| User’s and installer’s Manual   Sine wave Inverter, Battery charger, Transfersystem   HP-COMPACT - HPC 2800-12   HP-COMPACT - HPC 4400-24   HP-COMPACT - HPC 6000-48   HP-COMPACT - HPC 8000-48   Remote control RCC-01   Remote - Power sharing RPS-01   Temperature sensor CT-35   STUDER INNOTEC   Rue des Casernes 57   CH – 1950 Sion   TEL : ++41 (0)27 205 60 80   FAX : ++41 (0)27 205 60 88   E-MAIL : [email protected]   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   English description   1 General Information   1.1 Operating instructions   This manual is part of the delivery package of every HP-COMPACT inverter-charger.   It serves as guidelines for safe and efficient operation of HP-COMPACT. The   instructions are only valid for use with the following devices and options:   − HP-COMPACT : HPC 2800-12 – HPC 4400-24 – HPC 6000-48– HPC 8000-48   − Temperature sensor : CT-35   − Remote Control : RCC 01   − Remote power sharing : RPS-01   Every person who installs a HP-COMPACT and/or works with it must be fully familiar   with the content of this manual and must follow exactly all the warning and safety   instructions. Installation of or any work on the HP-COMPACT must be carried out by   a skilled and trained personnel. Installation and application must comply with the   respective local installations codes and safety regulations.   1.2 Quality and Warranty   During production and assembling, all HP-COMPACT appliances go through many   controls and tests. Production, controls and tests are carried out in accordance with   firm and established procedures. Every HP-COMPACT has its own serial number,   which helps to refer back to its original data in the event of controls or repairs. That is   why you should never remove the identification plate showing the serial number. The   production assembly and tests on all HP-COMPACT appliances are totally carried   out in our company in Sion, Switzerland. The warranty for these appliances is valid   for uses and operating possibilities mentioned in this manual.   The warranty period for the HP-COMPACT is 2 years.   1.3 Warranty Disclaimer   We do not accept any liability for any damages occurring through use, manipulation,   working situation and handling, which are not explicitly mentioned in these operating   instructions.   Following cases are not covered by the warranty:   − High voltage at INPUT (i.e. 48V at the Battery INPUT of HP-COMPACT 2800-   12)   − Reverse polarity on Battery connections (+/- reversed)   − Running liquid or oxidation through condensation in the appliance   − Defects caused by force, physical or mechanical means   − Changes not explicitly authorized by STUDER INNOTEC   − Not or only partly tightened screws and nuts after change of fuses or cables   connecting   − Transport damage, i.e. through bad handling and /or packing   − Damage from atmospheric over voltage (lightning)   HP-COMPACT V5.4   5/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   1.4 Liability Disclaimer   Respecting this manual, servicing and method of installation, functioning, application   and maintenance of the appliance can not be controlled or supervised by STUDER   INNOTEC. Hence we do not accept any liability and responsibility for damages,   losses and costs which result through the use of this appliance or which result   through incorrect installation, incorrect operation or wrong application and   maintenance, or which by some other means maybe connected to each other.   The use of STUDER INNOTEC’s inverters does exclusively involve the user’s   liability.   This device is not designed for applications involving health care and medical   treatments where the patient life is concerned and where any mishap may be lethal.   Similarly, we do not accept any liability for any violation of the patents rights or   violation of any third party’s rights resulting from the use of this appliance   STUDER INNOTEC reserves the right to modify the technical data or these operating   instructions without any prior notice.   1.5 Warning   This manual must be readily available for the user at any time. The user must be   familiar with the precautions and safety aspects in the country of installation.   During operation of HP-COMPACT, high voltages are generated at the connections   and inside of the appliance which could be lethal. Work on the appliance and on the   installation should only be carried out by skilled and trained people.   The whole installation connected with the HP-COMPACT must comply with the rules   and codes in force.   People without the written authorization from STUDER INNOTEC are strictly   forbidden to carry out any change or repair on the appliances. For authorized   changes only original parts are to be used.   The HP-COMPACT may only be used when it has been installed in accordance with   these instructions and all parts have been correctly assembled and installed.   The HP-COMPACT may only be connected to lead-acid or lead-gel batteries.   Caution: Even when a HP-COMPACT has been disconnected from all   connections, at the OUTPUT point there could still be deadly voltages present.   To remove these voltages you must switch on the HP-COMPACT ON with the   ON/OFF switch. After one minute the electronics are discharged and any work   can now be safely carried out.   The HP-COMPACT is only suitable for internal use and under no circumstances   should it be subjected to snow, rain, or any other wet conditions.   By installations in motorized vehicles the HP-COMPACT must be protected from   water-spray and any other wet conditions.   Caution: In normal use lead-acid and lead-gel batteries give out explosive   gases. Never smoke or allow a spark or flame in the vicinity of batteries. The   batteries must always be stored or placed in a well ventilated room, they   should be placed in such a way that there is no danger of short-circuit through   carelessness. Never charge frozen batteries.   1.6 Special precautions   − While working on batteries there should always be a second person close to you   or within your voice range, in case help is needed.   HP-COMPACT V5.4   6/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   − Plenty of fresh water and soap must be ready at hand so that in case of acid   coming in contact with skin, eyes and clothes, the areas in question can be   thoroughly washed.   − If acid enters the eyes, you must thoroughly wash them with cold running water   for at least 15 minutes. It is recommended that you immediately consult a   medical doctor.   − Baking powder neutralizes battery acid electrolyte. Always keep some at hand.   − Special care must be taken when working with metal tools near or on the   batteries. With tools such as screwdrivers, spanners etc. short-circuits can   result. Sparks produced by the short circuit can cause an explosion.   − When working on batteries all personal metal items such as rings, necklaces   and bracelets must be removed. Batteries are so powerful that short-circuit with   these items can melt them and thus cause severe burns. Always follow the   battery manufacturer instructions.   − Under certain conditions HP-COMPACT or a connected generator can start   automatically. While working on an electrical installation you must ensure that   these appliances are disconnected beforehand from the installation.   2 Introduction   The HP-COMPACT is a sine wave inverter with integrated battery charger with many   additional functions, it has been developed to be used as stand-alone (no grid-   feeding) AC provider, or as continuous / break-free current supply provider (UPS).   2.1 Principle schematic   Notes:   (1) The neutral of the appliance is not connected to the earth whatever the   function mode is. If requested and according to the local regulation, an automatic   HP-COMPACT V5.4   7/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   connection between Neutral and earth in inverter mode only may be done by   installing a bridge internally to the unit. Please contact your installer regarding this   point.   (2) Remote control for remote adjustment of the input limit. (see chap. 4.6.3)   2.2 Description of the main functions   2.2.1 The inverter   The sine wave inverter HP-COMPACT generates a sinusoidal AC voltage with an   exceptionally precise voltage and stabilized frequency. In order to start large electric   motors, the user has the possibility to use a short surge power which is 3 times the   nominal power of the HP-COMPACT.   The inverter is protected against overload and short circuit. A power stage with the   latest MOS-FET power transistors, a toroidal transformer, and a fast regulating   system makes a robust and reliable inverter with the highest efficiency. A 1-20 Watt   adjustable charge detection system allows the smallest energy consumption and   ensures a long life for the battery.   2.2.2 The transfer system   HP-COMPACT can be connected to an AC source. For example a stand-by   emergency generator or the AC network. With the transfer system, on one side you   have an alternating voltage at the output for the use of consumer appliances. On the   other side the battery park is being charged. The distribution of energy between the   consumer appliances and battery charger is automatic.   2.2.3 The battery charger   The built-in battery charger is so designed that it can charge the battery quickly and   fully. A microprocessor controlled, Step charging process, ensures the optimal   charging of the battery. The desired charging current can be set continuously from 0   to 70/90/100/110 A, as per the model. The setting is made accordingly to the battery   capacity and power available.   The battery charger is designed for lead-acid and lead-gel batteries. Thanks to the   floating charge system the batteries can remain continuously connected.   2.2.4 Remote control   As an option, a remote control RCC-01 can be connected to HP-COMPACT. All   operating features and displays, save the adjustment levels (22/23/24/26), are   available on the re-mote control. It is supplied with a 20m long cable. This cable can   be up to 40m long. On the remote control, output power and charging current are   also displayed.   2.2.5 Remote control for Power Sharing   This remote control RPS-01 can be connected to the HP-COMPACT in the gland for   the temperature sensor. The maximum current available from the energy source can   be adjusted by the turning button.   HP-COMPACT V5.4   8/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   2.3 Battery connecting   Lead-acid batteries are normally available in blocks of 2V, 6V or 12V. In most cases,   to generate the necessary operating voltage and the capacity of the batteries for the   HP-COMPACT many batteries have to be connected together in parallel and or in   series. Here are 3 examples of connection:   2.3.1 Connection in parallel   2.3.2 Serial connection   2.3.3 Serial and parallel connection   HP-COMPACT V5.4   9/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   3 Mounting and installing   3.1 Installation place   The location of the HP-COMPACT must be driven by the following criteria:   − Protection from unauthorized handling   − Dry dust free room, no condensation   − Never install directly over the battery and never in a cabinet together with the   batteries   − Keep ventilation holes free   − In mobile installations it is important to keep the vibrations down as low as   possible   3.2 Fixing   Basically the HP-COMPACT can be installed in any desired location but only   vertically. First of all the plate supplied along with the HP-COMPACT must be   screwed firmly (due to the weight of the device) on the wall. Then the HP-COMPACT   is hooked on the plate and screwed underneath.   Cautious: the fixing must be fully made otherwise the HP-COMPACT may fall   and cause important damages.   In motor vehicles HP-COMPACT must be fixed on vibrations reducing elements. The   HP-COMPACT must not be fixed on a combustible base, as the back of the casing   can get hot and reach up to 60 degrees Celsius.   3.3 Connections   3.3.1 General instructions on connecting   − The cable connection on the terminals AC INPUT and AC OUTPUT must be   carried out with a screwdriver Nr.3 and the connection of the AUX RELAY   terminal with a screwdriver Nr.2.   − The conductor cross section on the terminals AC INPUT / AC OUTPUT / must   comply with the local rules.   − All connecting cables and also the battery cables must be fixed with strain relief   clamps.   − The fuses supplied with the HPC 4400-24, 6000-48 and 8000-48 have to be   installed (see description in 3.4). The cable cross section for the HP 2800-12,   4400-24, 6000-48 and 8000-48 is resp. 95, 70, 50 and 70 mm2 and their length   must be as short as possible (max. 2m).   − The fuse supplied with the product (save for HPC 2800-12) does not protect the   battery cables.   − To protect the battery cables, a fuse corresponding to the conductor cross   section must be fixed directly on to the battery.   − All cables must be tightly screwed in place. For safety, a yearly control is   recommended. In mobile installations controls must be carried out more often.   − Connecting must be done by qualified people. Material such as cable,   connectors and distribution boxes, fuses etc. used in the installation must   comply with the respective valid low-voltage installation rules and regulations in   force.   