Westinghouse Power Hammer IL 33 DAH 1 User Manual

IL 33-DAH-1  
Digitrip Retrofit System for  
Westinghouse DA-75 Breakers  
Table of Contents  
SAFETY PRECAUTIONS ................................................................................................................1  
Kit Components List .........................................................................................................................2  
Step 1: General Breaker Preparation ............................................................................................3  
Step 2: Removing the Original Electromechanical Trip Units ........................................................3  
Step 3: Preparing the Sensors ......................................................................................................4  
Step 4: Installing the Sensors........................................................................................................4  
Step 5: Installing the Trip Unit Mounting Platform..........................................................................5  
Step 6: Preparing the Trip Unit Assembly......................................................................................6  
Step 7: Installing the Trip Unit........................................................................................................6  
Step 8: Installing the Trip Finger ....................................................................................................7  
Step 9: Installing the Reset Arm Assembly ...................................................................................7  
Step 10: Installing the DTA Assembly .............................................................................................8  
Step 11: Installing the 2-Point Terminal Block .................................................................................9  
Step 12: Installing the Breaker Mounted CPT .................................................................................9  
Step 13: Final Connection of the Harnesses and Wiring...............................................................11  
Step 14: Installing the Auxiliary Switch..........................................................................................14  
Step 15: Testing the Breaker .........................................................................................................15  
Step 16: Mounting the Cell Harness .............................................................................................15  
Step 17: Installing the Retrofitted Breaker in the Cell....................................................................16  
Kit Parts List ...................................................................................................................................17  
Torque Values for General Mounting ..............................................................................................21  
Torque Values for Copper BUS Connectors ...................................................................................21  
INDEX ............................................................................................................................................25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 2  
IL 33-DAH-1  
Cutler-Hammer Digitrip Retrofit Kits are available in  
a number of configurations that provide a wide  
range of features. The Digitrip System starts with  
the 510 Basic Kit which offers true RMS sensing,  
overcurrent protection, and self-testing features.  
Advanced Digitrip Retrofit Kits feature zone  
interlocking, digital alphanumeric displays, remote  
alarm signals, IMPACC communications, energy  
monitoring capabilities, power factors, and  
harmonic content measurements.  
which level of Retrofit Kit is to be installed and  
which components are included with the Kit.  
The instructions contained in this manual cover the  
installation of all levels of Retrofit Kit. If the Kit you  
are installing does not contain a certain component,  
skip the instructions for that component and  
proceed to the next.  
Throughout the Retrofit process, refer to the Torque  
Tables at the back of this manual for specific  
torque values.  
The following table provides a quick reference of  
the components supplied with each level of Retrofit  
Kit. Before beginning the Retrofit process, take a  
minute to review the information contained in the  
table. It is important that the Retrofitter understand  
If you have any questions concerning the Retrofit  
Kit and / or the Retrofit process, contact  
Cutler-Hammer at 1-800-937-5487.  
510 with  
Components  
510 Basic  
Zone  
610  
810  
910  
Interlock  
Trip Unit  
Rating Plug  
Auxiliary Current  
Transformer  
(CT) Module  
Auxiliary  
CT Harness  
Sensors  
Sensor Harness  
Direct Trip  
Actuator (DTA)  
Mounting Brackets  
and Hardware  
External  
Harness  
Plug  
1 Connector  
Harness  
2 Connector  
Harness  
4 Connector  
Harness  
4 Connector  
Harness  
Cell Harness  
Breaker Mounted  
Control Power  
Transformer (CPT)  
Potential Transformer  
(PT) Module  
Auxiliary Switch  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 3  
IL 33-DAH-1  
Step 1: General Breaker Preparation  
To begin the Retrofit Process, refer to the  
components list at the end of this manual. Lay  
out the components and hardware according  
to the steps outlined. The components and  
hardware will be used to complete each step  
in the Retrofit Process.  
Before attempting to remove the Breaker from  
the cell or perform any Retrofit Operation, be sure  
to read and understand the Safety Precautions  
section of this manual. In addition, be sure to read  
and understand the Instructions for the Application  
of Digitrip RMS Retrofit Kits on Power Circuit  
Breakers (Retrofit Application Data - Publication  
AD 33-855-1), supplied with the Digitrip Retrofit Kit.  
Step 2: Removing the Original  
Electromechanical Trip Units  
Follow the Westinghouse DA-75 Instruction Manual,  
originally supplied with the Breaker, to perform the  
following procedure.  
WARNING  
DO NOT ATTEMPT TO INSTALL OR PERFORM  
MAINTENANCE ON EQUIPMENT WHILE IT IS  
ENERGIZED. SEVERE PERSONAL INJURY OR  
DEATH CAN RESULT FROM CONTACT WITH  
ENERGIZED EQUIPMENT. VERIFY THAT NO  
VOLTAGE IS PRESENT BEFORE PROCEEDING.  
A. Remove and scrap the original  
Electromechanical Trip units and all  
associated hardware.  
