Burnham SCG User Manual

INSTALLATION, OPERATING AND  
SERVICE INSTRUCTIONS FOR  
SCG™  
GAS - FIRED BOILER  
As an ENERGY STAR® Partner, Burnham Hydronics has determined that the SCG meets the ENERGY  
STAR® guidelines for energy efciency established by the United States Environmental Protection Agency (EPA).  
For service or repairs to boiler, call your heating contractor. When seeking information on  
boiler, provide Boiler Model Number and Serial Number as shown on Rating Label.  
Boiler Model Number  
Boiler Serial Number  
Installation Date  
SCG _ _ _ _ - _ _ _  
_ _ _ _ _ _ _ _  
Heating Contractor  
Phone Number  
Address  
8140705R3-1/07  
Price - $5.00  
WARNING  
This boiler requires regular maintenance and service to operate safely. Follow the  
instructions contained in this manual.  
Improper installation, adjustment, alteration, service or maintenance can cause property  
damage, personal injury or loss of life. Read and understand the entire manual before  
attempting installation, start-up operation, or service. Installation and service must be  
performed only by an experienced, skilled, and knowledgeable installer or service agency.  
This boiler must be properly vented.  
This boiler needs fresh air for safe operation and must be installed so there are provisions  
for adequate combustion and ventilation air.  
The interior of the venting system must be inspected and cleaned before the start of the  
heating season and should be inspected periodically throughout the heating season for any  
obstructions. A clean and unobstructed venting system is necessary to allow noxious  
fumes that could cause injury or loss of life to vent safely and will contribute toward  
maintaining the boiler's efficiency.  
Installation is not complete unless a pressure relief valve is installed into the tapping  
located on top of appliance. - See the Water Piping and Trim Section of this manual for  
details.  
This boiler is supplied with safety devices which may cause the boiler to shut down and not  
re-start without service. If damage due to frozen pipes is a possibility, the heating system  
should not be left unattended in cold weather; or appropriate safeguards and alarms should  
be installed on the heating system to prevent damage if the boiler is inoperative.  
This boiler contains very hot water under high pressure. Do not unscrew any pipe fittings  
nor attempt to disconnect any components of this boiler without positively assuring the  
water is cool and has no pressure. Always wear protective clothing and equipment when  
installing, starting up or servicing this boiler to prevent scald injuries. Do not rely on the  
pressure and temperature gauges to determine the temperature and pressure of the boiler.  
This boiler contains components which become very hot when the boiler is operating. Do  
not touch any components unless they are cool.  
Boiler materials of construction, products of combustion and the fuel contain alumina, silica,  
heavy metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful  
substances which can cause death or serious injury and which are known to the state of  
California to cause cancer, birth defects and other reproductive harm. Always use proper  
safety clothing, respirators and equipment when servicing or working nearby the appliance.  
Failure to follow all instructions in the proper order can cause personal injury or death.  
Read all instructions, including all those contained in component manufacturers manuals  
which are provided with the boiler before installing, starting up, operating, maintaining or  
servicing.  
Keep boiler area clear and free from combustible materials, gasoline and other flammable  
vapors or liquids.  
All cover plates, enclosures and guards must be in place at all times.  
NOTICE  
This boiler has a limited warranty, a copy of which is printed on the back of this manual.  
It is the responsibility of the installing contractor to see that all controls are correctly installed  
and are operating properly when the installation is complete.  
3
Table of Contents  
I. Pre-Installation............................... 6  
VI. Electrical....................................... 53  
VII. Modular Installation .................... 62  
VIII. System Start-up ............................ 64  
IX. Service .......................................... 68  
X. Repair Parts.................................. 74  
II. Unpack Boiler ................................ 7  
III. Venting/Air Intake Piping .............. 8  
IV. Water Piping and Trim ................. 45  
V. Gas Piping.................................... 50  
Figure 1: Minimum Clearances to Combustibles  
4
5
I. Pre-Installation  
WARNING  
F. Provide combustion and ventilation air in accordance  
with applicable provisions of local building codes,  
or: USA - National Fuel Gas Code, NFPA 54/ANSI  
Z223.1, Air for Combustion and Ventilation;  
Canada - Natural Gas Installation Code, CAN/  
CGA-B149.1, or Propane Installation Code, CAN/  
CGA-B149.2, Venting Systems and Air Supply for  
Appliances.  
If you do not follow these instructions  
exactly, a fire or explosion may result  
causing property damage or personal  
injury.  
DANGER  
WARNING  
Do not install boiler where gasoline or other  
flammable vapors or liquids, or sources of  
hydrocarbons (i.e. bleaches, cleaners,  
chemicals, sprays, paint removers, fabric  
softeners, etc.) are used or stored.  
Adequate combustion and ventilation air  
must be provided to assure proper  
combustion.  
The following guideline is based on the National Fuel Gas  
Code, NFPA 54/ANSI Z223.1.  
NOTICE  
1. Determine volume of space (boiler room). Rooms  
communicating directly with space (through  
openings not furnished with doors) are considered  
part of space.  
Due to the low water content of the boiler,  
mis-sizing of the boiler with regard to the  
heating system load will result in excessive  
boiler cycling and accelerated component  
failure. Burnham DOES NOT warrant  
failures caused by mis-sized boiler  
applications. DO NOT oversize the boiler to  
the system. Modular boiler installations  
greatly reduce the likelihood of boiler  
oversizing.  
Volume [ft³] = Length [ft] x Width [ft] x Height [ft]  
2. Determine Total Input of all appliances in space.  
Round result to nearest 1,000 Btu per hour (Btuh).  
3. Determine type of space. Divide Volume by Total  
Input.  
a. If result is greater than or equal to 50 ft³ per  
1,000 Btuh, space is considered an unconned  
space.  
A. Installation must conform to the requirements of the  
authority having jurisdiction. In the absence of such  
requirements, installation must conform to the National  
Fuel Gas Code, NFPA 54/ANSI Z223.1, and/or CAN/  
CGA B149 Installation Codes.  
b. If result is less than 50 ft³ per 1,000 Btuh, space  
is considered a conned space.  
4. Determine building type. A building of unusually  
tight construction has the following characteristics:  
a. Walls and ceiling exposed to outside atmosphere  
have a continuous water vapor retarder with a  
rating of 1 perm or less with openings gasketed  
and sealed, and;  
B. Appliance is design certied for installation on  
combustible ooring. Do not install boiler on  
carpeting.  
b. Weather-stripping has been added on openable  
windows and doors, and;  
C. Provide clearance between boiler jacket and  
combustible material in accordance with local re  
ordinance. Refer to Figure 1 for minimum listed  
clearance from combustible material. Recommended  
service clearance is 24 inches from left side, right  
side and front. Service clearances may be reduced to  
minimum clearances to combustible materials.  
c. Caulking or sealants applied in joints around  
window and door frames, between sill plates and  
oors, between wall-ceiling joints, between wall  
panels, at plumbing and electrical penetrations,  
and at other openings.  
5. For boiler located in an unconned space in a  
building of other than unusually tight construction,  
adequate combustion and ventilation air is normally  
provided by fresh air inltration through cracks  
around windows and doors.  
D. Install on level oor. For basement installation provide  
solid base such as concrete, if oor is not level or if  
water may be encountered on oor around boiler. Floor  
must be able to support weight of boiler, water and all  
additional system components.  
