Sanyo Xhx1852 User Manual

TEST RUN SERVICE MANUAL  
R410A Models  
Indoor Units  
Class  
4-Way Air Discharge Semi-Concealed  
1-Way Air Discharge Semi-Concealed AHX0752 AHX0952 AHX1252  
7
9
12  
18  
24  
36  
48  
X
A
U
D
T
XHX1252 XHX1852 XHX2452 XHX3652  
Concealed-Duct  
UHX0752  
UHX1252 UHX1852 UHX2452 UHX3652  
DHX3652 DHX4852  
Concealed-Duct High-Static Pressure  
Ceiling-Mounted  
THX1252 THX1852 THX2452  
KHX0752 KHX0952 KHX1252 KHX1852 KHX2452  
K
Wall-Mounted  
Outdooe Units  
Class  
90  
140  
C
ECO-i W-2WAY  
CHDX09053 CHDX14053  
85464849257000  
REFERENCE NO.  
SM830157  
Check of Density Limit  
2. The standards for minimum room volume are as fol-  
lows.  
The room in which the air conditioner is to be  
installed requires a design that in the event of refrig-  
erant gas leaking out, its density will not exceed a set  
limit.  
(1) No partition (shaded portion)  
The refrigerant (R410A), which is used in the air con-  
ditioner, is safe, without the toxicity or combustibility of  
ammonia, and is not restricted by laws imposed to protect  
the ozone layer. However, since it contains more than air,  
it poses the risk of suffocation if its density should rise  
excessively. Suffocation from leakage of refrigerant is  
almost non-existent. With the recent increase in the num-  
ber of high density buildings, however, the installation of  
multi air conditioner systems is on the increase because of  
the need for effective use of floor space, individual control,  
energy conservation by curtailing heat and carrying power,  
etc.  
(2) When there is an effective opening with the adjacent  
room for ventilation of leaking refrigerant gas (open-  
ing without a door, or an opening 0.15% or larger  
than the respective floor spaces at the top or bottom  
of the door).  
Outdoor unit  
Refrigerant tubing  
Most importantly, the multi air conditioner system is able  
to replenish a large amount of refrigerant compared to  
conventional individual air conditioners. If a single unit  
of the multi air conditioner system is to be installed in a  
small room, select a suitable model and installation pro-  
cedure so that if the refrigerant accidentally leaks out,  
its density does not reach the limit (and in the event of  
an emergency, measures can be made before injury can  
occur).  
In a room where the density may exceed the limit, create  
an opening with adjacent rooms, or install mechanical  
ventilation combined with a gas leak detection device.  
The density is as given below.  
Indoor unit  
(3) If an indoor unit is installed in each partitioned room  
and the refrigerant tubing is interconnected, the  
smallest room of course becomes the object. But  
when mechanical ventilation is installed interlocked  
with a gas leakage detector in the smallest room  
where the density limit is exceeded, the volume of the  
next smallest room becomes the object.  
Refrigerant tubing  
Total amount of refrigerant (lbs)  
Min. volume of the indoor unit installed room (ft.3)  
3
<
Density limit (oz/ft. )  
Outdoor unit  
The density limit of refrigerant which is used in multi air  
conditioners is 0.3 oz/ft.3 (ISO 5149).  
Very  
small  
Indoor unit  
room  
NOTE  
Small  
room  
Medium  
room  
Large room  
1.If there are 2 or more refrigerating systems in a single  
refrigerating device, the amount of refrigerant should be  
as charged in each independent device.  
Mechanical ventilation device – Gas leak detector  
3. The minimum indoor floor space compared with the  
amount of refrigerant is roughly as follows: (When the  
ceiling is 8.8 ft. high)  
For the amount of charge in this example:  
Outdoor unit  
ft.3  
4000  
ft.2  
454  
e.g., charged  
amount (353 oz)  
e.g., charged  
amount (529 oz)  
Range below  
the density limit of  
0.3 oz/ft.3  
(countermeasures  
not needed)  
3500  
3000  
2500  
2000  
1500  
1000  
500  
398  
341  
284  
227  
170  
114  
57  
Indoor unit  
Room A Room B Room C Room D Room E Room F  
Range above  
the density limit of  
0.3 oz/ft.3  
(countermeasures  
needed)  
The possible amount of leaked refrigerant gas in  
rooms A, B and C is 353 oz.  
The possible amount of leaked refrigerant gas in  
rooms D, E and F is 529 oz.  
0
0
0
200 400 600 800 1000 1200  
oz  
Total amount of refrigerant  
ii  
Contents  
Section 1: TEST RUN..............................................................................................................1-1  
1. Test Run...........................................................................................................1-2  
2. Setting of Unit Control PCB .............................................................................1-4  
3. Auto Address Setting .......................................................................................1-6  
4. Remote Controller Test Run Settings.............................................................1-12  
5. Caution for Pump Down.................................................................................1-13  
6. Meaning of Alarm Messages .........................................................................1-14  
Section 2: REMOTE CONTROL FUNCTIONS........................................................................2-1  
1. Main Operating Functions................................................................................2-2  
2. Wireless Remote Controller.............................................................................2-4  
3. Timer Remote Controller (RCS-TM80BG).....................................................2-15  
Section 3: TROUBLE DIAGNOSIS .........................................................................................3-1  
1. Contents of Remote Controller Switch Alarm Display......................................3-2  
2. Outdoor Unit Control PCB LED Display...........................................................3-4  
3. W-2WAY ECO-i Alarm Codes..........................................................................3-5  
4. Blinking (Inspection) Display on the Remote Controller ............................3-22  
Section 4: PCB AND FUNCTIONS .........................................................................................4-1  
1. Outdoor Unit Control PCB................................................................................4-2  
2. Indoor Unit Control PCB ..................................................................................4-6  
Section 5: SELF-DIAGNOSIS FUNCTION TABLE .................................................................5-1  
1. Self-Diagnosis Function Table..........................................................................5-2  
Section 6: SERVICE CHECKER .............................................................................................6-1  
1. Outdoor Unit Maintenance Remote Controller.................................................6-2  
iii  
Test Run  
Contents  
1.TEST RUN  
1. Test Run..............................................................................................................................1-2  
1. Preparing for Test Run......................................................................................................1-2  
2. Test Run Procedure..........................................................................................................1-3  
2. Setting of Unit Control PCB...............................................................................................1-4  
1. Main Outdoor Unit PCB Setting........................................................................................1-4  
3. Auto Address Setting.........................................................................................................1-6  
1. Auto Address Setting........................................................................................................1-6  
4. Remote Controller Test Run Setting ...............................................................................1-12  
5. Caution for Pump Down...................................................................................................1-13  
6. Meaning of Alarm Messages ...........................................................................................1-14  
1
1-1  
Test Run  
1.Test Run  
1. Preparing for Test Run  
Before attempting to start the air conditioner, check the fol-  
lowing.  
z
(1) All loose matter is removed from the cabinet, especially  
steel filings, bits of wire, and clips.  
ON  
(2) The control wiring is correctly connected and all electrical  
connections are tight.  
(Power must be turned ON  
at least 5 hours before  
attempting test run)  
(3) The protective spacers for the compressor used for trans-  
portation have been removed. If not, remove them now.  
(4) The transportation pads for the indoor fan have been  
removed. If not, remove them now.  
Power mains switch  
(5) The power has been connected to the unit for at least 5  
hours before starting the compressor. The bottom of the  
compressor should be warm to the touch and the crank-  
case heater around the feet of the compressor should be  
hot to the touch.  
(6) Both the gas and liquid tube service valves are open. If  
not, open them now.  
(7) Request that the customer be present for the trial run.  
Explain the contents of the instruction manual, then have  
the customer actually operate the system.  
1
(8) Be sure to give the instruction manual and warranty cer-  
tificate to the customer.  
(9) When replacing the control PCB, be sure to make all the  
same settings on the new PCB as were in use before  
replacement.  
The existing EEP ROM is not changed, and is connected  
to the new control PCB.  
Balance tube  
Liquid tube  
Gas tube  
1-2  
Test Run  
1.Test Run  
2.Test Run Procedure  
Recheck the items to check before the test run.  
Items to Check Before the Test Run  
1. Turn the remote power switch on at least 5 hours before  
the test, in order to energize the crankcase heater.  
NO  
2. After performing the leak inspection, applying vacuum,  
and performing refrigerant charge for the tubing which  
is connected on-site, fully open the outdoor unit service  
Have the outdoor sub units been connected?  
YES  
<Outdoor unit control PCB>  
Unit No. setting switch  
(S007)  
*1 The unit with the unit  
*1  
valve. However if only one outdoor unit is installed, a  
balance tube is not used. Therefore, leave the valve fully  
closed.  
Set the unit address.  
No. set to 1 is the  
main unit. All other  
units are sub units.  
<Outdoor unit control PCB>  
Unit No. setting switch  
(S006)  
3. When replacing the control PCB, be sure that the settings  
on the new PCB match those on the old PCB.  
Set the No. of outdoor units.  
Set the No. of indoor units.  
4. Use caution when making the settings. If there are dupli-  
cated system addresses, or if the settings for the Nos. of  
the indoor units are not consistent, an alarm will occur  
and the system will not start.  
<Outdoor unit control PCB>  
Unit No. setting switch  
(S004 and S005)  
5. These settings are not made on the indoor unit PCB.  
Are the inter-unit control wires  
connected to more than 1 refrigerant  
system?  
CASE 1  
NO  
(Check the link wiring.)  
<Outdoor unit control PCB>  
Unit No. setting switch  
(S002 and S003)  
YES  
Set the system address.  
When multiple outdoor main units exist, disconnect the terminals  
extended from the shorted plugs (CN003) at all outdoor main unit  
PCBs except for 1.  
Note: It is not necessary to remove  
the socket that is used to short-  
circuit the terminal plugs from  
the outdoor sub unit PCBs.  
1
Alternatively, move the sockets to the OPEN side.  
CASE 2  
Is it possible to turn ON the power only  
for the 1 refrigerant system where the  
test run will be performed?  
YES  
Turn ON the indoor and  
outdoor unit power for that  
refrigerant system only.  
NO  
Will automatic address setting be  
performed in Heating mode?  
Make necessary corrections.  
Short-circuit the automatic address pin (CN100)  
on the outdoor main unit PCB for 1 second or  
longer, then release it.  
NO  
Turn OFF the indoor and  
outdoor unit power.  
YES  
CASE 3B  
CASE 3A  
LED 1 and 2 blink alternately  
(about 2 or 3 minutes).  
Is it OK to start the compressors?  
Is it OK to start the compressors?  
Check the alarm contents.  
Turn ON the indoor and  
outdoor unit power.  
Turn ON the indoor and  
outdoor unit power.  
NO  
Are LED 1 and 2 on the  
outdoor unit PCB OFF?  
Make necessary  
corrections  
*2  
*2  
Refer to "Table of Self-  
Diagnostic Functions and  
Description of Alarm Displays."  
Short-circuit the mode change pin  
Short-circuit the automatic address  
pin (CN100) on the outdoor main  
unit PCB for 1 second or longer,  
then release it.  
(CN101) on the outdoor main unit PCB.  
At the same time, short-circuit the  
automatic address pin (CN100) for 1  
second or longer, then release it.  
YES  
Turn OFF the indoor  
and outdoor unit  
*3  
*3  
Start indoor and outdoor unit  
cooling operation.  
LED 1 and 2 blink alternately.  
Start indoor and outdoor unit  
heating operation.  
Check the alarm  
contents.  
LED 1 and 2 blink alternately.  
*2 A minimum of 5 hours must have passed after the  
power was turned ON to the outdoor unit.  
*3 All indoor units operate in all refrigerant systems  
where the power is ON.  
NO  
Are LED 1 and 2 on the  
outdoor unit PCB OFF?  
YES  
Check that test run preparation is OK.  
(Do not allow the short-circuited pins to remain short-circuited.)  
Set the wired remote controller for test run.  
Refer to the remote  
controller test-run  
settings.  
NO  
Check and make corrections according to  
"Table of Self-Diagnostic Functions."  
Does system operate?  
YES  
Return remote control to normal mode  
End test run.  
1-3  
Test Run  
2. Setting of Unit Control PCB  
1. Main Outdoor Unit PCB Setting  
S004  
S005  
S006  
S007  
S002  
S003  
CN100  
CN101  
CN003  
1
1-4  
Test Run  
2. Setting of Unit Control PCB  
Examples of the No. of indoor units settings (S005, S004)  
z
Indoor unit setting (S005)  
Indoor unit setting (S004)  
(Rotary switch, red)  
No. of indoor units  
(3P DIP switch, blue)  
10 20 30  
ON  
ON  
1 unit (factory setting)  
11 units  
All OFF  
Set to 1  
Set to 1  
Set to 1  
Set to 1  
Set to 0  
2
2
2
2
2
3
3
3
3
3
1
OFF  
ON  
ON  
1 ON  
1
OFF  
ON  
ON  
21 units  
2 ON  
1
OFF  
ON  
ON  
31 units  
3 ON  
1
OFF  
ON  
ON  
40 units  
1 & 3 ON  
1
OFF  
Examples of refrigerant circuit (R.C.) address settings (required when link wiring is used) (S003, S002)  
z
System address (S003)  
System address (S002)  
(Rotary switch, black)  
System address No.  
(2P DIP switch, blue)  
10 20  
ON  
ON  
Set to 1  
Both OFF  
System 1 (factory setting)  
System 11  
2
2
2
2
1
OFF  
ON  
ON  
1
1 ON  
Set to 1  
Set to 1  
Set to 0  
1
OFF  
ON  
ON  
System 21  
2 ON  
1
OFF  
ON  
ON  
System 30  
1 & 2 ON  
1
OFF  
Examples of the No. of outdoor units settings (S006)  
z
Outdoor unit setting (S006)  
No. of outdoor units  
(3P DIP switch, blue)  
ON  
ON  
1 unit (factory setting)  
1 ON  
2 ON  
1
2
2
2
3
3
3
OFF  
ON  
ON  
2 units  
3 units  
1
OFF  
ON  
ON  
1 & 2 ON  
1
OFF  
Address setting of main outdoor unit (S007)  
z
z
Address setting of outdoor unit (S007)  
(3P DIP switch, blue)  
Unit No. setting  
ON  
ON  
Unit No. 1 (main unit)  
(factory setting)  
1
2
3
OFF  
Address setting of sub outdoor unit  
Address setting of outdoor unit (S007)  
(3P DIP switch, blue)  
Unit No. setting  
ON  
ON  
Unit No. 2 (sub unit)  
(factory setting)  
2 ON  
1
2
2
3
3
OFF  
ON  
ON  
Unit No. 3 (sub unit)  
1 & 2 ON  
1
OFF  
The sub unit control PCB contains the same switches as the main unit control PCB for No. of indoor units, No. of outdoor units,  
and system address. However it is not necessary to set these switches.  
1-5  
Test Run  
3. Auto Address Setting  
1. Auto Address Setting  
Basic wiring diagram: Example (1)  
• If link wiring is not used  
(The inter-unit control wires are not connected to multiple refrigerant systems.)  
Indoor unit addresses can be set without operating the compressors.  
No. 1 (main outdoor unit)  
settings  
No. of indoor units  
(10 units setting)  
System address  
(S004)  
(system 1 setting)  
0
(S002) (S003)  
ON  
ON  
OFF  
(S005)  
ON  
No. 3 (sub unit)  
No. 2 (sub unit)  
ON  
1
2
1
2
3
OFF  
Unit  
number  
setting  
(S007)  
ON  
Unit  
number  
setting  
(S007)  
No. of  
outdoor  
(S006)  
ON  
(S007)  
ON  
ON  
OFF  
ON  
Unit number  
setting  
(Unit No. 1)  
ON  
ON  
ON  
units (3 units  
setting)  
OFF  
1
2
3
1
2
3
(Unit No. 3)  
1
2
3
OFF  
(Unit No. 2)  
1
2
3
OFF  
Leave the socket that  
is used to short-circuit  
the terminal plug.  
(CN003)  
Unit  
No. 1  
(Main)  
Unit  
No. 2  
(Sub)  
Unit  
No. 3  
(Sub)  
Outdoor Unit  
Outdoor main/sub  
control wiring  
Outdoor main/sub  
control wiring  
Inter-unit control wiring  
1
Indoor Unit  
1-1  
1-2  
1-3  
1-10  
Remote controller  
cross-over wiring  
Remote controller  
Case 1  
(1) Automatic Address Setting from the Outdoor Unit  
1. To set the number of outdoor units, on the outdoor main unit control PCB set the No. of outdoor units DIP switch (S006) to  
ON  
ON  
ON  
(3 units), and set the unit No. DIP switch (S007) to  
(unit No. 1 - main outdoor unit).  
1
2
3
1
2
3
OFF  
ON  
2. On the No. 2 (sub) unit control PCB, set the unit No. switch (S007) to  
On the No. 3 (sub) unit control PCB, set the unit No. switch (S007) to  
(unit No. 2).  
1
2
2
3
ON  
(unit No. 3).  
1
3
3. On the outdoor main unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the DIP  
ON  
ON  
switch (S003) is set to  
“0.(These are the settings at the time of factory shipment.)  
1
2
OFF  
4. To set the number of indoor units that are connected to the outdoor unit to 10, on the outdoor main unit control PCB set the  
ON  
ON  
No. of indoor units DIP switch (S005) to  
“1.and set the rotary switch (S004) to “0.”  
1
2
3
OFF  
5. Turn ON the power to the indoor and outdoor units.  
6. On the outdoor main unit control PCB, short-circuit the automatic address pin (CN100) for 1 second or longer, then release it.  
(Communication for automatic address setting begins.)  
* To cancel, again short-circuit the automatic address pin (CN100) for 1 second or longer, then release it.  
The LED that indicates that automatic address setting is in progress turns OFF and the process is stopped.  
Be sure to perform automatic address setting again.  
(Automatic address setting is completed when LEDs 1 and 2 on the outdoor main unit control PCB turn OFF.)  
7. Operation from the remote controllers is now possible.  
* To perform automatic address setting from the remote controller, perform steps 1 to 5, then use the remote controller and  
complete automatic address setting.  
Refer to “Automatic Address Setting from the Remote Controller.”  
1-6  
z
Test Run  
3. Auto Address Setting  
Basic wiring diagram: Example (2)  
* When multiple outdoor main units exist, remove the socket that is  
used to short-circuit the terminal plug (CN003) from all outdoor  
main unit PCBs except for one unit.  
• If link wiring is used  
No. 1 (main outdoor unit) settings  
No. of indoor units  
(13 units setting)  
(S004)  
System address  
(system 1 setting)  
Alternatively, move the sockets to the “OPEN” side.  
(S002) (S003)  
ON  
OFF  
ON  
1
2
(S005)  
ON  
ON  
No. 2 (sub unit)  
No. 3 (sub unit)  
1
2
3
OFF  
No. of  
outdoor units  
(3 units  
(S006)  
ON  
Unit  
number  
setting  
(S007)  
Unit  
Unit  
(S007)  
ON  
(S007)  
ON  
ON  
ON  
ON  
ON  
number  
setting  
(unit No. 3)  
ON  
number  
setting  
(unit No. 2)  
setting)  
1
2
3
1
2
3
(unit No. 1)  
OFF  
OFF  
2
3
1
OFF  
1
2
3
OFF  
Leave the socket that  
is used to short-circuit  
the terminal plug.  
(CN003)  
Unit  
No. 1  
(Main)  
Unit  
No. 2  
(Sub)  
Unit  
No. 3  
(Sub)  
Outdoor unit  
system 1  
Outdoor main/sub  
control wiring  
Inter-unit control wiring  
1
1-1  
1-2  
1-3  
1-13  
Indoor unit  
Remote controller  
communication wiring  
Remote  
controller  
No. 1 (main unit) settings  
System address  
(system 2 setting)  
No. 2  
Refrigerant  
circuit  
No. of indoor units  
(9 units setting)  
(S004)  
(S002) (S003)  
ON  
OFF  
ON  
1
2
(S005)  
ON  
ON  
No. 2 (sub unit) settings  
1
2
3
OFF  
Unit  
(S007)  
ON  
No. of  
outdoor  
units (2 units  
setting)  
(S006)  
ON  
Unit  
number  
setting  
(S007)  
ON  
ON  
number  
setting  
(unit No. 2)  
ON  
ON  
1
2
3
OFF  
2
3
1
2
3
1
(unit No. 1)  
OFF  
OFF  
Unit  
No. 1  
(Main)  
Unit  
No. 2  
(Sub)  
Move the socket to  
the OPEN side  
(CN003).  
Outdoor unit  
system 2  
Outdoor main/sub control wiring  
Inter-unit control wiring  
Indoor unit  
2-1  
2-2  
2-9  
To other system  
link wiring  
Remote controller  
cross-over wiring  
Remote  
controller  
Make settings as appropriate for the cases listed below.  
(Refer to the instructions on the following pages.)  
· Indoor and outdoor unit power can be turned ON for each system separately.  
Case 2  
· Indoor and outdoor unit power cannot be turned ON for each system separately.  
Automatic address setting in Heating mode  
Case 3A  
Case 3B  
Automatic address setting in Cooling mode  
1-7  
Test Run  
3. Auto Address Setting  
Case 2 Automatic Address Setting (no compressor operation)  
Indoor and outdoor unit power can be turned ON for each system separately.  
Indoor unit addresses can be set without operating the compressors.  
z
Automatic Address Setting from Outdoor Unit  
ON  
1. On the No. 1 (main) unit control PCB, set the unit No. switch (S007) to  
(unit No. 1).  
1
2
3
ON  
On the No. 2 (sub) unit control PCB, set the unit No. switch (S007) to  
On the No. 3 (sub) unit control PCB, set the unit No. switch (S007) to  
(unit No. 2).  
(unit No. 3).  
1
2
2
3
3
ON  
1
2. To set the number of outdoor units on the outdoor main unit control PCB, set the No. of outdoor units DIP switch (S006) to  
ON  
ON  
(3 units).  
1
2
3
OFF  
3. On the outdoor main unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the DIP  
ON  
ON  
1
switch (S003) is set to “0”  
. (These are the settings at the time of factory shipment.)  
1
2
OFF  
4. To set the number of indoor units that are connected to the outdoor unit to 13, on the outdoor main unit control PCB set the  
ON  
ON  
No. of indoor units DIP switch (S005) to “1”  
, and set the rotary switch (S004) to “3.”  
1
2
3
OFF  
5. Turn on power to all indoor and outdoor units in the system.  
6. Short-circuit the automatic address pin at the outdoor main unit (CN100) for 1 second or longer, then release it.  
(Communication for automatic address setting begins.)  
* To cancel, again short-circuit the automatic address pin (CN100) for 1 second or longer, then release it.  
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped. Be  
sure to perform automatic address setting again.  
(Automatic address setting is completed when LEDs 1 and 2 on the outdoor main unit control PCB turn OFF.)  
7. Next turn the power ON only for the indoor and outdoor units of the next (different) system. Repeat steps 1 - 5 in the same  
way to complete automatic address settings for all systems.  
8. Operation from the remote controllers is now possible.  
* To perform automatic address setting from the remote controller, perform steps 1 - 5, then use the remote controller and  
complete automatic address setting.  
Refer to “Automatic Address Setting from Remote Controller.”  
z
1-8  
Test Run  
3. Auto Address Setting  
Case 3A Automatic Address Setting in Heating Mode  
Indoor and outdoor unit power cannot be turned ON for each system separately.  
z
In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating.  
Therefore perform this process only after completing all refrigerant tubing work.  
Automatic Address Setting from Outdoor Unit  
Case 2  
1. Perform steps 1 - 4 in the same way as for  
.
5. Turn the indoor and outdoor unit power ON at all systems.  
6. To perform automatic address setting in Heating mode , on the outdoor main unit control PCB in the refrigerant system  
where you wish to set the addresses, short-circuit the automatic address pin (CN100) for 1 second or longer, then release  
it. (Be sure to perform this process for one system at a time. Automatic address settings cannot be performed for more than  
one system at the same time.)  
(Communication for automatic address setting begins, the compressors turn ON, and automatic address setting in Heating  
mode begins.)  
(All indoor units operate.)  
* To cancel, again short-circuit the automatic address pin (CN100) for 1 second or longer, then release it. The  
LED that indicates automatic address setting is in progress turns OFF and the process is stopped. Be sure to  
perform automatic address setting again.  
1
(Automatic address setting is completed when the compressors stop and LED 1 and 2 on the main unit control PCB turn  
OFF.)  
7. At the outdoor main unit in the next (different) system, short-circuit the automatic address pin (CN100) for 1 second or  
longer, then release it.  
(Repeat the same steps to complete automatic address setting for all units.)  
8. Operation from the remote controllers is now possible.  
* To perform automatic address setting from the remote controller, perform steps 1 - 5, then use the remote controller and  
to complete automatic address setting.  
Refer to “Automatic Address Setting from Remote Controller.”  
z
1-9  
Test Run  
3. Auto Address Setting  
Case 3B Automatic Address Setting in Cooling Mode  
Indoor and outdoor unit power cannot be turned ON for each system separately. In the following, automatic setting of indoor  
unit addresses is not possible if the compressors are not operating. Therefore perform this process only after completing all  
refrigerant tubing work.  
z
Automatic address setting can be performed during Cooling operation.  
Automatic Address Setting from Outdoor Unit  
Case 2  
1. Perform steps 1 - 4 in the same way as for  
.
5. Turn the indoor and outdoor unit power ON at all systems.  
6. To perform automatic address setting in Cooling mode , on the outdoor main unit control PCB in the refrigerant system  
where you wish to set the addresses, short-circuit the mode change 2P pin (CN101). At the same time, short-circuit the  
automatic address pin (CN100) for 1 second or longer, then release it. (Be sure to perform this process for one system at a  
time. Automatic address settings cannot be performed for more than one system at the same time.)  
(Communication for automatic address setting begins, the compressors turn ON, and automatic address setting in Cooling  
mode begins.)  
(All indoor units operate.)  
* To cancel, again short-circuit the automatic address pin (CN100) for 1 second or longer, then release it. The  
LED that indicates automatic address setting is in progress turns OFF and the process is stopped. Be sure to  
perform automatic address setting again.  
1
(Automatic address setting is completed when the compressors stop and LED 1 and 2 on the outdoor main unit control PCB  
turn OFF.)  
7. At the outdoor main unit in the next (different) system, short-circuit the automatic address pin (CN100) for 1 second or  
longer, then release it.  
(Repeat the same steps to complete automatic address setting for all units.)  
8. Operation from the remote controllers is now possible.  
* Automatic address setting in Cooling mode cannot be done from the remote controller.  
Automatic Address Setting* from the Remote Controller  
Selecting each refrigerant system individually for automatic address setting  
---Automatic address setting for each system: Item code “A1.”  
