Ultimate Products Electric Heater AL User Manual

Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING: Improper installation,  
adjustment, alteration, service or  
maintenance can cause property  
damager, injury, or death. Read the  
installation, operating, and maintenance  
instructions thoroughly before installing or  
servicing this equipment.  
A.INSTALLATION INSTRUCTIONS  
A.1  
TECHNICAL DATA  
(a) General Information  
Model & Heat Input  
Information all units:  
Gas Supply Connection:  
½-inch NPT Male  
Electrical Supply: 120V, 1 phase, 60Hz  
Current Rating: 1.2 AMP MAX (Burner-0.3/Fan –  
0.9)  
Ignition: Electronic Program Start-up with  
Spark Ignition  
OPTIONS:  
1. Modify combustion chamber air intake for fresh air duct.  
2. Ultimate Products Black Bulb Thermostat.  
3. Control Panel with multi-zone capabilities. (Not A.G.A. Certified)  
4. Individual Heater Vent to Exterior.  
Notes:  
A. Heater is intended for heating non-residential indoor and outdoor spaces and  
should only be installed where flammable gases or vapors are not generally  
present.  
B. Indoor heaters may be suspended either horizontal or at an angle, or may be wall  
mounted. Outdoor heaters must be suspended horizontally. SEE SECTION A.3  
FOR CLEARANCES.  
C. Installation shall conform with local building code requirements and with National  
Fuel code ANSI-Z223.1.A. (Latest Edition) and section 7.8A-3; Z223.1 (Latest  
Edition).  
D. The unit shall be electrically grounded in accordance with National Electric Code  
ANSI/NFPA 70-1987.  
E. The heater may be installed in aircraft hangars when conformation with  
ANSI/NFPA 409-1985 for Aircraft Hangars and in automotive garages when  
conforming with ANSI-NFPA 88A (Latest Edition) for Parking Structures and  
ANSI/NFPA 88B (Latest Edition) for Repair Garages.  
Insure that minimum clearance will be maintained to vehicles parked below  
the heater.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 2 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pipe Capacities For Propane and Natural Gas  
Pipe Capacities For Propane in Thousands of BTUsPer Hour  
For pressure drop of 0.5” W.C., based on low-pressure piping based on 6 oz. per  
sq. in. pressure. Based on one Cubic Foot of Propane = 2500 BTUs.  
SIZE  
PIPE  
LENGTH OF STRAIGHT PIPE IN FEET  
INCHES  
15  
105  
425  
787.5  
1542.5  
2425  
5040  
13545  
28035  
30  
77.5  
300  
45  
65  
245  
60  
55  
212.5  
440  
770  
1212.5  
2520  
6772.5  
14017.5  
75  
50  
190  
90  
45  
172.5  
362.5  
630  
977.5  
2047.5  
5512.5  
11497.5  
105  
40  
160  
120  
150  
180  
210  
240  
270  
300  
450  
600  
½
¾
1
1¼  
1 ½  
2
150  
315  
137.5  
282.5  
487.5  
772.5  
1575  
125  
252.5  
440  
115  
237.5  
410  
107.5  
220  
385  
607.5  
1245  
3387.5  
6930  
102.5  
205  
362.5  
95  
80  
67.5  
137.5  
237.5  
377.5  
770  
197.5  
347.5  
542.5  
1117.5  
3072.5  
6300  
157.5  
282.5  
440  
897.5  
2520  
5040  
615  
505  
395  
330  
1070  
1700  
3490  
9607.5  
19687.5  
882.5  
1402.5  
2835  
7875  
16222.5  
677.5  
1070  
2205  
5985  
12600  
582.5  
912.5  
1890  
5197.5  
10710  
542.5  
857.5  
1732.5  
4882.5  
9922.5  
700  
645  
575  
1417.5  
3937.5  
8032.5  
1322.5  
3622.5  
7560  
1165  
3232.5  
6615  
3
4
4252.5  
8820  
2127.5  
4410  
Pipe Capacities For Natural Gas In Thousands of BTUs Per Hour  
For pressure drop of 0.5” W.C. pressure. Based on one Cubic Foot on Natural  
Gas = 100 BTUs.  
