| Technical Instructions   Document No. 155-517P25   July 9, 2007   SQM5…   Reversing Actuators   ISO 9000 and 14000   REGISTERED FIRM   ¤ Description   SQM5... reversing actuators are used for the positioning of flow control valves, butterfly   valves, dampers, or any application requiring rotary motion. The SQM5… actuators   accommodate control input signals of 4 to 20 mA, 0 to 135 Ω, 0 to 10 Vdc, 0 to 20 mA,   position proportional and floating control. The available output signals include   4 to 20 mA, 0 to 135 Ω, 0 to 10 Vdc, 0 to 20 mA, and 0 to 1000 Ω. SQM5… actuators   are available with up to six internal, easily adjustable switches.   A selection of exchangeable circuit boards provide a variety of functions including   auto/manual selector switch, manual forward/reverse toggle switch, zero and span   adjustment, parallel or master/slave operation, split range control, input signal override,   and selectable electronic linearization.   The SQM5… is engineered for precision. It is particularly well suited for applications   requiring a high degree of modulating accuracy and repeatability. Drive shaft play is   limited to 0.3° with a modulating accuracy of 250 repositions through 90° of travel.   The SQM5… actuator may be mounted in any position. A selection of mounting   brackets and shafts provides installation flexibility and allows for the simple   replacement of most competitive actuators.   • • • • • • • • • • • Modulating accuracy of 250 repositions through 90°   Two limit switches, plus up to four internal auxiliary switches   Fully closed “economy position” switch   Features   Drive shaft and cam drum disengagement clutches   Auto/manual switch, manual control forward/reverse toggle switch   UL, CSA approved 24 and 110 Vac versions   CE approved 220 Vac versions   Field reversible clockwise (cw) or counterclockwise (ccw) operation   Various torque ratings and running times available   Selection of field exchangeable single-ended and dual-ended shafts   Mounting brackets to replace competitive actuators   Siemens Building Technologies, Inc.   SQM5… Reversing Actuators   Technical Instructions   Document No. 155-517P25   July 9, 2007   Table Of Contents   Application   Page 2   Product Numbers   Product numbers for pre-assembled UL/CSA/CE-approved   actuators, Table 1   Product numbers for accessories, Table 2   SQM5… Product Number Identification Legend   Installation and Operating Instructions   Shaft Installation   Page 4   Page 5   Page 6   Page 7   Page 8   Page 8   Page 8   Page 9   Page 9   Rotational Direction Verification   Actuator Mounting   Switch Adjustment   Shaft Adjustment   Cam Drum Adjustment   Wiring   Electrical Connection   Grounding   Page 9   Page 9   Wiring Connections   AGA56.1… circuit boards   AGA56.41/42/43… circuit boards   AGA56.9… circuit boards   Commissioning   Page 10   Page 11   Page 13   Modulation Adjustment   Zero Adjustment   Span Adjustment   Page 15   Page 15   Page 15   Page 16   Cover Installation   Features   SQM5x.xxxxxZx actuators   SQM5x.xxxxxGx actuators   SQM5x.xxxxxHx actuators   SQM5x.xxxxxKx actuators   SQM5x.xxxxxAx actuators   Service Guide   Page 16   Page 18   Page 18   Page 18   Page 18   Reversing Rotational Direction   Shaft Installation   Circuit Board Installation   AGA56.41/42/43…   Page 18   Page 20   Page 20   Page 20   Page 22   Page 24   Page 25   Page 26   Page 29   AGA56.9A   AGA56.1A97   Potentiometer Removal/Installation   Specification Data   Dimensions   Siemens Building Technologies, Inc.   Page 3   Technical Instructions   Document No. 155-517P25   July 9, 2007   SQM5… Reversing Actuators   Table 1. Product Numbers for Pre-assembled Actuators.   Product Numbers   Torque1   Running   Input Control Signals3   Product Number   220 V   Time 2   [lb-in]   90°@ 60   110 V   24 V   Hzsec   90   90   90   90   90   90   90   8 8 8 8 8 8 8 ccw   cw   ccw   cw   ccw   cw   ccw   ccw   cw   ccw   ccw   cw   ccw   ccw   ccw   cw   ccw   ccw   ccw   ccw   cw   x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x SQM50.261R1G3   SQM50.261R1G3R   SQM50.264R1A   SQM50.264R2A   SQM50.264R1A0R   SQM50.264R1A3   SQM50.264R1G3R   SQM50.264R1G4   SQM50.361R1G3   SQM50.361R1G3R   SQM50.361R1G7   SQM50.364R1G3   SQM50.364R1G3R   SQM50.461R1A   SQM50.461R1A3   SQM50.461R1G3   SQM50.461R1G3R   SQM50.461R1H3   SQM50.461R1Z3   SQM50.461R1Z7   SQM50.464R1A   x x x x x x x 140   140   140   140   140   140   140   140   140   140   140   140   140   140   140   140   140   140   140   140   140   140   200   200   200   200   200   200   200   200   200   310   310   310   310   310   400   400   400   400   400   400   12   12   12   12   12   25   25   25   25   25   25   25   25   25   25   25   25   25   25   25   25   25   25   25   25   25   25   25   25   25   25   37   37   37   37   37   50   50   50   50   50   50   x x x x x x x x x SQM50.464R8A   SQM50.464R8G3   SQM50.464R1A0R   SQM50.464R1A3   SQM50.464R1A3R   SQM50.464R1G3   SQM50.464R1G3R SQM50.464R2G3R   SQM50.464R1G7   ccw   cw   ccw   cw   ccw   cw   x x x x SQM50.464R1G7R   SQM50.464R1H3   ccw   ccw   ccw   ccw   ccw   ccw   cw   ccw   ccw   cw   ccw   ccw   ccw   ccw   ccw   ccw   ccw   ccw   cw   x x SQM50.464R8H3   SQM50.464R8Z3   x x SQM50.464R1Z3   SQM53.464R1A   SQM53.464R1A3   SQM53.464R1G3   SQM53.464R1G7   SQM53.464R1G7R   SQM53.464R1Z3   SQM53.467R1Z3   SQM53.467R1Z3R   SQM50.464R2Z3   x x x x x x x x x x x x SQM53.464R2Z3   SQM53.467R2A3   SQM56.564R1A   SQM56.564R1G4   SQM56.564R1G7   SQM56.564R1H4   SQM56.564R1Z3   SQM56.664R1G3   SQM56.664R1Z3   SQM56.667R1A3R   SQM56.667R1G3   SQM56.667R1G7R   SQM56.667R1Z3   x x x x x x x x x x ccw   cw   ccw   x x x x x 1. Torque will vary with the selection of the shaft. See Specifications.   2. Running time for 135° Æ multiply by 1.5. For 50 Hz Æ multiply by 1.2   3. SQM5x.xxxxxZx models also accept a 0 to 20 mA input signal.   Page 4   Siemens Building Technologies, Inc.   SQM5… Reversing Actuators   Technical Instructions   Document No. 155-517P25   July 9, 2007   Table 2. Product Numbers for Accessories.   Shafts   Electronic Circuit Boards   AGA58.1 10 mm round with key. Gear end only.   AGA58.2 12 mm round with key. Gear end only.   AGA58.3 9 mm square. Dual-ended.   AGA58.4 3/8 inch square. Dual-ended.   AGA58.7 14 mm round with key. Gear end only.   For exact shaft sizes, see Dimensions.   