auxiliary equipment
R S T
3-phase AC
power supply
Personal
computer
MR Configurator
No-fuse
breaker(NFB)
The MR Configurator is required for
parameter setting.
Converter unit
Communication
cable
Magnetic
contactor(MC)
Drive unit(Note 3)
Line noise
filter(FR-BLF)
L
L
C
P2P1
(Note 1)
L
L1
L2
L3
L
L11
L21
(MR-J3CDL05M)
L11
L21
Magnetic contactor
operation coil
(I/O signal)
L11
L21
No-fuse
breaker(NFB)
P2
Power factor improving
DC reactor
Encoder cable
(MR-HSCBL M)
P1
(MR-DCL K)
(Note 2)
BU BV
BW
E U V W
Regenerative option
R
C
Servo motor
HA-LP series
S
P
Note 1. The L+ and L- connection conductors used to connect a converter unit to a drive unit are standard accessories. The converter
unit is attached to the drive unit actually. (Refer to section 13.2.1.)
2. The power supply of the servo motor cooling fan differs depending on the capacity of a servo motor. Refer to section 13.3.6.
3. For MR-J3-DU30KB4 or MR-J3-DU37KB4.
13 - 19
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.2 Installation
Stacking in excess of the limited number of products is not allowed.
Install the equipment to incombustibles. Installing them directly or close to
combustibles will led to a fire.
Install the equipment in a load-bearing place in accordance with this Instruction
Manual.
Do not get on or put heavy load on the equipment to prevent injury.
Use the equipment within the specified environmental condition range. (For the
environmental conditions, refer to section 13.1.3.)
Provide an adequate protection to prevent screws, metallic detritus and other
conductive matter or oil and other combustible matter from entering the converter
CAUTION
unit drive unit.
Do not block the intake/exhaust ports of the converter unit drive unit. Otherwise,
a fault may occur.
Do not subject the converter unit drive unit to drop impact or shock loads as they
are precision equipment.
Do not install or operate a faulty converter unit drive unit.
When the product has been stored for an extended period of time, consult
Mitsubishi.
When treating the converter unit drive unit, be careful about the edged parts
such as the corners of the converter unit drive unit.
POINT
Explanations on the following item are the same as those for servo amplifiers
with 22kW or less. Refer to the section below for details.
Keep out foreign materials Refer to section 2.2.
Cable stress Refer to section 2.3.
SSCNET cable laying Refer to section 2.4.
Parts Having Service Lives Refer to section 2.6.
13 - 20
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.2.1 Installation direction and clearances
Install the equipment in the specified direction. Not doing so can cause a failure.
Leave the specified clearances between the converter unit/drive unit and the
control box inside walls or other equipment. Not doing so can cause a failure.
CAUTION
(1) Installation
POINT
Make sure to connect a drive unit to the right side of a converter unit as
shown in the diagram.
Cooling fan
wind direction
100mm or
more
80mm or
more
Converter unit
Drive unit
30mm or
more
30mm or
more
Air
intake
120mm or more
Front view
Side view
(2) Mounting dimensional diagram
[Unit: mm]
Approx. W5
Approx. W3
Approx. 9.5
Approx. 20
Dimensions
W1 W2 W3 W4 W5
300
281
260
W1
W4
W2
Drive unit model
W5
W3
9.5
A
20
MR-J3-DU30KB, 37KB,
45KB4, 55KB4
MR-J3-DU30KB4,
37KB4
300 260 20 281 9.5 M6
240 120 60 222 M5
9
Converter unit
punched hole
Drive unit
punched hole
4-M6 screw
4-M6 screw
(3) Others
When using heat generating equipment such as the regenerative option, install them with full consideration
of heat generation so that the converter unit and drive unit is not affected.
Install the converter unit and drive unit on a perpendicular wall in the correct vertical direction.
13 - 21
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.2.2 Inspection
Before starting maintenance and/or inspection, turn off the power and wait for 20
minutes or more until the charge lamp turns off. Then, confirm that the voltage
between L and L is safe with a voltage tester and others. Otherwise, an
electric shock may occur. In addition, always confirm from the front of the converter
unit whether the charge lamp is off or not.
WARNING
CAUTION
Any person who is involved in inspection should be fully competent to do the work.
Otherwise, you may get an electric shock. For repair and parts replacement,
contact your safes representative.
POINT
Do not test the converter unit drive unit with a megger (measure insulation
resistance), or it may become faulty.
It is recommended to make the following checks periodically.
1) Check for loose terminal block screws. Retighten any loose screws.
2) Check the servo motor bearings, brake section, etc. for unusual noise.
3) Check the cables and the like for scratches and cracks. Perform periodic inspection according to operating
conditions.
4) Check the servo motor shaft and coupling for misalignment.
13 - 22
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.3 Signals and wiring
Any person who is involved in wiring should be fully competent to do the work.
Before wiring, turn off the power and wait for 20 minutes or more until the charge
lamp turns off. Then, confirm that the voltage between L and L is safe with a
voltage tester and others. Otherwise, an electric shock may occur. In addition,
always confirm from the front of the converter unit whether the charge lamp is off
or not.
WARNING
Ground the converter unit drive unit and the servo motor securely.
Do not attempt to wire the converter unit drive unit and servo motor until they
have been installed. Otherwise, you may get an electric shock.
The cables should not be damaged, stressed excessively, loaded heavily, or
pinched. Otherwise, you may get an electric shock.
Wire the equipment correctly and securely. Otherwise, the servo motor may
operate unexpectedly, resulting in injury.
Connect cables to correct terminals to prevent a burst, fault, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
The surge absorbing diode installed to the DC relay designed for control output
should be fitted in the specified direction. Otherwise, the signal is not output due to
a fault, disabling the forced stop (EM1) and other protective circuits.
Converter unit
drive unit
Converter unit
drive unit
24VDC
24VDC
DOCOM
DICOM
DOCOM
DICOM
Control
output
signal
Control
output
signal
RA
RA
CAUTION
Use a noise filter, etc. to minimize the influence of electromagnetic interference,
which may be given to electronic equipment used near the converter unit drive
unit.
Do not install a power capacitor, surge suppressor or radio noise filter (FR-BIF-(H)
option) with the power line of the servo motor.
When using the regenerative resistor, switch power off with the alarm signal.
Otherwise, a transistor fault or the like may overheat the regenerative resistor,
causing a fire.
Do not modify the equipment.
During power-on, do not open or close the motor power line. Otherwise, a
malfunction or faulty may occur.
13 - 23
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
POINT
Explanations on the following item are the same as those for servo amplifiers
with 22kW or less. Refer to the section below for details.
I/O signal connection example Refer to section 3.2.
Signal (device) explanations Refer to section 3.5.
Interfaces Refer to section 3.7.
Treatment of cable shield external conductor Refer to section 3.8.
SSCNET cable connection Refer to section 3.9.
Grounding Refer to section 3.12.
Control axis selection Refer to section 3.13.
The pins with the same signal name are connected in the drive unit.
13.3.1 Magnetic contactor control connector (CNP1)
Always connect the magnetic contactor wiring connector to the converter unit. If
the connector is not connected, an electric shock may occur since CNP1-1 and L11
are always conducting.
WARNING
By enabling the control function of the magnetic contactor (parameter No.PA02
1 (initial value)), main
circuit power supply can be shut off automatically when an alarm occurs on the converter unit or the drive unit.
Parameter No.PA02
1
Used to select the output of the external magnet contactor drive signal.
0: No used
1: Used (initial value)
13 - 24
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(1) Enabling control function of magnetic contactor (parameter No.PA02
Connecting the magnetic contactor control connector (CNP1) to the operating coil of the magnetic contactor
enables to control the magnetic contactor.
1 (initial value))
Converter unit
NFB
MC
L1
Power supply
L2
L3
L11
Control circuit
power supply
L21
CNP1
1
MC1
MC2
2
(Note)
Operation
-ready
OFF/ON
Drive unit Servo motor
trouble thermal relay
RA1 RA2 RA3
Forced stop
EM1
RA4
MC
SK
Controller
forced stop
Converter
unit trouble
Note. Stepdown transformer is required when coil voltage of the magnetic contactor is 200V class, and the converter unit and the drive
unit are 400V class.
When the converter unit receives a start command from the drive unit while the magnetic contactor control
connector (CNP1) is connected to the magnetic contactor (refer to section 13.3.2 (1)), CNP1-2 and L21
conduct in the converter unit. Then the control circuit power is supplied to turn ON the magnetic contactor
and the main circuit power is supplied to the converter unit.
Either when an alarm occurs on the converter unit or the drive unit while the control function of the magnetic
contactor is enabled, or when the forced stop (EM1) of the converter unit or the drive unit is turned OFF, the
switch between CNP1-2 and L21 in the converter unit is disconnected and the main circuit power supply is
automatically shut off.
To automatically shut off the main circuit power supply by alarm, enable the control function of the magnetic
contactor.
(2) Disabling control function of magnetic contactor (parameter No.PA02
0)
When not connecting the magnetic contactor control connector (CNP1) to the operating coil of the magnetic
contactor, configure the circuit to shut off the main circuit power supply when detecting an alarm since the
main circuit power supply is not automatically shut off even when an alarm occurs on the converter unit or
the drive unit.
13 - 25
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.3.2 Input power supply circuit
Insulate the connections of the power supply terminals. Not doing so can cause an
electric shock.
WARNING
Magnetic contactor wiring connector on the converter unit CNP1.
Unattached state may cause an electric shock.
Always, connect the magnetic contactor (MC) between the main circuit power
supply and L1, L2, and L3 of the converter unit, and configure to shut off the power
supply on the side of the converter unit power supply. If the magnetic contactor
(MC) is not connected, a large current keeps flowing and may cause a fire when
the converter unit or the drive unit malfunctions.
Use the trouble signal to switch power off. Otherwise, a regenerative transistor
fault or the like may overheat the regenerative resistor, causing a fire.
CAUTION
Connect the power supply phases (U, V, W) of the servo amplifier and servo motor
correctly. Not doing so can cause the servo motor to run abnormally.
Do not connect a 3-phase 200V power supply or a 3-phase 400V power supply
directly to the servo motor. Doing so can cause a failure.
POINT
Magnetic contactor control connector (CNP1) of the converter unit can be
made valid or invalid with parameter No.PA02 of the converter unit. Refer to
section 13.3.1 and 13.3.6 for details of CNP1 and section 13.5 for the
parameter settings.
When using the external dynamic brake, refer to section 11.6 and 13.9.3.
13 - 26
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(1) When magnetic contactor control connector (CNP1) is made valid (factory-set)
POINT
The converter unit controls the main circuit magnetic contactor.
Refer to section 13.3.7 (1) for the power circuit timing chart, section 13.3.7 (2)
for the alarm occurrence timing chart, section 13.3.7 (3) for the forced stop
(EM1) timing chart.
Always connect a protection coordination cable (MR-J3CDL05M) and a
termination connector (MR-J3-TM). When they are not connected properly,
the servo-on may not be turned ON.
For the control power supplies of the converter unit and the drive unit, always
turn ON or OFF at the same time.
(a) 200V class (MR-J3-DU30KB MR-J3-DU37KB)
Converter unit
Drive unit
Dynamic
brake
(Option)
TE2-2
L
TE2-1
L
NFB
MC
L
L
L1
Servo motor
M
3-phase
200 to 230VAC
50/60Hz
CN40
L2
CN40A
MR-J3CDL05M
cable
Termination
connector
MR-J3-TM
(Option)
L3
U
V
CN40B U
L11
L21
V
W
W
Encoder cable
NFB
CNP1 CN1
CN2
DICOM
MC1
MC2
1
2
1
5
6
2
7
9
Encoder
24VDC
BU
BV
BW
DOCOM
(Note 4)
Power
supply
Power factor improving
DC reactor (Option)
DICOM
Cooling fan
(Note 2)
ALM
RA2
P1
EM1
OHS2
24VDC
power supply
OHS1
P2
(Note 3)
Servo
motor
thermal
relay
DOCOM
C
RA3
CN3
10
P
C
P
C
P
C
DICOM
G3
G4
G3
G4
G3
G4
Regenerative
option(Note 1)
Regenerative
option(Note 1)
Regenerative
option(Note 1)
15 ALM
RA1
24VDC
Cooling fan
Cooling fan
Cooling fan
DICOM
5
R
S
R
S
R
S
DOCOM
3
20 EM1
Plate SD
L11
L21
(Note 3)
(Note 3) Operation
Drive
unit
RA1 RA2 RA3 RA4
Motor
-ready
Forced stop
thermal relay
EM1
OFF/ON
MC
SK
Controller
forced stop
Converter
unit
Note 1. For the MR-RB137. For the MR-RB137, three units are used as one set (permissible wattage: 3900W).
2. When using the Power factor improving DC reactor, disconnect the short bar across P1-P2.
3. Make up a sequence that turns off the drive unit forced stop (EM1) and the converter unit forced stop (EM1) at the same time.
4. For specifications of cooling fan power supply, refer to section 13.3.8.
13 - 27
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(b) 400V class (MR-J3-DU30KB4 to MR-J3-DU55KB4)
NFB
(Note 5)
Power
supply
Converter unit
Drive unit
TE2-2
L
TE2-1
L
L
L
Dynamic
brake
Dynamic
brake
CN40
CN40A
(Option)
NFB
(Option)
MR-J3CDL05M
cable
Termination
connector
MR-J3-TM
(Option)
MC
L1
L2
L3
CN40B
3-phase
380 to 480VAC
50/60Hz
Servo motor
M
U
V
CN1
1
L11
U
V
DICOM
L21
24VDC
W
DOCOM
5
6
2
7
9
W
CNP1
1
DICOM
MC1
MC2
CN2
BU
BV
BW
2
ALM
RA2
Encoder
Power factor improving
DC reactor (Option)
EM1
Encoder cable
(Note 3)
Cooling fan
DOCOM
P1
(Note 2)
P2
C
OHS1
OHS2
Servo motor
thermal relay
24VDC
power supply
RA3
P
C
P
C
P
C
CN3
10
G3
Regenerative
option(Note 1)
G4
G3
Regenerative
option(Note 1)
G4
G3
Regenerative
option(Note 1)
G4
DICOM
Cooling fan
R400S400
Cooling fan
R400S400
Cooling fan
R400S400
15 ALM
RA1
24VDC
DICOM
5
DOCOM
3
L11
20 EM1
Plate SD
L21
(Note 3)
(Note 4)
Drive
unit
Motor
Operation
-ready
Stepdown
(Note 3)
Forced stop
EM1
transformer
thermal relay
OFF/ON
RA1 RA2 RA3 RA4
MC
SK
Controller
forced stop
Converter
unit
Note 1. For the MR-RB138-4. For the MR-RB138-4, three units are used as one set (permissible wattage: 3900W).
2. When using the Power factor improving DC reactor, disconnect the short bar across P1-P2.
3. Make up a sequence that turns off the drive unit forced stop (EM1) and the converter unit forced stop (EM1) at the same time.
4. Stepdown transformer is required for coil voltage of magnetic contactor more than 200V class.
5. For specifications of cooling fan power supply, refer to section 13.3.8.
13 - 28
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(2) When magnetic contactor control connector (CNP1) is made invalid
POINT
The converter unit controls the main circuit magnetic contactor.
When making CNP1 invalid, set "0000" in parameter No.PA02.
(Refer to section 13.5.)
Always connect a protection coordination cable (MR-J3CDL05M) and a
termination connector (MR-J3-TM). When they are not connected properly,
the servo-on may not be turned ON.
For the control power supplies of the converter unit and the drive unit, always
turn ON or OFF at the same time.
(a) 200V class (MR-J3-DU30KB MR-J3-DU37KB)
Converter unit
Drive unit
Dynamic
brake
(Option)
TE2-2
L
TE2-1
L
NFB
MC
L
L
L1
Servo motor
M
3-phase
200 to 230VAC
50/60Hz
CN40
L2
CN40A
MR-J3CDL05M
cable
Termination
connector
MR-J3-TM
(Option)
L3
U
V
CN40B U
L11
L21
V
W
W
Encoder cable
NFB
(Note 4)
MC1
CNP1 CN1
CN2
DICOM
1
2
1
5
6
2
7
9
Encoder
24VDC
BU
BV
BW
DOCOM
MC2
(Note 5)
Power
supply
Power factor improving
DC reactor (Option)
DICOM
Cooling fan
(Note 2)
ALM
RA2
P1
EM1
OHS2
24VDC
power supply
OHS1
P2
(Note 3)
Servo
motor
thermal
relay
DOCOM
C
RA3
CN3
10
P
C
P
C
P
C
DICOM
G3
G4
G3
G4
G3
G4
Regenerative
option(Note 1)
Regenerative
option(Note 1)
Regenerative
option(Note 1)
15 ALM
RA1
24VDC
Cooling fan
Cooling fan
Cooling fan
DICOM
5
R
S
R
S
R
S
DOCOM
3
20 EM1
Plate SD
L11
L21
(Note 3)
(Note 3) Operation
-ready
Drive
unit
RA1 RA2 RA3 RA4
Motor
Forced stop
EM1 OFF
thermal relay
ON
MC
SK
Controller
forced stop
Converter
unit
MC
Note 1. For the MR-RB137. For the MR-RB137, three units are used as one set (permissible wattage: 3900W).
2. When using the Power factor improving DC reactor, disconnect the short bar across P1-P2.
3. Make up a sequence that turns off the drive unit forced stop (EM1) and the converter unit forced stop (EM1) at the same time.
4. Attach connector for magnetic contactor control (CNP1) on the converter unit. Unattached state may cause an electric shock.
5. For specifications of cooling fan power supply, refer to section 13.3.8.
13 - 29
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(b) 400V class (MR-J3-DU30KB4 to MR-J3-DU55KB4)
NFB
(Note 6)
Power
supply
Converter unit
Drive unit
TE2-2
L
TE2-1
L
L
L
Dynamic
brake
(Option)
CN40
CN40A
NFB
MR-J3CDL05M
cable
Termination
connector
MR-J3-TM
(Option)
MC
L1
L2
L3
CN40B
3-phase
380 to 480VAC
50/60Hz
Servo motor
M
U
V
CN1
1
L11
U
V
DICOM
L21
24VDC
W
DOCOM
5
6
2
7
9
W
(Note 5)
MC1
CNP1
1
DICOM
CN2
BU
BV
BW
MC2
2
ALM
RA2
Encoder
Power factor improving
DC reactor (Option)
EM1
Encoder cable
(Note 3)
Cooling fan
DOCOM
P1
(Note 2)
P2
C
OHS1
OHS2
Servo motor
thermal relay
24VDC
power supply
RA3
P
C
P
C
P
C
CN3
10
G3
Regenerative
option(Note 1)
G4
G3
Regenerative
option(Note 1)
G4
G3
Regenerative
option(Note 1)
G4
DICOM
Cooling fan
R400 S400
Cooling fan
R400 S400
Cooling fan
R400 S400
15 ALM
RA1
24VDC
DICOM
5
DOCOM
3
L11
20 EM1
Plate SD
L21
(Note 3)
(Note 4)
Drive
unit
Motor
Operation
-ready
Stepdown
(Note 3)
Forced stop
transformer
thermal relay
ON
EM1 OFF
RA1 RA2 RA3 RA4
MC
SK
Controller
forced stop
Converter
unit
MC
Note 1. For the MR-RB138-4. For the MR-RB138-4, three units are used as one set (permissible wattage: 3900W).
2. When using the Power factor improving DC reactor, disconnect the short bar across P1-P2.
3. Make up a sequence that turns off the drive unit forced stop (EM1) and the converter unit forced stop (EM1) at the same time.