3.3.2 Protection cover of the terminals connections   The protection cover must to be closed after any service on the appliance.   3.4 Connection Plan   HP-COMPACT V5.4   10/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   A Battery +/-   Reserved   Connection terminal (M8) for battery cable (HPC 4400-24/6000-   48/8000-48 with fuse)   - B C D E F Remote contr. Connection terminal for Remote Control RCC-01   Transfer delay Slide switch for Transfer Delay   Equalize   Temp.   Slide switch for equalization of the Battery   Connection terminal for Temperature sensor CT-35 and/or   Remote Power Sharing RPS-01   G H J K L Aux. Contact Connection terminal for Auxiliary Contact   AC Input   ID Plate   AC Output   Reserved   Hole   Connection terminal for AC-input   Identification plate with Technical data and Serial number   Connection terminal for AC-output   - Pass through hole for RCC-01, CT-35 and RPS-01   Thermal circuit breaker 30A (50A for HPC 8000-48) for the   Transfer system   M N Protection   3.5 Cabling   Connecting the HP-COMPACT is a very important step of the installation. You must   take care that all connection work is carried out in a clean and correct way and that   under no circumstance a cable is connected to a wrong terminal.   Connecting of the HP-COMPACT must be carried out in the following order. In case   of dismantling this order must be reversed.   3.6 Pre-installation settings   Before you start with the cabling of the HP-COMPACT you must set the type of   battery. In case sealed-gel batteries are used then you must set the small slide-   switch „Equalize“ which is on the front with the connection terminals, in OFF position.   In case of „normal“ lead-acid – batteries, these can handle a higher equalizing   HP-COMPACT V5.4   11/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   charge, the same slide switch can be set in ON position. In case of doubt leave the   setting in OFF position.   This will allow an equalizing cycle (higher end of charge voltage) during the next   charge process. Since then equalizing will occur every 25 usual cycles.   3.6.1 Connection to battery   3.6.1.1 On the appliance side   Mount the supplied glands on the battery cable before the setting of the cable   terminal. Set the cable terminal and mount the glands on the appliance. Repeat the   process for the second battery cable.   Connect   the   red   cable (+) on the “+   Battery”   connection   appliance   point   according to the plan   below.   Connect the black   cable (-) on the “-   Battery”   connection   appliance   point   according to the plan   above.   The supplied fuse   (except with the HPC   2800-12) must be   mounted according to   the plan below.   3.6.1.2 On the battery side   Caution: before connecting the battery, check carefully the voltage and the   battery polarity with a voltmeter. A polarity reverse will seriously damage the   inverter (for example: connecting a HPC 2800-12 to a 48V-Battery).   Get the batteries ready for connection: suitable terminals, fuse on one of the   connection points, cable in good shape with, if necessary, terminals rightly set. Mount   the red cable on the positive (+) pole, and the black cable on the negative (-) pole of   the battery.   While connecting the second cable, a spark due to the charge of the capacities at the   input stage is normal. In the same time an acoustic signal tells that the control   processor has started. All LED’s of the synoptic light during a short time, then the   synoptic shows that the appliance has stopped. The LED “OFF” (13) must be turned   on.   After the battery connection, the battery state-of-charge LED shows a 100% capacity   during 1 to 2 minutes, the necessary time for the processor to compute again the   current state-of-charge of the battery.   If the LED “Battery Low/High” (12) is lighting, the battery voltage is too low. If it is   blinking, the battery voltage is too high. Caution: a battery voltage too high or   inappropriate can seriously damage the HP-COMPACT. For instance the connection   of a 24 V battery with the HP-COMPACT 2800-12.   If by mistake the HP-COMPACT has been wrongly been connected (reverse battery   polarity) it is likely that the internal protection fuse has melted and has to be replaced.   In that case it is necessary to disconnect all connections to the HP-COMPACT,   HP-COMPACT V5.4   12/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   including the battery. If after the fuse replacement and after re-connection of the   battery with the right polarity, the HP-COMPACT remains out of order, it must be   brought back to your merchant for service.   3.6.2 Connection to the 230Vac-consumer appliances (AC OUTPUT)   The 230V consumer appliances must be connected to the terminals AC OUTPUT   with cables which cross section has to follow the local rules in force (usually   2.5mm2). Connections are marked as follows “N“ Neutral, “PE“ Earth (connected to   the appliance box), “L“ Live.   Caution: High voltages can be there. Make sure that the HP-COMPACT is   turned off (LED 13 lighting) before the connection.   3.6.3 Connection to the 230Vac Input (AC INPUT)   The 230V-supply from network or from a generator must be connected to the input   terminals AC INPUT with cables which cross section depends on the power source   (usually 2.5mm2). Connections are marked as follows: “N“ Neutral, “PE“ Earth, “L“   Live (connected to the appliance case).   3.6.4 Connection to Auxiliary Contact   This contact is a potential free change over contact the currents and voltages allowed   for this contact are max. 16A/250Vac. The LED 5 “Contact active” shows the position   of them: alight mind active and off mind non-active. The schematic view of the   connections on the front, show the relay in the non-active mode.   3.6.5 Connection to Remote control   The Remote Control RCC-01 is connected in the terminal marked „Remote control“   with a 20m long cable and a RJ11/8 connector. The Remote Control can be plugged   IN or plugged OUT during any operation situation. Push in the connector softly until   you hear the „click“ showing that the connector is locked. The same applies to the   plug in the Remote Control.   The length of the cable for Remote Control should not exceed 40m. We deliver it with   20m cable.   3.6.6 Connection to Temperature Sensor (Temp.)   The temperature sensor CT-35 is connected in the terminal marked „Temp“ with a   3m long cable and a RJ11/6 connector. The temperature sensor can be plugged IN   or plugged OUT during any operating situation. Push in the connector softly until you   hear the „click“ showing that the connector is locked. The temperature sensor must   be glued to the wall of the battery or near it. The Temperature Sensor cable must   not be tied together with the battery cables or laid in a rope/bundle.   