SIZE  
PIPE  
INCHES  
LENGTH OF STRAIGHT PIPE IN FEET  
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
125  
150  
175  
200  
300  
400  
500  
600  
700  
800  
1000  
½
¾
170  
360  
118  
245  
95  
198  
80  
169  
71  
150  
64  
135  
60  
123  
55  
115  
52  
108  
49  
102  
44  
92  
40  
83  
37  
77  
34  
71  
27  
57  
23  
48  
21  
43  
19  
39  
1
540  
440  
790  
1200  
2225  
3525  
6500  
9500  
325  
660  
1000  
1855  
3000  
5300  
7880  
285  
570  
865  
1600  
2600  
4600  
6780  
9450  
250  
510  
780  
1450  
2350  
4435  
6140  
8500  
225  
465  
720  
1375  
2175  
3780  
5670  
7880  
215  
440  
670  
1250  
2025  
3530  
5280  
7325  
195  
410  
620  
1175  
1890  
3290  
4940  
6870  
185  
390  
600  
1120  
1810  
3140  
4685  
6550  
177  
375  
570  
1075  
1745  
3020  
4300  
6300  
155  
355  
510  
970  
1570  
2905  
4000  
5600  
140  
305  
455  
880  
1420  
2840  
3660  
5125  
130  
280  
430  
820  
1315  
2450  
3380  
4760  
120  
260  
400  
760  
1225  
2140  
3185  
4400  
100  
205  
315  
610  
80  
70  
165  
240  
470  
740  
1210  
1890  
2870  
65  
57  
125  
195  
390  
620  
930  
1545  
2400  
48  
115  
180  
365  
570  
900  
1445  
2100  
40  
100  
150  
320  
500  
760  
1245  
1800  
1 ¼  
1 ½  
2
2 ½  
3
1125  
1700  
3100  
5040  
9100  
180  
265  
530  
845  
1385  
2300  
3010  
140  
215  
420  
660  
1085  
1690  
2670  
995  
1640  
2500  
3145  
3 ½  
4
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 3 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A.2  
PACKAGING AND SHIPPING INFORMATION  
See Appendix ‘A’ for assembly drawings. Materials lists with part numbers and  
descriptions for each part will accompany each shipment.  
Heaters include: Burner/Control  
Radiant Tubes  
Reflectors  
Brackets  
Vacuum Fan  
U-Bend (U-Tube Units only)  
Wiring Junction Boxes (Straight Tube Units Only)  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 4 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A.2  
PACKAGING AND SHIPPING INFORMATION (CONT.)  
Options:  
Fresh air Intake (Mounted to Burner/Control)  
Fan Vent Adapters- Vertical and Horizontal  
Thermostat  
Flexible Gas Connector  
Ball Valve  
Vent Hoods  
Hanging Assembly (chain, etc.)  
Shipping packages for individual projects will be boxed and crated as outlined  
on the specific bill of lading.  
A.3  
MOUNTING CLEARANCES  
The heater should be positioned so that clearances from combustible materials  
will meet or exceed those shown in the following table. Also, ensure that there is  
at least 6” clearance on all sides of burner for service access and for free flow of  
combustionair. When heater is angle mounted, the burner/control assembly  
must remain horizontal.  
Minimum Clearances To Combustibles In Inches  
Model  
Input – BTU / HR  
40,000  
A
B
D
4
*
*
*
12  
12  
12  
E
6
6
6
6
6
6
6
GH / ER / AL / SC 12  
GH / ER / AL / SC 15  
GH / ER / AL / SC 18  
GH / ER / AL / SC 22  
GH / ER / AL / SC 29  
GH / ER / AL / SC 38  
GH / ER / AL / SC 44  
43  
66  
66  
66  
72  
72  
93  
20  
20  
20  
20  
30  
30  
36  
50,000  
60,000  
75,000  
100,000  
130,000  
150,000  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 5 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A.3  
MOUNTING CLEARANCES (CONT.)  
MOUNTING HEIGHT ABOVE FLOOR  
Mounting  
Position  
40,000 – 75,000 B.T.U 100,000 – 130,000 B. T. U.  
150,000 B. T. U  
Horizontal  
Recommended  
Minimum  
14 ft  
12ft  
16ft  
14ft  
18ft  
16ft  
Inclined  
Recommended  
Minimum  
11ft  
10ft  
13ft  
12ft  
15ft  
14ft  
Ensure that there is adequate provision in the building for combustion and  
ventilating air supply. Installation must meet minimum requirements of applicable  
codes.  
When installed in public garages and airplane hangars ensure that minimum  
clearances specified in ANSI/NFPA 88A or B, ANSI/NFPA 409, respectively, are  
met; and in no case less than those in the preceding tables.  
A.4  
PRE-ASSEMBLY  
Each heating unit is assembled as follows:  
Note that the emitter tube consists of more than one tube. The tube to be  
connected to the burner box is the thinner stainless steel or aluminized steel  
tube. Other tubes may be mild (thicker tubes), stainless or aluminized steel.  
Connections between tubes is by a coupling with three bolts. The coupling has  
an inner compression sleeve that holds the pipe securely when the nuts are  
turned tight.  
Support the assembled radiant tube with screws facing upwards, on blocks, etc.  
at least 6” above floor level, preferably under the position of installation. Ensure  
that the tube is clear internally.  
