|
INSTALLATION, OPERATING AND
SERVICE INSTRUCTIONS FOR
SCG™
GAS - FIRED BOILER
As an ENERGY STAR® Partner, Burnham Hydronics has determined that the SCG meets the ENERGY
STAR® guidelines for energy efficiency established by the United States Environmental Protection Agency (EPA).
For service or repairs to boiler, call your heating contractor. When seeking information on
boiler, provide Boiler Model Number and Serial Number as shown on Rating Label.
Boiler Model Number
Boiler Serial Number
Installation Date
SCG _ _ _ _ - _ _ _
_ _ _ _ _ _ _ _
Heating Contractor
Phone Number
Address
8140705R3-1/07
Price - $5.00
WARNING
This boiler requires regular maintenance and service to operate safely. Follow the
instructions contained in this manual.
Improper installation, adjustment, alteration, service or maintenance can cause property
damage, personal injury or loss of life. Read and understand the entire manual before
attempting installation, start-up operation, or service. Installation and service must be
performed only by an experienced, skilled, and knowledgeable installer or service agency.
This boiler must be properly vented.
This boiler needs fresh air for safe operation and must be installed so there are provisions
for adequate combustion and ventilation air.
The interior of the venting system must be inspected and cleaned before the start of the
heating season and should be inspected periodically throughout the heating season for any
obstructions. A clean and unobstructed venting system is necessary to allow noxious
fumes that could cause injury or loss of life to vent safely and will contribute toward
maintaining the boiler's efficiency.
Installation is not complete unless a pressure relief valve is installed into the tapping
located on top of appliance. - See the Water Piping and Trim Section of this manual for
details.
This boiler is supplied with safety devices which may cause the boiler to shut down and not
re-start without service. If damage due to frozen pipes is a possibility, the heating system
should not be left unattended in cold weather; or appropriate safeguards and alarms should
be installed on the heating system to prevent damage if the boiler is inoperative.
This boiler contains very hot water under high pressure. Do not unscrew any pipe fittings
nor attempt to disconnect any components of this boiler without positively assuring the
water is cool and has no pressure. Always wear protective clothing and equipment when
installing, starting up or servicing this boiler to prevent scald injuries. Do not rely on the
pressure and temperature gauges to determine the temperature and pressure of the boiler.
This boiler contains components which become very hot when the boiler is operating. Do
not touch any components unless they are cool.
Boiler materials of construction, products of combustion and the fuel contain alumina, silica,
heavy metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful
substances which can cause death or serious injury and which are known to the state of
California to cause cancer, birth defects and other reproductive harm. Always use proper
safety clothing, respirators and equipment when servicing or working nearby the appliance.
Failure to follow all instructions in the proper order can cause personal injury or death.
Read all instructions, including all those contained in component manufacturers manuals
which are provided with the boiler before installing, starting up, operating, maintaining or
servicing.
Keep boiler area clear and free from combustible materials, gasoline and other flammable
vapors or liquids.
All cover plates, enclosures and guards must be in place at all times.
NOTICE
This boiler has a limited warranty, a copy of which is printed on the back of this manual.
It is the responsibility of the installing contractor to see that all controls are correctly installed
and are operating properly when the installation is complete.
3
Table of Contents
I. Pre-Installation............................... 6
VI. Electrical....................................... 53
VII. Modular Installation .................... 62
VIII. System Start-up ............................ 64
IX. Service .......................................... 68
X. Repair Parts.................................. 74
II. Unpack Boiler ................................ 7
III. Venting/Air Intake Piping .............. 8
IV. Water Piping and Trim ................. 45
V. Gas Piping.................................... 50
Figure 1: Minimum Clearances to Combustibles
4
5
I. Pre-Installation
WARNING
F. Provide combustion and ventilation air in accordance
with applicable provisions of local building codes,
or: USA - National Fuel Gas Code, NFPA 54/ANSI
Z223.1, Air for Combustion and Ventilation;
Canada - Natural Gas Installation Code, CAN/
CGA-B149.1, or Propane Installation Code, CAN/
CGA-B149.2, Venting Systems and Air Supply for
Appliances.
If you do not follow these instructions
exactly, a fire or explosion may result
causing property damage or personal
injury.
DANGER
WARNING
Do not install boiler where gasoline or other
flammable vapors or liquids, or sources of
hydrocarbons (i.e. bleaches, cleaners,
chemicals, sprays, paint removers, fabric
softeners, etc.) are used or stored.
Adequate combustion and ventilation air
must be provided to assure proper
combustion.
The following guideline is based on the National Fuel Gas
Code, NFPA 54/ANSI Z223.1.
NOTICE
1. Determine volume of space (boiler room). Rooms
communicating directly with space (through
openings not furnished with doors) are considered
part of space.
Due to the low water content of the boiler,
mis-sizing of the boiler with regard to the
heating system load will result in excessive
boiler cycling and accelerated component
failure. Burnham DOES NOT warrant
failures caused by mis-sized boiler
applications. DO NOT oversize the boiler to
the system. Modular boiler installations
greatly reduce the likelihood of boiler
oversizing.
Volume [ft³] = Length [ft] x Width [ft] x Height [ft]
2. Determine Total Input of all appliances in space.
Round result to nearest 1,000 Btu per hour (Btuh).
3. Determine type of space. Divide Volume by Total
Input.
a. If result is greater than or equal to 50 ft³ per
1,000 Btuh, space is considered an unconfined
space.
A. Installation must conform to the requirements of the
authority having jurisdiction. In the absence of such
requirements, installation must conform to the National
Fuel Gas Code, NFPA 54/ANSI Z223.1, and/or CAN/
CGA B149 Installation Codes.
b. If result is less than 50 ft³ per 1,000 Btuh, space
is considered a confined space.
4. Determine building type. A building of unusually
tight construction has the following characteristics:
a. Walls and ceiling exposed to outside atmosphere
have a continuous water vapor retarder with a
rating of 1 perm or less with openings gasketed
and sealed, and;
B. Appliance is design certified for installation on
combustible flooring. Do not install boiler on
carpeting.
b. Weather-stripping has been added on openable
windows and doors, and;
C. Provide clearance between boiler jacket and
combustible material in accordance with local fire
ordinance. Refer to Figure 1 for minimum listed
clearance from combustible material. Recommended
service clearance is 24 inches from left side, right
side and front. Service clearances may be reduced to
minimum clearances to combustible materials.
c. Caulking or sealants applied in joints around
window and door frames, between sill plates and
floors, between wall-ceiling joints, between wall
panels, at plumbing and electrical penetrations,
and at other openings.
5. For boiler located in an unconfined space in a
building of other than unusually tight construction,
adequate combustion and ventilation air is normally
provided by fresh air infiltration through cracks
around windows and doors.
D. Install on level floor. For basement installation provide
solid base such as concrete, if floor is not level or if
water may be encountered on floor around boiler. Floor
must be able to support weight of boiler, water and all
additional system components.
E. Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during boiler operation
and service (circulator replacement, condensate trap,
control replacement, etc.).
6
c. Horizontal ducts. Minimum free area of one (1)
square inch per 2,000 Btu per hour input of all
equipment in space. Duct cross-sectional area
shall be same as opening free area.
NOTICE
Boilers operated with direct vent (sealed
combustion) are exempt from needing
provisions for combustion air from the
room, provided air intake piping is installed
per code and the instructions in this
manual.
Alternate method for boiler located within
confined space. Use indoor air if two permanent
openings communicate directly with additional
space(s) of sufficient volume such that combined
volume of all spaces meet criteria for unconfined
space. Size each opening for minimum free area
of one (1) square inch per 1,000 Btu per hour
input of all equipment in spaces, but not less than
100 square inches.
6. For boiler located within unconfined space in building
of unusually tight construction or within confined
space, provide outdoor air through two permanent
openings which communicate directly or by duct
with the outdoors or spaces (crawl or attic) freely
communicating with the outdoors. Locate one opening
within twelve (12) inches of top of space. Locate
remaining opening within twelve (12) inches of bottom
of space. Minimum dimension of air opening is three
(3) inches. Size each opening per following:
7. Combustion Air/Ventilation Duct Louvers and
Grilles. Equip outside openings with louvers to
prevent entrance of rain and snow, and screens to
prevent entrance of insects and rodents. Louvers and
grilles must be fixed in open position or interlocked
with equipment to open automatically before burner
operation. Screens must not be smaller than ¼ inch
mesh.
a. Direct communication with outdoors. Minimum
free area of one (1) square inch per 4,000 Btu per
hour input of all equipment in space.
Consider the blocking effect of louvers, grilles and
screens when calculating the opening size to provide
the required free area. If free area of louver or grille
is not known, assume wood louvers have 20-25
percent free area and metal louvers and grilles have
60-75 percent free area.
b. Vertical ducts. Minimum free area of one (1)
square inch per 4,000 Btu per hour input of all
equipment in space. Duct cross-sectional area
shall be same as opening free area.
CAUTION
If using indoor air for combustion (see Venting Section - Indoor Air), avoid operating this boiler in an
environment where saw dust, loose insulation fibers, dry wall dust, etc. are present. If boiler is
operated under these conditions, the burner interior and ports must be cleaned and inspected daily
to insure proper operation.
II. Unpack Boiler
WARNING
CAUTION
Installation of this boiler should be
undertaken only by trained and skilled
personnel from a qualified service agency.
Do not drop boiler. Do not bump boiler
jacket against floor.
A. Move boiler to approximate installed position.
E. Tilt the boiler to its front side or back side and slide a
wooden slat under the three raised feet.
B. Remove all crate fasteners.
F. Tilt the boiler in the opposite direction and slide
C. Lift and remove outside container. Save two of the
wooden slats from the container sleeve for use in Steps
E and F.
another wooden slat under the three raised feet.
G. Slide the boiler left or right off the skid using the two
wooden slats as runners.
D. Remove all boiler hold-down fasteners.
H. Move boiler to its permanent location.
7
III. Venting / Air Intake Piping
WARNING
Do not use this boiler with galvanized, Type 304 or Type 316 stainless steel, non metallic or
any other non AL29-4C® based vent systems.
Do not use a barometric damper or drafthood with this appliance.
Do not use vent dampers with this boiler.
Moisture and ice may form on surfaces around termination. To prevent deterioration,
surfaces should be in good repair (sealed, painted, etc.).
This appliance needs fresh air for safe operation and must be installed so there are
provisions for adequate combustion and ventilation air.
Do not reduce size of air intake pipe.
Read, understand and follow combustion air instruction restrictions contained in the Pre-
Installation instructions of this manual.
Do not operate appliance where gasoline or other flammable vapors or liquids, or sources of
hydrocarbons (i.e. bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners,
etc.) are used, stored and/or present in the air.
When installing vent pipe through chimney, no other appliance can be vented into the
chimney.
Do not exceed maximum vent/air intake lengths. Refer to Table 4.
Table 1: Air Intake / Vent System Options
Installation
Additional
Part
Number
Drawing and
Specification
(See Section)
Option
Description
Vent Kit
Required
Direct Vent (sealed combustion) with both the vent
pipe and air intake pipe terminating horizontally
(through a sidewall) with individual penetrations for
the vent and air intake piping and terminals.
1. Separate
Horizontal
See
Table 2
No
No
D.
E.
F.
Direct Vent (sealed combustion) with both the vent
pipe and air intake pipe terminating vertically
(through the roof) with individual penetrations for
the vent and air intake piping and terminals.
2. Separate
Vertical
See
Table 2
Direct Vent (sealed combustion) with the vent pipe
3. Combination and air intake pipe joining at a common terminal
3 - 6 Section
(61106012)
Yes
Horizontal
and terminating horizontally (through a sidewall up
to 15" thick) with only one penetration.
Direct Vent (sealed combustion) with the vent pipe
4. Combination and air intake pipe joining at a common terminal
3 - 4 Section
(100222-01)
5 - 6 Section
(100223-01)
Yes
No
No
G.
H.
I.
Vertical
and terminating vertically (through the roof) with
only one penetration.
Power Vent - Air used for combustion is provided
from within the building.
5. Indoor Air
See Table 2
Direct Vent (sealed combustion) with both the vent
pipe and air intake pipe terminating horizontally
(through a sidewall) with individual penetrations for
the vent and air intake piping and terminals.
