Honeywell Local Operator Interface S7999B User Manual

S7999B, S7999C SOLA  
Local Operator Interface  
PRODUCT DATA  
From behind into a panel cutout (5.45 in. W X 4.3 in. H)  
using 4 #6-32 screws, nuts and 4 standoffs (provided).  
Wiring connections to the S7999C are made via a 4-pin  
connector on the back of the display.  
NOTE: If display S7999B is used to monitor a lead/lag sys-  
tem, display S7999C can NOT be used.  
FEATURES  
Individual boiler status, configuration, history, and  
diagnostics.  
Allows configuration and monitoring of the Sola  
Controls (R7910A Hydronic Controls or R7911 Steam  
Control) burner control sequence, flame signal,  
diagnostics, historical files, and faults.  
S7999B OI Display only:  
APPLICATION  
Allows switching view between multiple boilers  
Allows viewing Lead-Lag Master  
Ethernet port for downloading software upgrades  
(when required)  
The S7999B and S7999C are microprocessor-based touch-  
screen Operator Interface (OI) displays that provide an  
operator interface for monitoring and configuring parameters  
in the Sola Hydronic Control and Sola Steam Control system.  
Real-time data trending analysis and transferring  
saved trend data to Excel spreadsheet.  
Audible Alarm  
COM 2 Modbus port for Building Automation System  
applications.  
The S7999B can be used to monitor an individual boiler but is  
primarily used for multiple boiler applications in a lead/lag  
arrangement. COM 2 port is available for Building Automation  
applications. The S7999B display is flush mounted into a  
panel cutout (8-1/8 in. W x 5-7/8 in. H). Wiring connections to  
the S7999B are through a removable 9-pin wiring header.  
LED indicators:  
Power  
Network  
COM 2  
COM 1  
The S7999C display is used for individual boiler monitoring.  
The S7999C is mounted:  
Models available:  
S7999B1026 has Blue Border  
onto a panel using the wallplate provided.  
from the front into a panel cutout (7.6 in. W X 5.4 in. H)  
using 4 #6-32 screws and nuts (provided).  
S7999B1067 has Black Border  
S7999C OI Display only:  
Contents  
Table 61 Configurable Parameters. .................................. 53  
Table 62 Other Tables. ..................................................... 61  
65-0303-05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
The software upgrade is automatic after the above steps. The  
OI Display connects to the Honeywell server, which verifies the  
configuration file, erases the old application and downloads the  
new one.  
Storage/Shipping Temperature: -40°F to 158°F  
(-40°C to 70°C).  
Humidity:  
85% maximum relative humidity.  
The OI Display may have difficulty finding the new  
configuration file at first. In this case, the procedure  
automatically starts over again until it works.  
Approvals:  
FCC Part 15, Class A Digital Device  
Underwriter’s Laboratories, Inc. (UL) (cUL) Component  
Recognized (for non-continuous operation): File Number  
MH20613 (MCCZ)  
S7999C Only  
Canada: ICES-003  
Software upgrades for S7999C OI Display (when needed) will  
be provided by Honeywell and are accomplished through the  
MMC port located on the top back of the device.  
Dimensions: See Fig. 1.  
Replacement Parts (S7999B)  
SPECIFICATIONS  
9-pin connector—50020034-001  
Power Supply—Manufactured by MeanWell,  
Model S-25-12 (order from manufacturer).  
#6-32 X1-in. screws(4) with nuts (4)  
Electrical Ratings:  
+12 Vdc input, maximum of 500 mA current drain.  
Included Power Supply for S7999B:  
Inputs: 85 to 264 Vac, 47 to 63 Hz; 120 to 370 Vdc.  
Output: 12 Vdc; 0 to 2.1 A.  
Power: 25 W.  
Supplied Parts (S7999C)  
Mounting Plate - see Fig. 9 for dimensions and hole  
locations.  
Included Power Supply for S7999C:  
Inputs: 100 to 240 Vac.  
Output: 12 Vdc; 0.42 A.  
Power: 25 W.  
#6-32 X 1-in. screws (4) with nuts (4)  
Standoffs 5/16-in. dia. X 3/8 in. long (4)  
Power Supply—Manufactured by V-infinity  
Model FSC-S5-12U (order from manufacturer).  
Operating Temperature: 32°F to 122°F (0°C to 50°C)  
9-7/16 (240)  
8-15/16 (227)  
7-19/32 (193)  
1
3-1/2  
(89)  
6-21/32  
(169)  
5-13/32  
(137)  
1
1-33/64  
(39)  
1
PANEL HOLE CUTOUT SIZE 7-19/32 (193) WIDE X 5-13/32 (137) HIGH FOR S7999B DISPLAY 7.6 WIDE X 5.4 HIGH..  
M29867A  
Fig. 1. OI Display dimensions (S7999C shown) in in. (mm).  
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the  
FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment  
is operated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy and, if  
not installed and used in accordance with the instruction manual, may cause harmful interference to radio communica-  
tions. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be  
3
65-0303—05  
 
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
required to correct the interference at his own expense.  
This Class A digital apparatus complies with Canadian ICES-003.  
Cet Appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.  
SAFETY FEATURES  
The OI Displays contain software that incorporates many  
features that are designed to guide you safely through the  
commissioning process. Safety, however, is your responsibility.  
Read all documentation carefully and respond appropriately to  
all error messages.  
1
2
3
4 5  
6
7
8
9
WARNING  
Improper configuration can cause fuel buildup and  
explosion.  
Explosion Hazard.  
M28859A  
Fig. 2. S7999B OI Display connector terminals.  
Improper user operation may result in PROPERTY  
LOSS, PHYSICAL INJURY or DEATH.  
7. Select a location inside the enclosure for mounting the  
power supply.  
8. Using the power supply as a template, mark the loca-  
tions of the two mounting holes in the enclosure.  
9. Remove the power supply.  
Using the OI Displays to change parameters, must be  
attempted by only experienced and/or licensed  
burner/boiler operators and mechanics.  
10. Drill 1/4 in. holes through the panel at the marked loca-  
tions and secure the power supply with the two #6-32  
screws and nuts provided.  
11. Remove the 9-pin connector plug from the back of the OI  
Display.  
12. Wire the connector to the power supply and the RS-485  
cables using the wiring diagram in Fig. 3.  
13. Ensure the 9-pin connector plug is aligned with the  
header pins when inserting the 9-pin connector plug  
back onto the Display. Secure firmly.  
INSTALLATION INSTRUCTIONS  
(S7999B OI DISPLAY)  
NOTE: For S7999C OI Display installation instructions, see  
Mounting the S7999B OI Display and  
Power Supply  
WIRING (S7999B OI DISPLAY)  
The OI Display can be mounted on the door panel of an  
electrical enclosure.  
The S7999B OI Display must be appropriately wired for both  
power and communications. An external 12V power supply  
(provided) with an appropriate power rating is connected to  
pins 1, 2 and 3 to power the device.  
1. Select the location on the door panel to mount the dis-  
play; note that the device will extend into the enclosure  
at least one inch past the mounting surface.  
2. Provide an opening in the panel door 8-1/8 in. wide by 5-  
7/8 in. high.  
Communication is done over a RS-485 bus:  
3. Place the OI Display in the opening and use it as a tem-  
plate to mark the location of the four mounting screw  
holes. Remove the device.  
COM1 connected directly to the SOLA Device J3 connector  
to either Modbus (MB1 or MB2).  
COM2: A bus to the Building Automation System.  
4. Using pilot holes as guides, drill 1/4 in. holes through the  
See Fig. 2 for S7999B Display connector terminals. Wiring  
connections are listed in Table 1. See Fig. 3 for wiring.  
door panel.  
5. Place the display in the opening, aligning the mounting  
holes in the device with the drilled holes in the panel.  
6. Secure the display to the panel with four #6-32 screws  
and nuts provided.  
Table 1. 9-pin Connector Terminals  
Pin #  
Function  
1
2
3
4
5
6
7
8
12V input  
12V input  
Common (Power, COM 1)  
COM 1 (b) to MB1 or MB2 terminal  
COM 1 (a) to MB1 or MB2 terminal  
Not used  
Not used  
COM 2 (a)  
65-0303—05  
4
   
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 1. 9-pin Connector Terminals  
Pin #  
Function  
9
COM 2 (b)  
S7999B  
AS LOCAL DISPLAY  
COM2  
8
COM1  
1
2
3
4
5
6
7
9
120  
VAC  
L1  
L2  
GND  
(C)  
(B) (A)  
+12  
+12  
(B)  
(A)  
N/C N/C  
BAS  
NEUTRAL (L2)  
N
L
120VAC (L1)  
EARTH  
GROUND  
MEAN WELL S-25-12  
POWER SUPPLY  
12 DC OUT +  
2
V+  
V-  
1
DC OUT  
(COMMON GND)  
A
B
C
A
B
C
1
2
3
J3  
MB1  
MB2  
ECOM  
V ADJ  
SOLA CONTROL  
WIRING KEY  
LINE VOLTAGE  
LOW VOLTAGE  
DATA  
1
2
DO NOT CONNECT THE S7999B TO TERMINALS 1 2 3. THIS WILL RENDER THE DISPLAY INOPERABLE.  
DISPLAY CAN ALSO BE CONNECTED TO MB2; A, B, C.  
M32004  
Fig. 3. S7999B wiring diagram.  
5
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
S7999B  
AS SYSTEM DISPLAY  
COM1  
120  
COM2  
8
L1  
VAC  
1
2
3
4
5
6
7
9
L2  
GND  
(C)  
(B)  
N/C N/C  
(A)  
(A)  
(B)  
+12 +12  
NEUTRAL (L2)  
120VAC (L1)  
N
L
EARTH  
GROUND  
MEAN WELL S-25-12  
POWER SUPPLY  
12 DC OUT +  
V+  
V-  
2
DC OUT  
(COMMON GND)  
VADJ  
A
A
A
A
B
MB1  
3
C
C
C
C
A
B
C
1
1
1
1
2
ECOM  
1
3
J3  
MB2  
WIRING KEY  
SOLA LL MASTER  
AND SLAVE 1  
LINE VOLTAGE  
LOW VOLTAGE  
DATA  
1
2
3
DO NOT CONNECT THE S7999B TO TERMINALS 1 2 3.  
THIS WILL RENDER THE DISPLAY INOPERABLE.  
B
A
B
C
2
3
DISPLAY CAN ALSO BE CONNECTED TO MB2; A, B, C  
AND THE SOLA SLAVES NEED TO BE WIRED TO MB1.  
J3  
MB1  
MB2  
ECOM  
SOLA SLAVE 2  
CONTROLLER HAS TWO AVAILABLE MODBUS  
CONNECTIONS: THIS CONFIGURATION REQUIRES ONE  
FOR CONTROL LEAD LAG COMMUNICATION AND ONE  
FOR A S7999B SYSTEM DISPLAY.  
THERE IS NOT A CONNECTION AVAILABLE FOR A  
LOCAL TOUCHSCREEN DISPLAY (S7999C).  
B
A
B
C
2
3
THE ECOM CONNECTION IS AVAILABLE FOR  
CONNECTIONS OF A LOCAL KEYBOARD  
DISPLAY MODULE.  
J3  
MB1  
MB2  
ECOM  
SOLA SLAVE 3  
4
UP TO A MAXIMUM OF 8 SOLA SLAVES IN A  
LEAD LAG NETWORK.  
B
A
B
C
2
3
J3  
MB1  
MB2  
ECOM  
4
SOLA SLAVE 4  
M32005  
Fig. 4. S7999B wiring diagram for lead lag.  
Ensure all S7999B devices have unique Modbus addresses as  
defined in Fig. 5.  
BUILDING AUTOMATION  
SYSTEM (BAS)  
CONFIGURATION  
Connect the BAS Modbus wiring to COM2 of the S7999B as  
shown in Fig. 5.  
65-0303—05  
6
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
BAS  
COM 2  
S7999B  
COM 1  
COM 2  
S7999B  
COM 1  
COM 2  
S7999B  
1
COM 1  
3
UP TO 8  
SOLAS  
1
2
4
5
SOLA  
SOLA  
SOLA  
SOLA  
SOLA  
1
EACH SOLA IN THE BAS WILL HAVE A DIFFERENT MODBUS ADDRESS.  
M32006  
Fig. 5. S7999B in a Building Automation System.  
BAS Modbus message timeout should be set to 1.0 seconds or  
higher. This means it could take up to 1.0 seconds (max) for  
the System Display to reply to a BAS message.  
If the screen is dim, check the pin 1 and 2 wiring connections.  
NOTE: An Advanced Startup screen displays for five seconds  
after power-up before the Home page displays. This  
screen allows the user to upgrade the software in the  
System Display (see “Preface” on page 2) and should  
normally be bypassed.  
Retries: BAS must setup retries upon timeout to ensure the  
Modbus request is accepted.  
BAS Modbus poll rate should be set to 1.0 seconds. This  
means that the BAS should wait for a minimum of 1.0 seconds  
after receiving a Modbus message from Sola before sending a  
new Modbus message.  
Three LEDs exist for I/O traffic: one for the Ethernet network  
port and two for Modbus™ ports. The ethernet port should only  
be used if instructed by Honeywell that an update is necessary.  
Modbus Com Port 2 is not active on this device.  
1. Make sure the Power and COM1 LEDs are blinking.  
2. If the LEDs are not blinking:  
QUICK SETUP (S7999B OI  
DISPLAY)  
a. Make sure the proper connections have been made  
between the Modbus COM1 Port and the first control-  
ler device in the Modbus network.  
proper wiring of the OI Display 9-pin Header  
Connections.  
1. Make sure the S7999B 9-pin connector is properly  
aligned and pressed firmly in place.  
2. Make sure the wires between the 9-pin connector and  
the controller are properly wired and secure.  
3. If connected to a BAS application, COM2 LED will blink  
indicating BAS traffic.  
WARNING  
Can cause severe injury, death or equipment  
damage.  
Home Page (S7999B OI Display)  
Electrical Shock Hazard.  
Make sure a screen similar to Fig. 6 appears after the OI  
Display has completely powered up.  
Line voltage is present at the 120 Vac power supply.  
On System applications, each SOLA Control is represented on  
the Home page by an icon and name. Pressing the icon allows  
the user to zoom in on that boiler and see its specific details.  
These details are provided on a new page, which can include  
additional buttons that display additional detail and operation  
information, which itself leads to other pages. The pages are  
traversed in a tree structure method, as shown in Fig. 8.  
3. Make sure the power supply is connected securely to the  
120 Vac power source.  
STARTING THE S7999B OI  
DISPLAY  
The Sola icons will appear in one of four colors indicating the  
boiler status.  
Power-up Validation  
Blue: Normal operation  
Red: Lockout condition  
Gray: Standby mode (burner switch off)  
The Home page will appear and the “Power” LED will be  
blinking when the device is properly powered. Select the 1234  
Setup button to adjust the contrast and sound as desired.  
7
65-0303—05  
 