E. Protect gas ignition system components from water  
(dripping, spraying, rain, etc.) during boiler operation  
and service (circulator replacement, condensate trap,  
control replacement, etc.).  
6
c. Horizontal ducts. Minimum free area of one (1)  
square inch per 2,000 Btu per hour input of all  
equipment in space. Duct cross-sectional area  
shall be same as opening free area.  
NOTICE  
Boilers operated with direct vent (sealed  
combustion) are exempt from needing  
provisions for combustion air from the  
room, provided air intake piping is installed  
per code and the instructions in this  
manual.  
Alternate method for boiler located within  
conned space. Use indoor air if two permanent  
openings communicate directly with additional  
space(s) of sufcient volume such that combined  
volume of all spaces meet criteria for unconned  
space. Size each opening for minimum free area  
of one (1) square inch per 1,000 Btu per hour  
input of all equipment in spaces, but not less than  
100 square inches.  
6. For boiler located within unconned space in building  
of unusually tight construction or within conned  
space, provide outdoor air through two permanent  
openings which communicate directly or by duct  
with the outdoors or spaces (crawl or attic) freely  
communicating with the outdoors. Locate one opening  
within twelve (12) inches of top of space. Locate  
remaining opening within twelve (12) inches of bottom  
of space. Minimum dimension of air opening is three  
(3) inches. Size each opening per following:  
7. Combustion Air/Ventilation Duct Louvers and  
Grilles. Equip outside openings with louvers to  
prevent entrance of rain and snow, and screens to  
prevent entrance of insects and rodents. Louvers and  
grilles must be xed in open position or interlocked  
with equipment to open automatically before burner  
operation. Screens must not be smaller than ¼ inch  
mesh.  
a. Direct communication with outdoors. Minimum  
free area of one (1) square inch per 4,000 Btu per  
hour input of all equipment in space.  
Consider the blocking effect of louvers, grilles and  
screens when calculating the opening size to provide  
the required free area. If free area of louver or grille  
is not known, assume wood louvers have 20-25  
percent free area and metal louvers and grilles have  
60-75 percent free area.  
b. Vertical ducts. Minimum free area of one (1)  
square inch per 4,000 Btu per hour input of all  
equipment in space. Duct cross-sectional area  
shall be same as opening free area.  
CAUTION  
If using indoor air for combustion (see Venting Section - Indoor Air), avoid operating this boiler in an  
environment where saw dust, loose insulation fibers, dry wall dust, etc. are present. If boiler is  
operated under these conditions, the burner interior and ports must be cleaned and inspected daily  
to insure proper operation.  
II. Unpack Boiler  
WARNING  
CAUTION  
Installation of this boiler should be  
undertaken only by trained and skilled  
personnel from a qualified service agency.  
Do not drop boiler. Do not bump boiler  
jacket against floor.  
A. Move boiler to approximate installed position.  
E. Tilt the boiler to its front side or back side and slide a  
wooden slat under the three raised feet.  
B. Remove all crate fasteners.  
F. Tilt the boiler in the opposite direction and slide  
C. Lift and remove outside container. Save two of the  
wooden slats from the container sleeve for use in Steps  
E and F.  
another wooden slat under the three raised feet.  
G. Slide the boiler left or right off the skid using the two  
wooden slats as runners.  
D. Remove all boiler hold-down fasteners.  
H. Move boiler to its permanent location.  
7
III. Venting / Air Intake Piping  
WARNING  
Do not use this boiler with galvanized, Type 304 or Type 316 stainless steel, non metallic or  
any other non AL29-4C® based vent systems.  
Do not use a barometric damper or drafthood with this appliance.  
Do not use vent dampers with this boiler.  
Moisture and ice may form on surfaces around termination. To prevent deterioration,  
surfaces should be in good repair (sealed, painted, etc.).  
This appliance needs fresh air for safe operation and must be installed so there are  
provisions for adequate combustion and ventilation air.  
Do not reduce size of air intake pipe.  
Read, understand and follow combustion air instruction restrictions contained in the Pre-  
Installation instructions of this manual.  
Do not operate appliance where gasoline or other flammable vapors or liquids, or sources of  
hydrocarbons (i.e. bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners,  
etc.) are used, stored and/or present in the air.  
When installing vent pipe through chimney, no other appliance can be vented into the  
chimney.  
Do not exceed maximum vent/air intake lengths. Refer to Table 4.  
Table 1: Air Intake / Vent System Options  
Installation  
Additional  
Part  
Number  
Drawing and  
Specification  
(See Section)  
Option  
Description  
Vent Kit  
Required  
Direct Vent (sealed combustion) with both the vent  
pipe and air intake pipe terminating horizontally  
(through a sidewall) with individual penetrations for  
the vent and air intake piping and terminals.  
1. Separate  
Horizontal  
See  
Table 2  
No  
No  
D.  
E.  
F.  
Direct Vent (sealed combustion) with both the vent  
pipe and air intake pipe terminating vertically  
(through the roof) with individual penetrations for  
the vent and air intake piping and terminals.  
2. Separate  
Vertical  
See  
Table 2  
Direct Vent (sealed combustion) with the vent pipe  
3. Combination and air intake pipe joining at a common terminal  
3 - 6 Section  
(61106012)  
Yes  
Horizontal  
and terminating horizontally (through a sidewall up  
to 15" thick) with only one penetration.  
Direct Vent (sealed combustion) with the vent pipe  
4. Combination and air intake pipe joining at a common terminal  
3 - 4 Section  
(100222-01)  
5 - 6 Section  
(100223-01)  
Yes  
No  
No  
G.  
H.  
I.  
Vertical  
and terminating vertically (through the roof) with  
only one penetration.  
Power Vent - Air used for combustion is provided  
from within the building.  
5. Indoor Air  
See Table 2  
Direct Vent (sealed combustion) with both the vent  
pipe and air intake pipe terminating horizontally  
(through a sidewall) with individual penetrations for  
the vent and air intake piping and terminals.  