1. Press the remote controller timer time  
button and  
or  
button at the same  
button. (Check that  
time.  
(Press and hold for 4 seconds or longer.)  
2. Next, press either the temperature setting  
the item code is “A1.)  
3. Use either the  
or  
button to set the system No. to perform auto-  
matic address setting.  
4. Then press the  
button.  
(Automatic address setting for one refrigerant system begins.)  
(When automatic address setting for one system is completed, the system returns  
to normal stopped status.) <Approximately 4 - 5 minutes is required.>  
(During automatic address setting, “NOW SETTING” is displayed on the remote  
controller. This message disappears when automatic address setting is completed.)  
5. Repeat the same steps to perform automatic address setting for each successive system.  
1-10  
Test Run  
3. Auto Address Setting  
Display during automatic address setting  
On outdoor main unit PCB  
z
1
2
LED  
*
Do not short-circuit the automatic address setting pin (CN100) again while automatic address setting is in  
progress. Doing so will cancel the setting operation and will cause LED 1 and 2 to turn OFF.  
Blink alternately  
*
*
*
When automatic address setting has been successfully completed, both LED 1 and 2 turn OFF.  
LED 1 is D72. LED 2 is D75.  
If automatic address setting is not completed successfully, refer to the table below and correct the problem. Then perform  
automatic address setting again.  
Display of LED 1 and 2 on the outdoor unit control PCB  
z
(
: ON  
: Blinking  
:OFF)  
LED1  
LED2  
Display meaning  
After the power is turned ON (and automatic address setting is not in progress), no communication with the indoor  
units in that system is possible.  
After the power is turned ON (and automatic address setting is not in progress), 1 or more indoor units are  
confirmed in that system; however, the number of indoor units does not match the number that was set.  
1
Automatic address setting is in progress.  
Alternating  
Automatic address setting completed.  
At time of automatic address setting, the number of indoor units did not match the number that was set.  
”(when indoor units are operating) indication appears on the display.  
Simultaneous  
Alternating  
Refer to “Table of Self-Diagnostic Functions and Description of Alarm Displays.”  
Note: “ ” indicates that the solenoid is fused or that there is a CT detection current failure (current is detected when the com-  
pressor is OFF).  
Remote controller display  
z
is blinking  
1-11  
Test Run  
3. Auto Address Setting  
4. Remote Controller Test Run Settings  
Request concerning recording the indoor/outdoor unit combination Nos.  
After automatic address setting has been completed, be sure to record them for future reference.  
List the outdoor main unit system address and the addresses of the indoor units in that system in an easily visible location (next  
to the nameplate), using a permanent marking pen or similar means that cannot be abraded easily.  
Example: (Outdoor) 1 - (Indoor) 1-1, 1-2, 1-3…  
(Outdoor) 2 - (Indoor) 2-1, 2-2, 2-3…  
These numbers are necessary for later maintenance. Please be sure to indicate them.  
Checking the indoor unit addresses  
Use the remote controller to check the indoor unit address.  
<If 1 indoor unit is connected to 1 remote controller>  
1. Press and hold the  
button and  
button for 4 seconds or longer (simple settings mode).  
2. The address is displayed for the indoor unit that is connected to the remote controller.  
(Only the address of the indoor unit that is connected to the remote controller can be checked.)  
3. Press the  
button again to return to normal remote controller mode.  
<If multiple indoor units are connected to 1 remote controller (group control)>  
1. Press and hold the  
2. “ALL is displayed on the remote controller.  
3. Next, press the button.  
button and  
button for 4 seconds or longer (simple settings mode).  
4. The address is displayed for 1 of the indoor units which is connected to the remote controller. Check that the fan of that  
indoor unit starts and that air is discharged.  
1
5. Press the  
6. Press the  
button again and check the address of each indoor unit in sequence.  
button again to return to normal remote controller mode.  
Number changes to indicate which indoor unit is currently selected.  
4. Remote Controller Test Run Settings  
1. Press the remote controller  
button for 4 seconds or longer. Then press the  
button.  
“TEST RUN” appears on the LCD display while the test run is in progress.  
The temperature cannot be adjusted when in Test Run mode.  
(This mode places a heavy load on the machines. Therefore use it only when performing the test run.)  
2. The test run can be performed using the HEAT, COOL, or FAN operation modes.  
Note: The outdoor units will not operate for approximately 3 minutes after the power is turned ON and after operation is  
stopped.  
3. If correct operation is not possible, a code is displayed on the remote controller LCD display.  
(Refer to “Table of Self-Diagnostic Functions” and correct the problem.)  
4. After the test run is completed, press the  
button again. Check that “TEST RUN” disappears from the LCD display. (To  
prevent continuous test runs, this remote controller includes a timer function that cancels the test run after 60 minutes.)  
If the test run is performed using the wired remote controller, operation is possible even if the cassette-type ceiling panel has  
not been installed. (“P09” display does not occur.)  
*
1-12  
Test Run  
5. Caution for Pump Down  
5. Caution for Pump Down  
Pump down means refrigerant gas in the system is returned to the outdoor unit. Pump down is used when the unit is to be  
moved, or before servicing the refrigerant circuit.  
This outdoor unit cannot collect more  
than the rated refrigerant amount as  
shown by the nameplate on the back.  
If the amount of refrigerant is more  
than that recommended, do not  
CAUTION  
conduct pump down. In this case use  
another refrigerant collecting system.  
1
1-13  
Test Run  
6. Meaning of Alarm Messages  
6. Meaning of Alarm Messages  
Table of Self-Diagnostics Functions and Description of Alarm Displays  
Alarm messages are indicated by the blinking of LED 1 and 2 (D72, D75) on the outdoor unit PCB. They are also displayed on  
the wired remote controller.  
Viewing the LED 1 and 2 (D72 and D75) alarm displays  
z
LED1  
LED2  
Alarm contents  
Alarm Display  
LED 1 blinks M times, then LED 2 blinks N times. The cycle then repeats.  
M = 2: P alarm 3: H alarm 4: E alarm 5: F alarm 6: L alarm  
N = Alarm No.  
Alternating  
Example: LED 1 blinks 2 times, then LED 2 blinks 17 times. The cycle then repeats.  
Alarm is "P17".  
(
: Blinling) Connect the outdoor maintenance remote controller to the RC socket on the outdoor main unit control PCB (3P,  
blue),and check the Alarm Messages on the remote controller display.  
Alarm  
Message  
Possible cause of malfunction  
Serial  
Remote controller is detecting  
error signal from indoor unit.  
Error in receiving serial communication signal.  
(Signal from main indoor unit in case of group control)  
Ex: Auto address is not completed.  
communication  
errors  
<E01>  
Mis-setting  
Error in transmitting serial communication signal.  
<E02>  
Indoor unit is detecting error signal from remote controller (and system controller).  
<<E03>>  
Indoor unit is detecting error  
signal from main outdoor unit.  
Error in receiving serial communication signal.  
When turning on the power supply, the number of connected indoor units  
does not correspond to the number set. (Except R.C. address is "0.")  
E04  
1
Error of the main outddor unit in receiving serial communication signal  
from the indoor unit.  
<E06>  
E08  
Improper setting of indoor unit  
or remote controller.  
Indoor unit address setting is duplicated.  
Remote controller adress connector (RCU. ADR) is duplicated.  
(Duplication of main remote controller)  
<<E09>>  
During auto address setting,  
Starting auto address setting is prohibited.  
number of connected units does This alarm message shows that the auto address connector CN100 is  
E12  
not correspond to number set.  
shorted while other RC line is executing auto address operation.  
Error in auto address setting. (Number of connected indoor units is less  
than the number set.)  
E15  
E16  
When turning on the power  
supply, number of connected  
units does not correspond to  
number set.  
Error in auto address setting. (Number of connected indoor units is more  
than the number set.)  
No indoor unit is connected during auto address setting.  
Main outdoor unit is detecting error signal from sub outdoor unit.  
Error of outdoor unit address setting.  
E20  
E24  
E25  
(Except R.C. address is "0.")  
The number of connected main and sub outdoor units do not correspond  
to the number set at main outdoor unit PCB.  
E26  
E29  
E18  
L02  
Error of sub outdoor unit in receiving serial communication signal from  
main outdoor unit.  
Indoor unit communication error Error of main indoor unit in receiving serial communication signal from  
of group control wiring.  
sub indoor units.  
Improper setting.  
This alarm message shows when an indoor unit for multiple-useis not  
connected to the outdoor unit.  
Duplication of main indoor unit address setting in group control.  
Duplication of outdoor R.C. address setting.  
<L03>  
L04  
There are 2 or more indoor unit  
controllers that have oparation  
mode priority in refrigerant circuit.  
Priority set remote controller  
L05  
Non-priority set remote controller  
L06  
L07  
Group control wiring is connected to individual control indoor unit.  
Indoor unit address is not set.  
L08  
Capacity code of indoor unit is not set.  
<<L09>>  
L10  
Capacity code of outdoor unit is not set.  
Mis-matched connection of outdoor units that have different kinds of  
refrigerant.  
L17  
4-way valve operation failure  
L18  
<<P01>>  
<<P09>>  
<<P10>>  
P12  
Activation of  
protective  
device  
Protective device in indoor unit  
is activated.  
Thermal protector in indoor unit fan motor is activated.  
Improper wiring connections of ceiling panel.  
Float switch is activated.  
Operation of protective function of fan inverter.  
O2 sensor (detects low oxygen level) activated.  
P14  
Continued  
1-14  
Test Run  
6. Meaning of Alarm Messages  
Alarm  
Message  
Possible cause of malfunction  
Activation of  
protective  
device  
Protective device in outdoor unit Compressor therminal protector is activated.  
is activated.  
Power supply voltage is unusual. (The voltage is more than 260 V or less  
than 160 V between L1 and L2 phase.)  
P02  
Incorrect discharge temperature. (Comp. No. 1)  
High pressure switch is activated.  
Negtive (defective) phase.  
P03  
P04  
P05  
Compressor running failure resulting from missing phase in the  
compressor wiring, etc. (Start failure not caused by IPM or no gas.)  
P16  
Incorrect discharge temperature. (Comp. No. 2)  
Compressor 3 discharge temp. failure  
Outdoor unit fan motor is unusual.  
P17  
P18  
P22  
Overcurrent at time of compressor runs more than 80Hz (DCCT  
secondary current or ACCT primary current is detected at a time other  
than when IPM has tripped.)  
P26  
IPM trip (IPM current or temperature)  
H31  
P29  
Inverter for compressor is unusual. (DC compressor does not operate.)  
Indoor coil temp. sensor (E1)  
Thermistor fault  
Indoor thermistor is either open  
or damaged.  
<<F01>>  
<<F02>>  
<<F03>>  
<<F10>>  
<<F11>>  
F04  
Indoor coil temp. sensor (E2)  
Indoor coil temp. sensor (E3)  
Indoor suction air (room) temp. sensor (TA)  
Indoor discharge air temp. sensor (BL)  
1
Outdoor thermistor is either  
open or damaged.  
Comp. No. 1 discharge gas temp. sensor (DISCH1)  
Comp. No. 2 discharge gas temp. sensor (DISCH2)  
Outdoor No. 1 coil gas temp. sensor (EXG1)  
Outdoor No. 1 coil liquid temp. sensor (EXL1)  
Outdoor air temp. sensor (AIR TEMP)  
F05  
F06  
F07  
F08  
Compressor intake port temperature sensor (RDT)  
High pressure sensor. Negative (defective) N phase.  
Low-pressure sensor failure  
F12  
F16  
F17  
Compressor 3 discharge temp. sensor failure (DISCH3)  
Outdoor No. 2 coil gas temp. sensor (EXG2)  
Outdoor No. 2 coil liquid temp. sensor (EXL2)  
F22  
F23  
F24  
EEP ROM on indoor unit PCB failure  
F29  
Protective  
device for  
compressor is  
activated  
Protective device for  
compressor No.1 is activated.  
EEP ROM on the main or sub outdoor unit PCB has failed.  
Current is not detected when comp. No. 1 is ON.  
F31  
H03  
Discharge gas temperature of the comp. No. 1 is not detected.  
Temp. sensor is not seated at the sensor holder.  
H05  
Protective device for  
compressor No.2 is activated  
Overload current is detected.  
H11  
H12  
H13  
H15  
H21  
H22  
H23  
H25  
H06  
H07  
H08  
H27  
H28  
Lock current is detected.  
Current is not detected when comp. No.2 is ON.  
Discharge gas temperture of comp. No.2 is not detected.  
Compressor No.3 current trouble (overcurrent)  
Compressor No.3 current trouble (locked)  
Compressor No.3 CT sensor disconnected or short circuit  
Compressor No.3 discharge temp. sensor disconnected  
Low pressure switch is activated.  
Protective device for  
compressor No.3 is activated.  
Low oil level.  
Oil sensor fault.  
(Disconnection, etc.)  
Comp. No.1 oil sensor  
Comp. No.2 oil sensor  
Oil sensor (connection) failure  
Continued  
1-15  
Test Run  
6. Meaning of Alarm Messages  
Alarm messages displayed on system controller  
Serial  
Error in transmitting serial  
communication signal  
Indoor or main outdoor unit is not oparating correctly.  
Mis-wiring of control wiring between indoor unit, main outdoor unit and  
system controller.  
communication  
errors  
C05  
C06  
P30  
Mis-setting  
Error in receiving serial  
communication signal  
Indoor or main outdoor unit is not operating correctly.  
Mis-wiring of control wiring between indoor unit, main outdoor unit and  
system controller.CN1 is not connected properly.  
Activation of  
protective  
device  
Protective device of sub indoor  
unit in group control is activated  
When using wireless remote controller or system controller, in order to  
check the alarm message in detail, connect wired remote controller to  
indoor unit temporarily.  
NOTE  
1. Alarm messages in << >> do not affect other indoor unit operations.  
2. Alarm messages in < > sometimes affect other indoor unit operations depending on the fault.  
1
1-16  
Remote Control Functions  
Contents  
2. REMOTE CONTROL FUNCTIONS  
1.Main Operating Functions ..................................................................................................2-2  
1. Room Temperature Control ..............................................................................................2-2  
2. Automatic Control for Heating and Cooling ......................................................................2-3  
2.Wireless Remote Controller ...............................................................................................2-4  
1. How to Use the Wireless Remote Controller ....................................................................2-4  
2. Receiver ...........................................................................................................................2-7  
3. Operation..........................................................................................................................2-8  
4. Using the Wireless Remote Control Unit..........................................................................2-9  
5. Address Settings ............................................................................................................2-10  
6. Emergency Operation.....................................................................................................2-12  
7. Troubleshooting ..............................................................................................................2-14  
3.Timer Remote Controller (RCS-TM80BG) ......................................................................2-15  
1. How to Use the Timer Remote Controller.......................................................................2-15  
2. Names and Operations...................................................................................................2-16  
3. Installation Manual for Timer Remote Controller ............................................................2-18  
4. How to Install the Remote Controller..............................................................................2-18  
5. Group Control Using 2 Remote Controllers....................................................................2-19  
6. Remote Controller Setting Mode....................................................................................2-19  
7. Indoor Unit Setting Mode................................................................................................2-19  
8. To Display the Sensor Temperature................................................................................2-19  
9. To Display the Trouble History ........................................................................................2-19  
10. Setting the Present Time..............................................................................................2-21  
11. Weekly Program Function ............................................................................................2-22  
12. Outing Function............................................................................................................2-27  
13. Sleeping Function.........................................................................................................2-29  
14. Wired Remote Controller Test Run Setting...................................................................2-30  
15. Simple Settings Function..............................................................................................2-31  
16. Detailed Settings Function............................................................................................2-33  
17. Remote Controller Servicing Functions........................................................................2-40  
2
2-1  
Remote Control Functions  
1. Main Operating Functions  
1. Room Temperature Control  
The thermostat is turned ON/OFF according to as shown below.  
T = Room temperature - Set temperature  
Room temperature = Temperature detected by the remote controller sensor  
Room temperature = Temperature detected by the body sensor - Intake shift temperature*  
When remote controller sensor  
is used  
When body sensor is used  
* Intake shift temperature (enabled only during heating)  
During heating, a difference in temperature occurs between the top and bottom of a room. This value is set in consideration for  
the difference between the temperature detected by the body sensor and the temperature at the bottom of the room.  
<Value set for intake shift temperature at time of shipment>: 39°F (4°C)  
Note: The shift temperature can be selected in the range of 32 – 50°F (0 – 10°C), by using the remote controller simplified set-  
ting mode.  
Cooling  
Heating  
T
T
Room temperature  
Room temperature  
(deg)  
(deg)  
+2  
+4  
+2  
Set temperature  
Set temperature  
–2  
–4  
–2  
Thermostat  
ON  
OFF  
ON  
Thermostat  
ON  
OFF  
ON  
2
(1) After the thermostat turns ON, it will not turn OFF again as a result of for 5 minutes.  
(2) After the thermostat turns OFF, it will not turn ON again for 3 minutes. (It also will not turn ON for 3 minutes after the power  
is switched ON.)  
(3) The compressor turns OFF if the mode is changed cooling  
heating (or heating  
cooling) while the compressor is ON.  
(4) If “test run” mode is selected, the thermostat will not turn OFF as a result of for 60 minutes. (The thermostat is forced ON.)  
2-2  
Remote Control Functions  
1. Main Operating Functions  
2. Automatic Control for Heating and Cooling  
Automatic Heating/Cooling Control  
(1) When operation starts, heating or cooling is selected according to the set temperature and the room temperature.  
Room temperature Set temperature + 2F Cooling  
Set temperature – 2F < Room temperature Set temperature + 2F  
Room temperature < Set temperature – 2F Heating  
Monitoring mode (*1)  
*1: If the difference between the room temperature and set temperature is small when operation starts, the cooling  
thermostat remains in standby status (OFF) until the temperature difference increases. When the temperature differ-  
ence increases, either cooling operation or heating operation is selected. This standby status is known as “monitoring  
mode.”  
(2) After operation starts in the selected operating mode, the set temperature is automatically shifted by + 4°F (2°C) (cooling  
operation) or – 4°F (2°C) (heating operation).  
Example: Temperature set on the remote controller is 68°F (20°C).  
Selected operating mode  
Cooling  
Shifted set temp.  
Remote controller display  
1
2
72°F  
64°F  
68°F  
68°F  
(22°C)  
(18°C)  
(20°C)  
(20°C)  
Heating  
(3) Operating mode changes (heating  
cooling, cooling  
heating) which occur during operation as a result of temperature  
changes are handled as shown below.  
Heating  
Cooling  
cooling: Room temperature  
heating: Room temperature  
Shifted set temperature (set temperature + 4F (2°C)) + 1F (0.5°C)  
Shifted set temperature (set temperature – 4F (2°C)) – 2F (1.0°C)  
Example: Temperature set on the remote controller is 68°F (20°C).  
Operating mode change  
Shifted set temp.  
68 + 4 + 1 = 73°F or higher  
1
2
Heating  
Cooling  
Cooling  
Heating  
(*2)  
(20 + 2 + 0.5 = 22.5°C or higher)  
68 – 4 – 2 = 62°F or lower  
(20 – 2 – 1.0=17.0°C or lower)  
*2: During heating operation when the body sensor is used, a temperature shift is applied to the intake temperature  
detected by the sensor, in consideration for the difference in temperature at the top and bottom of the room. (Refer  
to the “Room Temperature Control” item.) If this intake shift temperature is 8°F (– 13°C), then the heating  
change occurs when the temperature detected by the body sensor is 80°F (26.5°C) or higher.  
cooling  
2
(4) Cooling (heating) operation does not change if the room temperature changes from area C  
minutes after the compressor turns OFF. (Monitoring mode is excepted.)  
(5) When the heating/cooling change  
A (or A  
C) within 10  
occurs, the 4-way valve switches  
approximately 30 to 50 seconds  
after the compressor turns ON.  
A
B
C
+6 deg  
+5 deg  
+4 deg  
Selected operating mode  
Shifted set temp  
+2 deg  
Remote controller display  
–2 deg  
Shifted set temp –4 deg  
Selected operating mode  
–6 deg  
Thermostat  
ON  
OFF  
ON OFF ON OFF ON OFF ON OFF ON  
Heating  
Cooling  
Heating  
2-3  
Remote Control Functions  
2. Wireless Remote Controller  
Optional Controller (Remote Controller)  
Wireless Remote Controller / RCS-SH80AAB.WL (for X Type) / RCS-TRP80AAB.WL (for A,T Type) / RCS-  
BH80AAB.WL (for U, D Type) / RCS - SH1AAB (for K Type)  
1. How to Use the Wireless Remote Controller  
B: Transmitter  
O: Remote control sensor  
A: ON/OFF operation button  
C: MODE button  
D: Temperature setting buttons  
E: FAN SPEED selector button  
J: TIMER SET button  
I: FLAP button  
K: Time setting buttons  
G: ADDRESS button  
L: SET button  
F: FILTER button  
M: CL button  
N: VENTILATION button  
P: ACL button  
(ALL CLEAR)  
H: A/C SENSOR button  
Q: Slide switch  
2
NOTE  
The illustration above pictures the wireless remote control unit after the cover  
has been lowered and removed.  
A: ON/OFF operation button  
B:Transmitter  
This button is for turning the air conditioner on and off.  
When you press the buttons on the wireless remote control unit, the mark appears in the  
display to transmit the setting changes to the receiver in the air conditioner.  
C: MODE button  
Use this button to select one of the following five operating modes.  
(AUTO)  
: Used to automatically set cooling or heating operation. Only for single heat pump  
type  
~
(Temperature range: 62 80°F (17 to 27°C))  
: Used for normal heating operation. Only for heat pump type  
(Temperature range: 60 78°F (16 to 26°C))  
: Used for dehumidifying without changing the room temperature.  
(HEAT)  
(DRY)  
~
~
(Temperature range: 64 86°F (18 to 30°C))  
(COOL)  
: Used for normal cooling operation.  
~
(Temperature range: 64 86°F (18 to 30°C))  
(FAN)  
: Used to run the fan only, without heating or cooling operation.  
D:Temperature setting buttons  
: Press this button to increase the temperature setting.  
: Press this button to decrease the temperature setting.  
E: FAN SPEED selector button  
(AUTO)  
(HI)  
: The air conditioner automatically decides the fan speeds.  
: High fan speed  
(MED)  
(LO)  
: Medium fan speed  
: Low fan speed  
Continued  
2-4  
Remote Control Functions  
2. Wireless Remote Controller  
F: FILTER button  
If a separately installed signal receiver is being employed, this button is used to turn off its  
filter lamp. When the filter lamp has lighted, first clean the filter, and then press the FILTER  
button to turn off the filter lamp. When a wired remote control unit and wireless remote  
control unit are both used, the filter sign on the wired remote control unit will appear. When  
this happens, first clean the filter, and then press the FILTER button on one of the remote  
control units to turn off the filter sign.  
G: ADDRESS button  
When a multiple number of indoor units that can be operated by the wireless remote  
control unit have been installed in the same room with a multi-unit or single-unit installation,  
this button enables addresses to be set in order to prevent the sending of signals to the  
wrong indoor unit. Each of up to six indoor units can be controlled separately using its own  
wireless remote control unit by matching the number of the address switch on the operation  
area of the indoor unit and the number used for the address of its remote control unit. (The  
indoor units cannot be controlled separately when they are used in a flexible combination  
format, simultaneous operation of multi units format or any other such format since they will  
all operate at the same time.)  
When the batteries are replaced, the address setting returns to "ALL", so you must make  
the setting again.  
NOTE  
NOTE  
H: A/C SENSOR button  
I: FLAP button  
When you press this button (use a narrow-tipped object such as a ballpoint pen), the  
indication will disappear on the display. The room temperature is detected by the sensor  
which is built into the indoor unit and the air conditioner is controlled accordingly.  
If the remote control is located near a heat source, such as a space heater or in direct  
sunlight, press the A/C SENSOR button to switch to the sensor on the indoor unit.  
1. Use this button to set the airflow direction to a specific angle.  
The airflow direction is displayed on the remote control unit.  
Operation mode  
Number of airflow direction settings  
(COOL) or (DRY)  
(HEAT) or (FAN)  
(AUTO)  
3
5
2
Cooling mode:  
Heating mode:  
3
5
In the Cool mode and Dry mode, if the flaps are set in a downward  
position, condensation may form and drip around the vent.  
Do not move the flap with your hands.  
CAUTION  
NOTE This function is available only for models X, A, T and K.  
(SWEEP) 2. Use this button to make the airflow direction sweep up and down automatically.  
Press this button several times until the  
symbol appears on the display.  
To stop the swing operation  
Press the FLAP button again during the flap swing operation to stop the flap at the desired  
position. Then, the airflow can be set from the top position by pressing the FLAP button  
again.  
2-5  
Remote Control Functions  
2. Wireless Remote Controller  
Indicator when swing operation is stopped  
Fan and heating Cooling and drying  
During cooling and drying, the flap does not stop at the downward position.  
Even if the flap is stopped at the downward position during the swing operation, it does not  
stop until it moves to the third position from the top.  
NOTE This function is available only for models X, A, T and K.  
J:TIMER SET button  
(OFF Timer)  
(OFF Cycle Timer)  
(ON Timer)  
K:Time setting buttons  
Use this button while the unit is operating to switch between timer settings.  
: The air conditioner stops after a preset time elapses.  
: The air conditioner always stops after a preset time elapses.  
: The air conditioner starts after a preset time elapses.  
: Press this button to increase the time.  
: Press this button to decrease the time.  
L: SET button  
Use this button to set the timer.  
M: CL button  
Use this button to clear the timer setting.  
N:VENTILATION button  
This is used when a ventilation fan (available commercially) is connected. Pressing the  
VENTILATION button turns the fan on and off. The ventilation fan also turns on and off when  
the air conditioner unit is turned on and off. (The display of the remote control unit shows  
"
" while the ventilation fan is running.)  
* If the VENTILATION button is held down for 4 or more seconds when the batteries have  
been replaced, " " appears on the display, and the ventilation fan can be used.  
O: Remote control sensor  
P: ACL button (ALL CLEAR)  
Q: Slide switch  
This detects the temperature around the remote control unit when the remote control unit  
position has been selected using the sensor button.  
2
Puts the wireless remote control unit into pre-operation status. This is used after the batter-  
ies have been replaced or when the slide switch setting has been changed.  
This switch is for setting the operation mode of the indoor unit and setting the flaps.  
The wireless remote control unit sends the temperature signal to the air  
NOTE  
conditioner regularly at five-minute intervals. If the signal from the wireless  
remote control unit stops for more than ten minutes due to the loss of the  
wireless remote control unit or other trouble, the air conditioner will switch to  
the temperature sensor which is built into the indoor unit and control the room  
temperature. In these cases, the temperature around the wireless remote  
control unit may differ from the temperature detected at the air conditioner's  
position.  