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Gray and crossed out: communication error (disconnected  
or powered off)  
Up to 8 Systems can be displayed on the Home page. The  
name of each boiler is displayed next to the Sola icon button.  
When Lead Lag is enabled, the system header temperature  
and firing rate are displayed for each System. When the burner  
is in standby or not firing the firing rate is not displayed.  
NOTE: The boiler name may be cut off on the Home page  
when all icons are present.  
The Home page also includes a System Analysis button that  
allows the user to view status information on a system-wide  
(that is, multiple boiler) basis. The user can choose which  
status information to compare from the SOLA Controls in the  
system.  
Pressing the 1 2 3 4 Setup button on the Home page displays  
miscellaneous setup and diagnostic functions beginning on  
page 47 (see also Table 61 on page 53). It also contains the  
setup configuration for BAS applications, under the Advanced  
Setup button.  
Fig. 6. S7999B Home page (Boiler 1 in normal operation).  
Pressing the SOLA icon opens that control’s status page. Go to  
Fig. 7. S7999B Lead Lag Home page.  
65-0303—05  
8
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
HOME  
PAGE  
1 2 3 4  
PROGRAM  
SETUP  
MODULE  
KEY  
CLEAN  
SCREEN  
BUTTON FLOW  
BACK ICON FLOW  
SYSTEM  
CONFIG.  
HOME ICON ALWAYS TAKES  
YOU TO THE HOME PAGE  
SUMMARY  
PAGE  
ADVANCED  
SETUP  
CONFIGURE  
OPERATION  
DIAGNOSTICS  
DETAILS  
History  
HISTORY  
MODULATION  
SETPOINTS  
Configuration  
Groups  
CH  
Diagn.  
Test  
OK  
Login  
Logout  
Verify  
Login  
DHW  
Lockouts  
Burner  
Control  
Alerts  
PUMPS  
?
Diagn.  
Alerts  
Digital  
I/O  
Analysis  
Silence  
Analog  
I/O  
M13965  
Fig. 8. S7999B display page flow.  
INSTALLATION INSTRUCTIONS  
(S7999C OI DISPLAY)  
2-3/4 (70)  
1/2  
(13)  
NOTE: For S7999B OI Display installation instructions, see  
page 4.  
1-21/32  
(42)  
3-13/64  
(81)  
The S7999C display is used for individual boiler monitoring.  
The S7999C is mounted:  
onto a panel using the wallplate provided.  
from the front into a panel cutout (7.6 in. W X 5.4 in. H)  
using 4 #6-32 screws and nuts (provided).  
From behind into a panel cutout (5.45 in. W X 4.3 in. H)  
using 4 #6-32 screws, nuts and 4 standoffs (provided).  
1-13/16 (46)  
M27606  
Mounting the S7999C OI Display  
using the wallplate (provided)  
Fig. 9. S7999C wallplate dimensions in in. (mm).  
1. Select the location to mount the OI display; this could be  
a location up to 1000 feet from the SOLA control.  
Mounting the S7999C OI Display  
directly to the Door Panel  
2. Use the device wallplate as a template to mark the loca-  
tion of three or four mounting screw holes. See Fig. 9.  
3. Drill 3/16 in. holes for mounting the wallplate.  
4. Secure the wallplate with three or four #6-32 screws.  
5. Bring power and communication wire through the wall  
plate and attach to the terminals on the back of the dis-  
play before installing the display to the wall plate.  
1. Select the location to mount the display.  
2. Cut an opening to facilitate mounting the display into the  
door panel. See Fig. 1 for the dimensions for mounting  
the display from the front of the door. See Fig. 10 for  
mounting the display to the back of the door. If desired,  
cut a notch so the LEDs will be visible as well. Tear off  
templates are also available on the back pages of this  
Manual (see Fig. 121 on page 63 and Fig. 122 on page  
65).  
3. Fit the display into the opening and use the screw holes  
in the device as a template to mark the location of the  
four mounting screw holes.  
9
65-0303—05  
 
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
4. Drill 3/16 in. holes for mounting the display.  
5. Secure the OI Display to the panel using the four #6-32  
screws and nuts, as shown in Fig. 10. (Standoffs are pro-  
vided for mounting the OI Display from the back of the  
door.)  
OPTIONAL  
CUTOUT  
CUTOUT  
SPACER (4)  
WALL  
M29868  
Fig. 10. Mounting the S7999C OI Display behind the door panel.  
Table 2. 4-pin Connector Terminals (located on the  
back of the S7999C OI Display).  
S7999C OI Display Power supply  
mounting.  
Pin #  
Function  
1. Select a location inside the enclosure for mounting the  
power supply.  
+
-
12Vdc input  
12Vdc Input  
2. Using the power supply as a template, mark the loca-  
tions of two mounting holes in the enclosure.  
3. Remove the power supply.  
G
Data (+) Output (Modbus a)  
4. Drill 1/4 in. holes through the panel at the marked loca-  
tions and secure the power supply with the two #6-32  
screws and nuts provided.  
S7999C CAN BE  
CONNECTED TO  
EITHER MB1 OR  
MB2 A, B, C  
S7999C MID-  
LEVEL DISPLAY  
+
G
Y
WIRING (S7999C OI DISPLAY)  
TERMINALS  
L2  
L1  
V+  
V–  
N
L
120  
VAC  
V-INFINITY  
FSC-S5-12U  
The S7999C OI display must be appropriately wired for both  
power and communications.  
1
WIRING KEY  
LINE VOLTAGE  
LOW VOLTAGE  
DATA  
A
B
MB1  
A
B
MB2  
2
3
C
C
1
1. Wire the power supply and the RS-485 communication  
ECOM J3  
R7910 HYDRONIC CONTROL OR  
cables per Table 2 and the wiring diagram in Fig. 11.  
R7911 STEAM CONTROL  
Y and G are connected directly to the display and  
either SOLA Control connector J3 Modbus (MB1) or  
Modbus (MB2).  
1
DO NOT CONNECT S7999C TO TERMINALS 1 2 3 AS THIS WILL RENDER  
THE DISPLAY INOPERABLE.  
M32008  
2. Make sure the 12 Vdc power supply (supplied with the  
S7999C) is connected securely to the 120 Vac power  
source.  
Fig. 11. S7999C wiring diagram.  
Table 2. 4-pin Connector Terminals (located on the  
back of the S7999C OI Display).  
WARNING  
Electrical Shock Hazard.  
Can cause severe injury, death or equipment  
damage.  
Line voltage is present at the power supply.  
Pin #  
Function  
Y
Data (-) Output (Modbus b)  
65-0303—05  
10  
 
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
S7999C  
3
4
MID-LEVEL DISPLAY  
Y
+
G
L2  
L1  
N
L
V+  
V-  
120  
V-INFINITY  
FSC-S5-12U  
VAC  
WIRING KEY  
LINE VOLTAGE  
A
B
C
A
B
C
1
2
ECOM  
1
3
J3  
MB1  
MB2  
S7999C  
MID-LEVEL DISPLAY  
LOW VOLTAGE  
DATA  
SOLA  
2
4
3
LL MASTER AND SLAVE 1  
Y
+
G
1
2
DO NOT CONNECT THE S7999C TO  
TERMINALS 1 2 3. THIS WILL RENDER  
THE DISPLAY INOPERABLE.  
DISPLAY CAN BE CONNECTED TO MB1  
OR MB2; A, B, C AS LONG AS THE  
REMAINING MB TERMINAL IS USED  
FOR THE SLAVE COMMUNICATIONS.  
A
B
C
A
B
C
1
2
ECOM  
1
3
S7999C  
MID-LEVEL DISPLAY  
J3  
MB1  
MB2  
SOLA SLAVE 2  
2
4
3
3
4
WIRE V-INFINITY POWER SUPPLY  
TO + AND - TERMINALS.  
Y
+
G
S7999C CONNECTED TO THE MASTER  
CAN CONFIGURE THE MASTER.  
IT CAN ALSO CONFIGURE THE SLAVE  
INFORMATION IN THIS CONTROL AS WELL  
AS MONITOR THIS SLAVE’S ACTIVITIES.  
A
B
C
A
B
C
1
2
ECOM  
1
3
J3  
S7999C  
MID-LEVEL DISPLAY  
MB1  
MB2  
S7999C CONNECTED TO EACH SLAVE  
CAN ONLY CONFIGURE THAT SLAVE AS  
WELL AS MONITOR THAT SLAVE’S ACTIVITY.  
SOLA SLAVE 3  
2
4
3
Y
+
G
5
UP TO A MAXIMUM OF 8 SOLA SLAVES  
IN A LEAD LAG NETWORK.  
A
B
C
A
B
C
1
2
3
J3  
MB1  
MB2  
ECOM  
1
2
SOLA SLAVE 4  
5
M32007  
Fig. 12. S7999C wiring diagram for lead lag.  
11  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
The “COM” LED exists for I/O traffic.  
STARTING THE S7999C OI  
DISPLAY  
1. Make sure the LED is blinking.  
2. If the LED is not blinking:  
a. Make sure the proper connections have been made  
between the display and the Sola Control.  
proper wiring of the display connections.  
Power-up Validation  
The Home page will appear and the “Power” LED will be on  
continuously and the “COM” LED will be blinking when the  
device is properly powered and communicating to the Sola  
Control.  
HOME  
PAGE  
OPERATION  
DIAGNOSTICS  
CONFIGURE  
DETAILS  
HISTORY  
MODULATION  
SETPOINTS  
CONFIGURATION  
GROUPS  
HISTORY  
ALERTS  
CH  
DIAGNOSTIC  
TEST  
OK  
LOGIN  
LOGIN  
LOCKOUTS  
BURNER  
CONTROL  
PUMPS  
?
LOGOUT  
VERIFY  
DIAGNOSTIC  
ANALYSIS  
ALERTS  
DHW  
DIGITAL I/O  
ANALOG I/O  
SILENCE  
ANNUNCIATION  
DISPLAY  
SETUP  
PROGRAM  
MODULE  
KEY  
BUTTON FLOW  
CLEAN  
SCREEN  
BACK ICON FLOW  
HOME ICON ALWAYS  
TAKES YOU TO THE  
HOME PAGE  
SYSTEM  
CONFIGURATION  
ADVANCED  
SETUP  
M29774  
Fig. 13. S7999C display page flow.  
Status or Home Page  
PAGE NAVIGATION  
A status (summary) page (Fig. 14) is displayed when the  
S7999C display is connected. This status page appears on the  
S7999B when the Sola control icon is pressed on the “Home”  
page. The status page displays the current condition of the  
burner control and displays some of the more important  
configuration settings.  
The Sola OI Displays present information and options in a  
paged manner. Pages are displayed in a tree structure in which  
the user navigates up and down to arrive at the desired  
Function (see Fig. 8 for S7999B or Fig. 13 for S7999C). The  
page descriptions are provided below so that you can  
understand the purpose of each and view the selections,  
parameters, and information that is available or required on  
each.  
The boiler name associated with the burner control is  
displayed in the title on the status page.  
NOTE: When the burner control has no boiler name defined,  
Modbus address is used to identify the boiler.  
Common OI Display Page Symbols  
The initial status page displayed contains summary status  
information as shown in Fig. 14. Any status information not  
applicable for the installation is grayed/blanked out on the  
screen.  
Most pages have a Home button  
in the top-left corner of  
the screen and a Back button  
in the top-right corner of  
the screen. The Home button returns the user to the Home  
page and terminates any operation in progress. The Back  
button returns the user to the previous page.  
Buttons on this screen include:  
Configure: used to configure the burner control (see  
Operation: used to perform daily or frequent functions with  
the burner control, such as setpoint adjustment, etc. See  
Two other icons may be noticed near the boiler name.  
A bell  
will be displayed if the system is in Lockout that  
reset will be required.  
Diagnostic: used to view burner control diagnostic  
details).  
Details: used to view burner control detail status  
information (see “Details” on page 38).  
A padlock  
will be shown on screens that require a password  
to change the parameter. An unlocked padlock indicates the  
password has been entered to change the parameter.  
65-0303—05  
12  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
History: used to view burner control history (see “History  
?: used to expand the pump status information.  
Modulation: used to toggle between status displays: pump,  
setpoints, and modulation.  
Fig. 15. Configuration menu page. Shown is the S7999C on  
a Hydronic Control.  
No specific order for configuration is required. All parameters  
are enabled for editing, though some may not be applicable  
(e.g., a configuration parameter may disable a control feature).  
Selecting a parameter group from the menu displays  
parameters exclusively applicable for the functional group on  
the page (see Fig. 16). These parameters can be edited, and  
when the user is finished, control returns back to the  
configuration menu page.  
Fig. 14. Summary status page (Hydronic Control shown).  
Configure Button  
Pressing the Configure button (bottom left) on the Status page  
opens the Configuration page. The Configuration page shown  
in Fig. 15 is for the S7999C OI display.  
The S7999B Configuration page does not have a “Display  
Setup” button.  
Display Setup (S7999C only): Pressing the Display Setup  
button displays miscellaneous S7999C OI Display setup and  
diagnostic functions (See page 47 for options). (The same  
function as the 1234 Setup on the S7999B home page.)  
The configuration page allows the user to view and set  
parameters that define how the connected R7910A functions in  
the hydronic heating system or the R7911 steam heating  
system.  
The configuration page contains a menu of parameters  
grouped into functional areas that the user selects for  
configuration (see Fig. 16). See Table 61 on page 53 for all  
parameters available for configuration. If some parameters are  
not visible, they have been made invisible by Honeywell.  
Fig. 16. Sample configuration page for the S7999B  
Hydronic Control.  
Each parameter is displayed in its group. If there are more  
parameters than will fit on the screen, a vertical scroll bar  
allows the user to scroll up and down to view all parameters.  
The parameter name is displayed on the left and the current  
setting is displayed in the text box on the right.  
Configuration Password  
Some parameters require a valid configuration password be  
entered by the user before the parameter can be changed. The  
password need only be entered once while the user remains  
on the configuration pages. Leaving the configuration pages  
ends the scope of the password.  
13  
65-0303—05  
 
