FUJITSU GENERAL AOU24RLX User Manual

SPLIT TYPE  
ROOM AIR CONDITIONER  
type  
CASSETTE  
INVERTER  
SERVICE  
INSTRUCTION  
Models Indoor unit Outdoor unit  
AOU18RLX  
AOU24RLX  
AOU36RLX  
AOU42RLX  
AUU18RCLX  
AUU24RCLX  
AUU36RCLX  
AUU42RCLX  
3. REPLACEMENT PARTS  
1 REPLACEMENT PARTS ( For OUTDOOR UNIT )....................................................... 03-01  
03-01  
03-01  
1-1 For AOU18/ 24/ 36RLX...........................................................................................  
1-1-1 PARTS LAYOUT DRAWING...............................................................................  
1-1-2 WIRING................................................................................................................ 03-03  
1-1-3 DISASSEMBLY PROCESS.................................................................................  
1-1-4 ASSEMBLY PROCESS of INVERTER UNIT......................................................  
03-04  
03-09  
03-15  
03-15  
1-2 For AOU42RLX.......................................................................................................  
1-2-1 PARTS LAYOUT DRAWING...............................................................................  
1-2-2 WIRING................................................................................................................ 03-17  
1-2-3 DISASSEMBLY PROCESS.................................................................................  
1-2-4 ASSEMBLY PROCESS of INVERTER UNIT......................................................  
03-19  
03-25  
2 REPLACEMENT PARTS ( For INDOOR UNIT )........................................................... 03-30  
03-30  
2-1 PARTS LAYOUT DRAWING...................................................................................  
CASSETTE type  
INVERTER  
1 . DESCRIPTION OF EACH  
CONTROL OPERATION  
1. COOLING OPERATION  
1-1 COOLING CAPACITY CONTROL  
A sensor (room temperature thermistor) built in the indoor unit will usually perceive  
difference or variation between a set temperature and present room temperature, and  
controls the operation frequency of the compressor.  
* If the room temperature is 3.6 degF(2 degC) higher than a set temperature,  
the compressor operation frequency will attain to maximum performance.  
* If the room temperature is 3.6 degF(2 degC) lower than a set temperature, the compressor  
will be stopped.  
* When the room temperature is between +3.6 degF(+2 degC) to -3.6 degF(-2 degC) of  
the setting temperature, the compressor frequency is controlled within the range shown in Table1.  
However, the maximum frequency is limited in the range shown in Figure 1 based on the  
fan speed mode and the outdoor temperature.  
( Table 1 : Compressor Frequency Range )  
minimum  
frequency  
20Hz  
20Hz  
20Hz  
maximum  
frequency  
63Hz  
80Hz  
90Hz  
AUU18RCLX  
AUU24RCLX  
AUU36RCLX  
AUU42RCLX  
25Hz  
92Hz  
( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )  
Fan speed mode  
Outdoor air  
temperature  
Hi  
Me  
Lo  
AUU18RCLX A zone  
B zone  
C zone  
D zone  
AUU24RCLX A zone  
B zone  
C zone  
D zone  
AUU36RCLX A zone  
B zone  
C zone  
D zone  
AUU42RCLX A zone  
B zone  
63Hz  
45Hz  
35Hz  
35Hz  
80Hz  
55Hz  
45Hz  
45Hz  
90Hz  
75Hz  
70Hz  
63Hz  
92Hz  
72Hz  
60Hz  
60Hz  
45Hz  
35Hz  
35Hz  
30Hz  
55Hz  
45Hz  
45Hz  
35Hz  
75Hz  
70Hz  
63Hz  
55Hz  
72Hz  
60Hz  
60Hz  
53Hz  
45Hz  
35Hz  
35Hz  
30Hz  
55Hz  
45Hz  
45Hz  
35Hz  
75Hz  
70Hz  
63Hz  
55Hz  
72Hz  
60Hz  
60Hz  
53Hz  
A zone  
B zone  
87.8°F  
(31°C)  
66.2°F  
(19°C)  
C zone  
D zone  
51.8°F  
(11°C)  
C zone  
D zone  
01-01  
2. HEATING OPERATION  
2-1 HEATING CAPACITY CONTROL  
A sensor (room temperature thermistor) built in the indoor unit will usually perceive  
difference or variation between a set temperature and present room temperature, and  
controls the operation frequency of the compressor.  
* If the room temperature is lower 5.4 degF(3 degC) than a set temperature,  
the compressor operation frequency will attain to maximum performance.  
* If the room temperature is higher 3.6 degF(2 degC) than a set temperature, the compressor  
will be stopped.  
* When the room temperature is between +3.6 degF(+2 degC) to -5.4 degF(-3 degC) of  
the setting temperature, the compressor frequency is controlled within the range shown in Table2.  
However, the maximum frequency is limited in the range shown in Figure 2 based on  
the outdoor temperature.  
( Table 2 : Compressor Frequency Range )  
minimum  
frequency  
20Hz  
20Hz  
20Hz  
maximum  
frequency  
87Hz  
87Hz  
95Hz  
AUU18RCLX  
AUU24RCLX  
AUU36RCLX  
AUU42RCLX  
23Hz  
92Hz  
( Fig.2 : Limit of Maximum Frequency based on Outdoor Temperature )  
Limit of Maximum  
Outdoor air  
temperature  
Frequency  
AUU18RCLX A zone  
B zone  
87Hz  
85Hz  
70Hz  
70Hz  
60Hz  
87Hz  
85Hz  
70Hz  
70Hz  
60Hz  
95Hz  
95Hz  
90Hz  
80Hz  
80Hz  
92Hz  
92Hz  
90Hz  
80Hz  
80Hz  
E zone  
D zone  
68°F  
(20°C)  
C zone  
D zone  
E zone  
60.8°F  
(16°C)  
AUU24RCLX A zone  
B zone  
C zone  
C zone  
D zone  
E zone  
53.6°F  
(12°C)  
B zone  
A zone  
AUU36RCLX  
AUU42RCLX  
A zone  
B zone  
C zone  
D zone  
E zone  
A zone  
B zone  
C zone  
D zone  
E zone  
41°F  
(5°C)  
01-02  
3. DRY OPERATION  
3-1 INDOOR UNIT CONTROL  
The compressor rotation frequency shall change according to set temperature and room  
temperature variation which the room temperature sensor of the indoor unit has detected  
as shown in the Table 3.  
( Table 3 : Compressor frequency )  
Operating frequency  
AUU18RCLX  
AUU24RCLX  
AUU36RCLX  
AUU42RCLX  
25Hz  
30Hz  
45Hz  
30Hz  
( Fig.3 : Compressor Control based on Room Temperature )  
Room Room  
temperature temperature  
Compressor ON  
Ts+2.7 degF  
(1.5 degC)  
Ts+1.8 degF  
(1 degC)  
Compressor OFF  
Ts : Setting temperature  
( Fig.4 : Indoor Fan Control )  
Compressor  
ON  
OFF  
Indoor fan  
air flow mode  
ON  
OFF  
30  
5
30  
120  
5
(sec)  
180  
180  
Air flow mode : Lo  
01-03  
4. AUTO CHANGEOVER OPERATION  
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum  
mode from among the HEATING, COOLING and MONITORING modes. During operation, the  
optimum mode is automatically swiched in accordance with temperature changes. The temperature  
can be set between 64°F(18°C) and 88°F(30°C) in 2 degF(1 degC) steps.  
1 When operation starts, only the indoor fan is operated for 1 minute. (Air flow mode: S- Lo)  
After 1 minute, depends on the room temperature and outdoor unit's operarion mode,  
the operation mode is selected in accordance with the table below.  
( Table 4 : Operation mode selection table )  
Operation mode  
Room temperature :TR  
TR > Ts +3.6 degF  
=
Cooling  
(2 degC)  
Ts +3.6 degF > TR > Ts-3.6 degF  
Monitoring  
Heating  
(2 degC)  
(2 degC)  
Ts +3.6 degF > TR  
=
(2 degC)  
Ts : Setting temperature  
2
3
4
1
When COOLING was selected at , the same operation as COOLING OPERATION is performed.  
When HEATING was selected at  
, the same operation as HEATING OPERATION is performed.  
1
When the compressor was stopped for 6 consecutive minutes by the temperature control function  
after the COOLING or HEATING operation mode was selected at 1 above, operation is switched  
to MONITORING and the operation mode is selected again.  
01-04  
5. INDOOR FAN CONTROL  
1. Fan speed  
( Table 5 : Indoor Fan Speed )  
AUU18RCLX  
AUU24RCLX  
Operation mode  
Heating  
Air flow mode  
Speed (rpm)  
Operation mode  
Heating  
Air flow mode  
Speed (rpm)  
Hi  
Me  
Lo  
S-Lo  
Hi  
Me  
Lo  
S-Lo  
440  
380  
330  
250  
490  
430  
360  
250  
Hi  
Me  
Lo  
S-Lo  
Hi  
Me  
Lo  
S-Lo  
400  
350  
310  
250  
450  
390  
330  
250  
Cooling  
Cooling  
AUU42RCLX  
AUU36RCLX  
Operation mode  
Heating  
Air flow mode  
Speed (rpm)  
Operation mode  
Heating  
Air flow mode  
Speed (rpm)  
Hi  
Me  
Lo  
S-Lo  
Hi  
Me  
Lo  
S-Lo  
620  
550  
470  
300  
620  
550  
470  
300  
Hi  
Me  
Lo  
S-Lo  
Hi  
Me  
Lo  
S-Lo  
580  
510  
440  
300  
580  
510  
440  
300  
Cooling  
Cooling  
2. FAN OPERATION  
The airflow can be switched in 4 steps such as AUTO, LOW, MED, HIGH, while the indoor  
fan only runs.  
When [AUTO] is selected, the indoor fan motor runs LO and OFF at 1 minute intervals.  
3. COOLING OPERATION  
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,  
as shown in Figure 5.  
On the other hand, if switched in [HIGH] [LOW], the indoor motor will run at a constant airflow of [COOL]  
operation modes LOW, MED, HIGH,as shown in Table 5.  
( Fig.5 : Airflow change - over ( Cooling : AUTO ) )  
*1  
When the room  
temperature rises  
TR : Room temperature  
Ts : Setting temperature  
TR-Ts > 5.4 degF  
=
(3 degC)  
TR-Ts > 3.6 degF  
=
HIGH mode  
(2 degC)  
5.4 degF > TR-Ts > 3.6 degF  
=
(3 degC)  
(2 degC)  
3.6 degF > TR-Ts > 1.8 degF  
=
MED mode  
LOW mode  
(2 degC)  
(1 degC)  
3.6 degF > TR-Ts  
(2 degC)  
1.8 degF > TR-Ts  
(1 degC)  
When the room  
temperature drops  
*1 : Contains a condition to the following  
When the operation mode is set to AUTO mode  
at the start of operation.  
When the setting temperature was changed.  
When the operation mode was changed to COOLING mode.  
When the airflow mode was changed to AUTO mode.  
01-05  
4. HEATING OPERATION  
When the airflow is set to [AUTO], the indoor fan  
motor operates [MED] mode.  
Then the indoor fan motor will run according  
to a room temperature, as shown in Figure 6.  
( Fig.6 : Airflow change - over ( Heating : AUTO ) )  
Indoor heat exchanger  
temperature  
Go up one-step  
116.6°F  
(47°C)  
On the other hand, if switched in [HIGH] [LOW],  
the indoor motor will run at a constant airflow  
of [COOL] operation modes LOW, MED, HIGH,  
as shown in Table 5.  
Hold  
105.8°F  
(41°C)  
Go down one-step  
5. COOL AIR PREVENTION CONTROL (Heating mode)  
The maximum value of the indoor fan speed is set as shown in Figure 7, based on the detected  
temperature by the indoor heat exchanger sensor on heating mode.  
( Fig.7 : Cool Air Prevention Control )  
Indoor heat exchanger  
temperature  
Indoor heat exchanger  
temperature  
SETTING  
FAN MODE  
91.4°F  
(33°C)  
86°F  
(30°C)  
LO mode  
86°F  
S-LOW mode  
(30°C)  
6. DRY OPERATION  
Refer to the Figure 4.  
During the dry mode operation, the fan speed setting can not be changed.  
01-06  
6. OUTDOOR FAN CONTROL  
1. Outdoor Fan Motor  
Following table shows the fan speed of the outdoor unit.  
( Table 6 : Fan speed of the outdoor unit )  
Cooling  
Heating  
AUU18RCLX  
AUU24RCLX  
AUU36RCLX  
780/ 400/ 250/ 220/ 200 rpm  
780/ 400/ 250/ 220/ 200 rpm  
900/ 780/ 400/ 250/ 220/ 200 rpm  
900/ 850/ 780/ 400/ 250/ 220/ 200 rpm  
850/ 780/ 400/ 350/ 300 rpm  
780/ 750/ 350/ 0 rpm  
900/ 850/ 780/ 350/ 200/ 170/ 150 rpm  
850/ 780/ 750/ 350/ 200/ 170/ 150 rpm  
Upper fan  
Lower fan  
AUU42RCLX  
AUU42RCLX has two fan motors.  
*
*
The outdoor fan speed changs in the range mentioned avobe depending on the compressor  
frequency and outdoor temperature.  
(When the compressor frequency and outdoor temperature increase, the outdoor fan speed  
also changes to the higher speed.  
When the compressor frequency and outdoor temperature decrease, the outdoor fan  
speed also changes to the lower speed.)  
For AUU18RCLX  
*
*
*
It runs at 250rpm for 20 seconds after starting up the outdoor fan.  
