| 	
		 AIR CONDITIONER (SPLIT TYPE)   
					Installation manual   
					For OUTDOOR USE only   
					Outdoor Unit   
					Model name:   
					RAV-SP300AT2-UL   
					RAV-SP360AT2-UL   
					RAV-SP420AT2-UL   
					Installation manual   
					Air conditioner (Split type)   
					English   
					1 
					Manuel d'installation   
					Climatiseur (Type split)   
					Français   
					23   
				Installation Manual   
					Outdoor Unit   
					1 DIMENSION   
					Drain hole   
					(Ø1.0"(25) burring hole)   
					15.0"(380)   
					7.9"(200)   
					Air intake   
					2.4"(60)   
					B legs   
					0.5"(12)   
					Air intake   
					Mounting bolt hole   
					(Ø0.5"(12) × 0.7"(17) U-shape hole)   
					3.0"(75)   
					Details of B legs   
					Air   
					discharge   
					A legs   
					Mounting bolt hole   
					(Ø0.5"(12) × 0.7"(17) long hole)   
					15.1"(383)   
					2.8"(70)   
					1.5"(39)   
					3.8"(96)   
					5-drain hole   
					Ø0.8"(20) ~ 3.5"(88)   
					burring hole   
					Details of A legs   
					5.9"(150)   
					2.0"(52)   
					23.6"(600)   
					12.6"(320)   
					35.4"(900)   
					21.7"(550)   
					Refrigerant pipe connecting port   
					(Ø0.4”(9.5) flare at liquid side)   
					Refrigerant pipe connecting port   
					(Ø0.6”(15.9) flare at gas side)   
					1.2"(30)   
					Conduit connection   
					hole   
					Refrigerant piping   
					knockout   
					Refrigerant piping   
					knockout   
					2.4"(60)   
					2.7"(68)   
					7"(178) 7"(178) 7"(178)   
					20.4"(518)   
					0.7"(18)   
					3.9"(99)   
					2.3"(58)   
					15.7"(400)   
					Z 
					12.9"(327)   
					0.5"(12)   
					2.5"(64)   
					3.3"(83)   
					0.3"(7)   
					Mounting hole sold separately   
					(24 - Ø0.1"(3) emboss)   
					Knockout for bottom piping   
					Z views   
					EN   
					2-EN   
					– 2 –   
				Installation Manual   
					Outdoor Unit   
					2 ACCESSORY PARTS   
					Part name   
					Q’ty   
					Shape   
					Usage   
					Installation manual   
					1 
					This manual   
					(Hand this directly to the customer.)   
					Drain nipple   
					1 
					Waterproof rubber cap   
					Edge Guard   
					5 
					1 
					Protects piping against sharp edges   
					NOTE   
					Use drain nipple and waterproof rubber cap as necessary.   
					3-EN   
					– 3 –   
				Installation Manual   
					Outdoor Unit   
					3 SYSTEM REQUIREMENTS   
					Refrigerant charge   
					Piping (Field supplied)   
					• Minimum refrigerant line length between the outdoor   
					unit and indoor unit is 16.5” (5 m)   
					Length of refrigerant   
					pipe connected to   
					indoor/outdoor unit   
					Additional refrigerant   
					• Maximum pipe lengths   
					9’10” - 98’5”   
					(3 - 30 m)   
					None   
					Allowable   
					pipe length   
					(ft (m))   
					Height difference   
					(Indoor-outdoor H)   
					(ft (m))   
					Number of   
					Add 0.43 oz/ft (40 g/m) of   
					refrigerant for piping that exceeds   
					98’5” (30 m) up to 246’1” (75 m).   
					bent portions   
					*98’5” - 246’1”   
					(30 - 75 m)   
					Totallength   
					L 
					Indoor unit: Outdoor unit:   
					Upper   
					Lower   
					10 or less   
					* Caution during addition of refrigerant   
					Max. amount of additional refrigerant is 1.8 lbs (800   
					g).   
					Charge the refrigerant accurately. Overcharging   
					may cause serious trouble with the compressor.   
					246’1” (75)   
					98’5” (30)   
					98’5” (30)   
					Figure of Single   
					Indoor Unit   
					* Minimum refrigerant pipe is 16’5”(5 m).   
					This may cause a malfunction of the compressor or   
					other devices.   
					Metering Device is an electronic EXV (PMV) in   
					outdoor unit.   
					Outdoor Unit   
					 
					Connecting power and control   
					cables (Field supplied)   
					• The main power is supplied to the outdoor unit. The   
					field supplied connecting cables from the outdoor   
					unit to the indoor unit consist for 4 wires and provides   
					the power for the indoor unit as well as the   
					communication signal between the outdoor and   
					indoor unit.   
					Refrigerant sizes   
					Liquid side   
					Outer   
					Gas side   
					Outer   
					Thickness   
					Thickness   
					diameter   
					diameter   
					• System interconnection wire size must be AWG12.   
					• Breaker must have a capacity specified in the   
					following table.   
					• All wiring must comply with local electric codes and   
					NEC (National Electric Code) or CEC (Canadian   
					Electric Code).   
					0.04”   
					(1.0 mm)   
					Ø3/8”   
					0.03”   
					Ø5/8”   
					(9.5 mm)   
					(0.8 mm)   
					(15.9 mm)   
					Flare nuts and flaring   
					• The flare nuts and flaring are different from those for   
					the conventional refrigerant.   