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Three levels of access to Sola Control parameters are  
permitted. Each access level has defined rights when  
interfacing with configuration and status parameters within the  
controls.  
The user is not required to enter a configuration password for a  
parameter that has a lower access level than the access level  
achieved by an earlier password entry for any configuration  
group (as long as the user stays in the configuration pages).  
The user only needs to enter a password once until a  
parameter that has a higher access level is selected.  
End user: The end user can read or view the control  
parameters and be allowed to change some operating  
parameters, CH setpoint as an example.  
Installer: The installer can read all control parameters and  
change Honeywell's allowed parameters. This access level  
is used to customize the control for a particular installation.  
OEM: The OEM can read and change all parameters,  
change sensor limits and burner control safety parameters.  
Keyboard  
Some pages request user entry of characters. When this type  
of input is required, a keyboard page appears, as shown in Fig.  
18. The text box at the top of the screen displays the current  
(or default) setting of the user input. The user can add to this  
text, clear it, or change it.  
Different passwords exist in the Sola Control for each access  
level. The end user level requires no password, but the  
installer and OEM levels have unique passwords defined for  
them.  
The Shift key on the left side of the screen shifts between  
upper and lowercase characters. Pressing the Shift key  
toggles the keyboard from one mode to the other (continuous  
pressing of the Shift button is not required). The OK button  
should be pressed when the user is done entering the text  
input. The Cancel button on the bottom of the screen allows  
the user to ignore any text changes that have been made and  
keep the original text value. Pressing the OK or Cancel buttons  
returns the user to the page displayed prior to the keyboard  
page.  
The installer and OEM passwords can be changed in the Sola  
Control after logging in with the current password. When the  
password is changed, it is saved for all future logins.  
NOTE: For the S7999B System OI display, each boiler in a  
multi-boiler configuration has its own set of installer  
and OEM passwords. To avoid user confusion, the  
passwords should be changed to the same password  
in each control, but there is no requirement to do so.  
Make sure to record your password.  
Login  
Pressing the Login button allows entering the password from a  
keyboard as shown in Fig. 18. After the password is entered,  
the OK button is selected. The Cancel button aborts the  
password login.  
The user is notified that a new password is needed to change a  
parameter (or until a password is entered successfully)—see  
Fig. 17. The user can continue viewing the configuration  
parameters regardless of whether a password is entered  
successfully.  
Fig. 18. Device login screen.  
Fig. 17. Login required. (S7999B Hydronic Control Shown.)  
WARNING  
Improper configuration can cause fuel buildup and  
explosion.  
Improper user operation may result in PROPERTY  
LOSS, PHYSICAL INJURY or DEATH.  
Explosion Hazard.  
The Sola Controls maintain a password time-out that limits the  
scope of the password entry. Once a password is successfully  
entered, the control starts an internal timer that expires after 10  
minutes of inactivity. After the timer expires, the user is  
required to re-enter a password before a parameter can be  
changed.  
Using the OI Displays to change parameters must be  
attempted by only experienced and/or licensed  
burner/boiler operators and mechanics.  
65-0303—05  
14  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Like operating parameters, safety parameters can be viewed  
without the need to enter a password.  
Change Parameter Settings  
Change parameter settings by selecting the parameter on the  
page. A dialog box displays for the parameter with controls  
allowing the user to change the value (see Fig. 19). After  
changing the setting to a new value, press the OK button.  
Pressing the Cancel button leaves the parameter unchanged.  
Safety parameter blocks that have been changed require  
verification. The verification steps do not have to be completed  
immediately; the installer can move between and change  
parameter groups before the verification is done. A Verify  
button is enabled that allows the installer to conduct verification  
sessions (the example of the Verify button in Fig. 15 is not yet  
enabled because the installer hasn’t logged in).  
The changed setting is reflected on the screen and sent to the  
control when the OK button is pressed.  
NOTE: When the installer proceeds with the safety parameter  
configuration, the control unlocks the safety parame-  
ters in this group and marks them unusable. Failure to  
complete the entire safety configuration procedure  
leaves the control in an un-runnable state (lockout 2).  
All safety configuration parameters in the group should have  
the same access level. If this condition isn’t so, the user is  
asked to enter another password when a higher access level is  
needed.  
Successful login is noted by the lock icon, which changes to  
“unlocked” on the page. The installer may begin to change  
safety parameters (or any other parameters) at that time. (See  
Fig. 21.) If the Sola Control is in an unconfigured (or new)  
state, then this warning doesn’t appear. All parameters that  
need changes should be changed during the login.  
Fig. 19. Change configuration parameter page example of  
a Hydronic Control.  
Verify  
Pressing the Verify button displays safety configuration  
parameters for an additional verification step to commit the  
changes.  
Safety parameters are grouped into blocks that include only  
safety parameters, not a mixture of safety data and non-safety  
data. All parameters within the safety group undergo a  
verification process. A safety parameter group is identified on  
the display to indicate when the configuration parameters are  
safety-related. Each safety parameter group is verified one at a  
time until all have been verified. See Fig. 20.  
Fig. 21. Edit safety data.  
If the safety configuration session is terminated after it has  
started (in the Edit or Verify stages), the Sola Control is left in  
an unconfigured (unrunnable) state.  
The installer can terminate the session by pressing the Menu  
button or by attempting to leave the Verification page with the  
Home or Back buttons (top-left and -right screen corners,  
respectively). However, leaving the session at this point leaves  
the control in an unrunnable state and confirms whether the  
installer still wants to do so.  
The settings of all parameters in each safety block must be  
verified to save them in the control.  
When the installer is done changing safety parameters,  
pressing the Verify button on the configuration screen begins  
the Verification process. The settings for all safety parameters  
in each changed block are presented and Verified by the  
installer (see Fig. 22).  
Fig. 20. Safety verification.  
15  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Safety lockouts are indicated on each configuration page as an  
alarm bell symbol. At the home (for S7999C) or status page  
(for S7999B), the History button turns red. If the S7999B is  
displaying the system status icons, the control in alarm will turn  
red.  
The lockout history can be displayed by pressing on the  
History button. The state information about each lockout is  
displayed along with the date/time that the lockout occurred  
(see Table 3). Current date/time stamp is a display setup  
feature.  
NOTE: In the event of a power interruption, the date/time  
must be reset. The OI Display does NOT have a  
backup means.  
Table 3. Sola Control Lockout History.  
Data  
Lockout time  
Comment  
Set by display  
Fig. 22. Safety parameter confirmation.  
Fault code  
Unique code defining which  
lockout occurred.  
Press the Yes button to confirm each safety parameter block. If  
the No button is selected, the safety parameter block remains  
unconfirmed and the Configuration menu page is displayed.  
The control remains in an unconfigured state in this case.  
Annunciator first out  
First interlock in limit string  
results in a shutdown.  
Description  
Fault description  
After all safety parameter blocks have been confirmed, the  
installer is asked to press and hold the Reset button on the  
Sola Control to complete the safety verification session (see  
Fig. 23).  
Burner Lockout/Hold  
Source/reason for lockout/  
hold  
Burner control state  
Sequence time  
Burner control state timer at  
time of fault  
Cycle  
Burner control cycle  
Burner control hours  
Run Hours  
I/O  
All digital I/O status at time of  
fault  
Annunciator 1-8 states  
Fault data  
All annunciator I/O status at  
time of fault  
Fault dependent data  
An alert log can be displayed for each control by pressing the  
Alert button on the bottom of the history status page. A  
description of the alert is displayed along with the time when  
the alert occurred (see Table 4).  
Table 4. Sola Control Alert Log.  
Data  
Comment  
Set by display  
Fig. 23. Safety parameter reset.  
Alert time  
Alert code  
Unique code defining which  
fault occurred.  
When the Reset button is pressed and held for 3 seconds the  
confirmed safety parameters are saved in the control. The  
above Reset dialog box automatically closes when this step is  
completed.  
Description  
Alert description  
If this step is not performed, the control remains in a safety  
lockout state until the installer resolves the unverified safety  
parameters.  
History Button  
The History button on the Home page serves not only as a  
button, but also displays Sola Control lockouts, holds, and  
alerts as they occur. The History button can be selected at any  
time, regardless of which type of information is displayed, to  
view history information. Pressing the History button displays a  
dialog box (see Fig. 24) that allows the user to select the type  
Fault/Alarm Handling  
Each Sola Control reports to the OI display when a safety  
lockout or an Alert occurs.  
65-0303—05  
16  
   
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
of history to view. The user can also silence an audible alarm  
generated by the control during a lockout or alert by alarm  
condition.  
The date and time that each fault occurred is displayed in the  
lockout history. The lockout timestamp displays in both the  
lockout summary and detail information.  
This History dialog box provides an exploded view of the status  
information displayed in the History button (the font is larger).  
One of the four buttons (OK, Lockouts, Alerts, or Silence) can  
be selected. If none of these buttons are selected the dialog  
box closes after 30 seconds.  
The Sola Control does not maintain date or time of day  
information. The date and time stamp is assigned by the OI  
display. When the OI display first obtains the lockout and alert  
history from the control (during the display data  
synchronization), no timestamps are assigned since the times  
that the lockouts occurred are unknown. All new lockouts that  
occur after the synchronization are assigned timestamps.  
NOTE: The system time can be set in the OI display to  
ensure that correct timestamps are given to the con-  
trols’ lockouts and alerts. Power interruptions will  
require the time to be reset as the display DOES NOT  
have a time backup means.  
The Clear Lockout button allows the user to acknowledge and  
clear (reset) the lockout when in lockout state, much the same  
as pressing the reset button on the front of the Sola Control.  
The user can toggle between displaying the controls’ lockout  
history and alert log by pressing the Alerts or Lockouts button  
on the bottom of the pages.  
Fig. 24. Hydronic history example shown—exploded view.  
Two types of historical data can be displayed on the history  
page: lockout history and alert log.  
The entire 15 fault code history is displayed in a scrollable list  
with the most recent fault displayed first followed by the next  
most recent fault. Summary information is displayed for each  
fault entry, including the burner cycle count, fault code, and  
fault number with description. Detailed information for a  
specific fault entry that also includes burner control sequence  
state, burner run-time hours, annunciation status, etc., is  
viewed by selecting (touching the History line) the lockout entry  
in the list (see “Fault/Alarm Handling” on page 16 for details).  
Fig. 26. Alert log example shown.  
To see additional detail about a lockout or alert, touching on the  
lockout or alert in the list expands the view of that lockout or  
alert, as shown in Fig. 27 and 28.  
Fig. 25. Lockout history example shown.  
17  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Fig. 27. Control expanded lockout detail.  
Fig. 29. Hydronic operation page shown.  
Fig. 28. Control expanded alert detail.  
Fig. 30. Programmable annunciation.  
Operation Button  
The operation button displays the SOLA Control running  
operation, including setpoint and firing rate values. From this  
page the user can change setpoints, manually control the  
boiler’s firing rate, manually turn pumps on, view annunciation  
information, and switch between hydronic heating loops  
(Central Heat and Domestic Hot Water), as shown in Fig. 22. If  
a password is required to change any of the settings on this  
page, the user can press the Login button to enter the  
password.  
Annunciation information is shown in Fig. 23 and Fig 24.  
Fig. 31. Fixed annunciation.  
65-0303—05  
18  
 
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Diagnostics Button  
System Configuration  
The Diagnostics button displays analog and digital I/O status of  
the SOLA Control. A snapshot of the diagnostic status is  
displayed and updated once per second as it changes in the  
more information about this status.  
(S7999B OI DisplayOnly)  
The OI Display has some functions related to general  
configuration for the control in the end user installation.  
Pressing the Display Refresh button invokes a search  
procedure (see Fig. 34). A new R7910A Hydronic Control or  
R7911 Steam Control is identified by “Unknown” status next to  
its name in the boiler system list (see Fig. 35). “Unknown”  
indicates that configuration data has not been retrieved from  
the control yet.  
The digital I/O data is displayed as LEDs that are either on  
(green) or off (red) (See Fig. 23). Not all digital I/O can be  
displayed at the same time on the page, so a horizontal scroll  
bar is used to move the view left and right to show all digital  
I/O data.  
Fig. 34. System refresh.  
Fig. 32. Diagnostic page (digital I/O).  
The control analog I/O can also be viewed on the OI Display. A  
snapshot of the diagnostic status is displayed and updated as  
it changes in the control.  
The analog I/O data is displayed as bar charts with I/O level  
represented in the I/O range (see Figure 24.) Analog I/O that is  
not enabled for the installation displays a blank I/O level. Not  
all analog I/O can be displayed at the same time on the page,  
so a horizontal scroll bar is used to move the view left and right  
to show all analog I/O status.  
Fig. 35. System configuration page.  
The control connected to the Modbus network is indicated to  
the user after the search procedure has concluded.  
Once the control is located it must be synchronized with the OI  
Display before it can be displayed. New controls are not  
displayed on the Home page until this synchronization (see  
below) is performed.  
System Synchronization  
(S7999B OI Display Only)  
Fig. 33. Diagnostics page (analog I/O).  
The user can manually synchronize configuration data from the  
connected controls at any time.  
19  
65-0303—05  
   
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
A new control is visible when configuration and status data is  
gathered from it. This collection procedure takes a few  
minutes. The control is marked as “Unknown” when no  
configuration information exists. Normally, control configuration  
data collection only needs to be performed when the control is  
initially installed. However, a re synchronization is necessary  
after the OI Display is reset. See Fig. 36.  
Table 5. Functional Configuration Groups.  
Hydronic Control  
T-Rise Limit  
Steam Control  
Heat Exchanger High Limit  
Anti-condensation  
Burner Control Flame Failure  
System Configuration  
Frost Protection  
Configuration  
The user presses the Synchronize button to begin  
synchronization with the control. See Fig. 36.  
Annunciation Configuration Fan Configuration  
Burner Control Interlocks  
Lead Lag Configuration  
Burner Control Timings and  
Rates  
Burner Control Ignition  
Burner Control Flame Failure  
System Configuration  
Fan Configuration  
Sensor Configuration  
Lead Lag Slave  
Configuration  
Lead Lag Master  
Configuration  
Most of this configuration is performed by either the contractor/  
installer or at Honeywell. Each functional group is displayed on  
the Configuration menu page.  
Fig. 36. System synchronization.  
Parameters in functional groups that are not applicable for the  
installation can be ignored. In some cases, features in a  
functional group are disabled by default and are enabled when  
needed for the installation.  
Status of the synchronization is reflected in the dialog box. The  
synchronization can be aborted by selecting the Cancel button.  
Configuration  
R7910A HYDRONIC CONTROL,  
R7911 STEAM CONTROL  
CONFIGURATION  
The SOLA Control can be configured from the OI Display. The  
control configuration is grouped into the functional groups seen  
in Table 5.  
Table 5. Functional Configuration Groups.  
PARAMETERS  
Hydronic Control  
Steam Control  
The following pages list the configuration parameters available  
for the R7910A or R7911 installed.  
System Identification and  
Access  
Steam Identification and  
Access  
NOTE: Individual Configuration pages may differ from this  
text as features are added or amended by Honeywell.  
CH - Central Heat  
Outdoor Reset  
Steam Configuration  
Modulation Configuration  
A password is required to make changes to the Configuration  
Parameters. The SOLA Control will be in a Lockout 2 “waiting  
for safety data verification” as received or will go to a Lockout 2  
when changes are made to the safety data.  
DHW - Domestic Hot Water Pump Configuration  
DHW Storage  
DHW Plate  
Warm Weather Shutdown  
Demand Priority  
WARNING  
Improper configuration can cause fuel buildup and  
Modulation Configuration  
Pump Configuration  
Statistics Configuration  
High Limit  
Statistics Configuration  
Stack Limit  
Explosion Hazard.  
explosion.  
Annunciation Configuration  
Burner Control Interlocks  
Improper user operation may result in PROPERTY  
LOSS, PHYSICAL INJURY or DEATH.  
Stack Limit  
Burner control Timings and  
Rates  
The OI Display used to change parameters, must be  
attempted by only experienced and/or licensed  
burner/boiler operators and mechanics.  
Delta T Limits  
65-0303—05  
20  
 