When the outdoor heat exchanger tenperature is lower than 35.6°F (2°C),  
the fan speed switches to 780rpm on heating mode.  
For AUU24RCLX / AUU36RCLX  
It runs at 250rpm for 20 seconds after starting up the outdoor fan.  
When the outdoor heat exchanger tenperature is lower than 35.6°F (2°C),  
the fan speed switches to 900rpm on heating mode.  
For AUU42RCLX  
It runs at 500rpm for 20 seconds after starting up the outdoor fan.  
When the outdoor heat exchanger tenperature is lower than 35.6°F (2°C),  
the fan speed switches to 900rpm(Upper fan) and 850rpm(Lower fan) on heating mode.  
01-07  
7. LOUVER CONTROL  
1. VERTICAL LOUVER CONTROL  
(Function Range)  
Each time the button is pressed, the air direction range will change as follows:  
(Fig.8 : Air Direction Range)  
(Operation Range)  
Cooling / Dry mode  
Heating mode  
1
2
3
Fan mode  
4
Use the air direction adjustments within the ranges shown above.  
The vertical airflow direction is set automatically as shown, in accordance with the type of operation  
selected.  
Cooling / Dry / Fan mode Horizontal flow  
Heating mode  
Downward flow  
For AUU18/ 24RCLX  
At the start of operation if the setting louver position is  
,the setting position is set to  
after the louver moves from totally-enclosed position to . (Positioning Control)  
For AUU36/ 42RCLX  
At the start of operation if the setting louver position is  
or  
,the setting position is set to  
or  
after the louver moves from totally-enclosed position to . (Positioning Control)  
The indoor fan motor starts after the louver reaches to the setting position.  
2. SWING OPERATION  
When the swing signal is received from the remote controller, the vertical louver starts to swing.  
The range of swing depends on the set airflow direction.  
(Swinging Range)  
Airflow direction set  
Range of swing  
to  
to  
to  
to  
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted  
and the louver stops at the memorized position.  
( Stop mode means Operation stop.)  
01-08  
8. COMPRESSOR CONTROL  
1. OPERATION FREQUENCY RANGE  
The operation frequency of the compressor is different based on the operation mode as  
shown in Table 7.  
(Table 7 : Compressor Operation Frequency Range)  
Cooling  
Heating  
Dry  
Min  
Max  
Min  
Max  
AUU18RCLX  
AUU24RCLX  
AUU36RCLX  
AUU42RCLX  
20Hz  
20Hz  
20Hz  
25Hz  
63Hz  
80Hz  
90Hz  
92Hz  
20Hz  
20Hz  
20Hz  
23Hz  
87Hz  
87Hz  
95Hz  
92Hz  
25Hz  
30Hz  
45Hz  
30Hz  
2. OPERATION FREQUENCY CONTROL AT START UP  
The compressor frequency soon after the start-up is controlled as shown in Figure 9.  
(Fig.9 : Compressor Control at Start-up)  
Frequency  
1
Hold  
Frequency  
2
Time A  
Time B  
Time C  
Time E  
Time D  
(Frequency)  
For AUU18/ 24/ 36RCLX  
1 Discharge pipe temp. > 50°F (10°C) ,86°F (30°C)  
=
Frequency  
Frequency  
(Cooling)  
(Heating)  
2 Discharge pipe temp. < 50°F (10°C) ,86°F (30°C)  
(Cooling) (Heating)  
AUU18RCLX  
AUU24RCLX  
AUU36RCLX  
AUU42RCLX  
40Hz  
56Hz  
56Hz  
70Hz  
For AUU42RCLX  
1 Discharge pipe temp. > 50°F (10°C) ,95°F (35°C)  
=
(Cooling)  
2 Discharge pipe temp. < 50°F (10°C) ,95°F (35°C)  
(Cooling) (Heating)  
(Heating)  
(Time)  
Time A  
Time B  
Time C  
Time D  
Time E  
AUU18RCLX  
AUU24RCLX  
AUU36RCLX  
AUU42RCLX  
180sec  
180sec  
60sec  
80sec  
120sec  
180sec  
720sec  
720sec  
120sec  
180sec  
01-09  
9. TIMER OPERATION CONTROL  
9-1 Wired Remote Controller  
AR-3TA14  
ON / TIMER  
OFF / TIMER  
WEEKLY TIMER  
TEMPERATURE SET BACK TIMER  
1. ON / OFF TIMER  
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.  
Operation mode  
Stop mode  
Set time of timer  
ON timer : When the clock reaches the set time, the air conditioner will be turned on.  
Operation mode  
Stop mode  
Set time of timer  
2. WEEKLY TIMER  
2-1. WEEKLY TIMER  
Use this timer function to set operating time for each day of the week.  
The weekly timer allows up to two ON and OFF time to set up per day.  
Operation mode  
Operation mode  
Operation mode  
Stop mode  
Stop mode  
Stop mode  
Set time  
Set time  
Set time  
Set time  
The operating time can be set in 30 min increments only.  
The OFF time can be carried over to next day.  
The ON timer and the OFF timer functions cannot be set with using the weekly timer.  
Both ON and OFF time must be set.  
01-10  
2-2. DAY OFF setting  
The DAY OFF setting is only available for days for which weekly settings already exist.  
If the operating time carries over to the next day (during a next day setting), the effective  
DAY OFF range will be set as shown below.  
Normal  
DAY OFF  
Operation mode  
Stop mode  
Operation mode  
Stop mode  
Stop mode  
Preceding day  
Setting day  
DAY OFF  
Next day  
Next day setting  
Operation mode  
Operation mode  
Stop mode  
Next day  
Stop mode  
Stop mode  
Preceding day  
Setting day  
The DAY OFF setting can only be set one time. The DAY OFF setting is cancelled automatically  
after the set day has passed.  
3. TEMPERATURE SET BACK TIMER  
The SET BACK timer only changes the set temperature for 7 days, it cannot be used to start or stop  
air conditioner operation.  
The SET BACK timer can be set to operate up to two times per day but only one temperature setting  
can be used.  
During the COOL/DRY mode, the air conditioner will operate at a minimum of 64°F(18°C) even if  
the SET BACK temperature is set to 62°F(17°C) or lower.  
Case of SET BACK timer on the Cooling operation.  
( Setting temperature :72°F(22°C), SET BACK temperature :80°F(26°C))  
ON  
OFF  
ON  
OFF  
SET BACK setting  
80°F(26°C)  
Operation  
temperature  
72°F(22°C)  
*1  
80°F(26°C)  
76°F(24°C)  
72°F(22°C)  
Operation  
temperature  
*1: During the SET BACK function,  
the setting temperature is changed.  
Chenge the setting temperature:  
72°F(22°C) 76°F(24°C)  
01-11  
10. ELECTRONIC EXPANSION VALVE CONTROL  
The most proper opening of the electronic expansion valve is calculated and controlled under the  
present operating condition based on the following values.  
The compressor frequency, the temperatures detected by the discharge temperature sensor  
and the outdoor temperature sensor.  
The pulse range of the electronic expansion valve control is between 50 to 480 pulses.  
At the time of supplying the power to the outdoor unit, the initialization of the electronic  
expansion valve is operated (1000 pulses are input to the closing direction).  
11. TEST OPERATION CONTROL  
With Wired Remote Controller  
Under the condition where the air conditioner stops, press the MASTER CONTROL button and  
the FAN CONTROL button simultaneously for 5 seconds or more, and the test operation control  
mode will appear.  
During test running, " " will display on the remote controller display.  
Set the test operation mode, and the compressor will continue to run regardless of whatever  
the room temperature sensor detects.  
The test operation mode is released if 60 minutes have passed after setting up the test operation.  
12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )  
The compressor won't enter operation status for 3 minutes after the compressor is stopped,  
even if any operation is given.  
13. 4-WAY VALVE EXTENSION SELECT  
At the time when the air conditioner is switched from the cooling mode to heating mode,  
the compressor is stopped, and the 4-way valve is switched in 3 minutes later  
after the compressor stopped.  
14. AUTO RESTART  
When the power was interrupted by a power failure, etc. during operation, the operation contents  
at that time are memorized and when power is recovered, operation is automatically resumed with  
the memorized operation contents.  
When the power is interrupted and recovered during timer operation, timer operation is canceled,  
but only setting time is memorized.  
[Operation contents memorized when the power is interrupted]  
Operation mode  
Set temperature  
Set air flow  
Timer mode and timer time  
Air flow Direction  
Swing  
Thermistor detected position  
01-12  
15. PUMP DOWN ( Refrigerant collecting operation )  
Perform the following procedures to collect the refrigerant when moving the indoor unit or the outdoor unit.  
When the product is stopped:  
1. Press the PUMP DOWN switch (SW2) on the outdoor unit.  
(The LED on the outdoor unit circuit board flickers every 1second.)  
2. The pump down operation (cooling operation) begins right away.  
After operation starts, close the 3-way valve (liquid).  
3. After 2-3minutes, operation stops. Close the 3-way valve (gas) within 1minute after operations stops.  
4. The LED will go out 3minutes after it stops. Disconnect the power supply after confirming that the LED has gone out.  
When the product is operating:  
1. Press the PUMP DOWN switch (SW2) on the outdoor unit. The LED on the outdoor unit circuit board flickers  
every 1second, and operation stops.  
At this point, recovery has not been completed, so do not close the 2 and 3-way valves.  
2. The pump down operation (cooling operation) begins after 3minutes.  
Close the 3-way valve (liquid) after operation starts.  
3. After 2-3minutes, operation stops. Close the 3-way valve (gas) within 1minute after operations stops.  
4. The LED will go out 3minutes after it stops. Disconnect the power supply after confirming that the LED has gone out.  
16. COMPRESSOR PREHEATING  
When the outdoor heat exchanger temperature is lower than Operation temperature (Refer to Table 8) and the heating  
operation has been stopped for 3 hours, power is applied to the compressor and the compressor is heated.  
(By heating the compressor, warm air is quickly discharged when operation is started.)  
When operation was started, and when the outdoor temperature rises to Release temperature or greater,  
preheating is over.  
(Table 8 : Preheating Operation / Release Temperature)  
Before 24 hour  
Operation Release  
temperature temperature temperature temperature  
After 24 hour  
Operation Release  
AUU18RCLX  
AUU24RCLX  
AUU36RCLX  
AUU42RCLX  
37.4°F  
(3°C)  
44.6°F  
(7°C)  
32°F  
(0°C)  
39.2°F  
(4°C)  
17. DEFROST OPERATION CONTROL  
1. CONDITION OF STARTING THE DEFROST OPERATION  
The defrost operation starts when the outdoor heat exchanger temperature sensor detects  
the temperature lower than the values shown in Table 9.  
(Table 9 : Condition of starting Defrost Operation)  
Compressor integrating  
operation :45min and over  
Outdoor temp. -  
Outdoor heat exchanger temp. exchanger temp.  
Outdoor heat  
Compressor integrating  
operation :Less than 45min.  
After 6 min. *1  
Less than 6 min. *1  
or 10min. *2  
or 10min. *2  
AUU18RCLX  
AUU24RCLX  
AUU36RCLX  
AUU42RCLX  
17.6°F(-8°C) *3  
14°F (-10°C) *4  
Does not operate  
21.6 degF (12 degC)  
- 4°F (-20°C)  
*1. It means contiguous operation time.  
*2. Compressor stop time: Below 20min.  
Above 20min.  
*3. Outdoor temp. > 30.2°F (-1°C)  
=
*4. Outdoor temp. < 30.2°F (-1°C)  
Select 6min.  
Select 10min.  
2. CONDITION OF THE DEFROST OPERATION COMPLETION  
Defrost operation is released when the conditions become as shown in Table 10.  
(Table 10 : Defrost Release Condition)  
Release Condition  
AUU18RCLX  
Outdoor heat exchanger temperature sensor value is higher than 53.6°F(12°C) or  
Compressor operation time has passed 15 minutes.  
AUU24RCLX  
AUU36RCLX  
AUU42RCLX  
01-13  
3. Defrost Flow Chart  
The defrosting shall proceed by the integrating operation time and outdoor heat exchanger temperature as follows.  
Heating operation start : Compressor ON  
(Not defrosted for 6 or 10 minutes)  
AUU42RCLX  
AUU18/ 24/ 36RCLX  
Compressor integrating  
Compressor integrating  
operation:  
operation:  
45 minutes and over  
45 minutes and over  
Outdoor temp. > 30.2°F  
Outdoor temp. < 30.2°F  
Outdoor temp. > 30.2°F  
=
Outdoor temp. < 30.2 F  
(-1°C)  
=
(-1°C)  
(-1°C)  
(-1°C)  
Outdoor heat exchanger  
temperarure:  
Outdoor heat exchanger  
temperarure:  
Outdoor heat exchanger  
temperarure:  
Outdoor heat exchanger  
temperarure:  
Below 17.6°F (-8°C)  
Below 14°F (-10°C)  
Below 17.6°F (-8°C)  
Below 14°F (-10°C)  
Outdoor temp -  
temperature:  
Outdoor heat exchanger  
temperarure:  
Below - 4°F (-20°C)  
Outdoor heat exchanger  
Above 21.6 degF (12 degC)  
Defrost start  
Defrost start  
Defrost Indicator:  
Defrost Indicator:  
[Operation lamp]  
[Operation lamp]  
9 sec ON / 1 sec OFF  
9 sec ON / 1 sec OFF  
Compressor : 30 Hz  
3 sec later Compressor OFF  
Outdoor fan motor OFF  
4-way valve OFF  
Compressor ON  
3 sec later Outdoor fan motor OFF  
28 sec later 4-way valve OFF  
34 sec later compressor ON  
(Frequency : 92 Hz)  
(Frequency : 92 Hz)  
Outdoor heat exchanger temperature: Over 53.6°F (12°C)  
or  
Compressor ON time: Over 15 minutes  
Defrost end  
01-14  
18. DRAIN PUMP OPERATION  
During Cooling / Dry operation  
1. When the compressor starts, the drain pump starts simultaneously.  
2. The drain pump operates continuously for 3 minutes after the compressor is turned off.  
3. When the compressor stops by the "Indoor heat exchanger de-icing function", the drain pump is turned off in 1 hour  
after the compressor stops.  