When low fan speed is selected and the air conditioner is in cooling opera-  
tion at a low outdoor temperature of less than 50°F (10°C), the air conditioner  
may automatically switch to medium fan speed to prevent freezing.  
2-6  
Remote Control Functions  
2. Wireless Remote Controller  
2. Receiver  
The signal receivers with the exception of the separately installed signal receiver are mounted on the indoor units.  
T type  
X type  
Separately installed  
signal receiver  
(A, U, D type)  
K type  
A: Receiver  
This section picks up infrared signals from the wireless remote control unit (transmitter).  
2
Indication lamps  
One of these lamps will blink when trouble has occurred. When an indicator lamp starts to  
blink, refer to “Troubleshooting” on page 2-14.  
B: Operation lamp  
C: Timer lamp  
This lamp lights when the appliance is turned on.  
This lamp lights when the system is being controlled by the timer.  
D: Standby lamp  
• This lamp lights at the following times during heating operations:  
When operation has started, when the thermostat has been activated, during a defrosting  
operation.  
• The lamp blinks when trouble has occurred.  
E: Emergency operation  
button  
This is used when operation cannot be performed due to trouble with or loss of the wireless  
remote control unit.  
F: ADDRESS switch  
This switch is used in order to prevent the sending of signals to the wrong indoor unit when  
a multiple number of indoor units that can be operated by the wireless remote control units  
have been installed in the same room.  
G: SWING button  
H: FILTER lamp  
When this button is pressed, the airflow sweeps up and down automatically.  
This lamp lights to indicate that it is time to clean the filter.  
• If two beeps are heard, the operation lamp among the indication lamps has lighted and the timer lamp and standby  
lamp blink alternately. In cases where heat pump models are used, this indicates a cooling/heating mode mismatch  
and, as such, operation in the desired mode cannot be performed. (The same beeps will be heard and the same  
operation lamps will light when auto cooling/heating has been selected on a model which does not have the auto  
cooling/heating function.)  
• When local operation has been set to disable because the centralized control mode is established, for instance,  
pressing the ON/OFF operation button, MODE button or temperature setting buttons results in the sounding of  
five beeps, and the attempted change in the operation will not be accepted.  
2-7  
Remote Control Functions  
2. Wireless Remote Controller  
3. Operation  
STEP 1, 6  
STEP 2  
STEP 4  
STEP 5  
STEP 3  
To warm up the system, the power mains must be turned on at least five (5) hours before operation.  
NOTE  
STEP 1  
STEP 2  
To start the air conditioner: Press the operation button (ON/OFF button).  
Setting the mode:  
Press the MODE button to select the mode of your choice.  
(AUTO), (HEAT), (DRY), (COOL) or (FAN) ]  
[
STEP 3  
Setting the fan speed:  
Press the FAN SPEED selector button to select the fan speed of your choice.  
(AUTO), (HI.), (MED.) or (LO.) ]  
If AUTO is selected, the fan speed switches automatically.  
[
2
STEP 4  
STEP 5  
STEP 6  
Setting the temperature:  
Use the  
reduces the temperature, and  
* The temperature cannot be set during FAN mode operation.  
or  
button as appropriate to change the temperature setting as desired.  
(
increases the temperature. )  
Setting the airflow direction: When more than one indoor unit is connected, the UNIT button is used first to  
select a unit. Then use the FLAP button to set the airflow direction to a specific  
angle or to sweep.  
To stop the air conditioner: Press the operation button (ON/OFF button) again.  
Automatic heating and  
cooling  
The air conditioner automatically performs heating and cooling operation based on the  
difference between the temperature setting and room temperature. All indoor units in the  
same refrigerant system can be operated with a single group control.  
Simultaneous operation of  
multiple units (Group  
control)  
Group control is suitable for air conditioning of a large room using multiple air conditioning  
units.  
• One remote control unit can control up to eight indoor units.  
• All indoor units have the same settings except for the airflow direction.  
• The temperature sensors at the indoor unit side are used.  
Outdoor unit  
Indoor unit  
Signal line  
Remote control unit  
2-8  
Remote Control Functions  
2. Wireless Remote Controller  
4. Using the Wireless Remote Control Unit  
Slide switch This is used to set the operation mode of the indoor units and to set the flaps.  
• Depending on the indoor unit used, the operation display and airflow direction display  
settings will differ as shown below.  
• Use a pointed implement to change the switch position.  
• When the switch position has been changed, press the ACL button.  
* For details on the flap functions, refer to the operating instructions of the indoor unit used.  
Model which supports  
different flap settings  
Swing-only model  
No-flap model  
Slide switch position  
Flap display on wireless  
remote control unit  
Heat pump (with auto  
cooling/heating  
function)  
Heat pump (without  
auto cooling/heating  
function)  
Cooling only  
Operation mode display  
on wireless remote  
control unit  
With the battery cover  
removed  
Slide switch position  
• Before use, check that the slide switch has been set to the position shown in the figure  
above. For details on how to set the slide switch, consult your dealer.  
2
How to install  
batteries  
1. Slide the cover in the direction indicated by the arrow and  
remove it.  
2. Install two AAA alkaline batteries. Make sure the batteries  
point in the direction marked in the battery compartment.  
3. Use a pointed implement to press the ACL button.  
• The batteries last about a year, depending on how much  
you use the wireless remote control unit. Replace the  
batteries when the wireless remote control unit's display  
fails to light, or when the remote control cannot be used  
to change the air conditioner's settings.  
• When the batteries are to be replaced, make sure that both  
batteries are new and that the same kind of battery is used.  
ACL  
button  
Cover  
• Remove the batteries if the wireless remote control unit is  
not going to be used for a prolonged period.  
• Dispose of the used batteries at the designated location.  
How to use the  
wireless remote  
control unit  
• Point the wireless remote control unit's transmitter at the signal receiver. If the signal is  
received properly, a beep is heard. (Two beeps are heard only when operation starts up.)  
• Signals can be received over a distance of approximately 26 ft. This distance is  
approximate: it may be slightly more or less depending on how much charge remains in the  
batteries and on other factors.  
• Ensure that the signals will not be blocked by any objects positioned between the transmitter  
and signal receiver.  
• Avoid placing the wireless remote control unit where it will be exposed to direct sunlight or in  
the direct path of the air blown out from the air conditioner, near a heating appliance, etc.  
• Do not drop, throw or wash the wireless remote control unit.  
• Signal reception may not be accepted in rooms with fluorescent lights that use the electronic  
instantaneous lighting system (rapid start system) or inverter system.  
For further details, contact your dealer.  
2-9  
Remote Control Functions  
2. Wireless Remote Controller  
When mounting the  
wireless remote control  
unit on a wall for use  
• Before mounting the wireless remote control unit on the wall, place the unit at the mounting  
position, press the ON/OFF operation button and check that the signals are received  
properly.  
To remove the wireless remote control unit, disengage it by pulling it toward you.  
Secure the installation fitting of the wireless  
remote control unit using the screws.  
Place here.  
1
Procedure for installing the  
wireless remote control unit  
Press.  
2
Installation fitting of wireless remote control unit  
Operating tips • Do not operate the wireless remote control unit too far away from the signal receiver.  
Doing so may cause operational errors.  
Make absolutely sure that the wireless remote control unit and signal receiver are both in  
the same room.  
• When operating the wireless remote control unit, point it directly at the signal receiver.  
A beep is heard when a signal is received properly.  
• Avoid places where the wireless remote control unit will be obscured by curtains, etc.  
Remove it before operation.  
2
5. Address Settings  
When a multiple number of indoor units that can be operated by the wireless remote control unit  
have been installed in the same room with a multi-unit or single-unit installation, this button enables  
addresses to be set in order to prevent the sending of signals to the wrong indoor unit. Each of up to  
six indoor units can be controlled separately using its own wireless remote control unit by matching  
the number of the address switch on the operation area of the indoor unit and the number used for  
the address of its wireless remote control unit. (The indoor units cannot be controlled separately  
when they are used in a flexible combination format, simultaneous operation of multi units format or  
any other such format since they will all operate at the same time.)  
The signal receiver has an address switch for signal reception, and the wireless remote control unit  
has an address switch for signal transmission.  
How to check the  
addresses  
When the ADDRESS button on the wireless remote control unit is pressed, the current address  
appears on the wireless remote control unit's display. The buzzer sounds if the address  
displayed matches the signal receiver's address. (The buzzer always sounds if “ALLappears  
as the address display.)  
If “ALLappears as the address display, operations can be performed irrespective of the signal  
receiver's address. Point the wireless remote control unit at the signal receiver of the unit to be  
operated, and send the signal.  
How to set the  
Wireless remote control unit̉s address setting  
matching address  
1. When the ADDRESS button is held down for 4 or more seconds, “  
” lights on the  
wireless remote control unit's display, and the current address blinks.  
2. Each time the ADDRESS button is now pressed, the address changes by one setting in the  
following sequence: ALL ALL.  
1
2
3
6
Select the setting which matches the setting of the address switch in the operation area of  
the indoor unit to be operated.  
3. When the SET button is now pressed, the address stops blinking and lights instead, and it  
remains on the display for 5 seconds.  
The buzzer sounds if the setting matches the setting of the address switch in the operation  
area of the indoor unit.  
When the batteries are replaced, the address setting returns to “ALL ”.  
2-10  
NOTE  
Remote Control Functions  
2. Wireless Remote Controller  
Wireless remote  
control unit  
address displays  
……  
X type  
For positions 1, 2 and 3, set the  
knob to the left; conversely, for 4, 5  
and 6, set the knob to the right.  
* The address switch  
in the operation  
area may be set to  
any position.  
Position of  
address switch on  
signal receiver  
(inside indoor unit)  
……  
T type  
For positions 1, 2 and 3, set the  
knob to the left; conversely, for 4, 5  
and 6, set the knob to the right.  
* The address switch  
in the operation  
area may be set to  
any position.  
Position of  
address switch on  
signal receiver  
(inside indoor unit)  
……  
K type  
* The address switch  
in the operation  
area may be set to  
any position.  
Position of  
address switch  
inside indoor unit  
……  
For positions 1, 2 and 3,set the  
knob upward (1); conversely, for 4,  
5 and 6, set the knob downward  
(ON).  
2
A, U, D type  
For positions 1, 2 and 3, set the  
knob to the left; conversely, for 4, 5  
and 6, set the knob to the right.  
* The address switch  
in the operation  
area may be set to  
any position.  
Position of  
address switch in  
signal receiver  
……  
2-11  
Remote Control Functions  
2. Wireless Remote Controller  
6. Emergency Operation  
In any of the following events, use the Emergency operation button to operate the air  
conditioner on a makeshift basis.  
• When there is no charge remaining in the wireless remote control unit's batteries  
• When the wireless remote control unit has failed  
• When the wireless remote control unit has been lost or misplaced  
X type Initiate operation using the Emergency operation button in the operation area of the indoor unit.  
Operation  
Press the Emergency operation button.  
The air conditioner initiates a cooling operation when its operation is started up at  
a room temperature of 75°F (24°C) or above.  
Conversely, it initiates a heating operation when its operation is started up at a  
room temperature below 75°F (24°C).  
Shutdown  
Press the Emergency operation button once more.  
T type Initiate operation using the Emergency operation button in the signal receiver on the indoor  
unit.  
Operation  
Press the Emergency operation button.  
The air conditioner initiates a cooling operation when its operation is started up at  
a room temperature of 75°F (24°C) or above.  
Conversely, it initiates a heating operation when its operation is started up at a  
room temperature below 75°F (24°C).  
2
Shutdown  
Press the Emergency operation button once more.  
K type Initiate operation using the Emergency operation button in the operation area of the indoor unit.  
Operation  
Set the ON/OFF operation switch to “OFFfirst.  
Then set it to “ON. ”  
If a heat pump is used, the air conditioner initiates a cooling operation when its  
operation is started up at a room temperature of 75°F (24°C) or above or it initiates  
a heating operation when its operation is started up at a room temperature below  
75°F (24°C).  
Shutdown  
Set the ON/OFF operation switch to “OFF.”  
• TEST is used to initiate a trial run when the air conditioner is first installed. It is not used  
under normal circumstances.  
To restart the wireless remote control unit's operation, the ON/OFF operation switch must  
be set to ON without fail. If it is kept at the OFF setting, the signals from the wireless remote  
control unit will not be accepted.  
NOTE  
2-12  
Remote Control Functions  
2. Wireless Remote Controller  
A, U, D type  
Initiate operation using the Emergency operation button in the signal receiver.  
1. Press the Emergency operation button.  
The air conditioner initiates a cooling operation when its operation is started  
up at a room temperature of 75°F (24°C) or above.  
Conversely, it initiates a heating operation when its operation is started up at a  
room temperature below 75°F (24°C).  
2. When the SWING button is pressed, the air direction is automatically switched  
from upward to downward or vice versa.  
Shutdown  
Press the Emergency operation button once more.  
2
2-13  
Remote Control Functions  
2. Wireless Remote Controller  
7.Troubleshooting  
Check out the following points before requesting service.  
Trouble  
Possible Cause  
Remedy  
Is the air conditioner in the shutdown mode or  
was the switch operated after a power failure?  
Press the wireless remote control unit's  
ON/OFF operation button again.  
The air conditioner  
does not run even  
when the ON/OFF  
operation switch has  
been set to ON.  
How about the local power switch?  
Have any of the fuses blown?  
If it was off, set it now to on.  
If a fuse has blown, contact your dealer.  
Clear the timer operation.  
Is the ON timer operation mode established?  
If the signal receiver's NORMAL/ALL OFF  
switch set to “ALL OFF”?  
If it is, set it to the “NORMALposition and  
cancel the operation.  
Have the wireless remote control unit's  
batteries run down?  
If they have, replace them with new ones.  
Do the indication lamps show a cooling/heating Change the operation mode.  
mismatch or is the auto cooling/heating  
function not available?  
Auto cooling/heating or heating appears on the display even though the air  
conditioner is a cooling-only model.  
Change the setting of the wireless remote  
control unit's slide switch. (See page 2-9)  
Trouble  
Possible Cause  
(An indicator lamp is blinking.)  
• Some kind of trouble has occurred in communication between the signal  
receiver and indoor unit. Alternatively, the wrong address has been set  
when a wired remote control unit is used.  
Operation  
Operation  
Operation  
Operation  
Timer  
Timer  
Timer  
Timer  
Preparing for  
operation  
2
Preparing for  
operation  
• Some kind of trouble has occurred in communication between the indoor  
unit and outdoor unit.  
Preparing for  
operation  
• The indoor unit's protection device has been activated. Alternatively, the  
auto flap connector of the ceiling panel has been disconnected.  
Preparing for  
operation  
• The outdoor unit's protection device has been activated.  
Operation  
Operation  
Timer  
Timer  
Preparing for  
operation  
• Something is wrong with the temperature sensor.  
• The outdoor unit's compressor has been protected.  
• A trial run mode is underway. Set the trial run mode to Off.  
Preparing for  
operation  
Operation  
Timer  
Preparing for  
operation  
If the trouble persists even after performing the checks recommended above, shut down the air conditioner's operation, set the  
local power switch to OFF, and contact your dealer with the model number and trouble symptoms.You must NOT attempt to  
make repairs yourself due to the dangers involved. If one or more of the indication lamps is blinking, give this information to the  
dealer as well.  
2-14  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
1. How to Use the Timer Remote Controller  
Operating buttons  
13  
1
2
3
12  
11  
10  
9
4
5
6
7
8
2
Display  
1
2 34  
5 6 7 8 9 1031 11 12  
13  
30 28 27 25  
29 26  
23 22  
24  
21  
18 17 1615 14  
20  
2-15  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
2. Names and Operations  
Operation Section (Refer to the previous page)  
1.  
Start/Stop button  
10.  
Ventilation button  
Pushing this button starts, and pushing again stops the  
unit.  
Use this button when you installed a fan available in the  
market. Pressing this button turns on and off the fan.  
When turning off the air conditioner, the fan will be also  
turned off.  
2. Operation lamp  
The lamp is turned on when an air conditioner is in opera-  
tion.  
This lamp blinks when an error occurs or a protective  
device is activated.  
(While the fan is operating,  
will appear in the display.)  
*If is displayed on the LCD of the remote control unit  
when pressing the ventilation button, no fans are installed.  
11.  
12.  
Inspection button  
Do not use this button.  
3.  
Mode Select button  
Pushing this button to select an operation mode. (AUTO  
/HEAT /DRY /COOL /FAN ).  
Sleeping button  
(
Sleeping Function)  
4. Temperature setting buttons  
Changing the temperature setting.  
13. Remote control sensor  
Normally, the temperature sensor of the indoor unit is  
used to detect the temperature. However, it is also pos-  
sible to detect the temperature around the remote control  
unit.  
5.  
6.  
FAN speed button  
Changing the fan speed.  
Swing/Air direction button *1  
Use this button to set the auto swing or air direction to a  
specific angle.  
*1 Do not move the flap (vertical airflow adjustment board)  
with your hand.  
7.  
Unit Select button  
When more than one indoor unit is operated by one re-  
mote control unit, this button is used to select a unit when  
adjusting the air direction.  
The flap is automatically directed down when the unit is  
stopped.  
The flap is directed up during the HEAT standby. The  
flap starts swinging after the HEAT standby is can-  
celled, although the AUTO flap indication on the remote  
control unit is displayed during the HEAT standby.  
8. Timer setting buttons  
Weekly Program Function)  
FILTER reset button  
(
9.  
Use this button to reset the filter sign.  
When is displayed, press this button after cleaning the  
filter.  
2
2-16  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
Display Section (Refer to the page 2-15)  
17.  
Operation mode change control indication  
1.  
2.  
SETTING indication  
Appears when the timer program is being set.  
Displays when an operation mode is entered by the re-  
mote control unit, while another operation mode has been  
already selected. This indicates that the operation mode  
cannot be changed.  
UNIT indication  
Indicates the unit No. of the indoor unit which is selected  
with the Unit Select button, or the unit in which an abnor-  
mality occurs.  
18.  
20.  
Disabled Feature indication  
Displayed if the selected feature was disabled during  
installation.  
3.  
TIMER No. indication  
Appears when the time program is being set.  
Heating standby mode indication  
appears when the fan of the indoor unit is stopped or in  
low fan speed.  
4. Timer program  
: The indoor unit starts operation at the programmed  
time.  
: The indoor unit stops operation at the programmed  
time.  
Today’s day of the week  
21.  
22.  
23.  
24.  
25.  
/
/
/
Fan mode select indication  
The selected fan mode is displayed.  
SWING indication  
Appears while the flap swings.  
5.  
6.  
Indicates today’s day of the week.  
Flap position indication  
Indicates the flap position.  
Program schedule indication  
Appears under days that are scheduled for program op-  
eration.  
Filter indication  
Appears when filter needs cleaning. Clean the filter.  
7. Present time  
Displays the present time on a 24-hour clock. Also, dis-  
plays settings in the various setting modes.  
Inspection indication  
Appears when the protective device is activated or when  
an abnormality occurs.  
8.  
TIMER OFF indication  
Displayed when the timer has been turned OFF.  
26.  
27.  
Ventilation indication  
Appears when a fan available in the market is installed  
and is operating.  
9.  
ERROR indication  
Displayed when a mistake is made during timer setting.  
Oil indication  
10.  
Outing indication (  
Outing function)  
Appears when the engine oil needs to be changed. (Ap-  
pears when the gas heat pump air conditioner is used.)  
Appears when the outing function is set.  
2
11. Upper and lower limit indication of the outing func-  
tion  
28.  
29.  
Sleeping  
Appears during the sleeping function.  
: Indicates the upper limit of the temperature  
: Indicates the lower limit of the temperature  
CAUTION  
Appears when the protective device is activated or when  
an abnormality occurs.  
12. Operation Mode indication  
Displays the selected operation mode. (AUTO /HEAT  
/DRY /COOL /FAN ).  
30. Unit No. indication  
Indicates the unit No. of the selected indoor unit.  
13. Temperature indication  
Indicates the set temperature.  
31.  
TEST indication  
Appears while in test operation.  
14. °F / °C temperature unit indication  
15.  
Remote control sensor indication  
Appears when the remote control sensor is used.  
16.  
Centralized control indication  
Appears when operated in centralized control. If the  
remote control operation is not permitted to the remote  
unit, when the Start/Stop button, Mode Select button or  
Temperature setting button is pressed,  
rejects the change.  
flashes and  
2-17  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
3. Installation Manual for Timer Remote Controller  
Accessories for remote controller switch  
Remote controller  
Wood screws  
Wire joints  
Operation manual  
Installation manual  
(with 8 in.  
wire)  
4. How to install the Remote Controller  
Do not supply power to the unit or try to operate it until the tubing and wiring to the outdoor unit is  
completed.  
CAUTION  
Do not twist the control wiring with the power wiring or run it in the same metal conduit, because  
this may cause malfunction.  
Install the remote controller away from sources of electrical noise.  
Install wiring correctly(incorrect wiring will damage the equipment).  
Install a noise filter or take other appropriate action if electrical noise affects the power supply circuit  
of the unit.  
When wiring, do not connect the remote controller wires to the adjacent terminal block for the power  
wiring. Otherwise, the unit will break down.  
Use shielded wires for remote control wiring and ground the shield on indoor unit sides. (Fig. 2-1)  
Otherwise misoperation due to noise may occur.  
The mounting position for the remote controller should be located in an accessible place for control.  
Never cover the remote controller or recess it into the wall.  
(1) When you open the decorative cover (Fig. 2-4), you will see 2 gaps under the remote controller.  
Insert a coin into these gaps and pry off the back case.  
(2) Attach the back case with the 2 wood screws provided. Using a screwdriver, push open the cut-outs on the back case.  
These holes are for screws. (Fig. 2-5)  
(3) Connect the remote controller wiring (2 wires) correctly to the corresponding terminals in the electrical component box of  
the indoor unit.  
(4) To nish, fit the back tabs of the case into the remote controller and mount it.  
2
Basic Wiring Diagram  
Connection diagram  
Approx.  
8 in.  
Terminal board for  
indoor unit remote  
controller wiring  
Remote  
controller  
unit  
1
2
W
1
2
Shielded wire  
BK  
Ground  
Power wire from remote  
controller unit  
Connector  
Remote controller wiring  
(field supply)  
Fig. 2-1  
2-18  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
Provided wire joint (white)  
Use AWG#20 to AWG#16 wires.  
Remote controller wiring can be extended to a maximum  
of 1640 ft.  
Remote controller wiring  
(1) Strip the insulation to approximately 35/64" from the ends  
of the wires that will be connected.  
(2) Twist together the 2 wires and create a crimp connection  
at the wire joint.  
(3) If a special crimping tool is not used, or if the connection  
is soldered, insulate the wires using insulation tape.  
Power wire from remote  
controller unit  
Wire joint  
Fig. 2-2  
Remote controller  
(main)  
(sub)  
5. Group Control Using 2 Remote Controllers  
Connection wiring  
for group control  
1 2  
1 2  
It does not matter which of the 2 remote controllers you  
set as the main controller. When using multiple remote  
controllers (up to 2 can be used), one serves as the  
main remote controller and the other as the sub-remote  
controller.  
2P terminal  
base for remote  
control wiring  
1 2  
Indoor unit  
No. 1  
1 2  
Indoor unit  
No. 2  
1 2  
Indoor unit  
No. 3  
1 2  
Indoor unit  
No. 8  
: Ground (earth)  
Fig. 2-3  
6. Remote Controller Setting Mode  
To set the remote controller main/sub setting or change the sensor, follow the steps below.  
Press both  
4 seconds together.  
Select CODE No. with  
Change DATA with  
and  
buttons on the remote controller for more than  
DATA  
CODE  
ITEM  
ITEM  
buttons.  
(TIMER) buttons.  
RCU. Main/Sub  
Clock display  
RCU. CK  
Sub  
Main  
Press  
. Finally, press  
.
24 hours 12 hours (AM/PM)  
* DATA is memorized in the RCU. (DATA setting will not be changed even  
when the power is turned off.)  
* Make sure to set [Normal] for RCU. CK.  
RCU. CK  
Normal  
RCU  
Room temperature sensor Main unit  
2
7. Indoor Unit Setting Mode  
To select the ventilation setting or change the temperature unit, follow the steps below.  
Press  
+
+
buttons on the remote controller for more than 4 sec-  
onds together.  
Select CODE No. with  
Change DATA with  
DATA  
CODE  
ITEM  
ITEM  
buttons.  
(TIMER) buttons.  
Vent. button  
No  
oC  
Yes  
oF  
Press  
. Finally, press  
.
Temperature unit  
* DATA is memorized in the indoor unit. (DATA setting will not be changed  
even when the power is turned off.)  
8.To Display the Sensor Temperature:  
Press both  
and  
buttons on the remote controller for more than 4 seconds together.  
Change the sensor address (CODE No.) with  
Select the UNIT No. which you want to call with the  
buttons.  
button.  
Press the  
button to finish service mode.  
9.To Display the Trouble History:  
Press both  
Change the alarm message:  
Press the button to finish service mode.  
and  
buttons on the remote controller for more than 4 seconds together.  
buttons  
CODE No.  
(New) (Old)  
2-19  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
Fig. 2-4  
Fig. 2-5  
Caution when installing the remote controller  
*1 Install the remote controller more than 3-3/8" apart from the wall surface.  
*2 To install the remote controllers side-by-side, keep the space between each for more than 4-59/64".  
*3 To install the remote controllers one above the other, keep the space between each for more than 1".  
5/32  
2
4-23/32  
5/8  
1-1/2  
1
1
11/64 × 3/8  
3/16 × 27/64  
1/16  
1-13/16  
unit :in.  
53/64  
15/16  
11/64 × 3/8  
3/16 × 3/8  
4-13/32  
2-20  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
10. Setting the Present Time  
1. Press and hold  
for more than 2 seconds to enter in the present  
day and time setting mode.  
Once you enter in the setting mode,  
, “ ”(day) and “time” flash.  
2. Set “ ” to today’s day of the week.  
1
Press  
Su  
*
to move “ ” (flashing on the display) in the order of :  
.... Press to move it in the order of : Su St  
Mo  
....  
Tu  
Fr  
*1  
While in time setting mode, the temperature setting buttons function as  
(changing day) button.  
3. Press  
Set the present hour and press  
to change the present “hour” in the range of 0 to 23*2.  
3,4 1,3,4  
2
.
The “hour” digits light up, and the “minute” digits start flashing.  
*2  
If the clock uses the 12 hours AM/PM setting, the hour is displayed in the range of AM 0 to  
11/PM 0 to 11.  
4. Press  
, to change the present “minute” in the range of 0 to 59.  
Set the present minute and press . The day and time are set and finishes the setting mode.  
Note  
• The unit returns to the normal mode if  
is pressed or there is no operation made for 3 minutes  
during the setting. In this case, all the settings in progress will be lost.  