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Central Heat Parameters  
(R7910A Hydronic Control Only)  
Table 8 displays Central Heat Hydronic Control configuration  
parameters.  
Fig. 37. System identification and access configuration.  
(Hydronic Screen Shown.)  
Table 6 displays System Identification and Access parameters.  
Fig. 38. Central Heat hydronic configuration.  
Table 6. System Identification and Access Parameters.  
Parameter  
Boiler Name  
Comment  
Table 8. Central Heat Hydronic  
Configuration Parameters.  
Name to identify boiler (up to 20  
characters)  
Installation  
Notes regarding installation (up to 20  
characters)  
Parameter  
CH enable  
Comment  
Disable or Enable Central Heating  
Loop  
Installer password  
OEM password  
Factory Data  
Change installer password setting  
Change OEM password setting  
Demand switch  
Sensor for Central Heat demand:  
Sensor only  
Sensor & STAT terminal  
Sensor & Remote Stat  
LCI & Sensor  
OEM name to associate with boiler  
(up to 20 characters)  
When the burner name is changed, the name is saved in the  
R7910A or R7911 and displayed in the title of all pages that  
zoom into the control.  
Outdoor reset  
Enabled  
Disabled  
Default parameter settings for installer and Honeywell  
passwords are “sola” and “solaoem,” respectively. These  
passwords most likely have been changed by Honeywell.  
CH has priority over Yes, No, Cancel  
Lead Lag  
Setpoint source  
Local  
Factory Data gives Honeywell an option to display a brand  
name other than Sola on this configuration page. Additional  
information displayed on this page is listed in Table 7.  
S2 (J8-6) 4-20mA  
Setpoint  
Setpoint for normal Central Heat  
modulation:  
-40 °F to 266 °F (-40 °C to 130 °C)  
Time of day setpoint Setpoint when Time Of Day switch is  
on. -40 °F to 266 °F (-40 °C to 130 °C)  
Table 7. System Identification Information.  
Status  
Product Type  
OS Number  
Comment  
Off hysteresis  
Differential above setpoint when boiler  
is turned off.  
32 °F to 266 °F (0 °C to 130 °C)  
Type of product that the burner is  
Model number associated with burner  
On hysteresis  
Differential from setpoint when boiler  
is turned on. 32 °F to 266 °F (0 °C to  
130 °C)  
Software Version  
Version of software running in the  
R7910A or R7911  
Date Code  
Date when R7910A or R7911 was  
assembled  
4 mA water  
temperature  
-40 °F to 266 °F (-40 °C to 130 °C)  
-40 °F to 266 °F (-40 °C to 130 °C)  
Outlet sensor, Inlet sensor, S5 (J8-11)  
Application Revision Version of application data in the  
R7910A or R7911  
20 mA water  
temperature  
Safety Revision  
Revision of safety data in the R7910A  
or R7911  
Modulation sensor  
21  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 8. Central Heat Hydronic  
Table 9. Steam Configuration Parameters  
Configuration Parameters. (Continued)  
Parameter  
Comment  
Parameter  
Comment  
Steam pressure on Differential from setpoint when boiler  
Modulation Rate  
Sensor  
Local  
hysteresis  
is turned on.  
Adjustable 0 to 15 or 0 to 150 (sensor  
dependant)  
P-gain  
Gain applied for the P portion of the  
PID equation  
0-400  
Steam hysteresis  
step time  
Time between hysteresis changes 0 to  
600 seconds (0=disable)  
I-gain  
Gain applied for the I portion of the  
PID equation  
0-400  
Steam P Gain  
Gain applied for the P portion of the  
PID equation  
0-400  
D-gain  
Gain applied for the D portion of the  
PID equation  
0-400  
Steam I Gain  
Steam D Gain  
Gain applied for the I portion of the PID  
Equation - 0-400  
Gain applied for the D portion of the  
Hysteresis step time Time between hysteresis step  
changes: 0-600 seconds (0=Disable  
hysteresis stepping)  
PID equation  
0-400  
Steam 4-20 ma  
remote control  
uses 4-20ma remote control function to  
control either the setpoint or  
modulation for Steam  
Disable, setpoint, modulation  
Outdoor Reset Parameters  
(R7910A Hydronic Control Only)  
Table 10 displays Outdoor Reset configuration parameters.  
Pressing the left or right arrow displays Lead Lag, which lists  
the same parameters.  
Fig. 39. R7911 Steam Configuration.  
Table 9. Steam Configuration Parameters  
Parameter  
Comment  
Steam enable  
Disable/enable steam feature  
Steam demand  
source  
Sensor and LCI  
Sensor and Remote Stat  
Sensor and Stat Terminal  
Sensor Only  
Fig. 40. Outdoor reset configuration.  
Steam pressure  
setpoint  
Setpoint for normal modulation  
Adjustable 0 to 15 or 0 to 150 (sensor  
dependant)  
Table 10. Outdoor Reset Configuration Parameters.  
Parameter  
Comment  
Steam time of day  
setpoint  
Setpoint when TOD switch on  
Adjustable 0 to 15 or 0 to 150 (sensor  
dependant)  
Maximum outdoor  
temperature  
-40 °F to 266 °F (-40 °C to 130 °C)  
Minimum steam  
pressure  
Establishes setpoint for the 4ma. input.  
Adjustable 0 to 15 or 0 to 150 (sensor  
dependant)  
Minimum outdoor  
temperature  
-40 °F to 266 °F (-40 °C to 130 °C)  
-40 °F to 266 °F (-40 °C to 130 °C)  
-40 °F to 266 °F (-40 °C to 130 °C)  
-40 °F to 266 °F (-40 °C to 130 °C)  
Low water  
temperature  
Steam pressure off Differential below setpoint when boiler  
hysteresis  
is turned off  
Adjustable 0 to 15 or 0 to 150 (sensor  
dependant)  
Minimum water  
temperature  
Maximum off point  
65-0303—05  
22  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 11. Domestic Hot Water (DHW)  
Configuration Parameters. (Continued)  
Domestic Hot Water (DHW)  
Configuration Parameters  
(R7910A Hydronic Control Only)  
Parameter  
Comment  
Hysteresis step  
time  
___hour ___min ___sec  
Table 11 displays Domestic Hot Water (DHW) configuration  
parameters.  
DHW priority vs CH Which system has priority:  
Central Heat over Domestic Hot  
Water, or  
Domestic Hot Water over Central Heat  
DHW priority vs  
Lead Lag  
Which system has priority:  
Lead Lag over Domestic Hot Water,  
Domestic Hot Water over Lead Lag  
DHW P-gain  
DHW I-gain  
DHW D-gain  
Gain applied for the P portion of the  
PID equation  
0-400  
Gain applied for the I portion of the  
PID equation  
0-400  
Gain applied for the D portion of the  
PID equation  
0-400  
DHW Storage Configuration  
Table 12 displays DHW Storage configuration parameters.  
Fig. 41. Domestic Hot Water (DHW) configuration.  
Table 12. DHW Storage Configuration Parameters.  
Table 11. Domestic Hot Water (DHW)  
Configuration Parameters.  
Parameter  
Comment  
Enabled, Disabled  
Parameter  
Enable  
Comment  
DHW storage  
enable  
Disable or Enable Domestic Hot  
Water Loop  
Storage time  
Setpoint  
___hour ___min ___sec  
Demand switch  
Sensor for Central Heat demand:  
DHW sensor only,  
-40 °F to 266 °F (-40 °C to 130 °C)  
-0 °F to 180 °F (-17 °C to 82 °C)  
-0 °F to 180 °F (-17 °C to 82 °C)  
Off hysteresis  
On hysteresis  
DHW sensor & Remote Stat,  
DHW switch & inlet sensor, or  
DHW switch & outlet sensor  
Priority source  
Priority method  
Which system has priority:  
Disabled or  
Heat Demand  
DHW Plate Heat Exchanger  
Configuration  
Table 13 displays DHW Plate Heat Exchanger configuration  
parameters.  
Boost during priority time  
Drop after priority time  
Modulation sensor DHW Sensor  
Outlet Sensor  
Table 13. DHW Plate Heat Exchanger  
Configuration Parameters.  
Inlet Sensor  
Auto: DHW (S6) or Inlet Sensor  
Auto: DHW (S6) or Outlet Sensor  
Parameter  
Comment  
Setpoint  
-40 °F to 240 °F (-40 °C to 115 °C)  
Tap detect degrees -0 °F to 180 °F (-17 °C to 82 °C)  
Time of day setpoint Setpoint when Time Of Day switch is  
on. -40 °F to 240 °F (-40 °C to 115 °C)  
Tap detect on  
recognition time  
___hour ___min ___sec  
Off hysteresis  
Differential above setpoint when boiler  
is turned off. -40 °F to 240 °F (-40 °C  
to 115 °C)  
Tap detect on  
threshold  
-0 °F to 180 °F (-17 °C to 82 °C)  
Tap detect minimum ___hour ___min ___sec  
on time  
On hysteresis  
Differential from setpoint when boiler  
is turned on.  
2 °F to 234 °F (-16 °C to 112 °C)  
Tap stop inlet-DHW -0 °F to 180 °F (-17 °C to 82 °C)  
degrees  
DHW priority  
override time  
___hour ___min ___sec  
Tap stop outlet-Inlet -0 °F to 180 °F (-17 °C to 82 °C)  
degrees  
23  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 13. DHW Plate Heat Exchanger  
Configuration Parameters. (Continued)  
Table 14. Warm Weather Setpoint  
Configuration Parameters.  
Parameter  
Comment  
Parameter  
Comment  
Enabled, disabled  
-40 °F to 266 °F (-40 °C to 130 °C)  
Plate preheat  
setpoint  
-40 °F to 266 °F (-40 °C to 130 °C)  
Enable  
Plate preheat on  
recognition time  
___hour ___min ___sec  
Setpoint  
Plate preheat on  
hysteresis  
-0 °F to 180 °F (-17 °C to 82 °C)  
-0 °F to 180 °F (-17 °C to 82 °C)  
Demand Priority Configuration  
Parameters  
Plate preheat off  
hysteresis  
Fig. 42 displays R7910A Hydronic Control Demand Priority  
configuration options. Press the arrows to change the priority  
order.  
Plate preheat detect -0 °F to 180 °F (-17 °C to 82 °C)  
on threshold  
Plate preheat detect -0 °F to 180 °F (-17 °C to 82 °C)  
off threshold  
Plate preheat  
___hour ___min ___sec  
minimum on time  
Plate preheat delay ___hour ___min ___sec  
after tap  
Warm Weather Shutdown  
Configuration  
Table 14 displays Warm Weather Setpoint configuration  
parameters.  
Fig. 42. Demand priority configuration.  
65-0303—05  
24  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Modulation Configuration  
Parameters  
Steam Modulation Configuration  
Parameters  
Table 15 displays R7910A Hydronic Control Modulation  
configuration parameters.  
Table 16 displays R7911 Steam Modulation Configuration  
parameters.  
Fig. 43. Modulation configuration.  
Fig. 44. Steam modulation configuration.  
Table 15. R7910A Hydronic Control Modulation Configura-  
tion Parameters.  
Table 16. R7911 Steam Modulation Configuration  
Parameters.  
Parameter  
Comment  
Parameter  
Comment  
CH maximum  
modulation rate  
RPM or %  
RPM or %  
CH maximum  
modulation rate  
RPM or %  
DHW maximum  
modulation rate  
Minimum modulation RPM or %  
rate  
Minimum modulation RPM or %  
rate  
CH forced rate time 0-600 seconds  
CH forced rate  
RPM or %  
CH forced rate time 0-600 seconds  
CH forced rate RPM or %  
DHW forced rate time 0-600 seconds  
DHW forced rate RPM or %  
0-10/4-20 mA Output  
hysteresis  
CH slow start enable Enabled  
Disabled  
DHW slow start  
enable  
Enabled  
Disabled  
Slow start degrees  
Slow start ramp  
-40 °F to 266 °F (-40 °C to 130 °C)  
RPM /minute or %/minute  
0-10/4-20 mA Output  
hysteresis  
25  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
NOTE: The R7911 Steam Control does not have pumps, but  
the outputs are available to operate air dampers or  
accessories. CH Pump, Boiler Pump and System  
Pump are used for these output options.  
Pump Configuration Parameters  
Table 17 displays Pump configuration parameters. Use the left  
and right arrows to switch between Central Heat, Boiler, DHW,  
System, Auxiliary 1, and Auxiliary 2 pumps. The parameters  
are the same for all pumps.  
Table 17a. Pump Configuration Parameters for R7911  
Steam Modulation Configuration Parameters.  
Pressing the Advanced Settings button brings up a number of  
other advanced configuration options for each pump. Press the  
Control Settings button to return to the screen shown in Fig.  
45.  
Parameter  
Comment  
Auxiliary pump control  
Auto  
On  
Auxiliary pump is on when  
Auxiliary pump output  
CH pump is ON  
Slave command  
Pump A  
Pump B  
Pump C  
None  
Boiler pump control  
Boiler pump output  
Auto  
On  
Pump A  
Pump B  
Pump C  
None  
Boiler pump overrun time  
CH pump control  
0-600 seconds  
0 = Not configured  
Auto  
On  
Fig. 45. Pump configuration.  
CH pump output  
Pump A  
Pump B  
Pump C  
None  
Table 17. Pump Configuration Parameters for  
R7910A Hydronic System.  
CH pump overrun time  
System pump control  
System pump output  
0-600 seconds  
0 = Not configured  
Parameter  
Pump control  
Comment  
Auto  
On  
Auto  
On  
Pump output  
Pump A  
Pump B  
Pump C  
None  
Pump A  
Pump B  
Pump C  
None  
Pump start delay  
Overrun time  
___hour ___min ___sec  
___hour ___min ___sec  
System pump ourrun time  
Pump exercise time  
0-600 seconds  
0 = Not configured  
*Table 61 on page 53 has more parameters listed.  
0-600 seconds  
0= Not configured  
65-0303—05  
26  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Statistics Configuration Parameters  
High Limit Configuration Parameters  
Table 15 displays Statistics configuration parameters.  
(R7910A Hydronic Control Only)  
Table 19 displays outlet high limit configuration parameters.  
Fig. 46. Statistics configuration.  
Fig. 47. High Limits configuration.  
Table 18. Statistics Configuration Parameters.  
Parameter  
Comment  
Table 19. High Limit Configuration Parameters.  
Auxiliary pump cycles 0-999,999  
Parameter  
Comment  
Boiler pump cycles  
Burner cycles  
0-999,999  
0-999,999  
0-999,999  
0-999,999  
0-999,999  
DHW high limit  
Enabled  
Disabled  
Burner run time  
CH pump cycles  
DHW pump cycles  
DHW high limit  
response  
Recycle & hold  
Lockout  
DWH high limit  
setpoint  
-40 °F to 266 °F (-40 °C to 130 °C)  
System pump cycles 0-999,999  
Auxiliary 2 pump  
cycles  
0-999,999  
Outlet high limit  
Enabled  
Disabled  
Outlet high limit  
response  
Recycle & hold  
Lockout  
Outlet high limit  
setpoint  
-40 °F to 266 °F (-40 °C to 130 °C)  
27  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Stack Limit Configuration Parameters Delta T Limit Configuration  
Table 20 displays stack limit configuration parameters.  
Parameters  
(R7910A Hydronic Control Only)  
Table 21 displays other limit parameters. Use the left and right  
arrows to switch between Inlet to Outlet Flow and Exchanger to  
Outlet Flow. The parameters are the same for all pumps.  
Fig. 48. Stack Limit configuration.  
Table 20. Stack Limit Configuration Parameters.  
Parameter  
Stack limit  
Comment  
Fig. 49. Delta T Limit configuration.  
Enabled dual sensor safety  
Enabled single sensor non safety  
Disabled  
Table 21. Delta T Limit  
Configuration Parameters.  
Stack limit delay  
___hour ___min ___sec  
Stack limit response Lockout  
Recycle & delay  
Parameter  
Comment  
Delta T enable  
Enabled  
Disabled  
Stack limit setpoint  
32 °F to 266 °F (0 °C to 130 °C)  
Delta T degrees  
Delta T delay  
0 °F to 234 °F (-17 °C to 112 °C)  
___hour ___min ___sec  
Delta T response  
Recycle & delay  
Recycle & Delay with retry limit  
Lockout  
Delta T retry limit  
0–100  
Delta T rate limit  
enable  
Enabled  
Disabled  
Delta T inverse limit ___hour ___min ___sec  
time  
Delta T inverse limit Recycle & delay  
response  
Recycle & delay with retry limit  
Lockout  
65-0303—05  
28  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
T-Rise Limit Configuration  
Anti-Condensation Configuration  
Parameters (R7910A Hydronic  
Parameters  
Table 22 displays T-Rise limit parameters.  
Control Only  
)
Table 24 displays anti-condensation parameters. Use the left  
and right arrows to switch between Central Heat, Domestic Hot  
Water, Frost Protection, and Priority parameters.  
Table 22. T-Rise Limit Configuration Parameters.  
Parameter  
Comment  
Outlet T-rise enable Enabled  
Disabled  
Heat exchanger T-  
rise enable  
Enabled  
Disabled  
T-rise degrees  
T-rise response  
0 °F to 234 °F (-17 °C to 112 °C)/sec  
Recycle & delay  
Recycle & delay with retry limit  
Lockout  
T-rise retry limit  
T-rise delay  
0 to 100  
___hour ___min ___sec  
Heat Exchanger High Limit  
Configuration Parameters  
Table 23 displays T-Rise limit parameters.  
Fig. 50. Anti-condensation configuration.  
Table 23. Heat Exchanger High Limit  
Configuration Parameters.  
Table 24. Anti-Condensation Configuration Parameters.  
Parameter  
Comment  
Heat exchanger high Enabled  
Parameter  
CH Enable  
Comment  
limit enable  
Disabled  
Enabled  
Disabled  
Heat exchanger high -40 °F to 266 °F (-40 °C to 130 °C)  
limit setpoint  
CH Setpoint  
DHW Enable  
-40 °F to 266 °F (-40 °C to 130 °C)  
Heat exchanger high Recycle & delay  
Enabled  
Disabled  
limit response  
Recycle & delay with retry limit  
Lockout  
DHW Setpoint  
-40 °F to 266 °F (-40 °C to 130 °C)  
Heat exchanger retry 0 to 100  
limit  
Frost Protection  
Enable  
Enabled  
Disabled  
Heat exchanger high ___hour ___min ___sec  
limit delay  
Anticondensation  
Priority  
Anticondensation is more important  
than (check those that apply):  
Stack limit  
Delta T limit  
Slow start  
Forced rate  
Outlet high limit  
29  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Frost Protection Parameters  
Annunciation Configuration  
(R7910A Hydronic Control Only)  
Parameters  
Table 25 displays frost protection parameters.  
Table 26 displays annunciation configuration parameters.  
Fig. 51. Frost Protection configuration.  
Fig. 52. Annunciation configuration example.  
Table 25. Frost Protection Configuration Parameters.  
Table 26. Annunciation Configuration Parameters.  
Parameter  
Comment  
Parameter  
Comment  
CH frost protection  
enable  
Enabled  
Disabled  
Annunciation enable Enabled  
Disabled  
DHW frost protection Enabled  
Annunciator (1–8)  
location  
01 - Annunciator 1  
02 - Annunciator 2  
enable  
Disabled  
03 - Annunciator 3  
04 - Annunciator 4  
05 - Annunciator 5  
06 - Annunciator 6  
07 - Annunciator 7  
08 - Annunciator 8  
PII - Pre-Ignition ILK  
LCI - Load Control Input  
ILK - Interlock  
Lead Lag frost  
protection enable  
Enabled  
Disabled  
Outdoor frost  
protection setpoint  
-40 °F to 266 °F (-40 °C to 130 °C)  
(applicable for CH only)  
Lead Lag frost  
protection rate  
___%  
CH pump frost  
overrun time  
___hour ___min ___sec  
___hour ___min ___sec  
Annunciator (1–8)  
short name  
Up to 3 characters  
DHW pump frost  
overrun time  
Annunciator (1–8)  
name  
Up to 20 characters  
Safety Configuration Parameters  
Table 27 through 30 display safety parameters.  
NOTE: Login is required to change Safety Parameters and  
the SOLA Control will go to a Lockout 2 “waiting for  
safety data verification” when a change is made.  
65-0303—05  
30  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Fig. 53. Burner Control Interlocks control.  
Fig. 54. Burner Control Timings and Rates configuration.  
Table 27. Burner Control  
Interlocks Configuration.  
Table 28. Burner Control Timings and Rates Configura-  
tion.  
Parameter  
Comment  
Parameter  
Prepurge rate  
Prepurge time  
Comment  
PII enable  
Enabled  
Disabled  
RPM or %  
___hour ___min ___sec  
LCI enable  
Enabled  
Disabled  
Run stabilization time ___hour ___min ___sec  
Standby Rate  
Postpurge rate  
Postpurge time  
RPM or %  
Interrupted air switch Enable during purge and ignition  
(IAS) enable  
RPM or %  
Disabled  
Enable during purge  
___hour ___min ___sec  
___day ___hour ___min  
Interlock (ILK) start  
check enable  
No ILK check  
ILK check  
Forced recycle  
interval time  
ILK/IAS open  
response  
Recycle  
Lockout  
ILK bounce detection Enabled  
enable  
Disabled  
Purge rate proving  
Fan Speed  
High Fire Switch  
None  
Lightoff rate proving Fan Speed  
Low Fire Switch  
None  
Fig. 55. Burner Control Ignition configuration.  
31  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 30. Burner Control Flame  
Failure Configuration. (Continued)  
Table 29. Burner Control Ignition Configuration.  
Ignite failure retries  
1, 3, or 5  
Parameter  
Pilot test hold  
Comment  
MFEP flame failure  
response  
Recycle  
Lockout  
On  
Off  
Run flame failure  
response  
Recycle  
Lockout  
Ignition source  
Pilot type  
Hot Surface Igniter  
External ignition  
Internal ignition  
Fan speed error  
response  
Recycle  
Lockout  
Direct burner constant ignition  
Direct burner pulsed ignition  
Intermittent  
Safety Parameter Verification  
Interrupted  
When any of the safety configuration parameters are changed,  
the safety parameter verification procedure must be performed  
before the control will resume burner control. The control  
enters a lockout state, if not already in one, and remains locked  
out until this verification procedure is performed.  
Lightoff rate  
Preignition time  
Pilot Flame  
Establishing Period 10 secs  
4 secs  
RPM or %  
___hour ___min ___sec  
15 secs  
Safety parameter verification lockout occurs when safety  
parameter setting is changed. See Fig. 57.  
Igniter on during  
1st half of PFEP  
Pilot Flame Establishing Period  
Main Flame  
15 secs  
Establishing Period 10 secs  
5 secs  
Flame Threshold  
μA/V  
Fig. 57. Safety verification lockout.  
The user must log in before verification can be completed, as  
shown in Fig. 58.  
Fig. 56. Burner Control Flame Failure configuration.  
Table 30. Burner Control Flame  
Failure Configuration.  
Parameter  
Ignite failure  
response  
Comment  
Lockout  
Recycle  
Recycle & hold  
Recycle & lockout  
Ignite failure delay  
___hour ___min ___sec  
Fig. 58. Safety verification login.  
65-0303—05  
32  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
After successful login, the user presses the Begin button to  
start safety parameter verification. See Fig. 59.  
After the first safety parameter group has been confirmed by  
the user (by pressing the Yes button), the next safety  
parameter group waits for verification as shown in Fig. 61.  
Fig. 59. Begin safety verification.  
Fig. 61. Safety parameter settings confirmed; next group  
waiting for confirmation.  
The first group of safety configuration parameters that needs  
verification is displayed. The user is asked to confirm that the  
settings are correct, as shown in Fig. 60.  
The user has 30 secs to confirm each safety configuration  
group’s settings. If the user takes too long to confirm the  
settings, an error message is displayed, as shown in Fig. 62.  
Fig. 60. Confirm safety parameter settings.  
Fig. 62. Confirmation timed out.  
After all safety parameter groups have been verified, the user  
must press the Reset button on the control within 30 seconds  
to confirm the correct device. See Fig. 63.  
33  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
If for some reason the user does not press the Reset button on  
the control within 30 seconds, the configuration is cancelled,  
as shown in Fig. 65.  
Fig. 63. Reset R7910A or R7911.  
When the user has pressed the Reset button on the control,  
completing verification procedure, a Verification Complete  
screen is displayed, as shown in as shown in Fig. 64.  
Fig. 65. Control reset timed out.  
Fig. 64. Safety parameter configuration complete.  
65-0303—05  
34  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 32. R7911 System  
Configuration Parameters. (Continued)  
Individual R7910A or R7911  
Configuration Parameters  
Parameter  
Anti short cycle time  
Alarm silence time  
Power up with lockout  
Comment  
___hour ___min ___sec  
___day ___hour ___min  
Table 31 and Table 32 displays system configuration  
parameters for individual controls.  
Clear lockout  
Do NOT clear lockout  
Inlet connector type  
Stack connector type  
0-15 psi  
0-150 psi  
UNCONFIGURED  
10k NTC dual safety  
10k NTC single non-safety  
12k NTC single non-safety  
UNCONFIGURED  
Header  
4-20ma  
UNCONFIGURED  
Fan Parameters  
Table 33 displays fan parameters.  
Fig. 66. System configuration (R7911 shown).  
Table 31. R7910AHydronic  
System Configuration Parameters.  
Parameter  
Comment  
Flame sensor type  
Flame rod  
UV power tube  
UV power tube with spark interference  
None  
Modulation output  
4-20mA  
0-10V  
Fan PWM  
Blower/HSI  
Blower  
Hot surface ignition  
Temperature units  
Fahrenheit  
Celsius  
Fig. 67. Fan configuration.  
Anti short-cycle time ___hour ___min ___sec  
Alarm silence time  
___hour ___min ___sec  
Table 33. Fan Configuration Parameters.  
Parameter Comment  
500–12000 RPM  
Power up with  
Lockout  
Clear lockout  
Do NOT clear lockout  
STAT & EnviraCOM Enabled  
remote stat  
Absolute maximum  
fan speed  
Disabled  
Absolute minimum  
fan speed  
500–12000 RPM  
Table 32. R7911 System  
Configuration Parameters.  
Fan gain down  
Fan gain up  
0-100  
0-100  
Parameter  
Comment  
Minimum duty cycle 1-100%  
Pulses per revolution 1-10  
Flame sensor type  
Flame rod  
UV  
Modulation output  
4-20ma  
0-10V  
Fan PWM  
PWM frequency  
1000  
2000  
3000  
4000  
Blower/HSI  
Blower  
Hot surface ignitor  
Slow down ramp  
Speed up ramp  
0-12000 RPM/sec  
0-12000 RPM/sec  
Temperature units  
Fahrenheit  
Celsius  
35  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Use the left and right arrows to switch between Modulation,  
CH, DHW, Frost Protection, Warm Weather Shutdown,  
Algorithms, Rate Allocation, Add stage and Drop stage  
parameters.  
Lead Lag Slave Configuration  
Parameters (Hydronic Control Only)  
Table 34 displays Lead Lag Slave Configuration parameters.  
Fig. 69. Lead Lag master configuration and Advanced  
Settings button.  
Fig. 68. Lead Lag slave configuration.  
Table 34. Lead Lag Slave  
Configuration Parameters.  
Table 35. Lead Lag Master Configuration Parameters.  
Parameter  
Comment  
Parameter  
Slave enable  
Comment  
Master enable  
Enabled  
Disabled  
Slave  
ModBUS slave  
Disabled  
CH setpoint  
-40 °F to 266 °F (-40 °C to 130 °C)  
-40 °F to 266 °F (-40 °C to 130 °C)  
Slave mode  
Use first  
Use last  
CH time of day  
setpoint  
Equalize run time  
ModBus port  
MB1  
MB2  
No port  
Base load rate  
0–6000 rpm  
0–8  
Slave sequence  
order  
ModBus address  
1–250  
Demand to firing  
delay  
___hour ___min ___sec  
0–12000 rpm  
Table 36. Lead Lag Master Configuration  
Advanced Settings: Modulation Parameters.  
Fan rate during off  
cycle  
Parameter  
Comment  
Lead outlet sensor  
Slave outlet sensor average  
Disabled  
ModBus port  
MB1  
MB2  
No port  
Modulation backup  
sensor  
ModBus address  
0–250  
Off hysteresis  
On hysteresis  
0 °F to 234 °F  
(-17 °C to 112 °C)  
Lead Lag Master Configuration  
0 °F to 234 °F  
(-17 °C to 112 °C)  
Parameters (Hydronic Control Only)  
Table 35 displays Lead Lag Master Configuration parameters.  
Hysteresis step time ___Hour ____Minute _____Second  
P gain  
I gain  
0 - 400  
0 - 400  
0 - 400  
Click the Advanced Settings button to see available advanced  
parameters as shown in Table 36–44.  
D gain  
65-0303—05  
36  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 37. Lead Lag Master Configuration  
Advanced Settings: Central Heat Parameters.  
Table 41. Lead Lag Master Configuration  
Advanced Settings: Algorithms Parameters.  
Parameter  
Comment  
Parameter  
Comment  
Sequence order  
Measured run time  
Demand switch  
Stat  
Lead selection  
method  
Remote Stat  
ModBus Stat  
Disabled  
Lag selection method Sequence order  
Measured run time  
Setpoint source  
Setpoint  
Local  
ModBus  
4-20 ma  
Lead rotation time  
___day ____hour _____min  
___day ____hour _____min  
Force lead rotation  
time  
-40 °F to 266 °F (-40 °C to 130 °C)  
Time of day setpoint -40 °F to 266 °F (-40 °C to 130 °C)  
Table 42. Lead Lag Master Configuration  
Advanced Settings: Rate Allocation Parameters.  
4 ma water  
temperature  
-40 °F to 266 °F (-40 °C to 130 °C)  
Parameter  
Comment  
20 ma water  
temperature  
-40 °F to 266 °F (-40 °C to 130 °C)  
Base load common ? %  
Outdoor reset  
Enabled  
Disabled  
Table 43. Lead Lag Master Configuration  
Advanced Settings: Add Stage Parameters.  
Table 38. Lead Lag Master Configuration  
Advanced Settings: DHW Parameters.  
Parameter  
Method  
Comment  
Error threshold  
Firing rate threshold  
Parameter  
Comment  
DHW heat demand  
Disabled  
Priority source  
Disabled  
Detection time  
Error threshold  
Rate offset  
___Hour ____Minute _____Second  
0 °F to 234 °F (-17 °C to 112 °C)  
+ ________ %  
Priority method  
Boost during priority time  
Drop after priority time  
DHW priority override ___Hour ____Minute _____Second  
time  
Interstage delay  
___Hour ____Minute _____Second  
Table 44. Lead Lag Master Configuration  
Advanced Settings: Drop Stage Parameters.  
Table 39. Lead Lag Master Configuration  
Advanced Settings: Frost Protection Parameters.  
Parameter  
Method  
Comment  
Error threshold  
Firing rate threshold  
Parameter  
Enable  
Comment  
Enabled  
Disabled  
Detection time  
Error threshold  
Rate offset  
___Hour ____Minute _____Second  
0 °F to 234 °F (-17 °C to 112 °C)  
+ ________ %  
Outdoor setpoint  
-40 °F to 266 °F (-40 °C to 130 °C)  
Frost protection rate ____%  
Interstage delay  
___Hour ____Minute _____Second  
Table 40. Lead Lag Master Configuration Advanced  
Settings: Warm Weather Shutdown Parameters.  
Parameter  
Enable  
Comment  
Enabled  
Disabled  
Setpoint  
-40 °F to 266 °F (-40 °C to 130 °C)  
37  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
R7910A or R7911 Status  
DETAILS  
Data in Tables 45–Table 56 are displayed on the R7910A  
Hydronic or R7911 Steam status pages. A complete list of  
Status tables can be found in Table 60 on page 53.  
Details of the hydronic or steam system is accomplished  
through the detail status pages. The detail status page is  
shown below.  
The CH status data shown in Table 45 displays first when the  
CH Hydronic heating loop is selected on the Home page.  
Screens will appear only if they are configured for your system.  
Information shown is current status. For example: firing rate is  
the current fan speed or motor position; timing shown is current  
time Sola is at.  
Table 45. CH Hydronic Status.  
Data  
CH enable  
Comment  
Enabled, Disabled  
CH burner demand  
CH pump  
On or Off  
On or Off  
On or Off  
CH pump demand  
CH pump overrun  
time  
Running overtime for CH pump  
(seconds)  
CH requested rate  
CH OFF setpoint  
CH setpoint  
RPM or %  
Setpoint plus hysteresis  
Temp setting between -40 °F to 266 °F  
(-40 °C to 130 °C)  
CH ON setpoint  
Setpoint minus hysteresis  
CH setpoint source  
Normal, TOD, Outdoor reset, Remote  
control  
CH status  
Disabled, Normal, Suspended  
Demand source  
Sensor only, Sensor and Stat terminal,  
Sensor and Remote Stat, LCI and  
sensor  
Fig. 70. Hydronic CH detail status page.  
Outlet high limit  
Yes or No  
Status information on the detail status page is organized into  
groups and displayed on the page one group at a time. The  
user moves from one group to another using the left and right  
arrow buttons.  
Outlet high limit  
setpoint  
Temp setting between -40 °F to 266 °F  
(-40 °C to 130 °C)  
Outlet sensor state  
None, Normal, Open, Shorted,  
Outside high range, Outside low  
range, Not reliable (None = no outlet  
sensor)  
Status data on the detail status page is displayed in a menu for  
the group that is currently displayed. If more status items exist  
in the group than will fit on the screen, a vertical scroll bar  
allows the user to see all status data. If the user selects a line  
of status data in the menu, it will expand in bigger, more easily  
readable text, as show in Fig. 71. Additional information about  
Status data and groups that are displayed are provided in the  
R7910A or R7911 Status section of this document.  
Outlet temperature  
Outlet temperature (same as bar  
graph)  
Fig. 72. CH Hydronic Status menu (top).  
Fig. 71. Hydronic “expanded” detail status.  
65-0303—05  
38  
 