3.6.7 Connection to the Remote Control for the „Power Sharing“ (RPS-01)   This remote control is connected with a 20m long cable and a RJ11/6 connector in   the connection terminal „F“ (Temp. sensor). It can be connected and disconnected at   any time. Push in the connector softly until you hear the „click“ showing that the   connector is locked. In case the remote control is connected together with the Temp.   sensor, a short cable with a Y-connector will be connected in the terminal „F“ (can be   supply as an option).   HP-COMPACT V5.4   13/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   4 Control   4.1 Display and control parameters   HP-COMPACT V5.4   14/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   4.2 Light Emitting Diodes (LED)   LED   Marking   LED lit   LED blinks   Voltage   corresponding to   self-adjusted   A voltage outside the self-adjusted   values is at the AC IN input, or the   HP-COMPACT is in synchronization   1 AC IN   values is at the AC phases   IN input.   Battery charger is   working   The battery charger is locked OFF   (see chap. 4.6) or provisory out of   order. In that last case it will restart   within 10 seconds   2 CHARGER   3 4 Reserved   Program   Program mode for   Aux. Contact   Contact   active   Contact   manual   Auxiliary Contact is   activated   Aux. Cont.   5 6 manually activated   Transfer system is Transfer (bypass) is disabled (see   active. In- coming   chap. 4.7)   7 TRANSFER voltage is being   sent directly to AC   OUT outlet   There is a voltage   The Inverter is in Standby-Mode   8 9 AC OUT   at the AC OUT   outlet   INVERTER Inverter is working Forced Inverter Mode (see chap. 4.5)   For the time being   the HP-COMPACT   Over Temp. is out of service   because of   10   11   overheating.   The HP-   COMPACT is out   Overload   of service because   of overload or   short-circuit   Batt.   Low/High   Battery voltage is   too low   HP-COMPACT is   Battery voltage is or was to high   12   13   HP-COMPACT is for the time being   turned off. Turning turned off. Turning it back on will   OFF   it back on is only   possible manually.   Battery equalizing   is set   follow automatically !   14   EQUALIZE   State of charge of   the battery   LED 15 – Absorption time is running   15–18   HP-COMPACT V5.4   15/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   Display the value of the output power in % of Pnom (in   POWER   25   Inverter Mode) and the charge current in Amps (in Charger   Mode). In this mode the red LED indicates that power   sharing is in use (>100A).   MONITOR   4.3 Push buttons   Turning the HP-COMPACT on and off (Help Button for   Programming)   Alarm Signal off (Help Button for Programming)   19   ON/OFF   RESET   20   21   Aux. Contact Control Aux. contact (Help Button for Programming)   4.4 Turning Knobs   22   23   24   26   CHARGER Adjustment for max. Charging Current   Adjustment for Transfer Voltage Threshold (TRANSFER –   INVERTER)   TRANSFER   STANDBY Adjustment for „Standby“ system   Must be adjusted to the maximal available current of your   INPUT LIMIT   AC INPUT supply   4.5 The Inverter   An Inverter is built in the HP-COMPACT, which generates a sinusoidal alternating   voltage of a very high quality. With this Inverter any 230Vac alternating voltage   appliance up to the nominal power of your HP-COMPACT can be operated. Thanks   to the generous dimensioning of the HP-COMPACT, you can operate appliances   requiring higher power than the nominal power of the HP-COMPACT for a short time.   The HP-COMPACT provides up to 3-times the nominal power to start motors.   The Inverter mode is displayed through LED 9 (Inverter). If the Inverter Mode is   disabled (see chap. 5.5) LED 9 will blink. If the LED 9 is lit, the Inverter is in operation   and you have 230Vac at the output AC OUT. The actual power of the connected   appliance is displayed on the power monitor 25 and on the Remote Control.   4.5.1 Charge detection system „Standby“   In order to avoid unnecessary discharge of the battery, the inverter switches OFF   automatically if no appliance is connected and switches ON automatically again if   appliance is connected. The LED 8 blinks if the inverter is in Standby-Mode. The   switching-on/starting level can be adjusted with the turning knob 24 „STANDBY”.   Adjusting the switching-on level is as follows: Switch off all consuming devices, turn   the Turning Knob 24 to the right until the LED 8 is blinking, switch on the smallest   consuming device (i.e. Mobile phone charger), turn the Turning Knob slowly to the   left until LED 8 is lit.   If the Standby-Mode is not wanted, turn the Turning Knob 24 to the left, to the OFF   position.   4.5.2 Overload   If the Inverter is too long or too heavily overloaded, it switches off. The LED 11   „Overload“ is lit and LED 13 „OFF“ blinks. After ca. 10 seconds the Inverter switches   on automatically. If the Inverter is overloaded four times one after another in a short   HP-COMPACT V5.4   16/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   time, then it no longer switches on automatically. The LED 13 remains lit. Press the   push button 19 „ON/OFF“ in order to switch on the Inverter.   4.5.3 Overheating (Over Temp.)   If the Inverter has been overloaded for a long time or it has been working in too high   surrounding temperatures, it will switch off. The LED 10 „Over Temp.“ is lit and the   LED 13 „OFF“ blinks. After cooling down, the inverter switches back on automatically.   One minute before the inverter switches off for too high temperature it gives out an   acoustic alarm signal. If the Auxiliary Contact has been programmed to detect the   high temperature then it synchronizes the relay with the alarm signal. In this way, for   example, an emergency back- up system can be started without any break in the   energy supply.   4.5.4 Battery Condition   Deep discharge of the lead-acid batteries leads to high losses in capacity and early   aging. That is why the battery condition is continuously controlled and supervised.   With low volt-age the inverter switches off. The LED 12 „L/H Batt.“ is lit and the LED   13 „OFF“ blinks. When the battery voltage gets up to 12.1V / 24.2V / 48.4V, the   Inverter switches on automatically. One minute before the Inverter switches off due to   low voltage it gives out an acoustic alarm signal. If the Auxiliary Contact has been   programmed to detect the low voltage then it synchronizes the Aux. Contact with the   alarm signal. In this way, for example, an emergency back up system can be started   without any break in the energy supply.   