4. Stepdown transformer is required for coil voltage of magnetic contactor more than 200V class.
5. Attach connector for magnetic contactor wiring on the converter unit. Unattached state may cause an electric shock.
6. For specifications of cooling fan power supply, refer to section 13.3.8.
13 - 30
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.3.3 Terminal
Refer to section 13.7 for the terminal block arrangement and signal layout.
(1) Converter unit
Connection target
(Application)
(Note)
Description
Abbreviation
Terminal block
MR-J3-CR55K
MR-J3-CR55K4
Connect 3-phase 200 to
230VAC, 50/60Hz to L1, L2, L3.
Connect 1-phase 200 to
230VAC, 50/60Hz.
Connect 3-phase 380 to
480VAC, 50/60Hz to L1, L2, L3.
Connect 1-phase 380 to
480VAC, 50/60Hz.
Main circuit power supply
Control circuit power supply
L1 L2 L3
L11 L21
P1 P2
TE1-1
TE3
Power factor improving
DC reactor
When using the power factor improving DC reactor, connect it after
removing the connection plate across P1-P2.
TE1-2
TE1-2
Regenerative brake
P2
C
Connect to the P2 and C terminals of the regenerative option.
Connect to the L , L terminals of the drive unit.
Use the connection bar, which is supplied with the drive unit, to
connect.
DC link
L
L
TE2-2
Connect this terminal to the protective earth (PE) terminals of the
servo motor and control box for grounding.
Grounding
PE
Note. The permissible tension applied to any of the terminal blocks TE1-1, TE1-2, TE2-2 is 350[N].
(2) Drive unit
Description
Connection target
(Application)
(Note)
Abbreviation
MR-J3-DU30KB
MR-J3-DU37KB
MR-J3-DU30KB4 to
MR-J3-DU55KB4
Terminal block
Connect 1-phase 200 to
230VAC, 50/60Hz.
Connect 1-phase 380 to
480VAC, 50/60Hz.
Control circuit power supply
L11 L21
TE3
Connect to the L and L terminals of the converter unit.
Use the connection bar, which is supplied with the drive unit, to
connect.
L
L
power supply input
L
L
TE2-1
Servo motor power
Grounding
U
V
W
TE1A
PE
Connect to the servo motor power terminals (U, V, W).
Connect this terminal to the protective earth (PE) terminals of the
servo motor and control box for grounding.
Note. The permissible tension applied to any of the terminal blocks TE1, TE2-1 is 350[N].
13 - 31
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.3.4 How to use the connection bars
Make sure to use the supplied connection conductors and connect the L and L of the drive unit to those of
the converter unit as shown below. Never use connection conductors other than the ones supplied with the
drive unit. Both units are shown without the front covers.
Converter unit
Drive unit
Connection
conductors
L
L
L
L
13 - 32
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.3.5 Connectors and signal arrangements
POINT
The pin configurations of the connectors are as viewed from the cable
connector wiring section.
(1) Converter unit
CN1 (Digital I/O connector)
CN6 Leave this open.
Model: 17JE-23090-02 (D8A) K11-CG (D-sub 9 pin or
equivalent)
CN40 Connect to CN40A of the
(DDK)
CNP1 CN1
drive unit.
CHARGE
CN3 Leave this open.
5
9
DOCOM
DOCOM
4
3
8
WNG
7
EM1
2
6
ALM
DICOM
1
DICOM
CNP1 (Magnetic contactor wiring connector)
Model: GFKC 2.5/2-STF-7.62
(Phoenix Contact)
1
MC1
2
MC2
13 - 33
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(2) Drive unit
The drive unit front view shown is that of the MR-J3-DU30KB4, MR-J3-DU37KB4 or less. Refer to section
13.7 Outline Drawings for the appearances and connector layouts of the MR-J3-DU30KB, MR-J3-DU37KB,
MR-J3-DU45KB4, MR-J3-DU55KB4.
CN5 (USB connector)
Refer to section 11.8.
CN3 (I/O signal connector)
Refer to section 3.4.
Connector for the front axis of
CN1A SSCNET cable.
Connector for the rear axis of
CN1B SSCNET cable.
CN2 (Encoder connector)
Refer to section 3.4.
The frames of the CN2 and CN3 connectors are
connected to the PE (earth) terminal in the amplifier.
13 - 34
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.3.6 Converter unit signal (device) explanations
POINT
Explanations on the drive unit signals are the same as those for servo
amplifiers with 22kW or less. Refer to section 3.5.
(1) Signals
For the I/O interfaces (symbols in I/O column in the table), refer to (b) of this section.
I/O
Signal name
Pin code Pin No.
Function/Application
division
Digital I/F power
supply input
DICOM
CN1-1 Used to input 24VDC (24VDC 10% 150mA) for I/O interface. The power supply
CN1-6 capacity changes depending on the number of I/O interface points to be used.
For the source interface, connect
of 24VDC external power supply.
Forced stop
EM1
CN1-7 Turn EM1 off to bring the motor to a forced stop state, in which the magnetic
connector is turned off and the servo-off signal is output to the drive unit.
Turn EM1 on in the forced stop state to reset that state.
DI
Trouble
ALM
CN1-2 ALM turns off when power is switched off or the protective circuit is activated.
Without alarm occurring, ALM turns on within about 1.5s after power-on.
CN1-8 When warning has occurred, WNG turns on.
DO
DO
Warning
WNG
Digital I/F common DOCOM
CN1-5 Common terminal for the ALM and WNG output signals of the converter unit.
CN1-9 Separated from LG.
Pins are connected internally. For the source interface, connect
external power supply.
of 24VDC
Magnetic contactor
drive output
MC1
CNP1-1 Connect to the operation coil of the magnetic contactor. Always supplies the
control circuit power since it is conducted with L11 in the converter unit.
Magnetic contactor wiring
connector on the converter unit.
WARNING
Connected state may cause an
electric shock.
MC2
CNP1-2 Connect to the operation coil of the magnetic contactor. When the converter unit
(Note) receives a start command from the drive unit, it is conducted with L21 inside, the
control circuit power is supplied, and then the magnetic contactor is turned ON.
Change parameter No.PA02 setting to “
0” when controlling without
magnetic contactor control connector (CNP1). (Refer to section 13.3.1.)
13 - 35
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(2) I/O interfaces
(a) Digital input interface (DI)
Give a signal with a relay or open collector transistor. Refer to section 3.7.3 for the source input.
Converter unit
For transistor
EM1 5.6k
Approx. 5mA
Switch
TR
DICOM
VCES 1.0V
ICEO 100
24VDC 10
150mA
A
(b) Digital output interface (DO)
A lamp, relay or photocoupler can be driven. Install a diode for an inductive load, or install an inrush
current suppressing resistor for a lamp load. (Permissible current: 40mA or less, inrush current: 100mA
or less) A maximum of 2.6V voltage drop occurs in the servo amplifier.
Refer to section 3.7.3 for the source output.
If polarity of diode is
reversed, converter
unit will fail.
Converter unit
ALM,
etc.
Load
DOCOM
(Note) 24VDC 10
150mA
Note. If the voltage drop (maximum of 2.6V) interferes with the relay operation, apply high
voltage (up to 26.4V) from external source.
13 - 36
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.3.7 Timing chart
(1) Power circuit timing chart
Power-on procedure
(a) Always wire the power supply as shown in above section 13.3.2 using the magnetic contactor with the
main circuit power supply (3-phase: L , L , L ). Configure up an external sequence to switch off the
1
2
3
magnetic contactor as soon as an alarm occurs.
(b) Switch on the control circuit power supply L , L simultaneously with the main circuit power supply or
11 21
before switching on the main circuit power supply. If the main circuit power supply is not on, the display
shows the corresponding warning. However, by switching on the main circuit power supply, the warning
disappears and the drive unit will operate properly.
1) When control function of magnetic contactor is enabled and the status remains at ready on
The main circuit power is not shut off with servo off.
Coasting
Servo motor speed
0r/min
ON
Drive unit control
power supply
OFF
ON
Converter unit control
power supply
OFF
ON
Main circuit
power supply
OFF
(Note 5)
Tb
(3s)
ON
Electromagnetic
brake operation
delay time
Base circuit
OFF
(Note 1) ON
Electromagnetic
brake interlock (MBR)
OFF
(95ms)
ON
Servo on command
(from controller)
OFF
(Note 3)
Position command
(Note 4)
0r/min
Release delay
time and external
relay (Note 2)
Release
Activate
Electromagnetic
brake
Release delay time and external relay (Note 2)
Note 1. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated
2. Electromagnetic brake is released after delaying for the release time of electromagnetic brake and operation time of
external circuit relay. For the release delay time of electromagnetic brake, refer to the Servo Motor Instruction Manual
(Vol.2).
3. Make the controller execute the position command after the electromagnetic brake is released.
4. In position control mode
5. “Tb” refers to a delay time when the electromagnetic brake interlock (MBR) is turned off until when the base circuit is shut
off at servo-off. Set Tb using parameter No.PC02.
13 - 37
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
2) When control function of magnetic contactor is enabled and the status returns to ready off
The magnetic contactor of the converter unit is turned off with servo off, and the main circuit magnetic
contactor is shut off.
Coasting
Servo motor speed
0r/min
ON
Drive unit control
power supply
OFF
ON
Converter unit control
power supply
OFF
ON
Main circuit
power supply
OFF
(3s)
ON
Electromagnetic
brake operation
delay time
Base circuit
OFF
(Note 1) ON
Electromagnetic
brake interlock (MBR)
OFF
(3s)
ON
Servo on command
(from controller)
OFF
(Note 3)
Position command
(Note 4)
0r/min
Release delay
time and external
relay (Note 2)
Release
Activate
Electromagnetic
brake
Release delay time and external relay (Note 2)
Note 1. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated
2. Electromagnetic brake is released after delaying for the release time of electromagnetic brake and operation time of
external circuit relay. For the release delay time of electromagnetic brake, refer to the Servo Motor Instruction Manual
(Vol.2).
3. Make the controller execute the position command after the electromagnetic brake is released.
4. In position control mode
13 - 38
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
3) When controlling magnetic contactor by external sequence
When an alarm occurs, turn OFF the magnetic contactor by the external sequence and shut off the
main circuit power supply.
Coasting
Servo motor speed
0r/min
ON
Drive unit control
power supply
OFF
ON
Converter unit control
power supply
OFF
ON
Main circuit
power supply
OFF
(Note 5, 6)
Tb
(3s)
ON
Electromagnetic
brake operation
delay time
Base circuit
OFF
(Note 1) ON
Electromagnetic
brake interlock (MBR)
OFF
(95ms)
ON
Servo on command
(from controller)
OFF
(Note 3)
Position command
(Note 4)
0r/min
Release delay
time and external
relay (Note 2)
Release
Activate
Electromagnetic
brake
Release delay time and external relay (Note 2)
Note 1. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated
2. Electromagnetic brake is released after delaying for the release time of electromagnetic brake and operation time of
external circuit relay. For the release delay time of electromagnetic brake, refer to the Servo Motor Instruction Manual
(Vol.2).
3. Make the controller execute the position command after the electromagnetic brake is released.
4. In position control mode
5. “Tb” refers to a delay time when the electromagnetic brake interlock (MBR) is turned off until when the base circuit is shut
off at servo-off. Set Tb using parameter No.PC02.
6. When turning OFF servo amplifiers, the base circuit remains ready on state. When the status is ready off, the base circuit
and the servo-on command turns OFF at the same time. (Tb=0)
13 - 39
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(2) Alarm occurrence timing chart
When an alarm has occurred, remove its cause, make sure that the operation
signal is not being input, ensure safety, and reset the alarm before restarting
operation.
CAUTION
As soon as an alarm occurs, make the Servo off status and interrupt the main
circuit power.
(a) When control function of magnetic contactor is enabled
1) Converter unit
When an alarm occurs in the converter unit, the magnetic contactor is turned off and the main circuit
magnetic contactor is shut off. The drive unit in operation stops. To deactivate the alarm, turn the
control circuit power off, then on or request the operation from the driver unit. However, the alarm
cannot be deactivated unless its cause is removed.
b)
ON
Converter unit control
power supply
OFF
ON
Main circuit
power supply
OFF
a)
d)
c)
OFF
ON
OFF
ON
OFF
Converter unit alarm
Alarm occurrence
Alarm occurrence
ON
Drive unit control
power supply
OFF
ON
Base circuit
OFF
(3s)
(3s)
ON
Servo-on command
(from controller)
OFF
OFF
ON
OFF
Drive unit alarm
1.5s
ON
Reset command
(from controller)
OFF
50ms or more
a) in Figure
Even if an alarm occurs in the converter when the drive unit is at servo off, the
drive unit does not detect the alarm.
b) c) in Figure To deactivate the alarm of the converter unit, turn the power of the converter unit
off, and then on (b)) or make the drive unit servo on (c)). (Refer to section 13.6.1.)
d) in Figure
If an alarm occurs in the converter when the drive unit is at servo on, the alarm
also occurs in the drive unit and the drive unit becomes servo off.
13 - 40
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
2) Drive unit
When an alarm occurs on the drive unit, the base circuit is shut off and the servo motor coasts. When
using a dynamic brake (option), the dynamic brake is activated to stop the servo motor. To deactivate
the alarm, power the control circuit off, then on, turn the reset (RES) on or CPU reset command.
However, the alarm cannot be deactivated unless its cause is removed.
ON
Converter unit control
power supply
OFF
a)
a)
ON
Main circuit
power supply
OFF
OFF
Converter unit alarm
ON
Drive unit control
power supply
OFF
ON
Base circuit
OFF
(3s)
(3s)
ON
Servo-on command
(from controller)
OFF
OFF
ON
OFF
Drive unit alarm
1.5s
Alarm occurrence
ON
Reset command
(from controller)
OFF
50ms or more
a) in Figure
After completing to start the drive unit, the main circuit power is supplied while the
drive unit and the converter unit have no alarms.
13 - 41
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(b) When controlling magnetic contactor by external sequence
1) Converter unit
When an alarm occurs on the converter unit, the servo-on turns OFF; however, the main circuit power
supply is not shut off. Therefore, shut off the main circuit power supply by the external sequence.
After cancelling the alarm on the converter unit (when an alarm is also occurring on the drive unit
after cancelling the alarm on the drive unit as well), turning ON the reset command enables to
operate again.
b)
ON
Converter unit control
power supply
OFF
e)
ON
Main circuit
power supply
OFF
a)
d)
c)
OFF
ON
OFF
ON
OFF
Converter unit alarm
Alarm occurrence
Alarm occurrence
ON
Drive unit control
power supply
OFF
ON
Base circuit
OFF
(3s)
(3s)
ON
Servo-on command
(from controller)
OFF
OFF
ON
OFF
Drive unit alarm
1.5s
ON
Reset command
(from controller)
OFF
50ms or more
a) in Figure
Even if an alarm occurs in the converter when the drive unit is at servo off, the
drive unit does not detect the alarm.
b) c) in Figure To deactivate the alarm of the converter unit, turn the power of the converter unit
off, and then on (b)) or make the drive unit servo on (c)). (Refer to section 13.6.1.)
d) in Figure
e) in Figure
If an alarm occurs in the converter unit when the drive unit is at servo on, the
alarm also occurs in the drive unit and the drive unit becomes servo off.
Shut off the main circuit power supply by the external sequence as soon as an
alarm occurs.
13 - 42
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
2) Drive unit
When an alarm occurs in the drive unit, the drive unit turns into the servo off but the main circuit
power supply is not shut off. Therefore, shut off the main circuit power supply using the external
sequence. Operation can be resumed by turning the reset (RES) ON after the alarm is deactivated in
the drive unit.
ON
Converter unit control
power supply
OFF
a)
b)
ON
Main circuit
power supply
OFF
OFF
Converter unit alarm
ON
Drive unit control
power supply
OFF
ON
Base circuit
OFF
(3s)
(3s)
ON
Servo-on command
(from controller)
OFF
OFF
ON
OFF
Drive unit alarm
1.5s
Alarm occurrence
ON
Reset command
(from controller)
OFF
50ms or more
a) in Figure
b) in Figure
When an alarm occurs on the drive unit, shut off the main circuit power supply by
the external sequence.
Turn ON the main circuit power supply while an alarm of the drive unit is
cancelled.
13 - 43
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(3) Forced stop (EM1) ON/OFF timing chart
(a) When control function of magnetic controller is enabled
1) Converter unit
When the forced stop (EM1) is made valid in the converter unit, the magnetic contactor is turned off
and the main circuit power supply is shut off. The drive unit in operation stops, and Main circuit off
warning (E9) appears. When the forced stop (EM1) is deactivated in the converter unit, the magnetic
contactor is turned on, the main circuit power is supplied, and then the drive unit automatically
resumes the operation.
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake release
Servo motor speed
Base circuit
Electromagnetic brake
(3s)
(10ms)
ON
OFF
Electromagnetic brake
operation delay time
(3s)
(3s)
(Note)
ON
Electromagnetic brake
interlock (MBR)
OFF
ON
Converter main circuit
off warning
OFF
ON
Main circuit
power supply
OFF
Invalid (ON)
Valid (OFF)
Forced stop (EM1)
Note. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated
13 - 44
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
2) When CNP1 is invalid
When the forced stop (EM1) is input in the converter unit, the drive unit in operation stops and Main
circuit off warning (E9) appears. When the forced stop (EM1) is deactivated in the converter unit, the
drive unit automatically resumes the operation.
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake release
Servo motor speed
Base circuit
Electromagnetic brake
(3s)
(10ms)
ON
OFF
Electromagnetic brake
operation delay time
(3s)
(3s)
(Note) ON
OFF
Electromagnetic brake
interlock (MBR)
ON
Converter main circuit
off warning
OFF
ON
Main circuit
power supply
OFF
Invalid (ON)
Valid (OFF)
Forced stop (EM1)
Note. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated
13 - 45
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(b) Forced stop in the drive unit
When the forced stop (EM1) is made valid in the drive unit, the drive unit in operation stops, Main circuit
off warning (E9) appears, and then the drive unit is forcedly stopped. Configure to activate the forced
stop (EM1) of the drive unit as the forced stop (EM1) of the converter unit is activated, and to activate
the forced stop (EM1) of the converter unit as the forced stop (EM1) of the drive unit is activated. Shut
off the power supply by the external sequence as soon as the forced stop (EM1) is activated.
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake release
(3s)
Servo motor speed
Base circuit
Electromagnetic brake
(10ms)
ON
OFF
Electromagnetic brake
operation delay time
(3s)
(Note) ON
OFF
Electromagnetic brake
interlock (MBR)
Forced stop command
(from controller) or
forced stop (EM1)
Invalid (ON)
Valid (OFF)
ON
Main circuit
power supply
OFF
Note. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated
13 - 46
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.3.8 Servo motor side details
Encoder connector signal arrangement
Terminal box
Encoder connector
CM10-R10P
CM10-R10P
Terminal
No.
Signal
7
6
5
4
10
9
3
2
1
1
2
MR
MRR
8
3
4
BAT
LG
5
6
7
8
P5
9
10
SHD
HA-LP30K1
HA-LP37K1
HA-LP30K1M
HA-LP37K1M
HA-LP30K2
HA-LP37K2
HA-LP45K1M4
HA-LP50K1M4
HA-LP45K24
HA-LP55K24
HA-LP25K14
HA-LP30K14
HA-LP37K14
HA-LP37K1M4
HA-LP30K1M4 HA-LP30K24
HA-LP37K24
Motor power
supply terminal
block screw size
Earth screw size
M8
M6
M10
M6
Motor power supply
Terminal block signal arrangement
BU BV BW OHS1OHS2
terminal block
Encoder connector
CM10-R10P
(U V W) M8 screw
U
V
W
U
W
V
Thermal sensor
terminal block
(OHS1 OHS2)
M4 screw
Cooling fan
terminal block
(BU BV BW)
M4 screw
Earth terminal M6 screw
13 - 47
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
Signal name
Abbreviation
Description
Connect to the motor power terminals (U, V, W) of the drive unit. During power-on, do not
open or close the motor power line.