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 46. DHW Hydronic Status. (Continued)  
Data  
Comment  
DHW high limit  
Temp setting between -40 °F to 266 °F  
(-40 °C to 130 °C)  
DHW high limit  
setpoint  
Temp setting between -40 °F to 266 °F  
(-40 °C to 130 °C)  
DHW priority override 0-600 seconds  
time  
DHW pump  
On or Off  
DHW pump demand On or Off  
DHW pump overrun Running overrun time for DHW pump  
time  
(seconds)  
DHW requested rate RPM or %  
DHW sensor state  
None, Normal, Open, Shorted,  
Outside high range, Outside low  
range, Not reliable (None = no outlet  
sensor)  
Fig. 73. CH Hydronic Status menu (middle).  
DHW OFF setpoint  
DHW setpoint  
Setpoint plus hysteresis  
Temp setting between -40 °F to 266 °F  
(-40 °C to 130 °C)  
DHW ON setpoint  
Setpoint minus hysteresis  
DHW setpoint source Normal, TOD, Outdoor reset  
DHW status  
Disabled, Normal, Suspended  
DHW temperature  
DHW temperature (same as bar  
graph)  
The bar graph displayed for the CH control loop (hydronic) is  
the outlet sensor temperature; for the DHW control loop it is  
the DHW sensor temperature. When no analog DHW sensor is  
installed (digital switch instead), the inlet sensor temperature is  
displayed.  
Fig. 74. CH Hydronic Status menu (bottom).  
The status data in Table 46 displays first when the DHW  
Hydronic heating loop is selected on the Home page. Scrolling  
through the status groups eventually shows both.  
Table 46. DHW Hydronic Status.  
Data  
DHW enable  
Demand source  
Comment  
Enabled, Disabled  
Unknown, No source demand, CH,  
DHW, Lead Lag, CH frost protection,  
DHW frost protection, No demand due  
to burner switch  
DHW burner demand On or Off  
Fig. 75. DHW Hydronic Status menu (top).  
39  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 47. Burner Control Status. (Continued)  
Data  
Firing rate  
Comment  
% or RPM. Adjustable when firing rate  
control set to Manual.  
Firing rate control  
Flame signal  
Hold code  
Auto or Manual  
Flame signal strength  
Description of hold message if locked  
out  
Lockout  
Description of lockout message if  
locked out  
Pilot test hold  
Remote STAT  
Off or Hold  
On or Off  
Note: Steam will show Steam psi as the bar graph  
The bar graph displayed for this status is the outlet sensor  
temperature.  
Fig. 76. DHW Hydronic Status menu (middle).  
Fig. 77. DHW Hydronic Status menu (bottom).  
Fig. 78. Burner Control Status menu (top).  
Burner Control Status  
The Burner Control status page will display the status data  
shown in Table 47.  
Table 47. Burner Control Status.  
Data  
Comment  
Alarm reason  
Description for alarm being on (maybe  
lockout or a hold message)  
Annunciator first out First annunciator input related to  
lockout  
Annunciator hold  
Burner state  
First annunciator input related to hold  
Disabled, Locked out, Anti-short cycle,  
Unconfigured safety data, Standby  
Hold, Standby, Delay, Normal  
Standby, Preparing, Firing, Postpurge  
Sequence time  
Delay time  
Running time for timed burner control  
operation (seconds)  
Fig. 79. Burner Control Status menu (bottom).  
Running display of delay time when  
burner control in delay state.  
Burner control can be turned on and off in the R7910A or  
R7911 by the user.  
65-0303—05  
40  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Hydronic Demand and Modulation  
Status  
Table 49 displays the status page data for R7910A.  
Table 48. Hydronic Demand and Modulation Status.  
Data  
Comment  
Demand source  
CH, DHW, Lead Lag, or Frost  
Protection (parameter that has current  
priority)  
Firing rate  
% or RPM. Adjustable when firing rate  
control set to Manual.  
Demand rate  
Rate limiter  
% or RPM.  
None, Outlet high limit, Delta T limit,  
Stack limit, Slow start limit, Anti-  
condensation, Minimum modulation,  
Forced rate  
Fig. 81. Demand and Modulation Status menu (bottom).  
Limited rate  
% or RPM  
Rate override  
Burner control default, Burner control,  
manual firing rate off, None  
Inlet Temperature Status  
Table 49 displays the status page data for R7910A inlet  
temperature.  
Override rate  
% or RPM  
The bar graph displayed for this status is the outlet sensor  
temperature.  
Table 49. Inlet High Limit Status.  
Data  
Comment  
Inlet sensor state  
None, Normal, Open, Shorted,  
Outside high range, Outside low  
range, Not reliable (None=no outlet  
sensor)  
Inlet temperature  
Inlet sensor temperature (same as bar  
graph)  
The bar graph displayed for this status is the inlet sensor  
temperature.  
Fig. 80. Demand and Modulation Status menu (top).  
Fig. 82. Inlet High Limit Status menu.  
Fan Status  
Table 50 displays the status page data for the fan in the control.  
41  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 50. Control Fan Status.  
Data  
Fan speed  
Comment  
% or RPM (current fan speed)  
Maximum fan speed Setpoint of maximum fan speed (% or  
RPM)  
Minimum fan speed Setpoint of minimum fan speed (% or  
RPM)  
The bar graph displayed for this status is the fan speed.  
Fig. 84. Hydronic CH pump status menu.  
Flame Detection Status  
The status data shown in Table 52 is displayed for flame  
detection in the R7910A or R7911.  
Table 52. Flame Detection Status.  
Data  
Flame detected  
Flame signal  
Comment  
Yes or No  
Flame signal strength (same as bar  
graph)  
Fig. 83. Control Fan Status menu.  
Pilot test hold  
Off or hold  
Hydronic Pump Status  
Table 51 displays the status page data for this example,  
Central Heat pump in the R7910A. Screens available for DHW,  
Boiler, System, Aux1 and Aux2 will be the same if that pump is  
configured.  
The bar graph displayed for this status is the flame signal.  
Table 51. Hydronic CH Pump Status.  
Data  
CH Pump  
Comment  
On or Off  
Controlling Pump  
Terminal  
Pump A, B, or C  
Status  
On, Off, or Not Used  
Duration of delay time  
Duration of overrun time  
Duration of frost overrun time  
Number of days idle  
Delay time  
Overrun time  
Frost overrun time  
Idle days  
Cycle count  
Number of cycles  
Fig. 85. Flame Detection Status menu.  
NOTE: This same status is also displayed for burner control  
status. A separate status group is defined to provide a  
bar graph of the flame signal.  
65-0303—05  
42  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Statistics Status  
Stack Limit Status  
Table 53 displays the statistics status page data for the  
R7910A or R7911. Though the Steam control will not have a  
pump, the output can be used to run some other auxiliary  
equipment.  
Table 54 shows the status page data for the control Stack Limit.  
Table 54. Stack Limit Status.  
Data  
Stack limit enable  
Stack limit  
Comment  
Enabled or Disabled  
Table 53. Control Statistics Status.  
Temp setting between -40 °F to 266 °F  
(-40 °C to 130 °C)  
Data  
Comment  
Number of cycles  
Burner cycles  
Burner run time  
CH pump cycles  
Stack limit setpoint  
Stack sensor state  
Temp setting between -40 °F to 266 °F  
(-40 °C to 130 °C)  
Duration of run time  
Number of cycles  
None, Normal, Open, Shorted,  
Outside high range, Outside low  
range, Not reliable (None=no stack  
temp sensor)  
System pump cycles Number of cycles  
Controller cycles  
Number of cycles  
Controller run time  
Duration of run time  
Stack temperature  
Stack sensor temperature (same as  
bar graph)  
The bar graph displayed for this status is the outlet sensor  
temperature.  
The bar graph displayed for this status is the stack sensor  
temperature.  
Fig. 86. Control Statistics Status menu (top).  
Fig. 88. Stack Limit Status menu.  
Lead Lag Slave Status - Hydronic  
Only  
Table 55 shows the status page data for Lead Lag Slave.  
Table 55. Lead Lag Slave.  
Data  
Comment  
Type  
Slave  
Command Received Yes/No  
Demand  
Off  
Request Rate  
Burner Control  
Modulating  
Priority  
RPM  
Standby  
No  
Fig. 87. Control Statistics Status menu (bottom).  
43  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Fig. 89. Lead Lag Slave Status menu.  
Fig. 90. Lead Lag Master Status menu.  
Lead Lag Master Status - Hydronic  
R7910A OR R7911  
DIAGNOSTICS  
Only  
Table 56 shows the status page data for Lead Lag Master.  
The diagnostic page displays analog and digital I/O status of  
the control. The digital I/O data is displayed as LEDs that are  
either on (green) or off (red) (see Fig. 91–93). Not all digital I/O  
can be displayed at the same time on the page, so a horizontal  
scroll bar is used to move the view left and right to show all  
digital I/O data.  
Table 56. Lead Lag Master.  
Data  
Master enabled  
Status  
Comment  
Enabled  
normal  
Demand source  
Active Service  
Off setpoint  
Setpoint  
Lead lag slave  
None  
160 °F (71 °C)  
150 °F (66 °C)  
145 °F (63 °C)  
150 °F (66 °C)  
On setpoint  
operating  
temperature  
Sensor state  
normal  
Sensor temperature 150 °F (66 °C)  
Slave firing  
no  
Stager state  
idle  
Stager timer  
CH demand  
CH frost demand  
DHW frost demand  
no  
no  
Fig. 91. Diagnostic digital I/O page (left).  
65-0303—05  
44  
 
