| INSTALLATION INSTRUCTIONS   – Split System Air Conditioner –   COOL/DRY Model   Contents   Model Combinations   Page   Combine indoor and outdoor units only as listed   below.   IMPORTANT!   Please Read Before Starting .................................. 2   Indoor Units   Outdoor Units   C0951   1. GENERAL .......................................................... 3   1-1. Tools Required for Installation (not supplied)   1-2. Accessories Supplied with Unit   KS0951   CL0951   1-3. Optional Copper Tubing Kit   KS1251   C1251   1-4. Type of Copper Tube and Insulation Material   1-5. Field Wiring   CL1251   Power Source:   1-6. Additional Materials Required for Installation   60 Hz, single-phase, 115 V   2. INSTALLATION SITE SELECTION ................... 4   2-1. Indoor Unit   KS1852   C1852   2-2. Outdoor Unit   CL1852   2-3. Baffle Plate for the Outdoor Unit   Power Source:   60 Hz, single-phase, 230/208 V   3. HOW TO INSTALL THE INDOOR UNIT ............ 6   3-1. Remove the Rear Panel from the Unit   3-2. Make a Hole   3-3. Install the Rear Panel on the Wall   3-4. Remove the Grille to Install the Indoor Unit   3-5. Shape the Indoor Side Tubing   3-6. Wiring Instructions   5-7. Finishing the Installation   3-7. Recommended Wire Length and Diameter   3-8. Wiring Instructions for Inter-unit Connections   3-9. Mounting   6. AIR PURGING................................................... 18   I Air Purging with a Vacuum Pump (for Test Run)   I Basic Function of the Service Valves   I Pump Down   3-10. Drain Hose   4. HOW TO INSTALL THE OUTDOOR UNIT ....... 15   7. REMOTE CONTROL UNIT INSTALLATION   POSITION ......................................................... 22   7-1. Mounting on a Wall   4-1. Wiring Instructions for the Outdoor Unit   5. REFRIGERANT TUBING.................................. 16   5-1. Use of the Flaring Method   5-2. Flaring Procedure with a Flare Tool   5-3. Caution before Connecting Tubes Tightly   5-4. Connecting Tubing between Indoor and   Outdoor Units   5-5. Insulation of Refrigerant Tubing   5-6. Taping the Tubes   IMPORTANT   Power source for C0951, CL0951, C1251 and   CL1251 is 60 Hz, single-phase 115V.   In Canada   SANYO FISHER COMPANY   SANYO Canada Inc.   A DIVISION OF SANYO NORTH AMERICA CORPORATION 300 Applewood Crescent, Concord   21605 Plummer Street   Ontario, L4K 5C7, Canada   85264189593004 © SANYO 2002 Chatsworth, CA 91311 U.S.A.   W 1. General   This booklet briefly outlines where and how to install the   air conditioning system. Please read over the entire set   of instructions for the indoor and outdoor units and   make sure all accessory parts listed are with the system   before beginning.   5. Carpenter’s level   6. Sabre saw or key hole saw   7. Hacksaw   8. Core bits   9. Hammer   10. Drill   1-1. Tools Required for Installation (not supplied)   1. Standard screwdriver   11. Tube cutter   12. Tube flaring tool   13. Torque wrench   14. Adjustable wrench   15. Reamer (for deburring)   2. Phillips head screwdriver   3. Knife or wire stripper   4. Tape measure   1-2. Accessories Supplied with Unit   Table 1   Parts   Figure   Q’ty   Parts   Figure   Truss-head   Phillips   5/32 × 5/8" (4 × 16 mm)   Q’ty   Parts   Remote   Figure   Q’ty   Tapping   screw   Rawl plug   12   12   1 control unit   Remote   control   holder   AAA alkaline   battery   Drain hose   adapter   1 2 1 1 Hex   wrench*   * Packed in the outdoor unit.   1-3. Optional Copper Tubing Kit   2. Foamed polyethylene insulation for the specified   O.D. copper tubes as required to precise length of   tubing. Wall thickness of the insulation should be   not less than 0.3 in. (8 mm).   Copper tubing for connecting the outdoor unit to the   indoor unit is available in kits which contain the narrow   and wide tubing, fittings and insulation. Consult your   nearest sales outlet or A/C workshop.   1-5. Field Wiring   1-4. Type of Copper Tube and Insulation Material   Use insulated copper wire for field wiring. Wire size   varies with the total length of wiring. Refer to 3-6. Wiring   Instructions for details.   If you wish to purchase these materials separately from   a local source, you will need:   1. Deoxidized annealed copper tube for refrigerant   tubing as detailed in Table 2.   Check local electrical codes   and regulations before   obtaining wire. Also, check   any specified instructions or   limitations.   CAUTION   When cutting tubing, add approximately 12” to 16”   (30 cm to 40 cm) to each tube length to reduce   vibration between the air conditioning units.   Table 2   Narrow Tube   Wide Tube   Model   Outer Dia.   Thickness   Outer Dia.   