Servo motor
power supply
U
V
W
Otherwise, a malfunction or faulty may occur.
Supply power which satisfies the following specifications.
Power
consumption
[W]
Rated
current
[A]
Voltage
division
Voltage/
Servo motor
frequency
HA-LP30K1M, 30K2,
37K2
200V 3-phase 200 to 230VAC
class 50Hz/60Hz
65(50Hz)
85(60Hz)
120(50Hz)
175(60Hz)
65(50Hz)
85(60Hz)
110(50Hz)
150(60Hz)
0.20(50Hz)
0.22(60Hz)
0.65(50Hz)
0.80(60Hz)
0.12(50Hz)
0.14(60Hz)
0.20(50Hz)
0.22(60Hz)
HA-LP30K1, 37K1,
37K1M
Cooling fan
BU BV BW
HA-LP30K1M4,
30K24, 37K24
HA-LP30K14, 37K14,
37K1M4, 45K1M4,
50K1M4, 45K24,
55K24
400V 3-phase 380 to 460VAC
class 50Hz
3-phase 380 to 480VAC
60Hz
OHS1-OHS2 are opened when heat is generated to an abnormal temperature.
Motor thermal relay OHS1 OHS2 Maximum rating: 125V AC/DC, 3A or 250V AC/DC, 2A
Minimum rating: 6V AC/DC, 0.15A
Earth terminal
For grounding, connect to the earth of the control box via the earth terminal of the drive unit.
13 - 48
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.4 Display section and operation section of the converter unit
13.4.1 Display flowchart
Use the display (3-dight, 7-segment LED) on the front panel of the converter unit for status display, parameter
setting, etc. Set the parameters before operation, diagnose an alarm, confirm external sequences, and/or
confirm the operation status.
Press the MODE, UP or DOWN button once to move the next screen.
Button
MODE
Status display
Diagnosis
Alarm
Basic parameters
(Note)
Status
External I/O
signal display
Current alarm
Parameter
No.PA01
(Note)
Bus voltage
[V]
Output signal
forced output
First alarm in
past
Parameter
No.PA02
Effective load
ratio [%]
Software version
low
DOWN
UP
Peak load ratio
[%]
Software version
high
(Note)
(Note)
Regenerative load
ratio [%]
Sixth alarm in
past
Parameter
No.PA18
Parameter error
No.
Parameter
No.PA19
Note. When parameter is selected, parameter group and parameter No. are displayed
alternately. Refer to section 13.4.5 for details.
13 - 49
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.4.2 Status display mode
The servo status during operation is shown on the 3-digit, 7-segment LED display. Press the "UP" or "DOWN"
button to change display data as desired.
When the required data is selected, the corresponding symbol is displayed. Press the "SET" button to display
that data.
The converter unit display section can show four items of data such as the effective load factor.
(1) Display examples
The following table shows the display examples.
Item
Status
Display
Ready off
Status
Ready on
Bus voltage
300[V]
67[%]
95[%]
90[%]
Effective load ratio
Peak load ratio
Regenerative load ratio
(2) Status display list
The following table lists the converter unit statuses that may be displayed.
Indication
range
Status display
Ready
Symbol
Unit
Description
The ready off is displayed during initialization or alarm occurrence, in the
forced stop status, or when the bus voltage is not established.
The ready on is displayed when the servo was switched on after completion
of initialization and the servo amplifier is ready to operate.
The converter unit voltage is displayed.
roF
off
Status
Ready
on
ron
Bus voltage
d
J
V
0 to 999
Continuous effective load torque is displayed. (Note)
The effective value in the past 15 seconds is displayed relative to the rated
current of 100%.
Effective load
ratio
%
0 to 300
The peak output is displayed. (Note)
Peak load ratio
b
L
%
%
The peak value in the past 15 seconds is displayed relative to the rated
torque of 100%.
0 to 400
0 to 300
Regenerative
load ratio
The percentage of regenerative power to the permissible regenerative value
is displayed.
Note. Output = converter unit bus voltage
output current
13 - 50
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.4.3 Diagnostic mode
(1) Diagnostic list
Name
Display
Unit
Not ready.
Initializing.
An alarm occurred.
External forced stop status.
Sequence
Bus voltage is not established.
Ready
Indicates that the servo was switched on after completion of
initialization and the drive unit is ready to operate.
Indicates the ON/OFF status of external I/O signal.
Lit
: ON
External I/O signal display
Extinguished: OFF
For details, refer to (2) of this section.
Allows external I/O signal to be switched on/off forcibly. For
details, refer to (3) of this section.
Output signal forced output
Software version low
Indicates the version of the software.
Software version high
Indicates the system number of the software.
(2) External I/O signal display
The ON/OFF states of the digital I/O signals connected to the converter unit can be confirmed.
(a) Operation
Call the display screen shown after power-on. Using the "MODE" button, show the diagnostic screen.
Press MODE once.
External I/O signal display screen
13 - 51
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(b) Display definition
The 7-segment LED segments and CN1 connector pins correspond as shown below.
CN1-7: Forced stop (EM1)
Input signals
Output signals
CN1-8:
CN-2:
Warning (WNG) Trouble (ALM)
Lit: ON
Extinguished: OFF
The LED segment corresponding to the pin is lit to indicate ON, and is extinguished to indicate OFF.
(3) Output signal forced output
You can force the output signal to be switched on/off, independently of the converter status.
This function is used for wiring check of output signal.
When turning CN1-8 on and off
Press MODE once.
External I/O signal display screen
Press UP once.
Press SET for more than 2 seconds.
The signal under the lit LED is switched on/off.
Indicates ON/OFF of the trouble (ALM) signal. (Lit: ON, extinguished: OFF)
CN1-8 CN1-2
Press MODE once.
The lit LED moves to the upper LED of CN1-8.
Press UP once.
CN1-8 switches on. (WNG-DOCOM are connected.)
CN1-8
Press DOWN once.
CN1-8 switches off.
Press SET for more than 2 seconds.
Call the display screen shown after power-on.
13 - 52
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.4.4 Alarm mode
The current alarm, parameter error and point table error are displayed.
The lower 2 digits on the display indicate the alarm number that has occurred or the parameter number in error.
Display example are shown below.
Name
Display
Description
Indicates on occurrence of an alarm.
Current alarm
Indicates that overvoltage (A.33) occurred.
Flickers at alarm occurrence.
Indicates that the last alarm is overload (A.50).
Indicates that the second alarm in the past is overvoltage
(A.33).
Indicates that the third alarm in the past is undervoltage (A.10).
Alarm history
Indicates that the fourth alarm in the past is undervoltage
(A.10).
Indicates that the fifth alarm in the past is undervoltage (A.10).
Indicates that the sixth alarm in the past is overload (A.50).
Indicates no occurrence of parameter error (A.37).
Parameter error No.
Displayed
alternately
Indicates that the data of parameter No.PA01 is faulty.
13 - 53
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
Functions at occurrence of an alarm
(1) Any mode screen displays the current alarm.
(2) The other screen is visible during occurrence of an alarm. At this time, the decimal point in the third digit
flickers.
(3) To clear any alarm, switch power off, then on or press the "SET" button on the current alarm screen. Note
that this should be done after removing the case of the alarm.
13.4.5 Parameter mode
POINT
The display section of the converter unit has three digits. When a parameter
No. is displayed, parameter group and parameter No. are displayed
alternately.
When, for example, "PA01" is displayed,
alternately.
and
are displayed
The following example gives the operation procedure after power-on for use of the regenerative options (MR-
RB137).
Press MODE three time
Displayed
The parameter number is displayed.
alternately
For parameter No.PA01, “PA” and “01” are displayed alternately.
Press UP or DOWN to change the number.
Press MODE twice
The set value of the specified parameter number flickers.
In this case, the lower three digits “0000” of the set value “0000” are
displayed.
(Note)
Press MODE once
During flickering, the set value can be change.
Use UP or DOWN .
(
2: MR-RB137 (3 pcs.) are used.)
Press SET to enter.
Note. If the "MODE" button is pressed when the lower three digits of the four digits "0000" are displayed, the fourth digit "0000" is
displayed as
. However, do not change the setting of the fourth digit. Press the "MODE" button again to reset the display
.
to the lower three digits
To shift to the next parameter, press the "UP"/"DOWN" button.
When changing the parameter No.PA01 setting, change its set value, then switch power off once and switch it
on again to make the new value valid.
13 - 54
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.5. Parameters for converter unit
Never adjust or change the parameter values extremely as it will make operation
CAUTION
instable.
POINT
Refer to chapter 5 for parameters for drive unit.
Parameter whose symbol is preceded by * is made valid with the following
conditions.
* : Set the parameter value, switch power off once after setting, and then
switch it on again, or perform the controller reset.
Never change parameters for manufacturer setting.
13.5.1 Parameter list
No. Symbol
Name
Initial value
0000h
0001h
0001h
0
Unit
PA01 *REG Regenerative option
PA02 *MCC Magnetic contactor drive output selection
PA03
PA04
PA05
PA06
PA07
For manufacturer setting
100
0
100
PA08 *DMD Status display selection
PA09 *BPS Alarm history clear
0000h
0000h
0
PA10
PA11
PA12
PA13
PA14
PA15
PA16
PA17
PA18
PA19
For manufacturer setting
0000h
0002h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
*DIF
Input filter setting
For manufacturer setting
13 - 55
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.5.2 List of details
Initial
value
Setting
range
No. Symbol
Name and function
Unit
PA01 *REG Regenerative option
0000h
Refer to
Name
Used to select the regenerative option.
and
0 0
function
column.
Select the regenerative option.
00: No used
01: MR-RB139
02: MR-RB137(3 pcs.)
11: MR-RB136-4
Only for MR-J3-CR55K
Only for MR-J3-CR55K4
12: MR-RB138-4(3 pcs.)
"01" and "02" are the set values for the MR-J3-CR55K only, and "11"
and "12" are those for the MR-J3-CR55K4 only.
Wrong setting will result in parameter alarm (A.37).
PA02 *MCC Magnetic contactor drive output selection
Used to select the output of the magnetic contactor drive power supply.
0001h
Refer to
Name
and
0 0 0
function
column.
Used to select the output of the magnetic contactor drive power
supply.
0: No used
1: Used
PA03
PA04
PA05
PA06
PA07
For manufacturer setting
0001h
0
Do not change this value by any means.
100
0
100
0000h
PA08 *DMD Status display selection
Used to select the status display shown at power-on.
Refer to
Name
and
0 0 0
function
column.
Status display of converter unit display section at power-on.
0: Status
1: Bus voltage
2: Effective load ratio
3: Peak load ratio
4: Regenerative load ratio
PA09 *BPS Alarm history clear
0000h
Refer to
Name
Used to clear the alarm history.
and
0 0 0
function
column.
Alarm history clear
0: Invalid
1: Valid
When alarm history clear is made valid, the alarm history is cleared
at next power-on.
After the alarm history is cleared, the setting is automatically made
invalid (reset to 0).
PA10
PA11
For manufacturer setting
0
Do not change this value by any means.
0000h
13 - 56
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
Initial
value
Setting
range
No. Symbol
Name and function
Unit
PA12 *DIF Input filter setting
Select the input filter.
0002h
Refer to
Name
and
0 0 0
function
column.
Input signal filter
If external input signal causes chattering due to noise, etc., input
filter is used to suppress it.
0: None
1: 1.777[ms]
2: 3.555[ms]
3: 5.333[ms]
PA13
PA14
PA15
PA16
PA17
PA18
PA19
For manufacturer setting
Do not change this value by any means.
0000h
0000h
0000h
0000h
0000h
0000h
0000h
13.6 Troubleshooting
13.6.1 Converter unit
(1) Alarms and warning list
When a fault occurs during operation, the corresponding alarm or warning is displayed. If any alarm or
warning has occurred, refer to (2) or (3) of this section and take the appropriate action.
Switch power off, then on to deactivate the alarm. The alarms marked " " in the alarm deactivation column
of the table can be deactivated by pressing the "RES" key of the converter unit side parameter unit or
switching on the reset signal (RES).
Alarm deactivation
Display
A.91
Name
Overheat warning
Display
Name
Power
Error
reset
OFF ON
Excessive regenerative load
warning
A.E0
A.10 Undervoltage
A.12 Memory error1 (RAM)
A.15 Memory error2 (EEP-ROM)
A.17 Board error
A.E1 Over load warning
A.E6 Converter forced stop warning
Cooling fan speed reduction
A.E8
A.19 Memory error3 (Flash-ROM)
A.30 Regenerative error
A.33 Over voltage
warning
(Note)
(Note)
A.37 Parameter error
A.38 MC drive circuit error
A.39 Open phase
Inrush current suppressor circuit
A.3A
error
A.45 Main circuit device overheat
A.47 Cooling fan error
A.50 Over load 1
(Note)
(Note)
(Note)
(Note)
(Note)
(Note)
A.51 Over load 2
888
Watchdog
Note. Deactivate the alarm about 30 minutes of cooling time after removing the cause of occurrence.
13 - 57
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(2) Remedies for alarms
When any alarm has occurred, eliminate its cause, ensure safety, then reset the
CAUTION
alarm, and restart operation. Otherwise, injury may occur.
POINT
When any of the following alarms has occurred, always remove its cause and
allow about 30 minutes for cooling before resuming operation. If operation is
resumed by switching control circuit power off, then on to reset the alarm, the
converter unit and regenerative option may become faulty.
Regenerative error (A.30)
Over load 1 (A.50)
Over load 2 (A.51)
Main circuit device overheat (A.45)
The alarm can be deactivated by switching the power off, then on or by the
error reset command from the host controller. Refer to (1) in this section for
details.
When an alarm occurs, the trouble (ALM) signal switches off and the display section shows the alarm number.
Remove the cause of the alarm in accordance with this section.
Display
Name
Definition
Cause
Action
A.10 Undervoltage
Power supply voltage
dropped.
1. Instantaneous control power failure
occurred for more than 60ms.
2. Shortage of power supply capacity
caused the power supply voltage to
drop at start, etc.
Review the power supply.
3. Failure of the part in the converter
Change the Converter unit.
unit.
Checking method
Alarm (A.10) occurs if power is
switched on after connectors
disconnected.
A.12 Memory error 1 RAM memory fault
(RAM)
Failure of the part in the converter unit. Change the converter unit.
Checking method
Alarm (A.12) occurs if power is
switched on after connectors
disconnected.
A.15 Memory error 2 EEP-ROM fault
(EEP-ROM)
1. Failure of the part in the converter
Change the converter unit.
unit.
Checking method
Alarm (A.15) occurs if power is
switched on after connectors
disconnected.
2. The number of write times to EEP-
ROM exceeded 100,000.
A.17 Board error
CPU/parts fault
Failure of the part in the converter unit. Change the converter unit.
Checking method
A.19 Memory error 3 ROM memory fault
(Flash-ROM)
Alarm (A.17/A.19) occurs if power is
switched on after connectors
disconnected.
13 - 58
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
Display
Name
Definition
Cause
Action
A.30 Regenerative
error
Permissible regenerative
power of regenerative
option is exceeded.
1. Wrong setting of parameter No.PA01 Set correctly.
2. Regenerative option is not
connected.
Connect correctly.
3. High-duty operation or continuous
regenerative operation caused the
permissible regenerative power of
the regenerative option to be
exceeded.
1. Reduce the frequency of
positioning.
2. Use the regenerative option of
larger capacity.
3. Reduce the load.
Checking method
Call the status display and check the
regenerative load ratio.
4. Power supply voltage is abnormal.
MR-J3-CR55K: 260VAC or more
MR-J3-CR55K4: 520VAC or more
5. Regenerative option faulty.
Review power supply
Change converter unit or
regenerative option.
6. Ground fault occurred in servo motor Correct the wiring.
power (U, V, W).
Regenerative transistor fault 7. Regenerative transistor faulty.
Checking method
Change the converter unit.
1) The regenerative option has
overheated abnormally.
2)
The alarm occurs even after
removal of the built-in
regenerative resistor or
regenerative option.
A.33 Over voltage
Converter bus voltage
exceeded to following
voltage.
1. Regenerative option is not used.
2. Though the regenerative option is
used, the parameter No.PA01 setting
Use the regenerative option.
Set correctly.
MR-J3-CR55K: 400VDC
MR-J3-CR55K4: 800VDC
is "
00 (not used)".
3. Lead of regenerative option is open
or disconnected.
1. Change lead.
2. Connect correctly.
4. Regenerative transistor faulty.
5. Wire breakage of regenerative
option.
Change the converter unit.
Change the regenerative option.
6. Capacity of regenerative option is
insufficient.
Add regenerative option or
increase capacity.
7. Power supply voltage high.
Review the power supply.
8. Ground fault occurred in servo motor Correct the wiring.
power (U, V, W).
A.37 Parameter
error
Parameter setting is wrong. 1. Converter unit fault caused the
parameter setting to be rewritten.
2. Regenerative option not used with
converter unit was selected in
Change the converter unit.
Set parameter No.PA01 correctly.
parameter No.PA02.
3. The number of write times to
EEP-ROM exceeded 100,000 due to
parameter write, etc.
Change the converter unit.
13 - 59
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
Display
Name
Definition
Cause
Action
Review the wiring.
A.38 MC drive circuit Magnetic contactor drive
1. Wrong connection of the magnetic
contactor.
error
circuit error
(When the magnetic
contactor is turned on: the
main circuit power supply is
not turned on within two
seconds after the servo-on
of the drive unit.
2. Parameters specifying whether to
use/not use the magnetic contactor
do not match the configuration.
3. Magnetic contactor failed.
4. Magnetic contactor drive circuit
Set parameter No.PA02 correctly.
Change the magnetic contactor.
Change the converter unit.
faulty.
When the magnetic
contactor is opened: the
main circuit power supply is
turned on although the
magnetic contactor is
opened.)
Checking method
Check the output of magnetic
contactor control connector (CNP1) .
Power supply voltage is applied to
this connector. Take care to avoid an
electric shock at connecting.
5. Mismatch of an external sequence.
Review the power-on sequence.
(Refer to section 3.3.2.)
A.39 Open phase
Power supply error
1. Any of L1, L2 and L3 is disconnected. Review the wiring.
Or, open.
2. Failure of the part in the converter
Change the converter unit.
unit.
A.3A Inrush current
suppressor
Inrush current suppressor
circuit error
1. Power-on/off was repeated with high Review operation pattern.
frequency.
circuit error
2. Inrush current suppressor resistance Change the converter unit.
overheated.
3. Inrush current suppressor circuit
faulty.
A.45 Main circuit
device
Main circuit device
overheat.
1. The power supply was turned on and Review operation pattern.
off continuously by overloaded
status.
overheat
2. Ambient temperature of converter
unit is over 55
Review environment so that
ambient temperature is 0 to 55
Change the converter unit.
Change the cooling fan of the
converter unit.
.
.
3. Converter unit faulty.
1. Cooling fan life expiration. (Refer to
section 2.6.)
A.47 Cooling fan
alarm
The cooling fan of the
converter unit stopped, or its
speed decreased to or
below the alarm level.
2. Foreign matter caught in the cooling Remove the foreign matter.
fan stopped rotation.
