Weil McLain Boiler 550 110 260 02002 User Manual

Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
Contents  
How it works.................................................................. 2–3  
Hazard definitions.............................................................. 4  
Please read before proceeding......................................... 5  
1. Prepare boiler location ............................................ 6–11  
2. Prepare boiler......................................................... 12–13  
3. Water piping........................................................... 14–23  
4. Venting & combustion air............................................ 24  
5. Gas piping .............................................................. 24–25  
6. Field wiring................................................................... 26  
7. Start-up .................................................................. 27–29  
8. Check-out procedure................................................... 30  
9. Operation ............................................................... 31–34  
10. Service and maintenance.................................... 35–40  
11. Troubleshooting .................................................. 41–51  
12. Replacement parts............................................... 52–57  
13. Dimensions and ratings ...................................... 58–59  
Hazard definitions  
The following defined terms are used throughout this manual to bring attention to the presence of hazards of  
various risk levels or to important information concerning the life of the product.  
Indicates presence of hazards that will cause severe personal injury, death or substantial  
property damage.  
Indicates presence of hazards that can cause severe personal injury, death or substantial  
property damage.  
Indicates presence of hazards that will or can cause minor personal injury or property damage.  
Indicates special instructions on installation, operation or maintenance that are important  
but not related to personal injury or property damage.  
4
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
Please read before proceeding  
Installer  
User  
Read all instructions before  
installing. Follow all instructions in  
proper order to prevent personal  
injury or death.  
This manual is for use only by your qualified  
heating installer/service technician.  
Please refer to the User’s Information Manual for  
your reference.  
We recommend regular service by a qualified  
service technician, at least annually.  
Also refer to CGs Venting Supplements.  
Consider piping and installation when  
determining boiler location.  
Any claims for damage or shortage in shipment  
must be filed immediately against the  
transportation company by the consignee.  
When calling or writing about the boiler— Please have the boiler model number from the  
boiler rating label and the CP number from the boiler jacket. You may list the CP number in  
the space provided on the Installation and service certificate found on page 30.  
Failure to adhere to the guidelines on this page can result in severe personal injury, death  
or substantial property damage.  
Continual fresh makeup water will reduce boiler  
life. Mineral buildup in sections reduces heat  
transfer, overheats cast iron, and causes section  
failure. Addition of oxygen and other gases can  
cause internal corrosion. Leaks in boiler or piping  
must be repaired at once to prevent makeup  
water.  
When servicing boiler —  
To avoid electric shock, disconnect electrical  
supply before performing maintenance.  
To avoid severe burns, allow boiler to cool before  
performing maintenance.  
Boiler operation —  
Do not add cold water to hot boiler. Thermal  
shock can cause sections to crack.  
Do not block flow of combustion or ventilation  
air to boiler.  
Should overheating occur or gas supply fail to  
shut off, do not turn off or disconnect electrical  
supply to circulator. Instead, shut off the gas Glycol — potential fire hazard —  
supply at a location external to the appliance.  
All glycol is flammable when exposed to high  
Do not use this boiler if any part has been under  
temperatures. If glycol is allowed to accumulate in  
water. Immediately call a qualified service  
or around the boiler or any other potential ignition  
technician to inspect the boiler and to replace any  
source, a fire can develop. In order to prevent  
part of the control system and any gas control  
potential severe personal injury, death or substantial  
that has been under water.  
property damage from fire and/or structural damage:  
Never store glycol of any kind near the boiler or  
any potential ignition source.  
Monitor and inspect the system and boiler  
regularly for leakage. Repair any leaks  
immediately to prevent possible accumulation  
of glycol.  
Boiler water —  
Do not use petroleum-based cleaning or sealing  
compounds in boiler system. Water seal  
deterioration will occur, causing leakage between  
sections. This can result in substantial property  
damage.  
Never use automotive antifreeze or ethylene  
glycol in the system. Using these glycols can lead  
to hazardous leakage of glycol in the boiler  
system.  
Do not use "homemade cures" or "boiler patent  
medicines". Serious damage to boiler, personnel  
and/or property may result.  
5
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
1a  
Prepare boiler location — codes & checklist  
Installations must  
Local, state, provincial, and national codes, laws, regulations and  
ordinances.  
follow these codes:  
National Fuel Gas Code, ANSI Z223.1 – latest edition.  
Standard for Controls and Safety Devices for Automatically Fired  
Boilers, ANSI/ASME CSD-1, when required.  
National Electrical Code.  
For Canada only: B149.1 or B149.2 Installation Code, CSA C22.1  
Canadian Electrical Code Part 1 and any local codes.  
The CGs boiler gas manifold and controls met safe  
lighting and other performance criteria when boiler  
underwent tests specified in ANSI Z21.13 — latest  
edition.  
Before locating the boiler,  
check the following:  
Check for nearby connection to:  
System water piping  
Venting connections  
Gas supply piping  
Electrical power  
Check area around boiler. Remove any combustible materials, gasoline  
and other flammable liquids.  
Failure to keep boiler area clear and free of combustible  
materials, gasoline and other flammable liquids and  
vapors can result in severe personal injury, death or  
substantial property damage.  
Boiler must be installed so that gas control system components are  
protected from dripping or spraying water or rain during operation  
or service.  
If new boiler will replace existing boiler, check for and correct system  
problems, such as:  
1. System leaks causing oxygen corrosion or section cracks from  
hard water deposits.  
2. Incorrectly-sized expansion tank.  
3. Lack of antifreeze in boiler water causing system and boiler to  
freeze and leak.  
6
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
1b  
Prepare boiler location — clearances  
Provide the following clearances: Flooring and foundation  
Flooring  
1. Hot water pipes — at least ½" from combustible  
materials.  
The CGs boiler is approved for installation on  
combustible flooring, but must never be installed on  
carpeting.  
2. Recommended service clearances — See Figure 1.  
3. Minimum clearances for tight spaces — See  
Figure 2.  
Do not install boiler on carpeting  
even if foundation is used. Fire can  
result, causing severe personal  
injury, death or substantial property  
damage.  
Figure 1 Recommended clearances for service  
Foundation  
Provide a solid brick or minimum 2-inch thick  
concrete foundation pad if any of the following is true:  
floor can become flooded.  
the boiler mounting area is not level.  
The minimum foundation size is 25" long by:  
Boiler model number  
CGs-3  
Width — Inches  
15  
18  
21  
24  
Figure 2 Minimum clearances for tight spaces  
CGs-4  
CGs-5  
CGs-6  
Residential garage installation  
Precautions  
Take the following special precautions when installing  
the boiler in a residential garage. If the boiler is located  
in a residential garage, per ANSI Z223.1, paragraph  
5.1.9:  
Mount the boiler a minimum of 18 inches  
above the floor of the garage to assure the  
burner and ignition devices will be no less  
than 18 inches above the floor.  
Locate or protect the boiler so it cannot be  
damaged by a moving vehicle.  
7
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
1c  
Prepare boiler location — vent system  
appliance to their previous conditions of use.  
Removing from existing vent  
Any improper operation of common venting system  
Do not install the CGs into a  
common vent with any other  
appliance. This will cause flue gas  
spillage or appliance malfunction,  
should be corrected so the installation conforms with  
the National Fuel Gas Code, ANSI Z223.1 — latest  
edition. Correct by resizing to approach the minimum  
size as determined using the appropriate tables in Part  
resulting in possible severe personal 11 of that code. Canadian installations must comply  
injury, death or substantial property  
damage.  
with B149.1 or B149.2 Installation Code.  
Failure to follow all instructions can  
result in flue gas spillage and carbon  
monoxide emissions, causing  
severe personal injury or death.  
CGs special vent system  
Ventsystem  
The CGs boiler requires a special vent system, designed  
for pressurized venting. Model CGs-3 is rated ANSI  
Z21.13 Category IV (pressurized vent, likely to  
condense in the vent). Models CGs-4, -5 and -6 are rated  
Z21.13 Category III (pressurized vent).  
Whenremovingboilerfromexisting  
commonventsystem:  
At the time of removal of an existing boiler, the  
following steps shall be followed with each appliance  
remaining connected to the common venting system  
placed in operation, while the other appliances  
remaining connected to the common venting system  
are not in operation.  
You may use any of the vent systems covered by the  
CGs Venting Supplements included in the envelope  
assembly. The CGs vent starter is a special item, designed  
only for the CGs boiler, available from each vendor.  
Do not attempt to connect the vent to the CGs boiler  
with any other means.  
a. Seal any unused openings in the common venting  
DO NOT mix components from  
different systems. The vent system  
could fail, causing leakage of flue  
products into the living space.  
system.  
b. Visually inspect the venting system for proper  
size and horizontal pitch and determine there is  
no blockage or restriction, leakage, corrosion or  
other deficiencies which could cause an unsafe  
condition.  
Ventterminationand  
combustionairsupply  
c. Test vent system — Insofar as is practical, close  
all building doors and windows and all doors  
between the space in which the appliances  
remaining connected to the common venting  
system are located and other spaces of the building.  
Turn on clothes dryers and any appliance not  
connected to the common venting system. Turn on  
any exhaust fans, such as range hoods and  
bathroom exhausts, so they will operate at  
maximum speed. Do not operate a summer exhaust  
fan. Close fireplace dampers.  
The CGs boiler may be vented through the roof or  
through a side wall. Follow the appropriate vent  
supplement for the vent system chosen. The maximum  
vent length depends on boiler size. Refer to the vent  
supplement to determine acceptable vent length.  
Combustion air for the CGs boiler may be from inside  
or ducted directly to the boiler from outside. For  
outside air (direct vent installation), two options are  
available for the flue/air termination. The air supply  
must ALWAYS terminate at the same location as the  
d. Place in operation the appliance being inspected. flue, using either:  
Follow the lighting instructions. Adjust thermostat  
so appliance will operate continuously.  
1. Vertical direct vent installation. Obtain the Weil-  
McLain Through-Roof or Through-Unused  
Chimney termination kit and supplement. Refer to  
Vertical DirectVentingVenting Supplement,packed  
with the kit, and to the vent manufacturer’s  
instructions for the vent material chosen.  
e. Test for spillage at draft hood relief opening after  
5 minutes of main burner operation. Use the flame  
of a match or candle, or smoke from a cigarette,  
cigar, or pipe.  
f. After it has been determined that each appliance 2. Sidewall direct vent installation. Use the Vent/Air  
remaining connected to the common venting  
system properly vents when tested as outlined  
above, return doors, windows, exhaust fans,  
fireplace dampers, and any other gas-burning  
Intake termination kit shipped with the boiler.  
Refer to CGs Direct Venting: Sidewall & Direct  
Exhaust Venting: Vertical or Sidewall Venting  
Supplement shipped with the boiler.  
8
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
1d  
Prepare boiler location — contamination  
Air contamination  
Refer to Table 1 for products and areas which may cause  
contaminated combustion air.  
Please review the following information on potential  
combustion air contamination problems.  
If the boiler is installed in any area likely to cause contamination, or if products which  
would contaminate the air cannot be removed, you must pipe combustion air to the boiler  
air intake. Contaminated combustion air will damage the boiler, resulting in possible severe  
personal injury, death or substantial property damage. Do not install CGs boiler in a laundry  
room or pool facility, for example, without using ducted outside air. These areas will always  
contain contaminants.  
Table 1 Corrosive contaminants  
Products to avoid  
Areas likely to have contaminants  
Spray cans containing chloro/fluorocarbons  
Permanent wave solutions  
Dry cleaning/laundry areas and establishments  
Swimming pools  
Chlorinated waxes/cleaners  
Metal fabrication plants  
Beauty shops  
Chlorine-based swimming pool chemicals  
Calcium chloride used for thawing  
Sodium chloride used for water softening  
Refrigerant leaks  
Refrigeration repair shops  
Photo processing plants  
Auto body shops  
Paint or varnish removers  
Plastic manufacturing plants  
Furniture refinishing areas and establishments  
New building construction  
Remodeling areas  
Hydrochloric acid/muriatic acid  
Cements and glues  
Antistatic fabric softeners used in clothes dryers  
Chlorine-type bleaches, detergents, and cleaning  
solvents found in household laundry rooms  
Garages with workshops  
Adhesives used to fasten building products and  
other similar products  
9
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
1e  
Prepare boiler location — air openings  
CGs combustion air options  
Louverallowance  
Using inside air — direct exhaust vent  
The free area of openings means the area after  
reduction for any installed louvers or grilles. Be sure  
The CGs boiler can use inside air if no contaminants to consider this reduction when sizing the air openings.  
are present in the boiler space. If contaminants are likely  
to be present, install the CGs boiler as a direct vent  
appliance, using the appropriate vent supplement and  
the instructions in this manual.  
Special considerations  
Using outside air — direct vent  
Tightconstruction  
Combustion air can be ducted directly from outside  
to the CGs boiler air intake fitting. This method is  
ANSI Z223.1 defines unusually tight construction  
where:  
defined as direct vent (also referred to as sealed  
combustion). Refer to the appropriate vent supplement  
and the instructions in this manual. Two options are  
a. Walls and ceilings exposed to the outside  
available: sidewall or vertical direct vent. Each requires  
atmosphere have a continuous water vapor retarder  
a special vent component kit.  
with a rating of 1 perm or less with openings  
gasketed, and . . .  
b. Weather-stripping has been added on openable  
windows and doors, and . . .  
c. Caulking or sealants are applied to areas such as  
joints around windows and door frames, between  
sole plates and floors, between wall-ceiling joints,  
Sizing air openings  
between wall panels, at penetrations for plumbing,  
electrical, and gas lines, and in other openings.  
Air openings provide for ventilation (as well as  
combustion air) to prevent overheating of the boiler  
controls and boiler space. Air is also needed for other  
appliances located in the same space.  
For buildings with such construction, provide air  
openings into the building from outside, sized per the  
appropriate case in Figure 3 if appliances are to use  
inside air for combustion and ventilation.  
Use Figure 3, selecting the appropriate installation  
conditions. Note that the sizing given in Figure 3  
applies only to CGs installations with clearances no  
smaller than shown in Figure 1, page 7 of this manual.  
For smaller clearances, regardless of how the air  
openings are arranged, two openings providing free  
area of 1 square inch per 1,000 Btuh input of all  
appliances in the space are required.  
Exhaust fans and air movers  
The appliance space must never be under a negative  
pressure unless all appliances are installed as direct vent.  
Always provide air openings sized not only to the  
dimensions required for the firing rate of all appliances,  
but also to handle the air movement rate of the exhaust  
fans or air movers using air from the building or space.  
Air openings must be sized to  
handle all appliances and air  
movers (exhaust fans, etc.) using the  
air supply.  
Motorizedairdampers  
The sizing given in Figure 3 is based on the National  
Fuel Gas Code, ANSI Z223.1, allowing adequate air  
opening for gravity-vented gas appliances (Category I).  
The CGs boiler is rated Category III or IV (pressurized  
vent), and has different requirements for combustion  
and ventilation air, reflected by the special sizing  
instructions given in Figure 3. The air openings  
recommended in Figure 3 will allow adequate  
ventilation and combustion air provided the boiler  
room is not subjected to negative pressure due to  
exhaust fans or other mechanical ventilation devices.  
