Xantrex Technology Battery Charger DR1512 User Manual

DR1512  
DR2412  
DR1524  
DR2424  
DR3624  
DR1512W  
DR1524W  
DR1512E  
DR1524E  
DR1548E  
DR2424E  
Installation and Operations Manual  
DR Inverter/Charger  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DR Inverter/Charger  
Installation and Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
About Xantrex  
Xantrex Technology Inc. is a world-leading supplier of advanced power electronics and controls with products from  
50 watt mobile units to one MW utility-scale systems for wind, solar, batteries, fuel cells, microturbines, and backup  
power applications in both grid-connected and stand-alone systems. Xantrex products include inverters, battery  
chargers, programmable power supplies, and variable speed drives that convert, supply, control, clean, and distribute  
electrical power.  
Trademarks  
DR Inverter/Charger is a trademark of Xantrex International. Xantrex is a registered trademark of Xantrex  
International.  
Other trademarks, registered trademarks, and product names are the property of their respective owners and are used  
herein for identification purposes only.  
Notice of Copyright  
DR Inverter/Charger Installation and Operations Manual © March 2005 Xantrex International. All rights reserved.  
Disclaimer  
UNLESS SPECIFICALLY AGREED TO IN WRITING, XANTREX TECHNOLOGY INC. (“XANTREX”)  
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY  
TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.  
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT,  
INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH  
INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK.  
Date and Revision  
March 2005 Revision  
Part Number  
975-0012-01-02 Rev A  
Contact Information  
Telephone: 1 800 670 0707 (toll free North America)  
1 360 925 5097 (direct)  
Fax:  
1 800 994 7828 (toll free North America)  
1 360 925 5143 (direct)  
Email:  
Web:  
www.xantrex.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
About This Manual  
Purpose  
The purpose of this Installation and Operation Manual is to provide explanations  
and procedures for installing, operating, maintaining, and troubleshooting the DR  
Inverter/Charger.  
Scope  
The Manual provides safety guidelines, detailed planning and setup information,  
procedures for installing the inverter, as well as information about operating and  
troubleshooting the unit. It does not provide details about particular brands of  
batteries. You need to consult individual battery manufacturers for this  
information.  
Audience  
The Manual is intended for anyone who needs to install and operate the DR  
Inverter/Charger. Installers should be certified technicians or electricians.  
Organization  
This Manual is organized into four chapters and three appendices.  
Chapter 1, “Introduction” contains information about the features and functions of  
the DR Inverter/Charger.  
Chapter 2, “Installation” contains information about how to plan for and install  
the DR Inverter/Charger.  
Chapter 3, “Operation” contains information about how to operate the DR  
Inverter/Charger.  
Chapter 4, “Troubleshooting” contains information about how to troubleshoot  
possible error conditions while using the DR Inverter/Charger.  
Appendix A, “Specifications” contains information about the electrical  
specifications and environmental specifications of the DR Inverter/Charger.  
Appendix B, “Appendix B, “Battery Information” supplies general information  
about batteries such as battery types, battery bank sizing, battery configurations,  
and battery care. For detailed information, see your battery manufacturer or your  
system designer.”  
Appendix C, “Multi-wire Branch Circuit Wiring” supplies information about  
Multi-wire Branch Circuit Wiring Precautions when using stand-alone 120 Vac  
inverters or generators.  
975-0012-01-02 Rev A  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
About This Manual  
Conventions Used  
The following conventions are used in this guide.  
WARNING  
Warnings identify conditions or practices that could result in personal injury or loss of life  
CAUTION  
Cautions identify conditions or practices that could result in damage to the unit or other  
equipment.  
Important: These notes describe things which are important for you to know, but not as  
serious as a caution or warning.  
Abbreviations and Acronyms  
AC  
Alternating Current  
ASC  
AHJ  
Authorized Service Center  
Authority Having Jurisdiction  
COMmunications Port  
Clockwise (rotates to the right)  
Counter-clockwise (rotates to the left)  
Direct Current  
COM  
CW  
CCW  
DC  
DR Inverter  
DRI  
DR Inverter/Charger  
DR Interface (for stacking)  
Light Emitting Diode  
LED  
PV  
Photovoltaic  
PVGFP  
RE  
PV Ground Fault Protection  
Renewable Energy  
RMA  
Return Material Authorization  
Related Information  
You can find more information about Xantrex Technology Inc. as well as its  
products and services at www.xantrex.com.  
iv  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Important Safety Instructions  
SAVE THESE INSTRUCTIONS  
This manual contains important instructions for all DR Inverter/Charger models  
that shall be followed during installation and maintenance of the inverter.  
General  
1. Before installing and using the DR Inverter/Charger, read all instructions and  
cautionary markings on the DR Inverter/Charger and all appropriate sections  
of this guide. Be sure to read all instructions and cautionary markings for any  
equipment attached to this unit.  
2. This unit is designed for indoor use only. Do not expose the DR Inverter/  
Charger to rain, snow, or spray.  
3. To reduce risk of fire hazard, do not cover or obstruct the ventilation  
openings. Do not install the DR Inverter/Charger in a zero-clearance  
compartment. Overheating may result.  
4. Use only attachments recommended or sold by the manufacturer. Doing  
otherwise may result in a risk of fire, electric shock, or injury to persons.  
5. To avoid a risk of fire and electric shock, make sure that existing wiring is in  
good condition and that wire is not undersized. Do not operate the DR  
Inverter/Charger with damaged or substandard wiring.  
6. Do not operate the DR Inverter/Charger if it has received a sharp blow, been  
dropped, or otherwise damaged in any way. If the DR Inverter/Charger is  
damaged, see the Warranty section.  
7. Do not disassemble the DR Inverter/Charger. It contains no user-serviceable  
parts. See Warranty for instructions on obtaining service. Attempting to  
service the DR Inverter/Charger yourself may result in a risk of electrical  
shock or fire. Internal capacitors remain charged after all power is  
disconnected.  
8. The DR Inverter contains more than one live circuit (batteries and AC line).  
Power may be present at more than one source. To reduce the risk of electrical  
shock, disconnect both AC and DC power from the DR Inverter/Charger  
before attempting any maintenance or cleaning or working on any circuits  
connected to the DR Inverter/Charger. Turning off controls will not reduce  
this risk.  
9. Use insulated tools to reduce the chance of short-circuits when installing or  
working with the inverter, the batteries, or a PV array.  
975-0012-01-02 Rev A  
v
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety  
Wiring Requirements  
1. All wiring methods and materials shall be in accordance with the National  
Electrical Code ANSI/NFPA 70 (Current Edition). When sizing conductors  
and conduits interfacing to the DR Inverter, both shall be in accordance with  
the National Electric Code ANSI/NFPA 70, as well as all state and local code  
requirements.  
2. This product is intended to be installed as part of a permanently grounded  
electrical system per the National Electric Code ANSI/NFPA 70 (current  
edition). This is the single point earth ground for the inverter system.  
3. Use copper conductors only with insulation rated for 75 °C.  
4. The grounds on the DR Inverter are marked with this symbol:  
5. The AC voltage and current on the DR Inverter is marked with this symbol:  
6. The DC voltage and current on the DR Inverter is marked with this  
symbol:  
7. Phase on the DR Inverter is marked with this symbol:  
WARNING Fire Hazard:  
Do not install 120 volt AC stand-alone inverters onto 120/240 volt AC multi-branch  
circuit wiring. This could pose a fire hazard due to an overloaded neutral return wire in  
this configuration. See “Multi-wire Branch Circuit Wiring” on page C–1 for details.  
Explosive gas precautions  
WARNING: Explosion Hazard  
Working in the vicinity of lead-acid batteries is dangerous. Batteries generate  
explosive gases during normal operation. Therefore, you must read this guide and  
follow the instructions exactly before installing or using your DR Inverter/  
Charger.  
1. This equipment contains components which tend to produce arcs or sparks.  
To prevent fire or explosion, do not install the DR Inverter/Charger in  
compartments containing batteries or flammable materials, or in locations  
that require ignition-protected equipment. This includes any space containing  
gasoline-powered machinery, fuel tanks, as well as joints, fittings, or other  
connections between components of the fuel system.  
2. To reduce the risk of battery explosion, follow these instructions and those  
published by the battery manufacturer and the manufacturer of the equipment  
in which the battery is installed.  
vi  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety  
Precautions When Working With Batteries  
WARNING: Explosion or Fire Hazard  
Follow all instructions published by the battery manufacturer and the  
manufacturer of the equipment in which the battery is installed.  
1. Make sure the area around the battery is well ventilated.  
2. Never smoke or allow a spark or flame near the engine or batteries.  
3. Use caution to reduce the risk or dropping a metal tool on the battery. It could  
spark or short circuit the battery or other electrical parts and could cause an  
explosion.  
4. Remove all metal items, like rings, bracelets, and watches when working with  
lead-acid batteries. Lead-acid batteries produce a short circuit current high  
enough to weld metal to skin, causing a severe burn.  
5. Have someone within range of your voice or close enough to come to your aid  
when you work near a lead-acid battery.  
6. Have plenty of fresh water and soap nearby in case battery acid contacts skin,  
clothing, or eyes.  
7. Wear complete eye protection and clothing protection. Avoid touching your  
eyes while working near batteries.  
8. If battery acid contacts skin or clothing, wash immediately with soap and  
water. If acid enters your eye, immediately flood it with running cold water  
for at least twenty minutes and get medical attention immediately.  
9. If you need to remove a battery, always remove the grounded terminal from  
the battery first. Make sure all accessories are off so you don’t cause a spark.  
10. Always use identical types of batteries.  
11. Never install old or untested batteries. Check each battery’s date code or label  
to ensure age and type.  
12. Batteries are temperature sensitive. For optimum performance, the should be  
installed in a stable temperature environment.  
13. Always recycle old batteries. Contact your local recycling center for proper  
disposal information.  
975-0012-01-02 Rev A  
vii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
viii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Important Safety Instructions- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -v  
1
Introduction  
Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–2  
Features - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–2  
AC Side - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–3  
DC Side - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4  
Optional Equipment - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4  
Remote Control (RC8) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4  
Stacking Interface (DRI) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4  
Conduit Box (DRCB) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4  
Unpacking and Inspection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4  
Model Identification and Numbering Conventions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–5  
2
Installation  
Pre-installation Planning- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–2  
Location - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–2  
Mounting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–3  
Ventilation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–3  
Tools Required - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–3  
Hardware / Materials Required - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4  
Wiring Considerations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4  
DC Terminal Connections - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4  
Grounding Considerations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4  
AC Grounding - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4  
DC Grounding - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4  
Wire Routing - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4  
Electrical Panels and Circuit Breaker Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–5  
AC Distribution Panel (Sub-Panel) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–5  
DC Disconnect - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–5  
Battery Considerations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–5  
Battery Location - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–6  
Battery Temperature - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–6  
Basic Configurations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–6  
Generators - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10  
Inverter Mounting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–11  
DC Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–13  
DC Circuit Grounding - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–13  
General DC Grounding Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–13  
975-0012-01-02 Rev A  
ix  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Batteries - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–15  
Battery Types - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–15  
Battery Bank Sizing - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–15  
Battery Configuration - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–15  
Battery Cable Sizing - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–16  
DC Disconnect and Over-current Protection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–17  
Battery Cable Connections - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–18  
Connecting the Battery Bank to the Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–19  
Installing a Battery Temperature Sensor - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–21  
AC Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–22  
AC Distribution Panel (Sub-panel) Mounting and Conduit Installation - - - - - - - - - - - - - - -2–22  
Accessing the AC Terminals - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–22  
AC Output Wiring to the AC Distribution Panel (Sub-panel) - - - - - - - - - - - - - - - - - - - - - -2–25  
AC Input Wiring - On-Grid Applications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–26  
AC Input Wiring using a Generator in an On-Grid Application - - - - - - - - - - - - - - - - - - - - -2–27  
AC Input Wiring - Off-Grid Applications using a 120 Vac Generator - - - - - - - - - - - - - - - -2–28  
AC Input Wiring - Off-Grid Applications using a 240 Vac Generator for 120 Vac Loads - - -2–29  
Series Stacking (120 Vac/60 Hz Models only) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–30  
3
Operation  
Front Panel Controls and Indicators- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2  
POWER ON/OFF Switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2  
Ports - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3  
BATTERY SENSE Port - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3  
COM Port - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3  
Remote Controls (RC8/RC4) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3  
Stacking Interface - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4  
Controls - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4  
Battery Type Selector - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4  
SEARCH MODE WATTS Potentiometer - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–6  
Battery Charger Rate - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–7  
Over Discharge Protection/AC Transfer Voltage - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–8  
Over Discharge Protection (ODP) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–9  
AC Transfer Voltage - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–10  
Battery Capacity - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–12  
LED Indicators - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–13  
Inverter Mode LED - Green - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–13  
Over Temp / Overload LED - Red / Green (error condition) - - - - - - - - - - - - - - - - - - - -3–13  
Battery High/Battery Low LED - Red/Green (error condition) - - - - - - - - - - - - - - - - - -3–13  
Charger LED - Orange / Green - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–14  
Audible Indicator (internal) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–14  
Circuit Breakers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–15  
x
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Start-up - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–16  
Charger Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–17  
3-Stage Charging Process - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–17  
Equalize Charging - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–18  
4
Troubleshooting  
Troubleshooting the DR Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–2  
Problem Loads - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–3  
Ceiling Fans - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–3  
Cell Phones - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–3  
Computers and Sensitive Electronics - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–3  
Consumer Electronics - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–3  
Clocks - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–4  
Decreasing Loads - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–4  
Dimmer Switches - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–4  
Fluorescent Lights - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–4  
Heavy Loads - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–4  
Microwave Ovens - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–4  
Printers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–5  
Rechargeable Devices - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–5  
Undersized Loads - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–5  
A
B
Specifications  
Specifications of the DR Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -A–2  
Battery Information  
Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–2  
Battery Types - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–2  
Deep-cycle Flooded Lead Acid (FLA) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–2  
Sealed Batteries (Gel and AGM) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–3  
NiCad and NiFe Batteries - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–3  
Understanding Battery Capacity Ratings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–4  
Battery Bank Sizing- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–4  
Understanding Amp-hour Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–5  
Calculating Amp Hours - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–5  
Amp Hour Example Worksheet - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–6  
Battery bank size worksheet - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–7  
Battery Configurations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–8  
Wiring Batteries in Series - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–8  
Wiring Batteries in Parallel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–9  
Wiring Batteries in Series-Parallel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–10  
Battery Connections for Stacked Inverters - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–12  
975-0012-01-02 Rev A  
xi  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Battery Maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–13  
Battery Charging - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–13  
Equalization Charging - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–15  
General Maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–16  
C
Multi-wire Branch Circuit Wiring  
Multi-wire Branch Circuits - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–2  
Identifying Multi-wire Branch Circuits - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–4  
Correcting Multi-wire Branch Circuit Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–5  
Warranty and Return Information - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - WA–1  
Index - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - IX–1  
xii  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figures  
Figure 1-1 Front Panel Features - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–3  
Figure 1-2 AC Side of the DR Inverter- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–3  
Figure 1-3 DC Side of the DR Inverter- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4  
Figure 1-4 Product Identification - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–5  
Figure 1-5 Model/Serial Number Sticker - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–6  
Figure 2-1 On-Grid Basic Configuration (Utility Backup)- - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–7  
Figure 2-2 Off-Grid Configuration (Generator only) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–7  
Figure 2-3 On-Grid Configuration - with Renewable Energy Sources - - - - - - - - - - - - - - - - - - - - - 2–8  
Figure 2-4 Off-Grid Configuration - with Renewable Energy Sources- - - - - - - - - - - - - - - - - - - - - 2–9  
Figure 2-5 Charge Rate versus Peak AC Voltage- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10  
Figure 2-6 Dimensions (not to scale) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–11  
Figure 2-7 Suggested Mounting Method - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–12  
Figure 2-8 Mounting on Plywood - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–12  
Figure 2-9 DC Grounding - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–14  
Figure 2-10 Battery Cable Connections - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–18  
Figure 2-11 DC Terminals on the DR Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–19  
Figure 2-12 Connecting the Battery Bank to the DR Inverter/Charger- - - - - - - - - - - - - - - - - - - - - 2–20  
Figure 2-13 Battery Temperature Sensor (BTS) RJ11 Jack Location - - - - - - - - - - - - - - - - - - - - - 2–21  
Figure 2-14 Connecting the BTS to the DR Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–21  
Figure 2-15 AC Side Cover Panels - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–23  
Figure 2-16 AC Terminals for AC Input to the Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–24  
Figure 2-17 AC Terminals for AC output to the Sub-panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–25  
Figure 2-18 AC Wiring- On-Grid Application - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–26  
Figure 2-19 AC Wiring using a Generator - On-Grid Application - - - - - - - - - - - - - - - - - - - - - - - 2–27  
Figure 2-20 AC Wiring using a 120 Vac Generator - Off-Grid Application - - - - - - - - - - - - - - - - - 2–28  
Figure 2-21 AC Wiring using a 240 Vac Generator with 120 Vac Loads only- Off-Grid Application2–29  
Figure 2-22 AC Wiring for dual-inverters - On-Grid Application (120 Vac models only) - - - - - - - 2–31  
Figure 2-23 Wiring for dual-inverters - On-Grid Application (120 Vac models only) - - - - - - - - - - 2–32  
Figure 3-1 Front Panel Controls and Indicators - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2  
Figure 3-2 Battery Type Selector Adjustment - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4  
Figure 3-3 Battery Type Selector Adjustment - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–7  
Figure 3-4 Battery Charger Rate Potentiometer (DR1512 values used) - - - - - - - - - - - - - - - - - - - - 3–8  
Figure 3-5 ODP Enabled/Disabled Positions- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–9  
Figure 3-6 Automatically Calculated Discharge Cutoff Voltage per Cell - - - - - - - - - - - - - - - - - - - 3–9  
Figure 3-7 ODP Enabled/Disabled Positions- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–11  
Figure 3-8 Typical Setting for Most Utility Application - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–11  
975-0012-01-02 Rev A  
xiii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figures  
Figure 3-9 Battery Capacity Potentiometer (new) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–12  
Figure 3-10 Battery Capacity Potentiometer (old)- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–12  
Figure 3-11 LED Indicators - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–13  
Figure 3-12 AC Pass-through and Charger AC Input Circuit Breakers- - - - - - - - - - - - - - - - - - - - -3–15  
Figure 3-13 Startup Items - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–16  
Figure 3-14 Charger Controls and Indicators - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–18  
Figure 3-15 Equalize Positions on Battery Type Selector Switch - - - - - - - - - - - - - - - - - - - - - - - -3–19  
Figure 3-16 Equalize 1 Battery Charger Rate Potentiometer (Position “1”)- - - - - - - - - - - - - - - - - -3–20  
Figure 3-17 Equalize 2 Battery Capacity Rate Potentiometer (Position “0”) - - - - - - - - - - - - - - - - -3–20  
Figure B-1 6-volt Battery Wiring - “Series” Configuration - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–8  
Figure B-2 12-volt Battery Wiring - “Series” Configuration - - - - - - - - - - - - - - - - - - - - - - - - - - - B–9  
Figure B-3 Battery Wiring in Parallel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–9  
Figure B-4 Battery Wiring 24-volt - Parallel Configuration - Step 1- - - - - - - - - - - - - - - - - - - - - B–10  
Figure B-5 Battery Wiring 24-volt - Parallel Configuration - Step 2- - - - - - - - - - - - - - - - - - - - - B–10  
Figure B-6 Battery Wiring 24-volt - Parallel Configuration - Step 3- - - - - - - - - - - - - - - - - - - - - B–11  
Figure B-7 Example of Battery Connections for Stacked Inverters (24 Vdc shown) - - - - - - - - - - B–12  
Figure C-1 Conventional Home-type Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–2  
Figure C-2 Multi-wire Branch Circuit Wiring and Current Flow - - - - - - - - - - - - - - - - - - - - - - - - C–3  
Figure C-3 120 Vac Inverter Incorrectly Wired in a Multi-wire Branch Circuit - - - - - - - - - - - - - - C–3  
Figure C-4 Multi-wire Branch Circuit Wiring- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–4  
Figure C-5 Using a Step-down Autotransformer in Multi-wire Branch Circuit Wiring - - - - - - - - C–6S  
xiv  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Tables  
Table 1-1  
Table 1-2  
Table 2-1  
Table 2-2  
Table 2-3  
Table 2-4  
Table 2-5  
Model Identification and Numbering Conventions - - - - - - - - - - - - - - - - - - - - - - - - - - 1–5  
Letter Suffix Code Definitions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–6  
Peak Input Filtrate versus Charging Current - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10  
Safety Ground Conductor Size - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–13  
Minimum Recommended Battery Cable Size versus Length - - - - - - - - - - - - - - - - - - 2–16  
Battery Cable to Maximum Breaker/Fuse Size- - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–17  
Minimum Recommended Wire Size, Torque Values (Input and Output),  
and Maximum Output Breaker Size - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–23  
Table 3-1  
Table 3-2  
Table 3-3  
Table 3-4  
Table 3-5  
Table 4-1  
Battery Type Selector Switch Settings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–5  
Approximate Charge rate Setting/Amperage - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–8  
ODP/AC Transfer Voltage - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–10  
AC Pass-through Circuit Breakers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–15  
Battery Charger Circuit Breakers- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–15  
Troubleshooting the DR Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–2  
Table A-1 Electrical Specifications for the DR Inverter/Charger - 120 Vac/60 Hz Models- - - - - - -A–2  
Table A-2 Electrical Specifications for the DR Inverter/Chargers - 220 Vac/60 Hz Models - - - - - -A–4  
Table A-3 Electrical Specifications for the DR Inverter/Charger - 230 Vac/50 Hz Models- - - - - - -A–5  
Table A-4 Environmental Specifications for the DR Inverter/Charger - - - - - - - - - - - - - - - - - - - -A–7  
Table B-1  
Table B-2  
Table B-3  
Table B-4  
Table B-5  
Table B-6  
Determining Average Daily Load in Amp-hours (Example - - - - - - - - - - - - - - - - - - - -B–6  
Determining Battery Bank Size - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–7  
Typical Appliance Wattage- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–7  
Variances in Charging Voltage based on Battery Temperature - - - - - - - - - - - - - - - - - B–14  
Temperature Compensation Calculation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–14  
Battery State-of-Charge - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–17  
975-0012-01-02 Rev A  
xv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
xvi  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
1
Chapter 1, “Introduction” contains information about the features and  
functions of the DR Inverter/Charger.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
Introduction  
Thank you for purchasing the DR Inverter/Charger from Xantrex Technology Inc.  