6. Optional
Separate
See Table 2
Horizontal
8
Table 2: Vent System Components Included with Boiler
Vent System Components
Part Number
8110701
Gasketed Vent Terminal 3"
Horizontal (SCG-3 thru SCG-7)
Gasketed Vent Terminal 4"
Horizontal (SCG-8 & SCG 9)
8110702
6116045
6116049
6116063
Disc Air Intake - 3"
(SCG-3 & SCG-4)
Disc Air Intake - 4"
(SCG-5 & SCG-6)
Air Intake - 5"
(SCG-7 thru SCG-9)
Table 3: Burnham Vent System and Air Intake System Components
Vent System
Component
Part
Number
Equivalent
Feet of Pipe
3" Dia. Pipe x 1 Ft
8116296U
100176-01
8116298U
100177-01
8116300U
100178-01
8116319U
1
3
5
4" Dia. Pipe x 1 Ft
3" Dia. Pipe x 3 Ft
4" Dia. Pipe x 3 Ft
3" Dia. Pipe x 5 Ft
4" Dia. Pipe x 5 Ft
3" Dia. Pipe x Adjustable
Intake System
Components
(Parts by Others)
Equivalent
Feet of Pipe *
3", 4", or 5" ID Pipe x 1 Ft
3", 4", or 5" ID Pipe x 2 Ft
3", 4", or 5" ID Pipe x 4 Ft
3", 4", or 5" ID Pipe x 5 Ft
3", or 4" 90° Elbow
1
2
4
5
5
5
6
6
**Equal to
Installed Length
(1.06 to 1.64)
4" Dia. Pipe x Adjustable
3" Dia. 90° Elbow
100179-01
8116294U
100180-01
8116292U
100181-01
8166302U
100182-01
8116304U
100183-01
8116116
5
5
4" Dia. 90° Elbow
3", or 4" 45° Elbow
3" Dia. 45° Elbow
4" Dia. 45° Elbow
5" 90° Elbow
3" Dia. Horizontal Drain Tee
4" Dia. Horizontal Drain Tee
3" Dia. Vertical Drain Tee
4" Dia. Vertical Drain Tee
3" Single Wall Thimble
4" Single Wall Thimble
3" Double Wall Thimble
4" Double Wall Thimble
5" 45° Elbow
7½
7½
---
---
* Equivalent Feet of Pipe Based on
Standard 4" Smoke Pipe Design
100184-01
8116115
100185-01
Table 4: Vent/Air Intake Length
3" Air Intake Pipe 4" Air IntakePipe 5" Air IntakePipe
(Equiv. Ft.) (Equiv. Ft.) (Equiv. Ft.)
3" Vent Pipe
(Equiv. Ft.)
4" Vent Pipe
(Equiv. Ft.)
Model
Min. Max. Min. Max. Min. Max.
50 ---- ---- ---- ----
Min.
8
Max.
50
Min.
----
----
----
8
Max.
----
----
SCG-3 & SCG-4
SCG-5 & SCG-6
SCG-7
8
----
----
----
----
----
----
8
50
----
----
----
8
----
50
40
8
50
----
----
8
50
----
40
SCG-8 & SCG-9
8
----
----
9
A. Vent Guidelines Due to Removal of an Existing
Boiler
B. General Guidelines
1. Vent system installation must be in accordance
with National Fuel Gas Code, NFPA 54/ANSI
Z221.3 or applicable provisions of local building
codes. Contact local building or fire officials about
restrictions and installation inspection in your area.
For installations not involving the replacement of an
existing boiler, proceed to Step B.
When an existing boiler is removed from a common
venting system, the common venting system is likely
to be too large for proper venting of the remaining
appliances. At the time of removal of an existing
boiler, the following steps shall be followed with each
appliance remaining connected to the common venting
system placed in operation, while the other appliances
remaining connected to the common venting system are
not in operation:
2. The SCG is designed to be installed as either
a Direct Vent boiler or Power Vent boiler. In
the Direct Vent configuration all of the air for
combustion is supplied directly to the burner
enclosure from outdoors and flue gases are vented
directly outdoors (through wall or roof). In the
Power Vent configuration, room air provides air
for combustion and ventilation. Flue gases are still
vented directly outdoors (through wall or roof).
Note: Venting requirements change if indoor air is
used.
1. Seal any unused openings in the common venting
system.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion, and other
deficiencies which could cause an unsafe condition.
3. Refer to the appropriate drawings in this section of
this manual to determine the proper configuration of
venting system. See Table 1.
3. Insofar as is practical, close all building doors and
windows and all doors between the space in which
the appliances remaining connected to the common
venting system are located and other spaces of the
building. Turn on clothes dryers and any appliance
not connected to the common venting system.
Turn on any exhaust fans, such as range-hoods and
bathroom exhausts, so they will operate at maximum
speed. Do not operate a summer exhaust fan. Close
fireplace dampers.
4. This appliance requires a Special Gas Vent. The
product is designed to use Burnham supplied
AL 29-4C® Stainless Steel vent system components.
The following manufacturers offer similar
AL 29-4C® components and are approved for use
with this product. Heat-Fab Inc. - Saf-T-Vent, Flex-L
International Inc. - Star-34, Z-Flex U. S., Inc. -
Z-Vent, and Protech Systems , Inc.- FasNSeal™ or
equivalent. The use of these alternate manufacturer’s
venting systems will require adapters to connect
to the Burnham supplied vent connector and vent
terminal. These adapters are not supplied with this
unit and should be obtained from the supplier of
the alternate manufacturer’s venting system. See
Table 3 for complete list of Burnham Vent System
Components.
4. Place in operation the appliance being inspected.
Follow the Lighting (or Operating) Instructions.
Adjust thermostat so appliance will operate
continuously.
5. Test for spillage at the draft hood relief opening
after five (5) minutes of main burner operation. Use
the flame of a match or candle, or smoke from a
cigarette, cigar or pipe.
5. Horizontal vent pipe must maintain a minimum ¼
inch per foot slope down towards boiler.
6. After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers and
any other gas burning appliance to their previous
conditions of use.
6. Use noncombustible ¾ inch pipe strap to support
horizontal runs and maintain vent location and
slope while preventing sags in pipe. Do not restrict
thermal expansion or movement of vent system.
Maximum support spacing is five (5) feet. Do not
penetrate any part of the vent system with fasteners.
7. Any improper operation of the common venting
system should be corrected so the installation
conforms with the National Fuel Gas Code, NFPA
54/ANSI Z223.1. When resizing any portion of the
common venting system, the common venting
system should be resized to approach the minimum
size as determined using the appropriate tables in
Part II in the National Fuel Gas Code, NFPA 54/
ANSI Z223.1.
7. Vent length restrictions are based on equivalent
length of vent/air pipe (total length of straight
pipe plus equivalent length of fittings). Maximum
vent/air lengths are listed in Table 4. Do not exceed
maximum vent/air intake lengths. Table 3 lists
equivalent lengths for fittings. Do not include vent/
air terminals in equivalent feet calculations.
8. Provide and maintain vent pipe minimum clearances
to combustible materials. Vent pipe minimum
clearance to combustible material is four (4) inches
when vent is installed in a fully enclosed (chase)
application or three (3) inches when vent is installed
10
11. Plan venting system to avoid possible contact with
plumbing or electrical wires. Start at vent connector
on top of boiler and work towards vent terminal.
with at least one side open, similar to a joist bay
application. Use double wall thimble [Burnham
Part No. 8116115 (3”), 100185-01 (4”)] when
penetrating a combustible wall.
12. Once a vent pipe manufacturer and system is chosen
never mix and match vent systems.