Thickness   6.35 mm (1/4")   6.35 mm (1/4")   6.35 mm (1/4")   0.8 mm (0.0314")   0.8 mm (0.0314")   0.8 mm (0.0314")   9.52 mm (3/8")   12.7 mm (1/2")   0.8 mm (0.0314")   0.8 mm (0.0314")   C0951, CL0951   C1251, CL1251   C1852, CL1852   15.88 mm (5/8") 1.0 mm (0.0394")   3 1-6. Additional Materials Required for Installation   Indoor unit   1. Refrigeration (armored) tape   2. Insulated staples or clamps for connecting wire   (See local codes)   3. Putty   4. Refrigeration lubricant   5. Clamps or saddles to secure refrigerant tubing   Drain hose   2. Installation Site Selection   Outside drainage   2-1. Indoor Unit   Fig. 1   To prevent abnormal heat genera-   WARNING   tion and the possibility of fire, do   2" (5 cm) min.   *6" (15 cm) min.   not place obstacles, enclosures   and grilles in front of or surround-   ing the air conditioner in a way that   may block air flow.   2" (5 cm) min.   *6" (15 cm) min.   2" (5 cm) min.   *6" (15 cm) min.   Front View   *KS1852 only   AVOID:   Fig. 2   I direct sunlight.   Tubing length (L)   I nearby heat sources that may affect performance of the   INDOOR   UNIT   unit.   I areas where leakage of flammable gas may be expected.   Elevation   difference (H)   I places where large amount of oil mist exist.   OUTDOOR   UNIT   DO:   I select an appropriate position from which every corner of   Fig. 3a   the room can be uniformly cooled. (High on a wall is best.)   I select a location that will hold the weight of the unit.   CAUTION   Indoor unit   Wall   I select a location where tubing and drain hose have the   shortest run to the outside. (Fig. 1)   For stable operation of   the air conditioner, do   not install wall-mounted   type indoor units under   5 ft. (1.5 m) from floor   level.   I allow room for operation and maintenance as well as unre-   Minimum height   from floor level   5 ft. (1.5 m)   stricted air flow around the unit. (Fig. 2)   I install the unit within the maximum elevation difference (H)   above the outdoor unit and within a total tubing length (L)   from the outdoor unit as detailed in Table 3 and Fig. 3a.   Floor level   Fig. 3b   Table 3   Max. Allowable Tubing   Length at Shipment   (ft.)   Limit of Tubing   Length (L)   (ft.)   Limit of Elevation   Difference (H)   (ft.)   Required Amount of   Additional Refrigerant   (oz./ft.)*   Model   25   25   50   65   23   23   a) 0.16   b) 0.27   9,000 BTU   12,000/18,000 BTU   * If total tubing length becomes a) 25 to 50 ft. (max.), b) 25 to 65 ft. (max.) charge additional refrigerant (R22) by a) 0.16 oz./ft., b) 0.27 oz./ft.   No additional compressor oil is necessary.   4 2-2. Outdoor Unit   Exhaust fan   NO   AVOID:   Hot air   I heat sources, exhaust fans, etc. (Fig. 4)   I damp, humid or uneven locations.   DO:   Heat source   Outdoor unit   I choose a place as cool as possible.   I choose a place that is well ventilated.   I allow enough room around the unit for air intake/   Fig. 4   exhaust and possible maintenance. (Fig. 5a)   Obstacle above   CAUTION   Min.   Min.   7 ft.   (2 m)   7 ft.   Air intake   Min. 6" (15 cm)   Valve side   Min. 10"   (25 cm)   (2 m)   I Install the outdoor unit above snowfall line.   I Do not place objects on or sit on the out-   door unit. Also, never block the air   intake/outlet or exhaust. Distortion of the   outdoor unit or incomplete combustion   may result.   Min. 6"   (15 cm)   Air discharge   Min. 12"   (30 cm)   Ground   Min. 6 in.   (15 cm)   Air intake   I Do not introduce foreign matter into the air   intake/outlet or exhaust. Do not poke them   with such objects as a stick.   Fig. 5a   Anchor bolts   (4 pcs)   I provide a solid base (level concrete pad, concrete   block, 4 in. × 16 in. (10 × 40 cm) beams or equal), a   minimum of 4 in. (10 cm) above ground level to   reduce humidity and protect the unit against possible   water damage and decreased service life (Fig. 5b).   Min. 4"   (10 cm)   Air intake   Concrete   I use lug bolts or equal to bolt down unit, reducing   or equal   vibration and noise.   2-3. Baffle Plate for the Outdoor Unit   (CL×× models only)   NOTE   Fig. 5b   It is recommended to use baffle plates for models   CL1251, CL1852 and CL0951. The baffle plates are not   normally required for the other models.   6" min   Baffle   plate   Baffle   plate   When the outdoor unit is installed in a position exposed   to strong wind (like seasonal winds with low air temper-   ature in winter), baffle plates must be installed in front   of the outdoor unit. (Fig. 5c)   This unit is designed so that the fan of the outdoor unit   runs at low speed when the air conditioner is operated   at low outdoor air temperatures. When the outdoor unit   is exposed to strong wind, the system pressure drops   because of the freeze protector.   Air discharge   Fig. 5c   5 3. How to Install the Indoor Unit   3-1. Remove the Rear Panel from the Unit   (1) Remove and discard the set screw on the rear panel. (Fig. 6)   (2) Press the 2 I marks on the frame cover and disengage the sta-   tionary tabs from the frame. (Fig. 7)   (3) Remove the rear panel.   Set screw only for transportation   NOTE   Fig. 6   Tubing can be extended in 5 directions (KS0951, KS1251 and   KS1852) as shown in Fig. 8a or 8b. Select the direction you need   providing the shortest run to the outside unit.   