Refer to the National Fuel Gas Code for dealing with  
other conditions.  
If the air openings are fitted with motorized dampers,  
electrically interlock the damper to:  
Prevent the boiler from firing if the damper is not  
fully open.  
Shut the boiler down should the damper close  
during boiler operation.  
To accomplish this interlock, wire an isolated contact  
(proving the damper open) in series with the  
thermostat input to the boiler. The boiler will not start  
if this contact is open, and will shut down should it  
open during operation.  
10  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
Figure 3 Sizing air openings for CGs installations  
Room Air Openings  
Required area of the air openings given in this  
table are free area — after the correction for  
louver obstruction. (See Exception below.)  
Direct exhaust vent installation  
Direct vent installation  
(CGs using room air for combustion)  
(combustion air piped to CGs)  
Combustion  
air piping  
Combustion  
air piping  
Apply this table only to installations with  
clearances no smaller than those shown in  
Figure 1, page 7 of this manual.  
Other  
appliances  
Other  
appliances  
CGs  
CGs  
CGs  
CGs  
For installations with clearances less than  
shown in Figure 1, page 7 of this manual,  
provide 2 openings, each with 1 square inch  
of free area per 1,000 Btuh of total input of  
all appliances.  
Room shared  
with other appliances  
Room shared  
with other appliances  
CGs alone  
in room  
CGs alone  
in room  
2 Openings —  
each opening:  
2 Openings —  
each opening:  
2 Openings —  
each opening:  
NO Openings are  
needed, provided:  
12”  
Max  
A Air from Inside  
Air  
opening  
1 square inch  
1 square inch  
1 square inch  
free area per  
free area per  
free area per  
Clearance around  
boiler is NO LESS  
than shown in  
Figure 1, page 7  
of this manual.  
1,000 Btuh input of  
other appliances  
plus CGs  
4,000 Btuh input  
of CGs  
1,000 Btuh input of  
other appliances  
only (not CGs)  
Air  
opening  
CGs  
12”  
Max  
2 Openings —  
each opening:  
2 Openings —  
each opening:  
2 Openings —  
each opening:  
NO Openings are  
needed, provided:  
12”  
Max  
B Air Directly  
from Outside  
Air  
opening  
1 square inch  
1 square inch  
1 square inch  
free area per  
free area per  
free area per  
Clearance around  
boiler is NO LESS  
than shown in  
Air  
4,000 Btuh input of  
other appliances  
plus CGs  
4,000 Btuh input  
of CGs  
4,000 Btuh input of  
other appliances  
only (not CGs)  
opening  
CGs  
12”  
Figure 1, page 7  
of this manual.  
Max  
Duct  
Duct  
2 Openings —  
each opening:  
2 Openings —  
each opening:  
2 Openings —  
each opening:  
NO Openings are  
needed, provided:  
12”  
C Air from Outside  
Through horizontal  
ducts  
Max  
Air  
opening  
1 square inch  
1 square inch  
1 square inch  
free area per  
free area per  
free area per  
Clearance around  
boiler is NO LESS  
than shown in  
Figure 1, page 7  
of this manual.  
2,000 Btuh input of  
other appliances  
plus CGs  
4,000 Btuh input  
of CGs  
2,000 Btuh input of  
other appliances  
only (not CGs)  
Air  
opening  
CGs  
12”  
Max  
Outside or ventilated attic  
2 Openings —  
each opening:  
2 Openings —  
each opening:  
2 Openings —  
each opening:  
NO Openings are  
needed, provided:  
D Air from Outside or Attic —  
Lower Opening in Floor  
or Vertical Duct  
Duct  
1 square inch  
1 square inch  
1 square inch  
free area per  
free area per  
free area per  
Clearance around  
boiler is NO LESS  
than shown in  
Figure 1, page 7  
of this manual.  
CGs  
12”  
Max  
4,000 Btuh input of  
other appliances  
plus CGs  
4,000 Btuh input  
of CGs  
4,000 Btuh input of  
other appliances  
only (not CGs)  
Or  
Ventilated  
crawl space  
26007  
NOcombustion air openings are needed when the boiler (and other appliances) are installed in a space with a volume  
NO LESS than 50 cubic feet per 1,000 Btuh of all installed appliances. Sum the total input of all appliances in MBH  
(1,000'sofBtuh) andmultiply thisnumber times 50. Building must notbeof Tightconstruction(seepage10).  
Exception to  
combustion air  
opening rules:  
Example: For total input of 100 MBH (100,000 Btuh), minimum volume is 50 x 100 = 5,000 cubic feet. At a ceiling  
height of8feet, spacemust haveatleast5,000 ÷ 8 =625square feet(25feetx25feet, forinstance).  
11  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
2a  
Prepare boiler — placement & setup  
Place boiler/crate near position  
death or substantial property  
damage.  
1. Leave boiler in crate and on pallet until installation  
site is ready.  
3. Reinstall inlet air box top panel.  
Inlet air box top panel must be in  
2. Move entire crate and pallet next to selected  
location.  
position during boiler operation.  
Failure to do so could result in  
severe personal injury, death or  
substantial property damage.  
3. Remove crate.  
4. Remove boiler from pallet.  
Do not drop boiler or bump jacket  
on floor or pallet. Damage to boiler  
can result.  
Orifice replacement procedure  
(when required)  
1. Remove the screws securing the inlet air box top  
panel.  
a. Tilt left side of boiler up and place a board  
under left legs.  
2. Remove inlet air box top panel and inspect the fiber  
gasket. Verify the gasket is in good condition and  
can seal around the complete perimeter of the air  
box. Replace the gasket if necessary.  
b. Tilt boiler the other way and place a board  
under right legs.  
c. Slide boiler backward off pallet and into  
position.  
7
3. Using a /16" open-end wrench, remove the burner  
orifices from the manifold.  
5. Check level.  
4. Apply a small amount of pipe dope to each of the  
new orifices and install in the manifold using a 7/16"  
open-end wrench. Make sure the orifices are aligned  
correctly, not cross-threaded in the manifold  
tappings.  
a. Shim legs, if necessary.  
b. Do not alter legs.  
Use only pipe dope compatible with  
propane gas, even if boiler is to be  
operated on natural gas. Failure to  
comply could result in severe  
personal injury, death or substantial  
property damage.  
Inspect orifices and burners  
1. Remove front jacket door. Remove inlet air box  
top panel (see Figure 27, item 13, page 54).  
2. Check for correctly-sized manifold orifices. See 5. Carefully replace the inlet air box top panel, making  
Table 2 for sizing. (The orifice size is stamped on  
the orifice spud barrel.)  
sure the gasket is in place will seal all around the  
perimeter.  
Correctly-sized manifold orifices 6. Follow the check-out procedure, section 8 page 30,  
must be used. Failure to do so will  
result in severe personal injury,  
to assure the boiler is now operating properly after  
orifices are replaced.  
Table 2 Manifold orifice sizing  
Location  
U. S.  
Natural gas  
Propane gas  
0-2,000 ft  
over 2,000 ft  
(Note 1)  
0-2,000 ft  
1.65 mm  
0-2,000 ft  
1.65 mm  
over 2,000 ft  
(Note 1)  
2.70 mm  
0-2,000 ft  
2.70 mm  
2,000-4,500  
#38  
2,000-4,500  
#53  
Canada  
Note 1: For elevations above 2,000 feet, contact your local Weil-McLain sales office for details.  
12  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
2b  
Prepare boiler — pressure test  
Perform hydrostatic pressure test  
Pressure test boiler before attaching water or gas piping (except as noted below) or electrical  
supply.  
Prepare boiler for test  
1. Remove the shipping nipple (from CGs supply tapping) and remove the boiler relief  
valve. Temporarily plug the relief valve tapping with a ¾" NPT pipe plug.  
2. Remove 1¼" nipple, reducing tee and drain valve from accessory bag. Install in boiler  
return connection as shown on page 3 and Figure 29, page 56. Install circulator on either  
the return or supply.  
3. Remove 1¼" nipple, 1¼" tee, bushing and pressure/temperature gauge from accessory  
bag. Pipe to boiler supply connection as shown on page 3 and Figure 29, page 56. (Use  
pipe dope sparingly.)  
4. Connect a hose to boiler drain valve, the other end connected to a fresh water supply.  
Make sure hose can also be used to drain boiler after test.  
5. Connect a nipple and shutoff valve to system supply connection on the 1¼" tee. This  
valve will be used to bleed air during the fill. (Valve and nipple are not included with  
boiler.)  
6. Connect a nipple and shutoff valve to system return connection (at circulator flange if  
circulator installed on return). This valve will be used to bleed air during the fill. (Valve  
and nipple are not included with boiler.)  
Fill and pressure test  
1. Open the shutoff valves you installed on supply and return connections.  
2. Slowly open boiler drain valve and fresh water supply to fill boiler with water.  
3. When water flows from shutoff valves, close boiler drain valve.  
4. Close shutoff valves.  
5. Slowly reopen boiler drain valve until test pressure on the pressure/temperature gauge  
reaches no more than:  
45 psig for boilers with 30 psig relief valve.  
75 psig for boilers with 50 psig relief valve.  
6. Test for no more than 10 minutes at:  
45 psig for boilers with 30 psig relief valve.  
75 psig for boilers with 50 psig relief valve.  
Do not leave boiler unattended. A cold water fill could expand and cause  
excessive pressure, resulting in severe personal injury, death or substantial  
property damage.  
7. Make sure constant gauge pressure has been maintained throughout test. Check for leaks.  
Repair if found.  
Leaks must be repaired at once. Failure to do so can damage boiler,  
resulting in substantial property damage.  
Do not use petroleum-based cleaning or sealing compounds in boiler  
system. Severe damage to boiler will occur, resulting in substantial property  
damage.  
Drain and remove fittings  
1. Disconnect fill water hose from water source.  
2. Drain boiler at drain valve or out hose, whichever provides best access to drain. Remove  
hose after draining if used to drain boiler.  
3. Remove nipples and valves unless they will remain for use in the system piping.  
4. Remove plug from relief valve tapping. See section 3a to replace relief valve.  
13  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
3a  
Water piping — general information  
General piping information  
Circulator  
If installation is to comply with ASME or Canadian requirements, an  
additional high temperature limit is needed. Install control in supply  
piping between boiler and isolation valve. Set second control to minimum  
20 °F above setpoint of first control. Maximum allowable setpoint is 240 °F.  
See section 9b, page 32 for wiring.  
The circulator is shipped loose (wiring pre-attached  
to boiler) to allow you to locate it either in the return  
or supply piping, as desired. See page 3 for a typical  
installation. Pipe the expansion tank to the suction side  
of the circulator whenever possible. Install an air  
separator in the supply piping. Connect the expansion  
tank to the air separator only if the separator is on the  
suction side of the circulator. Always install the system  
fill connection at the same point as the expansion tank  
connection to the system. Figures 4 and 5 show typical  
near-boiler piping connections.  
A low water cutoff device is required when boiler is installed above  
radiation level or by certain state or local codes or insurance companies.  
Use low water cutoff designed for water installations. Electrode probe-  
type is recommended. Purchase and install in tee in supply piping above  
boiler.  
Use backflow check valve in cold water supply as required by local codes.  
System water piping  
Pressure/temperature gauge  
See Figure 4 (diaphragm-type or bladder-type  
expansion tank) or Figure 5 (closed-type expansion  
tank) on page 15, and Table 3 below, for near-boiler  
and single-zone systems designed for return water at  
least 130 °F.  
Install pressure/temperature gauge in tee on supply piping (as shown in  
drawing on page 3). The gauge well is a self-closing valve, allowing removal  
of the gauge without draining the system.  
Slowly remove pressure/temperature gauge from well.  
The self-closing valve could leak if clogged with  
sediment. If water begins to spray, stop removing gauge.  
Close system fill valve and drain enough water to release  
system pressure before continuing with gauge removal.  
Escaping hot water could cause severe personal injury.  
See pages 16-17 to complete multiple-zone piping or  
pages 18-23 to complete piping for radiant heating  
systems or converted gravity systems.  
Refer to page 23 for boilers used with refrigeration systems.  
Table 3 Water pipe size (based on 20 °F rise)  
Relief valve  
Install relief valve vertically in ¾" tapping on side of boiler. See Figure 4  
or 5 and the tag attached to the relief valve for manufacturer’s instructions.  
Boiler  
model  
To  
system  
From  
system  
number  
To avoid water damage or scalding due to relief valve  
operation:  
CGs-3  
CGs-4  
CGs-5  
CGs-6  
1"  
1"  
1"  
1"  
Discharge line must be connected to relief valve outlet and run to a  
safe place of disposal. Terminate the discharge line to eliminate  
possibility of severe burns should the valve discharge.  
1"  
1"  
1 ¼"  
1 ¼"  
Discharge line must be as short as possible and be the same size as  
the valve discharge connection throughout its entire length.  
Note: Circulator flange supplied with boiler is same size as  
recommended piping above.  
Discharge line must pitch downward from the valve and terminate at  
least 6" above the floor drain where any discharge will be clearly visible.  
Install boiler such that —  
The discharge line shall terminate plain, not threaded, with a material  
serviceable for temperatures of 375 °F or greater.  
Chilled medium, if used, is piped in parallel with  
heating boiler. Use appropriate valves to prevent  
chilled medium from entering boiler. Consult  
I=B=R Installation and Piping Guides.  
Do not pipe the discharge to any place where freezing could occur.  
No shutoff valve shall be installed between the relief valve and boiler,  
or in the discharge line. Do not plug or place any obstruction in the  
discharge line.  
If boiler is connected to heating coils located in air  
handling units where they can be exposed to  
refrigerated air, use flow control valves or other  
automatic means to prevent gravity circulation  
during cooling cycle. Circulation of cold water  
through the boiler could result in damage to the  
heat exchanger, causing possible severe personal  
injury, death or substantial property damage.  
Failure to comply with the above guidelines could result in failure of  
the relief valve to operate, resulting in possibility of severe personal  
injury, death or substantial property damage.  
Test the operation of the valve after filling and pressurizing system  
by lifting the lever. Make sure the valve discharges freely. If the valve  
fails to operate correctly, replace it with a new relief valve.  
14  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
3b  
Water piping — single-zone system  
Expansion tank  
Closed-type expansion tank —  
Diaphragm-typeorbladder-type  
expansion tank — Figure 4  
Figure 5  
1. Ensure expansion tank size will handle boiler and  
system water volume and temperature. See tank  
manufacturer’s instructions for details.  
1. Ensure expansion tank size will handle boiler and  
system water volume and temperature. Tank must  
be located in boiler return piping as close to boiler 2. Connect tank to ½" NPT tapping located behind  
as possible, before inlet side of circulator. See tank  
manufacturer’s instructions for details.  
2. Install an automatic air vent in air vent tapping as  
shown.  
supply outlet, using ½" NPT piping. Pitch any  
horizontal piping up towards tank 1 inch per 5 feet  
of piping.  