The low voltage is set to 11.6V / 23.2V / 46.4V. These settings are standard for most   batteries. These voltage levels are maintained by the built-in Battery-Management-   System of the HP-COMPACT by matching the load and the battery condition.   This setting is comparable with the levels of 10.8V/ 21.6V / 43.2 which are given   for most batteries at nominal load.   All voltage levels can be programmed. See the instructions under the section on   Programming. Check with your battery supplier which voltage values should be set.   HP-COMPACT V5.4   17/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   4.6 The battery charger   4.6.1 Cycle of charge   The full automatic HP-COMPACT Battery Charger is adjusted at the factory so that   most lead-acid and lead-gel batteries can be charged to the maximum. As soon as   the minimum alternating voltage for the AC IN set on the Turning Knob 23 is available   at the input (LED 1 AC IN is lit), the Battery Charger is switched on automatically   (LED 2 CHARGER is lit). The battery is fully automatically charged matching to the   charge level, the adjusted volt-age levels and the charge current. Thanks to the built-   in Float Charge System, the batteries can be left connected for unlimited time with   the Battery Charger switched on.   During the charging phase the appliances at the outlet AC OUT are continually   supplied with power (LED 8 AC OUT is lit).   The charger functions are shown in the following diagram:   4.6.2 Default values for battery voltage thresholds   Absorption   time   Equalization   Low voltage   Float charge   Absorption   Equalization   time   12V 24V 48V 12V 24V 48V 12V 24V 48V 12V 24V 48V   12/24/48V   12/24/48V   11.6 23.2 46.4 13.5 27.0 54.0 14.4 28.8 57.6 15.6 31.2 62.4   2h   20’   These values can be modified by mean of the optional remote control   4.6.3 Equalization charging   Before you program the HP-COMPACT for Equalization-charge you must check with   your supplier that the batteries are suitable for this process.   Equalization is recommended for the lead-acid batteries in order to mix well the   electrolyte fluid and to clean the lead plates.   If the HP-COMPACT is operating with a lead-acid battery, which is suitable for   equalization, the slide switch „Equalize“ which is on the cable connection side, must   be placed in the ON position. In this setting, every 25 charge cycles an equalization is   HP-COMPACT V5.4   18/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   carried out for 20 minutes (factory setting). During such a charge cycle the LED 14 is   lit and during equalizing it is blinking. Charge cycle with equalization can be started   independently from the actual program. For this purpose the slide switch must be slid   from “OFF” to the “ON” position. The LED 14 will light up. If the periodic equalization   is not required, slide switch must be slid back to the „OFF“ position after the   completion of the manual cycle.   The equalizing voltage can be changed. How to proceed is explained in chap. 5.3.   Batteries not designed for equalize should never been charged this way.   CAUTION: During the equalization process, the batteries produce a lot more   gas. DANGER OF AN EXPLOSION !! The battery room must be well ventilated.   Equalization mode should never be used when using Gel-Batteries.   4.6.4 Input current repartition (Power sharing)   To manage the power available on the AC INPUT (depends on the supply use) the   HP-COMPACT is equipped with a system usually called “Power sharing” or INPUT   power distribution. With this function it is possible to limit the AC INPUT current   assigned to the charger. The more current it uses on the OUTPUT the less it gives to   the charger. Priority to the OUTPUT. When the power sharing is used the LED 200%   (red) is lit to point out that the charge is limited.   Caution: if the power use on the OUTPUT is higher than the value of the INPUT   LIMIT (26) the HP-COMPACT cannot limit the current, then the generator means   to stop or the circuit breaker means to break before.   4.6.5 Set the INPUT LIMIT (26)   The current available for the HP-COMPACT   depends on the supply used from a motor   generator, the network of a camping or of a shore   connection. The value of the turning knobs INPUT   LIMIT (26) must be adjusted lower or equal to the   current available from the source.   For example if you have a generator of 2kW you   must adjust the turning knobs 26 to a max. 8.5A. To   calculate this, one divides the nominal power   (2000W) by the voltage (230V). If you have a circuit   breaker (i.e. 6A) before the HP-COMPACT, then   you set this value on the turning knobs (26) (i.e. 6A).   This adjustment can be done remotely with the optional RPS-01 (see section 3.6.7).   In that case the smallest values will be taken into account.   4.6.6 Charging current   The maximum charging current for the battery can be adjusted with the Turning Knob   22 (CHARGER). The charging current of the battery should be set to approximately   10 – 20% of the battery capacity (at C10). This means that the charging current for a   battery with 300Ah should be set between 30 – 60A.   The charging current is displayed on POWER MONITOR (25) of the front panel   or on the Remote Control.   4.6.7 Battery Condition   Built-in microprocessor with a specially developed algorithm calculates the actual   state of charge of the battery and displays it on LED 15 – 18. The LED 14 is lit when   the system is carrying out a charge cycle with equalization.   Notice: the exact measure of the battery state of charge with electrical parameters is   al-most impossible. The display of the state of charge is always more or less precise.   HP-COMPACT V5.4   19/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   The measure system built in the HP-COMPACT takes into account the battery   voltage, the discharge and charge current as well as the undulation of the voltage. If   the battery and the HP-COMPACT are used according to their technical data, the   battery state of charge is displayed accurately. In the following cases of use the   display can diverge:   − Battery charge or discharge with too high   currents   − Battery cable cross section too small   − Battery connections badly tightened or corroded   − Charge of the battery with external battery   charger   − Discharge of the battery with users not   connected to the HP-COMPACT   − Work with defective or sulphated batteries   This means that the display can, within few minutes   during the charge, commute from 25% to 75% or   during the discharge, to the opposite direction.   As many of the working cases mentioned above often occur, the measure system of   the HP-COMPACT takes into account, during the charge, only the peaks of the   voltage undulation. As a consequence, the battery voltage at the start of the   absorption stage, measured by a voltmeter will appear deeper. By decrease of the   charge current the voltage will reach the exact values.   