AGA56.1A97 24-250 Vac (A) board for SQM5x.xxxxxAx   AGA56.9A87 24 Vac   AGA56.9A17 110 Vac   AGA56.9A27 220 Vac   AGA56.41A87 24 Vac   AGA56.41A17 110 Vac   AGA56.41A27 220 Vac   AGA56.42A87 24 Vac   AGA56.42A17 110 Vac   AGA56.42A27 220 Vac   AGA56.43A87 24 Vac   AGA56.43A17 110 Vac   AGA56.43A27 220 Vac   (Z) board for SQM5x.xxxxxZx   (Z) board for SQM5x.xxxxxZx   (Z) board for SQM5x.xxxxxZx   (G) board for SQM5x.xxxxxGx   (G) board for SQM5x.xxxxxGx   (G) board for SQM5x.xxxxxGx   (H) board for SQM5x.xxxxxHx   (H) board for SQM5x.xxxxxHx   (H) board for SQM5x.xxxxxHx   (K) board for SQM5x.xxxxxKx   (K) board for SQM5x.xxxxxKx   (K) board for SQM5x.xxxxxKx   Crank Arm, Push Rods   338 031 Crank arm kit. Includes two crank arms for   connecting the AGA58.4 shaft to a ∅ 1/2-inch   damper shaft with two ball joints. (Does not include   push rod.)   338 041 ∅ 5/16" damper push rod, 12 inches long.   338 042 ∅ 5/16" damper push rod, 15 inches long.   338 043 ∅ 5/16" damper push rod, 18 inches long.   338 044 ∅ 5/16" damper push rod, 24 inches long.   338 045 ∅ 5/16" damper push rod, 36 inches long.   338 046 ∅ 5/16" damper push rod, 48 inches long.   See Product Number Identification Legend, Figure 1.   Mounting Brackets & Adapters   AGA57.3 for replacement of Honeywell MOD III, IV   actuators   AGA57.4 for replacement of Honeywell M640/740/940 and   Barber Colman EA20/40/50/60 actuators. Directly   adaptable to Eclipse butterfly valves.   ASK33.9 mounting kit for direct attachment to Siemens   VKF41... butterfly valve. (Shaft AGA58.1   required)   Potentiometers   ASZ12.803 and ASZ12.30 1000Ω, 90°   ASZ12.833 and ASZ12.33 1000Ω, 135°   ASZ22.803 and ASZ22.30 1000/1000Ω double   potentiometer, 90°   ASZ22.833 and ASZ22.33 1000/1000Ω double   potentiometer, 135°   ASZ16.703 135Ω, 90° (wire wound)   ASZ16.733 135Ω, 135° (wire wound)   ASZ66.733 135Ω/135Ω, double potentiometer 135°   (wire wound)   Additional potentiometer models available. See   Siemens technical data sheet 7921.   Siemens Building Technologies, Inc.   Page 5   Technical Instructions   Document No. 155-517P25   July 9, 2007   SQM5… Reversing Actuators   Product Number Identification Legend   For actuator identification only. To select product numbers for ordering, see Table 1.   Figure 1. SQM5… Product Number Identification Legend.   SQM5   0 . 4 8 0 R 1 Z 3 R Actuator family   Torque in-lb @ 60 (50) Hz.   0 0 3 6 6 90 for 8 (10) sec. running time   140 for 12 (15), 25 (30), 37 (45) sec.   200 for 25 (30) sec.   310 for 37 (45) sec.   400 for 50 (60), 75 (90)sec.   Running time for 90°   Not all actuator running times are   available in each torque.   Refer to table 1   60 Hz.   50 Hz.   2 10 sec.   2 3 4 5 6 8 sec.   12 sec.   25 sec.   37 sec.   50 sec.   3 4 5 6 15 sec.   30 sec.   45 sec.   60 sec.   Number of SPDT switches   2 limit and 4 auxiliary switches   6 Shaft selection   no shaft (shaft must be ordered separately)   round 10 mm, single ended (for use with VKF41... butterfly valves)   square 3/8 inch, dual ended   0 1 4 7 round 14 mm, single ended   Approvals   R UL recognized, CSA certified   Operating voltage (Vac @50-60 Hz)   1 2 8 110-120 Vac   220-240 Vac   24 Vac   Internal circuit board (SQM5x.xxxxx G, H, K , Zx actuators require potentiometer ASZ…)   A G H K Z AGA56.1A97 (position proportional control)   AGA56.41A... (4 to 20 mA input)   AGA56.42A... (0 to 135 Ohm input)   AGA56.43A... (0 to 10 Vdc input)   AGA56.9... (all inputs/outputs, linearization, split ranging, override and pre-set positioning)   (1000 Ohm required when using SQM5x.xxxxx G, H, K, Zx actuators)   Potentiometer   3 4 ASZ12.30 (1000 ohm, 90°)   ASZ12.33 (1000 Ohm, 135°)   7 8 B C L ASZ22.30 (1000/1000 Ohm, 90°)   ASZ22.33 (1000/1000 Ohm, 135°)   ASZ16.703 (135 Ohm, 90°)   ASZ16.733 (135 Ohm, 135°)   ASZ66.733 (135/135 Ohm, 135°)   Rotational Direction   Clockwise (when facing gear end. See Figure 6 .)   (Product numbers ending without R are ccw)   R Page 6   Siemens Building Technologies, Inc.   SQM5… Reversing Actuators   Technical Instructions   Document No. 155-517P25   July 9, 2007   Installation and   Operation   SQM5… actuators are sometimes shipped without the shaft installed. To install the   selected shaft:   Instructions   1. Loosen the two screws on the actuator cover corners. See Figure 2.   2. Lift the screws and raise the cover. See Figure 3.   Shaft Installation   Figure 3.   Figure 2.   3. Each shaft is supplied with two washers and a “C” clip. See Figure 4. Using   spreading pliers, remove the “C” clip and the washers from the shaft.   KEY END   INSERT END   SHAFT KEY   WASHERS ON   BOTH SIDES   OF THE BEARING   C-CLIP   Figure 4.   4. Insert the “insert end” of the shaft into the “gear end” of the actuator.   5. Push the shaft until the “insert end” reaches just short of the brass bushing at the   other end of the actuator.   6. Put one of the washers on the insert end of the shaft. See Figure 5.   WASHERS   Figure 5.   7. Line up the “shaft key” with the key slot on the “gear end” of the actuator and slide   the shaft until the “insert end” is completely through the brass bushing.   8. Place the second washer onto the “insert end” of the shaft. Using spreading pliers,   install the “C” clip.   Siemens Building Technologies, Inc.   Page 7   Technical Instructions   Document No. 155-517P25   July 9, 2007   SQM5… Reversing Actuators   Actuator model numbers that end with “R” are factory configured for clockwise (cw),   minimum to maximum rotation when facing the gear end of the actuator, or   counterclockwise (ccw) rotation when facing the other end of the actuator. The gear end   of the actuator is the side opposite of the visual position indicator.   Rotational Direction   Verification   To field reverse the direction of rotation, see Service Guide, “Reversing Rotational   Direction”.   Actuator Mounting   SQM5… actuators can be mounted in any orientation using the four 1/4"-20 UNC   tapped holes located on the bottom corners of the actuator base. Optional base   mounting brackets are available. See Table 2.   SQM5… actuators can also be face mounted using self tapping screws in combination   with the various holes on the face of the actuator gear end.   ACTUATOR   POSITION SCALE   SWITCH CAM I   SET AT MAXIMUM   ACTUATOR POSITION   INDICATING DIAL   DIAL POINTER   SWITCH CAM II   SET AT ZERO ("ECONOMY")   ACTUATOR POSITION   INDICATING POINTER   CAM DRUM   ASZ... (1000 Ohm)   FEEDBACK POTENTIOMETER   SWITCH CAM III   SET AT MINIMUM   50   30   50   30   50   30   10   0 10   CAM DRUM   RELEASE BUTTON   30   50   10   0 10   0 10   0 0 0 0 70   SINGLE SWITCH   CAM POINTER   GEAR END   DOUBLE SWITCH CAM POINTER   Figure 6. Component Identification on the Cam Drum Side of the SQM5… Actuator.   Switch Adjustment   All SQM5…actuators are factory wired with Switch I (maximum), Switch II (fully closed   “economy position”) and Switch III (minimum). The individual switch cams I, II, and III   are factory set to 90°, 0° and 10° respectively.   See Figure 6.   NOTE: The single switch cam pointers are used together with the black scales when   configured for counterclockwise (ccw) operation.   The double switch cam pointers are used together with the red scales when   configured for clockwise (cw) operation.   