Undersized expansion tanks cause system water to be lost from relief valve and makeup water  
to be added through fill valve. Eventual section failure can result.  
Use Figure 4 or Figure 5 only for single-zone systems designed for return water at least 130 °F.  
For systems with low return water temperature possible, such as converted gravity systems  
and radiant heating systems, refer to the special piping suggestions of pages 18-23. Failure to  
prevent low return water temperature to the boiler could cause corrosion of the boiler sections  
or burners, resulting in severe personal injury, death or substantial property damage.  
Figure 4 Diaphragm- or bladder-type expansion tank  
Figure 5 Closed-type expansion tank  
Piping to single-zone system using  
diaphragm-type or bladder-type expansion  
tank. See Table 3 for piping sizes.  
Piping to single-zone system using closed-  
type expansion tank. See Table 3 for piping  
sizes.  
Cold  
water  
fill  
From  
system  
CLOSED-type  
expansion tank  
To DIAPHRAGM  
expansion tank  
and fittings  
From  
Cold water fill  
system  
Isolation  
valve  
Isolation  
valve  
Isolation  
valve  
Isolation  
valve  
Relief  
valve  
To system  
Circulator*  
To system  
Relief  
valve  
Circulator*  
Automatic  
air vent  
Circulator  
Drain  
valve  
Drain  
valve  
Circulator  
*Alternate  
location  
*Alternate  
location  
26010  
26011  
15  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
3c  
Water piping — multiple zones  
Piping multiple zones  
Follow instructions on pages 14 and 15 to install near-boiler or single-zone piping. (Also  
refer to Piping for radiant heating systems or converted gravity systems, below, if  
applicable.)  
See Figure 6 or Figure 7 to complete installation.  
1. Size each circulator to individual circuit requirements.  
Zoning with  
circulators, return  
temp over 130 °F  
2. Do not install circulator on boiler (except for primary/secondary piping).  
3. Install isolation (balancing) valves to adjust flow to distribute heat to all zones.  
4. Install and wire a separate relay for each zone circulator.  
1. Install isolation (balancing) valves to adjust flow to distribute heat to all zones.  
Zoning with zone  
valves, return temp  
over 130 °F  
2. Provide a separate 24-volt transformer to power the zone valves. Size the transformer to  
handle the total rated load of all connected zone valves.  
Converted gravity (or steam) systems  
Piping for radiant  
heating systems or  
converted gravity  
systems  
Whenever possible, use the primary/secondary piping shown in Figures 8 or 9 on page 19.  
This piping design allows changing boiler flow rate without affecting primary circuit flow  
rate.  
If Figures 8 or 9 cannot be used, use the boiler-bypass piping shown in Figure 10 or Figure  
11 on page 21. You can also use the piping shown in Figure 12 on page 23 (system-bypass), if  
the reduced flow rate in the heating system will not cause heat distribution problems.  
Failure to prevent low return water temperature to the boiler could cause corrosion of the  
boiler sections or burners, resulting in severe personal injury, death or substantial property  
damage.  
Radiantheatingsystems  
Preferably, use primary/secondary piping, as shown in Figures 8 or 9 on page 19.Alternatively,  
use the method of either Figure 10 or Figure 11 on page 21. Do not use the piping of Figure  
12 (system-bypass), because this method does not control radiant system supply temperature.  
If radiant system tubing has no oxygen barrier, a heat exchanger must be used.  
Radiant heating system piping should include a means of regulating the boiler return water  
temperature and the system supply temperature (such as provided by an injection pumping  
control). Boiler return water temperature will be adequately controlled using the methods  
shown in this manual provided the system supply temperature is relatively constant.  
Do not apply the methods in this manual if the system is equipped with an outdoor reset  
control. Instead, provide controls and piping which can regulate the boiler return water  
temperature at no less than 130 °F regardless of system supply temperature. Contact your  
Weil-McLain representative for suggested piping and control methods. Failure to prevent  
cold return water temperature to the boiler could cause corrosion damage to the sections or  
burners, resulting in possible severe personal injury, death or substantial property damage.  
16  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
typical piping — multiple-zone installations  
Figure 6  
Figure 7  
Zoning with circulators  
— return water 130 °F or higher.  
Zoning with zone valves  
— return water 130 °F or higher.  
ZONE 2  
ZONE 2  
ZONE 1  
ZONE 1  
1
1
2
1
1
5
3
2
1
1
13  
13  
10  
6
6
6
6
1
1
Alternate  
circulator  
location  
9
9
10  
11  
12  
Cold  
water  
fill  
11  
12  
Cold  
water  
fill  
26012  
26013  
1
2
3
5
6
9
Boiler isolation (balancing) valves  
Flow/check valve  
System or zone circulator  
Zone valve  
air vent when using closed-type expansion tank. It  
would allow air to leave the system, causing  
waterlogging of the expansion tank.  
11 Fill valve  
12 Diaphragm-type or bladder-type expansion tank,  
if used (For closed-type expansion tank, pipe from  
top of air separator to tank fitting as in Figure 5.)  
Drain valve  
Relief valve  
13 Air separator and automatic vent, if used (Note that  
the fill valve must always be connected to the  
expansion tank, regardless of location of expansion  
tank circulator or air separator.  
10 Automatic air vent (with diaphragm-type  
expansion tank), or connect to tank fitting (closed-  
type expansion tank). DO NOT use an automatic  
For systems with possible low return-water temperature (such as converted gravity systems,  
radiant heating systems and heat pump systems), refer to the special piping suggestions of  
Figures 8 - 12, as applies. Failure to prevent sustained low return water temperature to the  
boiler could cause corrosion of the boiler sections, resulting in severe personal injury, death  
or substantial property damage.  
17  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
3d  
Water piping — low temp systems  
Primary/secondary  
(preferred) bypass  
piping method  
Primary/secondary bypass piping is preferred because the flow rate and temperature drop in  
the heating circuit(s) is determined only by the heating circuit circulator(s). So adjustment  
of the bypass valves in the boiler circuit will not cause a change in the heating circuit rate and  
temperature distribution.  
Figures 8 and 9 show suggested bypass arrangements using primary/secondary bypass piping  
(preferred) for low temperature systems such as radiant heating systems or converted gravity  
systems. For alternatives, see pages 20 through 23.  
The bypass valves (items 7a and 7b) provide mixing of hot boiler outlet water with cooler  
system return water — set to assure a minimum return water temperature (at least 130 °F) to  
the boiler. Set the valves as explained below.  
Gauge 4a is suggested, but optional on any system.  
Temperature gauges  
Gauge 4b is optional on converted gravity systems, but required on radiant heating systems  
— to display the water temperature being supplied to the radiant tubing.  
Gauge 8 is required on all systems to assure the return water temperature is accurately set for  
a minimum of 130 °F. If this gauge is not available however, adjust the valves such that the  
boiler-mounted temperature/pressure gauge reads at least 150 °F when the system return  
water is cold (approximately 60 °F water temperature).  
Valve adjustment  
(Figure 12 and 13 only)  
1. Set the valves while the system is cool, setting for the coldest expected water temperature  
(usually 60 °F since the system will often drop to room temperature between cycles).  
2. Start with valve 7a fully closed and 7b fully open.  
3. Gradually open valve 7a while closing valve 7b until the temperature at gauge 8 reads  
130 °F when gauge 4a reads 60 °F.  
4. Note that valve 7a regulates the amount of hot water from the boiler supply which mixes  
with return water. Valve 7b regulates the amount of system water flowing through the  
boiler secondary loop.  
Failure to prevent low return water temperature to the boiler could cause corrosion of  
the boiler sections or burners, resulting in severe personal injury, death or substantial property  
damage.  
Radiant heating system piping should include a means of regulating the boiler return  
water temperature and the system supply temperature (such as provided by an injection  
pumping control).  
Boiler return water temperature will be adequately controlled using the methods shown in  
this manual provided the system supply temperature is relatively constant.  
DO NOT apply the methods of this manual if the system is equipped with an outdoor  
reset control. Instead, provide controls and piping which can regulate the boiler return  
water temperature at no less than 130 °F regardless of system supply temperature. Contact  
your Weil-McLain representative for suggested piping and control methods.  
Failure to prevent cold return water temperature to the boiler could cause corrosion  
damage to the sections or burners, resulting in possible severe personal injury, death or  
substantial property damage.  
18  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
primary/secondary (preferred) bypass piping —  
for radiant heating or converted gravity systems  
Figure 8  
Figure 9  
Zoning with circulators  
Zoning with zone valves  
ZONE 2  
ZONE 1  
ZONE 2  
ZONE 1  
1
5
1
1
2
1
4a  
4b  
4a  
4b  
12"  
MAX.  
12"  
MAX.  
3
3
2
1
1
13  
1
13  
1
6
7b  
6
6
6
7b  
7a  
7a  
9
Alternate  
circulator  
location  
Alternate  
circulator  
location  
8
8
10  
9
10  
11  
12  
11  
12  
Cold  
water  
fill  
Cold  
water  
fill  
26014  
26015  
1
2
3
4
5
6
7
Boiler isolation (balancing) valves  
Flow/check valve  
10 Automatic air vent (with diaphragm-type expansion  
tank), or connect to tank fitting (closed-type expansion  
tank). DO NOT use an automatic air vent when using  
closed-type expansion tank. It would allow air to leave  
the system, causing waterlogging of the expansion tank.  
System or zone circulator  
System temperature gauges  
Zone valve  
11 Fill valve  
12 Diaphragm-type or bladder-type expansion tank, if  
used (For closed-type expansion tank, pipe from top  
of air separator to tank fitting as in Figure 5.)  
Drain valve  
System temperature valves (see instructions to the  
left for adjusting valves)  
13 Air separator and automatic vent, if used (Note that  
the fill valve must always be connected to the expansion  
tank, regardless of location of expansion tank,  
circulator or air separator.)  
8
9
Blend temperature gauge  
Relief valve  
19  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
3e  
Boiler-bypass piping  
method  
Water piping — low temp systems  
This piping method is called a boiler-bypass because part of the circulator flow is bypassed  
around the boiler (through valve 7a). This method reduces the flow rate throughout the  
boiler, in order to raise the average water temperature in the boiler enough to prevent flue gas  
condensation. Boiler-bypass piping is effective for some boilers — including the CGs —  
provided the flow rates are adjusted according to the instructions following.  
Figures 10 and 11 are alternative piping suggestions for converted gravity (large water content  
or steam systems) or radiant heating system — for use when primary/secondary piping  
can’t be applied. (Figure 12 is another alternative, using system bypass in place of boiler-  
bypass piping. Figure 12 however, is not suitable for radiant heating applications because it  
does not protect the radiant system from possible high water temperature.)  
Boiler-bypass piping keeps system flow rate as high as possible and temperature drop as low  
as possible, helping to equalize the building heat distribution.  
Temperature gauges Gauge 4a is optional if the bypass valves will be adjusted using cold (or room temperature)  
return water to the boiler. (When setting the valves without gauge 4a installed — using cold  
or room temperature water — assume the return water temperature to be 60 °F. Set the valves  
so gauge 8 reads at least 120 °F.  
Gauge 4b is optional on converted gravity systems, but required on radiant heating systems  
— to display the water temperature being supplied to the radiant tubing.  
Gauge 8 is required on all systems to assure reliable adjustment of the bypass valves. The  
boiler-mounted temperature/pressure gauge can be used if a separate temperature gauge is  
not installed.  
1. Start with valve 7a fully closed and 7b fully open.  
Valve adjustment  
2. Gradually open valve 7a while closing valve 7b until the temperature at gauge 8 reads  
60 °F higher than gauge 4a. A minimum 60 °F temperature rise through the boiler assures  
a low enough flow rate and high enough average temperature to prevent condensation  
even with low system return water temperature.  
3. Valve 7a regulates the system flow rate, while valve 7b regulates the boiler flow rate.  
4. The boiler-mounted temperature/pressure gauge may be used in place of a separate  
gauge 8.  
Failure to prevent low return water temperature to the boiler could cause corrosion of  
the boiler sections or burners, resulting in severe personal injury, death or substantial property  
damage.  
Radiant heating system piping should include a means of regulating the boiler return  
water temperature and the system supply temperature (such as provided by an injection  
pumping control).  
Boiler return water temperature will be adequately controlled using the methods shown in  
this manual provided the system supply temperature is relatively constant.  
DO NOT apply the methods of this manual if the system is equipped with an outdoor  
reset control. Instead, provide controls and piping which can regulate the boiler return  
water temperatureat no less than 130 °F regardless of system supply temperature. Contact  
your Weil-McLain representative for suggested piping and control methods.  
Failure to prevent cold return water temperature to the boiler could cause corrosion  
damage to the sections or burners, resulting in possible severe personal injury, death or  
substantial property damage.  
20  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
boiler-bypass (alternate) piping —  
for radiant heating or converted gravity systems  
Figure 10 Boiler-bypass piping  
Figure 11 Boiler-bypass piping  
Zoning with circulators  
Zoning with zone valves  
(Alternative to primary/secondary piping  
Figures 8 and 9)  
(Alternative to primary/secondary piping  
Figures 8 and 9)  
ZONE 2  
ZONE 1  
ZONE 2  
ZONE 1  
1
1
2
1
1
5
4a  
6
4b  
3
4b  
6
2
13  
8
1
1
13  
6
Alternate  
circulator  
location  
6
7a  
7a  
8
7b  
10  
7b  
9
10  
9
4a  
11  
Cold  
water  
fill  
11  
Cold  
water  
fill  
12  
12  
3
26016  
26017  
10 Automatic air vent (with diaphragm-type  
expansion tank), or connect to tank fitting (closed-  
type expansion tank). DO NOT use an automatic  
air vent when using closed-type expansion tank. It  
would allow air to leave the system, causing  
waterlogging of the expansion tank.  
1
2
3
4
5
6
7
Boiler isolation (balancing) valves  
Flow/check valve  
System or zone circulator  
System temperature gauges  
Zone valve  
11 Fill valve  
12 Diaphragm-type or bladder-type expansion tank,  
if used (For closed-type expansion tank, pipe from  
top of air separator to tank fitting as in Figure 5.)  
Drain valve  
System temperature valves (see instructions to the left  
for adjusting valves)  
13 Air separator and automatic vent, if used (Note that  
the fill valve must always be connected to the  
expansion tank, regardless of location of expansion  
tank, circulator or air separator.)  
8
9
Blend temperature gauge  
Relief valve  
21  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
3f  
System-bypass  
piping method  
Water piping — low temp systems  
This piping method is called a system-bypass because part of the circulator flow bypasses  
the system (through valve 7a). This bypassed hot water from the boiler outlet mixes with  
cooler system return water temperature in order to provide minimum 130 °F return water to  
the boiler. Valve 7b will most often be full open, but may need to be slightly closed on some  
low pressure drop systems in order to cause enough flow through valve 7a.  
Figure 12 is an alternative piping method that provides return water temperature control for  
boilers installed on converted gravity systems (large water content or steam systems).  