4.When the water level in the drain pan rises up and then the float switch functions:  
The compressor, indoor and outdoor fan motor operation are stopped.  
1
2 Drain pump operates continuously for 3 minutes after the float switch is turned off.  
(Almost condensing water may be drained)  
5. When the float switch turns ON continuously for 3 min., "FAILURE INDICATION" operates.  
6. When the float switch turns OFF within 3 min., the unit starts cooling operation.  
During Heating / Fan / Stop operation  
1.When the water level in the drain pan rises up and then the float switch functions:  
Drain pump operates continuously for 3 minutes after the float switch is turned off.  
(Almost condensing water may be drained)  
1
2. When the float switch turns ON continuously for 3 min., "FAILURE INDICATION" operates.  
19. ENERGY SAVE FUNCTION  
1. During Cooling / Dry operation:  
The thermostat temperature setting increases by 1.8 degF (1 degC) as soon as the ENERGY SAVE button is pressed,  
and then increases by 1.8 degF (1 degC) after 1 hour later.  
Afterwards, energy consumption is saved by continuing to cool or dry at a thermostat temperature of 3.6 degF (2 degC)  
higher than setting temperature.  
ENERGY  
SAVE ON  
1hour.  
3.6 degF (2 degC)  
1.8 degF  
(1 degC)  
Setting  
temperature  
2. During Heating operation:  
The thermostat temperature setting decreases by 1.8 degF (1 degC) as soon as the ENERGY SAVE button is pressed,  
and then decreases by another 1.8 degF (1 degC) every 30 minutes.  
Afterwards, energy consumption is saved by continuing to heat at a thermostat temperature of 7.2 degF (4 degC)  
lower than setting temperature.  
1.8degF 3.6degF 5.4degF 7.2degF  
(1degC) (2degC) (3degC) (4degC)  
Setting  
temperature  
ENERGY  
SAVE ON  
30min.  
1 hour.  
1 hour  
30 min.  
01-15  
20. VARIOUS PROTECTIONS  
1. DISCHARGE GAS TEMPERATURE OVER RISE PREVENTION CONTROL  
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas  
temperature.  
When the discharge temperature becomes higher than Temperature ,the compressor frequency  
is decreased 10 Hz, and it continues to decrease the frequency for 10 Hz every 120 seconds until  
the temperature becomes lower than Temperature .  
When the discharge temperature becomes lower than Temperature ,the control of the compressor  
frequency is released.  
When the discharge temperature becomes higher than Temperature ,the compressor stops.  
When the discharge temperature becomes lower than Temperature ,the compressor operates.  
(Table 11 : Discharge Temperature Over Rise Prevention Control / Release Temperature)  
Temperature  
Temperature  
Temperature  
Temperature  
AUU18RCLX  
AUU24RCLX  
AUU36RCLX  
AUU42RCLX  
221°F (105°C)  
212°F (100°C)  
239°F (115°C)  
176°F (80°C)  
2. CURRENT RELEASE CONTROL  
The compressor frequency is controlled so that the outdoor unit input current does not exceeds  
the current limit value that was set up with the outdoor temperature.  
The compressor frequency returns to the designated frequency of the indoor unit at the time  
when the frequency becomes lower than the release value.  
(Table 12 : Current Release Operation Value / Release Value)  
[ Heating ]  
AUU18RCLX  
Outdoor unit fan speed  
780 rpm  
400 rpm  
250 rpm  
220, 200 rpm  
6.0A / 5.5A  
T0 > 68°F (20°C)  
=
T0 < 68°F (20°C)  
10.0A / 9.5A  
12.0A / 11.5A  
10.0A / 9.5A  
8.0A / 7.5A  
T0: Outdoor temperature  
AUU24RCLX  
Outdoor unit fan speed  
900, 780 rpm  
10.0A / 9.5A  
12.0A / 11.5A  
400 rpm  
250 rpm  
220, 200 rpm  
6.0A / 5.5A  
T0 > 68°F (20°C)  
=
T0 < 68°F (20°C)  
10.0A / 9.5A  
8.0A / 7.5A  
T0: Outdoor temperature  
AUU36RCLX  
Outdoor unit fan speed  
400 rpm  
900 rpm  
780 rpm  
250 rpm  
220 ,200 rpm  
8.0A / 7.5A  
T0 > 53.6°F (12°C)  
=
15.0A / 14.5A 15.0A / 14.5A 13.0A / 12.5A 10.0A / 9.5A  
18.0A / 17.5A  
53.6°F > T0 > 41°F  
=
(12°C)  
(5°C)  
18.0A / 17.5A 18.0A / 17.5A 18.0A / 17.5A 18.0A / 17.5A  
T0 < 41°F (5°C)  
T0: Outdoor temperature  
01-16  
Outdoor unit fan speed  
AUU42RCLX  
Upper fan  
Lower fan  
900 ,850 ,780 ,350 rpm  
850 ,780 ,750 ,350 rpm  
20.0A / 19.5A  
200 rpm  
200 rpm  
170 rpm  
170 rpm  
150 rpm  
150 rpm  
T0 > 53.6°F (12°C)  
=
T0 < 53.6°F (12°C)  
15.0A / 14.5A 12.0A / 11.5A 12.0A / 11.5A  
20.0A / 19.5A 20.0A / 19.5A 20.0A / 19.5A  
20.0A / 19.5A  
T0: Outdoor temperature  
[ Cooling ]  
AUU18RCLX  
Outdoor unit fan speed  
400 rpm 250 rpm  
8.0A / 7.5A 5.0A / 4.5A  
780 rpm  
220, 200 rpm  
4.0A / 3.5A  
T0 > 113°F (45°C)  
=
8.0A / 7.5A  
113°F > T0 > 77°F  
=
10.0A / 9.5A  
(45°C)  
(25°C)  
77°F > T0 > 66.2°F  
=
12.0A / 11.5A 12.0A / 11.5A  
7.0A / 6.5A  
8.0A / 7.5A  
(25°C)  
(19°C)  
66.2°F > T0 > 55.4°F  
=
(19°C)  
(13°C)  
55.4°F > T0 > 44.6°F  
=
8.5A / 8.0A  
9.0A / 8.5A  
5.0A / 4.5A  
(13°C)  
(7°C)  
44.6°F > T0 > 32°F  
=
6.5A / 6.0A  
7.5A / 7.0A  
(7°C)  
(0°C)  
T0 < 32°F (0°C)  
T0: Outdoor temperature  
AUU24RCLX  
Outdoor unit fan speed  
900 ,850 rpm  
8.0A / 7.5A  
780 rpm  
400 rpm  
250 rpm  
220, 200 rpm  
4.0A / 3.5A  
T0 > 113°F (45°C)  
=
8.0A / 7.5A  
8.0A / 7.5A  
5.0A / 4.5A  
113°F > T0 > 100.4°F  
=
10.0A / 9.5A 10.0A / 9.5A  
12.0A / 11.5A  
(45°C)  
(38°C)  
100.4°F > T0 > 77°F  
=
(38°C)  
(25°C)  
77°F > T0 > 66.2°F  
=
12.0A / 11.5A 12.0A / 11.5A 7.0A / 6.5A  
8.0A / 7.5A  
(25°C)  
(19°C)  
66.2°F > T0 > 55.4°F  
=
(19°C)  
(13°C)  
55.4°F > T0 > 44.6°F  
=
8.5A / 8.0A  
9.0A / 8.5A  
5.0A / 4.5A  
6.5A / 6.0A  
(13°C)  
(7°C)  
44.6°F > T0 > 32°F  
=
(7°C)  
(0°C)  
7.5A / 7.0A  
T0 < 32°F (0°C)  
T0: Outdoor temperature  
01-17  
AUU36RCLX  
Outdoor unit fan speed  
780 rpm 400 rpm  
900 ,850 rpm  
250 rpm  
220, 200 rpm  
5.5A / 5.0A  
T0 > 113°F (45°C)  
=
10.0A / 9.5A 10.0A / 9.5A 10.0A / 9.5A  
14.0A / 13.5A 14.0A / 13.5A  
7.0A / 6.5A  
113°F > T0 > 100.4°F  
=
(45°C)  
(38°C)  
100.4°F > T0 > 66.2°F  
=
18.0A / 17.5A  
(38°C)  
(19°C)  
66.2°F > T0 > 55.4°F  
=
15.0A / 14.5A 15.0A / 14.5A  
7.0A / 6.5A  
9.5A / 9.0A  
(19°C)  
(13°C)  
55.4°F > T0 > 44.6°F  
=
12.0A / 11.5A  
(13°C)  
(7°C)  
44.6°F > T0 > 32°F  
=
(7°C)  
(0°C)  
T0 < 32°F (0°C)  
T0: Outdoor temperature  
Outdoor unit fan speed  
AUU42RCLX  
Upper fan  
850 rpm  
750 rpm  
780 rpm  
780 rpm  
350 rpm  
350 rpm  
400 rpm  
0 rpm  
350, 300 rpm  
0 rpm  
Lower fan  
T0 > 113°F (45°C)  
=
12.0A / 11.5A 12.0A / 11.5A 12.0A / 11.5A 12.0A / 11.5A 12.0A / 11.5A  
20.0A / 19.5A 20.0A / 19.5A  
113°F > T0 > 87.8°F  
=
(45°C)  
(31°C)  
87.8°F > T0 > 77°F  
=
18.0A / 17.5A  
18.0A / 17.5A  
(31°C)  
(25°C)  
77°F > T0 > 66.2°F  
=
(25°C)  
(19°C)  
66.2°F > T0 > 55.4°F  
=
15.0A / 14.5A  
18.0A / 17.5A  
20.0A / 19.5A  
(19°C)  
(13°C)  
T0 < 55.4°F (13°C)  
T0: Outdoor temperature  
01-18  
3. ANTI-FREEZING CONTROL (Cooling mode)  
The compressor frequency decreases on cooling mode when the indoor heat exchanger  
temperature sensor detects the temperature lower than 37.4°F (3°C).  
Then, the anti-freezing control is released when it becomes higher than 42.8°F (6°C).  
(Fig 10 : Anti-freezing Protection Operation / Release Temperature)  
Indoor heat exchanger  
temperature  
The compressor frequency is  
decreased 10Hz every 120seconds.  
37.4°F  
(3°C)  
Hold  
42.8°F  
(6°C)  
Compressor OFF : Hold  
Compressor ON : Release of protection  
53.6°F  
(12°C)  
Release of protection  
When the compressor frequency becomes lower than minimum frequency,  
the compressor operates at minimum frequency.  
If the indoor heat exchanger temperature sensor detects the temperature lower than  
37.4°F (3°C) after 2minutes upon operating the compressor at minimum frequency,  
the compressor stops.  
4. COOLING PRESSURE OVER RISE PROTECTION  
When the outdoor unit heat exchange sensor temperature rises to 158.9°F (70.5°C) or greater,  
the compressor is stopped and error display is indicated.  
5. HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )  
On heating mode, the compressor frequency is controlled as following based on the  
detection value of the indoor heat exchanger temperature sensor.  
(Fig 11 : Heating Overload Protection Control)  
Indoor heat exchange  
temperature  
Compressor is OFF  
145.4°F  
(63°C)  
The compressor frequency is  
decreased 10Hz every 60seconds.  
129.2°F  
(54°C)  
Hold  
122°F  
(50°C)  
Compressor OFF :  
Release of protection  
Compressor ON :  
The compressor frequency is  
increased 10Hz every 60seconds.  
01-19  
CASSETTE type  
INVERTER  
2 . TROUBLE SHOOTING  
2. TROUBLESHOOTING  
2-1 ERROR DISPLAY  
2-1-1 WIRED REMOTE CONTROLLER DISPLAY  
1. SELF - DIAGNOSIS  
When the error indication "E:EE" is displayed, inspection of the air conditioning system is necessary.  
Please consult authoilzed servise personnel.  
Run [Self-Diagnosis] if [E:EE] flashes on the clock display of the remote controller.  
Display  
Error code  
SU MO TU WE TH FR SA  
SU MO TU WE TH FR SA  
Ex. Self-diagnosis  
DAY  
D
CLOCK ADJUST  
SET BACK  
CLOCK ADJUST  
SET BACK  
DAY OFF  
D
ENERGY  
SAVE  
ENERGY  
SAVE  
THERMO  
SENSOR  
DELETE  
SET  
DELETE  
1. Stop the air conditioner operation.  
2. Press the SET TEMPERATURE buttons  
to start the self-diagnosis.  
and  
and  
simultaneously for 5 seconds or more  
simultaneously for 5 seconds or more  
3. Press the SET TEMPERATURE buttons  
or there is no key input for 20 seconds to stop the self-diagnosis.  
Trouble  
shooting  
Error contents  
Error code  
1
2
Communication error (indoor unit  
remote control)  
Communication error (Serial reverse transfer error)  
Room temperature sensor open  
3
Room temperature sensor short-circuited  
Indoor heat exchanger temperature sensor open  
Indoor heat exchanger temperature sensor short-circuited  
4
5
6
Outdoor heat exchanger temperature sensor error  
Water drain abnormal  
7
Outdoor temperature sensor error  
Outdoor discharge pipe temperature sensor error  
Indoor EEPROM abnormal (Model No.)  