The DR Inverter is one of the finest inverter/chargers on the market today,  
incorporating state-of-the-art technology and high reliability.  
The inverter features an AC pass-through circuit, powering your home appliances  
from utility or generator power while charging the batteries. When utility power  
fails, the battery backup system keeps your appliances powered until utility power  
is restored. Internal protection circuits prevent over-discharge of the batteries by  
shutting down the inverter when a low battery condition occurs. When utility or  
generator power is restored, the inverter transfers to the AC source and recharges  
the batteries.  
The front panel features LEDs for reading system status, and controls to  
customize the inverter settings for your battery bank.  
The DR Inverter is an economical product designed to provide a reliable supply of  
electricity to all the essential circuits in the home or business during a power  
outage. The critical loads can be powered for hours or days, depending on the size  
of the system battery bank. When utility grid power returns, the batteries are  
quickly recharged to ensure they will be ready to supply backup power during the  
next outage.  
Accessories allow the DR Series to also serve as a central hub of a renewable  
energy system.  
Modified Sine  
Wave Power  
The DR Inverter provide a modified sine wave output which operates most AC  
appliances and equipment.  
Battery Charger/AC  
Transfer Relay  
The inverter/charger includes a 3-stage battery charger designed to recharge any  
type of battery in the shortest possible time. The built-in, fully automatic AC  
transfer relay automatically transfers power from the utility to the inverter and  
handles a full 60 amps of current at 120 Vac (30 amps for pass-through plus  
20 to 30 amps for charging - depending on the model).  
Simplicity  
The DR Inverter is simple to operate. All inverter and battery charger controls are  
located on the front panel.  
High Efficiency  
The inverter/charger operates at over 90% efficiency through most of its power  
range in Invert-mode.  
Low Power  
Consumption  
DR Inverter use extremely low current while in the search mode, consuming less  
than 1 watt of power. In the ON mode, the inverter/charger uses less than 12 watts  
of power.  
Features  
The following sections illustrate the features of the DR Inverter. Figure 1-1 shows  
the features of the front side of the DR Inverter and identifies the AC side from the  
DC side.  
1–2  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features  
AC End  
DC End  
COM Port  
Front Panel Controls  
and Indicators  
Battery Sense Port  
Battery Caps  
Figure 1-1 Front Panel Features  
AC Side  
The AC side of the DR Inverter has one 30-amp breaker for pass-thru AC Input,  
and one 30-amp (20 amp in certain models) breaker for charger AC input.  
30 Amp Breaker for  
Pass-thru AC Input  
20 or 30 Amp Breaker  
for Charger AC Input  
Ventilation Holes  
Cover plate is not shown  
in this photo.  
Figure 1-2 AC Side of the DR Inverter  
975-0012-01-02 Rev A  
1–3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
DC Side  
The DC side of the DR Inverter has the equipment ground lug, the positive (+)  
battery terminal, and the negative (–) battery terminal.  
Battery Positive  
(+) Terminal  
Ventilation Holes  
Battery Negative  
(–) Terminal  
Ventilation Holes  
Ground Lug  
Figure 1-3 DC Side of the DR Inverter  
Optional Equipment  
The following options are available for the DR Inverter/Chargers.  
Remote Control (RC8)  
The RC8 allows the inverter to be switched ON or OFF remotely and includes an  
LED status indicator. This unit is also compatible with the RC4 (the predecessor  
to the RC8); although the RC4 is no longer available for purchase from Xantrex.  
Stacking Interface (DRI)  
The DRI stacking interface provides 3-wire 120/240 Vac at twice the power using  
dual DR Inverters (120 Vac/60 Hz units only).  
Conduit Box (DRCB)  
The DRCB conduit box connects to the DC side of the inverter and accepts a DC  
conduit run.  
Unpacking and Inspection  
Carefully unpack the inverter/charger from its shipping carton.  
1–4  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features  
Important: The unit weighs 35–45 lb/15.9–20.4 kg (depending on model). Have  
additional help available if necessary, to assist in lifting the unit during installation.  
Verify all of the items listed on the packing material sheet are present. Please  
call Xantrex Customer Service at (800) 670-0707 if any items are missing.  
Save your proof-of-purchase. This is required if the unit should require  
warranty service.  
Save the original shipping carton and packing materials! If the inverter ever  
needs to be returned for service, it should be shipped in the original carton.  
This is also a good way to protect the inverter if it ever needs to be moved.  
Record the unit’s model, serial number and date of purchase in the appropriate  
fields in section “Information About Your System” on page WA–4.  
Important: Due to continual improvement through product updates, photographs and/  
or illustrations used in this manual may not exactly match your unit. Xantrex Technology  
Inc. reserves the right to update this product without notice or releasing an updated  
manual when fit, form or function are not affected.  
Model Identification and Numbering Conventions  
The DR Inverter is identified by the model/serial number labels. The Serial  
Number can be located on the mounting rail or inside the top cover. Model  
Number labels may be located on the bottom side of the front cover or possibly  
inside the front cover. All the necessary information is provided on the label such  
as AC output voltage, power and frequency (punch holes).  
The inverter also has a letter designator followed by 4 or 5 digits (depending on  
revision). The model number describes the type of inverter, the output  
specifications, the required battery voltage and the output voltage and frequency  
Table 1-1 Model Identification and Numbering Conventions  
indicates the type of inverter/charger - DR Series.  
DR  
15  
12  
E
the first two digits of the numerical designator indicate the inverter’s output  
power - 1500 Watts.  
the second two digits indicate the required nominal battery bank voltage -  
12 Vdc.  
the letter suffix code indicates the output voltage and frequency of the inverter -  
230 Vac/50 Hz.  
Product Family  
Country Code  
(Letter Suffix)  
Example: DR 1512 E  
Battery Voltage  
Output Power  
Figure 1-4 Product Identification  
975-0012-01-02 Rev A  
1–5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
Table 1-2 Letter Suffix Code Definitions  
Letter Suffix  
Output Voltage  
120 Vac  
Output frequency  
60 Hz  
(no letter)  
E
J
230 Vac  
50 Hz  
105 Vac  
50 Hz  
K
W
105 Vac  
60 Hz  
220 Vac  
60 Hz  
Figure 1-5 Model Number Sticker  
Regulatory  
The 120 Vac/60 Hz models of the DR Series inverter/charger (models DR1512,  
DR1524, DR2412, DR2424, and DR3624) are ETL Listed to UL Standard 1741,  
(First Edition) Power Conditioning Units for use in Residential and Commercial  
Photovoltaic Power Systems.  
These standards guarantee that the DR Inverter/Charger has been tested to  
nationally recognized safety standards (UL for the US) and have been found to be  
free from reasonably foreseeable risk of fire, electric shock and related hazards.  
The DR Inverter/Charger is intended to be used for residential or commercial  
applications. Do NOT use this unit for applications for which it is not listed  
(i.e., land vehicles or marine craft). It may not comply with the safety code  
requirements or could possibly present other operational or safety hazards.  
1–6  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
2
Chapter 2, “Installation” contains information about how to plan for  
and install the DR Inverter/Charger.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Pre-installation Planning  
Important: Before installing and using the DR Inverter/Charger, read all instructions  
and cautionary markings on the DR Inverter/Charger and all appropriate sections of this  
guide. Be sure to read all instructions and cautionary markings for any equipment attached  
to this unit.  
Take some time prior to installing the equipment to pre-plan the installation.  
Location, mounting, and ventilation should be taking into consideration before  
any cabling can be done.  
CAUTION: Personal Injury  
The inverter/charger can weigh up to 45 lbs (20.4 kg) depending upon configuration.  
Always use proper lifting techniques during installation to prevent personal injury.  
Location  
Inverters contain sophisticated electronic components and should be located in a  
well protected, dry environment away from sources of fluctuating or extreme  
temperatures and moisture. Exposure to saltwater is particularly destructive and  
potentially hazardous.  
Locate the inverter as close to the batteries as possible in order to keep the battery  
cable length short. However, do not locate the inverter above the batteries or in the  
same compartment as vented batteries. Batteries generate hydrogen sulfide gas  
which is corrosive to electronic equipment. They also generate hydrogen and  
oxygen. If accumulated, an arc caused by connecting the battery cables or  
switching a relay could ignite this mixture. Mounting the inverter in a ventilated  
enclosure with sealed batteries is acceptable.  
CAUTION: Corrosion Damage  
If the inverter is installed in a location where it is exposed to a corrosive or condensing  
environment and fails due to corrosion, it will not be covered under warranty.  
Important: Inverters can generate RFI (Radio Frequency Interference). Locate any  
sensitive electronic equipment susceptible to RFI as far away from the inverter as  
possible. This includes radios and TVs.  
2–2  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pre-installation Planning  
Mounting  
The National Building Code requires the inverter be mounted on a vertical surface  
(or wall). The keyhole slots must not be used as the only method of mounting. The  
purpose of the wall mounting requirement is to orient the inverter so that its  
bottom cover, which has no holes, will not allow burning material to be ejected in  
the event of an internal fire. Use 0.25-inch diameter bolts for mounting. The  
mounting surface must be capable of supporting twice the weight of the inverter to  
comply with UL 1741.  
Ventilation  
Install the inverter in a well ventilated area/enclosure for proper operation. The  
inverter’s thermal shutdown point will be reached sooner than normal in a poorly  
ventilated environment, resulting in reduced peak power output and surge  
capability, as well as shorter inverter life.  
The inverter contains an internal fan. Ensure the air vents and intakes are not  
obstructed in any way. Provide a minimum clearance of 6 inches around the top  
and sides of the inverter for ventilation.  
Tools Required  
The following tools may be required to complete this installation.  
#2 Phillips screw driver  
Slotted screw driver  
Assorted open-end wrenches  
Socket wrench and fittings  
Multimeter (True rms)  
Hole saw  
Level  
Wire strippers  
Torque wrench  
Electrical tape  
Pencil  
Utility knife  
975-0012-01-02 Rev A  
2–3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Hardware / Materials Required  
The following hardware or materials may be required to complete this installation.  
4 ft. x 4 ft. sheet of 3/4" plywood or 2 x 4’s studding material  
#12 wood screws (or 1/2" x 1-1/4" lag bolts)  
Conduit and appropriate fittings  
Wire nuts  
Wiring Considerations  
All wiring and installation methods should conform to applicable electrical and  
building codes.  
Pre-plan the wire and conduit runs.  
The AC terminals accept cable sizes up to #6 AWG.  
The DC terminals accept cable sizes up to #4/0 AWG that use ring terminals  
with 5/16" holes.  
For maximum safety, run both AC and DC cables in conduit.  
DC Terminal Connections  
Battery-to-inverter cabling should be only as long as required.  
For Example: If #4/0 AWG cables are used, do not exceed 5 feet (one way) in  
12 Vdc systems; do not exceed 10 feet (one way) in 24 Vdc systems.  
For optimum performance, use pre-assembled battery cables designed specifically  
for this application (available from Xantrex).  
Grounding Considerations  
AC Grounding  
The inverter/charger should be connected to a grounded, permanent wiring  
system. Neutral and ground conductors should only be bonded at the main  
electrical service panel.  
DC Grounding  
The negative battery conductor should be bonded to the grounding system at only  
one point in the system. The size for the conductor is usually based on the size of  
the largest conductor in the DC system.  
2–4  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pre-installation Planning  
Wire Routing  
Determine all wire routes both to and from the inverter and which knockouts are  
best suited for connecting the AC conduits. Possible routing scenarios include:  
AC input wiring from the main electrical service panel to the inverter/charger  
(if used)  
AC input wiring from the generator to the inverter/charger (if used)  
DC input wiring from the RE to the inverter/charger (if used)  
DC input wiring from the batteries to the inverter/charger  
AC output wiring from the inverter/charger to the sub-panel  
Battery Temperature Sensor cable from the batteries to the inverter/charger (if  
used)  
Remote control cable to the inverter/charger (if used)  
DC ground from the batteries to an external ground rod  
Load circuit wiring rerouted from the main service panel to the sub-panel  
Check for existing electrical or plumbing prior to making cuts in the walls. Cut  
holes in the walls at appropriate locations for routing wiring/cables.  
Electrical Panels and Circuit Breaker Requirements  
The following electrical panels and circuit breakers may be required for this  
installation.  
AC Distribution Panel (Sub-Panel)  
Loads backed up by the inverter will need to be rerouted from the main electrical  
panel to a sub-panel. This can be done several different ways, depending upon the  
installation. Always refer to electrical codes for safe wiring practices.  
DC Disconnect  
Install a DC disconnect breaker or fuse in the positive battery line. This breaker  
protects the DC wiring in the event of an accidental short. Size the breaker in  
accordance with the battery cables. Switch this breaker OFF whenever servicing  
the batteries.  
Battery Considerations  
The DR Inverter can support either 12-volt battery banks or 24-volt battery banks.  
The battery voltage MUST match the voltage requirements of the inverter. To  
determine the correct voltage for the system, check the last two digits on the  
inverter’s model number. For example, the DR1512 is a 12-volt inverter and  
requires a 12 Vdc battery system. The DR2424 is a 24-volt inverter and requires a  
24 Vdc battery system.  
975-0012-01-02 Rev A  
2–5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Battery Location  
Locate the batteries in an accessible location. Two feet clearance above the  
batteries is recommended for access to the battery caps. They should be located as  
close to the inverter as possible without limiting access to the inverter’s  
disconnects. Install the batteries to the left of a wall mounted inverter for easy  
access to the DC side of the inverter and shorter cable runs.  
For safety and to limit access to the batteries, a lockable, ventilated, battery  
enclosure or dedicated room should be used. If an enclosure is used, it should be  
vented to the outside via a one inch vent pipe located at the top of the enclosure.  
Install an intake vent at the bottom of the enclosure to promote air circulation.  
These vents exhaust explosive hydrogen gases and must not be overlooked when  
designing an enclosure.  
The enclosure should be made of an acid resistant material or have a finish that  
resists acid to prevent corrosion. It should be capable of holding the electrolyte  
from at least one battery should a leak occur.  
Place a layer of baking soda on the shelves to neutralize any acid that may be  
spilled in the future (lead-acid batteries only).  
Enclosures located outside must be rainproof and screened to prevent access by  
rodents or insects.  
Battery Temperature  
The battery enclosure should provide a fairly stable temperature for the batteries.  
If it is installed in a cold environment, insulation should be used to protect the  
batteries from the cold. The insulation also provides a more consistent  
temperature and better system performance.  
The battery enclosure should not be installed in direct sunlight where the summer  
sun can overheat the batteries. Locate the enclosure where it will be protected  
from the afternoon sun and provide vents in the top and bottom of the enclosure to  
provide air flow. High battery temperatures greatly shortens the life of the  
batteries.  
Basic Configurations  
The following illustrations show basic applications for the DR Inverter/Charger.  
They include the following configurations.  
On-Grid Configuration - Utility Backup  
Off-Grid Configuration - Generator only  
On-Grid Configuration with Renewable Energy Sources  
Off-Grid Configuration with Renewable Energy Sources and a Generator  
Consult with your system design for other possible configurations depending on  
site and code requirements.  
2–6  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pre-installation Planning  
Figure 2-1 On-Grid Basic Configuration (Utility Backup)  
Figure 2-2 Off-Grid Configuration (Generator only)  
975-0012-01-02 Rev A  
2–7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Figure 2-3 On-Grid Configuration - with Renewable Energy Sources  
2–8  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pre-installation Planning  
Figure 2-4 Off-Grid Configuration - with Renewable Energy Sources  
975-0012-01-02 Rev A  
2–9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Generators  
An AC generator can be used as an input source instead of the utility power, or  
can be connected (using additional hardware) to power the loads when utility is  
not present (utility outage), and to charge the batteries. The generator must be of  
the permanently installed type and not a portable type unit used for emergency  
power. Small emergency type (lower power) generators may not have a stable  
enough voltage for the inverter to synchronize to or provide enough current to  
fully charge the batteries.  
The maximum charge rate the battery charger can deliver is dependant upon the  
peak AC voltage available. Since the battery charger uses only the top portion of  
the input sine wave, small variations in peak voltage result in large variations in  
the amount of energy to the charger. The charger’s rated output is based on a  
utility voltage of 120 Vac RMS (the usual measured value). This should have a  
peak voltage of 169 Vac (230 Vac has a peak voltage of 325 Vac). For every 10  
p
p
volts of peak lost, the charge rate is reduced by approximately half.  
Size the generator appropriately for the system, including battery charge and load  
current (typically twice the wattage output of the inverter).  
Table 2-1 and Figure 2-5 demonstrates how the peak voltage available affects the  
charging current.  
Table 2-1 Peak Input Filtrate versus Charging Current  
Peak Voltage  
Available  
DR1512  
70 amps  
35 amps  
15 amps  
DR2412  
120 amps  
60 amps  
25 amps  
DR1524  
35 amps  
17.5 amps  
7 amps  
DR242  
70 amps  
35 amps  
15 amps  
DR3624  
70 amps  
35 amps  
15 amps  
170 Vac  
160 Vac  
145 Vac  
p
p
p
Figure 2-5 Charge Rate versus Peak AC Voltage  
2–10  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pre-installation Planning  
Inverter Mounting  
The DR Series inverter can weigh as much as 45 lb. (20.4 kg). Wallboard is not  
strong enough to support its weight so additional support must be used or added.  
The inverter can be mounted directly to the wall studs if the wall studs are 16"  
apart. If not, then 2x4’s or plywood can be used.  
WARNING: Personal Injury  
Use appropriate lifting techniques. Have extra people on hand to assist in lifting the  
inverter into position while it is being secured.  