6. Optional  
Separate  
See Table 2  
Horizontal  
8
Table 2: Vent System Components Included with Boiler  
Vent System Components  
Part Number  
8110701  
Gasketed Vent Terminal 3"  
Horizontal (SCG-3 thru SCG-7)  
Gasketed Vent Terminal 4"  
Horizontal (SCG-8 & SCG 9)  
8110702  
6116045  
6116049  
6116063  
Disc Air Intake - 3"  
(SCG-3 & SCG-4)  
Disc Air Intake - 4"  
(SCG-5 & SCG-6)  
Air Intake - 5"  
(SCG-7 thru SCG-9)  
Table 3: Burnham Vent System and Air Intake System Components  
Vent System  
Component  
Part  
Number  
Equivalent  
Feet of Pipe  
3" Dia. Pipe x 1 Ft  
8116296U  
100176-01  
8116298U  
100177-01  
8116300U  
100178-01  
8116319U  
1
3
5
4" Dia. Pipe x 1 Ft  
3" Dia. Pipe x 3 Ft  
4" Dia. Pipe x 3 Ft  
3" Dia. Pipe x 5 Ft  
4" Dia. Pipe x 5 Ft  
3" Dia. Pipe x Adjustable  
Intake System  
Components  
(Parts by Others)  
Equivalent  
Feet of Pipe *  
3", 4", or 5" ID Pipe x 1 Ft  
3", 4", or 5" ID Pipe x 2 Ft  
3", 4", or 5" ID Pipe x 4 Ft  
3", 4", or 5" ID Pipe x 5 Ft  
3", or 4" 90° Elbow  
1
2
4
5
5
5
6
6
**Equal to  
Installed Length  
(1.06 to 1.64)  
4" Dia. Pipe x Adjustable  
3" Dia. 90° Elbow  
100179-01  
8116294U  
100180-01  
8116292U  
100181-01  
8166302U  
100182-01  
8116304U  
100183-01  
8116116  
5
5
4" Dia. 90° Elbow  
3", or 4" 45° Elbow  
3" Dia. 45° Elbow  
4" Dia. 45° Elbow  
5" 90° Elbow  
3" Dia. Horizontal Drain Tee  
4" Dia. Horizontal Drain Tee  
3" Dia. Vertical Drain Tee  
4" Dia. Vertical Drain Tee  
3" Single Wall Thimble  
4" Single Wall Thimble  
3" Double Wall Thimble  
4" Double Wall Thimble  
5" 45° Elbow  
7½  
7½  
---  
---  
* Equivalent Feet of Pipe Based on  
Standard 4" Smoke Pipe Design  
100184-01  
8116115  
100185-01  
Table 4: Vent/Air Intake Length  
3" Air Intake Pipe 4" Air IntakePipe 5" Air IntakePipe  
(Equiv. Ft.) (Equiv. Ft.) (Equiv. Ft.)  
3" Vent Pipe  
(Equiv. Ft.)  
4" Vent Pipe  
(Equiv. Ft.)  
Model  
Min. Max. Min. Max. Min. Max.  
50 ---- ---- ---- ----  
Min.  
8
Max.  
50  
Min.  
----  
----  
----  
8
Max.  
----  
----  
SCG-3 & SCG-4  
SCG-5 & SCG-6  
SCG-7  
8
----  
----  
----  
----  
----  
----  
8
50  
----  
----  
----  
8
----  
50  
40  
8
50  
----  
----  
8
50  
----  
40  
SCG-8 & SCG-9  
8
----  
----  
9
A. Vent Guidelines Due to Removal of an Existing  
Boiler  
B. General Guidelines  
1. Vent system installation must be in accordance  
with National Fuel Gas Code, NFPA 54/ANSI  
Z221.3 or applicable provisions of local building  
codes. Contact local building or re ofcials about  
restrictions and installation inspection in your area.  
For installations not involving the replacement of an  
existing boiler, proceed to Step B.  
When an existing boiler is removed from a common  
venting system, the common venting system is likely  
to be too large for proper venting of the remaining  
appliances. At the time of removal of an existing  
boiler, the following steps shall be followed with each  
appliance remaining connected to the common venting  
system placed in operation, while the other appliances  
remaining connected to the common venting system are  
not in operation:  
2. The SCG is designed to be installed as either  
a Direct Vent boiler or Power Vent boiler. In  
the Direct Vent conguration all of the air for  
combustion is supplied directly to the burner  
enclosure from outdoors and ue gases are vented  
directly outdoors (through wall or roof). In the  
Power Vent conguration, room air provides air  
for combustion and ventilation. Flue gases are still  
vented directly outdoors (through wall or roof).  
Note: Venting requirements change if indoor air is  
used.  
1. Seal any unused openings in the common venting  
system.  
2. Visually inspect the venting system for proper  
size and horizontal pitch and determine there is no  
blockage or restriction, leakage, corrosion, and other  
deciencies which could cause an unsafe condition.  
3. Refer to the appropriate drawings in this section of  
this manual to determine the proper conguration of  
venting system. See Table 1.  
3. Insofar as is practical, close all building doors and  
windows and all doors between the space in which  
the appliances remaining connected to the common  
venting system are located and other spaces of the  
building. Turn on clothes dryers and any appliance  
not connected to the common venting system.  
Turn on any exhaust fans, such as range-hoods and  
bathroom exhausts, so they will operate at maximum  
speed. Do not operate a summer exhaust fan. Close  
replace dampers.  
4. This appliance requires a Special Gas Vent. The  
product is designed to use Burnham supplied  
AL 29-4C® Stainless Steel vent system components.  
The following manufacturers offer similar  
AL 29-4C® components and are approved for use  
with this product. Heat-Fab Inc. - Saf-T-Vent, Flex-L  
International Inc. - Star-34, Z-Flex U. S., Inc. -  
Z-Vent, and Protech Systems , Inc.- FasNSeal™ or  
equivalent. The use of these alternate manufacturer’s  
venting systems will require adapters to connect  
to the Burnham supplied vent connector and vent  
terminal. These adapters are not supplied with this  
unit and should be obtained from the supplier of  
the alternate manufacturer’s venting system. See  
Table 3 for complete list of Burnham Vent System  
Components.  
4. Place in operation the appliance being inspected.  
Follow the Lighting (or Operating) Instructions.  
Adjust thermostat so appliance will operate  
continuously.  
5. Test for spillage at the draft hood relief opening  
after ve (5) minutes of main burner operation. Use  
the ame of a match or candle, or smoke from a  
cigarette, cigar or pipe.  
5. Horizontal vent pipe must maintain a minimum ¼  
inch per foot slope down towards boiler.  
6. After it has been determined that each appliance  
remaining connected to the common venting system  
properly vents when tested as outlined above, return  
doors, windows, exhaust fans, replace dampers and  
any other gas burning appliance to their previous  
conditions of use.  
6. Use noncombustible ¾ inch pipe strap to support  
horizontal runs and maintain vent location and  
slope while preventing sags in pipe. Do not restrict  
thermal expansion or movement of vent system.  
Maximum support spacing is ve (5) feet. Do not  
penetrate any part of the vent system with fasteners.  
7. Any improper operation of the common venting  
system should be corrected so the installation  
conforms with the National Fuel Gas Code, NFPA  
54/ANSI Z223.1. When resizing any portion of the  
common venting system, the common venting  
system should be resized to approach the minimum  
size as determined using the appropriate tables in  
Part II in the National Fuel Gas Code, NFPA 54/  
ANSI Z223.1.  
7. Vent length restrictions are based on equivalent  
length of vent/air pipe (total length of straight  
pipe plus equivalent length of ttings). Maximum  
vent/air lengths are listed in Table 4. Do not exceed  
maximum vent/air intake lengths. Table 3 lists  
equivalent lengths for ttings. Do not include vent/  
air terminals in equivalent feet calculations.  
8. Provide and maintain vent pipe minimum clearances  
to combustible materials. Vent pipe minimum  
clearance to combustible material is four (4) inches  
when vent is installed in a fully enclosed (chase)  
application or three (3) inches when vent is installed  
10  
11. Plan venting system to avoid possible contact with  
plumbing or electrical wires. Start at vent connector  
on top of boiler and work towards vent terminal.  
with at least one side open, similar to a joist bay  
application. Use double wall thimble [Burnham  
Part No. 8116115 (3”), 100185-01 (4”)] when  
penetrating a combustible wall.  
12. Once a vent pipe manufacturer and system is chosen  
never mix and match vent systems.  