9. Do not install venting system components on
the exterior of the building except as specifically
required by these instructions. The vent termination
location is restricted as follows:
13. If a non-standard length pipe is required:
Gasketed Vent System: The use of the adjustable
length pipe (P/N 8116319U) is recommended to
complete a non-standard pipe length. This pipe
requires a minimum installed length of 12¾ inch
and can adjust across a 7 inch gap up to a maximum
of 19¾ inch long. (Note for the adjustable pipe
the installed length should be measured from the
centerline of the bead on the male end of the first
pipe to the end of the female pipe excluding the
locking band of the second pipe with a single
gasket.) Only in the event the adjustable length pipe
is not sufficient a standard length pipe may be cut
using the procedure outlined below for the Gasket-
Less Vent System.
a. Minimum twelve (12) inches above grade plus
normally expected snow accumulation level, or
seven (7) feet above grade if located adjacent
to public walkway. Do not install over public
walkway where local experience indicates
appliance flue gas vapor or condensate creates a
nuisance or hazard.
b. Minimum three (3) feet above any forced air
inlet located within ten (10) feet.
c. Direct Vent - Minimum one (1) foot below, one
(1) foot horizontally from, or one (1) foot above
any door, window, or gravity air inlet.
Power Vent - Minimum four (4) feet below, four
(4) feet horizontally from, or four (4) feet above
any door, window, or gravity air inlet.
WARNING
Never exceed maximum installed length of
19¾ inches for adjustable length pipe.
Risk of flue gas leakage is possible.
d. Minimum four (4) feet horizontally from electric
meters, gas meters, regulators, and relief valves.
This distance may be reduced if equipment is
protected from damage due to condensation or
vapor by enclosure, overhangs, etc.
NOTICE
e. Minimum twelve (12) inches from overhang or
corner of building.
Cut must be square with pipe and filed or
sanded smooth before joining. Carefully
ensure roundness of cut pipe by hand with
gloves before installing. Seal joint with RTV
specified in this manual.
10. Enclose vent passing through occupied or
unoccupied spaces above the boiler with material
having a fire resistance rating of at least equal to the
rating of the adjoining floor or ceiling. Maintain
minimum clearances to combustible materials. See
Figure 1.
C. Install Vent Pipe, Burnham Gasketed Vent System.
1. Procedure for Joining Burnham Gasketed Vent Pipe
and Fittings. See Figure 3.
Note: For one or two family dwellings, fire
resistance rating requirement may not need to be
met, but is recommended.
Figure 3: Burnham Gasketed Vent Joint Detail
11
a. Wipe the male end of each joint using an alcohol
pad to remove any dirt and grease.
8. Locate air intake termination on the same wall as
the vent termination if possible, to prevent nuisance
boiler shutdowns. However, boiler may be installed
with vertical venting and sidewall combustion air
inlet or visa versa, if installation conditions do not
allow alternate arrangement.
b. Align weld seams in pipes and use a slight
twisting motion to FULLY insert male end into
female end of joint. Ensure bead in male end
of pipe is below locking band and rest against
the end of the female pipe. Verify the factory-
installed gasket is not dislodged or cut.
9. Do not exceed air intake length. See Table 4.
10. Use single wall metal or PVC pipe.
c. Tighten locking band by HAND with a 5/16”
nut driver until snug plus ¼ turn. DO NOT
SECURE JOINTS WITH SHEET METAL
SCREWS OR POP RIVETS. DO NOT
PUNCTURE THE VENT SYSTEM!
a. Air intake pipe diameter is based on boiler size.
SCG-3 & SCG-4 uses 3 inch diameter piping.
SCG-5 & SCG-6 uses 4 inch diameter piping.
SCG-7 thru SCG-9 uses 5 inch diameter piping.
d. Once the installation is complete, operate
appliance and inspect all joints to ensure that flue
gases and/or liquid condensate will not escape.
11. Air intake termination must be located:
Horizontal - At least twelve (12) inches above
grade plus the expected snow accumulation.
D. Separate Horizontal Venting System. See Figures 4,
12. Start at collar on burner enclosure (inside boiler
jacket) and work towards the air intake terminal.
5A and 5B.
Vent Piping –
13. Maintain minimum of ¼ inch per foot slope on
horizontal runs. Slope towards air inlet terminal
when possible. If not, slope towards boiler.
1. This boiler is supplied with components as standard
equipment for installation of the separate horizontal
venting system.
14. The air intake pipe must be adequately supported
with straps or supports no less than five (5) feet
apart on horizontal runs. The complete air intake
piping system must be rigid and able to withstand
minor impacts without collapse.
2. Do not exceed maximum vent/air intake lengths.
Refer to Table 4.
3. Recommended horizontal installation consists of
vent being sloped down ¼ inch per foot away from
boiler. See Figure 4.
15. Inlet air pipe penetration:
4. Use appropriate designed thimbles when passing
through combustible walls (thimble use optional for
noncombustible walls). Insert thimble through wall
from outside. Secure outside flange to wall with
nails or screws, and seal ID, OD and vent holes with
sealant material. Install inside flange to inside wall,
secure with nails or screws, and seal with sealant
material.
Horizontal - Size wall penetration to allow easy
insertion of air inlet piping. Seal around pipe with
sealant to form weathertight exterior joint.
16. Seal all joints airtight, using silicone caulk or self-
adhesive aluminum tape.
17. Install Air Intake Terminal:
Horizontal - Remove four (4) screws from cover
plate and remove cover plate from terminal. Insert
intake piping into intake terminal collar. Secure
terminal to intake piping and seal joint with silicone
caulk or self-adhesive aluminum tape. Apply
continuous bead of silicone caulk around the back
of the intake terminal, approximately ¼ inch from
its edge. Push inlet terminal inward until terminal’s
back flange is against the wall surface. Secure the
terminal with noncorrosive fasteners (stainless steel,
brass or aluminum) to the wall. Reinstall the cover
plate with four (4) screws. Apply a bead of silicone
caulk to perimeter of intake terminal’s back flange
to provide a weathertight seal.
5. For noncombustible wall application when thimble
is not used, size opening such that bell with locking
band attached cannot pass through.
6. Join vent terminal to vent pipe. See Figures 5A and
5B.
7. Insert vent pipe through thimble/opening from
outside and join to vent system. Apply sealant
between vent pipe and opening/thimble to provide
weathertight seal.
Air Intake piping - See Figures 4, 5A and 5B.
12
13
14
15
16
E. Separate Vertical Venting System - See Figures 6, 7, 8A, 8B and 9.
NOTICE
Roof penetrations require the use of roof
flashing and storm collar - not supplied with
boiler.
Vertical Venting –
8. Locate air intake termination on the same roof
location as the vent termination if possible, to
prevent nuisance boiler shutdowns. However, boiler
may be installed with vertical venting and sidewall
combustion air inlet or visa versa, if installation
conditions do not allow alternate arrangement.
1. Do not exceed maximum vent lengths. Refer to
Table 4.
2. Installation of a vertical vent tee 8116304U is
required on all vertical vent applications. See
Figures 6 and 7. Attach vertical vent drain tee
directly to elbow or horizontal pipe from an elbow
immediately after vent connector.
9. Use single wall metal pipe or PVC and fittings
available at most heating distributors.
a. Air intake pipe diameter is based on boiler size.