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 57. Control Digital I/O Data.  
Data  
Comment  
Pump C  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
On/Off  
Blower/HSI  
Pilot valve  
Main valve  
Load Control Input  
STAT  
Pre-ignition interlock  
Interlock  
External ignition  
Alarm  
Pilot test hold  
Time Of Day  
Safety relay  
Low Gas  
Fig. 92. Diagnostic digital I/O page (center).  
High Gas  
Annunciator 3  
Annunciator 4  
PM  
Annunciator 5  
Annunciator 6  
Annunciator 7  
Annunciator 8  
PM Lead/Lag  
“On” status is indicated by a green LED and “Off” status is  
indicated by a red LED.  
Table 58. Control Analog I/O Data.  
Data  
Comment  
Fig. 93. Diagnostic digital I/O page (right).  
Outlet  
Temperature sensors or pressure sensors also display the  
current sensor state, (i.e., whether there is a fault condition or  
the sensor is in a normal monitoring state). The user can toggle  
between displaying the control digital and analog I/O (the initial  
display is the digital I/O). The Digital or Analog button on the  
bottom of the diagnostic page changes the I/O displayed to the  
type indicated by the button.  
Inlet  
If enabled  
Firing rate  
% or RPM  
V
Flame signal  
Fan speed  
RPM (if applicable). Should  
match with firing rate.  
Domestic Hot Water  
Stack  
If enabled  
If enabled  
If enabled  
If enabled  
The following data is displayed on the control diagnostics page  
(see Fig. 91–93).  
Outdoor  
Header  
Table 57. Control Digital I/O Data.  
Data  
Comment  
Analog I/O data is displayed as bar charts depicting the I/O  
level (see Fig. 94). Analog I/O that is not enabled for the  
installation displays a blank I/O level. To see all analog I/O, use  
the horizontal scroll bar to move the view left and right.  
Pump A  
Pump B  
On/Off  
On/Off  
45  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
INSTALLER CHECKOUT  
Diagnostics Tests  
Pressing the Diagnostics Test button launches the diagnostic  
tests. The first test displayed on the right side of the screen is  
the last selected test shown, as seen in Fig. 97.  
This screen enables the user to perform the following tests:  
Modulation Test: enables the user to verify that the burner is  
firing at the correct rate. (See Fig. 97.)  
Pilot Test: enables the user to verify that the pilot valve is  
functioning properly. The user can also perform burner  
adjustments for the pilot flame. (See Fig. 98.)  
Pump Test: enables the user to verify that the correct pump is  
on or off. The Start Test button will test all pumps; pressing an  
individual pump tests that pump only. (See Fig. 99.)  
Burner Switch: this button turns the burner on or off.  
Start Test: runs the test for 5 minutes.  
Fig. 94. Diagnostics analog I/O page (left).  
Fig. 97. Modulation test.  
Fig. 95. Diagnostics analog I/O page (center).  
Fig. 98. Pilot test.  
Fig. 96. Diagnostics analog I/O page (right).  
65-0303—05  
46  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
If Contrast or Volume are changed, Fig. 101 displays to allow  
saving these changes.  
Fig. 99. Pump test.  
Fig. 101. Setup settings changed.  
S7999B OR S7999C  
DISPLAY SETUP AND  
DIAGNOSTICS  
Cleaning the Screen  
When the user wants to clean the touch screen, the CLEAN  
SCREEN button is selected to freeze touch input temporarily for  
30 seconds to allow the user to clean the screen. (See Fig. 102.)  
The following pages apply to display setup and diagnostics for  
the S7999B or S7999C OI Displays.  
Setup  
The Setup button on the Home page (for S7999B OI Display)  
or Display Setup Button on the Configuration Screen for the  
S7999C OI Display is selected to go to these pages. The Setup  
screen (see Fig. 100) is displayed first. It allows for some OI  
Display settings. The Advanced Setup button permits the user  
to run some diagnostic functions for the display and to set  
advanced features for run-time operation. See “Advanced  
Setup” on page 48 for these features.  
Fig. 102. Clean screen setup.  
A countdown screen (Fig. 103) displays during the screen  
disable period. It disappears when the touch screen is  
re-enabled.  
Fig. 100. R7910A setup.  
47  
65-0303—05  
 
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Fig. 105. Ethernet settings.  
Fig. 103. Screen disabled for cleaning.  
A Honeywell software server connectivity check can be  
performed by selecting the Check button. This button is only  
enabled when the Ethernet interface is enabled and active.  
The connectivity check tries for 15 seconds to connect to the  
Honeywell software server. Successful connection displays a  
“CONNECTED” message on the screen. An unsuccessful  
attempt displays “NOT CONNECTED.”  
Pressing the SYSTEM CONFIGURATION button starts up the  
system configuration. For more information, see “System  
Pressing the ADVANCED SETUP button starts the Advanced  
Setup.  
The MAC (Media Access Control) address is a hardware  
address that uniquely identifies the S7999B on the network.  
This information is likely only of interest to the network  
administrator.  
ADVANCED SETUP  
Pressing the ADVANCED SETUP button on the Setup page  
displays more options that can be set by the user (Fig. 104).  
The IP (Internet Protocol) address is the address that the  
S7999B has been assigned by the DHCP server in the local  
network to use for others to access the S7999B. This address  
is necessary for the remote user to identify the S7999B in an  
FTP (File Transfer Protocol) application for transferring trend  
analysis information. Like the MAC address, it is displayed for  
informational purposes for the network administrator.  
If the IP address has a private network designation (192.x.x.x),  
remote access from outside the local network may not be  
possible. Contact the network administrator for assistance in  
this case. If the IP address is 255.255.255.255, then no IP  
assignment has been made, and there is no connection to the  
network. This possibility could be due to no physical  
connection to an Ethernet network, or there is no DHCP server  
present on the Ethernet network. Check with the network  
administrator for assistance.  
The Gateway IP address is displayed for informational  
purposes for the network administrator. The gateway node  
provides remote access for devices located off of the local  
network to the S7999B.  
Fig. 104. Advanced Setup.  
The Enable Network checkbox specifies that the Ethernet  
interface is on or not when the S7999B is powered up. The  
selection must be saved to permanent storage (flash) with the  
Save button for it take effect at boot time. This checkbox  
should normally be disabled, and enabled when Ethernet  
access to the S7999B is necessary. This interface must also  
be enabled for the Software Server Connectivity check to  
function properly (the Check button). If the Ethernet interface is  
disabled, the check procedure fails.  
Ethernet Settings (S7999B Only)  
Ethernet Settings is used to enable Ethernet communications  
for remote diagnostics, file transfers, and remote support, and  
is not typically enabled (Fig. 105). This feature should remain  
disabled unless directed to do so for remote troubleshooting.  
Once the feature is enabled, the S7999B must be reset to start  
it at power-up. The Ethernet interface can also be used to  
transfer profile curve files to/from the S7999B over a local  
intranet or the Internet.  
65-0303—05  
48  
 