A. Trip the Breaker and remove it from the Cell.  
Move the Breaker to a clean, well-lit work  
bench.  
NOTE: It is the responsibility of the  
Retrofitter to insure that the Breaker and  
all original components are in good  
condition. Visually inspect all Breaker  
components for signs of damage or wear.  
If any signs of damage or wear are  
detected for components not included in the  
Retrofit Kit, secure the necessary  
replacement parts before beginning the  
Retrofit Process.  
The force necessary to trip the Breaker  
should not exceed seven (7) lbs.  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 4  
IL 33-DAH-1  
Step 3: Preparing the Sensors  
Step 4: Installing the Sensors  
A. Place each Sensor between two Glass Poly  
Insulation Plates. The connector stabs should  
be positioned towards the cutouts in the  
Insulation Plates as shown.  
A. Remove and save the center bolts securing the  
bottom Finger Clusters to the Breaker Stabs.  
Remove the Finger Clusters.  
B. Secure the Glass Poly Plates on either side of  
the Sensors using the (12) .250-20 × 2.00"  
bolts, (24) flat washers, and (12) elastic stop  
nuts supplied. Note that the bolts must be  
installed so that the bolt heads will be against  
the back of the Breaker and the stop nuts away  
from the Breaker (same side as the screw  
heads of the Sensor terminals). Do not over  
tighten the bolts.  
B. Install a Sensor Assembly over each Breaker  
Stab, with the Sensor terminals pointing  
downward and the bolt heads outward as  
shown.  
C. Reinstall the Finger Clusters and secure them  
using the original hardware.  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 5  
IL 33-DAH-1  
Step 5: Installing the Trip Unit Mounting  
Platform  
B. Mount the right and left Trip Unit Support Brackets  
to the Breaker side plates as shown, using the  
(4) .312-18 × .750" flat head screws, (4) flat  
washers, (4) lock washers, and (4) nuts supplied.  
Do not tighten them completely at this time.  
A. Using Drilling Plan “A”, drill and counter sink  
two .375" holes in both the left and right  
Breaker side plates.  
NOTE: The holes for mounting the DTA  
(see Step 10) should also be drilled and  
countersunk in the right Breaker Frame  
at this time.  
NOTE: For ease of assembly, the 2-Point  
Terminal Block (Step 11-A) can be mounted  
to the inside of the right Trip Unit Support  
Bracket at this time.  
C. Mount the Trip Unit Mounting Platform to the  
Support Brackets using the (4) .312-18 × .750"  
bolts, (8) flat washers, (4) lock washers, and (4)  
nuts supplied. Tighten the hardware connecting  
the Mounting Platform to the Support Brackets,  
and then the Support Brackets to the Breaker  
side plates. Assure that the Mounting Platform  
and Support Brackets are square with the Breaker.  
Drilling Plan “A”  
6.50"  
2.00"  
2.38"  
1.81"  
0.75"  
Drill 0.375" Dia. and  
Countersink to 0.578"  
Head Size (2)  
0.75"  
Drill 0.375" Dia. and  
Countersink to 0.578"  
Head Size (4)  
Right Side Only  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 6  
IL 33-DAH-1  
Step 6: Preparing the Trip Unit Assembly  
D. Mount the Trip Unit Mounting Brackets to the  
sides of the Aux. CT Module, using the (4)  
.190-32 × .375" screws, (4) lock washers, and  
(4) flat washers supplied, so they “pinch” the  
Trip Unit in place.  
A. For Kits Supplied with a PT Module Only. Mount  
the PT Module to the Glass Poly Insulation  
Barrier as shown, using the (2) .138-32 × .500"  
screws, (4) flat washers, (2) lock washers, and  
(2) nuts supplied.  
E. Remove the Trip Unit cover and install the  
Rating Plug. Replace the cover.  
F. Install the Digitrip Nameplate on the top of the  
Trip Unit.  
G. Connect the Aux. CT Harness to the Trip Unit  
and Aux. CT Module.  
Step 7: Installing the Trip Unit  
B. Secure the Glass Poly Insulation Barrier to  
the back of the Aux. CT Module using the (2)  
.190-32 × .375" screws, (2) lock washers, and  
(2) flat washers supplied.  
C. Install the Trip Unit on the top of the Aux. CT  
Module using the (2) brass spacers, (2)  
.190-32 × 4.00" screws, (2) lock washers, and  
(2) flat washers supplied as shown. Note that  
the brass spacers are placed between the  
bottom of the Trip Unit and the top of the Aux.  
CT Module.  
A. Mount the Trip Unit / Aux. CT Module Assembly  
to the Trip Unit Mounting Platform as shown,  
using the (4) .250-20 × .750" bolts, (8) flat  
washers, (4) lock washers, and (4) nuts supplied.  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 7  
IL 33-DAH-1  
Step 8: Installing the Trip Finger  
Step 9: Installing the Reset Arm Assembly  
A. Note the position of the original Trip Finger and  
associated “gap” between the Trip Finger and  
manual Trip Shaft. Remove the original Trip  
Finger and scrap the mounting hardware.  