					Use the flare nuts supplied with the air conditioner or   
					those for R410A.   
					Model RAV-   
					SP420   
					208/230 V, 60 Hz   
					24 A   
					• Before performing flaring, carefully read   
					“REFRIGERANT PIPING”   
					Power supply   
					MCA   
					MOCP (MAX Fuse/CB)   
					Breaker   
					40 A   
					Insulation   
					Both lines need to be insulated. Use a minimum 0.4”   
					(10 mm) wall thickness.   
					25 A   
					System interconnection wires   
					MCA = Minimum Circuit Amps   
					AWG12   
					MOCP =Maximum Over Protection Device Amps.   
					EN   
					– 4 –   
					4-EN   
				Installation Manual   
					Outdoor Unit   
					4 PRECAUTIONS FOR SAFETY   
					Installing, starting up, and servicing air--conditioning equipment can be hazardous due to system pressures,   
					electrical components, and equipment location (roofs, elevated structures, etc.).   
					Only trained, qualified installers and service mechanics should install, start--up, and service this equipment.   
					Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should   
					be performed by trained service personnel.   
					When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached   
					to the equipment.   
					Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby   
					when brazing. Use care in handling, rigging, and setting bulky equipment.   
					Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the   
					unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety   
					information. This is the safety--alert symbol   
					. When you see this symbol on the unit and in instructions or   
					manuals, be alert to the potential for personal injury.Understand these signal words: DANGER, WARNING, and   
					CAUTION. These words are used with the safety--alert symbol.   
					DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING   
					signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which   
					may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which   
					will result in enhanced installation, reliability, or operation.   
					WARNING   
					• 
					Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner.   
					Perform installation work properly according to the Installation Manual.   
					Inappropriate installation may result in water leakage, electric shock or fire.   
					• Be sure to ground the equipment   
					Improper grounding may cause an electric shock.   
					Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires.   
					• Turn off the circuit breaker before attempting any electrical work and maintenance.   
					Make sure the circuit breaker is off. Failure to do so may cause electric shock.   
					Use an exclusive power circuit for the air conditioner. Use the rated voltage.   
					• When moving the air conditioner for installation to another place, be very careful not to allow the specified   
					refrigerant (R410A) to become mixed with any other gaseous body into the refrigeration cycle.   
					If air or any other gas mixes with the refrigerant, the gas pressure in the refrigeration cycle will become abnormally   
					high and it may result in the pipe bursting or personal injuries.   
					• Do not modify this unit by removing any of the safety guards or by by-passing any of the safety interlock   
					switches.   
					• Do not touch the intake or aluminium fins of the outdoor unit.   
					Doing so may result in injury.   
					• Tighten the flare nut with a torque wrench in the specified manner.   
					Excessive tightening of the flare nut may cause a crack in the flare nut after a long period, which may result in   
					refrigerant leakage.   
					• Install the air conditioner securely in a location where the base can sustain the weight of the unit adequately.   
					• If refrigerant gas has leaked during the installation work, ventilate the room immediately.   
					If the leaked refrigerant gas comes in contact with fire, noxious gas may be generated.   
					• After the installation work, confirm that refrigerant gas does not leak.   
					If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas may be   
					generated.   
					• Electrical work must be performed by a qualified electrician in accordance with the NEC or local code. Make   
					sure the air conditioner uses an exclusive power supply.   
					An insufficient power supply capacity or inappropriate installation may cause fire.   
					• Use only the specified wiring during the unit installation. Ensure that all terminals are securely fixed, so   
					preventing any external forces having a negative effect on the terminals.   
					5-EN   
					– 5 –   
				Installation Manual   
					Outdoor Unit   
					WARNING   
					• When the air conditioner cannot cool or heat a room well, contact the dealer from whom you purchased the   
					air conditioner as refrigerant leakage is considered as the cause.   
					In the case of repair that requires refill of refrigerant, ask service personnel about details of the repair.   
					The refrigerant used in the air conditioner is harmless.   
					Generally, the refrigerant does not leak. However, if the refrigerant leaks in a room and a heater or stove burner in   
					the room catches fire, it may generate toxic gas.   
					When you ask service personnel for repairing refrigerant leakage, confirm that the leakage portion has been   
					completely repaired.   
					• Do not install the air conditioner in a location that may be subjected to a risk of exposure to a combustible   
					gas.   
					If a combustible gas leaks and becomes concentrated around the unit, a fire may occur.   
					• Install the refrigerant pipe securely during the installation work before operating the air conditioner.   
					If the compressor is operated with the valve open and without the refrigerant pipe, the compressor sucks air and the   
					refrigeration cycle is over pressurized, which may cause a burst or injury.   
					• When carrying out the pump-down work, shut down the compressor before disconnecting the refrigerant   
					pipe.   
					Disconnecting the refrigerant pipe with the service valve left open and with the compressor still operating will cause   
					air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly   
					resulting in rupturing, injury, etc.   
					CAUTION   
					• Do not climb onto or place objects on top of the outdoor unit.   
					You may fall or the objects may fall off of the outdoor unit and result in injury.   
					• Wear heavy gloves during the installation work to avoid injury.   