3. The power supply of the cooling fan
failed.
Change the converter unit.
A.50 Overload 1
A.51 Overload 2
Load exceeded overload
protection characteristic of
converter unit.
Converter unit is used in excess of its
continuous output current.
1. Reduce load.
2. Review operation pattern.
Load exceeded overload
protection characteristic of
converter unit.
Converter unit is used in excess of its
output current for a short time.
Review operation pattern of a
drive unit.
(Note) Watchdog
888
CPU/parts fault
Failure of the part in the converter unit. Change the converter unit.
Checking method
Alarm (888) occurs if power is
switched on after connectors
disconnected.
Note. At power-on, "888" appears instantaneously, but it is not an error.
13 - 60
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(3) Remedies for warnings
Continuing operation in an alarm occurrence status may result in an alarm or disable proper operation.
Eliminate the cause of the warning according to this section. The warning displayed will disappear when the
cause of its occurrence is resolved.
Display
Name
Definition
Cause
Action
A.91 Overheat
warning
The temperature of the fin
exceeded the warning level.
1. Operated in the overloaded status.
2. Ambient temperature of converter
Review operation pattern.
Review environment so that
ambient temperature is 0 to 55
Use within the range of
specifications.
unit is over 55
.
.
3. Used beyond the specifications of
close mounting.
4. Converter unit faulty.
Change the converter unit.
A.E0 Excessive
regenerative
There is a possibility that
regenerative power may
exceed permissible
Regenerative power increased to 85% 1. Reduce frequency of
or more of permissible regenerative
power of regenerative option.
Checking method
positioning.
load warning
2. Change regenerative option for
the one with larger capacity.
3. Reduce load.
regenerative power of
regenerative option.
Call the status display and check the
regenerative load ratio.
A.E1 Overload
warning
There is a possibility that
overload alarm 1 or 2 may
occur.
Load increased to 85% or more of
Refer to A.50, A.51.
overload alarm 1 or 2 occurrence level.
Cause, checking method
Refer to A.50, 51.
A.E6 Converter
forced stop
warning
EM1 is off.
External forced stop was made valid.
(EM1 was turned off.)
Ensure safety and deactivate
forced stop.
A.E8 Cooling fan
speed
The speed of the converter
unit cooling fan decreased
to or below the warning
level.
1. Cooling fan life expiration. (Refer to
section 2.6.)
Change the cooling fan of the
converter unit.
reduction
2. The power supply of the cooling fan
failed.
Change the converter unit.
warning
(4) Clearing the alarm history
You can clear the alarm numbers stored in the alarm history of the alarm mode. To ensure that you can
control the alarms that will occur after regular operation, make this setting before starting regular operation
to clear the alarm history.
After setting "0001" in parameter No.PA09, switch power off once. Switching it on again clears the alarm
history. At this time, the parameter No.PA09 setting returns to "0000".
13 - 61
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.6.2 Drive unit
POINT
Explanation made in this section is exclusively for the driver unit.
Other troubleshooting is the same as that for servo amplifiers with 22kW or
less. Refer to chapter 8.
As soon as an alarm occurs, make the Servo off status and interrupt the main
circuit power.
(1) Alarms and warning list
When a fault occurs during operation, the corresponding alarm or warning is displayed. If any alarm or
warning has occurred, refer to (2) or (3) of this section and take the appropriate action. When an alarm
occurs, the ALM turns OFF.
After its cause has been removed, the alarm can be deactivated in any of the methods marked in the alarm
deactivation column. The alarm is automatically canceled after removing the cause of occurrence.
Alarm deactivation
Error reset
Display
9C
Name
Display
1B
Name
Power
OFF ON
Converter
warning
CPU reset
Alarms
Converter
alarm
Main circuit off
warning
Alarms
E9
(2) Remedies for alarms
When any alarm has occurred, eliminate its cause, ensure safety, then reset the
alarm, and restart operation. Otherwise, injury may occur.
CAUTION
As soon as an alarm occurs, mark servo-off and power off the main circuit and
control circuit.
POINT
The alarm can be deactivated by switching power off, then on or by the error
reset command CPU reset from the servo system controller. For details, refer
to (1) of this section.
When an alarm occurs, the trouble (ALM) switches off and the dynamic brake is operated to stop the servo
motor. At this time, the display indicates the alarm No.
The servo motor comes to a stop. Remove the cause of the alarm in accordance with this section. MR
Configurator may be used to refer to the cause.
Display
1B
Name
Definition
Cause
Action
Converter
alarm
An alarm occurred in the
converter unit during servo
on.
1. An alarm occurred in the converter
unit during servo on.
Check the alarm of the converter
unit, and take the action following
the remedies for alarms of the
converter unit. (Refer to section
13.6.1 (2).)
2. The protection coordination cable or Connect correctly.
terminal connector is not correctly
connected.
13 - 62
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(3) Remedies for warnings
Continuing operation in an alarm occurrence status may result in an alarm or disable proper operation.
Eliminate the cause of the warning according to this section. The warning displayed will disappear when the
cause of its occurrence is resolved.
Indication
9C
Name
Definition
Cause
Action
Converter
warning
A warning occurred in the
converter unit during the
servo-on command.
Check the warning of the
converter unit, and take the action
following the remedies for
warnings of the converter unit.
(Refer to section 13.6.1 (3).)
E9
Main circuit
off warning
The forced stop of the
converter unit is made valid
during the servo-on
command.
1. The forced stop of the converter unit Deactivate the forced stop of the
is made valid. converter unit.
2. The protection coordination cable or Connect correctly.
terminal connector is not correctly
connected.
13 - 63
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.7 Outline drawings
POINT
Refer to section 13.2.1 for outline dimension drawing.
13.7.1 Converter unit (MR-J3-CR55K(4))
[Unit: mm]
Cooling fan
wind direction
2- 7 Installation hole
328
Approx. 20
300
260
128
Approx. 200
180
Terminal block layout
(Terminal cover removed)
Approx. 80
20
CHARGE
TE2-2
TE2-2
TE3
TE3
PE
TE1-1
TE1-2
TE1-1
TE1-2
7
277
Mass: 25[kg] (55.2[lb])
Terminal block signal layout
TE2-2
L
Terminal block screw: M6
Tightening torque: 3.0 [N m]
Mounting screw
Screw size: M6
Tightening torque: 5.4 [N m]
(47.8 [lb in])
L
(26.6 [lb in])
TE3
Terminal block screw: M4
Tightening torque: 1.2 [N m]
L11
L21
(10.6 [lb in])
TE1-1
L1
Terminal block screw: M10
Tightening torque: 10.0 [N m]
(88.5 [lb in])
L2
L3
TE1-2
C
Terminal block screw: M10
Tightening torque: 10.0 [N m]
(88.5 [lb in])
P2 P1
PE
Terminal block screw: M10
Tightening torque: 10.0 [N m]
(88.5 [lb in])
13 - 64
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.7.2 Drive unit
(1) MR-J3-DU30KB MR-J3-DU37KB
MR-J3-DU45KB4 MR-J3-DU55KB4
[Unit: mm]
2- 7 Installation hole
Approx. 20
300
260
Approx. 200
180
Cooling fan
wind direction
Approx. 80
20
Terminal block layout
(Terminal cover removed)
For mounting
MR-J3BAT
TE2-1
TE2-1
TE3
TE1
TE3
TE1
PE
Approx. 200
128
7
328
277
Mass: 26[kg] (57.3[lb])
Terminal block signal layout
TE2-1
L
Terminal block screw: M6
Tightening torque: 3.0 [N m]
(26.6 [lb in])
Mounting screw
Screw size: M6
Tightening torque: 5.4 [N m]
(47.8 [lb in])
L
TE3
Terminal block screw: M4
Tightening torque: 1.2 [N m]
L11
L21
(10.6 [lb in])
TE1
U
Terminal block screw: M10
Tightening torque: 10.0 [N m]
(88.5 [lb in])
V
W
PE
Terminal block screw: M10
Tightening torque: 10.0 [N m]
(88.5 [lb in])
13 - 65
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(2) MR-J3-DU30KB4 MR-J3-DU37KB4
[Unit: mm]
2- 6 Installation hole
Approx. 60
240
120
Approx. 200
180
Cooling fan
wind direction
Approx. 80
Terminal block layout
(Terminal cover removed)
60
For mounting
MR-J3BAT
TE2
TE3
TE1
Approx. 200
128
6
328
219.2
Mass: 18[kg] (39.7[lb])
Terminal block signal layout
TE2
Terminal block screw: M6
Tightening torque: 3.0 [N m]
Mounting screw
Screw size: M5
Tightening torque: 3.2 [N m]
(28.3 [lb in])
L
L
(26.6 [lb in])
TE3
Terminal block screw: M4
Tightening torque: 1.2 [N m]
L11
L21
(10.6 [lb in])
TE1
U
Terminal block screw: M8
Tightening torque: 6.0 [N m]
V
W
(53.1 [lb in])
PE
Terminal block screw: M8
Tightening torque: 6.0 [N m]
(53.1 [lb in])
13 - 66
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.8 Characteristics
13.8.1 Overload protection characteristics
An electronic thermal relay is built in the converter unit and drive unit to protect the servo motor, converter unit
and drive unit from overloads.
Overload 1 alarm (50) occurs if overload operation performed is above the electronic thermal relay protection
curve shown below. Overload 2 alarm (51) occurs if the maximum current flew continuously for several
seconds due to machine collision, etc. Use the equipment on the left-hand side area of the continuous or
broken line in the graph.
It is recommended to use the machine which generates unbalanced torque, e.g. a vertical lift application, so
that the unbalanced torque is not more than 70% of the rated torque.
10000
1000
100
10000
1000
100
During rotation
During rotation
During servo lock
10
1
10
1
(Note 2)
(Note 2)
0
100
200
250
0
100
200
250
Load ratio [%]
Converter unit
(Note 1) Load ratio [%]
Drive unit
Note 1. If operation that generates torque more than 100% of the rating is performed with an abnormally high frequency in a servo motor
stop status (servo lock status) or in a 30r/min or less low-speed operation status, the drive unit may fail even when the electronic
thermal relay protection is not activated.
2. Load ratio 100% indicates the rated output of each converter unit and drive unit. Refer to section 13.1.4 for rated output.
Fig. 13.1 Overload protection characteristics
13 - 67
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.8.2 Power supply equipment capacity and generated loss
POINT
The calculation method of heat dissipation area for enclosed control panel is
the same as that for servo amplifiers with 22kW or less. Refer to section 10.2
(2).
Table 13.1 indicates the generated loss and power supply capacity under rated load per combination of the
converter unit and drive unit. When the servo motors is run at less than the maximum speed, the power supply
equipment capacity is lower than the value in the table but the heat generated does not change.
Since the servo motor requires 2 to 2.5 times greater instantaneous power for acceleration, use the power
supply which ensures that the voltage lies within the permissible voltage fluctuation at the main circuit power
supply terminals (L1, L2, L3) of the converter unit. The power supply equipment capacity changes with the power
supply impedance.
The actually generated heat falls within the ranges at rated torque and at zero torque according to the
frequencies of use during operation. When designing an enclosed control box, use the values in the table,
considering the worst operating conditions. The generated heat in Table 13.1 does not include heat produced
during regeneration.
Table 13.1 Power supply capacity and generated heat per servo amplifier at rated output
Power supply
capacity [kVA]
(Note)
Area required
for heat
Drive unit-generated heart[W]
Power factor
Converter unit
MR-J3-CR55K
Drive unit
Servo motor
Power factor
dissipation
[m2]
improving DC
reactor is not
used
improving DC At rated torque At zero torque
reactor is used
HA-LP30K1
MR-J3-DU30KB HA-LP30K1M
HA-LP30K2
48
40
1550(1100+450)
31.0
HA-LP37K1
MR-J3-DU37KB HA-LP37K1M
HA-LP37K2
59
40
48
49
35
40
1830(1280+550)
1080(850+230)
1290(1010+280)
36.6
21.6
25.8
HA-LP25K14
MR-J3-
HA-LP30K14
HA-LP30K1M4
HA-LP30K24
HA-LP37K14
HA-LP37K1M4
HA-LP37K24
HA-LP45K1M4
HA-LP45K24
HA-LP50K1M4
HA-LP55K24
DU30KB4
60(30+30)
MR-J3-
MR-J3-CR55K4
59
71
49
59
1542(1200+342)
1810(1370+440)
30.8
36.2
DU37KB4
MR-J3-
DU45KB4
MR-J3-
80
87
67
72
2120(1650+470)
2150(1650+500)
42.4
43.0
DU55KB4
Note. The heat generated by the drive unit is indicated in the left term within the parentheses, and the heat generated by the converter
unit in the right term.
13 - 68
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.8.3 Dynamic brake characteristics
(1) Dynamic brake operation
(a) Calculation of coasting distance
Fig. 13.2 shows the pattern in which the servo motor comes to a stop when the dynamic brake is
operated. Use Equation 13.1 to calculate an approximate coasting distance to a stop. The dynamic
brake time constant varies with the servo motor and machine operation speeds. (Refer to (b). Please
contact us for the servo motor not indicated.)
ON
Forced stop (EM1)
OFF
Time constant
V0
Machine speed
Time
te
Fig 13.2 Dynamic Brake Operation Diagram
Vo
60
JL
JM
te
1
Lmax
·················································································································· (13.1)
Lmax
V0
JM
JL
: Maximum coasting distance ·········································································································· [mm]
: Machine rapid feed rate ······························································································ [mm/min][in/min]
: Servo motor inertial moment ······················································································ [kg cm2][oz in2]
: Load inertia moment converted into equivalent value on servo motor shaft ·············· [kg cm2][oz in2]
: Brake time constant ·························································································································· [s]
: Delay time of control section ············································································································ [s]
For 7kW or less servo, there is internal relay delay time of about 30ms. For 11k to 22kW servo, there
is delay time of about 100ms caused by a delay of the external relay and a delay of the magnetic
contactor built in the external dynamic brake.
te
13 - 69
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(b) Dynamic brake time constant
The following shows necessary dynamic brake time constant
for the equations (13.1).
40
40
HA-LP25K14
HA-LP30K14
35
30
35
HA-LP30K1
HA-LP37K1
30
HA-LP37K14
25
20
15
10
5
25
20
15
10
5
0
0
0
200 400 600 800 1000 1200
Speed [r/min]
0
200 400 600 800 1000 1200
Speed [r/min]
HA-LP1000r/min series
60
50
40
30
20
10
0
60
HA-LP37K1M
HA-LP37K1M4
HA-LP45K1M4
HA-LP50K1M4
50
HA-LP30K1M
40
HA-LP30K1M4
30
20
10
0
0
0
500
1000
1500
2000
500
1000
1500
2000
Speed [r/min]
Speed [r/min]
HA-LP1500r/min series
13 - 70
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
45
40
35
30
25
20
15
10
5
45
40
35
30
25
20
15
10
5
HA-LP45K24
HA-LP30K2
HA-LP37K2
HA-LP55K24
HA-LP37K24
HA-LP30K24
0
0
0
500
1000
1500
0
500
1000
1500
2000
2000
Speed [r/min]
Speed [r/min]
HA-LP2000r/min series
(2) The dynamic brake at the load inertia moment
Use the dynamic brake under the load inertia moment ratio indicated in the following table. If the load inertia
moment is higher than this value, the external dynamic brake may burn. If there is a possibility that the load
inertia moment may exceed the value, contact Mitsubishi.
The values of the load inertia moment ratio in the table are the values at the maximum rotation speed of the
servo motor.
Load inertia moment ratio
Drive unit
[Multiplier ( 1)]
MR-J3-DU30KB(4)
MR-J3-DU37KB(4)
10
MR-J3-DU45KB4
MR-J3-DU55KB4
13 - 71
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.8.4 Inrush currents at power-on of main circuit and control circuit
The following table indicates the inrush currents (reference data) that will flow when the maximum permissible
voltage (200V class: 253VAC, 400V class: 528VAC) is applied at the power supply capacity of 2500kVA and
the wiring length of 1m.
Inrush currents (A0-p)
Converter unit
MR-J3-CR55K
Drive unit
Main circuit power supply (L1, L2, L3)
163A
Control circuit power supply (L11, L21)
18A
MR-J3-DU30KB
MR-J3-DU37KB
MR-J3-DU30KB4
MR-J3-DU37KB4
MR-J3-DU45KB4
MR-J3-DU55KB4
(Attenuated to approx. 20A in 180ms) (Attenuated to approx. 0A in 100ms)
339A
19A
MR-J3-CR55K4
(Attenuated to approx. 20A in 70ms)
(Attenuated to approx. 0A in 60ms)
Since large inrush currents flow in the power supplies, always use no-fuse breakers and magnetic contactors.
(Refer to section 13.9.5.)
When circuit protectors are used, it is recommended to use the inertia delay type that will not be tripped by an
inrush current.
13.9 Options
Before connecting any option or peripheral equipment, turn off the power and wait
for 20 minutes or more until the charge lamp turns off. Then, confirm that the
voltage between L and L is safe with a voltage tester and others. Otherwise,
WARNING
an electric shock may occur. In addition, always confirm from the front of the
converter unit whether the charge lamp is off or not.
Use the specified auxiliary equipment and options. Unspecified ones may lead to a
CAUTION
fault or fire.
POINT
Explanations on the following item are the same as those for servo amplifiers
with 22kW or less. Refer to the section below for details.
Cable/connector sets Refer to section 11.1.
Junction terminal block Refer to section 11.7.
MR Configurator Refer to section 11.8.
Battery Refer to section 11.9.
Relays Refer to section 11.15.
Surge absorbers Refer to section 11.16.
Radio noise filter (FR-BIF(-H)) Refer to section 11.17 (2) (e).
13.9.1 Cables and connectors
POINT
Other connectors are the same as those for servo amplifiers with 22kW or
less. Refer to section 11.1.
13 - 72
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(1) Makeup of cables and like
The following shows the cable makeup for connection with the servo motor and other model.
Converter unit
Drive unit
7)
8)
CNP1
CN40
CN1
CN40A
1)
CN2
CN40B
2)
6)
3)
4) 5)
Servo motor
HA-LP
Terminal
box
No.
Product
Protection
Model
Description
Application
1)
MR-J3CDL M
Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
Connector: PCR-S20FS+
Case: PCR-LS20LA1
coordination
cable
Refer to (2) of this
section.
(Honda Tsushin Kogyo)
2)
Connector set
MR-J2CN1-A
Refer to (2) of this
section.
Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
Connector: PCR-S20FS+
Shell kit: PCR-LS20LA1
(Honda Tsushin Kogyo)
3)
4)
Termination
connector
MR-J3-TM
Encoder cable MR-J3ENSCBL M-L
Cable length:
IP67
Standard
life
2
5
10 20 30m
Encoder cable MR-J3ENSCBL M-H For HA-LP series
Cable length: Refer to section 11.1.2 (4) for details.
10 20 30
5)
IP67
Long flex
life
2
5
40 50m
6)
7)
Encoder
MR-J3SCNS
IP67
connector set
For HA-LP series
Refer to section 11.1.2 (4) for details.
Converter unit side connector
(Phoenix Contact)
Magnetic
contactor
wiring
Supplied
with
Socket: GFKC 2.5/2-STF-7.62
converter
unit
connector
Digital
8)
Converter unit side connector
(DDK)
I/O connector
Connector: 17JE23090-02(D8A)K11-CG
13 - 73
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(2) MR-J3CDL05M(0.5m) Protection coordination cable
Connect protection coordination cables correctly if they are fabricated.
CAUTION
Otherwise, the system may perform unexpected operation.