• If the present time is invalid, “– – : – –” is displayed.  
If the power failure for more than 1 hour occurs, check if the set data of day and time are valid.  
2
2-21  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
11. Weekly Program Function  
Checking Weekly Timer  
Set the weekly program assigning a given timer to each day of the week.  
Maximum of 6 programs a day and 42 programs a week can be set.  
Select the day and the TIMER number you want to program.  
Program image diagram  
button  
Vertical scale indicates the TIMER No.,  
and horizontal scale indicates the day.  
TIMER No.  
Su Mo Tu We Th Fr Sa  
*
If the day is changed, the TIMER No.  
returns to “1”.  
1
2
3
4
5
6
Select a section from  
the 42 programs.  
1. Press  
to enter the program confirmation mode  
” and start setting.  
Once you enter the program confirmation mode, the  
present day is indicated as TIMER No. “1”.  
2. Select the day.  
Press  
and  
/
to move the “ ” horizon-  
tally on the day to select.  
1
3
Press  
order of : Su  
Press  
to move “ ” (flashing on the display) in the  
Mo Tu....  
to move it in the order of : Su  
Sa  
Fr....  
program CHeck  
2
2
“– – : – –” is displayed when the program is not set.  
3. Select a Timer number.  
Press  
Press  
Press  
/
to select a TIMER No. from 1 to 6.  
to move up from 1.  
to move down from 6.  
TIMER No. 1~6  
2-22  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
Changing the Program Timer  
To set the weekly program, follow the steps below.  
1. Select the program you want to set in the program  
confirmation mode, and press .The enters the  
setting mode of the program currently displayed.  
* In the program setting mode,  
, “hour”,  
“minute” and “item” flash on the display.  
2. Set the “hour”. (program step 1)  
Press  
Confirm the “hour” and press . The enters the pro-  
gram changing mode (setting of the “minute”).  
3. Set the “minute”. (program step 2)  
Press to set the “minute”.  
/
to set the “hour”.  
2,3,4 1,2,3,4 4  
Program step1  
/
Confirm the “minute” and press .The unit enters  
(the program pattern selection mode).  
Program step2  
normal remote controller  
PROGRAM  
CANCEL  
SET  
Changing hour digits  
CANCEL,DEL  
CANCEL,DEL  
SET  
program check  
2
Changing minute digits  
Program  
SET  
Changing patterns  
SET,CANCEL,DEL  
PROGRAM  
Selecting copy source  
CANCEL  
SET  
Selecting copy destination  
SET,CANCEL  
2-23  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
4. Set the program pattern.  
(program step 3)  
Pattern 1  
Pattern 2  
Pattern 3  
Pattern 4  
There are 4 program patterns.  
Pressing  
/
repeats the following display patterns.  
Pattern 1  
The indoor unit starts operation at the programmed  
time.  
Pattern 2  
The indoor unit stops operation at the programmed  
time.  
Pattern 3  
The indoor unit starts operation at the programmed  
time and changes the temperature settings.  
Press  
/
to change the temperature setting.  
Pattern 4  
The indoor unit changes the temperature setting at  
the programmed time.  
Press  
/
to change the temperature setting.  
2
Select the program pattern and press . The program timer setting is confirmed and the unit enters the confirmation mode  
.
Note  
If you press  
during the setting, it returns to the program confirmation mode.  
If there is no operation made for 3 minutes during the setting, it returns to the normal mode.  
In this case, all the settings in progress will be invalid.  
2-24  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
Deleting the Program Timer  
To delete the program timer setting, follow the steps below.  
1. Press  
to enter the program confirmation mode.  
2. Press  
lete.  
/
to select the day of the program you want to de-  
3. Press  
4. Press  
/
to select a TIMER No. (from 1 to 6).  
to display the program setting mode  
to delete the program.  
.
5. Press  
Note  
After deleting, the unit returns to the program confirmation mode  
If you press during the setting, the unit returns to the program  
confirmation mode.  
.
If there is no operation made for 3 minutes during the setting, the unit re-  
turns to the normal mode.  
Invalidating Program Timer  
5 3 4 1 2  
If you want to adjourn the program operation for more than 1 week, you can  
invalidate all the timer settings.  
Once the timer settings are invalidated, the program will not be operated until the invalidation is cancelled.  
<<How to invalidate the program timer>>  
Press and hold  
for more than 2 seconds.  
is displayed and the programs will be invalidated from the next one.  
<<How to cancel the program timer invalidation>>  
2
Press and hold  
for more than 2 seconds.  
disappears and the programs will be validated from the next one.  
If Power Failure Occurred  
If the power recovers in a short time period, the program after the recovered time will be valid.  
If the power recovered more than 1 hour after the failure, the present time information will be lost. In this case, the program will  
not be operated.  
2-25  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
Duplicating the Program Timer  
You can duplicate the preset program by day.  
Select the copy source.  
1. If  
is pressed in program checking mode , it enters  
the copy mode (Selecting the copy source ) of the pro-  
gram timer.  
While in the copy mode of the program timer,  
(day) of the copy source flash on the display.  
and  
2. Press  
/
to select the day of the copy source.  
1 3,5  
2,4  
Select the copy destination.  
3. If  
is pressed in the mode of selecting the copy source  
, it enters the copy mode (Selecting the copy destina-  
tion ) of the program timer.  
4. Press  
Then, press  
/
to select the day of the copy source.  
to complete copying and return to the  
program checking mode.  
Note  
The program will be overwritten if the preprogrammed day is selected as a copy source.  
Before Asking Repair Work  
Before asking repair work, please check the followings.  
Trouble  
Possible Cause/Remedy  
“ERROR” is displayed when the If there is another TIMER No. which has the program of the same time and same day, you cannot overlap the  
minute digits are entered.  
The set data is not stored.  
setting.  
The stored programs are automatically sorted by the time. Check if the data is stored in the other TIMER No.  
Check if the time indication is not “– – : – –”.  
When the time is invalid, the program is also invalid.  
2
Program does not function.  
Check the remote controller prohibition inside.  
In that case, the program is invalid.  
2-26  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
12. Outing Function  
Outing function is a function that prevents the room temperature from increasing too much (or decreasing too much) when no  
one is in the room.  
An air conditioner works automatically if this function is set effective.  
General Performance of the Outing Function  
COOL / DRY  
The air conditioner starts operation when the room temperature increases up to –1.8°F(1°C) of the upper limit.  
The air conditioner stops operation when the room temperature decreases up to –3.6°F(2°C) of the upper limit.  
For Example  
Setting at Outing Temperature 86°F (30°C)  
Outing function Upper limit  
(Setting at Outing Temperature)  
86°F(30°C)  
84°F(29°C)  
82°F(28°C)  
(ON)  
1.8°F(1°C)  
3.6°F(2°C)  
Room temperature  
(OFF)  
HEAT  
The air conditioner starts operation when the room temperature decreases up to +1.8°F(1°C) of the lower limit.  
The air conditioner stops operation when the room temperature increases up to +3.6°F(2°C) of the lower limit  
2
For Example  
Setting at Outing Temperature 53°F (12°C) .  
(OFF)  
Room temperature  
57°F(14°C)  
55°F(13°C)  
53°F(12°C)  
3.6°F(2°C)  
(ON)  
1.8°F(1°C)  
Outing function Lower limit  
(Setting at Outing Temperature)  
[Precautions]  
The outing control only starts/stops the air conditioner. It does not change the operation mode/temperature setting.  
Therefore, the operation mode/temperature needs to be set beforehand so that the outing function turns on the air condition-  
er with your desired operation mode/ temperature setting.  
If the room temperature rapidly changes, the room temperature may get over the upper or lower limit when the outing func-  
tion is activated.  
The outing function is invalid during FAN/AUTO operation mode.  
The air conditioner's stop order (stated in /above) is valid only when the outing function is operated.  
If operated using other remote control unit (or a centralized control device such as a system control), the outing function does  
not work.  
2-27  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
Setting the Outing Function  
1. Press and hold  
setting screen.  
for more than 2 seconds to display the upper limit temperature  
,
and the upper limit temperature start flashing.  
(The default value of the upper limit temperature is 99°F (37°C).)  
2. Press  
value.The lower limit temperature setting screen is displayed.  
3. Press to select the lower limit temperature, and press  
/
to select the upper limit temperature and press  
to fix the  
to fix the  
2
3
/
value.The outing function setting is completed. (The default value of the lower limit  
temperature is 50°F (10°C).)  
*
The unit returns to the normal mode if  
is pressed or there is no operation made for 3  
minutes during the setting. In this case, all the settings in progress will be lost.  
Canceling the outing function  
Press and hold  
for more than 2 seconds while the outing function is set.  
Outing function indication  
Outing function indication  
Status  
Off  
The outing function is not set.  
Flashing  
Lighting  
The outing function is now being set, or under operation.  
Although the outing function is set, not under operation.  
Note  
A remote controller loses outing function operation information when it is cut for more than one hour during the outing function  
operation by electricity. It reverts from the blackout, and an air conditioner does not drive in outing function when operation is  
started. At this time, an air conditioner does not stop at outing function.  
2
2-28  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
13. Sleeping Function  
*
This function leads you to a comfortable sleep and chang-  
es the room temperature during your sleep.  
You can set the off timer every one hour from 1 to 10  
hours.  
When the off time comes:  
The indoor unit stops.  
* The temperature returns to the setting at the time when  
sleeping function operation started.  
*
Display of remote control unit  
(during the time setting)  
Operating time  
To cancel the sleeping function operation:  
Press  
.
* The temperature setting remains at the time cancelled.  
The following buttons also cancel the sleeping function  
operation.  
button  
In case the present time  
is 23:00.  
Off time  
Sleeping function  
indication  
Stop the indoor unit after the sleeping function operation  
is cancelled.  
button  
Display of remote control unit (dur-  
ing sleeping function setting)  
Changes the operation mode after the sleeping function  
operation is cancelled.  
Sleeping function indication  
*
If no operation is made for 3 minutes, the time setting  
mode will be automatically finished.  
Ex. In case of 7 hours timer  
1. Press  
2
.
Each time the button is pressed, the indication changes in  
the following order.  
(every one hour)  
(Press  
to stop the time setting.)  
2. Press  
.
The sleeping operation starts.  
2-29  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
14. Wired Remote Controller Test Run Settings  
1. Press the remote controller  
button for 4 seconds or longer.  
2. “TEST” appears on the LCD display while the test run is in progress.  
3. Then press the  
button.  
The temperature cannot be adjusted when in Test Run mode.  
(This mode places a heavy load on the machines. Therefore use it only when performing the test run.)  
The test run can be performed using the HEAT, COOL, or FAN operation modes.  
Note: The outdoor units will not operate for approximately 3 minutes after the power is turned ON and after operation is  
stopped.  
If correct operation is not possible, an error code is displayed on the remote controller LCD display.  
(Refer to “Table of Self-Diagnostic Functions” and correct the problem.)  
4. After the test run is completed, press the  
button again. Check that “TEST” disappears from the LCD display.  
To prevent continuous test runs, this remote controller includes a timer function that cancels the test run after 60 minutes.  
The operation is possible even if the cassette-type ceiling panel has not been installed. (“P09” display does not occur.)  
2
2-30  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
15. Simple Settings Function  
• This allows the filter lifetime, operating mode prior-  
ity change, central control address, and other set-  
tings to be made for an individual or group-control  
indoor unit to which the remote controller used for  
simple settings is connected.  
2
When this function is engaged, operation stops at  
the individual or group-control indoor unit to which  
the remote controller for simple settings is con-  
nected.  
<Procedure>  
Press and hold the  
simultaneously for 4 seconds or longer.  
7
3
4
buttons  
and  
,” unit No. “  
” (or “  
” in the case of  
group control), item code “  
,” and settings data  
” are displayed blinking on the remote  
1
6
5
controller LCD display. At this time, the indoor unit  
fan (or all indoor unit fans in the case of group  
control) begins operating.  
If group control is in effect, press the  
button and select the address (unit No.) of the  
indoor unit to set. At this time, the fan at the  
indoor unit begins operating.  
2
* If unit No. “  
” is displayed, the same setting  
will be made for all indoor units.  
Press the temperature setting  
/
buttons to select the item code to change.  
Press the timer time  
/
buttons to select  
the desired setting data.  
* For item codes and setting data, refer to the  
following page.  
Press the  
button.  
(The display stops blinking and remains lit, and  
setting is completed.)  
Press the  
button to return to normal remote  
controller display.  
2-31  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
List of Simple Setting Items  
0000 Not displayed  
0001 150 hours  
0002 2,500 hours  
Filter sign ON time  
(filter lifetime)  
0003 5,000 hours  
0004 10,000 hours  
0005 Use the filter clogging sensor.  
0000 Standard (setting at time of shipping)  
Degree of filter fouling  
Central control address  
Highly fouled  
0001  
(Filter sign ON time is reduced to one-half the set time.)  
0001 Central control address 1  
0002 Central control address 2  
0003 Central control address 3  
0064 Central control address 64  
0099 No central control address set (setting at time of shipping)  
0000 Normal (setting at time of shipping)  
0001 Priority  
Operating mode  
priority change  
Compressor ON  
Compressor OFF  
2
0000  
0001  
0002  
0004  
0005  
0006  
MED 1 min., LO 3 min.  
LO  
LO  
MED  
Fan speed when  
heating thermostat is  
OFF  
LO  
LO  
MED 1 min., LO 3 min.  
MED  
MED  
MED  
MED  
LO  
0000 No shift  
0001  
0002  
0003  
0004  
0005  
0006  
Shifts intake temperature 2°F (1°C) down.  
Shifts intake temperature 4°F (2°C) down.  
Shifts intake temperature 6°F (3°C) down.  
Shifts intake temperature 8°F (4°C) down.  
Heating intake  
temperature shift  
Shifts intake temperature 10°F (5°C) down.  
Shifts intake temperature 12°F (6°C) down.  
0000 No heater  
Electric heater  
installation  
0001 Heater installed  
0000 No (setting at time of shipping)  
0001 Yes  
Humidifying when  
heater thermostat is  
OFF  
Change to remote  
controller sensor  
thermostat differential  
0000 Thermostat OFF differential: –2°F (– 1°C) (setting at time of shipping)  
0001 Thermostat OFF differential: –1°F (– 0.5°C)  
0000 Normal  
0001  
Mode  
dependency  
0000 Normal  
0001 Cooling only  
Cooling-only  
2-32  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
16. Detailed Settings Functions  
2
• This allows the system address, indoor unit  
address, and other settings to be made for the  
individual or group-control indoor unit to which the  
remote controller used for detailed settings is con-  
nected.  
When detailed settings mode is engaged, opera-  
tion stops at the individual or group-control indoor  
unit where the remote controller used for detailed  
settings is connected. Simple settings items can  
also be set at this time.  
7
3
4
<Procedure>  
Press and hold the  
and  
buttons  
,
simultaneously for 4 seconds or longer.  
1
6
1
5
,” unit No. “  
group control), item code “ ,and settings data  
” are displayed blinking on the remote  
” (or “  
” in the case of  
controller LCD display.  
At this time, the indoor unit fan (or all indoor unit  
fans in the case of group control) begins operat-  
ing.  
If group control is in effect, press the  
button and select the address (unit No.) of the  
indoor unit to set. At this time, the fan at the  
indoor unit begins operating.  
2
Press the temperature setting  
/
buttons to select the item code to change.  
Press the timer time  
/
buttons to select  
the desired setting data.  
* For item codes and setting data, refer to the  
following page.  
Press the  
button.  
(The display stops blinking and remains lit, and  
setting is completed.)  
Press the  
button to return to normal remote  
controller display.  
2-33  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
List of Detailed Setting Items  
Setting data  
Description  
Item code  
Item  
No.  
No.  
No.  
Description  
Description  
1-Way Air Discharge  
Semi-Concealed (A)  
4-Way Air Discharge  
Semi-Concealed (X)  
0001  
0000  
0005  
Concealed Duct (U)  
Type  
Concealed Duct High  
Static Pressure (D)  
0006  
0001  
0009  
0017  
0007  
0003  
Ceiling-Mounted (T)  
28 (Type 0952)  
0008  
0005  
0015  
Wall-mounted (K)  
36 (Type 1252)  
112 (Type 3652)  
22 (Type 0752)  
56 (Type 1852)  
Indoor unit  
capacity  
80 (Type 2452)  
(Except FR254, FMR254)  
0012  
140 (Type 4852)  
0001 Unit No. 1  
0002 Unit No. 2  
0003 Unit No. 3  
System  
address  
0030 Unit No. 30  
0099 Not set  
0001 Unit No. 1  
0002 Unit No. 2  
0003 Unit No. 3  
Indoor unit  
address  
2
0064 Unit No. 64  
0099 Not set  
0000 Individual (1:1 = Indoor unit with no group wiring)  
0001 Main unit (One of the group-control indoor units)  
0002 Sub unit (All group-control indoor units except for main unit)  
0099 Not set  
Group  
control  
address  
010 Shifts intake temperature by
؁
20°F (
؁
10°C).  
009 Shifts intake temperature by
؁
18°F (
؁
9°C).  
Cooling  
intake  
temperature  
shift  
001 Shifts intake temperature by
؁
2°F (
؁
1°C).  
0000 No intake temperature shift  
0001 Shifts intake temperature by +2°F (+1°C).  
0009  
0010  
Shifts intake temperature by +18°F (+9°C).  
Shifts intake temperature by +20°F (+10°C).  
Automatic  
stop time  
after  
operation  
start  
0000 Function disabled  
0001 Stops automatically 5 minutes after operation starts.  
0002 Stops automatically 10 minutes after operation starts.  
0123 Stops automatically 615 minutes after operation starts.  
0124 Stops automatically 620 minutes after operation starts.  
0125 Stops automatically 625 minutes after operation starts.  
*Can be set  
in 5-minute  
units.  
2-34  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
Setting data  
Description  
Item  
Item code  
No.  
0000  
0001  
010  
5 minutes  
4 minutes  
Forced thermostat ON  
time  
(1B)  
009  
Cooling discharge  
temperature shift  
008  
0010  
010  
009  
008  
Heating discharge  
temperature shift  
0010  
0001  
0002  
0003  
Temperature shift for  
cooling/heating change  
in “Auto Heat/Cool” mode  
0007  
0018  
0019  
64°F (18°C) (Lower limit at time of shipping)  
66°F (19°C)  
(Upper limit)  
(Lower limit)  
0029  
0030  
0016  
0017  
84°F (29°C)  
2
86°F (30°C) (Upper limit at time of shipping)  
60°F (16°C) (Lower limit at time of shipping)  
62°F (17°C)  
(Upper limit)  
(Lower limit)  
0029  
0030  
0018  
0019  
84°F (29°C)  
Change to remote  
control  
86°F (30°C) (Upper limit at time of shipping)  
64°F (18°C) (Lower limit at time of shipping)  
66°F (19°C)  
temperature  
setting range  
(Upper limit)  
(Lower limit)  
0029  
0030  
0017  
0018  
84°F (29°C)  
86°F (30°C) (Upper limit at time of shipping)  
62°F (17°C) (Lower limit at time of shipping)  
64°F (18°C)  
(Upper limit)  
(Lower limit)  
78°F (26°C)  
0026  
0027  
0000  
0001  
0000  
0001  
80°F (27°C) (Upper limit at time of shipping)  
Normal  
Humidifier operation  
Ignore heat exchanger temperature conditions.  
Filter input (differential pressure switch input)  
Alarm input (for trouble input about air cleaner or similar device)  
Filter (CN70) input  
switching  
Humidifier input (Operates linked with drain pump  
when humidifier is ON.)  
0002  
0000  
0002  
Present (Setting at time of shipping)  
None  
Indoor unit electronic  
control valve  
Normal (Used as optional relay PCB or JEMA  
standard HA terminal.)  
0000  
T10 terminal switching  
0001  
0002  
Used for OFF reminder  
Fire prevention input  
2-35  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
Setting data  
Description  
Item  
Item  
code  
No.  
0000 No forced operation  
0001 Forced operation for 1 minute  
Automatic drain pump  
operation  
0060 Continuous operation  
0000 None  
Ventilation fan operation  
0001 Ventilation fan operated by remote controller.  
0000 Not used. (Body sensor is used.)  
0001 Remote control sensor is used.  
0000 Normal (displayed)  
Wired remote controller sensor  
“Operation change control in  
progress” display  
0001 Not displayed  
0000 None  
OFF reminder function for  
when weekly timer is used  
0001 Only stop time setting is enabled.  
0000 Discharge temperature control OFF  
0001 Discharge temperature control ON  
0000 RAP valve control OFF  
Discharge temperature control  
RAP valve  
0001 RAP valve control ON  
Control temperature 55°F (13°C )  
0013  
Heat exchanger temperature  
for cold air discharge  
0014 Control temperature 57°F (14°C )  
(Heat exchanger control point  
for control to prevent cold air)  
Control temperature 77°F (25°C )  
0025  
2
0026 Control temperature 78°F (26°C )  
Output linked with fan. (ON when indoor unit fan is  
operating.)  
0000  
Fan output switching  
0001 Fan mode operation output  
0000 No delayed start  
0001 1 sec. delayed start  
0002 2 sec. delayed start  
Drain pump delayed start time  
0058 58 sec. delayed start  
0059 59 sec. delayed start  
0060 60 sec. delayed start  
0000 Humidifier output OFF. Drain pump stopped.  
0001 Humidifier output ON. Drain pump operates.  
Humidifier setting  
Humidifier output ON. Drain pump operates for 1 minute  
0002  
when total humidifier operating time reaches 60 minutes.  
0003 Humidifier output ON. Drain pump stopped.  
0000 Standard setting  
Flap operation mode  
Flap swing mode  
Draft reduction mode (Flap swing lower-limit position is  
0001  
upwards.)  
Smudging reduction mode (Flap swing upper-limit position  
is shifted downwards.)  
0000  
0001 Normal mode  
Draft reduction mode (Flap lower-limit position is shifted  
shifted upwards.)  
0002  
2-36  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
Setting data  
Description  
Purpose  
Item  
code  
Item  
No.  
DC fan tap  
operating mode  
0000 Standard  
High ceiling use  
Standard (setting at time of shipping)  
High ceiling setting 1 (with standard panel)  
For low  
static-pressure  
filter  
Ultra long-life filter, oil guard panel, ammonia  
deodorizing filter, optical regenerative deodorizing  
filter  
Fan tap setting  
(Fan tap change  
in order to prevent  
drop in air  
0001  
High ceiling use  
High ceiling setting 2 (with standard panel)  
discharge caused  
by filter  
(Antibacterial) high-performance filter (90%)  
(Antibacterial) high-performance filter (65%)  
Air-cleaning unit, air-cleaning unit + optical  
regenerative deodorizing filter, deodorant (activated  
charcoal) filter  
For low  
static-pressure  
filter  
installation)  
0003  
0006  
For air-blocking  
material  
For air-blocking  
material  
For 3-way discharge, when discharge duct is  
connected  
For 2-way discharge  
0000 No humidifier output  
0001 1 sec.  
Humidifier ON  
time  
0002 2 sec.  
(ON time per 60  
seconds)  
0058 58 sec.  
2
0059 59 sec.  
0060 Continuously ON  
0000 Function disabled  
0001 Function enabled  
0000 Function disabled  
0001 Function enabled  
Repeat timer  
switching  
Timer function  
change prohibit  
Smudging control 0000 No smudging control  
2-37  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
Selecting the DC fan motor tap  
(when setting with the remote controller)  
<Procedure>  
Stop the system before performing these steps.  
Press and hold the  
for 4 seconds or longer.  
If group control is in effect, press the  
and  
buttons simultaneously  
,
button and select  
the address (unit No.) of the indoor unit to set. At this time, the  
fan at the indoor unit begins operating.  
6
2
3
Use the temperature setting buttons to select item code “5d.”  
Press the timer time  
setting data.  
/
buttons to select the desired  
* For item codes and setting data, refer to Table 1 – Table 4.  
Press the button. (The display stops blinking and remains  
lit, and setting is completed.)  
1
5
1
4
* If air-blocking material is used, use the same procedure as in  
steps (3) – (5) above and change the setting for item code “62”  
to “0000.”  
* Failure to make this setting may result in  
decreased airflow and condensation.  
To change the selected indoor unit, go to step (2).  
Press the  
button to return to normal remote controller display.  
Table 1 Table of DC Fan Motor Tap Settings (4-way Air Discharge Semi-Concealed type)  
Setting No. Remote controller setting data  
Purpose of use, names of accessories  
Standard (setting at time of shipping)  
0000  
High ceiling setting 1 (for standards panel)  
Super long-life filter  
2
Oil guard panel  
(1)  
0001  
Oil guard panel with raising / lowering grille  
Ammonia deodorant filter  
Optical regeneration deodorant filter  
High ceiling setting 2 (for standards panel)  
Ceiling panel with special raising / lowering grille for high locations  
High performance filter (90% by JIS colorimetric method)  
High performance filter (65% by JIS colorimetric method)  
Air cleaning unit  
(3)  
(6)  
0003  
0006  
Optical regeneration deodorant filter for air cleaning unit  
Deodorant filter  
Air-blocking material (for 3-way air discharge)  
Air-blocking material (when a discharge duct is connected)  
Air-blocking material (for 2-way air discharge)  
Table 2 Table of DC Fan Motor Tap Settings (ceiling-mounted type)  
Setting No. Remote controller setting data  
0000  
Purpose of use, names of accessories  
Standard (setting at time of shipping)  
High ceiling setting  
Super long-life filter  
(1)  
(3)  
0001  
0003  
Ammonia deodorant filter (65% by JIS colorimetric method)  
Optical regeneration deodorant filter  
High performance filter (65% by JIS colorimetric method)  
Deodorant filter (65% by JIS colorimetric method)  
Table 3 Table of DC Fan Motor Tap Settings (1-way Air Discharge Semi-Concealed type)  
Setting No. Remote controller setting data  
0000  
Purpose of use, names of accessories  
Standard (setting at time of shipping)  
Optical regeneration deodorant filter  
(1)  
(3)  
0001  
0003  
Deodorant filter (65% by JIS colorimetric method)  
Ammonia deodorant filter (65% by JIS colorimetric method)  
2-38  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
Selecting the DC fan motor tap (when setting from the PCB)  
4-way Air Discharge Semi-Concealed type  
<Procedure> Stop the system before performing these steps.  
Open the electrical component box cover, then check the indoor unit control PCB.  
Connect the jumper connector (2P: yellow) which was supplied with the accessory to the correct connector pin  
on the indoor unit control PCB according to the setting number which was confirmed in Table 1 (Table of DC  
Fan Motor Tap Settings).  
If the setting No. is (1), then connect the jumper connector to the connector pin TP1 (2P: red) on the indoor unit  
control PCB.  