					EQUIPMENT DAMAGE HAZARD   
					Failure to follow this caution may result in equipment damage or improper operation.   
					Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must be   
					a 6 in. (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length is   
					buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes   
					refrigerant slugging and could possibly damage the compressor at start-up.   
					EN   
					6-EN   
					– 6 –   
				Installation Manual   
					Outdoor Unit   
					5 INSTALLATION OF NEW REFRIGERANT   
					AIR CONDITIONER   
					CAUTION   
					New Refrigerant Air Conditioner Installation   
					• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY   
					OZONE LAYER.   
					R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the working   
					pressure of R410A refrigerant is approx. 1.6 times as that of refrigerant R22. Accompanied with the adoption of the new   
					refrigerant, the refrigerant oil has also been changed. Therefore, during installation work, be sure that water, dust,   
					former refrigerant, or refrigerant oil does not enter the new type refrigerant R410A air conditioner cycle.   
					To prevent mixing of refrigerant or refrigerant oil, the sizes of connecting sections of charging port on main unit and   
					installation tools are different from those of the conventional refrigerant units. Accordingly, special tools are required for   
					the new refrigerant (R410A) units. For connecting pipes, use new and clean piping materials with high pressure fittings   
					made for R410A only, so that water and/or dust does not enter.   
					Required Tools/Equipment and Precautions for Use   
					Prepare the tools and equipment listed in the following table before starting the installation work.   
					: R410A exclusive   
					: Generic   
					Tools/equipment   
					Manifold gauge*   
					Use   
					Vacuuming/charging refrigerant   
					and operation check   
					Charging hose   
					Gas leak detector   
					Gas leak check   
					Vacuum drying   
					Vacuum pump with backflow   
					prevention function   
					Flare tool   
					Flare machining of pipes   
					Bending pipes   
					Usable if dimensions are adjusted.   
					Bender   
					Refrigerant recovery equipment   
					Torque wrench   
					Pipe cutter   
					Refrigerant recovery   
					Tightening flare nuts   
					Cutting pipes   
					Ø1/2” (12.7 mm) and 5/8” (Ø15.9 mm)   
					Brazing torch and nitrogen   
					cylinder   
					Braze pipes   
					Refrigerant charging scales   
					4 mm hexagon wrench   
					Charging refrigerant   
					Opening liquid valve   
					7-EN   
					– 7 –   
				Installation Manual   
					Outdoor Unit   
					When an outdoor unit is installed in a location that is   
					always exposed to strong winds like a coast or on   
					the high stories of a building, one of the following is   
					recommended.   
					• Install the unit so that its discharge faces the wall of   
					the structure.   
					Installation Location   
					WARNING   
					Install the outdoor unit in a location that can support   
					the weight of the outdoor unit.   
					Insufficient durability may cause the outdoor unit to fall,   
					which may result in injury.   
					Keep a distance 19.7” (500 mm) or more between the   
					unit and wall.   
					19.7" (500 mm)   
					CAUTION   
					Do not install the outdoor unit in a location that is   
					subject to combustible gas leaks.   
					Accumulation of combustible gas around the outdoor   
					unit may cause a fire.   
					Install the outdoor unit in a location that meets the   
					following conditions.   
					• A well-ventilated location free from obstacles near the   
					air inlets and air outlet   
					• A location that does not increase the operating noise   
					or vibration of the outdoor unit   
					• Install the unit so that the discharge is at a right angle   
					relative to the wind direction.   
					• A location that does not produce any drainage   
					problems from discharged water   
					Strong wind   
					• Location with easy access to power.   
					Strong wind   
					Do not install the outdoor unit in the following   
					location.   
					• A location with a saline atmosphere (coastal area) or   
					one that is full of sulfide gas (hot-spring area) (Special   
					maintenance is required.)   
					• A location subject to oil, vapor, oily smoke, or   
					corrosive gases   
					• Use wind baffle. Produce those parts in the field.   
					• When outside temperature conditions are 23 °F (-5   
					°C) or lower and unit is running in cooling mode.   
					• A location in which organic solvent is used   
					• A location where high-frequency equipment (including   
					inverter equipment, private power generator, medical   
					equipment, and communication equipment) is used   
					(Installation in such a location may cause malfunction   
					of the air conditioner, abnormal control or problems   
					due to noise from such equipment.)   
					• A location in which the discharged air of the outdoor   
					unit blows against the window of a neighboring house   
					• A location where the operating noise of the outdoor   
					unit is transmitted   
					<Example>   
					Wind shield   
					Wind shield   
					Wind shield   
					• When the outdoor unit is installed in an elevated   
					position, be sure to secure its feet.   
					• A location in which drain water poses any problems.   
					EN   
					– 8 –   
					8-EN   
				Installation Manual   
					Unit : in (mm)   
					Outdoor Unit   
					Required Clearances   
					Barrier at rear side   
					Barrier in front   
					▼ Upper side is free   
					1. Single unit installation   
					▼ Above unit is free   
					1. Single unit installation   
					2. Barrier on right, left and rear.   
					2. Multiple units installation   
					The height of the   
					barrier should be   
					lower than the height   
					of the outdoor unit.   