Rear panel   3-2. Make a Hole   (1) Place the rear panel from the indoor unit on the wall at the loca-   tion selected. Make sure the panel is horizontal, using a carpen-   ter’s level or tape measure to measure down from the ceiling.   Wait until after cutting the hole before attaching the rear panel to   the wall.   Fig. 7   I marks   (2) Determine which side of the unit you should make the hole for   tubing and wiring. (Fig. 9)   KS0951, KS1251   Right-rear   tubing   (recommended)   (3) Before making the hole, check carefully that no studs or pipes   are directly run behind the spot to be cut.   Left   tubing   CAUTION   Left-rear   tubing   Right tubing   Fig. 8a   I Also avoid areas where electrical wiring or conduits are   Downward tubing   located.   KS1852   I Switching drain hose and drain cap   Left   tubing   (a) Locate the drain hose and the drain cap. (Fig. 8c)   Right-rear   tubing   (recommended)   (b) Remove the drain hose on the right side by pushing and   turning the hose connector counter-clockwise to release it.   (Fig. 8c)   (c) Apply moderate force to pull off the drain cap on the left   side. (If you cannot pull it off by hand, use a long-nose pli-   ers.)   Right tubing   Fig. 8b   Downward tubing   (d) Reattach the drain hose to the left side and the drain cap   to the right side. (Fig. 8c)   The above precautions are also applicable if tubing goes through the   wall in any other location.   Drain hose   In case of right-rear   Clamp   To slip on   Drain cap   60°   To remove   Fig. 9   Fig. 8c   6 (4) Using a sabre saw, key hole saw or hole-cutting drill   attachment, cut a hole in the wall. See Table 4 and   Fig. 10.   NOTE   Hole should be made at a slight downward slant to the   outdoor side.   Table 4   Indoor   side   Outdoor   side   Hole Dia.   2-9/16" (65 mm) / 3-5/32" (80 mm)   (5) Measure the thickness of the wall from the inside   edge to the outside edge and cut PVC pipe at a   slight angle 0.25 in. (6 mm) shorter than the thick-   ness of the wall. (Fig. 11)   Fig. 10   PVC pipe (locally purchased)   (6) Place the plastic cover (locally purchased) over the   end of the pipe (for indoor side only) and insert the   pipe in the wall. (Fig. 12)   3-3. Install the Rear Panel on the Wall   Cut at slight angle   Be sure to confirm that the wall is strong enough to sus-   pend the unit.   Fig. 11   INSIDE   OUTSIDE   See either Item a) or b) below depending on the wall type.   Wall   Plastic   cover   a) If Wooden Wall   PVC pipe   Slight   angle   (1) Attach the rear panel to the wall with the 10 screws   provided. (Fig. 13)   If you are not able to line up the holes in the rear   panel with the beam locations marked on the wall,   use rawl plugs or toggle bolts to go through the   holes on the panel or drill 3/16 in. (5 mm) dia. holes   in the panel over the stud locations and then mount   the rear panel.   Fig. 12   (2) Double check with a ruler or carpenter’s level that   the panel is level. This is important to install the unit   properly. (Fig. 14)   Fig. 13   Fig. 14   (3) Make sure the panel is flush against the wall. Any   space between the wall and unit will cause noise   and vibration.   b) If Block, Brick, Concrete or Similar Type Wall   Make 3/16 in. (4.8 mm) dia. holes in the wall. Insert   rawl plugs for appropriate mounting screws. (Fig. 15)   3/16" (4.8 mm)   dia. hole   Rawl plug   Fig. 15   7 3-4. Remove the Grille to Install the Indoor Unit   KS0951, KS1251   Basically, these models can be installed and wired with-   out removing the grille. If access to any internal part is   needed, follow the steps as given below:   How to remove the grille   (1) Set the flap in the horizontal position.   (2) Unscrew the screws. (Fig. 16a or 16b)   (3) Remove the grille. (Fig. 17)   Screw cover   Flap   (Up and down air direction louvre)   Fig. 16a   (a) Hold both corners of the air intake grille, then   pull out and up to open.   KS1852   (b) Pull the lower part of the grille toward you to   remove.   (c) Use a standard screwdriver to push up the 3   tabs to remove the grille.   How to replace the grille   (1) Close the flaps.   Fig. 16b   (2) Reinstall the grille into the lower part while aligning   its tabs on the upper part. (Fig. 18) Insert the tabs in   the slots and push the lower part of the grille back   into position.   Air intake grille   (3) Press at each of the 4 tabs to completely close the   grille. Make sure that the grille and frame are firmly   fitted together. (Fig. 19)   Fig. 17   Fig. 18   Fig. 19   8 3-5. Shape the Indoor Side Tubing   1) Arrangement of tubing by directions   a) Right or left tubing   Frame   Cut out the corner of the right/left frame with a   hacksaw or the like. (Figs. 20 and 21)   Left tubing   outlet   b) Right-rear or left-rear tubing   In this case, the corner of the frame need not be   cut.   2) To mount the indoor unit on the rear panel:   Fig. 20   Hang the 2 mounting slots of the unit on the   upper tabs of the rear panel. (Fig. 22)   Frame   3-6. Wiring Instructions   General precautions on wiring   Right tubing   outlet   1) Before wiring, confirm the rated voltage of the unit   as shown on its nameplate, then carry out the   wiring closely following the wiring diagram.   