For safety reasons, you must get the recommended charge voltage and charge   currents from your battery supplier. The voltage levels and charge characteristics can   be changed through Programming. The instruction for programming of battery   charger is in the section „Programming“ (Chap. 5.3). The correct charging is   mandatory for a safe function and a long-life of the battery.   The battery charger are described by the graphic in chap. 4.6.1.   4.7 The Transfer system   When an AC voltage is at the input AC IN of the HP-COMPACT, the LED 1 AC IN is   lit. When this voltage matches the lowest adjusted value set by the Turning Knob 23   TRANSFER, and the frequency is between 44Hz and 65Hz, this voltage is switched   directly to the battery charger and to the output AC OUT. The LED 7 TRANSFER is   lit. The inverter is switched off and the battery charger switched on. This process is   automatic, unless the charger mode or the transfer mode is disabled (see Chap. 5.5).   The maximum current of the Transfer switch is 30A (50A for HPC-8000-48). That   means through this system, appliances up to a maximum of al 6900 Watt at 230V   (11500W for HPC 8000-48) can be operated. When the Battery Charger is working,   part of this power is used for charging according to the power sharing system.   The Transfer system is protected against overload with a circuit breaker on the AC   Input side of the HP-COMPACT. If the system has been overloaded, the button/pin of   the fuse will pop out. To put the automatic safety system back in to operating you   must push this pin back.   Note: in the Inverter operation, The HP-COMPACT generates a true sinusoidal and   quartz stabilized output voltage. However if the HP-COMPACT is supplied from a grid   or a generator and the transfer contact is active, then you have at the output AC OUT   the same voltage as that at the input. This voltage can not be modified by the HP-   COMPACT !   HP-COMPACT V5.4   20/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   4.7.1 Set the transfer voltage threshold   The voltage threshold of the transfer can be adjusted between 150 to 230V with the   turning knobs (23). From factory this value is 200V. Most appliances can work on this   voltage. When the Input voltages reach the selected value on turning knob, the   inverter switches off and the AC INPUT goes directly on the AC OUTPUT. When the   voltage INPUT is less of 20V the value set, the transfer is stopped and the OUTPUT   switches back on the inverter.   Note : Don’t use the turning knobs “TRANSFER” (23) to adjust the AC OUTPUT   voltage ! This is only it’s only a voltage threshold level to enable or disable the   transfer.   4.7.2 FAST (UPS)- MODE for the Transfer Switch   The quick and break free Transfer mode is programmed with a slide switch „Transfer   De-lay“ OFF, which is on the front side (cable connections side).   The aim of the HP-COMPACT is to supply the appliance with a break-free alternating   volt-age. When the incoming voltage AC IN no longer matches values which have   been set with the Turning Knob 23, the inverter switches on at once. The transfer is   carried out in 0.02 seconds. This quick transfer ensures a break-free function for   most appliances. If you have an alternating voltage back at the input AC IN, transfer   system starts up again with-out any break, and the inverter is stopped.   4.7.3 Delayed mode of the Transfer System   The delayed mode of the transfer system „Transfer Delay ON“ is programmed with   the slide switch on front with the cable connections. The HP-COMPACT provides a   break-free alternating voltage for the appliance. A quick transfer switch is not always   sensitive nor is it always desired. For example, when the appliances are operated by   a small back-up generator. An overload of a short period on such a generator, i.e.   start of a vacuum cleaner etc., has the effect of decreasing the voltage for a short   time. As in such cases the transfer to the Inverter is not desired, the transfer system   can be programmed with a delay. When the slide switch (Transfer delay) is in the   „On“ position, the transfer to the inverter takes place with a delay of 5 seconds. If the   voltage falls below 100Vac, the transfer takes place without delay ! The transfer   switching to the Inverter takes place without any break.   4.8 The Multifunctional Contact   In the HP-COMPACT there is a built-in programmable power relay. The potential-free   change-over contact (NO – NC) of this power relay is connected to the screw   terminal AUX CONTACT.   Maximum Contact load: 230Vac / 12Vdc / 24Vdc / 16A !   > 36Vdc / 3A !   With the Push Button 21 „AUXILIARY CONTACT“ the contact can be manually   switched on or off independently from programming and from the operating situation.   The LED 5 “Contact active” shows the status of the contact. The drawing up the   screw terminal “AUX CONTACT” is the inactive position mode, LED 5 “Contact   active” off.   The switching on and off of this contact can be freely programmed for every   operating situation of the HP-COMPACT witch situation is indicated with a LED.   There is no limitation to its application and it is left to your wishes as to where and   how you would like to use it. The example and the setting of this contact are   explained in chapter 5.4.   In factory we program this for a dysfunction alarm. The contact is active when one of   these situations is detected:   HP-COMPACT V5.4   21/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   − Over temperature (LED 10 lit)   − Overload (LED 11 lit)   − Over or less voltage of batteries (LED 12 lit or blinking)   − HP-COMPACT is turned off manually or with a fault (LED 13 lit)   In case this function is not wished, it must be modified by programming according to   procedure in chap. 5.4.   4.9 The Remote Control RCC-01   As an option, a Remote Control   can be connected to the HP-   COMPACT.   All   operating   controls and displays except   from level adjustment are   available on the Remote   Control. The Remote Control is   supplied with a 20m long cable.   It can as long as 40m. The   Remote Control is suitable for   surface mounting on the wall or   on to a switch board. It is fixed   with   COMPACT   4 screws. The HP-   can also be   programmed with the Remote   Control. The Programming is   described   in   the   section   „Programming“.   The output power and the charging currents are displayed on the Remote Control.   