B. Mount the new Trip Finger on the top of the  
Cross Bar (with the curve upward and the notch  
to the right) as shown, and the original Trip  
Finger back on the bottom of the Cross Bar.  
Secure using the (2) .190-32 × 1.75" bolts,  
(4) flat washers, (2) lock washers, and  
(2) nuts supplied.  
A. Remove the original Interlock Arm. Scrap the  
original bolts, washers, and nuts.  
B. Mount the Reset Arm Assembly to the bottom  
of the Cross Bar and the original Interlock Arm  
to the top of the Cross Bar in its original  
position, using the (2) .190-32 × 1.75" bolts, (4)  
flat washers, (2) lock washers, and (2) nuts  
supplied. The Reset Arm Assembly should be  
positioned so that the Reset Arm is hanging  
downward as shown.  
C. Verify that the original Trip Finger has been  
reinstalled in its initial position by checking the  
gap (noted in Step 8-A) between the original  
Trip Finger and manual Trip Shaft.  
GAP  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 8  
IL 33-DAH-1  
Step 10: Installing the DTA Assembly  
B. Remove the two nuts, flat washers, and spring  
from the Reset Assembly, being careful that the  
brass spacer does not slide off the all-thread.  
C. Position the DTA Assembly behind the DTA  
Mounting Bracket, with the Reset Assembly  
Shaft going through the slot in the DTA Reset  
Arm. Mount the DTA Assembly to the DTA  
Mounting Bracket, as shown, using the (4)  
.164-32 × .312" pan / lock screws and (4) flat  
washers provided.  
D. With the DTA in the latched position and the  
DTA Release Arm lifted up over the brass  
sleeve, reinstall the large flat washer, spring,  
small flat washer, and (1) nut onto the Reset  
Assembly Arm. Snug the nut against the brass  
sleeve.  
®
E. Apply Loc-Tite 242 to the threads at the base  
of the installed nut. Install the second nut and  
tighten the nuts against each other.  
A. Mount the DTA Mounting Bracket to the right  
Breaker side panel, as shown, using the holes  
drilled in Step 5 A and the (2) .312-18 × .750"  
screws, (2) flat washers, (2) lock washers, and  
(2) nuts provided.  
F. Connect a 24 VDC power supply to the DTA  
terminals; positive to positive and negative to  
negative. Close the Breaker manually. Energize  
the DTA to trip the Breaker; de-energize when  
the Breaker trips. Make certain that the DTA  
resets. If the Breaker fails to properly trip or  
reset, it may be necessary to shorten the brass  
spacer on the Reset Assembly Shaft. Make the  
necessary adjustments until the trips and resets  
are sure and positive each time.  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 9  
IL 33-DAH-1  
Step 11: Installing the 2-Point Terminal Block  
For Kits Supplied with a Breaker Mounted  
CPT Only.  
Step 12: Installing the Breaker Mounted CPT  
A. Mount the 2-Point Terminal Block to the  
pre-drilled holes in the right Trip Unit Support  
Bracket as shown, using the (2) .138-32 × .750"  
screws, (4) flat washers, (2) lock washers, and  
(2) nuts supplied.  
A. Align the holes in the Breaker Mounted CPT  
with the predrilled holes on the left side of the  
Trip Unit Mounting Platform. Secure the CPT to  
the Trip Unit Mounting Platform using the (4)  
.190-32 × .500" screws, (8) flat washers, (4)  
lock washers, and (4) nuts supplied. Note that  
the X1 and X2 terminals face the front of the  
Breaker.  
B. Route the DTA wires from the DTA Assembly to  
the 2-Point Terminal Block. After assuring the  
wires are clear of any moving components  
within the Breaker, connect the DTA wires to  
the 2-Point Terminal Block.  
B. Insert the black plug of the CPT Harness into  
the receptacle in the Trip Unit.  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 10  
IL 33-DAH-1  
C. Route the CPT Harness between the Trip Unit  
and the Insulation Barrier to the CPT. Strip .250"  
of insulation and attach a .138" ring terminal to  
each wire of the CPT Harness. Connect the  
CPT Harness wires to the X1 and X2 terminals  
of the CPT.  
E. Attach the Glass Poly Insulation Plate to the top  
of the CPT, as shown, using the screws and  
lock washers supplied with the CPT kit.  
D. Position the fuses on the High Voltage (HV)  
Wires in an accessible location. Route the HV  
Wires between the Trip Unit and Insulation  
Barrier to the Breaker Mounted CPT, then cut  
the Load Side of each HV Wire to an  
appropriate length. Strip .250" from the Load  
Side HV Wires and attach a .138" ring terminal  
to each. Attach the HV Wires to the CPT  
terminals to achieve the required voltage (see  
the following table). The HV Wires will be  
connected to the Phase Frames later in the  
Retrofit process.  