					5.9” (150)   
					or more   
					11.8” (300) or more   
					3. Multiple units installation   
					▼ Barrier also above unit   
					39.4” (1000)   
					or more   
					5.9”   
					(150)   
					or more   
					11.8”   
					11.8”   
					11.8”   
					(300)   
					(300)   
					(300)   
					or more   
					or more   
					or more   
					The height of the obstacle should be lower than the   
					height of the outdoor unit.   
					▼ Barrier also above unit   
					5.9” (150)   
					or more   
					9-EN   
					– 9 –   
				Installation Manual   
					Outdoor Unit   
					Barriers in front and back of unit   
					Installation of Outdoor Unit   
					• Before installation, check the strength and horizontal   
					of the base so that abnormal sounds do not   
					emanate.   
					• According to the following base diagram, fix the base   
					firmly with the anchor bolts.   
					(Anchor bolt, nut: 3/8” (M10) x 4 pairs)   
					Open above and to the right and left of the unit.   
					The height of an barrier in both the front and rear of the   
					unit, should be lower than the height of the outdoor   
					unit.   
					▼ Standard installation   
					1. Single unit installation   
					Drain hole   
					5.9” (150)   
					20.7” (525)   
					5.9” (150)   
					23.6” (600)   
					1.8” (45)   
					Drain   
					nipple mounting hole   
					2. Multiple unit installation   
					Drain hole   
					a. Intake and supply parallel   
					1) Field fabricate a snow or an ice stand for the   
					unit using the above dimension.   
					2) Place snow or ice stand on a foundation/pad   
					and secure it to the foundation/pad and secure   
					it to the foundation/pad by anchor bolts.   
					NOTE   
					11.8” (300)   
					or more   
					When the outdoor unit is anchored directly on   
					the foundation/pad (cooling only protrude a   
					minimum of 0.6” (15 mm)).   
					11.8” (300) or more   
					b. Intake and supply in line   
					Open above and to the right and left of the unit.   
					The height of an obstacle in both the front and   
					rear of the unit should be lower than the height   
					of the outdoor unit.   
					0.6” (15 mm) or less   
					▼ Standard installation   
					7.9”   
					(200)   
					or more   
					59.1”   
					(1500)   
					or more   
					78.7”   
					(2000)   
					or more   
					39.4”   
					(1000)   
					or more   
					11.8”   
					(300) or   
					more   
					EN   
					– 10 –   
					10-EN   
				Installation Manual   
					Outdoor Unit   
					3) Place unit on stand. Make sure it is level and   
					fasten securely to the stand.   
					• 
					As shown in the figure below, install the   
					foundation and vibration-proof rubber pads to   
					directly support the bottom surface of the fixing   
					leg that is in contact with the bottom plate of the   
					outdoor unit.   
					Waterproof rubber cap   
					(5pcs.)   
					Drain nipple   
					• 
					When installing the foundation for an outdoor   
					unit with downward piping, consider the piping   
					work.   
					GOOD   
					Mounting leg   
					Drain nipple   
					Waterproof rubber cap   
					Foundation   
					GOOD   
					For Reference   
					Bottom plate   
					of outdoor unit   
					If a heating operation is to be continuously performed   
					for a long time under the condition that the outdoor   
					temperature is 32 °F (0 °C) or lower, draining defrosted   
					water may be difficult due to the bottom plate freezing,   
					resulting in trouble with the cabinet or fan.   
					Foundation   
					Support the bottom surface of the   
					mounting leg that is in contact with   
					and underneath the bottom plate of   
					the outdoor unit.   
					Do not support   
					NO GOOD   
					the outdoor unit   
					only with the   
					If only the end of the   
					mounting leg is   
					supported, it may   
					deform.   
					mounting leg.   
					Foundation   
					• When water is to be drained through the drain hose,   
					attach the following drain nipple and waterproof   
					rubber cap, and use the drain hose (Inner diameter:   
					0.6” (16 mm)) sold on the market. Also seal the   
					screws securely with silicone material, etc., to   
					prevent water from leaking.   
					Some conditions may cause condensation or   
					dripping of water.   
					• When collectively draining discharged water   
					completely, use a drain pan.   
					11-EN   
					– 11 –   
				Installation Manual   
					Outdoor Unit   
					6 REFRIGERANT PIPING   
					Piping connections are inside the front panel of the unit   
					and the front panel and pipe cover needs to be   
					removed before piping and wiring connections are   
					made.   
					Flaring   
					1. Cut the pipe with a pipe cutter.   
					Be sure to remove burrs that may cause a gas   
					leak.   
					2. Insert the supplied flare nut into the pipe, and then   
					flare the pipe.   
					Piping can enter the outdoor unit from the back, from   
					the side or from the bottom as shown   
					As the flaring sizes of R410A differ from those of   
					refrigerant R22, the flare tools newly manufactured   
					for R410A are recommended.   
					Front panel   
					However, the conventional tools   
					B 
					can be used by adjusting the   
					projection margin of the copper   
					pipe.   