To secure the DR Inverter to the wall studs:  
1. Locate the studs and mark their location on the wall.  
2. Measure the desired height from the floor for the inverter to be mounted.  
3. Using a level, run a horizontal line. The length of the line must span at least  
three studs.  
4. Using the dimensions illustrated in Figure 2-6, drill mounting holes into the  
center of the studs for the inverter.  
5. Secure the inverter to the studs using ¼ x 1½ inch lag bolts and washers.  
Figure 2-6 Dimensions (not to scale)  
To secure the DR Inverter to the mounting location using 2 x 4’s or plywood:  
1. Repeat steps 1 through 3 above.  
2. Place a pre-cut 2 x 4 (flat side against the wall) on the marked location and  
drill pilot holes through the 2 x 4’s and studs.  
975-0012-01-02 Rev A  
2–11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
3. Secure the 2 x 4 with #10 wood screws (length to penetrate 1½ inches into the  
studs) as shown in Figure 2-7.  
4. Measure 7 5/8" from the center of the first 2 x 4 and draw another level line.  
Place the center of the second 2 x 4 over this line and secure to the wall as  
described in Step 5.  
5. Using the dimensions illustrated in Figure 2-6, drill mounting holes into the  
center of the 2 x 4’s for the inverter.  
6. Secure the inverter to the 2 x 4’s using ¼ x 1½ inch lag bolts and washers.  
Figure 2-7 Suggested Mounting Method  
Ensure the plywood spans  
across a minimum of three wall  
studs for adequate support.  
Figure 2-8 Mounting on Plywood  
2–12  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DC Wiring  
DC Wiring  
This section describes the DC wiring requirements and how to make the  
connections. It provides the required cable and wire sizes, recommended lengths  
for cables, and disconnect/circuit breaker requirements.  
DC Circuit Grounding  
Grounding is an important part of the system installation and must be performed  
correctly to ensure safe operation of the equipment. Grounding requirements vary  
by country and application. Consult the NEC for specific requirements.  
The ground conductor should be sized appropriately for the over-current  
protection device being used and according to NEC 250-95 (Ninth Edition)  
(see Table 2-2 below for a portion of the NEC code).  
Table 2-2 Safety Ground Conductor Size  
Size of Over-current Device  
Protecting the Conductor  
Minimum Size of the Copper  
Ground Wire  
30 or 60 amp  
100 amp  
#10 AWG  
#8 AWG  
#6 AWG  
#4 AWG  
#3 AWG  
200 amp  
300 amp  
400 amp  
General DC Grounding Requirements  
This product is intended to be installed as part of a permanently grounded  
electrical system per the National Electric Code ANSI/NFPA 70 (current edition).  
This is the single point earth ground for the inverter system.  
To ground the DC circuits:  
1. Connect the negative (-) terminal of the battery bank to an appropriately sized  
conductor and connect it to the ground bus in the DC Disconnect.  
2. Connect an appropriately sized conductor to the Ground bus in the DC  
Disconnect and connect it to the primary system ground.  
The system ground is the same ground used by the AC side of the system.  
975-0012-01-02 Rev A  
2–13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Figure 2-9 DC Grounding  
2–14  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DC Wiring  
Batteries  
The DR Inverter can support either 12-volt battery banks or 24-volt battery banks.  
Before proceeding, ensure you have the appropriate sized batteries for this  
inverter.  
Battery Types  
Batteries are available in different sizes, amp-hour ratings, voltage, liquid or gel,  
vented or non-vented, chemistries, etc. They are also available for starting  
applications (such as an automobile starting battery) and deep discharge  
applications. Only the deep discharge types are recommended for inverter  
applications. Choose the batteries best suited for the inverter installation and cost.  
Use only the same battery type for all batteries in the bank. For best performance,  
all batteries should be from the same lot and date. This information is usually  
printed on a label located on the battery.  
Additional information regarding batteries can be found in the Appendix B,  
“Battery Information”.  
Battery Bank Sizing  
The size of the battery bank determines how long the AC loads will operate in a  
backup mode without utility power. The larger the battery bank, the longer the run  
time. Size the battery bank to the AC load requirements and length of time  
required to run from the batteries. In general, the battery bank should not be  
discharged more than 50%. Additional DC charging devices such as solar, wind,  
hydro, etc., can provide longer run times by recharging the batteries in the absence  
of AC utility or generator power.  
Additional details on estimating battery bank size and capacity can be found in  
“Battery Bank Sizing” on page B–4.  
Battery Configuration  
The battery bank must be wired to match the inverter’s DC input voltage  
specifications (12 Vdc, 24 Vdc, or 48 Vdc). In addition, the batteries can be wired  
to provide additional run time. The various wiring configurations are:  
SERIES - Wiring batteries in series increases the total bank output voltage (to  
match the inverter’s DC requirements).  
PARALLEL - Wiring the batteries in parallel increases the total run time the  
batteries can operate the AC loads.  
SERIES-PARALLEL - Series-parallel configurations increase both the  
battery voltage (to match the inverter’s DC requirements) and run-time for  
operating the AC loads.  
For additional information on how to wire these battery-bank configurations, see  
“Battery Configurations” on page B–8.  
975-0012-01-02 Rev A  
2–15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Battery Cable Sizing  
Proper cable sizing (diameter and length) is critical to the safe and efficient  
operation of an inverter system. Larger diameter cables (smaller AWG number)  
have less voltage drop and are, therefore, more efficient when transferring power  
to and from the batteries. If a cable is undersized (diameter too small), it could  
potentially overheat, creating a fire hazard.  
Cable length is another important factor. Runs should be kept as short as practical.  
Longer cable runs increase resistance, thus lowering the overall efficiency of the  
system. This is especially true in lower voltage systems (i.e., 12 Vdc) where,  
depending upon the length of the cable run, it may be necessary to oversize the  
diameter of the wire, or parallel (double) the cables.  
Important: Only use copper cables. Always use a properly sized cable and length rated  
for the amperage of the inverter and batteries.  
WARNING: Fire Hazard  
Undersized cables can overheat and melt, creating a fire hazard when subjected to heavy  
(peak) loads.  
Table 2-3 provides recommended minimum cable sizes for various cable lengths  
and inverter amperages. These recommendations may not meet all local or NEC  
requirements.  
Important: Run the positive and negative battery cables as close to each other as  
possible by taping them together. This reduces the effects of inductance and produces a  
better waveform thus increasing efficiency. See Xantrex Technical Note 008 on the  
Xantrex website for additional information on Battery Cable Inductance.  
Table 2-3 Minimum Recommended Battery Cable Size versus Length  
Inverter  
Model  
Typical  
Amperage  
1 to 3 feet (one-way) 3 to 5 feet (one-way) 5 to 10 feet (one-way)  
2
2
2
DR1512  
DR2412  
DR1524  
DR2424  
DR3624  
150 A  
240 A  
75 A  
#2/0 AWG (67.4 mm )  
#2/0 AWG (67.4 mm )  
#4/0 AWG (107 mm )  
2
2
2
#4/0 AWG (107 mm )  
#2/0 AWG (67.4 mm )  
#2/0 AWG (67.4 mm )  
2
2
2
#2/0 AWG (67.4 mm )  
#2/0 AWG (67.4 mm )  
#2/0 AWG (67.4 mm )  
2
2
2
120 A  
180 A  
#2/0 AWG (67.4 mm )  
#4/0 AWG (107 mm )  
#4/0 AWG (107 mm )  
2
2
2
#4/0 AWG (107 mm )  
#4/0 AWG (107 mm )  
#4/0 AWG (107 mm )  
Important: If the system includes a large battery bank or large DC source (such as a  
micro-hydroelectric plant or wind generator), increasing the size of the cables and  
disconnects will greatly reduce the number of nuisance outages associated with breaker  
tripping and open fuses.  
2–16  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DC Wiring  
DC Disconnect and Over-current Protection  
For safety and to comply with regulations, battery over-current protection is  
required. Fuses and disconnects must be sized to protect the wiring in the system  
and are required to open before the wire reaches its maximum current carrying  
capability.  
The National Electrical Code (NEC) requires both over-current protection and a  
disconnect switch for residential and commercial electrical systems. These items  
are not supplied as part of the inverter. However, Xantrex offers a DC rated, ETL  
Listed, circuit breaker disconnect module specifically designed for use with  
Xantrex™ inverters to meet NEC compliance. Two amperage ratings are  
available: a DC250 (250 amps) and a DC175 (175 amps) in either single or dual  
breaker configurations for single- or dual-inverter installations.  
Important: Xantrex™ DC disconnects are not designed to accept doubled  
(paralleled) cables which may be required for long cable runs. Also, the plastic  
red and black covers on the DC inverter inputs are not designed to accommodate  
dual cables. If dual cables are used, the optional conduit box (DRCB) must be  
used.  
Some installations may not require conduit or a disconnect device, although  
over-current protection is still required. Xantrex offers a fuse block (TFB)  
providing the code required inverter over-current protection for these applications.  
Refer to the table below for the proper size disconnect device for specific cable  
diameters.  
Table 2-4 Battery Cable to Maximum Breaker/Fuse Size  
Cable Size  
Required  
Maximum Breaker Rating in “Free  
Maximum Fuse  
Size  
Rating in Conduit Size  
Air”  
#2 AWG  
115 amps max  
175 amps max  
250 amps max  
N/A  
170 amps max  
265 amps max  
360 amps max  
TFB200  
TFB300  
TFB400  
#2/0 AWG  
#4/0 AWG  
DC175  
DC250  
Important: The NEC allows rounding to the next standard fuse size from the cable  
rating (i.e., 150 amp cable size rounds up to a standard 175 amp size). The term “free air”  
is defined by the NEC as cabling that is not enclosed in a conduit or a raceway. Cables  
enclosed in conduit or raceways have substantially lower continuous current carrying  
ability due to heating factors.  
975-0012-01-02 Rev A  
2–17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Battery Cable Connections  
Battery cables must have crimped (or preferably, soldered and crimped) copper  
compression lugs unless aluminum mechanical lugs are used. Soldered  
connections alone are not acceptable. High quality, UL-listed battery cables are  
available from Xantrex in an assortment of lengths: 1½ to 10 feet, and in  
#2/0 AWG or #4/0 AWG sizes. These cables are color-coded with pressure  
crimped, sealed ring terminals.  
Figure 2-10 illustrates the proper method to connect the battery cables to the DR  
Inverter’s DC terminals.  
Do not place anything  
between battery cable lug  
and terminal surface.  
Assemble exactly as shown.  
2/0 Copper Compression Lug  
2/0 Aluminum Mechanical Lug  
Figure 2-10 Battery Cable Connections  
CAUTION: Equipment Damage  
The inverter is not reverse polarity protected. Reversing the battery polarity on the DC  
input connections will cause permanent damage to the inverter which is not covered under  
warranty. Always check polarity before making connections to the inverter.  
WARNING: Shock Hazard  
Ensure the inverter is off before disconnecting the battery cables, and that AC power is  
disconnected from the inverter input.  
2–18  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DC Wiring  
Positive (+)  
Battery Terminal  
Negative (–)  
Battery Terminal  
Torque the  
Positive (+)  
Batteryterminalto  
10-15 ft-lbs  
(13.6 to 20.3 nm)  
Torque the  
Negative (–)  
Battery terminal to  
10-15 ft-lbs  
(13.6 to 20.3 nm)  
Torque value for  
the Ground Lug  
is 10-15 in-lbs  
(1.1 to 1.7 nm)  
Ground Lug  
Figure 2-11 DC Terminals on the DR Inverter  
Connecting the Battery Bank to the Inverter  
Follow the procedure below to connect the battery bank to the inverter.  
WARNING: Shock Hazard  
Ensure the inverter is off before connecting or disconnecting the battery cables and that all  
AC power is disconnected from the inverter’s inputs.  
:
To connect the battery bank to the inverter:  
1. Determine the correct size battery cable to use for installation from Table 2-3  
on page 2–16.  
2. Determine the correct size disconnect/fuse for installation from Table 2-4 on  
page 2–17.  
3. Color code the cables with tape or heat shrink tubing. The standard colors are  
red for positive (+) and black for negative (–). (NEC requires white for the  
negative conductors.)  
4. Connect the negative (–) cable to the battery’s negative terminal (torque to  
manufacturer’s recommendations).  
5. Install the over-current device (fuse or circuit breaker) between the battery’s  
positive terminal and the inverter’s positive terminal (as close to the batteries  
as possible).  
6. Connect the (short) positive cable to the battery’s positive terminal (torque to  
manufacturer’s recommendations).  
7. Ensure the correct polarity of the cables with a DC voltmeter (DVM).  
975-0012-01-02 Rev A  
2–19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
8. Observing battery polarity, connect the positive battery cable (from the  
over-current device) to the inverter’s positive terminal.  
Important: The next step may cause a small spark and snapping sound when  
connecting the cable to the inverter. This is normal, and is caused by the inverter’s  
capacitors charging up.  
9. Observing battery polarity, connect the negative battery cable to the inverter’s  
negative terminal.  
10. Use an insulated ½ inch wrench or socket to tighten the 5/16 SAE nuts to  
10-15 ft-lb (13.6 to 20.3 nm) for each inverter input terminal.  
CAUTION: Equipment Damage  
Do not put anything between the cable ring terminal and the flat metal part of the terminal.  
overheating of the terminal may occur. Do not apply any type of antioxidant paste until  
after the battery cable wiring is tightened.  
:
Equip  
11. Apply antioxidant paste to the battery and inverter terminals.  
12. Install the battery terminal connection covers (red for positive, black for  
negative) over the inverter’s DC terminals and secure with the screws and  
washers provided.  
Figure 2-12 Connecting the Battery Bank to the DR Inverter/Charger  
2–20  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DC Wiring  
Installing a Battery Temperature Sensor  
A battery temperature sensor (BTS) option can easily be installed in the system to  
ensure proper charging of the batteries based on temperature. Installing a BTS  
extends battery life by preventing overcharging in warm temperatures and  
undercharging in cold temperatures.  
To install the Battery Temperature Sensor:  
1. Run the battery temperature sensor wire in the DC conduit (if used) and route  
the RJ11 connector end to the BATTERY SENSE port located on the front of  
the inverter.  
2. Secure the sensor to one of the batteries located in the center of the battery  
pack.  
Battery Sense  
(RJ11) port  
Figure 2-13 Battery Temperature Sensor (BTS) RJ11 Jack Location  
Figure 2-14 Connecting the BTS to the DR Inverter  
975-0012-01-02 Rev A  
2–21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
AC Wiring  
This section describes the AC wiring requirements and how to make the  
connections. It provides the required wire sizes, recommended lengths for  
conductors, and disconnect/circuit breaker requirements.  
Important: The installation of sub-panels and wiring should be performed by a  
qualified person or a licensed electrician following all local and NEC codes.  
AC Distribution Panel (Sub-panel) Mounting and Conduit Installation  
WARNING: Shock Hazard  
Disconnect the power from the utility’s main breaker box before proceeding.  
1. Determine the location of the sub-panel and install it according to the  
manufacturer’s directions.  
2. Install the AC conduit between the sub-panel (output) and inverter.  
3. Install conduit between the inverter (input) and the main breaker box.  
4. Determine which circuits require backup. Install the appropriate circuit  
breakers into the sub-panel.  
5. Install an appropriately sized circuit breaker (30 amp maximum) in the  
sub-panel. This will later be wired to the inverter’s output. If two inverters are  
being used in a stacked configuration, install a double-pole circuit breaker for  
240 Vac service.  
Accessing the AC Terminals  
CAUTION: Equipment Damage  
The inverter’s AC output must never be wired to the utility or generator output. This will  
cause severe damage to the inverter which is not covered under warranty.  
All AC wiring connects to the terminal block located on the right-hand side of the  
inverter.  
To make the AC connections to the inverter:  
1. To access the terminal block, remove the side cover panels (if installed) by  
removing the two (or three) Phillips screws. Units are shipped without the  
covers installed (packed in a small plastic bag with additional hardware).  
2. Locate the AC input and output terminals on the block. Refer to Figure 2-15  
on page 2–23.  
2–22  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AC Wiring  
Important: The lower AC cover varies depending on the model. DR24XX and  
DR36XX models are equipped with a conduit box and not a plate. The conduit box is  
required for the larger diameter wire providing ample bending radius.  
Screws  
Standard Cover Plate  
High Power Conduit Box  
DR24XX and DR36XX models  
DR15XX  
Figure 2-15 AC Side Cover Panels  
Before wiring the input of the inverter, refer to Table 2-5 below for the minimum  
recommended wire size.  
Important: Refer to the NEC for actual wire sizes for specific installations.  
Table 2-5 Minimum Recommended Wire Size, Torque Values (Input and Output), and Maximum Output  
Breaker Size  
AC Input  
220-240 Vac 120 Vac  
AC Output  
Torque Value Maximum  
for Terminal Output  
Inverter  
Model  
120 Vac  
220-240 Vac Connections Breaker Size  
DR1512 #8 or 6 AWG  
DR2412 #6 AWG  
DR1524 #8 or 6 AWG  
DR2424 #6 AWG  
DR3624 #6 AWG  
#10 AWG  
#10 AWG  
#10 AWG  
#10 AWG  
#10 AWG  
#10 AWG  
#10 AWG  
#10 AWG  
#16 AWG  
#14 AWG  
#16 AWG  
#14 AWG  
16 in-lbs  
(1.8 nm)  
30 amps AC  
30 amps AC  
30 amps AC  
30 amps AC  
30 amps AC  
16 in-lbs  
(1.8 nm)  
16 in-lbs  
(1.8 nm)  
16 in-lbs  
(1.8 nm)  
Not Available #8 AWG  
Not Available 16 in-lbs  
(1.8 nm)  
WARNING: Fire Hazard  
To reduce the risk of fire, connect only to a circuit provided with the maximum  
branch-circuit overcurrent protection noted above in accordance with the National  
Electrical Code, ANSI/FFPA70.  
975-0012-01-02 Rev A  
2–23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Important: The U.S. requires conduit be used in this type of installation. Refer to the  
NEC and local codes. Conduit fittings can be replaced with strain reliefs where code  
permits.  
WARNING: Shock Hazard  
Disconnect the battery cables from the inverter if they are already connected.  
To connect the AC Input to the Inverter:  
1. Disconnect the main breaker at the main electrical service panel (if used) or  
disconnect the AC generator.  
2. Install an appropriately sized circuit breaker in the electrical service panel.  
This will serve as both an AC disconnect and over-current protection. If using  
a generator only, use the circuit breaker in the generator.  
3. Feed the HOT, NEUTRAL, and GROUND wires (using conduit) from the  
inverter to the AC source. Leave several inches of extra wire at each end.  
4. Make the connections to the inverter first. Wiring to the AC source is  
performed after all connections have been made in the inverter.  
a) Connect the GROUND (green) wire to the inverter’s AC GROUND  
terminal.  
b) Connect the NEUTRAL (white) wire from the AC source to the inverter’s  
NEUTRAL INPUT terminal.  
c) Connect the HOT (black) wire from the AC source to the inverter’s AC  
HOT INPUT terminal.  
5. Torque all connections to 16 in-lbs (1.8 nm).  
Torque the  
terminal  
connections to  
16 in-lbs (1.8 nm)  
NEUTRAL IN  
GROUND  
HOT IN  
Figure 2-16 AC Terminals for AC Input to the Inverter  
2–24  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AC Wiring  
AC Output Wiring to the AC Distribution Panel (Sub-panel)  
Important: The ground and neutral must be bonded at one place, and only one place, in  
the system. If the generator is the main source of power, (i.e., no utility grid power) then  
the neutral and ground connections are bonded at the generator. If the generator is acting  
as a backup for the utility grid, then the bond should be at the main utility service entrance  
box. In this case, ensure that no bond exists at the generator output.  
To connect the AC output wiring to the sub-panel:  
1. Connect the GROUND wire to the inverter’s AC GROUND chassis terminal.  
Connect the other end of this wire to the GROUND bus in the sub-panel.  
2. Connect the NEUTRAL (white) wire to the inverter’s NEUTRAL OUTPUT  
terminal. Connect the other end of this wire to the NEUTRAL bus in the  
sub-panel.  