Do not apply the piping of Figure 12 on radiant heating systems. It provides no method  
regulating the water temperature provided to the system and could result in excessive water  
temperature in the radiant tubing.  
System-bypass piping as shown in Figure 12 can be used with either zone valve or circulator  
zoning. When used with circulator zoning however, the boiler circulator (item 3), must be  
piped as shown. It cannot be used as one of the zoning circulators.  
Do not apply system-bypass piping if the reduced flow in the system could cause poor heat  
distribution. That is, system-bypass piping reduces the flow in the system and increases the  
water temperature supplied to the system. This can cause increased heat from radiators at the  
beginning of the system and reduced heat from radiators near the end of the system.  
Valve adjustment 1. Start with valve 7a fully closed and 7b fully open.  
2. Gradually open valve 7a while closing valve 7b until the temperature at gauge 8 reads at  
least 130 °F at all times.  
3. Valve 7a regulates the amount of boiler supply water mixed with return water. Valve 7b  
causes a pressure drop in the system needed to balance flow through valve 7a and the  
system.  
4. The valve adjustment should be done with the system at the coldest expected temperature  
(60 °F for converted gravity systems or high mass radiant systems).  
Failure to prevent low return water temperature to the boiler could cause corrosion of  
the boiler sections or burners, resulting in severe personal injury, death or substantial property  
damage.  
Radiant heating system piping should include a means of regulating the boiler return  
water temperature and the system supply temperature (such as provided by an injection  
pumping control).  
Boiler return water temperature will be adequately controlled using the methods shown in  
this manual provided the system supply temperature is relatively constant.  
DO NOT apply the methods of this manual if the system is equipped with an outdoor  
reset control. Instead, provide controls and piping which can regulate the boiler return  
water temperatureat no less than 130 °F regardless of system supply temperature. Contact  
your Weil-McLain representative for suggested piping and control methods.  
Failure to prevent cold return water temperature to the boiler could cause corrosion  
damage to the sections or burners, resulting in possible severe personal injury, death or  
substantial property damage.  
22  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
3f  
system-bypass (alternate) piping —  
for converted gravity (or steam) systems  
From system  
To system  
Figure 12 System-bypass piping  
7b  
7a  
Zoning with zone valve or circulators, return  
water 130 °F or higher.  
(Alternative to boiler-bypass piping  
Figures 10 and 11)  
Alternate  
circulator  
location  
8
3
7
System or zone circulator  
9
10  
System temperature valves (see instructions to the left for  
adjusting valves)  
11  
12  
Cold  
water  
fill  
8
9
Blend temperature gauge  
Relief valve  
10 Automatic air vent (with diaphragm-type expansion  
tank), or connect to tank fitting (closed-type expansion  
tank). DO NOT use an automatic air vent when using  
closed-type expansion tank. It would allow air to leave  
the system, causing waterlogging of the expansion tank.  
11 Fill valve  
12 Diaphragm-type or bladder-type expansion tank, if used  
(For closed-type expansion tank, pipe from top of air  
separator to tank fitting as in Figure 5.)  
26018  
3g  
Water piping — refrigeration system  
Prevent chilled water from  
Figure 13 Piping refrigeration systems  
entering boiler  
Expansion tank  
System  
Install boiler so that chilled  
supply  
medium is piped in parallel with  
the heating boiler. Use appropriate  
valves to prevent chilled medium  
from entering boiler. See Figure 13  
for typical installation of balancing  
valve and check valve.  
Shut-off  
valve  
Circulator  
Water  
chiller  
If boiler is connected to heating  
coils located in air handling units  
where they can be exposed to  
refrigerated air, use flow control  
valves or other automatic means to  
prevent gravity circulation during  
cooling cycle.  
Strainer  
MODEL  
CGs  
Boiler  
Check  
valve  
System  
return  
Balancing  
valve  
26019  
23  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
4
5
Venting and combustion air  
CGs Boiler must be vented and supplied with  
Install vent piping and air piping  
(if used) per appropriate Venting  
Supplement included in boiler  
envelope assembly.  
combustion and ventilation air as described in  
Weil-McLain CGs Venting Supplements packed in  
envelope assembly with boiler. Failure to do so will  
cause severe personal injury or death.  
Use direct vent (sealed combustion) if combustion  
air quality cannot be assured to be free of  
contaminants. Refer to page 9 for a list of potential  
contaminants and locations likely to contain them.  
Operating the boiler with contaminated air will damage  
the boiler sections and vent, resulting in possible boiler  
failure or leakage of flue products, causing severe  
personal injury, death or substantial property damage.  
Refer to Venting Supplements and  
to manual section 1 regarding  
requirements for:  
vent system  
combustion air openings  
combustion air quality  
Gas piping  
Connecting gas supply piping to boiler  
Figure 14 Gas supply piping  
1. Remove jacket front panel and refer to Figure 14  
to pipe gas to boiler.  
a. Install drip leg at inlet of gas connection to  
boiler. Where local utility requires drip leg to  
be extended to the floor, use appropriate length  
of pipe between cap and tee.  
Manual main  
shutoff gas valve  
(when required)  
Ground joint union  
(when required)  
b. Install ground joint union for servicing, when  
required.  
c. Install manual shutoff valve in gas supply  
piping outside boiler jacket when required by  
local codes or utility requirements.  
Tee  
Nipple  
Cap  
d. In Canada — When using manual main shutoff  
valve, it must be identified by the installer.  
26020  
24  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
5
Gas piping continued  
2. Support piping with hangers, not by boiler or its Natural Gas:  
accessories.  
1. Refer to Table 4 for pipe length and diameter. Base  
on rated boiler input (divide by 1,000 to obtain  
cubic feet per hour). Table 4 is only for gas with  
specific gravity 0.60, with a pressure drop  
through the gas piping of 0.30" w.c. For additional  
gas pipe sizing information, refer to ANSI Z223.1  
(or B149.1 or B149.2 for Canadian installations).  
3. Purge all air from gas supply piping.  
4. Before placing boiler in operation, check boiler  
and its gas connection for leaks.  
a. Close manual main shutoff valve during any  
pressure testing at less than 13" w.c.  
2. Inlet pressure required at gas valve inlet:  
• Maximum: 13" w.c.  
b. Disconnect boiler and gas valve from gas  
supply piping during any pressure testing  
greater than 13" w.c.  
• Minimum: 5" w.c.  
• Manifold gas pressure: 3.5" w.c.  
Do not check for gas leaks with  
an open flame — use bubble test. 3. Install 100% lockup gas pressure regulator in  
Failure to use bubble test or check  
for gas leaks can cause severe  
personal injury, death or substantial  
property damage.  
supply line if inlet pressure exceeds 13" w.c.  
Adjust for 13" w.c. maximum.  
1. Contact gas supplier to size pipes, tanks and 100%  
lockup gas pressure regulator.  
5. Use pipe dope compatible with propane gases.  
Apply sparingly only to male threads of pipe joints  
so that pipe dope does not block gas flow.  
2. Adjust propane supply regulator provided by gas  
supplier for 13" w.c. maximum pressure.  
3. Inlet pressure required at gas valve inlet:  
• Maximum: 13" w.c.  
Failure to apply pipe dope as  
detailed above can result in severe  
personal injury, death or substantial  
property damage.  
• Minimum: 11" w.c.  
• Manifold gas pressure: 10" w.c.  
Table 4 Pipe capacity for 0.60 specific gravity natural gas  
Capacity of pipe for pipe size of:  
(Capacity in cubic feet gas per hour)  
Gas pipe  
length  
(feet)  
½"  
¾"  
1"  
1¼"  
1½"  
10  
20  
132  
92  
73  
63  
56  
45  
38  
31  
278  
190  
152  
130  
115  
93  
520  
350  
285  
245  
215  
175  
150  
120  
1050  
730  
590  
500  
440  
360  
305  
250  
1600  
1100  
860  
760  
670  
545  
460  
380  
30  
40  
50  
75  
100  
150  
79  
64  
25  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
6
Field wiring  
For your safety, turn off electrical  
Wiring connections  
Boiler is shipped with controls completely wired.  
power supply at service entrance  
panel before making any electrical  
connections to avoid possible  
electric shock hazard. Failure to do  
so can cause severe personal injury  
or death.  
Thermostat  
1. Connect thermostat as shown on wiring diagram  
on boiler.  
2. Install on inside wall away from influences of  
drafts, hot or cold water pipes, lighting fixtures,  
television, sunrays, or fireplaces.  
Wiring must be N.E.C. Class 1.  
3. If thermostat has a heat anticipator, set heat  
anticipator in thermostat to match power  
requirements of equipment connected to it. If  
connected directly to boiler, set for 0.4 amps. For  
other devices, refer to manufacturer’s specifications.  
Wiring diagram on boiler gives setting for control  
module and gas valve. Also see instructions with  
thermostat.  
If original wiring as supplied with  
boiler must be replaced, use only  
type 105 °C wire or equivalent.  
Boiler must be electrically  
grounded as required by National  
Electrical Code ANSI/NFPA 70 –  
latest edition.  
Junction Box (furnished)  
1. Connect 120 VAC power wiring as shown in  
Electrical installation  
must comply with:  
Figure 15.  
2. Fused disconnect or service switch (15 amp.  
recommended) may be mounted on this box. For  
those installations with local codes which prohibit  
installation of fused disconnect or service switch  
on boiler, install a 2 x 4 cover plate on the boiler  
junction box and mount the service switch  
remotely as required by the code.  
1. National Electrical Code and  
any other national, state,  
provincial or local codes or  
regulations.  
2. In Canada, CSA C22.1  
Canadian Electrical Code Part 1,  
and any local codes.  
Service  
120 VAC  
Hot  
Figure 15  
switch  
(not provided)  
Neutral  
Ground  
Field wiring connections —  
service switch and thermostat  
(or end switch) provided by  
installer  
Thermostat  
or end switch  
(not provided)  
Service  
switch  
(not provided)  
Thermostat  
or end switch  
(not provided)  
Ground screw  
Green  
Wire nuts  
Black  
White  
Black  
Black  
The CGs control module is  
polarity-sensitive. The hot and  
neutral wires must be connected to  
the correct leads. A flashing POWER  
light usually indicates reversed  
polarity of 120 VAC lead wires.  
Thermostat  
leads, through  
jacket left side  
Junction box,  
boiler left side  
26021  
26  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
7a  
Start-up — preparation  
Determine if water treatment is needed  
Fill the system with water  
Do not use petroleum-based cleaning or sealing  
compounds in boiler system. Severe damage to boiler  
will occur, resulting in substantial property damage.  
1. Close manual and automatic air vents and boiler  
drain cock.  
2. Fill to correct system pressure. Correct pressure  
will vary with each application. Typical cold water  
fill pressure for a residential system is 12 psi.  
Eliminate all system leaks. Continual fresh makeup  
water will reduce boiler life. Minerals can build up in  
sections, reducing heat transfer, overheating cast iron,  
and causing section failure.  
3. Purge air from system:  
a. Connect a hose to the purge valve (see drain  
valves, item 6, in suggested piping diagrams  
on pages 17 through 21, Figure 6 through  
Figure 11). Route hose to an area where water  
can drain and be seen.  
Verify water chemistry  
Consult local water treatment companies for unusually  
hard water areas (above 7 grains hardness) or low pH  
water conditions (below 7.0). Boiler water pH of 7.0  
to 8.5 is recommended.  
b. Close the boiler or system isolation valve  
between the purge valve and fill connection to  
the system.  
Freeze protection (when used)  
Use antifreeze made especially for hydronic systems.  
Inhibited propylene glycol is recommended.  
c. Close zone isolation valves.  
Do not use ethylene glycol,  
d. Open quick-fill valve on cold water makeup  
line.  
automotive  
or  
undiluted  
antifreeze. Severe personal injury  
or death can result.  
e. Open purge valve.  
f. One zone at a time, open the isolation valves.  
Allow water to run through the zone, pushing  
out the air. Run until no noticeable air flow is  
present. Close the zone isolation valves and  
proceed with the next zone. Follow this  
procedure until all zones are purged.  
1. Determine antifreeze quantity according to system  
water content. Boiler water content is listed on  
page 59. Remember to include expansion tank water  
content.  
2. Follow antifreeze manufacturer's instructions.  
3. A 50% solution of propylene glycol/water provides  
maximum protection to about -30 °F.  
g. Close the quick-fill water valve and purge valve  
and remove the hose. Open all isolation valves.  
Watch that system pressure rises to correct  
cold-fill pressure.  
4. Local codes may require back flow preventer or  
actual disconnect from city water supply.  
5. When using antifreeze in a system with automatic  
fill, install a water meter to monitor water makeup.  
Glycol will leak before the water begins to leak,  
causing glycol level to drop. Added water will dilute  
the antifreeze, reducing the freeze protection level.  
h. After the system has operated for a while,  
eliminate any residual air by using the manual  
air vents located throughout the system.  
i. If purge valves are not installed in system, open  
manual air vents in system one at a time,  
beginning with lowest floor. Close vent when  
water squirts out. Repeat with remaining vents.  
Check for gas leaks  
Before starting the boiler, and during initial operation,  
smell near the floor and around the boiler for gas  
odorant or any unusual odor. Do not proceed with  
start-up if there is any indication of a gas leak. Repair  
any leak at once.  
4. Open automatic air vent (diaphragm-type or  
bladder-type expansion tank systems only) one  
turn.  
5. Open other vents:  
Propane boilers only — Your propane supplier mixes  
an odorant with the propane to make its presence  
detectable. In some instances, the odorant can fade, and  
the gas may no longer have an odor. Before start-up  
(and periodically thereafter), have the propane supplier  
verify the correct odorant level in the gas.  
a. Starting on the lowest floor, open air vents one  
at a time until water squirts out.  
b. Repeat with remaining vents.  
6. Refill to correct pressure.  
27  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
7a  
7b  
Start-up — preparation continued  
Inspect system water piping  
Inspect base insulation  
After filling the boiler and system  
with water, inspect all piping  
throughout the system for leaks. If  
found, repair immediately. Repeat  
this inspection after the boiler has  
been started and the system has  
heated up.  
Check to make sure insulation is  
secure against all four sides of the  
base. If insulation is damaged or  
displaced, do not operate boiler.  
Replace or reposition insulation.  
Failure to replace damaged  
insulation or reposition insulation  
can result in a fire hazard, causing  
severe personal injury, death or  
substantial property damage.  
Leaks must be repaired at once.  
Failure to do so can damage the  
boiler, resulting in substantial  
property damage.  
The boiler contains ceramic fiber  
and fiberglass materials. Use care  
when handling these materials per  
instructions on page 60 of this  
manual. Failure to comply could  
result in severe personal injury.  
Do not use petroleum-based  
cleaning or sealing compounds in  
boiler system. Severe damage to  
boiler will occur, resulting in  
substantial property damage.  
Start-up — operate boiler  
Eliminate all system leaks.  
Continual fresh makeup water will  
reduce boiler life. Minerals can  
build up in sections, reducing heat  
transfer, overheating cast iron, and  
causing section failure.  