					Pipe cover   
					Rear   
					▼ Projection margin in flaring : B (Unit : in (mm))   
					Rigid (Clutch type)   
					R410A tool   
					used   
					Conventional   
					tool used   
					Outer diameter of   
					copper pipe   
					R410A   
					Side   
					0.04” - 0.06”   
					(1.0 - 1.5)   
					3/8” (9.5)   
					0 - 0.02” (0 - 0.5)   
					5/8” (15.9)   
					Bottom   
					1. Remove the front panel of the unit.   
					2. Remove the pipe cover.   
					▼ Flaring diameter size : A (Unit : in (mm))   
					+0   
					Outer diameter of copper pipe   
					3/8” (9.5)   
					A 
					-0.02"(–0.4)   
					3. Remove the appropriate knockout depending   
					on the orientation of the piping.   
					0.52” (13.2)   
					0.78” (19.7)   
					5/8” (15.9)   
					The pipe cover is easily mounted by cutting off   
					the slit at the lower part of the pipe cover.   
					* In case of flaring for R410A with the   
					conventional flare tool, pull the tool out   
					approx. 0.02” (0.5 mm) more than that for   
					R22 to adjust it to the specified flare size.   
					The copper pipe gauge is useful for   
					adjusting the projection margin size.   
					A 
					* Be sure to wear heavy work gloves while working.   
					4. Remove the burrs from the knockout opening   
					and use the factory supplied protective edge   
					guard material around the opening to protect the   
					piping and the wiring.   
					5. Remove the flare nut from the service valve on   
					outdoor unit. Insert the flare nut into the field   
					piping, and flare the pipe.   
					EN   
					Bend the pipe approx. 90 degree with a pipe   
					bender for side and rear piping.   
					6. When the piping connections are complete re-   
					install the pipe cover.   
					– 12 –   
					12-EN   
				Installation Manual   
					Outdoor Unit   
					• After the installation work, be sure to check for gas   
					leaks of the pipe connections with nitrogen.   
					Tightening of Flare   
					Connections   
					1. Align the centers of the flare connections and fully   
					tighten the flare nuts with your fingers.   
					NO GOOD   
					Cover   
					Valve at liquid side   
					Charge orifice   
					Cap   
					Piping valve   
					Tightened   
					Loosened   
					CAUTION   
					1. Do not put the crescent wrench on the charge   
					orifice or cover.   
					Flare nut   
					The valve may be broken.   
					2. If applying excessive torque, the nut may break   
					according to some installation conditions.   
					2. Use two wrenches to loosen or tighten the flare nut   
					on the gas service valve as shown in the figure.   
					Use only one wrench to loosen or tighten the flare   
					not on the liquid service valve.   
					• Pressure of R410A is higher than that of R22   
					(Approx. 1.6 times).   
					The final tightening with a torque wrench should be   
					to the specifications shown in table below.   
					Unit : ft•lbs (N•m)   
					Therefore, using a torque wrench, tighten the flare   
					pipe connecting sections that connect the indoor/   
					outdoor units at the specified tightening torque.   
					Incomplete connections may cause not only a gas   
					leak, but also trouble with the refrigeration cycle.   
					Outer diameter of copper pipe   
					3/8” (9.5 mm)   
					Tightening torque   
					24 - 31 (33 - 42)   
					50 - 60 (68 - 82)   
					Do not apply refrigerant oil to the flared   
					surface.   
					5/8” (15.9 mm)   
					Valve at gas side   
					Cover   
					Cap   
					Piping valve   
					Charge orifice   
					Flare nut   
					Tightened   
					Loosened   
					13-EN   
					– 13 –   
				Installation Manual   
					Outdoor Unit   
					7 ELECTRICAL CONNECTIONS   
					Field wiring   
					WARNING   
					The dashed lines show field wiring.   
					ELECTRICAL SHOCK HAZARD   
					(Field power   
					supply)   
					(System   
					interconnection wires)   
					Failure to follow this warning could result in   
					personal injury or death.   
					L 
					1 
					2 
					L 
					1 
					2 
					L 
					L 
					1 
					2 
					Input   
					power   
					• The unit cabinet must have an uninterrupted or   
					unbroken ground to minimize personal injury if an   
					electrical fault should occur. The ground may consist   
					of electrical wire or metal conduit when installed in   
					accordance with existing electrical codes.   
					• Before performing service or maintenance, be sure   
					main power switch is turned OFF.   
					L 
					L 
					208/230 V~,   
					60 Hz   
					Remote   
					controller   
					S 
					S 
					circuit breaker   
					Outdoor unit   
					Indoor unit   
					ground   
					• System interconnection wire size must be AWG12.   
					• Breaker must have a capacity specified in the   
					following table.   
					CAUTION   
					• All wiring must comply with local electric codes and   
					NEC (National Electric Code) or CEC (Canadian   
					Electric Code).   
					All wiring and connections must comply with NEC, CEC,   
					local codes.   
					UNIT DAMAGE HAZARD   
					Failure to follow this caution may result in damage   
					or improper operation.   
					• Unit failure as a result of operation on improper line   
					voltage or excessive phase imbalance constitutes   
					abuse and may cause damage to electrical   
					components.   
					• Wrong wiring may cause a burn-out of some electrical   
					parts.   
					• Do not damage or scratch the conductive core or inner   
					insulator of the power and inter-connecting wires   
					when peeling them.   
					Model RAV-   
					SP420   
					208/230 V, 60 Hz   
					24 A   
					Power supply   
					MCA   
					MOCP (MAX Fuse/CB)   
					Breaker   
					40 A   
					25 A   
					System interconnection wires   
					MCA = Minimum Circuit Amps   
					AWG12   
					MOCP =Maximum Over Protection Device Amps.   