The individual switch cams can be adjusted by hand or with the use of the tool   attached to the outside of the hinged switch terminal protection lid.   Page 8   Siemens Building Technologies, Inc.   SQM5… Reversing Actuators   Technical Instructions   Document No. 155-517P25   July 9, 2007   Switch Adjustment,   Continued   NOTE: If a potentiometer is installed, the adjustable range of the switches depends   on the range of the potentiometer.   SQM5x.xxxxxAx actuators may be adjusted between 0° and 160°.   SQM5x.xxxxxx3 actuators have a 90° potentiometer and the switches must be   adjusted only between 0 and 90°.   SQM5x.xxxxxx4 actuators have a 135° potentiometer and the switches must   be adjusted only between 0 and 135°.   Shaft Adjustment   The actuator shaft can be disengaged by pressing the silver shaft release button. The   button is located above the grounding screw, under the hinged terminal protection   cover, and to the right of the auto/manual switch. After pressing the shaft release button   in and slightly upward, the shaft can be manually rotated. After the shaft has been   manually aligned to the closed position, re-engage the shaft by pushing the shaft   release button downwards.   See Figure 6.   Once the shaft has been set, the cam drum must be manually aligned by pressing and   holding the black cam drum release button (see Figure 6). Rotate the cam drum until   the “0” mark on the actuator position scale (left scale on the cam drum) is aligned with   the gray actuator position indicating pointer.   Cam Drum Adjustment   See Figure 6.   Position Indicating Dial   Adjustment   The actual position of the SQM5… actuator is indicated by the gray actuator position   indicating pointer (see Figure 6). The position is also displayed by the indicating dial   through the housing’s window. Ensure that the actuator position indicating dial is   aligned with the actuator position scale. If necessary, rotate the dial in the clockwise   direction.   CAUTION:   Turning the dial in the counterclockwise direction may loosen the   potentiometer locking screw.   Wiring   SQM5… actuators are equipped with two removable conduit connection plates located   on the upper corner of the gear housing. Each plate is provided with two threaded   connections for 1/2" NPSM conduit connectors. The use of flexible stranded wire is   recommended.   Electrical Connection   Grounding   CAUTION:   To avoid electro-magnetic interference, the SQM5… actuators must be   grounded.   The ground terminal is located to the right of the auto/manual switch.   Disconnect the circuit board wire marked 51 during high voltage testing.   Reconnect it to the grounding terminal after the test.   Siemens Building Technologies, Inc.   Page 9   Technical Instructions   Document No. 155-517P25   July 9, 2007   SQM5… Reversing Actuators   Wiring Connections   NOTE: SQM5… actuators require a single source, single phase power supply.   Wiring connections vary depending on which AGA56…. circuit board is installed.   AGA56.1… circuit boards.   Manual Operation   See Figures 7 and 8.   1. Set the AUTO/MAN switch in the MAN position.   2. Connect ground to the screw located below the shaft release button.   3. Connect neutral to the double terminal block, located on the left side of the gray   switch housing.   4. Only terminal "L" must be to enable manual operation. The actuator can now be   driven to the maximum position (switch cam I) or the fully closed "economy   position" (switch cam II) by using the toggle switch located to the left of the   AUTO/MAN switch.   Automatic Operation   1. Set the AUTO/MAN switch in the AUTO position.   2. Connect ground to the screw located below the shaft release button.   3. Connect neutral to the double terminal block located on the left side of the gray   switch housing.   4. Connect line voltage to terminal A to drive the actuator in the opening direction.   5. Connect line voltage to terminal Z to drive the actuator in the closing direction.   CAUTION:   Do not power terminals A and Z simultaneously. Actuator damage will occur.   A L Z AGA56.1A97   51   actuator switch   I Maximum/High fire   MAN   AUTO   shown in   auto position   II   III   IV...VI   "Economy"/Fully closed   Minimum/Low fire   Auxilliary   1 1 2 13   N c b 4 3 5 6 2 V VI   I II   IV   III   13 23   wire leads   ASZ...   (1000 Ohm)   M 11 21   12 22   14 24   15 25   16 26   21 12   a Figure 7. Basic Functional Diagram of AGA56.1…   Page 10   Siemens Building Technologies, Inc.   SQM5… Reversing Actuators   Technical Instructions   Document No. 155-517P25   July 9, 2007   Wiring, Continued   A A Z Z L L MAN.   0 AUTO.   AGA56.1A97   Figure 8. AGA56.1A97 Terminal/Auto-Manual Board.   Manual Operation   AGA56.41/42/43…   Circuit Boards.   1. Set the AUTO/MAN switch in the MAN position.   2. Connect ground to the screw located below the shaft release button.   3. Connect neutral to terminal N.   See Figures 9 and 10.   4. Only terminal "L" must be powered to enable manual operation. The actuator can   now be driven to the maximum (high fire) position (switch cam I) or the fully closed   "economy position" (switch cam II) by using the toggle switch located to the left of   the AUTO/MAN switch.   Automatic Operation   1. Set the AUTO/MAN switch in the AUTO position.   2. Connect ground to the screw located below the shaft release button.   3. Connect neutral to terminal N.   4. Connect line voltage at all times to terminal L to provide power to the electronic   circuit board.   5. Connect line voltage to terminal LR to provide power when modulating. Connect   line voltage to Terminal LR only after removing power on terminals A and Z   (otherwise actuator damage may result).   6. Connect line voltage to terminal A to drive the actuator to the maximum (high fire   purge) position.   Once the maximum position is reached, terminal 11 (on switch I) will be energized   to provide position feedback.   7. Connect power to terminal ZL to drive the actuator to the minimum (low-fire)   position. Once the minimum position is reached, terminal 23 (on switch III) will be   energized to provide position feedback. Adjustment of switch III will determine the   low-fire stop position. Switch III (low fire) must be set at a higher position than   switch II (fully closed). Terminal ZL may be energized only after removing power   from terminals A, Z, 13, and LR.   8. Connect line voltage to terminal Z to drive the actuator to the fully closed/economy   position (switch II).   9. Connect the input control signal wires to the appropriate terminals. See Figure 9.   CAUTION:   Do not power terminals A and Z simultaneously. Actuator damage will   occur.   Siemens Building Technologies, Inc.   Page 11   Technical Instructions   Document No. 155-517P25   July 9, 2007   SQM5… Reversing Actuators   Wiring, Continued   A 13 ZL   LR   N Z L AGA56.4...   