When fabricating a protection coordination cable, use the recommended wires given in section 13.9.4, and
fabricate a protection coordination cable as shown in the wiring diagram in this section.
MR-J3CDL05M
10120-3000PE (Connector)
10320-52F0-008 (Shell kit)
PCR-S20FS (Connector)
PCR-LS20LA1 (Case)
9
1
ACD2
11 ACD2*
ACD3
12 ACD3*
PAL
13 PAL*
ACD1
14 ACD1*
LG
15 LG
19
10
20
7
2
3
17
8
4
18
5
5
15
6
16
3
6
GOF
Converter unit side
Drive unit side
16 GOF*
7
PMC
17 PMC*
PSD
18 PSD*
LG
13
4
8
14
1
9
11
2
19 LG
10 PRD
20 PRD*
12
SD
Plate
Plate
Table 13.2 Recommended wire
Characteristics of one core
(Note 2)
Length
[m(ft)]
Core size Number
Finishing
OD
[mm]
Conductor Insulation coating
Model
Wire model
Structure
[Wires/mm]
[mm2]
of cores
resistance
[ /mm]
OD d[mm]
(Note 1)
0.5 to 5
(1.64 to 16.4)
20
(10 pairs)
UL20276 AWG#28
10pair (CREAM)
MR-J3CDL05M
0.08
7/0.127
222
0.38
6.1
Note 1. d is as shown below.
d
Conductor Insulation sheath
2. Standard OD. Max. OD is about 10% greater.
13 - 74
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.9.2 Regenerative option
The specified combinations of regenerative options, converter unit and drive unit
CAUTION
may only be used. Otherwise, a fire may occur.
POINT
The calculation method of regenerative energy is the same as that for servo
amplifiers with 22kW or less. Refer to section 11.2 (2).
(1) Combination and regenerative power
The regenerative power values in the table are the regenerative power of the resistor and are not the rated
power.
Regenerative Power [W]
(Note 1) Three
MR-RB137
(Note 2) Three
MR-RB138-4
(5 ) in parallel
Converter unit
MR-J3-CR55K
MR-J3-CR55K4
Drive unit
MR-RB139
MR-RB136-4
(5 )
(1.3
)
(1.3 ) in parallel
MR-J3-DU30KB
MR-J3-DU37KB
MR-J3-DU30KB4
MR-J3-DU37KB4
MR-J3-DU45KB4
MR-J3-DU55KB4
1300
3900
1300
3900
Note. 1. The composite resistor value of three options is 1.3 . The resistor value of one option is 4 .
2. The composite resistor value of three options is 5 . The resistor value of one option is 15 .
(2) Parameter setting
POINT
Always set parameter No.PA02 of the drive unit to “
00”(Not used) since
the regenerative option cannot be connected to the drive unit.
When using the regenerative option, set the parameter of the converter unit. Match parameter No.PA01 to
the regenerative option used.
Parameter No.PA01
0 0
Regenerative option selection
00: Not used
01: MR-RB139
02: MR-RB137 (3 pcs.)
11: MR-RB136-4
12: MR-RB138-4 (3 pcs.)
(3) Regenerative loss of drive unit and servo motor
Drive unit
Inverse efficiency [%]
C charge [J]
450
MR-J3-DU30KB
MR-J3-DU37KB
MR-J3-DU30KB4
MR-J3-DU37KB4
MR-J3-DU45KB4
MR-J3-DU55KB4
90
13 - 75
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(4) Connection of the regenerative option
Always supply 1-phase 200V and 400V respectively to the cooling fan. The cooling fan specifications are as
follows.
Table 13.3 Cooling fan
Item
200V class
400V class
Model
MR-RB137 MR-RB139
MR-RB136-4 MR-RB138-4
Voltage Frequency
Power consumption [W]
1-phase 198 to 242VAC, 50/60Hz 1-phase 380 to 480VAC, 50/60Hz
20 (50Hz)/18 (60Hz) 20 (50Hz)/18 (60Hz)
The regenerative option generates heat of 100 higher than the ambient temperature. Fully consider heat
dissipation, installation position, used wires, etc. to place the option. For wiring, use flame-resistant wires or
make the wires flame-resistant and keep them away from the regenerative option. The G3 and G4 terminals act
as a thermal sensor. G3-G4 are opened when the regenerative option overheats abnormally.
Always twist the wires for connection with the converter unit and connect the wires within the overall distance of
5m.
(a) MR-RB139 MR-RB136-4
Converter unit
Power factor improving
DC reactor (Option)
P1
(Note 1)
Servo motor
P2
C
C
5m or less
OHS1
RA
OHS2
Servo motor
thermal relay
24VDC
power supply
P
(Note 2)
G3
G4
Regenerative
option
Cooling fan
(Note 4)
R
S
(Note 3)
Power supply
Note 1. When using the Power factor improving DC reactor, remove the short bar across P1-P2.
2. G3-G4 contact specifications
Maximum voltage: 120V AC/DC
Maximum current: 0.5V/4.8VDC
Maximum capacity: 2.4VA
3. For specifications of cooling fan power supply, refer to Table 13.3.
4. For MR-RB136-4, “R” is “R400” and “S” is “S400”.
13 - 76
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(b) MR-RB137 MR-RB138-4
POINT
Three of MR-RB137 or MR-RB138-4 are required per converter unit. Please
purchase three of MR-RB137 or MR-RB138-4.
Converter unit
Power factor improving
DC reactor (Option)
P1
(Note 1)
Servo motor
P2
C
C
5m or less
OHS1
RA
OHS2
Servo motor
thermal relay
24VDC
power supply
P
C
P
P
C
(Note 2)
G3
G4
G3
G4
G3
G4
Regenerative
Regenerative
Regenerative
option
option
option
Cooling fan
(Note 4)
Cooling fan
(Note 4)
Cooling fan
(Note 4)
R
S
R
S
R
S
(Note 3)
Power supply
Note 1. When using the Power factor improving DC reactor, remove the short bar across P1-P2.
2. G3-G4 contact specifications
Maximum voltage: 120V AC/DC
Maximum current: 0.5V/4.8VDC
Maximum capacity: 2.4VA
3. For specifications of cooling fan power supply, refer to Table 13.3.
4. For MR-RB138-4, “R” is “R400” and “S” is “S400”.
13 - 77
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(5) Outline dimension drawings
[Unit:mm]
2- 10 hole
TE1
10
2.3
230
260
197
215
15
15
15
Mass
[kg(lb)]
Regenerative option
MR-RB139 MR-RB136-4 10(22.05)
MR-RB137 MR-RB138-4 11(24.25)
Cooling fan (Note 1)
Terminal block signal layout
TE1
R
S
G4 G3
C
P
(Note 2) (Note 2)
Terminal screw: M5
Tightening torque: 2.0 [N m] (17.7 [lb in])
Mounting screw
Screw size: M8
Tightening torque: 13.2 [N m] (117 [lb in])
Note 1. One cooling fan for MR-RB136-4, MR-RB138-4.
2. For MR-RB138-4, “R” is “R400” and “S” is “S400”.
13 - 78
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.9.3 External dynamic brake
POINT
Configure up a sequence which switches off the contact of the brake unit after
(or as soon as) it has turned off the servo on (signal) at a power failure or
failure.
For the braking time taken when the dynamic brake is operated, refer to
section 13.8.3.
The brake unit is rated for a short duration. Do not use it for high duty.
The specifications of the input power supply for external dynamic brake are
the same as those of the converter unit control circuit power supply.
Operation timing is the same as that for servo amplifiers with 22kW or less.
Refer to section 11.6.
(1) Selection of dynamic brake
The dynamic brake is designed to bring the servo motor to a sudden stop when a power failure occurs or
the protective circuit is activated. When using the external dynamic brake, assign the dynamic brake
interlock (DB) to any of CN3-9, CN3-13, and CN3-15 pins in parameter No.PD07 to PD09.
Converter unit
MR-J3-CR55K
Drive unit
Dynamic brake
DBU-37K
MR-J3-DU30KB
MR-J3-DU37KB
MR-J3-DU30KB4
MR-J3-DU37KB4
MR-J3-DU45KB4
MR-J3-DU55KB4
MR-J3-CR55K4
DBU-55K-4
(2) Connection example
Use the following wires to connect the dynamic brake.
Dynamic
brake
Wire[mm2] (Note)
a
b
U
V
W
DBU-37K
2
14
DBU-55K-4
Note. Selection condition of wire size is as follows.
Wire type: 600V Polyvinyl chloride insulated wire (IV wire)
Construction condition: One wire is constructed in the air
13 - 79
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
Converter unit
Drive unit
L
L
L
L
Servo motor
M
NFB
MC
(Note 4)
Power
supply
U
V
L1
L2
U
V
CN1
W
L3
W
DICOM
1
L11
DOCOM
DICOM
5
6
2
7
9
CN3
15 ALM
L21
CNP1
1
RA1
RA4
(Note 3)
RA2
MC1
MC2
ALM
DB
DICOM
2
EM1
10
5
(Note 3)
DOCOM
DICOM
DOCOM
3
L11
L21
20 EM1
Plate SD
Forced stop
(Note 5)
(Note 2)
Drive
unit
Controller (Note 5) Operation
forced stop Forced stop -ready
(Note 1)
EM1
OFF/ON
RA1 RA2 RA3
MC
SK
14
13 W
V
U
Converter
unit
a
b
RA4
Dynamic brake
Note 1 Terminals 13, 14 are N/O contact outputs. When the dynamic brake has stuck, terminals 13, 14 are opened. Therefore, configure
up the circuit to prevent servo-on in the external sequence.
2. For converter unit and servo amplifier 400 V class, stepdown transformer is required for coil voltage of magnetic contactor more
than 200 V class.
3. Assign the dynamic brake interlock (DB) in parameter No.PD07 to PD09.
4. Refer to section 13.1.3 for the power supply specifications.
5. Make up a sequence that turns off the drive unit forced stop (EM1) and the converter unit forced stop (EM1) at the same time.
13 - 80
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(3) Outline dimension drawing
[Unit:mm]
2- 10 installation hole
Terminal block
TE1
U
V
W
Terminal screw: M5
Tightening torque: 2.0 [N m] (17.7 [lb in])
TE2
a
b
13 14
Terminal screw: M5
Tightening torque: 0.8 [N m] (7.1 [lb in])
a b1314
U
V
W
Mounting screw
Screw size: M8
TE2
TE1
Tightening torque: 13.2 [N m] (117 [lb in])
2.3
15
10
15
15
15
15
220
235
230
260
230
Mass
Dynamic brake
[kg(lb)]
8(17.64)
11(24.25)
DBU-37K
DBU-55K-4
13 - 81
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.9.4 Selection example of wires
POINT
Wires indicated in this section are separated wires. When using a cable for
power line (U, V, and W) between the servo amplifier and servo motor, use a
600V grade EP rubber insulated chloroprene sheath cab-tire cable (2PNCT).
For selection of cables, refer to appendix 6.
To comply with the UL/C-UL (CSA) Standard, use UL-recognized copper
wires rated at 60 (140 ) or more for wiring. To comply with other
standards, use a wire that is complied with each standard
Selection condition of wire size is as follows.
Construction condition: One wire is constructed in the air
Wire length: 30m or less
The following diagram shows the wires used for wiring. Use the wires given in this paragraph or equivalent.
Converter unit
Drive unit
Servo motor
3) Motor power supply lead
3)
Power factor
improving
DC reactor
U
U
P1
P2
V
V
Motor
1)
W
W
4) Regenerative option lead
Regenerative option
C
Encoder cable
1) Main circuit power
supply lead
Power supply
Encoder
L1
L2
L3
6) Thermal relay
Thermal
relay
OHS1
OHS2
L11
L11
Power supply
5) Cooling fan
lead
Cooling fan
L21
L21
BU
BV
BW
2) Control power supply lead
13 - 82
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(1) When using the 600V Polyvinyl chloride insulated wire (IV wire)
Selection example of wire size when using IV wires is indicated below.
Table 13.4 Wire size selection example 1 (IV wire)
Wires[mm2] (Note 1, 3)
3) U 4)
P1 P2 P2
(Note 2)
Converter unit
MR-J3-CR55K
1)
2)
V
W
5)
6)
Drive unit
L1 L2 L3
L11 L21
C
BU BV BW OHS1 OHS2
MR-J3-DU30KB
MR-J3-DU37KB
50(AWG1/0): d
60(AWG2/0): d
60(AWG2/0): d
(Note 4)
2(AWG14)
MR-J3-DU30KB4 22(AWG4): b
MR-J3-DU37KB4 30(AWG2): c
MR-J3-DU45KB4 38(AWG2): c
MR-J3-DU55KB4 50(AWG1/0): d
30(AWG2): c
38(AWG2): c
50(AWG1/0): d
60(AWG2/0): d
2(AWG14)
5.5(AWG10): a
1.25(AWG16)
1.25(AWG16)
MR-J3-CR55K4
Note 1. Alphabets in the table indicate crimping tools. For crimping terminals and applicable tools, refer to (3) in this section.
2. When connecting to the terminal block, be sure to use the screws which are provided with the terminal block.
3. For the servo motor with a cooling fan.
4. Wires are selected based on the highest rated current among combining servo motors.
(2) When using the 600V Grade heat-resistant polyvinyl chloride insulated wire (HIV wire)
Selection example of wire size when using HIV wires is indicated below.
Table 13.5 Wire size selection example 2 (HIV wire)
Wires[mm2] (Note 1, 3)
3) U 4)
P1 P2 P2
(Note 2)
Converter unit
MR-J3-CR55K
1)
2)
V
W
5)
6)
Drive unit
L1 L2 L3
L11 L21
C
BU BV BW OHS1 OHS2
MR-J3-DU30KB
MR-J3-DU37KB
38(AWG2): c
60(AWG2/0): d
60(AWG2/0): d
22(AWG4): e
22(AWG4): e
38(AWG2): c
38(AWG2): c
2(AWG14)
60(AWG2/0): d
MR-J3-DU30KB4 22(AWG4): b
MR-J3-DU37KB4 22(AWG4): b
MR-J3-DU45KB4 38(AWG2): c
MR-J3-DU55KB4 38(AWG2): c
2(AWG14)
5.5(AWG10): a
1.25(AWG16)
1.25(AWG16)
MR-J3-CR55K4
Note 1. Alphabets in the table indicate crimping tools. For crimping terminals and applicable tools, refer to (3) in this section.
2. When connecting to the terminal block, be sure to use the screws which are provided with the terminal block.
3. For the servo motor with a cooling fan.
(3) Selection example of crimping terminals
The table below shows a selection example of crimping terminals for the servo amplifier terminal block
when using the wires mentioned in (1) and (2) in this section.
Servo amplifier side crimping terminals
Symbol
(Note 2)
Applicable tool
Head
Manufacturer
Crimping terminal
Body
YNT-1210S
YF-1 E-4
YPT-60-21
YF-1 E-4
YPT-60-21
YF-1 E-4
YF-1 E-4
Dice
a
b
FVD5.5-10
FVD22-10
YNE-38
DH-123 DH113
(Note 1) R38-8
TD-124 TD112 Japan Solderless
Terminal
c
R38-10
R60-10
FVD22-8
YET-60-1
(Note 1)
d
TD-125 TD113
YET-60-1
YNE-38
e
DH-123 DH-113
Note 1. Coat the part of crimping with the insulation tube.
2. Make sure to use recommended crimping terminals or equivalent since some crimping terminals
cannot be installed depending on the size.
13 - 83
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.9.5 No-fuse breakers, fuses, magnetic contactors.
Always use one no-fuse breakers and one magnetic contactor with one drive unit.
No-fuse breaker
Fuse
Magnetic
contactor
Power factor
improving DC
Power factor
improving DC
Converter unit
Drive unit
Current
[A]
Voltage
AC [V]
Class
reactor is not used reactor is used
400A frame 250A 225A frame 225A
400A frame 300A 400A frame 300A
225A frame 150A 225A frame 125A
225A frame 175A 225A frame 150A
225A frame 225A 225A frame 175A
400A frame 250A 225A frame 225A
MR-J3-DU30KB
MR-J3-DU37KB
MR-J3-DU30KB4
MR-J3-DU37KB4
MR-J3-DU45KB4
MR-J3-DU55KB4
450
500
225
250
350
400
S-N150
S-N180
S-N95
MR-J3-CR55K
250
600
T
S-N125
S-N150
S-N180
MR-J3-CR55K4
13.9.6 Power factor improving DC reactor
The input power factor is improved to about 95%.
[Unit: mm]
Power factor improving
DC reactor
Terminal
Mass
Converter unit
MR-J3-CR55K
Drive unit
W
D
H
W1
80
X
screw
[kg (lb)]
MR-J3-DU30KB
MR-J3-DU37KB
MR-DCL30K
MR-DCL37K
9.5
255
205
225
240
260
215
232
175
197
212
232
M12
(20.94)
6.5
(14.33)
7
MR-J3-DU30KB4
MR-J3-DU37KB4
MR-J3-DU45KB4
MR-J3-DU55KB4
MR-DCL30K-4
MR-DCL37K-4
MR-DCL45K-4
MR-DCL55K-4
75
135
200
215
(15.43)
7.5
MR-J3-CR55K4
M8
80
(16.54)
9.5
(20.94)
Terminal block (M3.5 screw)
For thermal sensor
Terminal screw
Terminal cover
P1
P2
1.5
Approx. W1
W or less
X
1.5
Mounting hole
for M8
D or less
13 - 84
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.9.7 Line noise filter (FR-BLF)
POINT
This section explains how to use the line noise filter unique to servo amplifiers
with a large capacity. Other noise reduction products are the same as those
for servo amplifiers with 22kW or less. Refer to section 11.17.
This filter is effective in suppressing noises radiated from the power supply side and output side of the
converter unit, drive unit and also in suppressing high-frequency leakage current (zero-phase current)
especially within 0.5MHz to 5MHz band. The filters are used with the converter power supply wires (L1 L2 L3)
and drive unit power wires (U V W).
(1) Usage
Pass the 3-phase wires through four line noise filters. When using the line noise filters with the power wires,
passing the power wires together with the ground wire will reduce the filter effect. Run the ground wire
separately from the power wires.
Use four FR-BLFs.
(2) Outline drawing
[Unit: mm]
7
130
85
160
180
13 - 85
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.9.8 Leakage current breaker
(1) Selection method
High-frequency chopper currents controlled by pulse width modulation flow in the AC servo circuits.
Leakage currents containing harmonic contents are larger than those of the motor which is run with a
commercial power supply.
Select a leakage current breaker according to the following formula, and ground the drive unit, servo motor,
etc. securely.
Make the input and output cables as short as possible, and also make the grounding cable as long as
possible (about 30cm) to minimize leakage currents.
Rated sensitivity current 10 {Ig1 Ign Iga
K
(Ig2 Igm)} [mA] ··········································· (13.2)
K: Constant considering the harmonic contents
Leakage current breaker
Cable
K
Noise filter
NV
Mitsubishi
Type
Cable
Converter
unit
Drive
unit
products
M
NV-SP
Models provided with
harmonic and surge
reduction techniques
NV-SW
NV-CP
NV-CW
NV-HW
BV-C1
NFB
1
3
Ig1 Ign
Ig2
Igm
Iga
General models
NV-L
Ig1: Leakage current on the electric channel from the leakage current breaker to the input terminals of the drive
unit (Found from Fig. 13.3.)
Ig2: Leakage current on the electric channel from the output terminals of the servo amplifier to the servo
motor (Found from Fig. 13.3.)
Ign: Leakage current when a filter is connected to the input side (4.4mA per one FR-BIF or FR-BIF-H)
Iga: Leakage current of the drive unit (Found from Table 13.7.)