3. Slope horizontal runs minimum ¼ inch per foot.
Slope towards vertical vent drain tee. Position weld
seams in vent pipes, in all horizontal runs, at the top
to avoid condensate from lying on the seams.
SCG-3 & SCG-4 uses 3 inch diameter piping.
SCG-5 & SCG-6 uses 4 inch diameter piping.
SCG-7 thru SCG-9 uses 5 inch diameter piping.
4. Install fire stops where vent passes through floors,
ceilings or framed walls. The fire stop must close
the opening between the vent pipe and the structure.
10. Air intake termination must be located:
Vertical - At least twelve (12) inches above the roof
surface plus the expected snow accumulation.
5. Whenever possible, install vent straight through
the roof. Refer to Figure 7 if offset is necessary.
Maintain minimum clearance to combustible
materials.
11. Start at collar on burner enclosure (inside boiler
jacket) and work towards the air intake terminal.
12. Maintain minimum of ¼ inch per foot slope on
horizontal runs. Slope down towards boiler.
6. Install Vent Terminal.
13. The air intake pipe must be adequately supported
with straps or supports no less than five (5) feet
apart on horizontal runs. The complete air intake
piping system must be rigid and able to withstand
minor impacts without collapse.
a. Size roof opening to maintain minimum
clearance from combustible materials.
b. Extend vent pipe to maintain minimum vertical
and horizontal distance of twelve (12) inches
from roof surface. Allow additional vertical
distance for expected snow accumulation.
Provide brace as required. Refer to Figures 8A
and 8B.
14. Inlet air pipe penetration:
Vertical - Size roof opening to allow easy insertion
of inlet piping and allow proper installation of
flashing and storm collar.
NOTICE
a. Use appropriately designed vent flashing
when passing through roofs. Follow flashing
manufacturers’ instructions for installation
procedures. Flashing manufacturers are Air-
Jet, American Metal Products, Metal Fab, and
Simpson Dura-Vent.
Vertical venting requires the use of roof
flashing and a storm collar to prevent
moisture from entering the structure.
c. Install storm collar on vent pipe immediately
above flashing. Apply Dow Corning Silastic 732
RTV Sealant between vent pipe and storm collar
to provide weathertight seal.
b. Extend air intake pipe to maintain minimum
vertical and horizontal distance of twelve
(12) inches from roof surface. Allow
additional vertical distance for expected snow
accumulation. Provide brace as required. Refer
to Figures 8A and 8B.
d. Attach vent terminal.
Vertical Air Intake Piping –
7. Do not exceed maximum air intake length. Refer to
Table 4.
c. Vertical air intake requires flashing and a storm
collar to prevent moisture from entering the
structure.
17
d. Install storm collar on air intake pipe
immediately above flashing. Apply Dow
Corning Silastic 732 RTV Sealant between
air intake pipe and storm collar to provide
weathertight seal.
15. Seal all joints airtight, using silicone caulk or self-
adhesive aluminum tape.
16. Install Air Intake Terminal:
Vertical - Insert intake piping into intake terminal
collar. Secure terminal to intake piping and seal
joint with silicone caulk.
e. All exposed air intake piping must be
constructed of corrosion resistant material such
as aluminum, stainless steel or PVC.
18
19
20
21
Figure 9: Vertical Air Intake Piping
22
F. Combination Horizontal Venting System –SCG-3 Through SCG-6 ONLY – See Figures 10 and 11.
1. Do not exceed maximum vent/air intake lengths.
Refer to Table 4.
NOTICE
This vent system requires components not
supplied with the boiler.
2. Install Combination Vent/Air Terminal. See Figure 11.
a. After determining the location with reference to Section B - General Venting Guidelines, cut a 6-1/8 inch square
opening in the wall for the air box sub-assembly which is 6 inch square.
b. Remove and save shipping screw from end panel with collar and vent pipe assembly. This will be reinstalled in a later
step.
Vent Carton Part Number 61106012 (includes items below)
Description
Component Part Number
61106011
A
B
C
D
E
F
Air Box Sub-Assembly (6" square x 2' long)
Exterior Wall Cover (10" square)
71106016
4" x 3" Vent Pipe Reducer
8116239
Plate-Seal Exterior Cover (2)
71106017
#8 x ½" Stainless Steel Sheet Metal Screw (19)
#10 - 32 x ¼" Stainless Steel Machine Screw (8)
#10 - 32 x ½" Aluminum Spacer (4)
80860047
80860842
G
80861617
COMBINATION HORIZONTAL VENT SYSTEM COMPONENTS
23
c. From exterior of building, insert air box sub-
assembly into square opening. Push air box
inward until wall flange is against wall, check
for level and mark the location of the four (4)
securing holes on the exterior wall. Remove air
box from wall.
3. Install Vent Piping. See Figure 10 and 11.
a. Start at vent connector on boiler and work
towards combination vent/air terminal.
b. Installation of a vertical vent tee 8116304U is
required on all vertical vent applications. See
Figures 12 and 13. Attach vertical vent drain
tee directly to elbow or horizontal pipe from an
elbow immediately after vent connector.
d. Drill four (4) pilot holes, properly sized for the
non-corrosive fasteners (stainless steel, brass, or
aluminum) to be used to secure the wall flange to
the exterior wall. (Securing screws not supplied
with kit.)
c. Slope horizontal runs minimum ¼ inch per foot.
Slope towards vertical vent drain tee. Position
weld seams in vent pipes, in all horizontal runs,
at the top to avoid condensate from lying on the
seams.
e. Attach four (4) 1/2 inch long threaded aluminum
spacers to the outer flanges of the exterior
wall flange with four (4) number 10 - 32 x 1/4
inch stainless steel machine screws provided.
(See Figure 11.)
d. Use 3/4 inch pipe strap to support horizontal runs
and maintain vent location and slope. Maximum
support spacing is five (5) feet.
f. Apply a 1/4 inch thick continuous bead of
silicone caulk to perimeter of exterior wall
flange’s back surface to provide a weathertight
seal.
e. Install vent piping to connect vent connector
on boiler and combination vent/air terminal.
Reference Section B - General Venting
Guidelines for proper procedure for joining pipe
and fittings.
g. Reinstall air box sub-assembly into opening in
exterior wall and secure to wall.
f. Connect vent piping to combination vent/air
terminal. See Figure 10.
WARNING
4. Install Air Intake Piping. See Figures 10 and 11.
a. Do not exceed air intake length. See Table 4.
Non-corrosive fasteners must be used.
b. Use single wall metal pipe or PVC and fittings
h. Apply a bead of silicone caulk to perimeter of
wall flange, where the wall and flange join. Use
a tool or your finger and apply pressure while
smoothing caulking to provide a weathertight
seal.
available at most heating distributors.
c. Air intake pipe diameter is based on boiler size.
SCG-3 & SCG-4 uses 3 inch diameter piping.