Y+   AGA56.41...   ("G" board 4...20 mA)   Y-   (+2 V)   B U M Y AGA56.42...   ("H" board   0-135 Ohm)   135 Ohm   REG   OPE   MAX   MIN   W R MAX   MIN   0...2 V   MIN   MAX   Y M Y AGA56.43...   ("K" board 0...10 V)   51   MIN MAX   MAN   AUTO   shown in   actuator switch   auto position   I Maximum/High fire   II   III   IV...VI   "Economy"/Fully closed   Minimum/Low fire   Auxilliary   N 1 2 13   3 c b 1 2 3 4 5 6 I II   III   13 23   wire leads   IV   V VI   ASZ...   (1000 Ohm)   M 11 21   12 22   14 24   15   25   16   26   21 12   a Figure 9. Basic Functional Diagram of AGA56.4…   OPE MAX MIN   Y-   Y+   ZL   N 13   LR   A Z L OPE MAX MIN   Y M U ZL   N 13   LR   A Z L MAX   MAX   MIN   MIN   MAN.   AUTO.   MAN.   0 0 AUTO.   AGA56.42A...   AGA56.41A...   "H" Board   0 to 135 ohm   "G" Board   4 to 20mA   ZL   13   LR   A Z L N OPE MAX MIN   Y M MAX   MIN   MAN.   AUTO.   0 AGA56.43A...   "K" Board   0 to 10V   Figure 10. AGA56.41/42/43… Terminal and Trim Potentiometer Boards.   Page 12   Siemens Building Technologies, Inc.   SQM5… Reversing Actuators   Technical Instructions   Document No. 155-517P25   July 9, 2007   AGA56.9… Circuit   Boards   Manual Operation   1. Set the AUTO/MAN switch in the MAN position.   See Figures 11 and 12.   2. Connect ground to the screw located below the shaft release button.   3. Connect neutral to terminal N.   4.   Only terminal "L" must be powered to enable manual operation. The actuator can   now be driven to the maximum (high fire) position (switch cam I) or the fully closed   "economy position" (switch cam II) by using the toggle switch located to the left of   the AUTO/MAN switch.   Automatic Operation   1. Set the AUTO/MAN switch in the AUTO position.   2. Connect ground to the screw located below the shaft release button.   3. Connect neutral to terminal N.   4. Connect line voltage at all times to terminal L to provide power to the electronic   circuit board.   5. Connect line voltage to terminal L1 to provide power when modulating. Connect line   voltage to terminal L1 only after removing power on terminals A and Z (otherwise   actuator damage may result).   6. Connect line voltage to terminal A to drive the actuator to the maximum (high fire   purge) position. Once the maximum position is reached, terminal 11 (on switch I)   will be energized to provide position feedback.   7. Connect power to terminal ZL to drive the actuator to the minimum (low-fire)   position. Once the minimum position is reached, terminal 23 (on switch III) will be   energized to provide position feedback. Adjustment of switch III will determine the   low-fire stop position. Switch III (low fire) must be set at a higher position than   switch II (fully closed). Terminal ZL may be energized only after removing power   from terminals A, Z, 13, and LR.   8. Connect line voltage to terminal Z to drive the actuator to the fully closed/economy   position (switch II).   9. Connect the input control signal wires to the appropriate terminals. See Figure 11.   CAUTION:   Do not power terminals A and Z simultaneously. Actuator damage will   occur.   Siemens Building Technologies, Inc.   Page 13   Technical Instructions   Document No. 155-517P25   July 9, 2007   SQM5… Reversing Actuators   Wiring, Continued   N A L Z ZL   L 1 P AGA56.9...   SHIFT   ZF   POS   LIN   20 mA   18 mA 16 mA   4...20 mA   14 mA   MAX   75%   M 0 or 12 mA   10 mA   8 6 mA   mA   ZF   = 50%   25%   MIN   POS   4 mA   (+2 V)   B U 4 MIN25% 50%75% MAX   Y0...3   Y0...3   Y0...3   135 Ohm   W R M 0...2 V   Y 0 POS   M 1 2 REG   4...20 mA   0...10 V   Y 3 OPE   MAX   MIN   MAX   MIN   J1   M LIN   Y 1 MIN   MAX   Y0...3   M 0...20 mA   MAX   MIN   Y2   51   U 3 4...20 mA   0...20 mA   1 2 U2   0...10 V   U 1 MAN   AUTO   shown in   auto position   J2   actuator switch   I Maximum/High fire   common   M II   III   IV...VI   "Economy"/Fully closed   Minimum/Low fire   Auxilliary   N 1 2 13   3 c b 1 2 3 4 5 6 II   IV   V VI   I III   13 23   wire leads   ASZ...   (1000 Ohm)   M 11 21   12 22   14 24   15   25   16   26   21 12   a Figure 11. Basic Functional Diagram of AGA56.9…   U M Y 0 Y 1 Y 2 Y 3 L P L N A Z ZL   4 1 1 2 1 2 OPE   MAX   MIN   J1   J2   LIN   MAX POS MIN   U1...U3   JUMPERS   3-POSITION   SWITCH   POT. METERS   ZF   M M U U U 3 1 2 MAN.   0 AUTO.   AGA56.9A...   Figure 12. AGA56.9… Terminal and Trim Potentiometer/Jumper Board.   Page 14   Siemens Building Technologies, Inc.   SQM5… Reversing Actuators   Technical Instructions   Document No. 155-517P25   July 9, 2007   Modulation Adjustment   The blue trim potentiometers allow the adjustment of the minimum (zero) and   maximum (span) positions.   See Figures 10 and 12.   The factory setting of the MIN trim potentiometer is rotated fully counter clockwise.   The factory setting of the MAX trim potentiometer is rotated fully clockwise.   Zero Adjustment   Set the OPE/MAX/MIN slide switch to MIN. The blue MIN trim potentiometer can now   be gently adjusted to the required minimum position. Return the OPE/MAX/MIN slide   switch to OPE for operation.   NOTE: Do not set switch cam I higher than:   90° when using feedback potentiometers ASZxx.30   135° when using feedback potentiometers ASZxx.33   Span Adjustment   Set the OPE/MAX/MIN slide switch to MAX. The blue MAX trim potentiometer can now   be gently adjusted to the required maximum position. Return the OPE/MAX/MIN slide   switch to OPE for operation.   NOTE: The actual minimum and maximum   modulating range is determined either   by the setting of the MIN and MAX trim   potentiometers or the setting of switch   Example of limit switch I and III   and trim potentiometer settings   cam III (Minimum) and switch cam I   (Maximum). The actuator can never   modulate outside of the range set by   switch cam I and III. If the MIN and MAX   trim potentiometers are set outside the   setting range of switch cams I and III,   then the switch cam settings determine   the modulating range. If a soft stop is   desired, the modulating range can be   defined by the trim potentiometers if the   MIN and MAX trim potentiometers are   set inside the setting range of switch   cams I and III. See the example in   Figure 13.   0 deg.   Figure 13. Switch cam and Trim   Potentiometer Setting.   Siemens Building Technologies, Inc.   Page 15   Technical Instructions   Document No. 155-517P25   July 9, 2007   SQM5… Reversing Actuators   1. Lift the two screws on the cover corners and slide the cover end into the grooves   at the gear end of the actuator. See Figure 14.   Cover Installation   2. Press the cover into place and then press the screws inward and tighten. See   Figure 15.   Figure 14.   Figure 15.   