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
The S7999B must be assigned an IP address by a DHCP  
server for it to operate on the local network, so the Use DHCP  
box should be checked. However, because the S7999B  
requires this feature, it ignores the checkbox and always  
regards it as checked. The checkbox is included for future  
purposes when dynamic IP addressing isn’t required.  
The status variable with the largest range (minimum to  
maximum) is used as the Y-axis range in the graph.  
As the status variables are selected they are listed in a trend  
variables list box. The user chooses the status variables from a  
drop down menu and then presses the Add button to add each  
status variable to the trend variable list. See Fig. 108. After all  
status variables have been selected press the Show button to  
view the trend analysis graph.  
Trend Analysis Page (S7999B Only)  
Trend analysis of R7910 or R7911 status data can be viewed  
on the S7999B. A graph displays a historical view of R7910 or  
R7911 status data over varying time periods.  
A 2-dimensional graph with status data values shown on the Y  
axis over time specified on the X axis is displayed. Status for  
the most recent time is represented on the left side of the  
graph with older status running towards the right side of the  
graph.  
Fig. 108. Trend analysis menu page.  
Each status variable displayed in the trend analysis is  
represented by a different colored line, as follows:  
1. First status variable = green  
2. Second status variable = yellow  
3. Third status variable = red  
4. Fourth status variable = blue  
Fig. 106. Trend analysis page.  
No more than two different measurement units (such as  
degrees), are allowed for the status variables selected in the  
trend analysis graph. Attempts to add a status variable with a  
third measurement unit are rejected.  
Up to 4 R7910 or R7911 status variables can be viewed at the  
same time on one trend analysis graph. Select the status  
variables for the graph on the menu page (see Fig. 107). This  
menu displays when the Trend Analysis button is selected on  
the R7910 or R7911 status page.  
A second Y axis is displayed on the right side of the graph to  
represent the scale for the second measurement unit. This can  
result in minor clipping of the curves on the right side, as  
shown in Fig. 109 and 110.  
Fig. 107. Trend analysis menu page.  
49  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
the graph so the Y axis depicts different degrees of detail for  
the data range. The viewing window can be moved up and  
down the graph to see the complete range when zoomed in.  
The smallest measurement interval is a single whole digit (no  
fractional precision) when the entire range exceeds 10 units,  
e.g., 20–30 degrees.  
Pressing the Stop button will pause trend data updates of the  
graph. The graph “freezes” the view when stopped. However,  
trend data sampling from the R7910 or R7911 continues  
regardless whether the graph update is stopped or not.  
Restarting the updates causes the graph to be refreshed with  
the latest data samples.  
Pressing the Clear button will clear the trend sample data for  
an R7910 or R7911. All trend data for the R7910 or R7911 is  
cleared including status variables that are not included in the  
graph. The user is asked to confirm this action before  
proceeding.  
Fig. 109. Trend analysis page with firing rate.  
NOTE: For system trend analysis graphs the Clear button  
isn’t present, so no status variables can be cleared.  
A snapshot of the trend analysis graph can be taken and saved  
to the S7999B. The user is asked to confirm the save before it  
occurs.  
NOTE: While this snapshot is saved, trend data sampling for  
all R7910s or R7911s is temporarily halted. Gaps or  
static level values occur in the trend data as a result.  
The date and time that the snapshot is taken is stored with the  
snapshot. Only the status variables displayed in the graph are  
stored in the snapshot. All raw sample data for the status  
variables are stored so that any sample rate can be viewed  
offline.  
Sample data stored in snapshot is either the real-time status at  
the time that the Save button is pressed or it is the sample data  
at the time that the graph is stopped.  
Special case trend analysis graphs for PID tuning can be  
viewed for CH, DHW, and Lead Lag demands.  
Fig. 110. Trend analysis page with demand source.  
If any of the status variables has degrees as a unit of  
measurement, degrees is used for the main Y axis (on the left  
of the graph). The status variables selected are saved and are  
displayed by default when the trend analysis menu page is first  
displayed. Status data is updated on the graph with new status  
at the same rate as the sample time period selected. The  
current sample time period is displayed in a button on the page  
(in Fig. 109 and 110, the button is “Seconds”).  
Status older than the sample time period is dropped from the  
right end of the curve as newer status appears on the left end  
of the curve.  
Trend data can be viewed in one-second (most recent 60  
second time period), 15-second (most recent 15-minute time  
period), and hour (most recent 24 hour time period) intervals.  
NOTE: Full graphs require that the S7999B has been moni-  
toring the R7910 or R7911 for the complete time  
period. Partial graphs display if this is not the case.  
Fig. 111. PID Trend analysis page.  
The buttons at the bottom can be used to change the view of  
the graph. The user can change the sample rates of the  
display by pressing the Seconds, Minutes, Hours, or Days  
button (the button changes depending on what sample rate is  
currently displayed). The + and - buttons zoom in and out of  
Data included in the PID analysis graph are:  
Sensor temperature (outlet for CH, DHW for DHW, and  
header for Lead Lag)  
65-0303—05  
50  
Setpoint (for corresponding demand source)  
Burner firing rate  
Hysteresis on (for corresponding demand source)  
Table 59. R7910/R7911 Trend Analysis Data. (Continued)  
Data  
Comment  
If enabled  
Hysteresis off (for corresponding demand source)  
Stack temperature  
Header temperature (R7910 If enabled  
only)  
The Clear button is disabled for the PID analysis (doesn’t apply to  
hysteresis).  
CH setpoint  
Actual CH setpoint based on  
time of day (TOD).  
The default sample rate is 15 sec periods (a tick mark on the X axis  
for every 15 second period, with minutes displayed every 4 tick  
marks).  
DHW setpoint (R7910 only)  
Actual DHW setpoint based  
on TOD.  
Special case trend analysis graph for R7910/R7911 vessel heat  
exchange can be selected.  
Central Heat Operation  
Analysis  
Domestic Hot Water  
Operation Analysis (R7910  
only)  
Vessel Analysis  
Trend Analysis Snapshot  
The trend analysis snapshot file is stored in Comma Separated Value  
(CSV) format in the S7999B so it can be imported into a spreadsheet  
program such as Microsoft Excel.  
The trend analysis snapshot file can be viewed in graph form on the  
S7999B. It is also accessible in an Ethernet FTP session with the  
S7999B. This FTP session can be used to export the trend analysis  
snapshot file from the S7999B.  
Diagnostics  
Pressing the Diagnostics button permits some display hardware  
diagnostics (see Fig. 104). Normally, these diagnostics are  
applicable only for factory testing purposes, but conditions may  
arise that warrant this testing.  
Fig. 112. Vessel analysis page.  
Data included in the vessel analysis graph are:  
Outlet temperature  
Inlet temperature  
Heat exchange (outlet – inlet)  
Burner firing rate  
Automatic sampling of trend data takes place when the trend  
analysis report is displayed. No user intervention is necessary to  
invoke sampling.  
NOTE: Sample data is collected and stored in the S7999B. The  
R7910 or R7911 don’t collect any historical data for trending  
purposes. For this reason any S7999B reset causes all  
R7910 or R7911 sampling to start over with no data.  
Trend analysis of the following data from each R7910/R7911 is  
possible:  
Table 59. R7910/R7911 Trend Analysis Data.  
Fig. 113. Display diagnostics.  
Data  
Demand source  
Comment  
CH, DHW, LL (Lead Lag), or  
FP (Frost Protection) Steam  
Sensor  
NOTE: COM 1 Communication test is a factory-only test. Perform-  
ing this text when not connected to a factory test fixture will  
always yield a “Failed” result.  
Outlet temperature (R7910  
only)  
Each test is invoked by pressing the Test button next to the  
diagnostic. The results of the diagnostic test (“PASS” or “FAIL”)  
display in the text box next to the Test button.  
Firing rate  
% or RPM  
PWM feedback  
V
Fan speed  
Flame signal strength  
Date and Time  
Inlet temperature (R7910  
only)  
If enabled  
Display time can be configured in the S7999B and S7999C OI  
Displays and applied to the R7910A or R7911. A date and time is  
entered by the user at the display and any data that is timestamped is  
marked with the current time and date in the display.  
DHW temperature (R7910  
only)  
If enabled  
If enabled  
Outdoor temperature  
51  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
The Display clock is set by selecting the Date and Time button  
on the Advanced Setup page. A screen similar to the following  
figure (Fig. 114) displays.  
NOTE: It’s important that the time be set in the Display so  
correct timestamps are given to the R7910A or  
R7911 lockouts. The display’s time and date need  
to be set should power be interrupted to the dis-  
play.  
Fig. 116. Code Version—bottom view.  
User Preferences  
The User Preferences button displays General options as well  
as those for for COM1 and COM2.  
Fig. 114. Display Date and Time.  
Edit the date and time and press the OK button to set the new  
settings. Press the Cancel button to exit without changing the  
time or date.  
Version  
Pressing the Version button on the Advanced Setup page  
displays manufacturer and software version information (Fig.  
115 and 116).  
Fig. 117. General tab.  
The General tab (see Fig. 117) contains the following settings:  
Display alerts on Status Summary Bar? This determines  
whether non-safety alerts will be shown on the summary bar  
of the home page.  
Display empty parameter groups? This cleans up the  
home page by hiding unused parameter groups.  
Automatic synchronization with control when  
connections is made? This allows automatic display of  
new control to update when the connection is identified  
instead of manually making the synchronization when the  
operator is ready.  
Sound Audio Alarm for faults? This uses the display  
speaker to sound an alarm on shutdown for SOLA faults.  
Fig. 115. Code version—top view.  
The COM1 tab (see Fig. 118) contains the following setting:  
Modbus address range 1-N: Sets the Modbus address for  
the connected device (range is 1 to 250).  
65-0303—05  
52  
Fig. 118. COM1 tab.  
Fig. 120. Processor Reset.  
When the Display is reset, the display will reboot and automatically  
seek out the Modbus™ device connected to it. When the search is  
complete, the display will return to the home page.  
S7999B Only  
COM2 is a Modbus gateway for Building Automation System (BAS)  
networking.  
Press the COM2 tab (see Fig. 119) to define settings:  
Table 60. Status Tables.  
Enable Modbus Gateway: This box must be selected to enable  
the COM2 BAS interface.  
Modbus Gateway Speed: Select the baud rate (38400, 19, 200,  
or 9600 bps)  
Modbus Gateway Timeout: Defines how long the BAS will wait  
after sending a Modbus message before timing out and sending  
the next modbus message (currently non-functional; leave at 1.0)  
Name  
Table #  
45  
Page #  
38  
CH  
DHW  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
39  
40  
41  
41  
42  
42  
42  
43  
43  
43  
44  
Burner Control  
Demand and Modulation  
Inlet High Limit  
Fan  
Pump  
Flame Detection  
Statistics  
Stack Limit  
Lead Lag Slave  
Lead Lag Master  
Parameters  
A complete list of configurable parameters is shown in Table 61.  
Table 61. Configurable Parameters.  
Table Page  
Fig. 119. COM 2 tab.  
Parameter  
Comment  
#
#
Display Reset  
Boiler Name Name to identify boiler (up to 20 6  
characters)  
21  
The user can reset the display and force a power-up by pressing the  
Display Reset button. A pop-up dialog box confirming the reset  
request displays (Fig. 120) before the reset proceeds.  
Installation  
Notes regarding installation (up  
to 20 characters)  
Installer  
password  
Change installer password  
setting  
OEM  
Change OEM password setting  
password  
Factory Data OEM name to associate with  
boiler (up to 20 characters)  
53  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 61. Configurable Parameters. (Continued)  
Table Page  
Table 61. Configurable Parameters. (Continued)  
Table Page  
Parameter  
Comment  
#
#
Parameter  
Comment  
#
#
CH enable  
Disable or Enable Central  
Heating Loop  
8
21  
Steam  
enable  
Disable/enable steam feature  
9
22  
CH demand Sensor for Central Heat  
Steam  
demand  
source  
Sensor and LCI  
switch  
demand:  
Sensor only  
Sensor and Remote Stat  
Sensor and Stat Terminal  
Sensor Only  
Sensor & STAT terminal  
Sensor & Remote Stat  
LCI & Sensor  
Steam  
pressure  
setpoint  
Setpoint for normal modulation  
Adjustable 0 to 15 or 0 to 150  
(sensor dependant)  
CH Outdoor Enabled  
reset  
Disabled  
Steam time Setpoint when TOD switch on  
CH has  
priority over  
Lead Lag  
Yes, No, Cancel  
of day  
setpoint  
Adjustable 0 to 15 or 0 to 150  
(sensor dependant)  
Minimum  
steam  
Establishes setpoint for the  
4ma. input.  
CH Setpoint Local  
source  
S2 (J8-6) 4-20mA  
pressure  
Adjustable 0 to 15 or 0 to 150  
(sensor dependant)  
CH Setpoint Setpoint for normal Central  
Heat modulation:  
Steam  
Differential below setpoint when  
-40 °F to 266 °F  
(-40 °C to 130 °C)  
pressure off boiler is turned off  
hysteresis  
Adjustable 0 to 15 or 0 to 150  
(sensor dependant)  
CH time of  
Setpoint when Time Of Day  
day setpoint switch is on. -40 °F to 266 °F  
(-40 °C to 130 °C)  
Steam  
pressure on boiler  
hysteresis  
Differential from setpoint when  
is turned on.  
Adjustable 0 to 15 or 0 to 150  
(sensor dependant)  
CH off  
Differential above setpoint  
when boiler is turned off. -40 °F  
to 266 °F (-40 °C to 130 °C)  
hysteresis  
Steam  
hysteresis  
step time  
Time between hysteresis  
changes 0 to 600 seconds  
(0=disable)  
CH on  
hysteresis  
Differential from setpoint when  
boiler is turned on.-40 °F to 266  
°F (-40 °C to 130 °C)  
Steam P  
Gain  
Gain applied for the P portion of  
the PID equation  
0-400  
4 mA water -40 °F to 266 °F  
temperature (-40 °C to 130 °C)  
20 mA water -40 °F to 266 °F  
temperature (-40 °C to 130 °C)  
Steam I Gain Gain applied for the I portion of  
the PID Equation - 0-400  
Modulation  
sensor  
Outlet sensor, Inlet sensor, S5  
(J8-11)  
Steam D  
Gain  
Gain applied for the D portion of  
the PID equation  
0-400  
Modulation  
Local  
Rate Sensor  
Steam 4-20 uses 4-20ma remote control  
ma remote  
control  
CH P-gain  
CH I-gain  
CH D-gain  
Time between hysteresis step  
changes: 0-400  
function to control either the  
setpoint or modulation for  
Steam  
Time between hysteresis step  
changes: 0-400  
Disable, setpoint, modulation  
CHmaximum -40 °F to 266 °F  
outdoor  
temperature  
10  
22  
Time between hysteresis step  
changes: 0-400  
(-40 °C to 130 °C)  
Hysteresis  
step time  
Time between hysteresis step  
changes: 0-600 seconds  
(0=Disable hysteresis stepping)  
CH minimum -40 °F to 266 °F  
outdoor  
temperature  
(-40 °C to 130 °C)  
Low water  
-40 °F to 266 °F  
temperature (-40 °C to 130 °C)  
Minimum  
water  
-40 °F to 266 °F  
(-40 °C to 130 °C)  
temperature  
Maximum off -40 °F to 266 °F  
point (-40 °C to 130 °C)  
65-0303—05  
54  