Slip the suspension brackets onto the tube assembly and attach by means of “U”  
bolts and nuts. Note that there are two types of brackets; type C and type B.  
Type C attaches reflectors together. Bracket C & B are placed on the assembled  
radiant tube in position shown on the assembly drawing in APPENDIX “A”.  
Tighten nuts to secure brackets to the tubes at spacing indicated with all brackets  
oriented in the same level position.  
NOTE: CLOSE ALL S-HOOKS TO INSURE THAT THE CHAINS DO NOT  
COME OFF OF THE HOOK.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 6 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A.5  
INSTALLATION  
Heater units: At this point raise the tube assembly into position and suspend from  
previously fixed chains (9 gauge min. galvanized welded link construction), or  
attach to wall mounting brackets. Wall mounting brackets must support heater at  
an angle of inclination of 45° ±10°. Longer tube assembly may be raised in more  
than one sub-assembly with final tube connection made in the air.  
It is recommended that the heater be suspended to slope slightly downward from  
the burner approximately 1 inch in 20 feet, but not more than 2-inches total.  
Remove the protective plastic film from the reflector surface. Note that each  
section ofreflector has two holes punched at one end. This end is firmly fixed by  
bolting to the lugs provided on the reflector bracket type C. The other end of each  
reflector section is free floating in suspension bracket type B thereby allowing for  
thermal expansion.  
Position reflector sections so that ends with holes lap at type C brackets and  
secure with nuts, bolts, and large washers provided in the burner box crate.  
Reflector should be allowed free movement through brackets type B. Note:  
Reflectors may be installed before tube is raised to position at installer’s option.  
Slide burner/control assembly onto the burner end of the radiant tube ensuring it  
is fully engaged and upright, (i.e. with air inlet cover plate facing upwards) and  
secure with locking screws provided.  
Slide the fan assembly on the opposite end of radiant tube, ensuring that it is fully  
engaged with fan outlet facing horizontally for outdoor installations and for indoor  
installations either unvented or with horizontal thru wall venting. Fan outlet should  
face upward for vertical venting thru the roof.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 7 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A.6  
GAS CONNECTION  
The gas connection on the heater is ½” NPT external thread.  
SERVICE REQUIREMENTS  
NAT. GAS  
L.P. GAS  
Max. inlet gas supply pressure (in.w.c.)  
Min. inlet gas supply pressure (in.w.c.)  
10.0  
6.5  
14.0  
11.0  
Injector sizes and manifold pressure for the burner are shown in the attached  
table for all heater units.  
The gas supply piping and connections must be installed so that the minimum  
pressure stated is achieved.  
A gas shut-off valve and union should be fitted in the gas supply line close to the  
heater, and a 1/8 inch N.P.T. plugged tapping, accessible for test gauge  
connection, provided immediately upstream of the appliance gas inlet.  
It is essential to provide some flexibility in the final gas connection preferably by  
use of an approved armored flexible connector or stainless steel expansion loop.  
(See Appendix ‘A’)  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 8 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Air Inlets  
(Inches/ Millimeters)  
Natural Gas  
Orifice  
Liquid Petroleum  
Orifice  
Model Designation  
Input  
KW  
BTU/HR  
Injector  
Diameter  
(inches )  
Manifold  
Pressure Diameter  
(in.W.C.)  
Injector  
Manifold  
Pressure  
(in./mm)  
Model Tube  
Configuration  
Tube Dia.  
(In)  
Burner Intake  
(in. / M.M.)  
Fan Inlet  
(in. / M.M.)  