F. Attach the appropriate warning label for the  
Breaker to the left of the CPT on the Trip Unit  
Mounting Platform.  
Voltage Required  
CPT Terminals Used  
600 Volt Circuit  
H1 & H2  
Voltage Required  
480 Volt Circuit  
240 Volt Circuit  
208 Volt Circuit  
CPT Terminals Used  
H1 & H4  
H1 & H3  
H1 & H2  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 11  
IL 33-DAH-1  
Step 13: Final Connection of the  
Harnesses and Wiring  
B. Route the Sensor Harness between the Glass  
Poly Insulation Barrier and the back of the Trip  
Unit, then down along the right Trip Unit  
Mounting Bracket and through the hole in the  
Breaker Back Plate as shown. Secure the  
Sensor Harness as shown using the wire  
clamps and (6) .138-20 × .500" thread cutting  
screws supplied.  
A. Feed the Sensor Harness through the hole in  
the left side of the Aux. CT Module. Connect the  
Sensor Harness to the proper terminals on the  
Aux. CT Module. Refer to Section 12 of the  
Retrofit Application Data, supplied with the  
Retrofit Kit, for detailed wiring specifications.  
Connect the green ground wire from the Sensor  
Harness (with the ring terminal) to the screw in  
the left side of the Aux. CT Module.  
C. Route the Sensor Harness to the bottom of the  
Sensors. Connect the ring terminals of the  
Sensor Harness to the Sensors. Refer to  
Section 12 of the Retrofit Application Data,  
supplied with the Retrofit Kit, for detailed wiring  
specifications.  
Depending on the Sensors supplied with the  
Retrofit Kit, the following convention applies.  
Sensor Style No.  
4A35613H01  
X1-X2 = 3000 A  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 12  
IL 33-DAH-1  
D. For Kits Supplied with a PT Module Only.  
Refer to Section 7-3, Power Flow Convention of  
the Retrofit Application Data, supplied with the  
Retrofit Kit for additional wiring information and  
to verify the Phase Convention used on this  
Breaker Application.  
E. For Kits Supplied with a Breaker Mounted CPT  
Only. Route the Line Side HV Wires to the rear  
of the Breaker through the opening in the  
Breaker Back Plate and along the rear of the  
Breaker to the top Phase Frames.  
Note: The power convention of the  
Westinghouse DA-75 Series Breakers is  
normally Top to Bottom, meaning the Top  
Breaker Phase Frames are on the Line Side  
of the Breaker and the Bottom Breaker  
Stabs are on the Load Side.  
Route the PT Wires between the Glass Poly  
Insulation Barrier and the back of the Trip Unit,  
then down along the right Trip Unit Mounting  
Bracket to the area where the original  
Electromechanical Trip devices were removed  
(Step 2).  
The HV Wires from the CPT MUST BE  
ATTACHED to the Line Side of the Breaker. If  
it is determined that the power flow for the  
Breaker application is opposite the normal  
convention, the HV Wires must be attached  
to the Bottom Phase Frames.The bolts used  
to secure the PT Wires can be used to  
connect the HV Wires.  
The PT Wires are marked for connection to  
Phases 1, 2, and 3 with corresponding  
numbers.  
NOTE: Before cutting the PT Wires, verify  
the Phase Convention used on the Breaker  
Application.  
Note: The Line Side HV Wires are longer  
than necessary and are cut during the  
following steps. Before cutting the wires, be  
sure that sufficient length is left so that the  
connections can be made to the correct  
Finger Clusters or Phase Frames.  
Route the PT Wires to a position suitable for  
attachment to the proper Breaker Phase  
Frames. Move the PT Wire markers to a  
position where they will still be attached to the  
wires after cutting. Cut the wires to length, strip  
each wire .250", and install a .250" ring terminal  
to each PT Wire.  
F. For Kits Supplied with a Breaker Mounted CPT  
Only. Using a .234" drill, drill and tap one hole in  
the top of the Phase 1 and 2 or Phase 2 and 3  
Phase Frames.  
Connect each PT Wire to the corresponding  
Breaker Phase Frames using the (3)  
.250-20 × .500" bolts, (3) lock washers, and  
(3) flat washers supplied.  
G. For Kits Supplied with a Breaker Mounted CPT  
Only. Cut the HV Wires to the appropriate  
length for attachment to the appropriate Phase  
Frames. Strip .250" from each HV Wire and  
attach a .250" ring terminal. Using the (2)  
.250-20 × .500" bolts, (2) flat washers, and (2)  
lock washers supplied, connect the HV Wires  
to the appropriate Phase Frames.  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 13  
IL 33-DAH-1  
H. Feed the two wires from the DTA Extension  
Harness through the opening in the left side of  
the Aux. CT Module. Connect the wire marked  
“+” to the “OP” terminal and the unmarked wire  
to the “ON” terminal.  