Final check before starting boiler  
Read manual section 9 including the Lighting  
instructions procedure (Figure 21, page 34).  
Verify the boiler and system are full of water.  
Verify the Start-up preparation procedures of  
section 7a have been completed.  
1. Check system piping for leaks. If found, shut  
down boiler and repair immediately.  
2. Vent air from system using manual vents. Air in  
the system will interfere with circulation and cause  
heat distribution problems and noise.  
Start the boiler  
Follow the Lighting instructions from section 9c  
to start the boiler.  
3. Inspect vent system thoroughly for signs of  
deterioration from corrosion, physical damage or  
sagging. In addition — Check for gas-tight seal at  
every connection and seam.  
See section 7c if boiler fails to start.  
Check system and boiler  
Venting system must be sealed  
gas-tight to prevent flue gas spillage  
and carbon monoxide emissions  
which will result in severe personal  
injury or death.  
Do not use petroleum-based  
cleaning or sealing compounds in  
boiler system. Severe damage to  
boiler will occur, resulting in  
substantial property damage.  
28  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
7b  
Start-up — operate boiler continued  
4. Check around the boiler for gas odor following  
Figure 16 Typical pilot burner flame  
the procedure of section 7a of this manual.  
If you discover evidence of any gas leak, shut down  
the boiler at once. Find the leak source with bubble  
test and repair immediately. Do not start boiler again  
until corrected. Failure to comply could result in severe  
personal injury, death or substantial property damage.  
Inner  
cone  
Spark  
electrode  
Check burner flames  
Pilot  
flame  
sensor  
View pilot and main flames through the inspection port  
in the Air inlet box front cover.  
Pilotburnerflame  
Proper pilot flame characteristics (see Figure 16):  
1. Blue flame.  
2. Inner cone engulfing pilot flame sensor.  
3. Pilot flame sensor glowing cherry red.  
26023  
Improper pilot flame characteristics:  
1. Overfired — Large flame lifting or blowing past  
pilot flame sensor.  
2. Underfired — Small flame. Inner cone not engulfing  
pilot flame sensor.  
3. Lack of primary air — Yellow flame tip.  
4. Incorrectly heated pilot flame sensor.  
Figure 17 Typical main burner flame  
Mainburnerflame  
Proper main burner flame characteristics  
(see Figure 17):  
1. Yellow-orange streaks may appear (caused by dust).  
Transparent  
blue flame  
Improper main burner flame characteristics:  
1. Overfired — Large flames.  
Inner flame  
2. Underfired — Small flames.  
3. Lack of primary air — Yellow tipping on flames  
(sooting will occur).  
26024  
7c  
Start-up — if boiler doesn’t start . . .  
Check for:  
4. Gas not turned on at meter or boiler?  
1. Loose connections, blown fuse or service switch  
off?  
5. Incoming gas pressure less than:  
5" w.c. for natural gas?  
2. High limit switch set below boiler water  
temperature?  
11" w.c. for propane gas?  
If none of the above corrects the problem, refer to  
Troubleshooting, section 11 of this manual.  
3. Thermostat set below room temperature?  
29  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
8
Check-out procedure — checklist  
Boiler and heat distribution units filled with water?  
Automatic air vent, if used, open one full turn?  
Air purged from system?  
e. Pilot will relight, flame sensing element will sense pilot  
flame and main burners will reignite.  
Set limit control(s) to system temperature requirements.  
Adjust balancing valves and controls to provide design  
temperature to system.  
Air purged from gas piping? Piping checked for leaks?  
For multiple zones, adjust flow so it is about the same in  
each zone.  
Correctly sized manifold orifices installed? Refer to manual  
section 2a to check size and fuel type.  
Verify thermostat heat anticipator (if available) set properly?  
Refer to Field wiring, manual section 6a, Thermostat(s).  
Correctly sized manifold orifices must be  
used. Failure to do so will cause severe  
personal injury, death or substantial property  
damage.  
Cycle boiler with thermostat — Raise to highest setting  
and verify boiler goes through normal start-up cycle. Lower  
to lowest setting and verify boiler goes off.  
Followed operating instructions on boiler or in manual  
section 9 for proper start-up?  
Measure natural gas input:  
Proper burner flame observed? Refer to Check burner  
flame, manual section 7b.  
a. Operate boiler 10 minutes.  
b. Turn off other appliances.  
c. At natural gas meter, measure time (in seconds)  
required to use one cubic foot of gas.  
d. Calculate gas input:  
Test limit control — While burners are operating, move  
indicator on limit control below actual boiler water  
temperature. Burners should go off while circulator  
continues to operate. Raise setting on limit control above  
boiler water temperature and burners should reignite.  
3600 x 1000  
= Btuh  
number of seconds from step c  
e. Btuh calculated should approximate input rating on  
boiler rating label.  
Test additional field-installed controls — If boiler has a  
low water cutoff, additional high limit or other controls,  
test for operation as outlined by manufacturer. Burners  
should be operating and should go off when controls are  
tested. When controls are restored, burners should reignite.  
Check manifold gas pressure by connecting manometer to  
downstream test tapping on main gas valve. Manifold  
pressure for natural gas should be 3.5" w.c. and for propane  
gas should be 10" w.c.  
Test ignition system safety device:  
Observe several operating cycles for proper operation.  
Set room thermostat to desired room temperature.  
Fill in Installation and service certificate below?  
a. Connect manometer to outlet side of gas valve.  
b. Start boiler, allowing for normal start-up cycle to occur  
and main burners to ignite.  
c. With main burners on, manually shut off gas supply  
at manual main shutoff gas valve. Burners should go  
off.  
Review all instructions shipped with this boiler with owner  
or maintenance person. Return instructions to envelope  
and give to owner or place in pocket inside front panel in  
boiler.  
d. Open manual main shutoff gas valve. Manometer  
should confirm there is no gas flow.  
Installation and service certificate  
Boiler model __________________  
Series __________  
CP number ___________  
Date installed _______________  
Installation instructions have been followed.  
Check out sequence has been performed.  
Above information is certified to be correct.  
Measured Btuh input ____________  
Information received and left with owner/maintenance person  
Installer ________________________  
(company)  
________________________________  
(address)  
______________________________  
(phone)  
_____________________________________  
(installer’s signature)  
30  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
9a  
Operation — sequence  
1. Read Lighting instructions on page 34. This  
information is also located on a label on the inside  
of the boiler jacket door panel.  
b. If power is interrupted, control system shuts  
off pilot and main gas valves and restarts at step  
1 when power is restored.  
2. Raise room thermostat to call for heat.  
6. In the event the limit control shuts down the  
boiler — The control module closes the pilot and  
main gas valves, but keeps the inducer operating  
for 15-second postpurge.  
3. Inducer and circulator energize. After pressure  
switch proves proper airflow, control module  
initiates 30-second prepurge.  
— The circulator continues to operate.  
4. Control module sparks the pilot and opens pilot  
7. Lower room thermostat setting to stop call for heat.  
Thermostat is satisfied — Pilot and main gas valves  
are closed — Inducer operates for 15-second  
postpurge — Circulator is shut off.  
valve in main gas valve.  
a. If pilot does not light within 15 seconds, pilot  
valve is closed and spark generator is turned  
off. Control module initiates a 15-second  
postpurge, then starts a new cycle.  
8. Boiler is now in the off cycle.  
b. If pilot does light and control module senses 9. Repeat steps 1 through 6 several times to verify  
flame current, spark generator is turned off and  
main valve opens.  
operation.  
10. Return the thermostat to normal setting.  
5. During main burner operation:  
11. Set thermostat heat anticipator setting to 0.4 amps,  
adjusted for gas valve and control current.  
a. Control module monitors pilot flame current.  
If signal is lost, main valve closes, spark  
generator activates and sequence returns to  
step 4.  
Figure 18 Control module sequence of operation — status light indications  
Call for  
heat?  
POWER  
TSTAT  
CIRC  
LIMIT  
PRESS  
SWITCH  
FLAME  
Timing  
Steps  
(Following step 8, cycle goes back to step 1.)  
1. Standby  
NO  
·
Waiting for call for heat  
2. Call for heat  
Circulator on  
Blower on  
·
·
YES  
3. Limit circuit  
Limit controls closed  
Block switch contacts closed  
·
·
YES  
YES  
4. Pressure circuit  
Pressure switch contacts closed  
Prepurge for 30 seconds  
·
·
35 sec  
15 sec  
5. Pilot flame proven *  
·
·
·
Gas valve open  
Pilot remains on  
Boiler producing heat  
YES  
YES  
6. Limit cycle  
Limit circuit open  
Gas valve closed  
·
·
7. Flame outage *  
Flame out  
Boiler recycles  
·
·
YES  
NO  
NO  
8. Thermostat satisfied  
Circulator off  
Blower postpurge  
·
·
15 sec  
30 sec  
9. Circulator exercise routine  
Circulator turns on for 30 seconds  
if boiler not operated for 30 days  
·
or  
= "ON"  
= "OFF"  
*
If pilot flame is not proven in 15 seconds, control module will flash the FLAME light, but will continue indefinitely with attempts to light the pilot burner.  
The control module will not lockout on a failure to establish flame. It will lockout if line voltage polarity is reversed, stray voltage is sensed on thermostat  
line, pressure switch sticks closed or fails to make within 5 minutes or if flame is sensed when it shouldn’t be there. The boiler will reset after these lockouts  
if any of the following occurs:  
• 1 hour waiting period  
• Opening and closing of thermostat circuit  
• Removal of 120 VAC power for at least 45 seconds.  
26030  
31  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
9b  
Operation — wiring diagrams  
Figure 19 Schematic wiring diagram  
32  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
Figure 20 Ladder wiring diagram  
Hot  
Neutral  
Gnd  
Electrical shock hazard — can cause  
severe injury or death. Disconnect  
power before installing or servicing.  
120 VAC  
SERVICE  
SWITCH  
All contacts are shown without power  
applied.  
Legend for ladder wiring diagram  
INDUCER MOTOR  
CIRCULATOR  
CONTROL  
MODULE  
120 VAC  
120 VAC field wiring  
Low voltage field wiring  
120 VAC factory wiring  
Low voltage factory wiring  
High voltage spark ignition wiring  
Ground connectors  
SECTION  
HIGH  
VOLTAGE  
PILOT  
IGNITION  
ELECTRODE  
Table G: Gas valve terminals and anticipator settings  
Anticipator  
Gas valve  
"A"  
"B"  
"C"  
120 VAC  
amps  
Honeywell VR8204  
Honeywell VR8304  
White-Rodgers 36E  
White-Rodgers 36C  
MV/PV MV  
PV  
PV  
3
0.6  
MV/PV  
MV  
0.8  
0.64  
0.7  
2
1
24 VAC  
2–4 *  
1
3
* Terminals 2–4 are factory-jumpered on the  
White-Rodgers 36C gas valve.  
Power  
G
R
R
R
R
1. All wiring must be installed in accordance with:  
A. U.S.A. — N.E.C. And any other national, state,  
or local code requirements.  
B. Canada — C.S.A. C22.1 C.E.C. Part 1 and any  
other national, provincial, or local code require-  
ments.  
THERMOSTAT  
PILOT GAS  
VALVE  
Tstat–Circ  
Limit  
2. Pilot lead wires are not field replaceable. Replace pi-  
"C"  
"A"  
WATER TEMP  
LIMIT SWITCH  
ROLLOUT  
TFE  
lot assembly if necessary.  
3. If any of the original wire as supplied with the ap-  
pliance must be replaced, use minimum 105 °C  
wire or equivalent. Exception — wires to a rollout  
TFE must be 200 °C or equivalent.  
4. Thermostat anticipator setting (single zone) — see  
Table G for anticipator setting, depending on  
which gas valve is installed in boiler.  
5. For multiple zoning, use either zone valves or  
circulators. Refer to the component manufac-  
turer's instructions and this manual for applica-  
tion and wiring suggestions.  
Additional  
limits (note 7)  
"B"  
MAIN GAS  
VALVE  
AIR PRESSURE  
Press switch  
Flame  
SWITCH  
See Table G  
HIGH  
VOLTAGE  
PILOT  
FLAME  
SENSOR  
6. Refer to control component instructions packed  
with the boiler for application information.  
Control module  
low voltage  
section  
7. Wire any additional limit controls (low water cut-  
off, additional high limit, etc.) in series with boiler  
limit control as shown.  
71033  
33  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
9c  
Operation — lighting instructions  
Figure 21 Lighting instructions  
FOR YOUR SAFETY READ BEFORE OPERATING  
If you do not follow these instructions exactly, a fire or explosion may  
result causing property damage, personal injury or loss of life.  
A. This appliance does not have a pilot. It is  
C. Use only your hand to turn the gas control knob. Never use  
tools. If the knob will not turn by hand, don't try to repair it,  
call a qualified service technician. Force or attempted repair  
may result in a fire or explosion.  
equipped with an ignition device which  
automatically lights the burner. Do not try to  
light the burner by hand.  
B. Before OPERATING, smell all around the  
appliance area for gas. Be sure to smell next to  
the floor because some gas is heavier than air  
and will settle on the floor. See below.  
D. Do not use this appliance if any part has been under water.  
Immediately call a qualified service technician to inspect the  
appliance and to replace any part of the control system and  
any gas control, which has been under water.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
Immediately call your gas supplier from a neighbor's phone.  
Follow the gas supplier's instructions.  
Do not touch any electric switch; do not use  
any phone in your building.  
If you cannot reach your gas supplier, call the fire department.  
OPERATING INSTRUCTIONS  
26070  
1. Stop! Read the safety information above on this label.  
2. Set the thermostat to lowest setting.  
White-Rodgers  
36C Gas valve  
3. Turn off all electrical power to the appliance.  
4. Remove jacket front panel.  
5. This appliance is equipped with an ignition device which automatically lights the burner.  
Do not try to light the burner by hand.  
Position indicator  
(shown in "ON" position)  
Gas control knob  
6. Turn Gas control knob clockwise  
to OFF.  
White-Rodgers  
36E Gas valve  
7. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If  
you smell gas, STOP! Follow "B" in the safety information above. If you don't smell gas,  
go to the next step.  
Position indicator  
(shown in "ON" position)  
8. Turn Gas control knob counterclockwise  
9. Turn on all electric power to the appliance.  
10. Set thermostat to desired setting.  
to ON.  
Gas control knob  
Honeywell  
VR8204 or  
VR8304  
Gas valve  
11. If the appliance will not operate, follow the instructions "ToTurn Off GasTo Appliance"  
below and call your service technician or gas supplier.  
Position indicator  
(shown in "ON" position)  
12. Replace jacket front panel.  
Gas control knob  
TO TURN OFF GAS TO THE APPLIANCE  
1. Set the thermostat to lowest setting.  
2. Turn off all electric power to the appliance if service is to be performed.  
3. Remove jacket front panel.  
4. Turn Gas control knob clockwise  
to OFF. Do not force.  