(inches)  
GH/ER/AL/SC  
GH/ER/AL/SC  
12/40,000  
15/150000  
S-20  
S-25  
S-30  
U-20  
U-30  
S-20  
S-25  
3"  
3"  
3"  
3"  
3"  
3"  
3"  
1.125"/29mm  
1.125"/29mm  
1.125"/29mm  
1.125"/29mm  
1.125"/29mm  
1.312"/33MM  
1.125"/29 MM  
1.312"/33mm  
1.438" /37mm  
1.438" /37mm  
1.187/30mm  
1.187/30mm  
1.438"/37 MM  
1.438"/37 MM  
0.130"  
0.130"  
0.130"  
0.130"  
0.130"  
0.130"  
0.130"  
1.9  
1.9  
1.9  
1.9  
1.9  
3
0.080"  
0.080"  
0.080"  
0.080"  
0.080"  
0.080"  
0.080"  
6.7  
6.7  
6.7  
6.7  
6.7  
6.7  
6.7  
3
S-30  
U-20  
U-30  
S-20  
S-25  
S-30  
S-40  
S-20  
S-30  
S-40  
S-20  
S-25  
3"  
3"  
3"  
3"  
3"  
3"  
3"  
3"  
3"  
3"  
3"  
3"  
1.125"/29 MM  
1.312"/33MM  
1.312"/33MM  
1.750"/44 MM  
1.312"/33 MM  
1.312"/ 33 MM  
1.312" /33 MM  
1.312" /33 MM  
1.312" /33 MM  
1.312" /33 MM  
1.750"/44 MM  
1.750"/44 MM  
1.438"/37 MM  
1.438"/37 MM  
1.312"/33 MM  
2.00"/50 MM  
1.438"/37 MM  
1.438"/37 MM  
1.438"/37 MM  
1.750"/44MM  
1.438"/37 MM  
1.312"/33MM  
2.625"/67 MM  
2.00"/50 MM  
0.130"  
0.130"  
0.130"  
0.161"  
0.161"  
0.161"  
0.161"  
0.161"  
0.161"  
0.161"  
0.161"  
0.161"  
3
0.080"  
0.080"  
0.080"  
0.098"  
0.098"  
0.098"  
0.098"  
0.098"  
0.098"  
0.098"  
0.098"  
0.098"  
6.7  
6.7  
6.7  
6.7  
6.7  
6.7  
6.7  
6.7  
6.7  
6.7  
10.5  
10.5  
3
3
GH/ER/AL/SC  
18/60,000  
2.4  
2.4  
2.4  
2.4  
2.4  
2.4  
2.4  
3.8  
3.8  
GH/ER/AL/SC 22/75,000  
S-30  
S-40  
U-20  
U-30  
U-40  
S-40  
S-50  
S-60  
U-35  
S-40  
S-50  
S-60  
U-35  
3"  
3"  
3"  
3"  
3"  
4"  
4"  
4"  
4"  
4"  
4"  
4"  
4"  
1.750"/44 MM  
1.750"/44 MM  
1.750"/44 MM  
1.750"/44 MM  
1.750"/44 MM  
2.312"/59 MM  
2.312"/59 MM  
2.312"/59 MM  
2.312"/59 MM  
2.312"/59 MM  
2.312"/59 MM  
2.312"/59 MM  
2.312"/59 MM  
2.00/50 MM  
1.75"/44MM  
2.625"/67 MM  
2.00/50 MM  
2.00/50 MM  
2.00"/50 MM  
2.00"/50 MM  
2.00"/50 MM  
2.00"/50 MM  
2.625"/67MM  
2.625"/67MM  
2.625"/67MM  
2.625"/67MM  
0.161"  
0.161"  
0.161"  
0.161"  
0.161"  
0.182"  
0.182"  
0.182"  
0.182"  
0.206"  
0.206"  
0.206"  
0.206"  
3.8  
3.8  
3.8  
3.8  
3.8  
4.9  
4.9  
4.9  
4.9  
4.9  
4.9  
4.9  
4.9  
0.098"  
0.098"  
0.098"  
0.098"  
0.098"  
1.20"  
10.5  
10.5  
10.5  
10.5  
10.5  
10  
GH/ER/l/SC  
29/100,000  
1.20"  
10  
1.20"  
10  
1.20"  
10  
GH/ER/AL/SC 38/130,000  
0.136"  
0.136"  
0.136"  
0.136"  
10  
10  
10  
10  
S-40  
S-50  
4"  
4"  
2.312"/59 MM  
2.312"/59 MM  
4.00"/100MM  
4.00"/100MM  
0.228"  
0.228  
4.6  
4.6  
0.149"  
0.149"  
10  
10  
SC/ER/GX  
44/150,000  
S-60  
U-35  
4"  
4"  
2.312"/59 MM  
2.312"/59 MM  
4.00"/100MM  
4.00"/100MM  
0.228  
0.228  
4.6  
4.6  
0.149"  
0.149"  
10  
10  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 9 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A. 7 ELECTRICAL CONNECTION  
(a)  
Burner/Control Internal Wiring  
IMPORTANT: All electrical work should be done by a qualified  
electrician in accordance with the National Electrical Code  
ANSI/NFPA 70.  
Supply: 120 V, 60 Hz, single phase  
Current Rating: 0.3 amp max  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 10 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A. 7 ELECTRICAL CONNECTION (CONT.)  
The electrical supply to the heater is by three wires: live, neutral and ground  
connections. It is recommended that the supply cable be in metallic conduit to  
the 3/4'” hole provided.  
Power is ONLY supplied to the terminal in the back of burner as shown below:  
Power is supplied to fan through the knock out on the side of the burner housing.  
Fan leads should be connected to the burner leads using the wire nuts provided.  
Connect yellow/green wire from fan, to green wire of the burner, connect either  
black wire from the fan, one to the white and one to the black/brown of burner.  
Insure that conduit clamp is firmly tightened.  