SCG-5 & SCG-6 uses 4 inch diameter piping.
SCG-7 thru SCG-9 uses 5 inch diameter piping.
i. From interior of building, insert end panel with
collar and vent pipe assembly into open end of
air box sub-assembly. (See Figure 11.)
d. Start at collar on burner enclosure (inside boiler
jacket) and work towards the combination vent/
air terminal.
j. Secure end panel to air box sub-assembly with
shipping screw and thirteen (13) number 8 sheet
metal screws provided.
e. Maintain minimum of 1/4 inch per foot slope on
horizontal runs. Slope down towards boiler.
k. From exterior of building, position 10 inch
square exterior wall cover over exterior wall
flange. Insert 3 inch diameter vent pipe into
center opening in terminal cover. Align four
(4) holes on cover with 1/2 inch long threaded
spacers on wall flange. Secure terminal cover
with four (4) number 10 - 32 x 1/4 inch stainless
steel machine screws provided.
f. The air intake pipe must be adequately supported
with straps or supports no less than five (5)
feet apart on horizontal runs. The complete air
intake piping system must be rigid and able to
withstand minor impacts without collapse.
g. Connect Air Intake Piping to Combination Vent/
Air Terminal. See Figure 10.
l. Apply a bead of silicone caulk to perimeter of
plate-seal and around pipe. Secure plate-seal to
exterior cover with six (6) #8 stainless steel sheet
metal screws provided. Smooth caulk around
plate-seal and pipe to provide weathertight seal.
NOTE: When installing 3 inch diameter air intake
piping for a SCG-3 or SCG-4 application, the use of
a 4 inch x 3 inch reducer will be required to connect
air intake piping to combination vent/air terminal.
(Reducer included with combination horizontal
venting kit).
m. Install Vent Terminal supplied with boiler to vent
pipe penetrating through terminal cover. Join
terminal and pipe with locking band and seal
with RTV (see Figure 3).
h. Seal all joints airtight, using silicone caulk or
self-adhesive aluminum tape.
24
25
26
G. Combination Vertical Venting System – SCG-3 Through SCG-6 ONLY – See Figures 12, 13 and 14.
NOTICE
This vent system requires components not
supplied with the boiler.
Part Number
SCG-5 & SCG-6
Description
SCG-3 & SCG-4
100222-01
Vent Carton Part Number
Starter Tee
100223-01
100225-01
100224-01
Vent/Air Adaptor
100226-01
COMBINATION VERTICAL VENT SYSTEM COMPONENTS
27
1. Saf-T Vent SC is an advanced concentric vent
system designed for zero clearance installation
in residential applications. The inner wall is
constructed from superferritic AL29-4C® stainless
steel. The outer wall is also constructed from
stainless steel, providing durability and a lasting
finish.
the system in place. A continuous straight-line
pitch of at least ¼” (2°) to the foot on horizontal
runs must be maintained in order to properly rid
the system of the corrosive condensate.
5. General Installation Requirements:
•
Saf-T Vent SC vent sections, or other Saf-T
Vent products, must be used throughout the
entire length of the system. Alternatives such
as galvanized pipe, PVC, nonmetallic pipe,
prefabricated chimney, field-fabricated vents
or Type B vent sections must not be used. Do
not mix pipes, fittings, or joining methods from
different manufacturers.
2. As a Special Gas Vent system: Saf-T Vent is
approved for use on ANSI Category I, II, III, and
IV Gas-Burning Appliances and certain Direct Vent
Appliances. Saf-T Vent SC is appropriate for use on
appliances that specify an AL29-4C venting system.
3. As a Sealed Combustion system: The unique
concentric design of Saf-T Vent SC also allows it
to function as a pipe-in-a-pipe vent. Products of
combustion are exhausted out through the inner wall
while combustion air is drawn in through the outer
wall. An appliance can be direct-vented with only
a single penetration through the building structure.
This application must be approved by the
Appliance Manufacturer.
•
•
•
More than one appliance may not be
interconnected to any part of the venting system.
Any penetrations of ceilings, floors or walls must
be properly fire-stopped.
Whenever gas-burning equipment is installed in
the same space where halogenated substances
may exist (refrigerants, solvents, bleaches,
salts, etc.), clean outside air must be utilized for
combustion.
Note: Saf-T Vent SC includes an integral seal and
does not require RTV sealant. However, sealant
may be necessary when connecting Saf-T Vent SC
components directly to certain appliance flue collars
and to the gasket-less Saf-T Vent GC and Saf-T Vent
CI vent systems.
•
•
•
The vent system shall not be routed into,
through or within any other actively used vent or
chimney.
Seal weather exposed joints of the outer jacket
with foil tape or an exterior grade silicone
sealant.
For applications up to 550°F/288°C, approved
sealants include GE RTV 106 and Dow Corning
736.
Combustible Material is any material made of
or surfaced with wood, compressed paper, plant
fibers, or other materials that are capable of
being ignited or burned. Such material shall be
considered combustible even though it is flame-
proofed, fire-retardant, or plastered. (Source:
NPFPA54/ANSI Z223.1-1999.)
For applications up to 300°F/149°C, approved
sealants include GE RTV 106 and Dow Corning
732.
4. Pre-Installation Considerations:
•
Proper planning prior to installation is essential
as to avoid possible contact with concealed
plumbing or electrical wiring inside walls,
floors or ceilings as well as maintaining proper
clearances. Be sure to plan a sufficient number
of supports for the entire system that will
•
Non-Combustible Material is any material that
is not capable of being ignited and burned, such
material consisting entirely of, or a combination
of, steel, iron, brick, tile, concrete, slate,
asbestos, glass and plaster. (Source: NPFPA54/
ANSI Z223.1-1999.)
maintain the required straight-line pitch and hold
Clearances to Combustibles:
Clearance to
Maximum Flue
Diameter Combustible
Gas Temp. (°F)
Orientation
Enclosure
Material
Vertical,
No Offsets
550
0"
Fully enclosed by combustible
material on all sides
330
Horizontal,
Vertical with
Offsets
1"
0"
1"
0"
400
400
3" - 4"
Unenclosed, at least 1 side open,
combustible material on a
maximum of 3 sides
550
550
Any
Noncombustible material
28
6. Vertical Installation Requirements:
•
For a venting system that extends through
any zone above that on which the connected
appliance is located (except for one and two
family dwellings), the vent system shall be
enclosed with an enclosure having a fire
resistance rating equal to or greater than that of
the floor or roof assemblies through which it
passes.
a. Seal weather exposed joints of the outer jacket
with foil tape or an exterior grade silicone
sealant.
b. The vent system must terminate at least 3 feet
above the roof line and at least 2 feet higher than
any portion of the building within 10 feet.
c. When terminated at a height of more than 6 feet
the stack must be supported by a support bracing.
The vent should be supported every 10 feet.
•
•
Design any enclosure to permit inspection of the
system.