5. Replace jacket front panel.  
34  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
10a  
Service and maintenance — schedule  
Table 5 Service and maintenance schedules  
Service technician  
(see following pages for instructions)  
Owner maintenance  
(see CGs User’s Information Manual for instructions)  
• Check boiler area  
Inspect:  
• Check air openings  
• Reported problems  
• Boiler area  
Daily  
• Check boiler pressure/  
temperature gauge  
• Air openings  
• Check boiler interior piping  
• Check venting system  
• Check air vents  
• Flue gas vent system (and air piping)  
• Pilot and main burner flames  
• Water piping  
Monthly  
• Check boiler relief valve  
• Boiler heating surfaces  
• Burners, base and inlet air box  
• Condensate drain system  
Service:  
• Check condensate drain system  
• Check automatic air vents (if  
used)  
• Test low water cutoff (if used)  
• Inducer motor  
Periodically  
• Clean vent termination/air intake  
screens  
• Oiled-bearing circulators  
Start-up:  
• Oil inducer motor  
Every 6 months  
• Perform start-up per manual  
Check/test:  
• Operate relief valve  
• Gas piping  
• Cold fill and operating pressures  
• Air vents and air elimination  
• Limit controls and cutoffs  
• Expansion tank  
End of season  
• Shut down procedure  
• Boiler relief valve  
Review:  
• Review with owner  
Follow the Service and maintenance procedures given throughout this manual and in  
component literature shipped with the boiler. Failure to perform the service and maintenance  
could result in damage to the boiler or system. Failure to follow the directions in this manual  
and component literature could result in severe personal injury, death or substantial property  
damage.  
35  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
10b  
Service & maintenance — annual start-up  
The boiler should be inspected and started annually, at the beginning of the heating season, only by a qualified  
service technician. In addition, the maintenance and care of the boiler designated in Table 5 and explained on  
the following pages must be performed to assure maximum boiler efficiency and reliability. Failure to service  
and maintain the boiler and system could result in equipment failure.  
Inspect . . . . . . . . . .  
Reportedproblems  
Flue gas vent system (and air piping)  
Inspect any problems reported by owner and correct 1. Visually inspect entire flue gas venting system  
before proceeding.  
(and air piping, if installed) for blockage,  
deterioration or leakage. Repair any joints that show  
signs of leakage in accordance with vent  
manufacturer’s instructions. When air is ducted to  
boiler, verify that air inlet hose is connected and  
properly sealed.  
Boiler area  
1. Verify that boiler area is free of any combustible  
materials, gasoline and other flammable vapors and  
liquids.  
Failure to inspect for the above  
conditions and have them repaired  
can result in severe personal injury  
or death.  
2. Verify that boiler area (and air intake) is free of any  
of the contaminants listed on page 9 of this  
manual. If any of these are present in the boiler  
intake air vicinity, they must be removed. If they  
cannot be removed, install combustion air piping  
to the boiler in accordance with the appropriate  
venting supplement.  
Pilot and main burner flames  
1. Visually inspect pilot burner and main burner  
flames as directed under Start-up, section 7 of this  
manual.  
Air openings  
1. Verify that combustion and ventilation air openings  
to the boiler room and/or building are open and  
Water piping  
unobstructed. Check operation and wiring of 1. Check the boiler interior piping and all system  
automatic combustion air dampers, if used. piping for signs of leaks.  
2. Verify that boiler vent discharge and air intake are 2. Repair any leaks before proceeding.  
clean and free of obstructions.  
The boiler contains ceramic fiber and fiberglass materials. Use care when handling these  
materials per instructions on page 60 of this manual. Failure to comply could result in severe  
personal injury.  
36  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
6. Check inside and around boiler for evidence of any  
leaks from the boiler. If found, locate source of leaks  
and repair.  
Inspect . . . . . . . . . .  
Eliminate all system or boiler leaks. Continual fresh  
makeup water will reduce boiler life. Minerals can build  
up in sections, reducing heat transfer, overheating cast  
iron, and causing section failure. Leaking water may  
also cause severe property damage.  
Burners, base and inlet air box  
1. After turning off power to the boiler, remove the inlet  
air box top panel (Figure 27, item 13, page 54).  
2. Inspect gasket (item 14). Replace if necessary.  
Do not use petroleum-based cleaning or sealing  
compounds in boiler system. Severe damage to boiler  
will occur, resulting in substantial property damage.  
3. Inspect burners and all other components in the  
inlet air box and boiler base.  
4. If burners must be cleaned, first remove item 4,  
Figure 27, page 54. Access the burner assembly by  
first removing burner baffle, item 4. Then remove  
the screws securing the burner tray to the manifold.  
Slide the burner tray out. Then brush and vacuum  
the burners thoroughly, making sure all ports are  
free of debris.  
Electrical shock hazard — Turn off power to the boiler  
before any service operation on the boiler except as  
noted otherwise in this instruction manual. Failure to  
turn off electrical power could result in electrical shock,  
causing severe personal injury or death.  
5. Inspect the slotted jacket cooling openings in the  
bottom left and rear of the base pan (Figure 27,  
item 1, page 54).  
Boiler heating surfaces  
1. Disconnect the vent pipe at the boiler inducer outlet  
connection after turning off power to the boiler.  
6. Inspect the base insulation. Pay attention to the  
WARNING on page 36 regarding working with  
insulation materials. Verify that the insulation is  
intact and secure against all four sides of the base.  
2. Use a bright light to inspect the flue pipe interior  
and inducer interior.  
3. Inspect the boiler vent outlet area and heating  
surfaces by looking through the opening.  
If insulation is damaged or  
displaced, do not operate the boiler.  
Replace or reposition insulation as  
necessary. Failure to replace  
damaged insulation can result in a  
fire hazard, causing severe personal  
injury, death or substantial property  
damage.  
4. If the vent pipe or inducer interior show evidence  
of soot, follow Cleaning boiler heating surfaces  
in this manual section to remove the flue collector  
and clean the boiler if necessary after close  
inspection of boiler heating surfaces. If there is  
evidence of rusty scale deposits, check the water  
piping and control system to make sure the boiler  
return water temperature is properly maintained  
(per this manual).  
Condensate drain system  
5. Reconnect vent to inducer outlet and replace all  
boiler components before returning to service.  
1. Inspect condensate drain fittings and tubing.Verify  
that condensate can flow freely to drain.  
Service . . . . . . . . . .  
Oiled bearing circulators  
Inducer motor  
1. With boiler power OFF, place a few drops of S.A.E.  
1. The circulator shipped with the CGs boiler is  
water-lubricated. No oiling is required.  
20 motor oil in each of the two oil cups.  
Use only S.A.E. 20 motor oil to  
lubricate the inducer motor. Do not  
use universal household oils. Motor  
could be damaged, resulting in  
possible severe property damage.  
2. Check other circulators in the system. Oil any  
circulators requiring oil, following circulator  
manufacturer’s instructions. Over-oiling will  
damage the circulator.  
37  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
10b  
Service & maint. — annual start-up continued  
Start-up . . . . . . . . .  
4. Check gas piping, per manual Sections 5 and 7,  
verifying no indications of leakage and all piping  
and connections are in good condition.  
1. Start the boiler, following the instructions in  
manual section 7.  
2. Verify cold fill pressure is correct and that fill 5. Read the Lighting instructions (Figure 21 of this  
system is working properly.  
manual or on boiler label) applying to the boiler.  
3. Verify antifreeze level (if used) is at the right 6. Start the boiler following the Lighting instructions  
concentration and that inhibitor level is correct.  
and manual section 7.  
Check/test . . . . . . .  
2. Inspect and test additional limit controls or low  
water cutoffs installed on system.  
Gas piping  
1. Sniff near floor and around boiler area for any  
indication of a gas leak.  
Figure 22 Automatic air vent, typical  
A
2. Test gas piping using bubble test, per section 5  
of this manual, if there is any indication of a leak.  
B
Cold fill and operating pressures  
1. While the system is cold, note the pressure reading  
on the boiler pressure/temperature gauge.Verify that  
cold fill pressure is correct.  
2. Watch the pressure as the boiler and system heat  
up to ensure pressure rise is normal. Too high a  
rise would indicate a waterlogged or undersized  
expansion tank.  
26031  
Air vents and air elimination  
1. Inspect automatic air vents (if used). Also inspect  
air separators to ensure they are operational.  
Expansion tank  
1. Expansion tanks provide space for water to move  
in an out as the heating system water expands due  
to temperature increase or contracts as the water  
cools. Tanks may be open, closed or diaphragm or  
bladder type. See section 3 of this manual for  
suggested best location of expansion tanks and air  
eliminators.  
2. The cap must be unscrewed one turn to allow air  
to escape.  
3. See Figure 22. If the air vent is leaking, remove cap  
A and briefly push valve B and then release to clean  
the valve seat.  
Open-type — located above highest radiator or  
baseboard unit, usually in the attic or closet. Has a  
gauge glass and overflow pipe to a drain.  
4. Replace cap A by twisting all the way onto valve B  
and then unscrewing one turn.  
Closed-type — welded gas tight and located above  
boiler. Tank is partially filled with water, leaving an  
air cushion for expansion.  
Limit controls and cutoffs  
1. Inspect and test the boiler limit control. Verify  
operation by turning control set point below boiler  
temperature. Boiler should cycle off. Return dial to  
original setting.  
Make sure this type of tank is fitted with a tank  
fitting, such as the B & G Tank-Trol or Taco  
Taco-Trol. This fitting reduces gravity  
38  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
discharge line have not been altered or tampered with  
illegally. Certain naturally occurring conditions may  
corrode the valve or its components over time,  
rendering the valve inoperative. Such conditions are  
not detectable unless the valve and its components are  
physically removed and inspected. This inspection must  
only be conducted by a plumbing contractor or  
authorized inspection agency — not by the owner.  
Failure to reinspect the boiler relief valve as directed  
could result in unsafe pressure buildup, which can  
result in severe personal injury, death or substantial  
property damage.  
Check/test . . . . . . .  
circulation of air-saturated tank water back to  
the system and prevents the air from bubbling  
up through the water as it returns from the  
system.  
Do not use automatic air vents in systems  
with closed-type tanks. The air will escape  
from the system instead of returning to the  
tank. Eventually, the tank will waterlog and no  
longer control pressurization. The boiler relief  
valve will weep frequently.  
Following installation, the valve  
lever must be operated AT LEAST  
Diaphragm- or bladder-type — welded gas tight  
with a rubber membrane to separate the tank  
pressurizing air and the water. May be located at  
any point in the system, but most often found near  
the boiler.  
ONCE A YEAR to ensure that waterways are clear.  
Certain naturally occurring mineral deposits may  
adhere to the valve, rendering it inoperative. When  
manually operating the lever, water will discharge and  
precautions must be taken to avoid contact with hot  
water and to avoid water damage. Before operating  
lever, check to see that a discharge line is connected to  
this valve directing the flow of hot water from the valve  
to a proper place of disposal otherwise severe personal  
injury may result. If no water flows, valve is inoperative.  
Shut down boiler until a new relief valve has been  
installed.  
Systems with this type of expansion tank  
require at least one automatic air vent,  
preferably located on top of an air eliminator,  
as shown in examples in manual section 3.  
2. If relief valve has tended to weep frequently, the  
expansion tank may be waterlogged or undersized.  
Closed-type tank — tank is most likely  
waterlogged. Install a tank fitting if not already  
installed. Then check fill level per fitting  
manufacturer’s instructions. If fill level is correct,  
check tank size against manufacturer’s instructions.  
Replace with a larger tank if necessary.  
2. After following the above warning directions, if the  
relief valve weeps or will not seat properly, replace  
the relief valve. Ensure that the reason for relief valve  
weeping is the valve and not over-pressurization  
of the system due to expansion tank waterlogging  
or undersizing.  
Diaphragm- or bladder-type — first, check tank  
size to be sure it is large enough for the system. If  
size is too small, add additional tank(s) as necessary  
to provide sufficient expansion. If tank size is large  
enough, remove tank from system and check charge  
pressure (usually 12 psig for residential  
applications). If tank won’t hold pressure,  
membrane has been damaged. Replace tank.  
Figure 23 Relief valve, typical  
Boiler relief valve  
1. Inspect the relief valve and lift the lever to verify  
flow as in the following warnings, excerpted from  
a relief valve manufacturer’s warning label. Before  
operating any relief valve, ensure that it is piped  
with its discharge in a safe area to avoid severe scald  
potential. Read manual section 3a before  
proceeding further.  
Safety relief valves should be  
reinspected AT LEAST ONCE  
EVERY THREE YEARS, by a licensed plumbing  
contractor or authorized inspection agency, to ensure  
that the product has not been affected by corrosive  
water conditions and to ensure that the valve and  
26032  
39  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
10b  
Service & maint. — annual start-up  
Review with owner . . . . . . . .  
1. Review the User’s Information Manual with the owner.  
2. Emphasize the need to perform the maintenance schedule specified in the User’s  
Information Manual (and in this manual as well).  
3. Remind the owner of the need to call in a licensed contractor should the boiler or system  
exhibit any unusual behavior.  
4. Remind the owner to follow the proper shutdown procedure and to schedule an annual  
start-up at the beginning of the next heating season.  
Cleaning boiler heating surfaces  
1. Shut down boiler:  
Follow “ToTurn Off Gas to Appliance” instructions on boiler and Lighting  
instructions.  
Do not drain boiler unless it will be exposed to freezing temperatures. If using  
antifreeze in system, do not drain.  
2. Follow shutdown procedure.  
3. Remove venting system connection to boiler.  
4. Remove top jacket panel. Turn back insulation.  
5. Remove collector box/transition assembly. Clean sealant from assembly and sections.  
6. Remove radiation plates hanging between sections.  
7. Remove burners from base. Brush and vacuum burners to remove all dust and lint. Verify  
that all burner ports are free of debris.  
8. Place newspapers in base of boiler to collect soot.  
9. Clean between sections with wire flue brush.  
10. Remove newspaper and soot. Vacuum or brush base and surrounding area.  
11. Reinstall radiation plates.  
12. Replace collector box/transition assembly. Seal with sealant.Obtain gas-tight seal to prevent  
flue gas spillage and carbon monoxide emissions, resulting in severe personal injury or  
death.  
13. Replace insulation and jacket top panel.  
14. Start up boiler following section 7 of this manual and the boiler Lighting instructions.  
Excessive sooting indicates improper gas combustion. If found check for proper  
combustion and make any necessary adjustments.  
The boiler contains ceramic fiber and fiberglass materials. Use care when handling these  
materials per instructions on page 60 of this manual. Failure to comply could result in severe  
personal injury.  
40  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
11a  
Troubleshooting — procedure  
Label all wires prior to disconnection when servicing controls. Wiring  
errors can cause improper and dangerous operation.  
Never jumper (bypass) rollout thermal fuse element or any other device  
except for momentary testing as outlined in Troubleshooting Charts. Severe  
personal injury, death or substantial property damage can result.  