It is recommended that the electrical circuit controlling the heater or group of  
heaters include thermostats, a time switch and if required manual control  
switches. All such controls and switchgear must be rated to handle the total  
inductive load of the circuit they control. For large installations, the use of relays  
or contractors should be considered.  
Control panels are available from the manufacturer incorporating multiple Black  
Bulb Thermostats controlling up to 10 heaters per thermostat for zone control of  
the heated area. Typical External Wiring is shown in diagram. (Control panels are  
not A.G.A. design certified.)  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 11 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A. 8 VENT REQUIREMENTS AND DETAILS  
(1) UNVENTED UNITS: Heaters may be installed without a flue providing the  
governing building codes are met and that consideration is properly given to  
possibilities of condensation on cold surfaces.  
Installation shall meet the following requirements when unvented:  
(A) Internal volume of the heated room must be greater than 214 cu. ft. per  
100 BTU/HR of heaters installed.  
(B) Natural or mechanical means shall be provided to supply and exhaust at  
least 4 CFM per 1,000 BTU per hour input of installed heaters.  
(C) Combustion gases shall not impinge on combustible materials with a  
temperature in excess of 150° F.  
(D) The blower discharge must be horizontal.  
(2) VERTICAL VENTING: The heater may be installed with a vertical flue. A  
down vent elbow must be fitted to the induced draft fan exhaust outlet, which  
should be rotated to a vertical position.  
A vent elbow designed to accept a 6-inch nominal sheet metal flue pipe is  
available as an optional extra.  
All flue piping should be adequately supported from the building structure and  
terminated with an approved terminal. The maximum flue length is 30 ft. with  
a maximum of two bends. All connections should be properly sealed.  
Generally, terminal may be located horizontally a dimension equal to its  
vertical dimension.  
(3) HORIZONTAL VENTING: Individual units may be vented horizontally  
through side walls. Venting must be installed inaccordance with ANSI  
Z2223.1 (NFPA-54) and local codes.  
Maximum length of vent is 25 ft. with 2-90 degree long radius elbows.  
Runs of 12 ft. or shorter can use 4-inch diameter flue with Ultimate Products  
part number V0200.  
Runs over 12 ft. should use 6-inch dia. flue pipe. Any portion of flue that  
passes through a combustible wall must be insulated or use an approved  
insulating thimble.  
Recommended parts are Ultimate Products’ (Part # V-0200) for 4-inch flue  
and (Part # V-0800) for 6-inch flue. Standard vent terminals must extend at  
least 6-inches from the wall and at least 24-inches from any combustible  
overhang. Protect the building material from degradation by flue gases.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 12 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A. 8 VENT REQUIREMENTS AND DETAILS (CONT.)  
Flue joints should be sealed using RTV high temperature sealant and secured  
using at least three (3) sheet metal screws. Should condensation occur flue  
should be shortened or insulated.  
The terminal must exit the building at least 7 ft. above any area accessible to  
the public.  
The terminal must be at least 3ft. away from any air intake to the building.  
If the heater is equipped with ducted combustion air, the terminal must be at  
least 3 ft. away from the air inlet and located higher than the inlet.  
The vent terminal must be protected from blockage by snow.  
A.9  
FRESH AIR DUCTED INTAKE  
Whenever the heater is installed in locations where air born dust or other polluted  
atmosphere is present; a fresh air supply should be ducted to the burner.  
A heater modified for fresh air intake should be specified when ordering. This  
model is modified with a 4-inch diameter duct connection at the burner.  
A fresh air duct of 4-inch diameter should be installed from the fresh air to the air  
intake connection on the burner housing. A flexible jointing piece should be  
installed at the burner connection with hose clamps to facilitate the disconnection  
when servicing the burner assembly.  
The maximum recommended length of fresh air duct is 25 feet and the  
maximum number of bends is two (2). The minimum length is 18 inches. The  
location of the fresh air duct inlet must be where it will receive dust free clean air.  
An Ultimate Products inlet cap with bird screen must be fitted at the inlet of the  
duct. If the duct inlet is located above the roof the underside of the inlet terminal  
must be at least 2 ft. above roof level and at least 10 inches above any projection  
on the roof within 7 ft. of the inlet.  
See Appendix ‘A’ for typical installation drawing and Ultimate Products part  
numbers. Intake pipe, fittings, and sealant are not furnished by Manufacturer.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 13 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A.10 INSTALLATION CHECK OUT AND START UP  
Inspect installation and ensure that it has been carried out in accordance with  
these instructions. Ensure that electrical and gas supplies are isolated.  
The gas supply should be purged and tested for soundness in accordance with  
Local and National Safety codes.  
Open isolating gas valve and test gas connections for soundness using soap  
solution.  