I. Route the DTA Extension Harness between the  
Glass Poly Insulation Barrier and the back of  
the Trip Unit, then down along the right Trip Unit  
Support Bracket to the 2-Point Terminal Block.  
Connect the wire from the DTA Extension  
Harness marked with “+” to the “+” terminal and  
the unmarked wire to the other terminal.  
NOTE: For 510 Basic Retrofit Kits, the  
External Harness is the plug pictured above.  
It is to be plugged into the right side of the  
Trip Unit.  
K. For Kits Supplied with a PT Module Only.  
Connect the PT Harness to the External  
Harness.  
L. Use the wire ties, wire clamps, and self  
adhesive wire clips provided to dress all wires  
and harnesses to keep them away from any  
moving parts within the Breaker.  
NOTE: The self adhesive wire clips should  
be attached to the right Breaker side panel  
to secure the Sensor Harness.The wire  
clamps should be attached to the hardware  
mounting the Aux. CT Module and the Trip  
Unit, as shown, to secure the Sensor  
Harness, External Harness, and PT  
Extension Harness.  
J. Connect the External Harness to the Trip Unit.  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 14  
IL 33-DAH-1  
For Kits Supplied with an Aux. Switch Only.  
C. Connect the two wires (with ring terminals) from  
the External Harness to the Auxiliary Switch.  
Connect one wire to the normally “Open”  
terminal and the other wire to the “Common”  
terminal of the Auxiliary Switch.  
Step 14: Installing the Auxiliary Switch  
D. Making sure the Microswitch arm is behind the  
Interlock Bar, mount the Aux. Switch Assembly  
to the pre-drilled holes in the right Trip Unit  
Mounting Bracket, using the (2) .164-32 × .500"  
screws, (4) flat washers, (2) lock washers, and  
(2) nuts supplied.  
A. Using diagonals, cut 2.625" off the  
Microswitch Arm.  
B. Mount the Microswitch to the Auxiliary Switch  
Mounting Bracket, as shown, using the (2)  
.138-32 × 1.25" screws, (8) flat washers, (4)  
lock washers, and (4) nuts supplied.  
NOTE: To provide correct spacing, the  
hardware must be installed in the following  
order. Insert screws with flat washers  
installed through the switch. Install flat  
washers, lock washers, and tighten the nuts.  
Install another set of flat washers, then the  
mounting bracket, flat washers, lock  
washers, and nuts.  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 15  
IL 33-DAH-1  
Step 15: Testing the Breaker  
3. For 810 and 910 Kits Only. Without any  
power applied to the system (neither the 120  
volt power supply nor the Aux. Power  
Module connected), plug the External  
Harness into the Cell Harness and check the  
impedance between COM 1 and COM 2.The  
impedance should be between one (1) and  
three (3) ohms. If the impedance is not  
within this range, trace the wiring and  
examine each connection to assure its  
integrity.  
A. Measure the force necessary to trip the  
Breaker at the point where the DTA impacts the  
Trip Finger. The force necessary to trip the  
Breaker MUST NOT EXCEED SEVEN (7) lbs.  
B. The Retrofit must be tested using primary  
injection. Refer to Section 8 of the Instructions  
for the Application of Digitrip RMS Retrofit Kits  
on Power Circuit Breakers (Publication  
AD 33-855-1, June, 1997), supplied with the  
Retrofit Kit, for detailed testing procedures and  
specifications. For test information specific to  
the Trip Unit, refer to the IL publication supplied  
with the Retrofit Kit (see the Pick List for the  
IL number).  
Confirm that the IMPACC communication  
wiring is correct by following the procedures  
detailed in Section 7.4 of the Instructions for  
the Application of Digitrip RMS Retrofit Kits  
on Power Circuit Breakers. Note that for 810  
and 910 Kits, the impedance between COM 1  
and COM 2 should be between one (1) and  
three (3) ohms.  
C. While Section 8 of the Instructions for the  
Application of Digitrip RMS Retrofit Kits on  
Power Circuit Breakers provides the information  
necessary for testing the Breaker, please keep  
the following notes in mind when reviewing  
other sections of the publication.  
When testing is complete, disconnect the  
External Harness from the Cell Harness.  
Final External Harness connection will be  
performed in Step 16.  
CAUTION: When all testing is complete, the Trip  
Unit must be reset. Failure to do so may cause  
the battery in the Rating plug to run down.  
For Kits Supplied with a Cell Harness Only.  
Step 16: Mounting the Cell Harness  
Notes:  
A. The Cell Harness is to be mounted in the  
Breaker Cell. The connector end is to be  
mounted on the right front side of the Cell, in a  
location suitable for connection with the  
External Harness. The Terminal Blocks can be  
mounted anywhere space is available in the  
Cell as long as connection to the External  
Harness can be made.  
1. Publication AD-33-855 was created  
specifically for the “hundred” series (500,  
600, 700, etc.) Retrofit Kits.Therefore certain  
sections and figures do not apply to the  
“ten” series (510, 610, 810, etc.) Retrofit Kits.  