Before troubleshooting:  
1. Have the following items:  
a. Voltmeter that can check 120 VAC and 24 VAC.  
b. Microammeter with a minimum scale range of 0-25.  
c. Continuity checker.  
d. Inclined manometer with 0 – 2" w.c. range.  
2. Check for 120 VAC (minimum 102 VAC to maximum 132 VAC) to  
boiler.  
3. Make sure thermostat is calling for heat and contacts (including  
appropriate zone controls) are closed. Check for 24 VAC between  
thermostat wire nuts and ground.  
Check the following:  
1. Wire connectors to control module are securely plugged in at module  
and originating control.  
2. Air pressure switch hoses are properly and securely plugged in and are  
not damaged.  
3. Gas pressures:  
a. With boiler off — 13" w.c. maximum natural or propane gas  
pressure upstream of gas valve.  
b. With boiler on:  
5" w.c. natural gas pressure or 11" w.c. propane gas pressure  
upstream of gas valve.  
3 ½" w.c. natural gas pressure or 10" w.c. propane gas pressure  
downstream tapping on gas valve — Can be adjusted by  
regulator on gas valve.  
VERIFY PROPER OPERATION AFTER SERVICING.  
41  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
11b  
Troubleshooting — air pressure switch  
Make sure boiler water temperature  
Table 6 Pressure switch setpoint  
is 100 °F or cooler before starting  
(for elevations above 2,000 ft, contact your  
procedure to obtain appropriate  
readings.  
local Weil-McLain sales office for details.)  
Boiler model number  
Inches W.C.  
1.79"  
CGs-3  
CGs-4  
CGs-5  
CGs-6  
Check pressure switch setting  
1. See Figure 24 and Table 6.  
1.48"  
1.22"  
2. Remove both air pressure switch hoses from air  
pressure switch.  
0.95"  
3. Install tees and tubing as shown in Figure 24 to  
inclined manometer.  
4. Turn off gas valve and set thermostat to call for heat.  
Inducer will run but burners will not ignite.  
Troubleshooting air pressure reading  
1. If manometer reading is lower than the setpoint  
of the switch (see Table 6) — check for possible  
causes:  
5. Check for 24 VAC between both air pressure switch  
terminals and ground.  
blockage in hoses  
6. If manometer reading is above the setpoint of the  
switch (see Table 6), but there is not 24 VAC  
between both air pressure switch terminals and  
ground — replace air pressure switch.  
obstruction in inducer housing outlet  
loose inducer wheel on motor shaft  
inducer motor not in proper rpm  
inducer back plate not sealed properly  
blockage in block assembly  
blockage in flue pipe or termination  
incorrect pressure switch  
Figure 24 Manometer connections  
Pressure  
Suction  
Return to normal operation  
Inclined tube  
manometer  
When pressure reading is correct and air pressure  
switch is operating properly — remove tees and  
reinstall hoses to air pressure switch.  
White  
Flue collector  
Red  
The boiler will not operate correctly  
unless pressure switch hoses are  
correctly located. The red hose  
connects from the right side  
(negative) hose barb to the flue  
collector. The white hose connects  
from the left side (positive) hose  
barb of the switch to the connector  
box (between flue collector and  
inducer) as shown in Figure 24.  
White  
Red  
Rear  
panel  
Red  
White  
Interior panel  
Side  
panel  
26035  
42  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
11c  
Troubleshooting — control module  
Make sure ground wiring is installed  
per wiring diagram. Good  
grounding is extremely important  
for proper operation.  
Solder or water splatter between  
plugs and circuit board can cause  
improper operation of control  
module. Place a shield over the  
boiler internal controls and  
components during installation.  
Failure to comply could result in  
severe personal injury, death or  
substantial property damage.  
Control indicator lights —  
lockout modes  
See Charts 1 through 7 in this section for detailed  
troubleshooting procedures.  
To reset control after a lockout, turn off power at the  
120 VAC service switch or turn down all thermostats.  
Wait 45 seconds. Then restore power or call for heat.  
26036  
POWERlightflashingalone  
Control indicator lights —  
non-lockoutmodes  
Usually indicates reversed polarity of 120 VAC power  
wires.  
FLAMElight flashing alone  
POWER and TSTAT CIRC lights flashing  
Usually indicates pilot flame was not established within  
15 seconds from application of spark. Control will flash  
light, but will continue to cycle indefinitely until flame  
is established or problem is corrected.  
Usually indicates stray voltage on external thermostat  
circuit wires (usually due to miswired 3-wire zone  
valve).  
PRESS SWITCH light flashing alone  
POWER and PRESS SWITCH lights flashing  
Usually indicates pressure switch opened during the  
run cycle.  
Usually indicates pressure switch is closed when it  
should not be, or pressure switch failed to close within  
5 minutes of inducer starting.  
Troubleshooting the control  
module  
POWER and FLAME lights flashing  
Usually indicates false flame sense or flame sensed when See Figure 25 for location of harness plug receptacles  
it shouldn’t be there. and plugs on the control module.  
43  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
11c  
Troubleshooting — control modulecontinued  
Figure 25 Control module connections  
Black  
White  
Black  
120 VAC H  
120 VAC H  
Green  
Entrance  
ground  
High voltage to  
pilot spark electrode  
Green  
White  
Chassis  
ground  
SJO cable  
to J-box  
120 VAC N  
120 VAC to  
transformer  
120 VAC N  
Red wire to  
gas valve MV  
120 VAC IN  
Black wires to  
thermostat circuit  
Blue wire to  
gas valve PV  
White wire to  
gas valve MV/PV  
Yellow wires to limit control  
and rollout switch  
24 VAC  
Red wires to  
pressure switch  
24 VAC from transformer  
24 VAC control  
circuits  
FLAME  
Ground  
Green  
PRESS SWITCH  
LIMIT  
120 VAC H  
Black  
120 VAC N  
White  
TSTAT CIRC  
POWER  
120 VAC to  
inducer motor  
High voltage to spark electrode  
120 VAC to transformer  
120 VAC IN  
Yellow  
120 VAC H  
White  
120 VAC N  
24 VAC control circuits  
120 VAC to circulator  
24 VAC from transformer  
120 VAC to inducer motor  
120 VAC to circulator  
Sense wire to flame sensor  
26037  
Flame sense wire to pilot  
44  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
11d  
Troubleshooting — control module lights  
CHART 1 — Troubleshooting POWER light status  
— Usually indicates reversed 120 VAC polarity if POWER light flashes by itself —  
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow  
instructions could result in severe personal injury, death or substantial property damage.  
Is POWER light off?  
• Make sure service switch or circuit breaker is on or fuses  
are good.  
No  
Yes  
Remove 120 VAC IN plug (Figure 25, item 3, page  
44) on control module.  
• Using voltmeter, check across top and bottom pins of  
120 VAC IN plug.  
Is POWER light...  
Does voltmeter indicate 120 VAC?  
Flashing  
alone  
Flashing with  
another light  
On steady  
(not flashing)  
No  
Yes  
TSTAT CIRC  
light flashing  
Problem is with incoming  
electricity. Have licensed  
electrician repair circuit.  
Chart 2  
Chart 3  
Chart 4  
PRESS SWITCH  
light flashing  
Chart 5  
Chart 6  
FLAME  
light flashing  
• Reconnect 120 VAC IN plug.  
Remove 120 VAC transformer PRIMARY plug (Figure  
25, item 2, page 44) on control module.  
For insufficient heat or no heat problem, go to  
Chart 7 if POWER light is on steady, with no other  
light flashing.  
• Using voltmeter, check across top and bottom pins of  
PRIMARY receptacle.  
Does voltmeter indicate 120 VAC?  
No  
Yes  
• Usually indicates polarity on incoming 120 VAC power  
Replace control module.  
Retest.  
line is wrong.  
TURN OFF POWERat service switch or breaker,  
then reverse the HOT and NEUTRAL wires entering the  
boiler in the J-box.  
• Reinstall 120 VAC transformer PRIMARY plug.  
• Restore POWER at service switch or breaker.  
Remove 24 VAC transformer plug (Figure 25, item 5,  
page 44) on control module.  
Is POWER light flashing now?  
• Using voltmeter, check across pins of receptacle.  
No  
Yes  
Does voltmeter indicate 24 VAC?  
No  
Yes  
Have system checked by a  
licensed electrician.  
If problem persists, call your  
local Weil-McLain sales  
representative.  
Boiler should now  
operate normally.  
Replace transformer.  
Retest.  
Replace control module.  
Retest.  
45  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
11d  
Troubleshooting — control module lights  
CHART 2 TSTAT CIRC & POWER lights flashing  
— Usually indicates 48 VAC on thermostat circuit (stray voltage) —  
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow  
instructions could result in severe personal injury, death or substantial property damage.  
• Disconnect the two external wires connected to the boiler  
• If a voltage does occur under any condition, check and  
correct the external wiring. (This is a common problem  
when using 3-wire zone valves.)  
thermostat leads (two black low voltage leads in J-box).  
• Connect a voltmeter across these two incoming wires.  
Close each thermostat, zone valve and relay in the  
external circuit one at a time and check the voltmeter  
reading across the wires.  
• Once the external thermostat circuit wiring is checked and  
corrected if necessary, reconnect the external thermostat  
circuit wires to the boiler thermostat wires and allow the  
boiler to cycle.  
• There should NEVER be a voltage reading.  
Did you find a voltage across the two external thermostat circuit wires?  
Yes  
No  
• If no voltage is found under any condition of the external  
thermostat circuit, connect the two boiler thermostat  
connection leads together (or jumper the boiler aquastat  
T-T terminals).  
• Leave external boiler thermostat connection wires  
disconnected from boiler.  
• Troubleshoot the external thermostat circuit until you find  
the source of the stray voltage. (Pay close attention to  
the wiring connections to 3-wire zone valves.)  
• Turn off power to the boiler for 1 minute.  
• Turn on power and allow boiler to cycle.  
Do the TSTAT and POWER lights still flash?  
• Correct the problem and repeat the voltmeter test above,  
verifying there is no longer a voltage reading under any  
condition in the external thermostat circuit.  
No  
Yes  
• Boiler should now operate per the normal sequence of  
• Replace control module.  
• Retest.  
operation shown in Figure 18, page 31.  
46  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
continued  
CHART 3 PRESS SWITCH & POWER lights flashing  
— Usually indicates pressure switch stuck closed or failed to make within 5 minutes —  
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow  
instructions could result in severe personal injury, death or substantial property damage.  
• Reset boiler control by turning off power at service switch or turning down thermostat for at least 45 seconds.  
• Thermostat should call for heat and appropriate zone valves open.  
Does inducer motor operate?  
No  
Yes  
• Wait 45 seconds.  
Does inducer motor operate?  
No Yes  
• Remove INDUCER plug (Figure 25, Item 6, page 44)  
from plug receptacle of control module.  
• Place voltmeter leads across the 120 VAC N and  
120 VAC H pins of the INDUCER receptacle (left column  
center and right column bottom pins).  
• Wait 5 minutes.  
Is PRESS SWITCH light flashing?  
No  
Yes  
Does the voltmeter indicate 120 VAC?  
No  
Yes  
• Try reseating plug in  
module receptacle and  
restart.  
• If inducer still does not  
work, replace inducer  
assembly.  
• Boiler should be in  
normal operating  
sequence.  
• Observe operation until  
thermostat is satisfied  
and inducer has  
Are vent or combustion air  
passages blocked?  
• Retest.  
completed its post-purge  
cycle.  
• Remove one of the wires connected to the pressure  
switch.  
No  
Yes  
• Check continuity across the switch terminals.  
Does the ohmmeter indicate the switch is closed?  
No  
Yes  
• Check air pressure switch  
per manual Section 11.  
• Replace if necessary.  
• Retest.  
• Replace control  
module.  
• Retest.  
• Clear passages and  
recycle boiler.  
• Recheck boiler operation.  
47  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
11d  
Troubleshooting — control module lights  
CHART 4 FLAME & POWER lights flashing  
— Usually indicates flame sensed when it shouldn't be there —  
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow  
instructions could result in severe personal injury, death or substantial property damage.  
Are manual main shutoff valve and gas valve open?  
No  
Yes  
• Turn off power to the boiler at service switch or breaker.  
• Wait at least 45 seconds.  
• Turn on power to boiler.  
• Restart boiler, following Lighting instructions in this  
manual (Figure 21, page 34).  
• Look through the pilot inspection port (in front of air inlet  
box) to see if the pilot is burning during the prepurge  
period (first 30 seconds of operation).  
• Leave main manual gas valve closed.  
• Turn off power to boiler at service switch or breaker.  
• Wait at least 45 seconds.  
• Turn on power to boiler.  
• Restart boiler, following Lighting instructions in this  
manual (Figure 21, page 34).  
Do FLAME and POWER lights still flash?  
Is pilot burning during prepurge period?  
No  
Yes  
No  
Yes  
• Replace control module.  
• Retest.  
• Replace gas valve.  
• Retest boiler.  
• Allow boiler to continue cycling.  
Are FLAME & POWER lights flashing?  
Are FLAME and POWER lights flashing?  
No  
No  
Yes  
Yes  
• Boiler may now be  
operating  
• Replace control  
module.  
• Boiler should now  
operate normally.  
• Replace control  
module.  
TURN OFF POWER▲  
to boiler at service switch  
or breaker.  
normally.  
• Retest.  
• Original flashing  
FLAME light  
caused by gas  
valve not  
• Retest.  
• Open main manual gas  
valve.  
• Turn on power to boiler  
at service switch or  
breaker.  
• Restart boiler per lighting  
instructions.  
• Perform start-up  
procedures in boiler  
manual to verify proper  
operation.  
• Perform start-up  
procedures in  
boiler manual to  
verify proper  
operating  
properly.  
operation.  
• See normal  
sequence of  
operation,  
Figure 18,  
page 31.  
48  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
continued  
CHART 5 FLAME light flashing and POWER light on steady  
ALSO — Troubleshooting failure to establish main flame  
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow  
instructions could result in severe personal injury, death or substantial property damage.  
Are main manual shutoff valve and boiler gas valve open?  
No Yes  
Is pilot flame visible through inspection port?  
No  
Yes  
TURN OFF POWERto boiler at service switch or breaker.  
Open main manual shutoff valve and boiler gas valve (per  
Lighting instructions in this manual). Wait at least 45  
seconds.  
Turn on power at service switch or breaker. Allow boiler to  
cycle.  
Check the voltage across  
terminals "C" and "A" of the  
gas valve (see Table G,  
page 33).  
Make sure ground wire  
terminal is securely fastened  
to control module mounting  
screw.  
Is 24 VAC present there?  
Does FLAME light flash now?  
Yes  
No  
No  
Yes  
Check the voltage across  
terminals "B" and "A" (see  
Table G, page 33) of the  
gas valve.  
Verify inlet gas pressure at gas  
valve:  
If the wiring from the  
control module to gas  
valve is intact, replace the  
control module.  
Boiler should be in  
normal operating  
sequence.  
Natural gas — 5.0" w.c. min/14.0"  
w.c. max  
Is 24 VAC present there?  
Retest.  