Features of   SQM5x.xxxxxZx   Actuators   SQM5xx.xxxxxZx actuators contain the AGA56.9A… multi function circuit board. This   circuit board provides the following features:   Multiple Input Signals   The AGA56.9A… circuit board accepts the following input signals:   Line voltage   • • • • • • • Power to A drives the actuator open to the setting of switch cam I (Maximum).   Power to ZL drives the actuator closed to the setting of switch cam III (Minimum).   Power to Z drives the actuator closed to the setting of switch cam II (Economy).   4 to 20 mA (Signal to Y3, common to M)   0 to 135 Ω (Slide wire signal to Y0, potentiometer connected to M and U4)   0 to 10 Vdc (Signal to Y1, common to M)   0 to 20 mA (Signal to Y2, common to M)   Multiple Output Signals   The AGA56.9A… circuit board provides the following output signals:   • • • 4 to 20 mA (Signal from U3, common to M)   0 to 10Vdc (Signal from U1, common to M)   0 to 20mA (Signal from U2, common to M)   Double potentiometers ASZ22… provide additional output signals.   Page 16   Siemens Building Technologies, Inc.   SQM5… Reversing Actuators   Technical Instructions   Document No. 155-517P25   July 9, 2007   Electronic Linearization   Function   Butterfly valves have non-linear flow characteristics. Near the fully closed position, a   small change in the valve’s position will produce a very large change in flow. Near the   fully open position, a large position change will produce a relatively small change in flow.   The linearization function is intended to minimize the initial steep flow curve   characteristics of a typical butterfly valve. The linearization function is enabled when   Jumper J1 is in position 1 (upper position). Consequently, the actuator will make smaller   rotational movements when subjected to lower input signals and larger rotational   movements when subjected to higher input signals.   For example (based on a 90° modulating range), a change in input signal from 4 to 8 mA   will cause a rotational movement of 11.25°. An equal change from 16 to 20 mA will cause   a rotational movement of 45°. Thus, with the linearization function enabled, the change in   flow is closely proportional to the change in input signal.   The linearization function is disabled when Jumper J1 is in position 2 (lower position).   When disabled, the rotational movement of the shaft is proportional to the input signal.   Input Signal Override   Parallel Operation   Line voltage to terminal P will drive the actuator to a pre-set adjustable position,   overriding all modulating input signals. Use the potentiometer marked POS to adjust the   override position to any setting within the setting range of switch cams I and III.   NOTE: The input signal override can also be used for the ignition position of burners if   different from the low fire position.   Set Jumper J2 in position 1 (upper position) to configure the actuator for parallel   operation. Input signals Y0, Y1, Y2 or Y3 are directly shunted to output signals U1, U2   and U3. All output signals are available regardless of which input signal is applied.   Master/Slave Operation   Split Ranging   Set J2 in position 2 (lower position) to configure the actuator for master/slave operation.   The output signals U1, U2 and U3 reflect actual shaft position.   AGA56.9… circuit boards have a modulating signal shift feature which can be used for   split ranging. If no signal is present on Y0, Y1, Y2 or Y3, the actuator will modulate   through the full rotational range in response to a 12 to 20 mA signal applied at ZF. If a   maximum signal is present on Y0, Y1, Y2, or Y3, then the actuator will modulate through   the full rotational range in response to a 4 to 12 mA signal applied at ZF. (Maximum   signal can be easily achieved by bridging terminals U4 and Y0.) See Figure 16.   NOTE: It is possible to configure the actuator for split range operation 12 to 4 mA and   20 to 12 mA. Consult your authorized Siemens Building Technologies   combustion products sales representative for details.   20 mA18 mA16 mA14 mA12 mA   MAX   10 mA   8 mA   6 mA   4 mA   75%   50%   25%   MIN   MIN 25% 50% 75% MAX   Y0...3   Figure 16. Split Ranging.   Siemens Building Technologies, Inc.   Page 17   Technical Instructions   Document No. 155-517P25   July 9, 2007   SQM5… Reversing Actuators   Features of   SQM5x.xxxxxGx actuators contain the AGA56.41A… circuit board with terminals Y- and   Y+ for 4 to 20 mA modulating input.   SQM5x.xxxxxGx,   SQM5x.xxxxxHx,   SQM5x.xxxxxKx   Actuators   SQM5x.xxxxxHx actuators contain the AGA56.42A… circuit board with terminals Y, M   and U for 0 to 135 Ω modulating input.   SQM5x.xxxxxKx actuators contain the AGA56.43A… circuit board with terminals Y and M   for 0 to 10 Vdc modulating input.   Input Signals   The AGA56.4xA… circuit boards accept the following additional input signal:   Line voltage   • • • Power to A drives the actuator open to the setting of switch cam I (Maximum).   Power to Z drives the actuator closed to the setting of switch cam II (Economy).   Power to ZL drives the actuator closed to the setting of switch cam III (Minimum).   Output Signals   The AGA56.4xA… circuit boards do not provide output signals. Install a double   potentiometer ASZ22…to obtain a 0 to 1000 Ω actuator position output signal.   Features of   SQM5x.xxxxxAx   Actuators   The AGA56.1A97… circuit boards accept the following additional input signal:   Line voltage   Input Signals   • • • Power to A drives the actuator open to the setting of switch cam I (Maximum).   Power to Z drives the actuator closed to the setting of switch cam II (Economy).   Power to switch III, terminal 3 drives the actuator to the setting of switch cam III   (Minimum).   Output Signals   The AGA56.1A97 circuit board provides no output signals. Install an ASZ… potentiometer   to obtain an actuator position output signal.   Service Guide   WARNING:   Disconnect the power supply to the actuator before performing any service   functions.   Reversing Rotational   Direction   1. Disconnect the wires marked 21 and 12, and reverse.   2. Adjust all switch cams to the desired settings (see Figure 6):   • For CCW rotation use the black cam drum scales and the single switch cam   pointers.   • For CW rotation, use the red cam drum scales and the double switch cam pointers.   NOTE: Press and hold the black cam drum release button to rotate the cam drum.   This will give easy access to the switch cams and a better view of the cam   drum scales.   If no potentiometer ASZ… is installed, the reversing procedure is complete. If a   potentiometer ASZ… is installed, complete Steps 3 through 9.   Page 18   Siemens Building Technologies, Inc.   SQM5… Reversing Actuators   Technical Instructions   Document No. 155-517P25   July 9, 2007   Reversing Rotational Direction,   Continued   POSITION   INDICATION   POINTER   POSITION   INDICATION   POINTER   POSITION   m i n .   