Remove burner cover plate by unscrewing 6 screws. Take care not to damage  
the sealing gasket. Inspect the burner and electrode assemblies ensuring these  
are securely fixed and all electrical connections securely made. Replace the  
burner cover plate ensuring that the sealing gasket is correctly positioned and the  
six screws are fully tightened. The heater will not operate until this plate is  
refitted.  
Remove the control housing cover plate by unscrewing the five securing screws.  
Ensure all internal components are securely fixed and all connections securely  
made. Open the manual gas valve.  
Switch on the electrical supply to the heater and observe the correct start up  
sequence. Ensure that the settings of any time switch and thermostat are such  
that the heating system will be required to operate.  
The fan will start to run and “Power On” lamp will illuminate. Safe-start checks  
are carried out automatically.  
After the fan has run up to full speed and a satisfactory vacuum condition has  
been established, ignition sequence will commence. The spark ignition will be  
energized producing a spark at the ignition electrode. The gas valve will at the  
same time be energized.  
If the ignition is successful the flame sensing probe and the ignition spark is  
switched off. The ‘burner on” lamp indicates that the gas solenoid valve is  
energized.  
If ignition is unsuccessful the gas valve will close and the spark ignition de-  
energized after approximately 6 seconds. For approximately 10 to 20 seconds  
the fan will purge the system then re-ignition will be attempted. After three (3)  
attempts at ignition the control unit will “lock-out” - the “power on” lamp will  
remain illuminated and the fan will continue to run. To reset after “lock-out” switch  
off the power supply to the system and wait 5 minutes. Then turn the power on.  
If repeated “locked-out” occurs investigate the cause.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 14 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A.10 INSTALLATION CHECK OUT AND START UP (CONT.)  
To shut down the heater, switch off the power supply to the system. Automatic  
control of the heater or a series of heaters may be achieved by incorporating  
thermostats, time switches, manual over-ride switches etc. in the electrical supply  
to the heater(s). It is essential to allow a delay of 15 seconds after switching off  
the system before attempting to restart.  
If at any time after completion of the start up sequence, loss of flame should  
occur, the control unit will attempt to reignite. If this is unsuccessful lock out will  
occur.  
Set burner gas pressure as follows. Switch off the power supply to the heating  
system. Connect a ‘U’ tube manometer to the pressure test nipple provided on  
the combination gas control valve. Remove the cover from the pressure regulator  
revealing the adjustable screw. Start the heater and using a suitable screwdriver  
adjust the pressure regulator, turning the screw clockwise to increase the  
pressure or counter clockwise to decrease the pressure. Set the pressure to  
appropriate in w.c. from the table of dimensions for correct heater description.  
Switch off the power supply to the heating system. Disconnect ‘U’ tube  
manometer and securely replace screw in pressure test nipple. Replace cover  
screw on pressure regulator.  
Check the operation of the flame safeguard equipment as follows: With the  
heater running normally, switch off the gas supply at the shut off valve. The  
heater should attempt to relight and if the gas valve has been left off “lockout”  
should occur indicated by the “Power On” light only being illuminated and fan  
running.  
Check the operation of the vacuum proving switch as follows. With the heater  
running normally, pull off the silicone rubber tube connecting the vacuum switch  
to the combustion chamber. Within one second, the burner should shut off. Then  
replace the tube securely and observe that the heater proceeds to ignite in the  
normal way.  
Replace the controls cover securing the five fixing screws.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 15 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. SERVICE AND MAINTENANCE  
INSTRUCTIONS  
B.1 SERVICING INSTRUCTIONS  
Under normal working conditions, it is recommended that the Ultimate Products  
Heater should be serviced annually. In exceptionally dirty or dusty conditions  
such as may occur in a foundry, more frequent servicing may be desirable.  
Servicing work should be carried out by a qualified gas service engineer.  
IMPORTANT:  
1.  
2.  
Never rest anything, especially ladders, against the heater.  
Turn off gas and electrical supplies before servicing or repair work is  
started.  
3.  
Unless otherwise instructed, reassemble parts in reverse order to the  
following instructions.  
B.2 ROUTINE SERVICE  
A. FAN – Inspect the main fan propeller and remove any dust brushing with a  
soft brush. Similarly remove any dust from the finger guard covering the  
secondary (cooling) impeller and the mesh aperture in the motor cover. Ensure  
that the impeller turns  
freely and that there is not excessive play in the bearings.  
B. EMITTER TUBE – Brush away any dust on the exterior of the emitter tube.  
Inspect the emitter tube internally by removing the burner control box as directed  
in “D” below. If there is any appreciable build up of dust or deposits, the tube  
should be cleaned internally. The emitter tube may be cleaned by use of an  
industrial vacuum cleaner with a long extension tube, which is passed down the  
emitter tube.  