					• Connect the system interconnection (indoor to   
					outdoor) wires to the identical terminal numbers on   
					the terminal block of each unit.   
					Electrical control box   
					Field wiring   
					Incorrect connection may cause a failure.   
					terminal   
					blocks   
					Front panel   
					1. With the front panel removed the electrical control   
					box is exposed at the top right corner of the unit.   
					2. Terminate the field wiring conduit (if used) at the   
					conduit connection holes provided.   
					Banding   
					band   
					3. Route the field power wires and the system   
					interconnection wires as shown on the following   
					pages. Terminate the wires at field wiring terminal   
					blocks located immediately below the electrical   
					control box.   
					Conduit connection   
					holes   
					Piping knockout   
					Front pipe cover   
					EN   
					– 14 –   
					14-EN   
				Installation Manual   
					Outdoor Unit   
					2. Remove the wire cover from back of the front pipe   
					cover.   
					Field power supply   
					terminal block   
					System   
					interconncection   
					terminal block   
					Wire cover   
					Cable cover   
					L1   
					L2   
					S 
					L 
					1 
					L2   
					Ground screw   
					Ground screw   
					System   
					interconnection   
					wires   
					Field power   
					supply wires   
					Banding band   
					3. Pass the wires through the conduit connection holes   
					and attach the conduit connecters.   
					Wiring   
					1. Remove front panel and remove the front pipe   
					cover.   
					Remove the 4   
					screws.   
					Conduit connector   
					4. Connect the wires to the terminal blocks and fix the   
					wires to the wiring guide with the 3 included banding   
					band.   
					Front pipe cover   
					Terminal block   
					Wire guide   
					Fix with the 3   
					banding band   
					15-EN   
					– 15 –   
				Installation Manual   
					Outdoor Unit   
					5. Pass the wires through the wiring guide of the front   
					pipe cover and adjust the wire lengths.   
					8. Connect 2 conduits.   
					Wiring guide   
					conduit   
					6. Attach the wire cover and hold the wires with the   
					wiring guide hooks.   
					Do not clip or damage the wires with the cover.   
					Fix with a screw.   
					Hook   
					Wire cover   
					7. Attach the front pipe cover with 4 screws.   
					Fix with 4   
					screws.   
					EN   
					– 16 –   
					16-EN   
				Installation Manual   
					Outdoor Unit   
					8 EVACUATE AND DEHYDRATE THE   
					SYSTEM   
					6. After evacuation is complete, fully close the low side   
					of manifold gage and stop operation of vacuum   
					pump.   
					CAUTION   
					UNIT DAMAGE HAZARD   
					Failure to follow this caution may result in equipment   
					damage or improper operation.   
					Never use the system compressor as a vacuum pump.   
					Deep Vacuum Method   
					The deep vacuum method requires a vacuum pump   
					capable of pulling a vacuum of 500 microns and a   
					vacuum gage capable of accurately measuring this   
					vacuum depth. The deep vacuum method is the most   
					positive way of assuring a system is free of air and   
					liquid water.   
					Refrigerant tubes and indoor heat exchanger should   
					be evacuated using the recommended deep vacuum   
					method of 500 microns. The alternate triple evacuation   
					method may be used if the procedure outlined below is   
					followed. Always break a vacuum with dry nitrogen.   
					Deep Vacuum Graph   
					5000   
					4500   
					4000   
					SYSTEM VACUUM AND   
					CHARGE   
					LEAK IN   
					SYSTEM   
					3500   
					3000   
					2500   
					2000   
					Using Vacuum Pump   
					1. Completely tighten flare nuts A, B, C, D, connect   
					manifold gage charge hose to a charge port of the   
					low side service valve.   
					VACUUM TIGHT   
					TOO WET   
					1500   
					1000   
					TIGHT DRY   
					SYSTEM   
					500   
					Service Valve   
					Refrigerant   
					Low Side   
					Indoor Unit   
					0 
					1 
					2 
					3 
					4 
					5 
					6 
					7 
					Outdoor Unit   
					C 
					D 
					A 
					B 
					MINUTES   
					High Side   
					Triple Evacuation Method   
					Service Valve   
					The triple evacuation method should only be used   
					when vacuum pump is only capable of pumping down   
					to 28 in. of mercury vacuum and system does not   
					contain any liquid water.   
					Refer to “Triple Evacuation Method chart” and proceed   
					as follows:   
					2. Connect charge hose to vacuum pump.   
					3. Fully open the low side of manifold gage.   
					Manifold   
					Manifold Gage   
					500 microns   
					1. Pump system down to 28 in. of mercury and allow   
					pump to continue operating for an additional 15   
					minutes.   
					Low side valve   
					High side valve   
					Charge hose   
					2. Close service valves and shut off vacuum pump.   
					3. Connect a nitrogen cylinder and regulator to system   
					and open until system pressure is 2 psig.   
					4. Close service valve and allow system to stand for 1   
					hr. During this time, dry nitrogen will be able to   
					diffuse throughout the system absorbing moisture.   
					5. Repeat this procedure as indicated in the chart.   
					System will then be free of any cotaminants and   
					water vapor.   