Indoor fan motor abnormal  
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
Outdoor communication signal error (Forward transfer signal error)  
Compressor temperature sensor error  
Pressure switch error  
IPM error  
CT error  
Active filter module (AFM) error  
Compressor rotor location cannot detect (permanent stop)  
Outdoor unit fan motor error  
02-01  
2. ERROR CODE HISTORY DISPLAY  
Up to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.  
1. Stop the air conditioner operation.  
2. Press the SET TEMPERATURE buttons  
,
and the START/STOP button  
simultaneously  
for 5 seconds or more to start the self-diagnosis.  
SU MO TU WE TH FR SA  
D
3. Press the START/STOP button.  
Error code  
Error history number  
SU MO TU WE TH FR SA  
DAY  
4. Press the SET TEMPERATURE button to select the error history number.  
0
F
1
2
d
ı
3
c
4
b
5
6
9
7
8
DAY  
E
A
Lower Raise  
5. Press the SET TEMPERATURE buttons  
,
and START/STOP button  
simultaneously  
for 5 seconds or more or there is no key input for 20 seconds to stop the display.  
02-02  
2-1-2 OUTDOOR UNIT DISPLAY  
1. ERROR DISPLAY  
Error contents  
Display Trouble  
LED Flashing  
Pattern  
priority  
shooting  
Outdoor communication signal error  
(Forward transfer signal error)  
11  
1 time flash  
1
8
5
Outdoor discharge pipe temperature sensor error  
Outdoor heat exchanger temperature sensor error  
Outdoor temperature sensor error  
Compressor temperature sensor error  
Heat sink temperature sensor error  
Pressure switch abnormal  
2 times blink  
3 times blink  
4 times blink  
7 times blink  
8 times blink  
9 times blink  
12 times blink  
13 times blink  
14 times blink  
15 times blink  
16 times blink  
2
3
4
5
6
7
8
7
12  
19  
13  
14  
17  
20  
IPM error  
Compressor rotor location cannot detect  
Compressor Start-up error  
9
10  
11  
Outdoor unit fan motor error (upper fan)  
Outdoor unit fan motor error (lower fan)  
18  
12  
2. ERROR DISPLAY METHOD  
Outdoor LED Blink (1 to 16 times) 0.5sec ON / 0.5sec OFF blinking  
0.5sec 0.5sec 2sec  
ON  
OFF  
3. NORMAL OPERATION DISPLAY  
Operation  
Normal operation  
LED Blinking Pattern  
Continuously lighting  
5sec ON / 1sec OFF  
1sec ON / 1sec OFF  
Protected operation  
Pump down operation  
02-03  
2-2 TROUBLE SHOOTING WITH ERROR CODE  
Trouble shooting 1  
INDOOR UNIT Error Method:  
Indicate or Display:  
Indoor Unit : No LED  
Communication Error  
Outdoor Unit : No indication  
ERROR CODE : E : 00  
(Indoor unit  
Remote control)  
Detective details:  
Detective Actuators:  
When the indoor unit cannot receive the signal from Wired Remote  
more than 10seconds after power ON, or the indoor unit cannot receive  
the signal more than 1minute during normal operation.  
Indoor unit controller PCB circuit  
Wired Remote Control  
Forecast of Cause:  
1. Terminal connection abnormal 2. Wired Remote Control failure 3. Controller PCB failure  
Check Point 1 : Check the connection of terminal  
After turning off the power, check & correct the followings.  
Check the connection of terminal between remote control and Indoor unit,  
and check if there is a disconnection of the cable.  
OK  
Check Point 2 : Check Remote Control and Controller PCB  
Check Voltage at CN17 of Controller PCB. (Power supply to Remote Control)  
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal)  
>> Replace Remote Control  
>> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB  
Upon correcting the removed connector or mis-wiring, reset the power.  
02-04  
InnddiiccaatteeoorrDDisipslpalya:y:  
Indoor Unit : No LED  
Trouble shooting 2  
OUTDOOR UNIT Error Method:  
Outdoor Unit : No indication  
ERROR CODE : E : 01  
Communication Error  
(Serial Reverse Transfer Error)  
Detective details:  
Detective Actuators:  
When the indoor unit cannot receive the serial signal from Outdoor unit  
more than 10seconds.  
Outdoor Unit Main PCB Circuit  
Active Filter Module  
Forecast of Cause:  
1. Connection failure 2. External cause 3. Main PCB failure 4. Active Filter Module failure  
Check Point 1-1 : Reset the power and operate  
NO  
Does Error indication show again?  
YES  
Check Point 1-2:  
Check Point 2 : Check Connection  
Check external cause such as noise  
Check any loose or removed connection line of  
Check the complete insulation of the grounding.  
Indoor unit and Outdoor unit.  
Check if there is any equipment that causes harmonic wave  
near the power cable (Neon light bulb or any electronic  
equipment which causes harmonic wave).  
>> If there is an abnormal condition, correct it by  
referring to Installation Manual or Data &  
Technical Manual.  
Check connection between Outdoor Unit Main PCB  
and Filter PCB.  
(If there is loose connector or open cable)  
OK  
Check Point 3 : Check the voltage of power supply  
Check the voltage of power supply  
>> Check if AC208 - 230V appears at Outdoor Unit Terminal L - N.  
OK  
Check Point 4 : Check Serial Signal (Reverse Transfer Signal)  
Check Serial Signal (Reverse Transfer Signal)  
>> Check if Indicated value swings between AC70V and AC130V at Outdoor Unit Terminal 1 - 3.  
>> If it is abnormal, Check Active Filter Module. (PARTS INFORMATION 3)  
>>If Active Filter Module is abnormal, replace it.  
>>If Active Filter Module is normal, replace Main PCB.  
WHITE  
N
BLACK  
L
RED  
+
-
3
2
1
WHITE  
BLACK  
02-05  
Indicate or Display:  
Indoor Unit : No LED  
Outdoor Unit : No indication  
Trouble shooting 3  
INDOOR UNIT Error Method:  
INDOOR UNIT  
Room Temperature Sensor Error  
ERROR CODE : E : 02 / 03  
Detective details:  
Detective Actuators:  
When Room Temperature Thermistor open or short-circuit is  
detected at power ON.  
Indoor Unit Controller PCB Circuit  
Room Temperature Thermistor  
Forecast of Cause :  
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure  
Check Point 1 : Check connection of Connector  
Check if connector is removed.  
Check erroneous connection.  
Check if thermistor cable is open.  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
Chheecckk PPooiinntt 22 :: Remove connector and check Thermistor resistance value  
Thermistor Characteristics (Approx. value)  
Temperature  
32°F  
41°F  
50°F  
59°F  
68°F  
77°F  
86°F  
95°F  
(0°C)  
(5°C) (10°C) (15°C) (20°C) (25°C) (30°C) (35°C)  
Resistance Value (k  
Temperature  
)
33.6  
25.9 20.2 15.8 12.5 10.0 8.04 6.51  
104°F 113°F 122°F  
(40°C) (45°C) (50°C)  
Resistance Value (k  
)
5.30  
4.35  
3.59  
If Thermistor is either open or shorted, replace it and reset the power.  
OK  
Chheecckk PPooiinntt 33 :: Check voltage of Controller PCB (DC5.0V)  
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)  
THERMISTOR  
(PIPE TEMP.)  
THERMISTOR  
(ROOM TEMP.)  
1 2 1 2  
1 2 1 2  
CN7 CN8  
If the voltage does not appear, replace Controller PCB.  
02-06  
Indicate or Display:  
Indoor Unit : No LED  
Outdoor Unit : No indication  
Trouble shooting 4  
INDOOR UNIT Error Method:  
INDOOR UNIT  
Indoor Heat Exchanger Temperature  
Sensor Error  
ERROR CODE : E : 04 / 05  
Detective Actuators:  
Detective details:  
When Heat Exchanger Temperature Thermistor open or short-circuit is  
detected at power ON.  
Indoor Unit Controller PCB Circuit  
Heat Exchanger Temperature Thermistor  
Forecast of Cause :  
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure  
Check Point 1 : Check connection of Connector  
Check if connector is removed.  
Check erroneous connection.  
Check if thermistor cable is open.  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
Chheecckk PPooiinntt 22 :: Remove connector and check Thermistor resistance value  
Thermistor Characteristics (Approx. value)  
Temperature  
32°F  
41°F  
50°F  
59°F  
68°F  
77°F  
86°F  
95°F  
(0°C)  
(5°C) (10°C) (15°C) (20°C) (25°C) (30°C) (35°C)  
Resistance Value (k  
Temperature  
)
176  
134 103 80.3 62.9 49.7 39.6 31.7  
104°F 113°F 122°F  
(40°C) (45°C) (50°C)  
Resistance Value (k  
)
25.6  
20.8  
17.1  
If Thermistor is either open or shorted, replace it and reset the power.  
OK  
Check Point 3 : Check voltage of Controller PCB (DC5.0V)  
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)  
THERMISTOR  
(PIPE TEMP.)  
THERMISTOR  
(ROOM TEMP.)  
1 2 1 2  
1 2 1 2  
CN7 CN8  
If the voltage does not appear, replace Controller PCB.  
02-07  
Indicate or Display:  
Indoor Unit : No LED  
Trouble shooting 5  
OUTDOOR UNIT Error Method:  
Outdoor Unit : LED 3 times blink  
Outdoor Heat Exchanger Temperature  
Sensor Error  
ERROR CODE : E : 06  
Detective Actuators:  
Detective details:  
Outdoor Unit Main PCB Circuit  
Heat Exchanger Temperature Thermistor  
When Heat Exchanger Temperature Thermistor open or short-circuit is  
detected at power ON or while running the compressor.  
Forecast of Cause :  
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure  
Check Point 1 : Check connection of Connector  
Check if connector is removed.  
Check erroneous connection.  
Check if thermistor cable is open.  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
CChheeckk PPooiinntt 22 :: Remove connector and check Thermistor resistance value  
Thermistor Characteristics (Approx. value)  
Temperature  
14°F 23°F 32°F 41°F 50°F 59°F 68°F 77°F 86°F  
(-10°C) (-5°C) (0°C) (5°C) (10°C) (15°C) (20°C) (25°C) (30°C)  
3.95  
Resistance Value (k  
)
27.5 20.9 16.1 12.4  
9.73 7.67 6.10  
4.89  
If Thermistor is either open or shorted, replace it and reset the power.  
OK  
Check Point 3 :  
Check Point 3 : Check voltage of Main PCB (DC5.0V)  
DC  
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)  
1 2  
1 2  
1 2  
1 2  
1 2  
CN21  
CN22 CN23  
CN26  
CN25  
If the voltage does not appear, replace Main PCB.  
02-08  
Indicate or Display:  
Indoor Unit : No LED  
Outdoor Unit : No indication  
Trouble shooting 6  
INDOOR UNIT Error Method:  
Water Drain Abnormal  
ERROR CODE : E : 09  
Detective Actuators:  
Detective details:  
Indoor Unit Controller PCB Circuit  
Float Switch  
When Float Switch is ON for more than 3 minutes.  
Forecast of Cause :  
1. Float Switch failure 2. Shorted connector/ wire 3. Controller PCB failure  
Check Point 1 : Check Float Switch  
Check operation of float switch. (any blocking by dust, etc.)  
ON  
OFF  
Remove Float switch and check ON/OFF switching operation  
by using a meter.  
>>If Float switch is detective, replace it.  
OK  
Chheecckk PPooiinntt 22 :: Check Connector (CN15) / Wire  
Check loose contact of CN15 /shorted wire (pinched wire).  
>>Replace Float switch if the wire is abnormal  
OK  
Check Point 3 : Replace Controller PCB  
If Check Point 1 & 2 do not improve the symptom, change Controller PCB.  
02-09  
Indicate or Display:  
Indoor Unit : No LED  
Trouble shooting 7  
OUTDOOR UNIT Error Method:  
INDOOR UNIT  
Outdoor Unit : LED 4 times blink  
ERROR CODE : E : 0A  
Outdoor Temperature Sensor Error  
Detective Actuators:  
Detective details:  
When Outdoor Temperature Thermistor open or short-circuit is  
detected at power ON or while running the compressor.  
Outdoor Unit Main PCB Circuit  
Outdoor Temperature Thermistor  
Forecast of Cause :  
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure  
Check Point 1 : Check connection of Connector  
Check if connector is removed.  
Check erroneous connection.  
Check if thermistor cable is open.  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
CChheeckk PPooiinntt 22 :: Remove connector and check Thermistor resistance value  
Thermistor Characteristics (Approx. value)  
Temperature  
- 4°F  
14°F  
23°F  
32°F  
41°F  
50°F  
59°F  
68°F  
(-20°C) (-10°C) (-5°C)  
(0°C)  
(5°C) (10°C) (15°C) (20°C)  
Resistance Value (k  
Temperature  
)
115  
62.3  
46.6  
35.2  
26.9 20.7 16.1 12.6  
86°F  
(30°C)  
104°F 122°F 140°F 158°F  
(40°C) (50°C) (60°C) (70°C)  
Resistance Value (k  
)
7.97  
5.18  
3.45  
2.36  
1.65  
If Thermistor is either open or shorted, replace it and reset the power.  
OK  
Check Point 3 :  
Check Point 3 : Check voltage of Main PCB (DC5.0V)  
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)  
1 2  
1 2  
1 2  
1 2  
1 2  
CN21  
CN22 CN23  
CN26  
CN25  
If the voltage does not appear, replace Main PCB.  