m a x .   INDICATION   POINTER   m i n .   m a x .   POSITION   INDICATION   POINTER   m i n .   m a x .   m i n .   m a x .   Clockwise   Counterclockwise   Figure 17. Reversing Rotational Direction on the ASZ Potentiometer.   GEAR WITH MARK "0"   FOR CLOCKWISE   ROTATION   GEAR WITH MARK "1" FOR   COUNTERCLOCKWISE ROTATION   BOARD   ALIGNMENT   SCREW   BOARD   ALIGNMENT   SCREW   TERMINAL   BLOCK   TERMINAL   BLOCK   POTENTIOMETER GEAR   ALIGNMENT POINTER   POTENTIOMETER GEAR   ALIGNMENT POINTER   POTENTIOMETER   POTENTIOMETER   POTENTIOMETER GEAR   ATTACHMENT SCREW   POTENTIOMETER GEAR   ATTACHMENT SCREW   Figure 17a. Reversing Rotational Direction on the ASZ Potentiometer (Gear Models).   3. Disconnect the blue and brown wires from the terminal block located on the ASZ…   potentiometer circuit board and reverse. The black wire remains connected to the   middle terminal. See Figures 17 and 17a.   4. Remove the white plastic actuator position-indicating dial by gently pulling while rotating   in the clockwise direction. See Figure 6.   5. The actuator position indicating pointer, located near the actuator gear end of the cam   drum, must point to the “0” mark on the actuator position scale (scale on the cam drum   nearest to the actuator gear end). Press and hold the black cam drum release button   while manually rotating the cam drum.   6. Loosen the black potentiometer cam attachment screw approximately one turn. Gently   wedge a small screwdriver between the potentiometer and the gray plastic housing.   Gently twist the screwdriver until the potentiometer releases from the cam drum shaft.   7. Change potentiometer end position:   • Manually rotate the potentiometer position indication pointer exactly to the other   end mark (see Figure 17).   • Gear models (see Figure 17a):   For clockwise rotation, manually rotate the potentiometer gear until the white line   next to the “0” mark on the potentiometer gear face is exactly in alignment with the   potentiometer gear alignment pointer.   For counterclockwise rotation, manually rotate the potentiometer gear until the   white line next to the “1” mark on the potentiometer gear face is exactly in   alignment with the potentiometer gear alignment pointer   Page 19   Siemens Building Technologies, Inc.   Technical Instructions   Document No. 155-517P25   July 9, 2007   SQM5… Reversing Actuators   Reversing Rotational   Direction, Continued   8. Firmly tighten the black potentiometer cam attachment screw while manually   holding the potentiometer position indication pointer in alignment. Check the   alignment again.   9. Re-install the white actuator-indicating dial by gently pressing it onto the   potentiometer cam attachment screw. Align scale position “0” on the actuator   position indicating dial with the dial pointer by rotating the dial in the clockwise   direction to avoid loosening the potentiometer cam attachment screw.   Shaft Installation   See Installation and Operation Instructions.   Preparation Before   Circuit Board Installation   WARNING:   Disconnect the power supply to the actuator before replacing the circuit   boards.   The black circuit board mounting   bracket, installed on the inside base of   the SQM5… actuator has four vertical,   slotted circuit board supports. Remove   the terminal section and circuit board(s)   from the mounting bracket.   The actuator motor capacitor is   attached to the lower section of the gray   plastic switch housing using snap-on   holding clips. Gently pull the capacitor   forward until it unclips and temporarily   place it on top of the gear housing. See   CAPACITOR   Figure 18.   Figure 18.   CAUTION:   Do not disconnect any capacitor wiring.   AGA56.41/42/43   Circuit Board   Installation   1. Remove the AGA56.41/42/43…   TERMINAL   SECTION   circuit board from the packaging. The   circuit board is shipped as one board.   2. Separate the board at the perforation   by holding the circuit board at both   ends and gently bending the board   until it separates.   3. Move the terminal section containing   the auto/manual switch to the   opposite end of the base circuit   board.   BASE   CIRCUIT   BOARD   4. From the switch housing side of the   actuator, guide the base circuit board   into the bottom of the circuit board   mounting bracket. See Figure 19.   Figure 19.   Page 20   Siemens Building Technologies, Inc.   SQM5… Reversing Actuators   Technical Instructions   Document No. 155-517P25   July 9, 2007   AGA56.41/42/43   Circuit Board   Installation,   Continued   5. Re-install the actuator motor capacitor.   See Figure 20.   6. Gently guide the terminal section into   the support slots and slide the terminal   board downward until both supports   snap into place. Ensure that the four   brown wires and the flat white   connector cable which connect the two   circuit boards are positioned correctly   in their respective corners allowing the   board to freely slide into place without   pinching either wire. See Figure 21.   CAPACITOR   Figure 20.   7. Connect the bundled blue, black and   brown potentiometer wires to the   terminal block located on the ASZ…   potentiometer circuit board. See   Potentiometer Installation.   TERMINAL   SECTION   Figure 21.   Siemens Building Technologies, Inc.   Page 21   Technical Instructions   Document No. 155-517P25   July 9, 2007   SQM5… Reversing Actuators   AGA56.41/42/43   Circuit Board   Installation, Continued   8. Make the following connections to the   actuator: See Figure 22.   18 17 16 15 14 13 12 11   28 27 26 25 24 23 22 21   a. Connect the wire, marked “1” from   the circuit board to switch I,   terminal 1.   8 7 6 5 4 3 2 1 VIII VII VI   V IV   III   II   I b. Connect the wire, marked “2” from   the circuit board to switch II,   terminal 2.   13   c. Connect the wire, marked “3” from   the circuit board to switch III,   terminal 3.   d. Connect the wire, marked “13”   from the circuit board to switch III,   terminal 13.   3 2 N 1 TERMINAL   BLOCK   e. Connect the blue neutral wire   marked “N” to the double terminal   block located on the outer end of   the switch housing   MAN.   0 AUTO   f. Connect the grounding wire   marked "51" to the ground terminal   located to the right of the   auto/manual switch.   N Figure 22.   AGA56.9A…   Circuit Board   Installation   1. Remove the ASZ... potentiometer if   already installed on the SQM5...   actuator. See Potentiometer   Removal/Installation Instructions.   2. Remove the AGA56.9A… circuit   boards from the packaging. The three   separate AGA56.9A circuit boards are   shipped in a circuit board mounting   bracket.   3. Remove the two upright circuit boards   from the mounting bracket by gently   pulling aside the vertical supports and   sliding the boards upward. Remove   the base circuit board from the bottom   of the mounting bracket. Discard the   shipping mounting bracket.   