If the setting No. is (3), then connect the jumper connector to the connector pin TP3 (2P: yellow) on the indoor unit  
control PCB.  
White Yellow Red  
TP6 TP3 TP1  
2
Suspended type  
<Procedure> Stop the system before performing these steps.  
Open the electrical component box cover, then check the indoor unit control PCB.  
Connect the jumper connector (2P: yellow) which was supplied with the accessory to the correct connector pin  
on the indoor unit control PCB according to the setting number which was confirmed in Table 2 (Table of DC  
Fan Motor Tap Settings).  
If the setting No. is (1), then connect the jumper connector to the connector pin TP1 (2P: red) on the indoor unit  
control PCB.  
If the setting No. is (3), then connect the jumper connector to the connector pin TP3 (2P: yellow) on the indoor unit  
control PCB.  
1-way Air Discharge Semi-Concealed type  
<Procedure> Stop the system before performing these steps.  
Open the electrical component box cover, then check the indoor unit control PCB.  
Connect the jumper connector (2P: yellow) which was supplied with the accessory to the correct connector pin  
on the indoor unit control PCB according to the setting number which was confirmed in Table 3 (Table of DC  
Fan Motor Tap Settings).  
If the setting No. is (1), then connect the jumper connector to the connector pin TP1 (2P: red) on the indoor unit  
control PCB.  
If the setting No. is (3), then connect the jumper connector to the connector pin TP3 (2P: yellow) on the indoor unit  
control PCB.  
2-39  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
17. Remote Controller Servicing Functions  
Operation with  
Press and hold the  
for 4 seconds or longer.  
button  
Test run  
forced thermostat  
ON  
Sensor  
temperature  
display  
Temperature  
display from each  
sensor  
Press and hold the  
buttons for 4 seconds or longer.  
and  
Current operation is  
maintained.  
Press and hold the  
and  
Servicing check Alarm history  
buttons for 4 seconds or longer.  
display  
display  
Press the  
button.  
Filter lifetime,  
operating mode  
Simple settings priority, central  
control address,  
Press and hold the  
buttons for 4 seconds  
or longer.  
and  
When settings are made  
from a remote controller,  
the indoor unit where that  
remote controller is  
and other settings  
System address,  
Press and hold the  
,
indoor unit address,  
Detailed settings central control  
address, and other  
settings  
connected stops.  
and  
buttons for 4 seconds  
or longer.  
Automatic address  
setting based on  
Press and hold the  
timer operation  
and the  
Automatic  
buttons  
command from the  
address  
Automatic reset  
wired remote  
for 4 seconds or longer.  
controller  
Entire system stops.  
Press and hold the  
and the  
Change of indoor  
Address change  
Press the  
button.  
timer operation  
buttons  
unit address  
2
for 4 seconds or longer.  
2-40  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
2
Test Run Function  
Operates the unit with the thermostat forced ON.  
<Procedure>  
Press and hold the  
longer.  
button for 4 seconds or  
3
Test” appears on the remote controller LCD  
display.  
Start operation.  
Press the  
button to return to normal remote  
controller display.  
1
4
2
2-41  
Remote Control Functions  
3.Timer Remote Controller (RCS-TM80BG)  
Sensor Temperature Diaplay  
Sensor Temperature Display Function  
(displayed regardless of whether unit is  
operating or stopped)  
2
The procedure below displays the sensor tempera-  
tures from the remote controller, indoor unit, and out-  
door unit on the remote controller.  
<Procedure>  
Press and hold the  
and  
buttons  
simultaneously for 4 seconds or longer.  
The unit No. “  
” (main unit No.), item code “XX”  
(sensor address), and servicing monitor “ XX”  
X-X  
3
(sensor temperature) are displayed on the remote  
controller LCD display.  
5
4
1
Press the temperature setting  
/
buttons and select the item code to the address of  
the sensor to monitor.  
NOTE:  
The temperature on the remote controller is displayed  
in Celusis (C).  
Please note that you will not mistakenly read it  
in Fahrenheit (F) on the display.  
(For the relationships between the sensor  
addresses and sensor types, refer to the table of  
temperature sensors and addresses below.)  
If group control is in effect, press the  
button to select the unit to monitor.  
Press the temperature setting buttons  
to select the item code to change.  
0A  
2
2A  
2B  
2C  
2D  
2E  
2F  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
3A  
3B  
3C  
3D  
3E  
3F  
40  
41  
42  
4A  
4B  
4C  
4D  
4E  
4F  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
5A  
5B  
5C  
5D  
5E  
5F  
60  
61  
62  
6A  
6B  
6C  
6D  
6E  
6F  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
7A  
7B  
7C  
7D  
7E  
7F  
80  
81  
82  
Discharge temp. 1  
Discharge temp. 2  
High-pressure sensor temp.  
Heat exchanger gas 1  
Heat exchanger liquid 1  
Heat exchanger gas 2  
Heat exchanger liquid 2  
Outdoor air temp.  
Press the  
button to return to  
0B  
0C  
0D  
0E  
0F  
10  
11  
normal remote controller display.  
NOTE  
The temperature display appears as “- - - -”  
for units that are not connected.  
* If monitor mode is engaged while normal  
operation is in progress, only the parts of  
the LCD display shown in the figure will  
change. Other parts continue to display  
the same information as during normal  
operation.  
12  
13  
14  
15  
16  
17  
18  
19  
1A  
1B  
1C  
1D  
1E  
1F  
20  
21  
22  
CT2  
Discharge temp. 3  
CT3  
02  
03  
04  
05  
06  
07  
Intake temp.  
E1  
Low-pressure sensor temp.  
Suction temp.  
E3  
Oil 1  
Oil 2  
Oil 3  
Discharge temp.  
Discharge temp. setting  
Position of indoor unit  
Motor Operated Valve (MOV)  
08  
2-42  
Trouble Diagnosis  
Contents  
3.TROUBLE DIAGNOSIS  
1. Contents of Remote Controller Switch Alarm Display....................................................3-2  
2. Outdoor Unit Control PCB LED Display ...........................................................................3-4  
3. W-2WAY ECO-i Alarm Codes..............................................................................................3-5  
4. Blinking (Inspection) Display on the Remote Controller......................................... 3-22  
3
3-1  
Trouble Diagnosis  
1. Contents of Remote Controller Switch Alarm Display  
ON:  
Blinking:  
OFF:  
Wired  
Wireless  
remote controller  
receiver display  
remote  
control  
display  
Possible cause of malfunction  
Error in receiving serial communication signal.  
Remote controller is  
detecting error signal from  
indoor unit.  
Serial  
communication  
errors  
(Signal from main indoor unit in case of group control)  
Outdoor system address, indoor unit address, or indoor unit  
address independent/main/sub unit setting has not been made.  
(Auto address is not completed.)  
Operating  
lamp blinking  
<E01>  
Mis-setting  
<E02>  
Error in transmitting serial communication signal.  
Indoor unit is detecting error signal from remote controller and system controller.  
<<E03>>  
Error in receiving serial communication signal.  
When turning on the power supply, the number of connected  
indoor units does not correspond to the number set. (Except R.C.  
address is “0.)  
Indoor unit is detecting error  
signal from outdoor unit.  
E04  
Heating ready  
lamp blinking  
Group wiring failure of indoor units in the refrigerant system  
(occurring when remote controller is operated immediately after  
automatic address setting)  
Outdoor unit is detecting error Error in receiving serial communication signal.  
signal from indoor unit.  
There is an indoor unit which does not send signals when the  
power is ON.  
E06  
3
Improper setting  
<<E08>>  
<<E09>>  
Indoor unit address setting is duplicated.  
Duplicated remote controller “main” setting.  
Automatic address setting start is prohibited.  
AP pin was short-circuited at time when automatic address setting  
was started.  
Operating  
lamp blinking  
Improper setting  
E12  
Indoor unit communication  
error of group control wiring.  
Error of main indoor unit in receiving serial communication signal  
from sub indoor units.  
E18  
E15  
During auto. address setting, Number of connected indoor units is less than the number set.  
number of connected units  
does not correspond to  
Number of connected indoor units is more than the number set.  
E16  
E20  
E24  
E25  
E26  
Heating ready  
lamp blinking  
number set.  
No indoor unit is connected during auto. address setting.  
Main outdoor unit is detecting error signal from sub outdoor unit.  
Duplicated outdoor unit address.  
Mismatch in “No. of outdoor units” setting.  
Error of sub outdoor unit in receiving serial communication signal  
from main outdoor unit.  
E29  
<<L02>>  
<L03>  
Connected indoor unit is not a multi unit.  
Improper setting  
Duplication of main indoor unit address setting in group control.  
Duplicated indoor unit priority (priority indoor unit).  
L05  
L06  
Operating and heating  
ready lamps blinking  
simultaneously  
Duplicated indoor unit priority (non-priority indoor unit) and  
outdoor unit.  
Group control wiring is connected to individual control indoor unit.  
Indoor unit address is not set.  
L07  
L08  
<<L09>>  
L17  
Capacity code of indoor unit is not set.  
Mismatch of outdoor unit type.  
Operating and heating  
ready lamps blinking  
simultaneously  
Duplication of outdoor R.C. address setting.  
L04  
Capacity code of outdoor unit is not set.  
L10  
Indoor coil temp. sensor (E1)  
Operating and timer  
lamps blinking  
alternately  
<<F01>>  
<<F03>>  
<<F10>>  
<<F11>>  
Indoor unit  
Thermistor  
fault  
Indoor coil temp. sensor (E3)  
Indoor suction air (room) temp. sensor  
Indoor discharge air temp. sensor  
Continued  
3-2  
Trouble Diagnosis  
1. Contents of Remote Controller Switch Alarm Display  
ON:  
Blinking:  
OFF:  
Wired  
Wireless  
remote controller  
receiver display  
remote  
control  
display  
Possible cause of malfunction  
Compressor 1 (INV) discharge temp. sensor  
Compressor 2 (constant speed) discharge temp. sensor  
Compressor 3 (constant speed) discharge temp. sensor  
Outdoor air temp. sensor  
Outdoor unit  
F04  
F05  
F22  
F08  
Thermistor  
fault  
F07  
F06  
Heat exchanger 1 liquid temp. sensor  
Heat exchanger 1 gas temp. sensor  
Compressor intake temp. sensor (suction temp)  
High-pressure sensor  
Operating and timer  
lamps blinking  
alternately  
F12  
F16  
Low-pressure sensor  
F17  
Heat exchanger 2 liquid temp. sensor  
Heat exchanger 2 gas temp. sensor  
F24  
F23  
<<P09>>  
Ceiling panel connection failure  
Timer and heat  
ready lamp blinking  
alternately  
Thermal protector in indoor unit fan motor is activated.  
Float switch is activated.  
<<P01>>  
<<P10>>  
<<P12>>  
P14  
Indoor unit  
Protective  
device  
3
Fan inverter protection function activated.  
O2 sensor activated  
Outdoor unit  
Compressor 1 (INV) discharge temp. trouble  
High-pressure switch  
P03  
P04  
Reverse phase (missing phase) detected.  
DCCT, ACCT overcurrent (compressor less than 80 Hz)  
Compressor 2 (constant speed) discharge temp. trouble  
P05  
P16  
P17  
Operating and heat  
ready lamp blinking  
alternately  
Compressor 3 (constant speed) discharge temp. trouble  
Outdoor unit fan trouble  
P18  
P22  
P26  
DCCT, ACCT overcurrent (80 Hz or more)  
Start failure caused by compressor wire missing phase, DCCT  
failure, or similar problem (INV compressor start failure).  
P29  
Operating and timer  
lamp blinking  
simultaneously  
Failure of nonvolatile memory IC (EEPROM) on indoor unit control PCB  
Failure of nonvolatile memory IC (EEPROM) on outdoor unit control PCB  
Compressor 2 (constant speed)  
F29  
Operating and timer  
lamp blinking  
simultaneously  
F31  
H11  
H21  
H12  
H22  
Overload current detected.  
Lock current detected.  
Protective  
device  
Compressor 3 (constant speed)  
Compressor 2 (constant speed)  
Compressor 3 (constant speed)  
Compressor 1 (INV)  
H03  
H13  
H23  
No current detected when  
compressor was ON.  
Compressor 2 (constant speed)  
Compressor 3 (constant speed)  
Compressor 2 (constant speed)  
Compressor 3 (constant speed)  
Low-pressure trouble  
Timer lamp blinking  
Discharge temp. sensor  
trouble  
H15  
H25  
H06  
H31  
Outdoor unit protection  
Outdoor unit protection  
HIC trouble alarm  
Compressor 1 (INV)  
Compressor 2 (constant speed)  
Compressor 3 (constant speed)  
H08  
H27  
H28  
Connection failure of oil detection sensor  
Fusing of electromagnetic contact (Current detected when compressor was OFF)  
Automatic backup operation  
only blinking (No display changes)  
<< >> alarm indication: Does not affect the operation of other indoor units.  
<
> alarm indication: In some cases may affect the operation of other indoor units.  
3-3  
Trouble Diagnosis  
2. Outdoor Unit Control PCB LED Display  
(
: ON  
: Blinking  
: OFF)  
LED (RED)  
Display meaning  
1
2
After the power is turned ON (and automatic address setting is not in progress), no  
communication with the indoor units in that system is possible.  
(Both OFF)  
After power is turned ON (and automatic address setting is not in progress), 1 or more indoor  
units are confirmed in that system; however, the number of indoor units does not match the  
number that was set.  
(OFF)  
(ON)  
Automatic address setting was completed successfully. (After the power is turned ON,  
and automatic address setting is not in progress, the number of detected indoor units  
connected to that system matches the number that was set, and regular communications  
are occurring.)  
(Both OFF)  
Automatic address setting is in progress.  
(Blinking alternately)  
(Both blinking)  
3
At time of automatic address setting, the number of indoor units did not match the  
number that was set.  
Alarm display  
LED 1 blinks M times, then LED 2 blinks N times. The cycle then repeats.  
M = 2: P alarm 3: H alarm 4: E alarm 5: F alarm 6: L alarm  
N = Alarm No.  
(Blinking alternately)  
Example: LED 1 blinks 2 times, then LED 2 blinks 17 times. The cycle then repeats.  
Alarm is “P17.”  
3-4  
Trouble Diagnosis  
3. W-2WAY ECO-i Alarm Codes  
W-2WAY ECO-i Trouble Diagnosis  
Alarm code  
Alarm meaning  
Page  
E06  
E12  
E15  
E16  
E20  
E24  
Outdoor unit failed to receive serial communication signals from indoor unit.  
Automatic address setting start is prohibited.  
Automatic address setting alarm (too few units)  
Automatic address setting alarm (too many units)  
No indoor units at automatic address setting.  
3-6  
3-6  
3-6  
3-7  
3-7  
Outdoor unit (INV) failed to receive communications from another outdoor  
unit (constant-speed).  
3-7  
3-8  
3-8  
3-8  
E25  
E26  
E29  
Outdoor unit address setting failure (duplication)  
Mismatch in outdoor unit quantity  
Outdoor unit failed to receive communication from relay control unit  
3-9  
3-9  
F04  
F05  
F22  
F06  
F07  
F08  
F12  
F16  
F17  
F23  
F24  
F31  
Compressor 1 discharge temperature sensor trouble  
Compressor 2 discharge temperature sensor trouble  
Compressor 3 discharge temperature sensor trouble  
Gas temperature sensor trouble at outdoor heat exchanger 1 (In)  
Liquid temperature sensor trouble at outdoor heat exchanger 1 (Out)  
Outdoor air temperature sensor trouble  
Compressor intake temperature sensor trouble  
High-pressure sensor trouble  
Low-pressure sensor trouble  
3-9  
3-10  
3-10  
3-11  
3-11  
3-11  
3-11  
3-10  
3-10  
3-12  
3
Gas temperature sensor trouble at outdoor heat exchanger 2 (In)  
Liquid temperature sensor trouble at outdoor heat exchanger 2 (Out)  
Outdoor unit non-volatile memory (EEPROM) trouble  
H03  
H11  
H12  
H05  
H06  
H13  
H15  
H21  
H22  
H23  
H25  
H31  
Compressor CT sensor disconnected or short-circuit.  
Constant speed compressor 2 overcurrent alarm  
Constant speed compressor 2 lock current alarm  
Compressor 1 discharge temperature sensor disconnected  
Low-pressure trouble in refrigerant circuit.  
Compressor 2 CT sensor disconnected or short-circuit  
Compressor 2 discharge temperature sensor disconnected  
Compressor 3 overcurrent alarm  
3-12  
3-14  
3-14  
3-15  
3-13  
3-15  
3-15  
3-14  
3-14  
3-15  
3-15  
3-16  
Compressor 3 lock current alarm  
Compressor 3 CT sensor disconnected or short-circuit  
Compressor 3 discharge temperature sensor disconnected  
HIC trouble alarm  
3-16  
3-16  
3-17  
3-17  
3-17  
3-17  
L04  
L05  
L06  
L10  
L17  
L18  
Outdoor unit address duplication  
Duplicated indoor unit priority (alarm at priority indoor units)  
Duplicated indoor unit priority (alarm at non-priority indoor units)  
Outdoor unit capacity not set  
Outdoor unit model mismatch  
4-way valve operation failure.  
3-18  
3-19  
3-20  
3-20  
3-18  
3-18  
3-21  
3-21  
3-21  
P03  
P04  
P05  
P16  
P17  
P18  
P22  
P26  
P29  
Compressor 1 discharge temperature trouble  
High-pressure switch activated  
Reverse phase (or missing phase) detected, capacity mismatch  
Compressor 1 overcurrent  
Compressor 2 discharge temp trouble  
Compressor 3 discharge temp trouble  
Fan motor trouble  
Inverter compressor high-frequency overcurrent alarm  
Inverter compressor missing phase or lock alarm  
CHECK blinking (1)  
CHECK blinking (2)  
3-22  
3-23  
Blinking on the wired remote controller  
3-5  
Trouble Diagnosis  
3. W-2WAY ECO-i Alarm Codes  
E06 Alarm  
Alarm code  
E06  
Alarm meaning  
Alarm conditions  
Probable cause  
Outdoor unit failed to receive serial communication signals from indoor unit.  
Outdoor unit failed to receive serial communication signals from indoor unit.  
(1) The indoor unit power was cut OFF after initial communications were completed.  
(2) An open circuit or short circuit occurred in the inter-unit control wiring after initial  
communications were completed.  
Check  
Check the power at the indoor and outdoor units, and check the inter-unit control wiring.  
Correction  
Example  
Notes  
This alarm is detected after initial communications are completed. Therefore, it does not occur in  
cases of “disconnected serial connector,no terminal unit set,or other trouble that occurs  
before initial communications are completed. If initial communications have not been completed,  
alarm E04 occurs.  
E12 Alarm  
Alarm code  
E12  
Automatic address setting start is prohibited.  
Alarm meaning  
Alarm conditions  
Automatic address setting was started when automatic address setting was in progress at  
another outdoor unit in the same link.  
Automatic address setting is in progress at another outdoor unit.  
Probable cause  
Check  
This alarm is not displayed on the remote controller. Therefore check the blinking  
on the outdoor unit PCB.  
3
Correction  
Wait for automatic address setting to be completed at the outdoor unit where it is currently in  
progress. Then start automatic address setting again.  
Example  
Notes  
E15 Alarm  
Alarm code  
E15  
Alarm meaning  
Alarm conditions  
Probable cause  
Automatic address setting alarm (too few units)  
The number of indoor units was too few when automatic address setting was performed.  
(1) The number of indoor units set at the indoor unit quantity setting SW (No. of I/U: S004, S005)  
on the outdoor unit PCB is too many.  
(2) The inter-unit control wiring between indoor units has been cut.  
Check  
(1) Refer to the test run servicing materials and check the indoor unit quantity setting SW (No. of  
I/U: S004, S005).  
(2) Check the inter-unit control wiring at the indoor and outdoor units.  
After correcting the indoor unit quantity setting or the inter-unit control wiring, perform automatic  
address setting again.  
Correction  
Example  
Notes  
W-2WAY ECO-i switch position  
S004  
S005  
3-6  
Trouble Diagnosis  
3. W-2WAY ECO-i Alarm Codes  
E16 Alarm  
Alarm code  
E16  
Alarm meaning  
Alarm conditions  
Automatic address setting alarm (too many units)  
There were a number of indoor units was too many when Automatic address setting was performed  
at a number of indoor units.  
After initial communications were completed, an unrecognized unit was detected.  
Probable cause  
(1) The SW for setting the number of indoor units is incorrect.  
(2) The inter-unit control wiring is wired incorrectly.  
Check  
(1) Refer to the test run servicing materials and check the number of indoor units that is set.  
(2) Check the inter-unit control wiring at the indoor and outdoor units.  
Correction  
After correcting the indoor unit quantity setting or the inter-unit control wiring, perform automatic  
address setting again.  
Example  
Notes  
E20 Alarm  
Alarm code  
E20  
Alarm meaning  
Alarm conditions  
Probable cause  
No indoor units at automatic address setting.  
When automatic address setting was performed, no indoor units were recognized.  
(1) The inter-unit control wiring from the outdoor unit to the indoor units has been cut.  
(2) Serial connector (OC: CN001) is disconnected at the outdoor unit.  
(3) The power is OFF at all indoor units in the system.  
3
Check  
(1) Check whether the inter-unit control wiring from the outdoor unit to the indoor units is cut.  
(2) Check whether serial connector (OC: CN001) is disconnected at the outdoor unit.  
(3) Check the power at the indoor units.  
Reconnect the inter-unit control wire from the outdoor unit to the indoor unit.  
Correction  
Example  
Notes  
(1)  
Position of serial connector (OC: CN001) on W-2WAY control PCB  
CN001  
E24 Alarm  
Alarm code  
E24  
Alarm meaning  
Alarm conditions  
Probable cause  
Outdoor unit (main) failed to receive signal from other outdoor unit (sub).  
After initial communications were completed, communications from an outdoor unit stopped.  
(1) After initial communications were completed, the outdoor unit main/sub control wiring was cut.  
(2) After initial communications were completed, the outdoor unit power was turned OFF.  
Check  
Correction  
Example  
Notes  
3-7  
Trouble Diagnosis  
3. W-2WAY ECO-i Alarm Codes  
E25 Alarm  
Alarm code  
E25  
Alarm meaning  
Alarm conditions  
Outdoor unit address setting failure (duplication)  
Communication by the outdoor unit main/sub control wiring was received that contained the  
same address as that unit 5 times or more within 3 minutes.  
The unit number is set incorrectly.  
Probable cause  
Check  
Check the unit number again.  
Correction  
Correct the incorrect unit number setting.  
Example  
Notes  
Recovery from this alarm occurs automatically (when communication that contains the same  
address is not received for 3 minutes).  
E26 Alarm  
Alarm code  
E26  
Alarm meaning  
Alarm conditions  
Mismatch in outdoor unit quantity  
After power initialization, the set outdoor unit quantity did not match the number of outdoor units  
detected on the outdoor unit main/sub control wiring for 3 minutes or longer.  
(1) The outdoor unit quantity is set incorrectly.  
(2) The outdoor unit main/sub control wiring is cut.  
(1) Check the outdoor unit quantity setting again.  
Probable cause  
Check  
(2) Check the outdoor unit main/sub control wiring.  
(1) Correct the incorrect outdoor unit quantity setting.  
(2) Repair the outdoor unit main/sub control wiring.  
3
Correction  
Example  
Notes  
Recovery from this alarm occurs automatically (when the set outdoor unit quantity matches the  
number of outdoor units detected on the outdoor unit main/sub control wiring).  
E29 Alarm  
Alarm code  
E29  
Alarm meaning  
Alarm conditions  
Probable cause  
Outdoor unit (sub) failed to receive signal from outdoor unit (main).  
Outdoor unit (sub) communications from outdoor unit (main) were interrupted for 3 minutes or longer.  
(1) After initial communications were completed, the outdoor unit main-sub control wiring was  
cut.  
(2) After initial communications were completed, the RC connector (CN006) became disconnected.  
(3) The power at the outdoor unit (main) is turned OFF.  
(1) Check the outdoor unit main/sub control wiring.  
(2) Check the RC connectors.  
(3) Check the power at the outdoor unit (main/sub).  
(1) Repair the outdoor unit main/sub control wiring.  
(2) Correct the RC connector connection.  
(3) Turn ON the outdoor unit (main/sub) power.  
Check  
Correction  
Example  
Notes  
3-8  
Trouble Diagnosis  
3. W-2WAY ECO-i Alarm Codes  
F04, F05, F22 Alarm  
Alarm code  
F04, F05, F22  
Alarm meaning  
Compressor 1 discharge temperature sensor (DISCH1) trouble, compressor 2 discharge  
temperature sensor (DISCH2) trouble, Compressor 3 discharge temperature sensor (DISCH3) trouble.  
(1) Discharge temp. of 212°F (100°C) or higher was detected 20 minutes or more after that  
compressor stopped operating.  
Alarm conditions  
Probable cause  
(2) Discharge temp. of 176°F (80°C) or higher was detected after all compressors had been  
stopped for 60 minutes or longer.  
(3) A/D step is 10 steps or less (short circuit).  
(1) Sensor malfunction  
• Sensor element malfunction  
• Sensor wiring is partially disconnected, resulting in increased electrical resistance.  
This alarm does not occur when the wiring is cut or when the connector is not connected to  
the outdoor unit control PCB.  
(2) Crossed wiring or installation error  
• The discharge temperature sensor of that compressor is connected to the discharge tube  
of the other compressor.  
• The connector for the discharge temperature sensor of the problem compressor is  
connected to the outdoor unit PCB connector for the other compressor.  
(3) Outdoor unit PCB failure  
(4) The check valve on the discharge tube for that compressor is wet.  
(5) An air short blockage in the area around the outdoor unit has increased the outdoor unit  
ambient temperature, reducing the cooling effects after the compressor stops.  
(6) There is a cause that results in P03, P17, or P18 alarm.  
3
Check  
(1) Sensor malfunction and outdoor unit PCB failure  
Trouble: • Constantly indicates a high temperature.  
• When monitoring software or other means are used for monitoring, the discharge  
temperature at times fluctuates suddenly and wildly.  
• In some cases, the precise temperature may not be known, even when monitoring  
software is used.  
Check: • Wiggle the sensor and check whether the trouble continues.  
• Check whether the connector is partially disconnected from the PCB.  
An F04 alarm will not result if the connector is completely disconnected (circuit is  
open).  
• If the cause is still uncertain, check the following to determine whether a sensor or  
PCB failure has occurred.  
Step 1: Connect the other compressor discharge sensor, or a discharge sensor where  
the F04 alarm has not occurred, to the connector for this compressor on the  
PCB. Measure the temperature at the same point (a location where  
temperature fluctuations are small), and check whether there is a temperature  
difference.  