Igm: Leakage current of the servo motor (Found from Table 13.6.)
Table 13.6 Servo motor’s leakage current
example (lgm)
Table 13.7 Converter unit
drive unit's leakage
current Example (Iga)
Servo motor power
[kW]
Leakage current
Converter unit
Leakage current
[mA]
[mA]
2.5
Drive unit
All series
30 to 55
5
120
100
80
120
100
80
60
40
20
0
60
40
20
0
2
5.5 14 38100
3.5 8 22 60150
30 80
2
5.5
3.5 8 22 60150
30
14
38
100
80
Cable size [mm2]
Cable size [mm2]
a) 200V class
b) 400V class
Fig.13.3 Leakage current example (lg1, lg2) for CV cable run in metal conduit
13 - 86
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(2) Selection example
Indicated below is an example of selecting a leakage current breaker under the following conditions.
30mm2 5mm
22mm2 5mm
NV
Converter
unit
Drive
unit
M
Servo motor
Ig1
Ig2
Igm
Iga
Use a leakage current breaker designed for suppressing harmonics/surges.
Find the terms of Equation (13.2) from the diagram.
5
1000
Ig1 = 95
= 0.475 [mA]
5
1000
Ig2 = 105
= 0.525 [mA]
Ign = 0(not used)
Iga = 5 [mA]
Igm = 2.5 [mA]
Insert these values in Equation (13.2).
Ig 10 {0.475+0+5+1 (0.525+2.5)}
85 [mA]
According to the result of calculation, use a leakage current breaker having the rated sensitivity current (Ig)
of 85[mA] or more. A leakage current breaker having Ig of 200[mA] is used with the NV-SP/SW/CP/CW/HW
series.
13 - 87
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.9.9 EMC filter (recommended)
For compliance with the EMC directive of the EN Standard, it is recommended to use the following filter. Some
EMC filters are large in leakage current.
(1) Converter unit Drive unit
Recommended filter
(Soshin Electric)
Converter unit
Drive unit
Mass [kg]
Leakage current
[mA]
Model
MR-J3-CR55K
MR-J3-CR55K4
MR-J3-DU30KB MR-J3-DU37KB
MR-J3-DU30KB4 to MR-J3-DU55KB4
HF3200A-UN
TF3150C-TX
9
18
31
5.5
(2) Connection example
EMC filter
NFB
Converter unit
MC
1
2
3
4
5
6
E
L1
L2
L3
(Note)
Power supply
L11
L21
Drive unit
L11
L21
Note. For power supply specifications, refer to section 13.1.3.
13 - 88
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(3) Outline drawing
HF3200A-UN
[Unit: mm]
3- 6.5 Length: 8
3- 6.5 3-M10
480
500
1
5
M8
TF3150C-TX
[Unit: mm]
8-R 4.25 Length: 12
(for M8)
M8
3-M8
3-M8
M4
M4
110
2
2
210
150
1
150
452
500
1
5
3
150
1
M4
(227)
260
3
13 - 89
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.9.10 FR-BU2-(H) Brake Unit
POINT
Use a 200V class brake unit and a resistor unit with a 200V class converter
unit, and a 400V class brake unit and a resistor unit with a 400V class
converter unit. Combination of different voltage class units cannot be used.
Install a brake unit and a resistor unit on a flat surface vertically. When the
unit is installed horizontally or diagonally, the heat dissipation effect
diminishes.
Temperature of the resistor unit case rises to higher than 100 . Keep cables
and flammable materials away from the case.
Ambient temperature condition of the brake unit is between 10 to 50
Note that the condition is different from the ambient temperature condition of
the converter unit (between 0 to 55 ).
.
Configure the circuit to shut down the power-supply with the alarm output of
the brake unit and the resistor unit under abnormal condition.
Use the brake unit with a combination indicated in (1) of this section.
For executing a continuous regenerative operation, use FR-RC-(H) power
regeneration converter or FR-CV-(H) power regeneration common converter.
Connect the brake unit to the bus of the converter unit (L and L of TE2-1) for use. As compared to the MR-
RB regenerative brake option, the brake unit can return larger power. Use the brake unit when the regenerative
brake option cannot provide sufficient regenerative brake capability.
When using the brake unit, set the parameter No.PA02 of the converter unit to “
01”.
When using the brake unit, always refer to the FR-BU2-(H) Brake Unit Instruction Manual.
(1) Selection
Use a combination of converter unit, brake unit and resistor unit listed below.
Number of
connected
units
Permissible
continuous
power [kW]
Total
Applicable converter
unit
Brake unit
Resistor unit
resistance
[
]
200V FR-BU2-55K
class
FR-BR-55K
2 (parallel)
2 (parallel)
2 (parallel)
2 (parallel)
7.82
11.0
7.82
15.0
1
1
4
MR-J3-CR55K
MR-J3-CR55K
MR-J3-CR55K4
MR-J3-CR55K4
MT-BR5-55K
FR-BR-H55K
MT-BR5-H75K
400V FR-BU2-H55K
class
FR-BU2-H75K
3.25
13 - 90
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(2) Brake unit parameter setting
Normally, changing parameters of the FR-BU2-(H) is not necessary. Whether a parameter can be changed
or not is listed below.
Parameter
Name
Change
possible/
impossible
Remarks
No.
0
1
Brake mode switchover
Impossible
Possible
Do not change the parameter.
Refer to FR-BU2-(H) Brake Unit
Instruction Manual.
Monitor display data selection
2
3
Input terminal function selection 1
Input terminal function selection 2
Parameter write selection
Impossible
Do not change the parameter
77
78
Cumulative energization time
carrying-over times
CLr Parameter clear
ECL Alarm history clear
C1
For manufacturer setting
(3) Connection example
POINT
Connecting PR terminal of the brake unit to L terminal of the converter unit
results in a brake unit malfunction. Always connect the PR terminal of the
brake unit to the PR terminal of the resistor unit.
(a) Combination with FR-BR-(H) resistor unit
POINT
To use brake units with a parallel connection, use two sets of FR-BU2-(H)
brake unit. Combination with other brake unit results in alarm occurrence or
malfunction.
Always connect the master and slave terminals (MSG and SD) of the two
brake units.
Do not connect as shown below.
Converter unit
Brake unit
Converter unit
Brake unit
L
L
P/
N/
L
L
P/
N/
Brake unit
Brake unit
P/
N/
P/
N/
Connecting two cables to
P and N terminals
Passing wiring
13 - 91
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
Converter unit
Drive unit
L
L
L
L
NFB
MC
L1
(Note 1)
P1
(Note 3)
L2
Power supply
P2
L3
CN1
DICOM
1
L11
L21
24VDC
DOCOM
DICOM
5
6
2
7
9
CN3
15 ALM
RA1
CNP1
1
DICOM
DICOM
DOCOM
MC1
MC2
ALM
RA2
10
5
24VDC
2
EM1
(Note 2)
DOCOM
3
L
(Note 9)
20 EM1
Plate SD
L
Forced stop
(Note 2)
L11
L21
(Note 5)
(Note 2)
Drive
unit
RA1
Controller
Forced stop
forced stop
EM1
RA3 RA4
RA2
MC
SK
Converter
unit
Operation
ready
OFF/ON
Servo motor
thermal relay
(Note 8)
FR-BR-(H)
(Note 6)
TH1
TH2
P
PR
FR-BU2-(H)
(Note 12)
PR
P/
MSG
(Note 11)
(Note 4)
SD
A
N/
B
C
BUE
(Note 7)
(Note 10)
SD
Terminal
block
FR-BR-(H)
(Note 6)
TH1
TH2
P
PR
FR-BU2-(H)
PR
P/
MSG
(Note 11)
(Note 4)
SD
A
N/
B
C
BUE
SD
(Note 10)
(Note 7)
13 - 92
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
Note 1. For power supply specifications, refer to section 13.1.3.
2. Configure the circuit to turn OFF the forced stop (EM1) of the drive unit and the converter unit at the same time.
3. Always connect P1 and P2 terminals (Factory-wired). When using the power factor improving DC reactor, refer to section 13.9.6.
4. Connect P/ and N/ terminals of the brake unit to a correct destination. Wrong connection results in the converter unit and
brake unit malfunction.
5. For the converter unit and the drive unit of 400V class, a stepdown transformer is required.
6. Contact rating: 1b contact, 110VAC_5A/220VAC_3A
Normal condition: TH1-TH2 is conducting. Abnormal condition: TH1-TH2 is not conducting.
7. Contact rating: 230VAC_0.3A/30VDC_0.3A
Normal condition: B-C is conducting/A-C is not conducting. Abnormal condition: B-C is not conducting/A-C is conducting.
8. Connect the thermal relay censor of the servo motor.
9. Do not connect more than one cable to each L and L terminals of TE2-1 of the converter unit.
10. Always connect BUE and SD terminals (Factory-wired).
11. Connect MSG and SD terminals of the brake unit to a correct destination. Wrong connection results in the converter unit and
brake unit malfunction.
12. For connecting L and L - terminals of TE2-1 of the converter unit to the terminal block, use the cable indicated in (3) (d) of
this section.
13 - 93
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(b) Combination with MT-BR5-(H) resistor unit
1) When connecting a brake unit to a converter unit
Converter unit
Drive unit
L
L
L
L
NFB
MC
L1
(Note 1)
Power supply
P1
(Note 3)
L2
P2
L3
CN1
DICOM
1
L11
L21
24VDC
DOCOM
DICOM
5
6
2
7
9
CN3
15 ALM
RA1
CNP1
1
DICOM
DICOM
DOCOM
MC1
MC2
ALM
RA2
10
5
24VDC
2
EM1
(Note 2)
DOCOM
3
L
(Note 9)
20 EM1
Plate SD
L
Forced stop
(Note 2)
L11
L21
(Note 5)
(Note 2)
Forced stop
EM1
Drive
unit
Controller
forced stop
RA1 RA2 RA3 RA4 RA5
MC
SK
Servo motor
thermal relay
(Note 8)
Operation
ready
OFF/ON
Converter
unit
SK
MT-BR5-(H)
(Note 6)
TH1
TH2
P
RA5
PR
FR-BU2-(H)
PR
P/
MSG
SD
A
(Note 4)
N/
B
C
BUE
SD
(Note 7)
(Note 10)
Note 1. For power supply specifications, refer to section 13.1.3.
2. Configure the circuit to turn OFF the forced stop (EM1) of the drive unit and the converter unit at the same time.
3. Always connect P1 and P2 terminals (Factory-wired). When using the power factor improving DC reactor, refer to section 13.9.6.
4. Connect P/ and N/ terminals of the brake unit to a correct destination. Wrong connection results in the converter unit and
brake unit malfunction.
5. For the converter unit and the drive unit of 400V class, a stepdown transformer is required.
6. Contact rating: 1a contact, 110VAC_5A/220VAC_3A
Normal condition: TH1-TH2 is not conducting. Abnormal condition: TH1-TH2 is conducting.
7. Contact rating: 230VAC_0.3A/30VDC_0.3A
Normal condition: B-C is conducting/A-C is not conducting. Abnormal condition: B-C is not conducting/A-C is conducting.
8. Connect the thermal relay censor of the servo motor.
9. Do not connect more than one cable to each L and L terminals of TE2-1 of the converter unit.
10. Always connect BUE and SD terminals (Factory-wired).
13 - 94
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
2) When connecting two brake units to a converter unit
POINT
To use brake units with a parallel connection, use two sets of FR-BU2-(H)
brake unit. Combination with other brake unit results in alarm occurrence or
malfunction.
Always connect the master and slave terminals (MSG and SD) of the two
brake units.
Do not connect the converter unit and brake units as below. Connect the
cables with a terminal block to distribute as indicated in this section.
Converter unit
Brake unit
Converter unit
Brake unit
L
L
P/
N/
L
L
P/
N/
Brake unit
Brake unit
P/
N/
P/
N/
Connecting two cables to
P and N terminals
Passing wiring
13 - 95
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
Converter unit
Drive unit
L
L
L
L
NFB
MC
(Note 1)
Power
supply
L1
P1
(Note 3)
L2
P2
L3
CN1
DICOM
1
L11
L21
24VDC
DOCOM
DICOM
5
6
2
7
9
CN3
15 ALM
RA1
CNP1
1
DICOM
DICOM
DOCOM
MC1
MC2
ALM
RA2
10
5
24VDC
2
EM1
(Note 2)
DOCOM
3
L
(Note 9)
20 EM1
Plate SD
L
Forced stop
(Note 2)
L11
L21
(Note 5)
(Note 2)
Forced stop
EM1
Controller
forced stop
RA1 RA2 RA3 RA4 RA5 RA6
Drive
unit
MC
SK
Operation
ready
OFF/ON
Converter Servo motor
unit
thermal relay
(Note 8)
SK
MT-BR5-(H)
(Note 6)
TH1
TH2
P
RA3
PR
FR-BU2-(H)
(Note 12)
PR
P/
MSG
(Note 11)
(Note 4)
SD
A
N/
B
C
BUE
(Note 7)
SD(Note 10)
Terminal
block
SK
MT-BR5-(H)
(Note 6)
TH1
TH2
P
RA4
PR
FR-BU2-(H)
MSG
PR
P/
(Note 11)
SD
A
(Note 4)
N/
B
C
BUE
SD
(Note 7)
(Note 10)
13 - 96
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
Note 1. For power supply specifications, refer to section 13.1.3.
2. Configure the circuit to turn OFF the forced stop (EM1) of the drive unit and the converter unit at the same time.
3. Always connect P1 and P2 terminals (Factory-wired). When using the power factor improving DC reactor, refer to section 13.9.6.
4. Connect P/ and N/ terminals of the brake unit to a correct destination. Wrong connection results in the converter unit and
brake unit malfunction.
5. For the converter unit and the drive unit of 400V class, a stepdown transformer is required.
6. Contact rating: 1a contact, 110VAC_5A/220VAC_3A
Normal condition: TH1-TH2 is conducting. Abnormal condition: TH1-TH2 is not conducting.
7. Contact rating: 230VAC_0.3A/30VDC_0.3A
Normal condition: B-C is conducting/A-C is not conducting. Abnormal condition: B-C is not conducting/A-C is conducting.
8. Connect the thermal relay censor of the servo motor.
9. Do not connect more than one cable to each L and L terminals of TE2-1 of the converter unit.
10. Always connect BUE and SD terminals (Factory-wired).
11. Connect MSG and SD terminals of the brake unit to a correct destination. Wrong connection results in the converter unit and
brake unit malfunction.
12. For connecting L and L - terminals of TE2-1 of the converter unit to the terminal block, use the cable indicated in (3) (d) of
this section.
(c) Precautions for wiring
The cables between the converter unit and the brake unit, and between the resistor unit and the brake
unit should be as short as possible. Always twist the cable longer than 5m (twist five times or more per
one meter). Even when the cable is twisted, the cable should be less than 10m. Using cables longer
than 5m without twisting or twisted cables longer than 10m, may result in the brake unit malfunction.
Converter unit
Converter unit
Brake unit
Resistor unit
Brake unit
Resistor unit
Twist
Twist
P
N
P
PR
P
PR
P
N
P
N
P
PR
P
PR
P
N
5m or less
5m or less
10m or less
10m or less
(d) Cables
1) Cables for the brake unit
For the brake unit, HIV cable (600V grade heat-resistant PVC insulated wire) is recommended.
a) Main circuit terminal
Main
circuit
terminal
screw
size
Crimping
terminal
Wire size
Tightening
torque
N/ , P/ , PR,
Brake unit
N/ , P/
PR,
,
HIV wire
[N m]
AWG
[mm2]
N/
P/
PR
200V
class
FR-BU2-55K
M6
14-6
4.4
14
6
Terminal block
400V FR-BU2-H55K
class FR-BU2-H75K
M5
M6
5.5-5
14-6
2.5
4.4
5.5
14
10
6
13 - 97
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
b) Control circuit terminal
POINT
Under tightening can cause a cable disconnection or malfunction. Over
tightening can cause a short circuit or malfunction due to damage to the
screw or the brake unit.
Sheath
RES
MSG MSG
SD
SD SD
Core
BUE
PC
SD
Jumper
A
B
C
6mm
Terminal block
Wire the stripped cable after twisting to prevent the cable
from becoming loose. In addition, do not solder it.
Screw size: M3
Tightening torque: 0.5N m to 0.6N
m
Wire size: 0.3mm2 to 0.75 mm2
Screw driver: Small flat-blade screwdriver
(Tip thickness: 0.4mm/Tip width 2.5mm)
2) Cables for connecting the servo amplifier and a distribution terminal block when connecting two sets
of the brake unit
Wire size
Brake unit
HIV wire
[mm2]
AWG
2
200V
class
FR-BU2-55K
38
400V FR-BU2-H55K
class FR-BU2-H75K
14
38
6
2
13 - 98
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(e) Crimping terminals for L and L terminals of TE2-1 of servo amplifier
1) Recommended crimping terminals
POINT
Always use recommended crimping terminals or equivalent since some
crimping terminals cannot be installed depending on the size.
Number of
(Note 1)
Applicable
tool
Converter unit
Brake unit
connected
units
Crimping terminal (Manufacturer)
200V MR-J3-CR55K
FR-BU2-55K
2
38-S6(Japan Solderless Terminal)
(Note 2)
a
class
R38-6S (NICHIFU) (Note 2)
400V MR-J3-CR55K4
class
FR-BU2-H55K
FR-BU2-H75K
2
2
FVD14-6(Japan Solderless Terminal)
b
a
38-S6(Japan Solderless Terminal)
(Note 2)
R38-6S (NICHIFU) (Note 2)
Note 1. Symbols in the applicable tool field indicate the following applicable tools.
Servo amplifier side crimping terminals
Symbol
Crimping
terminal
Crimping terminal
Head
Manufacturer
Body
Dice
YPT-60-21
Japan Solderless
Terminal
38-S6
TD-124 TD-112
YF-1 E-4
NOP60
YET-60-1
YNE-38
a
b
R38-6S
NICHIFU
NOM60
Japan Solderless
Terminal
FDV14-6
YF-1 E-4
DH-112 DH-122
2. Coat the crimping part with an insulation tube.
13 - 99
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(4) Outline dimension drawings
(a) FR-BU2- (H) brake unit
[Unit: mm]
FR-BU2-55K
FR-BU2-H55K, H75K
2- 5hole
(Screw size: M4)
Rating
plate
5
5
18.5
6
158
170
6
52
72
142.5
(b) FR-BR- (H) resistor unit
[Unit: mm]
2-
C
(Note)
Control circuit
terminal
(Note)
Main circuit
terminal
C
C
Approx. 35
Approx. 35
W1
1
A hanging bolt is placed on two locations
(Indicated below).
Hanging bolt
204
W
5
Note. Ventilation ports are provided on both sides and the top. The bottom is open.
Approximate
mass [kg]
Resistor unit
FR-BR-55K
FR-BR-H55K
W
W1
H
H1
H2
H3
D
D1
C
200V
class
400V
class
480 410 700 620 40 670 450 3.2
480 410 700 620 20 670 450 3.2
12
12
70
70
13 - 100
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(c) MT-BR5- (H) resistor unit
[Unit: mm]
Resistance Approximate
Resistor unit
200V
value
mass [kg]
MT-BR5-55K
2.0
50
NP
class
400V
class
MT-BR5-H75K
6.5
70
M4
M6
193
189
37
60 10 21
480
510
75
300
450
75
4
15 mounting hole
7.5
7.5
13 - 101
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
MEMO
13 - 102
APPENDIX
App. 1 Parameter list
POINT
Parameter whose symbol is preceded by * is made valid with the following
conditions.