3. Connect the HOT (black) wire to the inverter’s terminal labeled AC HOT  
OUTPUT. Connect the other end of this wire to the sub-panel’s input circuit  
breaker.  
4. Torque all inverter terminal block connections to 16 in-lbs (1.8 nm).  
5. Refer to the sub-panel manufacturer’s specifications for wire torque  
requirements to sub-panel terminals.  
Torque the terminal  
connections to  
16 in-lbs (1.8 nm)  
NEUTRAL  
OUT  
GROUND  
HOT  
OUT  
Figure 2-17 AC Terminals for AC output to the Sub-panel  
Important: The two neutral connections (input and output) are common to one another  
and may be used in any combination.  
975-0012-01-02 Rev A  
2–25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
The following diagrams illustrate the AC wiring for the following basic  
120/240 Vac scenarios. Consult your system design for other possible  
configurations.  
On-Grid Application (See Figure 2-18)  
On-Grid using with a generator Backup (See Figure 2-19)  
On-Grid Dual-Inverter Application (See Figure 2-20)  
Off Grid Application using a 120 Vac Generator (See Figure 2-21)  
Off-Grid Application using a 240 Vac Generator (See Figure 2-22)  
Off-Grid Dual-Inverter Application (see Figure 2-23)  
AC Input Wiring - On-Grid Applications  
Follow the example below to complete the wiring for an on-grid application.  
Figure 2-18 AC Wiring- On-Grid Application  
2–26  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AC Wiring  
AC Input Wiring using a Generator in an On-Grid Application  
If a generator is used as a backup for the utility, then a manual transfer switch  
must be added to provide a means to switch the generator power to the inverter’s  
inputs. The generator can be used during extended outages to recharge the  
batteries and provide pass through power for the loads. Start and stop the  
generator manually using the generator’s pull-cord, ON/OFF switch, etc.  
Figure 2-19 AC Wiring using a Generator - On-Grid Application  
975-0012-01-02 Rev A  
2–27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
AC Input Wiring - Off-Grid Applications using a 120 Vac Generator  
Follow the example below to complete the wiring for an off-grid application.  
Figure 2-20 AC Wiring using a 120 Vac Generator - Off-Grid Application  
2–28  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AC Wiring  
AC Input Wiring - Off-Grid Applications using a 240 Vac Generator for  
120 Vac Loads  
Follow the example below to complete the wiring for an off-grid application.  
Figure 2-21 AC Wiring using a 240 Vac Generator with 120 Vac Loads only- Off-Grid Application  
975-0012-01-02 Rev A  
2–29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Series Stacking (120 Vac/60 Hz Models only)  
This COM port allows two DR Inverters (120 Vac/60 Hz models only) to be used  
in the same system in a “SERIES” configuration to operate 240 Vac loads. Series  
stacking can also be used to connect to 240 Vac only power systems providing  
both 120 and 240 Vac outputs. A series stacking interface cable (DRI) is required  
to connect the series stacking port of the inverters.  
In this mode, one of the inverters will function as the “primary” and the other  
inverter becomes the “secondary.” The first unit switched ON becomes the  
primary and ensures the secondary’s output is 180 degrees out of phase for  
240 Vac operation. Both units can charge the batteries or provide battery backup  
power during a utility outage.  
The following illustrations provide a general overview of AC configurations using  
stacked inverters. Detailed wiring and operating instructions are provided with the  
DRI interface kit available from Xantrex Technology Inc.  
The following diagrams illustrate the AC Wiring for a basic On-Grid and Off-Grid  
application.  
2–30  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AC Wiring  
Figure 2-22 AC Wiring for dual-inverters - On-Grid Application (120 Vac models only)  
975-0012-01-02 Rev A  
2–31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Figure 2-23 Wiring for dual-inverters - On-Grid Application (120 Vac models only)  
2–32  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
3
Chapter 3, “Operation” contains information about how to operate the  
DR Inverter/Charger.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Front Panel Controls and Indicators  
All operating controls, indicators and sense connectors are located on the front  
panel of the unit. The controls are easily accessible, and the LEDs provide  
inverter/charger status at a glance.  
Battery Charge Control  
LED Status  
Indicators  
Battery Type Selector  
Inverter Mode Controls  
(Search Watts)  
Inverter Mode Indicator  
Battery Sense Port  
POWER ON/OFF  
COM Port  
Figure 3-1 Front Panel Controls and Indicators  
POWER ON/OFF Switch  
The POWER ON/OFF control is a momentary contact switch that turns the  
inverter/charger ON or OFF by pressing it once. When the inverter is first  
connected to the batteries, it will run through a self test consisting of flashing the  
LEDs in sequence, operating the cooling fan momentarily and switching the  
transfer relay three times. Once the self test has successfully completed, the  
POWER ON/OFF switch is activated. Pressing the switch once turns the inverter  
ON. Another press turns the inverter OFF.  
3–2  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Front Panel Controls and Indicators  
Ports  
There are two ports on the inverter/charger. Both ports are RJ11 type telephone  
style connectors. One is used for connecting a remote control to the inverter. The  
other is used for regulating the charger voltage based on the temperature of the  
battery bank.  
BATTERY SENSE Port  
The BATTERY SENSE Port is used for connecting a battery temperature sensor  
(BTS) to control the charging rate based on battery temperature. The sensor  
should be taped onto the side of one of the batteries. The information received in  
this port adjusts the charger’s output higher in cold temperatures, assuring the  
batteries receive a full charge, and lowers it during warm temperatures, reducing  
battery gassing and providing overcharge protection.  
Important: The Battery Sense only adjusts charging voltage. It does not disable the  
charger.  
Refer to the Installation section for the BTS location on the battery.  
COM Port  
COM PORT (J1) is a dual function RJ11 (6-pin) connector. Its primary function is  
to provide serial communications to an optional Xantrex™ remote control unit  
(RC4 or RC8). The port also acts as a stacking interface control when two DR  
Inverters are used in a series configuration. When two inverters are stacked, a  
remote control cannot be used with either unit.  
Remote Controls (RC8/RC4)  
DR Inverter are designed to operate with either an RC8 or RC4 remote control  
units. Both remotes incorporate a membrane switch with a single red LED display  
combination to start and stop the inverter, as well as provide overall system  
operating status.  
Solid - With AC line power present, the unit is charging the batteries while  
directing AC to the load. With no AC line power present, the inverter is  
running on the batteries and supplying AC to the load.  
Blinking Slow (1 to 3 flashes @ 1 second intervals) - The inverter is in search  
mode (no load connected).  
Blinking Fast (3 to 5 flashes @ 1 second intervals) - The inverter is charging  
the batteries.  
Flickering (3 to 5 flashes @ 1 second intervals) - The inverter has detected an  
over-current error. The LED (and inverter) will turn OFF whenever an over-  
current condition exceeds eight seconds.  
975-0012-01-02 Rev A  
3–3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Erratic Blinking (0 to 3 and 2 to 5 flashes @ 2 second intervals) - The  
inverter has detected an error condition caused by overheating, low battery  
voltage, or high battery voltage.  
OFF - The inverter is OFF.  
The remote control must be connected prior to switching the inverter ON;  
otherwise, the micro-controller will not recognize (or respond to) the remote. If  
the remote is not recognized, switch the inverter OFF and then ON using the  
inverter’s front panel POWER ON/OFF switch.  
Stacking Interface  
Whenever two DR Series inverters are used in a series (stacked) configuration,  
one unit (primary) controls the other unit (secondary). Communication between  
the two inverters is done via the COM port (J1). The first unit switched ON, using  
its front panel POWER ON/OFF switch, becomes the controlling (primary)  
inverter.  
Controls  
There are several controls on the inverter’s front panel that provide adjustments  
for the battery charger, and AC output energy saving mode.  
Battery Type Selector  
The Battery Type Selector is a 10 position rotary switch used to set the inverter’s  
charger for the proper Float and Bulk voltage levels. These levels are selected  
depending on the type of batteries used.  
There are also 2 positions (0 and 1) which allow the batteries to be equalized.  
Equalizing batteries should only be done on liquid lead acid batteries and never on  
gel batteries. Refer to the table below for the charge voltages in the various switch  
positions. Consult the battery manufacturer for optimum battery voltage charging  
settings.  
Battery Type Selector Enlargement  
(pointing to Setting 7)  
Figure 3-2 Battery Type Selector Adjustment  
3–4  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Front Panel Controls and Indicators  
Table 3-1 Battery Type Selector Switch Settings  
12-volt Models  
24-volt Models  
Charge Function  
Bulk/  
Equalize* Float  
Bulk/  
Equalize*  
Equalize Charge  
Switch  
Position  
Float  
Voltage Voltage  
Description  
Rate  
Equalize Time  
Voltage Voltage  
0
Equalize 1 -  
equalizes at a rate  
equal to the  
13.2  
*15.0  
26.4  
*30.0  
Battery Capacity  
Setting (C/40)  
6 hrs. minimum  
12 hrs. maximum  
battery bank  
capacity (in amp-  
hours) divided by  
40.  
1
2
Equalize 2 -  
charges at a rate  
set by the  
BATTERY  
CHARGER  
RATE control.  
13.2  
13.3  
*15.5  
15.0  
26.4  
26.6  
*31.0  
30.0  
Battery Charger  
Rate Setting  
(manual)  
6 hrs. minimum  
12 hrs. maximum  
Deep Cell Lead  
Acid 2  
Provides an additional Float and Bulk  
settings for deep cycle, lead acid batteries.  
Refer to the battery manufacturer’s  
recommendation for Float and Bulk  
settings.  
3
4
Not Specified  
Gel Cel 2  
13.6  
13.7  
14.3  
14.4  
27.2  
27.4  
28.6  
28.8  
Provides an additional setting of Bulk and  
Float voltages.  
Recommended for gel cell batteries that  
specify high float voltages. Check with the  
battery’s manufacturer.  
5
6
Gel Cell 1  
13.5  
13.2  
14.1  
14.3  
27.0  
26.4  
28.2  
28.6  
Typical gel cell setting.  
PcCa-lead  
Calcium  
Use this setting for sealed type car  
batteries.  
7
Deep Cycle  
Lead Acid 1  
13.4  
14.6  
26.6  
29.2  
Factory setting for typical deep cycle  
lead acid batteries.  
(Default Setting)  
8
9
NiCad 1  
NiCad 2  
14.0  
14.5  
16.0  
16.0  
28.0  
29.0  
32.0  
32.0  
Use for NiCad battery systems.  
Recommended for use with nickel iron  
batteries.  
See Important notes that follow.  
975-0012-01-02 Rev A  
3–5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Important:  
1. Switch positions “0” and “1” are for monthly battery maintenance only.  
Return the switch to the appropriate position for the system’s batteries when  
Equalize charging has completed. NEVER EQUALIZE GEL BATTERIES!  
Use together with BATTERY CHARGER RATE potentiometer (position1) or  
BATTERY CAPACITY potentiometer (position 0).  
2. Equalize voltages are displayed in the table with an asterisk (*) - Switch  
positions “0” and “1” only.  
3. Switch position “7” is the default values as shipped from the factory.  
4. Always refer to the battery manufacturer’s specifications for equalization.  
SEARCH MODE WATTS Potentiometer  
The Search Mode Watts potentiometer adjusts the current threshold required to  
bring the inverter out of search mode into full wave operation. With search mode  
enabled, the inverter pulses the AC output looking for an applied load. With no  
load detected, the inverter goes into the search mode to minimize energy  
consumption. When a load is applied, the load current is sensed, bringing the  
inverter into full power operation. Disabling the threshold (setting the  
potentiometer fully CCW) causes the inverter to remain ON (in full power  
operation) regardless of an applied load.  
To set the Search Mode Watts:  
1. Remove the AC input source from the inverter. The inverter switches to  
battery operation. Ensure all inverter supported appliances are switched OFF.  
2. Turn the potentiometer completely CW (to MAX).  
3. Switch on the load which will trigger the inverter to full power. This could be  
a lamp located in a convenient location if the power goes out. The light may  
flicker as the inverter searches the line for a load. The green INVERTER  
MODE LED blinks 2-3 times a second, indicating the inverter is in the  
SEARCH MODE.  
4. Slowly turn the potentiometer CCW (toward MIN) when the proper setting is  
found, the lamp and INVERTER MODE LED will light steady.  
5. Turn the lamp OFF for a moment. The inverter should switch back to the  
SEARCH MODE. Turn the lamp ON. Ensure the inverter comes out of the  
Search Mode. Adjust the potentiometer up or down as necessary.  
Important: The Search Mode only activates when the unit is operating in the inverter  
mode (from batteries) to prevent unnecessary battery discharge when electrical power is  
not required. If the inverter is supporting loads that must constantly be powered, turn the  
search mode OFF by setting the potentiometer fully CCW to the DEFEAT position.  
3–6  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Front Panel Controls and Indicators  
Important: Some loads constantly draw power even though they are switched OFF.  
These include: TVs with instant-ON circuits, microwaves with digital displays, VCRs,  
etc. It is best to operate these devices from another circuit or install a switch to turn these  
OFF completely or don’t use the Search Mode.  
Important: When the SEARCH MODE is used with series stacked inverters, only  
120 Vac loads connected to the “master” inverter will bring the unit out of the search  
mode. See “AC Transfer Voltage” on page 3–10.  
Lower wattage device  
turns ON inverter  
Search Mode  
Potentiometer  
Higher wattage device  
DEFEAT Switches  
Search Mode OFF  
turns ON inverter  
Figure 3-3 Battery Type Selector Adjustment  
Battery Charger Rate  
The Battery Charger Rate potentiometer sets the maximum charge current  
supplied to the battery bank and is also used to regulate constant current in the  
Bulk Charge Mode. The level should be adjusted to provide a charge rate less than  
or equal to the amp-hour capacity of the battery bank divided by a factor of five.  
Example:  
1. Inverter DR1512 has a maximum charge rate of 70 amps.  
a) Battery bank amp-hour capacity = 500 amp-hours using gel cell batteries.  
b) Divide the amp-hour capacity by 5 (500/5 = 100).  
c) Set the potentiometer to MAX (70 amps) as it is less than 100.  
2. Inverter DR1512 has maximum charge rate of 70 amps.  
a) Battery bank amp/hour capacity is 250 amp-hours using gel cell batteries.  
b) Divide the amp-hour capacity by 5 (250/5 = 50).  
c) Set the potentiometer to approximately 71% (50 amps).  
975-0012-01-02 Rev A  
3–7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Use Table 3-2 to find the approximate setting of the Battery Charge Rate  
potentiometer. The settings do not need to be exact, but should be as close as  
possible to the actual value required.  
Important: The potentiometer does not have an arrow to indicate its position. Use a  
small blade screwdriver and rotate the control completely CCW to find the start position.  
Rotate the potentiometer CW to the desired position (i.e., halfway between the stops for a  
50% setting).  
Table 3-2 Approximate Charge rate Setting/Amperage  
Percent of Potentiometer Rotation (between stops)  
100%  
Model  
0% Min.  
25%  
50%  
75%  
Max  
DR1512  
DR2424  
DR3624  
0 amps  
17.5 amps  
35 amps  
52.5 amps 70 amps  
DR2412  
DR1524  
0 amps  
0 amps  
30 amps  
60 amps  
90 amps  
120 amps  
8.75 amps  
17.5 amps  
26.25 amps 35 amps  
25%  
(17.5 amps  
50%  
(35 amps  
75%  
(50 amps)  
Example 2  
0%  
(0 amps  
100%  
(70 amps)  
Example 1  
Figure 3-4 Battery Charger Rate Potentiometer (DR1512 values used)  
Over Discharge Protection/AC Transfer Voltage  
The Over Discharge Protection/AC Transfer Voltage potentiometer performs two  
related functions. When set between the 2 and 5 o’clock position (right), both  
ODP and the AC Transfer Voltage function simultaneously (see table on next  
page). When the potentiometer is set between the 9 and 1 o’clock position (left),  
only the AC Transfer Voltage is functional (ODP is disabled).  
Important: The ODP is not scaled. It is either on or off. The min/max settings only  
refer the AC transfer function.  
3–8  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Front Panel Controls and Indicators  
Over Discharge Protection (ODP)  
When enabled, ODP shuts down the inverter at a specified voltage (low battery  
cutoff) to protect the batteries from over discharge damage. The inverter circuitry  
calculates the lowest (safe) DC voltage (leaving approximately 20% battery  
capacity) based on the position the Battery Type Selector switch and the amount  
of current drawn by the load. Under no-load conditions this level is typically  
between 11.8 and 12.0 Vdc (for a 12-volt battery bank).  
Important: The range of set points between 2 and 5 o’clock also determine the low AC  
Transfer Voltage. This must be considered when adjusting this potentiometer with ODP  
enabled (see Table 3-3).  
Important: When ODP is disabled (set points between 9 and 1 o’clock), the inverter is  
programmed to shut OFF when the batteries reach approximately 8.5 Vdc (1.4166 V/cell)  
for 12-Vdc systems (17 Vdc for 24-volt systems).  
ODP Disabled  
Range  
ODP Enabled  
Range  
Figure 3-5 ODP Enabled/Disabled Positions  
12 Vdc 24 Vdc  
12.0  
24.0  
2
1.95  
1.9  
11.4  
10.8  
22.8  
21.6  
1.85  
1.8  
1.75  
1.7  
10.2  
9.6  
20.4  
19.2  
1.65  
1.6  
1.55  
1.5  
9.0  
18.0  
1
0.001  
0.01  
Discharge Rate/Battery Capacity  
0.1  
Figure 3-6 Automatically Calculated Discharge Cutoff Voltage per Cell  
975-0012-01-02 Rev A  
3–9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
AC Transfer Voltage  
During normal operation, the inverter supplies AC power to the applied loads  
through the pass-through circuit and simultaneously charges the system batteries.  
Whenever the external AC source drops below the AC Transfer Voltage (set by  
the potentiometer), the inverter switches to battery power in order to maintain the  
connected load.  
Examples (120 Vac inverter system):  
1. The AC Transfer Voltage potentiometer is set to 9:00 o’clock with ODP  
disabled. Whenever the incoming AC voltage drops to 40 volts or below, the  
inverter will switch to battery power.  
2. The AC Transfer Voltage potentiometer is set to 2:00 o’clock with ODP  
enabled. Whenever the incoming AC voltage drops to 105 volts or below, the  
inverter will switch to battery power.  
Important: ODP does not affect the operation of the AC Transfer Voltage. ODP is  
either ON or OFF, depending upon the position of the potentiometer.  
Important: There are 6 settings available for the AC Transfer Voltage for both ODP  
OFF and ON as shown in the Table 3-3 below.  
Important: To achieve the fastest transfer time (typically less than 16 ms), set the AC  
Transfer Voltage potentiometer near the 2:00 o’clock position (with the ODP enabled); or,  
near the 1:00 o’clock position (with the ODP disabled). If a high number of “nuisance  
transfers” caused by transients on the AC line occur, adjust the potentiometer from the  
maximum position toward the minimum position (i.e., 2 o’clock toward 5 o’clock with  
ODP enabled; or 1 o’clock toward 9 o’clock with ODP disabled).  
Table 3-3 ODP/AC Transfer Voltage  
ODP Adjustment  
AC Transfer Voltage  
220 to 230 Vac  
100 to 105 Vac  
(-J/-K Models)  
ODP Disabled  
9:00  
ODP Enabled  
120 Vac Models (-W /-E Models)  
30 Vac  
77 Vac  
81 Vac  
86 Vac  
90 Vac  
45 Vac  
85 Vac  
90 Vac  
95 Vac  
100 Vac  
90 Vac  
5:00  
170 Vac  
180 Vac  
190 Vac  
200 Vac  
Approximate  
Approximate  
Approximate  
Approximate  
Approximate  
Approximate  
Approximate  
Approximate  
95 Vac  
105 Vac  
210 Vac  
Approximate  
Approximate  
3–10  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Front Panel Controls and Indicators  
Maximum  
(105 Vac for 120 Vac models)  
AC Transfer Voltage (Adjustable)  
with ODP Disabled  
Maximum  
(105 Vac for 120 Vac models)  
Minimum  
AC Transfer Voltage (Adjustable)  
with ODP Enabled  
(45 Vac for 120 Vac models)  
Minimum  
(45 Vac for 120 Vac models)  
Figure 3-7 ODP Enabled/Disabled Positions  
Important: Most AC appliances will operate properly with an AC pass-through  
voltage between 95 and 105 volts. Setting the AC Transfer Voltage potentiometer between  
these values will allow the incoming source voltage to drop to this level and still operate  
the connected appliances (load). If the appliances do not operate properly at the lower AC  
utility pass-through voltage, increasing the setting of the potentiometer (toward MAX)  
allows the inverter to transfer to battery power (providing full AC output) during these  
periods.  