Specifically, these are Sections 13 and 14, as  
well as Figures 3-2, 3-3, and 3-4.  
2. For All Kits Other Than 510 Basic. If testing  
the Breaker with Short Delay or Ground  
Fault functions, be sure to either plug in the  
Cell Harness Assembly or use the Zone  
Interlock Shorting Plug. Failure to do so may  
result in shorter than expected trip times.  
B. Route the Cell Harness wiring to keep it away  
from any moving parts within the Cell Housing.  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 16  
IL 33-DAH-1  
Step 17: Installing the Retrofitted Breaker  
in the Cell  
NOTE: It is the responsibility of the Retrofitter  
to insure proper Breaker / Cell fit.When racking  
the Breaker into the Connected position, the  
Retrofitter MUST FOLLOW BOTH the  
manufacturer’s instructions and the customer’s  
safety standards and procedures for racking a  
Breaker into the Connected position.  
WARNING  
Do not leave the Breaker in an intermediate  
position in the switchgear cell. Always leave  
it in the CONNECTED, DISCONNECTED, or  
(Optional) TEST position. Failure to do so could  
lead to improper positioning of the Breaker and  
flashover, causing death, serious personal  
injury, and / or property damage.  
A. With the Breaker in the Open position and the  
springs discharged, slowly rack the Breaker into  
the Connected position, making sure there is no  
interference or binding. The Breaker should rack  
smoothly and without mechanical interference  
between any Breaker and Cell parts. The  
Retrofitter will feel some resistance when the  
primary fingers connect onto the stabs of the  
Cell. This is normal.  
WARNING  
It is solely the responsibility of the Retrofitter to  
make the necessary modifications to the origi-  
nal Racking Mechanism, or to manufacture a  
Racking Bar Adapter, to insure safe racking of  
the Breaker into the Cell. If the Retrofitter opts  
to modify the original Racking Mechanism, the  
Racking Bar Receptacle must be removed from  
the Racking Mechanism, moved to a location  
where the Racking Bar will not contact the DTA  
during racking, and welded to the Racking  
Mechanism.  
However, if any unusual resistance is detected  
that could be abnormal interference between  
the Breaker and Cell parts, stop immediately  
and move the Breaker out of the Connected  
position. Examine what is causing the  
interference and correct the situation.  
If the Retrofitter opts to manufacture a Racking  
Bar Adapter for use with the original Racking  
Mechanism configuration, the drawing and  
photo below should be used as a basis.  
Breaker Racking Pivot  
Adapter  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 17  
IL 33-DAH-1  
Digitrip Retrofit Kit Installation Components for the Westinghouse DA-75 Breakers  
Step  
Description  
Style No.  
Qty.  
Comment  
Step 3  
Sensors 3000/5000  
4A35613H01  
4A35618G04  
3
1
6
12  
24  
12  
Sensor Mounting Parts  
Glass Poly Mounting Plates  
.250 - 20 × 2.00 Lng. Hex Bolt  
.250 Flat Washer Stl.  
.250 - 20 Elastic Stop Nut  
Step 5  
Trip Unit Mounting Platform Parts  
Trip Unit Support Bracket R. H.  
Trip Unit Support Bracket L. H.  
Trip Unit Mounting Platform  
.312 - 18 × .750 Lng. Screw Flat  
.312 - 18 × .750 Lng. Hex Bolt  
.312 Flat Washer Stl.  
4A35618G05  
1
1
1
1
4
4
12  
.312 Lock Washer Stl.  
.312 - 18 Nut Hex Stl.  
8
8
Step 6  
Trip Unit  
Rating Plug  
Aux. CT Module  
Aux. CT Harness  
1
1
1
1
1
1
1
1
1
2
2
6
8
8
1
2
4
2
2
5
See Pick List  
See Pick List  
6502C78G__  
6502C84G01  
4A35618G07  
Trip Unit Assembly Parts  
Mounting Bracket L. H.  
Mounting Bracket R. H.  
Barrier  
Digitrip Nameplate  
Spacer Brass  
.190 - 32 × 4.00 Lng. Screw Fil.  
.190 - 32 × .375 Lng. Screw Fil.  
.190 Flat Washer Stl.  
.190 Lock Washer Stl.  
PT Module Kit  
6502C82G01  
.138-32 × .500 Lng. Screw  
.138 Flat Washer  
.138 Lock Washer  
.138-32 Nut Hex Stl.  
Ring Terminals (.190, .250, .312, .375, .500), 3 Each Size  
Comm. Only  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 18  
IL 33-DAH-1  
Digitrip Retrofit Kit Installation Components for the Westinghouse DA-75 Breakers (Continued)  
Step  
Description  
Style No.  
Qty.  
Comment  
Step 7  
Trip Unit Assembly (From Step 6)  
Trip Unit Mounting Hardware  
.250 - 20 × .750 Lng. Hex Bolt  
.250 Flat Washer Stl.  