					Charge hose   
					Vacuum pump   
					Low side valve   
					4. Start vacuum pump.   
					5. Evacuate using either deep vacuum or triple   
					evacuation method.   
					17-EN   
					– 17 –   
				Installation Manual   
					Outdoor Unit   
					Triple Evacuation Method chart   
					Open service valves   
					EVACUATE   
					Open or close the valve.   
					▼ 
					▼ Liquid side   
					BREAK VACUUM WITH DRY NITROGEN   
					Open the valve with a 4 mm hexagon wrench.   
					▼ 
					WAIT   
					▼ Gas side   
					▼ 
					Valve unit   
					EVACUATE   
					▼ 
					BREAK VACUUM WITH DRY NITROGEN   
					▼ 
					WAIT   
					Using a straight blade   
					▼ 
					EVACUATE   
					▼ 
					screwdriver, turn it 90°   
					counter clockwise until   
					the valve is fully open   
					(against the stop).   
					Charge orifice   
					CHECK FOR TIGHT, DRY SYSTEM   
					(IF IT HOLDS DEEP VACCUM)   
					▼ 
					Flare nut   
					RELEASE CHARGE INTO SYSTEM   
					Final Tubing Check   
					Handle position   
					Fully closed   
					Fully opened   
					IMPORTANT:   
					Check to be certain factory tubing on both indoor and   
					outdoor unit has not shifted during shipment. Ensure   
					tubes are not rubbing against each other or any sheet   
					metal. Pay close attention to feeder rubes, making sure   
					wire ties on feeder tubes are secure and tight.   
					Stop pin   
					Main stopper   
					• While the valve is fully opened, after the screwdriver   
					has reached the stopper, do not apply torque   
					exceeding 4 ft•lbs (5 N•m). Applying excessive   
					torque may damage the valve.   
					Valve handling precautions   
					• Open the valve stem until it reaches the stop.   
					It is unnecessary to apply further force.   
					• Securely tighten the cap with a torque wrench.   
					• Cap tightening torque   
					Ø3/8” (9.5 mm)   
					24 - 31 ft•lbs (33 - 42 N•m)   
					Valve size   
					Ø5/8” (15.9 mm) 15 - 18 ft•lbs (20 - 25 N•m)   
					10 - 13 ft•lbs (14 - 18 N•m)   
					Charge port   
					EN   
					– 18 –   
					18-EN   
				Installation Manual   
					Outdoor Unit   
					9 FINISHING   
					After the refrigerant pipe, inter-unit wires, and drain pipe have been connected, make sure they are supported and   
					fixed in place for the entire length.   
					Keep the power wires and system interconnection wires away from all factory wiring and piping.   
					10TEST RUN   
					• Turn on the circuit breaker at least 12 hours before starting the system to preheat the compressor and   
					prevent damage.   
					To protect the compressor, power is supplied from the 208/230 VAC input to the unit to preheat the compressor.   
					• Check the following before starting a test run:   
					• That all pipes are connected securely without leaks.   
					• That the valve is open.   
					If the compressor is operated with the valve closed, the outdoor unit will become over pressurized, which may   
					damage the compressor or other components.   
					If there is a leak at a connection, air can be sucked in and the internal pressure further increases, which may   
					cause a burst or injury.   
					• Operate the air conditioner using the correct procedure as specified in the Owner’s Manual.   
					11PERIODIC MAINTENANCE   
					• For an air conditioning system that is operated on a regular basis, cleaning and maintenance of the indoor/   
					outdoor units are strongly recommended.   
					As a general rule, if an indoor unit is operated for about 8 hours daily, the indoor/outdoor units will need to be   
					cleaned at least once every 3 months. This cleaning and maintenance should be carried out by a qualified   
					service person.   
					Failure to clean the indoor/outdoor units regularly will result in poor performance, icing, water leaking and even   
					compressor failure.   
					19-EN   
					– 19 –   
				Installation Manual   
					Outdoor Unit   
					12TROUBLESHOOTING   
					You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition   
					to using the check codes displayed on the wired remote controller of the indoor unit.   
					Use the LEDs and error codes for various checks. Details of the error codes displayed on the wired remote   
					controller of the indoor unit are described in the Installation Manual of the indoor unit.   
					Verifying Error code status (Outdoor control   
					board)   
					Verifying Error code status stored in   
					memory (Outdoor control board)   
					1. Check that DIP switch SW803 is set to off.   
					2. Record the states (on or off) of LED 800 to LED 804   
					(Display mode 1).   
					1. Check that DIP switch SW803 is set to on.   
					2. Record the states (on or off) of LED 800 to LED 804   
					(Display mode 1).   
					3. Press SW800 for at least 1 second. The LED status   
					changes to display mode 2.   
					3. Press SW800 for at least 1 second. The LED status   
					changes to display mode 2.   
					4. Since display mode 1 covers multiple errors with the   
					same code display, mode 2 must also be used to   
					determine the final error. Use the status recorded for   
					LED 800 to LED 804 in display mode 1 (Item 2   
					above) and combine it with the status for the same   
					LED’s in display mode 2 (Item 3 above) to determine   
					the complete error code using the chart below.   