Important: When setting the AC Transfer Voltage potentiometer for generator  
applications, the setting may need to be lowered if high powered loads cause the generator  
voltage to momentarily drop.  
Typical Setting Range for Utility  
Application (ODP OFF)  
Typical Setting Range for Utility  
Application (ODP ON)  
Figure 3-8 Typical Setting for Most Utility Application  
975-0012-01-02 Rev A  
3–11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Battery Capacity  
The Battery Capacity potentiometer is used to set the correct charge profile for the  
battery capacity (amp-hours) used with the inverter (see illustration below). The  
setting allows the inverter to calculate over-discharge protection values and also  
the end of the Bulk/Absorption charge mode, at which point the inverter switches  
to the Float mode of battery charging.  
The potentiometer should be adjusted as close as possible to the actual capacity of  
the battery bank for optimum charging. If the system’s battery bank is larger than  
1000 amp-hours, set the potentiometer for 1K.  
Important: If using dual inverters configurations, set each charger for half the value.  
Important: Most battery manufacturers list the amp/hour rating on the battery label.  
1000 amp-hours  
50 amp-hours  
(1000 amp-hour or larger  
(small battery bank)  
battery banks)  
Figure 3-9 Battery Capacity Potentiometer (new)  
Important: The Battery Capacity (Amp/Hrs) potentiometer values have changed  
between the minimum value of 50 Ah and 1 kAh. Please use the photo that matches your  
unit.  
250 amp-hours  
125 amp-hours  
370 amp-hours  
500 amp-hours  
50 amp-hours  
(small battery bank)  
1000 amp-hours  
(1000 amp-hour or larger battery banks)  
Figure 3-10 Battery Capacity Potentiometer (old)  
3–12  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Front Panel Controls and Indicators  
LED Indicators  
There are four LEDs on the inverter’s front panel, indicating inverter status,  
battery condition, over temperature/overload conditions and charger status. These  
LEDs blink or change color depending on the condition or function they are  
displaying.  
OVER TEMP/OVERLOAD  
INVERTER  
MODE  
BATTERY HIGH/LOW  
BATTERY CHARGER  
Figure 3-11 LED Indicators  
Inverter Mode LED - Green  
The green Inverter Mode LED lights (solid) to indicate the inverter is running on  
batteries (full wave operation). When the inverter is in search mode (no load  
applied) the LED flashes 2 to 3 times per second. During AC line operation, with  
AC passing directly through to the connected load, the LED remains OFF.  
Over Temp / Overload LED - Red / Green (error condition)  
The Over Temp / Overload LED is a dual color, dual function indicator. When the  
inverter’s temperature is too high for safe operation, the LED lights (red) to  
indicate the Over Temp condition. When the temperature returns to a safe level,  
the LED turns OFF. If the condition persists, the inverter will shut down, cool and  
then restart.  
Whenever the current draw exceeds a value programmed into the micro-  
controller, the LED lights (green) to indicate the Overload condition. The LED  
can remain ON for up to one hour (before inverter shutdown) if the condition is  
caused by a fault in the charger circuit. When the fault condition clears, the LED  
turns OFF. If the condition is caused by backfeed (connecting the AC line to the  
inverter’s output) the LED will remain ON for approximately 10 seconds before  
the inverter shuts down.  
Battery High/Battery Low LED - Red/Green (error condition)  
The Battery Hi / Battery Low LED is a dual-color, dual-function indicator.  
Whenever battery voltage exceeds a safe value, the LED lights red to indicate the  
condition. This value is typically 15.5 volts DC for a 12 volt system (31 volts DC  
for a 24 volt system). If the condition persists, the inverter will shut down until the  
battery voltage returns to a safe level and then restart.  
975-0012-01-02 Rev A  
3–13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Important: In renewable energy applications (solar, wind, hydro, etc.) the DC charge  
controllers must be set to a level below the inverter’s maximum input voltage or the  
inverter shuts OFF.  
Whenever the battery voltage drops to its lowest (safe) level (as calculated by the  
ODP), the LED lights green to indicate the condition. If the condition persists, the  
inverter will shut down until the battery voltage returns to a safe level and then  
restart.  
Important: The inverter automatically restarts when the following error conditions are  
detected: LOW/HIGH BATTERY, OVER TEMPERATURE, or a quick duration  
SHORTED OUTPUT or OVER-CURRENT. The inverter shuts OFF and requires a  
MANUAL restart if the following conditions are detected: a prolonged overload condition  
(approximately 10 seconds) or the inverter’s output is connected directly to an AC power  
source (utility grid or generator).  
Charger LED - Orange / Green  
The Charger LED is a dual color (red/green), triple function indicator.  
When the charger is in Bulk mode, the LED lights orange.  
When the charger is in Absorption mode, the LED blinks orange.  
When the charger is in Float mode, the LED lights green.  
Important: Orange is a flickering mix of red and green. It can look different depending  
on the angle at which the LED is viewed. It should never be a solid red.  
Important: The battery charger control circuit operates from the battery voltage. If the  
battery voltage falls below 7 volts, the inverter/charger will not operate. The batteries  
must first be recharged using a stand-alone charger to bring the voltage up to a level where  
the inverter/charger can operate.  
Audible Indicator (internal)  
A buzzer is located on the control board as an audible alert to fault conditions such  
as Battery High/Battery Low, or Overload. Steady buzzing indicates an impending  
inverter shut down. A pulsing chirp indicates the inverter is temporarily off-line  
due to a fault condition (either within the inverter or related to the system).  
3–14  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Front Panel Controls and Indicators  
Circuit Breakers  
The DR Inverter contains two circuit breakers located on the right-hand side of the  
chassis, directly above the AC input terminal block. The pass-through AC input  
circuit breaker protects the AC wiring and connected load. The charger AC input  
circuit breaker protects the charger circuit. The breakers are rated for the  
maximum charge rate and pass-through current allowed according to the rating of  
the internal relay.  
Table 3-4 AC Pass-through Circuit Breakers  
Models  
DR15XX  
30 amps  
15 amps  
DR24XX  
30 amps  
15 amps  
DR36XX  
30 amps  
N/A  
120 Vac  
210-230 Vac  
Table 3-5 Battery Charger Circuit Breakers  
Models  
DR15XX  
20 amps  
8 amps  
DR24XX  
30 amps  
15 amps  
DR36XX  
30 amps  
N/A  
120 Vac  
210-230 Vac  
AC Pass-through  
Circuit Breaker  
Charger AC Input  
Circuit Breaker  
Figure 3-12 AC Pass-through and Charger AC Input Circuit Breakers  
975-0012-01-02 Rev A  
3–15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Start-up  
Once the inverter is properly connected to the batteries, AC source, and loads  
(using a sub-panel) the inverter is ready for operation. Recheck the controls and  
ensure they are in the proper position. Recheck all wiring and ensure it is correct.  
Starting the inverter:  
1. Apply DC power to the inverter by switching on the DC disconnect circuit  
breaker. The inverter will go through a self-test and then shut OFF.  
2. Press the ON/OFF button once. The inverter will sound an audible chirp.  
3. Apply AC power to the inverter.  
4. The inverter starts charging the batteries in the Bulk mode, indicated by the  
CHARGER LED illuminating a solid orange.  
5. Using a true RMS AC voltmeter, check the output voltage of the inverter. This  
voltage can be checked at either the AC terminal block or in the sub-panel  
(between the HOT and NEUTRAL lines). The voltage should be 120 Vac  
(230 Vac for “E” models, 220 Vac for “W” models, or 105 Vac for “J” and  
“K” models). (Non-true RMS meters register from 90 to 110 Vac.)  
6. Switch the AC disconnect circuit breaker to OFF. The inverter will go into the  
inverter mode (if a sufficient load is applied to the AC output while in the  
search mode). The green INVERTER MODE LED will light solid indicating  
the inverter is active. The voltage on the AC output of the inverter will remain  
the same as above (± 5% maximum).  
Important: If the inverter is in the SEARCH MODE (INVERTER MODE LED  
flashing) and a sufficient load is not available to bring the inverter up to full voltage, turn  
the SEARCH MODE WATTS potentiometer fully CCW to defeat the search function.  
7. Reapply the AC power by switching the AC disconnect to ON. Allow the  
batteries to fully recharge.  
POWER ON/OFF Switch  
INVERTER MODE LED  
Charger LED  
SEARCH MODE WATTS Potentiometer  
Figure 3-13 Startup Items  
Important: The unit will not use renewable energy for AC output as long as AC input  
(utility or generator) is available to the inverter.  
3–16  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Charger Mode  
Charger Mode  
3-Stage Charging Process  
The charging cycle uses a 3-stage charging process to maintain the batteries.  
Whenever nominal AC is present at the inverter’s input, it passes power through  
to the connected load and begins charging the batteries, indicated by the dual color  
BATTERY CHARGER LED.  
Bulk Charge  
Bulk charge is the first stage in the charging process and provides the batteries  
with a controlled, constant current. A solid orange BATTERY CHARGER LED  
indicates bulk charge. The bulk charge level is adjustable using the BATTERY  
CHARGER RATE potentiometer. Once the battery voltage rises to the bulk  
voltage threshold, the charger then switches to the absorption mode.  
Absorption Charge  
Absorption charge is the second stage of battery charging and provides the  
batteries a controlled, constant voltage for a set period of time. A blinking orange  
BATTERY CHARGER LED indicates absorption charge.  
During this stage the current supplied to the batteries slowly decreases. When the  
current equals the programmed return amps value (battery bank capacity/40) set  
with the BATTERY BANK CAPACITY potentiometer, the charger switches to  
the third stage–float.  
Important: If there are DC loads connected to the battery, the current may never  
decrease to the level to initiate the float stage. The inverter/charger incorporates a timer  
circuit which starts counting when AC voltage is applied. To ensure that the charger does  
not stay indefinitely in the absorption charge mode, the timer automatically switches to  
the float charge mode when 12 hours have elapsed.  
Float Charge  
Float charge, the final stage of battery charging, maintains a charge to the batteries  
whenever AC is present on the inverter’s input. A solid green BATTERY  
CHARGER LED indicates float charging which reduces battery gassing,  
minimizes watering requirements (for flooded batteries) and ensures the batteries  
are in a constant state of readiness.  
A new 3-stage charging cycle is initiated after an AC source is reapplied to the  
inverter’s AC input terminals such as after a utility outage.  
Important: The Float Charge is a very low-current charge, also called a “trickle-  
charge”. Some batteries may require higher current. Consult the battery manufacturer to  
determine if the batteries being used can handle a float charge. The inverter will adjust its  
charge rate to meet the battery requirement.  
975-0012-01-02 Rev A  
3–17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Battery Charger LED  
Solid Orange = Bulk  
Battery Capacity  
Blinking Orange = Absorption  
Solid Green = Float  
Figure 3-14 Charger Controls and Indicators  
Equalize Charging  
Equalize charging is a special mode of battery charging. During use, the battery’s  
cells can become unequal in the voltage and current they can deliver. This is due  
to a buildup of sulfate on the plates as well as stratified electrolyte. Sulfate  
prevents the cells from receiving or delivering full power. If the sulfate is left on  
the plates, it will harden, and permanently reduce the battery’s capacity.  
Stratification separates the heaver acid from the water, and the concentrated acid  
remains at the lower portion of the plates, eventually corroding them.  
Equalize charging holds the battery at the Equalize voltage for a minimum of  
6 hours. This stirs up the electrolyte, distributing the acid, and removing the  
sulfate from the plates. Equalizing the batteries every month or two (depending on  
usage) prolongs the life of the batteries and provides better battery performance.  
CAUTION: Explosion Hazard  
Only unsealed or vented batteries should be equalize charged. Since Hydrogen and  
oxygen gases are produced when equalized, provide adequate ventilation and remove all  
sources of ignition to prevent explosion. Remove DC loads while equalizing as they can  
be damaged by the higher battery voltage. Consult the battery manufacturer’s  
recommendation for equalize charging settings.  
To Set the Equalize Charge:  
1. Remove all DC loads connected to the batteries.  
2. Remove all battery vent caps.  
3. Check the battery water level, it should be just over the top of the plates (do  
not overfill). Use only distilled water for filling batteries.  
3–18  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Charger Mode  
Important: Recheck the water the level after equalize charging and refill if necessary.  
4. Set the BATTERY TYPE SELECTOR switch to position “0” or “1”. To start  
the equalization charging process, cycle the AC power (i.e., disconnect and  
then reconnect the AC source). A solid orange BATTERY CHARGER LED  
indicates equalize charge.  
a) Position “0” equalizes the batteries at the rate of the battery bank capacity  
divided by 40 (C/40) at a voltage of 15 volts for 12-volt systems or  
30 volts for 24-volt systems. This is set with the BATTERY CAPACITY  
potentiometer.  
b) Position “1” equalizes the batteries at the rate set with the BATTERY  
CHARGER RATE CONTROL at a voltage of 15.5 volts for 12-volt  
systems or 31 volts for 24-volt systems.  
When the voltage condition is met and 6 hours have elapsed, the charger will  
switch to the float mode. If the condition is not met (i.e., the current draw is  
above the rate set with the BATTERY CAPACITY potentiometer (position  
“0”) or BATTERY CHARGER RATE potentiometer (position “1”)), the  
charger will continue until the condition is met, or for a maximum of  
12 hours. At this point the charger switches to float at the equalize 1 or 2  
voltage setting (see Figure 3-1, “Battery Type Selector Switch Settings” on  
page 3–5).  
5. Reset the BATTERY TYPE SELECTOR potentiometer to the appropriate  
setting for the system’s batteries when the Equalize charge has completed.  
Important: Refer to “Battery Maintenance” on page B–13 for additional information.  
Equalize 1  
Equalize 2  
Figure 3-15 Equalize Positions on Battery Type Selector Switch  
975-0012-01-02 Rev A  
3–19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
See Table 3-1 Switch Position “1”.  
Figure 3-16 Equalize 1 Battery Charger Rate Potentiometer (Position “1”)  
See Table 3-1 Switch Position “0”.  
Figure 3-17 Equalize 2 Battery Capacity Rate Potentiometer (Position “0”)  
3–20  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
4
Chapter 4, “Troubleshooting” contains information about how to  
troubleshoot possible error conditions while using the DR  
Inverter/Charger.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Troubleshooting the DR Inverter  
Table 4-1 provides a list of possible error conditions that may occur, their possible  
causes, and possible solutions to resolve the error condition.  
Table 4-1 Troubleshooting the DR Inverter  
Error Condition  
Possible Cause  
Solution  
No AC output voltage and no  
warning LEDs on ON.  
Battery voltage at the inverter  
terminals is too high or low.  
Check the battery voltage, fuses or  
breakers, and cable connections.  
AC output voltage is low and the  
inverter turns loads ON and OFF.  
Low Battery.  
Check the condition of the batteries  
and recharge if possible.  
Replace the batteries.  
AC output is low.  
Loose or corroded battery  
connections.  
Check and clean all DC connections.  
Loose AC output connections.  
Wrong voltmeter is being used.  
Check all AC output connections.  
Use a True RMS voltmeter.  
Charger is inoperative.  
AC voltage has dropped  
out-of-tolerance  
Check the AC voltage for proper  
voltage and frequency (depending on  
model).  
Loose AC input connections.  
Check all AC output wiring  
connections  
Charger is supplying a lower charge Charger controls are improperly set.  
rate.  
Refer to the section on adjusting the  
“Charger Rate”.  
Low peak AC input voltage (169 Vac Use larger generator (increasing AC  
p
voltage/RPM’s may help).  
required for full charger output)  
Check and clean all DC connections.  
Loose or corroded battery  
connections.  
Check all AC output wiring  
connections.  
Loose AC input connections.  
Turn BATTERY CHARGER RATE  
potentiometer down to less than  
halfway until problem is gone.  
Generator is unstable - charger is  
losing synchronization.  
AC LEDs flicker while charging.  
Generator is unstable and charger is  
losing synchronization.  
Turn BATTERY CHARGER RATE  
potentiometer down to less than  
halfway until problem is gone.  
4–2  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Problem Loads  
Table 4-1 Troubleshooting the DR Inverter  
Error Condition  
Possible Cause  
Solution  
CHARGER LED:  
- indicates charging, but no charge  
is going to the batteries.  
Circuit Breaker on the side of the  
inverter is open.  
Reset the AC CHARGER circuit  
breaker on the side of the unit.  
- is ON, but there is no output  
power.  
No AC voltage on inverter’s AC  
terminal block.  
Check “AC PASS-THRU” Circuit  
Breaker on the side of the inverter.  
Good AC voltage on inverter’s AC  
terminal block.  
Check for open AC output breakers  
or uses and AC wiring connections.  
Charger turns OFF while charging  
from a generator  
High peak AC input voltages from the Load the generator down with a  
generator  
heavy load.  
Turn the generator output voltage  
down.  
Problem Loads  
The inverter can drive most loads, however, there are special conditions that can  
cause a load to behave differently than expected. The following describes some of  
the common problems encountered when using an inverter.  
Ceiling Fans  
Cell Phones  
Most large diameter, slow turning fans run correctly, but generate more noise than  
when connected to utility power. High speed fans tend to operate normally.  
Some cellular telephones experience interference in the form of a clicking sound.  
Computers and Sensitive Electronics  
Some computers and sophisticated electronics have power supplies that do not  
present a load until correct line voltage is available. When this occurs, each unit  
waits for the other to begin. This can usually be solved by plugging in an  
additional load (such as a lamp) to bring the inverter out of its search mode. Also,  
when using a computer, avoid starting large loads.  
Consumer Electronics  
AM radios tend to pick up inverter noise, especially on the lower half of their  
band. Inexpensive tape recorders are likely to experience noise as well. When  
using sensitive electronic devices, avoid starting large loads.  
975-0012-01-02 Rev A  
4–3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Clocks  
The inverter’s crystal controlled oscillator keeps the frequency accurate to within  
a few seconds a day; however, external loads in the system may alter the inverter’s  
output waveform causing clocks to run at different speeds. There may be periods  
where clocks keep time and then mysteriously do not. This is because most clocks  
do not draw enough power to trigger the load sensing circuit. In order to operate,  
especially with no other loads present, the inverter’s load sensing circuit will have  
to be defeated. Refer to the Operation/Search Mode Watts.  
Decreasing Loads  
If the amount of power a load draws decreases after it has been switched on (such  
as with a small motor) and its current draw becomes less than the load sensing  
threshold, it will be turned alternately ON and OFF by the inverter. This can  
usually be solved by plugging in an additional load (such as a lamp).  
Dimmer Switches  
Most dimmer switches lose their ability to dim the lights when used with an  
inverter and operate only in the fully ON or OFF position. Newer, microprocessor  
controlled dimmers tend to work better in inverter applications.  
Fluorescent Lights  
Some devices cannot be detected by the inverter’s load sensor and will not  
operate. Small fluorescent lights are the most common example. This can usually  
be solved by plugging in an additional load. Also, try turning the lamps AC plug  
over.  
Heavy Loads  
If the battery bank cannot deliver the necessary amperage to drive a heavy load,  
the inverter will shut OFF. The battery voltage will then slowly rise back above  
the low voltage threshold causing the inverter to resume operation. As soon as the  
heavy load draws the batteries down, the cycle will continue unless the load is  
reduced or an additional source of power is added.  
Microwave Ovens  
Microwave ovens are sensitive to peak output voltages. The higher the voltage,  
the faster they cook. Since the inverter’s peak output voltage is dependent upon  
battery voltage and load size, the microwave’s cook time may need to be  
increased.  