* : Set the parameter value, switch power off once after setting, and then
switch it on again, or perform the controller reset.
**: Set the parameter value, switch power off once, and then switch it on
again.
App. 1.1 Servo amplifier (drive unit)
Basic setting parameters (PA
)
Gain/filter parameters (PB
Name
)
No. Symbol
PA01
Name
No. Symbol
PB01 FILT
For manufacturer setting
Adaptive tuning mode (Adaptive filter
)
PA02 **REG Regenerative option
PA03 *ABS Absolute position detection system
PA04 *AOP1 Function selection A-1
Vibration suppression control filter tuning mode
(advanced vibration suppression control)
PB02 VRFT
PB03
For manufacturer setting
PA05
to
For manufacturer setting
PB04 FFC
PB05
Feed forward gain
For manufacturer setting
PA07
For manufacturer setting Ratio of load inertia
moment to servo motor inertia moment
PB06 GD2
PA08
ATU
Auto tuning mode
PA09 RSP
Auto tuning response
In-position range
PB07 PG1
PB08 PG2
PB09 VG2
Model loop gain
PA10
PA11
to
INP
Position loop gain
For manufacturer setting
Speed loop gain
PB10
VIC
Speed integral compensation
Speed differential compensation
For manufacturer setting
Machine resonance suppression filter 1
PA13
PB11 VDC
PB12
PA14 *POL
PA15 *ENR
PA16
Rotation direction selection
Encoder output pulses
PB13 NH1
For manufacturer setting
PB14 NHQ1 Notch form selection 1
to
PB15 NH2
Machine resonance suppression filter 2
PA18
PB16 NHQ2 Notch form selection 2
PA19 *BLK
Parameter write inhibit
PB17
PB18
Automatic setting parameter
LPF
Low-pass filter
Vibration suppression control vibration frequency
setting
PB19 VRF1
PB20 VRF2
Vibration suppression control resonance frequency
setting
PB21
For manufacturer setting
PB22
PB23 VFBF
PB24 *MVS
PB25
Low-pass filter selection
Slight vibration suppression control selection
For manufacturer setting
PB26 *CDP
PB27 CDL
PB28 CDT
Gain changing selection
Gain changing condition
Gain changing time constant
Gain changing ratio of load inertia moment to servo
motor inertia moment
PB29 GD2B
PB30 PG2B Gain changing position loop gain
PB31 VG2B Gain changing speed loop gain
PB32 VICB
Gain changing speed integral compensation
Gain changing vibration suppression control
vibration frequency setting
PB33 VRF1B
Gain changing vibration suppression control
resonance frequency setting
PB34 VRF2B
PB35
to
For manufacturer setting
PB45
App. - 1
APPENDIX
Extension setting parameters (PC
)
I/O setting parameters (PD
Name
)
No. Symbol
PC01 *ERZ
PC02 MBR
Name
No. Symbol
Error excessive alarm level
PD01
to
For manufacturer setting
Electromagnetic brake sequence output
PD06
PC03 *ENRS Encoder output pulses selection
PC04 **COP1 Function selection C-1
PC05 **COP2 Function selection C-2
PC06 *COP3 Function selection C-3
PD07 *DO1
PD08 *DO2
PD09 *DO3
PD10
Output signal device selection 1 (CN3-13)
Output signal device selection 2 (CN3-9)
Output signal device selection 3 (CN3-15)
For manufacturer setting
PC07 ZSP
PC08
Zero speed
to
For manufacturer setting
PD13
PC09 MOD1 Analog monitor 1 output
PC10 MOD2 Analog monitor 2 output
PD14 *DOP3 Function selection D-3
PC11 MO1
PC12 MO2
Analog monitor 1 offset
Analog monitor 2 offset
PD15
to
For manufacturer setting
PD32
PC13 MOSDL Analog monitor feedback position output
standard data Low
PC14 MOSDH Analog monitor feedback position output
standard data High
PC15
to
For manufacturer setting
PC16
PC17 **COP4 Function selection C-4
PC18
to
For manufacturer setting
PC20
PC21 *BPS
PC22
Alarm history clear
For manufacturer setting
to
PC32
App. 1.2 Converter unit
No. Symbol
Name
Regenerative selection
PA02 *MCC Magnetic contactor drive output selection
PA01 *REG
PA03
to
For manufacturer setting
PA07
PA08 *DMD Auto tuning mode
PA09 *BPS
PA10
Alarm history clear
For manufacturer setting
PA11
PA12 *DIF
PA13
Input filter setting
For manufacture setting
to
PA19
App. - 2
APPENDIX
App. 2 Signal layout recording paper
1
11
LG
13
2
DI1
4
12
DI2
14
LG
3
DOCOM
MO1
6
MO2
16
5
15
DICOM
LA
8
LAR
18
7
LB
9
17
LBR
19
LZ
LZR
20
10
DI3
DICOM
EM1
App. 3 Twin type connector : Outline drawing for 721-2105/026-000(WAGO)
[Unit: mm]
Latch Coding finger
Size [mm]
Model
A
5
B
C
5
D
721-2105/026-000
721-2205/026-000
20
30
5.25
7.75
7.5
7.5
Detecting hole
4
A( B)
26.45
15.1
25
2.75
A
2.9
D
C
4.75
2.7
Driver slot
Wire inserting hole
App. - 3
APPENDIX
App. 4 Change of connector sets to the RoHS compatible products
The following connector sets have been changed to RoHS compliant since September 2006.
RoHS compliant and non-RoHS compliant connector sets may be mixed based on availability.
Only the components of the connector set that have changed are listed below.
Model
MR-J3SCNS Amplifier connector (3M or equivalent of 3M)
MR-ECNM 36210-0100JL (Receptacle) (Note)
MR-PWCNS4 Power supply connector (DDK)
Current Product
RoHS Compatible Product
Amplifier connector (3M or equivalent of 3M)
36210-0100PL (Receptacle)
Power supply connector (DDK)
CE05-6A18-10SD-B-BSS (Connector and Back shell) CE05-6A18-10SD-D-BSS (Connector and Back shell)
CE3057-10A-1 (D265) (Cable clump)
CE3057-10A-1-D (Cable clump)
Power supply connector (DDK)
MR-PWCNS5 Power supply connector (DDK)
CE05-6A22-22SD-B-BSS (Connector and Back shell) CE05-6A22-22SD-D-BSS (Connector and Back shell)
CE3057-12A-1 (D265) (Cable clump)
CE3057-12A-1-D (Cable clump)
Power supply connector (DDK)
MR-PWCNS3 Power supply connector (DDK)
CE05-6A32-17SD-B-BSS (Connector and Back shell) CE05-6A32-17SD-D-BSS (Connector and Back shell)
CE3057-20A-1 (D265) (Cable clump)
CE3057-20A-1-D (Cable clump)
Power supply connector (DDK)
MR-PWCNS1 Power supply connector (DDK)
CE05-6A22-23SD-B-BSS (Connector and Back shell) CE05-6A22-23SD-D-BSS (Connector and Back shell)
CE3057-12A-2 (D265) (Cable clump)
CE3057-12A-2-D (Cable clump)
Power supply connector (DDK)
MR-PWCNS2 Power supply connector (DDK)
CE05-6A24-10SD-B-BSS (Connector and Back shell) CE05-6A24-10SD-D-BSS (Connector and Back shell)
CE3057-16A-2 (D265) (Cable clump)
Electromagnetic brake connector
MS3106A10SL-4S(D190) (Plug, DDK)
Amplifier connector (3M or equivalent of 3M)
10120-3000VE (connector)
CE3057-16A-2-D (Cable clump)
MR-BKCN
MR-CCN1
Electromagnetic brake connector
D/MS3106A10SL-4S(D190) (Plug, DDK)
Amplifier connector (3M or equivalent of 3M)
10120-3000PE (connector)
Note. RoHS compatible 36210-0100FD may be packed with current connector sets.
App. - 4
APPENDIX
App. 5 MR-J3-200B-RT servo amplifier
Connectors (CNP1, CNP2, and CNP3) and appearance of MR-J3-200B servo amplifier have been changed
from January 2008 production. Model name of the existing servo amplifier is changed to MR-J3-200B-RT. The
difference between new MR-J3-200B servo amplifier and existing MR-J3-200B-RT servo amplifier is described
in this appendix. Sections within parentheses in the following sections indicate corresponding sections of the
instruction manual.
App. 5.1 Parts identification (1.7.1 Parts identification)
Detailed
Name/Application
explanation
Display
The 3-digit, seven-segment LED shows the servo
status and alarm number.
Chapter 4
Rotary axis setting switch (SW1)
SW1
8
Used to set the axis No. of servo amplifier.
Section 3.13
8
0
0
ON 4F
SW1
TEST
SW2
Test operation select switch (SW2-1)
Used to perform the test operation
mode by using MR Configurator.
1
2
SW2
Section 3.13
Spare (Be sure to set to the "Down"
position).
1
2
Main circuit power supply connector (CNP1)
Connect the input power supply.
Section 3.1
Section 3.3
USB communication connector (CN5)
Connect the personal computer.
Section 11.8
I/O signal connector (CN3)
Used to connect digital I/O signals.
More over an analog monitor is output.
Section 3.2
Section 3.4
Servo motor power connector (CNP3)
Connect the servo motor.
Section 3.1
Section 3.3
SSCNET cable connector (CN1A)
Used to connect the servo system controller or the front
axis servo amplifier.
Section 3.2
Section 3.4
SSCNET cable connector (CN1B)
Used to connect the rear axis servo amplifier. For the final
axis, puts a cap.
Section 3.2
Section 3.4
Encoder connector (CN2)
Used to connect the servo motor encoder.
Section 3.4
Section 11.1
Battery connector (CN4)
Used to connect the battery for absolute position data
backup.
Section 11.9
Chapter 12
Control circuit connector (CNP2)
Connect the control circuit power supply/regenerative
option.
Section 3.1
Section 3.3
Battery holder
Contains the battery for absolute position data backup.
Section 12.3
Charge lamp
Lit to indicate that the main circuit is charged. While
this lamp is lit, do not reconnect the cables.
Protective earth (PE) terminal (
Ground terminal.
)
Section 3.1
Section 3.3
Cooling fan
Rating plate
Fixed part
(3 places)
Section 1.5
App. - 5
APPENDIX
App. 5.2 Configuration including auxiliary equipment (1.8 Configuration including auxiliary equipment)
R S T
(Note 3)
Power supply
No-fuse breaker
(NFB) or fuse
Magnetic
contactor
(MC)
Personal
computer
MR Configurator
CN5
CN3
(Note 2)
Line noise filter
(FR-BLF)
Servo amplifier
Junction
terminal
block
L1
L2
L3
P1
P2
Servo system
controller or Front axis
servo amplifier CN1B
CN1A
CN1B
(Note 2)
Power factor
improving DC
reactor
Regenerative
option
(FR-BEL)
L11
P
C
Rear servo amplifier
CN1A or Cap
L21
CN2
CN4
(Note 1)
Battery
MR-J3BAT
W
U V
Servo motor
Note 1. The battery (option) is used for the absolute position detection system in the position control mode.
2. The AC reactor can also be used. In this case, the DC reactor cannot be used. When not using DC reactor, short P1-P2.
3. Refer to section 1.3 for the power supply specification.
App. - 6
APPENDIX
App. 5.3 CNP1, CNP2, CNP3 wiring method (3.3.3 CNP1, CNP2, CNP3 wiring method)
(a) Servo amplifier power supply connectors
Servo amplifier power supply connectors
Connector for CNP1
PC4/6-STF-7.62-CRWH
(Phoenix Contact)
Servo amplifier
<Applicable cable example>
Cable finish OD: 5mm or less
CNP1
Connector for CNP3
PC4/3-STF-7.62-CRWH
(Phoenix Contact)
CNP3
CNP2
Connector for CNP2(Note)
54928-0520 (Molex)
<Applicable cable example>
Cable finish OD: 3.8mm or less
Note. As twin type connector for CNP2 (L11, L21) is the same as MR-J3-100B or smaller. Refer to section (1) (c).
(b) Termination of the cables
1) CNP1 CNP3
Solid wire: After the sheath has been stripped, the cable can be used as it is.
Sheath
Core
7mm
Twisted wire: Use the cable after stripping the sheath and twisting the core. At this time, take care to
avoid a short caused by the loose wires of the core and the adjacent pole. Do not
solder the core as it may cause a contact fault. Alternatively, a bar terminal may be
used to put the wires together.
Cable size
Bar terminal type
For 1 cable For 2 cables
AI1.5-8BK
Crimping tool
Manufacturer
2
[mm ]
AWG
16
1.25/1.5
2.0/2.5
3.5
AI-TWIN2 1.5-8BK
AI-TWIN2 2.5-10BU
14
AI2.5-8BU
AI4-10Y
CRIMPFOX-ZA3
Phoenix Contact
12
2) CNP2
CNP2 is the same as MR-J3-100B or smaller capacities. Refer to section 3.3.3 (1) (b).
App. - 7
APPENDIX
App. 5.4 OUTLINE DRAWINGS (Chapter 9 OUTLINE DRAWINGS)
[Unit: mm]
6 mounting hole
90
85
6
Approx.80
45
195
21.4
6
Cooling fan
wind direction
Approx.
25.5
6
Approx.68
78
With MR-J3BAT
6
Mass: 2.3 [kg] (5.07 [lb])
Terminal signal layout
PE terminal
Mounting screw
Screw size: M5
Tightening torque: 3.24 [N m] (28.7 [lb in])
L1
L2
L3
N
Approx. 90
CNP1
P1
P2
Screw size: M4
Tightening torque:
1.2 [N m] (10.6 [lb in])
U
V
CNP3
CNP2
W
3-M5 screw
P
C
D
L11
L21
Approx. 6
Mounting hole process drawing
Approx. 6
78 0.3
App. - 8
APPENDIX
App. 6 Selection example of servo motor power cable
POINT
Selection condition of wire size is as follows.
Wire length: 30m or less
Depending on the cable selected, there may be cases that the cable does not
fit into the Mitsubishi optional or recommended cable clamp. Select a cable
clamp according to the cable diameter.
Selection example when using the 600V grade EP rubber insulated chloroprene sheath cab-tire cable (2PNCT)
for servo motor power (U, V, and W) is indicated below.
Servo motor
HF-SP52
Wire size [mm2]
Servo motor
HC-LP152
Wire size [mm2]
Servo motor
HA-LP30K2
Wire size [mm2]
1.25
1.25
2
2
3.5
5.5
1.25
2
60
60
5.5
5.5
8
HF-SP102
HF-SP152
HF-SP202
HF-SP352
HF-SP502
HF-SP702
HF-SP51
HC-LP202
HA-LP37K2
HC-LP302
HA-LP6014
2
HC-UP72
HA-LP8014
3.5
5.5
8
HC-UP152
HC-UP202
HC-UP352
HC-UP502
HA-LP601
HA-LP12K14
HA-LP15K14
HA-LP20K14
HA-LP25K14
HA-LP30K14
HA-LP37K14
HA-LP701M4
HA-LP11K1M4
HA-LP15K1M4
HA-LP22K1M4
HA-LP30K1M4
HA-LP37K1M4
HA-LP45K1M4
HA-LP50K1M4
HA-LP11K24
HA-LP15K24
HA-LP22K24
HA-LP30K24
HA-LP37K24
HA-LP45K24
HA-LP55K24
3.5
5.5
5.5
8
14
14
22
22
22
5.5
8
1.25
1.25
2
HF-SP81
HF-SP121
HF-SP201
HF-SP301
HF-SP421
HF-SP524
HF-SP1024
HF-SP1524
HF-SP2024
HF-SP3524
HF-SP5024
HF-SP7024
HC-RP103
HC-RP153
HC-RP203 (Note)
HC-RP353 (Note)
HC-RP503 (Note)
HC-LP52
HA-LP801
14
14
22
38
38
38
60
8
2
HA-LP12K1
HA-LP15K1
HA-LP20K1
HA-LP25K1
HA-LP30K1
HA-LP37K1
HA-LP701M
HA-LP11K1M
HA-LP15K1M
HA-LP22K1M
HA-LP30K1M
HA-LP37K1M
HA-LP502
3.5
5.5
1.25
1.25
2
14
14
22
22
38
38
8
2
2
14
22
38
60
60
5.5
8
3.5
5.5
2
14
14
22
22
38
38
2
3.5
5.5
5.5
1.25
1.25
HA-LP702
HA-LP11K2
HA-LP15K2
HA-LP22K2
14
22
22
HC-LP102
Note. Use a composite cable and others when combining with wiring of the electromagnetic brake power in the same cable.
App. - 9
REVISIONS
*The manual number is given on the bottom left of the back cover.