Difference  
No difference  
A PCB or sensor failure is possible.  
PCB and sensor are normal.  
Step 2: If an abnormality was found at Step 1, connect the problem compressor  
sensor to the other compressor connector on the PCB, or to the PCB  
connector of a device where the F04 alarm has not occurred. Measure the  
temperature at the same point (a location where temperature fluctuations are  
small), and check whether there is a temperature difference.  
Difference  
Sensor failure.  
PCBfailure.  
No difference  
It is convenient at this time to have a discharge temperature sensor on hand.  
(2) Crossed wiring or installation error  
Although the other compressor is operating and this compressor is stopped, the  
discharge temperature of the other compressor does not increase and the discharge  
temperature of this compressor rises.  
Trouble:  
* The discharge temperature remains high immediately after the compressor stops. Wait  
for some time after the compressor stops and observe.  
Check: Check for crossed wiring and installation errors.  
Continued  
3-9  
Trouble Diagnosis  
3. W-2WAY ECO-i Alarm Codes  
(3) Leakage from the discharge tube check valve  
Trouble: Although the other compressor is operating and this compressor is stopped, the  
discharge temperature of this compressor rises together with the temperature of the  
other compressor.  
(4) The ambient temperature around the outdoor unit when it is stopped is 109°F (43°C) or higher.  
Correction  
(1) Replace the sensor.  
(2) Replace the outdoor unit PCB.  
(3) Repair the refrigerant tubing.  
(4) Adjust the amount of refrigerant.  
(5) Correct the trouble.  
Example  
Notes  
(1) Sensor wiring is partially cut.  
This alarm does not indicate that the sensor is disconnected.  
In order to prevent overheating during operation, the outdoor units in this system will not allow a  
compressor to start if the discharge temperature does not decrease while the compressor is  
stopped. If a sensor malfunction results in continuous detection of a high discharge temperature,  
then the compressor may stop for no apparent reason. The purpose of this alarm is to facilitate  
identification of the problem in this case.  
F06, F23 Alarm  
Alarm code  
F06, F23  
Alarm meaning  
Gas temperature sensor (EXG1) trouble at outdoor heat exchanger 1; Gas temperature sensor  
(EXG2) trouble at outdoor heat exchanger 2  
3
Alarm conditions  
Probable cause  
Check  
(1) A/D step is 10 steps or less (short circuit).  
(2) A/D step is 1014 steps or more (open circuit).  
(1) Sensor malfunction (including connector)  
(2) PCB malfunction  
(1) Measure the sensor resistance. Check that the sensor is operating normally.  
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by  
the microcomputer.  
Correction  
Example  
Notes  
F07, F24 Alarm  
Alarm code  
F07, F24  
Alarm meaning  
Liquid temperature sensor (EXL1) trouble at outdoor heat exchanger 1; Liquid temperature sensor  
(EXL2) trouble at outdoor heat exchanger 2  
(1) A/D step is 10 steps or less (short circuit).  
(2) A/D step is 1014 steps or more (open circuit).  
(1) Sensor malfunction (including connector)  
(2) PCB malfunction  
(1) Measure the sensor resistance. Check that the sensor is operating normally.  
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by  
the microcomputer.  
Alarm conditions  
Probable cause  
Check  
Correction  
Example  
Notes  
3-10  
Trouble Diagnosis  
3. W-2WAY ECO-i Alarm Codes  
F08  
Alarm meaning  
Alarm conditions  
Outdoor air temperature sensor (AIR TEMP) trouble  
(1) A/D step is 10 steps or less (short circuit).  
(2) A/D step is 1014 steps or more (open circuit)  
(1) Sensor malfunction (including connector)  
(2) PCB malfunction  
Probable cause  
Check  
(1) Measure the sensor resistance. Check that the sensor is operating normally.  
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by  
the microcomputer.  
Correction  
Example  
Notes  
Alarm code  
F12  
Alarm meaning  
Alarm conditions  
Compressor intake temperature sensor (SCT) trouble  
(1) A/D step is 10 steps or less (short circuit).  
(2) A/D step is 1014 steps or more (open circuit)  
(1) Sensor malfunction (including connector)  
(2) PCB malfunction  
(1) Measure the sensor resistance. Check that the sensor is operating normally.  
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by  
the microcomputer.  
Probable cause  
Check  
3
Correction  
Example  
Notes  
F16 Alarm  
Alarm code  
F16  
Alarm meaning  
Alarm conditions  
High-pressure sensor (HPS) trouble  
(1) Sensor short circuit  
(2) Sensor open circuit  
(1) Sensor malfunction (including connector)  
(2) PCB malfunction  
(1) Measure the sensor resistance. Check that the sensor is operating normally.  
(2) Use a remote monitor or a PC monitor to check the temperature that is recognized  
by the microcomputer.  
Probable cause  
Check  
Correction  
Example  
Notes  
F17 Alarm  
Alarm code  
F17  
Alarm meaning  
Alarm conditions  
Low-pressure sensor (LPS) trouble  
(1) Sensor short circuit  
(2) Sensor open circuit  
(1) Sensor malfunction (including connector)  
(2) PCB malfunction  
(1) Measure the sensor resistance. Check that the sensor is operating normally.  
(2) Use a remote monitor or a PC monitor to check the temperature that is recognized  
by the microcomputer.  
Probable cause  
Check  
Correction  
Example  
Notes  
3-11  
Trouble Diagnosis  
3. W-2WAY ECO-i Alarm Codes  
F31 Alarm  
Alarm code  
F31  
Alarm meaning  
Alarm conditions  
Outdoor unit non-volatile memory (EEPROM) trouble  
(1) Non-volatile memory is not present when power initialization occurs.  
(2) Read values do not match after writing to non-volatile memory is complete.  
Probable cause  
(1) Memory was not inserted after the PCB was replaced.  
(2) The lifetime of the non-volatile memory has been reached.  
(3) Non-volatile memory is installed incorrectly (wrong direction, bent pins, etc.).  
Check  
(1) Check the non-volatile memory on the PCB.  
Correction  
Example  
Notes  
H03 alarm  
Alarm code  
H03  
Alarm meaning  
Alarm conditions  
Compressor CT sensor disconnected or short-circuit  
Alarm occurs if the current value is 1.5 A or less when 2 seconds or longer have elapsed after  
output from that compressor started.  
* No current is detected even though the compressor is operating.  
(1) CT circuit failure (including cut wiring, etc.)  
(2) Disconnected CT circuit connector  
(3) This CT circuit is connected to the connector of the other CT circuit.  
(4) PCB failure  
Probable cause  
Check  
3
(5) Noise  
(1) CT circuit failure, PCB failure  
Trouble: • Current value during compressor operation is below the threshold value.  
Check: • Check that the connector is not disconnected.  
• Check the continuity of the CT circuit.  
Install a normal CT in place of this CT and check. If current is detected, then the  
PCB can be judged OK.  
CT circuit failure  
• Check that current is flowing in the phase where the CT circuit is connected.  
Check voltage and current.  
(2) Crossed wiring or installation error  
Trouble: When the compressor is stopped, the current value at the other compressor is high.  
(3) If the cause is still unknown after checking the above, then it is possible that noise is the  
cause of the trouble. It is necessary to connect a  
PC or other instrument.  
Correction  
(1) Replace the CT circuit.  
(2) Replace the outdoor unit PCB.  
(3) Correct the problem.  
(1) The connector was not inserted after the PCB was replaced.  
Use a normal CT as a tool to determine whether the trouble is a PCB failure or CT failure.  
Example  
Notes  
3-12  
Trouble Diagnosis  
3. W-2WAY ECO-i Alarm Codes  
H06 Alarm  
Alarm code  
H06  
Alarm meaning  
Alarm conditions  
Abnormal low-pressure drop  
A pre-trip occurs during the unit’s operation when the low-pressure sensor installed at constant  
low-pressure parts detects a pressure of 7.25 psi or less continuously for 2 minutes,  
or an instantaneous pressure of 2.90 psi or less. (These values represent abnormal low pressure  
which may damage the compressor.)  
However, the alarm does not actually occur the first 2 times that the above operation takes place.  
At these times, the outdoor unit is stopped and the conditions are monitored. The alarm occurs  
when the above operation occurs for the third time. The first 2 times before the alarm occurs are  
called “pre-trip.After pre-trip occurs, if the low-pressure sensor detects a pressure of 21.8 psi  
or more for 3 minutes of continuous operation, the pre-trip count is reset to 0.  
If the low-pressure sensor detects a pressure of 23.2 psi or less continuously for 60 minutes  
when the compressor is stopped, an alarm occurs immediately (no pre-trip).  
Probable cause  
The unit low pressure has dropped to a level that does not occur under ordinary conditions.  
(1) The absolute amount of gas in the system is too low (as a result of insufficient refrigerant  
charge or leak).  
(2) The refrigerant has accumulated in the circuit and has not returned to the compressor.  
Refrigerant has accumulated in a location of one-way flow and cannot escape.  
High-pressure level is low, resulting in poor flow of refrigerant in the circuit. (A lower high-  
pressure level results in a smaller difference between low pressure and high pressure, that  
may be insufficient to cause refrigerant flow.)  
(3) The refrigerant circuit has become closed, and refrigerant has not returned to the  
compressor. In some cases when moisture enters the refrigerant circuit, it can freeze at the  
low-pressure locations and the resulting ice can block the circuit.)  
If the alarm occurs when there is sufficient refrigerant in the system ((1) and (3)), liquid  
refrigerant has definitely accumulated somewhere in the system. Liquid refrigerant generally  
accumulates in high-pressure locations. In this case the high pressure gradually increases  
(however it may not increase if the location where the liquid accumulates is sufficiently  
large). Depending on the refrigerant saturation temperature, it may also accumulate in low-  
pressure locations. In this case the high pressure is unlikely to increase.  
(1) Check that the service valve is open.  
(2) Check that none of the valves (mechanical valves) in the main refrigerant  
circuit is closed due to an operation failure.  
(3) Check that there is no possibility of foreign objects or water having entered the refrigerant  
circuit.  
(4) Check that valve leakage at a stopped sub unit has not resulted in accumulation of  
refrigerant at that sub unit.  
(5) Check that no refrigerant leakage has occurred.  
(1) If there was a valve operation failure, in general it is necessary to replace the valve.  
(2) If a foreign object or moisture has entered the circuit, install a strainer or dry core (depending  
on the degree of the problem).  
(3) If refrigerant has leaked into stopped sub units, it is likely that valve leakage has occurred.  
The valve must be replaced.  
3
Check  
Correction  
Example  
Notes  
3-13  
Trouble Diagnosis  
3. W-2WAY ECO-i Alarm Codes  
H11, H12, H21, H22 Alarm  
Alarm code  
H11, H12, H21, H22  
H11: Compressor 2 (constant speed) overcurrent alarm  
H12: Compressor 2 (constant speed) lock current alarm  
H21: Compressor 3 (constant speed) overcurrent alarm  
H22: Compressor 3 (constant speed) lock current alarm  
Alarm meaning  
Alarm conditions  
H11, H21: During operation, the compressor current value exceeded 12 A for 30 seconds or longer.  
However this alarm is not detected for 4 seconds after the compressor starts.  
H12, H22: During operation, the compressor current value exceeded 15 A for 2 seconds or longer.  
However this alarm is not detected for 4 seconds after the compressor starts.  
(1) Compressor failure (locked or partially locked)  
(2) CT (Current Transformer) circuit failure (including cut wiring)  
(3) Low power voltage  
Probable cause  
Check  
(4) PCB failure  
(1) Compressor failure (partially locked)  
Trouble: Current value during operation greatly exceeds the value shown above.  
Check: When the current for each phase is measured with a clamp meter or similar  
instrument, check that the current value for all phases is not high. If MG was forced  
ON (use caution), check that compressor noise will not occur or the compressor will  
not run with a groaning sound.  
(2) CT circuit failure, PCB failure  
Trouble:  
Check: · Check for poor connector contact.  
· Check the continuity of the CT circuit.  
· Install a normal CT in place of this CT and check. If current is detected, then the  
PCB can be judged OK.  
3
CT circuit failure  
· Check that current is flowing in the phase where the CT circuit is connected.  
Check voltage and current.  
(3) Low power voltage  
Trouble: In most cases, this occurs when another constant-speed compressor (including  
compressors in other units) or other device starts. It also occurs when the power  
wiring is extremely long.  
Check: Check the voltage between each of the phases. However if this trouble occurs when  
other devices or compressors start, then an oscilloscope is required.  
(4) PCB failure  
Trouble:  
Check: Check that the current value measured with the clamp meter is not lower than the  
value measured with the PC or remote controller.  
Correction  
(1) Replace the compressor.  
(2) Replace the CT circuit.  
(3) Adjust the primary-side power. Repair the power wiring.  
(4) Replace the outdoor unit PCB.  
(5) Correct the trouble.  
* In the case of a compressor failure, it is likely that steps must be taken to correct the cause  
of the compressor failure (such as liquid back-up) in order to prevent recurrence. Be sure to  
check that there is no cause which may result in compressor locking.  
Example  
3-14  
Trouble Diagnosis  
3. W-2WAY ECO-i Alarm Codes  
H13, H23 Alarm  
Alarm code  
H13, H23  
Alarm meaning  
Compressor 2 CT sensor (CT2) disconnected or short-circuit; Compressor 3 CT sensor (CT3)  
disconnected or short-circuit.  
Alarm conditions  
Probable cause  
The current is still 1.5 A or less when 2 seconds or longer has elapsed after output from that  
compressor started.  
* No current is detected even though the compressor is operating.  
(1) CT circuit failure (including cut wiring, etc.)  
(2) Disconnected CT circuit connector  
(3) Missing phase where CT circuit is connected  
(4) This CT circuit is connected to the connector of other CT circuit.  
(5) PCB failure  
Check  
(1) CT circuit failure, PCB failure  
Trouble: • Current value during compressor operation is below the threshold value.  
• Check that the connector is not disconnected.  
Check:  
• Check the continuity of the CT circuit.  
• Install a normal CT in place of this CTand check. If current is detected, then the  
PCB can be judged OK.  
CT circuit failure  
• Check that current is flowing in the phase where the CT circuit is connected.  
Check voltage and current.  
(2) Crossed wiring or installation error  
Trouble: When the compressor is stopped, the current value at the other compressor is high.  
When this type of condition occurs, seizing-detection control takes priority.  
3
Correction  
(1) Replace the CT circuit.  
(2) Replace the outdoor unit PCB.  
(3) Correct the problem.  
(1) The connector was not inserted after the PCB was replaced.  
Use a normal CT as a tool to determine whether the trouble is a PCB failure or CT failure.  
Example  
Notes  
H05, H15, H25 Alarm  
Alarm code  
H05, H15, H25  
Alarm meaning  
Compressor 1 discharge temperature sensor (DISCH1) disconnected; Compressor 2 discharge  
temperature sensor (DISCH2) disconnected; Compressor 3 discharge temperature sensor  
(DISCH3) disconnected  
Alarm conditions  
• This alarm occurs when the discharge sensor temperature detector is not inserted into the tube’s  
sensor holder, or when the sensor itself has suffered some kind of malfunction other than a cut  
wire.  
• When outdoor air temperature is 32°F (0°C) or higher:  
Alarm occurs if the temperature detected by the discharge sensor has changed by less than  
4 deg. when the compressor has operated for 10 minutes immediately after start.  
• When outdoor air temperature is below 32°F (0°C):  
Alarm occurs if the temperature detected by the discharge sensor has changed by less than  
4 deg. when the compressor has operated for 30 minutes immediately after start.  
(1) Discharge sensor temperature detector is not inserted into the tube’s sensor holder.  
(2) Discharge sensor itself has suffered some kind of malfunction other than a cut wire.  
(1) Check that the discharge temperature sensor is inserted into the sensor holder.  
(2) Check that sufficient heat-conducting putty is applied.  
(3) Remove the discharge sensor from the sensor holder and expose the sensor to the outside  
air for approximately 5 minutes. Check that the temperature detected by the sensor changes  
to match the outside air temperature. (However the sensor cannot detect temperatures at or  
below 32°F (0°C).)  
(1) Install the sensor into the holder, and apply sufficient heat-conducting putty.  
(2) If the sensor is malfunctioning, replace it.  
Probable cause  
Check  
Correction  
Example  
Notes  
The discharge temperature sensor is generally a sensor intended for accurate detection of high  
temperatures. Therefore, it will not accurately detect the temperature if the temperature at the  
measurement point is 68°F (20°C) or below.  
3-15  
Trouble Diagnosis  
3. W-2WAY ECO-i Alarm Codes  
H31 Alarm  
Alarm code  
H31  
Alarm meaning  
Alarm conditions  
HIC trouble alarm  
This alarm occurs when the microcomputer identifies a trouble signal (indicating abnormal HIC  
temperature or other trouble) from the HIC.  
The HIC judges the current and temperature, and outputs the trouble signal. In general this  
indicates trouble with the HIC itself.  
Probable cause  
Check  
Overcurrent in HIC circuit, and resultant abnormal heating, caused by HIC failure  
Check the power wiring and connector wiring. If the wiring and connectors are normal, use a  
tester to measure the resistance between the compressor HIC power (HIC+) and ground (HIC–).  
If there is a short circuit, there is an HIC malfunction.  
-
+
HIC  
HIC  
3
HIC PCB  
Correction  
Example  
Notes  
If an HIC failure is found, replace the PCB.  
Turn OFF the power, and check the continuity of HIC+ and HIC– on the HIC PCB.  
L04 Alarm  
Alarm code  
L04  
Alarm meaning  
Alarm conditions  
Outdoor unit refrigerant system address duplication  
Communication by inter-unit control wiring was received that contained the same address as that  
unit 5 times or more within 3 minutes.  
Incorrect outdoor system address settings  
Check the system address settings again.  
Probable cause  
Check  
Correction  
Example  
Notes  
Correct the system address settings.  
Recovery from this alarm occurs automatically (when communication that contains the same  
address as that unit is not received for 3 minutes after detection).  
L05 Alarm  
Alarm code  
L05  
Alarm meaning  
Alarm conditions  
Probable cause  
Check  
Duplicated indoor unit priority (alarm at priority indoor units)  
Multiple indoor units set as the priority unit were detected.  
More than one indoor unit is set as the priority unit.  
From the wired remote controller, use the indoor unit EEPROM simple settings mode and  
check whether or not the value for item code 04 is “0001.”  
Correction  
If the value of indoor unit EEPROM item code 04 is incorrect, set the correct value from the  
wired remote controller.  
Example  
Notes  
This alarm is displayed at the indoor units which are set as the priority unit. At indoor units which  
are not set as the priority unit, alarm L06 is displayed.  
3-16  
Trouble Diagnosis  
3. W-2WAY ECO-i Alarm Codes  
L06 Alarm  
Alarm code  
L06  
Alarm meaning  
Alarm conditions  
Probable cause  
Duplicated indoor unit priority (alarm at non-priority indoor units and outdoor unit)  
Multiple indoor units set as the priority unit were detected in the system.  
More than one indoor unit is set as the priority unit in the system.  
Check  
Find the indoor units in the system where alarm L05 has occurred.  
Refer to the description of alarm L05.  
Correction  
Example  
Notes  
Alarm L06 occurs as a result of alarm L05. Therefore, correcting the duplicated priority  
settings will also correct alarm L06.  
L10 Alarm  
Alarm code  
L10  
Alarm meaning  
Alarm conditions  
Probable cause  
Check  
Outdoor unit capacity not set  
The outdoor unit capacity has not been set, or the setting is not allowed by the system.  
This alarm occurs because the capacity has not been set.  
Connect the outdoor unit maintenance remote controller. On the outdoor unit EEPROM detailed  
setting mode screen, check the value for the outdoor unit capacity (item code 81). Check that it is  
not set to “0” or to a capacity that is not allowed.  
3
Correction  
If item code 81 is incorrect, use the outdoor unit maintenance remote controller and set it  
correctly.  
* After changing the setting, be sure to reset both the indoor and outdoor power.  
Example  
Notes  
The outdoor unit maintenance remote controller is required in order to set the capacity in the  
outdoor unit EEPROM.  
L17 Alarm  
Alarm code  
L17  
Alarm meaning  
Alarm conditions  
Probable cause  
Outdoor unit model mismatch  
This alarm occurs when a unit other than a R410A refrigerant model is connected.  
(1) A unit that uses R407C refrigerant, or a R22 model unit, was connected by mistake.  
(2) The connected unit is correct, however the refrigerant type setting in the outdoor unit  
EEPROM (item code 80) is incorrect.  
(1) Check the refrigerant type at the connected unit.  
(2) Use the outdoor unit maintenance remote controller and check the item code 80 refrigerant  
type. If the setting is incorrect, change it to R410A.  
Check  
Correction  
Example  
Notes  
The outdoor unit maintenance remote controller is required in order to set the refrigerant type in  
the outdoor unit EEPROM.  
L18 alarm  
Alarm code  
Alarm meaning  
Alarm conditions  
L18  
4-way valve operation failure  
During heating operation (Comp. ON), the highest detected temperature at an outdoor unit heat  
exchanger (EXG 1, EXG 2, EXL1, or EXL2) was 68°F (20°C) or more above the outdoor air  
temperature (Air Temp.) continuously for 5 minutes or longer, or the detected suction temperature  
(SCT) was 68°F (20°C) or more above the outdoor air temperature continuously for 5 minutes or longer.  
Probable cause  
Check  
(1) The 4-way valve connector (20S CN060) has become disconnected from the control PCB.  
(2) The 4-way valve circuit is locked (mal functioning).  
(1) Check the 4-way valve connector (20S CN060).  
(2) If the connector is normal, check the 4-way valve wiring and the PCB circuit.  
If the connector is normal, correct or replace the problem locations.  
Correction  
Example  
Notes  
3-17  
Trouble Diagnosis  
3. W-2WAY ECO-i Alarm Codes  
P03, P17, P18 Alarm  
Alarm code  
P03, P17, P18  
Alarm meaning  
Compressor 1 discharge temperature trouble; Compressor 2 discharge temperature trouble;  
Compressor 3 discharge temperature trouble  
Alarm conditions  
Probable cause  
Pre-trip stop at 222°F (106°C) or higher  
This alarm occurs when the pre-trip counter reaches 4. However the counter is reset when the  
compressor has operated continuously for a certain length of time.  
(1)  
(2)  
(3)  
Operation failure of mechanical valve 3  
Clogging of mechanical valve 3  
Insufficient amount of refrigerant (including trouble resulting from an insufficient initial charge  
and from gas leakage)  
Blocking of low-pressure parts caused by intrusion of foreign objects (moisture, scale, etc.)  
(4)  
(5) Crossing (tubing or PCB connectors) with the other compressor thermistor  
(6) Expansion valve operation failure  
(7) Accumulation of refrigerant at stopped outdoor units  
(8) Compressor discharge sensor failure  
(9) PCB failure (A/D conversion failure)  
Check  
Operation failure of mechanical valve 3  
(1)  
Trouble: The compressor discharge temperature does not decrease even when  
mechanical valve 3 is opened to 480 pulses.  
Check:  
Check whether or not mechanical valve 3 makes a grinding sound when the power is reset.  
(2) Clogging of mechanical valve 3  
Trouble: The compressor discharge temperature does not decrease even when  
mechanical valve 3 is ON.  
Check: If mechanical valve 3 is open to 480 pulses, then check whether or not the  
secondary side of the valve is cold.  
3
(3) Insufficient refrigerant  
Trouble:  
Liquid effectiveness is poor.  
Check: Check whether or not the superheating temperature is declining if the evaporator  
mechanical valve is opened to 300 pulses or more (after checking for  
foreign object intrusion).  
(4) Foreign object intrusion  
Trouble: Liquid valve effectiveness is poor.  
Check: Check that there is no difference in the condensation or frost conditions between the  
strainer primary-side and secondary-side tubing.  
(5)  
(6)  
Crossed thermistor  
Trouble: The discharge temperature of the other compressor is high although only this  
compressor is operating.  
When the liquid valve turns ON, the discharge temperature of the other compressor  
decreases.  
Accumulation of refrigerant in stopped outdoor units  
Trouble:  
• System is OK when all outdoor units are operating, however symptoms of  
insufficient gas occur when a certain outdoor unit is stopped.  
Condensation or frost is visible up to the top of the accumulator of the stopped outdoor unit.  
• After an outdoor unit stops, there is the sound of refrigerant flowing into an outdoor  
unit that was stopped for a long time.  
• When an outdoor unit starts after being stopped for a long time, the start is  
accompanied by much vibration.  
Check: • In some cases, leakage may be occurring from the evaporator mechanical valve  
or mechanical valve 3 at a stopped outdoor unit.  
(7) Sensor failure  
Check: • This alarm is likely to occur when wiring is partially cut. (It is difficult to identify, even  
when continuity is checked.) The detected discharge temperature is high.  
• Although such conditions rarely occur, a P02 alarm is likely if the detected  
discharge temperature is low.  
Replace the sensor with another discharge sensor and compare the temperature conditions.  
Correction  
(1) Replace the sensor.  
(2) Replace the outdoor unit PCB.  
(3) Correct the problem locations.  
All of the probable causes  
Operates continuously for a set length of time.  
Indicates 2.5 minutes or longer for an inverter compressor (compressor 1) and 30 seconds or  
longer for a constant-speed compressor (compressor 2 and 3).  
Example  
Notes  
3-18  
Trouble Diagnosis  
3. W-2WAY ECO-i Alarm Codes  
P04 Alarm  
Alarm code  
P04  
Alarm meaning  
Alarm conditions  
High-pressure switch activated.  
When the electrical circuit of the high-pressure switch is activated, then depending on the  
pressure, the terminals may be short-circuited. If the pressure is 464 psi or higher, the terminals  
will be short-circuited. When they have been short-circuited, they remain short-circuited until the  
pressure decreases to 360 psi.  
Probable cause  
(1) The check valve installed on the compressor discharge-side tubing has malfunctioned.  
(2) The service valve is closed.  
(3) The outdoor unit heat exchanger became clogged during cooling operation.  
(4) An air short circuit occurred in the outdoor unit during cooling operation.  
(5) The outdoor unit fan malfunctioned during cooling operation.  
(6) The indoor unit air filter became clogged during heating operation.  
(7) An air short circuit occurred in the indoor unit during heating operation.  
(8) The indoor fan failed during heating operation.  
(9) The refrigerant circuit has become clogged.  
(10) The mechanical valve failed.  
(11) The solenoid valve kit failed.  
(12) Refrigerant overcharge has occurred.  
(13) The high-pressure switch failed.  
Check  
(1) Check that the high-pressure switch connector is connected securely.  
(2) If it is connected securely, then connect a pressure gauge to the high-pressure outlet and  
monitor the high pressure while operating the system. Check the pressure at the time when  
the high-pressure switch operates. If the pressure is less than 551 psi then it is possible  
that the check valve has failed.  