9. Do not install venting system components on  
the exterior of the building except as specically  
required by these instructions. The vent termination  
location is restricted as follows:  
13. If a non-standard length pipe is required:  
Gasketed Vent System: The use of the adjustable  
length pipe (P/N 8116319U) is recommended to  
complete a non-standard pipe length. This pipe  
requires a minimum installed length of 12¾ inch  
and can adjust across a 7 inch gap up to a maximum  
of 19¾ inch long. (Note for the adjustable pipe  
the installed length should be measured from the  
centerline of the bead on the male end of the rst  
pipe to the end of the female pipe excluding the  
locking band of the second pipe with a single  
gasket.) Only in the event the adjustable length pipe  
is not sufcient a standard length pipe may be cut  
using the procedure outlined below for the Gasket-  
Less Vent System.  
a. Minimum twelve (12) inches above grade plus  
normally expected snow accumulation level, or  
seven (7) feet above grade if located adjacent  
to public walkway. Do not install over public  
walkway where local experience indicates  
appliance ue gas vapor or condensate creates a  
nuisance or hazard.  
b. Minimum three (3) feet above any forced air  
inlet located within ten (10) feet.  
c. Direct Vent - Minimum one (1) foot below, one  
(1) foot horizontally from, or one (1) foot above  
any door, window, or gravity air inlet.  
Power Vent - Minimum four (4) feet below, four  
(4) feet horizontally from, or four (4) feet above  
any door, window, or gravity air inlet.  
WARNING  
Never exceed maximum installed length of  
19¾ inches for adjustable length pipe.  
Risk of flue gas leakage is possible.  
d. Minimum four (4) feet horizontally from electric  
meters, gas meters, regulators, and relief valves.  
This distance may be reduced if equipment is  
protected from damage due to condensation or  
vapor by enclosure, overhangs, etc.  
NOTICE  
e. Minimum twelve (12) inches from overhang or  
corner of building.  
Cut must be square with pipe and filed or  
sanded smooth before joining. Carefully  
ensure roundness of cut pipe by hand with  
gloves before installing. Seal joint with RTV  
specified in this manual.  
10. Enclose vent passing through occupied or  
unoccupied spaces above the boiler with material  
having a re resistance rating of at least equal to the  
rating of the adjoining oor or ceiling. Maintain  
minimum clearances to combustible materials. See  
Figure 1.  
C. Install Vent Pipe, Burnham Gasketed Vent System.  
1. Procedure for Joining Burnham Gasketed Vent Pipe  
and Fittings. See Figure 3.  
Note: For one or two family dwellings, re  
resistance rating requirement may not need to be  
met, but is recommended.  
Figure 3: Burnham Gasketed Vent Joint Detail  
11  
a. Wipe the male end of each joint using an alcohol  
pad to remove any dirt and grease.  
8. Locate air intake termination on the same wall as  
the vent termination if possible, to prevent nuisance  
boiler shutdowns. However, boiler may be installed  
with vertical venting and sidewall combustion air  
inlet or visa versa, if installation conditions do not  
allow alternate arrangement.  
b. Align weld seams in pipes and use a slight  
twisting motion to FULLY insert male end into  
female end of joint. Ensure bead in male end  
of pipe is below locking band and rest against  
the end of the female pipe. Verify the factory-  
installed gasket is not dislodged or cut.  
9. Do not exceed air intake length. See Table 4.  
10. Use single wall metal or PVC pipe.  
c. Tighten locking band by HAND with a 5/16”  
nut driver until snug plus ¼ turn. DO NOT  
SECURE JOINTS WITH SHEET METAL  
SCREWS OR POP RIVETS. DO NOT  
PUNCTURE THE VENT SYSTEM!  
a. Air intake pipe diameter is based on boiler size.  
SCG-3 & SCG-4 uses 3 inch diameter piping.  
SCG-5 & SCG-6 uses 4 inch diameter piping.  
SCG-7 thru SCG-9 uses 5 inch diameter piping.  
d. Once the installation is complete, operate  
appliance and inspect all joints to ensure that ue  
gases and/or liquid condensate will not escape.  
11. Air intake termination must be located:  
Horizontal - At least twelve (12) inches above  
grade plus the expected snow accumulation.  
D. Separate Horizontal Venting System. See Figures 4,  
12. Start at collar on burner enclosure (inside boiler  
jacket) and work towards the air intake terminal.  
5A and 5B.  
Vent Piping –  
13. Maintain minimum of ¼ inch per foot slope on  
horizontal runs. Slope towards air inlet terminal  
when possible. If not, slope towards boiler.  
1. This boiler is supplied with components as standard  
equipment for installation of the separate horizontal  
venting system.  
14. The air intake pipe must be adequately supported  
with straps or supports no less than ve (5) feet  
apart on horizontal runs. The complete air intake  
piping system must be rigid and able to withstand  
minor impacts without collapse.  
2. Do not exceed maximum vent/air intake lengths.  
Refer to Table 4.  
3. Recommended horizontal installation consists of  
vent being sloped down ¼ inch per foot away from  
boiler. See Figure 4.  
15. Inlet air pipe penetration:  
4. Use appropriate designed thimbles when passing  
through combustible walls (thimble use optional for  
noncombustible walls). Insert thimble through wall  
from outside. Secure outside ange to wall with  
nails or screws, and seal ID, OD and vent holes with  
sealant material. Install inside ange to inside wall,  
secure with nails or screws, and seal with sealant  
material.  
Horizontal - Size wall penetration to allow easy  
insertion of air inlet piping. Seal around pipe with  
sealant to form weathertight exterior joint.  
16. Seal all joints airtight, using silicone caulk or self-  
adhesive aluminum tape.  
17. Install Air Intake Terminal:  
Horizontal - Remove four (4) screws from cover  
plate and remove cover plate from terminal. Insert  
intake piping into intake terminal collar. Secure  
terminal to intake piping and seal joint with silicone  
caulk or self-adhesive aluminum tape. Apply  
continuous bead of silicone caulk around the back  
of the intake terminal, approximately ¼ inch from  
its edge. Push inlet terminal inward until terminal’s  
back ange is against the wall surface. Secure the  
terminal with noncorrosive fasteners (stainless steel,  
brass or aluminum) to the wall. Reinstall the cover  
plate with four (4) screws. Apply a bead of silicone  
caulk to perimeter of intake terminal’s back ange  
to provide a weathertight seal.  
5. For noncombustible wall application when thimble  
is not used, size opening such that bell with locking  
band attached cannot pass through.  
6. Join vent terminal to vent pipe. See Figures 5A and  
5B.  
7. Insert vent pipe through thimble/opening from  
outside and join to vent system. Apply sealant  
between vent pipe and opening/thimble to provide  
weathertight seal.  
Air Intake piping - See Figures 4, 5A and 5B.  
12  
13  
14  
15  
16  
E. Separate Vertical Venting System - See Figures 6, 7, 8A, 8B and 9.  
NOTICE  
Roof penetrations require the use of roof  
flashing and storm collar - not supplied with  
boiler.  
Vertical Venting –  
8. Locate air intake termination on the same roof  
location as the vent termination if possible, to  
prevent nuisance boiler shutdowns. However, boiler  
may be installed with vertical venting and sidewall  
combustion air inlet or visa versa, if installation  
conditions do not allow alternate arrangement.  
1. Do not exceed maximum vent lengths. Refer to  
Table 4.  