Revision
Print Data
May, 2005
Jan., 2006
*Manual Number
SH(NA)030051-A First edition
SH(NA)030051-B Addition of servo amplifier MR-J3-11KB(4), 15KB(4) and 22KB(4)
Addition of servo motor HC-RP, HC-UP, HC-LP and HA-LP4 series
Section 1.5 (2)
Section 1.7.2
: Addition of regeneration brake resistor-less specification
: Addition of removal and reinstallation of front cover for
11KB(4) or more
Section 2.1
: (1) Addition of 7kW or less
(2) Addition of 11kW or more
Section 3.7.1
: Error correction of differential line driver output as 35mA
: Addition of "For CN2 connector"
Section 3.8 (2)
Section 3.11.2 (4) : Addition of time from invalid to valid of electromagnetic brake
interlock
Section 5.1.3
: Addition of sentence when using with 11KB or more for
parameter No.PA02 00 Addition of FA
: PC13 PC14 description change
Section 5.3.1
Section 5.3.2
Section 5.3.3 (2)
Section 5.3.3 (3)
Section 5.4.2
Section 8.2
: PC13 PC14 description change
: Addition of Note3
: Partial figure change of analog monitor block
: Partial sentence addition of parameter No.PD07
: Addition of "IGBT" to Cause 2. of alarm No. 32 indicated as
Display in the remedies list for alarms
: Addition of POINT
Section 8.3
Section 11.1.1
Section 11.2 (3)
: Partial figure addition
: Addition of sentence when using with 11KB or more for
parameter No.PA02 00 Addition of FA
Section 11.2 (5) (d) : Addition
Section 11.5
Section 11.6
Section 11.7
Section 11.10
Section 11.11
: Addition
: Addition
: Error correction
: Addition
: Addition of cooling fan thermal
Addition of Table 11.2, Note. 2
: Addition of EMC filter HF3100A-UN
Section 11.19
Jul., 2007
SH(NA)030051-C Addition of servo amplifier MR-J3-60B4 to 350B4
Addition of servo amplifier MR-J3-500B4 and 700B4
Addition of servo motor HF-SP524 / 1024 / 1524 / 2024 / 3524
Addition of drive units MR-J3-DU30KB(4), 37KB(4), 45KB4 and 55KB4
Addition of converter unit MR-J3-CR55K(4)
Deletion of setup software notation
Compliance with RoHS
Safety instructions 1.: To prevent electric shock: Addition of Note for 30kW or more
Safety instructions 4.: Additional instructions (2): Correction of the connection
diagram
Conformance with UL/C-UL standard (4): Addition of the capacitor discharge time
for 30kW or more
Conformance with UL/C-UL standard (5): Addition of the fuse for 30kW or more
About the manuals
Section 1.2
: Addition of description about MR-J3-DU B(4)
: Power supply description change
Print Data
Jul., 2007
*Manual Number
Revision
SH(NA)030051-C Section 1.2(1)
Section 1.3
: Unification of Note 3 to Note 2, addition of new Note 3
: Addition of MR-J3-500B4 and 700B4
: Addition of MR-J3-60B4 to 350B4
: Addition of MR-J3-60B4 to 350B4
: Addition of MR-J3-500B4 and 700B4
Addition of combination: MR-J3-60B4 to 350B4 and
servo motor
Section 1.3(2)
Section 1.5(2)
Section 1.6
Section 1.7
: Addition of MR-J3-60B4 to 350B4 as (2) and (4)
: Change of description for "servo motor power supply
connector" to "servo motor power connector"
: Change CAUTION to WARNING
: Power supply description change
: Unification of Note 4 to Note 3, addition of explanation
to Note 2
Section 1.7.1(1) (3)
Section 1.7.2
Section 1.8
Section 1.8(1) (a)
Section 1.8(2) to (7)
Section 2.1(b)
: Addition of explanation to Note 2
: Change of description to "Mounting closely is available
for a combination of servo amplifiers of 200V, 3.5kW or
less"
Chapter 3
: Addition of CAUTION
Section 3.1
: Addition of MR-J3-500B4 and 700B4
: Addition of MR-J3-60B4 to 350B4
: Addition of Note 7
Section 3.1(4)
Section 3.1(6)
Section 3.1(7)
Section 3.1(8)
Section 3.3.1
: Change of description for Note 7
: Change of description for Note 7, addition of Note 9
: Addition of sentence to UVW Description
Addition of MR-J3-60B4 to 350B4 notation to L1, L2, L3,
L11 and L21
Section 3.3.3(1) (b)
Section 3.3.3(2) (b)
Section 3.3.3(3)
: Table content change
: Table content change
: Addition of POINT
Addition of cable handling procedures for MR-J3-200B4
and 350B4
Section 3.3.3(4)
Section 3.3.3(5)
Section 3.4
: Addition and change of description
: Change of description
: Change of CN2 connection diagram to RoHS compliant
parts
Section 3.5(2)
: Addition of sentence to the dynamic brake interlock
description
Change of the zero speed diagram
: Change of description for Function/Application of Digital
I/F common from "DOG EMG" to "EM1"
: Addition of supplementary explanation to the output
pulse
Section 3.5(2) (d)
Section 3.7.2(3) (b)
Section 3.10
: Addition of CAUTION
Section 3.10.1
: Change of description for "motor power supply" to
"servo motor power"
Section 3.10.2(2)
: Addition of POINT for contactor connection, Change of
Note1, Change of “servo alarm” switch to “trouble
(ALM)” in (a) Wiring diagrams
Print Data
Jul., 2007
*Manual Number
Revision
SH(NA)030051-C Section 3.10.2(3)
: Change of Note1 and 3 in (a) 1) and 2), Addition and
change of (b) Terminal box inside diagrams, Addition
and change of corresponding motor models in the
cooling fan power supply list
Section 3.10.2(3) (b)
Section 3.11.3(1)
Section 3.12
: Change of servo motor diagram
: Change of Note1
: Deletion of power specification notation, addition of
Note
Section 4.3(2)
: Correction of indication “Ab.” To “Ab .”, Change of
description for “AC”
Chapter 5
: Change of Basic setting parameters description
: Addition of setting available options
Addition of parameter setting due to addition of
regenerative option
Section 5.1.3
Section 5.1.8
Section 5.2.1
Section 5.3.1
Section 5.3.2
: Deletion of POINT "This parameter cannot be used in
the speed control mode"
: Change of parameter No.PB17 from “for manufacturer
setting” to “Automatic setting parameter”
: Change of parameter No.PC06 from “for manufacturer
setting” to “function selection C-3”
: Addition of Note for parameter No.PC01, Change of
parameter No.PC06 from “for manufacturer setting” to
“function selection C-3”, Addition of Note4 for
parameter No.PC09, Change of setting description for
parameter No.PC10
Section 5.3.3(2)
Section 6.3(1) (a)
Section 6.4(2)
Section 8.2
: Addition of Note4
: Addition of parameter No.PB07
: Change of description for Adjustment procedure Step5
: Addition of Note to the Definition for alarm (32),
Correction of the Cause4 for alarm (52)
: Addition of MR-J3-60B4 to 350B4
Section 9.1
Section 9.1(1) to (7)
Section 9.2(3)
Section 10.1
: Addition of mounting hole dimension diagram
: Description method change
: Change of graph from servo motor standards to servo
amplifier standards
Addition of MR-J3-60B4 to 350B4
Section 10.2
: Addition of MR-J3-60B4 to 350B4 and corresponding
servo motor
Section 10.2(1)
Section 10.3
: Addition of MR-J3-500B4 and 700B4
: Addition of MR-J3-500B4 and 700B4
Paragraphing of section 10.3.1 and section 10.3.2
Addition of dynamic brake time constant for servo motor
HF-SP524 / 1024 / 1524 / 2024 / 3524
Addition of section 10.3.2: Permissible inertia load
moment for MR-J3-60B4 to 350B4
Section 10.5
: Addition of MR-J3-500B4 and 700B4
Addition of inrush current for MR-J3-60B4 to 350B4
Print Data
Jul., 2007
*Manual Number
Revision
SH(NA)030051-C Section 11.1.1
: Change of Application description for No.34 from
“outside panel long distance cable” to “long distance
cable”
Change of connector model
Addition of 2) Connector for 2kW and 3.5kW (400V)
: Deletion of 0.3m from table
Section 11.1.2(1)
Section 11.1.2(1) (a)
: Change of CN2 connection diagram to RoHS compliant
parts
Section 11.1.2(1) (a) (c) : Addition and change of connector description
Section 11.1.2(2)
: Deletion of 0.3m from table
Section 11.1.2(2) (a)
: Addition and change of connector description
Change of CN2 connection diagram to RoHS compliant
parts
Section 11.1.2(3) (a) (c) : Addition and change of connector description
Section 11.1.2(4) (a)
: Change of CN2 connection diagram to RoHS compliant
parts
Section 11.1.2(5) (a)
Section 11.1.4
Section 11.2
: Addition of connector set
: Deletion of 20 to 30m from table
: Addition of regenerative brake options for MR-J3-500B4
and 700B4
Section 11.2(1)
Section 11.2(2) (b)
Section 11.2(3)
: Addition of regenerative option capable for MR-J3-60B4
to 350B4
: Addition of inverse efficiency and capacitor charging for
MR-J3-350B4
: Addition of parameter setting due to addition of
regenerative option
Section 11.2(4)
: Addition of regenerative option MR-RB5G-4
: Addition of regenerative option MR-RB3M-4, MR-
RB3G-4
Section 11.2(5) (b)
Section 11.2(5) (c)
Section 11.2(5) (f)
Section 11.3
: Addition of regenerative option MR-RB5G-4
: Addition of regenerative option MR-RB1H-4
: Addition of brake unit for MR-J3-500B4 and 700B4
: Change of description
Section 11.3(3) (b)
Section 11.4
: Addition of power regeneration converter for MR-J3-
500B4 and 700B4
Section 11.4(2)
: Deletion of notation for power supply specification,
change of description in Note 5, addition of Note 6
: Addition of Note 6 to disconnect the wiring of
regenerative brake register in servo amplifier of 7kW or
less
Section 11.4(3) (b)
Section 11.5(3) (b)
Section 11.5(4) (b) 2)
Section 11.5(6)
: Addition of Note 8
: Revision of cable diameter for 400V, deletion of Note
: For item: Altitude, vibration, deletion of description
"compliant with JIS"
Section 11.6(1)
Section 11.6(2)
Section 11.8(1)
Section 11.11
: Addition of Note 5
: Change of CN3 description Deletion of Note 1
: Addition of MR Configurator compatible version
: Addition of recommended wires for MR-J3-500B4 and
700B4
Print Data
Jul., 2007
*Manual Number
Revision
SH(NA)030051-C Section 11.11(1)
: Addition of cable diameter for MR-J3-60B4 to 350B4,
addition of Note 3: Cable 5) to 7) of MR-J3-700B(4)
: Addition of MR-J3-60B4 to 350B4 compliant products
Addition of no-fuse breakers, fuses and magnetic
contactors for MR-J3-500B4 and 700B4
: Addition of MR-J3-60B4 to 350B4 compliant products,
unification of (1) and (2)
Section 11.12
Section 11.13
Addition of power factor improving DC reactors for MR-
J3-500B4 and 700B4 Change of (2) Note2 Addition of
Note3
Section 11.14
Section 11.18
: Addition of MR-J3-60B4 to 350B4 compliant products
Addition of power factor improving AC reactors for MR-
J3-500B4 and 700B4
: Addition of MR-J3-60B4 to 350B4 as earth leakage
circuit breaker selection example
Section 11.19
: Addition of EMC filter for MR-J3-500B4 and 700B4
: Addition of MR-J3-60B4 to 350B4 compliant products,
deletion of Note from TX series
Section 11.19(1)
Section 11.19(3)
Section 12.3(1)
: Addition of TF3005C-TX
: Addition of description for 30kW or more in
“WARNING”, Addition of POINT
Chapter 13
: New addition of the details for 30kW or more
Change of notation "magnet contactor" to "magnetic
contactor"
Section 13.1.6(1)
: Change of description "I/O signal connector" to "Digital
I/O connector", addition of rating plate
Change in description of CN3 and CN6
: Change of rating plate designated position
: Enlargement of diagram for removing and reinstalling
terminal block cover
Section 13.1.6(2) (3)
Section 13.1.7
Section 13.3
: Addition of POINT: reference "Signal (device)
explanations, section 3.5"
Section 13.3.1(1) (a)
Section 13.3.1(1) (b)
Section 13.3.1(2) (a)
: Revision of magnetic contactor sequence, addition of
Note 3
: Revision of magnetic contactor sequence, addition of
Note 3 and 4
: Revision of magnetic contactor sequence, addition of
Note 3 and 4, addition of magnetic contactor control
(CNP1)
13.3.1(2) (b)
13.3.2(1), (2)
: Revision of magnetic contactor sequence, addition of
Note 3 to 5, addition of magnetic contactor control
(CNP1)
: Change of description in Note for "servo motor output"
and "servo motor power supply" to "servo motor power"
: Correction of reference for CN2 and CN3
: Raise of section 13.3.5 (3) to section 13.3.6
: Raise from section 13.3.6, Change of description in
chart: "servo motor power" to "servo motor power
supply"
Section 13.3.4(2)
Section 13.3.6
Section 13.3.7
Section 13.4.3(2) (b)
Section 13.4.3(3)
: Change of display
: Deletion
Print Data
Jul., 2007
*Manual Number
Revision
SH(NA)030051-C Section 13.5.2
Section 13.6.1(3)
: Deletion of parameter No.PA08 name and initial value
: Deletion of "built-in regenerative register" from
excessive regenerative load warning (A.E0) definition
and cause
Section 13.8.1
Section 13.9.1
: Division of Load ratio graph for MR-J3- B(4) and MR-
J3-CR55K(4)
: Addition of notation "supplied with converter unit" for
7) and 8)
Section 13.9.2(5)
Section 13.9.3(2)
: Addition of Note
: Revision of connection diagram, change of Note 2,
addition of Note 5
Section 13.9.3(3)
Section 13.9.4
Section 13.9.5
Section 13.9.7
Section 13.9.8(1) (2)
Appendix 1
: Addition of mass table
: Deletion of notation for UL/C-UL from body paragraph
: Deletion of Note
: Change of body paragraph
: Change of Iga display range in the diagram
: Change of parameter No.PB17 from “for manufacturer
setting” to “Automatic setting parameter”
Change of parameter No.PC06 from “for manufacturer
setting” to “function selection C-3”
Appendix 5
: Update of the “combination of servo amplifier and
servo motor” table
Jun, 2008
SH(NA)030051-D (2)Wiring
: Change of description for “the servo motor will operate
improperly” to “the servo motor will not operate
properly” for the item of connection between the servo
amplifier and the servo motor
Conformance with UL/C-UL standard (3): Change of description
Conformance with UL/C-UL standard (5): Deletion of list of combination with fuse
About the wires used for wiring: Addition of the selected standard temperature
Section 1.2 (1) to (3)
Section 1.3 (1)
: Change of switch numbers
: Change of description for the mass “2.3” to “2.1”of
MR-J3-200B, Change of pound notation for mass to
three significant digits
Section 1.5 (2)
Section 1.6
: Change of appearance of MR-J3-200B to the same as
MR-J3-200B4
: Addition of models with reduction gear to body
paragraph
Section 1.7.1 (3) (4)
: Switch between (3) and (4), Change of the description
for MR-J3-200B to the same as MR-J3-200B4,
Addition of Note 4 to (3).
Section 1.8 (3) (4)
Section 2.1 (1) (b)
: Switch between (3) and (4), Change of the description
for MR-J3-200B to the same as MR-J3-200B4,
Addition of Note 4 to (3). Deletion of Note 3 from (4)
Addition of description for FR-BEL to (3)
: Change of description for “Mounting closely is
available for a combination of servo amplifiers of
3.5kW or less in 200V or 100V class.” to “Mounting
closely is available for a combination of servo
amplifiers of 3.5kW or less in 200V or 400W or less in
100V class.”
Section 2.3 (2)
: Change of description
Section 3.1 (5) to (8)
: Addition of NFB for the fan power cables of the servo
motor’s cooling fan
Print Data
Jun, 2008
*Manual Number
Revision
SH(NA)030051-D Section 3.2
: Change of Note 15
Section 3.3.3 (1) (a)
: Change of CNP2 connector model from “54927-0520”
to “54928-0520”
Section 3.3.3 (2) (3)
Section 3.7.2 (2)
: Switch between (2) and (3), Change of the description
for MR-J3-200B to the same as MR-J3-200B4
: Addition of description for the condition “Maximum
current: 50mA or less” to body paragraph
Section 3.10.2 (3) (a) 1) to : Addition of NFB for fan power cable of servo motor’s
2)
cooling fan, Change of description for Note 1
: Change of servo motor’s terminal diagram
: Change of timing chart
Section 3.10.2 (3) (b)
Section 3.11.2
Section 4.1.2 (1) (c) 2) to : Change of description for “D terminal” to “C terminal”
3)
Section 5.2.1
: Change of PB06 and PB29 unit for “times” to
“Multiplier(×1)”
Section 7.4
: Change of description
Section 7.6.3
: Change of PB06 and PB29 unit for “times” to
“Multiplier(×1)”
Section 7.6.4 (1) (a)
Section 7.6.4 (2) (a)
Section 10.1 (5) (6)
: Change of PB06 and PB29 unit for “times” to
“Multiplier(×1)”
: Change of PB06 and PB29 unit for “times” to
“Multiplier(×1)”
: Switch between (5) and (6), Change of the description
for MR-J3-200B to the same as MR-J3-200B4,
Addition of POINT to (5)
Section 10.3.1 (2)
: Addition of dynamic brake characteristics of HA-SP,
HA-LP, HC-RP, HC-UP, and HC-LP
Section 11.1
: Addition of POINT for protective structure
: Deletion of 2kW from Application, upper stand of 2) in
Table, Change of description for “2kW or less in 400V
class” to “2kW in 200V and 400V class”, Change of
corresponding model from “HF-SP121
٠ 201” to “HF- SP121 to 301” for 29) in Table, Change of
corresponding model for 30) in Table, Deletion of IP65
from Application, Change of corresponding model for
38) and 40) in Table, Deletion of IP67 from
Application, Deletion of IP67 from Application for 39)
in Table
Section 11.1.1
Section 11.1.2 (2) (b)
Section 11.1.2 (3) (a)
Section 11.1.2 (4)
: Correction of Note position for connecting diagrams
such as MR-EKCBL30M-H
: Addition of description “Crimping tool: 91529-1” in the
list of Junction Connector
: Change of corresponding model of “HF-SP” to “HF-
SP HA-LP HC-RP HC-UP HC-LP”
: Addition of corresponding model of “HA-LP HC-
RP HC-UP HC-LP”
Section 11.1.2 (5)
Section 11.1.2 (5) (a)
: Change of junction connector of “36110-3000PL” to
“36110-3000FD", Battery connector from “DF3-
EP2428PCFA” to “DF3-EP2428PCA”
: Addition of Note
Section 11.1.3 (2)
Section 11.1.4 (2)
Section 11.2 (1)
: Addition of Note
: Change of built-in regenerative register value of MR-
J3-60B4 100B4 from “15” to “20”, Addition of Note 1
Print Data
Jun, 2008
*Manual Number
Revision
SH(NA)030051-D Section 11.2 (4)
Section 11.2 (5) (a)
: Change of description
: Change of tightening torque size from “3.2” to “3.24”
: Change of description
Section 11.3.3 (4) (a)
Section 11.3.4 (2)
: Correction of C dimension
Section 11.5 (4) (a) 1)
: Addition of POINT for selection condition of wire sizes,
Deletion of “The used wires are based on the 600V
vinyl wires.” from the sentence
Section 11.5 (4) (b) 1)
Section 11.5 (4) (b) 2)
: Change of wiring length of servo amplifier (3.5kW) in
connection diagram from “5.5mm2” to “3.5mm2”
: Change of wiring length between the servo amplifier
(2kW) and the one (15kW) in connecting diagram
: Addition of Note to Table
Section 11.6 (3) (a)
Section 11.6 (3) (b)
Section 11.8 (2) (a)
: Addition of Note to Table
: Table content change, Change of position for
Windows Vista, Deletion of RS-422/232C conversion
cable
Section 11.11
: Change of description for “Recommended wires” to
“Wires selection example”, Addition of three POINTs
: Deletion of body paragraph, Change of description for
IV wires selection example, Addition of HIV wires
selection example, Change of crimping terminal
selection example
Section 11.11 (1)
Section 11.12
: Change of Table
Section 11.13
: Addition of table for dynamic brake wire size
: Deletion of AC electromagnetic brake from body
paragraph
Section 11.17 (2) (b)
Chapter 12
: Change of description for Note, Addition of POINT
: Partial deletion of body paragraph
Section 13.1.5
Section 13.3
: Change of description for Note
Section 13.3.7 (1) (b)
: Change of timing chart
Section 13.3.7 (3) (a) 1) to : Addition of Note
3)
Section 13.7.1
: Change of pound notation for mass to three significant
digits
Section 13.7.2
Section 13.8.3
: Change of pound notation for mass to three significant
digits
: Change of description form, Change of dynamic brake
of HA-LP2000r/min series characteristics, Change of
body paragraph
Section 13.9.1 (2)
Section 13.9.3 (2)
Section 13.9.4
: Change of Note
: Addition of Note to Table
: Change of description for "Recommended wires” to
“Wires selection examples”, Addition of three POINTs
: Deletion of body paragraph, Change of description for
IV wires selection example, Addition of HIV wires
selection example, Change of crimping terminal
selection example
Section 13.9.4 (1)
Section 13.9.5
Section 13.9.9 (2)
Section 13.9.10 (4) (b)
Appendix 4
: Deletion of Note
: Deletion of surge protectors from wiring diagram
: Correction of C dimension
: Change of body paragraph
: New addition for explanation of servo amplifier MR-J3-
200B-RT
Appendix 5
Print Data
Jun, 2008
*Manual Number
SH(NA)030051-D
Revision
Appendix 6
: New addition of servo motor power cables selection
example
SH(NA)030051-D
MR-J3-B INSTRUCTIONMANUAL
MODEL
MODEL
CODE
1CW202
HEAD OFFICE : TOKYO BLDG MARUNOUCHI TOKYO 100-8310
This Instruction Manual uses recycled paper.
Specifications subject to change without notice.
SH (NA) 030051-D (0806) MEE
Printed in Japan
|