Do not place any type of insulation in any
required clearance spaces surrounding the vent
system.
d. The total continuous distance of the vent system
from the appliance flue collar to the termination
shall not exceed that specified in the appliance
manufacturer’s installation instructions.
e. In cold climates do not install a condensate drain
on the exterior of the building. Doing so may
result in dangerous icy conditions on surfaces
near the drain and may cause damage to the vent
system and/or the building exterior.
f. Install supports every 10 feet vertically along the
vent pipe route. Vertical supports are required
after every transition to vertical and are required
after every offset elbow. When the vent is free
standing and penetrates a roof/ceiling another
means of support must be used at a second
location. Refer to the Vertical Supports section
in this manual.
29
7. Joint Assembly Instructions:
a. Before joining the sections or fittings together, use an alcohol pad to wipe the joint area of both ends of the inner
pipe. This will remove any foreign matter which may affect the integrity of the seal. Install the system with the
female ends (ends with the red seal) pointing away from the appliance. (Unless specified differently by the appliance
manufacturer.)
b. Insert the male end of the inner pipe into the female end of the previous section. In extremely dry conditions it may be
helpful to moisten the seal with clean water prior to assembly. Push firmly until the outer jacket has made contact with
the snap ring located inside the female end of the previous section. When fully assembled the outer female end will
overlap the male end 1”.
c. Use the three (3) self-tapping screws provided to connect the outer vents. No pre-drilling is required.
CAUTION
Do not overtighten. If using a variable torque drill, use a low torque setting to install screws, as
not to strip out the holes. If a hole becomes stripped due to overtightening, a larger diameter
screw (½" long max.) or short pot rivet can be used.
30
8. Straight Sections Cut To Length:
e. Add 3” to the distance measured previously for the
cut length of the inner vent pipe. Mark a cut line on
the inner vent on the male end (the end without the
red seal).
If a custom length of SC is necessary, a standard vent
section can be cut.
a. Measure the distance of the length needed, taking the
measurement from the end of one of the outer jackets
to the beginning of the other outer jacket on the
section to connect to, (A to B on diagram).
The inner pipe is always cut 1” longer than the
outer pipe.
f. WEAR GLOVES, as cut ends are very sharp. Cut
the pipes with an abrasive cutoff saw, plasma cutter,
or compound snips. If using snips, start the cut at
the male end and follow a spiral path around the pipe
until the cutoff mark is reached. File off any burrs
or rough edges that develop in the cutting process
and clean off any dust or grit. If the cutting process
distorts the roundness of the pipes, carefully use your
thumbs to re-round the ends.
b. Select a section that is longer than the required
length.
c. It will be necessary to disassemble the vent prior to
cutting.
Stand the section on end with the holes up. Find the
end of snap ring and pry it out of its groove, being
careful not to damage the ends of the vent pipes.
Pull up on end of the snap ring and pull it out from
the end of the pipe. It may want to spiral out as it is
removed. After the snap ring is removed, the inner
vent pipe can be separated from the outer jacket.
g. Reassemble the inner vent into the outer jacket and
reinstall the snap ring into the groove. Push the
inner vent into the outer jacket until the triangle on
the inner vent is seated firmly against the bead on
outer jacket. Start one end of the snap ring into the
groove of the outer pipe. Slowly turn and feet the
snap ring into the groove in a spiral motion, and
continue around the pipe until the snap ring is fully
inserted. Ensure that the triangle on the inner vent is
all the way down against the bead of the outer jacket
by pushing in firmly. Also ensure that the snap ring
is completely in the groove all the way around outer
jacket.
d. Add 2” to the distance measured previously for the
cut length of the outer jacket. Mark a cut line on the
outer jacket on the male end (the end without holes in
it).
An effective way of marking is to run a length of tape
around the section, assuring a square cut.
31
9. Air Intake Connections for Direct Vent and Sealed
Combustion Appliances*:
The Air Intake Tee may be used on approved direct vent
and sealed combustion appliances that have separate (non-
concentric) air intake and flue exhaust collars. The male end
of the tee connects to EZ Seal appliance adapters and the tee
takeoff/snout connects to the appliance air intake.
•
•
•
Insert the male end of the Air Intake Tee into the female
end of the EZ Seal vent section or appliance adapter and
complete the ring and tab connection.
Insert the male end of the next SC section into the female
end of the Air Intake Tee and secure as described elsewhere
in this manual.
Connect the tee takeoff to the appliance combustion air inlet
using appropriate hose or pipe.
*
Direct Vent Appliances are constructed and installed so that
all air for combustion is supplied directly from the outside
atmosphere. The passage for the combustion air is allowed
a small amount of leakage in the building environment. No
special installation considerations are required to use Saf-T
Vent SC on Direct Vent appliances unless specified by the
appliance manufacturer. Sealed Combustion appliances are
similar to Direct Vent except the combustion air passage must
be sealed to prevent leakage within the building envelope.
When Saf-T Vent SC is used on approved Sealed Combustion
appliances the joints of the outer jacket must be sealed with
a foil tape (example: 3M 425), or approved silicone sealant
(example: Dow Corning 732).
10. Condensate Drains:
When An Internal Condensate Drain is NOT Part of the
Appliance:
•
A Saf-T Vent SC In-Line Drain Section is strongly
recommended. Install this drain fitting as close to the
appliance flue collar as possible.
•
A condensate drain is required for every 30 feet of
horizontal vent and at/near the bottom of a vertical stack.
•
Use the In-Line Drain Section for a straight horizontal or
vertical run. When used horizontally, rotate the fitting so that
the drain tube is as vertical as possible.
•
A Condensate Drain Tube Kit is available to direct the
condensate to an appropriate location, i.e. floor drain or
vented sanitary sewer connection. A trap loop must be
formed into the drain hose and must be a diameter that is
at least four (4) times the appliance’s rated stack pressure
in inches of water column or 3 inches, whichever is
greater. Secure the loop with a cable tie. Prior to final
assembly the trap loop must be ‘primed’ by pouring a
small quantity of water into the drain hose. Inspect at least
annually to verify the trap is ‘primed’.
•
•
Follow all local and national codes and regulations for the
draining of acidic condensate.
In cold climates do not install a condensate drain on the
exterior of the building. Doing so may result in dangerous
icy conditions on surfaces near the drain and may cause
damage to the vent system and/or the building exterior.
32
11. Horizontal Supports:
Saf-T Vent SC must have supports for every six (6) feet of horizontal run and after every transition from vertical to
horizontal. Support hangers by themselves do not maintain the necessary clearances to combustible materials; be sure to
consider clearances when planning the system.
The supports must be secured to solid material using at least #10 fasteners. Do not fasten supports to drywall sheathing
without using hollow wall anchors. The conduit supports must maintain the ¼” per foot pitch to avoid collection of
condensate in the vent. Position the vent so that the welded seam is on the top.