Replace the burner/control assemblies engaging them fully on their tubes and  
secure by tightening the screws ensuring that they are squarely positioned (i.e.  
with the air inlet cover plate facing upwards).  
C. REFLECTOR The condition of the reflector should be noted and any  
necessary cleaning performed. The reflectors can be simply removed for  
cleaning by removing the reflector clamp screws securing them to the  
suspension brackets and sliding them out of the suspension brackets. The  
reflector can be cleaned with a soft cloth and detergent in water.  
A mild non-abrasive metal polish may be used in cases of extreme discoloration.  
D. REMOVAL OF BURNER/CONTROL ASSEMBLY – Remove the burner/  
control assembly by disconnecting the gas and electrical supply (and fresh air  
inlet duct if fitted). Slacken the burner fixing screws and draw the assembly off  
the emitter tube.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 16 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E. BURNER NER/ELECTRODE ASSEMBLY – Inspect the burner/electrode  
assembly by removing the six screws securing the combustion chamber cover  
plate to top of  
control box, taking care not to damage the sealing gasket.  
Remove the burner head by unscrewing it from the injector taking care not to  
drop it on the leads of the ignition electrodes. Replace the electrode assembly if it  
is not in good condition. The assembly is removed by removing the screws which  
attach it to the bracket on the front wall of the combustion chamber. The  
assembly is then lifted out of the combustion chamber and the cable  
disconnected. If the electrode assembly is in good order check the spark  
electrode gap, this should be .125 inches ±.030 inches. Adjust the gap if  
necessary by bending the ground rod. Ensure the electrical connections are  
secure.  
Inspect the injector and clean as necessary using a soft bristle brush. To remove  
or replace the injector, with the burner head removed, unscrew the injector from  
its carrier using a wrench, on the hexagon portion of its body. When replacing the  
injector ensure that it is fully tightened in its carrier. (TIGHTEN SNUG -- DO NOT  
OVERTIGHTEN)  
Replace the burner head. Replace the combustion chamber top cover, renewing  
the rubber sealing gasket if this is not in good condition.  
Inspect the burner fresh air inlet duct if fitted and ensure that it is free of any  
blockage or obstruction. Inspect the air inlet terminal and ensure this is not  
liable to obstruction.  
Recheck the heater by following the procedure for check out and start up,  
taking care to check that the burner gas pressure is correctly set, and that the  
vacuum switch and flame safeguard equipment function correctly.  
F. AUXILIARY CONTROLS – Check that auxiliary controls such as room  
thermostats, time switches, etc. function correctly and are set to operate at the  
desired temperatures. Ensure that the user is aware of the functions of the  
auxiliary controls and their correct settings. For most efficient operation of the  
heating system the time switch, if fitted, should be set to switch on normally  
between ¼ hour and 1 hour before commencement of occupancy of the building  
depending on local conditions. The correct setting of the room thermostat can  
only be determined byexperience in cold weather when it should be set to shut  
off the heaters when a comfortable level of warmth has been achieved. This  
setting will normally be several degrees below that which would be required with  
a convective heating system.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 17 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. 3 REPLACEMENT OF COMPONENTS  
WARNING: TURN OFF GAS AND ELECTRICAL SUPPLIES  
BEFORE STARTING REPAIR WORK.  
A. TO REPLACE ANY COMPONENTS IN THE BURNER/CONTROL  
ASSEMBLY – This assembly should be removed from the heater by  
disconnecting the gas and electrical supplies (also the fresh air intake  
duct if used). Loosen the bolts and slide the burner/control assembly  
from the emitter tube.  
B. TO REPLACE ELECTRODE ASSEMBLY – Remove top cover of  
combustion chamber by removing six (6) screws. Remove the screws  
securing the electrode assembly and pull off the electrode cable  
connector. Reconnect the cable connector to the new electrode  
assembly and replace the assembly. Replace the cover plate and  
gasket. Spark electrode gap .125 ±.030”.  
C. TO REPLACE THE BURNER HEAD – Remove combustion chamber  
cover as in section B above. Unscrew burner head from injector. Screw  
on new burner head. Replace combustion chamber cover.  
D. TO REPLACE THE INJECTOR – SEE PAGE 17  
E. TO REPLACE COMBINATION GAS VALVE – Remove combustion  
chamber cover as in paragraph B. Remove control housing cover.  
Remove burner head as in paragraph C. Unscrew the gas supply pipe  
entering the combination gas valve. Remove the electrical connections  
from the valve. Remove the two (2) screws holding the gas valve. The  
combination gas valve can now be removed.  
Replace any defective component and reassemble using approved  
pipe joining compound on pipe threads.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 18 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F. TO REPLACE THE BURNER/CONTROL UNIT – Remove the control  
housing cover. After observing their positions, disconnect the wires to  
the burner control unit. Remove the screws securing the burner control  
unit to the base of the control housing. Remove the burner control unit.  