2) Provide a power outlet to be used exclusively for   each unit, with a power supply disconnect and cir-   cuit breaker for overcurrent protection provided in   the exclusive line.   Fig. 21   3) To prevent possible hazard due to insulation failure,   the unit must be grounded.   4) Each wiring connection must be done tightly and in   accordance with the wiring system diagram. Wrong   wiring may cause the unit to misoperate or become   damaged.   Fig. 22   5) Do not allow wiring to touch the refrigerant tubing,   compressor, or any moving parts of the fan.   6) Unauthorized changes in the internal wiring can be   very dangerous. The manufacturer will accept no   responsibility for any damage or misoperation that   occurs as a result of such unauthorized changes.   9 3-7. Recommended Wire Length and Diameter   Regulations on wiring diameter differ from locality to   locality. For field wiring requirements, please refer to   your local electrical codes. Carefully observe these reg-   ulations when carrying out the installation.   WIRING SYSTEM DIAGRAM   C0951, CL0951, C1251, CL1251 Models   INDOOR   NOTE   OUTDOOR UNIT   Terminal   INDOOR UNIT   Terminal   (Inter-unit)   Power lines   Refer to the wiring system diagram (Fig. 23)   115V   115V   115V   Refer to your local codes or in the absence of local   codes with the National Electric Code: ANSI/NFPA70.   1 2 3 1 Fuse   2 3 4 Disconnect   switch   (Field supply)   L N 5 6 WARNING   G G Grounding   line   I Be sure to comply with local codes on running   the wire from the outdoor unit to the indoor unit   (size of wire and wiring method, etc.).   C1852, CL1852 Models   I Each wire must be firmly connected.   INDOOR   I No wire should be allowed to touch refrigerant   tubing, the compressor, or any moving part.   OUTDOOR UNIT   INDOOR UNIT   Terminal   (Inter-unit)   Power lines   Terminal   1 230/208 V   230/208 V   230/208 V   1 2 3 Fuse   2 3 4 5 6 WARNING   Disconnect   switch   (Field supply)   L1   L2   I To avoid the risk of electric shock, each air   conditioner unit must be grounded.   G G Grounding   line   CAUTION   Fig. 23   I Be sure to connect the power supply line to the   outdoor unit as shown in the wiring diagram. The   indoor unit draws its power from the outdoor   unit.   3-8. Wiring Instructions for Inter-unit Connections   a) Remove the grille. (See 3-4. Remove the Grille to   Install the Indoor Unit on page 8.)   Rear   panel   Wall   Plastic   cover   b) Insert the inter-unit wiring (according to local codes)   into the through-the-wall PVC pipe. Run the wiring   toward the indoor side allowing approx. 10 in. (25   cm) to extend from the wall face. (Fig. 24)   Wiring   Never fix the wiring by any   10 in.   (25 cm)   CAUTION   means before the indoor unit   is fully seated on the rear   panel.   Fig. 24   10   c) Remove the screws to open the cover plate secur-   ing the electrical component box. (Figs. 25a, 25b,   25c and 25d)   KS0951, KS1251   KS0951, KS1251   Cover   plate   Electrical   component box   Cover   plate   d) Insert the wrapped tubing into the hole in the wall.   e) Hang the indoor unit on the rear panel.   f) Using a Phillips screwdriver, take out the screws on   the earth plate. (Fig. 26a KS0951, 1251 models   only) Remove the earth plate.   Terminal   plate   Earth plate   Electrical   component box   g) Remove the lock nut from the conduit connector.   Insert the conduit connector through the opening   from the underside of the electrical component box.   After insertion, Fit the screw at the top of the con-   duit connector into the cut-out. (Fig. 26b). Position   the earth plate over the conduit connector, allowing   the connector and wires to extend through the hole   in the plate. Next, attach the conduit connector to   the earth plate by replacing and tightening the lock   nut (Figs. 26c and 26d). Then re-attach the earth   plate to the electrical component box with the 2   screws.   Fig. 25b   Fig. 25a   KS1852   KS1852   Electrical   component box   Cover   plate   Cover   plate   Terminal   plate   Earth plate   h) Give some play to the inter-unit wiring from the out-   door unit to the corresponding terminals on the termi-   nal base. (See Wiring System Diagram on page 10.)   Electrical   component box   Fig. 25c   KS0951, KS1251   Fig. 25d   WARNING   Top of conduit   connector   KS1852   I Be sure to refer to the Wiring System Diagram   label inside the electrical component box and   carry out the correct field wiring. Wrong wiring   can cause the unit to misoperate or result in a fire   hazard.   