02-10  
Indicate or Display:  
Indoor Unit : No LED  
Outdoor Unit : LED 2 times blink  
Trouble shooting 8  
OUTDOOR UNIT Error Method:  
INDOOR UNIT  
Outdoor Discharge Pipe Temperature  
Sensor Error  
ERROR CODE : E : 0C  
Detective details:  
Detective Actuators:  
When Discharge Pipe Temperature Thermistor open or short-circuit  
is detected at power ON or while running the compressor.  
Outdoor Unit Main PCB Circuit  
Discharge Pipe Temperature Thermistor  
Forecast of Cause :  
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure  
Check Point 1 : Check connection of Connector  
Check if connector is removed.  
Check erroneous connection.  
Check if thermistor cable is open.  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
CChheeckk PPooiinntt 22 :: Remove connector and check Thermistor resistance value  
Thermistor Characteristics (Approx. value)  
Temperature  
32°F 41°F 50°F 59°F 68°F 86°F 104°F 122°F 140°F  
(0°C) (5°C) (10°C) (15°C) (20°C) (30°C) (40°C) (50°C) (60°C)  
12.5  
Resistance Value (k  
Temperature  
)
176  
135  
105  
81.8  
64.5 41.1 26.9 18.1  
158°F 176°F 194°F 212°F 248°F 284°F 320°F 356°F  
(70°C) (80°C) (90°C) (100°C) (120°C) (140°C) (160°C) (180°C)  
Resistance Value (k  
)
8.78 6.31 4.61 3.43 1.98  
1.21 0.77 0.51  
If Thermistor is either open or shorted, replace it and reset the power.  
OK  
Check Point 3 :  
Check Point 3 : Check voltage of Main PCB (DC5.0V)  
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)  
1 2  
1 2  
1 2  
1 2  
1 2  
CN21  
CN22 CN23  
CN26  
CN25  
If the voltage does not appear, replace Main PCB.  
02-11  
Indicate or Display:  
Indicate or Display:  
Trouble shooting 9  
INDOOR UNIT Error Method:  
Indoor Unit  
: No LED  
Outdoor Unit : No indication  
ERROR CODE : E : 11  
Indoor EEPROM abnormal  
(Model No.)  
Detective details:  
Detective Actuators:  
When the model information being read from EEPROM has  
an apparent error.  
Indoor Unit Controller PCB circuit  
Forecast of Cause:  
1. External cause 2. Defective connection of electric components 3. Controller PCB failure  
Check Point 1-1 : Reset Power Supply and operate  
NO  
Does Error indication show again?  
YES  
Check Point 1-2 :  
Check external cause at Indoor and Outdoor  
Check Point 2 :  
Check Indoor Unit electric components  
(Voltage drop or Noise)  
Check all connectors.  
(loose connector or incorrect wiring)  
Instant drop : Check if there is a large load electric apparatus  
in the same circuit.  
Check any shortage or corrosion on PCB.  
Momentary power failure : Check if there is a defective contact  
or leak current in the power supply  
circuit.  
Noise : Check if there is any equipment causing harmonic  
wave near electric line.(Neon bulb or electric  
equipment that may cause harmonic wave)  
Check the complete insulation of grounding.  
Check Point 3 : Replace Controller PCB  
Change Controller PCB.  
Note : EEPROM  
EEPROM(Electronically Erasable and  
Programmable Read Only Memory) is a non-  
volatile memory which keeps memorized  
information even if power is turned off. It can  
change the contents electronically.  
To change the contents, it uses higher  
voltage than normal, and it can not change a  
partial contents. (Rewriting shall be done  
upon erasing the all contents.)  
There is a limit in a number of rewriting.  
02-12  
Indicate or Display:  
Indoor Unit : No LED  
Trouble shooting 10  
INDOOR UNIT Error Method:  
Outdoor Unit : No indication  
ERROR CODE : E : 12  
Indoor Fan Motor abnormal  
Detective Actuators:  
Detective details:  
Indoor Unit Controller PCB Circuit  
Indoor Fan Motor  
When the condition that actual frequency of Indoor Fan is  
below 1/3 of target frequency is continued more than 56 seconds.  
Forecast of Cause:  
1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temperature rise  
4. Capacitor failure 5. Control PCB failure  
Check Point 1 : Check rotation of Fan  
Rotate the fan by hand when operation is off.  
(Check if fan is caught, dropped off or locked motor)  
>>If Fan or Bearing is abnormal, replace it.  
OK  
Check Point 2 : Check Motor winding  
Check Indoor Fan motor. (PARTS INFORMATION 5)  
>>If Fan motor is abnormal, replace it.  
OK  
Check Point 3 : Check ambient temp. around motor  
Check excessively high temperature around the motor.  
(If there is any surrounding equipment that causes heat)  
>>Upon the temperature coming down, restart operation.  
OK  
Check Point 4 : Check Motor Capacitor  
Check continuity of motor capacitor  
>>If it is shorted, replace the capacitor.  
Check Point 5 : Check Output Voltage of Control PCB  
Check indoor unit circuit diagram  
and the output voltage (between 2 (White) and 3 (Red)) of CN5.  
AUU18RCLX : 77% of Input AC voltage (Cooling, Airflow[HIGH])  
73% of Input AC voltage (Heatling, Airflow[HIGH])  
AUU24RCLX : 93% of Input AC voltage (Cooling, Airflow[HIGH])  
81% of Input AC voltage (Heatling, Airflow[HIGH])  
AUU36RCLX : 91% of Input AC voltage (Cooling, Airflow[HIGH])  
91% of Input AC voltage (Heatling, Airflow[HIGH])  
AUU42RCLX : 98% of Input AC voltage (Cooling, Airflow[HIGH])  
98% of Input AC voltage (Heatling, Airflow[HIGH])  
If the voltage is not correct, replace Controller PCB.  
02-13  
InnddiiccaatteeoorrDDisipslpalya:y:  
Trouble shooting 11  
INDOOR UNIT Error Method:  
Indoor Unit  
: No LED  
Outdoor Communication Signal Error  
(Forward Transfer Signal Error)  
Outdoor Unit : LED 1 time blink  
ERROR CODE : E : 13  
Detective details:  
Detective Actuators:  
Indoor Unit Controller PCB Circuit  
When the outdoor unit cannot receive the serial signal from Indoor unit  
more than 10seconds.  
Forecast of Cause:  
1. Connection failure 2. External cause 3. Controller PCB failure  
Check Point 1-1 : Reset the power  
NO  
Does Error indication reappear?  
YES  
Check Point 1-2:  
Check Point 2 : Check Connection  
Check external cause such as noise  
Check any loose or removed connection line of  
Indoor unit and Outdoor unit.  
>> If there is an abnormal condition, correct it by  
referring to Installation Manual or Data &  
Technical Manual.  
Check the complete insulation of the grounding.  
Check if there is any equipment that causes harmonic wave  
near the power cable (Neon light bulb or any electronic  
equipment which causes harmonic wave).  
Check connection between Indoor Unit Controller PCB  
and Filter PCB.  
(If there is loose connector or open cable)  
OK  
Check Point 3 : Check the voltage of power supply  
Check the voltage of power supply  
>> Check if AC208 - 230V appears at Outdoor Unit Terminal L - N.  
OK  
Check Point 4 : Check Serial Signal (Forward Transfer Signal)  
Check Serial Signal (Forward Transfer Signal)  
>> Check if Indicated value swings between AC70V and AC130V at Outdoor Unit Terminal 2 - 3.  
>> If it is abnormal, Controller PCB is failure. >> Replace Controller PCB  
WHITE  
N
BLACK  
L
+
-
RED  
3
2
1
WHITE  
BLACK  
02-14  
Indicate or Display:  
Indoor Unit : No LED  
Outdoor Unit : LED 7 times blink  
Trouble shooting 12  
OUTDOOR UNIT Error Method:  
Compressor Temperature Sensor Error  
ERROR CODE : E : 15  
Detective Actuators:  
Detective details:  
When Compressor Temperature Thermistor open or short-circuit is  
detected at power ON or while running the compressor.  
Outdoor Unit Main PCB Circuit  
Compressor Temperature Thermistor  
Forecast of Cause :  
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure  
Check Point 1 : Check connection of Connector  
Check if connector is removed.  
Check erroneous connection.  
Check if thermistor cable is open.  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
CChheeckk PPooiinntt 22 :: Remove connector and check Thermistor resistance value  
Thermistor Characteristics (Rough value)  
Temperature  
32°F 41°F 50°F 59°F 68°F 86°F 104°F 122°F 140°F  
(0°C) (5°C) (10°C) (15°C) (20°C) (30°C) (40°C) (50°C) (60°C)  
12.5  
Resistance Value (k  
Temperature  
)
176  
135  
105  
81.8  
64.5 41.1 26.9 18.1  
158°F 176°F 194°F 212°F 248°F 284°F 320°F 356°F  
(70°C) (80°C) (90°C) (100°C) (120°C) (140°C) (160°C) (180°C)  
Resistance Value (k  
)
8.78 6.31 4.61 3.43 1.98  
1.21 0.77 0.51  
If Thermistor is either open or shorted, replace it and reset the power.  
OK  
Check Point 3 :  
Check Point 3 : Check voltage of Main PCB (DC5.0V)  
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)  
1 2  
1 2  
1 2  
1 2  
1 2  
CN21  
CN22 CN23  
CN26  
CN25  
If the voltage does not appear, replace Main PCB.  
02-15  
Indicate or Display:  
Indicate or Display:  
Trouble shooting 13  
OUTDOOR UNIT Error Method:  
INDOOR UNIT  
Indoor Unit  
: No LED  
Outdoor Unit : LED 9 times blink  
Pressure Switch Error  
ERROR CODE : E : 16  
Detective details:  
Detective Actuators:  
When pressure switch open is detected in 10 seconds  
after the power is turned on.  
Outdoor Unit Main PCB Circuit  
Pressure Switch  
Forecast of Cause :  
1. Connector connection failure 2. Pressure Switch failure 3. Main PCB failure  
Check Point 1 : Reset Power Supply and operate  
NO  
Does abnormal LED indication show again?  
YES  
Chheecckk PPooiinntt 32 :: Check voltage of Main PCB (DC5.0V)  
Make sure circuit diagram of outdoor unit and check terminal voltage  
at Pressure Switch. (DC5.0V)  
HIGH PRESSURE SW  
RED  
1
RED  
CN37  
2
BLACK  
BLACK  
1
2
3
4WV  
If the voltage does not appear, replace Main PCB.  
OK  
Check Point 3 : Check Pressure Switch  
Check if connector is loose or cable is open.  
>> If no abnormal connection is found,  
replace Pressure Switch.  
After replacing Pressure Switch, check operating  
condition and pressure in operation.  
02-16  
Indicate or Display:  
Trouble shooting 14  
Indoor Unit  
: No LED  
OUTDOOR UNIT Error Method:  
Outdoor Unit : LED 12 times blink  
ERROR CODE : E : 17  
IPM error (Permanent Stop)  
Detective details:  
Detective Actuators:  
When more than normal operating current to IPM in Main PCB flows,  
the compressor stops.  
After the compressor restarts, if the same operation is repeated within 40sec,  
the compressor stops again.  
Outdoor Unit Main PCB Circuit  
Compressor  
If  
and  
repeats 5 times, the compressor stops permanently.  
Forecast of Cause :  
1. Defective connection of electric components 2. Outdoor Fan Operation failure  
3. Outdoor Heat Exchanger clogged 4. Compressor failure  
5. Main PCB failure  
Check Point 1 : Check connections of Outdoor Unit Electrical Components  
Check if the terminal connection is loose.  
Check if connector is removed.  
Check erroneous connection.  
Check if cable is open.  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
Check Point 2 : Check Outdoor Fan, Heat Exchanger  
Is there anything obstructing the air distribution circuit?  
Is there any clogging of Outdoor Heat Exchanger?  
Is the Fan rotating by hand when operation is off ?  
>> If the Fan Motor is locked, replace it.  
Check Outdoor Fan Motor. (Refer to Trouble shooting 18)  
>> If the Fan Motor is failure, replace it.  
OK  
Check Point 3 : Check Compressor  
Check Compressor. (PARTS INFORMATION 2)  
OK  
Check Point 4 : Replace Main PCB  
If Check Point 1, 2, 3 do not improve the symptom, change Main PCB.  
02-17  
Indicate or Display:  
Trouble shooting 15  
Indoor Unit  
: No LED  
OUTDOOR UNIT Error Method:  
Outdoor Unit : No indication  
ERROR CODE : E : 18  
CT error  
Detective details:  
Detective Actuators:  
Outdoor Unit Main PCB Circuit  
Outdoor Unit Filter PCB Circuit  
(Input current sensor unit)  
When Input Current Sensor has detected lower than 0.5A  
while Inverter Compressor is operating at higher than 56Hz,  
after 1minute upon starting the Compressor.  
(Except during the defrost operation)  
Forecast of Cause :  
1. Defective connection of electric components 2. External cause 3. Filter PCB failure 4. Main PCB failure  
Check Point 1-1 : Reset Power Supply and operate  
NO  
Does Error indication show again?  
YES  
Check Point 2 :  
Check Point 1-2 :  
Check connections of Outdoor Unit Electrical Components  
Check external cause at Indoor and Outdoor  
(Voltage drop or Noise)  
Check if the terminal connection is loose.  
Check if connector is removed.  
Check erroneous connection.  
Check if cable is open.  
>>Upon correcting the removed connector or mis-wiring,  
reset the power.  
Instant drop : Check if there is a large load electric  
apparatus in the same circuit.  