4A35618G08  
1
4
8
4
4
.250 Lock Washer Stl.  
.250 - 20 Nut Hex Stl.  
Step 8  
Step 9  
Breaker Trip Finger Parts  
Trip Finger  
4A35618G09  
4A35618G10  
1
1
2
4
2
2
.190-32 × 1.75 Lng. Screw Fil.  
.190 Flat Washer Stl.  
.190 Lock Washer Stl.  
.190 - 32 Nut Hex Stl.  
Breaker Reset Parts  
Reset Assembly  
1
1
2
4
2
2
.250 - 20 × 1.75 Lng. Hex Bolt  
.250 Flat Washer Stl.  
.250 Lock Washer Stl.  
.250 - 20 Nut Hex Stl.  
Step 10 DTA Assembly Parts  
High Force Trip Actuator  
DTA Mounting Hardware  
Mounting Bracket  
4A35618G11  
4A35618G33  
4A35618G12  
1
1
1
1
2
2
2
2
4
4
1
.312 - 18 × .750 Lng. Screw Flat  
.312 Flat Washer Stl.  
.312 Lock Washer Stl.  
.312 - 18 Nut Hex Stl.  
.164 - 32 × .312 Lng. Screw Pan Lock  
.164 Flat Washer Stl.  
Loc-Tite® 242  
Step 11 Terminal Block Parts  
4A35618G13  
1
1
2
4
2
2
2-Point Terminal Block  
.138 - 32 × .750 Lng. Screw Fil.  
.138 Flat Washer Stl.  
.138 Lock Washer Stl.  
.138 - 32 Nut Hex Stl.  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 19  
IL 33-DAH-1  
Digitrip Retrofit Kit Installation Components for the Westinghouse DA-75 Breakers (Continued)  
Step  
Step 12 Breaker Mounted CPT Kit  
Ring Terminals (.138, .190, .250, .312, .375, .500)  
Description  
Style No.  
Qty.  
Comment  
8259A91G05  
1
2
1
1
4
8
4
4
2
2
2
1
CPT Only  
Each Size CPT Only  
CPT Only  
CPT Mounting Parts  
4A35618G20  
Glass Poly Insulation Plate  
.190-32 × .500 Lng. Screw Fil.  
.190 Flat Washer Stl.  
.190 Lock Washer Stl.  
.190-32 Nut Hex Stl.  
.250-20 × .500 Lng. Hex Bolt  
.250 Flat Washer Stl.  
.250 Lock Washer Stl.  
Warning Label (208, 240, 480, & 600 Volt - 1 each)  
Step 13 Sensor Harness  
1
1
6
6
6
6
4
3
3
3
2
2
2
1
1
1
4
Sensor Harness Parts  
Wire Clamp Nylon  
4A35618G14  
.138 - 20 × .500 Lng. Screw T. C.  
.138 Flat Washer Stl.  
.138 Lock Washer Stl.  
Wire Clip  
.250 - 20 × .500 Lng. Hex Bolt  
.250 Flat Washer Stl.  
.250 Lock Washer Stl.  
.250-20 × .500 Lng. Hex Bolt  
.250 Flat Washer Stl.  
.250 Lock Washer Stl.  
DTA Extension Harness  
External Harness  
Comm. Only  
From Step 12  
6503C83G01  
6502C83G0__  
4A35618G15  
External Harness Parts  
Wire Clamp Nylon  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 20  
IL 33-DAH-1  
Wire Tie Nylon  
10  
Digitrip Retrofit Kit Installation Components for the Westinghouse DA-75 Breakers (Continued)  
Step  
Description  
Style No.  
Qty.  
Comment  
Step 14 Aux. Switch Kit  
Microswitch  
4A35618G02  
1
1
1
2
4
2
2
2
8
4
4
Mounting Bracket  
.164 - 32 × .500 Lng. Screw Fil.  
.164 Flat Washer Stl.  
.164 Lock Washer Stl.  
.164 - 32 Nut Hex Stl.  
.138 - 32 × 1.25 Lng. Screw Fil.  
.138 Flat Washer Stl.  
Comm. Only  
.138 Lock Washer Stl.  
.138 - 32 Nut Hex Stl.  