Install replacement unit, observing correct positions for color coded  
cables.  
G. TO REPLACE THE VACUUM SWITCH – Remove the burner control  
unit as in paragraph F. Disconnect the rubber tube connection at the  
vacuum switch. Disconnect push on connectors from the vacuum  
switch. Remove the screws securing the vacuum switch and slip the  
switch out of its bracket. Installing is the reversal of the above taking  
care to correctly reconnect the cables.  
H. TO REPLACE THE RELAY - Remove control housing cover. The  
relay is a plug-in type and can be changed without removing any other  
components. However, if necessary, remove the burner control unit to  
gain better access to the relay.  
B. 4 USERS INSTRUCTIONS  
Hand the Users Instruction to the user and explain how to operate the heater.  
Leave the Installation and Servicing Instructions with the service maintenance  
engineer or manager for use on future service calls.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 19 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
USER INSTRUCTIONS  
ULTIMATE PRODUCTS TUBULAR RADIANT HEATERS  
Ultimate Products is the distributor of a series of tubular infrared heaters  
designed for overhead heating of industrial and commercial buildings. Individual  
heating units are suspended from the roof or mounted at an angle on the wall  
when inside buildings or horizontal when outside.  
IMPORTANT  
1. This appliance must only be installed by qualified craftsman in accordance  
with the requirements of local and national codes.  
2. This appliance must be grounded in accordance with the National Electrical  
code ANSI/NFPA No.70.  
3. Never rest anything, especially ladders, against the heater.  
TO START THE HEATER  
1. First ensure that the gas supply to each heater is turned on by opening main  
gas shut-off valve and manual valve on combination control.  
2. Ensure that the settings of any time switch and thermostat are such that the  
heating system will be required to operate.  
3. Switch on the electrical supply to the heater. The fan will start, the “Power On”  
light on the burner will illuminate and ignition will commence.  
4. Ignition will occur and the burner light, colored orange, will illuminate.  
5. If ignition is unsuccessful the gas valve will close and the spark igniter de-  
energize after approximately six (6) seconds. For approximately 10 to 20  
seconds the fan will purge the system then re-ignition will be attempted. After  
three (3) attempts at ignition the control unit will lockout, the “power-on” lamp  
will remain illuminated and the fan will continue to run. To reset after  
“lockout”, switch off the power supply to the heater and wait 5 minutes. Then  
turn the power on. If repeated “lockout” occurs investigate the cause.  
TO SWITCH OFF THE HEATER  
Switch off the electrical supply. The burner will shut off and the fan will stop.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 20 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICING  
To ensure continued efficient and safe operation it is recommended that the  
heater be serviced regularly by a qualified person, e.g. every year in normal  
working conditions but in exceptionally dusty or polluted conditions more frequent  
servicing may be needed.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 21 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix A  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 22 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 23 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 24 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 25 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND  
0.25 BSSR  
1.0 BTL  
2BA RSE  
0.25” INSULATED FEMALE RECEPTACLE  
1.0mm2 NON-INSULATED BOOTLACE TERMINAL  
2BA RED SHROUDED EYELET  
0.187 BSSR  
0.25 NIFR  
5 NIFB  
0.187” INSULATED FEMALE RECEPTACLE  
0.25” NON-INSULATED FLAG TERMINAL  
5mm NON-INSULATED FEMALE BULLET  
WIRE SPECS:  
ALL ~ 18 A.W.G. UL 1015  
WIRE LENGTH TOL:  
+10 / -0  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 26 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 27 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 28 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Schematic  
(Part #: S-0500A)  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 29 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 30 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 31 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 32 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 33 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 34 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 35 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 36 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 37 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 38 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 39 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 40 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 41 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 42 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 43 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 44 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 45 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 46 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 47 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 48 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 49 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 50 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 51 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 52 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 53 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX ‘B’  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 54 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 55 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2319 Laurelbrook Street, Raleigh, NC 27604 · (800) 542-7221 · FAX (919) 834-4526 · www.ultimate-products.com  
- 56 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Tascam CD Player LR 10 User Manual
Think Outside PDAs Smartphones Travel Mouse for Asus MyPal A620BT User Manual
Toastmaster Range RH36D4 User Manual
Toshiba DVD Player SD V296 User Manual
Tricity Bendix Washer AW 1100 S User Manual
Tripp Lite Surge Protector P050 008 User Manual
Uniden Two Way Radio POLARIS User Manual
Unified Brands Ventilation Hood Kitchen Ventilation Systems User Manual
Universal Remote Control Universal Remote MRF 300 RFX150 User Manual
Valor Auto Companion Inc Indoor Fireplace 1210DKA User Manual