Observe operation  
until thermostat is  
satisfied and blower  
has completed its  
post-purge cycle.  
No  
Yes  
Propane — 11.0" w.c. min/14.0"  
w.c. max  
Is gas present at gas valve inlet and  
within above range?  
Verify inlet gas pressure at gas valve:  
Yes  
No  
Natural gas — 5.0" w.c. min/14.0" w.c. max  
Propane — 11.0" w.c. min/14.0" w.c. max  
TURN OFF POWERto  
boiler at service switch or  
breaker.  
Remove air inlet box top  
(see Figure 27, page 54 for  
location).  
Is gas present at gas valve inlet and within above range?  
No Yes  
Contact gas supplier to correct  
pressure or gas supply.  
TURN OFF POWERto boiler at service switch or breaker.  
Check flame signal — Detach sense lead from igntion control  
(Figure 25, item 8, page 44).  
TURN OFF POWERto boiler  
at service switch or breaker.  
Remove air inlet box cover (see  
Figure 27, page 54 for location).  
Verify pilot gas line is not  
kinked, obstructed or damaged  
and is correctly attached to  
pilot and gas valve.  
Verify pilot ignition electrode,  
electrode ceramic and spark  
lead wire from control are in  
good condition. Spark gap  
should be approximately 1/8".  
Correct any above problems,  
replacing pilot if burner or  
wiring is damaged.  
Reinstall air box top to operate  
boiler for retest after any  
changes or corrections.  
Connect negative lead of MICROAMMETER to control sense  
terminal (Figure 25, item 8, page 44). Connect positive lead of  
MICROAMMETER to sense wire.  
DISCONNECT red wire connected to terminal "B" (see Table  
G, page 33) of the gas valve.  
Turn on power to boiler and allow to cycle. As soon as pilot is  
burning, the MICROAMMETER should read at least 1.0  
microamp.  
Verify pilot burner is securely  
attached to pilot bracket, bracket is  
securely attached to cross tie, and  
there is no corrosion on the parts  
which would affect the ground path  
for flame sense.  
Verify that pilot flame rod, flame rod  
ceramic and lead wire from control  
module to flame rod are in good  
condition.  
Is flame signal at least 1.0 microamp?  
No  
Yes  
If none of the previous steps  
(including replacing pilot)  
corrects problem, then replace  
the control module, reinstall air  
box cover and retest.  
If the wiring from the  
If none of the above corrects  
problem, then replace the  
control module, reinstall air box  
top, and retest.  
Correct any above problems,  
replacing pilot if burner or wiring is  
damaged.  
control module to gas  
valve is intact, replace the  
control module and retest.  
49  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
11d  
Troubleshooting — control module lights  
CHART 6 PRESS SWITCH light flashing and POWER light on steady  
— Usually indicates pressure switch opened during run cycle —  
— May also be caused by wind gusts in excess of 31 mph for non-direct vent sidewall-vented boilers —  
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow  
instructions could result in severe personal injury, death or substantial property damage.  
• Reset boiler control by turning off power at service switch or turning down thermostat for at least 45 seconds.  
• Thermostat should call for heat and appropriate zone valves open.  
Does blower motor operate?  
No  
Yes  
• Remove INDUCER plug (Figure 25, Item 6, page 44)  
from plug receptacle of control module.  
• Place voltmeter leads across the 120 VAC N and  
120 VAC H pins of the INDUCER receptacle (left column  
center and right column bottom pins).  
• Wait 5 minutes.  
Is PRESS SWITCH light flashing?  
Does the voltmeter indicate 120 VAC?  
No  
Yes  
No  
Yes  
• Replace inducer  
assembly.  
• Retest.  
• Boiler should be in  
normal operating  
sequence.  
• Observe operation  
until thermostat is  
satisfied and inducer  
has completed its post-  
purge cycle.  
• Remove one of the wires connected to the pressure  
switch.  
• Check continuity across the switch terminals.  
Does the ohmmeter indicate the switch is closed?  
No  
Yes  
• Inspect and check wire  
harness from control  
module to pressure switch.  
• Reseat connector in control  
module receptacle.  
Are vent or combustion air passages blocked?  
No  
Yes  
• If harness is intact and  
properly seated, but  
problem persists, replace  
control module.  
• Clear passages and recycle  
boiler.  
• Recheck boiler operation.  
• Check air pressure switch per manual Section 11.  
• Replace if necessary. Retest.  
• Retest.  
50  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
continued  
CHART 7 — Insufficient heat or no heat to system (POWER light on steady)  
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow  
instructions could result in severe personal injury, death or substantial property damage.  
• Has it been at least 5 minutes since setting thermostat to  
call for heat? If not, wait 5 minutes. Is system heating?  
• Is thermostat set to call for heat? Remove thermostat  
wires at boiler and check continuity across the two wires.  
If circuit isn't closed, check external thermostat (zone  
valve, relay, etc.) wiring. Correct problems and retry.  
• Reconnect external thermostat wiring at boiler.  
Is boiler System circulator operating?  
No Yes  
• Remove CIRCULATOR harness plug from  
CIRCULATOR plug receptacle (Figure 25, Item  
7, page 44). Check with voltmeter across pins of  
control module receptacle.  
Is thermostat circuit closed (continuity across wires)?  
Does voltmeter show 120 VAC across pins?  
No  
Yes  
No  
Yes  
• Boiler is in standby.  
• Set thermostat to call for  
heat and recheck  
operation.  
• Verify Sequence of  
operation, Figure 18,  
page 31.  
Are all red lights off?  
• Repair/replace  
circulator. Retest.  
• Repair/replace  
wiring. Retest.  
• Replace control  
module.  
• Retest.  
No  
Yes  
Wait 30 seconds.  
Are all red lights off?  
• Wait 5 minutes.  
No  
Yes  
Is FLAME light on?  
Yes  
No  
Replace control  
module. Retest.  
• If you have sufficient heat — boiler should be in normal  
operating sequence. (See normal sequence of  
operation, Figure 18.)  
Is LIMIT light on?  
No  
Yes  
• If you have less than sufficient heat —  
Is vent or combustion air piping free of blockage?  
• Check limit switch  
contacts with continuity  
checker.  
• Replace control module.  
• Retest.  
No  
Yes  
• Correct conditions and  
recheck operation.  
• See Figure 18, page 31  
for normal sequence of  
operation.  
Contact your Weil-McLain  
sales representative.  
Are limit switch contacts  
closed?  
Check rollout switch  
continuity — is switch  
closed?  
No  
Yes  
No  
Yes  
• Wait for boiler water to cool to temperature 20 to 30 ˚F  
lower than temperature set on limit switch.  
Are limit switch contacts closed?  
• Replace rollout switch.  
No  
Yes  
• Check any other  
limit controls wired  
into the limit  
circuit. If all are  
OK, then replace  
control module.  
• Retest.  
If rollout thermal fuse element has  
opened, determine cause and  
correct condition. Failure to do so  
will cause severe personal injury,  
death or substantial property  
damage.  
• Boiler water temperature exceeded  
setting on limit switch with thermostat  
calling for heat. Boiler is OK. (See normal  
sequence of operation, Figure 18, p. 31.)  
• Also check setting on limit switch (should  
be above 140˚F.).  
• Replace  
limit switch.  
• Retest.  
51  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
12a  
Replacement parts  
Section assembly................................................ 53  
Base assembly .................................................... 54  
Jacket assembly ................................................. 55  
Trim assembly..................................................... 56  
Gas control assembly ......................................... 57  
Replacement parts must be purchased through a local Weil-McLain  
distributor. When ordering, specify boiler model and size and include  
description and part number of replacement part. Results from using  
modified or other manufactured parts will not be covered by warranty  
and may damage boiler or impair operation.  
Weil-McLain part numbers are found in Weil-McLain Boilers and  
Controls Repair Parts Lists.  
The boiler contains ceramic fiber and fiberglass materials. Use care when  
handling these materials per instructions on page 60 of this manual. Failure  
to comply could result in severe personal injury.  
52  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler  
13a  
Dimensions  
Figure 31 Dimensional drawing  
3"/3½" Dia. air pipe connection  
Gas supply piping  
Supply piping (note 1)  
Return piping (note 1)  
Relief valve, ¾" NPT  
11¹⁄₈  
Drain valve  
Gas supply entrance (right or left side)  
Pressure/temperature gauge  
½" NPT to expansion tank/air vent  
3" Diameter vent  
3¹⁄₄  
Note1: Boiler supply and return tappings are both 1¼" NPT.  
See Table 3, page 14 for recommended system sup-  
ply andreturn pipingsizes.  
2¹⁄₄  
A
TOP VIEW  
Note2: Boiler circulator is shipped loose. Circulator may be  
mounted on either boiler supply or return piping.  
Circulator flange provided with boiler is same size as  
recommended pipe size in Table 3, page14.  
A LL DIMENSIONS IN INCHES  
2³⁄₈  
13¹⁄₄  
4³⁄₄  
4³⁄₄  
NOTE 2  
NOTE 2  
28³⁄₈  
19  
19  
13¹¹ꢀ₁₆  
12  
9
W
23¹⁄₄  
1⁵⁄₈  
26060  
LEFT SIDE  
FRONT  
R IGHT SIDE  
Boiler  
model  
Supply  
tapping  
Return  
Gas  
Gas  
“A”  
“W”  
tapping connection size manifold size  
Air inlet  
pipe center  
(inches)  
Jacket  
width  
(inches)  
number (inches NPT) (inches NPT)  
Note 3  
(inches NPT)  
Note 3  
(inches NPT)  
CGs-3  
CGs-4  
CGs-5  
CGs-6  
1 ¼  
1 ¼  
1 ¼  
1 ¼  
1 ¼  
1 ¼  
1 ¼  
1 ¼  
½
½
½
½
½
½
½
½
6 ½  
8
13  
16  
19  
22  
9 ½  
11  
Note 3: Gas piping from meter to boiler to be sized per local utility requirements.  
58  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boiler Manual  
13b  
Ratings  
DOE  
(Note 5)  
Table 7 Boiler ratings  
Boiler  
model  
number  
DOE  
Heating  
capacity  
(Btuh)  
0-2,000 feet  
2,000-4,500 feet  
Net  
Boiler  
water  
content  
DOE  
Vent  
size  
I=B=R  
ratings  
(Btuh)  
Seasonal  
efficiency  
(% AFUE)  
Input  
Output  
(Btuh)  
Input  
Output  
(Btuh)  
(Btuh)  
(Btuh)  
(gallons)  
(Note 1)  
(Note 2)  
(Note 3)  
(Note 5)  
(Note 4)  
3"  
CGs-3  
(Note 5)  
57,000  
67,000  
57,300  
85,000  
60,300  
90,000  
51,600  
76,500  
50,000  
1.5  
2.1  
2.7  
3.3  
85.3  
CGs-4  
CGs-5  
CGs-6  
85,000  
112,000  
140,000  
100,000  
74,000  
97,000  
84.6  
84.0  
83.4  
3"  
3"  
3"  
133,000 112,400  
167,000 140,300  
119,000  
150,300  
100,600  
126,300  
122,000  
Notes  
1. Add “PIN” for natural gas boiler - “PILfor propane gas  
boiler.  
2. Based on standard test procedures prescribed by the  
United States Department of Energy.  
3. Net I=B=R ratings are based on net installed radiation of  
sufficient quantity for the requirements of the building  
and nothing need be added for normal piping and  
pickup. Ratings are based on a piping and pickup  
allowance of 1.15. An additional allowance should be  
made for unusual piping and pickup loads.  
4. CGs boilers require special venting, consistent with  
Category III or IV boiler. Use only the vent materials and  
methods specified in CGs vent supplements. CGs boilers  
may be direct-vented (using 3" diameter air piping) as  
specified in the direct vent supplements.  
5. As an Energy Star Partner, Weil-McLain has determined  
that the CGs-3meets the Energy Star guidelines for energy  
efficiency.  
CGs boilers for residential radiant panel systems, converted gravity heating systems or other low water temperature  
applications should be installed with balancing valves and bypass piping equal to the supply and return size to  
avoid excessive flue gas condensation due to lower operating water temperatures. For alternate piping, contact  
your Weil-McLain sales office. CSA design certified for installation on combustible flooring. Tested for 50 psi  
working pressure.  
59  
Part number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GOLD CGs Gas-Fired Water Boiler — Boiler Manual  
Handling ceramic fiber and fiberglass materials  
REMOVAL OF COMBUSTION CHAMBER LINING OR BASE PANELS  
The combustion chamber lining or base insulation panels in this product contain ceramic fiber materials. Ceramic  
fibers can be converted to cristobalite in very high temperature applications. The International Agency for  
Research on Cancer (IARC) has concluded, "Crystalline silica inhaled in the form of quartz or cristobalite from  
occupational sources is carcinogenic to humans (Group 1).":  
Avoid breathing dust and contact with skin and eyes.  
Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements  
for cristobalite at the time this document was written. Other types of respirators may be needed depending  
on the job site conditions. Current NIOSH recommendations can be found on the NIOSH web site at  
numbers are also listed on this web site.  
Wear long-sleeved, loose fitting clothing, gloves, and eye protection.  
Apply enough water to the combustion chamber lining or base insulation to prevent airborne dust.  
Remove combustion chamber lining or base insulation from the boiler and place it in a plastic bag for  
disposal.  
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.  
NIOSH stated First Aid.  
Eye: Irrigate immediately  
Breathing: Fresh air.  
REMOVAL OF FIBERGLASS WOOL — OR —  
INSTALLATION OF FIBERGLASS WOOL, COMBUSTION CHAMBER LINING OR BASE  
PANELS:  
This product contains fiberglass jacket insulation and ceramic fiber materials in combustion chamber lining or  
base panels in gas fired products. Airborne fibers from these materials have been listed by the State of California  
as a possible cause of cancer through inhalation.  
Avoid breathing dust and contact with skin and eyes.  
Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements  
for fiberglass wool at the time this document was written. Other types of respirators may be needed  
depending on the job site conditions. Current NIOSH recommendations can be found on the NIOSH  
and phone numbers are also listed on this web site.  
Wear long-sleeved, loose fitting clothing, gloves, and eye protection.  
Operations such as sawing, blowing, tear out, and spraying may generate airborne fiber concentration requiring  
additional protection.  
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.  
NIOSH stated First Aid.  
Eye: Irrigate immediately  
Breathing: Fresh air.  
Weil-McLain  
500 Blaine Street  
Michigan City, IN 46360-2388  
60  
Part Number 550-110-260/0200  
Download from Www.Somanuals.com. All Manuals Search And Download.  

West Bend Wok 79586R
Whirlpool Dishwasher WDF510PAY User Manual
Xantech Speaker XOD65 User Manual
Xtant Speaker A212 User Manual
Yamaha DJ Equipment 01v User Manual
Zanussi Convection Oven 240204 User Manual
Zanussi Oven 238500 User Manual
Zanussi Oven ZOU 575 User Manual
Zanussi Range ZGF 782 User Manual
Zanussi Washer ZWX 1506 W User Manual