4–4  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Problem Loads  
Printers  
Most inkjet type printers work well in inverter applications. Laser printers,  
however, require high current for their fusing circuit and are not recommended for  
use with an inverter.  
Rechargeable Devices  
When first using a rechargeable device, monitor its temperature for 10 minutes to  
ensure it does not become abnormally hot. Excessive heat will indicate that it is  
incompatible with the inverter.  
Undersized Loads  
If the power consumed by a device is less than the inverter’s search mode circuitry  
threshold, it will not run. This can usually be solved by plugging in an additional  
load such as a 100 watt light bulb.  
CAUTION: Equipment Damage  
Some products can be damaged when used with modified sine-wave power. If in doubt,  
check with the product’s manufacturer.  
975-0012-01-02 Rev A  
4–5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4–6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
A
Appendix A, “Specifications” contains information about the  
electrical specifications and environmental specifications of the DR  
Inverter/Charger.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Specifications of the DR Inverter  
Table A-1 provides the electrical specifications for the DR Inverter/Charger  
(120 Vac/60 Hz. models).  
Table A-2 provides the electrical specifications for the DR Inverter/Charger  
(220 Vac/60 Hz. models).  
Table A-3 provides the electrical specifications for the DR Inverter/Charger  
(230 Vac/50 Hz. models).  
Table A-4 provides the environmental specifications for all models of the DR  
Inverter/Charger.  
Table A-1 Electrical Specifications for the DR Inverter/Chargera - 120 Vac/60 Hz Models  
Model  
DR1512  
120 Vac  
DR2412  
120 Vac  
DR1524  
120 Vac  
DR2424  
120 Vac  
DR3624  
120 Vac  
AC Input Voltage  
AC Input Low  
40-105 Vac  
40-105 Vac  
40-105 Vac  
40-105 Vac  
40-105 Vac  
Transfer Voltage  
b
45 amps  
55 amps  
2400 VA  
45 amps  
1500 VA  
55 amps  
2400 VA  
55 amps  
3600 VA  
AC Input Current  
Continuous Power 1500 VA  
(@ 25°C)  
Continuous Output 12.5 amps AC  
(@25 °C)  
20 amps AC  
12.5 amps AC  
20 amps AC  
30 amps AC  
Efficiency  
94% max  
94% max  
120 Vac  
94% max  
120 Vac  
95% max  
120 Vac  
95% max  
120 Vac  
AC Output Voltage 120 Vac  
(rms)  
Frequency:  
60 Hz  
60 Hz  
60 Hz  
60 Hz  
60 Hz  
(± 0.04% Crystal  
controlled)  
Surge Capability:  
5 sec Rating 2400 watts  
1 mSec Rating 38 amps AC  
100 mSec Rating 27 amps AC  
DC Input Current:  
4200 watts  
77 amps AC  
55 amps AC  
3500 watts  
6200 watts  
80 amps AC  
58 amps AC  
7500 watts  
412 amps AC  
29 amps AC  
100 amps AC  
72 Amps AC  
Search Mode  
Full Voltage  
0.045 amps  
0.700 amps  
165 amps  
0.055 amps  
0.900 amps  
280 amps  
0.030 amps  
0.350 amps  
80 amps  
0.030 amps  
0.450 amps  
140 amps  
0.030 amps  
0.500 amps  
210 amps  
DC Current at  
Rated Power  
Short Circuit  
Current  
400 amps  
800 amps  
280 amps  
560 amps  
720 amps  
A–2  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications of the DR Inverter  
Table A-1 Electrical Specifications for the DR Inverter/Chargera - 120 Vac/60 Hz Models  
Model  
DR1512  
DR2412  
DR1524  
DR2424  
DR3624  
DC Input Voltage  
12.6 Vdc  
12.6 Vdc  
25.2 Vdc  
25.2 Vdc  
25.2 Vdc  
c
(nominal)  
DC Input Voltage  
Range  
10.8 to 15.5 Vdc 10.8 to 15.5 Vdc 21.6 to 31.0 Vdc 21.6 to 31.0 Vdc 21.6 to 31.0 Vdc  
Auto Low Battery 11 V  
Protection enabled  
11 V  
22 V  
22 V  
22 V  
DC Charger Rate  
(Adjustable)  
0 to 70 amps  
0 to 120 amps  
0 to 35 amps  
0 to 70 amps  
0 to 70 amps  
Common Specifications:  
Voltage Regulation ± 5%  
(maximum)  
Voltage Regulation ±2. 5%  
(Typical)  
Waveform  
modified sine wave  
Load Power Factor 0.5 to 1.0 (leading or lagging)  
(allowed)  
Adjustable Load  
Sensing Range  
5 watts minimum to 100 watts maximum  
Series Operation  
Yes  
Force Air Cooling Variable speed fan  
AutomaticTransfer 30 amps  
Relay  
Number of  
10  
Charging Profiles  
Three-stage  
Charging  
Yes (float, absorption, bulk)  
Temperature Comp optional  
Probe (BTS)  
Remote Control  
optional  
d
(RC8)  
a.Specifications subject to change without notice.  
b.This is the minimum AC current required to obtain full pass-through and maximum battery charging.  
c.Product may not meet voltage regulation specifications at other than "Input Nominal" at full-rated load.  
d.Also compatible with the RC4.  
975-0012-01-02 Rev A  
A–3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Table A-2 Electrical Specifications for the DR Inverter/Chargersa - 220 Vac/60 Hz Models  
Model  
DR1512W  
220 Vac  
DR2412W  
220 Vac  
AC Input Voltage  
AC Input Low Transfer Voltage  
80 to 210 Vac  
45 amps  
80 to 210 Vac  
55 amps  
b
AC Input Current  
Continuous Power (@ 25°C)  
Continuous Output (@25 °C)  
Efficiency  
1500 VA  
2400 VA  
6.8 amps AC  
94% max  
220 Vac  
6.8 amps AC  
94% max  
220 Vac  
AC Output Voltage (rms)  
Frequency: (± 0.04% Crystal controlled) 60 Hz.  
Surge Capability:  
60 Hz.  
1 mSec Rating  
DC Input Current:  
Search Mode  
20 amps AC  
20 amps AC  
0.045 amps  
0.700 amps  
150 amps  
400 amps  
12.6 Vdc  
0.055 amps  
0.900 amps  
80 amps  
Full Voltage  
DC Current at Rated Power  
Short Circuit Current  
800 amps  
12.6 Vdc  
c
DC Input Voltage (nominal)  
DC Input Voltage Range  
10.8 to 15.5 Vdc  
11 V  
10.8 to 15.5 Vdc  
11 V  
Auto Low Battery Protection enabled  
Charger Rate (Adjustable)  
Common Specifications:  
Voltage Regulation (maximum)  
Voltage Regulation (Typical)  
Waveform  
0 to 70 amps  
0 to 120 amps  
± 5%  
±2. 5%  
modified sine wave  
0.5 to 1.0 (leading or lagging)  
Load Power Factor (allowed)  
Adjustable Load Sensing Range  
Series Operation  
5 watts minimum to 100 watts maximum  
NO  
Force Air Cooling  
Variable speed fan  
Automatic Transfer Relay  
Number of Charging Profiles  
Three-stage Charging  
20 amps  
10  
Yes (float, absorption, bulk)  
A–4  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications of the DR Inverter  
Table A-2 Electrical Specifications for the DR Inverter/Chargersa - 220 Vac/60 Hz Models  
Model  
DR1512W  
optional  
DR2412W  
Temperature Comp Probe (BTS)  
d
optional  
Remote Control (RC8)  
a.Specifications subject to change without notice.  
b.This is the minimum AC current required to obtain full pass-through and maximum battery charging.  
c.Product may not meet voltage regulation specifications at other than "Input Nominal" at full-rated load.  
d.Also compatible with the RC4.  
Table A-3 Electrical Specifications for the DR Inverter/Chargera - 230 Vac/50 Hz Models  
Model  
DR1512E  
DR1524E  
230 Vac  
DR1548E  
230 Vac  
DR2424E  
230 Vac  
AC Input Voltage  
230 Vac  
AC Input Low Transfer 80 to 210 Vac  
Voltage  
80 to 210 Vac  
80 to 210 Vac  
80 to 210 Vac  
b
55 amps  
1500 VA  
55 amps  
1500 VA  
55 amps  
1500 VA  
55 amps  
2400 VA  
AC Input Current  
Continuous Power  
(@ 25°C)  
Continuous Output  
(@25 °C)  
12.5 amps AC  
20 amps AC  
12.5 amps AC  
20 amps AC  
Efficiency  
94% max  
230 Vac  
94% max  
230 Vac  
94% max  
230 Vac  
95% max  
230 Vac  
AC Output Voltage  
(rms)  
Surge Capability:  
1 mSec Rating 20 amps AC  
DC Input Current:  
20 amps AC  
20 amps AC  
40 amps AC  
Search Mode  
Full Voltage  
0.045 amps  
0.700 amps  
165 amps  
0.055 amps  
0.900 amps  
280 amps  
0.030 amps  
0.350 amps  
80 amps  
0.030 amps  
0.450 amps  
140 amps  
DC Current at Rated  
Power  
Short Circuit Current  
DC Input Voltage  
400 amps  
12.6 Vdc  
800 amps  
25.2 Vdc  
280 amps  
50.4 Vdc  
560 amps  
25.2 Vdc  
c
(nominal)  
DC Input Voltage  
Range  
10.9 to 15.5 Vdc  
21.8 to 31 Vdc  
43.6 to 62 Vdc  
21.8 to 31 Vdc  
975-0012-01-02 Rev A  
A–5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Table A-3 Electrical Specifications for the DR Inverter/Chargera - 230 Vac/50 Hz Models  
Model  
DR1512E  
DR1524E  
DR1548E  
DR2424E  
Auto Low Battery  
Protection enabled  
11 V  
11 V  
22 V  
22 V  
DC Charger Rate  
(Adjustable)  
0 to 70 amps  
0 to 35 amps  
0 to 17.5 amps  
0 to 70 amps  
Common Specifications:  
Voltage Regulation  
(maximum)  
± 5%  
Voltage Regulation  
(Typical)  
±2. 5%  
Waveform  
modified sine wave  
Load Power Factor  
(allowed)  
0.5 to 1.0 (leading or lagging)  
Adjustable Load  
Sensing Range  
5 watts minimum to 100 watts maximum  
Series Operation  
Force Air Cooling  
NO  
Variable speed fan  
20 amps  
Automatic Transfer  
Relay  
Number of Charging  
Profiles  
10  
Three-stage Charging  
Yes (float, absorption, bulk)  
optional  
Temperature Comp  
Probe (BTS)  
d
optional  
Remote Control (RC8)  
a.Specifications subject to change without notice.  
b.This is the minimum AC current required to obtain full pass-through and maximum battery charging.  
c.Product may not meet voltage regulation specifications at other than "Input Nominal" at full-rated load.  
d.Also compatible with the RC4.  
A–6  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications of the DR Inverter  
Table A-4 Environmental Specifications for the DR Inverter/Chargera  
Model  
DR1512  
DR2412  
DR1524  
DR2424  
DR3624  
b
8.5" w x 7.25" H x 21" D (21.6 cm W x 18.4 cm H x 54.6 cm D  
Dimensions  
Unit Weight  
“E” Models  
35 lbs (16 kg)  
38 lbs (18 kg)  
45 lbs (21 kg)  
N/A  
35 lbs (16 kg)  
39 lbs (18 kg)  
40 lbs (16 kg)  
(45 lbs (21 kg)  
45 lbs (21 kg)  
N/A  
Ambient Temp Range (rated 0 to 25 °C):  
Operating 0 °C to +50 °C  
Storage -55 °C to +75 °C  
Altitude:  
Operating  
15,000 feet  
50,000 feet  
Non-operating  
Mounting  
Wall-mount (with 16" mounting centers)  
Shelf Mount  
a.Specifications subject to change without notice.  
b.Allows for hardware extensions such as mounting rails, DC terminals, and front panel controls.  
975-0012-01-02 Rev A  
A–7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A–8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Information  
B
Appendix B, “Battery Information” supplies general information  
about batteries such as battery types, battery bank sizing, battery  
configurations, and battery care. For detailed information, see your  
battery manufacturer or your system designer.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Information  
Introduction  
Batteries  
Batteries are available in different sizes, amp-hour ratings, voltage, liquid or gel,  
vented or non-vented, chemistries, etc. They are also available for starting  
applications (such as an automobile starting battery) and deep discharge  
applications.  
Recommendations  
Consider the following recommendations for battery use.  
Use only the deep discharge types for inverter applications.  
Use the same battery type for all batteries in the bank.  
Use only batteries from the same lot and date in your battery bank. This  
information is usually printed on a label located on the battery.  
Battery Types  
There are two principal types of batteries: starting and deep-discharge (with  
several different types of chemistries). Batteries can be either sealed or non-sealed  
(vented).  
Deep discharge  
Starting  
The battery types recommended for use in an inverter system are: Flooded Lead  
Acid (FLA), Sealed Gel Cells (GEL), Sealed Absorbed Glass Mat (AGM); and  
alkaline types Nickel-iron (NiFe) and Nickel-Cadmium (NiCad).  
Automotive (starting) batteries are designed to provide high starting current for  
short periods of time and are not appropriate for inverter applications.  
Deep-cycle Flooded Lead Acid (FLA)  
Description  
A flooded lead acid battery is designed to be deep-discharged before being  
recharged, making it suitable for inverter applications. Flooded batteries require  
periodic maintenance consisting mainly of adding distilled water to the cells.  
Attributes  
Types of FLA Batteries  
Attributes  
Golf Cart  
Popular for smaller off-grid home  
systems  
Many medium sized inverter  
systems use “L16” batteries  
Rugged, long lasting  
Typically rated at 6 volts  
(220 to 350 amp hours)  
Industrial (electric forklift)  
Popular in large inverter systems  
Extremely rugged - lasts up to 10  
years or more in an inverter system  
Typically 2 volt cells  
(1,000 amp hours or more)  
B–2  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Types  
Sealed Batteries (Gel and AGM)  
Description  
Gel Cell and absorbed glass mat (AGM) batteries are sealed and do not require the  
addition of distilled water. Since these batteries are valve regulated, over-charging  
can cause irreversible damage.  
Attributes  
Attributes of sealed batteries are:  
Types of Sealed Batteries  
Attributes  
Gel Cell  
Gelled electrolyte instead of  
liquid  
Long life (up to 1500 cycles,  
typical)  
Low self-discharge  
Absorbed Glass Mat  
Electrolyte is contained in  
glass-fibre mats between battery  
plates  
Similar to gel cells in  
characteristics  
Good low temperature  
performance  
NiCad and NiFe Batteries  
Disadvantages  
These types of batteries can be used but are not optimized for the DR Inverter for  
the following reasons:  
Alkaline batteries, such as NiCad and NiFe types, have a nominal cell voltage  
of 1.2 volts per cell.  
Xantrex inverters and battery chargers are optimized for use with lead acid  
batteries having a nominal 2.0 volts per cell (that is, 12 cells for a 24-volt  
system and 24 cells for a 48-volt system).  
The number of cells required in a battery bank for alkaline batteries must,  
therefore, be adjusted for a 24- and 48-volt system  
(i.e, 20 cells for a 24-volt system and 40 cells for a 48-volt system).  
Alkaline batteries require a higher charge voltage to fully recharge, and drop  
to a lower voltage during discharge compared to a similarly sized lead-acid  
type battery.  
Other options  
Another option for 24 volt (only) alkaline battery banks is to use only 19 cells  
instead of 20. Fewer cells allow the battery charger to operate more closely to the  
settings used for lead-acid batteries. However, the battery voltage will drop to as  
low as 18 volts when discharging the batteries.  
Consult the battery manufacturer or supplier regarding system requirements and  
battery charger settings for alkaline type batteries.  
975-0012-01-02 Rev A  
B–3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Information  
Understanding Battery Capacity Ratings  
Discharge rate  
Deep cycle batteries have their amp-hour rating expressed as “at the x-hour rate”.  
The hour rating refers to the time it takes to discharge the batteries. A faster hour  
rate (6 hour rate) means more current is withdrawn from the batteries during their  
discharge period. There is an inevitable amount of heat associated with the flow of  
current through a battery and the higher amount of current the greater the amount  
of heat will be generated. The heat is energy which is no longer available to the  
battery to power loads. a relatively long discharge rate (72 hour rate) will result in  
a larger number of amp-hours being available for electrical loads.  
Calculation  
This calculation shows how to determine the level of current drawn from a battery  
at any given hour rate—battery capacity divided by the hour rate equals the  
current drawn from the battery. For example, a battery rated 220 Ah at a 6 hour  
rate would be discharged at 36 amps (220/6).  
For most residential applications of the DR Inverter the 72 hour rate is appropriate  
because on average a household uses low amounts of current (lights, TV, radio for  
example) with occasional bursts or higher consumption appliances like toasters or  
washing machines. For those installations where high continuous electrical  
consumption rates are anticipated it is more appropriate to use the 20 hour rate.  
CCA rating  
The CCA rating (cold cranking amps) shown on starting batteries expresses  
battery capacity in terms of its ability to provide large amounts of current for  
intervals measured in minutes, not hours. This is why starting batteries are not  
appropriate for inverter systems.  
Battery Bank Sizing  
Running time and  
size  
The battery bank’s size determines the length of time the inverter can supply AC  
output power. The larger the bank, the longer the inverter can run.  
Depth of discharge  
In general, the battery bank should be designed so the batteries do not discharge  
more than 60% of their capacity on a regular basis. Discharging up to 80% is  
acceptable on a limited basis, such as a prolonged utility outage. Totally  
discharging a battery can reduce its effective life or permanently damage it.  
Days of autonomy  
For off-grid, stand-alone applications, design a battery bank that can power the  
loads for three to five days without requiring recharging. This design calculation  
assumes a worst case scenario where there is no recharging taking place during  
these days of autonomy.  
Days of autonomy may vary depending upon the availability of other charging  
sources, the critical nature of the load and other factors. If the system is to be  
powered by renewable energy sources such as solar, wind, and micro-hydro,  
determine the appropriate number of days of autonomy by allowing for cloudy or  
calm weather as well as other seasonal variations in available energy.  
If an engine generator is part of the system design, the days of autonomy can be  
determined by simply deciding how often you are prepared to run the generator.  
Significant battery cost reductions can be achieved by shortening the days of  
autonomy and allowing a generator to run for a schedule time period daily.  
B–4  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Bank Sizing  
Back up power systems which use utility power for recharging should use the  
estimated number of days of maximum power outage for determining days of  
autonomy.  
Understanding Amp-hour Requirements  
Amp-hours  
To estimate the battery bank requirements, you must first calculate the amount of  
power you will draw from the batteries during your period of autonomy. This  
power draw is then translated into amp hours (Ah)—the unit of measure to  
express deep-cycle battery capacity.  
Amp hours are calculated multiplying the current drawn by the load by the length  
of time it will operate.  
Watts to amps  
To calculate amps when the power consumption is expressed in watts, use the  
following equation:  
A = W/V  
where W = watts and V = volts DC  
For example:  
A 100 watt light bulb will draw approximately 8.33 amps  
8.33 = 100 /12  
If the light runs for three hours it will consume (8.33 x 3) or 25 Ah of power.  
Time and power  
The length of time a load is operated will affect the power draw. In some cases, an  
appliance which draws a large wattage may not consume as many amp hours as a  
load drawing fewer watts but running for a longer period of time.  
For Example:  
A circular saw draws 1500 watts or 125 amps. It takes 5 seconds to complete  
a cross cut. Twelve such cuts would take a minute and you would consume 125  
A x 0.016* hour = 2 Ah  
*1/60 = 0.016  
Observation The circular saw, while it draws more power, consumed fewer  
amp hours of electricity because it ran for a short period of time.  
Calculating Amp Hours  
Calculations  
To determine the amp hours you will consume, you need to list your anticipated  
loads and the length of time you will operate each one. Determine the number of  
hours per day and the number of days during the week you will use the appliance.  