Earth   plate   Screw   Screw   hole   I Check local electrical codes and any specified   wiring instructions or limitations.   Fig. 26a   KS0951, KS1251   i) Fix cover plate and cover plate and back into posi-   tion with their screws.   Fig. 26b   Inter-unit   wiring   NOTE   Earth   plate   KS1852   When closing the air intake grille, press on both corners   and the center. (Fig. 27)   Lock nut   Inter-unit   wiring   Top of conduit   connector   Earth   plate   Lock   nut   Fig. 26c   Top of conduit   connector   Fig. 27   Fig. 26d   11   Loose wiring may cause the termi-   nal to overheat or result in unit mal-   function. A fire hazard may also   exist. Therefore, be sure all wiring   is tightly connected.   WARNING   When connecting each power wire to the corresponding termi-   nal, follow the instructions “How to connect wiring to the termi-   nal” and fasten the wire securely tight with the fixing screw of   the terminal plate.   9/32" (7 mm)   (ACTUAL   SIZE)   STRIP   SIZE   Fig. 28   How to connect wiring to the terminal   a) For Indoor Unit   (1) Cut the wire end with a cutting pliers, then strip the insu-   lation to expose the wire about 9/32 in. (7 mm). See the   label (Fig. 28) near the terminal plate.   Solid wire   Loop   (2) Using a screwdriver, loosen the terminal screw on the ter-   minal plate.   Insulation   (3) Insert the wire and tighten the terminal screw completely   using a screwdriver.   Fig. 29   Stranded wire   b) For Outdoor Unit   Ring   Connector   I For solid core wiring (or F-cable)   (1) Cut the wire end with a cutting pliers, then strip the insu-   lation to expose the solid wire about 15/16 in. (25 mm).   (Fig. 29)   Fig. 30   (2) Using a screwdriver, remove the terminal screw(s) on the   terminal plate.   Twist wire ends   (3) Using the pliers, bend the solid wire to form a loop suit-   able for the terminal screw.   (4) Shape the loop wire properly, place it on the terminal   plate and fix it securely with the removed terminal screw   using a screwdriver.   I For stranded wiring   Fig. 31   (1) Cut the wire end with a cutting pliers, then strip the insu-   lation to expose the stranded wiring about 3/8 in. (10 mm)   and tightly twist the wire ends. (Figs. 30 and 31)   Special   washer   Screw   (2) Using a screwdriver, remove the terminal screw(s) on the   terminal plate.   Screw and   special washer   Ring connector   Terminal plate   (3) Using a ring connector fastener or pliers, securely clamp   each stripped wire end with a ring connector. (Fig. 30)   Ring   connector   Wire   (4) Place the ring connector wire, and replace and tighten the   removed terminal screw using a screwdriver. (Fig. 32)   Wire   Fig. 32   12   3-9. Mounting   (1) To install the indoor unit, mount the indoor unit onto   the 2 tabs on the upper part of the rear plate.   (2) Hold down the air discharge outlet and press the   lower part of the indoor unit until it clicks to secure-   ly fasten to the 2 tabs on the lower part of the rear   plate. (Fig. 33)   Push   NOTE   Fig. 33   For tubing, choose either the right or left tubing direc-   tion and follow the steps below. Also, extend the sup-   port on the back of the indoor unit as a stand to make   your work easier. (Fig. 34)   I Right-side tubing   (1) Shape the refrigerant tubing so that it can easily go   into the wall hole. (Fig. 35)   Stand   Fig. 34   (2) Push the wiring, refrigerant tubing, and drain hose   through the hole in the wall. Adjust the indoor unit   so it is securely seated on the rear panel. (Fig. 36)   Rear panel   Cover   (3) Carefully bend the tubing (if necessary) to run   along the wall in the direction of the outdoor unit   and then tape as far as the fittings. (See Caution   on page 17.) The drain hose should come straight   down the wall to a point where water runoff won’t   stain the wall.   Refrigerant   tubing   Inter-unit   wiring   Drain hose   (4) Connect the refrigerant tubing to the outdoor unit.   (After performing a leak test on the connecting part,   insulate it with the tubing insulation (Fig. 37a)).   Also, refer to Section 5-4. Connecting Tubing   between Indoor and Outdoor Units.   Fig. 35   (5) Assemble the refrigerant tubing, drain hose, and   conduit (including inter-unit wiring) as shown in   Fig. 37b.   Fig. 36   Refrigerant tubing   Insulation   Fig. 37a   Conduit   Drain hose   Inter-unit wiring   Fig. 37b   13   To unmount indoor unit   Press the 2 I marks on the lower part of the indoor   unit and unlatch the tabs. Then lift the indoor unit and   unmount. (Fig. 38)   3-10. Drain Hose   a) The drain hose should be slanted downward to the   outdoors. (Fig. 39)   b) Never form a trap in the course of the hose.   c) If the drain hose will run in the room, insulate the   hose with insulation* so that chilled condensation   will not damage furniture or floors. (Fig. 40)   Push   Fig. 38   * Foamed polyethylene or its equivalent is recom-   mended.   