Momentary power failure : Check if there is a defective  
contact or leak current in the  
power supply circuit.  
Noise : Check if there is any equipment causing harmonic  
wave near electric line.(Neon bulb or electric  
equipment that may cause harmonic wave)  
Check the complete insulation of grounding.  
OK  
Check Point 3 : Check Filter PCB and Main PCB  
Check DC voltage of CN1 (between 2 (Brown) and 3 (Red)) on Filter PCB.  
>> After 40seconds upon starting the Compressor,  
If it is higher than 0.2V, Main PCB is failure. (Filter PCB is normal) >> Replace Main PCB  
>> If it is lower than 0.2V, Filter PCB is failure.  
>> Replace Filter PCB  
If it does not improve the symptom, change Main PCB.  
02-18  
Indicate or Display:  
Indoor Unit : No LED  
Outdoor Unit : No indication  
ERROR CODE : E : 19  
Trouble shooting 16  
OUTDOOR UNIT Error Method:  
INDOOR UNIT  
Active Filter Module (AFM) error  
Detective details:  
Detective Actuators:  
Outdoor Unit Main PCB Circuit  
Active Filter Module  
When inverter input DC voltage is higher than 467V or  
lower than 237V.  
When a momentary power cut off occurred on low voltage.  
Forecast of Cause :  
1. External cause 2. Connector connection failure 3. Active Filter Module failure˴㧠. Main PCB failure  
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)  
Instant drop : Check if there is a large load electric apparatus in the same circuit.  
Momentary power failure : Check if there is a defective contact or leak current  
in the power supply circuit.  
Noise : Check if there is any equipment causing harmonic wave near electric line.  
(Neon bulb or electric equipment that may cause harmonic wave)  
Check the complete insulation of grounding.  
OK  
Check Point 2 : Check connection of Connector  
Check if connector is removed.  
Check erroneous connection.  
Check if cable is open.  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
Check Point 3 : Check Active Filter Module  
Check Active Filter Module. (PARTS INFORMATION 3)  
>>If Active Filter Module is abnormal, replace it.  
OK  
Check Point 4 : Replace Main PCB  
If Check Point 1, 2 do not improve the symptom, change Main PCB.  
02-19  
InnddiiccaatteeoorrDDisipslpalya:y:  
Trouble shooting 17  
Indoor Unit  
: No LED  
OUTDOOR UNIT Error Method:  
Outdoor Unit : LED 13 times blink  
ERROR CODE : E : 1A  
Compressor rotor location cannot detect  
(Permanent Stop)  
Detective details:  
Detective Actuators:  
While running the compressor, if the detected rotor location is out of  
phase with actual rotor location more than 90 degrees,  
the compressor stops.  
Outdoor Unit Main PCB Circuit  
After the compressor restarts, if the same operation is repeated  
within 40sec, the compressor stops again.  
If  
and  
repeats 5 times, the compressor stops permanently.  
Forecast of Cause :  
1. Defective connection of electric components 2. Main PCB failure  
Check Point 1 : Check connection of around the Compressor components  
For Compressor Terminal, Main PCB  
Check if connector is removed.  
Check erroneous connection.  
Check if cable is open.  
(Refer to PARTS INFORMATION 2)  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
Check Point 2 : Replace Main PCB  
If Check Point 1 do not improve the symptom, change Main PCB.  
02-20  
Indicate or Display:  
Indoor Unit : No LED  
Trouble shooting 18  
OUTDOOR UNIT Error Method:  
Outdoor Unit : LED 15 (Fan motor 1)/ 16(Fan motor 2) times blink  
ERROR CODE : E : 1b  
Outdoor Unit Fan Motor Error  
Detective Actuators:  
Detective details:  
When outdoor fan rotation speed is less than 100rpm in 20 seconds  
after fan motor starts, fan motor stops.  
After fan motor restarts, if the same operation within 60sec is repeated  
3 times in a row, compressor and fan motor stops.  
Outdoor Unit Main PCB Circuit  
Outdoor Fan Motor  
If  
and  
repeats 5 times in a row, compressor and fan motor stops  
permanently.  
Forecast of Cause:  
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Main PCB failure  
Check Point 1 : Check rotation of Fan  
Rotate the fan by hand when operation is off.  
(Check if fan is caught, dropped off or locked motor)  
>>If Fan or Bearing is abnormal, replace it.  
OK  
Check Point 2 : Check ambient temp. around motor  
Check excessively high temperature around the motor.  
(If there is any surrounding equipment that causes heat)  
>>Upon the temperature coming down, restart operation.  
OK  
Check Point 3 : Check Output Voltage of Main PCB  
Check outdoor unit circuit diagram and the voltage. (Measure at Main PCB side connector)  
AUU18/ 24/ 36RCLX  
AUU42RCLX  
FAN MOTOR 1  
FM  
FAN MOTOR 1  
FM  
RED  
RED  
1
1
2
3
4
5
6
2
BLACK  
WHITE  
YELLOW  
BLUE  
BLACK  
WHITE  
YELLOW  
BLUE  
CN802  
CN803  
CN802  
3
4
5
6
FAN MOTOR 2  
FM  
RED  
1
2
3
4
5
6
Read wire  
DC voltage  
BLACK  
WHITE  
YELLOW  
BLUE  
Red - Black  
White - Black  
150380V  
15 1.5V  
If the voltage is not correct, replace Main PCB.  
02-21  
Indicate or Display:  
Indoor Unit : No LED  
Trouble shooting 19  
OUTDOOR UNIT Error Method:  
Outdoor Unit : LED 8 times blink  
ERROR CODE : No indication  
Heat Sink Temperature Sensor Error  
Detective details:  
Detective Actuators:  
When Heat Sink Temperature Thermistor open or short-circuit is  
detected at power ON or while running the compressor.  
Outdoor Unit Main PCB Circuit  
Heat Sink Temperature Thermistor  
Forecast of Cause :  
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure  
Check Point 1 : Check connection of Connector  
Check if connector is removed.  
Check erroneous connection.  
Check if thermistor cable is open.  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
CChheeckk PPooiinntt 22 :: Remove connector and check Thermistor resistance value  
Thermistor Characteristics (Approx. value)  
Temperature  
32°F  
(0°C)  
41°F  
50°F  
59°F  
68°F  
86°F  
104°F 122°F  
(40°C) (50°C)  
(5°C) (10°C) (15°C) (20°C) (30°C)  
Resistance Value (k  
Temperature  
)
16.1  
12.4 9.73 7.67 6.10  
3.95  
2.62  
1.79  
140°F 158°F 176°F 194°F 212°F 230°F 248°F  
(60°C) (70°C) (80°C) (90°C) (100°C) (110°C) (120°C)  
Resistance Value (k  
)
1.25  
0.89  
0.65  
0.48  
0.36  
0.27  
0.21  
If Thermistor is either open or shorted, replace it and reset the power.  
OK  
Check Point 3 :  
Check Point 3 : Check voltage of Main PCB (DC5.0V)  
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)  
1 2  
1 2  
1 2  
1 2  
1 2  
CN21  
CN22 CN23  
CN26  
CN25  
If the voltage does not appear, replace Main PCB.  
02-22  
Indicate or Display:  
Trouble shooting 20  
Indoor Unit  
: No LED  
OUTDOOR UNIT Error Method:  
Compressor Start-up error  
(Permanent Stop)  
Outdoor Unit : LED 14 times blink  
ERROR CODE : No indication  
Detective Actuators:  
Detective details:  
On start-up the compressor, when detected rotor position is out of phase  
with actual rotor position more than 90 degrees,the compressor stops.  
After the compressor restarts, if the same operation is repeated  
within 40sec, the compressor stops again.  
Outdoor Unit Main PCB Circuit  
If  
and  
repeats 5 times, the compressor stops permanently.  
Forecast of Cause :  
1. Defective connection of electric components 2. Main PCB failure  
Check Point 1 : Check connection of around the Compressor components  
For Compressor Terminal, Main PCB  
Check if connector is removed.  
Check erroneous connection.  
Check if cable is open.  
(Refer to PARTS INFORMATION 2)  
>>Upon correcting the removed connector or mis-wiring, reset the power.  
OK  
Check Point 2 : Replace Main PCB  
If Check Point 1 do not improve the symptom, replace Main PCB.  
02-23  
2-3 TROUBLE SHOOTING WITH NO ERROR CODE  
Forecast of Cause:  
Trouble shooting 21  
1. Power Supply failure 2. External cause  
3. Electrical Components defective  
Indoor Unit - No Power  
Check Point 1 : Check Installation Condition  
Isn’t the breaker down?  
Check loose or removed connection cable.  
>>If abnormal condition is found, correct it by referring  
to Installation Manual or Data & Technical Manual.  
OK  
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)  
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.  
Momentary power failure ----- Check if there is a defective contact or leak current in  
the power supply circuit.  
Noise ----- Check if there is any equipment causing harmonic wave near electric line.  
(Neon bulb or electric equipment that may cause harmonic wave)  
Check the complete insulation of grounding.  
OK  
Check Point 3 : Check Electrical Components  
NO  
Check Voltage of power supply.  
>> Check AC208 - 230V appears at Indoor Unit Terminal 1 - 2 (Power Supply).  
YES  
Check Fuse (F101) in Filter PCB.  
>> If Fuse is open, check if the wiring between Terminal and Filter PCB  
is loose, and replace Fuse.  
Check Varistor (VA101, VA102) in Filter PCB.  
>> If Varistor is defective, there is a possibility of an abnormal power supply.  
Check the correct power supply and replace Varistor.  
OK  
If the symptom does not change by above Check3, replace Filter PCB.  
02-24  
Forecast of Cause:  
Trouble shooting 22  
1. Power Supply failure 2. External cause  
3. Electrical Components defective  
Outdoor Unit - No Power  
Check Point 1 : Check Installation Condition  
Isn’t the breaker down?  
Check loose or removed connection cable.  
>>If abnormal condition is found, correct it by referring  
to Installation Manual or Data & Technical Manual.  
OK  
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)  
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.  
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.  
Noise ----- Check if there is any equipment causing harmonic wave near electric line.  
(Neon bulb or electric equipment that may cause harmonic wave)  
Check the complete insulation of grounding.  
OK  
Check Point 3 : Check Electrical Components  
NO  
Check the voltage of power supply.  
>> Check if AC208 - 230V appears at Outdoor Unit Terminal L - N.  
YES  
Check Fuse (F2, F4) in Main PCB.  
>> If Fuse is open, check loose terminal or removed connector (CN1) , and replace Fuse.  
Check Varistor in Main PCB (VA103).  
>> If Varistor is defective, there is a possibility of an abnormal power supply.  
Check the correct power supply and replace Varistor.  
Upon checking the normal power supply, replace Varistor.  
YES  
Check Active Filter Module. (PARTS INFORMATION 3)  
>>If Active Filter Module is abnormal, replace it.  
OK  
If the symptom does not change by above Check 3, replace Main PCB.  
02-25  
Forecast of Cause:  
Trouble shooting 23  
1. Setting/ Connection failure 2. External cause  
3. Electrical Component defective  
No Operation (Power is ON)  
Check Point 1 : Check indoor and outdoor installation condition  
Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control, or terminals between Indoor Units.  
Or, check if there is an open cable connection.  
Are these Indoor Unit, Outdoor Unit, and Remote Control suitable model numbers to connect?  
>> If there is some abnormal condition, correct it by referring to Installation manual and  
Data & Technical Manual.  
OK  
Turn off Power and check/ correct followings.  
Is there loose or removed communication line of Indoor Unit and Outdoor Unit?  
OK  
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)  
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.  
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.  
Noise ----- Check if there is any equipment causing harmonic wave near electric line.  
(Neon bulb or electric equipment that may cause harmonic wave)  
Check the complete insulation of grounding.  
OK  
Check Point 3 : Check Electrical Components at Indoor and Outdoor  
Check Voltage at CN17 of Controller PCB. (Power supply to Remote Control)  
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal)  
>> Replace Remote Control  
>> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB  
>> If the symptom does not change by above Check 1, 2, 3, replace Main PCB of Outdoor unit.  
02-26  
Forecast of Cause:  
Trouble shooting 24  
1. Indoor Unit error 2. Outdoor Unit error  
3. Effect by Surrounding environment  
No Cooling / No Heating  
4. Connection Pipe / Connection Wire failure 5. Refrigeration cycle failure  
Check Point 1 : Check Indoor Unit  
Does Indoor Unit FAN run on HIGH FAN?  
Is Air Filter dirty?  
Is Heat Exchanger clogged?  
Check if Energy save function is operated.  
OK  
Check Point 2 : Check Outdoor Unit Operation  
Check if Outdoor Unit is operating  
(If not, refer to Trouble shooting 23)  
Check any objects that obstruct the air flow route.  
Check clogged Heat Exchanger.  
Is the Valve open?  
OK  
Attention  
Check Point 3 : Check Site Condition  
Strainer normally does not have temperature difference  
between inlet and outlet as shown in , but if there is a  
difference like shown in , there is a possibility of inside  
clogged. In this case, replace Strainer.  
Is capacity of Indoor Unit fitted to Room size?  
Any windows open? Or direct sunlight ?  
OK  
Pipe (In)  
Pipe (Out)  
Check Point 4 :  
Check Indoor/ Outdoor Installation Condition  
Check connection pipe  
(specified pipe length & Pipe diameter?)  
Check any loose or removed communication line.  
>> If there is an abnormal condition, correct it by  
referring to Installation Manual or Data & Technical  
Manual.  
psi psi  
OK  
Pipe (In)  
Pipe (Out)  
Check Point 5 : Check Refrigeration Cycle  
Check if Strainer is clogged (Refer to the figure at right).  