Page 22   Siemens Building Technologies, Inc.   SQM5… Reversing Actuators   Technical Instructions   Document No. 155-517P25   July 9, 2007   AGA56.9A…   Circuit Board   Installation, Continued   4. Guide the base circuit board from the   switch housing side of the actuator into   the bottom of the circuit board mounting   bracket. See Figure 23.   5. Re-install the actuator motor capacitor.   See Figure 24.   6. Gently guide the terminal board into the   support slots and slide the terminal   board downward until both supports   snap into place. See Figure 25.   BASE   CIRCUIT   BOARD   7. See Figure 26 and make the following   connections to the actuator:   Figure 23.   a. Connect the wire, marked “1” from   the circuit board to switch I,   terminal 1.   b. Connect the wire, marked “2” from   the circuit board to switch II,   terminal 2. Connect the white wire,   marked “3” from the circuit board to   switch III, terminal 3.   c. Connect the wire, marked “13” from   the circuit board to switch III,   terminal 13.   CAPACITOR   d. Connect the neutral wire, marked   “N” to the double terminal block   located on the outer end of the   switch housing.   Figure 24.   TERMINAL   SECTION   e. Connect the grounding wire marked   "51" to the ground terminal located   to the right of the auto/manual   switch.   Figure 25.   Siemens Building Technologies, Inc.   Page 23   Technical Instructions   Document No. 155-517P25   July 9, 2007   SQM5… Reversing Actuators   AGA56.9A…   Circuit Board   Installation, Continued   8. Gently guide the L-shaped circuit   board containing the three blue trim   potentiometers into the vertical support   slots located on the cam drum side of   the actuator. See Figure 27.   18 17 16 15 14 13 12 11   28 27 26 25 24 23 22 21   8 7 6 5 4 3 2 1 VIII VII VI   V IV   III   II   I 13   9. Slide the circuit board downward until   both supports snap into place. Install   the ASZ… potentiometer. (See   Potentiometer Removal/Installation   Instructions.)   3 2 N 1 10. Connect the bundled blue, black and   brown potentiometer wires to the   terminal block located on the ASZ…   potentiometer circuit board.   MAN.   0 AUTO   N Figure 26.   - L SHAPED   CIRCUIT   BOARD   Figure 27.   AGA56.1A97   Circuit Board   Installation   1. Install the AGA56.1A97 circuit board into the two slotted circuit board supports   located on the switch housing side of the actuator.   2. Gently guide the AGA56.1A97 circuit board into the support slots and slide the board   downward until both supports snap into place.   3. Make the following connections to the actuator:   a. Connect the wire, marked “1” from the circuit board to switch I, terminal 1.   b. Connect the wire, marked “2” from the circuit board to switch II, terminal 2.   c. Connect the wire, marked “13” from the circuit board to switch III, terminal 13.   Page 24   Siemens Building Technologies, Inc.   SQM5… Reversing Actuators   Technical Instructions   Document No. 155-517P25   July 9, 2007   Potentiometer   Removal   9. Remove the white plastic actuator position-indicating dial by gently pulling while   rotating in the clockwise direction. See Figure 6.   10. Disconnect the blue, black and brown wire from the potentiometer terminal block. See   Figure 17.   11. Remove the silver potentiometer alignment screw.   12. Loosen the black potentiometer cam attachment screw approximately one turn.   13. Gently wedge a small screwdriver between the potentiometer and the gray plastic   housing.   14. Carefully twist the screwdriver until the potentiometer releases from the cam drum   shaft. Remove the ASZ… potentiometer.   Potentiometer   Installation   1. Install the new ASZ… potentiometer by gently sliding the bushing over the cam drum   shaft.   2. Align the potentiometer alignment screw hole with the hole in the gray plastic housing   and install the potentiometer alignment screw. See Figures 17 and 17a.   3. The actuator position indicating pointer, located near the actuator gear end of the cam   drum, must point to the “0” mark on the actuator position scale. See Figure 6. The   scale is located on the cam drum nearest to the actuator gear end. Press and hold   the black cam drum release button while manually rotating the cam drum.   4. If installing a potentiometer without gear, manually rotate the potentiometer pointer   until the pointer is exactly in the “min” position. See Figure 17. Firmly tighten the   black potentiometer cam attachment screw while manually holding the potentiometer   pointer in alignment. Check the alignment again.   5. If installing a gear model potentiometer, manually rotate the potentiometer gear until   the white line next to the “0” or “1” mark on the potentiometer gear face is exactly in   alignment with the potentiometer gear alignment pointer. See Figure 17a.   For counterclockwise (ccw) operation the line beside the “1” mark must exactly align   with potentiometer gear alignment pointer. For clockwise (cw) operation the line   beside the “0” mark must exactly align with potentiometer gear alignment pointer.   Firmly tighten the black potentiometer cam attachment screw while manually holding   the potentiometer gear in alignment. Check the alignment again.   6. Connect the bundled blue, black and brown potentiometer wires to the terminal block   located on the ASZ… potentiometer board. See Potentiometer Installation and   Figures 17 and 17a.   7. Re-install the white actuator-indicating dial by gently pressing it onto the   potentiometer cam attachment screw. Align scale position “0” on the actuator position   indicating dial with the dial pointer by rotating the dial in the clockwise direction to   avoid loosening the potentiometer gear attachment screw. See Figure 6.   Siemens Building Technologies, Inc.   Page 25   Technical Instructions   Document No. 155-517P25   July 9, 2007   SQM5… Reversing Actuators   Specifications   SQM5... Reversing actuator   Agency approvals   UL, CSA, CE   SQM5... Reversing   Actuator   Operating voltage   24 Vac +10%-15%   110 Vac-15% to 120 Vac +10%   220 Vac-15% to 240 Vac +10%   Operating frequency   Power consumption   Type of motor   50 to 60 Hz   20 VA   Reversing synchronous motor   100%   Duty cycle   Torque   See Table 1.   Maximum shaft torque   AGA58.1   90 lb-in   AGA58.2   200 lb-in   220 lb-in   270 lb-in   400 lb-in   See Table 1.   AGA58.3   AGA58.4   AGA58.7   Timings   Rotational range of operation   SQM5x.xxxxxA models   SQM5x.xxxxxx3 models   SQM5x.xxxxxx4 models   SQMSx.xxxxxx6 models   Direction of rotation   Shaft   0° to 160°   0° to 90°   0° to 135°   0° to 160°   Reversible   Selectable. See Table 2.   