For example, you use the microwave every day, but a breadmaker only once a  
week. If you use an appliance for less than an hour, express the time as a decimal  
portion of an hour.  
Amps to watts  
All electrical appliances have labels which state their energy consumption. Look  
for an amps rating on motors and a watts rating on other appliances.  
If the label plate has expressed power consumption in amps, multiply by volts for  
the watts required. (watts = volts x amps).  
975-0012-01-02 Rev A  
B–5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Information  
Considerations  
When calculating battery bank size, consider the following:  
Motors typically require 3 to 6 times their running current when starting.  
Check the manufacturer’s data sheets for their starting current requirements.  
If you will be starting large motors from the inverter, increase the battery bank  
size to allow for the higher start-up current.  
Refrigerators and ice-makers typically run only about 1/3 of the time,  
therefore, the running wattage is 1/3 of the total wattage of the appliance.  
Divide the total wattage of the appliance by 3 when determining the battery  
requirements.  
Amp Hour Example Worksheet  
Complete the following steps to calculate the amp-hour requirements per day for  
your system. Use and Table B-2 as examples to complete your own.  
To calculate amp-hour requirements:  
1. Determine the loads the inverter will power and enter their wattage in the  
watts column.  
2. Determine the number of hours (or decimal portion of hours) the appliance is  
used each day. Enter this figure in the Hours column.  
3. Determine the number of days the appliance will be used during the week.  
Enter this figure in the Days column.  
4. Multiply Hours x Days for each load identified to determine the watt/hours  
per week.  
5. Add the total watt/hours per week for all loads then divide by 7 to obtain the  
average total watt/hours per day.  
6. Divide the total average per day by the DC nominal voltage.  
This figure represents the average amp-hours per day that you will use.  
Table B-1 Determining Average Daily Load in Amp-hours (Example  
Days per  
Hours per Day week used  
Weekly  
watt-hours  
Load  
Watts  
75 W  
5 lights: 15 W CFL  
Breadmaker  
5
7
2
2625  
1800  
1200  
0.75  
24  
Energy-efficient  
refrigerator  
200 x 0.3  
10080  
Laptop computer  
50  
6
5
1500  
Total weekly watt-hours of AC load  
Divided by days per week  
16005 Wh  
7
2286  
24  
Average total watt-hours per day  
Divided by DC nominal voltage  
Average amp-hours per day (Ah/d)  
95  
B–6  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Bank Sizing  
Battery bank size worksheet  
Calculation  
To calculate the battery bank size, use the average amp-hours per day that you  
calculated using Table B-1, then make the other calculation shown in Table B-2 to  
calculate the battery bank size you need to support your loads.  
Table B-2 Determining Battery Bank Size  
Average amp hours per day  
95  
Divided by inverter efficiency (90%) for DR Inverter  
Divided by battery efficiency (usually 0.75)  
Adjusted hours per day  
0.9  
0.75  
140  
0.6  
Divided by Depth of Discharge (usually 60%)  
Multiplied by days of autonomy  
5
Battery bank size required  
1173 Ah  
Worksheets  
Table B-1 and Table B-2 are examples only. Use the specifications noted on the  
label of each AC appliance and fill in the values specific for the appliances used in  
this installation on the a work sheet.  
Table B-3 provides a typical wattage for selected appliances. However, you  
should try to find the exact wattage on the appliance label.  
Table B-3 Typical Appliance Wattage  
Appliance  
Watts  
Appliance  
Blender  
Watts  
400  
Fluorescent Type Light 10  
Computer  
200-300  
Toaster  
1000  
1800  
Microwave (compact)  
Microwave (full-size)  
Stereo or VCR  
600-800  
1500  
50  
Hot Plate  
Washer/Dryer  
3/8" Drill  
375-1000  
500  
Color Television (19")  
Refrigerator (3 cu ft)  
Refrigerator (12 cu ft)  
150  
Hair Dryer or Iron  
Vacuum Cleaner  
Coffee Maker  
1000  
180  
1200  
480  
1200  
975-0012-01-02 Rev A  
B–7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Information  
Battery Configurations  
The battery bank must be wired to match the inverter’s DC input voltage  
specifications (12 or 24 Vdc). In addition, the batteries can be wired to provide  
additional run time. The various wiring configurations are:  
Series  
Wiring batteries in series increases the total bank output voltage. This voltage  
MUST match the DC requirements of the inverter or inverter and/or battery  
damage may occur.  
Parallel  
Wiring the batteries in parallel increases the total run time the batteries can  
operate the AC loads. The more batteries connected in parallel the longer the  
loads can be powered from the inverter.  
Series-Parallel  
Series-parallel configurations increase both the battery voltage (to match the  
inverter’s DC requirements) and run-time for operating the AC loads. This voltage  
must match the DC requirements of the inverter.  
Batteries with more than two or three series strings in parallel often exhibit poor  
performance characteristics and shortened life.  
Wiring Batteries in Series  
Effect  
Wiring the batteries in a series configuration increases the voltage of the battery  
string. Six-volt batteries can be combined to form 12-volt, 24-volt, or 48-volt  
battery banks. In the same way, 12-volt batteries connected in series form 24-volt  
battery banks. The total current capacity of the bank does not increase and  
remains the same amp-hour rating as it does for a single battery.  
Important  
The voltage must match the DC requirements of the inverter.  
Each battery’s amp-hour  
Each battery's amp-hour  
rating is 100 Ah.  
rating is 100 Ah.  
+
-
+
-
+
-
+
-
+
-
+
-
6 V  
6 V  
6 V  
6 V  
6 V  
6 V  
SHUNT  
SHUNT  
DC Disconnect  
(either a circuit  
breaker or a  
fuse with a  
DC Disconnect  
(either a circuit  
breaker or a  
fuse with a  
+
-
+
-
disconnect)  
12 V INVERTER  
(Total battery capacity = 100 Ah)  
24 V INVERTER  
(Total battery capacity = 100 Ah)  
disconnect)  
Figure B-1 6-volt Battery Wiring - “Series” Configuration  
B–8  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Configurations  
Each battery's  
amp-hour rating  
is 100 Ah.  
+
-
+
-
-
12 V  
12 V  
SHUNT  
DC Disconnect  
(either a circuit  
breaker or a  
fuse with a  
+
disconnect)  
24 V INVERTER  
(Total battery capacity = 100 Ah)  
Figure B-2 12-volt Battery Wiring - “Series” Configuration  
Wiring Batteries in Parallel  
Effect  
Wiring the batteries in a parallel configuration increases the current of the battery  
string. The voltage of the battery bank remains the same as an individual battery.  
“Parallel” configurations extend the run times of the AC loads by providing  
increased current for the inverter to draw from. In a parallel configuration, all the  
negative battery terminals are connected together and all the positive battery  
terminals are connected together.  
Wiring example  
Figure B-3 is an example of how to wire batteries in a parallel configuration.  
Each battery's  
amp-hour rating  
is 100 Ah.  
+
-
+
-
12 V  
12 V  
SHUNT  
DC Disconnect  
(either a circuit  
breaker or a  
fuse with a  
+
-
disconnect)  
12 V INVERTER  
(Total battery capacity = 200 Ah)  
Figure B-3 Battery Wiring in Parallel  
975-0012-01-02 Rev A  
B–9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Information  
Wiring Batteries in Series-Parallel  
Effect  
Wiring the batteries in a series-parallel configuration increases the current and  
voltage of the battery bank. “Series-parallel” wiring is more complicated and care  
should be taken when wiring these banks.  
Steps  
It is done in three steps; wiring the batteries in series, wiring them in parallel, then  
wiring the string to the inverter.  
Series wiring  
To wire in series:  
1. First wire the batteries in “series” (voltage adds) with the positive terminal of  
one battery connected to the negative terminal of the next battery to meet the  
inverter’s DC input requirements (24 volts shown in Figure B-4 and Figure  
B-5.)  
2. Repeat this step for the next battery string.  
Two identical strings of batteries are now wired in series.  
+
+
+
+
+
+
+
Series String 1  
6 V  
6 V  
6 V  
6 V  
Each battery's amp-hour  
rating is 100 Ah.  
+
Series String 2  
6 V  
6 V  
6 V  
6 V  
Figure B-4 Battery Wiring 24-volt - Parallel Configuration - Step 1  
Parallel wiring  
To wire the batteries in parallel:  
1. Connect the positive terminal of the first battery string to the positive terminal  
of the second battery string.  
2. Connect the negative terminal of the first battery string to the negative  
terminal of the second battery string.  
Each battery's amp-hour  
rating is 100 Ah.  
+
+
+
+
+
+
+
+
Series String 1  
6 V  
6 V  
6 V  
6 V  
Parallel  
Connection  
Parallel  
Connection  
Series String 2  
6 V  
6 V  
6 V  
6 V  
Figure B-5 Battery Wiring 24-volt - Parallel Configuration - Step 2  
B–10  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Configurations  
Connect to inverter  
To connect to the inverter:  
1. Connect a cable from the positive terminal of the first battery string to the  
inverter’s positive DC terminal (via a fused device).  
2. Connect the negative terminal of the last battery string to the negative  
terminal of inverter’s DC terminal.  
Connection from Series String 1  
to inverter's positive (+) terminal  
+
+
+
+
+
+
+
Series String 1  
6 V  
6 V  
6 V  
6 V  
Each battery's amp-hour  
rating is 100 Ah.  
+
Series String 2  
6 V  
6 V  
6 V  
6 V  
SHUNT  
DC Disconnect (can be  
either a circuit breaker or a  
fuse with a disconnect)  
Connection from Series String 2 to  
inverter's negative (–) terminal  
+
24 V INVERTER  
(Total battery capacity = 200 Ah)  
Figure B-6 Battery Wiring 24-volt - Parallel Configuration - Step 3  
Important: Connecting the positive and negative wires to the inverter from different  
strings ensures a balanced charge/discharge through the batteries, resulting in longer run  
times and improved battery life.  
975-0012-01-02 Rev A  
B–11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Information  
Battery Connections for Stacked Inverters  
When using inverters in a stacked configuration, the same battery bank must be  
used for both inverters. To ensure even charging of the batteries, each inverter  
must be connected to both strings (i.e., positive cable to string two, and negative  
cable to string one for inverter 1, and positive cable to string one and negative  
cable to string two for inverter 2) as shown in the diagram below.  
DC CONDUIT  
FOR  
INVERTER 2  
(Secondary)  
DC CONDUIT  
FOR  
INVERTER 1  
(Primary)  
DC Disconnect  
(either a circuit  
breaker or a  
fuse with a  
DC Disconnect  
(either a circuit  
breaker or a  
fuse with a  
disconnect)  
disconnect)  
Shunt  
Series String 1  
24 VDC/200 Ah  
+
+
+
+
12 Volt  
Battery  
200 Ah  
12 Volt  
Battery  
200 Ah  
Batteries in  
Parallel  
24 VDC 400 Ah  
Series String 2  
24 VDC/200 Ah  
12 Volt  
Battery  
200 Ah  
12 Volt  
Battery  
200 Ah  
Figure B-7 Example of Battery Connections for Stacked Inverters (24 Vdc  
shown)  
B–12  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Maintenance  
Battery Maintenance  
Maintenance  
strategy  
To get the best performance from an inverter system, the batteries must be  
properly setup and maintained. This includes setting the proper voltages for Bulk  
and Float charging. See the “CAUTIONS” in the section on Equalization  
Charging that follows. In addition, the battery terminals should be inspected,  
cleaned, and re-torqued if necessary.  
Neglecting any of these items may result in poor inverter performance and greatly  
reduce battery life.  
Battery Charging  
Charge Rate  
The maximum safe charge rate is related to the size and type of the batteries.  
Flooded lead acid batteries (with removable caps) can be charged at a high rate.  
Small batteries may require a lower charge rate. Check with your battery vendor  
for the proper battery charging rate for the batteries used in the system.  
Bulk Voltage  
Float Voltage  
This is the maximum voltage the batteries will be charged to during a normal  
charge cycle. Gel cell batteries are set to a lower value and non-sealed batteries  
are set to a higher voltage setting.  
The Float voltage is set lower than the Bulk voltage and provides a maintenance  
charge on the batteries to keep them in a ready state.  
Temperature  
Compensation  
For optimal battery charging, the Bulk and Float charge rates should be adjusted  
according to the temperature of the battery. This can be accomplished  
automatically by using a BTS. The sensor attaches directly to the side of one of  
the batteries in the bank and provides precise battery temperature information.  
When battery charging voltages are compensated based on temperature, the  
charge voltage will vary depending on the temperature around the batteries. The  
following table describes approximately how much the voltage may vary  
depending on the temperature of the batteries.  
If you have liquid lead acid batteries (non-sealed), you may need to periodically  
equalize your batteries. Check the water level monthly to maintain it at the  
appropriate level.  
975-0012-01-02 Rev A  
B–13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Information  
Table B-4 Variances in Charging Voltage based on Battery Temperature  
Temperature  
(around the BTS)  
12-volt units  
24-volt units  
48-volt units  
Lead Acid NiCad  
Lead Acid NiCad  
Lead Acid NiCad  
Celsius Fahrenheit (6 cells)  
(10 cells) (12 cells) (20 cells) (24 cells) (40 cells)  
60  
55  
50  
45  
40  
35  
30  
25  
20  
15  
10  
5
140  
131  
122  
113  
104  
95  
86  
77  
68  
59  
50  
41  
32  
23  
14  
5
-4  
-1.05  
-0.90  
-0.75  
-0.60  
-0.45  
-0.30  
-0.15  
0.00  
0.15  
0.30  
0.45  
0.90  
0.75  
0.90  
1.05  
1.20  
1.35  
1.50  
1.65  
1.80  
1.95  
-0.70  
-0.60  
-0.50  
-0.40  
-0.30  
-0.20  
-0.10  
0.00  
0.10  
0.20  
0.30  
0.60  
0.50  
0.60  
1.20  
0.80  
1.40  
1.00  
1.10  
1.20  
1.30  
-2.10  
-1.80  
-1.50  
-1.20  
-0.90  
-0.60  
-0.30  
0.00  
0.30  
0.60  
0.90  
1.20  
1.50  
1.80  
2.10  
2.40  
2.70  
3.00  
3.30  
3.60  
3.90  
-1.40  
-1.20  
-1.00  
-0.80  
-0.60  
-0.40  
-0.20  
0.00  
0.20  
0.40  
0.60  
0.80  
1.00  
1.20  
1.40  
1.60  
1.80  
2.00  
2.20  
2.40  
2.60  
-4.20  
-3.60  
-3.00  
-2.40  
-1.80  
-1.20  
-0.60  
0.00  
0.60  
1.20  
1.80  
2.40  
3.00  
3.60  
4.20  
4.80  
5.40  
6.00  
6.60  
7.20  
7.80  
-2.80  
-2.40  
-2.00  
-1.60  
-1.20  
-0.80  
-0.40  
0.00  
0.40  
0.80  
1.20  
1.60  
2.00  
2.40  
2.80  
3.20  
3.60  
4.00  
4.40  
4.80  
5.20  
0
-5  
-10  
-15  
-20  
-25  
-30  
-35  
-40  
-13  
-22  
-31  
-40  
Temperature compensation is based on battery type — 5 mv/cell for lead acid type  
batteries and 2 mv/cell for alkaline type batteries (NiCad or NiFe). The  
temperature compensation calculations are derived from Table B-5.  
Table B-5 Temperature Compensation Calculation  
Battery Type  
24-volt Systems  
48-volt Systems  
Lead Acid  
0.060 volts (60 mV) per  
degree Celsius  
0.120 Volts (120 mV) per degree  
Celsius  
NiCad  
0.040 volts (40 mV) per  
degree Celsius  
0.080 volts (80 mV) per degree  
Celsius  
Important: If the battery temperature is allowed to fall to extremely cold  
temperatures, the inverter with a BTS may not be able to properly recharge cold  
batteries due to maximum voltage limits of the inverter. Ensure the batteries are  
protected from extreme temperatures.  
B–14  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Maintenance  
Equalization Charging  
Purpose  
An equalize charge helps to remove sulfate buildup on the battery plates and  
balances the charge of individual cells.  
Effect  
Equalize charging also produces gassing which stirs up the electrolyte mixture  
and helps distribute the acid more evenly.  
Non-equalized  
batteries  
Batteries that are not equalize charged can be damaged by sulfate accumulation,  
thus sealing off a percentage of the plates and reducing battery capacity. They may  
also have sulfuric acid accumulate at the bottom of the battery, potentially  
damaging the plates. At the same time, the electrolyte at the top of the battery gets  
watery. This effect is called stratification.  
Frequency  
Every month or two the batteries should be equalize charged.  
CAUTION: Damage to DC Loads  
The high voltages reached during an equalize charge may damage DC loads that  
are connected to the inverter. Disconnect any DC loads from the inverter before  
running an equalize charge.  
CAUTION: Damage to Batteries  
Equalization should be done for standard electrolyte vented batteries only. Sealed  
or GEL cell batteries should not be equalize charged. Consult your battery  
supplier for details on equalize charging for the battery type in your system.  
975-0012-01-02 Rev A  
B–15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Information  
General Maintenance  
Water Levels  
Flooded lead acid batteries require periodic water refills in each battery cell. Only  
distilled water should be used in a battery, as tap or mineral water may contain  
contaminants which will upset the battery chemistry and may damage the battery.  
When filling the battery, clean the surface first to prevent dirt from entering the  
cell. Fill the cell to just above the plates or to the bottom of the internal collar  
inside the battery. Never fill the cells to the top or acid will leak out during  
charging.  
Check the water level in the batteries frequently when performing an equalize  
charge and add water if necessary. Always follow the safety steps covered in the  
front of the manual.  
Battery Cables and  
Posts  
Battery posts must be clean to reduce the resistance between the battery post and  
cable connection. A buildup of dirt or oxidation may eventually lead to the cable  
terminal overheating during periods of high current draw.  
Use a stiff wire brush and remove all dirt and corrosion from the battery terminals  
and cables. Use an alkaline solution of baking soda and water to clean the  
terminals and neutralize any battery acid on the terminals or cable lugs.  
WARNING: Shock Hazard  
Before attempting to clean the battery posts, turn off the DC circuit breaker. Use  
only insulated tools and remove all jewellery.  
CAUTION: Damage to Batteries  
Never let a baking soda solution get into the battery as it will neutralize the acid  
resulting in permanent damage.  
Torque Battery  
Connections  
After the terminals are clean, reassemble the cable to the battery terminal and  
torque the connections to the battery manufacturer’s recommendations.  
Coat the battery terminals with an antioxidant compound.  
B–16  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Maintenance  
State of Charge  
The battery’s state-of-charge should be checked often and only when the battery at  
a state of rest (when the battery is not powering loads or actively being charged).  
First thing in the morning is usually the best time to check the state of charge. If  
the batteries are readily accessible, measure the voltage across the individual  
battery terminals. There should be less than a 0.2 volt difference between each  
battery.  
To determine the individual cell voltage, divide the voltage by the number of cells  
in the battery (25.2 volts divided by 12 cells = 2.1 volts per cell). If a greater  
difference is measured, the batteries may need to be equalized (liquid lead-acid  
types only) or replaced.  
All batteries in the bank should measure the same voltage (this is not an accurate  
measurement for cross-tied batteries’ as each battery is in parallel with another  
battery making individual battery measurements impossible).  
The voltage should match the following table for the entire battery bank output.  
These values indicate the overall battery’s state of charge for the entire bank.  
Individual cell voltages (if available) are also shown as a percentage of charge.  
The values given are for a temperature of 77 °F (25 °C). Cooler temperatures  
produce lower voltage measurements.  
Table B-6 Battery State-of-Charge  
System Voltage  
Individual  
Percent of Full  
Charge  
Cell  
Voltage  
12 Volt  
12.7  
24 Volt  
25.4  
48 Volt  
50.8  
100%  
90%  
80%  
70%  
60%  
50%  
40%  
30%  
20%  
10%  
0%  
2.12  
2.10  
2.08  
2.05  
2.03  
2.02  
2.00  
1.97  
1.95  
1.93  
< 1.93  
12.6  
25.2  
50.4  
12.5  
25.0  
50.0  
12.3  
24.6  
49.2  
12.2  
24.4  
48.8  
12.1  
24.2  
48.4  
12.0  
24.0  
48.0  
11.8  
23.6  
47.2  
11.7  
23.4  
46.8  
11.6  
23.2  
46.4  
< 11.6  
< 23.2  
< 46.4  
Important: Table B-6 only applies for batteries that have been at rest for a minimum of  
3 hours (i.e., no inverting, no charging).  