2. Installation of a vertical vent tee 8116304U is  
required on all vertical vent applications. See  
Figures 6 and 7. Attach vertical vent drain tee  
directly to elbow or horizontal pipe from an elbow  
immediately after vent connector.  
9. Use single wall metal pipe or PVC and ttings  
available at most heating distributors.  
a. Air intake pipe diameter is based on boiler size.  
3. Slope horizontal runs minimum ¼ inch per foot.  
Slope towards vertical vent drain tee. Position weld  
seams in vent pipes, in all horizontal runs, at the top  
to avoid condensate from lying on the seams.  
SCG-3 & SCG-4 uses 3 inch diameter piping.  
SCG-5 & SCG-6 uses 4 inch diameter piping.  
SCG-7 thru SCG-9 uses 5 inch diameter piping.  
4. Install re stops where vent passes through oors,  
ceilings or framed walls. The re stop must close  
the opening between the vent pipe and the structure.  
10. Air intake termination must be located:  
Vertical - At least twelve (12) inches above the roof  
surface plus the expected snow accumulation.  
5. Whenever possible, install vent straight through  
the roof. Refer to Figure 7 if offset is necessary.  
Maintain minimum clearance to combustible  
materials.  
11. Start at collar on burner enclosure (inside boiler  
jacket) and work towards the air intake terminal.  
12. Maintain minimum of ¼ inch per foot slope on  
horizontal runs. Slope down towards boiler.  
6. Install Vent Terminal.  
13. The air intake pipe must be adequately supported  
with straps or supports no less than ve (5) feet  
apart on horizontal runs. The complete air intake  
piping system must be rigid and able to withstand  
minor impacts without collapse.  
a. Size roof opening to maintain minimum  
clearance from combustible materials.  
b. Extend vent pipe to maintain minimum vertical  
and horizontal distance of twelve (12) inches  
from roof surface. Allow additional vertical  
distance for expected snow accumulation.  
Provide brace as required. Refer to Figures 8A  
and 8B.  
14. Inlet air pipe penetration:  
Vertical - Size roof opening to allow easy insertion  
of inlet piping and allow proper installation of  
ashing and storm collar.  
NOTICE  
a. Use appropriately designed vent ashing  
when passing through roofs. Follow ashing  
manufacturers’ instructions for installation  
procedures. Flashing manufacturers are Air-  
Jet, American Metal Products, Metal Fab, and  
Simpson Dura-Vent.  
Vertical venting requires the use of roof  
flashing and a storm collar to prevent  
moisture from entering the structure.  
c. Install storm collar on vent pipe immediately  
above ashing. Apply Dow Corning Silastic 732  
RTV Sealant between vent pipe and storm collar  
to provide weathertight seal.  
b. Extend air intake pipe to maintain minimum  
vertical and horizontal distance of twelve  
(12) inches from roof surface. Allow  
additional vertical distance for expected snow  
accumulation. Provide brace as required. Refer  
to Figures 8A and 8B.  
d. Attach vent terminal.  
Vertical Air Intake Piping –  
7. Do not exceed maximum air intake length. Refer to  
Table 4.  
c. Vertical air intake requires ashing and a storm  
collar to prevent moisture from entering the  
structure.  
17  
d. Install storm collar on air intake pipe  
immediately above ashing. Apply Dow  
Corning Silastic 732 RTV Sealant between  
air intake pipe and storm collar to provide  
weathertight seal.  
15. Seal all joints airtight, using silicone caulk or self-  
adhesive aluminum tape.  
16. Install Air Intake Terminal:  
Vertical - Insert intake piping into intake terminal  
collar. Secure terminal to intake piping and seal  
joint with silicone caulk.  
e. All exposed air intake piping must be  
constructed of corrosion resistant material such  
as aluminum, stainless steel or PVC.  
18  
19  
20  
21  
Figure 9: Vertical Air Intake Piping  
22  
F. Combination Horizontal Venting System –SCG-3 Through SCG-6 ONLY – See Figures 10 and 11.  
1. Do not exceed maximum vent/air intake lengths.  
Refer to Table 4.  
NOTICE  
This vent system requires components not  
supplied with the boiler.  
2. Install Combination Vent/Air Terminal. See Figure 11.  
a. After determining the location with reference to Section B - General Venting Guidelines, cut a 6-1/8 inch square  
opening in the wall for the air box sub-assembly which is 6 inch square.  
b. Remove and save shipping screw from end panel with collar and vent pipe assembly. This will be reinstalled in a later  
step.  
Vent Carton Part Number 61106012 (includes items below)  
Description  
Component Part Number  
61106011  
A
B
C
D
E
F
Air Box Sub-Assembly (6" square x 2' long)  
Exterior Wall Cover (10" square)  
71106016  
4" x 3" Vent Pipe Reducer  
8116239  
Plate-Seal Exterior Cover (2)  
71106017  
#8 x ½" Stainless Steel Sheet Metal Screw (19)  
#10 - 32 x ¼" Stainless Steel Machine Screw (8)  
#10 - 32 x ½" Aluminum Spacer (4)  
80860047  
80860842  
G
80861617  
COMBINATION HORIZONTAL VENT SYSTEM COMPONENTS  
23  
c. From exterior of building, insert air box sub-  
assembly into square opening. Push air box  
inward until wall ange is against wall, check  
for level and mark the location of the four (4)  
securing holes on the exterior wall. Remove air  
box from wall.  
3. Install Vent Piping. See Figure 10 and 11.  
a. Start at vent connector on boiler and work  
towards combination vent/air terminal.  
b. Installation of a vertical vent tee 8116304U is  
required on all vertical vent applications. See  
Figures 12 and 13. Attach vertical vent drain  
tee directly to elbow or horizontal pipe from an  
elbow immediately after vent connector.  
d. Drill four (4) pilot holes, properly sized for the  
non-corrosive fasteners (stainless steel, brass, or  
aluminum) to be used to secure the wall ange to  
the exterior wall. (Securing screws not supplied  
with kit.)  
c. Slope horizontal runs minimum ¼ inch per foot.  
Slope towards vertical vent drain tee. Position  
weld seams in vent pipes, in all horizontal runs,  
at the top to avoid condensate from lying on the  
seams.  
e. Attach four (4) 1/2 inch long threaded aluminum  
spacers to the outer anges of the exterior  
wall ange with four (4) number 10 - 32 x 1/4  
inch stainless steel machine screws provided.  
(See Figure 11.)  
d. Use 3/4 inch pipe strap to support horizontal runs  
and maintain vent location and slope. Maximum  
support spacing is ve (5) feet.  
f. Apply a 1/4 inch thick continuous bead of  
silicone caulk to perimeter of exterior wall  
ange’s back surface to provide a weathertight  
seal.  
e. Install vent piping to connect vent connector  
on boiler and combination vent/air terminal.  
Reference Section B - General Venting  
Guidelines for proper procedure for joining pipe  
and ttings.  
g. Reinstall air box sub-assembly into opening in  
exterior wall and secure to wall.  
f. Connect vent piping to combination vent/air  
terminal. See Figure 10.  
WARNING  
4. Install Air Intake Piping. See Figures 10 and 11.  
a. Do not exceed air intake length. See Table 4.  