3
The following concern cases in which the pressure is actually too high.  
(3) If the operation is cooling operation, check that the outdoor heat exchanger has not become  
clogged or blocked. Remove any objects that impede the flow of air.  
(4) If the operation is cooling operation, check that an air short circuit has not occurred at the  
outdoor unit. The status is OK as long as the temperature in the area around the outdoor  
unit does not become abnormally high during operation.  
(5) If the operation is cooling operation, check that the outdoor unit fan has not failed. Check that  
the screws which fasten the fan have not become loose. Check that the fan connector has  
been securely inserted into the outdoor unit PCB.  
(6) If the operation is heating operation, check that the indoor unit air filter has not become  
clogged. If it is clogged, clean it.  
(7) If the operation is heating operation, check that an air short circuit has not occurred at the  
indoor unit. The status is OK as long as the temperature in the area around the indoor unit  
air intake does not become abnormally high during operation.  
(8) If the operation is heating operation, check that the indoor unit fan has not failed.  
(9) Check that the refrigerant circuit has not become clogged. Check that all the service valves  
are fully opened. Check that the welded connections are not clogged.  
(10) Check that the mechanical valves have not failed. Check whether or not mechanical valve 3  
makes a grinding sound when the power is reset. At the indoor unit, the mechanical valve is  
located at a position where it is difficult to hear, so this check should be made electronically.  
Check that 4 V is being output to the mechanical valve connector pin on the PCB. Also check  
that the mechanical valve coil winding resistance is several tens of Ohms.  
(11) Check that the solenoid valve kit has not failed. Removing the coil when the valve is ON should  
produce a click sound. Removing the coil when the valve is OFF should produce no sound.  
(12) Check that refrigerant overcharge has not occurred. If the sub-cool temperature at the  
condenser discharge is 59°F (15°C) or higher, overcharge has occurred.  
Correction  
Example  
Notes  
Replace the failed part and correct the amount of refrigerant charge.  
3-19  
Trouble Diagnosis  
3. W-2WAY ECO-i Alarm Codes  
P05 Alarm  
Alarm code  
P05  
Alarm meaning  
Alarm conditions  
Probable cause  
Check  
Reverse phase (or missing phase) detected  
This alarm occurs when a reverse phase or missing phase is detected in the L1-L2-L3 phases.  
Reverse phase or missing phase in the L1-L2-L3 phases  
Check the wiring at the power terminal plate.  
Correction  
Example  
Notes  
Switch the phases and reinsert. Check if the result is OK.  
P16 Alarm  
Alarm code  
P16  
Alarm meaning  
Alarm conditions  
Compressor 1 (INV) overcurrent alarm  
This alarm occurs when current trouble or current detection trouble occurs at an inverter frequency  
of less than 80 Hz after start (when trouble judgment current is detected 13.5 A or higher in the  
primary or secondary current).  
Probable cause  
There is a strong possibility of a compressor failure.  
An alarm occurs for current detection trouble when it is judged that no current is flowing after start  
(DCCT is damaged). In this case, the cause is a DCCT failure. The cause may be the effects of  
noise in some cases.  
Check  
Check the power wiring and connector wiring.  
Correction  
Example  
Notes  
It is possible to resolve this trouble by limiting the maximum frequency.  
3
3-20  
Trouble Diagnosis  
3. W-2WAY ECO-i Alarm Codes  
P22 Alarm  
Alarm code  
P22  
Alarm meaning  
Alarm conditions  
Probable cause  
Check  
Fan motor trouble  
Fan motor start failure, fan motor Hall IC input failure  
Possible causes are a Hall IC input circuit failure and a fan HIC failure.  
Check the fan motor wiring, the Hall IC wiring, and the connector connections. If the wiring and  
connectors are normal, then check that the capacitor of the Hall IC input circuit is securely  
soldered onto the PCB. Also use a tester and measure the resistance between fan HIC power  
(HIC+) and ground (HIC–). If there is a short circuit, there is an HIC malfunction.  
(-)  
(+)  
3
Correction  
If the fan does not start, the below corrections may be effective.  
(1) If there is a fan HIC failure or circuit failure, replace the PCB.  
(2) If the fan motor is locked, replace the fan motor.  
Example  
Notes  
Turn OFF the power, and check the continuity of “+” and “–” on the fan circuit PCB.  
P26 Alarm  
Alarm code  
P26  
Alarm meaning  
Alarm conditions  
Inverter compressor high-frequency overcurrent alarm  
This alarm occurs when current trouble or current detection trouble occurs at an inverter frequency  
of 80 Hz or higher after start (when trouble judgment current is detected 13.5 A higher in the  
primary or secondary current).  
The detection methods are the same as for P16. However the fact that operation up to high  
frequencies is possible does not necessarily mean that a compressor failure is the cause of the  
trouble. Start the compressor several times. If alarm P26 occurs every time and alarm P16 does  
not occur at all, then the possibility of a compressor failure is low. It is also possible that the  
cause may be the effects of noise.  
Probable cause  
Check  
Check the power wiring and connector wiring.  
Correction  
Example  
Notes  
It is possible to resolve this trouble by limiting the maximum frequency.  
P29 Alarm  
Alarm code  
P29  
Alarm meaning  
Alarm conditions  
Inverter compressor missing phase or lock alarm  
This alarm may occur at start, and occurs when missing phase or lock is detected, and when a  
DCCT failure occurs.  
Generally this alarm occurs when the refrigerant pressure balance is uneven at start, or when  
inverter compressor lock occurs, there is a missing phase in the inverter compressor wiring, or a  
DCCT failure occurs. This can be judged to be starting trouble which is not caused by HIC.  
Check the power wiring and connector wiring.  
DCCT failure (replace PCB) or compressor failure  
Use a tester to measure the voltage between the DCCT output terminal on the rear of the PCB  
and the ground. If the voltage is not within 2 – 3 V, then the DCCT has malfunctioned.  
Probable cause  
Check  
Correction  
Example  
Notes  
3-21  
Trouble Diagnosis  
4. Blinking  
(Inspection) Display on the Remote Controller  
Currently the blinking inspection display can be displayed only on the wired remote  
controller and system remote controller.  
CAUTION  
Blinking  
inspection display (1) (Automatic backup)  
Alarm code  
(Blinking  
inspection display)  
Alarm meaning  
Automatic backup is in progress. A/C units can be operated.  
Status: The compressor at one of the outdoor units where the outdoor unit fan is running  
should be operating.  
* Blinking inspection display also occurs when seizing of the compressor magnet SW is  
detected. Because this may also be the case, refer to “Blinking inspection display (2)  
(compressor magnet SW seizing detection).”  
Alarm conditions  
Probable cause  
When alarm P16, P22, P26, P29, Hx1, Hx2, or H31 has occurred, correcting the control device  
(remote controller, etc.) input engages this mode.  
Because alarm P16, P22, P26, P29, Hx1, Hx2, or H31 has occurred, check the alarm history  
then refer to the corresponding items.  
Correction  
Recovery  
Follow the instructions in the corresponding items to correct the trouble.  
After repairing the malfunctioning locations, reset the power for the system (all outdoor units).  
Caution: Automatic backup mode will not be canceled until the power is reset.  
Automatic backup mode is not engaged in cases of alarms other than those listed above.  
Reasons: There is no need for automatic backup if recovery is possible by correcting the  
remote controller input.  
Notes  
With alarms for which automatic recovery is possible (such as sensor alarms), the  
presence of electrical noise may result in a new alarm. However, it is believed that  
this occurs for a comparatively short time only. In these cases, a mode (automatic  
backup mode) that limits operation may be engaged.  
Control is not possible when a communications system alarm has occurred.  
Automatic backup mode is not engaged in order to avoid causing secondary  
damage.  
3
3-22  
Trouble Diagnosis  
4. Blinking  
(Inspection) Display on the Remote Controller  
Blinking inspection display (2) (compressor magnet SW seizing detection)  
(Blinking  
inspection display)  
Alarm code  
Alarm meaning  
Compressor magnet SW seizing detected  
Status: The compressor and outdoor unit fan motor continue to run even though all indoor units  
within that refrigerant tubing system are stopped.  
Because the fan is running only at the outdoor unit where seizing was detected, check  
the corresponding outdoor unit.  
* The fan may also run on its own when fan cracking prevention control is in effect or  
when snowfall sensor input is present. Therefore monitor for approximately 10  
minutes if the outdoor unit fans are operating at multiple units.  
Alarm conditions  
Current is detected in the CT circuit when the compressor is stopped.  
(1) This control is not engaged for the first 30 seconds after the compressor turns ON  
OFF.  
(2) For 1 minute following the first 30 seconds after the compressor turned ON  
threshold for the detected current is 10 A or more continuing for 2 seconds.  
(3) All times other than the above:  
OFF, the  
If the low-pressure SW has not activated, the threshold for the detected current is 7A or  
more continuing for 5 seconds.  
If the low-pressure switch has activated, the threshold for the detected current is 7 A or  
more continuing for 2 seconds.  
Probable cause  
(1) Magnet SW malfunction  
The magnet SW has seized, and the compressor is continuing to run.  
Even when the power is turned OFF, the primary side and secondary side contacts  
remain together.  
3
The conditions of magnet SW operation are poor (difficult to open).  
When a magnet SW is used in a DC circuit, it may be difficult for the SW to open at  
times. In an AC circuit the magnet SW should open instantaneously as long as the  
current is within the allowable range. However, this kind of trouble can occur if  
excessive current flows, and may prevent the SW from opening.  
(2) CT circuit failure or PCB failure (A/D failure)  
CT circuit contact failure  
Check that the connector is not partially disconnected.  
Wiggle the connector to check the connection.*  
* These symptoms will not occur if the connector is completely disconnected or the  
wire is cut. In these cases alarm Hx3 occurs.  
Current of 7A or higher was detected although the compressor was stopped, or a  
higher current was detected at occasional intervals.  
The compressor continues to operate at a time when the outdoor unit should be  
stopped (such as when all indoor units are stopped).  
Check whether or not 200 V is output from the PCB to the magnet SW. If the voltage  
is output, there is a PCB failure.  
(3) Installation error  
CT1 connector is connected to the compressor 2 side  
CT1 circuit is connected to the compressor 2 side  
CT2 connector is connected to the compressor 1 side  
CT2 circuit is connected to the compressor 1 side  
Correction  
Notes  
(1) Replace the CT circuit.  
(2) Replace the magnet SW.  
(3) Replace the PCB.  
If the above probable causes are not the cause of the alarm, it is possible that in rare cases  
the alarm may be caused by the effects of noise. See notes.  
3-23  
PCB and Functions  
Contents  
4. PCB AND FUNCTIONS  
1. Outdoor Unit Control PCB .................................................................................................4-2  
1. Outdoor Unit Control PCB CR-CHDX14053.....................................................................4-2  
2. Functions (for CR-CHDX14053).......................................................................................4-3  
2. Indoor Unit Control PCB ....................................................................................................4-6  
1. Indoor Unit Control PCB Switches and Functions............................................................4-6  
1. For AC Fan Motor (CR-UXRP71B-B)...........................................................................4-7  
2. For DC Fan Motor (SXRP56B-B) .................................................................................4-7  
3. CR1 (for CR-KR74GXH56A/KHX0752~KHX1852) (Wall Mounted).............................4-8  
4. CR1 (for CR-KR254GXH56A/KHX2452) (Wall Mounted) ............................................4-9  
5. CR2 (for POW-KR74GXH56/KHX0752~KHX2452) (Wall Mounted)..........................4-10  
6. Explanation of Functions (CR-KXRP56AN, CR-KXRP80AN, POW-KRP50A)...........4-11  
4
4-1  
PCB and Functions  
1. Outdoor Unit Control PCB  
1. Outdoor Unit Control PCB CR-CHDX14053  
Alarm LED  
(LED1,2)  
A.ADD(CN100)pin  
OAC(CN105)pin  
MODE(CN101)pin  
AP(CN102)pin  
STOP(CN104)pin  
CHK(CN023)pin  
RUN(CN103)pin  
TEST(CN022)pin  
Terminal plug  
S002  
S004  
S006  
S010  
S007  
EMG(CN002)plug  
EEPROM  
memory IC  
(IC018)  
Control circuit fuse(F003)  
OC(CN001)plug  
RC(CN006)plug  
S005  
S003  
4
RC1(CN106)plug  
Low-pressure sensor  
Comp. discharge 3 temp.  
Outdoor air temp.  
Comp. discharge 2 temp.  
Gas temp. sensor  
at heat exchanger 1,2  
Comp. discharge 1 temp.  
CT2,CT3  
High-pressure sensor  
LIquid temp. sensor  
at heat exchanger 1,2  
Power LED  
(D53)  
CTL1,CTL2  
Suction temp.  
Oil detection sensor  
HIC2  
HIC1  
HIC3  
(F04)  
4-2  
PCB and Functions  
1. Outdoor Unit Control PCB  
2. Functions (for CR-CHDX14053)  
Automatic address setting  
(CN100)  
2P plug (white): Automatic address setting pin  
• Short-circuit this pin for 1 second or longer to automatically set the addresses at the indoor  
units that are connected to that outdoor unit and are within the same system.  
• The system address is "1" at the time of shipment. Automatic address setting is necessary  
even for communications lines in a single system where the inter-unit control wiring does  
not cross to any other systems.  
• While automatic address setting is in progress, the 2 LEDs (LED1, 2: red) on the outdoor  
unit control PCB blink alternately. (Short-circuiting this pin while automatic address setting is  
in progress will stop the automatic address setting operation.)  
S002  
Rotary switch (10 positions, black): Outdoor system address setting switch  
• The setting is "1" at the time of shipment. It is not necessary to change the setting if wiring  
is connected only to an outdoor unit and indoor units in a single system and the inter-unit  
control wiring does not cross multiple systems.  
• If wiring links the inter-unit control wiring for multiple systems to the same communications  
lines, then a different address must be set for each refrigerant tubing system.  
• If wiring links multiple systems, a maximum of 30 systems (up to 64 indoor units) can be  
connected. This setting can be set up to "39," however control will be for 30 systems even  
if the setting is set to higher than 30. An alarm will be displayed if system addresses are  
duplicated. (For details, refer to Table 7-1.)  
4
S003  
DIP switch (2P, blue): Switches for setting system address 10s digit and 20s digit  
• If 10 systems or more are set, the setting is made by a combination of this DIP switch and  
S002.  
• If 10 - 19 systems are set, set switch 1 (10s digit) to ON.  
• If 20 - 29 systems are set, set switch 2 (20s digit) to ON, and set switch 1 (10s digit) to OFF.  
• If 30 systems are set, set both switch 1 (10s digit) and switch 2 (20s digit) to ON. (For  
details concerning S002 and S003, refer to Table 7-1.)  
S004  
S005  
Rotary switch (10 positions, red): Switch for setting the number of connected indoor units. In  
order to allow the outdoor unit to manage indoor units in the same refrigerant system, set the  
number of connected indoor units. (For details, refer to Table 7-2.)  
DIP switch (3P, blue): Switches for setting the 10s, 20s, and 30s digit for the number of  
connected indoor units  
• If 10 systems or more are set, the setting is made by a combination of this DIP switch and  
S004.  
• If 10 - 19 systems are set, set only switch 1 (10s digit) to ON.  
• If 20 - 29 systems are set, set switch 2 (20s digit) to ON, and set switch 1 (10s digit) to OFF.  
• If 30 - 39 systems are set, set only switch 3 (30s digit) to ON. (For details concerning S004  
and S005, refer to Table 7-2.)  
S006  
DIP switch (3P, blue): Switch for setting the number of outdoor units  
Turn the switches ON according to the number of outdoor units (1 - 4). (For details, refer to  
Table 7-3.)  
S007  
S010  
DIP switch (3P, blue): Unit No. setting switch  
• The setting is "1" at the time of shipment. (For details, refer to Table 7-4.)  
DIP switch (3P, blue): Backup operation switch  
If an INV compressor has malfunctioned, turn CT1 ON and Back Up SW ON to operate the  
outdoor unit using only the constant-speed compressor.  
If a constant-speed compressor has malfunctioned, turn CT2 ON and Back Up SW ON to  
operate the outdoor unit using only the INV compressor. (Disconnect the wiring from the  
constant-speed compressor.)  
4-3  
PCB and Functions  
1. Outdoor Unit Control PCB  
Terminal plug  
3P plug (black): For communications circuit impedance matching  
• A connecting socket (3P, black) is attached to the terminal plug at the time of shipment from  
the factory.  
• In the case of link wiring which combines the inter-unit control wiring for multiple systems  
into a single communications circuit, leave the connecting socket in place at only one of the  
outdoor units, and move the socket from the "SHORT" side to the "OPEN" side at all other  
outdoor units. If multiple connecting sockets are left in place, communications trouble will  
occur.  
LED1, 2  
LED (red × 2)  
D72, D75  
• LED 1 and 2 blink alternately while automatic address setting is in progress.  
• Display the alarm contents for alarms which were detected by the outdoor unit.  
Power LED  
D53  
LED (red): Power indicator  
Indicates the DC 5V power on the outdoor unit control PCB.  
Run  
2P plug (white): Start pin  
(CN103)  
Short-circuit this pin and apply a pulse signal to start all indoor units in that refrigerant system.  
4
Stop  
(CN104)  
2P plug (white): Stop pin  
Short-circuit this pin and apply a pulse signal to stop all indoor units in that refrigerant system.  
AP  
(CN102)  
2P plug (white): Vacuuming pin  
To perform vacuuming of the outdoor unit, short-circuit this pin and then turn the power ON.  
All solenoid valves turn ON and vacuuming begins smoothly. (Do not perform automatic  
address setting at this time.)  
• Release the short-circuit to return the unit to normal status.  
Mode  
(CN101)  
2P plug (white): Indoor unit Heating/Cooling mode change pin  
• When operating the compressors to perform automatic address setting, operation in Heating  
mode can be normally used. However, short-circuiting this pin performs operation in Cooling  
mode. (Static signal)  
• Short-circuiting this pin during ordinary operation changes the mode from Cooling to  
Heating (if the current mode is Cooling) or from Heating to Cooling (if the current mode is  
Heating).  
Test  
(CN022)  
2P plug (white)  
• This pin is used to test the PCB at the factory.  
• When the power is turned ON after this pin has been short-circuited, all output signals will  
be output in sequence. (Sequential output does not occur if this pin is short-circuited when  
the power is already ON.) Releasing this pin returns the unit to normal control.  
4-4  
PCB and Functions  
1. Outdoor Unit Control PCB  
Table 1. Setting the System Address [S002: Rotary switch (black), S003: 2P DIP (blue)]  
S003 setting  
Outdoor system address  
S002 setting  
1P (10s digit)  
2P (20s digit)  
1 refrigerant  
system only  
1
0
OFF  
OFF  
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
0
1
2
3
4
5
6
7
8
9
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
Link wiring  
4
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
0
1
2
3
4
5
6
7
8
9
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
30  
0
ON  
ON  
Table 2. Setting the Number of Indoor Units  
[S004: Rotary switch (red), S005: 2P DIP (blue)]  
Table 3. Setting the Number of Outdoor Units  
[S006: DIP switch (blue)]  
S005 Setting  
S006 Setting  
Number of  
Indoor Units  
Number of  
Indoor Units  
S004 Setting  
1
ON  
OFF  
ON  
OFF  
2
OFF  
ON  
ON  
OFF  
3
1
2
3
1
2
3
4
OFF  
OFF  
OFF  
ON  
1
2
3
1
2
3
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
9
10  
11  
9
0
1
OFF  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
Table 4. Setting the Outdoor Unit address  
S007 Setting  
Outdoor Unit  
Address  
1
ON  
OFF  
ON  
OFF  
2
OFF  
ON  
ON  
OFF  
3
19  
20  
21  
9
0
1
ON  
OFF  
OFF  
OFF  
ON  
ON  
OFF  
OFF  
OFF  
1
2
3
4
OFF  
OFF  
OFF  
ON  
29  
30  
31  
9
0
1
OFF  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
ON  
ON  
39  
40  
9
0
OFF  
ON  
OFF  
ON  
ON  
ON  
4-5  
PCB and Functions  
2. Indoor Unit Control PCB  
1. Indoor Unit Control PCB Switches and Functions  
Indoor unit control PCB  
T10:  
6P plug (yellow): Used for remote control. (Refer to the remote control section.)  
(CN61)  
Control items: (1) Start/stop input  
(3) Start signal output  
(2) Remote controller prohibit input  
(4) Alarm signal output  
EXCT:  
2P plug (red): Can be used for demand control. When input is present, forces the unit to operate with the thermostat  
(CN73)  
OFF.  
DISP:  
2P plug (white): Short-circuiting this plug allows the unit to be operated by the remote controller, even if it is not  
(CN72)  
connected to an outdoor unit.  
(In this case, alarm "E04," which indicates trouble in the serial communication between the indoor and outdoor unit,  
does not occur.)  
CHK:  
2P plug (white): Test pin. Short-circuiting this pin allows the indoor FM (H fan speed), drain pump, flap motor (F1  
position), and electronic expansion valve full-open position to be checked.  
However this function turns OFF if the indoor unit protection mechanism is activated. The unit can be operated even  
if the remote controller and outdoor unit are not connected. However even if the remote controller cannot is con-  
nected, it cannot be used to operate the unit. This function can be used for short-term tests.  
JP1:  
(J01)  
Jumper wire: Allows selection of the T10 terminal start/stop signal. (Refer to the remote control section.) Status at  
shipment: Pulse signal  
Jumper wire cut: Static signal (continuous signal)  
FAN DRIVE 2P plug (white): This terminal sends a signal to the ventilation fan when the FAN button on the wired remote con-  
troller is used to operate a commercially-available ventilation fan. (Refer to the remote control section.)  
Use a ventilation fan which can accept no-voltage A contact as the external input signal.  
4
FILTER:  
(CN70)  
2P (white): This terminal is used to connect contact input from the differential pressure switch which detects filter  
clogging. When the contacts turn ON, "FILTER" is displayed on the wired remote controller.  
Power LED: LED (red): Illuminates when power is supplied. Blinks when there is a failure in the EEPROM (IC10: nonvolatile  
memory).  
EEPROM: Nonvolatile memory: Memory which stores the unit type data and other information. When the PCB is replaced,  
(IC10)  
remove the EEPROM from the old PCB and install it onto the new PCB. If an IC failure occurs, replace with a new IC  
which was provided with the service PCB, and set the necessary information from the wired remote controller. (For  
the procedure, refer to the servicing technical materials.)  
GRL:  
(CN20)  
For AC fan motor (CR-UXRP71B-B: 3P (yellow))  
For DC fan motor (CR-SXRP56B-B: 5P (blue))  
The indoor unit power terminal plate will be a 7P type or may be a 5P type. (Refer to the figure at below.) The basic wiring dia-  
gram shows the 7P-type terminal plate. Therefore the terminal plate may differ from the illustrations.  
z
5P-type terminal plate  
7P-type terminal plate  
L1 L2  
U1 U2  
R
S
T
U1 U2  
1
2
Power  
supply  
Remote  
control line  
Power Inter-unit Remote  
supply control line control line  
4-6  
PCB and Functions  
2. Indoor Unit Control PCB  
1. For AC Fan Motor (CR-UXRP71B-B)  
EEPROM (IC010)  
EMG (CN044)  
OC (CN040)  
VARISTOR (VA100)  
4
JP001  
GRL (CN020)  
OPTION (CN060)  
EXCT (CN073)  
DISP (CN072)  
CHK (CN071)  
POWER LED (D002)  
FILTER (CN070)  
FAN DRIVE (CN032)  
T10 (CN061)  
2. For DC Fan Motor (CR-SXRP56B-B)  
POWER LED (D002)  
EEPROM (IC010)  
GRL  
(CN020)  
OPTION  
(CN060)  
FILTER  
(CN070)  
DISP  
(CN063)  
JP001  
VARISTOR  
(VA100)  
OC  
(CN040)  
FAN DRIVE  
(CN032)  
T10  
CHK  
(CN062)  
EXCT  
(CN073)  
EMG  
(CN044)  
(CN061)  
4-7  
PCB and Functions  
2. Indoor Unit Control PCB  
3. CR1 (for CR-KR74GXH56A/KHX0752~KHX1852) (Wall-Mounted)  
If the fuse (F002) has  
blown, determine the  
cause and correct it.  
Then change the socket  
from the OC plug to the  
EMG plug.  
CHK (test) pin  
DISP pin  
TRANS-S plug  
EMG plug  
OC plug  
Control circuit fuse  
(F002)  
4
Power LED  
(LD002)  
Microcomputer  
FAN DRIVE plug  
Nonvolatile memory IC  
Indoor heat exchanger  
(E2) sensor  
Indoor heat exchanger  
(E1) sensor  
T10 plug  
Room temperature  
(TA) sensor  
JP001  
OPTION plug  
EXCT plug  
4-8  
PCB and Functions  
2. Indoor Unit Control PCB  
4. CR1 (for CR-KR254GXH56A/KHX2452) (Wall-Mounted)  
If the fuse (F002) has  
blown, determine the  
cause and correct it.  
Then change the socket  
from the OC plug to the  
EMG plug.  
CHK (test) pin  
DISP pin  
TRANS-S plug  
Control circuit fuse  
(F002)  
EMG plug  
OC plug  
RC plug  
4
FAN DRIVE plug  
OPTION plug  
T10 plug  
Microcomputer  
JP001  
Nonvolatile memory IC  
Indoor heat exchanger  
(E2) sensor  
Power LED  
(LD002)  
EXCT plug  
Indoor heat exchanger  
(E1) sensor  
Room temperature  
(TA) sensor  
4-9  
PCB and Functions  
2. Indoor Unit Control PCB  
5. CR2 (for POW-KR74GXH56/KHX0752~KHX2452) (Wall-Mounted)  
Control circuit fuse  
(F201)  
T20 plug  
TRANS-S plug  
4
OP1 plug  
4-10  
PCB and Functions  
2. Indoor Unit Control PCB  
6. Explanation of Functions (CR-KXRP56AN, CR-KXRP80AN, POW-KRP50A)  
T10  
6P flag (yellow): Used for remote control.  
(CN105)  
(for remote control)  
Control items:  
Start/stop input  
Start signal output  
Remote controller prohibit input  
Alarm signal output  
EXCT  
(CN009)  
2P plug (red): Can be used for demand control. When input is present, forces the unit to  
operate with the thermostat OFF.  
Examples of wiring  
z
* Lead wire with 2P plug (special-order part: WIRE K/854 05280 75300)  
Relay (field supply)  
EXCT  
(2P plug (red))  
Relay coil signal  
Indoor unit control PCB  
Note: The length of the wiring from the indoor unit control PCB to the relay must be 6-9/16 ft.  
or less.  