0” Clearance Support Clamp, (SC_ _SUP): Attach the bracket to the structure but do not tighten in place. Open the
hose clamp and slip it under the support bracket. Position the clamp between the mounting screws and rotate the clamp
so that the screw housing will be accessible after the vent is installed. Restart the threads on the hose clamp and securely
tighten the mounting screws to the structure. This can also be installed vertically.
1” Clearance Support Clamp, (SC_ _SUP1): Supports the vent at 1” clearance to the structure. Line up the support
mounting brackets so that the mounting screws will follow the center line of the vent section. This can also be installed
vertically.
33
Support Clamp, (4_ _27SS): Support clamps are sold in pairs and can be clamped around the vent and suspended from a
rod or cable. They can be used singularly as a saddle clamp to rest the vent in and suspended from two (2) rods or cables.
Support Legs Rotated Horizontally: Support legs can be used on horizontal runs by rotating the clamp at the rivet
connection. The legs can be cut to shorter lengths if necessary.
Vertical Supports, (SC_ _VSL): Vertical support legs can be used above or below a structure for support. To install,
slide the support clamp over the end of the vent section, leaving the clamp loose. Position the support legs and install
two (2) screws through each leg into the structure. Tighten the clamp around vent pipe. The legs can be cut to shorter
lengths if necessary and can rotate around the support clamp at the rivet connection. By rotating the clamp to a horizontal
position the support legs can be used on horizontal runs.
34
Fire Stop/Wall Thimble/Support, (SC_ _FS):
•The Saf-T Vent SC Fire Stop can be used as a firestop, a wall thimble, or as a support plate.
•To use as a Wall Thimble prepare an opening according to the chart below. Remove any insulation from the opening,
using additional framing if necessary. Attach the plate over the center of the opening using appropriate fasteners.
•Install the vent section through the thimble plate and secure the section to the thimble by screwing the self-tapping
screws through the holes in the tabs on the plate and into the outer wall of the vent. Apply silicone sealant around the vent
section where it passes through the plate and around the plate where it is attached to the structure.
•To use as a Firestop before passing through ceilings or enclosed chases, prepare a round or square opening ¼” larger than
the outer jacket (5¼” for 3” vent or 7¼” for 4” vent). Remove any insulation from the opening. Secure the firestop to
the structure at the four (4) corners. Install the vent section through the firestop and secure to the thimble by screwing the
self-tapping screws through the holes in the tabs on plate and into outer wall of the vent. This method can also be used to
support the vent section either vertically or horizontally.
Tall Cone Flashing:
Directly On Roof or Curb:
Tall Cones are available for flat (SC_ _TCF), 2/12 pitch (SC_ _TCFA), and 6/12 - 12/12 pitch roofs (SC_ _TCFB).
Prepare a square or round opening at least 1/4” larger than the outer jacket (5¼” for 3” vent or 7¼” for 4” vent). Remove
any insulation from the opening. Apply weather-stripping or outdoor caulk to the bottom of the cone plate and attach the
plate to the roof using common construction methods. Flash over the cone plate and seal the fastener heads using normal
roofing requirements. When the vent pipe is in place through the Tall Cone, attach a storm collar (sold separately) around
the pipe. Apply high temperature silicone sealant around the pipe where it passes through the top of the storm collar.
Continue to install vent sections as needed to meet the height requirements by code. Seal weather exposed joints of the
outer jacket with foil tape or an exterior grade silicone sealant.
35
Vertical Terminations, (SC_ _VT): Install the vertical termination adapter into the last vent section and secure with the
three (3) self-tapping screws provided. If the exhaust termination needs to be extended, a section of EZ Seal vent can be
connected directly to the vertical termination adapter. Seal weather exposed joints of the outer jacket with foil tape or
an exterior grade silicone sealant. To allow for inspection of the system, do not seal the exhaust termination.
36
H. Indoor Air Installation – See Figures 12, 13, 14, 15 and 16.
1. Do not exceed maximum vent length. Refer to
Table 4.
Vertical –
10. Installation of a vertical vent tee 8116304U is
required on all vertical vent applications. See
Figure 6. Attach vertical vent drain tee directly to
elbow or horizontal pipe from an elbow immediately
after vent connector.
Horizontal –
2. Maintain minimum ¼ inch per foot slope in
horizontal runs.
3 Recommended horizontal installation consists of
vent being sloped down away from boiler. See
Figure 12.
11. Install fire stops where vent passes through floors,
ceilings or framed walls. The fire stop must close
the opening between the vent pipe and the structure.
Fire stop manufacturers are Air-Jet, American Metal
Products, Metal-Fab, and Simpson Dura-Vent.
4. Slope horizontal runs minimum ¼ inch per foot.
Slope towards vertical vent drain tee. Position weld
seams in vent pipes, in all horizontal runs, at the top
to avoid condensate from lying on the seams.
12. Whenever possible install vent straight through roof.
Refer to Figure 13 if offset is necessary. Maintain
minimum clearance to combustible materials.
5. Use appropriately designed thimbles when passing
through combustible walls (thimble use optional
for noncombustible walls). Insert thimble through
wall from outside. Secure outside flange to wall
with nails or screws, and seal with sealant material.
Install inside flange to inside wall, secure with nails
or screws, and seal with sealant material.
13. Install Vent Terminal.
a. Size roof opening to maintain minimum
clearance from combustible materials.
b. Use appropriately designed vent flashing
when passing through roofs. Follow flashing
manufacturers’ instructions for installation
procedures. Flashing manufacturers are Air-
Jet, American Metal Products, Metal Fab, and
Simpson Dura-Vent.
6. For noncombustible wall application when thimble
is not used, size opening such that female (bell) end
with locking band attached cannot pass through.
7. Join vent terminal to vent pipe. Locate vent
terminal between seventeen (17) inches and twenty-
nine (29) inches from wall when joined to inside
vent piping. See Figure 14.
c. Extend vent pipe to maintain minimum vertical
and horizontal distance of twelve (12) inches
from roof surface. Allow additional vertical
distance for expected snow accumulation.
Provide brace as required. Refer to Figure 15.
8. Insert vent pipe through thimble/opening from
outside and join to vent system. Apply sealant
between vent pipe and opening/thimble to provide
weathertight seal.
d. Vertical venting requires flashing and a storm
collar to prevent moisture from entering the
structure.
9. Join vent terminal to 45° elbow included in kit. Join
45° elbow/terminal assembly to vent pipe. Refer
to Section C for proper procedures for joining vent
pipe and fittings. See Figure 3 .
e. Install storm collar on vent pipe immediately
above flashing. Apply Dow Corning Silastic 732
RTV Sealant between vent pipe and storm collar
to provide weathertight seal.
f. Attach vent terminal.
14. Install supplied air intake terminal onto collar of the
jacket enclosure. See Figure 16.
37
38
|