Non-corrosive fasteners must be used.  
b. Use single wall metal pipe or PVC and ttings  
h. Apply a bead of silicone caulk to perimeter of  
wall ange, where the wall and ange join. Use  
a tool or your nger and apply pressure while  
smoothing caulking to provide a weathertight  
seal.  
available at most heating distributors.  
c. Air intake pipe diameter is based on boiler size.  
SCG-3 & SCG-4 uses 3 inch diameter piping.  
SCG-5 & SCG-6 uses 4 inch diameter piping.  
SCG-7 thru SCG-9 uses 5 inch diameter piping.  
i. From interior of building, insert end panel with  
collar and vent pipe assembly into open end of  
air box sub-assembly. (See Figure 11.)  
d. Start at collar on burner enclosure (inside boiler  
jacket) and work towards the combination vent/  
air terminal.  
j. Secure end panel to air box sub-assembly with  
shipping screw and thirteen (13) number 8 sheet  
metal screws provided.  
e. Maintain minimum of 1/4 inch per foot slope on  
horizontal runs. Slope down towards boiler.  
k. From exterior of building, position 10 inch  
square exterior wall cover over exterior wall  
ange. Insert 3 inch diameter vent pipe into  
center opening in terminal cover. Align four  
(4) holes on cover with 1/2 inch long threaded  
spacers on wall ange. Secure terminal cover  
with four (4) number 10 - 32 x 1/4 inch stainless  
steel machine screws provided.  
f. The air intake pipe must be adequately supported  
with straps or supports no less than ve (5)  
feet apart on horizontal runs. The complete air  
intake piping system must be rigid and able to  
withstand minor impacts without collapse.  
g. Connect Air Intake Piping to Combination Vent/  
Air Terminal. See Figure 10.  
l. Apply a bead of silicone caulk to perimeter of  
plate-seal and around pipe. Secure plate-seal to  
exterior cover with six (6) #8 stainless steel sheet  
metal screws provided. Smooth caulk around  
plate-seal and pipe to provide weathertight seal.  
NOTE: When installing 3 inch diameter air intake  
piping for a SCG-3 or SCG-4 application, the use of  
a 4 inch x 3 inch reducer will be required to connect  
air intake piping to combination vent/air terminal.  
(Reducer included with combination horizontal  
venting kit).  
m. Install Vent Terminal supplied with boiler to vent  
pipe penetrating through terminal cover. Join  
terminal and pipe with locking band and seal  
with RTV (see Figure 3).  
h. Seal all joints airtight, using silicone caulk or  
self-adhesive aluminum tape.  
24  
25  
26  
G. Combination Vertical Venting System – SCG-3 Through SCG-6 ONLY – See Figures 12, 13 and 14.  
NOTICE  
This vent system requires components not  
supplied with the boiler.  
Part Number  
SCG-5 & SCG-6  
Description  
SCG-3 & SCG-4  
100222-01  
Vent Carton Part Number  
Starter Tee  
100223-01  
100225-01  
100224-01  
Vent/Air Adaptor  
100226-01  
COMBINATION VERTICAL VENT SYSTEM COMPONENTS  
27  
1. Saf-T Vent SC is an advanced concentric vent  
system designed for zero clearance installation  
in residential applications. The inner wall is  
constructed from superferritic AL29-4C® stainless  
steel. The outer wall is also constructed from  
stainless steel, providing durability and a lasting  
nish.  
the system in place. A continuous straight-line  
pitch of at least ¼” (2°) to the foot on horizontal  
runs must be maintained in order to properly rid  
the system of the corrosive condensate.  
5. General Installation Requirements:  
Saf-T Vent SC vent sections, or other Saf-T  
Vent products, must be used throughout the  
entire length of the system. Alternatives such  
as galvanized pipe, PVC, nonmetallic pipe,  
prefabricated chimney, eld-fabricated vents  
or Type B vent sections must not be used. Do  
not mix pipes, ttings, or joining methods from  
different manufacturers.  
2. As a Special Gas Vent system: Saf-T Vent is  
approved for use on ANSI Category I, II, III, and  
IV Gas-Burning Appliances and certain Direct Vent  
Appliances. Saf-T Vent SC is appropriate for use on  
appliances that specify an AL29-4C venting system.  
3. As a Sealed Combustion system: The unique  
concentric design of Saf-T Vent SC also allows it  
to function as a pipe-in-a-pipe vent. Products of  
combustion are exhausted out through the inner wall  
while combustion air is drawn in through the outer  
wall. An appliance can be direct-vented with only  
a single penetration through the building structure.  
This application must be approved by the  
Appliance Manufacturer.  
More than one appliance may not be  
interconnected to any part of the venting system.  
Any penetrations of ceilings, oors or walls must  
be properly re-stopped.  
Whenever gas-burning equipment is installed in  
the same space where halogenated substances  
may exist (refrigerants, solvents, bleaches,  
salts, etc.), clean outside air must be utilized for  
combustion.  
Note: Saf-T Vent SC includes an integral seal and  
does not require RTV sealant. However, sealant  
may be necessary when connecting Saf-T Vent SC  
components directly to certain appliance ue collars  
and to the gasket-less Saf-T Vent GC and Saf-T Vent  
CI vent systems.  
The vent system shall not be routed into,  
through or within any other actively used vent or  
chimney.  
Seal weather exposed joints of the outer jacket  
with foil tape or an exterior grade silicone  
sealant.  
For applications up to 550°F/288°C, approved  
sealants include GE RTV 106 and Dow Corning  
736.  
Combustible Material is any material made of  
or surfaced with wood, compressed paper, plant  
bers, or other materials that are capable of  
being ignited or burned. Such material shall be  
considered combustible even though it is ame-  
proofed, re-retardant, or plastered. (Source:  
NPFPA54/ANSI Z223.1-1999.)  
For applications up to 300°F/149°C, approved  
sealants include GE RTV 106 and Dow Corning  
732.  
4. Pre-Installation Considerations:  
Proper planning prior to installation is essential  
as to avoid possible contact with concealed  
plumbing or electrical wiring inside walls,  
oors or ceilings as well as maintaining proper  
clearances. Be sure to plan a sufcient number  
of supports for the entire system that will  
Non-Combustible Material is any material that  
is not capable of being ignited and burned, such  
material consisting entirely of, or a combination  
of, steel, iron, brick, tile, concrete, slate,  
asbestos, glass and plaster. (Source: NPFPA54/  
ANSI Z223.1-1999.)  
maintain the required straight-line pitch and hold  
Clearances to Combustibles:  
Clearance to  
Maximum Flue  
Diameter Combustible  
Gas Temp. (°F)  
Orientation  
Enclosure  
Material  
Vertical,  
No Offsets  
550  
0"  
Fully enclosed by combustible  
material on all sides  
330  
Horizontal,  
Vertical with  
Offsets  
1"  
0"  
1"  
0"  
400  
400  
3" - 4"  
Unenclosed, at least 1 side open,  
combustible material on a  
maximum of 3 sides  
550  
550  
Any  
Noncombustible material  
28  
6. Vertical Installation Requirements:  
For a venting system that extends through  
any zone above that on which the connected  
appliance is located (except for one and two  
family dwellings), the vent system shall be  
enclosed with an enclosure having a re  
resistance rating equal to or greater than that of  
the oor or roof assemblies through which it  
passes.  
a. Seal weather exposed joints of the outer jacket  
with foil tape or an exterior grade silicone  
sealant.  
b. The vent system must terminate at least 3 feet  
above the roof line and at least 2 feet higher than  
any portion of the building within 10 feet.  
c. When terminated at a height of more than 6 feet  
the stack must be supported by a support bracing.  