Table 61. Configurable Parameters. (Continued)  
Table Page  
Table 61. Configurable Parameters. (Continued)  
Table Page  
Parameter  
Comment  
#
#
Parameter  
Comment  
#
#
DHW enable Disable or Enable Domestic Hot 11  
Water Loop  
23  
Tap detect  
degrees  
-0 °F to 180 °F (-17 °C to 82 °C) 13  
23  
DHW  
demand  
switch  
Sensor for Central Heat  
demand:  
DHW sensor only,  
Tap detect on ___hour ___min ___sec  
recognition  
time  
DHW sensor & Remote Stat,  
DHW switch & inlet sensor, or  
DHW switch & outlet sensor  
Tap detect on -0 °F to 180 °F (-17 °C to 82 °C)  
threshold  
Tap detect  
minimum on  
time  
___hour ___min ___sec  
DHW Priority Which system has priority:  
source  
Disabled or  
Heat Demand  
Tap stop  
inlet-DHW  
degrees  
-0 °F to 180 °F (-17 °C to 82 °C)  
-0 °F to 180 °F (-17 °C to 82 °C)  
DHW Priority Boost during priority time  
method  
Drop after priority time  
DHW  
Modulation  
sensor  
DHW Sensor  
Outlet Sensor  
Inlet Sensor  
Auto: DHW (S6) or Inlet Sensor  
Auto: DHW (S6) or Outlet  
Sensor  
Tap stop  
outlet-Inlet  
degrees  
Plate preheat -40 °F to 266 °F  
setpoint (-40 °C to 130 °C)  
Plate preheat ___hour ___min ___sec  
on  
recognition  
time  
DHW  
setpoint  
-40 °F to 240 °F  
(-40 °C to 115 °C)  
DHW time of Setpoint when Time Of Day  
day setpoint switch is on. -40 °F to 240 °F  
(-40 °C to 115 °C)  
Plate preheat -0 °F to 180 °F (-17 °C to 82 °C)  
on hysteresis  
DHW off  
hysteresis  
Differential above setpoint  
when boiler is turned off. -40 °F  
to 240 °F (-40 °C to 115 °C)  
Plate preheat -0 °F to 180 °F (-17 °C to 82 °C)  
off hysteresis  
Plate preheat -0 °F to 180 °F (-17 °C to 82 °C)  
detect on  
threshold  
DHW on  
hysteresis  
Differential from setpoint when  
boiler is turned on. 2 °F to  
234 °F (-16 °C to 112 °C)  
Plate preheat -0 °F to 180 °F (-17 °C to 82 °C)  
detect off  
threshold  
DHW priority ___hour ___min ___sec  
override time  
DHW  
hysteresis  
step time  
Time between hysteresis step  
changes: 0-600 seconds  
(0=Disable hysteresis stepping)  
Plate preheat ___hour ___min ___sec  
minimum on  
time  
DHW priority Which system has priority:  
Plate preheat ___hour ___min ___sec  
delay after  
tap  
vs CH  
Central Heat over Domestic Hot  
Water, or  
Domestic Hot Water over  
Central Heat  
Warm  
Enabled, disabled  
14  
24  
Weather  
Setpoint  
Enable  
DHW priority Which system has priority:  
vs LL  
Lead Lag over Domestic Hot  
Water,  
Domestic Hot Water over Lead  
Lag  
Warm  
Weather  
Setpoint  
-40 °F to 266 °F  
(-40 °C to 130 °C)  
DHW P-gain Time between hysteresis step  
changes: 0-400  
DHW I-gain Time between hysteresis step  
changes: 0-400  
DHW D-gain Time between hysteresis step  
changes: 0-400  
DHW storage Enabled, Disabled  
enable  
12  
23  
Storage time ___hour ___min ___sec  
Setpoint  
-40 °F to 266 °F  
(-40 °C to 130 °C)  
Off  
hysteresis  
-0 °F to 180 °F (-17 °C to 82 °C)  
-0 °F to 180 °F (-17 °C to 82 °C)  
On  
hysteresis  
55  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 61. Configurable Parameters. (Continued)  
Table Page  
Table 61. Configurable Parameters. (Continued)  
Table Page  
Parameter  
Comment  
#
#
Parameter  
Comment  
#
#
CHmaximum RPM or %  
modulation  
rate  
15  
25  
Auxiliary  
pump control On  
Auto  
17  
26  
Auxiliary  
pump is on  
when  
CH pump is ON  
Slave command  
DHW  
RPM or %  
RPM or %  
maximum  
modulation  
rate  
Auxiliary  
pump output Pump B  
Pump C  
Pump A  
Minimum  
modulation  
rate  
None  
Boiler pump Auto  
CH forced  
rate time  
0-600 seconds  
RPM or %  
control  
On  
Boiler pump Pump A  
output  
CH forced  
rate  
Pump B  
Pump C  
None  
DHW forced 0-600 seconds  
rate time  
Boiler pump 0-600 seconds  
overrun time 0 = Not configured  
DHW forced RPM or %  
rate  
CH pump  
control  
Auto  
On  
CH slow start Enabled  
enable  
Disabled  
CH pump  
output  
Pump A  
Pump B  
Pump C  
None  
DHW slow  
start enable Disabled  
Enabled  
Slow start  
degrees  
-40 °F to 266 °F  
(-40 °C to 130 °C)  
CH pump  
0-600 seconds  
overrun time 0 = Not configured  
System Auto  
pump control On  
Slow start  
ramp  
RPM /minute or %/minute  
0-10/4-20 mA Output hysteresis  
0-10/4-20mA  
Output  
hysteresis  
System  
pump output Pump B  
Pump C  
Pump A  
4-20 mA  
input  
hysteresis  
None  
System  
0-600 seconds  
pump ourrun 0 = Not configured  
time  
Pump control Auto  
On  
17  
26  
Pump  
0-600 seconds  
Pump output Pump A  
Pump B  
exercise time 0= Not configured  
Auxiliary  
pump cycles  
0-999,999  
18  
27  
Pump C  
None  
Boiler pump 0-999,999  
cycles  
Pump start  
delay  
___hour ___min ___sec  
Burner cycles 0-999,999  
Overrun time ___hour ___min ___sec  
Burner run  
time  
0-999,999  
Boiler pump Pump A  
output  
Pump B  
Pump C  
None  
CH pump  
cycles  
0-999,999  
DHW pump 0-999,999  
cycles  
System  
0-999,999  
pump cycles  
Auxiliary 2  
0-999,999  
pump cycles  
65-0303—05  
56  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 61. Configurable Parameters. (Continued)  
Table Page  
Table 61. Configurable Parameters. (Continued)  
Table Page  
Parameter  
Comment  
#
#
Parameter  
Comment  
#
#
DHW high  
limit  
Enabled  
Disabled  
19  
27  
Heat  
Enabled  
Disabled  
23  
29  
exchanger  
high limit  
enable  
DHW high  
limit  
response  
Suspend DHW  
Recycle & hold  
Lockout  
Heat  
-40 °F to 266 °F  
exchanger  
high limit  
setpoint  
(-40 °C to 130 °C)  
DHW high  
limit setpoint (-40 °C to 130 °C)  
-40 °F to 266 °F  
Outlet high  
limit  
response  
Recycle & hold  
Lockout  
Heat  
Recycle & delay  
Recycle & delay with retry limit  
Lockout  
exchanger  
high limit  
response  
Outlet high  
limit setpoint (-40 °C to 130 °C)  
-40 °F to 266 °F  
Heat  
exchanger  
retry limit  
0 to 100  
Stack limit  
Enabled  
Disabled  
20  
28  
Stack limit  
delay  
0-600 seconds  
Heat  
___hour ___min ___sec  
exchanger  
high limit  
delay  
Stack limit  
response  
Lockout  
Recycle & delay  
CH anticon- Enabled  
24  
29  
Stack limit  
setpoint  
-40 °F to 266 °F  
(-40 °C to 130 °C)  
densation  
Disabled  
enable  
Delta T  
enable  
Enabled  
Disabled  
21  
28  
CH anticon- Normal (no change)  
densation  
pump  
CH pump forced off  
Delta T  
degrees  
-40 °F to 266 °F  
(-40 °C to 130 °C)  
CH anticon- -40 °F to 266 °F  
Delta T delay 0-600 seconds  
densation  
setpoint  
(-40 °C to 130 °C)  
Delta T  
response  
Recycle & delay  
Lockout  
DHW anti-  
condensa-  
tion enable  
Enabled  
Disabled  
Delta T retry  
limit  
Delta T rate Enabled  
limit enable Disabled  
DHW anti-  
condensa-  
tion pump  
Normal (no change)  
DHW pump forced off  
Delta T  
inverse limit  
time  
___hour ___min ___sec  
DHW anti-  
condensa-  
tion setpoint  
-40 °F to 266 °F  
(-40 °C to 130 °C)  
Delta T  
Recycle & delay  
inverse limit Recycle & delay with retry limit  
response Lockout  
Anticondensa Anticondensation is more  
tion Priority important than (check those  
that apply):  
Stack limit  
Delta T limit  
Slow start  
Forced rate  
Outlet high limit  
Outlet T-rise Enabled  
22  
29  
enable  
Disabled  
Heat  
Enabled  
exchanger T- Disabled  
rise enable  
T-rise  
degrees  
0 °F to 234 °F  
(-17 °C to 112 °C)  
T-rise  
response  
Recycle & delay  
Recycle & delay with retry limit  
Lockout  
T-rise retry  
limit  
0 to 100  
T-rise delay ___hour ___min ___sec  
57  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 61. Configurable Parameters. (Continued)  
Table Page  
Table 61. Configurable Parameters. (Continued)  
Table Page  
Parameter  
Comment  
#
#
Parameter  
Comment  
#
#
CH frost  
protection  
enable  
Enabled  
Disabled  
25  
30  
PII enable  
Enabled  
Disabled  
27  
31  
LCI enable  
Enabled  
Disabled  
DHW frost  
protection  
enable  
Enabled  
Disabled  
Interrupted  
air switch  
Enable during purge and  
ignition  
Lead Lag  
frost  
Enabled  
Disabled  
(IAS) enable Disabled  
Enable during purge  
protection  
enable  
Interlock  
(ILK) start  
check enable  
No ILK check  
ILK check  
Outdoor frost -40 °F to 266 °F  
protection  
setpoint  
(-40 °C to 130 °C)  
(applicable for CH only)  
ILK/IAS open Recycle  
response Lockout  
Lead Lag  
frost  
protection  
___%  
ILK bounce Enabled  
detection  
Disabled  
enable  
rate  
Purge rate  
proving  
Fan Speed  
High Fire Switch  
None  
CH pump  
frost overrun  
time  
___hour ___min ___sec  
Lightoff rate Fan Speed  
DHW pump ___hour ___min ___sec  
frost overrun  
time  
proving  
Low Fire Switch  
None  
Prepurge  
rate  
RPM or %  
28  
31  
Annunciation Enabled  
enable  
26  
30  
Disabled  
Prepurge  
time  
0-600 seconds  
0 = Not configured  
Annunciator 01 - Annunciator 1  
(1–8) location 02 - Annunciator 2  
03 - Annunciator 3  
Run  
0-600 seconds  
stabilization 0 = Not configured  
time  
04 - Annunciator 4  
05 - Annunciator 5  
06 - Annunciator 6  
07 - Annunciator 7  
08 - Annunciator 8  
PII - Pre-Ignition ILK  
LCI - Load Control Input  
ILK - Interlock  
Standby Rate RPM or %  
Postpurge  
rate  
RPM or %  
Postpurge  
time  
0-600 seconds  
0 = Not configured  
Annunciator Up to 3 characters  
(1–8) short  
Forced  
recycle  
___hour ___min ___sec  
name  
interval time  
Annunciator Up to 20 characters  
(1–8) name  
65-0303—05  
58  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 61. Configurable Parameters. (Continued)  
Table Page  
Table 61. Configurable Parameters. (Continued)  
Table Page  
Parameter  
Comment  
#
#
Parameter  
Comment  
#
#
Pilot test hold On  
Off  
29  
32  
Flamesensor Flame rod  
31  
35  
type  
UV power tube  
UV power tube with spark  
interference  
Ignition  
source  
Hot Surface Igniter  
External ignition  
Internal ignition  
None  
Modulation  
output  
4-20mA  
0-10V  
Fan PWM*  
Pilot type  
Direct burner constant ignition  
Direct burner pulsed ignition  
Intermittent  
Interrupted  
Blower/HSI  
Blower  
Hot surface ignition  
Lightoff rate RPM or %  
Temperature Fahrenheit  
Preignition  
time  
0-600 seconds  
0 = Not configured  
units  
Celsius  
Anti short-  
cycle time  
0-600 seconds  
0 = Not configured  
Pilot Flame  
Establishing 10 secs  
15 secs  
Period  
4 secs  
Igniter on  
during  
1st half of PFEP  
Pilot Flame Establishing Period  
with Lockout Do NOT clear lockout  
Main Flame 15 secs  
Establishing 10 secs  
STAT & Enabled  
Period  
5 secs  
EnviraCOM Disabled  
remote stat  
Flame  
Threshold  
μA/V  
Flamesensor Flame rod  
32  
35  
type  
UV  
Ignite failure Lockout  
30  
32  
response  
Recycle  
Recycle & hold  
Recycle & lockout  
Modulation  
output  
4-20ma  
0-10V  
Fan PWM  
Ignite failure 0-600 seconds  
delay 0 = Not configured  
Blower/HSI  
Blower  
Hot surface ignitor  
Ignite failure 1, 3, or 5  
retries  
Temperature Fahrenheit  
units  
Celsius  
MFEP flame Recycle  
Anti short  
cycle time  
0-600 minutes  
failure  
Lockout  
response  
Alarm silence 0-600 minutes  
time  
Run flame  
failure  
response  
Recycle  
Lockout  
Power up  
Clear lockout  
with lockout Do NOT clear lockout  
Fan speed  
error  
response  
Recycle  
Lockout  
Inlet  
connector  
type  
0-15 psi  
0-150 psi  
UNCONFIGURED  
Stack  
connector  
type  
10k NTC dual safety  
10k NTC single non-safety  
12k NTC single non-safety  
UNCONFIGURED  
Header  
4-20ma  
UNCONFIGURED  
59  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 61. Configurable Parameters. (Continued)  
Table Page  
Table 61. Configurable Parameters. (Continued)  
Table Page  
Parameter  
Comment  
#
#
Parameter  
Comment  
#
#
Absolute  
maximum fan  
speed  
RPM  
RPM  
0-100  
33  
35  
Modulation  
backup  
sensor  
Lead outlet sensor  
Slave outlet sensor average  
Disabled  
36  
36  
Absolute  
minimum fan  
speed  
Off  
hysteresis  
0 °F to 234 °F  
(-17 °C to 112 °C)  
On  
hysteresis  
0 °F to 234 °F  
(-17 °C to 112 °C)  
Fan gain  
down  
Hysteresis  
step time  
___Hour ____Minute  
_____Second  
Fan gain up 0-100  
Minimum  
duty cycle  
1-100%  
P gain  
I gain  
0 - 400  
0 - 400  
0 - 400  
Pulses per  
revolution  
1-10  
D gain  
Demand  
switch  
Stat  
37  
37  
PWM  
frequency  
1000  
2000  
3000  
4000  
Remote Stat  
ModBus Stat  
Disabled  
Setpoint  
source  
Local  
ModBus  
4-20 ma  
Slow down  
ramp  
0-12000 RPM/sec  
Speed up  
ramp  
0-12000 RPM/sec  
Setpoint  
-40 °F to 266 °F  
(-40 °C to 130 °C)  
Slave enable Slave  
ModBUS slave  
34  
36  
Time of day -40 °F to 266 °F  
setpoint  
(-40 °C to 130 °C)  
Disabled  
4 ma water  
-40 °F to 266 °F  
Slave mode Use first  
Use last  
temperature (-40 °C to 130 °C)  
20 ma water -40 °F to 266 °F  
temperature (-40 °C to 130 °C)  
Equalize run time  
Base load  
rate  
0–6000 rpm  
0–8  
Outdoor  
reset  
Enabled  
Disabled  
Slave  
Priority  
source  
DHW heat demand  
Disabled  
38  
39  
37  
37  
sequence  
order  
Priority  
method  
Boost during priority time  
Drop after priority time  
Demand to  
firing delay  
___hour ___min ___sec  
0–12000 rpm  
DHW priority ___Hour ____Minute  
override time _____Second  
Fan rate  
during off  
cycle  
Enable  
Enabled  
Disabled  
ModBus port MB1  
MB2  
Outdoor  
setpoint  
-40 °F to 266 °F  
(-40 °C to 130 °C)  
No port  
ModBus  
address  
0–250  
Frost  
protection  
rate  
____%  
Master  
enable  
Enabled  
Disabled  
35  
36  
Enable  
Enabled  
Disabled  
40  
37  
CH setpoint -40 °F to 266 °F  
(-40 °C to 130 °C)  
Setpoint  
-40 °F to 266 °F  
(-40 °C to 130 °C)  
CH time of  
-40 °F to 266 °F  
day setpoint (-40 °C to 130 °C)  
ModBus port MB1  
MB2  
No port  
ModBus  
address  
0–250  
65-0303—05  
60  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Table 61. Configurable Parameters. (Continued)  
Table Page  
Table 61. Configurable Parameters. (Continued)  
Table Page  
Parameter  
Comment  
Sequence order  
Measured run time  
#
#
Parameter  
Comment  
#
#
Lead  
41  
37  
Method  
Error threshold  
Firing rate threshold  
Disabled  
44  
37  
selection  
method  
Lag selection Sequence order  
method Measured run time  
Detection  
time  
___Hour ____Minute  
_____Second  
Lead rotation ___day ____hour _____min  
time  
Error  
threshold  
0 °F to 234 °F  
(-17 °C to 112 °C)  
Force lead  
___day ____hour _____min  
Rate offset  
+ ________ %  
rotation time  
Interstage  
delay  
___Hour ____Minute  
_____Second  
Base load  
common  
? %  
42  
43  
37  
37  
Method  
Error threshold  
Firing rate threshold  
Disabled  
Table 62. Other Tables.  
Name  
Table #  
Page #  
10  
Detection  
time  
___Hour ____Minute  
_____Second  
4-pin Connector Terminals  
Lockout History  
Alert Log  
2
3
16  
16  
45  
45  
Error  
threshold  
0 °F to 234 °F  
(-17 °C to 112 °C)  
4
Digital I/O Data  
Analog I/O Data  
57  
58  
Rate offset  
+ ________ %  
Interstage  
delay  
___Hour ____Minute  
_____Second  
61  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
65-0303—05  
62  
M28852  
Fig. 121. S7999C front-mount template.  
63  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
65-0303—05  
64  
M28851  
Fig. 122. S7999C rear-mount template.  
65  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
65-0303—05  
66  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
67  
65-0303—05  
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE  
Automation and Control Solutions  
Honeywell International Inc.  
1985 Douglas Drive North  
Golden Valley, MN 55422  
Honeywell Limited-Honeywell Limitée  
35 Dynamic Drive  
® U.S. Registered Trademark  
Toronto, Ontario M1V 4Z9  
customer.honeywell.com  
© 2010 Honeywell International Inc.  
65-0303—05 M.S. Rev. 04-10  
Printed in U.S.A.  

Agilent Technologies 34401A User Manual
Aiwa CDC X427 User Manual
Alpine Electronics Car Stereo System CDE 101E User Manual
Baxi Potterton 33 HE User Manual
Canon ELURA 90 User Manual
Canon MD140 User Manual
Gemini XGA 5000 User Manual
Hafler SR2300CE User Manual
Jensen MCD6115 User Manual
JVC GR DVL 200 User Manual