Slant   Do not supply power to the   unit or operate it until all   tubing and wiring to the   outside unit are completed.   WARNING   Indoor   unit   Drain   hose   Fig. 39   Risk of Electric Shock   Condensation   Insulation material   (locally purchased)   must be used.   Fig. 40   14   4. How to Install the Outdoor Unit   Terminal   block   Lock nut   First refer to Section 2. Installation Site Selection.   4-1. Wiring Instructions for the Outdoor Unit   Access panel   Regulations on wire size differ from locality to locality. For field   wiring requirements, please refer to your local electrical   codes. Make sure that the installation fully complies with all   local and national regulations.   Conduit   plate   (1) Remove access panel. (Fig. 41)   (2) Connect the power line according to the drawing on the   panel side.   (3) Be sure to size each wire allowing approx. 4 in. (10 cm)   longer than the required length for wiring. Store excess   wiring inside the cabinet.   Plug   Power supply   Inter-unit line   (4) When connections are completed, check that all connec-   tions are correct as shown in the wiring system diagram   on panel side.   Fig. 41   (5) Be sure to ground the unit according to your local codes.   CAUTION   I Examples of Incorrect Wiring   The following are examples of improper wiring that result in system misoperation. You should confirm that you have   wired the units correctly before beginning the test run.   Problem 1   Problem 2   Short circuit will occur after approx.   3 minutes and the power circuit fuse   blows.   I Air conditioner will not operate.   I Disconnect   (A)   Disconnect   (B)   Disconnect   switch   (C)   switch   switch   1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 G G G G G G Grounding line   Grounding line   Grounding line   Outdoor unit   Outdoor unit   Outdoor unit   Indoor unit   Indoor unit   Indoor unit   Problem 3   Compressor will not start; only indoor unit will operate.   I Disconnect   switch   Disconnect   switch   (D)   (E)   1 2 3 1 2 3 1 2 3 1 2 3 G G G G Grounding line   Grounding line   Outdoor unit   Outdoor unit   Indoor unit   Indoor unit   15   5. Refrigerant Tubing   Deburring   After   Before   5-1. Use of the Flaring Method   Many of the conventional split system air conditioners   employ the flaring method to connect refrigerant tubes   which run between indoor and outdoor units. In this   method, the copper tubes are flared at each end and   connected with flare nuts.   5-2. Flaring Procedure with a Flare Tool   a) Cut the copper tube to the required length with a   tube cutter. It is recommended to cut approx. 12 to   20 in. (30 to 50 cm) longer than the tubing length   you estimate.   Fig. 42   Copper   tubing   b) Remove burrs at the end of the copper tube with a   tube reamer or file. This process is important and   should be done carefully to make a good flare.   (Fig. 42)   Reamer   NOTE   When reaming, hold the tube end downward and be   sure that no copper scraps fall into the tube. (Fig. 43)   Fig. 43   c) Remove the flare nut from the unit and be sure to   mount it on the copper tube.   d) Make a flare at the end of copper tube with a flare   tool.* (Fig. 44)   Flare nut   Copper   tubing   (*Use “RIGID” or equivalent.)   NOTE   A good flare should have the following characteristics:   I inside surface is glossy and smooth.   I edge is smooth.   Flare tool   Fig. 44   I tapered sides are of uniform length.   5-3. Caution before Connecting Tubes Tightly   a) Be sure to apply a sealing cap or water-proof tape   to prevent dust or water from getting into the tubes   before they are used.   Apply refrigerant   lubricant here and here   Fig. 45   b) Be sure to apply refrigerant lubricant to the match-   ing surfaces of the flare and union before connect-   ing them together. This is effective for reducing gas   leaks. (Fig. 45)   c) For proper connection, align the union tube and   flare tube straight with each other, then screw in   the flare nut lightly at first to obtain a smooth   match. (Fig. 46)   Flare nut   Union   Fig. 46   16   5-4. Connecting Tubing between Indoor and   Outdoor Units   Torque wrench   a) Tightly connect the indoor side refrigerant tubing extend-   ed from the wall with the outdoor side tubing. (Fig. 47)   Spanner   Indoor unit   b) To fasten the flare nuts, apply specified torque as:   Table 5   Outdoor unit   Tube Dia.   Tightening Torque   Approx. 130 – 170 lbs. in. (150 – 200 kg cm)   Fig. 47   1/4" (6.35 mm)   3/8" (9.52 mm)   1/2" (12.7 mm)   5/8" (15.88 mm)   · · Approx. 300 – 340 lbs. in. (350 – 400 kg cm)   · · Approx. 430 – 470 lbs. in. (500 – 550 kg cm)   · · Approx. 