The vent should be supported every 10 feet.  
Design any enclosure to permit inspection of the  
system.  
Do not place any type of insulation in any  
required clearance spaces surrounding the vent  
system.  
d. The total continuous distance of the vent system  
from the appliance ue collar to the termination  
shall not exceed that specied in the appliance  
manufacturer’s installation instructions.  
e. In cold climates do not install a condensate drain  
on the exterior of the building. Doing so may  
result in dangerous icy conditions on surfaces  
near the drain and may cause damage to the vent  
system and/or the building exterior.  
f. Install supports every 10 feet vertically along the  
vent pipe route. Vertical supports are required  
after every transition to vertical and are required  
after every offset elbow. When the vent is free  
standing and penetrates a roof/ceiling another  
means of support must be used at a second  
location. Refer to the Vertical Supports section  
in this manual.  
29  
7. Joint Assembly Instructions:  
a. Before joining the sections or ttings together, use an alcohol pad to wipe the joint area of both ends of the inner  
pipe. This will remove any foreign matter which may affect the integrity of the seal. Install the system with the  
female ends (ends with the red seal) pointing away from the appliance. (Unless specied differently by the appliance  
manufacturer.)  
b. Insert the male end of the inner pipe into the female end of the previous section. In extremely dry conditions it may be  
helpful to moisten the seal with clean water prior to assembly. Push rmly until the outer jacket has made contact with  
the snap ring located inside the female end of the previous section. When fully assembled the outer female end will  
overlap the male end 1”.  
c. Use the three (3) self-tapping screws provided to connect the outer vents. No pre-drilling is required.  
CAUTION  
Do not overtighten. If using a variable torque drill, use a low torque setting to install screws, as  
not to strip out the holes. If a hole becomes stripped due to overtightening, a larger diameter  
screw (½" long max.) or short pot rivet can be used.  
30  
8. Straight Sections Cut To Length:  
e. Add 3” to the distance measured previously for the  
cut length of the inner vent pipe. Mark a cut line on  
the inner vent on the male end (the end without the  
red seal).  
If a custom length of SC is necessary, a standard vent  
section can be cut.  
a. Measure the distance of the length needed, taking the  
measurement from the end of one of the outer jackets  
to the beginning of the other outer jacket on the  
section to connect to, (A to B on diagram).  
The inner pipe is always cut 1” longer than the  
outer pipe.  
f. WEAR GLOVES, as cut ends are very sharp. Cut  
the pipes with an abrasive cutoff saw, plasma cutter,  
or compound snips. If using snips, start the cut at  
the male end and follow a spiral path around the pipe  
until the cutoff mark is reached. File off any burrs  
or rough edges that develop in the cutting process  
and clean off any dust or grit. If the cutting process  
distorts the roundness of the pipes, carefully use your  
thumbs to re-round the ends.  
b. Select a section that is longer than the required  
length.  
c. It will be necessary to disassemble the vent prior to  
cutting.  
Stand the section on end with the holes up. Find the  
end of snap ring and pry it out of its groove, being  
careful not to damage the ends of the vent pipes.  
Pull up on end of the snap ring and pull it out from  
the end of the pipe. It may want to spiral out as it is  
removed. After the snap ring is removed, the inner  
vent pipe can be separated from the outer jacket.  
g. Reassemble the inner vent into the outer jacket and  
reinstall the snap ring into the groove. Push the  
inner vent into the outer jacket until the triangle on  
the inner vent is seated rmly against the bead on  
outer jacket. Start one end of the snap ring into the  
groove of the outer pipe. Slowly turn and feet the  
snap ring into the groove in a spiral motion, and  
continue around the pipe until the snap ring is fully  
inserted. Ensure that the triangle on the inner vent is  
all the way down against the bead of the outer jacket  
by pushing in rmly. Also ensure that the snap ring  
is completely in the groove all the way around outer  
jacket.  
d. Add 2” to the distance measured previously for the  
cut length of the outer jacket. Mark a cut line on the  
outer jacket on the male end (the end without holes in  
it).  
An effective way of marking is to run a length of tape  
around the section, assuring a square cut.  
31  
9. Air Intake Connections for Direct Vent and Sealed  
Combustion Appliances*:  
The Air Intake Tee may be used on approved direct vent  
and sealed combustion appliances that have separate (non-  
concentric) air intake and ue exhaust collars. The male end  
of the tee connects to EZ Seal appliance adapters and the tee  
takeoff/snout connects to the appliance air intake.  
Insert the male end of the Air Intake Tee into the female  
end of the EZ Seal vent section or appliance adapter and  
complete the ring and tab connection.  
Insert the male end of the next SC section into the female  
end of the Air Intake Tee and secure as described elsewhere  
in this manual.  
Connect the tee takeoff to the appliance combustion air inlet  
using appropriate hose or pipe.  
*
Direct Vent Appliances are constructed and installed so that  
all air for combustion is supplied directly from the outside  
atmosphere. The passage for the combustion air is allowed  
a small amount of leakage in the building environment. No  
special installation considerations are required to use Saf-T  
Vent SC on Direct Vent appliances unless specied by the  
appliance manufacturer. Sealed Combustion appliances are  
similar to Direct Vent except the combustion air passage must  
be sealed to prevent leakage within the building envelope.  
When Saf-T Vent SC is used on approved Sealed Combustion  
appliances the joints of the outer jacket must be sealed with  
a foil tape (example: 3M 425), or approved silicone sealant  
(example: Dow Corning 732).  
10. Condensate Drains:  
When An Internal Condensate Drain is NOT Part of the  
Appliance:  
A Saf-T Vent SC In-Line Drain Section is strongly  
recommended. Install this drain tting as close to the  
appliance ue collar as possible.  
A condensate drain is required for every 30 feet of  
horizontal vent and at/near the bottom of a vertical stack.  
Use the In-Line Drain Section for a straight horizontal or  
vertical run. When used horizontally, rotate the tting so that  
the drain tube is as vertical as possible.  
A Condensate Drain Tube Kit is available to direct the  
condensate to an appropriate location, i.e. oor drain or  
vented sanitary sewer connection. A trap loop must be  
formed into the drain hose and must be a diameter that is  
at least four (4) times the appliance’s rated stack pressure  
in inches of water column or 3 inches, whichever is  
greater. Secure the loop with a cable tie. Prior to nal  
assembly the trap loop must be ‘primed’ by pouring a  
small quantity of water into the drain hose. Inspect at least  
annually to verify the trap is ‘primed’.  
Follow all local and national codes and regulations for the  
draining of acidic condensate.  
In cold climates do not install a condensate drain on the  
exterior of the building. Doing so may result in dangerous  
icy conditions on surfaces near the drain and may cause  
damage to the vent system and/or the building exterior.  
32  
11. Horizontal Supports:  
Saf-T Vent SC must have supports for every six (6) feet of horizontal run and after every transition from vertical to  
horizontal. Support hangers by themselves do not maintain the necessary clearances to combustible materials; be sure to  
consider clearances when planning the system.  