					4. Since display mode 1 covers multiple errors with the   
					same code display, mode 2 must also be used to   
					determine the final error. Use the status recorded for   
					LED 800 to LED 804 in display mode 1 (Item 2   
					above) and combine it with the status for the same   
					LED’s in display mode 2 (Item 3 above) to determine   
					the complete error code using the chart below.   
					NOTE   
					An outside air temperature (TO) sensor error can be   
					checked only when an error occurs.   
					Display mode 1   
					Display mode 2   
					No.   
					Cause   
					D800 D801 D802 D803 D804 D800 D801 D802 D803 D804   
					1 
					2 
					3 
					4 
					5 
					6 
					7 
					Normal   
					● 
					{ 
					{ 
					{ 
					{ 
					{ 
					{ 
					● 
					{ 
					{ 
					{ 
					{ 
					{ 
					{ 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					{ 
					{ 
					{ 
					{ 
					{ 
					{ 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					Discharge (TD) sensor error   
					Heat exchanger (TE) sensor error   
					Heat exchanger (TL) sensor error   
					Outside air temperature (TO) sensor error   
					Suction (TS) sensor error   
					● 
					● 
					● 
					● 
					● 
					Heat sink (TH) sensor error   
					Outdoor temperature sensor (TE/TS) connection   
					error   
					8 
					9 
					{ 
					{ 
					● 
					● 
					{ 
					● 
					Outdoor EEPROM error   
					{ 
					● 
					● 
					● 
					● 
					{ 
					● 
					● 
					● 
					● 
					● 
					{ 
					{ 
					{ 
					{ 
					● 
					● 
					● 
					● 
					● 
					{ 
					{ 
					{ 
					{ 
					{ 
					10 Compressor lock   
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					● 
					11 Compressor lock   
					● 
					12 Current detection circuit error   
					13 Thermostat for compressor activated   
					● 
					● 
					Model data not set   
					14   
					● 
					{ 
					{ 
					● 
					{ 
					● 
					● 
					● 
					(on the service P.C. board)   
					15 MCU-MCU communication error   
					16 Discharge temperature error   
					● 
					{ 
					{ 
					{ 
					{ 
					● 
					● 
					{ 
					{ 
					● 
					● 
					{ 
					● 
					● 
					● 
					● 
					● 
					Abnormal power   
					(open phase detected or abnormal voltage)   
					17   
					{ 
					{ 
					{ 
					● 
					{ 
					EN   
					18 Heat sink overheat   
					{ 
					{ 
					{ 
					{ 
					{ 
					{ 
					{ 
					{ 
					{ 
					{ 
					{ 
					{ 
					● 
					● 
					● 
					● 
					{ 
					{ 
					{ 
					{ 
					● 
					● 
					19 Gas leak detected   
					20 4-way valve reverse error   
					21 High pressure release operation   
					● 
					● 
					● 
					● 
					● 
					– 20 –   
					20-EN   
				Installation Manual   
					Outdoor Unit   
					22 Outdoor fan motor error   
					{ 
					{ 
					{ 
					{ 
					{ 
					{ 
					{ 
					{ 
					{ 
					● 
					● 
					● 
					{ 
					{ 
					{ 
					● 
					● 
					● 
					23 Compressor driver short-circuit protection   
					24 Position detection circuit error in one-line display   
					● 
					● 
					(●:OFF {:ON :Flashing)   
					* The LEDs and DIP switches are located on the lower left of the P.C. board of the outdoor unit.   
					SW801   
					SW800   
					Enlargedview   
					of LEDs   
					D800   
					LED   
					D800   
					D801   
					D802   
					D803   
					D804   
					D805   
					SW804   
					D801   
					D802   
					D803   
					D804   
					D805   
					SW803   
					SW802   
					21-EN   
					– 21 –   
				Installation Manual   
					Outdoor Unit   
					13UNIT PUMP DOWN   
					• Use the pump down switch SW801 on the P.C. board of the outdoor unit to pump down the unit.   
					Procedure   
					1. Turn on the power of the air conditioner.   
					2. Select the FAN mode for indoor unit operation with the remote controller.   
					3. Set SW804 on the P.C. board of the outdoor unit to all OFF, and then press SW801 for 1 second or more. The   
					air conditioner enters the forced cooling mode for up to 10 minutes.   
					Pump down the unit during this 10 minutes.   
					4. Upon completion of pump down the unit, close the valve and press SW801 for at least 1 second to stop   
					operation.   
					5. Turn off the power.   
					P.C. board   
					Refrigerant   
					recovery switch   
					SW801   
					Optional   
					connector CN610   
					Special operation   
					select switch   
					SW804   
					Power save switch   
					SW802   
					DANGER   
					Be careful of electric shock because the P.C. board has an electrical current running through it.   
					14POWER SAVE   
					• Power save can be set by setting SW802 dip switch.   
					Procedure   
					1. Turn on the SW802 dip switch 2 to activate Power save.   
					Power save controls reducing compressor periodicity (by approx. 10%) depending on the indoor unit heat   
					exchanger temperature in heating operation   
					SW802   
					... Power save setting   
					* All switches are OFF as factory default.   
					EN   
					CAUTION   
					Do not touch SW802 dip switch 1, 3 and 4.   
					If any changes are made, the unit may not work properly.   
					22-EN   
					– 22 –   
				EH99865501   
				 |