520 – 560 lbs. in. (600 – 650 kg cm)   · · Insulation   5-5. Insulation of Refrigerant Tubing   IMPORTANT   Fig. 48   To prevent heat loss and wet floors due to dripping of con-   densation, both tubes must be well insulated with a prop-   er insulation material. (Fig. 48) The thickness of the insula-   tion should be a minimum 5/16" (8 mm). (Fig. 49)   Insulation   Thickness:   min. 5/16" (8 mm)   Min.   5/16" (8 mm)   After a tube has been insulated,   CAUTION   never try to bend it into a narrow   curve, as this may cause the tube to   break or crack.   Fig. 49   5-6. Taping the Tubes   a) At this time, the 2 refrigerant tubes (and electrical wire if   local codes permit) should be taped together with armor-   ing tape. The drain hose may also be included and taped   together as 1 bundle with the tubing.   Clamp   Insulated tubes   b) Wrap the armoring tape from the bottom of the outdoor   unit to the top of the tubing where it enters the wall. As   you wrap the tubing, overlap half of each previous tape   turn. (Fig. 50)   Fig. 50   c) Clamp tubing bundle to wall, using 1 clamp approx. every   47 in. (120 cm).   Apply putty here   NOTE   Do not wind the armoring tape too tightly, since this will   decrease the heat insulation effect. Also, be sure the conden-   sation drain hose splits away from the bundle and drips clear   of the unit and the tubing.   Tubing   5-7. Finishing the Installation   Fig. 51   After finishing insulating and taping over the tubing, use seal-   ing putty to seal off the hole in the wall to prevent rain and   draft from entering. (Fig. 51)   17   6. Air Purging   Indoor unit   Air and moisture remaining in the refrigerant system have   undesirable effects as indicated below. Therefore, they must   be purged completely.   I pressure in the system rises   I operating current rises   Outdoor unit   I cooling (or heating) efficiency drops   I moisture in the air may freeze and block capillary tubing   I water may lead to corrosion of parts in the refrigerant sys-   tem   I Air Purging with a Vacuum Pump (for Test Run)   (1) Check that each tube (both narrow and wide tubes)   between the indoor and outdoor units have been properly   connected and all wiring for the test run has been com-   pleted. Note that both narrow and wide tube service   valves on the outdoor unit are kept closed at this stage.   Manifold valve   (2) Using an adjustable wrench or box wrench, remove the   valve caps from the service valve on both narrow and   wide tubes.   Pressure   gauge   Lo   Hi   (3) Connect a vacuum pump and a manifold valve (with pres-   sure gauges) to the service port on the wide tube service   valve. (Fig. 52)   Be sure to use a manifold valve for   CAUTION   air purging. If it is not available, use   a stop valve for this purpose. The   “Hi” knob of the manifold valve   must always be kept closed.   (4) With the “Lo” knob of the manifold valve open, run the   vacuum pump. The operation time for the vacuum pump   varies with tubing length and the capacity of the pump.   The following table shows the amount of time for evacua-   tion:   Vacuum pump   Fig. 52   Table 6   Required time for evacuation when capacity   of 100 liter/h vacuum pump is used   If tubing length is   If tubing length is   less than 33 ft. (10 m)   more than 33 ft. (10 m)   10 min. or more   15 min. or more   NOTE   The required time in the above table is calculated based on   the assumption that the ideal (or target) vacuum condition is   around 10 mmHg abs.   18   (5) With the vacuum pump still running, close the “Lo”   knob of the manifold valve. Then stop the vacuum   pump.   90° (1/4 turn)   Narrow tube   (6) With the accessory hex wrench, turn the valve   stem on the narrow tube service valve counter-   clockwise by 90 degrees (1/4 turn) for 10 seconds,   and then turn the stem clockwise to close it again.   (Fig. 53)   Hex wrench   Wide tube   Be sure to completely insert   CAUTION   Valve cap   the hex wrench before   Vacuum hose to manifold valve   attempting to turn the valve.   Fig. 53   (7) Leak test all joints at the tubing (both indoor and   outdoors) with liquid soap. Bubbles indicate a leak.   Be sure to wipe off the soap with a clean cloth.   (8) With the hex wrench, turn the wide tube service   valve stem counter-clockwise to fully open the   valve.   (9) Turn the narrow tube service valve stem counter-   clockwise to fully open the valve.   (10) Loosen the vacuum hose connected to the wide   tube service port slightly to release the pressure.   Then, remove the hose.   (11) Replace the bonnet and flare nut on the wide tube   service port and fasten the flare nut securely with   an adjustable wrench or box wrench. Next, mount   the valve cap and tighten it with a torque wrench   (the cap needs to be tightened with the torque of   170 lbs.•in. (200 kg•cm)). This process is very   important to prevent gas from leaking from the   system.   (12) Test run the air conditioner. (See next page.)   (13) While the air conditioner is running, apply liquid   soap to check for any gas leaks around the ser-   vice valves or caps.   (14) If there is no leakage, stop the air conditioner.   (15) Wipe off the soap on the tubing.   This completes air purging with a vacuum pump and   the air conditioner is ready for actual operation.   19   * How to Test Run the Air Conditioner.   KS0951, KS1251   (1) Switch on the power source.   (2) Press the ON/OFF button on the remote control   unit once.   ON   OFF   TEST   (3) Set the operation selector switch of the indoor unit   to the TEST position. This starts the fan, producing   uncooled forced air. (Figs. 54a and 54b)   (4) After 3 minutes, the system shifts into cooling   operation, and cool air will start to be felt. Cooling   operation during with the switch at the TEST posi-   tion is unaffected by the room temperature.   (5) After stopping the test run, turn the operation   selector switch of indoor unit to the OFF position   once, then move to ON position.   OPERATION   TIMER   (6) Press the ON/OFF button on the remote control   unit to stop the air conditioner.   NOTE   If the unit does not operate and the OPERATION lamp   on the unit is blinking after going through the proce-   dure, check the wiring between the units.   Fig. 54a   KS1852   Operation   selector   switch   ON   OFF   TEST   Fig. 54b   20   I Basic Function of the Service Valves   The basic function of the service valves are given in Table 7 below.   Table 7   Narrow Tube Service   Valve (2-Way)   Wide Tube Service   Valve (3-Way)   Action   O-ring   Valve cap   Stem   CLOSED   Shipping   Fully OPEN   Fully OPEN   CLOSED   Operating and   test running   the air conditioner   Measuring pressure   and gas charging   * Air purging with   a vacuum pump   * * The service port on the wide tube service   valve uses a Schrader core valve to access   the refrigerant system. Therefore, be sure to   use a hose connector which has a push-pin   inside. (Fig. 55)   Service valve   Hose with push-pin   PUSH   Fig. 55   I Pump Down   valve clockwise all the way to close the service   valve. (Be sure to confirm that the wide tube ser-   vice valve is fully open.)   Pump down means collecting all refrigerant gas in the   system back into the outdoor unit without losing any of   the gas. Pump down is used when the unit is to be   moved or before servicing the refrigerant circuit.   (3) Press the operation button and start cooling opera-   tion.   Pump Down Procedure   (4) When the low pressure gauge reading falls to 1 to   0.5 kg/cm2 (14.2 to 7.1 PSI), fully close the wide   tube valve stem with a standard screwdriver. Then   quickly stop the unit.   Be sure to carry out pump down with the unit in   cooling mode.   (1) Connect the Lo side charging hose of the manifold   valve to the service port on the wide tube service   valve.   (5) Disconnect all gauges and hoses, and replace the   bonnets and the valve caps as they were before.   (2) Using a hex wrench, turn the narrow tube service   21   7. Remote Control Unit Installation Position   The remote control unit can be operated from either a   non-fixed position or a wall-mounted position.   To ensure that the air conditioner operates correctly, do   not install the remote control unit in the following   places:   I In direct sunlight   I Behind a curtain or other place where it is covered   I More than 26 ft. (8 m) away from the air conditioner   I In the path of the air conditioner’s airstream   I Where it may become extremely hot or cold   I Where it may be subject to electrical or magnetic   interference   7-1. Mounting on a Wall   Truss-head   tapping screw   5/32 × 5/8" (4 × 16mm supplied)   1) Confirm the indoor unit beeps when the   ON/OFF button is pressed at the wall location   where the remote control unit is to be attached,   then attach the holder to the wall. (Fig. 56)   2) When taking out the remote control unit, pull it   from the holder.   Remote   control   unit holder   When using the remote control unit   • Point the transmission portion of the remote   control unit at the receiver area of the indoor   unit when operating the remote control unit,   and during operation of the air conditioner.   Fig. 56   • Do not place objects that may block the trans-   mitted signals between the receiver and the   remote control unit.   When mounting the remote control unit to   prevent theft   Truss-head   tapping screw   5/32 × 5/8" (4 × 16mm supplied)   1) Mount the holder to the wall with one of the   screws (using only the hole in the top of the   holder) (Fig. 57).   Holder   2) Remove the cover of the remote control unit   and take out the batteries. Next, place the   remote control unit in the holder.   3) Fasten both the remote control unit and holder   to the wall with the remaining screw (using the   hole in the bottom of the holder).   Holder   Fig. 57   4) Install the batteries in the remote control unit   and close the cover.   22   |