Custom versions on request   Shaft disengagement   Number of auxiliary switches   Limit switches   Independent, cam and drive shaft   4 switches (standard, maximum 6)   2 switches (standard)   Electrical rating of auxiliary switches   Mounting position   7.5 (3) A, 250 Vac   Optional   Ambient operating temperature   Shipping temperature   NEMA ratings   -5°F to 140°F (-20°C to 60°C)   -58°F to 140°F (-50°C to 60°C)   NEMA 1, 2, 3, 3R, 3S, 5, 12, and 13   Connections   Switches   Boards   Spade connectors   Screwed and spade connectors   Dimensions   Weight   See Figures 28 through 31.   7.3 lb (3.3 kg)   Housing   Aluminum pressure die casting   Lexan   Enclosure (cover)   Motor   Lock resistant   Disengagements   Manual for drive and cam shaft   Page 26   Siemens Building Technologies, Inc.   SQM5… Reversing Actuators   Technical Instructions   Document No. 155-517P25   July 9, 2007   Conduit connection   Two removable inserts with two   1/2-inch NPSM threads.   Specifications   Each insert allows insertion of entire   cable tree for easy servicing   SQM5... Reversing   Actuator, Continued   Gears and bearings   Mounting   Maintenance-free   Four 1/4"-20 UNC screws in bottom   Face mounting at gear side also   possible   Adaptation to other actuator brands   Screw pattern and shaft height   Adaptation with AGA57... adapters   See Table 2.   AGA56.1A97 Switch circuit board   Operating voltage   Voltage independent   50 to 60 Hz   Circuit Boards   AGA56.1A97   Operating frequency   Auto/manual switch   2-position switch   Manual toggle switch   3-position switch   Ambient operating temperature   Shipping temperature   -5°F to 140°F (-20°C to 60°C)   -58°F to 140°F (-50°C to 60°C)   0.22 lb (0.1 kg)   Weight   AGA56.41A… Electronic circuit boards   Single potentiometer   ASZ... (1000 ohm) is required   Operating voltage   24 Vac +10%-15%   110 Vac -15% to 120 Vac +10%   220 Vac -15% to 240 Vac +10%   50 to 60 Hz   AGA56.41A…   Operating frequency   Ambient operating temperature   Shipping temperature   Input signal   -5°F to 140°F (-20°C to 60°C)   -58°F to 140°F (-50°C to 60°C)   4 to 20 mA   Impedance   Current input   ≤300 Ω   Zero adjustment   MIN: 0 to 75%   MAX: min 100%   2-position switch   3-position switch   0.7 lb (0.33 kg)   Span adjustment   Auto/manual switch   Manual toggle switch   Weight   AGA56.42A… Electronic circuit boards   Same specifications as AGA56.41A   except   Input signal   Impedance   Current input   Voltage input   0 to 135 ohm   AGA56.42A…   ≤300 Ω   ≥100K Ω   Siemens Building Technologies, Inc.   Page 27   Technical Instructions   Document No. 155-517P25   July 9, 2007   SQM5… Reversing Actuators   Specifications,   continued   AGA56.43A…   AGA56.43A… Electronic circuit boards   Same specifications as AGA56.41A   except:   Input signal   Impedance   Voltage input   0 to 10 Vdc   ≥100K Ω   AGA56.9A… Multi function electronic   circuit boards   Operating voltage   Single potentiometer   ASZ... (1000 ohm) is required   24 Vac +10%-15%   AGA56.9A   110 Vac -15% to 120 Vac +10%   220 Vac -15% to 240 Vac +10%   Operating frequency   Input signals   50 to 60 Hz   4 to 20 mA   0 to 20 mA   0 to 10 Vdc   0 to 135 ohm   Impedance   Current input   Voltage input   Output signals   ≤300 Ω   ≥100K Ω   4 to 20 mA   0 to 20 mA   0 to 10 Vdc   Max output load   Current output   <600 ohm   Voltage output   > 1.5K ohm   Zero adjustment   MIN: 0 to 75%   MAX: min-100%   4 to 20 mA on terminal ZF   Span adjustment   Split ranging (SHIFT)   Input signal override (POS)   Line voltage (... Vac) on terminal P   adjust with POS potentiometer   Ambient operating temperature   Shipping temperature   Auto/manual switch   Manual toggle switch   Weight   -5°F to 140°F (-20°C to 60°C)   -58°F to 140°F (-50°C to 60°C)   2-position switch   ASZ... Potentiometers   3-position switch   0.7 lb (0.33 kg)   ASZ... Potentiometers   Versions   Single and double potentiometer   See Table 2 and Data Sheet 7921.   < 0.3% related to drive shaft   Resistor values   Hysteresis   Page 28   Siemens Building Technologies, Inc.   SQM5… Reversing Actuators   Technical Instructions   Document No. 155-517P25   July 9, 2007   Dimensions   The first dimension given is measured in inches. Millimeters are shown in parentheses.   5/8   (16)   1-3/16   (30)   Pg 13.5 / 1/2"   NPSM   ALLOW 3.5" SPACE FOR   COVER REMOVAL   1/4   (6)   M 8   1-3/16   (30)   1-7/16   (36)   5-1/4   (133)   3/8   (10)   2-5/8   (67)   7-1/16   (180)   7-1/16   (180)   1/8   (3.5)   1/16   (1)   1/4"-20   UNC   4-7/16   (113)   3-1/8   (80)   5-3/16   (132)   6-7/16   (164)   5/16   (8.5)   5/16   (7.5)   Figure 28. SQM5x.xxxRxx Dimensions.   Siemens Building Technologies, Inc.   Page 29   Technical Instructions   Document No. 155-517P25   July 9, 2007   SQM5… Reversing Actuators   Dimensions, Continued   6-7/16   (164)   11/16   (18)   9/16   (14.5)   4-1/16   (103.3)   4-7/8   (123.8)   AGA57.3   4-7/16   (113)   3-1/8   (80)   C L 4 X 1/4   (7)   4 X 1/4   (7)   1/8   (3)   Figure 29. Mounting Bracket AGA57.3.   7-5/16   (185)   1-9/16   (40)   2-1/4   (57.15)   7/16   (11)   6-7/16   (164)   5/16   (7.94)   5/16   (7.94)   5-5/16   (135)   4-7/16   (113)   4-3/4   (120.65)   4-7/16   (113)   AGA57.4   4 5/16   (8.73)   (101.5)   3-1/8   (80)   1-3/8   (35)   C L 3-1/8   (80)   2-3/8   (60.4)   5/16   (8.73)   2-1/2   (63.5)   5/16   (7.94)   2-3/8   (60.64)   1-5/8   (42)   2 1-11/16   (43)   (50.8)   1-1/2   (38.1)   45   45   1/2   (12.5)   13/16   (20.3)   13/16   (20.3)   1/8   (3)   All non-sized holes   O 5/16 (7.62)   Figure 30. AGA57.4 Mounting Bracket.   Page 30   Siemens Building Technologies, Inc.   SQM5… Reversing Actuators   Technical Instructions   Document No. 155-517P25   July 9, 2007   Dimensions, Continued   7.09   GEAR SIDE   (180)   1 (25.5)   0.39   (10)   0.31   (8)   0.79   (20)   0.35   (9)   0.12   (3)   AGA58.1   AGA58.2   AGA58.3   0.44   (11.2)   1 (25.5)   0.79   (20)   0.47   (12)   0.35   (9)   0.12   (3)   0.52   (13.2)   0.81   (20.5)   0.85   (21.5)   0.35   (9)   0.35   (9)   0.35   (9)   0.43   (11)   M5 x 9   M5 x 9   0.67   (17)   0.78   (19.8)   0.42   (10.6)   0.42   (10.6)   0.375   (9.5)   0.375   (9.5)   0.27   (6.9)   0.27   (6.9)   AGA58.4   8-32 UNC   28 x 0.56   (14.2)   8-32 UNC   28 x 0.56   (14.2)   0.05   (1.3)   0.05   (1.3)   0.55   (14)   1.71   (43.5)   1.10   (28)   0.20   (5)   0.20   (5)   AGA58.7   0.60   (15.1)   Figure 31. Shaft Dimensions.   Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as   design improvements are introduced. Other product or company names mentioned herein may be the trademarks of their respective owners.   © 2007 Siemens Building Technologies, Inc.   Your feedback is important to us. If you have   comments about this document, please send them   Document No.155-517P25   Country of Origin: US   Siemens Building Technologies, Inc.   1000 Deerfield Parkway   Buffalo Grove, IL 60089-4513   U.S.A.   Page 31   |