The supports must be secured to solid material using at least #10 fasteners. Do not fasten supports to drywall sheathing  
without using hollow wall anchors. The conduit supports must maintain the ¼” per foot pitch to avoid collection of  
condensate in the vent. Position the vent so that the welded seam is on the top.  
0” Clearance Support Clamp, (SC_ _SUP): Attach the bracket to the structure but do not tighten in place. Open the  
hose clamp and slip it under the support bracket. Position the clamp between the mounting screws and rotate the clamp  
so that the screw housing will be accessible after the vent is installed. Restart the threads on the hose clamp and securely  
tighten the mounting screws to the structure. This can also be installed vertically.  
1” Clearance Support Clamp, (SC_ _SUP1): Supports the vent at 1” clearance to the structure. Line up the support  
mounting brackets so that the mounting screws will follow the center line of the vent section. This can also be installed  
vertically.  
33  
Support Clamp, (4_ _27SS): Support clamps are sold in pairs and can be clamped around the vent and suspended from a  
rod or cable. They can be used singularly as a saddle clamp to rest the vent in and suspended from two (2) rods or cables.  
Support Legs Rotated Horizontally: Support legs can be used on horizontal runs by rotating the clamp at the rivet  
connection. The legs can be cut to shorter lengths if necessary.  
Vertical Supports, (SC_ _VSL): Vertical support legs can be used above or below a structure for support. To install,  
slide the support clamp over the end of the vent section, leaving the clamp loose. Position the support legs and install  
two (2) screws through each leg into the structure. Tighten the clamp around vent pipe. The legs can be cut to shorter  
lengths if necessary and can rotate around the support clamp at the rivet connection. By rotating the clamp to a horizontal  
position the support legs can be used on horizontal runs.  
34  
Fire Stop/Wall Thimble/Support, (SC_ _FS):  
The Saf-T Vent SC Fire Stop can be used as a restop, a wall thimble, or as a support plate.  
To use as a Wall Thimble prepare an opening according to the chart below. Remove any insulation from the opening,  
using additional framing if necessary. Attach the plate over the center of the opening using appropriate fasteners.  
Install the vent section through the thimble plate and secure the section to the thimble by screwing the self-tapping  
screws through the holes in the tabs on the plate and into the outer wall of the vent. Apply silicone sealant around the vent  
section where it passes through the plate and around the plate where it is attached to the structure.  
To use as a Firestop before passing through ceilings or enclosed chases, prepare a round or square opening ¼” larger than  
the outer jacket (5¼” for 3” vent or 7¼” for 4” vent). Remove any insulation from the opening. Secure the restop to  
the structure at the four (4) corners. Install the vent section through the restop and secure to the thimble by screwing the  
self-tapping screws through the holes in the tabs on plate and into outer wall of the vent. This method can also be used to  
support the vent section either vertically or horizontally.  
Tall Cone Flashing:  
Directly On Roof or Curb:  
Tall Cones are available for at (SC_ _TCF), 2/12 pitch (SC_ _TCFA), and 6/12 - 12/12 pitch roofs (SC_ _TCFB).  
Prepare a square or round opening at least 1/4” larger than the outer jacket (5¼” for 3” vent or 7¼” for 4” vent). Remove  
any insulation from the opening. Apply weather-stripping or outdoor caulk to the bottom of the cone plate and attach the  
plate to the roof using common construction methods. Flash over the cone plate and seal the fastener heads using normal  
roong requirements. When the vent pipe is in place through the Tall Cone, attach a storm collar (sold separately) around  
the pipe. Apply high temperature silicone sealant around the pipe where it passes through the top of the storm collar.  
Continue to install vent sections as needed to meet the height requirements by code. Seal weather exposed joints of the  
outer jacket with foil tape or an exterior grade silicone sealant.  
35  
Vertical Terminations, (SC_ _VT): Install the vertical termination adapter into the last vent section and secure with the  
three (3) self-tapping screws provided. If the exhaust termination needs to be extended, a section of EZ Seal vent can be  
connected directly to the vertical termination adapter. Seal weather exposed joints of the outer jacket with foil tape or  
an exterior grade silicone sealant. To allow for inspection of the system, do not seal the exhaust termination.  
36  
H. Indoor Air Installation – See Figures 12, 13, 14, 15 and 16.  
1. Do not exceed maximum vent length. Refer to  
Table 4.  
Vertical –  
10. Installation of a vertical vent tee 8116304U is  
required on all vertical vent applications. See  
Figure 6. Attach vertical vent drain tee directly to  
elbow or horizontal pipe from an elbow immediately  
after vent connector.  
Horizontal –  
2. Maintain minimum ¼ inch per foot slope in  
horizontal runs.  
3 Recommended horizontal installation consists of  
vent being sloped down away from boiler. See  
Figure 12.  
11. Install re stops where vent passes through oors,  
ceilings or framed walls. The re stop must close  
the opening between the vent pipe and the structure.  
Fire stop manufacturers are Air-Jet, American Metal  
Products, Metal-Fab, and Simpson Dura-Vent.  
4. Slope horizontal runs minimum ¼ inch per foot.  
Slope towards vertical vent drain tee. Position weld  
seams in vent pipes, in all horizontal runs, at the top  
to avoid condensate from lying on the seams.  
12. Whenever possible install vent straight through roof.  
Refer to Figure 13 if offset is necessary. Maintain  
minimum clearance to combustible materials.  
5. Use appropriately designed thimbles when passing  
through combustible walls (thimble use optional  
for noncombustible walls). Insert thimble through  
wall from outside. Secure outside ange to wall  
with nails or screws, and seal with sealant material.  
Install inside ange to inside wall, secure with nails  
or screws, and seal with sealant material.  
13. Install Vent Terminal.  
a. Size roof opening to maintain minimum  
clearance from combustible materials.  
b. Use appropriately designed vent ashing  
when passing through roofs. Follow ashing  
manufacturers’ instructions for installation  
procedures. Flashing manufacturers are Air-  
Jet, American Metal Products, Metal Fab, and  
Simpson Dura-Vent.  
6. For noncombustible wall application when thimble  
is not used, size opening such that female (bell) end  
with locking band attached cannot pass through.  
7. Join vent terminal to vent pipe. Locate vent  
terminal between seventeen (17) inches and twenty-  
nine (29) inches from wall when joined to inside  
vent piping. See Figure 14.  
c. Extend vent pipe to maintain minimum vertical  
and horizontal distance of twelve (12) inches  
from roof surface. Allow additional vertical  
distance for expected snow accumulation.  
Provide brace as required. Refer to Figure 15.  
8. Insert vent pipe through thimble/opening from  
outside and join to vent system. Apply sealant  
between vent pipe and opening/thimble to provide  
weathertight seal.  
d. Vertical venting requires ashing and a storm  
collar to prevent moisture from entering the  
structure.  
9. Join vent terminal to 45° elbow included in kit. Join  
45° elbow/terminal assembly to vent pipe. Refer  
to Section C for proper procedures for joining vent  
pipe and ttings. See Figure 3 .  
e. Install storm collar on vent pipe immediately  
above ashing. Apply Dow Corning Silastic 732  
RTV Sealant between vent pipe and storm collar  
to provide weathertight seal.  
f. Attach vent terminal.  
14. Install supplied air intake terminal onto collar of the  
jacket enclosure. See Figure 16.  
37  
38