4
DISP  
(CN010)  
2P plug (white): Short-circuiting this plug allows the unit to be operated by the remote  
controller, even if it is not connected to an outdoor unit. (In this case, alarm "E04," which  
indicates trouble in the serial communication between the indoor and outdoor unit, does not  
occur.)  
CHK  
(CN011)  
2P plug (white): Test pin. Short circuiting this plug allows the operation of the indoor fan  
motor (high) and flap motor (F1 position) to be checked.However this test operation stops  
if the indoor unit protection mechanism is activated. The unit can be operated even if the  
remote controller and outdoor unit are not connected. However even if the remote controller  
cannot be connected, it cannot be used to operate the unit. This function can be used for  
short-term tests.  
JP001  
Jumper wire: Allows selection of the T10 terminal start/stop signal. Status at shipment: Pulse  
signal. Jumper wire cut: Static signal (continuous signal)  
FAN DRIVE  
(CN017)  
2P plug (white): This terminal sends a signal to the ventilation fan when the FAN button on  
the wired remote controller is used to operate a commercially-available ventilation fan.Use a  
ventilation fan that can accept no-voltage A contact as the external input signal.  
Examples of wiring  
z
* Lead wire with 2P plug (special-order part: WIRE K/854 05280 50600)  
Relay (field supply)  
DC 12V  
FAN DRIVE  
(2P plug  
(white))  
To external-control input  
terminal on ventilation fan  
Indoor unit control PCB  
Note: The length of the wiring from the indoor unit control PCB to the relay must be 6-9/16 ft.  
or less.  
4-11  
PCB and Functions  
2. Indoor Unit Control PCB  
OPTION  
(CN014)  
6P (white): Outputs external signals as shown in the figure below.  
Relay (DC 12V, field supply) (Note)  
Fan signal  
OPTION  
(white)  
Heat start signal  
Cool start signal  
DC 12V  
Indoor unit control PCB (CR1)  
Thermostat signal  
Defrost signal  
4
Note: The relay must be installed at a distance of 6-9/16 ft. or less from the PCB.  
4-12  
Self-Diagnosis Function Table  
Contents  
5. SELF-DIAGNOSIS FUNCTION TABLE  
1. Self-Diagnosis Function Table..........................................................................................5-2  
5
5-1  
Self-Diagnosis Function Table  
1. Self-Diagnosis Function Table  
1. Self-Diagnosis Function Table  
Causes and corrections in instances when automatic address setting cannot be started  
Trouble  
Cause and correction  
The power LED (D53) on the outdoor unit control PCB does not turn ON. Check for any errors in the power wiring to  
the outdoor unit, and check for a missing  
phase.  
LED 1 and 2 on the outdoor unit control PCB do not turn OFF when Check the “Alarm Display” table and  
the outdoor unit power is turned ON, and automatic address setting  
cannot be started.  
correct the problem.  
(Refer to Section 3 Trouble Diagnosis)  
An alarm appears immediately when automatic address setting is  
started from the wired remote controller.  
Nothing happens when the operator attempts to start automatic  
address setting from the wired remote controller.  
Check that the wired remote controller  
wiring and the inter-unit control wiring are  
connected correctly.  
Check that the indoor unit power is ON.  
Causes and corrections in instances when automatic address setting starts, but cannot be completed successfully  
5
Trouble  
Cause and correction  
An alarm appears on the wired remote controller sometime from several  
seconds to several minutes after automatic address setting is started.  
Check the “Alarm Display” table and  
correct the problem.  
(Refer to Section 3 Trouble Diagnosis.)  
LED 1 and 2 on the outdoor unit control PCB indicate that automatic  
address setting is in progress (the LEDs blink alternately) for several  
minutes after automatic address setting is started (the compressors  
may also start and stop several times), however LED 1 and 2 never  
indicate that automatic address setting is completed (turn OFF).  
Check the alarm details on the “Outdoor  
Unit Control PCB LED 1 and 2 Alarms” ,  
then correct the problem.  
If alarm E15, E16, or E20 appears after automatic address setting is started, check the following items.  
Alarm display  
Alarm description  
The number of indoor units detected during automatic address setting was smaller than the  
number of indoor units which was set with switch S004 and S005 on the outdoor unit PCB.  
E15  
The number of indoor units detected during automatic address setting was larger than the  
number of indoor units which was set with switch S004 and S005 on the outdoor unit PCB.  
E16  
E20  
The outdoor unit received no serial signals from indoor units within 90 seconds after automatic  
address setting was started.  
5-2  
Self-Diagnosis Function Table  
1. Self-Diagnosis Function Table  
Check items  
Check that the indoor unit power is turned ON.  
E15 E16 E20  
Check that the inter-unit control wiring is connected correctly. (Check that there are no open  
circuits, short circuits, terminal plugs, incorrect wiring to the remote controller terminals, or  
similar problems.)  
Check that the remote controller wiring is connected correctly. (Check that there are no open  
circuits, short circuits, incorrect wiring to the inter-unit control wiring terminals, group control  
crossover wiring, or similar problems.)  
Check that the number of indoor units has been set correctly using switch S004 and S005  
on the outdoor unit control PCB.  
Check that the amount of additional refrigerant charge is correct when performing Auto  
Address Setting Case 3A or Case 3B in the flow chart described on page 1-3.  
Check that the refrigerant tubing connections are correct when performing Auto Address  
Setting Case 3A or Case 3B in the flow chart described on page 1-3.  
Check that there are no problems with indoor unit sensors E1 and E3 when performing Auto  
Address Setting Case 3A or Case 3B in the flow chart described on page 1-3.  
Check that there are no indoor units where the system address was already incorrectly set  
by manual or automatic address setting.  
5
•When automatic address setting is started from the outdoor unit control PCB or from the remote controller,  
(SETTING) appears on the remote controller at units where the inter-unit control wiring and remote  
controller wiring are connected correctly. LED 1 and 2 on the outdoor unit control PCB blink alternately.  
•In the case of indoor unit group control, if there is a mistake in the group-control wiring, addresses may not be set  
even if  
(SETTING) appears.  
•Even if alarm E15 or E16 appears, addresses are set at those indoor units which could be verified. The set  
addresses can be checked using the wired remote controller.  
If one of the below alarms appears when the remote controller is operated after automatic address setting was  
completed (LED 1 and 2 on the outdoor unit control PCB are turned OFF), follow the instructions in the table  
below and correct the problem location.  
Remote controller  
Cause  
display  
Nothing is  
displayed.  
The remote controller is not connected correctly (power trouble).  
The indoor unit power was cut off after automatic address setting was completed.  
The remote controller is not connected correctly (remote controller receiving trouble).  
The remote controller of an indoor unit where the indoor unit address is not set is inadvertently  
operated. (Communications with the outdoor unit are not possible.)  
E01  
The remote controller is not connected correctly (trouble with sending of the signal from the  
remote controller to the indoor unit).  
E02  
P09  
The indoor unit ceiling panel connector is not connected correctly.  
5-3  
Self-Diagnosis Function Table  
1. Self-Diagnosis Function Table  
The outdoor unit maintenance remote controller can be used to check the alarm display.  
The number of times that LED 1 and 2 blink on the outdoor unit control PCB can be used to check the alarm display.  
(Refer to “Checking the LED 1 and 2 Alarm Display on the Outdoor Unit Control PCB.)  
Alarm code  
Alarm meaning  
E06  
E12  
E15  
E16  
E20  
E24  
E25  
E26  
E29  
E30  
F04  
F05  
F06  
F07  
F08  
F12  
F16  
F17  
F22  
F23  
F24  
F31  
H03  
H06  
H08  
H11  
H12  
H13  
H15  
H21  
H22  
H23  
H25  
H27  
H28  
H31  
L04  
L05  
L06  
L10  
L17  
L18  
P03  
P04  
P05  
P14  
P16  
P17  
P18  
P22  
P26  
P29  
Outdoor unit failed to receive serial communication signals from indoor unit.  
Automatic address setting start is prohibited.  
Automatic address setting alarm (too few units)  
Automatic address setting alarm (too many units)  
No indoor units at automatic address setting.  
Outdoor unit failed to receive communications from another outdoor unit.  
Outdoor unit address setting failure (duplication)  
Mismatch in outdoor unit quantity  
Outdoor unit failed to receive communication from another outdoor unit.  
Outdoor unit serial communications failure  
Compressor 1 discharge temperature sensor trouble  
Compressor 2 discharge temperature sensor trouble  
Gas temperature sensor trouble at outdoor heat exchanger 1  
Liquid temperature sensor trouble at outdoor heat exchanger 1  
Outdoor air temperature sensor trouble  
(DISCH1)  
(DISCH2)  
(EXG1)  
(EXL1)  
(AIR TEMP)  
(SCT)  
Compressor intake temperature sensor trouble  
High-pressure sensor trouble  
(HPS)  
5
Low-pressure sensor trouble  
(LPS)  
Compressor 3 discharge temperature sensor trouble  
Gas temperature sensor trouble at outdoor heat exchanger 2  
Liquid temperature sensor trouble at outdoor heat exchanger 2  
Outdoor unit non-volatile memory (EEPROM) trouble  
Compressor 1 CT sensor disconnected or short-circuit  
Low-pressure trouble  
(DISCH3)  
(EXG2)  
(EXL2)  
Compressor 1 oil detection sensor (connection) trouble  
Constant speed compressor 2 overcurrent alarm  
Constant speed compressor 2 lock current alarm  
Compressor 2 CT sensor disconnected or short-circuit  
Compressor 2 discharge temperature sensor disconnected  
Compressor 3 overcurrent alarm  
Compressor 3 lock current alarm  
Compressor 3 CT sensor disconnected or short-circuit  
Compressor 3 discharge temperature sensor disconnected  
Compressor 2 lock current alarm  
Compressor 3 lock current alarm  
HIC trouble alarm  
Outdoor unit address duplication  
Duplicated indoor unit priority (alarm at priority indoor units)  
Duplicated indoor unit priority (alarm at non-priority indoor units and outdoor unit)  
Outdoor unit capacity not set  
Outdoor unit model mismatch  
4-way valve operation failure.  
Compressor 1 discharge temperature trouble  
High-pressure switch activated  
Reverse phase (or missing phase) detected, capacity mismatch  
O2 sensor is activated.  
Compressor 1 overcurrent  
Compressor 2 discharge temp trouble  
Compressor 3 discharge temp trouble  
Fan motor trouble  
Inverter compressor high-frequency overcurrent alarm  
Inverter compressor missing phase or lock alarm  
5-4  
Service Checker  
Contents  
6. SERVICE CHECKER  
1. Outdoor Unit Maintenance Remote Controller ................................................................6-2  
1. Over View .........................................................................................................................6-2  
2. Functions..........................................................................................................................6-2  
3. Ordinary Display Controls and Functions.........................................................................6-3  
4. Monitoring Operations......................................................................................................6-7  
5. Outdoor Unit Alarm History Monitor .................................................................................6-8  
6. Setting the Outdoor Unit EEPROM Data..........................................................................6-9  
6
6-1  
Service Checker  
1. Outdoor Unit Maintenance Remote Controller  
1. Overview  
About the outdoor unit maintenance remote controller  
The outdoor unit utilizes non-volatile memory (EEPROM) on its PCB.  
This allows EEPROM data to replace the setting switches that were  
present on previous PCBs. The outdoor unit maintenance remote  
controller is used to set and change these EEPROM data.  
In addition to setting and checking the outdoor unit EEPROM data, this  
remote controller can also be used to monitor the outdoor unit alarm  
history, monitor the various indoor and outdoor temperatures, and  
check the indoor unit connection status  
(number of units, operating mode, etc.).  
NOTE  
Outdoor unit maintenance remote controller does not function as an  
ordinary remote controller. It is therefore only used for test runs and  
during servicing.  
System Diagram  
Outdoor unit maintenance  
6
remote controller  
Outdoor unit  
Inter-unit control wiring  
Special service checker wiring  
Outdoor unit  
control PCB  
Indoor unit  
Indoor unit  
Remote controller Assy  
Remote  
controller  
Remote  
controller  
* Operation manual included in package.  
The special service checker wiring is required in order to connect the outdoor unit maintenance remote controller  
to the outdoor unit PCB.  
Ordinary remote controllers or other controllers are still required for the indoor units, even when the outdoor unit  
maintenance remote controller is connected.  
2. Functions  
Functions on the ordinary display  
(1) Press the buttons to execute the following functions.  
• All indoor units stop/start  
• Cooling/heating change  
• All indoor units test run  
(2) Display: The following displays are possible.  
• Alarm display  
• No. of indoor/outdoor units  
• Unit Nos. of connected indoor/outdoor units  
• Operating status of indoor/outdoor units (Blinks when alarm occurs.)  
• Indoor thermostat ON  
• Display of individual outdoor unit alarms  
Total operating time of outdoor unit compressors  
• Oil level of the outdoor unit oil sensor  
Total outdoor unit power ON time  
• Outdoor unit microcomputer version, other information.  
6-2  
Service Checker  
1. Outdoor Unit Maintenance Remote Controller  
Temperature monitor  
Displays the temperature from each indoor/outdoor sensor.  
Outdoor unit alarm history monitor  
Displays the outdoor unit alarm history.  
Setting the outdoor unit EEPROM data  
Settings mode 1 and settings mode 2 can be used to make outdoor unit EEPROM data settings.  
3. Ordinary Display Controls and Functions  
Functions on the ordinary display  
Connect the special service checker wiring to the outdoor unit PCB.  
The connection diagram is shown below.  
If the inter-unit control wiring  
is connected, it can be left  
as-is.  
Outdoor unit PCB  
RC (3P, blue)  
PCB connector (3P, blue)  
In the case of an independent  
outdoor unit (1 maintenance  
remote controller connected  
to 1 outdoor unit, automatic  
address setting for indoor  
units not completed), both  
setting mode 1 and setting  
mode 2 can be used for  
outdoor unit EEPROM data  
settings.  
Special service checker wiring  
6
Relay connector (2P, white)  
The overall system status for  
that refrigerant system is  
displayed.  
Outdoor unit maintenance remote controller  
All units start/stop (Fig. 6-1)  
<Operation>  
The  
(ON/OFF operation) button can be used to start and stop all  
LED  
indoor units.  
• The LED illuminates if any indoor unit is operating.  
• The LED blinks if an alarm occurs at any of the operating indoor units.  
Cooling/heating change (Fig. 6-1)  
<Operation>  
The  
(MODE) button can be used to change between heating and  
Fig. 6-1  
cooling operation.  
• The display indicates the operating mode of the indoor unit with the lowest  
unit No.  
All units test run (Fig. 6-2)  
<Operation>  
The  
(CHECK) button can be used to start and stop a test run for all  
units.  
(To start, press and hold the button for 4 seconds.)  
During the test run, “Test” is displayed.  
• The status of test runs performed from the indoor unit remote controller is  
not displayed on the outdoor unit maintenance remote controller.  
Fig. 6-2  
6-3  
Service Checker  
1. Outdoor Unit Maintenance Remote Controller  
Display (functions)  
l The item codes can be changed with the  
and  
buttons.  
Item code  
Item  
Remarks  
Outdoor unit alarm  
Alarm code display  
Quantity  
No. of connected indoor units  
Unit Nos. of connected indoor unit  
Operating status of indoor unit  
Thermostat ON status of indoor unit  
No. of connected outdoor units  
Unit Nos. of connected outdoor units  
7-segment display  
7-segment display  
7-segment display  
1 – 4  
7-segment display  
7-segment display  
Operating status of outdoor unit compressor  
Compressor 1 operating time  
Compressor 2 operating time  
Compressor 3 operating time  
0 – 99999999 hrs  
0 – 99999999 hrs  
6
Compressor 1 oil level  
Compressor 2 oil level  
Compressor 3 oil level  
2 = Sufficient  
2 = Sufficient  
2 = Sufficient  
0 = Empty 1 = Insufficient  
0 = Empty 1 = Insufficient  
0 = Empty 1 = Insufficient  
Outdoor unit power ON time  
Compressor 1 operation count  
Compressor 2 operation count  
Compressor 3 operation count  
0 – 99999999 hrs  
0 – 65535 times  
0 – 65535 times  
0 – 65535 times  
Alarm history 1 (most recent)  
Alarm history 2  
Display only. Alarm code and unit No. of unit  
where alarm occurred are displayed alternately.  
0 = CCU  
Alarm history 3  
Alarm history 4  
Alarm history 5  
1 – 4 = Outdoor unit  
Alarm history 6  
Alarm history 7  
Alarm history 8 (oldest)  
Firmware version  
Program version  
Displays the version No. × 100.  
Displays the version No. × 100.  
and  
correspond to Fig. 6-3 on the next page.  
6-4  
Service Checker  
1. Outdoor Unit Maintenance Remote Controller  
XX-YY R.C.  
3
2
1
Displays the outdoor unit sub-bus address which is  
currently selected.  
XX = Outdoor unit system address (1 – 30)  
YY = Outdoor unit address (1 – 4)  
The locations where  
shown on Fig. 6-3.  
,
and  
are displayed as  
LED  
Fig. 6-3  
Sample display (Fig. 6-4, Fig. 6-5)  
6
<No. of connected indoor units>  
4 units connected  
Fig. 6-4  
<Unit Nos. 1, 2, 3, 4 connected>  
Fig. 6-5  
6-5  
Service Checker  
1. Outdoor Unit Maintenance Remote Controller  
Concerning the 7-segment 4-digit display of remote controller timer time  
The unit Nos. of connected units are indicated by four 7-segment digits  
and a colon.  
Display of unit Nos. 1 20  
1
Meaning of colon  
1
6
11  
16  
3
8
13  
18  
4
9
14  
19  
20  
2
7
12  
17  
5
10  
15  
1 – 20 21 – 40 41 – 60 61 – 80  
Meaning of colon  
2 Display of unit Nos. 21 40  
21  
22  
26  
27  
31  
32  
36  
37  
23  
28  
33  
38  
24  
25  
29  
30  
34  
35  
39  
40  
1 – 20 21 – 40 41 – 60 61 – 80  
3 The meaning of the colon changes in the same way to indicate unit Nos. up to 80.  
Sample displays of connected indoor unit Nos.  
Display of unit No. 1  
4
6
Display of unit Nos. 1 and 2  
Display of unit Nos. 1, 2, and 3  
Display of unit Nos. 1, 2, 3, and 4  
The change of the colon display (between unit Nos. 1 20 to unit Nos. 21 40) occurs automatically  
every 10 seconds. (However the display does not change if there are no higher-number units connected.)  
To change the display to the higher-number units before 10 seconds have passed,  
press the  
(FLAP) button.  
An 8-digit display is used for display of the compressor total operating time (in 1-hour units).  
When the first 4 digits are displayed, the bottom dot of the colon is illuminated. (Figure (A))  
When the last 4 digits are displayed, the colon dot is OFF. (Figure (B))  
The display of the first 4 digits and last 4 digits changes automatically after 10 seconds.  
The display can also be changed by pressing the  
(FLAP) button.  
<Compressor total operating time>:  
(A) and (B) are displayed alternately  
(The example here (0000, 0062)  
indicates 62 hours.)  
Sample Display (A), (B)  
6-6  
Service Checker  
1. Outdoor Unit Maintenance Remote Controller  
4. Monitoring Operations  
Display the indoor unit and outdoor unit sensor temperatures.  
<Operating procedure>  
Press and hold the  
4 seconds or longer to engage temperature monitor mode.  
During temperature monitoring, illuminates.  
(CHECK) and  
(CANCEL) buttons simultaneously for  
(The display and operations are the same as for monitor mode using the indoor  
unit remote controller.)  
Press the  
(UNIT) button and select the indoor unit to monitor.  
Press the temperature setting  
and  
buttons and select the item  
code of the temperature to monitor.  
The unit No. of the selected indoor unit, and the temperature data, are displayed.  
To end monitoring, press the (CHECK) button.  
The display returns to the normal display.  
NOTE  
4
1
2
3
The display does not blink.  
Display of unit No. 1 (main unit)  
DN Description  
Remarks  
Intake temp.  
6
E1  
E2  
E3  
Indoor unit  
Discharge temp.  
Discharge temp. setting  
Indoor unit electronic control valve position  
Discharge temp. 1 at Compressor 1  
Discharge temp. 2 at Compressor 2  
High-pressure sensor temp.  
Heat exchanger gas 1  
Heat exchanger liquid 1  
Heat exchanger gas 2  
Heat exchanger liquid 2  
Outdoor air temp.  
STEP  
Not used  
Inverter primary current  
Current at Compressor 2 (CT2)  
MOV1 pulse  
A
Outdoor unit  
A
STEP  
STEP  
MOV2 pulse  
Discharge temp. 3 at Compressor 3  
Current at Compressor 3 (CT3)  
MOV3 pulse  
A
STEP  
Heat exchanger gas 3  
Heat exchanger liquid 3  
Low-pressure sensor temp.  
Suction temp.  
Oil 1  
Oil 2  
Oil 3  
Actual operating frequency  
Hz  
0A and subsequent items are outdoor unit data. 0A – 22 are for unit No. 1.  
2A – 42 are for unit No. 2. 4A – 62 are for unit No. 3. 62 – 89 are for unit No. 4.  
NOTE  
6-7  
Service Checker  
1. Outdoor Unit Maintenance Remote Controller  
5. Outdoor Unit Alarm History Monitor  
Recalls and displays the outdoor unit alarm history.  
This is for the outdoor unit only. Indoor unit alarms  
cannot be recalled.  
The indoor unit alarm history can be viewed on the  
indoor unit remote controller or other controller.  
<Operation procedure>  
Press and hold the  
(CHECK) button and  
(SET) button simultaneously for 4 seconds or lon-  
ger to engage outdoor unit alarm history mode.  
During temperature monitoring,  
illuminates.  
The display and operations are the same as for  
the alarm history monitor performed from the  
indoor unit remote controller. However the “unit  
No.” display shows the outdoor unit address.  
5
1
4
2
3
Press the  
outdoor unit for which to monitor the alarm history.  
Press the temperature setting and  
(UNIT) button, and select the  
6
buttons and select the item code for the alarm  
history. The selected outdoor unit address, the  
item code, and the alarm history (alarm data) are  
displayed.  
The outdoor unit address is displayed as R.C.  
XX – YY.  
(R.C. XX = Outdoor unit system address  
YY = Outdoor unit address  
Item codes 01 – 08 are displayed. 01 indicates the  
most recent alarm.  
The alarm history displays the alarm code.  
(If no alarms are present, then  
displayed.)  
is  
To clear the alarm history, press the  
(CANCEL) button.  
(The outdoor unit alarm history will be cleared.)  
To exit, press the (CHECK) button.  
The display returns to the normal display.  
6-8  
Service Checker  
1. Outdoor Unit Maintenance Remote Controller  
6. Setting the Outdoor Unit EEPROM Data  
(A)  
This function is used to make the outdoor unit  
EEPROM data settings.  
Setting mode 1  
4
Press the  
(CHECK) button and the  
(VENTILATION) button simultaneously for 4 sec-  
onds or longer.  
Press the temperature setting  
and  
buttons to change the item code. The item codes  
and setting data are shown in the table below.  
Press the timer time  
and  
buttons to  
change the setting data.  
To confirm the changed setting data, press the  
(SET) button.  
1
3
2
(A) and (B) are displayed alternately.  
(At this time, the “SET DATA” display stops blinking  
and remains lit.)  
” blinks when this mode is engaged, and  
” appears in the outdoor unit address section.  
(B)  
6
The item code number (values shown in the table  
below) and the corresponding setting data (6 dig-  
its) are also displayed. (The 6 digits of the setting  
data are displayed by changing between the first 3  
digits (Fig. (A) and the last three digits (Fig. (B).  
When the first 3 digits are displayed, the top dot of  
the colon is illuminated.)  
To exit setting mode, press the  
button.  
(CHECK)  
Code  
No.  
Parameter  
Description (SET DATA)  
0000 = Sensor input not present. Control is performed.  
0001 = Sensor input present. Control is performed.  
0002 = Sensor input not present. Control is not performed.  
0003 = Sensor input present. Control is not performed.  
Snowfall sensor usage  
0000 = Disabled  
0002 = Quiet mode 2  
0001 = Quiet mode 1  
0003 = Quiet mode 3  
Outdoor unit fan Quiet mode  
0004 = Quiet mode 4  
0000 Heat pump  
0001 Cooling  
Cooling  
0000 = 0% 0001 = 40 ... 0004 = 70 0007 = 100 0008 = 120  
0009 = 140 0010 = 160 0011 = 200 0012 = –1 (no limit)  
0000 = 0% 0001 = 40 ... 0004 = 70 0007 = 100 0008 = 120  
0009 = 140 0010 = 160 0011 = 200 0012 = –1 (no limit)  
Demand 1 current  
Demand 2 current  
6-9  
Service Checker  
1. Outdoor Unit Maintenance Remote Controller  
Setting mode 2  
Press the  
(CHECK) button,  
(SET)  
button and the  
ously for 4 seconds or longer.  
(CANCEL) button simultane-  
4
Press the temperature setting  
and  
buttons to change the item code. The item codes  
and setting data are shown in the table below.  
Press the timer time  
and  
buttons to  
change the setting data.  
To confirm the changed setting data, press the  
(SET) button.  
(At this time, the SET DATA display stops blinking  
and remains lit.)  
1
5
3
2
” blinks when this mode is engaged, and  
when this mode is engaged, “Now Setting” is dis-  
played blinking, and the address of the outdoor  
unit that is being set “System XX-YY” (System XX  
= System address, YY = Outdoor unit address),  
the item code No. (values from the table below),  
and the corresponding settings data (6 digits) are  
displayed. The item code number (values shown in  
the table below) and the corresponding setting  
data (6 digits) are also displayed. (The 6 digits of  
the setting data are displayed by changing  
(C) Display of first 3 digits  
between the first 3 digits (Fig. (C)) and the last  
three digits (Fig. (D)). When the first 3 digits are  
displayed, the top dot of the colon is illuminated.)  
To exit setting mode, press the  
(CHECK)  
button. Returns to normal display mode.  
(D) Display of last 3 digits  
6
Refrigerant type: (C) and (D) are displayed alternately.  
The example here (000, 410) indicates R410A.  
CODE  
NO.  
Parameter  
Description (SET DATA)  
0 = Disabled 112 (36 Type) 160 (60 Type)  
Outdoor unit capacity  
280 (90 Type) 450 (140 Type)  
6-10  
200706MDC  

White Rodgers 1f85 277 User Manual
Sharp Mx M450 User Manual
Samsung Um 18a1 B1 B2 User Manual
Samsung Clp 310kg User Manual
Ricoh Mp 2590 User Manual
Plustek All In One Printer 820 User Manual
NEC NP PX302WL BK User Manual
NEC MULTISYNC VT440 User Manual
Lexmark X 2650 User Manual
FURRION FACR13SA BL User Manual