Measure Gas Pressure and if there is a leakage, correct it.  
>> When recharging the refrigerant, make sure to perform  
vacuuming, and recharge the specified amount.  
Check EEV (PARTS INFORMATION 4)  
Check Compressor (PARTS INFORMATION 1,2)  
02-27  
Forecast of Cause :  
Trouble shooting 25  
1. Abnormal installation (Indoor/ Outdoor) 2. Fan failure(Indoor/ Outdoor)  
3. Compressor failure (Outdoor)  
Abnormal Noise  
Diagnosis method when Abnormal Noise is occurred  
Abnormal noise is coming from Indoor Unit.  
(Check and correct followings)  
Abnormal noise is coming from Outdoor Unit.  
(Check and correct followings)  
Is Main Unit installed in stable condition?  
Is Fan Guard installed normally?  
Is Main Unit installed in stable condition?  
Is the installation of Air suction grille and  
front panel normal?  
OK  
OK  
Is Fan broken or deformed?  
Is the screw of Fan loose?  
Is there any object which obstruct the Fan rotation?  
Is Fan broken or deformed?  
Is the screw of Fan loose?  
OK  
Is there any object which obstruct the Fan rotation?  
Check if vibration noise by loose bolt or contact noise  
of piping is happening.  
OK  
Is Compressor locked?  
>> Check Compressor (PARTS INFORMATION 1,2)  
Forecast of Cause:  
Trouble shooting 26  
1. Erroneous installation 2. Drain hose failure 3. Float Switch failure  
Water Leaking  
Diagnosis method when water is spitting out.  
Is the filter clogged?  
Diagnosis method when water leak occurs  
Is Main Unit installed in stable condition?  
Is Main Unit broken or deformed at the time of  
transportation or maintenance?  
OK  
OK  
psi psi  
Check Gas Pressure and correct it  
if there was a gas leak.  
Is Drain Hose connection loose?  
Is there a trap in Drain Hose?  
Is Drain Hose clogged?  
OK  
Is Fan rotating?  
>> Check Fan Motor (PARTS INFORMATION 5)  
OK  
Is Float Switch defective?  
>> Check Float Switch (Refer to Trouble Shooting 6)  
02-28  
2-4 SERVICE PARTS INFORMATION  
SERVICE PARTS INFORMATION 1  
Compressor  
Diagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting )  
Abnormal noise  
Stops soon after starting up  
Does not start up  
Check if vibration noise by  
loose bolt or contact noise  
of piping is happening.  
Is there open or loose connection  
cable?  
Is there open or loose connection  
cable?  
Is Gas Pipe Valve open?  
(Low Pressure is too low)  
Check Filter PCB, Main PCB,  
connection of Compressor,and winding  
resistance. (Refer to the next page).  
Defective Compressor  
can be considered.  
(due to inside dirt clogging  
or broken component)  
>> If there is no failure, the defect of  
Compressor is considered (Locked  
compressor due to clogged dirt or  
less oil)  
psi psi  
Check if Refrigerant is leaking.  
(Recharge Refrigerant)  
Replace Compressor  
Check if Strainer is clogged.  
(PARTS INFORMATION 4)  
Replace Compressor  
Check Filter PCB, Main PCB,  
connection of Compressor,and winding  
resistance. (Refer to the next page).  
>> If there is no failure, the defect of Compressor can be  
considered. (Compression part broken or valve defective.)  
Replace Compressor  
02-29  
SERVICE PARTS INFORMATION 2  
Inverter Compressor  
Check Point 1 : Check Connection  
Check terminal connection of Compressor  
(loose or incorrect wiring)  
Check connection of Main PCB  
(Loose or incorrect wiring)  
Terminal cover opened  
U(RED)  
W304  
MAIN PCB  
W305  
W303  
W
V (WHITE)  
(BLACK)  
RED  
WHITE  
BLACK  
Compressor  
Check Point 2 : Check Winding Resistance  
Check winding resistance of each terminal  
If the resistance value is 0 or infinite, replace Compressor.  
U
Resistance Value :  
0.88  
0.188 (For AUU42RCLX)  
at 68°F(20°C)  
(For AUU18/ 24/ 36RCLX)  
V
W
Check Point 3 : Replace Main PCB  
If the symptom does not change with above Check 1, 2, replace Main PCB.  
02-30  
SERVICE PARTS INFORMATION 3  
Active Filter Module  
Check Point 1 : Check Open or Short-circuit and Diode (D1)  
Remove connector, check the open or short-circuit and the diode in the module  
Check the open or short-circuit  
Terminal  
L1  
L2  
(+)  
( )  
P
Resistance value  
D1  
Tester(+) Tester(-)  
(+)  
( )  
P
( )  
N1  
(+)  
L2  
360k  
0
N1  
N2  
Io  
720k  
L1  
5.4M (approx.)  
Power factor control  
360k  
P
N1  
Control Box  
N2  
L1,L2  
L2  
5.8M (approx.)  
Check the diode  
Terminal  
Resistance value  
Tester(+) Tester(-)  
5.3M (approx.)  
L2  
P
P
5.4M (approx.)  
L2  
If it is abnormal,replace ACTIVE FILTER MODULE  
Check Point 2 : Check the Output DC voltage (between P and N1)  
Check the Output DC voltage (between P and N1) of compressor stopping and operating.  
>> If the output voltage of compressor operating is less than the output voltage of compressor stopping,  
Active Filter Module is detective. >> Replace Active Filter Module  
02-31  
SERVICE PARTS INFORMATION 4  
Outdoor unit Electronic Expansion Valve  
( EEV )  
Check Point 1 : Check Connections  
Check connection of connector (CN27)  
( Loose connector or open cable )  
EXPANSION  
VALVE COIL  
RED  
BROWN  
BLUE  
1
2
3
4
5
6
ORANGE  
YELLOW  
WHITE  
EV  
CN27  
Check Point 3 : Check Voltage from Main PCB.  
Check Point 2 : Check Coil of EEV  
DC  
Remove connector, check each winding  
resistance of Coil.  
Remove Connector and check Voltage (DC12V)  
If it does not appear, replace Main PCB.  
Read wire  
White - Red  
Resistance value  
Check Point 4 : Check Noise at start up  
Turn on Power and check operation noise.  
Yellow - Brown  
Orange - Red  
Blue - Brown  
46  
4
at 68°F(20°C)  
If an abnormal noise does not show, replace Main PCB.  
If Resistance value is abnormal, replace EEV.  
Check Point 5 : Check Opening and Closing Operation of Valve  
If it is open,  
When Valve is closed,  
it has no temp. difference between Inlet and Outlet.  
it has a temp. difference between Inlet and Outlet.  
CLOSE  
Example : Hot Gas  
OPEN  
Example : Hot Gas  
Pipe (In)  
Pipe (In)  
Hi TEMP.  
Hi TEMP.  
Pipe (Out)  
Hi TEMP.  
Pipe (Out)  
Normal TEMP.  
Check Point 6 : Check Strainer  
Strainer normally does not have temperature difference between inlet and outlet as shown in  
,
but if there is a difference as shown in , there is a possibility of inside clogged. In this case, replace Strainer.  
Pipe (In)  
Pipe (Out)  
Pipe (In)  
Pipe (Out)  
02-32  
SERVICE PARTS INFORMATION 5  
Indoor Unit Fan Motor  
Check Point : AUU18/ 24RCLX  
Check each winding resistance of the motor  
If Resistance value is abnormal, replace motor.  
BLUE  
Read Wire  
White - Red  
Red - Black  
Red - Purple  
Red - Purple  
Resistance value  
PURPLE  
120  
55.3  
61.2  
8%  
8%  
8%  
Thermal protector  
302°F (150°C)  
RED  
Pr  
(AC)  
BLACK  
WHITE  
283  
8%  
at 68°F(20°C)  
Check Point : AUU36/ 42RCLX  
Check each winding resistance of the motor  
If Resistance value is abnormal, replace motor.  
3
Pr  
The connector  
Resistance value  
Thermal protector  
257 275°F  
inserting numbers  
(125 135°C)  
1
2
3
3
44.5  
40.5  
10%  
10%  
2
1
at 68°F(20°C)  
(AC)  
02-33  
CASSETTE type  
INVERTER  
3 . REPLACEMENT PARTS  
1. REPLACEMENT PARTS (For OUTDOOR UNIT)  
1-1 For AOU18/ 24/ 36RLX  
1-1-1 PARTS LAYOUT DRAWING  
Active Filter Module  
Heat Exchanger  
Fan motor  
Thermistor (Heat sink)  
Main PCB  
Filter PCB  
4-way valve  
Fan  
A
Accumulator  
Solenoid  
Thermistor  
(Compressor temp.)  
Compressor  
Choke coil  
Thermistor  
(Discharge temp.)  
VIEW - A  
03-01  
Thermo Holder&  
Thermistor (Outdoor Temp.)  
Check valve  
Pressure SW  
AOU18  
2-way valve (Liquid)  
Coil (Expansion valve)&  
Expansion valve  
AOU24/ 36  
3-way valve (Liquid)  
Thermistor (Heat exchanger temp.)  
3-way valve  
(Gas)  
03-02  
1-1-2 WIRING (For AOU18/ 24/ 36RLX)  
CLAMP & BIND  
Thermistor (Discharge temp.) wire  
Thermistor (Outdoor temp.) wire  
Thermistor (Compressor temp.) wire  
Thermistor (Heat exchanger temp.) wire  
Coil (Expansion valve) wire  
Pressure SW wire  
CLAMP  
(Compressor wire)  
CLAMP  
(Fan motor wire)  
CLAMP  
(Solenoid wire)  
BIND  
(Compressor wire  
& Solenoid wire)  
BIND  
(Thermistor (Discharge temp.))  
(Thermistor (Compressor temp.))  
(Thermistor (Heat exchanger temp.))  
(Coil (Expansion valve))  
ENLARGED DETAIL  
Thermistor(Outdoor temp.)  
CLAMP  
(Pressure SW wire &  
Thermistor(Outdoor temp.))  
Coil (Expansion valve)  
BIND  
(Thermistor  
(Outdoor temp.))  
B
Pressure SW  
BIND  
(Pressure SW wire &  
Thermistor(Outdoor temp.))  
Thermistor  
(Heat exchanger temp.)  
BIND  
VIEW - B  
(Thermistor  
(Heat exchanger temp.))  
ENLARGED DETAIL  
03-03  
1-1-3 DISASSEMBLY PROCESS (For AOU18/ 24/ 36RLX)  
1. SERVICE PANEL removal  
Remove the 2 mounting screws.  
Remove the SERVICE PANEL by sliding downward.  
Replaceable Component  
Compressor  
Accumulator  
4-way valve  
Solenoid  
Thermistor (Compressor temp.)  
Thermistor (Discharge temp.)  
Thermistor (Outdoor temp.)  
Thermistor (Heat exchanger temp.)  
Pressure SW  
Hook  
(3 places)  
Coil (Expansion valve)  
2. TOP PANEL removal  
Remove the 7 mounting screws.  
Remove the TOP PANEL upward.  
FRONT VIEW  
REAR VIEW  
03-04  
3. INVERTER BOX removal  
Remove the 4 mounting screws.  
Remove the connectors and cords. (Refer to VIEW -C,-D)  
Remove the INVERTER BOX upward.  
C
REAR VIEW  
D
FRONT VIEW  
Remove power supply &  
Connection cord.  
Remove the connectors  
Remove the connectors  
Terminal  
G
G
VIEW - C  
Choke coil  
VIEW - D  
INVERTER BOX  
03-05  
Remove the 1 mounting screw.  
Remove the INVERTER BOX COVER upward.  
INVERTER BOX COVER  
F
Hook (2 places)  
E
Remove the connector and cords.  
Twist W6 and W7  
4 times or more.  
Twist W4 and W5  
2 times or more.  
CN1 (Black/Brown/Red)  
W8 (Black)  
W6 (Black)  
W9 (White)  
W4 (Black)  
W5 (White)  
W7 (White)  
W200 (Red)  
VIEW - E  
03-06  
Remove the connector and cords.  
Twist 4 times or more  
2 turn the Wire this way  
" - " (Black)  
" + " (Red)  
" L2 " (Brown)  
Thermistor (Heat sink)  
" L1 " (White)  
CN407  
" P " (Yellow)  
" N1 " (Blue)  
VIEW - F  
BIND  
W12 / "P" (Yellow)  
W13 / "N1"(Blue)  
CN407  
DETAIL  
03-07  
Remove the 6 mounting screws.  
Remove the INVERTER BOX A upward.  
INVERTER BOX A  
4
3
5
6
4
3
REAR VIEW  
6
5
1
2
LEFT SIDE VIEW  
Filter PCB  
Main PCB  
Remove the 2 mounting screws.  
Remove the Filter PCB upward.  
Remove the 1 mounting screw.  
Remove the Main PCB upward.  
Hook (3 places)  
Hook (2 places)  
Main PCB  
Filter PCB  
Screw  
03-08  
Screw  
1-1-4 ASSEMBLY PROCESS of INVERTER UNIT (For AOU18/ 24/ 36RLX)  
1. FILTER PCB  
As shown in Fig.1, assemble FILTER PCB to INVERTER BOX A.  
As shown in Fig.2, pull out the wires of FILTER PCB.  
Hook (2 places)  
Screw (2 places)  
INVERTER BOX A  
FILTER PCB  
Fig.1  
Fig.2  
2. MAIN PCB  
As shown in Fig.3, temporarily fix MAIN PCB to INVERTER BOX A.  