975-0012-01-02 Rev A  
B–17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B–18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Multi-wire Branch Circuit  
Wiring  
C
Appendix C, “Multi-wire Branch Circuit Wiring” supplies  
information about Multi-wire Branch Circuit Wiring Precautions  
when using stand-alone 120 Vac inverters or generators.  
WARNING  
A possible fire hazard can exist if 120 Vac only sources (such as inverters and  
generators) are wired incorrectly into 120/240 Vac panels containing multi-wire  
branch circuits. This section describes how to check for multi-wire branch  
circuits in the load center and presents some possible solutions to this wiring  
method.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Multi-wire Branch Circuit Wiring  
Multi-wire Branch Circuits  
Problem  
A potential safety problem exists when installing stand-alone 120 Vac inverters  
into existing 120/240 Vac wired panels where multi-wire branch circuit wiring  
methods were used.  
Legacy situation  
Multi-wire branch circuits are wired differently from “home run” type wiring  
(Figure C-1) in that only one neutral wire is used to provide the neutral-return path  
for each circuit connected to both phases of the AC grid. This method has been  
employed by electricians in recent years to keep construction costs down by  
saving copper and labor costs involved in running a separate Romex™ for each  
circuit.  
Normal condition  
Safety issue  
Under normal conditions, this technique is quite safe and meets code  
requirements. When used as originally installed, the current for each circuit is  
180° out-of-phase with each other, so the neutral wire never receives more current  
than it was designed to handle as the current from each circuit subtracts (or  
cancels out, leaving only the difference current between the two circuits). Refer to  
Figure C-2.  
A safety problem occurs when a stand-alone 120 Vac inverter is installed to power  
these circuits, causing the one neutral wire to now carry the in-phase currents for  
both circuits. Since the current is in-phase, the two circuits add instead of subtract,  
potentially doubling the current flow in the neutral return wire! Refer to Figure  
C-3. The branch circuit breakers do not protect the neutral wire from overload  
under this condition. This excess current will overheat the neutral wire, potentially  
creating a fire hazard.  
Load Center  
L1  
L2  
240 Vac  
from Grid  
Neutral  
15 A  
15 A  
Breaker  
Breaker  
Ground  
Black - Hot  
(Current Flow 15A)  
Black - Hot  
(Current Flow 15A)  
120 Vac  
120 Vac  
White - Neutral  
(Current Flow 15 A)  
White - Neutral  
(Current Flow 15 A)  
Bare - Ground  
Bare - Ground  
Figure C-1 Conventional Home-type Wiring  
C–2  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Multi-wire Branch Circuits  
Load Center  
Load Center  
L1  
L2  
L1  
L2  
240 Vac  
from Grid  
240 Vac  
from Grid  
Neutral  
15 A  
15 A  
Breaker  
(Ganged)  
(Ganged)  
15 A  
Breaker  
(Ganged)  
15 A  
Breaker  
(Ganged)  
Neutral  
Breaker  
Ground  
Ground  
Red - Hot  
(Current Flow 15 A)  
Red - Hot  
(Current Flow 15 A)  
Black - Hot  
Black - Hot  
(Current Flow 15 A)  
(Current Flow 5 A)  
Single White - Neutral  
(Current Flow 0 A)  
120 Vac  
120 Vac  
Single White - Neutral  
120 Vac  
(Current Flow 10 A)  
120 Vac  
Bare - Ground  
Bare - Ground  
Bare - Ground Splice  
When unbalanced  
current flows through  
each leg, only the  
difference current  
flows through the  
neutral return wire.  
White - Neutral Splice  
(Current Flow 15 A)  
White - Neutral Splice  
(Current Flow 15 A)  
Out-of-Phase current  
subtract at this point  
(Current Flow 0 A)  
Figure C-2 Multi-wire Branch Circuit Wiring and Current Flow  
Load Center  
120 Vac  
Inverter or Generator  
L1  
L2  
Neutral  
15 A  
15 A  
Breaker  
(Ganged)  
Breaker  
(Ganged)  
Ground  
Red - Hot  
(Current Flow 15 A  
Black - Hot  
(Current Flow 15 A)  
Single White - Neutral  
(Current Flow 30 A)  
120 Vac  
120 Vac  
Bare - Ground  
White - Neutral Splice  
(Current Flow 15 A)  
WARNING: FIRE HAZARD  
The in-phase currents ADDS  
at this point exceeding wire  
capacity!  
Figure C-3 120 Vac Inverter Incorrectly Wired in a Multi-wire Branch Circuit  
975-0012-01-02 Rev A  
C–3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Multi-wire Branch Circuit Wiring  
Identifying Multi-wire Branch Circuits  
WARNING: Shock Hazard  
The next step involves opening the load center, exposing live circuits. This  
procedure should only be performed by qualified persons or electricians.  
Identifying  
characteristic  
Multi-wire branch circuits can be identified by removing the cover on the load  
center and inspecting the wiring. Conventional 120 Vac circuits are identified by a  
2-wire-plus-ground (black, white, and copper) “romex” for each circuit.  
Multi-wire branch circuits use a 3-wire-plus-ground arrangement (black, red,  
white and copper) for each circuit run.  
If this arrangement exists in the panel and it is being powered by a stand-alone  
120 Vac inverter, a potential fire hazard exists! For safety, these circuits must be  
rewired to meet code.  
Red From L1  
Breaker  
Red From L2  
Breaker  
To Branch Circuits  
Single Neutral  
White  
Ground Bare  
Copper  
Figure C-4 Multi-wire Branch Circuit Wiring  
C–4  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Correcting Multi-wire Branch Circuit Wiring  
Correcting Multi-wire Branch Circuit Wiring  
Acceptable options  
Correcting multi-wire branch circuit wiring is not easy. Two options which will  
correct multi wiring branch circuit wiring are:  
Rewire existing multi-wire branch circuits to conventional “home run”  
wiring. This requires a qualified electrician (knowledgeable about multi-wire  
branch circuit wiring) and is expensive. There may be multiple multi-wire  
branch circuits located throughout the structure, requiring complete rewiring.  
Add a second inverter in a “series stacked” arrangement. This is an expensive  
solution, but would restore the original 240 Vac split-phase configuration.  
This solution may actually be less expensive than having an electrician  
re-wire the multi-wire branch circuits. It also provides increased power  
backup protection and can power 240 Vac loads.  
Recommended  
option  
Add a step-down autotransformer to the output of the inverter to restore the  
split-phase configuration. This is the least expensive and easiest method to correct  
for multi-wire branch circuit wiring. Refer to Figure C-5. Using this method, half  
of the current is supplied to one leg of the circuit and half to the other in a  
split-phase arrangement (180° out-of-phase). This will restore the original  
functionality and safety to the multi-wire branch circuit.  
WARNING: Fire Hazard  
Until one of the solutions above is implemented, a stand-alone 120 Vac inverter  
(or generator) must not be installed where multi-wire branch circuits exist.  
975-0012-01-02 Rev A  
C–5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Multi-wire Branch Circuit Wiring  
120 Vac  
Inverter or Generator  
T240  
AutoTransformer  
Load Center  
HOT - L1  
L1  
L2  
HOT - L2  
Neutral  
15 A  
15 A  
Breaker  
(Ganged)  
Breaker  
(Ganged)  
White - Neutral  
Ground  
Red - Hot  
(Current Flow 15 A  
Black - Hot  
(Current Flow 15 A)  
Single White - Neutral  
(Current Flow 0 A)  
120 Vac  
120 Vac  
Bare - Ground  
White - Neutral Splice  
(Current Flow 15 A)  
The out-of-phase  
current SUBTRACTS  
at this point.  
Figure C-5 Using a Step-down Autotransformer in Multi-wire Branch Circuit Wiring  
C–6  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warranty and Return Information  
Warranty  
What does this warranty cover? This Limited Warranty is provided by Xantrex Technology, Inc. ("Xantrex")  
and covers defects in workmanship and materials in your DR Inverter/Charger. This warranty period lasts for  
Warranty period from the date of purchase at the point of sale to you, the original end user customer. You require  
proof of purchase to make warranty claims.  
This Limited Warranty is transferable to subsequent owners but only for the unexpired portion of the Warranty  
Period. Subsequent owners also require proof of purchase.  
What will Xantrex do?  
Xantrex will, at its option, repair or replace the defective product free of charge, provided that you notify Xantrex of  
the product defect within the Warranty Period, and provided that Xantrex through inspection establishes the existence  
of such a defect and that it is covered by this Limited Warranty.  
Xantrex will, at its option, use new and/or reconditioned parts in performing warranty repair and building  
replacement products. Xantrex reserves the right to use parts or products of original or improved design in the repair  
or replacement. If Xantrex repairs or replaces a product, its warranty continues for the remaining portion of the  
original Warranty Period or 90 days from the date of the return shipment to the customer, whichever is greater. All  
replaced products and all parts removed from repaired products become the property of Xantrex.  
Xantrex covers both parts and labor necessary to repair the product, and return shipment to the customer via a  
Xantrex-selected non-expedited surface freight within the contiguous United States and Canada. Alaska and Hawaii  
are excluded. Contact Xantrex Customer Service for details on freight policy for return shipments outside of the  
contiguous United States and Canada.  
How do you get service? If your product requires troubleshooting or warranty service, contact your merchant. If  
you are unable to contact your merchant, or the merchant is unable to provide service, contact Xantrex directly at:  
Telephone: 1 800 670 0707 (toll free North America)  
1 360 925 5097 (direct)  
Fax:  
1 800 994 7828 (toll free North America)  
1 360 925 5143 (direct)  
Email:  
Direct returns may be performed according to the Xantrex Return Material Authorization Policy described in your  
product manual. For some products, Xantrex maintains a network of regional Authorized Service Centers. Call  
Xantrex or check our website to see if your product can be repaired at one of these facilities.  
What proof of purchase is required? In any warranty claim, dated proof of purchase must accompany the  
product and the product must not have been disassembled or modified without prior written authorization by Xantrex.  
Proof of purchase may be in any one of the following forms:  
The dated purchase receipt from the original purchase of the product at point of sale to the end user, or  
The dated dealer invoice or purchase receipt showing original equipment manufacturer (OEM) status, or  
The dated invoice or purchase receipt showing the product exchanged under warranty  
975-0012-01-02 Rev A  
WA–1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warranty and Return  
What does this warranty not cover? This Limited Warranty does not cover normal wear and tear of the  
product or costs related to the removal, installation, or troubleshooting of the customer's electrical systems. This  
warranty does not apply to and Xantrex will not be responsible for any defect in or damage to:  
a) the product if it has been misused, neglected, improperly installed, physically damaged or altered, either inter-  
nally or externally, or damaged from improper use or use in an unsuitable environment;  
b) the product if it has been subjected to fire, water, generalized corrosion, biological infestations, or input voltage  
that creates operating conditions beyond the maximum or minimum limits listed in the Xantrex product specifi-  
cations including high input voltage from generators and lightning strikes;  
c) the product if repairs have been done to it other than by Xantrex or its authorized service centers (hereafter  
"ASCs");  
d) the product if it is used as a component part of a product expressly warranted by another manufacturer;  
e) the product if its original identification (trade-mark, serial number) markings have been defaced, altered, or  
removed.  
Disclaimer  
Product  
THIS LIMITED WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY PROVIDED BY XANTREX IN CONNECTION WITH YOUR  
XANTREX PRODUCT AND IS, WHERE PERMITTED BY LAW, IN LIEU OF ALL OTHER WARRANTIES, CONDITIONS,  
GUARANTEES, REPRESENTATIONS, OBLIGATIONS AND LIABILITIES, EXPRESS OR IMPLIED, STATUTORY OR OTHERWISE IN  
CONNECTION WITH THE PRODUCT, HOWEVER ARISING (WHETHER BY CONTRACT, TORT, NEGLIGENCE, PRINCIPLES OF  
MANUFACTURER'S LIABILITY, OPERATION OF LAW, CONDUCT, STATEMENT OR OTHERWISE), INCLUDING WITHOUT  
RESTRICTION ANY IMPLIED WARRANTY OR CONDITION OF QUALITY, MERCHANTABILITY OR FITNESS FOR A PARTICULAR  
PURPOSE. ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE TO THE EXTENT  
REQUIRED UNDER APPLICABLE LAW TO APPLY TO THE PRODUCT SHALL BE LIMITED IN DURATION TO THE PERIOD  
STIPULATED UNDER THIS LIMITED WARRANTY.  
IN NO EVENT WILL XANTREX BE LIABLE FOR ANY SPECIAL, DIRECT, INDIRECT, INCIDENTAL OR CONSEQUENTIAL  
DAMAGES, LOSSES, COSTS OR EXPENSES HOWEVER ARISING WHETHER IN CONTRACT OR TORT INCLUDING WITHOUT  
RESTRICTION ANY ECONOMIC LOSSES OF ANY KIND, ANY LOSS OR DAMAGE TO PROPERTY, ANY PERSONAL INJURY, ANY  
DAMAGE OR INJURY ARISING FROM OR AS A RESULT OF MISUSE OR ABUSE, OR THE INCORRECT INSTALLATION,  
INTEGRATION OR OPERATION OF THE PRODUCT.  
Exclusions  
If this product is a consumer product, federal law does not allow an exclusion of implied warranties. To the extent you  
are entitled to implied warranties under federal law, to the extent permitted by applicable law they are limited to the  
duration of this Limited Warranty. Some states and provinces do not allow limitations or exclusions on implied  
warranties or on the duration of an implied warranty or on the limitation or exclusion of incidental or consequential  
damages, so the above limitation(s) or exclusion(s) may not apply to you. This Limited Warranty gives you specific  
legal rights. You may have other rights which may vary from state to state or province to province.  
Warning: Limitations On Use  
Please refer to your product manual for limitations on uses of the product.  
SPECIFICALLY, PLEASE NOTE THAT THE DR INVERTER/CHARGER SHOULD NOT BE USED IN CONNECTION WITH LIFE  
SUPPORT SYSTEMS OR OTHER MEDICAL EQUIPMENT OR DEVICES. WITHOUT LIMITING THE GENERALITY OF THE  
FOREGOING, XANTREX MAKES NO REPRESENTATIONS OR WARRANTIES REGARDING THE USE OF THE XANTREX DR  
INVERTER/CHARGER IN CONNECTION WITH LIFE SUPPORT SYSTEMS OR OTHER MEDICAL EQUIPMENT OR DEVICES.  
Please note that the DR Inverter/Charger is not intended for use as an uninterruptible power supply and Xantrex  
makes no warranty or representation in connection with any use of the product for such purposes.  
WA–2  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warranty and Return  
Return Material Authorization Policy  
Before returning a product directly to Xantrex you must obtain a Return Material Authorization (RMA) number and  
the correct factory "Ship To" address. Products must also be shipped prepaid. Product shipments will be refused and  
returned at your expense if they are unauthorized, returned without an RMA number clearly marked on the outside of  
the shipping box, if they are shipped collect, or if they are shipped to the wrong location.  
When you contact Xantrex to obtain service, please have your instruction manual ready for reference and be prepared  
to supply:  
The serial number of your product  
Information about the installation and use of the unit  
Information about the failure and/or reason for the return  
A copy of your dated proof of purchase  
Record these details in on page WA–4.  
Return Procedure  
1. Package the unit safely, preferably using the original box and packing materials. Please ensure that your product  
is shipped fully insured in the original packaging or equivalent. This warranty will not apply where the product is  
damaged due to improper packaging.  
2. Include the following:  
The RMA number supplied by Xantrex Technology, Inc. clearly marked on the outside of the box.  
A return address where the unit can be shipped. Post office boxes are not acceptable.  
A contact telephone number where you can be reached during work hours.  
A brief description of the problem.  
3. Ship the unit prepaid to the address provided by your Xantrex customer service representative.  
If you are returning a product from outside of the USA or Canada In addition to the above, you MUST  
include return freight funds and are fully responsible for all documents, duties, tariffs, and deposits.  
If you are returning a product to a Xantrex Authorized Service Center (ASC) A Xantrex return  
material authorization (RMA) number is not required. However, you must contact the ASC prior to returning the  
product or presenting the unit to verify any return procedures that may apply to that particular facility.  
Out of Warranty Service  
If the warranty period for your DR Inverter/Charger has expired, if the unit was damaged by misuse or incorrect  
installation, if other conditions of the warranty have not been met, or if no dated proof of purchase is available, your  
inverter may be serviced or replaced for a flat fee.  
To return your DR Inverter/Charger for out of warranty service, contact Xantrex Customer Service for a Return  
Material Authorization (RMA) number and follow the other steps outlined in “Return Procedure” on page WA–3.  
Payment options such as credit card or money order will be explained by the Customer Service Representative. In  
cases where the minimum flat fee does not apply, as with incomplete units or units with excessive damage, an  
additional fee will be charged. If applicable, you will be contacted by Customer Service once your unit has been  
received.  
975-0012-01-02 Rev A  
WA–3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warranty and Return  
Information About Your System  
As soon as you open your DR Inverter/Charger package, record the following information and be sure to keep your  
proof of purchase.  
_________________________________  
_________________________________  
_________________________________  
Serial Number  
Purchased From  
Purchase Date  
If you need to contact Customer Service, please record the following details before calling. This information will help  
our representatives give you better service.  
__________________________________  
__________________________________  
__________________________________  
__________________________________  
__________________________________  
__________________________________  
__________________________________  
__________________________________  
__________________________________  
Type of installation (e.g. On-Grid, Off-grid)  
Length of time inverter has been installed  
Battery/battery bank size  
Battery type (e.g. flooded, sealed gel cell, AGM)  
DC wiring size and length  
Alarm sounding?  
Description of indicators on front panel  
Appliances operating when problem occurred  
Description of problem  
______________________________________________________________________________________  
______________________________________________________________________________________  
WA–4  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
A
P
AM radios 4–3  
AWG 2–4  
peak output voltage 4–4  
Problem Loads 4–3  
proof of purchase WA–4  
purchase date WA–4  
B
Batteries  
R
Battery Care and Maintenance  
Equalization Charging B–15  
Temperature Compensation B–13  
Battery Types  
Reverse Polarity 2–18  
S
Absorbed Glass Mat B–3  
Flooded Lead Acid (FLA) B–2  
Gel Cell B–3  
safety instructions vii  
serial number WA–4  
Golf Cart B–2  
Industrial (electric forklift) B–2  
NiCad and NiFe B–3  
Charging  
Bulk Voltage B–13  
Charge Rates B–13  
Float Voltage B–13  
batteries  
first aid when working with vii  
precautions when working with vii  
Battery B–13  
W
warranty  
out of warranty service WA–3  
terms and conditions WA–1  
X
Xantrex  
web site iv  
C
computers 4–3  
computers - use with inverter 4–3  
Customer Service  
preparing to call WA–4  
F
first aid vii  
Fluorescent lights 4–4  
I
Information about Your System form WA–4  
inverter  
purchase date WA–4  
serial number WA–4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IX-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Xantrex Technology Inc.  
1 800 670 0707 Tel. toll free NA  
1 360 925 5097 Tel direct  
1 800 994 7828 Fax toll free NA  
1 360 925 5143 Fax direct  
www.xantrex.com  
PC Printed in the DR  
975-0012-01-02 Rev A  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Weslo Home Gym WLCCEX69871 User Manual
Whirlpool Air Conditioner 1157672 User Manual
Whirlpool Air Conditioner ACM122XR0 User Manual
Whirlpool Oven RS696PXGB8 User Manual
Whirlpool Range 98015195 User Manual
Whirlpool Range FEP210VL0 User Manual
White Rodgers Refrigerator 1609 User Manual
Xerox Flat Panel Television XM7 22w User Manual
Yamaha Music Mixer M3000A User Manual
Zenith Cable Box HCS5610 User Manual