Step 15 Cell Harness  
6503C57G__  
1
Except 510 Basics  
NOTE: Due to the wide vintage of breakers and the multiple functions of the Retrofit components, some excess  
hardware may remain when the Retrofit is complete.  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 21  
IL 33-DAH-1  
Torque Values for General Mounting  
Decimal  
Size (in)  
Standard  
Size  
Torque  
(in-lbs)  
Torque  
(ft-lbs)  
.112  
.138  
.164  
.190  
.250  
.312  
.375  
.438  
.500  
4-40  
6-32  
8-32  
10-32  
1/4-20  
5/16-18  
3/8-16  
7/16-14  
1/2-13  
10  
18  
36  
0.8  
1.5  
3.0  
3.8  
8.3  
17.2  
29.7  
47.7  
71.3  
46  
100  
206  
356  
572  
856  
Torque Values for Copper BUS Connectors  
Decimal  
Size (in)  
Standard  
Size  
Torque  
(in-lbs)  
Torque  
(ft-lbs)  
.250  
.312  
.375  
.500  
1/4-20  
5/16-18  
3/8-16  
1/2-13  
60  
5
144  
240  
600  
12  
20  
50  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 22  
IL 33-DAH-1  
B
C
A
E
F
I
K
J
H
G
L
A. Sensors  
B. Trip Unit  
G. PT Module  
H. Sensor Harness  
C. Aux. CT Module  
D. Rating Plug  
I. DTA Extension Harness  
J. Aux. CT Harness  
E. Direct Trip Actuator (DTA)  
F. Aux. Switch  
K. External Harness  
L. Cell Terminal Block Assembly  
CPT Kit not pictured.  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 23  
IL 33-DAH-1  
Notes:  
Effective December, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 24  
IL 33-DAH-1  
We wish to thank you for purchasing the Digitrip Retrofit System. Digitrip Retrofit Kits are designed and manufactured in  
America with pride. All the components are engineered to fit the existing Circuit Breaker with little or no modifications to  
the existing Breaker. However due to the wide variety and vintage of Breakers in use today, an occasional problem may  
arise. Please contact us with any questions, comments or concerns.  
Phone: 1-800-937-5487  
Fax. (724) 779-5899  
The instructions for installation, testing, maintenance, or repair herein are provided for the use of the  
product in general commercial applications and may not be appropriate for use in nuclear applications. Additional  
instructions may be available upon specific request to replace, amend, or supplement these instructions to qualify  
them for use with the product in safety-related applications in a nuclear facility.  
The information, recommendations, descriptions, and safety notations in this document are based on  
Cutler-Hammer’s experience and judgement with respect to retrofitting of power breakers. This information should not  
be considered to be all inclusive or covering all contingencies. If further information is required, Cutler-Hammer should  
be consulted.  
NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR  
PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF  
TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS AND DESCRIPTIONS  
CONTAINED HEREIN. In no event will Cutler-Hammer be responsible to the user in contract, in tort (including  
negligence), strict liability or otherwise, for any special, indirect, incidental, or consequential damage or loss  
whatsoever, including but not limited to damage to or loss of use of equipment, plant or power system, cost of capital,  
loss of profits or revenues, cost of replacement power, additional expenses in the use of existing power facilities, or  
claims against the user by its customers resulting from the use of the information, recommendations, and descriptions  
contained herein.  
Cutler-Hammer  
130 Commonwealth Drive  
Warrendale, PA 15086  
Effective December, 1998  
Printed in U.S.A. - K  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 25  
IL 33-DAH-1  
INDEX  
Symbols  
K
2-Point Terminal Block 9  
510 Basic Retrofit Kits 13  
Kit Components Table 1  
M
A
Mounting the Cell Harness 15  
Auxiliary Switch 14  
P
B
Phase Convention 12  
PT Wires 12  
Breaker Mounted CPT 9  
C
R
Cell Harness 15  
CPT Terminals 10  
Racking Bar Adapter 16  
Removing the Original Electromechanical Trip Units 3  
Reset Arm Assembly 7  
Retrofit Kit Installation Components 17  
Retrofitted Breaker 16  
D
Drilling Plan “A” 5  
DTA Assembly 8  
DTA Extension Harness 13  
S
SAFETY PRECAUTIONS 1  
Sensor Style No. 11  
Sensors 4  
F
Final Connection of the Harnesses and Wiring 11  
T
G
Testing the Breaker 15  
General Breaker Preparation 3  
Glass Poly Insulation Plate 10  
Torque Values for Copper BUS Connectors 21  
Torque Values for General Mounting 21  
Trip Finger 7  
Trip Unit Assembly 6  
Trip Unit Mounting Platform 5  
H
HV Wires 12  
I
Installing the 2-Point Terminal Block 9  
Installing the Auxiliary Switch 14  
Installing the Breaker Mounted CPT 9  
Installing the DTA Assembly 8  
Installing the Reset Arm Assembly 7  
Installing the Retrofitted Breaker in the Cell 16  
Installing the Sensors 4  
Installing the Trip Finger 7  
Installing the Trip Unit 6  
Installing the Trip Unit Mounting Platform 5  
Effective January, 1998  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Western Digital Computer Drive WD1003FBYZ User Manual
Whirlpool Ventilation Hood GZ7730XGS1 User Manual
Whirlpool Washer 8182748 User Manual
Whistler Radar Detector XTR 140 User Manual
Woodstock Paint Sprayer W1793 User Manual
Zanussi Clothes Dryer TD163 User Manual
Zanussi Cooktop GC 20M User Manual
Zanussi Freezer 727009 User Manual
Zanussi Plumbing Product 132360 User Manual
Zenoah Brush Cutter YM 415 DW User Manual