After it is temporary fix of MAIN PCB, As shown in the Fig 4 - 7,  
pull out the wires of MAIN PCB.  
W12(Yellow)  
W13(Blue)  
Fig.5  
Hook (3 places)  
Fig.4  
MAIN PCB  
Screw  
Fig.3  
Fig.6/ 7  
03-09  
As shown in Fig.4, pull out the wires.  
W16 (Red)  
W17 (Black)  
Thermistor  
(Heat sink)  
W303 (Black)  
W304 (White)  
W305 (Red)  
CN407  
Fig. 4  
As shown in Fig.5, pull out the wires and fix them.  
Hook (2 places)  
W12 (Yellow)  
W13 (Blue)  
W17 (Black)  
W16 (Red)  
W303 (Black)  
W304 (White)  
W305 (Red)  
Fig. 5  
03-10  
As shown in Fig.6, pull out the wires.  
CN1  
W200 (Red)  
Fig. 6  
As shown in Fig.7, pull out the wires.  
A
W200 (Red)  
HYIC1  
CN1 wire with connector  
Fig. 7  
Don't come in contact with HYIC1.  
DETAIL - A  
03-11  
For AOU18/ 24RLX  
As shown in Fig.8, connect wires.  
CN34 (Yellow)  
CN1 (White)  
Fig. 8  
As shown in Fig.9, connect wires.  
Through this hole.  
TM101 (Black line)  
TM102 (White line)  
Fig. 9  
03-12  
For AOU36RLX  
As shown in Fig.8, connect wires.  
CN34 (Yellow)  
CN1 (White)  
Fig. 8  
As shown in Fig.9, connect wires.  
W21 (Orange)  
W22 (Orange)  
PTC Thermistor  
Through this hole.  
TM101 (Black line)  
TM102 (White line)  
Fig. 9  
03-13  
As shown in Fig.10, fix the wire to INVERTER BOX A.  
Pull out the wire  
Hook (3 places)  
Thermistor (Heat sink)  
through this opening  
CN407  
Fig. 10  
As shown in the figures, set wire with connector and bind it to INVERTER BOX A.  
Bind wire to  
INVERTER BOX A.  
Through the guide  
W303 (Black)  
W304 (White)  
W305 (Red)  
Through the hole  
Fig. 11  
03-14  
1-2 For AOU42RLX  
1-2-1 PARTS LAYOUT DRAWING  
Active Filter Module  
Thermistor (Heat sink)  
D,Power (Bridge)  
Main PCB  
Filter PCB  
Heat Exchanger  
Fan motor  
Fan  
Choke coil  
4-way valve  
Thermistor  
(Discharge temp.)  
Solenoid  
Accumulator  
Thermistor  
(Compressor temp.)  
Compressor  
03-15  
Thermo Holder&  
Thermistor (Outdoor Temp.)  
Pressure SW  
Check valve  
3-way valve (Liquid)  
3-way valve (Gas)  
Coil (Expansion valve)&  
Expansion valve  
Thermistor (Heat exchanger temp.)  
03-16  
1-2-2 WIRING (For AOU42RLX)  
CLAMP  
(Compressor wire)  
BIND  
Don't use this  
CABLE CLIP.  
(Thermistor (Discharge temp.))  
(Thermistor (Compressor temp.))  
(Thermistor (Heat exchanger temp.))  
(Coil (Expansion valve))  
CLAMP  
(Compressor wire)  
CLAMP & BIND  
Thermistor (Discharge temp.) wire  
Thermistor (Outdoor temp.) wire  
Thermistor (Compressor temp.) wire  
Thermistor (Heat exchanger temp.) wire  
Coil (Expansion valve) wire  
Pressure SW wire  
CLAMP  
(Compressor wire)  
CLAMP  
(Fan motor wire x2)  
CLAMP  
(Solenoid wire)  
ENLARGED DETAIL  
03-17  
Thermistor(Outdoor temp.)  
Coil (Expansion valve)  
CLAMP with U PIPE  
(Thermistor (Heat exchanger temp.))  
(Coil (Expansion valve))  
Thermistor  
(Heat exchanger temp.)  
ENLARGED DETAIL  
03-18  
1-2-3 DISASSEMBLY PROCESS (AOU42RLX)  
1. SERVICE PANEL removal  
Remove the 2 mounting screws.  
Remove the SERVICE PANEL by sliding downward.  
Hook  
(3 places)  
Replaceable Component  
Compressor  
Accumulator  
4-way valve  
Solenoid  
Thermistor (Compressor temp.)  
Thermistor (Discharge temp.)  
Thermistor (Outdoor temp.)  
Thermistor (Heat exchanger temp.)  
Pressure SW  
Coil (Expansion valve)  
03-19  
2. TOP PANEL removal  
Remove the 7 mounting screws.  
Remove the TOP PANEL upward.  
FRONT VIEW  
REAR VIEW  
03-20  
3. INVERTER BOX removal  
Remove the 4 mounting screws.  
Remove the connectors and cords. (Refer to VIEW -C,-D)  
Remove the INVERTER BOX upward.  
C
REAR VIEW  
D
FRONT VIEW  
Remove power supply &  
Connection cord.  
Remove the connectors  
Remove the connectors  
Terminal  
G
G
VIEW - C  
Choke coil  
VIEW - D  
INVERTER BOX  
03-21  
Remove the 1 mounting screw.  
Remove the INVERTER BOX COVER upward.  
INVERTER BOX COVER  
F
Hook (2 places)  
E
Remove the connector and cords.  
Twist W6 and W7  
2 times or more.  
W1 (Black)  
W7 (White)  
W200 (Red)  
W6 (Black)  
W2 (White)  
VIEW - E  
03-22  
Remove the connector and cords.  
"
" (White)  
D,Power (Bridge)  
"
" (Gray)  
" L2 " (Brown)  
" L1 " (White)  
" - " (Black)  
" + " (Red)  
Thermistor (Heat sink)  
CN407  
BIND  
" P " (Yellow)  
" N1 " (Blue)  
"P" (Yellow)  
"N1"(Blue)  
CN407  
VIEW - F  
03-23  
Remove the 6 mounting screws.  
Remove the INVERTER BOX A upward.  
INVERTER BOX A  
4
3
5
6
4
3
REAR VIEW  
6
5
1
2
LEFT SIDE VIEW  
Filter PCB  
Main PCB  
Remove the 2 mounting screws.  
Remove the Filter PCB upward.  
Remove the 1 mounting screw.  
Remove the Main PCB upward.  
Hook (3 places)  
Hook (2 places)  
Main PCB  
Filter PCB  
Screw  
03-24  
Screw  
1-2-4 ASSEMBLY PROCESS of INVERTER UNIT (For AOU42RLX)  
1. FILTER PCB  
As shown in Fig.1, assemble FILTER PCB to INVERTER BOX A.  
As shown in Fig.2, pull out the wires of FILTER PCB.  
Hook (2 places)  
Screw (2 places)  
INVERTER BOX A  
FILTER PCB  
Fig.1  
Fig.2  
2. MAIN PCB  
As shown in Fig.3, temporarily fix MAIN PCB to INVERTER BOX A.  
After it is temporary fix of MAIN PCB, As shown in the Fig 4 - 6,  
pull out the wires of MAIN PCB.  
Fig.5  
W14(Yellow)  
W15(Blue)  
Hook (3 places)  
MAIN PCB  
Fig.4  
Screw  
Fig.6  
Fig.3  
03-25  
As shown in Fig.4, pull out the wires.  
Thermistor  
(Heat sink)  
CN407  
W303 (Black)  
W304 (White)  
W305 (Red)  
Fig. 4  
As shown in Fig.5, pull out the wires and fix them.  
W303 (Black)  
W304 (White)  
W305 (Red)  
Hook (2 places)  
W107 (White)  
W108 (Violet)  
CN407  
Thermistor  
(Heat sink)  
Fig. 5  
03-26  
As shown in Fig.6, pull out the wires.  
A
CN1 wire with connector  
HYIC1  
W200 (Red)  
Fig. 6  
Don't come in contact with HYIC1.  
VIEW - A  
As shown in Fig.7, connect wires.  
CN34 (Yellow)  
CN1 (White)  
Fig. 7  
03-27  
As shown in Fig.8, connect wires.  
W108 (Violet)  
W107 (White)  
Gray line  
Make White line  
on Black line  
Twist 5 times or more.  
Through this hole.  
TM101 (Black line)  
TM102 (White line)  
Fig. 8  
03-28  
As shown in Fig.9, fix the wire to INVERTER BOX A.  
Pull out the wire  
through this opening  
Hook (3 places)  
Thermistor (Heat sink)  
CN407  
Fig. 9  
As shown in the figures, set wire with connector and bind it to INVERTER BOX A.  
Bind wire to  
INVERTER BOX A.  
Through the guide  
W303 (Black)  
W304 (White)  
W305 (Red)  
Through the hole  
Fig. 10  
03-29  
2. REPLACEMENT PARTS (For INDOOR UNIT)  
2-1 PARTS LAYOUT DRAWING  
1. INTAKE GRILLE removal  
Push the INTAKE GRILLE pushbuttons (2 places).  
Open the INTAKE GRILLE  
PUSH  
OPEN  
INTAKE GRILLE  
PUSH  
Pushbotton  
(2 places)  
Remove the GRILLE hinge wire.  
Pull up while pressing the B section.  
B
Part A detail view  
A
GRILLE hinge wire  
Part B section view  
Remove the INTAKE GRILLE.  
03-30  
2. FILTER removal  
Remove the FILTER.  
Hook  
(3 places)  
FILTER  
3. CONTROL BOX COVER removal  
Remove the 5 mounting screws.  
Remove the CONTROL BOX COVER upward.  
CONTROL BOX COVER  
03-31  
4. Wiring and Parts layout  
CLAMP  
(PWB wire (For Power Supply PCB))  
(Wire with connector (For Float SW))  
(Wire with connector (For Remocon))  
Thermistor(Room temp.)  
CLAMP  
(Wire with connector (For Float SW))  
(Wire with connector (For Remocon))  
Terminal-3P  
Capacitor,Plastic  
Controller PCB  
Power Supply PCB  
BIND  
(Wire with connector (For Capacitor,Plastic))  
(PWB wire (For Power Supply PCB)X2)  
(Wire with connector (For Float SW))  
(Wire with connector (For Remocon))  
CN1  
(Power Supply PCB)  
BLACK  
CN17  
(Remocon)  
WHITE  
CN6  
(Drain Pump)  
CN15  
(Float SW)  
RED  
CN8  
Thermistor  
(Room temp.)  
Detail View  
CN7  
Thermistor  
(Heat Exchanger temp.)  
CN10  
(Stepping motor)  
CN5  
CN4  
CN16  
(MOTOR Feed Back)  
(FAN MOTOR) (Capacitor)  
Detail View  
03-32  
5. PANEL FRAME removal  
Pull up the corner section (A) of the PANEL FRAME as shown in  
figure (4 locations).  
A
PANEL FRAME  
A
A
B
A
Part A detail view  
Pull up in the direction of the arrow while holding down  
the C section of figure (4 locations).  
C
Part B detail view  
PANEL FRAME  
PANEL BASE  
03-33  
5. PANEL BASE removal  
Remove the 4 mounting bolts.  
Remove the PANEL BASE upward.  
PANEL BASE  
6. CONTROL UNIT removal  
Remove the 3 mounting bolts and 1 mouting screw.  
Remove the CONTROL UNIT upward.  
BOLT  
(3places)  
SCREW  
CONTROL UNIT  
03-34  
7. DRAIN PAN removal  
Remove the DRAIN PAN ASSY.  
DRAIN PAN ASSY  
03-35  
8. TURBO FAN removal  
Remove the M8 NUT and Washer(TURBO FAN).  
Remove the TURBO FAN ASSY.  
For AUU18/ 24RCLX  
M8 NUT  
Washer(TURBO FAN)  
TURBO FAN ASSY  
The M8 special NUT should  
be tightened with a torque of  
1.96 - 7.84 N m.  
For AUU36/ 42RCLX  
M8 NUT  
Washer(TURBO FAN)  
TURBO FAN ASSY  
The M8 special NUT should  
be tightened with a torque of  
1.96 - 7.84 N m.  
03-36  
9. FAN MOTOR removal  
For AUU18/ 24RCLX  
Remove the 3 mounting nuts.  
Remove the FAN MOTOR ASSY.  
Special NUT M6  
(3 places)  
FAN MOTOR ASSY  
Rubber  
(Vibration-proof) -A  
(3 places)  
Rubber  
(Vibration-proof) -B  
(3 places)  
For AUU36/ 42RCLX  
Remove the 4 mounting nuts.  
Remove the FAN MOTOR ASSY.  
Special NUT M6  
(4 places)  
FAN MOTOR ASSY  
03-37  
10. DRAIN PUMP removal  
Remove the 2 mounting screws.  
Remove the DRAIN PUMP UNIT.  
DRAIN PUMP UNIT  
DRAIN HOSE  
03-38  
1116,Suenaga,Takatsu-ku,Kawasaki 213-8502,Japan  
Apr. 2006 Printed in Japan  

Toshiba Ras M18eacv E User Manual
The Speaker Company Tsc Barcode Reader Me240 User Manual
Nokia Extra Power Dc 11 User Manual
LG 43UH7500 02 User Manual
Lexmark Interpret S400 User Manual
JVC CA D5T User Manual
EMERSON LIEBERT GXT4 5000RT208 User Manual
CRAFTSMAN 152.211240 User Manual
BLACK DECKER GSL35 User Manual
BLACK DECKER DP240P User Manual