In the Remote Control there is an additional Alarm Contact and a built-in Control   Input. These two functions are available through Tip-jack RJ11/4 for use. This   Auxiliary Contact is Front / Work Contact (max. 0.5A!), which is independent from the   Auxiliary Contact of the HP-   COMPACT. This contact is   active in case of an alarm of the   HP-COMPACT.   The Control Input is connected   in parallel to the ON/OFF- push   button. The HP-COMPACT can   be switched on or off through   this input with an impulse button   or an impulse contact.   Caution: No external voltage   should be connected to this   Input Control.   Order Number for Remote Control: RCC-01   Dimensions: H x B x T / 111.5 x 136.5 x 25mm   4.10 The Temperature sensor CT-35   Operating voltage of lead-acid batteries change depends on the   temperature. To correct the operating voltages according to the   HP-COMPACT V5.4   22/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   actual temperatures, a temperature sensor can be connected to the HP-COMPACT.   The compensation through the sensor is –3mV/°C/Cell.   Order Number: CT-35   Dimensions: H x B x T / 58 x 51.5 x 22mm   4.11 Remote control for „Power Sharing“ RPS-01   If the Remote control RPS-01 is installed, the Trimmer   (26) “INPUT LIMIT“ has to be set on the value max..   The HP-COMPACT takes into account the lowest   values set on the inverter and on the Remote control.   The current available at the HP-COMPACT input will be   determined by the power of the connected source   (generator, grid etc...). The potentiometer on the RPS-   01 must be adjusted lower or equal to max. value of the   power source.   For instance if the source is a generator of 2000 Watt, the potentiometer has to be   set at max. 8A. This value is obtained in dividing 2000 Watt by 230V. If the HP-   COMPACT is connected to a power source which is protected by a 6A circuit   breaker, the potentiometer must be set at a max. value of 6A.   Caution: the HP-COMPACT will not limit if an appliance draws more current   than available from the source ! This means that the connected generator will   be over-loaded or that the circuit-breaker before the HP-COMPACT will break.   5 Programming   The HP-COMPACT (except for 60Hz versions) is equipped with a Flash   processor fitted out with EEPROM Memory, which means that even when it is   disconnected from the battery, the parameters that were programmed for the   application remain after a new connection to the battery.   It is possible to reinitialize (RESET) the HP-COMPACT by pressing   simultaneously on the three push buttons 19/20/21 during at least 2 seconds. A   beep will confirm the RESET. The inverter switches off after this operation. It   can be turned on again after the beep. The programmed parameters will   remain.   5.1 Standard setting   The HP-COMPACT is delivered with the following default settings:   Auxiliary contact: active in case of defect or manual turn off with the LED 10/11/12/13   Battery voltage :   Low voltage   Float Charge   11.6V / 23.2V / 46.4V   13.5V / 27.0V / 54.0V   End of Charge Voltage 14.4V / 28.8V / 57.6V   Equalization   15.6V / 31.2V / 62.4V   2 Hours   Absorption Time :   Equalizing Time :   20 Minutes   HP-COMPACT V5.4   23/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   5.2 Reset value (default settings)   To come back to the default settings, press simultaneously on the push buttons   20/21 during at least 2 seconds. A beep will confirm the comeback to the factory   settings. The inverter switches off after this operation. It can be turned on again after   the beep.   5.3 Battery voltages and absorption time   5.3.1 Set the voltage and timing threshold   The programming is done in accordance with the following steps:   Push and hold down, the Push Button 21 (Program) and the Push Button 19 (Change   status) for minimum 2 seconds simultaneously.   With the Push Button 20 (select) select which of the battery level and of the   absorption time have to be changed.   These four red LED’s show the function set:   Low voltage   LED 13 (ON/OFF)   Float charge   Absorption (End of charge)   Equalization   LED 12 (Batt. Low/high)   LED 11 (Overload)   LED 10 (Overtemp.)   LED 10/11/12/13 (altogether)   Absorption Time   With the Push Button 19 (Change status) set the desired parameter (voltage or time)   to modify (LED 14/ 15/16/17/18). Push Button 19 (Change status) to set the desired   value according to the table 5.3.2.   If desired, repeat the operation with   any other parameter (voltage or   time) to be changed.   If during 30 seconds no buttons are   pressed, the selected values are   automatically stored and the HP-   COMPACT switches back in to the   normal operating status.   The voltage levels and times   changed through programming are   only first active with the next   charge cycle!   The voltage level which is not suitable can greatly reduce the battery life or   could even destroy it ! Therefore check beforehand with your battery supplier.   HP-COMPACT V5.4   24/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   5.3.2 Table of voltage and timing threshold   The voltage levels (low voltage, float charge, end of charge and equalization) and the   du-ration of the absorption charge can be changed.   The display of these voltages and the times in the program mode are in accordance   with the diagram shown below:   Equali-   zation   time   Absorption   Low voltage   Float charge   LED 12   Absorption   Equalization   time   LED   10/11/12/13   12/24/48   4h   LED 13   24   LED 11   24   LED 10   24   LED 10/11   12   48   12   24   48   12   48   12   48   12/24/48   3h   14 12.0   15 11.8   16 11.6   17 11.4   18 11.2   24.0   23.6   23.2   22.8   22.4   48.0   47.2   46.4   45.6   44.8   13.7   13.6   13.5   13.4   13.3   27.4   27.2   27.0   26.8   26.6   54.8   54.4   54.0   53.6   53.2   16.2   15.6   15   32.4   31.2   30   64.8   62.4   60   16.2   15.9   15.6   15.3   15   32.4   31.8   31.2   30.6   30   64.8   63.6   62.4   61.2   60   3h   2h   1h   0 – 1’   2h   1h   40’   20’   14.4   14.2   28.8   28.4   57.6   56.8   The heavy printed values show the standard settings.   5.4 Auxiliary contact   5.4.1 Principle   The Auxiliary Contact can be basically programmed for any operating situation of the   HP-COMPACT which is indicated with a LED. The programming is possible for one   or more operating situations. If the contact is programmed for many situations, it is   activated as soon as the HP-COMPACT finds itself in any one of the programmed   situations. That means that the work of the contact meets that of the logic OR–   Function.   5.4.2 The programming of the Auxiliary Contact   The programming of the Auxiliary Contact is carried out in the following Steps:   − The Push Button 21 (Program) presses down for min. 2 seconds. The LED 4   „Program“ is lit as an indication, that the HP-COMPACT is in program mode.   − A blinking LED shows the programmed condition for the auxiliary contact (LED   10/11/ 12/13 factory setting).   − With the Push Button 20 (select), select the desired condition in which the   contact should be activated.   − With the Push Button 19 (Change status) confirm or change the status for this   condition. If desired, with the Push Button 20 (select) select another condition in   which the contact should be activated.   − With the Push Button 19 (Change status) confirm or change the status for this   condition. If during 30 seconds no buttons are pushed, then the settled values   are automatically stored and the HP-COMPACT switches back to normal   operating condition.   5.4.3 Auxiliary Contact as generator starter   As per the battery capacity   When in the programming of the Auxiliary Contact, the Battery Capacity (LED 15-18)   is used as a condition, you must then take note of the following requirements.   If you have to start an emergency back-up supply with a battery having a certain   residual capacity, then two battery levels must be programmed. The first (i.e. Battery   25% LED 17) for the starting or activating the Auxiliary Contact and the second (i.e.   Battery 100% LED15) for stopping or disabling the Auxiliary Contact. Programmed   HP-COMPACT V5.4   25/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   like this the Auxiliary Contact works with the lowest set condition and stops when it   has reached the highest programmed condition through charging.   Example: start of a generator with the HP-COMPACT   In order to program the auxiliary contact to start at 25% and to stop at 75% of the   battery state-of-charge, here is the procedure to follow:   − Press the key AUX. CONTACT (Program) 21 during at least 2 seconds. Then   the states will be displayed blinking (factory settings LED’s 10/11/12/13). As   these states are not wished for the start of the generator, they must be disabled.   − With the key (select) 20, select the LED’s to disable (the active LED’s are   blinking) and disable them with the key 19 Change Status. Select the other   LED’s to switch off with the key (select) 20 and switch them off with the key 19   Change Status until all are disabled.   − Then select the LED 17 with the key (select) 20 and activate the contact with the   key 19 Change Status. The generator will start once the LED 17 switches of.   − Then select the LED 16 with the key (select) 20 and activate the contact with the   key 19 Change Status. The generator will stop once the LED 16 switches on.   − If no key is activated during 30 seconds, the normal operation states are   displayed automatically again.   For a control the key Program can be pressed at least 2 seconds. The values set are   displayed blinking.   As per the inverter output power (not available with some special executions)   Activating the auxiliary contact for the generator start can be programmed also on a   pre-determined output power of the inverter. The auxiliary contact will be activated if   the inverter output power exceeds 80% of the inverter nominal power during 3   minutes and/or 100% during 30 seconds.   The auxiliary contact will remain activated 30 minutes after the input current has   come back to a value lower than the one adjusted by the “INPUT LIMIT” (chap.   4.6.4). In other words, the contact will be deactivated 30 minutes after the lighting out   of the LED 200%.   This programming is achieved accordingly to chap. 5.4.2 of the user manual and by   activating the contact on LED 100% of “Power Monitor” (25).   5.4.4 Power cut of the second priority loads   The auxiliary contact can also be used to cut the power of less priority loads when   the battery state of charge is lower than a given threshold. In that case, only one of   the battery state of charge, or the “transfer” function will be programmed as power cut   criteria.   The second priority loads will be supplied only when the generator is ON or when the   battery has a sufficient threshold.   5.4.5 Manual operating of Auxiliary Contact   The Auxiliary Contact can be operated at any time with the Push Button 21 (AUX.   CONTACT). The LED 6 „Contact manual“ lights up as information that the Contact is   manually operated, and LED 5 „Contact active“ lights up when the Contact is active.   By pushing the Push Button 21 a second time, the Contact is disabled. By pushing it   the third time, automatic functions are restored.   HP-COMPACT V5.4   26/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   5.5 Disabling some of the HP-COMPACT functions   Each different function charger, inverter and transfer can be disabled. This is useful   for specific applications witch required to disable some of these three functions.   If you press the buttons 19 and 20 more than 2 seconds you can have access to the   different possibilities shown in the following diagram.   In programming mode the display shows only the different types of program with the   three LED’s 2, 7 and 9 to each function. To change the type of programming, press   shortly the button 20 until you reach the right function used according to the table   below. After 10 seconds the HP-COMPACT exits the programming mode and loads   the new change.   In user mode, the disabled functions are displayed by blinking LED. So you can see   which mode is disabled.   5.5.1 Diagram of the different modes   Shows an off LED   Shows a blinking LED   Shows a lighted LED   All the functions are enabled. This is the   factory setting.   The inverter is disabled. Only the transfer   switch and the charger will work   normally.   Inverter and charger are both disabled.   Only the transfer switch function is ena-   bled in input voltage and frequency is OK   Charger and transfer switch are disabled   the inverter will work continuously even if   there is a correct AC voltage at the input.   6 Installation Maintenance   Apart from the periodic controls mentioned for the connections, the HP-COMPACT   does need any maintenance. Keep the appliance clean and from time to time, wipe it   clean with a damp cloth.   7 Declaration of CE Compliance   Hereby we state that the products described in this user manual comply with the   following standards:   EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2, Dir.   89/336/EEC, LVD 73/23/EEC, EN 50091-2, EN 60950-1.   CH - 1950 Sion, the 31st of January 2002   STUDER INNOTEC (R. Studer)   HP-COMPACT V5.4   27/80   Download from Www.Somanuals.com. All Manuals Search And Download.   STUDER INNOTEC   HP-COMPACT   8 Technical Data   HP-COMPACT V5.4   28/80   Download from Www.Somanuals.com. All Manuals Search And Download.   |